Professional Documents
Culture Documents
Comments
SigN Date
SigN.
SigN.
SigN.
SigN.
SigN.
SigN.
VIETNAM ELECTRICITY
TRI AN HYDROPOWER COMPANY
LOT NO.5:“DESIGN,MATERIAL,EQUIPMENT SUPPLY AND
TECHNICAL SERVICES”
CONTRANT NO:99/HD-TDTA/ALSTOM
PURCHASER: SUPPLIER:
ALSTOM-HYDRO
UNIT LCU1&2&3&4
APPLICATION PROGRAM
SCAL SIZE
E
SUBSUPPLIER:
A4
REV. SH/SH N of
S
H-10207 00 CJA 00-001F FT END
A
1/240 240
TABLE DES MODIFICATIONS / MODIFICATIONS TABLE
XX PXXXXA4XXXX.3/A
4.32 SIG : SIGNALS - REV : 46 - 22/DEC/16 11:54 - POUName : L01_6SIG ................................................144
4.33 CON : CONDITIONS - REV : 44 - 14/JAN/17 09:19 - POUName : L01_3CON ......................................145
4.34 SIG : SIGNALS - REV : 37 - 22/DEC/16 11:54 - POUName : L01_6SIG ................................................146
4.35 CON : CONDITIONS - REV : 37 - 22/DEC/16 11:54 - POUName : L01_3CON ......................................147
4.36 SIG : SIGNALS - REV : 38 - 22/DEC/16 11:54 - POUName : L01_6SIG ................................................148
4.37 CON : CONDITIONS - REV : 52 - 14/JAN/17 09:18 - POUName : L01_3CON ......................................149
4.38 SIG : SIGNALS - REV : 44 - 22/DEC/16 11:54 - POUName : L01_6SIG ................................................151
4.39 CON : CONDITIONS - REV : 33 - 22/DEC/16 11:54 - POUName : L01_3CON ......................................152
4.40 SIG : SIGNALS - REV : 40 - 22/DEC/16 11:54 - POUName : L01_6SIG ................................................153
4.41 CON : CONDITIONS - REV : 31 - 22/DEC/16 11:54 - POUName : L01_3CON ......................................154
4.42 SIG : SIGNALS - REV : 35 - 22/DEC/16 11:54 - POUName : L01_6SIG ................................................155
4.43 CON : CONDITIONS - REV : 24 - 22/DEC/16 11:54 - POUName : L01_3CON ......................................156
4.44 SIG : SIGNALS - REV : 35 - 22/DEC/16 11:54 - POUName : L01_6SIG ................................................157
4.45 CON : CONDITIONS - REV : 39 - 22/DEC/16 11:54 - POUName : L01_3CON ......................................158
4.46 SIG : SIGNALS - REV : 44 - 03/JAN/17 15:36 - POUName : L01_6SIG .................................................160
4.47 CON : CONDITIONS - REV : 49 - 30/DEC/16 14:31 - POUName : L01_3CON ......................................161
4.48 SIG : SIGNALS - REV : 37 - 22/DEC/16 11:54 - POUName : L01_6SIG ................................................162
4.49 DE001 : UNIT ACTIVE POWER CONTROL - REV : 214 - 14/JAN/17 09:22 - POUName : L01_5ACT .163
4.50 DE002 : UNIT REACTIVE POWER CONTROL - REV : 210 - 14/JAN/17 09:21 - POUName : L01_5ACT
168
4.51 CON : CONDITIONS - REV : 27 - 22/DEC/16 11:54 - POUName : L01_3CON ......................................172
4.52 SIG : SIGNALS - REV : 25 - 22/DEC/16 11:54 - POUName : L01_6SIG ................................................173
4.53 CON : CONDITIONS - REV : 22 - 22/DEC/16 11:54 - POUName : L01_3CON ......................................174
4.54 SIG : SIGNALS - REV : 20 - 22/DEC/16 11:54 - POUName : L01_6SIG ................................................175
4.55 CON : CONDITIONS - REV : 26 - 14/JAN/17 09:18 - POUName : L01_3CON ......................................176
4.56 SIG : SIGNALS - REV : 22 - 22/DEC/16 11:54 - POUName : L01_6SIG ................................................178
4.57 GS003 : Disconnector Switch - REV : 61 - 22/DEC/16 11:54 - POUName : L01_5ACT .........................179
4.58 EB000 : L01 WATCHDOG - REV : 103 - 22/DEC/16 12:10 - POUName : L01_6SIG .............................181
4.59 GS901 : GCB - REV : 139 - 14/JAN/17 09:34 - POUName : L01_5ACT .................................................184
4.60 DG001 : WG OPENING LOAD CONTROL - REV : 56 - 22/DEC/16 11:54 - POUName : L01_5ACT ....187
4.61 DE003 : UNIT VOLTAGE CONTROL - REV : 48 - 14/JAN/17 09:21 - POUName : L01_5ACT ..............189
5 INTERNAL VARIABLES ..................................................................................................................................192
9 FORCED SFC...................................................................................................................................................239
XX PXXXXA4XXXX.4/A
LIST OF MODIFIED TABLES AND DIAGRAMS
XX PXXXXA4XXXX.5/A
1 EXTERNAL INTERFACES
XX PXXXXA4XXXX.6/A
NAME DESCRIPTION STATE INIT AL I/O FROM TO
01BAC00_GS901_ZL1 UNIT SELF SYNCHRONIZE HMI 186[17]
1 MODE ON CMD
01BAC00_GS901_ZL1 UNIT SELF SYNCHRONIZE HMI 186[14]
2 MODE OFF CMD
01BAC00_GS901_ZM1 UNIT GCB 185[21] HMI
0
01BAC00_GS901_ZM1 UNIT GCB CLOSG ORD 1 185[21] HMI
1
01BAC00_GS901_ZM1 UNIT GCB OPENG ORD 1 185[21] HMI
2
01BAC00_GS901_ZU0 UNIT GCB GS901 ANIMATION 185[21] HMI
1 WORD
01BAT00_CE002_XQ0 MAIN TRANSFORMER ZERO 0 <-> 100 L01_01-0-18-3 HMI
1 SEQUENCE VOLTAGE
01BAT00_EN001_XM0 TRANSF COOLING SYS IN L01_03-0-6-0 HMI
1 MANUAL POSITION
01BAT00_EN001_XM0 TRANSF COOLING SYS PUMP 2 L01_03-0-6-1 HMI,112[2]
2 MAIN POWER FAILURE
01BAT00_EN001_XM0 TRANSF COOLING SYS DC 2 L01_03-0-6-2 HMI,112[2]
3 POWER CONTROL FAILURE
01BAT00_EN001_XM0 TRANSF COOLING SYS PUMP 2 L01_03-0-6-3 HMI,112[2]
4 BACKUP POWER FAILURE
01BAT00_EN001_XM0 MAIN TRANSFORMER 2 L01_03-0-6-4 HMI,112[2]
5 COOLING SYSTEM FAILURE
01BAT00_EN001_XM0 TRANSF COOLING SYS B1 2 L01_03-0-6-5 HMI,112[2]
6 PUMP FAILURE
01BAT00_EN001_XM0 TRANSF COOLING SYS B2 2 L01_03-0-6-6 HMI,112[2]
7 PUMP FAILURE
01BAT00_EN001_XM0 TRANSFORMER COOLING L01_03-0-6-7 HMI,66[15],112[2]
8 SYSTEM AUTO POSITION
01BAT00_EN001_XM0 TRANSF COOLING SYS 2 L01_03-0-6-8 HMI,112[2]
9 SHUTOFF VALVE POWER
FAILURE
01BAT00_EN001_XM1 MAIN TRANSFORMER HIGH OIL 2 L01_03-0-6-9 HMI
0 TEMPERATURE
01BAT00_EN001_XM1 MAIN TRANSFORMER FIRE 2 L01_03-0-6-10 HMI,112[2]
1 VALVE STUCK
01BAT00_EN001_XM1 TRANSF COOLING SYS VALVE 2 L01_03-0-6-11 HMI,112[2]
2 CONTROL POWER FAILURE
01BAT00_EN001_XM1 TRANSFORMER FIRE VALVE L01_03-0-7-0 HMI
3 MANUAL POSITION
01BAT00_EN001_XM1 TRANSFORMER FIRE AUTO 2 L01_03-0-7-1 HMI
4 ORDERED
01BAT00_EN001_XM1 TRANSFORMER FIRE MANUAL 2 L01_03-0-7-2 HMI
5 ORDERED
01BAT00_EN001_XM1 MAIN TRANSF DC MAIN 2 L01_03-0-7-3 HMI,112[2]
6 PROTECTION POWER FAILURE
01BAT00_EN001_XM1 MAIN TRANSF DC BACKUP 2 L01_03-0-7-4 HMI,112[2]
7 PROTECTION POWER FAILURE
01BAT00_EN001_XM1 MAIN TRANSF PT FUSE 2 L01_03-0-7-5 HMI,112[2]
8 FAILURE MONITOR
01BAT00_EN001_XM1 MAIN TRANSFORMER HIGH OIL 2 L01_03-0-7-6 HMI
9 LEVEL ALARM
01BAT00_EN001_XM2 MAIN TRANSFORMER LOW OIL 2 L01_03-0-7-7 HMI
0 LEVEL ALARM
01BAT00_EN001_XM2 AUX TRANSF LOW OIL LEVEL 2 L01_03-0-7-8 HMI
1 ALARM
01BAT00_EN001_XM2 AUX TRANSF HIGH OIL 2 L01_03-0-7-9 HMI
2 TEMPERATURE ALARM
01BAT00_EN001_XM2 MAIN TRANSFORMER 2 L01_03-0-7-10 HMI
3 THERMAL OVERLOAD
PROTECTION ALARM
01BAT00_EN001_XM2 AUX TRANSF THERMAL 2 L01_03-0-7-11 HMI
4 OVERLOAD PROTECTION
ALARM
01BAT00_EN001_XM2 MAIN TRANSFORMER GAS 2 L01_03-0-8-0 HMI
5 RELAY ALARM
01BAT00_EN001_XM2 AUX TRANSF GAS RELAY 2 L01_03-0-8-1 HMI
6 ALARM
01BAT00_EN001_XM2 13,8KV EARTH FAULT 2 L01_03-0-8-2 HMI
7 CONDUCTORS ALARM
01BAT00_EN001_XM2 RELAY PROTECTION SYSTEMS L01_03-0-8-3 HMI
8 TESTED POSITION
01BAT00_EN001_XM2 TRANSFORMER PROT SIGNAL 2 L01_03-0-8-4 HMI,112[2]
9 UNIT POWER SUPPLY 1
FAILURE
01BAT00_EN001_XM3 TRANSFORMER PROT SIGNAL 2 L01_03-0-8-5 HMI,112[2]
0 UNIT POWER SUPPLY 2
FAILURE
01BAT00_EN001_XM3 MAIN TRANSFORMER 1 L01_03-0-9-0 HMI
2 SHUTOFF VALVE TRIP
01BAT00_EN001_XM3 MAIN TRANSFORMER GAS 1 L01_03-0-9-1 HMI
3 RELAY TRIP
01BAT00_EN001_XM3 AUX TRANSF GAS RELAY TRIP 1 L01_03-0-9-2 HMI
4
01BAT00_EN001_XM3 MAIN TRANSFORMER 1 L01_03-0-9-3 HMI
5 COOLING SYSTEM TRIP
XX PXXXXA4XXXX.7/A
NAME DESCRIPTION STATE INIT AL I/O FROM TO
01BAT00_EN001_XM3 AUX TRANSFORMER 1 L01_03-0-9-4 HMI
6 PRESSUER HIGH OIL TRIP
01BAT00_EN001_XM3 MAIN TRANSFORMER 1 L01_03-0-9-5 HMI,113[1]
7 PROTECTION TRIP
01BAT00_EN001_XM3 MAIN TRANSFORMER BACKUP 1 L01_03-0-9-6 HMI,113[1]
8 PROTECTION TRIP
01BAT00_EN001_XM3 AUX TRANSFORMER MAIN 1 L01_03-0-9-7 HMI,113[1]
9 PROTECTION TRIP
01BAT00_EN001_XM4 AUX TRANSFORMER BACKUP 1 L01_03-0-9-8 HMI,113[1]
0 PROTECTION TRIP
01BAT00_EN001_XM4 FROM GENERATOR 1 L01_03-0-9-9 HMI
1 PROTECTION TRIP
01BAT00_EN001_XM4 MAIN TRANSFORMER 1 L01_03-0-10-0 HMI
2 DIFFERENTIAL PROTECTION
87T TRIP
01BAT00_EN001_XM4 MAIN TRANSF RESTRICTED 1 L01_03-0-10-1 HMI
3 EARTH FAULT PROTECTION
50REF TRIP
01BAT00_EN001_XM4 MAIN TRANSF OVERCURRENT 1 L01_03-0-10-2 HMI
4 PROTECTION FOR PHASE
50/51 TRIP
01BAT00_EN001_XM4 MAIN TRANSF OVERCURRENT 1 L01_03-0-10-3 HMI
5 PROTECTION FOR EARTH
50N/51N TRIP
01BAT00_EN001_XM4 LINE CONDUCTORS 1 L01_03-0-10-4 HMI
6 DIFFERENTIAL PROTECTION
87L TRIP
01BAT00_EN001_XM4 LINE CONDUCTORS 1 L01_03-0-10-5 HMI
7 OVERCURRENT PROTECTION
FOR PHASE 50/51 TRIP
01BAT00_EN001_XM4 LINE CONDUCTORS 1 L01_03-0-10-6 HMI
8 OVERCURRENT PROTECTION
FOR EARTH 50N/51N TRIP
01BAT00_EN001_XM4 AUX TRANSF DIFFERENTIAL 1 L01_03-0-10-7 HMI
9 PROTECTION 87T TRIP
01BAT00_EN001_XM5 AUX TRANSF OVERCURRENT 1 L01_03-0-10-8 HMI
0 PROTECTION FOR PHASE
50/51 TRIP
01BAT00_EN001_XM5 AUX TRANSF OVERCURRENT 1 L01_03-0-10-9 HMI
1 PROT WITH UNDERVOLTAGE
SEAL-IN 51V TRIP
01BAT00_EN001_XM5 CIRCUIT BREAKER FAILURE 1 L01_03-0-10-10 HMI
2 PROTECTION 50BF TRIP
01BAT00_EN001_XQ0 MAIN TRANSFORMER OIL 0 <-> 200 L01_01-0-21-0 HMI
1 TEMPERATURE
01BAT00_EN001_XQ0 AUX TRANSFORMER OIL 0 <-> 200 L01_01-0-21-1 HMI
2 TEMPERATURE
01BAT00_EN001_XQ0 AUX TRANSFORMER ONLOAD 0 <-> 20 L01_01-0-21-2 HMI
3 TAP CHANGER POSITION
01BAT00_EU001_ZM0 MTR SYSTEM ELECTRICAL 0 113[1] HMI,113[3],140[2]
3 STOP COND
01BAT00_EU001_ZM0 MAIN TRANSFORMER SYSTEM 0 112[2] HMI,113[3],130[31]
4 STARTING COND
01BAT00_EU001_ZM5 MAIN TRANSFORMER READY 113[3]
1 TO OPERATION
01BAT00_MT001_XM0 MAIN TRANSFORMER 1 L01_03-0-3-10 HMI,113[1]
1 PROTECTION FROM MATRIX
01BBA00_CE001_XQ0 UNIT ACTIVE POWER -30 <-> 120 L01_01-0-16-0 HMI,104[5],70[40],72[6]
1
01BBA00_CE001_XQ0 UNIT VOLTAGE PHASE AB 0.000000 <- L01_01-0-16-1 HMI,106[9],72[48]
2 > 20.00000
XX PXXXXA4XXXX.8/A
NAME DESCRIPTION STATE INIT AL I/O FROM TO
01BBA00_FE001_RQ0 UNIT VOLTAGE PHASE A 0 <-> 20 L01_r5_2_0EX'ModbusClientInW HMI
2
01BBA00_FE001_RQ0 UNIT VOLTGAE PHASE AB 0 <-> 20 L01_r5_2_0EX'ModbusClientInW HMI,106[15],73[32]
3
01BBA00_FE001_RQ1 UNIT CURRENT PHASE B 0 <-> 10000 L01_r5_2_0EX'ModbusClientInW HMI
1
01BBA00_FE001_RQ1 UNIT VOLTAGE PHASE B 0 <-> 20 L01_r5_2_0EX'ModbusClientInW HMI
2
01BBA00_FE001_RQ1 UNIT VOLTGAE PHASE BC 0 <-> 20 L01_r5_2_0EX'ModbusClientInW HMI
3
01BBA00_FE001_RQ2 UNIT CURRENT PHASE C 0 <-> 10000 L01_r5_2_0EX'ModbusClientInW HMI
1
01BBA00_FE001_RQ2 UNIT VOLTAGE PHASE C 0 <-> 20 L01_r5_2_0EX'ModbusClientInW HMI
2
01BBA00_FE001_RQ2 UNIT VOLTGAE PHASE CA 0 <-> 20 L01_r5_2_0EX'ModbusClientInW HMI
3
01BBA00_FE001_RQ4 UNIT APPARENT POWER -200 <-> 200 L01_r5_2_0EX'ModbusClientInW HMI
1
01BBA00_FE001_RQ4 UNIT ACTIVE POWER -200 <-> 200 L01_r5_2_0EX'ModbusClientInW HMI,73[31],104[6]
2
01BBA00_FE001_RQ4 UNIT REACTIVE POWER -120 <-> 120 L01_r5_2_0EX'ModbusClientInW HMI,105[2],72[49]
3
01BBA00_FE001_RQ4 UNIT POWER FACTOR 0 <-> 1 L01_r5_2_0EX'ModbusClientInW HMI
4
01BBA00_FE001_RQ4 UNIT FREQUENCE 0 <-> 60 L01_r5_2_0EX'ModbusClientInW HMI,121[1]
5
01BBA00_FE001_RQ5 UNIT ACTIVE POWER ENERGY 0 <-> L01_r5_2_0EX'ModbusClientInW HMI
1 IMPORT 999999
XX PXXXXA4XXXX.9/A
NAME DESCRIPTION STATE INIT AL I/O FROM TO
01CHA00_11_GAPC1 State HMI
XA01
01CHA00_11_GAPC1 Mode -1000 <-> HMI
XA02 1000
XX PXXXXA4XXXX.10/A
NAME DESCRIPTION STATE INIT AL I/O FROM TO
01CHA00_11_PDIS1X Mode -1000 <-> HMI
A02 1000
XX PXXXXA4XXXX.11/A
NAME DESCRIPTION STATE INIT AL I/O FROM TO
01CHA00_11_PHIZ2X Behavior HMI
A00
01CHA00_11_PHIZ2X State HMI
A01
01CHA00_11_PHIZ2X Mode -1000 <-> HMI
A02 1000
XX PXXXXA4XXXX.12/A
NAME DESCRIPTION STATE INIT AL I/O FROM TO
01CHA00_11_PVPH1X OFF HMI
A05
01CHA00_11_PVPH2X Behavior HMI
A00
01CHA00_11_PVPH2X State HMI
A01
01CHA00_11_PVPH2X Mode -1000 <-> HMI
A02 1000
XX PXXXXA4XXXX.13/A
NAME DESCRIPTION STATE INIT AL I/O FROM TO
01CHA00_21_PDIF2X Behavior HMI
A00
01CHA00_21_PDIF2X State HMI
A01
01CHA00_21_PDIF2X Mode -1000 <-> HMI
A02 1000
XX PXXXXA4XXXX.14/A
NAME DESCRIPTION STATE INIT AL I/O FROM TO
01CHA00_21_PDUP2X Pickup HMI
A04
01CHA00_21_PDUP2X OFF HMI
A05
01CHA00_21_PHIZ1X Behavior HMI
A00
01CHA00_21_PHIZ1X State HMI
A01
01CHA00_21_PHIZ1X Mode -1000 <-> HMI
A02 1000
XX PXXXXA4XXXX.15/A
NAME DESCRIPTION STATE INIT AL I/O FROM TO
01CHA00_21_PTOCA Pickup HMI
XA03
01CHA00_21_PTOCA Pickup HMI
XA04
01CHA00_21_PTOCA OFF HMI
XA05
01CHA00_21_PVPH1X Behavior HMI
A00
01CHA00_21_PVPH1X State HMI
A01
01CHA00_21_PVPH1X Mode -1000 <-> HMI
A02 1000
XX PXXXXA4XXXX.16/A
NAME DESCRIPTION STATE INIT AL I/O FROM TO
01CHA00_EN001_XM2 F21 BREAKER FAILURE 1 L01_03-0-4-6 HMI
5 PROTECTION TRIP
01CHA00_EN001_XM2 GENERATOR STATOR 1 L01_03-0-4-7 HMI,80[12]
6 DIFFERENTIAL PROTECTION
87G TRIP
01CHA00_EN001_XM2 GENERATOR IMPEDANCE 1 L01_03-0-4-8 HMI
7 PROTECTION 21 TRIP
01CHA00_EN001_XM2 90-%-STATOR EARTH FAULT 1 L01_03-0-4-10 HMI
8 PROTECTION 64G TRIP
01CHA00_EN001_XM3 SENSITIVE ROTOR EARTH 1 L01_03-0-4-11 HMI
0 FAULT PROTECTION 64R TRIP
01CHA00_EN001_XM3 UNDER EXCITATION (LOSS-OF- 1 L01_03-0-5-0 HMI
1 FIELD) PROTECTION 40 TRIP
01CHA00_EN001_XM3 GENERATOR UNBALANCED 1 L01_03-0-5-1 HMI
2 LOAD PROTECTION 46 TRIP
01CHA00_EN001_XM3 OVERCURRENT PROT WITH 1 L01_03-0-5-2 HMI
3 UNDERVOLTAGE SEAL-IN
50/27 TRIP
01CHA00_EN001_XM3 GENERATOR INADVERTENT 1 L01_03-0-5-3 HMI
4 ENERGIZATION 50/27 TRIP
01CHA00_EN001_XM3 GENERATOR UNDER 1 L01_03-0-5-4 HMI
5 FREQUENCY 81 TRIP
01CHA00_EN001_XM3 GENERATOR OVER 1 L01_03-0-5-5 HMI
6 FREQUENCY 81 TRIP
01CHA00_EN001_XM3 GENERATOR REVERSE 1 L01_03-0-5-6 HMI
7 POWER PROTECTION 32R TRIP
01CHA00_EN001_XM3 OVEREXCITATION 1 L01_03-0-5-7 HMI
8 (VOLT/HERTZ) PROTECTION 24
TRIP
01CHA00_EN001_XM3 INVERSE-TIME 1 L01_03-0-5-8 HMI
9 UNDERVOLTAGE PROTECTION
27 TRIP
01CHA00_EN001_XM4 STATOR THERMAL OVERLOAD 1 L01_03-0-5-9 HMI
0 PROTECTION 49G TRIP
01CHA00_EN001_XM4 ROTOR THERMAL OVERLOAD 1 L01_03-0-5-10 HMI
1 PROTECTION 49R TRIP
01CHA00_MT001_XM GENERATOR MAIN 1 L01_03-0-3-8 HMI,111[2]
01 PROTECTION FROM MATRIX
01CHA00_MT001_XM GENERATOR MAIN 1 L01_03-0-3-9 HMI,111[2]
02 PROTECTION FROM MATRIX
01CHA00_MT001_XM GENERATOR FIRE COMMAND 1 L01_03-0-3-11 HMI,80[12],111[2]
03 TO PROTECTION
01CHA00_PT001_ZM0 Generator Protection 1 111[2] HMI
3 ELECTRICAL STOP COND
01CHA00_PT001_ZM0 Generator Protection 0 111[1] HMI,130[31]
4 ELECTRICAL STARTING COND
01CJA00_CE001_ZQ0 UNIT ACTIVE POWER 0 163[2] HMI,163[3,6],165[17],104[10,11]
1 MEASUREMENT VALIDATION
01CJA00_CE001_ZQ0 UNIT VOLTAGE PHASE AB AI 0 106[1] HMI,106[14,16],168[7],189[1],169[
2 VALIDATION 29]
01CJA00_CE001_ZQ0 UNIT REACTIVE POWER 0 169[2] HMI,170[16],168[7],169[21,23,32]
3 MEASUREMENT VALIDATION
01CJA00_CE023_ZQ0 UNIT Vab or Q Measurement 0 168[1] HMI,168[10]
1 VALIDATION
01CJA00_CP001_ZH0 PRESSURES OF 129[21] HMI,134[54,56]
6 COMPENSATED COMPRESSED
AIR TANK REACHED
01CJA00_DE001_ZG0 ACTIVE POWER SETPOINT 165[17] HMI,165[23],166[18]
1 ENABLED
01CJA00_DE001_ZG3 ACTIVE POWER CTRL MODE: 0 163[20] HMI,163[21,51,52]
1 ANA/ANA
01CJA00_DE001_ZG3 ACTIVE POWER CTRL MODE: 0 163[9] HMI,188[2],166[18]
2 ANA/PULSE
01CJA00_DE001_ZG3 ACTIVE POWER CTRL MODE: 163[12] HMI,167[41,46],165[17],187[1]
3 PULSE/PULSE
01CJA00_DE001_ZG4 LOAD CTRL OBJECT: ACT. 164[16] HMI,166[30],165[17],164[50,53]
1 POWER
01CJA00_DE001_ZG4 LOAD CTRL OBJECT: OPENING 164[16] HMI,70[42],187[1],164[32]
2 DEG
01CJA00_DE001_ZH0 ACTIVER SETPOINT OVER 3 165[24] HMI
6 HIGH LIMIT
01CJA00_DE001_ZL0 ACTIVE POWER INCREASE HMI 167[26]
1 CMD
01CJA00_DE001_ZL0 ACTIVE POWER DECREASE HMI 167[27]
2 CMD
01CJA00_DE001_ZL3 ACTIVE POWER CTRL MODE: HMI 163[4]
1 ANA/ANA CMD
01CJA00_DE001_ZL3 ACTIVE POWER CTRL MODE: HMI 163[8]
2 ANA/PULSE CMD
01CJA00_DE001_ZL3 ACTIVE POWER CTRL MODE: HMI 163[6]
3 PULSE/PULSE CMD
01CJA00_DE001_ZL4 LOAD CTRL OBJECT: ACT. HMI 164[15]
1 POWER SEL CMD
01CJA00_DE001_ZL4 LOAD CTRL OBJECT: OPENING HMI 164[14]
2 DEG SEL CMD
01CJA00_DE001_ZM0 ACTIVE POWER SP FORCED 0 165[23] HMI
1
XX PXXXXA4XXXX.17/A
NAME DESCRIPTION STATE INIT AL I/O FROM TO
01CJA00_DE001_ZM1 ACT POWER INCREASE REQ 167[36] HMI
1
01CJA00_DE001_ZM1 ACT POWER INCREASE REQ 167[37] HMI
2
01CJA00_DE001_ZP0 ACTIVE POWER SP FEEDBACK 0 <-> 120 165[24] HMI,166[25,35],165[29,39],70[14]
1
01CJA00_DE001_ZQ0 ACTIVE POWER MEAS VALUE -120 <-> 120 104[7] HMI,167[28],166[25,35],165[23],1
1 04[8,10,13]
01CJA00_DE001_ZR0 ACTIVE POWER SP CMD 0 <-> 120 HMI 165[23]
1
01CJA00_DE002_ZG0 REACTIVE POWER SETPOINT 170[16] HMI,170[18],171[17]
1 ENABLED
01CJA00_DE002_ZG3 REACTIVE POWER CTRL 0 168[41] HMI,168[3,42]
1 MODE: ANA/ANA
01CJA00_DE002_ZG3 REACTIVE POWER CTRL 168[13] HMI,190[2],171[17]
2 MODE: ANA/PULSE
01CJA00_DE002_ZG3 REACTIVE POWER CTRL 168[15] HMI,170[16],189[1],191[20,23]
3 MODE: PULSE/PULSE
01CJA00_DE002_ZG4 REACTIVE CTRL OBJECT: REA 169[35] HMI,169[43],72[51]
1 PWR
01CJA00_DE002_ZG4 REACTIVE CTRL OBJECT: 169[35] HMI,169[44],72[51]
2 VOLTAGE
01CJA00_DE002_ZH0 REACTIVER SETPOINT LESS 3 170[19] HMI
4 LOW LIMIT
01CJA00_DE002_ZH0 REACTIVER SETPOINT OVER 3 170[19] HMI
6 HIGH LIMIT
01CJA00_DE002_ZL0 REACTIVE POWER INCREASE HMI 191[6]
1 CMD
01CJA00_DE002_ZL0 REACTIVE POWER DECREASE HMI 191[8]
2 CMD
01CJA00_DE002_ZL3 REACTIVE POWER CTRL HMI 168[6]
1 MODE: ANA/ANA CMD
01CJA00_DE002_ZL3 REACTIVE POWER CTRL HMI 168[11]
2 MODE: ANA/PULSE CMD
01CJA00_DE002_ZL3 REACTIVE POWER CTRL HMI 168[8]
3 MODE: PULSE/PULSE CMD
01CJA00_DE002_ZL4 REACTIVE CTRL OBJECT: REA HMI 169[33]
1 PWR SEL CMD
01CJA00_DE002_ZL4 REACTIVE CTRL OBJECT: HMI 169[30]
2 VOLTAGE SEL CMD
01CJA00_DE002_ZM0 REACTIVE POWER SP 0 170[18] HMI
1 FORCED
01CJA00_DE002_ZM1 REA POWER INCREASE REQ 191[12] HMI
1
01CJA00_DE002_ZM1 REA POWER INCREASE REQ 191[13] HMI
2
01CJA00_DE002_ZP0 REACTIVE POWER SP -120 <-> 120 170[19] HMI,170[27],171[20,26],72[22]
1 FEEDBACK
01CJA00_DE002_ZQ0 REACTIVE POWER MEAS -120 <-> 120 0 105[3] HMI,170[18],105[3,4],171[20,26],1
1 VALUE 91[7,9]
01CJA00_DE002_ZR0 REACTIVE POWER SP CMD -120 <-> 120 HMI 170[18]
1
01CJA00_DE003_ZG0 UNIT VOLTAGE SETPOINT 189[1] HMI,190[2],189[3]
1 ENABLED
01CJA00_DE003_ZH0 VOLTAGE SETPOINT OVER 3 189[4] HMI
6 HIGH LIMIT
01CJA00_DE003_ZM0 UNIT VOLTAGE SP FORCED 0 189[3] HMI
1
01CJA00_DE003_ZP0 UNIT VOLTAGE SP FEEDBACK 0 <-> 189[4] HMI,190[5,11],189[14],72[21]
1 20.00000
XX PXXXXA4XXXX.18/A
NAME DESCRIPTION STATE INIT AL I/O FROM TO
01CJA00_EA001_ZS0 01 0 173[3] HMI,154[1]
11
01CJA00_EA001_ZS0 02 173[4] HMI
21
01CJA00_EA001_ZS0 03 173[5] HMI
31
01CJA00_EA001_ZS0 04 173[6] HMI
41
01CJA00_EA002_ZG0 SQ02: GC ->NMS SEQ 61[S0,S99] HMI,58[S0],50[T4,T11,T10],175[1,
1 8,12]
01CJA00_EA002_ZM0 SQ02: GC ->NMS SEQ 2 175[14] HMI
1 OVERTIME
01CJA00_EA002_ZQ0 SQ02: GC ->NMS SEQ TIME 0.000000 <- 0 175[13] HMI,175[13]
1 COUNT > 3600.000
XX PXXXXA4XXXX.19/A
NAME DESCRIPTION STATE INIT AL I/O FROM TO
01CJA00_EA027_ZQ0 SQ27:SR->SE SEQ TIME 0.000000 <- 0 146[9] HMI,146[9]
1 COUNT > 3600.000
XX PXXXXA4XXXX.20/A
NAME DESCRIPTION STATE INIT AL I/O FROM TO
01CJA00_EA061_ZM0 SQ61: TS->CH SEQ OVERTIME 2 151[16] HMI
1
01CJA00_EA061_ZQ0 SQ61: TS->CH SEQ TIME 0.000000 <- 0 151[15] HMI,151[15]
1 COUNT > 3600.000
XX PXXXXA4XXXX.21/A
NAME DESCRIPTION STATE INIT AL I/O FROM TO
01CJA00_EN002_ZM5 L01_02 CE1000 I/O 1 182[11] HMI
2 CONTROLLER E8000-1
01CJA00_EN002_ZM5 L01_02 CE1000 I/O 1 182[12] HMI
3 CONTROLLER E8000-2
01CJA00_EN003_ZM5 L01_03 CE1000 I/O 1 182[3] HMI,183[20],182[13,14]
1 CONTROLLER
01CJA00_EN003_ZM5 L01_03 CE1000 I/O 1 182[13] HMI
2 CONTROLLER E8000-1
01CJA00_EN003_ZM5 L01_03 CE1000 I/O 1 182[14] HMI
3 CONTROLLER E8000-2
01CJA00_EP001_XM5 GCB SYNCHRONIZER READY 2 L01_01-0-4-8 HMI,186[1],66[43],128[27,28]
1 FOR OPERATION
01CJA00_EP001_ZM0 UNIT SYNCHRONIZER OK / 0 128[29] HMI,145[5],133[41,43],134[54],12
4 SELF SYNCHRONIZE MODE 1[3],130[30]
01CJA00_EP002_XM5 GCB SYN. CHECK RELAY 2 L01_01-0-4-7 HMI,186[1],66[17],128[27,28]
1 READY FOR OPERATION
01CJA00_EP012_ZM0 GCB SYNCHRONIZER / CHECK 186[1] HMI,186[16]
1 RELAY FAULT
01CJA00_EU001_YL0 ELECTRICAL 86-1 EMERGENCY 140[29] L01_02-0-14-2
1 STOP
01CJA00_EU001_YL0 MECHANICAL 86-2 138[26] L01_02-0-14-3
2 EMERGENCY STOP
01CJA00_EU001_YL0 EMERGENCY STOP LEVEL 3 98[48] L01_02-0-14-4
3
01CJA00_EU001_ZA0 ANY UNIT STOP CMD 0 141[25] HMI,131[35],98[13],94[22],186[12]
1 ,161[1],133[40],135[67,72],132[60]
,127[77],174[1],82[1],119[1],134[5
3],89[29,32],95[2,9],172[1],139[20]
01CJA00_EU001_ZA9 UNIT MECHANICAL STOP 0 138[8] HMI,131[33],138[15,26,27]
2 COMMAND
01CJA00_EU001_ZA9 UNIT ELECTRICAL STOP 0 140[10] HMI,131[33],140[13]
3 COMMAND
01CJA00_EU001_ZG0 UNIT INIT STOP STATE 0 48[S0] HMI,138[4,5],124[9],139[20],123[2
0 0]
01CJA00_EU001_ZG0 UNIT STILL STOP STATE 0 48[S1] HMI,155[5],131[36],178[2],138[4,5
1 ],83[2],153[5],124[9,11,18],160[6],
151[9],157[4],144[6],120[4],137[3],
146[3],139[20],123[20],175[2],173[
2],148[6],162[3]
01CJA00_EU001_ZG0 UNIT INIT/STILL STOP STATE 0 138[5] HMI,186[16],138[16,18],102[12],1
2 15[19,20],139[19],140[14]
01CJA00_EU001_ZG0 UNIT RUNNING STATE 50[S2,S0] HMI,50[S102]
9
01CJA00_EU001_ZG1 UNIT IN SS/TS STATE 0 124[18] HMI,133[41],135[68,73],132[61],1
0 27[78],134[54]
01CJA00_EU001_ZG1 UNIT TS STATE 0 54[S0],48[S3],51[S0],45[S0],59[S0 HMI,131[35],94[35],96[20],124[12,
1 ] 18],139[19],123[20]
01CJA00_EU001_ZG1 UNIT P<MIN or WICKET 154[4] HMI,154[7],147[4],172[3]
2 OPEN<NO LOAD or INTAKE
GATE CLOSED
01CJA00_EU001_ZG1 WICKET GATE or INTAKE 0 158[1] HMI,159[6],174[9],82[1,3,5],172[9]
3 GATE CLOSED ,158[4,8]
01CJA00_EU001_ZG1 UNIT IN SELF SYNCHRONIZE 0 186[18] HMI,64[10],94[22,23],145[1,2],51[
4 STARTING MODE S2],62[S1],89[30,32,33],52[S1],14
2[1,2],128[29],185[24],72[44]
01CJA00_EU001_ZG2 UNIT SR STATE 0 48[S11] HMI,133[1],132[60],127[80],124[1
1 3],50[S3],123[20]
01CJA00_EU001_ZG2 UNIT IN SR/SE STABLE STATE 0 133[1] HMI,133[43]
7
01CJA00_EU001_ZG3 UNIT GE STATE 0 48[S20] HMI,88[47,50],133[40],125[19],13
1 2[63],124[14],134[56],166[40],50[
S3],123[20],187[1],164[10]
01CJA00_EU001_ZG3 UNIT IN G DERECT OPERATION 0 164[10] HMI,165[17]
2
01CJA00_EU001_ZG3 UNIT IN G/GC DERECT 0 125[19] HMI,170[16],189[1]
3 OPERATION
01CJA00_EU001_ZG4 UNIT GC STATE 0 48[S22] HMI,133[2,45],125[19],124[15],11
1 4[4,6,17],134[53],115[11,13],50[S
3],123[20],116[2,4]
01CJA00_EU001_ZG5 UNIT BS STATE 0 48[S51] HMI,135[72],50[S3],123[20]
1
01CJA00_EU001_ZG6 UNIT CH STATE 0 48[S41] HMI,133[49],135[67],124[17],50[S
1 3],123[20]
01CJA00_EU001_ZG7 UNIT SE-SPIN EXCITATION 48[S13] HMI,133[1],127[77],124[16],50[S3]
1 STATE ,123[20]
01CJA00_EU001_ZJ1 UNIT TS STATE 131[39] HMI,94[33],48[T2],123[3,4,5,6,7,8,
1 20]
01CJA00_EU001_ZJ1 UNIT NORMAL STOP TO TS 0 139[23] HMI,161[1],138[24],50[T101,T102,
2 T15]
01CJA00_EU001_ZJ2 UNIT SR STATE 132[66] HMI,94[33],48[T14,T10,T2],123[3]
1
01CJA00_EU001_ZJ3 UNIT GE STATE 133[52] HMI,94[33],125[19],48[T12,T42,T5
1 3,T23,T52,T17,T10,T2],123[4],164
[10]
01CJA00_EU001_ZJ4 UNIT GC STATE 134[59] HMI,94[33],125[19],48[T12,T17,T1
1 0,T21,T2],123[5]
01CJA00_EU001_ZJ5 UNIT BS STATE 135[76] HMI,48[T50,T2],123[7]
1
XX PXXXXA4XXXX.22/A
NAME DESCRIPTION STATE INIT AL I/O FROM TO
01CJA00_EU001_ZJ6 UNIT CH STATE 135[71] HMI,48[T40,T2],123[6]
1
01CJA00_EU001_ZJ7 UNIT SE-SPIN EXCITATION 127[83] HMI,94[33],48[T12,T10,T2],123[8]
1 STATE
01CJA00_EU001_ZL0 UNIT NORMAL STOP CMD HMI 138[17]
1
01CJA00_EU001_ZL1 UNIT EMERG STOP CMD 0 HMI 140[12]
0
01CJA00_EU001_ZL1 UNIT STOP TO TS CMD HMI 139[21]
1
01CJA00_EU001_ZL2 UNIT SR CMD1 HMI 132[62]
1
01CJA00_EU001_ZL3 UNIT GE CMD1 HMI 133[42]
1
01CJA00_EU001_ZL4 UNIT GC CMD1 HMI 134[55]
1
01CJA00_EU001_ZL5 UNIT BS CMD1 HMI 135[74]
1
01CJA00_EU001_ZL6 UNIT CH CMD1 HMI 135[69]
1
01CJA00_EU001_ZL7 UNIT SE-SPIN EXCITATION HMI 127[79]
1 CMD1
01CJA00_EU001_ZM0 UNIT INIT->STILL STOP STATE 0 141[11] HMI,48[T1,T4]
0 COND
01CJA00_EU001_ZM0 UNIT NORMAL STOP REQ 0 138[24] HMI,60[S1,S4],141[25],50[T15,T3]
1 ,123[2]
01CJA00_EU001_ZM0 UNIT MECH STOP REQ 0 1 138[16] HMI,60[S1],141[25],126[26],50[T3,
2 T15],139[19],123[1,2]
01CJA00_EU001_ZM0 UNIT EMERG STOP REQ 0 1 140[14] HMI,141[25],126[26],158[2],50[T6,
3 T7,T3,T15],185[3],139[19],123[1,2
,20]
01CJA00_EU001_ZM0 UNIT ELEC STARTING 130[32] HMI,131[36],133[41],135[68,73],1
4 CONDITION 32[61],127[78],134[54],136[1]
01CJA00_EU001_ZM0 UNIT MECH STARTING 129[25] HMI,131[36],133[41],135[68,73],1
5 CONDITION 32[61],127[78],134[54],136[1]
01CJA00_EU001_ZM0 UNIT PERMANENT START 131[34] HMI,131[36],133[41,43,47,49],135
6 CONDITION [68,73],154[5],132[61,63],127[78,8
0],147[2],176[1],134[54,56],149[1],
142[3],136[1],152[1],97[44]
01CJA00_EU001_ZM1 UNIT NORMAL STOP TO SS 138[18] HMI,138[24],139[19,20]
1
01CJA00_EU001_ZM1 UNIT EMERGENCY STOP 0 1 98[29] HMI,98[48],140[2]
3 LEVEL 3
01CJA00_EU001_ZM2 SWITCHYARD CONDITIONS 0 128[15] HMI,145[5],133[41,43,49],132[61],
1 FOR GENERATING 127[78,80],134[54],121[3],156[1]
01CJA00_EU001_ZM2 SWITCHYARD CONDITIONS 0 128[16] HMI,135[68]
2 FOR LINE CHARGING
01CJA00_EU001_ZM2 SWITCHYARD CONDITIONS 0 128[17] HMI,135[73]
3 FOR BLACK START
01CJA00_EU001_ZU0 UNIT STATE VALUE WORD 123[20] HMI
1
01CJA00_EU001_ZU0 UNIT STATE COLOR 123[20] HMI
2 ANIMATION
01CJA00_EU100_PS Supply status (0:OK ; 4:No NOT AFFECTED 181[7]
Power Supply ; 5:Supply
warning for ; 128:Global err)
01CJA00_EU100_ZM0 L04_01 ST00 PS9400 POWER 181[7] HMI,181[15]
1 SUPPLY
01CJA00_EU100_ZM5 L01_01 ST00 PS9400 POWER 181[15] HMI,183[20]
1 SUPPLY
01CJA00_EU115_PS Supply status (0:OK ; 4:No L01_01-0-15-0 181[4]
Power Supply ; 5:Supply
warning for ; 128:Global err)
01CJA00_EU115_ZM0 L01_01 ST15 PS3300 POWER 1 181[4] HMI,181[16]
1 SUPPLY
01CJA00_EU115_ZM5 L01_01 ST15 PS3300 POWER 1 181[16] HMI,183[20]
1 SUPPLY
01CJA00_EU200_PS Supply status (0:OK ; 4:No NOT AFFECTED 181[5]
Power Supply ; 5:Supply
warning for ; 128:Global err)
01CJA00_EU200_ZM0 L01_02 ST00 PS9400 POWER 181[5] HMI,181[17]
1 SUPPLY
01CJA00_EU200_ZM5 L01_02 ST01 PS9400 POWER 1 181[17] HMI,183[20]
1 SUPPLY
01CJA00_EU213_PS Supply status (0:OK ; 4:No L01_02-0-13-0 181[6]
Power Supply ; 5:Supply
warning for ; 128:Global err)
01CJA00_EU213_ZM0 L01_02 ST13 PS3300 POWER 1 181[6] HMI,181[18]
1 SUPPLY
01CJA00_EU213_ZM5 L01_02 ST13 PS3300 I/O 1 181[18] HMI,183[20]
1 POWER SUPPLY
01CJA00_EU300_PS Supply status (0:OK ; 4:No NOT AFFECTED 181[8]
Power Supply ; 5:Supply
warning for ; 128:Global err)
01CJA00_EU300_ZM0 L01_03 ST00 PS9400 POWER 181[8] HMI,181[19]
1 SUPPLY
01CJA00_EU300_ZM5 L01_03 ST01 PS9400 POWER 1 181[19] HMI,183[20]
1 SUPPLY
XX PXXXXA4XXXX.23/A
NAME DESCRIPTION STATE INIT AL I/O FROM TO
01CJA00_FE001_ZM0 MFC3000 vs FE001 MOD 0 3 75[13] HMI,105[3],106[17],104[7],130[30]
2 EXCHANGE
01CJA00_FE001_ZM1 MFC3000-M vs FE001 MOD 3 75[5] HMI
1 LINK
01CJA00_FE001_ZM1 MFC3000-M vs FE001 MOD 3 75[5] HMI,75[13]
2 EXCHANGE
01CJA00_FE001_ZM2 MFC3000-S vs FE001 MOD LINK 3 75[5] HMI
1
01CJA00_FE001_ZM2 MFC3000-S vs FE001 MOD 3 75[5] HMI,75[13]
2 EXCHANGE
01CJA00_FE002_ZM0 MFC3000 vs FE002 MOD 3 76[14] HMI
2 EXCHANGE
01CJA00_FE002_ZM1 MFC3000-M vs FE002 MOD 3 76[6] HMI
1 LINK
01CJA00_FE002_ZM1 MFC3000-M vs FE002 MOD 3 76[6] HMI,76[14]
2 EXCHANGE
01CJA00_FE002_ZM2 MFC3000-S vs FE002 MOD LINK 3 76[6] HMI
1
01CJA00_FE002_ZM2 MFC3000-S vs FE002 MOD 3 76[6] HMI,76[14]
2 EXCHANGE
01CJA00_FT001_ZM0 MFC3000 vs FT001 MOD 3 74[10] HMI
2 EXCHANGE
01CJA00_FT001_ZM1 MFC3000-M vs FT001 MOD LINK 3 74[2] HMI
1
01CJA00_FT001_ZM1 MFC3000-M vs FT001 MOD 3 74[2] HMI,74[10]
2 EXCHANGE
01CJA00_FT001_ZM2 MFC3000-S vs FT001 MOD LINK 3 74[2] HMI
1
01CJA00_FT001_ZM2 MFC3000-S vs FT001 MOD 3 74[2] HMI,74[10]
2 EXCHANGE
01CJA00_GH001_XL3 LCU CONTROL LEVEL IN L01_01-0-4-1 HMI,126[7,12,22],66[50]
1 REMOTE
01CJA00_GH001_XL3 LCU CONTROL LEVEL IN L01_01-0-4-0 HMI,186[16],126[3,5,8],66[50],87[
2 LOCAL 44,62]
01CJA00_GH001_XL3 LCU OPERATION LOCKED L01_01-0-4-2 HMI,131[33],126[5,8],66[50],97[42
3 ,44]
01CJA00_GH003_XL2 SYNCHRONIZING MODE IN L01_01-0-4-4 HMI,186[16],66[51],128[27],185[7]
1 AUTO
01CJA00_GH003_XL2 SYNCHRONIZING MODE IN L01_01-0-4-5 HMI,66[51],128[4]
2 MANU
01CJA00_GH003_XL2 SYNCHRONIZING MODE IN L01_01-0-4-6 HMI,66[51],128[4]
3 TEST
01CJA00_GH003_ZG2 SYNCHRONIZER IN TEST OR 128[4] HMI,128[28]
2 MANUAL
01CJA00_GK302_ZM0 MFC3000 vs GK302 MOD 3 74[9] HMI
2 EXCHANGE
01CJA00_GK302_ZM1 MFC3000-M vs GK302 MOD 3 74[1] HMI
1 LINK
01CJA00_GK302_ZM1 MFC3000-M vs GK302 MOD 3 74[1] HMI,74[9]
2 EXCHANGE
01CJA00_GK302_ZM2 MFC3000-S vs GK302 MOD 3 74[1] HMI
1 LINK
01CJA00_GK302_ZM2 MFC3000-S vs GK302 MOD 3 74[1] HMI,74[9]
2 EXCHANGE
01CJA00_GK901_XM5 S8000-1 NETWORK SWITCH 2 L01_01-0-3-8 HMI
1 GK901
01CJA00_GK902_XM5 S8000-2 NETWORK SWITCH 2 L01_01-0-3-9 HMI
1 GK902
01CJA00_GR001_XM5 220VDC/24VDC POWER 2 L01_01-0-3-4 HMI
1 MODULE GR001
01CJA00_GR002_XM5 220VDC/24VDC POWER 2 L01_01-0-3-5 HMI
1 MODULE GR002
01CJA00_GR003_XM5 220VAC/24VDC POWER 2 L01_01-0-3-6 HMI
1 MODULE GR003
01CJA00_GR004_XM5 220VAC/24VDC POWER 2 L01_01-0-3-7 HMI
1 MODULE GR004
01CJA00_GS001_XM5 220VDC INCOMING 1 POWER 2 L01_01-0-3-0 HMI
1 SUPPLY
01CJA00_GS002_XM5 220VAC INCOMING POWER 2 L01_01-0-3-1 HMI
1 SUPPLY
01CJA00_GS003_XM5 220VDC INCOMING 2 POWER 2 L01_01-0-3-2 HMI
1 SUPPLY
01CJA00_GS011_XM5 220VDC MEASUR DEVICES 2 L01_01-0-3-3 HMI,131[33],67[39]
1 POWER SUPPLY(5W1+)
01CJA00_GS012_XM5 220VDC EMERGENCY TRIP 2 L01_01-0-3-10 HMI,131[33],67[18]
1 POWER SUPPLY(5E1+)
01CJA00_GS101_XM5 LOCAL HMI POWER 2 L01_01-0-2-0 HMI
1 SUPPLY(2I1+)
01CJA00_GS102_XM5 MFC3000 PRIMARY POWER 2 L01_01-0-2-1 HMI
1 SUPPLY(2X1+)
01CJA00_GS103_XM5 MFC3000 SECONDARY POWER 2 L01_01-0-2-2 HMI
1 SUPPLY(2X2+)
01CJA00_GS104_XM5 S8000-1 NETWORK SWITCHS 2 L01_01-0-2-3 HMI
1 POWER SUPPLY(2N1+)
01CJA00_GS105_XM5 S8000-2 NETWORK SWITCHS 2 L01_01-0-2-4 HMI
1 POWER SUPPLY(2N2+)
01CJA00_GS106_XM5 EPL NETWORK HUB POWER 2 L01_01-0-2-5 HMI
1 SUPPLY 1(2N3+)
XX PXXXXA4XXXX.24/A
NAME DESCRIPTION STATE INIT AL I/O FROM TO
01CJA00_GS107_XM5 EPL NETWORK HUB POWER 2 L01_01-0-2-6 HMI
1 SUPPLY 2(2N4+)
01CJA00_GS108_XM5 MODBUS NETWORK POWER 2 L01_01-0-2-7 HMI
1 SUPPLY(2N5+)
01CJA00_GS109_XM5 24VDC CONTROL POWER 2 L01_01-0-2-8 HMI,131[33],67[44]
1 SUPPLY(2C1+)
01CJA00_GS110_XM5 24VDC DEVICE POWER 2 L01_01-0-2-9 HMI,131[33],67[5],128[27,28]
1 SUPPLY(2W1+)
01CJA00_GS111_XM5 24VDC ALARM & SIGNAL 2 L01_01-0-2-10 HMI
1 POWER SUPPLY 1(2S1+)
01CMA00_EU001_RQ Upper Guide bearing 0 <-> 100 L01_r5_7_0EX'ModbusClientInW HMI
01 Displacement X
01CMA00_EU001_RQ Upper Guide bearing 0 <-> 100 L01_r5_7_0EX'ModbusClientInW HMI
02 Displacement Y
01CMA00_EU001_RQ Thrust Bearing Displacement X 0 <-> 100 L01_r5_7_0EX'ModbusClientInW HMI
03
01CMA00_EU001_RQ Thrust Bearing Displacement Y 0 <-> 100 L01_r5_7_0EX'ModbusClientInW HMI
04
01CMA00_EU001_RQ Turbine Guide Bearing 0 <-> 100 L01_r5_7_0EX'ModbusClientInW HMI
05 Displacement X
01CMA00_EU001_RQ Turbine Guide Bearing 0 <-> 100 L01_r5_7_0EX'ModbusClientInW HMI
06 Displacement Y
01CMA00_EU001_RQ Upper Guide bearing Vibration 0 <-> 100 L01_r5_7_0EX'ModbusClientInW HMI
07 X
01CMA00_EU001_RQ Upper Guide bearing Vibration 0 <-> 100 L01_r5_7_0EX'ModbusClientInW HMI
08 Y
01CMA00_EU001_RQ Upper Guide bearing Vibration 0 <-> 100 L01_r5_7_0EX'ModbusClientInW HMI
09 Z
01CMA00_EU001_RQ Thrust Bearing Vibration X 0 <-> 100 L01_r5_7_0EX'ModbusClientInW HMI
10
01CMA00_EU001_RQ Thrust Bearing Vibration Y 0 <-> 100 L01_r5_7_0EX'ModbusClientInW HMI
11
01CMA00_EU001_RQ Thrust Bearing Vibration Z 0 <-> 100 L01_r5_7_0EX'ModbusClientInW HMI
12
01CMA00_EU001_RQ Turbine Guide Bearing 0 <-> 100 L01_r5_7_0EX'ModbusClientInW HMI
13 Vibration X
01CMA00_EU001_RQ Turbine Guide Bearing 0 <-> 100 L01_r5_7_0EX'ModbusClientInW HMI
14 Vibration Y
01CMA00_EU001_RQ Turbine Guide Bearing 0 <-> 100 L01_r5_7_0EX'ModbusClientInW HMI
15 Vibration Z
01CMA00_EU001_RQ Axial Position 0 <-> 100 L01_r5_7_0EX'ModbusClientInW HMI
16
01CMA00_EU001_XM TURBINE GUIDE BEARING 2 L01_02-0-11-0 HMI,109[1]
01 VIBRATION ALARM 1
01CMA00_EU001_XM TURBINE GUIDE BEARING 1 L01_02-0-11-1 HMI
02 VIBRATION ALARM 2
01CMA00_EU001_XM GEN THRUST BEARING 2 L01_02-0-11-2 HMI,109[1]
03 VIBRATION ALARM 1
01CMA00_EU001_XM GEN THRUST BEARING 1 L01_02-0-11-3 HMI
04 VIBRATION ALARM 2
01CMA00_EU001_XM GEN GUIDE BEARING 2 L01_02-0-11-4 HMI,109[1]
05 VIBRATION ALARM 1
01CMA00_EU001_XM GEN GUIDE BEARING 1 L01_02-0-11-5 HMI
06 VIBRATION ALARM 2
01CMA00_EU001_XM TURBINE GUIDE BEARING 2 L01_02-0-11-6 HMI,109[1]
07 RUNOUT ALARM 1
01CMA00_EU001_XM TURBINE GUIDE BEARING 1 L01_02-0-11-7 HMI
08 RUNOUT ALARM 2
01CMA00_EU001_XM GEN THRUST BEARING 2 L01_02-0-11-8 HMI,109[1]
09 RUNOUT ALARM 1
01CMA00_EU001_XM GEN THRUST BEARING 1 L01_02-0-11-9 HMI
10 RUNOUT ALARM 2
01CMA00_EU001_XM GEN GUIDE BEARING RUNOUT 2 L01_02-0-11-10 HMI,109[1]
11 ALARM 1
01CMA00_EU001_XM GEN GUIDE BEARING RUNOUT 1 L01_02-0-11-11 HMI
12 ALARM 2
01CMA00_EU001_ZM MFC3000 vs Unit Online MOD 77[11] HMI
01 LINK
01CMA00_EU001_ZM UNIT ONLINE MONITORING 0 109[1] HMI,129[24]
05 STARTING COND
01CMA00_EU001_ZM MFC3000-M vs Unit Online MOD 77[4] HMI
11 LINK
01CMA00_EU001_ZM MFC3000-M vs Unit Online MOD 77[4] HMI
12 EXCHANGE
01CMA00_EU001_ZM MFC3000-S vs Unit Online MOD 77[4] HMI,77[11]
21 LINK
01CMA00_EU001_ZM MFC3000-S vs Unit Online MOD 77[4] HMI,77[11]
22 EXCHANGE
01CVA00_EU001_XM0 STATOR WINDING TEMP 2 L01_03-0-11-0 HMI,84[1]
1 GROUP ALARM
01CVA00_EU001_XM0 STATOR WINDING TEMP 1 L01_03-0-11-1 HMI,84[2]
2 GROUP TRIP
01CVA00_EU001_XM0 STATOR CORE TEMP GROUP 2 L01_03-0-11-2 HMI,84[1]
3 ALARM
XX PXXXXA4XXXX.25/A
NAME DESCRIPTION STATE INIT AL I/O FROM TO
01CVA00_EU001_XM0 STATOR CORE TEMP GROUP 1 L01_03-0-11-3 HMI,84[2]
4 TRIP
01CVA00_EU001_XM0 TURBINE GUIDE BEARING 2 L01_03-0-11-4 HMI,84[1]
5 TEMP GROUP ALARM
01CVA00_EU001_XM0 TURBINE GUIDE BEARING 1 L01_03-0-11-5 HMI,84[2]
6 TEMP GROUP TRIP
01CVA00_EU001_XM0 GEN THRUST BEARING TEMP 2 L01_03-0-11-6 HMI,84[1]
7 GROUP ALARM
01CVA00_EU001_XM0 GEN THRUST BEARING TEMP 1 L01_03-0-11-7 HMI,84[2]
8 GROUP TRIP
01CVA00_EU001_XM0 GEN GUIDE BEARING TEMP 2 L01_03-0-11-8 HMI,84[1]
9 GROUP ALARM
01CVA00_EU001_XM1 GEN GUIDE BEARING TEMP 1 L01_03-0-11-9 HMI,84[2]
0 GROUP TRIP
01CVA00_EU001_XM1 GENERATOR AIR COOLER 2 L01_03-0-11-10 HMI,84[1]
1 TEMP GROUP ALARM
01CVA00_EU001_XM1 GENERATOR AIR COOLER 1 L01_03-0-11-11 HMI,84[2]
2 TEMP GROUP TRIP
01CVA00_EU001_ZM0 TEMP MEASURE SYS 1 84[2] HMI,138[7]
2 MECHANICAL STOP COND
01CVA00_EU001_ZM0 TEMP MEASURE SYS 84[1] HMI,129[24]
5 MECHANICAL STARTING COND
01CVA00_EU002_XM0 GENERATOR FIRE ALARM 1 2 L01_03-0-12-0 HMI,84[1]
1
01CVA00_EU002_XM0 GENERATOR FIRE ALARM 2 2 L01_03-0-12-1 HMI,84[1]
2
01MAU24_AA001_XG GOVERNOR PUMP AP001 L01_01-0-12-5 HMI
01 UNLOAD VALVE ENERGIZED
01MAU24_AA001_XL2 GOV PUMP AP001 UNLOAD L01_01-0-12-4 HMI,67[8],99[19]
1 VALVE
01MAU24_AA002_XG GOVERNOR PUMP AP001 L01_01-0-12-11 HMI
01 UNLOAD VALVE ENERGIZED
01MAU24_AA002_XL2 GOV PUMP AP002 UNLOAD L01_01-0-12-10 HMI,67[49],99[19]
1 VALVE
01MAU24_AA002_YL0 GOVERNOR SOLENOID AA002 100[26] L01_02-0-18-2
1 VALVE
01MAU24_AA002_ZG GOVERNOR SOLENOID AA002 100[23] HMI,70[42]
01 VALVE OPEN Memory
01MAU24_AA004_YL0 EMERGENCY SLIDE 95[52] L01_02-0-18-7
1 DISTRIBUTION VALVE (MSV)
01MAU24_AA005_XG GOV OIL SUMP TANK COOLING L01_01-0-14-9 HMI,103[28],63[36]
01 WATER VALVE OPEN
01MAU24_AA005_XG GOV OIL SUMP TANK COOLING L01_01-0-14-10 HMI,103[28],63[36]
02 WATER VALVE CLOSED
01MAU24_AA005_ZU0 SUMP TANK COOLING WATER 103[28] HMI
1 VALVE ANIMATION WORD
01MAU24_AP001_XG GOVERNOR PUMP AP001 L01_01-0-12-3 HMI,64[6],103[1,5],141[11],102[9],
01 RUNNING 63[17]
01MAU24_AP001_XL2 GOVERNOR PUMP AP001 IN L01_01-0-12-2 HMI,102[9],67[19],99[19]
1 AUTO MODE
01MAU24_AP001_XL4 GOV OIL PUMP 1 SELECT AS L01_01-0-13-0 HMI
1 MAIN
01MAU24_AP001_XM GOVERNOR PUMP AP001 2 L01_01-0-12-0 HMI,103[2],67[6],99[19]
51 MOTOR
01MAU24_AP001_XM GOVERNOR PUMP AP001 2 L01_01-0-12-1 HMI,103[2],67[45],99[19]
52 POWER
01MAU24_AP001_ZU0 GOVERNOR PUMP AP001 103[5] HMI
1 ANIMATION WORD
01MAU24_AP002_XG GOVERNOR PUMP AP002 L01_01-0-12-9 HMI,103[24,27],141[11],102[10]
01 RUNNING
01MAU24_AP002_XL2 GOVERNOR PUMP AP002 IN L01_01-0-12-8 HMI,102[10],67[47],99[19]
1 AUTO MODE
01MAU24_AP002_XL4 GOV OIL PUMP 2 SELECT AS L01_01-0-13-1 HMI
1 MAIN
01MAU24_AP002_XM GOVERNOR PUMP AP002 2 L01_01-0-12-6 HMI,103[25],67[46],99[19]
51 MOTOR
01MAU24_AP002_XM GOVERNOR PUMP AP002 2 L01_01-0-12-7 HMI,103[25],67[20],99[19]
52 POWER
01MAU24_AP002_ZU0 GOVERNOR PUMP AP002 103[27] HMI
1 ANIMATION WORD
01MAU24_AP003_XG LEAKAGE OIL PUMP AP003 L01_02-0-3-2 HMI,103[3,6],141[11]
01 RUNNING
01MAU24_AP003_XL2 LEAKAGE OIL PUMP AP003 IN L01_02-0-3-1 HMI,67[48],99[19]
1 AUTO MODE
01MAU24_AP003_XM LEAKAGE OIL PUMP AP003 2 L01_02-0-3-0 HMI,103[4],67[7],99[19]
51 FAULT
01MAU24_AP003_ZU0 LEAKAGE OIL PUMP AP003 103[6] HMI
1 ANIMATION WORD
01MAU24_AP012_XL2 GOV OIL PUMP 1&2 L01_01-0-13-2 HMI
1 MAIN/STANDBY AUTO SELECT
01MAU24_CL001_XH0 GOV OIL SUMP TANK OIL 2 L01_01-0-14-4 HMI,100[20],64[30]
3 LEVEL TOO LOW
01MAU24_CL001_XH0 GOV OIL SUMP TANK OIL 3 L01_01-0-14-5 HMI,99[19]
4 LEVEL LOW
01MAU24_CL001_XH0 GOV OIL SUMP TANK OIL 3 L01_01-0-14-6 HMI
6 LEVEL HIGH
01MAU24_CL002_XH0 GOV ACCUMULATOR OIL 1 L01_01-0-13-4 HMI,100[20],64[32]
3 LEVEL TOO LOW
XX PXXXXA4XXXX.26/A
NAME DESCRIPTION STATE INIT AL I/O FROM TO
01MAU24_CL002_XH0 GOV ACCUMULATOR OIL 2 L01_01-0-13-5 HMI,99[19]
4 LEVEL LOW
01MAU24_CL002_XH0 GOV ACCUMULATOR OIL 2 L01_01-0-13-8 HMI
7 LEVEL HIGH
01MAU24_CL002_XH5 GOV ACCUMULATOR OIL L01_01-0-13-6 HMI,64[15],102[21],176[1],149[1],
1 LEVEL BUILD UP 142[3],136[5]
01MAU24_CL002_XH5 GOV ACCUMULATOR OIL L01_01-0-13-7 HMI
2 LEVEL NORMAL
01MAU24_CL002_XQ0 GOVERNOR ACCUMULATOR 0.000000 <- L01_01-0-18-1 HMI
1 OIL LEVEL > 1.900000
XX PXXXXA4XXXX.27/A
NAME DESCRIPTION STATE INIT AL I/O FROM TO
01MEA41_CP101_XQ0 SPIRAL CASE INLET 0 <-> 10 L01_01-0-20-0 HMI
1 PRESSURE
01MEA41_CP108_XQ0 TURBINE WATER FLOW 0 <-> 1000 L01_01-0-20-3 HMI
1
01MEA41_CP109_XQ0 DIFFERENTIAL PRESURE 0.000000 <- L01_01-0-19-3 HMI,98[27]
1 WATER HEAD CP109T > 70
XX PXXXXA4XXXX.28/A
NAME DESCRIPTION STATE INIT AL I/O FROM TO
01MEU11_EN001_XG0 R80N MAIN T-SLG OPERATION L01_01-0-9-6 HMI,68[36],93[15]
1
01MEU11_EN001_XM R129N MAIN T-SLG UPC MINOR 2 L01_01-0-10-1 HMI,93[30]
01 FAULT
01MEU11_EN001_XM R29N MAIN T-SLG UPC MAJOR 1 L01_01-0-10-0 HMI,68[24],93[30]
51 FAULT
01MEU11_EN002_XG0 R80S STANDBY T-SLG L01_01-0-9-7 HMI,68[11],93[15]
1 OPERATION
01MEU11_EN002_XM R129S STANDBY T-SLG UPC 2 L01_01-0-10-3 HMI,93[30]
01 MINOR FAULT
01MEU11_EN002_XM R29S STANDBY T-SLG UPC 1 L01_01-0-10-2 HMI,68[38],93[30]
51 MAJOR FAULT
01MEU11_EN012_ZG0 MAIN or STANDBY T-SLG IN 93[15] HMI,93[30]
1 OPERATION
01MEU11_EU001_RG SPC not operational(DF_MJPO) 2 L01_r5_8_0EX'ModbusClientInB HMI
03
01MEU11_EU001_RG R11 Operation in limitation L01_r5_8_0EX'ModbusClientInB HMI
33
01MEU11_EU001_RG R104 Unit above speed-no-load L01_r5_8_0EX'ModbusClientInB HMI
35
01MEU11_EU001_RG R307 analog setpoint L01_r5_8_0EX'ModbusClientInB HMI
36
01MEU11_EU001_RG R270 Actuators in operation L01_r5_8_0EX'ModbusClientInB HMI
37
01MEU11_EU001_RG R305 Power feedback L01_r5_8_0EX'ModbusClientInB HMI
40
01MEU11_EU001_RG R328 Oper. in isolated network L01_r5_8_0EX'ModbusClientInB HMI
41
01MEU11_EU001_RG R313 Level feedback L01_r5_8_0EX'ModbusClientInB HMI
42
01MEU11_EU001_RG R80 Active governor L01_r5_8_0EX'ModbusClientInB HMI
43
01MEU11_EU001_RG R81 TEST mode L01_r5_8_0EX'ModbusClientInB HMI
44
01MEU11_EU001_RG Normal governor L01_r5_8_0EX'ModbusClientInB HMI
45
01MEU11_EU001_RG Standby governor L01_r5_8_0EX'ModbusClientInB HMI
46
01MEU11_EU001_RL2 R300-A LOCAL AUTO L01_r5_8_0EX'ModbusClientInB HMI
1
01MEU11_EU001_RL2 R300-M LOCAL MANU L01_r5_8_0EX'ModbusClientInB HMI
2
01MEU11_EU001_RM Major fault(R29) 2 L01_r5_8_0EX'ModbusClientInB HMI
01
01MEU11_EU001_RM Loss of unit freq signal 2 L01_r5_8_0EX'ModbusClientInB HMI
02
01MEU11_EU001_RM Comm. fault with red UPC 2 L01_r5_8_0EX'ModbusClientInB HMI
04
01MEU11_EU001_RM Minor fault(R29) 2 L01_r5_8_0EX'ModbusClientInB HMI
17
01MEU11_EU001_RM SPC minor fault 2 L01_r5_8_0EX'ModbusClientInB HMI
18
01MEU11_EU001_RM Network frequency L01_r5_8_0EX'ModbusClientInB HMI
19
01MEU11_EU001_RM Unit frequency lost 2 L01_r5_8_0EX'ModbusClientInB HMI
20
01MEU11_EU001_RM Power W L01_r5_8_0EX'ModbusClientInB HMI
21
01MEU11_EU001_RM Load set point OE circuit fault 2 L01_r5_8_0EX'ModbusClientInB HMI,163[3,21]
22
01MEU11_EU001_RM Discordance between freq L01_r5_8_0EX'ModbusClientInB HMI
27 measure
01MEU11_EU001_RM Comm. fault with red UPC L01_r5_8_0EX'ModbusClientInB HMI
28
01MEU11_EU001_RM SPC01 fault 2 L01_r5_8_0EX'ModbusClientInB HMI
49
01MEU11_EU001_RQ FG Unit freq 0.000000 <- L01_r5_8_1EX'ModbusClientInW HMI
01 > 300.0000
XX PXXXXA4XXXX.29/A
NAME DESCRIPTION STATE INIT AL I/O FROM TO
01MEU11_EU001_RQ CH Head 0.000000 <- L01_r5_8_1EX'ModbusClientInW HMI
14 > 80.00000
XX PXXXXA4XXXX.30/A
NAME DESCRIPTION STATE INIT AL I/O FROM TO
01MEU11_FS001_XH0 RV01 <5% NORMAL MECHANIC L01_01-0-10-10 HMI,50[T11,T10],70[42]
1 BRAKE VALID
01MEU11_FS001_XH0 RV02 <20% ES MECHANIC L01_01-0-10-11 HMI,82[1],158[4],70[42]
2 BRAKE VALID
01MEU11_FS001_XH0 RV03 <77% LOW FREQUENCY L01_01-0-11-0 HMI,70[42]
3 PROTECTION
01MEU11_FS001_XH0 RV04 <87% LOW FREQUENCY L01_01-0-11-1 HMI,145[3],143[9],70[54]
4 PROTECTION
01MEU11_FS001_XH0 RV05 >95% L01_01-0-11-2 HMI,145[5],177[7,13],121[3,5],70[
5 SYNCHRONISATION LAUNCH 42],150[7,13],72[51]
01MEU11_FS001_XH0 RV08 107% PROTECTION 2 L01_01-0-11-3 HMI,93[30]
8 INTERLOCK LEVEL 1
01MEU11_FS001_XH0 RV09 115% PROTECTION 2 L01_01-0-11-4 HMI,98[3],95[4]
9 INTERLOCK LEVEL 2
01MEU11_FS001_XH1 RV10 150% PROTECTION 1 L01_01-0-11-5 HMI,98[29,55],95[37,49]
0 INTERLOCK LEVEL 3
01MEU11_FS001_XH1 RV14 SPEED=0 L01_01-0-11-6 HMI,159[6],161[3],138[26],141[11]
4 ,143[9],82[3,5],177[7],158[8],70[42
],150[7]
01MEU11_FS001_XM0 RD129 TADT-MAIN MINOR 2 L01_01-0-10-7 HMI,93[30]
1
01MEU11_FS001_XM5 RD29 TADT MAJOR 1 L01_01-0-10-6 HMI,68[37],93[16],50[T11,T10]
1
01MEU11_FS001_ZH0 UNIT 115% PROTECTION WITH 1 98[3] HMI,98[29,55]
9 30Sec DELAY
01MEU11_FS001_ZH1 UNIT 115% OVERSPEED WITH 1 95[5] HMI,95[37,49]
9 LOAS 1Sec DELAY
01MEU11_FS001_ZM0 GOV T-ADT SPPED 2 94[36] HMI,95[37,49]
2 MEASUREMENT FAULT when
SPEEDUP
01MEU11_FS001_ZM5 GOVERNOR T-ADT 0 93[16] HMI,94[32],145[3,5],93[30],143[9],
1 MEASUREMENT 82[1],177[7,13],121[3],158[4],150[
7,13]
01MEU11_FS002_XM0 RD129 TADT-SECONDARY 2 L01_01-0-10-9 HMI
1 MINOR
01MEU11_GW001_XM GOV CONTROL POWER 24VDC 2 L01_01-0-9-3 HMI,93[30],69[12]
51 CIRCUIT 1
01MEU11_GW002_XM GOV CONTROL POWER 24VDC 2 L01_01-0-9-4 HMI,68[33],93[30]
51 CIRCUIT 2
01MKA54_AA001_XG GENERATOR EMERGENCY L01_02-0-8-7 HMI,141[11],81[16],63[4]
01 FIRE FIGHTING VALVE 1
01MKA54_AA001_XL2 GENERATOR EMERGENCY L01_02-0-8-6 HMI,79[9],81[6],69[28]
1 FIRE FIGHTING VALVE 1
01MKA54_AA001_XM GENERATOR EMERGENCY 2 L01_02-0-8-8 HMI,79[9],81[5]
01 FIRE FIGHTING VALVE 1 FAULT
01MKA54_AA001_YL0 GENERATOR EMERGENCY 81[16] 63[4],L01_02-0-19-8
1 FIRE FIGHTING VALVE 1
01MKA54_AA001_YL0 GENERATOR EMERGENCY 81[16] 63[4],L01_02-0-19-9
2 FIRE FIGHTING VALVE 1
01MKA54_AA001_ZM GEN EMERG FIRE FIGHTING 1 1 81[16] HMI
10
01MKA54_AA001_ZM GEN EMERG FIRE FIGHTING 1 1 81[16] HMI
11 OPENG TLTE
01MKA54_AA001_ZM GEN EMERG FIRE FIGHTING 1 1 81[16] HMI
12 CLOSG TLTE
01MKA54_AA001_ZU0 GEN EMERG FIRE FIGHTING 1 81[16] HMI
1 ANIMATION WORD
01MKA54_AA002_XG GENERATOR EMERGENCY L01_02-0-8-10 HMI,141[11],81[19],63[19]
01 FIRE FIGHTING VALVE 2
01MKA54_AA002_XL2 GENERATOR EMERGENCY L01_02-0-8-9 HMI,79[9],81[8],69[25]
1 FIRE FIGHTING VALVE 2
01MKA54_AA002_XM GENERATOR EMERGENCY 2 L01_02-0-8-11 HMI,79[9],81[7]
01 FIRE FIGHTING VALVE 2 FAULT
01MKA54_AA002_YL0 GENERATOR EMERGENCY 81[19] 63[19],L01_02-0-19-10
1 FIRE FIGHTING VALVE 2
01MKA54_AA002_YL0 GENERATOR EMERGENCY 81[19] 63[19],L01_02-0-19-11
2 FIRE FIGHTING VALVE 2
01MKA54_AA002_ZM GEN EMERG FIRE FIGHTING 2 1 81[19] HMI
10
01MKA54_AA002_ZM GEN EMERG FIRE FIGHTING 2 1 81[19] HMI
11 OPENG TLTE
01MKA54_AA002_ZM GEN EMERG FIRE FIGHTING 2 1 81[19] HMI
12 CLOSG TLTE
01MKA54_AA002_ZU0 GEN EMERG FIRE FIGHTING 2 81[19] HMI
1 ANIMATION WORD
01MKA54_AU001_YL0 MECHANICAL BRAKING 80[20] 63[2],L01_02-0-19-0
1 LAUNCH ORDER
01MKA54_AU001_ZM Mechanical Brake 1 80[11] HMI
10
01MKA54_AU001_ZM Mechanical Brake OPENG TLTE 1 80[11] HMI
11
01MKA54_AU001_ZM Mechanical Brake CLOSG TLTE 1 80[11] HMI
12
01MKA54_AU001_ZU0 MECHANICAL BRAKING 80[11] HMI
1 ANIMATION WORD
01MKA54_CG565_XG MECHANICAL BRAKING LIMIT L01_02-0-8-0 HMI,79[3,4],80[11],63[2,16],70[16]
01 SWITCHES SQ01-SQ18
XX PXXXXA4XXXX.31/A
NAME DESCRIPTION STATE INIT AL I/O FROM TO
01MKA54_CG565_ZG MECHANICAL BRAKING LIMIT 0 79[3] HMI,161[3],141[11],176[5],149[5],
01 SWITCHES SQ01-SQ18 142[7]
01MKA54_CG565_ZG MECHANICAL BRAKING LIMIT 0 79[4] HMI
02 SWITCHES SQ01-SQ18
APPLIED
01MKA54_CL301_XQ0 GEN THRUST BEARING OIL 0 <-> 400 L01_01-0-22-0 HMI
1 LEVEL
01MKA54_CL302_XH0 THRUST BEARING OIL LEVEL 1 L01_02-0-7-0 HMI,79[1]
3 VERY LOW
01MKA54_CL302_ZH1 THRUST BEARING OIL LEVEL 1 79[1] HMI,79[10]
3 VERY LOW 2s delay
01MKA54_CL303_XH0 THRUST BEARING OIL LEVEL 2 L01_02-0-7-1 HMI,79[9]
4 LOW
01MKA54_CL304_XH0 THRUST BEARING OIL LEVEL 2 L01_02-0-7-2 HMI
6 HIGH
01MKA54_CL305_XH0 THRUST BEARING OIL LEVEL 2 L01_02-0-7-3 HMI,79[9]
7 VERY HIGH
01MKA54_CL311_XQ0 GEN GUIDE BEARING OIL 0 <-> 400 L01_01-0-22-1 HMI
1 LEVEL
01MKA54_CL312_XH0 UPPER GUIDE BRG OIL LEVEL 1 L01_02-0-7-5 HMI,79[2]
3 VERY LOW
01MKA54_CL312_ZH1 UPPER GUIDE BRG OIL LEVEL 1 79[2] HMI,79[10]
3 VERY LOW 2s delay
01MKA54_CL313_XH0 UPPER GUIDE BRG OIL LEVEL 2 L01_02-0-7-6 HMI,79[9]
4 LOW
01MKA54_CL314_XM UPPER GUIDE BRG OIL LEVEL 2 L01_02-0-7-7 HMI
06 HIGH
01MKA54_CL314_XM UPPER GUIDE BRG OIL LEVEL 2 L01_02-0-7-8 HMI,79[9]
07 VERY HIGH
01MKA54_CP901_XM MECHANICAL BRAKING INLET 2 L01_02-0-8-1 HMI,79[9],69[29]
01 SOURCE PRESSURE
01MKA54_CP905_XM MECHANICAL BRAKING 2 L01_02-0-8-2 HMI
01 PRESSURE
01MKA54_EG901_YL0 UNIT IS IN OPERATION FOR 124[10] L01_02-0-15-0
1 DOOM LIGHT
01MKA54_EG901_YL0 UNIT NOT IN OPERATION FOR 124[9] 124[10],L01_02-0-15-1
2 DOOM LIGHT
01MKA54_EU001_ZM Generator Auxilaries 0 1 79[10] HMI,138[7]
02 MECHANICAL STOP COND
01MKA54_EU001_ZM Generator Auxilaries STARTING 0 79[9] HMI,129[24]
05 COND
01MKC65_ALM_WD01 AVRCONV_ALM_WD1 0.000000 <- L01_r5_4_0EX'ModbusClientInW 90[2]
> 65535.00
XX PXXXXA4XXXX.32/A
NAME DESCRIPTION STATE INIT AL I/O FROM TO
01MKC65_ALM_WD17 MKY10DU030_ALM_WD7 0.000000 <- L01_r5_5_0EX'ModbusClientInW 91[4]
> 65535.00
XX PXXXXA4XXXX.33/A
NAME DESCRIPTION STATE INIT AL I/O FROM TO
01MKC65_DE001_XM 2nd STAGE EXCITATION 1 L01_01-0-7-3 HMI,86[42]
04 FAULT
01MKC65_DE001_XM EXCITATION FAILURE TRIP 1 L01_01-0-7-4 HMI,86[42]
05
01MKC65_DE001_XM EXCITATION U/F LIMITATION 2 L01_01-0-8-6 HMI,86[40]
06
01MKC65_DE001_XM EXCITATION FIELD FLASH 2 L01_01-0-8-7 HMI,86[42]
07 FAILURE
01MKC65_DE001_XM IF<108A FOR GCB SELF L01_01-0-8-8 HMI
08 SYNCHRONIZE CONTROL
01MKC65_DE001_XM IF>108A FOR GCB SELF L01_01-0-8-9 HMI,186[12],89[32],72[53]
09 SYNCHRONIZE CONTROL
01MKC65_DE001_XM EXCITATION READY FOR L01_01-0-7-7 HMI,86[40],69[30]
51 OPERATION
01MKC65_DE010_XD4 SYNCHRO VOLTAGE FUSES 90[71] HMI
1
01MKC65_DE010_XD4 IEX164 SUPPLY FLT 90[72] HMI
2
01MKC65_DE010_XG CH 1 DC FEEDER FLT 90[14] HMI
42
01MKC65_DE010_XG CH 2 DC FEEDER FLT 90[14] HMI
43
01MKC65_DE010_XG PROTECTION RELAY 90[37] HMI
45 WATCHDOG
01MKC65_DE010_XG MX3 PROTECTION WATCHDOG 91[15] HMI
47 (TRIP)
01MKC65_DE050_XD4 AUTO (UEX) SP MAX 90[13] HMI
0
01MKC65_DE050_XD4 AUTO (UEX) SP MIN 90[13] HMI
1
01MKC65_DE050_XD8 AUTO (UEX) SP RAMP SLD 90[35] HMI
1
01MKC65_DE090_XB1 FLASHING INHIBITION 90[37] HMI
1
01MKC65_DE090_XD4 FLASHING TOO LONG 90[71] HMI
7
01MKC65_DE110_XD4 TAN PHI REGUL SP MAX 90[13] HMI
0
01MKC65_DE110_XD4 TAN PHI REGUL SP MIN 90[13] HMI
1
01MKC65_DE110_XD4 Q REGUL SP MAX 90[13] HMI
2
01MKC65_DE110_XD4 Q REGUL SP MIN 90[13] HMI
3
01MKC65_DE160_XD4 UST SET POINT MAX 90[36] HMI
0
01MKC65_DE160_XD4 UST SET POINT MIN 90[36] HMI
1
01MKC65_DT010_XD4 ROTOR OVTEMP 1ST STAGE 90[14] HMI
6
01MKC65_DU020_XD HOMOLOG REG APPLICATION 90[37] HMI
41 FAULT
01MKC65_DU020_XD REGULATOR CHANGE-OVER 90[37] HMI
42 BY UST
01MKC65_DU020_XD CURRENT REG APPLICATION 90[37] HMI
43 FAULT
01MKC65_DU020_XD CURRENT REG 1 MODULE 90[37] HMI
44 FAULT
01MKC65_DU020_XD HOMOLOG REG 1 MODULE 90[37] HMI
45 FAULT
01MKC65_DU020_XD DELTA UC FLT ON CHANGE 91[15] HMI
50 OVER RQST
01MKC65_DU020_XD IO FORCED 91[15] HMI
52
01MKC65_DU020_XD CURRENT REG REDUNDANCY 91[38] HMI
54 MEDIUM FAULT
01MKC65_DU020_XD CURRENT REG E8000 FAULT 91[38] HMI
55
01MKC65_DU020_XD REG CHANGEOVER ON PULSE 91[38] HMI
56 FLT
01MKC65_DU020_XD CHANGE OVER ON TPC DMD 91[38] HMI
61
01MKC65_DU020_XD DISTRIBUTED IO COMM FLT 91[15] HMI
82
01MKC65_DU020_XU CURRENT REGULATOR FAULT 90[36] HMI
46
01MKC65_DU030_XD CHANNEL 1 ACTIVE 90[70] HMI
01
01MKC65_DU030_XD CHANNEL 2 ACTIVE 90[70] HMI
02
01MKC65_DU030_XD AVR BATTERY LOW 91[15] HMI
03
01MKC65_DU040_XD GRID MEASUREMENT NOT 90[72] HMI
40 VALID
01MKC65_DU060_XD FIELD BREAKER POSN FLT 90[14] HMI
46
01MKC65_DU060_XD EXTERNAL SETPOINT FAULT 0 91[73] HMI,168[5]
48
XX PXXXXA4XXXX.34/A
NAME DESCRIPTION STATE INIT AL I/O FROM TO
01MKC65_DU060_XF4 FIELD BREAKER CLOSING 90[71] HMI
6 SPEED FLT
01MKC65_DU070_XD PULSE FLT DETECTION 91[15] HMI
81 INHIBITION
01MKC65_DU070_XD TPC1 INHIBITION 91[38] HMI
82
01MKC65_DU070_XD TPC2 INHIBITION 91[38] HMI
83
01MKC65_DU070_XD TPC3 INHIBITION 91[38] HMI
84
01MKC65_DU070_XD TPC4 INHIBITION 91[38] HMI
85
01MKC65_DU070_XD TPC5 INHIBITION 91[73] HMI
86
01MKC65_DU070_XD TPC6 INHIBITION 91[73] HMI
87
01MKC65_DU070_XD TPC7 INHIBITION 91[73] HMI
88
01MKC65_DU070_XD TPC8 INHIBITION 91[73] HMI
89
01MKC65_EA010_XD4 1ST STAGE EXC OVER- 90[71] HMI
6 CURRENT
01MKC65_EA102_XD8 AUTO (UEX) CHAN SLD 90[70] HMI
1
01MKC65_EA102_XD8 MANU (IEX) CHAN SLD 90[70] HMI
2
01MKC65_EA105_XD8 Q REGUL SLD 90[35] HMI
1
01MKC65_EA106_XD8 TAN PHI REGUL SLD 90[35] HMI
1
01MKC65_EA107_XB0 FIELD BREAKER CLD 90[35] HMI
1
01MKC65_EA107_XB0 FIELD BREAKER OPD 90[35] HMI
2
01MKC65_EA108_XD8 PSS SELECTED 90[35] HMI
1
01MKC65_EA108_XD8 PSS INHIBITION 90[35] HMI
2
01MKC65_EA109_XD8 VOLTAGE CTRL SLD 90[35] HMI
1
01MKC65_EA110_XD8 LOCAL MODE SLD 90[35] HMI
1
01MKC65_EA110_XD8 REMOTE MODE SLD 90[35] HMI
2
01MKC65_EA116_XD8 GENERATOR PE&QE MEAS 90[70] HMI
1 SLD
01MKC65_EA116_XD8 GRID PE&QE MEAS SLD 90[70] HMI
2
01MKC65_EA122_XD8 ELECTRICAL BRAKING 90[12] HMI
