Professional Documents
Culture Documents
<Name of Project>
Project No. <Project No>
=== This area is space for EPC or End-User Logo (if desired) ===
DOCUMENT TITLE:
Confidentiality Notice: This document and the information contained herein shall not be copied or used for other than the purposes for
which it is or has been provided or disclosed in any form or medium to third parties, except as expressly permitted by Yokogawa.
Doc. Title: SIS Hardware Functional Design Specification Page 2 of 105
Doc. No. <PJT Document No.> Doc. Rev. <Document Rev.>
REVISION DETAILS
Table of Contents
1 Introduction..................................................................................................................... 7
1.1 General...................................................................................................................... 7
1.2 Purpose and Scope of This Document.......................................................................7
1.3 Abbreviations and Definitions.....................................................................................8
1.3.1 Abbreviation.........................................................................................................8
1.3.2 Definitions.......................................................................................................... 10
1.4 Project Design References and Standards...............................................................12
1.4.1 Project Specifications Documents......................................................................12
1.4.2 Customer Reference Documents.......................................................................12
1.4.3 Yokogawa GES Template Documents...............................................................12
1.4.4 Other Yokogawa Documents.............................................................................12
1.4.5 Applicable Codes and Standards.......................................................................13
1.5 Order of Precedence................................................................................................14
1.5.1 Conflicting Requirements...................................................................................14
2 System Description......................................................................................................15
2.1 Plant Shutdown and Depressurizing overview..........................................................15
2.2 Safety System objective...........................................................................................15
2.3 System Overview.....................................................................................................16
2.4 Basis of Design........................................................................................................ 16
2.5 General Design Constraints.....................................................................................18
2.6 SIS Functional requirements....................................................................................18
2.7 Safety Instrumented Functions and SIL....................................................................18
2.8 System availability....................................................................................................18
2.9 General Design Requirements.................................................................................19
2.9.1 SIS Equipment and Location..............................................................................19
2.9.2 Electrical Power Supply Requirements..............................................................19
2.9.3 Electromagnetic Compatibility Requirements.....................................................20
2.9.4 Installation Environment and Power Supply Specification for ProSafe-RS.........21
2.9.5 Hardware and I/O Segregation..........................................................................22
2.9.6 Operating Plant Area Segregation.....................................................................22
2.9.7 Process Unit Segregation..................................................................................22
2.9.8 Controller Segregation.......................................................................................22
2.9.9 I/O Segregation..................................................................................................23
2.9.10 Segregation of Safety IOs and Non-Safety IOs..............................................23
1 Introduction
1.1 General
This section includes (but not limited to) details about Introduction to the Project; includes project
background, end users, consultant for the project, project location / country.
1.3.1 Abbreviation
Need to be updated as per Project requirement
Abbreviation Description
AIO Analog Input and Output
AMO Automatic Maintenance Override
ANN Annunciator
BPCS Basic Process Control System
CAMS Consolidated Alarm Management System
CCR Central Control Room
CERR Computation error
CPU Central Processing Unit
CTRL Control
DCS Distributed Control System
DINT Double Integer
DIO Digital Input and Output
DIP dual in-line package
DTS De-energise to Safe
EDP Emergency Depressurisation
EDV Emergency Depressurization Valve
ENG Engineering
EPC Engineering Procurement Construction
ESB Extended Serial Bus
ESD Emergency Shutdown System
ETS Energise to Safe
FAR Field Auxiliary Room
FAT Factory Acceptance Test
FBD Function Block Diagram
FCS Field Control Station
FDS Functional Design Specification
FER Field Equipment Room
FGS Fire & Gas System
FIFO First-in First out
FLT Fault
Abbreviation Description
FUP First-up
GES Global Engineering Standard
HART Highway Addressable Remote Transducer
HDD Hard disk drive
HIPPS High Integrity Pressure Protection System
HIS Human Interface Station
HMI Human Machin Interface
HRDY Hard-ready
ICSS Integrated Control & Safety System
IEC International Electrotechnical Commission
IER Instrument Equipment Room
IODB Input Output Data Base
IOP Input High/Low limit error occurred
IPS Instrumented Protective System
LAN Local Area Network
LCL Local
LCR Local Control Room
LED Light Emitting Diode
MAC Main Automation Contractor
MCB Main Control
MCR Main Control Room
MOS Maintenance override switch
MPU Microprocessor Unit
MTRP Manual Trip
MTTR Mean Time to Restoration
NAMUR User Association of Automation Technology in Process
Industries (Germany)
NDE Normally De-energise
OOP Output Channel Status-Open circuit/Short circuit
OOS Operational override switch
OOW Operational override warning
OPC Open Platform Communication
OVR Override
PID Proportional Integral Derivative
Abbreviation Description
POU Program organization unit
PRM Plant Resource Manager (IAMS)
PSD Plant Shutdown System
PST Partial Stroke Test
PSU Power Supply unit
RDY Ready
RST Reset
SAT Site Acceptance Test
SCS Safety control station
SCU Safety Control Unit
SENG Safety Engineering Station
SER Sequence of event Record
SIF Safety Instrumented Function
SIL Safety Integrity Level
SIS Safety Instrumented System
SOE Sequence of Event
SOER Sequence of Event Record
SRS Safety Requirement Specification
STAT Status
STBY Standby
SUO Start-up override
SVP Safety validation Plan
SYS System
TRANS Transmitter Higher/Lower limit error
TÜV Technischer Überwachungsverein
(German: Technical Monitoring Association)
UDFB User Defined Function Block
UPS Uninterruptible Power Supply
USB Universal Serial Bus
VOT Voting
Table 1-1 Abbreviations
1.3.2 Definitions
Company/Owner/End User :
Project :
2 System Description
2.1 Plant Shutdown and Depressurizing overview
Include brief description about ESD shutdown hierarchy based on Project Specifications.
