You are on page 1of 7

2004 35th Annual IEEE Power Electronics Specialists Conference Aochen, Germany, 2004

Mitigation of Voltage Swells by Static Series Compensator


Hilmy Awad, Student Member, IEEE Frede Blaabjerg, Fellow, IEEE

Dept. of Electric Power Eng. Institute of Energy Technology


Chalmers University of Technology Aalborg University
SE-41296 Gothenburg, Sweden DK-9220 Aalborg East, Denmark
Email: hilmy.awad@elkraft.chalmers.se Email: tbl@iet.aau.dk

Abstract- Swells and overvoltages can cause overheating, Basically, the SSC draws active power from its energy
tripping or even destruction of industrial equipment such as storage capacitor (ESC) to restore the load voltage. The
motor drives and control relays. This paper investigates the required active power depends mainly on the
possibility of employing the Static Series Compensator characteristics of the encountered dip and the load
(SSC) to mitigate voltage swellslovervoltages. I n the case of
voltage swells, active power may be drawn from the grid current. However, in the case of voltage swells, some
into the energy-storage capacitor (ESC) of the SSC, amount of active power may be drawn from the grid into
depending on the load current and the S S C impedance. This the SSC. Thus, the SSC design and the control should be
active power may overcharge the ESC. Two possibilities to done carefully in order to take this into account. In
overcome this situation are explored in this paper: I) if the literature concerning the SSC, the focus has been given to
dc-voltage of the ESC is lower than a predetermined voltage the operation of the SSC under voltage dips and distorted
level, the active power is employed to charge the ESC to this
voltage level; 2) otherwise, the overvoltage protection of the utility. In contrast to this, this paper investigates the
S S C must operate. This paper also applies an overvoltage operation of the SSC when a voltage swell is detected in
protection scheme based on a combination of a de resistor the grid side. The reminder of this paper is arranged as
with a chopper and the valves of the SSC. The design of the follows: Section 11 explains the operational principle as
de resistor is discussed. A 10 kV SSC experimental setup is well as the exploited controller of the SSC. The
exploited to carry out experiments in the case of balanced consequences of voltage swells on the SSC are explored
and unbalanced voltage swells at the grid side.
Index Term- Power Quality, Series-Connected Converters, in Section 111. Simulation results are presented in Section
Voltage swells [V. Section V shows the experimental verification of the
system performance. The overvoltage protection scheme
1. INTRODUCTION is discussed in Section VI and guidelines for designing
the dc resistor using a chopper are given.
USTOMERS of electric energy place their demands
C on the supplied voltage by utilities to be more or less
ideal. By definition, ideal sinusoidal voltage waveform
11. OPERATIONAL PRINCIPLE OF SSC
has the characteristics: constant magnitude at the required A. Description of SSC
level, constant frequency and balanced in the case of
The basic function of the SSC is to dynamically inject a
three-phase operation. Naturally, this is not always
controlled voltage to keep the load voltage constant. An
possible because of normal system variations and due to
idealized model of the SSC and the grid is shown in
the unavoidable incidents that temporarily can affect the
Fig.la where the SSC is modeled as an ideal voltage
operation such as short-circuit faults. For instance,
source. Fig.lb illustrates a vector diagram when the grid
switching off large loads and switching on capacitor
voltage up has a voltage dip with a phase angle jump.
banks may cause voltage swelVovervoltage at the grid
From Fig.lb, it is clear that the active power is drawn
voltage. In the standard IEEE-I 159-1995, the definition
from the SSC to the load. Fig.lc shows a more detailed
of voltage swell is quoted: A voltage swell is an increase
single-phase model of a distribution feeder with an SSC,
in the RMS voltage above 1. I pu at the power frequency
where the grid voltage us, the SSC voltage uml and the
for duration from 0.5 cycle to I minute. Swells and
load voltage uL are in series. From Fig.] the load voltage
overvoltages can cause overheating, tripping or even
destruction of industrial equipment such as motor drives vector is expressed as gL = 9, +g,nl. Here it is to be
and control relays. Many power quality surveys have noted that small-case letters denote time variables and
been made in order to check the load immunity against capital letters denote phasors. For simplicity, only details
power system disturbances [2, 31. From those surveys, it of a single-phase of the SSC are depicted in Fig.1~.The
can be stated that the voltage swells are experienced in main components of the SSC are: 1) voltage source
the power systems locally or remotely. The number of converter (VSC), 2) energy storage, 3) output LC-filter,
voltage swell events per year is naturally random but 4) injection transformer and 5) bypass switch (thy). As
from the statistics presented in [2] it can be concluded shown in Fig.lc, the LC-filters consists of a series
that not less than 165 eventdyear have been recorded. inductor with an inductance LF and a resistance RF and a
The duration of the recorded swells varies from one shunt capacitor with a capacitance CF.
fundamental cycle to 8 hours. The static series
compensator (SSC) is a power electronic apparatus that
has been used for the mitigation of voltage dips [4,5].
0-7803-8399-0/04/$20.00 02004 IEEE. 3505

