You are on page 1of 1

SM6 Protection & control monitoring

General characteristics Protection and sensor selection table

General common selection of protection


units
Protection type Code Protection units
Sepam VIP
series 10 series 20 series 40 series 60 series 80 35 300
Three-phase overcurrent 50 - 51 b b b b b b (2) b (1)
Zero-sequence overcurrent 50N - 51N b b b b b b (3) b (1)
Directional zero-sequence current 67N b b b
Undervoltage 27 b b b
Overvoltage 59 b b b
Thermal image 49 b b b b b
Zero-sequence overvoltage 59N b b b
Negative sequence overcurrent 46 b b b b
Long start-up and rotor blocking 51LR b b b b
Maximum number of start-ups 66 b b b b
Single-phase undercurrent 37 b b b b
Communication b b b b b
(1) DT, EI, SI, VI and RI trip curves.
(2) Inverse curve suited to transformer protection.
(3) DT trip curve.

Current sensor for VIP 35 and VIP 300LL


and Sepam series 10 for SM6-24
Type Dimensions (mm) Weight Ratio of Class of precision VIP 35 VIP Sepam 10
(kg) transformation 300LL
External Internal Thickness
Ø Ø (without fastening)
CRa 143.5 81 37.5 2.18 1/200 ± 2% from 10 A to 100 A On load 5.7 Ω (cal. x 1) b b
± 1% from 100 A to 1600 A
± 1% from 10 A to 10 kA On load 0.67 Ω (cal. x 4)
CRb 143.5 81 37.5 1.26 1/1250 ± 1% from 10 A to 11 kA On load 5.7 Ω (cal. x 1) b b
± 1 % from 10 A to 25 kA On load 0.67 Ω (cal. x 4)
CRc 143.5 81 37.5 2 S1-S2: 1/200 S1-S2: On load 0.6 Ω b
± 5% from 10 A to 80 A
± 2.5 % from 80 A to 600 A
S1-S3: 1/500 S1-S3:
± 2% from 20 A to 2200 A
DE58402

CRa, CRb, CRc current sensor

54 SM6 catalogue schneider-electric.com