Vacuum Circuit Breakers

VCB
Vacuum Circuit Breakers
Vacuum Circuit Breakers

Susol VCB is full line-up new VCB which has the


high interrupting capacity, large current(~50kA,
~4000A), and maximized compatibility with
existing products through the dual phases and
compact sized models.

Contents
External structure 26
Basic features and interrupting operation 28
Standards and certification 31
Types and ordering information 32
Type of circuit breakers 42
Ratings 46
Accessories 59
Control circuit diagrams 93
Dimensions 97
Side-Mount type VCB 247
Technical data 249
Vacuum Circuit Breaker, VCB is installed in the medium voltage distribution
lines to protect life and load equipment. In case of accidents such as over
current, short
shortcircuit
circuitand
andground
groundfault
fault
current,
current,
VCB
VCB
works
works
by interrupting
by interrupting
the
the circuit
circuit through
through
the inner
the inner
Vacuum
Vacuum
Interrupter
Interrupter
whichwhich
is acted
is acted
by signal
by signal
from
fromoutside
the the outside
separate
separate
relay. relay.

LSIS'
LS ELECTRIC'
Super Solution,
Super Solution,
Susol VCB
Susol
responds.
VCB responds.
- customer needs for the breakers with high interrupting capacity and large
current due to the integration
integrationand
andincrease
increaseof
ofthe
theload
loadcapacity.
capacity.
- worldwide
worldwidetrend
trendofof
diversification
diversification
in the
in the
medium
medium
voltage
voltage
distribution
distribution
lines.
- increase
lines. of the reliability for the temperature characteristics of circuit
- increase
breakers.of the reliability for the temperature characteristics of circuit
breakers.
Premium-type products to improve convenience and reliability of medium
Premium-type
voltage switchgear
products
configuration.
to improve convenience and reliability of medium
voltage
- full line-up
switchgear
modeling
configuration.
to the high interrupting capacity and large current.
- main
full line-up
structure
modeling
with high
to the
reliability
high interrupting
application.capacity and large current.
-a
main
variety
structure
of accessories
with high
and
reliability
ability to
application.
maximize.
- a variety of accessories and ability to maximize.
Suitable for use as the main circuit breaker to protect key installations in the
Suitable
places such
for as
usedevice
as theindustry,
main circuit
power
breaker
plants,
tohigh-rise
protect key
buildings,
installations
large ships.
in the
places such as device industry, power plants, high-rise buildings, large
ships.

4
<< Susol VCB Series

▶ Strengthening of the high interrupting capacity and large current


models and full line-up new VCB models to high/middle/low.
Voltage Interrupting current Rated current
7.2kV 8/12.5/20/25/31.5/40/50kA 400/630/1250/2000/3150/4000A
12kV 20/25/31.5/40/50kA 630/1000/1250/2000/2500/3150/4000/5000
17.5kV 20/25/31.5/40/50kA 630/1000/1250/2000/2500/3150/4000A
24kV 12.5/25/31.5/40kA 630/1250/2000/2500/3150A
25.8kV 12.5/16/25/31.5/40kA 630/1250/2000/3150A
36kV 25/31.5/40kA 1250/2000/3150A

▶ Main circuit structure with high reliability.


•Maximizing the durability and reliability of the main circuit contactors
(Stego Tulip contactor).
•Strong structure for the temperature rise (Natural cooling system).

▶ Convenience of switchgear configuration and a variety of


accessories.
•CB compartment structure: Metal isolation structures to prevent the
accident spread and ensure safety. And the convenience of switchgear
building is extended by its module style.
•A variety of accessories: UVT, Locking Magnet, Plug Interlock, Key lock,
Temperature Sensor, MOC, TOC, Earthing S/W.
•Maximizing compatibility with existing products through the dualistic
deployment of phases and compact models.

5
7.2kV (VL-06)
•Rated short-time (for withstand current ): 3sec.
•Rated operating sequence: O-0.3s-CO-15s-CO
•Type test level: M2, E2 (List1), C2
•100% Compatibility
- with existing fixed type breakers
- with existing drawout type breakers
•Various cradle: E, F and G type
•A variety of control power
- DC 24~30V, DC 48~60V, DC 110V, DC 125V, DC 220V
- AC 48V, AC 100~130V, AC 220~250V
•A variety of accessories
- Charge switch, UVT, Secondary trip Coil, Current trip coil,
Position S/W
- Key-lock, Button lock, Button cover, Padlock, UVT, Time
Delay Controller, CTD
•Anti Pumping Device
•TEST/SERVICE Automatic Position Indicator
•Standards and certification
- IEC62271-100 (2012) [M2, C2, E2 (List1)]
- Tested in enclosure
- KERI type tested, V-check (KESCO) certification

Susol VCB Family


Susol VCB series are premium-type products
featuring main structure with high reliability
application and a variety of accessories and
ability to maximize to be suitable for use as the
main circuit breaker to protect key installations
in the places such as device industry, power
plants, high-rise buildings, large ships

Ur Isc Ir
(kV) (kA) (A)
7.2 8 400
12.5 630

Full line-up & Compact


Full line-up new VCB models to the high interrupting
capacity and large current (~ 50kA, ~ 5000A) featuring
maximization of compatibility with existing products
through the dualistic deployment of phases and
compact models
6
< < Susol VCB Series

7.2/12/17.5/24/25.8/36kV (VL-06/12/17/20/25/36) 7.2/12/17.5/24/25.8/36kV (VH-06/12/17/20/25/36)


•Rated short-time (to withstand current ): 3sec. 4sec * •Rated short-time (to withstand current ): 3sec. 4sec *
•Rated operating sequence: O-0.3s-CO-15s-CO •Rated operating sequence: O-0.3s-CO-15s-CO, (O-0.3s-CO-3min-CO **)
•Type test level: M2, E2 (List3), C2 •Type test level: M2, E2 (List3), C2
•Compatibility with existing Pro-MEC breakers •Electrical and mechanical life: 20,000 operations
•Various cradle: E, F, G, Fs, Gs and H type •Various cradle: K, Fs, Gs and H type
•CB Compartment for MCSG available •CB Compartment for MCSG available
•A variety of control power •A variety of control power
- DC 24~30V, DC 48~60V, DC 110V, DC 125V, DC 220V - DC 48V, DC 110V, DC 125V, DC 220V
- AC 48V, AC 100~130V, AC 220~250V - AC 48V, AC 110V, AC 220V
•A variety of accessories •A variety of accessories
- VCB part: Charge switch, UVT, Secondary trip coil, Position switch, - VCB part: UVT, Secondary trip coil, Latch checking switch,
Locking magnet, Plug interlock, Key lock, Button cover, Button Position switch, Locking magnet, Plug interlock, Key lock,
padlock, Padlock (H type Door interlock), MOC Button cover, Button padlock, Padlock (H type Door interlock), MOC
- Cradle part: MOC (Mechanical Operated Cell switch), TOC (Truck - Cradle part: MOC (Mechanical Operated Cell switch), TOC (Truck
Operated Cell switch), Temperature sensor, Earthing switch & Operated Cell switch), Temperature sensor, Earthing switch &
Accessories, Door, Door interlock, Accessories, Door, Door interlock, Door emergency button
Ur Isc Ir
Door emergency button (kV) (kA) (A) - Others: Racking in/out handle, Lifting hook,
- Others: Racking in/out handle, 7.2 20 630 UVT Time delay controller,
1250
UVT Time delay controller, CTD 2000 CTD (Condensor Trip Device), Ur Isc Ir
25 630 (kV) (kA) (A)
(Condensor Trip Device), 1250 Temperature module 31.5 1250
7.2
Temperature module 31.5
2000
630
•Anti Pumping Device 12 2000
3150
•Anti Pumping Device 1250 •Standards and certification 40 1250
2000
•TEST/SERVICE Automatic Position 12 20 630 - IEC62271-100 (2012) [M2, C2, E2 (List3)] 2000
1000 3150
Indicator 1250 - KEMA, KERI type tested, 4000
•Standards and certification 2000 V-check (KESCO) certification 50 1250
2000
25 630
- IEC62271-100 (2012) 1000 Note ) * Please contact us 2500
1250 3150
[M2, C2, E2 (List3)] 2000
** Please refer to ratings
4000
- KEMA, KERI type tested, 31.5 630
1250
17.5 31.5 3150
1250
V-check (KESCO) certification 2000 40 2000
2500
3150
Note ) * Please contact us 17.5 20 630
50 1250
1250
2000 2000
25 630 2500
1250 3150
2000 24 25 2500
31.5 630 25.8 31.5 1250
1250 2000
2000 3150
2500 40 1250
24, 12.5 630 2000
25.8 1250 3150
16 630 36 25 1250
1250 2000
25 630
3150
1250
31.5 1250
2000
2500 2000
36 25 630 3150
1250 40 1250
2000 2000
2500 3150

VCB Cradle type

E type
F type

7
H type
Main circuit structure
with high reliability

Susol

VCB



Breaker

 Insulation rod
 Lower terminal
 Shunt
 Vacuum interrupter
 Upper terminal
 Tulip contactor

Vacuum Interrupter, VI
Fixed
electrode
Fixed
Contacts
seal cup
The vacuum rate within the VI is very special alloy (copper-chromium) and the
high (approximately 5x10-5 Torr) and interior is completely sealed to prevent
Arc shield

Bellows
shield
the spacing between fixed contact and loss of vacuum.
Ceramic movable contact is about 6~20mm, Therefore the wearing of the contacts can
depending on the voltage. be minimized in the event of short-circuit
Bellows
Movable
The contacts are in a structure that arc and the arc energy by overvoltage or
Movable
electrode
seal cup can easily be extinguished and the switching can be reduced effectively.
surfaces of the contacts are made of

8
< < Susol VCB Series

Convenience and
Variety

•Maximizing the durability and reliability


of the main circuit contactors
(Stego Tulip contactor)
•Strong structure for the temperature rise
(Natural cooling system)

9
Stego Tulip
Main circuit structure with high reliability
•Maximizing the durability and reliability of the main circuit contactors (Stego Tulip contactor)
•Strong structure for the temperature rise (Natural cooling system)

Tulip finger

Tulip spring

Main circuit terminal


of the breaker

Plate understar :
Securing freedom of Tulip

Plate star: Supporting Tulip for position maintaing and torsional flow prevention

Structure of Stego Tulip Terminal


•Maintaining the connection between breaker and cradle for the optimum current path through securing freedom of Tulip.
•Increasing the heat dissipation area of the contactors and minimizing aging.

Major supply records


- S Electro-Mechanics, Busan plant: 12kV 40kA 4000A VCB
- P Combined cogeneration power plant: 7.2kV 50kA 4000A VCB
- K Petrochemical, Ulsan plant: 7.2kV 40kA 4000A VCB
- P Steel plant, Gwangyang: 7.2kV 50kA 4000A VCB
- P Steel plant, Pohang: 7.2kV 50kA 4000A VCB
- L Chem, Cheongju plant: 7.2kV 40kA 4000A VCB
- S Electronics, Tangjeong plant: 7.2kV 40kA 4000A VCB

10
< < Susol VCB Series

7.2/12/17.5/24/25.8/36kV...
(VH-06/12/17/20/25/36)

•Drawout / natural cooling system


•Improved temperature
characteristics and ensured high
reliability

VL type Tulip contactor VH type Tulip contactor 36kV Tulip contactor

11
CB Compartment
Convenience in building switchgears
•CB compartment structure: H type cradle
•Metal isolation structure to prevent the accident spread and ensure safety
•Convenience of switchgear building

7.2/12/17.5/24/25.8/36kV 20/25/31.5/40/50kA
•Metal isolation structure to prevent the accident spread and ensure safety
•Convenience of operation by Truck
- Drawable in the closed position of the switchgear door
- Racking-in/out positions indicated mechanically
•Equipped with safety devices and accessories
- Control power connected Interlock
- Earthing S/W and interlock, MOC/TOC (ANSI)
•Convenience in building switchgears
- Module assembly with CB compartment

12
< < Susol VCB Series

LV
Compartment

CB
Compartment

Busbar & Cable


Compartment

Accessories of CB compartment
(H type cradle)
PT
■ MOC (Mechanism Operated Cell S/W)
Compartment
■ TOC (Truck Operated Cell S/W)
■ Shutter Padlock
■ Temperature Sensor
■ Door Emergency ON/OFF Button
■ Earthing switch & Accessories
Key lock for Earthing S/W
Locking Magnet for Earthing S/W
Position S/W for Earthing S/W
■ TM (Temperature Monitoring Unit)

13
Cradles
E, F, G, K and H type... Variety of the Cradles

F type
E type

E type F type
•Economic style cradle with the •Safety shutter has been
basic structure added to the cradle of type E
•No safety shutter and bushing •No bushing
•For MESG •For MESG
•Applies VL type VCB •Applies VL type VCB

E type F type H type

14
< < Susol VCB Series

H type
K type
G type

H type
•Metal isolation structure to prevent the
accident spread and ensure safety
K type •Convenience of operation by Truck
•Premium style cradle with - Drawable in the closed position of
metal safety shutter and the switchgear door
bushings - Racking-in/out positions indicated
•Metal isolated structure: mechanically
To prevent spreading - Control power connected Interlock
G type accident and secure safety •Convenience in building switchgears
•Premium style cradle •More convenient by - Module assembly with CB
with safety shutter and withdrawable Truck compartment
bushings •For MCSG - Assembly with CT/PT integrated
•For MESG •Applied to medium compartment
•Applies VL type VCB capacity/high capacity VCB •Applies VL/VH type VCB

Ha type Hb type VH type

15
Convenience
Convenience in building switchgears
- Maximizing compatibility with existing products through the dualistic deployment of phases and compact models.

150 210
150 210

VCB rating
Ur (kV) Isc (kA) Ir (A)
12 20/25 630
31.5 1000
1250
17.5 20/25 630
31.5 1250

P150 P210
(distance between phases: 150mm) (distance between phases: 210mm)

150 210
150 210

VCB rating
Ur (kV) Isc (kA) Ir (A)
12 20/25 2000

17.5 20/25 2000

P150 P210
(distance between phases: 150mm) (distance between phases: 210mm)

275
275
VCB rating
Ur (kV) Isc (kA) Ir (A)
12 31.5 2500
17.5

P275
(distance between phases: 275mm)

16
< < Susol VCB Series

VCB rating
210 275
210 275

Ur (kV) Isc (kA) Ir (A)


24 12.5 630
1250
16/25 630
1250
25 2000
2500 *
25.8 12.5 630
1250
16/25 630
1250
25 2000
2500 *
* 2500A: phases distance 275mm only P210 P275
(distance between phases: 210mm) (distance between phases: 275mm)

VCB rating
Ur (kV) Isc (kA) Ir (A)
24 31.5/40 2000

25.8 31.5/40 2000

P210 P275
(distance between phases: 210mm) (distance between phases: 275mm)

Function to locking a breaker during transport of a switchgear


- Fixed bracket must be dismantled first to rack in a breaker - interlocking system
Fix braket easily visible from the front of the breaker

VL type VCB (VL-06) VL type VCB (VL-06/12/17) VL/VH type VCB


(E/F/G type) (E/F/G type) (H type CB compartment)
17
Accessories

A variety of accessories for VL-06

If accessories are attached to


the breaker, the function of
the breaker is upgraded.
Susol VCB provides a variety of
accessories depending on the
purpose.









Breaker
 Motor  Current trip coil
 Closing coil  Key lock
 Trip coil  Button padlock
 Counter  Button cover
 Auxiliary contacts  Position switch
 UVT coil  Lead wire

18
< < Susol VCB Series

A variety of accessories for VCL-06

If accessories are attached to the


cradle, the function of
the breaker is upgraded.
Susol VCB provides a variety of
accessories depending on the
purpose.

Cradle
 Handle for Racking-in and out
 UVT time delay controller
 Condenser trip device

19
Accessories

A variety of accessories for VL-06/12/17/20/25/36

If accessories are attached to


the breaker, the function of
the breaker is upgraded.
Susol VCB provides a variety of
accessories depending on the
purpose.

  

  

  

  

Breaker
 Motor  Position switch
 Closing coil  Handle for Racking-in/out
 Trip coil  UVT time delay controller
 Counter  CTD (Condenser trip device)
 Auxiliary contacts  MOC (Mechanism operated cell switch)
 UVT coil  Padlock (H type Door Interlock)
 Key lock  Locking magnet
 Button padlock  Plug Interlock
 Button cover

20
< < Susol VCB Series

A variety of accessories for VL-06/12/17/20/25/36

If accessories are attached to the


cradle, the function of
the breaker is upgraded.
Susol VCB provides a variety of
accessories depending on the
purpose.





 

Cradle (H type)
 TOC (Truck operated cell s/w)  Emergency ON/OFF button
 MOC (Mechanical operated cell s/w)  Earthing switch & Accessory
 Temperature sensor Key lock for Earthing switch
 Door Locking Magnet for Earthing switch
 Door interlock Position s/w for Earthing switch
 Shutter padlock  TM (Temperature monitoring unit)

21
Accessories

A variety of accessories for VH-06/12/17/20/25/36

If accessories are attached to


the breaker, the function of
the breaker is upgraded.
Susol VCB provides a variety of
accessories depending on the
purpose.

Breaker
 Motor  Auxiliary contact wire  Door Interlock for withdrawable type
 AC/DC coil rectifier  Key lock  Lifting hook
 Trip coil/Closing coil  Button cover/Push bar  Charge handle
Secondary trip coil  Button padlock  Racking in/out handle
 AC/DC UVT coil rectifier  Position switch  UVT Time delay controller
 UVT coil  Locking magnet  CTD (Condenser trip device)
 Latch checking switch  Plug interlock  Wireless Temp. monitoring sensor

22
< < Susol VCB Series

A variety of accessories for VH-06/12/17/20/25/36

If accessories are attached to the


cradle, the function of
the breaker is upgraded.
Susol VCB provides a variety of
accessories depending on the
purpose.

Cradle (H type)
 MOC (Mechanism operated cell switch)  Earthing switch & Accessories
 TOC (Truck operated cell switch) Key lock for Earthing switch
 Shutter padlock Locking magnet for Earthing switch
 Temperature sensor Position switch for Earthing switch
 Door  TM (Temperature monitoring unit)
Emergency ON/OFF button

23
Standards and certifications

E2 (List 1 or List3)
E2 (List3) is first proposed in the IEC 62271-100(2008) to improve the efficiency of the interrupting test.
According to it the number of interrupting test T60 is increased instead of fewer number of T10 and
T30 compared to the existing List1. List3 compared with the List1 maintains the equivalent of the test but
has severe test conditions because 34% higher arc energy applied to the breaker. List3 is applied to
Susol VCB series.

IEC62271-100 (2002) IEC62271-100 (2008)

Arc Energy: List 1 (100%) < List 2 (125%) < List 3 (134%)

134%

125%
100%

E2 List1 E2 List2

E2 List3 E1

Arc energy applied to the breaker

24
< < Susol VCB Series

M2, C2
IEC standards to verify the relibilty of the product allows to select the quality level for the product to be
tested according to its real performance and practical usage. The highest quality level of M2, C2 has been
applied to Susol VCB.

M1 and M2: Test to determine the mechanical durability grade

C-O
2000 operation test
Sequence Control Voltage Number of operations
85% 500
M2 M2
C-O 100% 500
C-O 110% 500
O - CO - C 100% 250

M1 M110,000 10,000
operations operations

2,000 2,000
operations operations

•Pre-test (characteristics, isolation, and temperature) •Pre-test (characteristics, isolation, and temperature)
•Confirmative tests after the completion of 2000 •Confirmative tests after every 2000 operation
operations (Characteristics, isolation, temperature) •Confirmative tests after the completion of 10,000
operations (Characteristics, isolation, temperature)

C1, C2: Capacitive current breaking test is to verify the probability of restriking and C2 class is secured for all Susol VCB.

C1 during C22 restrikes are allowed


C1“O” 24 operations C2 Restrike is not allowed
during “O” 24 operations
and “CO” 24 operations and “CO” 24 operations

25
External structure of VCB

Breaker ... VL type

Name of eac part


Push ON Button

Push OFF Button

Charge/Discharge Indicator

ON/OFF Indicator

Manual Charging Handle

Key Lock

Operation Counter

TEST/SERVICE
Position Indicator

Back side

26
Susol VCB

Breaker ... VH type

Name of eac part


Push ON Button

Push OFF Button

Charge/Discharge Indicator

ON/OFF Indicator

Manual Charging Handle

Key Lock

Operation Counter

TEST/SERVICE
Position Indicator

Back side

27
Basic functions and interrupting operation

Basic functions

Manual operation
① Manual Charge
a) VL type: operate the charge handle 7-8 times as a fully stroke.
b) VH type: Insert the charge handle into the handle slot first. Rotate the handle clockwise 40 times more
and then charge will be complete with a click sound.
- When the closing spring is charged fully "CHARGED" is displayed at the charge indicator.

② Manual closing
a) Pressing the ON button the breaker is closed.
b) With the closing of the breaker "ON" is displayed at Close/Trip indicator and "DISCHARGED" at the
charge indicator.

③ Manual trip
a) Pressing the OFF button the breaker is opened.
b) "OFF" is displayed at Close/Trip indicator.

Electric operation
① Electric charge
The breaker is remotely closing with charging of closing spring.
If the breaker closing the closing spring is automatically charged by gear motors.

② Electric closing
Remote closing is operated by the closing coil.

③ Electric trip
Remote trip can be operated by the trip coil or UVT coil.

Main contacts are operated by the energy of the spring mechanism and closing spring is charged by the
motor in the mechanism.
Breaker is closed by closing coil and tripped by trip coil.
These operations are repeated in VCB as shown in the below sequence chart.

Start closing Complete closing


Closing signal Trip(Open) signal
Control power ON Start opening
Charging time of closing spring Complete
(VL type : 5 sec, VH type : 12 sec.) opening

Motor

Closing spring

Opening spring

Closing coil

Opening coil

Main contact
Closing time Opening time

Sequence of the switching mechanism

28
Susol VCB

The interruption of vacuum interrupters

The interruption of VCB is carried out by the vacuum interrupters.


Interrupter contacts as a key part made of copper - chromium (CuCr) material with spiral shape have low
contact wear characteristics and withstand voltage is excellent.
Spiral contacts make the arc generated between the surfaces of contacts rotated around the surface of
contact by the induced magnetic field generated due to the spiral contact structure, which results in
preventing local heating, thereby corruption and interrupting instantaneously.

Fixed electrode

Fixed seal cup

Fixed shield

Contacts Arc shield

Ceramic

Bellows shield

Bellows

Movable seal cup

An example of oscillogram obtained through the interrupting test using LC resonant circuit

29
Basic functions and interrupting operation

T e interruption of vacuum interrupters

In case of using the flat contact


any of the designs do not reflect
on when contacts are opening
the arc with high temperature is
contracted and fixed in the
center of the contacts,Which is
called pinch effect.
To prevent the effect two kinds
of contact shapes are designed.
One is Axial magnetic field
which spreads the arc before its
contraction, and the other is
Radial magnetic field which
permits the contraction of the
arc but makes it rotated to
disperse the energy.
Because contracted arc is
shaped like a cylinder it is called
Contracted arc or columnar arc.
Arc voltage waveforms and arc image captured during arcing time

Spiral contact structure (Radial magnetic field), using


the force (F j B) generated by the interaction of the Radial magnetic field type contact
radial magnetic field caused by the current flowing
through the arc between two contacts, disperse the arc
energy evenly on the surface of contact by rotating the
arc that is contracted by the pinch effect so as to
minimize contact damage.
The images show arc behavior during the arcing time
of about 8ms by shooting with high-speed camera
capable of shooting 10,000 frames per sec. (10000FPS) Columnar arc Direction of
by focusing on parts of the arcing time on the above rotating arc

graph and simultaneously measured arc voltage also Current

represented to show arc state by section.


Arc driving principle in the contacts of
Radial magnetic field

30
Standards and certification Susol VCB

Susol VCB has been type tested and obtained certifications according to the latest IEC standard
at international testing laboratory and can be installed and applied at the environment and
conditions in accordance with the standard.

Standard
- IEC 62271-1 (2007.10)
High-voltage switchgear and controlgear - Part 1: Common specifications.
- IEC 62271-100 (2008.04)
High-voltage switchgear and controlgear - Part 2: Alternating-current circuit breakers.

Test and certification


Test report (KERI)
Test report (KEMA)

31
Types and ordering information

7.2kV (VL-06)

Breaker

VL 06 P 08 A 04

Basic model name Rated voltage kV Version Rated short time current kA hase distance Compatibility Rated current A
VL Susol VCB 06 7.2 P Fixed 08 8 A Standard 04 400
E E type drawout 13 12.5 Compatible with 06 630
B existing breaker
F F type drawout Note6)

G G type drawout

VL-06E08A04 M1 C1 T1 SA1 U1 A 147

Motor control voltage Trip coil voltage VT ote

M1 DC 110V T1 DC 110V U0 Without UVT


M2 DC 220V~250V T2 DC 220V~250V U1 DC 110V
M3 DC 125V T3 DC 125V U2 DC 220V~250V
M4 DC 24V~30V T4 DC 24V~30V U3 DC 125V
M5 DC 48V~60V T5 DC 48V~60V U4 DC 24V~30V
M6 AC 48V T6 AC 48V U5 DC 48V~60V
M7 AC 100V~130V T7 AC 100V~130V U6 AC 48V
M8 AC 200V~250V T8 AC 200V~250V U7 AC 100V~130V
T9 Current trip coil U8 AC 200V~250V

Closing coil voltage Connector and wire ther accessories Note)


C1 DC 110V SA1 A type connector, 2a2b 1 Secondary Trip coil Note5)
C2 DC 220V~250V SA2 Standard A type connector, 4a4b Position S/W
3
C3 DC 125V SA3 A type connector, 6a6b Note5) (Test : 1a1b, Service : 2b)
C4 DC 24V~30V SA5 A type connector, 2a2b Position S/W
Flame 4
C5 DC 48V~60V SA6 A type connector, 4a4b (Test : 2a, Service : 2a)
retardant
C6 AC 48V SA7 A type connector, 6a6b Note5) Position S/W
5
C7 AC 100V~130V (Test : 1a1b, Service : 1a1b)
C8 AC 200V~250V 7 Key lock
Note)
ptional
8 Button Padlock
1. In the case of selecting accessories such as A1(Secondary trip coil), A4(Position S/W LH Lifting Hook
2a2a)and A7(Key lock), A147 is type name in the ordering.
9 Button cover
2. Unable to select A1(Secondary Trip coil), U1~U8(UVT)and T9(Current trip coil) CTD1 Condenser Trip Device(AC 110V)
simultaneously. A Lead wire
3. A4(Position S/W 2a2a) and A5(Position S/W 2a2b) can not be selected simultaneously. CTD2 Condenser Trip Device(AC 220V)
4. A8 (Button Padlock) and A9 (Button Cover) can not be selected simultaneously. B User Plug (Part)
UDC1 UVT Time Delay Controller(AC/DC 110V)
5. Maximum number of Auxiliary Contacts available are 5a5b, 5a6b in the case of
O Lead Wire special color (Blue)
selecting A1(Secondary trip coil), U1~U8(UVT). UDC2 UVT Time Delay Controller(AC/DC 220V)
6. In case of using the existing old type cradle and replacing breaker only please order Note) A is written only once in case of more
type B (Compatible with existing breaker). Compatibille busbars are required for UDC3 UVT Time Delay Controller(AC/DC 48V)
than one.
fixed version.
CTU Coil Test Unit
7. If T9(CTC) is selected, in case of adding Secondary trip coil, CTC is also added.

32
Susol VCB

Cradle

VCL 06 E 08 A 06

Basic model name Rated voltage kV Version Rated short time current kA hase distance Compatibility Rated current A
VCL Susol VCB 06 7.2 E E type drawout 08 8 A Standard 04 400
F F type drawout 13 12.5 Compatible with 06 630
B existing breaker
G G type drawout Note6)

Note) In case of replacing the existing old type VCB with Susol VCB please order type B for cradle and A for breaker.

33
Types and ordering information

7.2/12/17.5kV (VL-06/12/17)

Breaker

VL 06 H 20 A 06

Basic model name Rated voltage kV Version Rated short time current kA hase distance Compatibility Rated current A
VL Susol VCB 06 7.2 P Fixed 20 20 A 150mm 06 630
12 12 E E type drawout (for MESG) 25 25 B 210mm 13 1250
17 17.5 F F type drawout (for MESG) 32 31.5 D 275mm 20 2000
Fs Fs type drawout (Screw Type) Compatible with 25 2500
F
G G type drawout (for MESG) existing products
Gs Gs type drawout (Screw Type) Compatible with
K
K Pro-MEC G/T(T)
K type drawout (for MCSG
K Note)
compatible with Pro-MEC) 1. In case of 7.2kV
H H type drawout (for MCSG) 1) Phase distance 150mm only
2) 20/25kA: only 630/1250/2000A available (E/F/G)
Note) 1. Breaking current 31.5kA: E/F/Fs/G 3) 31.5kA: only 1250/2000A available (E/F/G)
2. K type: phase distance 150mm only
type can be used only with 7.2k
3. In case of 12/17.5kV
2. Gs/K type: Usable only 7.2/12kV 1) H type: phase distance 150/210/275 all available
K type Compatible with Pro-MEC G/T(T) 2) P type 630/1250A: phase distance 150/210 all available
(for withdrawable type for MCSG) 3) In case of 20/25kA: 12/17.5kV E/F type phase distance 210 available
4) K type: compatible with Pro-MEC G/T(T) (phase distance 150mm)
5) F type (compatible with existing products): Available only to
20/25kA and 630/1250A (phase distance 210mm)
4. Rated current 2500A: only available 31.5kA P/H type
(phase distance 210/275mm)

VL-06H20A06 M1 C1 T1 SQ2 U1 A 147

Motor control voltage Trip coil voltage VT


M1 DC 110V T1 DC 110V U0 Without UVT
M2 DC 220V~250V T2 DC 220V~250V U1 DC 110V
M3 DC 125V T3 DC 125V U2 DC 220V~250V
M4 DC 24V~30V T4 DC 24V~30V U3 DC 125V
M5 DC 48V~60V T5 DC 48V~60V U4 DC 24V~30V
M6 AC 48V T6 AC 48V U5 DC 48V~60V
M7 AC 100V~130V T7 AC 100V~130V U6 AC 48V
M8 AC 200V~250V T8 AC 200V~250V U7 AC 100V~130V
T9 Current trip coil U8 AC 200V~250V

Closing coil voltage Connector and wire ther accessories Note)


C1 DC 110V SA2 A type connector, 4a4b 1 Secondary Trip coil
Note) C2 DC 220V~250V SA4 A type connector, 10a10b 2 Secondary Trip Coil with TCM Contact
1. If A2 (UVT), A4 (Position S/W 2a2b) and A7 (Keylock) are Standard 3 Position S/W (Test : 1a1b, Service : 2b)
selected, A147 is the type name in the ordering. C3 DC 125V S 2 type connector, 4a4b 4 Position S/W (Test : 2a, Service : 2a)
2. Unable to select A1(Secondary trip coil), U1~U8(UVT) C4 DC 24V~30V S 4 type connector, 10a10b
simultaneously. 5 Position S/W (Test : 1a1b, Service : 1a1b)
3. A3(Position S/W 1a3b), A4(Position S/W 2a2a), A5(Position C5 DC 48V~60V SA6 A type connector, 4a4b 7 Key lock
S/W 2a2b)can not be selected simultaneously.
SA8 8 Button Padlock
4. A8 (Button Padlock) and A9 (Button Cover) can not be C6 AC 48V Flame A type connector, 10a10b
9 Button Cover
selected simultaneously. C7 AC 100V~130V S 6 retardant type connector, 4a4b
5. When A1 (Secondary Trip coil) is selected the maximum A Lead Wire
available auxiliary contacts are 9a9b. C8 AC 200V~250 S 8 type connector, 10a10b B User Plug (Part)
6. When A2(Secondary trip coil with TCM Contact) is selected C Plug Interlock
the maximum available auxiliary contacts are 4a3b, 9a8b.
7. AC (Plug interlock), AD (H type Door interlock), AE (MOC) and AF (Locking magnet) are available ptional D Padlock (H type Door Interlock)
only for H type. E MOC (Mechanical Operating Cell S/W)
8. A/ -type connector is applicable to P/E/F/G/K type and -type connector to H type. CTD1 Condenser Trip Device(AC 110V) F Locking Magnet
9. Lead wire special color (blue) is applicable to A-type connector. CTD2 Condenser Trip Device(AC 220V)
10. When the position switch is selected from accessories, auxiliary contacts and wiring ass y can be
G Keylock(Same key-One key for 3EA VCB)
selected as option A/ -type (P/E/F/G/K-type) or -type(H-type) connector UDC1 UVT Time Delay Controller(AC/DC 110V) I Mecha Shaft Interlock Lever
11. Locking magnet of H type breaker use the same control power supply as motor.
UDC2 UVT Time Delay Controller(AC/DC 220V) Door Interlock
12. Flame retardant type blue wire is not available. O Lead Wire special color (Blue)
13. When current Trip Coil AV(CTC 1A) or AW(CTC 5A) is selected, A1(Secondary Trip Coil), UDC3 UVT Time Delay Controller(AC/DC 48V)
U1~U8(UVT) cannot be selected simultaneously and the maximum auxiliary contact is 4a4b. V CT operated coil 1A
14. AI(Mecha Shaft Interlock Lever) is available only for 12kV, P type. CTU Coil Test Unit W CT operated coil 5A
Note) A is written only once in case of more
than one.