The ProSafe-RS systems are used for SIS/ESD/IPS applications for the Project xxxx.
Provide Project & plant information, Indicate sub systems (by Modbus), Show MATRIX/MIMIC
panels, indicate clearly the boundaries in scope of supply
The SIS/ESD/IPS I/O and logic solvers are distributed geographically into CCR and FER/FAR/IER.
The Vnet/IP link (redundant) is used for communication between SENG PC, SIS/ESD/IPS, FGS and
DCS.
Refer to the Hardware FDS document [xxxx] for the process segregation.
Refer Reliability / Availability Calculations [!SIS FDS Software Doc No.!] for availability calculations
for SIS equipment within MAC scope of supply.
If this document is used then availability calculation in SVP shall be excluded
The SIS equipment shall not be installed directly in the field or open areas.
Each of the SIS system CPU nodes and I/O nodes receive two independent UPS power feeders via
a power distribution arrangement in the Power distribution cabinet.
Non UPS power XX VAC, XX Hz supply is used for utility sockets and lighting in cabinets.
Field power supply
For Installation Environment and Power Supply Specification for Third Party Components refer to
Buyout Hardware Specification for ProSafe-RS-Doc no XXXX for details.
Controller
Plant Unit Unit Description Domain
Name
Figure 3-1 - Safety control unit and Safety node units connected
problem occurs in Bus 1, Bus 2 will be used. If Bus 1 recovers, communication will be switch back
to Bus-1 without disturbing the network communication. Bus switching (Manual bus switching is not
supported) is performed in every path up to the communication destination.
Update as per project requirement for equipments connected, open communications,
communications in Bus-2
Diagnostic tests of output modules are performed by the firmware periodically. When one of the
following faults is detected, the Output Shutoff Switch is activated to force the output channel to
OFF (0).
Fault in the common part of an output module
Stuck-at-ON, the case where the output cannot be turned to OFF
Output current read back error (analog output module)
In case of a communication fault between an output module and a CPU module, the failsafe value
for each channel is activated.
Peer-Peer Safety Communication:
The receiver side of SCS can detect failures caused by faults in the SCSs and the relay devices on
the communication path.
When a failure in peer to peer safety communication is detected, the predefined value is transferred
to the application logic in the receiver side of SCS.
As per project specification, failures of safety communication links within the safety systems shall
bring any safety related signals to a fail-safe state.
Time out of safety communication signals configured between domain SCSs or within domain SCS
or loss of communication, shall initiate a communications failure/discrepancy alarm to notify the
operator that manual intervention, maintenance or remedial action is required.
The communication failure shall trip its respective facilities upon total loss of communication signals
with the master peer.
Loss of DCS/SIS Communication:
Logic and/or hardware shall be configured in such a way that the shutdown shall not be initiated due
to the loss of DCS- SIS/ESD/IPS communication.
Loss of Remote I/O Communication:
The console SIS/ESD/IPS push buttons and lamps located in MCB shall be wired to the LCR
system remote I/O node in MCB. The default fail safe value for I/O’s shall be specified as ‘0’ fail
safe ( or de-energized ) for remote I/O module related fault or loss of communication to controller,
which cause SIF shutdown at LCR level.
Actions on Major System Failure:
All parts of the SIS/ESD/IPS system shall maintain safe operation after any failure; in case of a
major SIS system failure (total black out or other electric failure) the system shall always go to a
predefined failsafe position. In such cases, all ProSafe-RS outputs are set to de-energized state.
Diagnostic Messages:
SCS performs self-diagnosis regularly to detect hardware and software errors. It analyses the
detected errors and system configuration to determine the error level according to the error
occurred and executes error-handling operations according to the error level.
