CALCULATE SIZE OF DIESEL GENERATOR SET Jignesh.N.Parmar www.electricalnotes.wordpress.com jiguparmar@yahoo.

com
System Voltage ( P-P ) 400 Volt Linear Load: General Equipments, Heater
System Voltage ( P-N ) 230 Volt Non-Linear Load: UPS,Invertor,Ballast,VFD
Future Load Expansion 0% % 1
Average Intermittent Use of
0.8 (0.7 To 1.0) 0.8
Equipment
Total Connected Load on Diesel Generator Set Starting Condition Running Condition
Load Full Full Full
Sr. Starting Running Diversity Motor Starting Starting Starting
Equipment Load Type Supply Qty Load Load Load
No Load Kw/Hp P.F P.F Factor Starter Amp Kva Kw
Kva Kw Amp RESULTS
Tower Crain-E Motor 3Ph 1 43 Kw 0.8 0.8 0.5 Y-D 155 108 86 27 22 39 Starting Kva 296
Tower Crain-C Motor 3Ph 1 43 Kw 0.8 0.8 0.5 Y-D 155 108 86 27 22 39 Starting Kw 237
Tower Crain-C Motor 3Ph 1 43 Kw 0.8 0.8 0.5 Auto.Tra. 116 81 65 27 22 39 Starting Amp 427
0 0 0 0 0 0 Running Kva 81
0 0 0 0 0 0 Running Kw 65
0 0 0 0 0 0 Running Amp 116
0 0 0 0 0 0 Alternator Details
0 0 0 0 0 0 Voltage (P-N) 230
0 0 0 0 0 0 Efficiency 80%
0 0 0 0 0 0 Engine Overload Capacity 130% (Appro 130% To 150%)
0 0 0 0 0 0
0 0 0 0 0 0 Required Generator Rating
0 0 0 0 0 0 Generator KVA 237 (Select D.G near This Value)
0 0 0 0 0 0 Engine KW 67
0 0 0 0 0 0
0 0 0 0 0 0
0 0 0 0 0 0 Calculate D.G Set Efficiency & Unit Calculate Approximate
0 0 0 0 0 0 Rate of Power Fuel Consumption
0 0 0 0 0 0 D.G Size ( Kva ) 100
0 0 0 0 0 0 D.G P.F 1 D.G Size (Kva) 100
0 0 0 0 0 0 D.G Running Hours 8 D.G P.F 0.8
0 0 0 0 0 0 Diesel Consumption (Liter) 200 D.G Operation 1/2 Load
0 0 0 0 0 0 KWH Reading of Meter 28
0 0 0 0 0 0 M.F of KWH Meter 1 Required Diesel
0 0 0 0 0 0 Diesel Rate /Liter (Rs) 40 Liter/Hour 12.88
0 0 0 0 0 0 Efficiency of D.G 4%
0 0 0 0 0 0 KWH/Liter (Unit Per Liter) 0
0 0 0 0 0 0 Unit Rate of Power (Rs) 285.7
0 0 0 0 0 0