Model FFS / FFX

Architectural Linear Flow Bar Diffusers

Introduction
Jersey Linear Flow Bar is an architecturally designed
high capacity linear diffuser. It is designed to combine a
high air handling capacity with maximum flexibility and is
suitable for either ceiling or sidewall applications. The
flexibility of the system can blend into a design or
provide contrast with its striking but simple design. The
Flow Bar system satisfies the requirements for
designing an air distribution system, whilst becoming
an integral component of the architectural concept of
the project.
Application
• Linear diffuser system with engineered
• Desirable large capacity, single slot appearance
• Versatile pattern control for installation in low or high
sidewalls and ceilings
• Adjustable for horizontal or vertically projected air Pattern Control Flexibility
discharge patterns.
Horizontal Left
• Excellent for VAV applications
• Drywall / hard surface and suspended ceiling
applications
• Configured to your specification - Curvatures
• Mitered corners for ceiling and wall mounts.
Product Features
• Construction from heavy extruded aluminum 6063-T5
• 3m lengths available to minimize joints
• 25mm, 38mm, 50mm slot widths Horizontal Right
• 1 slot or 2 slots
• Field adjustable pattern controllers for horizontal left or
right, or vertical projection air discharge patterns
• Controllers are cut to nominal 600mm (allows for
alternating pattern
• changes within the run from left or right horizontal, to
vertical)
• Powder Coated to RAL 9010 finish
• Pattern Controllers are black.
• Center T’s on multiple slot units are RAL9010 Vertical

• Frameless Linear Flow Bar diffusers.


Options
• Custom RAL colours
• Mitered Corners
• Blank off Panels
• Curved Linear Flow bar diffusers to suit ceiling or wall
applications (air flow directions should be provided)

Flange Types

Type “S” - Standard Type “X” - Flangeless Product Selection Check List
(Surface mounting) • Select unit Length based on performance
• Review Architectural requirements
• Select slot width and number of slots required
• Select Type of Frame required
• Select End Connection requirements
• Select Accessories
• Select RAL colour required

*In the interest of product development, Jersey Manufacturing reserves the right to make changes without notice.

w ww .je rse yg rou p.com Jersey Manufacturing


1
Model FFS / FFX
Architectural Linear Flow Bar Diffusers

Type “S” Standard Frame ( Surface mounting)


FFS - 1 SLOT

D=DUCT OPENING
DIMENSIONS
DUCT
(BY OTHERS)
Model FFS (Supply) – with Pattern Control
Model FFS-R (Return) – Pattern control excluded
F
DAMPER Model FFS Pattern Control
(ONLY FOR
SUPPLY) Model FFS-R Control excluded
43

Model FFS-25 (25mm Slot Width)


3 G H # of SLOTS C D E F G H J
10 E=CEILING OPENING CEILING LINE
1 95 73 75 69 25 35 -
C
2 156 134 136 130 25 35 36
FFS - 2 SLOT

D=DUCT OPENING Model FFS-38 (38mm Slot Width)


DUCT
(BY OTHERS) # of SLOTS C D E F G H J

1 122 99 101 95 38 42 -
F
DAMPER
(ONLY FOR
2 209 186 188 182 38 42 49
SUPPLY)
43

Model FFS-50 (50mm slot width)


# of SLOTS C D E F G H J
3 J G H
10 E=CEILING OPENING CEILING LINE 1 147 125 127 121 50 48 -
C
2 260 238 240 234 50 48 62

Type “X” Flangeless Frame


FFX - 1 SLOT
DIMENSIONS
D=DUCT OPENING
DUCT
(BY OTHERS) Model FFX (Supply) – with Pattern Control
Model FFX-R (Return) – Pattern control excluded
F
DAMPER Model FFX-25 (25mm Slot Width)
(ONLY FOR
SUPPLY) # of SLOTS C D E F G H J
43

1 69 73 69 69 25 35 -

2 130 134 130 130 25 35 36


G H
E=CEILING OPENING CEILING LINE
C Model FFX-38 (38mm Slot Width)
# of SLOTS C D E F G H J
FFX - 2 SLOT
1 95 99 95 95 38 42 -
D=DUCT OPENING
DUCT
(BY OTHERS)
2 182 186 182 182 38 42 49

F
Model FFX-50 (50mm slot width)
DAMPER
(ONLY FOR # of SLOTS C D E F G H J
SUPPLY)
1 121 125 121 121 51 48 -
43

2 234 238 234 234 51 48 62

J G H
E=CEILING OPENING CEILING LINE
C

END CAP- MODEL - FFS END CAP- MODEL - FFX

L L
43

43

28
L+56 1.5
L3+
'L' : LENGTH OF FFS FRAME
'L' : LENGTH OF FFX FRAME

*In the interest of product development, Jersey Manufacturing reserves the right to make changes without notice.