1 SELECTED
01MKC65_EA123_XD8 GENERATOR MODE SELECTED 90[12] HMI
2
01MKC65_EA126_XD8 VOLTAGE MATCHING SLTD 90[35] HMI
1
01MKC65_EG010_XD LOCAL REMOTE 90[37] HMI
46 DISCREPANCY
01MKC65_EG010_XG MX3 UPS SUPPLY FAULT 90[72] HMI
46
01MKC65_EG010_XG EXCITATION 1ST STAGE 90[71] HMI
461 FAULT
01MKC65_EG012_XD ROTATING DIODE FAULT 91[73] HMI
46
01MKC65_EG013_XD ROTOR INSULATION FIELD 90[71] HMI
46 EARTH FLT
01MKC65_EG013_XG ROTOR EARTH PROTECTION 90[37] HMI
41 FUSE FLT
01MKC65_EG015_XG U/F PROTECTION ALARM (1ST 90[37] HMI
46 STAGE)
01MKC65_EG017_XD BACK TO BACK MIN CURRENT 91[15] HMI
47 PROTECT
01MKC65_EG018_XD BACK TO BACK MAX 91[15] HMI
47 CURRENT PROTECT
01MKC65_EG101_XD ALARM 90[14] HMI
46
01MKC65_EG802_XD TRIP 90[70] HMI
47
01MKC65_EG803_XD OVEXC LIMITATION ACTIVE 90[13] HMI
46
01MKC65_EG804_XD UNDEXC LIMITATION ACTIVE 90[36] HMI
46
01MKC65_EG805_XU AVR CHANGE OVER UPON 90[72] HMI
46 FAILURE
01MKC65_EG809_XD UST / FREQ RATIO MAX 90[13] HMI
46
01MKC65_EG810_XD UST / FREQ RATIO MIN 90[13] HMI
46
01MKC65_EG811_XD I STATOR LIMITATION ACTIVE 90[13] HMI
46
XX PXXXXA4XXXX.35/A
NAME DESCRIPTION STATE INIT AL I/O FROM TO
01MKC65_EG812_XD MANU USTATOR LIM ACTIVE 90[37] HMI
46
01MKC65_EG813_XB UNIT FAULT 91[15] HMI
11
01MKC65_EG814_XD MANU UEXCL LIM ACTIVE 91[73] HMI
46
01MKC65_EM001_YL0 EXC EXTERNAL SETPOINT 168[42] 72[51],L01_02-0-16-0
1 VALIDATION
01MKC65_EM001_YL1 EXCITATION INCREASE 191[22] 72[51],L01_02-0-16-1
1 ORDER
01MKC65_EM001_YL1 EXCITATION DECREASE 191[25] 72[51],L01_02-0-16-2
2 ORDER
01MKC65_EM001_YL3 EXCITATION MANUAL 87[46] 72[51],L01_02-0-16-4
1 CHANNEL SELECT
01MKC65_EM001_YL3 EXCIT AUTOMATIC CHANNEL 87[65] 72[51],L01_02-0-16-5
2 SELECT
01MKC65_EM001_YL4 REACT POWER REGULATION 169[43] L01_02-0-16-6
1 ON SELECTION
01MKC65_EM001_YL4 REACT POWER REGULATION 169[44] L01_02-0-16-7
2 OFF SELECTION
01MKC65_EM001_YL5 LINE CHARGE ORDER TO 87[28] 72[24],L01_02-0-16-3
1 EXCITATION
01MKC65_EM001_YL6 POWER SYSTEM STABILIZER 88[52] L01_02-0-16-10
1 ON ORDER
01MKC65_EM001_YL6 POWER SYSTEM STABILIZER 88[54] L01_02-0-16-11
2 OFF ORDER
01MKC65_EM001_YL7 UNIT GCB EXACT 89[31] L01_02-0-15-10
1 SYNCHRONIZE TO EXC
01MKC65_EM001_YL7 UNIT GCB SELF SYNCHRONIZE 89[43] L01_02-0-15-11
2 TO EXC
01MKC65_EU001_P01 AVR_P MODBUS REGISTER L01_r5_4_1EX'ModbusClientInW 92[5]
XX PXXXXA4XXXX.36/A
NAME DESCRIPTION STATE INIT AL I/O FROM TO
XX PXXXXA4XXXX.37/A
NAME DESCRIPTION STATE INIT AL I/O FROM TO
01MKC65_EU001_S07 AVR_S MODBUS REGISTER L01_r5_5_1EX'ModbusClientInW 92[74]
XX PXXXXA4XXXX.38/A
NAME DESCRIPTION STATE INIT AL I/O FROM TO
01MKC65_EZ010_XD4 1ST STAGE IEX MAX 90[13] HMI
6
01MKC65_EZ010_XD4 2ND STAGE IEX MAX 90[13] HMI
7
01MKC65_EZ020_XD4 U/F PROTECTION TRIP (2ND 90[37] HMI
0 STAGE)
01MKC65_EZ020_XD4 ROTOR INSULATION FLT 2ND 90[71] HMI
2 STAGE
01MKC65_EZ020_XD4 ROTOR OVER-VOLTAGE 90[36] HMI
3 CROWBAR
01MKC65_EZ020_XD4 ROTOR OVTEMP 2ND STAGE 90[14] HMI
4
01MKC65_EZ020_XD4 EXCIT-T OVTEMP TRIP 91[38] HMI
5
01MKC65_EZ020_XD4 2ND STAGE BUCHHOLZ 90[37] HMI
6
01MKC65_EZ020_XD4 2ND STAGE EXC OVER- 90[71] HMI
7 CURRENT
01MKC65_EZ020_XD5 TRIP ON TPC DMD 91[38] HMI
0
01MKC65_EZ020_XG4 BRIDGE PWR SPLY FAULT 90[14] HMI
7
01MKC65_FE001_YQ0 UNIT REACTIVE POWER -100 <-> 100 170[27] L01_01-0-26-0
1 SETPOINT
01MKC65_FE001_YQ0 UNIT VOLTAGE SETPOINT 12.42 <-> 189[14] L01_01-0-26-1
2 15.18
XX PXXXXA4XXXX.39/A
NAME DESCRIPTION STATE INIT AL I/O FROM TO
01MKC65_GX000_XG CH 1 AC FEEDER FLT 90[14] HMI
40
01MKC65_GX000_XG CH 2 AC FEEDER FLT 90[14] HMI
41
01MKC65_GX000_XG AC FEEDER FAULT 91[38] HMI
42
01MKC65_GX000_XG TPC NON BLOCKING ALARM 91[73] HMI
60
01MKC65_GX010_XD PULSE AMPLIFIER VALI - 90[70] HMI
01 BRIDGE 1
01MKC65_GX010_XG POWER CONVERTER 1 FLT 90[36] HMI
40
01MKC65_GX010_XG POWER CONVERTER 1 90[72] HMI
41 CONDUCTION FLT
01MKC65_GX020_XD PULSE AMPLIFIER VALI - 90[70] HMI
01 BRIDGE 2
01MKC65_GX020_XG POWER CONVERTER 2 FLT 90[36] HMI
40
01MKC65_GX020_XG POWER CONVERTER 2 90[72] HMI
41 CONDUCTION FLT
01MKC65_GX030_XG POWER CONVERTER 3 FLT 90[36] HMI
40
01MKC65_GX030_XG POWER CONVERTER 3 90[72] HMI
41 CONDUCTION FLT
01MKC65_GX040_XG POWER CONVERTER 4 FLT 90[36] HMI
40
01MKC65_GX040_XG POWER CONVERTER 4 90[72] HMI
41 CONDUCTION FLT
01MKC65_GX050_XG POWER CONVERTER 5 FLT 90[36] HMI
40
01MKC65_GX050_XG POWER CONVERTER 5 90[72] HMI
41 CONDUCTION FLT
01MKC65_GX060_XG POWER CONVERTER 6 FLT 90[36] HMI
40
01MKC65_GX060_XG POWER CONVERTER 6 90[72] HMI
41 CONDUCTION FLT
01MKC65_GX070_XG POWER CONVERTER 7 FLT 90[36] HMI
40
01MKC65_GX070_XG POWER CONVERTER 7 91[15] HMI
41 CONDUCTION FLT
01MKC65_GX080_XG POWER CONVERTER 8 FLT 90[36] HMI
40
01MKC65_GX080_XG POWER CONVERTER 8 91[15] HMI
41 CONDUCTION FLT
01MKC65_STA_WD01 MKY10CX040_START_STATUS 0.000000 <- L01_r5_4_0EX'ModbusClientInW 90[1]
> 65535.00
XX PXXXXA4XXXX.40/A
NAME DESCRIPTION STATE INIT AL I/O FROM TO
01PAC00_CF973_ZH0 GEN THRUST BRG COOLING 3 107[4] HMI
4 WTR FLOW
01PAC00_CF973_ZH0 GEN THRUST BRG COOLING 0 107[4] HMI,136[5]
6 WTR FLOW NORMAL
01PAC00_CF975_XQ0 GEN COOLER MAIN OUTLET 0 <-> 10 L01_01-0-23-1 HMI,64[26],107[5]
1 COOLING WTR FLOW
01PAC00_CF975_ZH0 GEN COOLER MAIN OUTLET 2 107[5] HMI
3 COOLING WTR FLOW
01PAC00_CF975_ZH0 GEN COOLER MAIN OUTLET 3 107[5] HMI
4 COOLING WTR FLOW
01PAC00_CF975_ZH0 GEN COOLER MAIN COOLING 0 107[5] HMI,136[5]
6 WTR FLOW NORMAL
01PAC00_CF976_XQ0 GEN GUIDE BRG COOLING 0 <-> 10 L01_01-0-23-0 HMI,64[27],108[6]
1 WTR FLOW
01PAC00_CF976_ZH0 GEN GUIDE BRG COOLING 2 108[6] HMI
3 WTR FLOW
01PAC00_CF976_ZH0 GEN GUIDE BRG COOLING 3 108[6] HMI
4 WTR FLOW
01PAC00_CF976_ZH0 GEN GUIDE BRG COOLING 0 108[6] HMI,136[5]
6 WTR FLOW NORMAL
01PAC00_EU001_ZM0 UNIT CLW SYSTEM STARTUP 0 107[7] HMI,129[24]
5 CONDITIONS
01PAC00_GH001_XM UNIT TECHNICAL WATER 2 L01_02-0-9-1 HMI,107[7],108[1]
01 VALVE AA001 FAILURE
01PAC00_GH001_YL0 UNIT COOL SYSTEM STARTING 108[8] 63[35,36],L01_02-0-20-0
1 ORDER
01PAC00_GH001_YL0 UNIT COOL SYSTEM STOPPING 108[8] 63[35,36],L01_02-0-20-1
2 ORDER
01SCC00_AA901_XG0 CONDENDSOR DEWATER L01_02-0-9-7 HMI,117[10],141[11],147[8],73[30]
1 MAIN VALVE ,118[6,8],63[3],116[8]
01SCC00_AA901_XG2 CONDENDSOR DEWATER L01_02-0-9-6 HMI,134[54,56],69[14],116[1]
1 MAIN VALVE
01SCC00_AA901_YL0 CONDENDSOR DEWATER 116[9] 63[3],L01_02-0-20-4
1 MAIN VALVE
01SCC00_AA901_ZG0 DEWATER MAIN VALVE AA901 118[6] HMI,119[9],118[13],116[8]
2 not OPEN Delay
01SCC00_AA901_ZM1 Dewater Main Valve AA901 2 116[8] HMI
0
01SCC00_AA901_ZM1 Dewater Main Valve AA901 2 116[8] HMI
1 OPENG TLTE
01SCC00_AA901_ZM1 Dewater Main Valve AA901 2 116[8] HMI
2 CLOSG TLTE
01SCC00_AA901_ZU0 DEWATER MAIN VALVE 116[8] HMI
1 ANIMATION WORD
01SCC00_AA902_XG0 CONDENDSOR DEWATER L01_02-0-9-11 HMI,117[10],141[11],147[8],119[2]
1 AUXILIARY VALVE ,114[6],73[30],63[18],115[18]
01SCC00_AA902_XL2 CONDENDSOR DEWATER L01_02-0-9-10 HMI,134[54,56],115[1],69[27]
1 AUXILIARY VALVE
01SCC00_AA902_YL0 CONDENDSOR DEWATER 115[21] 63[18],L01_02-0-20-6
1 AUXILIARY VALVE
01SCC00_AA902_ZG0 DEWATER AUXILARY VALVE 119[2] HMI,119[9],114[4],115[18]
2 AA902 not OPEN Delay
01SCC00_AA902_ZM1 DEWATER AUX VALVE AA902 2 115[18] HMI
0
01SCC00_AA902_ZM1 DEWATER AUX VALVE AA902 2 115[18] HMI
1 OPENG TLTE
01SCC00_AA902_ZM1 DEWATER AUX VALVE AA902 2 115[18] HMI
2 CLOSG TLTE
01SCC00_AA902_ZU0 DEWATER AUXIL VALVE 115[18] HMI
1 ANIMATION WORD
01SCC00_CP505_ZH0 HIGH WATER LEVEL UNDER 0 1 115[19] HMI
7 RUNER IN GC
01SCC00_DE001_ZH0 DEWATER STATE ACTIVE 0 1 115[20] HMI,138[6]
6 POWER TOO HIGH
01SCC00_EA001_ZG0 DEWATER SEQUENCE EA001 46[S0,S99] HMI,61[S3],58[S1],47[S1]
1
01SCC00_EA002_ZG0 REWATER SEQUENCE EA002 47[S0,S99] HMI
1
01SCC00_EU001_ZA0 RUNNER DEWATER REQUEST 53[S3] HMI,117[10],147[8]
1
01SCC00_EU001_ZA0 RUNNER REWATER REQUEST 61[S3],58[S1],55[S1] HMI,119[7]
2
01SCC00_EU001_ZG0 RUNNER DEWATER STATE 48[S1],47[S1],46[S2] HMI,118[13]
1
01SCC00_EU001_ZG0 RUNNER REWATER STATE 48[S1],47[S3],46[S2] HMI,61[S3],58[S1],82[3],119[12],1
2 58[8],152[3]
01SCC00_EU001_ZH0 DEWATER WATER LEVEL or 0 118[7] HMI,147[8],118[12]
3 ACTIVE POWER
01SCC00_EU001_ZH0 REWATER WATER LEVEL or 0 119[6] HMI,119[11]
7 ACTIVE POWER
20CBA00_CL012_ZQ0 WATER HEAD FROM UP/DOWN 0 <-> 70 HMI,98[12]
1 STREAM DIFF
20SCC01_CP001_ZH0 PRESSURES OF 2 HMI,129[21]
6 COMPENSATED COMPRESSED
AIR TANK REACHED
50CBD01_EE101_XG0 INTAKE GATE1 FULLY L08_01-0-5-5 HMI,128[18]
1 OPEN(8M)
XX PXXXXA4XXXX.41/A
NAME DESCRIPTION STATE INIT AL I/O FROM TO
50CBD01_EE101_XG0 INTAKE GATE1 FULLY L08_01-0-5-6 HMI,129[20]
2 CLOSED(0m)
50CBD01_EE101_ZH0 INTAKE GATE1 DROP DOWN 2 HMI,128[19]
4 7.1m
81ADD00_FE231_ZH0 1#MT HV SIDE DEAD VOLTAGE 0 HMI,184[2]
3
81ADD01_FE001_RQ4 1# MT HV SIDE 231 0 <-> 60 L06_r5_2_0EX'ModbusClientInW HMI,121[1]
5 FREQUENCE
81CBC00_01CJA_BS0 SWITCHYARD CONDITIONS 128[17]
1 FOR UNIT 1 BLACK START
81CBC00_01CJA_GE0 SWITCHYARD CONDITIONS 128[15]
1 FOR UNIT 1 GENERATING
81CBC00_01CJA_LC0 SWITCHYARD CONDITIONS 128[16]
1 FOR UNIT 1 LINE CHARGE
XX PXXXXA4XXXX.42/A
2 HIGH LEVEL DIAGRAMS
XX
PXXXXA4XXXX.43/A
3 SEQUENTIAL FUNCTION CHARTS
N S 01CJA00_EA007_ZG01
0
1 01CJA00_EA007_ZS015
N C 01MKA54_AU001_ZA01
1 Apply mechanical brake
2 01CJA00_EA007_ZS025
N C 01BAC00_GS003_ZA02
2 open unit DS
3 01CJA00_EA007_ZS035
N R 01CJA00_EA007_ZG01
99
99 1
TS->BS N S 01CJA00_EA051_ZG01
0 set seq in progress
N C 01CJA00_EU001_ZG11
transfer stop state
1 01CJA00_EA051_ZS015
N C 01BAC00_GS003_ZA01
1 CLOSE DISCONECTOR SWITCH GS003
2 01CJA00_EA051_ZS025
N C 01MKA54_AU001_ZA02
2 release mech brake
4 01CJA00_EA051_ZS035
N C 01MAU24_AA002_ZA01
3 open wg safty closing vavle
N C 01MEU11_EU001_ZA01
start governor R0
5 01CJA00_EA051_ZS045
N C 01BAC00_GS901_ZA01
4 GCB DEAD LINE CLOSING CMD
N C 01MEU11_EU001_ZA21
set isolated grid mode R128 to GOV
6 01CJA00_EA051_ZS055
N C 01MKC65_EU001_ZA04
5 unit CH mode order to excitation
N C 01MKC65_EU001_ZA22
EXC auto chanel select CMD
7 01CJA00_EA051_ZS065
N C 01MKC65_GS101_ZA01
6 starting excitation system
8 01CJA00_EA051_ZS075
N R 01CJA00_EA051_ZG01
99 reset seq in progress
99 1
P0 S 01SCC00_EA001_ZG01
0 DEWATER SEQUENCE IN PROGRESS
1 01SCC00_EA001_ZS015
N C 01SCC00_AA901_ZA01
1 OPEN MAIN DWATER VALVE
2 01SCC00_EA001_ZS025
N S 01SCC00_EU001_ZG01
2 SET RUNNER DEWATER STATE
N R 01SCC00_EU001_ZG02
RESET RUNNER REWATER STATE
3 01SCC00_EA001_ZS035
N C 01SCC00_AA901_ZA02
3 CLOSE MAIN DEWATER VALVE
4 01SCC00_EA001_ZS045
N R 01SCC00_EA001_ZG01
99 Reset Dewater sequence
P0 S 01SCC00_EA002_ZG01
0 REWATER SEQUENCE IN PROGRESS
1 01SCC00_EA002_ZS015
N C 01SCC00_AA901_ZA02
1 CLOSE HIGH PRESSURE DWATER VALVE
N C 01SCC00_AA902_ZA02
CLOSE AUXILARY LOW PRESSURE VALVE
N R 01SCC00_EU001_ZG01
RESET RUNNER DEWATER STATE
P1 F/ 01SCC00_EA001_SFC { 99 } 01SCC00_EA001_ZG01
2 01SCC00_EA002_ZS025
3 01SCC00_EA002_ZS035
N S 01SCC00_EU001_ZG02
3 SET RUNNER REWATER STATE
5 01SCC00_EA002_ZS045
N R 01SCC00_EA002_ZG01
99
RESET RUNNER REWATER SEQUENCE
6 1
IS N C 01CJA00_EU001_ZG00
0 initial state
1 01CJA00_EU001_ZM00
SS N C 01CJA00_EU001_ZG01
1 still stop state
N S 01SCC00_EU001_ZG02
SET REWATER STATE
N R 01SCC00_EU001_ZG01
RESET DEWATER STATE
2 1
2 (((((01CJA00_EU001_ZJ21 + 01CJA00_EU001_ZJ31) 4 /01CJA00_EU001_ZM00
+ 01CJA00_EU001_ZJ41) + 01CJA00_EU001_ZJ51)
+ 01CJA00_EU001_ZJ61) + 01CJA00_EU001_ZJ11) +
01CJA00_EU001_ZJ71
P1 F/ 01CJA00_EA010_SFC { 0 }
2 starting auxiliaries
3 /01CJA00_EA010_ZG01
TS N C 01CJA00_EU001_ZG11
3 transfer stop state
4 5 6
10 ((01CJA00_EU001_ZJ21 + 01CJA00_EU001_ZJ31)
40 01CJA00_EU001_ZJ61 50 01CJA00_EU001_ZJ51
+ 01CJA00_EU001_ZJ41) + 01CJA00_EU001_ZJ71
13 /01CJA00_EA027_ZG01
SE N C 01CJA00_EU001_ZG71
13 Spin Excitation state
17 01CJA00_EU001_ZJ31 + 01CJA00_EU001_ZJ41
P1 F/ 01CJA00_EA073_SFC { 0 }
17 SE->GE
GE N C 01CJA00_EU001_ZG31
20 generating state
1 2
14 01CJA00_EU001_ZJ21 21 01CJA00_EU001_ZJ41
P1 F/ 01CJA00_EA032_SFC { 0 } P1 F/ 01CJA00_EA043_SFC { 0 }
14 GE->SR
21 GE->GC
1 2
/01CJA00_EA032_ZG01 /01CJA00_EA043_ZG01
15 22
01CJA00_EU001_ZJ31
23
P1 F/ 01CJA00_EA034_SFC { 0 }
23 GC->GE
/01CJA00_EA034_ZG01
24
SS->TS
N S 01CJA00_EA010_ZG01
0 set seq in progress
1 01CJA00_EA010_ZS015
N C 01PAC00_AA001_ZA01
1 Start unit cooling system
N C 01MAU24_EA001_ZA01
Start governor oil station
3 01CJA00_EA010_ZS035
N R 01CJA00_EA010_ZG01
99 reset seq in progress
99 1
101
1 2
102 01CJA00_EU001_ZJ12
STOP N R 01CJA00_EU001_ZG09
0 reset unit running state
P1 F/ 01CJA00_EA100_SFC { 0 } P1 F/ 01CJA00_EA100_SFC { 3 } 01CJA00_EU001_ZG09
102
AUX. STARTED
1
1 2
15 ((01CJA00_EU001_ZM01 . /01CJA00_EU001_ZJ12) + 01CJA00_EU001_ZM02)
+ 01CJA00_EU001_ZM03
P1 F/ 01CJA00_EA009_SFC { 0 }
2 (01CJA00_EA021_ZG01 + 01CJA00_EA061_ZG01) + 01CJA00_EA051_ZG01
6 stop auxiliaries
N F/ 01CJA00_EA100_SFC { }
16 /01CJA00_EA009_ZG01 N S 01CJA00_EU001_ZG09
RUNNING 2 set unit running state
2 1
N F/ 01CJA00_EA100_SFC { }
4
5 1
3 2 1
7 01CJA00_EU001_ZM03
11 ((/01CJA00_EA002_ZG01 . /01CJA00_EA001_ZG01) .
01MEU11_FS001_XH01) . 01MEU11_FS001_XM51
10 ((/01CJA00_EA002_ZG01 . /01CJA00_EA001_ZG01) .
/01MEU11_FS001_XH01) . 01MEU11_FS001_XM51
ES without EB N F/ 01CJA00_EA008_SFC { 0 }
7
N F/ 01CJA00_EA002_SFC { }
P1 F/ 01CJA00_EA007_SFC { 0 }
10 N F/ 01CJA00_EA001_SFC { }
12 /01CJA00_EA007_ZG01 8 01CJA00_EA008_ZG01
N F/ 01CJA00_EA100_SFC { }
8
9 1
11
Reserved for EB
9
/01CJA00_EA007_ZG01 /01CJA00_EA008_ZG01
13 14
TS->SR
N S 01CJA00_EA021_ZG01
0 set seq in progress
N C 01CJA00_EU001_ZG11
transfer stop state
1 01CJA00_EA021_ZS015
N C 01BAC00_GS003_ZA01
1 CLOSE DISCONECTOR SWITCH GS003
2 01CJA00_EA021_ZS025
N C 01MKA54_AU001_ZA02
2 Release mechanical brake
N C 01MEU11_EU001_ZA09 01CJA00_EU001_ZG14
ISOLATED MODE R6 FOR SELF SYNCHRONIZE to GOV
4 01CJA00_EA021_ZS035
N C 01MAU24_AA002_ZA01
3 Open governor solenoid valve
N C 01MEU11_EU001_ZA01 01CJA00_EA021_DL04
Start speed governor
5 01CJA00_EA021_ZS045
N R 01CJA00_EA021_ZG01
99 reset seq in progress
99 1
N S 01CJA00_EA027_ZG01
0 set seq in progress
SR->SE 1 01CJA00_EA027_ZS015
N C 01MKC65_GS101_ZA01 /01CJA00_EU001_ZG14
1 START EXCITATION
11 01CJA00_EA027_ZS025
N R 01CJA00_EA027_ZG01
99 reset seq in progress
99 1
GE->GC N S 01CJA00_EA043_ZG01
0 set seq in progress
1 01CJA00_EA043_ZS015
N C 01CJA00_DE001_ZA12
1 set active power to minimal
N C 01CJA00_DE002_ZA11
set reactive power to ini
2 01CJA00_EA043_ZS025
N C 01MEU11_EU001_ZA11
2 governor condenser mode R70=1
3 01CJA00_EA043_ZS035
N C 01MAU24_AA002_ZA02
3 close wg safty closing vavle
N C 01SCC00_EU001_ZA01
runner dewatering
4 01CJA00_EA043_ZS045
N R 01CJA00_EA043_ZG01
99 reset seq in progress
99 01CJA00_EA043_ZD099
TS->CH N S 01CJA00_EA061_ZG01
0 set seq in progress
N C 01CJA00_EU001_ZG11
transfer stop state
1 01CJA00_EA061_ZS015
N C 01BAC00_GS003_ZA01
1 CLOSE DISCONECTOR SWITCH GS003
2 01CJA00_EA061_ZS025
N C 01MKA54_AU001_ZA02
2 release mech brake
4 01CJA00_EA061_ZS035
N C 01MAU24_AA002_ZA01
3 open wg safty closing vavle
N C 01MEU11_EU001_ZA01
start governor R0
5 01CJA00_EA061_ZS045
N C 01BAC00_GS901_ZA01
4 GCB DEAD LINE CLOSING CMD
N C 01MEU11_EU001_ZA21
set isolated grid mode R128 to GOV
6 01CJA00_EA061_ZS055
N C 01MKC65_EU001_ZA04
5 unit CH mode order to excitation
N C 01MKC65_EU001_ZA22
EXC auto chanel select CMD
7 01CJA00_EA061_ZS065
N C 01MKC65_GS101_ZA01
6 starting excitation system
8 01CJA00_EA061_ZS075
N R 01CJA00_EA061_ZG01
99 reset seq in progress
99 1
GC->GE N S 01CJA00_EA034_ZG01
0 set seq in progress
1 01CJA00_EA034_ZS015
N C 01SCC00_EU001_ZA02
1 runner rewatering transmit
N C 01CJA00_DE002_ZA11
set reactive power to 0
2 01CJA00_EA034_ZS025
N C 01MAU24_AA002_ZA01
2 open wg safty closing vavle
N C 01MEU11_EU001_ZA12
governor condenser mode R70=0
4 01CJA00_EA034_ZS035
N C 01CJA00_DE001_ZA11
3 set active power to init
5 01CJA00_EA034_ZS045
N R 01CJA00_EA034_ZG01
99 reset seq in progress
99 1
GE->SR N S 01CJA00_EA032_ZG01
0 set seq in progress
1 01CJA00_EA032_ZS015
N C 01CJA00_DE001_ZA12
1 SET ACT.POWER TO minimal
N C 01CJA00_DE002_ZA11
set reactive power to 0
2 01CJA00_EA032_ZS025
N C 01BAC00_GS901_ZA02
2 Open unit CB
3 01CJA00_EA032_ZS035
N C 01MKC65_GS101_ZA02
3 STOP EXCITATION
4 01CJA00_EA032_ZS045
N R 01CJA00_EA032_ZG01
99 reset seq in progress
99 1
CH->GE N S 01CJA00_EA036_ZG01
0
1 01CJA00_EA036_ZS015
N C 01MEU11_EU001_ZA22
1 reset isolated grid mode R128
2 01CJA00_EA036_ZS025
N C 01CJA00_DE001_ZA11
2 set init act. power
3 01CJA00_EA036_ZS035
N R 01CJA00_EA036_ZG01
99
99 1
N S 01CJA00_EA008_ZG01
ES->TS 0 set seq in progress
P1 F/ 01CJA00_EA021_SFC { 99 } 01CJA00_EA021_ZG01
P1 F/ 01CJA00_EA032_SFC { 99 } 01CJA00_EA032_ZG01
P1 F/ 01CJA00_EA027_SFC { 99 } 01CJA00_EA027_ZG01
P1 F/ 01CJA00_EA036_SFC { 99 } 01CJA00_EA036_ZG01
P1 F/ 01CJA00_EA034_SFC { 99 } 01CJA00_EA034_ZG01
P1 F/ 01CJA00_EA043_SFC { 99 } 01CJA00_EA043_ZG01
P1 F/ 01CJA00_EA061_SFC { 99 } 01CJA00_EA061_ZG01
P1 F/ 01CJA00_EA007_SFC { 99 } 01CJA00_EA007_ZG01
P1 F/ 01CJA00_EA001_SFC { 99 } 01CJA00_EA001_ZG01
P1 F/ 01CJA00_EA002_SFC { 99 } 01CJA00_EA002_ZG01
P1 F/ 01CJA00_EA051_SFC { 99 } 01CJA00_EA051_ZG01
P1 F/ 01CJA00_EA073_SFC { 99 } 01CJA00_EA073_ZG01
1 01CJA00_EA008_ZS015
N C 01BAC00_GS901_ZA02
1 OPEN UNIT GCB
N C 01MKC65_GS101_ZA02
STOP EXCITATION
N C 01MAU24_AA002_ZA02
Close governor solenoid valve
N C 01MEU11_EU001_ZA02
Stop speed governor
N C 01MEU11_EU001_ZA12
Reset GOV Condensor mode R70
N C 01MEU11_EU001_ZA22
Reset GOV Insolated Network mode R128
2 01CJA00_EA008_ZS025
N C 01MKA54_AU001_ZA01
2
Apply mechanical brake
3 01CJA00_EA008_ZS035
N C 01BAC00_GS003_ZA02
3 open unit DS
4 01CJA00_EA008_ZS045
N R 01CJA00_EA008_ZG01
99 reset seq in progress
1
99
TS->IS N S 01CJA00_EA009_ZG01
0 set seq in progress
P1 F/ 01CJA00_EA010_SFC { 99 } 01CJA00_EA010_ZG01
N C 01CJA00_EU001_ZG11
transfer stop state
1 01CJA00_EA009_ZS015
N C 01MAU24_EA001_ZA02
1 Stop governor oil station
N C 01MKA54_AU001_ZA02
Release mechanical brake
N C 01PAC00_AA001_ZA02
stop unit cooling system
N C 01BAC00_GS901_ZA02 /01BAC00_GS901_XG02
open unit CB if not
N C 01BAC00_GS003_ZA02 /01BAC00_GS003_XG02
open unit DS (CB open)
3 01CJA00_EA009_ZS025
N R 01CJA00_EA009_ZG01
99 reset seq in progress
99 1
P1 F/ 01CJA00_EA032_SFC { 99 } 01CJA00_EA032_ZG01
P1 F/ 01CJA00_EA027_SFC { 99 } 01CJA00_EA027_ZG01
P1 F/ 01CJA00_EA036_SFC { 99 } 01CJA00_EA036_ZG01
P1 F/ 01CJA00_EA034_SFC { 99 } 01CJA00_EA034_ZG01
P1 F/ 01CJA00_EA043_SFC { 99 } 01CJA00_EA043_ZG01
P1 F/ 01CJA00_EA051_SFC { 99 } 01CJA00_EA051_ZG01
P1 F/ 01CJA00_EA061_SFC { 99 } 01CJA00_EA061_ZG01
P1 F/ 01CJA00_EA073_SFC { 99 } 01CJA00_EA073_ZG01
1 01CJA00_EA001_ZS015
N C 01MAU24_AA002_ZA02 01CJA00_EU001_ZM02
1 close wg safty closing vavle
N C 01MEU11_EU001_ZA02 01CJA00_EU001_ZM02
stop governor R0=0
N C 01CJA00_DE001_ZA01 01BAC00_GS901_XG01 . 01CJA00_EU001_ZM01
set active power to 0
N C 01CJA00_DE002_ZA01 01BAC00_GS901_XG01
set reactive power to 0
2 01CJA00_EA001_ZS025 . 01CJA00_EA001_ZD001
N C 01BAC00_GS901_ZA02
2 open unit CB
3 01CJA00_EA001_ZS035
N C 01MKC65_GS101_ZA02
3 stopping excitation sys
4 01CJA00_EA001_ZS045
N C 01MAU24_AA002_ZA02 01CJA00_EU001_ZM01
4 close wg safty closing vavle
N C 01MEU11_EU001_ZA02 01CJA00_EU001_ZM01
stop governor R0=0
N C 01MEU11_EU001_ZA22
Reset GOV Insolated mode R128
5 01CJA00_EA001_ZS055
N R 01CJA00_EA001_ZG01
99 reset seq in progress
99 1
GC ->NMS N S 01CJA00_EA002_ZG01
0 set seq in progress
P1 F/ 01CJA00_EA034_SFC { 99 } 01CJA00_EA034_ZG01
P1 F/ 01CJA00_EA043_SFC { 99 } 01CJA00_EA043_ZG01
P1 F/ 01CJA00_EA021_SFC { 99 } 01CJA00_EA021_ZG01
P1 F/ 01CJA00_EA027_SFC { 99 } 01CJA00_EA027_ZG01
P1 F/ 01CJA00_EA073_SFC { 99 } 01CJA00_EA073_ZG01
1 01CJA00_EA002_ZS015
N C 01CJA00_DE002_ZA11
1 set reactive power to 0
N C 01MAU24_AA002_ZA02
close wg safty closing vavle
N C 01MEU11_EU001_ZA12
governor condenser mode R70=0
2 01CJA00_EA002_ZS025 . 01CJA00_EA002_ZD001
N C 01BAC00_GS901_ZA02
2 open unit CB
3 01CJA00_EA002_ZS035
N C 01MKC65_GS101_ZA02
3 stopping excitation sys
N C 01SCC00_EU001_ZA02 /01SCC00_EU001_ZG02 + 01SCC00_EA001_ZG01
runner rewatering shutdown
4 01CJA00_EA002_ZS045
N C 01MEU11_EU001_ZA02
4 stop governor R0=0
5 01CJA00_EA002_ZS055
N R 01CJA00_EA002_ZG01
99 reset seq in progress
99 1
N S 01CJA00_EA073_ZG01
0 set seq in progress
SE->GE 1 01CJA00_EA073_ZS015
10
1 2
3 1
N C 01BAC00_GS901_ZA03 /01CJA00_EU001_ZG14
4 01CJA00_EA073_ZS025 1 EXACT-SYNCHRONIZE CLOSE
UNIT CB CLOSED
N C 01BAC00_GS901_ZA04 01CJA00_EU001_ZG14 . 01BBA00_FE001_ZQ45
SELF-SYNCHRONIZE CLOSE
6 01CJA00_EA073_ZS025
N C 01CJA00_DE001_ZA11
2 set init act. power
N C 01CJA00_DE002_ZA11
set reactive power to 0
7 01CJA00_EA073_ZS035
N R 01CJA00_EA073_ZG01
99 reset seq in progress
5 1
29
ACURATOR PROCESS OR
01MKC65_GS101_YL01
IN1
01BAC00_GS901_XG01
IN2
1 17 34
SIM_DEVICE_2POS SIM_DEVICE_2POS SIM_DEVICE_2POS
01BAC00_GS003_YL01 01BAC00_GS003_XG01 01MAU24_EU001_YL01 01MAU24_AP001_XG01 01MKC65_GS101_XG01
Out ord1 Pos1 Out ord1 Pos1 Out ord1 Pos1
01BAC00_GS003_YL02 01BAC00_GS003_XG02 01MAU24_EU001_YL02 01MKC65_GS101_YL02 01MKC65_GS101_XG02
Out ord2 Pos2 Out ord2 Pos2 Out ord2 Pos2
0 0 0
Manu Manu Manu
0 0 0
Pos_Manu Pos_Manu Pos_Manu
Delay(Cyc) Delay(Cyc) Delay(Cyc)
10 10 10
7 16
MOVE_B SIM_STATUS_M
2 01MKA54_CG565_XG01 35
SIM_DEVICE_2POS IN RE Value Input SIM_DEVICE_2POS
01MKA54_AU001_YL01 01PAC00_GH001_YL01 01PAC00_AA001_XG01
Out ord1 Pos1 Out ord1 Pos1
01MKA54_CG565_XG01 01PAC00_GH001_YL02
Out ord2 Pos2 Out ord2 Pos2
0 0
Manu Manu
0 0
Pos_Manu Pos_Manu
Delay(Cyc) Delay(Cyc)
10 10
36
SIM_DEVICE_2POS
01PAC00_GH001_YL01 01MAU24_AA005_XG01
Out ord1 Pos1
01PAC00_GH001_YL02 01MAU24_AA005_XG02
Out ord2 Pos2
0
3 18 Manu
0
SIM_DEVICE_2POS SIM_DEVICE_2POS Pos_Manu
01SCC00_AA901_YL01 01SCC00_AA901_XG01 01SCC00_AA902_YL01 01SCC00_AA902_XG01
Out ord1 Pos1 Out ord1 Pos1 Delay(Cyc)
Out ord2 Pos2 Out ord2 Pos2 10
0 0
Manu Manu
0 0
Pos_Manu Pos_Manu
Delay(Cyc) Delay(Cyc)
10 10
4 19
SIM_DEVICE_2POS SIM_DEVICE_2POS
01MKA54_AA001_YL01 01MKA54_AA001_XG01 01MKA54_AA002_YL01 01MKA54_AA002_XG01
Out ord1 Pos1 Out ord1 Pos1
01MKA54_AA001_YL02 01MKA54_AA002_YL02
Out ord2 Pos2 Out ord2 Pos2
0 0
Manu Manu
0 0
Pos_Manu Pos_Manu
Delay(Cyc) Delay(Cyc)
10 10
9 12 01SIM_ACT_INT16_0001
AND SEL
01BAC00_GS901_YL03 01SIM_ACT_REAL_0001
IN1 G RE
01BAC00_GS901_ZA01
IN2 IN1
01SIM_REG01_RI06
IN2
10
AND
01CJA00_EU001_ZG14
IN1
01BAC00_GS901_YL04
IN2
5 13 20 24
SEL LAG_R AO_SCALE SIM_ANA_M 01PAC00_CF972_XQ01
01PAC00_AA001_XG01 01PAC00_CF972_XQ01
TURBINE GUIDE BRG COOLING WTR FLW
G RE IN RE IN RE Value Input Unit: m3/s
0 10 100
IN1 TFILT ULA IMax Err 6553/32767 (0/10 m3/s)
80 0
IN2 LLA IMin
100 32767
UL ERR OMax 25
0 6553
LL OMin SIM_ANA_M 01PAC00_CF973_XQ01
01PAC00_CF973_XQ01
GEN THRUST BRG COOLING WTR FLOW
Value Input Unit: m3/s
6553/32767 (0/10 m3/s)
26
SIM_ANA_M 01PAC00_CF975_XQ01
01PAC00_CF975_XQ01
GEN COOLER MAIN OUTLET COOLING WTR FLOW
Value Input Unit: m3/s
6553/32767 (0/10 m3/s)
27
SIM_ANA_M 01PAC00_CF976_XQ01
01PAC00_CF976_XQ01
GEN GUIDE BRG COOLING WTR FLOW
Value Input Unit: m3/s
6553/32767 (0/10 m3/s)
6 14 21 28
SEL LAG_R AO_SCALE SIM_ANA_M 01MAU24_CP001_XQ01
01MAU24_AP001_XG01 01MAU24_CP001_XQ01
GOVERNOR ACCUMULATOR OIL PRESSURE
G RE IN RE IN RE Value Input Unit: bar
01SIM_ACT_INIT 10 100
IN1 TFILT ULA IMax Err 6553/32767 (0/50 bar)
85 0
IN2 LLA IMin
100 32767
UL ERR OMax
0 6553
LL OMin
30
SIM_STATUS_M
01MAU24_CL001_XH03
Value Input
15 31
SIM_STATUS_M SIM_STATUS_M
01MAU24_CP001_ZH04 01MAU24_CL002_XH51 01MAU24_CP002_XH03
Value Input Value Input
23 32
MOVE_B SIM_STATUS_M
01MAU24_CP001_ZH03 01MAU24_CL002_XH03
IN RE Value Input
136/1(+1p)
41
15 SIM_STATUS_SEL
SIM_STATUS_SEL 01SIM_INIT_1SYCLE
01SIM_INIT_1SYCLE Sel 01BAC00_GS005_XG02
Sel 01BAT00_EN001_XM08 01BAC00_GS005_XG02 01BAC00_GS005_XG02 UNIT EARTHING SWITCH (901-5) OPEN
01BAT00_EN001_XM08 01BAT00_EN001_XM08 TRANSFORMER COOLING SYSTEM AUTO POSITION Value0 Input Ini:
Value0 Input Ini:
01SIM_INIT_TURE
01SIM_INIT_TURE Value1 DETECTED
Value1 DETECTED
42
SIM_STATUS_SEL
01SIM_INIT_1SYCLE
4 Sel 01BAC00_GS038_XG02
SIM_STATUS_SEL 01BAC00_GS038_XG02 01BAC00_GS038_XG02 UNIT EARTHING SWITCH (901-38) OPEN
01SIM_INIT_1SYCLE Value0 Input Ini:
Sel 01SIM_INIT_TURE
01BAC00_GS035_XG02 Value1 DETECTED
01BAC00_GS035_XG02 01BAC00_GS035_XG02 UNIT EARTHING SWITCH (901-35) OPEN
Value0 Input Ini:
01SIM_INIT_TURE
Value1 DETECTED
43
SIM_STATUS_SEL
01SIM_INIT_1SYCLE
Sel 01CJA00_EP001_XM51
01CJA00_EP001_XM51 01CJA00_EP001_XM51 GCB SYNCHRONIZER READY FOR OPERATION
Value0 Input Ini:
01SIM_INIT_TURE
16 Value1 DETECTED
SIM_STATUS_SEL
01SIM_INIT_1SYCLE
Sel 01BAC00_GS025_XG02
01BAC00_GS025_XG02 01BAC00_GS025_XG02 UNIT AUX TRF EARTHING SWITCH (641-25) OPEN
Value0 Input Ini:
01SIM_INIT_TURE
Value1 DETECTED
50
SIM_SELECTOR
01SIM_INIT_UP001 01CJA00_GH001_XL31
Up Sel 0
01SIM_INIT_DW001 01CJA00_GH001_XL32
Down Sel 1
01CJA00_GH001_XL33
Sel 2
Sel 3
17 Sel 4
SIM_STATUS_SEL
01SIM_INIT_1SYCLE
Sel 01CJA00_EP002_XM51
01CJA00_EP002_XM51 01CJA00_EP002_XM51 GCB SYN. CHECK RELAY READY FOR OPERATION
Value0 Input Ini:
01SIM_INIT_TURE 51
Value1 DETECTED
SIM_SELECTOR
01SIM_INIT_UP003 01CJA00_GH003_XL21
Up Sel 0
01SIM_INIT_DW003 01CJA00_GH003_XL22
Down Sel 1
01CJA00_GH003_XL23
Sel 2
Sel 3
Sel 4
XX INIT : Initial Pre Start Condition - REV : 99 - 11/JAN/17 15:50 - POUName : L01_7SIM
.66/A
135/2 (-1p) 135/1(-1p)
5
SIM_STATUS_SEL 39
01SIM_INIT_1SYCLE SIM_STATUS_SEL
Sel 01CJA00_GS110_XM51 01SIM_INIT_1SYCLE
01CJA00_GS110_XM51 01CJA00_GS110_XM51 24VDC DEVICE POWER SUPPLY(2W1+) Sel 01CJA00_GS011_XM51
Value0 Input Ini:
01CJA00_GS011_XM51 01CJA00_GS011_XM51 220VDC MEASUR DEVICES POWER SUPPLY(5W1+)
01SIM_INIT_TURE Value0 Input Ini:
Value1 PRESENCE 01SIM_INIT_TURE
Value1 PRESENCE
18
SIM_STATUS_SEL 44
01SIM_INIT_1SYCLE SIM_STATUS_SEL
Sel 01CJA00_GS012_XM51 01SIM_INIT_1SYCLE
01CJA00_GS012_XM51 01CJA00_GS012_XM51 220VDC EMERGENCY TRIP POWER SUPPLY(5E1+) Sel 01CJA00_GS109_XM51
Value0 Input Ini:
01CJA00_GS109_XM51 01CJA00_GS109_XM51 24VDC CONTROL POWER SUPPLY(2C1+)
01SIM_INIT_TURE Value0 Input Ini:
Value1 PRESENCE 01SIM_INIT_TURE
Value1 PRESENCE
45
SIM_STATUS_SEL
6 01SIM_INIT_1SYCLE
SIM_STATUS_SEL Sel 01MAU24_AP001_XM52
01SIM_INIT_1SYCLE 01MAU24_AP001_XM52 01MAU24_AP001_XM52 GOVERNOR PUMP AP001 POWER
Sel 01MAU24_AP001_XM51 Value0 Input Ini:
01MAU24_AP001_XM51 01MAU24_AP001_XM51 GOVERNOR PUMP AP001 MOTOR 01SIM_INIT_TURE
Value0 Input Value1 NORMAL
01SIM_INIT_TURE Ini:
Value1 NORMAL
46
SIM_STATUS_SEL
19 01SIM_INIT_1SYCLE
SIM_STATUS_SEL Sel 01MAU24_AP002_XM51
01SIM_INIT_1SYCLE 01MAU24_AP002_XM51 01MAU24_AP002_XM51 GOVERNOR PUMP AP002 MOTOR
Sel 01MAU24_AP001_XL21 Value0 Input Ini:
01MAU24_AP001_XL21 01MAU24_AP001_XL21 GOVERNOR PUMP AP001 IN AUTO MODE 01SIM_INIT_TURE
Value0 Input Value1 NORMAL
01SIM_INIT_TURE Ini:
Value1 DETECTED
47
SIM_STATUS_SEL
20 01SIM_INIT_1SYCLE
Sel 01MAU24_AP002_XL21
SIM_STATUS_SEL 01MAU24_AP002_XL21 01MAU24_AP002_XL21 GOVERNOR PUMP AP002 IN AUTO MODE
01SIM_INIT_1SYCLE Value0 Input Ini:
Sel 01MAU24_AP002_XM52 01SIM_INIT_TURE
01MAU24_AP002_XM52 01MAU24_AP002_XM52 GOVERNOR PUMP AP002 POWER Value1 DETECTED
Value0 Input Ini:
01SIM_INIT_TURE
Value1 NORMAL
48
SIM_STATUS_SEL
01SIM_INIT_1SYCLE
Sel 01MAU24_AP003_XL21
7 01MAU24_AP003_XL21 01MAU24_AP003_XL21 LEAKAGE OIL PUMP AP003 IN AUTO MODE
SIM_STATUS_SEL Value0 Input Ini:
01SIM_INIT_1SYCLE 01SIM_INIT_TURE
Value1 DETECTED
Sel 01MAU24_AP003_XM51
01MAU24_AP003_XM51 01MAU24_AP003_XM51 LEAKAGE OIL PUMP AP003 FAULT
Value0 Input Ini:
01SIM_INIT_TURE
Value1 NORMAL
49
SIM_STATUS_SEL
01SIM_INIT_1SYCLE
8 Sel 01MAU24_AA002_XL21
SIM_STATUS_SEL 01MAU24_AA002_XL21 01MAU24_AA002_XL21 GOV PUMP AP002 UNLOAD VALVE
01SIM_INIT_1SYCLE Value0 Input Ini:
Sel 01MAU24_AA001_XL21
01SIM_INIT_TURE
Value1 AUTO
01MAU24_AA001_XL21 01MAU24_AA001_XL21 GOV PUMP AP001 UNLOAD VALVE
Value0 Input Ini:
01SIM_INIT_TURE
Value1 AUTO
XX INIT : Initial Pre Start Condition - REV : 99 - 11/JAN/17 15:50 - POUName : L01_7SIM
.67/A
135/3 (-1p) 135/4 (-1p)
Turbine Auxilary Initial
9 31
SIM_STATUS_SEL SIM_STATUS_SEL
01SIM_INIT_1SYCLE 01SIM_INIT_1SYCLE
Sel 01MAU24_EU014_XM01 Sel 01MAU24_EU014_XM51
01MAU24_EU014_XM01 01MAU24_EU014_XM01 01MAU24_EU014_XM51 01MAU24_EU014_XM51 GOVERNOR OIL STATION CTRL POWER 24VDC 1
GOVERNOR OIL STATION PLC Value0 Input
Value0 Input Ini: 01SIM_INIT_TURE Ini:
01SIM_INIT_TURE Value1 NORMAL
Value1 NORMAL
21 35
SIM_STATUS_SEL SIM_STATUS_SEL
01SIM_INIT_1SYCLE 01SIM_INIT_1SYCLE
Sel 01MAU24_EU014_XM52 Sel 01MEA41_CF402_XM51
01MAU24_EU014_XM52 01MAU24_EU014_XM52 01MEA41_CF402_XM51 01MEA41_CF402_XM51 SHAFT SEAL INPUT WATER FLOW CF402S
GOVERNOR OIL STATION CTRL POWER 24VDC 2 Value0 Input
Value0 Input Ini: 01SIM_INIT_TURE Ini:
01SIM_INIT_TURE Value1 NORMAL
Value1 NORMAL
10 32
SIM_STATUS_SEL SIM_STATUS_SEL
01SIM_INIT_1SYCLE 01SIM_INIT_1SYCLE
Sel 01MEA41_CP402_XM51 Sel 01MEA41_GH001_XM51
01MEA41_CP402_XM51 01MEA41_CP402_XM51 01MEA41_GH001_XM51 01MEA41_GH001_XM51 UNIT INSTRUMENT CUBICLE 24VDC POWER MODULE 1
SHAFT SEAL INPUT WATER PRESSURE CP402S Value0 Input
Value0 Input Ini: 01SIM_INIT_TURE Ini:
01SIM_INIT_TURE Value1 NORMAL
Value1 NORMAL
22 36
SIM_STATUS_SEL SIM_STATUS_SEL
01SIM_INIT_1SYCLE 01SIM_INIT_1SYCLE
Sel 01MEA41_GH001_XM52 Sel 01MEU11_EN001_XG01
01MEA41_GH001_XM52 01MEA41_GH001_XM52 01MEU11_EN001_XG01 01MEU11_EN001_XG01 R80N MAIN T-SLG OPERATION
UNIT INSTRUMENT CUBICLE 24VDC POWER MODULE 2 Value0 Input
Value0 Input Ini: 01SIM_INIT_TURE Ini:
01SIM_INIT_TURE Value1 RUNNING
Value1 NORMAL
37
SIM_STATUS_SEL
01SIM_INIT_1SYCLE
Sel 01MEU11_FS001_XM51
11 01MEU11_FS001_XM51 01MEU11_FS001_XM51 RD29 TADT MAJOR
Value0 Input Ini:
SIM_STATUS_SEL 01SIM_INIT_TURE
01SIM_INIT_1SYCLE Value1 NORMAL
Sel 01MEU11_EN002_XG01
01MEU11_EN002_XG01 01MEU11_EN002_XG01 R80S STANDBY T-SLG OPERATION
Value0 Input Ini:
01SIM_INIT_TURE
Value1 RUNNING
33
SIM_STATUS_SEL
01SIM_INIT_1SYCLE
Sel 01MEU11_GW002_XM51
23 01MEU11_GW002_XM51 01MEU11_GW002_XM51 GOV CONTROL POWER 24VDC CIRCUIT 2
SIM_STATUS_SEL Value0 Input Ini:
01SIM_INIT_1SYCLE 01SIM_INIT_TURE
Value1 NORMAL
Sel 01MEU11_EU001_XL21
01MEU11_EU001_XL21 01MEU11_EU001_XL21 GOVERNOR SYSTEM REMOTE AUTO MODE
Value0 Input Ini:
01SIM_INIT_TURE
Value1 DETECTED
38
SIM_STATUS_SEL
01SIM_INIT_1SYCLE
Sel 01MEU11_EN002_XM51
24 01MEU11_EN002_XM51 01MEU11_EN002_XM51 R29S STANDBY T-SLG UPC MAJOR FAULT
Value0 Input Ini:
SIM_STATUS_SEL 01SIM_INIT_TURE
01SIM_INIT_1SYCLE Value1 N-DET
Sel 01MEU11_EN001_XM51
01MEU11_EN001_XM51 01MEU11_EN001_XM51 R29N MAIN T-SLG UPC MAJOR FAULT
Value0 Input Ini:
01SIM_INIT_TURE
Value1 N-DET
XX INIT : Initial Pre Start Condition - REV : 99 - 11/JAN/17 15:50 - POUName : L01_7SIM
.68/A
Governor Initial
12 28
SIM_STATUS_SEL SIM_STATUS_SEL
01SIM_INIT_1SYCLE 01SIM_INIT_1SYCLE
Sel 01MEU11_GW001_XM51 Sel 01MKA54_AA001_XL21
01MEU11_GW001_XM51 01MEU11_GW001_XM51 GOV CONTROL POWER 24VDC CIRCUIT 1 01MKA54_AA001_XL21 01MKA54_AA001_XL21
Value0 Input GENERATOR EMERGENCY FIRE FIGHTING VALVE 1
01SIM_INIT_TURE Ini: Value0 Input Ini:
Value1 NORMAL 01SIM_INIT_TURE
Value1 AUTO
25 29
SIM_STATUS_SEL SIM_STATUS_SEL
01SIM_INIT_1SYCLE 01SIM_INIT_1SYCLE
Sel 01MKA54_AA002_XL21 Sel 01MKA54_CP901_XM01
01MKA54_AA002_XL21 01MKA54_AA002_XL21 GENERATOR EMERGENCY FIRE FIGHTING VALVE 2 01MKA54_CP901_XM01 01MKA54_CP901_XM01
Value0 Input MECHANICAL BRAKING INLET SOURCE PRESSURE
01SIM_INIT_TURE Ini: Value0 Input Ini:
Value1 AUTO 01SIM_INIT_TURE
Value1 NORMAL
13
SIM_STATUS_SEL 30
01SIM_INIT_1SYCLE SIM_STATUS_SEL
Sel 01MKC65_GH001_XL31 01SIM_INIT_1SYCLE
01MKC65_GH001_XL31 01MKC65_GH001_XL31 EXCITATION CONTROL LEVEL Sel 01MKC65_DE001_XM51
Value0 Input Ini:
01MKC65_DE001_XM51 01MKC65_DE001_XM51 EXCITATION READY FOR OPERATION
01SIM_INIT_TURE Value0 Input Ini:
Value1 REMOTE 01SIM_INIT_TURE
Value1 DETECTED
26 34
SIM_STATUS_SEL SIM_STATUS_SEL
01SIM_INIT_1SYCLE 01SIM_INIT_1SYCLE
Sel 01PAC00_AA001_XL21 Sel 01MEA41_CG605_XG02
01PAC00_AA001_XL21 01PAC00_AA001_XL21 UNIT TECHNICAL WATER VALVE AA001 AUTO 01MEA41_CG605_XG02 01MEA41_CG605_XG02 REGULATING RING PIN CONTACTOR RELEASED
Value0 Input Ini: Value0 Input Ini:
01SIM_INIT_TURE 01SIM_INIT_TURE
Value1 DETECTED Value1 DETECTED
14
SIM_STATUS_SEL
01SIM_INIT_1SYCLE
Sel 01SCC00_AA901_XG21
01SCC00_AA901_XG21 01SCC00_AA901_XG21 CONDENDSOR DEWATER MAIN VALVE
Value0 Input Ini:
01SIM_INIT_TURE
Value1 AUTO
27
SIM_STATUS_SEL
01SIM_INIT_1SYCLE
Sel 01SCC00_AA902_XL21
01SCC00_AA902_XL21 01SCC00_AA902_XL21 CONDENDSOR DEWATER AUXILIARY VALVE
Value0 Input Ini:
01SIM_INIT_TURE
Value1 AUTO
XX INIT : Initial Pre Start Condition - REV : 99 - 11/JAN/17 15:50 - POUName : L01_7SIM
.69/A
4.3 REG01 : Governor and MIV regulator - REV : 159 - 12/JAN/17 08:42 - POUName : L01_7SIM
01MAU24_AA002_ZG01
GOVERNOR SOLENOID AA002 VALVE OPEN Memory
Ini:
S:EU014
YES
42
SIM_GOVERNOR
01MAU24_AA002_ZG01 01SIM_REG01_REAL_0005
01MEU11_EM001_ZG01 Open Saf eV Speed
GOVERNOR SYSTEM ON Memory 01MEU11_EM001_ZG01 01SIM_REG01_REAL_0006
Ini: R0-T(On) Power
S:EU001 01MEU11_EM001_YL11 01SIM_REG01_REAL_0004
YES R21(+) Opening
01MEU11_EM001_YL12
R22(-) 52 54
01MEU11_FS001_XH14
Sp=0% MOVE_B SIM_STATUS_M
01MEU11_EM001_YL06 01MEU11_FS001_XH04
R7(Ana) Sp>90% IN RE Value Input
01MEU11_EM001_YL05 01MEU11_FS001_XH05
14 Power_reg Sp>95%
01CJA00_DE001_ZG42 01MEU11_FS001_XH03
01CJA00_DE001_ZP01 DIV Openg_reg Sp<50%
ACTIVE POWER SP FEEDBACK 01CJA00_DE001_ZP01 01SIM_REG01_REAL_0001 01MEU11_FS001_XH02
Unit: MW IN1 Power sp Sp<20%
S:DE001 01SIM_REG01_RI07 : 10000.00000 01SIM_REG01_REAL_0003 01MEU11_FS001_XH01
0/12000 (0/120 MW) IN2 Opening sp Sp<5% 1: Speed Switch / WG full open/close no program;
2: Openg_reg no need: if not Power_reg;
15 01MEU11_EU001_TL04
01CJA00_DG001_ZP01 DIV R70(GC) 3: Insolated network mode, no program;
WG OPENING SP FEEDBACK 01CJA00_DG001_ZP01 4: Dewater power,no program, condensor speed logic wrong
Unit: % IN1 CB Clsd
01SIM_REG01_RI08 : 10000.00000 01MEU11_EU001_ZG21 5: ZG01 is not DO pulse
S:DG001 ISONET
0/10000 (0/100 %)
IN2 6: Full close input?
16 01SIM_REG01_BOO_0006 01MEA41_CG002_XG03
MOVE_B Braking E Full open
01MKA54_CG565_XG01 01MEA41_CG015_XG01
IN RE Braking M Full close
Noload(%) Step_reg
01SIM_REG01_RI01
01SIM_REG01_RI01 : 0.19000 01SIM_REG01_RI02 : 0.00500
Ini:0.19 (19 %)
17
0/1 (0/100 %) AND
01BAC00_GS901_XG01
IN1
01MKC65_GS101_XG01
IN2
01BBA00_DE003_ZH07
IN3
3 18 39
MUL AO_SCALE SIM_ANA_M 01MEU11_CS001_XQ01
01SIM_REG01_REAL_0005 01MEU11_CS001_XQ01 UNIT SPEED FROM GOV
IN1 IN RE Value Input Unit: %
01SIM_REG01_II02 : 4545 10000
IN2 IMax Err 6553/32767 (0/220 %)
0
IMin
32767
OMax
6553
1 OMin
SEL
01SIM_REG01_BI01
G RE
01SIM_REG01_REAL_0006
IN1
01SIM_REG01_REAL_0019
IN2 4 19 40
MUL AO_SCALE SIM_ANA_M 01BBA00_CE001_XQ01
01BBA00_CE001_XQ01 UNIT ACTIVE POWER
IN1 IN RE Value Input Unit: MW
01SIM_REG01_II03 : 10000 01SIM_REG01_R11
IN2 IMax Err 6553/32767 (-30/120 MW)
01SIM_REG01_R10
IMin
32767
OMax
6553
OMin
5 20 41
MUL AO_SCALE SIM_ANA_M 01MEU11_CG012_XQ01
01SIM_REG01_REAL_0004 01MEU11_CG012_XQ01 WICKET GATE OPEN DEGREE FROM GOV
IN1 IN RE Value Input Unit: %
01SIM_REG01_II01 : 4000 10000
IN2 IMax Err 6553/32767 (0/100 %)
0
IMin
32767
OMax
6553
OMin
XX REG01 : Governor and MIV regulator - REV : 159 - 12/JAN/17 08:42 - POUName : L01_7SIM
.70/A
13 36
GE SIM_STATUS_SEL
01SIM_REG01_REAL_0004
IN1 RE Sel 01MEA41_CG002_XG01
0 01MEA41_CG002_XG01 WICKET GATE ABOVE NO_LOAD POSIT
2 IN2 Value0 Input Ini:
SEL 1
Value1 DETECTED
01MEU11_EM001_ZG01
G RE
01SIM_REG01_RI22
IN1
01SIM_REG01_RI21
IN2
37
SIM_STATUS_M
01MEU11_EM001_YL06 01MEU11_EU001_XG04
Value Input
38
SIM_STATUS_M
01MEU11_EM001_YL05 01MEU11_EU001_XG02
Value Input
XX REG01 : Governor and MIV regulator - REV : 159 - 12/JAN/17 08:42 - POUName : L01_7SIM
.71/A
29 51
AND SIM_EXCITATION
01BAC00_GS901_XG01 01MKC65_GS101_YL01 01MKC65_GS101_XG01
IN1 On ord Field CB
01BBA00_DE003_ZH07 01MKC65_GS101_YL02 01SIM_REG01_REAL_0012
IN2 Of f ord Uf
01MKC65_EM001_YL11 01SIM_REG01_REAL_0018
Inc ord If
01MKC65_EM001_YL12
Dec ord
01MKC65_EM001_YL32 01MKC65_DE001_XL21
21 Auto A mode FB
01CJA00_DE003_ZP01 01MKC65_EM001_YL31 01SIM_REG01_BOO_0014
DIV Manu M mode FB
UNIT VOLTAGE SP FEEDBACK 01CJA00_DE003_ZP01 01CJA00_DE002_ZG42 01SIM_REG01_BOO_0001
Unit: kV IN1 Volt mode V Mode FB
S:DE003 01SIM_REG01_RI10 : 1380.00000 01CJA00_DE002_ZG41 01MKC65_DE001_XG03
0/2000 (0/20 kV) IN2 R.P mode RP Mode FB
01SIM_REG01_BOO_0009 01SIM_REG01_BOO_0010
22 PF mode PF Mode FB
01CJA00_DE002_ZP01 01MKC65_EM001_YL01
DIV Ana valid
REACTIVE POWER SP FEEDBACK 01CJA00_DE002_ZP01
Unit: Mvar IN1 GCB clsd
S:DE002 01SIM_REG01_RI09 : 10000.00000 01MEU11_FS001_XH05
-12000/12000 (-120/120 Mvar) IN2 Speed>95%
01SIM_REG01_REAL_0013 01SIM_REG01_REAL_0021
Volt sp Volt
01SIM_REG01_REAL_0015 01SIM_REG01_REAL_0026
6 23 R.P sp Re.P
01SIM_REG01_REAL_0017 01SIM_REG01_REAL_0024
AO_SCALE DIV PF sp PF
01BBA00_CE001_XQ01
IN RE IN1 Act.p meas
32767 01SIM_REG01_RI09 : 10000.00000 01MKC65_DE001_XG04
IMax Err IN2 ISO NET ISOLATED
6553
IMin
12000 24
OMax Ele.Brake E.Brk FB
-3000
OMin IV Reg step
44
01MKC65_EM001_YL51
RS SEL
S Q1
01CJA00_EU001_ZG14
01BBA00_DE003_ZH07 G RE
R1 01SIM_REG01_RI03
/Q1 : 0.00500
IN1
01SIM_REG01_RI13 : 1.00000
IN2
7 25 45
MUL AO_SCALE SIM_ANA_M 01MKC65_CE001_XQ01
01SIM_REG01_REAL_0012 01MKC65_CE001_XQ01 EXCITATION FIELD VOLTAGE N=400V
IN1 IN RE Value Input Unit: V
01SIM_REG01_II01 : 4000 10000
IN2 IMax Err 6553/32767 (0/1000 V)
0
IMin
32767
OMax 46 53
6553
OMin GE SIM_STATUS_M
01MKC65_DE001_XM09
IN1 RE Value Input
01SIM_REG01_RI16
IN2
8 26 47
MUL AO_SCALE SIM_ANA_M 01MKC65_CE002_XQ01
01SIM_REG01_REAL_0018 01MKC65_CE002_XQ01 EXCITATION FIELD CURRENT N=1600A
IN1 IN RE Value Input Unit: A
01SIM_REG01_II05 : 1600.00000 01SIM_REG01_II15 : 3200.00000
IN2 IMax Err 6553/32767 (0/3200 A)
0
IMin
32767
OMax
6553
OMin
9 27 48
MUL AO_SCALE SIM_ANA_M 01BBA00_CE001_XQ02
01SIM_REG01_REAL_0021 01BBA00_CE001_XQ02 UNIT VOLTAGE PHASE AB
IN1 IN RE Value Input Unit: kV
01SIM_REG01_II04 : 1380 2000
IN2 IMax Err 6553/32767 (0/20 kV)
0
IMin
32767
OMax
6553
OMin
28 49
MUL SIM_REAL_M 01BBA00_FE001_RQ43
01SIM_REG01_REAL_0026 01SIM_REG01_REAL_0020 01BBA00_FE001_RQ43 UNIT REACTIVE POWER
IN1 VALUE INPUT Unit: Mvar
01SIM_REG01_RI31
IN2 -1.2e+8/1.2e+8 (-120/120 Mvar)
XX REG01 : Governor and MIV regulator - REV : 159 - 12/JAN/17 08:42 - POUName : L01_7SIM
.72/A
Dewater Simulation Program
30
SIM_DEWATER
01SIM_REG01_REAL_0004 01SIM_REG01_REAL_0033
OPENING WATER_LVL
01SIM_REG01_REAL_0019
POWER
01MEU11_EU001_TL04
CONDENSER
01SCC00_AA901_XG01 01SIM_REG01_BI01
MAIN_VLV FLAG_DW
01SCC00_AA902_XG01
AUX_VLV
0
RLS_VLV
01BAC00_GS901_XG01
GCB_CLS
REG_STEP
01SIM_REG01_RI11
10 33 50
MUL AO_SCALE SIM_ANA_M 01MEA41_CP505_XQ01
01SIM_REG01_REAL_0033 01MEA41_CP505_XQ01 DRAFT TUBE DEWATER LEVEL IN CONDENSOR -3.5/-5.0m
IN1 IN RE Value Input Unit: mm
1000 1000
IN2 IMax Err 6553/32767 (0/2000 mm)
0
IMin
32767
OMax
6553
OMin
34 43
GE SIM_STATUS_M 01MKC65_DE001_XL21
01SIM_REG01_REAL_0021 01MKC65_DE001_XL21 EXCIT AUTO CHANNEL IN OPERATION
IN1 RE Value Input Ini:
0.8
IN2 DETECTED
35
01SIM_REG01_II06 SIM_ANA_M
01SIM_REG01_II06 01MEA41_CP501_XQ01
Ini:20000 (262.99 m) Value Input
6553/32767 (224/300 m)
11 31
MUL SIM_REAL_M
01BBA00_FE001_1_ZQ01 01BBA00_FE001_RQ42
IN1 VALUE INPUT
10
IN2
12 32
MUL SIM_REAL_M
01BBA00_FE001_5_ZQ01 01BBA00_FE001_RQ03
IN1 VALUE INPUT
10
IN2
XX REG01 : Governor and MIV regulator - REV : 159 - 12/JAN/17 08:42 - POUName : L01_7SIM
.73/A
4.4 EU101 : MODBUS COMMUNICATION - REV : 60 - 14/JAN/17 09:31 - POUName : L01_6SIG
1
CUR_MODBUS_PRES
0
NET_NUM
1
EQPT_NUM 01CJA00_GK302_ZM11
01CJA00_GK302_ZM11 MFC3000-M vs GK302 MOD LINK
LINK1_PRES Ini:
01CJA00_GK302_ZM21
LINK2_PRES PRESENCE
01CJA00_GK302_ZM12
LINK1_EXCH
01CJA00_GK302_ZM22
LINK2_EXCH 01CJA00_GK302_ZM21
MFC3000-S vs GK302 MOD LINK
Ini:
PRESENCE
01CJA00_GK302_ZM12
MFC3000-M vs GK302 MOD EXCHANGE
Ini:
PRESENCE
01CJA00_GK302_ZM22
MFC3000-S vs GK302 MOD EXCHANGE
Ini:
PRESENCE
9
OR 01CJA00_GK302_ZM02
01CJA00_GK302_ZM12 01CJA00_GK302_ZM02 MFC3000 vs GK302 MOD EXCHANGE
IN1 Ini:
01CJA00_GK302_ZM22
IN2 PRESENCE
2
CUR_MODBUS_PRES
0
NET_NUM
6
EQPT_NUM 01CJA00_FT001_ZM11
01CJA00_FT001_ZM11 MFC3000-M vs FT001 MOD LINK
LINK1_PRES Ini:
01CJA00_FT001_ZM21
LINK2_PRES PRESENCE
01CJA00_FT001_ZM12
LINK1_EXCH
01CJA00_FT001_ZM22
LINK2_EXCH 01CJA00_FT001_ZM21
MFC3000-S vs FT001 MOD LINK
Ini:
PRESENCE
01CJA00_FT001_ZM12
MFC3000-M vs FT001 MOD EXCHANGE
Ini:
PRESENCE
01CJA00_FT001_ZM22
MFC3000-S vs FT001 MOD EXCHANGE
Ini:
PRESENCE
10
OR 01CJA00_FT001_ZM02
01CJA00_FT001_ZM12 01CJA00_FT001_ZM02 MFC3000 vs FT001 MOD EXCHANGE
IN1 Ini:
01CJA00_FT001_ZM22
IN2 PRESENCE
471/2 (+1p)
5
CUR_MODBUS_PRES
0
NET_NUM
2
EQPT_NUM 01CJA00_FE001_ZM11
01CJA00_FE001_ZM11 MFC3000-M vs FE001 MOD LINK
LINK1_PRES Ini:
01CJA00_FE001_ZM21
LINK2_PRES PRESENCE
01CJA00_FE001_ZM12
LINK1_EXCH
01CJA00_FE001_ZM22 01CJA00_FE001_ZM21
LINK2_EXCH
MFC3000-S vs FE001 MOD LINK
Ini:
PRESENCE
01CJA00_FE001_ZM12
MFC3000-M vs FE001 MOD EXCHANGE
Ini:
PRESENCE
01CJA00_FE001_ZM22
MFC3000-S vs FE001 MOD EXCHANGE
Ini:
PRESENCE
13
OR 01CJA00_FE001_ZM02
01CJA00_FE001_ZM12 01CJA00_FE001_ZM02 MFC3000 vs FE001 MOD EXCHANGE
IN1 Ini:0 (ABSENCE)
01CJA00_FE001_ZM22
IN2 PRESENCE
471/1(+1p)
01CJA00_FE002_ZM12
MFC3000-M vs FE002 MOD EXCHANGE
Ini:
PRESENCE
01CJA00_FE002_ZM22
MFC3000-S vs FE002 MOD EXCHANGE
Ini:
PRESENCE
14
OR 01CJA00_FE002_ZM02
01CJA00_FE002_ZM12 01CJA00_FE002_ZM02 MFC3000 vs FE002 MOD EXCHANGE
IN1 Ini:
01CJA00_FE002_ZM22
IN2 PRESENCE
7
CUR_MODBUS_PRES
0
NET_NUM
5
EQPT_NUM 01MKC65_EU002_ZM11
01MKC65_EU002_ZM11 MFC3000-M vs EXC_S MOD LINK
LINK1_PRES Ini:
01MKC65_EU002_ZM21
LINK2_PRES PRESENCE
01MKC65_EU002_ZM12
LINK1_EXCH
01MKC65_EU002_ZM22 01MKC65_EU002_ZM21
LINK2_EXCH
MFC3000-S vs EXC_S MOD LINK
Ini:
PRESENCE
01MKC65_EU002_ZM12
MFC3000-M vs EXC_S MOD EXCHANGE
Ini:
PRESENCE
01MKC65_EU002_ZM22
MFC3000-S vs EXC_S MOD EXCHANGE
Ini:
PRESENCE
15
OR 01MKC65_EU002_ZM02
01MKC65_EU002_ZM12 01MKC65_EU002_ZM02MFC3000 vs EXC_S MOD EXCHANGE
IN1 Ini:
01MKC65_EU002_ZM22
IN2 PRESENCE
8
CUR_MODBUS_PRES
0
NET_NUM
4
EQPT_NUM 01MKC65_EU001_ZM11
01MKC65_EU001_ZM11 MFC3000-M vs EXC_P MOD LINK
LINK1_PRES Ini:
01MKC65_EU001_ZM21
LINK2_PRES PRESENCE
01MKC65_EU001_ZM12
LINK1_EXCH
01MKC65_EU001_ZM22 01MKC65_EU001_ZM21
LINK2_EXCH
MFC3000-S vs EXC_P MOD LINK
Ini:
PRESENCE
01MKC65_EU001_ZM12
MFC3000-M vs EXC_P MOD EXCHANGE
Ini:
PRESENCE
01MKC65_EU001_ZM22
MFC3000-S vs EXC_P MOD EXCHANGE
Ini:
PRESENCE
16
OR 01MKC65_EU001_ZM02
01MKC65_EU001_ZM12 01MKC65_EU001_ZM02MFC3000 vs EXC_P MOD EXCHANGE
IN1 Ini:0 (ABSENCE)
01MKC65_EU001_ZM22
IN2 PRESENCE
01MEU11_EU001_ZM12
MFC3000-M vs GOV MOD EXCHANGE
Ini:
PRESENCE
01MEU11_EU001_ZM22
MFC3000-S vs GOV MOD EXCHANGE
Ini:
PRESENCE
12
OR 01MEU11_EU001_ZM01
01MEU11_EU001_ZM12 01MEU11_EU001_ZM01MFC3000 vs GOV MOD EXCHANGE
IN1 Ini:
01MEU11_EU001_ZM22
IN2 PRESENCE
4
CUR_MODBUS_PRES
0
NET_NUM
7
EQPT_NUM 01CMA00_EU001_ZM11
01CMA00_EU001_ZM11 MFC3000-M vs Unit Online MOD LINK
LINK1_PRES Ini:
01CMA00_EU001_ZM12
LINK2_PRES PRESENCE
01CMA00_EU001_ZM21
LINK1_EXCH
01CMA00_EU001_ZM22 01CMA00_EU001_ZM12
LINK2_EXCH
MFC3000-M vs Unit Online MOD EXCHANGE
Ini:
PRESENCE
01CMA00_EU001_ZM21
MFC3000-S vs Unit Online MOD LINK
Ini:
PRESENCE
01CMA00_EU001_ZM22
MFC3000-S vs Unit Online MOD EXCHANGE
Ini:
PRESENCE
11
OR 01CMA00_EU001_ZM01
01CMA00_EU001_ZM21 01CMA00_EU001_ZM01MFC3000 vs Unit Online MOD LINK
IN1 Ini:
01CMA00_EU001_ZM22
IN2 PRESENCE
01CJA00_EU001_ZK05
2
01MEA41_CF402_XM51 AND 01MEA41_AU001_ZM05
SHAFT SEAL INPUT WATER FLOW CF402S 01MEA41_CF402_XM51 01MEA41_AU001_ZM05 Turbine Auxilaries STARTING COND
Ini: IN1 Ini:0 (N-READY)
IO:L01_02 Rack:0 Slot:ST5 (X20DI9371) Point:11 01MEA41_CG201_XG01
NORMAL IN2 READY
01MEA41_CP402_XM51
IN3
01MEA41_CG201_XG01 01MEA41_GH001_XM51
GUIDE VAN PIN BROKE CONTACTOR CG201S-220S IN4
01MEA41_GH001_XM52
Ini: IN5
IO:L01_02 Rack:0 Slot:ST4 (X20DI9371) Point:2 01MEA41_GH001_XM01
TRIPPED IN6
01MEA41_XL202_XH04
01MEA41_CP402_XM51 IN7
01MEA41_CG605_XG02
SHAFT SEAL INPUT WATER PRESSURE CP402S IN8
Ini:
IO:L01_02 Rack:0 Slot:ST5 (X20DI9371) Point:10
NORMAL
01MEA41_GH001_XM51
UNIT INSTRUMENT CUBICLE 24VDC POWER MODULE 1
Ini:
IO:L01_02 Rack:0 Slot:ST4 (X20DI9371) Point:8
NORMAL
01MEA41_GH001_XM52
UNIT INSTRUMENT CUBICLE 24VDC POWER MODULE 2
Ini:
IO:L01_02 Rack:0 Slot:ST4 (X20DI9371) Point:9
NORMAL
01MEA41_GH001_XM01
INSTRUMENT RTD TMEPERATURE ALARM HIGH
Ini:
IO:L01_02 Rack:0 Slot:ST4 (X20DI9371) Point:6
DETECTED
01MEA41_XL202_XH04
HEAD COVER WATER LEVEL HIGH CL202S
Ini:
IO:L01_02 Rack:0 Slot:ST5 (X20DI9371) Point:6
DETECTED
01MEA41_CG605_XG02
REGULATING RING PIN CONTACTOR RELEASED
Ini:
IO:L01_02 Rack:0 Slot:ST4 (X20DI9371) Point:1
DETECTED
01MEA41_AU001_RI01
1
01CJA00_EU001_ZK02
3
TP
01MEA41_GH001_XM02
TON_R AND 01MEA41_AU001_ZM02
INSTRUMENT RTD TMEPERATURE ALARM TOO HIGH 01MEA41_GH001_XM02 01MEA41_GH001_ZM01 01MEA41_AU001_ZM02 Turbine Auxilaries MECHANICAL STOP COND
Ini: IN REB IN1 Ini:0 (N-DET)
IO:L01_02 Rack:0 Slot:ST4 (X20DI9371) Point:7 01MEA41_CL402_XH03
RET IN2 DETECTED
DETECTED
01MEA41_CL402_XH03
TURBINE GUIDE BRG OIL LEVEL VERY LOW CL402S
Ini:
IO:L01_02 Rack:0 Slot:ST5 (X20DI9371) Point:0
DETECTED
01CJA00_EU001_ZK05
9
01MKA54_AA001_XL21 AND 01MKA54_EU001_ZM05
GENERATOR EMERGENCY FIRE FIGHTING VALVE 1 01MKA54_AA001_XL21 01MKA54_EU001_ZM05 Generator Auxilaries STARTING COND
Ini: IN1 Ini:0 (N-READY)
IO:L01_02 Rack:0 Slot:ST8 (X20DI9371) Point:6 01MKA54_AA001_XM01
AUTO
IN2 READY
01MKA54_AA002_XL21
IN3
01MKA54_AA001_XM01 01MKA54_AA002_XM01
GENERATOR EMERGENCY FIRE FIGHTING VALVE 1 FAULT IN4
01MKA54_CL303_XH04
Ini: IN5
IO:L01_02 Rack:0 Slot:ST8 (X20DI9371) Point:8 01MKA54_CL305_XH07
DETECTED IN6
01MKA54_CL313_XH04
01MKA54_AA002_XL21
IN7
01MKA54_CL314_XM07
GENERATOR EMERGENCY FIRE FIGHTING VALVE 2 IN8
Ini: 01MKA54_CP901_XM01
IO:L01_02 Rack:0 Slot:ST8 (X20DI9371) Point:9 IN9
AUTO
01MKA54_AA002_XM01
GENERATOR EMERGENCY FIRE FIGHTING VALVE 2 FAULT
Ini:
IO:L01_02 Rack:0 Slot:ST8 (X20DI9371) Point:11
DETECTED
01MKA54_CL303_XH04
THRUST BEARING OIL LEVEL LOW
Ini:
IO:L01_02 Rack:0 Slot:ST7 (X20DI9371) Point:1
DETECTED
01MKA54_CL305_XH07
THRUST BEARING OIL LEVEL VERY HIGH
Ini:
IO:L01_02 Rack:0 Slot:ST7 (X20DI9371) Point:3
DETECTED
01MKA54_CL313_XH04
UPPER GUIDE BRG OIL LEVEL LOW
Ini:
IO:L01_02 Rack:0 Slot:ST7 (X20DI9371) Point:6
DETECTED
01MKA54_CL314_XM07
UPPER GUIDE BRG OIL LEVEL VERY HIGH
Ini:
IO:L01_02 Rack:0 Slot:ST7 (X20DI9371) Point:8
DETECTED
01MKA54_CP901_XM01
MECHANICAL BRAKING INLET SOURCE PRESSURE
Ini:
IO:L01_02 Rack:0 Slot:ST8 (X20DI9371) Point:1
NORMAL
01MKA54_AU001_TD01
1
01CJA00_EU001_ZK02
TP 10
01MKA54_CL302_XH03
TON_R AND 01MKA54_EU001_ZM02
THRUST BEARING OIL LEVEL VERY LOW 01MKA54_CL302_XH03 01MKA54_CL302_ZH13 01MKA54_EU001_ZM02 Generator Auxilaries MECHANICAL STOP COND
Ini: IN REB IN1 Ini:0 (N-DET)
IO:L01_02 Rack:0 Slot:ST7 (X20DI9371) Point:0 01MKA54_CL312_ZH13
RET IN2 DETECTED
DETECTED
01MKA54_AU001_TD02
2
TP
01MKA54_CL312_XH03
UPPER GUIDE BRG OIL LEVEL VERY LOW
TON_R
01MKA54_CL312_XH03 01MKA54_CL312_ZH13
Ini: IN REB
IO:L01_02 Rack:0 Slot:ST7 (X20DI9371) Point:5
DETECTED
RET
3
MOVE_B
01MKA54_CG565_XG01 01MKA54_CG565_ZG01
IN RE
4
MOVE_B
01MKA54_CG565_XG01 01MKA54_CG565_ZG02
IN RE
01MKA54_AU001_ZM00 01MKA54_AU001_ZM10
FLT_IN ALARM
01MKA54_AU001_ZM50
AV REM_ATH
0
MANU
01MKA54_AU001_ZT11 : 8000
TLTE_OP
01MKA54_AU001_ZT12 : 10000
TLTE_CL
01MKA54_AU001_ZT01 : 5000
OP_PL
01MKA54_AU001_ZT02 : 8000 01MKA54_AU001_ZU01
CL_PL SIG
01MKA54_AU001_ZT00 : 500 01MKA54_AU001_ZU01_V
F_TP SIG_V
Type
2 18
MOVE_B
01MKA54_AA001_ZA01 01MKA54_AA002_ZA01
IN RE
01MKA54_AU001_TD03 : 900.00000
15 21
12 14 IV TP
01CHA00_MT001_XM03 OR AND
GENERATOR FIRE COMMAND TO PROTECTION 01CHA00_MT001_XM03
RS 01MKA54_AA001_ZA01
TON_R
Ini: IN1 IN1 S Q1 IN REB
IO:L01_03 Rack:0 Slot:ST3 (X20DI9371) Point:11 01CHA00_EN001_XM26 01MKA54_AA001_ZA02
DETECTED IN2 IN2 R1 /Q1 RET
01CHA00_EN001_XM26
GENERATOR STATOR DIFFERENTIAL PROTECTION 87G TRIP
Ini:
IO:L01_03 Rack:0 Slot:ST4 (X20DI9371) Point:7
DETECTED 17
MOVE_B
13 01MKA54_AA001_ZA02 01MKA54_AA002_ZA02
01BAC00_GS901_XG02 AND IN RE
UNIT GCB GS901 IN OPEN POSTION 01BAC00_GS901_XG02
Ini: IN1
IO:L01_01 Rack:0 Slot:ST5 (X20DI9371) Point:2 01MKC65_GS101_XG02
DETECTED IN2
01MKC65_GS101_XG02
EXCIT FIELD BREAKER OPEN
Ini:
IO:L01_01 Rack:0 Slot:ST8 (X20DI9371) Point:5
DETECTED
19
FB_VA2 01MKA54_AA002_YL01
01MKA54_AA002_ZA01 01MKA54_AA002_YL01 GENERATOR EMERGENCY FIRE FIGHTING VALVE 2
OP_A OR1 Ini:
OP_M DS1 OPENING
01MKA54_AA002_ZC01
OP_A_ATH
01MKA54_AA002_XG01 01MKA54_AA002_ZJ01
OP_M_ATH
GENERATOR EMERGENCY FIRE FIGHTING VALVE 2 01MKA54_AA002_XG01 01MKA54_AA002_ZM11
Ini: OP_PS TLTE1
IO:L01_02 Rack:0 Slot:ST8 (X20DI9371) Point:10 01MKA54_AA002_XG01_V
OPEN OP_PS_V
01MKA54_AA002_YL02
01MKA54_AA002_ZA02 01MKA54_AA002_YL02 GENERATOR EMERGENCY FIRE FIGHTING VALVE 2
CL_A OR2 Ini:
CL_M DS2 CLOSING
01MKA54_AA002_ZC02
CL_A_ATH
01MKA54_AA002_ZJ02
CL_M_ATH
01MKA54_AA002_XG01 01MKA54_AA002_ZM12
CL_PS TLTE2
01MKA54_AA002_XG01_V
7 CL_PS_V
01MKA54_AA002_XM01 OR
GENERATOR EMERGENCY FIRE FIGHTING VALVE 2 FAULT 01MKA54_AA002_XM01 01MKA54_AA002_ZM00 01MKA54_AA002_ZM10
Ini: IN1 FLT_IN ALARM
IO:L01_02 Rack:0 Slot:ST8 (X20DI9371) Point:11 0 01MKA54_AA002_ZM50
DETECTED IN2 AV REM_ATH
0
8 MANU
01MKA54_AA002_XL21 AND
GENERATOR EMERGENCY FIRE FIGHTING VALVE 2 01MKA54_AA002_XL21 01MKA54_AA002_ZT11 : 1200
Ini: IN1 TLTE_OP
IO:L01_02 Rack:0 Slot:ST8 (X20DI9371) Point:9 1 01MKA54_AA002_ZT12 : 1200
AUTO IN2 TLTE_CL
01MKA54_AA002_ZT01 : 1000
OP_PL 01MKA54_AA002_ZU01
01MKA54_AA002_ZT02 : 1000 01MKA54_AA002_ZU01 GEN EMERG FIRE FIGHTING 2 ANIMATION WORD
CL_PL SIG Ini:
01MKA54_AA002_ZT00 : 500 01MKA54_AA002_ZU01_V
F_TP SIG_V 0/127
Type
01CJA00_EA007_ZS010
1 2
01CJA00_EU001_ZA01 AND AND 01CJA00_EA007_ZS015
ANY UNIT STOP CMD 01CJA00_EU001_ZA01 01CJA00_EA007_ZS015 SQ07:NMS->TS STEP1 COND
Ini:0 (N-REQ) IN1 IN1 Ini:
S:CON 01MEU11_FS001_XH02 1
REQ
IN2 IN2 CORRECT
01MEU11_FS001_ZM51
IN3
01MEU11_FS001_XH02 01CJA00_EU001_ZG13
RV02 <20% ES MECHANIC BRAKE VALID IN4
Ini:
IO:L01_01 Rack:0 Slot:ST10 (X20DI9371) Point:11
DETECTED
01MEU11_FS001_ZM51
GOVERNOR T-ADT MEASUREMENT
Ini:0 (FAULT)
S:EU001
NORMAL
01CJA00_EU001_ZG13
WICKET GATE or INTAKE GATE CLOSED
Ini:0 (N-DET)
S:CON
DETECTED
01CJA00_EA007_ZS020
3 4
01MEU11_FS001_XH14 AND AND 01CJA00_EA007_ZS025
RV14 SPEED=0 01MEU11_FS001_XH14 01CJA00_EA007_ZS025 SQ07:NMS->TS STEP2 COND
Ini: IN1 IN1 Ini:
IO:L01_01 Rack:0 Slot:ST11 (X20DI9371) Point:6 01CJA00_EU001_ZG13 1
IN2 IN2 CORRECT
DETECTED 01SCC00_EU001_ZG02
IN3
01CJA00_EU001_ZG13
WICKET GATE or INTAKE GATE CLOSED rewatered
Ini:0 (N-DET)
S:CON
DETECTED
01SCC00_EU001_ZG02
RUNNER REWATER STATE
Ini:
S:SFC...