34
Susol VCB

Cradle

VCL 06 H 20 A 06 A 157

Basic model name Rated voltage kV Rated short time current kA Rated current A
VCL Susol VCB 06 7.2 20 20 06 630
12 12 25 25 13 1250
17 17.5 32 31.5 20 2000
25 2500

Version hase distance Compatibility ther accessories


P Fixed A 150mm ES(Standard earthing Switch)
1
E E type drawout (for MESG) B 210mm without option
F F type drawout (for MESG) D 275mm 2 ES with position S/W(2a2b)
Fs Fs type drawout (Screw Type) Compatible with 4 ES with position S/W(6a6b)
F
G G type drawout (for MESG) existing products 5 Key lock for ES
Gs Gs type drawout (Screw Type) Compatible with 6 Locking magnet for ES: DC 110V
K
K Pro-MEC G/T(T) 7 Locking magnet for ES: DC 220V
K type drawout (for MCSG
K
compatible with Pro-MEC) Note) 8 Locking magnet for ES: DC 125V
1. In case of 7.2kV
H H type drawout (for MCSG) 1) Phase distance 150mm only 9 Locking magnet for ES: DC 24V
2) 20/25kA: only 630/1250/2000A available (E/F/G)
Note) 1. Breaking current 31.5kA: E/F/Fs/G A Locking magnet for ES: DC 48V
3) 31.5kA: only 1250/2000A available (E/F/G)
type can be used only with 7.2k
2. Gs/K type: Usable only 7.2/12kV
2. K type: phase distance 150mm only B Locking magnet for ES: AC 48V
3. In case of 12/17.5kV
K type Compatible with Pro-MEC G/T(T)
1) H type: phase distance 150/210/275 all available C Locking magnet for ES: AC 110V
(for withdrawable type for MCSG)
2) P type 630/1250A: phase distance 150/210 all available D Locking magnet for ES: AC 220V
3) In case of 20/25kA: 12/17.5kV E/F type phase distance 210 available
4) K type: compatible with Pro-MEC G/T(T) (phase distance 150mm) E Shutter padlock
5) F type (compatible with existing products): Available only to 20/25kA
and 630/1250A (phase distance 210mm)
F TOC(Truck Operating Cell S/W)
4. Rated current 2500A: only available 31.5kA P/H type (phase distance G MOC (Mechanical Operating Cell S/W)
210/275mm)
H Door
Door Interlock
K Door Emergency Push Button
L Temperature Monitoring Sensor
H type Lead wire 4a4b
M
(Flame retardant wire)
H type Lead wire 10a10b
N
(Flame retardant wire)
H type Lead wire 4a4b
O
(Rated short time current)

Note) 1. These accessories for cradle and TM can be applied only to H type. (When ordering TM, AL option must be selected)
ptional
2. A and AK can not be selected without door (AH).
3. H type lead wire - one of AM, AN or AO is required for cradle in case of H type breaker. TM Temperature Monitoring
4. Unable to select AK at the cradle in the case of selecting A8(Button Padlock), A9(Button Cover) for body of H-type.
5. When Keylock(A5) is selected, Earthing Switch is included as standard. Note) A is written only once in case of more
6. Please contact us if you need IAC (Internal arc classification) of H type CB compartment. than one.

35
Types and ordering information

24/25.8/36kV (VL-20/25/36)

Breaker

VL 20 H 13 B 06

Basic model name Rated voltage kV Version Rated short time current kA hase distance Compatibility Rated current A
VL Susol VCB 20 24 P Fixed 13 12.5 B 210mm 06 630
25 25.8 E E type drawout (for MESG) 16 16 F 265mm 13 1250
36 36 F F type drawout (for MESG) 25 25 D 275mm 20 2000
G G type drawout (for MESG) Enclosed type, 25 2500
G
K type drawout (for MCSG Tulip Contact
K
compatible with Pro-MEC) Note) - P, E, F type : phase distance 265mm only
H H type drawout (for MCSG) - G-type: 630A and 1250A 210mm and 265mm
2000A - phase distance 210mm only
- K-type: 630A and 1250A - , 210mm and 265mm
2000A - phase distance 265mm only
- H-type: All ratings - dual phase distance, 210mm
and 275mm dual
(2500A - phase distance 275mm only)
- E, F-type: phase distance and appearance are
distinguished with F and G

VL-20H13B06 M1 C1 T1 SQ2 U1 A 147

Motor control voltage Trip coil voltage VT


M1 DC 110V T1 DC 110V U0 Without UVT
M2 DC 220V~250V T2 DC 220V~250V U1 DC 110V
M3 DC 125V T3 DC 125V U2 DC 220V~250V
M4 DC 24V~30V T4 DC 24V~30V U3 DC 125V
M5 DC 48V~60V T5 DC 48V~60V U4 DC 24V~30V
M6 AC 48V T6 AC 48V U5 DC 48V~60V
M7 AC 100V~130V T7 AC 100V~130V U6 AC 48V
M8 AC 200V~250V T8 AC 200V~250V U7 AC 100V~130V
T9 Current trip coil U8 AC 200V~250V

Closing coil voltage Connector and wire ther accessories Note)


C1 DC 110V SA2 A type connector, 4a4b 1 Secondary Trip coil
Note)
1. If A2 (UVT), A4 (Position S/W 2a2b) and A7 (Keylock) are C2 DC 220V~250V SA4 A type connector, 10a10b 2 Secondary Trip Coil with TCM Contact
Standard
selected, A147 is the type name in the ordering. C3 DC 125V S 2 type connector, 4a4b 3 Position S/W (Test : 1a1b, Service : 2b)
2. Unable to select A1(Secondary trip coil), U1~U8(UVT) C4 DC 24V~30V S 4 type connector, 10a10b 4 Position S/W (Test : 2a, Service : 2a)
simultaneously.
3. A3(Position S/W 1a3b), A4(Position S/W 2a2a), A5(Position
C5 DC 48V~60V SA6 A type connector, 4a4b 5 Position S/W (Test : 1a1b, Service : 1a1b)
S/W 2a2b)can not be selected simultaneously. C6 AC 48V SA8 Flame A type connector, 10a10b 7 Key lock
4. A8 (Button Padlock) and A9 (Button Cover) can not be C7 AC 100V~130V S 6 retardant type connector, 4a4b 8 Button Padlock
selected simultaneously.
C8 AC 200V~250 S 8 type connector, 10a10b 9 Button Cover
5. When A1 (Secondary Trip coil) is selected the maximum
available auxiliary contacts are 9a9b. A Lead Wire
6. When A2(Secondary trip coil with TCM Contact) is selected the maximum available auxiliary B User Plug (Part)
contacts are 4a3b, 9a8b.
ptional C Plug Interlock
7. AC (Plug interlock), AD (H type Door interlock), AE (MOC) and AF (Locking magnet) are available
D Padlock (H type Door Interlock)
only for H type. CTD1 Condenser Trip Device(AC 110V)
8. A/ -type connector is applicable to P/E/F/G type and -type connector to H type. E MOC (Mechanical Operating Cell S/W)
9. Lead wire special color (blue) is applicable to A-type connector.
CTD2 Condenser Trip Device(AC 220V)
F Locking Magnet
10. When the position switch is selected from accessories, auxiliary contacts and wiring ass y can UDC1 UVT Time Delay Controller(AC/DC 110V)
be selected as option A/ -type (P/E/F/G/K-type) or -type(H-type) connector Door Interlock
UDC2 UVT Time Delay Controller(AC/DC 220V)
11. Locking magnet of H type breaker use the same control power supply as motor. O Lead Wire special color (Blue)
12. Flame retardant type blue wire is not available. UDC3 UVT Time Delay Controller(AC/DC 48V) V CT operated coil 1A
13. When current Trip Coil AV(CTC 1A) or AW(CTC 5A) is selected, A1(Secondary Trip Coil),
CTU Coil Test Unit W CT operated coil 5A
U1~U8(UVT) cannot be selected simultaneously and the maximum auxiliary contact is 4a4b.
Note) A is written only once in case of more
than one.

36
Susol VCB

Cradle

VCL 20 H 13 B 06 A 157

Basic model name Rated voltage kV Rated short time current kA Rated current A
VCL Susol VCB 20 24 13 12.5 06 630
25 25.8 16 16 13 1250
36 36 25 25 20 2000
25 2500

Version hase distance Compatibility ther accessories


E E type drawout (for MESG) B 210mm ES(Standard earthing Switch)
1
F 265mm without option
F F type drawout (for MESG)
D 275mm 2 ES with position S/W(2a2b)
G G type drawout (for MESG)
Enclosed type, 4 ES with position S/W(6a6b)
K type drawout (for MCSG G
K Tulip Contact 5 Key lock for ES
compatible with Pro-MEC)
Note) - P, E, F type: phase distance 265mm only 6 Locking magnet for ES: DC 110V
H H type drawout (for MCSG)
- G-type: 630A and 1250A 210mm and 265mm 7 Locking magnet for ES: DC 220V
Note) K-type(compatible with Pro-MEC 2000A phase distance 210mm only
G/T(T)) cradle for MCSG is for below - K-type: 630A and 1250A, 210mm and 8 Locking magnet for ES: DC 125V
product - LCL-20G-13D/T,15D/T, 265mm 9 Locking magnet for ES: DC 24V
25D/T 2000A - phase distance 265mm only
- H-type: All ratings - dual phase distance, A Locking magnet for ES: DC 48V
210mm and 275mm dual
B Locking magnet for ES: AC 48V
(2500A - phase distance 275mm only)
- E, F-type: phase distance and appearance C Locking magnet for ES: AC 110V
are distinguished with F and G
D Locking magnet for ES: AC 220V
E Shutter padlock
F TOC(Truck Operating Cell S/W)
G MOC (Mechanical Operating Cell S/W)
H Door
Door Interlock
K Door Emergency Push Button
L Temperature Monitoring Sensor
H type Lead wire 4a4b
M
(Flame retardant wire)
H type Lead wire 10a10b
N
(Flame retardant wire)
Note) 1. These accessories for cradle and TM can be applied only to H type. H type Lead wire 4a4b
2. A and AK can not be selected without door (AH). O
3. TM (Temperature Monitoring) should be used with AL (Temperature Sensor).
(Rated short time current)
4. H type lead wire - one of AM, AN or AO is required for cradle in case of H type breaker.
5. Accessary A2~A is available to H-type. Exceptionally K-type is available to A1.
(Position S/W 4a4b is basic option of A1) ptional
6. Unable to select AK at the cradle in the case of selecting A8(Button Padlock), A9(Button TM Temperature Monitoring
Cover) for body of H-type.
7. When Keylock(A5) is selected, Earthing Switch is included as standard. Note) A is written only once in case of more
8. Please contact us if you need IAC (Internal arc classification) of H type CB compartment. than one.

37
Types and ordering information

7.2/12kV (LVB-06/12)

Breaker

LVB 06 G 40 L / 12 1A 2B BB6GT2

Basic model name Rated voltage kV Rated short time current kA Rated current A Connector and wire
LVB Susol VCB 06 7.2 32 31.5 12 1250 2B A type connector, 4a4b
12 12 40 40 20 2000 2E A type connector, 10a10b

30 3150 2M type connector, 4a4b


Note) In case of 31.5kA, 3150A
is availble only. 2N type connector, 10a10b
31.5kA 630/1250/2000/2500A:
Please refer to VL Series
00 Dummy VCB

Version Model version Control voltage ther accessories Note)


P Fixed L Susol 1A DC 110V B Position S/W(Test : 2a, Service : 2a)
E E type drawout 1B DC 220V~250V B1 Position S/W(Test : 1a1b, Service : 1a1b)
F F type drawout 1C DC 48V B2 Position S/W(Test : 1a1b, Service : 2b)
G G type drawout 1E DC 125V B6 User s Plug(Part)
G/T type drawout 1L AC 220V C1 Button Padlock(ON)
G
(for MESG) T2
1M AC 110V C2 Button Padlock(OFF)
1N AC 48V C3 Button Padlock(ON,OFF)
00 Dummy VCB D1 Button Cover(ON)
D2 Button Cover(OFF)
D3 Button Cover(ON OFF)
E Button Padlock(ON) Button Cover(OFF)
F Button Padlock(OFF) Button Cover(ON)
G Keylock
H Secondary Trip coil
Flame retardant wire
K Latch checking S/W
Note)
P1 Dummy VCB(A type connector)
1. H(Secondary trip coil) and V(UVT) can not be selected simultaneously.
2. B(Position S/W 2a2a), B1(Position S/W 2a2b) and B2(Position S/W 1a3b) can not be selected P2 Dummy VCB(B type connector)
simultaneously.
However, only B(Position S/W 2a2a) is available for G/T type(MCSG drawable type) S Padlock
3. If V(UVT) is selected , additional K(Latch checking S/W) is not allowed. T Tulip contact, Closed type
(Because if UVT is slected a latch checking S/W is included as standard for electrical interlocking )
4. One out of T and T2 should be selected for G/T type(MCSG drawable type). T2 T Earthing S/W Interlock change
T2 is the standard and T (Product before Earthing S/W interlock change) is suitable for compatibility
V UVT
with existing products.
5. In case of T(Tulip contact, closed type) 3150A is available only for open type housing .
6. Only G/T type is available for 12kV.

38
Susol VCB

Cradle

LCL 06 G 40 D / 12 BCDT2

Basic model name Rated voltage kV Rated short time current kA Rated current A
PRO-MEC 06 7.2 32 31.5 12 1250
LCL
Cradle 12 12 40 40 20 2000
30 3150

Version Model version ther accessories


P Fixed D Pro-MEC B Earthing Switch Note2)
E E type drawout C Earthing Switch Position S/W(ON/OFF)
F F type drawout D Earthing Switch Locking coil
G G type drawout T Tulip contact, Closed type Note1
G/T type drawout T2 T Earthing S/W Interlock change Note1
G
(for MESG) T2
T2 Earthing S/W without
T3
Conductor ass y Note1
U1 Reduced height type Note2)

Note) 1. One out of T, T2 and T3 should be selected for G/T type(MCSG drawable type).
T2 is the standard and T (Product before Earthing S/W interlock change)
is suitable for compatibility with existing products.
T3 is available only for 1250/2000A.
2. U1(Reduced height type) and B(Earthing S/W) can not be selected simultaneously.

39
Types and ordering information

7.2/12/17.5/24/25.8/36kV (VH-06/12/17/20/25/36)

Breaker

VH 06 H 25 B 13

Basic model name Rated voltage kV Version Rated short time current kA hase distance Compatibility Rated current A
VH Susol VCB 06 7.2 P Fixed 25 25 A 150mm 12 1200A
12 12 E E type drawout (for MESG) 32 31.5 B 210mm 13 1250A
17 17.5 F F type drawout (for MESG) 40 40 D 275mm 20 2000A
20 24 Fs Fs type drawout (Screw Type) 50 50 E 300mm 25 2500A
25 25.8 G G type drawout (for MESG) Note) Compatible with 32 3150A
K
1. 25kA is for 24/36kV K Pro-MEC G/T(T)
36 36 Gs Gs type drawout (Screw Type) 2. 31.5/40kA is for 40 4000A
7.2/12/17.5/24/36kV L 320mm
K type drawout (for MCSG 50 5000A
K 3. 50kA is for 7.2/12/17.5kV
compatible with Pro-MEC type) Note) K can be selected for
Pro-MEC G/T(T) Note) Refer to the rating
H H type drawout (for MCSG) compatible models table for selecting
ONL and the phase rated current.
distance is 150mm.

VH-06H25B13 M1 C1 T1 SQ2 U1 A 147

Motor control voltage Trip coil voltage VT


M1 DC 110V T1 DC 110V U0 Without UVT
M2 DC 220V~250V T2 DC 220V~250V U1 DC 110V
M3 DC 125V T3 DC 125V U2 DC 220V~250V
M5 DC 48V T5 DC 48V U3 DC 125V
M6 AC 48V T6 AC 48V U5 DC 48V
M7 AC 110V T7 AC 110V U6 AC 48V
M8 AC 220V T8 AC 220V U7 AC 110V
U8 AC 220V

Closing coil voltage Connector and wire ther accessories Note)


C1 DC 110V SA2 A type connector, 4a4b 1 Secondary Trip coil
C2 DC 220V~250V SA4 A type connector, 10a10b 2 Secondary Trip Coil with TCM Contact
Standard
C3 DC 125V
S 2 type connector, 4a4b 3 Position S/W (Test : 1a1b, Service : 2b)
Note)
1. If A1(Secondary trip coil), A4(Position S/W 2a2a), A7(Keylock) S 4 type connector, 10a10b 4 Position S/W (Test : 2a, Service : 2a)
C5 DC 48V
are selected, A147 is the type name in the ordering. SA6 A type connector, 4a4b 5 Position S/W (Test : 1a1b, Service : 1a1b)
2. A1(Secondary trip coil), U1~U8(UVT) can not be selected C6 AC 48V
simultaneously. SA8 Flame A type connector, 10a10b 7 Key lock
3. A3(Position S/W 1a3b), A4(Position S/W 2a2a), A5(Position C7 AC 110V S 6 retardant type connector, 4a4b
S/W 2a2b) can not be selected simultaneously.
8 Button Padlock
C8 AC 220V S 8 type connector, 10a10b
4. A8 (Button Padlock) and A9 (Button Cover) can not be 9 Button Cover
selected simultaneously.
5. AC (Plug interlock), AD (H type Door interlock), AE (MOC) and AF (Locking magnet) are available A Lead Wire
only for H type. B User Plug (Part)
6. A/ -type connector is applicable to P/E/F/G/K type and -type connector to H type.
7. Lead Wire Special Color(blue) is available only for A type connector and the flame retardant is ptional C Plug Interlock
not applicable to it. CTD1 Condenser Trip Device(AC 110V) D Padlock (H Door Interlock)
8. Locking magnet can be applied only to H type VCB - breaker and cradle.
9. Locking magnet of H type breaker use the same control power supply as motor. CTD2 Condenser Trip Device(AC 220V) E MOC (Mechanical Operating Cell S/W)
10. In case of selecting UVT A6 (Latch checking S/W) is not allowed. A6 (Latch checking S/W) is F Locking Magnet
installed by default to make electrical interlock with UVT. UDC1 UVT Time Delay Controller(AC/DC 110V)
11. Lead wire is enclosed in the breaker in case of ordering fixed type or H type breaker without G ANSI Charge interlock
UDC2 UVT Time Delay Controller(AC/DC 220V)
cradle, installed of cradle in case of ordering the breaker with cradle. If user plug is selected it
O Lead Wire special color ( )
will be enclosed in the breaker. UDC3 UVT Time Delay Controller(AC/DC 48V)
12. When A1(Secondary trip coil) is selected the maximum available auxiliary contacts are 10a10b. Wireless Temperature
13. When A2(Secondary Trip coil with TCM Contact) is selected the maximum available auxiliary CTU Coil Test Unit monitoring sensor
contacts are 4a3b, 10a9b.
Note) A is written only once in case of more
than one.

40
Susol VCB

Cradle

VCH 06 H 25 B 13 A 157

Rated voltage kV Rated short time current kA Rated current A


Basic model name
06 7.2 25 25 12 1200A
Susol VCB
VCH 12 12 32 31.5 13 1250A
Cradle
17 17.5 40 40 20 2000A
20 24 50 50 25 2500A
25 25.8 32 3150A
36 36 40 4000A
50 5000A

Version hase distance Compatibility ther accessories type


P Fixed A 150mm ES(Standard earthing Switch)
1
without option
E E type drawout (for MESG) B 210mm
2 ES with position S/W(2a2b)
F F type drawout (for MESG) D 275mm
4 ES with position S/W(6a6b)
Fs Fs type drawout (Screw Type) E 300mm
5 Key lock for ES
G G type drawout (for MESG) Rotated bushing
type (210mm) 6 Locking magnet for ES: DC 110V
Gs Gs type drawout (Screw Type)
L 320mm 7 Locking magnet for ES: DC 220V
K type drawout (for MCSG
K 8 Locking magnet for ES: DC 125V
compatible with Pro-MEC type)
H H type drawout (for MCSG) A Locking magnet for ES: DC 48V
* Only K-type cradle is available for 4000A. B Locking magnet for ES: AC 48V
* E/F/Fs/Gs/K-type (open type cradle)
C Locking magnet for ES: AC 110V
* H-type (box type cradle)
D Locking magnet for ES: AC 220V
E Shutter padlock
F TOC (Truck Operating Cell S/W)
G MOC (Mechanical Operating Cell S/W)
H Door
Door Interlock
K Door Emergency Push Button
L Temperature Sensor
H type Lead wire 4a4b (Flame
M
retardant wire)
Note)
1. Cradle accessories and the option TM are available only for H type(MCSG drawable type) H type Lead wire 10a10b (Flame
N
and Locking magnet is available in DC110V, DC125V for those three types. retardant wire)
K, Ha, Hb types can only be applied to A1.
H type Lead wire 4a4b (Rated
2. A and AK can not be selected without door (AH). O
short time current)
3. H type lead wire - one of AM, AN or AO is required for cradle in case of H type breaker.
4. If the H type breaker options A8(Button Padlock) and A9(Button Cover) are slected, the cradle ANSI type Charge interlock
option AK(Door Emergency Push Button) is not available.
Earthing S/W without conductor
5. When Keylock(A5) is selected, Earthing Switch is included as standard. T3
6. T3/SM/LC/U/U1 can be selected for K type ONL .
ass'y
7. When A1 is selected for 4000A, 5000A cradle, ES Position S/W with 4a4b is applied as default. LC Earthing S/W Locking coil
8. If TOC/MOC option is selected, cradle s height is increased
(E/S equipped structure, Hb ONL ). U1 Earthing S/W Locking coil
9. Ha type is open-type MCSG Cradle with NO door related options included. Note) T3, LC, U1 are options for K type cradle
10. Please contact us if you need IAC (Internal arc classification) of H type CB compartment. ONL (Compatible with previous
Pro-MEC models)

ptional
TM Temperature Monitoring
Note) A is written only once in case of more
than one.

41
Type of circuit breakers

7.2/12/17.5/24/25.8/36kV (VL-06/12/17/20/25/36)
Ur Isc Ir[A] VCB CRADLE
Connector
[kV] [kA] p 130 p 150 p 210 p 265 p 275 Type Version Type Version
VCL-06 08A04 E,F,G A
VL-06 08A04 P,E,F,G
8 400 VCL-06 08B04 E,F,G A
VL-06 08B04 P,E,F,G A
VCL-06 13A06 E,F,G A
VL-06 13A06 P,E,F,G
12.5 630 VCL-06 13B06 E,F,G A
VL-06 13B06 P,E,F,G A
630 VL-06 20A(K)06 P,E,F,G,H VCL-06 20A(K)06 E,F,G,K,H P,E,F,G,K:A/ ,H:
7.2 20 1250 VL-06 20A(K)13 P,E,F,G,H VCL-06 20A(K)13 E,F,G,K,H P,E,F,G,K:A/ ,H:
2000 VL-06 20A20 P,E,F,G,H VCL-06 20A20 E,F,G,H P,E,F,G:A/ ,H:
630 VL-06 25A(K)06 P,E,F,G,K.H VCL-06 25A06 E,F,G,K,H P,E,F,G,K:A/ ,H:
25 1250 VL-06 25A(K)13 P,E,F,G,K,H VCL-06 25A13 E,F,G,K,H P,E,F,G,K:A/ ,H:
2000 VL-06 25A(K)20 P,E,F,G,K,H VCL-06 25A20 E,F,G,K,H P,E,F,G,K:A/ ,H:
630 VL-06 32A06 P,H VCL-06H32A06 H
31.5 1250 VL-06 32A(K)13 P,E,F,Fs,G,Gs,K,H VCL-06 32A13 E,F,Fs,G,Gs,K,H P,E,F,Fs,G,Gs,K:A/ ,H:
2000 VL-06 32A(K)20 P,E,F,Fs,G,Gs,K,H VCL-06 32A20 E,F,Fs,G,Gs,K,H P,E,F,Fs,G,Gs,K:A/ ,H:
630 VL-12 20A(K)06 P,K,H VCL-12 20A06 K,H K:A/ ,H:
1250 VL-12 20A(K)13 P,K,H VCL-12 20A13 K,H K:A/ , H:
2000 VL-12H20A20 H VCL-12H20A20 H
630 VL-12 20B06 P,E,F,H VCL-12 20B06 E,F,H P,E,F:A/ ,H:
20
1250 VL-12 20B13 P,E,F,H VCL-12 20B13 E,F,H P,E,F:A/ ,H:
2000 VL-12 20B20 P,E,F,H VCL-12 20B20 E,F,H P,E,F:A/ ,H:
630 VL-12 20F06 E,F VCL-12 20F06 E,F A/
1250 VL-12 20F13 E,F VCL-12 20F13 E,F A/
630 VL-12 25A(K)06 P,K,H VCL-12 25A06 K,H K:A/ ,H:
1250 VL-12 25A(K)13 P,K,H VCL-12 25A13 K,H K:A/ ,H:
2000 VL-12 25A(K)20 K,H VCL-12 25A20 K,H K:A/ ,H:
630 VL-12 25B06 P,E,F,H VCL-12 25B06 E,F,H P,E,F:A/ ,H:
12 25
1250 VL-12 25B13 P,E,F,H VCL-12 25B13 E,F,H P,E,F:A/ ,H:
2000 VL-12 25B20 P,E,F,H VCL-12 25B20 E,F,H P,E,F:A/ ,H:
630 VL-12 25F06 E,F VCL-12 25F06 E,F A/
1250 VL-12 25F13 E,F VCL-12 25F13 E,F A/
630 VL-12 32A06 P,H VCL-12H32A06 H
1250 VL-12 32A(K)13 P,Gs,K,H VCL-12 32A13 Gs,K,H Gs,K:A/ ,H:
2000 VL-12 32A(K)20 Gs,K,H VCL-12 32A20 Gs,K,H Gs,K:A/ ,H:
630 VL-12 32B06 P,H VCL-12H32B06 H
31.5
1250 VL-12 32B13 P,H VCL-12H32B13 H
2000 VL-12 32B20 P,H VCL-12H32B20 H
2500 VL-12 32B25 P,H VCL-12H32B25 H
2500 VL-12 32D25 P,H VCL-12H32D25 H
630 VL-17H20A06 H VCL-17H20A06 H
1250 VL-17H20A13 H VCL-17H20A13 H
2000 VL-17H20A20 H VCL-17H20A20 H
630 VL-17 20B06 P,E,F,H VCL-17 20B06 E,F,H P,E,F:A/ ,H:
20
1250 VL-17 20B13 P,E,F,H VCL-17 20B13 E,F,H P,E,F:A/ ,H:
2000 VL-17 20B20 P,E,F,H VCL-17 20B20 E,F,H P,E,F:A/ ,H:
630 VL-17 20F06 E,F VCL-17 20F06 E,F A/
1250 VL-17 20F13 E,F VCL-17 20F13 E,F A/
630 VL-17H25A06 H VCL-17H25A06 H
1250 VL-17H25A13 H VCL-17H25A13 H
2000 VL-17H25A20 H VCL-17H25A20 H
630 VL-17 25B06 P,E,F,H VCL-17 25B06 E,F,H P,E,F:A/ ,H:
17.5 25
1250 VL-17 25B13 P,E,F,H VCL-17 25B13 E,F,H P,E,F:A/ ,H:
2000 VL-17 25B20 P,E,F,H VCL-17 25B20 E,F,H P,E,F:A/ ,H:
630 VL-17 25F06 E,F VCL-17 25F06 E,F A/
1250 VL-17 25F13 E,F VCL-17 25F13 E,F A/
630 VL-17 32A06 P,H VCL-17H32A06 H
1250 VL-17 32A13 P,H VCL-17H32A13 H
2000 VL-17 32A20 H VCL-17H32A20 H
630 VL-17 32B06 P,H VCL-17H32B06 H
31.5
1250 VL-17 32B13 P,H VCL-17H32B13 H
2000 VL-17 32B20 P,H VCL-17H32B20 H
2500 VL-17 32B25 P,H VCL-17H32B25 H
2500 VL-17 32D25 P,H VCL-17H32D25 H

42
Susol VCB

Ur Isc Ir[A] VCB CRADLE


Connector
[kV] [kA] p 130 p 150 p 210 p 265 p 275 Type Version Type Version
630 VL-20 13B06 G,K,H VCL-20 13B06 G,K,H G,K:A/ , H:
1250 VL-20 13B13 G,K,H VCL-20 13B13 G,K,H G,K:A/ , H:
630 VL-20 13F06 P,E,F,G,K VCL-20 13F06 E,F,G,K A/
630 VL-20 13G06 E,F VCL-20 13G06 E,F A/
12.5
1250 VL-20 13F13 P,E,F,G,K VCL-20 13F13 E,F,G,K A/
1250 VL-20 13G13 E,F VCL-20 13G13 E,F A/
630 VL-20H13D06 H VCL-20H13D06 H
1250 VL-20H13D13 H VCL-20H13D13 H
630 VL-20 16B06 G,K,H VCL-20 16B06 G,K,H G,K:A/ , H:
1250 VL-20 16B13 G,K,H VCL-20 16B13 G,K,H G,K:A/ , H:
630 VL-20 16F06 P,E,F,G,K VCL-20 16F06 E,F,G,K A/
630 VL-20 16G06 E,F VCL-20 16G06 E,F A/
16
1250 VL-20 16F13 P,E,F,G,K VCL-20 16F13 E,F,G,K A/
1250 VL-20 16G13 E,F VCL-20 16G13 E,F A/
24 630 VL-20H16D06 H VCL-20H16D06 H
1250 VL-20H16D13 H VCL-20H16D13 H
630 VL-20 25B06 G,K,H VCL-20 25B06 G,K,H G,K:A/ , H:
1250 VL-20 25B13 G,K,H VCL-20 25B13 G,K,H G,K:A/ , H:
2000 VL-20 25B20 G,H VCL-20 25B20 G,H G:A/ , H:
630 VL-20 25F06 P,E,F,G,K VCL-20 25F06 E,F,G,K A/
630 VL-20 25G06 E,F VCL-20 25G06 E,F A/
1250 VL-20 25F13 P,E,F,G,K VCL-20 25F13 E,F,G,K A/
25 1250 VL-20 25G13 E,F VCL-20 25G13 E,F A/
2000 VL-20 25F20 P,E,F,K VCL-20 25F20 E,F,K A/
2000 VL-20 25G20 E,F VCL-20 25G20 E,F A/
630 VL-20H25D06 H VCL-20H25D06 H
1250 VL-20H25D13 H VCL-20H25D13 H
2000 VL-20H25D20 H VCL-20H25D20 H
2500 VL-20H25D25 H VCL-20H25D25-AS H
630 VL-25 13B06 G,K,H VCL-25 13B06 G,K,H G,K:A/ , H:
1250 VL-25 13B13 G,K,H VCL-25 13B13 G,K,H G,K:A/ , H:
630 VL-25 13F06 P,E,F,G,K VCL-25 13F06 E,F,G,K A/
630 VL-25 13G06 E,F VCL-25 13G06 E,F A/
12.5
1250 VL-25 13F13 P,E,F,G,K VCL-25 13F13 E,F,G,K A/
1250 VL-25 13G13 E,F VCL-25 13G13 E,F A/
630 VL-25H13D06 H VCL-25H13D06 H
1250 VL-25H13D13 H VCL-25H13D13 H
630 VL-25 16B06 G,K,H VCL-25 16B06 G,K,H G,K:A/ , H:
1250 VL-25 16B13 G,K,H VCL-25 16B13 G,K,H G,K:A/ , H:
630 VL-25 16F06 P,E,F,G,K VCL-25 16F06 E,F,G,K A/
630 VL-25 16G06 E,F VCL-25 16G06 E,F A/
16
1250 VL-25 16F13 P,E,F,G,K VCL-25 16F13 E,F,G,K A/
1250 VL-25 16G13 E,F VCL-25 16G13 E,F A/
25.8 630 VL-25H16D06 H VCL-25H16D06 H
1250 VL-25H16D13 H VCL-25H16D13 H
630 VL-25 25B06 G,K,H VCL-25 25B06 G,K,H G,K:A/ , H:
1250 VL-25 25B13 G,K,H VCL-25 25B13 G,K,H G,K:A/ , H:
2000 VL-25 25B20 G,H VCL-25 25B20 G,H G:A/ , H:
630 VL-25 25F06 P,E,F,G,K VCL-25 25F06 E,F,G,K A/
630 VL-25 25G06 E,F VCL-25 25G06 E,F A/
1250 VL-25 25F13 P,E,F,G,K VCL-25 25F13 E,F,G,K A/
25 1250 VL-25 25G13 E,F VCL-25 25G13 E,F A/
2000 VL-25 25F20 P,E,F,K VCL-25 25F20 E,F,K A/
2000 VL-25 25G20 E,F VCL-20 25G20 E,F A/
630 VL-25H25D06 H VCL-25H25D06 H
1250 VL-25H25D13 H VCL-25H25D13 H
2000 VL-25H25D20 H VCL-25H25D20 H
2500 VL-25H25D25 H VCL-25H25D25-AS H
630 VL-36 25D06 P,H VCL-36 25D06 H P:A/ , H:
1250 VL-36 25D13 P,H VCL-36 25D13 H P:A/ , H:
36 25
2000 VL-36 25D20 P,H VCL-36 25D20 H P:A/ , H:
2500 VL-36 25D25 P,H VCL-36 25D25 H P:A/ , H:
Note) 1. Ur Rated voltage 2. Isc Rated short-circuit current
3. Ir Rated normal current 4. p Phase distance
5. E,F and G types are cradles for MESG(Metal Enclosed Switchgear) and H type for MCSG(Metal Clad Switchgear)
6. For the partial replacement of 7.2kV 8/12.5kA VCB, in case of using the existing old type cradle and replacing breaker only,
please order type B (Compatible with existing breaker). Compatibille busbars are required for fixed version.
To replace VCB fully(breaker and cradle) please order type A for breaker and compatible cradle B.