Jersey Manufacturing w w w . j e r s e yg r o u p.co m


Model FFS / FFX
Architectural Linear Flow Bar Diffusers

Face Miter Corner FACE MITER CORNER Custom Curvatures


F A
Custom Ceiling Curvature
E
GL
AN
Custom Formed Radius

Model FFS-25 (25mm Slot Width) Model FFS-25 (25mm Slot Width)
# of SLOTS F L A # of SLOTS F L A

1 95 245 150 1 70 220 150 Custom Formed Radius

2 157 307 150 2 132 282 150

Model FFS-38 (38mm Slot Width) Model FFS-38 (38mm Slot Width)
# of SLOTS F L A # of SLOTS F L A

1 121 270 150 1 96 245 150

2 208 358 150 2 183 333 150 Custom Wall Curvatures

Model FFS-50 (50mm slot width) Model FFS-50 (50mm Slot Width)
Custom Formed Radius
# of SLOTS F L A # of SLOTS F L A

1 146 296 150 1 121 271 150

2 259 408 150 2 234 383 150


SIDE THROW - CONCAVE

Stack Miter Corner


43

A Custom Formed Radius


F

SIDE THROW - CONVEX


43

ACCESSORIES
Model FFS-25 (25mm Slot Width) Model FFS-25 (25mm Slot Width)
# of SLOTS F L A # of SLOTS F L A
Blank Off Plates
1 95 193 150 1 70 193 150

2 157 193 150 2 132 193 150

Model FFS-38 (38mm Slot Width) Model FFS-38 (38mm Slot Width)
# of SLOTS F L A # of SLOTS F L A

1 121 193 150 1 96 193 150

2 208 193 150 2 183 193 150

Model FFS-50 (50mm slot width) Model FFS-50 (50mm Slot Width)
# of SLOTS F L A # of SLOTS F L A

1 146 193 150 1 121 193 150

2 259 193 150 2 234 193 150

*In the interest of product development, Jersey Manufacturing reserves the right to make changes without notice.

w ww .je rse yg rou p.com Jersey Manufacturing


3
Model FFS / FFX
Architectural Linear Flow Bar Diffusers

Performance Data

FF*- 25 25mm Slot width - Horizontal Pattern - One way

# CMH/M/
110 138 166 221 277 332 388 443 498 554
SLOTS SLOT

CMH 110 138 166 221 277 332 388 443 498 554

Ps 5.0 7.0 11.0 17.0 28.0 35.0 53.0 75.0 104.0 116.0
1
NC <15 <15 <15 19 22 28 32 35 38 41

Throw 1 2 4 2 2 4 2 3 5 3 4 6 3 4 7 4 5 8 4 6 8 5 6 8 5 7 9 6 7 10

CMH 220 276 332 442 554 664 776 886 996 1108

Ps 5.0 7.0 11.0 17.0 28.0 35.0 55.0 77.0 110.0 124.0
2
NC <15 <15 <15 20 24 30 34 37 40 44

Throw 2 3 5 2 3 6 3 4 7 4 5 8 4 6 10 5 7 10 6 8 11 6 8 12 7 9 13 8 10 13

FF*- 38 38mm Slot width - Horizontal Pattern - One way

# CMH/M/
166 221 277 332 388 443 498 554 609 665
SLOTS SLOT

CMH 166 221 277 332 388 443 498 554 609 665

Ps 9.0 14.0 20.0 25.0 33.0 42.0 55.0 77.0 97.0 121.0
1
NC <15 <15 <15 20 24 27 31 33 37 40

Throw 2 3 5 3 4 6 3 4 7 4 5 7 4 6 8 5 6 8 5 6 9 6 7 9 6 7 10 6 7 10

CMH 332 442 554 664 776 886 996 1108 1218 1330

Ps 9.0 14.0 20.0 28.0 33.0 42.0 61.0 77.0 99.0 124.0
2
NC <15 <15 16 22 27 31 35 38 41 44

