You are on page 1of 83

EN54 PRODUCT LINE

GST100 Panel Overview

2
1-Loop Fire Panel

GST100 Addressable Fire Alarm Control Panel

⚫ Single loop panel Max. 128 loop devices


⚫ 8 zones fire and fault/disable indication
⚫ Built in Sounder output, fire output and fault output
⚫ Programming via panel keypad
⚫ Optional network card networking with other GST
intelligent fire alarm control panel
⚫ Hungary or Portuguese version available (Fascia
keypad and LCD display)
⚫ Mains supply: 230V AC
⚫ Backup battery: 24VDC/7AH

3
GST200N Panel Overview

4
1/2-Loop Fire Panel

GST200N-1 GST200N-2 1/2 Loop Addressable Fire Alarm Control


⚫ Digital communication protocol,
Panel
⚫ Loop devices capacity: 235 addresses for GST200N-1;
477 addresses for GST200N-2
⚫ 30 zones fire and fault/disable indication
⚫ PAS and Acknowledge Function
⚫ Dirty detector reporting
⚫ Walk test feature
⚫ Build in RS485 repeater output, (maximum10 repeaters)
⚫ Standard: EN54-2/EN 54-4
⚫ Mains supply: 110-240V 50/60Hz
⚫ Backup battery: 24VDC/22AH
More Languages option:
GST200N-TK (Turkish), GST200N-FR (French),
GST200N-IT(Italian), GST200N-HU(Hungary)
GST200N-SP(Spanish) GST200N-PT(Portuguese ) 5
Addressable Fire Panel

Optional Components for GST200N

P-9901A
Micro Thermal Printer
Specification:

⚫ Power: 5v (from GST200-2 internal PSU


⚫ Communication: Ribbon cable connect to
GST200-2 main board printer port
⚫ Support all ASCII character

6
Addressable Fire Panel

Optional Components for GST200N-1

LC200
Loop card (2nd Loop)

Specification:

⚫ Power: 24v (from GST200N-1 internal PSU)


⚫ Communication: Ribbon cable connect to
GST200N main board XS2
⚫ Expand one more loop for GST200N-1 panel
⚫ Loop capacity :242 points

7
Addressable Fire Panel

Optional Components for GST200N

P-9930
GST200N Communication Card

Specification:

⚫ Powered by GST200N main board


⚫ RS232 or USB communication Interface
between computer and GST200N panel
⚫ Communication: 20 pin Ribbon cable
connect to GST200N main board XS2

8
Addressable Fire Panel

Optional Components for GST200N

P-9940A
RS485 class A network card
Specification:

⚫ Powered by GST200N main board

⚫ Communication: 20 pin Ribbon cable


connect to GST200N main board XS2
port

⚫ Networking interface with all GST


intelligent FACP RS485 Class A network

9
Addressable Fire Panel

Optional Components for GST200N

P-9960
Class B CAN network card

Specification:

⚫ Powered by GST200N main board

⚫ Communication: 20 pin Ribbon cable


connect to GST200N main board XS2
port

⚫ Networking interface with all GST


intelligent FACP CAN network

10
Addressable Fire Panel

Optional Components for GST200N

P-9960A
Class A CAN network card
Specification:

⚫ Powered by GST200N main board

⚫ Communication: 20 pin Ribbon cable


connect to GST200N main board XS2
port

⚫ Networking interface with all GST


intelligent FACP CAN network

11
Panel Overview GST-200N Structure

Structures

12
Panel Overview GST-200N Fascia

Fascia

LCD Display 8x18 Control Buttons LED indicator

Buttons & 32 Zone Indication & Manual Panel Keypad


Intervention

13
www.gst.com.cn
Panel Overview GST-200N External Wiring Diagram

Output to Repeater or Mimic Panel F7.820.828V1

Terminal Monitored

A
REPEATER

XT12
RS 485
B

B
Board

REPEATER

A
XT10
A
NETWORK
No connection

XT11
Refers to Optional

RS 485
Network Board

B
B

NETWORK

A
+
LOOP OUT

XT9
Loop Out (Out to First Device)

XT4
LOOP BUS
Monitored

D2 D1 Z- Z+ B
_

GND 24V DET BUS


LOOP 1

XT1
LOOP IN
_

XT2
Loop In (In From Last Device)

+
Standby Volatge:-9 to -11VDC

XT13
OUTPUT OUTPUT
ALARM
+
LOOP OUT

XT5
+

FIRE
4.7Kohms O/P
EOL

_
Non Monitored

Output Device with Sounder with


fitted diode built-in diode
Monitored

+
LOOP OUT

F.E.P.