Unused spare field cable cores shall not be wired to spare IO channels to avoid the
possibility of stray voltage pick up or earth faults.
For DPV, the following common cause failure avoidance shall be considered.
Segregation of redundant trip initiators and valves into separate cards installed in separate
racks with separate power supplies, separate cable routing for system and field cabling etc.
IO
parameter Safety Impact on
System
Failure Mode Settings in Remarks
Diagnostics Application Logic
Applicatio
n Software
‘The channel status is
reported as ‘good’.
Input channel is
turned ON.
DTS : The demand
Detect (OFF state) cannot be
Short circuit fault
short No system detected - Safety
between 24V DC
circuit-Not diagnostics impact
and input channel
configured ETS : Short circuit is
mistakenly
recognized as
demand, which may
cause a spurious trip
– Safety impact
Short circuit fault Detect Channel fault ‘The channel status is ‘Detect short
between 24V DC short notification on reported as ‘bad’. circuit’ is to be
and input channel circuit”Conf operation station if Input channel is set enabled in the
Fault igured the condition at based on ‘input Software
‘remarks’ column processing at fault’ configuration
meets definition. and SCB110 is
to be installed
DTS: The demand at field device.
(OFF state) cannot be
No redundant
detected. However,
switch over.
the diagnostics helps
to remove the cause
of the fault. Hence the
manual (operator)
IO
parameter Safety Impact on
System
Failure Mode Settings in Remarks
Diagnostics Application Logic
Applicatio
n Software
attention is required.
Failure of manual
attention may lead to
unsafe operation of
the plant.
ETS: The fault is
diagnosed for ETS for
operation action.
Hence the manual
(operator) attention is
required.
Failure of manual
attention may lead to
unsafe operation of
the plant.
Short circuit fault
Channel recover
between 24V DC Safety Interlock reset
notification on
and input channel required.
operation station
recover
‘The channel status is
reported as ‘good’.
Input channel is
turned OFF.
Input channel
disconnection Detect DTS : Spurious
Fault Disconnecti No system process trip
on-Not diagnostics ETS: The demand
configured cannot be detected –
Safety impact.
IO
parameter Safety Impact on
System
Failure Mode Settings in Remarks
Diagnostics Application Logic
Applicatio
n Software
the fault.
ETS: The demand
cannot be detected.
However, the
diagnostics helps to
remove the cause of
the fault. Hence the
manual (operator)
attention is required.
Failure of manual
attention may lead to
unsafe operation of
the plant.
Input channel Channel recover
Safety Interlock reset
disconnection notification on
required.
recover operation station
Failure alarm is If the
issued. redundant
Internal failure No safety impact
Switch over to the module is
standby. available
IO parameter
Settings in System Safety Impact on
Failure Mode Remarks
Application Diagnostics Application Logic
Software
‘‘The channel status
is reported as ‘good’.
Output channel value
depends on the
application logic.
The field device turns
ON
Short circuit
fault between Detect No system DTS: The field device
24V DC and Disconnection diagnostics on the affected
output channel -Not channel cannot be
configured shut down. - Safety
impact
ETS : Short circuit is
mistakenly
recognized as
demand, which may
cause a spurious trip
– Safety impact
IO parameter
Settings in System Safety Impact on
Failure Mode Remarks
Application Diagnostics Application Logic
Software
‘The channel status
is reported as ‘bad’.
Output channel is set
based on ‘Output
value in detecting
error’ definition.
DTS: Depending on
‘output value in
detecting error,
spurious process
shutdown can occur. ‘Detect
However, the disconnection’
diagnostics helps to is to be
Short circuit Channel fault remove the cause of enabled in the
fault between notification on the fault. Hence the Software
24V DC and Detect
operation station if manual (operator) configuration.
output channel Disconnection
the condition at attention is required.
-Configured
‘remarks’ column No redundant
ETS: Depending on
meets switch over.
‘output value in
detecting error’, the
process shutdown
demand cannot
meet. However, the
diagnostics helps to
remove the cause of
the fault. Hence the
manual (operator)
attention is required.
Failure of manual
attention may lead to
unsafe operation of
the plant.
Short circuit Detect
fault between Disconnection Output enable is to
24V DC and -Configured Channel recover be carried out at
output channel notification on SENG. Safety
recover operation station Interlock reset
required.
IO parameter
Settings in System Safety Impact on
Failure Mode Remarks
Application Diagnostics Application Logic
Software
channel shutdown.
Spurious process
shutdown
ETS: The field device
on the affected
channel cannot be
turned ON. – Safety
impact
‘The channel status
is reported as ‘good’.
Output channel is
turned OFF.
The field device turns
OFF.
‘The channel status
is reported as ‘bad’.
Output channel is set
based on ‘Output
value in detecting
error’ definition.
