Professional Documents
Culture Documents
NTPC CONSULTANCY
NTPC Limited, EOC Annex
SECTOR-24 NOIDA-201301
JUNE 2022
DISCLAIMER
This Report has been prepared on the basis set out in our contract for ‘Preparation of
DPR for NTPC SAIL Power Company Limited. A JVC of NTPC Ltd., SAIL Limited.
Nothing in this report constitutes a valuation or legal advice.
We have not verified the reliability or accuracy of any information obtained in the
course of our work, other than in the limited circumstances set out in the Services
Contract.
This Report is for the benefit of the Client only.
This Report has not been designed to be of benefit to anyone except the Client. In
preparing this Report, we have not considered the interests, needs or circumstances
of anyone apart from the Client, even though we may have been aware that others
might read this Report.
This Report in whole or in part may not be used by any person for any purpose other
than that specified, without the express written permission of NTPC limited.
Any liability arising out of use by a third party of this document for purposes not
wholly connected with the above shall be the responsibility of that party who shall
indemnify NTPC Limited against all claims costs damages and losses arising out of
such use.
EXECUTIVE SUMMARY
NTPC Ltd formed a joint venture with SAIL on 50:50 basis in March, 2001 in the name NTPC-
SAIL Power Company Limited (NSPCL). NSPCL took over captive power plant-II located at
Durgapur Steel Plant (2X60 MW) and Rourkela Steel Plant (2X60 MW) from SAIL.
NTPC Ltd formed another joint venture company with SAIL on 50:50 basis in March, 2002
in the name of Bhilai Electric Supply Company (P) Ltd. (BESCL). BESCL took over captive
power plant-II located at Bhilai Steel Plant (2X30 MW + 1X14 MW BPTG) from SAIL. With
effect from 11th September, 2006, BESCL was amalgamated with NSPCL and all properties,
licenses, permissions, debt, liabilities etc. with respect to BESCL now rests in NSPCL.
To supply power to Bhilai, Durgapur and Rourkela Steel Plants of Steel Authority of India
Ltd. (SAIL) on captive basis from its coal based captive power plants –II at Bhilai
(Chhattisgarh) 2X30 MW + 1X14 MW, Durgapur (West Bengal) 2X60 MW and Rourkela
(Orissa) 2X60 MW. To meet additional captive power requirement of Bhilai Steel Plant and
other units of SAIL, NSPCL commissioned Bhilai CPP-II Expansion Power Project
(2X250MW) during 2008-09 and commercialized the units during 2009-10. From the
expansion plant, NSPCL is supplying power to the beneficiaries viz. Union Territory of Dadra
& Nagar Haveli , Union Territory of Daman & Diu, Chhattisgarh and Bhilai Steel Plant / SAIL
in the western region.
NSPCL intends to implement 15 MW Floating Solar Photovoltaic (FSPV) project at their
water reservoir at Bhilai. Power generated from the FSPV plant can be sold to intending
customer on long term power purchase agreement (PPA) or utilized for captive use by
themselves.
The project is located at NSPCL, Bhilai of Chhattisgarh. The geographical location of the site
is Latitude: 21.1740 N, Longitude: 81.3650 E. The project site is about 50 kms approx. from
Raipur airport.
The proposed Floating Solar Photovoltaic (FSPV) power plant would set up in available 400
acres approx. of reservoir area. DC capacity in MWp, Indicative MW Capacity, and Point of
common coupling for grid interface has been tabulated in Table-1 based on the assumptions
as specified in Table - 2. DC capacity shown in the Table -1 is the Minimum DC (peak)
capacity which can be enhanced to optimize the cost of generation at the time of project
implementation, thus lowering the Levelized Cost of Energy (LCOE). Capacity and
Generation indicated in Table - 1 above is for Capital budgeting and not for project appraisal
purpose. Salient project feature is provided in Table - 3.
The Report presents feasible capacity possible with its technical and commercial feature for
setting up FSPV plant at NSPCL, Bhilai. It also compares various solar energy technologies
that are commercially available. Suitability of each technology is analyzed and it is found
that Crystalline (Mono or Poly) Solar PV technology is most widely used till date, hence it is
technology of choice. Estimated generation is derived with fixed tilt Floating structure,
losses and uncertainty as per Industry practice using PVSyst Software.
Project Implementation is suggested in Single EPC package with Online Reverse Auction for
project cost bidding. EPC contractor shall quote the generation above threshold value and
the price. Offers shall be evaluated on the basis of Price per MU (Million Unit) of generation
and bidder quoting lowest Price per MU shall be awarded the work of Solar Project
Development. Sites for Solar Project development is encumbrance free and is available for
Solar project activity. All the data is provided on best effort basis and remain valid at the
time of preparation of this report only. This document is prepared for feasibility study for
Floating Solar PV Project at NSPCL, Bhilai. Project Design specification need to be separately
prepared for Implementation of the project.
Table 1: Solar PV Project
DC Capacity AC Capacity Minimum Point of Measurement
Generation / year
21.75 MWp (min.) 15 MW 32.112 MU 132 kV
TABLE OF CONTENT
CHAPTER NO. CLAUSE NO. CHAPTER NAME PAGES
1 INTRODUCTION & FSPV OVERVIEW 16
1.1 Current Indian Energy Scenario
1.2 World Energy Scenario
1.3 Future Indian Energy Scenario
1.4 Climate Changes
1.5 CO2 Emissions
1.6 Carbon Credits
1.7 REC/RPO Mechanisms
1.8 Renewable Energy In India
1.9 Chhattisgarh Power Synopsis
1.10 Introduction To Floating PV
1.11 FPV Background
1.12 What is floating solar PV?
1.13 Comparison of FPV With On-Shore PV
1.14 Floating Solar: Market Trend
2 GENERAL TECHNICAL OVERVIEW 38
2.1 Introduction to Solar Energy
2.2 Assessment of Solar PV Technologies
2.3 Floating PV System
2.4 PV Modules
2.5 Recent Trends In Solar PV Cells
2.6 PV Technology Selection For The Reference Project
2.7 Floaters
2.8 Mooring
2.9 Anchoring
2.10 String Combiner Box
2.11 Inverters
3 SITE IDENTIFICATION AND ASSESSMENT 17
3.1 Introduction
3.2 Methods Of Assessment
3.3 Solar Resource Assessment
3.4 Climate Conditions
3.5 Soil Investigation And Water Analysis
3.6 Evacuation System
4 ENERGY YIELD 15
4.1 Introduction
4.2 Solar And Meteorology Data
4.3 Solar Energy Resource
4.4 PV Module
4.5 Inverter
4.6 Tilt Optimization
4.7 Inter-Row Spacing
4.8 Losses In The Solar PV System
12 STATUTORY CLEARANCES 2
12.1 Clearances
13 SOCIAL & ENVIRONMENT IMPACT 2
13.1 Social Aspect
13.2 Generation of Employment Opportunities
13.3 Environmental Impact
14 CONCLUSION & RECOMMENDATION 3
14.1 Introduction
LIST OF DRAWINGS
SL NO. DRAWING NO. DRAWING TITLE
CHAPTER-1
INTRODUCTION FSPV OVERVIEW
India has made rapid economic progress in the last decade. With electricity demand in
India expected to more than double in the next decade, the power sector faces two main
challenges: adequately powering the projected economic growth and bringing electricity
to the 300 million citizens who currently lack access. As of 31st May 2022, India had a total
installed power generation capacity of 402 GW. Conventional sources of power, largely
coal, account for around 59% of this and in comparison, Renewable Energy contributing
28% out of which 50% contribution by Solar ie., 14% of Installed capacity contribution is
by Solar. The installed capacity mix of various sources and installed capacity mixes of
various RE sources are represented below.
The world energy mix and World energy mix of renewables are presented below as per IEA
upto the year 2019 for reference.
The above indicates Solar and wind energy forms are the major contributors world over
and the energy has mix has been chosen based on various factors related to various
technologies
IEA (International Energy Agency) has predicted the growth under various scenarios and
stated policy scenario has been shown below where IEA predicts that Solar Energy shall
form 31.4% of Total Energy Mix in 2040 from 0% in 2000 with coal growing in absolute
terms but diminishing in relative terms
and accounting for close to 34.3% of the
total Energy generation in 2040 from
76% in 2015. The main reason in this
scenario is the scarcity of conventional
fuels, which could limit significantly the
possibilities of growth for India without
additional renewable energy. India has
adequate reserves of coal and availability
of coal, but the challenge lies in building
the infrastructure required for extraction
and transportation of coal, as well as the
steep environmental and social impact.
There is also the need for a major
transition in the energy sector due to the
decline in fossil fuel availability, their predicted gradual extinction, and the resultant price
volatility. The energy demand projection under various scenarios and the market potential
of india projection from 2019 to 2040 in Solar, Wind and Batteries is presented below
which shows Solar and Wind shall form the most important energy form by year 2040.
Fossil fuel-based energy production has resulted in release of greenhouse gases into the
atmosphere, CO2 being the main culprit. The concentration of CO2 in atmosphere is
causing global warming resulting substantial change in structure and functioning of
terrestrial and marine ecosystem limiting the greenhouse gas concentration in the
atmosphere is seen as a global effort that extends to all countries. Since energy production
using fossil fuels and especially electricity production is the single biggest contributor to
global warming, real mitigation would occur only through a gradual transition to a low-
carbon energy economy.
Co2 Emissions of various countries and their comparison is presented below from IEA.
India’s CO2 emissions till 2022 is about 2.41 metric gigatones (GT), making it the 3rd
largest CO2 emitting country, following the European Union, and well ahead of the Russian
Federation, which is the fourth largest emitting country . This high ranking is partly caused
by the size of its population and economy. China is the largest emitter of CO2 in the world,
with about 11.68 GT of carbon dioxide emissions in 2022. The per capita emission of india
is 1.91 which is much lower than USA for which per capita emission is around 15.52.
A carbon credit is a generic term for any tradable certificate or permit representing the
right to emit one ton of carbon dioxide or the mass of another greenhouse gas with a carbon
dioxide equivalent to one ton of carbon dioxide (tCO2e).
Carbon credits and carbon markets are a component of national and international attempts
to mitigate the growth in concentrations of greenhouse gases (GHGs). One carbon credit is
equal to one ton of carbon dioxide, or in some markets, carbon dioxide equivalent gases.
At present, CDM is facing one of most severe crisis since it was set up a decade ago. A
flagging demand with ad hoc restrictions from the buyer side coupled with a continuously
increasing supply has led to a significant decline in CER prices.
India is also addressing emission reduction in the energy generation in a pragmatic way by
introducing renewable energies like wind, hydro, solar and biomass. In 2010- 2011 Solar
Renewable Purchase Obligations (RPOs) and the Renewable Energy Certificate (REC)
mechanism were introduced as a pair of policy-based drivers aimed at promoting solar
development in India
Under the REC mechanism, a generator can generate electricity through the renewable
resources in any part of the country. For the electricity part, the generator receives the cost
equivalent to that from any conventional source while the environment attribute is sold
through the exchanges at the market determined price. The obligated entity from any part
of the country can purchase these RECs to meet its RPO compliance. RECs are tradable,
intangible energy commodities which represent the attributes of electricity generated
from renewable resources and is traded on energy exchanges
The main statutory framework for Renewable Purchase Obligation (RPO) is the Electricity
Act 2003, the National Action Plan on Climate Change (NAPCC) and National Tariff Policy
(NTP). In January 2011, MoP amended the NTP to require the SERC s to fix a percentage of
energy purchase from solar power under the RPO regime. For the year 2021-22, RPO target
for Chhattisgarh state for Solar is 10.5%. These RPO targets are provided to encourage the
purchase of Renewable power.
India receives solar energy equivalent to nearly 5000 trillion kWh/year, which is
equivalent to 600 GW. India receives solar radiation between 5 to 7 kWh/m2, 300 to 330
days in a year. The single biggest barrier for accelerated development of solar energy has
been the cost. Initially, the
initial cost of solar energy
system is higher than the
cost of conventional
energy system and also
that of some other
renewable energies, as
wind. Renewable energy
sector in India is emerging
as a significant player in
power generation
capacity. India has done a
remarkable job in terms of
deployment of renewable
energy-based installations, growing almost 3.5 folds in the last 5–6 years, with most of the
capacity coming from onshore wind and solar photovoltaic (PV) based installations. At
present India’s grid-connected solar PV sector is majorly dominated by the ground-based
installations (93%) while the balance is contributed by rooftop the based solar PV
installations. Solar addition progress as per IEA is shown for reference.
Chhattisgarh State Electricity Board has been reorganized into following five companies
for Generation, Transmission & Distribution along with Trading
The total installed capacity as on December 31, 2021 is 24660.58 MW as shown in Figure
5.1. The technology wise break up of total installations is displayed in Figure 5.2
STATE SECTOR
CENTRAL SECTOR
PVT SECTOR
Figure-5.1 Chhattisgarh Sector wise power chart and Technology wise Power Structure
Hydro RES
Coal
Figure-5.2 Chhattisgarh Sector wise power chart and Technology wise Power Structure
Resource: - "Western region installed capacity" (PDF). National Power Portal. Retrieved 28
January 2022.
It is well known that solar PV deployment is land intensive and scaling up the project sizes
requires large chunk of contiguous land parcels, which becomes challenging in many
situations. Floating solar PV (FSPV) is one such alternative, which has started getting
traction worldwide. As per TERI report, the overall potential is a strong indication of the
extent of the surface area than can be made available for setting up these projects, and even
a capacity of about 280 GW is possible. India potential along with Chhattisgarh and other
neighboring state summary of FSPV potential is presented in Chart 1.
This section provides an introductory overview of the FPV market and the involved
technology. Furthermore, the section also incorporates the prospects and potential of
Floating Solar PV systems.
FSPV is a solar PV application in which PV panels are designed and installed to float on
waterbodies such as reservoirs, hydroelectric dams, industrial ponds, water treatment
ponds, mining ponds, lakes, and lagoons. In this, solar panels are usually mounted upon a
pontoon-based floating structure and to keep its location fixed, floating structure is
anchored and moored, (refer to Figure 1 for more details). Recently there has been an
interest in FSPV globally as well as in India. Further, it is also seen that if the capacity of
FSPV deployment is scaled up, the tariff may also come down closer to the tariff discovered
for ground-mounted solar PV.
