You are on page 1of 84

Instruction Manual

Form 5196
May 2006 4194A, B, and C Series

4194A, B, and C Series Differential Pressure


Controllers1-1-
Contents 4. 4194B Series Proportional-Plus-Reset
Controllers and 4194C Series
1. Introduction
Proportional-Plus-Reset-Plus-Rate Controllers
Scope of Manual . . . . . . . . . . . . . . . . . . . . . . . . 1-3
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3 Adjustments for 4194B and C Series
Controllers . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
Manual Set Point Adjustment . . . . . . . . . . . . 4-1
Educational Services . . . . . . . . . . . . . . . . . . . . 1-5
Remote Set Point (suffix letter M)
Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
2. Installation
Proportional Band Adjustment (PB ADJ) . . 4-2
Controller Mounting Orientation . . . . . . . . . . . 2-1
Pipestand Mounting . . . . . . . . . . . . . . . . . . . . . 2-1 Changing Controller Action . . . . . . . . . . . . . . 4-2
Reset Adjustment . . . . . . . . . . . . . . . . . . . . . . 4-2
Panel Mounting . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Rate Adjustment . . . . . . . . . . . . . . . . . . . . . . . 4-2
Wall Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Actuator Mounting . . . . . . . . . . . . . . . . . . . . . . 2-1 Anti-Reset Windup (suffix letter F)
Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . 4-2
Pressure Connections . . . . . . . . . . . . . . . . . . . 2-2
Switching The Auto/Manual Station
Process Pressure Connections . . . . . . . . . . 2-3
Supply Pressure Connection . . . . . . . . . . . . 2-3 (suffix letter E) . . . . . . . . . . . . . . . . . . . . . . 4-2
Prestartup Checks for 4194B and C Series
Remote Set Point (suffix letter M)
Controllers . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3
Pressure Connection . . . . . . . . . . . . . . . . 2-3
Vent . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4 Startup for 4194B and C Series Controllers . 4-3
Calibration of 4194B and C Series
Controllers . . . . . . . . . . . . . . . . . . . . . . . . . . 4-4
3. 4194A Series Proportional-Only Controllers
Adjustments for 4194A Series Controllers . . 3-1 General Calibration Instructions . . . . . . . . . 4-4
Process Indicator Zero and Span
Manual Set Point Adjustment . . . . . . . . . . . . 3-1
Calibration . . . . . . . . . . . . . . . . . . . . . . . . . 4-5
Remote Set Point (suffix letter M)
Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . 3-1 Remote Set Point (suffix letter M)
Zero and Span Calibration . . . . . . . . . . . . 4-5
Proportional Band Adjustment (PB ADJ) . . 3-2
Flapper Alignment . . . . . . . . . . . . . . . . . . . . . 4-7
Changing Controller Action . . . . . . . . . . . . . . 3-2
Switching the Auto/Manual Station Anti-Reset Windup Differential Relief Valve
Calibration . . . . . . . . . . . . . . . . . . . . . . . . . 4-9
(suffix letter E) . . . . . . . . . . . . . . . . . . . . . . 3-2
Principle of Operation for 4194B and C Series
Prestartup Checks for 4194A Series
Controllers . . . . . . . . . . . . . . . . . . . . . . . . . 4-10
Controllers . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
Overall Operation . . . . . . . . . . . . . . . . . . . . . 4-10
Startup for 4194A Series Controllers . . . . . . 3-3
Anti-Reset Windup (suffix letter F)
Calibration of 4194A Series Controllers . . . . 3-3
Operation . . . . . . . . . . . . . . . . . . . . . . . . . 4-12
General Calibration Instructions . . . . . . . . . 3-4
Remote Set Point (suffix letter M)
Process Indicator Zero and Span
Operation . . . . . . . . . . . . . . . . . . . . . . . . . 4-13
Calibration . . . . . . . . . . . . . . . . . . . . . . . . . 3-4
Auto/Manual Station (suffix letter E)
Remote Set Point (suffix letter M)
Operation . . . . . . . . . . . . . . . . . . . . . . . . . 4-13
Zero and Span Calibration . . . . . . . . . . . . 3-4
Flapper Alignment . . . . . . . . . . . . . . . . . . . . . 3-5
5. Maintenance
Principle of Operation for 4194A Series
Inspection and Maintenance . . . . . . . . . . . . . . 5-1
Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-7
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . 5-1
Overall Operation . . . . . . . . . . . . . . . . . . . . . . 3-7
Replacing Common Controller Parts . . . . . . . 5-5
Remote Set Point (suffix letter M)
Replacing the Process Pressure Scale . . . 5-5
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . 3-8
Replacing the Relay . . . . . . . . . . . . . . . . . . . . 5-5
Auto/Manual Station (suffix letter E)
Replacing the Case and Cover . . . . . . . . . . 5-6
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . 3-8
D200154X012

www.Fisher.com
Instruction Manual
Form 5196
4194A, B, and C Series May 2006

Replacing the Gauges . . . . . . . . . . . . . . . . . . 5-6 Precalibration Procedures . . . . . . . . . . . . . 5-32


Replacing the Pressure Control Block . . . . 5-6 Aligning the Flexures . . . . . . . . . . . . . . . . . . 5-32
Replacing the Supply Gauge, Proportional, Setting the Travel Stops . . . . . . . . . . . . . . . 5-32
Reset, and Reset Valve Tubing Aligning the Linkage . . . . . . . . . . . . . . . . . . 5-33
Assemblies . . . . . . . . . . . . . . . . . . . . . . . . . 5-7 Remote Set Point Zero and Span
Replacing the Proportional Band Adjustment Adjustment . . . . . . . . . . . . . . . . . . . . . . . . 5-33
Knob, Nozzle Assembly, and Set Point Remote Set Point Linearity Adjustment . . 5-34
Beam Assembly . . . . . . . . . . . . . . . . . . . . . 5-7 Auto/Manual Station (suffix letter E)
Replacing the Flapper Assembly and Maintenance . . . . . . . . . . . . . . . . . . . . . . . . 5-34
Flapper Flexure Pivot Assembly . . . . . . 5-11 Replacing the Auto/Manual Station . . . . . . 5-34
Replacing the Proportional or Reset Replacing the Switch Body Assembly,
Bellows . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-15 Lever O-ring, Switch Body O-ring
Replacing the Reset Restriction Valve and Tubing Assembly . . . . . . . . . . . . . . . 5-35
(4194B Series) . . . . . . . . . . . . . . . . . . . . . 5-17 Replacing the Loader Range Spring,
Replacing the Rate/Reset Valve Assembly Diaphragm Assembly, Ball Seat,
(4194C Series) . . . . . . . . . . . . . . . . . . . . . 5-17 Tubing, and Ball . . . . . . . . . . . . . . . . . . . . 5-36
Replacing the Anti-Reset Windup Replacing the Loader Valve Plug and
(suffix letter F) Differential Relief Valve 5-18 Valve Plug Spring . . . . . . . . . . . . . . . . . . 5-36
Replacing the Anti-Reset Windup
(suffix letter F) Relief Valve Tubing 6. Parts
Assembly . . . . . . . . . . . . . . . . . . . . . . . . . 5-18 Parts Ordering . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
Replacing the Links . . . . . . . . . . . . . . . . . . . 5-19 Parts Kits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
Replacing Link 1 . . . . . . . . . . . . . . . . . . . . . 5-19 Parts List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
Replacing Link 2 . . . . . . . . . . . . . . . . . . . . . 5-19 Abbreviations Used in the Parts List . . . . . . 6-1
Replacing Link 3 . . . . . . . . . . . . . . . . . . . . . 5-20 Controller Common Parts . . . . . . . . . . . . . . . 6-1
Replacing Link 4 . . . . . . . . . . . . . . . . . . . . . 5-21 Process and Set Point Indicator
Replacing Link 5 . . . . . . . . . . . . . . . . . . . . . 5-21 Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . 6-8
Replacing the Capsular Element Capsular Element Assembly . . . . . . . . . . . 6-10
Assembly . . . . . . . . . . . . . . . . . . . . . . . . . 5-22 Indicator Assembly . . . . . . . . . . . . . . . . . . . 6-11
Replacing the Long Pivot Assembly . . . . . 5-22 Remote Set Point Assembly
Replacing the Short Pivot Assembly . . . . . 5-23 (suffix letter M) . . . . . . . . . . . . . . . . . . . . . 6-11
Replacing the Process Drive Flexure . . . . 5-24 Auto/Manual Station (suffix letter E) . . . . . 6-12
Replacing the Process Tubing . . . . . . . . . . 5-24 Internal/External Set Point
Capsular Element Maintenance Calibration 5-24 Assembly (Option) . . . . . . . . . . . . . . . . . . 6-14
Precalibration Procedures . . . . . . . . . . . . . 5-24 Controller Mounting Parts . . . . . . . . . . . . . . 6-14
Aligning the Drive Bracket Assembly . . . . 5-25 Pipestand Mounting . . . . . . . . . . . . . . . . . . 6-14
Setting the Travel Stops . . . . . . . . . . . . . . . 5-25 Pipestand Mounting with Regulator . . . . 6-14
Aligning the Linkage . . . . . . . . . . . . . . . . . . 5-25 Panel Mounting . . . . . . . . . . . . . . . . . . . . . 6-14
Zero and Span Adjustment . . . . . . . . . . . . . 5-27 Wall Mounting . . . . . . . . . . . . . . . . . . . . . . . 6-14
Remote Set Point (suffix letter M) Controller Mounting Parts for Actuator
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . 5-28 With Casing-Mounted Controller . . . . . . 6-15
Replacing the Remote Set Point Controller Mounting Parts for Actuator
Assembly . . . . . . . . . . . . . . . . . . . . . . . . . 5-28 With Yoke-Mounted Controller . . . . . . . 6-15
Replacing Remote Set Point Regulator Mounting Parts . . . . . . . . . . . . . . 6-15
Assembly Parts . . . . . . . . . . . . . . . . . . . . 5-29 Regulator Mounting Parts for
Replacing Pivot Assembly A (key 114) . . 5-30 Casing-Mounted Regulator . . . . . . . . . . 6-15
Replacing Pivot Assembly B (key 115) . . 5-30 Regulator Mounting Parts for
Replacing the Drive Flexure . . . . . . . . . . . 5-31 Yoke-Mounted Regulator (Mounting
Replacing the Remote Set Point Tubing 5-31 Bracket Not Required) . . . . . . . . . . . . . . 6-15
Replacing Link A . . . . . . . . . . . . . . . . . . . . 5-31 Regulator Mounting Parts for
Replacing Link B . . . . . . . . . . . . . . . . . . . . 5-31 Yoke-Mounted Regulator
Remote Set Point (suffix letter M) (With Mounting Bracket) . . . . . . . . . . . . . 6-15
Maintenance Calibration . . . . . . . . . . . . . . 5-32 Fittings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-15

1-2
Instruction Manual
Form 5196
May 2006 4194A, B, and C Series

W6390 / IL
W3358 / IL

Figure 1-1. 4194 Series Differential Pressure Controllers

Section 1 Description
Introduction The controllers described in this manual provide
differential pressure control with options as shown in
table 1-2.
Scope of Manual
This instruction manual provides installation,
operating, calibration, maintenance, and parts D 4194A Series: Proportional-only control
ordering information for the 4194A, 4194B and
4194C Series differential pressure indicating
controllers. D 4194B Series: Proportional-plus-reset control

Portions of this manual apply only to specific


configurations in the 4194 Series controller
configurations. These configurations are indicated D 4194C Series: Proportional-plus-reset-plus-rate
by letter suffixes in the type number that correspond control
to the mode and option designated in table 1-2.

The specific controller type number (with letter These controllers show process differential pressure
suffixes) is located on the nameplate shown in figure and set point on an easy-to-read process scale. The
1-1. Refer to table 1-2 for the definition of each 4194 controller output is a pneumatic signal that operates
Series type number. a final control element.

No person may install, operate, or maintain this


controller without first D being fully trained and
qualified in valve, actuator, and accessory
installation, operation and maintenance, and D
carefully reading and understanding the contents of Specifications
this manual. If you have any questions concerning
these instructions, contact your Emerson Process Specifications for the 4194A, B, and C Series
Managementt sales office before proceeding. controllers are listed in table 1-1.

1-3
Instruction Manual
Form 5196
4194A, B, and C Series May 2006

Table 1-1. Specifications

Available Configurations Reset(1): Adjustable from 0.01 to more than 74


See table 1-2 min per repeat (from 100 to less than 0.0135
repeats per min)
Input Signal(Differential Pressure Sensing Rate(1): Adjustable from 0 to 20 minutes
Element Range)(1) Set Point: Adjustable from 0 to 100% of the scale
range
Lower and Upper Range Limits: As shown in
table 1-3 Controller Performance
Maximum Allowable Pressure: As shown in
Repeatability (1): 0.4% of output span
table 1-3
Dead Band(1): Less than 0.4% of process scale
span
Output Signal
Typical Frequency Response(1): 1.5 Hz and 90
Proportional-Only, Proportional-Plus-Reset, deg phase shift with 3.05 m (10 ft) of 6.4 mm (1/4
or Proportional-Plus-Reset-Plus-Rate Range: inch) tubing and 1639 cm3 (100 cubic inch)
0.2 to 1.0 bar (3 to 15 psig) or 0.4 to 2.0 bar (6 to volume
30 psig)
Action: Field-reversible between direct Steady-State Air Consumption(1,5)
(increasing differential pressure increases output
pressure) or reverse (increasing differential Without Auto/Manual Station
pressure decreases output pressure) 0.2 to 1.0 Bar (3 to 15 Psig) Output: 0.1 m3/hr
(3.5 scfh)
Process Scale 0.4 to 2.0 Bar (6 to 30 Psig) Output: 0.14 m3/hr
(5.0 scfh)
Standard scale is matched to the range of the
differential pressure sensing element. Linear, With Auto/Manual Station (suffix letter E)
square root, and optional(2) scales available 0.2 to 1.0 Bar (3 to 15 Psig) Output: 0.28 m3/hr
(10.0 scfh)
Process Connections 0.4 to 2.0 Bar (6 to 30 Psig) Output:0.28 m3/hr
(10.0 scfh)
Standard: 1/4 inch NPT female stainless steel
(all input ranges); also available, steel or stainless
Delivery Capacity(5)
steel reducing adapters that permit 1/2 inch male
or female connections 0.2 to 1.0 Bar (3 to 15 Psig) Output: 5.6 m3/hr
Optional: 1/2 inch NPT male stainless steel (240 scfh)
0.4 to 2.0 Bar (6 to 30 Psig) Output: 9.9 m3/hr
Supply and Output Connections (350 scfh)
1/4 inch NPT female
Exhaust Capacity(5)
Supply Pressure Requirements(3) 0.2 to 1.0 Bar (3 to 15 Psig) Output: 4.6 m3/hr
See table 1-4 (186 scfh)
0.4 to 2.0 Bar (6 to 30 Psig) Output: 7.0 m3/hr
Supply Pressure Medium (295 scfh)
Air or natural gas(4)
Operative Ambient Temperature Limits(1,3)
Remote Set Point Pressures −40 to 70_C (−40 to 160_F)
0.2 to 1.0 bar (3 to 15 psig) or 0.4 to 2.0 bar (6 to
30 psig) Hazardous Area Classification
Complies with the requirements of ATEX Group II
Controller Adjustments Category 2 Gas and Dust
Proportional Band(1): 5 to 500% of process
scale range
continued

1-4
Instruction Manual
Form 5196
May 2006 4194A, B, and C Series

Table 1-1. Specifications (continued)

Housing Declaration of SEP


Designed to NEMA 3 (Weatherproof) and IEC Fisher Controls International LLC declares this
529 IP54 specifications product to be in compliance with Article 3
paragraph 3 of the Pressure Equipment Directive
Mounting (PED) 97 / 23 / EC. It was designed and
manufactured in accordance with Sound
Controller can be mounted on actuator, panel, Engineering Practice (SEP) and cannot bear the
wall, or pipestand CE marking related to PED compliance.
However, the product may bear the CE marking
Approximate Weight to indicate compliance with other applicable EC
4.5 kg (10 lb) Directives.
1. These terms are defined in ISA Standard S51.1
2. Consult your Emerson Process Management sales office for additional information
3. The pressure/temperature limits in this document and any applicable standard or code limitation should not be exceeded.
4. This product can be used with natural gas. Natural gas should not contain more that 20 ppm of H2S
5. Normal m3/hr—Normal cubic meters per hour (0_C and 1.01325 bar, absolute). Scfh—Standard cubic feet per hour (60_F and 14.7 psia).

Educational Services Note


For information on available courses for 4194A, B, Neither EmersonR, Emerson Process
and C Series differential pressure controllers, as well Management, FisherR, nor any of their
as a variety of other products, contact: affiliated entities assumes
Emerson Process Management responsibility for the selection, use,
Educational Services, Registration and maintenance of any product.
P.O. Box 190; 301 S. 1st Ave. Responsibility for the selection, use,
Marshalltown, IA 50158−2823 and maintenance of any product
Phone: 800−338−8158 or remains with the purchaser and
Phone: 641−754−3771 end-user.
FAX: 641−754−3431
e-mail: education@emersonprocess.com

1-5
Instruction Manual
Form 5196
4194A, B, and C Series May 2006

Table 1-2. Available Configurations for 4194A, 4194B, and 4194C Series Controllers
MODES OPTIONS
Proportional-
Proportional- Proportional- Internal
TYPE Plus-Reset- Remote
SERIES Only Plus-Reset Auto/Manual Anti-Reset Windup
NUMBER(1) Plus-Rate Set point
(One-Mode (Two-Mode Station (suffix letter F)
(Three-Mode (suffix letter M)
Controllers) Controllers) (suffix letter E)
Controllers)
4194A X −−− −−− −−− −−− −−−
4194AE X −−− −−− X −−− −−−
4194A
4194AM X −−− −−− −−− −−− X
4194AME X −−− −−− X −−− X
4194B −−− X −−− −−− −−− −−−
4194BE −−− X −−− X −−− −−−
4194BF −−− X −−− −−− X −−−
4194BFE −−− X −−− X X −−−
4194B
4194BM −−− X −−− −−− −−− X
4194BME −−− X −−− X −−− X
4194BFM −−− X −−− −−− X X
4194BFME −−− X −−− X X X
4194C −−− −−− X −−− −−− −−−
4194CE −−− −−− X X −−− −−−
4194CF −−− −−− X −−− X −−−
4194CFE −−− −−− X X X −−−
4194C
4194CM −−− −−− X −−− −−− X
4194CME −−− −−− X X −−− X
4194CFM −−− −−− X −−− X X
4194CFME −−− −−− X X X X
1. Reverse-acting constructions are designated by the suffix letter R added to the type number.

Table 1-3. Process Sensor (Capsular Element) Pressure Ratings and Material
DIFFERENTIAL STATIC PRESSURE
CAPSULAR SPAN OPERATING RANGE(3)
OPERATING STANDARD
UNITS ELEMENT Minimum
LIMITS(4) MATERIAL
RANGES Minimum(1) Maximum(2) Inches of Maximum
Mercury
0 to 350 mbar 175 mbar 350 mbar −350 mbar 455 mbar 500 mbar
Metric 0 to 0.7 bar 0.4 bar 0.7 bar −0.7 bar 0.9 bar 1.0 bar
Units 0 to 1.4 bar 0.7 bar 1.4 bar −1.0 bar 1.8 bar 2.1 bar
0 to 2.0 bar 1.0 bar 2.0 bar −1.0 bar 2.7 bar 3.1 bar
N09902
0 to 5 psid 2.5 psid 5 psid −10 6.5 psig 7.5 psig
U. S. 0 to 10 psid 5.0 psid 10 psid −20 13.5 psig 15.0 psig
Units 0 to 20 psid 10.0 psid 20 psid −30 27.0 psig 30.0 psig
0 to 30 psid 15.0 psid 30 psid −30 40.5 psig 45.0 psig
1. Span is adjustable between minimum shown and maximum of the capsular element operating range and can be positioned any where within this range. For example, if a 0 to 2.0 bar
(0 to 30 psid) capsular element is used with a minimum span of 1.0 bar (15 psid), 1.0 to 2.0 bar (15 to 30 psid), or any value between the minimum and maximum values of the
operating range is possible.
2. Maximum difference between the two input supply pressures.
3. Capsular element may be pressured to this value without permanent zero shift or structural damage to controller components.
4. With travel stops set, capsular element may be pressured to this value without permanent zero shift or structural damage to controller components.

Table 1-4. Supply Pressure Data


Maximum Pressure
Normal Operating
Output Signal Range To Prevent Internal
Supply Pressure(1)
Part Damage(2)
Metric 0.2 to 1.0 bar 1.4 bar 2.8 bar
Units 0.4 to 2.0 bar 2.4 bar 2.8 bar
U.S. 3 to 15 psig 20 psig 40 psig
Units 6 to 30 psig 35 psig 40 psig
1. If the pressure is exceeded, control stability may be impaired.
2. If the pressure is exceeded, damage to the controller may result.

1-6
Instruction Manual
Form 5196
May 2006 4194A, B, and C Series

Section 22-2- TYPE 657


ACTUATOR
Installation
TYPE 4194
CONTROLLER
WARNING

To avoid personal injury or property


damage resulting from the sudden
release of pressure:
D Always wear protective clothing,
gloves, and eyewear when performing
any installation operations.
D Personal injury or property
damage may result from fire or TYPE 67FR
explosion if natural gas is used as the FILTER
REGULATOR
supply medium and preventative
measures are not taken. Preventative
MOUNTING
measures may include: Remote PLATE
venting of the unit, re-evaluating the
W5661 / IL
hazardous area classification,
ensuring adequate ventilation, and the
Figure 2-1. Typical Actuator Mounting
removal of any nearby ignition
sources. For information on remote
venting of this controller, refer to
page 2-4.
Panel Mounting
Using the dimensions shown in figure 2-3, cut a hole
D If installing into an existing in the panel surface. Slide the controller into the hole
application, also refer to the and attach the bracket (key 68) to the rear of the
WARNING at the beginning of the controller using three cap screws (key 66) and lock
Maintenance section of this washers (key 67). Tighten the screws (key 70) to
instruction manual. seat the case snugly and evenly against the panel
D Check with your process or surface.
safety engineer for any additional
measures that must be taken to Wall Mounting
protect against process media.
Using the dimensions in figure 2-4, drill holes in the
wall to align with the four holes in the bracket (key
68). If the tubing is to run through the wall, drill a
Controller Mounting Orientation hole in the wall large enough to accept the tubing.

Mount the controller with the housing vertical, as Mount the controller to the bracket using three cap
shown in figure 2-1, so that the vent points down. screws (key 66) and lock washers (key 67). Attach
the bracket to the wall, using suitable screws or
bolts.

Pipestand Mounting Actuator Mounting


Refer to figure 2-2. Pipestand mounting parts are Refer to figure 2-1. A controller specified for
provided to mount the controller to a 2-inch mounting on a control valve actuator is mounted at
(nominal) pipe. Attach a bracket (key 68) to the the factory. If the controller is ordered separately for
controller with cap screws (key 66) and lock washers installation on a control valve actuator, mount the
(key 67). Attach two clamps (key 69) to the bracket, unit as described in this section. Mounting parts vary
and fasten the controller to the pipe. for different actuator types.

2-1
Instruction Manual
Form 5196
4194A, B, and C Series May 2006

HEX HEAD
CAP SCREW REGULATOR
(KEY 66)
HEX HEAD
LOCKWASHER CAP SCREW
(KEY 67) (KEY 362)

HEX NUT BRACKET


(KEY 364) (KEY 68)

LOCKWASHER
(KEY 363)

PIPE CLAMP ELBOW


(KEY 69) (KEY 365)

VERTICAL PIPE
HEX HEAD
CAP SCREW
(KEY 362)

LOCKWASHER PIPE CLAMP


(KEY 363) (KEY 69)

HEX NUT
(KEY 364)

HEX HEAD BRACKET


CAP SCREW (KEY 66) (KEY 68)

LOCKWASHER ELBOW
(KEY 67) (KEY 365)

49A3196-A
A6732 / IL HORIZONTAL PIPE

Figure 2-2. Pipestand Mounting

Attach the mounting bracket to the actuator yoke


84 with cap screws, lock washers, and spacer spools.
(3.29) Attach the controller to the bracket with cap screws,
63 lock washers, and spacer spools. On some designs,
LOCK
(2.49) the mounting bracket is attached to the actuator
WASHER
(KEY 67)
casing rather than to the yoke.
TOP VIEW
HEX HEAD 13
CAP SCREW (0.50)
(KEY 66)
BRACKET
Pressure Connections
(KEY 68) 62
(2.43)

ROUND
HEAD
WARNING
MACHINE 12.06
SCREW (306)
(KEY 70) To avoid personal injury or property
14
(0.56 R) damage resulting from the sudden
236
release of pressure, do not install any
(9.31) system component where service
REAR VIEW
36A9760-A
A6733 / IL
conditions could exceed the limits
DIMENSIONS OF
PANEL CUTOUT given in this manual. Use
mm pressure-relieving devices as required
(INCH) by government or accepted industry
codes and good engineering
Figure 2-3. Panel Mounting practices.

2-2
Instruction Manual
Form 5196
May 2006 4194A, B, and C Series
instrument for gas-filled lines. This reduces the
possibility of air becoming trapped in the sensor with
161 liquid-filled lines or of condensation becoming
(6.35)
trapped in gas-filled lines. The recommended slope
is 83 millimeters per meter (1 inch per foot).

TOP VIEW LOCKWASHER


(KEY 67)
260 Supply Pressure Connection
(10.25)
HEX HEAD
CAP SCREW
(KEY 66) WARNING

Severe personal injury or property


152
(6.00)
damage may occur if the instrument
air supply is not clean, dry, and
oil-free, or noncorrosive gas. While
62 use and regular maintenance of a filter
13 (2.43) that removes particles larger than 40
(0.50)
microns in diameter will suffice in
13
(0.50)
BRACKET most applications, check with an
36A9761-B (KEY 68)
A6734 / IL
REAR VIEW
Emerson Process Management field
mm
(INCH) office and industry instrument air
quality standards for use with
corrosive gas or if you are unsure
Figure 2-4. Wall Mounting about the proper amount or method of
air filtration or filter maintenance.

Refer to figure 2-5 for pressure connection locations. Supply pressure must be clean, dry air or
Supply, output, remote set point, and vent noncorrosive gas that meets the requirements of
connections are 1/4-inch NPT, female. Process ISA Standard S7.35. Use a suitable supply pressure
pressure connections are 1/4- or 1/2-inch NPT regulator to reduce the supply pressure source to
(optional). the normal operating supply pressure shown in table
1-4. Connect supply pressure to the SUPPLY
connection on the bottom of the case, shown in
figure 2-5.
Process Pressure Connections
Process pressures are piped to the connections
marked A and B on the bottom of the case, shown in Remote Set Point (suffix letter M)
figure 2-5. Pipe the high pressure line to connection
B and the low pressure line to connection A.
Pressure Connection
If the controller has remote set point (suffix letter M),
When installing process piping, follow accepted connect the remote set point pressure to the top of
practices to ensure accurate transmission of the the controller case at the location shown in figure
process pressure to the controller. Install a 2-5. Use clean dry air or noncorrosive gas. Use a
three-valve bypass, shutoff valves, vents, drains, or 0.2 to 1.0 bar (3 to 15 psig) remote set point
seal systems as needed in the process pressure pressure range for a 0.2 to 1.0 bar (3 to 15 psig)
lines. If necessary, install a needle valve in a controller output signal range or a 0.4 to 2.0 bar (6
process pressure sensing line to dampen pulsations. to 30 psig) remote set point pressure range for a 0.4
to 2.0 bar (6 to 30 psig) controller output signal
range. If pressure is supplied to the remote set point
If the instrument is located such that the adjacent connection with a regulator, a small bleed orifice
process pressure lines are approximately horizontal, should be placed between the regulator and remote
the lines should slope downward to the instrument set point connection to prevent pressure variations
for liquid-filled lines and upward toward the due to regulator lock-up.

