DUAL Datasheet
Single interlock Engineered system with Potter PFC-4410RC

FireFlex® DUAL description Features


The FireFlex® DUAL integrated system consists of an • FireFlex® DUAL system utilizes Novec 1230
integrated single interlock Electric release preaction extinguishing agent which is highly efficient for total
automatic sprinkler system combined with a clean agent fire flooding applications and a Preaction automatic sprinkler
extinguishing system, factory-assembled in a single cabinet. system.
All the components necessary for both extinguishing systems •
®
FireFlex DUAL system is FM Approved under the
®
are integrated. The FireFlex DUAL is fully tested at factory. heading: "FIXED EXTINGUISHING SYSTEMS, CLEAN
®
The FireFlex DUAL System uses Engineered SEVO™ 1230 AGENT FIRE EXTINGUISHING SYSTEMS".
FORCE500™ Clean Agent Fire Suppression System for
Class A, B and C fires. This clean extinguishing agent is • ISO-9001 manufacturing and quality control procedures.
based on sustainable technology and meets the most
stringent actual and future environmental standards • Novec 1230 extinguishing agent has zero ozone
depletion potential, an atmospheric lifetime of 0.014 year
Novec 1230 extinguishing agent description and a global warming potential of 1.
Designed as per NFPA 2001, the extinguishing agent used in • No Observed Adverse Effect Level (NOAEL) of 10%.
®
FireFlex DUAL system is Dodecafluoro-2-methylpentan-3-
one known as Novec 1230 Fire Protection Fluid (also known • USA TSCA: product complies with chemical notification
as FK-5-1-12, 3MTM NOVECTM 1230 Fire Protection Fluid, requirements. SNAP: approved for flooding (12/20/02)
C6-F-ketone) produced by 3M. and streaming (1/23/03)

Volumetric concentration varies from 4 - 6 % (not to exceed • Canada CDSL: product complies with chemical
10%) notification requirements

Novec 1230 Fire Protection Fluid is a colorless fluid. It is • Uses the Viking F1 Deluge Valves
stored as a pressurized liquid and injected into a room, area, • All trim piping is galvanized steel, Listed and Approved
or compartment that has the structural integrity to retain the for 250 psi (1724 kPa) service maximum.
agent that has been discharged.
Novec 1230 is dispensed as an odorless, electrically non- • Quick connections to water supply and drain on left side,
conductive vapor. It leaves no residue. and sprinkler riser on top of unit, available with grooved
end or flanged fittings
• No open drain cups inside unit
• Separate unlocked access hatch to emergency manual
release

1 of 16 FM-076D-0-6B
®
DUAL Datasheet
Single interlock Engineered system with Potter PFC-4410RC
System configurations
2” Single Interlock Preaction combined with single NOVEC cylinder, electric release
3” Single Interlock Preaction combined with single NOVEC cylinder, electric release

Cabinet Size of cylinder (lbs)


width 40 76 164 322 601 850
36" 1 1 1 n/a n/a n/a
46" n/a n/a n/a 1 1 n/a
52" n/a n/a n/a n/a n/a 1

Sequence of operation
Automatic release
1. Actuation of a detector from one detection zone:
d) "OUTPUT 1" (1ST ALARM) activates.
e) "ALARM" contact activates.
2. Actuation of a detector from the other detection zone for crossed zones configuration):
ND
b) "OUTPUT 2" (2 ALARM) activates.
c) Pre-discharge delay starts (not exceeding 60 sec).
4. After pre-discharge delay is completed:
a) "DISCHARGING" lamp illuminates steady.
b) "OUTPUT 4" lamp flashes.
d) NOVEC 1230 electric actuator (C) activates.
g) Preaction solenoid valve (F1) activates.
h) Deluge valve (A1) opens.

Note: Preaction piping network will be filled with water.

k) "RELEASING" contact activates.


