CALCULATE SIZE OF DIESEL GENERATOR SET Jignesh.N.Parmar www.electricalnotes.wordpress.com jiguparmar@yahoo.

com
System Voltage ( P-P ) 400 Volt Linear Load: General Equipments, Heater
System Voltage ( P-N ) 230 Volt Non-Linear Load: UPS,Invertor,Ballast,VFD
Future Load Expansion 10% % 1.1
Average Intermittent Use of
0.8 (0.7 To 1.0) 0.8
Equipment
Total Connected Load on Diesel Generator Set Starting Condition Running Condition
Load Full Full Full
Sr. Starting Running Diversity Motor Starting Starting Starting
Equipment Load Type Supply Qty Load Load Load
No Load Kw/Hp P.F P.F Factor Starter Amp Kva Kw
Kva Kw Amp RESULTS
Tower Crain-E Motor 3Ph 1 15 Kw 0.8 0.8 1 Freq.Conv 32 23 18 19 15 27 Starting Kva 58
Tower Crain-C Motor 3Ph 1 2.5 Kw 0.7 0.8 1 Dol 45 21 15 3 3 5 Starting Kw 43
Tower Crain-C Motor 3Ph 1 1.5 Kw 0.7 0.8 1 Dol 27 13 9 2 2 3 Starting Amp 110
z Linear 1Ph 1 1 Kw 0.7 0.8 1 5 1 1 1 1 5 Running Kva 25
0 0 0 0 0 0 Running Kw 20
0 0 0 0 0 0 Running Amp 40
0 0 0 0 0 0 Alternator Details
0 0 0 0 0 0 Voltage (P-N) 230
0 0 0 0 0 0 Efficiency 80%
0 0 0 0 0 0 Engine Overload Capacity 110% (Appro 130% To 150%)
0 0 0 0 0 0
0 0 0 0 0 0 Required Generator Rating
0 0 0 0 0 0 Generator KVA 51 (Select D.G near This Value)
0 0 0 0 0 0 Engine KW 18
0 0 0 0 0 0
0 0 0 0 0 0
0 0 0 0 0 0 Calculate D.G Set Efficiency & Unit Calculate Approximate
0 0 0 0 0 0 Rate of Power Fuel Consumption
0 0 0 0 0 0 D.G Size ( Kva ) 60
0 0 0 0 0 0 D.G P.F 1 D.G Size (Kva) 60
0 0 0 0 0 0 D.G Running Hours 20 D.G P.F 0.8
0 0 0 0 0 0 Diesel Consumption (Liter) 1000 D.G Operation Full Load
0 0 0 0 0 0 KWH Reading of Meter 10000
0 0 0 0 0 0 M.F of KWH Meter 1 Required Diesel
0 0 0 0 0 0 Diesel Rate /Liter (Rs) 40 Liter/Hour 15.15
0 0 0 0 0 0 Efficiency of D.G 1042%
0 0 0 0 0 0 KWH/Liter (Unit Per Liter) 10
0 0 0 0 0 0 Unit Rate of Power (Rs) 4.0
0 0 0 0 0 0