rated current of the upstream busbar trunking: 500 and 630 A

Upstream circuit breaker NS630N NS630H NS630L


Associated trip unit STR23SE/STR53UE STR23SE/STR53UE STR23SE/STR53UE
Upstream busbar trunking KSA / KVA / KVC KSA / KVA / KVC KSA / KVA / KVC
500 and 630 A 500 and 630 A 500 and 630 A
Level of protection of the 45 70 150
upstream busbar trunking (kA)
Downstream circuit breaker NS100N NS160N NS250N NS100N NS160N NS250N NS100H NS160H NS250H
Associated trip unit TMD / STR22SE TMD / STR22SE TMD / STR22SE
Downstream busbar trunking KSA KSA KSA KSA KSA KSA KSA KSA KSA
100 A 160 A 250 A 100 A 160 A 250 A 100 A 160 A 250 A
Discrimination limit between
upstream and downstream
circuit breakers (kA) 45 45 45 70 70 70 150 150 150
Reinforced breaking capacity of
the downstream circuit breaker (kA) 45 45 45 70 70 70 150 150 150
Reinforced protection of the
downstream busbar trunking(kA) 45 45 45 70 70 70 70 70 70

Upstream circuit breaker NS630N NS630H NS630L


Associated trip unit STR23SE/STR53UE STR23SE/STR53UE STR23SE/STR53UE
Upstream busbar trunking KSA / KVA / KVC KSA / KVA / KVC KSA / KVA / KVC
500 and 630 A 500 and 630 A 500 and 630 A
Level of protection of the 45 70 150
upstream busbar trunking (kA)
Downstream circuit breaker NS100N TMD / STR22SE NS100N TMD / STR22SE NS100N TMD / STR22SE
Associated trip unit 40 A 63 A 100 A 40 A 63 A 100 A 40 A 63 A 100 A
Downstream busbar trunking KN KN KN KN KN KN KN KN KN
40 A 63 A 100 A 40 A 63 A 100 A 40 A 63 A 100 A
Discrimination limit between
upstream and downstream
circuit breakers (kA) 45 45 45 70 70 70 150 150 150
Reinforced breaking capacity of
the downstream circuit breaker (kA) 45 45 45 70 70 70 150 150 150
Reinforced protection of the
downstream busbar trunking(kA) 45 45 45 50 50 50 50 50 50

rated current of the upstream busbar trunking: 315 and 400 A


Upstream circuit breaker NS400N NS400H NS400L
Associated trip unit STR23SE/STR53UE STR23SE/STR53UE STR23SE/STR53UE
Upstream busbar trunking KSA / KVA / KVC KSA / KVA / KVC KSA / KVA / KVC
315 and 400 A 315 and 400 A 315 and 400 A
Level of protection of the 45 70 150
upstream busbar trunking (kA)
Downstream circuit breaker NS100N NS160N NS100N NS160N NS100H NS160H
Associated trip unit TMD / STR22SE TMD / STR22SE TMD / STR22SE
Downstream busbar trunking KSA KSA KSA KSA KSA KSA
100 A 160 A 100 A 160 A 100 A 160 A
Discrimination limit between
upstream and downstream
circuit breakers (kA) 45 45 70 70 150 150
Reinforced breaking capacity of
the downstream circuit breaker (kA) 45 45 70 70 150 150
Reinforced protection of the
downstream busbar trunking(kA) 45 45 70 70 70 70

Upstream circuit breaker NS400N NS400H NS400L


Associated trip unit STR23SE/STR53UE STR23SE/STR53UE STR23SE/STR53UE
Upstream busbar trunking KSA / KVA / KVC KSA / KVA / KVC KSA / KVA / KVC
315 and 400 A 315 and 400 A 315 and 400 A
Level of protection of the 45 70 150
upstream busbar trunking (kA)
Downstream circuit breaker NS100N TMD / STR22SE NS100N TMD / STR22SE NS100N TMD / STR22SE
Associated trip unit 40 A 63 A 100 A 40 A 63 A 100 A 40 A 63 A 100 A
Downstream busbar trunking KN KN KN KN KN KN KN KN KN
40 A 63 A 100 A 40 A 63 A 100 A 40 A 63 A 100 A
Discrimination limit between
upstream and downstream
circuit breakers (kA) 45 45 45 70 70 70 150 150 150
Reinforced breaking capacity of
the downstream circuit breaker (kA) 45 45 45 70 70 70 150 150 150
Reinforced protection of the
downstream busbar trunking(kA) 45 45 45 50 50 50 50 50 50