However, the field
device turns OFF
DTS: Spurious Detect
process trip. disconnection'
However, the is to be
Channel fault
Output channel Detect diagnostics helps to enabled in the
notification on
disconnection Disconnection remove the cause of Software
operation station if
Fault - Configured the fault. configuration.
the condition at
‘remarks’ column ETS: The process
meets shutdown demand No redundant
cannot meet. switch over.
However, the
diagnostics helps to
remove the cause of
the fault. Hence the
manual (operator)
attention is required.
Failure of manual
attention may lead to
unsafe operation of
the plant
Output channel Detect Channel recover Output enable is to
disconnection Disconnection notification on be carried out at
recover -Configured operation station SENG. Safety
Interlock reset
IO parameter
Settings in System Safety Impact on
Failure Mode Remarks
Application Diagnostics Application Logic
Software
required.
Pulse test ON
or OFF and
Output Shutoff
Channel fault switch is to be
notification on enabled in the
operation station if software
the condition at configuration.
Internal failure ‘remarks’ column No safety impact
meets.
If the
Switch over to the redundant
standby module. module is
available
IO parameter
Settings in System Safety Impact on
Failure Mode Remarks
Application Diagnostics Application Logic
Software
Open / Short IOP+/-:Not No system ‘The channel
Circuit configured diagnostics status is reported
(IOP+/-) fault as ‘good’.
Input channel
follows field
transmitter current,
which could be
‘raw value’. i.e.
0mA in case
of open circuit
23.5mA in case
of short circuit (2
wire)
0mA in case
of short circuit (4
wire)
1ooN voted
transmitter
(applicable for
SIS/ESD/IPS)
Since the input
value is in the
range of ‘off scale’,
spurious process
shutdown is
IO parameter
Settings in System Safety Impact on
Failure Mode Remarks
Application Diagnostics Application Logic
Software
expected. The
cause of the
transmitter ‘off
scale’ is not
diagnosed by
analog input
module. – Safety
Impact
2ooN voted
transmitter
(applicable for
SIS/ESD/IPS)
Since the
transmitters are in
voted, the spurious
process shutdown
is avoided due to
the validation of
inputs. The cause
of the transmitter
‘off scale’ is not
diagnosed by
analog input
module – Safety
impact
Open / Short IOP+/-:configured IOP+/- fault The channel status IOP+/- are to
Circuit notification on is reported as ‘bad’ be enabled and
(IOP+/-) fault operator station and channel value threshold
is set to “input settings for
processing at fault” these items are
pre-defined value to be specified
1oo1 voted in software
transmitter configuration
(applicable for ‘Input
SIS/ESD/IPS) processing at
fault’ value is to
For 1oo1
be pre-defined
transmitter, the
automatic MOS
(AMO) is activated No redundant
to avoid the switch over
spurious process
shutdown
The process
shutdown is
expected upon
expiry of AMO
timer.
IO parameter
Settings in System Safety Impact on
Failure Mode Remarks
Application Diagnostics Application Logic
Software
Upon AMO alarm,
the manual
(operator)
attention is
required. Failure of
manual attention
may lead to
spurious process
shutdown
2ooN voted
transmitter
(applicable for
SIS/ESD/IPS)
For 2ooN
transmitter, the
time delay
shutdown is not
applicable. Since
the transmitters
are in voted, the
spurious process
shutdown is
avoided due to the
validation of
inputs.
1oo1 voted
transmitter
Open / Short (applicable for
Circuit IOP+/- recover SIS/ESD/IPS)
(IOP+/-) IOP+/-:configured notification on The AMO is
recover operator station removed
automatically, if
fault is recovered
within AMO timer
Over / Under Trans+/-:Not No system ‘The channel No redundant
range configured diagnostics status is reported switch over.
Transmitter as ‘good’.
(TRANS+/-) Input channel
fault follows field
transmitter current,
which could be ‘off
scale’. i.e.
<4mA in case
under range
>20mA in case
of short circuit
IO parameter
Settings in System Safety Impact on
Failure Mode Remarks
Application Diagnostics Application Logic
Software
DTS: The field
device on the
affected channel
shutdown.
Spurious process
shutdown
1oo1 voted
transmitter
Refer scenario of
‘Open / Short
Circuit (IOP+/-)
fault’
2ooN voted
transmitter
Refer scenario of
‘Open / Short
Circuit (IOP+/-)
fault’
Over / Under Trans+/-:Configure TRANS+/- are
Refer scenario of
range d to be enabled
TRANS+/- fault ‘Open / Short
Transmitter and threshold
notification on Circuit (IOP+/-)
(TRANS+/-) settings for
operator station fault’
fault these items are
to be specified
in software
configuration
Over / Under ‘Input
range Refer scenario of processing at
Transmitter TRANS+/- recover
Trans+/-:Configure ‘Open / Short fault’ value is to
(TRANS+/-) notification on
d Circuit (IOP+/-) be pre-defined
recover operator station
recover’
No redundant
switch over.
