STR-1356-Tech. Spec. App.1 Tests
STR-1356-Tech. Spec. App.1 Tests
Page 1 of 3
THE ISRAEL ELECTRIC CORPORATION LTD
ENGINEERING DIVISION SPEC: STR-1356
SUBSTATION PLANNING SECTOR Appendix № 1
3.4 Test to prove that hydrophobic The transformer passes the test if no
coating prevents the disruptive disruptive discharge occurs during 1 min
discharge under 100% relative under power-frequency voltage of 1.2Um
humidity and 100% relative humidity including dew
condensation on the transformer surface.
The test shall be performed with UV
camera, the transformer passes the test if,
under a/m conditions, corona phenomena
does not occurs.
Page 2 of 3
THE ISRAEL ELECTRIC CORPORATION LTD
ENGINEERING DIVISION SPEC: STR-1356
SUBSTATION PLANNING SECTOR Appendix № 1