DETECTED
01CJA00_EA007_ZS030
5 6
01MEU11_FS001_XH14 AND AND 01CJA00_EA007_ZS035
RV14 SPEED=0 01MEU11_FS001_XH14 01CJA00_EA007_ZS035 SQ07:NMS->TS STEP3 COND
Ini: IN1 IN1 Ini:
IO:L01_01 Rack:0 Slot:ST11 (X20DI9371) Point:6 01CJA00_EU001_ZG13 1
IN2 IN2 CORRECT
DETECTED
3
MOVE_B 01CJA00_EA007_ZS011
01CJA00_EA007_SFC_S1_X 01CJA00_EA007_ZS011 SQ07:NMS->TS STEP1
IN RE Ini:
IN-PROGR
4
MOVE_B 01CJA00_EA007_ZS021
01CJA00_EA007_SFC_S2_X 01CJA00_EA007_ZS021 SQ07:NMS->TS STEP2
IN RE Ini:
IN-PROGR
11
01CJA00_EA100_ZG21 AND 01CJA00_EA007_ZM01
UNIT LCU AUTO MODE 01CJA00_EA100_ZG21 01CJA00_EA007_ZM01
SQ07:NMS->TS SEQ OVERTIME
Ini: IN1 Ini:
S:CON PRESENCE
SELECTED
01CJA00_EA007_ZT01 : 12000 10 IN2
7 8
6 TP TP
AND TON_D TOF_R
5
01CJA00_EA100_ZG21
OR IN1 IN REB IN REB
1
01CJA00_EA007_ZG01 F_TRIG IN1 IN2 RET RET
SQ07:NMS->TS SEQ 01CJA00_EA007_ZG01
Ini: IN RE IN2
S:SFC...
IN-PROGR 9 10
OR SEL 01CJA00_EA007_ZQ01
2 01CJA00_EA007_ZQ01
01CJA00_EU001_ZG01 F_TRIG SQ07:NMS->TS SEQ TIME COUNT
IN1 G RE Ini:0 (0 NULL)
UNIT STILL STOP STATE 01CJA00_EU001_ZG01 01CJA00_EA007_ZQ01
Ini:0 (NO) IN RE IN2 IN1 0/360000 (0/3600 NULL)
S:SFC
YES
IN2
01CJA00_EU001_ZK05
1
01CVA00_EU001_XM01 AND 01CVA00_EU001_ZM05
STATOR WINDING TEMP GROUP ALARM 01CVA00_EU001_XM01 01CVA00_EU001_ZM05 TEMP MEASURE SYS MECHANICAL STARTING COND
Ini: IN1 Ini:
IO:L01_03 Rack:0 Slot:ST11 (X20DI9371) Point:0 01CVA00_EU001_XM03
ALARM
IN2 READY
01CVA00_EU001_XM05
IN3
01CVA00_EU001_XM03 01CVA00_EU001_XM07
STATOR CORE TEMP GROUP ALARM IN4
01CVA00_EU001_XM09
Ini: IN5
IO:L01_03 Rack:0 Slot:ST11 (X20DI9371) Point:2 01CVA00_EU001_XM11
ALARM IN6
01CVA00_EU002_XM01
01CVA00_EU001_XM05 IN7
01CVA00_EU002_XM02
TURBINE GUIDE BEARING TEMP GROUP ALARM IN8
Ini:
IO:L01_03 Rack:0 Slot:ST11 (X20DI9371) Point:4
ALARM
01CVA00_EU001_XM07
GEN THRUST BEARING TEMP GROUP ALARM
Ini:
IO:L01_03 Rack:0 Slot:ST11 (X20DI9371) Point:6
ALARM
01CVA00_EU001_XM09
GEN GUIDE BEARING TEMP GROUP ALARM
Ini:
IO:L01_03 Rack:0 Slot:ST11 (X20DI9371) Point:8
ALARM
01CVA00_EU001_XM11
GENERATOR AIR COOLER TEMP GROUP ALARM
Ini:
IO:L01_03 Rack:0 Slot:ST11 (X20DI9371) Point:10
ALARM
01CJA00_EU001_ZK02
2
01CVA00_EU001_XM02 AND 01CVA00_EU001_ZM02
STATOR WINDING TEMP GROUP TRIP 01CVA00_EU001_XM02 01CVA00_EU001_ZM02 TEMP MEASURE SYS MECHANICAL STOP COND
Ini: IN1 Ini:
IO:L01_03 Rack:0 Slot:ST11 (X20DI9371) Point:1 01CVA00_EU001_XM04
IN2 DETECTED
TRIPPED 01CVA00_EU001_XM06
IN3
01CVA00_EU001_XM04 01CVA00_EU001_XM08
STATOR CORE TEMP GROUP TRIP IN4
01CVA00_EU001_XM10
Ini: IN5
IO:L01_03 Rack:0 Slot:ST11 (X20DI9371) Point:3 01CVA00_EU001_XM12
TRIPPED IN6
01CVA00_EU001_XM06
TURBINE GUIDE BEARING TEMP GROUP TRIP
Ini:
IO:L01_03 Rack:0 Slot:ST11 (X20DI9371) Point:5
TRIPPED
01CVA00_EU001_XM08
GEN THRUST BEARING TEMP GROUP TRIP
Ini:
IO:L01_03 Rack:0 Slot:ST11 (X20DI9371) Point:7
TRIPPED
01CVA00_EU001_XM10
GEN GUIDE BEARING TEMP GROUP TRIP
Ini:
IO:L01_03 Rack:0 Slot:ST11 (X20DI9371) Point:9
TRIPPED
01CVA00_EU001_XM12
GENERATOR AIR COOLER TEMP GROUP TRIP
Ini:
IO:L01_03 Rack:0 Slot:ST11 (X20DI9371) Point:11
TRIPPED
1
01MKC65_GS101_ZA01 FB_CB 01MKC65_GS101_YL01
FIELD BRAKER GS101 AUTO CLOSG ORD 01MKC65_GS101_ZA01 01MKC65_GS101_YL01 EXCITATION BREAKER CLOSING ORDER
Ini:0 (N-CLSG) CL_A OR1 Ini:
S:SFC...
CLOSING
CL_M DS1 ON
01MKC65_GS101_ZC01
CL_A_ATH
01MKC65_GS101_ZJ01
01MKC65_GS101_XG01 CL_M_ATH
EXCIT FIELD BREAKER CLOSED 01MKC65_GS101_XG01 01MKC65_GS101_ZM11
Ini: CL_PS TLTE1
IO:L01_01 Rack:0 Slot:ST8 (X20DI9371) Point:4 01MKC65_GS101_XG01_V
DETECTED CL_PS_V
01MKC65_GS101_YL02
01MKC65_GS101_ZA02
01MKC65_GS101_ZA02 01MKC65_GS101_YL02 EXCITATION BREAKER OPENING ORDER
OP_A OR2 Ini:
FIELD BRAKER GS101 AUTO OPENG ORD
Ini:0 (N-OPNG) OP_M DS2 ON
S:SFC... 01MKC65_GS101_ZC02
OPENING
OP_A_ATH
01MKC65_GS101_ZJ02
OP_M_ATH
01MKC65_GS101_XG02 01MKC65_GS101_XG02 01MKC65_GS101_ZM12
EXCIT FIELD BREAKER OPEN OP_PS TLTE2
01MKC65_GS101_XG02_V
Ini: OP_PS_V
IO:L01_01 Rack:0 Slot:ST8 (X20DI9371) Point:5
DETECTED
01MKC65_GS101_ZM00 01MKC65_GS101_ZM10
FLT_IN ALARM
01MKC65_GS101_ZM50
AV REM_ATH
01MKC65_GS101_ZM09
EXTRD
0
MANU
01MKC65_GS101_ZT11 : 1000
TLTE
01MKC65_GS101_ZT01 : 500
CL_PL 01MKC65_GS101_ZU01
01MKC65_GS101_ZT02 : 500 01MKC65_GS101_ZU01 EXCITATION BREAKER GS101 ANIMATION WORD
OP_PL SIG Ini:
01MKC65_GS101_ZT00 : 1000 01MKC65_GS101_ZU01_V
F_TP SIG_V 0/127
Type
01MKC65_GS101_TP01 : 2
01CJA00_EU001_ZK04
40
01MKC65_DE001_XM01 AND 01MKC65_EU001_ZM04
UNDER EXCITATION LIMITER ACTIVE 01MKC65_DE001_XM01 01MKC65_EU001_ZM04 EXCITATION SYSTEM STARTING COND
Ini: IN1 Ini:0 (N-READY)
IO:L01_01 Rack:0 Slot:ST7 (X20DI9371) Point:0 01MKC65_DE001_XM02
DETECTED
IN2 READY
01MKC65_DE001_XM03
IN3
01MKC65_DE001_XM02 01MKC65_DE001_XM06
OVER EXCITATION LIMITER ACTIVE IN4
01MKC65_GH001_XL31
Ini: IN5
IO:L01_01 Rack:0 Slot:ST7 (X20DI9371) Point:1 01MKC65_DE001_XM51
DETECTED IN6
01MKC65_DE001_XM03
1ST STAGE EXCITATION FAULT
Ini:
IO:L01_01 Rack:0 Slot:ST7 (X20DI9371) Point:2
DETECTED
01MKC65_DE001_XM06
EXCITATION U/F LIMITATION
Ini:
IO:L01_01 Rack:0 Slot:ST8 (X20DI9371) Point:6
DETECTED
01MKC65_GH001_XL31
EXCITATION CONTROL LEVEL
Ini:
IO:L01_01 Rack:0 Slot:ST7 (X20DI9371) Point:8
REMOTE
01MKC65_DE001_XM51
EXCITATION READY FOR OPERATION
Ini:
IO:L01_01 Rack:0 Slot:ST7 (X20DI9371) Point:7
DETECTED
01CJA00_EU001_ZK03
42
01MKC65_DE001_XM05 AND 01MKC65_EU001_ZM03
EXCITATION FAILURE TRIP 01MKC65_DE001_XM05 01MKC65_EU001_ZM03 EXC SYSTEM ELECTRICAL STOP COND
Ini: IN1 Ini:0 (N-DET)
IO:L01_01 Rack:0 Slot:ST7 (X20DI9371) Point:4 01MKC65_DE001_XM04
IN2 DETECTED
DETECTED 01MKC65_DE001_XM07
IN3
01MKC65_DE001_XM04 01MKC65_CE002_ZH07
2nd STAGE EXCITATION FAULT IN4
Ini:
IO:L01_01 Rack:0 Slot:ST7 (X20DI9371) Point:3
DETECTED
01MKC65_DE001_XM07
EXCITATION FIELD FLASH FAILURE
Ini:
IO:L01_01 Rack:0 Slot:ST8 (X20DI9371) Point:7
DETECTED
01MKC65_CE002_ZH07
EXCITATION Backup OVERCURRENT TRIP
Ini:
S:EU001
DETECTED
28
TP
01MKC65_EU001_ZA04 01MKC65_EM001_YL51
Line Charge mode to exctation system TP_R
01MKC65_EU001_ZA04 01MKC65_EM001_YL51 LINE CHARGE ORDER TO EXCITATION
Ini: IN REB Ini:
S:SFC... ON
SELECTED RET
01MKC65_EU001_RI01 : 5.00000
46
45 TP
01MKC65_EU001_ZL21 AND 01MKC65_EM001_YL31
EXC MANU CHANNEL SEL CMD 01MKC65_EU001_ZL21
TP_R 01MKC65_EM001_YL31 EXCITATION MANUAL CHANNEL SELECT
Ini: IN1 IN REB Ini:
HMI DB Number:19 ON
SENT IN2 RET
01MKC65_EU001_ZK21
44
01MKC65_GH001_XL31 AND
EXCITATION CONTROL LEVEL 01MKC65_GH001_XL31
Ini: IN1
IO:L01_01 Rack:0 Slot:ST7 (X20DI9371) Point:8 01CJA00_GH001_XL32
REMOTE IN2
01CJA00_EA100_ZG22
IN3
01CJA00_GH001_XL32
01MKC65_DE001_XL21
IN4
LCU CONTROL LEVEL IN LOCAL
Ini:
IO:L01_01 Rack:0 Slot:ST4 (X20DI9371) Point:0
DETECTED
01CJA00_EA100_ZG22
UNIT STEP BY STEP MODE
Ini:
S:CON
SELECTED
01MKC65_EU001_RI01 : 5.00000
65
63 64 TP
01MKC65_EU001_ZL22 AND OR 01MKC65_EM001_YL32
EXC AUTO CHANNEL SEL CMD 01MKC65_EU001_ZL22
TP_R 01MKC65_EM001_YL32
EXCIT AUTOMATIC CHANNEL SELECT
Ini: IN1 IN1 IN REB Ini:
HMI DB Number:19 01MKC65_EU001_ZA22
IN2 IN2 RET ON
SENT
01MKC65_EU001_ZK22
62
AND
01MKC65_GH001_XL31
IN1
01CJA00_GH001_XL32
IN2
01MKC65_DE001_XL21 01CJA00_EA100_ZG22
IN3
EXCIT AUTO CHANNEL IN OPERATION 01MKC65_DE001_XL21
Ini: IN4
IO:L01_01 Rack:0 Slot:ST8 (X20DI9371) Point:0
DETECTED
01MKC65_EU001_ZA22
Exctation system Auto mode select
Ini:
S:SFC...
SELECTED
52
51 TP
01MKC65_EU001_ZL51 AND 01MKC65_EM001_YL61
EXC PSS Function Enable CMD TP_R
01MKC65_EU001_ZL51 01MKC65_EM001_YL61 POWER SYSTEM STABILIZER ON ORDER
Ini: IN1 IN REB Ini:
HMI DB Number:19 ON
SENT IN2 RET
01MKC65_EU001_ZK51
50
01MKC65_GH001_XL31 AND
EXCITATION CONTROL LEVEL 01MKC65_GH001_XL31 53
Ini: IN1
IO:L01_01 Rack:0 Slot:ST7 (X20DI9371) Point:8 01MKC65_DE001_XL21 IV
REMOTE IN2 RS 01MKC65_EU001_ZG51
01CJA00_EU001_ZG31 01MKC65_EU001_ZG51 EXC PSS Function Enabled
IN3 S Q1 Ini:0 (NO)
01MKC65_DE001_XL21 01MKC65_EU001_ZG51
EXCIT AUTO CHANNEL IN OPERATION IN4 R1 /Q1 YES
Ini:
IO:L01_01 Rack:0 Slot:ST8 (X20DI9371) Point:0
DETECTED
01CJA00_EU001_ZG31
UNIT GE STATE
Ini:0 (NO)
S:SFC
YES
01MKC65_EU001_RI01 : 5.00000
54
47 49 TP
OR AND TP_R 01MKC65_EM001_YL62
01MKC65_EU001_ZL52
01CJA00_EU001_ZG31 01MKC65_EM001_YL62 POWER SYSTEM STABILIZER OFF ORDER
IN1 IN1 IN REB Ini:
EXC PSS Function Disable CMD 01MKC65_EU001_ZL52
Ini: IN2 IN2 RET ON
HMI DB Number:19
SENT
01MKC65_EU001_ZK52
48
AND
01MKC65_GH001_XL31
IN1
01MKC65_EU001_ZG51
IN2
01CJA00_EU001_ZG14
UNIT IN SELF SYNCHRONIZE STARTING MODE
Ini:0 (N-DET)
S:GS901
DETECTED
29
01BAC00_GS901_XG01 OR
UNIT GCB GS901 IN CLOSED POSTION 01BAC00_GS901_XG01
Ini: IN1
IO:L01_01 Rack:0 Slot:ST5 (X20DI9371) Point:1 01CJA00_EU001_ZA01
DETECTED IN2
01CJA00_EU001_ZA01
ANY UNIT STOP CMD
Ini:0 (N-REQ)
S:CON
REQ
34
33 IV
AND RS 01BBA00_EM001_ZG72
01CJA00_EA027_ZG01 01BBA00_EM001_ZG72 UNIT GCB SELF SYNCHRONIZE TO EXC
IN1 S Q1 Ini:0 (N-DET)
01CJA00_EU001_ZG14
IN2 R1 /Q1 DETECTED
32 43
01MKC65_DE001_XM09 OR MOVE_B 01MKC65_EM001_YL72
IF>108A FOR GCB SELF SYNCHRONIZE CONTROL 01MKC65_DE001_XM09 01BBA00_EM001_ZG72 01MKC65_EM001_YL72
UNIT GCB SELF SYNCHRONIZE TO EXC
Ini: IN1 IN RE Ini:
IO:L01_01 Rack:0 Slot:ST8 (X20DI9371) Point:9 01CJA00_EU001_ZA01
IN2 ON
DETECTED 01CJA00_EU001_ZG14
IN3
01CJA00_EU001_ZA01
ANY UNIT STOP CMD
Ini:0 (N-REQ)
S:CON
REQ
2 13 36
SEL TWB TWB 71
01MKC65_EU001_ZM02 01MKC65_DE050_XD40 01MKC65_EG804_XD46
G RE IN RE1 IN RE1 TWB
01MKC65_ALM_WD11 01MKC65_DE050_XD41 01MKC65_DE160_XD40 01MKC65_EG013_XD46
IN1 RE2 RE2 IN RE1
01MKC65_ALM_WD01 01MKC65_CX020_XD40 01MKC65_DE160_XD41 01MKC65_EZ020_XD42
IN2 RE3 25 RE3 67 RE2
01MKC65_CX020_XD41 01MKC65_GX010_XG40 01MKC65_GS030_XG46
RE4 SEL RE4 SEL RE3
01MKC65_EZ010_XD46
01MKC65_EU001_ZM02 01MKC65_GX020_XG40 01MKC65_EU001_ZM02 01MKC65_DE090_XD47
RE5 G RE RE5 G RE RE4
01MKC65_EZ010_XD47
01MKC65_ALM_WD12 01MKC65_GX030_XG40 01MKC65_ALM_WD13 01MKC65_DE010_XD41
RE6 IN1 RE6 IN1 RE5
01MKC65_EZ010_XD43
01MKC65_ALM_WD02 01MKC65_GX040_XG40 01MKC65_ALM_WD03 01MKC65_CE220_XD40
RE7 IN2 RE7 IN2 RE6
01MKC65_EZ010_XD44 01MKC65_GX050_XG40 01MKC65_DE000_XD46
RE8 RE8 RE7
01MKC65_DE110_XD40 01MKC65_GX060_XG40 01MKC65_DE000_XD40
RE9 RE9 RE8
01MKC65_DE110_XD41 01MKC65_GX070_XG40 01MKC65_DU060_XF46
RE10 RE10 RE9
01MKC65_DE110_XD42 01MKC65_GX080_XG40 01MKC65_EA010_XD46
RE11 RE11 RE10
01MKC65_DE110_XD43 01MKC65_GX000_XD42 01MKC65_EZ020_XD47
RE12 RE12 RE11
01MKC65_EG809_XD46 01MKC65_GX000_XD46 01MKC65_GX000_XD57
RE13 RE13 RE12
01MKC65_EG810_XD46 01MKC65_GX000_XD47
RE14 RE14 RE13
01MKC65_EG811_XD46 01MKC65_EZ020_XD43 01MKC65_EG010_XG461
RE15 RE15 RE14
01MKC65_EG803_XD46 01MKC65_DU020_XU46
RE16 RE16 RE15
01MKC65_CX015_XD46
RE16
3 14 37 72
SEL TWB TWB TWB
01MKC65_EU001_ZM02 01MKC65_GW040_XG46 01MKC65_DU020_XD43 01MKC65_EG805_XU46
G RE IN RE1 IN RE1 IN RE1
01MKC65_ALM_WD14 01MKC65_DE010_XG42 01MKC65_DU020_XD41 01MKC65_EG010_XG46
IN1 RE2 RE2 RE2
01MKC65_ALM_WD04 01MKC65_DE010_XG43 01MKC65_DU020_XD42 01MKC65_DU040_XD40
IN2 RE3 26 RE3 68 RE3
01MKC65_GX000_XG40 01MKC65_DU020_XD44 01MKC65_DE010_XD42
RE4 SEL RE4 SEL RE4
01MKC65_GX000_XG41
01MKC65_EU001_ZM02 01MKC65_DU020_XD45 01MKC65_EU001_ZM02 01MKC65_GX000_XD51
RE5 G RE RE5 G RE RE5
01MKC65_GW030_XG41
01MKC65_ALM_WD15 01MKC65_CT061_XG46 01MKC65_ALM_WD16 01MKC65_GX000_XD52
RE6 IN1 RE6 IN1 RE6
01MKC65_GW030_XG42
01MKC65_ALM_WD05 01MKC65_CT063_XG46 01MKC65_ALM_WD06 01MKC65_GX000_XD53
RE7 IN2 RE7 IN2 RE7
01MKC65_GW030_XD43 01MKC65_EZ020_XD46 01MKC65_GX000_XD54
RE8 RE8 RE8
01MKC65_CE220_XD41 01MKC65_EG015_XG46 01MKC65_GX000_XD55
RE9 RE9 RE9
01MKC65_CE110_XD46 01MKC65_EZ020_XD40 01MKC65_GX000_XD56
RE10 RE10 RE10
01MKC65_EZ020_XD44 01MKC65_GW030_XG44 01MKC65_GX010_XG41
RE11 RE11 RE11
01MKC65_DT010_XD46 01MKC65_EG812_XD46 01MKC65_GX020_XG41
RE12 RE12 RE12
01MKC65_DU060_XD46 01MKC65_DE010_XG45 01MKC65_GX030_XG41
RE13 RE13 RE13
01MKC65_EG101_XD46 01MKC65_DE090_XB11 01MKC65_GX040_XG41
RE14 RE14 RE14
01MKC65_EG010_XD46 01MKC65_GX050_XG41
RE15 RE15 RE15
01MKC65_EZ020_XG47 01MKC65_EG013_XG41 01MKC65_GX060_XG41
RE16 RE16 RE16
01MKC65_CE002_ZQ01
EXCITATION FIELD CURRENT
Ini:0 (-999.92 A)
22.00000 6553/32767 (0/4000 A)
41
16 39 TP
01MKC65_CE002_XQ01 MOVE THR_HI 01MKC65_CE002_ZH07
EXCITATION FIELD CURRENT N=1600A 01MKC65_CE002_XQ01
TON_R 01MKC65_CE002_ZH07
EXCITATION Backup OVERCURRENT TRIP
Unit: A IN RE IN Hi IN REB Ini:
IO:L01_01 Rack:0 Slot:ST16 (X20AI4632) Point:3 01MKC65_CE002_ZH07_V
Val Err RET DETECTED
6553/32767 (0/3200 A)
Vus
01MKC65_CE002_ZW17
HIGH 1 THRESHOLD SP 01MKC65_CE002_ZW17
Ini:26213 (2999.92 A) Hi_Thr
01MKC65_CE002_ZW10
6553/32767 (0/4000 A) Hys
01MKC65_CE002_ZW10
HYS
Ini:100
-32768/32767
6 18 56 75
SEL SEL SEL SEL
01MKC65_EU001_ZM02 01MKC65_EU001_RQ08 01MKC65_EU001_ZM02 01MKC65_EU001_RQ09 01MKC65_EU001_ZM02 01MKC65_EU001_RQ10 01MKC65_EU001_ZM02 01MKC65_EU001_RQ11
G RE G RE G RE G RE
01MKC65_EU001_S08 01MKC65_EU001_S09 01MKC65_EU001_S10 01MKC65_EU001_S11
IN1 IN1 IN1 IN1
01MKC65_EU001_P08 01MKC65_EU001_P09 01MKC65_EU001_P10 01MKC65_EU001_P11
IN2 IN2 IN2 IN2
7 19 57 76
SEL SEL SEL SEL
01MKC65_EU001_ZM02 01MKC65_EU001_RQ12 01MKC65_EU001_ZM02 01MKC65_EU001_RQ13 01MKC65_EU001_ZM02 01MKC65_EU001_RQ14 01MKC65_EU001_ZM02 01MKC65_EU001_RQ15
G RE G RE G RE G RE
01MKC65_EU001_S12 01MKC65_EU001_S13 01MKC65_EU001_S14 01MKC65_EU001_S15
IN1 IN1 IN1 IN1
01MKC65_EU001_P12 01MKC65_EU001_P13 01MKC65_EU001_P14 01MKC65_EU001_P15
IN2 IN2 IN2 IN2
8 20 58 77
SEL SEL SEL SEL
01MKC65_EU001_ZM02 01MKC65_EU001_RQ16 01MKC65_EU001_ZM02 01MKC65_EU001_RQ17 01MKC65_EU001_ZM02 01MKC65_EU001_RQ18 01MKC65_EU001_ZM02 01MKC65_EU001_RQ19
G RE G RE G RE G RE
01MKC65_EU001_S16 01MKC65_EU001_S17 01MKC65_EU001_S18 01MKC65_EU001_S19
IN1 IN1 IN1 IN1
01MKC65_EU001_P16 01MKC65_EU001_P17 01MKC65_EU001_P18 01MKC65_EU001_P19
IN2 IN2 IN2 IN2
9 21 59 78
SEL SEL SEL SEL
01MKC65_EU001_ZM02 01MKC65_EU001_RQ20 01MKC65_EU001_ZM02 01MKC65_EU001_RQ21 01MKC65_EU001_ZM02 01MKC65_EU001_RQ22 01MKC65_EU001_ZM02 01MKC65_EU001_RQ23
G RE G RE G RE G RE
01MKC65_EU001_S20 01MKC65_EU001_S21 01MKC65_EU001_S22 01MKC65_EU001_S23
IN1 IN1 IN1 IN1
01MKC65_EU001_P20 01MKC65_EU001_P21 01MKC65_EU001_P22 01MKC65_EU001_P23
IN2 IN2 IN2 IN2
10 22 60 79
SEL SEL SEL SEL
01MKC65_EU001_ZM02 01MKC65_EU001_RQ24 01MKC65_EU001_ZM02 01MKC65_EU001_RQ25 01MKC65_EU001_ZM02 01MKC65_EU001_RQ26 01MKC65_EU001_ZM02 01MKC65_EU001_RQ27
G RE G RE G RE G RE
01MKC65_EU001_S24 01MKC65_EU001_S25 01MKC65_EU001_S26 01MKC65_EU001_S27
IN1 IN1 IN1 IN1
01MKC65_EU001_P24 01MKC65_EU001_P25 01MKC65_EU001_P26 01MKC65_EU001_P27
IN2 IN2 IN2 IN2
11 23 61 80
SEL SEL SEL SEL
01MKC65_EU001_ZM02 01MKC65_EU001_RQ28 01MKC65_EU001_ZM02 01MKC65_EU001_RQ29 01MKC65_EU001_ZM02 01MKC65_EU001_RQ30 01MKC65_EU001_ZM02 01MKC65_EU001_RQ31
G RE G RE G RE G RE
01MKC65_EU001_S28 01MKC65_EU001_S29 01MKC65_EU001_S30 01MKC65_EU001_S31
IN1 IN1 IN1 IN1
01MKC65_EU001_P28 01MKC65_EU001_P29 01MKC65_EU001_P30 01MKC65_EU001_P31
IN2 IN2 IN2 IN2
15
01MEU11_EN001_XG01 OR 01MEU11_EN012_ZG01
R80N MAIN T-SLG OPERATION 01MEU11_EN001_XG01 01MEU11_EN012_ZG01 MAIN or STANDBY T-SLG IN OPERATION
Ini: IN1 Ini:
IO:L01_01 Rack:0 Slot:ST9 (X20DI9371) Point:6 01MEU11_EN002_XG01
RUNNING
IN2 RUNNING
01MEU11_EN002_XG01
R80S STANDBY T-SLG OPERATION
Ini:
IO:L01_01 Rack:0 Slot:ST9 (X20DI9371) Point:7
RUNNING
16
01MEU11_FS001_XM51 AND 01MEU11_FS001_ZM51
RD29 TADT MAJOR 01MEU11_FS001_XM51 01MEU11_FS001_ZM51 GOVERNOR T-ADT MEASUREMENT
Ini: IN1 Ini:0 (FAULT)
IO:L01_01 Rack:0 Slot:ST10 (X20DI9371) Point:6
NORMAL
IN2 NORMAL
1
FB_UV_BV
01MEU11_FS001_XM51_V
USINT VALID
FORC_V
01CJA00_EU001_ZK05
30
01MEU11_EU001_XL21 AND 01MEU11_EU001_ZM05
GOVERNOR SYSTEM REMOTE AUTO MODE 01MEU11_EU001_XL21 01MEU11_EU001_ZM05 GOVERNOR SYSTEM STARTING COND
Ini: IN1 Ini:0 (N-READY)
IO:L01_01 Rack:0 Slot:ST9 (X20DI9371) Point:1 01MEU11_GW002_XM51
DETECTED
IN2 READY
01MEU11_EN012_ZG01
IN3
01MEU11_GW002_XM51 01MEU11_EN001_XM01
GOV CONTROL POWER 24VDC CIRCUIT 2 IN4
01MEU11_EN001_XM51
Ini: IN5
IO:L01_01 Rack:0 Slot:ST9 (X20DI9371) Point:4 01MEU11_EN002_XM01
NORMAL IN6
01MEU11_EN002_XM51
01MEU11_EN012_ZG01
IN7
01MEU11_FS001_XH08
MAIN or STANDBY T-SLG IN OPERATION IN8
Ini: 01MEU11_FS001_XM01
S:EU001 IN9
RUNNING
01MEU11_FS001_ZM51
I10
01MEU11_GW001_XM51
01MEU11_EN001_XM01 I11
R129N MAIN T-SLG UPC MINOR FAULT 01MEA41_CG201_XG01
Ini:
I12
IO:L01_01 Rack:0 Slot:ST10 (X20DI9371) Point:1
DETECTED
01MEU11_EN001_XM51
R29N MAIN T-SLG UPC MAJOR FAULT
Ini:
IO:L01_01 Rack:0 Slot:ST10 (X20DI9371) Point:0 01CJA00_EU001_ZK02
N-DET 31
AND 01MEU11_EU001_ZM02
01MEU11_EN002_XM01 01CJA00_EE101_ZM01 01MEU11_EU001_ZM02 GOV SYSTEM MECHANICAL STOP COND
R129S STANDBY T-SLG UPC MINOR FAULT IN1 Ini:0 (N-DET)
Ini:
0
IN2 DETECTED
IO:L01_01 Rack:0 Slot:ST10 (X20DI9371) Point:3
DETECTED
01MEU11_EN002_XM51
R29S STANDBY T-SLG UPC MAJOR FAULT
Ini:
IO:L01_01 Rack:0 Slot:ST10 (X20DI9371) Point:2
N-DET
01MEU11_FS001_XH08
RV08 107% PROTECTION INTERLOCK LEVEL 1
Ini:
IO:L01_01 Rack:0 Slot:ST11 (X20DI9371) Point:3
DETECTED
01MEU11_FS001_XM01
RD129 TADT-MAIN MINOR
Ini:
IO:L01_01 Rack:0 Slot:ST10 (X20DI9371) Point:7
FAULT
01MEU11_FS001_ZM51
GOVERNOR T-ADT MEASUREMENT
Ini:0 (FAULT)
S:EU001
NORMAL
01MEU11_GW001_XM51
GOV CONTROL POWER 24VDC CIRCUIT 1
Ini:
IO:L01_01 Rack:0 Slot:ST9 (X20DI9371) Point:3
NORMAL
XX EU001 : Speed Governor System - REV : 103 - 14/JAN/17 09:20 - POUName : L01_5ACT
.93/A
35 36
01CJA00_EU001_ZG11 OR AND 01MEU11_FS001_ZM02
UNIT TS STATE 01CJA00_EU001_ZG11 01MEU11_FS001_ZM02
GOV T-ADT SPPED MEASUREMENT FAULT when SPEEDUP
Ini:0 (NO) IN1 IN1 Ini:
S:SFC... 01CJA00_EA051_ZG01
IN2 IN2 DETECTED
YES 01CJA00_EA061_ZG01
IN3
01CJA00_EA051_ZG01
SQ51: TS->BS SEQ IN4
Ini:
S:SFC...
IN-PROGR
01CJA00_EA061_ZG01
SQ61: TS->CH SEQ
Ini:0 (N-PROGR)
S:SFC...
IN-PROGR
33 34
01CJA00_EU001_ZJ11 OR AND
UNIT TS STATE 01CJA00_EU001_ZJ11
Ini: IN1 IN1
S:CON 01CJA00_EU001_ZJ21
REQ IN2 IN2
01CJA00_EU001_ZJ31
IN3
01CJA00_EU001_ZJ21 01CJA00_EU001_ZJ41
UNIT SR STATE IN4
Ini: 01CJA00_EU001_ZJ71
IN5
S:CON
REQ
01CJA00_EU001_ZJ31
UNIT GE STATE
Ini:
S:CON
REQ
01CJA00_EU001_ZJ41
UNIT GC STATE
Ini:
S:CON
REQ
01BAC00_GS901_XG01
UNIT GCB GS901 IN CLOSED POSTION
Ini: 01CJA00_DE003_TD02 : 2.00000
IO:L01_01 Rack:0 Slot:ST5 (X20DI9371) Point:1
DETECTED 32
TP
01MEU11_FS001_ZM51
GOVERNOR T-ADT MEASUREMENT 01MEU11_FS001_ZM51
TON_R
Ini:0 (FAULT) IN REB
S:EU001
NORMAL RET
24
23 IV
01CJA00_EA021_ZG01 AND 01MEU11_EU001_ZG22
SQ21:TS->SR SEQ 01CJA00_EA021_ZG01
RS 01MEU11_EU001_ZG22 GOV ISOLATED MODE R6 FOR SELF SYNCHRONIZE
Ini:0 (N-PROGR) IN1 S Q1 Ini:0 (N-SEL)
S:SFC... 01CJA00_EU001_ZG14
IN2 R1 /Q1 SELECTED
IN-PROGR 01MEU11_EU001_ZA09
IN3
01CJA00_EU001_ZG14
UNIT IN SELF SYNCHRONIZE STARTING MODE
Ini:0 (N-DET) 47
S:GS901 MOVE_B
DETECTED 01MEU11_EM001_YL09
01MEU11_EU001_ZG22 01MEU11_EM001_YL09
GOV ISOLATED MODE R6 FOR SELF SYNCHRONIZE
22 IN RE Ini:
OR ON
01CJA00_EU001_ZA01 01CJA00_EU001_ZG14
IN1
ANY UNIT STOP CMD 01CJA00_EU001_ZA01
Ini:0 (N-REQ) IN2
S:CON
REQ
XX EU001 : Speed Governor System - REV : 103 - 14/JAN/17 09:20 - POUName : L01_5ACT
.94/A
01CJA00_EU001_ZK03
37
01MEU11_EU001_XM01 AND 01MEU11_EU001_ZM03
GOV DUAL T-SLG TRIP RELAY 01MEU11_EU001_XM01 01MEU11_EU001_ZM03 GOV SYSTEM ELECTRICAL STOP COND
Ini: IN1 Ini:0 (N-DET)
IO:L01_01 Rack:0 Slot:ST9 (X20DI9371) Point:0 01MEU11_FS001_XH10
IN2 DETECTED
ACT 01MEU11_FS001_ZM02
IN3
01MEU11_FS001_XH10 01CJA00_EN000_ZM51
RV10 150% PROTECTION INTERLOCK LEVEL 3 IN4
Ini: 01MEU11_CG001_ZG01
IN5 52
IO:L01_01 Rack:0 Slot:ST11 (X20DI9371) Point:5 01MEU11_FS001_ZH19
DETECTED IN6 MOVE_B 01MAU24_AA004_YL01
01MEU11_CG012_ZM01 01MEU11_EU001_ZM03 01MAU24_AA004_YL01
EMERGENCY SLIDE DISTRIBUTION VALVE (MSV)
IN7 IN RE Ini:
01MEU11_FS001_ZM02 CLOSED
GOV T-ADT SPPED MEASUREMENT FAULT when SPEEDUP
Ini:
S:EU001
DETECTED
01CJA00_EN000_ZM51
L01 UNIT01 LCU WATCHDOG
Ini:1 (NORMAL)
S:EB000
01CJA00_EU001_ZK14
NORMAL 49
AND
2 01MEU11_EU001_XM01 01MEU11_EU001_BOO_0004
01MEA41_CG201_XG01 AND IN1
GUIDE VAN PIN BROKE CONTACTOR CG201S-220S 01MEA41_CG201_XG01 01MEU11_CG001_ZG01 01MEU11_FS001_XH10
Ini: IN1 IN2
01CJA00_EU001_ZA01 01MEU11_FS001_ZM02
IO:L01_02 Rack:0 Slot:ST4 (X20DI9371) Point:2 IN3
TRIPPED IN2 01CJA00_EN000_ZM51
IN4
01MEU11_CG001_ZG01
01CJA00_EU001_ZA01 IN5
ANY UNIT STOP CMD 01MEU11_FS001_ZH19
Ini:0 (N-REQ) 01MEU11_EU001_T02 : 1.00000 IN6
01MEU11_CG012_ZM01
S:CON IN7
REQ 5
4 TP
01MEU11_FS001_XH09 AND
RV09 115% PROTECTION INTERLOCK LEVEL 2 01MEU11_FS001_XH09
TON_R 01MEU11_FS001_ZH19
Ini: IN1 IN REB
IO:L01_01 Rack:0 Slot:ST11 (X20DI9371) Point:4 01MEA41_CG002_XG01
DETECTED IN2 RET
01MEA41_CG002_XG01
WICKET GATE ABOVE NO_LOAD POSIT
Ini: 01CJA00_DE003_TD01 : 20.00000
IO:L01_02 Rack:0 Slot:ST6 (X20DI9371) Point:8
DETECTED 10
9 TP 26
01CJA00_EU001_ZA01 AND AND
ANY UNIT STOP CMD 01CJA00_EU001_ZA01
TON_R 01MEU11_CG012_ZM01
Ini:0 (N-REQ) IN1 IN REB IN1
S:CON 01MEU11_EM001_ZG01 01MEU11_CG012_ZH04
REQ IN2 RET IN2
01MEU11_EM001_ZG01
GOVERNOR SYSTEM ON Memory
Ini:
S:EU001
YES
01MEU11_CG012_ZH04
WICKET GATE OPEN DEGREE < 10%
Ini:
S:EU001
LOW
XX EU001 : Speed Governor System - REV : 103 - 14/JAN/17 09:20 - POUName : L01_5ACT
.95/A
01MEU11_EU001_R01 : 10.00000
7
TP
01MEU11_EU001_ZA01 01MEU11_EM001_YL01
Start speed governor TP_R
01MEU11_EU001_ZA01 01MEU11_EM001_YL01 GOVERNOR START R0
Ini: IN REB Ini:
S:SFC... ON
REQ RET
8
IV
RS 01MEU11_EM001_ZG01
GOVERNOR SYSTEM ON Memory
S Q1 Ini:
01MEU11_EU001_R01 : 10.00000 R1 /Q1 YES
6
TP
01MEU11_EU001_ZA02 01MEU11_EM001_YL02
Stop speed governor 01MEU11_EU001_ZA02
TP_R 01MEU11_EM001_YL02 GOVERNOR STOP R0-0
Ini: IN REB Ini:
S:SFC... ON
REQ RET
01MEU11_EU001_R01 : 10.00000
19
TP
01MEU11_EU001_ZA11 01MEU11_EM001_YL03
Set GOV Condensor mode R70 01MEU11_EU001_ZA11
TP_R 01MEU11_EM001_YL03 GOV UNIT SYN CONDENCER R70 SET
Ini: IN REB Ini:
S:SFC ON
REQ RET 40
IV 51
RS MOVE_B 01MEU11_EU001_TL04
01MEU11_EU001_TL04
R70 Synchronous condenser
S Q1 IN RE Ini:
01MEU11_EU001_R01 : 10.00000 R1 /Q1 ON
21
20 TP
01MEU11_EU001_ZA12 OR 01MEU11_EM001_YL13
Reset GOV Condensor mode R70 01MEU11_EU001_ZA12
TP_R 01MEU11_EM001_YL13 GOV UNIT SYN CONDENCER R70 RESET
Ini: IN1 IN REB Ini:
S:SFC... 01CJA00_EU001_ZG11
IN2 RET ON
REQ
01CJA00_EU001_ZG11
UNIT TS STATE
Ini:0 (NO)
S:SFC...
YES
41
MOVE_B 01MEU11_EU001_TL05
01MEU11_EU001_TL05 R128-ON Isolated network
01MEU11_EU001_R01 : 10.00000 IN RE Ini:
ON
17
TP
01MEU11_EU001_ZA21 01MEU11_EM001_YL07
Set GOV Insolated Network mode R128 01MEU11_EU001_ZA21
TP_R 01MEU11_EM001_YL07 GOV ISOLATED GRID OPERATION R128 SET
Ini: IN REB Ini:
S:SFC... ON
REQ RET
38
IV
RS 01MEU11_EU001_ZG21
01MEU11_EU001_ZG21 GOV Insolated Network R128
01MEU11_EU001_R01 : 10.00000 S Q1 Ini:0 (N-SEL)
R1 /Q1 SELECTED
18
TP
01MEU11_EU001_ZA22 01MEU11_EM001_YL08
Reset GOV Insolated Network mode R128 TP_R
01MEU11_EU001_ZA22 01MEU11_EM001_YL08 GOV ISOLATED GRID OPERATION R128 RESET
Ini: IN REB Ini:
S:SFC... OFF
REQ RET
39
MOVE_B 01MEU11_EU001_TL06
01MEU11_EU001_TL06 R128-OFF Isolated network
IN RE Ini:
ON
XX EU001 : Speed Governor System - REV : 103 - 14/JAN/17 09:20 - POUName : L01_5ACT
.96/A
46
45 IV
01MEU11_EU001_ZL01 AND 01MEU11_EU001_ZG41
GOV Frequency Insensitive mode Set 01MEU11_EU001_ZL01
RS 01MEU11_EU001_ZG41 GOV Frequency Insensitive mode
Ini: IN1 S Q1 Ini:0 (N-SEL)
HMI DB Number:19 SELECTED
SENT IN2 R1 /Q1
01MEU11_EU001_ZK01
44
01CJA00_GH001_XL33 AND
LCU OPERATION LOCKED 01CJA00_GH001_XL33
Ini: IN1
IO:L01_01 Rack:0 Slot:ST4 (X20DI9371) Point:2 01CJA00_EU001_ZM06
DETECTED IN2
01BAC00_GS901_XG01
IN3
01CJA00_EU001_ZM06 01MEU11_EU001_XL21
IN4
UNIT PERMANENT START CONDITION 01MEU11_EU001_XG01
Ini: IN5
S:CON
ESTABL 53
MOVE_B 01MEU11_EM001_YL04
01BAC00_GS901_XG01 FREQ INSENSITIVITY CHANGEOVER R4
UNIT GCB GS901 IN CLOSED POSTION IN RE Ini:
Ini: ON
IO:L01_01 Rack:0 Slot:ST5 (X20DI9371) Point:1
DETECTED
43 54
01MEU11_EU001_ZL02 AND MOVE_B 01MEU11_EU001_TL02
GOV Frequency Insensitive mode Reset 01MEU11_EU001_ZL02 R4 Insensitivity on speed
Ini: IN1 IN RE Ini:
HMI DB Number:19 ON
SENT 01MEU11_EU001_ZK02
42 IN2
AND
01MEU11_EU001_XG01 01CJA00_GH001_XL33
IN1
R304 1ST STAGE FREQUENCY INSENTIVITY ACTIVE 01MEU11_EU001_XG01
Ini: IN2
IO:L01_01 Rack:0 Slot:ST9 (X20DI9371) Point:9
DETECTED
11
01MEU11_CG012_XQ01 AI_SCALE 01CJA00_DG001_ZQ01
WICKET GATE OPEN DEGREE FROM GOV 01MEU11_CG012_XQ01 01CJA00_DG001_ZQ01 WG OPENING MEAS VALUE
Unit: % IN RI Ini:0 (0 %)
IO:L01_01 Rack:0 Slot:ST17 (X20AI4632) Point:1 0/10000 (0/100 %)
6553/32767 (0/100 %) _V(boo) RR
01MEU11_CG012_XQ01_V
_V(us) Err
01MEU11_EU001_3_ZW09 : 32767
IMax
01MEU11_EU001_3_ZW01 : 6553
IMin
01MEU11_EU001_3_ZW19 : 10000
OMax 25
01MEU11_EU001_3_ZW11 : 0
OMin THR_HL
01CJA00_DG001_ZQ01 01MEU11_CG012_ZH07_V
IN Hi2_V
01MEU11_CG012_ZH06_V
Val Hi1_V
01MEU11_CG012_ZH04_V
Vus Lo1_V
01MEU11_CG012_ZW10 01MEU11_CG012_ZH03_V
Hys Lo2_V 01MEU11_CG012_ZH04
WICKET GATE OPEN DEGREE < 10%
01MEU11_CG012_ZW17 01MEU11_CG012_ZH07 Ini:
H2_Thr Hi2 LOW
01MEU11_CG012_ZW16 01MEU11_CG012_ZH06
H1_Thr Hi1
01MEU11_CG012_ZW14 01MEU11_CG012_ZH04
L1_Thr Lo1 01MEU11_CG012_ZH03
01MEU11_CG012_ZW13 01MEU11_CG012_ZH03 WICKET GATE OPEN DEGREE < 2%
L2_Thr Lo2 Ini:0 (N-DET)
DETECTED
XX EU001 : Speed Governor System - REV : 103 - 14/JAN/17 09:20 - POUName : L01_5ACT
.97/A
01MEU11_EU001_ZQ01
Unit water head
Ini:0 (-17.5 m)
6553/32767 (0/70 m)
27 50
SEL MOVE 01MEU11_FE001_YQ02
01MEA41_CP109_XQ01 01MEU11_EU001_S8000 01MEU11_EU001_ZQ01 01MEU11_FE001_YQ02 WATER HEAD TO GOV
G RE IN RE Unit: m
DIFFERENTIAL PRESURE WATER HEAD CP109T 01MEA41_CP109_XQ01
Unit: m IN1 6553/32767 (0/70 m)
IO:L01_01 Rack:0 Slot:ST19 (X20AI4632) Point:3
6553/32767 (0/70 m) IN2
12
20CBA00_CL012_ZQ01 AI_SCALE
WATER HEAD FROM UP/DOWN STREAM DIFF 20CBA00_CL012_ZQ01
Unit: m IN RI
S:WH001
0/700 (0/70 m) _V(boo) RR
_V(us) Err
01MEU11_EU001_2_ZW19 : 700
IMax
01MEU11_EU001_2_ZW11 : 0
IMin
01MEU11_EU001_2_ZW09 : 32767
OMax
01MEU11_EU001_2_ZW01 : 6553
OMin
01CJA00_EU001_ZK13
29 48
01MEU11_FS001_XH10 AND MOVE_B 01CJA00_EU001_YL03
RV10 150% PROTECTION INTERLOCK LEVEL 3 01MEU11_FS001_XH10 01CJA00_EU001_ZM13 01CJA00_EU001_YL03
EMERGENCY STOP LEVEL 3
Ini: IN1 IN RE Ini:
IO:L01_01 Rack:0 Slot:ST11 (X20DI9371) Point:5 01MEU11_CG001_ZG01
IN2 ON
DETECTED 01MEU11_FS001_ZH09
IN3
01MEU11_CG001_ZG01
01MEU11_CG012_ZM02
IN4 01CJA00_EU001_ZM13
SHEAR PIN BROKE DURING UNIT STOP UNIT EMERGENCY STOP LEVEL 3
Ini: 01MEU11_EU001_T01 : 30.00000 Ini:0 (N-DET)
S:EU001 DETECTED
DETECTED 3
TP
01MEU11_FS001_XH09 01CJA00_EU001_ZK03
RV09 115% PROTECTION INTERLOCK LEVEL 2 TON_R 55
01MEU11_FS001_XH09 01MEU11_FS001_ZH09
Ini: IN REB AND
IO:L01_01 Rack:0 Slot:ST11 (X20DI9371) Point:4 01MEU11_FS001_XH10 01MEU11_EU001_BOO_0009
DETECTED RET IN1
01MEU11_CG001_ZG01
IN2
01MEU11_FS001_ZH09
01CJA00_DE003_TD11 : 40.00000 IN3
01MEU11_CG012_ZM02
14 IN4
13 TP 28
01CJA00_EU001_ZA01 AND AND
ANY UNIT STOP CMD 01CJA00_EU001_ZA01
TON_R 01MEU11_CG012_ZM02
Ini:0 (N-REQ) IN1 IN REB IN1
S:CON 01MEU11_EM001_ZG01 01MEU11_CG012_ZH03
REQ IN2 RET IN2
01MEU11_EM001_ZG01
GOVERNOR SYSTEM ON Memory
Ini:
S:EU001
YES 56
MOVE_B
01MEU11_CG012_ZH03
0 01MEU11_EU001_TL10
IN RE
WICKET GATE OPEN DEGREE < 2%
Ini:0 (N-DET) 57
S:EU001 MOVE
DETECTED 100 01MEU11_EU001_TQ03
IN RE
58
MOVE
0 01MEU11_EU001_TQ04
IN RE
59
MOVE_B
0 01MEU11_EU001_TL07
IN RE
XX EU001 : Speed Governor System - REV : 103 - 14/JAN/17 09:20 - POUName : L01_5ACT
.98/A
4.13 EU014 : Governor Oil Station - REV : 114 - 14/JAN/17 09:18 - POUName : L01_5ACT
01CJA00_EU001_ZK05
19
01MAU24_AP001_XM51 AND 01MAU24_EU014_ZM05
GOVERNOR PUMP AP001 MOTOR 01MAU24_AP001_XM51 01MAU24_EU014_ZM05 GOV OIL STATION STARTING COND
Ini: IN1 Ini:0 (N-READY)
IO:L01_01 Rack:0 Slot:ST12 (X20DI9371) Point:0 01MAU24_AP001_XM52
NORMAL
IN2 READY
01MAU24_AP001_XL21
IN3
01MAU24_AP001_XM52 01MAU24_AP002_XM51
GOVERNOR PUMP AP001 POWER IN4
01MAU24_AP002_XM52
Ini: IN5
IO:L01_01 Rack:0 Slot:ST12 (X20DI9371) Point:1 01MAU24_AP002_XL21
NORMAL IN6
01MAU24_AP003_XM51
01MAU24_AP001_XL21 IN7
01MAU24_AP003_XL21
GOVERNOR PUMP AP001 IN AUTO MODE IN8
Ini: 01MAU24_AA001_XL21
IO:L01_01 Rack:0 Slot:ST12 (X20DI9371) Point:2 IN9
01MAU24_AA002_XL21
DETECTED I10
01MAU24_CM001_XM01
01MAU24_AP002_XM51 I11
GOVERNOR PUMP AP002 MOTOR 01MAU24_EU014_XM01
Ini: I12
01MAU24_EU014_XM51
IO:L01_01 Rack:0 Slot:ST12 (X20DI9371) Point:6 I13
NORMAL 01MAU24_EU014_XM52
I14
01MAU24_CL002_XH04
01MAU24_AP002_XM52 I15
GOVERNOR PUMP AP002 POWER 01MAU24_CL001_XH04
Ini: I16
IO:L01_01 Rack:0 Slot:ST12 (X20DI9371) Point:7 01MAU24_CL003_XH07
NORMAL I17
01MAU24_CP001_ZH03
I18
01MAU24_AP002_XL21
GOVERNOR PUMP AP002 IN AUTO MODE
Ini:
IO:L01_01 Rack:0 Slot:ST12 (X20DI9371) Point:8
DETECTED
01MAU24_AP003_XM51
LEAKAGE OIL PUMP AP003 FAULT
Ini:
IO:L01_02 Rack:0 Slot:ST3 (X20DI9371) Point:0
NORMAL
01MAU24_AP003_XL21
LEAKAGE OIL PUMP AP003 IN AUTO MODE
Ini:
IO:L01_02 Rack:0 Slot:ST3 (X20DI9371) Point:1
DETECTED
01MAU24_AA001_XL21
GOV PUMP AP001 UNLOAD VALVE
Ini:
IO:L01_01 Rack:0 Slot:ST12 (X20DI9371) Point:4
AUTO
01MAU24_AA002_XL21
GOV PUMP AP002 UNLOAD VALVE
Ini:
IO:L01_01 Rack:0 Slot:ST12 (X20DI9371) Point:10
AUTO
01MAU24_CM001_XM01
DISCHARGE TANK WATER IN OIL
Ini:
IO:L01_01 Rack:0 Slot:ST14 (X20DI9371) Point:7
ALARM
01MAU24_EU014_XM01
GOVERNOR OIL STATION PLC
Ini:
IO:L01_01 Rack:0 Slot:ST14 (X20DI9371) Point:2
NORMAL
01MAU24_EU014_XM51
GOVERNOR OIL STATION CTRL POWER 24VDC 1
Ini:
IO:L01_01 Rack:0 Slot:ST14 (X20DI9371) Point:0
NORMAL
01MAU24_EU014_XM52
GOVERNOR OIL STATION CTRL POWER 24VDC 2
Ini:
IO:L01_01 Rack:0 Slot:ST14 (X20DI9371) Point:1
NORMAL
XX EU014 : Governor Oil Station - REV : 114 - 14/JAN/17 09:18 - POUName : L01_5ACT
.99/A
01CJA00_EU001_ZK02
20
01MAU24_CP001_XH03 AND 01MAU24_EU014_ZM02
GOV ACCUMULATOR PRESSURE TOO LOW 1 01MAU24_CP001_XH03 01MAU24_EU014_ZM02 GOV OIL STATION MECHANICAL STOP COND
Ini: IN1 Ini:0 (N-DET)
IO:L01_01 Rack:0 Slot:ST13 (X20DI9371) Point:9 01MAU24_CP002_XH03
IN2 DETECTED
N-DET 01MAU24_CL002_XH03
IN3
01MAU24_CP002_XH03 01MAU24_CL001_XH03
GOV ACCUMULATOR PRESSURE TOO LOW 2 IN4
Ini: 01MAU24_CP001_ZH07
IN5
IO:L01_01 Rack:0 Slot:ST13 (X20DI9371) Point:10
N-DET
01MAU24_CL002_XH03
GOV ACCUMULATOR OIL LEVEL TOO LOW
Ini:
IO:L01_01 Rack:0 Slot:ST13 (X20DI9371) Point:4
N-DET
01MAU24_CL001_XH03
GOV OIL SUMP TANK OIL LEVEL TOO LOW
Ini:
IO:L01_01 Rack:0 Slot:ST14 (X20DI9371) Point:4
N-DET
01MAU24_CP001_ZH07
GOV ACCUMULATOR OIL PRESSURE TOO HIGH
Ini:
S:EU014
DETECTED
01MAU24_EU014_RI01 : 10.00000
17
TP
01MAU24_EA001_ZA01 01MAU24_EU001_YL01
Start governor oil station TP_R
01MAU24_EA001_ZA01 01MAU24_EU001_YL01 GOVERNOR OIL STATION START ORDER
Ini: IN REB Ini:
S:SFC ON
REQ RET
01MAU24_EU014_RI01 : 10.00000
18
TP
01MAU24_EA001_ZA02 01MAU24_EU001_YL02
Stop governor oil station 01MAU24_EA001_ZA02
TP_R 01MAU24_EU001_YL02 GOVERNOR OIL STATION STOP ORDER
Ini: IN REB Ini:
S:SFC ON
REQ RET
01MAU24_EU014_RI01 : 10.00000
15 23
TP IV
01MAU24_AA002_ZA01 01MAU24_AA002_ZG01
Open governor solenoid valve 01MAU24_AA002_ZA01
TP_R RS 01MAU24_AA002_ZG01 GOVERNOR SOLENOID AA002 VALVE OPEN Memory
Ini: IN REB S Q1 Ini:
S:SFC... YES
REQ RET R1 /Q1
01MAU24_EU014_RI01 : 10.00000
16
TP 26
01MAU24_AA002_ZA02 MOVE_B 01MAU24_AA002_YL01
Close governor solenoid valve TP_R
01MAU24_AA002_ZA02 GOVERNOR SOLENOID AA002 VALVE
Ini: IN REB IN RE Ini:
S:SFC... CLOSED
REQ RET
XX EU014 : Governor Oil Station - REV : 114 - 14/JAN/17 09:18 - POUName : L01_5ACT
.100/A
7
01MAU24_CP001_XQ01 THR_HL
GOVERNOR ACCUMULATOR OIL PRESSURE 01MAU24_CP001_XQ01 01MAU24_CP001_ZH07_V
Unit: bar IN Hi2_V
IO:L01_01 Rack:0 Slot:ST18 (X20AI4632) Point:0 01MAU24_CP001_ZH06_V
6553/32767 (0/50 bar) Val Hi1_V
01MAU24_CP001_XQ01_V 01MAU24_CP001_ZH04_V
Vus Lo1_V
01MAU24_CP001_ZW10 01MAU24_CP001_ZH03_V
Hys Lo2_V
01MAU24_CP001_ZW17 01MAU24_CP001_ZH07
HIGH 1 THRESHOLD SP 01MAU24_CP001_ZW17 01MAU24_CP001_ZH07 GOV ACCUMULATOR OIL PRESSURE TOO HIGH
Ini:29612 (43.98 bar) H2_Thr Hi2 Ini:
01MAU24_CP001_ZW16 01MAU24_CP001_ZH06
H1_Thr Hi1 DETECTED
6553/32767 (0/50 bar)
L1_Thr Lo1
01MAU24_CP001_ZW16 01MAU24_CP001_ZW13 01MAU24_CP001_ZH03
L2_Thr Lo2 01MAU24_CP001_ZH06
HIGH 1 THRESHOLD SP GOV ACCUMULATOR OIL PRESSURE HIGH
Ini:28572 (42 bar) Ini:
DETECTED
6553/32767 (0/50 bar)
01MAU24_CP001_ZW13
LOW 2 THRESHOLD SP
Ini:25427 (36 bar)
8 01MAU24_CP001_ZH03
THR_HL GOV ACCUMULATOR OIL PRESSURE LOW
01MAU24_CP001_XQ01 Ini:0 (N-DET)
IN Hi2_V DETECTED
Val Hi1_V
01MAU24_CP001_XQ01_V
Vus Lo1_V
01MAU24_CP001_ZW10
Hys Lo2_V
XX EU014 : Governor Oil Station - REV : 114 - 14/JAN/17 09:18 - POUName : L01_5ACT
.101/A
22
21 IV
01MAU24_CL002_XH51 AND 01MAU24_EA001_ZG01
GOV ACCUMULATOR OIL LEVEL BUILD UP RS
01MAU24_CL002_XH51 01MAU24_EA001_ZG01 GOVERNOR OIL STATION STARTED IN AUTO MODE
Ini: IN1 S Q1
IO:L01_01 Rack:0 Slot:ST13 (X20DI9371) Point:6 01MAU24_CP001_ZH04 01MAU24_EA001_ZG02 Ini:0 (N-DET)
IN2 R1 /Q1 DETECTED
DETECTED
IN3
01MAU24_CP001_ZH04
GOV ACCUMULATOR OIL PRESSURE BUILDUP 01MAU24_EA001_ZG02
Ini:0 (N-DET) GOVERNOR OIL STATION STOPPED IN AUTO MODE
S:EU014 Ini:0 (N-DET)
DETECTED DETECTED
9 11
01MAU24_AP001_XG01 AND OR
GOVERNOR PUMP AP001 RUNNING 01MAU24_AP001_XG01
Ini: IN1 IN1
IO:L01_01 Rack:0 Slot:ST12 (X20DI9371) Point:3 01MAU24_AP001_XL21
DETECTED IN2 IN2
01MAU24_AP001_XL21
GOVERNOR PUMP AP001 IN AUTO MODE
Ini:
IO:L01_01 Rack:0 Slot:ST12 (X20DI9371) Point:2
DETECTED
10
01MAU24_AP002_XG01 AND
GOVERNOR PUMP AP002 RUNNING 01MAU24_AP002_XG01
Ini: IN1
IO:L01_01 Rack:0 Slot:ST12 (X20DI9371) Point:9 01MAU24_AP002_XL21
DETECTED IN2
01MAU24_AP002_XL21
GOVERNOR PUMP AP002 IN AUTO MODE
Ini: 01MAU24_EU014_RI02 : 5.00000
IO:L01_01 Rack:0 Slot:ST12 (X20DI9371) Point:8
DETECTED 14
13 TP
12
AND TON_R
01MAU24_EA001_ZA02 OR IN1 IN REB
Stop governor oil station 01MAU24_EA001_ZA02
Ini: IN1 IN2 RET
S:SFC 01CJA00_EU001_ZG02
REQ IN2
01CJA00_EU001_ZG02
UNIT INIT/STILL STOP STATE
Ini:0 (NO)
S:CON
YES
XX EU014 : Governor Oil Station - REV : 114 - 14/JAN/17 09:18 - POUName : L01_5ACT
.102/A
5 27
FB_VRE_2POS FB_VRE_2POS
01MAU24_AP001_XG01 01MAU24_AP002_XG01
1 01MAU24_AP001_XG01_V Pos1 2401MAU24_AP002_XG01_V Pos1
NOT Pos1_V NOT Pos1_V
01MAU24_AP001_XG01 01MAU24_AP002_XG01
IN Pos2 IN Pos2
01MAU24_AP001_XG01_V 01MAU24_AP002_XG01_V
2 Pos1_V 25 Pos1_V
01MAU24_EU014_BI01 01MAU24_EU014_BI02
OR Fault OR Fault
01MAU24_AP001_XM51 01MAU24_EU014_D01 : 200 01MAU24_AP001_ZU01 01MAU24_AP002_XM51 01MAU24_EU014_D02 01MAU24_AP002_ZU01
IN1 TLTE SIG IN1 TLTE SIG
01MAU24_AP001_XM52 01MAU24_EU014_W01 : 2 01MAU24_AP001_ZU01_V 01MAU24_AP002_XM52 01MAU24_EU014_W01 : 2 01MAU24_AP002_ZU01_V
IN2 Type SIG_V IN2 Type SIG_V
6 28
FB_VRE_2POS FB_VRE_2POS
01MAU24_AP003_XG01 01MAU24_AA005_XG01
3 01MAU24_AP003_XM51_V Pos1 Pos1
01MAU24_AA005_XG01_V
NOT Pos1_V Pos1_V
01MAU24_AP003_XG01 01MAU24_AA005_XG02
IN Pos2 Pos2
01MAU24_AP003_XM51_V 01MAU24_AA005_XG02_V
4 Pos1_V Pos1_V
01MAU24_EU014_BI03 01MAU24_EU014_BI04
OR Fault Fault
01MAU24_AP003_XM51 01MAU24_EU014_D03 01MAU24_AP003_ZU01 01MAU24_EU014_D04 01MAU24_AA005_ZU01
IN1 TLTE SIG TLTE SIG
0 01MAU24_EU014_W01 : 2 01MAU24_AP003_ZU01_V 01MAU24_EU014_W01 : 2 01MAU24_AA005_ZU01_V
IN2 Type SIG_V Type SIG_V
XX EU014 : Governor Oil Station - REV : 114 - 14/JAN/17 09:18 - POUName : L01_5ACT
.103/A
4.14 FE001 : Electrical Measurement - REV : 92 - 14/JAN/17 09:34 - POUName : L01_5ACT
01CJA00_FE001_ZM02
MFC3000 vs FE001 MOD EXCHANGE
Ini:0 (ABSENCE)
S:EU101
PRESENCE
7
SEL 01CJA00_DE001_ZQ01
01CJA00_CE001_ZQ01
01CJA00_FE001_ZM02 01CJA00_DE001_ZQ01 ACTIVE POWER MEAS VALUE
G RE Unit: MW
UNIT ACTIVE POWER MEASUREMENT VALIDATION
Ini:0 (NORMAL) IN1 -12000/12000 (-120/120 MW)
S:DE001 01BBA00_FE001_2_ZQ01
FAULT
IN2
10
SEL
5
01CJA00_CE001_ZQ01
01BBA00_CE001_XQ01 AI_SCALE G RE
UNIT ACTIVE POWER 01BBA00_CE001_XQ01
Unit: MW IN RI IN1
IO:L01_01 Rack:0 Slot:ST16 (X20AI4632) Point:0 01CJA00_DE001_ZQ01
6553/32767 (-30/120 MW)
_V(boo) RR IN2
_V(us) Err
01BBA00_FE001_1_ZW09 : 32767
IMax
01BBA00_FE001_1_ZW01 : 6553
IMin
01BBA00_FE001_1_ZW19 : 12000
OMax
01BBA00_FE001_1_ZW11 : -3000
OMin
6
01BBA00_FE001_RQ42 AO_SCALE
UNIT ACTIVE POWER 01BBA00_FE001_RQ42 01BBA00_FE001_2_ZQ01
Unit: MW IN RE
EXT:L01_r5_2_0EX'ModbusClientInW Point:98 01BBA00_FE001_2_ZW09 : 120000.00000
-2e+8/2e+8 (-200/200 MW)
IMax Err
01BBA00_FE001_2_ZW01 : -30000
IMin
01BBA00_FE001_2_ZW19 : 12000
OMax
01BBA00_FE001_2_ZW11 : -3000
OMin
11
AND 01CJA00_DE001_ZQ01_V
01CJA00_CE001_ZQ01 01CJA00_DE001_ZQ01_V Validator
IN1 Ini:0
01BBA00_FE001_RQ42_V
IN2
8 12
01CJA00_DE001_ZQ01 ABS THR_HL
ACTIVE POWER MEAS VALUE 01CJA00_DE001_ZQ01 01BBA00_DE001_ZH07_V
Unit: MW IN IN Hi2_V
S:FE001 01CJA00_DE001_ZQ01_V 01BBA00_DE001_ZH06_V
-12000/12000 (-120/120 MW)
Val Hi1_V 01BBA00_DE001_ZH07
01BBA00_DE001_ZH04_V REWATER STAGE ACTIVE POWER REACHED
Vus Lo1_V Ini:0 (N-DET)
01BBA00_DE001_ZW10
Hys Lo2_V DETECTED
01BBA00_DE001_ZW17
HIGH 1 THRESHOLD SP 01BBA00_DE001_ZW17 01BBA00_DE001_ZH07
Ini:1200 (12 MW) H2_Thr Hi2 01BBA00_DE001_ZH06
01BBA00_DE001_ZW16 01BBA00_DE001_ZH06 DEWATER STATE ACTIVE POWER TOO HIGH
0/12000 (0/120 MW)
H1_Thr Hi1 Ini:0 (N-DET)
01BBA00_DE001_ZW14 01BBA00_DE001_ZH04
L1_Thr Lo1 DETECTED
01BBA00_DE001_ZW16
HIGH 1 THRESHOLD SP L2_Thr Lo2
Ini:1000 (10 MW) 01BBA00_DE001_ZH04
G->GC DEWATER ACTIVE POWER
0/12000 (0/120 MW) Ini:0 (N-REACHD)
REACHED
01BBA00_DE001_ZW14
LOW 1 THRESHOLD SP
Ini:400 (4 MW)
13
THR_HI 01BBA00_DE001_ZH03
01CJA00_DE001_ZQ01 01BBA00_DE001_ZH03 UNIT ACTIVE POWER > MINIMAL
0/12000 (0/120 MW) IN Hi Ini:0 (N-DET)
Val Err DETECTED
Vus
01BBA00_DE001_ZW13
LOW 2 THRESHOLD SP 01BBA00_DE001_ZW13
Ini:800 (8 MW) Hi_Thr
01BBA00_DE001_ZW10
-12000/12000 (-120/120 MW)
Hys
19
AND 01CJA00_DE002_ZQ01_V
01BBA00_FE001_RQ43_V 01CJA00_DE002_ZQ01_V Validator
IN1 Ini:0
1
IN2
4 20
01CJA00_DE002_ZQ01 ABS THR_LO 01BBA00_DE003_ZH03
REACTIVE POWER MEAS VALUE 01CJA00_DE002_ZQ01 01BBA00_DE003_ZH03 UNIT REACTIVE POWER < MINIMAL
Ini:0 (0 Mvar) IN IN Lo Ini:0 (N-DET)
S:FE001 01BBA00_DE003_ZH03_V
Val Err DETECTED
-12000/12000 (-120/120 Mvar)
Vus
01BBA00_DE003_ZW13
LOW 2 THRESHOLD SP 01BBA00_DE003_ZW13
Ini:300 (3 Mvar) Lo_Thr
01BBA00_DE003_ZW10 : 50
-12000/12000 (-120/120 Mvar) Hys
15
01BBA00_FE001_RQ03 AO_SCALE
UNIT VOLTGAE PHASE AB 01BBA00_FE001_RQ03 01BBA00_FE001_6_ZQ01
Unit: kV IN RE
EXT:L01_r5_2_0EX'ModbusClientInW Point:4 01BBA00_FE001_6_ZW09 : 20000
0/20000 (0/20 kV) IMax Err
01BBA00_FE001_6_ZW01 : 0
IMin
01BBA00_FE001_6_ZW19 : 2000
OMax
01BBA00_FE001_6_ZW11 : 0
OMin
1 16
FB_UV_BV AND 01CJA00_DE003_ZQ01_V
01BBA00_CE001_XQ02_V 01CJA00_CE001_ZQ02 01CJA00_CE001_ZQ02 01CJA00_DE003_ZQ01_V Validator
USINT VALID IN1 Ini:0
01BBA00_FE001_RQ03_V
FORC_V IN2
18
01CJA00_DE003_ZQ01 THR_HL
UNIT VOLTAGE MEAS VALUE 01CJA00_DE003_ZQ01 01BBA00_DE003_ZH07_V
Ini:0 (0 kV) IN Hi2_V
S:FE001
0/2000 (0/20 kV) Val Hi1_V
Vus Lo1_V
01BBA00_FE001_II01 : 10 01BBA00_DE003_ZH04_V
Hys Lo2_V
01BBA00_DE003_ZW17 01BBA00_DE003_ZH07
HIGH 1 THRESHOLD SP 01BBA00_DE003_ZW17 01BBA00_DE003_ZH07 UNIT VOLTAGE >95%Un
Ini:1310 (13.1 kV) H2_Thr Hi2 Ini:0 (N-DET)
H1_Thr Hi1 DETECTED
0/2000 (0/20 kV)
L1_Thr Lo1
01BBA00_DE003_ZW14 01BBA00_DE003_ZW14 01BBA00_DE003_ZH04
LOW 1 THRESHOLD SP L2_Thr Lo2 01BBA00_DE003_ZH04
Ini:50 (0.5 kV) UNIT DEAD VOLTAGE
Ini:0 (N-DET)
0/2000 (0/20 kV) DETECTED
01CJA00_EU001_ZK05
7
01PAC00_AA001_XL21 AND 01PAC00_EU001_ZM05
UNIT TECHNICAL WATER VALVE AA001 AUTO 01PAC00_AA001_XL21 01PAC00_EU001_ZM05 UNIT CLW SYSTEM STARTUP CONDITIONS
Ini: IN1 Ini:0 (N-DET)
IO:L01_02 Rack:0 Slot:ST9 (X20DI9371) Point:0 01PAC00_GH001_XM01
DETECTED
IN2 DETECTED
01PAC00_GH001_XM01
UNIT TECHNICAL WATER VALVE AA001 FAILURE
Ini:
IO:L01_02 Rack:0 Slot:ST9 (X20DI9371) Point:1
DETECTED
3
01PAC00_CF972_XQ01 THR_HL
TURBINE GUIDE BRG COOLING WTR FLW 01PAC00_CF972_XQ01
Unit: m3/s IN Hi2_V
IO:L01_01 Rack:0 Slot:ST23 (X20AI4632) Point:2 01PAC00_CF972_ZH06_V
6553/32767 (0/10 m3/s)
Val Hi1_V
01PAC00_CF972_XQ01_V 01PAC00_CF972_ZH04_V
Vus Lo1_V
01PAC00_CF972_ZW10 01PAC00_CF972_ZH03_V
Hys Lo2_V
01PAC00_CF972_ZW17
H2_Thr Hi2 01PAC00_CF972_ZH06
01PAC00_CF972_ZW16 01PAC00_CF972_ZH06 TUR GUIDE BRG COOLING WTR FLW NORMAL
H1_Thr Hi1 Ini:0 (N-DET)
01PAC00_CF972_ZW14 01PAC00_CF972_ZH04
L1_Thr Lo1 DETECTED
01PAC00_CF972_ZW13 01PAC00_CF972_ZH03
L2_Thr Lo2
4
01PAC00_CF973_XQ01 THR_HL
GEN THRUST BRG COOLING WTR FLOW 01PAC00_CF973_XQ01
Unit: m3/s IN Hi2_V
IO:L01_01 Rack:0 Slot:ST23 (X20AI4632) Point:3 01PAC00_CF973_ZH06_V
6553/32767 (0/10 m3/s)
Val Hi1_V
01PAC00_CF973_XQ01_V 01PAC00_CF973_ZH04_V
Vus Lo1_V
01PAC00_CF973_ZW10 01PAC00_CF973_ZH03_V
Hys Lo2_V
01PAC00_CF973_ZW17
H2_Thr Hi2 01PAC00_CF973_ZH06
01PAC00_CF973_ZW16 01PAC00_CF973_ZH06 GEN THRUST BRG COOLING WTR FLOW NORMAL
H1_Thr Hi1 Ini:0 (N-DET)
01PAC00_CF973_ZW14 01PAC00_CF973_ZH04
L1_Thr Lo1 DETECTED
01PAC00_CF973_ZW13 01PAC00_CF973_ZH03
L2_Thr Lo2
5
01PAC00_CF975_XQ01 THR_HL
GEN COOLER MAIN OUTLET COOLING WTR FLOW 01PAC00_CF975_XQ01
Unit: m3/s IN Hi2_V
IO:L01_01 Rack:0 Slot:ST23 (X20AI4632) Point:1 01PAC00_CF975_ZH06_V
6553/32767 (0/10 m3/s) Val Hi1_V
01PAC00_CF975_XQ01_V 01PAC00_CF975_ZH04_V
Vus Lo1_V
01PAC00_CF975_ZW10 01PAC00_CF975_ZH03_V
Hys Lo2_V
01PAC00_CF975_ZW17
H2_Thr Hi2 01PAC00_CF975_ZH06
01PAC00_CF975_ZW16 01PAC00_CF975_ZH06 GEN COOLER MAIN COOLING WTR FLOW NORMAL
H1_Thr Hi1 Ini:0 (N-DET)
01PAC00_CF975_ZW14 01PAC00_CF975_ZH04
L1_Thr Lo1 DETECTED
01PAC00_CF975_ZW13 01PAC00_CF975_ZH03
L2_Thr Lo2
01PAC00_CF976_ZW17
H2_Thr Hi2 01PAC00_CF976_ZH06
01PAC00_CF976_ZW16 01PAC00_CF976_ZH06 GEN GUIDE BRG COOLING WTR FLOW NORMAL
H1_Thr Hi1 Ini:0 (N-DET)
01PAC00_CF976_ZW14 01PAC00_CF976_ZH04
L1_Thr Lo1 DETECTED
01PAC00_CF976_ZW13 01PAC00_CF976_ZH03
L2_Thr Lo2
8
01PAC00_AA001_ZA01 FB_VA2 01PAC00_GH001_YL01
UNIT TECHNICAL WATER VALVE AA001 AUTO ORD 01PAC00_AA001_ZA01 01PAC00_GH001_YL01 UNIT COOL SYSTEM STARTING ORDER
Ini:0 (N-OPNG) OP_A OR1 Ini:
S:SFC ON