2-3
Instruction Manual
Form 5196
4194A, B, and C Series May 2006

do not form gas tight seal when the


assembly is enclosed, a remote vent
REMOTE line, adequate ventilation, and
SET POINT necessary safety measures should be
CONNECTION
used to prevent the accumulation of
flammable or hazardous gas.
However, a remote vent pipe alone
cannot be relied upon to remove all
flammable and hazardous gas. Vent
TOP VIEW line piping should comply with local
and regional codes, and should be as
short as possible with adequate inside
diameter and few bends to reduce
case pressure buildup.
SUPPLY
PRESSURE

LOW
PRESSURE (A)
CAUTION
CONTROLLER
HIGH VENT OUTPUT
PRESSURE (B) PRESSURE When installing a remote vent pipe,
46A9765-A
A3001 / IL BOTTOM VIEW take care not to over-tighten the pipe
in the vent connection. Excessive
Figure 2-5. Location of Connections torque will damage the threads in the
connection.
If a remote vent is required, the vent line must be as
Vent short as possible with a minimum number of bends
and elbows. Vent line piping should have a minimum
inside diameter of 19 mm (3/4 inches) for runs up to
WARNING 6.1 meters (20 feet) and a minimum inside diameter
of 25 mm (1 inch) for runs from 6.1 to 30.5 meters
(20 to 100 feet).
Personal injury or property damage
could result from fire or explosion of The vent must be protected against the entrance of
accumulated gas, or from contact with any foreign material that could plug it; or, if a remote
hazardous gas, if a flammable or vent is not required, the vent opening in the case
hazardous gas is used as the supply must be protected against the entrance of any
pressure medium. Because the foreign material that could plug it. Check the vent
instrument case and cover assembly periodically to be certain it is not plugged.

2-4
Instruction Manual
Form 5196
May 2006 4194A, B, and C Series

METAL BALL

SWITCHING ZONE
INDICATOR

LOADER KNOB

AUTO/MANUAL
SWITCH

W3679 / IL

SET POINT
INDICATOR
AUTO/MANUAL STATION
(SUFFIX LETTER E)
PROCESS POINTER

PROPORTIONAL BAND
ADJUSTMENT

PROPORTIONAL BAND
INDICATOR COVER

OUTPUT PRESSURE
GAUGE

W6391 / IL

Figure 3-1. 4194A Series Controller Adjustment Locations

Section 33-3- set point does not affect the proportional band
setting.
4194A Series
Proportional-Only Controllers If the controller is equipped with the optional internal
or external set point adjustment, turn the adjustment
knob clockwise to increase the process set point and
Adjustments for 4194A Series counterclockwise to decrease the process set point.
Controllers
This section includes descriptions of adjustments Remote Set Point (suffix letter M)
and procedures for prestartup, startup, and Adjustment
calibration. Adjustment locations are shown in
figures 3-1 and 3-3. To better understand the
adjustments and overall controller operation, refer to CAUTION
the principle of operation section and to the
schematic diagrams in figures 3-4 and 3-5. Unless
otherwise noted, key numbers given in this section Do not manually move the set point
are found in figure 6-1. indicator on controllers with remote
set point. Manually moving the set
point indicator could damage the
Manual Set Point Adjustment controller.

Adjust the set point by moving the set point indicator If the controller is equipped with remote set point
until the line on the set point indicator is over the (suffix letter M), vary the remote set point pressure
desired value on the process differential pressure to change the set point. Increase the pressure to
scale. Move the indicator to the right to increase the increase the set point, and decrease the pressure to
set point, and to the left to decrease it. Adjusting the decrease the set point.

3-1
Instruction Manual
Form 5196
4194A, B, and C Series May 2006

After changing the action, tighten the two screws on


the proportional band indicator cover.

Switching the Auto/Manual Station


(suffix letter E)

Note
Switching the controller between
automatic and manual mode without
balancing can disturb the process and
cause controller cycling.
Refer to figure 3-1 if the controller has the
auto/manual station (suffix letter E). To switch from
automatic to manual mode, or from manual to
W3439 / IL
automatic, you must first balance the manual output
with the controller output. Two balance methods are
Figure 3-2. Changing Controller Action
(4194A Series Controllers)
available to equalize the manual output with the
controller output.

To switch from automatic to manual mode, carefully


Proportional Band Adjustment (PB ADJ) adjust the loader knob until the metal ball inside the
The proportional band determines the output plastic tube moves into the switching zone. Then
sensitivity of the controller. The proportional band move the automatic/manual switch to MANUAL.
adjustment is marked in percentages of process Turn the loader knob clockwise to increase the
differential pressure required to drive the controller controller output or counterclockwise to decrease it.
from zero output to full output.
To switch from manual to automatic mode, adjust
To adjust the proportional band, open the controller the set point to move the ball into the switching
cover and locate the proportional band adjustment zone. Turn the switch to AUTO and adjust the set
(PB ADJ) knob. Rotate the knob until the desired point to control the output.
value is opposite the line on the proportional band
indicator cover. When the auto/manual switch is in AUTO, adjusting
the loader knob has no effect on the controller
output. When the auto/manual switch is in MANUAL,
Changing Controller Action changing the set point has no effect on the controller
output.
To change the controller action from direct to
reverse or vice versa, loosen the screws on the
proportional band indicator cover. Lift the cover out Prestartup Checks for 4194A Series
as shown in figure 3-2 and rotate the proportional
band adjustment to the desired action. Setting the
Controllers
proportional band to the values in the white portion Refer to figure 3-1 for adjustment locations and refer
of the adjustment provides direct controller action; to figure 6-1 for key number locations.
setting proportional band in the black portion
provides reverse controller action. When performing the checks, open loop conditions
must exist. An open loop exists when the controller
For direct control action: output does not affect the input pressure or other
control signal to the controller.
An increasing sensed differential pressure increases
output pressure. Note
For reverse control action: If the controller has the auto/manual
station (suffix letter E), be sure the
An increasing sensed differential pressure controller is in the automatic mode
decreases output pressure. before performing prestartup checks.

3-2
Instruction Manual
Form 5196
May 2006 4194A, B, and C Series
1. Provide a means of measuring the controller 1. Be sure the supply pressure regulator is
output pressure by connecting the controller output delivering the proper supply pressure to the
to a pressure gauge. Connect supply pressure to the controller.
supply pressure regulator and be sure it is delivering
2. For controllers with:
the proper supply pressure to the controller. Do not
exceed the normal operating pressure in table 1-4. Manual set point:
2. For a controller with remote set point (suffix letter
M), connect regulated pressure of 0.2 to 1.0 bar (3 Move the set point indicator to the desired set point.
to 15 psig) or 0.4 to 2.1 bar (6 to 30 psig) to the
remote set point connection at the top of the Remote set point:
controller case.
a. See figure 2-5 for the location of the remote
3. Remove the two machine screws (key 6) and lift set point connection. Connect an adjustable
off the proportional band indicator cover (key 36). pressure source to the remote set point
4. Adjust the set point a minimum of 20 percent of connection.
input span above the process pointer.
b. Adjust the pressure source until the set point
5. Adjust the proportional band for 5 percent indicator reaches the desired set point.
DIRECT. Remember: Increasing the remote set point
pressure increases the set point.
6. If necessary, connect a pressure source to the
process connection and adjust the process pointer 3. Set the proportional band adjustment to 100
to the last mark on the left side of the scale. If the percent for fast processes. For slow processes,
last scale mark is 0 psig, a pressure source is not calculate the proportional band percentage from the
required. equation below:
7. The controller output pressure should be 0 psig. Proportional
8. Rotate the proportional band to 5 percent Band + 200 Allowable Overshoot
REVERSE. Adjustment Pressure Span

9. The controller output should be within 0.14 bar (2 For example:


psig) of the supply pressure.
200 2 Psig
10. If the controller output is within tolerance, adjust ^ 13%
the proportional band to 400 percent in the desired 30 Psig
action, secure the proportional band indicator cover 4. Create a load upset by momentarily changing the
(key 36) with the machine screws (key 6), and go to set point. Check for system cycling. If the system
the startup procedure. If the controller output does not cycle, lower the proportional band setting
pressure is not within tolerance, go to the 4194A (thus raising the gain) and disturb the system again
Series calibration procedure for recalibration. by changing the set point. Continue this procedure
until the system cycles. At this point, double the
proportional band setting (proportional band setting
2).
Startup for 4194A Series Controllers
5. Check the stability of the recommended
Perform the prestartup checks and, if necessary, proportional band setting by introducing a
calibrate the controller prior to this procedure. disturbance and monitoring the process.

Note Calibration of 4194A Series Controllers

When performing the startup


procedures, keep in mind that the
WARNING
initial settings are guidelines. They
will vary depending on the actual To avoid personal injury or property
process being controlled. damage resulting from the sudden

3-3
Instruction Manual
Form 5196
4194A, B, and C Series May 2006

release of pressure, do not exceed the 3. Apply process differential pressure equal to the
operating limits given in this manual. process scale span lower limit.
4. The process pointer should indicate the process
General Calibration Instructions scale lower limit. If not, adjust the process pointer to
the process scale lower limit by loosening the zero
adjustment locking screw and turning the zero
Note adjustment screw. Tighten the zero adjustment
locking screw.
If the controller has the auto/manual
station (suffix letter E), be sure the 5. Apply process differential pressure equal to the
controller is in the automatic mode process scale span upper limit.
before performing calibration. 6. The process pointer should indicate the process
scale upper limit. If not, adjust the span screw to
If the prestartup checks, or startup, reveal faulty correct one-half the error as follows: clockwise to
controller operation, perform the calibration increase span for a low indication (below the upper
described in this section. These instructions are limit); counterclockwise to decrease span for a high
valid for either shop or field calibration, provided that indication (above the upper limit).
open process loop conditions exist. Unless
otherwise noted, key numbers are found in figure 7. Repeat steps 3 through 6 until the error is
6-1. eliminated.
8. Apply process differential pressure equal to the
Do not use the gauges supplied with the controller mid-scale value of the process scale span. The
during calibration. Monitor process pressure, supply process pointer should indicate the mid-scale mark,
pressure, controller output pressure, and, if ±2 percent of span. If the error is greater than ±2
applicable, remote set point pressure with external percent, refer to the Maintenance section and
gauges. perform the zero and span adjustment procedure.
9. Adjust the process pointer to within ±1 percent of
Process Indicator Zero and Span the mid-scale mark by loosening the locking screw
Calibration and turning the zero adjustment screw. This
distributes the error over the entire scale span and
Before starting this procedure: brings all points within ±1 percent of the process
scale span.
D Provide a regulated process differential
10. Apply process differential pressure equal to the
pressure to the controller and a means of
process scale span lower limit.
measurement external to the controller.
11. The process pointer should indicate the process
D Provide a means of measuring the controller scale lower limit ±1 percent of the scale span.
output pressure by connecting the controller output
12. Apply process pressure equal to the process
to a pressure gauge (open-loop conditions must
scale span upper limit.
exist). Provide a regulated supply pressure to the
controller. Do not exceed the normal operating 13. The process pointer should indicate the process
pressure in table 1-4. scale upper limit ±1 percent of the process scale
span.
Note 14. If the error is greater than ±1 percent, repeat
steps 3 through 13.
Any change to the process pointer
span adjustment will require
readjustment of the process pointer Remote Set Point (suffix letter M) Zero
zero adjustment. and Span Calibration
Refer to figures 3-1 and 3-3 for adjustment
Refer to figures 3-1 and 3-3 for adjustment locations. Refer to figures 6-1 and 6-5 for key
locations. number locations.
1. Remove the two screws (key 6) and lift off the
proportional band indicator cover (key 36). Note
2. Set the proportional band between DIRECT and Any adjustment of the remote set
REVERSE. point span adjustment screw requires

3-4
Instruction Manual
Form 5196
May 2006 4194A, B, and C Series
readjustment of the remote set point Flapper Alignment
zero adjustment screw.
1. Remove the two screws (key 6) and lift off the Note
proportional band indicator cover (key 36). Perform the process indicator zero
and span calibration procedure and,
2. Set the proportional band between DIRECT and for controllers with remote set point
REVERSE. (suffix letter M), the remote set point
3. Apply remote set point pressure equal to the zero and span calibration procedure
lower range limit. before the flapper alignment.
Flapper leveling screw numbers and adjustments
4. The set point indicator should indicate the
are shown in figure 3-3. Key number locations are
process scale lower limit. If not, loosen the remote
shown in figure 6-1.
set point zero adjustment locking screw and adjust
the remote set point zero adjustment screw until the Provide a means of measuring the controller output
set point indicator aligns with the process scale pressure by connecting the controller output to a
lower limit. Tighten the zero adjustment locking pressure gauge (open-loop conditions must exist).
screw. Provide a regulated supply pressure to the
5. Apply remote set point pressure equal to the controller. Do not exceed the normal operating
pressure in table 1-4. After performing the flapper
upper range limit.
alignment procedure, go to the startup procedure.
6. The set point indicator should indicate the 1. For a controller with manual set point, move the
process scale upper limit. If not, adjust the remote set point indicator to the mid-scale mark on the
set point span adjustment screw to correct one-half process scale. For a controller with remote set point
the error as follows: clockwise to increase span for a (suffix letter M), adjust the remote set point pressure
low indication; counterclockwise to decrease span until the set point indicator is at the mid-scale on the
for a high indication. process scale.
7. Repeat steps 3 through 6 until the error is 2. Apply process differential pressure equal to the
eliminated. mid-scale value of the process scale span. If
pressure is not available to pressure the input
8. Apply remote set point pressure equal to the element to the mid-scale value, an alternate method
mid-range value. is to disconnect link number 1 at the input element
and tape the process pointer at the mid-scale mark
9. Make sure the set point indicator is within ±1 of the process scale. Note the hole from which link
percent of the mid-scale mark and if so, proceed to number 1 was removed for proper replacement. This
step 12. If the set point indicator is not within 1 method should only be used if pressure is not
percent, but is within ±2 percent of the mid-scale available to pressure the input element to the
mark, then proceed with step 10. If the set point mid-scale value.
indicator is not within ±2 percent, proceed to the
remote set point calibration procedure in the 3. Remove the two machine screws (key 6) and lift
Maintenance section. off the proportional band indicator cover (key 36).
4. Set the proportional band between DIRECT and
10. Loosen the remote set point zero adjustment REVERSE.
locking screw and adjust the remote set point zero
adjustment screw to correct for half the error at 5. The controller output should be 0.62 ±0.007 bar
mid-scale. Tighten the zero adjustment locking (9 ±0.10 psig) for a 0.2 to 1.0 bar (3 to 15 psig)
screw. output or 1.2 ±0.01 bar (18 ±0.2 psig) for a 0.4 to 2.0
bar (6 to 30 psig) output. If not, adjust flapper
11. Apply remote set point pressure equal to the leveling screw 2 (the screw nearest the nozzle) until
lower and upper range limits and make sure the set the output is within tolerance.
point indicator is within ±1 percent. 6. Set the proportional band to 30 percent DIRECT.
12. If necessary, perform the process indicator zero 7. The controller output should be 0.62 ±0.02 bar (9
and span calibration procedure in this section. ±0.25 psig) or 1.2 ±0.04 bar (18 ±0.5 psig). If not,
Otherwise, perform the flapper alignment procedure adjust flapper leveling screw 3 (the screw nearest
in this section. the nozzle).

3-5
Instruction Manual
Form 5196
4194A, B, and C Series May 2006

POINTER ZERO
ADJUSTMENT

POINTER ZERO
ADJUSTMENT
LOCKING SCREW

REMOTE SET POINT REMOTE SET POINT PROCESS POINTER


ZERO ADJUSTMENT ZERO ADJUSTMENT SPAN ADJUSTMENT
(SUFFIX LETTER M) LOCKING SCREW
W6391 / IL (SUFFIX LETTER M)

FRONT VIEW

SCREW 1

SCREW 2

SCREW 3

39A1126-B

PROCESS REMOTE SET POINT


POINTER SPAN SPAN ADJUSTMENT
ADJUSTMENT (SUFFIX LETTER M)
56A9752-S SHT 1

SIDE VIEW OF SET POINT/ SIDE VIEW OF CONTROLLER


A6730 / IL
PROCESS INDICATOR ASSEMBLY SHOWING FLAPPER LEVELING SCREWS

Figure 3-3. 4194A Series Controller Calibration Adjustment Locations

3-6
Instruction Manual
Form 5196
May 2006 4194A, B, and C Series

SET POINT INDICATOR RESET BELLOWS (VENTED) REVERSE ACTION


QUADRANT
PROPORTIONAL
BELLOWS PROPORTIONAL
BAND ADJUSTMENT
FEEDBACK
PROCESS POINTER LINK

REMOTE SET POINT


CONNECTED HERE
FEEDBACK
INPUT ELEMENT MOTION FLAPPER PIVOT
CONNECTED HERE
DIRECT ACTION
CONNECTING QUADRANT INPUT
LINK MOTION

FLAPPER DETAIL
BEAM
OUTPUT PRESSURE
TO FINAL CONTROL
ELEMENT

FLAPPER

NOZZLE
SUPPLY PRESSURE
RELAY
OUTPUT PRESSURE

SUPPLY
PROPORTIONAL PRESSURE PRESSURE

NOZZLE PRESSURE
46A9764-A
B1489-2 / IL

Figure 3-4. 4194A Series Controller Schematic

8. Set the proportional band to 30 percent the nozzle, restricting flow through the nozzle and
REVERSE. increasing nozzle pressure. When this occurs, relay
action increases the output pressure (delivery) of the
9. The controller output should be 0.62 ±0.02 bar (9
controller. Output pressure is fed back to the
±0.25 psig) or 1.2 ±0.04 bar (18 ±0.5 psig). If not,
proportional bellows. The action of the proportional
adjust flapper leveling screw 1 (the screw nearest
bellows counteracts the flapper movement that
the nozzle).
resulted from the process differential pressure
10. Repeat steps 4 through 9 until the controller change and backs the flapper away from the nozzle
output remains in tolerance without further leveling until equilibrium is reached.
screw adjustment.
11. If link 1 was disconnected, remove the tape and Moving the set point indicator changes the distance
reconnect link 1 to the input element. between the nozzle and flapper as does a change in
12. Set the proportional band to 400 percent in the process pressure, except that when the set point is
desired controller action and replace the proportional changed, the nozzle moves with respect to the
band indicator cover. flapper.

The proportional band adjustment positions the


Principle of Operation for 4194A Series nozzle on the flapper. Increasing (widening) the
Controllers proportional band moves the nozzle to a position on
the flapper where less input and more feedback
Overall Operation motion occurs, which decreases the gain of the
controller. Decreasing (narrowing) the proportional
Refer to the schematic diagram in figure 3-4. band moves the nozzle toward a position where
more input and less feedback motion occurs, which
The input element is connected to the process increases the gain. The controller action is changed
pointer and to the flapper by connecting links. As the from direct to reverse by turning the proportional
process differential pressure increases (in a band adjustment to position the nozzle on the
direct-acting controller), the flapper moves toward flapper quadrant to a point where the direction of the

3-7
Instruction Manual
Form 5196
4194A, B, and C Series May 2006

MANUAL LOADER
AUTOMATIC
POSITION

AUTO/MANUAL
SWITCH MANUAL
LOADER
KNOB

PLASTIC TUBE
OUTPUT PRESSURE
TO FINAL CONTROL METAL BALL
ELEMENT

MANUAL
RELAY POSITION

AUTO/MANUAL
SWITCH
SUPPLY
PRESSURE OUTPUT PRESSURE
TO FINAL CONTROL
RELAY OUTPUT PRESSURE ELEMENT
SUPPLY PRESSURE

MANUAL LOADER OUTPUT PRESSURE

48A5230-A
A2999-1 / IL

Figure 3-5. 4194A Series Auto/Manual Station Schematic

flapper motion versus input motion is reversed as on the output side of the relay as shown in figure
shown in the flapper detail of figure 3-4. With the 3-5. Supply pressure to the relay is also applied to
controller in the reverse-acting mode, an increase in the manual loader. The manual loader, functioning
process differential pressure causes a decrease in as a regulator, applies pressure to one side of the
output pressure. plastic tube and to the auto/manual switch. Output
pressure from the relay registers on the other side of
the plastic tube as well as in the auto/manual switch.
Remote Set Point (suffix letter M)
Operation
When the auto/manual switch is in the MANUAL
The capability to adjust the controller set point from
position, the manual loader output is channeled
a remote location is available with all 4194A Series
through the auto/manual switch and becomes the
controllers. This option is designated by the suffix
controller output. When the auto/manual switch is in
letter M in the type number.
the AUTO position, the relay output is channeled
through the switch to become the controller output.
A control pressure is applied to the capsular element
within the remote set point assembly. The expansion
and contraction of the capsule moves the set point
Before the auto/manual switch is operated, the relay
indicator via a connecting linkage. Increasing the
output must equal the manual loader output to avoid
control pressure to the capsule increases the set
bumping the process. Adjusting the set point varies
point setting and decreasing the control pressure
the pressure on the left-hand side of the plastic tube.
reduces the set point setting.
Adjusting the manual loader knob varies the
pressure on the right-hand side. When the pressures
Auto/Manual Station (suffix letter E) are equal, the metal ball is centered in the tube and
Operation is held in place by a small magnet. A pressure
imbalance forces the ball to one end of the tube
A controller with the auto/manual station (designated where it forms a seal, blocking air flow through the
by the suffix letter E in the type number) has piping tube.

3-8
Instruction Manual
Form 5196
May 2006 4194A, B, and C Series

METAL BALL

SWITCHING ZONE
INDICATOR

LOADER KNOB

AUTO/MANUAL
SWITCH

SET POINT
INDICATOR
W3679 / IL

PROCESS POINTER
AUTO/MANUAL STATION
PROPORTIONAL BAND (SUFFIX LETTER E)
INDICATOR COVER

PROPORTIONAL BAND
ADJUSTMENT

ANTI-RESET WINDUP
DIFFERENTIAL RELIEF
VALVE (SUFFIX LETTER F)

RATE
ADJUSTMENT RESET
SUPPLY RESET OUTPUT PRESSURE W3599−1 / IL ADJUSTMENT
PRESSURE GAUGE ADJUSTMENT GAUGE

TYPICAL ADJUSTMENTS 4194C RESET AND RATE ADJUSTMENTS


W6392 / IL 4194B SHOWN

Figure 4-1. 4194B and C Series Controller Adjustment Locations

Section 44-4- Manual Set Point Adjustment


Adjust the set point by moving the set point indicator
4194B Series Proportional- until the line on the set point indicator is over the
Plus-Reset Controllers And 4194C desired value on the process differential pressure
scale. Move the indicator to the right to increase the
Series Proportional- set point, and to the left to decrease it. Adjusting the
Plus-Reset-Plus-Rate Controllers set point does not affect the proportional band
setting.
If the controller is equipped with the optional internal
or external set point adjustment, turn the adjustment
knob clockwise to increase the process set point and
Adjustments for 4194B and C Series counterclockwise to decrease the process set point.
Controllers
Remote Set Point (suffix letter M)
This section includes descriptions of adjustments
Adjustment
and procedures for prestartup, startup and
calibration. Adjustment locations are shown in CAUTION
figures 4-1 and 4-3. To better understand the
adjustments and overall controller operation, refer to Do not manually move the set point
the principle of operation section and to the indicator on controllers with remote
schematic diagrams in figures 4-5, 4-6, 4-7 and 4-8. set point. Manually moving the set
Unless otherwise noted, key numbers given in this point indicator could damage the
section are found in figure 6-1. controller.

4-1
Instruction Manual
Form 5196
4194A, B, and C Series May 2006

For direct control action:

An increasing sensed differential pressure increases


output pressure.

For reverse control action:

An increasing sensed differential pressure


decreases output pressure.

After changing the action, tighten the two screws on


the proportional band indicator cover.

Reset Adjustment
To adjust reset, open the controller cover and locate
the RESET adjustment. Rotate the adjustment
clockwise to decrease the minutes per repeat or
W3439 / IL
counterclockwise to increase the minutes per repeat.
Increasing the minutes per repeat provides a slower
Figure 4-2. Changing Controller Action reset action.
(4194B and C Series Controllers)

Rate Adjustment
If the controller is equipped with remote set point
(suffix letter M), vary the remote set point pressure To adjust rate, open the controller cover and locate
to change the set point. Increase the pressure to the RATE adjustment. Rotate the adjustment
increase the set point, and decrease the pressure to clockwise to decrease the minutes (less rate action)
decrease the set point. or counterclockwise to increase the minutes (more
rate action).

Proportional Band Adjustment (PB ADJ) Anti-Reset Windup (suffix letter F)


Adjustment
The proportional band determines the output
sensitivity of the controller. The proportional band If the arrow on the differential relief valve points
adjustment is marked in percentages of process toward the bottom of the controller case, as shown
differential pressure required to drive the controller in figure 4-1, the relief valve opens with increasing
from zero output to full output. controller output pressure. If the arrow points in the
opposite direction, the relief valve opens with
decreasing controller output pressure. Differential
To adjust the proportional band, open the controller relief pressure is factory set at 0.3 bar (5 psig).
cover and locate the proportional band adjustment Maximum relief pressure is 0.5 bar (7 psig);
(PB ADJ) knob. Rotate the knob until the desired minimum is 0.1 bar (2 psig).
value is opposite the line on the proportional band
indicator cover. Turn the adjusting screw counterclockwise to
increase differential relief pressure, clockwise to
decrease it.
Changing Controller Action
To change the controller action from direct to Switching The Auto/Manual Station
reverse or vice versa, loosen the screws on the (suffix letter E)
proportional band indicator cover. Lift the cover out
as shown in figure 4-2 and rotate the proportional Note
band adjustment to the desired action. Setting the
proportional band to the values in the white portion Switching the controller between
of the adjustment provides direct controller action; automatic and manual mode without
setting proportional band in the black portion balancing can disturb the process and
provides reverse controller action. cause controller cycling.

4-2
Instruction Manual
Form 5196
May 2006 4194A, B, and C Series
Refer to figure 4-1 if the controller has the 3. Remove the two machine screws (key 6) and lift
auto/manual station (suffix letter E). To switch from off the proportional band indicator cover (key 36).
automatic to manual mode, or from manual to
automatic, you must first balance the manual output 4. Adjust the set point a minimum of 20 percent of
with the controller output. Two balance methods are input span above the process pointer.
available to equalize the manual output with the
controller output. 5. Turn the reset adjustment to 0.01 minutes per
repeat.
To switch from automatic to manual mode, carefully
6. Turn the rate adjustment to OFF (4194C Series).
adjust the loader knob until the metal ball inside the
plastic tube moves into the switching zone. Then 7. Adjust the proportional band for 5 percent
move the automatic/manual switch to MANUAL. DIRECT.
Turn the loader knob clockwise to increase the
controller output or counterclockwise to decrease it. 8. If necessary, connect a pressure source to the
process connection and adjust the process pointer
To switch from manual to automatic mode, adjust to the last mark on the left side of the scale. If the
the set point to move the ball into the switching last scale mark is 0 psig, a pressure source is not
zone. Turn the switch to AUTO and adjust the set required.
point to control the output.
9. The controller output pressure should be 0 psig.
When the automatic/manual switch is in AUTO,
adjusting the loader knob has no effect on the 10. Rotate the proportional band to 5 percent
controller output. When the automatic/manual switch REVERSE.
is in MANUAL, changing the set point has no effect
on the controller output. 11. The controller output should be within 0.14 bar
(2 psig) of the supply pressure.

