DISTANCE PROTECTION

INGEPAC EF-ZT
User Manual
UME_INGEPAC_ZT_eng Rev. I (11/19)

© All rights reserved. No part of this publication


may be reproduced, by whatever means, without
the prior written permission of Ingeteam
Technology.

Ingeteam Power Technology reserves the right to


make changes without prior notice.
INDEX 

1. GENERAL DESCRIPTION .......................................................................................................................... 11


1.1 FUNCTIONAL DESCRIPTION .................................................................................................................................... 11
1.2 MODEL ENCODING ................................................................................................................................................ 13
1.3 USER INTERFACE .................................................................................................................................................... 16
1.4 INTERCONNECTIONS .............................................................................................................................................. 16
1.4.1 CPU ...................................................................................................................................................................... 16
1.4.2 Power supply ....................................................................................................................................................... 17
1.4.3 Input/output cards .............................................................................................................................................. 17
1.4.4 Analogue inputs .................................................................................................................................................. 20
2. HARDWARE...................................................................................................................................... 26
2.1 CONSTRUCTION FEATURES .................................................................................................................................... 26
2.1.1 Half chassis (½ 19”) ............................................................................................................................................. 26
2.1.2 19” chassis ........................................................................................................................................................... 27
2.2 REAR TERMINALS................................................................................................................................................... 27
2.2.1 Configuration options ......................................................................................................................................... 27
2.2.2 Half chassis (½ 19”) ............................................................................................................................................. 27
2.2.3 19” chassis ........................................................................................................................................................... 28
2.2.1 Closed Terminals ................................................................................................................................................. 29
2.2.2 Wire section ........................................................................................................................................................ 29
2.3 FRONT INTERFACE ................................................................................................................................................. 30
2.3.1 Half chassis (½ 19”) ............................................................................................................................................. 30
2.3.2 19” chassis ........................................................................................................................................................... 30
2.4 TECHNICAL CHARACTERISTICS ............................................................................................................................... 31
2.4.1 Power supply voltage .......................................................................................................................................... 31
2.4.2 Digital outputs ..................................................................................................................................................... 32
2.4.3 Digital inputs ....................................................................................................................................................... 33
2.4.4 IRIG-B input and PPS ........................................................................................................................................... 33
2.4.5 Analogue ouputs ................................................................................................................................................. 34
2.4.6 RTD Inputs ........................................................................................................................................................... 34
2.4.7 Current and voltage circuits ................................................................................................................................ 34
2.4.8 Front communication .......................................................................................................................................... 36
2.4.9 Rear communications ......................................................................................................................................... 36
2.5 ENVIRONMENTAL CONDITIONS ............................................................................................................................. 39
2.5.1 Tropicalized ......................................................................................................................................................... 39
2.6 TESTS ..................................................................................................................................................................... 39
2.6.1 Climatic test ........................................................................................................................................................ 39
2.6.2 Insulation and electrical safety tests ................................................................................................................... 39
2.6.3 Mechanical tests ................................................................................................................................................. 39
2.6.4 Electromagnetic tests.......................................................................................................................................... 40
3. PROTECTION FUNCTIONS ................................................................................................................. 41
3.1 DISTANCE UNITS (21) ............................................................................................................................................. 41
3.1.1 Mho ..................................................................................................................................................................... 48
3.1.2 Quadrilateral ....................................................................................................................................................... 51
3.1.3 Timing Type for Tripping ..................................................................................................................................... 55
3.1.4 Zone 1 Extension ................................................................................................................................................. 58
3.1.5 High Speed zone .................................................................................................................................................. 59
3.1.6 Phase selector ..................................................................................................................................................... 63
3.1.7 Fault detection .................................................................................................................................................... 66
3.1.8 Mho and Quadrilateral Unit Supervision ............................................................................................................ 67
3.1.9 Capacitive Voltage Transformer (CVT) Lines ....................................................................................................... 77
3.2 SIGNALS AND COMMANDS .................................................................................................................................... 79
3.2.1 Signals ................................................................................................................................................................. 79

Ingeteam Power Technology S.A.


User Manual III
INDEX 

3.2.2 Commands .......................................................................................................................................................... 81


3.3 CURRENT UNITS ..................................................................................................................................................... 83
3.3.1 General overcurrent description ......................................................................................................................... 83
3.3.2 Directional characteristics ................................................................................................................................... 87
3.3.3 Polarization memory monitoring ...................................................................................................................... 103
3.3.4 Series compensation ......................................................................................................................................... 106
3.3.5 Phase overcurrent ............................................................................................................................................. 107
3.3.6 Neutral overcurrent .......................................................................................................................................... 108
3.3.7 Grounding overcurrent ..................................................................................................................................... 109
3.3.8 Unbalanced overcurrent ................................................................................................................................... 110
3.3.9 2nd harmonic restraint ..................................................................................................................................... 111
3.3.10 Broken conductor............................................................................................................................................ 114
3.3.11 Thermal image ................................................................................................................................................ 116
3.3.12 Undercurrent .................................................................................................................................................. 121
3.3.13 Stub bus .......................................................................................................................................................... 122
3.4 VOLTAGE UNITS ................................................................................................................................................... 126
3.4.1 General description ........................................................................................................................................... 126
3.4.2 Phase overvoltage ............................................................................................................................................. 128
3.4.3 Zero sequence overvoltage ............................................................................................................................... 130
3.4.4 Negative sequence overvoltage ........................................................................................................................ 131
3.4.5 Phase undervoltage........................................................................................................................................... 132
3.4.6 Minimum voltage .............................................................................................................................................. 134
3.5 FREQUENCY UNITS............................................................................................................................................... 135
3.5.1 Frequency.......................................................................................................................................................... 135
3.5.2 Frequency rate of change ................................................................................................................................. 138
3.6 POWER UNITS ...................................................................................................................................................... 141
3.6.1 General .............................................................................................................................................................. 141
3.6.2 Minimum real power ........................................................................................................................................ 142
3.6.3 Maximum real power ........................................................................................................................................ 143
3.6.4 Real power inversion......................................................................................................................................... 143
3.6.5 Reactive power inversion .................................................................................................................................. 143
3.6.6 Minimum apparent power ................................................................................................................................ 144
3.6.7 Maximum apparent power ............................................................................................................................... 144
3.7 LOAD ENCROACHMENT ....................................................................................................................................... 145
3.8 FUSE FAILURE ...................................................................................................................................................... 146
3.9 POWER SWING .................................................................................................................................................... 148
3.10 SWITCH ONTO FAULT......................................................................................................................................... 153
3.11 BREAKER FAILURE .............................................................................................................................................. 157
3.11.1 Single pole breaker Failure .............................................................................................................................. 157
3.11.2 Breaker failure with low load .......................................................................................................................... 161
3.12 TRIP LOGICS ....................................................................................................................................................... 165
3.12.1 67NQ Teleprotection Schemes ....................................................................................................................... 165
3.12.2 Z Teleprotection Schemes ............................................................................................................................... 180
3.12.3 Direct trip ........................................................................................................................................................ 204
3.12.4 External trip ..................................................................................................................................................... 206
3.12.5 Teleprotection serial communication ............................................................................................................. 207
3.12.6 Trip logic .......................................................................................................................................................... 208
3.13 CT SUPERVISION ................................................................................................................................................ 211
3.14 VT SUPERVISION ................................................................................................................................................ 212
4. BREAKER ........................................................................................................................................ 213
4.1 BREAKER LOGICS ................................................................................................................................................. 213
4.1.1 Breaker status ................................................................................................................................................... 213
4.1.2 Breaker failure and operating logic ................................................................................................................... 217

Ingeteam Power Technology S.A.


User Manual IV
INDEX 

4.1.3 Locking logic ...................................................................................................................................................... 218


4.1.4 Open pole detector ........................................................................................................................................... 220
4.1.5 Pole discordance ............................................................................................................................................... 224
4.2 BREAKER OPERATION SUPERVISION .................................................................................................................... 226
4.3 TRIP AND CLOSE CIRCUITS SUPERVISION ............................................................................................................. 230
5. DISCONNECTOR.............................................................................................................................. 233
6. AUTOMATISMS .............................................................................................................................. 235
6.1 SYNCHRONISM .................................................................................................................................................... 235
6.1.1 Undervoltage permission .................................................................................................................................. 241
6.1.2 Synchronism permission ................................................................................................................................... 241
6.1.3 Two breakers application .................................................................................................................................. 242
6.1.4 Application auxiliary voltage ............................................................................................................................. 244
6.2 RECLOSER ............................................................................................................................................................ 246
6.2.1 Settings, signals and commands ....................................................................................................................... 246
6.2.2 General operation ............................................................................................................................................. 253
6.2.3 Post-trip reclosure permission mask................................................................................................................. 256
6.2.4 Fault type selection ........................................................................................................................................... 260
6.2.5 Breaker open timeout ....................................................................................................................................... 260
6.2.6 Number of reclosures available ........................................................................................................................ 260
6.2.7 Reference voltage monitoring .......................................................................................................................... 261
6.2.8 Re-initiation of reclosure time .......................................................................................................................... 262
6.2.9 Pausing of reclosure time .................................................................................................................................. 262
6.2.10 Incomplete sequence block ............................................................................................................................ 263
6.2.11 Synchronism monitoring ................................................................................................................................. 263
6.2.12 Closure block by trip circuit monitoring .......................................................................................................... 263
6.2.13 52 closure timeout .......................................................................................................................................... 263
6.2.14 Recloser statuses............................................................................................................................................. 264
6.2.15 Application with two breakers ........................................................................................................................ 273
6.3 FREQUENCY RECLOSER ........................................................................................................................................ 277
7. BREAKER AND A HALF CONFIGURATION ......................................................................................... 283
7.1 PROTECTION FUNCTIONS .................................................................................................................................... 283
7.1.1 Distance functions ............................................................................................................................................. 285
7.1.2 General protection functions ............................................................................................................................ 286
7.1.3 Breaker .............................................................................................................................................................. 286
7.1.4 Breaker and a half supervision .......................................................................................................................... 287
8. FAULT LOCATOR ............................................................................................................................. 289
8.1 LOCATOR OPERATION ......................................................................................................................................... 291
8.1.1 Fault detection .................................................................................................................................................. 291
8.1.2 Pre-fault and post-fault filtering ....................................................................................................................... 291
8.1.3 Determination of the fault type ........................................................................................................................ 291
8.1.4 Distance calculation .......................................................................................................................................... 292
8.2 PRESENTATION OF THE RESULTS ......................................................................................................................... 292
8.3 CONFIGURATION EXAMPLE ................................................................................................................................. 293
9. MONITORING ................................................................................................................................. 295
9.1 EXTERNAL POWER SUPPLY MONITORING ............................................................................................................ 295
9.2 TEMPERATURE MONITORING .............................................................................................................................. 296
9.3 DIS BLOCKING BY LACK OF VAUX ......................................................................................................................... 297
9.4 INTERNAL BATTERY FAILURE MONITORING ......................................................................................................... 297
9.5 UNIT CHECKS ....................................................................................................................................................... 298
10. CONFIGURATION ............................................................................................................................ 301

Ingeteam Power Technology S.A.


User Manual V
INDEX 

10.1 CID ..................................................................................................................................................................... 301


10.1.1 Data Storage.................................................................................................................................................... 301
10.1.2 Updating CID ................................................................................................................................................... 301
10.2 GENERAL ............................................................................................................................................................ 301
10.3 FRECUENCY, MEASUREMENT AND TRANSFORMERS .......................................................................................... 303
10.3.1 Current ............................................................................................................................................................ 303
10.3.2 Frequency and voltage .................................................................................................................................... 304
10.3.3 Power and energy ........................................................................................................................................... 304
10.4 INPUTS/OUTPUTS .............................................................................................................................................. 305
10.4.1 Inputs .............................................................................................................................................................. 305
10.4.2 Outputs ........................................................................................................................................................... 306
10.4.3 Treatment of digital input flicker .................................................................................................................... 307
10.5 LEDS ................................................................................................................................................................... 307
10.5.1 Via GEN/IHMI node ......................................................................................................................................... 307
10.5.2 Via CTRL/IHMI node ........................................................................................................................................ 308
10.6 CONFIGURATION WITH INREF............................................................................................................................ 308
10.7 GENERIC COMMAND ......................................................................................................................................... 309
10.8 NAMES............................................................................................................................................................... 309
10.9 IPRV NODES CONFIGURATION ........................................................................................................................... 310
10.9.1 General IPRV settings ...................................................................................................................................... 310
10.9.2 IEC 61850 clients IPRV settings ....................................................................................................................... 311
10.10 Measurement’s range automatic configuration ............................................................................................... 311
11. SYNCHRONIZATION ........................................................................................................................ 313
11.1 GENERAL SETTINGS ............................................................................................................................................ 313
11.2 IEEE 1588v2 ....................................................................................................................................................... 315
11.2.1 Settings............................................................................................................................................................ 315
11.3 IRIG-B ................................................................................................................................................................ 315
11.4 SNTP .................................................................................................................................................................. 315
11.4.1 Settings............................................................................................................................................................ 316
11.5 QUALITY FLAGS IEC 61850.................................................................................................................................. 319
12. DATA ACQUISITION FUNCTIONS ..................................................................................................... 320
12.1 STATUS REPORT ................................................................................................................................................. 320
12.2 PRIMARY MEASUREMENTS REPORT .................................................................................................................. 323
12.3 FAULT REPORT ................................................................................................................................................... 324
12.4 INCIDENT REPORT .............................................................................................................................................. 326
12.5 HISTORICAL MEASUREMENT REPORT ................................................................................................................ 327
12.6 STATISTICAL DATA REPORT ................................................................................................................................ 329
12.7 MAXIMETER/MINIMETER REPORT ..................................................................................................................... 330
12.8 OSCILLOGRAPHY ................................................................................................................................................ 331
13. USB ACCESS.................................................................................................................................... 335
13.1 DOWNLOADING REPORTS ................................................................................................................................. 335
13.2 LOADING CID ..................................................................................................................................................... 336
13.3 LOADING FIREWALL CONFIGURATION ............................................................................................................... 336
13.4 FIRMWARE UPDATE ........................................................................................................................................... 336
13.5 USB ENABLING ................................................................................................................................................... 337
14. FTP ACCESS .................................................................................................................................... 338
14.1 ACCESS CONTROL .............................................................................................................................................. 339
15. MAPPING THE UNIT’S SIGNALS, MEASUREMENTS AND METERS ...................................................... 340
15.1 SIGNALS ............................................................................................................................................................. 340
15.1.1 Type A signals .................................................................................................................................................. 340

Ingeteam Power Technology S.A.


User Manual VI
INDEX 

15.1.2 Type B signals .................................................................................................................................................. 341


15.1.3 Type C signals .................................................................................................................................................. 342
15.1.4 Type D signals .................................................................................................................................................. 343
15.2 MEASUREMENTS ............................................................................................................................................... 344
15.3 COUNTERS ......................................................................................................................................................... 346
16. LOGICS ........................................................................................................................................... 347
16.1 CONTROL LOGICS ............................................................................................................................................... 347
16.2 PROTECTION LOGICS .......................................................................................................................................... 348
16.3 DATABASE SIGNALS ........................................................................................................................................... 349
16.4 output data upon power-up .............................................................................................................................. 349
17. IEC 61850 COMMANDS.............................................................................................................. 352
17.1 RUNNING IEC 61850 COMMANDS ............................................................................................................. 352
17.1.1 DIRECT_WITH_NORMAL_SECURITY (1) .......................................................................................................... 355
17.1.2 SBO_WITH_NORMAL_SECURITY (2) ............................................................................................................... 355
17.1.3 DIRECT_WITH_ENHANCED_SECURITY (3) ....................................................................................................... 356
17.1.4 SBO_WITH_ENHANCED_SECURITY (4) ............................................................................................................ 356
17.2 COMMAND BLOCKS .................................................................................................................................... 358
17.2.1 Command blocks by inconsistent parameters ........................................................................................ 358
17.2.2 Command blocks by switching hierarchy ................................................................................................ 358
17.2.3 Command 1 of n blocks.............................................................................................................................. 363
17.2.4 Command blocks by mode (Mod/Beh) ..................................................................................................... 363
17.2.5 Command blocks by Heatlh ....................................................................................................................... 364
17.2.6 Command blocks by Interlocking .............................................................................................................. 364
17.2.7 Commands blocks due to invalid/reached position ................................................................................ 364
17.3 COMMANDs for other positions ................................................................................................................. 365
17.4 COMMAND SADDRESS ............................................................................................................................... 365
18. RIO MODULES ................................................................................................................................ 367
18.1 CONFIGURATION ............................................................................................................................................... 367
18.2 OPERATION ....................................................................................................................................................... 367
19. CHANGES REQUIRING THE REBOOTING OF THE DEVICE ................................................................... 369
20. RECEPTION GOOSES ....................................................................................................................... 370
20.1 GOOSE SUBSCRIPTION .............................................................................................................................. 370
20.2 GOOSE SIMULATION .......................................................................................................................................... 371
20.3 TEST MODE ................................................................................................................................................... 373
20.3.1 Logical devices management hierarchy .................................................................................................. 373
20.4 SERVICE TRACKING .................................................................................................................................... 374
20.5 SUBSTITUTION MODEL ............................................................................................................................... 377
20.6 FILE TRANSFER ................................................................................................................................................... 378
20.7 EDITION1 SUBSCRIPTION. LGOS MODEL. ........................................................................................................... 378
20.7.1 Configuration values ....................................................................................................................................... 379
20.7.2 Supervision values ........................................................................................................................................... 380
20.7.3 Checked values ................................................................................................................................................ 380
21. TCP/IP NEWORK CONFIGURATION .................................................................................................. 381
21.1 DESCRIPTION ..................................................................................................................................................... 381
21.2 COMMUNICATIONS REDUNDANCY .................................................................................................................... 382
21.2.1 PARALLEL REDUNDANCY PROTOCOL (PRP) ..................................................................................................... 382
21.2.2 HIGH-AVAILABILITY SEAMLESS REDUNDANCY (HSR) ...................................................................................... 382
21.2.3 SWITCH MODE ................................................................................................................................................ 383
21.2.4 LINK FAILOVER REDUNDANCY ......................................................................................................................... 383

Ingeteam Power Technology S.A.