Floats/
Pontoo
ns
Figure-7 Schematic representation of a typical large-scale FPV system with its key
components
In electrical terms, FPV systems are identical to traditional onshore photovoltaic (PV)
systems. DC electricity is generated by PV modules and fed into inverters which convert
the energy generated into useable AC electricity. This is then either directly consumed or
fed into a distribution or transmission network to be consumed remotely. Therefore, PV
systems typically comprise as a minimum:
PV modules
Floating Platform
Inverter/s
Associated cabling and connectors
PV Modules
The basic integral part of the FSPV plant is solar PV modules and like conventional solar
projects generally, poly or monocrystalline or thin film solar panels are used for the
installation of the project. Selection of PV modules technology also defers because of space,
cost, relative humidity, type of waterbodies, etc. The criteria for selection of PV modules
are as follows: » Solar panel performance – power tolerance, efficiency, temperature
coefficient especially in high moisture, and high humidity conditions
Floating Platform
This is the most crucial component of FSPV, it supports all necessary components like solar
PV during the project time. Hence selection of appropriate materials for the floating
platform becomes imperative. HDPE is the most popular material being used in a majority
of the FSPV power plants across the globe. Other materials like FRP, medium density
polyethylene (MDPE), and ferro-cement has also been utilized as materials for the floating
platform.
Inverters
Like a conventional solar plant, DC power generated from solar PV modules is taken to the
inverter through a series of combiner boxes and finally converted into AC power. A
developer may select multiple string inverters or central inverters. Depending upon scale
and distance from shore, inverters can be placed either on a separate floating platform or
on land. Generally, for smaller capacity FSPV inverter may be located on land near to PV
arrays, otherwise for large capacity plants it is advisable to place inverter on a floating
platform to avoid excessive resistive losses.
In FSPV plants, cable routing and its management requires cautious planning. Unlike
ground-based solar PV installations, movement of floating platform on a water
surface causes cable length to vary in FSPV plants. The movement of floating platform
is due to wind load and variations in water level. This requires extra length in form of
slack to be provided for accommodating the movement of the floating platform.
Neglecting this, insufficient cable length may result in cables to snap and rupture due
to the tension. Apart from the cable length the other parameters upon which cable
size depends are voltage and current of the cable and losses from the cable. The cables
can be routed in two ways – either via float on water surfaces or via submarine cables,
later one being costlier. Cable trays, cable conduits, and cable clip holders are used to
keep cables on the water surface.
The single greatest difference to on-shore PV lies in how the PV modules are mounted
or placed. In the case of onshore systems, the mounting of panels is based on a rigid
structure with a firm foundation. Static and dynamic loads are readily calculated
according to established engineering methods and the geometry of the module
arrangements is relatively easy to control.
By contrast, in FPV systems the dynamic nature of the water surface, along with the
various forces (wind drag, tethering cables, wave motion etc.) acting on the modules,
require more novel structural designs that can withstand significant movement, and
wear and tear. In addition, control of the module geometry and implementation of
tracking is particularly challenging to achieve.
FPV installations reached 1.3 gigawatt-peak (GWp) of total installed global capacity
at the end of 2018 (figure 1.1), and deployment appears likely to accelerate as the
technologies mature, opening up a new frontier in the global expansion of renewable
energy (World Bank Group, ESMAP, and SERIS 2019). When combined with other
demonstrated benefits—such as higher energy yield, reduced parameters in real
time, ranging from electrical to meteorological and module-related factor.
With a global potential of 400 GWp under conservative assumptions, FPV could
become a significant market segment for solar photovoltaic (PV) deployment, without
the challenges of acquiring the land required for ground-mounted installations
(World Bank Group, ESMAP, and SERIS 2019).
CHAPTER-2
GENERAL TECHNICAL OVERVIEW
The amount of sunlight that strikes the earth's surface in an hour and a half is
enough to handle the entire world's energy consumption for a full year. Solar
technologies convert sunlight into electrical energy either through photovoltaic
(PV) panels or through mirrors that concentrate solar radiation. This energy can
be used to generate electricity or be stored in batteries or thermal storage. Figure
below shows the Solar resource map.
Solar Radiation
Solar radiation, often called the solar resource or just sunlight, is a general term
for the electromagnetic radiation emitted by the sun. Solar radiation can be
captured and turned into useful forms of energy, such as heat and electricity, using
a variety of technologies. However, the technical feasibility and economical
operation of these technologies at a specific location depends on the available
solar resource.
Every location on Earth receives sunlight at least part of the year. The amount of
solar radiation that reaches any one spot on the Earth's surface varies according
to:
Geographic location
Time of day
Season
Local landscape
Local weather.
Because the Earth is round, the sun strikes the surface at different angles, ranging
from 0° (just above the horizon) to 90° (directly overhead). When the sun's rays
are vertical, the Earth's surface gets all the energy possible. The more slanted the
sun's rays are, the longer they travel through the atmosphere, becoming more
scattered and diffuse.
The Earth revolves around the sun in an elliptical orbit and is closer to the sun
during part of the year. When the sun is nearer the Earth, the Earth's surface
receives a little more solar energy. The Earth is nearer the sun when it is summer
in the southern hemisphere and winter in the northern hemisphere.
The 23.5° tilt in the Earth's axis of rotation is a more significant factor in
determining the amount of sunlight striking the Earth at a particular location.
Tilting results in longer days in the northern hemisphere from the spring (vernal)
equinox to the fall (autumnal) equinox and longer days in the southern
hemisphere during the other 6 months. Days and nights are both exactly 12 hours
long on the equinoxes, which occur each year on or around March 23 and
September 22.
The sun's rays are far more slanted during the shorter days of the winter months.
The rotation of the Earth is also responsible for hourly variations in sunlight. In
the early morning and late afternoon, the sun is low in the sky. Its rays travel
further through the atmosphere than at noon, when the sun is at its highest point.
On a clear day, the greatest amount of solar energy reaches a solar collector
around solar noon.
Measurement
It represents solar radiation that does not arrive on a direct path from the sun but
has been scattered by clouds and particles in the atmosphere and comes equally
from all directions.
Figure shows the solar spectrum of which the yellow area shows the amount of
sunlight hitting the top of the atmosphere, and the red area is how much reaches
the ground.
Figure-5 Spectrum of Solar Radiation (Earth)
As depicted above, silicon solar panels can convert some of the ultraviolet portion
of sunlight on the far left. The amount increases as it becomes visible light and
panels go on to produce most of their electricity from visible light. Unlike with
ultraviolet, in the infrared there is a very sharp cut-off in the sunlight energy used
by the panel at 1,100 nanometers. This is because wavelengths longer than this
cannot be converted by Silicon. The range of energy that can be converted by PV
Cells was shown in the below figure.
Solar PV System:
Figure-7 A typical schematic of a Grid Connected Solar PV system
Main objectives of grid connected / grid - interactive SPV systems are to provide
demand side management, tail end voltage support, peak sharing requirements
and sustain essential power requirements in the event of grid outages if
demanded.
Solar Panels
Lightning protection system
Power conditioning units
Control room
Meteorological Equipment
Data Acquisition System
Cleaning devices, tools & tackles.
Electrical systems with power evacuation
Plant security and monitoring system
The electrical power generated by the PV array is fed into the grid. The output of
PV systems varies due to weather conditions / seasonal changes. In the event of
total grid – outage a limited load depending on user’s essential requirements can
be catered to by the PV array.
The photo voltaic arrays are divided in many units depending on inverter size.
Each string in the array shall have its own string monitoring unit which shall be
one of the major diagnostic tools for the system operator. The respective digital
outputs are taken to a supervisory controller located in the control room. The
inverter unit employs state of the art Digital Signal Processing based technology
to have conversion efficiency over 97%. Electronic surge arrestors provided at the
DC input & the AC output of each inverter. Necessary HT switch gears are provided
for HT isolation & protection.
Each inverter system will have an independent Data Acquisition system (DAS)
which would produce the real time Data as well as event logs indicating all the
supervisory faults also. These Data via bus is taken to a master Supervisory control
& Data Acquisition (SCADA System). Service interface on the operator panel is also
provided.
Inverters are connected in parallel on AC side. The system gets into Standby mode
when DC voltage falls below threshold value. In this mode only monitoring logic
will be active. The system is not switched ON until the solar array generates
sufficient power, which is a set point control as per inverter.
In the Automatic mode, all the PV sub arrays are connected after the system has
been switched ON. Then the Maximum Power Point Tracking controller
continuously searches for the Max. Power point thus operating at the proper MPP
voltage.
The Floating system comprises of the Floating unit, Module support structure and
anchoring/ mooring mechanism for the Floating Solar PV system (FSPV).
Figure above shows the typical floating PV Plant. The components of Floating Solar
PV System and Ground Mounted PV System are similar in nature except the way
of mounting the modules. The main components of the Solar PV Project are briefly
explained along with the recent advancements in the industry in the following
sections.
The main components of grid-connected solar PV power system include:
Solar PV modules- PV cells, made from semi-conducting material, converts
sunlight into useful Direct Current (DC) electrical energy. PV cells are small in size
and generates few Watts (W) of energy. To get higher quantum of power, they are
arranged in series – parallel combination in a module. Modules are again
connected in series to make strings having higher voltages. Strings are further
connected together in parallel to boost the current making complete system able
to deliver power in the range of Megawatts (MW). In this way solar radiation in
converted into electricity in a silent & clean process.
Module Mounting Systems allow PV modules to securely attach to the
ground/float on the water body at a fixed tilt angle, or on sun-tracking frames
(orient along with the incoming sunrays). Mounting systems are made robust to
support PV modules up to their working life.
Inverters convert the DC electricity to alternating current (AC) for connection to
the utility grid. Many modules in series and parallel strings are connected to the
inverters.
Step-up transformers - The output from inverters generally requires a further
step-up in voltage to reach the AC grid voltage level. The step-up transformer
takes the output from the inverters to the required grid voltage (for example 11
kV, 22 kV, 33 kV, 66 kV, 110 kV etc. depending on the level of power evacuation).
The grid connection interface - This is where the electricity is exported into the
grid network. A switchyard with required switchgear, control and protection of
the PV plant may be required for grid interfacing besides energy meters. The
substation and metering points are often external to the PV power plant boundary
and are typically located on the grid operator’s property.
Due to continuous Research & Development and growth of the global solar PV
sector, PV plant components have undergone through considerable enhancement
in technology in past few years. Selection of PV module is a very important activity
for any solar power plant, which drives the cost of the plant and enables better
utilization of the available area for higher production of electricity and better
returns to the investor.
2.4 PV MODULES
PV materials and devices convert sunlight into electrical energy. A single PV device
is known as a cell. An individual PV cell is usually small, typically producing about
1 or 2 watts of power. These cells are made of different semiconductor materials
and are often less than the thickness of four human hairs. In order to withstand
the outdoors for many years, cells are sandwiched between protective materials
in a combination of glass and/or plastics. To boost the power output of PV cells,
they are connected in chains to form larger units known as modules or panels.
Modules can be used individually, or several can be connected to form arrays. One
or more arrays is then connected to the electrical grid as part of a complete PV
system. Because of this modular structure, PV systems can be built to meet almost
any electric power need, small or large.
PV modules and arrays are just one part of a PV system. Systems also include mounting
structures that point panels toward the sun, along with the components that take the
direct-current (DC) electricity produced by modules and convert it to the alternating-
current (AC) electricity used to power all the appliances in your home.
Figure-9 Typical representation from Solar Cell to Module- Ref from Office of Energy
Efficiency and Renewable Energy
When light shines on a photovoltaic (PV) cell – also called a solar cell – that light
may be reflected, absorbed, or pass right through the cell. The PV cell is composed
of semiconductor material. There are several different semiconductor materials
used in PV cells.
When the semiconductor is exposed to light, it absorbs the light’s energy and
transfers it to negatively charged particles in the material called electrons. This
extra energy allows the electrons to flow through the material as an electrical
current. This current is extracted through conductive metal contacts – the grid-
like lines on a solar cell – and can then be used to power your home and the rest
of the electric grid.
The efficiency of a PV cell is simply the amount of electrical power coming out of
the cell compared to the energy from the light shining on it, which indicates how
effective the cell is at converting energy from one form to the other. The amount
of electricity produced from PV cells depends on the characteristics (such as
intensity and wavelengths) of the light available and multiple performance
attributes of the cell.
An important property of PV semiconductors is the bandgap, which indicates what
wavelengths of light the material can absorb and convert to electrical energy. If
the semiconductor’s bandgap matches the wavelengths of light shining on the PV
cell, then that cell can efficiently make use of all the available energy.
The main semiconductor used in solar cells, not to mention most electronics, is
silicon, an abundant element. In fact, it’s found in sand, so it’s inexpensive, but it
needs to be refined in a chemical process before it can be turned into crystalline
silicon and conduct electricity. To make a silicon solar cell, blocks of crystalline
silicon are cut into very thin wafers. The wafer is processed on both sides to
separate the electrical charges and form a diode, a device that allows current to
flow in only one direction. The diode is sandwiched between metal contacts to let
the electrical current easily flow out of the cell.
The technology used to make most of the solar cells, fabricated so far, borrows heavily
from the microelectronics industry, which is further classified into two categories as:
This is the most established and efficient solar cell technology till date, having a
higher Module efficiency up to around 22%. The Cell and Module fabrication
technology is well developed and reliable. These cells are manufactured from
single silicon crystal. During manufacturing, C-Si crystals are cut from cylindrical
ingots and therefore the cells do not completely cover a square solar cell module.
High efficiency multijunction devices use multiple bandgaps, or junctions, that are
tuned to absorb a specific region of the solar spectrum to create solar cells having
record efficiencies over 45%. The maximum theoretical efficiency that a single-
bandgap solar cell can achieve with non-concentrated sunlight is about 33.5%,
primarily because of the broad distribution of solar emitted photons. This limiting
efficiency, known as the Shockley-Queisser limit, arises from the fact that the
open-circuit voltage (Voc) of a solar cell is limited by the bandgap of the absorbing
material and that photons with energies below the bandgap are not absorbed.