Authorized licensed use limited to: UNIVERSIDAD POLITECNICA SALESIANA. Downloaded on July 04,2022 at 23:13:37 UTC from IEEE Xplore. Restrictions apply.
2004 35fh Annual IEEE Power Elecrronics Specialists Conference Aachen, Germany, 2004

compensate for the voltage drop across the LC output


filter [6]. The reference of the injected voltage is
calculated by subtracting the measured grid voltage at
Grid ssc Load . .
PCC from the reference of the load voltage;
g,nj=gL -up, where g, and are the grid voltage at
PCC and the reference of the load voltage, respectively. It
is to be noted that if the transformer is assumed ideal and
has 1:1 turns ratio, the injected voltage will be the same
as the voltage across the capacitor of the LC-filter shown
in Fig.1~.In the case of voltage dips in the grid, the
injected voltage is positive and the SSC should provide
this voltage rapidly such that the load does not sense any
dips. The equations of the controller have been obtained
as:
Voltage Controller Outer Loop

Current Controller Inner Loop

where Ldqand id'


are the required reference currents
and voltages to track the reference of the injected voltage.
The gains K , and K , are the dead-beat gains calculated
in terms of the filter parameters and the sampling time T,;
K,=C,/T,, K , = L , / T , + R , / Z . In ( I ) and (2), j
(4 means 9O0-phase shift which implies a cross coupling
Fig. 1. Operation principle of static series compensator (SSC): a) simplified between the d- and the q-components. A block diagram
circuit diagram of SSC b) vector diagram in case of dip with phase jump, c)
detailed single-phase model.
of the DVC is depicted in Fig. 4. To stabilize the system,
the gains K , and K , are altered from the dead-beat gains
Measured voltages and currents are the inputs to the
control unit in order to generate the reference voltage of by the factors K., and Kps, respectively. Thus, selecting
the VSC, when the measured quantities differ from the the values of the two factors K., and K p determines the
default settings. The voltage references are input to the system stability. In this paper, the factors K., and KpI are
PWM modulation unit to generate the modulating signals selected as 25% and 65% of the deadbeat gains. This is
for the valves of the VSC. The energy storage provides based on the stability analysis of the system, presented in
the required power to compensate for voltage dips. [71.
Installing a filter (normally LC-filter) reduces the dv/dt
effect on the windings of the injection transformer and it 111. CONSEQUENCES OF VOLTAGE SWELLSON ssc
is necessary to convert the pulse-modulated voltage of the A simplified circuit diagram for the SSC is depicted in
VSC into a sinusoidal voltage. The filtered voltage is Fig.3, where RLF+jXLFis the impedance of the LC-filter
injected into the distribution system by the series- inductor and RLT+jXLTis the impedance of the series
injecting transformer. The bypass switch is normally transformer. The voltage swell is an increase in the RMS
closed in order to short-circuit the SSC. In Fig.lc the voltage of the grid, which implies that the reference of the
controlled voltage by the SSC is denoted as U,.? The used injected voltage by the SSC is negative because E, is
control algorithm throughout this paper is the double
vector control algorithm [6],which is explained in the greater than E;. Hence, the direction of active power
following. flow may be reversed and overcharge the Energy Storage
Capacitor (ESC). A vector diagram in the case of voltage
B. Double Vector Control
swell is shown in Fig.5. Compared to the vector diagram
The double vector controller (DVC) is a cascade in Fig. 1b, the injected active power in this case is into the
controller using two vector-control loops 1 and g that SSC. In practice, the leakage impedance of the injection
track the reference of the injected voltage as well as to transformer causes a voltage drop in addition to the

3506

Authorized licensed use limited to: UNIVERSIDAD POLITECNICA SALESIANA. Downloaded on July 04,2022 at 23:13:37 UTC from IEEE Xplore. Restrictions apply.
~

2004 35th Annual IEEE Power Electronics Specialisfs Conference Aochen, Germany. 2004

voltage drop caused by the LC-filter as shown in Fig. 2.


