Date: 25.08.2017 Rav.

ALCOVE DEVELOPERS LLP


A Ref: ADLIP/SRP/Qc/DM-0004

ALEOV
eeding appy Fotore
NEW KOLKATA PROJECT

DESIGN MIX OF M30 (PILE)

Design Stipulation:

Grade of Concrete M

Minimum Compressive Strength of Cube after 28 days 30 N/mmn


(As per Table 5 of 1S 456)
Minimum Cement Content 100Kg/M
Maximum Fly Ash content (%) 35%
Maximum Nominal size of Aggregate 20 MM
Degree of Quality Control Very Good
Type of Exposure Condition Modera
Design Slump 165t 15 MM
(As per I5 456)
Degree of Workability Very H
Type of aggregate Angular Crushed
Method of Placing Direct/Pumping
Test Data :

CEMENT
Brand Name cOROMANDEL
Type of Cement OPC 43 GRADE as per IS 8112
Specific Gravity of Cement 315

ASH
Brand Name MEJIA
Type of Fly Ash Conforms to IS 3812 (PART-1)
Specific Gravity of Fly Ash 220

C.
FINEAGGREGATE
RIVER SAND

Type of Fine Aggregate ROUNDED


Water Absorption (%) 1 20%
Specific Gravity of Fine Aggregate 267

() STONE DUST -

Type of Fine Aggregate ANGULAR


Water Absorption (%) 240%
Specific Gravity of Fine Aggregate 282

D cOARSE AGGREGATE
(0) 20 MM:-
CRUSHED ANGULAR
Type of Coarse Aggregate
Water Absorption (%) 0.74%

Specific Gravity of Coarse Aggregate 2 86

(1) 10 MM:

Ype or Loarse Aggregate CRUSHEO ANGULAR

Water Absorption (%) 086%


Specific Gravity of Coarse Aggregate 1 85

WATER -
.

Bore Weil Water (Ground)


source of Water

Specific Gravity of Water 1 00

pH Value of Water 70

F. ADMIXTURE-

Name of Admixture
BASE Mster Rheobuid 1126 1

Brand Name BAS


Wa'er Reducing Admirtureíos per (5 9103
Tvpe of Admixture
Specitic Gravity of Admixture 25

The mixing ratio of 20 mm CA & 10 mm CA s 45%

The mixing ratio or Naturai S9na & Stone Dust s*

The mixing ratic of Cosrse Aggregate å Fine Agregate s $7 49% 42 52%

Design Mix Calcuiation:

() TARGET MEAN STRENGTH


A ALCOVE DEVELOPERS LLP
ALÇOVE NEW KOLKATA PROJECT Mef ADP/B/K/9m K04

DESIGN MIX OF M, (PILE)


/mm

H/nm

Where,

Target Me4n lrengih of Conetete ruie at


7K days in /mm
Characteristir Cimppresaiva t/ength of (onrete uhe after
74 days euuring parid in ta/n
isk Factof Tatla
as per
30 of P29 1 65 for 9% balirw aut6 from chargcterigtc strangh f ntrete

standard Devialion of Concrete in N/mm' per fatle


as 19 of
*7 5 9 fur "var yt/Mnf dogren f qaity t r

(11) WATER CEMENT RATIO

As per Table-5 of 15 456 2000 for ReinfarCed concrete & "Moderate" exposure condition, Water/cement ratio shall te 9 V9

Based on
experience, We adopt water/cement ratio as

041 O50

Then,
(1) WATER CONTENT

Now, as per Table-2 of iS 10262-2009, for 20 mm Crushed


angular coarse ageregate & 25 50 mm
slump rang",
Maximum free Water content 186 Litre

For 165 15 mm
design slump requirement, as per Table-36 of SP 23, t3% water content incerase
/ decrease with every additional 25 mn slurnp increase/decreae,
Total Water content
186
186 15 0% Litre

2139 Litre

We use BASF Master Rheobulld 1126 18 as a Water Reducing admixture or plasticizer in concrete mix, water will be reduced
19 60% (as per TDS), to 19 55% (as per

Total Water content


213 90 80 40% Lre

171 98
Litre
(IV) CEMENT CONTENT-

As per design, Cement content


1719
043

400

Now, as
per Table-5 of IS:456-2000, for reintorced concrete purpose & "Moderate"
exp0sure condtion, Minimum cement content shall
be =
300 kg/m
400
kg/m 300 kg/m

Then, K.

0, ement Content 400 X8000%


320 g

Fly Ash 20% of Cement content


00 320

80
K

(V DETERMINATION OF COARSE &FINE AGGREGATE CONTENT

As per Table-3 of IS 10262-2009, for waterfcement ratio = 0 5 & 20 mm size


aggregate & Zone-ill type sand is uLed,
Voiume of coarse ageregate wili be
.64

As per design calculafion, wjc ratio is 0 . 4 3

Now, for every 0.05 increase/decrease in water/cement ratio, sand content wil
increase/decrea e :1% 3s per Tabie-35 of P22

So, Corrected volume of coarse aggregate for

water/cement ratio of 043


DESIGN MIX OF M3oPILE)
0.6540
For Pump concrete
purpose, Coarse
be reduced to
aggregate will
5.0%
So. Actual volume of Coarse
aggregate
0.6540
95.0%

0 6213
Volume of Fine
Aggregate
0.6213

0 3787
Theoritical Calculation
Total Voiume
100

vowME OF CEMENT

1000
400 3.15
o 1270

vOLUME OF WATER

1000
171 98 1 00
0 1720

voLUME OF ADMIXTUJRE

1000
4 00
125
0 0032

Volume of All-in aggregate

1 00
O1270 01720 o 0032

O 6978

(V) FINE AGGREGATE CONTENT (NATURAL SANDI

Mass of fine aggregate 000 267 000% 3787% 6978

49392

FINE AGGREGATE CONTENT ISTONE DuST)

Mass of tine aggregate 100


6978

21 57

20 MM COAsE AGGREGATE CONTENT

Mass of 20 mm C Agregate

10 MM COARSE AGGREGATE COWTENT

Mass of 10 mm C. ARETegate 2 .3%

494
Date: 28.08.2017 Rev.-00
A- ALCOVE DEVELOPERS LLP
ALÇOVE
Buitding Mappy Futur
NEW KOLKATA PROJECT Ref: ADLLP/SRP/Qc/DM-0006
DESIGN MIX OF M30 (PILE)
Mix Calculation for Trial Mix:
Cement 400.00 kg/m
Water 171.98 kg/m
Natural Sand (FA) 493.92 kg/m
Stone Dust (FA) 223.57 kg/m
20 mm (CA) 744.00 kg/m
10 mm (CA) 494.27 kg/m
Admixture 4.000 kg/m 1.00% of Cementitious Material
Water/Cement Ratio 0.43
for free
NOTE Aggregate should be used in Saturated Surface Dry condition. If otherwise, when computing
the requirement
of mixing
water, allowance shall be made the
(surface)
moisture contributed by the Fine & Coarse aegregate. On the otherhand, ifthe aggregates are dry, the amount of mixing water should be increasedbyan
amount equal to the moisture likely
to be absorbed by the aggregates. Necessary adjustments are also reguired to be made in mass agregates.
The surface water & %
water absorption of aggregates shall be determined according to 1S:2386 (PART-3)-1963.
PREPARED BY: APPROVED BY:
(QA/QC HEAD)
(QC ENGINEER)
(ALCOVE DEVELOPERS LP)
(ALCOVE DEVELOPERS LLP)