Photons that have energies greater than the bandgap are absorbed, but the energy
greater than the bandgap is lost as heat.
Multijunction devices use a high-bandgap top cell to absorb high-energy photons
while allowing the lower-energy photons to pass through. A material with a
slightly lower bandgap is then placed below the high- bandgap junction to absorb
photons with slightly less energy (longer wavelengths). Typical multijunction cells
use two or more absorbing junctions, and the theoretical maximum efficiency
increases with the number of junctions.
PERC Cells
PERC stands for “passivated emitter and rear contact” or “rear cell”. PERC solar
panels are built with PERC cells, which have an additional layer on the back of the
traditional solar cells. This additional layer allows more sunlight to be captured
and turned into electricity, making PERC cells more efficient than traditional cells.
PERC modules are also able to mitigate rear recombination and prevent longer
wavelengths from becoming heat that would impair the cell’s performance.
Given that a standard module typically has an efficiency of 20%, a system using
PERC modules will generate about 5% more energy than a system using standard
modules, all else being equal.
reduce its efficiency. The passivation layer reflects these higher wavelengths
and stops them from heating up the back sheet.
Silicon may be the most common type of solar cell, but thin-film solar cells
generally cost less and can be easier to fabricate. Thin films make up 3% to 5% of
the global market but are usually less efficient than silicon. Thin-film solar cells
are made by coating a thin layer of a highly absorptive semiconductor material on
a sheet of glass, plastic, or metal foil called a substrate rather than creating a
crystal wafer. This material can be deposited on flexible surfaces, which keeps
costs down and the solar cells versatile. Thin films are typically dark or partially
transparent, so the modules look more uniform than the speckled, blue or black
crystalline-silicon modules. The record high thin-film cell efficiency is 22.1%,
while monocrystalline-silicon cells have reached 25%, and polycrystalline, over
20%.
Major recent advances and research in solar PV Cells are given below:
• Perovskite solar cells
• Quantum Dots
• Orgonic Photo Voltaics
• Earth-Abundant Materials
Perovskite solar cells have shown remarkable progress in recent years with rapid
increases in conversion efficiency, from reports of about 3% in 2006 to over 25%
today. While perovskite solar cells have become highly efficient in a very short
time, a number of challenges remain before they can become a competitive
commercial technology.
Organic Photovoltaics
Organic photovoltaic (OPV) solar cells aim to provide an Earth-abundant and low-
energy-production photovoltaic (PV) solution. This technology also has the
theoretical potential to provide electricity at a lower cost than first- and second-
generation solar technologies. Because various absorbers can be used to create
colored or transparent OPV devices, this technology is particularly appealing to
the building- integrated PV market. Organic photovoltaics have achieved
efficiencies near 11%, but efficiency limitations as well as long-term reliability
remain significant barriers.
Unlike most inorganic solar cells, OPV cells use molecular or polymeric absorbers,
which results in a localized exciton. The absorber is used in conjunction with an
electron acceptor, such as a fullerene, which has molecular orbital energy states
that facilitate electron transfer. Upon absorbing a photon, the resulting exciton
migrates to the interface between the absorber material and the electron acceptor
material. At the interface, the energetic mismatch of the molecular orbitals
provides sufficient driving force to split the exciton and create free charge carriers
(an electron and a hole).
Earth-Abundant Materials:
2 2 Temperature 11% 9 5 10
Tolerance
3 4 Shade Tolerance 10% 5 5 10
4 8 Power Output 7% 10 7 7
5 10 Market share 5% 8 10 3
6 9 Environmental 6% 10 10 3
Issues
7 11 Balance of System 4% 10 7 4
(mounting
Structure, Cabling
etc.)
8 12 Accessories & 3% 10 7 3
additional
materials
9 13 Inverter flexibility 2% 10 10 3
10 1 Cost 13% 5 8 8
11 14 Stabilization 1% 10 8 3
12 7 Status of 8% 10 10 9
commercialization
13 5 Proven at MW 10% 8 7 10
scale in Hot
climates
14 3 Special gain 9% 3 3 10
2.7 FLOATERS
Single materials or combination of materials may be used for floats. The materials
to be used for fabrication of floats must fulfil the material requirements.
Synthetic polymers (heavy duty plastics) have regularly been used in floats. Heavy
duty plastics offer floating solution that is lightweight and easy to assemble
(particularly in modular designs).
Others
• PU (polyurethane foam)
• fibreglass with epoxy or polyester resin
• ferrocement.
The most common FSPV arrays are structurally defined into three main categories.
These are:
• Pure Floats
• Modular Rafts
• Membranes
Pure Floats
Modular Rafts
Membranes
2.8 MOORING
The station keeping system refers to the mooring system, consisting of mooring
lines which are attached to the floating structure at one end and anchored to the
waterbed or the bank at the other end, and the anchors. In principle, station
keeping could also be provided by dynamic positioning or fixed structures (e.g.,
piles and rollers) restraining horizontal motions of the structure.
The station keeping system shall keep the horizontal excursions of the FSPV array
within acceptable levels. This shall allow for the intended operation, keeping a safe
distance to shore, any obstacles or other infrastructure, and to maintain the
integrity of any connected structures or components. The station keeping system
is vital for keeping the floating structure in position such that the FSPV array can
maintain generation and transfer of electricity. It can also be vital for avoiding
dislocation of floats and to limit stress concentration in float connections.
The following site condition factors shall be taken into consideration when
designing the mooring system arrangement:
The main configurations of mooring lines applicable for FSPV systems include:
• soil conditions
• bathymetry
• water depth
• water level variation
• environmental conditions
• marine growth.
The mooring system shall be designed and installed to ensure redundancy, i.e., the
failure of one mooring line shall not lead to progressive failures of several mooring
lines
Mooring Lines
• mooring line material such as fibre rope, chain or steel wire cable
• connecting elements such as shackles, links, connecting plates,
fittings, etc.
• mooring line segments, inserts and accessories such as elastic
elements, buoyancy elements, clump weights, etc.
2.9 ANCHORING
Anchors may be installed at the bank for shore mooring lines and/or at the
waterbed for submerged mooring lines. In specific locations, depending on the
nature of the water body and on local and national regulations, only waterbed
anchors or only shore anchoring may be allowed. Various types of Anchoring
systems, their advantages and challenges have been presented below for
reference.1
Possibly challenging
installation procedures
Table-4 Advantages and Challenges of Anchor Types
The output of the Solar module is connected to another module forming series
connection. No of such series connection shall be decided based on the rating of
inverter to be selected. Such series connections shall be terminated in a box called
String Combiner Box. Combiner box is used to pool the strings to form single
circuit to be fed to inverter The combiner box is made up of polycarbonate or glass
fiber and should be halogen free. Figure depicts the few illustrations of String
Combiner Boxes.
String Combiner Box (SCB) is used in multi-string photovoltaic systems to
combine the individual strings electrically and connect them to the Inverters. It
shall have protection devices to protect the PV modules from current/voltage
surges. Nos. of input to each SCB shall be decided during detail engineering based
on the approved Single Line Diagram (SLD) submitted by EPC agency.
Monitoring the current of each input string and system voltage enables the system
operator to identify areas of concern and to take appropriate maintenance action.
Combiner Box also come with string monitoring which indicate operational status
of each array strings. The measure data of each string can be made available to
SCADA using use of industry standard Modbus communication protocols. There
are two method of current measurement i.e. Hall effect method and Shunt Current
method. It should be noted that current monitoring mechanism requires external
power source which is in range of few Watts.
The wiring systems include Field disconnects for the Modules side and Isolator on
inverter side, Surge (over voltage) protection, and over current protection with
fuse for the solar modules. Most systems include a combiner board of some kind
since most modules require fusing for each module source circuit. Some inverters
include this fusing and combining function within the inverter enclosure.
With recent trend of solar project cost optimization, Individual string monitoring
in string combiner box is getting replaced by zone monitoring in inverter. String
monitoring tracks data on individual strings while Zone monitoring aggregates
module strings into string combiners. The output current of each string combiner
is measured and monitored on the DC input side of the central inverter. Thus, it
saves the cost of monitoring device in combiner box
2.11 INVERTERS
Inverters are solid state electronic devices. They convert DC electricity generated
by the PV modules into AC electricity, ideally conforming to the local grid
requirements. Inverters can also perform a variety of functions to maximise the
output of the plant. These range from optimising the voltage across the strings and
monitoring string performance to logging data and providing protection and
isolation in case of irregularities in the grid or with the PV modules.
There are two broad classes of inverters: central inverters and string inverters.
The central inverter configuration remains the first choice for many medium- and
large-scale solar PV plants. A large number of modules are connected in a series
to form a high voltage (HV) string. Strings are then connected in parallel to the
inverter.
Central inverters offer high reliability and simplicity of installation. However, they
have disadvantages: increased mismatch losses and absence of maximum power
point tracking (MPPT) for each string. This may cause problems for arrays that
have multiple tilt and orientation angles, or suffer from shading, or use different
module types. Typical Central Inverter of ABB is shown only as reference purpose.
Central inverters are usually three-phase and can include grid frequency
transformers. These transformers increase the weight and volume of the
inverters, although they provide galvanic isolation from the grid. In other words,
there is no electrical connection between the input and output voltages—a
condition that is sometimes required by national electrical safety regulations.
Central inverters are sometimes used in a “master-slave” configuration. This
means that some inverters shut down when the irradiance is low, allowing the
other inverters to run more closely to optimal loading. When the irradiance is high,
the load is shared by all inverters. In effect, only the required number of inverters
is in operation at any one time. As the operating time is distributed uniformly
among the inverters, design life can be extended.
In contrast, the string inverter concept uses multiple inverters for multiple strings
of modules. String inverters provide MPPT on a string level with all strings being
independent of each other. This is useful in cases where modules cannot be
installed with the same orientation or where modules of different specifications
are being used or when there are shading issues.
Advantages Disadvantages
More Popular in MW Range More system loss due to common MPPT function,
blocking diode and mismatch
Centralized Monitoring Reliability of the large part of system depends on
one inverter
Lesser Spares Need for higher voltage DC cable
Voltage can be immediately stepped Effect of localized shading is
up, which increases Power increased
evacuation efficiency
String inverters, which are usually in single phase, also have other advantages.
First of all, they can be serviced and replaced by non-specialist personnel.
Secondly, it is practical to keep spare string inverters on site. This makes it easy to
handle unforeseen circumstances, as in the case of an inverter failure. In
comparison, the failure of a large central inverter, with a long lead time for repair,
can lead to significant yield loss before it can be replaced.
Transformer
CHAPTER-3
SITE IDENTIFICATION AND
ASSESSMENT
The following studies shall be carried out for initial site assessment:
GIS-based assessment – Assessments through the GIS tool really help in finding
out the site feasibility for an FSPV plant establishment. The GIS tool provides
information on water surface variations due to seasonal changes in the past years.
The outcome of the analysis gives an approximate surface area of the waterbody
which remains permanent irrespective of seasonal water-level deviations.
For this project, Bathymetry study has been done by NSPCL separately. Therefore,
Details regarding depth of the reservoir and for ground profile in the reservoir,
bathymetry report may be referred.
This section addresses review of the solar radiation resource assessment of the
site at NSPCL Bhilai Maroda Reservoir.
Solar Resource
As with other PV projects, data on solar irradiance at the proposed water surface
is of primary importance. Because solar irradiance determines the energy yield
and project economics, it should therefore be assessed at the site-identification
stage. Such information can be readily retrieved from various resources such as
the Global Solar Atlas Figure-3.
With reference to the subject FPV installation, the solar resource data from
Solargis is presented below.
Figure-3 Solar Resource Map-GHI, Ref: Published by the World bank group, funded
by ESMAP and prepared by Solargis.
Figure-4 Solar Resource Map-GHI, Ref: Published by the World bank group, funded
by ESMAP and prepared by Solargis.
Data sources for solar radiation in India are of varying quality. Comparison and
judicious selection of data sources by specialists in solar resource assessment is
recommended while developing a project. Some of the more accessible data
sources include:
NASA’s Surface Meteorology and Solar Energy data set. This holds satellite –
derived monthly data for a grid of 1°x1° covering the globe for a 22 year
period (1984-2005). The data are considered accurate for preliminary
feasibility studies of solar energy projects in India. They are also particularly
useful for estimating the inter-annual variability of the Solar resource.
For solar irradiance, the first Source is the solar resource Map prepared by
Ministry of New & Renewable Energy.
Second source of information for solar irradiance considered for feasibility studies
was NASA Website (http://eosweb.larc.NASA.gov/sse/) where data tables for a
certain location and plots for a whole region are available for everyone free of
charge.
Various resources are used for estimation of global horizontal insolation of the
site.
1. METEONORM
The Meteonorm software provides basically monthly meteorological data for any
location on the earth. It also generates synthetic hourly values from these monthly
values, using stochastic models which have been improved in the latest versions.
It is a popular tool used by every solar power developer.
The data are based on 1325 measured meteo "stations", all over the world. Data
are monthly values, averaged over 20 years within the period 1961-1990. A
second period (1991-2010 for irradiations, 2000-2009 for temperatures) may be
chosen for some places since the version 6.0. There are about 10 to 20 "stations"
for each big central Europe country.
As per the meteonorm 8.1.1, the yearly global Horizontal Insolation of NSPCL,
Bhilai is 1811 kWhr/m2.
2. SOLARGIS
Solargis provide access to all solar resource and meteorological data parameters
required for evaluation of the energy potential of solar power system.
The PV Syst simulation has been carried out as per the latest available data from
SOLARGIS, which is 1869.9 kWhr/m2.
3. NASA-SSE
NASA-SSE (Surface Meteorology and Solar Energy programme) are monthly data,
average of 1983-2005 satellite measurements, provided for any cell in a grid of
1°x1° over the world (1° latitude is 111 km). See the NASA SSE site for further
information.
As per the NASA-SSE,, the yearly global Horizontal Insolation of NSPCL, Bhilai is
1851.5 kWhr/m2.
PVGIM TMY – Data from SARAH, COSMO or NSRDB
are available from 1983 to 2013 and cover the region ±65° longitude and
±65° latitude. The products are available as monthly, daily, and hourly
averages on a regular latitude/longitude grid with a spatial resolution of
0.05° x 0.05°.
