Version 2.3 | 2021-10-06


Quick Guide

1. Sebelum menyalakan MCB Baterai, Pastikan baterai sudah tersambung dengan grounding
2. Install 1 MCB 1 baterai lithium (penggunaan junction box opsional apabila jumlah MCB kurang dari
jumlah baterai pengiriman)
3. Pastikan Firmware sudah diupgrade ke versi terbaru untuk SMU dan SCC
4. Pastikan koefisien charging disetting ke 0.10C (apabila memungkinkan, bila tidak setting ke 0.05C)
5. Pastikan koneksi kabel power terinstall dengan benar
6. Check Indicator Led di Lithium setelah diinstall

2
Instalasi Mounting Lithium

3
Instalasi Mounting Lithium
Makesure before Turn on MCB Lihtium , need Change Charging
Coefficient will be 10 % (0.10)

Cable Power

4
Instalasi Mounting Lithium

RTN+
COM_IN + -48
RTN+
COM_OUT -
COM_IN MCB
Junction
+
COM_OUT - Dapat di gunakan untuk
Lithium 1 koneksi antar junction
atau ke input MCB
Lithium 2
Lithium 3
RTN+
COM_IN + -48

COM_OUT -
COM_IN 1 Set mounting terdapat 2 Junction
+
Junction RTN(+), 1pcs
COM_OUT -
Dummy Junction -48V, 1pcs
Lithium Installation Scenario

Scenario 1: Lithium + SCC800 -> setting SCC800 via login local


Scenario 2: Lithium + 3rd Party Rectifier -> setting menggunakan lithium
maintenance tool
Scenario 3: Lithium + Huawei Rectifier -> setting SMU via login local
Scenario 1

Scenario 1 (Lithium + SCC800) :


1. Lithium Battery maximum 4 Pcs
2. SCC800-S1 Function for monitoring

7
Scenario 1

Existing Rectifier have 2 MCB Battery,and


connect 2 bank Battery VLRA

8
Scenario 1

Turn Off MCB battery Bank 2

9
Scenario 1

Change battery VLRA bank 2 to Lithium


Battery

10
Scenario 1
Ilustration Conenction cable Monitoring and cable Power

RTN+

RTN+
COM_IN + -48

COM_OUT - MCB MCB

COM_IN
+
COM_OUT -
UPEU MON0 0/1

RTN+
COM_IN + -48

COM_OUT -
COM_IN
+
COM_OUT -
Dummy
11
Upgrade Firmware SCC800-S1
Connect kabel LAN dari PC to SCC800 port PoE 1/PoE 2
Web URL : https://192.168.0.10
Username: admin Password: Changeme

Files: https://drive.google.com/drive/folders/1DGnMwXkd3nilg_cQcURCfNFRDy30s05p?usp=sharing 12
Upgrade Firmware SCC800-S1
BSP Upgrade
Step 1: Klik Maintenance Step 3: Klik Select File Step 5: Klik Open
Step 2: Klik Software Upgrade Step 4: Choose File BSPV100R004C01SPC102.tar.gz

STEP 4

13
Upgrade Firmware SCC800-S1
Step 6: Klik Upload

STEP 6

14
Upgrade Firmware SCC800-S1
Step 7: Klik Common Packages
Step 8: Klik Local Upgrade

STEP 7

STEP 8

15
Upgrade Firmware SCC800-S1
After Upgrade, and then Click OK

16
Upgrade Firmware SCC800-S1
SMU Upgrade
Step 1: Klik Maintenance Step 3: Klik Select File Step 5: Klik Open
Step 2: Klik Software Upgrade Step 4: Choose File SMUV500R003C10SPC038_SCC800_S.tar.gz

STEP 4

17
Upgrade Firmware SCC800-S1
Step 6: Klik Upload

STEP 6

18
Upgrade Firmware SCC800-S1
Step 7: Klik Common Packages
Step 8: Klik Local Upgrade

STEP 7

STEP 8
19
Upgrade Firmware SCC800-S1
After Upgrade, and then Click OK

20
Setting Enable Anti Theft pada SCC
Step 1: Klik Monitoring Step 3: Fill Battery Attenuation Coef. To be 0.10
Step 2: Klik Li Battery Group Step 4: Fill Battery Installation Time
STEP 1

STEP 3

STEP 4

STEP 5

STEP 2

STEP 6

Step 5: Klik iLock Enabled to be Lock Enable


Step 6: Klik Submit

21
Setting Parameter Coefficient Charging on SCC800-S1
After Lithium battery has been connected to SCC800-S1, and continue to the next step which is change the
Coeffisien to 0.10

Ubah koefisien charging menjadi 0.10


apabila memungkinkan (bila tidak
setting menjadi 0.05)

22
Scenario 1

Connect Cable to SCC800 for monitoring


and Turn on MCB for Battery Lithium

23
Scenario 1

Turn Off MCB battery Bank 1

24
Scenario 1

Change battery VLRA bank 1 to Lithium


Battery (then repeat the same process
for setting battery lithium)