User Manual VII
INDEX 

21.3 GENERAL CONSIDERATIONS ABOUT NETWORK CONFIGURATION ..................................................................... 383


21.4 GOOSES ............................................................................................................................................................. 384
21.5 FIREWALL ........................................................................................................................................................... 384
22. COMMUNICATION BETWEEN DEVICES ............................................................................................ 385
22.1 DIRECT CONNECTION (POINT-TO-POINT) ........................................................................................................... 385
22.1.1 Multimode Optical Fibre ................................................................................................................................. 385
22.1.2 Single-mode optical fibre ................................................................................................................................ 385
22.2 CONNECTION WITH COMMUNICATIONS DEVICES (MULTIPLEXER) .................................................................... 386
22.2.1 IEEE-C37.94 Interface ...................................................................................................................................... 386
22.3 EXAMPLE OF CONNECTING A C37.94 - G.703 CONVERTER ................................................................................ 386
22.3.1 C37.94 - G.703 E1 2Mb Converter. ................................................................................................................. 386
22.3.2 C37.94 - G.703 E0 Converter. .......................................................................................................................... 388
23. KEYBOARD AND GRAPHIC DISPLAY ................................................................................................. 389
23.1 GENERAL OPERATION ........................................................................................................................................ 389
23.1.1 Display structure ............................................................................................................................................. 389
23.1.2 Organization of the pages ............................................................................................................................... 389
23.1.3 Treatment of the functional keys .................................................................................................................... 390
23.1.4 Graphics pages ................................................................................................................................................ 392
23.1.5 I/O pages ......................................................................................................................................................... 394
23.1.6 Event pages ..................................................................................................................................................... 395
23.1.7 Protection event pages ................................................................................................................................... 396
23.1.8 Alarm pages .................................................................................................................................................... 397
23.1.9 Device status pages ......................................................................................................................................... 398
23.1.10 Fault pages .................................................................................................................................................... 402
23.1.11 Measurement pages ..................................................................................................................................... 406
23.1.12 Menu to other screens page ......................................................................................................................... 408
23.1.13 Shortcut menu page ...................................................................................................................................... 409
23.2 CONTROL AND PROTECTION MENUS PAGES ...................................................................................................... 410
23.2.1 Operation of the menus .................................................................................................................................. 410
23.2.2 Password management ................................................................................................................................... 415
23.3 NETWORK CONFIGURATION .............................................................................................................................. 417
23.3.1 Ethernet Configuration ................................................................................................................................... 417
23.3.2 Gateway Configuration ................................................................................................................................... 421
23.4 OTHER SCREENS ................................................................................................................................................. 423
23.4.1 Contrast setting ............................................................................................................................................... 423
23.4.2 USB treatment................................................................................................................................................. 423
23.4.3 System Information ......................................................................................................................................... 424
23.4.4 CID validation .................................................................................................................................................. 425
23.4.5 Security Logs ................................................................................................................................................... 425
23.4.6 Test Screens .................................................................................................................................................... 425
23.4.7 Other Communications Menu Screens ........................................................................................................... 426
24. WEB APPLICATION ......................................................................................................................... 427
24.1 Introduction....................................................................................................................................................... 427
24.2 WEB application login ........................................................................................................................................ 427
24.2.1 Login ................................................................................................................................................................ 427
24.3 Tabs ................................................................................................................................................................... 428
24.3.1 Reports ............................................................................................................................................................ 428
24.3.2 Settings............................................................................................................................................................ 431
24.3.3 Maintenance ................................................................................................................................................... 432
24.3.4 SW/Configuration ........................................................................................................................................... 433
24.3.5 Logout ............................................................................................................................................................. 434

Ingeteam Power Technology S.A.


User Manual VIII
INDEX 

25. DNP PROTOCOL.............................................................................................................................. 435


25.1 INTRODUCTION ................................................................................................................................................. 435
25.2 CONFIGURATION SETTINGS ............................................................................................................................... 435
25.3 TABLES ............................................................................................................................................................... 440
25.3.1 Digital status table .......................................................................................................................................... 440
25.3.2 Analog values table ......................................................................................................................................... 440
25.3.3 Counters table ................................................................................................................................................. 441
25.3.4 Commands table ............................................................................................................................................. 441
25.4 DEVICE PROFILE ................................................................................................................................................. 443
25.4.1 OBJECT TABLE.................................................................................................................................................. 444
26. IEC 60870-5-103 PROTOCOL ............................................................................................................ 446
26.1 INTRODUCTION ................................................................................................................................................. 446
26.2 CONFIGURATION SETTINGS ............................................................................................................................... 446
26.3 Tables ................................................................................................................................................................ 449
26.3.1 Digital signals table ......................................................................................................................................... 449
26.3.2 Measurements table ....................................................................................................................................... 450
26.3.3 Commands table ............................................................................................................................................. 450
27. SLAVE PROCOME PROTOCOL .......................................................................................................... 451
27.1 INTRODUCTION ................................................................................................................................................. 451
27.2 CONFIGURATION SETTINGS ............................................................................................................................... 451
27.3 TABLES ............................................................................................................................................................... 453
27.3.1 Digital status table .......................................................................................................................................... 453
27.3.2 Analog values table ......................................................................................................................................... 453
27.3.3 Counters table ................................................................................................................................................. 454
27.3.4 Commands table ............................................................................................................................................. 454
28. MODBUS MASTER PROTOCOL ........................................................................................................ 455
28.1 INTRODUCTION ................................................................................................................................................. 455
28.2 CONFIGURATION SETTINGS ............................................................................................................................... 455
28.3 DATA TYPES ....................................................................................................................................................... 457
28.3.1 Digital signals .................................................................................................................................................. 457
28.3.2 Measurements ................................................................................................................................................ 457
28.3.3 Counters .......................................................................................................................................................... 458
28.3.4 Commands ...................................................................................................................................................... 458
28.3.5 Request of events to Ingeteam Power Technology devices ........................................................................... 458
28.3.6 Synchronization ............................................................................................................................................... 458
28.4 IMPLEMENTED FUNCTIONS ............................................................................................................................... 459
28.5 RTU TYPES ......................................................................................................................................................... 459
28.6 SW CONFIGURATION TOOL ................................................................................................................................ 460
28.6.1 Fields to be configured .................................................................................................................................... 460
28.6.2 Configuration example .................................................................................................................................... 468
28.7 SERIAL MESSAGES .............................................................................................................................................. 470
28.7.1 Format ............................................................................................................................................................. 470
28.7.2 Examples ......................................................................................................................................................... 471
29. MODBUS SLAVE PROTOCOL ............................................................................................................ 475
29.1 INTRODUCTION ................................................................................................................................................. 475
29.2 CONFIGURATION SETTINGS ............................................................................................................................... 475
29.3 PROTOCOL PROFILE ........................................................................................................................................... 478
29.3.1 Implemented functions in Modbus RTU ......................................................................................................... 478
29.3.2 Implemented functions in Modbus TCP/IP ..................................................................................................... 478
29.3.3 Exception codes .............................................................................................................................................. 479

Ingeteam Power Technology S.A.


User Manual IX
INDEX 

29.4 CONTROL PROCESSES ........................................................................................................................................ 479


29.4.1 Request for equipment status ........................................................................................................................ 479
29.4.2 Request for digital signals ............................................................................................................................... 479
29.4.3 Request for measurements and counters....................................................................................................... 479
29.4.4 Request for digital signal changes ................................................................................................................... 480
29.4.5 Requesting data via memory map .................................................................................................................. 481
29.4.6 Synchronization ............................................................................................................................................... 482
29.4.7 Command execution ....................................................................................................................................... 482
29.5 EQUIPMENT ADDRESS MAP ............................................................................................................................... 482
29.6 DATA FORMAT ................................................................................................................................................... 484
29.7 CONFIGURATION SOFTWARE TOOL ................................................................................................................... 485
29.7.1 Fields to be configured .................................................................................................................................... 485
29.7.2 Configuration example .................................................................................................................................... 488
29.8 SERIAL MESSAGES .............................................................................................................................................. 490
29.8.1 Format ............................................................................................................................................................. 490
29.8.2 Examples ......................................................................................................................................................... 491
29.9 TCP/IP MESSAGES .............................................................................................................................................. 495
29.9.1 Format ............................................................................................................................................................. 495
29.9.2 Examples ......................................................................................................................................................... 496
30. CURVES FOR TIMED CHARACTERISTICS ........................................................................................... 497
30.1 CEI 255-4 / BS142 CURVES ................................................................................................................................. 497
30.2 ANSI CURVES ..................................................................................................................................................... 510
30.2.1 Battery voltage curves .................................................................................................................................... 519
30.3 IEC 60255-151 curves ................................................................................................................................... 520
30.4 USER CURVES ..................................................................................................................................................... 527
31. MEASUREMENT LIST....................................................................................................................... 529
32. PREVENTIVE MAINTENANCE ........................................................................................................... 541
32.1 ERROR DETECTION ............................................................................................................................................. 542
32.2 ERROR HANDLING PROCEDURE ......................................................................................................................... 543
33. PROTECTION DEVICES WITH SAMPLED VALUES ............................................................................... 544
33.1 DEVICE MODELS................................................................................................................................................. 545
33.2 PUBLISHERS DECLARATION ................................................................................................................................ 545
33.3 SAMPLED VALUES SUBSCRIPTION ...................................................................................................................... 545
33.3.1 Configuration .................................................................................................................................................. 545
33.3.2 ADD-IN of subscription .................................................................................................................................... 546
33.3.3 Monitoring ...................................................................................................................................................... 548
33.4 CONFIGURABLE LOCAL MEASURES .................................................................................................................... 550
33.5 SAMPLED VALUES SIMULATION ......................................................................................................................... 550
33.6 TEST MODE FOR SAMPLED VALUES ................................................................................................................... 551
33.7 BEHAVIOUR WITH LOSS OF SYNCHRONIZATION ................................................................................................ 551

Ingeteam Power Technology S.A.


User Manual X
GENERAL DESCRIPTION 

1. GENERAL DESCRIPTION

1.1 FUNCTIONAL DESCRIPTION

Table 1 Functions depending on model

ZT0 ZT1 (52 ½)


Distance functions
Quadrilateral Characteristic (5 zones)  
Mho Characteristic (5 zones)  
21 High Speed  
Zone 1 Extension  
Double Lines  
Lines with Series Compensation  
CVT: Lines with Capacitive Voltage Transformers  
Common protection functions
SOTF Switch onto fault  
27 Undervoltage  
59 Overvoltage  
59N Zero sequence overvoltage  
47 V2 overvoltage  
Minimum voltage  
Frequency (81M/m)  
Frequency rate of change (81R)  
3x50/51 (67)  
50N/51N (67N)  
50G/51G. Earthing overcurrent  
46TOC (67Q), 46IOC(67Q)  
46BC Broken conductor  
50CSC Second harmonic restraint  
37 Undercurrent
49 Thermal image  
32 Power units  
Stub bus  
Stub bus differential 
50BF breaker failure (Single-pole/Three-pole)  
Breaker failure with low load (See note 1)  
49T Overtemperature through RTD (Only with RTD module)  
Teleprotection
Teleprotection (21)  
Teleprotection (67/67Q)  
Monitoring Units
68LE Load encroachment  
68FF Fuse failure  
78 Power Swing  
Fault locator  
Breaker Monitoring
Breaker monitoring per pole  
Closing and trip circuit monitoring  
Excessive number of trips  
Open pole / Dead line detector  
Breaker status logic  
Pole discordance  
Automatisms
Synchronism  
Recloser (Single-pole/Three-pole)  
Frequency recloser  
Data acquisition functions
Current and voltage measurements  
Active and reactive power and energy  

Ingeteam Power Technology S.A.


User Manual 11
GENERAL DESCRIPTION 

Historical event, protection event, fault recording and historical reports  


Oscillography  
CT and VT supervision  

Note 1: Available from firmware version 6.2.19.0 and ICD version 8.4.0.0

Ingeteam Power Technology S.A.


User Manual 12
GENERAL DESCRIPTION 

1.2 MODEL ENCODING

COM1
COM2
COM3
COM4
COM5
COM6

ETH1
ETH2
I/O 1

I/O 2

I/O 3

I/O 4

I/O 5

I/O 6

I/O 7

I/O 8
INGEPAC EF ZT MODEL INGEPAC EF- Z T - A - - -

MODEL
21, 85 (21), 85 (67/67Q), SOTF, 68LE, 68PS, 68FF, 67, 67N, 50/51, 50N/51N, 50G/51G, 67Q,
46BC, 37, 49, 59, 27, 59N, 47, 81O/u, 81R, 32, 25, 79, 79 (81), 74TC/CC, 50BF, Stub bus, Fault 0
Locator, Quality analysis
21, 85 (21), 85 (67/67Q), 52 ½, SOTF, 68LE, 68PS, 68FF, 67, 67N, 50/51, 50N/51N, 50G/51G,
67Q, 46BC, 37, 49, 59, 27, 59N, 47, 81O/u, 81R, 32, 25, 79, 74TC/CC, 50BF, Stub bus, Fault 1
Locator

EXTENDED CONTROL FUNCTIONS


No A
Yes B

HOUSING
1/2 chassis 19" 5U with configurable keyboard A
1/2 chassis 19" 5U with predefined keyboard Note 1 B
Chassis 19" 4U with configurable keyboard C
Chassis 19" 4U with predefined keyboard Note 1 D

POWER SUPPLY MODULE


Single PS 85-300 Vdc+ 6DI 125 Vdc + 4DO A
Single PS 85-300 Vdc+ 6DI 220 Vdc + 4DO B
Single PS 18-60 Vdc+ 6DI 24 Vdc + 4DO C
Single PS 18-60 Vdc+ 6DI 48 Vdc + 4DO D
Redundant PS 48 Vcc / 48Vcc F
Redundant PS 125 Vcc / 125Vcc G

REAR SERIAL COMMUNICATION PORTS


A GFO COM-1 (Note 7)
B PFO COM-2 (Note 7)
C RS232C COM-3
D RS485 COM-4
E FO singlemode 60km (ST) Note 8 COM-5
F FO singlemode 60km (LC) Note 8 COM-6
I C37.94 FO multimode (ST) Note 8
M FO singlemode 20-120km (ST) Note 8
N FO singlemode 20-120km (LC) Note 8
X No port

REAR ETHERNET COMMUNICATION PORTS


E GFO ETH-1
F RJ45 ETH-2
I GFO (Link failover redundancy) Note 6
J RJ45 (Link failover redundancy) Note 6
K LC (Link failover redundancy) Note 6
L LC
O LC (ETH with PRP/HSR/Switch) Note 9
P RJ45 (ETH with PRP/HSR/Switch) Note 9
X No port

TERMINALS
Pin type standard terminals A
Closed terminals Note 2 B
Closed terminals for analog inputs and pin type standard terminals for the rest C

