You are on page 1of 124

Dates : Name : Reference :

Approval Return Status

Comments

SigN Date

SigN.

SigN.

SigN.

SigN.

C SigN. 2017/02/28 UPDATED ACCORDING TO FAT COMMENTS GFE


HXN LPH LPH

B SigN. 2016/11/25 UPDATED ACCORDING TO 4th DLM COMMENTS GFE


HXN LPH LPH

A SigN. 2016/08/12 First Issue GFE


HXN LPH LPH

REV ESTABLISHED CHECKED APPROVED DATE MODIFICATIONS STAT.

VIETNAM ELECTRICITY
TRI AN HYDROPOWER COMPANY
LOT NO.5:“DESIGN,MATERIAL,EQUIPMENT SUPPLY AND
TECHNICAL SERVICES”
CONTRANT NO:99/HD-TDTA/ALSTOM

PURCHASER: SUPPLIER:

ALSTOM-HYDRO

CSCS
MAIN EQUIPMENT DATASHEETS

SCALE SIZE
SUBSUPPLIER:
A4

REV. SH/SH END N of S

H-10207 00 0EA 00-001F DA 1/124 124


C
MODIFICATIONS TABLE

REV ESTABLISHED CHECKED APPROVED DATE MODIFICATIONS Status.

A HXN LPH LPH 2016/08/12 FIRST ISSUE GFE

B HXN LPH LPH 2016/11/25 UPDATED ACCORDING TO 4th DLM COMMENTS GFE

C HXN LPH LPH 2017/02/28 UPDATED ACCORDING TO FAT COMMENTS GFE

CSCS MAIN EQUIPMENT DATASHEETS .2/C


- CONTENTS

MEAN WLL SDR-480P-24 Power Supply – Datasheet 5


MOXA EDS-408A-MM-SC - Rail Switch ETH 6TX-2FX SC Multimode 9
MOXA EDS-518E-MM-SC - Rail Switch ETH 14TX-2FX SC Multimode 11
ALSPA E8000 - HB2880 - 2 ETH Copper ports 29
ALSPA E8000 - HB8884 - Link Selector – Datasheet 31
PHOENIX Ethernet Hub FL HUB 8TX-ZF 33
ALSPA MFC3000 HCS LX- Multi Function Controller – Datasheet 39
SWITCH MOXA EDS-208_Series 41
MODBUS TCP GATEWAY MOXA MGate_MB3480 43
ALSPA CE1000 - BC8084 - Block Controller Module 45
ALSPA CE1000 - PS9400 - Power Supply Module – Datasheet 47
ALSPA CE1x00 - AO4632 - 4 Analog Outputs, 16bits, Voltage current – Datasheet 49
ALSPA CE1x00 - AI4632 - 4 Analog inputs, 16bits, Voltage current – Datasheet 51
ALSPA CE1x00 - DO9322 - 12 Digital Outputs 24VDC Source, 1Wire – Datasheet 53
ALSPA CE1x00 - DI9372 - 12 digital inputs 24VDC Source, 1 Wire – Datasheet 55
ALSPA CE1x00 - DI9371 - 12 digital inputs 24VDC Sink, 1 Wire – Datasheet 57
ALSPA CE1x00 – PS3300 - Power Supply – Datasheet 59
ALSPA CE1000 - BB80 - Bus Base – Datasheet 61
ALSPA CE1x00 - BM11- Bus Module – Datasheet 63
ALSPA CE1x00 - BM01 - Bus Module – Datasheet 65
ALSPA CE1x00 - TB12 -Terminal Block – Datasheet 67
HMI IPC ADVANTCH UNO-2473G – Datasheet 69
HMI Screen FPM-5151G_datasheet 71
Electrical measurement S7-330 –datasheet 73
Synchronizer WOODWARD-SPM-D2-10_YB –datasheet 77
Trip relay MVAJ05.10.20_EN –datasheet 81
BSS-3 GPS EN –datasheet 90
Dell-Precision - Workstation - T5810 – Datasheet 98
Dell- PowerEdge R630 Sever-Spec-Sheet 100
Dell Precision Tower 3000 Series (3620) Spec_sheet 102
Dell Precision 15 7000 Series (7510) Spec Sheet 104
Latitude_15_5000_Series_(E5570)_Spec_Sheet 106
SPR-A3-LCOLOR HP-5525dn – Datasheet 109
PR-A4-LCOLOR-110 - Printer laserjet Pro 400 M451DN – Datasheet 115
Cisco firewall ASA5506-SEC-BUN-K9– Datasheet 123

CSCS MAIN EQUIPMENT DATASHEETS .3/C


TriAn Replaced Devices List Compared with Contract
Item Contract model Description Contract Page Replaced Model Qty Replaced Reason
2.5 ‐ Detail list of equipment ‐ Appendix 5;
1 DELL Precision M4800  Engineering workstations(Laptop) Page: 4 DELL Precision 5510 1 Out of production
2.9 ‐ Attached tools ‐ Appendix 9
2 DELL E6540 or Equivalent Maintenance tools Page: 3 DELL E5570 2 Out of production
2.5 ‐ Detail list of equipment ‐ Appendix 5; CISCO ASA5506‐SEC‐
3 CISCO ASA5505‐SEC‐BUN‐K9 Network Firewall Page: 6 BUN‐K9 1 Out of production
2.5 ‐ Detail list of equipment ‐ Appendix 5;
4 HP 5500dn Report Printers Page: 7 HP CP5225dn 2 Out of production
2.5 ‐ Detail list of equipment ‐ Appendix 5;
5 HP M451dn Fault‐Event Printers Page: 7 HP M452dn 2 Out of production
DELL Desktop Computer 2.2 ‐ Performance guarantees and technical particulars ‐ 
6 DELL T3600 Online Monitoring Station Appendix 2 Page: 18 DELL T5810 1 Out of production
DELL Desktop Computer 2.2 ‐ Performance guarantees and technical particulars ‐ 
7 DELL T1700 Shift Engineer Station Appendix 2 Page: 19 DELL T3620 1 Out of production
DELL Desktop Computer 2.2 ‐ Performance guarantees and technical particulars ‐ 
8 DELL T1700 Chief Engineer Station Appendix 2 Page: 20 DELL T3620 1 Out of production
9
10
11
12
13
14
15
DIN Series 75~960W Slim and High Efficiency

Features
• High efficiency up to 94%
• Universal AC input / Full range (SDR-75/120/240/480)
AC input 180~264VAC only (S DR-960)
• Built-in active PFC function (SDR-120/240/480/960)
• Protections: Short circuit / Overload /
Over voltage / Over temperature
• Cooling by free air convection
• Can be installed on DIN rail TS-35 / 7. 5 or 15
• UL508(industrial control equipment) approved
• EN61000-6-2(EN50082-2) industrial immunity level
• Built-in DC OK relay contact (except f or SDR- 75)
• 150% peak load capability (SDR-75/120/240/480)
SDR-75 SDR-120 SDR-240 SDR-480 P SDR-960
130% peak load capability (SDR-960)
• Current sharing up to 3840W (7+1) fo r SDR- 480P
Current sharing up to 3840W (3+1) fo r SDR- 960
• Comply with GL (S DR-120/240/480)
Comply with SEMI F47 (S DR-75/120/ 240/ 480)
• 3 years warranty
General Specification (Please refer to www.meanwell.com for detail spec.)
M o d e l No. SDR- 75 SDR- 120 SDR-240 SDR-480 SDR-960
AC i n p u t v o lt a g e r a n g e 88~ 264VAC; 124~ 370VDC 90~264VAC; 127~370VDC 1 8 0 ~ 2 6 4 VA C ; 2 5 4 ~ 3 7 0 VD C
Cold s t ar t , Cold s t ar t , C o l d st a r t , C o l d st a r t , C o l d st a r t ,
AC i n r u s h c u r r e n t ( ma x .)
50A at 230VAC 70A at 230VAC 6 5 A a t 2 3 0 VA C 8 0 A a t 2 3 0 VA C 5 0 A a t 2 3 0 VA C
DC a d j u s t me n t r a n g e 12V: 12~ 14V ( only f or SDR- 75/ 1 2 0 ) , 2 4 V: 2 4 ~ 2 8 V, 4 8 V: 4 8 ~ 5 5 V
Normally works within 105%~130%
rated output power for 3 seconds
Normally works within 110%~150% rated output power for 3 seconds and then
and then shut down o/p voltage with
shut down output voltage with auto-recovery (re-power on to recover for SDR-75)
auto-recovery after 30 seconds if the
Ov e r l o a d p r o t e c t io n peak load condition is removed
Constant current limiting within
>150% rated power or short circuit, constant current limiting with auto-recovery 130%~150% rated output power for
within 2 seconds and may cause to shut down if over 2 seconds more than 3 seconds and then shut
down o/p voltage, re-power on to
recover
Range 14~ 17V f or 12V m odel( SDR- 75/ 1 2 0 ) , 2 9 ~ 3 3 V f o r 2 4 V mo d e l , 5 6 ~ 6 5 V f o r 4 8 V mo d e l
Over voltage
Shut down o/p voltage,
protection Type Shut down o/p voltage with auto-recovery, or re-power on to recover
re-power on to recover
Re- power on t o
Over temperature protection Recovers automatically after temperature goes down
recover
W i t h s t and v o lt a g e I / P- O / P: 3k VAC, I / P- FG : 1. 5k VAC , O/ P - F G: 0 . 5 kVA C , O/ P - D C OK : 0 . 5 kVA C ( e xce p t f o r S D R - 7 5 )
W o r ki n g t e m p e r a t u r e - 30~ + 70°C - 25~ + 70°C ( r e f e r t o o u t p u t d e r a t i n g cu r ve ) -30~+70°C
S af e t y s t a n d a r d s UL508, TUV EN60950- 1, G L ( SD R - 1 2 0 / 2 4 0 / 4 8 0 ) a p p r o ve d
EN55011( SDR- 120/ 240/ 480) , EN 5 5 0 2 2 cl a ss B , E N 6 1 0 0 0 - 3 - 2 , 3 , E N 6 1 0 0 0 - 4 - 2 , 3 , 4 , 5 , 6 , 8 , 11,
E M C s t and a r d s
EN61000- 6- 2 ( EN50082- 2) , EN6 1 2 0 4 - 3 ; S E MI ( S D R - 7 5 / 1 2 0 / 2 4 0 / 4 8 0 ) , GL ( S D R - 1 2 0 / 2 4 0 / 4 8 0 )
Co n n e c tio n
I/P: 3 poles, O/P: 4 poles I/P: 3 poles, O/P: 6 poles I/P: 3 poles, O/P: 8 poles I / P : 3 poles, O/P: 6 poles
(scr e w D IN te r m in a l)
Di m e n s i on ( Wx H x D ) ( mm) 32x125.2x102 40x125.2x113.5 63x 125.2x113.5 85.5x125.2x128.5 110x125.2x150

SDR-75 Series SE
M
I F4
PQ

7
SDR-240 Series GL
Marine
SE
M
I F4
PQ

Model No. Output Tol. R&N Effi.


Model No. Output Tol. R&N Effi. SDR-240-24 2 4 V, 0 ~ 1 0 A ±1 . 0 % 1 0 0 mV 94%
S DR- 7 5 - 1 2 1 2 V, 0 ~ 6. 3A ± 1. 0% 100m V 88.5% SDR-240-48 4 8 V, 0 ~ 5 A ±1 . 0 % 1 2 0 mV 94%
S DR- 7 5 - 2 4 2 4 V, 0 ~ 3. 2A ± 1. 0% 100m V 89.0%
SDR-480 Series GL
Marine
SE
M
I F4
PQ

S DR- 7 5 - 4 8 4 8 V, 0~ 1. 6A ± 1. 0% 120m V 90.0%


Model No. Output Tol. R&N Effi.
SDR-480 -24 2 4 V, 0 ~ 2 0 A ±1 . 2 % 1 0 0 mV 94%
SDR-120 Series GL
Marine
SE
M
I F4
PQ

7 SDR-480 -48 4 8 V, 0 ~ 1 0 A ±1 . 0 % 1 2 0 mV 94%


=blank, P ; Blank: basic function, P: with parallel function
Model No. Output Tol. R&N Effi.
SDR-960 Series
S DR- 12 0 - 1 2 1 2 V, 0~ 10A ± 1. 0% 100m V 89.0%
S DR- 12 0 - 2 4 2 4 V, 0~ 5A ± 1. 0% 100m V 91.0% Model No. Output Tol. R&N Effi.
SDR-960-24 2 4 V, 0 ~ 4 0 A ±1 . 0 % 1 8 0 mV 94%
S DR- 12 0 - 4 8 4 8 V, 0~ 2. 5A ± 1. 0% 120m V 90.5%
SDR-960-48 4 8 V, 0 ~ 2 0 A ±1 . 0 % 2 5 0 mV 94%

30
 3+&'/$I):'#&:8; :F-&,"GG'%&'  *+,-/01/

%)( 8,9 ''

94 ! 
: +07 7; 8,
7 <(=0 =00 )=0
 )! 0
: + )
! 61 <+=- 

>?@A  .B0
/3
+3+A/@+B  0
: +6C 

9   !+
'
 



 

 


  *+,-*.+  *+,-*+,

 
 
  
 
   
 
  
  3  3
  

  
31 $%5

  2
&'(! .  )0) 
 )0)

   

 

 
  3 
 
  
 

  
 
    
    

     ! 
 

   " 
 
  
# $   


  ! 
   
   $  ! 
   !   

 
    !    
 
 !   
 
8#(-#4-&,&'#$))-$###$,' $%'',$',-' )./$-&,0#$%.$#(



J#$)-$#%''%##$'&&&'/-&,0#$%.$#(-&,&'
$%''(%$,-'&.$#
$%'

 

 


 
"#$%&'()$*+,-' )./$-&,0#$%.$#(##$0)-$#'#$%.$#(
12+3*$$%',$&'4)-$#-&%,5

   
"#$%&'()$*+,-' )./$#$%.$#&%($#$)$##$/$-'
  

$
   &'(!  %    %    %  #$&&.$

    % 0
=1;$$#>$#&'/#.$>5

    $
;''0%'$'&'/
 
 
     $ 0= ;
 
   1
) 
)'$'*
?&' %(%$&'$%,'/@ABC$9D'&'/*)&'%$:7 0
0
 $    6 26 780))#.$91$$78
05
   
  : "0I "* E : "0G?*
E I "0G?*E I "0IE*E 
 $2

 
   : "0I ": "0G?I "0G?*JDI,   
 ;
    
)&'%$7878

1:+";

578
0 <780 0
0
 +!
)&'%$7800
  78
7800
178
0
578
0 ,$.(&'#($.$%#&$#& 
    $
+7D:G?F))#.$
) 
E,#&'D:F0<E0
G1
5

   
H

H
13HH5
  E/9 )%   E/ 6G2


     !
 " #$%& !'(!)
*'+''(
 #,-   
      )  ) 
, (' '((' !   . (  .!+ ( 
/$0
 1   ,(!(  )('(  '(  '
1(20(
 
3 4'5 (0)'( 5('
- 6)! '0 ) 7 (4()0  
 
 
 3+&'/$I):'#&:8; :F-&,"GG'%&'  *+,-/01/
45'614'7 41814'16 $8  6'&*






2<

=  L
IE
2<


IE
 




2$#&'"&'8 &/'$'12<5
"&'8 &/'$'
 G?

 8
 F


2$#&'"&'8 &/'$'12<
5
"&'8 &/'$'
D:++:<F7:80; :F*2+  I;2+   
I62"62=
 I62"620
 ;$('%
 8

)74: 1';0'&

IE

7D:G:F27; "G "I37; ;72:G:7;+ =


: " K +3:2:8? K
:;6:2 0
;72:G:7;+ G:F27;
I"
6 " IF"
G? 7272:I8
"3DK"G :;6:2
"G I82;IF
I82;IF
I "


7'6'4

'%$ "+6#'' IE


'%I)$' "+6#' G&
'%;&'/1C5   #$&&.$

 
 
 3+&'/$I):'#&:8; :F-&,"GG'%&'  *+,-/01/
':'>16;
15 1
5


3 
3

 3
3
$% $% $% $%

0'16;=0?
= =>0'16;16 =?7';





 G# $%1()5


 

 <!


 <!


 '&'




0
  
      1 7;2: F5      



 )    !   


 !-@

 
 
ALSPA Series 6
ALSPA S8000 Process Bus
EDS-408A-MM-SC - Ethernet Switch

Datasheet

2011-05-30
UXA100257 en Rev. A

EDS-408A-MM-SC - Ethernet Switch EDS-408A-MM-SC - Ethernet Switch


In the ALSPA Series 6 Control System, the EDS-408A-MM-
SC is the entry-level Ethernet switch that provides a flexible
solution for designing the S8000-E (Ethernet technology)
network in compliance with IEEE 802.3 based on fiber optic
technology in 100Mbits/s.
6 twisted pair ports (RJ45 Connector) based on
10/100BaseT(X), to connect terminals, controllers or other
twisted pair segments.
2 Multi Mode optic ports (SC/ST Connector) of 100Mbit/s
based on 100BASE-FX, multimode fiber cables, to connect
Ring or chain optic network.
The switch supports many useful functions including the
Ring/BUS, which can be set up easily using the web-based
management interface, or with DIP switches located on the
top panel of the EDS-408A-MM-SC switch.

FEATURES EDS-408A-MM-SC - Ethernet Switch


Reference Alstom EDS-408A-MM-SC – Part number: E52L0606050
Manufacturer MOXA - EDS-408A-MM-SC
Technology Protocols SNMPv1/v2c/v3, DHCP Server/Client, TFTP, SNTP, SMTP, RARP, RMON,
HTTP, Telnet, Syslog, DHCP Option 66/67/82, BootP, LLDP, Modbus/TCP,
IPv6
MIB MIB-II, Ethernet-Like MIB, P-BRIDGE MIB, Bridge MIB, RSTP MIB, RMON
MIB Group 1, 2, 3, 9
Flow Control IEEE 802.3x flow control, back pressure flow control
Switch Properties MAC Table Size 8K
Packet Buffer Size 1 Mbit
Interface Fiber Ports 2 x2 100BaseFX ports (SC/ST connector) for multimode protocol
RJ45 Ports 6 x 10/100BaseT(X) ports with auto negotiation speed, Full/Half duplex
mode, and auto MDI/MDI-X connection
Console Port 1 x RS-232 (RJ45 connector)
DIP Switches Turbo Ring, Master, Coupler, Reserve
LED Indicators PWR1, PWR2, FAULT, MSTR/HEAD, CPLR/TAIL, 10/100M
Alarm Contact 1 relay output with current carrying capacity of 1 A @ 24 VDC

© ALSTOM 2011. All rights reserved. The ALSTOM logo and any alternative version thereof are trademarks and service marks of ALSTOM. The other names mentioned, registered or not, are the
property of their respective companies. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given
or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. 1/2
ALSTOM Power PAC - Power Automation & Controls - Customer Support :+33 (0)1 60 13 43 91 -helpdesk.control-systems@power.alstom.com
ALSPA S8000 Process Bus
EDS-408A-MM-SC - Ethernet Switch

2011-05-30
UXA100257 en Rev. A

Optical Fib 100BaseFX Multi mode Single mode


Wavelength 1300 nm 1310 nm
Max / Min. TX -10 /-20 dBm 0 /-5 dBm
RX Sensitivity -32 dBm -34 dBm
Link Budget 12 dB 29 dB
Typical Distance 5 km (50/125 um multimode) 40 km (9/125 um monomode)
4 km (62.5/125 um multimode)
Saturation -6 dBm -3 dBm
Power Requirements Input Voltage 24 VDC (12 to 45 VDC), redundant dual inputs
Input Current 0.35 A @ 24 V
Protection Overload Current and Reverse Polarity
Connection 1 removable 6-contact terminal block
EMS EN61000-4-2 (ESD), level 3; EN61000-4-3 (RS), level 3;
EN61000-4-4 (EFT), level 3; EN61000-4-5 (Surge), level 3;
EN61000-4-6 (CS), level 3; EN61000-4-8
Maritime DNV, GL
Rail Traffic EN50121-4
Shock; Freefall; Vibration IEC 60068-2-27 ; IEC 60068-2-32 ; IEC 60068-2-6
Physical Housing Metal, IP30 protection
Dimensions 53.6 x 135 x 105 mm (2.11 x 5.31 x 4.13 in)
Weight 650 g
Installation DIN-Rail mounting, wall mounting (with optional kit)
Environmental Limits Operating Temperature Standard Models: 0 to 60°C (32 to 140°F)
Wide Temp. Models: -40 to 75°C (-40 to 167°F)

Storage Temperature -40 to 85°C (-40 to 185°F)


Ambient Relative Humidity 5 to 95% (non-condensing)
Regulatory Approvals Safety UL508, UL60950-1, CSA C22.2 No. 60950-1, EN60950-1
Hazardous Location UL/cUL Class I, Division 2, Groups A, B, C, and D (EDS-408A-
3M/3S/2M1S/1M2S Pending); ATEX Zone 2, Ex nC IIC (EDS-408A-
3M/3S/2M1S/1M2S Pending)
EMI FCC Part 15, CISPR (EN55022) class A
MTBF Meantime Between 363,000 hrs
Failures

© ALSTOM 2011. All rights reserved. The ALSTOM logo and any alternative version thereof are trademarks and service marks of ALSTOM. The other names mentioned, registered or not, are the
property of their respective companies. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given
or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. 2/2
ALSTOM Power PAC - Power Automation & Controls - Customer Support :+33 (0)1 60 13 43 91 -helpdesk.control-systems@power.alstom.com
EDS-518E Series
Hardware Installation Guide
Moxa EtherDevice™ Switch

First Edition, December 2014

 2014 Moxa Inc. All rights reserved.

P/N: 1802005180020
Package Checklist
The EDS-518E is shipped with the following items. If any of these items
are missing or damaged, please contact your customer service
representative for assistance.
• 1 EDS-518E Ethernet switch
• USB cable
• Protective caps for unused ports
• Hardware installation guide
• Documentation and software CD
• Moxa product warranty statement

Features
• 4 Gigabit combo Ethernet ports plus 14 Fast Ethernet ports for copper
and fiber
• Turbo Ring and Turbo Chain (recovery time < 20 ms @ 250 switches),
RSTP/STP, and MSTP for network redundancy
• RADIUS, TACACS+, SNMPv3, IEEE 802.1x, HTTPS, and SSH to
enhance network security
• EtherNet/IP, PROFINET, and Modbus/TCP protocols supported for
device management and monitoring

-2-
Panel Views of EDS-518E
1. Reset button
2. USB console port
3. DIP switches for Turbo Ring, Ring
Master, and Ring Coupler
4. Grounding screw
5. 4-pin terminal block for digital
input and power input 2
6. 4-pin terminal block for relay
output and power input 1
7. 10/100BaseT(X) port, ports 1 to
14
8. 100BaseT(X) LED indicator
9. 10BaseT(X) LED indicator
10. System status LED:
• STATE LED indicator
• PWR1 LED indicator
• PWR2 LED indicator
• FAULT LED indicator
• MSTR/HEAD LED indicator
• CPLR/TAIL LED indicator
11. USB storage port
12. G1 to G4 ports LED indicator
13. 10/100/1000BaseT(X) or
100/1000BaseSFP combo port,
ports G1 to G4
14. Model Name
15. Screw hole for Wall Mounting Kit
16. DIN-Rail Kit

-3-
Panel Views of EDS-518E (SC/ST Type)
NOTE:
The appearance of EDS-518E-SS-SC
is identical to EDS-518E-MM-SC.
The appearance of
EDS-518E-MM-ST is identical to
EDS-518E-MM-SC.

1. Reset button
2. USB console port
3. DIP switches for Turbo Ring, Ring
Master, and Ring Coupler
4. Grounding screw
5. 4-pin terminal block for digital
input and power input 2
6. 4-pin terminal block for relay
output and power input 1
7. 100BaseFX port LED indicator:
13, 14
8. 100BaseFX port (SC type), ports
13, 14
9. 10/100BaseT(X) port, ports 1 to
12
10. 100BaseT(X) LED indicator
11. 10BaseT(X) LED indicator
12. System status LED:
• STATE LED indicator
• PWR1 LED indicator
• PWR2 LED indicator
• FAULT LED indicator
• MSTR/HEAD LED indicator
• CPLR/TAIL LED indicator
13. USB storage port
14. G1 to G4 ports LED indicator
15. 10/100/1000BaseT(X) or
100/1000BaseSFP combo port,
ports G1 to G4
16. Model Name
17. Screw hole for Wall Mounting Kit
18. DIN-Rail Kit

-4-
Mounting Dimensions
Unit = mm (inch)

-5-
DIN-Rail Mounting
The metal DIN-rail kit is fixed to the back panel of the EDS-518E when
you take it out of the box. Mount the EDS-518E on corrosion-free
mounting rails that meet the EN 60715 standard.

Installation

STEP 1: Insert the upper lip of the DIN rail into the DIN-rail mounting kit.
STEP 2: Press the EDS-518E series towards the DIN rail until it snaps into
place.

Removal
STEP 1: Pull down the latch on the mounting kit with a screwdriver.
STEPS 2 & 3: Pull the EDS-518E forward slightly and then lift up to
remove it from the DIN rail.

ATTENTION
1. These devices are open-type devices that are to be installed
in an enclosure with tool removable cover or door suitable
for the environment at that location.
2. This equipment is suitable for use in Class I, Division 2,
Groups A, B, C, and D or non-hazardous locations only.

-6-
Wall Mounting (Optional)
For some applications, you will find it convenient to mount the Moxa
EDS-518E on a wall, as shown in the following illustrations:
STEP 1: Remove the
aluminum DIN-rail
attachment plate from the
rear panel of the EDS-518E,
and then attach the wall
mount plates with M3 screws,
as shown in the figure at the
right.

STEP 2: Mounting the EDS-518E series on a wall


requires 4 screws. Use the EDS-518E, with wall mount
plates attached, as a guide to mark the correct locations
of the 4 screws. The heads of the screws should be less
than 6.0 mm in diameter, and the shafts should be less
than 3.5 mm in diameter, as shown in the figure on at the
right.

NOTE Before tightening the screws into the wall, make sure the screw
head and shank size are suitable by inserting the screw through
one of the keyhole-shaped apertures of the wall mount plates.

Do not screw the screws in all the way—leave about 2 mm to allow room
for sliding the wall mount panel between the wall and the screws.
STEP 3: Once the screws are
fixed to the wall, insert the four
screw heads through the wide
parts of the keyhole-shaped
apertures, and then slide the
EDS-518E downwards, as
indicated in the figure at the
right. Tighten the four screws for
greater stability.

WARNING
1. EXPLOSION HAZARD—Do not disconnect equipment unless
power has been removed or the area is known to be
non-hazardous.
2. EXPLOSION HAZARD—Substitution of any components may
impair suitability for Class I, Division 2.
3. EXPOSURE TO SOME CHEMICALS MAY DEGRADE THE
SEALING PROPERTIES OF MATERIALS USED IN THE RELAY.

-7-
Wiring Requirements

WARNING
Do not disconnect modules or wires unless power has been
switched off or the area is known to be non-hazardous. The
devices may only be connected to the supply voltage shown on
the type plate. The devices are designed for operation with a
Safety Extra-Low Voltage. Thus, they may only be connected to
the supply voltage connections and to the signal contact with the
Safety Extra-Low Voltages (SELV) in compliance with IEC950/
EN60950/ VDE0805.

ATTENTION
This unit is a built-in type. When the unit is installed in another
piece of equipment, the equipment enclosing the unit must
comply with fire enclosure regulation IEC 60950/EN60950 (or
similar regulation).

ATTENTION
Safety First!
Be sure to disconnect the power cord before installing and/or
wiring your EDS-518E.
Calculate the maximum possible current in each power wire and
common wire. Observe all electrical codes dictating the
maximum current allowable for each wire size.
If the current goes above the maximum ratings, the wiring could
overheat, causing serious damage to your equipment.

Please read and follow these guidelines:


• Use separate paths to route wiring for power and devices. If power
wiring and device wiring paths must cross, make sure the wires are
perpendicular at the intersection point.
NOTE: Do not run signal or communications wiring and power wiring
through the same wire conduit. To avoid interference, wires with
different signal characteristics should be routed separately
• You can use the type of signal transmitted through a wire to
determine which wires should be kept separate. The rule of thumb is
that wiring that shares similar electrical characteristics can be
bundled together
• You should separate input wiring from output wiring
• We advise that you label the wiring to all devices in the system.

-8-
Grounding the Moxa EDS-518E
Grounding and wire routing help limit the effects of noise due to
electromagnetic interference (EMI). Run the ground connection from the
ground screw to the grounding surface prior to connecting devices.

ATTENTION
This product is intended to be mounted to a well-grounded
mounting surface such as a metal panel.

Wiring the Relay Contact


The EDS-518E series has one relay output. This relay contact uses two
contacts of the terminal block on the EDS-518E’s top panel. Refer to the
next section for detailed instructions on how to connect the wires to the
terminal block connector, and how to attach the terminal block connector
to the terminal block receptor. In this section, we illustrate the meaning
of the two contacts used to connect the relay contact.
FAULT:
The two contacts of the 4-pin terminal
block connector are used to detect
user-configured events. The two wires
attached to the fault contacts form an
open circuit when a user-configured
event is triggered. If a user-configured
event does not occur, the fault circuit
remains closed.

Wiring the Redundant Power Inputs


The EDS-518E has two sets of power inputs—power input 1 and power
input 2. The top view of the terminal block connectors is shown here.
STEP 1: Insert the negative/positive DC
wires into the V-/V+ terminals,
respectively.
STEP 2: To keep the DC wires from
pulling loose, use a small flat-blade
screwdriver to tighten the wire-clamp
screws on the front of the terminal block
connector.
STEP 3: Insert the plastic terminal block
connector prongs into the terminal block
receptor, which is located on the
EDS-518E’s top panel.

-9-
Wiring the Digital Inputs
The EDS-518E has one digital input (DI). The DI consists of two contacts
of the 4-pin terminal block connector on the EDS-518E’s top panel, which
are used for the two DC inputs. The top view of the terminal block
connectors is shown here.
STEP 1: Insert the negative
(ground)/positive DI wires into the
┴/I terminals, respectively.
STEP 2: To keep the DI wires from
pulling loose, use a small flat-blade
screwdriver to tighten the wire-clamp
screws on the front of the terminal block
connector.
STEP 3: Insert the plastic terminal block
connector prongs into the terminal block
receptor, which is located on the
EDS-518E’s top panel.

Communication Connections
Each EDS-518E switch has 4 types of communication ports:
• 1 USB console port (type B connector)
• 1 USB storage port (type A connector)
• 14 10/100BaseTX Ethernet ports (EDS-518E-4GTXSFP series) or 12
10/100BaseT(X) Ethernet ports plus 2 100BaseFX (SC/ST-type
connector) fiber ports (EDS-518E-MM-SC-4GTXSFP/
EDS-518E-SS-SC-4GTXSFP/EDS-518E-MM-ST-4GTXSFP)
• 4 Gigabit Ethernet combo ports:
4 10/100/1000BaseT(X) and 4 100/1000BaseSFP ports

USB Console Connection


The EDS-518E has one USB console port (type B connector) located on
the top panel. Use the USB cable (provided in the product package) to
connect the EDS-518E’s console port to your PC’s USB port and install the
USB driver (available on the software CD) on the PC. You may then use a
console terminal program, such as Moxa PComm Terminal Emulator, to
access the EDS-518E’s console configuration utility.
USB Console Port (Type B Connector) Pinouts

Pin Description
1 D– (Data–)
2 VCC (+5V)
3 D+ (Data+)
4 GND (Ground)

USB Storage Connection


The EDS-518E has one USB storage port (type A connector) on the front
panel. Use the Moxa ABC-02-USB-T automatic backup configurator to
connect the EDS-518E’s USB storage port for configuration backup,
firmware upgrade, or system log file backup.

- 10 -
ABC-02-USB Installation
Plug the ABC-02-USB into the USB
storage port of the Moxa EDS-518E.
The ABC-02-USB can be secured to
the wall with an M4 screw.

