13
2.4. Maintenance
This section provides instructions for normal
maintenance, a recommended maintenance
programme, troubleshooting and correction
guides, typical wiring diagrams and typical P
and I diagrams.
Warning! This section must be read and
understood before attempting to perform
any maintenance or service to the unit.
Normal Maintenance Operations
When performing maintenance you must take
several precautions to ensure your safely:
1. Ifunitis running, press stop koy.
2. Disconnect power from unit before
performing any maintenance.
3. Wear proper safely equipment when com-
pressor unit is opended to atmosphere.
4. Ensure adequate ventilation.
5. Take necessary safety precautions
roquired for the refrigerant being used.
Compressor Shutdown and Start-up
For seasonal or prolonged shutdowns the
following procedure should be followed:
1. Press stop key to cease operation.
2. Open disconnect switches for compressor
motor and oil pump starters.
3. Turn off oil heater circuit breaker.
4, Close suction and discharge service
valves, also liquid injection and
economizer service valves. Altach
CLOSED TAGS.
5. Shut off cooling water supply valve to oil
cooler, if applicable. Attach CLOSED TAG.
6. Protect oil cooler from ambient
temperalures below freezing or remove
water heads.
To start up afer a seasonal or prolonged
shutdown, the following procedure should be
followed:
1. Any water necessary for the operation of
the system that may have been drained or
shut off should be restored or turned on. If
cooler heads were removed, reinstall and
remove tags. sees
2 Close disconnect swilches for
compressor, motor, and oil pump starters.
8, Tum on oit circuit breaker.
4, Perform checkpoints on prestart check list,
then start unit.
General Instructions for Replacing
Compressor Unit Components
When replacing or repairing components which
are exposed to refigerant pressure, proceed
as follows:
4. Push stop key on control panel to shut
down unit.
2. Open disconnect switches for compressor
and pump motor starters.
3, Close suction and discharge valves, also
liquid injection, and economizer valves, if
applicable,
4, Vent separator to atmospheric pressure
using valve located on top of separator,
drain oil, if necessary.
5, Make replacement or repair, and add oil, if
drained.
6. Pressurize unit and leak test.
7. Evacuate unit.
8 Open suction and discharge service
valves, also liquid injection and
economizer service valves, if applicable.
9. Close disconnect switches for compressor
and oil pump motor starters.
10, Unitis ready to put into operation.
11. Perform checkpoints on prestart check list,
then start unit.