PLEASE NOTE:
DANGER b Electrical equipment should be installed, operated,
serviced, and maintained only by qualified personnel.
HAZARD OF ELECTRIC SHOCK, b No responsibility is assumed by Schneider Electric
EXPLOSION, OR ARC FLASH for any consequences arising out of the use of this
Disconnect all power before servicing material.
b This document is also available in French, Spanish,
equipment.
Italian, German, and Chinese for download on our
Failure to follow these instructions website at www.schneider-electric.com.
will result in death or serious injury.

A
Operating and Function
b LT47, solid state overload relay, compares motor Type Relay setting range
current with preset load current threshold (LOAD). LT 4706 0.5 - 6 A
b Motor currents are monitored through two internal LT 4730 3 - 30 A
current transformers.
LT 4760 5 - 60 A
b CT hole size is 12 mm in diameter. Please don't
allow excessive force on CTs.
b D-Time counts down and is only available for motor starting.
During steady state, if motor current is greater than current
setting(overloaded), LT47 switches its contacts after O-Time.
b For shear-pin (mechanical shock) protection, set O-Time knob
to its minimum in order to trip in 0.2-0.3 s.

W9 1636671 01 A03
02 - 2011
1/4
B Standard type (Manual / Electrical reset)

Combined signals from red and green LEDs indicate


motor status including trip cause.
Green LED
(LED OK) LED Signal
Condition
D-Time Red LED Green LED Red LED
Load (LED OL) Power on On Off
O-Time Test/Stop Starting
A1 A2 97 NO 98 95 NC 96
Reset Steady state On Off
Overloading On
Trip Off On
Auto Reset type
Off On Flickering
Green LED
(LED OK)
O-Time Red LED
Load (LED OL)
Test/Stop
R-Time
A1 A2 97 NO 98 95 NC 96
Reset

C
mm
77,2 63
in. Ø 12 3.04 2.48
Ø 0.47 62,2 51
2.45 2.01
Ø4.5
19.5
0.77

Ø0.18

20.4
0.80
PULL PULL
50.8
2.00

TEST/STOP

30.4
1.20
LOAD (A) D-TIME (s) O-TIME (s) RESET

A1 A2 97 NO 98 95 NC 96

56
6 x M3.5
2.20

W9 1636671 01 A03 2/4


D L1 L2 L3
MCCB
Note:
b LT47 may be influenced by the
Tr. harmonics on the control power.
FUSE
b The control power should be
supplied via the isolated transformer.
OFF b Output: Normally energized.

TEST/STOP
E------ (RESET)

RESET
KM1 13
KM1 E---START
14 Line
A1
KM1
96 A2
95
98
97
A2
A1
LT47
Load
M
~3 Straight-through-Wiring

When motor current is less than minimum current setting Line


(< 0.5A), looping conductors through CT holes can
be used. The following table explains number of looping
for low current setting.

No. of Loops Time of Passing Current Set. Range (A)


LT4706 0 1 0.50 - 6.0 A
1 2 0.25 - 3.0 A
Looping 2 3 0.17 - 2.0 A Load
Option 3 4 0.12 - 1.5 A Looping Option (1-Loop)
4 5 0.10 - 1.2 A

1
3
A1 A2 97 NO 98 95 NC 96

When putting 2 ring lug in the same terminal,


plug one after the other as shown in figure.

W9 1636671 01 A03 3/4


E
Setting Guide - Manual reset type
b Machine which can be loaded to its full load during the setting
1. Adjust Load, D-Time and O-Time knobs to their maximum value. Then start motor.
2. Adjust D-Time knob to the known motor start-up time. If start-up time is unknown, use clamp
current meter to find its value.
3. When motor reaches steady state, adjust Load knob counterclockwise until the red LED start
to flicker. Then slowly adjust the Load knob clockwise until red LED stops flickering.
4. Adjust O-Time knob to the desired trip delay time.
b Machine's load is unknown or load with high fluctuation.
1. Adjust Load knob to motor's nominal current or just upper value.
2. Adjust D-Time to the calculated time which take into account the machine feature (Torque, Inertia).
3. Adjust O-Time to desired trip relay time.
Setting Guide - Auto reset type
b Machine which can be loaded to its full load during the setting
1. Adjust Load and O-Time knobs to their maximum value.
Then start motor.
2. Adjust O-Time knob to a few seconds more than Adjustable
motor start-up time. If start-up time is unknown, Current
use clamp current meter to find its value.
3. When motor reaches steady state, adjust Load knob Is Is = Setting
counterclockwise until the red LED start to flicker. current
I=0
Then slowly adjust the Load knob clockwise
until red LED stops flickering. Time
4. Adjust R-Time knob to the desired auto-reset delay
time(1...120 s). D-Time O-Time Auto reset Time:
R-Time
b Machine's Load is unknown or load with high Output Relay
fluctuation.
1. Adjust Load knob to motor's nominal current or just 95 NC 96
upper value.
2. Adjust O-Time to the calculated time which take into 97 NO 98
Start/Motor ON
account the machine feature (Torque, Inertia). Power Supply : A1, A2 Reset
3. Adjust R-Time to desired auto-reset delay time. Note:
As shock relay utilisation, set O-Time at the
minimum scale (tripping time: 0.2-0.3 s).

F G H
Reset TEST function Stop function
available at no while motor is
load. running.
b Manual: Immediate reset b When LT47 is powered, keep b Must be associated
by RESET button Test button pushed for with 3-wire control
b Electrical: Immediate reset D-Time plus O-Time (Manual circuit.
by interrupting control reset type) or O-Time (Auto b The motor will be stopped
power (minimum 0.1s). reset type), till the internal immediately by pressing the
relay switches its contact. TEST/STOP button. In this
b Auto: reset by preset
R-Time, 1...120 s adjustable, b Periodic test is recommended. case, LT47 is automatically
Auto Reset type only. reset.

W9 1636671 01 A03 4/4