Professional Documents
Culture Documents
Energy Use in Hydrocooling Stone Fruit
Energy Use in Hydrocooling Stone Fruit
5'
-eo
differencein cooling times when water flow rates of 7 coolers in use. However, none of the previous work ra&
L/m2-s(0.17 gal/ft2-s) or 10 L/m2-s(0.25gal/ft2-s)are provides a detailed energyanalysisof hydrocoolerswith a >(;
{
used on a singlebin of peaches.Water flow rates are breakdown of the heat inputs to the coolers. f.,
listed in terms of watervolumeper time dividedby the The goals of our study are to 1) verify the hydrocooler
@
area of the water distribution pan. Zahradnik and energy use and the energy efficiency data presented by
Reinhatt(1972)showthat thereis onlya20Yoincreasein others, 2) determine the source and magnitude of heat
the effectiveheat transfer coefficient when water flow input to typical hydrocoolers, and 3) suggest possible
rates are increasedfrom 5.3 L/mz-s (0.13 gallft2-s)to energy conservationmeasures.
20.7 L/m2-s(0.51gallft2-s)for apples.They conclude
that heatflow resistancewithin the fruit limits coolingat PROCEDURE
waterflow ratesabove5.3 L/mz-s(0.13gallft2-s). We accomplish thesegoals by testing two hydrocoolers
Someof the earliestwork on hydrocoolingincludes that each have a refrigeration sourcethat is independent
somedata on energyusecharacteristicsof hydrocoolers. of any other refrigeration loads. Figures I and 2 are
Guillou (1958)indicatesthat 55% of the refrigeration diagrams of the hydrocoolersand Table 1 is a listing of
capacity(ice is usedfor refrigerationin this research)is the design featuresfor each. The product cooled is either
used for cooling product when the cooler operatesin a peachesor plums in pallet bins or a combination of bins
continuousfashion.Intermittent operationcausesonly of each fruit.
23% of the ice to be usedfor coolingfruit. He mentions Energy use and energy efficiency are determined by
poor insulation,openhandlingof iceand inabilityto use measuring total electricity consumption and heat
the coolingcapacityof ice left in the coolerat day'send removed during product cooling. The energy flows used
as reasonsfor poor efficiency.Perryand Perkins(1968) in calculations are shown in Fig. 3. Energy use is
recommendreducingthe volumeof water containedin a expressedin kJ of electricity consumedper kg of product
cooled. The energy efficiency is expressedas an energy
coefficient (EC), and defined as
Article was submittedfor publication in March 1989;reviewedand
approvedfor publicationby the Food and ProcessEngineeringDiv. of
ASAE in July 1989.Presentedas ASAE PaperNo. 86-6556. EC=y " "'t-l
tll
The authors are: J. F. THOMPSON, Extension Agricultural E
Engineer,Universityof California,Davis, and Y. L. CHEN, Professor,
Agricultural Machinery Engineering, National Taiwan University, W is the sensibleheat removedfrom the product and
Taipei, Taiwan, Republicof China. woodenbins, assuminga overall specificheat for the
fruit and binsof 3.8 kJlkg-"C (0.908BTU/lb oF. (Mass
Acknowled8men& This project was partially funded by the
Committeeon the Relationshipof Energyand Agticulture. The authors
wish to thank Jerry Knutson and JoseGoveafor helping with data of bins is about5% of total masscooled.)E is the total
collection. electricalenergy(expressed in kJ) consumedin operating
568 0883-8542/89/0504-0568$03.00
@ 1989AmericanSocietyof AgriculturalEngineers APPLIED ENGINEERINGin AGRICULTURE
Ftg. l-Stde view cchemadc of hydrocooler A, a batch type cooler for pallet blnc.