I/O BOARD CONFIGURATION


BOARD SELECTION (Note 3)
-A No board Board 2
-B 11 DI (24V dc) + 9 DO Board 3
-C 11 DI (48 Vdc) +9 DO Board 4 (Note 4)
-D 11 DI (125 Vdc) + 9 DO Board 5 (Note 4)
-E 11 DI (220 Vdc) + 9 DO Board 6 (Note 4)
-F 32 DI (24Vdc) Note 10 Board 7 (Note 4)
-G 32 DI (48Vdc) Note 10
-H 32 DI (125 Vdc) Note 10
-I 32 DI (220 Vdc) Note 10
-J 16 DI (24Vdc)-8 independent DO
-K 16 DI (48 Vdc)-8 independent DO
-L 16 DI (125 Vdc)-8 independent DO
-M 16 DI (220 Vdc)-8 independent DO
-N 16 DI (24 Vdc)- 16DO
-O 16 DI (48Vdc)- 16 DO
-P 16 DI (125 Vdc)- 16DO
-Q 16 DI (220 Vdc)- 16DO
-R 16 DI (24Vdc)-8 AI Note 5
-S 16 DI (48Vdc)-8 AI Note 5
-T 16 DI (125 Vdc)-8 AI Note 5
-U 16 DI (220 Vdc)-8 AI Note 5
-V 16 DI (24 Vdc)- 8 AI (4 isolated) Note 5
-W 16 DI (48Vdc)- 8 AI (4 isolated) Note 5
-X 16 DI (125 Vdc)- 8 AI (4 isolated) Note 5
-Y 16 DI (220 Vcc)- 8 AI (4 isolated) Note 5
-0 8DI (24Vcc) + 4DO (h.b.c.o.) + 4DO
-1 8DI (48Vcc) + 4DO (h.b.c.o.) + 4DO
-2 8DI (125Vcc) + 4DO (h.b.c.o.) + 4DO
-3 8DI (220Vcc) + 4DO (h.b.c.o.) + 4DO
-4 8DI (24Vcc) + 8DO
-5 8DI (48Vcc) + 8DO
-6 8DI (125Vcc) + 8DO
-7 8DI (220Vcc) + 8DO
-8 11 RTD + 4 AO Note 12
ZB 8DI (24Vcc) + 4DO (fast+h.b.c.o.) + 4DO Note 11
ZC 8DI (48Vcc) + 4DO (fast+h.b.c.o.) + 4DO Note 11
ZD 8DI (125Vcc) + 4DO (fast+h.b.c.o.) + 4DO Note 11
ZE 8DI (220Vcc) + 4DO (fast+h.b.c.o.) + 4DO Note 11
ZF 8ED (24Vcc) + 8SD (h.b.c.o.)
ZG 8ED (48Vcc) + 8SD (h.b.c.o.)
ZH 8ED (125Vcc) + 8SD (h.b.c.o.)
ZI 8ED (220Vcc) + 8SD (h.b.c.o.)

- Reservado
- Reservado
- Reservado

Note 1: Only selectable with extended control functions.


Note 2: The terminals for the power supply inputs are pyn type standard terminals.
Note 3:To know the order of the boards in the rack, consult the number of the terninals on the rear views of each chassis.
Note 4: Only available for 19" chassis.
Note 5: Standard analogue inputs configuration: +/-5mA, +/-5mA, +/-2.5mA, +/-2.5mA, +/-2.5mA, +/-2.5mA, +/-20mA, +/-20mA. Consult other configurations.
Note 6:This option requires selecting both ETH1 as ETH2 and supports any combination of options I , J and K.
Note 7: Teleprotection ports only can use COM1 and COM2
Note 8: Only for Teleprotection ports.
Note 9: If there is only one card with these options it should be placed in ETH-1. This options replace options G, H, M, N. To use replaced options consult Ingeteam.
Note 10: If REAR ETHERNET COMMUNICATION PORT is "O" or "P", not available on board I/O 2 (4U housing) neither on board I/O 3 (5U housing).
Note 11: Not available on board I/O 7. If REAR ETHERNET COMMUNICATION PORT is "O" or "P", not available on board I/O 2 (4U housing) neither on board I/O 3 (5U housing).
Note 12: The maximun number of RTD board in the device are 2 .

It´s available an external accessory (FC2910) to allow BNC connection with coaxial cable in Irig-B and PPS input.

Ingeteam Power Technology S.A.


User Manual 13
GENERAL DESCRIPTION 

ZT1 model is specific for breaker and a half. The analog input 7 can be selected between Polarization current and Parallel line Neutral
current 2
Available analog inputs in models

Model T1 T2 T3 T4 T5 T6 T7 T8 T9 T10 T11 T12


ZT0 IA IB IC I neutral Ipol In2 Vs2 Vs1 V neutral VA VB VC
ZT1 I A1 I B1 I C1 I A2 I B2 I C2 In2/Ipol Vs2 Vs1 VA VB VC

Figure 1 Board position according to model encoding 19” chassis

Figure 2 Board position according to model encoding ½ 19” chassis”

Figure 3 Redundant power supply ½ 19” chassis Figure 4 Redundant power supply 19” chassis

Ingeteam Power Technology S.A.


User Manual 14
GENERAL DESCRIPTION 

Figure 5 PRP Redundancy (2RJ45) Figure 6 PRP Redundancy (2RJ45 + 2LC)

Ingeteam Power Technology S.A.


User Manual 15
GENERAL DESCRIPTION 

1.3 USER INTERFACE

The front board is equipped with:

❑ 10-digit numerical keyboard with decimal point, plus R key


❑ 4 scroll keys:  (Up),  (Down),  (Left), → (Right)
❑ 3 general keys  (Enter), ESC (Escape), MENU
❑ Function keys depending on the model:
 5 function keys (I, O, DES, SEL, INF)
 7 function keys (I, O, F1...F5)
 12 function keys (I, O, DES, SEL, INF, F1…F7)
 16 function keys (I, O, F1…F14)
❑ 19 fully assignable LEDs
❑ 1 unit operation LED
❑ USB 2.0 front port for downloading reports and loading CID
❑ Front RJ45 port for communications
Dispone de un interface trasero con comunicaciones:

The rear communications could be:

❑ Ethernet. Up to two Ethernet port (IEC8802-3) with options of RJ45, GFO or LC. Redundant ports are optional.
❑ Serial. Up to 6 ports with options: RS232, RS485, GFO and PFO.

1.4 INTERCONNECTIONS

Interconnections depend on the modules selected. The connections associated with each of the modules are indicated, and thus the
diagram will depend on the modules installed.

1.4.1 CPU
Figure 7 3-contact relay and IRIG-B Figure 8 With BNC accessory

Ingeteam Power Technology S.A.


User Manual 16
GENERAL DESCRIPTION 

1.4.2 Power supply


The two options are a redundant power supply and a simple power supply with inputs/outputs.

Figure 9 Simple power supply

Figure 10 Double power supply

1.4.3 Input/output cards


The I/O modules available are:

❑ Module 1 (Figure 11): Equipped with 11 digital inputs and 9 digital outputs grouped as follows:
 Inputs: 4 independent + 3 with a common point + 4 with a common point.
 Outputs: 5 independent + 3 with a common point + 1 switched (3 contacts).

Figure 11 Module 11 digital inputs and 9 digital outputs

❑ Module 2 (Figure 12): Equipped with 16 digital inputs and 16 digital outputs grouped as follows:
 Inputs: 16 with a common point.
 Outputs: 16 with a common point.

Figure 12 Module 16 digital inputs and 16 digital outputs

❑ Module 3 (Figure 13): Equipped with 16 digital inputs and 8 digital outputs grouped as follows:
 Inputs: 16 with a common point.
 Outputs: 8 independent.

Ingeteam Power Technology S.A.


User Manual 17
GENERAL DESCRIPTION 

Figure 13 Module 16 digital inputs and 8 digital outputs

❑ Module 4 (Figure 14): Equipped with 32 digital inputs grouped as follows:


 Inputs: 16 with a common point + 16 with a common point.

Figure 14 Module 32 inputs

❑ Module 5 (Figure 15): Equipped with 16 digital inputs and 8 analogue inputs grouped as follows:
 Inputs: 16 with a common point.
 Analogue: 8 independent. The analogue inputs have standard configuration, that could be changed among the
options: ±1mA, ±2.5mA, ±5mA, ±20mA, ±5V, ±10V
Standard configuration of analogue inputs

Input 1 Input 2 Input 3 Input 4 Input 5 Input 6 Input 7 Input 8


+/- 5mA +/- 5mA +/- 2.5mA +/- 2.5mA +/- 2.5mA +/- 2.5mA +/- 20mA +/- 20mA

Figure 15 Module with 16 digital inputs and 8 analogue inputs

❑ Module 6 (Figure 16): Equipped with 16 digital inputs and 8 analogue inputs (4 isolated) grouped as follows:
 Inputs: 16 with a common point.
 Analogue: 8 independent, 4 of them are isolated and 4 have a common point. The analogue inputs have
standard configuration, that could be changed among the options: ±1mA, ±2.5mA, ±5mA, ±20mA, ±5V, ±10V

Standard configuration of analogue inputs

Input 5 Input 6 Input 7 Input 8


Input 1 Input 2 Input 3 Input 4
(isolated) (isolated) (isolated) (isolated)
+/- 5mA +/- 5mA +/- 2.5mA +/- 2.5mA +/- 2.5mA +/- 2.5mA +/- 20mA +/- 20mA

Figure 16 Module with 16 digital inputs and 8 analogue inputs (4 isolated)

Ingeteam Power Technology S.A.


User Manual 18
GENERAL DESCRIPTION 

❑ Module 7 (Figure 17): Equipped with 8 digital inputs, 4 high breaking capacity outputs (hbco) and 4 digital outputs
grouped as follows:
 Inputs: 8 independent.
 Outputs: 8 independent: the 4 hbco outputs are 1 to 4 (pins 1 to 8) and the 4 standard outputs are 5 to 8 (pins
10 a 17).

Figure 17 Módule 8 inputs, 4 outputs (hbco) and 4 digital outputs

❑ Module 8 (Figure 18): Equipped with 8 digital inputs, 8 digital outputs grouped as follows:
 Inputs: 8 independent.
 Outputs: 8 independent.

Figure 18 Módule 8 inputs, 8 outputs

❑ Module 9 (Figure 19): Equipped with 8 digital inputs, 4 fast and high breaking capacity outputs (hbco) and 4 digital outputs
grouped as follows:
 Inputs: 8 independent.
 Outputs: 8 independent: the 4 fast and hbco outputs are 1 to 4 (pins 1 to 8) and the 4 standard outputs are 5
to 8 (pins 10 a 17).

Figure 19 Module 8 inputs, 4 outputs (fast and hbco) and 4 digital outputs

❑ Module 10 (Figure 18): Equipped with 8 digital inputs, 8 high breaking capacity outputs (hbco) grouped as follows:
 Inputs: 8 independent.
 Outputs: 8 hbco independent outputs..

Figure 20 Module 8 inputs, 8 outputs (hbco)

Ingeteam Power Technology S.A.


User Manual 19
GENERAL DESCRIPTION 

❑ Module 11 (Figure 21): Equipped with 11 RTD inputs and 4 analogue outputs grouped as follows:
 RTD Inputs: 11 RTD.
 Analogue outputs: 4 independent. The analogue outputs can be configured with the options 0-1mA, 0-20mA,
4-20mA.
Figure 21 Module 11 RTD and 11 analog outputs

1.4.4 Analogue inputs


The following diagram shows the configuration of the analogue inputs:

ZT0 ZT1

Ingeteam Power Technology S.A.


User Manual 20
GENERAL DESCRIPTION 

1.4.4.1 Wiring diagrams


The following figures show different interconnection options for the analogue inputs, in accordance with the available inputs.

Figure 22 Wiring diagram Iphase, In, Ipol, Vphase, Vsyn

Ingeteam Power Technology S.A.


User Manual 21
GENERAL DESCRIPTION 

Figure 23 Wiring diagram Iphase, In, Vphase, Vsyn

Ingeteam Power Technology S.A.


User Manual 22
GENERAL DESCRIPTION 

Figure 24 Wiring diagram Iphase, In, Ipol, Vphase, V0 and Vsyn

Ingeteam Power Technology S.A.


User Manual 23
GENERAL DESCRIPTION 

Figure 25 Wiring diagram Iphase, In, Vphase, V0 and Vsyn

Ingeteam Power Technology S.A.


User Manual 24
GENERAL DESCRIPTION 

Figure 26 Wiring diagram 52 ½

Figure 27 Topology 52 ½

Ingeteam Power Technology S.A.


User Manual 25
HARDWARE 

2. HARDWARE
EF devices can be used as autonomous devices or as part of a protection and control system. The devices are implemented based on a
microprocessor and a DSP linked through shared RAM and communication lines.

The digital processing is done by a high accuracy 16 bit converter. Each signal reaches this converter after being conditioned, filtered and
amplified. A high frequency sampling is done at 144 samples per cycle (at 8640 Hz for 60 Hz systems or at 7200Hz for 50 Hz systems). This
sampling is transformed into 24 samples per cycle through a digital process before reaching the protection functions.

INGEPAC EF devices have non-volatile flash memory where the user settings, configurations and application are stored. This kind of
memory allows software updates and modifications without needing to manipulate the device hardware.

2.1 CONSTRUCTION FEATURES

Two options can be selected:

❑ Half chassis ½ 19” and 5U


❑ Chassis 19” and 4U

2.1.1 Half chassis (½ 19”)

Ingeteam Power Technology S.A.


User Manual 26
HARDWARE 

2.1.2 19” chassis

2.2 REAR TERMINALS

The rear section will vary in accordance with the options selected for the unit. The following figures show various possible
configurations.

2.2.1 Configuration options


The rear section options may vary depending on the options selected:

❑ Power supply unit. There are two options available:


 Simple with inputs/outputs. Equipped with a 3-contact terminal with power supply with screw and a 17-
contact terminal with screw (Figure 28).
 Redundant. Equipped with two 3-contact terminals for each of the power supplies.
❑ Inputs/outputs cards. All the input/output modules have two 17-contact terminals with screw.
❑ CPU. Equipped with a 6-contact terminal with screw for the digital output of 3 contacts and the IRIG-B inputs. Equipped
with different Ethernet and standard communications module options (Figure 7).
❑ Analogue. Equipped with two 12-contact terminals with screw.
❑ Communications. To choose between:
 Ethernet: RJ45 and G.F.O.
 Standard: RS232, RS485, G.F.O. and P.F.O.
Pin type or closed type terminals may be chosen for the analogue and input/output terminals.

2.2.2 Half chassis (½ 19”)


Different options which modify the view of the rear section may be selected (from top to bottom):

❑ Simple/redundant power supply


❑ 1 or 2 I/O modules

Ingeteam Power Technology S.A.


User Manual 27
HARDWARE 

❑ Communication ports in the CPU


❑ Analogue card with up to 12 transformers
Figure 28 shows rear section with the options:

❑ Simple power source with inputs/outputs


❑ 2 input/output cards
❑ CPU with communication ports:
 Ethernet GFO + RJ45
 Standard RS232+RS485+GFO+PFO
❑ Analogue card with up to 12 transformers

Figure 28 Rear section with analogue and simple source

Figure 29 Rear section without analogue and simple source

2.2.3 19” chassis


Different options which modify the view of the rear section may be selected (from top to bottom and left to right):

❑ Simple/redundant power supply


❑ 1 or no I/O modules
❑ Communication ports in the CPU

Ingeteam Power Technology S.A.


User Manual 28
HARDWARE 

❑ Analogue card with up to 12 transformers


❑ Number of I/O modules
In Figure 30 the next options can be seen:

❑ Simple power source with inputs/outputs


❑ 5 input/output cards
❑ CPU with communication ports:
 Ethernet GFO + RJ45
 Standard with 3 RS232 + 2 GFO + PFO
❑ Analogue card with up to 12 transformers
Figure 30 Rear section with analogue and simple source

2.2.1 Closed Terminals


The next figures show the closed terminals used in the digital I/O boards (Figure 31) and the transformer inputs (V/I) (Figure 32).

Figure 31 Closed Terminals I/O boards

Figure 32 Closed Terminals transformer inputs (V/I)

2.2.2 Wire section


The wires for the terminals should be copper with a section:

❑ Supply terminals:
Wire section AWG 16 to 12 (1.5 to 2.5 mm2)

❑ I/O terminals:
Wire section AWG 16 to 12 (1.5 to 2.5 mm2)

Ingeteam Power Technology S.A.


