You are on page 1of 3

Dd

D
h
DENSITY OF OIL
DENSITY OF WATER
C
I
A
L
W
d
VERTICAL RATE OF RISE OF OIL DROPLET IN WATER, V t
VERTICAL RATE OF RISE OF OIL DROPLET IN WATER, V t
q
Ac
Vh
Vh
FSC
Vh/Vt
RULES
dmin
dmax
Wmin
Wmax
D:W RATIOmin
D:W RATIOmax
W
Ac
Vh
Vh/Vt
Ft
F
L

FINAL DIMENSION OF SEPARATOR


L
W
d
UOM
DIFFERECE IN DENSITY BETWEEN WATER & OIL 137 KG/M³
DIAMETER OF OIL DROPLETS 150 MICROMETERS
DYNAMIC VISCOSITY OF WATER 0.001348 PASCAL-SECOND
860 KG/M³
997 KG/M³
RUN OFF COEFFICIENT OF MATERIAL 0.9
RAIN INTENSITY 40 MM/HR.
CATCHMENT AREA 2250 SQM
LENGTH OF RUN OFF CONCRETE 50 M
WIDTH OF RUN OFF CONCRETE 45 M
DEPTH OF SEPARATOR (ASSUMED) 1.3 M
4.48654673590505 M/HR
0.0747757789317507 M/MINUTE
RAIN WATER MAXIMUM RUN OFF 1.35 M³/MIN
CROSS SECTIONAL AREA OF SEPARATOR IN SQM
HORIZONTAL VELOCITY 1.12163668397626 M/MINUTE
HORIZONTAL VELOCITY 0.91 M/MINUTE
SHORT CIRCUITING FACTOR 1.2
RATIO 12.1697160898929

MINIMUM DEPTH OF SEPARATOR 1M


MAXIMUM DEPTH OF SEPARATOR 2.4 M
MINIMUM WIDTH OF SEPARATOR 2M
MAXIMUM WIDTH OF SEPARATOR 6M
MINIMUM DEPTH TO WIDTH RATIO 0.3
MAXIMUM DEPTH TO WIDTH RATIO 0.5
WIDTH OF SEPARATOR 2.6 M
CROSS SECTIONAL AREA OF SEPARATOR IN SQM 3.38 SQM
HORIZONTAL VELOCITY 0.399408284023669 M/min
RATIO OF HORIZONTAL VELOCITY TO VERTICAL VELO 5.34141255002126
TURBULENCE FACTOR 1.12
DESIGN FACTOR 1.344
LENGTH OF SEPARATOR 9.33251600739714 M

LENGTH 9.33251600739714 M
WIDTH 2.6 M
DEPTH 1.3 M
Vh/Vt TURBULENCE FACTOR, Ft
20 145
15 137
10 1.27
6 1.14
6 107

Vt=1.962*10^(-9)*Dd*D^2/h

C*I*A/60000

15Vt OR q/Ac

Vh/Vt

d/D:W RATIOmax
d*W
q/Ac
Vh/Vt
BY INTERPOLATION
Fsc*Ft
F*(Vh/Vt)*d