répartie
■ Limiting capacity
This fault current limitation means that BBT protection level is extremely high.
assumed Isc With present-day circuit-breakers (Compact NS type), a 10% limitation
at "A" 45 kA (IL /asymmetrical Isc) reduces to less than 1% the fault current flowing through
the installation.
The diagram opposite shows protection of the KSA40 distribution busbar trunking
by an NS400N limiting circuit-breaker. In this diagram:
■ the Isc is 45 kA at point A
E 36857E
48 kÂ
26 kÂ
E 38936E
Isc
40 kA
a. current limitation NS
A2s
354 x 106
1,6 x 106
E 38937E
Isc
40 kA
b. energy limitation NS