User Manual 29
HARDWARE 

❑ Current and voltage terminals:


Wire section AWG 10 (4 mm2)

2.3 FRONT INTERFACE

2.3.1 Half chassis (½ 19”)


There are two half-chassis front options (½ 19” and 5U):

❑ Configurable functional keys (Figure 33)


❑ Fixed functional keys (Figure 34).
The front interfaces are equipped with:

❑ Graphic display
❑ 19 general use LEDs with interchangeable labels
❑ 1 2-colour unit status LED
❑ Numeric keypad
❑ 7 operational keys
❑ Ethernet communication
❑ Master USB communication
❑ Depending on the model, the following are available:
 5 functional keys for selecting with interchangeable labels + 2 operational keys
 3 fixed function keys + 2 operational keys.

Figure 33 Configurable functional keys Figure 34 Fixed functional keys

2.3.2 19” chassis


There are two 19” and 4U chassis front options:

❑ Configurable functional keys (Figure 35)


❑ Fixed functional keys (Figure 36)
The front interfaces are equipped with:

❑ Graphic display
❑ 19 general use LEDs with interchangeable labels

Ingeteam Power Technology S.A.


User Manual 30
HARDWARE 

❑ 1 2-colour unit status LED


❑ Numeric keypad
❑ 7 operational keys
❑ Ethernet communication
❑ Master USB communication
❑ Depending on the model, the following are available:
 14 functional keys for selecting with interchangeable labels + 2 operational keys
 3 fixed function keys + 2 operational keys + 7 functional keys with interchangeable labels for selecting.

Figure 35 Configurable functional keys

Figure 36 Fixed functional keys

2.4 TECHNICAL CHARACTERISTICS

2.4.1 Power supply voltage


Single power supply 125/220 Vdc models: 110Vdc-20% up to 250Vac + 10%:

❑ Operating range:
 Direct: 88Vdc up to 300Vdc
 Alternating: 85Vac up to 265Vac
Single power supply 24/48 Vdc models: 24Vdc-20% up to 48Vdc + 20%:

❑ Operating range:
 Direct: 18Vdc up to 60Vdc
Redundant power supply 125Vdc models:

❑ Operating range:

Ingeteam Power Technology S.A.


User Manual 31
HARDWARE 

 Direct: 88Vdc up to 170Vdc


Redundant power supply 24/48 Vdc models:

❑ Operating range:
 Direct: 18Vdc up to 60Vdc
Burden. Depends on the cards connected.

❑ 20W + 0,5W for each relay activated


Battery failure signal. Minimum voltage to activate the signal

Power supply 24Vcc 48Vcc 125Vcc 220Vcc


Activation level 16V 37V 86V 170V
The wires for the terminals should be copper with a section AWG 16 to 12 (1.5 to 2.5 mm2).

2.4.2 Digital outputs


The wires for the I/O terminals should be copper with a section AWG 16 to 12 (1.5 to 2.5 mm2).

Independent standard and trip outputs:

The characteristics of the independent contact outputs are as follows:

❑ Permanent current: 8 A at 25ºC


❑ Make: 30 A 1sec
❑ Connection capacity 2500W at 250Vdc
❑ Open or break capacity:
200Vdc 125Vdc 48Vdc
With resistive load 1.0A 1.5A 2.0A
With inductive load L/R=40ms 0.7A 1.0A 1.5A

❑ Operating time: 5ms activation and 8ms deactivation


Signal outputs:

The characteristics of the 3-contact switched, common point signal outputs are:

❑ Permanent current: 5 A at 25ºC


❑ Make:
 30 A ½ sec.
 20 A 1 sec.
❑ Open or break capacity:
200Vdc 125Vdc 48Vdc
With resistive load 0.2A 0.4A 1.0A
With inductive load L/R=40ms 0.1A 0.2A 0.5A

❑ Operating time: 8ms activation and deactivation


The compliance of the common point outputs is the same as that of the independent outputs. However, due to sharing a common
point, only 2 relays can be activated simultaneously.

High break contact outputs (h.b.c.o) and Fast + high break contact outputs (fast + h.b.c.o):

The characteristics of the independent contact outputs are the same except the activation times:

❑ Permanent current: 8 A at 25ºC


❑ Make: 30 A 1sec

Ingeteam Power Technology S.A.


User Manual 32
HARDWARE 

❑ Connection capacity 2500W at 250Vdc


❑ Open or break capacity:
200Vdc 125Vdc 48Vdc
With resistive load 10A 10A 10A
With inductive load 10A L/R=20ms 10A L/R=40ms 10A L/R=40ms

❑ Cyclic capacity: 4 cycles in 1 second, 2 minutes waiting for thermal dissipation


❑ Operating time:
 h.b.c.o outputs
 5ms activation and 5ms deactivation with resistive load
 5ms activation and 14ms deactivation with L/R = 40ms
 Fast + h.b.c.o outputs
 3µs activation and 8ms deactivation with resistive load

2.4.3 Digital inputs


The input burden is lower than 3mA at nominal voltage.

The inputs do not have polarity.

The wires for the I/O terminals should be copper with a section AWG 16 to 12 (1.5 to 2.5 mm2).

They have a fixed range with 4 nominal voltage options:

Rated V Characteristics
Not activated below 9 Vdc.
24Vdc Activated above 12 Vdc.
Maximum voltage 72 Vdc
Not activated below 32 Vdc.
48Vdc Activated above 37 Vdc.
Maximum voltage 72 Vdc
Not activated below 82 Vdc.
125Vdc They are activated above 87 Vdc.
Maximum voltage 300 Vdc
Not activated below 165 Vdc.
250Vdc Activated above 172 Vdc.
Maximum voltage 300 Vdc

2.4.4 IRIG-B input and PPS


Equipped with an input for synchronization by GPS, using IRIG-B time codes (Figure 37) and a pulse per second (PPS) input for
synchronization with:

❑ Demodulated input (TTL levels).


❑ Cable type: 2-wire, shielded
❑ Insulation: 2000 V
The input circuit is a 440 ohm serial resistance with an opto-isolator; for a 5 V signal, the approximate burden is 10 mA.

The number of units that can be connected in parallel to a generator depends on the output current supply capacity; a typical value
is 70 mA, which would enable the connection of 6 units (although the length and the type of cable can also influence). The cable
must be shielded and twisted.

According to configuration, it synchronizes with frames B002 , B003 , B006 , B007 type . It also synchronizes with IEE1344.

Optionally, with an external adapter inputs IRIG- B and PPS can be BNC type. The connection must use a 50 Ω coaxial cable with a
male BNC connector.

Ingeteam Power Technology S.A.


User Manual 33
HARDWARE 

Figure 37 Connection example

2.4.5 Analogue ouputs


There is an I/O board with 4 continuous analogue outputs.

❑ Range can be selected by settings: 0 at 1 mA, 4 at 20mA and 0 at 20mA


❑ Accuracy: ± 1 % of full scale
❑ Maximum load: 1200 Ohms
❑ Isolation: 1 kV

2.4.6 RTD Inputs


There is a I/O board with 11 isolated RTDs suitable by setting for the following probes:

❑ 100Ω Platinum
❑ 100Ω Nickel
❑ 120Ω Nickel
❑ 10Ω Copper
Measurement range: -50ºC to +250ºC

Accuracy: ±2ºC

The wire must be shielded and twisted.

2.4.7 Current and voltage circuits


Phases, neutral and polarization. Single rated current 1/5 A.

❑ Measurement range: 0.02A to 200A.


❑ Thermal capacity
 Permanent 20 A
 Short duration 150 A (10 sec.)
500 A (1 sec.)

 Very short duration 1250 A (half cycle)


❑ Burden at In= 5 A <0.2VA

Ingeteam Power Technology S.A.


User Manual 34
HARDWARE 

❑ Burden at In= 1 A <0.02VA


Voltage:

❑ Measurement range: 1V to 200V.


❑ Rated voltages: Configurable 40Vac to 140Vac
❑ Thermal capacity
 Permanent 2 Un
 Short duration 5 Un (1 sec.)
3.5 Un (1 min)

❑ Burden at 63.5 V <0.015 VA


❑ Burden at 100 V <0.03 VA
The wires should be copper with a section AWG 10 (4 mm2).

2.4.7.1 Accuracy
❑ Current
 Measurement range (0 to 1.2*Ir)
 With Ir = 1: class 0.2 (0.2% of FS)
 With Ir = 5: class 0.2 (0.2% of FS)
 Protection range (0 to 200 A)
 1 % over the measurement or 1 mA (greater)
❑ Voltage
 Measurement range (0 to 1.2*Vr)
 Accuracy 0.2% of FS
 Protection range (0 to 200 Vac)
 1 % over the measurement or 50 mV (greater)
❑ Dephase angle
 Accuracy  1º
❑ Power
 Measurement range (0 to 1.2*Ir*1.2*Vr)
 With Ir = 1: class 0.5 (0,5% of Pr)
 With Ir = 5: class 0.5 (0,5% of Pr)
❑ Frequency: ±10mHz
Time accuracy:

❑ Additional time = 0ms


 Measurement/start value:
 From 1 to 1,5 times: Up to 40ms (typical 35ms). Up to 35ms with fast outputs.
 2 times: Between 30-35ms. Up to 30ms with fast outputs.
 From 3 times: Under 30ms. Under 25ms with fast outputs.
 Additional time higher than 50ms
 30ms or 3% of the theorical value (the higher of the two)
Currents must be above 100mA.

The drop-off percentages respect to the start setting in the protection units are:

❑ Overcurrent: 5%
❑ voltage: configurable from 1%

Ingeteam Power Technology S.A.


User Manual 35
HARDWARE 

❑ Distance: 5%
❑ Differential: 5%
❑ Frequency: 0,05%

2.4.8 Front communication


Ethernet (IEC8802-3) via RJ45 cable

❑ RJ45 connector (female)


❑ Cable type: Shielded
❑ Cable length: 100 m maximum
❑ Baud rate: 10/100 Mb.
❑ Insulation 500V
USB

❑ USB 2.0 compatible version


❑ Master operating mode
❑ Speed: 480Mbps (high-speed), 12Mbps (full-speed) or 1.5Mbps (low-speed)
❑ Insulation 500V

2.4.9 Rear communications

2.4.9.1 Ethernet communication


The device has two Ethernet port (IEC8802-3) with options of RJ45 or optical fiber.

Ethernet via RJ45 cable

❑ RJ45 connector (female)


❑ Cable type: Shielded
❑ Cable length: 100 m maximum
❑ Baud rate: 10/100 Mb.
❑ Insulation 500V
Ethernet via glass optical fiber (ST and LC)

❑ Connector
 ST
 LC
❑ Wavelength: 1310nm
❑ Multimode glass optical fiber: 62.5 /125 µm and 50/125 µm
❑ Permitted attenuation
 8 db with 50/125 µm
 11 db with 62.5/125 µm
❑ Typical transmitter optical power: -20dBm to -14dBm
❑ Receiver optical sensitivity: -31dBm
❑ Baud rate: 100 Mb.
❑ Maximum distance: 2 km

Ingeteam Power Technology S.A.


User Manual 36
HARDWARE 

2.4.9.2 Serial communications


Glass optical fiber

❑ ST connector
❑ Wavelength: 820nm
❑ Multimode glass optical fiber: 62.5 /125 µm and 50/125 µm
❑ Permitted attenuation
 9 db with 50/125 µm
 11 db with 62.5/125 µm
❑ Typical transmitter optical power: -17dBm to -11dBm
❑ Receiver optical sensitivity: -28dBm
❑ Maximum distance: 2 km
Plastic optical fiber

❑ V-Pin connector (HP standard)


❑ Wavelength: 660nm
❑ Multimode optical fiber HCS (silica) with 200 µm and plastic with 1mm
❑ Permitted attenuation:
 24.7db with 1mm plastic cable
 22db with 200 µm silica cable
❑ Typical transmitter optical power
 -17dBm to -8dBm with 1mm plastic cable
 -13,5dBm to -4,5dBm with 200 µm silica cable
❑ Receiver optical sensitivity: -39dBm
❑ Maximum distance: 115m with 1mm plastic cable and 1.9km with 200 µm silica cable
RS232

❑ DTE 9 pin female D type


❑ Cable type: Shielded
❑ Cable length: 15 m maximum
❑ Insulation 500V
RS485

❑ DTE 9 pin female D type


❑ Cable type: Shielded crossed pair
❑ Cable length: 1.000 m maximum.
❑ Insulation 500V
The serial ports pinout is shown in the table:

Pin RS232 RS485


1 CD D+
2 Rx D+
3 Tx D-
4 9 Vcc D-
5 GND GND
6 DSR
7 RTS
8 CTS
9

Ingeteam Power Technology S.A.


User Manual 37
HARDWARE 

For communications between devices, according to options available in each model, can be used:

FO single-mode (60km)

❑ Connector LC duplex or ST
❑ Wavelength: 1310nm, Laser
❑ Singlemode: 9/125 nm
❑ Permitted attenuation: 30db
❑ Typical transmitter optical power: -5dBm a 0dBm
❑ Receiver maximun optical power: 0dBm
❑ Maximum distance: 60km
❑ Minimum distance: 1km

FO single-mode (20-120km)

❑ Connector LC duplex or ST
❑ Wavelength: 1550nm, Laser
❑ Singlemode: 9/125 nm
❑ Permitted attenuation: 40db
❑ Typical transmitter optical power: 0dBm a 5dBm
❑ Receiver maximun optical power: 0dBm
❑ Maximum distance: 120km
❑ Minimum distance: 20km. It cannot be used below 20km.

C37.94 glass optical fiber

❑ ST connector
❑ Wavelength: 850nm
❑ Multimode glass optical fiber: 50/125µm and 62.5/125 µm
❑ Permitted attenuation:
 13db with 62,5/125 µm
 9dB with 50/125 µm
❑ Typical transmitter optical power: -16dBm a -11dBm
❑ Receiver maximun optical power: -32dBm
❑ Maximum distance: 2km

Ingeteam Power Technology S.A.


User Manual 38
HARDWARE 

2.5 ENVIRONMENTAL CONDITIONS

Operating temperature:

❑ Continuous: -25°C a +60 ºC


❑ <96h: -25°C a +70 °C
❑ <16h: -40°C a +85ºC
❑ HMI and MTBF may be affected outside the continuous operating temperature range
❑ The maximum operation temperature for LC communication ports is +70º
Storage temperature: -40 to 85 ºC

Relative humidity: Up to 95% without condensation

2.5.1 Tropicalized
Printed circuit boards are lacquered to protect against corrosion and biological factors in humid environments. Depending on the
type of card different methods are used, dipping or selective varnishing and different varnishes. It is a treatment that deposits a
layer of low surface energy that repels moisture and some types of dirt. This procedure is made by demand, in the order.

2.6 TESTS

2.6.1 Climatic test


Climatic test Standard
Cold IEC -60068-2-1 -40°C, 16 hours
Dry Heat IEC -60068-2-2 +85°C, 16 hours
Damp heat steady state IEC -60068-2-78 +40°C/93%RH, 96 hours
Damp heat cyclic IEC -60068-2-30 55ºC / 95% HR 6 cycles of 12+12 hours
Rapid change of temperature IEC -60068-2-14 -20ºC/+70ºC 5 cycles of 3+3 hours
External protection level IEC60529 IP30

2.6.2 Insulation and electrical safety tests


Insulation and electrical safety test Standard
Dielectric test IEC 60255-27 2 kVac
Insulation resistance test IEC 60255-27 > 100 MΩ at 500Vdc.
±5kV CM
Impulse voltage test IEC 60255-27
±1kV DM

2.6.3 Mechanical tests


Mechanical test Standard
Vibration (sinusoidal): Response IEC 60255-21-1 Class 2
Vibration (sinusoidal): Endurance IEC 60255-21-1 Class 1
Shocks and bumps IEC 60255-21-2 Class 1
Seismic IEC 60255-21-3 Class 2

Ingeteam Power Technology S.A.


User Manual 39
HARDWARE 

2.6.4 Electromagnetic tests


Electromagnetic test Standard
IEC 60255-26
Measurements of radiated disturbance field strength EN 55022 A Class
CISPR 11, 32
IEC 60255-26
A Class PS
Measurements of conducted radioelectric disturbances EN 55022
B class: Ethernet port
CISPR 11, 32
IEC 60255-26 ±2.8kV CM
Damped oscillatory waves immunity test
IEC 61000-4-18 ±1kV DM
IEC 60255-26
Electrostatic discharge immunity test ±8kV/±15kV
IEC 61000-4-2
IEC 60255-26
Electrical Fast transients immunity test ±4kV,5kHz
IEC 61000-4-4
IEC 60255-26 ±4kV CM
Surge immunity test IEC 61000-4-5 ±2kV DM
IEC 60255-26 100% 130 ms
DC power supply interruptions, dips and variations immunity test IEC 61000-4-29 60% 200 ms
IEC 61000-4-11 30% 5s
IEC 60255-26
Ripple immunity test 15% (50 and 100 Hz)
IEC 61000-4-17
IEC 60255-26
Power frequency immunity test IEC6100-4.16 300 V CM/ 150 V DM
IEC 60255-22-7
IEC 60255-26
Radiated radiofrequency electromagnetic field immunity test 10V/m
IEC 61000-4-3
IEC 60255-26
Conducted disturbances induced by radiofrequency fields immunity test 10Vrms
IEC 61000-4-6
IEC 60255-26
50 Hz magnetic fields immunity test 100 A/m 1000 A/m (2 s)
IEC 61000-4-8
IEC 60255-26
Pulse magnetic fields immunity test 1000 A/m
IEC 61000-4-9
Damped oscillatory magnetic fields immunity test IEC 61000-4-10 100 A/m
Radiated Electromagnetic Interference from Transceivers IEEE 37.90.2 35 V/m

Ingeteam Power Technology S.A.