As per the NASA-SSE,, the yearly global Horizontal Insolation of NSPCL, Bhilai is
2033.7 kWhr/m2.
Solar activity, including solar eruptions known as Coronal Mass Ejections (CMEs),
derive the bulk of their energy from the coronal magnetic field. This activity drives
space weather that impacts Earth, including damaging satellites, adversely
effecting communications, and posing hazards to astronauts. COSMO tracks the
energy build-up in the Sun's magnetic field and changes in plasma conditions in
the corona and in the atmospheric layer below the corona known as the
chromosphere.
Table- 1 GHI DATA
All Solar Database Resources indicate that the annual average daily GHI at the
selected Project location is nearer to 5.0 kWh/m2 which suggests that the current
location is suitable for solar power Project.
NTPC practice is to consider the Solar GIS data for Detailed Project
Reports/Feasibility Reports, however Actual data shall be obtained with the
pyranometer at site. Hence SolarGIS data base has been used for the energy yield
assessment of the PV project.
Therefore, Solar GIS data at the subject location is presented in a graphical manner
in the next few pages for easy reference.
Figure-9 Screen shot from Global Solar Atlas - Average hourly profiles of total
photovoltaic power output
Figure-10 Screen shot from Global Solar Atlas - Monthly averages on Direct Normal
Irradiation
The climate on site is warm, with temperatures never going below 0°C. The rainy
season is between June to August and construction times should be scheduled
outside of these months. Details about the meteorological conditions for the site
has been discussed in the subsequent sections. Climate details have been obtained
from meteoblue modelled parameters.
The climatologically details at NSPCL , Bhilai is placed at Table-2
Parameter Value
Mean Maximum Ambient Temperature Summer 43 oC
Mean Minimum Ambient Temperature Winter 13oC deg.
Max Relative Humidity 85 %
Min Relative Humidity 35 %
Maximum Annual Rainfall (2021) 226 mm
Basic Wind Speed for design as per IS 875 part 3. 47m/s
Temperature
Maximum temperature has been recorded during May (mean maximum 43°C)
while minimum temperature observed during January (mean minimum (13 oC).
Humidity
Humidity was high during the monsoon months as expected, particularly from July
to September and ranged from 80% to 85%. Humidity was lowest during the dry
summer months of March to May when it ranged between 35% to 40%. The
average Humidity its ranged 61.4%. Humidity Table from PVSyst is presented
below for reference.
Rainfall
To show variation within the months and just the monthly totals, we show the
rainfall accumulated over a sliding 31-day period centered around each day of the
year. the rainy period of the last year for 9.6 months, from January 15 to
November1,with a sliding 31-day rainfall of at least 0.5 inches, the most rain falls
during the 31days centered around July 31,with an average total accumulation of
9.8 inches.
Wind Speed
Accessibility
New Delhi is connected to site by road and rail, is well connected to the rest of
India through Road, Rail and air transportation services. The site NSPCL, Bhilai is
located at NH-53. Bhilai is well connected by State Roads to New Delhi which is
approx. 100 KM away. Nearest railway station is Durg which is 12 km away from
site. Nearest Airport is Raipur which is approx. 50 km away from site. Site is well
connected from port too. Nearest Sea port is Vishakhapatnam, it is approx. 550
kms away from site.
Available Area
The total area of reservoir is approx. 400 acers. The water bodies are owned by
NSPCL, Bhilai and has confirmed that they will hand over encumbrance free area
for Project activities. Shape of the area is not too narrow and found suitable for the
FPV.
Bathymetric surveys are a type of hydrographic survey which map out the details
of underwater terrain, illustrating the depth and land that lies beneath a body of
water. NSPCL has informed that they will conduct the bathymetry study
separately.
NSPCL to provide the inputs related to Soil investigation and Water analysis
The geotechnical investigations in this case will be limited the inverter room,
Pooling switchgear and Control room, 132kV substation are and, cable routing.
Shading Losses
FPV projects generally benefit from openness and flat water bodies that have
minimal shade; To avoid the shadow cast by Inverter, Transformer on the
performance of PV System, provision of Inverters and Transformer location on the
land nearer to FPV has been considered as the design has sufficient space both on
land and above the water (Voltage losses due to longer lengths of cable have been
taken in to consideration also). attention needs to be paid to central inverters at
the center of FPV arrays.
Some times, water bodies may be located in mountainous areas where horizontal
shading from afar may become a concern. This aspect has also been reviewed in
the PV Syst software which has been detailed in Energy Yield analysis.
From the points of Shading losses also, the location of FPV at NSPCL, Bhilai is
Justified.
Soling Losses
FPV systems also tend to suffer less soiling from dust than installations on land.
Bio soiling (particularly from bird droppings) can adversely impact performance.
This may lead to hotspots and accelerated degradation and higher O&M costs.
It may be noted that the subject location is inside the compound of SAIL which has
a very low dust concentration. Therefore, Water washing system shall be provided
in the FPV system inline with the provision employed for the FPVs on reservoirs
of thermal plants to maintain the soiling losses at minimum.
From the above, in view of the proven water washing provision to reduce the
effect of soling losses, the project location is justified.
CHAPTER-4
ENERGY YIELD
4. ENERGY YIELD
4.1 INTRODUCTION
For estimation of energy-yield analysis irradiance data from various sources shall
be used to predict how much electricity that the PV system might generate. Poor-
quality solar irradiance data will yield inaccurate results even if good simulation
programs are used. As mentioned in the previous sections of this report, for this
project The energy yield estimation has been carried out by the Consultant using
PVSyst software (V7.2.11) with irradiance data from being obtained from PV Solar
GIS. The complete Project has been planned using Mono crystalline Solar PV
Modules mounted on floaters with a tilt angle of 5° towards North.
For the detailed Solar Radiation Resource Assessment exercise, Global Solar Radiation,
Diffuse Solar Radiation and Mean monthly Temperature data from SolarGIS have been
used for estimation of the energy yield calculation for the proposed Power Plant.
Additionally, solar radiation data from all available sources, relevant to the site have been
collected and compared for the proposed site. The optimum and most relevant value of
the global horizontal irradiance have been considered for the energy yield calculation.
Site selection and planning of PV power plants requires reliable solar resource
data. Power production depends linearly on the plane of array irradiance, at least
to a first approximation. The solar resource of a location is usually defined by the
values of the global horizontal irradiation, direct normal irradiation and diffuse
horizontal irradiation as defined below.
Global Horizontal Irradiation (GHI) – GHI is the total solar energy received
on a unit area of horizontal surface. It includes energy from the sun that is
received in a direct beam and from all directions of the sky when radiation is
scattered off the atmosphere (diffuse irradiation). The yearly sum of the GHI
is of particular relevance for PV power plants, which are able to make use of
both the diffuse and beam components of solar irradiance.
Direct Normal Irradiation (DNI) – DNI is the total solar energy received on
a unit area of surface directly facing the sun at all times. The DNI is of
particular interest for solar installations that track the sun and for
concentrating solar technologies (as concentrating technologies can only
make use of the direct component of irradiation).
Irradiation is measured in kWh/m2, and values are often given for a period of a
day, a month or a year. A high long term average annual GHI is typically of most
interest to PV project developers. Average monthly values are important when
assessing the proportion of energy generated in each month.
4.4 PV MODULE
Solar PV Modules are one of the most important parts of the solar PV plant. It
accounts for almost 50-70% of the total power plant cost. In the proposed project,
540Wp PV Module of Mono Crystalline technology from Longi solar has been
considered for analysis purpose only. Technical Parameters of the selected PV
module is shown in the table below.
4.5 INVERTER
Sungrow make central solar inverters (Model – SG 250-HV-20) have been selected
for the proposed 15 MW AC solar PV Project. Technical parameters of the inverter
are shown in the table below.
The tilt optimization study for the subject Project has been done using PVSyst and
Solar GIS database for a typical fixed tilt configuration table with a fixed pitch of
1.28m. A summary of the tilt optimization study along with the graph has been
presented below:
As per the tilt optimisation study at a fixed pitch, tilt angle of 11 Deg will have
highest energy supply to grid, 32.7 GWh. But Higher tilt angles need more
supporting structures to cater the wind speed and more inter row spacing is also
required to minimize the shading losses. Correspondingly floaters size also
increases. So, a trade-off is to be made between cost of the generation and energy
production.
Considering the above, Tilt angle of 50 has been followed for this project as the
same has been accepted by most of the developers across the world for FSPV
installations. Further, it is relevant to mention that due to very high design wind
velocity requirement, the increase in tilt angle may considerably increase the cost
of mooring and anchoring.
Furthermore, lower tilt angles have a good ground coverage ratio and for the
selected tilt of 5 degree, ground coverage ratio is near about 80% and shading
losses are very minimum. Tilt angle of 5 degree will have a good ground coverage
ratio which is depicted in the following diagram.
Inter row spacing of the plant has been decided in such a way that direct shading
effect is minimized and a minimum effective clear distance between rows is
maintained to effectively carry out cleaning during O&M phase.
Accordingly, Height difference has been calculated from the back of the module to
the surface for tilt angle of 5˚considering the module width as 1133 mm which has
been taken from the solar PV module manufacturer data sheet.
That means for the inter row spacing of 140mm between the sheds, shading loss
will be minimum for tilt angle of 5 deg.
One more limiting factor for the inter row spacing is the size of the floater. Market
survey has been carried out and Floater width of 0.15 m is techno commercially
viable for the wind speed of 280kmph, hence Floater width of 0.15 meter has been
considered for this project. Accordingly Shading analysis has been carried out for
the same and near shading losses are well within the limit. (Ref: Loss diagram)
The technical losses considered for the estimation of Energy yield have been
summarised as below:
Optical Losses:
Optical losses are defined as energy losses resulting from reduced irradiance in
the plane of array for the FSPV system. Optical losses may be sub divided into
incidence angle modifier losses, near shading losses, far shading losses, soiling
losses.
Incidence angle modifier (IAM) losses are losses due the fraction of the incident
light that is lost due to reflection. IAM corresponds to the decrease of the
irradiance really reaching the PV cells’ surface, with respect to irradiance under
normal incidence. This decrease is mainly due to reflexions on the glass cover,
which increases with the incidence angle.
PVsyst (Software used to predict the Energy Yield) uses an IAM function, which
describes the deficit of transmission as a function of the incidence angle. This
function is applied either to the beam component, and to the diffuse and albedo,
using an integral over all "seen" directions, supposing an isotropic distribution of
the diffuse irradiance.
As per the module data sheet, Fresnel Calculation with AR Coating has been
considered for IAM losses.
Near shading denotes objects which cause smaller localised shadows that will
affect the FSPV system performance. The shading losses shall take into
consideration shading objects in and around the FSPV system in a 3D modelling
tool. These shading items may be transformer stations, maintenance buildings,
inverters, trees and over-head transmission lines. The near shading model shall
account for the PV module characteristics (e.g. number of bypass diodes),
electrical configuration and orientation of the PV modules and the system.
For the subject project, no objects were envisaged affecting near shading losses.
Soiling Losses
Soiling loss is when dust and grime accumulate on solar panels and other PV
surfaces over time, lowering the sunlight that reaches the solar panels. Since a PV
system's performance is directly tied to how much sunlight can be transformed
into electric energy, soil loss is a large aspect of calculating PV system losses.
Soling losses shall be considered based on presence of dust and/or air pollution in
the area, seasonal pollen, humidity, effect of water spray, Planned yearly PV
module washes, the historical records of presence and migrations of birds at the
proposed site, Bio fouling, Snow. Etc.
For the subject project, it is observed during visit to NSPCL Bhilai Site that the area
is free from dust, dirt, biofuel, bird dropping etc. However, Considering the location
is nearer to the premises of industrial locations Soling losses of 3% has been
considered as per the default soiling loss factor in PV Syst on yearly basis.
Cabling Losses
Accurate cable-loss estimates must consider the length of individual cables along
with the cable materials and cross-sections. The typical solar PV plant consists of
2 types of cables i.e.., AC Cables and DC Cables. PV Syst describes the cable losses
separately for DC and AC which have been described briefly as follows. The DC as
well as AC Cable losses shall be calculated based on the total wire length for the
project. For FSPV systems, consideration of cable losses should be taken when
determining inverter installation location.
DC Cable Losses
DC Cable losses refers to losses in the cable of series connected cable, Y Connector
to String Combiner Box (SCB) and From SCB to Inverter input.
For the subject project, based on the length mentioned above, the losses have been
obtained in the PV Syst and the same have been presented in the Energy Loss
Diagram.
AC Cable Losses
For the subject project, based on the length mentioned above, the losses have been
obtained in the PV Syst and the same have been presented in the Energy Loss
Diagram.
Transformer losses are fixed, and variable losses associated with the operation of
the transformer. Transformer loss considerations for medium and high voltage
(MV, HV) shall follow standard industry practices for transformer losses.
Considering the above, analysis has been carried out in PV Syst and report is
presented in attached in subsequent pages.
NSPCL-Bhilai-Marod
a Reservoir-01_Revised.VC5-Report.pdf
PERFORMANCE RATIO
Performance ratio (PR) is the ratio of measured output to expected output for a
given reporting period based on the system name-plate rating. The below table
depicts the PR on monthly wise.
The energy yield estimation for the proposed Plant at site has been carried out
using the above technical losses. The month wise pattern of energy generation
from the Project has been presented in Table below:
Over the estimated life of Solar PV Modules, generally considered as 25 years, the
performance of the Modules gradually degrades. Normally, PV Module
Manufacturers provide a Performance Guarantee and indicate the rate of
degradation over the Module lifetime.
Year-25
Total Generation 32.11
Degradation% 81.20%
After Degradation 26.07
Table-6 Solar PV Project life
In the present case, the Solar Radiation data has been derived from the monthly
Solargis data. Generally, GHI Uncertainty of Solar GIS data for the Project location
is 2-3%. Apart from the Uncertainty in Solar Irradiation data, there are other
factors like Ambient, Conversion to inclined surface, soiling which contribute to
the overall uncertainty in the energy yield estimation from the proposed Project.