43
Type of circuit breakers

7.2/12/17.5/24/25.8/36kV (VH-06/12/17/20/25/36)
Ur Isc Ir[A] VCB CRADLE
Connector
[kV] [kA] p 150 p 210 p 254 p 275 p 320 Type Version Type Version
VH-06 32A13 P,E,F,G VCH-06 32A13 E,F,G
1250 A/
LVB-06 -32L/12 P,E,F,G,G/T LCL-06 -32D/12 E,F,G,G/T
VH-06 32A20 P,E,F,G VCH-06 32A20 E,F,G
31.5 2000 A/
LVB-06 -32L/20 P,E,F,G,G/T LCL-06 -32D/20 E,F,G,G/T
VH-06 32B32 P,E,F,Fs,Gs,K,H VCH-06 32B32 E,F,Fs,Gs,K,H P,E,F,K:A/ ,
3150
LVB-06 -32L/30 P,E,F,G/T LCL-06 -32D/30 E,F,G,G/T Fs,Gs,H:
VH-06 40A13 P,E,F,Fs,G,Gs,K,H VCH-06 40A13 E,F,Fs,G,Gs,K,H P,E,F,Fs,G,
1250 1250
LVB-06 -40L/12 P,E,F,G,G/T LCL-06 -40D/12 E,F,G,G/T Gs,K:A/ ,H:
VH-06 40A20 P,E,F,Fs,G,Gs,K,H VCH-06 40A20 E,F,Fs,G,Gs,K,H P,E,F,Fs,G,
2000 2000
LVB-06 -40L/20 P,E,F,G,G/T LCL-06 -40D/20 E,F,G,G/T Gs,K:A/ ,H:
7.2 40 VH-06 40B32 P,E,F,Fs,G,Gs,K,H VCH-06 40B32 E,F,Fs,G,Gs,K,H P,E,F,G,K:A/
3150
LVB-06 -40L/30 P,E,F,G/T LCL-06 -40D/30 E,F,G,G/T Fs,Gs,H:
3150 VH-06 40D32 K,H VCH-06 40D32 K,H K:A/ ,H:
4000 VH-06 40D40 P,K,H VCH-06 40D40 K,Ha,Hb
5000 VH-06H40L50 H VCH-06Ha40L50 Ha
1250 VH-06 50B13 P,H VCH-06H50B13 H
2000 VH-06 50B20 P,H VCH-06H50B20 H
2500 VH-06 50D25 P,H VCH-06H50D25 H
50
3150 VH-06 50D32 P,H VCH-06H50D32 H
4000 VH-06 50D40 P,K,H VCH-06 50D40 K,Ha,Hb
5000 VH-06H50L50 H VCH-06Ha50L50 Ha
1250 1250 LVB-12G-32L/12-T2 G/T LCL-12G-32D/12-T2 G/T A/
2000 LVB-12G-32L/20-T2 G/T LCL-12G-32D/20-T2 G/T A/
31.5
VH-12 32B32 Gs,K,H VCH-12 32B32 Gs,K,H K:A/ ,Gs,H:
3150
LVB-12G-32L/30-T2 G/T LCL-12G-32D/30-T2 G/T A/
VH-12 40A(K)13 Gs,K,H VCH-12 40A(K)13 Gs,K,H Gs,K:A/ ,H:
1250 1250
LVB-12G-40L/12-T2 G/T LCL-12G-40D/12-T2 G/T A/
VH-12 40A(K)20 Gs,K,H VCH-12 40A(K)20 Gs,K,H K:A/ ,Gs,H:
2000 2000
LVB-12G-40L/20-T2 G/T LCL-12G-40D/20-T2 G/T A/
1250 VH-12 40B13 K,H VCH-12 40B13 K,H
40 2000 VH-12 40B20 K,H VCH-12 40B20 K,H
12 VH-12 40B32 Gs,K,H VCH-12 40B32 Gs,K,H K:A/ ,Gs,H:
3150
LVB-12G-40L/30-T2 G/T LCL-12G-40D/30-T2 G/T A/
3150 VH-12H40D32 H VCH-12H40D32 H
4000 VH-12 40D40 P,K,H VCH-12 40D40 K,Ha,Hb
5000 VH-12H40L50 H VCH-12Ha40L50 Ha
1250 VH-12 50B13 P,H VCH-12H50B13 H
2000 VH-12 50B20 P,H VCH-12H50B20 H
2500 VH-12 50D25 P,H VCH-12H50D25 H
50
3150 VH-12 50D32 P,H VCH-12H50D32 H
4000 VH-12 50D40 P,K,H VCH-12 50D40 K,Ha,Hb
5000 VH-12H50L50 H VCH-12Ha50L50 Ha
3150 VH-17H32B32 H VCH-17H32B32 H
31.5
3150 VH-17H32D32 H VCH-17H32D32 H
1250 VH-17 40B13 K,H VCH-17 40B13 K,H K:A/ ,H:
2000 VH-17 40B20 K,H VCH-17 40B20 K,H K:A/ ,H:
17.5
3150 VH-17H40B32 H VCH-17H40B32 H
40
3150 VH-17K40C32 K VCH-17K40C32 K A/
3150 VH-17H40D32 H VCH-17H40D32 H
4000 VH-17 40D40 P,K,H VCH-17 40D40 Ha,Hb

44
Susol VCB

Ur Isc Ir[A] VCB CRADLE


Connector
[kV] [kA] p 150 p 210 p 275 p 300 Type Version Type Version
1250 VH-17 50B13 P,H VCH-17H50B13 H
2000 VH-17 50B20 P,H VCH-17H50B20 H
17.5 50 2500 VH-17 50D25 P,H VCH-17H50D25 H
3150 VH-17 50D32 P,H VCH-17H50D32 H
4000 VH-17 50D40 P,H VCH-17 50D40 Ha,Hb
25 2500 VH-20 25D25 P,H VCH-20H25D25 H
VCH-20H32B13 H
1250 VH-20 32B13 P,H
VCH-20H32F13 H
VCH-20H32B20 H
2000 VH-20 32B20 P,H
31.5 VCH-20H32F20 H
1250 VH-20 32D13 P,H VCH-20H32D13 H
2000 VH-20 32D20 P,H VCH-20H32D20 H
24 3150 VH-20 32D32 P,H VCH-20H32D32 H
VCH-20H40B13 H
1250 VH-20 40B13 P,H
VCH-20H40F13 H
VCH-20H40B20 H
2000 VH-20 40B20 P,H
40 VCH-20H40F20 H
1250 VH-20 40D13 P,H VCH-20H40D13 H
2000 VH-20 40D20 P,H VCH-20H40D20 H
3150 VH-20 40D32 P,H VCH-20H40D32 H
25 2500 VH-25 25D25 P,H VCH-25H25D25 H
VCH-25H32B13 H
1250 VH-25 32B13 P,H
VCH-25H32F13 H
VCH-25H32B20 H
2000 VH-25 32B20 P,H
31.5 VCH-25H32F20 H
1250 VH-25 32D13 P,H VCH-25H32D13 H
2000 VH-25 32D20 P,H VCH-25H32D20 H
25.8 3150 VH-25 32D32 P,H VCH-25H32D32 H
VCH-25H40B13 H
1250 VH-25 40B13 P,H
VCH-25H40F13 H
VCH-25H40B20 H
2000 VH-25 40B20 P,H
40 VCH-25H40F20 H
1250 VH-25 40D13 P,H VCH-25H40D13 H
2000 VH-25 40D20 P,H VCH-25H40D20 H
3150 VH-25 40D32 P,H VCH-25H40D32 H
1250 VH-36 25E13 P,H VCH-36H25E13 H
25 2000 VH-36 25E20 P,H VCH-36H25E20 H
3150 VH-36 25E32 P,H VCH-36H25E32 H
1250 VH-36 32E13 P,H VCH-36H32E13 H
36 31.5 2000 VH-36 32E20 P,H VCH-36H32E20 H
3150 VH-36 32E32 P,H VCH-36H32E32 H
1250 VH-36 40E13 P,H VCH-36H40E13 H
40 2000 VH-36 40E20 P,H VCH-36H40E20 H
3150 VH-36 40E32 P,H VCH-36H40E32 H

Note) 1. Ur Rated voltage


2. Isc Rated short-circuit current
3. Ir Rated normal current
4. p Phase distance
5. H type is MCSG style drawable type with a box type cradle for CB compartment construction.
6. G/T types are MCSG style drawable types with a cradle for builting in the switchgear , not a box type. (K of VCL type name indicates 4000A)
Example of G/T type : LVB-06G-32L/12-T2, LCL-06G-32D/12-T2
7. G/T types use LVB and LCL names.
8. E, F and G types provide cradles for MESG(Metal Enclosed Switchgear) and H, G/T types for MCSG(Metal Clad Switchgear).
9. In case of 7.2/12kV, 31.5kA/40kA H type: Please contact us.

45
Ratings - 7.2kV 8/12.5kA 400/630A

VL-06

Item V V 1
Rated voltage Ur (kV) 7.2
Rated normal current Ir (A) 400 630
Rated frequency fr (Hz) 50/60
Rated short-circuit current Isc (kA) 8 12.5
Rated short-time withstand current Ik/tk (kA/s) 8/3 12.5/3
Rated short-circuit breaking capacity (MVA) 100 160
Rated short-circuit making current Ip (kA) 2.5 Isc (50Hz)/2.6 Isc (60Hz)
Rated breaking time (cycle) 3

Rated withstand Power frequency (1 min) Ud (kV) 20


voltage Impulse (1.2 50 ) Up (kV) 60
Rated operating sequence O-0.3s-CO-15s-CO
Control voltage Closing coil (V) AC/DC 100~130, AC/DC 200~250, DC 125, DC 24~30, DC 48~60, AC 48
Trip coil (V) AC/DC 100~130, AC/DC 200~250, DC 125, DC 24~30, DC 48~60, AC 48
Auxiliary contacts 2a2b, 4a4b, 6a6b
Rated opening time (sec) 0.04
No-load closing time (sec) 0.06
Type test class Mechanical M2
Electrical E2 (List 1)
Capacitive current switching C2

Installation Fixed P type


version Drawout E, F, G type (for MESG)
Phase distance (mm) 130
Weight Breaker (E, F, G type) (kg) 37 37
Cradle (E, F, G type) (kg) 18, 25, 32 19, 26, 33
Dimensions Breaker (E, F, G type) Page 97~98
Cradle (E, F, G type) Page 98~99
Standards IEC 62271-100, EC 2300/ IS C 4603, V-check(KESCO)

46
Ratings - 7.2/12/17.5kV 20/25kA 630/1250/2000A Susol VCB

VL-06/12/17

Item V 2 2 1 2 V 12 2 2 1 2 V 1 2 2 1 2
Rated voltage Ur (kV) 7.2 12 17.5
Rated normal current Ir (A) 630 1250 2000 630 1250 2000 630 1250 2000
Rated frequency fr (Hz) 50/60
Rated short-circuit current Isc (kA) 20, 25
Rated short-time withstand current Ik/tk (kA/s) 20/3, 25/3
Rated short-circuit breaking capacity (MVA) 250/310 410/520 600/750
Rated short-circuit making current Ip (kA) 2.5 Isc (50Hz)/2.6 Isc (60Hz)
Rated breaking time (cycle) 3

Rated withstand Power frequency (1 min) Ud (kV) 20 28 38


voltage Impulse (1.2 50 ) Up (kV) 60 75 95
Rated operating sequence O-0.3s-CO-15s-CO
Control voltage Closing coil (V) DC 24~30, DC 48~60, DC 110, DC 125, DC 220~250, AC 48, AC 100~130, AC 220~250
Trip coil (V) DC 24~30, DC 48~60, DC 110, DC 125, DC 220~250, AC 48, AC 100~130, AC 220~250
Auxiliary contacts 4a4b, 10a10b
Rated opening time (sec) 0.04
No-load closing time (sec) 0.06
Type test class Mechanical M2
Electrical E2 (List 3)
Capacitive current switching C2
Installation Fixed P type
version *
Drawout E, F, G type (for MESG), H type (for MCSG) E, F type (for MESG), H type (for MCSG)
Phase distance ** (mm) 150 150 (210) 150 (210)
Weight Breaker (E, F, G, K type) (kg) 100 100 130 115 (120) 115 (120) 130 (140) 115 (120) 115 (120) 130 (140)
Cradle (E, F, G, K type) (kg) 170 170 180 170 (200) 115 (120) 180 (200) 170 (200) 170 (200) 180 (200)
Dimensions Breaker (P, E, F, G, K, H type) Page 100~111 Page 100~111 Page 100~111
Cradle (E, F, G, K type) Page 100~111 Page 100~111 Page 100~111
Cradle (K, H type) Page 100~111 Page 100~111 Page 100~111
Standards IEC 62271-100, KERI/KEMA, V-check(KESCO)

* H type is a box type cradle with CB compartment style structure.


** ( ) displays option of phase distance.

47
Ratings - 7.2/12/17.5kV 31.5kA 630/1250/2000/2500A

VL-06/12/17

Item V 2 1 2 V 12 2 1 2 2 V 1 2 1 2 2
Rated voltage Ur (kV) 7.2 12 17.5
Rated normal current Ir (A) 630 1250 2000 630 1250 2000 2500 630 1250 2000 2500
Rated frequency fr (Hz) 50/60
Rated short-circuit current Isc (kA) 31.5
Rated short-time withstand current Ik/tk (kA/s) 31.5/3(4 Note1))
Rated short-circuit breaking capacity (MVA) 393 655 955
Rated short-circuit making current Ip (kA) 2.5 Isc (50Hz)/2.6 Isc (60Hz)
Rated breaking time (cycle) 3

Rated withstand Power frequency (1 min) Ud (kV) 20 28 38


voltage Impulse (1.2 50 ) Up (kV) 60 75 95
Rated operating sequence O-0.3s-CO-15s-CO
Control voltage Closing coil (V) DC 24~30, DC 48~60, DC 110, DC 125, DC 220~250, AC 48, AC 100~130, AC 220~250
Trip coil (V) DC 24~30, DC 48~60, DC 110, DC 125, DC 220~250, AC 48, AC 100~130, AC 220~250
Auxiliary contacts 4a4b, 10a10b
Rated opening time (sec) 0.04
No-load closing time (sec) 0.06
Type test class Mechanical M2
Electrical E2 (List 3)
Capacitive current switching C2
Installation Fixed P type P type P type
version *
H type E, F, Fs, G, Gs, K type H type Gs, K type
H type
Drawout (for MESG) (for MESG) H type (for MCSG)
(for MCSG) H type (for MCSG) (for MCSG) H type (for MCSG) (for MCSG)

Phase distance ** (mm) 150 150 (210) 210 (275) 150 (210) 210 (275
Weight Breaker (H type) (kg) 100 100 130 115/120 115/120 130/140 160/175 115/120 115/120 130/140 160/175
Cradle (H type) (kg) 170 170 200 170/200 170/200 170/200 260/290 170/200 170/200 170/200 260/290
Breaker (P, E, F, G, K type) (kg) 85 85 100 85/100 85/100 100/115 120/135 85/100 85/100 100/115 120/135
Dimensions Breaker (P, E, F, Fs, G, Gs, K, H type) Page 112~128 Page 129~161
Cradle (E, F, Fs, G, Gs, K, H type) Page 112~128 Page 129~161
Standards IEC 62271-100, KERI, V-check(KESCO)

* H type is a box type cradle with CB compartment style structure.


** ( ) displays option of phase distance.
Note1) For Icw 4s, please contact us..

48
Ratings - 24/25.8kV 12.5/16/25kA 630/1250/2000/2500A Susol VCB

VL-20/25

Item V 2 ,2 1 1 V 2 ,2 1 1 V 2 ,2 2 1 2 2
Rated voltage Ur (kV) 24/25.8
Rated normal current Ir (A) 630 1250 630 1250 630 1250 2000 2500
Rated frequency fr (Hz) 50/60
Rated short-circuit current Isc (kA) 12.5 16 25
Rated short-time withstand current Ik/tk (kA/s) 12.5/3 Note2) 16/3 Note2 25/3 Note2
Rated short-circuit breaking capacity (MVA) 520/560 665/715 1040/1120
Rated short-circuit making current Ip (kA) 2.5 Isc (50Hz)/2.6 Isc (60Hz)
Rated breaking time (cycle) 3

Rated withstand Power frequency (1 min) Ud (kV) 50/60


voltage Impulse (1.2 50 ) Up (kV) 125
Rated operating sequence O-0.3s-CO-15s-CO
Control voltage Closing coil (V) DC 24~30, DC 48~60, DC 110, DC 125, DC 220~250, AC 48, AC 100~130, AC 220~250
Trip coil (V) DC 24~30, DC 48~60, DC 110, DC 125, DC 220~250, AC 48, AC 100~130, AC 220~250
Auxiliary contacts 4a4b, 10a10b
Rated opening time (sec) 0.04
No-load closing time (sec) 0.06
Type test class Mechanical M2
Electrical E2 (List 3)
Capacitive current switching C2
Installation Fixed P type -
version *
Drawout E,F,G type (for MESG) / K, H type (for MCSG) H type (for MCSG)
Phase distance ** (mm) 210/265/275 275
Weight Breaker (H type) (kg) 120 (130) 130 (140) 150 (160)
Cradle (H type) (kg) 200 (220) 220 (250)
Breaker (P, E, F, G, K type) (kg) 110 115 120 135 -
Dimensions Breaker (P, E, F, G, K, H type) Page 162~171 Page 172~178 Page 178~182
Cradle (E, F, G, K type) Page 183~185 Page 183~185 Page 183~185
Cradle (H type) Page 186~190 Page 186~190 Page 186~190
Standards IEC 62271-100, KERI, V-check(KESCO)

* H type is a box type cradle with CB compartment style structure.


** ( ) displays option of phase distance.
Note 1) 24/25.8kV 25kA 2000A(Phase distance 210mm): 60Hz available only
2) For Icw 4s, please contact us..

49
Ratings - 36kV 25kA 630/1250/2000/2500A

VL-36

Item V 2 V 2 1 V 2 2 V 2 2
Rated voltage Ur (kV) 36

Rated normal current Ir (A) 630 1250 2000 2500

Rated frequency fr (Hz) 50/60

Rated short-circuit current Isc (kA) 25

Rated short-time withstand current Ik/tk (kA/s) 25/3(4 Note1))

Rated short-circuit breaking capacity (MVA) 1560

Rated short-circuit making current Ip (kA) 62.5/65

Rated breaking time (cycle) 3

Rated withstand Power frequency (1 min) Ud (kV) 70


voltage Impulse (1.2 50 ) Up (kV) 170

Rated operating sequence O-0.3s-CO-15s-CO

Control voltage Closing coil (V) DC 24~30, DC 48~60, DC 110, DC 125, DC 220~250, AC 48, AC 100~130, AC 220~250

Trip coil (V) DC 24~30, DC 48~60, DC 110, DC 125, DC 220~250, AC 48, AC 100~130, AC 220~250

Auxiliary contacts 4a4b, 10a10b

Rated opening time (sec) 0.04

No-load closing time (sec) 0.07

Type test class Mechanical M2

Electrical E2 (List 3)

Capacitive current switching C2

Installation Fixed P type


version
Drawout H type (for MCSG)

Phase distance (mm) 275

Weight Breaker (H type) (kg) 260 260 280 300

Cradle (H type) (kg) 440 440 450 460

Dimensions Breaker (H type) Page 191~196

Cradle (H type) Page 191~196

Standards IEC 62271-100

Note1) For Icw 4s, please contact us.

50
Ratings - 7.2/12kV 31.5/40kA 1250/2000/3150A Susol VCB

LVB-06/12

Item VB 2 2 VB 12, 2 , 2 VB 12 2 2 VB 12 12, 2 , 2


Rated voltage Ur (kV) 7.2 7.2 12 12

Rated normal current Ir (A) 3150 * 1250 2000 3150 * 3150 * 1250 2000 3150 *

Rated frequency fr (Hz) 50/60

Rated short-circuit current Isc (kA) 31.5 40 31.5 40

Rated short-time withstand current Ik/tk (kA/s) 31.5/3 40/3 31.5/3 40/3

Rated short-circuit breaking capacity (MVA) 393 499 655 831

Rated short-circuit making current Ip (kA) 2.5 Isc (50 )/2.6 Isc (60 )

Rated breaking time (cycle) 3

Rated withstand Power frequency (1 min) Ud (kV) 20 28


voltage Impulse (1.2 50 ) Up (kV) 60 75

Rated operating sequence O-0.3s-CO-3min-CO

Control voltage Closing coil (V) DC 48, DC 110, DC 125, DC 220~250, AC 48, AC 110, AC 220

Trip coil (V) DC 48, DC 110, DC 125, DC 220~250, AC 48, AC 110, AC 220

Auxiliary contacts 4a4b, 10a10b

Rated opening time (sec) 0.04

No-load closing time (sec) 0.06

Type test class Mechanical M2

Electrical E2 (List 3)

Capacitive current switching C2

Installation Fixed P type -


version
Drawout * E,F,G type (for MESG), MCSG Cradle MCSG Cradle

Phase distance (mm) 210 150 210 210 150 210

Weight Breaker (MESG, MCSG) (kg) 210, 220 135, 160 135, 160 210, 220 220 164 165 220

Cradle (MESG, MCSG) (kg) 135, 155 55, 110 63, 117 135, 155 155 110 117 155

Dimensions reaker (MESG, MCSG) Page 201~202 Page 197~198 Page 201~202 Page 201~202 Page 197~198 Page 201~202

Cradle (MESG, MCSG) Page 203~204 Page 199~200 Page 203~204 Page 203~204 Page 199~200 Page 203~204

Standards IEC 62271-100

* MCSG style drawable type provide a cradle for builting in the switchgear, not a box type for CB compartment. Ordering type is LVB.
Note 1) H type that is a box type cradle for enabling a CB compartment in MCSG is under development. Consult us for ordering.
2) Some LVB is the ordering name of the switchboard for export

51
Ratings - 7.2/12/17.5kV 40kA 1250/2000A

VH-06/12/17

Item V 12 1 2 V 12 1 1 2
Rated voltage Ur (kV) 7.2 12 7.2 12 17.5

Rated normal current Ir (A) 1250 2000 1250 2000 1250 2000 1250 2000 1250 2000

Rated frequency fr (Hz) 50/60

Rated short-circuit current Isc (kA) 40

Rated short-time withstand current Ik/tk (kA/s) 40/4

Rated short-circuit breaking capacity (MVA) 499 831 499 831 1212

Rated short-circuit making current Ip (kA) 2.5 Isc (50Hz)/2.6 Isc (60Hz)

Rated breaking time (cycle) 3

Rated withstand Power frequency (1 min) Ud (kV) 20 28 (42) 20 28 (42) 38


voltage Impulse (1.2 50 ) Up (kV) 60 75 60 75 95

Rated operating sequence O-0.3s-CO-3min-CO O-0.3s-CO-15s-CO

Control voltage Closing coil (V) DC 48, DC 110, DC 125, DC 220~250, AC 48, AC 110, AC 220

Trip coil (V) DC 48, DC 110, DC 125, DC 220~250, AC 48, AC 110, AC 220

Auxiliary contacts 4a4b, 10a10b

Rated opening time (sec) 0.04

No-load closing time (sec) 0.06

Type test class Mechanical M2

Electrical E2 (List 3)

Capacitive current switching C2

Installation version Drawout Fs, Gs, K, H type K, H type

Phase distance (mm) 150 210

Weight Breaker (H type) (kg) 165 215

Cradle (H type) (kg) 205 226

Dimensions Breaker (Fs, Gs, K, H type) Page 208~223 Page 208~223

Cradle (Fs, Gs, K, H type) Page 208~223 Page 208~223

Standards IEC 62271-100

52
Ratings - 7.2/12/17.5kV 31.5/40kA 3150A Susol VCB

VH-06/12/17

Item V 12 1 2 2
Rated voltage Ur (kV) 7.2 12 17.5

Rated normal current Ir (A) 3150

Rated frequency fr (Hz) 50/60

Rated short-circuit current Isc (kA) 31.5/40

Rated short-time withstand current Ik/tk (kA/s) 40/4

Rated short-circuit breaking capacity (MVA) 393/499 655/831 955/1212

Rated short-circuit making current Ip (kA) 2.5 Isc (50Hz)/2.6 Isc (60Hz)

Rated breaking time (cycle) 3

Rated withstand Power frequency (1 min) Ud (kV) 20 28 (42) 38


voltage Impulse (1.2 50 ) Up (kV) 60 75 95

Rated operating sequence O-0.3s-CO-15s-CO

Control voltage Closing coil (V) DC 48, DC 110, DC 125, DC 220~250, AC 48, AC 110, AC 220

Trip coil (V) DC 48, DC 110, DC 125, DC 220~250, AC 48, AC 110, AC 220

Auxiliary contacts 4a4b, 10a10b

Rated opening time (sec) 0.04

No-load closing time (sec) 0.06

Type test class Mechanical M2

Electrical E2 (List 3)

Capacitive current switching C2

Installation version Drawout Fs, Gs, K, H type Gs, K, H type K, H type K type K type

Phase distance (mm) 210 210 210 254 275

Weight Breaker (H type) (kg) 240 240 240 280 280

Cradle (H type) (kg) 235 235 235 250 250

Dimensions Breaker (H type) Page 208~223

Cradle (H type) Page 208~223

Standards IEC 62271-100

53
Ratings - 7.2/12/17.5kV 50kA 1250/2000/2500/3150A

VH-06/12/17

Item VH-06□50□13/20/25/32 VH-12□50□13/20/25/32 VH-17□50□13/20/25/32


Rated voltage Ur (kV) 7.2 12 17.5
Rated normal current Ir (A) 1250 2000 2500 3150 1250 2000 2500 3150 1250 2000 2500 3150
Rated frequency fr (Hz) 50/60
Rated short-circuit current Isc (kA) 50
Rated short-time withstand current Ik/tk (kA/s) 50/3
Rated short-circuit breaking capacity (MVA) 623 1039 1515
Rated short-circuit making current Ip (kA) 2.5×Isc (50Hz)/2.6×Isc (60Hz)
Rated breaking time (cycle) 3

Rated withstand Power frequency (1 min) Ud (kV) 20 28 (42) Note1) 38


voltage Impulse (1.2×50㎲) Up (kV) 60 75 95
Rated operating sequence O-0.3s-CO-15s-CO / O-0.3s-CO-3min-CO
Control voltage Closing coil (V) DC 48, DC 110, DC 125, DC 220~250, AC 48, AC 110, AC 220
Trip coil (V) DC 48, DC 110, DC 125, DC 220~250, AC 48, AC 110, AC 220
Auxiliary contacts 4a4b, 10a10b
Rated opening time (sec) ≤ 0.04
No-load closing time (sec) ≤ 0.06
Type test class Mechanical M2
Electrical E2 (List 3)
Capacitive current switching C2
Installation Fixed P type
version *
Drawout H type (for MCSG)
Phase distance (mm) 210 275 210 275 210 275
Weight Breaker (H type) (kg) 230 287 290 230 287 290 230 287 290
Cradle (H type) (kg) 175 320 320 175 320 320 175 320 320
Dimensions Breaker (H type) Page 224 Page 226 Page 224 Page 226 Page 224 Page 226
Cradle (H type) Page 225 Page 227 Page 225 Page 227 Page 225 Page 227
Standards IEC 62271-100, KERI/KEMA, V-check(KESCO)

* H type is a box type cradle with CB compartment style structure.


Note1) Contact us.