In steady-state basis, the reference of the injected voltage,
is computed as:
U,",= A!L = U , -Ug (3)
From Fig.3, the output voltage ofthe SSC is

+r
U = AC- ~ ( R L +LYLF)+!,(RLT
- F + LYLT)} (4)
where:
Resistance of the injection transformer, Fig. 1.Measured signals for applying double vector wntrol of SSC.
RT:
XLT: Leakage reactance of the injection transformer, RFS~LF R T , XLT

RF: Resistance of the LC-filter,


XLF: Leakage reactance of the LC-filter, u -
- --I -'"I

1: Current through the LC-filter inductor,


Xu:
L: Current through the LC-filter capacitor, -
L: Load current. Fig.3. Simplifiedsingle line diagram of static series compensator in steady
lfthe capacitor current 1, is ignored, the reference voltage
of the VSC is simplified to:
- voltaee
state during - swell.
U = W - - I ( R L F + RLT)I-.WLF + x L T ) l (5)
Equation ( 5 ) shows that even in the case of a voltage
swell, the reference voltage of the VSC may be positive
or negative depending on: 1) the characteristics of the
voltage swell; 2) the impedance of the series injection
transformer and the LC-filter. Being positive means that
the SSC is delivering active power to the load and the
ESC discharges. If the reference voltage of the VSC is
negative, this indicates that the grid is feeding active Fig. 4. Block diagram of double vector control algorithm
power to the SSC and the ESC is charged unless the
overvoltage protection is triggered. The phase of the grid
voltage may jump during the voltage swell either lagging
or leading the phase of the load voltage. A case of a
voltage swell with a lagging phase jump is shown in
Fig.5 while Fig.6 displays the case of leading phase jump.
The amount of active power that can be exchanged
during the voltage a swell with a lagging phase jump is Fig.5. Vector diagram of static series compensator performance in case of
voltage swell associated with phase angle jump.
calculated in pu (rated power of the load is taken as a
base) as:
en, =COS($)-(I + AU)COS($- 6) (6)
In the case of a voltage swell with a leading phase jump,
the active power is obtained as:
P,", =cos($) - (I + AU)cos($ + 6) (7)
where $: Load power factor angle,
6: Phase angle jump of the voltage swell, Fig.6. Vector diagram of static series compensator in case of voltage swell
I+AU Voltage swell in pu. associated with leading phase angle jump.
From (6) and (7), it is noted that the injected active power
depends on the load power factor, the voltage swell IV. SIMULATION
RESULTS
magnitude and the phase angle jump of the grid voltage
A PSCADlEMTDC model has been designed to simulate
during the swell. If the phase of the grid voltage does not
the system shown in Fig. 2 . The load is modeled as a
jump due to the swell; 6 = 0, the expressions in (6) and
resistive load of 20 a.A case of IO % three-phase
(7) are reduced to P,, = -AUcos($). The energy
balanced swell is made for a 100 ms duration. The
storeddelivered by the ESC is obtained as: EESC=
response of the SSC is depicted in Fig.7. Fig.7a shows
P,n,*t,w.l~,where tswcllis the swell duration. Hence by the
the three-phase voltage of the grid at the PCC where at 40
aid of (6), (7) and the expected duration of the voltage
ms the voltage swell starts and lasts for 100 ms. The SSC
swell, the size of the energy storage can be designed.
injects the correct voltage as displayed in Fig.7b to keep

3507

Authorized licensed use limited to: UNIVERSIDAD POLITECNICA SALESIANA. Downloaded on July 04,2022 at 23:13:37 UTC from IEEE Xplore. Restrictions apply.
2004 351h Annuul IEEE Power Elecrronics Speciulisrs Conference Auchen. Gerrnuny, 2004

the load voltage constant (Fig.7~)The dc-voltage of the


SSC drops during the swell (Fig.7d) because the voltage
swell is not high enough to make the reference injected
voltage by the SSC negative. The same performance is
noticed when a 15% balanced voltage swell is made as
shown in Fig. 8. Also a case of unbalanced swell is
presented in Fig.9. A hypothetical case with 50% voltage a
swell for 13 cycles is simulated and shown in Fig.10 to
show the operation of the overvoltage scheme. In this
case the load resistance is decreased to 5 R and the
voltage swell is very high, which causes the ESC to
overcharge during the swell. When the dc-voltage
increases to 1.05 pu, the overvoltage protection operates
to prevent the ESC from overcharging. Details regarding
the overvoltage protection are given in Section VI.

