CT TEST REPORT

DATE 05-Aug-22 PAGE 1

AMBIENT TEMP. JOB #

SUBSTATION GI TBROK HUMIDITY % ASSET ID

POSITION CT BUS B TEST STATUS

EQUIPMENT LOCATION FASA R

CT: CT1 Core1 NAMEPLATE DATA

MANUFACTURER TRENCH SERIAL NO. 1801241 IN SERVICE TAP

ASSET ID IOSK 170 ACCURACY CLASS SATURATION STD ANSI 45


PHASE 1S1 - 1S2. 1S1 - 1S3 BURDEN VA

Ratio Knee Phase Resist.


Tap Dev. Polarity (Ohms)
Nameplate Measured % Error Test V (V) Test I (A) Prim V (V) Volt.(V) Cur.(A)

X1-X2 2000:1 2002.91:1 0.146 149.43 0.0051 0.0746 343.22 0.0096 359°58' Correct 4.796

X1-X3 4000:1 4005.57:1 0.139 298.85 0.0025 0.0746 686.56 0.0048 359°58' Correct 10.739

X1-X2
X1-X3

TEST EQUIPMENT USED: 201710050027 TESTED BY: