44'-6" GENERAL NOTES :


16'-9" 11' 16'-9"
1. ALL DIMENSIONS ARE IN FEET & INCHES, UNLESS OTHERWISE
30'-6" SPECIFIED.
15'-3" 15'-3" 2. DRAWING SHOULD NOT BE SCALED, FOLLOW FIGURED DIMENSIONS.
PB204 PB204 PB204 3. ANY DISCREPANCY IN DRAWING SHALL BE BRING TO NOTICE OF
6 STRUCTURAL CONSULTANT BEFORE EXECUTION OF WORK.
F
9"x15" 9"x15" 9"x15" N 4. THIS DRAWING SHOULD BE READ ALONG WITH THE RELEVANT F
PB204 PB204 ARCHITECTURAL DRAWING.
13 5. IF THERE IS ANY REVISION IN DRAWING, FURTHER CONSTRUCTION
9"x15" 9"x15" SHALL BE EXECUTED AS PER THE LATEST REVISED DRAWING, ON THE
ISSUE OF LATEST REVISION.

PB203
PB204

9"x15"
9"x15"

PB204
9"x15"
PB203
9"x15"
6. GRADE OF CONCRETE SHALL BE M20.GRADE OF STEEL SHALL BE Fe500

PB201

PB201
9"x12"

9"x12"
16'-9"

10'-9"
PB201
7. CLEAR COVER FOR

9"x12"
FOOTING :2"(50mm)
GROUND BEAM :1 1/2"(40mm)
8' COLUMN :1 1/2"(40mm)
PB204 PB204 BEAM :1"(25mm)
12 SLAB :3/4"(20mm)
PB204 PB204 PB204 9"x15" 9"x15" 8. LAP LENGTH OF BARS : 50Ø, AT COLUMN LAPPING PROVIDE 4"
5

27'-6"
SPACING OF TIES, NO LAPPING ALLOWED AT BEAM-COLUMN JOINT.
9"x15" 9"x15" 9"x15"

PB201
9"x12"
PB201
9. DEVELOPMENT LENGTH (Ld) FOR REINFORCEMENT BARS

9"x12"

5'-6"
IN COMPRESSION : 40Ø
IN TENSION : 50Ø

PB203
PB201

9"x15"
PB203
9"x15"
E 4 10. IN CASE OF BEAM REINFORCEMENT, NO LAPPING SHALL BE ALLOWED E

16'-9"
IN FOLLOWING PLACES
PB204
9"x15"

9"x12" (a) TOP ROD NEAR COLUMN, L/4 ON EITHER SIDES OF COLUMN

PB204
9"x15"
PB201
9"x12"
(b) TOP ROD OF CANTILEVER BEAM ALONG THE LENGTH AND
PB201
9"x12"

ALSO DEVELOPMENT LENGTH, BEYOND COLUMN

55'-412"
11'
5'-112" (c) BOTTOM ROD AT MID SPAN OF BEAM
11. REMOVAL OF SHUTTERING / FORM WORK
PB205
CB1

(a) COLUMN : 24 HOURS


11 (b) BEAM SIDES : 24 HOURS
PB204 PB204 PB204 9"x18"
3 (c) BEAM BOTTOM : LESS THAN 20' SPAN : 14 DAYS
: MORE THAN 20' SPAN : 28 DAYS
9"x15" 9"x15" 9"x15" A1 B1 C1 (d) SLAB : LESS THAN 20'SPAN : 14 DAYS
9"
PB201
PB201

9"x12"
9"x12"

PB202
Y8@6"

9"x12"
: MORE THAN 20'SPAN : 28 DAYS
PLINTH BEAM LAYOUT
PB202

2Y10
9"x12"

