You are on page 1of 7

g BILL OF MATERIAL GE India Industrial Pvt Ltd

Revision No. Revision Details Date


01 Revised as per customer comments 03.11.10
02 Factory Asbuilt 03.12.10
g BILL OF MATERIAL GE India Industrial Pvt Ltd

Sl. GA / Scheme Ref Item Description Make Qty Item Code


No.
1. AEE910 132KV Feeder Control & Relay Panel MPP 1 EMS0002145
Type: Simplex
Dimensions: (H) 2250 (Including Base Frame-50mm + AV Pad-15mm) x (w) 900 x (d) 700
Painting: Powder Coating; Thickness: 60 microns minimum;
Paint shade: Exterior: RAL7035, Finish: Texture,
Interior – White, Finish: Glossy; Base Frame: Black
2. 21 Numerical Distance protection relay GE MULTILIN 1 ERL0050557
Type D60
Model No: D60-N03-HKH-F8L-H6D-MXX-P67-UXX-W67
Protection Functions:
Four Zone Distance Protection
PSB
VT Fuse failure
Broken Conductor
Recording Functions:
Disturbance Recorder
Fault recorder
Event Logger
Communication Protocol : IEC 104 / DNP3.0/IEC61850
3. 50/ 51 Numerical Non. Directional over current & Earth Fault Relay GE MULTILIN 1 ERL0050559
Type F650
Protection Functions:
Non Directional Over Current & Earth Fault with Highset
LBB
Model No.: F650-B-F-B-F-1-G-1-HI-6-E
Communication Protocol : IEC 104 / DNP3.0/IEC61850
4. 86A Group-A Mater trip Relay ABB 1 ERL0020457
86B Group-B Mater trip Relay 1
86LBB LBB trip Relay 1
Type: RXMVB2
Contacts:6 N/O + 2 N/C ER, Flag : HR
Aux DC: 24V
5. 86AR, Resistor unit for Trip Relay 86A ABB 1 ERL0020550
86BR, Resistor unit for Trip Relay 86B 1
86LBBR Resistor unit for Trip Relay 86LBB 1
Type: RXTMA
Aux DC: 110V
6. 86A/95 86A Trip relay coil supervision relay ABB 1 ERL0020407
86B/95 86B Trip relay coil supervision relay 1
86LBB/95 86LBB Trip relay coil supervision relay 1
Type: TSR
Contacts: 2 Change over S/R
Aux DC: 110V
g BILL OF MATERIAL GE India Industrial Pvt Ltd

7. 195 Trip Circuit Supervision Relay for CB Trip coil-1 (Both Pre close & Post close) ABB 1 ERL0020380
295 Trip Circuit Supervision Relay for CB Trip coil-2 (Both Pre close & Post close) 1
Type: RXTCS
Contacts: 1NO + 1NC + 2 C/O
Aux DC: 110V
8. 80AB DC supervision Relay for Main & Backup Protection ABB 1 ERL0020389
Type: RXSF (Double element)
Contacts: 1 N/O + 2 N/C SR in each element, Flag: SR Reverse
Aux DC: 110V
9. 80C Incoming DC Supply supervision Relay ABB 1 ERL0020389
Type: RXSF ( Double element)
Contacts: 1 N/O + 2 N/C SR in each element, Flag: SR Reverse
Aux DC: 110V
10. Q0-TX Contact Multiplication Relay for CB manual tripping ABB 1 ERL0020548
Type: RXME
Contacts: 2 N/O SR,
Aux. DC: 110V
11. 63AGX/ Contact Multiplication Relay for CB Low Gas Pressure ABB 1 ERL0020552
88MX Contact Multiplication Relay for CB Spring charge
Type: RXMM (Double Element )
Contacts: 2N/O + 1 N/C SR in each Element
Aux. DC: 110V
12. 21X/ Contact Multiplication Relay for Distance Protection Relay Faulty ABB 1 ERL0020421
50/51X Contact Multiplication Relay for Backup Protection Relay Faulty
Type: RXSF (Double Element )
Contacts: 3N/O SR in each Element, Flag: SR Forward
Aux. DC: 110V
13. Q9X Contact Multiplication Relay for Disconnector Q9 ABB 1 ERL0020413
Q8X Contact Multiplication Relay for Earth switch Q8 1
Type: RXPSU6
Contacts:3 N/O + 3 N/C ER, Flag : SR
Aux DC: 110V
14. C1/C2 Flasher Relay ABB 1 ERL0020549
Type: RXSU2
Aux DC: 110V
15. C1/C2X Auxiliary relay Flasher Relay ABB 1 ERL0020548
Type: RXME
Contacts: 2 N/O SR,
Aux. DC: 110V
16. FC Annunciator with inbuilt DC & AC supply fail annunciation ALAN 1 EMS0001856
Windows: 24 (4 Rows x 6 Coloumns)
Aux Supply – 110V DC / 230V AC
17. PB1, Push Buttons for Annunciation Accept - Colour : Red TEKNIC 1 EPB7010015
PB2, Push Buttons for Annunciation Reset - Colour :Yellow 1 EPB4110017
PB3 Push Buttons for Annunciation Test - Colour :Blue 1 EPB3110010
Contacts: 1 N/O + 1 N/C
g BILL OF MATERIAL GE India Industrial Pvt Ltd

