Protection functions
Functional overview
(Description of ANSI code nos., see Protection Functions Table)
DM101164EN
2 86 79
50N 46 46BC
50/51 51N 49 50BF
Numerical three phase and earth fault
overcurrent relay MiCOM P111 model E
ANSI Models
Functions
Code L N B A E
49 Thermal overload (true RMS): 2 independent thresholds (Alarm, Trip) b b b b
50BF Circuit breaker failure b b b b b
Three-phase non directional overcurrent: 3 independent thresholds (12 groups of IDMT curves) b b b b b
Switch on to fault (SOTF) b b b
Inrush blocking b b
50/51
Blocking logic b b b
Selective relay scheme logic b
Cold Load Pick-Up b b b b b
50N/51N Phase-earth non directional overcurrent: 2 independent thresholds (12 groups of IDMT curves) b b b b b
46 Negative phase sequence overcurrent b
46BC Broken conductor detection (I2/I1) b
79 Autorecloser (4 shots) b
86 Output relay latching b b b b b
2 setting groups b b b b b
Self-monitoring feature with watchdog contact WD 1 1 1 1 1
Freely configurable binary inputs / output relays (watchdog contact WD included) 0/4 0/6 4/4 4/8 8/6
8 signalling LEDs (“Healthy” + “Trip” + “Alarm” + 5 freely configurable LEDs) b b b b b
Circuit breaker supervision and counters b b
Trip circuit supervision b b
Fault records for the 20 most recent trips b b b b b
Event records (up to 200 events) b b b b
Disturbance records (up to 5 s) b b
LCD display b b back-lit back-lit back-lit
Front USB port for local downloading of settings, events and/or fault records b b b b
Rear port RS485 communications (Modbus RTU and IEC60870-5-103) Option b b b b
Measurements b b b b b
CB control: HMI, via binary input or RS485 b b b
Setting software: MiCOM S1 and/or S1 Studio b b b b
Optional cassette (adaptor) for wall-mounted solution b b b b b
Optional front cover preventing from unauthorized access b b b b b
34 NRJED112402EN
MiCOM series 10 MiCOM P111
Base Unit
Presentation
User-Machine Interface (HMI)
All functions, including protection, automation, communication, LEDs, inputs and
PC151007a
outputs, can be programmed and modified using the front panel user interface
(Human Machine Interface).
The LCD informs the user about settings, measurements & faults with a pull-down
menu structure allowing easy and quick access to any data.
Working language
2 The relay display language can be changed in the menu system.
All the texts and messages displayed on HMI are available in:
b English/German/French/Spanish/Russian/Turkish /Regional.
(Polish or Czech can overwrite on "Regional" )
Wiring
External connections are made via screw terminals.
The screw terminals allow connection of threaded wires of up to 2.5 mm or solid
wires of 4 mm of conductor cross section, with the exception of current terminals
that have up to 4mm for threaded wires and 6mm for solid wires.
Communication
Type port Physical link Connectors Data rate Comms. mode Protocol
RS485 Screened twisted Screws or snap-on 4.8 or 9.6 or 19.2 b Data Bit: 8 b Modbus RTU,
pair or 38.4 b Stop bit: 1/ 2 b IEC60870-5-103
(default:19.2 kbit/s) b Parity: (selectable in menu)
None/Odd/Even
b Address: 1 to 254
USB USB2.0 PC: type A male 115.2 kbits/s (fixed) b Data Bit:8 b Modbus RTU
b Stop bit: 1
P111: type mini B
b Parity: None
male
b Address: 1
44 NRJED112402EN
MiCOM series 10 MiCOM P111
Base Unit
(cont.)
Case
DM101136EN
All the models of P111 have a flush mounting plastic
case:
Dimensions
2
b Height 106.5 mm
b Width 106.5 mm
b Depth 118 mm
Weight
b P111 approx.0.5 Kg
Cut-out
NRJED112402EN 45
MiCOM series 10 MiCOM P111
Base Unit
(cont.)
PC151007a
4
5
2 6 Red programmable LED
4
9
7 5
8
6
9 Alphanumeric liquid crystal display:
16 character by 2 line
14
7
10 CLEAR key
8 15
11 READ key
12 An ENTER key, 4 ARROW keys
14 CB CLOSE key
1
15 CB OPEN key
16 USB port for local connection
16 12
1 Terminal block A:
b Auxiliary voltage Vaux 1
b Contact outputs: WD, RL1-RL3
b Binary inputs: L1, L2
b RS485
2 Current ring terminal block B:
b Contact outputs
RL6, RL7 (model A) or RL4, RL5 (model E)
b Binary inputs: 2
L3, L4 (model A) or L5, L6, L7, L8 (model E)
3 Terminal block B:
b Current analogue inputs (phases and earth)
b Output contacts RL4, RL5 (models N / A)
b Binary inputs: 3
L3, L4 (model E)
46 NRJED112402EN
MiCOM series 10 MiCOM P111
Base Unit
(cont.)
DM101158EN
P2 P1 Ia P2 P1 Ia
A A
S2 S1 S2 S1
B B
S2 S2
S1 S1
S2
C Ic Ib C Ic Ib
S2
S1 S1
S2 S1
A1 Auxiliary A1 Auxiliary
Voltage Voltage
A2 Vx A2 Vx
WD/RL0
A3
A4
Watchdog
WD/RL0
WD/RL0
A3
A4
Watchdog
WD/RL0
2
C5 A5 C5 A5
Ia Ia
C6 A6 C6 A6
Output Output
C7 A7 Contact C7 A7 Contact
Ib RL1 RL1 Ib RL1 RL1
C8 A8 C8 A8
C9 A9 C9 A9
Ic Output Ic Output
C10 A10 Contact C10 A10 Contact
RL2 RL2 RL2 RL2
C11 A11 C11 A11
IN IN
C12 A12 Output C12 A12 Output
RL3 Contact Contact
RL3
A13 RL3 A13 RL3
P111 +
A18 RS485
P111 +
A18 RS485
Model L RS485
- Optional
Model L RS485
- Optional
A19 A19
Model L: Model L:
Typical connection to 3 Phase CTs Typical connection to 3 Phase CTs + a Core Balance CT
DM101157EN
P2 P1 Ia
A
S2 S1
B
S2
C Ic Ib
S1
S2 S1
A1 Auxiliary
Voltage
A2 Vx
A3
Watchdog
A4 WD/RL0
WD/RL0
C5 A5
Ia
C6 A6
Output
C7 A7 Contact
Ib RL1 RL1
C8 A8
C9 A9
Ic Output
C10 A10 Contact
RL2 RL2
C11 A11
IN
C12 A12 Output
RL3 Contact
A13 RL3
P111 +
A18 RS485
Model L RS485
- Optional
A19
Model L:
Typical connection to 2 Phase CTs + a Core Balance CT
NRJED112402EN 47
Order form MiCOM P111
Ready-to-use configuration
Number of identical MiCOM This order form can be used to define a complete MiCOM configuration.
b Please indicate the Catalogue No. (for example: REL10010) to your Schneider Electric correspondant.
For other variant please contact your Schneider Electric correspondant.
188 NRJED112402EN
Order form MiCOM P111
Ready-to-use configuration
(cont.)
Model
L No Binary Inputs, 4 Binary Outputs
4
Earth current input
0 Ion = 1 A/5A (selectable via HMI); 0.01 – 2 Ion
P111 1 N N 9 N N N 1 N
NRJED112402EN 189