5. After a preaction sprinkler head fuses:
a) Water will flow into sprinkler piping network and out of sprinklers and any openings on the system piping.
Manual release
1. Actuation of a manual release pull station within the system:
ND
e) "OUTPUT 2" (2 ALARM) activates.
f) "ALARM" contact activates.
g) Pre-discharge delay starts (not exceeding 30 sec).
2. After pre-discharge delay is completed:
d) NOVEC 1230 electric actuator (C) activates.
g) Preaction solenoid valve (F1) activates.
h) Deluge actuator (A1) opens.

Note: Preaction piping network will be filled with water.

j) "DETECTION ZONE 3" (WATERFLOW) message appears on the display.


k) "RELEASING" contact activates.
3. After a preaction sprinkler head fuses:
a) Water will flow into sprinkler piping network and out of sprinklers and any openings on the system piping.

Note: At any time, if the optional mechanical activator (J) is activated, the NOVEC 1230 will be released.
At any time, if the emergency release valve (B10) is activated, the preaction piping network will be filled with water.

FM-076D-0-6B 2 of 16
®
DUAL Datasheet
Single interlock Engineered system with Potter PFC-4410RC
Standard equipment
Cabinet Control panel (Self-contained system only)
®
The FireFlex DUAL unit cabinet is made of sturdy 14 ‰ 120 VAC / 60 Hz, 165VA.
gauge steel. All surfaces are rust proof coated, inside and ‰ 220 VAC / 50 Hz, 185VA.
outside, with fire red, oven baked polyester powder on ‰ 12VDC / 7Ah batteries. (factory installed)
phosphate base. Cabinet is provided with one or two ‰ 12VDC / 12Ah batteries. (optional)
doors, all provided with a neoprene gasket to absorb ‰ Single Zone detection
vibrations. (Activated by Zone 1 or Zone 2)
Electrical junction boxes are integrated inside the cabinet ‰ Crossed-Zone detection
for connection of AC power, detection system, auxiliary (Activated by Zone 1 and Zone 2)
contacts and signaling devices. Knockouts can be drilled by
the installing contractor on-site. Cabinet doors are provided The release control panel integrated into the
®
with hinges that can easily be disassembled on site to FireFlex DUAL cabinet is Potter's Model PFC-4410 RC.
remove the door assemblies for servicing. This panel includes four Class B, programmable detection
zones (optional Class A); two Class B supervisory zones
and four Class B, programmable output circuits (optional
Class A). It is also provided with menu driven programming,
including a specific program assigned at the factory.
The panel is compatible with many types of fire alarm &
supervisory devices such as linear heat detectors, spot-
type heat and smoke detectors, water flow and release
indicators, low and high air pressure switches, manual pull
stations.
The control panel also includes an alphanumeric display
with 2 lines of 16 characters describing all the system
conditions, as well as a set of red and yellow LED lamps
individually indicating each of the alarm and trouble
conditions of the system
Easy to operate control buttons are also provided to
activate and operate the system's various functions.
Standard SEVO SYSTEMS equipment
Agent storage cylinder
The agent storage cylinder by SEVO Systems is a steel
pressure vessel manufactured, tested and stamped in
accordance with DOT 4BW500 or DOT 4BA500, TC
(Transport Canada).
The agent storage cylinder is designed to hold the clean
agent at a normal operating pressure of 500 psi (34.5 bar)
at 70°F (21.1°C). The agent storage cylinders are suitable
use at temperatures of 0°F (-17.8°C) to130°F (54.4°C).
A rupture disc is connected to the cylinder body to serve as
a pressure relief device to protect the cylinder against
excessive internal pressure. The disc rupture point is in the
range of 864 psi (59.5 bar) to 950 psi (65.5 bar) at 70°F
(21.1°C).