OPENING OP_M DS1
01PAC00_AA001_ZC01
OP_A_ATH
01PAC00_AA001_XG01 01PAC00_AA001_ZJ01
OP_M_ATH
UNIT TECHNICAL WATER VALVE AA001 POSITION 01PAC00_AA001_XG01 01PAC00_AA001_ZM11
Ini: OP_PS TLTE1
IO:L01_02 Rack:0 Slot:ST9 (X20DI9371) Point:2 01PAC00_AA001_XG01_V
OPEN OP_PS_V
01PAC00_GH001_YL02
01PAC00_AA001_ZA02 01PAC00_AA001_ZA02 01PAC00_GH001_YL02 UNIT COOL SYSTEM STOPPING ORDER
CL_A OR2 Ini:
UNIT TECHNICAL WATER VALVE AA001 AUTO ORDER
Ini:0 (N-CLSG) CL_M DS2 ON
S:SFC 01PAC00_AA001_ZC02
CLOSING CL_A_ATH
01PAC00_AA001_ZJ02
CL_M_ATH
01PAC00_AA001_XG01 01PAC00_AA001_ZM12
CL_PS TLTE2
01PAC00_AA001_XG01_V
1 CL_PS_V
01PAC00_GH001_XM01 OR
UNIT TECHNICAL WATER VALVE AA001 FAILURE 01PAC00_GH001_XM01 01PAC00_AA001_ZM00 01PAC00_AA001_ZM10
Ini: IN1 FLT_IN ALARM
IO:L01_02 Rack:0 Slot:ST9 (X20DI9371) Point:1 0 01PAC00_AA001_ZM50
DETECTED IN2 AV REM_ATH
0
2 MANU
01PAC00_AA001_XL21 AND
UNIT TECHNICAL WATER VALVE AA001 AUTO 01PAC00_AA001_XL21 01PAC00_AA001_ZT11
Ini: IN1 TLTE_OP
IO:L01_02 Rack:0 Slot:ST9 (X20DI9371) Point:0 1 01PAC00_AA001_ZT12
DETECTED IN2 TLTE_CL
01PAC00_AA001_ZT01
OP_PL 01PAC00_AA001_ZU01
01PAC00_AA001_ZT02 01PAC00_AA001_ZU01 UNIT TECHNICAL WATER VALVE AA001 ANIMATION WORD
CL_PL SIG Ini:
01PAC00_AA001_ZT00 01PAC00_AA001_ZU01_V
F_TP SIG_V 0/127
Type
01CJA00_EU001_ZK05
1
01CMA00_EU001_XM01 AND 01CMA00_EU001_ZM05
TURBINE GUIDE BEARING VIBRATION ALARM 1 01CMA00_EU001_XM01 01CMA00_EU001_ZM05 UNIT ONLINE MONITORING STARTING COND
Ini: IN1 Ini:0 (N-READY)
IO:L01_02 Rack:0 Slot:ST11 (X20DI9371) Point:0 01CMA00_EU001_XM03
DETECTED
IN2 READY
01CMA00_EU001_XM05
IN3
01CMA00_EU001_XM03 01CMA00_EU001_XM07
GEN THRUST BEARING VIBRATION ALARM 1 IN4
01CMA00_EU001_XM09
Ini: IN5
IO:L01_02 Rack:0 Slot:ST11 (X20DI9371) Point:2 01CMA00_EU001_XM11
DETECTED IN6
01CMA00_EU001_XM05
GEN GUIDE BEARING VIBRATION ALARM 1
Ini:
IO:L01_02 Rack:0 Slot:ST11 (X20DI9371) Point:4
DETECTED
01CMA00_EU001_XM07
TURBINE GUIDE BEARING RUNOUT ALARM 1
Ini:
IO:L01_02 Rack:0 Slot:ST11 (X20DI9371) Point:6
DETECTED
01CMA00_EU001_XM09
GEN THRUST BEARING RUNOUT ALARM 1
Ini:
IO:L01_02 Rack:0 Slot:ST11 (X20DI9371) Point:8
DETECTED
01CMA00_EU001_XM11
GEN GUIDE BEARING RUNOUT ALARM 1
Ini:
IO:L01_02 Rack:0 Slot:ST11 (X20DI9371) Point:10
DETECTED
2
FB_VRE_2POS
01BFA00_GS100_XG01
Pos1
01BFA00_GS100_XG01_V
Pos1_V
01BFA00_GS100_XG02
1 Pos2
01BFA00_GS100_XG02_V
OR Pos1_V
01BFA00_GS100_XM01
IN1 Fault
01BFA00_GS100_XM02 01BFA00_GS000_T01 01BFA00_GS000_ZU01
IN2 TLTE SIG
2 01BFA00_GS000_ZU01_V
Type SIG_V
4
FB_VRE_2POS
01BFA00_GS101_XG01
Pos1
01BFA00_GS101_XG01_V
Pos1_V
01BFA00_GS101_XG02
3 Pos2
01BFA00_GS101_XG02_V
OR Pos1_V
01BFA00_GS101_XM01
IN1 Fault
01BFA00_GS101_XM02 01BFA00_GS000_T01 01BFA00_GS101_ZU01
IN2 TLTE SIG
2 01BFA00_GS101_ZU01_V
Type SIG_V
6
FB_VRE_2POS
01BFA00_GS102_XG01
Pos1
01BFA00_GS102_XG01_V
Pos1_V
01BFA00_GS102_XG02
5 Pos2
01BFA00_GS102_XG02_V
OR Pos1_V
01BFA00_GS102_XM01
IN1 Fault
01BFA00_GS102_XM02 01BFA00_GS000_T01 01BFA00_GS102_ZU01
IN2 TLTE SIG
2 01BFA00_GS102_ZU01_V
Type SIG_V
01CJA00_EU001_ZK04
1
01CHA00_EN001_XM01 AND 01CHA00_PT001_ZM04
GENERATOR F11 MAIN PROTECTION FAILURE 01CHA00_EN001_XM01 01CHA00_PT001_ZM04 Generator Protection ELECTRICAL STARTING COND
Ini: IN1 Ini:0 (N-READY)
IO:L01_03 Rack:0 Slot:ST2 (X20DI9371) Point:0 01CHA00_EN001_XM02
DETECTED
IN2 READY
01CHA00_EN001_XM03
IN3
01CHA00_EN001_XM02 01CHA00_EN001_XM04
GENERATOR F21 BACKUP PROTECTION FAILURE IN4
01CHA00_EN001_XM05
Ini: IN5
IO:L01_03 Rack:0 Slot:ST2 (X20DI9371) Point:1 01CHA00_EN001_XM06
DETECTED IN6
01CHA00_EN001_XM07
01CHA00_EN001_XM03
IN7
01CHA00_EN001_XM08
F31 EXCITATION TRANSFORMER PROTECTION FAILURE IN8
Ini: 01CHA00_EN001_XM17
IO:L01_03 Rack:0 Slot:ST2 (X20DI9371) Point:2 IN9
01CHA00_EN001_XM18
DETECTED I10
01CHA00_EN001_XM09
01CHA00_EN001_XM04 I11
GENERATOR F32 ROTOR O/C PROTECTION FAILURE
Ini:
IO:L01_03 Rack:0 Slot:ST2 (X20DI9371) Point:3
DETECTED
01CHA00_EN001_XM05
GENERATOR MAIN PROTECT 220VDC POWER FAILURE
Ini:
IO:L01_03 Rack:0 Slot:ST2 (X20DI9371) Point:4
DETECTED
01CHA00_EN001_XM06
GENERATOR BACKUP PROTECT 220VDC POWER FAILURE
Ini:
IO:L01_03 Rack:0 Slot:ST2 (X20DI9371) Point:5
DETECTED
01CHA00_EN001_XM07
ROTOR EARTH FAULT PROTECT (1-3)HZ POWER FAILURE
Ini:
IO:L01_03 Rack:0 Slot:ST2 (X20DI9371) Point:6
DETECTED
01CHA00_EN001_XM08
GENERATOR PROTECTION FUSE TU9H21 FAILURE MONITOR
Ini:
IO:L01_03 Rack:0 Slot:ST2 (X20DI9371) Point:7
DETECTED
01CHA00_EN001_XM17
GENERATOR PROT SIGNAL UNIT POWER SUPPLY 1 FAILURE
Ini:
IO:L01_03 Rack:0 Slot:ST3 (X20DI9371) Point:4
DETECTED
01CHA00_EN001_XM18
GENERATOR PROT SIGNAL UNIT POWER SUPPLY 2 FAILURE
Ini:
IO:L01_03 Rack:0 Slot:ST3 (X20DI9371) Point:5
DETECTED
01CHA00_EN001_XM09
GENERATOR PROTECTION RELAY IN TEST MODE
Ini:
IO:L01_03 Rack:0 Slot:ST2 (X20DI9371) Point:8
DETECTED
01CJA00_EU001_ZK03
2
01CHA00_EN001_XM19 AND 01CHA00_PT001_ZM03
GENERATOR MAIN PROTECTION UNIT TRIP 01CHA00_EN001_XM19 01CHA00_PT001_ZM03 Generator Protection ELECTRICAL STOP COND
Ini: IN1 Ini:
IO:L01_03 Rack:0 Slot:ST4 (X20DI9371) Point:0 01CHA00_EN001_XM20
IN2 DETECTED
DETECTED 01CHA00_EN001_XM21
IN3
01CHA00_EN001_XM20 01CHA00_MT001_XM01
GENERATOR BACKUP PROTECTION UNIT TRIP IN4
Ini:
01CHA00_MT001_XM03
IN5
IO:L01_03 Rack:0 Slot:ST4 (X20DI9371) Point:1 01CHA00_MT001_XM02
DETECTED IN6
01CHA00_EN001_XM21
EXCITATION TRANSFORMER PROTECTION TRIP
Ini:
IO:L01_03 Rack:0 Slot:ST4 (X20DI9371) Point:2
DETECTED
01CHA00_MT001_XM01
GENERATOR MAIN PROTECTION FROM MATRIX
Ini:
IO:L01_03 Rack:0 Slot:ST3 (X20DI9371) Point:8
DETECTED
01CHA00_MT001_XM03
GENERATOR FIRE COMMAND TO PROTECTION
Ini:
IO:L01_03 Rack:0 Slot:ST3 (X20DI9371) Point:11
DETECTED
2
01BAT00_EN001_XM02 AND 01BAT00_EU001_ZM04
TRANSF COOLING SYS PUMP MAIN POWER FAILURE 01BAT00_EN001_XM02 01BAT00_EU001_ZM04 MAIN TRANSFORMER SYSTEM STARTING COND
Ini: IN1 Ini:0 (N-READY)
IO:L01_03 Rack:0 Slot:ST6 (X20DI9371) Point:1 01BAT00_EN001_XM03
DETECTED
IN2 READY
01BAT00_EN001_XM04
IN3
01BAT00_EN001_XM03 01BAT00_EN001_XM05
TRANSF COOLING SYS DC POWER CONTROL FAILURE IN4
Ini:
01BAT00_EN001_XM06
IN5
IO:L01_03 Rack:0 Slot:ST6 (X20DI9371) Point:2 01BAT00_EN001_XM07
DETECTED IN6
01BAT00_EN001_XM08
01BAT00_EN001_XM04
IN7
01BAT00_EN001_XM09
TRANSF COOLING SYS PUMP BACKUP POWER FAILURE IN8
Ini: 01BAT00_EN001_XM11
IO:L01_03 Rack:0 Slot:ST6 (X20DI9371) Point:3 IN9
DETECTED
01BAT00_EN001_XM12
I10
01BAT00_EN001_XM16
01BAT00_EN001_XM05 I11
MAIN TRANSFORMER COOLING SYSTEM FAILURE 01BAT00_EN001_XM17
Ini:
I12
01BAT00_EN001_XM18
IO:L01_03 Rack:0 Slot:ST6 (X20DI9371) Point:4 I13
DETECTED 01BAT00_EN001_XM29
I14
01BAT00_EN001_XM06
01BAT00_EN001_XM30
I15
TRANSF COOLING SYS B1 PUMP FAILURE
Ini:
IO:L01_03 Rack:0 Slot:ST6 (X20DI9371) Point:5
DETECTED
01BAT00_EN001_XM07
TRANSF COOLING SYS B2 PUMP FAILURE
Ini:
IO:L01_03 Rack:0 Slot:ST6 (X20DI9371) Point:6
DETECTED
01BAT00_EN001_XM08
TRANSFORMER COOLING SYSTEM AUTO POSITION
Ini:
IO:L01_03 Rack:0 Slot:ST6 (X20DI9371) Point:7
DETECTED
01BAT00_EN001_XM09
TRANSF COOLING SYS SHUTOFF VALVE POWER FAILURE
Ini:
IO:L01_03 Rack:0 Slot:ST6 (X20DI9371) Point:8
DETECTED
01BAT00_EN001_XM11
MAIN TRANSFORMER FIRE VALVE STUCK
Ini:
IO:L01_03 Rack:0 Slot:ST6 (X20DI9371) Point:10
DETECTED
01BAT00_EN001_XM12
TRANSF COOLING SYS VALVE CONTROL POWER FAILURE
Ini:
IO:L01_03 Rack:0 Slot:ST6 (X20DI9371) Point:11
DETECTED
01BAT00_EN001_XM16
MAIN TRANSF DC MAIN PROTECTION POWER FAILURE
Ini:
IO:L01_03 Rack:0 Slot:ST7 (X20DI9371) Point:3
DETECTED
01BAT00_EN001_XM17
MAIN TRANSF DC BACKUP PROTECTION POWER FAILURE
Ini:
IO:L01_03 Rack:0 Slot:ST7 (X20DI9371) Point:4
DETECTED
01BAT00_EN001_XM18
MAIN TRANSF PT FUSE FAILURE MONITOR
Ini:
IO:L01_03 Rack:0 Slot:ST7 (X20DI9371) Point:5
DETECTED
01BAT00_EN001_XM29
TRANSFORMER PROT SIGNAL UNIT POWER SUPPLY 1 FAILURE
Ini:
IO:L01_03 Rack:0 Slot:ST8 (X20DI9371) Point:4
DETECTED
01BAT00_EN001_XM30
TRANSFORMER PROT SIGNAL UNIT POWER SUPPLY 2 FAILURE
Ini:
IO:L01_03 Rack:0 Slot:ST8 (X20DI9371) Point:5
DETECTED
01BAT00_EN001_XM39
AUX TRANSFORMER MAIN PROTECTION TRIP
Ini:
IO:L01_03 Rack:0 Slot:ST9 (X20DI9371) Point:7
DETECTED
01BAT00_EN001_XM40
AUX TRANSFORMER BACKUP PROTECTION TRIP
Ini:
IO:L01_03 Rack:0 Slot:ST9 (X20DI9371) Point:8
DETECTED
01BAT00_MT001_XM01
MAIN TRANSFORMER PROTECTION FROM MATRIX
Ini:
IO:L01_03 Rack:0 Slot:ST3 (X20DI9371) Point:10
DETECTED
3
01BAT00_EU001_ZM04 AND 01BAT00_EU001_ZM51
MAIN TRANSFORMER SYSTEM STARTING COND 01BAT00_EU001_ZM04 01BAT00_EU001_ZM51 MAIN TRANSFORMER READY TO OPERATION
Ini:0 (N-READY) IN1 Ini:
S:PT001 01BAT00_EU001_ZM03
IN2 YES
READY
01BAT00_EU001_ZM03
MTR SYSTEM ELECTRICAL STOP COND
Ini:0 (N-DET)
S:PT001
DETECTED
17
01CJA00_EU001_ZG41 AND 01SCC00_AA902_ZA01
UNIT GC STATE 01CJA00_EU001_ZG41 01SCC00_AA902_ZA01 DEWATER AUX VALVE AUTO OPEN ORD
Ini:0 (NO) 01SCC00_AA902_RI03 : 1.00000 IN1 Ini:0 (N-OPNG)
S:SFC 1
Condensor Pressure not too low
YES 3 IN2 OPENING
2 16 IN3
TP
01MEA41_CP505_ZH04 OR TON_R OR
RUNNER DEWATER AIR INJECTION LEVEL -4.4m 01MEA41_CP505_ZH04
Ini: IN1 IN REB IN1
S:CON 0
DETECTED
IN2 RET IN2
01SCC00_AA902_RI01 : 1800.00000
5
4 TP
01CJA00_EU001_ZG41 AND TON_R
UNIT GC STATE 01CJA00_EU001_ZG41
Ini:0 (NO) IN1 IN REB
S:SFC 01SCC00_AA902_ZG02
YES
IN2 RET
01SCC00_AA902_BI01
IN3
01SCC00_AA902_ZG02
DEWATER AUXILARY VALVE AA902 not OPEN Delay
Ini:
S:CON
DETECTED
01SCC00_AA902_BI01
Timer Enable
Ini:0 01SCC00_AA902_RI02 : 180.00000
7
6 TP 15
AND TON_R OR 01SCC00_AA902_ZA12
01CJA00_EU001_ZG41 01SCC00_AA902_ZA12 DEWATER AUXIL VALVE CLOSE ORDER
01SCC00_AA902_XG01 IN1 IN REB IN1
CONDENDSOR DEWATER AUXILIARY VALVE 01SCC00_AA902_XG01 Ini:
Ini: IN2 RET IN2 DETECTED
IO:L01_02 Rack:0 Slot:ST9 (X20DI9371) Point:11 01SCC00_AA902_BI01 01SCC00_AA902_ZA02
OPEN IN3 IN3
0
01SCC00_AA902_RI04 : 1.00000 IN4
9
8 TP
01MEA41_CP505_ZH03 OR LP Pressure too low
RUNNER DEWATER LEVEL LOW -4.8m
TON_R
01MEA41_CP505_ZH03
Ini: IN1 IN REB
S:CON 0
V-LOW
IN2 RET
01SCC00_AA902_ZA02
DEWATER AUX VALVE AUTO CLOSE ORDER
Ini:0 (N-CLSG)
S:SFC
CLOSING
01SCC00_AA902_ZA12 01SCC00_AA902_ZA12
CL_A OR2
DEWATER AUXIL VALVE CLOSE ORDER
Ini: CL_M DS2
S:AA902 01SCC00_AA902_ZC02
DETECTED CL_A_ATH
01SCC00_AA902_ZJ02
CL_M_ATH
01SCC00_AA902_ZG02 01SCC00_AA902_ZM12
CL_PS TLTE2
CL_PS_V
1 01SCC00_AA902_ZM10
01SCC00_AA902_XL21
01SCC00_AA902_ZM00 01SCC00_AA902_ZM10 DEWATER AUX VALVE AA902
AND FLT_IN ALARM
CONDENDSOR DEWATER AUXILIARY VALVE 01SCC00_AA902_XL21 01SCC00_AA902_ZM50 Ini:
Ini: IN1 AV REM_ATH ALARM
IO:L01_02 Rack:0 Slot:ST9 (X20DI9371) Point:10 1 0
AUTO IN2 MANU
01SCC00_AA902_ZT11 : 1200
TLTE_OP
01SCC00_AA902_ZG02 01SCC00_AA902_ZT12 : 1200
TLTE_CL
DEWATER AUXILARY VALVE AA902 not OPEN Delay 01SCC00_AA902_ZT01 : 1000
Ini: OP_PL 01SCC00_AA902_ZU01
S:CON 01SCC00_AA902_ZT02 : 1000 01SCC00_AA902_ZU01 DEWATER AUXIL VALVE ANIMATION WORD
DETECTED CL_PL SIG Ini:
01SCC00_AA902_ZT00 : 500 01SCC00_AA902_ZU01_V
F_TP SIG_V 0/127
Type
01SCC00_AA902_RI05 : 30.00000
12 19
11 TP IV
01CJA00_EU001_ZG41 AND 01SCC00_CP505_ZH07
UNIT GC STATE 01CJA00_EU001_ZG41
TON_R RS 01SCC00_CP505_ZH07
HIGH WATER LEVEL UNDER RUNER IN GC
Ini:0 (NO) IN1 IN REB S Q1 Ini:0 (N-TRP)
S:SFC 01CJA00_EU001_ZG02
IN2 RET R1 /Q1 TRIPPED
YES 01SCC00_AA902_BI02 : 0
10 IN3
01MEA41_CP505_ZH07 OR
RUNNER DEWATER HIGH LEVEL TO GE -3.5m 01MEA41_CP505_ZH07
Ini:0 (N-DET) IN1
S:CON 0
DETECTED IN2
01CJA00_EU001_ZG02
UNIT INIT/STILL STOP STATE
Ini:0 (NO)
S:CON
YES
01SCC00_AA902_RI06 : 5.00000
14 20
13 TP IV
AND TON_R RS 01SCC00_DE001_ZH06
01BBA00_DE001_ZH06 01CJA00_EU001_ZG41 01SCC00_DE001_ZH06
DEWATER STATE ACTIVE POWER TOO HIGH
IN1 IN REB S Q1 Ini:0 (N-TRP)
DEWATER STATE ACTIVE POWER TOO HIGH 01BBA00_DE001_ZH06 01CJA00_EU001_ZG02
Ini:0 (N-DET) IN2 RET R1 /Q1 TRIPPED
S:FE001 01SCC00_AA902_BI03 : 0
DETECTED IN3
7
01SCC00_AA901_ZA01 OR 01SCC00_AA901_ZA11
Dewater Main Valve AUTO OPEN ORD 01SCC00_AA901_ZA01 01SCC00_AA901_ZA11 Dewater Main Valve AUTO OPEN ORD
Ini:0 (N-OPNG) IN1 Ini:
S:SFC
OPENING
IN2
01SCC00_AA901_RI01
3
2 TP
01CJA00_EU001_ZG41 AND TON_R
UNIT GC STATE 01CJA00_EU001_ZG41
Ini:0 (NO) IN1 IN REB
S:SFC 01MEA41_CP505_ZH06
YES
IN2 RET
01MEA41_CP505_ZH06
RUNNER DEWATER OPEN MAIN VALVE LEVEL -3.7m
Ini: Condensor Pressure not too low
S:CON
DETECTED
01SCC00_AA901_RI01
5
4 TP 6
AND TON_R OR 01SCC00_AA901_ZA12
01MEA41_CP505_ZH03
01CJA00_EU001_ZG41 01SCC00_AA901_ZA12 Dewater Main Valve AUTO CLOSE ORD
IN1 IN REB IN1 Ini:
RUNNER DEWATER LEVEL LOW -4.8m 01MEA41_CP505_ZH03 01SCC00_AA901_ZA02
Ini: IN2 RET IN2
S:CON
V-LOW
01SCC00_AA901_ZA02
Dewater Main Valve AUTO CLOSE ORDER
Ini:0 (N-CLSG)
S:SFC...
CLOSING
9
8 IV
01SCC00_AA901_ZA11 FB_VA2 RS 01SCC00_AA901_YL01
Dewater Main Valve AUTO OPEN ORD 01SCC00_AA901_ZA11 01SCC00_AA901_YL01
CONDENDSOR DEWATER MAIN VALVE
Ini: OP_A OR1 S Q1 Ini:
S:AA901 OPEN
OP_M DS1 R1 /Q1
01SCC00_AA901_ZC01
OP_A_ATH
01SCC00_AA901_ZJ01
01SCC00_AA901_XG01 OP_M_ATH
CONDENDSOR DEWATER MAIN VALVE 01SCC00_AA901_XG01 01SCC00_AA901_ZM11
Ini: OP_PS TLTE1
IO:L01_02 Rack:0 Slot:ST9 (X20DI9371) Point:7 01SCC00_AA901_XG01_V
OPEN OP_PS_V
01SCC00_AA901_ZA12
01SCC00_AA901_ZA12 CL_A OR2
Dewater Main Valve AUTO CLOSE ORD
Ini: CL_M DS2
S:AA901 01SCC00_AA901_ZC02
CL_A_ATH
01SCC00_AA901_ZJ02
CL_M_ATH
01SCC00_AA901_ZG02
01SCC00_AA901_ZG02 01SCC00_AA901_ZM12
CL_PS TLTE2
DEWATER MAIN VALVE AA901 not OPEN Delay
Ini: CL_PS_V
S:CON
DETECTED 01SCC00_AA901_ZM10
01SCC00_AA901_ZM00 01SCC00_AA901_ZM10 Dewater Main Valve AA901
FLT_IN ALARM Ini:
01SCC00_AA901_ZM50
AV REM_ATH ALARM
0
MANU
01SCC00_AA901_ZT11 : 1200
TLTE_OP
01SCC00_AA901_ZT12 : 1200
1 TLTE_CL
01SCC00_AA901_ZT01 : 1000
01SCC00_AA901_XG21 AND OP_PL 01SCC00_AA901_ZU01
CONDENDSOR DEWATER MAIN VALVE 01SCC00_AA901_XG21 01SCC00_AA901_ZT02 : 1000 01SCC00_AA901_ZU01 DEWATER MAIN VALVE ANIMATION WORD
Ini: IN1 CL_PL SIG Ini:
IO:L01_02 Rack:0 Slot:ST9 (X20DI9371) Point:6 1 01SCC00_AA901_ZT00 : 500 01SCC00_AA901_ZU01_V
IN2 F_TP SIG_V 0/127
AUTO
Type
1 2
01MEA41_CP505_XQ01 MOVE THR_HL
DRAFT TUBE DEWATER LEVEL IN CONDENSOR -3.5/-5.0m 01MEA41_CP505_XQ01 01MEA41_CP505_ZH03_V
Unit: mm IN RE IN Hi2_V
IO:L01_01 Rack:0 Slot:ST19 (X20AI4632) Point:1 01MEA41_CP505_ZH04_V
6553/32767 (0/2000 mm)
Val Hi1_V
01MEA41_CP505_ZH06_V
Vus Lo1_V
01MEA41_CP505_ZW10 01MEA41_CP505_ZH07_V
Hys Lo2_V
01MEA41_CP505_ZW13 01MEA41_CP505_ZH03
LOW 2 THRESHOLD SP 01MEA41_CP505_ZW13 01MEA41_CP505_ZH03 RUNNER DEWATER LEVEL LOW -4.8m
Ini:23592 (1299.99 mm) H2_Thr Hi2 Ini:
01MEA41_CP505_ZW14 01MEA41_CP505_ZH04
6553/32767 (0/2000 mm)
H1_Thr Hi1 V-LOW
01MEA41_CP505_ZW16 01MEA41_CP505_ZH06
L1_Thr Lo1
01MEA41_CP505_ZW14 01MEA41_CP505_ZW17 01MEA41_CP505_ZH07
L2_Thr Lo2 01MEA41_CP505_ZH04
LOW 1 THRESHOLD SP RUNNER DEWATER AIR INJECTION LEVEL -4.4m
Ini:18349 (899.98 mm) Ini:
DETECTED
6553/32767 (0/2000 mm)
01MEA41_CP505_ZW16 01MEA41_CP505_ZH06
HIGH 1 THRESHOLD SP RUNNER DEWATER OPEN MAIN VALVE LEVEL -3.7m
Ini:9174 (199.97 mm) Ini:
DETECTED
6553/32767 (0/2000 mm)
01MEA41_CP505_ZW17 01MEA41_CP505_ZH07
HIGH 1 THRESHOLD SP RUNNER DEWATER HIGH LEVEL TO GE -3.5m
Ini:6700 (11.22 mm) Ini:0 (N-DET)
DETECTED
6553/32767 (0/2000 mm)
01SCC00_EA001_ZS010
10 11
01SCC00_EU001_ZA01 AND AND 01SCC00_EA001_ZS015
RUNNER DEWATER REQUEST 01SCC00_EU001_ZA01 01SCC00_EA001_ZS015 DEWATER SEQUENCE STEP1 COND
Ini: IN1 IN1 Ini:
S:SFC 01SCC00_AA901_XG01 1
IN2 IN2 CORRECT
DETECTED 01SCC00_AA902_XG01
IN3
01SCC00_AA901_XG01 1
CONDENDSOR DEWATER MAIN VALVE IN4
Ini:
IO:L01_02 Rack:0 Slot:ST9 (X20DI9371) Point:7
OPEN CODENSOR HP Pressure OK
01SCC00_AA902_XG01
CONDENDSOR DEWATER AUXILIARY VALVE
Ini:
IO:L01_02 Rack:0 Slot:ST9 (X20DI9371) Point:11
OPEN
01SCC00_EA001_CONRI01 : 1.00000
4
3 TP 7 01SCC00_EA001_ZS030
12
01MEA41_CP505_ZH03 OR OR AND 01SCC00_EA001_ZS035
RUNNER DEWATER LEVEL LOW -4.8m 01MEA41_CP505_ZH03
TON_R 01SCC00_EU001_ZH03 01SCC00_EA001_ZS035DEWATER SEQUENCE STEP3 COND
Ini: IN1 IN REB IN1 IN1 Ini:
S:CON 0 1
IN2 RET IN2 IN2 CORRECT
V-LOW
01SCC00_EA001_CONRI02 : 240.00000
5
TP
01BBA00_DE001_ZH04
G->GC DEWATER ACTIVE POWER 01BBA00_DE001_ZH04
TON_R
Ini:0 (N-REACHD) IN REB
S:FE001
REACHED RET
01SCC00_EU001_ZH03
DEWATER WATER LEVEL or ACTIVE POWER
Ini:0 (N-REACHD)
S:CON
REACHED
01SCC00_EA001_CONRI03
6
TP 01SCC00_EA001_ZS040
13 14
01SCC00_AA901_XG01 AND AND 01SCC00_EA001_ZS045
CONDENDSOR DEWATER MAIN VALVE TON_R
01SCC00_AA901_XG01 01SCC00_AA901_ZG02 01SCC00_EA001_ZS045DEWATER SEQUENCE STEP4 COND
Ini: IN REB IN1 IN1 Ini:
IO:L01_02 Rack:0 Slot:ST9 (X20DI9371) Point:7 01SCC00_EU001_ZG01 1
RET IN2 IN2 CORRECT
OPEN
01SCC00_EU001_ZG01
RUNNER DEWATER STATE
Ini:
S:SFC...
DETECTED
01SCC00_EA002_ZS010
7 8
01SCC00_EU001_ZA02 AND AND 01SCC00_EA002_ZS015
RUNNER REWATER REQUEST 01SCC00_EU001_ZA02 01SCC00_EA002_ZS015 REWATER SEQUENCE STEP1 COND
Ini: IN1 IN1 Ini:
S:SFC... 1 1
DETECTED
IN2 IN2 CORRECT
01SCC00_EA002_ZS020
9 10
01SCC00_AA901_ZG02 AND AND 01SCC00_EA002_ZS025
DEWATER MAIN VALVE AA901 not OPEN Delay 01SCC00_AA901_ZG02 01SCC00_EA002_ZS025 REWATER SEQUENCE STEP2 COND
Ini: IN1 IN1 Ini:
S:CON 01SCC00_AA902_ZG02 1
DETECTED
IN2 IN2 CORRECT
01SCC00_EA002_CON_T01
2
TP
01SCC00_AA902_XG01
CONDENDSOR DEWATER AUXILIARY VALVE
TON_R
01SCC00_AA902_XG01 01SCC00_AA902_ZG02
Ini: IN REB
IO:L01_02 Rack:0 Slot:ST9 (X20DI9371) Point:11
OPEN RET
1
SEL
01CJA00_EU001_ZA01
G RE
01SCC00_EA002_CONRI03 : 2.00000
IN1
01SCC00_EA002_CONRI01 : 5.00000
IN2
4
3 TP 6 01SCC00_EA002_ZS030
11
01MEA41_CP505_ZH07 OR TON_R OR AND 01SCC00_EA002_ZS035
RUNNER DEWATER HIGH LEVEL TO GE -3.5m 01MEA41_CP505_ZH07 01SCC00_EU001_ZH07 01SCC00_EA002_ZS035REWATER SEQUENCE STEP3 COND
Ini:0 (N-DET) IN1 IN REB IN1 IN1 Ini:
S:CON 0 1
IN2 RET IN2 IN2 CORRECT
DETECTED
01SCC00_EA002_CONRI02 : 1.00000
5
TP
01BBA00_DE001_ZH07
REWATER STAGE ACTIVE POWER REACHED
TON_R
01BBA00_DE001_ZH07
Ini:0 (N-DET) IN REB
S:FE001
DETECTED RET
01SCC00_EU001_ZH07
REWATER WATER LEVEL or ACTIVE POWER
Ini:0 (N-REACHD)
S:CON
REACHED
01SCC00_EA002_ZS040
12 13
01SCC00_EU001_ZG02 AND AND 01SCC00_EA002_ZS045
RUNNER REWATER STATE 01SCC00_EU001_ZG02 01SCC00_EA002_ZS045REWATER SEQUENCE STEP4 COND
Ini: IN1 IN1 Ini:
S:SFC... 1 1
IN2 IN2 CORRECT
DETECTED
1
MOVE_B 01CJA00_EA073_ZS011
01CJA00_EA073_SFC_S1_X 01CJA00_EA073_ZS011 EA073 STEP1
IN RE Ini:
IN-PROGR
2
MOVE_B 01CJA00_EA073_ZS021
01CJA00_EA073_SFC_S2_X 01CJA00_EA073_ZS021 EA073 STEP2
IN RE Ini:
IN-PROGR
11
01CJA00_EA100_ZG21 AND 01CJA00_EA073_ZM01
UNIT LCU AUTO MODE 01CJA00_EA100_ZG21 01CJA00_EA073_ZM01
SQ73:SE->GE SEQ OVERTIME
Ini: IN1 Ini:
S:CON PRESENCE
SELECTED
01CJA00_EA073_ZT01 10 IN2
7 8
6 TP TP
AND TON_D TOF_R
5
01CJA00_EA100_ZG21
OR IN1 IN REB IN REB
3
01CJA00_EA073_ZG01
01CJA00_EA073_ZG01 F_TRIG IN1 IN2 RET RET
SQ73:SE->GE SEQ 01CJA00_EA073_ZG01
Ini: IN RE IN2
S:SFC...
IN-PROGR 9 10
OR SEL 01CJA00_EA073_ZQ01
4
01CJA00_EA073_ZG01 01CJA00_EA073_ZQ01
01CJA00_EU001_ZG01 F_TRIG SQ73:SE->GE SEQ TIME COUNTER
IN1 G RE Ini:0 (0 s)
UNIT STILL STOP STATE 01CJA00_EU001_ZG01 01CJA00_EA073_ZQ01
Ini:0 (NO) IN RE IN2 IN1 0/360000 (0/3600 s)
S:SFC
YES IN2
1 2 9
01BBA00_FE001_RQ45 ADD ABS LE 01BBA00_FE001_ZQ45
UNIT FREQUENCE 01BBA00_FE001_RQ45 01BBA00_FE001_ZQ45
UNIT / GRID FREQUENCY DEVIATION OK
Unit: Hz IN1 IN IN1 RE Ini:
EXT:L01_r5_2_0EX'ModbusClientInW Point:104 81ADD01_FE001_RQ45 01CJA00_EA073_II01
0/60 (0/60 Hz)
IN2 IN2 DETECTED
81ADD01_FE001_RQ45
1# MT HV SIDE 231 FREQUENCE
Unit: Hz
EXT:L06_r5_2_0EX'ModbusClientInW Point:104
0/60 (0/60 Hz)
01CJA00_EA073_ZS010
3 4
01CJA00_EU001_ZM21 AND AND 01CJA00_EA073_ZS015
SWITCHYARD CONDITIONS FOR GENERATING 01CJA00_EU001_ZM21 01CJA00_EA073_ZS015
Ini:0 (UNAVLBL) IN1 IN1 Ini:
S:CON 01CJA00_EP001_ZM04 01CJA00_EA100_ZA51
AVLBL
IN2 IN2 CORRECT
01MEU11_FS001_XH05
IN3
01CJA00_EP001_ZM04 01MEU11_FS001_ZM51
UNIT SYNCHRONIZER OK / SELF SYNCHRONIZE MODE IN4
Ini:0 (N-DET)
01MKC65_CS101_ZG01
IN5
S:CON 01BBA00_DE003_ZH17
DETECTED IN6
01MEU11_FS001_XH05
RV05 >95% SYNCHRONISATION LAUNCH
Ini:
IO:L01_01 Rack:0 Slot:ST11 (X20DI9371) Point:2
DETECTED
01MEU11_FS001_ZM51
GOVERNOR T-ADT MEASUREMENT
Ini:0 (FAULT)
S:EU001
NORMAL
01MKC65_CS101_ZG01
EXCIT FIELD BREAKER CLOSED or SELF SYNCHRONIZE STARTING
Ini:
S:CON
DETECTED
01BBA00_DE003_ZH17
UNIT VOLTAGE >95%Un or SELF SYNCHRONIZE STARTING
Ini:
S:CON
DETECTED
01CJA00_EA073_ZS020
5 6
AND AND 01CJA00_EA073_ZS025
01MKC65_GS101_XG01
01MEU11_FS001_XH05 01CJA00_EA073_ZS025
IN1 IN1 Ini:
EXCIT FIELD BREAKER CLOSED 01MKC65_GS101_XG01 1
Ini: IN2 IN2 CORRECT
IO:L01_01 Rack:0 Slot:ST8 (X20DI9371) Point:4 01BBA00_DE003_ZH07
DETECTED
IN3
01BAC00_GS901_XG01
IN4
01BBA00_DE003_ZH07
UNIT VOLTAGE >95%Un
Ini:0 (N-DET)
S:FE001
DETECTED
01BAC00_GS901_XG01
UNIT GCB GS901 IN CLOSED POSTION
Ini:
IO:L01_01 Rack:0 Slot:ST5 (X20DI9371) Point:1
DETECTED
01CJA00_EA073_ZS030
7 8
01BBA00_DE001_ZH03 AND AND 01CJA00_EA073_ZS035
UNIT ACTIVE POWER > MINIMAL 01BBA00_DE001_ZH03 01CJA00_EA073_ZS035
Ini:0 (N-DET) IN1 IN1 Ini:
S:FE001 1 1
IN2 IN2 CORRECT
DETECTED
ACTIVE POWER>MIN
20
01CJA00_EU001_ZG00 FB_UNIT_STA 01CJA00_EU001_ZU01
UNIT INIT STOP STATE 01CJA00_EU001_ZG00 01CJA00_EU001_ZU01 UNIT STATE VALUE WORD
Ini:0 (NO) INI_ST U_STA Ini:
S:SFC 01CJA00_EU001_ZM03 01CJA00_EU001_ZU01_V
YES ES_RQ ERR 0/127
01CJA00_EU001_ZU02
U_CLR
01CJA00_EU001_ZM03 QS_RQ
UNIT EMERG STOP REQ 01CJA00_EU001_ZG01
Ini:0 (N-REQ) SS_ST
S:CON
REQ
1 NS_RQ
AND 01CJA00_EU001_ZG11
TS_ST
01CJA00_EU001_ZM02 IN1 01CJA00_EU001_ZJ11
UNIT MECH STOP REQ 01CJA00_EU001_ZM02 TS_RQ
IN2 01CJA00_EU001_ZG21
Ini:0 (N-REQ) SR_ST
S:CON
REQ SR_RQ
01CJA00_EU001_ZG31
01CJA00_EU001_ZG01
GE_ST
UNIT STILL STOP STATE GE_RQ
Ini:0 (NO) 2 01CJA00_EU001_ZG41
S:SFC GC_ST
AND
YES 01CJA00_EU001_ZM03 GC_RQ
IN1 01CJA00_EU001_ZG61
01CJA00_EU001_ZM01
01CJA00_EU001_ZM02 LC_ST
IN2
UNIT NORMAL STOP REQ 01CJA00_EU001_ZM01 LC_RQ
Ini:0 (N-REQ) IN3
S:CON PU_ST
REQ PU_RQ
01CJA00_EU001_ZG11 replaced LA by SE in TRIAN project, remmeber to change the LA to SE in static PC_ST
UNIT TS STATE
Ini:0 (NO) 8 PC_RQ
01CJA00_EU001_ZG71
S:SFC... AND LA_ST
YES 01CJA00_EU001_ZJ11
IN1 LA_RQ
01CJA00_EU001_ZJ11
01CJA00_EU001_ZJ71 01CJA00_EU001_ZG51
IN2 BS_ST
UNIT TS STATE
Ini: BS_RQ
S:CON
REQ
01CJA00_EU001_ZG21
UNIT SR STATE
Ini:0 (NO)
S:SFC
3
YES
AND
01CJA00_EU001_ZJ11
01CJA00_EU001_ZJ21 IN1
UNIT SR STATE 01CJA00_EU001_ZJ21
Ini: IN2
S:CON
REQ
01CJA00_EU001_ZG31
UNIT GE STATE
Ini:0 (NO)
S:SFC
YES
4
AND
01CJA00_EU001_ZJ11
01CJA00_EU001_ZJ31 IN1
UNIT GE STATE 01CJA00_EU001_ZJ31
Ini: IN2
S:CON
REQ
01CJA00_EU001_ZG41
UNIT GC STATE
Ini:0 (NO)
S:SFC
5
YES
AND
01CJA00_EU001_ZJ11
01CJA00_EU001_ZJ41 IN1
UNIT GC STATE 01CJA00_EU001_ZJ41
Ini: IN2
S:CON
REQ
01CJA00_EU001_ZG61
UNIT CH STATE
Ini:0 (NO)
S:SFC
YES
6
AND
01CJA00_EU001_ZJ11
01CJA00_EU001_ZJ61 IN1
UNIT CH STATE 01CJA00_EU001_ZJ61
Ini: IN2
S:CON
REQ
01CJA00_EU001_ZG51
UNIT BS STATE
Ini:0 (NO)
S:SFC
7
YES
AND
01CJA00_EU001_ZJ51
01CJA00_EU001_ZJ11
IN1
UNIT BS STATE 01CJA00_EU001_ZJ51
Ini: IN2
S:CON
REQ
10
NOT 01MKA54_EG901_YL01
01MKA54_EG901_YL02 01MKA54_EG901_YL01 UNIT IS IN OPERATION FOR DOOM LIGHT
IN Ini:
ON
11
01CJA00_EU001_ZG01 MOVE_B 01CJA00_EG001_YG01
UNIT STILL STOP STATE 01CJA00_EU001_ZG01 01CJA00_EG001_YG01 UNIT STANDSTILL-SS STATE
Ini:0 (NO) IN RE Ini:
S:SFC ON
YES
12
01CJA00_EU001_ZG11 MOVE_B 01CJA00_EG002_YG01
UNIT TS STATE 01CJA00_EU001_ZG11 01CJA00_EG002_YG01 UNIT STANDBY-SB STATE
Ini:0 (NO) IN RE Ini:
S:SFC... ON
YES
13
01CJA00_EU001_ZG21 MOVE_B 01CJA00_EG003_YG01
UNIT SR STATE 01CJA00_EU001_ZG21 01CJA00_EG003_YG01 UNIT SPIN RESEVER WITHOUT EXC-SR STATE
Ini:0 (NO) IN RE Ini:
S:SFC ON
YES
14
01CJA00_EU001_ZG31 MOVE_B 01CJA00_EG005_YG01
UNIT GE STATE 01CJA00_EU001_ZG31 01CJA00_EG005_YG01 UNIT GENERATING-GE STATE
Ini:0 (NO) IN RE Ini:
S:SFC ON
YES
15
01CJA00_EU001_ZG41 MOVE_B 01CJA00_EG006_YG01
UNIT GC STATE 01CJA00_EU001_ZG41 01CJA00_EG006_YG01 UNIT GENERATING CONDENSOR-GC STATE
Ini:0 (NO) IN RE Ini:
S:SFC ON
YES
16
01CJA00_EU001_ZG71 MOVE_B 01CJA00_EG004_YG01
UNIT SE-SPIN EXCITATION STATE 01CJA00_EU001_ZG71 01CJA00_EG004_YG01 UNIT SPIN WITH EXCITATION-SE STATE
Ini: IN RE Ini:
S:SFC ON
YES
17
01CJA00_EU001_ZG61 MOVE_B 01CJA00_EG007_YG01
UNIT CH STATE 01CJA00_EU001_ZG61 01CJA00_EG007_YG01 UNIT LINE CHARGING-CH STATE
Ini:0 (NO) IN RE Ini:
S:SFC ON
YES
18
01CJA00_EU001_ZG01 OR 01CJA00_EU001_ZG10
UNIT STILL STOP STATE 01CJA00_EU001_ZG01 01CJA00_EU001_ZG10 UNIT IN SS/TS STATE
Ini:0 (NO) IN1 Ini:0 (N-DET)
S:SFC 01CJA00_EU001_ZG11
IN2 DETECTED
YES
01CJA00_EU001_ZG11
UNIT TS STATE
Ini:0 (NO)
S:SFC...
YES
01CJA00_EU001_ZJ41
UNIT GC STATE
Ini:
S:CON
REQ
01CJA00_EU001_ZG41
UNIT GC STATE
Ini:0 (NO)
S:SFC
YES
01CJA00_EA032_ZG01
SQ32:GE->SR SEQ
Ini:0 (N-PROGR)
S:SFC...
IN-PROGR
11
9 10 IV
01CJA00_EA100_ZL01 AND OR RS 01CJA00_EA100_ZG23
UNIT CONTROL MODE: LOCAL AUTO CMD 01CJA00_EA100_ZL01 01CJA00_EA100_ZG23 UNIT LCU LOCAL AUTO MODE
Ini: IN1 IN1 S Q1 Ini:
HMI DB Number:19
SENT
IN2 IN2 R1 /Q1 SELECTED
01CJA00_EA100_ZK01
8
01CJA00_GH001_XL32 AND
LCU CONTROL LEVEL IN LOCAL 01CJA00_GH001_XL32
Ini: IN1
IO:L01_01 Rack:0 Slot:ST4 (X20DI9371) Point:0 01CJA00_GH001_XL33
DETECTED
IN2
01CJA00_GH001_XL33 3
LCU OPERATION LOCKED R_TRIG
Ini: 01CJA00_GH001_XL32
IO:L01_01 Rack:0 Slot:ST4 (X20DI9371) Point:2 IN RE
DETECTED
7
01CJA00_GH001_XL31 OR
LCU CONTROL LEVEL IN REMOTE 01CJA00_GH001_XL31
Ini: IN1
IO:L01_01 Rack:0 Slot:ST4 (X20DI9371) Point:1
DETECTED
IN2
23
6 IV
01CJA00_EA100_ZL02 AND RS 01CJA00_EA100_ZG22
UNIT CONTROL MODE: STEP BY STEP 01CJA00_EA100_ZL02 01CJA00_EA100_ZG22 UNIT STEP BY STEP MODE
Ini: IN1 S Q1 Ini:
HMI DB Number:19
SENT IN2 R1 /Q1 SELECTED
01CJA00_EA100_ZK02
5
AND
01CJA00_GH001_XL32
IN1 22
01CJA00_GH001_XL33 OR
IN2
IN1
01CJA00_GH001_XL31
IN2
12
OR 01CJA00_EA100_ZG21
01CJA00_GH001_XL31 01CJA00_EA100_ZG21 UNIT LCU AUTO MODE
01CJA00_EA100_ZG23 IN1
UNIT LCU LOCAL AUTO MODE 01CJA00_EA100_ZG23 Ini:
Ini: IN2 SELECTED
S:CON
SELECTED
14
13 TP 26
01CJA00_EA100_ZL51 AND TP_R OR 01CJA00_EA100_ZA51
NEXT STEP CMD 01CJA00_EA100_ZL51 01CJA00_EA100_ZG51 01CJA00_EA100_ZA51STEP MODE CONDITION
Ini: IN1 IN REB IN1 Ini:
HMI DB Number:19 01CJA00_EA100_ZG21 01CJA00_EA100_ZG21
SENT
IN2 RET IN2
01CJA00_EU001_ZM02
IN3
01CJA00_EU001_ZM03
IN4
01CJA00_EA100_ZG21
UNIT LCU AUTO MODE
Ini:
S:CON
SELECTED
01CJA00_EU001_ZM02
UNIT MECH STOP REQ
Ini:0 (N-REQ)
S:CON
REQ
01CJA00_EU001_ZM03
UNIT EMERG STOP REQ
Ini:0 (N-REQ)
S:CON
REQ
01CJA00_EU001_ZM05
UNIT MECH STARTING CONDITION
Ini:
S:CON
ESTABL
01CJA00_EU001_ZM06
UNIT PERMANENT START CONDITION
Ini:
S:CON
ESTABL
01CJA00_EU001_ZM21
SWITCHYARD CONDITIONS FOR GENERATING
Ini:0 (UNAVLBL)
S:CON
AVLBL
81
01CJA00_EA027_ZL01 AND
SR->SE CMD 01CJA00_EA027_ZL01
Ini: IN1
HMI DB Number:19 01CJA00_EA027_ZK01
SENT 80 IN2
AND
01CJA00_EU001_ZG21 01CJA00_EU001_ZM06
IN1
UNIT SR STATE 01CJA00_EU001_ZG21
Ini:0 (NO) IN2
S:SFC 01CJA00_EU001_ZM21
YES IN3
77
01CJA00_EU001_ZA01 OR
ANY UNIT STOP CMD 01CJA00_EU001_ZA01
Ini:0 (N-REQ) IN1
S:CON 01CJA00_EU001_ZG71
REQ IN2
01CJA00_EU001_ZG71
UNIT SE-SPIN EXCITATION STATE
Ini:
S:SFC
YES
01CJA00_EP002_XM51
GCB SYN. CHECK RELAY READY FOR OPERATION
Ini:
IO:L01_01 Rack:0 Slot:ST4 (X20DI9371) Point:7
DETECTED
01CJA00_GS110_XM51
24VDC DEVICE POWER SUPPLY(2W1+) 01CJA00_EP001_ZK22
28
Ini: AND
IO:L01_01 Rack:0 Slot:ST2 (X20DI9371) Point:9 01CJA00_GS110_XM51
PRESENCE IN1
01CJA00_EP002_XM51
IN2
01CJA00_EA100_ZG22 01CJA00_EP001_XM51
IN3
UNIT STEP BY STEP MODE 01CJA00_EA100_ZG22
Ini: IN4
S:CON 01CJA00_GH003_ZG22
SELECTED IN5
4
01CJA00_GH003_XL22 OR
SYNCHRONIZING MODE IN MANU 01CJA00_GH003_XL22
Ini: IN1
IO:L01_01 Rack:0 Slot:ST4 (X20DI9371) Point:5 01CJA00_GH003_XL23
DETECTED IN2
01CJA00_GH003_XL23 01CJA00_EU001_ZG14
SYNCHRONIZING MODE IN TEST UNIT IN SELF SYNCHRONIZE STARTING MODE
Ini: Ini:0 (N-DET)
IO:L01_01 Rack:0 Slot:ST4 (X20DI9371) Point:6 S:GS901
DETECTED DETECTED
01CJA00_EA000_CON_E01
LCU1 & 3 S8000 NOT CONNECTED
Ini:0 (NO)
YES 15
SEL_B 01CJA00_EU001_ZM21
81CBC00_01CJA_GE01 01CJA00_EA000_CON_E01 01CJA00_EU001_ZM21 SWITCHYARD CONDITIONS FOR GENERATING
G RE Ini:0 (UNAVLBL)
SWITCHYARD CONDITIONS FOR UNIT 1 GENERATING 81CBC00_01CJA_GE01
Ini: IN1 AVLBL
S:EU001 1
AVLBL IN2
16
SEL_B 01CJA00_EU001_ZM22
81CBC00_01CJA_LC01 01CJA00_EA000_CON_E01 01CJA00_EU001_ZM22 SWITCHYARD CONDITIONS FOR LINE CHARGING
G RE Ini:0 (UNAVLBL)
SWITCHYARD CONDITIONS FOR UNIT 1 LINE CHARGE 81CBC00_01CJA_LC01
Ini: IN1 AVLBL
S:EU001 1
AVLBL IN2
17
SEL_B 01CJA00_EU001_ZM23
81CBC00_01CJA_BS01 01CJA00_EA000_CON_E01 01CJA00_EU001_ZM23 SWITCHYARD CONDITIONS FOR BLACK START
G RE Ini:0 (UNAVLBL)
SWITCHYARD CONDITIONS FOR UNIT 1 BLACK START 81CBC00_01CJA_BS01
Ini: IN1 AVLBL
S:EU001 1
AVLBL IN2
18
SEL_B 01CJA00_EE101_ZG01
50CBD01_EE101_XG01 01CJA00_EA000_CON_E02 01CJA00_EE101_ZG01 INTAKE GATE FULLY OPEN
G RE Ini:0 (N-DET)
INTAKE GATE1 FULLY OPEN(8M) 50CBD01_EE101_XG01
Ini: IN1 DETECTED
IO:L08_01 Rack:0 Slot:ST5 (X20DI9371) Point:5 1
DETECTED IN2
19
SEL_B 01CJA00_EE101_ZM01
50CBD01_EE101_ZH04 01CJA00_EA000_CON_E02 01CJA00_EE101_ZM01 INTAKE GATE DROP DOWN 7.1m
G RE Ini:0 (N-DET)
INTAKE GATE1 DROP DOWN 7.1m 50CBD01_EE101_ZH04
Ini: IN1 DETECTED
S:EE101 0
DETECTED IN2
421/1(+1p)
25
AND 01CJA00_EU001_ZM05
24 1 01CJA00_EU001_ZM05UNIT MECH STARTING CONDITION
01MEU11_EU001_ZM05 AND IN1
GOVERNOR SYSTEM STARTING COND 01MEU11_EU001_ZM05 Ini:
Ini:0 (N-READY) IN1 IN2 ESTABL
S:EU001 01MAU24_EU014_ZM05
READY IN2
01MKA54_EU001_ZM05
IN3
01MAU24_EU014_ZM05 01MEA41_AU001_ZM05
GOV OIL STATION STARTING COND IN4
Ini:0 (N-READY)
01CVA00_EU001_ZM05
IN5
S:EU014 01CMA00_EU001_ZM05
READY IN6
01PAC00_EU001_ZM05
01MKA54_EU001_ZM05 IN7
Generator Auxilaries STARTING COND
Ini:0 (N-READY)
S:AU001
READY
01MEA41_AU001_ZM05
Turbine Auxilaries STARTING COND
Ini:0 (N-READY)
S:AU001
READY
01CVA00_EU001_ZM05
TEMP MEASURE SYS MECHANICAL STARTING COND
Ini:
S:FT001
READY
01CMA00_EU001_ZM05
UNIT ONLINE MONITORING STARTING COND
Ini:0 (N-READY)
S:EU001
READY
01PAC00_EU001_ZM05
UNIT CLW SYSTEM STARTUP CONDITIONS
Ini:0 (N-DET)
S:AA001
DETECTED
21
SEL_B 01CJA00_CP001_ZH06
20SCC01_CP001_ZH06
01CJA00_EA000_CON_E03 01CJA00_CP001_ZH06 PRESSURES OF COMPENSATED COMPRESSED AIR TANK REACHED
G RE Ini:
PRESSURES OF COMPENSATED COMPRESSED AIR TANK REACHED 20SCC01_CP001_ZH06
Ini: IN1 DETECTED
S:EU001 1
DETECTED IN2
01CJA00_EU001_ZK04
30 32
01CJA00_EP001_ZM04 AND AND 01CJA00_EU001_ZM04
UNIT SYNCHRONIZER OK / SELF SYNCHRONIZE MODE 01CJA00_EP001_ZM04 01CJA00_EU001_ZM04 UNIT ELEC STARTING CONDITION
Ini:0 (N-DET) IN1 IN1 Ini:
S:CON 01CJA00_FE001_ZM02
IN2 IN2 ESTABL
DETECTED
01CJA00_FE001_ZM02
MFC3000 vs FE001 MOD EXCHANGE
Ini:0 (ABSENCE)
S:EU101
PRESENCE
31
01MKC65_EU001_ZM04 AND
EXCITATION SYSTEM STARTING COND 01MKC65_EU001_ZM04
Ini:0 (N-READY) IN1
S:EU001 01BAC00_EU001_ZM04
READY IN2
01BAT00_EU001_ZM04
IN3
01BAC00_EU001_ZM04 01CHA00_PT001_ZM04
IN4
UNIT GCB SWITCHBOARD STARTING COND
Ini:0 (N-READY)
S:GS901
READY
01BAT00_EU001_ZM04
MAIN TRANSFORMER SYSTEM STARTING COND
Ini:0 (N-READY)
S:PT001
READY
01CHA00_PT001_ZM04
Generator Protection ELECTRICAL STARTING COND
Ini:0 (N-READY)
S:PT001
READY
01CJA00_GS011_XM51
220VDC MEASUR DEVICES POWER SUPPLY(5W1+)
Ini:
IO:L01_01 Rack:0 Slot:ST3 (X20DI9371) Point:3
PRESENCE
01CJA00_GS012_XM51
220VDC EMERGENCY TRIP POWER SUPPLY(5E1+)
Ini:
IO:L01_01 Rack:0 Slot:ST3 (X20DI9371) Point:10
PRESENCE
01CJA00_GS109_XM51
24VDC CONTROL POWER SUPPLY(2C1+)
Ini:
IO:L01_01 Rack:0 Slot:ST2 (X20DI9371) Point:8
PRESENCE
01CJA00_GS110_XM51
24VDC DEVICE POWER SUPPLY(2W1+)
Ini:
IO:L01_01 Rack:0 Slot:ST2 (X20DI9371) Point:9
PRESENCE
39
37 38 IV
01CJA00_EA010_ZL01 AND OR 01CJA00_EU001_ZJ11
SS->TS CMD1 01CJA00_EA010_ZL01
RS 01CJA00_EU001_ZJ11 UNIT TS STATE
Ini: IN1 IN1 S Q1 Ini:
HMI DB Number:19 0
IN2 IN2 R1 /Q1 REQ
SENT
01CJA00_EA010_ZK01
36
01CJA00_EU001_ZG01 AND
UNIT STILL STOP STATE 01CJA00_EU001_ZG01
Ini:0 (NO) IN1
S:SFC 01CJA00_EU001_ZM04
YES IN2
01CJA00_EU001_ZM05
IN3
01CJA00_EU001_ZM04 01CJA00_EU001_ZM06
UNIT ELEC STARTING CONDITION IN4
Ini:
S:CON
ESTABL
01CJA00_EU001_ZM05
UNIT MECH STARTING CONDITION
Ini:
S:CON
ESTABL
01CJA00_EU001_ZM06
UNIT PERMANENT START CONDITION
Ini:
S:CON
ESTABL
35
01CJA00_EU001_ZA01 OR
ANY UNIT STOP CMD 01CJA00_EU001_ZA01
Ini:0 (N-REQ) IN1
S:CON 01CJA00_EU001_ZG11
REQ IN2
01CJA00_EU001_ZG11
UNIT TS STATE
Ini:0 (NO)
S:SFC...
YES
01CJA00_EU001_ZK21
61
01CJA00_EU001_ZG10 AND
UNIT IN SS/TS STATE 01CJA00_EU001_ZG10
Ini:0 (N-DET) IN1
S:STA 01CJA00_EU001_ZM04
DETECTED IN2
01CJA00_EU001_ZM05
IN3
01CJA00_EU001_ZM04 01CJA00_EU001_ZM06
UNIT ELEC STARTING CONDITION IN4
Ini:
01CJA00_EU001_ZM21
IN5
S:CON
ESTABL
01CJA00_EU001_ZM05
UNIT MECH STARTING CONDITION
Ini:
S:CON
ESTABL
01CJA00_EU001_ZM06
UNIT PERMANENT START CONDITION
Ini:
S:CON
ESTABL
01CJA00_EU001_ZM21
SWITCHYARD CONDITIONS FOR GENERATING
Ini:0 (UNAVLBL)
S:CON
AVLBL
64
01CJA00_EA032_ZL01 AND
GE->SR CMD 01CJA00_EA032_ZL01
Ini: IN1
HMI DB Number:19
01CJA00_EA032_ZK01
63 IN2
SENT
AND
01CJA00_EU001_ZG31
01CJA00_EU001_ZM06
IN1
UNIT GE STATE 01CJA00_EU001_ZG31
Ini:0 (NO) IN2
S:SFC
YES
60
01CJA00_EU001_ZA01 OR
ANY UNIT STOP CMD 01CJA00_EU001_ZA01
Ini:0 (N-REQ) IN1
S:CON 01CJA00_EU001_ZG21
REQ IN2
01CJA00_EU001_ZG21
UNIT SR STATE
Ini:0 (NO)
S:SFC
YES
01CJA00_EU001_ZM06
UNIT PERMANENT START CONDITION
Ini:
S:CON
ESTABL 40
01CJA00_EU001_ZA01 OR
01CJA00_EU001_ZM21 ANY UNIT STOP CMD 01CJA00_EU001_ZA01
SWITCHYARD CONDITIONS FOR GENERATING Ini:0 (N-REQ) IN1
Ini:0 (UNAVLBL) S:CON 01CJA00_EU001_ZG31
REQ IN2
S:CON
AVLBL
01CJA00_EU001_ZG31
01CJA00_EP001_ZM04 UNIT GE STATE
UNIT SYNCHRONIZER OK / SELF SYNCHRONIZE MODE Ini:0 (NO)
Ini:0 (N-DET) S:SFC
S:CON YES
DETECTED
44
01CJA00_EA073_ZL01 AND
SR/SE->GE CMD1 01CJA00_EA073_ZL01
Ini: IN1
HMI DB Number:19 01CJA00_EA073_ZK01
SENT 43 IN2
AND
01CJA00_EU001_ZM06
01CJA00_EU001_ZG21 IN1
01CJA00_EU001_ZM21
UNIT SR STATE IN2
Ini:0 (NO) 01CJA00_EP001_ZM04
S:SFC IN3
YES 01CJA00_EU001_ZG27
1 IN4
OR
01CJA00_EU001_ZG71
01CJA00_EU001_ZG21 01CJA00_EU001_ZG27
IN1
UNIT SE-SPIN EXCITATION STATE 01CJA00_EU001_ZG71
Ini: IN2 48
S:SFC AND
YES
IN1
01CJA00_EA034_ZK01
47 IN2
AND
01CJA00_EU001_ZM06
IN1
01CJA00_EA043_ZG41
IN2
2
01CJA00_EU001_ZG41 OR
UNIT GC STATE 01CJA00_EU001_ZG41 01CJA00_EA043_ZG41
Ini:0 (NO) IN1
S:SFC 01CJA00_EA043_ZG01
YES IN2
01CJA00_EA043_ZG01
SQ43: GE->GC SEQ
Ini:0 (N-PROGR)
S:SFC...
IN-PROGR
50 46
01CJA00_EA036_ZL01 AND 01CJA00_EA034_ZL01 OR
CH->GE CMD 01CJA00_EA036_ZL01 GC->GE CMD 01CJA00_EA034_ZL01
Ini: IN1 Ini: IN1
HMI DB Number:19 HMI DB Number:19
SENT 01CJA00_EA036_ZK01
49 IN2 SENT IN2
AND 45
WHAT ABOUT BS TO GE?????? 01CJA00_EU001_ZM06 01MEA41_CP505_ZH07
IN1 AND
01CJA00_EU001_ZM21 RUNNER DEWATER HIGH LEVEL TO GE -3.5m 01MEA41_CP505_ZH07
01CJA00_EU001_ZG61 IN2 Ini:0 (N-DET) IN1
UNIT CH STATE 01CJA00_EU001_ZG61 S:CON 01CJA00_EU001_ZG41
Ini:0 (NO) IN3 DETECTED IN2
S:SFC
YES
01CJA00_EU001_ZM06
UNIT PERMANENT START CONDITION
Ini:
S:CON
ESTABL
01CJA00_EU001_ZM21
SWITCHYARD CONDITIONS FOR GENERATING
Ini:0 (UNAVLBL)
S:CON
AVLBL
01CJA00_EP001_ZM04
UNIT SYNCHRONIZER OK / SELF SYNCHRONIZE MODE
Ini:0 (N-DET)
S:CON
DETECTED
57
01CJA00_EA043_ZL01 AND
GE->GC CMD 01CJA00_EA043_ZL01
Ini: IN1
HMI DB Number:19
SENT 01CJA00_EA043_ZK01
56 IN2
AND
01CJA00_EU001_ZG31
01CJA00_EU001_ZM06
IN1
UNIT GE STATE 01CJA00_EU001_ZG31
Ini:0 (NO) IN2
S:SFC 01SCC00_AA901_XG21
YES IN3
01SCC00_AA902_XL21
IN4
01SCC00_AA901_XG21 01CJA00_CP001_ZH06
IN5
CONDENDSOR DEWATER MAIN VALVE
Ini:
IO:L01_02 Rack:0 Slot:ST9 (X20DI9371) Point:6
AUTO
01SCC00_AA902_XL21
CONDENDSOR DEWATER AUXILIARY VALVE
Ini:
IO:L01_02 Rack:0 Slot:ST9 (X20DI9371) Point:10
AUTO
01CJA00_CP001_ZH06
PRESSURES OF COMPENSATED COMPRESSED AIR TANK REACHED
Ini:
S:CON
DETECTED
53
01CJA00_EU001_ZA01 OR
ANY UNIT STOP CMD 01CJA00_EU001_ZA01
Ini:0 (N-REQ) IN1
S:CON 01CJA00_EU001_ZG41
REQ IN2
01CJA00_EU001_ZG41
UNIT GC STATE
Ini:0 (NO)
S:SFC
YES
01CJA00_EU001_ZM05
UNIT MECH STARTING CONDITION
Ini:
S:CON
ESTABL
01CJA00_EU001_ZM06
UNIT PERMANENT START CONDITION
Ini:
S:CON
ESTABL
01CJA00_EU001_ZM22
SWITCHYARD CONDITIONS FOR LINE CHARGING
Ini:0 (UNAVLBL)
S:CON
AVLBL
67
01CJA00_EU001_ZA01 OR
ANY UNIT STOP CMD 01CJA00_EU001_ZA01
Ini:0 (N-REQ) IN1
S:CON 01CJA00_EU001_ZG61
REQ IN2
01CJA00_EU001_ZG61
UNIT CH STATE
Ini:0 (NO)
S:SFC
YES
BS CMD (RESERVED)
76
74 75 IV
01CJA00_EU001_ZL51 AND OR 01CJA00_EU001_ZJ51
UNIT BS CMD1 01CJA00_EU001_ZL51
RS 01CJA00_EU001_ZJ51
UNIT BS STATE
Ini: IN1 IN1 S Q1 Ini:
HMI DB Number:19 0
IN2 IN2 R1 /Q1 REQ
SENT
01CJA00_EU001_ZK51
73
01CJA00_EU001_ZG10
UNIT IN SS/TS STATE AND
Ini:0 (N-DET) 01CJA00_EU001_ZG10
IN1
S:STA 01CJA00_EU001_ZM04
DETECTED IN2
01CJA00_EU001_ZM05
01CJA00_EU001_ZM04 IN3
01CJA00_EU001_ZM06
UNIT ELEC STARTING CONDITION IN4
Ini: 01CJA00_EU001_ZM23
S:CON IN5
ESTABL
01CJA00_EU001_ZM05
UNIT MECH STARTING CONDITION
Ini:
S:CON
ESTABL
01CJA00_EU001_ZM06
UNIT PERMANENT START CONDITION
Ini:
S:CON
ESTABL
01CJA00_EU001_ZM23
SWITCHYARD CONDITIONS FOR BLACK START
Ini:0 (UNAVLBL)
S:CON
AVLBL 72
01CJA00_EU001_ZA01 OR
ANY UNIT STOP CMD 01CJA00_EU001_ZA01
Ini:0 (N-REQ) IN1
S:CON 01CJA00_EU001_ZG51
REQ IN2
01CJA00_EU001_ZG51
UNIT BS STATE
Ini:0 (NO)
S:SFC
YES
01CJA00_EA010_ZS010
1 2
01CJA00_EU001_ZM04 AND AND 01CJA00_EA010_ZS015
UNIT ELEC STARTING CONDITION 01CJA00_EU001_ZM04 01CJA00_EA010_ZS015 STEP01 COND
Ini: IN1 IN1 Ini:
S:CON 01CJA00_EU001_ZM05 1
ESTABL
IN2 IN2 CORRECT
01CJA00_EU001_ZM06
IN3
01CJA00_EU001_ZM05
UNIT MECH STARTING CONDITION
Ini:
S:CON
ESTABL
01CJA00_EU001_ZM06
UNIT PERMANENT START CONDITION
Ini:
S:CON
ESTABL
01CJA00_EA010_ZS020
3 4
01MAU24_EA001_ZG01 AND AND 01CJA00_EA010_ZS025
GOVERNOR OIL STATION STARTED IN AUTO MODE 01MAU24_EA001_ZG01 01CJA00_EA010_ZS025 STEP02 COND
Ini:0 (N-DET) IN1 IN1 Ini:
S:EU014 01MEA41_CG015_XG01 1
DETECTED IN2 IN2 CORRECT
01MEA41_CG015_XG01
WICKET GATE FULL CLOSED(CG015S)
Ini:
IO:L01_02 Rack:0 Slot:ST6 (X20DI9371) Point:10
DETECTED
01CJA00_EA010_ZS030
5 6
01MAU24_EA001_ZG01 AND AND 01CJA00_EA010_ZS035
GOVERNOR OIL STATION STARTED IN AUTO MODE 01MAU24_EA001_ZG01 01CJA00_EA010_ZS035 STEP03 COND
Ini:0 (N-DET) IN1 IN1 Ini:
S:EU014 01MEA41_CG605_XG02 1
IN2 IN2 CORRECT
DETECTED 01PAC00_AA001_XG01
IN3
01MEA41_CG605_XG02 01PAC00_CF972_ZH06
REGULATING RING PIN CONTACTOR RELEASED IN4
01PAC00_CF973_ZH06
Ini: IN5
IO:L01_02 Rack:0 Slot:ST4 (X20DI9371) Point:1 01PAC00_CF975_ZH06
DETECTED IN6
01PAC00_CF976_ZH06
01PAC00_AA001_XG01 IN7
01MAU24_CL002_XH51
UNIT TECHNICAL WATER VALVE AA001 POSITION IN8
Ini: 01MAU24_CP001_ZH04
IO:L01_02 Rack:0 Slot:ST9 (X20DI9371) Point:2 IN9
01MEA41_CG015_XG01
OPEN I10
01PAC00_CF972_ZH06
TUR GUIDE BRG COOLING WTR FLW NORMAL
Ini:0 (N-DET)
S:AA001
DETECTED
01PAC00_CF973_ZH06
GEN THRUST BRG COOLING WTR FLOW NORMAL
Ini:0 (N-DET)
S:AA001
DETECTED
01PAC00_CF975_ZH06
ALL THE COOLING WATER SUB SYSTEM FLOW OK
GEN COOLER MAIN COOLING WTR FLOW NORMAL
Ini:0 (N-DET)
S:AA001
DETECTED
01PAC00_CF976_ZH06
GEN GUIDE BRG COOLING WTR FLOW NORMAL
Ini:0 (N-DET)
S:AA001
DETECTED
01MAU24_CL002_XH51
GOV ACCUMULATOR OIL LEVEL BUILD UP
Ini:
IO:L01_01 Rack:0 Slot:ST13 (X20DI9371) Point:6
DETECTED
01MAU24_CP001_ZH04
GOV ACCUMULATOR OIL PRESSURE BUILDUP
Ini:0 (N-DET)
S:EU014
DETECTED
1
MOVE_B 01CJA00_EA010_ZS011
01CJA00_EA010_SFC_S1_X 01CJA00_EA010_ZS011 STEP01
IN RE Ini:
IN-PROGR
10
01CJA00_EA100_ZG21 AND 01CJA00_EA010_ZM01
UNIT LCU AUTO MODE 01CJA00_EA100_ZG21 01CJA00_EA010_ZM01
SQ10:SS->TS SEQ OVERTIME
Ini: IN1 Ini:
S:CON PRESENCE
SELECTED
01CJA00_EA010_ZT01 : 12000 10 IN2
6 7
5 TP TP
AND TON_D TOF_R
4
01CJA00_EA100_ZG21
OR IN1 IN REB IN REB
2
01CJA00_EA010_ZG01 F_TRIG IN1 IN2 RET RET
SQ10:SS->TS SEQ 01CJA00_EA010_ZG01
Ini:0 (N-PROGR) IN RE IN2
S:SFC...
8 9
IN-PROGR
OR SEL 01CJA00_EA010_ZQ01
3 01CJA00_EA010_ZQ01
01CJA00_EU001_ZG01 F_TRIG SQ10:SS->TS SEQ TIME COUNT
IN1 G RE Ini:0 (0 s)
UNIT STILL STOP STATE 01CJA00_EU001_ZG01 01CJA00_EA010_ZQ01
Ini:0 (NO) IN RE IN2 IN1 0/360000 (0/3600 s)
S:SFC
YES
IN2
01CJA00_EU001_ZK01
4 01CJA00_EU001_ZM11
01CJA00_EU001_ZG01 AND UNIT NORMAL STOP TO SS
UNIT STILL STOP STATE 01CJA00_EU001_ZG01 01CJA00_EA000_ZG01 Ini:
Ini:0 (NO) IN1 REQ
S:SFC 01CJA00_EU001_ZG00
YES IN2
5
OR 01CJA00_EU001_ZG02
01CJA00_EU001_ZG01 01CJA00_EU001_ZG02 UNIT INIT/STILL STOP STATE
01CJA00_EU001_ZG00 IN1
UNIT INIT STOP STATE 01CJA00_EU001_ZG00 Ini:0 (NO)
Ini:0 (NO) IN2 YES
S:SFC
YES
01CJA00_EU001_ZA92
UNIT MECHANICAL STOP COMMAND
Ini:0 (N-SENT)
SENT
16
01CJA00_EU001_ZK02
6 8 15 IV
01SCC00_DE001_ZH06 AND OR AND RS 01CJA00_EU001_ZM02
DEWATER STATE ACTIVE POWER TOO HIGH 01SCC00_DE001_ZH06 UNIT MECH STOP REQ
Ini:0 (N-TRP) IN1 IN1 IN1 S Q1 Ini:0 (N-REQ)
S:AA902 0 01CJA00_EU001_ZG02
TRIPPED
IN2 IN2 IN2 R1 /Q1 REQ
26
IV
RS 01CJA00_EU001_YL02
01CJA00_EU001_YL02 MECHANICAL 86-2 EMERGENCY STOP
S Q1 Ini:
01MEU11_FS001_XH14
R1 /Q1 TRIPPED
27
SEL_B 01CJA00_EA000_CONBI02
7 01CJA00_EA000_CONBI01 01CJA00_EA000_CONBI02 ENABLE MS FOR HEAT RUN TEST
G RE
01MEU11_EU001_ZM02 AND 0 Ini:
GOV SYSTEM MECHANICAL STOP COND 01MEU11_EU001_ZM02 IN1
Ini:0 (N-DET) IN1
S:EU001 01MAU24_EU014_ZM02 IN2
DETECTED
IN2
01MKA54_EU001_ZM02
IN3
01MAU24_EU014_ZM02 01MEA41_AU001_ZM02
GOV OIL STATION MECHANICAL STOP COND IN4
Ini:0 (N-DET)
01CVA00_EU001_ZM02
IN5
S:EU014
DETECTED
01MKA54_EU001_ZM02
Generator Auxilaries MECHANICAL STOP COND
Ini:0 (N-DET)
S:AU001
DETECTED
01MEA41_AU001_ZM02
Turbine Auxilaries MECHANICAL STOP COND
Ini:0 (N-DET)
S:AU001
DETECTED
01CVA00_EU001_ZM02
TEMP MEASURE SYS MECHANICAL STOP COND
Ini:
S:FT001
DETECTED
426/1(+1p)
01CJA00_EU001_ZK11
20
01CJA00_EU001_ZG01 AND
UNIT STILL STOP STATE 01CJA00_EU001_ZG01
Ini:0 (NO) IN1
S:SFC 01CJA00_EU001_ZG00
YES IN2
01CJA00_EU001_ZM11
IN3
01CJA00_EU001_ZG00 01CJA00_EA010_ZG01
UNIT INIT STOP STATE IN4
Ini:0 (NO) 01CJA00_EU001_ZA01
IN5
S:SFC
YES
01CJA00_EU001_ZM11
UNIT NORMAL STOP TO SS
Ini:
S:CON
REQ
01CJA00_EA010_ZG01
SQ10:SS->TS SEQ
Ini:0 (N-PROGR)
S:SFC...