25
Scenario 1

Turn on MCB Lithium bank 1 and 2

26
Scenario 2

Scenario 2 (Lithium + Rectifier 3rd Party) :


1. Lithium Battery maximum 4 Pcs

27
Scenario 2

Existing Rectifier have 2 MCB Battery,and


connect 2 bank Battery VLRA

28
Scenario 2

Turn Off MCB battery Bank 2

29
Scenario 2
Makesure before Turn on MCB Lihtium , need Change Charging
Coefficient will be 10 % (0.10)

Cable Power

30
Scenario 2

Change battery VLRA bank 2 to Lithium


Battery
Commissioning menggunakan Lithium
Maintenance tools

31
Scenario 2
Setting Parameter and Enabled Gyroscope
Cable Installation and cable connection use Adapter RS485 UGREEN TYPE

T/R+ → White Orange, Blue


T/R- → White Blue, Orange
Setting Parameter and Enabled Gyroscope
Check Port connect Converter
Pada bagian device manager
Setting Parameter and Enabled Gyroscope
Login software lithium maintenance tools
Setting Parameter and Enabled Gyroscope
Parameter Setting

:
Scenario 2

Turn on MCB for Battery Lithium

37
Scenario 2

Turn Off MCB battery Bank 1

38
Scenario 2

Change battery VLRA bank 1 to Lithium


Battery

39
Scenario 2

Turn on MCB Lithium bank 1 and 2

40
Setting Parameter and Enabled Gyroscope
Setelah baterai selesai diinstall dan dinyalakan (tidak dipindah posisi lagi)
klik Active Gyroscope dan Check Gyroscope Status
Scenario 3

Scenario 3 (Lithium + SMU02B, SMU02C (Rectifier Huawei)) :


1. Lithium Battery maximum 4 Pcs
2. SMU02B or SMU02C Function monitoring

42
Scenario 3

Existing Rectifier have 2 MCB Battery,and


connect 2 bank Battery VLRA

43
Scenario 3

Turn Off MCB battery Bank 2

44
Scenario 3

Change battery VLRA bank 2 to


Lithium Battery

45
Scenario 3
Ilustrasion with 2 MCB Battery and 4 pcs Lithium

RTN+

SMU02C COM_IN
RTN+
+ -48

COM_OUT - MCB MCB

COM_IN
+
SMU02B
COM_OUT -

RTN+
COM_IN + -48

COM_OUT -
COM_IN
+
COM_OUT -
Dummy
46
Upgrade Firmware SMU02B
Web Url: https://192.168.0.10
Username: admin Password: Changeme

Files: https://drive.google.com/drive/folders/1q0vxa7E8WTvQqXCKrI8NN_4aCoPsHmCd?usp=sharing 4
7
Upgrade Firmware SMU02B
BSP Upgrade
Step 1: Klik Maintenance Step 3: Klik Select File Step 5: Klik Open
Step 2: Klik Software Upgrade Step 4: Choose file BSPV100R004C01SPC102.tar.gz

48
Upgrade Firmware SMU02B
Step 6: Klik Upload

49
Upgrade Firmware SMU02B
Step 7: Klik Total Package
Step 8: Klik Local Upgrade

50
Upgrade Firmware SMU02B
After Upgrade, and then click OK

51
Upgrade Firmware SMU02B
SMU Upgrade
Step 1: Klik Maintenance Step 3: Klik Select File Step 5: Klik Open
Step 2: Klik Software Upgrade Step 4: Choose file SMUV500R002C20SPC961_02B.tar.gz

STEP 4

52
Upgrade Firmware SMU02B
Step 6: Klik Upload

53
Upgrade Firmware SMU02B
Step 7: Klik Total Package
Step 8: Klik Local Upgrade

STEP 7

STEP 8
54
Upgrade Firmware SMU02B
After Upgrade, and then click OK

55
Setting Parameter Coefficient Charging pada SMU
Step 1: Klik System Settings Step 3: Change Battery Vendor into AGISSON/SHOTO
Step 2: Klik Setup Parameter Step 4: Change Battery Model Into ESM-A Step 5: Change Hybrid Scenario Into No

STEP 12

STEP 13

STEP 14

56
Setting Parameter Coefficient Charging pada SMU
Step 6: Klik Monitoring Step 8: Fill Battery Attenuation Coef. To be 0.10
Step 7: Klik Li Battery Group Step 9: Fill Battery Installation Time

STEP 3

STEP 4

STEP 5

Step 5: Klik iLock Enabled to be Lock Enable


Step 6: Klik Submit

57
Setting Parameter Coefficient Charging pada SMU
Step 10: Klik Charge Parameters Step 12: Klik Submit
Step 11: fill Charge Current Limit Coef. Menjadi 0.10 bila memungkinkan (bila tidak
setting menjadi 0.05)

58
Scenario 3

Turn on MCB Lithium battery

59
Scenario 3

Turn Off MCB battery Bank 1

60
Scenario 3

Change battery VLRA bank 1 to Lithium


Battery

61
Scenario 3

Turn on MCB Lithium bank 1 and 2

62
Thank You