User Manual 40
PROTECTION FUNCTIONS

3. PROTECTION FUNCTIONS

3.1 DISTANCE UNITS (21)

Protections have measurement units per phase combination (AN, BN, CN, AB, BC, and CA), per characteristic (quadrilateral and Mho)
and per zone of operation (5 zones).

A distance protection measurement unit compares the voltage and current to calculate the impedance and the distance from the relay
to the fault to determine whether the fault is inside or outside the protected zone.

The protection has 5 zones of operation that can be configured independently with different characteristics. The overreaching zones
are useful as backup protection of the adjacent lines. The typical configuration uses three forward zones and one backwards.

❑ The first zone typically covers up to 80% of the protected line, causing instantaneous trips for faults in this zone.
❑ The second zone covers the rest of the line and part of the following one, usually up to 120% of the line. It provides trips or
signalling, depending on how it is programmed. The trips are not instantaneous, there is an additional programmable time for
giving another protection time to clear the fault if it is outside of its line.
❑ The third zone covers the rest of the overreach line and part of the next one. It provides trips or signalling, depending on how it is
programmed. The trips are not instantaneous, there is an additional programmable time available.
❑ The fourth zone covers the reverse line. It provides trips or signalling, depending on how it is programmed. The trips are not
instantaneous, there is an additional programmable time available.
❑ The fifth zone is used as backup and covers all the zones. It provides trips or signalling, depending on how it is programmed. The
trips are not instantaneous, there is an additional programmable time available.
The distance unit is supervised by the following functions:

❑ A directional function which provides the direction of the fault.


❑ A phase identifier which discriminates the phases involved in the fault, to prevent certain units from overreaching.
❑ Current supervision. This allows fixing the minimum value so that there are distance trips.
The Mho and/or quadrilateral characteristic can be used for both the single phase to ground faults and for phase - phase faults,
depending on which setting is selected.

The distance units for ground faults correct the current measured in each phase with the zero sequence using different compensation
factors for each zone.

In parallel lines, the distance units for ground faults correct the current measured in each phase with the neutral current using a mutual
compensation factor for each zone.

There are independent settings for each of the five zones (Table 2 and Table 3). Zone 1 has inductive tilting settings which do not exist
in the other zones (Table 2).

The reach of zone 1 can vary depending on the "Zone 1 extension" function.

❑ Nodes:
 Zone 1: PROT/PDIS1
 Zone 2: PROT/ZPDIS2
 Zone 3: PROT/ZPDIS3
 Zone 4: PROT/ZPDIS4
 Zone 5: PROT/ZPDIS5
There are 6 settings tables.

The settings used in these functions (Table 2 for zone 1 and Table 3 for the other zones) are as follows:

❑ Directional Mode. Indicates the direction of the characteristics. The directional supervision indicates the direction.

Ingeteam Power Technology S.A.


User Manual 41
PROTECTION FUNCTIONS

 Non directional (0). The unit acts as non-directional, in other words, directional supervision is disabled. In the
quadrilateral characteristic it operates forward and backwards, and in the Mho characteristic it operates forward
without being limited by directional supervision.
 Forward trip (1). It only operates with forward faults.
 Reverse trip (2). It only operates with backwards faults.
 Reverse start (3). It only operates with backwards faults. It does not generate trips, only starts.
 Forward start (4). It only operates with forward faults. It does not generate trips, only starts. This option is not found in
settings for zone 1.
❑ Characteristic angle (º). Indicates the characteristic angle.
❑ General trip. Indicates if this unit produces general trip or not. For additional details, see the section corresponding to the
recloser (3.12.6).
❑ Reclose Permission. Indicates whether each trip type can be reclosed or not, in accordance with the recloser's closing cycle
(See 6.2.3).
❑ Enable Events record. Allows the generation of protection events associated to the function. If set to “NO”, the function’s
protection events are not generated. If set to “YES”, the function’s specific mask is contemplated.
❑ Phase Enabled (Ph). Indicates whether or not the phase-phase characteristic is enabled.
❑ Phase Characteristic (Ph). Selects the phase-phase characteristic:
 Mho (0). Only the mho characteristic is enabled.
 Quadrilateral (1). Only the quadrilateral characteristic is enabled.
 Mho and Quad (2). Both characteristics are enabled.
❑ Phase Time (ms) (Ph). Indicates the time during which the conditions for the tripping must be met.
❑ Mho Reach (Ph). Indicates the reach of the mho phase-phase characteristic.
❑ Resistive Reach (Ph). Indicates the resistive reach of the quadrilateral phase-phase characteristic.
❑ X Reach Forward (Ph). Indicates the inductive reach forward of the quadrilateral phase-phase characteristic. If the
"Directional Mode" is set to reverse, the setting “X Reach Reverse (Ph)”is used.
❑ X Reach Reverse (Ph). Indicates the inductive reach backwards of the quadrilateral phase-phase characteristic. If the
"Directional Mode" is set to forward, the setting “X Reach Forward (Ph)”is used.
❑ R Blinder Angle (Ph). Indicates the slope angle of the resistive reach of the quadrilateral phase-phase characteristic.
❑ Block phase units (Ph). Selects the signal which, when active, blocks the phase-phase units.
❑ Enabled (Gnd). Indicates whether the phase-ground characteristic is enabled or not.
❑ Gnd Characteristic (Gnd). Selects the phase-ground characteristic:
 Mho (0). Only the mho characteristic is enabled.
 Quadrilateral (1). Only the quadrilateral characteristic is enabled.
 Mho and Quad (2). Both characteristics are enabled.
❑ Phase-ground time (ms). Indicates the time during which the conditions for the tripping must be met.
❑ Kn Module. Indicates the zero sequence compensation factor module.
❑ Kn Angle (º). Indicates the zero sequence compensation factor angle.
❑ Km Module. Indicates the mutual compensation factor module of the parallel lines.
❑ Km Angle (º). Indicates the parallel lines mutual compensation factor angle.
❑ Mho Reach (Gnd). Indicates the reach of the mho phase-ground characteristic.
❑ Resistive Reach (Gnd). Indicates the resistive reach of the quadrilateral phase-ground characteristic.
❑ X Reach Forward (Gnd). Indicates the inductive forward reach of the quadrilateral phase-ground characteristic. If the
"Directional Mode" is set to reverse, the setting “X Reach Reverse (Gnd)”is used.
❑ X Reach Reverse (Gnd). Indicates the inductive backwards reach of the quadrilateral phase-ground characteristic. If the
"Directional Mode" is set to forward, the setting “X Reach Forward (Gnd)”is used.

Ingeteam Power Technology S.A.


User Manual 42
PROTECTION FUNCTIONS

❑ R Blinder Angle (Gnd). Indicates the slope angle of the resistive reach of the quadrilateral phase-ground characteristic.
❑ Tilt Angle Gnd (º). Indicates the tilting angle of the resistive reach of the quadrilateral phase-ground characteristic. This
setting is only available for zone 1.
❑ Tilt Type (Gnd). Indicates the tilting type selected for the quadrilateral phase-ground characteristic. This setting is available
for zone 1.
 Disabled (0). Tilting is disabled.
 Time delayed (1). Enabled for the time selected, after fault detected.
 Continuous (2). Continuously enabled.
❑ Tilt Time Gnd (ms). Indicates the time during which inductive tilting of the phase-ground quadrilateral characteristic is
applied. This setting is available for zone 1.
❑ Quad. Type (Gnd). Indicates the quadrilateral unit polarization of the quadrilateral phase-ground characteristic.
 I0 (0). Zero sequence polarization.
 I2 (1). Negative sequence polarization.
 Max (I0, I2) (2). Polarization by the greater of the two (zero sequence and negative sequence).
❑ Block Gnd units. Selects the signal which, when active, blocks the phase-ground units.
❑ Block zone. Selects the signal which, when active, blocks the zone, in other words, the phase-ground and phase-phase
units.
❑ Timing type. Allows you to select how each zone's trip is delayed after the unit picks up (only zones 2, 3, 4 and 5). The
various modes are described in the section entitled "Timing Type".
❑ Ph-Ph Threshold (A)1. Each phase combination current must be above this value, to allow the corresponding phase-phase
distance unit of the zone. If it is set to zero, it is always allowed.
❑ Ph-Gnd Threshold (A)1. The phase current must be above this value, to allow the corresponding phase-gnd unit of the
distance zones selected as forward. If it is set to zero, it is always allowed.
❑ 3I0 Threshold (A) 1. The neutral current (3I0) must be above this value, to allow the phase-gnd distance unit of the zone. If
it is set to zero, it is always allowed.

1
Available since firmware version 6.2.19.3 and ICD 8.6.0.0

Ingeteam Power Technology S.A.


User Manual 43
PROTECTION FUNCTIONS

Table 2 Zone 1 Settings

Data Setting Minimum Maximum Step Remarks Type


Non Directional (0)
DirMod (OpType in Forward Trip (1)
Directional Mode enum
Ed2) Reverse Trip (2)
Reverse Start (3)
LinAng Characteristic Angle (º) 0 90 0.1 float
GenTrip General Trip NO / YES Boolean
NO (0)
Reclose 1 (1P) (1)
Reclose 1 (3P) (2)
Reclose 1 (1P/3P) (3)
ReclPerm Reclose permission 0 7 ING
Reclose 2-3-4 (4)
Reclose1(1P)-2-3-4 (5)
Reclose1(3P)-2-3-4 (6)
Reclose 1-2-3-4 (7)
MaskEna Enable Events Record NO / YES Boolean
PhEna Phase Enabled (Ph) NO / YES Boolean
Mho (0)
PhType Phase Characteristic (Ph) Quadrilateral (1) enum
Mho and Quad (2)
PhDlTmms Phase Time (ms) (Ph) 0 600000 10 int32
PhPoRch Mho reach (Ph) 0,05 500 0,01 float
RisPhRch Resistive Reach (Ph) 0,05 500 0,01 float
XPhRch X Reach Forward(Ph) 0,05 500 0,01 float
XPhRchB X Reach Reverse (Ph) 0,05 500 0,01 float
PhBlArg R Blinder Angle(Ph) 45 90 0.1 float
LogInPhBlk Block phase units (Ph) uint32
GndEna Enabled (Gnd) NO / YES Boolean
Mho (0)
GndType Gnd Characteristic (Gnd) Quadrilateral (1) enum
Mho and Quad (2)
GndDlTmms Phase-ground time (ms) 0 600000 10 int32
K0Fact Kn Module 0 10 0,01 float
K0FactAng Kn Angle (º) 0 359.9 0.1 float
K0MFact Km Module 0 10 0,01 float
K0MFactAng Km Angle(º) 0 359.9 0.1 float
GndPoRch Mho reach (Gnd) 0,05 500 0,01 float
RisGndRch Resistive Reach (Gnd) 0,05 500 0,01 float
XGndRch X Reach Forward(Gnd) 0,05 500 0,01 float
XGndRchB X Reach Reverse (Gnd) 0,05 500 0,01 float
GndBlArg R Blinder Angle(Gnd) 45 90 0.1 float
GndBaArg Tilt Angle Gnd (º) -10 10 1 float
Disabled (0)
GndTmType Tilt Type (Gnd) Time delayed (1) enum
Continuous (2)
GndBalTmms Tilt Time Gnd (ms) 0 500 10 int32
I0 (0)
GndPolType Quad. Type (Gnd) I2 (1) enum
Max(I0,I2) (2)
LogInGndBl Block Gnd units uint32
LogInBlk Block zone uint32
PhMinVal Ph-Ph Threshold (A) 0 150 0,01 float
GndMinVal Ph-Gnd Threshold (A) 0 150 0,01 float
I0MinVal 3I0 Threshold (A) 0 150 0,01 float

Ingeteam Power Technology S.A.


User Manual 44
PROTECTION FUNCTIONS

Table 3 Zones 2, 3, 4, and 5 Settings

Data Setting Minimum Maximum Step Remarks Type


Non Directional (0)
Forward Trip (1)
DirMod (OpType in
Directional Mode Reverse Trip (2) enum
Ed2)
Reverse Start (3)
Forward Start (4)
LinAng Characteristic Angle (º) 0 90 0.1 float
GenTrip General Trip NO / YES Boolean
NO (0)
Reclose 1 (3P) (2)
ReclPerm Reclose permission 0 7 ING
Reclose 2-3-4 (4)
Reclose 1-2-3-4 (7)
MaskEna Enable Events Record NO / YES Boolean
PhEna Phase Enabled (Ph) NO / YES Boolean
Mho (0)
PhType Phase Characteristic (Ph) Quadrilateral (1) enum
Mho and Quad (2)
PhDlTmms Phase Time (ms) (Ph) 0 600000 10 int32
PhPoRch Mho reach (Ph) 0,05 500 0,01 float
RisPhRch Resistive Reach (Ph) 0,05 500 0,01 float
XPhRch X Reach Forward (Ph) 0,05 500 0,01 float
XPhRchB X Reach Reverse (Ph) 0,05 500 0,01 float
PhBlArg R Blinder Angle(Ph) 45 90 0.1 float
LogInPhBlk Block phase units (Ph) uint32
GndEna Enabled (Gnd) NO / YES Boolean
Mho (0)
GndType Gnd Characteristic (Gnd) Quadrilateral (1) enum
Mho and Quad (2)
GndDlTmms Phase-ground time (ms) 0 600000 10 int32
K0Fact Kn Module 0 10 0,01 float
K0FactAng Kn Angle(º) 0 359.9 0.1 float
K0MFact Km Module 0 10 0,01 float
K0MFactAng Km Angle(º) 0 359.9 0.1 float
GndPoRch Mho reach (Gnd) 0,05 500 0,01 float
RisGndRch Resistive Reach (Gnd) 0,05 500 0,01 float
XGndRch X Reach Forward(Gnd) 0,05 500 0,01 float
XGndRchB X Reach Reverse (Gnd) 0,05 500 0,01 float
GndBlArg R Blinder Angle(Gnd) 45 90 0.1 float
I0 (0)
GndPolType Quad. Type (Gnd) I2 (1) enum
Max(I0,I2) (2)
LogInGndBl Block Gnd units uint32
LogInBlk Block zone uint32
Independent (0)
TimTyp Timing Type enum
Not Delayed (1)
PhMinVal Ph-Ph Threshold (A) 0 150 0,01 float
GndMinVal Ph-Gnd Threshold (A) 0 150 0,01 float
I0MinVal 3I0 Threshold (A) 0 150 0,01 float

❑ Commands There are 3 commands per zone:


 “DOrdBlk”: Block and unblock zone. Only acts when the function is enabled.
 “DOrdGBlk”: Block and unblock phase-ground units. Only acts when the function is enabled.
 “DOrdPhBlk”: Block and unblock phase-phase units. Only acts when the function is enabled.
❑ Outputs: Table 4 shows the function's output data (x can be 1, 2, 3, 4 and 5).
 Start Zx. Pickup by QUAD and/or MHO, where x is the zone. Indicates the distance unit (AN, BN, CN, AB, BC or CA)
which has started up. It is independent for each zone.
 Trip Zx. Trip by QUAD and/or MHO, where x is the zone. Indicates the distance unit (AN, BN, CN, AB, BC or CA) which
has tripped. It is independent for each zone.

Ingeteam Power Technology S.A.


