Professional Documents
Culture Documents
Collage of Engineering Undergraduate / Course Ass. Prof. Dr. Hadi Nasir AL-Maliki
ACI 318 - Fig. Minimum extensions for reinforcement in slabs without beams
ACI Code requires that at exterior corners of slabs supported by edge walls or where one or more edge
beams have a value of α greater than 1, top and bottom slab reinforcement shall be provided at exterior
corners in accordance with code.
1- Corner reinforcement in both top and bottom of slab shall be sufficient to resist a moment per unit
of width equal to the maximum positive moment per unit width in the slab panel.
2 -The moment shall be assumed to be about an axis perpendicular to the diagonal from the corner in
the top of the slab and about an axis parallel to the diagonal from the corner in the bottom of the slab.
3- Corner reinforcement shall be provided for a distance in each direction from the corner equal to
one-fifth the longer span.
4- Corner reinforcement shall be placed parallel to the diagonal in the top of the slab and perpendicular
to the diagonal in the bottom of the slab. Alternatively, reinforcement shall be placed in two layers
parallel to the sides of the slab in both the top and bottom of the slab.
The direct-design method also could have been called “the direct-analysis method,” because this method
essentially prescribes values for moments in various parts of the slab panel without the need for a
structural analysis. The reader should be aware that this design method was introduced in an era when
most engineering calculations were made with a slide rule and computer software was not available to
do the repetitive calculations required to analyze a continuous-floor slab system. Thus, for continuous
slab panels with relatively uniform lengths and subjected to distributed loading, a series of moment
coefficients were developed that would lead to safe flexural designs of two-way floor systems.
3. Successive span lengths in each direction shall not differ by more than one third of the longer span.
This limit is imposed so that certain standard reinforcement cutoff details can be used.
4. Columns may be offset from the basic rectangular grid of the building by up to ( 0.1 ) times the span
parallel to the offset. In a building laid out in this way, the actual column locations are used in
determining the spans of the slab to be used in calculating the design moments.
5. All loads must be due to gravity only and uniformly distributed over an entire panel. The direct-
design method cannot be used for unbraced, laterally loaded frames, foundation mats, or prestressed
slabs.
6. The service (unfactored) live load shall not exceed two times the service dead load. Strip or
checkerboard loadings with large ratios of live load to dead load may lead to moments larger than
those assumed in this method of analysis.
7. For a panel with beams between supports on all sides, the relative stiffness of the beams in the two
perpendicular directions given by ( )/( ) shall not be less than ( 0.2 ) or greater than ( 5 ).
The term ( ) was defined in the prior section, and and are the spans in the two directions.
Limitations ( 2 &7) do not allow use of the direct-design method for slab panels that transmit load as
one-way slabs.
The critical section for negative bending is taken at the face of rectangular supports, or at the face of an
equivalent square support having the same cross-sectional area as a round support.
In the case of end spans, the apportionment of the total static moment among the three critical moment
sections (interior negative, positive, and exterior negative, as illustrated by the figure below) depends
upon the flexural restraint provided for the slab by the exterior column or the exterior wall, as the case
may be, and depends also upon the presence or absence of beams on the column lines. ACI Code
13.6.3 specifies five alternative sets of moment distribution coefficients for end spans, as shown in the
next table and figure.