System Voltage ( P-P ) 415 Volt Linear Load: General Equipments, Heater
Non-Linear
System Voltage ( P-N ) 230 Volt UPS,Invertor,Ballast,VFD
Load:
Future Load Expansion 10% % 1.1
Average Use of Equipment 0.8 (0.7 To 1.0) 0.8
Total Connected Load on Diesel Generator Set
Load
Sr.N Running Diversity
Equipment Load Type Supply Qty Starting P.F
o Load Kw/Hp P.F Factor

motor Motor 1Ph 1 10 Kw 0.7 0.8 0.8


Motor 3Ph 1 120 Kw 0.7 0.8 0.8
Linear 1Ph 4 0.08 Kw 0.8 0.8 1
Non-Linear 1Ph 2 3 Kw 0.8 0.8 0.8
Non-Linear 1Ph 2 0.5 Kw 0.8 0.8 0.8
future
Free Electrical Tools
More Tools Download Now
HowToFactory.blogspot.com

Starting Condition Running Condition


Starting Full Load Full Load Full Load
Motor Starter Starting Kva Starting Kw
Amp Kva Kw Amp :Calculation:
Freq.Conv 52.2 13.7 9.6 10.0 8.0 43 Starting Kva
Auto.Tra. 500.8 411.4 288.0 120.0 96.0 167 Starting Kw
1.7 0.4 0.3 0.4 0.3 2 Starting Amp
41.7 9.6 7.7 6.0 4.8 26 Running Kva
7.0 1.6 1.3 1.0 0.8 4 Running Kw
0.0 0.0 0.0 0.0 0.0 0 Running Amp
0.0 0.0 0.0 0.0 0.0 0 Alternator Details
0.0 0.0 0.0 0.0 0.0 0 Voltage (P-N)
0.0 0.0 0.0 0.0 0.0 0 Efficiency
0.0 0.0 0.0 0.0 0.0 0 Engine Overload Capacity
0.0 0.0 0.0 0.0 0.0 0
0.0 0.0 0.0 0.0 0.0 0 :Required Size of Diesel Gen
0.0 0.0 0.0 0.0 0.0 0 Diesel Generator Size
0.0 0.0 0.0 0.0 0.0 0 Engine of Generator
0.0 0.0 0.0 0.0 0.0 0
0.0 0.0 0.0 0.0 0.0 0
0.0 0.0 0.0 0.0 0.0 0 Calculate Efficiency & Unit Rate of Power of
0.0 0.0 0.0 0.0 0.0 0 D.G set
0.0 0.0 0.0 0.0 0.0 0 D.G Size ( Kva )
0.0 0.0 0.0 0.0 0.0 0 D.G P.F
0.0 0.0 0.0 0.0 0.0 0 D.G Running Hours
0.0 0.0 0.0 0.0 0.0 0 Diesel Consumption (Liter)
0.0 0.0 0.0 0.0 0.0 0 KWH Reading of Meter
0.0 0.0 0.0 0.0 0.0 0 M.F of KWH Meter
0.0 0.0 0.0 0.0 0.0 0 Diesel Rate /Liter (Rs)
0.0 0.0 0.0 0.0 0.0 0 Efficiency of D.G
0.0 0.0 0.0 0.0 0.0 0 KWH/Liter (Unit Per Liter)
0.0 0.0 0.0 0.0 0.0 0 Unit Rate of Power (Rs)
0.0 0.0 0.0 0.0 0.0 0
603 437 307 137 110 243
:Calculation:
437 Kva
307 Kw
603 Amp
137 Kva
110 Kw
243 Amp
or Details
230 Volt
80%
130% (Appro 130% To 150%)

d Size of Diesel Generator:


384 KVA (Select D.G near This Value)
114 KW

& Unit Rate of Power of Calculate Approximate Fuel


G set Consumption
412
0.9 D.G Size (Kva) 412
5 D.G P.F 0.9
1000 D.G Operation Full Load
400
1 Required Diesel
54 Liter/Hour 95.1
22%
0.40