USB Storage Port (Type A Connector) Pinouts

Pin Description
1 VCC (+5V)
2 D– (Data–)
3 D+ (Data+)
4 GND (Ground)

10/100BaseT(X) Ethernet Port Connection


The 10/100BaseT(X) ports located on the EDS-518E’s front panel are
used to connect to Ethernet-enabled devices. Most users will choose to
configure these ports for Auto MDI/MDI-X mode, in which case the port’s
pinouts are adjusted automatically depending on the type of Ethernet
cable used (straight-through or cross-over), and the type of device
(NIC-type or HUB/Switch-type) connected to the port.
In what follows, we give pinouts for both MDI (NIC-type) ports and MDI-X
(HUB/Switch-type) ports. We also give cable wiring diagrams for
straight-through and cross-over Ethernet cables.
10/100Base T(x) RJ45 Pinouts
MDI Port Pinouts MDI-X Port Pinouts 8-pin RJ45
Pin Signal Pin Signal
1 Tx+ 1 Rx+
2 Tx- 2 Rx-
3 Rx+ 3 Tx+
6 Rx- 6 Tx-

RJ45 (8-pin) to RJ45 (8-pin) Straight-Through Cable Wiring

- 11 -
RJ45 (8-pin) to RJ45 (8-pin) Cross-Over Cable Wiring

100BaseFx Ethernet Port Connection


The concept behind the SC/ST port and cable is quite straightforward.
Suppose you are connecting devices I and II. As opposed to electrical
signals, optical signals do not require a circuit in order to transmit data.
Consequently, one of the optical lines is used to transmit data from device
I to device II, and the other optical line is used transmit data from device
II to device I, for full-duplex transmission.
All you need to remember is to connect the Tx (transmit) port of device I
to the Rx (receive) port of device II, and the Rx (receive) port of device I
to the Tx (transmit) port of device II. If you are making your own cable,
we suggest labeling the two sides of the same line with the same letter
(A-to-A and B-to-B, as shown by the following illustration, or A1-to-A2
and B1-to-B2).
SC-Port Pinouts SC-Port to SC-Port Cable Wiring

ST-Port Pinouts ST-Port to ST-Port Cable Wiring

ATTENTION
This is a Class 1 Laser/LED product. To prevent damage to your
eyes, do not stare directly into the laser beam.

- 12 -
1000BaseT Ethernet Port Connection
1000BaseT data is transmitted on differential TRD+/- signal pairs over
copper wires.
MDI/MDI-X Port Pinouts

Pin Signal
1 TRD(0)+
2 TRD(0)-
3 TRD(1)+
4 TRD(2)+
5 TRD(2)-
6 TRD(1)-
7 TRD(3)+
8 TRD(3)-

100/1000BaseSFP (mini-GBIC) Fiber Port


The Gigabit Ethernet fiber ports on the EDS-518E are 100/1000BaseSFP
fiber ports, which require using 100M or 1G mini-GBIC fiber transceivers
to work properly. Moxa provides a complete selection of transceiver
models for different distance requirements.
The concept behind the LC port and cable is straightforward. Suppose you
are connecting devices I and II; contrary to electrical signals, optical
signals do not require a circuit in order to transmit data. Consequently,
one of the optical lines is used to transmit data from device I to device II,
and the other optical line is used transmit data from device II to device I,
for full-duplex transmission.
Remember to connect the Tx (transmit) port of device I to the Rx (receive)
port of device II, and the Rx (receive) port of device I to the Tx (transmit)
port of device II. If you make your own cable, we suggest labeling the two
sides of the same line with the same letter (A-to-A and B-to-B, as shown
below, or A1-to-A2 and B1-to-B2).
LC-Port Pinouts LC-Port to LC-Port Cable Wiring

ATTENTION
This is a Class 1 Laser/LED product. To avoid causing serious
damage to your eyes, do not stare directly into the Laser Beam.

- 13 -
Reset Button
The Reset Button supports two functions. One is to reset the Ethernet
switch to factory default settings by pressing and holding the Reset
button for 5 seconds. Use a pointed object, such as a straightened paper
clip or toothpick, to depress the Reset button. This will cause the STATE
LED to blink once a second. After depressing the button for 5 continuous
seconds, the STATE LED will start to blink rapidly, indicating that factory
default settings have been loaded and you can release the reset button.
When the ABC-02-USB is connected to the EDS-518E Ethernet switch, the
reset button allows quick configuration and backs up log files to the
ABC-02-USB. Press the Reset button on top of the EDS-518E; the
Ethernet switch will start backing up the current system configuration
files and event logs to the ABC-02-USB.

NOTE Do NOT power off the Ethernet switch when loading default
settings.

Turbo Ring DIP Switch Settings


The EDS-518E switches are plug-and-play managed redundant Ethernet
switches. The proprietary Turbo Ring protocol was developed by Moxa to
provide better network reliability and faster recovery time. Moxa Turbo
Ring’s recovery time is less than 300 ms (Turbo Ring) or 20 ms (Turbo
Ring V2)—compared to a 3- to 5-minute recovery time for commercial
switches—decreasing the possible loss caused by network failures in an
industrial setting.
The 4 Hardware DIP Switches located on the top panel of the EDS-518E
can be used to easily configure Turbo Ring in only a few seconds. If you do
not want to use a hardware DIP switch to configure Turbo Ring, you can
use a web browser, Telnet, or serial console to disable the DIP switches.

NOTE Refer to the Turbo Ring section in the Communication


Redundancy User’s Manual for detailed information about the
settings and usage of Turbo Ring and Turbo Ring V2.

EDS-518E Series DIP Switches

The default setting for each DIP Switch is OFF. The


following table explains the effect of setting the DIP
Switch to the ON position.

“Turbo Ring” DIP Switch Settings


DIP 1 DIP 2 DIP 3 DIP 4
Reserved for ON: Enables this ON: Enables the ON: Activates
future use. EDS as the Ring default “Ring DIP switch 2 and
Master. Coupling” and 3 to configure
“Ring Coupling “Turbo Ring”
Control” ports. settings.
OFF: This EDS OFF: Do not use OFF: DIP switch
will not be the this EDS as the 1, 2, and 3 will be
Ring Master. ring coupler. disabled.

- 14 -
“Turbo Ring V2” DIP Switch Settings
DIP 1 DIP 2 DIP 3 DIP 4
ON: Enables the ON: Enables this ON: Enables the ON: Activates
default “Ring EDS as the Ring default “Ring DIP switch 1, 2,
Coupling Master. Coupling” port. and 3 to
(backup)” port configure “Turbo
when DIP switch Ring V2”
3 is already settings.
enabled.
OFF: Enables the OFF: This EDS OFF: Do not use OFF: DIP
default “Ring will not be the this EDS as a ring switches 1, 2,
Coupling Ring Master. coupler. and 3 will be
(primary)” port disabled.
when DIP switch
3 is already
enabled.

NOTE You must enable the Turbo Ring function first before using the
DIP switch to activate the Master and Coupler functions.

NOTE If you do not enable any of the EDS-518E series switches to be


the Ring Master, the Turbo Ring protocol will automatically
choose the EDS-518E series with the smallest MAC address range
to be the Ring Master. If you accidentally enable more than one
EDS-518E series to be the Ring Master, these EDS-518E series
switches will auto-negotiate to determine which one will be the
Ring Master.

LED Indicators
The front panel of the Moxa EDS-518E has several LED indicators. The
function of each LED is described in the following table:
LED Color Status Description
The system passed the self-diagnosis test
On
on boot-up and is ready to run.
• Once every second: The switch is
Green
being reset.
Blinking
• Once every two seconds: ABC-02-USB
is connected to the switch.
STATE The system failed self-diagnosis on
boot-up.
• RAM Test Fail / System Info. Read Fail
Red On / Switch Initial Fail / PTP PHY Error.
(+ Green MSTR lit on : HW FAIL)
• FW Checksum Fail / Uncompress Fail.
(+ Green Coupler lit on: SW FAIL)
1. The signal contact is open.
2. ABC Loading/Saving Fail.
3. The port is being disabled because the
ingress multicast and broadcast
FAULT Red On
packets exceed the ingress rate limit.
4. Incorrect loop connection in a single
switch.
5. Invalid Ring port connection.

- 15 -
LED Color Status Description
Power is being supplied to the main
On
module’s power input PWR1.
PWR1 Amber
Power is not being supplied to the main
Off
module’s power input PWR1.
Power is being supplied to the main
On
module’s power input PWR2.
PWR2 Amber
Power is not being supplied to the main
Off
module’s power input PWR2.
1. The switch is set as the Master of the
Turbo Ring, or as the Head of the
On Turbo Chain.
2. POST H.W. Fail (+Stat on and Fault
blinking).
1. The switch has become the Ring
Master of the Turbo Ring.
2. The switch has become the Head of
MSTR/
Green the Turbo Chain, after the Turbo Ring
HEAD Blinking
or Turbo Chain has gone down.
3. The switch is set as the Turbo Chain’s
Member and the corresponding chain
port is down.
1. The switch is not the Master of this
Turbo Ring.
Off
2. This switch is set as a Member of the
Turbo Chain.
1. The switch’s coupling function is
enabled to form a back-up path.
2. The switch is set as the Tail of the
On
Turbo Chain.
3. POST S.W. Fail (+Stat on and Fault
blinking)
CPLR/ 1. Turbo Chain is down.
Green
TAIL 2. The switch is set as Turbo Chain’s
Blinking
Member and the corresponding chain
port is down.
1. This switch has disabled the coupling
function.
Off
2. This switch is set as a Member of the
Turbo Chain.
FAULT + Rotate
MSTR/HEAD + Blinking ABC-02-USB is importing/exporting files.
CPLR/TAIL Sequentially
STATE +
FAULT + Switch is being discovered/located by
Blinking
MSTR/HEAD + MXview (twice per second).
CPLR/TAIL
On TP port’s 10 Mbps link is active.
10M
Green Blinking Data is being transmitted at 10 Mbps.
(TP)
Off TP port’s 10 Mbps link is inactive.
100M On TP/Fixed FX port’s 100 Mbps link is active.
(TP/ Blinking Data is being transmitted at 100 Mbps.
Green
Fixed TP/Fixed FX port’s 100 Mbps link is
Off
FX) inactive.

- 16 -
LED Color Status Description
100M TP/SFP combo port’s 100 Mbps link is
On
(TP/ active.
SFP Amber Blinking Data is being transmitted at 100 Mbps.
combo TP/SFP combo port’s 100 Mbps link is
Off
ports) inactive.
1000M TP/SFP combo port’s 1000 Mbps link is
On
(TP/ active.
SFP Green Blinking Data is being transmitted at 1000 Mbps.
combo TP/SFP combo port’s 1000 Mbps link is
Off
port) inactive.

Specifications
Technology
Standards IEEE 802.3 for 10BaseT
IEEE 802.3u for 100BaseT(X) and 100BaseFX
IEEE 802.3ab for 1000BaseT(X)
IEEE 802.3z for 1000BaseX
IEEE 802.3x for Flow Control
IEEE 802.1D-2004 for Spanning Tree Protocol
IEEE 802.1w for Rapid STP
IEEE 802.1s for Multiple Spanning Tree Protocol
IEEE 802.1Q for VLAN Tagging
IEEE 802.1p for Class of Service
IEEE 802.1x for Authentication
IEEE 802.3ad for Port Trunk with LACP
Protocols IGMPv1/v2/v3, GMRP, GVRP, SNMPv1/v2c/v3,
DHCP Server/Client, DHCP Option 66/67/82, BootP,
TFTP, SNTP, SMTP, RARP, RMON, HTTP, HTTPS,
Telnet, SSH, Syslog, EtherNet/IP, PROFINET,
Modbus/TCP, SNMP Inform, LLDP, IEEE 1588 v2 PTP,
IPv6, NTP Server/Client
MIB MIB-II, Ethernet-Like MIB, P-BRIDGE MIB,
Q-BRIDGE MIB, Bridge MIB, RSTP MIB, RMON MIB
Group 1, 2, 3, 9
Flow Control IEEE 802.3x flow control, back pressure flow control
Interface
RJ45 Ports EDS-518E-MM-ST/SC-4GTXSFP and
EDS-518E-SS-SC-4GTXSFP:
10/100BaseT(X) ports: 12
10/100/1000BaseT(X) ports: 4
EDS-518E-4GTXSFP:
10/100BaseT(X) ports: 14
10/100/1000BaseT(X) ports: 4
Fiber Ports EDS-518E-MM-ST/SC-4GTXSFP and
EDS-518E-SS-SC-4GTXSFP:
100BaseFX ports (SC/ST connector): 2
100/1000BaseSFP slots: 4
USB Ports USB console port (type B connector)
USB storage port (type A connector)
Button Reset button
LED Indicators PWR1, PWR2, FAULT, STATE, 10/100M, 100/1000M,
MSTR/HEAD, CPLR/TAIL

- 17 -
Alarm Contact 1 relay output with current carrying capacity of 1 A
@ 24 VDC
Digital Input 1 input with the same ground, but electrically
isolated from the electronics.
+13 to +30 V for state “1”
-30 to +3 V for state “0”
Max. input current: 8 mA
Power
Input Voltage 12/24/48/-48 VDC, redundant dual inputs
Input Current EDS-518E-4GTXSFP: 0.75 A @ 24 V
EDS-518E-MM-ST/SC-4GTXSFP: 0.61 A @ 24 V
EDS-518E-SS-SC-4GTXSFP: 0.61 A @ 24 V
Connection 2 removable 4-contact terminal blocks
Overload Current Present
Protection
Reverse Polarity Present
Protection
Physical Characteristics
Housing Metal, IP30 protection
Dimensions 94 x 135 x 138 mm (3.7 x 5.31 x 5.44 in)
Installation DIN-rail mounting, wall mounting (with optional kit)
Environmental Limits
Operating -10 to 60°C (14 to 140°F) for standard models
Temperature -40 to 75°C (-40 to 167°F) for -T models
Storage -40 to 85°C (-40 to 185°F)
Temperature
Ambient Relative 5 to 95% (non-condensing)
Humidity
Altitude Up to 2000 m
Note: Please contact Moxa if you require products
guaranteed to function properly at higher altitudes.
Regulatory Approvals
Safety UL 508
EMI FCC Part 15 Subpart B Class A, EN 55022 Class A
EMS EN 61000-4-2 (ESD) Level 4, EN 61000-4-3 (RS)
Level 3, EN 61000-4-4 (EFT) Level 4, EN 61000-4-5
(Surge) Level 4, EN 61000-4-6 (CS) Level 3, EN
61000-4-8
Shock IEC 60068-2-27
Free Fall IEC 60068-2-32
Vibration IEC 60068-2-6
Warranty
Warranty 5 years

Technical Support Contact Information


www.moxa.com/support

Moxa Americas: Moxa China (Shanghai office):


Toll-free: 1-888-669-2872 Toll-free: 800-820-5036
Tel: 1-714-528-6777 Tel: +86-21-5258-9955
Fax: 1-714-528-6778 Fax: +86-21-5258-5505
Moxa Europe: Moxa Asia-Pacific:
Tel: +49-89-3 70 03 99-0 Tel: +886-2-8919-1230
Fax: +49-89-3 70 03 99-99 Fax: +886-2-8919-1231

- 18 -
ALSPA Automation Cell
E8000 Ethernet Fieldbus Network
HB2880-Ethernet Expansion Module

Datasheet

2009-12-08
UPA100709-en-A

HB2880 – Ethernet Hub


The HB2880– Ethernet Hub is a module of the ALSPA
Ethernet Fieldbus E8000 Network (EPL Technology).
The HB2880 hub expansion module can be operated on the
BC8084 POWERLINK bus controller and on the HB8880
Ethernet Hub.
It is equipped with an integrated 2x hub.
The Ethernet connections are made using RJ45 connectors.
The module and Network status is indicated using LEDs.
• Hub expansion module
• 2x Fast Ethernet hub
• Hot-swap capable

FEATURES HB2880

Interface Type Ethernet

Standard (compliance) ANSI/IEEE 802.3

Signal 10/100 Base-T

Port design Shielded RJ45 ports


10 MBit/s or 100 MBit/s
Transfer rate Devices with 10/100 MBit/s auto-negotiation are operated at
100 MBit/s
Cable length Max. 100 m between two stations (segment length)

General information Status indicators Module status, bus function


Module status: Yes, with status LED
Diagnostics
Bus function: Yes, with status LED
Electrical isolation Fieldbus supply: Yes
Power consumption of
1,17 W
the bus
Certification CE, C-UL-US, GOST-R

Datasheet_Template_RevH (PTP20A43015 en H) - Copyright © ALSTOM 2009. ALSTOM, the ALSTOM logo and any alternative version thereof are trademarks and
service marks of ALSTOM. The other names mentioned, registered or not, are the property of their respective companies. The technical and other data contained in this
document is provided for information only. Neither ALSTOM, its officers and employees accept responsibility for or should be taken as making any representation or
warranty (whether express or implied) as to the accuracy or completeness of such data or the achievement of any projected performance criteria where these are
1/1
indicated. ALSTOM reserves the right to revise or change this data at any time without further notice. helpdesk.control-systems@power.alstom.com
E8000 Ethernet Fieldbus Network
HB2880-Ethernet Expansion Module

2009-12-08
UPA100709-en-A

Horizontal Installation: 00C to +550C


Operational conditions Operating temperature
Vertical Installation: 00C to +500C
Relative humidity 5 to 95% (non-condensing)

Mounting orientation Horizontal or vertical


0 – 2000m: No derating
Installation at altitudes
>2000m: Reduction of ambient temperature by
above sea level
0.5 °C per 100m
Protection type IP20
Storage and transport
Temperature -250C to +700C
conditions
Relative humidity 5 to 95% (non-condensing)
Mechanical
Slot Hub expansion for BC8084 and HB8880
characteristics
Status LED LED Color Status Description
s ERR Red On Slot not detected

RDY Orange On Slot detected, module is active

A link to the remote station has been


On
established.
L/A IFx Green A link to the remote station has been
Blinking established. The LED blinks when Ethernet
activity is present on the bus.
Operating and
connection elements

Copyright © ALSTOM 2009.


ALSTOM Power Energy Management Business 9, rue Ampère 91345 MASSY Cedex France 2/2
Customer Support: helpdesk.control-systems@power.alstom.com www.power.alstom.com x
ALSPA Automation Cell
Ethernet Fieldbus E8000 Network
HB8884 - Powerlink Link Selector

Datasheet

2009-10-23
PTP20A43173 en Rev B

HB8884 – Powerlink Link Selector


The HB8884 – Powerlink Link Selector is a module of the
ALSPA E8000 Ethernet fieldbus (EPL Technology).
The HB8884 module is a Ethernet fieldbus link selector
interface with POWERLINK V2, it provides supports
expansion with active CE1000 hub modules, status
indicator LEDs and 2 x RJ45 connections.
Compact link selector function
2 active hub expansion modules can be connected to the
bus controller
Redundant supply possible

FEATURES HB8884

POWERLINK compact Connecting POWERLINK V2 devices to a redundant


Short description
link selector POWERLINK V2 network
Fieldbus Type POWERLINK V2 100 Base-T (ANSI/IEE 802.3)
Controller, Processor,
EPL MAC, 32 Bit RISC, 512KB
Memory
Design Internal 2x hub, 2x shielded RJ45 port

Cable length Max. 100 m between two stations (segment length)

Transfer rate 100 MBit/s

General information Status indicators Module status, bus function


Module status: Yes, with status LED and software status
Diagnostics
Bus function: Yes, with status LED and software status
Fieldbus supply: Yes
Electrical isolation

Power consumption of
2.0 W
the bus
Certification CE, C-UL-US, GOST-R

Datasheet_Template_RevH (PTP20A43015 en H) - Copyright © ALSTOM 2009. ALSTOM, the ALSTOM logo and any alternative version thereof are trademarks and
service marks of ALSTOM. The other names mentioned, registered or not, are the property of their respective companies. The technical and other data contained in this
document is provided for information only. Neither ALSTOM, its officers and employees accept responsibility for or should be taken as making any representation or
warranty (whether express or implied) as to the accuracy or completeness of such data or the achievement of any projected performance criteria where these are
1/2
indicated. ALSTOM reserves the right to revise or change this data at any time without further notice. helpdesk.control-systems@power.alstom.com
Ethernet Fieldbus E8000 Network
HB8884 - Powerlink Link Selector

2009-10-23
PTP20A43173 en Rev B

Horizontal Installation: 00C to +550C


Operational conditions Operating temperature
Vertical Installation: 00C to +500C
Relative humidity 5 to 95% (non-condensing)

Mounting orientation Horizontal or vertical


0 – 2000m: No derating
Installation at altitudes
>2000m: Reduction of ambient temperature by
above sea level
0.5 °C per 100m
Protection type IP20
Storage and transport
Temperature -250C to +700C
conditions
Relative humidity 5 to 95% (non-condensing)

Mechanical X20BB81: 62.5 +0.2 mm


Spacing
characteristics X20BB82: 87.5 +0.2 mm

Status LEDs S/E Green – Status /red - Error

Blinking : A link to the remote station has been established.


L/A IFx (Green)
The LED blinks when Ethernet activity is present on the bus.
Operating and
connection elements

Copyright © ALSTOM 2009.


ALSTOM Power Energy Management Business 9, rue Ampère 91345 MASSY Cedex France 2/2
Customer Support: helpdesk.control-systems@power.alstom.com www.power.alstom.com x
FL HUB 8/16TX-ZF

Ethernet Hub With 8 or 16 RJ45 Ports

AUTOMATIONWORX
Data Sheet
7179_en_03 © PHOENIX CONTACT - 03/2007

Description
The hub is used for quick and cost-effective Ethernet net- Application:
work expansion. It has 8 or 16 twisted pair ports, which can – Simple expansion of networks without configuration.
be connected to additional network segments or termination – Using a standard system cabling
devices.
Local Diagnostic and Status Indicators
The Product Short Description supports Ethernet with
10 Mbps as well as with 100 Mbps. Des. Color Meaning
PWR Green Supply voltage
The hub regenerates the received signal levels. The re-
ceived data telegrams are send to the remaining ports. COL Yellow Telegram collision
One LED per port
For port 5, a port assignment switch is located on the hub.
Green Link active
The transmit and receive cables are exchanged at port 5 by
actuating the switch while polarity is maintained. Yellow Receiving telegrams

Please note that all devices connected to the hub are operated at the same data transmission rate.

Make sure you always use the latest documentation.


It can be downloaded at www.download.phoenixcontact.com.
A conversion table is available on the Internet at
www.download.phoenixcontact.com/general/7000_en_00.pdf.

This data sheet is valid for the products listed on the last page.
FL HUB 8/16TX-ZF

Ordering Data
Products
Description Type Order No. Pcs./Pkt.
Ethernet hub with 8 ports FL HUB 8TX-ZF 2832551 1
Ethernet hub with 16 ports FL HUB 16TX-ZF 2832564 1

Accessories
Description Type Order No. Pcs./Pkt.
Patch box 8 x RJ45 CAT5e pre-assembled, can be retrofitted FL PBX 8TX 2832496 1
Patch box 6 x RJ45 CAT5e and 4 SC-RJ, glass pre-assembled, FL PBX 6TX/4FX 2832506 1
can be retrofitted
Patch cable, CAT 5, pre-assembled, 0.3 m long FL CAT5 PATCH 0.3 2832250 10
Patch cable, CAT 5, pre-assembled, 0.5 m long FL CAT5 PATCH 0.5 2832263 10
Patch cable, CAT 5, pre-assembled, 1.0 m long FL CAT5 PATCH 1.0 2832276 10
Patch cable, CAT 5, pre-assembled, 1.5 m long FL CAT5 PATCH 1.5 2832221 10
Patch cable, CAT 5, pre-assembled, 2.0 m long FL CAT5 PATCH 2.0 2832289 10
Patch cable, CAT 5, pre-assembled, 3.0 m long FL CAT5 PATCH 3.0 2832292 10
Patch cable, CAT 5, pre-assembled, 5.0 m long FL CAT5 PATCH 5.0 2832580 10
Patch cable, CAT 5, pre-assembled, 7.5 m long FL CAT5 PATCH 7.5 2832616 10
Patch cable, CAT 5, pre-assembled, 10.0 m long FL CAT5 PATCH 10 2832629 10
Dust protection caps for RJ45 sockets FL RJ45 PROTECT CAP 2832991 10

Technical Data
General Data
Function Class II repeater/hub; in acc. with IEEE 802.3, IEEE 802.3u
Mode Half duplex
Data processing Bit re-timing
Maximum data telegram length 1522 Bytes
Housing dimensions FL HUB 8TX-ZF (width x height x depth) 45 mm x 99 mm x 112 mm
Housing dimensions FL HUB 16TX-ZF (width x height x depth) 90 mm x 99 mm x 112 mm
Permissible operating temperature FL HUB 8TX-ZF 0°C to 60°C
Permissible operating temperature FL HUB 16TX-ZF 0°C to 55°C
Permissible storage temperature -25°C up to +70°C
Degree of protection IP20, DIN 40050, IEC 60529
Class of protection Class 3 VDE 0106; IEC 60536
Maximum humidity (operation) 100%
Maximum humidity (storage/transport) 95% not condensing
Air pressure (operation) 81 kPa to 108 kPa, 2,000 m above sea level
Air pressure (storage) 66 kPa to 108 kPa, 3,500 m above sea level
Preferred mounting position Perpendicular to a standard DIN rail
Connection to protective By snapping it onto a grounded DIN rail/via COMBICON (optional)
Weight 266 g, typical (8TX)
422 g, typical (16TX)

Supply Voltage
Connection Via COMBICON;
maximum conductor cross-section = 2.5 mm2
Nominal value 24 V DC
Permissible ripple 3.6 Vpp within the permissible voltage range
Permissible voltage range 18 V DC to 32 V DC
Current consumption at nominal value of US 144 mA, typical (8TX)
230 mA, typical (16TX)

7179_en_03 PHOENIX CONTACT 2


FL HUB 8/16TX-ZF

Supply Voltage (Continued)


Test voltage 500 V DC for 1 minute
Protection against polarity reversal Present
Power consumption at nominal value of US 3.5 W, typical
5,5 W, typical

Interfaces
Ethernet interface in RJ45 format
Number 8/16
Connection format 8-pos. RJ45 socket on the hub
Connection medium Twisted pair cable with a conductor cross-section of 0.14 mm2 bis 0.22 mm2
Cable impedance 100 :
Transmission speed 10 Mbps and 100 Mbps, selectable
Maximum network segment expansion 100 m
Maximum delay 92 bit periods
Maximum extension of the collision domain during operation 205 m
at a transmission rate of 100 Mbps

Mechanical Tests
Shock test in acc. with IEC 60068-2-27 30g
Vibration resistance in acc. with IEC 60068-2-6 Operation / storage / transport: 5g, criterion A
Free fall according to IEC 60068-2-32 1m

Conformance With EMC Directives


Developed in acc. with IEC 61000-6.2
Emitted interference acc. with EN 55022: 1998 Class A (industrial applications)
+ A1: 2000 + A2: 2003 (Interference voltage)
Emitted interference acc. to EN 55011: 1998 Class A (industrial applications)
+ A1: 1999 + A2: 2002 (EMC protection)
Noise immunity in acc. with EN 61000-4-2 (IEC 1000-4-2) (ESD) Requirements in acc. with DIN EN 61000-6-2
Contact discharge Test intensitiy 2, criterion B
Air discharge Test intensitiy 3, criterion B
Indirect discharge Test intensitiy 2, criterion B
Noise immunity in acc. with EN 61000-4-3 (IEC 1000-4-3) Requirements in acc. with DIN EN 61000-6-2
(electromagnetic fields) Test intensitiy 3, criterion A
Noise immunity in acc. with EN 61000-4-4 (IEC 1000-4-4) (Burst) Requirements in acc. with DIN EN 61000-6-2
Data lines Test intensitiy 2, criterion B
Voltage supply Test intensitiy 3, criterion B
Noise immunity in acc. with EN 61000-4-5 (IEC 1000-4-5) (Surge) Requirements in acc. with DIN EN 61000-6-2
Data lines Test intensitiy 2, criterion B
Voltage supply Test intensitiy 1, criterion B
Noise immunity in acc. with EN 61000-4-6 (IEC 1000-4-6) (conducted) Requirements in acc. with DIN EN 61000-6-2
Test intensitiy 3, criterion A

7179_en_03 PHOENIX CONTACT 3


FL HUB 8/16TX-ZF

General Information

Warning
Disregarding this warning may result in damage to equipment and/or serious personal injury. Only qualified
personnel may start up and operate these devices. According to the safety instructions in this text, qualified
personnel are persons who are authorized to start up, to ground, and to mark devices, systems, and equip-
ment according to the standards of safety technology. In addition, these persons must be familiar with all
warning instructions and maintenance measures in this text.

Warning
The Product Short Description module is designed exclusively for SELV operation according to IEC 950 /
EN 60950/VDE 0805.

Installation and Mounting/Removal


Install the Product Short Description on a clean DIN rail according to DIN EN 50 022 (Phoenix Contact: product NS 35…).
To avoid contact resistance only use clean, corrosion-free DIN rails. Mount end clamps on both ends of the station in order
to prevent the module from slipping on the DIN rail.

Connect the DIN rail to protective earth ground using a grounding terminal block. The modules are
grounded when they are snapped onto the DIN rail. Optionally the module can be grounded via a second
COMBICON connector. Connect protective earth ground with low impedance.

Mounting:
1 Place the module onto the DIN rail from above. The upper holding keyway must be hooked onto the top edge of the
DIN rail.
2 Push the module from the front towards the mounting surface.
3 Once the module has been snapped on properly, check that it is fixed securely on the DIN rail.

Removal:
1 Pull the locking latch down using a screwdriver, needle-nose pliers or similar.
2 Pull the bottom edge of the module away from the mounting surface.
3 Pull the module diagonally upwards away from the DIN rail.

7179_en_03 PHOENIX CONTACT 4


FL HUB 8/16TX-ZF

Terminal Assignment

Terminal Meaning
1 2 3 4 5 6 7 8 1 +24 V DC supply voltage (internally
connected to terminal 3)
2 0 V DC (internally connected to terminal 4)
3 Supply voltage continuation
4 Continuation 0 V DC
5-8 Functional earth ground (optional)

100M CROSS

PWR
STRAIGHT

Figure 1 Terminal Assignment

Connecting the Supply Voltage


Connect the supply voltage via terminal 1 (+24 V DC) and terminal 2 (0 V). Inside the module, terminal 1 is connected to
terminal 3. Inside the module, terminal 2 is connected to terminal 4.
Use the internal voltage continuation for the connection of additional hubs only. In this context, please note that the maxi-
mum current carrying capacity of the connector of 12 A must not be exceeded.
Terminals 5 up to 8 are bridged inside the module and serve to connect functional earth ground (optional).

24 V DC 24 V DC 24 V DC

0 V DC

100M CROSS 100M CROSS

PWR PWR
STRAIGHT STRAIGHT

Figure 2 Connecting the supply voltage Figure 3 Voltage continuation

7179_en_03 PHOENIX CONTACT 5


FL HUB 8/16TX-ZF

Local Configuration Options


At the "10M - 100M“ slide switch at the front you have the Functions of the Hub
option to set the data transmission rate for the entire device
– Execute Segmentation
and thus for all connected devices to the fixed value of 10
If more than 128 collisions occur in direct succession at
Mbps or 100 Mbps.
one port, the receiving connection to this port is dis-
At the "CROSS - STRAIGHT“ slide switch at the front you abled.
have the option to set the port assignment for port 5 be- – Deactivate Segmentation
tween 1:1 (STRAIGHT) and cross-over (CROSS). For this Per default the segmentation is deactivated if transmit-
reason, port 5 is particularly suitable as uplink port. ting or receiving data without collision for the duration
Switch "10M -100M" for data transmission rate of 512 bit periods is possible.
– Jabber
Switch Position Data Transmission Rate
If a device is active for more than 64,000 bit periods,
10M 10 Mbps (default) the hub deactivates the transmit and receive port. The
100M 100 Mbps ports are automatically re-enabled as soon as valid
telegrams are received/transmitted again. The other
Please note that the data transmission rate that ports are not deactiviated.
is selected using the "10M - 100M" switch is
– Cascading Hubs
only valid after a reset (power-up) of the de-
Do not cascade more than 4 hubs in succession when
vice.
operating at a data transmission rate of 10 Mbps.
"STRAIGHT - CROSS" switch for cable type Do not cascade more than 2 hubs in succession when
operating at a data transmission rate of 100 Mbps. In
Switch Position Cable Type
this context, the length of the connection cable be-
STRAIGHT Normal (default) tween the hubs must not be longer than 5 m. The max-
CROSS Uplink imum extension of the collision domain when the hub is
operated at a transmission rate of 100 Mbps must not
exceed 205 m (Class II repeater).