54
Ratings - 7.2/12/17kV 40/50kA 4000A Susol VCB

VH-06/12/17

Item V 12 1 V 12 1
Rated voltage Ur (kV) 7.2 12 17.5 7.2 12 17.5
Rated normal current Ir (A) 4000
Rated frequency fr (Hz) 50/60
Rated short-circuit current Isc (kA) 40 50
Rated short-time withstand current Ik/tk (kA/s) 40/4 50/4
Rated short-circuit breaking capacity (MVA) 499 831 1212 624 1040 1515
Rated short-circuit making current Ip (kA) 104 130
Rated breaking time (cycle) 3

Rated withstand Power frequency (1 min) Ud (kV) 20 28(42) 38 20 28(42) 38


voltage Impulse (1.2 50 ) Up (kV) 60 75 95 60 75 95
Rated operating sequence O-0.3s-CO-15s-CO
Control voltage Closing coil (V) DC 48, DC 110, DC 125, DC 220~250, AC 48, AC 110, AC 220~250
Trip coil (V) DC 48, DC 110, DC 125, DC 220~250, AC 48, AC 110, AC 220~250
Auxiliary contacts 4a4b, 10a10b
Rated opening time (sec) 0.04
No-load closing time (sec) 0.06
Type test class Mechanical M2
Electrical E2 (List 1)
Capacitive current switching C2
Installation Fixed - - P type - - P type
version
Drawout H type H type H type H type H type H type
Phase distance (mm) 275
Weight Breaker (H type) (kg) 395
Cradle (H type) (kg) 200
Dimensions Breaker (Fs, Gs, K, H type) Page 228~233
Cradle (Fs, Gs, K, H type) Page 228~233
Standards IEC 62271-100

55
Ratings - 7.2/12kV 40/50kA 5000A

VH-06/12

Item V , V 12 ,
Rated voltage Ur (kV) 7.2 12

Rated normal current Ir (A) 5000

Rated frequency fr (Hz) 50/60

Rated short-circuit current Isc (kA) 40/50

Rated short-time withstand current Ik/tk (kA/s) 50/4

Rated short-circuit breaking capacity (MVA) 624 1040

Rated short-circuit making current Ip (kA) 130

Rated breaking time (cycle) 3

Rated withstand Power frequency (1 min) Ud (kV) 20 20


voltage Impulse (1.2 50 ) Up (kV) 60 75

Rated operating sequence O-0.3s-CO-15s-CO

Control voltage Closing coil (V) DC 48, DC 110, DC 125, DC 220~250, AC 48, AC 110, AC 220~250

Trip coil (V) DC 48, DC 110, DC 125, DC 220~250, AC 48, AC 110, AC 220~250

Auxiliary contacts 4a4b, 10a10b

Rated opening time (sec) 0.04

No-load closing time (sec) 0.06

Type test class Mechanical M2

Electrical E2 (List 1)

Capacitive current switching C2

Installation version Drawout H type (for MCSG)

Phase distance (mm) 320

Weight Breaker (H type) (kg) 430

Cradle (H type) (kg) 200

Dimensions Breaker (H type) Page 232~233

Cradle (H type) Page 232~233

Standards IEC 62271-100

56
Ratings - 24/25.8kV 25/31.5/40kA 1250/2000/2500/3150A Susol VCB

VH-20/25

Item V 2 ,2 2 2 V 2 ,2 2 1 2 2 V 2 ,2 1 2 2
Rated voltage Ur (kV) 24/25.8
Rated normal current Ir (A) 2500 1250 2000 3150 1250 2000 3150
Rated frequency *** fr (Hz) 50/60 60 50/60
Rated short-circuit current Isc (kA) 25 31.5 40
Rated short-time withstand current Ik/tk (kA/s) 25/3 31.5/3 40/3
Rated short-circuit breaking capacity (MVA) 1039/1117 1309/1407 1662/1787
Rated short-circuit making current Ip (kA) 2.5 Isc (50Hz)/2.6 Isc (60Hz) 2.6 Isc (60Hz) 2.5 Isc (50Hz)/2.6 Isc (60Hz)
Rated breaking time (cycle) 3

Rated withstand Power frequency (1 min) Ud (kV) 50 (65) Note1)


voltage Impulse (1.2 50 ) Up (kV) 125
Rated operating sequence **** O-0.3s-CO-15s-CO / O-0.3s-CO-3min-CO
Control voltage Closing coil (V) DC 48, DC 110, DC 125, DC 220~250, AC 48, AC 110, AC 220
Trip coil (V) DC 48, DC 110, DC 125, DC 220~250, AC 48, AC 110, AC 220
Auxiliary contacts 4a4b, 10a10b
Rated opening time (sec) 0.04
No-load closing time (sec) 0.06
Type test class Mechanical M2
Electrical E2 (List 3)
Capacitive current switching C2
Installation Fixed P type
version *
Drawout H type (for MCSG)
Phase distance ** (mm) 275 210 (275) 210 (275) 275 210 (275) 210 (275) 275
Weight Breaker (H type) (kg) 295 256 (273) 256 (273) 318 256 (273) 256 (273) 318
Cradle (H type) (kg) 316 257 (284) 257 (284) 316 257 (284) 257 (284) 316
Dimensions Breaker (H type) Page 234 Page 236~239 Page 241 Page 236~239 Page 241
Cradle (H type) Page 235 Page 237, 240 Page 242 Page 237, 240 Page 242
Standards IEC 62271-100, KERI/KEMA, V-check(KESCO)

* H type is a box type cradle with CB compartment style structure.


** ( ) displays option of phase distance.
*** Rated frequency(fr) 50Hz is certified only to 24kV.
**** Rated operating sequence O-0.3s-CO-15s-CO is certified only to 24kV 40kA.
Note1) Contact us.

57
Ratings - 36kV 25/31.5/40kA 1250/2000/3150A

VH-36

Item V 2 1 2 2 V 2 1 2 2 V 1 2 2
Rated voltage Ur (kV) 36
Rated normal current Ir (A) 1250 2000 3150 1250 2000 3150 1250 2000 3150
Rated frequency fr (Hz) 50/60
Rated short-circuit current Isc (kA) 25 31.5 40
Rated short-time withstand current Ik/tk (kA/s) 25/3 31.5/3 40/3
Rated short-circuit breaking capacity (MVA) 1559 1964 2494
Rated short-circuit making current Ip (kA) 2.5 Isc (50Hz)/2.6 Isc (60Hz)
Rated breaking time (cycle) 3

Rated withstand Power frequency (1 min) Ud (kV) 70 (95) Note1


voltage Impulse (1.2 50 ) Up (kV) 170
Rated operating sequence O-0.3s-CO-3min-CO
Control voltage Closing coil (V) DC 48, DC 110, DC 125, DC 220~250, AC 48, AC 110, AC 220
Trip coil (V) DC 48, DC 110, DC 125, DC 220~250, AC 48, AC 110, AC 220
Auxiliary contacts 4a4b, 10a10b
Rated opening time (sec) 0.04
No-load closing time (sec) 0.06
Type test class Mechanical M2
Electrical E2 (List 3)
Capacitive current switching C2
Installation Fixed P type
version *
Drawout H type (for MCSG)
Phase distance (mm) 300
Weight Breaker (H type) (kg) 400 490 400 490 400 490
Cradle (H type) (kg) 700 750 700 750 700 750
Dimensions Breaker (H type) Page 243 Page 245 Page 243 Page 245 Page 243 Page 245

Cradle (H type) Page 244 Page 246 Page 244 Page 246 Page 244 Page 246
Standards IEC 62271-100, KERI/KEMA, V-check(KESCO)

* H type is a box type cradle with CB compartment style structure.


Note1) Contact us.

58
Accessories Susol VCB

Supplied as
Mounting
Type Accessory VL: 7.2kV Remarks page
Position VL: 20/25kA VH
8/12.5kA

M Motor Attached at the factory 61


CC Closing Coil Attached at the factory 62
TC Trip Coil Attached at the factory 63
A1 Secondary Trip Coil Option Option Option Attached at the factory 64
A2 Secondary Trip Coil with TCM Contact - Option Option Attached at the factory 64, 80
T9 Current Trip Coil Option Option - Attached at the factory 65
Auxiliary Contact 2a2b - -

SA Auxiliary Contact 4a4b Option


Attached at the factory 66
(S ) Auxiliary Contact 6a6b Option - -
Auxiliary Contact 10a10b - Option Option
U Under Voltage Trip Coil Option Option Option Attached at the factory 67
A3 Position S/W(Test: 1a1b, Service: 2b) Option Option Option Attached at the factory 68
A4 Position S/W(Test: 2a, Service: 2a) Option Option Option Attached at the factory 68
A5 Position S/W(Test: 1a1b, Service: 1a1b) Option Option Option Attached at the factory 68
Breaker
(Internal) A6 Latch Checking Switch - - Option Attached at the factory 69
C Counter Attached at the factory 69
A7 Keylock Option Option Option Attached at the factory 70
A8 Button Padlock Option Option Option Attached at the factory 71
A9 Button cover Option Option Option Attached at the factory 72
AA Lead Wire: A/ type connector Option Option Option Attached at the factory 73
AB Plug/Terminal for Lead Wire Option Option Option Attached at the factory 73
AC Plug Interlock - Option Option Attached at the factory 77
AD Padlock (H type) - Option Option Attached at the factory 77
AE MOC(Mechanical Operated Cell Switch - Option Option Attached at the factory 78
AF Locking Magnet - Option Option Attached at the factory 79
A Door Interlock - Option Option Attached at the factory 89

Lead Wire: A type connector


AO Option Option - Attached at the factory 91
(Special Color: Blue)

Trip Coil Monitoring Contact Attached at the factory 80


CTD1 Condenser Trip Device(AC110V) Option Option Option - 82
CTD2 Condenser Trip Device(AC220V) Option Option Option - 82
UDC1 UVT Time Delay Controller(AD110V) Option Option Option - 83
Breaker
UDC2 UVT Time Delay Controller(AD220V) Option Option Option - 83
(External)
UDC3 UVT Time Delay Controller(AD48V) Option Option Option - 83
CTU Coil Test Unit Option Option Option - 81
TM Temperature Monitoring - Option Option - 84
* : Basic Installation

59
Accessories

Supplied as
Mounting
Type Accessory VL: 7.2kV Remarks page
Position VL: 20/25kA VH
8/12.5kA

A1 ES(Earthing Switch) without Option - Option Option Attached at the factory 85

ES(Earthing Switch)
A2 - Option Option Attached at the factory 85
with Position Switch(2a2b)

ES(Earthing Switch)
A4 - Option Option Attached at the factory 85
with Position Switch(6a6b)

A5 Keylock for ES(Earthing Switch) - Option Option Attached at the factory 86

Locking magnet(DC110V)
A6 - Option Option Attached at the factory 86
for ES(Earthing Switch)

Locking magnet(DC220V)
A7 - Option Option Attached at the factory 86
for ES(Earthing Switch)

Locking magnet(DC125V)
A8 - Option Option Attached at the factory 86
for ES(Earthing Switch)

Locking magnet(DC24V)
A9 - Option Option Attached at the factory 86
for ES(Earthing Switch)

Locking magnet(DC48V)
AA - Option Option Attached at the factory 86
for ES(Earthing Switch)

Locking magnet(AC48V)
AB - Option Option Attached at the factory 86
Cradle for ES(Earthing Switch)

Locking magnet(AC110V)
AC - Option Option Attached at the factory 86
for ES(Earthing Switch)

Locking magnet(AC220V)
AD - Option Option Attached at the factory 86
for ES(Earthing Switch)

AE Shutter padlock - Option Option Attached at the factory 87


AF TOC(Truck Operated Cell Switch) - Option Option Attached at the factory 87
AG MOC(Mechanical Operated Cell Switch) - Option Option Attached at the factory 86
AH Door - Option Option Attached at the factory 88
A Door Interlock - Option Option Attached at the factory 89
AK Door Emergency Push Button - Option Option Attached at the factory 89
AL Temperature Sensor - Option Option Attached at the factory 90
AM Type H Lead Wire 4a4b (Normal cable) - Option Option Attached at the factory 91

Type H Lead Wire 10a10b


AN - Option Option Attached at the factory 91
(Normal cable)

Type H Lead Wire 4a4b)


AO - Option Option Attached at the factory 91
(Flame retardant cable)
Door padlock - Option Option Attached at the factory 91

60
Susol VCB

Motor: M Installed inside of a breaker as standard

VL type Charge the closing spring of a circuit breaker


by the external power source. When the
charging is complete, control power of the
Motor motor will be OFF by the built-in Limit S/W.
Without the external power source, charge
manually.

Operating voltage range (IEC 60947)


Gear
85%~110%Vn

Main
shaft

Charge completion
contact Motor

Item VL Type
AC AC
Input voltage Vn DC 24 30V DC 48 60V DC 110V DC 125V DC 220V AC 48V
100 130V 200 250V
Load current (A) 5 3 1 1 05 3 1 05
Starting current (A) 5 times of load current
Charge time Within 5 sec.

Note) Rated operation and control voltage range, see page 65.

VH type

Motor

Item VH Type
Input voltage Vn DC 48V DC 110V DC 125V DC 220V AC 48V AC 110V AC 220V
Load current (A) 6 3 3 26 6 3 26
Starting current (A) 30 20 20 17 30 20 17
Charge time Within 12 sec.
Note) Rated operation and control voltage range, see page 65.

61
Accessories

Closing Coil: C Installed inside of a breaker as standard

VL type It is a control device which closes a circuit


breaker, when applying voltage continuously
or instantaneously over 200ms to the coil
control terminals.

Closing coil

Item VL Type
AC AC
Input voltage Vn DC 24 30V DC 48 60V DC 110V DC 125V DC 220V AC 48V
100 130V 200 250V
Power consumption (inrush, W) 200
Power consumption (steady, W) 5
Rated current A 10 5 4 2

Note) Rated operation and control voltage range, see page 65.

VH type It is a control device which closes a circuit


breaker, when applying voltage continuously
about 45ms to the coil control terminals.
Electrical pumping preventing circuit is built in.

Closing coil

Item VH Type
Input voltage (Vn) DC 48V DC 110V DC 125V DC 220V AC 48V AC 110V AC 220V
Rated current (A) 8 3 35 25 8 3 25

Note) Rated operation and control voltage range, see page 65.

62
Susol VCB

Trip Coil: T Installed inside of a breaker as standard

VL type It is a control device which trips a circuit breaker


from remote place, when applying voltage
continuously or instantaneously over 35ms to coil
control terminals.

When UVT coil is installed, its location is changed.

Trip coil

Item VL Type
AC AC
Input voltage Vn DC 24 30V DC 48 60V DC 110V DC 125V DC 220V AC 48V
100 130V 200 250V
Power consumption (inrush, W) 200
Power consumption (steady, W) 5
Rated current A 10 5 4 2

Note) Rated operation and control voltage range, see page 65.

VH type It is a control device which trips a circuit


breaker, when applying voltage continuously
or instantaneausly over 35ms to the coil
control terminals.

Trip coil

Item VH Type
Input voltage (Vn) DC 48V DC 110V DC 125V DC 220V AC 48V AC 110V AC 220V
Rated current (A) 8 3 35 25 8 3 25

Note) Rated operation and control voltage range, see page 65.

63
Accessories

Secondary Trip Coil: A1 Installed inside of a breaker as an option

Secondary Trip Coil with TCM Contact : A2


VL type It is a control device which trips a circuit
breaker doubly from the outside. If the trip coil
(T) fails, it can trip a circuit breaker safely.

Trip coil: Install it at existing location.

Secondary trip coil: Install it on the right side


of the trip coil.

It is not available with UVT coil when installing


secondary trip coil.

Secondary
Trip coil

Item VL Type
DC DC AC AC
Input voltage Vn DC 110V DC 125V DC 220V AC 48V
24 30V 48 60V 100 130V 200 250V
Power consumption (inrush, W) 200
Power consumption (inrush, W) 5

VH type It is a control device which trips a circuit


breaker doubly from the outside. If the trip coil
(T) fails, it can trip a circuit breaker safely.

It is not available with UVT coil when installing


secondary trip coil.

Secondary
Trip coil

Item VH Type
Input voltage Vn DC 48V DC 110V DC 125V DC 220V AC 48V AC 110V AC 220V
Rated current (A) 8 3 35 25 8 3 25

64
Susol VCB

Rated operation and control voltage range

Susol VCB
Item Remarks
VL 7 2kV8 12 5kA VL 20 25kA VH
AC 85 110% 85 110% 85 110%
Motor
DC 75 110% 85 110% 85 110%
AC 85 110% 85 110% 85 110%
Closing
DC 75 125% 85 110% 85 110%
AC 60 125% 85 110% 85 110%
Trip
DC 60 125% 70 110% 70 110%
IEC62271- IEC62271-100(2012)
Applied standards IEC62271-100(2012)
100(2012)KSC4611

Current Trip Coil Installed inside of a breaker as an option

VL type: T9 This trip coil uses the output of the CT as its


Current Trip Coil control power source and is used with over
current relay in combination.
Two current trip coils are supplied.

Coil burden is 90VA.(T9)

Coil impedance( ) is like below


- 3A: 10 or less, Operating current AC 3A (T9)
- 1A: 160 or less, Operating current AC 1A (AV)
- 5A: 6 or less, Operating current is AC 5A (AW)

CT must be installed at load side.


If it is installed at bus side there is the danger
of malfunction or damage to CT.

Don t disconnect the control power connector


on main power is live condition at service
VL type: AV, AW position.
Otherwise there is the danger of malfunction
or damage to CT.
Current Trip Coil
* CT is recommended to use 15VA 5P10 and more.

65
Accessories

Auxiliary Contact: SA Installed inside of a breaker as an option

VL type It is a contact used to monitor ON/OFF status


Auxiliary contact of a breaker from remote place.

The auxiliary contacts supplied as standard


configuration is 4a4b. 10a10b is also available
on request.

For 7.2kV 8/12.5kA VCB standard configuration


is 2a2b. 4a4b and 6a6b are optional.

VL 7 2kV VL 20 25kA
Item
8 12 5kA VH
Standard 2a2b 4a4b
Optional 4a4b 6a6b 10a10b

VH type

Auxiliary contact

VL VH Type
Item
Resistive load A Inductive load A Remarks
250V 10 5
AC
125V 10 5
Contact
250V 10 5 For all models
configuration
DC 125V 10 5
30V 10 5

66
Susol VCB

Under Voltage Trip Coil: U Installed inside of a breaker as an option

VL/VH type VL type VH type

VL type Under Voltage Under Voltage


Trip Coil Trip Coil

It is installed inside of a breaker to trip when the main power or control power voltage drops below certain
value. Instantaneous type is only available with UVT coil and Time delay type is available by connecting UVT coil
and UVT time delay controller.

The closing of a circuit breaker is impossible mechanically or electrically if control power is not supplied to UVT.
To close the circuit breaker, 65~85% of rated voltage should be applied.

UVT and secondary trip coil will not be selected together.

1. UVT rated voltage and characteristic


VH type - Operating voltage range: Pick up 0.65~0.85Vn, Drop out 0.4~0.6Vn
- Operating voltage ranges based on the minimum value of each rated voltage (Vn)

Item VL Type
AC AC
Input voltage Vn DC 24 30V DC 48 60V DC 110V DC 125V DC 220V AC 48V
100 130V 200 250V

Power consumption (inrush, W) 200

Power consumption (steady, W) 5

Item VH Type
Input voltage Vn DC 48V DC 110V DC 125V DC 220V AC 48V AC 110V AC 220V

Power consumption (inrush, W) 350

Power consumption (steady, W) 10

67
Accessories

Position Switch: A3, A4, A5 Installed inside of a breaker as an option

VL type VL 7.2kV 8/12.5kA VL 20/25kA


E/F/G Cradle

Small VCB (VL)

Position switch Position switch


Medium VCB (VL)

This switch is used to indicate the breaker position (SERVICE, TEST), and contact configuration is 2a2a or 2a2b.

VL/VH type VL 20/25kA VH


H Cradle

Large model (VH)


Position
switch
Position
switch

Contact
1 3 5 7 1 3 5 7 1 3 5 7
configuration

2 4 6 8 2 4 6 8 2 4 6 8
1a1b(TEST) 2b(SERVICE) 2a(TEST) 2a(SERVICE) 1a1b(TEST) 1a1b(SERVICE)

68
Susol VCB

Latch checking switch: A6 Installed inside of a breaker as an option

VH type This switch works in conjunction with the


mechanism of the breaker. It checks if the
breaker is ready to be closed.

When the mechanism is OFF and the closing


spring is at charged status the switch becomes
ON , which means the mechanism is ready to
be closed.

If the latch is not in a proper position the


switch prevents the breaker from closing. In
case of VH type it is connected internally in
series with the closing coil.

Latch checking
switch

Installed inside of a breaker as standard


Counter: C

VL/VH type It displays the total number of ON/OFF


operations of a breaker.

69
Accessories

Keylock: A7 Installed inside of a breaker as an option

VL type The key is to unlock the locking device first to


close the breaker electrically and mechanically.

* How to operate
- It is not possible to pull out the key in the
unlocked position, possible only in locked
status.
- Pushing OFF switch of a breaker turn the
key counter-clockwise to the locked position
and pull it out.
- It is not possible to close the breaker
electrically and mechanically in the locked
position.
- Insert the key and turn clockwise and then
the breaker can be closed electrically and
Keylock
mechanically.

VH type *How to operate


- It is not possible to pull out the key in the
unlocked position, possible only in locked
status.
- Trip the breaker first and then turn the key
counter-clockwise to the locked position and
pull it out.
- It is not possible to close the breaker electrically
and mechanically in the locked position.

Keylock

70
Susol VCB

Button Padlock: A8 Installed inside of a breaker as an option

VL type It is to prevent manual operation of ON/OFF


button due to user s wrong handling.

It is not possible to handle ON/OFF operation


under the “Button lock” status.

* Key lock is not supplied.

Button Padlock

VH type

Button Padlock

71
Accessories

Button Cover: A9 Installed inside of a breaker as an option

VL type It is a protection cover to prevent an accident


due to unintended operation of ON/OFF
button.
Use the push-bar to operate the ON/OFF
button.

Button Cover
Push Bar

VH type

Button Cover
Push Bar

72
Susol VCB

Lead wire Supplied separately from a breaker as an option

VL/VH type The wiring for connecting the control circuit


Lead wire of the circuit breaker from the outside is
supplied with 2m of wiring.
A type connector is supplied for P/E/F/G type
of VL VCB.
type connector is supplied for P type of VH
VCB.
In case of H type breaker of VL and VH models
A type connector
the Lead wire is installed in the cradle when
supplied.

type connector

Supply ays of Lead ires by VCB model


Cradle type
P E F G H
VCB model
Optional purchase or cradle shipment
VL Purchase separately see page 74
optional
Optional purchase or cradle shipment
VH Purchase separately see page 74
optional

Installation of CB Compartment
Plug/Terminal for lead wire Supplied separately from a breaker as an option

VL/VH type

A type connector type connector

It is connector to connect with the connector installed in the breaker.


(supply connectors and terminal only for lead wire)

Type of connector is depends on the type of connector installed in the breaker- A or .

73
Accessories

Standard Lead Wire

Auxiliary SA SB ype ) SA S ype )


iring lammability
ype etailed breaker type contact Color Standard wiring ptional wiring Standard wiring ptional wiring
type rating
connector (-) (A ,A ,A ,A4,A5) (-) (A ,A ,A ,A4,A5)
yellow 70723171101 70723171102 70723171101 70723171102
HB
blue 70723171107 70723171108 70723171107 70723171108
SA1
yellow 70723171113 70723171114 70723171113 70723171114
HHW
blue 70723171120 70723171121 70723171120 70723171121
yellow 70723171105 70723171106 70723171105 70723171106
HB
blue 70723171111 70723171112 70723171111 70723171112
Lead wire SA2
yellow 70723171117 70723171118 70723171117 70723171118
VL-06 08,13 04,06 HHW
blue 70723171122 70723171123 70723171122 70723171123
yellow 70723171103 70723171104 70723171103 70723171104
HB
blue 70723171113 70723171114 70723171113 70723171114
SA3
yellow 70723171115 70723171116 70723171115 70723171116
HHW
blue 70723171124 70723171125 70723171124 70723171125
SA1
User plug SA2 77023171003 77023171003
SA3
yellow 70723172101 70723172102 70723172101 70723172102
HB
blue 70723172112 70723172113 70723172112 70723172113
SA2
VL-Type yellow 70723172116 70723172117 70723172116 70723172117
HHW
blue 70723172144 70723172145 70723172144 70723172145
yellow 70723172103 70723172104 70723172103 70723172104
HB
blue 70723172114 70723172115 70723172114 70723172115
SA4
yellow 70723172118 70723172119 70723172118 70723172119
HHW
blue 70723172146 70723172147 70723172146 70723172147
Lead wire
yellow 70723172107 70723172503
VL-06,12,17,20,25 HB
S 2 blue 70723172149 70723172519
20,25,32 13,20,25 (SB2) yellow 70723172109 70723172505
HHW
blue 70723172150 70723172521
yellow 70723172108 70723172504
HB
S 4 blue 70723172151 70723172520
(SB4) yellow 70723172170 70723172506
HHW
blue 70723172522
SA2 77023172101 77023172101 77023172101 77023172101
SA4 77023172101 77023172101 77023172101 77023172101
User plug
S 2(SB2) 70723172110 70723172511
S 4(SB4) 70723172111 70723172512
yellow 70723173109 70723172503
HB
S 2 blue 70723173111 70723172519
(SB2) yellow 70723173119 70723172505
VH-06,12,17,20,25,36 Lead wire HHW
blue 70723173112 70723172521
VH-Type
32,40,50 13,20,25,32,40,50 S 4 yellow 70723173110 70723172504
HB
(SB4) blue 70723173113 70723172520
S 2(SB2) 70723173105 70723172511
User plug
S 4(SB4) 70723173106 70723172512
yellow 70723143117 70723143117 70723143117 70723143117
HB
blue 70713143020 70713143020 70713143020 70713143020
SA2
yellow 70713143012 70713143012 70713143012 70713143012
HHW
blue 70713143030 70713143030 70713143030 70713143030
yellow 70723143118 70723143118 70723143118 70723143118
HB
blue 70713143021 70713143021 70713143021 70713143021
SA4
yellow 70713143013 70713143013 70713143013 70713143013
HHW
blue 70713143031 70713143031 70713143031 70713143031
Lead wire
LVB-06,12 -32,40 /12,20,30 yellow 70713143024 70723143524
HB
2M blue 70713143044 70723143544
LVB-Type VH-06,12 32,40 12,20,30
(2G) yellow 70713143049 70723143549
HHW
(Pro-MEC & Susol PI ) blue 70713143047 70723143547
yellow 70713143025 70723143525
HB
2N blue 70713143045 70723143545
(2H) yellow 70713143048 70723143548
HHW
blue 70713143046 70723143546
2B 73263143007 73263143007
2E 73263143008 73263143008
User plug
2M(2G) 73263143030 70723143651
2N(2H) 73263143031 70723143652
*1: If even one of the options A1, A2, A3, A4, A5 is applied to the VCB code, please order with the optional wiring code.
(ex. Wiring (HB/ ellow) code conforming to VL-06F13A06-M1C1T1SA2U0-A4: 70723171106
*2: After April 2021, the B Type connector is changed to Type (VL/VH: SB- S , LVB: 2G, 2H- 2M, 2N), please order with the appropriate wiring.
(ex. Wiring (HB/ ellow) code conforming to VL-06F25A06-M1C1T1S 2U0: 70723172503

74
Susol VCB

Handle & Lifting Hook

acking handle Spring charge handle ifting ook


Breaker type Cradle
code Appearance code Appearance Breaker type code Appearance
P N. A.

VL-06 08,13 75123173131


E, F, G 55223171101
VH-06,12,
17 50 13,
P N. A.
20,25,32

75123173132
E, F, G 55213143005

A 55223172407 75123173105
type VH-20,25 25 25
VL-06,12, For medium size CB [Short]
17 20,25,31.5 VH-20,25 32,

B 40 13,20,32
55223172403 75123173106
VL-24,25 13, type

16,25 For medium size CB [Long]


H.K

C 55223172405 75123173165
type
With universal joint and plastic grip VH-36 25,32,
40 13,20,32

D 55223172406 75123173166
type
With universal joint

75
Accessories

Handle & Lifting Hook

Racking handle Spring charge handle Lifting Hook


Breaker type Cradle
code Appearance code Appearance Breaker type code Appearance
P N. A.

75123173981
E, F, G 55213143005 VH-06,12,
17 40,50 40

VH-06,12 40,
50 ,50
VH-06 32, 55213143001 75123173982
40(P,E,F,G)

LVB-06,
12 32,40L(G/T) Earthing switch operating handle (Common)
G/T 55213143022

Panel door type code Appearance

Right open
55213163003 (Standard 55223172701
handle)
With universal joint
P N. A.

Right open
A 55223172407 55213143006 (Standard 55223172703
type handle)

For medium size CB [Short]

Ratchet type
(In case of
B 55223172403 insufficient 55223172101
type
operating
For medium size CB [Long] space)

VH-06,
12,17 50
C 55223172405
type
H
VH-20,25, For lower size CB
36 25,32,40 [Universal, Short]

D 55223172406
type
For lower size CB
[Universal, Long]

AB
CD

76
Susol VCB

Plug interlock: AC Installed inside of a breaker as an option

VL/VH type It checks if the control power connector on the


(7.2kV 20/25kA 630A~)
Plug interlock cradle (H type) is connected with the
connecting terminal of the breaker before the
proceeding of draw-in or out.

It is not allowed to seperate the control power


connector from the breaker in the position of
draw-in /out or SERVICE, but TEST position.

Padlock/Door racking interlock: AD Installed inside of a breaker as an option

VL/VH type With this door options for H type cradle draw-
(7.2kV 20/25kA 630A~) in/out is allowed only when the door is closed.

If draw-in /out is necessary when the door is


open, use the operation lever put in the slot of
the breaker handle.
Insert it into the hole in the bottom of door
interlock.

Padlock is also optional, which can lock to


prevents the draw-in/out of the breaker in the
position of TEST and SERVICE.

Door interlock

77
Accessories

MOC drive device: AE Installed inside of a breaker as an option

VL type It must be installed in the breaker to drive the


(7.2kV 20/25kA 630A~) MOC installed in H type cradle.

MOC, Mechanically operated cell switch is the


device to indicates the Closed/Trip status of
VCB in 'SERVICE' position only.

This MOC drive device in the breaker should be


installed when MOC in the cradle is used.

MOC

VH type

MOC

78
Susol VCB

Locking magnet: AF Installed inside of a breaker as an option

VL type It allows the drawing-in of the breaker in the


TEST position under the condition that the
control power connector on the cradle (H type)
is connected with the connecting terminal of
the breaker and the power is supplied.

Constant power must be supplied to locking


magnet until the draw-in/out operation is
completed and operation handle is inserted
* Control power rating is the same as that of a motor.

Locking
magnet

VH type

Locking magnet

79
Accessories

Trip coil monitoring contact Installed inside of a breaker as standard

VL type Device for monitoring the functions of the trip coils.

To monitor the trip coils connect its terminals


Trip coil monitoring contact
Secondary trip coil with TCM Contact

with the trip coil monitoring relay as shown on


the circuit diagram.
- If the trip coil is normal: closed-circuit consisting
- If the trip coil is damaged: open circuit
1) Terminal A5 and A6 monitor the trip
coils(TC) in Closed position of the breaker
2) Terminal A6 and auxiliary contact terminal 34
monitor the trip coils(TC) in trip position of
the breaker
3) Terminal 11 and 12 monitor the secondary
trip coils(TC1) in Closed position of the breaker
4) Terminal 12 and auxiliary contact terminal
36 monitor the secondary trip coils(TC1) in
trip position of the breaker

Coil Test Unit is opional, which enable


monitoring the coils by connecting in parallel
with the trip coil operation switch.