Cylinder filling range


FireFlex® 1230 Cylinders
Size Fill Capacity (lbs)
40 16 - 40
76 31 - 76
164 66 – 164
322 129 – 322
601 241 - 601
850 366 - 854

3 of 16 FM-076D-0-6B
®
DUAL Datasheet
Single interlock Engineered system with Potter PFC-4410RC
Standard SEVO SYSTEMS equipment (cont’d)
Discharge valve Nozzles
The discharge valve is a Brass construction backpressure The Sevo® nozzles are designed to provide rapid and
type valve. The piston in the valve bore is equipped with a thorough vaporization and distribution of agent with the air
copolymer seal that keeps the Novec 1230 under pressure in the protected space. Standard nozzles are made of
within the cylinder. A small hole in the axis of the piston aluminum.
allows the cylinder pressure to equalize on both sides of Engineered system nozzles are available in five pipe sizes,
the piston. Since the area at the top of the piston is greater ½”, 1”, 1-½”, 2” and 2-½”, 180º and 360º discharge pattern.
than the area at the bottom of the piston, the net force Each nozzle has a standard female pipe thread for
seals the piston against the valve discharge outlet. When attachment to discharge piping. Nozzle shall be spaced in
the cylinder pressure on the top of the piston is released by accordance with the instructions in the “Engineered
means of automatic or manual actuation, the cylinder system design manual”. Each nozzle shall be marked
pressure acting against the piston causes it to slide to its with the Sevo® Systems part number.
fully open position allowing agent discharge.
The 40 lb and 76 lb cylinders are equipped with a 1” valve. ‰ 1/2” @ 180º ‰ 1/2” @ 360º
The 164 lb cylinders are equipped with a 1 ¼” valve. The
322 lb. and 601 lb. cylinders are equipped with 2 ½” valves. ‰ 1” @ 180º ‰ 1” @ 360º
‰ 1-1/2” @ 180º ‰ 1-1/2” @ 360º
‰ 2” @ 180º ‰ 2” @ 360º
‰ 2-1/2” @ 180º ‰ 2-1/2” @ 360º

The maximum nozzle height per layer of coverage is 16’-4”.


Electric actuator Both 180º and 360º nozzles were tested for a maximum
area coverage using a 32’ wide by 32’ long enclosure.
The SEVO electrical actuator is mounted on the top plug of
the cylinder valve. The 24 VDC electric actuator is required
to discharge the system electrically from a releasing control
panel. Pressure gauge integrated low pressure switch
Power Requirements 24 Volts d.c. The pressure gauge integrated switch is a means for both
Current 0.2A at 24 Volt d.c. visual and electronic monitoring of the pressure condition
within the cylinder. Furthermore, the pressure gauge
integrated switch eliminates the need for a separate
pressure switch.

- +

2 1

WARNING
DO NOT INSTALL IF PLUNGER IS EXTENDED

FM-076D-0-6B 4 of 16
®
DUAL Datasheet
Single interlock Engineered system with Potter PFC-4410RC
Standard SEVO SYSTEMS equipment (cont’d)
Liquid Level Indicator Releasing circuit disable switch
The SEVO Liquid Level Indicator is a simple, manually The releasing circuit disable switch is used to disable the
operated device, which provides means to determine the clean agent electrical actuator. When the key is set to
fluid level in a vertically mounted cylinder. Use of this “Disable”, the SEVO electrical actuator will be disconnected
device allows for the content of fluid to be determined from the control panel’s releasing circuit, causing a trouble
without removing cylinder from its bracketing and piping signal and preventing accidental discharge during
for weighing. maintenance or inspection.
Provided and available only on 322, 601 & 850 Cyl.

1 in

Optional SEVO SYSTEMS equipment


‰ Manual actuator (optional) ‰ Discharge pressure switch (optional)
The manual actuator features a push lever that vents The discharge pressure switch is used to provide a means of
pressure through the top of the valve causing the piston to detecting system activation. Upon activation of the cylinder
rise and allow for Novec 1230 to discharge through the valve, the discharge pressure switch contacts transfer to
valve outlet. The manual actuator also has the option to indicate discharge and/or to perform auxiliary functions
mount on top of the stackable electric actuator allowing required during system operation.
electrical or manual system activation.