Q*r.-Qpum=
l ( m . c p .* - * . o * ) o ^ J .l2l
Ev.podh6 ofibw lviar 'gEf
Amrih olllgdra 33,900tC c+efy
cdef
Initial Final
Mass Fruit Fruit Temp. Run Energy/
Cooled Temp, Temp. Drop Time Pump Comp. Total Mass Cooled Energy
Run ID Product (ke) fc) fc) fc) (min)(kwh) (kwh) (kwh) (kJ/kg) Coefficient
Hydrocooler A
L Peach 1 0 , 60 0 t6.6 5.6 11 . 0 91 44 136 21.2 72+ 0 . 55 '
z Peach 10,600 21.7 6.6 1 5. 1 63 30 91 t42 48 7.17
3 Peach 10,600 25.3 6.1 L9.2 81 39 777 t82 62 7.72
Peach 11,600 29.2 6.4 22.8 89 43 1.28 200 OL 1.26
Hydrocooler B
Cool down 65 64 759 255
1 p""Jlptu- zo,+oo;t ;; 1A I
83 59 707 195 794 0.73*
2 Plum 25,600 25.4 8.1 II.J 87 86 268 396 lo 1.08
Plum 25,600 26.0 7.8 L8.2 71. 70 179 284 40 1.63
4 Peach/Plum 16,600 24.7 9.2 15.5 51 50 1.52 227 49 1.10
Cool down 106 +z fJ
( Peach/Plum 35,800 26.0 9.7 IO.J 78 78 269 385 44* 1.61*
Average 16.2 54
DISCUSSION
0 10 20 30 The coolershaveECs of 1.00for A and 1.14for B,
ElapsedTime (min) which are well within the 0.7 to 2.2 range,although
Flg. 6-Recultc of exterlor heat galn tcrt for hydrocooler B.
slightly below the 1.4 averageEC reported in our
('F:oCr,l.E*32) previouswork on hydrocoolers(Thompsonand Chen,
1988).
remaining heat inputs are not associatedwith useful On the basis of the heat input resultsfor the two
wotk and representa significant potential for energy coolerstested,energyusein hydrocoolers canbe reduced
savings. significantlyby reducing exterior heat gain. As an
The rate of exterior heat gain is calculated using example of the potential savings,if cooler A were
equationI2l andthe slopeof the regression linesin Figs.5 insulatedto reduceits exteriorgain by 38%, to the same
and 6. Exterior heatgain is 28% ofthe total heatgain for rate of exteriorheat gainlbin as coolerB, its exterior
cooler A and 26To for cooler B, as shown in Table 5. gain basedon the data in Table 4 would be only 0.95 x
CoolerA has a 40% lowerexteriorheatgainlhour than 106kJ (935 x 103BTU) , reducingtotal heat input by
coolerB. But coolerA has a smallerproduct cooling 11%. We assumethat reducingthe total heatinput by
capacitythan coolerB. If they are comparedon the basis 11% would reducethe total energyuseof the cooler7To
of an equal cooling capacity (maximum number of becauserefrigerationis 65% of total energyuse.
bins/hour) cooler B has the lower rate of external heat The low exteriorheatgain of coolerB is partiallydue
gain. Table 5 showsthat cooler A has an exterior heat to its low external surface area per unit of cooling
gain of 10000kJ/bin (9480BTU/bin) whilecoolerB has capacity.CoolerA cannotbe easilymodifiedto reduce
6 200 kl/bin (5878BTU/bin) , a 38% lower rate of heat external area but it certainlycould be insulatedwith
gainlunit of coolingcapacity.(Noticethat the heat input morethanthe 1.5 cm (0.6in.) of insulationin coolerB.
data in Table 4 do not show this great a difference Exterior heat gain associated with air infiltration may
betweenthe two coolersbecauseambient temperature alsocontributeto the differencein heatgain betweenthe
TABLE 5. Exterior heat gain test of two hydrocoolers two coolers,but we have not measuredair infiltration
apart from the rest of the other sourcesof exteriorheat
Cooler A Cooler B gain, so we can not estimatethe potentialeffectof this.
Reducingsolar heat input by shading an uncovered
Heat gain (kJ/hr) 299 000 499 000
Max. cooling capacity (bin/hr) 30 80
cooleror at least painting it a light color should also
Heat gain per cooling reduceexteriorheatinput, but againwedo not havedata
capacity (kJ/bin) 10 000 6 200 on the magnitudeof the potentialsavings.
Reservoir-air temperature A key concernwith the insulationis that it must be
difference during test (oC) 25 27
able to maintain its insulating ability in a wet
NOTE: To convertkJ to BTU multiply by 0.948 environment.Durable, closed cell foam insulation
oF=oC*I.g+32 materialsappearto be bestchoicefor hydrocoolers. Most