Trip coil monitoring contact is available only


VH type when trip coils T1, T2, T3, T4, T5 are selected.
Closing coil monitoring contact Trip coil monitoring contact

Secondary trip coil with TCM Contact

Note 1)

80
Susol VCB

Coil Test Unit: CTU Installed inside of a breaker as an option

When no current flows through the coil it gives the test current which does not cause the coil to operate to check
whether the coil is disconnected or not.
- If the test current flows normally: coil normal
- If the test current does not flow through: coil disconnected

As it is connected in parallel it t e control part of t e coil t e normal operation of t e coil is not affected.
Monitoring of t e running coils is not possible.
ne test unit can monitor up to t o coils.

1. Input voltage: AC/DC 75V~264V

2. Contact output
1) 2 a contacts for Fail indication and 2 a contacts for Alarm
2) 250Vac/10A Resistive, 30Vdc/10A Resistive

3. Disconnection test cycle is 12 seconds (Test LED blinks)

4. The default operation


If Fail happens (coil disconnected), Fail LED turns on and the Fail contacts become short state.
If Fail happens three times in series, Alarm LED turns on and the Alarm contacts become short state.
In order to clear the Alarm status push up DIP switch on the front and then push down it (Off On Off)

Input voltage
AC/DC 75~264V

Fail 1

24~250V
(AC/DC) Alarm 1
Shunt 1
Coil
Test
Fail 2
Unit
24~250V
(AC/DC) Alarm 2
Shunt 2

CTU CTU
Input voltage Input voltage
Coil drive power(+) (+) (+)

1 2
Coil drive power
5 Fail (LED)
Fail (RELAY)
7
Coil Alarm (LED)
Coil test current Alarm (RELAY)
Coil Test Unit
Coil drive power(-)

81
Accessories

Condenser trip device: CTD Installed inside of a breaker as an option

Ratings atings Speci cation It gets a circuit breaker tripped electrically


Model CB T1 CB T2 within regular time when control power supply
is broken down and is used with Shunt coil,
Rated input voltage (V) AC 100 110 AC 200 220
SHT. In case there is no DC power, It can be
Frequency (Hz) 50 60 50 60
used as the rectifier which supplies DC power
Rated charge voltage (V) 140 155 280 310 to a circuit breaker by rectifying AC power.
Charging time Within 10sec Within 10sec
Tripping within 30 seconds on the power
Trip possible time Within 30sec Within 30sec failure is possible. However after that
Range of Input voltage 85% 110% 85% 110% automatic trip circuit must be configured
Condenser capacity ( F) 1 000 560 separately in the switchgear.

Terminal
arrangement

External
dimension
(Mounting hole)

Circuit diagram

82
Susol VCB

UVT Time delay: UDC Installed inside of a breaker as an option

UVT time delay, UDC is to delay the trip signal from UVT.

Without UDC the breaker will be tripped instantaneously by the trip signal from UVT installed inside of the
breaker even in the the momentary power failure.

UDC can delay the trip time to avoid this unintended instantaneous trip in the event of such power failure.

It can be installed on the cradle or inside of the switchgear.

UDC provides output contacts for indication of trip status due to the UVT coil inside of the breaker.
b contact is closed at normal state and a contact is closed at trip.

C aracteristics

Rated voltage Vn Opration voltage range V Consumption VA or W Time delay


DC V AC V Pick up Drop out Inrush Steady state ms
48~60 48
100~130 100~130 0 65 0 85 Vn 0 4 0 65 Vn 200 5 05 1 15 3
200~250 200~250

- Operating voltage ranges are based on the minimum value of each rated voltage (Vn)

Ratings of output contacts

Rated voltage V Rated current A Resistive load Max switching voltage A Max switching current A
24V DC 12
110V DC
120V AC 12 15
250V AC
250V AC 10

iring diagram

Delayed
trip signal

5 7

14 16
18(a)
Operating UVT Delay
UVT output 19(c)
18 19 20 contact 20(b) Controllor
a c b
0.5
1
Signal for 1.5
tripping 14 16
3

DC48~60V
AC48
[sec]
Instantaneous
5 7 trip signal
Time Delay for UVT
D1

D2
UVT

83
Accessories

Temperature sensor and monitoring unit: TM Installed inside of a breaker as an option

VL/VH type Temperature Alarm Unit displays the input


(7.2kV 20/25kA 630A~) temperature detected through the
temperature sensor installed in H-type cradle.

Temperature sensor can be installed up to


Temperature
three (R, S, T phase).
Sensor
Temperature Alarm Unit converts the
temperatures detected from the senser in the
cradle and displays the maximum value and
can transmit it throug communication.

If the input temperature is above standard it


may cause alarm.
Temperature Alarm Unit supports Modbus/
RS-485 communication and contact us
Profibus-DP communication.

Temperature sensor and


monitoring unit

LED temperature display ( ):


10 ~150 , Warning
Display maximum value
of temperatures

84
Susol VCB

Earthing Switch: A1 Built-in a cradle as an option

VL/VH type For the safety during the maintenance of


(7.2kV 20/25kA 630A~) switchgear in the position of TEST/Drawout
discharge the charging current in the load side
of a VCB with this earthing switch.
It is available onlt for H type drawout breaker.

* Regarding the operations of earthing switch and related


accessories see the instruction manual.
* Applicable Standards: IEC 62271-102

Earthing
Switch

Position switch for Earthing Switch: A2, A4 Built-in a cradle as an option

In case of using earthing switch it can be added to indicate the ON / OFF status of the earthing switch.

** Contact configuration: 2a2b, 6a6b

Position switch for E/S

Circuit diagram
E1 E3 E5 E7 E9 E11 E13 E15 E17 E19 E21 E23

E2 E4 E6 E8 E10 E12 E14 E16 E18 E20 E22 E24

85
Accessories

Keylock for Earthing Switch: A5 Built-in a cradle as an option

In case of using earthing switch it can be


added for two types of interlocking.

1) Interlock to keep opening

2) Interlock to keep earthing

Keylock for earthing switch

Locking magnet for Earthing Switch: A6~AD Built-in a cradle as an option

In case of using earthing switch it can be added to prevent the earthing switch from opening or earthing before
it is energized.

Verify if the locking magnet is energized before opening or earthing the earthing switch.

Control voltage

- DC 24V / DC 48V / DC 110V / DC 125V / DC 220V


- AC 48V / AC 110V / AC 220V

Locking magnet for


Earthing Switch

86
Susol VCB

Shutter padlock: AE Built-in a cradle as an option

VL/VH type •It is the locking device to lock the primary and
secondary shutter in closed state for safety
(7.2kV 20/25kA 630A~) while the breaker is drawn out for
maintenance.
•When the breaker is drawn in, the shutter is
automatically opened.
•There is a hole for padlock to lock the shutter.
•It can be applied only to H type cradle.

Shutter
padlock

Truck operated cell switch (TOC: AF) Built-in a cradle as an option

VL/VH type This auxiliary switch is used to indicate the


(7.2kV 20/25kA 630A~) 'SERVICE' position of VCB. It is installed in the
bottom of a H type cradle and operated by the
frame of a breaker.

TOC is consisted of 4 cell switches with


changeover contacts as below diagram.

VL type

Circuit diagram

121 122 124 125 127 128 130 131

TOC

VH Type
123 126 129 132

a Contact: 122-123, 125-126, 128-129, 131-132,


b Contact: 121-123, 124-126, 127-129, 130-132

87
Accessories

Mechanical Operated Cell Switch (MOC: AG) Built-in a cradle as an option

VL/VH type This auxiliary switch is used to indicate the


(7.2kV 20/25kA 630A~) Close/Trip of VCB. It is operated mechanically
at the SERVICE position and installed in the
bottom of a H type cradle and operated by the
frame of a breaker.

MOC is consisted of 4 cell switches with


changeover contacts as below diagram.

Circuit diagram
VL type 102 101 105 104 108 107 111 110

MOC

103 106 109 112

a Contact: 101-103, 104-106, 107-109, 110-112,


VH Type b Contact: 102-103, 105-106, 108-109, 111-112

Built-in a cradle as an option


Door: AH

VL/VH type It is outside door for H type cradle.


(7.2kV 20/25kA 630A~) Accessories are available for the door.

Door

88
Susol VCB

Door Interlock: AJ Built-in a cradle as an option

VL/VH type When the Door is installed to H type cradle,


(7.2kV 20/25kA 630A~) this door interlock prevents opening it at
SERVICE position.
Door
Interlock

Door Emergency Push button: AK Built-in a cradle as an option

VL/VH type It is used to enable the Close/Trip of the


(7.2kV 20/25kA 630A~) breaker manually from outside of the door
installed to H type cradle during an
emergency.

Push the ON/OFF button by ON/OFF handle


supplied seperately.

Door
Emergency
Push button

89
Accessories

Temperature Sensor: AC Built-in a cradle as an option

VL/VH type This sensor is used to detect the temperature


(7.2kV 20/25kA 630A~) in H-type cradle combined with Temperature
monitoring unit.

It can be installed up to three (R, S, T phase).


Temperature
Sensor

Racking In/Out handle

Susol VCB offers various kinds of handle suitable for each use of types and models.
The order can be proceeded with the code below and ordering quantity is flexibly adjustable.

ype Cradle acking in out handle Charging handle perating handle for earthing S
E 55223171101
VL-06 08, 13 F Not required
G
E 55213143005
VL-06 20, 25 F Not required
G
55223172407
A

VL-06 20, 25 Not required


55223172403
B
H
K 55223172405 55213143006
C
VH-06, 12, 17,
24, 35, 36 55223172406
D

Racking in/out
handle for
H, K cradle A B
C D

90
Susol VCB

Type H Cradle Lead Wire: AM~AO Built-in a cradle as an option

VL/VH type In case of H type breaker of VL and VH models


(7.2kV 20/25kA 630A~) the Lead wire is installed in the cradle when
supplied.

4a4b or 10a10b contacts are selectable


according to the auxiliary contact of the breaker.
Flame retardant cable is used for 4a4b.

Lead
Wire

Door Padlock Built-in a cradle as an option

VL/VH type It is supplied with a door for H type cradle as


(7.2kV 20/25kA 630A~) standard.

It can be locked by seperate padlock to prevent


entering the maunal handle.

Door
Padlock

91
Accessories

Auxiliary guide frame

Auxiliary guide frame is provided in order to move safely


36kV breaker into the switchgear.

It can be used in combination with the hand pallet which


meets the requirement shown below.

Applicable hand pallet

B If dimension A in Fig. 1 is
less than 120mm B type
Width : 550mm pallet can be used.
Min. height: 90mm In case of more than
550

120mm C type must be


applied.
Upper side of guide rail in switchgear C
A

Bottom

<Fig 1

92
VL-06
Trip coil monitoring contact

Note1)

Note2) Note3)

(Charge completion indicating contact)


<Connecting terminal arrangement>
Control circuit diagram - VL type

: External terminal of VCB LS2: Motor stop, close spring charged indication limit switch
52: Vacuum circuit breaker
M: Spring charging motor LS4, LS5: Position S/W (close in TEST position)
TC: Trip coil LS6, LS7: Position S/W (close in SERVICE position)
TC1: Secondary trip coil TEST 1a1b TEST : 2a TEST : 1a1b
C: Close coil SW SERVICE 2b SERVICE 2a SERVICE 1a1b
UVT: Under voltage trip No
A3 A4 A5
52a: Auxiliary switch (a) LS4 Close at TEST position Close at TEST position Close at TEST position
52b: Auxiliary switch (b)
LS5 OPEN at TEST position Close at TEST position OPEN at TEST position
CTC : Current trip coil
LS6 OPEN at SERVICE position Close at SERVICE position Close at SERVICE position
CTC1 : Secondary Current trip coil
LS7 OPEN at SERVICE position Close at SERVICE position OPEN at SERVICE position
CS : Closing spring charged Limit Switch
: Anti-Pumping Device
Anti-Pumping Device is installed inside
as standard IEC62271-100 3.6.128

Note) 1. Position S/W : TEST 2a, SERVICE 2a (Terminal No. : 1, 2, 3, 4, 5, 6, 7, 8)


-TEST position 1a1b, SERVICE position 1a1b/2b are available
(* marked contact is b contact)
2. UVT : Under Voltage Trip (Terminal No. : D1, D2) Option
3. TC1 : Secondary Trip Coil (Spare trip coil, terminal No. : 11, 12)
4. CTC : Current Trip Coil (Terminal No. : A5, A6)
CTC1 : Secondary Current Trip Coil (Terminal No. : 11, 12)
5. Close and Trip coil is One Pulse type, excluding trip coil (DC110,220V)
6. In above optional accessories, UVT,CTC and TC1 can not be selected simultaneously
7. UVT, TC1 are selected, Maximum auxiliary switch is 4a4b
8. Above circuit diagram is based on 'OFF' status of VCB and closing spring is charged
9. Please make sure that keep the direction of P,N on this circuit diagram
* : Anti-pumping device
Anti-pumping device supply anti-pumping function to VCB as below. It is composed with circuit in close coil and mechanism.
In case the closing coil(C) becomes permanently energized, the circuit breaker remains in the open position after it has been opened,
either by manual or electrical operation. The circuit breaker can be closed only if the closing coil(C) is momentarily de-energized.

93
Susol VCB
94
Trip coil monitoring contact
Secondary trip coil with TCM Contact

Note2)

VL-06/12/17/20/25/36

Note1)

Note3) Note4)

Note4) Note4)
Current Trip Coil(1A,5A) indicating contact
(Charge completion indicating contact)
<Connecting terminal arrangement>
: External terminal of VCB : Anti-Pumping Device
52 : Vacuum circuit breaker Anti-Pumping Device is installed inside as standard IEC62271-100 3.6.128 A type connector
M : Spring charging motor
LS4, LS5 : Position S/W (TEST position)
TC : Trip coil(SHT)
LS6, LS7 : Position S/W (SERVICE position)
Control circuit diagram - VL type

TC1 : Secondary Trip coil(SHT1)


C : Closing coil(CC) TEST 1a1b TEST : 2a TEST : 1a1b
UVT : Under Voltage Trip SW
SERVICE 2b SERVICE 2a SERVICE 1a1b
52a : Auxiliary switch (NO) No
A3 A4 A5
52b : Auxiliary switch (NC) LS4 Close at TEST position Close at TEST position Close at TEST position
LS2 : Motor stop limit switch
LS5 OPEN at TEST position Close at TEST position OPEN at TEST position
CTC : Current Trip coil(3A)
CTC1 : Secondary Current Trip coil(3A) LS6 OPEN at SERVICE position Close at SERVICE position Close at SERVICE position
CTC2 : Current Trip coil(1A,5A) LS7 OPEN at SERVICE position Close at SERVICE position OPEN at SERVICE position
CTC3 : Current Trip coil(1A,5A) LM : Locking magnet(only withdrawable type)
LET : Low Energy Trip Device(25m ,100m )
CS : Closing spring charged indication limit switch

Note) 1. CTC2 : Current Trip Coil(1A,5A) (Terminal NO : 13,14)


2. Position S/W - TEST 2a, SERVICE 2a(Terminal NO.:1,2,3,4,5,6,7,8)
- TEST position 1a1b, SERVICE position 1a1b/2b are available.
(* marked contact is b contact.)
3. UVT - Under Voltage Trip (Terminal NO.:D1, D2) Q type connector
4. TC1 - Secondary Trip Coil (Terminal NO.:11,12)
24 23 22 A6 A5 A4 A3 A2 A1 24 23 22 A6 A5 A4 A3 A2 A1
29 28 27 26 25 42 41 40 29 28 27 26 25
In case TC1 is selected and auxiliary switch is 10a10b, Some 'a' contact
49 48 47 46 45 44 43
51 50 39 38 37 36 51 50 39 38 37 36 61 60
(Terminal No.: 40,41) and 'b' contact(Terminal No.:54, 55) are not available.
53 52 58 57 56 55 54 53 52
Option
1 1 75 74 73 72 71 70 59
5. Secondary Trip Coil Monitoring Contact (Terminal NO.:36)
10 9 8 7 6 5 4 12 3 11 2 10 9 8 7 6 5 4 12 3 11 2
34 16 15 14 13 D2 D1 34 16 15 14 13 D2 D1
In case Secondary Trip Coil TCM Contact is selected and auxiliary switch is 9a8b, Some 'a' contact
13 D1
(Terminal No.: 40,41) and 'b' contact(Terminal No.:36, 37) are not available.
6. CTC - Current Trip Coil (Terminal No.: A5,A6)
CTC1 - Secondary Current Trip Coil (Terminal No.: 11,12) (4a4b) (10a10b)
CTC2 CTC3
CTC2 - Current Trip Coil (Terminal No.: 13,14)
CTC3 - Current Trip Coil (Terminal No.: D1,D2)
7. LET - Low Energy Trip Device (Terminal No.: 13,14)
8. LM - Locking Magent (Terminal No.:15, 16), In case of B type connector is available
14 D2
9. Close and Trip coil is One Pulse type, excluding Trip coil (DC110, 220V)
10. In above optional accessories, UVT,CTC and TC1 can not be selected simultaneously.
11. Above circuit diagram is based on OFF state of VCB and closing spring is charged.
12. Please, keep the direction of P,N on this circuit diagram.
* : Anti-pumping device
Anti-pumping device supply anti-pumping function to VCB as below. It is composed with circuit in close coil and mechanism.
In case the closing coil(C) becomes permanently energized, the circuit breaker remains in the open position after it has been opened,
either by manual or electrical operation. The circuit breaker can be closed only if the closing coil(C) is momentarily de-energized.
Closing coil monitoring contact Trip coil monitoring contact

Secondary trip coil with TCM Contact Note 6)

Note 2)

VH-06/12/17/20/25/36

Note 5)

Note 1)

Note 3) Note 4)

Closing Spring Contact charge completion indicating contact


Control circuit diagram - VH type

<Connecting terminal arrangement>

: External terminal of VCB


24 23 22 A6 A5 A4 A3 A2 A1
LS3: Anti-close, anti-pumping limit switch
52: Vacuum circuit breaker LCS1: Trip latch checking switch 29 28 27 26 25
51 50 39 38 37 36
M: Spring charging motor (preventing closing unless the trip latch is properly reset)
TC: Trip coil LS4, LS5: Position S/W (close in TEST position) 53 52
1
TC1: Secondary trip coil LS6, LS7: Position S/W (close in SERVICE position) 10 9 8 7 6 5 4 12
3 11
2
C: Close coil 76 34 16 15 D2 D1
: Anti-pump relay TEST 1a1b TEST : 2a TEST : 1a1b
SW
SERVICE 2b SERVICE 2a SERVICE 1a1b
UVT: Under voltage trip No
52a: Auxiliary switch (a) A3 A4 A5 (4a4b)
52b: Auxiliary switch (b) LS4 Close at TEST position Close at TEST position Close at TEST position
LS5 OPEN at TEST position Close at TEST position OPEN at TEST position
LS1: Close interlock limit switch (only 24 23 22 A6 A5 A4 A3 A2 A1
LS6 OPEN at SERVICE position Close at SERVICE position Close at SERVICE position 42 41 40 29 28 27 26 25
49 48 47 46 45 44 43
withdrawable type)
51 50 39 38 37 36 61 60
LS7 OPEN at SERVICE position Close at SERVICE position OPEN at SERVICE position
LS2: Motor stop, close spring charged
58 57 56 55 54 53 52
indication limit switch LM: Locking magnet (only withdrawable type) 1 75 74 73 72 71 70 59
10 9 8 7 6 5 4 12
3 11
2
76 34 16 15 D2 D1

Note) 1. LCS1 : Latch Checking Switch


2. Position S/W - TEST 2a, SERVICE 2a(Terminal No. 1, 2, 3, 4, 5, 6, 7, 8) (10a10b)
1a1b at TEST position and 1a1b at SERVICE position are also available.
(In case of 1a1b *marked contact is b - nomally open contact)
3. UVT - Under Voltage Trip (Terminal No. D1, D2) Option
4. TC1 - Secondary Trip Coil (Spare trip coil, terminal No. 11, 12)
5. LM - Locking Magnet (Terminal No. 15, 16), Type H only withdrawable type.
6. Secondary Trip Coil monitoring contact (Terminal No. 36)
b contact(36, 37) is not available if Trip Coil monitoring contact is applied to Secondary Trip Coil.
7. Above options TC1 and UVT can not be used simultaneously.
8. LS1(closing-interlock Limit-switch) is not available for fixed version
9. Above circuit diagram is based on OFF status of VCB and closing spring is charged.
10. Please make sure that keep the direction of P, N on this circuit diagram.

95
Susol VCB
96
Earthing S/W Auxiliary switch

6a 6b

Compartment
P
2a 2b
MOC Note2) TOC Note3) TM Note4)

E1 E5 E9 E13 E17 E21 E3 E7 E11 E15 E19 E23 17 102 101 105 104 108 107 111 110 121 122 124 125 127 128 130 131 8(R+) 9(S+) 10(T+)

E1 E5 E9 E13 E17 E21 E3 E7 E11 E15 E19 E23

E2 E6 E10 E14 E18 E22 E4 E8 E12 E16 E20 E24


Note1)

LM TM TM TM

LOCKING MAGNET POWER SOURCE


Control circuit diagram - VH type

E2 E6 E10 E14 E18 E22 E4 E8 E12 E16 E20 E24 18 103 106 109 112 123 126 129 132 12(R-) 12(S-) 12(T-)
N

: External terminals for auxiliary contacts and locking magnet


LM : Locking magnet for earthing swtich
MOC : Mechanism operated cell switch (for H type cradle)
TOC : Truck operated cell switch (for H type cradle)
TM : Temperature alarm (for H type cradle)

Note) 1. LM - If it is energized with the rated power the earthing switch can be closed or opened (for H type cradle)
2. MOC - This auxiliary switch is used to indicate the Close/Open of VCB (for H type cradle)
It is composed of 4 cell switches with 4 changeover contacts.
Option
3. TOC - This auxiliary switch is used to indicate the 'SERVICE' position of VCB (for H type cradle)
It is composed of 4 cell switches with 4 changeover contacts.
4. TM - Temperature Alarm Unit displays the input temperature detected through the temperature sensor installed in H-type
cradle. Temperature sensor can be installed in each phase and can be connected with the temperature module.
5. Please make sure that keep the direction of P, N on this circuit diagram.

* Above circuit diagram is based on the status that the earthing S/W is Open and the breaker is at Test or between Test and Service
position. MOC indicates the Open of the breaker. If the breaker is Closed from Service, the contacts configuration is displayed on
the contrary.
Dimensions - VL type (VL-06) Susol VCB

7.2kV, 8/12.5kA, 400/630A


Fixed P type, phase distance 130mm

(Mounting hole)

Main circuit terminal

Withdrawable Standard breaker E/F/G type, phase distance 130mm

Main circuit terminal

97
Dimensions - VL type (VL-06)

7.2kV, 8/12.5kA, 400/630A


Withdrawable Compatible with existing breaker E/F/G type, phase distance 130mm

Main circuit terminal

Withdrawable E type cradle, phase distance 130mm


Racking in/out
Stroke:150

<Main circuit terminals detail>


Note) Dimensions in ( ) apply to 12.5kA

(Earthing hole)

Racking in/out
Stroke:150 Main circuit terminal

98
Susol VCB

7.2kV, 8/12.5kA, 400/630A


Withdrawable F type cradle, phase distance 130mm
Racking in/out
Stroke:150

<Main circuit terminals detail>


Note) Dimensions in ( ) apply to 12.5kA

(Earthing hole)

Racking in/out
Main circuit terminal
Stroke:150

Withdrawable G type cradle, phase distance 130mm


Racking in/out
Stroke:150

<Main circuit terminals detail>


Note) Dimensions in ( ) apply to 12.5kA

(Earthing hole)

Racking in/out
Stroke:150 Main circuit terminal

99
Dimensions - VL type (VL-06/12/17/20/25/36)

7.2kV, 20/25kA, 630/1250A


Fixed P type, phase distance 150mm

M12
(Earthing hole)

91.5
281
96.5

6(10)

Note) Dimensions in ( ) apply to 1250A

Withdrawable E type unit, phase distance 150mm

Note) Dimensions in ( ) apply to 1250A

100
Susol VCB

7.2kV, 20/25kA, 630/1250A


Withdrawable F type unit, phase distance 150mm

Note) Dimensions in ( ) apply to 1250A

Withdrawable G type unit, phase distance 150mm


6(10)

Note) Dimensions in ( ) apply to 1250A

101
Dimensions - VL type (VL-06/12/17/20/25/36)

7.2kV, 20/25kA, 630/1250A


Withdrawable K type unit T type, phase distance 150mm
516
150 150

616
669
350

450 328 Stroke:225

295
29
692.5

672.5
332.5
230.5
104.5

13 288 32
522
12.5

351
53 383
436

Withdrawable K type unit T2 type, phase distance 150mm


516
150 150
616
669
350

450 328 Stroke:225


295
29
692.5

672.5
332.5
230.5
104.5

288
13 351 32
522
32.5

53 383
436

102
Susol VCB

7.2kV, 20/25kA, 630/1250A


Withdrawable E type cradle, phase distance 150mm
5- 12(Mounting hole) Racking in/out Stroke:132

Rating A 12 A
12(Earthing hole)
A 6 10
B 55 60
C 95 90

Withdrawable F type cradle, phase distance 150mm

5- 12(Mounting hole) Racking in/out Stroke:132


12(Earthing hole)

Rating A 12 A
A 6 10
B 55 60
C 95 90

103
Dimensions - VL type (VL-06/12/17/20/25/36)

7.2kV, 20/25kA, 630/1250A


Withdrawable G type cradle, phase distance 150mm

(Mounting hole) (Mounting hole) (Mounting hole)


(Earthing hole)

Rating A 12 A
A 6 10

273.5

Withdrawable H type unit, phase distance 150mm

194
112
110

Note) Please be informed that When -type connecter is


used to design switchgears, the height can be 110mm
higher based on “A”

Racking in/out
Stroke:200

104
Susol VCB

7.2kV, 20/25kA, 630/1250A


Withdrawable H type cradle, phase distance 150mm
317 323.4 42.3

(For assembly of (Mounting hole)


lifting hook and LV M12 (DP:25)
compartment

150 150
mounting hole)

(Mounting hole)
725 183.7
1017.7

(Mounting hole)
(Mounting hole)

65 285 150 150 258.7

8- 11
550

(Mounting hole)

Around assembling hole of earthing Around assembling hole of earthing


switch stator, cut the heat-shrinkable switch stator, cut the heat-shrinkable
tube to both upper and lower direction. tube to both upper and lower direction.

Connecting busbar method Connecting busbar method


(with earthing switch) (with earthing switch)
Busbar : 8t 40 (2 sheets) <1250A Busbar : 8t 40 (1 sheets) <630A
20 20
87.3 87.3
10.0

TUBE TUBE
30

30

Detail A Detail A

87.3
20
2-M8 (DP:18)
43.4

See Detail A Detail A

105
Dimensions - VL type (VL-06/12/17/20/25/36)

7.2kV, 20/25kA, 2000A


Fixed P type, phase distance 150mm

M12(Earthing hole)

96.5

46.8

Withdrawable E type unit, phase distance 150mm

106
Susol VCB

7.2kV, 20/25kA, 2000A


Withdrawable F/G type unit, phase distance 150mm

Withdrawable K type unit T type, phase distance 150mm

107
Dimensions - VL type (VL-06/12/17/20/25/36)

7.2kV, 20/25kA, 2000A


Withdrawable K type unit T2 type, phase distance 150mm

Withdrawable E type cradle, phase distance 150mm


40
166 175 (Racking in/out Stroke)
20
40
180
90
210
525
491

180
90

4- 14
260 410 6- 12
(Mounting hole)

150 150
62.4

600

108
Susol VCB

7.2kV, 20/25kA, 2000A


Withdrawable F type cradle, phase distance 150mm
40
166 175 (Racking in/out Stroke)
20

180
576
525
491

180
260 410 6- 12
(Mounting hole)
62.4

600
793

Withdrawable G type cradle, phase distance 150mm

166 175 (Racking in/out Stroke) 12- 14


(Mounting hole)
180
150
40
90
525
491

210

150
180
10

6- 12
(Fixed type hole)
40

260 410 210 40


62.4

600
793

109
Dimensions - VL type (VL-06/12/17/20/25/36)

7.2kV, 20/25kA, 2000A


Withdrawable H type unit, phase distance 150mm

194
112

110
A

Note) Please be informed that When -type connecter is


used to design switchgears, the height can be 110mm
higher based on “A”

Racking in/out
Stroke:220

110
Susol VCB

7.2kV, 20/25kA, 2000A


Withdrawable H type cradle, phase distance 150mm
317 323.4 42.3
25
(For assembly of (Mounting hole)
lifting hook and LV
compartment

150 150
mounting hole)

550.4
(Mounting hole)
725 202.7
1017.7

(Mounting hole) (Mounting hole)

310
465
65 285 150 150 277.7
550

(Mounting hole)

Around assembling hole of earthing


switch stator, cut the heat-shrinkable
tube to both upper and lower direction.

Connecting busbar method


(with earthing switch)
20 Busbar : 10t 75 (2 sheets)
68.3
10.0

TUBE
30

25
Detail A

68.3
20
2-M8 (DP:18)
43.4

See Detail A Detail A

111
Dimensions - VL type (VL-06/12/17/20/25/36)

7.2kV, 31.5kA, 630A


Fixed P type, phase distance 150mm

553
2- 14
Earthing position 150 150
40

40
4- 13

178
212
152
10
M12
(Earthing hole)

509
281

46.8
96.5

450 212

295
670

650
10
320
470 315 156
589 523.5

Withdrawable H type unit, phase distance 150mm

490
150 150
194
112
110
607
660
440

Note) Please be informed that When -type connecter is


used to design switchgears, the height can be 110mm
higher based on “A”

492 319 Stroke: 200

7.2kV,31.5kA,630, 150, P Type


310
35
688

623.5
280
154
76

320 25
21.5
19.5
4

13 358
503
53 383
469

112
Susol VCB

7.2kV, 31.5kA, 630A


Withdrawable H type cradle, phase distance 150mm

(For assembly of
lifting hook and LV (Mounting hole)
compartment
mounting hole)

(Mounting hole)

(Mounting hole)
(Mounting hole)

(Mounting hole)

Around assembling hole of earthing


switch stator, cut the heat-shrinkable
tube to both upper and lower direction.