Throw 3 4 7 4 5 8 4 6 9 5 7 10 6 8 11 7 8 11 7 9 12 8 9 13 8 10 13 8 10 14

FF*- 50 50mm Slot width - Horizontal Pattern - One way

# CMH/M/
332 388 443 498 554 609 665 720 776 831
SLOTS SLOT

CMH 332 388 443 498 554 609 665 720 776 831

Ps 9.0 14.0 20.0 25.0 35.0 42.0 55.0 77.0 94.0 124.0
1
NC <15 19 23 26 31 33 35 37 39 41

Throw 3 5 8 4 5 8 4 6 8 5 7 9 5 7 10 6 7 10 6 8 10 6 8 11 7 8 11 7 8 11

CMH 664 776 886 996 1108 1218 1330 1440 1552 1662

Ps 9.0 14.0 20.0 25.0 35.0 42.0 55.0 77.0 94.0 124.0
2
NC 19 22 28 31 34 36 38 40 42 44

Throw 4 7 10 5 8 11 6 8 12 7 9 13 7 10 13 8 10 14 8 10 15 9 11 15 9 11 15 10 11 16

Test Standard
ANSI / ASHRAE standard 70 “Method of Testing for Rating the Performance of Air Outlets and Inlets”

Data is based on 1200mm active length. For other active lengths, use the following adjustment factors

If Diffuser Length is 0.6m 1.2m 1.8m 3.6m 4.8m+

Adjust NC value by -3 0 +2 +3 +4

If Diffuser Length is 0.70 1.00 1.20 1.40 1.60

*In the interest of product development, Jersey Manufacturing reserves the right to make changes without notice.

Jersey Manufacturing w w w . j e r s e yg r o u p.co m


Model FFS / FFX
Architectural Linear Flow Bar Diffusers

Performance Data

FF*- 25 25mm Slot width - Vertical Projection (Free Jet)

# CMH/M/
139 167 195 222 278 333 389 444 499 555
SLOTS SLOT

CMH 139 167 195 222 278 333 389 444 499 555

Ps 3 7 10 11 14 20 28 35 42 55
1
NC <15 <15 <15 18 22 24 25 28 30 32

Throw 1 2 4 2 2 4 2 3 5 2 3 5 3 4 6 3 4 7 3 5 7 4 5 8 4 6 8 5 6 8

CMH 278 334 390 444 556 666 778 888 998 1110

Ps 3 7 10 11 14 20 28 35 42 55
2
NC <15 <15 <15 20 23 24 25 28 31 33

Throw 2 3 5 2 3 6 3 4 7 3 4 8 4 5 8 4 6 9 4 7 10 5 8 11 6 8 11 6 8 12

FF*- 38 38mm Slot width - Vertical Projection (Free Jet)

# CMH/M/
167 222 278 333 389 444 499 555 610 666
SLOTS SLOT

CMH 167 222 278 333 389 444 499 555 610 666

Ps 6 9 11 14 20 25 28 33 39 44
1
NC <15 <15 <15 19 22 24 26 29 32 34

Throw 1 2 4 2 2 4 2 3 5 2 4 6 3 4 7 3 4 7 4 5 7 4 5 8 4 6 8 4 6 8

CMH 334 444 556 666 778 888 998 1110 1220 1332

Ps 6 9 11 14 20 25 28 33 39 44
2
NC <15 <15 18 21 23 24 28 29 32 35

Throw 2 3 5 2 3 6 3 4 8 3 5 8 4 5 9 4 6 10 5 7 10 5 8 11 6 8 11 6 8 12

FF*- 50 50mm Slot width - Vertical Projection (Free Jet)

# CMH/M/
389 444 499 555 610 666 721 777 832 887
SLOTS SLOT

CMH 389 444 499 555 610 666 721 777 832 887

Ps 6 9 11 14 20 25 28 33 39 44
1
NC <15 <15 17 19 21 22 24 25 27 31

Throw 2 3 6 3 4 7 3 4 8 3 5 8 4 5 8 4 5 9 4 6 9 4 6 9 5 7 10 5 7 10

CMH 778 888 998 1110 1220 1332 1442 1554 1664 1774

Ps 6 9 11 14 20 25 28 33 39 44
2
NC <15 <15 18 20 21 23 24 26 28 31

Throw 3 4 9 4 5 10 4 6 11 4 6 11 5 7 11 5 8 12 6 8 13 6 9 13 6 9 14 7 10 14

Test Standard
ANSI / ASHRAE standard 70 “Method of Testing for Rating the Performance of Air Outlets and Inlets”

