2.3. Operating Instructions GM 1502 Microprocessor
The GRAMmatic 1502 contol panel is
equipped. with a microprocessor. The micro
processor monitors and adjusts the operation of
the compressor, and facilitates communication
between operator and the machine.
Monitoring
‘The microprocessor monitors and reacts to
‘error conditions in the compressor. The
following conditions are monitored:
— Suction temperature
~ Suction pressure
~ Discharge pressure
= Oil differential pressure
Pressure drop over oil fier
= Oil temperatures
~ Oil level in oll separator
— Pressure pipe temperature
IF the threshold limit value of the set point is
exceeded, possibly with a dolay for the
individual operating parameter, a message will
be sent either through an alarm or a cutout (the
compressor will slop).
Alarm
An alarm message means that a preset limiting
value has been exceeded, and something
might go wrong shortly. Le. a warning.
In the event of an alarm the message *P1
ALARM" will appear in the upper left-hand
corner followed by the operaling parameter
causing the alarm.
The alarm and the time of alarm will be stored
in the memory of the control, and can be read
out if the computer is connected to a main
‘control unit 7
An alarm is reset by pu: the (=
Clear Alarm; F6), but it will appear again
immediately, if the error causing the alarm is
not removed from the system.-~-~ v= +
Cutout
Cutout means that an operating situation has
arisen which requires the compressor to be
slopped.Cutout conditions are shown in the
same way as alarms, and are to be resel at the
before the compressor can be
restarted. If a picture with the operating
parameter concerned is not already shown in
the display, there will automatically be scrolled
to a display picture showing the operating
parameter together with a "frozen" cutout value.
Emergency stop
In the event of an emergency stop the
compressor and the oil pump will stop
immediately, but it will not prevent the next
slave from starting.
‘Aller deactivation of the” emergency slop,
must be keyed before the compressor
can be restarted.