Connecting busbar method


(with earthing switch)
Busbar : 10t 40 (1 sheets)

113
Dimensions - VL type (VL-06/12/17/20/25/36)

7.2kV, 31.5kA, 1250A


Fixed P type, phase distance 150mm
553 2- 14
150 150
Earthing position 60

40
4- 13

178
212
10
152
M12

509
(Earthing hole)

281

46.8
96.5

450 212

295
670

650
10
320
470 315 156
589 523.5

Withdrawable E type unit, phase distance 150mm

7.2kV,31.5kA,1250A, 150, P Type

114
Susol VCB

7.2kV, 31.5kA, 1250A


Withdrawable F/G type unit, phase distance 150mm

Withdrawable E type cradle, phase distance 150mm

40 20
2- 14 (Mounting hole) (Earthing hole)
70 105 70 105 70
180
35
150
150

180
40

270
62.4
80.2

115
Dimensions - VL type (VL-06/12/17/20/25/36)

7.2kV, 31.5kA, 1250A


Withdrawable F type cradle , phase distance 150mm

Racking in/out
166 Stroke: 175 40
40 20
20
2- 14

70 105 70 105 70

180
180
35
150

525

210
491
150

180

180
40

2-Ø14
270 260 410 6-Ø12
(Mounting hole)

150 150

10
295
720.2
326.2
139 790 150
600

Withdrawable G type cradle, phase distance 150mm

40 20
2- 14 (Mounting hole) (Earthing hole)
70 105 70 105 70
180
35
150
150

180
40

270
10
295
720.2
326.2
62.4
80.2

23.4
87.2

793 12
820
940

116
Susol VCB

7.2kV, 31.5kA, 1250A


Withdrawable K type unit T type, phase distance 150mm
516
150 150

616
669
350

328 Stroke:225
450

295
692.5

676
48
332.5
230.5
104.5
288 32 12.5
13 351
522 53 383
436

Withdrawable K type unit T2 type, phase distance 150mm


516
150 150
616
669
350

7.2/12kV,31.5kA,1250A, 150, K Type (T)

450 328 Stroke:225


295
48
692.5

676
332.5
230.5
104.5

288 32
32.5

13 351
522 53 383
436

117
Dimensions - VL type (VL-06/12/17/20/25/36)

7.2kV, 31.5kA, 1250A


Withdrawable G type cradle T type, phase distance 150mm
VIEW "C"
150 150
26

26
(Mounting
hole)

560
83
295
(Mounting hole)

100 660

S ST: 225

ST: 225

48
VIEW

295
"C"
1235

345
1250A: 12t
2000A: 25t

285
S
600 12 100 660 156
731.5
946

Withdrawable MCSG cradle T2 type, phase distance 150mm

150 150
60
26
26

150
600
560
83

150

(Mounting hole)

100 662

1250A:12t
2000A:25t
295
1235
630

731.5
946

118
Susol VCB

7.2kV, 31.5kA, 1250A


Withdrawable H type unit, phase distance 150mm
490
150 150
194
112

110
607
660
440 A

Note) Please be informed that When B-type connecter is


used to design switchgears, the height can be 110mm
higher based on “A”

492 319 Stroke: 200

310
35
688

623.5
280
154
76

320 25
21.5
19.5
4

13 358
503
53 383
469

7.2/12/17.5kV,31.5kA,630/1250A, 150, H Type

119
Dimensions - VL type (VL-06/12/17/20/25/36)

7.2kV, 31.5kA, 1250A


Withdrawable H type cradle, phase distance 150mm

(For assembly of
lifting hook and LV (Mounting hole)
compartment
mounting hole)

(Mounting hole)

(Mounting hole)
(Mounting hole)

(Mounting hole)

Around assembling hole of earthing


switch stator, cut the heat-shrinkable
tube to both upper and lower direction.

Connecting busbar method


(with earthing switch)
Busbar : 10t 40 (2 sheets)

120
Susol VCB

7.2kV, 31.5kA, 2000A


Fixed P type, phase distance 150mm

M12(Earthing hole)

96.5

46.8

Withdrawable E type unit, phase distance 150mm

121
Dimensions - VL type (VL-06/12/17/20/25/36)

7.2kV, 31.5kA, 2000A


Withdrawable F/G type unit, phase distance 150mm

Withdrawable E type cradle, phase distance 150mm

166 ST:175 40 20
4-Ø14
180
525
491

180

260 410 7-Ø12


(Mounting hole)
20
295
720.2
62.4
80.2

326
87.2

15
790 150
820

122
Susol VCB

7.2kV, 31.5kA, 2000A


Withdrawable F type cradle, phase distance 150mm

166 ST:175 40
20

180
525
491

180
4-Ø14
260 410 7-Ø12
(Mounting hole)

20
295
720.2
62.4
80.2

326
87.2

15
790 150
820

Withdrawable G type cradle, phase distance 150mm

166 ST:175 40
20
180
525
491

180

4-Ø14
260 410 7-Ø12
(Mounting hole)
20
295
720.2
62.4
80.2

326
87.2

15
790 150
820

123
Dimensions - VL type (VL-06/12/17/20/25/36)

7.2kV, 31.5kA, 1250/2000A


Withdrawable Fs type unit, phase distance 150mm
495.4
150 150

567.8
400.8

538.5
450 227 Stroke:225

295
705
400.5

345
205
13
522 62.8 288
53.2 386
514.8

Withdrawable Fs type cradle, phase distance 150mm

40 20 40 20 5-Ø12
38 749 40 20
(Mounting Hole)
70

40

40
180

180
70

40

180
40

481
613
585
530
503
180

180
40

180
40
70

24-Ø14
12-Ø14 24-Ø14
1250A 2000A

600
150 150

Rating 12 A 2 A
A 10 20
A
295
780
A
359.2
30.7

250 772 150


48

15

975

124
Susol VCB

7.2kV, 31.5kA, 2000A


Withdrawable K type unit T type, phase distance 150mm
516
150 150

616
669
350

328 Stroke:225
450

295
692.5

676
48
332.5
230.5
104.5
288 32 12.5
13 351
522 53 383
436
Withdrawable K type unit T2 type, phase distance 150mm
516
150 150
616
669
350

7.2/12kV,31.5kA,1250A, 150, K Type (T)

450 328 Stroke:225


295
48
692.5

676
332.5
230.5
104.5

288 32
32.5

13 351
522 53 383
436

125
Dimensions - VL type (VL-06/12/17/20/25/36)

7.2kV, 31.5kA, 2000A


Withdrawable G type cradle T type, phase distance 150mm
VIEW "C"
150 150
26

26
(Mounting
hole)

560
83
295
(Mounting hole)

100 660

S ST: 225

ST: 225

48
VIEW

295
"C"
1235

345
1250A: 12t
2000A: 25t

285

S
600 12 100 660 156
731.5
946

Withdrawable MCSG cradle T2 type, phase distance 150mm

150 150
60
26
26

150
600
560
83

150

(Mounting hole)

100 662

1250A:12t
2000A:25t
295
1235
630

731.5
946

126
Susol VCB

7.2kV, 31.5kA, 2000A


Withdrawable H type unit, phase distance 150mm

194
112

110
A

Note) Please be informed that When B-type connecter is


used to design switchgears, the height can be 110mm
higher based on “A”

Racking in/out
Stroke:220

127
Dimensions - VL type (VL-06/12/17/20/25/36)

7.2kV, 31.5kA, 2000A


Withdrawable H type cradle, phase distance 150mm
317 323.4 42.3
25
(For assembly of (Mounting hole)
lifting hook and LV
compartment

150 150
mounting hole)

550.4
(Mounting hole)
725 202.7
1017.7

(Mounting hole) (Mounting hole)

310
465
65 285 150 150 277.7
550

(Mounting hole)

Around assembling hole of earthing


switch stator, cut the heat-shrinkable
tube to both upper and lower direction.

Connecting busbar method


(with earthing switch)
20 Busbar : 10t 75 (2 sheets)
68.3
10.0

TUBE
30

25
Detail A

68.3
20
2-M8 (DP:18)
43.4

See Detail A Detail A

128
Susol VCB

12/17.5kV, 20/25kA, 630/1250A


Fixed P type, phase distance 150mm

M12(Earthing hole)

46.8
96.5

Fixed P type, phase distance 210mm

M12(Earthing hole)
46.8

96.5

129
Dimensions - VL type (VL-06/12/17/20/25/36)

12/17.5kV, 20/25kA, 630/1250A


Withdrawable Compatible with existing E type unit, phase distance 210mm
210 210

613.5
311.5

670
302

295
670

650
310
103 286
670 78 483
715 94.5 315
655.5

Withdrawable Compatible with existing F type unit, phase distance 210mm


695
210 210
613.5
311.5

670
302
295
670

650
310
169.5

103 286
670 78 483
715 94.5 315
655.5

130
Susol VCB

12/17.5kV, 20/25kA, 630/1250A


Withdrawable E type unit, phase distance 210mm

Withdrawable F type unit, phase distance 210mm

131
Dimensions - VL type (VL-06/12/17/20/25/36)

12kV, 20/25kA, 630/1250A


Withdrawable K type unit T type, phase distance 150mm
516
150 150

616
669
350

328 Stroke:225
450

295
Ø29
692.5

676
332.5
230.5
104.5
13 288 32 12.5
351
522 53 383
436

Withdrawable K type unit T2 type, phase distance 150mm


516
150 150
616
669
350

328 Stroke:225
450
295
Ø29
692.5

676
332.5
230.5
104.5

288
13 351 32
32.5

522 53 383
436

132
Susol VCB

12/17.5kV, 20/25kA, 630A


Withdrawable Compatible with existing E cradle, phase distance 210mm
Racking in/out
164 Stroke:182
70
2-M6 TAP
40
20
(Earthing hole)

11.8

210
139
766.4

690
725

210
50
270 440 340

295
720.2
6
87.2

326
278.5
800 860 40
1050

12/17.5kV, 20/25kA, 630A


Withdrawable Compatible with existing E cradle, phase distance 210mm
Racking in/out
164 Stroke:182
70
2-M6 TAP
40
20

(Earthing hole)
11.8

210
139
766.4
725
690

210
60

270 440 340


295
720.2
87.2

10
326

278.5
800 860 40
1050

133
Dimensions - VL type (VL-06/12/17/20/25/36)

12/17.5kV, 20/25kA, 630A


Withdrawable Compatible with existing F cradle, phase distance 210mm
Racking in/out
164 Stroke:182
70
2-M6 TAP
40
20

11.8
(Earthing hole)

210
766.4

690
725

210
50
270 440 340

295
720.2
6
87.2

326.2
278.5
800 860 55
1050

12/17.5kV, 20/25kA, 1250A


Withdrawable Compatible with existing F cradle, phase distance 210mm
Racking in/out
164 Stroke:182
70
2-M6 TAP 40
20

(Earthing hole)
11.8

210
139
766.4

690
725

210
60

270 440 340


295
10

720.2
87.2

326.2

278.5
800
860 40
1050

134
Susol VCB

12/17.5kV, 20/25kA, 630/1250A


Withdrawable E type cradle, phase distance 210mm
Racking in/out
Stroke:182

(Earthing hole)

(Mounting hole)

278.5

Withdrawable F type cradle, phase distance 210mm

Racking in/out
Stroke:182

(Earthing hole)

(Mounting hole)

278.5

135
Dimensions - VL type (VL-06/12/17/20/25/36)

12/17.5kV, 20/25kA, 630/1250A


Withdrawable H type unit, phase distance 150mm

194
112

110
A

Note) Please be informed that When B-type connecter is


used to design switchgears, the height can be 110mm
higher based on “A”

Racking in/out
Stroke:200

Withdrawable H type unit, phase distance 210mm

194
112
110

Note) Please be informed that When B-type connecter is


used to design switchgears, the height can be 110mm
higher based on “A”

Racking in/out
Stroke: 220

136
Susol VCB

12/17.5kV, 20/25kA, 630/1250A


Withdrawable H type cradle, phase distance 150mm

317 323.4 42.3


M12 (DP:25)
(For assembly of (Mounting hole)
lifting hook and LV
compartment
mounting hole)

150 150
550
(Mounting hole)
725 183.7
1017.7

600 650 560

(Mounting hole)
(Mounting hole)

400

400
1120

205
400

400

445
212.5

212.5

65 285 150 150 258.7

(Mounting hole)
550

Around assembling hole of earthing Around assembling hole of earthing


switch stator, cut the heat-shrinkable switch stator, cut the heat-shrinkable
tube to both upper and lower direction. tube to both upper and lower direction.

Connecting busbar method Connecting busbar method


(with earthing switch) (with earthing switch)
Busbar : 8t 40 (2 sheets) <1250A Busbar : 8t 40 (1 sheets) <630A
20 20
87.3 87.3
10.0

TUBE TUBE
30
30

Detail A Detail A

87.3
20

2-M8 (DP:18)
43.4

See Detail A Detail A

137
Dimensions - VL type (VL-06/12/17/20/25/36)

12/17.5kV, 20/25kA, 630/1250A


Withdrawable H type cradle, phase distance 210mm
317 323.4 42.3 M12 (DP:25)

(For assembly of (Mounting hole)


lifting hook and LV
compartment

210
mounting hole)

700

210
(Mounting hole)
725 183.7
1017.7

(Mounting hole)
(Mounting hole)

65 285 150 150 258.7

(Mounting hole)
700

Around assembling hole of earthing Around assembling hole of earthing


switch stator, cut the heat-shrinkable switch stator, cut the heat-shrinkable
tube to both upper and lower direction. tube to both upper and lower direction.

Connecting busbar method Connecting busbar method


(with earthing switch) (with earthing switch)
Busbar : 8t 40 (2 sheets) <1250A 20 Busbar : 8t 40 (1 sheets) <630A
20
87.3 87.3
10.0

TUBE TUBE
30
30

Detail A Detail A

87.3
20

2-M8(DP:18)
63.4

See Detail A Detail A

138
Susol VCB

12/17.5kV, 20/25kA, 2000A


Fixed P type, phase distance 210mm

M12(Earthing hole)

46.8
96.5

Withdrawable E type unit, phase distance 210mm

139
Dimensions - VL type (VL-06/12/17/20/25/36)

12/17.5kV, 20/25kA, 2000A


Withdrawable F type unit, phase distance 210mm

Withdrawable E type cradle, phase distance 210mm

(Earthing hole)

(Mounting hole)

140
Susol VCB

12/17.5kV, 20/25kA, 2000A


Withdrawable F type cradle, phase distance 210mm

(Earthing hole)

(Mounting hole)

141
Dimensions - VL type (VL-06/12/17/20/25/36)

12/17.5kV, 20/25kA, 2000A


Withdrawable H type unit, phase distance 150mm

194
112

110
A

Note) Please be informed that When B-type connecter is


used to design switchgears, the height can be 110mm
higher based on “A”

Racking in/out
Stroke:220

Withdrawable H type unit, phase distance 210mm

194
112
110

Note) Please be informed that When B-type connecter is


used to design switchgears, the height can be 110mm
higher based on “A”

Racking in/out
Stroke:220

142
Susol VCB

12/17.5kV, 20/25kA, 2000A


Withdrawable H type cradle, phase distance 150mm

317 323.4 42.3


25
(For assembly of (Mounting hole)
lifting hook and LV
compartment

150 150
mounting hole) 2-M12 (DP:25)

550

(Mounting hole)
725 202.7
1017.7

(Mounting hole) (Mounting hole)

65 285 150 150 277.7


550

(Mounting hole)

Around assembling hole of earthing


switch stator, cut the heat-shrinkable
tube to both upper and lower direction.

Connecting busbar method


(with earthing switch)
20 Busbar : 10t 75 (2 sheets)
68.3
10.0

TUBE
30

25
Detail A

68.3
20

2-M8 (DP:18)
43.4

See Detail A Detail A

143
Dimensions - VL type (VL-06/12/17/20/25/36)

12/17.5kV, 20/25kA, 2000A


Withdrawable H type cradle, phase distance 210mm
317 323.4 42.3

(For assembly of (Mounting hole) 2-M12 (DP:25)


lifting hook and LV
compartment

210 210

25
mounting hole)

700

(Mounting hole)
725 183.7
1017.7

(Mounting hole) (Mounting hole)

65 285 150 150 258.7


700

(Mounting hole)

Around assembling hole of earthing


switch stator, cut the heat-shrinkable
tube to both upper and lower direction.

Connecting busbar method


(with earthing switch)
20 Busbar : 10t 75 (2 sheets)
87.3
10.0

TUBE
30
25

Detail A

87.3
20

2-M8(DP:18)
63.4

See Detail A Detail A

144
Susol VCB

12/17.5kV, 31.5kA, 630/1250A


Fixed P type, phase distance 150mm

M12(Earthing hole)

46.8
96.5

Fixed P type, phase distance 210mm

M12(Earthing hole)
46.8

96.5

145
Dimensions - VL type (VL-06/12/17/20/25/36)

7.2/12kV, 31.5kA, 1250/2000A


Withdrawable Gs type unit, phase distance 150mm
150 150

668.8
426.8

639.5
450 328 Stroke:225

295
705
400.5

345
208.5
13
522 62.8 288
53.2 386
615.8

Withdrawable Gs type cradle, phase distance 150mm

5-Ø12 38 749 177


(Mounting Hole)

25
2-M12
150
613

530
585

481
503

150

DETAIL A

600
150 150
DETAIL A
295
780
349.2
30.7

250 825
48

15

1042

146
Susol VCB

12kV, 31.5kA, 1250A


Withdrawable K type unit T type, phase distance 150mm
516
150 150

616
669
350

328 Stroke:225
450

295
692.5

676
48
332.5
230.5
104.5
288 32 12.5
13 351
522 53 383
436

Withdrawable K type unit T2 type, phase distance 150mm


516
150 150
616
669
350

7.2/12kV,31.5kA,1250A, 150, K Type (T)

450 328 Stroke:225


295
48
692.5

676
332.5
230.5
104.5

288 32
32.5

13 351
522 53 383
436

147
Dimensions - VL type (VL-06/12/17/20/25/36)

12kV, 31.5kA, 1250A


Withdrawable G type cradle T type, phase distance 150mm
VIEW "C"
150 150
26

26
(Mounting
hole)

560
83
295
(Mounting hole)

100 660

S ST: 225

ST: 225

48
VIEW

295
"C"
1235

345
1250A: 12t
2000A: 25t

285

S
600 12 100 660 156
731.5
946

Withdrawable MCSG cradle T2 type, phase distance 150mm

150 150
60
26
26

150
600
560
83

150

(Mounting hole)

100 662

1250A:12t
2000A:25t
295
1235
630

731.5
946

148
Susol VCB

12kV, 31.5kA, 2000A


Withdrawable K type unit T type, phase distance 150mm
516
150 150

616
669
350

328 Stroke:225
450

295
692.5

676
48
332.5
230.5
104.5
288 32 12.5
13 351
522 53 383
436

Withdrawable K type unit T2 type, phase distance 150mm


516
150 150
616
669
350

7.2/12kV,31.5kA,1250A, 150, K Type (T)

450 328 Stroke:225


295
48
692.5

676
332.5
230.5
104.5

288 32
32.5

13 351
522 53 383
436

149
Dimensions - VL type (VL-06/12/17/20/25/36)

12kV, 31.5kA, 2000A


Withdrawable G type cradle T type, phase distance 150mm
VIEW "C"
150 150
26

26
(Mounting
hole)

560
83
295
(Mounting hole)

100 660

S ST: 225

ST: 225

48
VIEW

295
"C"
1235

345
1250A: 12t
2000A: 25t

285

S
600 12 100 660 156
731.5
946

Withdrawable MCSG cradle T2 type, phase distance 150mm


150 150
60
26
26

150
600
560
83

150

(Mounting hole)

100 662

1250A:12t
2000A:25t
295
1235
630

731.5
946

150
Susol VCB

12/17.5kV, 31.5kA, 630/1250A


Withdrawable H type unit, phase distance 150mm
490
150 150
194
112

110
607
660
A
440
Note) Please be informed that When B-type connecter is
used to design switchgears, the height can be 110mm
higher based on “A”

492 319 Stroke: 200

310
35
688

623.5
280
154
76
320 25
21.5
19.5
4

13 358
503
53 383
469

Withdrawable H type unit, phase distance 210mm

194
112
110

A
7.2/12/17.5kV,31.5kA,630/1250A, 150, H Type
Note) Please be informed that When B-type connecter is
used to design switchgears, the height can be 110mm
higher based on “A”

Racking in/out
Stroke: 220

151
Dimensions - VL type (VL-06/12/17/20/25/36)

12/17.5kV, 31.5kA, 630/1250A


Withdrawable H type cradle, phase distance 150mm

(For assembly of
lifting hook and LV (Mounting hole)
compartment
mounting hole)

(Mounting hole)

(Mounting hole)
(Mounting hole)

(Mounting hole)

Around assembling hole of earthing Around assembling hole of earthing


switch stator, cut the heat-shrinkable switch stator, cut the heat-shrinkable
tube to both upper and lower direction. tube to both upper and lower direction.

Connecting busbar method Connecting busbar method


(with earthing switch) (with earthing switch)
Busbar : 10t 40 (2 sheets) <1250A Busbar : 8t 40 (1 sheets) <630A

152
Susol VCB

12/17.5kV, 31.5kA, 630/1250A


Withdrawable H type cradle, phase distance 210mm
317 323.4 42.3
(For assembly of M12(DP:25)
lifting hook and LV (Mounting hole)
compartment
mounting hole)

210
210
35

(Mounting hole)
725 183.7
1112.7

750 650 37.5 710

(Mounting hole) (Mounting hole)

400
400

310
1120

400

400

465
212.5
212.5

65 285 150 150 258.7

(Mounting hole)
700

Around assembling hole of earthing Around assembling hole of earthing


switch stator, cut the heat-shrinkable switch stator, cut the heat-shrinkable
tube to both upper and lower direction. tube to both upper and lower direction.

Connecting busbar method Connecting busbar method


(with earthing switch) (with earthing switch)
20 Busbar : 10t 40 (2 sheets) <1250A 20 Busbar : 8t 40 (1 sheets) <630A
87.3 87.3
10.0

30
30

87.3
20
2-M8(DP:18)
63.4

DETAIL A
SCALE 2/15

SEE DETAIL A

153
Dimensions - VL type (VL-06/12/17/20/25/36)

12/17.5kV, 31.5kA, 2000A


Fixed P type, phase distance 210mm

M12(Earthing hole)

46.8
96.5

Withdrawable H type unit, phase distance 150mm

194
112
110

Note) Please be informed that When B-type connecter is


used to design switchgears, the height can be 110mm
higher based on “A”

Racking in/out
Stroke:220

154
Susol VCB

12/17.5kV, 31.5kA, 2000A


Withdrawable H type unit, phase distance 210mm

194
112

110
A

Note) Please be informed that When B-type connecter is


used to design switchgears, the height can be 110mm
higher based on “A”

Racking in/out
Stroke:220

155
Dimensions - VL type (VL-06/12/17/20/25/36)

12/17.5kV, 31.5kA, 2000A


Withdrawable H type cradle, phase distance 150mm
317 323.4 42.3
25
(For assembly of (Mounting hole)
lifting hook and LV
compartment

150 150
mounting hole)

550.4

14(Mounting hole)
725 202.7
1112.7

600 650 37.5 560

(Mounting hole)
(Mounting hole)

400
400

310
1120

400
400

465
212.5

212.5

65 285 150 150 277.2


550

(Mounting hole)

Around assembling hole of earthing


switch stator, cut the heat-shrinkable
tube to both upper and lower direction.

Connecting busbar method


(with earthing switch)
Busbar : 10t 80 (2 sheets)
20
68.3
10.0

30

25

DETAIL B

68.3
20
2-M8(DP:18)
43.4

DETAIL B
SCALE 2/15

SECTION A-A SEE DETAIL B

156
Susol VCB

12/17.5kV, 31.5kA, 2000A


Withdrawable H type cradle, phase distance 210mm
317 323.4 42.3
M12(DP:25)
(For assembly of
lifting hook and LV (Mounting hole)
compartment
mounting hole)

210

25
210
14(Mounting hole)
725 183.7
1112.7

750 650 37.5 710

(Mounting hole) (Mounting hole)

400
400

310
1120

400

400

465
212.5
212.5

65 285 150 150 258.7

(Mounting hole)
700

Around assembling hole of earthing


switch stator, cut the heat-shrinkable
tube to both upper and lower direction.

Connecting busbar method


(with earthing switch)
20 Busbar : 10t 80 (2 sheets)
87.3
10.0

30

DETAIL A

87.3
20
2-M8(DP:18)
63.4

DETAIL A
SCALE 1/6
SEE DETAIL A

157
Dimensions - VL type (VL-06/12/17/20/25/36)

12/17.5kV, 31.5kA, 2500A


Fixed P type, phase distance 210mm
753
210 210 6- 14
Earthing position 100
40

60
4- 13

178
212
152

523.5
10
M12(Earthing hole)

281

46.8
96.5

455
600 212

295
20

690
670

650
320
315 156
670
523.5
789
606.5

Fixed P type, phase distance 275mm


883.5
275 275
Earthing position 100
12/17.5kV,31.5kA,2500A,상간210, P Type
60

4- 13
178
212
152

523.5

M12
10

281

(Earthing hole)
46.8

96.5

800 212
295
20
670

650
320

800 315 156


919.5 523.5

158

12/17.5kV,31.5kA,2500A,상간275, P Type
Susol VCB

12/17.5kV, 31.5kA, 2500A


Withdrawable H type unit, phase distance 210mm
640
210 210
194
112

110
589
642
A

359.5
Note) Please be informed that When B-type connecter is
used to design switchgears, the height can be 110mm
higher based on “A”

640 301 Stroke:220

310
79
688

280
165
76
19.5
21.5
320 25 4
13 358
653
53 383
469

Withdrawable H type unit, phase distance 275mm


840
275 275
194
112
12/17.5kV,31.5kA,2500A,상간210, H Type
110
589
642

A
359.5

Note) Please be informed that When B-type connecter is


used to design switchgears, the height can be 110mm
higher based on “A”

890 301 Stroke:220


310
79
688

646.5
280
165
76

320 25
21.5
19.5
4

13 358
853 53 383
469

159

12/17.5kV,31.5kA,2500A,상간275, H Type
Dimensions - VL type (VL-06/12/17/20/25/36)

12/17.5kV, 31.5A, 2500A


Withdrawable H type cradle, phase distance 210mm
317 323.4 42.3
(For assembly of 35 M12(DP:25)
lifting hook and LV (Mounting hole)
compartment
mounting hole)

35
210
210
14(Mounting hole)

725 197.2
1017.2

750 650 37.5 710

(Mounting hole) (Mounting hole)

400
400

310
1120

400

400

465
212.5
212.5

65 285 150 150 272.2

(Mounting hole)
700

Around assembling hole of earthing


switch stator, cut the heat-shrinkable
tube to both upper and lower direction.

Connecting busbar method


(with earthing switch)
Busbar : 10t 100 (2 sheets)
20
73.8 35
32.5
10.0

35
35

73.8
20

2-M8(DP:18)
63.4

DETAIL A
SCALE 2/15
SEE DETAIL A

160
Susol VCB

12/17.5kV, 31.5A, 2500A


Withdrawable H type cradle, phase distance 275mm

317 323.4 42.3 35 4-M12 (DP:25)


(For assembly of
lifting hook and LV (Mounting hole)
compartment
mounting hole)

35
275
950.4

275
(Mounting hole)
725 197.2
1017.2

1000 650 37.5 960

(Mounting hole) (Mounting hole)

400

400

310
1120

400

400

465
212.5

212.5

65 285 150 150 272.2

(Mounting hole)
950

Around assembling hole of earthing


switch stator, cut the heat-shrinkable
tube to both upper and lower direction.

Connecting busbar method


(with earthing switch)
Busbar : 10t 100 (2 sheets)
20
73.8 35
32.5
10.0

35
35

73.8
20

2-M8(DP:18)
63.4

SEE DETAIL A DETAIL A

161
Dimensions - VL type (VL-06/12/17/20/25/36)

24/25.8kV 12.5kA 630A


Fixed P type, phase distance 265mm

(Earthing hole)

Withdrawable E type unit Visible, Clip contact, phase distance 265mm

162
Susol VCB

24/25.8kV 12.5kA 630A


Withdrawable F type unit Visible, Clip contact, phase distance 265mm
830
265 265
38

617.5
311.5

700 306

340
10

805
805

400
126.5
103 312
700 72 493
94.5 335
745
659.5

Withdrawable E type unit Enclosed, Tulip contact, phase distance 265mm

265 265
576
311.5

700 264.5
120
340
805
805

29
400

312
103
443
700 72 451.5
745 94.5 335
618

163
Dimensions - VL type (VL-06/12/17/20/25/36)

24/25.8kV 12.5kA 630A


Withdrawable F type unit Enclosed, Tulip contact, phase distance 265mm
830
265 265

576
311.5

700 264.5

120
340
805
805

29
400
126.5
312
103
443
700 72 451.5
745 94.5 335
618

Withdrawable G type unit Tulip contact, phase distance 265mm

830
265 265
671.5
311.5

700 360
340
29

805
805

400
126.5

103 312
72 547
700
94.5 335
745
713.5

164
Susol VCB

24/25.8kV 12.5kA 630A


Withdrawable G type unit, phase distance 210mm
210 210
60

139.5
379.5

576
600 301.5 264.5

76
120
340
805
805

29

400
103 94.5 72
600 312
645 335
443
451.5
618

Withdrawable K type unit, phase distance 210mm

656
210 210
767
820
437

600 479.5 Stroke: 310


340
29
827.5

827.5
422.5
301.5
185.5

13 350 50
12.5

653 53 437
463

165
Dimensions - VL type (VL-06/12/17/20/25/36)

24/25.8kV 12.5kA 630A


Withdrawable K type unit, phase distance 265mm
825
265 265

767
820
437

600 479.5 Stroke: 310

340
29

827.5
827.5

422.5
301.5
185.5
13 350 50

12.5
886 53 437
463

Withdrawable H type unit, phase distance 210mm


640
210 210
194
112
110
746
799

A
458

Note) Please be informed that When B-type connecter is


used to design switchgears, the height can be 110mm
higher based on “A”

458 Stroke: 300


636
310
35
770

756
325
198
4

72

13 365 35
19.5
21.5

653
403
53 438
524

166
Susol VCB

24/25.8kV 12.5kA 630A


Withdrawable H type unit, phase distance 275mm
840
275 275
194
112

110
746
799
A

458
Note) Please be informed that When B-type connecter is
used to design switchgears, the height can be 110mm
higher based on “A”

836 458 Stroke: 300

310
35
770

756
325
198
4

72
13 365 35

19.5
21.5
853 403
53 438
524

24/25.8kV 12.5kA 1250A


Fixed P type, phase distance 265mm

(Earthing hole)

167
Dimensions - VL type (VL-06/12/17/20/25/36)

24/25.8kV 12.5kA 1250A


Withdrawable E type unit Visible, Clip contact, phase distance 265mm

Withdrawable F type unit Visible, Clip contact, phase distance 265mm

830
265 265
58
617.5
311.5

700 306
340
10

805
805

400
126.5

103 312
72 493
700
94.5 335
745
659.5

168
Susol VCB

24/25.8kV 12.5kA 1250A


Withdrawable E type unit Enclosed, Tulip contact, phase distance 265mm
265 265

576
311.5

700 264.5

120
340
805
805

29
400
312
103 443
700 72 451.5
745 94.5 335
618

Withdrawable F type unit Enclosed, Tulip contact, phase distance 265mm

830
265 265
576
311.5

700 264.5
120
340
805
805

29
400
126.5

312
103
443
700 72 451.5
745 94.5 335
618

169
Dimensions - VL type (VL-06/12/17/20/25/36)

24/25.8kV 12.5kA 1250A


Withdrawable G type unit Tulip contact, phase distance 265mm
830
265 265

671.5
311.5

700 360

340
29

805
805

400
126.5
103 312
700 72 547
745 94.5 335
713.5

24/25.8kV 12.5kA 1250A & 16/25kA 630/1250A


Withdrawable G type unit, phase distance 210mm
210 210
139.5
379.5

576
301.5

600 264.5
76
120
340
29

805
805

400

103 94.5 72
600 312
335
645 443
451.5
618

170
Susol VCB

24/25.8kV 12.5kA 1250A


Withdrawable K type unit, phase distance 210mm
656
210 210

767
820
437

600 479.5 Stroke: 310

340
29

827.5
827.5

422.5
301.5
185.5
13 350 50 12.5
653 53 437
463

Withdrawable K type unit, phase distance 265mm

479.5 Stroke: 310


340
29

840
422.5
301.5
185.5

350 50
12.5

437
53 463

171
Dimensions - VL type (VL-06/12/17/20/25/36)

24/25.8kV 12.5kA 1250A


Withdrawable H type unit, phase distance 210mm
640
210 210
194
112

110
746
799
A
458

Note) Please be informed that When B-type connecter is


used to design switchgears, the height can be 110mm
higher based on “A”

458 Stroke: 300


636

310
35
770

756
325
198
72
4
13 365 35
19.5
21.5
653 438
53 471
524

Withdrawable H type unit, phase distance 275mm


840
275 275
194
112
110
746
799

A
458

Note) Please be informed that When B-type connecter is


used to design switchgears, the height can be 110mm
higher based on “A”

836 458 Stroke: 300


310
35
770

756
325
198
4

72

13 365 35
19.5
21.5

853 403
53 438
524

172
Susol VCB

24/25.8kV 16/25kA 630A


Fixed P type, phase distance 265mm

(Earthing hole)