XT6
+
+
OR 4.7Kohms FPE FPE
EOL

_
FPE with
fitted diode

SOUNDER
OUTPUT
CIRCUIT
+
LOOP OUT

XT7
+

+
4.7Kohms
EOL

_
Sounder with Sounder with
fitted diode built-in diode

Output Setting refers to Table List on the Manual


Non Monitored

NC COM NO
FAULT OUTPUT
X4

XT8
HL5
CLASS CHANGE

XT3

F1

X5 HL2

Terminal/Output Board X6 X1
F2
HL3

X7 X2
F3
HL4
EARTH
X3
X8

14
Panel Overview GST-200N System Diagram

Stand-alone Architecture

GST200N-1 – Capacities
•235 devices
•1.0 km max loop length
•1.5mm2 UTP fire cable

15
www.gst.com.cn
Panel Overview GST-200NSystem Diagram

Stand-alone Architecture

GST200N-2 – Capacities
•Loop 1 -235 devices
•Loop 2 – 242 devices
•1.0 km max loop length
•1.5mm2 UTP fire cable

16
Panel Overview GST-200N Repeater and GMC connection

Stand-alone Architecture
•Built-in Repeater/Mimic Output
• Up to 10 points
• RS485 – 1000meters
• Support Total 200 drawings, 30.000 points

• GSTGMC-up to 8 users
• Required P-9930
•RS232- 15 meters

17
GST-IFP8 Panel Overview

18
8-Loop Fire Panel

GST-IFP8 8 Loop Addressable Fire Alarm Control Panel

⚫ 1 to 4 loop cards , each with 2 loops


⚫ 242 device capacity for each loop
⚫ Standard: EN54-2/EN 54-4
⚫ Mains supply: 220/230VAC 50/60Hz
⚫ Backup battery: 24VDC/40AH
⚫ Optional Language version: Portuguese &
Hungarian
⚫ (Keypad, Fascia, LCD text display)

19
Addressable Fire Panel

Optional Components for GST-IFP8

LCIFP8
GST IFP8 Loop Card

Specification :

⚫ Powered by GST IFP8 mother board

⚫ Easy installation, set card address via on board


rotary switch then fix the card on mother board
loop board slot

⚫ Maximum output current: 300mA per loop

⚫ Capacity : 2 loops 484 points

20
Addressable Fire Panel

Optional Components for GST-IFP8

P-9935
GST IFP8 communication card

Specification :

⚫ Powered by GST IFP8 mother board

⚫ Easy installation, set card address via rotary


switch then fix the card on mother board Com
board slot

⚫ interface port: RS232 or USB port

21
Addressable Fire Panel

Optional Components for GST-IFP8

P-9945A
GST IFP8 RS485 Class A network card

Specification :

⚫ Powered by GST IFP8 mother board

⚫ Easy installed, set card address via on board


rotary switch then fix the card on mother board
loop board slot

⚫ Interface port : RS485

22
Addressable Fire Panel

Optional Components for GST-IFP8

P-9965
GST IFP8 CAN network card (Class B)

Specification :

⚫ Powered by GST IFP8 mother board

⚫ Easy installed, set card address via on board


rotary switch then fix the card on mother board
loop board slot

⚫ Interface port: CAN

23
Addressable Fire Panel

Optional Components for GST-IFP8

P-9965A
GST IFP8 CAN network card (Class A)

Specification :

⚫ Powered by GST IFP8 mother board

⚫ Easy installed, set card address via on board


rotary switch then fix the card on mother board
loop board slot

⚫ Interface port: CAN

24
Panel Overview GST-IFP8 Structure

Structures

25
Panel Overview GST-IFP8 Fascia

Fascia

LED indicator

Control Buttons

2 x 70 Zone Indication

26
www.gst.com.cn
Panel Overview GST-IFP8 Internal Parts Overview

LCD ,keypad and


Main Indication board

Zone Indication board

Micro Thermal Printer


27
www.gst.com.cn
Panel Overview GST-IFP8 Internal Parts Overview

PSU Interface Board


Mother Board

Panel PSU Main Power Switch


AC Power Filter
28
www.gst.com.cn
Panel Overview GST-IFP8 Internal Wiring

Basic Internal Wiring Diagram MAIN CONTROL BOARD

XS8
F7.820.1238V2 XS1

NO COM NC
OUTPUT
FAULT
INDICATOR BOARD
COM BOARD

REPEATER
B
A
XS9 XS2

F1
XS15

BACK
FEED

F2
MAIN BOARD

ROUTING
-
OUTPUT TO ALARM
XS5

+
TO MAINBOARD

SOUNDER
-
XS10 XS3

GND +5V

+
-
OUTPUT
TO FPE
LOOP BOARD

+
I-
0-
LOOP 01
XS11 XS4

XS1

I+
0+
I-
0-
LOOP 01

I+
0+
TO MAINBOARD
LOOP BOARD

I-
0-
+5V GND

LOOP 01

I+
XS12 XS5

0+
I-
RP1

0-
LOOP 01

I+
0+
LOOP BOARD

I-
0-
LOOP 01

I+
0+
I-
XS13 XS6

0-
IO ZONE

LOOP 01

I+
0+
I-
0-
LOOP 01
LOOP BOARD

I+
TO PRINT

0+
F7.820.1238V2 XS3

I-
0-
LOOP 01
XS6

I+
XS14 XS7

0+
I-
0-
LOOP 01

I+
0+
I-
LOOP BOARD GND 5V TX RX GND 24V

0-
LOOP 01

I+
0+
24V

MAIN POWER BOARD


HL HL HL HL HL HL HL HL HL HL HL HL HL HL

+ +
HL HL
+
HL
+
HL
+
HL
+
HL
+
HL
+
HL
+
HL
+
HL
+
HL
+
HL
ZS2
+
HL
+
HL F7.820.1311V2
+ + + + + + + + + + + +
HL HL HL HL HL HL
+ +
HL HL HL HL HL HL HL HL