V. EXPERIMENTAL
VERIFICATION
Appendix A provides the specifications for the DSP
controlled IO kV SSC platform used for this work. This
experimental setup has been built at the Institute of
Enerm Technolow. Aalbore University. Denmark 181.

(d) (d)
Fig.9. Simulated unbalanced 10 % Fig.10. Simulated balanced 50 %
20 %, 30 % voltage swell: a) grid swell: with resistive load: a) grid
voltage, b) injected voltage, c) load voltage, b) injected voltage, c)
voltage, d) dc-voltage. load voltage, d) dc-voltage.
%- The medium voltage prototype SSC was fed with a
programmable California Instruments Power Supply at
380 V, which was then fed into a distribution transformer
to create the IO kV line voltage. Three specially made 67
kVA 0.29 kV/2.9 kV single-phase series injection
transformers are used to series connect the SSCis 200
kVA low voltage inverter to the system. The load voltage
was stepped down using another distribution transformer
to allow low voltage linear and non-linear loads tn be
utilized. The dc-bus of the inverter is charged to 600 V
using a unidirectional dc supply, which provided 4680 J
of energy in the 26 mF of dc capacitors for transient use
in the SSC sag ride-through capabilities An Analog
Devices AD21062 floating-point Sharc DSP was used to
implement the DVC with the PWM signal generation for
the six IGBT phase-legs created using a Siemens SAB
8OC167 Micro Controller. The medium voltage supply
and load voltages required by the controller were
Fig.7. Simulated balanced 10 % Fig. 8. Simulated balanced 20 % measured with ABB resistive voltage transducers. The
voltage swell with resistive load: voltage swell with resistive load
a) grid voltage, b) injected a) grid voltage, b) injected
injected voltage is measured by LV 25-P/SP2 voltage
voltage, c) load voltage, d) dc- voltage, c) load voltage, d) dc- transducer. The grid current at low voltage side of the
voltage voltage. transformer is measured by LT 2OO-S/SP44 LEM current
transducer. During the experiments, the ESC was fed by a

3508

Authorized licensed use limited to: UNIVERSIDAD POLITECNICA SALESIANA. Downloaded on July 04,2022 at 23:13:37 UTC from IEEE Xplore. Restrictions apply.
2004 35th Annual IEEE Power Electronics Specialists Conference Aachen, Germany, 2004

separate dc source and thus the dc-voltage was stiff and


fixed to 0.8 pu. A three-phase resistive load of 20 R is,
connected downstream the SSC. Experimental results
with balanced dips of I O %, 20 % and 30 % are shown in
Fig.11, Fig.12 and Fig.13, respectively. Fig.14 shows the
case of unbalanced voltage swell where the voltages of
the supply are programmed to have I O %, 20 % and 30 %
voltage swell. As it can be noticed from Fig.1 I , Fig.12,
Fig.13, and Fig.14, the SSC can keep the load voltage
constant in all the measured cases. Not only this, but also
the transient performance of the load voltage is
satisfactory.

