You are on page 1of 2

Installation Guide

Solenoid Valve
Type EVR 25
032R9523

032R9523
Refrigerants Max. working pressure: 500 psig (35 bar)
R22/R407C, R404A/R507, R410A, R134a, R407A, R23.
For other refrigerants, please contact Danfoss. Max. test pressure: 650 psig (45 bar pe)

Max. opening diff. pressure (MOPD): a.c. 350 psig (24 bar pe)
d.c. 205 psig (14 bar pe)

Refrigerant temperature: Min. -40 °F (-40 °C) Max. 220 °F (105 °C) Ambient temperature: Min. -40 °F (-40 °C) Max. 122 °F (50 °C)

Mounting position Valve and coil


A32F542.11
Danfoss

EVR 25 Conduit boss Junction box

MADE IN DENMARK

Coil 018F4100

Type BJ024CS

24 V 60 Hz 14 Watt

24 V 50 Hz 14 Watt

Soldering of copper connections Identification of coil and valve

Max. 150 °C (300 °F)

Code no.
Max. 700 °C (1300 °F) Type

V +10 / -15 % (a.c.) MADE IN DENMARK

Coil 018F4100

Frequency
Type BJ024CS

24 V 60 Hz 14 Watt

24 V 50 Hz 14 Watt

Power

Caution
Tightening torques
Wiring and fusing (when used) must comply with
prevailing local and national wiring codes and
ordinances.
A
Warning
Never switch on power to the coil when the coil is
dismounted from the valve. Otherwise the coil may
be damaged and there is risk of injuries and burns.

Transformer selection

Inrush Holding
C Coil
[Volt-Amp] [W] [Volt-Amp]
208 – 240 V 50 Hz 49 14 28
[Nm] [kpm] [ft-lbs]
230 V 50 Hz 49 17 28
12 1.2 9
110 V 50 – 60 Hz 49 16 28
50 5.0 37
120 V 60 Hz 49 15 28
30 3.0 22.5 24 V 50 – 60 Hz 49 14 28

© Danfoss A/S (AC-MCI sw) 2013-08 DKRCC.PI.BB0.P4.22 / 520H8062 1


Valve and coil construction

A32H7.11
Danfoss

Cut-away
32F521.13
Danfoss

2 DKRCC.PI.BB0.P4.22 / 520H8062 © Danfoss A/S (AC-MCI sw) 2013-08