Switch over to
Internal failure the standby if
Failure alarm is
No safety impact redundant
issued.
module is
available
IO parameter
Settings in System Safety Impact on
Failure Mode Remarks
Application Diagnostics Application Logic
Software
Detect short ‘The channel status is
circuit-Not reported as ‘good’.
configured Output channel value
depends on the
application logic.
The field device is
Output channel 0mA
No system
short circuit
diagnostics DTS: The field device
fault
on the affected
channel shuts down
ETS: The field device
on the affected
channel cannot be
shuts down – Safety
impact
Output channel Detect short Channel fault ‘The channel status is “Detect short
short circuit circuit- notification on reported as ‘bad’. circuit” is to
fault Configured operation station if Output channel is set be enabled in
the condition at based on ‘Output the Software
‘remarks’ column value at fault’ configuration.
meets definition.
DTS: Depending on No redundant
‘output value at fault’, switch over.
spurious process
shutdown can occur.
However, the
diagnostics helps to
remove the cause of
the fault. Hence the
manual (operator)
attention is required.
ETS: Depending on
‘output value at fault,
the process shutdown
demand cannot meet.
However, the
diagnostics helps to
remove the cause of
the fault. Hence the
manual (operator)
attention is required.
Failure of manual
attention may lead to
unsafe operation of
IO parameter
Settings in System Safety Impact on
Failure Mode Remarks
Application Diagnostics Application Logic
Software
the plant.
Output channel Detect short
short circuit circuit- Channel recover
Output enable is to be
recover Configured notification on
carried out at SENG.
operation station
Output
Shutoff switch
Channel fault is to be
Internal failure enabled in
notification on
e.g. mismatch operation station if the software
between the the condition at configuration.
commanded ‘remarks’ column No safety impact
value and meets.
readback value If the
Switch over to the redundant
standby module module is
available
Safety Impact on
Failure Mode System Diagnostics Remarks
Application Logic
CPU fail / recover
Standby CPU
notification on operation No safety impact
fail / recover
station
CPU fail / recover
Active CPU fail /
notification on operation No safety impact Note:1
recovery
station
Notes:
1. Standby CPU takes over control right and recovered active CPU acts as standby CPU
3.3.2.2 CPU Module Failure (Total)
Safety Impact on
Failure Mode System Diagnostics Remarks
Application Logic
System Shutdown
Plant shutdown condition
Loss of controller data to
Operator/ HIS /SENG
Temporary loss of SOE
data
Safety communication
Active CPU and CPU fail notification failure
Standby CPU fail on operation station Remote I/O
communication failure
Spurious trip for De-energized
to Safe (DTS) system design
(SIS/ESD/IPS)
Unavailability for Energized to
Safe (ETS) system design –
Safety impact.
Resumption of safety
control station using
initial configured preset
Active CPU and CPU recover values.
Standby CPU notification on Resumption of SOE/HIS
recover operation station data update
Output enable is
required for each SCS
Safety Impact on
Failure Mode System Diagnostics Remarks
Application Logic
PSU fail / recover
Left PSU fail /
notification on operation No safety impact
recover
station
PSU fail / recover
Right PSU fail /
notification on operation No safety impact
recover
station
Both Left PSU
Refer scenario Active CPU
and Right PSU Refer scenario 3.3.2.2
and Standby CPU fail
fail
Both Left PSU
Refer scenario Active CPU
and Right PSU Refer scenario 3.3.2.2
and Standby CPU recover
recover
A diagnostic information message indicating “Diagnostic Error” will be sent from each
receiving station where a communication error has occurred.
Stop mode
Loading mode
Initial mode
Waiting mode
Running mode
3.4.3.1 Operating Mode of SCS
An overview of the operating modes is provided below.
The operating mode indicates the overall operating status of SCS, not the status of each
output module.
The operating mode indicates the status of a single SCS, regardless of whether the
configuration of CPU of SCS is single or dual-redundant.
If CPU of SCS is dual-redundant, the operating mode does not shift even if the control right
of CPU is switched.
Waiting Mode (Waiting for Output Enable Request): Application logic is periodically executed
on each scan time. However, if the status of any output channel is faulty, the result of the
application logic shall not be reflected in physical output, and the status of the faulty output
channel is set to “Output Disable”.
If the “Output enable operation” is executed just after starting up the SCS, the SCS also
enables the output of inter-SCS safety communication, SCS Link Transmission and
subsystem communication. The Waiting mode status can be checked in the SCS State
Management Window on the SENG and the LED display of the CPU module.