VI. OVERVOLTAGE PROTECTION SCHEME


If the dc-voltage of the SSC exceeds a predetermined
voltage level, the SSC should be protected against the
overvoltage. This overvoltage protection can be made
when the SSC is on-line or off-line depending on the
value of the measured dc-voltage. For instance, if the dc-
voltage reaches a value in the middle of the nominal
voltage and the maximum allowable voltage, the on-line
overvoltage protection should be triggered. The off-line *I m D .
1 m ,m ,* I
1o
Time Imsl T h e 1161
protection is triggered if the dc-voltage exceeds its (C) (c)
maximum allowable voltage. An illustration of the zones Fig.13. Measured balanced 30 % Fig 14 Measured unbalanced 10
of the overvoltage protection is shown in Fig.15. In voltage swell with resistive load: %, 20 %, 30 %voltage swell with
a) grid voltage, h) injected resistive load a) grid voltage, b)
Fig.15 the zone of the on-line protection is placed voltage, c ) load voltage. injected voltage, c) load voltage
between the nominal dc-voltage UdcNOM and the
The zone of the off-line protection is located between the
predetermined on-line protection voltage level U,. p'
maximum of the dc-voltage U,,,, and the setting of the
on-line protection Uonp
A. On-line protection
If the SSC is required to be in service during a voltage
swell, the overvoltage protection is realized on-line by
using a shunt resistor across the dc link together with a dc
chopper. A single-phase diagram of the overvoltage
protection scheme is shown in Fig.16. The dc chopper is
enabled when the dc-voltage exceeds a certain voltage
level (such as Uons in Fig.15). This voltage level is
determined by the voltage that the SSC valves can
withstand due to the voltage swell. If the dc chopper is
closed (on-state), the dc resistor dissipates the energy
excess in the dc capacitor. In other words, the dc
capacitor will discharge through the dc chopper and the
resistor.
B. Off-Iine protection
Off-line protection is realized by turning on the thyristor
. . pair thy on the line side ofthe SSC (Fig.16) as well as the
I
Tme 1ml
:
m e * m s , - , m m , m a m I .
) ., ,e 1o ,-l
T i m Im1
upper or the lower IGBTs in each phase leg of the VSC.
(C) (C)
Fig.ll.Measured balanced 10 % Fig.12.Measured balanced 20 %
Turning on the upper IGBTs and turning off the lower
voltage swell with resistive load: voltage swell with resistive load: IGBTs or vice versa interrupts the dc current and blocks
a) grid voltage, b) injected a) grid voltage, h) injected the dc-voltage. It is worth to note that turning on the
voltage, c) load voltage. voltage, c) load voltage. thyristors only is not sufficient to protect the VSC
because the thyristors will short-circuit the injection
transformer and the VSC.

3509

Authorized licensed use limited to: UNIVERSIDAD POLITECNICA SALESIANA. Downloaded on July 04,2022 at 23:13:37 UTC from IEEE Xplore. Restrictions apply.
2004 35lh Annual lEEE Power Electronics Spcialisls Conference Aochen, Germany, 2004

Idiwh: Initial discharging current;


tdj& Discharging time.

To clarify the significance of (8) and (9), a design


example is given here. A prototype SSC is under
development at the Department of Electric Power
Engineering, Chalmers University of Technology,
Sweden (in another project by another student). The
relevant data ofthis prototype is given in TABLE 1.
TABLE 1. Prototype SSC under consmaion.
Converter Model Danfoss VLT 5052 [9]
U0"J 700 v
&.NOM 600 V
Time [ms] Idirch 90 A
cdc 4.1 mF
Fig.15.Zones ofon-line and off-line overvoltage protection of SSC.

The discharging time tdirch is selected as R period of the


fundamental frequency (IO ms). This is due to the fact
qi&J that the switching frequency of the chopper is designed as
50 Hz and the duty cycle is 50 %. Thus, the discharging
o f the dc capacitor is assumed to be complete within one
switching cycle of the chopper. Applying (8) and (9)
with the data given in TABLE I and taking the
discharging time fdirrh as R period of the fundamental
frequency (IO ms) yields:
R,i.= 7.7 R
R,, = 13.8 R.
Protection Here it is worth to mention that the proposed value of the
Fig. 16. Overvoltage protection scheme of SSC. resistance by the manufacturer [9] is 12 R , which
In this case the energy stored in the capacitor of the VSC belongs to the range R,i.<RCh.,< R-.. A resistor of 9 R
will circulate a high current through the valves of the resistance was designed and used in the SSC prototype
VSC, which may he dangerous as well. given in TABLE I, which shows the significance of (8)
and (9).
C. Design of de resistor (RrhoJ
The resistance used with the chopper should satisfy two VII. CONCLUSIONS
main requirements: 1) the discharging process of the dc In this paper, the static series compensator (SSC) has
capacitor to the rated dc-voltage should be made in a shown the ability to compensate for voltage swells at the
reasonable time; 2) the initial discharging current should grid side. The voltage swell characteristics and loading
not exceed the maximum allowable current of the conditions are the factors that determine whether the
chopper. Fulfilling the first requirement obtains the energy storage capacitor of the SSC will charge or
maximum resistance value while the second requirement discharge during a voltage swell. If the case is that the
results in the minimum value. Consequently, the value of energy storage capacitor will charge, the charging process
the resistance (Rchap) should be within the may be allowed until reaching a predetermined dc-
R,,.<Rch.,< R,,. The minimum value of the resistance is voltage and then the overvoltage protection must operate.
obtained as: Overvoltage protection of the SSC can be made on-line
%in = u o n g Ildisch (8) or off-line depending on the reached level of the dc-
while the maximum value of the resistance is obtained as: voltage. The on-line protection is based on switching a
='disch '(cdc In(Udc-max lUdc-NOM)) (9) resistor via a dc-chopper to dissipate the energy excess in
the dc-capacitor. The off-line protection is triggered if the
where
dc-voltage exceeds its limit and hence the SSC should be
UonJ: Value of the dc-voltage, which triggers
bypassed. Design guidelines for the dc-resistor used with
the on-line protection;
the chopper are given and verified by an example of a
Udc-NoM:
Nominal dc-voltage;
prototype SSC.
C,: Energy-storage capacitor;