User Manual 45
PROTECTION FUNCTIONS

 Start Mho Zx Y. Pickup by MHO, where x is the zone. Y indicates the distance unit (AN, BN, CN, AB, BC or CA) which has
started up It is independent for each zone.
 Trip Mho Zx Y. Trip by MHO, where x is the zone. Y indicates the distance unit (AN, BN, CN, AB, BC or CA) which has
tripped. It is independent for each zone.
 Start Quad Zx Y. Pickup by QUAD, where x is the zone. Y indicates the distance unit (AN, BN, CN, AB, BC or CA) which
has started up It is independent for each zone.
 Trip Quad Zx Y. Trip by QUAD, where x is the zone. Y indicates the distance unit (AN, BN, CN, AB, BC or CA) which has
tripped. It is independent for each zone.
 Start Zx single-phase. Single phase pickup by QUAD and/or Mho, where x is the zone. It is independent for each zone.
 Start Zx Phase-phase. Two phase pickup by QUAD and/or Mho, where x is the zone. It is independent for each zone.
 Trip Zx single-phase. Single phase trip by QUAD and/or Mho, where x is the zone. It is independent for each zone.
 Trip Zx Phase-phase. Two phase trip by QUAD and/or Mho, where x is the zone. It is independent for each zone.
 Zx start. Pickup by QUAD and/or Mho, where x is the zone. It is independent for each zone.
 Zx trip. Trip by QUAD and/or Mho trip, where x is the zone. It is independent for each zone.
 Mho zone x ph-gnd Status. Indicates the Mho phase-ground function’s status, where x is the zone. It is active when
enabled and not blocked. It is independent for each zone.
 Mho zone x ph-ph Status. Indicates the Mho phase-phase function’s status, where x is the zone. It is active when
enabled and not blocked. It is independent for each zone.
 Quad zone x ph-gnd Status. Indicates the Quad phase-ground function’s status, where x is the zone. It is active when
enabled and not blocked. It is independent for each zone.
 Quad zone x ph-ph Status. Indicates the Quad phase-phase function’s status, where x is the zone. It is active when
enabled and not blocked. It is independent for each zone.

Ingeteam Power Technology S.A.


User Manual 46
PROTECTION FUNCTIONS

Table 4 Mho and Quad Function Outputs

Signal Data (Edition 1) Attribute (Edition 1) Data (Edition 2) Attribute (Edition 2)


Start Zx AN Str phsA Str phsA
Start Zx BN Str phsB Str phsB
Start Zx CN Str phsC Str phsC
Start Zx AB Str phsAB StrAB general
Start Zx BC Str phsBC StrBC general
Start Zx CA Str phsCA StrCA general
Trip Zx AN Op phsA Op phsA
Trip Zx BN Op phsB Op phsB
Trip Zx CN Op phsC Op phsC
Trip Zx AB Op phsAB OpAB general
Trip Zx BC Op phsBC OpBC general
Trip Zx CA Op phsCA OpCA general
Start Mho Zx AN MStr phsA MStr phsA
Start Mho Zx BN MStr phsB MStr phsB
Start Mho Zx CN MStr phsC MStr phsC
Start Mho Zx AB MStr phsAB MStrAB general
Start Mho Zx BC MStr phsBC MStrBC general
Start Mho Zx CA MStr phsCA MStrCA general
Trip Mho Zx AN MOp phsA MOp phsA
Trip Mho Zx BN MOp phsB MOp phsB
Trip Mho Zx CN MOp phsC MOp phsC
Trip Mho Zx AB MOp phsAB MOpAB general
Trip Mho Zx BC MOp phsBC MOpBC general
Trip Mho Zx CA MOp phsCA MOpCA general
Start Quad Zx AN QStr phsA QStr phsA
Start Quad Zx BN QStr phsB QStr phsB
Start Quad Zx CN QStr phsC QStr phsC
Start Quad Zx AB QStr phsAB QStrAB general
Start Quad Zx BC QStr phsBC QStrBC general
Start Quad Zx CA QStr phsCA QStrCA general
Trip Quad Zx AN QOp phsA QOp phsA
Trip Quad Zx BN QOp phsB QOp phsB
Trip Quad Zx CN QOp phsC QOp phsC
Trip Quad Zx AB QOp phsAB QOpAB general
Trip Quad Zx BC QOp phsBC QOpBC general
Trip Quad Zx CA QOp phsCA QOpCA general
Start Zx single-phase GndStr general StrGnd general
Start Zx Phase-phase PhStr general StrPh general
Trip Zx single-phase GndOp general OpGnd general
Trip Zx Phase-phase PhOp general PhOp general
Start Zx Str general Str general
Trip Zx Op general Op general
Mho zone x ph-gnd Status PgndEna general PgndEna general
Mho zone x ph-ph Status PPhEna general PPhEna general
Quad zone x ph-gnd Status PgndEna general PgndEna general
Quad zone x ph-ph Status PPhEna general PPhEna general

Ingeteam Power Technology S.A.


User Manual 47
PROTECTION FUNCTIONS

3.1.1 Mho
The Mho characteristic is used with a cosine type phase comparator with Sop and Spol input phasors.

Hence, the signals used in each phase of the Mho characteristic are shown in Table 5. The operation zone must fulfil:

−90º ≤ angle (Sop/Spol) ≤ 90º


Table 5 Mho Characteristic Signals

Unit Sop (Operation signal) Spol (Polarization signal)


AN [ Ia + 3·I0  knx +IN2  kMx ] (|ZxGF|ZxAº) – Va Va1: current or memorized
BN [ Ib + 3·I0  knx +IN2  kMx ] (|ZxGF|ZxAº) – Vb Vb1: current or memorized
CN [ Ic + 3·I0  knx +IN2  kMx] (|ZxGF|ZxAº) – Vc Vc1: current or memorized
AB Iab  (|ZxF|ZxAº) – Vab Vab1: current or memorized
BC Ibc  (|ZxF|ZxAº) – Vbc Vbc1: current or memorized
CA Ica  (|ZxF|ZxAº) – Vca Vca1: current or memorized
Where:

❑ ZxGF: Phase-ground reach impedance, where x is the zone (one setting per zone). Set in ohms.
❑ ZxF: Phase-phase reach impedance, where x is the zone (one setting per zone). Set in ohms.
❑ ZxAº: Line characteristic angle, where x is the zone (one setting per zone). Set in degrees.
❑ Knx: Zero compensation constant, where x is the zone (one setting per zone).
1 zl0
K n = ( − 1)
3 zl1

❑ Kmx: Mutual compensation constant (double lines) where x is the zone (one setting per zone).
𝑍𝑚0
𝐾𝑚 =
3 · zl1

❑ Ia, Ib, Ic: Phase currents.


❑ Iab, Ibc, Ica: Phase - phase currents (Iab = Ia - Ib, Ibc = Ib - Ic, Ica = Ic - Ia).
❑ 3 I0: Calculated neutral current.
❑ IN2: Measured neutral current of the parallel line. Only for double lines.
❑ Va, Vb, Vc: Phase voltages.
❑ Vab, Vbc, Vca: Phase - phase voltages.
❑ Va1, Vb1, Vc1: Positive sequence voltages referred to each of the phases. The value will be determined by the supervision
of the memorization voltage (See section 3.3.3).
Equation 1

Va1 1
π
(Vb1) = (e1j·240180 ) · V1
π
Vc1 e1j·120180
❑ Vab1, Vbc1, Vca1: Positive sequence voltages referred to phase - phase voltages. The value will be determined by the
supervision of the memorization voltage (See section 3.3.3).
Equation 2

𝜋
𝑉𝑎𝑏1 𝑒1𝑗·30180
𝜋
( 𝑉𝑏𝑐1 ) = √3 (𝑒1𝑗·270180 ) 𝑉1
𝑉𝑐𝑎1 𝜋
𝑒1𝑗·150180
The voltages and currents used correspond to the type of fault being analysed; for example, for an A phase to ground fault, the
corresponding phasors will be Ia and Va, for an A and B phase - phase fault, they will be Iab and Vab.

Ingeteam Power Technology S.A.


User Manual 48
PROTECTION FUNCTIONS

The phase current used for single phase faults correspond to the current measured in each phase compensated with the zero
sequence. Double lines are also compensated with neutral current (mutual compensation factor).

Important: To operate, the phase current analysed has to be greater than 10% of the rated current when the rated current is 1A
and greater than 5% of the rated current when the rated current is 5A.

All of the Mho units are supervised by a reactance unit (Inductive X limit). In this way, the tendency for the Mho units to overreach
is prevented due to the influence of the load beforehand.

Zero compensation for double lines (km) is only applicable if the neutral current in the parallel line (IN2) is less than 1.35 times the
neutral current of the protected line (3I0).

If a pole is opened (from the trip), the positive sequence voltage will be calculated without taking into account the open pole's
phase voltage to avoid the distortion from discharging the line capacitors on this open phase. In other words, normally (with 3
poles closed) V1=1/3·(Va+a·Vb+a²·Vc)

If pole A is opened, V1 is calculated as V1=1/2·(0+a·Vb+a²·Vc) even if there is voltage in Va.

Memory is used according to polarization memory supervision. See section 3.3.3.

Figure 38 shows the forward, backwards and non-directional Mho characteristics.

Figure 39 shows the logic diagram of the Mho characteristic for units AN and AB forward.

❑ The other units function in a similar way.


❑ If the unit is configured backwards, the "Reverse" permissions are used.
❑ If the unit is configured as "Non directional", neither "Forward" nor "Backwards" permissions are used.
The input signals of this scheme are:

❑ Pole A open, Pole B open, Pole C open: Activated when the pole "x" is open. They are outputs of the function open pole
detector.
❑ Phase A open (I<), Phase B open (I<), Phase C open (I<): Indicates that the phase current is below the open pole detector
level. They are outputs of the function open pole detector.
❑ Perm. I>ZA Forward. It allows the protection unit AN for the zones configured as forward. It is output of the “MHO and
QUAD unit supervision”.
❑ Perm. I> ZAB Forward. The same as precious for phase AB.
❑ Selector AN. It is the signal “AN/BCN Selector” of the "Phase selector".
❑ Selector AB. It is the signal “CN/ABN Selector” of the "Phase selector".
❑ Fuse failure start. Blocked by the fuse failure start signal.
❑ Power swing blocking. Blocked by the Power swing detector.
❑ Open Pole. Indicates, there´s any pole open. It is output of the function open pole detector.
❑ Load Encroachment. Blocked by the load Encroachment signal.

Ingeteam Power Technology S.A.


User Manual 49
PROTECTION FUNCTIONS

Figure 38 Mho Characteristics

Ingeteam Power Technology S.A.


User Manual 50
PROTECTION FUNCTIONS

Figure 39 Mho Logic Diagram

3.1.2 Quadrilateral
The Quadrilateral characteristic is used by making two comparisons for each zone and for each single phase component:

❑ The resistive component of each impedance with the corresponding "Resistive Reach" setting.
❑ The inductive component of each impedance with the corresponding "X Reach forward" or "X Reach reverse" (depending
on the sign and on the "Directional Mode" setting).

The resistive component of the impedance is calculated as follows:

Vpol
R = Re ( )
Ieq

Ingeteam Power Technology S.A.


User Manual 51
PROTECTION FUNCTIONS

The inductive component of the impedance is calculated as follows:


̅̅̅̅̅]
Im[Vpol · Ipol
X = Im(ZL1) ·
Im[ZL1 · (Ieq · ̅̅̅̅̅
Ipol)]

For single phase units in zone 1, the inductive component is calculated as follows:
̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅
Im[Vpol · (Ipol · 1∠Z1BASCA˚)]
X = Im(ZL1)Ÿ ·
̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅
Im [ZL1 · (Ieq · (Ipol · 1∠Z1BASCA˚))]

Where:

❑ Vpol: Unit's voltage.


❑ Ieq: Unit's current in the case of single phases corresponding to the compensated current.
❑ ZL1: Line impedance characterised by the "Characteristic angle (º)" (setting).
❑ Z1BASCAº : "Tilt Angle Gnd (º)" (setting). Only for zone 1 and single-phase units.
❑ Ipol: Polarization current.

The intervention of the tilt angle is regulated by two settings (only zone 1 and single phase units):

❑ Tilt type (Gnd): If defined as "Disabled", this angle's value is always 0. If defined as "Time delayed", this angle maintains its
setting value during the time indicated in the setting "Tilt time Gnd (ms)". If defined as "Continuous" it always keeps its
setting value.
❑ Tilt time Gnd (ms): Time, in ms, for applying the tilt angle after the fault detection, only if the setting "Tilt type (Gnd)" is set
as "Time delayed".

Important: To operate, the phase current analysed must be greater than 10% of the rated current.

Figure 40 shows the forward, backwards and non-directional quadrilateral characteristics.

The signals used in each phase of the Quadrilateral characteristic are shown in Table 6. The operation zone must be such that these
two components are less than the set reach.

Table 6 Quadrilateral Characteristic Signals

Unit Ieq Vpol Ipol


AN [ Ia + 3·I0  knx +IN2  kMx ] Va 3I0, 3I2 or Max(3I0, 3i2)
BN [ Ib + 3·I0  knx +IN2  kMx ] Vb 3I0, 3I2·a or Max(3I0, 3I2·a)
CN [ Ic + 3·I0  knx +IN2  kMx] Vc 3I0, 3I2·a2 or Max(3I0, 3I2·a2)
AB Iab Vab I2·a2·j or Iab
BC Ibc Vbc I2·j or Ibc
CA Ica Vca I2·a·j or Ica

Where:

❑ Knx: Zero compensation constant, where x is the zone (one setting per zone). Same setting as for Mho.
❑ Kmx: Mutual compensation constant (double lines), where x is the zone (one setting per zone). Same setting as for Mho.
❑ Ia, Ib, Ic: Phase currents.
❑ Iab, Ibc, Ica: Phase - phase currents (Iab = Ia - Ib, Ibc = Ib - Ic, Ica = Ic - Ia).
❑ 3 I0: Calculated neutral current.
❑ IN2: Measured neutral current of the parallel line. Only for double lines.
❑ Va, Vb, Vc: Phase voltages.
❑ Vab, Vbc, Vca: Phase - phase Voltages.
❑ I2: Negative sequence of the current calculated using the phase currents.

Ingeteam Power Technology S.A.


User Manual 52
PROTECTION FUNCTIONS

In the case of single phases faults, the polarization current (Ipol) for each phase is chosen according to the "Quad. type (Gnd)"
setting. There are three possible options: zero sequence, negative sequence, and the maximum of both.

In the case of the phase - phase ones, the polarization current applied is always the negative sequence current, unless the value of
the negative sequence is less than the 25%2 of the positive sequence or less than the 5% of the rated current or the current of the
three phases is greater than three times the rated current. In that case, the current between the two phases is used.

The zero compensation and the memory are applied following the same conditions as for the Mho characteristic.

The Figure 41 shows the logic diagram of the quadrilateral characteristic for units AN and AB forward.

The other units function in a similar way.

❑ If the unit is configured backwards, the "Reverse" permissions are used.


❑ If the unit is configured as "Non directional", neither "Forward" nor "Backwards" permissions are used.
The input signals of this scheme are:

❑ Pole A open, Pole B open, Pole C open: Activated when the pole "x" is open. They are outputs of the function open pole
detector.
❑ Phase A open (I<), Phase B open (I<), Phase C open (I<): Indicates that the phase current is below the open pole detector
level. They are outputs of the function open pole detector.
❑ Perm. I>ZA Forward. It allows the protection unit AN for the zones configured as forward. It is output of the “MHO and
QUAD unit supervision”.
❑ Perm. I> ZAB Forward. The same as precious for phase AB.
❑ Selector AN. It is the signal “AN/BCN Selector” of the "Phase selector".
❑ Selector AB. It is the signal “CN/ABN Selector” of the "Phase selector".
❑ Perm. dir IA Forward. Forward directional permission for phase A. Function "Directional supervision".
❑ Perm. dir IAB Forward. The same as precious for phase AB.
❑ Fuse failure start. Blocked by the fuse failure start signal.
❑ Power swing blocking. Blocked by the Power swing detector.
❑ Open Pole. Indicates, there´s any pole open. It is output of the function open pole detector.
❑ Load Encroachment. Blocked by the Load Encroachment signal.

2
Available from DSP firmware version 4.1. Upto this version the limit was 10%.

Ingeteam Power Technology S.A.


User Manual 53
PROTECTION FUNCTIONS

Figure 40 Quad Characteristics

Forward Reverse

Non directional

Ingeteam Power Technology S.A.


User Manual 54
PROTECTION FUNCTIONS

Figure 41 Logic Diagram for the Quad Characteristic

3.1.3 Timing Type for Tripping


The timing type for tripping indicates how the timing takes place from the start to the trip. This setting can only be selected in the
timed zones: 2, 3, 4 and 5.

There are two ways of tripping the distance units:

❑ Not delayed. This means that different starts in different phases do not delay the trip. For example, if a start takes place in
phase A and the start condition disappears in this phase, but phase B starts, timing continues. Hence, the trip is not
delayed.

Ingeteam Power Technology S.A.