18. PB4 Push Buttons for Trip relay –86A Reset - Colour - Black TEKNIC 1 EPB5110005
PB5 Push Buttons for Trip relay – 86B Reset - Colour - Black 1 EPB5110005
PB6 Push Buttons for Trip relay – 86LBB Reset - Colour - Black 1 EPB5110005
Contacts: 1 N/O + 1 N/C
19. A Ammeter RISHABH 1 EAM1010081
Type - Moving coil;
Class of Accuracy: 1
Size: 96sq.mm.
Scale :240 deg;
Scale Range: (0-800A)
CTR: 1200-800/1A
20. ASS Ammeter selector switch SWITRON 1 ECS0050067
No. of Positions:4 , Inscription: R-Y-B-OFF
21. V-L Voltmeter for 132KV Line RISHABH 1 EVM1010034
Type - Moving coil
Class of Accuracy: 1
Size 96sq.mm.
Scale : 240 deg;
PT Ratio: 132KV/R3 / 110V/R3
Scale Range: 0-150KV
22. V-B Voltmeter for 132KV Bus RISHABH 1 EVM1010034
Type - Moving coil
Class of Accuracy: 1
Size 96sq.mm.
Scale : 240 deg;
PT Ratio: 132KV/R3 / 110V/R3
Scale Range: 0-150KV
23. VSS-L Voltmeter selector switch for Line SWITRON 1 ECS0050057
No. of Positions:4 , Inscription: RY-YB-BR-OFF
24. VSS-B Voltmeter selector switch for Bus SWITRON 1 ECS0050057
No. of Positions:4 , Inscription: RY-YB-BR-OFF
25. MFM Multi Function Meter SATEC 1 EWH1020975
Class of Accuracy: 0.5s
Size: 114 Sq. mm
CT Ratio: 1200-800/1A
PT Ratio: 132KV/R3 / 110V/R3
3ph 4 wire 3 element
Aux DC : 110V
26. TVM-M Trivector Meter for Main ELSTER 1 EWH1020978
Type : A1800
Class of Accuracy: 0.2
CT Ratio: 1200-800/1A
PT Ratio: 132KV/R3 / 110V/R3
3ph 4 wire 3 element
g BILL OF MATERIAL GE India Industrial Pvt Ltd

27. TVM-C Trivector Meter for Check ELSTER 1 EWH1020978


Type : A1800
Class of accuracy: 0.2
CT Ratio: 1200-800/1A
PT Ratio: 132KV/R3 / 110V/R3
3ph 4 wire 3 element

28. TTB-TVM Test terminal block for Trivector meter DEEPL 1 EMS0002017
Type: 3 phase 4 wire rear connected link type
29. Q0 Control switch for CB with Flasher LED ABB 1 ECS0050133
Type: Discrepancy
No. of Position : 4 ( V2-Trip , V1-Normal after Trip , H2 – Close , H1 – Normal after Close)
Aux DC : 110V
30. Q1, Control switch for Disconnector Q1 with Flasher LED ABB 1 ECS0050134
Q9 Control switch for Disconnector Q9 with Flasher LED 1 ECS0050134
Type: Discrepancy
No. of Position : 4 ( V2-Open , V1-Normal after Open , H2 – Close , H1 – Normal after Close)
Aux DC : 110V
31. Q8 Automatic Semaphore indicator for Earth switch DEEPL 1 EMS0002021
Bezel size: 36mm dia,
Aux DC : 110V,
32. SL1 Indicating lamp, for CB Spring Charge TEKNIC 1 ELM3020030
Type: LED,
Size: 22.5mm dia;
Colour: Blue
Aux DC: 110V
33. TS-1 Test Switch for testing of Distance Protection Relay EASUN 1 EMS0002121
Type: ERMLG REYROLLE
34. TS-2 Test Switch for testing of Backup Protection Relay EASUN 1 EMS0002121
Type: ERMLG REYROLLE
g BILL OF MATERIAL GE India Industrial Pvt Ltd