LEAVE DOWEL RODS OF HOWEVER 7 DAYS STRENGTH OF CONCRETE SHOULD BE 65% OF THE

6"
11'-3"
Y16@4"FOR STAIRCASE 2Y10 TARGET STRENGTH, TO REMOVE FORM WORK.
TIE BEAM TO DETAIL 12. THIS BUILDING IS DESIGNED FOR GROUND + 1 FLOORS.
SCHEDULE OF PLINTH BEAM DETAILS
D PB204 PB204 PB204 D
2 PLINTH
C/S @ LHS C/S @ MID SECTION C/S @ RHS
9"x15" 9"x15" 9"x15" BEAM
LEGENDS :
PB201
9"x12"

PB201
9"x12"
9" 9" 9"

10'-1012"
PB201
9"x12"

PB201
9"x12"

2Y12 2Y12 2Y12


RHS

PB203 PB203 PB203 PB201


Y8@6" Y8@8" Y8@6"

1'

1'

1'
1
9"x15" 9"x15" 9"x15"
2Y12 2Y12 2Y12
A B C D
LHS

LHS RHS 9" 9" 9"


PLINTH BEAM LAYOUT
SUPPORT DESTINATION 2Y12 2Y12 2Y16
C 0.25 x L2 (OR) L
C
LHS OF TOP STEEL
RHS OF TOP STEEL WHICHEVER IS PB202
LHS OF TOP STEEL RHS OF TOP STEEL Y8@6" Y8@8" Y8@6"

1'

1'

1'
0.25 x L1 GREATER
LAP 50Ø 0.25 x L1 0.25 x L2 LAP 50Ø L

2Y12 2Y12 2Y16 REV NO Date REVISION REMARKS


Ld
LAP 50Ø
0.15 x L2 0.15 x L2
9" 9" 9"
0.15 x L1
0.1 X L1 MIDDLE BOTTOM STEEL MIDDLE BOTTOM STEEL
ER.JAGATHEESH KANNAN, KARUR
L1 L2 2Y12 2Y12 2Y12 PROJECT
FFL CONSULTANT
TYPICAL LAPPING & CURTAILMENT DETAILS OF BEAM PB203

1'-3"

1'-3"

1'-3"
(+10')LVL
Y8@6" Y8@8" Y8@6"
TIE BEAM DETAIL 9"
2Y12 2Y12 2Y12
(+5')LVL G+1 RESIDENTIAL BULIDING ,KARUR
BRICK WORK 2Y16 CLIENT
B SECONDARY BEAM B
TIE BEAM DETAIL
9" 9" 9"
1.5*D- Y8@4"c/c 1.5*D- Y8@4"c/c
1'-3"

Y8@4" 2'
2Y16 2Y16 2Y16
FGL (+0'0") PLINTH BEAM LAYOUT & REINFORCEMENT
DETAIL
PB204 DETAILS
2Y16
1'-3"

1'-3"

1'-3"
Y8@6" Y8@8" Y8@6"
D

60

PLINTH BEAM
Er.Y.BOOPATHI M.E(Struct), M.I.S.T.E,
°

CB01 DETAILS
P.C.C BENT UP HANGER BARS 2Y16 2Y16 2Y16 LICENSED STRUCTURAL ENGINEER-GRADE-1
MAIN BEAM TYPICAL HANGER BAR DETAILS STRUCTURAL
2Y12 CONSULTANT
PYRAMID STRUCTURAL CONSULTANT
COLUMN Contact No : +91 9597691155
9" 9" 9" Mail id :pyramidstrconsultant@gmail.com
TYPICAL WALL SECTION LINTEL BEAM 2Y16 2Y16 2Y16
SUNSHADE LINTEL BEAM Scale 1:150
4Y-10 DRAWN CHECKED APPR3VED
Y8@5"c/c Y8@8"c/c
PB205
A 6" 6" Date 01-06-2022 A
1'-6"

1'-6"

1'-6"
Y8@6" Y8@8" Y8@6"
6"

3"

BT KR YB Paper A3
Size
9" 9"
1'6" 9" BRICK WALL Rev.no R1
2Y16 3Y16 2Y16
TYPICAL SECTION OF LINTEL TYPICAL CUT LINTEL BEAM BEARING DETAIL DRAWING NO:- YB22032-ST03
(03 OF 11)
Sheet.no
CUM SUNSHADE DETAILS