As per NFPA 2001 (2008 Edition), 4.3.3.5.1. A discharge


pressure switch shall be required where mechanical
system actuation is possible.
R
W ED
H (+
BL ITE )
AC (G
K RO
(-) U
N D)

FM-076Z-0-2A

5 of 16 FM-076D-0-6B
®
DUAL Datasheet
Single interlock Engineered system with Potter PFC-4410RC
Standard Preaction equipment
Preaction valve Solenoid valve
The Viking Model F-1 Deluge Valve is a quick-opening, The high pressure solenoid valve is a two-way type with
differential diaphragm flood valve with one moving one inlet and one outlet. It is a packless, internal pilot
mechanism. The deluge valve is used to control water flow operated valve, suitable for use in releasing water pressure
in preaction sprinkler systems. The valve is held closed by from the priming chamber of Viking Deluge Valves. The
system water pressure trapped in the priming chamber, solenoid valve has floating diaphragm construction, which
keeping the outlet chamber and system piping dry. In fire requires a minimum pressure drop across the valve to
conditions, when the releasing system operates, pressure operate properly.
is released from the priming chamber. The deluge valve
clapper opens to allow water to flow into the system
‰ 2” ‰ 3”

IN OUT

Low air supervisory switch


The low pressure switch monitors the pressure within the
sprinkler piping should a loss of the air below 12 Psi occur.
The pressure switch contacts transfer indicating
supervisory signal.

POTTER
PS40-1A
Preaction riser check valve
The Viking 2” spring loaded In-Line check valve is a
general purpose rubber-faced check valve approved for
use in fire-service systems. The Spring Loaded In-Line
check valve is manufactured with a brass body, brass seat,
and a rubber-faced clapper assembly.
The Viking 3” Easy Riser® Swing check valve is a general Alarm pressure switch
purpose rubber-faced check valve approved for use in fire The alarm pressure switch monitors the water flow within
service systems. The valve is for use in preaction system the sprinkler piping. Should the Deluge Valve clapper
risers. opens to allow water to flow into the sprinkler piping. The
alarm pressure switch will activate, indicating a water flow
signal
‰ 2” ‰ 3”

POTTER
PS10-1A

FM-076D-0-6B 6 of 16
®
DUAL Datasheet
Single interlock Engineered system with Potter PFC-4410RC
Preaction system - Air supply
‰ Direct air compressor (Style “A”) ‰ Air Pressure Maintenance Device (Style “B”)
Used only for the sprinkler piping network of the preaction Used only for the sprinkler piping network of preaction
system. Air supply Style "A" includes the air compressor system, when an external air supply is provided by others
®
mounted inside the FIREFLEX DUAL cabinet with its (tank mounted compressor, plant air or dry nitrogen
supervisory trim and options. Compressor is factory piped cylinders) and piped to the air inlet port of the unit. Air
to the sprinkler piping system riser. It is available in supply style "B" provides an Air Pressure Maintenance
three (3) sizes: Device (APMD) trim, factory mounted in the
®
FireFlex DUAL cabinet.
 1/6HP 1/3HP 1/2HP
All the above air compressors are oiless piston type without
reservoir and have open, single phase motor with internal
thermal protection and supply voltage of
120Vca, 60Hz  220Vca, 50Hz.

Note: The external air supply must be restricted to insure


that it cannot replace air as fast as it escapes when a
releasing device or sprinkler operates.