+ + + + + + + + + + + + + +
HL HL HL HL HL HL HL HL HL HL HL HL HL HL GND 5V TX RX 24V GND
+ + + + + + + + + + + +
HL HL HL HL HL HL
+ +
HL HL HL HL HL HL HL HL

+ + + + + + + + + + + +
HL HL HL HL HL HL
+ +
HL HL HL HL HL HL HL HL

+5V GND
+ + + + + + + + + + + +
HL HL HL HL HL HL
+ +
HL HL HL HL HL HL HL HL

+ + + + + + + + + + + +
HL HL HL HL HL HL
+ +
HL HL HL HL HL HL HL HL

+ + + + + + + + + + + +
HL HL HL HL HL HL
+ +
HL HL HL HL HL HL HL HL

+ + + + + + + + + + + +
HL HL
HL HL
+ +
HL HL HL HL HL HL HL HL

27V GND
+ +
F7.820.1312V2 + + + + + + + + + +

BT1
ZONE INDICATOR BOARD

BAT+ BAT-
HL HL HL HL HL HL HL HL HL HL HL HL HL HL 90V/260/12V
+ + + + + + + + + + + + + +
HL HL HL HL HL HL HL HL HL HL HL HL
ZS2 HL HL

+ + + + + + + + + + + +
HL HL HL HL HL HL
+ + DC Output 27V 11.7A +V AJD
HL HL HL HL HL HL HL HL

+ + + + + + + + + + + +
XP1 + +
HL HL HL HL HL HL HL HL HL HL HL HL HL HL

+ + + + + + + + + + + +
HL HL HL HL HL HL
+ +
HL HL HL HL HL HL HL HL

+ + + + + + + + + + + +
HL HL HL HL
+ +
HL HL HL HL HL HL HL HL HL HL
V+

+ + + + + + + + + + + +
HL HL HL HL HL HL
+ +
HL HL HL HL HL HL HL HL

+ + + + + + + + + + + +
HL HL HL HL HL HL
+ +
HL HL HL HL HL HL HL HL

+ + + + + + + + + + + +
HL HL HL HL HL HL
+ +
HL HL HL HL HL HL HL HL
V-

+ + + + + + + + + + + + + +
HL HL
HL HL HL HL HL HL HL HL HL HL Fuse
+ +
F7.820.1312V2 + + + + + + + + + +
AC Input
L N

2A AC Input
AC220V

PRINTER
AC/DC POWER
CONVERTER AC FILTER POWER SWITCH

+ - + -

29
www.gst.com.cn
Panel Overview GST-IFP8 External Wiring

XS8
F7.820.1238V2 XS1

NO COM NC

System Connections
XT18

OUTPUT
FAULT
COM BOARD

REPEATER
B

XT14

B
Output to Repeater or
XS9 XS2 Mimic Panel

A
A
XS15

F2 F1
XT19

BACK
FEED
Fitted
470 ohms
EOL
4.7Kohms

MAIN BOARD

SOUNDER ROUTING
XT13

ALARM

_
O/P EOL
4.7Kohms

+
TO MAINBOARD

GST-IFP8
Sounder with Output Device with
built-in diode fitted diode

OUTPUT TO
XT12
XS10 XS3

_
O/P EOL

+
4.7Kohms

+
+
Sounder with Output Device with
built-in diode fitted diode

OUTPUT
XT11

TO FPE
_
FPE FPE EOL
4.7Kohms

+
+
LOOP BOARD

+
FPE with
fitted diode

XS11 XS4

LOOP 01 LOOP 02 LOOP 03 LOOP 04 LOOP 05 LOOP 06 LOOP 07 LOOP 08 LOOP 09 LOOP 10

I+ I-
XT10

O+ O- O+ O- O+ O- O+ O- O+ O- O+ O- O+ O- O+ O- O+ O- O+ O-
A1

O-
Out to next panel A2

LOOP 10
O+
Out to next panel B2
B1

I+ I-

XT10
XT9
Network Terminal - Class A
LOOP BOARD B2 In from next panel B1

I+
+5V GND

I+ I-
XS12 XS5

XT8
In from next panel A1

I-
A2

I+ I-
A

O-
Out to next panel A

XT7

LOOP 10
LOOP BOARD

O+
Out to next panel B
B

I+ I-

XT10
XT6
Network Terminal - Class B

I+
XS13 XS6

I+ I-
No connection

XT5

I-
I+ I-
XT4
LOOP BOARD
Out to first device

O-
I+ I-
Loop Out

XT3

LOOP 01
O+
XS14 XS7

XT1
I+ I-
XT2

I+
Loop In

I+ I-
LOOP BOARD

I-
GND 5V TX RX GND 24V In from last device

XT1
24V

30
Panel Overview GST-IFP8 External Wiring

Basic loop Terminal


Connect the loop within the panel as follows:
Loop OUT + to Loop IN+/ Loop OUT- to Loop
IN- . out to first device