Running Mode (Controlling Status): This mode indicates that the SCS is running normally.
All output channels of safety output modules are normal and physically transferring the
output values from the application logic. The Running mode status can be checked in the
SCS State Management Window on the SENG and LED display of the CPU module.
Output Status Monitoring: All output channels of safety output modules are monitored. If any
of the channels becomes “Output Disable” status due to a failure in the corresponding
module or in the output channel itself, or after adding new channels during online
modification, the SCS shall change its operating mode to the Waiting mode. The operating
mode changes to the Running mode when the cause of the channel failure is removed, the
output enable operation is completed and all output channels are placed in the Output
Enable status.
In general, online modifications may be carried out at SENG located at Engineering Room. It is
expected that the actual on-line download to SCS is to be carried out using SENG located at FAR
physically after enabling ‘Configuration Enable Switch’ at SCS cabinet.
The Analogue Input (SAI143-H) and Analogue output (SAI533-H) modules are in-built with HART
communication function. One HART device is connectable for each channel. Each channel is
equipped with a power supply function to the HART device.
“Smart” transmitters (HART) must be configured to “read only”. Some means of security or special
procedural instruction must be provided to assure that these transmitters are not electronically
reconfigured during testing, without proper authorization.
Partial Stroking Test:
In this project, for partial stroke testing, the SIS valve shall be provided with smart positioner with
HART protocol wired to SIS analog output card (HART pass through type). The SIS valve will be
provided with solenoid valve connected to SIS system for trip.
To avoid spurious trips, 4mA is set as full open and 20mA is set as full closed for fail close valves.
PST shall be initiated manually at required testing intervals from IAMS. Once PST command is
initiated at IAMS, HART signal will be sent through SIS analogue output module to valve positioner
to partially stroke the valve. The positive feedback signals and valve signature data from positioner
will be sent to PST software in IAMS via the SIS analogue out connection using HART protocol. The
PST software analyses the stroke testing and will notify the IAMS and HMI Operator.
A trip condition will override the PST and will force the valve to its fail safe position.
If valve position is used for trip action, then limit switch or position transmitter (with required SIL
rating) shall be used, this shall be hardwired to SIS system, to avoid spurious trip.
For automated partial stroke testing, application logic in the SIS will need to be programmed
considering partial closing of the valve (e.g. up to 20% valve stroking) based on feedback signal.
The valve stroking limit is specified in IAMS and partial stroking function is invisible to SIS
application logic.
Depending on smart positioner design, the failure of SIS analog output may cause the SIS valve to
fail safe position. Refer IAMS FDS – [!IAMS FDS Doc. No.!] for PST details.
Refer SIS FDS - Software [!SIS FDS Software Doc No.!] for SIS system configuration related to
PST.
Diagnostic alarms,
Event information is stored in the SOE event information storage memory of an SCS. There are two
types of files in which event information can be stored; an even log file and trip signal files. An even
log file stores the latest event information. In the trip signal file, events before and after each trip
signal are saved.
SCS creates only one event Log file. SCS always stores the latest information in the event log file.
SCS event log file can store up to a maximum of 15000 Events. If the number of events exceeds
maximum events, the older events are deleted and overwritten by new events based on ‘first in first
out’ (FIFO) sequence.
SCS creates a trip file if a trip event is detected. SCS creates only 2 trip file if more than one trip
event is detected. Each trip signal file stores 1500 events in total; the last 500 events generated
before trip event occurred and 1000 events generated after trip event occurred. The trip signal file
includes the trip Event.
Safety OPC Server collects the Sequence of Events (time stamped in safety system) from SCS via
Vnet/. The Safety SOE OPC Server buffers (log) the Sequence of Event locally and passes them to
the OPC Client ALMS.
The data value received from the producing side is output from the function block on the
consuming side. However, the UZ application logic needs logic reset function for SIF
shutdown recovery.
The communication status (parameter NR) becomes normal (TRUE).
A diagnostic information message notifying about the recovery is output.
SIS switch cabinet and DPV Switch cabinet shall be considered in each group within each HMI
operator console, for the hardware activation push buttons switches and lamps. The SIS hardwired
console located as a part of operator console consists of:
SIS shutdown switches
Depressurising valve switches
SIS MOS enable key switch
SIS SOS switches
Status Lamp indicators
SIS Switches:
The SIS switches shall be of a different shape/type (mushroom type, pressing type, protective
cover, etc.) and different colors according to Emergency levels. SIS switches shall require double
action (e.g. two separate mechanical movements). Switches shall be equipped with protective
covers to avoid spurious action and with internal lamps.
MOS Enable Key Switch:
The MOS Enable is the key switch on the SIS switch cabinet. A separate MOS confirm indication
lamp (Yellow) on the SIS switch cabinet shall be derived from the DO of the SIS system only. This
is to ensure that the MOS Enable Key switch is activated and the SIS Logic solver has received the
MOS Enable command and the actual feedbacks of MOS confirm lamp is derived from the SIS
logic.