Sl. GA / Scheme Ref Item Description Make Qty Item Code


No.
INTERNALLY MOUNTED EQUIPMENTS
35. U1 Programmable Multifunction Transducer RISHABH 1 ETR2110067
U2 Programmable Multifunction Transducer 1 ETR2110067
Model No: M42
Class of Accuracy: 0.5
CT Ratio: 800/1A
PT Ratio: 132KV/R3 / 110V/R3
3ph 4 wire 3 element
No of 4 to 20mA Outputs: 4 ( Programmable)
Output-1 : Current, Scale Range: 0-800A
Output-2 : Active Power, Scale Range: Shall be furnished by customer
Output-3 : Reactive Power, Scale Range: Shall be furnished by customer
Output-4 : Voltage, Scale Range: 0-150KV
Aux DC : 110V
36. U3 Voltage Transducer for 132KV Bus Voltage RISHABH 1 ETR2110069
Model No: E15
Class of Accuracy: 0.5
PT Ratio: 132KV/110V
Scale Range: 0-150KV
No of 4 to 20mA Outputs: 2
Aux DC : 110V
37. HT Space Heater : 60W, 240V AC SOFIA 1 EMS0001503
38. CFL Compact Fluorescent Lamp, 11W, 230V 50 HZ for cubicle lighting PHILIPS 1 EMS0001811
39. PS Case containing 3-PIN socket, 5/15A-230V AC + Switch ANCHOR 1 EMS0001305
40. HS Heater Switch, Type: 1C160, Position: ON/OFF SWITRON 1 ECS0020096
41. TH Thermostat AI 1 EMS0000293
42. DS Door Limit switch for cubicle lighting 1
43. EAD1 DC Bell for Trip Alarm ALAN 1 EMS0001813
Aux DC: 110V
44. EAD2 DC Hooter for Non Trip Alarm ALAN 1 EMS0001812
Aux DC: 110V
45. EAD3 AC Buzzer for DC fail Alarm ALAN 1 EMS0001814
Aux AC: 230V
46. MCB 01 DC MCB, 2 Pole, 20A, 110V DC for Incoming DC Circuit LEGRAND 1 EMC5080016
47. MCB 02 DC MCB, 2 Pole, 16A, 110V DC for CB Closing and Trip coil-1 Circuit LEGRAND 1 EMC1050025
48. MCB 03 DC MCB, 2 Pole, 16A, 110V DC for CB Trip coil-2 Circuit LEGRAND 1 EMC1050025
49. MCB 04 DC MCB, 2 Pole, 4A, 110V DC for Disconnector Control Circuit LEGRAND 1 EMC1050020
50. MCB 05 DC MCB, 2 Pole, 2A, 110V DC for Metering Circuit LEGRAND 1 EMC1050026
51. MCB 06 DC MCB, 2 Pole, 4A, 110V DC for Distance Protection Circuit LEGRAND 1 EMC1050020
52. MCB 07 DC MCB, 2 Pole, 4A, 110V DC for Backup Protection Circuit LEGRAND 1 EMC1050020
53. MCB 08 DC MCB, 2 Pole, 4A, 110V DC for Annunciator Circuit LEGRAND 1 EMC1050020
54. MCB 09 DC MCB, 2 Pole, 4A, 110V DC for LBB Trip Relay Circuit LEGRAND 1 EMC1050020
55. MCB 10 DC MCB, 2 Pole, 4A, 110V DC for Indication Circuit LEGRAND 1 EMC1050020
56. MCB 11 AC MCB, Single Pole + Neutral , 16A, 230V AC for Incoming Single Ph AC Circuit LEGRAND 1 EMC1050010
57. MCB 12 AC MCB, Single Pole + Neutral , 4A, 230V AC for Annunciator Circuit LEGRAND 1 EMC2050028
58. FS1, FS2,FS3 Fuse Assembly for Line VT Metering Ckt., NS2W GE 3 SFA9311002
59. LK3 Link Assembly for Line VT Metering Ckt., Neutral GE 1 EIL0080003
60. FS4, FS5, FS6 Fuse Assembly for Line VT Protection Ckt., NS2W GE 3 SFA9311002
g BILL OF MATERIAL GE India Industrial Pvt Ltd

Sl. GA / Scheme Ref Item Description Make Qty Item Code


No.
61. LK6 Link Assembly for Line VT Protection Ckt., Neutral GE 1 EIL0080003
62. FS7,FS8,FS9 Fuse Assembly for Bus VT Metering Ckt., NS2W GE 3 SFA9311002
63. LK9 Link Assembly for Bus VT Metering Ckt., Neutral GE 1 EIL0080003
64. FS19 Fuse Assembly for 1PH AC Ckt, NS2W for Cubicle Heater & Illumination Circuit GE 1 SFA9311002
65. LK19 Link Assembly for 1PH AC Ckt , Neutral for Cubicle Heater & Illumination Circuit GE 1 EIL0080003
66. TB’S Terminal Blocks Phoenix As per
DC/AC Incoming Circuits - Feed through type Terminal Block - UK5N-E scheme
CT/PT Circuits – Sliding type Disconnecting Terminal Block - URTK/S Requirement
DC Control Circuits – Knife type Disconnecting Terminal Block – MTK-P/P-E

You might also like