O- Loop Out
LOOP 01
O+
XT1
Loop Wiring
I+

Loop In
I-

in from last device

•Loop Address: 242 A1


O-

out to next panel A2


•Output Voltage:21-27Vdc
LOOP 10
O+

•Output Current: 300mA out to next panel B2


B1
•Wiring Topology: Class A or B
XT10

•Recommended Cable length: 1000 Terminal


Network meters - Class A
•Recommended Cable: B21.5mm 2 UTP fire cable
in from next panel B1
I+

•Loop protection: Optional loop isolator (C-9503/4)


in from next panel A1
I-

A2
31
Panel Overview GST-IFP8 External Wiring

Basic Output / Input Terminal

Device Alarm Delay Time Stop – via


Output Condition Disable CE Mode
Number (Default) Program Silence Button
Alarm
Routing A 00000083 Immediate Yes No Yes No
Routing
Output to
Sounder A 00000082 Immediate Yes Yes Yes Yes
Sounder
Output to
FPE A 00000081 Immediate Yes Yes No No
FPE

Note: For output dry contact use C-9302C (output capacity 5A/220VAC or 5A/24VDC)

32
www.gst.com.cn
Panel Overview GST-IFP8 Mother Board

Basic Mother Board Slot Positioning

33
Panel Overview GST-IFP8 Card Configuration

Card addressing
Each card (except main board) must be set
unique number (via onboard rotary switch) before
install it on motherboard,
Addressing sequence :loop card network card,
repeater card and RS232 communication card,
The number must start from No.1, and
continuously
Installation: recommend the card No.1 installed
on the lowest slot. Then card No.2 on the upper
slot, one by one till last card

CARD SUM:04 LOOP SUM:06 DEVICE SUM:614


*************************************************************
1 Loop 01: Loop Card, Devices Sum:184
2 Loop 02: Loop Card, Devices Sum:160
3 Loop 03: Loop Card, Devices Sum:150
4 Loop 04: Loop Card, Devices Sum:120
5 Loop 05: Net Unit
6 Loop 06: Color CRT

->[F1] to Print All Loop Devices Info.


->[F2] – Found Devices [F3] –Missed Devices

34
www.gst.com.cn
Panel Overview GST-IFP8 Card Configuration

Card Configuration

10 Loops + Repeater
10 Loops + Communication
8 Loops + Communication + Repeater
8 Loops + Communication+ Network
8 Loops + Network + Repeater
6 Loops + Communication + Network + Repeater

35
Panel Overview GST-IFP8 Card Configuration

Card Configuration
XS1
XS8 A1
9 01
HL1 Loop 11 - CRT Card 01
HL2
8
7
2
3 P-9935- Communication Card
6 5 4

XS2
XS9 Main Card

XS3
Loop 10-Loop card - Wired on Loop 10 terminal Sample…
XS10
LED HL2 LED HL1

9 01
8
7
6 5 4
2
3 Loop 9-Loop card - Wired on Loop 09 terminal 10 Loops + Repeater
A1
LCIFP8-Dual Loop Card 10 Loops + Communication
XS4
XS11
LED HL2

9 01
LED HL1
Loop 8-Loop card - Wired on Loop 08 terminal
8 2
7 3 Loop 7-Loop card - Wired on Loop 07 terminal
6 5 4
A1
LCIFP8-Dual Loop Card
XS5
XS12
LED HL2

9 01
LED HL1
Loop 6-Loop card - Wired on Loop 06 terminal
8 2
7 3 Loop 5-Loop card - Wired on Loop 05 terminal
6 5 4
A1
LCIFP8-Dual Loop Card

XS6
XS13
LED HL2

9 01
LED HL1
Loop 4-Loop card - Wired on Loop 04 terminal
8 2
7 3 Loop 3-Loop card - Wired on Loop 03 terminal
6 5 4
A1
LCIFP8-Dual Loop Card

XS7
XS17
LED HL2

9 01
LED HL1
Loop 2-Loop card - Wired on Loop 02 terminal
8 2
7 3 Loop 1-Loop card - Wired on Loop 01 terminal
6 5 4
A1
LCIFP8-Dual Loop Card

36
www.gst.com.cn
Panel Overview GST-IFP8 Card Configuration

Card Configuration
XS1
XS8 A1
9 01
HL1 Loop 10 - CRT Card 01
HL2
8
7
2
3 P-9935- Communication Card
654

XS2
XS9 Main Card

XS3 Sample…
XS10
LED HL2

9 01
LED HL1
Loop 9-Net Unit - Wired on Loop 10 terminal
8 2
7 3 P-9945A - Network Card
654
A1 8 Loops + Network + Communication card
XS4
XS11
LED HL2

9 01
LED HL1
Loop 8-Loop card - Wired on Loop 08 terminal
8
7
654
2
3 Loop 7-Loop card - Wired on Loop 07 terminal 8 Loops + Network + Repeater
A1
LCIFP8-Dual Loop Card
XS5
XS12
LED HL2

