Power Sytem Analysis 1

Laboratory 2
5.43

The maximum real power that can be transferred to the load with unity power is 2950 MW with a bus
voltage of 690.5 KV. This is the required voltage above 0.9 pu (688.5 KV). Below is result varied values of load
and how it affects the bus voltage with a corresponding graph to show their relationship. As the Load power
increases it results in decreasing value of the bus voltage.
UNIVERSITY OF SCIENCE AND TECHNOLOGY OF SOUTHERN PHILIPPINES
COLLEGE OF ENGINEERING AND ARCHITECTURE
ELECTRICAL ENGINEERING DEPARTMENT
CM Recto Avenue, Lapasan 9000, Cagayan de Oro City

5.44

The maximum reactive power that can be transferred to the load with unity power is 650 MVAR with a bus
voltage of 713.6 KV. This is the required voltage above 0.9 pu (688.5 KV). Below is result varied values of
load and how it affects the bus voltage with a corresponding graph to show their relationship. When the load
power is increased the bus voltage decreases.
UNIVERSITY OF SCIENCE AND TECHNOLOGY OF SOUTHERN PHILIPPINES
COLLEGE OF ENGINEERING AND ARCHITECTURE
ELECTRICAL ENGINEERING DEPARTMENT
CM Recto Avenue, Lapasan 9000, Cagayan de Oro City

5.53 If we require the load bus voltage to be greater than or equal to 730 kV even with any line segment out of
service, what is the maximum amount of real power that can be delivered to the load?

The maximum real power that can be delivered to the load with one line segment between bus 1 and bus 2 is out
of service and the required load bus voltage is equal or more than 730KV is 10,920 MW. With that load power
is load bus voltage is 729.9 KV which is approximately to the 730 KV condition.
UNIVERSITY OF SCIENCE AND TECHNOLOGY OF SOUTHERN PHILIPPINES
COLLEGE OF ENGINEERING AND ARCHITECTURE
ELECTRICAL ENGINEERING DEPARTMENT
CM Recto Avenue, Lapasan 9000, Cagayan de Oro City

5.54 Repeat Problem 5.53, but now assume any two line segments may be out of service.

With two line segment out of service between bus 1 and bus 2, the maximum real power that can be delivered to
the load without exceeding the load voltage of 730KV is 10,245 MW. The load bus voltage is 730.6 KV when
the load is 10,245 MW which is above the 730 KV condition. The graph below shows the relationship between
the load power and bus voltage. It shows that as the value of load power increases it decreases the value of bus
voltage that we can identify the maximum voltage without exceeding the condition.
UNIVERSITY OF SCIENCE AND TECHNOLOGY OF SOUTHERN PHILIPPINES
COLLEGE OF ENGINEERING AND ARCHITECTURE
ELECTRICAL ENGINEERING DEPARTMENT
CM Recto Avenue, Lapasan 9000, Cagayan de Oro City

5.65. Graph the load bus voltage as a function of load real power (assuming unity power factor at the load).
What is the maximum amount of real power that can be transferred to the load at unity power factor if we
require the load voltage always be greater than 0.85 per unit?

The maximum real power that can be transferred to the load witch exceeding the load voltage above 0.85 pu
(650.3 KV) is 3,135 MW with a load bus voltage of 650.7 KV. Below is the graph of how their relationship
works.
UNIVERSITY OF SCIENCE AND TECHNOLOGY OF SOUTHERN PHILIPPINES
COLLEGE OF ENGINEERING AND ARCHITECTURE
ELECTRICAL ENGINEERING DEPARTMENT
CM Recto Avenue, Lapasan 9000, Cagayan de Oro City

5.66 With the reactive power load fixed at 500 Mvar, graph the load bus voltage as the MW load is varied
between 0 and 2600 MW in 200 MW increments. Then repeat with both of the series compensation elements
out of service.

Graph when the series capacitive compensation at both ends of the line in service.

Graph when the series capacitive compensation at both ends of the line are out of service.