PLEASE NOTE:
DANGER b Electrical equipment should be installed, operated,
serviced, and maintained only by qualified personnel.
HAZARD OF ELECTRIC SHOCK, b No responsibility is assumed by Schneider Electric
EXPLOSION, OR ARC FLASH for any consequences arising out of the use of this
Disconnect all power before servicing material.
equipment. b This document is also available in French, Spanish,
Italian, German, and Chinese for download on our
Failure to follow these instructions
website at www.schneider-electric.com.
will result in death or serious injury.

A
Operating and Function
b LR97D, solid state overload relay, compares motor Type Relay setting range
current with preset load current threshold (LOAD). LR97D015 0.3 - 1.5 A
b Three phase motor currents are monitored through LR97D07 1.2 - 7 A
three internal current transformers. LR97D25 5 - 25 A
b D-Time counts down and is only available for LR97D38 20 - 38 A
motor starting.
During steady state, if motor current is greater than the current setting (overloaded), LR97D
switches its contacts after O-Time.
In case of phase failure and locked rotor, trip delay time is 3 s and 0.5 s respectively.
b For shear-pin (mechanical shock) protection, set O-Time knob to its minimum in order to trip in 0.2-0.3 s.

B Green LED
(LED OK)
Combined signals from red and green LEDs indicate
motor status including trip causes.
Red LED LED Signal (Pulse Chart)
Condition
Green LED Red LED
(LED OL)
Power on On Off
Reset Starting
D-Time
Steady state On Off
Load
O-Time Test/Stop Overloading On
Power Trip Overcurrent Off On
supply A1 A2 98 NO 95 NC 96 Relay output
Locked rotor Off
2T1 4T2 6T3 Phase L1 Off
Loss
L2 Off
(1) Select function by dip switch: L3 Off
b dip switch 1: 1 phase / 3 phase
b dip switch 2: Manual / Auto reset Available for 3 phase utilisation only (Dip SW on "3P" position)

W9 1636662 01 A03
02 - 2011
1/4
C 45
1.77
5.2
0.2
67.5
2.66

0.51
13
mm
in.

2.09
53
A1 A2 98 NO 95 NC 96

2T1 4T2 6T3

5 x M3 3 x M4

D
LC1D LR97D 2
+ + 1
LR97D LAD7B106

2
1

E
L1 L2 L3
MCCB
FUSE Tr.

OFF
E------ (RESET)
TEST/STOP

KM1 13
KM1 LAD7C1 LAD7C2
RESET

E--- START
14 D09/12/18 D25/35/38
L1 L2 L3
LR97D
A1 A2 98 95 96

A2
A1 A2 98 95 96
KM1
A1
T1 T2 T3
M
~3
Note:
b LR97D may be influenced by the harmonics on the control power.
b The control power should be supplied via the isolated transformer.
b Output : Normally energized.
b In case of LAD7C1 and LAD7C2 utilisation, it is impossible to wire electrically a trip status signalling.

W9 1636662 01 A03 2/4


F Extension leg shall be added in association
with Tesys Contactor from LC1D25 to LC1D38
LAD7C1 LAD7C2 Extention leg
D09/12/18 D25/35/38 D25/32/38

When putting 2 ring lug in the same terminal,


plug one after the other as below

G Protective Item Operating


Characteristics
Trip Delay Time Imax: Maximum phase current
Imin: Minimum phase current
Overcurrent Imax > Is O-Time Is: Overload setting current
Phase Loss Imin < 10 % of Imax < 3 s
Locked Rotor Imax > 3 x Is Starting: D-Time
Running: < 0.5 s

Setting Guide
b In case machine operates its full load.
1. Adjust Load, D-Time and O-Time knobs to their
maximum value. Then start motor. Adjustable load current
2. Adjust D-Time knob to the known motor start-up time. Current
If start-up time is unknown, use clamp current
meter to find its value.
Is Is = Setting
3. When motor reaches steady state, adjust Load knob current
counterclockwise until the red LED start to flicker. I=0
Then slowly adjust the Load knob clockwise until red
LED stops flickering. Time
4. Adjust O-Time knob to the desired trip delay time.
D-Time O-Time Auto reset : 120 s fixed
b In case load of machine is unknown or load with
high fluctuation.
1. Adjust Load knob to motor's nominal current or just
upper value. Output Relay
2. Adjust D-Time to the calculated time which take
into account the machine feature(Torque, Inertia)
96
3. Adjust O-Time to desired trip relay time.
95
b As shock relay utilisation, set O-Time at the 98
Start/Motor ON
minimum scale (tripping time: 0.2-0.3 s) Power Supply : A1, A2 Reset

W9 1636662 01 A03 3/4


H
Reset Function switch
b Manual: Immediate reset by RESET button
b Electrical: Immediate reset by interrupting
control power (minimum 0.1 s).
b Auto: 120 s fixed, selectable by dip switch
(Over current trip only).

I
TEST Function available at no load
b When LR97D is powered, keep Test button
pushed for D-Time plus O-Time till
internal relay switches its contact.
b Periodic test is recommended.
95 98
RESET
95 96

95 96 TEST

J
Stop Function while motor is running.
b Must be associated with 3-wire control circuit.
b The motor will be stopped immediately by pressing the TEST/STOP button.
In this case, LR97D is automatically reset.

W9 1636662 01 A03 4/4