Lamp test facility, colour engraved nameplates and plug-in terminal boards for external wiring shall
be provided.
Remote I/O:
The SIS switches (push buttons), MOS, SOS switch status and lamp located in CCR console are
hardwired to Remote I/O nodes located in CCR Equipment Room, segregated per FAR/SIS
controller. The FAR SIS controller is directly connected to Remote I/O over fiber optic.
Separate Remote I/O nodes in MCB shall be provided per SIS controller group in FAR. The
SIS push-buttons and lights indicators are powered by the SIS.
The SIS switches are line monitored. Refer section discrete input line monitoring in this FDS.
Item Specifications
Model SSC60D
Voltage & Frequency 100 ~ 120 VAC & 60 Hz
CPU Unit SCP461 Redundant
Power Supply Units SPW481 Redundant (100 to 120 V AC Power Supply)
ESB Modules SEC401 Redundant
Power Consumption of Unit 200 VA
Mounting type 19” Rack
Table 4-11: Safety Control Unit Specification
Figure 4-27 - Connector Unit for ESB Bus and Connector Unit with Terminator for ESB Bus
response time. CONTRACTOR shall specify the list of process trip switches require this function
along with filter timing.
The surge protection for input switches shall be implemented using surge protection device. For IS
discrete signals, the external barrier (isolator) shall be considered. IS isolators shall be evaluated for
SIL rating to meet the SIF SIL design target. The IS Isolators are mounted on termination board
(mother board).
Refer ICSS Buyout Hardware Specification [!ICSS Buyout Doc. No.!] for details about SPD, Isolator
specification and its SIL rating.
Item Specifications
Model SDV144
Number of input channels 16-channel, module isolation
No-voltage contact
Input signal
ON: 1 kΩ maximum, OFF: 100 kΩ minimum
6 mA ± 20 %,
Input current
(External power supply, 24 V DC at 0 Ω input)
External power supply 24 V DC ± 20 % / -10%
Install for individual channels at the field device end:
Field wiring diagnostics
SCB100: for defective open circuit detection while accepting
OFF signals
SIL support SIL3 capable
Redundancy Can be configured dual redundant for increased availability
Electronic current limit 6mA/channel
Coating G3
Table 4-16: SDV144 Specification
/switchboards or VSDS shall be hardwired via interposing relays located in substation. The relays
shall be driven from 24Vdc signals powered from the SIS system. A contact of this relay shall be
wired into the motor switchgear.
For interface with package control system PLCs, the trip signals from SIS to PLC shall be hardwired
via interposing relays located in PLC cabinet. The relay shall be driven from 24Vdc signal powered
from the SIS system.
Console LED/lamp shall be connected to redundant DO card channel from the MCB Equipment
room SIS system remote nodes (of the respective FAR SIS controllers)
The CONTRACTOR shall consider the following electrical interface requirements for selection of
SIS Output.
For 8 channel DO card (SDV531L, 0.6/channel), the load (SOV) specification shall be in the
range of 40Ω (OFF state) to 685Ω (ON state).
For 16 channel DO card (SDV541, 0.2/channel), the load (lamp or relay) specification shall
be in the range of 120 Ω (OFF state) to 685Ω (ON state).
The OFF state represents the DO in de-energized state and ON state represents the DO in
energized state.
The field cable sizing and selection shall be in line with the working voltage and minimum
operating voltage of the selected field devices. CONTRACTOR shall consider cable voltage
drop in field cable sizing calculations.
Total value of the capacitance of the ‘field devices’ and their ‘field cable wiring’ shall be
limited to < 0.1uF for Normally De-energized outputs (Solenoids) which require line
monitoring. CONTRACTOR shall select cables considering the total capacitance
requirement for the field device and the field cable run.
For IS circuits, the ENTITY parameters (resistance, inductance, capacitance) as specified in
IS barrier and Ex-i field device certificates should be considered.
If an SIS system has few interposing relay interfacing requirement or few lamp outputs and existing
SDV531L has sufficient spare outputs (excluding project spare requirement), then these outputs
shall be combined with SDV531L as part of I/O card optimization.
Item Specifications
Model SDV 531-L
Number of input channels 8-channel, module isolation
Output voltage 24V DC, (Output voltage drop: 1 V maximum)
Maximum load current 0.6 A/output line (4.8 A in total output of all the channels)
External power supply 24 V DC + 20 % / -10 %
Maximum leak current at 1.6 mA
output off status
Output format Current source
Minimum load current 35 mA
Load resistance range 40 to 685 Ω (Resistance value of the load for both ON and OFF
state, including the field wiring resistance.)