12. If the controller output is within tolerance, adjust


Prestartup Checks for 4194B and C the proportional band to 400 percent in the desired
Series Controllers action. Secure the proportional band indicator cover
(key 36) with the machine screws (key 6), and go to
Refer to figure 4-1 for adjustment locations and refer the startup procedure. If the controller output
to figure 6-1 for key number locations. pressure is not within tolerance, go to the 4194B and
C Series calibration procedure for recalibration.
When performing the checks, open loop conditions
must exist. An open loop exists when the controller
output does not affect the input pressure or other
control signal to the controller.
Startup for 4194B and C Series
Controllers
Note
Perform the prestartup checks and, if necessary,
If the controller has the auto/manual calibrate the controller prior to this procedure.
station (suffix letter E), be sure the
controller is in the automatic mode
before performing prestartup checks.
1. Provide a means of measuring the controller Note
output pressure by connecting the controller output
to a pressure gauge. Connect supply pressure to the
supply pressure regulator and be sure it is delivering When performing the startup
the proper supply pressure to the controller. Do not procedures, keep in mind that the
exceed the normal operating pressure in table 1-4. initial settings are guidelines. They
will vary depending on the actual
2. For a controller with remote set point (suffix letter process being controlled.
M), connect regulated pressure of 0.2 to 1.0 bar (3
to 15 psig) or 0.4 to 2.1 bar (6 to 30 psig) to the 1. Be sure the supply pressure regulator is
remote set point connection at the top of the delivering the proper supply pressure to the
controller case. controller.

4-3
Instruction Manual
Form 5196
4194A, B, and C Series May 2006

2. For controllers with: multiply the reset time setting by a factor of three
(reset setting 3) and slow down the reset by
Manual set point: changing the reset setting to the higher value. The
reset is now tuned.
Move the set point indicator to the desired set point.
Tuning rate action: For a controller with rate
Remote set point: (4194C Series), adjust the rate toward the higher
setting until cycling occurs. When the system cycles,
a. See figure 2-5 for the location of the remote divide the rate value by a factor of three (rate setting
set point connection. Connect an adjustable ÷3) and decrease the rate by changing the setting to
pressure source to the remote set point the lower value. The rate is now tuned.
connection.
7. Check the stability of the recommended
b. Adjust the pressure source until the set point proportional band settings by introducing a
indicator reaches the desired set point. disturbance and monitoring the process.
Remember: Increasing the remote set point 8. Once stable control is attained, the process
pressure increases the set point. pointer and set point indicator should be in line. If
3. Set the reset adjustment to 0.05 minutes per they are aligned, adjust the set point to the desired
repeat for fast processes. Set it to 0.5 minutes per value. If they are not, readjust the set point to the
repeat for slow processes. For controllers with rate, desired control point and proceed with step 9.
set the rate adjustment to OFF. 9. If the process pointer is within 5 percent of the
4. Set the proportional band adjustment to 100 set point indicator, turn the link 3 adjustment (see
percent for fast processes. For slow processes, figure 5-13 for location) until the process pointer
calculate the proportional band percentage from the aligns with the set point indicator. Turn the link 3
equation below: adjustment screw clockwise to increase the process
indication or counterclockwise to decrease it. If the
Proportional process pointer is misaligned with the set point
indicator by more than 5 percent of the scale span,
Band + 200 Allowable Overshoot
Adjustment Pressure Span perform the calibration procedures for 4194B and C
Series controllers.
For example:
200 2 Psig Calibration of 4194B and C Series
^ 13%
30 Psig Controllers
5. If the controller is used in conjunction with a
control valve, return the control valve to service by WARNING
slowly opening the upstream and downstream
manual control valves in the pipeline. Close the To avoid personal injury or property
manual bypass valve, if one is used. damage resulting from the sudden
6. Tune the various controller actions. release of pressure, do not exceed the
operating limits given in this manual.
Tuning proportional action: Create a load upset
by momentarily changing the set point. Check for
General Calibration Instructions
system cycling. If the system does not cycle, lower
the proportional band setting (thus raising the gain)
and disturb the system again by changing the set Note
point. Continue this procedure until the system If the controller has the auto/manual
cycles. At this point, double the proportional band station (suffix letter E), be sure the
setting (proportional band setting 2). controller is in the automatic mode
before performing calibration.
Tuning reset action: Disturb the system. If the
system does not cycle, speed up the reset by If the prestartup checks, or startup, reveal faulty
changing the setting to a lower value (faster reset). controller operation, perform the calibration
Disturb the system again. Continue this procedure described in this section. These instructions are
until the system cycles. When the system cycles, valid for either shop or field calibration, provided that

4-4
Instruction Manual
Form 5196
May 2006 4194A, B, and C Series
open process loop conditions exist. Unless limit); counterclockwise to decrease span for a high
otherwise noted, key numbers are found in figure indication (above the upper limit).
6-1.
7. Repeat steps 3 through 6 until the error is
eliminated.
Do not use the gauges supplied with the controller
during calibration. Monitor process pressure, supply 8. Apply process differential pressure equal to the
pressure, controller output pressure, and, if mid-scale value on the process scale span. The
applicable, remote set point pressure with external process pointer should indicate the mid-scale mark,
gauges. ±2 percent of span. If the error is greater than ±2
percent, refer to the Maintenance section and
perform the zero and span adjustment procedure.
Process Indicator Zero and Span
Calibration 9. Adjust the process pointer to within ±1 percent of
the mid-scale mark by loosening the locking screw
Before starting this procedure: and turning the zero adjustment screw. This
distributes the error over the entire scale range and
D Provide a regulated process differential brings all points within ±1 percent of the process
pressure to the controller and a means of scale span.
measurement external to the controller.
10. Apply process differential pressure equal to the
D Provide a means of measuring the controller process scale lower limit.
output pressure by connecting the controller output 11. The process pointer should indicate the process
to a pressure gauge (open-loop conditions must scale lower limit ±1 percent of the scale span.
exist). Provide a regulated supply pressure to the
12. Apply process differential pressure equal to the
controller. Do not exceed the normal operating
process scale upper limit.
pressure in table 1-4.
13. The process pointer should indicate the process
scale upper limit ±1 percent of the process scale
Note span.
Any change to the process pointer 14. If the error is greater than ±1 percent, repeat
span adjustment will require steps 3 through 13.
readjustment of the process pointer
zero adjustment.
Remote Set Point (suffix letter M) Zero
Refer to figures 4-1 and 4-3 for adjustment and Span Calibration
locations. Refer to figures 4-1 and 4-3 for adjustment
1. Remove the two screws (key 6) and lift off the locations. Refer to figures 6-1 and 6-5 for key
proportional band indicator cover (key 36). number locations.

2. Set the proportional band between DIRECT and


REVERSE. Note
3. Apply process differential pressure equal to the Any adjustment of the remote set
process scale span lower limit. point span adjustment screw requires
4. The process pointer should indicate the process readjustment of the remote set point
scale lower limit. If not, adjust the process pointer to zero adjustment screw.
the process scale lower limit by loosening the zero 1. Remove the two screws (key 6) and lift off the
adjustment locking screw and turning the zero proportional band indicator cover (key 36).
adjustment screw. Tighten the zero adjustment
locking screw. 2. Set the proportional band between DIRECT and
REVERSE.
5. Apply process differential pressure equal to the
process scale span upper limit. 3. Apply remote set point pressure equal to the
lower range limit.
6. The process pointer should indicate the process
scale upper limit. If not, adjust the span screw to 4. The set point indicator should indicate the
correct one-half the error as follows: clockwise to process scale lower limit. If not, loosen the remote
increase span for a low indication (below the upper set point zero adjustment locking screw and adjust

4-5
Instruction Manual
Form 5196
4194A, B, and C Series May 2006

POINTER ZERO
ADJUSTMENT
POINTER ZERO
ADJUSTMENT
LOCKING SCREW

PROCESS POINTER
SPAN ADJUSTMENT

ANTI-RESET WINDUP
RELIEF VALVE
(SUFFIX LETTER F)

ANTI-RESET WINDUP
VALVE ADJUSTING SCREW
(SUFFIX LETTER F)

RATE
REMOTE SET POINT REMOTE SET POINT RESET ADJUSTMENT RESET
ZERO ADJUSTMENT ZERO ADJUSTMENT ADJUSTMENT W3599−1 / IL ADJUSTMENT
(SUFFIX LETTER M) LOCKING SCREW
(SUFFIX LETTER M) 4194C SERIES

W6392 / IL
FRONT VIEW, 4194B SERIES

SCREW 1

SCREW 2

SCREW 3

PROCESS REMOTE SET POINT


POINTER SPAN SPAN ADJUSTMENT
ADJUSTMENT (SUFFIX LETTER M)

SIDE VIEW OF
SET POINT/PROCESS
INDICATOR ASSEMBLY
59A9752-S SHT 1

SIDE VIEW OF
39A1126-B CONTROLLER SHOWING
A6731 / IL
FLAPPER LEVELING SCREWS

Figure 4-3. 4194B and C Series Controller Calibration Adjustment Locations

4-6
Instruction Manual
Form 5196
May 2006 4194A, B, and C Series
the remote set point zero adjustment screw until the Provide a means of measuring the controller output
set point indicator aligns with the process scale pressure by connecting the controller output to a
lower limit. Tighten the zero adjustment locking pressure gauge (open-loop conditions must exist).
screw. Do not apply supply pressure at this time.

5. Apply remote set point pressure equal to the


upper range limit. Note
6. The set point indicator should indicate the 4194B and C Series controllers with
process scale upper limit. If not, adjust the remote anti-reset windup (suffix letter F) are
set point span adjustment screw to correct one-half supplied with two O-rings (key 52), a
the error as follows: clockwise to increase span for a valve cover (key 51) and two machine
low indication; counterclockwise to decrease span screws (key 53). Use these parts in the
for a high indication. next step.
7. Repeat steps 3 through 6 until the error is 1. For controllers with anti-reset windup (suffix letter
eliminated. F), record the direction of the arrow on the anti-reset
windup relief valve (key 55). Remove the relief valve
8. Adjust the remote set point pressure to the and install the two O-rings (key 52) and valve cover
mid-range value. (key 51) supplied with the controller. Secure the
valve cover with the two machine screws (key 53)
9. Make sure the set point indicator is within ±1
provided.
percent of the mid-scale mark, and if so, proceed to
step 12. If the set point indicator is not within 1 2. If necessary, remove the two machine screws
percent, but is within ±2 percent of the mid-scale (key 6) and lift off the proportional band indicator
mark, proceed with step 10. If the set point indicator cover (key 36).
is not within ±2 percent, proceed to the remote set 3. Provide regulated supply pressure to the
point zero and span adjustment procedure in the controller. Do not exceed the normal operating
Maintenance section. pressure in table 1-4.
10. Loosen the remote set point zero adjustment 4. For a controller with manual set point, move the
locking screw and adjust the remote set point zero set point indicator to the mid-scale mark of the
adjustment screw to correct for half the error at mid process scale span. For a controller with remote set
scale. Tighten the zero adjustment locking screw. point (suffix letter M), adjust the remote set point
11. Apply the remote set point pressure equal to the pressure until the set point indicator is at mid-scale
lower and upper range limits and make sure the set mark of the process scale.
point indicator is within ±1 percent. 5. Set the reset adjustment to 0.01 minutes per
repeat.
12. If necessary, perform the process indicator zero
and span calibration procedure in this section. 6. If the controller has rate (4194C Series), turn the
Otherwise, perform the flapper alignment procedure rate adjustment to OFF.
in this section. 7. Apply process differential pressure equal to the
mid-scale value of the process scale span. If
pressure is not available to pressure the input
Flapper Alignment element to the mid-scale value, an alternate method
is to disconnect link number 1 at the input element
Note and tape the process pointer at mid-scale mark on
the process scale. Note the hole where link number
Perform the process indicator zero 1 is connected to the input element, then disconnect
and span calibration procedure and, link 1. This method should only be used if pressure
for controllers with remote set point is not available to pressure the input element to the
(suffix letter M), the remote set point mid-scale value.
zero and span calibration procedure
before the flapper alignment. Note
Flapper leveling screw numbers and adjustments Because of the high controller gain,
are shown in figure 4-3. Key number locations are the controller output will not remain
shown in figure 6-1. stable in steps 8 through 12. The

4-7
Instruction Manual
Form 5196
4194A, B, and C Series May 2006

controller output gauge is adequate to


check the output pressure during this
procedure.
8. Set the proportional band between DIRECT and
REVERSE.
9. The controller output should be relatively stable
at any value within the output range. If not, adjust
flapper leveling screw 2 (the screw nearest the
nozzle) until the output is relatively stable.
10. Set the proportional band to 30 percent W4039-1 / IL
DIRECT. The controller output should be relatively
stable at any value within the output range. If not,
adjust flapper leveling screw 3 (the screw nearest
the nozzle) until the output is relatively stable.
11. Set the proportional band to 30 percent
REVERSE. The controller output should be relatively
stable within the output range. If not, adjust flapper
leveling screw 1 (the screw nearest the nozzle) until
the output is relatively stable.
12. Repeat steps 8 through 11 until the controller
output remains relatively stable without further
flapper leveling screw adjustment. W4038-1 / IL

Note
Figure 4-4. Alignment of the Process Pointer with the Set Point
Steps 13 through 19 check the flapper Indicator
alignment.
13. Set the proportional band to 30 percent
18. Apply process differential pressure to the input
DIRECT.
element or, if disconnected, move the process
14. Apply process differential pressure to the input pointer until it aligns with the left-hand edge of the
element or, if link 1 was disconnected, remove the set point indicator as shown in figure 4-4. The
tape from the process pointer and move the pointer controller output should be within 0.14 bar (2 psig) of
until it aligns with the right-hand edge of the set point the supply pressure.
indicator as shown in figure 4-4.
19. If the controller does not perform as indicated in
The controller output should be within 0.14 bar (2 steps 13 through 18, the flapper is not correctly
psig) of the supply pressure. aligned. This may occur because the output was not
sufficiently stabilized in steps 8 through 12. Repeat
15. Apply process differential pressure to the input steps 7 through 18.
element or, if disconnected, move the process
pointer until it aligns with the left-hand edge of the 20. Set the proportional band to 400 percent in the
set point indicator as shown in figure 4-4. desired controller action. Replace the proportional
band indicator cover (key 36) and tighten the two
The controller output pressure should go to 0 psig. screws (key 6). Reconnect link number 1, if
disconnected, to the same hole in the input element
16. Set the proportional band to 30 percent noted in step 7.
REVERSE.
21. For controllers with anti-reset windup (suffix
17. Apply process differential pressure to the input letter F), remove the two machine screws, valve
element or, if disconnected, move the process cover and two O-rings installed in step 1 of this
pointer until it aligns with the right-hand edge of the procedure. Install the anti-reset windup relief valve
set point indicator as shown in figure 4-4. The (key 55) with the arrow pointing in the direction
controller output should be 0 psig. recorded in step 1.

4-8
Instruction Manual
Form 5196
May 2006 4194A, B, and C Series
Anti-Reset Windup Differential Relief changing the controller set point. After each change
Valve Calibration in differential pressure or set point, the controller
output pressure should quickly change and then
Calibration for the differential relief valve to stabilize at the new value.
relieve on rising controller output pressure
10. Continue to change the controller output
1. Provide a means of measuring the controller pressure in 0.04 bar (0.5 psi) steps and check the
output pressure by connecting the controller output output pressure after each step to make sure it
to a pressure gauge (open-loop conditions must stabilizes. At some point, the controller output will
exist). Do not apply supply pressure at this time. start to ramp upward to supply pressure with no
further change to the controller input or set point.
2. Set the reset adjustment to 0.01 minutes per Record the controller output pressure where this
repeat (wide open) and the rate adjustment (4194C ramping action begins because this is the point at
Series only) to OFF. which the differential relief valve has relieved.
3. For a controller with manual set point, move the 11. To obtain the differential relief valve differential
set point indicator to the mid-scale mark on the setting, calculate the difference between the original
process scale. For a controller with remote set point, controller output pressure in step 7 and the
adjust the remote set point pressure until the set controller output pressure recorded in step 10.
point indicator is at the mid-scale mark of the
process scale. 12. If the differential pressure calculated in step 11
is incorrect for the application, adjust the differential
4. Set the proportional band to 100 percent in either pressure by turning the differential relief valve
the DIRECT or REVERSE action depending on the adjustment screw, shown in figure 4-3. Turn the
application requirements. screw clockwise to decrease the differential
5. Refer to figure 4-3 for the location of the pressure or counterclockwise to increase the
anti-reset windup differential relief valve. For the differential pressure. The differential relief valve is
differential relief valve to relieve on rising controller set at the factory to relieve at approximately 0.4 bar
output pressure, install the valve so the arrow on the (5 psi) differential pressure.
valve points down. To change the direction of the 13. Repeat steps 7 through 12 until the required
arrow, loosen the two mounting screws, pull the differential pressure is obtained.
valve out, and reinstall the valve with the arrow
pointing down. Tighten the two mounting screws. Calibration for the differential relief valve to
relieve on falling controller output pressure
6. Provide a regulated supply pressure to the
controller. Do not exceed the normal operating 1. Provide a means of measuring the controller
pressure in table 1-4. output pressure by connecting the controller output
to a pressure gauge (open-loop conditions must
exist). Do not apply supply pressure at this time.
Note
2. Set the reset adjustment to 0.01 minutes per
Because of the high controller gain repeat (wide open) and the rate adjustment (4194C
with the reset adjustment at 0.01 Series) to the OFF position.
minutes per repeat, the controller
output will not balance perfectly in the 3. For a controller with manual set point, move the
set point indicator to the mid-scale mark on the
following step. If the controller output
is stable for approximately 5 seconds, process scale. For a controller with remote set point,
it is adequately balanced. adjust the remote set point pressure until the set
point indicator is at the mid-scale mark on the
7. Increase the process differential pressure to the process scale.
controller until the controller output pressure
4. Set the proportional band to 100 percent in either
balances at 0.4 bar (6 psig) for a 0.2 to 1.0 bar (3 to
the DIRECT or REVERSE action depending on the
15 psig) output range or 0.8 bar (12 psig) for a 0.4 to
application requirements.
2.0 bar (6 to 30 psig) output range.
5. Refer to figure 4-3 for the location of the
8. Turn the reset adjustment to the CLOSED
anti-reset windup differential relief valve. For the
(4194B Series) or OFF (4194C Series) position.
differential relief valve to relieve on falling controller
9. Increase the controller output pressure in small output pressure, install the valve so the arrow on the
steps (approximately 0.04 bar (0.5 psig)) by valve points up. To change the direction of the
changing the process differential pressure or by arrow, loosen the two mounting screws, pull the

4-9
Instruction Manual
Form 5196
4194A, B, and C Series May 2006

valve out, and reinstall the valve with the arrow screw clockwise to decrease the differential
pointing up. Tighten the two mounting screws. pressure or counterclockwise to increase the
differential pressure. The differential relief valve is
6. Provide a regulated supply pressure to the
controller. Do not exceed the normal operating set at the factory to relieve at approximately 5 psi
(0.4 bar) differential pressure.
pressure in table 1-4.
13. Repeat steps 7 through 12 until the required
differential pressure is obtained.
Note
Because of the high controller gain
with the reset adjustment at 0.01 Principle of Operation for 4194B and C
minutes per repeat, the controller Series Controllers
output will not balance perfectly in the
following step. If the controller output
is stable for approximately 5 seconds, Overall Operation
it is adequately balanced. Refer to the schematic diagram in figure 4-5 for the
7. Increase the process differential pressure to the 4194B Series controllers, or to the schematic
controller until the controller output pressure diagram in figure 4-6 for the 4194C Series
balances at 0.8 bar (12 psig) for a 0.2 to 1.0 bar (3 controllers.
to 15 psig) output range or 1.6 bar (24 psig) for a 0.4
to 2.0 bar (6 to 30 psig) output range. The input element is connected to the process
pointer and to the flapper by connecting links. As the
8. Turn the reset adjustment to the CLOSED
process differential pressure increases (in a
(4194B Series) or OFF (4194C Series) position.
direct-acting controller), the flapper moves toward
9. Decrease the controller output pressure in small the nozzle, restricting flow through the nozzle and
steps (approximately 0.04 bar (0.5 psig)) by increasing nozzle pressure. When this occurs, relay
changing the process differential pressure or by action increases the output pressure (delivery) of the
changing the controller set point. After each change controller. Output pressure is fed back to the
in differential pressure or set point, the controller proportional bellows and to the reset bellows. The
output pressure should quickly change and then action of the proportional bellows quickly
stabilize at the new value. counteracts the flapper movement that resulted from
10. Continue to change the controller output the process differential pressure change and backs
pressure in 0.04 bar (0.5 psi) steps and check the the flapper away from the nozzle.
output pressure after each step to make sure it
stabilizes. At some point, the controller output will Pressure in the reset bellows opposes the action of
start to ramp downward to 0 psig with no further the proportional bellows and slowly moves the
change to the controller input or set point. Record flapper closer to the nozzle. The result of this
the controller output pressure where this ramping interaction is that, when the process differential
action begins because this is the point at which the pressure changes, proportional action temporarily
differential relief valve has relieved. reduces the gain of the controller for improved
stability. The process differential pressure then
11. To obtain the differential relief valve differential slowly returns to set point, as pressure in both
setting, calculate the difference between the original bellows equalizes via reset action.
controller output pressure in step 7 and the
controller output pressure recorded in step 10.
Moving the set point indicator changes the distance
12. If the differential pressure calculated in step 11 between the nozzle and flapper as does a change in
is incorrect for the application, adjust the differential process pressure, except that when the set point is
pressure by turning the differential relief valve changed, the nozzle moves with respect to the
adjustment screw, shown in figure 4-3. Turn the flapper.

4-10
Instruction Manual
Form 5196
May 2006 4194A, B, and C Series

SET POINT
INDICATOR RESET BELLOWS REVERSE ACTION
QUADRANT
PROPORTIONAL
BELLOWS PROPORTIONAL
BAND ADJUSTMENT
FEEDBACK
PROCESS POINTER LINK

REMOTE SET POINT


CONNECTED HERE
FEEDBACK
MOTION FLAPPER
INPUT ELEMENT
CONNECTED HERE PIVOT
DIRECT ACTION
QUADRANT
CONNECTING INPUT MOTION
LINK
FLAPPER DETAIL

BEAM OUTPUT PRESSURE


TO FINAL CONTROL
ELEMENT
FLAPPER
RESET
VALVE
NOZZLE
RELAY

SUPPLY
PRESSURE

TO
RESET
TO
PROPORTIONAL−PLUS−RESET CONTROL BELLOWS
NOZZLE

OUTPUT
TO
SUPPLY PRESSURE PROPORTIONAL
BELLOWS
OUTPUT PRESSURE

NOZZLE PRESSURE
RELAY

RESET PRESSURE
SUPPLY
RESET PRESSURE
VALVE

DIFFERENTIAL
RELIEF
46A9764−C VALVE
B1908−4 / IL
PROPORTIONAL−PLUS−RESET CONTROL WITH ANTI−RESET WINDUP

Figure 4-5. 4194B Series Controller Schematic

The proportional band adjustment positions the shown in the flapper detail of figure 4-5 or 4-6. With
nozzle on the flapper. Increasing (widening) the the controller in the reverse-acting mode, an
proportional band moves the nozzle to a position on increase in process differential pressure causes a
the flapper where less input and more feedback decrease in output pressure.
motion occurs, which decreases the gain of the
controller. Decreasing (narrowing) the proportional A 4194C Series controller also has a rate valve as
band moves the nozzle toward a position where shown in figures 4-6 and 4-7. This valve is an
more input and less feedback motion occurs, which adjustable restriction that momentarily increases the
increases the gain. The controller action is changed controller gain to accelerate the corrective action for
from direct to reverse by turning the proportional slow responding systems. A
band adjustment to position the nozzle on the proportional-plus-reset-plus-rate controller responds
flapper quadrant to a point where the direction of the to a change in process differential pressure as
flapper motion versus input motion is reversed as follows:

4-11
Instruction Manual
Form 5196
4194A, B, and C Series May 2006

SET POINT
INDICATOR RESET BELLOWS REVERSE ACTION
QUADRANT
PROPORTIONAL
BELLOWS PROPORTIONAL
BAND ADJUSTMENT
FEEDBACK
PROCESS POINTER LINK
REMOTE SET POINT
CONNECTED HERE
FEEDBACK
INPUT ELEMENT MOTION FLAPPER
CONNECTED HERE PIVOT
DIRECT ACTION
QUADRANT
CONNECTING INPUT MOTION
LINK
FLAPPER DETAIL

BEAM
OUTPUT PRESSURE
TO FINAL CONTROL
ELEMENT
FLAPPER

NOZZLE
RELAY

SUPPLY
PRESSURE
RATE VALVE

RESET VALVE

PROPORTIONAL-PLUS-RESET-PLUS-RATE CONTROL

TO
RESET TO
TO BELLOWS NOZZLE
PROPORTIONAL
BELLOWS

OUTPUT

SUPPLY PRESSURE

OUTPUT PRESSURE RELAY


DIFFERENTIAL
RELIEF VALVE
NOZZLE PRESSURE

RESET PRESSURE SUPPLY


PRESSURE

PROPORTIONAL PRESSURE RATE VALVE


RESET VALVE

PROPORTIONAL-PLUS-RESET-PLUS-RATE CONTROL
46A9764-B
C0593-3 / IL WITH ANTI-RESET WINDUP

Figure 4-6. 4194C Series Controller Schematic

D First, the rate action delays the proportional Anti-Reset Windup (suffix letter F)
action just long enough to allow the controller to Operation
respond to the change quickly with high gain, but not
long enough for the high gain to cause instability. Anti-reset windup is available on all 4194B and C
Series controllers and is designated by the letter F in
D Then, the low gain provided by the proportional the type number. The differential relief valve
action keeps the system stable. Finally, reset action operates when the difference between proportional
slowly increases the gain and returns the process bellows pressure and reset bellows pressure
differential pressure toward the set point. reaches a predetermined value. Anti-reset windup
reduces overshoot of the process differential
pressure that can result from large or prolonged
deviation from set point.

4-12
Instruction Manual
Form 5196
May 2006 4194A, B, and C Series
RELAY OUTPUT A control pressure is applied to the capsular element
PRESSURE
within the remote set point assembly. The expansion
RESET RATE and contraction of the capsule moves the set point
VALVE VALVE indicator via connecting linkage. Increasing the
control pressure to the capsule increases the set
point setting and decreasing the control pressure
reduces the set point setting.

Auto/Manual Station (suffix letter E)


GAIN Operation
LIMITER
A controller with the auto/manual station (designated
by the suffix letter E in the type number) has piping
on the output side of the relay as shown in figure
4-8. Supply pressure to the relay is also applied to
the manual loader. The manual loader, functioning
as a regulator, applies pressure to one side of the
plastic tube and to the auto/manual switch. Output
pressure from the relay registers on the other side of
the plastic tube as well as in the auto/manual switch.

When the auto/manual switch is in the MANUAL


RESET
BELLOWS
PROPORTIONAL
BELLOWS position, the manual loader output is channeled
through the auto/manual switch and becomes the
19A5000−A
controller output. When the auto/manual switch is in
A3237−2 / IL
the AUTO position, the relay output is channeled
through the switch to become the controller output.

Figure 4-7. Reset-Rate Schematic Before the auto/manual switch is operated, the relay
output must equal the manual loader output to avoid
bumping the process. Adjusting the set point varies
the pressure on the left-hand side of the plastic tube.
Remote Set Point (suffix letter M) Adjusting the manual loader knob varies the
Operation pressure on the right-hand side. When the pressures
are equal, the metal ball is centered in the tube and
The capability to adjust the controller set point from is held in place by a small magnet. A pressure
a remote location is available with all 4194B and C imbalance forces the ball to one end of the tube
Series controllers. This option is designated by the where it forms a seal, blocking air flow through the
suffix letter M in the type number. tube.

4-13
Instruction Manual
Form 5196
4194A, B, and C Series May 2006

MANUAL LOADER
AUTOMATIC
POSITION

AUTO/MANUAL
SWITCH MANUAL
LOADER
KNOB

PLASTIC TUBE
OUTPUT PRESSURE
TO FINAL CONTROL METAL BALL
ELEMENT

MANUAL
RELAY POSITION

AUTO/MANUAL
SWITCH
SUPPLY
PRESSURE OUTPUT PRESSURE
TO FINAL CONTROL
RELAY OUTPUT PRESSURE ELEMENT
SUPPLY PRESSURE

MANUAL LOADER OUTPUT PRESSURE

48A5230-A
A2999-1 / IL

Figure 4-8. Auto/Manual Station Schematic (4194B and C Series)

4-14
Instruction Manual
Form 5196
May 2006 4194A, B, and C Series

Section 55-5- measures are not taken. Preventative


measures may include: Remote
Maintenance venting of the unit, re-evaluating the
hazardous area classification,
Controller parts are subject to normal wear and must ensuring adequate ventilation, and the
be inspected and replaced as necessary. The removal of any nearby ignition
frequency of inspection and parts replacement sources. For information on remote
depends upon the severity of the service conditions. venting of this controller, refer to
When inspection or repairs are required, page 2-4.
disassemble only those parts necessary to D Check with your process or
accomplish the job. safety engineer for any additional
measures that must be taken to
protect against process media.