Compressor selection Table:

120VAC 220VAC
Compressor CFM System capacity System capacity
size @ 40 psi to pump 40 psi to pump 40 psi
in 30 minutes in 30 minutes
1/6 HP 1.33 CFM 110 gallons 90 gallons
1/3 HP 2.61 CFM 215 gallons 170 gallons
1/2 HP 4.06 CFM 335 gallons 270 gallons

Compressor Amp rating


Amp rating @ Amp rating @
Compressor size
120VAC, 60Hz 220VAC, 50/60Hz
1/6 HP 6.6 A 3.3 A
1/3 HP 6.6 A 3.3 A
1/2 HP 8A 4A

7 of 16 FM-076D-0-6B
®
DUAL Datasheet
Single interlock Engineered system with Potter PFC-4410RC
Optional PREACTION equipment
‰ Shut-off valve & sight glass (optional) ‰ Semi-flanged inlet / outlet (optional)
®
The Shut-off Valve & Sight Glass Option is intended to be When required by the user, FireFlex DUAL units can be
used for applications where testing of the system provided in a semi-flanged configuration.
operation without filling the sprinkler piping network is The semi flanged option provides flanged fittings only on the
desirable and where it is critical that all functions of the water inlet pipe (left side) and on the system riser outlet. The
preaction system be tested under actual discharge drain manifold is provided with a threaded connection (left
conditions. side). The rest of the fittings are the same as usual with the
main components being provided in the standard flanged /
grooved configuration.

‰ Dehydrator (optional)
The Viking Dehydrator is a manually regenerated
desiccant-type air dryer. The desiccant acts as a
moisture indicator by changing color, and is visible
through the required bowl guard and transparent plastic
bowl.

FM-076D-0-6B 8 of 16
®
DUAL Datasheet
Single interlock Engineered system with Potter PFC-4410RC
Optional control panel equipment
‰ Relay module ARM-44 ‰ Class A initiating device module CA2Z
The ARM-44 is an auxiliary relay module designed to The Model CA2Z Class A Module is designed to be used
®
operate with the FireFlex DUAL control panel to provide with the PFC-4410RC Fire Control Releasing Panel to
4 independent form C relay outputs. The 4 output circuits convert from two (Class B) initiating device circuits to two
each have a dedicated relay. Each relay is rated for 3 (Class A) circuits.
amps at 24 volts DC resistive load. The relay module The module is to be mounted in the upper right hand corner
mounts directly to the back of the cabinet and is of the panel. All the connections are wired back to the field
connected to the main board. All of the relay terminals are wiring junction box.
wired back to the field wiring junction box. A disable
switch is available for disabling the relays when the
system is being tested or serviced.

24Vdc RS-485

‰ Remote Annunciator RA-4410-RC


The RA-44410-RC remote annunciator is designed to
operate with the PCF-4410RC releasing control panel. ‰ CLASS A INDICATING APPLIANCE CIRCUIT
There are 34 LED's to indicate a change in panel status. MODULE
There is a buzzer on the annunciator that sounds for any The Model CAM Class A Module is designed to be used with
trouble or supervisory condition. The release control panel the PFC-4410RC Fire Control Releasing Panel to convert a
supervises and communicates with the annunciator via single (Class B) indicating appliance circuit to a (Class A)
separate connections for the RS-485 communication and circuit (one module is required for each indicating appliance
the 24VDC power requirement of the RA-4410-RC. circuit). After installing the CAM, the indicating circuit should
Separate cables should be used for power and be activated to ensure proper operation and connections.
communication. Shielded cable MUST be used for the The module is provided with double-sided foam tape and
RS-485 communication line. should be mounted in the field wiring junction box so that the
terminals are accessible.
RA-4410-RC
ZONE 1 OUTPUT 1
ZONE 1 OUTPUT 1

ZONE 2 OUTPUT 2
ZONE 2 OUTPUT 2
ZONE 3 OUTPUT 3

ZONE 4 OUTPUT 4
ZONE 3 OUTPUT 3
AC POWER SUPERVISORY

POWER SUPERVISORY LAMP TEST


TROUBLE TROUBLE
COMMON ALM. SILENCE
SYSTEM
TROUBLE ALM. SILENCE
GROUND STEADY : DISCHARGED
ZONE 4 OUTPUT 4
FAULT FLASHING : PRE-DISCHARGE

9 of 16 FM-076D-0-6B
®
DUAL Datasheet
Single interlock Engineered system with Potter PFC-4410RC
Details & field wiring diagrams
Cabinet with main components, shown without door(s)

