You are on page 1of 4

Jolim Consultant Co2 System

Revision 0

BATTERY CALCULATON FOR MAIN FIRE ALARM CONTROL PANEL

PROJECT : MDIS (Malaysia) Sdn Bhd


Part of Lot PTD 154971, Educity, Mukim Pulai, Daerah Johor Bahru, Johor Darul
Takzim.

BOMBA FILE NO. : JBPM/JH/BKK: 700-2/1/5/36-WPI Date : 14.02.2015

NO. OF ZONE : 2

LOCATION : GUARD HOUSE

A STANDING LOAD Qty Amp/Qty Amp

1 Master Control 1 0.0500 0.0500


2 Fire Brigade Unit 1 0.0050 0.0050
3 Zone Unit 10 0.0060 0.0600
4
5 Smoke Detector 2 0.0001 0.0002
6 Heat Detector 2 0.0001 0.0002
7

Total Standing Load 0.1154

B ALARM LOAD Qty Amp/Qty Amp

1 Master Control 1 0.0650 0.0650


2 Fire Brigade Unit 1 0.0200 0.0200
3 Zone Unit 2 0.0600 0.1200
4 Alarm Bell 1 0.0300 0.0300
5
6 Smoke Detector 2 0.0550 0.1100
7 Heat Detector 2 0.0600 0.1200
8
9 Ventilation Fan Tripping 1 0.1500 0.1500

Total Alarm Load 0.6150

C BATTERY CAPACITY Amp Hours AH

1 Standing Load 0.1154 72 8.3088


2 Alarm Load 0.6150 1 0.6150

Total Ampere-Hours 8.9238

Safety Factor - 20% 10.7086

Minimum Battery Capacity Recommended is 11 AH x 24 V

d:/dwg/2013/jc1300-wentel block b/wentel-bb-ff-cal.xls MFAP/1


Jolim Consultant Co2 System
Revision 0

BATTERY CALCULATON FOR MAIN FIRE ALARM CONTROL PANEL

PROJECT : MDIS (Malaysia) Sdn Bhd


Part of Lot PTD 154971, Educity, Mukim Pulai, Daerah Johor Bahru, Johor Darul
Takzim.

BOMBA FILE NO. : JBPM/JH/BKK: 700-2/1/5/36-WPI Date : 14.02.2015

d:/dwg/2013/jc1300-wentel block b/wentel-bb-ff-cal.xls MFAP/2


Jolim Consultant Co2 System
Revision 0

Johor Bahru, Johor Darul

d:/dwg/2013/jc1300-wentel block b/wentel-bb-ff-cal.xls MFAP/3


Jolim Consultant Co2 System
Revision 0

Johor Bahru, Johor Darul

d:/dwg/2013/jc1300-wentel block b/wentel-bb-ff-cal.xls MFAP/4