IN-PROGR
01CJA00_EU001_ZA01
ANY UNIT STOP CMD
Ini:0 (N-REQ)
S:CON
REQ
19
01CJA00_EU001_ZG11 OR
UNIT TS STATE 01CJA00_EU001_ZG11
Ini:0 (NO) IN1
S:SFC... 01CJA00_EU001_ZG02
YES IN2
01CJA00_EU001_ZM11
IN3
01CJA00_EU001_ZG02 01CJA00_EU001_ZM02
UNIT INIT/STILL STOP STATE IN4
Ini:0 (NO)
01CJA00_EU001_ZM03
IN5
S:CON
YES
01CJA00_EU001_ZM11
UNIT NORMAL STOP TO SS
Ini:
S:CON
REQ
01CJA00_EU001_ZM02
UNIT MECH STOP REQ
Ini:0 (N-REQ)
S:CON
REQ
01CJA00_EU001_ZM03
UNIT EMERG STOP REQ
Ini:0 (N-REQ)
S:CON
REQ
01CJA00_EU001_ZK03
9
01CJA00_EE001_XM02 AND
UNIT ELECTRIC MASTER TRIP RELAY 01CJA00_EE001_XM02
Ini: IN1
IO:L01_01 Rack:0 Slot:ST4 (X20DI9371) Point:11 0
TRIPPED IN2
10
01CJA00_EU001_ZK03
1 3
OR 01CJA00_EU001_ZA93
01CJA00_EE001_XM01 01CJA00_EU001_ZA93 UNIT ELECTRICAL STOP COMMAND
AND OR IN1
UNIT EMERGENCY STOP BUTTON 01CJA00_EE001_XM01 01CJA00_EA000_CONBOO_0002 Ini:0 (N-SENT)
Ini: IN1 IN1 IN2 SENT
IO:L01_01 Rack:0 Slot:ST4 (X20DI9371) Point:10 0
TRIPPED IN2 IN2
01CJA00_EU001_ZG02
UNIT INIT/STILL STOP STATE
Ini:0 (NO)
S:CON
YES
2
01BAT00_EU001_ZM03 AND
MTR SYSTEM ELECTRICAL STOP COND 01BAT00_EU001_ZM03
Ini:0 (N-DET) IN1
S:PT001 01CJA00_EU001_ZM13
DETECTED IN2
01MKC65_EU001_ZM03
IN3
01CJA00_EU001_ZM13 01MEU11_EU001_ZM03
UNIT EMERGENCY STOP LEVEL 3 IN4
Ini:0 (N-DET)
S:EU001
DETECTED
01MKC65_EU001_ZM03
EXC SYSTEM ELECTRICAL STOP COND
Ini:0 (N-DET)
S:EU001
DETECTED
01MEU11_EU001_ZM03
GOV SYSTEM ELECTRICAL STOP COND
Ini:0 (N-DET)
S:EU001
DETECTED
01BAC00_GS003_XG02
UNIT DISCONNECTOR GS003 (901-3) OPEN
Ini:
IO:L01_01 Rack:0 Slot:ST6 (X20DI9371) Point:2
OPEN
01MEU11_FS001_XH14
RV14 SPEED=0
Ini:
IO:L01_01 Rack:0 Slot:ST11 (X20DI9371) Point:6
DETECTED
01MAU24_AP001_XG01
GOVERNOR PUMP AP001 RUNNING
Ini:
IO:L01_01 Rack:0 Slot:ST12 (X20DI9371) Point:3
DETECTED
01MAU24_AP002_XG01
GOVERNOR PUMP AP002 RUNNING
Ini:
IO:L01_01 Rack:0 Slot:ST12 (X20DI9371) Point:9
DETECTED
25
01CJA00_EU001_ZM03 OR 01CJA00_EU001_ZA01
UNIT EMERG STOP REQ 01CJA00_EU001_ZM03 01CJA00_EU001_ZA01 ANY UNIT STOP CMD
Ini:0 (N-REQ) IN1 Ini:0 (N-REQ)
S:CON 01CJA00_EU001_ZM02
IN2 REQ
REQ 01CJA00_EU001_ZM01
IN3
01CJA00_EU001_ZM02
UNIT MECH STOP REQ
Ini:0 (N-REQ)
S:CON
REQ
01CJA00_EU001_ZM01
UNIT NORMAL STOP REQ
Ini:0 (N-REQ)
S:CON
REQ
01CJA00_EA100_ZA51
STEP MODE CONDITION
Ini:
S:CON
01CJA00_EA021_ZS010
3 4
01CJA00_EU001_ZM06 AND AND 01CJA00_EA021_ZS015
UNIT PERMANENT START CONDITION 01CJA00_EU001_ZM06 01CJA00_EA021_ZS015 STEP01 COND
Ini: IN1 IN1 Ini:
S:CON 01MAU24_CP001_ZH04 01CJA00_EA100_ZA51
ESTABL IN2 IN2 CORRECT
01MAU24_CL002_XH51
IN3
01MAU24_CP001_ZH04
GOV ACCUMULATOR OIL PRESSURE BUILDUP
Ini:0 (N-DET)
S:EU014
DETECTED
01MAU24_CL002_XH51
GOV ACCUMULATOR OIL LEVEL BUILD UP
Ini:
IO:L01_01 Rack:0 Slot:ST13 (X20DI9371) Point:6
DETECTED
01CJA00_EA021_ZS020
5 6
01BAC00_GS003_XG01 AND AND 01CJA00_EA021_ZS025
UNIT DISCONNECTOR GS003 (901-3) CLOSED 01BAC00_GS003_XG01 01CJA00_EA021_ZS025 STEP02 COND
Ini: IN1 IN1 Ini:
IO:L01_01 Rack:0 Slot:ST6 (X20DI9371) Point:1 1 1
CLOSED
IN2 IN2 CORRECT
01CJA00_EA021_ZS030
7 8
01CJA00_EE101_ZG01 AND AND 01CJA00_EA021_ZS035
INTAKE GATE FULLY OPEN 01CJA00_EE101_ZG01 01CJA00_EA021_ZS035 STEP03 COND
Ini:0 (N-DET) IN1 IN1 Ini:
S:CON 01MKA54_CG565_ZG01 01CJA00_EA100_ZA51
IN2 IN2 CORRECT
DETECTED 01MEU11_EU001_ZG23
IN3
01MKA54_CG565_ZG01
MECHANICAL BRAKING LIMIT SWITCHES SQ01-SQ18
Ini:0 (N-RELEAS)
S:AU001
RELEASE
2
01CJA00_EU001_ZG14 OR 01MEU11_EU001_ZG23
UNIT IN SELF SYNCHRONIZE STARTING MODE 01CJA00_EU001_ZG14 01MEU11_EU001_ZG23
GOV READY FOR EXACT or SELF SYNCHRONIZE
Ini:0 (N-DET) IN1 Ini:0 (N-DET)
S:GS901 DETECTED
DETECTED
IN2
1
01CJA00_EU001_ZG14 AND
UNIT IN SELF SYNCHRONIZE STARTING MODE 01CJA00_EU001_ZG14
Ini:0 (N-DET) IN1
S:GS901 01MEU11_EU001_ZG22
DETECTED
IN2
01MEU11_EU001_ZG22
GOV ISOLATED MODE R6 FOR SELF SYNCHRONIZE
Ini:0 (N-SEL)
S:EU001
SELECTED
01MEA41_CG015_XG01
WICKET GATE FULL CLOSED(CG015S)
Ini:
IO:L01_02 Rack:0 Slot:ST6 (X20DI9371) Point:10
DETECTED
01BAC00_GS035_XG02
UNIT EARTHING SWITCH (901-35) OPEN
Ini:
IO:L01_01 Rack:0 Slot:ST6 (X20DI9371) Point:4
DETECTED
01BAC00_GS038_XG02
UNIT EARTHING SWITCH (901-38) OPEN
Ini:
IO:L01_01 Rack:0 Slot:ST6 (X20DI9371) Point:6
DETECTED
01BAC00_GS005_XG02
UNIT EARTHING SWITCH (901-5) OPEN
Ini:
IO:L01_01 Rack:0 Slot:ST6 (X20DI9371) Point:8
DETECTED
01BAC00_GS003_XG01
UNIT DISCONNECTOR GS003 (901-3) CLOSED
Ini:
IO:L01_01 Rack:0 Slot:ST6 (X20DI9371) Point:1
CLOSED
1
MOVE_B 01CJA00_EA021_ZS011
01CJA00_EA021_SFC_S1_X 01CJA00_EA021_ZS011 STEP01
IN RE Ini:
IN-PROGR
2
MOVE_B 01CJA00_EA021_ZS021
01CJA00_EA021_SFC_S2_X 01CJA00_EA021_ZS021 STEP02
IN RE Ini:
IN-PROGR
3
MOVE_B 01CJA00_EA021_ZS031
01CJA00_EA021_SFC_S3_X 01CJA00_EA021_ZS031 STEP03
IN RE Ini:
IN-PROGR
01CJA00_EA021_SIGRI01 : 3.00000
4
TP
TON_R 01CJA00_EA021_DL04
01CJA00_EA021_SFC_S3_X 01CJA00_EA021_DL04 STEP4 TIME DELAY
IN REB Ini:0 (N-DET)
RET DETECTED
13
01CJA00_EA100_ZG21 AND 01CJA00_EA021_ZM01
UNIT LCU AUTO MODE 01CJA00_EA100_ZG21 01CJA00_EA021_ZM01
SQ21:TS->SR SEQ OVERTIME
Ini: IN1 Ini:
S:CON PRESENCE
SELECTED
01CJA00_EA021_ZT01 : 12000 10 IN2
9 10
8 TP TP
AND TON_D TOF_R
7
01CJA00_EA100_ZG21
OR IN1 IN REB IN REB
5
01CJA00_EA021_ZG01 F_TRIG IN1 IN2 RET RET
SQ21:TS->SR SEQ
Ini:0 (N-PROGR) IN RE IN2
S:SFC...
IN-PROGR 11 12
OR SEL 01CJA00_EA021_ZQ01
6 01CJA00_EA021_ZQ01
01CJA00_EU001_ZG01 F_TRIG SQ21:TS->SR SEQ TIME COUNT
IN1 G RE Ini:0 (0 s)
UNIT STILL STOP STATE 01CJA00_EU001_ZG01
Ini:0 (NO) IN RE IN2 IN1 0/360000 (0/3600 s)
S:SFC
YES
IN2
01CJA00_EA100_ZA51
STEP MODE CONDITION
Ini:
S:CON
01CJA00_EA027_ZS010
3 4
01MEU11_FS001_XH04 AND AND 01CJA00_EA027_ZS015
RV04 <87% LOW FREQUENCY PROTECTION 01MEU11_FS001_XH04 01CJA00_EA027_ZS015 STEP01 COND
Ini: IN1 IN1 Ini:
IO:L01_01 Rack:0 Slot:ST11 (X20DI9371) Point:1 01MEU11_FS001_ZM51 01CJA00_EA100_ZA51
DETECTED
IN2 IN2 CORRECT
01MKC65_GH001_XL31
IN3
01MEU11_FS001_ZM51 01MKC65_EU001_ZM04
GOVERNOR T-ADT MEASUREMENT IN4
Ini:0 (FAULT)
S:EU001
NORMAL
01MKC65_GH001_XL31
EXCITATION CONTROL LEVEL
Ini:
IO:L01_01 Rack:0 Slot:ST7 (X20DI9371) Point:8
REMOTE
01MKC65_EU001_ZM04
EXCITATION SYSTEM STARTING COND
Ini:0 (N-READY)
S:EU001
READY
EXCITATION NO FAULT
01CJA00_EA027_ZS020
5 6
01CJA00_EU001_ZM21 AND AND 01CJA00_EA027_ZS025
SWITCHYARD CONDITIONS FOR GENERATING 01CJA00_EU001_ZM21 01CJA00_EA027_ZS025 STEP02 COND
Ini:0 (UNAVLBL) IN1 IN1 Ini:
S:CON 01CJA00_EP001_ZM04 01CJA00_EA100_ZA51
IN2 IN2 CORRECT
AVLBL 01MEU11_FS001_XH05
IN3
01CJA00_EP001_ZM04 01MEU11_FS001_ZM51
UNIT SYNCHRONIZER OK / SELF SYNCHRONIZE MODE IN4
Ini:0 (N-DET)
01MKC65_CS101_ZG01
IN5
S:CON 01BBA00_DE003_ZH17
DETECTED IN6
01MEU11_FS001_XH05
RV05 >95% SYNCHRONISATION LAUNCH
Ini:
IO:L01_01 Rack:0 Slot:ST11 (X20DI9371) Point:2
DETECTED
01MEU11_FS001_ZM51
GOVERNOR T-ADT MEASUREMENT
Ini:0 (FAULT)
S:EU001
NORMAL
1
01CJA00_EU001_ZG14 SEL_B
UNIT IN SELF SYNCHRONIZE STARTING MODE 01CJA00_EU001_ZG14 01MKC65_CS101_ZG01
Ini:0 (N-DET) G RE
S:GS901 01MKC65_GS101_XG01
DETECTED
IN1
01BBA00_EM001_ZG72
IN2
01MKC65_GS101_XG01
EXCIT FIELD BREAKER CLOSED
Ini:
IO:L01_01 Rack:0 Slot:ST8 (X20DI9371) Point:4
DETECTED 2
SEL_B
01CJA00_EU001_ZG14 01BBA00_DE003_ZH17
01BBA00_DE003_ZH07 G RE
UNIT VOLTAGE >95%Un 01BBA00_DE003_ZH07
Ini:0 (N-DET) IN1
S:FE001 1
DETECTED
IN2
VOLTAGE>95%
1
MOVE_B 01CJA00_EA027_ZS011
01CJA00_EA027_SFC_S1_X 01CJA00_EA027_ZS011 STEP01
IN RE Ini:
IN-PROGR
10
01CJA00_EA100_ZG21 AND 01CJA00_EA027_ZM01
UNIT LCU AUTO MODE 01CJA00_EA100_ZG21 01CJA00_EA027_ZM01
SQ27:SR->SE SEQ OVERTIME
Ini: IN1 Ini:
S:CON PRESENCE
SELECTED
01CJA00_EA027_ZT01 : 12000 10 IN2
6 7
5 TP TP
AND TON_D TOF_R
4
01CJA00_EA100_ZG21
OR IN1 IN REB IN REB
2
01CJA00_EA027_ZG01 F_TRIG IN1 IN2 RET RET
SQ27:SR->SE SEQ 01CJA00_EA027_ZG01
Ini:0 (N-PROGR) IN RE IN2
S:SFC...
IN-PROGR 8 9
OR SEL 01CJA00_EA027_ZQ01
3 01CJA00_EA027_ZQ01
01CJA00_EU001_ZG01 F_TRIG SQ27:SR->SE SEQ TIME COUNT
IN1 G RE Ini:0 (0 s)
UNIT STILL STOP STATE 01CJA00_EU001_ZG01
Ini:0 (NO) IN RE IN2 IN1 0/360000 (0/3600 s)
S:SFC
YES IN2
01CJA00_EA100_ZA51
STEP MODE CONDITION
Ini:
S:CON
01CJA00_EA043_ZS010
2 3
01CJA00_EU001_ZM06 AND AND 01CJA00_EA043_ZS015
UNIT PERMANENT START CONDITION 01CJA00_EU001_ZM06 01CJA00_EA043_ZS015 STEP01 COND
Ini: IN1 IN1 Ini:
S:CON 1 1
ESTABL
IN2 IN2 CORRECT
01CJA00_EA043_ZS020
4 5
01CJA00_EU001_ZG12 AND AND 01CJA00_EA043_ZS025
UNIT P<MIN or WICKET OPEN<NO LOAD or INTAKE GATE CLOSED 01CJA00_EU001_ZG12 01CJA00_EA043_ZS025 STEP02 COND
Ini: IN1 IN1 Ini:
S:CON 1 01CJA00_EA100_ZA51
DETECTED
IN2 IN2 CORRECT
01CJA00_EA043_RI01 : 10.00000
1
TP 01CJA00_EA043_ZS030
6 7
01MEA41_CG015_XG01
TON_R AND AND 01CJA00_EA043_ZS035
WICKET GATE FULL CLOSED(CG015S) 01MEA41_CG015_XG01 01MEA41_CG015_ZG01 01CJA00_EA043_ZS035 STEP03 COND
Ini: IN REB IN1 IN1 Ini:
IO:L01_02 Rack:0 Slot:ST6 (X20DI9371) Point:10 1 1
RET IN2 IN2 CORRECT
DETECTED
01CJA00_EA043_ZS040
8 9
01SCC00_EU001_ZA01 AND AND 01CJA00_EA043_ZS045
RUNNER DEWATER REQUEST 01SCC00_EU001_ZA01 01CJA00_EA043_ZS045 STEP04 COND
Ini: IN1 IN1 Ini:
S:SFC 01SCC00_EU001_ZH03 1
IN2 IN2 CORRECT
DETECTED 01SCC00_AA901_XG01
IN3
01SCC00_EU001_ZH03 01SCC00_AA902_XG01
DEWATER WATER LEVEL or ACTIVE POWER IN4
Ini:0 (N-REACHD)
S:CON
REACHED
01SCC00_AA901_XG01
CONDENDSOR DEWATER MAIN VALVE
Ini:
IO:L01_02 Rack:0 Slot:ST9 (X20DI9371) Point:7
OPEN
01SCC00_AA902_XG01
CONDENDSOR DEWATER AUXILIARY VALVE
Ini:
IO:L01_02 Rack:0 Slot:ST9 (X20DI9371) Point:11
OPEN
1
MOVE_B 01CJA00_EA043_ZS011
01CJA00_EA043_SFC_S1_X 01CJA00_EA043_ZS011 STEP01
IN RE Ini:
IN-PROGR
2
MOVE_B 01CJA00_EA043_ZS021
01CJA00_EA043_SFC_S2_X 01CJA00_EA043_ZS021 STEP02
IN RE Ini:
IN-PROGR
3
MOVE_B 01CJA00_EA043_ZS031
01CJA00_EA043_SFC_S3_X 01CJA00_EA043_ZS031 STEP03
IN RE Ini:
IN-PROGR
01CJA00_EA043_ZT099 : 1.00000
4
TP
TON_R
01CJA00_EA043_SFC_S99_X 01CJA00_EA043_ZD099
IN REB
RET
13
01CJA00_EA100_ZG21 AND 01CJA00_EA043_ZM01
UNIT LCU AUTO MODE 01CJA00_EA100_ZG21 01CJA00_EA043_ZM01
SQ43: GE->GC SEQ OVERTIME
Ini: IN1 Ini:
S:CON PRESENCE
SELECTED
01CJA00_EA043_ZT01 : 12000 10 IN2
9 10
8 TP TP
AND TON_D TOF_R
7
01CJA00_EA100_ZG21
OR IN1 IN REB IN REB
5
01CJA00_EA043_ZG01 F_TRIG IN1 IN2 RET RET
SQ43: GE->GC SEQ 01CJA00_EA043_ZG01
Ini:0 (N-PROGR) IN RE IN2
S:SFC...
IN-PROGR 11 12
OR SEL 01CJA00_EA043_ZQ01
6 01CJA00_EA043_ZQ01
01CJA00_EU001_ZG01 F_TRIG SQ43: GE->GC SEQ TIME COUNT
IN1 G RE Ini:0 (0 s)
UNIT STILL STOP STATE 01CJA00_EU001_ZG01
Ini:0 (NO) IN RE IN2 IN1 0/360000 (0/3600 s)
S:SFC
YES
IN2
01CJA00_EA100_ZA51
STEP MODE CONDITION
Ini:
S:CON
01CJA00_EA061_ZS010
1 2
01CJA00_EU001_ZM06 AND AND 01CJA00_EA061_ZS015
UNIT PERMANENT START CONDITION 01CJA00_EU001_ZM06 01CJA00_EA061_ZS015
STEP01 COND
Ini: IN1 IN1 Ini:
S:CON 01MAU24_CP001_ZH04 01CJA00_EA100_ZA51
ESTABL
IN2 IN2 CORRECT
01MAU24_CL002_XH51
IN3
01MAU24_CP001_ZH04
GOV ACCUMULATOR OIL PRESSURE BUILDUP
Ini:0 (N-DET)
S:EU014
DETECTED
01MAU24_CL002_XH51
GOV ACCUMULATOR OIL LEVEL BUILD UP
Ini:
IO:L01_01 Rack:0 Slot:ST13 (X20DI9371) Point:6
DETECTED
01CJA00_EA061_ZS020
3 4
01BAC00_GS003_XG01 AND AND 01CJA00_EA061_ZS025
UNIT DISCONNECTOR GS003 (901-3) CLOSED 01BAC00_GS003_XG01 01CJA00_EA061_ZS025
STEP02 COND
Ini: IN1 IN1 Ini:
IO:L01_01 Rack:0 Slot:ST6 (X20DI9371) Point:1 1 01CJA00_EA100_ZA51
CLOSED
IN2 IN2 CORRECT
01CJA00_EA061_ZS030
5 6
01CJA00_EE101_ZG01 AND AND 01CJA00_EA061_ZS035
INTAKE GATE FULLY OPEN 01CJA00_EE101_ZG01 01CJA00_EA061_ZS035
STEP03 COND
Ini:0 (N-DET) IN1 IN1 Ini:
S:CON 01MKA54_CG565_ZG01 01CJA00_EA100_ZA51
IN2 IN2 CORRECT
DETECTED
01MKA54_CG565_ZG01
MECHANICAL BRAKING LIMIT SWITCHES SQ01-SQ18
Ini:0 (N-RELEAS)
S:AU001
RELEASE
437/1(+1p)
01MEA41_CG015_XG01
WICKET GATE FULL CLOSED(CG015S)
Ini:
IO:L01_02 Rack:0 Slot:ST6 (X20DI9371) Point:10
DETECTED
01BAC00_GS003_XG01
UNIT DISCONNECTOR GS003 (901-3) CLOSED
Ini:
IO:L01_01 Rack:0 Slot:ST6 (X20DI9371) Point:1
CLOSED
01BAC00_GS035_XG02
UNIT EARTHING SWITCH (901-35) OPEN
Ini:
IO:L01_01 Rack:0 Slot:ST6 (X20DI9371) Point:4
DETECTED
01BAC00_GS038_XG02
UNIT EARTHING SWITCH (901-38) OPEN
Ini:
IO:L01_01 Rack:0 Slot:ST6 (X20DI9371) Point:6
DETECTED
01CJA00_EA061_ZS050
9 10
01BAC00_GS901_XG01 AND AND 01CJA00_EA061_ZS055
UNIT GCB GS901 IN CLOSED POSTION 01BAC00_GS901_XG01 01CJA00_EA061_ZS055
STEP05 COND
Ini: IN1 IN1 Ini:
IO:L01_01 Rack:0 Slot:ST5 (X20DI9371) Point:1 01MEU11_EU001_ZG21 1
IN2 IN2 CORRECT
DETECTED
01MEU11_EU001_ZG21
GOV Insolated Network R128
Ini:0 (N-SEL)
S:EU001
SELECTED
01CJA00_EA061_ZS060
11 12
01MKC65_DE001_XG04 AND AND 01CJA00_EA061_ZS065
EXCIT LINE CHARGING IN OPERATION 01MKC65_DE001_XG04 01CJA00_EA061_ZS065
STEP06 COND
Ini: IN1 IN1 Ini:
IO:L01_01 Rack:0 Slot:ST8 (X20DI9371) Point:2 1 01CJA00_EA100_ZA51
IN2 IN2 CORRECT
DETECTED
01CJA00_EA061_ZS070
13 14
01MKC65_GS101_XG01 AND AND 01CJA00_EA061_ZS075
EXCIT FIELD BREAKER CLOSED 01MKC65_GS101_XG01 01CJA00_EA061_ZS075
STEP07 COND
Ini: IN1 IN1 Ini:
IO:L01_01 Rack:0 Slot:ST8 (X20DI9371) Point:4 01MEU11_FS001_ZM51 1
IN2 IN2 CORRECT
DETECTED 01MEU11_FS001_XH05
IN3
01MEU11_FS001_ZM51 01BBA00_DE003_ZH07
GOVERNOR T-ADT MEASUREMENT IN4
Ini:0 (FAULT)
S:EU001
NORMAL
01MEU11_FS001_XH05
RV05 >95% SYNCHRONISATION LAUNCH
Ini:
IO:L01_01 Rack:0 Slot:ST11 (X20DI9371) Point:2
DETECTED
01BBA00_DE003_ZH07
UNIT VOLTAGE >95%Un
Ini:0 (N-DET)
S:FE001
DETECTED
1
MOVE_B 01CJA00_EA061_ZS011
01CJA00_EA061_SFC_S1_X 01CJA00_EA061_ZS011 STEP01
IN RE Ini:
IN-PROGR
2
MOVE_B 01CJA00_EA061_ZS021
01CJA00_EA061_SFC_S2_X 01CJA00_EA061_ZS021 STEP02
IN RE Ini:
IN-PROGR
3
MOVE_B 01CJA00_EA061_ZS031
01CJA00_EA061_SFC_S3_X 01CJA00_EA061_ZS031 STEP03
IN RE Ini:
IN-PROGR
4
MOVE_B 01CJA00_EA061_ZS041
01CJA00_EA061_SFC_S4_X 01CJA00_EA061_ZS041 STEP04
IN RE Ini:
IN-PROGR
5
MOVE_B 01CJA00_EA061_ZS051
01CJA00_EA061_SFC_S5_X 01CJA00_EA061_ZS051 STEP05
IN RE Ini:
IN-PROGR
6
MOVE_B 01CJA00_EA061_ZS061
01CJA00_EA061_SFC_S6_X 01CJA00_EA061_ZS061 STEP06
IN RE Ini:
IN-PROGR
01CJA00_EA061_ZT002 : 5.00000
7
TP
TON_R
01CJA00_EA061_SFC_S3_X 01CJA00_EA061_ZD002
IN REB
RET
16
01CJA00_EA100_ZG21 AND 01CJA00_EA061_ZM01
UNIT LCU AUTO MODE 01CJA00_EA100_ZG21 01CJA00_EA061_ZM01
SQ61: TS->CH SEQ OVERTIME
Ini: IN1 Ini:
S:CON PRESENCE
SELECTED
01CJA00_EA061_ZT01 : 12000 10 IN2
12 13
11 TP TP
AND TON_D TOF_R
10
01CJA00_EA100_ZG21
OR IN1 IN REB IN REB
8
01CJA00_EA061_ZG01 F_TRIG IN1 IN2 RET RET
SQ61: TS->CH SEQ
Ini:0 (N-PROGR) IN RE IN2
S:SFC...
IN-PROGR 14 15
OR SEL 01CJA00_EA061_ZQ01
9 01CJA00_EA061_ZQ01
01CJA00_EU001_ZG01 F_TRIG SQ61: TS->CH SEQ TIME COUNT
IN1 G RE Ini:0 (0 s)
UNIT STILL STOP STATE 01CJA00_EU001_ZG01
Ini:0 (NO) IN RE IN2 IN1 0/360000 (0/3600 s)
S:SFC
YES
IN2
01CJA00_EA100_ZA51
STEP MODE CONDITION
Ini:
S:CON
01CJA00_EA034_ZS010
1 2
01CJA00_EU001_ZM06 AND AND 01CJA00_EA034_ZS015
UNIT PERMANENT START CONDITION 01CJA00_EU001_ZM06 01CJA00_EA034_ZS015 STEP01 COND
Ini: IN1 IN1 Ini:
S:CON 1 01CJA00_EA100_ZA51
ESTABL IN2 IN2 CORRECT
01CJA00_EA034_ZS020
3 4
01SCC00_EU001_ZG02 AND AND 01CJA00_EA034_ZS025
RUNNER REWATER STATE 01SCC00_EU001_ZG02 01CJA00_EA034_ZS025 STEP02 COND
Ini: IN1 IN1 Ini:
S:SFC... 1 1
DETECTED
IN2 IN2 CORRECT
01CJA00_EA034_ZS030
5 6
01MEA41_CG015_XG01 AND AND 01CJA00_EA034_ZS035
WICKET GATE FULL CLOSED(CG015S) 01MEA41_CG015_XG01 01CJA00_EA034_ZS035 STEP03 COND
Ini: IN1 IN1 Ini:
IO:L01_02 Rack:0 Slot:ST6 (X20DI9371) Point:10 1 01CJA00_EA100_ZA51
IN2 IN2 CORRECT
DETECTED
01CJA00_EA034_ZS040
7 8
01BBA00_DE001_ZH03 AND AND 01CJA00_EA034_ZS045
UNIT ACTIVE POWER > MINIMAL 01BBA00_DE001_ZH03 01CJA00_EA034_ZS045 STEP04 COND
Ini:0 (N-DET) IN1 IN1 Ini:
S:FE001 1 1
IN2 IN2 CORRECT
DETECTED
1
MOVE_B 01CJA00_EA034_ZS011
01CJA00_EA034_SFC_S1_X 01CJA00_EA034_ZS011 STEP01
IN RE Ini:
IN-PROGR
2
MOVE_B 01CJA00_EA034_ZS021
01CJA00_EA034_SFC_S2_X 01CJA00_EA034_ZS021 STEP02
IN RE Ini:
IN-PROGR
3
MOVE_B 01CJA00_EA034_ZS031
01CJA00_EA034_SFC_S3_X 01CJA00_EA034_ZS031 STEP03
IN RE Ini:
IN-PROGR
12
01CJA00_EA100_ZG21 AND 01CJA00_EA034_ZM01
UNIT LCU AUTO MODE 01CJA00_EA100_ZG21 01CJA00_EA034_ZM01
SQ34:GC->GE SEQ OVERTIME
Ini: IN1 Ini:
S:CON PRESENCE
SELECTED
01CJA00_EA034_ZT01 : 12000 10 IN2
8 9
7 TP TP
AND TON_D TOF_R
6
01CJA00_EA100_ZG21
OR IN1 IN REB IN REB
4
01CJA00_EA034_ZG01
01CJA00_EA034_ZG01 F_TRIG IN1 IN2 RET RET
SQ34:GC->GE SEQ 01CJA00_EA034_ZG01
Ini:0 (N-PROGR) IN RE IN2
S:SFC...
IN-PROGR 10 11
OR SEL 01CJA00_EA034_ZQ01
5
01CJA00_EA034_ZG01 01CJA00_EA034_ZQ01
01CJA00_EU001_ZG01 F_TRIG SQ34:GC->GE SEQ TIME COUNT
IN1 G RE Ini:0 (0 s)
UNIT STILL STOP STATE 01CJA00_EU001_ZG01
Ini:0 (NO) IN RE IN2 IN1 0/360000 (0/3600 s)
S:SFC
YES
IN2
01CJA00_EA100_ZA51
STEP MODE CONDITION
Ini:
S:CON
01CJA00_EA032_ZS010
5 6
01CJA00_EU001_ZM06 AND AND 01CJA00_EA032_ZS015
UNIT PERMANENT START CONDITION 01CJA00_EU001_ZM06 01CJA00_EA032_ZS015 STEP01 COND
Ini: IN1 IN1 Ini:
S:CON 1 1
ESTABL IN2 IN2 CORRECT
4
01MEA41_CG002_XG01 OR 01CJA00_EU001_ZG12
WICKET GATE ABOVE NO_LOAD POSIT 01MEA41_CG002_XG01 01CJA00_EU001_ZG12 UNIT P<MIN or WICKET OPEN<NO LOAD or INTAKE GATE CLOSED
Ini: IN1 Ini:
IO:L01_02 Rack:0 Slot:ST6 (X20DI9371) Point:8 01MEA41_CG015_XG01
DETECTED IN2 DETECTED
01CJA00_EE101_ZG02
IN3
01MEA41_CG015_XG01 01BBA00_DE001_ZH03
WICKET GATE FULL CLOSED(CG015S) IN4
Ini:
IO:L01_02 Rack:0 Slot:ST6 (X20DI9371) Point:10
DETECTED
01CJA00_EE101_ZG02
INTAKE GATE FULLY CLOSED
Ini:0 (N-DET)
S:CON
DETECTED
01BBA00_DE001_ZH03
UNIT ACTIVE POWER > MINIMAL
Ini:0 (N-DET)
S:FE001
DETECTED
01CJA00_EA032_ZS020
7 8
AND AND 01CJA00_EA032_ZS025
3
01CJA00_EU001_ZG12 01CJA00_EA032_ZS025
01BBA00_DE003_ZH03 OR STEP02 COND
IN1 IN1 Ini:
UNIT REACTIVE POWER < MINIMAL 01BBA00_DE003_ZH03 01BBA00_DE003_ZZ03 01CJA00_EA100_ZA51
Ini:0 (N-DET) IN1 IN2 IN2 CORRECT
S:FE001
DETECTED
IN2
01CJA00_EA032_CONR01 : 15.00000
2 01BBA00_DE003_ZZ03
UNIT Q<MIN or Step time delay 15s
1 TP Ini:
OR TON_R DETECTED
01CJA00_EA032_ZS011
IN1 IN REB
01CJA00_EA001_ZS011
IN2 RET
01CJA00_EA002_ZS011
IN3
01CJA00_EA032_ZS030
9 10
01BAC00_GS901_XG02 AND AND 01CJA00_EA032_ZS035
UNIT GCB GS901 IN OPEN POSTION 01BAC00_GS901_XG02 01CJA00_EA032_ZS035
STEP03 COND
Ini: IN1 IN1 Ini:
IO:L01_01 Rack:0 Slot:ST5 (X20DI9371) Point:2 01BAC00_GS901_XG01 01CJA00_EA100_ZA51
IN2 IN2 CORRECT
DETECTED
01BAC00_GS901_XG01
UNIT GCB GS901 IN CLOSED POSTION
Ini:
IO:L01_01 Rack:0 Slot:ST5 (X20DI9371) Point:1
DETECTED
01CJA00_EA032_ZS040
11 12
01MKC65_GS101_XG02 AND AND 01CJA00_EA032_ZS045
EXCIT FIELD BREAKER OPEN 01MKC65_GS101_XG02 01CJA00_EA032_ZS045
STEP04 COND
Ini: IN1 IN1 Ini:
IO:L01_01 Rack:0 Slot:ST8 (X20DI9371) Point:5 01MKC65_GS101_XG01 1
IN2 IN2 CORRECT
DETECTED
01MKC65_GS101_XG01
EXCIT FIELD BREAKER CLOSED
Ini:
IO:L01_01 Rack:0 Slot:ST8 (X20DI9371) Point:4
DETECTED
1
MOVE_B 01CJA00_EA032_ZS011
01CJA00_EA032_SFC_S1_X 01CJA00_EA032_ZS011 STEP01
IN RE Ini:0 (N-PROGR)
IN-PROGR
2
MOVE_B 01CJA00_EA032_ZS021
01CJA00_EA032_SFC_S2_X 01CJA00_EA032_ZS021 STEP02
IN RE Ini:
IN-PROGR
3
MOVE_B 01CJA00_EA032_ZS031
01CJA00_EA032_SFC_S3_X 01CJA00_EA032_ZS031 STEP03
IN RE Ini:
IN-PROGR
12
01CJA00_EA100_ZG21 AND 01CJA00_EA032_ZM01
UNIT LCU AUTO MODE 01CJA00_EA100_ZG21 01CJA00_EA032_ZM01
SQ32:GE->SR SEQ OVERTIME
Ini: IN1 Ini:
S:CON PRESENCE
SELECTED
01CJA00_EA032_ZT01 : 12000 10 IN2
8 9
7 TP TP
AND TON_D TOF_R
6
01CJA00_EA100_ZG21
OR IN1 IN REB IN REB
4
01CJA00_EA032_ZG01 F_TRIG IN1 IN2 RET RET
SQ32:GE->SR SEQ 01CJA00_EA032_ZG01
Ini:0 (N-PROGR) IN RE IN2
S:SFC...
IN-PROGR 10 11
OR SEL 01CJA00_EA032_ZQ01
5 01CJA00_EA032_ZQ01
01CJA00_EU001_ZG01 F_TRIG SQ32:GE->SR SEQ TIME COUNT
IN1 G RE Ini:0 (0 s)
UNIT STILL STOP STATE 01CJA00_EU001_ZG01
Ini:0 (NO) IN RE IN2 IN1 0/360000 (0/3600 s)
S:SFC
YES IN2
01CJA00_EA036_ZS010
1 2
01BAC00_GS901_XG01 AND AND 01CJA00_EA036_ZS015
UNIT GCB GS901 IN CLOSED POSTION 01BAC00_GS901_XG01 01CJA00_EA036_ZS015 STEP01 COND
Ini: IN1 IN1 Ini:
IO:L01_01 Rack:0 Slot:ST5 (X20DI9371) Point:1 01CJA00_EU001_ZM21 1
DETECTED IN2 IN2 CORRECT
01CJA00_EU001_ZM21
SWITCHYARD CONDITIONS FOR GENERATING
Ini:0 (UNAVLBL)
S:CON
AVLBL
01CJA00_EA036_ZS020
3 4
01MEU11_EU001_ZG21 AND AND 01CJA00_EA036_ZS025
GOV Insolated Network R128 01MEU11_EU001_ZG21 01CJA00_EA036_ZS025 STEP02 COND
Ini:0 (N-SEL) IN1 IN1 Ini:
S:EU001 01MKC65_DE001_XG04 1
SELECTED
IN2 IN2 CORRECT
01MKC65_DE001_XG04
EXCIT LINE CHARGING IN OPERATION
Ini:
IO:L01_01 Rack:0 Slot:ST8 (X20DI9371) Point:2
DETECTED
01CJA00_EA036_ZS030
5 6
01BBA00_DE001_ZH03 AND AND 01CJA00_EA036_ZS035
UNIT ACTIVE POWER > MINIMAL 01BBA00_DE001_ZH03 01CJA00_EA036_ZS035 STEP03 COND
Ini:0 (N-DET) IN1 IN1 Ini:
S:FE001 1 1
IN2 IN2 CORRECT
DETECTED
1
MOVE_B 01CJA00_EA036_ZS011
01CJA00_EA036_SFC_S1_X 01CJA00_EA036_ZS011 STEP01
IN RE Ini:
IN-PROGR
2
MOVE_B 01CJA00_EA036_ZS021
01CJA00_EA036_SFC_S2_X 01CJA00_EA036_ZS021 STEP02
IN RE Ini:
IN-PROGR
11
01CJA00_EA100_ZG21 AND 01CJA00_EA036_ZM01
UNIT LCU AUTO MODE 01CJA00_EA100_ZG21 01CJA00_EA036_ZM01
SQ36:CH->GE SEQ OVERTIME
Ini: IN1 Ini:
S:CON PRESENCE
SELECTED
01CJA00_EA036_ZT01 : 12000 10 IN2
7 8
6 TP TP
AND TON_D TOF_R
5
01CJA00_EA100_ZG21
OR IN1 IN REB IN REB
3
01CJA00_EA036_ZG01 F_TRIG IN1 IN2 RET RET
SQ36:CH->GE SEQ
Ini:0 (N-PROGR) IN RE IN2
S:SFC...
IN-PROGR 9 10
OR SEL 01CJA00_EA036_ZQ01
4 01CJA00_EA036_ZQ01
01CJA00_EU001_ZG01 F_TRIG SQ36:CH->GE SEQ TIME COUNT
IN1 G RE Ini:0 (0 s)
UNIT STILL STOP STATE 01CJA00_EU001_ZG01
Ini:0 (NO) IN RE IN2 IN1 0/360000 (0/3600 s)
S:SFC
YES IN2
01CJA00_EA008_ZS010
2 3
01CJA00_EU001_ZM03 AND AND 01CJA00_EA008_ZS015
UNIT EMERG STOP REQ 01CJA00_EU001_ZM03 01CJA00_EA008_ZS015 STEP01 COND
Ini:0 (N-REQ) IN1 IN1 Ini:
S:CON 1 1
REQ
IN2 IN2 CORRECT
01CJA00_EA008_ZS020
4 5
01BAC00_GS901_XG02 AND AND 01CJA00_EA008_ZS025
UNIT GCB GS901 IN OPEN POSTION 01BAC00_GS901_XG02 01CJA00_EA008_ZS025 STEP02 COND
Ini: IN1 IN1 Ini:
IO:L01_01 Rack:0 Slot:ST5 (X20DI9371) Point:2 01MKC65_GS101_XG02 1
DETECTED
IN2 IN2 CORRECT
01MEU11_FS001_XH02
IN3
01MKC65_GS101_XG02 01MEU11_FS001_ZM51
EXCIT FIELD BREAKER OPEN IN4
01CJA00_EU001_ZG13
Ini: IN5
IO:L01_01 Rack:0 Slot:ST8 (X20DI9371) Point:5
DETECTED
01MEU11_FS001_XH02
RV02 <20% ES MECHANIC BRAKE VALID
Ini:
IO:L01_01 Rack:0 Slot:ST10 (X20DI9371) Point:11
DETECTED
01MEU11_FS001_ZM51
GOVERNOR T-ADT MEASUREMENT
Ini:0 (FAULT)
S:EU001
NORMAL
1
01MEA41_CG015_XG01 OR
WICKET GATE FULL CLOSED(CG015S) 01MEA41_CG015_XG01 01CJA00_EU001_ZG13
Ini: IN1
IO:L01_02 Rack:0 Slot:ST6 (X20DI9371) Point:10 01CJA00_EE101_ZG02
DETECTED
IN2
0
IN3
01CJA00_EE101_ZG02
INTAKE GATE FULLY CLOSED
Ini:0 (N-DET)
S:CON
DETECTED
01CJA00_EA008_ZS030
8 9
01MEU11_FS001_XH14 AND AND 01CJA00_EA008_ZS035
RV14 SPEED=0 01MEU11_FS001_XH14 01CJA00_EA008_ZS035 STEP03 COND
Ini: IN1 IN1 Ini:
IO:L01_01 Rack:0 Slot:ST11 (X20DI9371) Point:6 01CJA00_EU001_ZG13 1
IN2 IN2 CORRECT
DETECTED 01SCC00_EU001_ZG02 01CJA00_EA008_ZD002
IN3 IN3
01CJA00_EU001_ZG13
WICKET GATE or INTAKE GATE CLOSED rewatered
Ini:0 (N-DET)
S:CON
DETECTED
01SCC00_EU001_ZG02
RUNNER REWATER STATE
Ini:
S:SFC...
DETECTED
1
MOVE_B 01CJA00_EA008_ZS011
01CJA00_EA008_SFC_S1_X 01CJA00_EA008_ZS011 STEP01
IN RE Ini:
IN-PROGR
2
MOVE_B 01CJA00_EA008_ZS021
01CJA00_EA008_SFC_S2_X 01CJA00_EA008_ZS021 STEP02
IN RE Ini:
IN-PROGR
3
MOVE_B 01CJA00_EA008_ZS031
01CJA00_EA008_SFC_S3_X 01CJA00_EA008_ZS031 STEP03
IN RE Ini:
IN-PROGR
01CJA00_EA008_ZT002 : 5.00000
4
TP
TON_R
01CJA00_EA008_SFC_S2_X 01CJA00_EA008_ZD002
IN REB
RET
13
01CJA00_EA100_ZG21 AND 01CJA00_EA008_ZM01
UNIT LCU AUTO MODE 01CJA00_EA100_ZG21 01CJA00_EA008_ZM01
SQ04: ES->TS SEQ OVERTIME
Ini: IN1 Ini:
S:CON PRESENCE
SELECTED
01CJA00_EA008_ZT01 : 12000 10 IN2
9 10
8 TP TP
AND TON_D TOF_R
7
01CJA00_EA100_ZG21
OR IN1 IN REB IN REB
5 01CJA00_EA008_SIGINT32_0001
01CJA00_EA008_ZG01 F_TRIG IN1 IN2 RET RET
SQ04: ES->TS SEQ 01CJA00_EA008_ZG01
Ini: IN RE IN2
S:SFC...
IN-PROGR 11 12
OR SEL 01CJA00_EA008_ZQ01
6 01CJA00_EA008_ZQ01
01CJA00_EU001_ZG01 F_TRIG SQ04: ES->TS SEQ TIME COUNT
IN1 G RE Ini:0 (0 s)
UNIT STILL STOP STATE 01CJA00_EU001_ZG01
Ini:0 (NO) IN RE IN2 IN1 0/360000 (0/3600 s)
S:SFC
YES
IN2
01CJA00_EA009_ZS010
1 2
01CJA00_EU001_ZA01 AND AND 01CJA00_EA009_ZS015
ANY UNIT STOP CMD 01CJA00_EU001_ZA01 01CJA00_EA009_ZS015 STEP01 COND
Ini:0 (N-REQ) IN1 IN1 Ini:
S:CON 01CJA00_EU001_ZJ12 1
REQ
IN2 IN2 CORRECT
01MEA41_CG015_XG01
IN3
01CJA00_EU001_ZJ12
UNIT NORMAL STOP TO TS
Ini:0 (N-REQ)
S:CON
REQ
01MEA41_CG015_XG01
WICKET GATE FULL CLOSED(CG015S)
Ini:
IO:L01_02 Rack:0 Slot:ST6 (X20DI9371) Point:10
DETECTED
01CJA00_EA009_ZS020
3 4
01MKA54_CG565_ZG01 AND AND 01CJA00_EA009_ZS025
MECHANICAL BRAKING LIMIT SWITCHES SQ01-SQ18 01MKA54_CG565_ZG01 01CJA00_EA009_ZS025 STEP02 COND
Ini:0 (N-RELEAS) IN1 IN1 Ini:
S:AU001 01MAU24_EA001_ZG02 1
RELEASE
IN2 IN2 CORRECT
01PAC00_AA001_XG01
IN3
01MAU24_EA001_ZG02 01MEU11_FS001_XH14
GOVERNOR OIL STATION STOPPED IN AUTO MODE IN4
Ini:0 (N-DET)
S:EU014
DETECTED
01PAC00_AA001_XG01
UNIT TECHNICAL WATER VALVE AA001 POSITION
Ini:
IO:L01_02 Rack:0 Slot:ST9 (X20DI9371) Point:2
OPEN
01MEU11_FS001_XH14
RV14 SPEED=0
Ini:
IO:L01_01 Rack:0 Slot:ST11 (X20DI9371) Point:6
DETECTED
1
MOVE_B 01CJA00_EA009_ZS011
01CJA00_EA009_SFC_S1_X 01CJA00_EA009_ZS011 STEP01
IN RE Ini:
IN-PROGR
10
01CJA00_EA100_ZG21 AND 01CJA00_EA009_ZM01
UNIT LCU AUTO MODE 01CJA00_EA100_ZG21 01CJA00_EA009_ZM01
SQ09: TS->SS SEQ OVERTIME
Ini: IN1 Ini:
S:CON PRESENCE
SELECTED
01CJA00_EA009_ZT01 : 12000 10 IN2
6 7
5 TP TP
AND TON_D TOF_R
4
01CJA00_EA100_ZG21
OR IN1 IN REB IN REB
2
01CJA00_EA009_ZG01 F_TRIG IN1 IN2 RET RET
SQ09: TS->SS SEQ
Ini: IN RE IN2
S:SFC...
IN-PROGR 8 9
OR SEL 01CJA00_EA009_ZQ01
3 01CJA00_EA009_ZQ01
01CJA00_EU001_ZG01 F_TRIG SQ09: TS->SS SEQ TIME COUNT
IN1 G RE Ini:0 (0 s)
UNIT STILL STOP STATE 01CJA00_EU001_ZG01
Ini:0 (NO) IN RE IN2 IN1 0/360000 (0/3600 s)
S:SFC
YES
IN2
5
01MEU11_EU001_XG01 OR
R304 1ST STAGE FREQUENCY INSENTIVITY ACTIVE 01MEU11_EU001_XG01
Ini: IN1 0
IO:L01_01 Rack:0 Slot:ST9 (X20DI9371) Point:9
DETECTED IN2 20
4 IV
01CJA00_DE001_ZL31 AND RS 01CJA00_DE001_ZG31
ACTIVE POWER CTRL MODE: ANA/ANA CMD 01CJA00_DE001_ZL31 01CJA00_DE001_ZG31 ACTIVE POWER CTRL MODE: ANA/ANA
Ini: IN1 S Q1 Ini:0 (N-SEL)
HMI DB Number:19
SENT
IN2 R1 /Q1 SELECTED
2
MOVE_B
01CJA00_DE001_ZQ01_V 01CJA00_CE001_ZQ01
IN RE 19 51
01CJA00_DE001_ZK31
OR MOVE_B 01MEU11_EM001_YL06
3 01CJA00_DE001_ZG31 01MEU11_EM001_YL06
01CJA00_CE001_ZQ01 AND GOV ANALOG LOAD CONTROL MODE R7
IN1 IN RE Ini:
UNIT ACTIVE POWER MEASUREMENT VALIDATION
Ini:0 (NORMAL) IN1 IN2 ON
S:DE001 01MEU11_EU001_RM22
FAULT IN2
01MEU11_EU001_XG04
IN3 52
01MEU11_EU001_RM22 MOVE_B 01MEU11_EU001_TL08
Load set point OE circuit fault 01CJA00_DE001_ZG31 01MEU11_EU001_TL08
R7 Load setpoint choice by OE
Ini: IN RE Ini:
EXT:L01_r5_8_0EX'ModbusClientInB Point:21 ON
DETECTED
ACTIVE POWER AI VALID &
ACTIVE POWER AO VALID &
01MEU11_EU001_XG04
R307 ANALOG SETPOINT MODE IN OPERATION
Ini:
IO:L01_01 Rack:0 Slot:ST11 (X20DI9371) Point:11
DETECTED
21 22
AND R_TRIG
01MEU11_EU001_RM22
IN1 IN RE 1
01CJA00_DE001_ZG31
IN2 9
ACTIVE POWER AO INVALID 8 IV
OR RS 01CJA00_DE001_ZG32
01CJA00_DE001_ZG32 ACTIVE POWER CTRL MODE: ANA/PULSE
01CJA00_DE001_ZL32 IN1 S Q1
ACTIVE POWER CTRL MODE: ANA/PULSE CMD 01CJA00_DE001_ZL32 Ini:0 (N-SEL)
Ini: IN2 R1 /Q1 SELECTED
HMI DB Number:19 01CJA00_DE001_ZA01
SENT
IN3
01CJA00_DE001_ZA11
IN4
01CJA00_DE001_ZA01
Force ACTIVE POWER sp to 0
Ini:0 7
S:SFC OR
IN1
01CJA00_DE001_ZA11 IN2
SET ACT.POWER TO INIT
Ini:
S:SFC...
YES
0
12
6 IV
01CJA00_DE001_ZL33 OR RS 01CJA00_DE001_ZG33
ACTIVE POWER CTRL MODE: PULSE/PULSE CMD 01CJA00_DE001_ZL33 01CJA00_DE001_ZG33 ACTIVE POWER CTRL MODE: PULSE/PULSE
Ini: IN1 S Q1 Ini:
HMI DB Number:19 01CJA00_CE001_ZQ01
IN2 R1 /Q1 SELECTED
SENT
ACTIVE POWER AI INVALID 11
OR
IN1
IN2
XX DE001 : UNIT ACTIVE POWER CONTROL - REV : 214 - 14/JAN/17 09:22 - POUName : L01_5ACT
.163/A
32 33 1
AND R_TRIG
31
01CJA00_DE001_ZG42 16
OR IN1 IN RE
01MEU11_CG001_ZQ01 15 IV
OR 01CJA00_DE001_ZG41
IN1 IN2 RS 01CJA00_DE001_ZG41
01MEA41_CG002_XG01 LOAD CTRL OBJECT: ACT. POWER
IN2 IN1 S Q1 Ini:
01CJA00_DE001_ZA01
IN2 R1 /Q1 01CJA00_DE001_ZG42 SELECTED
01CJA00_DE001_ZA01 01CJA00_DE001_ZA11
IN3
Force ACTIVE POWER sp to 0 01CJA00_DE001_ZL41
Ini:0 IN4
S:SFC
50
MOVE_B 01MEU11_EM001_YL05
01CJA00_DE001_ZA11
01CJA00_DE001_ZG41 01MEU11_EM001_YL05
POWER FEEDBACK RUNNING MODE R5
IN RE Ini:
SET ACT.POWER TO INIT
Ini: ON
S:SFC...
YES
53
01CJA00_DE001_ZL41 MOVE_B 01MEU11_EU001_TL01
LOAD CTRL OBJECT: ACT. POWER SEL CMD WG OPENING >NOLOAD POSITON &
01CJA00_DE001_ZG41 01MEU11_EU001_TL01
R5 Power feedback
Ini: WG OPENING AI VALID IN RE Ini:
HMI DB Number:19 ON
SENT
01CJA00_DE001_ZK42
13
1
AND
FB_UV_BV IN1 01CJA00_DE001_ZG42
01MEU11_CG012_XQ01_V 01MEU11_CG001_ZQ01 LOAD CTRL OBJECT: OPENING DEG
USINT VALID IN2 Ini:
01MEU11_EU001_XG02
FORC_V IN3 SELECTED
01MEA41_CG002_XG01
WICKET GATE ABOVE NO_LOAD POSIT
Ini:
IO:L01_02 Rack:0 Slot:ST6 (X20DI9371) Point:8
DETECTED
01MEU11_EU001_XG02
R305 ACTIVE POWER CONTROL IN OPERATION
Ini:
IO:L01_01 Rack:0 Slot:ST11 (X20DI9371) Point:9
DETECTED 14
AND
01CJA00_DE001_ZL42 IN1
LOAD CTRL OBJECT: OPENING DEG SEL CMD 01CJA00_DE001_ZL42
Ini: IN2
HMI DB Number:19
SENT
10
01CJA00_EU001_ZJ31 OR 01CJA00_EU001_ZG32
UNIT GE STATE 01CJA00_EU001_ZJ31 01CJA00_EU001_ZG32 UNIT IN G DERECT OPERATION
Ini: IN1 Ini:0 (N-DET)
S:CON 01CJA00_EU001_ZG31
IN2 DETECTED
REQ 01CJA00_EA032_ZG01
IN3
01CJA00_EU001_ZG31 01CJA00_EA043_ZG01
IN4
UNIT GE STATE 01CJA00_EA027_ZG01
Ini:0 (NO) IN5
S:SFC 01CJA00_EA073_ZG01
YES IN6
01CJA00_EA032_ZG01
SQ32:GE->SR SEQ
Ini:0 (N-PROGR)
S:SFC...
IN-PROGR
01CJA00_EA043_ZG01
SQ43: GE->GC SEQ
Ini:0 (N-PROGR)
S:SFC...
IN-PROGR
01CJA00_EA027_ZG01
SQ27:SR->SE SEQ
Ini:0 (N-PROGR)
S:SFC...
IN-PROGR
01CJA00_EA073_ZG01
SQ73:SE->GE SEQ
Ini:
S:SFC...
IN-PROGR
XX DE001 : UNIT ACTIVE POWER CONTROL - REV : 214 - 14/JAN/17 09:22 - POUName : L01_5ACT
.164/A
17
01CJA00_EU001_ZG32 AND 01CJA00_DE001_ZG01
UNIT IN G DERECT OPERATION 01CJA00_EU001_ZG32 01CJA00_DE001_ZG01 ACTIVE POWER SETPOINT ENABLED
Ini:0 (N-DET) IN1 Ini:
S:DE001 01CJA00_DE001_ZG33
IN2 SELECTED
DETECTED 01CJA00_DE001_ZG41
IN3
01CJA00_DE001_ZG33
01CJA00_CE001_ZQ01
IN4
ACTIVE POWER CTRL MODE: PULSE/PULSE 01BAC00_GS901_XG01
Ini: IN5
S:DE001 01MEU11_EU001_XL21
SELECTED IN6
01CJA00_DE001_ZG41
LOAD CTRL OBJECT: ACT. POWER
Ini:
S:DE001
SELECTED
01BAC00_GS901_XG01
UNIT GCB GS901 IN CLOSED POSTION
Ini:
IO:L01_01 Rack:0 Slot:ST5 (X20DI9371) Point:1
DETECTED
01MEU11_EU001_XL21
GOVERNOR SYSTEM REMOTE AUTO MODE
Ini:
IO:L01_01 Rack:0 Slot:ST9 (X20DI9371) Point:1
DETECTED
23
01CJA00_DE001_ZR01 FB_HMI_SP 01CJA00_DE001_ZP02
ACTIVE POWER SP CMD 01CJA00_DE001_ZR01 01CJA00_DE001_ZP02 ACTIVE POWER SP INTERNAL
Unit: MW IN SP Unit: MW
HMI DB Number:19 01CJA00_DE001_ZG01
Enable 0/12000 (0/120 MW)
0/12000 (0/120 MW) 01CJA00_DE001_ZU01 01CJA00_DE001_ZM01
Min Sp Forced
01CJA00_DE001_ZU01 01CJA00_DE001_ZW01
ACTIVE POWER MIN SP VALUE Init Sp 01CJA00_DE001_ZM01
Ini:800 (8 MW) 01CJA00_DE001_ZA11 ACTIVE POWER SP FORCED
Init Cmd Ini:0 (NO)
01CJA00_DE001_ZA12
0/12000 (0/120 MW) Forc_min YES
01CJA00_DE001_ZA01
01CJA00_DE001_ZW01 Forc_0
01CJA00_DE001_ZQ01
ACTIVE POWER Init sp value Follow
Ini:800 (8 MW)
Scale
0/12000 (0/120 MW)
01CJA00_DE001_ZV01
01CJA00_DE001_ZA11
SET ACT.POWER TO INIT
Ini:
S:SFC... 01CJA00_DE001_ZP01
YES ACTIVE POWER SP FEEDBACK
Unit: MW
01CJA00_DE001_ZA01 0/12000 (0/120 MW)
Force ACTIVE POWER sp to 0
Ini:0 24
S:SFC LIMIT
01CJA00_DE001_ZU01
LO RE 01CJA00_DE001_ZH06
01CJA00_DE001_ZQ01 01CJA00_DE001_ZP02 01CJA00_DE001_ZH06 ACTIVER SETPOINT OVER HIGH LIMIT
ACTIVE POWER MEAS VALUE IN HL Ini:
Unit: MW 01CJA00_DE001_HI
HI LL DETECTED
S:FE001
-12000/12000 (-120/120 MW)
01CJA00_DE001_ZU01
ACTIVE POWER MIN SP VALUE
Ini:800 (8 MW)
39
AO_SCALE 01MEU11_EU001_TQ02
01CJA00_DE001_ZP01 01MEU11_EU001_TQ02 OEW Load setpoint in power
IN RE Unit: MW
10000
IMax Err 0/25000 (0/1000 MW)
0
IMin
25000
OMax
0
OMin
XX DE001 : UNIT ACTIVE POWER CONTROL - REV : 214 - 14/JAN/17 09:22 - POUName : L01_5ACT
.165/A
25 34 38 40 42
SUB ABS GE OR SEL
01CJA00_DE001_ZP01
IN1 RE IN IN1 RE IN1 G RE
01CJA00_DE001_ZQ01 01CJA00_DE001_TH01 : 3000 01CJA00_EU001_ZG3101CJA00_DE001_TN1 : 8.00000
IN2 IN2 IN2 IN1
01CJA00_DE001_TN2 : 3.00000
IN2
01CJA00_DE001_TH01
ACTIVE POWER DLT THR 43
Ini:3000 (30 MW) SEL
44
35 TP TN
01CJA00_DE001_ZP01 FB_PULS_REG 01CJA00_DE001_INC
ACTIVE POWER SP FEEDBACK 01CJA00_DE001_ZP01
OSC_B 01CJA00_DE001_INC
ACT POWER INCREASE PULSE
Unit: MW SP Inc IN RE Ini:
S:DE001 01CJA00_DE001_ZQ01
0/12000 (0/120 MW) Meas Dec
Enable
01CJA00_DE001_ZQ01 01CJA00_DE001_ZZ01
ACTIVE POWER MEAS VALUE Dead
Unit: MW 01CJA00_DE001_ZX01
Rate(%) 48
S:FE001 01CJA00_DE001_DLT
-12000/12000 (-120/120 MW) Max_delta
01CJA00_DE001_ZT01 TP TN
T0(Cyc) OSC_B 01CJA00_DE001_DEC
01CJA00_DE001_ZG32 01CJA00_DE001_DEC
ACT POWER DECREASE PULSE
ACTIVE POWER CTRL MODE: ANA/PULSE IN RE Ini:
Ini:0 (N-SEL) DETECTED
S:DE001
SELECTED 18
AND
01CJA00_DE001_ZG01
01CJA00_DE001_ZG32
IN1
ACTIVE POWER SETPOINT ENABLED 01CJA00_DE001_ZG01
Ini: IN2
S:DE001
SELECTED
01CJA00_DE001_ZZ01
PULSE REGUL DEAD BAND
Ini:200 (2 MW)
01CJA00_DE001_ZX01
PULSE REGUL DELTA RATE(%)
Ini:50
-32768/32767
01CJA00_DE001_ZT01
PULSE REGUL INTERVAL TIME(CYC)
Ini:5
-32768/32767
30
01CJA00_DE001_ZG41 SEL 01MEU11_FE001_YQ01
LOAD CTRL OBJECT: ACT. POWER 01CJA00_DE001_ZG41 01MEU11_FE001_YQ01 UNIT ACT PWR/WG OPEN DEGREE SETP
Ini: G RE Unit: MW
S:DE001 01CJA00_DG001_ZP03
IN1 6553/32767 (0/120 MW)
SELECTED 01CJA00_DE001_ZP03
IN2
01CJA00_DG001_ZP03
WG OPENING SP INTERNAL
Ini:0 (-8.75 %)
S:DG001
6553/32767 (13/100 %)
01CJA00_DE001_ZP03
ACTIVE POWER SP INTERNAL
Unit: MW
S:DE001
6553/32767 (0/300 MW)
XX DE001 : UNIT ACTIVE POWER CONTROL - REV : 214 - 14/JAN/17 09:22 - POUName : L01_5ACT
.166/A
01CJA00_DE001_ZT02 : 0.50000
36
TP
TP_R 01CJA00_DE001_ZM11
01CJA00_DE001_ZM11 ACT POWER INCREASE REQ
IN REB Ini:
01CJA00_DE001_ZT02 : 0.50000 RET REQ
26
TP 41 45
01CJA00_DE001_ZL01 AND OR 01MEU11_EM001_YL11
ACTIVE POWER INCREASE CMD 01CJA00_DE001_ZL01
TP_R 01MEU11_EM001_YL11 GOVERNOR INCREASE ORDER
Ini: IN REB IN1 IN1 Ini:
HMI DB Number:19 01CJA00_DE001_ZG33 01CJA00_DE001_INC
RET IN2 IN2 ON
SENT 01CJA00_DG001_INC
IN3
01CJA00_DE001_ZG33
ACTIVE POWER CTRL MODE: PULSE/PULSE
Ini:
S:DE001
SELECTED
01CJA00_DE001_INC
ACT POWER INCREASE PULSE
Ini:
S:DE001
01CJA00_DG001_INC
WG OPENING INCREASE PULSE
Ini:0
S:DG001
01CJA00_DE001_ZT02 : 0.50000
27 46 49
AND OR 01MEU11_EM001_YL12
TP 01CJA00_DE001_ZG33 01MEU11_EM001_YL12 GOVERNOR DECREASE ORDER
01CJA00_DE001_ZL02 IN1 IN1
ACTIVE POWER DECREASE CMD TP_R Ini:
01CJA00_DE001_ZL02
Ini: IN REB IN2 IN2 ON
HMI DB Number:19 01CJA00_DE001_DEC
SENT RET IN3
01CJA00_DG001_DEC
28 47 IN4
01CJA00_DE001_ZQ01 GT AND
ACTIVE POWER MEAS VALUE 01CJA00_DE001_ZQ01
Unit: MW IN1 RE IN1
S:FE001 01CJA00_DE001_ZW01 01CJA00_DE001_ZA01
-12000/12000 (-120/120 MW) IN2 IN2
01CJA00_DE001_ZA01
Force ACTIVE POWER sp to 0
Ini:0
S:SFC
01CJA00_DE001_DEC
ACT POWER DECREASE PULSE
Ini:
S:DE001
DETECTED
01CJA00_DG001_DEC
WG OPENING DECREASE PULSE
Ini:0 (N-DET)
S:DG001
DETECTED 01CJA00_DE001_ZT02 : 0.50000
37
TP
TP_R 01CJA00_DE001_ZM12
01CJA00_DE001_ZM12 ACT POWER INCREASE REQ
IN REB Ini:
RET REQ
XX DE001 : UNIT ACTIVE POWER CONTROL - REV : 214 - 14/JAN/17 09:22 - POUName : L01_5ACT
.167/A
4.50 DE002 : UNIT REACTIVE POWER CONTROL - REV : 210 - 14/JAN/17 09:21 - POUName : L01_5ACT
41
6 IV
01CJA00_DE002_ZL31 AND RS 01CJA00_DE002_ZG31
REACTIVE POWER CTRL MODE: ANA/ANA CMD 01CJA00_DE002_ZL31 01CJA00_DE002_ZG31 REACTIVE POWER CTRL MODE: ANA/ANA
Ini: IN1 S Q1 Ini:0 (N-SEL)
HMI DB Number:19
SENT
IN2 R1 /Q1 SELECTED
01CJA00_DE002_ZK31
5
01MKC65_GH001_XL31 AND
EXCITATION CONTROL LEVEL 01MKC65_GH001_XL31
Ini: IN1 40 42
IO:L01_01 Rack:0 Slot:ST7 (X20DI9371) Point:8 01MKC65_DE001_XL21
IN2 OR MOVE_B 01MKC65_EM001_YL01
REMOTE 01MKC65_DU060_XD48 01CJA00_DE002_ZG31 01MKC65_EM001_YL01
EXC EXTERNAL SETPOINT VALIDATION
IN3 IN1 IN RE Ini:
01MKC65_DE001_XL21 IN2 ON
EXCIT AUTO CHANNEL IN OPERATION
Ini:
IO:L01_01 Rack:0 Slot:ST8 (X20DI9371) Point:0
DETECTED EXCTATION EXTERNAL SETPOINT VALIDATION
(VOLT AI & AO VALID or
REACTIVE POWER AI&AO VALID)
01MKC65_DU060_XD48
EXTERNAL SETPOINT FAULT AO validation from EXC modbus
Ini:0 (NO)
S:EU001
YES
01CJA00_DE002_ZK32
10
AND
01MKC65_DE001_XL21
IN1
01CJA00_CE023_ZQ01
IN2
1
OR 01CJA00_CE023_ZQ01
01CJA00_DE002_ZQ01_V 01CJA00_CE023_ZQ01 UNIT Vab or Q Measurement VALIDATION
IN1 Ini:0 (FAULT)
01CJA00_DE003_ZQ01_V
IN2 NORMAL 0
15
8 IV
01CJA00_DE002_ZL33 OR RS 01CJA00_DE002_ZG33
REACTIVE POWER CTRL MODE: PULSE/PULSE CMD 01CJA00_DE002_ZL33 01CJA00_DE002_ZG33 REACTIVE POWER CTRL MODE: PULSE/PULSE
Ini: IN1 S Q1 Ini:
HMI DB Number:19 01MKC65_GH001_XL31
IN2 R1 /Q1 SELECTED
SENT 01MKC65_DE001_XL21
IN3
7 IN4
AND
01CJA00_CE001_ZQ02 14
IN1 OR
01CJA00_CE001_ZQ03
IN2 IN1
IN2
XX DE002 : UNIT REACTIVE POWER CONTROL - REV : 210 - 14/JAN/17 09:21 - POUName : L01_5ACT
.168/A
VOLTAGE AI INVALID &
EXC REA REGULATOR NOT ACTIVE
35
21 22 34 IV
AND R_TRIG OR RS 01CJA00_DE002_ZG41
01MKC65_DE001_XG03 01CJA00_DE003_ZQ01_V 01CJA00_DE002_ZG41 REACTIVE CTRL OBJECT: REA PWR
IN1 IN RE IN1 S Q1 Ini:
EXCIT REACTIVE POWER REGULATION 01MKC65_DE001_XG03 01CJA00_DE002_ZA11 01CJA00_DE002_ZG42
Ini: IN2 IN2 R1 /Q1 SELECTED
IO:L01_01 Rack:0 Slot:ST8 (X20DI9371) Point:1 01BAC00_GS901_XG01
DETECTED IN3 IN3
01CJA00_CE001_ZQ03
IN4
01CJA00_DE002_ZA11
SET REA.POWER TO 0
Ini: 43
S:SFC... MOVE_B
YES 01MKC65_EM001_YL41
01CJA00_DE002_ZG41 01MKC65_EM001_YL41
REACT POWER REGULATION ON SELECTION
33 IN RE Ini:
01CJA00_DE002_ZL41 AND ON
REACTIVE CTRL OBJECT: REA PWR SEL CMD 01CJA00_DE002_ZL41
Ini: IN1
HMI DB Number:19
SENT IN2
01CJA00_DE002_ZK41
32
01MKC65_GH001_XL31 AND
EXCITATION CONTROL LEVEL 01MKC65_GH001_XL31 44
Ini: IN1 MOVE_B 01MKC65_EM001_YL42
IO:L01_01 Rack:0 Slot:ST7 (X20DI9371) Point:8 01MKC65_DE001_XG03 01CJA00_DE002_ZG42 01MKC65_EM001_YL42
REACT POWER REGULATION OFF SELECTION
REMOTE IN2 IN RE Ini:
01CJA00_CE001_ZQ03
IN3 ON
01BAC00_GS901_XG01 01MKC65_DE001_XL21
IN4
UNIT GCB GS901 IN CLOSED POSTION 01BAC00_GS901_XG01
Ini: IN5
IO:L01_01 Rack:0 Slot:ST5 (X20DI9371) Point:1
DETECTED 01CJA00_DE002_ZG42
REACTIVE CTRL OBJECT: VOLTAGE
2 Ini:
MOVE_B 01CJA00_CE001_ZQ03 SELECTED
01CJA00_DE002_ZQ01_V 01CJA00_CE001_ZQ03 UNIT REACTIVE POWER MEASUREMENT VALIDATION
IN RE Ini:0 (NORMAL)
FAULT
23 24 31
AND R_TRIG OR
01MKC65_DE001_XG03 01CJA00_CE001_ZQ03
IN1 IN RE IN1
EXCIT REACTIVE POWER REGULATION 01MKC65_DE001_XG03
Ini: IN2 IN2
IO:L01_01 Rack:0 Slot:ST8 (X20DI9371) Point:1 01BAC00_GS901_XG01
DETECTED IN3
30
01CJA00_DE002_ZL42 AND
REACTIVE CTRL OBJECT: VOLTAGE SEL CMD 01CJA00_DE002_ZL42
Ini: IN1
HMI DB Number:19
SENT IN2
01CJA00_DE002_ZK42
29
01CJA00_CE001_ZQ02 AND
UNIT VOLTAGE PHASE AB AI VALIDATION 01CJA00_CE001_ZQ02
Ini:0 (NORMAL) IN1
S:FE001 01MKC65_GH001_XL31
FAULT IN2
01MKC65_DE001_XL21
IN3
01BAC00_GS901_XG01
IN4
XX DE002 : UNIT REACTIVE POWER CONTROL - REV : 210 - 14/JAN/17 09:21 - POUName : L01_5ACT
.169/A
16
01CJA00_EU001_ZG33 AND 01CJA00_DE002_ZG01
UNIT IN G/GC DERECT OPERATION 01CJA00_EU001_ZG33 01CJA00_DE002_ZG01 REACTIVE POWER SETPOINT ENABLED
Ini:0 (N-DET) IN1 Ini:
S:STA 01CJA00_DE002_ZG33
IN2 SELECTED
DETECTED 01MKC65_GH001_XL31
IN3
01CJA00_DE002_ZG33
01MKC65_DE001_XG03
IN4
REACTIVE POWER CTRL MODE: PULSE/PULSE 01BAC00_GS901_XG01
Ini: IN5
S:DE002 01CJA00_CE001_ZQ03
SELECTED IN6
01MKC65_GH001_XL31
EXCITATION CONTROL LEVEL
Ini: REACTIVE POWER AI VALID
IO:L01_01 Rack:0 Slot:ST7 (X20DI9371) Point:8 GCB CLOSED
REMOTE
EXECITATION IN REMOTE
01MKC65_DE001_XG03
EXCIT REACTIVE POWER REGULATION
Ini:
IO:L01_01 Rack:0 Slot:ST8 (X20DI9371) Point:1
DETECTED
01BAC00_GS901_XG01
UNIT GCB GS901 IN CLOSED POSTION
Ini:
IO:L01_01 Rack:0 Slot:ST5 (X20DI9371) Point:1
DETECTED
01CJA00_CE001_ZQ03
UNIT REACTIVE POWER MEASUREMENT VALIDATION
Ini:0 (NORMAL)
S:DE002
FAULT
18
01CJA00_DE002_ZR01 FB_HMI_SP 01CJA00_DE002_ZP02
REACTIVE POWER SP CMD 01CJA00_DE002_ZR01 01CJA00_DE002_ZP02 REACTIVE POWER SP INTERNAL
Unit: Mvar IN SP Unit: Mvar
HMI DB Number:19 01CJA00_DE002_ZG01
Enable -12000/12000 (-120/120 Mvar)
-12000/12000 (-120/120 Mvar) 01CJA00_DE002_ZU01 01CJA00_DE002_ZM01
Min Sp Forced
01CJA00_DE002_ZU01 01CJA00_DE002_ZW01
REACTIVE POWER MIN SP VALUE Init Sp
Ini:-10000 (-100 Mvar) 01CJA00_DE002_ZA11
Init Cmd
-12000/12000 (-120/120 Mvar) Forc_min
01CJA00_DE002_ZA01
01CJA00_DE002_ZW01 Forc_0
01CJA00_DE002_ZQ01
REACTIVE POWER Init sp value Follow
Ini:0 (0 Mvar)
Scale
-12000/12000 (-120/120 Mvar)
01CJA00_DE002_ZV01
01CJA00_DE002_ZA11
SET REA.POWER TO 0
Ini:
S:SFC... 01CJA00_DE002_ZP01
YES REACTIVE POWER SP FEEDBACK
Unit: Mvar
01CJA00_DE002_ZA01 -12000/12000 (-120/120 Mvar)
Force REACTIVE POWER sp to 0
Ini:0 19
S:SFC LIMIT
01CJA00_DE002_LO 01CJA00_DE002_ZP01
LO RE 01CJA00_DE002_ZH06
01CJA00_DE002_ZQ01 01CJA00_DE002_ZP02 01CJA00_DE002_ZH06 REACTIVER SETPOINT OVER HIGH LIMIT
IN HL Ini:
REACTIVE POWER MEAS VALUE 01CJA00_DE002_HI 01CJA00_DE002_ZH04
Ini:0 (0 Mvar) HI LL DETECTED
S:FE001
-12000/12000 (-120/120 Mvar)
01CJA00_DE002_ZH04
01CJA00_DE002_LO REACTIVER SETPOINT LESS LOW LIMIT
REACTIVE POWER LOW LIMIT Ini:
Ini:-10000 (-100 Mvar) DETECTED
XX DE002 : UNIT REACTIVE POWER CONTROL - REV : 210 - 14/JAN/17 09:21 - POUName : L01_5ACT
.170/A
20 25 28 36
SUB ABS GE SEL
01CJA00_DE002_ZP01
IN1 RE IN IN1 RE G RE
01CJA00_DE002_ZQ01 01CJA00_DE002_TH01 01CJA00_DE002_TN1 : 8.00000
IN2 IN2 IN1
01CJA00_DE002_TN2 : 10.00000
IN2
01CJA00_DE002_TH01
REACTIVE POWER DLT THR 37
Ini:3000 (30 Mvar) SEL
38
26 TP TN
01CJA00_DE002_ZP01 FB_PULS_REG 01CJA00_DE002_INC
REACTIVE POWER SP FEEDBACK OSC_B
01CJA00_DE002_ZP01 01CJA00_DE002_INC REA POWER INCREASE PULSE
Unit: Mvar SP Inc IN RE Ini:
S:DE002 01CJA00_DE002_ZQ01
-12000/12000 (-120/120 Mvar) Meas Dec
Enable
01CJA00_DE002_ZQ01 01CJA00_DE002_ZZ01
Dead
REACTIVE POWER MEAS VALUE 01CJA00_DE002_ZX01
Ini:0 (0 Mvar) Rate(%) 39
S:FE001 01CJA00_DE002_DLT
-12000/12000 (-120/120 Mvar) Max_delta
01CJA00_DE002_ZT01 TP TN
T0(Cyc) OSC_B 01CJA00_DE002_DEC
01CJA00_DE002_ZG32
01CJA00_DE002_DEC REA POWER DECREASE PULSE
IN RE Ini:
REACTIVE POWER CTRL MODE: ANA/PULSE
Ini: DETECTED
S:DE002
SELECTED 17
AND
01CJA00_DE002_ZG01 01CJA00_DE002_ZG32
IN1
REACTIVE POWER SETPOINT ENABLED 01CJA00_DE002_ZG01
Ini: IN2
S:DE002
SELECTED
01CJA00_DE002_ZZ01
PULSE REGUL DEAD BAND
Ini:200 (2 Mvar)
01CJA00_DE002_ZX01
PULSE REGUL DELTA RATE(%)
Ini:50
-32768/32767
01CJA00_DE002_ZT01
PULSE REGUL INTERVAL TIME(CYC)
Ini:50
-32768/32767
XX DE002 : UNIT REACTIVE POWER CONTROL - REV : 210 - 14/JAN/17 09:21 - POUName : L01_5ACT
.171/A
4.51 CON : CONDITIONS - REV : 27 - 22/DEC/16 11:54 - POUName : L01_3CON
01CJA00_EA001_ZS010
1 2
01CJA00_EU001_ZA01 AND AND 01CJA00_EA001_ZS015
ANY UNIT STOP CMD 01CJA00_EU001_ZA01 01CJA00_EA001_ZS015 01
Ini:0 (N-REQ) IN1 IN1 Ini:
S:CON 1 1
REQ IN2 IN2 CORRECT
01CJA00_EA001_ZS020
3 4
01CJA00_EU001_ZG12 AND AND 01CJA00_EA001_ZS025
UNIT P<MIN or WICKET OPEN<NO LOAD or INTAKE GATE CLOSED 01CJA00_EU001_ZG12 01CJA00_EA001_ZS025 02
Ini: IN1 IN1 Ini:
S:CON 01BBA00_DE003_ZZ03 1
DETECTED IN2 IN2 CORRECT
01BBA00_DE003_ZZ03
UNIT Q<MIN or Step time delay 15s
Ini:
S:CON
DETECTED
01CJA00_EA001_ZS030
5 6
01BAC00_GS901_XG02 AND AND 01CJA00_EA001_ZS035
UNIT GCB GS901 IN OPEN POSTION 01BAC00_GS901_XG02 01CJA00_EA001_ZS035 03
Ini: IN1 IN1 Ini:
IO:L01_01 Rack:0 Slot:ST5 (X20DI9371) Point:2 01BAC00_GS901_XG01 1
IN2 IN2 CORRECT
DETECTED
01BAC00_GS901_XG01
UNIT GCB GS901 IN CLOSED POSTION
Ini:
IO:L01_01 Rack:0 Slot:ST5 (X20DI9371) Point:1
DETECTED
01CJA00_EA001_ZS040
7 8
01MKC65_GS101_XG02 AND AND 01CJA00_EA001_ZS045
EXCIT FIELD BREAKER OPEN 01MKC65_GS101_XG02 01CJA00_EA001_ZS045 04
Ini: IN1 IN1 Ini:
IO:L01_01 Rack:0 Slot:ST8 (X20DI9371) Point:5 01MKC65_GS101_XG01 1
IN2 IN2 CORRECT
DETECTED
01MKC65_GS101_XG01
EXCIT FIELD BREAKER CLOSED
Ini:
IO:L01_01 Rack:0 Slot:ST8 (X20DI9371) Point:4
DETECTED
01CJA00_EA001_ZS050
9 10
01CJA00_EU001_ZG13 AND AND 01CJA00_EA001_ZS055
WICKET GATE or INTAKE GATE CLOSED 01CJA00_EU001_ZG13 01CJA00_EA001_ZS055 05
Ini:0 (N-DET) IN1 IN1 Ini:
S:CON 1 1
IN2 IN2 CORRECT
DETECTED
3
MOVE_B 01CJA00_EA001_ZS011
01CJA00_EA001_SFC_S1_X 01CJA00_EA001_ZS011 01
IN RE Ini:0 (N-PROGR)
IN-PROGR
4
MOVE_B 01CJA00_EA001_ZS021
01CJA00_EA001_SFC_S2_X 01CJA00_EA001_ZS021 02
IN RE Ini:
IN-PROGR
5
MOVE_B 01CJA00_EA001_ZS031
01CJA00_EA001_SFC_S3_X 01CJA00_EA001_ZS031 03
IN RE Ini:
IN-PROGR
6
MOVE_B 01CJA00_EA001_ZS041
01CJA00_EA001_SFC_S4_X 01CJA00_EA001_ZS041 04
IN RE Ini:
IN-PROGR
01CJA00_EA001_ZT001 : 5.00000
7
TP
TON_R
01CJA00_EA001_SFC_S1_X 01CJA00_EA001_ZD001
IN REB
RET
14
01CJA00_EA100_ZG21 AND 01CJA00_EA001_ZM01
UNIT LCU AUTO MODE 01CJA00_EA100_ZG21 01CJA00_EA001_ZM01
SQ01: GE/SR/CH/BS ->NMS SEQ OVER
Ini: IN1 Ini:
S:CON PRESENCE
SELECTED
01CJA00_EA001_ZT01 : 12000 10 IN2
10 11
9 TP TP
AND TON_D TOF_R
8
01CJA00_EA100_ZG21
OR IN1 IN REB IN REB
1
01CJA00_EA001_ZG01 F_TRIG IN1 IN2 RET RET
SQ01: GE/SR/CH/BS ->NMS SEQ
Ini: IN RE IN2
S:SFC...
IN-PROGR 12 13
OR SEL 01CJA00_EA001_ZQ01
2 01CJA00_EA001_ZQ01
01CJA00_EU001_ZG01 F_TRIG SQ01: GE/SR/CH/BS ->NMS SEQ TIME
IN1 G RE Ini:0 (0 s)
UNIT STILL STOP STATE 01CJA00_EU001_ZG01
Ini:0 (NO) IN RE IN2 IN1 0/360000 (0/3600 s)
S:SFC
YES IN2
01CJA00_EA002_ZS010
1 2
01CJA00_EU001_ZA01 AND AND 01CJA00_EA002_ZS015
ANY UNIT STOP CMD 01CJA00_EU001_ZA01 01CJA00_EA002_ZS015 01
Ini:0 (N-REQ) IN1 IN1 Ini:
S:CON 1 1
REQ IN2 IN2 CORRECT
01CJA00_EA002_ZS020
3 4
01BBA00_DE003_ZZ03 AND AND 01CJA00_EA002_ZS025
UNIT Q<MIN or Step time delay 15s 01BBA00_DE003_ZZ03 01CJA00_EA002_ZS025 02
Ini: IN1 IN1 Ini:
S:CON 1 1
DETECTED
IN2 IN2 CORRECT
01CJA00_EA002_ZS030
5 6
01BAC00_GS901_XG02 AND AND 01CJA00_EA002_ZS035
UNIT GCB GS901 IN OPEN POSTION 01BAC00_GS901_XG02 01CJA00_EA002_ZS035 03
Ini: IN1 IN1 Ini:
IO:L01_01 Rack:0 Slot:ST5 (X20DI9371) Point:2 01BAC00_GS901_XG01 1
IN2 IN2 CORRECT
DETECTED
01BAC00_GS901_XG01
UNIT GCB GS901 IN CLOSED POSTION
Ini:
IO:L01_01 Rack:0 Slot:ST5 (X20DI9371) Point:1
DETECTED
01CJA00_EA002_ZS040
7 8
01MKC65_GS101_XG02 AND AND 01CJA00_EA002_ZS045
EXCIT FIELD BREAKER OPEN 01MKC65_GS101_XG02 01CJA00_EA002_ZS045 04
Ini: IN1 IN1 Ini:
IO:L01_01 Rack:0 Slot:ST8 (X20DI9371) Point:5 01MKC65_GS101_XG01 1
IN2 IN2 CORRECT
DETECTED
01MKC65_GS101_XG01
EXCIT FIELD BREAKER CLOSED
Ini:
IO:L01_01 Rack:0 Slot:ST8 (X20DI9371) Point:4
DETECTED
01CJA00_EA002_ZS050
9 10
01CJA00_EU001_ZG13 AND AND 01CJA00_EA002_ZS055
WICKET GATE or INTAKE GATE CLOSED 01CJA00_EU001_ZG13 01CJA00_EA002_ZS055 05
Ini:0 (N-DET) IN1 IN1 Ini:
S:CON 1 1
IN2 IN2 CORRECT
DETECTED
3
MOVE_B 01CJA00_EA002_ZS011
01CJA00_EA002_SFC_S1_X 01CJA00_EA002_ZS011 01
IN RE Ini:0 (N-PROGR)
IN-PROGR
4
MOVE_B 01CJA00_EA002_ZS021
01CJA00_EA002_SFC_S2_X 01CJA00_EA002_ZS021 02
IN RE Ini:
IN-PROGR
5
MOVE_B 01CJA00_EA002_ZS031
01CJA00_EA002_SFC_S3_X 01CJA00_EA002_ZS031 03
IN RE Ini:
IN-PROGR
6
MOVE_B 01CJA00_EA002_ZS041
01CJA00_EA002_SFC_S4_X 01CJA00_EA002_ZS041 04
IN RE Ini:
IN-PROGR
01CJA00_EA002_ZT001 : 5.00000
7
TP
TON_R
01CJA00_EA002_SFC_S1_X 01CJA00_EA002_ZD001
IN REB
RET
14
01CJA00_EA100_ZG21 AND 01CJA00_EA002_ZM01
UNIT LCU AUTO MODE 01CJA00_EA100_ZG21 01CJA00_EA002_ZM01
SQ02: GC ->NMS SEQ OVERTIME
Ini: IN1 Ini:
S:CON PRESENCE
SELECTED
01CJA00_EA002_ZT01 : 12000 10 IN2
10 11
9 TP TP
AND TON_D TOF_R
8
01CJA00_EA100_ZG21
OR IN1 IN REB IN REB
1
01CJA00_EA002_ZG01 F_TRIG IN1 IN2 RET RET
SQ02: GC ->NMS SEQ
Ini: IN RE IN2
S:SFC...
