Professional Documents
Culture Documents
[Fiber]
Fiber Number 54
Location A LOC A
Location B LOC B
Direction LOC A -> LOC B
Cable Id Location A
Fiber Id Location A Fiber
[Launch Cable]
Include Link Start Connector No
Include Link End Connector No
Launch Cable End 0.00 m
Receive Cable Start 0.00 m
[Setup]
Laser 1310nm
Pulse 30ns
Range 5km
Avr_Time 20.0s
Resolution 64cm
Scatter_Coef -79.0 dB
IOR 1.46750
[Alarms]
FAIL:
Threshold Default
Splice Loss 0.20 dB
Connector Loss 0.50 dB
Reflectance -35 dB
Slope 1.00 dB/Km
Orl 27 dB
Mux/Demux ---
Splitter 1x2 5.0 dB
Splitter 1x4 8.0 dB
Splitter 1x8 11.0 dB
Splitter 1x16 14.0 dB
Splitter 1x32 17.0 dB
Splitter 1x64 21.0 dB
Fiber Length Min ---
Fiber Length Max ---
Budget_Min ---
Budget_Max ---
WARNING:
Splice Loss ---
Connector Loss ---
Reflectance ---
[Summary]
Fiber Length(m) 255.36
Link Loss (dB) 5.524
Link ORL (dB) 36.80
Nb Of Events 7
Max Splice (dB) 0.212
Max Connector (dB) 3.112
Max Reflectance (dB) -21.96
[Results]
Event Slm Id Distance Loss Reflec Slope
Length TLoss Type Event Status
m dB dB dB/km m
dB
1 1 0.00 *1.230 *0.00 0.00
0.000 First Connector FAIL
2 2 19.15 *3.112 -44.57 19.15
1.230 Reflection FAIL
3 4 67.67 *0.212 48.52
4.370 Connector + Bend FAIL
4 5 77.88 *0.203 10.21
4.586 Splice FAIL
5 6 93.84 0.190 15.96
4.795 Splice PASS
6 7 121.30 0.165 27.45
5.023 Splice PASS
7 8 255.36 >-12.66 134.06
5.524 Fiber End N/A
<Metadata>
<Verdict>Fail</Verdict>
<Workorder></Workorder>
<TestLocation>LOC A</TestLocation>
<TestLocationB>LOC B</TestLocationB>
<TestDirection>A-B</TestDirection>
<Comments></Comments>
<AcqDate>26/06/2021 21:59:32</AcqDate>
<FiberNumber>54</FiberNumber>
<Wavelengths>1310nm</Wavelengths>
<LinkOrl>36.80</LinkOrl>
<TotalLoss>5.524</TotalLoss>
<TotalLength>255.36m</TotalLength>
<FiberId>Fiber</FiberId>
</Metadata>