Housing Dimensions
112 mm (4.409") 45 mm (1.772") 90 mm (3.544”)

100M CROSS 100M CROSS


105 mm (4.130")

PWR PWR

10M COL STRAIGHT 10M COL STRAIGHT

1 5
1
1 9 13

2 26 2 10 14
2

3 37 3 37 11 15
3

4 48 4 48 12 16
4

FL HUB 8TX FL HUB 16TX


Ord.-No.: 28 32 55 1 Ord.-No.: 28 32 56 4

Figure 4 Housing dimensions of the FL HUB 8TX-ZF or FL HUB 16TX-ZF

© PHOENIX CONTACT 03/2007

7179_en_03 PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany 6


Phone: +49-(0) 5235-3-00 • Fax: +49-(0) 5235-3-4 12 00
www.phoenixcontact.com


Ź ŹŒ’Š—‘’ƒ‹
}Ž€“}ŽŸ}}„



ŷ ŷ ŹŇńńńŹ 
ŷ‘‹‰}…‹ŠŹˆˆ ‘ˆ…ď‘Š…‹ŠŹ‹ŠŽ‹ˆˆŽ

ņńńŋďŅŅďŇń
 ņńŷňŇńņņ’čŶ




Ź Ź ʼnņņņ … } Œ‹“Ž‚‘ˆ Ž}ˆ
…‰ ‘ˆ…‘Š…‹ŠŹ‹ŠŽ‹ˆˆŽ‹‚„
Ź Ź Œ’Š —‘’ƒ‹č  ŒŽ‹’…€
„ ‚‹ˆˆ‹“…Šƒ ‰}…Š }‘‹‰}…‹Š ˆˆ
‚‘Š…‹Š}ˆ……Č
• } ŒŽ‹…Šƒ ‹‚ ŷ‘‹‰}…‹Š
€}}Ĥ‹ŒŠ€ˆ‹‹ŒĊˆ‹€ˆ‹‹Œĥ
• Ğ }Š}ƒ‰Š
• ‘ŒŽ’……‹Š€…}ˆ‹ƒ
• …ˆ€Š“‹Ž‡‰}Š}ƒ‰Š
• €‘Š€}Š…‰}Š}ƒ‰Š 
• …‰ }‰Œ…Šƒ ’Š }Š€ 
}‰Œˆ€‰}‘Ž‰Š 
• Ÿ…}ƒŠ‹…‰}ƒ
• ŹŠŽ}ˆ…–€ ˆˆ €‹“Šˆ‹}€…Šƒ }Š€
…Šƒ
• ‘Š‹ŠŽ‹ˆ
Ź‹‰Œ}}Š€}Š€}Ž€ĤŅōė„}…Ċ
Ň „…ƒ„ĥĊ „ Ź Ź ʼnņņņ
ŒŽ‹’…€ } Ž‹Šƒ Ž€‘Š€}Š
Ž‘‘Ž…Š}‰…Š…‰‘‰Œ}č
‹ˆˆ‹“…Šƒ „ „‹Š ‹Œ…‹ŠĊ „
Ž€‘Š€}Š• }Š ~ }ŽŽ…€ ‹‘ “…„
‹Š‹Ž“‹Ž}‡




’ŽňņŊʼnņŇŋƒŒƒ”
đŽ—‡…†’ĹŹ ňņņōďŹ Č’†ƒŹ Š…Œ‚Œ—Š’ƒŒ’‡”ƒ”ƒ‘‡Œ’†ƒƒ„ƒ’‚ƒ‹‰‘Œ‚‘ƒ”‡ƒ‹‰‘„Ź ď†ƒ
’†ƒ Œ‹ƒ‘ ‹ƒŒ’‡Œƒ‚Č ƒ…‡‘’ƒƒ‚  Œ’Č ƒ ’†ƒ ŽŽƒ’— „ ’†ƒ‡ ƒ‘Žƒ’‡”ƒ ‹ŽŒ‡ƒ‘ď †ƒ ’ƒ†Œ‡Š Œ‚ ’†ƒ ‚’ Œ’‡Œƒ‚ ‡Œ ’†‡‘ ‚“‹ƒŒ’ ‡‘ Ž”‡‚ƒ‚ „
‡Œ„‹’‡ŒŒŠ—ďƒ‡’†ƒŹ ȇ’‘„„‡ƒ‘Œ‚ƒ‹ŽŠ—ƒƒ‘ƒŽ’ƒ‘ŽŒ‘‡€‡Š‡’—„‘†“Š‚€ƒ’‰ƒŒ‘‹‰‡Œ…Œ—ƒŽƒ‘ƒŒ’’‡Œ•Œ’—Ħ•†ƒ’†ƒƒ–Žƒ‘‘
‡‹ŽŠ‡ƒ‚ħ‘’’†ƒ“—‹ŽŠƒ’ƒŒƒ‘‘„‘“†‚’’†ƒ†‡ƒ”ƒ‹ƒŒ’„Œ—Žˆƒ’ƒ‚Žƒ„‹Œƒ‡’ƒ‡•†ƒƒ’†ƒ‘ƒƒ‡Œ‚‡’ƒ‚ďŹ ƒ‘ƒ”ƒ‘’†ƒ‡…†’
ŅĞņ
’ƒ”‡‘ƒ†Œ…ƒ’†‡‘‚’’Œ—’‡‹ƒ•‡’†“’„“’†ƒŒ’‡ƒď 




ŷ ŷ ŹŇńńńŹ 
ŷ‘‹‰}…‹ŠŹˆˆ ‘ˆ…ď‘Š…‹ŠŹ‹ŠŽ‹ˆˆŽ

ņńńŋďŅŅďŇń
ņńŷňŇńņņ’čŶ


ŷˆ‹‰ ŹŇńńńďŹďďņŇń
‚ŽŠ
ŹŇńńńďŹďďņň
€‘Š€}Š•…Š}…Šƒˆ Ņ}‡ņ”ňˆ‹
}‡ }‡“…„ŷ ŷŌńńń ņ”Ņ‹“Ž‘ŒŒˆ…
Ź‹Š‚…ƒ‘Ž}…‹Š “‹Ž‡ ņ”ŅŹ“…„ņ„ŽŠŌńńńŠ“‹Ž‡‹Ž
ņ”Ņ„ŽŠ~‹}Ž€‚‹ŽŽ€‘Š€}Š•‰}Š}ƒ‰Š
ņ”Ņ‘}€„ŽŠ~‹}Ž€‹‚ň„ŽŠŒ‹ŽČ
Ņ‚‹Žŷ ŷŌńńń “‹Ž‡Ċ
 Ґ„ŽŠ‚ŽŒ‹Ž
‚‹Ž„‹‰‰‘Š…}…‹Š‹Œ…‹ŠĤ ‹€~‘ĥ
Ź„}… Ņōė„}…ĊŇ„…ƒ„
„}Š…}ˆ‚}‘Ž Ÿ…‰Š…‹ŠĤ ””ĥ ňŌņčʼnŊ‰‰”ŅŇŇčŇʼn‰‰”ņʼnńčń‰‰
…ƒ„ ōďŅņ
ƒ
ˆŽ‹‰}ƒŠ… ŹŽ…ŊŅńńń}Š€}Ž€‚‹ŽˆŽ‹‰}ƒŠ…Š’…Ž‹Š‰Š
Š’…Ž‹Š‰Š
‰ŒŽ}‘Ž ňńŨŹŠ‹‰…Š}ˆ
ŅņńĞņŇńŷŹ ŹďŇņʼnĞŷŹ
‹“Ž‘ŒŒˆ…
ņʼnńŇ”Ō‘Ž‹}Ž€Œ}‡}ƒ
ŅńńďņňńŷŹ
ʼnńďŊń–ďŅĊňŷĶņŇń
ņňŸŹ ŹďŇņʼnĞņň
ņʼnńŇ”Ō‘Ž‹}Ž€Œ}‡}ƒ
ŅŌďŇŊŸŹďŅňŷĶņňŸŹ
}Š€}Ž€ Źōʼnńċ ʼnʼnńņņĞŹŹŹˆ}ŷċŹŊńōʼnńŹˆ}
 Ź‰}Ž‡…Šƒ‹‰Œˆ…}ŠĢ‘ˆˆ•‹‰Œˆ…}Š“…„Ź 
Ź Ŷ‹}Ž€ ŹŇŌňń
ŠˆĸŹˆŽ‹Šĸ Ņ„
ʼnŅņ ~ŸŸŷ ŹŹċŽ‹ƒŽ}‰ ‰‹Ž•ņʼnŊ ~
ņŒ‹ŽďņŇņ
ņŒ‹Ž ňʼnŅńĞŅńńŶ}ď‚‹ŽŽ€‘Š€}ŠŌńńńŠ“‹Ž‡


Ŷ‹}Ž€ň‘}€„ŽŠ Źďďńň
Œ‹Ž ňŒ‹Ž ňʼnŅńĞŅńńŶ}ďďŌņʼnʼnŅ}„ŽŠ




’ŽňņŊʼnņŇŋƒŒƒ”
đŽ—‡…†’ĹŹ ňņņōďŹ Č’†ƒŹ Š…Œ‚Œ—Š’ƒŒ’‡”ƒ”ƒ‘‡Œ’†ƒƒ„ƒ’‚ƒ‹‰‘Œ‚‘ƒ”‡ƒ‹‰‘„Ź ď†ƒ
’†ƒ Œ‹ƒ‘ ‹ƒŒ’‡Œƒ‚Č ƒ…‡‘’ƒƒ‚  Œ’Č ƒ ’†ƒ ŽŽƒ’— „ ’†ƒ‡ ƒ‘Žƒ’‡”ƒ ‹ŽŒ‡ƒ‘ď †ƒ ’ƒ†Œ‡Š Œ‚ ’†ƒ ‚’ Œ’‡Œƒ‚ ‡Œ ’†‡‘ ‚“‹ƒŒ’ ‡‘ Ž”‡‚ƒ‚ „
‡Œ„‹’‡ŒŒŠ—ďƒ‡’†ƒŹ ȇ’‘„„‡ƒ‘Œ‚ƒ‹ŽŠ—ƒƒ‘ƒŽ’ƒ‘ŽŒ‘‡€‡Š‡’—„‘†“Š‚€ƒ’‰ƒŒ‘‹‰‡Œ…Œ—ƒŽƒ‘ƒŒ’’‡Œ•Œ’—Ħ•†ƒ’†ƒƒ–Žƒ‘‘
‡‹ŽŠ‡ƒ‚ħ‘’’†ƒ“—‹ŽŠƒ’ƒŒƒ‘‘„‘“†‚’’†ƒ†‡ƒ”ƒ‹ƒŒ’„Œ—Žˆƒ’ƒ‚Žƒ„‹Œƒ‡’ƒ‡•†ƒƒ’†ƒ‘ƒƒ‡Œ‚‡’ƒ‚ďŹ ƒ‘ƒ”ƒ‘’†ƒ‡…†’
ņĞņ
’ƒ”‡‘ƒ†Œ…ƒ’†‡‘‚’’Œ—’‡‹ƒ•‡’†“’„“’†ƒŒ’‡ƒď 

Industrial Ethernet Solutions

EDS-205/208 Series
5 and 8-port entry-level unmanaged Ethernet switches

› 10/100BaseT(X) (RJ45 connector), 100BaseFX (multi-mode, SC/


ST connectors)
› IEEE802.3/802.3u/802.3x support
› Broadcast storm protection
› DIN-Rail mounting ability
› -10 to 60°C operating temperature range

Introduction
The EDS-205/208 series of industrial Ethernet switches are entry- any harsh industrial environment. The switches can be easily installed
level industrial 5 and 8-port Ethernet switches that support IEEE on a DIN-Rail as well as in distribution boxes. The DIN-Rail mounting
802.3/802.3u/802.3x with 10/100M, full/half-duplex, MDI/MDIX auto- capability, wide operating temperature, and the the IP30 housing with
sensing RJ45 ports. The EDS-205/208 switches are rated to operate LED indicators make the plug-and-play EDS-205/208 switches easy to
at temperatures ranging from -10 to 60°C, and are rugged enough for use and reliable.

Specifications

Technology Power Requirements


Standards: Input Voltage:
IEEE 802.3 for 10BaseT EDS-205: 12 to 48 VDC, 18 to 30 VAC (47 to 63 Hz)
IEEE 802.3u for 100BaseT(X) and 100BaseFX EDS-208 series: 12 to 45 VDC, 18 to 30 VAC (47 to 63 Hz)
IEEE 802.3x for Flow Control Input Current:
Processing Type: Store and Forward EDS-205: 0.12 A @ 24 V
Flow Control: IEEE 802.3x flow control, back pressure flow control EDS-208: 0.14 A @ 24 V
Switch Properties EDS-208-M: 0.23 A @ 24 V
MAC Table Size: 1 K Overload Current Protection: 1.1 A
Packet Buffer Size: 512 Kbit Connection: 1 removable 3-contact terminal block
Reverse Polarity Protection: Present
Interface
Fiber Ports: 100BaseFX ports (SC/ST connector, multi-mode) Physical Characteristics
RJ45 Ports: 10/100BaseT(X) auto negotiation speed, Full/Half duplex Housing: Plastic, IP30 protection
mode, and auto MDI/MDI-X connection Dimensions:
LED Indicators: Power, 10/100M (TP port), 100M (fiber port) EDS-205: 24.9 x 100 x 86.5 mm (0.98 x 3.94 x 3.41 in)
EDS-208: 40 x 100 x 86.5 mm (1.57 x 3.94 x 3.41 in)
Optical Fiber
Weight:
100BaseFX EDS-205: 135 g
Multi-mode Single-mode EDS-208: 170 g
Wavelength 1300 nm 1310 nm Installation: DIN-Rail mounting

Max. TX -10 dBm 0 dBm


Environmental Limits
Operating Temperature: -10 to 60°C (14 to 140°F)
Min. TX -20 dBm -5 dBm Storage Temperature: -40 to 85°C (-40 to 185°F)
RX Sensitivity -32 dBm -34 dBm Ambient Relative Humidity: 5 to 95% (non-condensing)
Link Budget 12 dB 29 dB
5 km a
Typical Distance 40 km c
4 km b
Saturation -6 dBm -3 dBm
a. 50/125 μm, 800 MHz*km fiber optic cable
b. 62.5/125 μm, 500 MHz*km fiber optic cable
c. 9/125 μm single-mode fiber optic cable

1 w w w. m o x a . c o m info@moxa.com
Industrial Ethernet Solutions

Standards and Certifications MTBF (mean time between failures)


Safety: Time:
EDS-205: UL 508, EN 60950-1 EDS-205: 323,000 hrs
EDS-208: UL 508, UL 60950-1, EN 60950-1 EDS-208: 368,000 hrs
EMI: FCC Part 15 Subpart B Class A, EN 55022 Class A Database:
EMS: EDS-205: Telcordia (Bellcore), GB
EN 61000-4-2 (ESD) Level 2, EN 61000-4-3 (RS) Level 3, EDS-208: MIL-HDBK-217F, GB 25°C
EN 61000-4-4 (EFT) Level 3, EN 61000-4-5 (Surge) Level 3, Warranty
EN 61000-4-6 (CS) (EDS-205: Level 3; EDS-208: Level 2), Warranty Period: 5 years
EN 61000-4-8, EN 61000-4-11 Details: See www.moxa.com/warranty
Shock: IEC 60068-2-27
Freefall: IEC 60068-2-32
Vibration: IEC 60068-2-6
Note: Please check Moxa’s website for the most up-to-date certification status.

Dimensions
Unit: mm (inch)
74.0 (2.9)

15.0 (0.6) 15.0 (0.6)


32.0 (1.3) 10.5
(0.4)

40.0 (1.6)
23.0 (0.9)
100.0 (3.9)

100.0 (3.9)

100.0 (3.9)

74.0 (2.9)
12.0
76.2 (3.0)

(0.5)

86.5 (3.4) 40.0 (1.6) 24.9 (1.0)

Side View Front Views Rear Views Top & Bottom Views

Ordering Information
Available Models Port Interface
100BaseFX
Standard Temperature Housing Material Power Range
10/100BaseT(X) Multi-mode, Multi-mode,
(-10 to 60°C)
SC Connector ST Connector

EDS-205 5 – – Plastic 12 to 48 VDC

EDS-208 8 – – Plastic 12 to 45 VDC

EDS-208-M-SC 7 1 – Plastic 12 to 45 VDC

EDS-208-M-ST 7 – 1 Plastic 12 to 45 VDC

Optional Accessories (can be purchased separately) Package Checklist


DR-4524/75-24/120-24: 45/75/120 W DIN-Rail 24 VDC power supplies s EDS-205 or EDS-208 switch
MDR-40-24/60-24: 40/60 W DIN-Rail 24 VDC power supplies, -20 to 70°C operating temperature s Hardware installation guide (printed)
RK-4U: 4U-high 19” rack mounting kit
s Warranty card

2 © Moxa Inc. All Rights Reserved. Updated Mar. 14, 2011. Specifications subject to change without notice. Please visit our website for the most up-to-date product information.
߾ᄽपᅜ໿ྪྪ࠲

MGate™ MB3180/3280/3480
1/2/4੨Քጚ႙Modbusྪ࠲
› ྜ‫ׯ‬Modbus TCPࢅModbus RTU/ASCIIၹᅱኮ
क़‫ڦ‬ገ࣑
› ༵ࠃ1߲ᅜ໿ྪ੨ࢅ1/2/4߲RS-232/422/485‫ز‬੨
› ཞ้ኧ‫׼‬16߲TCP master૶থLj௅߲masterፌ‫ٷ‬
ཞ้ኧ‫׼‬32߲ంସ൩൱
› Ҿጎ੺໏०‫ڇ‬

4
०঻
߾ᄽपᅜ໿ྪྪ࠲ > MGate™ MB3180/3280/3480

MB3180LjMB3280ࢅMB3480๟Քጚ‫ڦ‬Modbusྪ࠲Lj໲੗ ૶থ31߲RTU/ASCII slavesยԢLj‫ܔ‬ᇀRTU/ASCII masterፌ


ᅜྜ‫ׯ‬Modbus TCPࢅModbus RTU/ASCIIၹᅱኮक़‫ڦ‬ገ ‫ٷ‬੗ᅜኧ‫׼‬32߲TCP slave ă
࣑ăཞ้ኧ‫׼‬16߲Modbus TCP master૶থLj௅߲‫܋‬੨੗ᅜ

ኝࢇՔጚ‫ڦ‬Modbusྪஏ
MGate™ MB3000 Քጚׂ೗Ԉࡤ MB3180LjMB3280 ࢅ ‫ںފ‬ኝࢇ‫ڟ‬၄ᆶ‫ڦ‬Modbus TCPྪஏዐLjժ൐Modbus TCP
MB3480Lj໲๟ྺ੺໏ኝࢇModbus TCPࢅRTU/ASCII ྪ slaveᄺ੗ᅜࢅserial masterኟ‫׉‬ཚრăMB3180LjMB3280ࢅ
ஏܸยऺ‫ڦ‬ă๑ᆩኄၵׂ೗LjModbus‫ز‬੨slaveยԢ੗ᅜ࿮ MB3480༵ࠃൟ຿੺໏ኝࢇLjଳऄ‫ڦ‬༬‫ۅ‬Ljग़ඹႠഽă

੗ፇॺߛ௢‫ྪ܈‬ஏLjᆶၳই‫ׯ࠲ྪگ‬Ԩ
MGate™ MB3000੗ᅜൟ຿ྜ‫ߛׯ‬௢‫܈‬Modbusব‫ྪۅ‬ஏ‫ڦ‬ ዁੗ᅜྺ௅߲ཚ‫ڦڢ‬Modbus RTUईModbus ASCIIದዃփ
ण‫ׯ‬ă๑ᆩMB3280ፌ‫ܠ‬੗ᅜ࠶૙62߲‫ز‬੨slaveব‫ۅ‬Ljܸ๑ ཞ‫ڦ‬հ༬୲LjሎႹփཞ‫ڦ‬Modbusྪஏኝࢇ‫ڟ‬ᅃ߲Modbus
ᆩMB3480ཚࡗRS-233/422/485‫ز‬੨੗ᅜ࠶૙‫ڟ‬124߲Ljฯ TCPྪஏฉઠă

ࡀ߭

ᅜ໿ྪ ‫ز‬੨႑ࡽ
‫܋‬੨ຕǖ1 RS-232ǖTxDLjRxDLjRTSLjCTSLjDTRLjDSRLjDCDLjGND
໏୲ǖ10/100 MbpsLjጲ๢ᆌMDI/MDIX RS-422ǖTx+LjTx-LjRx+LjRx-LjGND
থཀྵǖ8-pin RJ45 RS-485-4wǖTx+LjTx-LjRx+LjRx-LjGND
‫߰ىۉ‬૗ԍࢺǖాॺ1.5 KV RS-485-2wǖData+LjData-LjGND
‫ز‬੨ ෉ॲ༬‫ۅ‬
‫܋‬੨ຕǖ ֡ፕఇ๕ǖRTU SlaveLjRTU MasterLjASCII SlaveLjASCII
MB3180ǖ1 Master
MB3280ǖ2 ߾ਏǖMGate™ Manager for Windows 98/ME/NT/2000Lj
MB3480ǖ4 Windows XP/2003/Vista/2008/7 x86/x64
‫ز‬੨ՔጚǖRS-232/422/485Lj෉ॲ჋ስ ‫ܠ‬ዷऐࢅ‫૶ۅܠ‬থǖ
‫܋‬੨ૌ႙ǖDB9 male Masterఇ๕ǖፌ‫ٷ‬32߲TCP slave
ESDԍࢺǖඇ႑ࡽ15 KV Slave ఇ๕ǖ16 TCP masterLj௅߲masterሎႹཞ้32߲ంସ
RS-485ຕ਍ୁၠ੦዆ǖADDC®DŽຕ਍ୁၠጲ‫ۯ‬੦዆) ൩൱
‫ز‬੨ཚრ֖ຕ ༬๺ࠀీǖ዇ీୟᆯ
ຕ਍࿋ǖ7Lj8 ऐႁ༬Ⴀ
ཕኹ࿋ǖ1Lj2 ྔ੕ǖ
ၯᄓ࿋ǖNoneLjEvenLjOddLjSpaceLjMark MB3180/3280ǖূຌ
ୁ੦ǖRTS/CTSLjDTR/DSRDŽৈRS-232) MB3480ǖূຌLjIP30ԍࢺ
հ༬୲ǖ50 bps ~ 921.6 Kbps

4-8
߾ᄽጲ‫ྜࣅۯ‬ኝ঴ਦ‫ݛ‬ӄ

؅٫ǖ MGate™ M3480ǖ385 mADŽmax.)


࿮ࠬܺǖ Ҿࡀණኤ
MB3180ǖ22 x 52 x 80 mmDŽ0.87 x 2.05 x 3.15 in) EMCǖCEDŽEN55022 Class AࢅEN55024)LjFCC Part 15
MB3280ǖ22 x 77 x 111 mmDŽ0.87 x 3.03 x 4.37 in) Subpart B Class A
MB3480ǖ35.5 x 103 x 158 mmDŽ1.40 x 4.06 x 6.22 in) SafetyǖULDŽUL60950-1)LjTÜVDŽEN60950-1)
ᆶࠬܺǖ EMSǖ
MB3180ǖ22 x 75.2 x 80 mmDŽ0.87 x 2.96 x 3.15 in) EN61000-4-2DŽESD)ǖLevel 2
MB3280ǖ22 x 100 x 111 mmDŽ0.87 x 3.94 x 4.37 in) EN61000-4-3DŽRS)ǖLevel 2
MB3480ǖ35.5 x 103 x 181 mmDŽ1.40 x 4.06 x 7.14 in) EN61000-4-4DŽEFT)ǖLevel 2
߾ፕ࣍ৣ EN61000-4-5DŽSurge)ǖLevel 2
߾ፕ࿒‫܈‬ǖ0 ~ 55 ˚CDŽ32 ~ 131 ˚F) EN61000-4-6DŽCS)ǖLevel 2
߾ፕโ‫܈‬ǖ5 ~ 95% RH EN61000-4-8ǖPassed
٪‫ئ‬࿒‫܈‬ǖ-20 ~ 70 ˚CDŽ-4 ~ 158 ˚F) EN61000-4-11ǖPassed
‫ۉ‬ᇸႴ൱ EN61000-4-12ǖPassed
๼෇‫ۉ‬უǖ12 ~ 48 VDC
‫ۉ‬ᇸথ੨ǖ
MGate™ MB3180ǖ‫ۉ‬ᇸ֭ፗ
੗੍Ⴀ
MTBFǖ
MGate™ M3180ǖ628376ၭ้
4
MGate™ MB3280/3480ǖ‫ۉ‬ᇸ֭ፗࢅ‫܋‬ጱথ੨ MGate™ M3280ǖ503029ၭ้
‫ۉ‬ᇸࠀࡼǖ MGate™ M3480ǖ295812ၭ้

߾ᄽपᅜ໿ྪྪ࠲ > MGate™ MB3180/3280/3480


MGate™ M3180ǖ200 mADŽmax.) ԍႪ೺
MGate™ M3280ǖ250 mADŽmax.) ԍႪ೺ǖ5౎

؅٫
(0.87 in)

(0.87 in)

35.5 mm
(1.40 in)
22 mm
22 mm

52 mm (2.05 in) 181.3 mm (7.14 in)


169.3 mm (6.67 in)
63 mm (2.48 in) 9 mm (0.35 inch) 157.23 mm (6.19 in)
75 mm (2.95 in)
50.5 mm (1.99 in)
55.5 mm (2.19 in)

(1.69 in)

(1.34 in)
43 mm

34 mm

38.87 mm
(1.53 in)
111 mm (4.37 in)
43 mm (1.69 in)
80 mm (3.15 in)

(0.98 in)

102.72 mm
25 mm

(4.04 in)
(0.98 in)
10 mm (0.39 in)

25 mm
(0.98 in)
25 mm
12.5 mm
(0.49 in)

(0.20 in)
5 mm

34 mm
(1.34 in) 21.5 mm
(0.85 in)
77 mm (3.03 in)
88 mm (3.46 in)
100 mm (3.94 in)

۩ࠔ႑တ
੗჋႙ࡽ Ԉጎൣ‫ڇ‬
MGate™ MB3180ǖ1੨Քጚ႙Modbusྪ࠲ • MGate™ MB3180/MB3280/MB3480
MGate™ MB3280ǖ2੨Քጚ႙Modbusྪ࠲ Modbusྪ࠲
MGate™ MB3480ǖ4੨Քጚ႙Modbusྪ࠲ • ‫ۉ‬ᇸ๢ದഗ
• ࿔‫ڗ‬त෉ॲ࠼ಎ
੗჋޹ॲDŽႷ‫ࠔ܀ڇ‬ச)
• ੺໏ҾጎኸళDŽ‫ٶ‬ᆇӲDž
DK-35Aǖ‫ࡆڞ‬Ҿጎ༫ॲ(35mm)
• ԍႪਸ਼
DK-35A

ww w.m ox a.com .c n e - m a il ǖc h in a @m o xa . c o m ௨ ‫ ݯ‬र ຍ ඤ ၍ ǖ8 0 0 - 8 2 0 - 5 0 3 6 4-9


ALSPA Automation Cell
CE1000 & CE1500 Controllers
BC8084 - Powerlink Bus Controller

Datasheet

2009-10-15
PTP20A43178 en Rev B

BC8084 – Powerlink Bus Controller


The BC8084 – Powerlink Bus Controller is a module of the ALSPA
CE1000 and CE1500 controllers.
The BC8084 module is a CE1000 bus controller fieldbus interface
with POWERLINK V1/V2 interface and integrated Compact Link
Selector.
It provides supports expansion with active CE1000 hub modules,
status indicator LEDs and 2 x RJ45 connections.
The BC8084 bus controller makes it possible to connect X2X Link I/O
nodes to POWERLINK, standard protocol for Fast Ethernet with true
real-time properties.
POWERLINK V1/V2
•/O configuration and firmware update via the fieldbus
Integrated compact link selector function
2 active hub expansion modules can be connected to the bus
controller
Redundant supply possible
FEATURES BC8084
POWERLINK V1/V2 Controlled Node with Compact Link
Short description Bus controller
Selector
Fieldbus Type POWERLINK V1/V2 100 Base-T (ANSI/IEE 802.3)
Controller, Processor,
EPL MAC, 32 Bit RISC, 512KB
Memory
Design Internal 2x hub, 2x shielded RJ45 port
Cable length Max. 100 m between two stations (segment length)
Transfer rate 100 MBit/s
General information Status indicators Module status, bus function
Module status: Yes, with status LED and software status
Diagnostics
Bus function: Yes, with status LED and software status
Fieldbus X2X: Yes
Electrical isolation
Fieldbus – I/O : Yes
Power consumption of
2.0 W
the bus
Certification CE, C-UL-US, GOST-R

Datasheet_Template_RevH (PTP20A43015 en H) - Copyright © ALSTOM 2009. ALSTOM, the ALSTOM logo and any alternative version thereof are trademarks and
service marks of ALSTOM. The other names mentioned, registered or not, are the property of their respective companies. The technical and other data contained in this
document is provided for information only. Neither ALSTOM, its officers and employees accept responsibility for or should be taken as making any representation or
warranty (whether express or implied) as to the accuracy or completeness of such data or the achievement of any projected performance criteria where these are
1/1
indicated. ALSTOM reserves the right to revise or change this data at any time without further notice. helpdesk.control-systems@power.alstom.com
CE1000 & CE1500 Controllers
BC8084 - Powerlink Bus Controller

2009-10-15
PTP20A43178 en Rev B

Horizontal Installation: 00C to +550C


Operational conditions Operating temperature
Vertical Installation: 00C to +500C
Relative humidity 5 to 95% (non-condensing)

Mounting orientation Horizontal or vertical


0 – 2000m: No derating
Installation at altitudes
>2000m: Reduction of ambient temperature by
above sea level
0.5 °C per 100m
Protection type IP20
Storage and transport
Temperature -250C to +700C
conditions
Relative humidity 5 to 95% (non-condensing)
Mechanical X20BB81: 62.5 +0.2 mm
Spacing
characteristics X20BB82: 87.5 +0.2 mm
Status LEDs S/E Green – Status /red - Error
L/A IFx (Green) On : A link to the remote station has been established.
Blinking : A link to the remote station has been established.
The LED blinks when Ethernet activity is present on the bus.

Operating and
connection elements

Copyright © ALSTOM 2009.


ALSTOM Power Energy Management Business 9, rue Ampère 91345 MASSY Cedex France 2/2
Customer Support: helpdesk.control-systems@power.alstom.com www.power.alstom.com x
ALSPA Automation Cell
CE1000
PS9400 - Power Supply module

Datasheet

2009-08-20
PTP20A43035 en Rev D

PS 9400 Power Supply Module


The PS9400 is a module of the ALSPA CE1000 Controller.
This supply module is used together with a bus controller.
It is equipped with a feed for the bus controller, the X2X
Link, and the internal I/O supply.
The main features are:
Supply for the bus controller, X2X Link and internal I/O
supply,
Feed and bus controller / X2X Link supply electrically
isolated,
Redundancy of bus controller / X2X Link supply possible
by operating multiple supply modules simultaneously.

FEATURES PS9400
24V DC supply module for bus controller, X2X Link
Short Description Power Supply Module
bus supply and I/O
Bus Controller / X2X Link Supply
Input Voltage 24V DC (-15% / +20%)
Input
Input Current Max. 0.7A
Reverse Polarity Protection Yes
Fuse Integrated, can not be exchanged
Bus Controller / X2X Link Supply
Rated Output Power 7.0W
Output
Parallel Operation Yes
Redundant Operation of Bus
Yes
Controller / X2X Link Supply
I/O Supply Input Input Voltage 24V DC (-15% / +20%)
Fuse Recommended pre-fusing max. 10A slow-blow
I/O Supply Output Rated Output Voltage 24V DC
Allowable Contact Load 10.0A

PTP20A43015 en Rev L - Copyright © ALSTOM 2009. ALSTOM, the ALSTOM logo and any alternative version thereof are trademarks and service marks of ALSTOM.
The other names mentioned, registered or not, are the property of their respective companies. The technical and other data contained in this document is provided for
information only. Neither ALSTOM, its officers and employees accept responsibility for or should be taken as making any representation or warranty (whether express or
implied) as to the accuracy or completeness of such data or the achievement of any projected performance criteria where these are indicated. ALSTOM reserves the right
1/2
to revise or change this data at any time without further notice. helpdesk.control-systems@power.alstom.com
CE1000
PS9400 - Power Supply module

2009-08-20
PTP20A43035 en Rev D

General Information Status Display Overload, Operating status, Module status


Overload: Yes, with status LED and software status
Diagnostics Operating Status: Yes, with status LED
Module Status: Yes, with status LED
Bus Controller / X2X Link Supply : Yes
Electrical Isolation
I/O Supply: No
Certification CE, C-UL-US, GOST-R(in development)
0 0
Horizontal Installation: 0 C to +55 C
Operational Conditions Operating Temperature 0 0
Vertical Installation: 0 C to +50 C
Humidity 5 to 95% (non-condensing)
Mounting Orientation Horizontal or vertical
0 – 2000m: No derating
Installation at altitudes above
>2000m: Reduction of environmental temperature by
sea level
0.5 0C per 100m
Protection Type IP20
Mechanical Characteristics Spacing 12.5 +0.2mm
Required Accessories X20TB12 Standard X20 terminal block (12-pin)
Basic X20 bus controller, for bus controller field bus
X20BB80 interface and bus controller supply module, X20
connection
Connection Details Pin assignments Connection example
I/O Supply Output Rated Output Voltage 24V DC

Separate supplies

Supply with
jumper

Copyright © ALSTOM 2009.