9 01
LED HL1
Loop 6-Loop card - Wired on Loop 06 terminal
8 2
7 3 Loop 5-Loop card - Wired on Loop 05 terminal
654
A1
LCIFP8-Dual Loop Card

XS6
XS13
LED HL2

9 01
LED HL1
Loop 4-Loop card - Wired on Loop 04 terminal
8 2
7 3 Loop 3-Loop card - Wired on Loop 03 terminal
654
A1
LCIFP8-Dual Loop Card

XS7
XS17
LED HL2

9 01
LED HL1
Loop 2-Loop card - Wired on Loop 02 terminal
8 2
7 3 Loop 1-Loop card - Wired on Loop 01 terminal
654
A1
LCIFP8-Dual Loop Card

37
www.gst.com.cn
Panel Overview GST-IFP8 Card Configuration

Card Configuration
XS1
XS8 A1
9 01
HL1 Loop 9 - Repeater Card 01
HL2
8
7
2
3 P-9945RP - Repeater Card
65 4

XS2
XS9 Main Card

XS3
XS10
LED HL2

9 01
LED HL1
Loop 8-Net Unit - Wired on Loop 10 terminal
Sample…
8 2
7 3 P-9945A - Network Card - 01
65 4
A1

6 Loops + Network + Repeater+


XS4
XS11
LED HL2

9 01
LED HL1
Loop 7 - CRT Card 01
8 2
P-9935 - Communication Card
Communication card
7 3
65 4
A1

XS5
XS12
LED HL2

9 01
LED HL1
Loop 6-Loop card - Wired on Loop 06 terminal
8 2
7 3 Loop 5-Loop card - Wired on Loop 05 terminal
65 4
A1
LCIFP8-Dual Loop Card

XS6
XS13
LED HL2

9 01
LED HL1
Loop 4-Loop card - Wired on Loop 04 terminal
8 2
7 3 Loop 3-Loop card - Wired on Loop 03 terminal
65 4
A1
LCIFP8-Dual Loop Card

XS7
XS17
LED HL2

9 01
LED HL1
Loop 2-Loop card - Wired on Loop 02 terminal
8 2
7 3 Loop 1-Loop card - Wired on Loop 01 terminal
65 4
A1
LCIFP8-Dual Loop Card

38
www.gst.com.cn
Panel Overview GST-IFP8 System Diagram

Stand-alone Architecture

IFP8 Capacities
•LCIFP8 –dual loop
•Loop 10 -2420 devices
•1.0 km max loop length
•1.5mm2 UTP fire cable

39
Panel Overview GST-IFP8 Repeater and GMC connection

•Required P-9945RP Repeater card


• Up to 64 points (Repeater or Mimic panel)
• RS485 – 1000meters
• Support Total 200 drawings, 30.000 points

• GSTGMC-up to 8 users
• Required P-9935
•RS232- 15 meters

40
www.gst.com.cn
Panels Networking

41
Panels Networking

Network

⚫ Fire resistance cable, Min. 1.0mm2


⚫ 1.5sqmm UTP cable is recommended.
⚫ 1200 meters total distance for RS485 network Class B connection
⚫ 1200 meters distance between two panels for RS485 network Class A
connection
⚫ 3500 meters distance for each branch of CAN network.

42
Panels Networking

RS485 Class A Network •Maximum 32 FACP

RS 232 Card

Network Card RS 485 Network Card RS 485


(P-9945A) (P-9940A)

Length between panels1.2 Km (max)

Built-in Network Card RS 485


Network Card RS 485 (P-9940A)
(P-9940A)

43
Panels Networking

CAN Class A Network •Maximum 99 FACP

RS 232 Card

CAN Network Card CAN Network Card


CAN Network Card
(P-9965A) (P-9960A)
(P-9960A)

Length between panels 3.5Km (max)

CAN Network Card


CAN Network Card (P-9960A)
(P-9965A)

44
Panels Networking

Maximum 240 FACP in whole network.


CAN Class B Network Maximum 112 FACP in each branch

P-9960 P-9960
P-9965
Total Cable Length 3.5 Km (max)

P-9965

CAN HUB
CAN100H-4/8/12/16
P-9960 P-9965 P-9965

P-9960
45
Panels Networking

•Maximum 32 FACP
Fiber Optic Network

RS485 Class B Fiber Optic Network

Fibre Optic
+ +
P-9940A P-9945A

(For Single-Mode-25KM)
Interface FIB485S01
Optic

Optic
Fibre

Fibre
(For Multi Mode -4.5km)
Interface FIB485M01

+ +
P-9940A P-9940A

46
www.gst.com.cn
Panels Networking

Fiber Optic Network •Maximum 32 FACP

RS485 Class A Fiber Optic Network


Fibre Optic
+ +
P-9940A P-9945A

(For Single-Mode-25KM)
Interface FIB485S01
Fibre Optic

Fibre Optic
(For Multi Mode -4.5km)
Interface FIB485M01

Fibre Optic
+ +
P-9940A P-9940A

47
Panels Networking

TCP/IP Network

+ +

P-9935 TCPIP + NPort5230


NPort5230 + P-9930TCP/IP

TCP/IP

+
+
NPort5230 + P-9930TCP/IP
P-9935 TCPIP + NPort5230

48
Product Overview

49
Initiating Device

Intelligent Sensor ⚫ 8-bit micro-processor


⚫ Sensitive Ultraviolet sensor that detects the UV rays
produced by a flame
⚫ Dust/Corrosion/Humidity resistant
⚫ Electronically addressed by handheld programmer
⚫ Detection distance :
⚫ Level I: 25m (default) ; Level II: 17m ; Level III: 12m.
I-9104
Intelligent Ultraviolet ⚫ <Fire for Testing: 2000g industry ethanol burning in a
Flame Detector container (dimension: 33cm×33cm×5cm )>

