Marine Diesel Generators in Ships Firoz 8 years ago
Share Tweet Pin Mail SMS
In order to put a generator onto a live bus bar or in other words, for the parallel operation generators in ships, the following conditions must be fulfilled.
1. The incoming generator voltage is almost equal to
the bus bar voltage. 2. The incoming generator frequency is equal to or slightly higher than the bus bar frequency. 3. With the conditions 1 and 2 met, the incoming generator circuit breaker must be closed at the exact instant when the generator voltage is in phase in opposition to the bus bar voltage (synchronism)
The following describes, as an example, how to put
D/G 2 onto the main switch board (MSB) bus already served by D/G 1. Follow the procedure for proper placing of an incoming generator to the bus bar and to load shift a generator which is already powering up bus bar.
Engine Start and Voltage
Establishment
Start D/G 2 engine and let D/G 2 voltage establish to
the rated value.
Comparison of Voltage and
Frequencies
Compare D/G 2 voltage and frequency with the bus
voltage and frequency (D/G 1 voltage and frequency as measured on the bus). Read the bus voltage and frequency on the bus voltmeter and frequency meter, which are assumed to be at the rated values. To read D/G 2 voltage and frequency, set “VOLT & FREQ METER” switch on the synchro panel to D/G 2. Automatic voltage regulator will bring the D/G 2 voltage to its rated value. So no need to adjust voltages. At this step, the generator frequency is acceptable if it is sufficiently close to the bus frequency.
Synchronism
On confirmation that the frequency difference is
small (1 Hz or less), position “SYNCHROSCOPE” switch to D/G 2 and observe the movement of the synchroscope pointer as well as the brilliance change of the synchro lamps.
Synchroscope pointer is rotating in “FAST”
direction (clockwise)
The generator frequency (D/G 2 ‘s) is higher than the
bus frequency (D/G 1 ‘s). The sequence of the synchro lamp brilliance change is also in clockwise direction.
Synchroscope pointer is rotating in “SLOW”
direction (anticlockwise)
The incoming generator frequency is lower than the
bus frequency. The sequence of the synchro lamp brilliance change is also in anticlockwise direction.
Synchroscope pointer is stopping
The generator and bus frequency are the same. The
position of the synchroscope pointer (assumed to be stationary) indicates the relative phase angle. In this case, there is no synchro lamp brilliance change.
Synchroscope pointer is at 12 o’ clock position
Whether the synchroscope pointer is moving slowly
or stationary this condition indicates that the generator and bus voltages are in phase (synchronism). At that moment, the two outside synchro lamps will be on at the same brightness while the middle top one will be at completely dark.
Closing the Generator ACB at
Synchronism
Observing the synchroscope or synchrolamps, operate
“GOVERNOR MOTOR” switch for D/G 2 to RAISE or LOWER and bring D/G 2 frequency about 0.3 Hz higher than the bus frequency (in this case, synchroscope pointer will rotate in “FAST” direction and complete one rotation in 3 or 4 seconds). Operate ACB control switch for D/G 2 to CLOSE a little prior to synchronism, anticipating a timing that D/G 2 ACB be closed at the exact instant of synchronism.
Load Division
On closure of D/G 2 ACB, operate “GOVERNOR
MOTOR” switch for D/G 2 to RAISE so that D/G 2 takes on KW load and let each generator share the load in proportion to their capacity ratio. Also operate “GOVERNOR MOTOR” switch for D/G 1 if necessary to maintain the bus frequency at 60 Hz. Then position “SYNCHROSCOPE” switch to OFF.
Load Shift
To remove one of the generators running in parallel,
first transfer load on that generator to other generator(s). When the KW output of this generator is reduced to almost zero, remove the generator from the bus by opening its ACB. For example, to remove D/G 1 running in parallel with D/G 2as mentioned above, operate “GOVERNOR MOTOR” switch for D/G 1 to lower; load on D/G 1 transfers to D/G 2. Also operate GOVERNOR MOTOR” switch for D/G 2 if necessary to maintain the bus frequency at 60 Hz. When D/G 1 output is reduced to about 5% of its rated output, operate “ACB CONTROL” switch for D/G 1 to open from the bus.
Cautions
1. Pay attention to the variation in bus frequency
during the load division or shift control, and be sure to maintain it at 60 Hz. 2. Pay attention to the loading condition of the generator(s) remaining on the bus during the load shift control, and do not overload it for them. 3. If the output of a generator is reduced below 0 KW during the load shift control, the induction type reverse power relay (RP setting: 10% of the rated output, time setting: 10 sec) will operate and trip the generator ACB.
Related Posts
May 25, 2014 Diesel Generator
Control Procedure on Installation in Ships
May 25, 2014 Starting and
Stopping of Diesel Engine Generator Sets in Ships
October 5, 2015 Capacity Control
or Regulation for Refrigeration Compressor on
Ships
May 2, 2014 MEO Class 4 Oral
and Written Questions 3
April 30, 2014 Remote Water
Level Indicator for Boilers
May 2, 2014 Fuel Oil Viscosity
Controller Working Principle
December 10, 2015 Action on
Scavenge Fire on Ships – Marine Engineering
April 29, 2014 Navigation
Checklist in Coastal Waters and Traffic Separation
Scheme (TSS)
October 27, 2015 Framo
Hydraulic Cargo Pumping System on Ships
May 1, 2014 Precautions in
Storage and Handling of Acetylene Cylinders
Categories: Marine Electrical Technology
Tags: bus bar, diesel generator in ships, diesel generator
taking on load, generator load shift, meaning of synchroscope pointer movement, parallel operation of generators, parallelling, synchronism, synchronizing two generators, take load on generator