Inspection and Maintenance Note


Unless otherwise noted, key numbers
refer to figures 6-1 through 6-7.
WARNING Figures 3-1 and 3-3 show adjustment
locations for 4194A Series controllers.
Figures 4-1 and 4-3 show adjustment
The following maintenance locations for 4194B and C Series
procedures require taking the controllers. For maintenance on the
controller out of service. To avoid indicator assembly, refer to figures
personal injury and property damage 6-2, 6-3, and 6-4.
caused by uncontrolled process
pressure, observe the following before Select the appropriate maintenance procedure, and
performing any maintenance perform the numbered steps. Shut off supply
procedures: pressure and process pressure before beginning
maintenance.
D Always wear protective clothing,
gloves, and eyewear. The maintenance procedures section describes part
replacement common to 4194A, B, and C Series
D Provide some temporary means controllers. After completing the maintenance
of control for the process before procedures, perform the appropriate calibration
taking the controller out of service. procedures. Unless otherwise noted, calibration
procedures for the 4194A Series controller are in
D Shut off the supply pressure to Section 3; calibration procedures for the 4194B and
the controller. C Series controller are in Section 4. If difficulty is
encountered performing the calibration procedures
D Disconnect any operating lines in Section 3 or 4, refer to the calibration procedures
providing supply air pressure, a in this section.
process input signal, or other
pressure source to the controller.

D Personal injury or property


Troubleshooting
damage may result from fire or As an aid to troubleshooting, table 5-1 lists some
explosion if natural gas is used as the common operating faults, their probable cause, and
supply medium and preventative suggests procedures for correcting the faults.

5-1
Instruction Manual
Form 5196
4194A, B, and C Series May 2006

Table 5-1. Troubleshooting Chart


Fault Possible Cause Check Correction
1. Process wanders or cycles about 1.1 Proportional band and reset 1.1 Refer to the Start-up section for 1.1 If stable control cannot be
set point settings controller settings. attained, and all other elements of
the loop are functionally correct,
examine other possible causes
related to the controller.
1.2 Supply pressure varying 1.2 Monitor the supply pressure 1.2 Correct as necessary. One
with an external gauge. Ensure that regulator per instrument is
it is set correctly and does not recommended.
fluctuate. Note the number of
instruments being supplied by the
regulator.
1.3 Process pointer rubbing on 1.3 Note if the pointer is bent. 1.3 Bend pointer to provide
cover or scale clearance.
1.4 Input element failure 1.4 Inspect the element for loose 1.4 Repair or replace parts as
screws and damaged flexures, necessary.
links or pivots. Using a soap
solution, check the sensing
element for leaks.
1.5 Linkage failure 1.5 Check for links bent or not 1.5 Replace or repair as necessary.
connected properly, flexures bent
or broken, pivots broken.
1.6 Relay malfunction 1.6 By changing the process 1.6 If the output moves fast in one
differential pressure and observing direction and sluggishly in the
the output, verify that the output other, replace the relay.
moves at about the same speed in
both directions.
1.7 Anti-Reset Windup differential 1.7 The minimum relief valve 1.7 If the anti-reset windup
relief valve set too low (suffix letter setting is dependent on the loop differential relief valve appears to
F only) dynamics and the controller be set too low, perform the
settings if, under normal load anti-reset windup calibration
changes the relief valve opens, procedures in Section 4.
instability can occur. Check by
observing the controller reaction to
a set point or load change under
closed loop conditions.
2. Controlling off set point as 2.1 Supply pressure not set 2.1 Check with an external source. 2.1 Reset the supply pressure if
reflected by process and set point correctly necessary. If the condition occurs
indicators. again, rebuild or replace the
regulator.
Note: Some offset is inherent with 2.2 Linkage not connected 2.2 Inspect for loose screws and 2.2 Repair or replace parts as
proportional only controllers (4194A correctly. damaged flexures, links or pivots. necessary.
Series). The amount of offset is a
function of the proportional band
setting.
2.3 Leak in input element/tubing 2.3 Using soap solution, check the 2.3 Repair or replace parts as
assembly. input element and tubing for leaks. necessary.
2.4 Indicators out of calibration. 2.4 Refer to the process indicator 2.4 Adjust as necessary.
and remote set point (if applicable)
zero and span calibration
procedures in Section 3 or 4.
2.5 Flapper not aligned. 2.5 Refer to the Flapper alignment 2.5 Align the flapper as necessary.
procedures in Section 3 or 4.
2.6 Leak in feedback system. 2.6 Open the reset valve to .01 2.6 Repair as necessary.
minutes/repeat. Adjust output
pressure to 1.4 bar (20 psig). Using
soap solution, check for leaks in
the proportional and reset bellows
and in the tubing that connects
these bellows.
−Continued−

5-2
Instruction Manual
Form 5196
May 2006 4194A, B, and C Series
Table 5-1. Troubleshooting Chart (Continued)
Fault Possible Cause Check Correction
2. Controlling off set point as 2.7 Reset valve leaks. 2.7 Adjust output to 1.0 bar (15 2.7 Replace the reset valve.
reflected by process and set point psig) for a 0.2 to 1.0 bar (3 to 15
indicators. psig) output or 2.0 bar (30 psig) for
a 0.4 to 2.0 bar (6 to 30 psig)
output. Close the reset valve. If the
controller output varies and no
leaks were found in the rest of the
feedback system (Step 2.6), the
reset valve is leaking.
2.8 Leak in the remote set point 2.8 Adjust remote set point 2.8 Repair or replace parts as
system (suffix letter M only). pressure to 1.0 bar (15 psig). Using necessary.
soap solution, check for leaks in
the remote set point element and
tubing assembly.
2.9 Input element over pressured. 2.9 Check for zero shift. 2.9 Replace input element and
adjust travel stops.
3. Controlling off set point but not 3.1 Out of calibration 3.1 Refer to the process indicator, 3.1 Adjust as necessary
reflected by process and set point remote set point (if applicable), and
indicators. flapper alignment procedures in
Section 3 or 4.
4. No reset action (4194B and 4.1 Reset valve is plugged 4.1 Turn the reset valve through its 4.1 If reset action returns, no
4194C Series) range several times to remove any further action is necessary. If not,
restrictions. replace the reset valve (4194B
Series) or the rate/reset valve
(4194C Series).
4.2 Reset pressure leak 4.2 Adjust the output to 1.0 bar (15 4.2 Replace the reset valve (4194B
psig) for a 0.2 to 1.0 bar (3 to 15 Series) or the rate/reset valve
psig) output or g2.0 bar (30 psi) for (4194C Series)
a 0.4 to 2.0 bar (6 to 30 psig)
output. Close the reset valve. If the
output varies and no leaks were
found in the rest of the feedback
system (see Step 2.6), the reset
valve is leaking.
4.3 Tubing leak 4.3 With reset valve positioned at 4.3 Repair or replace parts as
0.01 minutes/repeat, put 1.0 bar necessary.
(15 psig) to the output port. Using
soap solution, check for leaks in
the reset bellows and attached
tubing assembly.
5. Abnormal control point shift 5.1 Flapper is dirty or pitted 5.1 Inspect the flapper. 5.1 Clean, or replace flapper as
when proportional band is changed. necessary.
5.2 Flapper is out of alignment 5.2 Refer to flapper alignment 5.2 Align flapper as necessary.
procedures in Section 3 or 4.
6. Controller will not attain full 6.1 Output pressure gauge not 6.1 Measure the output with an 6.1 Replace the gauge if it is
output range. functioning external pressure gauge. defective.
6.2 Supply pressure not correct 6.2 Check with an external source. 6.2 Repair or replace the supply
pressure regulator, if necessary.
Replace the supply pressure gauge
if necessary.
6.3 Proportional band setting two 6.3 Adjust proportional band setting 6.3 Use a narrower proportional
wide (4194A Series only) to 10. Manually cap the nozzle. band setting (decrease the
Output should increase. proportional band setting).
6.4 Input element or linkage failure 6.4 Inspect the element for 6.4 Repair or replace parts as
alignment, loose screws and necessary.
damaged flexures, links or pivots.
Using soap solution, check the
sensing element for leaks.
−Continued−

5-3
Instruction Manual
Form 5196
4194A, B, and C Series May 2006

Table 5-1. Troubleshooting Chart (Continued)


Fault Possible Cause Check Correction
6. Controller will not attain full 6.5 Leak in nozzle pressure tubing 6.5 Using soap solution, check for 6.5 Replace faulty parts as
output range. leaks in the nozzle tubing necessary. Clean out the relay
assembly. primary orifice with the cleanout
wire attached to the relay to ensure
the orifice is not clogged.
6.6 Relay malfunction 6.6 Manually push the flapper away 6.6 If the output does not change
from the nozzle. The output as described, remove the relay.
pressure should be zero. Cap the Replace O-rings, if necessary.
nozzle. The output should increase Replace relay, if necessary.
rapidly to within 35 mbar (0.5 psig)
of the supply pressure.
7. Controller remains at full output 7.1 Supply pressure too high 7.1 Check with an external 7.1 Replace supply pressure
pressure gauge. regulator or gauge as necessary.
7.2 Output gauge not functioning 7.2 Vary supply pressure to see if 7.2 If output gauge does not
output gauge responds. respond, replace it.
7.3 Input element or linkage failure 7.3 Vary the process differential 7.3 Repair or replace parts as
pressure and observe the flapper necessary.
for movement. Inspect the input
element and linkage for damage.
7.4 Mechanical alignment 7.4 Move the set point and verify 7.4 Repair or replace parts as
that the nozzle is uncapped by the necessary.
flapper. If not, inspect linkages and
flexures for damage.
7.5 Relay failure or restriction in 7.5 Manually move flapper 1.6 mm 7.5 If the output pressure remains
nozzle passage (1/16-inch) from the nozzle. at the supply pressure, remove the
controller case and cover assembly
and test again with the relay nozzle
tubing nut (key 18) loose. If the
output is 0 psig, clean or replace
the nozzle assembly. If the output
remains at supply pressure, replace
the relay.
7.6 Flapper misaligned 7.6 Manually push the flapper away 7.6 Perform the flapper alignment
from the nozzle. Controller output procedures in Section 3 or 4.
should go to 0 psig.
8. Controller remains at zero output 8.1 Gauge not functioning 8.1 Verify that the supply pressure 8.1 Replace gauges as necessary
is at its correct value and that the
controller output is zero.
8.2 Input element or linkage failure 8.2 Vary the process differential 8.2 Repair or replace parts as
pressure and observe the flapper necessary
for movement. Inspect the input
element and linkage for damage.
8.3 Mechanical alignment 8.3 Move the set point and verify 8.3 Repair or replace parts as
that the nozzle is capped by the necessary
flapper. If not, inspect linkages and
flexures for damage.
8.4 Relay malfunction 8.4 Check for air at the nozzle. Cap 8.4 Clean out the relay primary
the nozzle and note that the orifice with the cleanout wire
controller output increases to within attached to the relay to ensure the
0.5 psig of supply pressure. orifice is not clogged. If the problem
persists, replace the relay.
8.5 Nozzle pressure leak 8.5 Using a soap solution, check 8.5 Tighten the relay nozzle tubing
for nozzle tubing leaks with the nut (key 18), tighten manifold
nozzle capped by the flapper. screws (keys 34 and 131), or
Press the nozzle cap (key 23) replace nozzle assembly O-ring or
gently to ensure nozzle O-ring (key set point beam assembly as
24) is sealing. Ensure the relay appropriate.
nozzle tubing nut (key 18) and the
manifold screws (keys 34 and 131)
are tight.

5-4
Instruction Manual
Form 5196
May 2006 4194A, B, and C Series
Replacing Common Controller Parts

WARNING

To avoid personal injury or property


damage caused by the uncontrolled
release of pressure, be sure any
trapped process pressure is properly
vented from the controller. Vent any
supply pressure from the controller
before disassembly. W3440 / IL
DEFLECT LOWER PORTION OF THE SLOT

Replacing the Process Pressure Scale

WARNING

Refer to the Maintenance WARNING


on page 5-1.

CAUTION
W3492 / IL
AND LIFT THE SCALE UP AND OFF
To prevent the pointer or set point
indicator from rubbing on the cover or Figure 5-1. Changing the Scale
scale, and producing an inaccurate 7. Perform the appropriate process indicator zero
indication, take care not to bend the and span calibration and the flapper alignment
process pointer or the set point procedures in Section 3 or 4.
indicator while performing the
following procedure. Replacing the Relay
Refer to figure 5-1.
WARNING
1. Adjust the set point indicator (either manually or
with the remote set point pressure) to the mid-scale
Refer to the Maintenance WARNING
mark on the process scale.
on page 5-1.
2. Remove the four self-tapping screws (key 37). 1. Loosen the two captive screws that hold the relay
3. Slide the process scale (key 61) downward so (key 50) in place.
that the top of the slot touches the set point 2. Tip the relay slightly toward the side of the case
indicator. Deflect the lower portion of the slot to clear the output pressure gauge (key 46) and lift
outward and carefully slide the scale up and off, out the relay.
clearing the set point indicator as shown in
3. Make sure the replacement relay has three
figure 5-1.
O-rings (keys 13 and 15) installed as shown in
4. To install the replacement scale, deflect the lower figure 5-2. The fourth port is for exhaust and does
part of the slot slightly so that the scale slides not require an O-ring.
downward over the set point indicator and under the 4. Install the replacement relay, making sure the tab
process pointer. on the relay, shown in figure 5-2, aligns with the tab
5. Secure the scale with the four self-tapping on the frame.
screws (key 37). 5. Tighten the two screws that hold the relay in
6. If the controller has remote set point (suffix letter place.
M), perform the appropriate remote set point zero 6. Perform the appropriate Flapper Alignment
and span calibration procedure in Section 3 or 4. procedure in Section 3 or 4.

5-5
Instruction Manual
Form 5196
4194A, B, and C Series May 2006

5. Start the nine mounting screws, but do not


CLEAN-OUT
WIRE EXHAUST PORT
tighten.
(NO O-RING
USED) 6. Slide the controller assembly down to assure an
O-ring seal at the pressure connections along the
bottom of the case. Hold the controller assembly in
O-RINGS
place while tightening the nine mounting screws.
7. Remove the blow-out plug (key 72) from the
original case, and install it in the replacement case.
8. Perform the controller calibration procedures and,
if necessary, the appropriate remote set point
calibration procedure in Section 3 or 4.
9. Mount the controller as described in the
Installation section.
10. Connect the external piping to the controller.
RELAY
TAB RELAY
MOUNTING
W5744 / IL SCREWS Replacing the Gauges

WARNING
Figure 5-2. Relay Construction

Refer to the Maintenance WARNING


Replacing the Case and Cover on page 5-1.

WARNING CAUTION

Refer to the Maintenance WARNING Before performing this procedure, be


on page 5-1. sure the replacement gauges are the
correct range so that they are not
damaged by overpressure.
CAUTION 1. Unscrew the output pressure gauge (key 46) or
the supply pressure gauge (key 47) from the frame
(key 3).
The case and cover are an integral
unit; attempting to separate them will 2. Before installing the replacement gauge, coat the
damage the hinge. If the cover needs threads on the gauge with a sealant such as
to be replaced, replace the case also. key 311.
1. Remove the external piping and fittings from the 3. Screw the replacement gauge into the frame.
controller. 4. Apply the correct supply pressure and check for
2. Remove the controller from its mounting to a leaks with the nozzle capped for full output pressure.
maintenance area.
3. Remove the nine screws (key 38) from the case Replacing the Pressure Control Block
and cover assembly (key 1) and lift out the controller
assembly. If the controller has remote set point
(suffix letter M), use a screwdriver or appropriate WARNING
tool to deflect the case slightly at the remote set
point connection to remove the controller assembly. Refer to the Maintenance WARNING
Inspect the O-rings around the external piping on page 5-1.
connections and replace as necessary.
1. After bleeding away pressure, remove the
4. Position the controller assembly in the process pressure or remote set point piping from the
replacement case and cover. controller.

5-6
Instruction Manual
Form 5196
May 2006 4194A, B, and C Series
2. At the pressure control block (key 57), unscrew 8. Mount the controller as described in the
the nut that secures the capsular element tubing so Installation section.
that the tubing can be removed from the pressure
control block. 9. Connect external piping to the controller.

3. Remove the two cap screws (key 58) that hold


the pressure control block to the frame, and lift out Replacing the Proportional Band
the pressure control block. Adjustment Knob, Nozzle Assembly,
4. Install the O-ring (key 7) on the replacement and Set Point Beam Assembly
pressure control block. Figure 5-3 shows the parts locations for the
5. Position the replacement pressure control block proportional band adjustment and set point beam.
Unless otherwise noted, refer to this figure while
on the frame and fasten with the two cap screws
performing the following procedures.
(key 58).

6. Insert the tubing from the capsular element into Disassembly


the pressure control block and tighten the nut
loosened in step 2. 1. Remove the controller assembly from the case
7. Apply pressure equal to the maximum value on by performing steps 1 through 3 of the case and
cover replacement procedures.
the process scale, and check for leaks.
2. Remove the two machine screws (key 6), and lift
8. Reconnect the piping, removed in step 1, to the off the proportional band indicator cover (key 36).
controller. See figure 6-1 for parts location.
3. Disconnect link 3 from the set point beam shoe,
Replacing the Supply Gauge, part of the set point beam assembly (key 23).
Proportional, Reset, and Reset Valve 4. Remove the set point beam bias spring (key 28).
Tubing Assemblies
5. Remove the screw and washer (keys 19 and 20)
1. Remove the controller assembly from the case that hold the adjustable set point pivot assembly
by performing steps 1 through 3 of the case and (key 17) to the frame, and remove the pivot
cover replacement procedures. assembly.
2. Unscrew the nuts at each end of the tubing 6. Unscrew the nut that secures the relay nozzle
assembly. Remove the tubing assembly. tubing assembly (key 18) to the frame manifold
(key 135).
3. Install the replacement tubing assembly.
7. While holding the proportional band adjustment
4. Set the reset adjustment to 0.01 (4194B and C knob, remove the screw and washer (keys 19
Series) and set the rate adjustment to OFF (4194C and 20) that hold the relay nozzle tubing assembly
Series). (key 18) to the frame.

5. Apply the correct supply pressure and check for 8. Remove the proportional band adjustment knob,
leaks with the nozzle capped for full output pressure. relay nozzle tubing assembly, and the set point
Then, remove the pressure. beam assembly from the controller.

6. Position the controller assembly in the case and 9. Remove the relay nozzle tubing assembly
start, but do not tighten the nine mounting screws. (key 18) from the set point beam assembly (key 23).
Slide the controller assembly down to assure an 10. Remove the E-ring (key 27) from the nozzle
O-ring seal at the pressure connections along the assembly (key 21).
bottom of the case. Hold the controller assembly in
place while tightening the nine mounting screws. 11. Remove the nozzle assembly (key 21) and
plastic washer (key 22) from the bottom of the set
7. Perform the controller calibration procedures and, point beam assembly (key 23).
if necessary, the appropriate remote set point
calibration procedure in Section 3 or 4. 12. Remove the retaining clip (key 26).

5-7
Instruction Manual
Form 5196
4194A, B, and C Series May 2006

RELAY
PLASTIC CAP NOZZLE TUBING
ASSEMBLY WASHER
WASHER (KEY 20)
(KEY 18)

SCREW
(KEY 19)
E-RING
(KEY 27)

RETAINING CLIP
(KEY 26) O-RING

PROPORTIONAL
BAND ADJUSTMENT
(KEY 25) ADJUSTABLE PLASTIC
SET POINT WASHER
PIVOT ASSEMBLY (KEY 22)
(KEY 17)
SET POINT SET POINT NOZZLE
BEAM ASSEMBLY BEAM SHOE ASSEMBLY
(KEY 23) (KEY 29) (KEY 21)
W4193 / IL

EXPLODED VIEW

FLAPPER

RETAINING
CLIP

E-RING

CAP

PROPORTIONAL
BAND
ADJUSTMENT
KNOB

SET POINT BEAM


BIAS SPRING
SHOE
ADJUSTMENT
SCREWS

SET POINT SET POINT RELAY NOZZLE


BEAM ASSEMBLY LINK 3
BEAM SHOE TUBING ASSEMBLY
W4194 / IL

ASSEMBLED VIEW (CONTROLLER REMOVED FROM CASE)

Figure 5-3. Proportional Band Adjustment and Set Point Beam Details

13. Remove the proportional band adjustment knob 15. Inspect the nozzle assembly O-ring (key 24)
(key 25) and plastic washer from the set point beam and replace it, if necessary.
assembly (key 23).
Assembly
14. Inspect the nozzle assembly (key 21), and
replace it if necessary. Inspect the nozzle orifice, 1. Apply a suitable lubricant, such as key 318, to
and clean it, if necessary. Also, inspect the plastic the set point beam assembly; then position a plastic
washers, and replace them if necessary. washer (key 22) and the proportional band

5-8
Instruction Manual
Form 5196
May 2006 4194A, B, and C Series
adjustment knob (key 25) on the set point beam
assembly (key 23) as shown in figure 5-3.
2. Position the retaining clip (key 26) on the three TAB

posts of the proportional band adjustment knob.


HOLE
3. Place the second plastic washer on the nozzle
assembly. Apply a suitable lubricant, such as key
317, to the nozzle assembly O-ring.
4. Insert the nozzle assembly (key 21) through the
set point beam assembly (key 23), the plastic
washer (key 22), the proportional band adjustment
knob (key 25) and the retaining clip (key 26) into the
cap. Align the nozzle with the tab on the proportional
band adjustment knob shown in figure 5-4; make
sure the proportional band adjustment knob engages
the flats on the nozzle assembly.
5. While holding the nozzle assembly (key 21)
against the set point beam assembly (key 23),
depress the retaining clip (key 26), and install the
E-ring (key 27) into the E-ring groove on the nozzle
assembly (key 21). Ensure that all three tabs of the
E-ring are engaged.
W3761 / IL

6. Inspect the O-ring on the relay nozzle tubing


assembly (key 18) and replace it, if necessary.
Apply a suitable lubricant to the O-ring.
7. Install the relay nozzle tubing assembly (key 18) Figure 5-4. Proportional Band Adjustment Knob Setting
into the set point beam assembly.
8. Set the proportional band adjustment between 13. Insert the screw, with washer (keys 19 and 20),
DIRECT and REVERSE. Do this by aligning the tab through the frame (key 3) and start it into the
on the proportional band adjustment knob with the adjustable set point pivot assembly (key 17), but do
hole in the set point beam assembly as shown in not tighten.
figure 5-4.
14. Squeeze the adjustable set point pivot assembly
9. Position the proportional band adjustment knob, against the set point beam assembly. Check to be
relay nozzle tubing assembly and the set point beam sure the nozzle is still centered on the flapper and
assembly on the frame. Screw the relay nozzle tighten the machine screw (key 19). If necessary,
tubing nut loosely into the frame manifold. loosen both machine screws (key 19) to allow
10. Insert the machine screw, with plain washer slightly moving the adjustable set point pivot
(keys 19 and 20), through the frame and start it into assembly, set point beam assembly and the relay
the relay nozzle tubing assembly (key 18), but do nozzle tubing assembly as a unit to center the
not tighten. nozzle on the flapper. After centering the nozzle,
tighten the two machine screws.
11. Center the nozzle on the flapper as shown in
figure 5-5 while squeezing the set point beam 15. Turn the proportional band adjustment knob to 5
assembly firmly against the relay nozzle tubing percent DIRECT. Refer to figure 5-6 to locate the
assembly. With the nozzle centered on the flapper, locking nut on the adjustable set point pivot
tighten the machine screw (key 19). Ensure that the assembly. Loosen the locking nut and back out the
nozzle is still centered on the flapper. set screw slightly so that the set point beam
assembly falls under its own weight when pivoted
12. Insert the pivot of the adjustable set point pivot upward. Also, maintain a minimum side play
assembly (key 17) into the hole in the set point between the adjustable set point pivot assembly and
beam assembly (key 23). the nozzle tubing assembly. Tighten the locking nut.

5-9
Instruction Manual
Form 5196
4194A, B, and C Series May 2006

LOCKING ADJUSTABLE SET POINT


NUT PIVOT ASSEMBLY

SCREW AND WASHER SCREW AND WASHER


(KEYS 19 AND 20) 2 (KEYS 19 AND 20) 1
NOTES:
1 SCREW INSERTED INTO THE ADJUSTABLE SET POINT PIVOT ASSEMBLY.
2 SCREW INSERTED INTO THE RELAY NOZZLE TUBING ASSEMBLY.
W4195 / IL

Figure 5-6. Adjustable Set Point Pivot Assembly


Locking Nut Location

FLAPPER NOZZLE 20. Apply the correct supply pressure (refer to


W3449 / IL table 1-4) to the controller and provide an accurate
means of measuring the controller output pressure.
21. Perform the appropriate process indicator zero
and span calibration procedure and, if necessary,
Figure 5-5. Nozzle-Flapper Positioning the remote set point zero and span calibration
procedure in Section 3 or 4. When calibration is
complete, continue with step 22 below.
16. At the frame manifold (key 135), tighten the nut
that secures the tubing from the relay nozzle tubing Note
assembly (key 18). Apply full supply pressure with
the nozzle capped and check for leaks. Remove The following procedure (steps 22
supply pressure. through 28) matches the process
pointer motion to the set point
17. Install the set point beam bias spring (key 28) indicator motion so the controller will
into the frame bore and onto the spring seat on the control at set point at all positions on
set point beam assembly. the process scale.

18. Attach link 3 to the set point beam shoe as 22. Set the proportional band to 40 percent
shown in figure 5-3. REVERSE or DIRECT depending on the desired
controller action.
19. For controllers with reset or rate adjustment 23. Adjust the set point to the lower limit on the
(4194B or 4194C Series), turn the reset adjustment process scale.
to the CLOSED (4194B) or OFF (4194C) position.
24. Disconnect link 1 from the input element, noting
Set the rate adjustment to the OFF position.
the hole from which it is removed and tape the
process pointer to the lower limit on the process
The controller output must be 0 bar (0 psig). To be scale. The output pressure may be anywhere
sure the controller output is 0 bar (0 psig), remove between 0.2 to 1.0 bar (3 and 15 psig) for a 0.2 to
supply pressure, set the reset adjustment to 0.01 1.0 bar (3 to 15 psig) output signal range or between
minutes per repeat and wait 30 seconds; then, turn 0.4 to 2.0 bar (6 and 30 psig) for a 0.4 to 2.0 bar (6
the reset adjustment to the CLOSED (4194B) or to 30 psig) output signal range. If the output is not
OFF (4194C) position. within the specified range, adjust the flapper leveling

5-10
Instruction Manual
Form 5196
May 2006 4194A, B, and C Series
screw nearest the nozzle until the output is within 2. Remove the two screws (key 6), and lift off the
the range specified. Record the output pressure. proportional band indicator cover (key 36).
25. Adjust the set point to the upper limit on the 3. Disconnect link 3 from the set point beam shoe,
process scale. part of the set point beam assembly (key 23). Refer
26. Remove the tape and move the process pointer to figure 5-3 for the link location.
until the controller output equals the pressure
recorded in step 24. Note the process pressure 4. Remove the set point beam bias spring (key 28),
indication. refer to figure 5-3 for the spring location.
27. The process pressure indication should be 5. Remove the screw and washer (keys 19 and 20)
within ±2 percent of the upper limit on the process that hold the adjustable set point pivot assembly
scale. (key 17) to the frame.
If the process pressure indication in step 26 is 6. Remove the adjustable set point pivot assembly
greater than the upper limit of the process scale by 2 (key 17).
percent, loosen the shoe adjustment screws (key
30), shown in figure 5-3, and move the set point 7. Unscrew the nut that secures the relay nozzle
beam shoe (key 29) slightly away from the center of tubing assembly (key 18) to the frame manifold
the flapper assembly. (key 135). Refer to figure 5-3.