24/25.8kV 16kA 630A


Withdrawable E type unit Visible, Clip contact, phase distance 265mm
265 265
38
617.5
311.5

700 306
340
10

805
805

400

103 312
72 493
700
94.5 335
745 659.5

173
Dimensions - VL type (VL-06/12/17/20/25/36)

24/25.8kV 16kA 630A


Withdrawable F type unit Visible, Clip contact, phase distance 265mm
830
265 265
38

617.5
311.5

700 306

340
10

805
805

400
126.5
103 312
700 72 493
745 335
659.5

24/25.8kV 16/25kA 1250A


Fixed P type, phase distance 265mm

(Earthing hole)

174
Susol VCB

24/25.8kV 25kA 630A & 24/25.8kV 16/25kA 1250A


Withdrawable E type unit Visible, Clip contact, phase distance 265mm

Withdrawable F type unit Visible, Clip contact, phase distance 265mm

830
265 265
58
617.5
311.5

700 306
340
10

805
805

400
126.5

103 312
72 493
700
94.5 335
745
659.5

175
Dimensions - VL type (VL-06/12/17/20/25/36)

24/25.8kV 16/25kA 630/1250A


Withdrawable E type unit Enclosed, Tulip contact, phase distance 265mm

265 265

576
311.5

700 264.5

120
340
805
805

29
400
312
103 443
700 72 451.5
745 94.5 335
618

Withdrawable F type unit Enclosed, Tulip contact, phase distance 265mm

830
265 265
576
311.5

700 264.5
120
340
805
805

29
400
126.5

312
103
443
700 72 451.5
745 94.5 335
618

176
Susol VCB

24/25.8kV 16/25kA 630/1250A


Withdrawable G type unit Tulip contact, phase distance 265mm
830
265 265

671.5
311.5

700 360

340
29

805
805

400
126.5
103 312
700 72 547
745 94.5 335
713.5

Withdrawable K type unit, phase distance 210mm

656
210 210
767
820
437

600 479.5 Stroke: 310


340
29

827.5
827.5

422.5
301.5
185.5

13 350 50
12.5

653 53 437
463

177
Dimensions - VL type (VL-06/12/17/20/25/36)

24/25.8kV 16/25kA 630/1250A


Withdrawable K type unit, phase distance 265mm

479.5 Stroke: 310

340
29

840
422.5
301.5
185.5
350 50

12.5
437
53 463

Withdrawable H type unit, phase distance 210mm

640
210 210
194
112
110
746
799

A
458

Note) Please be informed that When -type connecter is


used to design switchgears, the height can be 110mm
higher based on “A”

458 Stroke: 300


636
310
35
770

756
325
198
72
4

13 365 35
19.5
21.5

653 438
53 471
524

178
Susol VCB

24/25.8kV 16/25kA 630/1250A


Withdrawable H type unit, phase distance 275mm
840
275 275 194
112

110
746
799
A

458
Note) Please be informed that When -type connecter is
used to design switchgears, the height can be 110mm
higher based on “A”

836 458 Stroke: 300

310
35
770

756
325
198
4

72
13 365 35

19.5
21.5
853 403
53 438
524

24/25.8kV 25kA 2000A


Fixed P type, phase distance 265mm

(Earthing hole)

179
Dimensions - VL type (VL-06/12/17/20/25/36)

24/25.8kV 25kA 2000A


Withdrawable E type unit Visible, Clip contact, phase distance 265mm
265 265
78

617.5
311.5

700 306

340
10

805
805

400
103 312
700 72 493
745 94.5 335
659.5

Withdrawable F type unit Visible, Clip contact, phase distance 265mm

830
265 265
78
617.5
311.5

700 306
340
20

805
805

400
126.5

103 312
700 72 493
745 94.5 335
659.5

180
Susol VCB

24/25.8kV 25kA 2000A


Withdrawable E type unit Enclosed, Tulip contact, phase distance 265mm
265 265

576
311.5

700 264.5

120
340
805
805

48
400
103 312
700 443
745 72 451.5
94.5 335
618

Withdrawable F type unit Enclosed, Tulip contact, phase distance 265mm

830
265 265
576
311.5

700 264.5
120
340
805
805

48
400
126.5

103 312
443
700 72 451.5
745 94.5 335
618

181
Dimensions - VL type (VL-06/12/17/20/25/36)

24/25.8kV 25kA 2000A


Withdrawable G type unit, phase distance 210mm
210 210
60

139.5
379.5

576
301.5
600 264.5

95
120
340
48
805

805
400
103 94.5 72
600 312
645 335
443
451.5
618

Withdrawable K type unit, phase distance 265mm


825
265 265
767
820
437

479.5 Stroke: 310


840
340
48

827.5
827.5

422.5
301.5
185.5

350 50
12.5

886 13 437
53 463
516

182
Susol VCB

24/25.8kV 25kA 2000A


Withdrawable H type unit, phase distance 210mm
640
210 210
194
112

110
746
799
447.5 A

Note) Please be informed that When B-type connecter is


used to design switchgears, the height can be 110mm
higher based on “A”

636 458 Stroke: 300

310
48
770

756
345
181
4

89
13 365 35
19.5
21.5
653 403
53 438
524

Withdrawable H type unit, phase distance 275mm


840
275 275
194
112
110
746
799

A
447.5

Note) Please be informed that When B-type connecter is


used to design switchgears, the height can be 110mm
higher based on “A”

836 458 Stroke: 300


310
48
770

756
345
181
89
4

13 365 35
19.5
21.5

853
403
53 438
524

183
Dimensions - VL type (VL-06/12/17/20/25/36)

24/25.8kV 25kA 2500A


Withdrawable H type unit, phase distance 275mm
840
275 275
194
112

110
746
799
A

447.5
Note) Please be informed that When B-type connecter is
used to design switchgears, the height can be 110mm
higher based on “A”

836 458 Stroke: 300

310
79
770

756
345
181
89
4
13 365 35

21.5
19.5
853 403
53 438
524

24/25.8kV 12.5/16/25kA 630/1250/2000A


Withdrawable E type cradle Visible, Clip contact, phase distance 265mmm

Rating A B T
630, 1250A 768 190.5 10
2000A 778 185.5 20

<Terminal conductor> <Earthing terminal>


(12.5/16kA 630A) (25kA 630A) (12.5/16/25kA 1250A) (25kA 2000A)
Insulation Barrier
(Earthing hole)
65

43
42
45 67

660
85

120
65

168 260
265

Ø6.5 Earthing
300

2-Ø14 2-Ø14 4-Ø14 4-Ø14


145
820

85
65

85
45

40 20 40 20 40 20 40 20
252.5

179
225

300
215
265

7-Ø14
25

120
65

(Mounting hole)
85
45

110 400 400 210

184
Susol VCB

24/25.8kV 12.5/16/25kA 630/1250/2000A


Withdrawable F type cradle Visible, Clip contact, phase distance 265mm

Insulation
Barrier

Rating A B T
630, 1250A 768 190.5 10
2000A 778 185.5 20

<Terminal conductor> <Earthing terminal>


(12.5/16kA 630A) (25kA 630A) (12.5/16/25kA 1250A) (25kA 2000A)
Insulation Barrier
65

43
(Earthing hole)

42
45 67

660

85

120
65

168 260
265

Ø6.5 Earthing

300
2-Ø14 2-Ø14 4-Ø14 4-Ø14
145
820

85
65

85
45

40 20 40 20 40 20 40 20
252.5

179
225

300
215
265

7-Ø14
25

120
65

(Mounting hole)
85
45

110 400 400 210

24/25.8kV 12.5/16/25kA 630/1250/2000A


Withdrawable E type cradle Enclosed, Tulip contact, phase distance 265mm

185
Dimensions - VL type (VL-06/12/17/20/25/36)

24/25.8kV 12.5/16/25kA 630/1250/2000A


Withdrawable F type cradle Enclosed, Tulip contact, phase distance 265mm

24/25.8kV 12.5/16/25kA 630/1250A


Withdrawable G type cradle Tulip contact, phase distance 265mm

186
Susol VCB

24/25.8kV 12.5/16/25kA 630A


Withdrawable G type cradle, Tulip contact, phase distance 210mm
300 300
6-Ø14
260 260
40

40

210
400
210 210

1120
400
300
34.7

110

720
860 6-Ø14(Mounting Hole)
920
239

288.5
10
340
1033
.5°
72

404.5
631 954.5 Ø11(Earthing Hole)
661 1122.5

24/25.8kV 12.5/16/25kA 1250A


Withdrawable G type cradle, Tulip contact, phase distance 210mm
6-Ø14 300 300
235 235 65
40

210
400

210 210
1120
400
300
34.7

110

720
860 6-Ø14(Mounting Hole)
920
239
288.5
10
340
1033

.5°
72
404.5

631 954.5 Ø11(Earthing Hole)


661 1122.5

187
Dimensions - VL type (VL-06/12/17/20/25/36)

24/25.8kV 12.5/16/25kA 2000A


Withdrawable G type cradle, Tulip contact, phase distance 210mm
300 300
12-Ø14 220 220
40 80
40

210
400
210 210

1120
400
300
34.7

110

720
860 6-Ø14(Mounting Hole)
920
239

283.5
20
340
1033
.5°
72

409.5
631 954.5 Ø11(Earthing Hole)
661 1122.5

24/25.8kV 12.5/16/25kA 630/1250/2000A


Withdrawable K type cradle Enclosed, Tulip contact, phase distance 210/265mm

Note) In case of phase distance 210mm ( ) means dimensions and 630A, 1250A areavailable only
Items : VCL-20K13B06, VCL-20K13B13, (G-type closed Tulip way, 630A, 1250A)

188
Susol VCB

24/25.8kV 12.5/16/25kA 630/1250A


Withdrawable H type cradle, phase distance 210mm

(For assembly of
lifting hook and LV (Mounting hole)
compartment
mounting hole)

(Mounting hole)

(Mounting hole)
(Mounting hole)

(Mounting hole)

Around assembling hole of earthing Around assembling hole of earthing


switch stator, cut the heat-shrinkable switch stator, cut the heat-shrinkable
tube to both upper and lower direction. tube to both upper and lower direction.

Connecting busbar method Connecting busbar method


(with earthing switch) (with earthing switch)
Busbar : 10t 40 (2 sheets) <1250A Busbar : 10t 40 (1 sheets) <630A

DETAIL A
DETAIL A

SEE DETAIL A
DETAIL A

189
Dimensions - VL type (VL-06/12/17/20/25/36)

24/25.8kV 12.5/16/25kA 630/1250A


Withdrawable H type cradle, phase distance 275mm
367 413.4 42.3
(For assembly of
lifting hook and LV (Mounting hole)
M12(DP: 25)
compartment
mounting hole)

275
275

35
(Mounting hole)
865 275.5
1239.5

1000 790 37.5 960


(Mounting hole)
(Mounting hole)

455

455

310
1230

455

455

510
212.5

212.5

65 285 220 220 350.5

(Mounting hole)
950

Around assembling hole of earthing Around assembling hole of earthing


switch stator, cut the heat-shrinkable switch stator, cut the heat-shrinkable
tube to both upper and lower direction. tube to both upper and lower direction.
12 12
Connecting busbar method Connecting busbar method
(with earthing switch) (with earthing switch)
Busbar : 10t 40 (2 sheets) <1250A Busbar : 10t 40 (1 sheets) <630A
20 20
87.3 87.3
14 14
2- 12 2- 12
10.0

30

30

DETAIL A DETAIL A

87.3
20
2-M8(DP: 18)
63.4

SEE DETAIL A DETAIL A

190
Susol VCB

24/25.8kV 25kA 2000A


Withdrawable H type cradle, phase distance 210mm
367 413.4 42.3
(For assembly of
lifting hook and LV (Mounting hole) M12(DP: 25)
compartment
mounting hole)

210 210

25
750.4

49
(Mounting hole)
865 275.5
1239.5

800 790 37.5 760


(Mounting hole)
(Mounting hole)

455

455

310
1230

455

455

530
212.5

212.5

65 285 220 220 350.5

(Mounting hole)
750

Around assembling hole of earthing


switch stator, cut the heat-shrinkable
tube to both upper and lower direction.
12
Connecting busbar method
(with earthing switch)
20 Busbar : 10t 20 (2 sheets)
87.3 14

2- 12
10.0

30
25

DETAIL A

87.3
20

2-M8(DP: 18)
63.4

SEE DETAIL A DETAIL A

191
Dimensions - VL type (VL-06/12/17/20/25/36)

24/25.8kV 25kA 2000A


Withdrawable H type cradle, phase distance 275mm
367 413.4 42.3
(For assembly of
lifting hook and LV (Mounting hole)
compartment
mounting hole) 2-M 12(DP: 25)

275
950.4

25
275

49
(Mounting hole)
865 275.5
1239.5

1000 790 37.5 960


(Mounting hole)
(Mounting hole)

455

455

310
1230

455

455

530
212.5

212.5

65 285 220 220 350.5

(Mounting hole)
950

Around assembling hole of earthing


switch stator, cut the heat-shrinkable
tube to both upper and lower direction.
12
Connecting busbar method
(with earthing switch)
20 Busbar : 10t 80 (2 sheets)
87.3 14

2- 12
10.0

30
25

DETAIL A

87.3
20

2-M8(DP: 18)
63.4

SEE DETAIL A DETAIL A

192
Susol VCB

24/25.8kV 25kA 2500A


Withdrawable ■ H type cradle, phase distance 275mm

(For assembly of
lifting hook and LV
compartment
mounting hole)

(Mounting hole)

(Mounting hole)
(Mounting hole)

(Mounting hole)

Connecting busbar method


(with earthing switch)
Busbar : 10t×100 (2 sheets)

193
Dimensions - VL type (VL-06/12/17/20/25/36)

36kV 25kA 630/1250A


Fixed P type, phase distance 275mm
895
275 275 2-Ø14
60

40
4-Ø13
M12

243
315.5
255.5
10
(Earthing hole)

705.5

43
369
97

760
802 315.5

380

1043.5
1003.5

15

970.5
492.5
403 221
811
705.2
931
857.7

Withdrawable H type unit, phase distance 275mm

848.4
275 275
1048.5
995
600

629 Stroke: 440mm


853
Ø92

380
Ø32
1004.5

983
462
244.3
134.3

12.8 516
19.5
21.5
21.5

853 574 37.3


53 611
695

194
Susol VCB

36kV 25kA 630/1250A


Withdrawable H type cradle, phase distance 275mm

4-Ø14 494 613.7 44


(For assembly of 2-Ø14 M12(DP:25)
lifting hook and LV (Mounting hole)
compartment
mounting hole)

275 275
950.4

Ø35
1194 335
1624

1000 1125 31.5 960


6-Ø11 6-Ø11
(Mounting hole) (Mounting hole)

565

530
1700

380
565

530

665
212.5

212.5
8-Ø11 65 427 277.4 300 459.6
(Mounting hole)
951

Around assembling hole of earthing Around assembling hole of earthing


switch stator, cut the heat-shrinkable switch stator, cut the heat-shrinkable
tube to both upper and lower direction. tube to both upper and lower direction.
Ø12 Ø12
Connecting busbar method Connecting busbar method
(with earthing switch) (with earthing switch)
Busbar : 10t 50 (1 sheets) <630A Busbar : 12t 60 (1 sheets) <1250A
87.3 87.3
4 4
Ø1 Ø1
30

30
128.5

128.5

Ø12 Ø12

TUBE TUBE

2-Ø 2-Ø
12 12
20

20

Section B-B Section B-B


Scale 2/15 Scale 2/15

87.3 56
M8(DP:18)
25
73.6
20

Detail A
Scale 2/15

Section B-B See Detail A

195
Dimensions - VL type (VL-06/12/17/20/25/36)

36kV 25kA 2000A


Fixed P type, phase distance 275mm
895
275 275 2-Ø14
80
40

40
4-Ø13 M12

315.5
243
(Earthing hole)

10
255.5

43
705.5
369
97

760
802 315.5

380

1043.5
1003.5

970.5
20
492.5
403 221
811
705.5
931 858

Withdrawable H type unit, phase distance 275mm

848.4
275 275
1048.3
995
600

629 Stroke: 440mm


853
Ø95

380
Ø48
1004.5

983
462
244.3
134.3

12.8 516
21.5
19.5
21.5

853 574 37.3


53 611
695

196
Susol VCB

36kV 25kA 2000A


Withdrawable H type cradle, phase distance 275mm

4-Ø14 494 613.7 44


(For assembly of 2-Ø14 M12(DP:25)
lifting hook and LV (Mounting hole)
compartment
mounting hole)

275 275
950.4
SCALE 3/10

Ø49
1194 335
1624

1000 1125 31.5 960


6-Ø11 6-Ø11
(Mounting hole) (Mounting hole)

565

530
1700

380
565

530

665
212.5

212.5

8-Ø11 65 427 277.4 300 459.6


(Mounting hole)
951

Around assembling hole of earthing


switch stator, cut the heat-shrinkable
tube to both upper and lower direction.
Ø12
Connecting busbar method
4

(with earthing switch)


Ø1

Busbar : 12t 60 (2 sheets) <2000A


25 30

87.3
12

141

Ø12

2-
Ø1
20

TUBE

87.3 56
M8(DP:18)
25
73.6
20

Detail A
Scale 2/15

Section A-A See Detail A

197
Dimensions - VL type (VL-06/12/17/20/25/36)

36kV 25kA 2500A


Fixed P type, phase distance 275mm

895
275 275 6-Ø14
100
40

60
M12

315.5
243
255.5
10
(Earthing hole)

43
705.5
369
97

760
802 315.5

380
20

1043.5
1003.5

970.5
492.5
403 221
811
705.5
931
858

Withdrawable H type unit, phase distance 275mm

848.4
275 275
1048.3
995
600

629 Stroke: 440mm


853
Ø126

380
Ø79
1004.5

983
462
244.3
134.3

12.8 516
19.5
21.5
21.5

853 574 37.3


53 611
695

198
36kV,25kA,2500A,P275,H Type
Susol VCB

36kV 25kA 2500A


Withdrawable ■ H type cradle, phase distance 275mm

(For assembly of
lifting hook and LV (Mounting hole)
compartment
mounting hole)

(Mounting hole) (Mounting hole)

(Mounting hole)

Around assembling hole of earthing


switch stator, cut the heat-shrinkable
tube to both upper and lower direction.

Connecting busbar method


(with earthing switch)
Busbar : 12t×80 (2 sheets) <2500A>

199
Dimensions - LVB, VH type (LVB, VH-06/12)

7.2kV, 40kA, 1250/2000A


Fixed P type, phase distance 150mm
80
150 150 60 2- 14 40 4- 14

20

20
2-M12(Earthing hole)

40

40
118
271
1250A(E, F type) 2000A(E, F type)

125.5 4- 13
553
478

20
295
130

670
670

20
286.6

320
115.5 400.6 117
515 547
589
A type connector Q type connector

Withdrawable E,F,G type unit, phase distance 150mm


150 150

60 80 60 80
468.5

1250A 2000A 1250A 2000A


(E, F type) (E, F type) (G type) (G type)

125.5

478
295
130

670

670
286.6

310
169.5

115.5 Used only for F and G types


515 582.5 - 2 EA at both sides
A type connector Q type connector

200
Susol VCB

7.2/12kV, 40kA, 1250/2000A


Withdrawable MCSG type unit, phase distance 150mm: option type T
150 150

689

528 15
516
478

295
130

702.5
705.5

702.5
342.5
319.1

114.5 126

115.5 350.7 47

3
501 388.5
618
A type connector Q type connector
668

7.2/12kV, 31.5/40kA, 1250/2000A


Withdrawable MCSG type unit, phase distance 150mm: option type T2(standard)
150 150
689

528 15
516
478
295
130

715.5
715.5
725.5

355.5
127.5 126
332.1

115.5 350.7 60
10

496 388.5
618
A type connector Q type connector 668

201
Dimensions - LVB, VH type (LVB, VH-06/12)

7.2kV, 40kA 1250/2000A


Withdrawable E type cradle, phase distance 150mm
Only for 50 Racking in/out Stroke:175
40 20 40 20
3 position type 12
(Earthing hole)

87.5 90 80 90 87.5
70 105 70 105 70
180

180

139
50

525
180

180
2- 14 4- 14
7- 12
1250A 2000A 260 410 210
(Mounting hole)

Rating 12 A 2 A
150 150 A 10 20

A
295
720.2
23.2 A
326.2
600 790 15
820
940

Withdrawable F, G type cradle, phase distance 150mm

Only for 50 Racking in/out Stroke:175


40 20 40 20
3 position type 12
(Earthing hole)
87.5 90 80 90 87.5
70 105 70 105 70

180
180

139

50
525
180
180

4- 14 2- 14
2- 14
1250A 2000A 7- 12 260 410 210
(Mounting hole)

Rating 12 A 2 A
A 10 20
150 150
A
295
720.2
23.2 A
326.2

600 790 15
820
940

202
Susol VCB

7.2/12kV, 40kA 1250/2000A


Withdrawable MCSG type cradle, phase distance 150mm

(Mounting hole)

203
Dimensions - LVB, VH type (LVB, VH-06/12)

7.2kV, 31.5/40kA, 3150A


Fixed P type, phase distance 210mm
210 210
110 6- 14
M-12(Earthing hole) 80

20
69 4040
330
125.5 4- 13
703 (Mounting hole)
620

40
350
750.5

750.5
130

40
328.5
286.6

115.5 463.6 104 M-12


665 597 (Earthing hole)
739

A type connector Q type connector

Withdrawable E,F,G type unit, phase distance 210mm


210 210
507.5
436.5

125.5

620
360
750.5

750.5
130

303.5
286.6

129

115.5 507.5 Used only for type


665 630 - 2 EA at both sides
680

A type connector Q type connector

204
Susol VCB

7.2kV, 31.5/40kA, 3150A


Withdrawable MCSG type unit, phase distance 210mm
210 210

693
714 16.5
690
620

360
795.5
805.5
795.5
130

140.2 135.6
331.6

348.5
115.5 321.7 60

10
687 450.6
624.7
A type connector Q type connector 674.4

12kV, 31.5/40kA, 3150A


Withdrawable MCSG type unit, phase distance 210mm
210 210
693

714 16.5
690
620
360
795.5
805.5
130

795.5
140.2 135.6
331.6

348.5

115.5 321.7 60
10

687 450.6
624.7
A type connector Q type connector 674.4

205
Dimensions - LVB, VH type (LVB, VH-06/12)

7.2kV, 31.5/40kA 3150A


Withdrawable E type cradle, phase distance 210mm
Only for 50 Racking in/out Stroke:175
3 position type
50
80 (Earthing hole)
50

139
50

675
4-M12 DP25

210 210 7- 12 265 530 135


(Mounting hole)

940.2
309.7 360
23.4
750 825 15
877
930

Withdrawable F, G type cradle, phase distance 210mm


Only for 50 Racking in/out Stroke:175
3 position type
50
80 (Earthing hole)
50

139

4-M12 DP25

7- 12 265 530 135


210 210 (Mounting hole)
940.2
309.7
23.4

750 825 15
877
930

206
Susol VCB

7.2/12kV, 31.5/40kA 3150A


Withdrawable MCSG type cradle, phase distance 210mm

(Mounting hole)

207
Dimensions - VH type (VH-06/12/17/20/25/36)

7.2kV 40kA 1250/2000A


Withdrawable Fs type unit, phase distance 150mm
150 150

400.5

584
478
227 Stroke:225

295
130

703

342.5
319.1

205
62.5 294
528 12

3
53.5 388
A type connector Q type connector 514.5

Withdrawable Fs type cradle, phase distance 150mm

40 20 40 20 5-Ø12
38 749 40 20
(Mounting Hole)
70

40

40
180

180
70

40

180
40

481
613
585
530
503
180

180
40

180
40
70

24-Ø14
12-Ø14 24-Ø14
1250A 2000A

600
150 150

Rating 12 A 2 A
A 10 20
A
295
780
A
359.2
30.7

250 772 150


48

15

975

208
Susol VCB

7.2kV, 31.5/40kA, 3150A


Withdrawable Fs type unit, phase distance 210mm
210 210

462.6 714
620 335 Stroke:220

360
Ø79
808.5
805
130

357.5
336

129.3
3.5
12 Ø79
53.5 442.5
673 475.5
Q type connector 644.5

Withdrawable Fs type cradle, phase distance 210mm

5-Ø12 50
(Mounting hole)
50
786.4

750
672
750
674

4-M12 DP25

DETAIL A

26 869
210 210
DETAIL A
360
990
361.2
22

925
73

38.7

1030

209
Dimensions - VH type (VH-06/12/17/20/25/36)

7.2/12kV, 40kA, 1250/2000A


Withdrawable Gs type unit, phase distance 150mm
150 150

427

687.5
478 330.5 Stroke:225

295
Ø48
130

703
706

342.5
319.1

205.5
12 62.5 294
528

3
53.5 388
A type connector Q type connector 618

Withdrawable Gs type cradle, phase distance 150mm

5-Ø12 38 749 177


(Mounting Hole)

25
2-M12
150
613

530
585

481
503

150

DETAIL A

600
150 150
DETAIL A
295
780
349.2
30.7

250 825
48

15

1042

210
Susol VCB

7.2/12kV, 31.5/40kA, 3150A


Withdrawable Gs type unit, phase distance 210mm
210 210

422.6
714
620 335 Stroke:220

360
Ø79
808.5
805
130

357.5
336

138.4
3.5
12 53.5 442.5 Ø79
673 475.5
Q type connector 644.5

Withdrawable Gs type cradle, phase distance 210mm


5-Ø12
(Mounting hole)
40
5-M12
786.4
750
674

672
750

40

DETAIL A
26 869

210 210 473.2 DETAIL A


360
990
361.2
22

925
38.7
73

1056.5

211
Dimensions - VH type (VH-06/12/17/20/25/36)

7.2/12kV, 40kA, 1250/2000A


Withdrawable K type unit, phase distance 150mm, G / T (T) compatible
687.5
150 150 330.5 Stroke: 225

295
48
137.5 126

355.5
53.5 350.7
528 11.8 60
388.5

10
618
478
130

716
726
332.1

496
A type connector Q type connector

Withdrawable K type unit, phase distance 150mm, G / T (T2) compatible


687.5
150 150 330.5 Stroke: 225
295
48
137.5 126

355.5

53.5 350.7
528 11.8 60
388.5
10

618
478
130

716
726
332.1

496
A type connector Q type connector

212
Susol VCB

7.2/12kV, 40kA, 1250/2000A


Withdrawable K type cradle, phase distance 150mm

1250/2000A G class

Section S-S
VIEW "C"

Rating 12 A 2 A (Mounting hole)


A 12 25
B 48

(Mounting hole)

Withdrawable MCSG cradle T2 type, phase distance 150mm

4-Ø14
(Mounting hole)
VIEW "A"
2-Ø13 60
12 25
26
26
660

83
290

(1250A) (2000A)
100

560 260
Section S-S
S 225 38 12
(stroke)
150 150
46

A
295
295
203

1235

10
46

205.5
630
17

S
537 946
600

213
Dimensions - VH type (VH-06/12/17/20/25/36)

7.2/12/17.5kV, 40kA, 1250/2000A


Withdrawable K type unit, phase distance 210mm, G / T (T2) compatible
705.7
210 210 326.7 Stroke: 240

360
48
180.7 120
358.2
10
670 11.8
54 328.2
80
443
636.2
620
799.2
809.2
130
336.2

644
Q type connector
A type connector

Withdrawable MCSG cradle T2 type, phase distance 210mm

(Earthing hole)

214
(Mounting hole)
Susol VCB

7.2/12kV, 31.5/40kA, 3150A


Withdrawable K type unit, phase distance 210mm, G / T (T2) compatible
696
210 210 317 Stroke: 240

360
Ø79
181 120
358.5
714 11.8

10
Ø80
53.5 328.2
441
626.5

620
799.5
809.5
130
336.5

737.6
Q type connector
A type connector

Withdrawable MCSG cradle T2 type, phase distance 210mm


24
360
360

1300
639

61

800 1013.8

210 210
230 230
24

110 120 115 6-Ø14


107.8

70
35
145
724

360

RUN
293

100

715
6-Ø14 (Mounting hole) 230 230
760

215
Dimensions - VH type (VH-06/12/17/20/25/36)

17.5kV, 40kA, 3150A


Withdrawable K type unit, phase distance 254mm, G / T (T) compatible
703.7
254 254 324.7 Stroke: 240

360
79
180.7 120
358.2
11.8

10
814
54 328.2 80
443
634.2
774
799.2
809.2
130
340.2

788
Q type connector
A type connector

Withdrawable MCSG cradle T2 type, phase distance 254mm

(Earthing hole)

(Mounting hole)

216
Susol VCB

7.2/12kV, 40kA, 1250A


Withdrawable H type unit, phase distance 150mm
150 150

522 11.8
714
538 357 Stroke: 220

295
48
130

750.3
753.9

363.5
336

123.5 89
53.5 386.2 79
495

3.5
442.5
644.5

7.2/12kV, 40kA, 2000A


Withdrawable H type unit, phase distance 150mm
150 150

522 11.8
714
538
357 Stroke: 220
295
48
130

750.3
753.8

363.5
336

123.5 89
3.5

53.5 386.2 79
495
442.5
644.5

217
Dimensions - VH type (VH-06/12/17/20/25/36)

7.2/12kV, 40kA, 1250/2000A


Withdrawable H cradle, phase distance 150mm
780
720
150 150
A

292.7
73
2-M12(DP:25mm)

61.5 61.5
8-Ø13

780
680 2-Ø 8.4
25
50 <Earthing S/W stator
mounting hole>
37.5

Detail A
Scale 3/10

650
565

295
1230
73

545
350
185

284.6 459
81.8

524 780

252 90.3 Tulip contact area when product


is inserted : 15±1mm
Ø49
909
764

364
105

59
459 See Detail A
Section A-A
Around assembling hole of earthing
switch stator, cut the heat-shrinkable
tube to both upper and lower direction.
Ø8
Connecting busbar method
(with earthing switch)
Busbar : 10t 80 (2 sheet) <1250/2000A
56.8
Ø8 Ø12
27

218
Susol VCB

7.2/12/17.5kV, 40kA, 1250/2000A


Withdrawable H type unit, phase distance 210mm
210 210

673 11.8

714
692 335 Stroke: 220

360
48
806.5
130

803

357.5
336

124 89
3.5
645 53.5 414 79
442.5
644.5

7.2/12/17.5kV, 31.5/40kA, 3150A


Withdrawable H type unit, phase distance 210mm
210 210

673 11.8
714
692 335 Stroke: 220
360

A
79
806.5
130

803

357.5
336

124 89

3.5

53.5 475.5
673 79
442.5
644.5

219
Dimensions - VH type (VH-06/12/17/20/25/36)

7.2/12/17.5kV, 40kA, 1250/2000A


Withdrawable H cradle, phase distance 210mm
930
870
100 2-M12 (DP : 25mm)
210 210
37.5 25

292.7

37.5
71.5
8-Ø13

81.5
680
780
2-Ø 8.4
37.5

50 50 <Earthing S/W stator


mounting hole>
Detail A
Scale 1/5
800
719.6
A

360
1230
73

539
350
185

A 484
81.8

362.1
803.4
674

252.3 Tulip contact area when product


is inserted : 15±1mm
90.3
Ø49
909
814

105
354
181

59
484 See Detail A

Around assembling hole of earthing


switch stator, cut the heat-shrinkable
tube to both upper and lower direction.
Ø8
Connecting busbar method
(with earthing switch)
Busbar : 12t 60 (2 sheet) <1250/2000A
57.3
Ø12
Ø8
27

220
Susol VCB

7.2/12/17.5kV, 31.5/40kA, 3150A


Withdrawable H cradle, phase distance 210mm
930
100
870
210 210 40 5-M12 (DP : 25mm)
20

291.7

85

40
75
8-Ø13

81.5

20
780
680
2-Ø 8.2
<Earthing S/W stator
37.5

50 mounting hole>
Detail A
Scale 1/5
800
715.6

360
1230
73

539
350
185
81.8

A
361.9 484
803.4
674

252.3 90.3 Tulip contact area when product


is inserted : 15±1mm
Ø79
909
814

105
358

59
484
See Detail A
Section A-A
Around assembling hole of earthing
switch stator, cut the heat-shrinkable
tube to both upper and lower direction.
Ø8
Connecting busbar method
(with earthing switch)
Busbar : 10t 120 (2 sheet) <3150A
57.3

Ø8
35

221
Dimensions - VH type (VH-06/12/17/20/25/36)

17.5kV, 31.5/40kA, 3150A


Withdrawable H type unit, phase distance 275mm

275 275

853 11.8

714
890 335 Stroke: 220

360
79
808.5
130

805

357.5
332

124 89
3.5
54 414 79
826
442.5
644.5

222
Susol VCB

17.5kV, 31.5/40kA, 3150A


Withdrawable H cradle, phase distance 275mm

1130
1070 100
275 275 40
20 5-M12 (DP : 25mm)

291.7

20
85
8-Ø13

40
75
81.5
780
680
37.5 2-Ø 8.2
<Earthing S/W stator
mounting hole>
50
Detail A
Scale 1/5
1000
915.6
A

360
1230
73

539
350
185

A
484
81.8

461.9
803.4
855

252.3 90.3 Tulip contact area when product


is inserted : 15±1mm
Ø79
911.3
814

358
105
181

59 Section A-A See Detail A


484

Around assembling hole of earthing


switch stator, cut the heat-shrinkable
tube to both upper and lower direction.
Ø8
Connecting busbar method
(with earthing switch)
Busbar : 10t 120 (2 sheet) <3150A
56.8

Ø8
35

223
Dimensions - VH type (VH-06/12/17/20/25/36)

7.2/12/17.5kV, 50kA, 1250/2000A


Fixed P type, phase distance 210mm

2-M12 (DP:25)

25
610
862.5
816
130

M12
(Earthing hole)
285

108
115.5 94 137
360 144
602
695

Withdrawable H type unit, phase distance 210mm

Racking in/out
12 725 Stroke:220
653
353
644
340
48
130

380
335

89
193.5

412
72
3.5
42

447
53 656

224
Susol VCB

7.2/12/17.5kV, 50kA, 1250/2000A


Withdrawable H cradle, phase distance 210mm

42.3 317 378.4


2-M12 (DP:25)

25
(For assembly of

210
lifting hook and LV
compartment

210

49
mounting hole)

780 187
1073

750 705 37.5 710

(Mounting hole) (Mounting hole)

450

450

340
1325

450

450

565
212.5

65 285 200 200 217 212.5

(Mounting hole)

Around assembling hole of earthing Around assembling hole of earthing


switch stator, cut the heat-shrinkable switch stator, cut the heat-shrinkable
tube to both upper and lower direction. tube to both upper and lower direction.
Connecting busbar method Connecting busbar method
(with earthing switch) (with earthing switch)
Busbar : 12t 60 (1 sheet) <1250A Busbar : 12t 60 (2 sheets) <2000A
60

60

12 84.3 20
84.3 20
12

30
30

TUBE TUBE

84.3
20
2-M8 (DP:18)
63.3

See Detail A Detail A

225
Dimensions - VH type (VH-06/12/17/20/25/36)

7.2/12/17.5kV, 50kA, 2500/3150A


Fixed P type, phase distance 275mm

4-M12 (DP:25)

50
79
50

750
862.5
130

M12
(Earthing hole)
285

108
115.5 94
786 360 114 142
864 602
695

Withdrawable H type unit, phase distance 275mm

12
Racking in/out
725 Stroke:220
844 353
340
869.5
130

380
335

89
193.5

400
42
3.5

447
53 656

226
Susol VCB

7.2/12/17.5kV, 50kA, 2500/3150A


Withdrawable H cradle, phase distance 275mm
352 413
30
(Mounting hole) 4-M12 (DP:25)

4-M12

50
(For assembly of
lifting hook and LV
compartment
mounting hole) 50

(Mounting hole)
825 239.5
1167

1000 750 37.5 950

(Mounting hole) (Mounting hole)

450

450

340
1325

450

450

565
212.5

212.5

60 300 210 230 264.5

(Mounting hole)

Around assembling hole of earthing Around assembling hole of earthing


switch stator, cut the heat-shrinkable switch stator, cut the heat-shrinkable
tube to both upper and lower direction. tube to both upper and lower direction.

