You are on page 1of 1

STAGE:

Kingspan Multibeam rail to Engineer's details


THIẾT KẾ CHI TIẾT/DETAIL DESIGN
Parapet flashing with 150mm sealed butt straps.
Film backed butyl tape applied
over any breaks in supporting secondary
steelwork to give a continuous bearing face NOTE
Air seal - 20x9mm PVC foam tape

3 °
Gun grade sealant to panel joint
inline with internal air seal

60
Self-drilling self tapping primary fixings with a minimum of 16mm
diameter non-ferrous EPDM backed washer
Any joints in the parapet rail to be sealed using
Profiled filler bedded top and bottom on gun grade sealant film backed butyl tape applied
over any breaks in supporting secondary
Site applied LPCB/FM certified PIR insulation board Stitching screws with minimum 14mm diameter non
steelwork to give a continuous bearing face
any gaps filled with fire rated canister insulation ferrous EPDM backed washer fitted at every crown

300

3 °
Air seal - 20x9mm PVC foam tape
Gun grade sealant to panel joint KS1000 RW / LPCB insulated wall panel, vertically laid
inline with internal air seal Gun grade sealant to panel joint
inline with internal air seal

90
Self-drilling self-tapping primary fixings with minimum Site applied LPCB / FM certified PIR insulation board
16mm diameter non-ferrous EPDM backed washer at 1000mm ctrs PVC Membrane Strip any gaps filled with fire rated canister insulation Profiled filler bedded top and bottom on gun grade sealant
Self-drilling self-tapping counter sunk raised Gun grade sealant to panel joint
Air seal - 20x9mm PVC foam tape head high thread fastener at 200mm centres inline with internal air seal Stitching screws with minimum 14mm diameter non
EPDM backed washer fitted at every crown
KS1000 TD / LPCB insulated roof panel Self-drilling self-tapping primary fixings with minimum
Low profile stitching screws with minimum 14mm diameter non 16mm diameter non-ferrous EPDM backed washer at 1000mm ctrs KS1000 RW / LPCB insulated wall panel, vertically laid
ferrous EPDM backed washer fitted at maximum 450mm centres Air seal - 20x9mm PVC foam tape
1.31%

595
4mm butyl rubber sealant Air seal - 20x9mm PVC foam tape Gun grade sealant to panel joint inline with internal air seal

240
AWP Filler bedded on gun grade sealant Kingspan insulated membrane lined gutter Self-drilling self tapping primary fixings with a minimum of 16mm

480
Low profile stitching screws with minimum 14mm diameter non diameter non-ferrous EPDM backed washer
KSD1000 AWP / LPCB insulated wall panel vertically laid ferrous EPDM backed washer fitted at maximum 450mm centres
Verge flashing, with 150mm sealed laps
4mm butyl rubber sealant
Membrane coated galvanised steel flashing, Site applied LPCB / FM certified PIR insulation board

355
any joint sealed with welding strip AWP Filler bedded on gun grade sealant any gaps filled with fire rated canister insulation

0 .7 5 °
PVC Membrane Strip Membrane coated galvanised steel upstand
470 Kingspan Multichannel/Multibeam rails to Engineers details flashing, and joints sealed with welding strip
170 115 185 5
2 0
200
KSD1000 AWP / LPCB insulated wall panel vertically laid PVC Membrane Strip

150
Profiled filler bedded on gun grade sealant
Self-drilling self-tapping counter sunk raised
head high thread fastener at 200mm centres
Self-coring primary fixings
°
KS1000 TD / LPCB insulated roof panel
1 3 7
with washer 1No. per Trough

2 5 0
Multibeam Purlin to Engineer's details

200 860

Air seal - 20x9mm PVC foam tape


Self-coring primary fixings with washer at 500mm Centres
KEYPLAN
Membrane Disk Internal flashing with 150mm overlap
sealed with film backed butyl tape
Kingspan eaves beam to Engineer's details

Kingspan Multibeam purlin to Engineer's details

Kingspan Multicleat

CHI TIẾT SENO D1/ SENO D1 DETAILS CHI TIẾT D2/ D2 DETAILS
1:7 1:7

PVC Membrane Strip

0.7mm Galvanised Plate with Welted Edges Self-drilling self-tapping counter


sunk raised head high thread
fastener at max 200mm centres
KS1000 TD / LPCB insulated roof panel
1.31% 1.31%

DATE DATE
0 .7 5 °

0 .7 5 °

APPROVED BY APPROVED BY

Profiled filler bedded on gun grade sealant Kingspan Company Limited IntES Vietnam Company Limited
Site applied fire rated
canister insulation
Internal ridge flashing with 150mm overlap Self-coring primary fixings
sealed with film backed butyl tape with washer 1No. per Trough

Kingspan Multibeam Purlin to Engineer's details

CHI TIẾT D3/ D3 DETAILS


1:7

01 23.02.22 FOR REVIEW T.N.HOANG L.THE.HOANG D.N.SON


00 25.10.21 FOR REVIEW T.N.HOANG L.THE.HOANG D.N.SON
REV DATE DESCRIPTION DESIGN CHECK APPROVAL
KSD1000 AWP insulated Air seal - 6mm bead
wall panel vertically laid of gun-grade sealant Stanchion Horizontal sheeting rail
Sheeting rail Corner stub CLIENT:
Air seal - gun-grade
sealant at male panel joint Air seal - 6mm bead
Corner column Kingspan Company Limited
Optional internal closure Lot B4, D1a Street, Phu My II Expansion IP, Phu My District,
Air seal - Vapourflex of gun-grade sealant
flashing to mask
sealant applied over insulation from view Horizontal sheeting rail Ba Ria-Vung Tau Province, Vietnam
Internal corner flashing
joints in supports Gun applied fire
rated canister Air seal - 6mm bead
Air seal - 6mm Ø bead
insulation of gun-grade sealant
of gun-grade sealant CONSULTANT
Drip flashing Closure flashing with 4mm Ø butyl IntES Vietnam Company Limited
lap joints air sealed rubber sealant 3rd floor, SB Building, 140 Bach Dang Street
4mm Ø butyl
PIR insulation board Ward 2, Tan Binh District, Ho Chi Minh City, Vietnam
Air seal - 6mm bead rubber sealant low profile fastener
of gun-grade sealant The gap between the
panel and the drip External corner flashing PROJECT:
AWP joint filler and flashing needs to be Kingspan Vietnam Greenfield
gun-grade sealant 6mm minimum
KSD1000 AWP insulated Gun applied fire
wall panel vertically laid Air seal - gun-grade Drip flashing rated canister
sealant at male insulation 4mm Ø butyl DWG. TITLE: NHÀ SẢN XUẤT CHÍNH / MAIN BUILDING
Air seal - continuous bead Edge of vertical rubber sealant
panel joint
of gun-grade sealant sheeting site cut
CHI TIẾT NHÀ CHÍNH 02/ MAIN BUILDING DETAILS 02
CHI TIẾT LIÊN KẾT TẤM CHI TIẾT ỐP CHÂN TƯỜNG CHI TIẾT ỐP GÓC SCALE SHEET
ORDER No. SUB DRAWING NUMBER
1:5 1:5 1:5

84T.21019 00 1141606 As 1
indicated

© Copyright IntES Co., Ltd.


All rights reserved. No part of this publication may be reproduced or transmitted in any form or by any means without permission of the publisher.