If the process pressure indication in step 26 is less 8. While holding the proportional band adjustment
than the upper limit of the process scale by 2 knob, remove the screw and washer (keys 19
percent, loosen the shoe adjustment screws (key and 20) that hold the relay nozzle tubing assembly
30), shown in figure 5-3, and move the set point (key 18) to the frame.
beam shoe (key 29) slightly toward the center of the
flapper assembly. 9. Remove the proportional band adjustment knob,
relay nozzle tubing assembly, and the set point
28. Repeat steps 23 through 27 until the error is beam assembly from the controller.
less than 2 percent of the process scale range at the
upper limit of the process scale. 10. Disconnect link 2 from the flapper assembly
29. Remove the tape from the process pointer and (key 11). Refer to figure 5-7 for the link location.
reconnect link 1 to the input element. Be sure to
reconnect link 1 in the same hole noted in step 24. 11. Disconnect link 4 from the bellows bracket
(key 31). Refer to figure 5-7 for the link location.
30. Position the controller assembly in the case and
start, but do not tighten the nine mounting screws. 12. Remove the two cap screws (key 12) from the
Slide the controller assembly down to assure an flexure pivot assembly (key 9). See figure 5-8 for
O-ring seal at the pressure connections along the screw location.
bottom of the case. Hold the controller assembly in
place while tightening the nine mounting screws. 13. Remove the flapper assembly and link 4 as
shown in figure 5-9.
31. Perform the controller calibration procedures
and, if necessary, the appropriate remote set point
14. Remove the four machine screws (key 10),
calibration procedure in Section 3 or 4.
shown in figure 5-9, that hold the flexure pivot
32. Mount the controller as described in the assembly to the frame.
Installation section.
15. Remove the flexure pivot assembly (key 9).
33. Connect external piping to the controller.
16. Install the replacement flexure pivot assembly
with the four screws (key 10). Do not tighten the
Replacing the Flapper Assembly and screws.
Flapper Flexure Pivot Assembly
1. Remove the controller assembly from the case 17. With the controller in the upright position, move
by performing steps 1 through 3 of the case and the flexure pivot assembly down as far as possible,
cover replacement procedures. and tighten the four screws (key 10).

5-11
Instruction Manual
Form 5196
4194A, B, and C Series May 2006

PROPORTIONAL
BELLOWS

BELLOWS
BRACKET
(KEY 31)

ADJUSTABLE
SET POINT PIVOT
ASSEMBLY (KEY 17)

SCREW AND
WASHER
(KEYS 19 AND 20)

LINK 4

W4199 / IL
LINK 2

Figure 5-7. Bellows Assembly and Proportional Band Adjustment (Process Scale and Proportional Band Indicator Cover Removed)

FLAPPER LEVELING FLAPPER FLEXURE PIVOT


SCREW NUMBER 2 ASSEMBLY ASSEMBLY FLAPPER
FOUR SCREWS
(KEY 10) (KEY 9) ASSEMBLY
AND LINK 4

W4198 / IL

OBLONG HOLE FLEXURE PIVOT


IN FRAME ASSEMBLY SCREWS (KEY 12) Figure 5-9. Exploded View of Flexure Pivot Assembly
W4770 / IL

19. Position the flapper assembly (key 11) on the


flexure pivot assembly (key 9) and start the cap
Figure 5-8. Leveling Screw Alignment screws (key 12) that hold the flapper assembly to
the flexure pivot assembly. Do not tighten the
screws.
18. Place the flapper assembly (key 11) on the 20. Align flapper leveling screw number 2 with the
flexure pivot assembly (key 9) with link 4 through the centerline of the oblong hole in the frame as shown
hole in the frame. in figure 5-8. Tighten the cap screws (key 12).

5-12
Instruction Manual
Form 5196
May 2006 4194A, B, and C Series
LINK 4 LINK 4 ADJUSTMENT 26. Insert the machine screw, with plain washer
(keys 19 and 20), through the frame and start it into
the relay nozzle tubing assembly (key 18), but do
not tighten.
27. Center the nozzle on the flapper as shown in
figure 5-5 while squeezing the set point beam
assembly firmly against the relay nozzle tubing
assembly. With the nozzle centered on the flapper,
tighten the machine screw (key 19). Ensure that the
nozzle is still centered on the flapper.
28. Insert the pivot of the adjustable set point pivot
assembly (key 17) into the hole in the set point
beam assembly (key 23).
29. Insert the screw, with washer (keys 19 and 20),
through the frame (key 3) and start it into the
adjustable set point pivot assembly (key 17), but do
not tighten.
30. Squeeze the adjustable set point pivot assembly
against the set point beam assembly. Check to be
LINK 2 sure the nozzle is still centered on the flapper and
LINK 2 ADJUSTMENT
W3442-1 / IL
LINK 3
tighten the machine screw (key 19). If necessary,
loosen both machine screws (key 19) to allow
Figure 5-10. Link 2 and 4 Adjustment Locations slightly moving the adjustable set point pivot
assembly, set point beam assembly and the relay
nozzle tubing assembly as a unit to center the
Note
nozzle on the flapper. After centering the nozzle,
The following procedure (steps 21 tighten the two machine screws.
through 23) adjusts link 2 to ensure 31. Turn the proportional band adjustment knob to 5
that it will always be in tension to percent DIRECT. Refer to figure 5-6 to locate the
eliminate possible instability due to locking nut on the adjustable set point pivot
lost motion. assembly. Loosen the locking nut and back out the
set screw slightly so that the set point beam
21. Disconnect link 1 from the input element, noting assembly falls under its own weight when pivoted
the hole location, and manually position the process upward. Also, maintain a minimum side play
pointer to the process scale upper limit. Tape the between the adjustable set point pivot assembly and
pointer in this position. the nozzle tubing assembly. Tighten the locking nut.
22. Adjust the length of link 2 by turning the 32. At the frame manifold (key 135), tighten the nut
adjustment screw, shown in figure 5-10, clockwise to that secures the tubing from the relay nozzle tubing
increase the length or counterclockwise to decrease assembly (key 18). Apply full supply pressure with
the length, so that the pin on the end of the link is the nozzle capped (to obtain maximum output
approximately one-half of its diameter short of pressure) and check for leaks. Remove supply
aligning with the hole in the flapper assembly, as pressure.
shown in figure 5-11.
33. Install the set point beam bias spring (key 28)
23. Connect link 2 to the flapper assembly. into the frame bore and onto the spring seat on the
set point beam assembly, as shown in figure 5-3.
24. Set the proportional band between DIRECT and
REVERSE. Do this by aligning the tab on the 34. Attach link 3 to the set point beam shoe as
proportional band adjustment knob with the hole in shown in figure 5-3.
the set point beam assembly as shown in figure 5-4.
Note
25. Position the proportional band adjustment knob,
nozzle assembly, set point beam assembly, and The following procedure (steps 35
nozzle tubing assembly on the frame, and screw the through 41) adjusts link 4 so it will
relay nozzle tubing assembly nut loosely onto the always be in compression to eliminate
frame manifold (key 135). possible instability due to lost motion.

5-13
Instruction Manual
Form 5196
4194A, B, and C Series May 2006

LEVELING
SCREW
NUMBER 1

CONNECTING TAB ON
FLAPPER ASSEMBLY

1/2 OF PIN
W4191 / IL DIAMETER
W3451 / IL

Figure 5-11. Link 2 Adjustment

35. For controllers with reset and rate adjustments 42. Adjust the proportional band to 40 percent
(4194B or 4194C Series), remove the supply REVERSE or DIRECT depending on the desired
pressure; then, turn the reset adjustment to the controller action.
CLOSED (4194B) or OFF (4194C) position. 43. Adjust the set point to the process scale lower
limit.
The controller output must be 0 bar (0 psig). To be
sure the controller output is at 0 bar (0 psig), remove 44. Tape the process pointer at the process scale
supply pressure, set the reset adjustment to 0.01 lower limit. The output pressure may be anywhere
minutes per repeat and wait 30 seconds; then, turn between 0.2 to 1.0 bar (3 and 15 psig) for a 0.2 to
the reset adjustment to the CLOSED (4194B) or 1.0 bar (3 to 15 psig) output signal range or between
OFF (4194C) position. 0.4 to 2.0 bar (6 and 30 psig) for a 0.4 to 2.0 bar (6
to 30 psig) output signal range. If the output is not
36. Apply the correct supply pressure (refer to within the specified range, adjust the flapper leveling
table 1-4) to the controller and provide an accurate screw nearest the nozzle until the output is within
means of measuring the controller output pressure. the range specified. Record the output pressure.
37. Adjust the proportional band to 5 percent 45. Adjust the set point to the process scale upper
REVERSE and adjust the set point to the process limit.
scale upper limit. 46. Remove the tape and move the process pointer
38. With link 1 disconnected, tape the process until the controller output equals the pressure
pointer at the process scale lower limit. The output recorded in step 44. Note the process pressure
pressure should be within 0.14 bar (2 psig) indication.
of supply pressure. If not, adjust flapper leveling 47. The process pressure indication should be
screw 1 (the screw nearest the nozzle) until the within ±2 percent of the process scale upper limit.
output is within 0.14 bar (2 psig) of supply pressure.
If the process pressure indication in step 46 is
39. Loosen the two adjustment screws on link 4, greater than the process scale upper limit by 2
shown in figure 5-10, and connect the link to the percent, loosen the shoe adjustment screws
bellows bracket (key 31), allowing the link to find its (key 30), shown in figure 5-3, and move the set point
free length. beam shoe (key 29) slightly away from the center of
40. Tighten the two adjusting screws on link 4. the flapper assembly.

41. Lift link 4 out of the hole in the bellows bracket If the process pressure indication in step 46 is less
(key 31) and ensure it drops back into the hole than the process scale upper limit by 2 percent,
under its own weight. If not, repeat steps 39 and 40. loosen the shoe adjustment screws (key 30), shown

5-14
Instruction Manual
Form 5196
May 2006 4194A, B, and C Series
FOUR SCREWS (KEY 6) 1. Remove the controller assembly from the case
by performing steps 1 through 3 of the case and
cover replacement procedures.
RESET
BELLOWS 2. Remove the two screws (key 6), and lift off the
WASHER proportional band indicator cover (key 36).
(KEY 362) PROPORTIONAL
BELLOWS 3. Disconnect link 4 (key 65) from the bellows
TWO SCREWS
(KEY 35) bracket (key 31).
RESET
GAIN
4. Remove the two machine screws (key 35) and
washer (key 362) from the bellows assemblies.
BELLOWS
BRACKET
(KEY 31)
5. Remove the four machine screws (key 6) from
the bellows beam (key 49) and remove the bellows
bracket (key 31).
6. Remove the proportional tubing assembly (key
40) from the proportional bellows, or remove the
reset tubing assembly (key 43) from the reset
bellows, depending on which bellows are to be
replaced.
LINK 4
(KEY 65)

7. Remove the four machine screws (key 71) from


W4199 / IL
the bellows beam and remove the bellows beam
from the frame.
Figure 5-12. Bellows Assembly, Bellows Bracket,
and Bellows Beam Location
CAUTION
in figure 5-3, and move the set point beam shoe
(key 29) slightly toward the center of the flapper When removing and replacing the
assembly. proportional or reset bellows, keep in
mind that the bellows has left-hand
48. Repeat steps 43 through 47 until the error is threads. Overtightening could damage
less than 2 percent of the process scale span at the the threads.
process scale upper limit.
49. Remove the tape from the process pointer and Note
reconnect link 1 to the input element. Be sure to
reconnect the link to the same hole noted in step 21. Both bellows need not be removed if
only one requires replacement.
50. Position the controller assembly in the case and
start, but do not tighten the nine mounting screws. 8. Unscrew the bellows assembly (key 48). If the
Slide the controller assembly down to assure an bellows assembly cannot be removed by hand,
O-ring seal at the pressure connections along the thread a machine screw (key 35) into the bellows
bottom of the case. Hold the controller assembly in until tight; then loosen the bellows assembly by
place while tightening the nine mounting screws. applying clockwise torque to the machine screw.
9. Before installing the replacement bellows, coat
51. Perform the controller calibration procedures
the threads with a suitable lubricant, such as key
and, if necessary, the appropriate remote set point 310. Screw in the replacement bellows until it is
calibration procedure in Section 3 or 4.
finger tight against the frame (key 3).
52. Mount the controller as described in the 10. Reinstall the bellows beam (key 49) and tighten
Installation section. the machine screws (key 71).
53. Connect external piping to the controller. 11. Position the bellows bracket (key 31) over the
bellows. Insert a machine screw (key 35) through
the bellows bracket (key 31) and into the
Replacing the Proportional or Reset proportional bellows. Do not tighten.
Bellows
12. Place the washer (key 362) on the second
Refer to figure 5-12, unless otherwise noted. machine screw (key 35) and start the screw through

5-15
Instruction Manual
Form 5196
4194A, B, and C Series May 2006

the bellows bracket (key 31) into the reset bellows. 24. Adjust the reset adjustment to 0.01 minutes per
Do not tighten. repeat. For a 4194C Series controller, set the rate
adjustment to OFF.
13. Compress the bellows and start the four
machine screws (key 6) through the bellows bracket 25. Increase the process differential pressure until
(key 31) into the bellows beam (key 49), but do not the output pressure stabilizes at 0.2 bar (3 psig) for
tighten. a 0.2 to 1.0 bar (3 to 15 psig) output or 0.4 bar (6
psig) for a 0.4 to 2.0 bar (6 to 30 psig) output.
14. Be sure that the bellows bracket is aligned such Record the process differential pressure reading.
that it does not rub on the frame at any point and
tighten the screws (key 6 and 35). Note
15. Install the proportional or reset tubing assembly When the reset valve is at 0.01, the
on the bellows base. controller is very sensitive to any
16. For a 4194B or C Series controller, set the reset process pressure change. Only small
adjustment for 0.01 minutes per repeat. For a 4194C process pressure changes may be
Series controller, set the rate adjustment to OFF. necessary.
26. Very slowly increase the process differential
17. Apply the correct supply pressure with the pressure until the output pressure stabilizes at 1.0
nozzle capped and check for leaks. Remove the bar (15 psig) for a 0.2 to 1.0 bar (3 to 15 psig) output
supply pressure. or 2.0 bar (30 psig) for a 0.4 to 2.0 bar (6 to 30 psig)
18. Reconnect link 4 (key 65) to the bellows output. Record the process differential pressure
bracket. Be sure that the link does not contact the reading.
frame. If it does, loosen the four screws (key 6) that 27. If the difference between the recorded process
attach the bellows bracket to the bellows beam and differential pressures in step 25 and step 26 is larger
reposition the bellows bracket to provide clearance. than ±1 percent of the process scale span, proceed
Be sure the bellows bracket does not rub on the with step 28. If the difference is less than ±1
frame; then, tighten the screws. percent, go to step 33.
19. Lift link 4 out of the hole in the bellows bracket 28. Loosen the proportional bellows screw (key 35).
(key 31) and ensure it drops back into the hole 29. If the reading recorded in step 26 is greater than
under its own weight. If not, perform steps 35 in step 25, adjust the reset gain screw (key 34)
through 41 of the Flapper Assembly and Flapper one-half turn in (clockwise). If the reading recorded
Flexure Pivot Assembly replacement procedures. in step 26 is less than in step 25, adjust the reset
gain screw (key 34) one-half turn out
20. If the controller is proportional-only (4194A
(counterclockwise).
series), go to step 34. If the controller has reset
(4194B or C Series), continue with step 21. 30. Tighten the proportional bellows screw (key 35).
31. Repeat steps 25 through 30 until the difference
is less than ±1 percent of the process scale span.
Note 32. If ±1 percent of the process scale span cannot
be achieved by adjusting the gain screw (key 34),
The following procedure (steps 21 loosen the machine screw (key 35) attaching the
through 32) adjusts the reset gain of reset bellows and slide it to the left if the reading in
the controller to minimize steady-state step 26 is greater than in step 25, or to the right if
offset. the reading in step 26 is less than in step 25.
21. Apply the correct supply pressure to the Tighten the screw and repeat steps 25 through 31.
controller and provide an accurate means of 33. Remove the supply pressure, the output
measuring controller output pressure. Also, provide measurement device, and the regulated differential
a means of applying regulated differential process process pressure source.
pressure. 34. Position the controller assembly in the case and
22. Adjust the proportional band to 100 percent start, but do not tighten the nine mounting screws.
DIRECT. Slide the controller assembly down to assure an
O-ring seal at the pressure connections along the
23. Adjust the set point to the mid-scale mark on bottom of the case. Hold the controller assembly in
the process scale. place while tightening the nine mounting screws.

5-16
Instruction Manual
Form 5196
May 2006 4194A, B, and C Series
35. Perform the controller calibration procedures Replacing the Rate/Reset Valve
and, if necessary, the appropriate remote set point Assembly (4194C Series)
calibration procedure in Section 3 or 4.
36. Mount the controller as described in the Note
Installation section.
Read this entire procedure before
37. Connect external piping to the controller. removing any parts. Refer to the
4194C Series portion of figure 6-1 for
key number locations.
Replacing the Reset Restriction Valve
(4194B Series) 1. Remove the controller assembly from the case
by performing steps 1 through 3 of the case and
Refer to the 4194B Series portion of figure 6-1 for cover replacement procedures.
key number locations.
2. Remove the two machine screws (key 71) on the
1. Remove the controller assembly from the case side of the rate/reset valve assembly (key 262).
by performing steps 1 through 3 of the case and 3. Gently pull the rate tubing assembly away from
cover replacement procedures. the rate/reset assembly and remove the gasket (key
5) from the side of the rate/reset assembly.
2. Remove the reset valve tubing assembly (key 42)
from the reset restriction valve (key 54). 4. Unscrew the nut holding the reset tubing
assembly (key 43) into the rate/reset valve
3. Remove the reset tubing assembly (key 43) from assembly.
the reset restriction valve.
5. Unscrew the nut holding the proportional tubing
4. For controllers with anti-reset windup (suffix letter assembly (key 40) into the rate/reset assembly.
F), remove the relief valve tubing assembly (key 44)
from the reset restriction valve. 6. For controllers with anti-reset windup (suffix letter
F), unscrew the nut holding the relief tubing
5. Remove the screw (key 162) that fastens the assembly into the rate/reset assembly.
reset restriction valve to the frame.
7. While holding the rate/reset valve assembly,
6. Install the replacement reset restriction valve and remove the machine screw (key 162) from the
secure it with the screw removed in step 5. frame.
7. Install the reset valve tubing assembly (key 42), 8. Remove the rate/reset valve assembly from the
the reset tubing assembly (key 43), and for frame.
controllers with anti-reset windup, the relief valve 9. Inspect, and if necessary, replace the gasket
tubing assembly (key 44). Tighten all connections. (key 5).
8. Set the reset adjustment to 0.01 minutes per 10. To install the replacement rate/reset valve
repeat. assembly, position the assembly on the frame
(key 3) and secure it with the mounting screw
9. Apply the proper supply pressure to the
(key 162).
controller, cap the nozzle and check for leaks.
Remove the supply pressure. 11. Position the gasket (key 5) on the rate/reset
valve assembly. Hold the gasket in place while
10. Position the controller assembly in the case and installing the rate tubing assembly (key 137) on the
start, but do not tighten the nine mounting screws. valve assembly using the two machine screws
Slide the controller assembly down to assure an (key 71).
O-ring seal at the pressure connections along the
bottom of the case. Hold the controller assembly in 12. Insert the reset tubing assembly (key 43) into
place while tightening the nine mounting screws. the rate/reset valve assembly and tighten the nut.
11. Perform the controller calibration procedures 13. Insert the proportional tubing assembly (key 40)
and, if necessary, the remote set point calibration into the rate/reset valve assembly and tighten the
procedure in Section 4. nut.

12. Mount the controller as described in the 14. For controllers with anti-reset windup (suffix
Installation section. letter F), insert the relief tubing assembly (key 44)
into the rate/reset valve assembly and tighten the
13. Connect external piping to the controller. nut.

5-17
Instruction Manual
Form 5196
4194A, B, and C Series May 2006

15. Set the reset to 0.01 minutes per repeat and the LINK 5 LINK 1 LINK 4 LINK 4 ADJUSTMENT
rate to OFF.

16. Apply the proper supply pressure to the


controller, cap the nozzle and check for leaks.

17. Position the controller assembly in the case and


start, but do not tighten the nine mounting screws.
Slide the controller assembly down to assure an
O-ring seal at the pressure connections along the
bottom of the case. Hold the controller assembly in
place while tightening the nine mounting screws. LINEARITY LINK 2 LINK 3
ADJUSTMENT
SCREW LINK 2 ADJUSTMENT LINK 3
18. Perform the controller calibration procedures W4769 / IL ADJUSTMENT
and, if necessary, the remote set point calibration Figure 5-13. Link Locations
procedure in Section 4.

19. Mount the controller as described in the 5. The relief valve differential pressure is factory-set
Installation section. at 0.3 bar (5 psig). Maximum differential pressure
is 0.5 bar (7 psig); minimum differential pressure
20. Connect external piping to the controller. is 0.14 bar (2 psig). If a different differential pressure
setting is desired, refer to the anti-reset windup
valve calibration procedure in Section 4.
Replacing the Anti-Reset Windup (suffix
letter F) Differential Relief Valve Replacing the Anti-Reset Windup (suffix
letter F) Relief Valve Tubing Assembly
Refer to the 4194B or 4194C Series suffix letter F
WARNING portion of figure 6-1 for key number locations.

1. Remove the controller assembly from the case


Refer to the Maintenance WARNING by performing steps 1 through 3 of the case and
on page 5-1. cover replacement procedures.

Refer to the 4194B or 4194C Series suffix letter F 2. Loosen the nuts at both ends of the relief valve
portion of figure 6-1 for key number locations. tubing (key 44), and remove the tubing.
3. Install the replacement relief valve tubing, and
1. Loosen the two mounting screws in the tighten the tubing nuts at both ends.
differential relief valve (key 55), and remove the
relief valve. 4. Apply the proper supply pressure to the
controller, cap the nozzle and check for leaks.
2. Inspect the O-rings on the replacement relief Remove the supply pressure.
valve. Apply a suitable lubricant to the O-rings. 5. Position the controller assembly in the case and
3. Install the replacement relief valve into the start, but do not tighten the nine mounting screws.
controller frame, keeping in mind that: Slide the controller assembly down to assure an
O-ring seal at the pressure connections along the
bottom of the case. Hold the controller assembly in
D When the arrow points up, the valve relieves place while tightening the nine mounting screws.
with decreasing output pressure.
6. Perform the controller calibration procedures and,
if necessary, the remote set point calibration
D When the arrow points down, the valve relieves procedure in Section 4.
with increasing output pressure.
7. Mount the controller as described in the
Installation section.
4. Tighten the two screws that hold the relief valve
to the frame. 8. Connect external piping to the controller.

5-18
Instruction Manual
Form 5196
May 2006 4194A, B, and C Series
Replacing the Links process pointer and pointer subassembly. Tighten
the zero adjustment locking screw.
6. Apply process differential pressure equal to the
WARNING mid-scale value of the process scale span. The
process pointer should indicate mid-scale ±3 percent
Refer to the Maintenance WARNING of the process scale span. If not, loosen the screw in
on page 5-1. link 1 or link 5, and move the pointer to the
mid-scale mark on the process scale. Tighten the
This section describes the separate replacement of screw.
five links in the controller. Figure 5-13 shows the
7. Perform the controller calibration procedures and,
location of each link. To clarify the location of each
if necessary, the appropriate remote set point
link, the links are numbered as follows:
calibration procedure in Section 3 or 4.
D Link 1 connects the short pivot clevis assembly Replacing Link 2
and the process pointer 1. Remove the two screws (key 6), and lift off the
proportional band indicator cover (key 36).
D Link 2 connects the process pointer and the
2. Disconnect link 2 from the process pointer and
flapper assembly (key 11)
from the flapper assembly (key 11). Remove the
link.
D Link 3 connects the set point indicator and the
set point beam assembly (key 23) 3. Install the replacement link with the screw head
nearest the process pointer as shown in figure 5-13.
D Link 4 (key 65) connects the flapper assembly Connect the link to the process pointer only.
and the bellows bracket (key 31) 4. The process pointer should be aligned with the
pointer subassembly as shown in figure 5-14. If not,
D Link 5 (key 88 in figure 6-3) connects the short loosen the zero adjustment locking screw and adjust
pivot clevis assembly (key 89) and the long pivot the process pointer zero adjustment to align the
clevis assembly (key 78). pointer with the process pointer subassembly.
Tighten the zero adjustment locking screw.
Replacing Link 1 5. Move the set point indicator, manually or with
remote set point pressure, to the process scale
1. Remove the two screws (key 6), and lift off the
lower limit and set the proportional band to 5 percent
proportional band indicator cover (key 36).
REVERSE. The nozzle should not be touching the
2. Note the hole position of link 1 and disconnect flapper. If it is, adjust flapper leveling screw 1 (the
the link from the short pivot clevis assembly and screw nearest the nozzle) until clearance is
from the process pointer. Remove the link. obtained.
3. Attach the replacement link in the same holes 6. Note the hole position and disconnect link 1 from
noted in step 2 to the process pointer and the short the short pivot clevis assembly. Manually position
pivot clevis assembly. If you do not know in which the process pointer to the process scale upper limit
hole in the process pointer the link was connected, and tape the process pointer in this position.
place it in the middle hole. If during the process 7. Adjust the length of link 2 (by turning the
indicator zero and span calibration, the pointer will adjusting screw clockwise to increase the length or
not travel the full scale, even after full span counterclockwise to decrease the length) so that the
adjustment, move the link to the bottom hole (the pin on the end of the link is approximately one-half
hole nearest the pointer pivot). If the process pointer of its diameter short of aligning with the hole in the
has too much travel, move the link to the top hole flapper assembly as shown in figure 5-11. This
(the hole furthest from the pointer pivot). adjustment provides the proper tension on the link to
4. Move the set point indicator, manually or with eliminate lost motion.
remote set point pressure, to the mid-scale mark on 8. Connect link 2 to the flapper assembly.
the process scale and set the proportional band 9. Remove the tape from the process pointer and
between DIRECT and REVERSE. reconnect link 1 to the hole in the short pivot clevis
5. The process pointer should be aligned with the assembly noted in step 6.
pointer subassembly as shown in figure 5-14. If not, 10. Perform the controller calibration procedures
loosen the zero adjustment locking screw and adjust and, if necessary, the appropriate remote set point
the process pointer zero adjustment to align the calibration procedure in Section 3 or 4.

5-19
Instruction Manual
Form 5196
4194A, B, and C Series May 2006

ALIGNED
ZERO ADJUSTMENT MISALIGNED FINE ZERO
LOCKING SCREW ADJUSTMENT
W3443-1 / IL
W3475-1 / IL

Figure 5-14. Process Pointer Alignment

Replacing Link 3 CLINCH


NUT
FLAPPER LEVELING
SCREW

1. Remove the two screws (key 6), and lift off the
proportional band indicator cover (key 36).

2. Disconnect link 3 from the set point indicator and


the set point beam assembly (key 23).

3. Adjust the replacement link to the same length as


the link removed.

4. Install the replacement link with the screw head


toward the set point beam assembly as shown in
figure 5-13.

5. Check that the set point beam bias spring


(key 28) is correctly located in the frame bore and
the spring seat on the set point beam assembly as W4191-1 / IL
shown in figure 5-3.
Figure 5-15. Flapper Leveling Screw and Clinch Nut
6. Move the set point indicator to the mid-scale
mark on the process scale.
8. Adjust the proportional band to 5 percent
7. Apply process differential pressure to position the DIRECT. Turn flapper leveling screw 3 (the screw
process pointer at the mid-scale mark on the nearest the nozzle) until the nozzle just touches the
process scale. flapper.