The combined overall Project Uncertainty of the Project has been analysed and
computed to be around 4 %.
Author
Project: NSPCL-Bhilai-Solar GIS-Final
Variant: DC-AC-Ratio-1.45
PVsyst V7.2.5
VC5, Simulation date:
24/06/22 16:35
with v7.2.5
Project summary
Geographical Site Situation Project settings
NSPCL-Solar GIS-Maroda Latitude 21.18 °N Albedo 0.20
India Longitude 81.36 °E
Altitude 297 m
Time zone UTC+5.5
Meteo data
NSPCL
SolarGIS Monthly aver. , period not spec. - Synthetic
System summary
Grid-Connected System Sheds on ground
PV Field Orientation Near Shadings User's needs
Fixed plane Linear shadings Unlimited load (grid)
Tilt/Azimuth 5/0 °
System information
PV Array Inverters
Nb. of modules 40320 units Nb. of units 6 units
Pnom total 21.77 MWp Pnom total 15.00 MWac
Pnom ratio 1.452
Results summary
Produced Energy 32672 MWh/year Specific production 1501 kWh/kWp/year Perf. Ratio PR 78.19 %
Table of contents
Project and results summary 2
General parameters, PV Array Characteristics, System losses 3
Near shading definition - Iso-shadings diagram 5
Main results 6
Loss diagram 7
Special graphs 8
PVsyst V7.2.5
VC5, Simulation date:
24/06/22 16:35
with v7.2.5
General parameters
Grid-Connected System Sheds on ground
PV Field Orientation
Orientation Sheds configuration Models used
Fixed plane Nb. of sheds 1440 units Transposition Perez
Tilt/Azimuth 5/0 ° Sizes Diffuse Perez, Meteonorm
Sheds spacing 1.28 m Circumsolar separate
Collector width 1.13 m
Ground Cov. Ratio (GCR) 88.2 %
Shading limit angle
Limit profile angle 32.6 °
PV Array Characteristics
PV module Inverter
Manufacturer Longi Solar Manufacturer Sungrow
Model LR5-72 HPH 540 M Model SG2500-HV-20
(Custom parameters definition) (Original PVsyst database)
Unit Nom. Power 540 Wp Unit Nom. Power 2500 kWac
Number of PV modules 40320 units Number of inverters 6 units
Nominal (STC) 21.77 MWp Total power 15000 kWac
Modules 1440 Strings x 28 In series Operating voltage 800-1300 V
At operating cond. (50°C) Max. power (=>25°C) 2750 kWac
Pmpp 19.90 MWp Pnom ratio (DC:AC) 1.45
U mpp 1046 V
I mpp 19020 A
Array losses
Array Soiling Losses Thermal Loss factor DC wiring losses
Loss Fraction 3.0 % Module temperature according to irradiance Global array res. 0.78 m
Uc (const) 29.0 W/m²K Loss Fraction 1.3 % at STC
Uv (wind) 0.0 W/m²K/m/s
LID - Light Induced Degradation Module Quality Loss Module mismatch losses
Loss Fraction 2.0 % Loss Fraction -0.4 % Loss Fraction 2.0 % at MPP
PVsyst V7.2.5
VC5, Simulation date:
24/06/22 16:35
with v7.2.5
System losses
Unavailability of the system Auxiliaries loss
Time fraction 2.0 % Proportionnal to Power 6.0 W/kW
7.3 days, 0.0 kW from Power thresh.
3 periods
AC wiring losses
Inv. output line up to MV transfo
Inverter voltage 550 Vac tri
Loss Fraction 0.94 % at STC
Inverter: SG2500-HV-20
Wire section (6 Inv.) Alu 6 x 3 x 4000 mm²
Average wires length 100 m
MV line up to Injection
MV Voltage 33 kV
Average each inverter
Wires Alu 3 x 240 mm²
Length 4500 m
Loss Fraction 0.58 % at STC
AC losses in transformers
MV transfo
Grid voltage 33 kV
Operating losses at STC
Nominal power at STC 21555 kVA
Iron loss (night disconnect) 10.78 kW/Inv.
Loss Fraction 0.10 % at STC
Coils equivalent resistance 3 x 0.28 m /inv.
Loss Fraction 1.00 % at STC
PVsyst V7.2.5
VC5, Simulation date:
24/06/22 16:35
with v7.2.5
Iso-shadings diagram
PVsyst V7.2.5
VC5, Simulation date:
24/06/22 16:35
with v7.2.5
Main results
System Production
Produced Energy 32672 MWh/year Specific production 1501 kWh/kWp/year
Performance Ratio PR 78.19 %
Legends
GlobHor Global horizontal irradiation EArray Effective energy at the output of the array
DiffHor Horizontal diffuse irradiation E_Grid Energy injected into grid
T_Amb Ambient Temperature PR Performance Ratio
GlobInc Global incident in coll. plane
GlobEff Effective Global, corr. for IAM and shadings
PVsyst V7.2.5
VC5, Simulation date:
24/06/22 16:35
with v7.2.5
Loss diagram
1869 kWh/m² Global horizontal irradiation
+2.7% Global incident in coll. plane
PVsyst V7.2.5
VC5, Simulation date:
24/06/22 16:35
with v7.2.5
Special graphs
Daily Input/Output diagram
CHAPTER-5
PLANT LAYOUT AND POWER
EVACUATION PLAN
5.1 INTRODUCTION
The major considerations which have been taken into account while planning layout of
various facilities in the plant are site coordinates, size and topography of land, approach
to the site, row to row distance, row to row shading of Modules, predominant wind
directions, water supply, tracking arrangement, selection of Modules, Inverters, Inverter
Transformers and other electrical equipment’s, optimization of cables, power evacuation
corridor, etc. The layout of the array structures shall be so designed that it shall occupy
minimum space without sacrificing the output of solar PV Modules.
5.2 LAYOUTS
Plant Layout
The Proposed Plant shall be based on Modules with Mono-crystalline Silicon solar PV
technology. The DC Power generated from the DC Field shall be converted into 550V,
50Hz AC (550V shall be indicative only. However, Voltage value shall be as per the
inverter manufacturer/EPC Designer), three phase using Solar Inverters and further
stepped up to 33kV through Inverter Transformers. This 33 kV voltage is further stepped
up to 132 kV for ultimate evacuation to the Grid. An Indicative Layout for the Complete
Plant has been presented in this document.
DC Field Layout
Mono-crystalline Solar PV Modules type LR72HPH of Longi solar has been used for
analysis of this Project. Twenty-eight (28) Modules will be clubbed together to form a
string. There shall be around 240 Nos. of strings clubbed together with each Solar
Inverter to generate the nominal power of 21773 kWp at STC. A total of 1440 strings
(40320 Nos. of Solar PV Modules) are planned for this solar PV Project which shall be
distributed throughout the plant. The Modules shall be mounted on fixed tilt at angle of 5
deg inclined towards the Equator (Towards south Direction).
Since the total output current of all the strings combined shall be very high, these strings
will be divided into several subgroups and connected to String Monitoring Boxes (SMB)/
Combiner Boxes and the String Monitoring Boxes / Combiner Boxes will be connected to
the Inverter inputs. A summary of the DC Field layout is furnished in Table indicated
below:
AC Field Layout
There shall be a total of two (02) Nos. Inverter Stations with one Main Control Building
in this Plant. The Main Control Building shall house the 33kV Switchgear for power
evacuation.
Inverter Stations
Each Inverter Station shall consist of other (3) No. of 2.5 MW Inverters, 63KVA, 550/
415V Auxiliary Transformers, LV Distribution Boards, Inverter Transformer Protection
Panels, UPS and Battery etc.
There shall be one no. of four winding 7.5 MVA, 33kV/550V/550V/550V Inverter
Transformers outside each Inverter Station. LT cables shall be provided to interconnect
LV winding of Inverter Transformers with the Solar Inverters. Ventilation system with air
ducts for the Inverters along with fire protection and detection system shall be provided
at the Inverter Stations.
As informed in the FR, The Inverter Station along with Transformer shall be housed in a
separate building of permanent structure or shall be made of Pre-Engineered Building
with proper thermal insulation as per the NSPCL Bhilai requirement.
The Main Control Building shall consist of the 33 kV Switchgear Room, SCADA/ Control
Room, Battery/ Auxiliary Room apart from One owner Room, one Pantry along with
Toilets, Stores etc. Air conditioning shall be provided in the SCADA/ Control Room and
Heat Ventilation System shall be provided in the 33 kV Switchgear Room, Auxiliary Room,
Battery Room and Toilets. The entire Building shall be provided with fire protection and
detection system. The Control Building shall have RCC Plinth with RCC columns, brick
walls and RCC Roof. There shall also be an overhead water tank of 2000 Litres (mounted
on separate structures adjacent to the Building or on the roof of the Building), adequately
sized septic tank and required wash basins. The MV Switchgear Room shall be provided
with mechanical ventilation system having a minimum of 8 air changes during normal
condition and 30 air changes in the event of fire. The Exhaust Fans shall be hooked to the
Fire Detection System. Energy efficient Split ACs will be provided in Control Room, SCADA
Room, and owner Room with a nominal operating temperature of 23 deg C and shall
comply with all applicable international standards. Internal electrification with minimum
illumination of 300 Lux shall be maintained in all Control Rooms.
Therefore, after step-up of the voltage to 33 KV from the inverter transformer, the AC
power from both the inverter duty transformers will be pooled at 33 KV in a separate HT
Switchgear Panel. The HT Switchgear panel shall be housed in CMCS building. HT
Switchgear panel shall consist of 2 incomers from both the inverter duty transformers,
one bus PT and 2 outgoing feeder panels (of which 1 feeder is used to connect to the
nearest 132 KV line and another will be kept for standby). The cable from the HT
Switchgear panel to the existing 132 KV switchyard shall be laid underground. The
proposed 132KV bay SLD at the existing switchyard is attached as Annexure to this
report.
The augmentation of another bay may require dismantling of the compound wall and
rebuilt which shall be kept in the scope of EPC bidder as requested by NSPCL.
Presently, two ABT meters (main and check) for the outgoing feeder in MV Switchgear.
Additional meters may be installed in 132KV bay metering panels also as per the
requirement of owner based on their recommendation.
CHAPTER-6
ENGINEERING DESIGN
6. ENGINEERING DESIGN
6.1 INTRODUCTION
Floating PV systems can in fact have different applications with unique qualities:
The “above water” application is, however, the most common and proven, and
therefore it was only considered for the project of FPV on Maroda Reservoir which
will be explained in subsequent sections.
The engineering design of “above water” FPV plants resembles that of ground-
mounted in many respects; of course, the floating structures and the anchoring
and mooring systems are different. Relevant site conditions, required
functionality, O&M, environmental impact and quality aspects of the floating
structures, the mooring and anchoring systems have been taken into
consideration. In addition, Cable routing and management are also considered as
they are comparatively more critical than for ground-mounted systems.
Technology Recommendation
Since the Solar PV modules shall be installed on the Maroda reservoir (a water
body), the recommended technology for mounting the Solar modules would be
floating platform. World is preferring Solar Crystalline PV technology and as
informed in Chapter-3, Solar PV crystalline based technology is recommended for
Maroda reservoir in Bhilai.
DC: AC Ratio
This DC/AC ratio shall not be too high also because the likelihood of the PV array
producing more power than the inverter can handle will increase. In such cases,
the inverter will reduce its output voltage and thus the drop in power output and
this loss is known as clipping losses. These clipping losses will create a major
impact on the energy yield as well.
To get the optimum DC/AC Ratio for this project different scenarios has been
verified as mentioned below. This analysis has been carried out only for the
selection of DC/AC Ratio without considering the losses and other factors which
are explained in Energy Yield analysis. Therefore, the results can not be compared
with the results of Energy Yield analysis.
Table-1
Based on the above scenarios and considering the Clipping losses, DC: AC
ratio as 1.45 is considered for this Project
From the input provide by owner, the vicinity of the reservoir seems that the
floating PV island will not having shading affects with respect to topography,
therefore, it is envisaged that the floating PV island is unlikely to be affected by
nearby tree lines or structures.
General Layout
Figure shows the project site for the proposed floating solar plant located on the
reservoir. The complete solar plant consists of 6 nos of Panel Arrays of size
141mx170m each. 6720 modules to be installed in each panel. Block AC capacity
will be 2.5 MW with module of 540 Wp.
Tilt angle
Every location will have an optimal tilt angle that maximises the total annual
irradiation (averaged over the whole year) on the plane of the collector. For fixed
tilt grid connected power plants, the theoretical optimum tilt angle may be
calculated from the latitude of the site. However, adjustments may need to be
made to account for Soiling and Shadings.
Higher tilt angles have lower soiling losses. The natural flow of rainwater cleans
modules more effectively and snow slides off more easily at higher tilt angles.
More highly tilted modules provide more shading on modules behind them. As
shading impacts energy yield much more than maybe expected simply by
calculating the proportion of the module shaded, a good option (other than
spacing the rows more widely apart) is to reduce the tilt angle. It is usually better
to use a lower tilt angle as a trade-off for loss in energy yield due to inter-row
shading.
More tilt angle requires more spacing between the module support structures ie.,
floaters. To provide the O&M of the floating plant access to each module by O&M
staff is important. Due to this cost of floaters will increase subsequent to increase
of floaters for walkway. A trade-off is to be made between cost of the generation
and energy production.
PV Module Configuration
Inter row spacing between the modules have been shown in the layout which is
attached as Annexure to this report.
Orientation
PV plants in the portion above the equator (North Side) shall have more exposure
to Sun when installed in south side and similarly PV plants in the portion below
the equator (South Side) shall have more exposure to Sun when installed in North
Side.
The subject location is located in North side (above the equator) and therefore
orientation of South side for the module has been considered to optimise the solar
potential.
PV Modules
Inverters
The grid tie inverter in a solar PV power plant converts the DC power generated
by the PV module into suitable AC power for feeding to the grid. This inverter
The inverters with their own weatherproof enclosure installed in close proximity
to PV modules are considered for this project. The inverters will be housed in a
structure to protect them from the weather and from tampering.
The solar PV module and inverter system form the heart of the solar power plant
and all efforts needs to be addressed to install the latest state of the art plant with
fail safe design and technology at same time.