Connecting busbar method Connecting busbar method


(with earthing switch) (with earthing switch)
100
80

Busbar : 12t 80 (2 sheets) <2500A Busbar : 12t 100 (2 sheets) <3150A


90.8 20 90.8 20
25 25
25 25
12

12
30

30

TUBE TUBE
25

25

90.8
20

2-M8 (DP:18)
49.4

See Detail A Detail A

227
Dimensions - VH type (VH-06/12/17/20/25/36)

7.2/12/17.5kV, 40/50kA, 4000A


Fixed P type, phase distance 275mm
980
157 275 275

614.6
661 65 4-M12 DP30
380

65
400
290

819
949

27

421
864
980

Withdrawable H type unit, phase distance 275mm

157 275 275


702

380 Stroke: 310


400
290

819
999
738.5

27
474.5

864 410
568.6
3.5

906
708.6

228
Susol VCB

7.2/12/17.5kV, 40/50kA, 4000A


Withdrawable Ha type cradle, phase distance 275mm, Normal Type
1000

68
387

1294
479

81
908

275 275

400
400

1294
561.5
561.5

1030.8 11.3 210


1150.8
1183.5

327 270
309 220
210 50
M12
5
40
40
228

240
340
50

50

40
424.7

Section A-A

229
Dimensions - VH type (VH-06/12/17/20/25/36)

7.2/12/17.5kV, 40/50kA, 4000A


Withdrawable Ha type cradle, phase distance 275mm, with Earthing Switch
(The same applies to MOC or TOC)

1000
387

68
81
908

1000
275 275

400
1485
479
752.5
14.3
447

200

1030.8
1150.8
1183.5

327 270
309 220
210 50
M12
40
5
40
340
228

240
50

50

425

Section A-A

230
Susol VCB

7.2/12/17.5kV, 40/50kA, 4000A


Withdrawable Hb type cradle, phase distance 275mm
1050

77
908

1083.5
389
400
2015
1226

1050

250 275 275


455.9

210 315

231
Dimensions - VH type (VH-06/12/17/20/25/36)

7.2/12kV, 40/50kA, 5000A


Withdrawable H type unit, phase distance 320mm
320 320

1.6

Stroke: 300

410
340
929.5

929.5
6.3

926

389.5
350
1009 27 410
1031 700.5
1033

Withdrawable Ha type cradle, phase distance 320mm, Normal Type


407
38
1219

41

1013.3 1038
162.5

1133.3 1130
1149

320 320
M16 90
90

410
476.5

529.5

232
Susol VCB

7.2/12kV, 40/50kA, 5000A


Withdrawable Ha type cradle, phase distance 320mm, with Earthing Switch
(The same applies to MOC or TOC)

259
686
436

968
1038
1130.6
1152.2

320 320
35 295 90
4-M16(Mounting Hole)
295

90
410
1409.7

667.2
105.3

211

1014 320 320


Ø14(Earthing Hole)
1133.3 747
1149.01
1218.3

233
Dimensions - VH type (VH-06/12/17/20/25/36)

24kV, 25kA, 2500A


Fixed P type, phase distance 275mm

4-M12 (DP:25)

214
320
834

750
130

M12
(Earthing hole)
287.5

110.5
115.5 118 142
786 174
864

Withdrawable H type unit, phase distance 275mm

12
853
Racking in/out
857 Stroke:310
850 445
340
130

440
80
335

225

497
3.5
41.5

535
53 788

234
Susol VCB

24kV, 25kA, 2500A


Withdrawable H cradle, phase distance 275mm

352 558
30
(Mounting hole)
4-M12 4-M12 (DP:25)
(For assembly of
lifting hook and LV

50
275
compartment
mounting hole)

275
50

(Mounting hole)
970 240
1312

1000 895 37.5 950

(Mounting hole) (Mounting hole)

500

500

340
1380

500

500

625
212.5
212.5

60 300 280 300 270

(Mounting hole)

Around assembling hole of earthing


switch stator, cut the heat-shrinkable
tube to both upper and lower direction.

Connecting busbar method


(with earthing switch)
80

Busbar : 12t 80(2 sheets)


90.3 20
25
25
12

30

TUBE
25

90.3
20

2-M8 (DP:18)
49.4

See Detail A Detail A

235
Dimensions - VH type (VH-06/12/17/20/25/36)

24kV, 31.5/40kA, 1250/2000A


Fixed P type, phase distance 210mm

2-M12 (DP:25)

610
130

M12
(Earthing hole)
287.5

110.5
115.5 118 137
174

Withdrawable H type unit, phase distance 210mm

12
653
Racking in/out
857 Stroke:310
652 445
340
130

440
80
335

225

497
41.5
3.5

535
53 788

236
Susol VCB

24kV, 31.5/40kA, 1250/2000A


Withdrawable H cradle, phase distance 210mm
352 558
30
(Mounting hole)

4-M12

25
(For assembly of

210 210
lifting hook and LV
compartment
mounting hole) 2-M12 (DP:25)

(Mounting hole)
970 239.5
1302

800 895 37.5 750

(Mounting hole) (Mounting hole)

500

500

340
1380

500

500

625
212.5

212.5
60 300 280 300 269.5

(Mounting hole)

Around assembling hole of earthing Around assembling hole of earthing


switch stator, cut the heat-shrinkable switch stator, cut the heat-shrinkable
tube to both upper and lower direction. tube to both upper and lower direction.

Connecting busbar method Connecting busbar method


(with earthing switch) (with earthing switch)
60

60

12 Busbar : 12t 60 (1 sheets) <1250A 85.8 20 Busbar : 12t 60 (2 sheets) <2000A


85.8 20
12

30
30

TUBE TUBE

85.8
20

2-M8 (DP:16)
49.4

See Detail A Detail A

237
Dimensions - VH type (VH-06/12/17/20/25/36)

24kV, 31.5/40kA, 1250/2000A


Withdrawable H cradle, Rotated bushing type, phase distance 210mm

210 210

25
2-M12 (DP:25)

970 239.5
1302

800 895 37.5 750

(Mounting hole)
(Mounting hole)

500

500

340
1380

500

500

625
212.5

212.5
60 300 280 300 269.5

(Mounting hole)

238
Susol VCB

24kV, 31.5/40kA, 1250/2000A


Withdrawable H cradle, phase distance 210mm

2-M12 (DP:25)

750
130

M12
(Earthing hole)
287.5

110.5
115.5 118 142
174

Withdrawable H type unit, phase distance 210mm

12
853
Racking in/out
857 Stroke:310
850 445
340
130

440
80
335

225

497
41.5
3.5

535
53 788

239
Dimensions - VH type (VH-06/12/17/20/25/36)

24kV, 31.5/40kA, 1250/2000A


Withdrawable H cradle, phase distance 275mm

352 558
30
(Mounting hole)
4-M12

25
(For assembly of
lifting hook and LV

275
compartment 2-M12 (DP:25)
mounting hole)

275
(Mounting hole)
970 239.5
1302

1000 895 37.5 950

(Mounting hole) (Mounting hole)

500

500

340
1380

500

500

625
212.5

212.5

60 300 280 300 269.5

(Mounting hole)

Around assembling hole of earthing


switch stator, cut the heat-shrinkable
tube to both upper and lower direction.
Connecting busbar method
(with earthing switch)
Busbar : 12t 60 (2 sheets)
60

85.8 20
12

30

TUBE

85.8
20

2-M8 (DP:18)
49.4

See Detail A Detail A

240
Susol VCB

24kV, 31.5/40kA, 3150A


Fixed P type, phase distance 275mm

4-M12 (DP:25)

(Mounting hole)

750
130

M12
(Earthing hole)
287.5

110.5
115.5 118 142
786 174
864

Withdrawable H type unit, phase distance 275mm

12
853
Racking in/out
857 Stroke:310
850 445
340
130

440
335

80
225

497
41.5
3.5

535
53 788

241
Dimensions - VH type (VH-06/12/17/20/25/36)

24kV, 31.5/40kA, 3150A


Withdrawable H cradle, phase distance 275mm

352 558
30
(Mounting hole)
4-M12 4-M12 (DP:25)
(For assembly of
lifting hook and LV

50
275
compartment
mounting hole)

275
50

(Mounting hole)
970 240
1312

1000 895 37.5 950

(Mounting hole) (Mounting hole)

500

500

340
1380

500

500

625
212.5
212.5

60 300 280 300 270

(Mounting hole)

Around assembling hole of earthing


switch stator, cut the heat-shrinkable
tube to both upper and lower direction.

Connecting busbar method


(with earthing switch)
100

Busbar : 12t 100 (2 sheets)


90.3 20
25
25
12

30

TUBE
25

90.3
20

2-M8 (DP:18)
49.4

See Detail A Detail A

242
Susol VCB

36kV, 25/31.5/40kA, 1250/2000A


Fixed P type, phase distance 300mm

M12

(Mounting hole)
1042.5

551.5
294.1

(Earthing hole)
220.1

115.5
Withdrawable H type unit, phase distance 300mm
(Relative connection conductor)

Racking in/out
Stroke:440
8.5

8.5

243
Dimensions - VH type (VH-06/12/17/20/25/36)

36kV, 25/31.5/40kA, 1250/2000A


Withdrawable H type cradle, phase distance 300mm
40 1194 466
180 255 35 61

11-M8

43

300
Mounting TAP Mounting hole

300

221.5 221.5
402
1150
1100
900

300
570

300
300
24

300
20 Duct hole for wiring

6-M5
Mounting TAP
6-M8 45
Mounting TAP
Mounting hole 65 270 270

1200
1100
300 300
A (symmetrically)

60
Mounting hole 23.5
288

9-M8
Mounting TAP 7 14
480

40
288

216.5
480
2165
2150

2200

400
216.5

See Detail A
600

53.5
480

15
901
600

480

604
104
140

140

A
485 649 360.5 25 1194 608 66
740
846

Remove both side of shrink tube


30 40 127.5 30 for bolting busbar when using Cu PIPE
14
60

300 300 300


24-M8
7 Mounting TAP
STS HEX M8X70 BOLT
268 268 268

BUS BAR: 60 X 12t


53.5

Using Cu PIPE(2ea) as right figure


Detail A Scale 1/5
or Bending BUSBAR(53.5mm)
734 365 30
<For connecting BUSBAR> Mounting hole
2140

488

290
285
268 268 268

Mounting hole
285

Remove the plates for


203.8

both sides when


290

assembled in pannel
300 300 300 Duct hole for wiring
40

52

185 300 300 1160

563

244
Susol VCB

36kV, 25/31.5/40kA, 3150A


Fixed P type, phase distance 300mm

M12

(Mounting hole)
1042.5

551.5
(Earthing hole)
294.1

220.1

115.5
Withdrawable H type unit, phase distance 300mm
(Relative connection conductor)

Racking in/out
Stroke:440
8.5

8.5

245
Dimensions - VH type (VH-06/12/17/20/25/36)

36kV, 25/31.5/40kA, 3150A


Withdrawable H type cradle, phase distance 300mm

25 1194 466

40
14
300
296.5 40
201.5

300

12
10
221.5
1200 505
A

<Detail dimension for bushing part>


2200

400
1520

855

203.8
50.5

290

61 563 463
56.12

A
46

120
740 1226.7 140.5
846
873.4

Ø25
30 40 127.5 30 Remove both side of shrink tube
for bolting busbar when using Cu PIPE
110
40

14

7 Ø10
STS HEX M8X70 BOLT

BUSBAR: 110 X 12t


28.5

Ø19
Using Cu PIPE(2ea) as right figure
Detail A or Bending BUSBAR(28.5mm)
Ø8.5

<For connecting BUSBAR>

See Detail A
28.5

Remove the plates for


both sides when
203.8
604

assembled in pannel
104

25 1194 568 66 185 300 300


14(Earthing hole) 563

* Mounting information is same as 36kV 25/31.5/40kA 1250/2000A

246
Side-Mount type VCB Susol VCB

25.8kV 16kA 630A

Item VL-25 16B 06


Rated voltage Ur (kV) 25.8

Rated normal current Ir (A) 630

Rated frequency fr (Hz) 50/60

Rated short-circuit breaking current Isc (kA) 16

Rated short-time withstand current (3 sec) Ik (kA) 16

Rated short-circuit breaking capacity (MVA) 665/715

Rated short-circuit making current Ip (kA) 40/41.6

Rated breaking time (cycle) 3

Rated withstand Power frequency (1 min) Ud (kV) 60


voltage Up (kV) 125
Impulse (1.2 50 )

Rated operating sequence O-0.3s-CO-3min-CO

Control voltage Closing coil (V) DC 24~30V, DC 48~60V, DC 110V, DC 125V, DC 220V, AC 48V, AC 100~130V, AC 200~250V

Trip coil (V) DC 24~30V, DC 48~60V, DC 110V, DC 125V, DC 220V, AC 48V, AC 100~130V, AC 200~250V

Auxiliary contact 5 ,5

Rated opening time (sec) 0.04

No-load closing time (sec) 0.06

Mechanical M1
Type test class Electrical E1

Capacitive current switching C1

Lifetime * Mechanical (time) 2,000

Electrical (time) 2,000

Installation Fixed Right R type

Left L type

Pole centre distance (mm) 210

Weight CB (kg) 95

C IEC 62271-100

* Lifetime with maintenance

247
Side-Mount type VCB

Control circuit diagram


P P Auxiliary switch
P 5a 5b

A1 9 A3 D1 A5 22 24 26 28 40 36 38 50 52 54

LS2 CS
MOTOR POWER SOURCE

CLOSE POWER SOURCE

TRIP POWER SOURCE


22 24 26 28 40 36 38 50 52 54

52a

23 25 27 29 41
M 37 39 51 53 55

C Note1)
UVT TC

A2 10 A4 D2 A6 23 25 27 29 41 37 39 51 53 55
N N N
Closing Spring Contact (Charge switch) <Connecting terminal arrangement>

: External terminal of VCB C : Closing coil(CC) LS2 : Motor stop limit switch
A2 A4 A6 10 D2 23 25 27 29 41 37 39 51 53 55

52 : Vacuum circuit breaker UVT : Under Voltage Trip CS : Closing spring charged
A B
A1 A3 A5 9 D1 22 24 26 28 40 36 38 50 52 54

M : Spring charging motor 52a : Auxiliary switch (a) indication limit switch
TC : Trip coil(SHT) 52b : Auxiliary switch (b)
(5a5b)

Note) 1. UVT : Under Voltage Trip (No. D1, D2) Option


* Closing and Trip coil : One Pulse type
* This circuit diagram is based on 'OFF' status of CB and Closing spring is charged.

Dimension 210 210

145
210 210

M10-DP 25
212.5

120
600
605

818
355.5
38.5

100
169 873
300 1000
M10-DP 20
Note) This external shape is based on “R” Type (Installation type)

Ordering information

Basic model name Rated voltage (kV) Installation type Breaking Phase distance/Compatibility Rated current (A)
e-VCB 25 25.8 R On the right (Fixed type) 16 16 B 210mm 06 680
L On the left (Fixed type)

SA5

Motor control voltage Closing coil voltage Trip coil voltage Aux. contact & wire ass'y UVT Other accessories
M0 Without Motor C0 Without Closing coil T0 Without Trip coil A type connector, U0 Without UVT AA Lead Wire
SA5
M1 DC 110V C1 DC 110V T1 DC 110V 5a5b U1 DC 110V AB User Plug(Part)
M2 DC 220V C2 DC 220V T2 DC 220V U2 DC 220V
M3 DC 125V C3 DC 125V T3 DC 125V U3 DC 125V
M4 DC 24V~30V C4 DC 24V~30V T4 DC 24V~30V U4 DC 24V~30V
M5 DC 48V~60V C5 DC 48V~60V T5 DC 48V~60V U5 DC 48V~60V
M6 AC 48V C6 AC 48V T6 AC 48V U6 AC 48V
M7 AC 100V~130V C7 AC 100V~130V T7 AC 100V~130V U7 AC 100V~130V
M8 AC 200V~250V C8 AC 200V~250V T8 AC 200V~250V U8 AC 200V~250V

247
Technical data Susol VCB

Electrical endurance by interrupting current


Number ops.

Number ops.

Interrupting current kA Interrupting current kA

VI model LV2 at 7.2kV VI model LV3 at 7.2kV


•N : Operation numbers •N : Operation numbers
•I : Interrupting current •I : Interrupting current
Number ops.

Number ops.

Interrupting current kA Interrupting current kA

VI model LV4 at 24kV VI model LV5 at 17.5kV


•N : Operation numbers •N : Operation numbers
•I : Interrupting current •I : Interrupting current

248
Technical data

Electrical endurance by interrupting current


Number ops.

Number ops.

Interrupting current kA Interrupting current kA

VI model LV8 at 17.5kV VI model LV7-P1 at 24kV


•N : Operation numbers •N : Operation numbers
•I : Interrupting current •I : Interrupting current
Number ops.

Interrupting current kA

VI model LV8 at 36kV


•N : Operation numbers Note) 1. Above graphs represent the characteristics of the electrical life of LS Susol VCB.
2. Life characteristics of each model in each rating represents the LOG-LOG graphs.
•I : Interrupting current

249
Susol VCB

Standard Use Environment for Susol VCB


The operation characteristic of Vacuum Circuit Breaker such as insulation and endurance is often influenced
largely by external environment and thus should be applied appropriately with conditions of the place where
it is used taken into consideration.

The following values are the limits have been set in accordance with IEC 62271-100 (IEC 62271-1)

Ambient Temperature
- maximum temperature: 40
- 24-hour average maximum temperature: 35
- minimum temperature: -5

Altitude
- 1000m or less above sea level

Relative Humidity
- 24 hours average value: 95% or less
- One month average: 90% or less

If a standard circuit breaker is used in high temperature exceeding


40 , you are advised to use it according to the current corrected for
each level of ambient temperature in catalog.
If used in conditions of high humidity, the dielectric strength or electric
performance may be degraded.

It is highly recommended to use a dust cover or anti-humid agent if it is


used in dusty and humid conditions.
Excessive vibration may cause a trip breaker such as connection fault
or flaw on mechanical parts.

If it is left ON or OFF for a long time, it is recommended to switch load


current on a regular basis.
It is recommend to put it in the sealed protection if corrosive gas is
prevalent.

250
Technical data

Special Use Environment

The circuit breaker is designed for use in standard use environment specified in Section 2.1 of IEC62271-1.
Concerning the special use environments as below the special use conditions are required to be considered,
thus please contact us in advance.

- where altitude and ambient temperature are out of standard use environment.(-40 )
- where a strong sea breeze blows
- when usually used in a humid place
- where a lot of steam or oil steam exists
- where explosive, flammable and other harmful gases might permeate the breaker
- In a dusty place
- where abnormal vibration or shock exists
- where a lot of ice and snow exist
- other special conditions

it stand voltage compensation according to altitude


If the breaker is used in areas of sea level higher than 1000m the degradation of insulation performance should
be taken into consideration.

70 36 170
50(65) 24 125
38 17.5 95
28(42) 12 75(82)
20 7.2 60
Ud [kV/1min] Ur[kV] Up [kV/1.2 50 ]
Power Frequency Impulse Withstand Voltage
Withstand Voltage

<Table 1 Criteria of withstand voltages by rated voltages specified in IEC62271-1

251
Susol VCB

it stand voltage compensation according to altitude


1.5

Correction parameter 1 1.45

1.4

1.35

1.3

1.25

1.2

1.15

1.1

1.05

1
1000 1500 2000 2500 3000 3500 4000
Altitude (m)

<Fig.1 withstand voltage correction parameter 1 by altitude (based on a required withstand voltage)

1
Correction parameter 2

0.95

0.9

0.85

0.8

0.75

0.7

0.65

0.6

0.55

0.5
1000 1500 2000 2500 3000 3500 4000
Altitude (m)

<Fig.2 withstand voltage correction parameter 2 by altitude (based on a applicable withstand voltage)

E ) Selecting a breaker to be used in a place of 2500m above sea level it a rated voltage 7.2kV
(correction parameter 1 applied)
- Correction parameter at 2500m is 1.2
- Criteria of withstand voltage by rated voltage:
Power Frequency Withstand Voltage (Ud) 20kV, Impulse Withstand Voltage (Up) 60kV
- Requirements withstand voltage criteria:
Power Frequency Withstand Voltage (Ud) 20 1.2 24kV, Impulse Withstand Voltage (Up) 72kV
Therefore rated voltage 12kV breaker shall apply to satisfy the required withstand voltage.

E ) To apply a breaker it a rated voltage 12kV to t e place of 2,500m above sea level
(correction parameter 2 applied)
- Correction parameter at 2500m is 0.825
- Dielectric strength of VCB : Power Frequency Withstand Voltage (Ud) 28 0.825 23.1kV,
Impulse Withstand Voltage (Up) 75 0.825 62kV/1.2 50
Therefore above breaker with rated voltage 12kV shall apply to rated voltage system 7.2kV at the altitude.

252
Technical data

Special Use Environment

Rated current compensation in accordance it ambient temperature


When normal ambient temperature exceeds the temperature specified in the environment the following formula
help to select the applicable current.

Ia= Ir ( ( max - a)/ r)1/2


Ia: allowable continuous current in the actual ambient temperature a
Ir: rated current at 40 ambient temperature
max: acceptable overall temperature of the hottest spot

a: the actual ambient temperature expected at -30 and 60


r: allowable temperature in the hottest place at rated current

Ex) The calculation of the applicable load current value when a breaker with rated current
2000A is used at 55 ambient temperature
Ia 2000 ((105-55)/65)1/2 2000 0.87 1754A

Ambient temperature ( )
Rated current A
20 25 30 35 40 45 50 55 60
4000 4000 4000 4000 4000 4000 3843 3679 3508 3328
3150 3150 3150 3150 3150 3150 3026 2898 2763 2621
2000 2000 2000 2000 2000 2000 1922 1840 1754 1664
1250 1250 1250 1250 1250 1250 1201 1150 1096 1040
630 630 630 630 630 630 605 580 553 524

<Table 2 Allowable load current by ambient temperature

<Figure 3 Allowable load current by ambient temperature

253
Susol VCB

Comparison of GCB & VCB

In the system of medium voltage lines VCB uses a vacuum which is an eco friendly medium for arc extinguishing.
It also offers excellent interrupting properties and ease of maintenance and has expanded the area to the scope
of the GCB as the overlap increases.

Comparison
Items CB VCB Remarks
results
Images

VI

Arc extinguish SF6 gas Vacuum


medium and - Greenhouse gas that causes global - Green clean medium.
characteristics
warming. - 5 10-5 Torr vacuum rate to maintain. VCB is better
- The toxic gas generated by chemical than GCB
reactions due to arc energy.
- 5kgf/ high pressure required.

Maintenance of - Periodic check and supplement the gas - Available until the product life.
the arc media pressure required. - Always keep trip-first feature.
- Automatic locking if gas pressure In the VCB is better
event of an accident while the gas valve When an accident occurs the trip-first than GCB
is locked trip is disable and the load feature functions to protect the
equipment can not be protected. equipment.

Rated voltage VCB has been


range (kV) increasing
GCB is better rapidly in the
3.6~550 3.6~36
than VCB medium
voltage
systems.

Applicable rate IEC62271-100


of transient Annex M
recovery VCB is better applied/
Low High
voltage than GCB Interrupting
(RRRV) performance
verified.

Development Decline Increasing


and trends
- Company M discontinued producing GCB. - Companies A and S have developed
- Company A manufactures VCB in medium new VCBs.
VCB is better
voltage GCB production factory. - Development trend that the voltage
than GCB
- GCB Maker S started the production of coverage of VCB expands.
VCB. - VI increased coverage.
(GIS, DAIS, SIS, etc.)

254
www.ls-electric.com

 Headquarter  Overseas Branches


127 LS-ro (Hogye-dong) Dongan-gu, Anyang-si, Gyeonggi-Do, 14119, Korea • LS ELECTRIC Tokyo Office (Japan)
Tel: 81-3-6268-8241 E-Mail: tokyo@ls-electric.com
 Seoul Office
LS Yongsan Tower, 92, Hangang-daero, Yongsan-gu, Seoul, 04386, Korea • LS ELECTRIC Beijing Office (China)
Tel. 82-2-2034-4916, 4684, 4429 Tel: 86-10-5095-1631 E-Mail: china@lselectric.com.cn
• LS ELECTRIC Shanghai Office (China)
 Overseas Subsidiaries
Tel: 86-21-5237-9977 E-Mail: china@lselectric.com.cn
• LS ELECTRIC Japan Co., Ltd. (Tokyo, Japan) • LS ELECTRIC Guangzhou Office (China)
Tel: 81-3-6268-8241 E-Mail: japan@ls-electric.com
Tel: 86-20-3818-2883 E-Mail: china@lselectric.com.cn
• LS ELECTRIC (Dalian) Co., Ltd. (Dalian, China)
Tel: 86-411-8730-5872 E-Mail: china.dalian@lselectric.com.cn • LS ELECTRIC Chengdu Office (China)
Tel: 86-28-8670-3201 E-Mail: china@lselectric.com.cn
• LS ELECTRIC (Wuxi) Co., Ltd. (Wuxi, China)
Tel: 86-510-6851-6666 E-Mail: china.wuxi@lselectric.com.cn • LS ELECTRIC Qingdao Office (China)
• LS ELECTRIC Vietnam Co., Ltd. (Hanoi, Vietnam) Tel: 86-532-8501-2065 E-Mail: china@lselectric.com.cn
Tel: 84-93-631-4099 E-Mail: vietnam@ls-electric.com • LS ELECTRIC Nanjing Office (China)
• LS ELECTRIC Middle East FZE (Dubai, U.A.E.) Tel: 86-25-8467-0005 E-Mail: china@lselectric.com.cn
Tel: 971-4-886-5360 E-Mail: middleeast@ls-electric.com • LS ELECTRIC Bangkok Office (Thailand)
• LS ELECTRIC Europe B.V. (Hoofddor, Netherlands) Tel: 66-90-950-9683 E-Mail: thailand@ls-electric.com
Tel: 31-20-654-1424 E-Mail: europartner@ls-electric.com • LS ELECTRIC Jakarta Office (Indonesia)
• LS ELECTRIC America Inc. (Chicago, USA) Tel: 62-21-2933-7614 E-Mail: indonesia@ls-electric.com
Tel: 1-800-891-2941 E-Mail: sales.us@lselectricamerica.com
• LS ELECTRIC Moscow Office (Russia)
• LS ENERGY SOLUTIONS LLC (Charlotte, USA) Tel: 7-499-682-6130 E-Mail: info@lselectric-ru.com
Tel: 1-704-587-4051 E-Mail: cmfeldman@ls-es.com
• LS ELECTRIC America Western Office (Irvine, USA)
• LS ELECTRIC Turkey Co., Ltd. (Istanbul, Turkey) Tel: 1-949-333-3140 E-Mail: america@ls-electric.com
Tel: 90-212-806-1252 E-Mail: turkey@ls-electric.com
• LS ELECTRIC India Office (India)
Tel: 91-80-6142-9108 E-Mail: Info_india@ls-electric.com
• LS ELECTRIC Singapore Office (Singapore)
Tel: 65-6958-8162 E-Mail: singapore@ls-electric.com

Specifications in this catalog are subject to change without notice due to


2022. 01 continuous product development and improvement.