Data is based on 1200mm active length. For other active lengths, use the following adjustment factors

If Diffuser Length is 0.6m 1.2m 1.8m 3.6m 4.8m+

Adjust NC value by -3 0 +2 +3 +4

If Diffuser Length is 0.70 1.00 1.20 1.40 1.60

*In the interest of product development, Jersey Manufacturing reserves the right to make changes without notice.

w ww .je rse yg rou p.com Jersey Manufacturing


5
Model FFS / FFX
Architectural Linear Flow Bar Diffusers

Performance Data - Return Air

FFR-25 (25mm Slot Width) FFR-38 (38mm Slot Width) FFR-50 (50mm Slot Width)
1 Slot 2 Slot 1 Slot 2 Slot 1 Slot 2 Slot
CMH/M CMH/M CMH/M
Ps NC Ps NC Ps NC Ps NC Ps NC Ps NC

110 3.0 - 110 221 3.0 -

221 10.0 - 3.0 - 221 5.0 - 332 5.0 -

332 23.0 20 5.0 - 332 8.0 - 3.0 - 443 8.0 - 3.0 -

443 43.0 24 10.0 - 443 15.0 - 5.0 - 554 13.0 - 3.0 -

554 65.0 29 15.0 - 554 23.0 20 5.0 - 692 20.0 - 5.0 -

665 23.0 21 665 33.0 23 8.0 - 831 30.0 22 8.0 -

776 33.0 23 776 43.0 25 10.0 - 970 40.0 25 10.0 -

886 43.0 25 886 55.0 27 15.0 - 1108 50.0 27 13.0 -

997 53.0 28 997 68.0 29 18.0 - 1247 65.0 30 18.0 -

1108 1108 85.0 31 23.0 21 1385 20.0 20

1219 1219 28.0 22 1662 30.0 23

1330 1330 33.0 24 1940 40.0 26

1441 1441 38.0 25 2217 50.0 28

Test Standard
ANSI / ASHRAE standard 70 “Method of Testing for Rating the Performance of Air Outlets and Inlets”

Data based on non-ducted, pressurized ceiling plenum applications. Ducted plenums should be sized with inlet velocities less than 750 fpm while maintaining equal
discharge velocities along the diffuser length to maintain catalogue data.

Sound Levels
NC is noise criteria curve that will not be exceeded at the operating point. This is determined by assuming a 10dB (ref: 10-12 watts) room attenuation that is subtracted
from the power levels in each of the 2nd thru 7th octave bands
NC shown is based on 1200mm diffuser length. For other active lengths, use the following adjustment factors:

If Diffuser Length is 0.6m 1.2m 1.8m 3.6m 4.8m+

Adjust NC value by -3 0 +2 +3 +4

Throw (Horizontal Pattern)


The numbers shown in table are throw distances, in meters, measured along the jet trajectory axis relating to terminal velocities of 0.75m/s,0.5m/s, & 0.25m/s, with the jet
attached to a surface for a 4.8m+ active length. These are ONE-way patterns. For other active lengths, use the following throw adjustment factors:

If Diffuser Length is 0.6m 1.2m 1.8m 3.6m 4.8m+

Adjust NC value by 0.70 1.0 1.2 1.4 1.6

For installation with a free, unattached jet, multiply throw value by 0.70. For two way applications, determine proportion of air in each direction and refer to throw distance
for number of slots in the same direction.

Terminal velocity is the air speed, in meters per second, measured in the supply air stream

Pressure
Ps represents Static Pressure, Pa

*In the interest of product development, Jersey Manufacturing reserves the right to make changes without notice.

Jersey Manufacturing w w w . j e r s eyg r o u p .co m


Model FFS / FFX
Architectural Linear Flow Bar Diffusers

*In the interest of product development, Jersey Manufacturing reserves the right to make changes without notice.

w ww .je rse yg rou p.com Jersey Manufacturing


7

You might also like