User Manual 55
PROTECTION FUNCTIONS

❑ Independent. Each phase has an independent timer. For example, if a start takes place in phase A and the start condition
disappears in this phase, but phase B starts, timing for tripping starts again.
In zone 1 (not timed), the "Independent" mode is always applied.

The condition for activating a unit (prior to the trip) is activated if there is a startup in any of the units (this is the case in "Not
delayed" mode) or in the specific unit (this is the case in the "Independent" mode) and the corresponding timing is fulfilled.

In the case of the "Independent" mode, once the corresponding condition for activating the unit has been activated, a seal is
applied so that the condition is not deactivated while there is an overcurrent (only in zones 2, 3, 4 and 5).

In order for a unit to trip, besides the unit having to be activated, there must be a closed phase or V1>80%Vrated for 1/4 cycle.

Figure 42 shows the logic diagram for trip mode without a delay between phases.

The input signals of this scheme are:

❑ Pole A open, Pole B open, Pole C open: Activated when the pole "x" is open. They are outputs of the function open pole
detector.
❑ Phase A open (I<), Phase B open (I<), Phase C open (I<): Indicates that the phase current is below the open pole detector
level. They are outputs of the function open pole detector.
❑ Selector AN/BCN. Enables AN and BC units and blocks the other units. It is the signal “AN/BCN Selector” of the "Phase
selector".
❑ Selector BN/CAN. Enables BN and CA units and blocks the other units. It is the signal “BN/CAN Selector” of the "Phase
selector".
❑ Selector CN/ABN. Enables CN and AB units and blocks the other units. It is the signal “CN/ABN Selector” of the "Phase
selector".
❑ Zone n start AN. Indicated that the AN unit of the zone has started.
❑ Zone n start BN. The same as precious for phase BN.
❑ Zone n start CN. The same as precious for phase CN.
❑ Zone n start AB. The same as precious for phase AB.
❑ Zone n start BC. The same as precious for phase BC.
❑ Zone n start CA. The same as precious for phase CA.
❑ IA>IA Forward. It is the signal "Perm. IA Forward" of the function Overcurrent supervision.
❑ IB>IB Forward. The same as precious for phase B.
❑ IC>IC Forward. The same as precious for phase C.
❑ IAB>IAB Forward. The same as precious for phase AB.
❑ IBC>IBC Forward. The same as precious for phase BC.
❑ ICA>ICA Forward. The same as precious for phases CA.

Figure 44 shows the logic diagram for the independent trip mode for zone 1 in single phase units.

Figure 43 shows the logic diagram for the independent trip mode for zone 1 in two phase units.

Ingeteam Power Technology S.A.


User Manual 56
PROTECTION FUNCTIONS

Figure 42 Logic Diagram for Tripping without a Delay between Phases.

Figure 43 Logic Diagram for Two Phase Independent Trip

Ingeteam Power Technology S.A.


User Manual 57
PROTECTION FUNCTIONS

Figure 44 Logic Diagram for Single Phase Independent Trip

3.1.4 Zone 1 Extension


The zone 1 extension makes possible to vary the reach of the zone 1 in the first trip, returning to the set reach for the successive
trips. The zone 1 extension is applied when it is enabled and the recloser is in standby and it is not extended after the first reclose.

Zone 1 cannot be extended when the recloser is disabled or blocked.

It is applied to the mho and quadrilateral characteristics, there is an independent compensation factor for ground faults and for
phase - phase faults.

The settings are as follows:

❑ Enabled: Enables and disables the function.


❑ Gnd extension ratio: Factor by which the phase-ground reach setting of zone 1's Mho and Quad characteristics are
multiplied.
❑ Ph - ph extension ratio: Factor by which the phase-phase reach setting of zone 1's Mho and Quad characteristics are
multiplied.
❑ Blocking input: Selects the signal which, when active, blocks the zone extension.
❑ Enable Events record. Allows the generation of protection events associated to the function. If set to “NO”, the function’s
protection events are not generated. If set to “YES”, the function’s specific mask is contemplated.
There are settings, commands and outputs:

Ingeteam Power Technology S.A.


User Manual 58
PROTECTION FUNCTIONS

❑ Node: PROT/RZEX1
❑ Settings and logical inputs. There are 6 settings tables. For details, see Table 7.
❑ Commands:
 “DOrdBlk”: Blocks and unblocks the function. Only acts when the function is enabled.
❑ Outputs: Table 8 shows the function's output data.
 Zone 1 Extension: Indicates that the zone extension is activated.
 Zone 1 Extension Status: Indicates the function’s status. It is active when enabled and not blocked.

Table 7 Zone 1 Extension Settings

Data Setting Minimum Maximum Step Remarks Type


Ena Enabled NO / YES enum
Z1GVal Gnd extension ratio 0,1 3 0,001 float32
Z1Gval Ph-Ph extension ratio 0,1 3 0,001 float32
LoghBlk Blocking input uint32
MaskEna Enable Events Record NO / YES Boolean

Table 8 Zone 1 Extension Outputs

Signal Data Attribute


Zone 1 Extension Z1Ext general
Zone 1 Extension Status StEna general (stVal in Ed2)

Figure 45 shows the logic diagram corresponding to the zone 1 extension.

The recloser signals used in this function are:

❑ Recloser in standby. Indicates the recloser is in standby status.


❑ Reclosing 1 in progress. Indicates the recloser´s cycle 1 is ongoing.
❑ Safety time 1st reclosing. Indicates the recloser is in safety time after the first reclose.
❑ Recloser Blocked. Indicates the recloser is blocked.

Figure 45 Zone 1 Extension Logic Diagram

Setting
ENABLED = YES

DIGITAL INPUT
Blocking input

DIGITAL SIGNAL
Recloser in standby WORKING SETTING
Working Z1GF=Z1GF·Gnd extension ratio
DIGITAL SIGNAL Working Z1F =Z1F·Ph-Ph extension ratio
Reclosing 1 in progress
WORKING SETTING
DIGITAL SIGNAL Working Z1GF=Z1GF
Safety time 1st reclosing Working Z1F =Z1F

DIGITAL SIGNAL
Recloser Blocked

3.1.5 High Speed zone


There is a high speed operation unit for zone 1 (only forward) and another one for zone 4 (only backwards), based on the half cycle
DFT, for both characteristics (Mho and Quad).

The high speed zone 1 can only be active if zone 1 is programmed forward and enabled.

Ingeteam Power Technology S.A.


User Manual 59
PROTECTION FUNCTIONS

The high speed zone 4 will only be active if zone 4 is programmed backwards and enabled.

The high speed zone is made by including an internal zone in zone 1 and zone 4 such as that |X|<80%ZxF, |R|<20%ZxF, where ZxF is
the reach of the corresponding zone.

The settings are as follows:

❑ Zone 1 enabled: Indicates whether the high speed zone 1 is enabled or not.
❑ Zone 4 enabled: indicates whether the high speed zone 4 is enabled or not.
❑ Zone 1 Blocking input: Selects the signal which, when active, blocks the high speed zone 1.
❑ Zone 4 Blocking input: Selects the signal which, when active, blocks the high speed zone 4.
❑ Enable Events record. Allows the generation of protection events associated to the function. If set to “NO”, the function’s
protection events are not generated. If set to “YES”, the function’s specific mask is contemplated.

There are settings and outputs.

❑ Node: PROT/PHSZ1
❑ Settings and logical inputs. There are 6 settings tables. For details, see Table 9.
❑ Outputs: Table 10 shows the function's output data.
 High speed zone 1: Indicates whether or not the high speed zone 1 is enabled and not blocked.
 High speed zone 4: Indicates whether or not the high speed zone 4 is enabled and not blocked.

Table 9 High Speed Operation Zone Settings

Data Setting Minimum Maximum Step Remarks Type


Z1QEna Zone 1 enabled NO / YES enum
Z4QEna Zone 4 enabled NO / YES enum
LogInZ1Bl Zone 1 Blocking input uint32
LogInZ4Bl Zone 4 Blocking input uint32
MaskEna Enable Events Record NO / YES Boolean

Table 10 High Speed Zone Outputs Edition 1

Signal Data Attribute


High speed zone 1 StEna1 general
High speed zone 4 StEna4 general

Table 11 High Speed Zone Outputs Edition 2

Signal Data Attribute


High speed zone 1 StEna1 stVal
High speed zone 4 StEna4 stVal

Figure 46 shows the Mho and Quad characteristics of the high speed zone 1.

Ingeteam Power Technology S.A.


User Manual 60
PROTECTION FUNCTIONS

Figure 46 High speed zone Mho and Quad Characteristics

Figure 47 shows the functional logic diagram of the high speed operation Mho characteristic.

The input signals of this function are the indicated in the mho and quadrilateral units.

Ingeteam Power Technology S.A.


User Manual 61
PROTECTION FUNCTIONS

Figure 47 Logic Diagram for the High Speed Mho Characteristic

Ingeteam Power Technology S.A.


User Manual 62
PROTECTION FUNCTIONS

3.1.6 Phase selector


The phase selector determines the fault type, allowing the trip as a result of this and blocking the others. The phases involved in the
fault are selected as follows:

Two conditions are defined:

Condition 1 (3 · I0 > 5% ∙ 𝐼𝑟𝑎𝑡𝑒𝑑 𝑝ℎ𝑎𝑠𝑒)&(3 · 𝐼0 > 10% ∙ 𝐼1) (1)

Zero sequence current greater than 5% of Irated (0.25A for Irated=5A and 0.05A for Irated=1A) and the percentage must be greater
than the 10% of the maximum phase current.

Condition 2 (3 · I2 > 5% ∙ 𝐼𝑟𝑎𝑡𝑒𝑑 𝑝ℎ𝑎𝑠𝑒)&(𝐼2 > 10% ∙ 𝐼1) (2)

Negative sequence current greater than 5% of Irated (0.25A for Irated=5A and 0.05A for Irated=1A) and the percentage must be
greater than the 10% of the positive sequence.

THREE PHASE FAULTS

It has to fulfil at least one of the following conditions:

❑ If neither (1) nor (2) are fulfilled.


❑ The values of the phase-phase currents minus their prefault values are analysed. The three of them must be greater than
the 70% of the maximum value.
The three zones Zxab, Zxbc, Zxca must be simultaneously failing for a three-phase fault to be signalled (even if the three phase-
phase units are enabled, it will not be signalled unless this condition is fulfilled).

TWO PHASE FAULTS

If only (2) is fulfilled, the fault is phase-phase.

When the fault detector is disabled, all the phase-phase units are enabled.

When the fault detector is enabled, the angle is analysed to determinate the faulted phases:

𝐴𝑛𝑔𝑙𝑒 = a𝑛𝑔𝑙𝑒(𝐼2 ) − a𝑛𝑔𝑙𝑒(∆𝐼1 )

Where:

❑ I1 is the positive sequence current. Fault current minus prefault current.


❑ I2 in the negative sequence current.
The prefault value is captured from the fault detector. When the fault is detected, the previous 2 cycles of the current are captured.
This value is subtracted to the fault positive sequence.

Figure 48 Two phases fault identifier

SINGLE PHASE OR TWO PHASE TO GROUND FAULTS

If (1) and (2) are fulfilled, the fault is to ground (single phase or phase - phase). In this case, the angular selector becomes involved.

If the angles are not involved, the detection is made by voltages.

Ingeteam Power Technology S.A.


User Manual 63
PROTECTION FUNCTIONS

If a single phase / two phase fault to ground is detected, only the units involved will be enabled. If it is a CN/ABN, units CN and AB
are enabled and the others are blocked.

Figure 49 Phase Identifier

UNDETERMINED IDENTIFICATION

If (1) is fulfilled but (2) is not, all of the units will be enabled, since the relay cannot determine what type of fault is processed.

67NQ SINGLE PHASE FAULTS3

In the 67NQ teleprotection scheme, single pole trips are allowed. In case of single phase or two phase to ground faults, another
selector is used to determinate the fault type.

The angle is analysed to determinate the fault type:

𝐴𝑛𝑔𝑙𝑒 = a𝑛𝑔𝑙𝑒(𝐼2 ) − a𝑛𝑔𝑙𝑒(∆𝐼1 )

Where:

❑ I1 is the positive sequence current. Fault current minus prefault current.


❑ I2 in the negative sequence current.

Figure 50 AN and BCN fault identifier Figure 51 BN and CAN fault identifier Figure 52 CN and ABN fault identifier

All of the units will be enabled if there is an open pole, in other words, if a single-pole opening has occurred.

Outputs are available.

❑ Node: PROT/DISPTRC1
❑ Outputs: Table 12 shows the output data.
 AN/BCN Selector: Enables the AN and BC units and blocks the others.
 BN/CAN Selector: Enables the BN and CA units and blocks the others.

3
Available from firmware version 6.0.8.0 and ICD version 8.1.0.4

Ingeteam Power Technology S.A.


User Manual 64
PROTECTION FUNCTIONS

 CN/ABN Selector: Enables the CN and AB units and blocks the others.
 Unknown Fault: Enables all of the units.
 ABC Fault: Enables units AB, BC and CA. This is only indicated if there has been a simultaneous fault in AB, BC and CA.
 Phase - Phase Fault: Enables the phase-phase units.
 Ground fault: It is activated when there is a ground fault.
 AN Selector3: Enables the AN unit and blocks the others.
 BN Selector3: Enables the BN unit and blocks the others.
 CN Selector3: Enables the CN unit and blocks the others.
 AB Selector3: Enables the AB unit and blocks the others.
 BC Selector3: Enables the BC unit and blocks the others.
 CA Selector3: Enables the CA unit and blocks the others.

Table 12 Phase Identifier Outputs

Signal Data (Edition 1) Attribute (Edition 1) Data (Edition 2) Attribute (Edition 2)


AN/BCN Selector PhId PhANBCN PhAnBCn stVal
BN/CAN Selector PhId PhBNCAN PhBnCAn stVal
CN/ABN Selector PhId PhCNABN PhCnABn stVal
Unknown Fault UnFa general UnFa general
ABC Fault ABCFaDet general ABCFltDet general
Phase - Phase Fault PhFaDet general PhFltDet general
Ground Fault GndFaDet general GndFltDet general
AB Selector PhAB stVal PhAB stVal
BC Selector PhBC stVal PhBC stVal
CA Selector PhCA stVal PhCA stVal
AN Selector PhAN stVal PhAN stVal
BN Selector PhBN stVal PhBN stVal
CN Selector PhCN stVal PhCN stVal

Figure 53 shows the phase identifier’s logic diagram.

The input signals of this scheme are:

❑ Pole A open, Pole B open, Pole C open: Activated when the pole "x" is open. They are outputs of the function open pole
detector.
If any of the poles is open, the phase selector is not taken into account. In this case, the loops containing the open pole are blocked.
E.g.: If the open pole is A, loops AB, CA and AN are blocked. The trip will be three-pole.

In the case of a three-phase opening, if only the breaker status generic input is programmed (not by pole); the phase selector
continues being used. In other words, only the phase selector is disabled in the case of a single-phase opening. In this case, the fault
type is defined by the active distance units. If any of the phase-phase distance units is activated, a phase-phase fault will be
indicated.

Ingeteam Power Technology S.A.


User Manual 65
PROTECTION FUNCTIONS

Figure 53 Phase Identifier's Logic Diagram

3.1.7 Fault detection


This function detects the start of the fault by checking the differences in the actual zero sequence, positive sequence and negative
sequence currents, with those in two cycles before.

It is activated when:

❑ The difference between the actual measurement of the current's positive sequence (I1) and the measurement two cycles
beforehand exceeds the 10% of the rated current and one of the following conditions is fulfilled:
 The difference between the current measurement of the negative sequence of the current (I2) and the
measurement two cycles before exceeds 4% of the rated current.
 The difference between the current measurement of the zero sequence of the current (I0) and the
measurement two cycles before exceeds 4% of the rated current.
 The positive sequence of the current (I1) increases by more than 25% compared to two cycles before.
When one of these thresholds is exceeded or if the phase selector identifies a fault which is not three-phase, the fault detector is
activated. The fault detector stays active for 30ms after the previous situation disappears. If a distance unit or an overcurrent
startup occurs while the fault detector is active, the fault detector will stay active for 30 ms after the trip disappears.

Table 13 shows the output data.

❑ Node: PROT/DISPTRC1
❑ Outputs. Table 13 shows the output data.
 Fault detection: Indicates a fault has been detected.
Table 13 Fault Detector Outputs.

Signal Data (Edition 1) Attribute (Edition 1) Data (Edition 2) Attribute (Edition 2)


Fault detection FaDet general FltDet general

Ingeteam Power Technology S.A.