Clean agent outlet

Air compressor
Isolation switch

Junction box
TBA, TBB & TBC Air compressor

Releasing circuit
disable switch
Control panel

Preaction outlet

Preaction assembly

Agent storage cylinder

Drain outlet

Water inlet

FM-076Z-0-5B-1

FM-076D-0-6B 10 of 16
®
DUAL Datasheet
Single interlock Engineered system with Potter PFC-4410RC
Wiring diagram

TBA
1 AC POWER SOURCE INPUTS
+ TBB
2 5.1K ZONE 1
3 1/4W DETECTION ZONE 1 120VAC, 60 Hz 1 LINE (L1)
- CONTROL PANEL
4 2 NEUTRAL 1.4A / 120VAC
220VAC, 50/60 Hz 0.7A / 220VAC
5 3 GROUND
+
6 5.1K ZONE 2 4 GROUND AIR COMPRESSOR
7 1/4W DETECTION ZONE 2 5 NEUTRAL 1/2 HP MAXIMUM
-
8 6 LINE (L2) 120 / 220VAC
9
10 5.1K ZONE 4 Two (2) circuits are required.
11 1/4W MANUAL PULL STATIONS ! Control panel shall have a dedicated circuit breaker.
12

13
+ + OUTPUT 1
5.1K
1/4W AUDIBLE DEVICES
14
- - 1st ALARM

+ + OUTPUT 2
LEGEND
15 5.1K
1/4W AUDIBLE DEVICES
16
- - 2nd ALARM SMOKE DETECTOR
17
18 ALARM Activated by ZONE 1, HEAT DETECTOR
ZONE 2, ZONE 3 or ZONE 4
19
AUXILIARY PULL STATION
20 DRY CONTACT
21 TROUBLE Activated by any abnormal RELAY OUTPUTS
electrical condition of the system END OF LINE RESISTOR
22 TO BE USED ONLY WITH
23 RELEASING Activated by ZONE 3 - Waterflow or POWER LIMITED CIRCUITS
optional releasing switch on NOVEC 1230 cylinder BELL OR HORN
24
25 SUPERVISORY Activated by a tamper switch
26 or a low cylinder pressure condition DRY CONTACT DEVICE
+
27 POWER LIMITED 24VDC - REGULATED SOURCE
28 FOR RESISTIVE OR INDUCTIVE DEVICES (0.2A MAX)
-

Power limited (supervised) initiating device circuits


Optional Class A (Style D) Wiring ZONE 1, 2, 3 and 4
Requires modules Model: CA2Z
TBA End of line resistor: 5.1KΩ, ¼W
1 Leave EOL resistor (provided) on all unused circuits.
2 ZONE 1 Loop resistance: 100Ω max.
3 DETECTION ZONE 1
4
Refer to the PFS-4410RC control panel manual for smoke
5 detector compatibility.
6 ZONE 2
7 DETECTION ZONE 2 Power limited (supervised) initiating device circuits
8
SUPERVISORY 1 and 2
9
10 ZONE 4 End of line resistor: 5.1KΩ, ¼W
11 MANUAL PULL STATIONS Leave EOL resistor (provided) on all unused circuits.
12
Loop resistance: 100Ω max.
For dry contact supervisory devices only (Class B only)
Optional Auxiliary Relays Power limited (supervised) notification appliance circuits
TBC Requires module Model: ARM44
OUTPUT 1 and 2
1
2 1st ALARM End of line resistor: 5.1KΩ, ½W
3
Activated by any alarm
Leave EOL resistor (provided) on all unused circuits.
4
2nd ALARM
Operating voltage: 27VDC max. (ripple: 0.3V)
AUXILIARY
5 Activated after
DRY CONTACT
Usable current per circuit: 1A max.
pre-discharge delay
6 RELAY OUTPUTS Total current (all circuits): 2.5A max.
7
8
RELEASING
Activated after
TO BE USED ONLY WITH Polarity is reversed in supervisory condition.
9
pre-discharge delay
POWER LIMITED CIRCUITS
Refer to the PFC-4410RC control panel manual for device
10
RELEASING
compatibility.
11 Activated after
12
pre-discharge delay Auxiliary Power 24VDC Regulated Source
FM-076Z-0-6B
Available current: 0.2A max. for resettable 4 wires smoke
detectors
Auxiliary relay contacts
Rated 3A, 30VDC resistive