5-20
Instruction Manual
Form 5196
May 2006 4194A, B, and C Series
BELLOWS BRACKET
LINK 4 ADJUSTMENT
The controller output must be 0 bar (0 psig). To be
sure the controller output is at 0 bar (0 psig), remove
(KEY 31)
SCREW HEADS
supply pressure, set the reset adjustment to 0.01
minutes per repeat and wait 30 seconds; then, turn
the reset adjustment to the CLOSED (4194B) or
OFF (4194C) position.
5. Adjust the proportional band to 5 percent
REVERSE and move the set point indicator to the
process scale upper limit.
6. Disconnect link 1 from the pivot arm. Tape the
process pointer to the process scale lower limit (the
last mark on the left side of the scale).
7. Apply the correct supply pressure to the
controller. The output of the controller should be
W4195 / IL within 0.14 bar (2 psig) of supply pressure. If not,
adjust flapper leveling screw 1 (the screw nearest
Figure 5-16. Position of Link 4 Adjustment Screws
the nozzle) until the output is within 0.14 bar (2 psig)
of supply pressure.
9. Adjust the proportional band to 5 percent
REVERSE. Turn flapper leveling screw 1 (the screw 8. Loosen the two adjusting screws on link 4.
nearest the nozzle) until the nozzle just touches the Connect the free end of the link to the bellows
flapper. bracket and allow the link to find its free length.
10. Flapper leveling screws 1 and 3 should protrude 9. Tighten the two adjusting screws on the link.
the same distance from the clinch nuts. A clinch nut 10. Raise link 4 out of the hole in the bellows
is shown in figure 5-15. bracket (key 31) and ensure that it drops back into
the hole under its own weight. If not, repeat steps 8
11. If leveling screw 1 protrudes further than
and 9.
leveling screw 3, turn the link 3 adjusting screw
counterclockwise. If leveling screw 3 protrudes 11. For a controller with reset, adjust the reset
further than leveling screw 1, turn the link 3 adjusting adjusment to 0.01. The rate adjustment (4194C)
screw clockwise. should remain in the OFF position.
12. Repeat steps 8 through 11 until leveling screws 12. The controller output should be within 0.14 bar
1 and 3 protrude an equal distance from the clinch (2 psig) of the supply pressure. If not, adjust flapper
nuts. leveling screw 1 (the screw nearest the nozzle) until
the output is within 0.14 bar (2 psig) of supply
13. Perform the controller calibration procedures pressure.
and, if necessary, the appropriate remote set point
13. Remove the tape from the process pointer and
calibration procedure in Section 3 or 4.
connect link 1 to the pivot arm.
Replacing Link 4 14. Perform the controller calibration procedures
and, if necessary, the appropriate remote set point
1. Remove the two screws (key 6), and lift off the calibration procedure in Section 3 or 4.
proportional band indicator cover (key 36).
Replacing Link 5
2. Disconnect link 4 from the bellows bracket (key
31) and the flapper assembly (key 11). 1. Note the location of the connection holes and
disconnect both ends of link 5 (key 88) from the
3. Connect the replacement link to the flapper
lever arms of the two pivot assemblies. Refer to
assembly so that the two adjusting screws on the
figure 5-17 for parts locations.
link are nearest to the bellows bracket (key 31) and
so that the screw heads are facing the bottom of the 2. Loosen the adjustment screw on the replacement
controller as shown in figure 5-16. link, and adjust the length to match the original link.
Tighten the adjustment screw.
4. For controllers with reset (4194B Series) or reset
and rate adjustments (4194C Series), turn the reset 3. Attach the replacement link to the two lever arms
adjustment to the CLOSED (4194B) or OFF (4194C) in the same holes noted in step 1.
position. Turn the rate adjustment (4194C Series) to 4. Remove the two machine screws (key 6) and lift
the OFF position. off the proportional band indicator cover (key 36).

5-21
Instruction Manual
Form 5196
4194A, B, and C Series May 2006

GUIDE 1. Remove process pressure from the controller.


FLEXURE
2. Note the hole location and disconnect link 1
(key 90) from the process pointer.
DRIVE
3. Disconnect the process pressure connection
FLEXURE unions (key 93) from the pedestal assembly
(key 81). Use two 5/16-inch hex wrenches.
4. Remove the four mounting screws (key 127) that
LONG
PIVOT LINK 1 attach the capsular element assembly to the
indicator assembly (key 101).
LINK 5

LINK 2
CAUTION
SHORT
PIVOT
LINEARITY In the following step, do not lift out
ADJUSTMENT
38A1731-B
the capsular element assembly by
C0630 / IL SENSING ELEMENT holding the capsular element or
linkages. These parts may be
damaged.
Figure 5-17. Process Input Capsular Element Assembly Part
and Adjustment Locations 5. Lift out the capsular element assembly by holding
the tie bar (key 97), mounting plate (key 77), travel
5. Move the set point indicator (manually or with stop (key 83), or pedestal assembly (key 81).
remote set point pressure) to the mid-scale mark on 6. Position the replacement capsular element
the process scale. Set the proportional band assembly over the mounting screw holes. Install and
between DIRECT and REVERSE. tighten the mounting screws (key 127).
6. The process pointer should be aligned with the 7. Reconnect link 1 (key 90) to the process pointer
pointer subassembly as shown in figure 5-14. If not, in the same hole noted in step 2.
loosen the zero adjustment locking screw and adjust
the process pointer zero adjustment to align the 8. Reconnect the process pressure connection
process pointer and pointer subassembly. Tighten unions (key 93).
the zero adjustment locking screw. 9. Apply process differential pressure to the
controller, and check for leaks.
7. Apply the process differential pressure equal to
the mid-scale value of the process scale span. The 10. Perform the capsular element maintenance
process pointer should indicate mid-scale ±3 percent calibration procedures in this section. Perform the
of the scale span. If not, loosen the screw in link 1 or controller calibration procedures and, if necessary,
link 5, move the process pointer to the mid-scale the appropriate remote set point calibration
mark ±3 percent of the scale span. Tighten the procedure in Section 3 or 4.
screw.
8. Perform the controller calibration procedures and, Replacing the Long Pivot Assembly
if necessary, the appropriate remote set point
calibration procedure in Section 3 or 4.
WARNING
Replacing the Capsular Element Refer to the Maintenance WARNING
Assembly on page 5-1.

WARNING CAUTION

Refer to the Maintenance WARNING Avoid bending or kinking the drive


on page 5-1. flexure during the following
procedure. Bending or kinking the
Refer to figures 6-2 and 6-3 for key number drive flexure can result in product
locations. damage and impaired performance.

5-22
Instruction Manual
Form 5196
May 2006 4194A, B, and C Series

BEARING See figure 5-18. The adjustment arm of the long


1 END BUSHING
pivot clevis assembly is connected to a shaft that
turns on bushings at each end of the shaft. In the
ADJUSTMENT ARM next step, position the shaft so that both bushings
‘‘float’’ inside the bearings and do not rest against
the end of either bearing.
9. Apply 75 percent of the capsular element range
to the capsule. The drive flexure should be straight
and horizontal. Before tightening the drive flexure
cap screws (key 12), hold the pivot shaft in the
SHAFT
middle of the bushing end play. Be sure neither
bushing is resting against the inside end of either
bearing. Tighten the drive flexure cap screws to hold
1 END BUSHING the pivot shaft in position. Adjust the length of the
pivot adjustment arm as needed until the drive
flexure is horizontal. Take care not to kink or twist
BEARING
the flexure when tightening the screws.
10. Connect the left-hand end of link 5 (key 88) to
NOTE: the pivot adjustment arm in the hole position noted
1 BEFORE TIGHTENING THE DRIVE FLEXURE MOUNTING SCREWS, in step 3.
POSITION THE SHAFT SO THE END BUSHINGS “FLOAT” IN THE BEARINGS.
11. Replace the tie bar (key 97).
26A9784-E
A5682 / IL

Figure 5-18. Cutaway of Long Pivot Clevis Assembly


12. Perform the capsular element maintenance
calibration procedures in this section. Perform the
controller calibration procedures and, if necessary,
Refer to figure 6-3 for capsular element key number perform the appropriate remote set point calibration
locations. procedure in Section 3 or 4.
1. Remove process pressure from the controller.
Replacing the Short Pivot Assembly
2. Remove the tie bar (key 97) from the capsular
element assembly by removing the mounting screws
(key 103). WARNING
3. Note the hole position of link 5 (key 88) and
disconnect the link from the pivot adjustment arm on Refer to the Maintenance WARNING
the long pivot clevis assembly (key 78). on page 5-1.
4. Using an Allen wrench, remove the cap screw Refer to figure 6-3 for capsular element key number
and washer (keys 12 and 13) that attach the drive locations.
flexure (key 79) to the pivot adjustment arm of the
long pivot clevis assembly. Take care not to bend or 1. Remove the process pressure from the
kink the drive flexure. controller.
5. Remove the two screws (key 102) attaching the 2. Note the hole positions of links 1 and 5 (keys 88
long pivot clevis assembly to the mounting plate and 90) and disconnect the links from the short pivot
(key 77). clevis assembly (key 89). Also, note the screw
position of the linearity adjustment for later
6. Loosen the screw on the pivot adjustment arm of reference.
the replacement pivot clevis assembly, and adjust
the arm to the same length as the arm on the pivot 3. Remove the two machine screws (key 102)
assembly being replaced. attaching the short pivot clevis assembly (key 89) to
the mounting plate (key 77), and remove the pivot
7. Attach the replacement pivot clevis assembly to clevis assembly.
the mounting plate with the two mounting screws
4. Set the linearity adjustment screw on the
(key 102).
replacement pivot clevis assembly to approximately
8. Loosely connect the drive flexure to the pivot the same location as noted in step 2. The linearity
adjustment arm of the new pivot clevis assembly. adjustment screw location is shown figure 5-17.

5-23
Instruction Manual
Form 5196
4194A, B, and C Series May 2006

5. Position the replacement short pivot clevis bearings and do not rest against the
assembly on the mounting plate, and attach it with end of either bearing.
the two mounting screws.
5. Before tightening the drive flexure cap screws
6. Attach links 1 and 5 (keys 88 and 90) in the same (key 12), hold the pivot shaft in the middle of the
hole position as noted in step 2. bushing end play. Be sure neither bushing is resting
against the inside end of either bearing. Tighten the
7. Perform the capsular element maintenance
drive flexure cap screws to hold the pivot shaft in
calibration procedures in this section. Perform the
position. Take care not to kink or twist the flexure
controller calibration procedures and, if necessary,
when tightening the screws.
the appropriate remote set point calibration
procedure in Section 3 or 4. 6. Perform the capsular element maintenance
calibration procedures in this section. Perform the
controller calibration procedures and, if necessary,
Replacing the Process Drive Flexure the appropriate remote set point calibration
procedures in Section 3 or 4.
WARNING
Replacing the Process Tubing
Refer to the Maintenance WARNING
on page 5-1. WARNING

CAUTION Refer to the Maintenance WARNING


on page 5-1.
Avoid bending or kinking the drive 1. Remove process pressure from the controller.
flexure during the following 2. Using two open-end 5/16-inch wrenches,
procedure. Bending or kinking the disconnect the process tubing (keys 91 or 92) at the
drive flexure can result in product pedestal assembly (key 81) and at the bottom of the
damage and impaired performance. controller case. Remove the tubing.
Refer to figure 6-3 for the capsular element key 3. Install the replacement tubing, and tighten all
number locations. connections. Check for leaks.
1. Set the process pressure to 75 percent of the 4. Perform the controller calibration procedures and,
capsular element span. if necessary, the appropriate remote set point
calibration procedure in Section 3 or 4.
2. Remove the tie bar (key 97) from the capsular
element assembly by removing the mounting screws
(key 103). Capsular Element Maintenance
3. Using an Allen wrench, remove the cap screws Calibration
and washers (keys 12 and 13) to disconnect the
drive flexure (key 79) from the drive bracket Precalibration Procedures
assembly (key 84) and from the pivot adjustment
arm of the long pivot clevis assembly (key 78).
Remove the drive flexure. WARNING
4. Loosely connect the replacement drive flexure,
making sure it is straight and horizontal. Refer to the Maintenance WARNING
on page 5-1.
Note 1. Remove the two machine screws (key 6) and lift
off the proportional band cover (key 36).
See figure 5-18. The adjustment arm of
2. Set the proportional band between DIRECT and
the long pivot clevis assembly is
REVERSE.
connected to a shaft that turns on
bushings at each end of the shaft. In 3. Remove the two screws (key 103) and remove
the next step, position the shaft so the tie bar (key 97) from the capsular element
that both bushings ‘‘float’’ inside the assembly.

5-24
Instruction Manual
Form 5196
May 2006 4194A, B, and C Series
Aligning the Drive Bracket Assembly range and make sure the capsule stack is not
contacting the travel stop (key 83).

WARNING 3. Zero stop—Adjust process differential pressure


input to 0 percent of the capsular element range.
Refer to the Maintenance WARNING Slide the travel stop nut (key 86), along the
on page 5-1. diaphragm capsule extension (key 82) until it is
approximately 0.4 mm (1/64-inch) away from the
Refer to figures 5-17 and 6-3. travel stop. Tighten the set screw to lock the travel
1. With an Allen wrench, loosen the set screw in the stop nut in position.
hex nut (key 86) of the drive bracket assembly (key
84). Aligning the Linkage
2. Loosen the screw (key 98) that holds the guide
flexure to the tab on the mounting plate (key 77).
The guide flexure location is shown in figure 5-17. WARNING
3. Apply process differential pressure equal to 75
percent of the capsular element range. Refer to the Maintenance WARNING
on page 5-1.
4. Slide the drive bracket assembly (key 84) along
the diaphragm capsule extension (key 82) until the Refer to figure 5-17 and 6-3.
guide flexure is aligned with the center of the long
pivot clevis assembly (key 78). 1. Adjust the process differential pressure input to
75 percent of the capsular element range. The drive
5. Tighten the machine screw (key 98) and the set flexure (key 79) should be straight and horizontal. If
screw in the hex nut to fasten the drive bracket it is not, proceed as follows:
assembly in that position.
a. Loosen the screw on the pivot adjustment arm
Setting the Travel Stops on the long pivot clevis assembly (key 78) and
the two screws mounting the drive flexure.

WARNING b. Adjust the length of the pivot adjustment arm


so that the drive flexure is parallel to the
centerline of the capsules. Tighten the screw to
Refer to the Maintenance WARNING
set the length of the pivot adjustment arm in that
on page 5-1.
position.
1. Loosen the set screw in the travel stop nut
(key 86).
Note
Note See figure 5-18. The adjustment arm of
the long pivot clevis assembly is
Make sure the loose travel stop nut connected to a shaft that turns on
does not bind on the diaphragm bushings at each end of the shaft. In
capsule extension when pressurizing the next step, position the shaft so
the capsules. Damage to the capsules that both bushings ‘‘float’’ inside the
may result. bearings and do not rest against the
2. For Full span stop—Apply process differential end of either bearing.
pressure equal to 5 percent greater than the
capsular element range. c. Before retightening the drive flexure screws,
hold the long pivot clevis assembly shaft in the
Loosen the screws (key 139) that secure the travel middle of the bushing end play. Be sure neither
stop (key 83) to the mounting plate (key 77). Slide bushing is resting against the inside end of either
the travel stop until it is just touching the end of the bearing.
capsule stack. Tighten the travel stop mounting
screws to lock it into position. Decrease the input d. Tighten the drive flexure screws to hold the
pressure to 100 percent of the capsular element pivot clevis assembly shaft in position.

5-25
Instruction Manual
Form 5196
4194A, B, and C Series May 2006

POINTER ZERO
ADJUSTMENT

POINTER ZERO
ADJUSTMENT
LOCKING SCREW

PROCESS POINTER
SPAN ADJUSTMENT

ANTI-RESET WINDUP
RELIEF VALVE 2

ANTI-RESET WINDUP
VALVE ADJUSTING SCREW 2

RATE
ADJUSTMENT RESET
REMOTE SET POINT REMOTE SET POINT RESET ADJUSTMENT
1 W3599−1 / IL
ZERO ADJUSTMENT ZERO ADJUSTMENT ADJUSTMENT
LOCKING SCREW 4194C SERIES
NOTES:
1 AVAILABLE ON 4194B SERIES ONLY.
W6392 / IL FRONT VIEW, 4194B SERIES 2 AVAILABLE ON 4194B AND C SERIES SUFFIX LETTER F ONLY.

SCREW 1

SCREW 2

SCREW 3

PROCESS REMOTE SET POINT


POINTER SPAN SPAN ADJUSTMENT
ADJUSTMENT (SUFFIX LETTER M)

SIDE VIEW OF
SET POINT/PROCESS
INDICATOR ASSEMBLY
59A9752-S SHT 1

SIDE VIEW OF
39A1126-B CONTROLLER SHOWING
A6731 / IL
FLAPPER LEVELING SCREWS

Figure 5-19. 4194 Controller Calibration Adjustment Locations

5-26
Instruction Manual
Form 5196
May 2006 4194A, B, and C Series
2. Set the linearity adjustment screw on the short Note
pivot clevis assembly so the two arms of the short
pivot clevis assembly are parallel. The linearity Any adjustment of the process pointer
adjustment screw should be near the center of its span adjustment screw requires
slot. readjustment of the process pointer
zero adjustment screw.
3. Make certain that the process pointer and pointer
subassembly are aligned as shown in figure 5-14. If 1. Remove the two machine screws (key 6) and lift
not, loosen the zero adjustment locking screw and off the proportional band indicator cover (key 36).
adjust the process pointer zero adjustment screw to 2. Set the proportional band between DIRECT and
align the process pointer and pointer subassembly. REVERSE.
Tighten the zero adjustment locking screw.
3. Adjust the reset valve (4194B and C Series only)
4. Adjust the process differential pressure input to to 0.01 minutes per repeat.
50 percent of capsular element range. 4. Adjust the rate (4194C Series only) to OFF.
5. Loosen the screw on link 5 (key 88) and adjust 5. For a controller with manual set point, move the
the link length so that the pivot arms of the short set point indicator to the mid-scale mark on the
pivot clevis assembly (key 89) and the long pivot process scale. For a controller with remote set point,
clevis assembly (key 78) are parallel. Tighten the adjust the remote set point pressure until the set
screw. point indicator is at the mid-scale mark on the
6. Complete the maintenance calibration by process scale.
performing the zero and span adjustments in the 6. Apply a process differential pressure equal to the
following procedure. mid-scale value of the process scale span.
7. The process pointer should be aligned with the
Zero and Span Adjustment pointer subassembly as shown in figure 5-14. If not,
loosen the zero adjustment locking screw and adjust
the zero adjustment screw to align the process
WARNING pointer with the pointer subassembly. Tighten the
zero adjustment locking screw.

Refer to the Maintenance WARNING 8. The process pointer should indicate mid-scale ±3
on page 5-1. percent of the process scale span. If not, loosen the
screw on either link 1 or link 5 and adjust the length
so that the process pointer points to the mid-scale
Note mark on the process scale. Tighten the screw.
9. Apply process differential pressure equal to the
For routine zero and span calibration, process scale lower limit.
refer to the appropriate procedures in
Section 3 or 4. Use the following 10. The process pointer should indicate the process
maintenance zero and span scale lower limit. If not, loosen the zero adjustment
adjustment procedure only if difficulty locking screw and adjust the zero adjustment screw
is encountered with the routine until the process pointer indicates the lower limit.
procedure or if nonlinearity occurs. Tighten the zero adjustment locking screw.
11. Apply process differential pressure equal to the
Provide a means of applying process differential process scale upper limit.
pressure to the sensing element and a regulated
supply pressure adjusted to the normal operating 12. The pointer should indicate the process scale
pressure (see table 1-4). Plug the controller output upper limit. If not, proceed as follows:
or connect it to a gauge. Monitoring the controller a. If the pointer indicates less than the process
output is not necessary. However, the flapper should scale upper limit, rotate the pointer span
not contact the nozzle at any time while performing adjustment clockwise to increase the span.
this procedure. If it does, adjust flapper screw 2 (the Adjust the span adjustment screw to correct for
screw nearest the nozzle) to provide clearance. half of the error.

Refer to figure 5-19 for the adjustment locations. b. If the pointer indicates greater than the
Refer to figure 6-1 for the key number locations. process scale upper limit, rotate the pointer span

5-27
Instruction Manual
Form 5196
4194A, B, and C Series May 2006

adjustment counterclockwise to decrease the a. If the error at mid-scale is high (process


span. Adjust the span adjustment screw to pointer is to the right side of the mid-scale mark),
correct for half of the error. loosen the linearity adjustment screw and slide it
upward in the curved slot. Tighten the screw and
13. Repeat steps 9 through 12 until the zero and return to step 6.
span indications are within ±1 percent of the scale
limits with no further adjustment. If the span b. If the error at mid-scale is low (process
adjustment screw is adjusted to its limit and the pointer is to the left side of the mid-scale mark),
span is still too short or too long, proceed with step loosen the linearity adjustment screw and slide it
14. If proper span is achieved, proceed to step 16. downward in the curved slot. Tighten the screw
and return to step 6.
14. Within the process pointer subassembly, there
are three holes for the connection of link 1. Use 17. Adjust the process pointer to within ±1 percent
procedure (a.) or (b.) below to make the coarse of the mid-scale mark by loosening the zero
span adjustment with link 1. adjustment locking screw and adjusting the zero
adjustment screw. Tighten the zero adjustment
a. If the span is short (process pointer indication locking screw. This distributes the error over the
is less than the process scale upper limit), entire process scale and keeps all points within ±1
disconnect link 1 from the process pointer percent of the process scale span.
subassembly, move the link to the lowest hole
(the hole nearest the pointer pivot), and return to 18. Adjust the process differential pressure to the
step 9. If the link is already in the lowest hole, lower and upper limits of the scale span to make
proceed to step 15. sure the process pointer is still within ±1 percent of
the lower and upper scale limits.
b. If the span is long (process pointer indication
is greater than the process scale upper limit), 19. Perform the flapper alignment procedure and, if
disconnect link 1 from the process pointer necessary, the appropriate remote set point
subassembly, move the link to the highest hole calibration procedure in Section 3 or 4.
(hole furthermost from the pointer pivot), and
return to step 9. If the link is already in the
highest hole, proceed to step 15.
Remote Set Point (suffix letter M)
15. At either end of link 5, there are four holes in Maintenance
which the link may be connected. A coarse span
adjustment can be made by moving both ends of link Replacing the Remote Set Point
5 up or down. Assembly
a. If the span is short (process pointer indication
is less than the process scale upper limit), WARNING
disconnect both ends of link 5, move the link
down one set of holes, and return to step 6.
Refer to the Maintenance WARNING
on page 5-1.
b. If the span is long (process pointer indication
is greater than the process scale upper limit), Use the following procedures to replace the remote
disconnect both ends of link 5, move the link up set point assembly. Figure 5-20 shows the parts
one set of holes, and return to step 6. locations. Refer to figure 6-5 for key number
locations.
16. Apply process differential pressure equal to the
mid-scale value of the process scale span. The
process pointer should indicate mid-scale ±2 percent Note
of the scale span. If the process pointer error is ±2
Remove the supply pressure gauge
percent or less, proceed to step 17. If the process
before attempting to remove the
pointer error exceeds ±2 percent, the linearity can
remote set point assembly.
be improved with the linearity adjustment. See figure
5-17 for the linearity adjustment screw location. 1. Decrease the remote set point pressure to 0 psig.

5-28
Instruction Manual
Form 5196
May 2006 4194A, B, and C Series

GUIDE
FLEXURE MOUNTING
SCREW DRIVE FLEXURE
LINK A ADJUSTMENT
SCREW LOWER TRAVEL
STOP
PIVOT
ASSEMBLY A
UPPER TRAVEL
LINK B STOP

LINEARITY
ADJUSTMENT

PIVOT
ASSEMBLY B
MOUNTING
TIE BAR SCREW CAPSULES

REMOTE SET POINT ZERO ADJUSTMENT SCREW


ZERO ADJUSTMENT LOCKING SCREW
36A9751-C
B1668-4 / IL FRONT VIEW SIDE VIEW

Figure 5-20. Remote Set Point (suffix letter M) Parts and Adjustment Locations

2. Remove the supply pressure gauge. 7. Align the replacement assembly with the
mounting screw holes. Replace the mounting
3. Remove the pressure connection (key 93 at the
screws.
pedestal assembly (key 105). Use two 5/16 inch
wrenches. 8. Reconnect the remote set point pressure
connection union (key 93). Apply full remote set
4. Disconnect link B (key 126) from the connection point pressure and check for leaks.
hole on the set point indicator.
9. Connect link B (key 126) to the connecting hole
5. Remove the three mounting screws (keys 120 on the set point indicator.
and 140) that attach the remote set point assembly
to the process/set point indicator assembly. Figure 10. Replace the supply pressure gauge.
5-20 shows the mounting screw locations. 11. Perform the remote set point maintenance
calibration procedures. Perform the appropriate
process indicator zero and span calibration and
CAUTION flapper alignment procedure in Section 3 or 4.

In the following step, do not lift out Replacing Remote Set Point Assembly
the remote set point assembly by Parts
holding the capsular element or
linkages. These parts may be
damaged. WARNING
6. Lift out the remote set point assembly by holding
the tie bar (key 106), mounting plate (key 111), Refer to the Maintenance WARNING
travel stop (key 83), or pedestal assembly (key 105). on page 5-1.

5-29
Instruction Manual
Form 5196
4194A, B, and C Series May 2006

Figure 5-20 shows the parts and adjustment ensure the diaphragm assembly extension (key 134)
locations. Refer to figure 6-5 for key number is centered in the upper travel stop (key 83) hole.
locations.
10. Apply remote set point pressure equal to 50
percent of the remote set point input range.
Replacing Pivot Assembly A (Key 114)
Note

CAUTION See figure 5-18. The adjustment arm of


the remote set point pivot assembly A
turns on a bushing at each end of the
Avoid bending or kinking the drive shaft supporting the adjustment arm.
flexure during the following In the next step, position the shaft so
procedure. Bending or kinking the both bushings ‘‘float’’ inside the
drive flexure can result in product bearings and do not rest against the
damage and impaired performance. end of either bearing.
1. Decrease the remote set point pressure to 0 psig. 11. Connect the drive flexure (key 79) to the arm on
the replacement pivot assembly, making sure it
2. Remove two screws (key 103) and remove the stays straight and vertical. Adjust the length of the
tie bar (key 106). pivot arm, if necessary, until the flexure is vertical.
Before tightening the drive flexure screws, hold the
3. Note where link A is connected. Disconnect link pivot assembly shaft in the middle of the bushing
A (key 116) from the lever arm on pivot assembly A end play. Be sure neither bushing is resting against
(key 114). the inside end of either bearing. Tighten the drive
4. Disconnect the drive flexure (key 79) from the flexure screws to hold pivot assembly A in this
adjustment arm of pivot assembly A. Be careful not position. Do not bend or twist the flexure when
to bend or kink the drive flexure. tightening the screws.