SIL support SIL3 capable
Redundancy Can be configured dual redundant for increased availability
Electronic current limit 0.63A/channel (short circuit limit)
Coating G3
Table 4-17: SDV531L Specifications
Item Specifications
Refer ICSS Buyout Hardware Specification [!ICSS Buyout Doc. No.!], for project specific
Workstation and Server specification.
will include the row number. Cable overall screens will be terminated on ground terminal block
mounted on insulated DIN Rail which will be connected to Instrument Earth bar. A PVC cable duct
adjacent to the terminal row serves to run the cable inside the cabinet.
Where practicable a dedicated marshalling cabinets will be provided for IS and Non-IS signals.
Where the IO count does not justify dedicated cabinets, IS and Non-IS will be assigned to front and
rear of the cabinet respectively. IS signals wiring duct and terminals will be blue in colour. The
termination board for IS signals will include IS modules.
Depending on the heat dissipation requirement, fans will be provided on the roof of the cabinet to
circulate air inside the cabinet to ensure cabinet temperature is within the specified limit of the
components in the cabinet.
ELCO boards will be used for interconnection between SIS Switch cabinet and marshalling cabinet.
All interconnect wiring between marshalling cabinets will be using multi-core cabling by
CONTRACTOR.
RTD (where applicable) will be provided in the cabinet for cabinet temperature. An earth leakage
relay is provided in marshalling cabinets for redundant 24V DC power supply for earth fault
detection and alarm.
Each marshalling cabinet will have earthing bars in the front and rear for the following grounding
requirement.
Safety Earth bar non-isolated
Instrument Earth bar isolated
DI and DO Marshalling cabinets will be provided with two incoming double pole MCBs of
appropriate rating for UPS incoming power supply.
Surge arrestors where provided will be installed in place of terminals.
For more details on Marshalling Cabinet refer to following documents:
Refer ICSS Buyout Hardware Specification [!ICSS Buyout Doc. No.!], for cabinet specification
details
Refer ICSS Marshalling Cabinet Typical layout Drawing [XXXX] for details about system cabinet GA
& wiring.
The power supply to the input and output circuits shall be floating (non-earthed). Hardware shall be
provided which automatically checks and alarms if the supply is not floating due to a fault in the
system. These alarms shall be included in the common cabinet utility alarm.
Refer ICSS Buyout Hardware Specification [!ICSS Buyout Doc. No.!], for field power supply
specification details.
4.5 Grounding
Need to be updated as per project requirements.
Safety Control Units and Safety Node Units:
To protect from external noises, the safety control units and the safety node units must be
grounded. Grounding is to be connected to an independent earth of resistance up to 100 ohm using
a grounding cable with minimum nominal conductor cross-sectional area of 2.0 mm2.
The safety control units, safety nodes and Node power supply modules shall be connected to
‘Reference Earth’ in cabinet
SIS System Cabinets:
To avoid shock hazards and minimize the effects of external noise, the ProSafe-RS system must be
grounded with a ground resistance of 100 ohms or less through a grounding bus of 22 mm2 or
thicker. When multiple ProSafe-RS cabinets are installed in the same room, the ground cables of
those cabinets may be connected to one ground bus inlet as illustrated below. A ground cable of at
least 5.5 mm2 should be used to connect each cabinet and the inlet.
Suitable SIL rated signal splitter shall be used to meet the design SIF SIL requirement. All splitters
selected for use in the Project are rated for minimum SIL2 applications.
Refer ICSS Buyout Hardware Specification [!ICSS Buyout Doc. No.!], for Splitter details along with
SIL capability information.
5 System Security
5.1 Necessity for Security
Along with the recent advancement in network and information technologies, latest control systems
have adopted open technologies used in information systems, such as OS and communication
protocols. It is an accelerating factor for establishing close connections between information
systems and production control systems.
On the other hand, in this kind of open environment, production control systems are targeted by
malicious attackers represented by computer viruses and others that cause hazardous incidents.
Nowadays, security threats aimed at control systems are increasing by malwares (i.e. worms,
viruses, Trojan horse, etc.) and appearance of Advanced Persistent Threats (APT) (i.e. targeted
attacks).
In order to operate industrial plants and factories in safe and stable conditions, it is inevitable to
protect the plants’ production equipment.
6 Appendices
6.1 3rd Party Material Selection – Compliance Check Sheets
Based on Project requirement, the applicable 3rd party material selection cheek sheets to be
attached.
The document number for the attachments are intentionally considered as Hardware FDS template
number. The cover sheet of the attachment to be deleted and it can be included in this same
document as appendixes. The following items are listed for references:
A1.1.1.1
Author 1 Reviewers
R4.00.00 09/14/16 (see 1 (see Y. Yamada Initial release
below) below)