DZ-03
Standard Base
50
Detector

⚫ Advance digital communication


Digital Intelligent Sensor
⚫ Drift compensation, reject false alarm from environment
changing, dust accumulation and component aging.
⚫ Electrically addressed by handheld programmer
⚫ Built-in remote indicator output
⚫ Special LED blink under dirty
⚫ A2R Heat alarming
⚫ Typical Fixed Alarm Temperature:62℃
⚫ Magnetic test
DI-9101E
Intelligent Combination ⚫ LED blink could be optionally disabled
Heat Photoelectric Smoke ⚫ Detector store most recent 5 fire alarms and fault alarms,
Detector
as well as total number of alarms.
⚫ IP Rate: IP2X

DB-01 C-9314P
Standard Base Remote Indicator
51
Detector

⚫ Advance digital communication


Digital Intelligent Sensor
⚫ Drift compensation, reject false alarm from environment
changing, dust accumulation and component aging.
⚫ Electrically addressed by handheld programmer
⚫ Built-in remote indicator output
⚫ Special LED blink under dirty
⚫ LED blink could be optionally disabled
⚫ Magnetic test
⚫ Detector store most recent 5 fire alarms, and fault
alarms, as well as total number of alarms.
DI-9102E
Intelligent Photoelectric ⚫ IP Rate: IP2X
Smoke Detector

DB-01 C-9314P
Standard Base Remote Indicator
52
Detector

⚫ Advance digital communication


Digital Intelligent Sensor
⚫ A1R/A2S/BS Selectable(LPCB)
⚫ Typical Fixed Alarm Temperature:
A1: 58℃ A2:62℃ B:77℃
⚫ Electrically addressed by handheld programmer
⚫ Built-in remote indicator output
⚫ LED blink could be optionally disabled
⚫ Magnetic test
⚫ Detector store most recent 5 fire alarms, and fault

DI-9103E alarms, as well as total number of alarms.


Intelligent Rate of Rise ⚫ IP Rate: IP2X
and Fixed Temperature
Heat Detector

DB-01 C-9314P
Standard Base Remote Indicator
53
Initiating Device

Beam Detector

⚫ Infrared beam detector


⚫ Detection range 8 to 100 meters
⚫ Path width 7 meters each side
⚫ 1 to 4 reflectors for different path length
⚫ Standard EN54-12
⚫ Electronically addressed by programmer
⚫ Additional Fire and Fault dry contact relay output
⚫ 24VDC supply required

I-9105R
Reflective Beam Detector

54
Initiating Device

Manual Call Points ⚫ Semi-flush or Surface mounted


⚫ Standard EN54-11
⚫ Re-settable (non-breaking glass)
⚫ LED indicator
⚫ Electronically addressed by handheld programmer
⚫ Friendly installation and test
⚫ Optional flipping plastic cover (D-92FC)
⚫ Optional weatherproof box(D-92WPB)
⚫ Optional back box for surface mount
DI-9204E
Digital manual Call Point

D-92FC D-92WPB
Protective Flip Cover Waterproof Box 55
Notification Device

I-9401N Sounder Strobe

⚫ Addressable combined flashing high intensity LED


beacon and sounder
⚫ Sound pressure level 95db@1M
⚫ external 24VDC required
⚫ Electronically addressed by handheld programmer
⚫ Easy installation and connection

56
Notification Device

I-9403 Sounder Strobe ⚫ 16 selectable tone


⚫ High sound level
⚫ Low/high power consumption modes
⚫ Loop powered or external 24VDC
⚫ Max. 30 pieces per loop when powered by loop
⚫ High intensity LED cluster
⚫ Programmable evacuate only or alert/evacuate mode
⚫ Standard EN54-3
⚫ Electronically addressed by handheld programmer
⚫ Easy installation and connection

C-94DB
Optional deep base for I-9403

57
Notification Device

I-9404 Intelligent Sounder ⚫ 16 selectable tone


⚫ High sound level
⚫ Low/high power consumption modes
⚫ Loop powered or external 24VDC
⚫ Max. 30 pieces per loop when powered by loop
⚫ Programmable evacuate only or alert/evacuate mode
⚫ Standard EN54-3
⚫ Electronically addressed by handheld programmer
⚫ Easy installation and connection