IN-PROGR 12 13
OR SEL 01CJA00_EA002_ZQ01
2 01CJA00_EA002_ZQ01
01CJA00_EU001_ZG01 F_TRIG SQ02: GC ->NMS SEQ TIME COUNT
IN1 G RE Ini:0 (0 s)
UNIT STILL STOP STATE 01CJA00_EU001_ZG01 01CJA00_EA002_ZQ01
Ini:0 (NO) IN RE IN2 IN1 0/360000 (0/3600 s)
S:SFC
YES IN2
01CJA00_EA100_ZA51
STEP MODE CONDITION
Ini:
S:CON
01CJA00_EA051_ZS010
1 2
01CJA00_EU001_ZM06 AND AND 01CJA00_EA051_ZS015
UNIT PERMANENT START CONDITION 01CJA00_EU001_ZM06 01CJA00_EA051_ZS015
STEP01 COND
Ini: IN1 IN1 Ini:
S:CON 01MAU24_CP001_ZH04 01CJA00_EA100_ZA51
ESTABL
IN2 IN2 CORRECT
01MAU24_CL002_XH51
IN3
01MAU24_CP001_ZH04
GOV ACCUMULATOR OIL PRESSURE BUILDUP
Ini:0 (N-DET)
S:EU014
DETECTED
01MAU24_CL002_XH51
GOV ACCUMULATOR OIL LEVEL BUILD UP
Ini:
IO:L01_01 Rack:0 Slot:ST13 (X20DI9371) Point:6
DETECTED
01CJA00_EA051_ZS020
3 4
01BAC00_GS003_XG01 AND AND 01CJA00_EA051_ZS025
UNIT DISCONNECTOR GS003 (901-3) CLOSED 01BAC00_GS003_XG01 01CJA00_EA051_ZS025
STEP02 COND
Ini: IN1 IN1 Ini:
IO:L01_01 Rack:0 Slot:ST6 (X20DI9371) Point:1 1 01CJA00_EA100_ZA51
CLOSED
IN2 IN2 CORRECT
01CJA00_EA051_ZS030
5 6
01CJA00_EE101_ZG01 AND AND 01CJA00_EA051_ZS035
INTAKE GATE FULLY OPEN 01CJA00_EE101_ZG01 01CJA00_EA051_ZS035
STEP03 COND
Ini:0 (N-DET) IN1 IN1 Ini:
S:CON 01MKA54_CG565_ZG01 01CJA00_EA100_ZA51
IN2 IN2 CORRECT
DETECTED
01MKA54_CG565_ZG01
MECHANICAL BRAKING LIMIT SWITCHES SQ01-SQ18
Ini:0 (N-RELEAS)
S:AU001
RELEASE
463/1(+1p)
01MEA41_CG015_XG01
WICKET GATE FULL CLOSED(CG015S)
Ini:
IO:L01_02 Rack:0 Slot:ST6 (X20DI9371) Point:10
DETECTED
01BAC00_GS003_XG01
UNIT DISCONNECTOR GS003 (901-3) CLOSED
Ini:
IO:L01_01 Rack:0 Slot:ST6 (X20DI9371) Point:1
CLOSED
01BAC00_GS035_XG02
UNIT EARTHING SWITCH (901-35) OPEN
Ini:
IO:L01_01 Rack:0 Slot:ST6 (X20DI9371) Point:4
DETECTED
01BAC00_GS038_XG02
UNIT EARTHING SWITCH (901-38) OPEN
Ini:
IO:L01_01 Rack:0 Slot:ST6 (X20DI9371) Point:6
DETECTED
01CJA00_EA051_ZS050
9 10
01BAC00_GS901_XG01 AND AND 01CJA00_EA051_ZS055
UNIT GCB GS901 IN CLOSED POSTION 01BAC00_GS901_XG01 01CJA00_EA051_ZS055
STEP05 COND
Ini: IN1 IN1 Ini:
IO:L01_01 Rack:0 Slot:ST5 (X20DI9371) Point:1 01MEU11_EU001_ZG21 1
IN2 IN2 CORRECT
DETECTED
01MEU11_EU001_ZG21
GOV Insolated Network R128
Ini:0 (N-SEL)
S:EU001
SELECTED
01CJA00_EA051_ZS060
11 12
01MKC65_DE001_XG04 AND AND 01CJA00_EA051_ZS065
EXCIT LINE CHARGING IN OPERATION 01MKC65_DE001_XG04 01CJA00_EA051_ZS065
STEP06 COND
Ini: IN1 IN1 Ini:
IO:L01_01 Rack:0 Slot:ST8 (X20DI9371) Point:2 1 01CJA00_EA100_ZA51
IN2 IN2 CORRECT
DETECTED
01CJA00_EA051_ZS070
13 14
01MKC65_GS101_XG01 AND AND 01CJA00_EA051_ZS075
EXCIT FIELD BREAKER CLOSED 01MKC65_GS101_XG01 01CJA00_EA051_ZS075
STEP07 COND
Ini: IN1 IN1 Ini:
IO:L01_01 Rack:0 Slot:ST8 (X20DI9371) Point:4 01MEU11_FS001_ZM51 1
IN2 IN2 CORRECT
DETECTED 01MEU11_FS001_XH05
IN3
01MEU11_FS001_ZM51 01BBA00_DE003_ZH07
GOVERNOR T-ADT MEASUREMENT IN4
Ini:0 (FAULT)
S:EU001
NORMAL
01MEU11_FS001_XH05
RV05 >95% SYNCHRONISATION LAUNCH
Ini:
IO:L01_01 Rack:0 Slot:ST11 (X20DI9371) Point:2
DETECTED
01BBA00_DE003_ZH07
UNIT VOLTAGE >95%Un
Ini:0 (N-DET)
S:FE001
DETECTED
3
MOVE_B 01CJA00_EA051_ZS011
01CJA00_EA051_SFC_S1_X 01CJA00_EA051_ZS011 STEP01
IN RE Ini:
IN-PROGR
4
MOVE_B 01CJA00_EA051_ZS021
01CJA00_EA051_SFC_S2_X 01CJA00_EA051_ZS021 STEP02
IN RE Ini:
IN-PROGR
5
MOVE_B 01CJA00_EA051_ZS031
01CJA00_EA051_SFC_S3_X 01CJA00_EA051_ZS031 STEP03
IN RE Ini:
IN-PROGR
6
MOVE_B 01CJA00_EA051_ZS041
01CJA00_EA051_SFC_S4_X 01CJA00_EA051_ZS041 STEP04
IN RE Ini:
IN-PROGR
7
MOVE_B 01CJA00_EA051_ZS051
01CJA00_EA051_SFC_S5_X 01CJA00_EA051_ZS051 STEP05
IN RE Ini:
IN-PROGR
8
MOVE_B 01CJA00_EA051_ZS061
01CJA00_EA051_SFC_S6_X 01CJA00_EA051_ZS061 STEP06
IN RE Ini:
IN-PROGR
01CJA00_EA051_ZT002 : 5.00000
9
TP
TON_R
01CJA00_EA051_ZS031 01CJA00_EA051_ZD002
IN REB
RET
16
01CJA00_EA100_ZG21
Unit LCU Auto Mode AND 01CJA00_EA051_ZM01
UNIT LCU AUTO MODE 01CJA00_EA100_ZG21 01CJA00_EA051_ZM01
SQ51: TS->BS SEQ OVERTIME
Ini: IN1 Ini:
S:CON PRESENCE
SELECTED
IN2
01CJA00_EA051_ZT01 10
12 13
11 TP TP
AND TON_D TOF_R
10
01CJA00_EA100_ZG21
OR IN1 IN REB IN REB
1
01CJA00_EA051_ZG01 F_TRIG IN1 IN2 RET RET
SQ51: TS->BS SEQ
Ini: IN RE IN2
S:SFC...
IN-PROGR
14 15
OR SEL 01CJA00_EA051_ZQ01
2 01CJA00_EA051_ZQ01
01CJA00_EU001_ZG01 F_TRIG SQ51: TS->BS SEQ TIME COUNT
IN1 G RE Ini:0 (0 s)
UNIT STILL STOP STATE 01CJA00_EU001_ZG01
Ini:0 (NO) IN RE IN2 IN1 0/360000 (0/3600 s)
S:SFC
YES
IN2
4
01BAC00_GS003_ZA01 FB_CB 01BAC00_GS003_YL01
UNIT DS GS003 (901-3) AUTO CLOSE ORD 01BAC00_GS003_ZA01 01BAC00_GS003_YL01 UNIT DS GS003 (901-3) CLOSE COMMAND
Ini:0 (N-CLSG) CL_A OR1 Ini:
S:SFC...
CLOSING
CL_M DS1 CLOSING
01BAC00_GS003_ZC01
CL_A_ATH
01BAC00_GS003_ZJ01
01BAC00_GS003_XG01 CL_M_ATH
UNIT DISCONNECTOR GS003 (901-3) CLOSED 01BAC00_GS003_XG01 01BAC00_GS003_ZM11
Ini: CL_PS TLTE1
IO:L01_01 Rack:0 Slot:ST6 (X20DI9371) Point:1 01BAC00_GS003_XG01_V
CLOSED CL_PS_V
01BAC00_GS003_YL02
01BAC00_GS003_ZA02
01BAC00_GS003_ZA02 01BAC00_GS003_YL02 UNIT DS GS003 (901-3) OPEN COMMAND
OP_A OR2 Ini:
UNIT DS GS003 (901-3) AUTO OPEN ORD
Ini:0 (N-OPNG) OP_M DS2 OPENING
S:SFC... 01BAC00_GS003_ZC02
OPENING
OP_A_ATH
01BAC00_GS003_ZJ02
OP_M_ATH
01BAC00_GS003_XG02 01BAC00_GS003_ZM12
01BAC00_GS003_XG02 OP_PS TLTE2
UNIT DISCONNECTOR GS003 (901-3) OPEN 01BAC00_GS003_XG02_V
Ini: OP_PS_V
IO:L01_01 Rack:0 Slot:ST6 (X20DI9371) Point:2
OPEN 2 01BAC00_GS003_ZM00 01BAC00_GS003_ZM10
AND FLT_IN ALARM
01BAC00_GS003_XL31 01BAC00_GS003_ZM50
IN1 AV REM_ATH
1 01BAC00_GS003_ZM09
IN2 EXTRD
0
MANU
01BAC00_GS003_XL31
UNIT DS GS003 (901-3) CONTROL IN REMOTE 01BAC00_GS003_ZT11 : 1000
Ini: TLTE
IO:L01_01 Rack:0 Slot:ST6 (X20DI9371) Point:0 01BAC00_GS003_ZT01 : 200
DETECTED
CL_PL 01BAC00_GS003_ZU01
01BAC00_GS003_ZT02 : 200 01BAC00_GS003_ZU01 UNIT DS GS003 (901-3) ANIMATION WORD
OP_PL SIG Ini:
01BAC00_GS003_ZT00 : 1000 01BAC00_GS003_ZU01_V
F_TP SIG_V 0/127
Type
01CJA00_EB000_RI01 : 5.00000
15
7 TP
01CJA00_EU100_PS FB_UV_BV TOF_R 01CJA00_EU100_ZM51
Supply status (0:OK ; 4:No Power Supply ; 5:Supply warning for ; 128:Global err) 01CJA00_EU100_PS 01CJA00_EU100_ZM51 L01_01 ST00 PS9400 POWER SUPPLY
Ini: USINT VALID IN REB Ini:
IO:L01_01 Rack:0 Slot:ST0 (X20BC8084-PS9400) Point:0
FORC_V RET NORMAL
01CJA00_EU100_ZM01
L04_01 ST00 PS9400 POWER SUPPLY
Ini:
S:EB000
FAULT
01CJA00_EB000_RI01 : 5.00000
16
4 TP
01CJA00_EU115_PS FB_UV_BV TOF_R 01CJA00_EU115_ZM51
Supply status (0:OK ; 4:No Power Supply ; 5:Supply warning for ; 128:Global err) 01CJA00_EU115_PS 01CJA00_EU115_ZM51 L01_01 ST15 PS3300 POWER SUPPLY
Ini: USINT VALID IN REB Ini:
IO:L01_01 Rack:0 Slot:ST15 (X20PS3300) Point:0
FORC_V RET NORMAL
01CJA00_EU115_ZM01
L01_01 ST15 PS3300 POWER SUPPLY
Ini:
S:EB000
FAULT
01CJA00_EB000_RI01 : 5.00000
17
5 TP
01CJA00_EU200_PS FB_UV_BV TOF_R 01CJA00_EU200_ZM51
Supply status (0:OK ; 4:No Power Supply ; 5:Supply warning for ; 128:Global err) 01CJA00_EU200_PS 01CJA00_EU200_ZM51 L01_02 ST01 PS9400 POWER SUPPLY
Ini: USINT VALID IN REB Ini:
IO:L01_02 Rack:0 Slot:ST0 (X20BC8084-PS9400) Point:0
FORC_V RET NORMAL
01CJA00_EU200_ZM01
L01_02 ST00 PS9400 POWER SUPPLY
Ini:
S:EB000
FAULT
01CJA00_EB000_RI01 : 5.00000
18
6 TP
01CJA00_EU213_PS FB_UV_BV TOF_R 01CJA00_EU213_ZM51
Supply status (0:OK ; 4:No Power Supply ; 5:Supply warning for ; 128:Global err) 01CJA00_EU213_PS 01CJA00_EU213_ZM51 L01_02 ST13 PS3300 I/O POWER SUPPLY
Ini: USINT VALID IN REB Ini:
IO:L01_02 Rack:0 Slot:ST13 (X20PS3300) Point:0 NORMAL
FORC_V RET
01CJA00_EU213_ZM01
L01_02 ST13 PS3300 POWER SUPPLY
Ini:
S:EB000
FAULT
01CJA00_EB000_RI01 : 5.00000
19
8 TP
01CJA00_EU300_PS FB_UV_BV TOF_R 01CJA00_EU300_ZM51
Supply status (0:OK ; 4:No Power Supply ; 5:Supply warning for ; 128:Global err) 01CJA00_EU300_PS 01CJA00_EU300_ZM51 L01_03 ST01 PS9400 POWER SUPPLY
Ini: USINT VALID IN REB Ini:
IO:L01_03 Rack:0 Slot:ST0 (X20BC8084-PS9400) Point:0 NORMAL
FORC_V RET
01CJA00_EU300_ZM01
L01_03 ST00 PS9400 POWER SUPPLY
Ini:
S:EB000
FAULT
10
AND 01CJA00_EN001_ZM53
01CJA00_EN001_ZM53 L01_01 CE1000 I/O CONTROLLER E8000-2
IN1 Ini:
IN2 PRESENCE
2
CUR_EPL_PRES
2
EQPT_NUM 01CJA00_EN002_ZM51
01CJA00_EN002_ZM51 L01_02 CE1000 I/O CONTROLLER
LINK_PRES Ini:
LINK1_PRES PRESENCE
LINK2_PRES 11
AND 01CJA00_EN002_ZM52
01CJA00_EN002_ZM52 L01_02 CE1000 I/O CONTROLLER E8000-1
IN1 Ini:
IN2 PRESENCE
12
AND 01CJA00_EN002_ZM53
01CJA00_EN002_ZM53 L01_02 CE1000 I/O CONTROLLER E8000-2
IN1 Ini:
IN2 PRESENCE
3
CUR_EPL_PRES
3
EQPT_NUM 01CJA00_EN003_ZM51
01CJA00_EN003_ZM51 L01_03 CE1000 I/O CONTROLLER
LINK_PRES Ini:
LINK1_PRES PRESENCE
LINK2_PRES 13
AND 01CJA00_EN003_ZM52
01CJA00_EN003_ZM52 L01_03 CE1000 I/O CONTROLLER E8000-1
IN1 Ini:
IN2 PRESENCE
14
AND 01CJA00_EN003_ZM53
01CJA00_EN003_ZM53 L01_03 CE1000 I/O CONTROLLER E8000-2
IN1 Ini:
IN2 PRESENCE
01CJA00_EU213_ZM51
L01_02 ST13 PS3300 I/O POWER SUPPLY
Ini:
S:EB000
NORMAL
01CJA00_EU300_ZM51
L01_03 ST01 PS9400 POWER SUPPLY
Ini:
S:EB000
NORMAL
01CJA00_EN001_ZM51
L01_01 CE1000 I/O CONTROLLER
Ini:
S:EB000
PRESENCE
01CJA00_EN002_ZM51
L01_02 CE1000 I/O CONTROLLER
Ini:
S:EB000
PRESENCE
01CJA00_EN003_ZM51
L01_03 CE1000 I/O CONTROLLER
Ini:
S:EB000
PRESENCE
21
01CJA00_EN000_ZM51 MOVE_B 01CJA00_EN001_YM01
L01 UNIT01 LCU WATCHDOG 01CJA00_EN000_ZM51 01CJA00_EN001_YM01 CONTROLLER WATCHDOG
Ini:1 (NORMAL) IN RE Ini:
S:EB000 NORMAL
NORMAL
9
01BAC00_GS901_XG01 AND
UNIT GCB GS901 IN CLOSED POSTION 01BAC00_GS901_XG01 01BAC00_GS901_ZC01
Ini: IN1
IO:L01_01 Rack:0 Slot:ST5 (X20DI9371) Point:1 01BAC00_GS901_XG02
DETECTED
IN2
01BAC00_GS003_XG01
IN3
01BAC00_GS901_XG02 01BAC00_GS003_XG02
UNIT GCB GS901 IN OPEN POSTION IN4
Ini:
01BAC00_GS005_XG01
IN5
IO:L01_01 Rack:0 Slot:ST5 (X20DI9371) Point:2 01BAC00_GS005_XG02
DETECTED IN6
01BAC00_GS035_XG01
01BAC00_GS003_XG01
IN7
01BAC00_GS035_XG02
UNIT DISCONNECTOR GS003 (901-3) CLOSED IN8
Ini: 01BAC00_GS038_XG01
IO:L01_01 Rack:0 Slot:ST6 (X20DI9371) Point:1 IN9
CLOSED
01BAC00_GS038_XG02
I10
01BAC00_GS901_ZM00
01BAC00_GS003_XG02 I11
UNIT DISCONNECTOR GS003 (901-3) OPEN 01BAC00_GS901_ZM50
Ini:
I12
IO:L01_01 Rack:0 Slot:ST6 (X20DI9371) Point:2
22 23
OPEN
AND OR 01BAC00_GS901_YL03
01BAC00_GS005_XG01
01BAC00_GS901_ZC01 01BAC00_GS901_YL03
UNIT GCB SYNCHRO/DEADLINE CLOSE AUTHORIZATION
IN1 IN1 Ini:
UNIT EARTHING SWITCH (901-5) CLOSED 01BAC00_GS901_ZA03 01BAC00_GS901_YL01
Ini: IN2 IN2 ON
IO:L01_01 Rack:0 Slot:ST6 (X20DI9371) Point:7
DETECTED
01BAC00_GS005_XG02
UNIT EARTHING SWITCH (901-5) OPEN
Ini:
IO:L01_01 Rack:0 Slot:ST6 (X20DI9371) Point:8
DETECTED
01BAC00_GS035_XG01
UNIT EARTHING SWITCH (901-35) CLOSED
Ini:
IO:L01_01 Rack:0 Slot:ST6 (X20DI9371) Point:3
DETECTED
01BAC00_GS035_XG02
UNIT EARTHING SWITCH (901-35) OPEN
Ini:
IO:L01_01 Rack:0 Slot:ST6 (X20DI9371) Point:4
DETECTED
01BAC00_GS038_XG01
UNIT EARTHING SWITCH (901-38) CLOSED
Ini:
IO:L01_01 Rack:0 Slot:ST6 (X20DI9371) Point:5
DETECTED
01BAC00_GS038_XG02
UNIT EARTHING SWITCH (901-38) OPEN
Ini:
IO:L01_01 Rack:0 Slot:ST6 (X20DI9371) Point:6
DETECTED
01BAC00_GS901_ZM00
UNIT GCB
Ini:0 (NORMAL)
S:GS901
FAULT
01BAC00_GS901_ZA03
GCB SYNCHRO CLOSING
Ini:
S:SFC
REQ
20
01BAC00_GS901_ZA01 AND 01BAC00_GS901_YL01
UNIT GCB DEADLINE AUTO CLOSE ORD 01BAC00_GS901_ZA01 01BAC00_GS901_YL01 UNIT GCB DEADLINE CLOSE ENABLE
Ini:0 (N-CLSG) IN1 Ini:
S:SFC... 01BAC00_GS901_ZC01
IN2 ON
CLOSING
19 IN3
01BBA00_DE003_ZH04 AND
UNIT DEAD VOLTAGE 01BBA00_DE003_ZH04 DEAD LINE CONDITIONS
Ini:0 (N-DET) IN1
S:FE001
DETECTED IN2
Switchyard Line voltage deadline 2
SEL_B
01CJA00_EA000_CON_E01 11
81ADD00_FE231_ZH03 G RE OR
1#MT HV SIDE DEAD VOLTAGE 81ADD00_FE231_ZH03 01BAC00_GS901_ZA03
Ini:0 (N-DET) IN1 IN1
S:FE001 1 01BAC00_GS901_ZA01
DETECTED IN2 IN2
01BAC00_GS901_ZA04
IN3
467/2 (+1p) 467/1(+1p)
24
01CJA00_EU001_ZG14 AND 01BAC00_GS901_YL04
UNIT IN SELF SYNCHRONIZE STARTING MODE 01CJA00_EU001_ZG14 01BAC00_GS901_YL04
UNIT GCB GS901 SELF SYNCHRONIZE CLOSE
01BAC00_GS901_ZA02 Ini:0 (N-DET) IN1
UNIT GCB AUTO OPEN ORD Ini:
S:GS901 CLOSING
Ini:0 (N-OPNG) DETECTED IN2
S:SFC...
OPENING 3
OR
01CJA00_EU001_ZM03 01BAC00_GS901_ZA02
IN1
UNIT EMERG STOP REQ 01CJA00_EU001_ZM03
Ini:0 (N-REQ) IN2
S:CON
REQ 21
FB_CB
CL_A OR1
CL_M DS1
01BAC00_GS901_ZC01
CL_A_ATH
01BAC00_GS901_ZJ01
4 CL_M_ATH
01BAC00_GS901_XG01 01BAC00_GS901_ZM11
AND CL_PS TLTE1
1 01BAC00_GS901_ZC02 01BAC00_GS901_XG01_V
IN1 CL_PS_V
1
IN2 01BAC00_GS901_YL02
01BAC00_GS901_YL02
UNIT GCB GS901 OPEN COMMAND
OP_A OR2 Ini:
OP_M DS2 OPENING
NO OPEN BLOCKING 01BAC00_GS901_ZC02
OP_A_ATH
01BAC00_GS901_ZJ02
OP_M_ATH
01BAC00_GS901_XG02 01BAC00_GS901_ZM12
OP_PS TLTE2
01BAC00_GS901_XG02_V
6 OP_PS_V
01BAC00_GS901_XM01 OR
UNIT CONTROL CIRCUIT FAILURE 01BAC00_GS901_XM01 01BAC00_GS901_ZM00 01BAC00_GS901_ZM00 01BAC00_GS901_ZM10
Ini: IN1 FLT_IN ALARM
IO:L01_01 Rack:0 Slot:ST5 (X20DI9371) Point:3 01BAC00_GS901_XM02 01BAC00_GS901_ZM50
DETECTED IN2 AV REM_ATH
01BAC00_GS901_XM04 01BAC00_GS901_ZM09
IN3 EXTRD
01BAC00_GS901_XM02 01BAC00_GS901_XM05 0
IN4 MANU
UNIT GCB MOTOR FAILURE 01BAC00_GS901_XM08
Ini: IN5
IO:L01_01 Rack:0 Slot:ST5 (X20DI9371) Point:4 01BAC00_GS901_ZT11 : 12000
DETECTED IN6 TLTE
01BAC00_GS901_ZT01 : 200
CL_PL 01BAC00_GS901_ZU01
01BAC00_GS901_XM04 01BAC00_GS901_ZT02 : 500 01BAC00_GS901_ZU01
UNIT GCB GS901 ANIMATION WORD
UNIT GCB SF6 DENSITY LOW ALARM OP_PL SIG Ini:
Ini: 01BAC00_GS901_ZT00 : 1000 01BAC00_GS901_ZU01_V
F_TP SIG_V 0/127
IO:L01_01 Rack:0 Slot:ST5 (X20DI9371) Point:6
DETECTED Type
01BAC00_GS901_XM05 2
UNIT GCB SF6 DENSITY LOW CLOSE & TRIP BLOCKING
Ini:
IO:L01_01 Rack:0 Slot:ST5 (X20DI9371) Point:7
DETECTED
01BAC00_GS901_XM08
UNIT GCB RECLOSE BLOCKED
Ini:
IO:L01_01 Rack:0 Slot:ST5 (X20DI9371) Point:10
DETECTED
5
01BAC00_GS901_XM06 AND
UNIT GCB TRIP 1 CIRCUIT SUPERVISION 01BAC00_GS901_XM06
Ini: IN1
IO:L01_01 Rack:0 Slot:ST5 (X20DI9371) Point:8 01BAC00_GS901_XM07
ALARM IN2
01BAC00_GS901_XM07
UNIT GCB TRIP 2 CIRCUIT SUPERVISION
Ini:
IO:L01_01 Rack:0 Slot:ST5 (X20DI9371) Point:9
ALARM
8
01BAC00_GS003_XL31 AND
UNIT DS GS003 (901-3) CONTROL IN REMOTE 01BAC00_GS003_XL31 01BAC00_GS901_ZM50
Ini: IN1
IO:L01_01 Rack:0 Slot:ST6 (X20DI9371) Point:0
DETECTED 7 IN2
OR
01CJA00_GH003_XL21 IN1
SYNCHRONIZING MODE IN AUTO 01CJA00_GH003_XL21
Ini: IN2
IO:L01_01 Rack:0 Slot:ST4 (X20DI9371) Point:4
DETECTED
18
17 IV
01BAC00_GS901_ZL11 AND 01CJA00_EU001_ZG14
UNIT SELF SYNCHRONIZE MODE ON CMD 01BAC00_GS901_ZL11
RS 01CJA00_EU001_ZG14
UNIT IN SELF SYNCHRONIZE STARTING MODE
Ini: IN1 S Q1 Ini:0 (N-DET)
HMI DB Number:19 DETECTED
SENT IN2 R1 /Q1
01BAC00_GS901_ZK11
16
01CJA00_GH003_XL21 AND
SYNCHRONIZING MODE IN AUTO 01CJA00_GH003_XL21
Ini: IN1
IO:L01_01 Rack:0 Slot:ST4 (X20DI9371) Point:4 01CJA00_EU001_ZG02
DETECTED IN2
01CJA00_EP012_ZM01
IN3
01CJA00_EU001_ZG02 01CJA00_GH001_XL32
IN4
UNIT INIT/STILL STOP STATE
Ini:0 (NO)
S:CON
YES
1
01CJA00_EP001_XM51 OR
GCB SYNCHRONIZER READY FOR OPERATION 01CJA00_EP001_XM51 01CJA00_EP012_ZM01
Ini: IN1
IO:L01_01 Rack:0 Slot:ST4 (X20DI9371) Point:8 01CJA00_EP002_XM51
DETECTED IN2
01CJA00_EP002_XM51
GCB SYN. CHECK RELAY READY FOR OPERATION
Ini:
IO:L01_01 Rack:0 Slot:ST4 (X20DI9371) Point:7
DETECTED
12 15
01CJA00_EU001_ZA01 OR OR
ANY UNIT STOP CMD 01CJA00_EU001_ZA01
Ini:0 (N-REQ) IN1 IN1
S:CON 01MKC65_DE001_XM09
REQ IN2 IN2
01MKC65_DE001_XM09
IF>108A FOR GCB SELF SYNCHRONIZE CONTROL
Ini:
IO:L01_01 Rack:0 Slot:ST8 (X20DI9371) Point:9
DETECTED
14
01BAC00_GS901_ZL12 AND
UNIT SELF SYNCHRONIZE MODE OFF CMD 01BAC00_GS901_ZL12
Ini: IN1
HMI DB Number:19
SENT IN2
01BAC00_GS901_ZK12
13
01CJA00_EA027_ZG01 AND
SQ27:SR->SE SEQ 01CJA00_EA027_ZG01
Ini:0 (N-PROGR) IN1
S:SFC... 1
IN-PROGR IN2
1
01CJA00_EU001_ZG31 AND 01CJA00_DG001_ZG01
UNIT GE STATE 01CJA00_EU001_ZG31 01CJA00_DG001_ZG01 WG OPENING SETPOINT ENABLED
Ini:0 (NO) IN1 Ini:
S:SFC 01CJA00_DE001_ZG33
YES IN2 SELECTED
01CJA00_DE001_ZG42
IN3
01CJA00_DE001_ZG33 01MEU11_CG001_ZQ01
ACTIVE POWER CTRL MODE: PULSE/PULSE IN4
01BAC00_GS901_XG01
Ini: IN5
S:DE001 01MEU11_EU001_XL21
SELECTED IN6
01CJA00_DE001_ZG42
LOAD CTRL OBJECT: OPENING DEG WG OPENING AI VALID
Ini: GCB CLOSED
S:DE001
SELECTED GOV NOT IN LOCAL
01MEU11_CG001_ZQ01
WG OPENING DEGREE AI VALIDATION
Ini:
S:DE001
FAULT
01BAC00_GS901_XG01
UNIT GCB GS901 IN CLOSED POSTION
Ini:
IO:L01_01 Rack:0 Slot:ST5 (X20DI9371) Point:1
DETECTED
01MEU11_EU001_XL21
GOVERNOR SYSTEM REMOTE AUTO MODE
Ini:
IO:L01_01 Rack:0 Slot:ST9 (X20DI9371) Point:1
DETECTED
3
01CJA00_DG001_ZR01 FB_HMI_SP 01CJA00_DG001_ZP02
WG OPENING SP CMD 01CJA00_DG001_ZR01 01CJA00_DG001_ZP02 WG OPENING SP INTERNAL
Unit: % IN SP Unit: MW
HMI DB Number:19 01CJA00_DG001_ZG01
0/10000 (0/100 %)
Enable 0/10000 (0/100 MW)
01CJA00_DG001_ZU01 01CJA00_DG001_ZM01
Min Sp Forced
01CJA00_DG001_ZU01 01CJA00_DG001_ZW01
WG OPENING MIN SP VALUE Init Sp
Ini:1300 (13 %)
01CJA00_DG001_BI 01CJA00_DG001_ZM01
Init Cmd WG OPENING SP FORCED
0/10000 (0/100 %) Forc_min Ini:0 (NO)
01CJA00_DG001_ZA01 YES
01CJA00_DG001_ZW01
Forc_0
01CJA00_DG001_ZQ01
WG OPENING Init sp value Follow
Ini:1400 (14 %)
Scale
0/10000 (0/100 %)
01CJA00_DG001_ZV01
01CJA00_DG001_ZA01
Force WG OPENING sp to 0
Ini:0
01CJA00_DG001_ZP01
WG OPENING SP FEEDBACK
Unit: %
01CJA00_DG001_ZQ01 0/10000 (0/100 %)
WG OPENING MEAS VALUE
Ini:0 (0 %) 4
S:EU001 LIMIT
0/10000 (0/100 %) 01CJA00_DG001_ZU01 01CJA00_DG001_ZP01
LO RE 01CJA00_DG001_ZH06
01CJA00_DG001_ZP02 01CJA00_DG001_ZH06 WG OPENING SETPOINT OVER HIGH LIMIT
01CJA00_DG001_ZU01 IN HL
WG OPENING MIN SP VALUE 01CJA00_DG001_HI Ini:
Ini:1300 (13 %) HI LL DETECTED
0/10000 (0/100 %)
01CJA00_DG001_HI
WG OPENING HIGH LIMIT
Ini:9800 (98 %)
0/10000 (0/100 %) 6 9
ADD AO_SCALE 01CJA00_DG001_ZP03
01CJA00_DG001_ZP01 01CJA00_DG001_ZP03 WG OPENING SP INTERNAL
IN1 IN RE Ini:0 (-8.75 %)
01CJA00_DG001_ZU01 10000
IN2 IMax Err 6553/32767 (13/100 %)
0
IMin
32767
OMax
6553
OMin
10
AO_SCALE 01MEU11_EU001_TQ01
01MEU11_EU001_TQ01 OEO Load setpoint in opening
IN RE Unit: %
10000
IMax Err 0/1000 (13/100 %)
0
IMin
1000
OMax
0
OMin
01CJA00_DG001_TH1
WG OPENING DLT THR 13
Ini:1000 (10 %) SEL
0/10000 (0/100 %) G RE
01CJA00_DG001_TP1 : 0.50000
IN1
01CJA00_DG001_TP2 : 1.00000
IN2
14
8 TP TN
01CJA00_DG001_ZP01 FB_PULS_REG 01CJA00_DG001_INC
WG OPENING SP FEEDBACK 01CJA00_DG001_ZP01
OSC_B 01CJA00_DG001_INC WG OPENING INCREASE PULSE
Unit: % SP Inc IN RE Ini:0
S:DG001 01CJA00_DG001_ZQ01
0/10000 (0/100 %) Meas Dec
Enable
01CJA00_DG001_ZQ01
01CJA00_DG001_ZZ01
Dead
WG OPENING MEAS VALUE 01CJA00_DG001_ZX01
Ini:0 (0 %) Rate(%) 15
S:EU001 01CJA00_DG001_DLT
0/10000 (0/100 %) Max_delta
01CJA00_DG001_ZT01 TP TN
T0(Cyc) OSC_B 01CJA00_DG001_DEC
01CJA00_DE001_ZG32 01CJA00_DG001_DEC WG OPENING DECREASE PULSE
IN RE Ini:0 (N-DET)
ACTIVE POWER CTRL MODE: ANA/PULSE
Ini:0 (N-SEL) DETECTED
S:DE001
SELECTED 2
AND
01CJA00_DG001_ZG01 01CJA00_DE001_ZG32
IN1
WG OPENING SETPOINT ENABLED 01CJA00_DG001_ZG01
Ini: IN2
S:DG001
SELECTED
01CJA00_DG001_ZZ01
PULSE REGUL DEAD BAND
Ini:100 (1 %)
-10000/10000 (-100/100 %)
01CJA00_DG001_ZX01
PULSE REGUL DELTA RATE(%)
Ini:1
-32768/32767
01CJA00_DG001_ZT01
PULSE REGUL INTERVAL TIME(CYC)
Ini:5
-32768/32767
1
01CJA00_EU001_ZG33 AND 01CJA00_DE003_ZG01
UNIT IN G/GC DERECT OPERATION 01CJA00_EU001_ZG33 01CJA00_DE003_ZG01 UNIT VOLTAGE SETPOINT ENABLED
Ini:0 (N-DET) IN1 Ini:
S:STA 01CJA00_DE002_ZG33
DETECTED
IN2 SELECTED
01MKC65_DE001_XG03
IN3
01MKC65_GH001_XL31
01CJA00_DE002_ZG33 IN4
REACTIVE POWER CTRL MODE: PULSE/PULSE 01BAC00_GS901_XG01
Ini: IN5
S:DE002 01CJA00_CE001_ZQ02
SELECTED IN6
01MKC65_DE001_XG03
EXCIT REACTIVE POWER REGULATION
UNIT VOLTAGE AI VALID
Ini:
IO:L01_01 Rack:0 Slot:ST8 (X20DI9371) Point:1 GCB CLOSED
DETECTED
EXECITATION IN REMOTE
01MKC65_GH001_XL31
EXCITATION CONTROL LEVEL
Ini:
IO:L01_01 Rack:0 Slot:ST7 (X20DI9371) Point:8
REMOTE
01BAC00_GS901_XG01
UNIT GCB GS901 IN CLOSED POSTION
Ini:
IO:L01_01 Rack:0 Slot:ST5 (X20DI9371) Point:1
DETECTED
01CJA00_CE001_ZQ02
UNIT VOLTAGE PHASE AB AI VALIDATION
Ini:0 (NORMAL)
S:FE001
FAULT
3
01CJA00_DE003_ZR01 FB_HMI_SP 01CJA00_DE003_ZP02
UNIT VOLTAGE SP CMD 01CJA00_DE003_ZR01 01CJA00_DE003_ZP02 UNIT VOLTAGE SP INTERNAL
Unit: kV IN SP Unit: kV
HMI DB Number:19 01CJA00_DE003_ZG01
0/1500 (0/15 kV)
Enable 0/2000 (0/20 kV)
01CJA00_DE003_ZU01 01CJA00_DE003_ZM01
Min Sp Forced
01CJA00_DE003_ZU01 01CJA00_DE003_ZW01
UNIT VOLTAGE MIN SP VALUE Init Sp
Ini:1242 (12.42 kV)
01CJA00_DE003_BI01
Init Cmd
0/2000 (0/20 kV) Forc_min
01CJA00_DE003_ZA01
01CJA00_DE003_ZW01
Forc_0
01CJA00_DE003_ZQ01
UNIT VOLTAGE Init sp value Follow
Ini:1380 (13.8 kV)
Scale
0/2000 (0/20 kV)
01CJA00_DE003_ZV01
01CJA00_DE003_ZA01
Force UNIT VOLTAGE sp to 0
Ini:0 01CJA00_DE003_ZP01
UNIT VOLTAGE SP FEEDBACK
Unit: kV
0/2000 (0/20 kV)
01CJA00_DE003_ZQ01
UNIT VOLTAGE MEAS VALUE
Ini:0 (0 kV) 4
S:FE001 LIMIT
0/2000 (0/20 kV) 01CJA00_DE003_ZU01 01CJA00_DE003_ZP01
LO RE 01CJA00_DE003_ZH06
01CJA00_DE003_ZP02 01CJA00_DE003_ZH06 VOLTAGE SETPOINT OVER HIGH LIMIT
01CJA00_DE003_ZU01 IN HL
UNIT VOLTAGE MIN SP VALUE 01CJA00_DE003_HI Ini:
Ini:1242 (12.42 kV) HI LL DETECTED
01CJA00_DE003_HI
UNIT VOLTAGE HIGH LIMIT 14
Ini:1518 (15.18 kV) AO_SCALE 01MKC65_FE001_YQ02
01CJA00_DE003_ZP01 01MKC65_FE001_YQ02 UNIT VOLTAGE SETPOINT
0/2000 (0/20 kV) IN RE Unit: V
1518
IMax Err 6553/32767 (12.42/15.18 V)
1242
IMin
32767
OMax
6553
OMin
18
11 TP TN
01CJA00_DE003_ZP01 FB_PULS_REG 01CJA00_DE003_INC
UNIT VOLTAGE SP FEEDBACK 01CJA00_DE003_ZP01
OSC_B 01CJA00_DE003_INC UNIT VOLTAGE INCREASE PULSE
Unit: kV SP Inc IN RE Ini:
S:DE003 01CJA00_DE003_ZQ01
0/2000 (0/20 kV) Meas Dec
Enable
01CJA00_DE003_ZQ01 01CJA00_DE003_ZZ01
Dead
UNIT VOLTAGE MEAS VALUE 01CJA00_DE003_ZX01
Ini:0 (0 kV) Rate(%) 19
S:FE001 01CJA00_DE003_DLT
0/2000 (0/20 kV) Max_delta
01CJA00_DE003_ZT01 TP TN
T0(Cyc) OSC_B 01CJA00_DE003_DEC
01CJA00_DE003_ZG01 01CJA00_DE003_DEC UNIT VOLTAGE DECREASE PULSE
IN RE Ini:
UNIT VOLTAGE SETPOINT ENABLED
Ini: DETECTED
S:DE003
SELECTED 2
AND
01CJA00_DE002_ZG32 01CJA00_DE003_ZG01
IN1
REACTIVE POWER CTRL MODE: ANA/PULSE 01CJA00_DE002_ZG32
Ini: IN2
S:DE002
SELECTED
01CJA00_DE003_ZZ01
PULSE REGUL DEAD BAND
Ini:5
-32768/32767
01CJA00_DE003_ZX01
PULSE REGUL DELTA RATE(%)
Ini:50
-32768/32767
01CJA00_DE003_ZT01
PULSE REGUL INTERVAL TIME(CYC)
Ini:5
-32768/32767
12
TP
TP_R 01CJA00_DE002_ZM11
01CJA00_DE002_ZM11 REA POWER INCREASE REQ
IN REB Ini:
01CJA00_DE003_R01 RET REQ
6
TP 20 22
01CJA00_DE002_ZL01 AND OR 01MKC65_EM001_YL11
REACTIVE POWER INCREASE CMD TP_R
01CJA00_DE002_ZL01 01MKC65_EM001_YL11 EXCITATION INCREASE ORDER
Ini: IN REB IN1 IN1 Ini:
HMI DB Number:19 01CJA00_DE002_ZG33
RET IN2 IN2 ON
SENT 01CJA00_DE002_INC
IN3
01CJA00_DE002_ZG33 01CJA00_DE003_INC
IN4
REACTIVE POWER CTRL MODE: PULSE/PULSE
Ini:
S:DE002
SELECTED
7 21
01CJA00_DE002_ZQ01 LT AND
REACTIVE POWER MEAS VALUE 01CJA00_DE002_ZQ01
Ini:0 (0 Mvar) IN1 RE IN1
S:FE001 01CJA00_DE003_I01 01CJA00_DE002_ZA01
-12000/12000 (-120/120 Mvar) IN2 IN2
01CJA00_DE002_ZA01
Force REACTIVE POWER sp to 0
Ini:0
S:SFC
01CJA00_DE002_INC
REA POWER INCREASE PULSE
Ini:
S:DE002
01CJA00_DE003_INC
UNIT VOLTAGE INCREASE PULSE
Ini:
S:DE003
0.50000
8 23 25
AND OR 01MKC65_EM001_YL12
TP 01CJA00_DE002_ZG33 01MKC65_EM001_YL12 EXCITATION DECREASE ORDER
01CJA00_DE002_ZL02 IN1 IN1
REACTIVE POWER DECREASE CMD TP_R Ini:
01CJA00_DE002_ZL02
Ini: IN REB IN2 IN2 ON
HMI DB Number:19 01CJA00_DE002_DEC
SENT RET IN3
01CJA00_DE003_DEC
9 24 IN4
GT AND
01CJA00_DE002_ZQ01
IN1 RE IN1
01CJA00_DE003_I02 01CJA00_DE002_ZA01
IN2 IN2
01CJA00_DE002_DEC
REA POWER DECREASE PULSE
Ini:
S:DE002
DETECTED
01CJA00_DE003_DEC
UNIT VOLTAGE DECREASE PULSE
Ini:
S:DE003
DETECTED
0.50000
13
TP
TP_R 01CJA00_DE002_ZM12
01CJA00_DE002_ZM12 REA POWER INCREASE REQ
IN REB Ini:
RET REQ
XX PXXXXA4XXXX.192/A
NAME DESCRIPTION STATE INIT FROM TO
01BAC00_GS901_ZM5 UNIT GCB 1 185[8] 184[9],185[21]
0
01BAC00_GS901_ZT0 UNIT GCB FAULT DELAY S:1000 185[21]
0
01BAC00_GS901_ZT0 UNIT GCB CLOSG PULSE S:200 185[21]
1 VALUE
01BAC00_GS901_ZT0 UNIT GCB OPENG PULSE S:500 185[21]
2 VALUE
01BAC00_GS901_ZT1 UNIT GCB TLTE TEMPO VALUE S:12000 185[21]
1
01BAC00_GS901_ZU0 Validant 0 185[21]
1_V
01BBA00_CE001_XQ0 Status 106[1,9]
2_V
01BBA00_DE001_ZH0 Validator 0 104[12]
4_V
01BBA00_DE001_ZH0 Validator 0 104[12]
6_V
01BBA00_DE001_ZH0 Validator 0 104[12]
7_V
01BBA00_DE001_ZW HYS S:100 104[12,13]
10
01BBA00_DE001_ZW LOW 2 THRESHOLD SP -120 <-> 120 S:800 104[13]
13
01BBA00_DE001_ZW LOW 1 THRESHOLD SP 0.000000 <- S:400 104[12]
14 > 120
01BBA00_DE001_ZW HIGH 1 THRESHOLD SP 0.000000 <- S:1000 104[12]
16 > 120
01BBA00_DE001_ZW HIGH 1 THRESHOLD SP 0.000000 <- S:1200 104[12]
17 > 120
01BBA00_DE003_ZH0 Validator 0 105[20]
3_V
01BBA00_DE003_ZH0 Validator 0 106[18]
4_V
01BBA00_DE003_ZH0 Validator 0 106[18]
7_V
01BBA00_DE003_ZW HYS S:50 105[20]
10
01BBA00_DE003_ZW LOW 2 THRESHOLD SP -120 <-> 120 S:300 105[20]
13
01BBA00_DE003_ZW LOW 1 THRESHOLD SP 0.000000 <- S:50 106[18]
14 > 20
01BBA00_DE003_ZW HIGH 1 THRESHOLD SP 0.000000 <- S:1310 106[18]
17 > 20
01BBA00_FE001_1_Z Result 104[5] 73[11],104[10]
Q01
01BBA00_FE001_1_Z INPUT MIN S:6553 104[5]
W01
01BBA00_FE001_1_Z INPUT MAX S:32767 104[5]
W09
01BBA00_FE001_1_Z OUTPUT MIN S:-3000 104[5]
W11
01BBA00_FE001_1_Z OUTPUT MAX S:12000 104[5]
W19
01BBA00_FE001_2_Z Result 104[6] 104[7]
Q01
01BBA00_FE001_2_Z INPUT MIN S:-30000 104[6]
W01
01BBA00_FE001_2_Z INPUT MAX S:120000 104[6]
W09
01BBA00_FE001_2_Z OUTPUT MIN S:-3000 104[6]
W11
01BBA00_FE001_2_Z OUTPUT MAX S:12000 104[6]
W19
01BBA00_FE001_3_Z Result 105[2] 105[3]
Q01
01BBA00_FE001_3_Z INPUT MAX S:120000.00000 105[2]
W01
01BBA00_FE001_3_Z INPUT MIN S:-120000.00000 105[2]
W09
01BBA00_FE001_3_Z OUTPUT MIN S:-12000 105[2]
W11
01BBA00_FE001_3_Z OUTPUT MAX S:12000 105[2]
W19
01BBA00_FE001_5_Z Result 106[9] 106[14],73[12]
Q01
01BBA00_FE001_5_Z INPUT MIN S:6553 106[9]
W01
01BBA00_FE001_5_Z INPUT MAX S:32767 106[9]
W09
01BBA00_FE001_5_Z OUTPUT MIN S:0 106[9]
W11
01BBA00_FE001_5_Z OUTPUT MAX S:2000 106[9]
W19
01BBA00_FE001_6_Z Result 106[15] 106[17]
Q01
01BBA00_FE001_6_Z INPUT MIN S:0 106[15]
W01
XX PXXXXA4XXXX.193/A
NAME DESCRIPTION STATE INIT FROM TO
01BBA00_FE001_6_Z INPUT MAX S:20000 106[15]
W09
01BBA00_FE001_6_Z OUTPUT MIN S:0 106[15]
W11
01BBA00_FE001_6_Z OUTPUT MAX S:2000 106[15]
W19
01BBA00_FE001_II01 0.000000 <- S:10 106[18]
> 30.00000
01BBA00_FE001_INT1 106[14] 106[17]
6_0001
01BBA00_FE001_INT1 0 105[4] 105[20]
6_0002
01BBA00_FE001_INT1 0 104[8] 104[12]
6_0005
01BBA00_FE001_INT1 0 104[10] 104[7]
6_0006
01BBA00_FE001_RQ0 Validant 0 106[16]
3_V
01BBA00_FE001_RQ4 Validant 0 104[11]
2_V
01BBA00_FE001_RQ4 Validant 0 105[19]
3_V
01BFA00_GS000_T01 S:800 110[2,4,6]
01BFA00_GS000_ZU0 Validant 0 110[2]
1_V
01BFA00_GS100_XG0 Status 110[2]
1_V
01BFA00_GS100_XG0 Status 110[2]
2_V
01BFA00_GS101_XG0 Status 110[4]
1_V
01BFA00_GS101_XG0 Status 110[4]
2_V
01BFA00_GS101_ZU0 Validant 0 110[4]
1_V
01BFA00_GS102_XG0 Status 110[6]
1_V
01BFA00_GS102_XG0 Status 110[6]
2_V
01BFA00_GS102_ZU0 Validant 0 110[6]
1_V
01CJA00_DE001_1_Z INPUT MIN S:0 165[29,39]
W21
01CJA00_DE001_1_Z INPUT MAX S:10000 165[29,39]
W29
01CJA00_DE001_1_Z OUTPUT MIN S:6553 165[29]
W31
01CJA00_DE001_1_Z OUTPUT MAX S:32767 165[29]
W39
01CJA00_DE001_2_Z OUTPUT MIN S:0 165[39]
W31
01CJA00_DE001_2_Z OUTPUT MAX S:25000 165[39]
W39
01CJA00_DE001_BO 166[40] 166[42,43]
O_0001
01CJA00_DE001_BO 163[5] 163[7,11,20]
O_0003
01CJA00_DE001_BO 166[35] 166[44]
O_0004
01CJA00_DE001_BO 166[38] 166[40]
O_0005
01CJA00_DE001_BO 166[35] 166[48]
O_0006
01CJA00_DE001_BO 163[6] 163[7,12,19]
O_0012
01CJA00_DE001_BO 0 163[22] 163[8]
O_0014
01CJA00_DE001_BO 167[27] 167[37,46]
O_0015
01CJA00_DE001_BO 167[28] 167[47]
O_0016
01CJA00_DE001_BO 0 164[33] 164[15]
O_0021
01CJA00_DE001_BO 166[18] 166[35]
O_0024
01CJA00_DE001_BO 167[26] 167[36,41]
O_0026
01CJA00_DE001_DEC ACT POWER DECREASE 166[48] 167[49]
PULSE
01CJA00_DE001_DLT ACTIVE POWER reg max delta 0.000000 <- S:1000.000000000 166[35]
> 300.0000
01CJA00_DE001_HI ACTIVE POWER HIGH LIMIT 0.000000 <- S:10000 165[24]
> 120
01CJA00_DE001_INC ACT POWER INCREASE PULSE 166[44] 167[45]
01CJA00_DE001_INT1 166[25] 166[34]
6_0001
XX PXXXXA4XXXX.194/A
NAME DESCRIPTION STATE INIT FROM TO
01CJA00_DE001_INT1 166[34] 166[38]
6_0003
01CJA00_DE001_REA 166[43] 166[44,48]
L_0004
01CJA00_DE001_REA 166[42] 166[44,48]
L_0005
01CJA00_DE001_TH0 ACTIVE POWER DLT THR 0.000000 <- S:3000 166[38]
1 > 120
01CJA00_DE001_TN1 <-> S:8.000000000000 166[42]
01CJA00_DE001_TN2 <-> S:3.00000 166[42]
01CJA00_DE001_TP1 <-> S:1.00000 166[43]
01CJA00_DE001_TP2 <-> S:1.000000000000 166[43]
01CJA00_DE001_ZA0 Force ACTIVE POWER sp to 0 0 60[S1] 167[47],164[15],165[23],163[8]
1
01CJA00_DE001_ZA1 SET ACT.POWER TO INIT 62[S2],57[S2],55[S3] 164[15],165[23],163[8]
1
01CJA00_DE001_ZA1 SET ACT.POWER TO minimal 53[S1],56[S1] 165[23]
2
01CJA00_DE001_ZP0 ACTIVE POWER SP INTERNAL 0.000000 <- 165[23] 165[24]
2 > 120
01CJA00_DE001_ZP0 ACTIVE POWER SP INTERNAL 0.000000 <- 165[29] 166[30]
3 > 300.0000
01CJA00_DE001_ZQ0 Validator 0 104[11] 163[2],104[12]
1_V
01CJA00_DE001_ZT0 PULSE REGUL INTERVAL S:5 166[35]
1 TIME(CYC)
01CJA00_DE001_ZT0 PULSE LENGTH S:0.50000 167[26,27,36,37]
2
01CJA00_DE001_ZU0 ACTIVE POWER MIN SP VALUE 0.000000 <- S:800 165[23,24]
1 > 120
01CJA00_DE001_ZV0 Input Scale to output S:1 165[23]
1
01CJA00_DE001_ZW0 ACTIVE POWER Init sp value 0.000000 <- S:800 167[28],165[23]
1 > 120
01CJA00_DE001_ZX0 PULSE REGUL DELTA RATE(%) S:50 166[35]
1
01CJA00_DE001_ZZ0 PULSE REGUL DEAD BAND -120 <-> 120 S:200 166[35]
1
01CJA00_DE002_1_Z INPUT MIN -120 <-> 120 S:-10000 170[27]
W21
01CJA00_DE002_1_Z INPUT MAX -120 <-> 120 S:10000 170[27]
W29
01CJA00_DE002_1_Z OUTPUT MIN S:6553 170[27]
W31
01CJA00_DE002_1_Z OUTPUT MAX S:32767 170[27]
W39
01CJA00_DE002_BO 168[4] 168[12]
O_0001
01CJA00_DE002_BO 169[22] 169[34]
O_0002
01CJA00_DE002_BO 171[17] 171[26]
O_0003
01CJA00_DE002_BO 171[26] 171[38]
O_0004
01CJA00_DE002_BO 169[24] 169[31]
O_0005
01CJA00_DE002_BO 171[26] 171[39]
O_0006
01CJA00_DE002_BO 171[28] 171[36,37]
O_0007
01CJA00_DE002_DEC REA POWER DECREASE 171[39] 191[25]
PULSE
01CJA00_DE002_DLT REACTIVE POWER reg max -300.000 <-> S:1000.000000000 171[26]
delta 300.0000
01CJA00_DE002_HI REACTIVE POWER HIGH LIMIT -120 <-> 120 S:10000 170[19]
01CJA00_DE002_INC REA POWER INCREASE PULSE 171[38] 191[22]
01CJA00_DE002_INT1 171[20] 171[25]
6_0002
01CJA00_DE002_INT1 171[25] 171[28]
6_0007
01CJA00_DE002_LO REACTIVE POWER LOW LIMIT -120 <-> 120 S:-10000 170[19]
01CJA00_DE002_REA 171[37] 171[38,39]
L_0001
01CJA00_DE002_REA 171[36] 171[38,39]
L_0002
01CJA00_DE002_TH0 REACTIVE POWER DLT THR -120 <-> 120 S:3000 171[28]
1
01CJA00_DE002_TN1 <-> S:8.000000000000 171[36]
01CJA00_DE002_TN2 <-> S:10.00000 171[36]
01CJA00_DE002_TP1 <-> S:0.500000000000 171[37]
01CJA00_DE002_TP2 <-> S:1.000000000000 171[37]
01CJA00_DE002_ZA0 Force REACTIVE POWER sp to 0 60[S1] 170[18],168[12],191[21,24]
1 0
01CJA00_DE002_ZA1 SET REA.POWER TO 0 53[S1],62[S2],61[S1],56[S1],55[S1] 170[18],168[12],169[34]
1
XX PXXXXA4XXXX.195/A
NAME DESCRIPTION STATE INIT FROM TO
01CJA00_DE002_ZP0 REACTIVE POWER SP -120 <-> 120 170[18] 170[19]
2 INTERNAL
01CJA00_DE002_ZQ0 Validator 0 105[19] 168[1],169[2]
1_V
01CJA00_DE002_ZT0 PULSE REGUL INTERVAL S:50 171[26]
1 TIME(CYC)
01CJA00_DE002_ZU0 REACTIVE POWER MIN SP -120 <-> 120 S:-10000 170[18]
1 VALUE
01CJA00_DE002_ZV0 Input Scale to output S:1 170[18]
1
01CJA00_DE002_ZW0 REACTIVE POWER Init sp value -120 <-> 120 S:0 170[18]
1
01CJA00_DE002_ZX0 PULSE REGUL DELTA RATE(%) S:50 171[26]
1
01CJA00_DE002_ZZ0 PULSE REGUL DEAD BAND -120 <-> 120 S:200 171[26]
1
01CJA00_DE003_1_Z INPUT MIN 0.000000 <- S:1242 189[14]
W21 > 20.00000
01CJA00_DE003_1_Z INPUT MAX 0.000000 <- S:1518 189[14]
W29 > 20.00000
01CJA00_DE003_1_Z OUTPUT MIN S:6553 189[14]
W31
01CJA00_DE003_1_Z OUTPUT MAX S:32767 189[14]
W39
01CJA00_DE003_BI01 Voltage init flag S:0 189[3]
01CJA00_DE003_BO 190[2] 190[11]
O_0001
01CJA00_DE003_BO 191[6] 191[12,20]
O_0002
01CJA00_DE003_BO 191[8] 191[13,23]
O_0003
01CJA00_DE003_BO 191[9] 191[24]
O_0004
01CJA00_DE003_BO 191[7] 191[21]
O_0005
01CJA00_DE003_BO 190[11] 190[18]
O_0006
01CJA00_DE003_BO 190[11] 190[19]
O_0007
01CJA00_DE003_BO 190[15] 190[16,17]
O_0008
01CJA00_DE003_DEC UNIT VOLTAGE DECREASE 190[19] 191[25]
PULSE
01CJA00_DE003_DLT UNIT VOLTAGE reg max delta 0.000000 <- S:50.00000000000 190[11]
> 30.00000
01CJA00_DE003_HI UNIT VOLTAGE HIGH LIMIT 0.000000 <- S:1518 189[4]
> 20.00000
01CJA00_DE003_I01 -100.000 <-> S:-200 191[7]
100.0000
01CJA00_DE003_I02 -100.000 <-> S:200 191[9]
100.0000
01CJA00_DE003_INC UNIT VOLTAGE INCREASE 190[18] 191[22]
PULSE
01CJA00_DE003_INT1 190[5] 190[10]
6_0002
01CJA00_DE003_INT1 190[10] 190[15]
6_0003
01CJA00_DE003_R01 S:0.50000 191[6,8,12,13]
01CJA00_DE003_REA 190[17] 190[18,19]
L_0001
01CJA00_DE003_REA 190[16] 190[18,19]
L_0002
01CJA00_DE003_TD0 <-> S:20 95[10]
1
01CJA00_DE003_TD0 <-> S:2 94[32]
2
01CJA00_DE003_TD1 <-> S:40 98[14]
1
01CJA00_DE003_TH1 UNIT VOLTAGE DLT THR 0.000000 <- S:50 190[15]
> 20.00000
01CJA00_DE003_TN1 <-> S:8.000000000000 190[16]
01CJA00_DE003_TN2 <-> S:10.00000 190[16]
01CJA00_DE003_TP1 <-> S:0.500000000000 190[17]
01CJA00_DE003_TP2 <-> S:1.000000000000 190[17]
01CJA00_DE003_ZA0 Force UNIT VOLTAGE sp to 0 S:0 189[3]
1
01CJA00_DE003_ZP0 UNIT VOLTAGE SP INTERNAL 0.000000 <- 189[3] 189[4]
2 > 20.00000
01CJA00_DE003_ZQ0 Validator 0 106[16] 168[1],169[21]
1_V
01CJA00_DE003_ZT0 PULSE REGUL INTERVAL S:5 190[11]
1 TIME(CYC)
01CJA00_DE003_ZU0 UNIT VOLTAGE MIN SP VALUE 0.000000 <- S:1242 189[3,4]
1 > 20.00000
01CJA00_DE003_ZV0 Input Scale to output S:1 189[3]
1
XX PXXXXA4XXXX.196/A
NAME DESCRIPTION STATE INIT FROM TO
01CJA00_DE003_ZW0 UNIT VOLTAGE Init sp value 0.000000 <- S:1380 189[3]
1 > 20.00000
01CJA00_DE003_ZX0 PULSE REGUL DELTA RATE(%) S:50 190[11]
1
01CJA00_DE003_ZZ0 PULSE REGUL DEAD BAND S:5 190[11]
1
01CJA00_DG001_1_Z INPUT MIN 0.000000 <- S:0 187[9,10]
W21 > 100.0000
01CJA00_DG001_1_Z INPUT MAX 0.000000 <- S:10000 187[9,10]
W29 > 100.0000
01CJA00_DG001_1_Z OUTPUT MIN S:6553 187[9]
W31
01CJA00_DG001_1_Z OUTPUT MAX S:32767 187[9]
W39
01CJA00_DG001_2_Z OUTPUT MIN S:0 187[10]
W31
01CJA00_DG001_2_Z OUTPUT MAX S:1000 187[10]
W39
01CJA00_DG001_BI WG init flag S:0 187[3]
01CJA00_DG001_BO 188[2] 188[8]
O_0001
01CJA00_DG001_BO 188[11] 188[12,13]
O_0002
01CJA00_DG001_BO 188[8] 188[14]
O_0003
01CJA00_DG001_BO 188[8] 188[15]
O_0004
01CJA00_DG001_DEC WG OPENING DECREASE 0 188[15] 167[49]
PULSE
01CJA00_DG001_DLT WG OPENING reg max delta 0.000000 <- S:500.0000000000 188[8]
> 100.0000
01CJA00_DG001_HI WG OPENING HIGH LIMIT 0.000000 <- S:9800 187[4]
> 100.0000
01CJA00_DG001_INC WG OPENING INCREASE 0 188[14] 167[45]
PULSE
01CJA00_DG001_INT 187[6] 187[9,10]
16_0001
01CJA00_DG001_INT 188[5] 188[7]
16_0002
01CJA00_DG001_INT 188[7] 188[11]
16_0004
01CJA00_DG001_REA 188[13] 188[14,15]
L_0001
01CJA00_DG001_REA 188[12] 188[14,15]
L_0002
01CJA00_DG001_TH1 WG OPENING DLT THR 0.000000 <- S:1000 188[11]
> 100.0000
01CJA00_DG001_TN1 <-> S:8.000000000000 188[12]
01CJA00_DG001_TN2 <-> S:4.00000 188[12]
01CJA00_DG001_TP1 <-> S:0.50000 188[13]
01CJA00_DG001_TP2 <-> S:1.000000000000 188[13]
01CJA00_DG001_ZA0 Force WG OPENING sp to 0 S:0 187[3]
1
01CJA00_DG001_ZP0 WG OPENING SP INTERNAL 0.000000 <- 187[3] 187[4]
2 > 100.0000
01CJA00_DG001_ZP0 WG OPENING SP INTERNAL 13.00000 <- 0 187[9] 166[30]
3 > 100.0000
01CJA00_DG001_ZT0 PULSE REGUL INTERVAL S:5 188[8]
1 TIME(CYC)
01CJA00_DG001_ZU0 WG OPENING MIN SP VALUE 0.000000 <- S:1300 187[3,4,6]
1 > 100.0000
01CJA00_DG001_ZV0 Input Scale to output S:1 187[3]
1
01CJA00_DG001_ZW0 WG OPENING Init sp value 0.000000 <- S:1400 187[3]
1 > 100.0000
01CJA00_DG001_ZX0 PULSE REGUL DELTA RATE(%) S:1 188[8]
1
01CJA00_DG001_ZZ0 PULSE REGUL DEAD BAND -100.000 <-> S:100 188[8]
1 100.0000
01CJA00_EA000_CON S:0 138[27]
BI01
01CJA00_EA000_CON ENABLE MS FOR HEAT RUN 138[27] 140[28]
BI02 TEST
01CJA00_EA000_CON 140[3] 140[10,28]
BOO_0002
01CJA00_EA000_CON LCU1 & 3 S8000 NOT S:0 184[2],128[15,16,17]
_E01 CONNECTED
01CJA00_EA000_CON LCU1 & 8 S8000 NOT S:0 129[20],128[18,19]
_E02 CONNECTED
01CJA00_EA000_CON LCU1 & 5 S8000 NOT S:0 129[21]
_E03 CONNECTED
01CJA00_EA000_ZG0 UNIT NOT IN SS/IS STATE 138[4] 138[15,17],140[12]
1
01CJA00_EA001_SFC 173[3,7]
_S1_X
01CJA00_EA001_SFC 173[4]
_S2_X
XX PXXXXA4XXXX.197/A
NAME DESCRIPTION STATE INIT FROM TO
01CJA00_EA001_SFC 173[5]
_S3_X
01CJA00_EA001_SFC 173[6]
_S4_X
01CJA00_EA001_SIG 173[1] 173[8]
BOO_0001
01CJA00_EA001_SIG 173[10] 173[11]
BOO_0002
01CJA00_EA001_SIG 173[11] 173[14]
BOO_0003
01CJA00_EA001_SIG 173[2] 173[12]
BOO_0004
01CJA00_EA001_SIGI 173[10] 173[13]
NT32_0001
01CJA00_EA001_ZD0 step01 time delay 0 173[7] 60[T2]
01
01CJA00_EA001_ZS0 01 172[2] 60[T1]
15
01CJA00_EA001_ZS0 02 172[4] 60[T2]
25
01CJA00_EA001_ZS0 03 172[6] 60[T3]
35
01CJA00_EA001_ZS0 04 172[8] 60[T4]
45
01CJA00_EA001_ZS0 05 172[10] 60[T5]
55
01CJA00_EA001_ZT0 step01 delay <-> S:5.00000 173[7]
01
01CJA00_EA001_ZT0 SQ01: GE/SR/CH/BS ->NMS S:12000 173[10]
1 SEQ OVER
01CJA00_EA002_SFC 175[3,7]
_S1_X
01CJA00_EA002_SFC 175[4]
_S2_X
01CJA00_EA002_SFC 175[5]
_S3_X
01CJA00_EA002_SFC 175[6]
_S4_X
01CJA00_EA002_SIG 175[1] 175[8]
BOO_0001
01CJA00_EA002_SIG 175[10] 175[11]
BOO_0002
01CJA00_EA002_SIG 175[11] 175[14]
BOO_0003
01CJA00_EA002_SIG 175[2] 175[12]
BOO_0004
01CJA00_EA002_SIGI 175[10] 175[13]
NT32_0001
01CJA00_EA002_ZD0 step01 time delay 0 175[7] 61[T2]
01
01CJA00_EA002_ZS0 01 174[2] 61[T1]
15
01CJA00_EA002_ZS0 02 174[4] 61[T2]
25
01CJA00_EA002_ZS0 03 174[6] 61[T3]
35
01CJA00_EA002_ZS0 04 174[8] 61[T4]
45
01CJA00_EA002_ZS0 05 174[10] 61[T5]
55
01CJA00_EA002_ZT0 step01 delay <-> 5.00000000000 175[7]
01
01CJA00_EA002_ZT0 SQ02: GC ->NMS SEQ S:12000 175[10]
1 OVERTIME SP
01CJA00_EA007_SFC 83[3]
_S1_X
01CJA00_EA007_SFC 83[4]
_S2_X
01CJA00_EA007_SIG 83[1] 83[5]
BOO_0001
01CJA00_EA007_SIG 83[2] 83[9]
BOO_0002
01CJA00_EA007_SIG 83[8] 83[11]
BOO_0009
01CJA00_EA007_SIG 83[7] 83[8]
BOO_0010
01CJA00_EA007_SIGI 83[7] 83[10]
NT32_0003
01CJA00_EA007_ZS0 SQ07:NMS->TS STEP1 COND 82[2] 44[T1]
15
01CJA00_EA007_ZS0 SQ07:NMS->TS STEP2 COND 82[4] 44[T2]
25
01CJA00_EA007_ZS0 SQ07:NMS->TS STEP3 COND 82[6] 44[T3]
35
01CJA00_EA007_ZT0 SQ07:NMS->TS SEQ OVERTIME S:12000 83[7]
1 SP
01CJA00_EA008_SFC 160[1]
_S1_X
XX PXXXXA4XXXX.198/A
NAME DESCRIPTION STATE INIT FROM TO
01CJA00_EA008_SFC 160[2,4]
_S2_X
01CJA00_EA008_SFC 160[3]
_S3_X
01CJA00_EA008_SIG 160[5] 160[7]
BOO_0001
01CJA00_EA008_SIG 160[9] 160[10]
BOO_0002
01CJA00_EA008_SIG 160[10] 160[13]
BOO_0003
01CJA00_EA008_SIG 160[6] 160[11]
BOO_0005
01CJA00_EA008_SIGI 160[9] 160[12]
NT32_0001
01CJA00_EA008_ZD0 step02 time delay 0 160[4] 158[9]
02
01CJA00_EA008_ZS0 STEP01 COND 158[3] 58[T1]
15
01CJA00_EA008_ZS0 STEP02 COND 158[5] 58[T2]
25
01CJA00_EA008_ZS0 STEP03 COND 158[9] 58[T3]
35
01CJA00_EA008_ZS0 STEP04 COND 159[7] 58[T4]
45
01CJA00_EA008_ZT0 step02 delay <-> 5.00000000000 160[4]
02
01CJA00_EA008_ZT0 SQ04: ES->TS SEQ OVERTIME S:12000 160[9]
1 SP
01CJA00_EA009_SFC 162[1]
_S1_X
01CJA00_EA009_SIG 162[2] 162[4]
BOO_0001
01CJA00_EA009_SIG 162[6] 162[7]
BOO_0002
01CJA00_EA009_SIG 162[7] 162[10]
BOO_0003
01CJA00_EA009_SIG 162[3] 162[8]
BOO_0005
01CJA00_EA009_SIGI 162[6] 162[9]
NT32_0001
01CJA00_EA009_ZS0 STEP01 COND 161[2] 59[T1]
15
01CJA00_EA009_ZS0 STEP02 COND 161[4] 59[T3]
25
01CJA00_EA009_ZT0 SQ09: TS->SS SEQ OVERTIME S:12000 162[6]
1 SP
01CJA00_EA010_SFC 137[1]
_S1_X
01CJA00_EA010_SIG 137[2] 137[4]
BOO_0001
01CJA00_EA010_SIG 137[6] 137[7]
BOO_0002
01CJA00_EA010_SIG 137[7] 137[10]
BOO_0003
01CJA00_EA010_SIG 137[3] 137[8]
BOO_0005
01CJA00_EA010_SIGI 137[6] 137[9]
NT32_0001
01CJA00_EA010_ZS0 STEP01 COND 136[2] 49[T1]
15
01CJA00_EA010_ZS0 STEP02 COND 136[4]
25
01CJA00_EA010_ZS0 STEP03 COND 136[6] 49[T3]
35
01CJA00_EA010_ZT0 SQ10:SS->TS SEQ OVERTIME S:12000 137[6]
1 SP
01CJA00_EA021_DL0 STEP4 TIME DELAY 0 144[4] 51[S3]
4
01CJA00_EA021_SFC 144[1]
_S1_X
01CJA00_EA021_SFC 144[2]
_S2_X
01CJA00_EA021_SFC 144[3,4]
_S3_X
01CJA00_EA021_SIG 144[5] 144[7]
BOO_0001
01CJA00_EA021_SIG 144[9] 144[10]
BOO_0002
01CJA00_EA021_SIG 144[10] 144[13]
BOO_0003
01CJA00_EA021_SIG 144[6] 144[11]
BOO_0005
01CJA00_EA021_SIGI 144[9] 144[12]
NT32_0001
01CJA00_EA021_SIG S:3.000000000000 144[4]
RI01
01CJA00_EA021_ZS0 STEP01 COND 142[4] 51[T1]
15
XX PXXXXA4XXXX.199/A
NAME DESCRIPTION STATE INIT FROM TO
01CJA00_EA021_ZS0 STEP02 COND 142[6] 51[T2]
25
01CJA00_EA021_ZS0 STEP03 COND 142[8] 51[T4]
35
01CJA00_EA021_ZS0 STEP04 COND 143[10] 51[T5]
45
01CJA00_EA021_ZT0 SQ21:TS->SR SEQ OVERTIME S:12000 144[9]
1 SP
01CJA00_EA027_SFC 146[1]
_S1_X
01CJA00_EA027_SIG 146[2] 146[4]
BOO_0001
01CJA00_EA027_SIG 146[6] 146[7]
BOO_0002
01CJA00_EA027_SIG 146[7] 146[10]
BOO_0003
01CJA00_EA027_SIG 146[3] 146[8]
BOO_0005
01CJA00_EA027_SIGI 146[6] 146[9]
NT32_0001
01CJA00_EA027_ZS0 STEP01 COND 145[4] 52[T1]
15
01CJA00_EA027_ZS0 STEP02 COND 145[6] 52[T11]
25
01CJA00_EA027_ZT0 SQ27:SR->SE SEQ OVERTIME S:12000 146[6]
1 SP
01CJA00_EA032_CON 154[2] 154[3]
BOO_0001
01CJA00_EA032_CON S:15.0000000000 154[2]
R01
01CJA00_EA032_SFC 155[1]
_S1_X
01CJA00_EA032_SFC 155[2]
_S2_X
01CJA00_EA032_SFC 155[3]
_S3_X
01CJA00_EA032_SIG 155[4] 155[6]
BOO_0001
01CJA00_EA032_SIG 155[8] 155[9]
BOO_0002
01CJA00_EA032_SIG 155[9] 155[12]
BOO_0003
01CJA00_EA032_SIG 155[5] 155[10]
BOO_0005
01CJA00_EA032_SIGI 155[8] 155[11]
NT32_0001
01CJA00_EA032_ZS0 STEP01 COND 154[6] 56[T1]
15
01CJA00_EA032_ZS0 STEP02 COND 154[8] 56[T2]
25
01CJA00_EA032_ZS0 STEP03 COND 154[10] 56[T3]
35
01CJA00_EA032_ZS0 STEP04 COND 154[12] 56[T4]
45
01CJA00_EA032_ZT0 SQ32:GE->SR SEQ OVERTIME S:12000 155[8]
1 SP
01CJA00_EA034_SFC 153[1]
_S1_X
01CJA00_EA034_SFC 153[2]
_S2_X
01CJA00_EA034_SFC 153[3]
_S3_X
01CJA00_EA034_SIG 153[4] 153[6]
BOO_0001
01CJA00_EA034_SIG 153[8] 153[9]
BOO_0002
01CJA00_EA034_SIG 153[9] 153[12]
BOO_0003
01CJA00_EA034_SIG 153[5] 153[10]
BOO_0005
01CJA00_EA034_SIGI 153[8] 153[11]
NT32_0001
01CJA00_EA034_ZS0 STEP01 COND 152[2] 55[T1]
15
01CJA00_EA034_ZS0 STEP02 COND 152[4] 55[T2]
25
01CJA00_EA034_ZS0 STEP03 COND 152[6] 55[T4]
35
01CJA00_EA034_ZS0 STEP04 COND 152[8] 55[T5]
45
01CJA00_EA034_ZT0 SQ34:GC->GE SEQ OVERTIME S:12000 153[8]
1 SP
01CJA00_EA036_SFC 157[1]
_S1_X
01CJA00_EA036_SFC 157[2]
_S2_X
01CJA00_EA036_SIG 157[3] 157[5]
BOO_0001
XX PXXXXA4XXXX.200/A
NAME DESCRIPTION STATE INIT FROM TO
01CJA00_EA036_SIG 157[7] 157[8]
BOO_0002
01CJA00_EA036_SIG 157[8] 157[11]
BOO_0003
01CJA00_EA036_SIG 157[4] 157[9]
BOO_0005
01CJA00_EA036_SIGI 157[7] 157[10]
NT32_0001
01CJA00_EA036_ZS0 STEP01 COND 156[2] 57[T1]
15
01CJA00_EA036_ZS0 STEP02 COND 156[4] 57[T2]
25
01CJA00_EA036_ZS0 STEP03 COND 156[6] 57[T3]
35
01CJA00_EA036_ZT0 SQ36:CH->GE SEQ OVERTIME S:12000 157[7]
1 SP
01CJA00_EA043_RI01 S:10.00000 147[1]
01CJA00_EA043_SFC 148[1]
_S1_X
01CJA00_EA043_SFC 148[2]
_S2_X
01CJA00_EA043_SFC 148[3]
_S3_X
01CJA00_EA043_SFC 148[4]
_S99_X
01CJA00_EA043_SIG 148[5] 148[7]
BOO_0001
01CJA00_EA043_SIG 148[9] 148[10]
BOO_0002
01CJA00_EA043_SIG 148[10] 148[13]
BOO_0003
01CJA00_EA043_SIG 148[6] 148[11]
BOO_0005
01CJA00_EA043_SIGI 148[9] 148[12]
NT32_0001
01CJA00_EA043_ZD0 step99 time delay 0 148[4] 53[T99]
99
01CJA00_EA043_ZS0 STEP01 COND 147[3] 53[T1]
15
01CJA00_EA043_ZS0 STEP02 COND 147[5] 53[T2]
25
01CJA00_EA043_ZS0 STEP03 COND 147[7] 53[T3]
35
01CJA00_EA043_ZS0 STEP04 COND 147[9] 53[T4]
45
01CJA00_EA043_ZT0 SQ43: GE->GC SEQ OVERTIME S:12000 148[9]
1 SP
01CJA00_EA043_ZT0 step99 delay <-> 1.00000000000 148[4]
99
01CJA00_EA051_SFC 178[3]
_S1_X
01CJA00_EA051_SFC 178[4]
_S2_X
01CJA00_EA051_SFC 178[5]
_S3_X
01CJA00_EA051_SFC 178[6]
_S4_X
01CJA00_EA051_SFC 178[7]
_S5_X
01CJA00_EA051_SFC 178[8]
_S6_X
01CJA00_EA051_SIG 178[1] 178[10]
BOO_0001
01CJA00_EA051_SIG 178[2] 178[14]
BOO_0002
01CJA00_EA051_SIG 178[12] 178[13]
BOO_0003
01CJA00_EA051_SIG 178[13] 178[16]
BOO_0004
01CJA00_EA051_SIGI 178[12] 178[15]
NT32_0001
01CJA00_EA051_ZD0 Step02 time delay 0 178[9]
02
01CJA00_EA051_ZS0 STEP01 COND 176[2] 45[T1]
15
01CJA00_EA051_ZS0 STEP02 COND 176[4] 45[T2]
25
01CJA00_EA051_ZS0 STEP03 COND 176[6] 45[T4]
35
01CJA00_EA051_ZS0 STEP04 COND 177[8] 45[T5]
45
01CJA00_EA051_ZS0 STEP05 COND 177[10] 45[T6]
55
01CJA00_EA051_ZS0 STEP06 COND 177[12] 45[T7]
65
01CJA00_EA051_ZS0 STEP07 COND 177[14] 45[T8]
75
XX PXXXXA4XXXX.201/A
NAME DESCRIPTION STATE INIT FROM TO
01CJA00_EA051_ZT0 step02 delay <-> 5.00000000000 178[9]
02
01CJA00_EA051_ZT0 SQ51: TS->BS SEQ OVERTIME S:12000 178[12]
1 SP
01CJA00_EA061_SFC 151[1]
_S1_X
01CJA00_EA061_SFC 151[2]
_S2_X
01CJA00_EA061_SFC 151[3,7]
_S3_X
01CJA00_EA061_SFC 151[4]
_S4_X
01CJA00_EA061_SFC 151[5]
_S5_X
01CJA00_EA061_SFC 151[6]
_S6_X
01CJA00_EA061_SIG 151[8] 151[10]
BOO_0001
01CJA00_EA061_SIG 151[12] 151[13]
BOO_0002
01CJA00_EA061_SIG 151[13] 151[16]
BOO_0003
01CJA00_EA061_SIG 151[9] 151[14]
BOO_0005
01CJA00_EA061_SIGI 151[12] 151[15]
NT32_0001
01CJA00_EA061_ZD0 step02 time delay 0 151[7]
02
01CJA00_EA061_ZS0 STEP01 COND 149[2] 54[T1]
15
01CJA00_EA061_ZS0 STEP02 COND 149[4] 54[T2]
25
01CJA00_EA061_ZS0 STEP03 COND 149[6] 54[T4]
35
01CJA00_EA061_ZS0 STEP04 COND 150[8] 54[T5]
45
01CJA00_EA061_ZS0 STEP05 COND 150[10] 54[T6]
55
01CJA00_EA061_ZS0 STEP06 COND 150[12] 54[T7]
65
01CJA00_EA061_ZS0 STEP07 COND 150[14] 54[T8]
75
01CJA00_EA061_ZT0 step02 delay <-> 5.00000000000 151[7]
02
01CJA00_EA061_ZT0 SQ61: TS->CH SEQ OVERTIME S:12000 151[12]
1 SP
01CJA00_EA073_CON 121[2] 121[9]
INT16_0001
01CJA00_EA073_II01 FREQ DELTA S:50 121[9]
01CJA00_EA073_SFC 120[1]
_S1_X
01CJA00_EA073_SFC 120[2]
_S2_X
01CJA00_EA073_SIG 120[4] 120[9]
BOO_0001
01CJA00_EA073_SIG 120[8] 120[11]
BOO_0002
01CJA00_EA073_SIG 120[3] 120[5]
BOO_0003
01CJA00_EA073_SIG 120[7] 120[8]
BOO_0004
01CJA00_EA073_SIGI 120[7] 120[10]
NT32_0001
01CJA00_EA073_ZS0 121[4] 62[T1]
15
01CJA00_EA073_ZS0 121[6] 62[T6,T4]
25
01CJA00_EA073_ZS0 122[8] 62[T7]
35
01CJA00_EA073_ZT0 SQ73:SE->GE SEQ OVERTIME S:12000 120[7]
1 SP
01CJA00_EA100_CON 126[3] 126[10]
BOO_0001
01CJA00_EA100_ZA5 STEP MODE CONDITION 126[26] 177[8,12],176[2,4,6],149[2,4,6],145[4
1 ,6],142[4,8],121[4],154[8,10],150[8,1
2],152[2,6],147[5]
01CJA00_EB000_BO 182[1] 182[9]
O_0001
01CJA00_EB000_BO 182[1] 182[10]
O_0002
01CJA00_EB000_BO 182[2] 182[11]
O_0003
01CJA00_EB000_BO 182[2] 182[12]
O_0005
01CJA00_EB000_BO 182[3] 182[13]
O_0010
01CJA00_EB000_BO 182[3] 182[14]
O_0011
XX PXXXXA4XXXX.202/A
NAME DESCRIPTION STATE INIT FROM TO
01CJA00_EB000_RI01 S:5.00000000000 181[15,16,17,18,19]
01CJA00_EU001_STA 123[1] 123[20]
BOO_0001
01CJA00_EU001_STA 123[2] 123[20]
BOO_0003
01CJA00_EU001_STA 123[3] 123[20]
BOO_0004
01CJA00_EU001_STA 123[5] 123[20]
BOO_0005
01CJA00_EU001_STA 123[4] 123[20]
BOO_0006
01CJA00_EU001_STA 123[8] 123[20]
BOO_0007
01CJA00_EU001_STA 123[6] 123[20]
BOO_0011
01CJA00_EU001_STA 123[7] 123[20]
BOO_0012
01CJA00_EU001_ZU0 Validant 0 123[20]
1_V
01MAU24_AA002_ZA0 Open governor solenoid valve 45[S3],54[S3],51[S3],55[S2] 100[15]
1
01MAU24_AA002_ZA0 Close governor solenoid valve 53[S3],61[S1],58[S1],60[S1,S4] 100[16]
2
01MAU24_AA005_XG Status 103[28]
01_V
01MAU24_AA005_XG Status 103[28]
02_V
01MAU24_AA005_ZU0 Validant 0 103[28]
1_V
01MAU24_AP001_XG Status 103[5]
01_V
01MAU24_AP001_ZU0 Validant 0 103[5]
1_V
01MAU24_AP002_XG Status 103[27]
01_V
01MAU24_AP002_ZU0 Validant 0 103[27]
1_V
01MAU24_AP003_XM Status 103[6]
51_V
01MAU24_AP003_ZU0 Validant 0 103[6]
1_V
01MAU24_CP001_XQ Status 101[7,8]
01_V
01MAU24_CP001_ZH0 Validator 0 101[7]
3_V
01MAU24_CP001_ZH0 Validator 0 101[7]
4_V
01MAU24_CP001_ZH0 Validator 0 101[7]
6_V
01MAU24_CP001_ZH0 Validator 0 101[7]
7_V
01MAU24_CP001_ZW HYS S:100 101[7,8]
10
01MAU24_CP001_ZW LOW 2 THRESHOLD SP 0 <-> 50 S:25427 101[7]
13
01MAU24_CP001_ZW LOW 1 THRESHOLD SP 0 <-> 50 S:26475 101[8]
14
01MAU24_CP001_ZW HIGH 1 THRESHOLD SP 0 <-> 50 S:28572 101[7]
16
01MAU24_CP001_ZW HIGH 1 THRESHOLD SP 0 <-> 50 S:29612 101[7]
17
01MAU24_EA001_ZA0 Start governor oil station 49[S1] 100[17]
1
01MAU24_EA001_ZA0 Stop governor oil station 59[S1] 102[12],100[18]
2
01MAU24_EU014_BI0 103[2] 103[5]
1
01MAU24_EU014_BI0 103[25] 103[27]
2
01MAU24_EU014_BI0 103[4] 103[6]
3
01MAU24_EU014_BI0 0 103[28]
4
01MAU24_EU014_BO 100[16] 100[23]
O_0001
01MAU24_EU014_BO 103[1] 103[5]
O_0002
01MAU24_EU014_BO 102[14] 102[22]
O_0003
01MAU24_EU014_BO 100[15] 100[23]
O_0004
01MAU24_EU014_BO 103[24] 103[27]
O_0005
01MAU24_EU014_BO 100[23] 100[26]
O_0007
01MAU24_EU014_BO 103[3] 103[6]
O_0008
XX PXXXXA4XXXX.203/A
NAME DESCRIPTION STATE INIT FROM TO
01MAU24_EU014_D01 S:200 103[5]
01MAU24_EU014_D02 S:200 103[27]
01MAU24_EU014_D03 S:200 103[6]
01MAU24_EU014_D04 S:200 103[28]
01MAU24_EU014_RI0 <-> S:10.0000000000 100[15,16,17,18]
1
01MAU24_EU014_RI0 <-> S:5.00000000000 102[14]
2
01MAU24_EU014_W0 S:2 103[5,6,27,28]
1
01MEA41_AU001_RI0 S:2 78[1]
1
01MEA41_CP505_ZH0 Validator 0 117[2]
3_V
01MEA41_CP505_ZH0 Validator 0 117[2]
4_V
01MEA41_CP505_ZH0 Validator 0 117[2]
6_V
01MEA41_CP505_ZH0 Validator 0 117[2]
7_V
01MEA41_CP505_ZW HYS S:200 117[2]
10
01MEA41_CP505_ZW LOW 2 THRESHOLD SP 0 <-> 2000 S:23592 117[2]
13
01MEA41_CP505_ZW LOW 1 THRESHOLD SP 0.000000 <- S:18349 117[2]
14 > 2000
01MEA41_CP505_ZW HIGH 1 THRESHOLD SP 0.000000 <- S:9174 117[2]
16 > 2000
01MEA41_CP505_ZW HIGH 1 THRESHOLD SP 0.000000 <- S:6700 117[2]
17 > 2000
01MEU11_CG012_XQ Status 164[1],97[11]
01_V
01MEU11_CG012_ZH0 Validator 0 97[25]
3_V
01MEU11_CG012_ZH0 Validator 0 97[25]
4_V
01MEU11_CG012_ZH0 Validator 0 97[25]
6_V
01MEU11_CG012_ZH0 Validator 0 97[25]
7_V
01MEU11_CG012_ZW HYS S:100 97[25]
10
01MEU11_CG012_ZW LOW 2 THRESHOLD SP S:1000 97[25]
13
01MEU11_CG012_ZW LOW 1 THRESHOLD SP S:4000 97[25]
14
01MEU11_CG012_ZW HIGH 1 THRESHOLD SP S:6000 97[25]
16
01MEU11_CG012_ZW HIGH 1 THRESHOLD SP S:7000 97[25]
17
01MEU11_EU001_2_Z INPUT MIN S:6553 98[12]
W01
01MEU11_EU001_2_Z INPUT MAX S:32767 98[12]
W09
01MEU11_EU001_2_Z OUTPUT MIN S:0 98[12]
W11
01MEU11_EU001_2_Z OUTPUT MAX S:700 98[12]
W19
01MEU11_EU001_3_Z INPUT MIN S:6553 97[11]
W01
01MEU11_EU001_3_Z INPUT MAX S:32767 97[11]
W09
01MEU11_EU001_3_Z OUTPUT MIN S:0 97[11]
W11
01MEU11_EU001_3_Z OUTPUT MAX S:10000 97[11]
W19
01MEU11_EU001_BO 93[1] 93[16]
O_0001
01MEU11_EU001_BO 96[40] 96[51]
O_0002
01MEU11_EU001_BO 95[10] 95[26]
O_0003
01MEU11_EU001_BO 95[49]
O_0004
01MEU11_EU001_BO 94[32] 94[36]
O_0005
01MEU11_EU001_BO 98[14] 98[28]
O_0006
01MEU11_EU001_BO 98[55]
O_0009
01MEU11_EU001_INT 98[12] 98[27]
16_0001
01MEU11_EU001_R01 S:10.0000000000 96[6,7,17,18,19,21]
01MEU11_EU001_S80 S8000 to LCU5 OK S:1 98[27]
00
01MEU11_EU001_T01 S:30 98[3]
XX PXXXXA4XXXX.204/A
NAME DESCRIPTION STATE INIT FROM TO
01MEU11_EU001_T02 S:1 95[5]
01MEU11_EU001_ZA0 Start speed governor 45[S3],54[S3],51[S3] 96[7]
1
01MEU11_EU001_ZA0 Stop speed governor 61[S4],58[S1],60[S1,S4] 96[6]
2
01MEU11_EU001_ZA0 ISOLATED MODE R6 FOR SELF 51[S2] 94[23]
9 SYNCHRONIZE to GOV
01MEU11_EU001_ZA1 Set GOV Condensor mode R70 53[S2] 96[19]
1
01MEU11_EU001_ZA1 Reset GOV Condensor mode 61[S1],58[S1],55[S2] 96[20]
2 R70
01MEU11_EU001_ZA2 Set GOV Insolated Network 45[S4],54[S4] 96[17]
1 mode R128
01MEU11_EU001_ZA2 Reset GOV Insolated Network 58[S1],60[S4],57[S1] 96[18]
2 mode R128
01MEU11_EU001_ZM2 MFC3000-S vs GOV MOD 77[3] 77[12]
2 EXCHANGE
01MEU11_FS001_XM5 Status 93[1]
1_V
01MKA54_AA001_XG Status 81[16]
01_V
01MKA54_AA001_ZA0 GEN EMERG FIRE FIGHTING 1 0 80[15] 81[16],80[18,21]
1 AUTO ORD
01MKA54_AA001_ZA0 GEN EMERG FIRE FIGHTING 1 0 80[15] 81[16],80[17]
2 AUTO ORDER
01MKA54_AA001_ZC0 GEN EMERG FIRE FIGHTING 1 1 81[16]
1 AUTO OPENG AUTH
01MKA54_AA001_ZC0 GEN EMERG FIRE FIGHTING 1 1 81[16]
2 AUTO CLOSG AUTH
01MKA54_AA001_ZJ0 GEN EMERG FIRE FIGHTING 1 1 81[16]
1 MANU OPENG ATH
01MKA54_AA001_ZJ0 GEN EMERG FIRE FIGHTING 1 1 81[16]
2 MANU CLOSG ATH
01MKA54_AA001_ZM GEN EMERG FIRE FIGHTING 1 0 81[5] 81[16]
00
01MKA54_AA001_ZM GEN EMERG FIRE FIGHTING 1 1 81[6] 81[16]
50
01MKA54_AA001_ZT0 GEN EMERG FIRE FIGHTING 1 S:500 81[16]
0 FAULT TEMPO VALUE
01MKA54_AA001_ZT0 GEN EMERG FIRE FIGHTING 1 S:1000 81[16]
1 OPENG PULSE VALUE
01MKA54_AA001_ZT0 GEN EMERG FIRE FIGHTING 1 S:1000 81[16]
2 CLOSG PULSE VALUE
01MKA54_AA001_ZT1 GEN EMERG FIRE FIGHTING 1 S:1200 81[16]
1 TLTE TEMPO VALUE
01MKA54_AA001_ZT1 GEN EMERG FIRE FIGHTING 1 S:1200 81[16]
2 TLTE TEMPO VALUE
01MKA54_AA001_ZU0 Validant 0 81[16]
1_V
01MKA54_AA002_XG Status 81[19]
01_V
01MKA54_AA002_ZA0 GEN EMERG FIRE FIGHTING 2 0 80[18] 81[19]
1 AUTO ORD
01MKA54_AA002_ZA0 GEN EMERG FIRE FIGHTING 2 0 80[17] 81[19]
2 AUTO ORDER
01MKA54_AA002_ZC0 GEN EMERG FIRE FIGHTING 2 1 81[19]
1 AUTO OPENG AUTH,
01MKA54_AA002_ZC0 GEN EMERG FIRE FIGHTING 2 1 81[19]
2 AUTO CLOSG AUTH
01MKA54_AA002_ZJ0 GEN EMERG FIRE FIGHTING 2 1 81[19]
1 MANU OPENG ATH
01MKA54_AA002_ZJ0 GEN EMERG FIRE FIGHTING 2 1 81[19]
2 MANU CLOSG ATH
01MKA54_AA002_ZM GEN EMERG FIRE FIGHTING 2 0 81[7] 81[19]
00
01MKA54_AA002_ZM GEN EMERG FIRE FIGHTING 2 1 81[8] 81[19]
50
01MKA54_AA002_ZT0 GEN EMERG FIRE FIGHTING 2 S:500 81[19]
0 FAULT TEMPO VALUE
01MKA54_AA002_ZT0 GEN EMERG FIRE FIGHTING 2 S:1000 81[19]
1 OPENG PULSE VALUE
01MKA54_AA002_ZT0 GEN EMERG FIRE FIGHTING 2 S:1000 81[19]
2 CLOSG PULSE VALUE
01MKA54_AA002_ZT1 GEN EMERG FIRE FIGHTING 2 S:1200 81[19]
1 TLTE TEMPO VALUE
01MKA54_AA002_ZT1 GEN EMERG FIRE FIGHTING 2 S:1200 81[19]
2 TLTE TEMPO VALUE
01MKA54_AA002_ZU0 Validant 0 81[19]
1_V
01MKA54_AU001_BO 80[11] 80[20]
O_0004
01MKA54_AU001_BO 80[11] 80[20]
O_0005
01MKA54_AU001_BO 0 80[21] 80[15]
O_0008
01MKA54_AU001_TD0 S:2 79[1]
1
XX PXXXXA4XXXX.205/A
NAME DESCRIPTION STATE INIT FROM TO
01MKA54_AU001_TD0 S:2 79[2]
2
01MKA54_AU001_TD0 S:900 80[21]
3
01MKA54_AU001_ZA0 Apply mechanical brake 58[S2],44[S1] 80[11]
1
01MKA54_AU001_ZA0 Release mechanical brake 45[S2],54[S2],51[S2],59[S1] 80[11]
2
01MKA54_AU001_ZC0 Mechanical Brake AUTO 1 80[11]
1 OPENG AUTH,
01MKA54_AU001_ZC0 Mechanical Brake AUTO 1 80[11]
2 CLOSG AUTH
01MKA54_AU001_ZJ0 Mechanical Brake MANU 1 80[11]
1 OPENG ATH
01MKA54_AU001_ZJ0 Mechanical Brake MANU 1 80[11]
2 CLOSG ATH
01MKA54_AU001_ZM Mechanical Brake 0 80[11]
00
01MKA54_AU001_ZM Mechanical Brake 1 80[11]
50
01MKA54_AU001_ZT0 Mechanical Brake FAULT S:500 80[11]
0 TEMPO VALUE
01MKA54_AU001_ZT0 Mechanical Brake OPENG S:5000 80[11]
1 PULSE VALUE
01MKA54_AU001_ZT0 Mechanical Brake CLOSG S:8000 80[11]
2 PULSE VALUE
01MKA54_AU001_ZT1 Mechanical Brake TLTE TEMPO S:8000 80[11]
1 VALUE
01MKA54_AU001_ZT1 Mechanical Brake TLTE TEMPO S:10000 80[11]
2 VALUE
01MKA54_AU001_ZU0 Validant 0 80[11]
1_V
01MKA54_CG565_XG Status 80[11]
01_V
01MKC65_CE002_ZH0 Validator 0 91[39]
7_V
01MKC65_CE002_ZW HYS S:100 91[39]
10
01MKC65_CE002_ZW HIGH 1 THRESHOLD SP 0.000000 <- S:26213 91[39]
17 > 4000.000
01MKC65_EU001_BO 91[39] 91[41]
O_0001
01MKC65_EU001_R02 S:22.00000000000 91[41]
01MKC65_EU001_RI0 <-> S:5.00000000000 87[28,46,65],88[52,54]
1
01MKC65_EU001_UIN 90[1] 90[12]
T16_0001
01MKC65_EU001_UIN 90[24] 90[35]
T16_0003
01MKC65_EU001_UIN 90[66] 90[70]
T16_0006
01MKC65_EU001_UIN 90[2] 90[13]
T16_0008
01MKC65_EU001_UIN 90[25] 90[36]
T16_0010
01MKC65_EU001_UIN 90[67] 90[71]
T16_0012
01MKC65_EU001_UIN 90[3] 90[14]
T16_0017
01MKC65_EU001_UIN 90[26] 90[37]
T16_0018
01MKC65_EU001_UIN 90[68] 90[72]
T16_0019
01MKC65_EU001_UIN 91[4] 91[15]
T16_0023
01MKC65_EU001_UIN 91[27] 91[38]
T16_0024
01MKC65_EU001_UIN 91[69] 91[73]
T16_0025
01MKC65_EU001_ZA0 Line Charge mode to exctation 45[S5],54[S5] 87[28]
4 system
01MKC65_EU001_ZA2 Exctation system Auto mode 45[S5],54[S5] 87[64]
2 select
01MKC65_GS101_TP0 S:2 85[1]
1
01MKC65_GS101_XG Status 85[1]
01_V
01MKC65_GS101_XG Status 85[1]
02_V
01MKC65_GS101_ZA0 FIELD BRAKER GS101 AUTO 0 45[S6],52[S1],54[S6] 85[1]
1 CLOSG ORD
01MKC65_GS101_ZA0 FIELD BRAKER GS101 AUTO 0 61[S3],56[S3],58[S1],60[S3] 85[1]
2 OPENG ORD
01MKC65_GS101_ZC0 FIELD BRAKER GS101 AUTO 1 85[1]
1 CLOSG AUTH
01MKC65_GS101_ZC0 FIELD BRAKER GS101 AUTO 1 85[1]