It is not possible to formulate an optimal inverter sizing strategy that applies in all
cases. Both Central and String Inverters can be chosen. However, Central inverter
has been chosen as per the industry practice. For the subject project, 6 nos of
Central inverters have been considered.
The final selected Inverter Details for the analysis of this project are as Follows:
Inverter Type Central
Inverter Model Sungrow SG 2500 HV 20
Inverter Rating 2500KW
No. of Inverters 6 Nos
Floaters are considered as one of the most important components of the floating
solar plant. Each system of the FSPV should be design considering the functional
parameters, environmental parameters and geotechnical parameters. The
following shall be generally considered while envisaging conceptual design of
floater:
For the reliability of the design, floater had to comply with the essential conditions
which are described below:
Energy Requirement: The aim is to design the FSPV of 15 Mega Watt (MW) of
power which can be used for scaling up power for the project by using multiple
blocks of 2.5 MW. This division is done to match the power of inverters and
transformers as well as to avoid the crashing of the full plant if a module blacks
out, it will only affect that plant and the rest of the plants will still able to run.
Wave Slope: The floater should follow the wave slope to reduce wave slamming
as well as to reduce wave forces on the structure.
Space requirement: Space requirement for modules will depend on the capacity
of module, in this case 540 Wp module size has been envisaged. Apart from the
space requirement of module, walk way of 600mm after every 4th row of floaters
has been kept in the layout for maintenance purpose. The utility corridor is
envisaged on the top and bottom of the floater for the cable route and inverter as
well as It is also acted for the movement and the maintenance purpose.
Air Gap: The minimum air gap should be required as per relevant codes to avoid
slamming from the maximum individual wave height (1 m envisaged) which is
expected to break on the floater.
Good mooring design for the FSPV should comply with the following conditions:
The general requirement that mooring should comply with unless or until it is
practical and feasible are summarized below:
The slackness of the mooring line should be optimized to avoid the snap
loads and compression in the lines as well the vertical loads generating at
the anchors.
Mooring lines should not clash with anything including the power cables
going from the plant to the shore.
The design of the mooring line should be done in a way to allow the future
adjustment in the cables for elongation, creep, settlement.
Mooring system should have adequate life that exceeds the field life
including the fatigue safety factor since it is one of the prominent failure
modes.
Additional requirement for the mooring system which can be implied to optimize
the mooring system are summarized below:
The planning of mooring lines should be done in the way to reduce the
impact and hazard of the lines on the marine ecosystem as well as a
reduction in the installation of the mooring lines.
For the given location, the FPV plant must be able to withstand a 3s gust
of 50 m/s.
Wind Speed
For the given location, the FPV plant must be able to withstand a 3s gust
of 50 m/s.
Given the size of the reservoir and that it is well protected from all the sides with
areas of higher elevation, the effect of waves and current shall be negligible. Hence,
the same has not been considered for the anchoring analysis.
The anchoring system shall be designed with the objective to maintain the station
keeping of the FPV array under the influence of the external environmental
factors. Further, during the influence of the extreme weather conditions, the FPV
array shall have sufficient safety factor to avoid any permanent
deformation/damage.
This is done with the help of mooring lines which are attached to the floating
structure at one end and anchored to the waterbed or the bank at the other end.
The anchoring system shall keep the horizontal excursions of the FPV array within
acceptable levels. For the subject plant, we shall limit the horizontal excursions
below 2m in any direction along with a twist limitation of 1.5 deg. This shall allow
for the intended operation, keeping a safe distance to shore, any obstacles or other
infrastructure, and to maintain the integrity of any connected structures or
components.
The station keeping system is vital for keeping the floating structure in position
such that the FPV array can maintain generation and transfer of electricity. It can
also be vital for avoiding dislocation of floats and to limit stress concentration in
float connections.
The mooring lines proposed for the subject FPV array shall be Taut Leg mooring.
Each connection point on the FPV array will be connected to the anchoring point
via a single composite mooring line. Further, the mooring lines shall be configured
and installed to ensure redundancy, i.e., the failure of one mooring line shall not
lead to progressive failures of several mooring lines. The mooring arrangement
shall be designed to maintain station keeping capabilities throughout the range of
water levels as stated above.
Ground Anchor
The anchoring system proposed for the subject FPV array shall be underwater
anchoring. For the given site conditions, we shall be using concrete sinker blocks
as ground anchor points on all four sides of the FPV array. This configuration will
also be effective in providing resistance to prevent FPV array uplift under severe
wind speed conditions. The concrete blocks shall be designed with sufficient
safety factor for uplift, overturning and sliding resistance. Also with time, these
blocks will have subsidence effect into the bed of the reservoir which may add
additional holding capacity to them. The blocks shall be deployed under water
with the help of specialized equipment at GPS guided coordinates. The blocks size
shall be determined during detail engineering stage and also after considering site
and machinery restrictions.
DC System
Protection devices.
Earthing.
During sizing the DC component of the plant, the maximum voltage and current of
the individual strings and PV arrays has been calculated using the maximum
output of the individual modules. PVSyst simulation program has been used for
the design. DC components should be rated to allow for thermal and voltage limits.
PV Array Design
The design of a PV array will depend on the inverter specifications and the chosen
system architecture. Using many modules in series in high voltage (HV) arrays
minimises ohmic losses.
The highest module voltage that can occur in operation is the open-circuit voltage
in the coldest daytime temperatures at the site location. The maximum number of
modules in a string (n_max) may therefore be calculated using the formula:
Depending upon the selection of the module and inverter and based on the
philosophy described above, PVSyst calculates both maximum and minimum no
of modules that can be connected in the string. For easy reference, typical screen
shot of PVSyst is attached below.
For the subject project, 28 nos of modules are connected in series to form a string.
Combiner box is used to pool the strings to form single circuit to be fed to inverter.
The combiner box is made up of polycarbonate or glass fiber and should be
halogen free. Combiner boxes area available in varying sizes depending on nos. of
channels i.e., 8, 16 and 24. String Combiner box is also provided with isolation
switch to isolate it from inverter.
Monitoring the current of each input string and system voltage enables the system
operator to identify areas of concern and to take appropriate maintenance action.
Combiner Box also come with string monitoring which indicate operational status
of each array strings. The measure data of each string can be made available to
SCADA using use of industry standard Modbus communication protocols. There
are two methods of current measurement i.e., Hall effect method and Shunt
Current method. It should be noted that current monitoring mechanism requires
external power source which is in range of few Watts.
The wiring systems include Field disconnects for the Modules side and Isolator on
inverter side, Surge (over voltage) protection, and over current protection with
fuse for the solar modules. Most systems include a combiner board of some kind
since most modules require fusing for each module source circuit. Some inverters
include this fusing and combining function within the inverter enclosure.
With recent trend of solar project cost optimisation, Individual string monitoring
in string combiner box is getting replaced by zone monitoring in inverter. String
monitoring tracks data on individual strings while Zone monitoring aggregates
module strings into string combiners. The output current of each string combiner
is measured and monitored on the DC input side of the central inverter. Thus, it
saves the cost of monitoring device in combiner box.
For the subject project 16 in and 1 out SCB has been considered.
6.5 CABLES
Cable from Module to String Combiner Box (Solar Cables)
Halogen Free
UV Resistant
Flame Retardant
Tinned Copper
Electron beam curing
Standard cable size of 6 sq,mm has been considered for each polarity.
Cables used between SCBs and Inverters shall be of 3.3 kV (E) grade. These Power
cables shall have compacted Aluminium/copper conductor, XLPE insulated, PVC
inner-sheathed (as applicable), Armoured/ Unarmoured, FRLS PVC outer
sheathed conforming to IS: 7098 (Part-II).
Cable size shall be selected on 3 criteria:
For the subject project Cable of 1C x 400 Sq.mm of 2 runs( One for positive and
another for Negative) have been considered.
6.6 AC SYSTEM
For the Subject project, the inverter output voltage would be 550V AC. The point
of coupling as informed by NSPCL is 132KV Switchyard. Therefore, as per the
availability of the step-up inverter duty transformer, initially output voltage of
inverter will be stepped up to 33KV voltage level and pooled in 33KV Switchgear
near Reservoir. Therefore, output voltage of the inverter duty transformer would
be 33 KV. The project capacity is 15MW AC as informed by NSPCL, To ensure the
availability of 50% solar power in case of any failure of single component like
transformer here, 2 nos of transformers are to be provided. Therefore, 7.5 MVA
Transformer of each is has been proposed with 2X50% capacity. To attain 7.5 MVA
capacity, 3 nos 2.5 MVA blocks are pooled in to one incomer of 33 KV Switchgear
through a 7.5MVA, 4 winding transformer of capacity 2.5MVA / 2.5MVA / 2.5MVA
/ 7.5MVA where each LV winding shall be of 2.5 MVA capacity and HV winding
shall be of 7.5MVA Capacity.
bias component of 0.5% of rated Inverter output current is to be accounted for its
effect on the transformer design.
The adverse effect on life of transformer due to cloud intermittency and solar
generation loading cycle must be compensated through suitable design (as
applicable). The thermal design of Inverter Transformer needs to consider the
temperature dependent performance of the Inverter. It is to in accordance with
Inverter output and under worst condition it should not limit Inverter output.
Further, as NSPCL envisages the PoD (Point of Delivery) as 132 KV, 33KV outgoing
line shall be laid underground to the 132KV existing NSPCL Switchyard, where
132KV bay will be augmented to the existing switchyard with 15MVA 132/33KV
Transformer and other bay equipment. However, NSPCL informed to provide a
20MVA 132/33KV Transformer to accommodate any future load.
For complete Details of AC and DC System of Floating Solar plant, SLD may be
referred which is attached as annexure to this report.
HT Switchgear Panels
Circuit breakers of Vacuum or SF6 type shall be used to control and protection of
power evacuation circuit. It should be free standing, Floor mounted, metal clad,
fully compartmentalized, re-strike free, trip free, stored energy operated and with
electrical anti- pumping features. They shall comprise of three separate, identical
single pole interrupting units, operated through a common shaft by a sturdy
operating mechanism.
The closing coil and spring charging motor should be able to operate satisfactorily
at all values of control supply voltage between 187V-242V DC / 93.5V-121V DC.
The shunt trip coil shall operate satisfactorily under all operating conditions of the
circuit breaker up to its rated short circuit breaking current at all values of control
supply voltage between 154V-242V DC / 77V-121V DC.
For the subject project, HT Switchgear panel considered shall have the following:
2 Incomers
2 Outgoing (1 Outgoing and another Spare)
1 BPT
ABT meters (1 Nos Main and 1 Nos Check) for outgoing feeders to
HT Panel and Numerical relay in all the feeders
AC Cables
The cables shall be suitable for laying on racks, in ducts, trenches, conduits and
underground (buried) installation with chances of flooding by water. Cables shall
be flame retardant, low smoke (FRLS) type designed to withstand all mechanical,
electrical and thermal stresses develop under steady state and transient operating
conditions. Copper/aluminium conductor used in power cables shall have tensile
strength as per relevant standards. Conductors shall be multi stranded.
For the subject project, ,6 runs of 1C x 400 Sq.mm 3.3 KV (E) Grade AL FRLS
XLPE Armoured Cable has been considered from Inverter to Inverter Duty
Transformer (IDT) assuming 100 mtr length for each phase.
33kV (UE) ,1C x 240 Sq.mm AL FRLS XLPE Armoured Cable has been considered
from IDT to 33KV HT Switchgear for each phase.
33kV (UE) ,1C x 400 Sq.mm AL FRLS XLPE Armoured Cable has been considered
from 33KV HT Switchgear to 132KV existing switchyard of NSPCL to connect to
132/33KV, 20 MVA Transformer for each phase.
Typical drawings for underground cable laying, on cable tray, on floaters shall be
provided in the NIT/Bid Documents.
Electronic surge arrestors provided at the DC input & the AC output of each
inverter. Necessary HT switch gears are provided for HT isolation & protection.
Each inverter system will have an independent Data Acquisition system (DAS)
which would produce the real time Data as well as event logs indicating all the
supervisory faults also. These Data via bus is taken to a master Supervisory control
& Data Acquisition (SCADA System). Service interface on the operator panel is also
provided.
PCUs are configured in Master /Slave mode. Inverters are connected in parallel on
AC & DC sides. Depending on the magnitude of solar power generated, which
depends on solar radiation, one more inverter is switched ON automatically. This
ensures better conversion efficiency as the solar power generation increases. The
system gets into Standby mode when DC voltage falls below threshold value. In
this mode only monitoring logic will be active. The system is not switched ON until
the solar array generates sufficient power, which is a set point control as per
inverter.
In the Automatic mode, all the PV sub arrays are connected after the system has
been switched ON. Then the Maximum Power Point Tracking controller
continuously searches for the Max. Power point thus operating at the proper MPP
voltage.
The plant shall be automatically operated and shall be controlled by SCADA. There
shall be data logging and display system for continuous monitoring of data. The
complete Solar PV plant shall be integrated with SCADA which should
communicate with all the inverters and combiner box and displaying parameters
as mentioned below. SCADA shall also have provision to control turning ON and
OFF of any inverter of the grid connected Solar PV plant.
SCADA System shall have the provision to perform the following functions:
SCADA shall be provided with a reliable power supply along with a backup
supply for at least one hour to cater to outage of grid.
are used for measuring the irradiance on a plane surface, normally from solar
radiation.
Pyranometer is essentially just a thermopile
mounted on a black carbon disc, which
generates electricity according to how hot it
gets (how much solar radiation falls on it).
It consist of dome made from one or two
layers of ground and polished optical glass or
acrylic plastic covering the thermopile, which
eliminates air movements and dirt that might
affect the measurements (the curved outer
surface also ensures any raindrops fall away
quickly).
A small, replaceable cartridge of silica gel (or other desiccant) inside the dome
absorbs any dew. Since a thermopile typically sits outside in an exposed position,
it's case has to be made from something like toughened, rustproof, anodized
aluminium. Typically, there's a built-in spirit level so one can be sure that
pyranometer is flat (though some are designed to be used on inclined surfaces as
well).
