VIETNAM ELECTRICITY
TRI AN HYDROPOWER COMPANY
LOT NO.5:“DESIGN,MATERIAL,EQUIPMENT SUPPLY AND
TECHNICAL SERVICES”
CONTRANT NO:99/HD-TDTA/ALSTOM
PURCHASER: SUPPLIER:
ALSTOM-HYDRO
CSCS
CONTROLOG FUNCTION TEST PROCEDURE
SCALE SIZE
SUBSUPPLIER:
A4
1.3.2 Configuration.................................................................................................................. 6
1.1 AIMS
The document to be validated is the system considered from the functional point of
view in conformance with the Standard General Technical Specifications.
The aim of the session is to verify:
- The functional aspects
- The system management aspects
• System start-up/shutdown,
• Maintenance tools
• Redundancy management,
• Gateway functions (IEC60870.5-101/104)
At the start of the session, AHC hands over the pre-acceptance document to the
customer. This document is identical to the Acceptance Test Book and demonstrates
that AHC has already run all the tests. The customer then indicates which of the tests
in the book he wishes to verify.
The different Acceptance Forms are passed in the order defined in the Acceptance
Test Book.
As the tests proceed the forms are completed with the following information:
• initial conditions,
• results observed,
• result of the step: accepted, refused, accepted with reservation,
• any remarks.
For each step or sub-step, the full series of results is entered on an Acceptance Test
Report Form. Any anomalies are entered on an Anomaly Report (RA) and indexed on
the Acceptance Test Report Form.
PROJECT TRI AN
CE1500
CP1485-1 - CPU NA
ALSPA HMI - VERSION 6.3.17
1.3.2 Configuration
The test platform will be composed of the ALSPA CONTROPLANT Serial 6 system of this project.
Please refer the doc:
H-10207 00 0EA00-001F FA-CSCS SYSTEM CONFIGURATION DIAGRAM
The aim of this step is to review the supervision functions described in the documents
below:
- PTP 20A48014
ALSPA Series 6 CONTROPLANT Hydro DCS LX Architecture
- GFR-020C04020-EDC-200092-en-A
ALSPA HMI - V6 - Bargraphs & Trends Viewers - Reference Manual
- GFR-020C04020-EDC-200082-en-A
ALSPA HMI - V6 - Y=f(x) Curve Viewer - Reference Manual
- GFR-020C04020-EDC-200080-en-B
ALSPA HMI - V6 - Y=f(t) Curve Viewer - Reference Manual
2. Access to Mimics
Assign/Disassign a variable
Change scale
Assign/Disassign a variable
Change scale
Assign/Disassign a variable
Change scale
Assign/Disassign a variable
Show All
Show Boolean
Show Analog
Show Command
Show Set-point
1. Check of Access
Acknowledge alarm
Acknowledge alarm
5. Check of Chronology
Initial conditions
The control blocks utilised in this section are those used to test the Command
and Set point transmission control functions.
Setpoint
Command
Transmit a setpoint
Transmit a command
The printer output functions are presented in detail in the following documents:
- GFR-020C04020-EDC-200073-en-B
ALSPA HMI - V6 - Workspace - Reference Manual
This function is available for Control room station and simulator station.
HISTORIAN functions are presented in detail in the following documents:
- GFR-020C04020-EDC-200091-en-C
ALSPA HMI - V6 - Historian Function - Reference Manual
2. Consultation of samples
Change zoom
3. Consultation of events
Store a base
Consult samples
Consult events
- ALSPA_Series6_Response_Time
ALSPA Series 6 - System Response Time - PPT
Update Views
Update Sheets
Sub-step: HMI
ACCEPTANCE FORM
Sub-step: System
Status: C30/CIS/S8000/MFC3000
Status: CE1000
Status: HISTORIAN
Status: CVS
Status: C10
- GFR-020C04010-EDC-202007-en-B
ALSPA Controcad - V5 - Mimics Views Configuration - Reference Manual
1. Mimics Modification
Modify a Mimic
Update Views
2. Database Modification
Modify a variable
Generate Database
Select database
Update database
Project: TRI AN
System ALSPA CONTROPLANT Serial 6
Qualitative appraisal
Remarks:
Company : Company :
Name : Name :
Position : Position :
Signature : Signature :