C-94DB
Optional deep base for I-9404

58
Notification Device

DI-9405 Addressable ⚫ “sandwich” structure


Sounder Base ⚫ Termination suitable for “DI” range detectors
⚫ Loop powered
⚫ Maximum 30 pieces per loop
⚫ Three working modes settable (Mode I, II, III,
and the latter two available with pre-alarm state).
⚫ 16 tones of sound.
⚫ Electronically addressed. The address and
tones can be modified in field.
⚫ Tone 14 and 16 are certified by EN54-3.
⚫ IP Rate: IP21C

59
Notification Device

DI-9406 Addressable
Sounder Beacon Base ⚫ “sandwich” structure
⚫ Termination suitable for “DI” range detectors
⚫ 16 selectable tone
⚫ Loop powered
⚫ Maximum 30 pieces per loop
⚫ Three working modes settable (Mode I, II, III, and
the latter two available with pre-alarm state).
⚫ 16 tones of sound and bright flashing light.
⚫ Electronically addressed. The address and tones
can be modified in field.
⚫ Tone 14 and 16 are certified by EN54-3.
⚫ IP Rate: IP21C

60
Isolator

Loop Isolator Base

⚫ Termination suitable for “DI” range detectors


⚫ Isolates faulty part of the loop in case short circuit
⚫ Auto resume when trouble removed
⚫ LED status indicator
⚫ Not occupy loop address
⚫ Maximum 128 pcs per loop
⚫ IP Rate: IP33 With Cover / IP22 Without Cover

DC-9504E
Base Mount Short Circuit Isolator

61
Module

⚫ Din-Rail Mounted or Surface mounted


⚫ Loop Powered
⚫ Low Power consumption
Standby loop current: ≤0.26mA
Active loop current: ≤0.5mA
⚫ Electronically addressed by handheld programmer
⚫ LED status indication for fault or activation
⚫ Programmable N/O or N/C dry contact input
⚫ Cable monitored
⚫ Standards:UL864
⚫ IP Rate: IP30

DI-9300E ⚫ Dimension:78x45.3x28.4mm
Digital Single Input Module

62
Module

⚫ Din-Rail Mounted or Surface mounted


⚫ Loop Powered
⚫ Low Power consumption
Standby loop current: ≤0.26mA
Active loop current: ≤0.7mA
⚫ Electronically addressed by handheld programmer
⚫ LED status indication for fault or activation
⚫ N/O or N/C dry contact output (30VDC@2A)
⚫ Programmable taken 1 address (monitor and control
one equipment) or 2 individual address (monitor and
control different equipment)
DI-9301E
Digital Single Input / Output ⚫ IP Rate: IP30
Module ⚫ Dimension: 85.3x78x30.6 mm

63
Module

⚫ Din-Rail Mounted or Surface mounted


⚫ Low Power consumption,
Standby loop current: ≤0.26mA
Active loop current: ≤0.5mA
⚫ Maximum Output Load:2A @ 30VDC,0.35PF
⚫ Electronically addressed by handheld programmer
⚫ LED status indication for fault or activation
⚫ Provide 24V output with cable monitoring ( external
24V input needed)
⚫ Interface with GST Voice alarm system connect to
DI-9305E field speakers
Digital Single Riser
⚫ Relay capacity: 30VDC 2A / 125VAC 0.5A
Output Module
⚫ IP Rate: IP30
⚫ Dimension: 85.3x78x30.6 mm

64
Module

⚫ Din-Rail Mounted or Surface mounted


⚫ Low Power consumption
Standby loop current: ≤0.23mA
Active loop current: ≤0.25mA
Standby external 24V input current: ≤10mA
Active external 24V input current : ≤60mA
⚫ Interface with conventional fire devices
⚫ 24VDC required
⚫ Cable monitored
⚫ Electronically addressed by handheld programmer
DI-9319E ⚫ LED status indication for fault or alarm condition
Digital Zone Monitor Module ⚫ Provide on board NO/NC dry contact relay output , auto to
triggered by input circuit alarm signal
⚫ IP Rate: IP30
⚫ Dimension: 85.3x78x30.6 mm
65
Module

⚫ Din-Rail Mounted or Surface mounted


⚫ Low Power consumption
Standby loop current: ≤0.15mA
Active loop current: ≤1.5mA
⚫ Isolates faulty part of the loop in case short
circuit
⚫ Auto resume when trouble removed
⚫ LED status indicator
⚫ Not occupy loop address
⚫ Maximum 128 pcs per loop
⚫ IP Rate: IP30
DC-9503E ⚫ Dimension:78x45.3x28.4mm
Loop Isolator

66
Programmer

Handheld Programmer

⚫ Set address to loop devices


⚫ Change parameter setting of loop device
⚫ Program graphic repeater panel LEDs

P-9910B Programmer

67
Commissioning Tool

• Small and Exquisite with large LCD screen


• Portable and easy carry
• Register loop devices, change parameters ( replacing P-9910B)
• Loop devices checking, type, quantity, address, status etc.
• Single device test, group devices test
• Duplicated address checking
• Device functional test: start/stop module outputs, start/stop
sounders, On/Off devices status indicators etc.