ALSTOM Power Energy Management Business 9, rue Ampère 91345 MASSY Cedex France 2/2
Customer Support: helpdesk.control-systems@power.alstom.com www.power.alstom.com x
ALSPA Automation Cell
CE1000 & CE1500 Controllers
A04632 - Analog Output Module

Datasheet

2009-12-18
PTP20A43053-en-E

A04632 Analog Output Module


The AO4632 is a module of the ALSPA CE1000 and
CE1500 controllers.
The AO4632 module is equipped with four outputs with
16-bit digital converter resolution. Using different
connection terminals you can select between the current
and voltage signal.
The main features are:
4 analog outputs,
Both current and voltage signals are possible,
16-bit digital converter resolution

FEATURES A04632
Short description I/O Module 4 analog outputs, ±10V or 0 to 20mA
Analog outputs Output ±10V or 0 to 20mA, using different connection terminals
Digital converter resolution 16-bit
Power On/Off behaviour Internal enable relay for boot procedure and error
Conversion Time 50us for all outputs
Voltage : ±10V (load Ű.Ŋ
Load per channel
Current : Max. load 500 Ŋ
Short circuit protection Current limitation ± 40 mA
st
Output Filter Low pass 1 order / Cut-off Frequency 10 KHz
Maximum Gain Drift <0.01 % per °C,based on the current output value
Maximum Offset Drift <0.012 % per °C,based on the entire output range
Gain: <0.04 %, based on the current output value
Maximum error at 25°C
Offset: <0.022 %, based on the entire output range
Voltage : Max.0.02 % (from 10 MŊÆ1 KŊUHVLVWLYH)
Error caused by load change
Current : Max.0.5 % (from 1 ŊÆ500 ŊUHVLVWLYH
Isolation voltage betw.channel and bus 500 Veff
Non-linearity <0.005 % based on the output range

Datasheet_Template_RevH - Copyright © ALSTOM 2009. ALSTOM, the ALSTOM logo and any alternative version thereof are trademarks and service marks of
ALSTOM. The other names mentioned, registered or not, are the property of their respective companies. The technical and other data contained in this document is
provided for information only. Neither ALSTOM, its officers and employees accept responsibility for or should be taken as making any representation or warranty (whether
express or implied) as to the accuracy or completeness of such data or the achievement of any projected performance criteria where these are indicated. ALSTOM reserves
1/2
the right to revise or change this data at any time without further notice. helpdesk.control-systems@power.alstom.com
CE1000 & CE1500 Controllers
A04632 - Analog Output Module

2009-12-18
PTP20A43053-en-E

General information Status display I/O function per channel, Operating state, Module status
Channel Status: Yes, with status LED and software
Diagnostics Operating Status: Yes, with status LED
Module Status: Yes, with status LED
Channel – Bus: Yes
Electrical isolation
Channel – Channel: No
Rev. <B0: Bus-Typ. 0.01W, I/O Internal-Typ. 2.0W
Power consumption
Rev.ŰB0: Bus-Typ. 0.01W, I/O Internal-Typ. 1.6W
Certification CE, C-UL-US, GOST-R(in development)
Horizontal Installation : 0°C to +45°C
Operational conditions Operating temperature
Vertical Installation: 0°C to +40°C
Humidity 5 to 95% (non-condensing)

Mounting orientation Horizontal or vertical


0 – 2000m: No derating
Installation at altitudes above
>2000m: Reduction of environmental temperature by
sea level
0.50C per 100m
Protection type IP20
Mechanical
Spacing 12.5 +0.2mm
characteristics
Required accessories TB12 Standard terminal block(12-pin)
standard bus module, internal I/O supply is
BM11, BM01
interconnected
Connection details Pin assignments Connection example

Copyright © ALSTOM 2009.


ALSTOM Power Energy Management Business 9, rue Ampère 91345 MASSY Cedex France 2/2
Customer Support: helpdesk.control-systems@power.alstom.com www.power.alstom.com x
ALSPA Automation Cell
CE1000 & CE1500 Controllers
AI4632 - Analog Input Module

Datasheet

2009-10-15
PTP20A43049 en Rev D

AI4632 Analog Input Module


The AI4632 is a module of the ALSPA CE1000 or CE1500
controllers.
The AI4632 module is equipped with four inputs with 16-
bit digital converter resolution. Using different connection
terminals you can select between the current and voltage
signal.
The main features are:
4 analog inputs,
Both current and voltage signals are possible,
16-bit digital converter resolution,
Simultaneous input conversion,
Very fast conversion time,
Integrated oscilloscope function.

FEATURES AI4632

Short description I/O Module 4 analog inputs, ±10V or 0 to 20mA

Analog inputs Voltage Current

Digital converter
±15-bit 15-bit
resolution
Input impedance in signal
20Mť -
range
Load - <400ť
Gain: <0.08% Gain: <0.08%
Maximum error at 25 0C
Offset: <0.01% Offset: <0.02%
Input ±10V or 0 to 20mA, using different connection terminals

Input type Differential input

Conversion time 50Ŧs for all inputs

Output format INT

Datasheet_Template_RevH (PTP20A43015 en H) - Copyright © ALSTOM 2009. ALSTOM, the ALSTOM logo and any alternative version thereof are trademarks and
service marks of ALSTOM. The other names mentioned, registered or not, are the property of their respective companies. The technical and other data contained in this
document is provided for information only. Neither ALSTOM, its officers and employees accept responsibility for or should be taken as making any representation or
warranty (whether express or implied) as to the accuracy or completeness of such data or the achievement of any projected performance criteria where these are
1/2
indicated. ALSTOM reserves the right to revise or change this data at any time without further notice. helpdesk.control-systems@power.alstom.com
CE1000 & CE1500 Controllers
AI4632 - Analog Input Module

2009-10-15
PTP20A43049 en Rev D

Input protection Protection against wiring with supply voltage


I/O function per channel, Operating state,
General information Status display
Module status
Channel Status: Yes, with status LED and software status
Diagnostics Operating Status: Yes, with status LED
Module Status: Yes, with status LED
Channel – Bus: Yes
Electrical isolation
Channel – Channel: No
Bus: Typ. 0.01W
Power consumption
I/O Internal: 1.5W
Certification CE, C-UL-US, GOST-R(in development)
Horizontal installation: 00C to +550C
Operational conditions Operating temperature
Vertical installation: 00C to +500C
Humidity 5 to 95% (non-condensing)

Mounting orientation Horizontal or Vertical


0 – 2000m: No derating
Installation at altitudes
>2000m: Reduction of environmental temperature by
above sea level
0.50C per 100m
Protection type IP 20
Mechanical
Spacing 12.5 +0.2mm
characteristics
Required accessories X20TB12 Standard X20 terminal block (12-pin)
X20 Standard bus module, internal I/O supply is
X20BM11
interconnected
Connection details Pin assignments Connection example

Copyright © ALSTOM 2009.


ALSTOM Power Energy Management Business 9, rue Ampère 91345 MASSY Cedex France 2/2
Customer Support: helpdesk.control-systems@power.alstom.com www.power.alstom.com x
ALSPA Automation Cell
CE1000 & CE1500 Controllers
D09322 - Digital Output Module

Datasheet

2009-10-15
PTP20A43047 en Rev D

D09322 Digital Output Module


The DO9322 is a module of the ALSPA CE1000 and
CE1500 controllers.
The DO9322 module is equipped with twelve outputs for
1-wire connections. The DO9322 is designed for source
output wiring.
The main features are:
12 digital outputs,
Source connection,
1-wire connection,
Integrated output protection.

FEATURES D09322

Short description I/O Module Twelve 24V DC digital outputs for 1-wire connections

Digital outputs Rated voltage 24V DC

Rated output current 0.5A

Total current 6.0A

Output circuit Source


Thermal cut-off for over-current and short circuit,
Output protection
integrated protection for switching inductances

Datasheet_Template_RevH (PTP20A43015 en H) - Copyright © ALSTOM 2009. ALSTOM, the ALSTOM logo and any alternative version thereof are trademarks and
service marks of ALSTOM. The other names mentioned, registered or not, are the property of their respective companies. The technical and other data contained in this
document is provided for information only. Neither ALSTOM, its officers and employees accept responsibility for or should be taken as making any representation or
warranty (whether express or implied) as to the accuracy or completeness of such data or the achievement of any projected performance criteria where these are
1/2
indicated. ALSTOM reserves the right to revise or change this data at any time without further notice. helpdesk.control-systems@power.alstom.com
CE1000 & CE1500 Controllers
D09322 - Digital Output Module

2009-10-15
PTP20A43047 en Rev D

I/O function per channel, Operating state, Module


General information Status display
status
Outputs: Yes, with status LED and software status
(output error status)
Diagnostics
Operating Status: Yes, with status LED
Module Status: Yes, with status LED
Certification CE, C-UL-US, GOST-R (in development)
Channel – Bus: Yes
Electrical isolation
Channel – Channel: No
Bus: Typ. 0.21W
Power consumption
I/O Internal: Typ. 0.99W
Horizontal Installation: 00C to +550C
Operational conditions Operating temperature
Vertical Installation: 00C to +500C
Humidity 5 to 95% (non-condensing)
Mounting orientation Horizontal or vertical
0 – 2000m: No derating
Installation at altitudes above
>2000m: Reduction of environmental temperature by
sea level
0.50C per 100m
Protection type IP20
Mechanical
Spacing 12.5 +0.2mm
characteristics
Required accessories X20TB12 Standard X20 terminal block (12-pin)
X20 standard bus module, internal I/O supply is
X20BM11
interconnected
Connection details Pin assignments Connection example

Copyright © ALSTOM 2009.


ALSTOM Power Energy Management Business 9, rue Ampère 91345 MASSY Cedex France 2/2
Customer Support: helpdesk.control-systems@power.alstom.com www.power.alstom.com x
ALSPA Automation Cell
CE1000 & CE1500 Controllers
DI9372 - Digital Input Module

Datasheet

2009-10-15
PTP20A43042 en Rev D

DI9372 Digital Input Module


The DI9372 is a module of the ALSPA CE1000 and CE1500
controllers.
The DI9372 module is equipped with twelve inputs for 1-wire
connections. The DI9372 is designed for source input wiring.
The main features are:
12 digital inputs,
Source connection,
1-wire connection,
Software input filter can be configured for entire module

FEATURES DI9372
Short description I/O Module Twelve 24V DC digital inputs for 1-wire connections
Digital inputs Rated voltage 24V DC
Hardware input filter š100Ŧs
Default 1ms, can be configured between 0 and 25ms in
Software input filter
0.2ms intervals
Input circuit Source
General information Status display I/O function per channel Operating state Module status
Operating Status : Yes, with status LED
Diagnostics
Module Status : Yes, with status LED
Certification CE, C-UL-US, GOST-R(in development)
Channel – Bus: Yes
Electrical isolation
Channel – Channel: No
Bus : Typ. 0.2W
Power consumption
I/O Internal : Max. 1.56W

Datasheet_Template_RevH (PTP20A43015 en H) - Copyright © ALSTOM 2009. ALSTOM, the ALSTOM logo and any alternative version thereof are trademarks and
service marks of ALSTOM. The other names mentioned, registered or not, are the property of their respective companies. The technical and other data contained in this
document is provided for information only. Neither ALSTOM, its officers and employees accept responsibility for or should be taken as making any representation or
warranty (whether express or implied) as to the accuracy or completeness of such data or the achievement of any projected performance criteria where these are
1/2
indicated. ALSTOM reserves the right to revise or change this data at any time without further notice. helpdesk.control-systems@power.alstom.com
CE1000 & CE1500 Controllers
DI9372 - Digital Input Module

2009-10-15
PTP20A43042 en Rev D

Horizontal Installation: 00C to +550C


Operational condition Operating temperature
Vertical Installation: 00C to +500C
Humidity 5 to 95% (non-condensing)
Mounting orientation Horizontal or vertical
0 – 2000m: No derating
Installation at altitudes above
>2000m: Reduction of environmental temperature by
sea level
0.50C per 100m
Protection type IP20
Storage and transport
Temperature -25 0C to +70 0C
conditions
Humidity 5 to 95% (non-condensing)
Mechanical
Spacing 12.5 +0.2mm
characteristics
Required accessories X20TB12 Standard X20 terminal block (12-pin)
X20 standard bus module, internal I/O supply is
X20BM11
interconnected
Pin assignments Connection example

Copyright © ALSTOM 2009.


ALSTOM Power Energy Management Business 9, rue Ampère 91345 MASSY Cedex France 2/2
Customer Support: helpdesk.control-systems@power.alstom.com www.power.alstom.com x
A

ALSPA Automation Cell


CE1000 & CE1500 Controllers
DI9371 : 12 Sink Digital Inputs

Datasheet

2009-12-08
PTP20A43041-en-E

In the ALSPA Automation Cell, the CE1000 & CE1500 field


controllers propose a large range of I/O modules.
The DI9371 module is equipped with Twelve 24 VDC
digital inputs for 1-line connection.
The DI9371 is designed for sink input wiring.
The main features are:
12 digital inputs,
Sink connection,
1-wire connection,
Software input filter can be configured for entire
module

FEATURES DI9371
Short Description I/O Module 12x 24V DC digital inputs for 1-wire connections
Digital Inputs Rated Voltage 24V DC

Hardware Input Filter ů100us

Default 1ms, can be configured between 0 and 25ms in


Software Input Filter
0.2ms intervals
Input Circuit Sink
General Information Status Display I/O function per channel, Operating state, Module status
Operating Status: Yes, with status LED
Diagnostics
Module Status: Yes, with status LED
Certification CE, C-UL-US (in development), GOST-R

PTP20A43015 en Rev M - Copyright © ALSTOM 2009. ALSTOM, the ALSTOM logo and any alternative version thereof are trademarks and service marks of ALSTOM.
The other names mentioned, registered or not, are the property of their respective companies. The technical and other data contained in this document is provided for
information only. Neither ALSTOM, its officers and employees accept responsibility for or should be taken as making any representation or warranty (whether express or
implied) as to the accuracy or completeness of such data or the achievement of any projected performance criteria where these are indicated. ALSTOM reserves the right
1/2
to revise or change this data at any time without further notice. helpdesk.control-systems@power.alstom.com
CE1000 & CE1500 Controllers
DI9371 : 12 Sink Digital Inputs

2009-12-08
PTP20A43041-en-E

Channel – Bus: Yes


Electrical Isolation
Channel – Channel: No
Bus: Typ. 0.18W
Power Consumption I/O Internal: -
I/O External: Max. 1.75W
Operational Horizontal Installation: 00C to +550C
Operating Temperature
Conditions Vertical Installation: 00C to +500C
Humidity 5 to 95% (non-condensing)
Mounting Orientation Horizontal or vertical
0 – 2000m: No derating
Installation at altitudes
>2000m: Reduction of environmental temperature by 0.50C
above sea level
per 100m
Protection Type IP20
Storage and Transport
Temperature -250C to +700C
Conditions
Humidity 5 to 95% (non-condensing)
Mechanical
Spacing 12.5 +0.2mm
Characteristics
Required Accessories X20TB12 Standard X20 terminal block(12-pin)
X20 standard bus module, internal I/O supply is
X20BM11
interconnected
Connection Details Pin assignments Connection example

Copyright © ALSTOM 2009.


ALSTOM Power Energy Management Business 9, rue Ampère 91345 MASSY Cedex France 2/2
Assistance Customer: helpdesk.control-systems@power.alstom.com www.power.alstom.com x
;36
7KH;36VXSSO\PRGXOHLVHTXLSSHGZLWKDIHHGIRUWKH;;OLQNDVZHOODVWKHLQWHUQDO,2VXSSO\

6KRUWGHVFULSWLRQ
3RZHUVXSSO\PRGXOH 9'&VXSSO\PRGXOHIRU,2DQGEXV

*HQHUDOLQIRUPDWLRQ
6WDWXVLQGLFDWRUV 2YHUORDGRSHUDWLQJVWDWXVPRGXOHVWDWXV
'LDJQRVWLFV
0RGXOHUXQHUURU <HVZLWKVWDWXV/('DQGVRIWZDUHVWDWXV
2YHUORDG <HVZLWKVWDWXV/('DQGVRIWZDUHVWDWXV
3RZHUFRQVXPSWLRQ
%XV :
,2LQWHUQDO :
$GGLWLRQDOSRZHUGLVVLSDWLRQFDXVHGE\WKH 
DFWXDWRUV UHVLVWLYH >:@
(OHFWULFDOLVRODWLRQ
,2IHHG,2VXSSO\ 1R
Ŷ 6XSSO\ IRU ;; /LQN DQG LQWHU
;;/LQNIHHG;;/LQNVXSSO\ <HV
QDO,2VXSSO\
&HUWL¿FDWLRQ
Ŷ (OHFWULFDO LVRODWLRQ RI IHHG DQG F8/XV <HV
;;/LQNVXSSO\ &( <HV
Ŷ 5HGXQGDQF\ RI ;; /LQN VXS *2675 <HV
SO\ SRVVLEOH E\ RSHUDWLQJ PXO
;;/LQNVXSSO\LQSXW
WLSOHVXSSO\PRGXOHVVLPXOWDQH
,QSXWYROWDJH 9'&
RXVO\
,QSXWFXUUHQW 0D[$
)XVH ,QWHJUDWHGFDQQRWEHH[FKDQJHG
5HYHUVHSRODULW\SURWHFWLRQ <HV
 

;;/LQNVXSSO\RXWSXW


5DWHGRXWSXWSRZHU :
3DUDOOHORSHUDWLRQ <HV
5HGXQGDQWRSHUDWLRQ <HV
2YHUORDGEHKDYLRU 6KRUWFLUFXLWWHPSRUDU\RYHUORDGSURWHFWLRQ
 
   
 

 



 
,QSXW,2VXSSO\
 
,QSXWYROWDJH 9'&
)XVH 5HFRPPHQGHGSUHIXVLQJPD[$VORZEORZ

2XWSXW,2VXSSO\
PS 5DWHGRXWSXWYROWDJH 9'&
3HUPLWWHGFRQWDFWORDG $

2SHUDWLQJFRQGLWLRQV
0RXQWLQJRULHQWDWLRQ
T 10 A

X2X Link +
slow-blow
+ I/O
9HUWLFDO <HV
+RUL]RQWDO <HV
Power supply _ _ Power supply

+24 VDC
GND
(1SURWHFWLRQ ,3

(QYLURQPHQWDOFRQGLWLRQV
7HPSHUDWXUH
2SHUDWLRQ
9HUWLFDOLQVWDOODWLRQ WRƒ&
+RUL]RQWDOLQVWDOODWLRQ WRƒ&
5HODWLYHKXPLGLW\

;6\VWHP 
6XSSO\PRGXOHV

;36
2SHUDWLRQ WR

0HFKDQLFDOFKDUDFWHULVWLFV
1RWH 2UGHU[;7%WHUPLQDOEORFNVHSDUDWHO\
2UGHU[;%0VXSSO\PRGXOHVHSDUDWHO\
6SDFLQJ PP

7KHVSHFL¿HGYDOXHVDUHPD[LPXPYDOXHV7KHH[DFWFDOFXODWLRQLVDOVRDYDLODEOHIRUGRZQORDGDVDGDWDVKHHWZLWKWKHRWKHUPRGXOHGRFXPHQWDWLRQRQWKH% 5
KRPHSDJH

,QSDUDOOHORSHUDWLRQRQO\RIWKHUDWHGSRZHUFDQEHDVVXPHG3OHDVHHQVXUHWKDWDOOSDUDOOHORSHUDWLQJSRZHUVXSSOLHVDUHVZLWFKHGRQDQGRIIVLPXOWDQHRXVO\

5HTXLUHGDFFHVVRULHV
;%0 ;VXSSO\EXVPRGXOHLQWHUQDO,2VXSSO\LVLVRODWHGWRWKHOHIW 
;7% ;WHUPLQDOEORFNSLQ9FRGHG 

 ;6\VWHP
ALSPA Automation Cell
CE1000 Controller
BB80 - Bus Module

Datasheet

2009-10-15
PTP20A43062 en Rev C

BB80 Bus Module


The BB80 bus is a module of the ALSPA CE1000
controller.
The BB80 bus module is the basis for all X20 bus
controllers. The left and right locking plates are included in
the delivery.

FEATURES BB80

Bus controller – backplane for bus controller fieldbus


Short description Bus module
interface and bus controller supply module
Bus: -
General information Power consumption
I/O internal: -
Certification CE, C-UL-US(in development), GOST-R (in development)
Operational Horizontal installation: 00C to +550C
Operating temperature
conditions Vertical installation: 00C to +500C
Humidity 5 to 95%, non-condensing

Datasheet_Template_RevH (PTP20A43015 en H) - Copyright © ALSTOM 2009. ALSTOM, the ALSTOM logo and any alternative version thereof are trademarks and
service marks of ALSTOM. The other names mentioned, registered or not, are the property of their respective companies. The technical and other data contained in this
document is provided for information only. Neither ALSTOM, its officers and employees accept responsibility for or should be taken as making any representation or
warranty (whether express or implied) as to the accuracy or completeness of such data or the achievement of any projected performance criteria where these are
1/2
indicated. ALSTOM reserves the right to revise or change this data at any time without further notice. helpdesk.control-systems@power.alstom.com
CE1000 Controller
BB80 - Bus Module

2009-10-15
PTP20A43062 en Rev C

Mounting orientation Horizontal or vertical


0-2000m: No derating
Installations at altitudes above
>2000m: Reduction of environmental temperature by
sea level
0.50C per 100m
Protection type IP20
Storage and transport
Temperature -250C to +700C
conditions
Humidity 5 to 95%, non-condensing
Mechanical
Spacing 37.5+0.2mm
characteristics

Potential control

Copyright © ALSTOM 2009.


ALSTOM Power Energy Management Business 9, rue Ampère 91345 MASSY Cedex France 2/2
Customer Support: helpdesk.control-systems@power.alstom.com www.power.alstom.com x
ALSPA Automation Cell
CE1000 & CE1500 Controllers
BM11 - Bus Module

Datasheet

2009-10-15
PTP20A43061 en Rev C

BM11 Bus Module


The BM11 bus is a module of the ALSPA CE1000 and
CE1500 controllers.
The BM11 bus module is the basis for all X20 I/O
modules.
Standard bus module
The internal I/O supply is interconnected

FEATURES BM11

Short description Bus mdule Supply bus module, the internal I/O supply is interconnected
Bus: Typ. 0.13W
General information Power consumption
I/O internal: -
Certification CE, C-UL, GOST-R (in development)
Horizontal installation: 0°C to +55°C
Operational conditions Operating temperature
Vertical installation: 0°C to +50°C
Humidity 5 to 95%, non-condensing

Datasheet_Template_RevH (PTP20A43015 en H) - Copyright © ALSTOM 2009. ALSTOM, the ALSTOM logo and any alternative version thereof are trademarks and
service marks of ALSTOM. The other names mentioned, registered or not, are the property of their respective companies. The technical and other data contained in this
document is provided for information only. Neither ALSTOM, its officers and employees accept responsibility for or should be taken as making any representation or
warranty (whether express or implied) as to the accuracy or completeness of such data or the achievement of any projected performance criteria where these are
1/2
indicated. ALSTOM reserves the right to revise or change this data at any time without further notice. helpdesk.control-systems@power.alstom.com
CE1000 & CE1500 Controllers
BM11 - Bus Module

2009-10-15
PTP20A43061 en Rev C

Mounting orientation Horizontal or vertical


0-2000m: No derating
Installations at altitudes above
>2000m: Reduction of environmental temperature by
sea level
0.50C per 100m
Protection type IP20
Storage and transport
Temperature -25°C to +70°C
conditions
Humidity 5 to 95%, non-condensing
Mechanical
Spacing 12.5+0.2mm
characteristics
Potential control

Copyright © ALSTOM 2009.


ALSTOM Power Energy Management Business 9, rue Ampère 91345 MASSY Cedex France 2/2
Customer Support: helpdesk.control-systems@power.alstom.com www.power.alstom.com x
ALSPA Automation Cell
CE1000 & CE1500 Controllers
BM01 - Bus Module

Datasheet

2009-10-15
PTP20A43060 en Rev C

BM01 Bus Module


The BM01 bus is a module of the ALSPA CE1000 and
CE1500 controllers.
The BM01 bus module is the basis for all X20 supply
modules.
The main features are:
Basis for all X20 supply modules
For creating electrical potential groups
The internal I/O supply is interrupted towards the left

FEATURES BM01

Supply bus module, internal I/O supply is interrupted to the


Short Description Bus Module
left
Bus: Typ. 0.13W
General Information Power Consumption
I/O internal: -
Certification CE, C-UL, GOST-R (in development)
Operational Horizontal installation: 00C to +550C
Operating Temperature
Conditions Vertical installation: 00C to +500C
Humidity 5 to 95%, non-condensing

Datasheet_Template_RevH (PTP20A43015 en H) - Copyright © ALSTOM 2009. ALSTOM, the ALSTOM logo and any alternative version thereof are trademarks and
service marks of ALSTOM. The other names mentioned, registered or not, are the property of their respective companies. The technical and other data contained in this
document is provided for information only. Neither ALSTOM, its officers and employees accept responsibility for or should be taken as making any representation or
warranty (whether express or implied) as to the accuracy or completeness of such data or the achievement of any projected performance criteria where these are
1/2
indicated. ALSTOM reserves the right to revise or change this data at any time without further notice. helpdesk.control-systems@power.alstom.com
CE1000 & CE1500 Controllers
BM01 - Bus Module

2009-10-15
PTP20A43060 en Rev C

Mounting Orientation Horizontal or vertical


0-2000m: No derating
Installations at altitudes above
>2000m: Reduction of environmental temperature by
sea level
0.50C per 100m
Protection Type IP20
Storage and Transport
Temperature -250C to +700C
Conditions
Humidity 5 to 95%, non-condensing
Mechanical
Spacing 12.5+0.2mm
Characteristics
Potential Control

Copyright © ALSTOM 2009.


ALSTOM Power Energy Management Business 9, rue Ampère 91345 MASSY Cedex France 2/2
Customer Support: helpdesk.control-systems@power.alstom.com www.power.alstom.com x
ALSPA Automation Cell
CE1000 & CE1500 Controllers
TB12 - Terminal Block

Datasheet

2009-10-15
PTP20A43063 en Rev C

TB12 terminal block.


The X20 is a module of the ALSPA CE1000 and CE1500
controllers.
The X20 modules are wired using the TB12 terminal
blocks.
The main features are:
Tool-free wiring with push-in technology
Simple wire release using lever
Ability to label each terminal
Plain text labelling also possible
Test access for standard probes
Potential for customer coding

FEATURES TB12

Short description Terminal block 12 pin

Terminal block Type of terminal Push-in terminal


Left – right: 4.2mm
Distance between contacts
Above – below: 10.96mm
Contact resistance š5mť

Rated voltage 230V AC

Rated current 10A / contact


Solid wire line: 0.08mm2 – 2.5mm2 / AWG 28 – 14
Fine wire line: 0.25mm2 – 2.5mm2 / AWG 24 – 14
Connection cross section
With wire tip sleeves: 0.25mm2 – 1.5mm2 / AWG 24 – 16
Up to 2 x 0.75 mm2 with double wire tip sleeves
Cable type Only copper wires (no aluminium wires)

Datasheet_Template_RevH (PTP20A43015 en H) - Copyright © ALSTOM 2009. ALSTOM, the ALSTOM logo and any alternative version thereof are trademarks and
service marks of ALSTOM. The other names mentioned, registered or not, are the property of their respective companies. The technical and other data contained in this
document is provided for information only. Neither ALSTOM, its officers and employees accept responsibility for or should be taken as making any representation or
warranty (whether express or implied) as to the accuracy or completeness of such data or the achievement of any projected performance criteria where these are
1/2
indicated. ALSTOM reserves the right to revise or change this data at any time without further notice. helpdesk.control-systems@power.alstom.com
CE1000 & CE1500 Controllers
TB12 - Terminal Block

2009-10-15
PTP20A43063 en Rev C

Copyright © ALSTOM 2009.


ALSTOM Power Energy Management Business 9, rue Ampère 91345 MASSY Cedex France 2/2
Customer Support: helpdesk.control-systems@power.alstom.com www.power.alstom.com x
Intel® Atom™ Regular-Size Automation

UNO-2473G Computer w/ 4 x GbE, 3 x mPCIe,


HDMI/VGA

NEW Features
ƒ 4th Generation Intel® Atom™ Processor up to 1.91GHz with 4GB DDR3L
Memory
ƒ 4 x GbE, 4 x USB 2.0/3.0, 2 x RS-232, 2 x RS-422/485, 1 x VGA, 1 x HDMI,
Audio
ƒ Comprehensive Palm, Small, Regular-size form-factor
ƒ Compact with Fanless Design
ƒ Rubber Stopper Design with Captive Screw
ƒ Diverse system I/O and Isolated Digital I/O by iDoor Technology
ƒ 3G/GPS/GPRS/Wi-Fi Communication by iDoor Technology
ƒ Supports MRAM by iDoor Technology
ƒ Chassis Grounding Protection
ƒ LAN Redundancy (Teaming)
ƒ Fault-Protected RS-485 Transceivers With Extended Common-Mode Range

RoHS
COMPLIANT
2002/95/EC

Introduction
Advantech’s UNO-2000 series of Embedded Automation Computers are fanless with highly ruggedized with an embedded operating system (Linux-Embedded). It also includes iDoor
technology which supports automation feature extensions such as industry fieldbus communication, Wi-Fi/3G, Digital I/O, including Palm, Small, and Regular-size Form-Factors
with indicated market segments in terms of entry, value and performance product positioning. Both entry and value Embedded Automation Computers feature specific functions and
they are suitable for data gateway, concentrator and data server applications. The performance model can shorten your development time and offer multiple networking interfaces to
fulfill a diverse range of requirements.

Specifications Environment
ƒ Operating Temperature UNO-2473G-E3AE: - 20 ~ 60°C (-4 ~ 140°F) @ 5 ~ 85% RH
with 0.7m/s airflow
General UNO-2473XXXXX: - 40 ~ 60°C (-40 ~ 140°F) @ 5 ~ 85% RH
ƒ Certification CE, FCC, UL, CCC, BSMI with 0.7m/s airflow
ƒ Dimensions ( W x D x H ) 252 x 149 x 62 mm (9.9" x 5.9" x 2.4") ƒ Storage Temperature - 40 ~ 85°C ( -40 ~ 185°F)
ƒ Form Factor Regular Size ƒ Relative Humidity 10 ~ 95% RH @ 40°C, non-condensing
ƒ Enclosure Aluminum Housing ƒ Shock Protection Operating, IEC 60068-2-27, 50G, half sine, 11ms
ƒ Mounting Stand, Wall, VESA (Optional), Din-rail (Optional) ƒ Vibration Protection Operating, IEC 60068-2-64, 2Grms, random, 5 ~ 500Hz,
ƒ Weight (Net) 1.6kg (3.5lbs) 1hr/axis (mSATA)
ƒ Power Requirement 24VDC ± 20% Operating, IEC 60068-2-64, 0.7Grms, random, 5 ~ 500Hz,
ƒ Power Consumption 28W (Typical), 48W (Max) 1hr/axis (HDD)
ƒ OS Support Microsoft® Windows 7/8 ƒ Ingress Protection IP40

System Hardware Application Software


ƒ BIOS AMI UEFI 128Mbit Flash BIOS
ƒ Watchdog Timer Programmable 256 levels timer interval, from 1 to 255 sec Version : V2.1 or above
ƒ Processor Intel® Atom™ Processor E3845 1.91 GHz Quad Core, 2MB L2 An innovative remote device management software, allowing
ƒ System Chip Intel Atom SoC integrated efficient remote monitoring, quick recovery & backup, and
ƒ Memory On-board 4GB DDR3L 1600 MHz real-time remote configuration, to create a more intelligent and
ƒ Graphics Engine Intel® HD Graphics: Gen7 with 4EU interconnected embedded computing solution.
ƒ Ethernet Intel® i210-IT GbE, 802.1Qav, IEEE1588/802.1AS, 802.3az Version : V7.1 or above
ƒ LED Indicators LEDs for Power, battery, LAN (Active, Status), Tx/Rx and HDD
ƒ Storage One mSATA WebAccess, as the core of Advantech’s IoT solution, is full web
One drive bay for SATA 2.5" HDD (Compatible with 9.5mm browser-based software package for HMI and SCADA software.
height HDD) All HMI and SCADA software features including: Animated
CFast drive by iDoor Technology (Optional) Graphics Displays, Real-time Data, Control, Trends, Alarms
ƒ Expansion 3 x Full-size mPCIe slot, mPCIe 2.0 and Logs, are available in a standard web browser. WebAccess
is built around the latest internet technologies. With its open
I/O Interfaces architecture, vertical domain applications can easily be
integrated.
ƒ Serial Ports 2 x RS-232, DB9, 50~115.2kbps
2 x RS-422/485, DB9, auto flow control, 50~115.2kbps Version : V2.0.3.8 or above
ƒ LAN Ports 4 x RJ45, 10/100/1000 Mbps IEEE 802.3u 1000Base-T Fast Panel Express, a windows based HMI mini SCADA, realizes
Ethernet the cross platform flexibility offered by WebOP Designer to
ƒ USB Ports 4 x USB Ports (3 x USB2.0, 1 x USB3.0 compliant ) switch hardware for the consideration of cost and performance
ƒ Displays 1 x VGA (2560x1600) become an easy job. Panel Express software provides the best
1 x HDMI (1920x1200) economic and express solution for data intensive high-end
ƒ Audio Line-In, Line-Out HMI applications.
ƒ Power Connector 1 x 3 Pins, Terminal Block
ƒ Grounding Protection Chassis Grounding Version : V2.0.3.8 or above
An easy to use integrated development tool featuring solution-
oriented screen objects, high-end graphics, Windows fonts for
multi-language applications. WebOP runtime, a part of WebOP
Designer, guarantees reliability and performance because of the
minimum system overhead, high communication data rates,
and sub-second screen switching.