The CMCS building shall be main control centre of the Solar Plant. It will house all
the electronic equipment to aggregate data from field equipment to SCADA.
Operator Work station (OWS) will be located in SCADA room pf the CMCS building.
Operator can monitor the Plant data and control, if required the Switchgear from
Graphical user interface of the OWS. CMCS can house the Pooling switchgear and
some Indoor Inverter. CMCS will have store room, Toilet, Pantry room equipment
inverters (in case indoor), Low Voltage Panels, High Voltage Panels, etc. The
approximate area required would be 100- 150 sq.m.
Module can be dry cleaned or water washed. Dry cleaning is suggested in the area
where there is acute shortage of water. Dry Cleaning can be manual (with blower
or Vacuum cleaner) or Automated. There are many supplier of automated dry
cleaning system.
In water washing system, Module is cleaned with water. Washing frequency may
be adjusted depending upon the power generation output & weather condition.
Washing of the modules/panels of the array shall only be done before Sun rise or
sufficiently after Sun set to prevent thermo shock to the top glass cover of the
modules. Approximately 3 Litre water per module will be required for washing of
module. Water for the cleaning shall be sourced from reservoir itself.
Design of solar PV module cleaning system shall be such that complete solar plant
shall be cleaned with fresh water once in a fortnight. Module cleaning system
piping network shall be closed looped pipe network configuration consists of Main
pipe, sub-main and branches. Module cleaning system piping network may be
design for dead end/tree pipe network configuration. Minimum 3
tapping/washing point shall be functional at same time. Cut-off valves shall be
provided at suitable junction point so that the repair works may be conducted at
a particular area without disturbing the whole area. The water used for cleaning
should be of appropriate quality fit for cleaning purpose as per the
recommendations of module manufacturer.
Water shall be supplied by the owner (CEB) at one location as per the requirement.
HDPE pipes shall run along separate floaters with suitable tapping points at
appropriate locations. The floaters used for cable routing arrangement may be
utilized for HDPE pipes.
6.11BATTERIES
In case of a power outage during daytime (system black out), inverters for utility-
scale solar power plants, can automatically restart operation when the DC input
voltage from the PV modules reaches their minimum operating voltage threshold
(i.e. the PV start Voltage is configurable from 300 to 600 VDC). Thus, Grid-
connected Solar Power Plant does not require a backup power supply for its
operation. However, battery is required for its meeting power requirement of
Emergency lighting, SCADA and breaker operation.
Battery Charger
Battery Charger will be Float & Float cum Boost Charger of suitable capacity for
quick boost and trickle charging as well as supplying the DC loads. The Battery
Chargers will have silicon-controlled rectifier or any other rectifier device,
6.14 EARTHING:
Each Array Structure of the Solar PV area as well as the 33 kV AC System shall be
grounded properly. The Array Structures are to be connected to earth pits as per
international standards. Necessary provision shall be made for bolted isolating
joints of each earthing pit for periodic checking of earth resistance. The earth
conductor shall run through appropriate pipes partly buried and partly on the
surface of the Control Buildings/ Inverter Stations. The complete earthing system
shall be mechanically & electrically connected to provide independent conforming
to IEEE:80
The complete Power Plant shall comprise of Six Blocks, each Block consisting of
one (01) Nos. of 2500kW Solar Inverters, out of which 3 blocks of FPV shall be
pooled through one (01) Nos. Four winding Inverter Transformers to 33KV
Switchgear, another 3 blocks of FPV shall be pooled through another four winding
inverter transformer to 33KV Switchgear. The total pooled power shall be fed
through 33KV underground cable to the existing 132KV Switchyrad of NSPCL
Bhilai where this 33KV shall be stepped up through 132/33KV MVA Transformer
and other bay equipment. An Indicative Electrical Single Line Diagram for the
Complete Plant has been attached as Annexure of this chapter.
Mono-crystalline Solar PV Modules LR5-72 HPH 540 M of longi solar has been
envisaged for this Project. Twenty eight (28) Modules will be clubbed together in
series to form a string. Several strings shall be connected to each String Monitoring
Box (SMB)/ Combiner Box in parallel. At the SMB end, each string shall be
provided with DC fuse. Monitoring shall be done at string level. The basic function
of the String Monitoring Boxes (SMB)/ Combiner Box shall be to combine group of
parallel connected Module strings and connect the same to the Inverter Individual
input terminal. All the individual input terminals of Inverter shall have
disconnection facility. Solar grade DC cables shall be provided for interconnection
between Modules and the SMB/ Combiner Boxes.
DC Side Protection:
The Solar Modules are made of Semiconductor material which will in turn act as a
Diode. These are connected in series to make the desired system voltage. The
following protection equipment’s shall be provided for the Solar PV Module
Strings at the String Monitoring Boxes (SMB)/ Combiner Box end.
· Fuses for Short Circuit Protection.
· Surge Protection Device – To protect from Transfer Surges at the DC side.
The Solar Inverter is the link between the PV Array DC system and the grid
connected AC system. Its basic task is to convert the DC electricity generated by
the PV Modules into AC by synchronizing itself to the frequency and voltage level
of the Utility Grid. The Inverter receives varying DC input power from the Module
due to varying nature of solar radiation and motion of Sun throughout the day &
year, which is converted into AC power by its highly efficient Power Electronics
Circuit working based on Multi MPPT mode and synchronizing to the Grid
Frequency and Voltage. The output of the Solar Inverter shall be 2500kW, 550V,
50 Hz AC with ± 10 % voltage variation.
Two (02) Nos. four (4) winding outdoor Inverter Transformers, each of rating 7.5
MVA, 33kV/0.55 kV (Inverter output voltage as per the design) are envisaged for
the Plant. Three Nos. of 2500 kW Solar Inverter shall be connected with one Four
Winding Inverter Transformer i.e. Three Inverters per Transformer. The Inverter
Transformers will step up the Inverter output voltage, 50Hz AC to 33kV, 50Hz AC.
The power output of Two Nos. Inverter Transformers i.e. total 15 MW approx.
shall be connected to the Main 33 kV Switchgear through the Cables. From the 33
kV Switchgear, the generated power shall be evacuated to the nearest 132 KV
existing Grid Substation of NSPCL by augmenting another bay complete with all
the necessary equipment like CT, Isolator, CB, PT, BPT..etc along with one
132/33KV 20 MVA Transformer.
For Auxiliary System Power Supply, each inverter station shall consists of 100
kVA, 550/415V Auxiliary Transformers, each fed from the LV winding of the
Inverter Transformer to meet the common auxiliary load requirements, have been
envisaged. The capacities of the Auxiliary Transformer shall be finalized during
detailed engineering based on proper sizing calculation. In order to ensure
reliability in the Auxiliary Power Supply, a Ring Main Scheme shall be considered.
AC Side Protection:
Inverter Protection: The followings monitoring/ protection features shall be
provided for each Solar Inverter.
Over Voltage protection
Grid Monitoring – Adjustable Voltage and Frequency range
PV Generator connection – Insulation monitoring, polarity reversal
protection.
DC Filter.
DC disconnect switch.
AC side Insulation monitoring device
Earth-fault protection.
Each Inverter Transformer shall be protected through the VCB at the 33KV Local
Switchgear and Air Circuit Breaker (ACB) on the LV side. The following electrical
and mechanical protections for Inverter Transformers shall be provided:
50 – Instantaneous Over Current Relay
50N – Instantaneous Earth Fault Relay
51 – IDMT over current relay
51N – IDMT Earth Fault Relay
49WT – Winding Temperature protection - Alarm / Trip
49OT – Oil Temperature Protection - Alarm
OL – Magnetic Oil Gauge (MOG) - Alarm
63 – Buchholz Relay protection - Alarm / Trip
PRV – Pressure Release Valve - Alarm / Trip
The above protections will trip the 33 kV VCB through the Master Trip Relay (86).
In addition, the VCB shall be provided with the following protections.
95 - Trip Circuit supervision protection
94 - Anti Pumping Relay
The above protections will trip the 33 kV VCB through the Master Trip Relay (86).
Moulded Case Circuit Breakers (MCCBs) will be provided for the Incomers/ Bus
Ties of the LV Auxiliary Switchboards for short circuit and over current
protections. Outgoing feeders shall be provided with Miniature Circuit Breaker
(MCB). The design concept of the electrical system as a whole shall be based on
the requirements for safe and reliable operation of the Plant with provision for
easy maintenance. The design and performance requirements of equipment will
be generally as per the latest Mauritius Standards and the Codes of Practice,
International standards like IEC. wherever applicable will also apply.
CHAPTER-7
PROJECT SCHEDULE &
IMPLEMENTATION
It is proposed that project shall be set up on EPC basis using open category modules
(without restriction of sourcing cell and/or module domestically) with three years of
Operation and Maintenance (O&M) contract of solar plant.
Bid shall be evaluated on the basis of price quoted per Million Unit (MU) of generation.
The bidding process shall be under Domestic Competitive Bidding (DCB). The Bids shall
be evaluated and tendered on generation-based bidding as to keep minimum cost of
generation i.e. Crore/MU. The generation and other related figures for bid evaluation are
listed below.
The minimum generation (G1) and their point of power measurement is shown below:
The Evaluation criteria for the unit size shall be based on L (Price per MU) as per the
following formula:
Where Generation G remains fixed during Reverse Auction for the respective bidder as
quoted in the Techno-commercial bid.
Bidder with lowest L is successful bidder shall be awarded the work of development and
O&M of the solar plant
Project Schedule
The date of Award has been reckoned as the zero date of the project.
Period from
Sl.No Activities/Milestone LOA(Months)
Start Finish
1 Site Mobilization, Opening of Site office and preparatory 0.5 1.5
2 Topography & Geo technical investigations 1 2
3 Approval of Details Required (DR) category Vendors 0.5 1.5
4 Basic Engineering & approvals (Approval of Layout, SLD and floaters, 0.5 3
anchoring and control/inverter rooms and datasheet of Module and
Inverters)
5 Ordering of BOIs 2 5
6 Detailed Engineering and Approvals 3 7
7 Control Room works – Civil and Electrical works 6 9
8 Inverter Room works – Civil and Electrical works 6 9
9 Supply of Float Structure 6 11
10 Installation, anchoring, fixing of floaters for SPV panels, pathways 7 12
11 Supply of SPV Modules 7 13
12 Installation of SPV Modules 8 15
13 Supply of cables, inverter transformer, inverters, 33 KV Switchgear & 7 10
other electrical equipment
14 Installation of cables, inverter transformer, inverters, 33 KV Switchgear 8 15
& other electrical equipment
15 Supply of 33/220 KV, 125 MVA Tie Transformer, 1 no. of 220KV bay 7 15
structure with bus extension including firefighting and civil works.
16 Installation of 33/220 KV, 125 MVA Tie Transformer, 1 no. of 220KV 8 17
bay structure with bus extension including firefighting and civil works.
17 Testing of Equipment & Readiness of SCADA - 17
18 Commissioning - 17
19 Stabilization & Trial Run 17 18
20 Completion of facilities - 18
All equipment, materials and services whether explicitly stated or otherwise and that are
necessary for the satisfactory operation of the Solar PV system and its integration with
the APCPL Central Switching Station is included in the scope of work of the Turn Key
contract, the salient features of this contract is delineated below and elaborated in the
next section.
7.3 ENGINEERING
Detailed design of Grid Interactive Solar PV Plant system and its associated civil, electrical
& mechanical auxiliary systems includes preparation of foundation drawings, single line
diagrams, installation drawings, electrical layouts, design calculations etc. Design
memorandum and other relevant drawings and documents required for engineering of
all facilities within the scope to be provided under this contract, are covered under
contractor’s scope of work.
Shall have an accuracy of energy measurement of at least Class 0.2S for active energy and
at least Class 0.5 for reactive energy.
Meter shall be suitable for interfacing for synchronizing the built in clock of the meter by
GPS time synchronization equipment.
Contractor shall be asked to demonstrate the quoted generation for a certain period. The
variation in radiation shall be taken in consideration.
DC SIDE
1 Solar PV Modules
2 DC Cables including field connectors and DWC pipes
3 String Combiner Box(if applicable)
4 Central Inverter / String Inverter
AC SIDE
5 LT Switchgear
6 HT Switchgear
7 Inverter Transformer& Auxiliary Transformer
8 LT Cables
9 HT Cables
10 SCADA & Time Synchronization Equipment
11 Instrumentation and Communication cable
12 Earthing System
13 Lightning Protection System
14 Plant Illumination system
15 Auxiliary Power Supply System
16 Battery and Battery Charger
17 UPS
18 132 kV Transformer bay Solar Incomers at NSPCL switchyard for 20 MVA
19 33/132 kV Tie Transformer 20 MVA at NSPCL
20 Inter Connection upto GCP
21 Grid interfacing so as to meet statutory requirements and state regulations if
applicable
GENERAL SYSTEMS
22 Weather Monitoring Station
23 Fire Detection and protection system
24 Module Washing system
Civil
The broad civil scope of work under this package shall include Civil, Structural and
Architectural Works related to but not limited to the following areas, System, Structures
/ Substructures, Buildings and Facilities:
Any other misc. requirement necessary for completion of commissioning & operation in
line with Bidder’s technical proposal / detailed Engineering.
B. Site Preparation (as required for installation of panels / equipment etc. during
construction, erection and commissioning activities).
1. Geo-Technical investigation
2. Bathometry studies
CHAPTER - 8
COST ESTIMATE
& FINANCIAL ANALYSIS
Further, the O&M costs vs tariff, ROE Vs Tariff are represented below:
ROE Vs Tariff
3.95
3.90
3.85
3.80
3.75
3.70
3.65
11.5 12 12.5 13 13.5 14 14.5
Useful life
Tariff Structure
To arrive at a Levelized cost of energy for Hybrid projects the following cost
components were assessed.
1) Return on Equity
2) Interest on Loan capital
3) Depreciation
4) Interest on Working capital
5) Operation and Maintenance Expenses
Since no additional “fuel” is needed for power generation from this system a
single part tariff was discovered.
Methodology
A generic tariff based on estimated costs of running Floating Solar PV plant was
determined on levelized basis for the tariff period of 25 years.
