STANDARD ANCHOR BOLTS TOLERANCES

HOLD HOLD

PLANT NORTH

Y=89667.000
Y=89654.000
Z Y My

PL4
"K" "K"
P32 P30 P28
X

Mx

CL ECONOMIZER

P50
CL STACK
SECT."K-K"
P31 P29 P27

P20 P17

SAMPLING
P55
SYSTEM

P19
P16 P14
P9 P12

PL2
P18 P15 P13

P2 P1
X=6330.550 (70B02)
X=6354.650 (70B03) NOTE :
THIS DRAWING IS REFERRED TO BOILER PACKAGE
P8 P11 "70B02" (MACCHI REF.1252).
P38 IT IS APPLICABLE TO BOILERS PACKAGE
P26 P24 "70B03" (MACCHI REF.1253).
P53
P23
PL1
THIS DOCUMENT IS TECNIMONT'S PROPERTY AND CANNOT BE USED BY OTHERS FOR ANY PURPOSE, WITHOUT PRIOR WRITTEN CONSENT

P36
P34 BOILER FRONT
CL F.D. FAN OUTLET REFERENCE DRAWINGS
MACCHI Doc. N. PROJECT Doc. N. TITLE
P35 P33 1252-0-M-011 4239-FB-VD-LG9859170B0203001 BOILER GENERAL ARRANGEMENT
FUEL OIL
SKID 1252-0-M-021 4239-FB-VD-LF9859170B0203002 FOUNDATIONS DETAILS
P22 1252-0-M-022 4239-FB-VD-LF9859170B0203007 STACK FOUNDATION DETAILS
P4 P3 1252-0-M-023 4239-FB-VD-LF9859170B0203003 FOUNDATIONS LOADS TABLE
P52
1252-0-M-024 4239-FB-VD-LF9859170B0203004 F.D. FAN FOUNDATIONS
CL F.D. FAN

1252-0-M-025 4239-FB-VD-LF9859170B0203005 FOUNDATION BOLTS AND PLATES


P25 P21 P37 1252-0-M-026 4239-FB-VD-LF9859170B0203006 TEMPLATE FOR STACK FOUNDATION
P5
NOTES
PL3
P54 P6 P7 P10 1 - ALL ELEVATIONS ARE REFERRED TO GROUND LEVEL 0.00 (HPP 100.000)
CORRESPONDS TO +15.55 METERS ABOVE THE LOW LOW WATER SPRING (LLWS)
LUBE OIL
SKID 2 - ALL DIMENSIONS ARE IN MILLIMETRES
PS1
3 - THE CONCRETE WORK DIMENSIONS SHALL BE FIXED BY THE BUILDER
WHO SHALL OBSERVE ONLY THE DIMENSIONS EXPLICITY INDICATED

4 - ANCHOR BOLTS FOR MAIN STACK WILL BE EMBEDDED INTO THE PLINTH
HOLD BY MEANS OF TEMPLATE
5 - ALL LEVELING AND FILLING WORKS SHOULD BE CARRIED OUT
USING ANTISHRINKAGE MORTAR AFTER POSITIONING OF THE EQUIPMENT.

FUEL GAS
6- DENOTES PIT-SUMP APPROXIMATE POSITION
SKID OF COLLECTION POINTS FOR DRAINS
7- SOCLES OR SMALL BASES WITH HEIGHT OF 50 mm APPROX
P51 FOR THE SUPPORTING OF MINOR LOADS AS :
PIPELINES AND CABLES TRAYS WILL BE CARRIED OUT BY MEANS
OF MORTAR DURING THE ERECTION ACTIVITIES AND MAKING USE OF
EXPANSION BOLTS, SUPPLIED WITH THEW RELEVANT EQUIPMENT,
FOR THE FIXING OF THE SAME ONE.
HOLD 8- PLINTHS DIMENSIONS ARE PRELIMINARY TO BE CONSIDERED FOR REFERENCE ONLY.
DIMENSIONS WILL BE FINALIZED DURING DETAIL ENGINEERING.

DIFFERENTIAL SETTLEMENTS
0.1% OF DISTANCE BETWEEN TWO POINTS ON BASE FOUNDATION OF MAIN STACK
0.05% OF DISTANCE BETWEEN THE PLINTH OF BOILER
10 mm MAX BETWEEN THE PLINTHS OF DIFFERENT EQUIPMENT
( FOR TYPE OF EQUIPMENT SEE DOC. N° 1252-0-M-023 )

VENDOR'S JOB: VENDOR'S DOC NO.:

1252 1252-0-M-020
PURCHASE ORDER NO.: MATERIAL REQUISITION NO.:

PLINTHS TYPICAL DETAILS 7500098591 4239-FB-MR-000001

CONTRACTOR DOCUMENT Class RF/R/I


R
FOR BOILER - STEEL STRUCTURES - EQUIPMENTS Checker
Acceptance Discipline
( FOR FOUNDATION DETAILS SEE DWG. 1252-0-M-021 / 024 ) Status Code Abbreviation Name Signature
Date Acceptance Status Description:

E-Sign - P: Fabio.Caldiroli C: Fabio.Caldiroli C: andrea.zaffaroni C: A: Marsilio.Resente ON: 22-Dec-2021


A Accepted
AC Accepted with Comments
CR Commented
CONTRACTOR's acceptance of this document does in no way relieve the NA Not Accepted
VENDOR of its contractual obligations

00 20.Dec.2021 IFR- Issue


IFI - ISSUE FOR REVIEW
for Information C.F. CALDIROLI ZAFFARONI RESENTE
Issue Date Reason for Issue - Revision Description Prepared Checked Checked Approved

Digital signature

PLINTHS FOR BOILER PLINTHS FOR STEEL STRUCTURES P5 ÷ P34 PLINTHS FOR STAIRS PS1
P1-P2-P3-P4 AND LADDERS PL1-PL2-PL3-PL4 REHABILITATION OF
TECNIMONT IDENTIFICATION CODE

Job-EC-Type-N°
PLINTHS AIR DUCT P35 ÷ P38 PORT HARCOURT 4239-FB-VD-LF9859170B0203001
REFINERY PROJECT SHEET DOC. CLASS. ISSUE
PLINTH STACK P50 (Port Harcourt - Nigeria) 1/1 3 00
CLIENT IDENTIFICATION CODE

PLINTHS EQUIPMENTS P51 ÷ P55 PORT HARCOURT


REFINING COMPANY -
LIMITED (PHRC)
TITLE
DOCUMENT TYPE
BOILER
FOUNDATIONS ASSEMBLY SCALE
1:50
ORIG. SIZE
A0