Système de distribution

répartie
BBT protection summarizing table

Network characteristics
Isc
Circuit-breaker characteristics / Short-circuit constraints
Icu ≥ Isc at point A
BBT characteristics / Short-circuit constraints (1)
peak l Icw for T (3) A2s
BBT withstand permissible instantaneous
at peak current short-term current thermal withstand
k kA rms x f(T) kA2s
time-delayed non-limiting peak l ≥ Isc x k (2) Icw ≥ Icc
circuit-breaker
limiting breaker-circuit peak l ≥ IL limited kA 2s (BBT) ≥kA 2s limited
by the circuit-breaker by the circuit-breaker

characteristics that are not applicable or that are naturally verified


(1)
the Isc of the network under consideration is that at the BBT connection point (at point A)
asymmetry factor (see page 13)
(2)
T: total breaking time including any time delays.

circuit-breaker

'A

circuit-breaker cable

Isc at point A

A
B

BBT
E 36854E

E 36855E

BBT

■ the busbar trunking short-circuit protection level can be either total or partial:
v total protection: the busbar trunking is protected up to the ultimate breaking
capacity of the circuit-breaker
v partial protection: the busbar trunking is protected up to a high short-circuit
current level (e.g. 55 kA) but less than circuit-breaker ultimate breaking capacity
(lcu) (e.g. lcu = 70 kA).

Ipeak (Â) Ipeak (Â)


total protection total protection

BBT 1 BBT 1
partial partial
protection protection

BBT 2 BBT 2

circuit-breaker
curve
limiting
E 39592E

E 39593E

circuit-breaker
curve

I (12 kA) Icu (25 kA) Isc I (25 kA) Icu Isc
BBT2 BBT2 (150 kA)
protection protection
limit limit

Non-limiting circuit-breaker Limiting circuit-breaker

15