Embedded Automation Computers


All product specifications are subject to change without notice Last updated : 24-Jul-2015
UNO-2473G

Dimensions Unit: mm
252.8
251.8
241.8
227.8

104.6
111.1
117.6
138.4
149.3
R2
R2. .0
7
10.5

1.6
59.1
61.5

Front I/O View Rear I/O View


HDMI RJ45 LAN Power Connector Audio Ports
USB 2.0/3.0 Ports VGA RS-422/485 RJ45 LAN Rubber Stopper

Power LED Transmit & Receive LEDs BTR, HDD & PWR LED Lights Antenna RS-232 iDoor Expansion Slot
Reset Button Chassis Grounding RS-232 Antenna

Ordering Information Accessories


ƒ UNO-2473G-E3AE Intel® Atom E3845 1.91GHz, 4GB, 4 x LANs, ƒ 1757002321 63WC to DC UNO series power adapter (Industrial Grade)
3 x mPCIe ƒ PWR-249-AE 65W AC to DC power adapter (Commercial Grade)
ƒ 1702002600 Power Cable US Plug 1.8 M (Industrial Grade)
ƒ 1702002605 Power Cable EU Plug 1.8 M (Industrial Grade)
iDoor Modules ƒ 1702031801 Power Cable UK Plug 1.8 M (Industrial Grade)
ƒ 1700000596 Power Cable China/Australia Plug 1.8 M (Industrial Grade)
ƒ PCM-24D4R2-AE 4-Port Non-Isolated RS-232 mPCIe, DB37 ƒ 1700001524 Power Cable 3-pin US type 1.8 M (Commercial Grade)
ƒ PCM-24D4R4-AE 4-Port Non-Isolated RS-422/485 mPCIe, DB37 ƒ 170203183C Power Cable 3-pin EU type 1.8 M (Commercial Grade)
ƒ PCM-26D2CA-AE 2-Port Isolated CANBus mPCIe, CANOpen, DB9 ƒ 170203180A Power Cable 3-pin UK type 1.8 M (Commercial Grade)
ƒ PCM-27D24DI-AE 24-Channel Isolated Digital I/O w/ counter mPCIe,
DB37
ƒ PCM-2300MR-AE MR4A16B, MRAM, 2 MByte, mPCIe
Embedded OS & Automation Software
ƒ PCM-23U1DG-AE USB Slot w/ Lock for USB Dongle ƒ 2070013268 Image WES7P X64 MUI. V4.12 B001 for UNO-2473G-Ex
ƒ PCM-24S2WF-AE WiFi 802.11 a/b/g/n 2T2R w/ Bluetooth4.0, Half-size ƒ 968WEXP003X PanelExpress V2.0 300 tags S/W license
mPCIe, 2-port SMA ƒ 968WEXP015X PanelExpress V2.0 1500 tags S/W license
ƒ PCM-24U2U3-AE 2-Port USB 3.0, mPCIe, USB-A type ƒ 968WEXP050X PanelExpress V2.0 5000 tags S/W license
ƒ PCM-24R2GL-AE 2-Port Gigabit Ethernet, mPCIe, RJ45
ƒ PCM-24S23G-AE Wide-Temp 3.75G HSPA and GPS, 2-in-1, Full-size
mPCIe w/ Redundant SIM Card holder, 2-port SMA

Online Download www.advantech.com/products


FPM-5151G
FPM-5171G 15" XGA / 17" SXGA / 19" SXGA
Industrial Monitors with Resistive
FPM-5191G Touchscreens, Direct-VGA, and DVI Ports

NEW Features
ƒ 15" XGA or 17" / 19" SXGA TFT LCDs
ƒ Direct VGA & DVI-D input interface
ƒ Lockable OSD keys with 2 user-defined contrast/brightness settings
ƒ Flat-sealed front panel
ƒ Robust design with anti-rust chassis and aluminum die-cast front panel
ƒ Front accessible USB connector
ƒ Combo RS-232 & USB interface for touchscreen function (optional)
ƒ Supports industrial 10-30 VDC power input with Phoenix jack
ƒ Supports panel, wall, desktop, rack or VESA arm mounting
ƒ Front panel is NEMA4/IP65 compliant

Introduction
The FPM-5000G series provides 15", 17" and 19" color TFT LCD flat panel monitors specifically designed for industrial applications. With a viewing size from 15" to 19", they present
ample display areas as well as vivid and sharp images. It features Direct-VGA & DVI-D signal transmission, which allows VGA control cards to be used in your system. The onscreen
display allows users to adjust the images on the screen with two user-defined settings. The front access USB connector provides easy access the controller, and the industrial 10-30
Vdc wide range power support makes this product an excellent option for Factory and Machine Automation display solutions.

Specifications
General Touchscreen (Optional)
ƒ Button Controls OSD control pad on rear side with lockable function ƒ Sensor AMT
ƒ Certification BSMI, CCC, CE, FCC Class B, UL ƒ Driver Penmount 6000
ƒ Dimensions (WxHxD) 5151G: 449.92 x 315.63 x 50.5 mm (17.71" x 12.43" x 2") ƒ Type 8-wire / 8-wire / 5-wire Resistive
5171G: 481.9 x 355.9 x 55 mm (18.97" x 14.01" x 2.17") ƒ Interface RS-232 & USB
5191G: 481.93 x 384.6 x 59 mm (18.97" x 15.14" x 2.32") ƒ Lifespan 10/ 10/ 36 million with a silicone rubber of R8 finger,
ƒ Enclosure Front panel: Aluminum and flat-sealed writing rate is by 250g at 2 times/s
Rear cover: Anti-rust coating ƒ Light Transmission > 80%
ƒ Mounting Panel, wall, desktop, VESA arm, or 19" rackmount ƒ OS Support Windows 2000, XP, Vista, 7, XPe, CE and Linux
ƒ Power Input Phoenix Jack - 10 ~ 30 VDC input ƒ Power Consumption +5 V @ 100 mA
Optional external 57 W power adapter, with AC
ƒ Touch Resolution Linearity
100 V ~ 240 V input and DC +12 V @ 4.7A output
ƒ Power Consumption 18 W + 20% / 31 W + 20% / 32 W + 20% Environment
ƒ USB Front USB access for extension ƒ Operation Temperature 0 ~ 50°C (32 ~ 122°F)
ƒ Video Port VGA & DVI-D ƒ Storage Temperature -20 ~ 60°C (-4 ~ 140°F)
ƒ Weight (Net) 6 kg (13.22 lbs) / 8 kg (17.63 lbs) / 10 kg (22.04 lbs) ƒ Humidity (Storage) 10 ~ 90% non-condensing
LCD Display ƒ Waterproof Front panel is NEMA4/IP65 compliant
ƒ Vibration 5 ~ 500 Hz, 1 Grms (Operating, Random)
ƒ Display Type XGA/ SXGA/ SXGA TFT LCDs
ƒ Display Size 15"/ 17"/ 19"
ƒ Max. Resolution 1024 x 768 / 1280 x 1024 / 1280 x 1024 Ordering Information
ƒ Max. Color 16.2M ƒ FPM-5191G-X0AE 19" SXGA Ind. Monitor
ƒ Viewing Angle (H/V°) 160/130, 170/160, 178/178 ƒ FPM-5191G-R3AE 19" SXGA Ind. Monitor w/Resistive TS (RS-232, USB)
ƒ Luminance (cd/m2) 250 / 380 / 300 ƒ FPM-5171G-X0AE 17" SXGA Ind. Monitor
ƒ Backlight Life (hrs) 50,000 ƒ FPM-5171G-R3AE 17" SXGA Ind. Monitor w/Resistive TS (RS-232, USB)
ƒ Contrast Ratio 700:1 / 1000:1 / 1300 : 1 ƒ FPM-5151G-X0AE 15" XGA Ind. Monitor
ƒ FPM-5151G-R3AE 15" XGA Ind Monitor w/Resistive TS (RS-232, USB)

Industrial Monitors and Display Solutions


FPM-5151G / FPM-5171G / FPM-5191G

Dimensions Unit: mm

FPM-5151G: 422.40 [16.63]


FPM-5151G: 3.00 [0.12] FPM-5171G: 449.97 [17.72]
FPM-5171G: 6.00 [0.24] FPM-5191G: 445.92 [17.56]
FPM-5191G: 7.00 [0.28]
257.50 [10.14]
FPM-5151G: 449.92 [17.71] FPM-5151G: 50.50 [2.00]
FPM-5171G: 481.93 [18.97] FPM-5171G: 55.00 [2.17] 100.00 [3.94]
FPM-5191G: 481.93 [18.97] FPM-5191G: 59.00 [2.32] 75.00 [2.95]

FPM-5151G: 291.40 [11.47]


FPM-5171G: 334.97 [13.19]
FPM-5191G: 334.44 [13.17]
FPM-5151G: 315.63 [12.43]
FPM-5171G: 355.87 [14.01]
FPM-5191G: 384.60 [15.14]

M4 M4

100.00 [3.94]
256.40 [10.09]

75.00 [2.95]
M4 M4

M4 M4
M4 M4

Panel Cut-out Dimensions: FPM-5151G: 424 X 293 mm


FPM-5171G: 454 X 338 mm
Panel Cut-out Dimensions: FPM-5151G: 424 x 293 FPM-5191G: 454 X 338
mm (16.69" mm
x 11.54")
FPM-5171G: 454 x 338 mm (17.87" x 13.31")
FPM-5191G: 454 x 338 mm (17.87" x 13.31")

Accessories I/O View


ƒ FPM-5151G-SMKE FPM-5151G/5171G Stand Kit 10-30 VDC Power Input
ƒ FPM-5191G-SMKE FPM-5191G Stand Kit with Phoenix Jack VGA Port
ƒ IPPC-6152A-RMKE IPPC-6152A/FPM-5151G Rack Mount Kit 12V Power Input
TS Interface - USB Port with DIN-rail
ƒ IPPC-6172A-RMKE IPPC-6172A/FPM-5171G Rack Mount Kit
ƒ IPPC-6192A-RMKE IPPC-6192A/FPM-5191G Rack Mount Kit
TS Interface -
ƒ 1702002600 Power Cable US Plug 1.8 M RS-232 Port
ƒ 1702002605 Power Cable EU Plug 1.8 M
ƒ 1702031801 Power Cable UK Plug 1.8 M
ƒ 1702031836 Power Cable China/Australia Plug 1.8 M
ƒ 1757002742 Adapter AC 90-264V 57W SPU63-105 Panel Mount T/S Interface Switch DVI-D port
Note: VESA mounting screw length: M4x6mm

Front Accessible USB Port Back View


VESA Mount

LCD OSD Control Keys Wallmount

Online Download www.advantech.com/products


S 7-330 CE
Multifunctional Power Meter

Measurement of current, voltage, active, Dual relay contacts for energy or alarm out-
reactive and apparent power, power factor, put (option).
line frequency, energy, harmonic and MD. Dual analong output (option).
High-brightness LED display. Setting protected by password.
Extreme accuracy up to 0.2%. Memory of all setting value and energy data
Programmable adjustment for current and over ten years.
voltage transformers ratio. Memory of the Max. And Min. Value
With RS485 output. (V. A. W)
Indication of neutral current. Outside dimension compatible for DIN Stan-
dard 96 X 96mm.

TAIK ELECTRIC
Multifunctional Power Meter S 7 -330
The S7-330 is an upgraded model under the S7 Series of Multifunctional Power Meters. This
new model equips not only original features but also adds new state of the art characteristics
and functions.

The S7-330 is a microprocessor-based instrument with a 16 bit algorithm witch is used for
the measurement, monitoring, and management of electrical parameters in either single-
phase or 3-phase systems, This meter offers outstanding quality, flexibility, and ease of use
in a low-cost and compact configuration.

These added characteristics include actual demand measurement in 2 parameters (A,


W ). The demand measurement of these selected parameters will be programmed by
setting the time in a period. This unit also equips 2 galvanically isolated analog outputs
(DC4-20mA or DC1-5V), and these measured electrical parameters can be assigned to
the required analong signal fur a aprecise control to the load. Furthermore, this model
also aiiow for the acquirement of mea-
Multifunctional Power Meter
sured signals with harmonics up to the
31th content as the C % waveform is in a
distored and non- E continuous condition.
The S7-330 is pro- M k V A r W gammable measuring
instrument for monitor- ing voltage, current,
C %
power factor, active power, reactive power,
E
apparent power, freqency, harmonic
M k V A r W ENTER
components and max. demand in A, W.
C %
SET
TAIK's new S7-330 E is also programmed
by 5 push buttons on M k V A r W h Z the front panel, and
the displaying screen in 3 rows of 4 digits
S7-330 TAIK
resolution on all in- stantaneous alphanu-
meric readings is luminesced by the selected bright LEDs. With this meter, the required
electric parameters can be effectively monitored by relay contactors, analong outputs and a
convenient digital output. This meter is equipped with serial communication for a remote
control through standard interface in the form of RS-485.Meanwhile,, the S7-330 also ultilizes
the Modbus communication protocal to transmit all electrical information in a digital form to
PC, PLC, SCADA and even a display repeater.

This unit has specially designed for power monitoring applications in the field of industry,
factory and building. It features main advantages with high performance, low cost, easy
installations and stability, which can completely satisfy all customers' demand on their
applications, With a combination of innovation and conventional process is thoroughtly cre-
ated a multi-function measuring instrument for a complete resolution of all difficulties in
electricity. With this meter will save you more cost on all energy consumption.
Multifunctional Power Meter S 7 -330
SPECIFICATION CE
** Demand
Local display Total Phase 1 Phase 2 Phase 3 Accuracy Actual demand parameters A, W
L-L voltage Time of period 1 ~ 60 min. Programmable

*
0.2%
Max. demand A, W
L-N voltage 0.2%
Analog output
Line current
*

0.2%
Output DC 4 ~ 20mA (0 ~ 500Ω)
Neutral current 1% or DC 1 ~ 5V ( 1KΩ)
Output points Max. 2 points, programmable
Active power 0.5%
Output accuracy 0.5% RO.
Reactive power 0.5%
Apparent power Communication
0.5%
Interface RS485
Power factor
*

0.5% Protocol MODBUS, RTU framing


Frequency Baud rate 1200 ~ 38400 programmable
*

0.05%
Address range 1 ~255 programmable
Active energy + 0.5%
Data format N.8.1/N.8.2/O.8.1/E.8.1 pro.
Reactive energy + 0.5% Number of meter Up to 32 on standard RS485

Active energy - 0.5%


General
Reactive energy - 0.5% Dielectric strength IEC 60688, AC 2.3KV 1 minute
between Input/Output/Power
Total harmonic -1 (1)
*

2%
AC 2.8KV 1 minute between all terminal/ground
(1)
Total harmonic -V 2%
*

O
Operating temperature 0 ~ 60 C
Storage temperature -10 ~ 70 C
O
*

**

(1) up to 31th harmonic * Average value ** Full scale of ranges


Temperature coefficient 100PPM/ C O

Max. humidity 95%


Accuracy performance range
Electromagnetic Compatibility
Current range 2 ~ 120%
Withstanding impulse voltage IEC 61000-4-5
Voltage range 2 ~ 120%
Electrical transient in burst IEC 61000-4-4
Power & energy current, 2 ~ 120%, Voltage, 2 ~ 120%
Electrostatic discharge IEC 61000-4-2
Power factor range cos (sin )0.5 ~1
Electromagnetic fields immunity IEC 61000-4-3
Frequency range 45 ~ 70HZ
Wave damping IEC 255-4
Distortion level from 10% to 120%

Input voltage
Voltage range (line to line) 8 ~ 500V ORDERING INFORMATION
Voltage range (line to neutral) 5 ~ 290V
Maximum overload 750V
S7-330
Input impedance 200KΩ
Model
Input current
Current range 5A or 1A Input current
Maximum overload 6A, continuous, 50A 5 sec. 1: 1A
15A, continuous, 250A 1 se c. (Option) 5: 5A
Input burden 0.1VA O: Option
Isolation Each phase, 600V
Aux. Power supply
Starting current 1% F.S.
1: AC /DC 85 - 265 V
Power supply 2: DC 20-60 V
Nominal voltage AC/DC 85-265 V 0: Option
or DC 20-60 V(Option)
RS485 output
Burden AC 5VA,DC 5W
Y: Yes
Display N: No
Type High-brightness red LED
Digital height 0.4", 10.2mm Relay contacts or analog output
Digital format 3 rows of 4 digits 1: Relay contacts output
Digits for Wh, Varh, Vah 8 digits (two rows) 2: Analog output (Standard DC 4 ~ 20mA)
N: No
Relay contacts output for energy or alarm
Energy value 100 pulse for 1 KWh or 1KVarh Harmonic
Alarm set point 2 point, programmable Y: Yes
Relay contacts AC 240V 1 A, DC 24V 1A N: No
Multifunctional Power Meter S 7 -330
CONNECTION
1-Phase 3-Wire 1-Phase 3-Wire
P N 1 N 2

RS-485 Output

O B- A+

TC

TB TB
1K 1L 2K 2L 3K 3L 1K 1L 2K 2L 3K 3L

L3 L2 L1 N P2 P1 L3 L2 L1 N P2 P1 RS-485

TA TA

POWER SUPPLY POWER SUPPLY

Relay Contacts
Output
LOAD LOAD

1a 1G 2a 2G

TD

3-Phase 3-Wire (2CT ) 3-Phase 4-Wire


(A) (B) (C) (A) (B) (C)
R S T R S T N
Alarm or Energy
Output

TB TB
Analog Output
1K 1L 2K 2L 3K 3L 1K 1L 2K 2L 3K 3L
1+ 1- 2+ 2-
L3 L2 L1 N P2 P1 L3 L2 L1 N P2 P1

TD
TA TA

POWER SUPPLY POWER SUPPLY


Analog Output

LOAD LOAD

OUTSIDE DIMENSION(Unit:mm)

Panel Cut-Out
1+ 1 2+2 1K 1L 2K 2L 3K 3L
Max.25

TD TB 90.0 +0.5
0.0

96 96

90.0 +0.5
0.0
TC TA

O B A+ L3 L2 L1 N P2 P1

96 6.6 110.8

TAIK ELECTRIC CO., LTD.


4TH FL., NO .5, ALLEY 11, LANE 327, CHUNGSHAN RD., SEC . 2,
CHUNGHE DISTRICT, NEW TAIPEI CITY, TAIWAN , R.O.C.
TEL: 886-2-22426825 E-mail: taikco@ms15.hinet.net
FAX: 886-2-22426827 http://www.taik.com.tw
Product Specification
37622A
SPM-D2-10 Series
New Features
 USB connectivity to PC
 ToolKit configuration support
 Password protection to all variants
 Same look & feel as SPM-D
 Drop-In replacement

 Synchronization for one


Synchronizers or two circuit breakers

for 2/3-phase AC Gen-Sets  Frequency, Phase and


Voltage Matching
DESCRIPTION
 Selectable control out-
Woodward understands the time-intensive nature of Power Generation projects. Ensuring the lon-
gevity of components is one way we can make our customers successful. Woodward has supplied
puts for speed and volt-
and supported the well-established SPM-D line of synchronizers for 20+ years. With the state of age biasing
the art Drop-In replacement successor, SPM-D2 the life of this synchronizer line is now extended.
All of the SPM-D2 synchronizers are password protected and are configurable either through HMI  Compatible with a wide
as before or through ToolKit configuration tool with USB connectivity.
range of GOVs and
The SPM-D2-10 series are microprocessor-based synchronizers designed for use on two or three AVRs
phase AC generators equipped with Woodward or other compatible speed controls and automatic
voltage regulators. The SPM-D2-10 synchronizers provide automatic frequency, phase and voltage
matching using either analog- or discrete output bias signals. These synchronizers are applied to a  Circuit breaker time
wide range of prime movers and generators, as its control signals may be set to fit several types of compensation
gensets - from fast reacting diesel engines to soft reacting gas turbines.

The SPM-D2-10 synchronizers are available in 3 base models:


 Two lines bright LCD
 SPM-D2-10 … : provides 1-phase / 2-wire voltage measurement with options for analog and/or display for generator
discrete biasing signals and wide range power supply and bus values
 SPM-D2-10 …/YB: provides 3-phase / 4-wire voltage measurement with discrete biasing signals
and option for wide range power supply  Front face synchrono-
scope for easy commis-
 SPM-D2-10 …/PSY5: provides 1-phase / 2-wire voltage measurement with discrete biasing sig- sioning
nals, option for wide range power supply and 2 sets of switchable parameter set.

FEATURES  True RMS measurement


for reliable operation
 Phase match or slip frequency synchronization with voltage matching
 Two-Phase or three-phase true RMS voltage sensing of generator and bus with Class I accuracy  Configurable through
 Selectable operating modes like SPM-A (Run, Check, Permissive and Off) HMI or PC
 Synch-Check and synchronization time monitoring
 Dead bus closing of CB on demand  Wide range power sup-
 2 setting blocks, each containing 7 configurable parameters (in PSY5 variants) selectable
through DI: Frequency/Voltage control dead-band, Frequency/Voltage control time pulse, Fre-
ply available
quency/Voltage control gain, Circuit breaker time compensation
 Control outputs: Discrete raise/lower for speed and voltage in all variants, | X and XN variants:  Switchable parameter
also configurable analog signals (Voltage, Current and PWM) sets available
 Voltage and frequency control in isolated operation
 Two line bright liquid crystal display for operation, alarm, measuring values visualization and  CE Marked (RoHS 2
parametrization
 Front face with synchronoscope and indication of breaker state/control activity
compliant)
 Multi-level password protection of parameters
 Woodward ToolKit™ software for configuration via USB  UL/cUL Listed
 Two built-in languages: English, German
SPECIFICATIONS
Power supply Relay outputs .................................................................................... isolated
[Standard]..........................................................12/24 VDC (9.5 to 32 VDC) Contact material ................................................................................... AgCdO
[N, XN and NYB Packages] .................... 90 to 250Vac / 120 to 375 Vdc; Load (GP) (Vcont, relay output) AC: .......................................... 2.00 AAC@250 VAC
............................................ 100 to 240 Vac -15%/+10% (UL rating only) DC: 2.00 ADC@24 VDC / 0.36 ADC@125 VDC / 0.18 ADC@250 VDC
Intrinsic consumption ................................................................. max. 10 W Pilot Duty (PD) AC: ................................................................................. B300
Ambient temperature (operation) ............................................. -20 to 70 °C DC: 1.00 ADC@24 VDC / 0.22 ADC@125 VDC / 0.10 ADC@250 VDC
[N, XN and NYB Packages] -20 to 60 °C Analog Outputs (isolated) ......................................................freely scalable
Ambient temperature (storage) ................................................ -30 to 80 °C Type ......................................................................... ± 10 V / ± 20 mA / PWM
Ambient humidity....................................................... 95%, non-condensing Insulation voltage (continuously, AVR out) ......................................... 300 VAC
Voltage .............................................................................................. ( /) Insulation voltage (continuously, Gov out) .......................................... 100 VAC
[1] 100 Vac Rated (Vrated) ............................................ 66/115 VAC Resolution .............................................................................................. 12 Bit
Max. value (Vmax) ................................................. 150 VAC ± 10 V (scalable) ..............................................internal resistance 500 Ohms
or [4] 400 Vac Rated (Vrated) .......................................... 230/400 VAC ± 20 mA (scalable) ................................................ maximum load 500 Ohms
Max. value (Vmax) ................................................. 300 VAC Housing Front panel flush mounting ............. Type APRANORM DIN 43 700
Rated surge volt. (Vsurge) .............................. [1] 2.5kV, [4] 4.0 kV Dimensions WxHxD .......................................... 144 × 72 × 122 mm
Accuracy .......................................................................................... Class 1 Front cutout WxH .................................... 138 [+1.0] × 68 [+0.7] mm
Measuring frequency............................................... 50/60 Hz (40 to 70 Hz) Connection (screw/plug terminals depending on connector) .. 1.5 mm² or 2.5 mm²
Linear measuring range ........................................................... 1.3 x Vrated Front.................................................................................... insulating surface
Input resistance ...................................... [1]0.21 MOhms, [4]0.696 MOhms Protection System / Sealing.............................................................................
Current Rated (Irated) .................................................. [1]…/1A, [5] … /5A Front .................................IP42 with correct installation
Linear measuring range ................................................................. 3.0×Irated Front ....................... IP54 (with gasket P/N 8923-1037)
Burden .......................................................................................... < 0.15 VA Back ...................................................................... IP20
Rated short-time overcurrent (1 s) ..........................[1] 50×Irated, [5] 10×Irated Weight ........................................................................................approx. 800 g
Discrete inputs .............................................................................. isolated Listings tested according to applicable IEC standards ..................................
Input range ...................................................12/24 VDC or 18 to 250 Vac/dc ......................................................... CE, UL/cUL listing for ordinary locations
Input resistance ........................................approx. 6.8 kOhms or 68 kOhms Marine (Pending) ........................ LR (Type Approval), ABS (Type Approval)

DIMENSIONS
TERMINAL DIAGRAM
NOTE The terminals used for connection depend on the implemented functionality of each package.
The drawing below gives an overview with sample package XN – for details please see the dedicated
Technical Manual listed in the features table at the rear page.

RELATED PRODUCTS
 Load Share Synchronizer SPM-D2-11 (Product Specification # 37623)
 Digital Synchronizer and Load Control DSLC-2 (Product Specification # 37493)
 Master Synchronizer and Load Control MSLC-2 (Product Specification # 37494)
 Load Share speed control 2301E (Product Specification # 03404)
 Load Sharing Module LSM (Product Specification # 82686)
 SPM-A Synchronizer (Product Specification # 82383)
 Power Generation Learning Module (Product Specification # 03412): P/N 8447-1012
FEATURES OVERVIEW
CONTACT SPM-D2-10 Series
SPM-D2-10 Series
Package - X N XN PSY5 PSY5...W YB NYB
North & Central America
Tel.: +1 970 962 7331 Measuring / Display
Generator/System A voltage 2-ph 2-ph 2-ph 2-ph 2-ph 2-ph 3/2-ph 3/2-ph
 SalesPGD_NAandCA@woodward.com
Busbar/System B voltage 2-ph 2-ph 2-ph 2-ph 2-ph 2-ph 3/2-ph 3/2-ph
South America Control
Tel.: +55 19 3708 4800 Breaker 1 1 1 1 1 or 2 1 or 2 1 1
 SalesPGD_SA@woodward.com Synchronization 2-ph 2-ph 2-ph 2-ph 2-ph 2-ph 3/2-ph 3/2-ph
Isolated Operation        
Europe On- On- On- On- On- On-
Dead bus start functionality#1 Enhanced Enhanced
Tel. Stuttgart: +49 711 78954 510 demand demand demand demand demand demand
Tel. Kempen: +49 2152 145 331 Switchable parameter#2 - - - -   - -
 SalesPGD_EUROPE@woodward.com Controller
Discrete raise/lower: Speed  #3  #3    
Middle East & Africa Discrete raise/lower: Voltage  #3  #3    
Tel.: +971 2 6275185 Analog Output: Speed#4 -  -  - - - -
 SalesPGD_MEA@woodward.com Analog Output: Voltage#4 -  -  - - - -
PWM Output: Speed#5 -  -  - - - -
Russia I/Os
Tel.: +7 812 319 3007 Discrete alarm inputs 4 4 4 4 4 4 5 5
 SalesPGD_RUSSIA@woodward.com Discrete outputs 2 2 2 2 3 3 3 3
Analog outputs: +/- 10 V, +/- 20 mA, PWM; configurable - 2 - 2 - - - -
China USB Serial interface 1 1 1 1 1 1 1 1
Tel.: +86 512 8818 5515 Power Supply
 SalesPGD_CHINA@woodward.com 24 Vdc   - -  -  -
Wide Range: 90 to 250 VAC / 120 to 375 VDC - -   -  - 
India
Tel.: +91 124 4399 500 Accessories
 SalesPGD_INDIA@woodward.com Configuration via PC (ToolKit)        
Listings/Approvals
ASEAN & Oceania UL / cUL Listing (61010, 6200)        
Tel.: +49 711 78954 510 CE Marked        
 SalesPGD_ASEAN@woodward.com Part Numbers
Measuring inputs 100 Vac: 8440-… …-2166 …-2168 …-2174 …-2172 - - …-2167 …-2177
www.woodward.com Measuring inputs 400 Vac#6: 8440-… …-2164 …-2171 …-2175 …-2190 …-2170 …-2173 …-2176 …-2189
Technical Manual B37615 B37616 B37617
Subject to alterations, errors excepted.
#1 Dead bus start functionality
Subject to technical modifications. On-Demand: Closing of CB on demand
Enhanced: Black start (closing to de-energized second side of a breaker for following
This document is distributed for informa- conditions):
tional purposes only. It is not to be con- - dead system 1 - live system 2
strued as creating or becoming part of - live system 1 - dead system 2
- dead system 1 - dead system 2
any Woodward Company contractual or
#2 Switch from Parameter set #A to #B by activating DI #6
warranty obligation unless expressly #3 Configurable to either speed or voltage
stated in a written sales contract. #4 Analog bias outputs for voltage and speed freely configurable for all levels (+/-1 V, +/-3 V,
0 to 5 V, 0.5 to 4.5 V, +/-10 V +/-5 V, 0 to 20 mA, +/-20 mA, and much more)
We appreciate your comments about the #5 Speed bias output configurable as 500 Hz PWM output with adjustable voltage level
content of our publications. Please send #6 All units with 400 V measuring inputs can also be used for 100 V system voltage
comments including the document num-
ber below to
stgt-doc@woodward.com

© Woodward

All Rights Reserved


For more information contact:

37622A - 2016/02/Stuttgart
Type MVAJ 05/10/20: Tripping and control relays

Protective relays are precise measuring devices, the contacts of which should not be expected to switch large electrical loads. In some
cases, the protective relay may trip a circuit breaker directly, or according to the coil rating and the number of circuits to be energised,
may do so using a MVAJ tripping relay. The MVAJ relay interfaces the protection relay with the circuit breaker to provide the higher
contact capacity, additional contacts for tripping multiple circuit breakers, control functions, signalling and interlocking.

The MVAJ range comprises highly reliable hinged armature relays designed to directly operate circuit breaker trip coils. Built to very
high specifications, the MVAJ range provides a highly flexible and reliable link between the protective relays and the circuit breakers.