5. Remove the screw (key 122), washer (key 123) 12. Decrease the remote set point pressure to 0
and nut (key 124) that attach the guide flexure psig.
(key 119) to the top of the pivot assembly. 13. Connect the end of link A (key 116) to the pivot
lever arm in the same holes noted in step 3.
6. Remove the pivot screw and spring washer
(keys 109 and 112) and the mounting screw (key 14. Replace the tie bar (key 106).
102) attaching the pivot assembly to the mounting
15. Perform the remote set point maintenance
plate (key 111). Lift out pivot assembly A. calibration procedures. Perform the appropriate
7. Loosen the adjustment screw (key 118) on the process indicator zero and span calibration and
adjustment arm of the replacement pivot assembly, flapper alignment procedures in Section 3 or 4.
and set the arm to the same length as the arm on
the pivot assembly being replaced. Tighten the Replacing Pivot Assembly B (Key 115)
screw. 1. Decrease the remote set point pressure to 0 psig.
8. To replace the pivot assembly, first put the spring 2. Note the holes where links A and B are
washer (key 112) on the screw (key 109). Then, connected. Disconnect links A and B (keys 116 and
insert the screw through the replacement pivot 126) from the arms of pivot assembly B (key 115).
assembly and into the mounting plate and tighten.
Install the mounting screw (key 102) and tighten. 3. Remove the two screws (key 102) that attach
pivot assembly B to the mounting plate (key 111).
9. Connect the guide flexure (key 119) to the top of Remove the pivot assembly.
the replacement pivot assembly with the screw (key
4. Loosen the linearity adjustment screw on the
122), washer (key 123), and nut (key 124) as it was
replacement pivot assembly, and set it in the same
before. The guide flexure should be straight and
position as the adjustment on the original pivot
horizontal as shown in figure 5-20. If not, loosen the
assembly. Tighten the screw.
screws (key 122) and retighten to eliminate any
bowing. Loosen the screws (key 139) and raise or 5. Set the replacement pivot assembly on the
lower the pedestal assembly (key 105) to get the link mounting plate, and attach it with the two machine
horizontal. Retighten the screws (key 139) and screws.

5-30
Instruction Manual
Form 5196
May 2006 4194A, B, and C Series
6. Attach links A and B (keys 116 and 126) to the 4. Install the replacement tubing, and reconnect the
arms of the replacement pivot assembly in the same two pressure connections.
holes noted in step 2.
5. Apply full remote set point pressure, and check
7. Perform the remote set point maintenance
for leaks.
calibration procedure. Perform the appropriate
process indicator zero and span calibration and
flapper alignment procedures in Section 3 or 4. Replacing Link A
Replacing the Drive Flexure

1. Using an Allen wrench, remove the cap screws This procedure describes link A (key 116)
(key 12) and washers (key 13) to disconnect the replacement in the input portion of the remote set
drive flexure (key 79) from the drive bracket (key point assembly. Figure 5-20 shows the link location.
121) and from the adjustment arm of pivot assembly
A. Remove the drive flexure. 1. Note the holes where link A is connected.
2. Set the remote set point pressure to 50 percent Disconnect link A (key 116) from the lever arms on
of the remote set point input range. pivot assembly A and pivot assembly B.

2. Loosen the screw in the replacement link A and


Note adjust the length to match the link being replaced.
Tighten the screw.
See figure 5-18. The adjustment arm of
the remote set point pivot assembly A 3. Refer to figure 5-20 for the correct link
turns on a bushing at each end of the orientation. Attach replacement link A to the two
shaft supporting the adjustment arm. lever arms in the same holes noted in step 1.
In the next step, position the shaft so
both bushings ‘‘float’’ inside the 4. Perform the remote set point maintenance
bearings and do not rest against the calibration procedure. Perform the appropriate
end of either bearing. process indicator zero and span calibration and
flapper alignment procedures in Section 3 or 4.
3. Connect the new drive flexure making sure it
stays straight and vertical. Adjust the length of the
pivot arm, if necessary, until the drive flexure is Replacing Link B
straight. Before tightening the drive flexure screws,
hold the pivot assembly A shaft in the middle of the
bushing end play. Be sure neither bushing is resting This procedure describes the link B (key 126)
against the inside end of either bearing. Tighten the replacement of the remote set point assembly.
drive flexure screws to hold the pivot shaft in this Figure 5-20 shows the link location.
position. Do not bend or twist the flexure when
tightening the screws.
1. Note the holes where link B is connected.
4. Decrease the remote set point pressure to 0 psig. Disconnect link B (key 126) from the pivot arm and
5. Perform the remote set point maintenance from the set point indicator.
calibration procedure. Perform the appropriate
process indicator zero and span calibration and 2. Loosen the screw in the replacement link B and
flapper alignment procedures in Section 3 or 4. adjust the length to match the link being replaced.
Tighten the screw.
Replacing the Remote Set Point Tubing
3. Refer to figure 5-20 for the correct orientation of
1. Decrease the remote set point pressure to 0 psig. link B. Attach replacement link B to the pivot arm
and to the set point indicator in the same position as
2. Using two 5/16-inch open-end wrenches,
noted in step 1.
disconnect the pressure connection union (key 93)
from the pedestal assembly (key 105) and the
4. Perform the remote set point maintenance
connection to the case exterior at the top of the
calibration procedure. Perform the appropriate
case.
process indicator zero and span calibration and
3. Remove the tubing (key 104). flapper alignment procedures in Section 3 or 4.

5-31
Instruction Manual
Form 5196
4194A, B, and C Series May 2006

Remote Set Point (suffix letter M) b. Set the length of the adjustment arm so that
Maintenance Calibration the drive flexure is parallel to the centerline of the
diaphragm capsule assembly (key 80).
Refer to figure 5-20 for parts and adjustment
locations. Refer to figure 6-5 for key number c. Tighten the screw (key 118) on the
locations. adjustment arm.

Note
Precalibration Procedures
See figure 5-18. The adjustment arm of
the remote set point pivot assembly A
WARNING turns on a bushing at each end of the
shaft supporting the adjustment arm.
In the next step, position the shaft so
Refer to the Maintenance WARNING
both bushings ‘‘float’’ inside the
on page 5-1.
bearings and do not rest against the
1. Remove the two screws (key 6) and lift off the end of either bearing.
proportional band indicator cover (key 36).
d. Hold the pivot assembly A shaft in the middle
2. Set the proportional band between DIRECT and of the bushing end play. Be sure neither bushing
REVERSE. is resting against the inside end of either bearing.
3. Remove the two screws (key 103) and remove
e. Tighten the screws that hold the drive flexure
the tie bar (key 106) from the remote set point
in place.
assembly.

Setting the Travel Stops


Aligning the Flexures
WARNING
WARNING
Refer to the Maintenance WARNING
Refer to the Maintenance WARNING on page 5-1.
on page 5-1. 1. Loosen the set screw (key 87) in the travel stop
1. Apply remote set point pressure input equal to 50 nut (key 86).
percent of the remote set point input range.
2. The guide flexure (key 119) should be straight CAUTION
and horizontal. If not, straighten the flexure by
loosening the machine screw (key 122) on the end Make sure the loose travel stop nut
of the flexure that is attached to the top of pivot does not bind on the diaphragm
assembly A (key 114) and allow the flexure to capsule extension (key 134) when
straighten itself. Tighten the machine screw. pressurizing the capsules (key 80).
3. If the flexure is not horizontal, loosen the two Damage to the capsules may result.
machine screws (key 139) and raise or lower the 2. Full span stop—Adjust the remote set point
pedestal assembly (key 105) until the guide flexure pressure to 2-1/2 percent of span greater than the
is horizontal. Retighten the machine screws remote set point input range upper limit.
(key 139) and ensure the diaphragm assembly
extension (key 134) is centered in the upper travel Loosen the two screws (keys 139 and 140) that
stop (key 83) hole. secure the travel stop (key 83) to the mounting plate
(key 111). Slide the travel stop until it is just touching
4. The drive flexure (key 79) should be straight. If the end of the capsule stack. Tighten the travel stop
not, proceed as follows: mounting screws to lock it into position.
a. Loosen the screw (key 118) on the adjustment 3. Zero stop—Adjust the remote set point pressure
arm of pivot assembly A (key 114) and loosen input to 2-1/2 percent of span less than the remote
the screws holding the drive flexure. set point input range lower limit.

5-32
Instruction Manual
Form 5196
May 2006 4194A, B, and C Series
Slide the travel stop nut (key 86), along the 2. The set point indicator should indicate the lower
diaphragm capsule extension (key 134) until it is just limit of the process scale span. If not, loosen the
touching the travel stop (key 83). Tighten the set adjustment screw on link A (key 116), and adjust the
screw (key 87) to lock the travel stop nut in position. length so that the set point indicator points to the
lower limit of the process scale. Tighten the screw.
Aligning the Linkage 3. Make fine zero adjustments by loosening the
zero adjustment locking screw (key 102) and turning
the zero adjustment screw (key 108). Tighten the
WARNING locking screw. Refer to figure 5-20 for the screw
locations.
Refer to the Maintenance WARNING 4. Apply a remote set point pressure equal to 100
on page 5-1. percent of the remote set point input range.
1. Adjust the remote set point pressure to 50 5. The set point indicator should indicate the upper
percent of the remote set point input range. limit of the process scale span.
6. To increase the span, proceed as follows:
2. Set the linearity adjustment screw in the center of
the slot on the lever arm of pivot clevis assembly B a. Turn the remote set point span adjustment
(key 115). See figure 5-20 for the linearity screw clockwise.
adjustment location.
3. Set the length of link A (key 116) so the lever b. To increase the span further than the
arms of pivot assembly A and pivot assembly B are adjustment screw allows, move both ends of link
parallel and link A is perpendicular to them. A (key 116) to the right.

4. Set the length of link B (key 126) so the set point c. Make fine adjustments with the remote set
indicator indicates mid-scale on the process scale point span adjustment screw.
span.
7. To decrease the span, proceed as follows:
5. Replace the tie bar (key 106) and install the two
screws (key 103). a. Turn the remote set point span adjustment
screw counterclockwise.
Remote Set Point Zero and Span b. To decrease the span further than the
Adjustment adjustment screw allows, move both ends of link
A (key 116) to the left.
WARNING c. Make fine adjustments with the remote set
point span adjustment screw.
Refer to the Maintenance WARNING 8. Repeat the adjustments until the upper and lower
on page 5-1. indications are aligned with the upper and lower
limits on the process scale.
Note 9. Adjust the remote set point pressure for 50
percent of the remote set point input range.
For routine remote set point zero and
span calibration, refer to the 10. The set point indicator should indicate mid-scale
appropriate procedures in Section 3 or ±2 percent of the process scale span. If the error is
4. Use the following maintenance within ±2 percent, proceed to step 11. If the error is
remote set point zero and span greater than ±2 percent of the scale span, proceed
adjustment procedure only if difficulty to the remote set point linearity adjustment
is encountered with the routine procedure.
procedure or if nonlinearity occurs. 11. Adjust the set point indicator to mid-scale ±1
percent of the process scale span by loosening the
Refer to figures 5-19 and 5-20 for adjustment zero adjustment locking screw and turning the zero
locations. adjustment screw. Tighten the locking screw.
1. Decrease the remote set point pressure to 0 12. Adjust the remote set point pressure to the
percent of remote set point input range. upper and lower limits of the remote set point input

5-33
Instruction Manual
Form 5196
4194A, B, and C Series May 2006

range and make sure the set point indicator is still Auto/Manual Station (suffix letter E)
within ±1 percent of the lower and upper limits of the Maintenance
process scale.
13. Perform the appropriate flapper alignment Replacing the Auto/Manual Station
procedure and, if necessary, the process indicator
Refer to figures 6-1 and 6-6 for key number
zero and span calibration procedure in Section 3
locations.
or 4.
Note
Remote Set Point Linearity Adjustment This procedure also permits
replacement of the switch manifold
O-rings (key 312), the auto/manual
WARNING tubing assembly (key 138), and the
frame gaskets (keys 4 and 5).
Refer to the Maintenance WARNING Disassembly
on page 5-1.
1. Remove the controller assembly from the case
Adjust the linearity by loosening and repositioning by performing steps 1 through 3 of the case and
the linearity adjustment screw in the curved slot on cover replacement procedures.
the lever arm of pivot assembly B (key 115). 2. Loosen the screw (key 316) that holds the
Adjusting the linearity affects the zero and span auto/manual station (key 273) to the controller
adjustment. frame.
3. Loosen the two screws (key 314 and 315) that
1. Adjust the remote set point pressure to 50 hold the auto/manual station to the auto/manual
percent of the remote set point input range. The set tubing assembly (key 138).
point indicator should indicate mid-scale ±1 percent
of the process scale span. If not, make fine 4. Remove the auto/manual station from the
adjustments by loosening the zero adjustment controller frame.
locking screw and turning the zero adjustment 5. Remove the switch manifold O-rings (key 312).
screw.
6. Carefully loosen the nut on the relay nozzle
2. Adjust the remote set point pressure to 0 percent tubing assembly (key 18) where it connects to the
of the remote set point input range and note the auto/manual tubing assembly (key 138). Loosen
indicator position relative to the process scale lower three screws (keys 34 and 131), and remove the
limit. tubing assembly and frame gaskets (keys 4 and 5).
3. Adjust the remote set point pressure to 100 7. Inspect the gaskets (keys 4 and 5) and O-rings
percent of the remote set point input range and note (key 312) for wear. Replace if necessary.
the indicator position relative to the process scale
upper limit. Assembly

4. If the greatest misalignment is positive (the set 1. Install the gaskets and the tubing assembly to the
point indicator is to the right of the process scale frame. Start, but do not tighten, the three screws
limits), loosen the linearity screw and move it (keys 34 and 131) and the nut on the relay nozzle
clockwise in the slot. If the misalignment is negative, tubing assembly (key 18).
move the linearity screw counterclockwise in the 2. Install the switch manifold O-rings (key 312), and
slot. secure the auto/manual station to the controller
frame with the screw (key 316) and to the tubing
5. If misalignment is greater than 1 percent of the assembly (key 138) with two screws (keys 314 and
process scale span at the lower and upper limits, 315). Do not tighten any screws.
with one positive and the other negative, perform the
remote set point zero and span adjustment
procedure to correct a span error. CAUTION
6. Repeat steps 1 through 4 until lower, middle, and
upper indications are within ±1 percent of the In the next step, take care to tighten
process scale markings. the two screws (keys 314 and 315)

5-34
Instruction Manual
Form 5196
May 2006 4194A, B, and C Series
evenly. Uneven tightening could
damage the tubing assembly. WARNING
3. Position the auto/manual station as far down on The switch body springs (key 295) are
the frame and toward the scale as possible. under preload. To avoid personal
Carefully tighten the two screws (keys 314 and 315) injury or parts loss, carefully separate
so that the auto/manual station contacts the three the switch body assembly from the
pads on the tubing assembly. loader assembly.
4. Carefully tighten the remaining screws and nuts. 6. Loosen the two screws (key 290), and separate
the switch body assembly (key 291) from the loader
5. Plug the controller output connection and apply assembly (key 282).
supply pressure to the controller. Check for leaks.
7. Remove the O-rings (keys 292, 293, and 294),
6. Position the controller assembly in the case and switch body springs (key 295), and balls (key 296).
start, but do not tighten the nine mounting screws. 8. Loosen two screws (key 308), and remove the
Slide the controller assembly down to assure an closing plate (key 307) and the closing plate gasket
O-ring seal at the pressure connections along the (key 306).
bottom of the case. Hold the controller assembly in
place while tightening the nine mounting screws. 9. Pull the clip (key 300) from its engagement with
the lever assembly shaft (key 297).
7. Perform the appropriate calibration procedure in 10. Pull the lever assembly from the switch body
Section 3 or 4. assembly (key 291) and rocker (key 299).
11. Remove the O-ring (key 298).
Replacing the Switch Body Assembly, 12. Inspect the O-rings and gaskets for damage or
Lever O-Ring, Switch Body O-Ring and wear; replace if necessary.
Tubing Assembly Assembly
Refer to figure 6-6 for key number location. 1. Insert the lever assembly (key 297) into the
switch body assembly (key 291) and hold the rocker
(key 299) with the flats on the lever assembly shaft.
Disassembly
2. Insert the clip (key 300) in the groove of the lever
1. Remove the auto/manual station from the assembly shaft to hold the lever assembly (key 297)
controller as described in steps 1 through 4 of the in the switch body assembly (key 291).
Replacing the Auto/Manual Station Procedure. 3. Position the closing plate gasket (key 306) and
the closing plate (key 307). Secure with two screws
2. Loosen the two screws (key 288), and remove
(key 308).
the lever cover plate (key 305).
Note
After assembly in step 3, be sure the
WARNING side of the closing plate marked OUT
is visible.
4. Place the balls (key 296), switch body springs
The lever spring (key 302) is under (key 295), and O-rings (keys 292, 293, and 294) in
preload. To avoid personal injury or the switch body assembly (key 291).
parts loss, carefully disassemble the
auto/manual station. Note
3. Using a 1.5 mm (1/16-inch) punch, push the In the following step, the ends of the
groove pin (key 303) out toward the surface of the springs must be in the counterbored
lever cover plate. spring seats before compression.
4. Remove the switch lever (key 304), lever spring 5. Compress the switch body springs with the
(key 302), and lever spring seat (key 301). loader assembly (key 282), and bolt the switch body
assembly (key 291) to the loader assembly using the
5. Remove the tubing assembly (key 309). two screws (key 290).

5-35
Instruction Manual
Form 5196
4194A, B, and C Series May 2006

6. Reconnect the tubing assembly (key 309). 2. Position the range spring cup (key 284), the
7. Locate the lever spring (key 302) and the spring range spring (key 283), and the diaphragm
seat (key 301) on the switch lever (key 304), and assembly (key 281) on the upper loader assembly
position these parts in the opening of the loader (key 282).
assembly (key 282). 3. Position the ball (key 279), the tube (key 278),
8. Push the switch lever down, using the lever and the ball seats (key 280) between the ears of the
spring seat (key 301) and the lever assembly (key loader assemblies (keys 282 and 274); position the
297) to preload the spring. Make sure the notch of diaphragm assembly (key 281) between the main
the switch lever engages the pin of the lever halves of the loader assemblies.
assembly.
Note
9. Drive in the groove pin (key 303) to hold the
switch lever. The tube (key 278) must be well seated
10. Replace the lever cover plate (key 305), and in the cups of the ball seats (key 280).
attach with two screws (key 288). 4. Bolt the loader assembly halves together using
11. Perform the Assembly portion of the Replacing the four screws (key 289).
the Auto/Manual Station procedure.
Note
Replacing the Loader Range Spring, Be sure that the supply and exhaust
Diaphragm Assembly, Ball Seat, Tubing, seats of the loader are correctly
aligned. Misalignment will impair
and Ball loader performance.
Refer to figure 6-6 for key number location. 5. Attach the tubing assembly (key 309).
Disassembly 6. Perform the Assembly portion of the replacing
the Auto/Manual Station procedure.
1. Remove the auto/manual station from the
controller as described in steps 1 through 4 of the Replacing the Loader Valve Plug and
Replacing the Auto/Manual Station procedure.
Valve Plug Spring
2. Remove the tubing assembly (key 309).
Refer to figure 6-6 for key number location.
1. Remove the controller assembly from the case
WARNING by performing steps 1 through 3 of the case and
cover replacement procedures.
To avoid personal injury caused by 2. Loosen the spring seat screw (key 275).
preload from the range spring (key
283), turn the loader knob (key 287) 3. Remove the valve plug spring (key 276) and the
counterclockwise (opposite to the valve plug (key 277).
arrow) to relieve pressure on the 4. Inspect the parts, and replace as necessary.
spring.
5. Install the valve plug spring and valve plug.
3. Loosen the four screws (key 289), and separate
the upper loader assembly (key 282) and the lower 6. Tighten the spring seat screw.
loader assembly (key 274). 7. Temporarily apply supply pressure and process
4. Remove the loader range spring (key 283), range differential pressure and check for leaks.
spring cup (key 284), and diaphragm assembly 8. Position the controller assembly in the case and
(key 281). start, but do not tighten the nine mounting screws.
5. Remove the tube (key 278), ball seats (key 280) Slide the controller assembly down to assure an
and ball (key 279). O-ring seal at the pressure connections along the
bottom of the case. Hold the controller assembly in
Assembly place while tightening the nine mounting screws.
9. Mount the controller as described in the
1. Turn the loader knob (key 287) counterclockwise
Installation section.
to back the spring adjustment screw (key 285) all
the way out to eliminate loading the range spring. 10. Connect external piping to the controller.

5-36
Instruction Manual
Form 5196
May 2006 4194A, B, and C Series
Description Part Number
Section 66-6-
4190 Series Relay Replacement Kit
Parts Contains Relay Assembly
(includes keys 13 and 15) and key 10
0.2 to 1.0 bar (3 to 15 psig) RRELAYX83C2
Parts Ordering 0.4 to 2.0 bar (6 to 30 psig) RRELAYX83D2

Whenever corresponding with your Emerson Type 4194BF Anti-Reset Windup Retrofit Kit,
Process Management sales office about this SST tubing, contains keys 44 and 55 R4190X00S22
equipment, always mention the controller serial
number. When ordering replacement parts, refer to
the 11-character part number of each required part
as found in the following parts list.
Parts List
Note
Abbreviations Used In The Parts List
Use only genuine Fisher replacement adj: adjustment
parts. Components that are not alt desgntn: alternative designation
ass’y: assembly
supplied by Emerson Process
conn(s): connection(s)
Management, should not, under any diff: differential (as in process differential
circumstances, be used in any Fisher pressure)
instrument. Use of components not fdback: feedback
supplied by Emerson Process fill hd: fillister head (as in fillister head cap screw)
Management will void your warranty, frame: controller frame (key 3)
ext: external
might adversely affect the
hd: head (as in machine screw head)
performance of the instrument, and ind: indicator
might jeopardize worker and int: internal
workplace safety. OD: outside diameter
pl: plated (as in plated steel)
prop: proportional
Note pt: point (as in set point)
qty: quantity
Neither Emerson, Emerson Process SST: stainless steel
Management, Fisher, nor any of their w/: with
affiliated entities assumes w/o: without
responsibility for the selection, use, Key Description Part Number
and maintenance of any product.
Responsibility for the selection, use,
and maintenance of any product Controller Common Parts (figure 6-1)
remains with the purchaser and
Note
end-user.
Figure 6-1 shows key numbers for the construction
Parts Kits of the Fisher Type 4194A, 4194B, and 4194C
controller. Figure 6-1 continues over several pages.
Description Part Number
Be sure to check all pages of Figure 6-1 to find the
key numbers.
4190 Series Auto/Manual Repair Kit
Contains keys 277, 278, 279, 281, 1 Case and cover ass’y
292, 293, 294, 298, 306, 312 R4190X0AM12 For use w/ or w/o int set pt and
4190 Series Auto/Manual Retrofit Kit, SST tubing w/o remote or ext set pt 46A5903X012
Contains keys 138, 273, 312, 313, For use w/remote set pt and w/o
314, 315, 316 R4190X00S12 int or ext set pt 46A5902X012
4190 Series Case Handle Kit 2 Nameplate, A91100 (aluminum) −−−
Contains lever and mounting hardware R4190X00H12 3 Frame, A03600 (aluminum) 56A7001X012
4190 Series Controller Repair Kit 4* Gasket, chloroprene
Contains keys 4, 5, 7, 8, 24, 52 R4190X00C12 for use between frame and frame
4190 Series Pointer and Bracket Repair Kit manifold (key 135) 18A0749X012
Contains pointer and bracket ass’y, 5* Gasket, chloroprene
three machine screws, three washers R4190X00P12 4194A and 4194B (1 req’d), 4194C (2 req’d) 18A0742X012

*Recommended spare parts 6-1


Instruction Manual
Form 5196
4194A, B, and C Series May 2006

Key Description Part Number Key 46/47. Pressure Gauge(1)


6 Machine screw, fill hd, 18-8 SST
GAUGE MATERIAL
2 req’d to mount the prop band ind cover RANGE
to the frame Brass SST
4 req’d to mount bellows bracket Dual Scale Gauge
(key 31) to bellows beam (key 49) 0 to 30psig/
2 req’d to attach process scale 11B8577X042 11B8583X032
0 to 2 kg/cm2
brackets (keys 376, 377) to frame 1P4373X0012
0 to 60 psig/
7* O-ring, nitrile 11B8577X052 −−−
0 to 4 kg/cm2
Used between frame and case at conns:
Triple Scale Gauge
low and high process diff pressure,
output and supply pressure, and 0 to 30psig/
remote set pt conn 0 to 200 kPa/ 11B8577X012 11B8583X012
4 req’d w/o remote set pt 0 to 2 bar
5 req’d w/remote set pt 1C376206992 0 to 60 psig/
8* O-ring, nitrile 0 to 400 kPa/ 11B8577X022 11B8583X022
Used between frame and case on 0 to 4 bar
mounting bosses extending from the frame 1. One type of pressure gauge is used for both output pressure and supply
pressure indication.
through the back of the case (3 req’d) 16A6903X012
9 Flexure pivot ass’y, sapphire/SST 29A4340X012
Key Description Part Number
10 Machine screw, fill hd, 18-8 SST
Used to attach the flexure pivot ass’y 39 Supply gauge tubing ass’y SST 16A6952X022
(key 9) to the frame (4 req’d) 18B0008X012 40 Proportional Tubing Ass’y (SST)
11* Flapper ass’y 29A9518X012 For 4194A & B Series 28A0766X022
12 Cap screw, hex socket, 18-8 SST For 4194C Series 27A3217X022
For flapper ass’y (key 11) (2 req’d) 10B0700X012
17 Adjustable set pt pivot ass’y, SST 19A1121X012 41 Plug, S30300 (303 SST),
18 Relay nozzle tubing ass’y, SST 18A0765X012 For all 4194A & B Series (1 req’d)
19 Machine screw, fill hd, 18-8 SST For 4194C, CM, CE and CME (2 req’d)
1 req’d to attach adjustable set pt pivot For 4194CF, CFM, CFE and CFME (1 req’d) 1P2796X0012
ass’y (key 17) to frame 42 Reset Valve Tubing Ass’y (4194B series only)
For 4194C Series SST 16A6949X022
3 req’d to attach relay nozzle tubing 43 Reset Tubing Ass’y, SST
ass’y (key 18) to frame 1C8990X0012 For 4194B Series 26A6950X022
20 Plain washer, 18-8 SST For 4194C Series 28A0764X022
Used w/key 19 (2 req’d) 1K261028992 44 Relief Tubing Ass’y, SST
21 Nozzle ass’y, SST 26A6904X012 For Types 4194BF, BFM,BFE,and BFME only 16A6951X022
22 Washer, plastic (2 req’d) 16A9767X012 For Types 4194CF, CFM, CFE,
23 Set pt beam ass’y, aluminum/SST 16A6939X012 and CFME only 18A0763X022
24* O-ring, nitrile
Note
1 req’d for noz tubing ass’y (key 18)
1 req’d for noz ass’y (key 21) 1E222606992
One type of pressure gauge is used for both output
25 Proportional band knob, polycarbonate 36A6911X012
pressure and supply pressure indication. See Key
26 Retaining clip, S30200 (302 SST) 16A6913X012
27 E-ring, SST 1V5929X0012 46/47 table for part numbers.
28 Set pt beam bias spring, pl steel 16A6909X012 46* Output gauge See Key 46/47 table
29 Set pt beam shoe, G10100 (pl steel) 16A6910X012 47* Supply gauge See Key 46/47 table
30 Cap screw, hex socket, 18-8 SST 48* Bellows ass’y (2 req’d)
Used w/key 29 (2 req’d) 19A1155X022 Brass 16A6953X012
31 Bellows bracket, A95052 (aluminum) 26A6932X012 S32100 (321 SST) / S30400 (304 SST) 16A6953X022
32 Bellows adj bracket, G10100 (pl steel) 16A6933X012 49 Bellows beam, A96061 (aluminum)
33 Bellows adj spring, pl steel 16A6934X012 0.2 to 1.0 bar (3 to 15 psig) 16A6957X012
34 Machine screw, fill hd, 18-8 SST 0.4 to 2.0 bar (6 to 30 psig) 16A6958X012
used to attach frame manifold (key 135) to 50 Relay Assembly (includes keys 13 and 15)
frame and for reset gain adjustment (2 req’d) 18B0009X012
35 Machine screw, hex hd, 18-8 SST The part numbers listed for key 50 are for the complete relay
Used to attach bellows bracket (key 31) assembly. The relay assembly is included in the Replay
to each bellows ass’y (key 48) (2 req’d) 16A6935X022 Replacement kit.
36 Proportional band indicator cover,
ABS w/polyester label 36A6936X012 Relay, 0.2 to 1.0 bar (3 to 15 psig) 32B0257X0C2
37 Self-tapping screw, 18-8 SST Relay, 0.4 to 2.0 bar (6 to 30 psig) 32B0257X0D2
4 req’d to attach process scale (key 61)
to process scale bracket (key 376) 16A6938X022 51 Relief valve cover plate, A03600 (aluminum) 2V597308012
38 Self-tapping screw, 18-8 SST 52* O-ring, nitrile
Used to attach frame inside case (9 req’d) 16A6959X022 Used w/key 51 (2 req’d) 1C853806992