Capital Cost
Floating Solar is fairly developed technology and quotations are easily available
for each technology independently. Capital cost should be taken for a solar
project at based on actual design quotations, obtained after bidding. For our
analysis, we have considered present cost trends.
These shall be estimated based on bidding and the price quoted for O&M contract.
For our analysis, we have considered present cost trends. Insurance costs were
included in the Operation and maintenance expense estimate.
Depreciation
CUF/PLF
This was determined for based on solar resource availability based on technical
assessments by us.
Main Assumptions
NSPCL stipulated that 80:20 % Equity for the 15MW Floating Solar project. As per
CERC guidelines, the Debt to Equity ratio to be utilized for Tariff/ LCOE
calculation is 80:20. The financial parameters to be considered for financial
analysis were obtained from NSPCL. Based on the received inputs, financial
analysis was carried out for 15 MW Solar NSPCL Bhilai project. The table below
shows the various assumptions that have been considered.
Further, financial analysis was also carried out as per CERC guidelines. The
assumptions and computed tariff for 15 MW Solar project is enclosed at Annexure
-C
Table-4 Financial Analysis - Assumptions
8.6 CONCLUSION
NSPCL current power cost is INR ________ per unit. Levelized Cost from solar
floating plant is INR 3.90 per unit which is very much less than the cost of power
being bought by NSPCL. Thus, project may be considered as feasible.
CHAPTER -9
OPERATION & MAINTENANCE
Comprehensive O&M of the Floating Solar PV plant (s) for a period of three years
from the date of successful completion of trial run is in the scope of the bidder.
The contractor shall be responsible for the Operation and Maintenance of the
entire Floating Solar PV plant during the O&M period. The brief scope of works is
listed below.
(a) Ensuring successful operation of FLSPV Plant for optimum energy
generation.
(b) Ensuring Breakdown maintenance, Preventive maintenance overhauls,
Arranging visit of O&M experts (when required) to maximize the availability
of the solar plant.
(c) Daily work of the operators involves logging the voltage, current, power
factor, power and energy output of the FLSPV plant, temperature, logging
down individual array output data once a day
(d) The operator shall record monthly energy output of each array and
transformer and reports shall be prepared on performance of FLSPV plant
(e) Submission of periodical reports to the owner on the energy generation &
operating conditions of the FLSPV plant.
(f) Ensuring Safety and protection of the plant by deputing sufficient security
personals
(g) Monitoring, controlling, troubleshooting, maintaining of records, registers.
(h) Supply of all type of maintenance spares, consumables and fixing /
application of the same. In order to meet the emergent requirements,
contractor, with the permission of Employer can utilize the mandatory
spares being supplied under the contract. However, the used spares shall be
replenished by the contractor within reasonable time.
(i) Cleaning of the plant including array yard on regular basis and as and when
required.
(j) Cleaning of drains, cable trenches, box culverts etc.
(k) Module washing as per as per approved schedule.
(l) Herbicide spray and grass cutting on a periodic basis
(m) The contractor shall at his own expense provide all amenities to his
workmen as per applicable laws and rules.
(n) The Contractor shall ensure that all safety measures are taken at the site to
avoid accidents to his employees or his Co-contractor’s employees
(o) The Contractor shall immediately report the accidents, if any, to the Engineer
In charge & to all the concerned authorities as per prevailing laws of the
state.
(p) The Contractor shall comply with the provision of all relevant Acts of Central
or State Governments including payment of Wages Act 1936, Minimum
Wages Act 1948, Employer's Liability Act 1938, Workmen's Compensation
Act 1923, Industrial Dispute Act 1947, Maturity Benefit Act 1961, Employees
State Insurance Act 1948, Contract Labor (Regulations & Abolishment) Act
1970 or any modification thereof or any other law relating whereto and rules
made there under from time to time.
(q) In order to ensure longevity, safety of the core equipment and optimum
performance of the system the contractor should use only genuine spares of
high quality standards.
(r) Deployment of Plant in Charge, adequate number of technical support staff
and other supporting personnel during the O&M period
(s) Bidder is required to maintain adequate O&M spare during the O&M contract
period of the Floating Solar PV plant with the view to maximize availability
and generation of the plant. In case, Contractor uses mandatory spares,
provided by NSPCL, the contractor shall have to return/replenish the
spare(s) of the matching quality, quantity and rating within shortest possible
time.
(t) At the time handing over of the plant by the contractor to NSPCL, the
contractor shall handover equipment and spares in healthy condition.
(u) Bidder has to take Comprehensive Annual Maintenance Contract (AMC) from
Original Equipment Manufacturer (OEM) or OEM authorized service
provider for a period of 10 years for the following components:
PCU System - Replacement of spares like inductors, capacitors, electronic
cards as per OEM recommendations
SCADA
Dry cleaning/Robotic Cleaning if offered.
(v) Replacement of equipment/spare parts/ updating of software being phased
out or not being supported by OEM’s is also included in bidder’s scope.
(w) Contractor shall be responsible to carry out all test and work as required
by statutory regulation in effect as on date of Techno-commercial bid
opening during O&M period.
Comprehensive AMC shall include all preventive maintenance and breakdown
maintenance including replacement of any component to ensure that equipment
CHAPTER -10
RISK & MITIGATION
This section identifies and presents the various risks to the project. The impacts
of the major risks on the financial returns from the project are quantified and
mitigation measures suggested. Two types of risks are analyzed,
(i) the first set of risks is applicable to the factors used to analyze financial
feasibility of the project,
(ii) the second set of risks may arise at planning stage, implementation stage
and operational stage, thereby affecting the performance of the project.
The input parameters related risks having impacts on the financial feasibility of
the project are described in Table 1. The degree of confidence for each of the
parameters is logically derived (logic provided in the remarks column).
Table-1 Parameters and associated risk affecting financial feasibility of the project
The second set of risks is associated with different stages of the project. They are
defined as under:
Table-2 Project Risks associated with different project stages
warranties can be
enforced.
Can be reduced by
adding performance
linked O&M Payout
clauses within the O&M
Operational contract, based on the
Stage availability of the plant
and targets for energy
Inefficiencies in the yield or performance
O&M operation and ratio
consideration management of the Also establish a right to
project could reduce seek SCADA data from
the energy output. the plant for
independent analysis by
NSPCL’s own engineers
and third party
engineers to ensure that
independent check on
losses is there
System of regular
Performance Audits by
independent engineers
to ensure long term
health and good
maintenance practices.
Using QA data during
construction,
strict enforcement of
Warranties.
CHAPTER -11
CLEAN DEVELOPMENT
MECHANISM (CDM)
Installed Capacity 15 MW
First Year Generation 32.112 MU
ACM0002 (Latest Version): Large-scale
CDM Methodology adopted Consolidated Methodology- Grid- connected
electricity generation from renewable
sources
Calculation method
0.83 (Calculated as per CEA CO2 Baseline
Database for the Indian Power Sector
Grid Emission Factor in tCO2/MWh Version 13.0 Dec 2019 and Tool to calculate
the emission factor for an electricity system
published by the CDM Executive Board)
= Emission factor (tCO2/MWh) x net Energy
Projected CO2 reduction generation (MWh)
emission = 0.83 x 32112
= 26,653 Tonnes CO2 per year
= 26,653 CERs
CHAPTER -12
STATUTORY CLEARANCES
CHAPTER -13
SOCIAL & ENVIRONMENT IMPACT
CHAPTER -14
CONCLUSION &
RECOMMENDATION
Annexure A – 15 MW SLD
GE-650
GE-650
P2 86, 95, 50, 51 P2 86, 95, 50, 51
C.T 1-3 H1 H2 H3 C.T 1-3 H1 H2 H3 Fuse Fuse
50N, 27, 59, MFM 50N, 27, 59, MFM
C.T 1-3 Core 1: Core 1: C.T 1-3
GE-650
Core 1: 150 /1A H6 H5 H4 150 /1A H6 H5 H4 Core 1: H7 H8 H9
H1 H2 H3 H1 H2 H3
150 /1A 150 /1A
Spare
CL-5P20 CL-5P20
CL-5P20 , H6 H5 H4 5VA 5VA CL-5P20 , H6 H5 H4
5VA P1 5VA P1
VSS+V
74 63 49 26 74 63 49 26
SURGE
ARRESTER)
Trafo. Faults Relay Trafo. Faults Relay
BCS L/R
BCS BCS
CBCT L/R CBCT 75 / 1A L/R CBCT 75 / 1A CBCT L/R
BCS
75/ 1A BZ
BZ BZ BZ 75/ 1A BZ
REFER DRAWING:-
Trafo.-1 Trafo.-2
7.5mVA, 7.5mVA,
I.V/33KV I.V/33KV
(**) SEE NOTE (**) SEE NOTE
(##) (##)
(6R:1Cx400 Sq.mm (6R:1Cx400 Sq.mm (6R:1Cx400 Sq.mm (6R:1Cx400 Sq.mm (6R:1Cx400 Sq.mm (6R:1Cx400 Sq.mm
XLPE Al.Ar.Cable XLPE Al.Ar.Cable XLPE Al.Ar.Cable XLPE Al.Ar.Cable XLPE Al.Ar.Cable XLPE Al.Ar.Cable
Grade 3.3KV (E) )/phase Grade 3.3KV (E) )/phase Grade 3.3KV (E) )/phase Grade 3.3KV (E) )/phase Grade 3.3KV (E) )/phase Grade 3.3KV (E) )/phase
Air Circuit M
Air Circuit M
Air Circuit M
Air Circuit M
Air Circuit M
Air Circuit M
AUX. ACDB Breaker TP Breaker TP Breaker TP AUX. ACDB Breaker TP Breaker TP Breaker TP
EDO P2
BCS L/R
EDO P2
BCS L/R
EDO P2
BCS L/R
EDO P2
BCS L/R
EDO P2
BCS L/R
EDO P2
BCS L/R
UPS MISC. LT GS 50x6mm Flat GS 50x6mmFlat GS 50x6mm Flat GS 50x6mmFlat GS 50x6mm Flat GS 50x6mmFlat
UPS MISC. LT GS 50x6mm Flat GS 50x6mmFlat GS 50x6mm Flat GS 50x6mmFlat GS 50x6mm Flat GS 50x6mmFlat
LOADS Earthing Strip Riser Earthing Strip Riser Earthing Strip Riser Earthing Strip Riser Earthing Strip Riser Earthing Strip Riser
LOADS Earthing Strip Riser Earthing Strip Riser Earthing Strip Riser Earthing Strip Riser Earthing Strip Riser Earthing Strip Riser
lighting lighting
UPS DB washing UPS DB washing
etc. etc.
& OTHER EMERGENCY LOADS 2.5MW, 2.5MW, 2.5MW, & OTHER EMERGENCY LOADS 2.5MW, 2.5MW, 2.5MW,
AC DC AC DC AC DC AC DC AC DC AC DC
50sq.mm flx. 50sq.mm flx. 50sq.mm flx. 50sq.mm flx. 50sq.mm flx. 50sq.mm flx.
cu.cable cu.cable cu.cable cu.cable cu.cable cu.cable
PROPOSED
BUS CVT
Vk > 1200V/600V/300V
CORE-5 TRANSF. DIFFRENTIAL / LINE imax < 40-80-160mA @Vk RCT <
PROTECTION 10/5/2.5 Ohm
TRANS. BAY TRANS. BAY TRANS. BAY TRANS. BAY
(4T) (3T) (2T) (1T)
a b c d e f g h
86 95 94 80DC
CL-0.2S,20VA LINE PT
BILL OF QUANTITY-132KV EQUIPMENTS, 31.5KA FOR 1 SEC.
CORE-2 600/300/1A
CL-5P20,20VA
SYMBOL LEGEND DESCRIPTION Quantity (Nos.)
CORE-1 600/300/1A 50N 51N
CT SYSTEM DESIGN PARAMETERS
89 H.C.B ISOLATOR WITH ONE E/S 1250A (3 PHASE) 01 50 51
HIGHEST SYSTEM VOLTAGE : 145KV (rms)
LIGHTING IMPULSE VOLTAGE : ± 650KA KVP
POWER FREQVENCY WITH STAND FOR 1 min. (rms) : 275KV (rms)
25KA/1SEC
89 H.C.B ISOLATOR WITH TWO E/S 1250A (3 PHASE) 01 MAX FAULT LEVEL (sec.) : 31.5 KA
33KV, 630A M
VCB MINIMUM CREEPAGE DISTANCE : 3625mm
CL-0.2 ,20VA
52 CIRCUIT BREAKER 1250A (3 PHASE) 01 600/300/1A
CT
CURRENT TRANSFORMER, 1200,
CT 03
120% EXTENDED CURRENT RATING, (1 PHASE) CL-0.2 ,50VA
LEGEND:
ROLLING SHUTTER
PORTICO
(Vehicle Stoppage)
LOBBY
10.0000 AREA 2.0000 4.0000
ACDB
BATTERY HT/LT SWITCHGEAR ROOM 4.0000
DCDB
NOTE: ALL DIMENSION ARE TENTATIVE.
2.5000
4.0000 10.0000
2.5000
CMCS LAYOUT PLAN
EXISTING 132KVA SWITCHYARD
354.6
130.0
SEE
ENLARGED 183.0
VIEW Enlarged view
336.0 2.5 MW Floating drawing for Bhilai
IR REFER
DETAIL 'A'
0.6000
0.6000
Inverter
1.6609
0.5242
2.2900
0.0500
1.1500
5.0045
BLOCK DETAILS:-
0.1500
SCB-1
DETAIL 'A'
860.0 SCB-5
0.5242
1.6609
0.0500
SCB-6
183.4500
0.6000
1.1500
SCB-7 2.2900
0.6000
SCB-8
SCB-9 0.1500
SCB-10
SCB-11
SCB-12
130.0370
2.5 MW Floating drawing for Bhilai
Inverter
DETAIL 'A'
1.6609
0.0500
0.6000
1.1500
2.2900
0.6000
BLOCK DETAILS:-
0.1500
SCB-1
DETAIL 'A'
0.5242
SCB-5
1.6609
0.0500
SCB-6
183.4500
0.6000
1.1500
SCB-7 2.2900
0.6000
SCB-8
SCB-9 0.1500
SCB-10
SCB-11
SCB-12
130.0370