You are on page 1of 2

Area to be Faule

occupancy Electrical Load


Airconditioned ceiling
Sr. No. Space Description
Lighting Eqpt
Sq ft ft Nos.
Load Load
Watts Kw
1 G-SHOP 1350.00 9.50 35 1.25 1.5
2 F-SHOP 877.50 9.5 25 1.25 1
3 F-CONFERANCE 146.88 9.5 7 1 0.6
4 F-CABIN 1 111.63 9.5 4 1 0.3
5 F-CABIN 2 111.63 9.5 3 1 0.3
6 F-WORK 101.58 9.5 5 1 0.6
7 F-RECEPTION AND WAITIONG 127.40 9.5 5 1 0.6
TOTAL 2826.60 66.50 84.00 7.50 4.90
As per heat load PROPOSED INDOOR UNIT

TR CFM Type TR CFM

9.82 4659.28 -- 11.20 3495


6.26 3034.42 -- 6.40 2190
1.48 635.82 -- 1.60 576
1.06 442.70 -- 1.30 468
1.06 451.71 -- 1.30 468
1.15 494.97 -- 1.30 468
2.83 818.58 -- 2.00 720
23.66 10537.49 25.10 8385.00
TOTAL ESTIMATED LOAD 23.66
TOTAL PROPOSED LOAD 25.10
HP 31.375
SELECTED ODU CAPACITY 28
DIVERSITY 1.120536