Index: 14.12.20 21.01.2021
1. Manufacturer 1
Operating Schedule,
7. 24, 365 Noted 1
Hrs/Day
Fluid Data
Revision A 0
Index: 14.12.20 21.01.2021
Design Data
Material
34. Wedge material same material as for valve body Confirm as EN-GJS-400-15 1
EN 1.4462 (ASTM A182 F51) or
35. Stem material Confirm as F51 1, 3
equivalent
2 Lining of valve body shall be extended to cover raised face of the valve flanges.
3 For detailed information see doc. 90-U-DM39-010 - Specification for Main Valves.
4 Vendor to confirm that materials of all wetted parts are suitable for the given water quality data.
5 Flanges which are not covered in EN 1092 shall be designed in accordance with EN 1591 – 1.
For metallic seated gate valve, flushing valves shall be considered to remove the collected solids in the
6 groove at bottom of the valve body to ensure tightness of the valve. It is acceptable to use resilient seated
gate valve also for larger size (above 24”).