Features Models Available Application


• Directly operates circuit breaker • Trip relays Self reset relays reset when the initiating
trip coils signal is removed, making them suitable for
Trip relays possess a standard
use as trip relays in auto-reclose schemes
• High reliability hand reset flag and operate
and also for general flagging purposes.
within 10ms. Table 1 shows the
• High speed operation Hand reset relays require manual resetting
trip relay versions available.
making them effective lockout relays, which
• Negligible contact bounce
• Control relays are commonly used to trip circuit breakers
• 10 contacts in Midos size 2 case associated with transformers. Electrical reset
Control relay variants of each trip
• Supplied as high burden relays require a voltage to be applied to the
relay are available. These relays
unit to reset the contacts. These relays may
possess a following flag and
• Low burden selectable by be used in auto-reclose schemes, or where
operate in approximately 15ms.
removing an external link remote resetting of the relay is required.
• All relays configured for high
• Hand, electrical, hand or
burden applications are suitable
electrical and self reset versions
for dc operation only.
• Reset inhibition feature

• Immunity to wiring capacitance


discharge

• Delayed cut-off available in high


burden applications

• AC or DC operation for low


Figure 1
burden configuration
MVAJ 05 Relay
• 2.5 second time delay
MVAJ 05/10/20

489
Trip relay Where required, multiple operate lines Low burden application
may be used to drive a single MVAJ trip
With the exception of MVAJ 102 and relay. In these cases MCAA relays may be These relays are suitable for general
MVAJ 202 time delayed self reset relays, connected in series with each of the applications where the initiating contact is
all trip relays are suitable for either low operate lines to indicate which line caused located close to the relay. When
burden or high burden applications. the trip condition. configured for low burden applications, by
removing the external link from terminals
Type MVAJ 102 and 202 relays have 22 and 24, the burden is either cut off
High burden application been specifically designed for applications during operation or is economised to a
requiring a tripping relay which is self- low figure instantaneously.
These relays, supplied as high burden, are
resetting after a nominal delay of 2.5
suitable for use in high security circuit
seconds.
breaker tripping circuits. The high burden Control relay
provides greater immunity to capacitance This relay may be used, for example, for
discharge currents, which can result at the inter-tripping between higher voltage and Control relay variants of the standard trip
inception of an earth fault on battery wiring. lower voltage circuit breakers of a large relay are suitable for applications where
This makes the relays particularly suitable for three phase power transformer. This may the operating time of the unit is not critical
use in distributed tripping or control relay become necessary when the higher voltage but where the condition of the armature
contact logic schemes, where the initiating circuit breaker is tripped after a heavy should be clear from the position of the
contact may be remote from the relay. internal fault, by protection which cannot following flag.
conveniently provide an auxiliary contact
• MVAJ 05
with a dwell time long enough to ensure
Configuration
When configured for high burden correct tripping of the lower voltage circuit
applications the burden is either cut off at breaker. All trip relays are supplied as high
operation or is economised to a low figure burden. With the exception of MVAJ 102
Typically, the relay is initiated by
instantaneously. and 202, they may be converted to low
transformer protection, such as overall
• MVAJ 10, MVAJ 20 differential, restricted earth fault and burden by removing the link between case
Buchholz relays, in arrangements where terminals 22 and 24.
When configured for high burden
both the HV and LV circuit breakers are to A second link connected between case
applications the burden is either cut off or
be tripped simultaneously. terminals 21 and 23 enables a reset
is economised to a low figure after a 40 -
60ms time delay. The HV breaker may be expected to trip inhibitor feature to be introduced into the
more quickly than the LV breaker so the circuit of 10 and 20 contact electrical reset
Due to the greater minimum operating
tripping signal is maintained by the relays ensuring that the reset circuit is
current, the high burden also permits the
delayed reset. This ensures complete disabled when the operate circuit is
use of supervision relays such as type
clearance by the LV circuit breaker, even energised.
MVAX 11, where the wiring is at risk. The
though the fault may have been cleared On relay types 104, 105, 204 and 205
40 - 60ms time delay ensures reliable
largely by the HV breaker and the this link may be removed if this feature is
operation of series elements such as type
protection has started to reset. not required.
MCAA repeat relays.
This link must remain fitted to MVAJ 101
and 201 relays to enable the economising
circuit.

Tables 2 and 3 describe the user selectable


features which are available by external
linkconnection.
MVAJ 05/10/20

Reset mechanism 5 contacts 10 contacts 20 contacts

Self reset MVAJ 051 MVAJ 101 MVAJ 201

Self reset (2.5s delayed reset) - MVAJ 102 MVAJ 202

Hand reset MVAJ 053 MVAJ 103 MVAJ 203


Table 1
Electrical reset MVAJ 054 MVAJ 104 MVAJ 204
Trip relay model variants
Hand and electrical reset MVAJ 055 MVAJ 105 MVAJ 205

490
Description For type MVAJ 104, 105, 204 and 205 Self reset relays types MVAJ
relays configured for high burden 051, 101, 201
operation, as supplied, the burden is
General Self reset relays operate in the same
reduced to approximately 100W for 40-
manner as the hand and electrical
60ms before being cut off to either zero
The relays are built around a simple models but have a residual gap in the
or an economised level.
magnetic latch system which holds the magnetic path to ensure that they reset.
attracted armature unit in the operated For a hand/electrically reset relay, once
For a self-reset relay, when the attracted
state. Versions have either one or two the main attracted armature unit is
armature unit RL1 is energised by the
elements depending upon the number of latched in the operated state internal
protection contact PR, contact RL1-A
output contacts required. The contacts contact RL1-B closes, thus enabling the
opens, switching in resistance in series
themselves have been designed reset circuit. The relay may then be reset
with RL1 and reducing the burden to a
specifically to minimise the amount of by energising the reset coil by means of
level sufficient to hold RL1 in the
contact bounce experienced on the relay. closing the reset contact. If the reset
operated condition. On the opening of
contact is closed while the protective
PR this economised burden is removed
contact PR is also closed, the relay will
Hand reset relays types MVAJ and RL1 resets.
oscillate between operated and reset
053, 103, 203 states. For all relays in the low burden
configuration and for the MVAJ 051 relay
These relays incorporate an internal If required, the reset inhibitor may be
in high burden configuration the burden
break contact RL1-A in series with the activated by linking case terminals 21
is economised instantaneously. For type
operate coil of attracted armature unit and 23. This circuit ensures that while PR
MVAJ 101 and 201 relays configured for
RL1. This contact breaks the coil circuit is closed contact RL2-1 is open, stopping
high burden operation the burden is
and reduces the burden to zero for all the reset circuit from being
reduced to approximately 100W for 40-
relays in the low burden configuration simultaneously energised and thus
60ms before being cut off to an
and for the MVAJ 053 relay in high protecting the circuit.
economised level. The external link
burden configuration. between case terminals 21 and 23 must
For type MVAJ 103 and 203 relays remain fitted on these relays.
configured for high burden operation, as
supplied, the burden is reduced to
approximately 100W for 40-60ms before
being cut off to zero. When the break Relay type Feature Link in Link out
contact cuts-off RL1, the high burden is MVAJ 051, 053, 054, 055 Burden High Low
held through R5 until the time delay
circuit switches it out. This time delay t Cut-off Instantaneous Instantaneous
allows any flagging or auxiliary element MVAJ 101, 103, 104, 105 Burden High Low
in series with the tripping relay to operate
before full cut-off. 201, 203, 204, 205 Cut-off 40-60ms time delayed Instantaneous

The relay is reset by means of a push- MVAJ 102, 202 Link not necessary – as configured as high
button located on the front cover. For burden models
type MVAJ 20 relays each element is
reset separately. Note: At the point at which the relay cut-off occurs the current drawn by the relay is either reduced
to an economised level or is removed entirely (ie. zero watt cut-off state for MVAJ 05 or 2mA
for MVAJ 10 and MVAJ 20).
Electrical, hand/electrical reset
relays types MVAJ 054, 055, Table 2 Configuration of high/low burden link (terminals 22 to 24)
104, 105, 204, 205
Relay type Feature Link in Link out
These relays operate similarly to the
hand reset relays. The internal break MVAJ 051, 053, 054, Link not available
MVAJ 05/10/20

contact in series with the operate coil


breaks the coil circuit and reduces the 055, 102, 202
burden to zero for all relays in the low MVAJ 101, 201 Link fitted (relay cut-off to economised state)
burden configuration and for the MVAJ
054 and 055 relays in high burden MVAJ 103, 203 Link not available (relay cut-off to zero watts)
configuration. MVAJ 104, 105, 204, 205 Cut-off state economised zero watts

reset inhibitor active disabled

Table 3 Configuration of economising/reset inhibit link (terminals 21 to 23)

491
2.5 second time delayed Technical Data
self reset relays
types MVAJ 102, 202 Ratings
The MVAJ 102 and 202 relays can • Auxiliary voltage (Vx) Rated voltage Operative range
accept either a fleeting initiation or (Vx) (V)
persistent initiation. With the latter, the 24/27 14.4 - 32.4
relay will provide a tripping signal of 30/34 18.0 - 40.8
corresponding duration plus the 2.5s 48/54 28.8 - 64.8
time delay. This relay uses the same 110/125 66 - 150
basic principal of operation as that 220/250 132 - 300
described for the standard self reset • Minimum operate voltage 35% of lower rated voltage
relay. The burden is reduced to an
economised level 40-60ms after
Burdens
operation.
Burden at higher rated voltage Minimum operating current
For a time delayed self reset relay, the (W) (mA)
connection to terminal 25 is used to hold To operate*Operated To reset up to 125V* 220/250V*
the relay in the energised state until a MVAJ 05 80/150 ≤5 <40 >25/50 >10/20
timer on the circuit board times out. The MVAJ 10 50/150 ≤4 <40 >25/50 >10/20
timer begins the timing sequence when MVAJ 20 50/150 ≤4 <80 >25/50 >10/20
the PR contact opens.
* low/high burden configuration

Flagging Operate time


Operate time Operate time
Standard flag (Standard flag) (Following flag)
MVAJ 05 <8ms 15ms
All MVAJ trip relays are fitted with a MVAJ 10 <8ms 15ms
standard hand reset flag which drops MVAJ 20 <10ms 15ms
upon the operation of the relay. When
the relay is reset the flag stays in the The relay operate time will not increase by more than 1ms due to contact bounce.
operated state indicating that a fault has
occurred. The flag(s) may be reset by Reset time
means of a lever on the cover.
• Self reset relays <20ms
• 2.5s delayed self reset c. 2.5s
Following flag • Electrical reset <15ms
Following flags are generally fitted to
relays required for control functions. Operation indicator
Upon the operation or reset of the relay All relays are available with either a hand reset flag or a following flag.
the flag follows the armature to indicate
the current condition of the relay.
Contacts
Where the following flag is fitted, the
See Table 4 for contact combinations available
operation of the relay is increased to
approximately 15ms which is generally
unsuitable for trip relay applications. Contact ratings
Make and carry for 3 seconds ac 7500VA
with maxima of 30A and 300V
dc 7500W with maxima of 30A and 300V
MVAJ 05/10/20

Make and carry continuously ac 1250VA with maxima of 5A and 300V


Break dc 1250W with maxima of 5A and 300V
ac 1250VA with maxima of 5A and 300V
dc 80W resistive
40W inductive (L/R=0.04s) with
maxima of 5A and 300V

Durability
Loaded contact 10,000 operations minimum
Unloaded contact 100,000 operations minimum

492
Figure 2 Type MVAJ 103 hand reset relay circuit

MVAJ 05/10/20

Figure 3 Type MVAJ 105 hand/electrical reset relay circuit

493
Figure 4 Type MVAJ 051 self reset circuit
MVAJ 05/10/20

Figure 5 Type MVAJ 202 self reset (2.5s delayed reset) circuit

494
Table 4 Contact combinations available Electrical Environment
• AC ripple on dc supply
Make Break MVAJ 051 MVAJ 101 MVAJ 103 MVAJ 201 MVAJ 203 CC* IEC 60255-11:1979
MVAJ 053 MVAJ 102 MVAJ 104 MVAJ 202 MVAJ 204
MVAJ 054 MVAJ 105 MVAJ 205 The unit will withstand 12% ac
MVAJ 055 ripple on the dc supply.
5 0 • 00 • High frequency disturbance
4 1 • 01
IEC 60255-22-1:1988 Class III
3 2 • 02
2.5kV peak between independent
2 3 • 03
circuits and between independent
10 0 • • 00 circuits and case earth.
8 2 • • 02
6 4 • • 04 1.0kV peak across terminals of the
4 6 • • 06 same circuit except metallic
2 8 • 08 contacts.
20 0 • • 00 • Electrostatic discharge
18 2 • • 02
IEC 60255-22-2:1996 Class 3
16 4 • • 04
14 6 • • 06 8kV discharge in air with cover in
12 8 • • 08 place
10 10 • • 10 6kV contact discharge with cover
8 12 • • 12 removed.
6 14 • 14
• Fast transient disturbance
4 16 • 16
IEC 60255-22-4:1992 Class IV
* Contact combination required when ordering - use on page 8.
4kV, 2.5kHz applied directly to
auxiliary supply.
Capacitance discharge Specifications 4kV, 2.5kHz applied directly to all
withstand inputs.
ESI 48-4 EB1:1983 - Low burden
• High burden configuration • Surge immunity
ESI 48-4 EB2:1983 - High burden
For relays with rated voltage up to IEC 61000-4-5:1995 Level 3
and including the 125V, the relays High Voltage Withstand 2kV peak, 1.2/50μs between all
will withstand, without operating, a groups and case earth.
discharge into their operate circuits of • Dielectric withstand
a 10μF capacitor charged to 120% 1kV peak, 1.2/50μs between
IEC 60255-5:1977
of the higher rated voltage for the terminals of each group.
2kV rms for 1 minute between all
relay. terminals and case earth. • IEEE Radiated immunity
For relays with rated voltage of 2kV rms for 1 minute between ANSI/IEEE C37.90.2:1995
220/250V, the relays will withstand, terminals of independent circuits with
25 - 1000MHz
without operating a discharge into terminals on each independent circuit
zero and 100% square wave
their operate circuits of a 10μF connected together.
modulated
capacitor charged to 110% of the ANSI/IEEE C37.90: 1989 Field strength 35V/m
higher rated voltage for the relay, ie.
1.5kV rms for 1 minute across • IEEE Surge withstand capability (SWC)
275V.
normally open contacts.
• Low burden configuration ANSI/IEEE C37.90.1:1989
• High voltage impulse
MVAJ 05/10/20

When operating in low burden IEC 60255-5:1977 4kV fast transient and 2.5kV
configuration, the relays will oscillatory applied directly to each
Three positive and three negative
withstand, without operating, a input and earth
impulses of 5kV peak,1.2/50μs. 0.5J
discharge into their operate circuit of
between all terminals of the 4kV fast transient and 2.5kV
a 1μF capacitor charged to 120% of
same circuit (except output oscillatory applied directly across
the higher rated voltage for the relay.
contacts), between independent each output contact, opto input and
circuits, and between all terminals power supply circuit
connected together and case earth.

495
• EMC compliance Cases Additional information
89/336/EEC
MVAJ 05 and MVAJ 10 relays are Service Manual R8141
Compliance to the European
housed in size 2 Midos cases as shown Product Guide PG6141
Commission Directive on EMC is
in Figure 2.
claimed via the Technical Construction
File route. MVAJ 20 relays are housed in size 4
EN50081-2:1994 Midos cases as shown in Figure 3.
EN50082-2:1995
Generic Standards were used to
establish conformity. 13
4 holes 4.4ø 24
• Product Safety 45

72/23/EEC Compliance with the


European Commission low voltage
168 159
directive
EN 61010-1:1993/A2:1995
EN 60950:1992/A11:1997
Push button 48
Compliance is demonstrated by projection 10 max
Panel cut-out:
reference to generic safety standards.
Flush mounting fixing details

Atmospheric Environment 32 212 25 min.

• Temperature
IEC 60255-6:1988
Storage and transit –25°C to +70°C 177 157 max.
Operating –25°C to +55°C
Reset
IEC 60068-2-1:1990/A2: 1994
Cold 51 Flush mounting
IEC 60068-2-2:1974/A2: 1994 All dimensions in mm
Dry heat
• Humidity Figure 6 Case outline size 2
IEC 60068-2-3:1969
56 days at 93% RH and +40oC. 52
• Enclosure protection 97 4 holes Ø 4.4
23.5
IEC 60529:1989
IP50 (dust protected)
All dimensions in mm.
168 159
Mechanical Environment
• Vibration
IEC 60255-21-1:1988
Push button
99
Response Class 2 projection 10 max.
Endurance Class 2 Panel cut-out:
Flush mounting fixing details.
• Shock and bump
IEC 60255-21-2:1988 Shock 32 212
25 min.
response Class 2
MVAJ 05/10/20

Shock withstand Class 1


Bump Class 1
• Seismic
177 157 max.
IEC 60255-21-3:1993
Class 2

103 11
Flush mounting.

Figure 7 Case outline size 4

496
Information required with order

Relay Type: MVAJ

Number of contacts:
5 contact 05
10 contact 10
20 contact 20

Contact mechanism:
Self reset 1
2.5s delayed self reset
(not available with 5 contacts) 2
Hand reset 3
Electrical reset 4
Hand/electrical reset 5

Case size:
5/10 contacts - size 2 case B
20 contacts - size 4 case D

Flag:
Standard hand reset flag (trip relay) A
Following (self reset) flag (control relay) B

Voltage rating:
24/27 V 0 0
30/34 V 0 2
48/54 V 0 5
110/125 V 0 8
220/250 V 1 0

Output contact configuration


Reference should be made to Table 4, page 6 CC
MVAJ 05/10/20

Design Suffix

Please leave case size and design suffix blank as these will be completed by AREVA T&D

497
Introduction

BSS-3 series of GPS synchronization clock provides precise time display and signal output
based on the Global Positioning System( GPS ). GPS is a satellite-based navigation system
that uses a constellation of 24 satellites orbiting the earth and control stations on the ground
developed by USA. At any place and any time on the earth surface, when a receiver have
received enough GPS satellite signal, it can determine current position and accurate time after
calculation.

BSS-3 series of GPS synchronization clock uses Motorala GPS receiver which have 12
parallel receiving channels and an antenna with power supply. The receiver can achieve time
accuracy of nanoseconds level when it have detected 4 satellites and received it’s signals.

BSS-3 series of GPS synchronization clock is specialized for power system use, it is designed
and manufactured to fit the demand of various detecting, control, and fault recording devices,
it is a suitable solution for time synchronization systems require of excellent performances
and high stability.

Features

… The equipment cabinet is made of alloy aluminum material, it’s electromagnetic


compatibility can withstand strong disturbances, it’s a standard 2U-19 inch rack, it’s function
modules are set in from backward, it’s structure is compact and can be expanded flexibly and
maintained conveniently.

… Time accuracy higher than 1 millisecond.

… Various output signals: pulse, serial port, IRIG-B code, DCF77 code, all photoelectrical
separated from each other.

… Rich output channels, can be combined flexibly as user’s demand.

… High performance, high-power and wide-scale power supply, it works stably.

… Alarm(relay contact output): power failure, device fault

… 14 digits LED display on front panel, displaying year, month, date, hour, minute, second; and
LEDs indicate working state.

-1-
Construction

The device is a unit of 2U-19 inch rack made of alloy aluminum, equipped of a main board
bus inside and a antenna outside. It’s modules include 1 power supply module, 1 receiver
module and 6 output modules, are set in from backward.
The device’s LED display on front panel, shows year, month, date, hour, minute and second.
LED indicator shows device state, ‘Sync’ LED shows that it has detected more than 4
satellites, has got GPS time, a usual speaking of ‘position fixed’, ‘PPS’ LED indicates that
GPS receiver works, ‘OUTPUT’ LED indicates that output signals have been sent.

Front panel and rear panel described as figure

Figure-1: front panel

Figure-2: rear panel

1. Power supply module

This high performance, high-power power supply module services for the other modules’
normal work, the input voltage is 100V~260V can be either AC or DC, the power rating is 50
watts, there are 3 sets of power supply: 5V/5A, +12V/1A and –12V/1A. The module has
supplied components such as power filters to withstand disturbance and 1 ‘device fault’
relay(T1, T2), 1 ‘alarm’ relay(C1, C2) contact, capacity of each contact is: 220AC 1A.

Figure-3: power supply module

-2-
2. Receiver module

This module is equipped with GPS receiver and additional circuits for receive GPS signals
through antenna. Having detected signals from 4 satellites and calculated, it provides accurate
time.

Figure-4: receiver module

3. Antenna

There are three optional length of antennas for uses to choose, 30 meters, 50 meters and 100
meters. If even the 100 meters antenna can’t fit use, a transfer clock BSS-3Y for long
distance use can be served.
… Optional antenna A03: default option, 30 meters long with power supply, connector type
is BNC (diameter 15mm), diameter of cable is 5mm.
… Optional antenna A05: 50 meters long with power supply, diameter of BNC connector is
15mm, diameter of cable is 7mm.
… Optional antenna A10: 100 meters long with power supply, diameter of BNC connector
is 20mm, diameter of cable is 10.5mm.

4. Output modules

4.1 Pulse Output Unit


There are 12 channels of pulse output on this unit, either 1PPS or 1PPM as user’s choice.
Change the selection as this way: unscrew it’s bolt and pull out the unit, you will see 12
selection pins on the board, it’s serial number is the same as it’s corresponding output contact,
you can set the jumpers as the board indicate according to your selection( they are set as use’s
contract, or on PPM by default ).
There are 2 types of Pulse output unit: P01 and P02. P01 is open circuit output unit, pulse
width is 200mS, 300V/DC, 100mA. P02 is close circuit output unit, pulse width is 200mS,
80V/DC, 25mA. P01 and P02 figures the same. Figure-5 shows that.

-3-
Figure-5: Module P01 and P02

4.2 Serial Port Output Unit

Serial port connector is of DB9(pin) type, Figure-6 shows that.

Figure-6: Module S01

Serial format : baud rate 9600, 8 bits data , 1 bit stop, even parity.
Code output format in Protocol A˄BSS˅: at 0 point per minute, send 9 bytes hex data. The
first three codes are: 00, FF, 81, next 6 bytes are: year, month, date, hour, minute, second.
00 FF 81 year month date hour minute second

Code output format in Protocol B˄GCB˅: at 0 point per minute, send 20 bytes ASCII data.
SOH 10Year Year : 10Month Month : 10Date Date :

10Hour Hour : 10Minute Minute : 10Second Second CR LF

Serial port connector is of DB9(pin) type, 2 type of signals can be send at the same time:
Pin1(-)|Pin2(+) for RS422(RS485), Pin3(TXD)|Pin5(COM) for RS232. They are seldom used
at the same time, because they are not photoelectrical separated. All serial output ports are
separated from each other. RS422(RS485) can transfer data as long as 500 meters(too long
will delay the synchronization), and RS232 30 meters.

-4-
Installation

1. Installation and connection

shows as figure-7:

Figure-7: description of equipment’s installation and connection

2. Equipment dimension

shows as figure-8, depth is 260mm.

Figure-8: Equipment dimension

3. Installation of antenna
To observe 4 satellites at the same time and get it’s signals, The antenna should be installed at
places with broadly sky, it is best to fix it at the top of the building. You can fix the antenna to
the supporter we present with the equipment, and fix it at the top of the building with bolts.
When you install the antenna, you shouldn’t wheel sharp turn to the cable, the cable’s length
is designed according to strictly calculated amplitude and shouldn’t be cut or extended, in
case the receiver will not work.

4. Power on
When power connector, antenna and synchronization cables are all connected correctly, you
can switch on the power, 14 ‘8’ will be display on front panel, you can check if there are any

-5-
breaks on it. A moment later, date and time will be displayed, and show time run, ‘PPS’
indicator will blink, the time information may not be correct for receiver won’t fix
immediately, when absent to GPS signals, pulse and serial port output will not work, but
IRIG-B codes will send because the fix status is included in it. After a few minutes ‘Sync’
indicator flow and the clock will send out synchronization signals. When pulse and serial port
signals are send at 0 point every minute, ‘Output’ indicator will highlight once.

5. Connection of pulse synchronization


This signal output use open circuit, user should add DC supply to it, and pay attention to
polarity, it won’t work if polarity is wrong.

The principle of pulse synchronization interface is shown at figure-9.

Figure-9: The principle of pulse synchronization interface

If TTL is needed, Reference connection is shown as figure-10

User device

Figure-10: TTL pulse synchronization interface

There are 12 channels of pulse output on this unit, either 1PPS or 1PPM as user’s choice.
Change the selection as this way: unscrew it’s bolt and pull out the unit, you will see 12
selection pins on the board, it’s serial number is the same as it’s corresponding output contact,
you can set the jumpers as the board indicate according to your selection.
For open circuit output unit, it’s pulse width is 200mS, 300V/DC, 100mA.
For close circuit output unit, it’s pulse width is 200mS, 80V/DC, 25mA.

Close circuit output connection shown as figure-11.

Figure-11: Close circuit output connection

-6-
6. Connection of serial port synchronization
There are 4 serial port connectors on each S01 module( serial port synchronization output
module ). Each serial port connector is of DB9(pin) type, 2 type of signals can be send at the
same time: Pin1(-)|Pin2(+) for RS422(RS485), Pin3(TXD)|Pin5(COM) for RS232. They are
seldom used at the same time, because they are not photoelectrical separated.
Connection of serial port synchronization is shown as figure-12, figure-13.

Figure-12: RS232 output connection

Figure-13: RS422 output connection

The format is set as user’s contract. It seldom be changed out of the factory.

-7-
Specifications

Dimension Width: standard 19 inch, height: 2U or 4U


Mount dimension: 440 width h 89 height h 260 depth (2U)
440 width h 178 height h 260 depth (4U)
Power Supply Option: 100V~260V /DC or AC
Rated power: 50 watts
Consumption: < 10 watts at 220V DC, < 15 watts at 220V AC
Front Panel 14 digits LED display
Transfer Distance Pulse: 30 meters, ordinary 2-line cable
& Cable Serial: RS232 30m, RS485 500m, 2-line screen cable
Accuracy Pulse: 1­S
Output Channels Pulse: 12 channels per module
Serial port: 4 channels of RS485 and 4 channels of RS232 for every
module
Modules Option Dimension of functional modules are same, every position can set in
any module, set in modules of same type will not concern with the
performance.
Environment Temperature: -5e& ~ +40eC
Relative humidity: 10% ~ 90%
Air pressure: 85 ~ 110 KPa
Insulation Power circuit: 1500V/AC 50Hz 1 minute
Other circuits: 500V/AC 50Hz 1 minute

-8-
Dell Precision Tower
5000 Series (5810)
Big power in a compact, innovative
design

Experience the evolution of productivity Best-in-class chassis design


Power resource-exhausting, graphics- • Straightforward, clutter-free interior
intensive workloads with ease, featuring: provides superb air flow, easy access to
• Dell Precision Optimizer v 3.0, enhances components for serviceability and
application performance by optimizing modifications, and improved acoustics
settings, for up to 121 percent
• The only mainstream tower workstation
application performance improvement
family to offer an externally accessible
• Intel® Xeon® processor E5-1600 v3 tool-less (lockable) power supply for
product family, including select high- superior serviceability
end E5-2600 v3 CPUs, provides the
• Integrated front and rear aluminum
performance and flexibility you need to
handles for easy deployment and moves
complete complex tasks quickly
• Room for up to (3) 3.5” or (4) 2.5” tool-
• Manage large data sets with ease, with
less hard drives
up to 256GB4 of quad-channel DDR4
ECC RDIMM memory • Easy rack mounting via 0U rail shelf kit10
• Choose from a broad selection of Exceptional Service & Support
professional grade AMD FirePro™ or
• Rest assured that your Dell Precision
NVIDIA® Quadro® graphics
workstation will be well protected
• Optional Intel PCIe SSD drives and m.2 should an issue arise, with a standard 3
PCIe SSDs on the actively cooled year limited hardware warranty7
Precision Zoom card deliver superb The Precision Experience
read/write throughput, combined with
exceptional reliability. Dell makes it easy to choose, buy and own
all of the essential accessories you need to
• Intel CAS-W storage option enables enhance your workstation productivity.
performance that is near solid state drive
speeds at a significantly reduced cost • Enjoy outstanding color accuracy,
versus a full SSD storage solution6 consistency and richness with state-of-
the-art Dell UltraSharp monitors with
Reduce environmental impact Premier Color (optional color calibrator)
• Dell Precision Tower 5000 Series is
EPEAT®-registered3 and offers ENERGY
STAR® configurations, including 80
PLUS®-registered Gold power supplies
Feature Precision Tower 5000 Series (5810) Technical Specification
Intel® Xeon® processor E5-1600 v3 Series plus select Intel Xeon E5-2600 v3 with up to 14 cores and Intel Advanced Vector Extensions, Intel
Processor Options
Trusted Execution Technology, Intel AES New instructions, Optimized Intel Turbo Boost and optional Intel vPro™ technology

Windows® 10 Professional (64 bit) Red Hat® Enterprise Linux® 7.0 –(6.5 supported)
Operating
Windows® 8.1 Professional (64-Bit) Ubuntu 12.04
System Options Windows® 7 Professional (64-Bit) NeoKylin 6.0 (China only)

Chipset Intel® C610

Quad channel memory up to 256GB 2133MHz DDR4 RDIMM ECC memory, 8 DIMM Slots. Note: memory speed is dependent on specific
Memory Options
Intel Xeon E5-1600 v3 or E5-2600 v3 Series processor installed

Graphics4 Options Support for 2 PCI Express® x16 Gen 2/Gen 3 graphics cards up to 450W (total graphics in 2 slots, (with 825W PSU)

High end 3D cards: Mid-range 3D cards: Entry 3D cards: Professional 2D cards:


AMD FirePro W8100 AMD FirePro W7100 AMD FirePro W4100 NVIDIA NVS 510
NVIDIA Quadro M6000 AMD FirePro W5100 AMD FirePro W2100 NVIDIA NVS 315
NVIDIA Quadro M5000 NVIDIA Quadro M4000 NVIDIA Quadro K620 NVIDIA NVS 310
NVIDIA Quadro K5200 NVIDIA Quadro K4200 NVIDIA Quadro K420
NVIDIA Quadro M4000 NVIDIA Quadro K2200

Storage Options Support for up to (4) M.2 PCIe SSDs and up to (3) 3.5” SATA or (4) 2.5” SATA/SAS Optional controller required for SAS.

M.2 PCIe SSD (NVMe) 2.5” SATA SSD 2.5” SATA 7200 3.5” SATA 2.5” SAS 10K RPM 2.5” Self Encrypting
Up to (4) 1TB drives on Up to (4) 1TB RPM Up to (3) 4TB 12Gb/s Drives
Up to (4) 512GB Up to (4) 1.8TB
Precision Zoom 4 PCIe drives 5400 RPM 512GB 2.5” FIPS SED
7200 RPM
SSD card. 2.5” SAS 15K RPM (OPAL 2.0) SSD
PCIe SSD HH/HL card Up 12Gb/s
to (2) Intel 1.2TB PCIe SSD Up to (4) 600GB
NVMe drives

Integrated: Intel AHCI 6Gb/s SATA controller with six ports, two reserved for optical drives, Intel RSTe supports host based software RAID
0,1,5,10
Storage Controller Optional: LSI MegaRAID® SAS 9341-8i 12Gb/s SAS (6Gb/s SATA) PCIe controller supports software RAID 0,1,5,10.
LSI MegaRAID® SAS 9341-8i 12Gb/s SAS (6Gb/s SATA) ) PCIe controller (1GB cache with Flash module/Super Cap backup) supports
hardware RAID 0,1,5,10

Integrated: Intel Ethernet Connection I219-LM 10/100/1000


Communications
Optional: Intel 10/100/1000 PCIe Gigabit network card, Intel X540-T2 10GbE dual port PCIe network card,

Audio Controller Integrated Realtek ALC3861 High Definition Audio Codec (2 Channel)

Speakers Internal Speaker; Optional Dell 2.0 stereo speaker systems available and Dell sound bar for select flat-panel displays

Optional; Precision Zoom 2 (HH/HL) and Zoom 4 (FH/FL) PCIe SSD cards with Optional dual & quad display Teradici PCoIP remote
active cooling. Support up to 2 and 4 m.2 drives respectively workstation host PCIe cards
Add-in cards
Optional 1394 a/b PCIe Card (3 Ports – 2x 1394b + 1x 1394a) Optional Thunderbolt 2 PCIe Card
Optional Serial Port PCIe Card

Front Internal Rear


2 – USB 2.0 1 – USB 2.0 2 – USB 2.0 1 1 – RJ45 Network Connector
2 – USB 3.0 1 2x5 USB 2.0 header. (Requires optional 4 – USB 3.0 1 – Serial
I/O Ports 1 – Microphone splitter cable to support 2 x USB 2.0 Type A 2 – PS2 1 – Audio Line in/Microphone
1 – Headphone ports) 2 – DisplayPort 1 – Audio Line out
4 – SATA 6Gb/s 1 – HDMI

HxWxD: 16.30 x 6.79 x 18.54"; 414 x 172.6 x 471mm


Bays: (1) external slimline optical bay; (2) internal 3.5” bays (support (2) 3.5” or 2.5” drives); (1) external 5.25” bay
Chassis
Slots: (2) PCIe x16 Gen 3; (1) PCIe x16 Gen 3 (wired x8) half length; (1) PCIe x4 Gen 2; (1) PCIe x1 Gen 2; (1) PCI 32
Power Supply: 825W, 685W, 425W 90% efficient (80PLUS Gold Certified) Externally accessible/removable

Storage devices Slimline options: DVD-ROM; DVD+/-RW, Optional 5.25" bay devices: BD, DVD+/-RW; 19-in-1 media reader, 2 x 2.5” HDD/SSD kit

Dell UltraSharp Monitors – Award-winning high-performance monitors with PremierColor (on select models) and ultra-wide viewing, from
Monitors
21.5”- 34” Dell Monitors (P models) available from 19” – 28”.

