Flowmeter Promag 53H (Endress+Hauser)

Customer: VITANUOVA
Plant: PASTA LARGA
Place: San José , Prov. La Habana
Country: Cuba
Product: LWVIN1 Order no.: 527 769

Group Function Standard Promag 1


value (Example) Promag 2
A MEASURING VAR.
AAA MESURING VAR.
0000 CALCULATED MASS FLOW -
0001 VOLUME FLOW -
0005 DENSITY 1.0 kg/l

ACA SYSTEM UNITS 040 CONFIGURATION


0400 UNIT MASS FLOW kg/m
0401 UNIT MASS kg
0402 UNIT VOLUME FLOW l/h
0403 UNIT VOLUME l

042 ADDITIONAL CONFIGURATION


0420 UNIT DENSITY kg/l
0424 UNIT LENGTH mm

AEA SPECIAL UNITS 060 ARBITRARY UNIT


0602 TEXT ABITRARY VOLUME UNIT -
0603 FACTOR ABITRARY VOL. UNIT 1.0 /l

070 DENSITY PARAMETER


0700 DENSITY VALUE 1.0 kg/l

B QUICK SETUP
1002 QUICK SETUP COMISSION -
1003 QUICK SETUP PULSING FLOW -
1009 T-DAT SAVE/LOAD -

C USER INTERFACE
CAA CONTROL 200 BASIC CONFIGURATION
2000 LANGUAGE English
2002 DISPLAY DAMPING 1.0 s
2003 CONTRAST LCD 50 %

202 UNLOCKING/LOCKING
2021 DEFINE PRIVATE CODE 53

204 OPERATION
2040 TEST DISPLAY Off

CCA MAIN LINE 220 CONFIGURATION


2200 ASSIGNMENT Volume flow
2202 FORMAT XXX.XX

 Copyright 2007 Promag_53H_EN_LWVIN1


2 Flowmeter Promag 53H (Endress+Hauser)

222 MULTIPLEX
2220 ASSIGNMENT Off

CEA ADDITIONAL LINE 240 CONFIGURATION


2400 ASSIGNMENT Totalizer 1
2402 FORMAT XXXXX.

242 MULTIPLEX.
2420 ASSIGNMENT Off

CGA INFORMATION LINE 260 CONFIGURATION


2600 ASSIGNMENT Operation./Sys.
Conditions

262 MULTIPLEX.
2620 ASSIGNMENT Off

D TOTALIZER
DAA TOTALIZER 1 300 CONFIGURATION
3000 ASSIGNMENT Volume flow
3001 UNIT TOTALIZER l
3002 TOTALIZER MODE Balance
3003 RESET TOTALIZER No

304 OPERATION
3040 SUM ... l
3041 OVERFLOW 0 E7 l

DAB TOTALIZER 2 300 CONFIGURATION


3000 ASSIGNMENT Volume flow
3001 UNIT TOTALIZER l
3002 TOTALIZER MODE Forward
3003 RESET TOTALIZER No

304 OPERATION
3040 SUM …l
3041 OVERFLOW 0 E7 l

DAC TOTALIZER 3 300 CONFIGURATION


3000 ASSIGNMENT Volume flow
3001 UNIT TOTALIZER l
3002 TOTALIZER MODE Reverse
3003 RESET TOTALIZER No

304 OPERATION
3040 SUM …l
3041 OVERFLOW 0 E7 l

DJA HANDLING TOTALIZ.


3800 RESET ALL TOTALIZERS No
3801 FAILSAFE ALL TOTALIZERS Stop

Promag_53H_EN_LWVIN1  Copyright 2007


Flowmeter Promag 53H (Endress+Hauser) 3

E OUTPUTS
EAA CURRENT OUTPUT 400 CONFIGURATION
1
4000 ASSIGN. CURRENT OUTPUT Volume flow
4001 CURRENT SPAN 4-20mA Hart
4002 VALUE 0_4 mA 0 l/h
4003 VALUE 20 mA 950 l/h
4004 MEASURING MODE Standard
4005 TIME CONSTANT 1.0 s
4006 FAILSAFE MODE Min. Current

404 OPERATION
4040 ACUTAL CURRENT
4041 SIMULATION CURRENT Off
4042 VALUE SIMULATION CURRENT

408 INFORMATION
4080 TERMINAL NUMBER 26(+) / 27(-)

ECA PULSE/FREQUENCY 420 CONFIGURATION


OUTPUT 1
4200 OPERATION MODE Pulse
4221 ASSIGNMENT PULSE Volume flow
4222 PULSE VALUE 1.0 l/p
4223 PULSE WIDTH 500 ms
4225 MEASURING MODE Standard
4226 OUTPUT SIGNAL Passive-Negative
4227 FAILSAFE MODE Fallback value