2 OPENG AUTH.
XX PXXXXA4XXXX.206/A
NAME DESCRIPTION STATE INIT FROM TO
01MKC65_GS101_ZJ0 FIELD BRAKER GS101 MANU 1 85[1]
1 CLOSG ATH
01MKC65_GS101_ZJ0 FIELD BRAKER GS101 MANU 1 85[1]
2 OPENG ATH
01MKC65_GS101_ZM FIELD BRAKER GS101 0 85[1]
00
01MKC65_GS101_ZM FIELD BRAKER GS101 0 85[1]
09 EXTRACTED
01MKC65_GS101_ZM FIELD BRAKER GS101 1 85[1]
50
01MKC65_GS101_ZT0 FIELD BRAKER GS101 FAULT S:1000 85[1]
0 DELAY
01MKC65_GS101_ZT0 FIELD BRAKER GS101 CLOSG S:500 85[1]
1 PULSE VALUE
01MKC65_GS101_ZT0 FIELD BRAKER GS101 OPENG S:500 85[1]
2 PULSE VALUE
01MKC65_GS101_ZT1 FIELD BRAKER GS101 TLTE S:1000 85[1]
1 TEMPO VALUE
01MKC65_GS101_ZU0 Validant 0 85[1]
1_V
01PAC00_AA001_XG0 Status 108[8]
1_V
01PAC00_AA001_ZA0 UNIT TECHNICAL WATER 0 49[S1] 108[8]
1 VALVE AA001 AUTO ORD
01PAC00_AA001_ZA0 UNIT TECHNICAL WATER 0 59[S1] 108[8]
2 VALVE AA001 AUTO ORDER
01PAC00_AA001_ZC0 UNIT TECHNICAL WATER 1 108[8]
1 VALVE AA001 AUTO OPENG
AUTH,
01PAC00_AA001_ZC0 UNIT TECHNICAL WATER 1 108[8]
2 VALVE AA001 AUTO CLOSG
AUTH
01PAC00_AA001_ZJ0 UNIT TECHNICAL WATER 1 108[8]
1 VALVE AA001 MANU OPENG
ATH
01PAC00_AA001_ZJ0 UNIT TECHNICAL WATER 1 108[8]
2 VALVE AA001 MANU CLOSG
ATH
01PAC00_AA001_ZM0 UNIT TECHNICAL WATER 0 108[1] 108[8]
0 VALVE AA001
01PAC00_AA001_ZM5 UNIT TECHNICAL WATER 1 108[2] 108[8]
0 VALVE AA001
01PAC00_AA001_ZT0 UNIT TECHNICAL WATER S:500 108[8]
0 VALVE AA001 FAULT TEMPO
VALUE
01PAC00_AA001_ZT0 UNIT TECHNICAL WATER S:1000 108[8]
1 VALVE AA001 OPENG PULSE
VALUE
01PAC00_AA001_ZT0 UNIT TECHNICAL WATER S:1000 108[8]
2 VALVE AA001 CLOSG PULSE
VALUE
01PAC00_AA001_ZT1 UNIT TECHNICAL WATER S:1200 108[8]
1 VALVE AA001 TLTE TEMPO
VALUE
01PAC00_AA001_ZT1 UNIT TECHNICAL WATER S:1200 108[8]
2 VALVE AA001 TLTE TEMPO
VALUE
01PAC00_AA001_ZU0 Validant 0 108[8]
1_V
01PAC00_CF972_XQ0 Status 107[3]
1_V
01PAC00_CF972_ZH0 Validator 0 107[3]
3_V
01PAC00_CF972_ZH0 Validator 0 107[3]
4_V
01PAC00_CF972_ZH0 Validator 0 107[3]
6_V
01PAC00_CF972_ZW1 HYS S:100 107[3]
0
01PAC00_CF972_ZW1 LOW 2 THRESHOLD SP S:3000 107[3]
3
01PAC00_CF972_ZW1 LOW 1 THRESHOLD SP S:4000 107[3]
4
01PAC00_CF972_ZW1 HIGH 1 THRESHOLD SP 0 <-> 10 S:24902 107[3]
6
01PAC00_CF972_ZW1 HIGH 1 THRESHOLD SP S:7000 107[3]
7
01PAC00_CF973_XQ0 Status 107[4]
1_V
01PAC00_CF973_ZH0 Validator 0 107[4]
3_V
01PAC00_CF973_ZH0 Validator 0 107[4]
4_V
01PAC00_CF973_ZH0 Validator 0 107[4]
6_V
01PAC00_CF973_ZW1 HYS S:100 107[4]
0
01PAC00_CF973_ZW1 LOW 2 THRESHOLD SP S:3000 107[4]
3
XX PXXXXA4XXXX.207/A
NAME DESCRIPTION STATE INIT FROM TO
01PAC00_CF973_ZW1 LOW 1 THRESHOLD SP S:4000 107[4]
4
01PAC00_CF973_ZW1 HIGH 1 THRESHOLD SP 0 <-> 10 S:24902 107[4]
6
01PAC00_CF973_ZW1 HIGH 1 THRESHOLD SP S:7000 107[4]
7
01PAC00_CF975_XQ0 Status 107[5]
1_V
01PAC00_CF975_ZH0 Validator 0 107[5]
3_V
01PAC00_CF975_ZH0 Validator 0 107[5]
4_V
01PAC00_CF975_ZH0 Validator 0 107[5]
6_V
01PAC00_CF975_ZW1 HYS S:100 107[5]
0
01PAC00_CF975_ZW1 LOW 2 THRESHOLD SP S:3000 107[5]
3
01PAC00_CF975_ZW1 LOW 1 THRESHOLD SP S:4000 107[5]
4
01PAC00_CF975_ZW1 HIGH 1 THRESHOLD SP 0 <-> 10 S:24902 107[5]
6
01PAC00_CF975_ZW1 HIGH 1 THRESHOLD SP S:7000 107[5]
7
01PAC00_CF976_XQ0 Status 108[6]
1_V
01PAC00_CF976_ZH0 Validator 0 108[6]
3_V
01PAC00_CF976_ZH0 Validator 0 108[6]
4_V
01PAC00_CF976_ZH0 Validator 0 108[6]
6_V
01PAC00_CF976_ZW1 HYS S:100 108[6]
0
01PAC00_CF976_ZW1 LOW 2 THRESHOLD SP S:3000 108[6]
3
01PAC00_CF976_ZW1 LOW 1 THRESHOLD SP S:4000 108[6]
4
01PAC00_CF976_ZW1 HIGH 1 THRESHOLD SP 0 <-> 10 S:24902 108[6]
6
01PAC00_CF976_ZW1 HIGH 1 THRESHOLD SP S:7000 108[6]
7
01SCC00_AA901_BO 116[8] 116[9]
O_0003
01SCC00_AA901_BO 116[8] 116[9]
O_0004
01SCC00_AA901_BO 116[3] 116[7]
O_0005
01SCC00_AA901_BO 116[5] 116[6]
O_0006
01SCC00_AA901_RI0 <-> S:1 116[3,5]
1
01SCC00_AA901_XG0 Status 116[8]
1_V
01SCC00_AA901_ZA0 Dewater Main Valve AUTO 0 46[S1] 116[7]
1 OPEN ORD
01SCC00_AA901_ZA0 Dewater Main Valve AUTO 0 47[S1],46[S3] 116[6]
2 CLOSE ORDER
01SCC00_AA901_ZA1 Dewater Main Valve AUTO 116[7] 116[8]
1 OPEN ORD
01SCC00_AA901_ZA1 Dewater Main Valve AUTO 116[6] 116[8]
2 CLOSE ORD
01SCC00_AA901_ZC0 Dewater Main Valve AUTO 1 116[8]
1 OPENG AUTH,
01SCC00_AA901_ZC0 Dewater Main Valve AUTO 1 116[8]
2 CLOSG AUTH
01SCC00_AA901_ZJ0 Dewater Main Valve MANU 1 116[8]
1 OPENG ATH
01SCC00_AA901_ZJ0 Dewater Main Valve MANU 1 116[8]
2 CLOSG ATH
01SCC00_AA901_ZM0 Dewater Main Valve 0 116[8]
0
01SCC00_AA901_ZM5 Dewater Main Valve AA901 1 116[1] 116[8]
0
01SCC00_AA901_ZT0 Dewater Main Valve FAULT S:500 116[8]
0 TEMPO VALUE
01SCC00_AA901_ZT0 Dewater Main Valve OPENG 1000 116[8]
1 PULSE VALUE
01SCC00_AA901_ZT0 Dewater Main Valve CLOSG S:1000 116[8]
2 PULSE VALUE
01SCC00_AA901_ZT1 Dewater Main Valve TLTE S:1200 116[8]
1 TEMPO VALUE
01SCC00_AA901_ZT1 Dewater Main Valve TLTE S:1200 116[8]
2 TEMPO VALUE
01SCC00_AA901_ZU0 Validant 0 116[8]
1_V
01SCC00_AA902_BI0 Timer Enable S:0 114[4,6]
1
XX PXXXXA4XXXX.208/A
NAME DESCRIPTION STATE INIT FROM TO
01SCC00_AA902_BI0 HIGH WATER TRIP ENABLE S:0 115[11]
2
01SCC00_AA902_BI0 HIGH ACTIVE POWER TRIP S:0 115[13]
3 ENABLE
01SCC00_AA902_BO 115[12] 115[19]
O_0002
01SCC00_AA902_BO 115[18] 115[21]
O_0003
01SCC00_AA902_BO 115[14] 115[20]
O_0004
01SCC00_AA902_BO 115[18] 115[21]
O_0005
01SCC00_AA902_BO 114[3] 114[16]
O_0010
01SCC00_AA902_BO 114[5] 114[16]
O_0011
01SCC00_AA902_BO 114[7] 114[15]
O_0014
01SCC00_AA902_BO 114[9] 114[15]
O_0016
01SCC00_AA902_RI0 CLOSE DURATION S:1800.00000 114[5]
1
01SCC00_AA902_RI0 OPEN DURATION S:180.00000 114[7]
2
01SCC00_AA902_RI0 S:1.00000 114[3]
3
01SCC00_AA902_RI0 S:1.00000 114[9]
4
01SCC00_AA902_RI0 S:30.0000000000 115[12]
5
01SCC00_AA902_RI0 S:5.00000000000 115[14]
6
01SCC00_AA902_XG0 Status 115[18]
1_V
01SCC00_AA902_ZA0 DEWATER AUX VALVE AUTO 0 114[17] 115[18]
1 OPEN ORD
01SCC00_AA902_ZA0 DEWATER AUX VALVE AUTO 0 47[S1] 114[15]
2 CLOSE ORDER
01SCC00_AA902_ZA1 DEWATER AUXIL VALVE 114[15] 115[18]
2 CLOSE ORDER
01SCC00_AA902_ZC0 DEWATER AUX VALVE AUTO 1 115[18]
1 OPENG AUTH,
01SCC00_AA902_ZC0 DEWATER AUX VALVE AUTO 1 115[18]
2 CLOSG AUTH
01SCC00_AA902_ZJ0 DEWATER AUX VALVE MANU 1 115[18]
1 OPENG ATH
01SCC00_AA902_ZJ0 DEWATER AUX VALVE MANU 1 115[18]
2 CLOSG ATH
01SCC00_AA902_ZM0 DEWATER AUX VALVE 0 115[18]
0
01SCC00_AA902_ZM5 DEWATER AUX VALVE 1 115[1] 115[18]
0
01SCC00_AA902_ZT0 DEWATER AUX VALVE FAULT S:500 115[18]
0 TEMPO VALUE
01SCC00_AA902_ZT0 DEWATER AUX VALVE OPENG S:1000 115[18]
1 PULSE VALUE
01SCC00_AA902_ZT0 DEWATER AUX VALVE CLOSG S:1000 115[18]
2 PULSE VALUE
01SCC00_AA902_ZT1 DEWATER AUX VALVE TLTE S:1200 115[18]
1 TEMPO VALUE
01SCC00_AA902_ZT1 DEWATER AUX VALVE TLTE S:1200 115[18]
2 TEMPO VALUE
01SCC00_AA902_ZU0 Validant 0 115[18]
1_V
01SCC00_EA001_CO 118[4] 118[7]
NBOO_0001
01SCC00_EA001_CO 118[5] 118[7]
NBOO_0002
01SCC00_EA001_CO 117[1] 117[2]
NREAL_0001
01SCC00_EA001_CO S:1.00000000000 118[4]
NRI01
01SCC00_EA001_CO S:240.000000000 118[5]
NRI02
01SCC00_EA001_CO AA901 OPEN-CLOSE Delay <-> S:20 118[6]
NRI03
01SCC00_EA001_SFC 46[T5]
_S99_X
01SCC00_EA001_ZS0 DEWATER SEQUENCE STEP1 117[11] 46[T1,T5]
15 COND
01SCC00_EA001_ZS0 DEWATER SEQUENCE STEP2 118[9] 46[T2]
25 COND
01SCC00_EA001_ZS0 DEWATER SEQUENCE STEP3 118[12] 46[T3]
35 COND
01SCC00_EA001_ZS0 DEWATER SEQUENCE STEP4 118[14] 46[T4]
45 COND
01SCC00_EA002_CO 119[4] 119[6]
NBOO_0001
XX PXXXXA4XXXX.209/A
NAME DESCRIPTION STATE INIT FROM TO
01SCC00_EA002_CO 119[5] 119[6]
NBOO_0002
01SCC00_EA002_CO 119[1] 119[4]
NREAL_0001
01SCC00_EA002_CO S:5.00000 119[1]
NRI01
01SCC00_EA002_CO S:1.00000000000 119[5]
NRI02
01SCC00_EA002_CO S:2.00000 119[1]
NRI03
01SCC00_EA002_CO <-> S:10 119[2]
N_T01
01SCC00_EA002_ZS0 REWATER SEQUENCE STEP1 119[8] 47[T1]
15 COND
01SCC00_EA002_ZS0 REWATER SEQUENCE STEP2 119[10] 47[T2]
25 COND
01SCC00_EA002_ZS0 REWATER SEQUENCE STEP3 119[11] 47[T3]
35 COND
01SCC00_EA002_ZS0 REWATER SEQUENCE STEP4 119[13] 47[T5]
45 COND
01SIM_ACT_BOO_000 63[7] 63[16]
1
01SIM_ACT_BOO_000 64[11] 64[22]
2
01SIM_ACT_BOO_000 64[23] 64[30,31,32],65[33]
3
01SIM_ACT_BOO_000 63[2,7]
4
01SIM_ACT_BOO_000 63[29] 63[34]
6
01SIM_ACT_INIT S:75 64[6]
01SIM_ACT_INT16_00 S:100 64[22]
01
01SIM_ACT_INT16_00 64[20] 64[24,25,26,27]
02
01SIM_ACT_INT16_00 64[21] 64[28]
05
01SIM_ACT_REAL_00 64[12]
01
01SIM_ACT_REAL_00 64[5] 64[13]
02
01SIM_ACT_REAL_00 64[13] 64[20]
03
01SIM_ACT_REAL_00 64[14] 64[21]
08
01SIM_ACT_REAL_00 64[6] 64[14]
09
01SIM_INIT_1SYCLE 5s Startup later as 1st Sycle 66[2] 68[9,10,11,21,22,23,24,31,32,33,35,
36,37,38],66[3,4,15,16,17,40,41,42,4
3],67[5,6,7,8,18,19,20,39,44,45,46,4
7,48,49],69[12,13,14,25,26,27,28,29,
30,34]
01SIM_INIT_BOO_000 66[1] 66[2]
4
01SIM_INIT_DW001 LCU Control Level DOWN 66[50]
01SIM_INIT_DW003 Synchronizer Control Mode 66[51]
DOWN
01SIM_INIT_TURE 1st Sycle default value 1 S:1 68[9,10,11,21,22,23,24,31,32,33,35,
36,37,38],66[3,4,15,16,17,40,41,42,4
3],67[5,6,7,8,18,19,20,39,44,45,46,4
7,48,49],69[12,13,14,25,26,27,28,29,
30,34]
01SIM_INIT_UP001 LCU Control Level UP 66[50]
01SIM_INIT_UP003 Synchronizer Control Mode UP 66[51]
01SIM_REG01_BI01 DEWATER STATE FOR POWER 73[30],70[1]
SELECTOR
01SIM_REG01_BOO_ 72[51]
0001
01SIM_REG01_BOO_ 70[17] 70[42]
0002
01SIM_REG01_BOO_ 73[34] 73[43]
0003
01SIM_REG01_BOO_ 72[24] 72[51]
0004
01SIM_REG01_BOO_ 70[42]
0006
01SIM_REG01_BOO_ 71[13] 71[36]
0007
01SIM_REG01_BOO_ 72[29] 72[51]
0008
01SIM_REG01_BOO_ 72[51]
0009
01SIM_REG01_BOO_ 72[51]
0010
01SIM_REG01_BOO_ 72[46] 72[53]
0011
01SIM_REG01_BOO_ 72[51]
0014
XX PXXXXA4XXXX.210/A
NAME DESCRIPTION STATE INIT FROM TO
01SIM_REG01_BOO_ 70[42,52]
0016
01SIM_REG01_BOO_ 70[52] 70[54]
0018
01SIM_REG01_BOO_ 70[16] 70[42]
0020
01SIM_REG01_II01 S:4000 70[5],72[7]
01SIM_REG01_II02 S:4545 70[3]
01SIM_REG01_II03 S:10000 70[4]
01SIM_REG01_II04 0.000000 <- S:1380 72[9]
> 20.00000
01SIM_REG01_II05 S:1600 72[8]
01SIM_REG01_II06 224.0000 <- S:20000 73[35]
> 300.0000
01SIM_REG01_II15 S:3200 72[26]
01SIM_REG01_INT16_ 70[18] 70[39]
0001
01SIM_REG01_INT16_ 72[6] 72[23]
0003
01SIM_REG01_INT16_ 70[19] 70[40]
0004
01SIM_REG01_INT16_ 72[25] 72[45]
0005
01SIM_REG01_INT16_ 70[20] 70[41]
0006
01SIM_REG01_INT16_ 72[26] 72[47]
0007
01SIM_REG01_INT16_ 72[27] 72[48]
0010
01SIM_REG01_INT16_ 73[33] 73[50]
0012
01SIM_REG01_R10 S:-3000.00000 70[19]
01SIM_REG01_R11 S:12000.00000 70[19]
01SIM_REG01_REAL_ 70[14] 70[42]
0001
01SIM_REG01_REAL_ 70[3] 70[18]
0002
01SIM_REG01_REAL_ 70[15] 70[42]
0003
01SIM_REG01_REAL_ 73[30],71[13],70[5,42]
0004
01SIM_REG01_REAL_ 70[3,42]
0005
01SIM_REG01_REAL_ 70[1,42]
0006
01SIM_REG01_REAL_ 73[11] 73[31]
0007
01SIM_REG01_REAL_ 72[7] 72[25]
0008
01SIM_REG01_REAL_ 70[4] 70[19]
0009
01SIM_REG01_REAL_ 72[23] 72[51]
0010
01SIM_REG01_REAL_ 70[5] 70[20]
0011
01SIM_REG01_REAL_ 72[7,51]
0012
01SIM_REG01_REAL_ 72[21] 72[51]
0013
01SIM_REG01_REAL_ 72[22] 72[51]
0015
01SIM_REG01_REAL_ 72[8] 72[26,46]
0016
01SIM_REG01_REAL_ 72[51]
0017
01SIM_REG01_REAL_ 72[8,51]
0018
01SIM_REG01_REAL_ 73[30],70[1]
0019
01SIM_REG01_REAL_ 72[28] 72[49]
0020
01SIM_REG01_REAL_ 73[34],72[9,51]
0021
01SIM_REG01_REAL_ 73[12] 73[32]
0022
01SIM_REG01_REAL_ 72[44] 72[51]
0023
01SIM_REG01_REAL_ 72[51]
0024
01SIM_REG01_REAL_ 72[9] 72[27]
0025
01SIM_REG01_REAL_ 72[28,51]
0026
01SIM_REG01_REAL_ 70[1] 70[4]
0027
XX PXXXXA4XXXX.211/A
NAME DESCRIPTION STATE INIT FROM TO
01SIM_REG01_REAL_ 71[2] 71[13]
0029
01SIM_REG01_REAL_ 73[10,30]
0033
01SIM_REG01_REAL_ 73[10] 73[33]
0034
01SIM_REG01_RI01 0.000000 <- S:0.19000 70[42]
> 100.0000
01SIM_REG01_RI02 0.000000 <- S:0.00500 70[42]
> 100.0000
01SIM_REG01_RI03 0.000000 <- S:0.00500 72[44]
> 100.0000
01SIM_REG01_RI06 S:100.000000000 64[12]
01SIM_REG01_RI07 S:10000.00000 70[14]
01SIM_REG01_RI08 S:10000.0000000 70[15]
01SIM_REG01_RI09 S:10000.00000 72[22,23]
01SIM_REG01_RI10 S:1380.00000 72[21]
01SIM_REG01_RI11 S:1.00000 73[30]
01SIM_REG01_RI13 0.000000 <- S:1 72[44]
> 100.0000
01SIM_REG01_RI16 S:108 72[46]
01SIM_REG01_RI21 S:0.18 71[2]
01SIM_REG01_RI22 S:0.2 71[2]
01SIM_REG01_RI31 S:100000 72[28]
XX PXXXXA4XXXX.212/A
6 ADJUSTABLE PARAMETERS
XX PXXXXA4XXXX.213/A
DIAGRAM SHEET FUNCTIONAL BLOCK NAME STATE RANGE INIT LABEL
NAME NUMBER VALUE
TON_R 12 01SCC00_AA902_RI 30
05
AND 13 01SCC00_AA902_BI 0 HIGH ACTIVE POWER TRIP
03 ENABLE
TON_R 14 01SCC00_AA902_RI 5
06
FB_VA2 18 01SCC00_AA902_Z 500 DEWATER AUX VALVE
T00 FAULT TEMPO VALUE
01SCC00_AA902_Z 1000 DEWATER AUX VALVE
T01 OPENG PULSE VALUE
01SCC00_AA902_Z 1000 DEWATER AUX VALVE
T02 CLOSG PULSE VALUE
01SCC00_AA902_Z 1200 DEWATER AUX VALVE TLTE
T11 TEMPO VALUE
01SCC00_AA902_Z 1200 DEWATER AUX VALVE TLTE
T12 TEMPO VALUE
ACT 64 SEL 6 01SIM_ACT_INIT 75
Actuator Simulate 12 01SIM_REG01_RI06 100
SIM_DEVICE_2P 22 01SIM_ACT_INT16_ -32768 <-> 100
OS 0001 32767
AU001 78 TON_R 1 01MEA41_AU001_R 2
Turbine Auxilary I01
AU001 79 TON_R 1 01MKA54_AU001_T 2
Generator Auxilary D01
2 01MKA54_AU001_T 2
D02
80 FB_VA2 11 01MKA54_AU001_Z 500 Mechanical Brake FAULT
T00 TEMPO VALUE
01MKA54_AU001_Z 5000 Mechanical Brake OPENG
T01 PULSE VALUE
01MKA54_AU001_Z 8000 Mechanical Brake CLOSG
T02 PULSE VALUE
01MKA54_AU001_Z 8000 Mechanical Brake TLTE
T11 TEMPO VALUE
01MKA54_AU001_Z 10000 Mechanical Brake TLTE
T12 TEMPO VALUE
81 FB_VA2 16 01MKA54_AA001_Z 500 GEN EMERG FIRE FIGHTING
T00 1 FAULT TEMPO VALUE
01MKA54_AA001_Z 1000 GEN EMERG FIRE FIGHTING
T01 1 OPENG PULSE VALUE
01MKA54_AA001_Z 1000 GEN EMERG FIRE FIGHTING
T02 1 CLOSG PULSE VALUE
01MKA54_AA001_Z 1200 GEN EMERG FIRE FIGHTING
T11 1 TLTE TEMPO VALUE
01MKA54_AA001_Z 1200 GEN EMERG FIRE FIGHTING
T12 1 TLTE TEMPO VALUE
19 01MKA54_AA002_Z 500 GEN EMERG FIRE FIGHTING
T00 2 FAULT TEMPO VALUE
01MKA54_AA002_Z 1000 GEN EMERG FIRE FIGHTING
T01 2 OPENG PULSE VALUE
01MKA54_AA002_Z 1000 GEN EMERG FIRE FIGHTING
T02 2 CLOSG PULSE VALUE
01MKA54_AA002_Z 1200 GEN EMERG FIRE FIGHTING
T11 2 TLTE TEMPO VALUE
01MKA54_AA002_Z 1200 GEN EMERG FIRE FIGHTING
T12 2 TLTE TEMPO VALUE
80 TON_R 21 01MKA54_AU001_T 900
D03
CON 147 TON_R 1 01CJA00_EA043_RI 10
CONDITIONS 01
119 SEL 1 01SCC00_EA002_C 5
ONRI01
01SCC00_EA002_C 2
ONRI03
154 TON_R 2 01CJA00_EA032_C 15
ONR01
117 THR_HL 2 01MEA41_CP505_Z -32768 <-> 200 HYS
W10 32767
01MEA41_CP505_Z 0 <-> 2000 6553 <-> 23592 LOW 2 THRESHOLD SP
W13 32767
01MEA41_CP505_Z 0.000000 <- 6553 <-> 18349 LOW 1 THRESHOLD SP
W14 > 2000 32767
01MEA41_CP505_Z 0.000000 <- 6553 <-> 9174 HIGH 1 THRESHOLD SP
W16 > 2000 32767
01MEA41_CP505_Z 0.000000 <- 6553 <-> 6700 HIGH 1 THRESHOLD SP
W17 > 2000 32767
119 TON_R 2 01SCC00_EA002_C 10
ON_T01
118 TON_R 4 01SCC00_EA001_C 1
ONRI01
5 01SCC00_EA001_C 240
ONRI02
119 TON_R 5 01SCC00_EA002_C 1
ONRI02
118 TON_R 6 01SCC00_EA001_C 20 AA901 OPEN-CLOSE Delay
ONRI03
XX PXXXXA4XXXX.214/A
DIAGRAM SHEET FUNCTIONAL BLOCK NAME STATE RANGE INIT LABEL
NAME NUMBER VALUE
121 LE 9 01CJA00_EA073_II0 -128 <-> 127 50 FREQ DELTA
1
128 SEL_B 15 01CJA00_EA000_C 0 LCU1 & 3 S8000 NOT
ON_E01 CONNECTED
16 01CJA00_EA000_C 0 LCU1 & 3 S8000 NOT
ON_E01 CONNECTED
17 01CJA00_EA000_C 0 LCU1 & 3 S8000 NOT
ON_E01 CONNECTED
18 01CJA00_EA000_C 0 LCU1 & 8 S8000 NOT
ON_E02 CONNECTED
19 01CJA00_EA000_C 0 LCU1 & 8 S8000 NOT
ON_E02 CONNECTED
129 SEL_B 20 01CJA00_EA000_C 0 LCU1 & 8 S8000 NOT
ON_E02 CONNECTED
21 01CJA00_EA000_C 0 LCU1 & 5 S8000 NOT
ON_E03 CONNECTED
138 SEL_B 27 01CJA00_EA000_C 0
ONBI01
DE001 165 FB_HMI_SP 23 01CJA00_DE001_Z 0.000000 <- 0 <-> 12000 800 ACTIVE POWER MIN SP
UNIT ACTIVE POWER CONTROL U01 > 120 VALUE
01CJA00_DE001_Z -32768 <-> 1 Input Scale to output
V01 32767
01CJA00_DE001_Z 0.000000 <- 0 <-> 12000 800 ACTIVE POWER Init sp value
W01 > 120
LIMIT 24 01CJA00_DE001_HI 0.000000 <- 0 <-> 30000 10000 ACTIVE POWER HIGH LIMIT
> 120
01CJA00_DE001_Z 0.000000 <- 0 <-> 12000 800 ACTIVE POWER MIN SP
U01 > 120 VALUE
167 TP_R 26 01CJA00_DE001_Z 0.50000 PULSE LENGTH
T02
27 01CJA00_DE001_Z 0.50000 PULSE LENGTH
T02
GT 28 01CJA00_DE001_Z 0.000000 <- 0 <-> 12000 800 ACTIVE POWER Init sp value
W01 > 120
165 AO_SCALE 29 01CJA00_DE001_1_ -32768 <-> 0 INPUT MIN
ZW21 32767
01CJA00_DE001_1_ -32768 <-> 10000 INPUT MAX
ZW29 32767
01CJA00_DE001_1_ -32768 <-> 6553 OUTPUT MIN
ZW31 32767
01CJA00_DE001_1_ -32768 <-> 32767 OUTPUT MAX
ZW39 32767
166 FB_PULS_REG 35 01CJA00_DE001_D 0.000000 <- 0.000000000 1000 ACTIVE POWER reg max
LT > 300.0000 00 <-> delta
30000.00000
00
01CJA00_DE001_Z -32768 <-> 5 PULSE REGUL INTERVAL
T01 32767 TIME(CYC)
01CJA00_DE001_Z -32768 <-> 50 PULSE REGUL DELTA
X01 32767 RATE(%)
01CJA00_DE001_Z -120 <-> 120 -12000 <-> 200 PULSE REGUL DEAD BAND
Z01 12000
167 TP_R 36 01CJA00_DE001_Z 0.50000 PULSE LENGTH
T02
37 01CJA00_DE001_Z 0.50000 PULSE LENGTH
T02
166 GE 38 01CJA00_DE001_T 0.000000 <- 0 <-> 12000 3000 ACTIVE POWER DLT THR
H01 > 120
165 AO_SCALE 39 01CJA00_DE001_1_ -32768 <-> 0 INPUT MIN
ZW21 32767
01CJA00_DE001_1_ -32768 <-> 10000 INPUT MAX
ZW29 32767
01CJA00_DE001_2_ -32768 <-> 0 OUTPUT MIN
ZW31 32767
01CJA00_DE001_2_ -32768 <-> 25000 OUTPUT MAX
ZW39 32767
166 SEL 42 01CJA00_DE001_T 8
N1
01CJA00_DE001_T 3
N2
43 01CJA00_DE001_T 1
P1
01CJA00_DE001_T 1
P2
DE002 170 FB_HMI_SP 18 01CJA00_DE002_Z -120 <-> 120 -12000 <-> -10000 REACTIVE POWER MIN SP
UNIT REACTIVE POWER CONTROL U01 12000 VALUE
01CJA00_DE002_Z -32768 <-> 1 Input Scale to output
V01 32767
01CJA00_DE002_Z -120 <-> 120 -12000 <-> 0 REACTIVE POWER Init sp
W01 12000 value
LIMIT 19 01CJA00_DE002_HI -120 <-> 120 -12000 <-> 10000 REACTIVE POWER HIGH
12000 LIMIT
01CJA00_DE002_L -120 <-> 120 -12000 <-> -10000 REACTIVE POWER LOW
O 12000 LIMIT
XX PXXXXA4XXXX.215/A
DIAGRAM SHEET FUNCTIONAL BLOCK NAME STATE RANGE INIT LABEL
NAME NUMBER VALUE
171 FB_PULS_REG 26 01CJA00_DE002_D -300.000 <-> - 1000 REACTIVE POWER reg max
LT 300.0000 30000.00000 delta
0 <->
30000.00000
00
01CJA00_DE002_Z -32768 <-> 50 PULSE REGUL INTERVAL
T01 32767 TIME(CYC)
01CJA00_DE002_Z -32768 <-> 50 PULSE REGUL DELTA
X01 32767 RATE(%)
01CJA00_DE002_Z -120 <-> 120 -12000 <-> 200 PULSE REGUL DEAD BAND
Z01 12000
170 AO_SCALE 27 01CJA00_DE002_1_ -120 <-> 120 -12000 <-> -10000 INPUT MIN
ZW21 12000
01CJA00_DE002_1_ -120 <-> 120 -12000 <-> 10000 INPUT MAX
ZW29 12000
01CJA00_DE002_1_ -32768 <-> 6553 OUTPUT MIN
ZW31 32767
01CJA00_DE002_1_ -32768 <-> 32767 OUTPUT MAX
ZW39 32767
171 GE 28 01CJA00_DE002_T -120 <-> 120 -12000 <-> 3000 REACTIVE POWER DLT THR
H01 12000
SEL 36 01CJA00_DE002_T 8
N1
01CJA00_DE002_T 10
N2
37 01CJA00_DE002_T 0.500000
P1 000000
01CJA00_DE002_T 1
P2
DE003 189 FB_HMI_SP 3 01CJA00_DE003_BI 0 Voltage init flag
UNIT VOLTAGE CONTROL 01
01CJA00_DE003_Z 0 Force UNIT VOLTAGE sp to 0
A01
01CJA00_DE003_Z 0.000000 <- 0 <-> 2000 1242 UNIT VOLTAGE MIN SP
U01 > 20.00000 VALUE
01CJA00_DE003_Z -32768 <-> 1 Input Scale to output
V01 32767
01CJA00_DE003_Z 0.000000 <- 0 <-> 2000 1380 UNIT VOLTAGE Init sp value
W01 > 20.00000
LIMIT 4 01CJA00_DE003_HI 0.000000 <- 0 <-> 2000 1518 UNIT VOLTAGE HIGH LIMIT
> 20.00000
01CJA00_DE003_Z 0.000000 <- 0 <-> 2000 1242 UNIT VOLTAGE MIN SP
U01 > 20.00000 VALUE
191 TP_R 6 01CJA00_DE003_R 0.50000
01
LT 7 01CJA00_DE003_I0 -100.000 <-> -10000 <-> -200
1 100.0000 10000
TP_R 8 01CJA00_DE003_R 0.50000
01
GT 9 01CJA00_DE003_I0 -100.000 <-> -10000 <-> 200
2 100.0000 10000
190 FB_PULS_REG 11 01CJA00_DE003_D 0.000000 <- 0.000000000 50 UNIT VOLTAGE reg max delta
LT > 30.00000 00 <->
3000.000000
00
01CJA00_DE003_Z -32768 <-> 5 PULSE REGUL INTERVAL
T01 32767 TIME(CYC)
01CJA00_DE003_Z -32768 <-> 50 PULSE REGUL DELTA
X01 32767 RATE(%)
01CJA00_DE003_Z -32768 <-> 5 PULSE REGUL DEAD BAND
Z01 32767
191 TP_R 12 01CJA00_DE003_R 0.50000
01
13 01CJA00_DE003_R 0.50000
01
189 AO_SCALE 14 01CJA00_DE003_1_ 0.000000 <- 0 <-> 2000 1242 INPUT MIN
ZW21 > 20.00000
01CJA00_DE003_1_ 0.000000 <- 0 <-> 2000 1518 INPUT MAX
ZW29 > 20.00000
01CJA00_DE003_1_ -32768 <-> 6553 OUTPUT MIN
ZW31 32767
01CJA00_DE003_1_ -32768 <-> 32767 OUTPUT MAX
ZW39 32767
190 GE 15 01CJA00_DE003_T 0.000000 <- 0 <-> 2000 50 UNIT VOLTAGE DLT THR
H1 > 20.00000
SEL 16 01CJA00_DE003_T 8
N1
01CJA00_DE003_T 10
N2
17 01CJA00_DE003_T 0.500000
P1 000000
01CJA00_DE003_T 1
P2
DG001 187 FB_HMI_SP 3 01CJA00_DG001_BI 0 WG init flag
WG OPENING LOAD CONTROL 01CJA00_DG001_Z 0 Force WG OPENING sp to 0
A01
XX PXXXXA4XXXX.216/A
DIAGRAM SHEET FUNCTIONAL BLOCK NAME STATE RANGE INIT LABEL
NAME NUMBER VALUE
01CJA00_DG001_Z 0.000000 <- 0 <-> 10000 1300 WG OPENING MIN SP VALUE
U01 > 100.0000
01CJA00_DG001_Z -32768 <-> 1 Input Scale to output
V01 32767
01CJA00_DG001_Z 0.000000 <- 0 <-> 10000 1400 WG OPENING Init sp value
W01 > 100.0000
LIMIT 4 01CJA00_DG001_HI 0.000000 <- 0 <-> 10000 9800 WG OPENING HIGH LIMIT
> 100.0000
01CJA00_DG001_Z 0.000000 <- 0 <-> 10000 1300 WG OPENING MIN SP VALUE
U01 > 100.0000
ADD 6 01CJA00_DG001_Z 0.000000 <- 0 <-> 10000 1300 WG OPENING MIN SP VALUE
U01 > 100.0000
188 FB_PULS_REG 8 01CJA00_DG001_D 0.000000 <- 0.000000000 500 WG OPENING reg max delta
LT > 100.0000 00 <->
10000.00000
00
01CJA00_DG001_Z -32768 <-> 5 PULSE REGUL INTERVAL
T01 32767 TIME(CYC)
01CJA00_DG001_Z -32768 <-> 1 PULSE REGUL DELTA
X01 32767 RATE(%)
01CJA00_DG001_Z -100.000 <-> -10000 <-> 100 PULSE REGUL DEAD BAND
Z01 100.0000 10000
187 AO_SCALE 9 01CJA00_DG001_1 0.000000 <- 0 <-> 10000 0 INPUT MIN
_ZW21 > 100.0000
01CJA00_DG001_1 0.000000 <- 0 <-> 10000 10000 INPUT MAX
_ZW29 > 100.0000
01CJA00_DG001_1 -32768 <-> 6553 OUTPUT MIN
_ZW31 32767
01CJA00_DG001_1 -32768 <-> 32767 OUTPUT MAX
_ZW39 32767
10 01CJA00_DG001_1 0.000000 <- 0 <-> 10000 0 INPUT MIN
_ZW21 > 100.0000
01CJA00_DG001_1 0.000000 <- 0 <-> 10000 10000 INPUT MAX
_ZW29 > 100.0000
01CJA00_DG001_2 -32768 <-> 0 OUTPUT MIN
_ZW31 32767
01CJA00_DG001_2 -32768 <-> 1000 OUTPUT MAX
_ZW39 32767
188 GE 11 01CJA00_DG001_T 0.000000 <- 0 <-> 10000 1000 WG OPENING DLT THR
H1 > 100.0000
SEL 12 01CJA00_DG001_T 8
N1
01CJA00_DG001_T 4
N2
13 01CJA00_DG001_T 0.50000
P1
01CJA00_DG001_T 1
P2
EB000 181 TOF_R 15 01CJA00_EB000_RI 5
L01 WATCHDOG 01
16 01CJA00_EB000_RI 5
01
17 01CJA00_EB000_RI 5
01
18 01CJA00_EB000_RI 5
01
19 01CJA00_EB000_RI 5
01
EU001 98 TON_R 3 01MEU11_EU001_T 30
Speed Governor System 01
95 TON_R 5 01MEU11_EU001_T 1
02
96 TP_R 6 01MEU11_EU001_R 10
01
7 01MEU11_EU001_R 10
01
95 TON_R 10 01CJA00_DE003_T 20
D01
97 AI_SCALE 11 01MEU11_EU001_3 -32768 <-> 6553 INPUT MIN
_ZW01 32767
01MEU11_EU001_3 -32768 <-> 32767 INPUT MAX
_ZW09 32767
01MEU11_EU001_3 -32768 <-> 0 OUTPUT MIN
_ZW11 32767
01MEU11_EU001_3 -32768 <-> 10000 OUTPUT MAX
_ZW19 32767
98 AI_SCALE 12 01MEU11_EU001_2 -32768 <-> 6553 INPUT MIN
_ZW01 32767
01MEU11_EU001_2 -32768 <-> 32767 INPUT MAX
_ZW09 32767
01MEU11_EU001_2 -32768 <-> 0 OUTPUT MIN
_ZW11 32767
01MEU11_EU001_2 -32768 <-> 700 OUTPUT MAX
_ZW19 32767
TON_R 14 01CJA00_DE003_T 40
D11
XX PXXXXA4XXXX.217/A
DIAGRAM SHEET FUNCTIONAL BLOCK NAME STATE RANGE INIT LABEL
NAME NUMBER VALUE
96 TP_R 17 01MEU11_EU001_R 10
01
18 01MEU11_EU001_R 10
01
19 01MEU11_EU001_R 10
01
21 01MEU11_EU001_R 10
01
97 THR_HL 25 01MEU11_CG012_Z -32768 <-> 100 HYS
W10 32767
01MEU11_CG012_Z -32768 <-> 1000 LOW 2 THRESHOLD SP
W13 32767
01MEU11_CG012_Z -32768 <-> 4000 LOW 1 THRESHOLD SP
W14 32767
01MEU11_CG012_Z -32768 <-> 6000 HIGH 1 THRESHOLD SP
W16 32767
01MEU11_CG012_Z -32768 <-> 7000 HIGH 1 THRESHOLD SP
W17 32767
98 SEL 27 01MEU11_EU001_S 1 S8000 to LCU5 OK
8000
EU001 87 TP_R 28 01MKC65_EU001_R 5
Excitation System I01
EU001 94 TON_R 32 01CJA00_DE003_T 2
Speed Governor System D02
EU001 91 THR_HI 39 01MKC65_CE002_Z -32768 <-> 100 HYS
Excitation System W10 32767
01MKC65_CE002_Z 0.000000 <- 6553 <-> 26213 HIGH 1 THRESHOLD SP
W17 > 4000.000 32767
TON_R 41 01MKC65_EU001_R 22
02
87 TP_R 46 01MKC65_EU001_R 5
I01
88 TP_R 52 01MKC65_EU001_R 5
I01
54 01MKC65_EU001_R 5
I01
87 TP_R 65 01MKC65_EU001_R 5
I01
EU014 103 FB_VRE_2POS 5 01MAU24_EU014_D 0 <-> 200
Governor Oil Station 01 2147483647
01MAU24_EU014_ 0 <-> 65535 2
W01
6 01MAU24_EU014_D 0 <-> 200
03 2147483647
01MAU24_EU014_ 0 <-> 65535 2
W01
101 THR_HL 7 01MAU24_CP001_Z -32768 <-> 100 HYS
W10 32767
01MAU24_CP001_Z 0 <-> 50 6553 <-> 25427 LOW 2 THRESHOLD SP
W13 32767
01MAU24_CP001_Z 0 <-> 50 6553 <-> 28572 HIGH 1 THRESHOLD SP
W16 32767
01MAU24_CP001_Z 0 <-> 50 6553 <-> 29612 HIGH 1 THRESHOLD SP
W17 32767
8 01MAU24_CP001_Z -32768 <-> 100 HYS
W10 32767
01MAU24_CP001_Z 0 <-> 50 6553 <-> 26475 LOW 1 THRESHOLD SP
W14 32767
102 TON_R 14 01MAU24_EU014_R 5
I02
100 TP_R 15 01MAU24_EU014_R 10
I01
16 01MAU24_EU014_R 10
I01
17 01MAU24_EU014_R 10
I01
18 01MAU24_EU014_R 10
I01
103 FB_VRE_2POS 27 01MAU24_EU014_D 0 <-> 200
02 2147483647
01MAU24_EU014_ 0 <-> 65535 2
W01
28 01MAU24_EU014_D 0 <-> 200
04 2147483647
01MAU24_EU014_ 0 <-> 65535 2
W01
FE001 105 AO_SCALE 2 01BBA00_FE001_3_ 120000 INPUT MAX
Electrical Measurement ZW01
01BBA00_FE001_3_ -120000 INPUT MIN
ZW09
01BBA00_FE001_3_ -32768 <-> -12000 OUTPUT MIN
ZW11 32767
01BBA00_FE001_3_ -32768 <-> 12000 OUTPUT MAX
ZW19 32767
104 AI_SCALE 5 01BBA00_FE001_1_ -32768 <-> 6553 INPUT MIN
ZW01 32767
XX PXXXXA4XXXX.218/A
DIAGRAM SHEET FUNCTIONAL BLOCK NAME STATE RANGE INIT LABEL
NAME NUMBER VALUE
01BBA00_FE001_1_ -32768 <-> 32767 INPUT MAX
ZW09 32767
01BBA00_FE001_1_ -32768 <-> -3000 OUTPUT MIN
ZW11 32767
01BBA00_FE001_1_ -32768 <-> 12000 OUTPUT MAX
ZW19 32767
AO_SCALE 6 01BBA00_FE001_2_ -32768 <-> -30000 INPUT MIN
ZW01 32767
01BBA00_FE001_2_ 120000 INPUT MAX
ZW09
01BBA00_FE001_2_ -32768 <-> -3000 OUTPUT MIN
ZW11 32767
01BBA00_FE001_2_ -32768 <-> 12000 OUTPUT MAX
ZW19 32767
106 AI_SCALE 9 01BBA00_FE001_5_ -32768 <-> 6553 INPUT MIN
ZW01 32767
01BBA00_FE001_5_ -32768 <-> 32767 INPUT MAX
ZW09 32767
01BBA00_FE001_5_ -32768 <-> 0 OUTPUT MIN
ZW11 32767
01BBA00_FE001_5_ -32768 <-> 2000 OUTPUT MAX
ZW19 32767
104 THR_HL 12 01BBA00_DE001_Z -32768 <-> 100 HYS
W10 32767
01BBA00_DE001_Z 0.000000 <- 0 <-> 12000 400 LOW 1 THRESHOLD SP
W14 > 120
01BBA00_DE001_Z 0.000000 <- 0 <-> 12000 1000 HIGH 1 THRESHOLD SP
W16 > 120
01BBA00_DE001_Z 0.000000 <- 0 <-> 12000 1200 HIGH 1 THRESHOLD SP
W17 > 120
THR_HI 13 01BBA00_DE001_Z -32768 <-> 100 HYS
W10 32767
01BBA00_DE001_Z -120 <-> 120 -12000 <-> 800 LOW 2 THRESHOLD SP
W13 12000
106 AO_SCALE 15 01BBA00_FE001_6_ -32768 <-> 0 INPUT MIN
ZW01 32767
01BBA00_FE001_6_ -32768 <-> 20000 INPUT MAX
ZW09 32767
01BBA00_FE001_6_ -32768 <-> 0 OUTPUT MIN
ZW11 32767
01BBA00_FE001_6_ -32768 <-> 2000 OUTPUT MAX
ZW19 32767
THR_HL 18 01BBA00_DE003_Z 0.000000 <- 0 <-> 2000 50 LOW 1 THRESHOLD SP
W14 > 20
01BBA00_DE003_Z 0.000000 <- 0 <-> 2000 1310 HIGH 1 THRESHOLD SP
W17 > 20
01BBA00_FE001_II0 0.000000 <- 0 <-> 3000 10
1 > 30.00000
105 THR_LO 20 01BBA00_DE003_Z -32768 <-> 50 HYS
W10 32767
01BBA00_DE003_Z -120 <-> 120 -12000 <-> 300 LOW 2 THRESHOLD SP
W13 12000
GS000 110 FB_VRE_2POS 2 01BFA00_GS000_T 0 <-> 800
Unit 400V Switchboard 01 2147483647
4 01BFA00_GS000_T 0 <-> 800
01 2147483647
6 01BFA00_GS000_T 0 <-> 800
01 2147483647
GS003 180 FB_VRE_2POS 1 01BAC00_GS003_T 0 <-> 800
Disconnector Switch 01 2147483647
3 01BAC00_GS003_T 0 <-> 800
01 2147483647
179 FB_CB 4 01BAC00_GS003_Z 0 <-> 1000 UNIT DS GS003 (901-3)
T00 2147483647 FAULT DELAY
01BAC00_GS003_Z 200 UNIT DS GS003 (901-3)
T01 CLOSG PULSE VALUE
01BAC00_GS003_Z 200 UNIT DS GS003 (901-3)
T02 OPENG PULSE VALUE
01BAC00_GS003_Z 1000 UNIT DS GS003 (901-3) TLTE
T11 TEMPO VALUE
180 FB_VRE_2POS 5 01BAC00_GS003_T 0 <-> 800
01 2147483647
GS101 85 FB_CB 1 01MKC65_GS101_T 0 <-> 65535 2
Excitation Field Breaker P01
01MKC65_GS101_Z 0 <-> 1000 FIELD BRAKER GS101
T00 2147483647 FAULT DELAY
01MKC65_GS101_Z 500 FIELD BRAKER GS101
T01 CLOSG PULSE VALUE
01MKC65_GS101_Z 500 FIELD BRAKER GS101
T02 OPENG PULSE VALUE
01MKC65_GS101_Z 1000 FIELD BRAKER GS101 TLTE
T11 TEMPO VALUE
GS901 184 SEL_B 2 01CJA00_EA000_C 0 LCU1 & 3 S8000 NOT
GCB ON_E01 CONNECTED
185 FB_CB 21 01BAC00_GS901_Z 0 <-> 1000 UNIT GCB FAULT DELAY
T00 2147483647
XX PXXXXA4XXXX.219/A
DIAGRAM SHEET FUNCTIONAL BLOCK NAME STATE RANGE INIT LABEL
NAME NUMBER VALUE
01BAC00_GS901_Z 200 UNIT GCB CLOSG PULSE
T01 VALUE
01BAC00_GS901_Z 500 UNIT GCB OPENG PULSE
T02 VALUE
01BAC00_GS901_Z 12000 UNIT GCB TLTE TEMPO
T11 VALUE
INIT 66 SIM_STATUS_SE 3 01SIM_INIT_TURE 1 1st Sycle default value 1
Initial Pre Start Condition L 4 01SIM_INIT_TURE 1 1st Sycle default value 1
67 SIM_STATUS_SE 5 01SIM_INIT_TURE 1 1st Sycle default value 1
L 6 01SIM_INIT_TURE 1 1st Sycle default value 1
7 01SIM_INIT_TURE 1 1st Sycle default value 1
8 01SIM_INIT_TURE 1 1st Sycle default value 1
68 SIM_STATUS_SE 9 01SIM_INIT_TURE 1 1st Sycle default value 1
L 10 01SIM_INIT_TURE 1 1st Sycle default value 1
11 01SIM_INIT_TURE 1 1st Sycle default value 1
69 SIM_STATUS_SE 12 01SIM_INIT_TURE 1 1st Sycle default value 1
L 13 01SIM_INIT_TURE 1 1st Sycle default value 1
14 01SIM_INIT_TURE 1 1st Sycle default value 1
66 SIM_STATUS_SE 15 01SIM_INIT_TURE 1 1st Sycle default value 1
L 16 01SIM_INIT_TURE 1 1st Sycle default value 1
17 01SIM_INIT_TURE 1 1st Sycle default value 1
67 SIM_STATUS_SE 18 01SIM_INIT_TURE 1 1st Sycle default value 1
L 19 01SIM_INIT_TURE 1 1st Sycle default value 1
20 01SIM_INIT_TURE 1 1st Sycle default value 1
68 SIM_STATUS_SE 21 01SIM_INIT_TURE 1 1st Sycle default value 1
L 22 01SIM_INIT_TURE 1 1st Sycle default value 1
23 01SIM_INIT_TURE 1 1st Sycle default value 1
24 01SIM_INIT_TURE 1 1st Sycle default value 1
69 SIM_STATUS_SE 25 01SIM_INIT_TURE 1 1st Sycle default value 1
L 26 01SIM_INIT_TURE 1 1st Sycle default value 1
27 01SIM_INIT_TURE 1 1st Sycle default value 1
28 01SIM_INIT_TURE 1 1st Sycle default value 1
29 01SIM_INIT_TURE 1 1st Sycle default value 1
30 01SIM_INIT_TURE 1 1st Sycle default value 1
68 SIM_STATUS_SE 31 01SIM_INIT_TURE 1 1st Sycle default value 1
L 32 01SIM_INIT_TURE 1 1st Sycle default value 1
33 01SIM_INIT_TURE 1 1st Sycle default value 1
69 SIM_STATUS_SE 34 01SIM_INIT_TURE 1 1st Sycle default value 1
L
68 SIM_STATUS_SE 35 01SIM_INIT_TURE 1 1st Sycle default value 1
L 36 01SIM_INIT_TURE 1 1st Sycle default value 1
37 01SIM_INIT_TURE 1 1st Sycle default value 1
38 01SIM_INIT_TURE 1 1st Sycle default value 1
67 SIM_STATUS_SE 39 01SIM_INIT_TURE 1 1st Sycle default value 1
L
66 SIM_STATUS_SE 40 01SIM_INIT_TURE 1 1st Sycle default value 1
L 41 01SIM_INIT_TURE 1 1st Sycle default value 1
42 01SIM_INIT_TURE 1 1st Sycle default value 1
43 01SIM_INIT_TURE 1 1st Sycle default value 1
67 SIM_STATUS_SE 44 01SIM_INIT_TURE 1 1st Sycle default value 1
L 45 01SIM_INIT_TURE 1 1st Sycle default value 1
46 01SIM_INIT_TURE 1 1st Sycle default value 1
47 01SIM_INIT_TURE 1 1st Sycle default value 1
48 01SIM_INIT_TURE 1 1st Sycle default value 1
49 01SIM_INIT_TURE 1 1st Sycle default value 1
REG01 71 SEL 2 01SIM_REG01_RI21 0.18
Governor and MIV regulator 01SIM_REG01_RI22 0.2
70 MUL 3 01SIM_REG01_II02 0 <-> 220 6553 <-> 4545
32767
4 01SIM_REG01_II03 -32768 <-> 10000
32767
5 01SIM_REG01_II01 -32768 <-> 4000
32767
72 MUL 7 01SIM_REG01_II01 -32768 <-> 4000
32767
8 01SIM_REG01_II05 1600
9 01SIM_REG01_II04 0.000000 <- 0 <-> 2000 1380
> 20.00000
70 DIV 14 01SIM_REG01_RI07 10000
15 01SIM_REG01_RI08 10000
AO_SCALE 19 01SIM_REG01_R10 -3000
01SIM_REG01_R11 12000
72 DIV 21 01SIM_REG01_RI10 1380
22 01SIM_REG01_RI09 10000
23 01SIM_REG01_RI09 10000
AO_SCALE 26 01SIM_REG01_II15 3200
MUL 28 01SIM_REG01_RI31 100000
73 SIM_DEWATER 30 01SIM_REG01_RI11 1
XX PXXXXA4XXXX.220/A
DIAGRAM SHEET FUNCTIONAL BLOCK NAME STATE RANGE INIT LABEL
NAME NUMBER VALUE
SIM_ANA_M 35 01SIM_REG01_II06 224.0000 <- 6553 <-> 20000
> 300.0000 32767
70 SIM_GOVERNOR 42 01SIM_REG01_RI01 0.000000 <- 0.000000000 0.19000
> 100.0000 000 <->
1.000000000
000
01SIM_REG01_RI02 0.000000 <- 0.000000000 0.00500
> 100.0000 000 <->
1.000000000
000
72 SEL 44 01SIM_REG01_RI03 0.000000 <- 0.000000000 0.00500
> 100.0000 000 <->
1.000000000
000
01SIM_REG01_RI13 0.000000 <- 0.000000000 1
> 100.0000 000 <->
1.000000000
000
GE 46 01SIM_REG01_RI16 108
SIG 144 TON_R 4 01CJA00_EA021_SI 3
SIGNALS GRI01
162 TON_D 6 01CJA00_EA009_ZT 0 <-> 12000 SQ09: TS->SS SEQ
01 2147483647 OVERTIME SP
137 TON_D 6 01CJA00_EA010_ZT 0 <-> 12000 SQ10:SS->TS SEQ
01 2147483647 OVERTIME SP
146 TON_D 6 01CJA00_EA027_ZT 0 <-> 12000 SQ27:SR->SE SEQ
01 2147483647 OVERTIME SP
173 TON_R 7 01CJA00_EA001_ZT 5 step01 delay
001
83 TON_D 7 01CJA00_EA007_ZT 0 <-> 12000 SQ07:NMS->TS SEQ
01 2147483647 OVERTIME SP
157 TON_D 7 01CJA00_EA036_ZT 0 <-> 12000 SQ36:CH->GE SEQ
01 2147483647 OVERTIME SP
120 TON_D 7 01CJA00_EA073_ZT 0 <-> 12000 SQ73:SE->GE SEQ
01 2147483647 OVERTIME SP
155 TON_D 8 01CJA00_EA032_ZT 0 <-> 12000 SQ32:GE->SR SEQ
01 2147483647 OVERTIME SP
153 TON_D 8 01CJA00_EA034_ZT 0 <-> 12000 SQ34:GC->GE SEQ
01 2147483647 OVERTIME SP
160 TON_D 9 01CJA00_EA008_ZT 0 <-> 12000 SQ04: ES->TS SEQ
01 2147483647 OVERTIME SP
144 TON_D 9 01CJA00_EA021_ZT 0 <-> 12000 SQ21:TS->SR SEQ
01 2147483647 OVERTIME SP
148 TON_D 9 01CJA00_EA043_ZT 0 <-> 12000 SQ43: GE->GC SEQ
01 2147483647 OVERTIME SP
173 TON_D 10 01CJA00_EA001_ZT 0 <-> 12000 SQ01: GE/SR/CH/BS ->NMS
01 2147483647 SEQ OVER
175 TON_D 10 01CJA00_EA002_ZT 0 <-> 12000 SQ02: GC ->NMS SEQ
01 2147483647 OVERTIME SP
178 TON_D 12 01CJA00_EA051_ZT 0 <-> 12000 SQ51: TS->BS SEQ
01 2147483647 OVERTIME SP
151 TON_D 12 01CJA00_EA061_ZT 0 <-> 12000 SQ61: TS->CH SEQ
01 2147483647 OVERTIME SP
XX PXXXXA4XXXX.221/A
7 FBD ARGUMENTS
XX PXXXXA4XXXX.222/A
DIAGRAM SHEET FUNCTIONAL BLOCK ARGUMENTS
BLOCK NUMBER
SIM_DEVICE_2 3 OUT1:01SCC00_AA901_YL01 OUT2: POS1:01SCC00_AA901_XG01
POS POS2: MANU:0 POS_M:0
DELAY:10
SIM_DEVICE_2 4 OUT1:01MKA54_AA001_YL01 OUT2:01MKA54_AA001_YL02 POS1:01MKA54_AA001_XG01
POS POS2: MANU:0 POS_M:0
DELAY:10
64 SEL 5 G:01PAC00_AA001_XG01 IN1:0 IN2:80
RE:01SIM_ACT_REAL_0002
SEL 6 G:01MAU24_AP001_XG01 IN1:01SIM_ACT_INIT IN2:85
RE:01SIM_ACT_REAL_0009
63 MOVE_B 7 IN:01SIM_ACT_BOO_0004 RE:01SIM_ACT_BOO_0001
64 SEL 12 G:0 IN1:0 IN2:01SIM_REG01_RI06
RE:01SIM_ACT_REAL_0001
LAG_R 13 IN:01SIM_ACT_REAL_0002 TFILT:10 UL:100
LL:0 RE:01SIM_ACT_REAL_0003 ULA:
LLA: ERR:
LAG_R 14 IN:01SIM_ACT_REAL_0009 TFILT:10 UL:100
LL:0 RE:01SIM_ACT_REAL_0008 ULA:
LLA: ERR:
SIM_STATUS_M 15 VALUE:01MAU24_CP001_ZH04 INPUT:01MAU24_CL002_XH51
63 SIM_STATUS_M 16 VALUE:01SIM_ACT_BOO_0001 INPUT:01MKA54_CG565_XG01
SIM_DEVICE_2 17 OUT1:01MAU24_EU001_YL01 OUT2:01MAU24_EU001_YL02 POS1:01MAU24_AP001_XG01
POS POS2: MANU:0 POS_M:0
DELAY:10
SIM_DEVICE_2 18 OUT1:01SCC00_AA902_YL01 OUT2: POS1:01SCC00_AA902_XG01
POS POS2: MANU:0 POS_M:0
DELAY:10
SIM_DEVICE_2 19 OUT1:01MKA54_AA002_YL01 OUT2:01MKA54_AA002_YL02 POS1:01MKA54_AA002_XG01
POS POS2: MANU:0 POS_M:0
DELAY:10
64 AO_SCALE 20 IN:01SIM_ACT_REAL_0003 IN_MAX:100 IN_MIN:0
OUT_MAX:32767 OUT_MIN:6553 RE:01SIM_ACT_INT16_0002
ERR:
AO_SCALE 21 IN:01SIM_ACT_REAL_0008 IN_MAX:100 IN_MIN:0
OUT_MAX:32767 OUT_MIN:6553 RE:01SIM_ACT_INT16_0005
ERR:
SIM_DEVICE_2 22 OUT1:01SIM_ACT_BOO_0002 OUT2:01BAC00_GS901_YL02 POS1:01BAC00_GS901_XG01
POS POS2:01BAC00_GS901_XG02 MANU:0 POS_M:0
DELAY:01SIM_ACT_INT16_0001
MOVE_B 23 IN:01MAU24_CP001_ZH03 RE:01SIM_ACT_BOO_0003
SIM_ANA_M 24 VALUE:01SIM_ACT_INT16_0002 INPUT:01PAC00_CF972_XQ01
SIM_ANA_M 25 VALUE:01SIM_ACT_INT16_0002 INPUT:01PAC00_CF973_XQ01
SIM_ANA_M 26 VALUE:01SIM_ACT_INT16_0002 INPUT:01PAC00_CF975_XQ01
SIM_ANA_M 27 VALUE:01SIM_ACT_INT16_0002 INPUT:01PAC00_CF976_XQ01
SIM_ANA_M 28 VALUE:01SIM_ACT_INT16_0005 INPUT:01MAU24_CP001_XQ01
SIM_STATUS_M 30 VALUE:01SIM_ACT_BOO_0003 INPUT:01MAU24_CL001_XH03
SIM_STATUS_M 31 VALUE:01SIM_ACT_BOO_0003 INPUT:01MAU24_CP002_XH03
SIM_STATUS_M 32 VALUE:01SIM_ACT_BOO_0003 INPUT:01MAU24_CL002_XH03
65 SIM_STATUS_M 33 VALUE:01SIM_ACT_BOO_0003 INPUT:01MAU24_CP001_XH03
63 SIM_DEVICE_2 34 OUT1:01SIM_ACT_BOO_0006 OUT2:01MKC65_GS101_YL02 POS1:01MKC65_GS101_XG01
POS POS2:01MKC65_GS101_XG02 MANU:0 POS_M:0
DELAY:10
SIM_DEVICE_2 35 OUT1:01PAC00_GH001_YL01 OUT2:01PAC00_GH001_YL02 POS1:01PAC00_AA001_XG01
POS POS2: MANU:0 POS_M:0
DELAY:10
SIM_DEVICE_2 36 OUT1:01PAC00_GH001_YL01 OUT2:01PAC00_GH001_YL02 POS1:01MAU24_AA005_XG01
POS POS2:01MAU24_AA005_XG02 MANU:0 POS_M:0
DELAY:10
AU001 78 TON_R 1 IN:01MEA41_GH001_XM02 TP:01MEA41_AU001_RI01 REB:01MEA41_GH001_ZM01
Turbine Auxilary RET:
AU001 79 TON_R 1 IN:01MKA54_CL302_XH03 TP:01MKA54_AU001_TD01 REB:01MKA54_CL302_ZH13
Generator Auxilary RET:
TON_R 2 IN:01MKA54_CL312_XH03 TP:01MKA54_AU001_TD02 REB:01MKA54_CL312_ZH13
RET:
MOVE_B 3 IN:01MKA54_CG565_XG01 RE:01MKA54_CG565_ZG01
MOVE_B 4 IN:01MKA54_CG565_XG01 RE:01MKA54_CG565_ZG02
80 FB_VA2 11 I01:01MKA54_AU001_ZA01 I02:0 I03:01MKA54_AU001_ZC01
I05:01MKA54_CG565_XG01 I06:01MKA54_CG565_XG01_V
O01:01MKA54_AU001_BOO_0004 O02: I11:01MKA54_AU001_ZA02
I12:0 I13:01MKA54_AU001_ZC02 I15:01MKA54_CG565_XG01
I16:01MKA54_CG565_XG01_V O05:01MKA54_AU001_BOO_0005 O06:
I17:01MKA54_AU001_ZM00 I19:0 P01:01MKA54_AU001_ZT11
P02:01MKA54_AU001_ZT12 P03:01MKA54_AU001_ZT01 P04:01MKA54_AU001_ZT02
P06:01MKA54_AU001_ZT00 O07:01MKA54_AU001_ZU01 O08:01MKA54_AU001_ZM10
O09:01MKA54_AU001_ZM11 O10:01MKA54_AU001_ZM12 O11:
I04:01MKA54_AU001_ZJ01 I14:01MKA54_AU001_ZJ02 O12:01MKA54_AU001_ZU01_V
I18:01MKA54_AU001_ZM50 TYPE:2
RS 15 S:(connection) R1:01MKA54_AU001_BOO_0008 IV:0
Q1:01MKA54_AA001_ZA01 NQ1:01MKA54_AA001_ZA02
81 FB_VA2 16 I01:01MKA54_AA001_ZA01 I02:0 I03:01MKA54_AA001_ZC01
I05:01MKA54_AA001_XG01 I06:01MKA54_AA001_XG01_V O01:01MKA54_AA001_YL01
O02: I11:01MKA54_AA001_ZA02 I12:0
I13:01MKA54_AA001_ZC02 I15:01MKA54_AA001_XG01 I16:01MKA54_AA001_XG01_V
O05:01MKA54_AA001_YL02 O06: I17:01MKA54_AA001_ZM00
I19:0 P01:01MKA54_AA001_ZT11 P02:01MKA54_AA001_ZT12
P03:01MKA54_AA001_ZT01 P04:01MKA54_AA001_ZT02 P06:01MKA54_AA001_ZT00
O07:01MKA54_AA001_ZU01 O08:01MKA54_AA001_ZM10 O09:01MKA54_AA001_ZM11
O10:01MKA54_AA001_ZM12 O11: I04:01MKA54_AA001_ZJ01
I14:01MKA54_AA001_ZJ02 O12:01MKA54_AA001_ZU01_V I18:01MKA54_AA001_ZM50
TYPE:2
XX PXXXXA4XXXX.223/A
DIAGRAM SHEET FUNCTIONAL BLOCK ARGUMENTS
BLOCK NUMBER
80 MOVE_B 17 IN:01MKA54_AA001_ZA02 RE:01MKA54_AA002_ZA02
MOVE_B 18 IN:01MKA54_AA001_ZA01 RE:01MKA54_AA002_ZA01
81 FB_VA2 19 I01:01MKA54_AA002_ZA01 I02:0 I03:01MKA54_AA002_ZC01
I05:01MKA54_AA002_XG01 I06:01MKA54_AA002_XG01_V O01:01MKA54_AA002_YL01
O02: I11:01MKA54_AA002_ZA02 I12:0
I13:01MKA54_AA002_ZC02 I15:01MKA54_AA002_XG01 I16:01MKA54_AA002_XG01_V
O05:01MKA54_AA002_YL02 O06: I17:01MKA54_AA002_ZM00
I19:0 P01:01MKA54_AA002_ZT11 P02:01MKA54_AA002_ZT12
P03:01MKA54_AA002_ZT01 P04:01MKA54_AA002_ZT02 P06:01MKA54_AA002_ZT00
O07:01MKA54_AA002_ZU01 O08:01MKA54_AA002_ZM10 O09:01MKA54_AA002_ZM11
O10:01MKA54_AA002_ZM12 O11: I04:01MKA54_AA002_ZJ01
I14:01MKA54_AA002_ZJ02 O12:01MKA54_AA002_ZU01_V I18:01MKA54_AA002_ZM50
TYPE:2
80 RS 20 S:01MKA54_AU001_BOO_0004 R1:01MKA54_AU001_BOO_0005 IV:0
Q1:01MKA54_AU001_YL01 NQ1:
TON_R 21 IN:01MKA54_AA001_ZA01 TP:01MKA54_AU001_TD03
REB:01MKA54_AU001_BOO_0008 RET:
CON 147 TON_R 1 IN:01MEA41_CG015_XG01 TP:01CJA00_EA043_RI01 REB:01MEA41_CG015_ZG01
CONDITIONS RET:
117 MOVE 1 IN:01MEA41_CP505_XQ01 RE:01SCC00_EA001_CONREAL_0001
119 SEL 1 G:01CJA00_EU001_ZA01 IN1:01SCC00_EA002_CONRI03 IN2:01SCC00_EA002_CONRI01
RE:01SCC00_EA002_CONREAL_0001
145 SEL_B 1 G:01CJA00_EU001_ZG14 IN1:01MKC65_GS101_XG01 IN2:01BBA00_EM001_ZG72
RE:01MKC65_CS101_ZG01
117 THR_HL 2 IN:01SCC00_EA001_CONREAL_0001 H1_THR:01MEA41_CP505_ZW14
H2_THR:01MEA41_CP505_ZW13 L1_THR:01MEA41_CP505_ZW16 L2_THR:01MEA41_CP505_ZW17
HYS:01MEA41_CP505_ZW10 H1:01MEA41_CP505_ZH04 IN_VAL:
H1_V:01MEA41_CP505_ZH04_V H2:01MEA41_CP505_ZH03 H2_V:01MEA41_CP505_ZH03_V
L1:01MEA41_CP505_ZH06 L1_V:01MEA41_CP505_ZH06_V L2:01MEA41_CP505_ZH07
L2_V:01MEA41_CP505_ZH07_V IN_VUS:
154 TON_R 2 IN:(connection) TP:01CJA00_EA032_CONR01
REB:01CJA00_EA032_CONBOO_0001 RET:
145 SEL_B 2 G:01CJA00_EU001_ZG14 IN1:01BBA00_DE003_ZH07 IN2:1
RE:01BBA00_DE003_ZH17
119 TON_R 2 IN:01SCC00_AA902_XG01 TP:01SCC00_EA002_CON_T01 REB:01SCC00_AA902_ZG02
RET:
126 R_TRIG 3 IN:01CJA00_GH001_XL32 RE:01CJA00_EA100_CONBOO_0001
118 TON_R 4 IN:(connection) TP:01SCC00_EA001_CONRI01
REB:01SCC00_EA001_CONBOO_0001 RET:
119 TON_R 4 IN:(connection) TP:01SCC00_EA002_CONREAL_0001
REB:01SCC00_EA002_CONBOO_0001 RET:
TON_R 5 IN:01BBA00_DE001_ZH07 TP:01SCC00_EA002_CONRI02
REB:01SCC00_EA002_CONBOO_0002 RET:
118 TON_R 5 IN:01BBA00_DE001_ZH04 TP:01SCC00_EA001_CONRI02
REB:01SCC00_EA001_CONBOO_0002 RET:
TON_R 6 IN:01SCC00_AA901_XG01 TP:01SCC00_EA001_CONRI03 REB:01SCC00_AA901_ZG02
RET:
121 LE 9 IN1:01CJA00_EA073_CONINT16_0001 IN2:01CJA00_EA073_II01
RE:01BBA00_FE001_ZQ45
126 RS 11 S:(connection) R1:(connection) IV:0
Q1:01CJA00_EA100_ZG23 NQ1:
TP_R 14 IN:(connection) TP:1 REB:01CJA00_EA100_ZG51
RET:
140 RS 14 S:(connection) R1:01CJA00_EU001_ZG02 IV:0
Q1:01CJA00_EU001_ZM03 NQ1:
128 SEL_B 15 G:01CJA00_EA000_CON_E01 IN1:81CBC00_01CJA_GE01 IN2:1
RE:01CJA00_EU001_ZM21
SEL_B 16 G:01CJA00_EA000_CON_E01 IN1:81CBC00_01CJA_LC01 IN2:1
RE:01CJA00_EU001_ZM22
138 RS 16 S:(connection) R1:01CJA00_EU001_ZG02 IV:0
Q1:01CJA00_EU001_ZM02 NQ1:
128 SEL_B 17 G:01CJA00_EA000_CON_E01 IN1:81CBC00_01CJA_BS01 IN2:1
RE:01CJA00_EU001_ZM23
138 RS 18 S:(connection) R1:01CJA00_EU001_ZG02 IV:0
Q1:01CJA00_EU001_ZM11 NQ1:
128 SEL_B 18 G:01CJA00_EA000_CON_E02 IN1:50CBD01_EE101_XG01 IN2:1