3510

Authorized licensed use limited to: UNIVERSIDAD POLITECNICA SALESIANA. Downloaded on July 04,2022 at 23:13:37 UTC from IEEE Xplore. Restrictions apply.
2004 35th Annual lEEE Power Electronics Specialists Conference Aachen. Germany, 2004

VIII. ACKNOWLEDGMENTS [9] Danfoss Design Guide for Frequency Conveners VLT 5000,
w.Danfoss.com, November 26,2003.
The authors would like to thank Hans Nilesen for his help!
with the experimental setup at Aalborg University,
Denmark. Thanks go to Massimo Bongiorno for APPENDIX A: SYSTEM DATAFOR TEST SETUP
providing the data of the SSC he builds at Chalmers TABLE. 11. SYSXMPARAMETERS OF SSC.
Universitv. Sweden. I ri. nnnv

Ix.REFERENCES
IEEE standard dictionay of electrical and electronics terms, 6’h
edition, IEEE Std 100-1996, IEEE, New York, 1997.
D.S. Don; M.B. Hughes, T.M., Gruzs, R.E. Jurewicz, J.L., LC-Filter
McClaine, i Interpreting recent power quality surveys to define the
electrical environmen1,i IEEE Trons. on lndusny Applrcalions,
vol. 33, no. 6, pp. 1480-1487. 0.2 M V A
D. 0. Koval, R.A. Bocancea, K. Yao, M.B. Hughes, icanadian Grid 0.4 k V
national power quality survey: frequency and duration of voltage 50 Hz
sags and surges at industrial sitesi, IEEE Trans. on lnduslry TABLE. 111. PARAMETERS OF ~NJECT~ONTR~NSFORMER
M
Applimlions, vol. 34, no. 5, pp. 904.910. ssc.
N. H. Woodley; S . Middlekauff: A. Sundaram, i Dynamic Voltage lJI 2.9 k V
Primary Voltage
Restorer Demonstration Project Experiencej in Proc of the SI”
Annuol Power Drsrrlbution Conference,The University of Texas,
Secondary Voltage U, 0.29 k V
Austin, Oct. 19-21,1998 Rated M V A Ssc 0.067MVA
P. K a n a D. Dahler; Amhof, H. Gruning, i Power Supply Quality Short-circuit Impedance zsc 0 . 0 5 ~ ~
Improvement with a Dynamic Voltage Restorer (DVR),i in Prm. TABLE. IV. STEP-UP (Y/A) TRANSFORMER IN TEST-SEI”.
of rhe Applied Power Eleclrronrcs conference and Erposition Primary Voltage 0.4 V
(APEC), 1998, vol. 2, pp. 986-993. Secondary Voltage U2 IO k V
H. Awad, J. Svenssan, iDouble Vector Control for Series
Rated M V A SSC 0.05 M V A
Connected Voltage Source Conveners,i in Proc of (he IEEE
Power Engineering Sociery WiMer Ueeling 2002, vol. 2, pp. 707- Short-Circuit Impedance Zsc 0.03 pu
112. TABLE. V. STEP-DOWN(b/Y) TRANSFORMERlNTEST-Sl3UP.
H. Awad, ivector Control of Static Series Compensator for Primary Voltage U, 10 v
Mitigation of Voltage Dipsi, Licentiate Thesis, Depanment of Secondary Voltage U2 0.4 k V
Electric Power Engineering, Chalmers University of Technology, Rated M V A SSC 0.05 MVA
Gothenburg. Sweden, April 2002 Short-circuit Impedance Zsc 0.036~~
J. G . Nielsen, iDesign and Control of a Dynamic Voltage
Res1orer.i Ph.D Thesis, Institute of Energy Technology, Aalborg
University, 2002. ISBN: 87-8917942-0.

Authorized licensed use limited to: UNIVERSIDAD POLITECNICA SALESIANA. Downloaded on July 04,2022 at 23:13:37 UTC from IEEE Xplore. Restrictions apply.

You might also like