Trusted Platform Module (TPM 1.2); Chassis Intrusion switch; Setup/BIOS Password; I/O Interface Security; Kensington® lock slot, Padlock
Security Options ring, lockable power supply; Dell Data Protection (DDP): DDP | Security Tools for authentication; DDP | Protected Workspace for malware;
DDP | Encryption for data protection

Energy Star® configurations available including 80 PLUS® registered Gold power supplies; EPEAT® registered (see epeat.net for specific
Regulatory &
registration rating/status by country); China CECP; GS Mark. For a complete listing of declarations & certifications, see Dell’s regulatory &
Environmental compliance homepage at dell.com/regulatory_compliance

3-Year Limited Hardware Warranty and 3-year NBD On-Site Service after Remote Diagnosis
Warranty & Support
Optional: Dell ProSupport is designed to rapidly respond to your business’s needs, help protect your investment and sensitive data, and
Services
provide enhanced proactive support services to help reduce risk and complexity within your IT environment

TAA
Configurations Yes, available

1.  ISV certification applies to select configurations; 2.  A 64-bit operating system is required to support 4GB or more of system memory; 3.  See epeat.net for specific registration rating/status by
country; 4.  GB means 1 billion bytes and TB equals 1 trillion bytes; significant system memory may be used to support graphics, depending on system memory size and other factors;, 5.  GB means 1
billion bytes and TB equals 1 trillion bytes; actual capacity varies with preloaded material and operating environment and will be less; 6.  Available in select regions; 7.  For copy of Ltd Hardware
Warranty, write Dell USA LP, Attn: Warranties, One Dell Way, Round Rock, TX 78682 or see www.dell.com/warranty; 8.  Remote Diagnosis is determination by online/phone technician of cause of
issue; may involve customer access to inside of system and multiple or extended sessions. If issue is covered by Limited Hardware Warranty and not resolved remotely, technician and/or part will be
dispatched, usually within 1 business day following completion of Remote Diagnosis. Availability varies. Other conditions apply; 9.  Availability and terms of Dell Services vary by region. For more
information, visit www.dell.com/servicedescriptions.;, 10. Available in select countries via S & P. Dell PCs use Genuine Microsoft Windows. Intel, the Intel logo, Xeon & Xeon Inside are trademarks or
registered trademarks of Intel Corporation in the U.S. & other countries. Microsoft, Windows & Windows Vista are trademarks or registered trademarks of Microsoft Corporation in the U.S. and other
countries.
PowerEdge R630
8JUIDPNQVUJOHDBQBCJMJUZQSFWJPVTMZPOMZTFFOJO6TFSWFST UIFVMUSBEFOTF
1PXFS&EHF3UXPTPDLFU6SBDLTFSWFSEFMJWFSTBOJNQSFTTJWFTPMVUJPOGPS
WJSUVBMJ[BUJPOFOWJSPONFOUT MBSHFCVTJOFTTBQQMJDBUJPOTPSUSBOTBDUJPOBMEBUBCBTFT
The PowerEdge R630 server is versatile and highly *OOPWBUJWFNBOBHFNFOUXJUI
DPOţHVSBCMFGPSBWBSJFUZPGTPMVUJPOT EFMJWFSJOHUIF
latest Intel® Xeon®QSPDFTTPS&WQSPEVDU JOUFMMJHFOUBVUPNBUJPO
GBNJMZ %*..TPGIJHIQFSGPSNBODF%%3 5IF%FMM0QFO.BOBHFTZTUFNTNBOBHFNFOU
NFNPSZBOEBCSPBESBOHFPGMPDBMTUPSBHFPQUJPOT QPSUGPMJPJODMVEFTJOOPWBUJWFTPMVUJPOTUIBUTJNQMJGZ
BOEBVUPNBUFFTTFOUJBMTFSWFSMJGFDZDMFNBOBHFNFOU
%FMJWFSQFBLQFSGPSNBODF UBTLTŊNBLJOH*5PQFSBUJPOTNPSFFťDJFOUBOE
#VJMEBCMB[JOHMZGBTUUSBOTBDUJPOBMEBUBCBTFXJUI %FMMTFSWFSTUIFNPTUQSPEVDUJWF SFMJBCMFBOEDPTU
UIF3BMMŤBTIESJWFDPOţHVSBUJPO$PNCJOF FŢFDUJWF-FWFSBHJOHUIFJODPNQBSBCMFBHFOUGSFF
UIFEFOTJUZ TDBMBCJMJUZBOEQFSGPSNBODFPGŐ DBQBCJMJUJFTPGUIF1PXFS&EHFFNCFEEFEJOUFHSBUFE
44%TXJUIEVBM1&3$DBQBCJMJUZUPEFMJWFSBTVQFSJPS %FMM3FNPUF"DDFTT$POUSPMMFS *%3"$
XJUI
TPMVUJPOUIBUDBOCPPTUQFSGPSNBODFCZTUPSJOHBO -JGFDZDMF$POUSPMMFSUFDIOPMPHZ TFSWFSEFQMPZNFOU 
FOUJSFEBUBCBTF8IFODPNCJOFEXJUIUIF4BO%JTL® DPOţHVSBUJPOBOEVQEBUFTBSFTUSFBNMJOFEBDSPTT
%"4$BDIFTPMVUJPO UIF3DBOIFMQJODSFBTF UIF0QFO.BOBHFQPSUGPMJPBOEUISPVHIJOUFHSBUJPO
0-51USBOTBDUJPOTBOEDPODVSSFOUVTBHFGPS XJUIUIJSEQBSUZNBOBHFNFOUTPMVUJPOT
MBUFODZTFOTJUJWFBQQMJDBUJPOT TVDIBTFDPNNFSDF .POJUPSJOHBOEDPOUSPMPG%FMMBOEUIJSEQBSUZ
PSţOBODJBMUSBEJOH EBUBDFOUFSIBSEXBSFJTQSPWJEFECZ0QFO.BOBHF
&TTFOUJBMTBOEXJUIBOZUJNF BOZXIFSFNPCJMF
%JTDPWFSHSFBUFSWFSTBUJMJUZ BDDFTT UISPVHI0QFO.BOBHF.PCJMF0QFO.BOBHF
&TTFOUJBMTOPXBMTPEFMJWFST4FSWFS$POţHVSBUJPO
8JUIVQUP%*..TPGNFNPSZ BOEDPOţHVSFE .BOBHFNFOUDBQBCJMJUJFTUIBUBVUPNBUFPOFNBOZ
XJUIVQUPŐESJWFT UIF3DBOQSPWJEF 1PXFS&EHFCBSFNFUBMTFSWFSBOE04EFQMPZNFOUT 
BEFOTF SFTPVSDFSJDINJETJ[FEWJSUVBMJ[BUJPO RVJDLBOEDPOTJTUFOUSFQMJDBUJPOPGDPOţHVSBUJPOT
FOWJSPONFOUUPESJWFCVTJOFTT*OUFMMJHFODFBQQMJDBUJPOT  BOEFOTVSFDPNQMJBODFUPBQSFEFţOFECBTFMJOF
GSPNDVTUPNFSSFMBUJPOTIJQNBOBHFNFOU $3.
UP XJUIBVUPNBUFEESJGUEFUFDUJPO
FOUFSQSJTFSFTPVSDFQMBOOJOH &31
XIJMFJUTBWFTPO
TQBDF FOFSHZBOEDBQJUBMDPTUT

:PVDBOBMTPJODSFBTFUIFTQFFEPGEBUBBDDFTTVTJOH PowerEdge R630


VQUPGPVS/7.F1$*F&YQSFTT'MBTIEFWJDFTXJUI
'MVJE$BDIFUFDIOPMPHZŊBOETIBSFUIBUDBDIJOH • Latest Intel Xeon E5-2600 v3
BEWBOUBHFBDSPTTPUIFSOFUXPSLFETFSWFST QSPDFTTPSTŋVQUPDPSFT
.BYJNJ[FPQFSBUJPOBMFťDJFODZ • 6QUP%*..TIJHIDBQBDJUZ
2VJDLMZBOETFDVSFMZNPOJUPSPSNPEJGZDSJUJDBM %%3NFNPSZ
TFSWFSTFUUJOHTŏBUUIFCPYŐXJUIUIF
J%3"$2VJDL4ZODCF[FMXJUIFNCFEEFEOFBSţFME • 6QUPŐ44%T 5#

DPNNVOJDBUJPO /'$
DBQBCJMJUZ6TFBIBOEIFME
EFWJDFXJUIUIFCF[FMUPRVJDLMZDIFDLTZTUFN • 6QUP1$*FFYQBOTJPO
IFBMUIEFUBJMT BOEVTFJ%3"$%JSFDUUPFBTJMZEFQMPZ
PSNPEJGZTFUUJOHTBDSPTTNVMUJQMFTFSWFSTXJUIB slots
64#LFZPSMBQUPQ FMJNJOBUJOHUIFQPUFOUJBMGPS
DPOţHVSBUJPOFSSPST • 6QUP&YQSFTT'MBTI/7.F
1$*F44%T
Feature 1PXFS&EHF3UFDIOJDBMTQFDJţDBUJPO
Form factor 6SBDL
Processor Intel® Xeon®QSPDFTTPS&WQSPEVDUGBNJMZ
Processor sockets 2

Dimensions YŐBOEYŐESJWFDPOţHVSBUJPO)DN JO


Y8DN JO
Y%DN JO

YŐESJWFDPOţHVSBUJPO)DN JO
8DN JO
%DN JO

Cache .#QFSDPSFDPSFPQUJPOT      


Chipset *OUFM$TFSJFTDIJQTFU
Memory1 6QUP(# %*..TMPUT
(#(#(#(#%%3VQUP.5T
I/O slots 6QUPY1$*FTMPUTQMVTEFEJDBUFE1&3$TMPU
Internal controllers1&3$4 483"*%
1&3$) 1&3$) 1&3$)1
RAID controllers External HBAs (RAID)1&3$)
External HBAs (non-RAID)(CQT4"4)#"
Internal hard drive bay and hot-plug backplane:
Drive bays 6QUPYŐ4"5"44%
6QUPYŐ)%%4"4 4"5" OFBSMJOF4"444%4"4 4"5" 6QUP/7.F1$*F
6QUPYŐ)%%4"4 4"5" OFBSMJOF4"444%4"4 4"5"
)%%4"4 4"5" OFBSMJOF4"444%4"4 4"5" /7.F1$*F
Maximum internal YŐ44%ŊVQUP5#WJB5#IPUQMVH4"5"44%
storage1 YŐŊVQUP5#WJB5#IPUQMVH4"4)%%
YŐŊVQUP5#WJB5#IPUQMVH4"4)%%
Embedded NIC Y(C Y(C Y(C Y(C
Power supplies 5JUBOJVNFťDJFODZ8"$QPXFSTVQQMZ8%$QPXFSTVQQMZ1MBUJOVNFťDJFODZ8 8 8
&$$NFNPSZ IPUQMVHIBSEESJWFT IPUQMVHSFEVOEBOUDPPMJOH IPUQMVHSFEVOEBOUQPXFS JOUFSOBMEVBM4%
Availability NPEVMF TJOHMFEFWJDFEBUBDPSSFDUJPO 4%%$
TQBSFSBOL TVQQPSUGPSIJHIBWBJMBCJMJUZDMVTUFSJOHBOEWJSUVBMJ[BUJPO 
QSPBDUJWFTZTUFNTNBOBHFNFOUBMFSUT
Systems management: *1.*DPNQMJBOU Dell OpenManage Integrations:
%FMM0QFO.BOBHF&TTFOUJBMT%FMM0QFO.BOBHF.PCJMF • %FMM0QFO.BOBHF*OUFHSBUJPO4VJUFGPS
%FMM0QFO.BOBHF1PXFS$FOUFS .JDSPTPGU®4ZTUFN$FOUFS
• %FMM0QFO.BOBHF*OUFHSBUJPOGPS7.XBSF®
Remote management J%3"$XJUI-JGFDZDMF$POUSPMMFS  W$FOUFSś
Systems management J%3"$&YQSFTT EFGBVMU
J%3"$&OUFSQSJTF VQHSBEF
Dell OpenManage Connections:
(#W'MBTINFEJB VQHSBEF
(#W'MBTINFEJB VQHSBEF
• )10QFSBUJPOT.BOBHFS *#.5JWPMJ® /FUDPPM®
J%3"$2VJDL4ZOD BOE$"/FUXPSLBOE4ZTUFNT.BOBHFNFOU
• %FMM0QFO.BOBHF1MVHJOGPS0SBDMF®%BUBCBTF
.BOBHFS

Rack support 3FBEZ3BJMTś**TMJEJOHSBJMTGPSUPPMMFTTNPVOUJOHJOQPTUSBDLTXJUITRVBSFPSVOUISFBEFESPVOEIPMFTPSUPPMFE


NPVOUJOHJOQPTUUISFBEFEIPMFSBDLT XJUITVQQPSUGPSPQUJPOBMUPPMMFTTDBCMFNBOBHFNFOUBSN
.JDSPTPGU8JOEPXT4FSWFS®3 Optional embedded hypervisors:
.JDSPTPGU8JOEPXT4FSWFS $JUSJY® XenServer®
.JDSPTPGU8JOEPXT4FSWFS3 7.XBSFW4QIFSF®&49Jś
Operating systems .JDSPTPGU8JOEPXT)1$4FSWFS 'PSNPSFJOGPSNBUJPOPOUIFTQFDJţDWFSTJPOTBOE
/PWFMM®464&®-JOVY&OUFSQSJTF4FSWFS BEEJUJPOT WJTJU%FMMDPN04TVQQPSU
3FE)BU®&OUFSQSJTF-JOVY®
7.XBSF&49®
OEM-ready version 'SPNCF[FMUP#*04UPQBDLBHJOH ZPVSTFSWFSTDBOMPPLBOEGFFMBTJGUIFZXFSFEFTJHOFEBOECVJMUCZZPV'PS
available NPSFJOGPSNBUJPO WJTJU%FMMDPN0&.
%FMM1SP4VQQPSU1MVTGPSDSJUJDBMTZTUFNTPS%FMM1SP4VQQPSUGPSQSFNJVNIBSEXBSFBOETPGUXBSFTVQQPSUGPSZPVS
Recommended 1PXFS&EHFTPMVUJPO$POTVMUJOHBOEEFQMPZNFOUPŢFSJOHTBSFBMTPBWBJMBCMF$POUBDUZPVS%FMMSFQSFTFOUBUJWF
support UPEBZGPSNPSFJOGPSNBUJPO"WBJMBCJMJUZBOEUFSNTPG%FMM4FSWJDFTWBSZCZSFHJPO'PSNPSFJOGPSNBUJPO WJTJU
%FMMDPN4FSWJDFT

(#FRVBMTCJMMJPOCZUFTBOE5#FRVBMTUSJMMJPOCZUFTBDUVBMDBQBDJUZWBSJFTXJUIQSFMPBEFENBUFSJBMBOEPQFSBUJOHFOWJSPONFOUBOEXJMMCFMFTT

&OEUPFOEUFDIOPMPHZTPMVUJPOT
3FEVDF*5DPNQMFYJUZ MPXFSDPTUTBOEFMJNJOBUFJOFťDJFODJFTCZNBLJOH*5BOECVTJOFTTTPMVUJPOTXPSLIBSEFSGPSZPV
:PVDBODPVOUPO%FMMGPSFOEUPFOETPMVUJPOTUPNBYJNJ[FZPVSQFSGPSNBODFBOEVQUJNF"QSPWFOMFBEFSJO4FSWFST 
4UPSBHFBOE/FUXPSLJOH %FMM&OUFSQSJTF4PMVUJPOTBOE4FSWJDFTEFMJWFSJOOPWBUJPOBUBOZTDBMF"OEJGZPVōSFMPPLJOHUP
QSFTFSWFDBTIPSJODSFBTFPQFSBUJPOBMFťDJFODZ %FMM'JOBODJBM4FSWJDFTśIBTBXJEFSBOHFPGPQUJPOTUPNBLFUFDIOPMPHZ
BDRVJTJUJPOFBTZBOEBŢPSEBCMF$POUBDUZPVS%FMM4BMFT3FQSFTFOUBUJWFGPSNPSFJOGPSNBUJPO

-FBSO.PSFBU %FMMDPN1PXFS&EHF
f%FMM*OD"MMSJHIUTSFTFSWFE%FMM UIF%&--MPHP UIF%&--CBEHF 1PXFS&EHF BOE0QFO.BOBHFBSFUSBEFNBSLTPG%FMM*OD0UIFSUSBEFNBSLTBOEUSBEF
OBNFTNBZCFVTFEJOUIJTEPDVNFOUUPSFGFSUPFJUIFSUIFFOUJUJFTDMBJNJOHUIFNBSLTBOEOBNFTPSUIFJSQSPEVDUT%FMMEJTDMBJNTQSPQSJFUBSZJOUFSFTUJOUIF
NBSLTBOEOBNFTPGPUIFST5IJTEPDVNFOUJTGPSJOGPSNBUJPOBMQVSQPTFTPOMZ%FMMSFTFSWFTUIFSJHIUUPNBLFDIBOHFTXJUIPVUGVSUIFSOPUJDFUPBOZQSPEVDUT
IFSFJO5IFDPOUFOUQSPWJEFEJTBTJTBOEXJUIPVUFYQSFTTPSJNQMJFEXBSSBOUJFTPGBOZLJOE -FBTJOHBOEţOBODJOHQSPWJEFEBOETFSWJDFECZ%FMM'JOBODJBM
4FSWJDFT--$PSJUTBťMJBUFPSEFTJHOFF ŏ%'4Ő
GPSRVBMJţFEDVTUPNFST0ŢFSTNBZOPUCFBWBJMBCMFPSNBZWBSZJODFSUBJODPVOUSJFT8IFSFBWBJMBCMF PŢFST
NBZCFDIBOHFEXJUIPVUOPUJDFBOEBSFTVCKFDUUPQSPEVDUBWBJMBCJMJUZ DSFEJUBQQSPWBM FYFDVUJPOPGEPDVNFOUBUJPOQSPWJEFECZBOEBDDFQUBCMFUP%'4 BOE
NBZCFTVCKFDUUPNJOJNVNUSBOTBDUJPOTJ[F0ŢFSTOPUBWBJMBCMFGPSQFSTPOBM GBNJMZPSIPVTFIPMEVTF%FMMBOEUIF%&--MPHPBSFUSBEFNBSLTPG%FMM*OD

.BZ]7FSTJPO
%FMM@1PXFS&EHF@3@4QFD4IFFU
Dell Precision Tower
3000 Series (3620)
Workstation performance and reliability in an
expandable mini tower

The Dell Precision Tower 3000 Series is a new NECC and ECC DDR4 2133Mhz
fully customizable, entry workstation memory, and optional Thunderbolt® 2 card
certified to run professional applications to provide you with the performance to
ideal for people who need the performance make the most of your time. A new
and reliability, but felt a workstation was addition to the entry workstation is
out of their budget. Optional PCIe SSD Storage that can be
configured via a PCIe M.2 Slot on the
Every Dell Precision is designed around
motherboard, as well on an actively cooled
innovation, performance and reliability. We
Dell Precision Ultra-Speed drive Duo, which
understand the importance of time and
deliver exception read/write storage
workflow for all professional creators. With
performance
this in mind we design technology with the
most innovative performance technologies, Outstanding reliability
and work with our software partners to test
The software applications that many
and certify all Dell Precisions, so that we
industries use to create demand computers
maximize performance and minimize
that are stable and reliable. Dell invests
downtime.
thousands of hours with Independent
Powerful performance Software Vendors (ISV) rigorously testing
our Dell Precision workstations so we can
Professional software applications and the
deliver a tested, and fully optimized
time it takes you to render, model, and
workstation to you. We partner with
process are all key factors to your creativity.
companies like Autodesk, Adobe, and
Every Dell Precision comes with the
Solidworks and many others to ensure your
exclusive Dell Precision Optimizer installed.
Dell Precision workstations work
This unique software, which can be
harmoniously with your software, as well as
centrally managed using your existing
improve the quality of technical support
System Center Configuration Manager
you will receive in the event that you need
(SCCM) console, enables users to
it. If you do need technical support, Dell
experience increased application
ProSupport Plus is the most complete
performance and productivity from their
service and support offering in the industry.
Dell Precision workstation by automatically
adjusting system settings based on the Recommended accessories
needs of specific professional software
Dell offers a complete portfolio of
applications. The Dell Precision Tower
recommended accessories for your Dell
3620 includes the latest 6th Generation
Precision workstations. These accessories
Intel® Core™ and Intel® Xeon™
include the world’s #1 Dell monitor brand,
processors, NVIDIA Quadro® or AMD
industry-specific peripherals, keyboards
FirePro™ professional graphics card,
and mice.
Feature Precision Tower 3000 Series (3620) Technical Specification
Intel® Xeon® Processor E3-1200 v5 Family; 6th generation Add Intel Core i7 (Including I7-6700K Processor), i5 and i3; Intel Turbo Boost
Processor Options1
technology(5) and Intel Integrated HD Graphics on select Processors; optional vPro™ Technology

Windows® 10 Professional (64 bit) Windows® 7 Professional (32-Bit)


Windows® 10 Home (64 bit) Windows® 7 Professional (64-Bit)
Operating
Windows® 8.1 Professional (64-Bit) Red Hat® Enterprise Linux® 7.2
System Options2 Windows® 8.1 Home (64 bit) Ubuntu Linux 14.04
NeoKylin 6.0 (China only)

Chipset Intel® C236 Chipset

Memory Options 3 4 Dimm Slots; Up to 64GB 2133Mhz Non-ECC DDR4 Memory; Up to 64GB 2133Mhz ECC DDR4 Memory

Graphics Options 3 One PCI Express® x16 Gen 3 Graphics card up to 150W (Total for Graphics) (Some cards available in Dual Config)

Mid-range 3D cards: Entry 3D cards: Professional 2D cards:


AMD FirePro W7100 AMD FirePro W4100 NVIDIA NVS 510
AMD FirePro W5100 AMD FirePro W2100 NVIDIA NVS 315
NVIDIA Quadro M4000 NVIDIA Quadro K620
NVIDIA Quadro K2200 NVIDIA Quadro K420
NVIDIA NVS 310
NVIDIA Quadro M2000 Intel HD Graphics 530/P530

Support for up to (1) M.2 PCIe SSD on motherboard slot and Up to (2) 3.5” SATA or (4) 2.5” SATA. Support for Intel Ready Mode technology
Storage Options4 Support for up to (1) additional PCIe SSD on Dell Precision Ultra-Speed drive (x8) with active cooling

M.2 PCIe SSD (NVMe) 2.5” SATA SSD 2.5” SATA 7200 RPM 3.5” SATA Self Encrypting Drives
Up to (1) 1TB on MB Up to (4) 512GB Up to (4) 1TB 7200 Up to (2) 4TB 5400 RPM
RPM 500 GB 7200 RPM or
Up to (1) 1TB on Dell Up to (2) 2TB 7200 RPM
512GB 2.5” SSD
Precision Ultra-Speed
drive

Storage Controller Integrated: Intel Rapid storage Controller 12.0 supporting SATA 6Gb/s and host based RAID 0/1/5/10

Integrated: Intel Ethernet Connection I219-LM 10/100/1000


Communications
Optional: Intel 10/100/1000 PCIe Gigabit Networking card

Audio Controller Integrated Realtek ALC3861 High Definition Audio Codec (2 Channel)

Speakers Internal Speaker; Optional Dell 2.0 stereo speaker systems available and Dell sound bar for select flat-panel displays

Optional Thunderbolt 2 PCIe Card (coming soon) Optional Serial/Parallel Port PCIe Card
Add-in cards Optional 1394 a/b PCIe Card (3 Ports – 2x 1394b + 1x 1394a) Support for up to (1) additional PCIe SSD on Dell Precision Ultra-Speed drive
(x8) with active cooling

Front Internal Rear


2 – USB 2.0 1 – USB 2.0 2 – USB 2.0 1 – RJ45 Network Connector
2 – USB 3.0 4 – SATA 6Gb/s 4 – USB 3.0 1 – Serial
I/O Ports 1 – Microphone
1 – Headphone
2 – PS2 1 – Audio Line in/Microphone
2 – DisplayPort 1 – Audio Line out
1 – HDMI
HxWxD: 14.17” x 6.89” x 17.12” (36cm x 17.5cm x 43.5cm)
Bays: (2) internal 3.5” bays - supports (2) 3.5” or (4) 2.5” drives; (2) external 5.25” optical bays
Slots: (1) Full Height PCIe x16 Gen3; (1) Full Height PCIe x16 Gen 3 (wired x4); (1) Full Height PCIe x4 Gen3; (1) Full Height PCI; (1) M.2
Chassis
(22x80 mm)
Power Supply: 365W 90% efficient PSU (80PLUS Gold Certified Certified) Energy Star compliant;
290W 85% efficient PSU (80PLUS Bronze Certified) Energy Star Compliant

Storage devices Optional: Up to 2 optical drives: DVD-ROM; DVD+/-RW, Blu Ray Writer, 19-in-1 Media Card reader installed in 5.25" bay

Trusted Platform Module TPM 1.2 (TPM 2.0 - firmware upgradable) Dell Data Protection| Security Tools, Dell Data Protection| Encryption,
Dell HW Crypto Accelerator, Microsoft Windows Bitlocker, Local HDD data wipe via BIOS ("Secure Erase"), Encryption - SED HDD (Opal
Security Options FIPS), Chassis lock slot support, Chassis Intrusion Switch, D-Pedigree (Secure Supply Chain Functionality), Setup/BIOS Password, Optional
Smart Card keyboards, Intel® Trusted Execution Technology, Intel® Identity Protection Technology, Dell Secure Works, BIOS support
optional Computrace5 , Intel Software Guard extensions

Systems Management6 Dell Client Command Suite; Out of Band management support via vPro

ENERGY STAR® configurations available including 80 PLUS® Platinum power supplies; EPEAT® registered (see epeat.net for specific
Regulatory &
registration rating/status by country); China CECP; GS Mark. For a complete listing of declarations & certifications, see Dell’s regulatory &
Environmental compliance homepage at dell.com/regulatory_compliance

3-Year Limited Hardware Warranty and 3-year NBD On-Site Service after Remote Diagnosis
Warranty & Support
Optional: Dell ProSupport is designed to rapidly respond to your business’s needs, help protect your investment and sensitive data, and
Services7
provide enhanced proactive support services to help reduce risk and complexity within your IT environment

TAA TAA Configurations Available

Some options available only in select regions; ISV certification applies to select configurations; 1Intel Turbo Boost mode only available on Xeon, Core i7 and Core i5 processors. Intel Integrated HD graphics only available with select
processors; 2A 64-bit operating system is required to support 4GB or more of system memory; . 3GB means 1 billion bytes and TB equals 1 trillion bytes; actual capacity varies with preloaded material and operating environment and will
be less; 4GB means 1 billion bytes and TB equals 1 trillion bytes; significant system memory may be used to support graphics, depending on system memory size and other factors; 5Computrace is not a Dell offer. Certain conditions
apply. For full details, see terms and conditions at www.absolute.com/en/about/legal/agreements. 6Systems Management Options:Intel® vPro Technology - Fully vPro-capable at point of purchase; the vPro systems management
option requires vPro processors. Includes support for Intel Advanced Management Technology (AMT) 9.x. Intel® Standard Manageability - Fully enabled at point of purchase, the Intel Standard Management option is a subset of the
AMT features. ISM is not upgradeable to vPro technology post-purchase. No Out-of-Band Systems Management - This option entirely removes Intel out of band systems (OOB) management features. The system can still support in
band management. OOB management support through AMT cannot be upgraded post-purchase. 7Availability and terms of Dell Services vary by region. For more information, visit Dell.com/servicecontracts/global; Limited Hardware
Warranty available by writing Dell USA LP, Attn: Warranties, One Dell Way, Round Rock, TX 78682 or see www.dell.com/warranty; Onsite Service after Remote Diagnosis: Remote Diagnosis is determination by online/phone technician
of cause of issue; may involve customer access to inside of system and multiple or extended sessions. If issue is covered by Limited Hardware Warranty (www.dell.com/warranty) and not resolved remotely, technician and/or part will
be dispatched, usually within 1 business day following completion of Remote Diagnosis. Availability varies. Other conditions apply.
Copyright 2015 Dell Inc. All rights reserved. Venue is a trademark of Dell Inc. Intel and Xeon are trademarks or registered trademarks of Intel Corporation or its subsidiaries in the United States of America and other countries. Microsoft,
and Windows are trademarks or registered trademarks of Microsoft Corporation in the U.S. and other countries. . Other trademarks or trade names may be used in this document to refer to either the entities claiming the marks and
names or their products. Dell disclaims proprietary interest in the marks and names of others. Reproduction in any manner whatsoever without express written permission from Dell Inc. is strictly forbidden.
Dell Precision 15
7000 Series (7510)
Dell’s most powerful 15 inch mobile
workstation ever

The Dell Precision 15 7000 Series is Dell Precision workstation by automatically


completely re-designed to look as good as adjusting system settings based on the
it performs. needs of specific professional software
applications. The Dell Precision 15 7000
Every Dell Precision is designed around
Series includes the latest 6th Generation
innovation, performance and reliability. We
Intel® Core™ and the world’s first Intel®
understand the importance of time and
Xeon™ mobile processors and the choice
workflow for all professional creators. With
of NVIDIA Quadro® or AMD FirePro™
this in mind we design technology with the
professional graphics cards to provide you
most innovative performance technologies,
with the performance to make the most of
and work with our software partners to test
your time. The Dell Precision 15 7000
and certify all Dell Precisions so that we
supports RAID and up to 3TB storage,
maximize performance and minimize
including ultra-fast PCIe NVMe SSDs.
downtime.
Outstanding reliability
Innovative design
The software applications that many
Our goal was to create a workstation with
industries use to create demand computers
tower-like performance in a form factor
that are stable and reliable. Dell invests
that is not only mobile, but one that a
thousands of hours with Independent
person would be proud to carry. The
Software Vendors (ISV) rigorously testing
design team used new technologies and
our Dell Precision workstations so we can
premium materials to create a device that
deliver a tested, and fully optimized
delivers the most performance possible,
workstation to you. We partner with
while being truly mobile and beautiful to
companies like Autodesk, Adobe, and
look at. Dell’s cooling solution is so
Solidworks and many others to ensure your
advanced, your most processor-intensive
Dell Precision workstations work
applications will benefit from never
harmoniously with your software, as well as
dropping out of turbo frequencies.
improve the quality of technical support
Powerful Performance you will receive in the event that you need
it. If you do need technical support, Dell
Professional software applications and the ProSupport Plus is the most complete
time it takes you to render, model, and service and support offering in the industry.
process are all key factors to your creativity.
Every Dell Precision comes with the Recommended accessories
exclusive Dell Precision Optimizer installed.
Dell offers a complete portfolio of
This unique software, which can be
recommended accessories for your Dell
centrally managed using your existing
Precision workstations. These accessories
System Center Configuration Manager
including docking, the world’s #1 Dell
(SCCM) console. It enables users to
monitor brand, industry-specific
experience increased application
peripherals and carrying cases.
performance and productivity from their
Feature Dell Precision 15 7000 Series Technical Specifications
Model 7510

Processors1 Intel Core Xeon Ex-xxx Z3+ Quad Core Xeon x.xxGHz, x.xGHz Turbo, 16MB 45W (coming soon)
Intel Core Xeon Ex-xxx Z2+ Quad Core Xeon x.xxGHz, x.xGHz Turbo, 16MB 45W (coming soon)
Intel Core Xeon E3-1535M v5 Quad Core Xeon 2.90GHz, 3.80GHz Turbo, 8MB 45W
Intel Core Xeon E3-1505M v5 Quad Core Xeon 2.80GHz, 3.70GHz Turbo, 8MB 45W
Intel Core i7-6920HQ Quad Core 2.90GHz, 3.80GHz Turbo, 8MB 45W
Intel Core i7-6820HQ Quad Core 2.70GHz, 3.60GHz Turbo, 8MB 45W
Intel Core i5-6300HQ Quad Core 2.30GHz, 3.20GHz Turbo, 6MB 45W

Operating Systems2 Windows™ 7 Pro (64-bit)


Windows™ 8.1 Pro (64-bit)
Windows™ 10 Pro, Downgrade to Win 7 & 8.1 Pro (64-bit)
Windows™ 10 Home (64-bit)
Red Hat Enterprise Linux (RHEL) 7.2 (coming soon)
Canonical Ubuntu 14.04 SP1 (coming soon)

Chipset Intel Mobile CM236

Memory3 4 DIMM slots: up to 64GB DDR4 2133MHz


Up to 32GB DDR4 2667MHz overclocked memory (coming soon)
Up to 32GB ECC DDR4 2133MHz

Graphics3 AMD FirePro W5170M with 2GB GDDR5 dedicated memory


NVIDIA Quadro M1000M with 2GB GDDR5 dedicated memory
Nvidia Quadro M2000M with 4GB GDDR5 dedicated memory
Intel® HD Graphics P530 & 530
Display Options 15.6" FHD (1920x1080) Anti-Glare LED-backlit (45% color gamut)
15.6" UltraSharp™ FHD IPS (1920x1080) Wide View Anti-Glare LED-backlit with Premium Panel Guarantee (72% color gamut)
15.6" UltraSharp™ FHD IPS Touch(1920x1080) Wide View Anti-Glare LED-backlit with Premium Panel Guarantee (72% color
gamut)
15.6" UltraSharp™ UHD IGZO(3840x2160) PremierColor Wide View Anti-Glare LED-backlit with Premium Panel Guarantee (100%
Adobe color gamut)

Storage Options4 Support for two storage devices: one M.2 PCIe solid state drive and one 2.5” PCIe/SATA drive: Dell Fast Response Free Fall
Sensor standard
Hard Disk Drive (HDD): 2.5” 500GB 7200RPM up to 2TB 2.5” 5400RPM SATA 6Gb/s
Solid State Drive (SSD): 256GB, 512GB, 512GB SED, 1TB 2.5” SATA 6Gb/s
M.2 PCIe NVMe Solid State Drive (M.2 SSD): 256GB, 512GB, 512GB SED (coming soon) 1TB SSD

Communication Options5 Wired: Integrated Intel 82580 10/100/1000 Gigabit Ethernet


Wireless LAN & Bluetooth:
Intel® 8260 Dual-Band 2x2 802.11 ac (Miracast) Bluetooth® 4.0, NFC
Dell DW1830 3x3 802.11ac + Bluetooth 4.0, NFC
Dell DW1820A 2x2 801.11ac + Bluetooth 4.1, NFC
Mobile Broadband & GPS:
DW5811e (Gobi 4g/LTE – FMC)

Multimedia Dual integrated high quality speakers and optional dual integrated noise cancelling digital array microphones
MaxxAudio® Pro by Waves
Optional integrated light sensitive HD video webcam

I/O Ports and Connectors 1 x SD Card Reader (SD, SDHC, SDXC, supporting up to 64GB); 1 x Thunderbolt® 3 optional (coming Jan. 2016)
4 x USB3.0 with PowerShare; 1 x mDP; 1 x HDMI; 1 x Headphone and microphone combo jack; 1 x SmartCard Reader (optional)

Security6 Intel® Platform Trust Technology, Trusted Platform Module (TPM) 1.2, Chassis lock slot support
Support for optional Computrace and Optional SmartCard Reader, Contactless SmartCard Reader/Fingerprint Reader or FIPS
Fingerprint Reader

Dimensions and weight7 Width: 14.88” / 378mm; Depth: 10.38”/ 261mm ;Height (front-Rear): Front 1.09”/27.76mm – 1.3”/(33mm)
Starting at 2.79kg (6.16lb)

Battery 72Whr Lithium Ion polymer battery


91Whr Lithium Ion polymer battery
85Whr long life cycle battery

Power Adaptor 180 Watt AC adapter (7mm barrel)

Regulatory and Environmental8 ENERGY STAR 6.1; EPEAT registered


Compliance
TAA Configurations available YES

Some options available only in select regions; ISV certification applies to select configurations; 1Intel Turbo Boost mode only available on Xeon, Core i7 and Core i5 processors. Intel
Integrated HD graphics only available with select processors; 2A 64-bit operating system is required to support 4GB or more of system memory; . 3GB means 1 billion bytes and TB equals 1
trillion bytes; actual capacity varies with preloaded material and operating environment and will be less; 4GB means 1 billion bytes and TB equals 1 trillion bytes; significant system memory
may be used to support graphics, depending on system memory size and other factors; 5Miracast wireless technology: requires a compatible media adapter (sold separately) and an HDMI-
enabled display. 6Computrace is not a Dell offer. Certain conditions apply. For full details, see terms and conditions at www.absolute.com/en/about/legal/agreements. 7Weights vary
depending on configuration and manufacturing variability. 8See epeat.net for specific registration rating/status by country. For a complete listing of declarations & certifications, see Dell’s
regulatory & compliance homepage at dell.com/regulatory_compliance. Availability and terms of Dell Services vary by region. For more information, visit Dell.com/servicecontracts/global;
Limited Hardware Warranty available by writing Dell USA LP, Attn: Warranties, One Dell Way, Round Rock, TX 78682 or see www.dell.com/warranty; Onsite Service after Remote Diagnosis:
Remote Diagnosis is determination by online/phone technician of cause of issue; may involve customer access to inside of system and multiple or extended sessions. If issue is covered by
Limited Hardware Warranty (www.dell.com/warranty) and not resolved remotely, technician and/or part will be dispatched, usually within 1 business day following completion of Remote
Diagnosis. Availability varies. Other conditions apply. FPO
Copyright 2015 Dell Inc. All rights reserved. Venue is a trademark of Dell Inc. Intel and Xeon are trademarks or registered trademarks of Intel Corporation or its subsidiaries in the United
States of America and other countries. Microsoft, and Windows are trademarks or registered trademarks of Microsoft Corporation in the U.S. and other countries. Other trademarks or trade
names may be used in this document to refer to either the entities claiming the marks and names or their products. Dell disclaims proprietary interest in the marks and names of others.
Reproduction in any manner whatsoever without express written permission from Dell Inc. is strictly forbidden.
Latitude 15 5000
Series (E5570)

Built for work. Designed to impress.