RE:01CJA00_EE101_ZG01
SEL_B 19 G:01CJA00_EA000_CON_E02 IN1:50CBD01_EE101_ZH04 IN2:0
RE:01CJA00_EE101_ZM01
129 SEL_B 20 G:01CJA00_EA000_CON_E02 IN1:50CBD01_EE101_XG02 IN2:0
RE:01CJA00_EE101_ZG02
SEL_B 21 G:01CJA00_EA000_CON_E03 IN1:20SCC01_CP001_ZH06 IN2:1
RE:01CJA00_CP001_ZH06
126 RS 23 S:(connection) R1:(connection) IV:0
Q1:01CJA00_EA100_ZG22 NQ1:
139 RS 23 S:(connection) R1:(connection) IV:0
Q1:01CJA00_EU001_ZJ12 NQ1:
138 RS 26 S:01CJA00_EU001_ZA92 R1:01MEU11_FS001_XH14 IV:0
Q1:01CJA00_EU001_YL02 NQ1:
SEL_B 27 G:01CJA00_EA000_CONBI01 IN1:0 IN2:01CJA00_EU001_ZA92
RE:01CJA00_EA000_CONBI02
140 TOF_R 29 IN:(connection) TP:5 REB:01CJA00_EU001_YL01
RET:
131 RS 39 S:(connection) R1:(connection) IV:0
Q1:01CJA00_EU001_ZJ11 NQ1:
133 RS 52 S:(connection) R1:(connection) IV:0
Q1:01CJA00_EU001_ZJ31 NQ1:
134 RS 59 S:(connection) R1:(connection) IV:0
Q1:01CJA00_EU001_ZJ41 NQ1:
XX PXXXXA4XXXX.224/A
DIAGRAM SHEET FUNCTIONAL BLOCK ARGUMENTS
BLOCK NUMBER
132 RS 66 S:(connection) R1:(connection) IV:0
Q1:01CJA00_EU001_ZJ21 NQ1:
135 RS 71 S:(connection) R1:(connection) IV:0
Q1:01CJA00_EU001_ZJ61 NQ1:
RS 76 S:(connection) R1:(connection) IV:0
Q1:01CJA00_EU001_ZJ51 NQ1:
127 RS 83 S:(connection) R1:(connection) IV:0
Q1:01CJA00_EU001_ZJ71 NQ1:
DE001 164 FB_UV_BV 1 UV:01MEU11_CG012_XQ01_V FORC_V:0 VALID:01MEU11_CG001_ZQ01
UNIT ACTIVE POWER
CONTROL 163 MOVE_B 2 IN:01CJA00_DE001_ZQ01_V RE:01CJA00_CE001_ZQ01
RS 9 S:(connection) R1:(connection) IV:1
Q1:01CJA00_DE001_ZG32 NQ1:
RS 12 S:01CJA00_DE001_BOO_0012 R1:(connection) IV:0
Q1:01CJA00_DE001_ZG33 NQ1:
164 RS 16 S:(connection) R1:(connection) IV:1
Q1:01CJA00_DE001_ZG41 NQ1:01CJA00_DE001_ZG42
163 RS 20 S:01CJA00_DE001_BOO_0003 R1:(connection) IV:0
Q1:01CJA00_DE001_ZG31 NQ1:
R_TRIG 22 IN:(connection) RE:01CJA00_DE001_BOO_0014
165 FB_HMI_SP 23 IN:01CJA00_DE001_ZR01 ENB:01CJA00_DE001_ZG01
INITVAL:01CJA00_DE001_ZW01 FORC0:01CJA00_DE001_ZA01 OUT:01CJA00_DE001_ZP02
SCALE:01CJA00_DE001_ZV01 MEAS:01CJA00_DE001_ZQ01
FORC_ST:01CJA00_DE001_ZM01 MINVAL:01CJA00_DE001_ZU01
INITCMD:01CJA00_DE001_ZA11 FORCMIN:01CJA00_DE001_ZA12
LIMIT 24 LO:01CJA00_DE001_ZU01 IN:01CJA00_DE001_ZP02 HI:01CJA00_DE001_HI
RE:01CJA00_DE001_ZP01 HL:01CJA00_DE001_ZH06 LL:
166 SUB 25 IN1:01CJA00_DE001_ZP01 IN2:01CJA00_DE001_ZQ01
RE:01CJA00_DE001_INT16_0001
167 TP_R 26 IN:01CJA00_DE001_ZL01 TP:01CJA00_DE001_ZT02
REB:01CJA00_DE001_BOO_0026 RET:
TP_R 27 IN:01CJA00_DE001_ZL02 TP:01CJA00_DE001_ZT02
REB:01CJA00_DE001_BOO_0015 RET:
GT 28 IN1:01CJA00_DE001_ZQ01 IN2:01CJA00_DE001_ZW01 RE:01CJA00_DE001_BOO_0016
XX PXXXXA4XXXX.225/A
DIAGRAM SHEET FUNCTIONAL BLOCK ARGUMENTS
BLOCK NUMBER
171 FB_PULS_REG 26 SP:01CJA00_DE002_ZP01 MEAS:01CJA00_DE002_ZQ01
ENB:01CJA00_DE002_BOO_0003 DEAD:01CJA00_DE002_ZZ01 T0:01CJA00_DE002_ZT01
INC:01CJA00_DE002_BOO_0004 DEC:01CJA00_DE002_BOO_0006 RATE:01CJA00_DE002_ZX01
MAX_DELTA:01CJA00_DE002_DLT
170 AO_SCALE 27 IN:01CJA00_DE002_ZP01 IN_MAX:01CJA00_DE002_1_ZW29
IN_MIN:01CJA00_DE002_1_ZW21 OUT_MAX:01CJA00_DE002_1_ZW39
OUT_MIN:01CJA00_DE002_1_ZW31 RE:01MKC65_FE001_YQ01
ERR:
171 GE 28 IN1:01CJA00_DE002_INT16_0007 IN2:01CJA00_DE002_TH01
RE:01CJA00_DE002_BOO_0007
169 RS 35 S:(connection) R1:(connection) IV:0
Q1:01CJA00_DE002_ZG41 NQ1:01CJA00_DE002_ZG42
171 SEL 36 G:01CJA00_DE002_BOO_0007 IN1:01CJA00_DE002_TN1 IN2:01CJA00_DE002_TN2
RE:01CJA00_DE002_REAL_0002
SEL 37 G:01CJA00_DE002_BOO_0007 IN1:01CJA00_DE002_TP1 IN2:01CJA00_DE002_TP2
RE:01CJA00_DE002_REAL_0001
OSC_B 38 IN:01CJA00_DE002_BOO_0004 TP:01CJA00_DE002_REAL_0001
TN:01CJA00_DE002_REAL_0002 RE:01CJA00_DE002_INC
OSC_B 39 IN:01CJA00_DE002_BOO_0006 TP:01CJA00_DE002_REAL_0001
TN:01CJA00_DE002_REAL_0002 RE:01CJA00_DE002_DEC
168 RS 41 S:(connection) R1:(connection) IV:0
Q1:01CJA00_DE002_ZG31 NQ1:
MOVE_B 42 IN:01CJA00_DE002_ZG31 RE:01MKC65_EM001_YL01
169 MOVE_B 43 IN:01CJA00_DE002_ZG41 RE:01MKC65_EM001_YL41
MOVE_B 44 IN:01CJA00_DE002_ZG42 RE:01MKC65_EM001_YL42
DE003 189 FB_HMI_SP 3 IN:01CJA00_DE003_ZR01 ENB:01CJA00_DE003_ZG01
UNIT VOLTAGE CONTROL INITVAL:01CJA00_DE003_ZW01 FORC0:01CJA00_DE003_ZA01 OUT:01CJA00_DE003_ZP02
SCALE:01CJA00_DE003_ZV01 MEAS:01CJA00_DE003_ZQ01
FORC_ST:01CJA00_DE003_ZM01 MINVAL:01CJA00_DE003_ZU01
INITCMD:01CJA00_DE003_BI01 FORCMIN:0
LIMIT 4 LO:01CJA00_DE003_ZU01 IN:01CJA00_DE003_ZP02 HI:01CJA00_DE003_HI
RE:01CJA00_DE003_ZP01 HL:01CJA00_DE003_ZH06 LL:
190 SUB 5 IN1:01CJA00_DE003_ZP01 IN2:01CJA00_DE003_ZQ01
RE:01CJA00_DE003_INT16_0002
191 TP_R 6 IN:01CJA00_DE002_ZL01 TP:01CJA00_DE003_R01
REB:01CJA00_DE003_BOO_0002 RET:
LT 7 IN1:01CJA00_DE002_ZQ01 IN2:01CJA00_DE003_I01 RE:01CJA00_DE003_BOO_0005
XX PXXXXA4XXXX.226/A
DIAGRAM SHEET FUNCTIONAL BLOCK ARGUMENTS
BLOCK NUMBER
SEL 13 G:01CJA00_DG001_BOO_0002 IN1:01CJA00_DG001_TP1 IN2:01CJA00_DG001_TP2
RE:01CJA00_DG001_REAL_0001
OSC_B 14 IN:01CJA00_DG001_BOO_0003 TP:01CJA00_DG001_REAL_0001
TN:01CJA00_DG001_REAL_0002 RE:01CJA00_DG001_INC
OSC_B 15 IN:01CJA00_DG001_BOO_0004 TP:01CJA00_DG001_REAL_0001
TN:01CJA00_DG001_REAL_0002 RE:01CJA00_DG001_DEC
EB000 182 CUR_EPL_PRE 1 EQPT_NUM:1 LINK_PRES:01CJA00_EN001_ZM51
L01 WATCHDOG S LINK1_PRES:01CJA00_EB000_BOO_0001
LINK2_PRES:01CJA00_EB000_BOO_0002
CUR_EPL_PRE 2 EQPT_NUM:2 LINK_PRES:01CJA00_EN002_ZM51
S LINK1_PRES:01CJA00_EB000_BOO_0003
LINK2_PRES:01CJA00_EB000_BOO_0005
CUR_EPL_PRE 3 EQPT_NUM:3 LINK_PRES:01CJA00_EN003_ZM51
S LINK1_PRES:01CJA00_EB000_BOO_0010
LINK2_PRES:01CJA00_EB000_BOO_0011
181 FB_UV_BV 4 UV:01CJA00_EU115_PS FORC_V:0 VALID:01CJA00_EU115_ZM01
XX PXXXXA4XXXX.227/A
DIAGRAM SHEET FUNCTIONAL BLOCK ARGUMENTS
BLOCK NUMBER
EU001 90 TWB 12 IN:01MKC65_EU001_UINT16_0001 RE1:
Excitation System RE2:01MKC65_EA123_XD82 RE3:01MKC65_EA122_XD81 RE4:
RE5: RE6: RE7:
RE8: RE9: RE10:
RE11: RE12: RE13:
RE14: RE15: RE16:
TWB 13 IN:01MKC65_EU001_UINT16_0008 RE1:01MKC65_DE050_XD40
RE2:01MKC65_DE050_XD41 RE3:01MKC65_CX020_XD40 RE4:01MKC65_CX020_XD41
RE5:01MKC65_EZ010_XD46 RE6:01MKC65_EZ010_XD47 RE7:01MKC65_EZ010_XD43
RE8:01MKC65_EZ010_XD44 RE9:01MKC65_DE110_XD40 RE10:01MKC65_DE110_XD41
RE11:01MKC65_DE110_XD42 RE12:01MKC65_DE110_XD43 RE13:01MKC65_EG809_XD46
RE14:01MKC65_EG810_XD46 RE15:01MKC65_EG811_XD46 RE16:01MKC65_EG803_XD46
TWB 14 IN:01MKC65_EU001_UINT16_0017 RE1:01MKC65_GW040_XG46
RE2:01MKC65_DE010_XG42 RE3:01MKC65_DE010_XG43 RE4:01MKC65_GX000_XG40
RE5:01MKC65_GX000_XG41 RE6:01MKC65_GW030_XG41 RE7:01MKC65_GW030_XG42
RE8:01MKC65_GW030_XD43 RE9:01MKC65_CE220_XD41 RE10:01MKC65_CE110_XD46
RE11:01MKC65_EZ020_XD44 RE12:01MKC65_DT010_XD46 RE13:01MKC65_DU060_XD46
RE14:01MKC65_EG101_XD46 RE15: RE16:01MKC65_EZ020_XG47
EU001 98 TON_R 14 IN:(connection) TP:01CJA00_DE003_TD11
Speed Governor System REB:01MEU11_EU001_BOO_0006 RET:
XX PXXXXA4XXXX.228/A
DIAGRAM SHEET FUNCTIONAL BLOCK ARGUMENTS
BLOCK NUMBER
TWB 37 IN:01MKC65_EU001_UINT16_0018 RE1:01MKC65_DU020_XD43
RE2:01MKC65_DU020_XD41 RE3:01MKC65_DU020_XD42 RE4:01MKC65_DU020_XD44
RE5:01MKC65_DU020_XD45 RE6:01MKC65_CT061_XG46 RE7:01MKC65_CT063_XG46
RE8:01MKC65_EZ020_XD46 RE9:01MKC65_EG015_XG46 RE10:01MKC65_EZ020_XD40
RE11:01MKC65_GW030_XG44 RE12:01MKC65_EG812_XD46 RE13:01MKC65_DE010_XG45
RE14:01MKC65_DE090_XB11 RE15:01MKC65_EG010_XD46 RE16:01MKC65_EG013_XG41
91 TWB 38 IN:01MKC65_EU001_UINT16_0024 RE1:01MKC65_DU020_XD54
RE2:01MKC65_DU020_XD55 RE3:01MKC65_CX025_XD46 RE4:01MKC65_EZ020_XD45
RE5:01MKC65_CX025_XD41 RE6:01MKC65_CX025_XD42 RE7:01MKC65_CX025_XD43
RE8:01MKC65_CX025_XD44 RE9:01MKC65_GX000_XG42 RE10:01MKC65_DU020_XD61
RE11:01MKC65_EZ020_XD50 RE12:01MKC65_DU020_XD56 RE13:01MKC65_DU070_XD82
RE14:01MKC65_DU070_XD83 RE15:01MKC65_DU070_XD84 RE16:01MKC65_DU070_XD85
EU001 96 RS 38 S:01MEU11_EM001_YL07 R1:01MEU11_EM001_YL08 IV:0
Speed Governor System Q1:01MEU11_EU001_ZG21 NQ1:
EU001 91 THR_HI 39 IN:01MKC65_CE002_ZQ01 THR:01MKC65_CE002_ZW17 HYS:01MKC65_CE002_ZW10
Excitation System RO:01MKC65_EU001_BOO_0001 ERR:01MKC65_CE002_ZH07_V IN_VAL:
IN_VUS:
EU001 96 MOVE_B 39 IN:01MEU11_EM001_YL08 RE:01MEU11_EU001_TL06
Speed Governor System RS 40 S:01MEU11_EM001_YL03 R1:01MEU11_EM001_YL13 IV:0
Q1:01MEU11_EU001_BOO_0002 NQ1:
EU001 91 TON_R 41 IN:01MKC65_EU001_BOO_0001 TP:01MKC65_EU001_R02 REB:01MKC65_CE002_ZH07
Excitation System RET:
EU001 96 MOVE_B 41 IN:01MEU11_EM001_YL07 RE:01MEU11_EU001_TL05
Speed Governor System
EU001 89 MOVE_B 43 IN:01BBA00_EM001_ZG72 RE:01MKC65_EM001_YL72
Excitation System 87 TP_R 46 IN:(connection) TP:01MKC65_EU001_RI01 REB:01MKC65_EM001_YL31
RET:
EU001 97 RS 46 S:(connection) R1:(connection) IV:0
Speed Governor System Q1:01MEU11_EU001_ZG41 NQ1:
94 MOVE_B 47 IN:01MEU11_EU001_ZG22 RE:01MEU11_EM001_YL09
98 MOVE_B 48 IN:01CJA00_EU001_ZM13 RE:01CJA00_EU001_YL03
MOVE 50 IN:01MEU11_EU001_ZQ01 RE:01MEU11_FE001_YQ02
96 MOVE_B 51 IN:01MEU11_EU001_BOO_0002 RE:01MEU11_EU001_TL04
EU001 88 TP_R 52 IN:(connection) TP:01MKC65_EU001_RI01 REB:01MKC65_EM001_YL61
Excitation System RET:
EU001 95 MOVE_B 52 IN:01MEU11_EU001_ZM03 RE:01MAU24_AA004_YL01
Speed Governor System
EU001 88 RS 53 S:(connection) R1:(connection) IV:0
Excitation System Q1:01MKC65_EU001_ZG51 NQ1:
EU001 97 MOVE_B 53 IN:01MEU11_EU001_ZG41 RE:01MEU11_EM001_YL04
Speed Governor System MOVE_B 54 IN:01MEU11_EU001_ZG41 RE:01MEU11_EU001_TL02
EU001 88 TP_R 54 IN:(connection) TP:01MKC65_EU001_RI01 REB:01MKC65_EM001_YL62
Excitation System RET:
92 SEL 55 G:01MKC65_EU001_ZM02 IN1:01MKC65_EU001_S06 IN2:01MKC65_EU001_P06
RE:01MKC65_EU001_RQ06
SEL 56 G:01MKC65_EU001_ZM02 IN1:01MKC65_EU001_S10 IN2:01MKC65_EU001_P10
RE:01MKC65_EU001_RQ10
EU001 98 MOVE_B 56 IN:0 RE:01MEU11_EU001_TL10
Speed Governor System MOVE 57 IN:100 RE:01MEU11_EU001_TQ03
EU001 92 SEL 57 G:01MKC65_EU001_ZM02 IN1:01MKC65_EU001_S14 IN2:01MKC65_EU001_P14
Excitation System RE:01MKC65_EU001_RQ14
EU001 98 MOVE 58 IN:0 RE:01MEU11_EU001_TQ04
Speed Governor System
EU001 92 SEL 58 G:01MKC65_EU001_ZM02 IN1:01MKC65_EU001_S18 IN2:01MKC65_EU001_P18
Excitation System RE:01MKC65_EU001_RQ18
SEL 59 G:01MKC65_EU001_ZM02 IN1:01MKC65_EU001_S22 IN2:01MKC65_EU001_P22
RE:01MKC65_EU001_RQ22
EU001 98 MOVE_B 59 IN:0 RE:01MEU11_EU001_TL07
Speed Governor System
EU001 92 SEL 60 G:01MKC65_EU001_ZM02 IN1:01MKC65_EU001_S26 IN2:01MKC65_EU001_P26
Excitation System RE:01MKC65_EU001_RQ26
SEL 61 G:01MKC65_EU001_ZM02 IN1:01MKC65_EU001_S30 IN2:01MKC65_EU001_P30
RE:01MKC65_EU001_RQ30
87 TP_R 65 IN:(connection) TP:01MKC65_EU001_RI01 REB:01MKC65_EM001_YL32
RET:
90 SEL 66 G:01MKC65_EU001_ZM02 IN1:01MKC65_STA_WD13 IN2:01MKC65_STA_WD03
RE:01MKC65_EU001_UINT16_0006
SEL 67 G:01MKC65_EU001_ZM02 IN1:01MKC65_ALM_WD13 IN2:01MKC65_ALM_WD03
RE:01MKC65_EU001_UINT16_0012
SEL 68 G:01MKC65_EU001_ZM02 IN1:01MKC65_ALM_WD16 IN2:01MKC65_ALM_WD06
RE:01MKC65_EU001_UINT16_0019
91 SEL 69 G:01MKC65_EU001_ZM02 IN1:01MKC65_ALM_WD19 IN2:01MKC65_ALM_WD09
RE:01MKC65_EU001_UINT16_0025
90 TWB 70 IN:01MKC65_EU001_UINT16_0006 RE1:01MKC65_CX030_XD82
RE2:01MKC65_EA116_XD81 RE3:01MKC65_EA116_XD82 RE4:01MKC65_GX010_XD01
RE5:01MKC65_GX020_XD01 RE6:01MKC65_GS100_XB01 RE7:
RE8: RE9:01MKC65_EG802_XD47 RE10:01MKC65_EA102_XD81
RE11:01MKC65_EA102_XD82 RE12:01MKC65_DU030_XD01 RE13:01MKC65_DU030_XD02
RE14:01MKC65_CX010_XD44 RE15:01MKC65_CX010_XD43 RE16:01MKC65_CX025_XD01
TWB 71 IN:01MKC65_EU001_UINT16_0012 RE1:01MKC65_EG013_XD46
RE2:01MKC65_EZ020_XD42 RE3:01MKC65_GS030_XG46 RE4:01MKC65_DE090_XD47
RE5:01MKC65_DE010_XD41 RE6:01MKC65_CE220_XD40 RE7:01MKC65_DE000_XD46
RE8:01MKC65_DE000_XD40 RE9:01MKC65_DU060_XF46 RE10:01MKC65_EA010_XD46
RE11:01MKC65_EZ020_XD47 RE12:01MKC65_GX000_XD57 RE13:
RE14:01MKC65_EG010_XG461 RE15: RE16:01MKC65_CX015_XD46
XX PXXXXA4XXXX.229/A
DIAGRAM SHEET FUNCTIONAL BLOCK ARGUMENTS
BLOCK NUMBER
TWB 72 IN:01MKC65_EU001_UINT16_0019 RE1:01MKC65_EG805_XU46
RE2:01MKC65_EG010_XG46 RE3:01MKC65_DU040_XD40 RE4:01MKC65_DE010_XD42
RE5:01MKC65_GX000_XD51 RE6:01MKC65_GX000_XD52 RE7:01MKC65_GX000_XD53
RE8:01MKC65_GX000_XD54 RE9:01MKC65_GX000_XD55 RE10:01MKC65_GX000_XD56
RE11:01MKC65_GX010_XG41 RE12:01MKC65_GX020_XG41 RE13:01MKC65_GX030_XG41
RE14:01MKC65_GX040_XG41 RE15:01MKC65_GX050_XG41 RE16:01MKC65_GX060_XG41
91 TWB 73 IN:01MKC65_EU001_UINT16_0025 RE1:01MKC65_DU070_XD86
RE2:01MKC65_DU070_XD87 RE3:01MKC65_DU070_XD88 RE4:01MKC65_DU070_XD89
RE5:01MKC65_GX000_XG60 RE6:01MKC65_EG012_XD46 RE7:01MKC65_EG814_XD46
RE8:01MKC65_CX060_XD40 RE9: RE10:01MKC65_DU060_XD48
RE11: RE12: RE13:
RE14: RE15: RE16:
92 SEL 74 G:01MKC65_EU001_ZM02 IN1:01MKC65_EU001_S07 IN2:01MKC65_EU001_P07
RE:01MKC65_EU001_RQ07
SEL 75 G:01MKC65_EU001_ZM02 IN1:01MKC65_EU001_S11 IN2:01MKC65_EU001_P11
RE:01MKC65_EU001_RQ11
SEL 76 G:01MKC65_EU001_ZM02 IN1:01MKC65_EU001_S15 IN2:01MKC65_EU001_P15
RE:01MKC65_EU001_RQ15
SEL 77 G:01MKC65_EU001_ZM02 IN1:01MKC65_EU001_S19 IN2:01MKC65_EU001_P19
RE:01MKC65_EU001_RQ19
SEL 78 G:01MKC65_EU001_ZM02 IN1:01MKC65_EU001_S23 IN2:01MKC65_EU001_P23
RE:01MKC65_EU001_RQ23
SEL 79 G:01MKC65_EU001_ZM02 IN1:01MKC65_EU001_S27 IN2:01MKC65_EU001_P27
RE:01MKC65_EU001_RQ27
SEL 80 G:01MKC65_EU001_ZM02 IN1:01MKC65_EU001_S31 IN2:01MKC65_EU001_P31
RE:01MKC65_EU001_RQ31
EU014 103 FB_VRE_2POS 5 PS1:01MAU24_AP001_XG01 PS1_V:01MAU24_AP001_XG01_V
Governor Oil Station PS2:01MAU24_EU014_BOO_0002 PS2_V:01MAU24_AP001_XG01_V FLT:01MAU24_EU014_BI01
TLTE:01MAU24_EU014_D01 TYPE:01MAU24_EU014_W01 SIG:01MAU24_AP001_ZU01
SIG_V:01MAU24_AP001_ZU01_V
FB_VRE_2POS 6 PS1:01MAU24_AP003_XG01 PS1_V:01MAU24_AP003_XM51_V
PS2:01MAU24_EU014_BOO_0008 PS2_V:01MAU24_AP003_XM51_V FLT:01MAU24_EU014_BI03
TLTE:01MAU24_EU014_D03 TYPE:01MAU24_EU014_W01 SIG:01MAU24_AP003_ZU01
SIG_V:01MAU24_AP003_ZU01_V
101 THR_HL 7 IN:01MAU24_CP001_XQ01 H1_THR:01MAU24_CP001_ZW16 H2_THR:01MAU24_CP001_ZW17
L1_THR: L2_THR:01MAU24_CP001_ZW13 HYS:01MAU24_CP001_ZW10
H1:01MAU24_CP001_ZH06 IN_VAL: H1_V:01MAU24_CP001_ZH06_V
H2:01MAU24_CP001_ZH07 H2_V:01MAU24_CP001_ZH07_V L1:
L1_V:01MAU24_CP001_ZH04_V L2:01MAU24_CP001_ZH03 L2_V:01MAU24_CP001_ZH03_V
IN_VUS:01MAU24_CP001_XQ01_V
THR_HL 8 IN:01MAU24_CP001_XQ01 H1_THR:01MAU24_CP001_ZW14 H2_THR:
L1_THR: L2_THR: HYS:01MAU24_CP001_ZW10
H1:01MAU24_CP001_ZH04 IN_VAL: H1_V:
H2: H2_V: L1:
L1_V: L2: L2_V:
IN_VUS:01MAU24_CP001_XQ01_V
102 TON_R 14 IN:(connection) TP:01MAU24_EU014_RI02
REB:01MAU24_EU014_BOO_0003 RET:
100 TP_R 15 IN:01MAU24_AA002_ZA01 TP:01MAU24_EU014_RI01
REB:01MAU24_EU014_BOO_0004 RET:
TP_R 16 IN:01MAU24_AA002_ZA02 TP:01MAU24_EU014_RI01
REB:01MAU24_EU014_BOO_0001 RET:
TP_R 17 IN:01MAU24_EA001_ZA01 TP:01MAU24_EU014_RI01 REB:01MAU24_EU001_YL01
RET:
TP_R 18 IN:01MAU24_EA001_ZA02 TP:01MAU24_EU014_RI01 REB:01MAU24_EU001_YL02
RET:
102 RS 22 S:(connection) R1:01MAU24_EU014_BOO_0003 IV:0
Q1:01MAU24_EA001_ZG01 NQ1:01MAU24_EA001_ZG02
100 RS 23 S:01MAU24_EU014_BOO_0004 R1:01MAU24_EU014_BOO_0001 IV:0
Q1:01MAU24_AA002_ZG01 NQ1:01MAU24_EU014_BOO_0007
MOVE_B 26 IN:01MAU24_EU014_BOO_0007 RE:01MAU24_AA002_YL01
103 FB_VRE_2POS 27 PS1:01MAU24_AP002_XG01 PS1_V:01MAU24_AP002_XG01_V
PS2:01MAU24_EU014_BOO_0005 PS2_V:01MAU24_AP002_XG01_V FLT:01MAU24_EU014_BI02
TLTE:01MAU24_EU014_D02 TYPE:01MAU24_EU014_W01 SIG:01MAU24_AP002_ZU01
SIG_V:01MAU24_AP002_ZU01_V
FB_VRE_2POS 28 PS1:01MAU24_AA005_XG01 PS1_V:01MAU24_AA005_XG01_V PS2:01MAU24_AA005_XG02
PS2_V:01MAU24_AA005_XG02_V FLT:01MAU24_EU014_BI04 TLTE:01MAU24_EU014_D04
TYPE:01MAU24_EU014_W01 SIG:01MAU24_AA005_ZU01
SIG_V:01MAU24_AA005_ZU01_V
EU101 74 CUR_MODBUS_ 1 NET_NUM:0 EQPT_NUM:1
MODBUS PRES LINK1_PRES:01CJA00_GK302_ZM11
COMMUNICATION LINK2_PRES:01CJA00_GK302_ZM21
LINK1_EXCH:01CJA00_GK302_ZM12
LINK2_EXCH:01CJA00_GK302_ZM22
CUR_MODBUS_ 2 NET_NUM:0 EQPT_NUM:6
PRES LINK1_PRES:01CJA00_FT001_ZM11
LINK2_PRES:01CJA00_FT001_ZM21
LINK1_EXCH:01CJA00_FT001_ZM12
LINK2_EXCH:01CJA00_FT001_ZM22
77 CUR_MODBUS_ 3 NET_NUM:0 EQPT_NUM:8
PRES LINK1_PRES:01MEU11_EU001_ZM11
LINK2_PRES:01MEU11_EU001_ZM21
LINK1_EXCH:01MEU11_EU001_ZM12
LINK2_EXCH:01MEU11_EU001_ZM22
CUR_MODBUS_ 4 NET_NUM:0 EQPT_NUM:7
PRES LINK1_PRES:01CMA00_EU001_ZM11
LINK2_PRES:01CMA00_EU001_ZM12
LINK1_EXCH:01CMA00_EU001_ZM21
LINK2_EXCH:01CMA00_EU001_ZM22
75 CUR_MODBUS_ 5 NET_NUM:0 EQPT_NUM:2
PRES LINK1_PRES:01CJA00_FE001_ZM11
LINK2_PRES:01CJA00_FE001_ZM21
LINK1_EXCH:01CJA00_FE001_ZM12
LINK2_EXCH:01CJA00_FE001_ZM22
XX PXXXXA4XXXX.230/A
DIAGRAM SHEET FUNCTIONAL BLOCK ARGUMENTS
BLOCK NUMBER
76 CUR_MODBUS_ 6 NET_NUM:0 EQPT_NUM:3
PRES LINK1_PRES:01CJA00_FE002_ZM11
LINK2_PRES:01CJA00_FE002_ZM21
LINK1_EXCH:01CJA00_FE002_ZM12
LINK2_EXCH:01CJA00_FE002_ZM22
CUR_MODBUS_ 7 NET_NUM:0 EQPT_NUM:5
PRES LINK1_PRES:01MKC65_EU002_ZM11
LINK2_PRES:01MKC65_EU002_ZM21
LINK1_EXCH:01MKC65_EU002_ZM12
LINK2_EXCH:01MKC65_EU002_ZM22
CUR_MODBUS_ 8 NET_NUM:0 EQPT_NUM:4
PRES LINK1_PRES:01MKC65_EU001_ZM11
LINK2_PRES:01MKC65_EU001_ZM21
LINK1_EXCH:01MKC65_EU001_ZM12
LINK2_EXCH:01MKC65_EU001_ZM22
FE001 106 FB_UV_BV 1 UV:01BBA00_CE001_XQ02_V FORC_V:0 VALID:01CJA00_CE001_ZQ02
Electrical Measurement
105 AO_SCALE 2 IN:01BBA00_FE001_RQ43 IN_MAX:01BBA00_FE001_3_ZW01
IN_MIN:01BBA00_FE001_3_ZW09 OUT_MAX:01BBA00_FE001_3_ZW19
OUT_MIN:01BBA00_FE001_3_ZW11 RE:01BBA00_FE001_3_ZQ01
ERR:
SEL 3 G:01CJA00_FE001_ZM02 IN1:01CJA00_DE002_ZQ01 IN2:01BBA00_FE001_3_ZQ01
RE:01CJA00_DE002_ZQ01
104 AI_SCALE 5 IN:01BBA00_CE001_XQ01 IN_VAL:
IN_MAX:01BBA00_FE001_1_ZW09 IN_MIN:01BBA00_FE001_1_ZW01
OUT_MAX:01BBA00_FE001_1_ZW19
OUT_MIN:01BBA00_FE001_1_ZW11 RI:01BBA00_FE001_1_ZQ01
ERR: IN_VUS: RR:
AO_SCALE 6 IN:01BBA00_FE001_RQ42 IN_MAX:01BBA00_FE001_2_ZW09
IN_MIN:01BBA00_FE001_2_ZW01 OUT_MAX:01BBA00_FE001_2_ZW19
OUT_MIN:01BBA00_FE001_2_ZW11 RE:01BBA00_FE001_2_ZQ01
ERR:
SEL 7 G:01CJA00_FE001_ZM02 IN1:01BBA00_FE001_INT16_0006
IN2:01BBA00_FE001_2_ZQ01 RE:01CJA00_DE001_ZQ01
106 AI_SCALE 9 IN:01BBA00_CE001_XQ02 IN_VAL:
IN_MAX:01BBA00_FE001_5_ZW09 IN_MIN:01BBA00_FE001_5_ZW01
OUT_MAX:01BBA00_FE001_5_ZW19
OUT_MIN:01BBA00_FE001_5_ZW11 RI:01BBA00_FE001_5_ZQ01
ERR: IN_VUS:01BBA00_CE001_XQ02_V RR:
104 SEL 10 G:01CJA00_CE001_ZQ01 IN1:01BBA00_FE001_1_ZQ01 IN2:01CJA00_DE001_ZQ01
RE:01BBA00_FE001_INT16_0006
THR_HL 12 IN:01BBA00_FE001_INT16_0005 H1_THR:01BBA00_DE001_ZW16 H2_THR:01BBA00_DE001_ZW17
L1_THR:01BBA00_DE001_ZW14 L2_THR: HYS:01BBA00_DE001_ZW10
H1:01BBA00_DE001_ZH06 IN_VAL:01CJA00_DE001_ZQ01_V H1_V:01BBA00_DE001_ZH06_V
H2:01BBA00_DE001_ZH07 H2_V:01BBA00_DE001_ZH07_V L1:01BBA00_DE001_ZH04
L1_V:01BBA00_DE001_ZH04_V L2: L2_V:
IN_VUS:
THR_HI 13 IN:01CJA00_DE001_ZQ01 THR:01BBA00_DE001_ZW13 HYS:01BBA00_DE001_ZW10
RO:01BBA00_DE001_ZH03 ERR: IN_VAL:
IN_VUS:
106 SEL 14 G:01CJA00_CE001_ZQ02 IN1:01BBA00_FE001_5_ZQ01 IN2:01CJA00_DE003_ZQ01
RE:01BBA00_FE001_INT16_0001
AO_SCALE 15 IN:01BBA00_FE001_RQ03 IN_MAX:01BBA00_FE001_6_ZW09
IN_MIN:01BBA00_FE001_6_ZW01 OUT_MAX:01BBA00_FE001_6_ZW19
OUT_MIN:01BBA00_FE001_6_ZW11 RE:01BBA00_FE001_6_ZQ01
ERR:
SEL 17 G:01CJA00_FE001_ZM02 IN1:01BBA00_FE001_INT16_0001
IN2:01BBA00_FE001_6_ZQ01 RE:01CJA00_DE003_ZQ01
THR_HL 18 IN:01CJA00_DE003_ZQ01 H1_THR: H2_THR:01BBA00_DE003_ZW17
L1_THR: L2_THR:01BBA00_DE003_ZW14 HYS:01BBA00_FE001_II01
H1: IN_VAL: H1_V:
H2:01BBA00_DE003_ZH07 H2_V:01BBA00_DE003_ZH07_V L1:
L1_V: L2:01BBA00_DE003_ZH04 L2_V:01BBA00_DE003_ZH04_V
IN_VUS:
105 THR_LO 20 IN:01BBA00_FE001_INT16_0002 THR:01BBA00_DE003_ZW13 HYS:01BBA00_DE003_ZW10
RO:01BBA00_DE003_ZH03 IN_VAL:0 IN_VUS:0
ERR:01BBA00_DE003_ZH03_V
GS000 110 FB_VRE_2POS 2 PS1:01BFA00_GS100_XG01 PS1_V:01BFA00_GS100_XG01_V PS2:01BFA00_GS100_XG02
Unit 400V Switchboard PS2_V:01BFA00_GS100_XG02_V FLT:0 TLTE:01BFA00_GS000_T01
TYPE:2 SIG:01BFA00_GS000_ZU01
SIG_V:01BFA00_GS000_ZU01_V
FB_VRE_2POS 4 PS1:01BFA00_GS101_XG01 PS1_V:01BFA00_GS101_XG01_V PS2:01BFA00_GS101_XG02
PS2_V:01BFA00_GS101_XG02_V FLT:0 TLTE:01BFA00_GS000_T01
TYPE:2 SIG:01BFA00_GS101_ZU01
SIG_V:01BFA00_GS101_ZU01_V
FB_VRE_2POS 6 PS1:01BFA00_GS102_XG01 PS1_V:01BFA00_GS102_XG01_V PS2:01BFA00_GS102_XG02
PS2_V:01BFA00_GS102_XG02_V FLT:0 TLTE:01BFA00_GS000_T01
TYPE:2 SIG:01BFA00_GS102_ZU01
SIG_V:01BFA00_GS102_ZU01_V
GS003 180 FB_VRE_2POS 1 PS1:01BAC00_GS005_XG01 PS1_V:01BAC00_GS005_XG01_V PS2:01BAC00_GS005_XG02
Disconnector Switch PS2_V:01BAC00_GS005_XG02_V FLT:0 TLTE:01BAC00_GS003_T01
TYPE:2 SIG:01BAC00_GS005_ZU01
SIG_V:01BAC00_GS005_ZU01_V
FB_VRE_2POS 3 PS1:01BAC00_GS035_XG01 PS1_V:01BAC00_GS035_XG01_V PS2:01BAC00_GS035_XG02
PS2_V:01BAC00_GS035_XG02_V FLT:0 TLTE:01BAC00_GS003_T01
TYPE:2 SIG:01BAC00_GS035_ZU01
SIG_V:01BAC00_GS035_ZU01_V
XX PXXXXA4XXXX.231/A
DIAGRAM SHEET FUNCTIONAL BLOCK ARGUMENTS
BLOCK NUMBER
179 FB_CB 4 I01:01BAC00_GS003_ZA01 I02:0 I03:01BAC00_GS003_ZC01
I04:01BAC00_GS003_ZJ01 I06:01BAC00_GS003_XG01_V O01:01BAC00_GS003_YL01
O02: I07:01BAC00_GS003_ZA02 I08:0
I09:01BAC00_GS003_ZC02 I10:01BAC00_GS003_ZJ02 I11:01BAC00_GS003_XG02
I12:01BAC00_GS003_XG02_V O03:01BAC00_GS003_YL02 O04:
I16:0 P01:01BAC00_GS003_ZT11 P02:01BAC00_GS003_ZT01
P03:01BAC00_GS003_ZT02 P04:01BAC00_GS003_ZT00 O05:01BAC00_GS003_ZU01
O06:01BAC00_GS003_ZM10 O07:01BAC00_GS003_ZM11 O08:01BAC00_GS003_ZM12
O09: I15:01BAC00_GS003_ZM09 O10:01BAC00_GS003_ZU01_V
I05:01BAC00_GS003_XG01 I13:01BAC00_GS003_ZM00 I14:01BAC00_GS003_ZM50
TYPE:2
180 FB_VRE_2POS 5 PS1:01BAC00_GS038_XG01 PS1_V:01BAC00_GS038_XG01_V PS2:01BAC00_GS038_XG02
PS2_V:01BAC00_GS038_XG02_V FLT:0 TLTE:01BAC00_GS003_T01
TYPE:2 SIG:01BAC00_GS038_ZU01
SIG_V:01BAC00_GS038_ZU01_V
GS101 85 FB_CB 1 I01:01MKC65_GS101_ZA01 I02:0 I03:01MKC65_GS101_ZC01
Excitation Field Breaker I04:01MKC65_GS101_ZJ01 I06:01MKC65_GS101_XG01_V O01:01MKC65_GS101_YL01
O02: I07:01MKC65_GS101_ZA02 I08:0
I09:01MKC65_GS101_ZC02 I10:01MKC65_GS101_ZJ02 I11:01MKC65_GS101_XG02
I12:01MKC65_GS101_XG02_V O03:01MKC65_GS101_YL02 O04:
I16:0 P01:01MKC65_GS101_ZT11 P02:01MKC65_GS101_ZT01
P03:01MKC65_GS101_ZT02 P04:01MKC65_GS101_ZT00 O05:01MKC65_GS101_ZU01
O06:01MKC65_GS101_ZM10 O07:01MKC65_GS101_ZM11 O08:01MKC65_GS101_ZM12
O09: I15:01MKC65_GS101_ZM09 O10:01MKC65_GS101_ZU01_V
I05:01MKC65_GS101_XG01 I13:01MKC65_GS101_ZM00 I14:01MKC65_GS101_ZM50
TYPE:01MKC65_GS101_TP01
GS901 184 SEL_B 2 G:01CJA00_EA000_CON_E01 IN1:81ADD00_FE231_ZH03 IN2:1
GCB RE:01BAC00_GS901_BOO_0006
186 RS 18 S:(connection) R1:(connection) IV:0
Q1:01CJA00_EU001_ZG14 NQ1:
185 FB_CB 21 I01:01BAC00_GS901_BOO_0004 I02:0 I03:01BAC00_GS901_ZC01
I04:01BAC00_GS901_ZJ01 I06:01BAC00_GS901_XG01_V
O01:01BAC00_GS901_BOO_0007 O02:
I07:01BAC00_GS901_BOO_0005 I08:0 I09:01BAC00_GS901_ZC02
I10:01BAC00_GS901_ZJ02 I11:01BAC00_GS901_XG02 I12:01BAC00_GS901_XG02_V
O03:01BAC00_GS901_YL02 O04: I16:0
P01:01BAC00_GS901_ZT11 P02:01BAC00_GS901_ZT01 P03:01BAC00_GS901_ZT02
P04:01BAC00_GS901_ZT00 O05:01BAC00_GS901_ZU01 O06:01BAC00_GS901_ZM10
O07:01BAC00_GS901_ZM11 O08:01BAC00_GS901_ZM12 O09:
I15:01BAC00_GS901_ZM09 O10:01BAC00_GS901_ZU01_V I05:01BAC00_GS901_XG01
I13:01BAC00_GS901_ZM00 I14:01BAC00_GS901_ZM50 TYPE:2
INIT 66 TP_R 1 IN:1 TP:5 REB:01SIM_INIT_BOO_0004
Initial Pre Start Condition RET:
R_TRIG 2 IN:01SIM_INIT_BOO_0004 RE:01SIM_INIT_1SYCLE
SIM_STATUS_S 3 SEL:01SIM_INIT_1SYCLE VALUE0:01BAC00_GS003_XL31 VALUE1:01SIM_INIT_TURE
EL INPUT:01BAC00_GS003_XL31
SIM_STATUS_S 4 SEL:01SIM_INIT_1SYCLE VALUE0:01BAC00_GS035_XG02 VALUE1:01SIM_INIT_TURE
EL INPUT:01BAC00_GS035_XG02
67 SIM_STATUS_S 5 SEL:01SIM_INIT_1SYCLE VALUE0:01CJA00_GS110_XM51 VALUE1:01SIM_INIT_TURE
EL INPUT:01CJA00_GS110_XM51
SIM_STATUS_S 6 SEL:01SIM_INIT_1SYCLE VALUE0:01MAU24_AP001_XM51 VALUE1:01SIM_INIT_TURE
EL INPUT:01MAU24_AP001_XM51
SIM_STATUS_S 7 SEL:01SIM_INIT_1SYCLE VALUE0:01MAU24_AP003_XM51 VALUE1:01SIM_INIT_TURE
EL INPUT:01MAU24_AP003_XM51
SIM_STATUS_S 8 SEL:01SIM_INIT_1SYCLE VALUE0:01MAU24_AA001_XL21 VALUE1:01SIM_INIT_TURE
EL INPUT:01MAU24_AA001_XL21
68 SIM_STATUS_S 9 SEL:01SIM_INIT_1SYCLE VALUE0:01MAU24_EU014_XM01 VALUE1:01SIM_INIT_TURE
EL INPUT:01MAU24_EU014_XM01
SIM_STATUS_S 10 SEL:01SIM_INIT_1SYCLE VALUE0:01MEA41_CP402_XM51 VALUE1:01SIM_INIT_TURE
EL INPUT:01MEA41_CP402_XM51
SIM_STATUS_S 11 SEL:01SIM_INIT_1SYCLE VALUE0:01MEU11_EN002_XG01 VALUE1:01SIM_INIT_TURE
EL INPUT:01MEU11_EN002_XG01
69 SIM_STATUS_S 12 SEL:01SIM_INIT_1SYCLE VALUE0:01MEU11_GW001_XM51 VALUE1:01SIM_INIT_TURE
EL INPUT:01MEU11_GW001_XM51
SIM_STATUS_S 13 SEL:01SIM_INIT_1SYCLE VALUE0:01MKC65_GH001_XL31 VALUE1:01SIM_INIT_TURE
EL INPUT:01MKC65_GH001_XL31
SIM_STATUS_S 14 SEL:01SIM_INIT_1SYCLE VALUE0:01SCC00_AA901_XG21 VALUE1:01SIM_INIT_TURE
EL INPUT:01SCC00_AA901_XG21
66 SIM_STATUS_S 15 SEL:01SIM_INIT_1SYCLE VALUE0:01BAT00_EN001_XM08 VALUE1:01SIM_INIT_TURE
EL INPUT:01BAT00_EN001_XM08
SIM_STATUS_S 16 SEL:01SIM_INIT_1SYCLE VALUE0:01BAC00_GS025_XG02 VALUE1:01SIM_INIT_TURE
EL INPUT:01BAC00_GS025_XG02
SIM_STATUS_S 17 SEL:01SIM_INIT_1SYCLE VALUE0:01CJA00_EP002_XM51 VALUE1:01SIM_INIT_TURE
EL INPUT:01CJA00_EP002_XM51
67 SIM_STATUS_S 18 SEL:01SIM_INIT_1SYCLE VALUE0:01CJA00_GS012_XM51 VALUE1:01SIM_INIT_TURE
EL INPUT:01CJA00_GS012_XM51
SIM_STATUS_S 19 SEL:01SIM_INIT_1SYCLE VALUE0:01MAU24_AP001_XL21 VALUE1:01SIM_INIT_TURE
EL INPUT:01MAU24_AP001_XL21
SIM_STATUS_S 20 SEL:01SIM_INIT_1SYCLE VALUE0:01MAU24_AP002_XM52 VALUE1:01SIM_INIT_TURE
EL INPUT:01MAU24_AP002_XM52
68 SIM_STATUS_S 21 SEL:01SIM_INIT_1SYCLE VALUE0:01MAU24_EU014_XM52 VALUE1:01SIM_INIT_TURE
EL INPUT:01MAU24_EU014_XM52
SIM_STATUS_S 22 SEL:01SIM_INIT_1SYCLE VALUE0:01MEA41_GH001_XM52 VALUE1:01SIM_INIT_TURE
EL INPUT:01MEA41_GH001_XM52
SIM_STATUS_S 23 SEL:01SIM_INIT_1SYCLE VALUE0:01MEU11_EU001_XL21 VALUE1:01SIM_INIT_TURE
EL INPUT:01MEU11_EU001_XL21
SIM_STATUS_S 24 SEL:01SIM_INIT_1SYCLE VALUE0:01MEU11_EN001_XM51 VALUE1:01SIM_INIT_TURE
EL INPUT:01MEU11_EN001_XM51
69 SIM_STATUS_S 25 SEL:01SIM_INIT_1SYCLE VALUE0:01MKA54_AA002_XL21 VALUE1:01SIM_INIT_TURE
EL INPUT:01MKA54_AA002_XL21
XX PXXXXA4XXXX.232/A
DIAGRAM SHEET FUNCTIONAL BLOCK ARGUMENTS
BLOCK NUMBER
SIM_STATUS_S 26 SEL:01SIM_INIT_1SYCLE VALUE0:01PAC00_AA001_XL21 VALUE1:01SIM_INIT_TURE
EL INPUT:01PAC00_AA001_XL21
SIM_STATUS_S 27 SEL:01SIM_INIT_1SYCLE VALUE0:01SCC00_AA902_XL21 VALUE1:01SIM_INIT_TURE
EL INPUT:01SCC00_AA902_XL21
SIM_STATUS_S 28 SEL:01SIM_INIT_1SYCLE VALUE0:01MKA54_AA001_XL21 VALUE1:01SIM_INIT_TURE
EL INPUT:01MKA54_AA001_XL21
SIM_STATUS_S 29 SEL:01SIM_INIT_1SYCLE VALUE0:01MKA54_CP901_XM01 VALUE1:01SIM_INIT_TURE
EL INPUT:01MKA54_CP901_XM01
SIM_STATUS_S 30 SEL:01SIM_INIT_1SYCLE VALUE0:01MKC65_DE001_XM51 VALUE1:01SIM_INIT_TURE
EL INPUT:01MKC65_DE001_XM51
68 SIM_STATUS_S 31 SEL:01SIM_INIT_1SYCLE VALUE0:01MAU24_EU014_XM51 VALUE1:01SIM_INIT_TURE
EL INPUT:01MAU24_EU014_XM51
SIM_STATUS_S 32 SEL:01SIM_INIT_1SYCLE VALUE0:01MEA41_GH001_XM51 VALUE1:01SIM_INIT_TURE
EL INPUT:01MEA41_GH001_XM51
SIM_STATUS_S 33 SEL:01SIM_INIT_1SYCLE VALUE0:01MEU11_GW002_XM51 VALUE1:01SIM_INIT_TURE
EL INPUT:01MEU11_GW002_XM51
69 SIM_STATUS_S 34 SEL:01SIM_INIT_1SYCLE VALUE0:01MEA41_CG605_XG02 VALUE1:01SIM_INIT_TURE
EL INPUT:01MEA41_CG605_XG02
68 SIM_STATUS_S 35 SEL:01SIM_INIT_1SYCLE VALUE0:01MEA41_CF402_XM51 VALUE1:01SIM_INIT_TURE
EL INPUT:01MEA41_CF402_XM51
SIM_STATUS_S 36 SEL:01SIM_INIT_1SYCLE VALUE0:01MEU11_EN001_XG01 VALUE1:01SIM_INIT_TURE
EL INPUT:01MEU11_EN001_XG01
SIM_STATUS_S 37 SEL:01SIM_INIT_1SYCLE VALUE0:01MEU11_FS001_XM51 VALUE1:01SIM_INIT_TURE
EL INPUT:01MEU11_FS001_XM51
SIM_STATUS_S 38 SEL:01SIM_INIT_1SYCLE VALUE0:01MEU11_EN002_XM51 VALUE1:01SIM_INIT_TURE
EL INPUT:01MEU11_EN002_XM51
67 SIM_STATUS_S 39 SEL:01SIM_INIT_1SYCLE VALUE0:01CJA00_GS011_XM51 VALUE1:01SIM_INIT_TURE
EL INPUT:01CJA00_GS011_XM51
66 SIM_STATUS_S 40 SEL:01SIM_INIT_1SYCLE VALUE0:01BAC00_GS003_XL31 VALUE1:01SIM_INIT_TURE
EL INPUT:01BAC00_GS003_XL31
SIM_STATUS_S 41 SEL:01SIM_INIT_1SYCLE VALUE0:01BAC00_GS005_XG02 VALUE1:01SIM_INIT_TURE
EL INPUT:01BAC00_GS005_XG02
SIM_STATUS_S 42 SEL:01SIM_INIT_1SYCLE VALUE0:01BAC00_GS038_XG02 VALUE1:01SIM_INIT_TURE
EL INPUT:01BAC00_GS038_XG02
SIM_STATUS_S 43 SEL:01SIM_INIT_1SYCLE VALUE0:01CJA00_EP001_XM51 VALUE1:01SIM_INIT_TURE
EL INPUT:01CJA00_EP001_XM51
67 SIM_STATUS_S 44 SEL:01SIM_INIT_1SYCLE VALUE0:01CJA00_GS109_XM51 VALUE1:01SIM_INIT_TURE
EL INPUT:01CJA00_GS109_XM51
SIM_STATUS_S 45 SEL:01SIM_INIT_1SYCLE VALUE0:01MAU24_AP001_XM52 VALUE1:01SIM_INIT_TURE
EL INPUT:01MAU24_AP001_XM52
SIM_STATUS_S 46 SEL:01SIM_INIT_1SYCLE VALUE0:01MAU24_AP002_XM51 VALUE1:01SIM_INIT_TURE
EL INPUT:01MAU24_AP002_XM51
SIM_STATUS_S 47 SEL:01SIM_INIT_1SYCLE VALUE0:01MAU24_AP002_XL21 VALUE1:01SIM_INIT_TURE
EL INPUT:01MAU24_AP002_XL21
SIM_STATUS_S 48 SEL:01SIM_INIT_1SYCLE VALUE0:01MAU24_AP003_XL21 VALUE1:01SIM_INIT_TURE
EL INPUT:01MAU24_AP003_XL21
SIM_STATUS_S 49 SEL:01SIM_INIT_1SYCLE VALUE0:01MAU24_AA002_XL21 VALUE1:01SIM_INIT_TURE
EL INPUT:01MAU24_AA002_XL21
66 SIM_SELECTOR 50 UP:01SIM_INIT_UP001 DOWN:01SIM_INIT_DW001 SEL0:01CJA00_GH001_XL31
SEL1:01CJA00_GH001_XL32 SEL2:01CJA00_GH001_XL33 SEL3:
SEL4:
SIM_SELECTOR 51 UP:01SIM_INIT_UP003 DOWN:01SIM_INIT_DW003 SEL0:01CJA00_GH003_XL21
SEL1:01CJA00_GH003_XL22 SEL2:01CJA00_GH003_XL23 SEL3:
SEL4:
REG01 70 SEL 1 G:01SIM_REG01_BI01 IN1:01SIM_REG01_REAL_0006 IN2:01SIM_REG01_REAL_0019
Governor and MIV RE:01SIM_REG01_REAL_0027
regulator 71 SEL 2 G:01MEU11_EM001_ZG01 IN1:01SIM_REG01_RI22 IN2:01SIM_REG01_RI21
RE:01SIM_REG01_REAL_0029
72 AO_SCALE 6 IN:01BBA00_CE001_XQ01 IN_MAX:32767 IN_MIN:6553
OUT_MAX:12000 OUT_MIN:-3000 RE:01SIM_REG01_INT16_0003
ERR:
71 GE 13 IN1:01SIM_REG01_REAL_0004 IN2:01SIM_REG01_REAL_0029 RE:01SIM_REG01_BOO_0007
70 MOVE_B 16 IN:01MKA54_CG565_XG01 RE:01SIM_REG01_BOO_0020
AO_SCALE 18 IN:01SIM_REG01_REAL_0002 IN_MAX:10000 IN_MIN:0
OUT_MAX:32767 OUT_MIN:6553 RE:01SIM_REG01_INT16_0001
ERR:
AO_SCALE 19 IN:01SIM_REG01_REAL_0009 IN_MAX:01SIM_REG01_R11 IN_MIN:01SIM_REG01_R10
OUT_MAX:32767 OUT_MIN:6553 RE:01SIM_REG01_INT16_0004
ERR:
AO_SCALE 20 IN:01SIM_REG01_REAL_0011 IN_MAX:10000 IN_MIN:0
OUT_MAX:32767 OUT_MIN:6553 RE:01SIM_REG01_INT16_0006
ERR:
72 RS 24 S:01MKC65_EM001_YL51 R1:01BBA00_DE003_ZH07 IV:0
Q1:01SIM_REG01_BOO_0004 NQ1:
AO_SCALE 25 IN:01SIM_REG01_REAL_0008 IN_MAX:10000 IN_MIN:0
OUT_MAX:32767 OUT_MIN:6553 RE:01SIM_REG01_INT16_0005
ERR:
AO_SCALE 26 IN:01SIM_REG01_REAL_0016 IN_MAX:01SIM_REG01_II15 IN_MIN:0
OUT_MAX:32767 OUT_MIN:6553 RE:01SIM_REG01_INT16_0007
ERR:
AO_SCALE 27 IN:01SIM_REG01_REAL_0025 IN_MAX:2000 IN_MIN:0
OUT_MAX:32767 OUT_MIN:6553 RE:01SIM_REG01_INT16_0010
ERR:
73 SIM_DEWATER 30 WATER_LVL:01SIM_REG01_REAL_0033
POWER:01SIM_REG01_REAL_0019 OPENING:01SIM_REG01_REAL_0004
MAIN_VLV:01SCC00_AA901_XG01 AUX_VLV:01SCC00_AA902_XG01 RLS_VLV:0
GCB_CLS:01BAC00_GS901_XG01 REG_STEP:01SIM_REG01_RI11 FLAG_DW:01SIM_REG01_BI01
CONDENSER:01MEU11_EU001_TL04
XX PXXXXA4XXXX.233/A
DIAGRAM SHEET FUNCTIONAL BLOCK ARGUMENTS
BLOCK NUMBER
SIM_REAL_M 31 INPUT:01BBA00_FE001_RQ42 VALUE:01SIM_REG01_REAL_0007
SIM_REAL_M 32 INPUT:01BBA00_FE001_RQ03 VALUE:01SIM_REG01_REAL_0022
AO_SCALE 33 IN:01SIM_REG01_REAL_0034 IN_MAX:1000 IN_MIN:0
OUT_MAX:32767 OUT_MIN:6553 RE:01SIM_REG01_INT16_0012
ERR:
GE 34 IN1:01SIM_REG01_REAL_0021 IN2:0.8 RE:01SIM_REG01_BOO_0003
SIM_ANA_M 35 VALUE:01SIM_REG01_II06 INPUT:01MEA41_CP501_XQ01
71 SIM_STATUS_S 36 SEL:01SIM_REG01_BOO_0007 VALUE0:0 VALUE1:1
EL INPUT:01MEA41_CG002_XG01
SIM_STATUS_M 37 VALUE:01MEU11_EM001_YL06 INPUT:01MEU11_EU001_XG04
SIM_STATUS_M 38 VALUE:01MEU11_EM001_YL05 INPUT:01MEU11_EU001_XG02
70 SIM_ANA_M 39 VALUE:01SIM_REG01_INT16_0001 INPUT:01MEU11_CS001_XQ01
XX PXXXXA4XXXX.234/A
DIAGRAM SHEET FUNCTIONAL BLOCK ARGUMENTS
BLOCK NUMBER
148 MOVE_B 2 IN:01CJA00_EA043_SFC_S2_X RE:01CJA00_EA043_ZS021
146 F_TRIG 2 IN:01CJA00_EA027_ZG01 RE:01CJA00_EA027_SIGBOO_0001
175 F_TRIG 2 IN:01CJA00_EU001_ZG01 RE:01CJA00_EA002_SIGBOO_0004
178 F_TRIG 2 IN:01CJA00_EU001_ZG01 RE:01CJA00_EA051_SIGBOO_0002
162 F_TRIG 2 IN:01CJA00_EA009_ZG01 RE:01CJA00_EA009_SIGBOO_0001
83 F_TRIG 2 IN:01CJA00_EU001_ZG01 RE:01CJA00_EA007_SIGBOO_0002
157 MOVE_B 2 IN:01CJA00_EA036_SFC_S2_X RE:01CJA00_EA036_ZS021
137 F_TRIG 2 IN:01CJA00_EA010_ZG01 RE:01CJA00_EA010_SIGBOO_0001
173 F_TRIG 2 IN:01CJA00_EU001_ZG01 RE:01CJA00_EA001_SIGBOO_0004
120 MOVE_B 2 IN:01CJA00_EA073_SFC_S2_X RE:01CJA00_EA073_ZS021
144 MOVE_B 3 IN:01CJA00_EA021_SFC_S3_X RE:01CJA00_EA021_ZS031
178 MOVE_B 3 IN:01CJA00_EA051_SFC_S1_X RE:01CJA00_EA051_ZS011
137 F_TRIG 3 IN:01CJA00_EU001_ZG01 RE:01CJA00_EA010_SIGBOO_0005
160 MOVE_B 3 IN:01CJA00_EA008_SFC_S3_X RE:01CJA00_EA008_ZS031
162 F_TRIG 3 IN:01CJA00_EU001_ZG01 RE:01CJA00_EA009_SIGBOO_0005
157 F_TRIG 3 IN:01CJA00_EA036_ZG01 RE:01CJA00_EA036_SIGBOO_0001
83 MOVE_B 3 IN:01CJA00_EA007_SFC_S1_X RE:01CJA00_EA007_ZS011
175 MOVE_B 3 IN:01CJA00_EA002_SFC_S1_X RE:01CJA00_EA002_ZS011
148 MOVE_B 3 IN:01CJA00_EA043_SFC_S3_X RE:01CJA00_EA043_ZS031
155 MOVE_B 3 IN:01CJA00_EA032_SFC_S3_X RE:01CJA00_EA032_ZS031
173 MOVE_B 3 IN:01CJA00_EA001_SFC_S1_X RE:01CJA00_EA001_ZS011
120 F_TRIG 3 IN:01CJA00_EA073_ZG01 RE:01CJA00_EA073_SIGBOO_0003
153 MOVE_B 3 IN:01CJA00_EA034_SFC_S3_X RE:01CJA00_EA034_ZS031
151 MOVE_B 3 IN:01CJA00_EA061_SFC_S3_X RE:01CJA00_EA061_ZS031
146 F_TRIG 3 IN:01CJA00_EU001_ZG01 RE:01CJA00_EA027_SIGBOO_0005
148 TON_R 4 IN:01CJA00_EA043_SFC_S99_X TP:01CJA00_EA043_ZT099 REB:01CJA00_EA043_ZD099
RET:
153 F_TRIG 4 IN:01CJA00_EA034_ZG01 RE:01CJA00_EA034_SIGBOO_0001
144 TON_R 4 IN:01CJA00_EA021_SFC_S3_X TP:01CJA00_EA021_SIGRI01 REB:01CJA00_EA021_DL04
RET:
155 F_TRIG 4 IN:01CJA00_EA032_ZG01 RE:01CJA00_EA032_SIGBOO_0001
151 MOVE_B 4 IN:01CJA00_EA061_SFC_S4_X RE:01CJA00_EA061_ZS041
160 TON_R 4 IN:01CJA00_EA008_SFC_S2_X TP:01CJA00_EA008_ZT002 REB:01CJA00_EA008_ZD002
RET:
178 MOVE_B 4 IN:01CJA00_EA051_SFC_S2_X RE:01CJA00_EA051_ZS021
120 F_TRIG 4 IN:01CJA00_EU001_ZG01 RE:01CJA00_EA073_SIGBOO_0001
157 F_TRIG 4 IN:01CJA00_EU001_ZG01 RE:01CJA00_EA036_SIGBOO_0005
173 MOVE_B 4 IN:01CJA00_EA001_SFC_S2_X RE:01CJA00_EA001_ZS021
83 MOVE_B 4 IN:01CJA00_EA007_SFC_S2_X RE:01CJA00_EA007_ZS021
175 MOVE_B 4 IN:01CJA00_EA002_SFC_S2_X RE:01CJA00_EA002_ZS021
148 F_TRIG 5 IN:01CJA00_EA043_ZG01 RE:01CJA00_EA043_SIGBOO_0001
153 F_TRIG 5 IN:01CJA00_EU001_ZG01 RE:01CJA00_EA034_SIGBOO_0005
160 F_TRIG 5 IN:01CJA00_EA008_ZG01 RE:01CJA00_EA008_SIGBOO_0001
144 F_TRIG 5 IN:01CJA00_EA021_ZG01 RE:01CJA00_EA021_SIGBOO_0001
155 F_TRIG 5 IN:01CJA00_EU001_ZG01 RE:01CJA00_EA032_SIGBOO_0005
151 MOVE_B 5 IN:01CJA00_EA061_SFC_S5_X RE:01CJA00_EA061_ZS051
178 MOVE_B 5 IN:01CJA00_EA051_SFC_S3_X RE:01CJA00_EA051_ZS031
173 MOVE_B 5 IN:01CJA00_EA001_SFC_S3_X RE:01CJA00_EA001_ZS031
175 MOVE_B 5 IN:01CJA00_EA002_SFC_S3_X RE:01CJA00_EA002_ZS031
MOVE_B 6 IN:01CJA00_EA002_SFC_S4_X RE:01CJA00_EA002_ZS041
151 MOVE_B 6 IN:01CJA00_EA061_SFC_S6_X RE:01CJA00_EA061_ZS061
162 TON_D 6 IN:(connection) TP:01CJA00_EA009_ZT01
REB:01CJA00_EA009_SIGBOO_0002
RET:01CJA00_EA009_SIGINT32_0001
137 TON_D 6 IN:(connection) TP:01CJA00_EA010_ZT01
REB:01CJA00_EA010_SIGBOO_0002
RET:01CJA00_EA010_SIGINT32_0001
173 MOVE_B 6 IN:01CJA00_EA001_SFC_S4_X RE:01CJA00_EA001_ZS041
144 F_TRIG 6 IN:01CJA00_EU001_ZG01 RE:01CJA00_EA021_SIGBOO_0005
178 MOVE_B 6 IN:01CJA00_EA051_SFC_S4_X RE:01CJA00_EA051_ZS041
160 F_TRIG 6 IN:01CJA00_EU001_ZG01 RE:01CJA00_EA008_SIGBOO_0005
148 F_TRIG 6 IN:01CJA00_EU001_ZG01 RE:01CJA00_EA043_SIGBOO_0005
146 TON_D 6 IN:(connection) TP:01CJA00_EA027_ZT01
REB:01CJA00_EA027_SIGBOO_0002
RET:01CJA00_EA027_SIGINT32_0001
162 TOF_R 7 IN:01CJA00_EA009_SIGBOO_0002 TP:10
REB:01CJA00_EA009_SIGBOO_0003 RET:
157 TON_D 7 IN:(connection) TP:01CJA00_EA036_ZT01
REB:01CJA00_EA036_SIGBOO_0002
RET:01CJA00_EA036_SIGINT32_0001
83 TON_D 7 IN:(connection) TP:01CJA00_EA007_ZT01
REB:01CJA00_EA007_SIGBOO_0010
RET:01CJA00_EA007_SIGINT32_0003
151 TON_R 7 IN:01CJA00_EA061_SFC_S3_X TP:01CJA00_EA061_ZT002 REB:01CJA00_EA061_ZD002
RET:
173 TON_R 7 IN:01CJA00_EA001_SFC_S1_X TP:01CJA00_EA001_ZT001 REB:01CJA00_EA001_ZD001
RET:
146 TOF_R 7 IN:01CJA00_EA027_SIGBOO_0002 TP:10
REB:01CJA00_EA027_SIGBOO_0003 RET:
XX PXXXXA4XXXX.235/A
DIAGRAM SHEET FUNCTIONAL BLOCK ARGUMENTS
BLOCK NUMBER
137 TOF_R 7 IN:01CJA00_EA010_SIGBOO_0002 TP:10
REB:01CJA00_EA010_SIGBOO_0003 RET:
178 MOVE_B 7 IN:01CJA00_EA051_SFC_S5_X RE:01CJA00_EA051_ZS051
175 TON_R 7 IN:01CJA00_EA002_SFC_S1_X TP:01CJA00_EA002_ZT001 REB:01CJA00_EA002_ZD001
RET:
120 TON_D 7 IN:(connection) TP:01CJA00_EA073_ZT01
REB:01CJA00_EA073_SIGBOO_0004
RET:01CJA00_EA073_SIGINT32_0001
157 TOF_R 8 IN:01CJA00_EA036_SIGBOO_0002 TP:10
REB:01CJA00_EA036_SIGBOO_0003 RET:
151 F_TRIG 8 IN:01CJA00_EA061_ZG01 RE:01CJA00_EA061_SIGBOO_0001
155 TON_D 8 IN:(connection) TP:01CJA00_EA032_ZT01
REB:01CJA00_EA032_SIGBOO_0002
RET:01CJA00_EA032_SIGINT32_0001
83 TOF_R 8 IN:01CJA00_EA007_SIGBOO_0010 TP:10
REB:01CJA00_EA007_SIGBOO_0009 RET:
120 TOF_R 8 IN:01CJA00_EA073_SIGBOO_0004 TP:10
REB:01CJA00_EA073_SIGBOO_0002 RET:
178 MOVE_B 8 IN:01CJA00_EA051_SFC_S6_X RE:01CJA00_EA051_ZS061
153 TON_D 8 IN:(connection) TP:01CJA00_EA034_ZT01
REB:01CJA00_EA034_SIGBOO_0002
RET:01CJA00_EA034_SIGINT32_0001
137 SEL 9 G:0 IN1:01CJA00_EA010_ZQ01
IN2:01CJA00_EA010_SIGINT32_0001 RE:01CJA00_EA010_ZQ01
178 TON_R 9 IN:01CJA00_EA051_ZS031 TP:01CJA00_EA051_ZT002 REB:01CJA00_EA051_ZD002
RET:
148 TON_D 9 IN:(connection) TP:01CJA00_EA043_ZT01
REB:01CJA00_EA043_SIGBOO_0002
RET:01CJA00_EA043_SIGINT32_0001
144 TON_D 9 IN:(connection) TP:01CJA00_EA021_ZT01
REB:01CJA00_EA021_SIGBOO_0002
RET:01CJA00_EA021_SIGINT32_0001
153 TOF_R 9 IN:01CJA00_EA034_SIGBOO_0002 TP:10
REB:01CJA00_EA034_SIGBOO_0003 RET:
162 SEL 9 G:0 IN1:01CJA00_EA009_ZQ01
IN2:01CJA00_EA009_SIGINT32_0001 RE:01CJA00_EA009_ZQ01
146 SEL 9 G:0 IN1:01CJA00_EA027_ZQ01
IN2:01CJA00_EA027_SIGINT32_0001 RE:01CJA00_EA027_ZQ01
151 F_TRIG 9 IN:01CJA00_EU001_ZG01 RE:01CJA00_EA061_SIGBOO_0005
160 TON_D 9 IN:(connection) TP:01CJA00_EA008_ZT01
REB:01CJA00_EA008_SIGBOO_0002
RET:01CJA00_EA008_SIGINT32_0001
155 TOF_R 9 IN:01CJA00_EA032_SIGBOO_0002 TP:10
REB:01CJA00_EA032_SIGBOO_0003 RET:
120 SEL 10 G:0 IN1:01CJA00_EA073_ZQ01
IN2:01CJA00_EA073_SIGINT32_0001 RE:01CJA00_EA073_ZQ01
160 TOF_R 10 IN:01CJA00_EA008_SIGBOO_0002 TP:10
REB:01CJA00_EA008_SIGBOO_0003 RET:
144 TOF_R 10 IN:01CJA00_EA021_SIGBOO_0002 TP:10
REB:01CJA00_EA021_SIGBOO_0003 RET:
148 TOF_R 10 IN:01CJA00_EA043_SIGBOO_0002 TP:10
REB:01CJA00_EA043_SIGBOO_0003 RET:
175 TON_D 10 IN:(connection) TP:01CJA00_EA002_ZT01
REB:01CJA00_EA002_SIGBOO_0002
RET:01CJA00_EA002_SIGINT32_0001
173 TON_D 10 IN:(connection) TP:01CJA00_EA001_ZT01
REB:01CJA00_EA001_SIGBOO_0002
RET:01CJA00_EA001_SIGINT32_0001
83 SEL 10 G:0 IN1:01CJA00_EA007_ZQ01
IN2:01CJA00_EA007_SIGINT32_0003 RE:01CJA00_EA007_ZQ01
157 SEL 10 G:0 IN1:01CJA00_EA036_ZQ01
IN2:01CJA00_EA036_SIGINT32_0001 RE:01CJA00_EA036_ZQ01
155 SEL 11 G:0 IN1:01CJA00_EA032_ZQ01
IN2:01CJA00_EA032_SIGINT32_0001 RE:01CJA00_EA032_ZQ01
153 SEL 11 G:0 IN1:01CJA00_EA034_ZQ01
IN2:01CJA00_EA034_SIGINT32_0001 RE:01CJA00_EA034_ZQ01
173 TOF_R 11 IN:01CJA00_EA001_SIGBOO_0002 TP:10
REB:01CJA00_EA001_SIGBOO_0003 RET:
175 TOF_R 11 IN:01CJA00_EA002_SIGBOO_0002 TP:10
REB:01CJA00_EA002_SIGBOO_0003 RET:
151 TON_D 12 IN:(connection) TP:01CJA00_EA061_ZT01
REB:01CJA00_EA061_SIGBOO_0002
RET:01CJA00_EA061_SIGINT32_0001
144 SEL 12 G:0 IN1:01CJA00_EA021_ZQ01
IN2:01CJA00_EA021_SIGINT32_0001 RE:01CJA00_EA021_ZQ01
148 SEL 12 G:0 IN1:01CJA00_EA043_ZQ01
IN2:01CJA00_EA043_SIGINT32_0001 RE:01CJA00_EA043_ZQ01
160 SEL 12 G:0 IN1:01CJA00_EA008_ZQ01
IN2:01CJA00_EA008_SIGINT32_0001 RE:01CJA00_EA008_ZQ01
178 TON_D 12 IN:(connection) TP:01CJA00_EA051_ZT01
REB:01CJA00_EA051_SIGBOO_0003
RET:01CJA00_EA051_SIGINT32_0001
TOF_R 13 IN:01CJA00_EA051_SIGBOO_0003 TP:10
REB:01CJA00_EA051_SIGBOO_0004 RET:
175 SEL 13 G:0 IN1:01CJA00_EA002_ZQ01
IN2:01CJA00_EA002_SIGINT32_0001 RE:01CJA00_EA002_ZQ01
151 TOF_R 13 IN:01CJA00_EA061_SIGBOO_0002 TP:10
REB:01CJA00_EA061_SIGBOO_0003 RET:
XX PXXXXA4XXXX.236/A
DIAGRAM SHEET FUNCTIONAL BLOCK ARGUMENTS
BLOCK NUMBER
173 SEL 13 G:0 IN1:01CJA00_EA001_ZQ01
IN2:01CJA00_EA001_SIGINT32_0001 RE:01CJA00_EA001_ZQ01
151 SEL 15 G:0 IN1:01CJA00_EA061_ZQ01
IN2:01CJA00_EA061_SIGINT32_0001 RE:01CJA00_EA061_ZQ01
178 SEL 15 G:0 IN1:01CJA00_EA051_ZQ01
IN2:01CJA00_EA051_SIGINT32_0001 RE:01CJA00_EA051_ZQ01
STA 124 MOVE_B 11 IN:01CJA00_EU001_ZG01 RE:01CJA00_EG001_YG01
Unit state MOVE_B 12 IN:01CJA00_EU001_ZG11 RE:01CJA00_EG002_YG01
MOVE_B 13 IN:01CJA00_EU001_ZG21 RE:01CJA00_EG003_YG01
MOVE_B 14 IN:01CJA00_EU001_ZG31 RE:01CJA00_EG005_YG01
MOVE_B 15 IN:01CJA00_EU001_ZG41 RE:01CJA00_EG006_YG01
MOVE_B 16 IN:01CJA00_EU001_ZG71 RE:01CJA00_EG004_YG01
MOVE_B 17 IN:01CJA00_EU001_ZG61 RE:01CJA00_EG007_YG01
123 FB_UNIT_STA 20 INI_ST:01CJA00_EU001_ZG00 ES_RQ:01CJA00_EU001_ZM03
QS_RQ:01CJA00_EU001_STABOO_0001 SS_ST:01CJA00_EU001_ZG01
NS_RQ:01CJA00_EU001_STABOO_0003 TS_ST:01CJA00_EU001_ZG11
TS_RQ:01CJA00_EU001_ZJ11 SR_ST:01CJA00_EU001_ZG21
SR_RQ:01CJA00_EU001_STABOO_0004 GE_ST:01CJA00_EU001_ZG31
GE_RQ:01CJA00_EU001_STABOO_0006 GC_ST:01CJA00_EU001_ZG41
GC_RQ:01CJA00_EU001_STABOO_0005 LC_ST:01CJA00_EU001_ZG61
LC_RQ:01CJA00_EU001_STABOO_0011 PU_ST:0
PU_RQ:0 PC_ST:0 PC_RQ:0
LA_ST:01CJA00_EU001_ZG71 LA_RQ:01CJA00_EU001_STABOO_0007
BS_ST:01CJA00_EU001_ZG51 BS_RQ:01CJA00_EU001_STABOO_0012
STATE_VAL:01CJA00_EU001_ZU01
ERROR:01CJA00_EU001_ZU01_V STATE_CLR:01CJA00_EU001_ZU02
XX PXXXXA4XXXX.237/A
8 FBD IN SFC ACTIONS
XX PXXXXA4XXXX.238/A
9 FORCED SFC
XX PXXXXA4XXXX.239/A
10 STEP VARIABLES
XX PXXXXA4XXXX.240/A