P-9920 Commisioning Tool

68
Power Supply

Intelligent Power Supply Unit

PSU24-5/5A 5A Power Supply Unit

PSU24-10/10A 10A Power Supply Unit

⚫ Indication of output voltage, output current, main's


fault, battery fault, output fault and charger fault
⚫ 24VDC power unit for high consumption devices
⚫ Integrated battery charger

69
Repeater Panel

GST-852RP Passive Repeater Panel

⚫ Compatible with all GST intelligent fire alarm


control panel
⚫ Fire Event Display
⚫ Local Sounder mute and Scroll alarm buttons
⚫ Connect to RS485 repeater loop

70
Repeater Panel

GST-NRP00 Network Repeater Panel

⚫ Display network message (Fire, Plant and Fault)


⚫ Achieve remote control of systems
⚫ Password protected
⚫ Connect in GST panel network

Note: Optional network card (P-9940A or P-9960A)


need ordered separate and installed on site

71
Repeater Panel

GST-8903 –A1/A2/A3 Graphic Repeater Panel

⚫ Up to 100 LED per module


⚫ Custom graphical layout
⚫ Display individual points and zone wise fire
and fault signal
⚫ Display individual points action signal.
⚫ Connect to RS485 repeater loop (can be
mixed with GST852RP)

72
Graphic Station

GST-GMC Graphic Monitor Center

⚫ Display message (Fire, Fault, Action, Disable)


⚫ Remote full control and monitor of systems
⚫ Multi-level Password protected
⚫ Historic data of all the system events
⚫ Clock synchronization with panels
⚫ Up to 8 users plus the server in a Network
⚫ Connect with panel through RS232 cable
⚫ Support Total 200 drawings, 30.000 points

73
Intrinsically Safe
&
Explosion Proof Products
Intrinsically Safe Detector

DC-9101(IS) DC-9102(IS) DC-9103(IS)


Intrinsically Safe Intrinsically Safe Intrinsically Safe
Conventional Combination Conventional Conventional Rate of Rise
Heat Photoelectric Smoke Photoelectric Smoke and Fixed Temperature Heat
Detector Detector Detector

• Applicable to zone 1 and zone 2 of areas


• with explosion-proof requirement in petroleum and chemical industries

75
Intrinsically Safe Initiating Device

⚫ Reusable button, can be reset manually by special key;


⚫ Plug-in structure.
⚫ Explosion-proof Mark: Exib ⅡCT6
⚫ IP43

DC-9202(IS)
Intrinsically Safe
Conventional Manual Call Point

76
Intrinsically Safe Notification Device

DC-9404(IS)
DC-9404(IS)
Intrinsically Safe Conventional Sounder
Intrinsically Safe Conventional Sounder

• Sound level: 85dB~115dB


• Strobe: Flashing Frequency: 1.4×(1±20%)Hz
• Tone Modification Period:0.7s±20%
• Explosion-proof Mark: Exib ⅡCT6
• IP33

77
Intrinsically Safe Module

• Built-in safety barrier, connect Intrinsically Safe


devices into GST intelligent system.
• Electrically addressing,1 address
• Operating Voltage :Loop voltage:24V
Power voltage:24VDC
• Loop Current : Standby current≤0.5mA;
Alarm current≤5mA
I-9332/I-9333 • Safety Barrier Parameters:
Flame Proof Zone
U0=28V, I0=93mA,
Monitor Interface
L0=4mH, C0=0.083F
• IP65

78
Explosion Proof Detector

⚫ Addressable mode and conventional working mode


optional
⚫ Dust-proof, damp-proof and corrosion-proof.
⚫ Detection Distance : 25m for Level I, 17m for Level II and
12m for Level III.
⚫ IP66
⚫ -20℃~+60℃ ambient, ≤95%RH , non-condensing
DI-9104Exd ⚫ Ex & ATEX
Digital Flame Proof
UV Flame Detector

79
Explosion Proof Detector

⚫ Addressable and Conventional mode optional


⚫ Two sensitivity levels can be set in field
⚫ Maximum monitoring area: 14×100=1400m2
⚫ Maximum width: 14m
⚫ Length of Optical Pathway: 8m~100m
⚫ IP66
⚫ -20℃~+40℃ ambient, ≤95%RH , non-condensing
D-9105RExd ⚫ Ex
Digital Flame Proof
Reflective Beam Detector

80
Explosion Proof Detector

⚫ Addressable mode and conventional working


mode optional
⚫ Dual-band infrared light detection
⚫ Detection Distance:
⚫ Sensitivity Level I: 25m (furthest)
⚫ Sensitivity Level II: 17m
⚫ Sensitivity Level III: 12m
⚫ IP66, -20℃~+55℃ ambient, ≤95%RH , non-
D-9107RExd condensing
Digital Flame Proof Dual
IR Flame Detector ⚫ Ex & ATEX

81
Explosion Proof Initiating Device

⚫ Addressable mode and conventional working


mode optional
⚫ Reusable button, that can be reset manually;
⚫ Electrically addressed by handheld
programmer;
⚫ IP65, -40℃~+70℃ ambient, ≤95%RH , non-
condensing
DI-9204Exd
Digital Flame-proof Manual ⚫ Ex & ATEX
Call Point

82
THANK YOU

83

You might also like