The sleek new Latitude 15 5000 Series helps end users get more done with an
expansive array of features, ports and options. The world’s most secure mainstream
laptop also combines the manageability and reliability expected from Latitude.

It’s beautifully designed and built-to last with an enhanced exterior design, utilizing
carbon fiber reinforced polymer materials for added durability, and an optional
touch-screen clad with Corning® Gorilla® NBT™ for a brilliant display and ultimate
scratch resistance.

This 15-inch laptop features the latest 6th generation Intel® Core™ i vPro dual or quad
core processors and advanced features such as industry-leading M.2 solid state drives
and DDR4 memory, plus a full assortment of business ready ports.

It’s also well-equipped with a portfolio of essential accessories for ultimate on-the-
go or at-the-desk productivity and backed by 24/7 access to enterprise-class support
with optional Dell ProSupport™ Plus.

For more information visit: dell.com


Feature Technical Specification
Model Number1 Latitude 15 5000 Series E5570
Processor Options1 6th Generation Intel® up to Core™ i7 Processors, U, 6th Generation Intel® up to Core™ i7 Processors, H,
ULT, Dual Core Standard Volt, Quad Core
Operating System1,2 Microsoft® Windows® 7 Professional 32/64 bit
Microsoft® Windows® 7 Professional 32/64-bit (available through downgrade rights from Windows® 10 64-bit)
Microsoft® Windows® 8.1, Pro, Single Language, 64-bit
Microsoft® Windows® 8.1 Pro 64-bit (available through downgrade rights from Windows® 10 64-bit)
Microsoft® Windows® 10 Home, Home Single Language, Pro, 64 bit
Ubuntu Linux 14.04 LTS SP1 64-bit
NeoKylin v6.0 32 bit
Memory Options1,2,3 DDR4 2133MHz; 2 slots supporting up to 16GB
1
Chipset Integrated with the Processor
Intel Responsiveness Intel® Rapid Storage Technology
Technologies1,7
Graphics1,13 Intel® HD Graphics 520 Intel® HD Graphics 530
AMD Radeon™ R7 M360 AMD Radeon™ R7 M370
Display1 15.6” HD (1366 x 768) Anti-glare (16:9) WLED, 200 nits, Carbon Fiber Reinforced Polymer LCD Back
15.6” FHD WVA (1920 x 1080) Anti-glare (16:9) WLED, 300 nits, Carbon Fiber Reinforced Polymer LCD Back
15.6” FHD WVA Touch with Corning® Gorilla® NBT, (1920 x 1080), 270 nits, Carbon Fiber Reinforced Polymer
LCD Back
Storage Options 1, 5 HDD: up to 1TB, Hybrid, OPAL SED options
SSD 2.5”, 7mm: up to 480GB
SSD M.2 SATA: up to 512GB, OPAL SED options
SSD M.2 PCIe: up to 512GB options
Dell Fast Response Free Fall Sensor and HDD Isolation (standard feature)
Security TPM 1.2 - FIPS 140-2 and TCG certified (Windows 7, 8.1 and 10)17
TPM 2.0 - FIPS 140-2 and TCG Certified (Spring of 2016) (Windows 10)17
Optional Touch Finger Print Reader, Contacted FIPS 201 Smart Card Reader, Contactless Smart Card Reader/
NFC with FIPS 140-2 Level 3 (Spring 2016) Dell Control Vault 2™
Optional FIPS Touch Finger Print Reader, Contacted FIPS 201 Smart Card Reader, Contactless Smart Card
Reader/NFC with FIPS 140-2 Level 3 (Spring 2016) Dell Control Vault 2™
Optional Contacted FIPS 201 Smart Card Reader with Control Vault 2 FIPS 140-2 Level 3 (Spring 2016)
Certification
Optional Hardware Crypto Accelerator (HCA) FIPS 140-2 Level 3 Certification
DDP|Security Tools
DDP|Protected Workspace (1 year subscription included)
Optional DDP| Encryption Software
Optional DDP|Endpoint Security Software
Lock slot
Docking1 EDocking EDocking
Dell Wireless Dock (Optional, sold separately, requires Dell Wireless Dock (Optional, sold separately, requires
optional installed Intel® Tri-Band Wireless-AC 18260 optional installed Intel® Tri-Band Wireless-AC 18260
WiGig + Wi-Fi + BT4.18(Winter 2016) WiGig + Wi-Fi + BT4.18(Winter 2016)
Dell Dock (optional, sold separately)
Dell Thunderbolt™ Dock (optional, sold separately)
Optical Drive Options External Options Only
Multimedia1 High Quality Speakers
Headset/mic combo jack
Noise reducing array microphones
Optional HD or FHD video webcam. No web cam option
Battery Options1 47 Whr (3 Cell) Lithium Polymer battery with 62 Whr (4 Cell) Lithium Polymer battery with
ExpressCharge™ (UMA) ExpressCharge™
62 Whr (4 Cell) Lithium Polymer battery with 62 Whr (4 Cell) Long Life Cycle Lithium Polymer
ExpressCharge™ battery with ExpressCharge™ (Winter 2016)
62 Whr (4 Cell) Long Life Cycle Lithium Polymer 84 Whr (6 Cell) Lithium Polymer battery with
battery with ExpressCharge™ ExpressCharge™
84 Whr (6 Cell) Long Life Cycle Lithium Polymer
battery with ExpressCharge™ (Winter 2016)
Power Options1 65W adapter 65W adapter
65W BFR/PVC free adapter 65W BFR/PVC free adapter
90W adapter
Connectivity options1,14,15 10/100/1000 Ethernet
Wireless LAN Options:
Dell Wireless™ 1820 802.11AC Dual-Band Wi-Fi + BT 4.1 Wireless Card (2x2)
Intel® Dual-Band Wireless-AC 8260 Wi-Fi Wireless Card (No BT) (2x2)
Intel® Dual-Band Wireless-AC 8260 Wi-Fi + BT 4.1 Wireless Card (2x2)
Dell Wireless™ 1820A Dual-Band Wireless-AC + BT 4.1 (2x2) (Winter 2016)
Optional Mobile Broadband Options:8, 10
Qualcomm® Snapdragon™ X7 LTE (DW5811) (EMEA/APJ/ROW)
Qualcomm® Snapdragon™ X7 LTE (DW5811) for AT&T (Winter 2016), Verizon, Sprint (Spring 2016) (US)
Qualcomm® Snapdragon™ X7 HSPA+ (DW5811) (China/Indonesia)
Optional WiGig Option:8
Intel® Tri-Band Wireless-AC 18260 WiGig + Wi-Fi + BT4.1 Wireless Card
Feature Technical Specification
Model Number1 Latitude 15 5000 Series E5570
Ports, Slots & Chassis1 3 USB 3.0 (one with PowerShare), HDMI, VGA 3 USB 3.0 (one with PowerShare), HDMI, VGA
Network connector (RJ-45), external SIM card tray Network connector (RJ-45), external SIM card tray
option option
SD 4.0 Memory card reader SD 4.0 Memory card reader
Headset/mic combo jack Headset/mic combo jack
Optional Contacted SmartCard Reader and touch Optional Contacted SmartCard Reader and touch
Fingerprint Reader Fingerprint Reader
Two M.2 Expansion slots: 1 WWAN/HCA and 1 Two M.2 Expansion slots: 1 WWAN/HCA and 1 WLAN/
WLAN/BT/WiGig BT/WiGig
EDock port EDock port
Lock slot Lock slot
Thunderbolt™ 3 (Winter 2016)
Dimensions & Weight1,16 Width: 14.8” / 377.1mm Width: 14.8” / 377.1mm
Height (front): 0.9“ / 23.8mm Height (front): 1.0“ / 24.6mm
Depth: 9.9” / 252.6mm Depth: 9.9” / 252.6mm
Starting weight: 4.37 lbs. / 1.98 kg Starting weight: 4.61 lbs. / 2.09 kg
(3 cell battery, M.2 SSD, non touch HD LCD) (4 cell battery, M.2 SSDA, non touch, FHD LCD)
Regulatory and Environmental Regulatory Model: P48F
Compliance1 Regulatory Type: P48F001
ENERGY STAR 6.1
EPEAT Gold Registered. For specific country participation and rating, please see www.epeat.net
BFR/PVC free9
TAA configurations available
Input1 Dual Pointing non-backlit Keyboard
Dual Pointing backlit Keyboard
Multi-touch Touchpad
Systems Management1 Intel® vPro™ Technology (iAMT 9.0) (optional, requires Intel WiFi® Link WLAN and a vPro compatible
processor), Dell Client Command Suite available (dell.com/command), Factory Installed Dell Client
Command | Update, Factory Installed Dell Command | Power Manager
Warranty and Service1 Limited Hardware Warranty4 Standard 1 year Mail-in Service after Remote Diagnosis11 optional 3, 4 and 5 year
hardware warranty extensions and 3-5 year Dell ProSupport contracts available12
Peripheral Ecosystem1 Purpose built ecosystem to enable productivity on the go or at the desk. Includes Dell E-Port Replicator,
Dell Power Companions, Dell Wireless Dock, Dell Professional Briefcase, Dell 24” Monitor, and Dell Wireless
Keyboard and Mouse

1
Offering may vary by country and by configuration
2
A 64-bit operating system is required to support 4GB or more of system memory.
3
GB means 1 billion bytes and TB equals 1 trillion bytes; actual capacity varies with preloaded material and operating environment and will be less.
4
Limited Hardware Warranty: For copy of Limited Hardware Warranty, write Dell USA LP, Attn: Warranties, One Dell Way, Round Rock, TX 78682 or see www.dell.com/warranty
5
GB means 1 billion bytes and TB equals 1 trillion bytes; actual capacity varies with preloaded material and operating environment and will be less.
6
COMPUTRACE Not a Dell offer. Certain conditions apply. For full details, see terms and conditions at www.absolute.com/en/about/legal/agreements.
7
Intel Rapid Storage Technology requires a HDD, mSATA, or an SSD, as primary storage device. See OS requirements
8
Wireless antenna available only at time of system purchase
9
Dell Latitude 5000 Series are brominated flame retardant free (BFR-free) and polyvinyl chloride free (PVC-free); meeting the definition of BFR-/PVC-free as set forth in the iNEMI Position Statement
on the ‘Definition of Low-Halogen Electronics (BFR-/CFR-/PVC-free)’. Plastic parts contain less than 1,000 ppm (0.1%) of bromine (if the Br source is from BFRs) and less than 1,000 ppm (0.1%)
of chlorine (if the Cl source is from CFRs or PVC or PVC copolymers). All printed circuit board (PCB) and substrate laminates contain bromine/chlorine total less than 1,500 ppm (0.15%) with a
maximum chlorine of 900 ppm (0.09%) and maximum bromine being 900 ppm (0.09%). 
10
Mobile Broadband Subject to service provider’s broadband subscription and coverage area; additional charges apply.
11
Onsite Service after Remote Diagnosis: Remote Diagnosis is determination by online/phone technician of cause of issue; may involve customer access to inside of system and multiple or
extended sessions. If issue is covered by Limited Hardware Warranty (www.dell.com/warranty) and not resolved remotely, technician and/or part will be dispatched, usually within 1 business day
following completion of Remote Diagnosis. Availability varies. Other conditions apply.
12
Dell Services: Availability and terms of Dell Services vary by region. For more information, visit www.dell.com/servicedescriptions.
13
GB means 1 billion bytes and TB equals 1 trillion bytes; significant system memory may be used to support graphics, depending on system memory size and other factors.
14
Miracast Wireless Technology: Requires a compatible media adapter (sold separately) and an HDMI-enabled display.
15
Intel Wireless Display: Requires an Intel wireless card, a compatible media adapter (sold separately) and an HDMI or composite AV-enabled display.
16
Weights vary depending on configuration and manufacturing variability.
17
Field upgradable from FIPS 140-2 Certified TPM 1.2
1 Product basics

ł Product comparison

ł Environmental features

ł Product features

ł Product views

ENWW 1
Product comparison
Base models

ł Prints up to 20 pages per minute (ppm) on letter-size and A4-size media.

ł 100-sheet multipurpose tray (Tray 1) and 250-sheet input tray (Tray 2)

ł Optional 500-sheet input tray (Tray 3)

ł Hi-Speed universal serial bus (USB) 2.0 port

Network models

ł Prints up to 20 ppm on letter-size and A4-size media.

ł 100-sheet multipurpose tray (Tray 1) and 250-sheet input tray (Tray 2)

ł Optional 500-sheet input tray (Tray 3)

ł Hi-Speed universal serial bus (USB) 2.0 port

ł Built-in 10/100 Base-T network port with IPv4/IPv6

Duplex models

ł Prints up to 10 ppm on letter-size and A4-size media.

ł 100-sheet multipurpose tray (Tray 1) and 250-sheet input tray (Tray 2)

ł Optional 500-sheet input tray (Tray 3)

ł Hi-Speed universal serial bus (USB) 2.0 port

ł Built-in 10/100 Base-T network port with IPv4/IPv6

ł Automatic duplexer

2 Chapter 1 Product basics ENWW


Environmental features
Duplex Save paper by using duplex printing as your default print setting.

Recycling Reduce waste by using recycled paper.

Recycle print cartridges by using the HP Planet Partners return process. See HP LaserJet print
supplies on page 141.

For more information about recycling, go to www.hp.com/recycle.

Energy savings Save energy by initiating sleep mode for the product.

HP Smart Web printing Use HP Smart Web printing to select, store, and organize text and graphics from multiple Web
pages and then edit and print exactly what you see onscreen. It gives you the control you need
for printing meaningful information while minimizing waste.

Job storage Use the job storage features to manage print jobs. By using job storage, you activate printing
while you are at the shared product, eliminating lost print jobs that are then reprinted.

ENWW Environmental features 3


Product features
Print ł Prints up to 20 pages per minute (ppm) on letter-size and A4-size media.

ł Prints at 600 x 600 dots per inch (dpi) with Image REt 3600 text and graphics.

ł Includes adjustable settings to optimize print quality.

ł Offers automatic duplexing (duplex models only).

Memory ł Includes 192-megabyte (MB) random-access memory (RAM).

Supported operating ł Windows Vista (Starter Edition, 32-bit, and 64-bit)


systems
ł Windows Vista Server 2008 (32-bit)

ł Windows XP (32-bit, Service Pack 2)

ł Windows XP (64-bit, Service Pack 1)

ł Windows Server 2003 (Service Pack 1)

ł Windows 2000 (Service Pack 4)

ł Mac OS X v10.3, v10.4, v10.5, and v10.6

Paper handling ł Tray 1 (multipurpose tray) holds up to 100 sheets of print media or 10 envelopes.

ł Tray 2 holds up to 250 sheets of print media.

ł Optional Tray 3 holds up to 500 sheets of print media.

ł Output bin holds up to 250 sheets of print media.

Printer driver features ł ImageREt 3600 has been improved for this product. The improvements offer trapping
technologies, greater control over dot placement, and more precise control of toner
distribution within a dot. These new technologies result in high quality printing with smooth
colors.

Interface connections ł Includes a Hi-Speed USB 2.0 port.

ł Built-in 10/100 Base-T network port with IPv4/IPv6 (network models only).

Environmental features ł To determine the Energy Star® qualification status for this product, see the Product Data
Sheet or Specifications Sheet.

Economical printing ł Provides N-up printing (printing more than one page on a sheet).

ł The printer driver provides the option to manually print on both sides.

Supplies ł The print cartridges use HP ColorSphere toner. For information about the number of pages
the cartridges can print, see www.hp.com/go/pageyield. Actual yield depends on specific
use.

Accessibility ł Online user guide is compatible with text screen-readers.

ł Print cartridges can be installed and removed by using one hand.

ł All doors and covers can be opened by using one hand.

4 Chapter 1 Product basics ENWW


Product views
Front and side view

4
6
5
1 Output bin (holds 250 sheets of standard paper)

2 Front door (provides access to the print cartridges)

3 Tray 2 (holds 250 sheets of standard paper and provides jam access)

4 Optional Tray 3 (holds 500 sheets of standard paper)

5 Power button

6 Control panel

7 Optional Tray 3 right jam access

8 Tray 1 (multipurpose tray—holds 100 sheets of standard paper)

ENWW Product views 5


Back view

2 4
3
1 Rear door (for toner waste bin access)

2 DIMM door (for adding memory—one additional DIMM slot is available)

3 Hi-Speed USB 2.0 port and network port (network models only)

4 Power connection

Model and serial numbers


The model number and serial number are listed on an identification label located on the left side of the
product.

The label contains information about the country/region of origin and the revision level, manufacturing
date, production code, and production number of the product. The label also contains power rating and
regulatory information.

6 Chapter 1 Product basics ENWW


1 Product basics

ł Product comparison

ł Environmental features

ł Accessibility features

ł Product views

ENWW 1
Product comparison
HP LaserJet Pro 300 color M351a ł Performance: Prints 18 pages per minute (ppm) on A4-size paper snf 19 ppm on Letter-
size paper
CE955A
ł Paper handling:

Tray 1 holds 50 sheets, Tray 2 holds 250 sheets

Optional Tray 3 holds 250 sheets

The output bin holds 150 sheets

ł Supported operating systems:

Windows XP, 32-bit

Windows Vista, 32-bit and 64-bit

Windows 7, 32-bit and 64-bit

Mac OS X v10.5 and later

ł Connectivity: Hi-Speed USB 2.0

ł Software installation: For Windows, use the product CD for software installation.

ł Memory: 128 MB RAM, expandable to 384 MB

ł Control-panel display: 2-line text

HP LaserJet Pro 400 color M451nw Has the same features as the HP LaserJet Pro 300 color M351a model, with the following
differences:
CE956A
ł Performance: Prints 20 pages per minute (ppm) on A4-size paper and 21 ppm on
Letter-size paper

ł Connectivity:

Hi-Speed USB 2.0

10/100 Ethernet LAN connection

Wireless network connection

2 Chapter 1 Product basics ENWW


HP LaserJet Pro 400 color M451dn Has the same features as the HP LaserJet Pro 300 color M351a model, with the following
differences:
CE957A
ł Performance: Prints 20 pages per minute (ppm) on A4-size paper and 21 ppm on
Letter-size paper

ł Connectivity:

Hi-Speed USB 2.0

10/100 Ethernet LAN connection

ł Automatic duplex printing

HP LaserJet Pro 400 color M451dw Has the same features as the HP LaserJet Pro 300 color M351a model, with the following
differences:
CE958A
ł Performance: Prints 20 pages per minute (ppm) on A4-size paper and 21 ppm on
Letter-size paper

ł Connectivity:

Hi-Speed USB 2.0

10/100 Ethernet LAN connection

Wireless network connection

ł Automatic duplex printing

ENWW Product comparison 3


Environmental features
Duplex printing Save paper by using the manual duplex printing option. Automatic duplex printing is available
with the HP LaserJet Pro 400 color M451dn and HP LaserJet Pro 400 color M451dw models.

Print multiple pages per sheet Save paper by printing two or more pages of a document side-by-side on one sheet of paper.
Access this feature through the printer driver.

Recycling Reduce waste by using recycled paper.

Recycle print cartridges by using the HP Planet Partners return process.

Energy savings Instant on Fusing technology and sleep mode enable this product to quickly go into reduced
power states when not printing, thus saving energy.

Accessibility features
The product includes several features that aid users with accessibility issues.

ł Online user guide that is compatible with text screen-readers.

ł Print cartridges can be installed and removed by using one hand.

ł All doors and covers can be opened by using one hand.

4 Chapter 1 Product basics ENWW


Product views

Front view

1 Output bin

2 Legal-output extension

3 Front door (provides access to the print cartridges)

4 Tray 1 (multipurpose tray)

5 Tray 2 (provides jam access)

6 Optional Tray 3

7 Power button

8 Wireless button (wireless models only)

9 Control panel

10 DIMM door (for adding additional memory)

ENWW Product views 5


Back view

1 Hi-Speed USB 2.0 port and network port

NOTE: The network port is present on the M451nw, M451dn, and M451dw models only.

2 Power connection

3 Rear door (for jam access)

Interface connections

1 Network port (top)

2 USB port (bottom)

6 Chapter 1 Product basics ENWW


Serial number and model number location
The serial number and product model number label is on the inside of the front door.

ENWW Product views 7


Control panel layout

1 Control-panel display: The display provides information about the product. Use the menus on the display to establish
product settings.

2 Back arrow button: Use this button for the following actions:

ł Exit the control-panel menus.

ł Scroll back to a previous menu in a submenu list.

ł Scroll back to a previous menu item in a submenu list (without saving changes to the menu item).

3 Left arrow button: Use this button to navigate through the menus or to decrease a value that appears on the display.

4 OK button: Press the OK button for the following actions:

ł Open the control-panel menus.

ł Open a submenu displayed on the control-panel display.

ł Select a menu item.

ł Clear some errors.

ł Begin a print job in response to a control-panel prompt (for example, when the message Press [OK] to continue
appears on the control-panel display).

5 Right arrow button: Use this button to navigate through the menus or to increase a value that appears on the display.

6 Cancel button: Press this button to cancel a print job whenever the attention light is blinking or to exit the control-
panel menus.

7 Ready light (green): The Ready light is on when the product is ready to print. It blinks when the product is receiving print
data, or when the product is in sleep mode.

8 Attention light (amber): The Attention light blinks when the product requires user attention.

8 Chapter 1 Product basics ENWW


LASYSTEMS - Brusselsesteenweg 208 - 1730 Asse - Belgium
Phone: +32-2-4531312 - Fax: +32-2-4531763
E-mail: info@lasystems.be

Cisco ASA 5506-X (ASA5506-SEC-BUN-K9)


125 Mbps, ASDM 7.3.x, Concurrent sessions 50000, Connections per second 5000, 80+
URL categories, FirePOWER Services and Security Pius License

Price details: PDF generated on: 17 November, 2016

Price excl. VAT: 923.97 €


Eco fees: 0.04 €
VAT 21 %: 194.04 €
Product details:
Product code: ASA5506-SEC-BUN-K9
EAN: 0882658797309
Manufacturer: Cisco

1,118.05 €
* VAT included

Meet the industry's first adaptive, threat-focused next-generation firewall (NGFW) designed for a new era of threat and
advanced malware protection. Cisco® ASA with FirePOWER Services delivers integrated threat defense for the entire
attack continuum - before, during, and after an attack. How? By combining the proven security capabilities of the Cisco
ASA firewall with the industry-leading Sourcefire® threat and Advanced Malware Protection (AMP) features together in a
single device. The solution uniquely extends the capabilities of the Cisco ASA 5500-X Series Next-Generation Firewalls
beyond what today's NGFW solutions are capable of. Whether you need protection for a small or midsized business, a
distributed enterprise, or a single data center, Cisco® ASA with FirePOWER Services provides the needed scale and
context in a NGFW solution.

Superior Multilayered Protection


Cisco ASA with FirePOWER Services brings distinctive threat-focused next-generation security services to the Cisco
ASA 5500-X Series Next-Generation Firewalls and Cisco ASA 5585-X Adaptive Security Appliance firewall products. It
provides comprehensive protection from known and advanced threats, including protection against targeted and
persistent malware attacks (Figure 1). Cisco ASA is the world's most widely deployed, enterprise-class stateful firewall.
Cisco ASA with FirePOWER Services features these comprehensive capabilities:

- Site-to-site and remote access VPN and advanced clustering provide highly secure, high-performance access and
high availability to help ensure business continuity.
- Granular Application Visibility and Control (AVC) supports more than 3,000 application-layer and risk-based controls
that can launch tailored intrusion prevention system (IPS) threat detection policies to optimize security effectiveness.
- The industry-leading Cisco ASA with FirePOWER next-generation IPS (NGIPS) provides highly effective threat
prevention and full contextual awareness of users, infrastructure, applications, and content to detect multivector threats
and automate defense response.
- Reputation- and category-based URL filtering offer comprehensive alerting and control over suspicious web traffic and
enforce policies on hundreds of millions of URLs in more than 80 categories.
- AMP provides industry-leading breach detection effectiveness, a low total cost of ownership, and superior protection
value that helps you discover, understand, and stop malware and emerging threats missed by other security layers.

Unprecedented Network Visibility


Cisco ASA with FirePOWER Services is centrally managed by the Cisco FireSIGHT Management Center, which
provides security teams with comprehensive visibility into and control over activity within the network. Such visibility
includes users, devices, communication between virtual machines, vulnerabilities, threats, client-side applications, files,
and web sites. Holistic, actionable indications of compromise (IoCs) correlate detailed network and endpoint event
information and provide further visibility into malware infections. Cisco's enterprise-class management tools help
administrators reduce complexity with unmatched visibility and control across NGFW deployments. Cisco FireSIGHT
Management Center also provides content awareness with malware file trajectory that aids infection scoping and root
cause determination to speed time to remediation.

Cisco Security Manager provides scalable and centralized network operations workflow management. It integrates a
powerful suite of capabilities; including policy and object management, event management, reporting, and
troubleshooting for Cisco ASA firewall functions when utilizing Cisco FireSIGHT Management Center.

For local, on-device management including deployments for small and midsized businesses, Cisco Adaptive Security
Device Manager (ASDM) 7.3.x provides, access control and advanced threat defense management. ASDM V 7.3.x
provides an enhanced user interface that provides quick views on trends and the ability to drill down for further analysis.

Reduced Costs and Complexity


Cisco ASA with FirePOWER Services incorporates an integrated approach to threat defense, reducing capital and
operating costs and administrative complexity. It smoothly integrates with the existing IT environment, work stream, and
network fabric. The appliance family is highly scalable, performs at up to multigigabit speeds, and provides consistent
and robust security across branch, Internet edge, and data centers in both physical and virtual environments.

With Cisco FireSIGHT Management Center, administrators can streamline operations to correlate threats, assess their
impact, automatically tune security policy, and easily attribute user identities to security events. Cisco FireSIGHT
Management Center continually monitors how the network is changing over time. New threats are automatically
assessed to determine which ones can affect your business. Responses are then focused on remediation and network
defenses are adapted to changing threat conditions. Critical security activities such as policy tuning are automated,
saving time and effort, while protections and countermeasures are maintained in an optimal state.

Cisco FireSIGHT Management Center integrates easily with third-party security solutions through the eStreamer API to
streamline operation workflows and fit existing network fabrics.

Main specifications:

Data transmission
Data transfer rate (max): 250 Mbit/s
Firewall throughput: 125 Mbit/s
Networking
Number of VPN connections: 50
Number of VLANs: 30
Ports & interfaces
Connectivity technology: Wired
USB 2.0 ports quantity: 1
Ethernet LAN (RJ-45) ports: 8
Serial ports quantity: 1
WAN connection: Ethernet (RJ-45)
Management features
LED indicators: Y
Power
AC input voltage: 90-240 V
AC input frequency: 50/60 Hz
Storage
Storage media type: SSD
Storage drive interface: mSATA
Solid-state drive capacity: 50 GB
Performance
Certification: 47 CFR CISPR22CNS13438EN 300 386EN 55022EN61000-3-
2EN61000-3-3ICES-003 QCVN 54 TCVN 7189VCCICISPR24EN 300
386 EN301 489-1 EN301 489-17 EN301 489-24 EN301 489-4 EN301
489-7 EN55024QCVN 18 TCVN 731
Operational conditions
Operating temperature (T-T): 0 - 40 °C
Storage temperature (T-T): -20 - 70 °C
Operating relative humidity (H-H): 10 - 90 %
Storage relative humidity (H-H): 10 - 90 %
Operating altitude: 0 - 3048 m
Non-operating altitude: 0 - 4572 m
Weight & dimensions
Dimensions (WxDxH): 234 x 43 x 199 mm
Weight: 1820 g

*PLEASE NOTE: Every effort has been made to ensure the accuracy of all information contained herein. Lasystems makes no warranty expressed or implied with respect to
accuracy of the information, including price, editorials or specifications. Lasystems or its suppliers shall not be liable for incidental, consequential or special damages arising from, or
as a result of, any electronic transmission or the accuracy of the information contained herin, even if Lasystems has been advised of the possibility of such damages. Product and
manufacturer names are used only for the purpose of identification.

You might also like