438 INFORMATION
4380 TERMINAL NUMBER 24(+) / 25(-)

EGA RELAY OUTPUT 1 470 CONFIGURATION


4700 ASSIGNMENT RELAY Fault message

474 OPERATION
4740 ACTUAL STATUS RELAY
4741 SIMULATION SWITCH POINT Off
4742 VALUE SIM. SWITCH POINT -

478 INFORMATION
4780 TERMINAL NUMBER 22(+) / 23(-)

EGB RELAY OUTPUT 2 470 CONFIGURATION


4700 ASSIGNMENT RELAY Fault message

474 OPERATION
4740 ACTUAL STATUS RELAY
4741 SIMULATION SWITCH POINT Off
4742 VALUE SIM. SWITCH POINT -

478 INFORMATION
4780 TERMINAL NUMBER 20(+) / 21(-)

G BASIC FUNCTION
GAA HART 600 CONFIGURATION

 Copyright 2007 Promag_53H_EN_LWVIN1


4 Flowmeter Promag 53H (Endress+Hauser)

6000 TAG NAME -


6001 TAG DESCRIPTION -
6002 BUS ADDRESS 0
6003 HART PROTOCOL On
6004 WRITE PROTECTION Off
604 INFORMATION
6040 MANUFACTURER ID E+H
6041 DEVICE ID 42 (hex)

GIA PROCESS PARAM. 640 CONFIGURATION


6400 ASSIGN LOW FLOW CUT OFF Volume flow
6402 ON-VAL. LOW FLOW CUT OFF 6.0 l/h
6403 OFF-VAL. LOW FLOW CUT OFF 50 %
6404 PRESSURE SHOCK 0s
SUPRESSION

642 EMPTY PIPE DET. PARAMETER


6420 EPD/OED MODE EPD ON
6425 EPD/OED RESPONSE TIME 1.0 s

648 ADJUSTMENT
6481 EPD/OED ADJUSTMENT Off

GLA SYSTEM PARAM. 660 CONFIGURATION


6600 INSTALLATION DIRECTION Normal
SENSOR
6603 FLOW DAMPING 7
6604 INTEGRATION TIME 20 ms
6605 POSITIVE ZERO RETURN Off

GNA SENSOR DATA 680 CONFIGURATION


6801 K-FACTOR POSITIVE 1.3038
6802 K-FACTOR NEGATIVE 1.3038
6803 ZERO POINT 0
6804 NOMINAL DIAMETER DN8

682 OPERATION
6820 MEASURING PERIOD
6821 OVERVOLTAGE TIME
6822 EPD ELECTRODE YES

J SUPERVISION
JAA SYSTEM 800 CONFIGURATION
8000 ASSIGN SYSTEM ERROR Cancel
8002 ASSIGN PROCESS ERROR Cancel
8004 ACKNOWLEDGE FAULTS Off
8005 ALARM DELAY 0s

804 OPERATION
8040 ACTUAL SYSTEM CONDITION System OK
8041 PREVIOUS SYSTEM COND.
8042 SIMULATION FAILSAFE MODE
8043 SIMULATION MEASURAND Off
8046 SYSTEM RESET No
8047 TROUBLESHOOTING Cancel

Promag_53H_EN_LWVIN1  Copyright 2007


Flowmeter Promag 53H (Endress+Hauser) 5

JCA VERSION-INFO 820 SENSOR


8200 SERIAL NUMBER 520A8691000
8201 SENSOR TYPE H
8202 HW REV.-NO. SENSOR V1.04.00

822 AMPLIFIER
8222 SOFTWARE REV.-NO. AMP. V1.04.00
8225 SOFTWARE REV.-NO. T-DAT V1.04.00
824 F-CHIP
8240 STATUS F-CHIP No F-Chip HW

830 I/O-MODULE
8300 I/O-MODULE TYP I/O X3
8303 SOFTWARE REV.-NO. I/O-MOD. V1.02.01

832 IN-/OUTPUT 1
8320 TYPE IN-/ OUTPUT 1 Current output
8322 HW IDENT.-NO. IN-/ OUTPUT 1 V1.02.01

834 IN-/OUTPUT 2
8340 TYPE IN-/ OUTPUT 2 Pulse/Frequency
8342 HW IDENT.-NO. IN-/ OUTPUT 2 V1.02.01

836 IN-/OUTPUT 3
8360 TYPE IN-/ OUTPUT 3 Stat. Relay outp.
8362 HW IDENT.-NO. IN-/ OUTPUT 3 V1.02.01

838 IN-/OUTPUT 4
8380 TYPE IN-/ OUTPUT 4 Stat. Relay outp.
8382 HW IDENT.-NO. IN-/ OUTPUT 4 V1.02.01

Changing parameters:
1. Change to USER INTERFACE – CONTROL – BASIC CONFIGURATION – UNLOCKING-/LOCKING
2. at ACCESS CODE (2020) enter code with +/- Code (Factory default: 53)
3. change the required parameters

Date: 13.02.2007 Start up Engineer: L. Rodowski

Reference: Operating instruction manual Endress+Hauser PROline Promag 53: Electromagnetic Flow
Measuring System BA048D/06/en/06.01