6-2 *Recommended spare parts


Instruction Manual
Form 5196
May 2006 4194A, B, and C Series
Key Description Part Number Key 56. Process/Set Point Indicator Assembly
53 Machine screw, fill hd, 18-8 SST
Used w/key 51 (2 req’d) 1U8842X0012 Differential W/O Remote W/ Remote
54 Reset Restriction Valve (4194B Series only) 19A4361X032 Pressure Range Set Point Set Point
55 Differential Relief Valve 0−5 psid 36A6985X052 36A6985X132
For all 4194B and C Series w/suffix 0−10 psid 36A6985X062 36A6985X142
letter F, anti-reset windup 21A6447X0A2 0−20 psid 36A6985X072 36A6985X152
0−30 psid 36A6985X082 36A6985X162
56 Process and set pt indicator ass’y w/capsular Key Description Part Number
element ass’y for sensing of process diff pressure 62 Remote set pt ass’y (suffix letter M)
The part numbers listed for key 62 are for the complete remote
The part numbers in the Key 56 table are for the complete set pt (suffix letter M) ass’y. Individual assembly parts are
process and set pt indicator ass’y with capsular elements for listed in the Remote Set Point Assembly subsection of the
sensing process diff pressure. Individual indicator ass’y parts parts list. Key numbers for individual ass’y parts also appear in
are listed in three subsections of this parts list: the Process and figure 6-5.
Set Point Indicator Assembly (key 56) subsection, the Indicator
Assembly (key 101) subsection, and the Capsular Element Remote set pt ass’y (suffix letter M)
Ass’y (key 113) subsection. Key numbers for individual N09902 Nickel Alloy
indicator parts also appear in figures 6-2 and 6-4. 0.8 bar (12 psig) span 36A6988X032
1.7 bar (24 psig) span 36A6988X042
Process and set pt indicator ass’y w/capsular SST
element ass’y for sensing of process diff 0.8 bar (12 psig) span 36A6988X012
pressure plastic/aluminum/stainless steel see Key 56 table 1.7 bar (24 psig) span 36A6988X022

57 Pressure control block, CF8M (316 SST Casting) 64 Machine screw, fill hd,18-8 SST
For female process connections (2 req’d) 26A6962X012 4 req’d to attach process set pt and
For male process connections (2 req’d) 20B7911X012 indicator ass’y (key 56/101) to frame 1J8415X0012
For remote set point connection (female) 26A6962X012 65 Feedback link ass’y, aluminum/brass/SST 16A7036X012
71 Machine screw, fill hd, 18-8 SST
58 Cap screw, hex hd, SST For all 4194A and B Series (4 req’d)
2 req’d for use w/each pressure For all 4194C Series (6 req’d) 1P4743X0012
control block (key 57) 1A352538992 72 Blowout plug 2V766005312
59 Hex reducing nipple, 1/2-inch NPT male
(2 req’d) (Use only when specified) 120 Machine screw, fill hd, 18-8 SST
Steel 16A6992X012 2 required to mount remote set pt ass’y
SST 16A6992X022 (suffix letter M) to base plate of
60 Reducing adaptor, 1/2-inch NPT female indicator ass’y (key 56/101) 1J8415X0012
(2 req’d) (Use only when specified) 131 Machine screw, fill hd, S30400 (304 SST)
Steel 16A6993X012 2 req’d to attach rate/reset manifold
SST 16A6993X022 (key 136) to frame manifold (key 135) 1C101535042
135 Frame manifold, A03600 (aluminum)
61 Process scale, aluminum For all types except w/suffix letter E,
for indicator ass’y (key 101) auto/manual station 28A0756X012
0-5 psid 1R0003X0282 136 Rate/reset manifold A03600 (aluminum)
0-10 psid 1R0003X0292 For all types except 4194C Series 28A0747X012
0-15 psid 1R0003X1912 137 Rate Tubing Ass’y
0-20 psid 1R0003X0302 4194C Series only 28A0762X042
0-30 psid 1R0003X0312
0-40 psid 1R0003X1902 138 Auto/manual tubing ass’y Use w/suffix letter E,
0-50 psid 1R0003X1732 auto/manual station only
0-60 psid 1R0003X1742 SST/aluminum 38A2859X022
0-75 psid 1R0003X1642 140 Machine screw, fill hd, 18-8 SST
0-250 mbar differential 1R0003X1062 Required to mount remote set pt ass’y
0-0.6 bar differential 1R0003X1072 (suffix letter M) to indicator ass’y 16A7007X022
0-1.4 bar differential 1R0003X1082 162 Machine screw, hex hd, 18-8 SST
0-1.6 bar differential 1R0003X1092 (For 4194B and C Series only) 1B8480X0012
0-2 bar differential 1R0003X1552 262 Rate/reset valve ass’y (For 4194C Series)
0-50 in. w.c. differential 1R0003X1312 Brass bellows
0-5 psid 1R0003X0282 0.2 to 1.0 bar (3 to 15 psig) 39A6013X052
0-75 in. w.c. differential 1R0003X1922 0.4 to 2.0 bar (6 to 30 psig) 39A6013X072
0-100 in. w.c. differential 1R0003X1212 SST bellows
0-100 percent 1R0003X1042 0.2 to 1.0 bar (3 to 15 psig) 39A6013X062
0-10 square root 1R0003X1172 0.4 to 2.0 bar (6 to 30 psig) 39A6013X082
0-100 square root 1R0003X1292

6-3
Instruction Manual
Form 5196
4194A, B, and C Series May 2006

38A3819-B / DOC
SECTION B-B
SEE VIEW E

SECTION D-D
56A9752-S SHT 1 / DOC

j APPLY LUB/SEALANT VIEW C-C, 4194A SERIES CONTROLLERS WITH REMOTE SET POINT
NOTE: (SUFFIX LETTER M)
1 KEY 4 GASKET IS USED BETWEEN INTERNAL FRAME AND FRAME MANIFOLD.
2 KEY 5 GASKET IS USED BETWEEN FRAME MANIFOLD AND RATE/RESET MANIFOLD.

Figure 6-1. Controller Assembly Drawings

Key Description Part Number Key Description Part Number

273 Auto/manual station (suffix letter E) 48A2905X012 313 Auto/Manual scale, plastic
For all types w/suffix letter E,
The part number listed for key 273 is for the complete auto/manual station 38A2901X012
auto/manual station (suffix letter E). Individual assembly parts 314 Machine screw, fill hd, S30400 (304 SST)
are listed in the Auto/Manual Station subsection of the parts For all types w/suffix letter E,
list. Key numbers for individual ass’y parts also appear in figure auto/manual station 1C101535042
6-6. 315 Machine screw, fill hd, 18-8 SST
310 Lithium grease (not furnished with controller) For all types w/suffix letter E,
311 Anti-seize sealant, (not furnished with controller) auto/manual station 1B9925X0012
312* O-ring, nitrile (3 req’d) 316 Machine screw, fill hd, 18-8 SST
For all types w/suffix letter E, For all types w/suffix letter E,
auto/manual station (3 req’d) 1P8453X0022 auto/manual station 1U8841X0012

6-4 *Recommended spare parts


Instruction Manual
Form 5196
May 2006 4194A, B, and C Series

VIEW F-F VIEW F-F

VIEW K-K
PROCESS CONNECTION ADAPTERS

VIEW E, 4194B SERIES VIEW E, 4194B SERIES,


WITH ANTI-RESET WINDUP
(SUFFIX LETTER F)

56A9752-S SHT 2 / DOC


VIEW C-C, 4194B SERIES VIEW C-C, 4194B SERIES,
WITH ANTI-RESET WINDUP
(SUFFIX LETTER F)

Figure 6-1. Controller Assembly Drawings (cont’d)

Key Description Part Number Key Description Part Number

317 Silicone based lubricant, (not furnished with controller) 362 Spring retaining washer, SST 1B196138992
318 Lubricant, silicone sealant (not furnished with controller) 365 Washer, 18-8 SST 11B6501X012

6-5
Instruction Manual
Form 5196
4194A, B, and C Series May 2006

VIEW F-F VIEW F-F

F F F F

VIEW E, 4194C SERIES,


VIEW E, 4194C SERIES WITH ANTI-RESET WINDUP
(SUFFIX LETTER F)

VIEW C-C, 4194C SERIES VIEW C-C, 4194C SERIES,


WITH ANTI-RESET WINDUP
56A9752-S / DOC
(SUFFIX LETTER F)

Figure 6-1. Controller Assembly Drawings (cont’d)

6-6
Instruction Manual
Form 5196
May 2006 4194A, B, and C Series

SECTION B-B, 4194A SERIES SECTION B-B, 4194B SERIES SECTION B-B, 4194C SERIES

56A9752-S / DOC

CONTROLLERS WITH AUTO/MANUAL STATION


(SUFFIX LETTER E)

Figure 6-1. Controller Assembly Drawings (cont’d)

6-7
Instruction Manual
Form 5196
4194A, B, and C Series May 2006

36A6985-C / DOC

Figure 6-2. Process and Set Point Indicator Assembly

Key Description Part Number Key Description Part Number

Process and Set Point Indicator 113 Capsular element ass’y (cont’d)

Assembly (key 56) (figure 6-2) Capsular element assemblies are available in a wide variety of
101 Indicator ass’y ranges and materials of construction. A few typical part
numbers are listed here. Contact your Emerson Process
The part numbers listed here for key 101 are for the complete Management sales office for assistance in the selection of
indicator ass’y. Individual part numbers are listed in the specific parts.
Indicator Assembly and the Capsular Element Assembly
subsections of this parts list. Key numbers for individual N09902 Nickel Alloy
assembly parts also appear in figures 5-23 and 5-24. 0 to 350 mbar (0 to 5 psid) 58A0706X052
0 to 700 mbar (0 to 10 psid) 58A0706X062
For use w/o remote set pt 39A1126X012 0 to 1.4 bar (0 to 20 psid) 58A0706X072
For use w/remote set pt 39A1126X022 0 to 2 bar (0 to 30 psid) 58A0706X082

113 Capsular element ass’y (for sensing of 127 Machine screw, fill hd, 18-8 SST
process diff pressure) For mounting capsular element ass’y to
indicator ass’y (4 req’d) 1J8415X0012
The part numbers listed here for key 113 are for the complete
capsular element ass’y. Individual part numbers are listed in
the Capsular Element Assembly subsection of this parts list.
Key numbers for individual assembly parts also appear in figure
5-23.

6-8
Instruction Manual
Form 5196
May 2006 4194A, B, and C Series

VIEW A-A

A A

58A0706-C / DOC

Figure 6-3. Capsular Element Assembly

6-9
Instruction Manual
Form 5196
4194A, B, and C Series May 2006

39A1126-H / DOC

Figure 6-4. Indicator Assembly

Key Description Part Number Key Description Part Number

88 Connecting link ass’y,


aluminum/bronze/brass 10B8448X012
89 Short pivot clevis ass’y, plastic/SST 16A9791X012
Capsular Element Assembly (key 113) 90 Connecting link ass’y,
(figure 6-3) aluminum/bronze/brass 10B8769X012
12 Cap screw, hex socket, 18-8 SST 91 Process tubing ass’y, S30400 (304 SST)
(4 req’d) 1U621332982 Connects the high pressure capsule
13 Plain washer, 18-8 SST ass’y to the high pressure input
(2 req’d) 61000310X12 pressure control block (key 57) 28A0682X012
77 Mounting plate, G10100 (pl steel) 38A0667X012 92 Process tubing ass’y, S30400 (304 SST)
78 Long pivot clevis ass’y, plastic/SST 26A9784X012 Connects the low pressure capsule
79 Drive flexure, S30200 (302 SST) 16A9794X012 ass’y to the low pressure input
80 Diaphragm capsule ass’y (2 req’d) pressure control block (key 57) 18A0683X012
93 Union, S31600 (316 SST) (2 req’d) 1A5782X0022
Diaphragm capsule ass’ies are available in a wide variety of 97 Tie bar, G10100 (pl steel) 26A9803X012
ranges and materials of construction. A few typical part 98 Machine screw, pan hd, 18-8 SST
numbers are listed here. Contact your Emerson Process Used to attach the guide flexure (P/O
Management sales office for assistance in the selection of drive bracket ass’y) to mounting plate 18A0703X022
specific parts. 99 Plain washer, 18-8 SST 61000370X12
102 Machine screw, pan hd, 18-8 SST
N09902 Nickel Alloy For mounting the short pivot clevis ass’y
0.15 bar (2.17 psig) span 26A9773X012 (key 89) and the long pivot clevis ass’y
0.7 bar (10 psig) span 26A9780X012 (key 78) to the mounting plate (key 77)
1.4 bar (20 psig) span 26A9781X012 (4 req’d) 18A0703X022
2.1 bar (30 psig) span 26A9782X012 103 Machine screw, pan hd, 18-8 SST
81 Pedestal assembly, SST (2 req’d) 18A0670X012 For mounting tie bar (key 97) to pedestal
82 Diaphragm Ass’y Extension 18A0698X012 ass’ies (key 81) and to travel stop (key 83)
83 Travel stop, CF8 (SST casting) 16A9797X012 (3 req’d) 18A0703X022
84 Drive bracket ass’y, SST 16A9798X012 139 Machine screw, fill hd, 18-8 SST
85 Follower bracket ass’y, SST 16A9796X012 2 req’d to mount each pedestal ass’y (key 81)
86 Travel stop nut, S30300 (303 SST) 16A9799X012 2 req’d to mount travel stop (key 83)
87 Set screw, 18-8 SST 1J8406X0012 Qty of 6 req’d 1J8415X0012

6-10
Instruction Manual
Form 5196
May 2006 4194A, B, and C Series

j APPLY LUB/SEALANT
36A6988-C / DOC

Figure 6-5. Remote Set Point Assembly Drawing

Key Description Part Number Key Description Part Number


376 Dial Bracket, G10080 (steel) 36A7050X012
377 Dial bracket, G10080 (steel) 36A7051X012
Indicator Assembly (key 101) (figure 6-4) 378 Screw, self-tapping, 18-8 SST
Note (2 req’d) 16A9772X022

Key numbers 37, 61, 376, 377, and 378 are not
included as part of the indicator assembly (key 101). Remote Set Point Assembly (suffix letter
If replacing the indicator assembly and these parts
M) (key 62) (figure 6-5)
are required, order them separately. 12 Cap screw, hex socket, 18-8 SST
37 Self-tapping screw, 18-8 SST (4 req’d) 16A6938X022 (2 req’d) 1U621332982
61 Process scale 13 Plain washer, 18-8 SST
See Key 61 listing in Controller Parts section (3 req’d) 61000310X12
353 Machine screw, pan hd. 18-8 SST 79 Drive flexure, S30200 (302 SST) 16A9794X012
(4 req’d) 16A7044X022 80 Diaphragm capsule ass’y, for remote set pt ass’y
366 Controller Mounting Plate, 18-8 SST 38A1735X012 1 bar (12 psig) span
367 Support bracket ass’y, zinc/brass 16A7013X012 N09902 Nickel Alloy 26A9776X032
368 Link ass’y, SST/brass (2 req’d) 16A7039X012 SST 28A2848X022
369 Process pointer adj ass’y, 1.6 bar (24 psig) span
aluminum/SST/brass 28A1736X012 N09902 Nickel Alloy 26A9778X022
SST 28A2850X022
370 Set pt pointer adj ass’y aluminum/SST/brass 26A9750X012 83 Travel stop, CF8 (SST casting) 16A9797X012
371 Pivot pin, 18-8 SST (2 req’d) 16A7027X012 86 Travel stop nut, S30300 (303 SST) 16A9799X012
372 Washer, plain, 18-8 SST (4 req’d) 1V7657X0012 87 Set screw, hex socket, 18-8 SST 1J8406X0012
374 Pointer and bracket ass’y aluminum/steel 26A7059X012 93 Union, S31600 (316 SST) 1A5782X0022
375 Set pt indicator ass’y, A93003 (aluminum) 99 Plain washer, 18-8 SST 61000370X12
for controllers w/remote set pt 31B2241X012 102 Machine screw, fill hd, 18-8 SST
for controllers w/o remote set pt 26A7045X012 (4 req’d) 1H2675X0012

6-11
Instruction Manual
Form 5196
4194A, B, and C Series May 2006

Key Description Part Number Key Description Part Number


103 Machine screw, pan hd, 18-8 SST
(2 req’d) 18A0703X022 278 Tube, plastic 18A2880X012
104 Remote set pt tubing ass’y, 279 Ball, SST 18A2902X012
S30400 (304 SST) 28A0697X012 280 Ball seat, nitrile (2 req’d) 18A2881X012
105 Pedestal ass’y, SST 18A0669X022 281* Diaphragm ass’y, nitrile/aluminum 18A2884X012
106 Tie bar, G10100 (pl steel) 16A9789X022 282 Loader ass’y, aluminum/plastic 18A2893X012
107 Spring, pl steel 18A0704X012 283 Range spring, SST 18A2885X012
108 Zero adj screw, S30300 (303 SST) 18A1737X022 284 Range spring cup, pl steel 18A2869X012
109 Pivot screw, S30300 (303 SST) 18A1738X022 285 Spring adj screw, pl steel 18A2886X012
110 Zero adj bracket, S30400 (304 SST) 28A0661X012 286 Retaining ring, pl steel 18A2903X012
111 Mounting plate, G10100 (pl steel) 38A0668X012 287 Loader knob, plastic 18A2891X012
112 Spring washer, pl steel 17A2700X012 288 Machine screw, rd hd, 18-8 SST
114 Pivot clevis ass’y A, plastic/SST 18A0658X012 (2 req’d) 1C208235072
115 Pivot clevis ass’y B, plastic/SST 16A9808X012 289 Machine screw, fill hd, 18-8 SST
116 Connecting link ass’y, (4 req’d) 1C8969X0012
aluminum/bronze/brass 18A0666X012 290 Machine screw, fill hd, S30200 (302 SST)
(2 req’d) 1K318838992
118 Cap screw, hex socket, 18-8 SST 1U621332982 291 Switch body ass’y, aluminum/nitrile 28A2890X012
119 Guide flexure, S30200 (302 SST) 18A0660X012 292* O-ring, nitrile 1U2398X0032
121 Drive bracket, S30400 (304 SST) 28A0662X012 293* O-ring, nitrile 11A8741X052
122 Machine screw, fill hd, SST (2 req’d) 1U3737X0012 294* O-ring, nitrile 13A1584X012
123 Plain washer, 18-8 SST 1P752438982 295 Switch body spring, A228 (”music wire”)
124 Nut, Hex, 18-8 SST 60000410X12 alt desgntn: K08500 (pl steel) (2 req’d) 18A2889X012
125 Spacer, A92011 (aluminum) 18A0702X012 296 Ball, SST (2 req’d) 1J1550X0012
126 Connecting link ass’y, 297 Lever ass’y, SST 18A2866X012
aluminum/bronze/brass 18A0676X012 298* O-ring, nitrile 1E2226X0032
134 Diaphragm ass’y extension, A92011 (aluminum) 18A1739X012 299 Rocker arm, A96061 (aluminum) 18A2871X012
139 Machine screw, fill hd, 18-8 SST 300 Clip, SST 18A2872X012
(3 req’d) 1J8415 X0012 301 Lever spring seat, SST 18A2870X012
141 Adj arm, S30400 (304 SST) 28A0663X012 302 Lever spring, A228 (”music wire”)
311 Anti-seize sealant, (not furnished with controller) alt desgntn: K08500 (pl steel) 18A2895X012
303 Groove pin, SST 16A6380X012
304 Switch lever, plastic/SST 38A2897X012
305 Switch lever cover plate, aluminum/chromate 18A2873X012
Auto/Manual Station (suffix letter E) 306* Closing plate gasket, chloroprene 18A2898X012
(figure 6-6) 307 Closing plate, SST 18A2875X012
274 Lower loader ass’y, aluminum 18A2892X012 308 Machine screw, pan hd, 18-8 SST
275 Spring seat screw, pl steel 18A2876X012 (2 req’d) 18A2899X022
276 Valve plug spring, A228 (“music wire”) 309 Continuous output tubing ass’y, SST 28A2863X012
alt desgntn: K08500 (pl steel) 18A2877X012 310 Lithium grease, (not furnished with controller)
277 Valve plug, 18-8 SST 18A2878X012 311 Anti-seize sealant, (not furnished with controller)

6-12 *Recommended spare parts


Instruction Manual
Form 5196
May 2006 4194A, B, and C Series

B C

A C
48A2905-A SHT 1 / DOC

SECTION A-A

SECTION B-B

SECTION C-C

j APPLY LUB/SEALANT
48A2905-A SHT 2 / DOC

Figure 6-6. Auto/Manual Station Assembly Drawing

6-13
Instruction Manual
Form 5196
4194A, B, and C Series May 2006

VIEW N-N VIEW N-N


j APPLY LUB/ADHESIVE INTERNAL SET EXTERNAL SET
56A9752-S / DOC

Figure 6-7. Internal and External Set Point Option

Key Description Part Number Key Description Part Number

Controller Mounting Parts


Note
Internal/External Set Point Assembly
Contact your Emerson Process Management sales
(Option) (figure 6-7)
office for any additional parts required for controller
340 Bracket, alloy steel pl 26A5893X012 mounting.
341 Pinion gear, PPS 16A5892X012
Pipestand Mounting (figure 2-2)
342 Pinion shaft
For int set pt ass’y only 26A5894X012 66 Cap screw, hex hd, pl steel (3 req’d) 1A352624052
343 Spring, SST 19A2333X012 67 Lock washer, pl steel (7 req’d) 1C225728982
344 E-ring, SST 1E2143X0012 68 Bracket, pl steel 36A9755X012
345 Pinion rack, polycarbonate 36A5895X012 69 Clamp, pl steel (2 req’d) 1P427028982
346 Machine screw, rd hd, 18-8 SST 1E6453X0022 Pipestand Mounting with Regulator (figure 2-2)
347 Drive coupler, polycarbonate
66 Cap screw, hex hd, pl steel (3 req’d) 1A352624052
For ext set pt ass’y only 26A5897X012
67 Lock washer, pl steel (7 req’d) 1C225728982
68 Bracket, pl steel 36A9755X012
348 Flexible drive, polycarbonate
69 Clamp, pl steel (2 req’d) 1P427028982
For ext set pt ass’y only 36A5896X012
362 Cap screw, hex hd, pl steel (2 req’d) T14109T0012
349* O-ring, nitrile
363 Lock washer, pl steel (2 req’d) 1C225728982
For ext set pt ass’y only 15A1283X012
364 Hex nut, A563 pl steel (2 req’d) 1A352724122
350 Set pt knob, plastic/al/stl
365 Tubing fittings (2 req’d) See fittings subsection
For ext set pt ass’y only 26A5901X012
351 Knob insert, aluminum Panel Mounting (figure 2-3)
For int set pt ass’y only 16A5904X012 66 Cap screw, hex hd, pl steel (3 req’d) 1A352624052
352 Spring, SST 67 Lock washer, pl steel (3 req’d) 1C225728982
For ext set pt ass’y only 16A5898X012 68 Bracket, A569 (pl steel) 36A6990X012
353 Machine screw, pan hd, 18-8 SST 16A7044X022 70 Machine Screw, rd hd, pl steel (4 req’d) 16A9763X012
354 Adhesive, vinyl
For int set pt ass’y only, (not furnished with controller) Wall Mounting (figure 2-4)
355 Lubricant, silicone sealant 66 Cap screw, pl steel (3 req’d) 1A352624052
For ext set pt ass’y only, (not furnished with controller) 67 Lock washer, pl steel (3 req’d) 1C225728982
356 Rack support, alloy steel pl 16A5905X012 68 Bracket, pl steel 36A6990X012

6-14
Instruction Manual
Form 5196
May 2006 4194A, B, and C Series
Description Part Number Description Part Number

Controller Mounting Parts for Actuator With Regulator Mounting Parts for Yoke-Mounted
Casing-Mounted Controller Regulator (Mounting Bracket Not Required)
Spacer spool, steel (3 req’d) 1C559024092
Cap screw, hex hd, pl steel (3 req’d) 1B762424052 Cap screw, hex hd, pl steel (2 req’d) T14109T0012
Lock washer, pl steel (5 req’d) 1C225728982 Lock washer, pl steel (2 req’d) 1C225728982
Mounting bracket, A569 (pl steel) 36A9754X012
Cap screw, hex hd, pl steel (2 req’d) 1C379124052
Mounting bracket, G10100 (pl steel)
Regulator Mounting Parts for Yoke-Mounted
For 657/667 size 80 & 100 26A0350X012 Regulator (With Mounting Bracket)
For all other types 1F401225072
Cap screw, hex hd, pl steel (2 req’d) 1A368324052 Cap screw, hex hd, pl steel (2 req’d) 1A381624052
Hex nut, pl steel (2 req’d) 1E944024112 Lock washer, pl steel (4 req’d) 1C225728982
Washer, pl steel (2 req’d) 1B865928982 Cap screw, hex hd, pl steel (2 req’d) T14109T0012
Washer, G10100 (pl steel) (2 req’d) 1H723125072 Hex nut, pl steel (2 req’d) 1A352724122
Mounting bracket, G10100 (pl steel)
Controller Mounting Parts for Actuator With For 1061, size 30, all shaft sizes 23A8891X012
Yoke-Mounted Controller (figure 2-1) For all other types 1C221825022
Spacer spool, steel (3 req’d) 1C559024092
Cap screw, hex hd, pl steel (3 req’d) 1B762424052
Lock washer, pl steel (5 req’d) 1C225728982
Mounting bracket, steel Fittings
For 1061 w/switches or manual operator 36A6991X012 Fittings for 3/8-inch copper tubing, casing- or
For all other types 36A9754X012 yoke-mounted controller with regulator
Spacer spool, steel (2 req’d) 1J830724092 Connector, brass (2 req’d) 1B885618992
Elbow, brass (2 req’d) 1B884618992
Fittings for 3/8-inch copper tubing,
Regulator Mounting Parts pipestand-mounted controller with regulator
Regulator Mounting Parts for Casing-Mounted Elbow, brass (2 req’d) 1B884618992
Fittings for 3/8-inch copper tubing,
Regulator
all controllers without regulator
Cap screw, hex hd, pl steel (2 req’d) 1A582824052 Connector, brass (1 req’d) 1B885618992
Lock washer, pl steel (2 req’d) 1C225728982 Elbow, brass (1 req’d) 1B884618992
Cap screw, hex hd, pl steel (2 req’d) T14109T0012 Fittings for 1/2-inch synthetic rubber hose,
Hex nut, pl steel (2 req’d) 1A352724122 all controllers with or w/o regulator
Mounting bracket, G10100 (pl steel) Connector, 316 SST 15A6002XK32
For 657/667, size 80 & 100 26A0350X012 Elbow, 316 SST 15A6002XK12
For all other types 1F401225072 Swivel, 316 SST (2 req’d) 15A6002XK22

6-15
Instruction Manual
Form 5196
4194A, B, and C Series May 2006

Fisher is a mark owned by Fisher Controls International LLC, a member of the Emerson Process Management business division of Emerson
Electric Co. Emerson, Emerson Process Management, and the Emerson logo are trademarks and service marks of Emerson Electric Co. All
other marks are the property of their respective owners.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they
are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or
applicability. We reserve the right to modify or improve the designs or specifications of such products at any time without notice.
Neither Emerson, Emerson Process Management, Fisher, nor any of their affiliated entities assumes responsibility for the selection, use and
maintenance of any product. Responsibility for the selection, use and maintenance of any product remains with the purchaser and end-user.

Emerson Process Management


Fisher
Marshalltown, Iowa 50158 USA
Cernay 68700 France
Sao Paulo 05424 Brazil
Singapore 128461
www.Fisher.com

6-16 Controls International LLC 1983, 2006; All Rights Reserved


EFisher Printed in USA

You might also like