11 of 16 FM-076D-0-6B
®
DUAL Datasheet
Single interlock Engineered system with Potter PFC-4410RC
Cabinet
®
The FIREFLEX DUAL cabinet is made of sturdy 14 gauge Figure 1 - Drilling details
steel. Refer to table 1 and figure 2 for dimensions.
All surfaces are rust proof coated, inside and outside, with
fire red, oven baked polyester powder on phosphate base.
Cabinet is provided with two doors, all provided with a Drilling area
neoprene gasket to avoid vibrations, giving the access to the
pressure gauges reading and the manual emergency
release. 4½"
Top of Cabinet
TBB
Cabinet doors are provided with hinges that can easily be
disassembled on site to remove the door assemblies for TBA &
installation and servicing. The cabinet assembly is pre- LOW 5½"
VOLT.
assembled, pre-wired, and factory tested under ISO-9001
conditions. Refer to tables 2 & 3 and figures 3 & 4 for 3½"
installation and clearances details.
Electrical junction boxes are integrated inside the cabinet for
4½" FM-061H-0-68A-12

connection of detection system, auxiliary contacts and


signaling devices. Knockouts can be drilled by the installing
contractor on-site but must adhere to the restrictions
indicated on figure 1.

FM-076D-0-6B 12 of 16
®
DUAL Datasheet
Single interlock Engineered system with Potter PFC-4410RC
Table 1 - Cabinet dimensions
Size A B C D E F G
36" 35¾" 25" 77⅛" 39¾" 15" 37¾" 12¾"
46" 46" 25" 77⅛" 50" 15" 48" 23"
52" 52" 31" 81" 56" 21" 54" 26"

Table 2 - Preaction piping installation


H J K L M N1 N2 O P Q
2" 11½" 8" 5" 9¾" 45" 48⅞" 4" 11½" 3½"

3" 11½" 9" 4" 9½" 45" 48⅞" 4" 12¾" 3"

Notes:
1. N1 refers to 36" or 46" cabinet. N2 refers to 52" cabinet.
2. Dimensions may slightly differ from real unit.

Table 3 - NOVEC 1230 piping installation


Lbs R S T U
40 1" 2¾" 3¼" 6"

76 1¼" 2¾" 3¼" 6"

164 1½" 2¾" 1¾" 6"

322 2" 6¾" 4¾" 6"

601 2½" 6½" 3¾" 6"

850 3" 9" 5" 7"

Note: Dimensions may slightly differ from real unit.

13 of 16 FM-076D-0-6B
®
DUAL Datasheet
Single interlock Engineered system with Potter PFC-4410RC
Figure 2 - Cabinet dimensions
A B

U
M RØ

S T

C
J

Q O
2"Ø


L

P
K

D FM-061H-1-49B-2

Figure 3 - Floor anchoring template Figure 4 - Required clearance

Ø3/4"
5''
12'' 12''
MIN MIN

22''
MIN

FM-061H-1-49B-7
G FM-061H-1-49B-6

FM-076D-0-6B 14 of 16
®
DUAL Datasheet
Single interlock Engineered system with Potter PFC-4410RC

This page was intentionally left blank

15 of 16 FM-076D-0-6B
1935, Lionel-Bertrand Blvd.
Boisbriand QC Canada J7H 1N8
Tel.: 450-437-3473 • Fax: 450-437-1930
Toll Free: 866-347-3353
Email: info@fireflex.com • Web: www.fireflex.com

FM-076D-0-6B 16 of 16