User Manual 66
PROTECTION FUNCTIONS

Figure 54 shows the functional logic diagram of the fault detector.

The input signals of this scheme are:

❑ 2 Phase Fault. It is the signal "Phase - Phase Fault" of the Phase selector.
❑ Ground fault. It is the signal "Ground fault" of the Phase selector.
❑ Start signals. Indicates that any of the started units generate the general start signal.
Figure 54 Fault Detector's Logic Diagram

3.1.8 Mho and Quadrilateral Unit Supervision


The supervision unit disables the startup of the MHO and QUAD units, differentiating between single-phase and phase-phase units.

Figure 55 shows the supervision logic diagram for single-phase units.

Single-Phase Units. The blocking conditions for phase-ground units are as follows:

❑ If the phase identifier does not detect the fault in the corresponding loop.

Ingeteam Power Technology S.A.


User Manual 67
PROTECTION FUNCTIONS

❑ If ((3·I0>5%·Irated phase) AND (3·I0>10%·I1)) is not fulfilled. Phase identifier condition 1.


❑ No current can be seen in the single-phase unit's phase ("detection logic of the open pole by current").
❑ Ia, Ib, Ic (as corresponds) must be 10% greater than Irated for In=1A and 5% for In=5A, even if the supervision by means of
overcurrent is not been used.
❑ If the power swing function is activated and if it is programmed for this.
❑ If the fuse failure function is activated.
❑ If the polarization voltage is less than 2V. Supervision is in directional supervision mode.
❑ If the overcurrent supervision (only single phase units) is enabled, when the phase current or the neutral current (3·I0), are
less than the phase threshold and neutral threshold of the selected direction for that zone.
❑ If there is no directional permission. The phase-ground units are supervised by the polarised directional units by phase
currents, by negative sequence and by zero sequence. In the case of an open pole, only phase current polarizations are
used.
The input signals of these schemes are:

❑ Pole A open, Pole B open, Pole C open: Activated when the pole "x" is open. They are outputs of the function open pole
detector.
❑ Phase A open (I<), Phase B open (I<), Phase C open (I<): Indicates that the phase current is below the open pole detector
level. They are outputs of the function open pole detector.
❑ Fuse failure start. Blocked by the fuse failure start signal.
❑ Load Encroachment. Blocked by the Load Encroachment signal.

Ingeteam Power Technology S.A.


User Manual 68
PROTECTION FUNCTIONS

Figure 55 Logic Diagram from Single-Phase Unit Supervision

Figure 56 shows the supervision logic diagram for phase-phase units.

Phase-phase units. The blocking conditions for phase-phase units are as follows:

❑ If the phase selector does not detect the fault in the corresponding loop.
❑ No current is detected in one of the unit phases. If there is no current in A, neither unit AB nor CA unit are activated
("detection logic for open pole by current").
❑ Iab, Ibc, Ica must be 10% greater than Irated for In=1A and 5% for In=5A, even if the overcurrent supervision is not been
used.
❑ If the power swing function is activated and if it is programmed for this.
❑ If the fuse failure function is activated.
❑ If the polarization voltage is less than 2V. Supervision is in directional supervision mode.
❑ If phase-phase unit overcurrent supervision has been enabled. If the phase-phase overcurrent of the direction
corresponding to the zone is not exceeded. The threshold must be exceeded in each phase of the ones involved in the unit
(e.g. in unit AB, currents of phases A and B and AB.

Ingeteam Power Technology S.A.


User Manual 69
PROTECTION FUNCTIONS

❑ If the "load encroachment" unit is activated.


❑ If there is no directional permission.
Figure 56 Logic Diagram from Phase-Phase Unit Supervision

The settings are as follows:

❑ Enable Events record. Allows the generation of protection events associated to the function. If set to “NO”, the function’s
protection events are not generated. If set to “YES”, the function’s specific mask is contemplated.
There are settings and outputs.

Ingeteam Power Technology S.A.


User Manual 70
PROTECTION FUNCTIONS

❑ Node: PROT/DISPTRC1
❑ Settings and logical inputs. There are 6 settings tables. For details, see Table 14.
❑ Outputs: Table 15 shows the output data.
 Permission I>ZA Forward. Indicates that it allows the AN distance unit to operate for zones programmed forward.
 I>ZB Forward Permission. Indicates that it allows the BN distance unit to operate for zones programmed forward.
 I>ZC Forward Permission. Indicates that it allows the CN distance unit to operate for zones programmed forward.
 I>ZAB Forward Permission. Indicates that it allows the AB distance unit to operate for zones programmed forward.
 I>ZBC Forward Permission. Indicates that it allows the BC distance unit to operate for zones programmed forward.
 I>ZCA Forward Permission. Indicates that it allows the CA distance unit to operate for zones programmed forward.
 I>ZA Reverse Permission. Indicates that it allows the AN distance unit to operate for zones programmed backwards.
 I>ZB Reverse Permission. Indicates that it allows the BN distance unit to act. For zones programmed backwards.
 I>ZC Reverse Permission. Indicates that it allows the CN distance unit to operate for zones programmed backwards.
 I>ZAB Reverse Permission. Indicates that it allows the AB distance unit to operate for zones programmed backwards.
 I>ZBC Reverse Permission. Indicates that it allows the BC distance unit to operate for zones programmed backwards.
 I>ZCA Reverse Permission. Indicates that it allows the CA distance unit to operate for zones programmed backwards.
Table 14 MHO and QUAD Unit Supervision Settings

Data Setting Minimum Maximum Step Remarks Type


MaskEna Enable Events Record NO / YES Boolean

Table 15 MHO and QUAD Unit Supervision Outputs

Signal Data (Edition 1) Attribute (Edition 1) Data (Edition 2) Attribute (Edition 2)


Perm. I> ZA Forward ZFw phsA ZFw phsA
Perm. I> ZB Forward ZFw phsB ZFw phsB
Perm. I> ZC Forward ZFw phsC ZFw phsC
Perm. I> ZAB Forward ZFw phsAB ZFwAB general
Perm. I> ZBC Forward ZFw phsBC ZFwBC general
Perm. I> ZCA Forward ZFw phsCA ZFwCA general
Perm. I> ZA Reverse ZRv phsA ZRv phsA
Perm. I> ZB Reverse ZRv phsB ZRv phsB
Perm. I> ZC Reverse ZRv phsC ZRv phsC
Perm. I> ZAB Reverse ZRv phsAB ZRvAB general
Perm. I> ZBC Reverse ZRv phsBC ZRvBC general
Perm. I> ZCA Reverse ZRv phsCA ZRvCA general

3.1.8.1 Overcurrent Supervision


This unit supervises the startup of the MHO and QUAD units. If a series of conditions, which depend on the settings, are not
fulfilled, it disables the startup of the corresponding units. The settings are independent for phase-ground, phase-phase,
forward and backwards.

Single-Phase Units:

Supervises the phase-ground units of the distance characteristics (mho and quadrilateral).

It is used to measure each phase measurement and neutral measurement (In or 3I0 as selected).

It compares the current of each phase with the threshold established as the setting, activating when it is exceed and
deactivating when it is lower than 95%. The analysis is made for each phase independently, generating an output per phase,
which allows the distance units of each phase to operate if the current measured is greater than the threshold and disables it
otherwise.

Ingeteam Power Technology S.A.


User Manual 71
PROTECTION FUNCTIONS

To have permission in a phase, both the measurements of the phase and of the neutral (3I0) must exceed their corresponding
thresholds.

The settings are as follows:

❑ Enabled: Enables and disables the function:


❑ Phase Forward threshold (A): the phase current must be above this value, to allow the corresponding phase-gnd unit of
the distance zones selected as forward.
❑ Phase Reverse threshold (A): the phase current must be above this value, to allow the corresponding phase-gnd unit of the
distance zones selected as backwards.
❑ 3I0 Forward threshold (A): the neutral current (3I0) must be above this value, to allow the phase-gnd distance zones
selected as forward.
❑ 3I0 Reverse threshold (A): the neutral current (3I0) must be above this value, to allow the phase-gnd distance zones
selected as backwards.
❑ Blocking input: Selects the signal which, when active, blocks single-phase overcurrent supervision.
❑ Enable Events record. Allows the generation of protection events associated to the function. If set to “NO”, the function’s
protection events are not generated. If set to “YES”, the function’s specific mask is contemplated.
There are settings, commands and outputs:

❑ Node: PROT/GRZOS1
❑ Settings and logical inputs. There are 6 settings tables. For details, see Table 16.
❑ Commands:
 “DOrdBlk”: Blocking and unblocking of single-phase overcurrent supervision. Only acts when the function is enabled.
❑ Outputs: Table 17 shows the function's output data.
 IA Forwards Permission. Indicates that the overcurrent supervision allows the AN distance unit to act (for zones
programmed forward).
 IB Forwards Permission. Indicates that the overcurrent supervision allows the BN distance unit to act (for zones
programmed forward).
 IC Forwards Permission. Indicates that the overcurrent supervision allows the CN distance unit to act (for zones
programmed forward).
 IA Reverse Permission. Indicates that the overcurrent supervision allows the AN distance unit to act (for zones
programmed backwards).
 IB Reverse Permission. Indicates that the overcurrent supervision allows the BN distance unit to act (for zones
programmed backwards).
 IC Reverse Permission. Indicates that the overcurrent supervision allows the CN distance unit to act (for zones
programmed backwards).
 Gnd supervision status. Indicates that phase-ground overcurrent supervision is activated and not blocked.

Table 16 Single-Phase Overcurrent Settings

Data Setting Minimum Maximum Step Remarks Type


Ena Enabled NO / YES enum
FwPhVal Phase Forward threshold (A) 0,05 150 0,01 float32
RvPhVal Phase Reverse threshold (A) 0.05 150 0,01 float32
FwNVal 3I0 Forward threshold (A) 0.05 150 0.01 float32
RvNVal 3I0 Reverse threshold (A) 0.05 150 0.01 float32
LoghBlk Blocking input uint32
MaskEna Enable Events Record NO / YES Boolean

Ingeteam Power Technology S.A.


User Manual 72
PROTECTION FUNCTIONS

Table 17 Single-Phase Unit Overcurrent Outputs

Signal Data Attribute


Perm. IA Forward IFw phsA
Perm. IB Forward IFw phsB
Perm. IC Forward IFw phsC
Perm. IA Reverse IRv phsA
Perm. IB Reverse IRv phsB
Perm. IC Reverse IRv phsC
Gnd Supervision Status StEna general (stVal in Ed2)

Phase-Phase Units:

Supervises the phase-phase units of the distance characteristics (mho and quadrilateral).

It compares the phase - phase current of each two phases and the current of each phase with the threshold established as the
setting, activating when it exceeds it and deactivating when it is lower than 95%. The analysis is made for each phase
combination independently, generating an output per combination, which allows the distance units of each combination to act
if the current measured is greater than the threshold and disables it otherwise.

The threshold must be exceeded for the phase - phase current and for each phase involved in the phase - phase current.

The settings are as follows:

❑ Enabled: Enables and disables the function:


❑ Forward threshold (A): each phase combination current must be above this value, to allow the corresponding phase-phase
distance unit of the zones selected as forward.
❑ Reverse threshold (A): each phase combination current must be above this value, to allow the corresponding phase-phase
distance unit of the zones selected as forward.
❑ Blocking input: Selects the signal which, when active, blocks phase-phase overcurrent supervision.
❑ Enable Events record. Allows the generation of protection events associated to the function. If set to “NO”, the function’s
protection events are not generated. If set to “YES”, the function’s specific mask is contemplated.
There are settings, commands and outputs:

❑ Node: PROT/PHRZOS1
❑ Settings and logical inputs. There are 6 settings tables. For details, see Table 18.
❑ Commands:
 “DOrdBlk”: Blocking and unblocking of phase-phase overcurrent supervision. Only acts when the function is enabled.
❑ Outputs: Table 19 shows the function's output data.
 IAB Forwards Permission. Indicates that the overcurrent supervision allows the AB distance unit to act (for zones
programmed forward).
 IBC Forwards Permission. Indicates that the overcurrent supervision allows the BC distance unit to act (for zones
programmed forward).
 ICA Forwards Permission. Indicates that the overcurrent supervision allows the CA distance unit to act (for zones
programmed forward).
 IAB Reverse Permission. Indicates that the overcurrent supervision allows the AB distance unit to act (for zones
programmed backwards).
 IBC Reverse Permission. Indicates that the overcurrent supervision allows the BC distance unit to act (for zones
programmed backwards).
 ICA Reverse Permission. Indicates that the overcurrent supervision allows the CA distance unit to act (for zones
programmed backwards).
 Ph-Ph supervision status. Indicates that phase-phase overcurrent supervision is activated and not blocked.

Ingeteam Power Technology S.A.


User Manual 73
PROTECTION FUNCTIONS

Table 18 Phase-Phase Unit Overcurrent Settings

Data Setting Minimum Maximum Step Remarks Type


Ena Enabled NO / YES enum
FwPhVal Forward threshold (A) 0,05 150 0,01 float32
RvPhVal Reverse threshold (A) 0.05 150 0,01 float32
LoghBlk Blocking input uint32
MaskEna Enable Events Record NO / YES Boolean

Table 19 Phase-Phase Unit Overcurrent Outputs

Signal Data (Edition 1) Attribute (Edition 1) Data (Edition 2) Attribute (Edition 2)


Perm. IAB Forward IFw phsAB IFwAB general
Perm. IBC Forward IFw phsBC IFwBC general
Perm. ICA Forward IFw phsCA IFwCA general
Perm. IAB Reverse IRv phsAB IRvAB general
Perm. IBC Reverse IRv phsBC IRvBC general
Perm. ICA Reverse IRv phsCA IRvCA general
Ph-Ph Supervision Status StEna general StEna stVal

3.1.8.2 Directional supervision


It supervises the direction of the fault such that it only allows faults that occur in the direction programmed in each zone. This is
applicable to all distance units (Mho and Quad).

Functioning is conditioned by polarization memory supervision. Hence, if the logic indicates that the memorised voltage must
be used, this is used during the set time. See section 3.3.3.

Table 20 shows the comparisons for determining the direction of the different types of faults:

Table 20 Directional Supervision Comparisons.

Unit S1 S2 Calculus
Ia  ZGDIRA set Va1 mem
AN |Angle(S1)-Angle(S2)| < ZGAMPA/2
& I2_A  ZGDIRA set
Ib  ZGDIRA set Vb1 mem
BN |Angle(S1)-Angle(S2)| < ZGAMPA/2
& I2_B  ZGDIRA set
Ic  ZGDIRA set Vc1 mem
CN |Angle(S1)-Angle(S2)| < ZGAMPA/2
& I2_C  ZGDIRA set
AB Iab  ZDIRA set Vab1 mem |Angle(S1)-Angle(S2)| < ZAMPA/2
BC Ibc  ZDIRA set Vbc1 mem |Angle(S1)-Angle(S2)| < ZAMPA/2
CA Ica  ZDIRA set Vca1 mem |Angle(S1)-Angle(S2)| < ZAMPA/2

Where:

❑ ZGDIRA set: Phase-ground angle. Set in degrees.


❑ ZGAMPA: Phase-ground amplitude. Set in degrees.
❑ ZDIRA set: Phase-phase angle. Set in degrees.
❑ ZAMPA: Phase-phase amplitude. Set in degrees.
❑ Vx1 mem: Positive sequence of the phase or combination of corresponding phases. The value is conditioned by
polarization memory supervision (See section 3.3.3). Where x indicates the corresponding unit.
In order for the directional to function, the voltage must be greater than 2V and the currents must be greater than 5% of the
rated current, for Ir=5A and 10% of the rated current, for Ir=1A.

The direction is determined by the comparison between the positive sequence voltage and current (See Figure 57).

It is indicated as forward if:

Ingeteam Power Technology S.A.


User Manual 74
PROTECTION FUNCTIONS

|angle(S1) − angle(S2)| < 𝐴𝑚𝑝𝑙𝑖𝑡𝑢𝑑𝑒/2

There is a 5º zone between the non-trip zone and the trip zone in which the current directional status is maintained.

The torque angle is the directional setting angle with the setting amplitude.

This directional is used in all zones and fault types.

Figure 57 Directional Supervision

In the case of an open pole, only phase current polarizations are used, not by I2.

The maximum torque angle will correspond to the directional angle set with an adjustable margin.

This directional is applied to all zones and types of phases.

The settings are as follows:

❑ Ph-Ph angle (º). Indicates the directional angle for phase-phase supervision.
❑ Ph-Ph amplitude (º). Indicates the angle that covers the trip zone for phase-phase supervision.
❑ Gnd angle (º). Indicates the directional angle for single-phase supervision.
❑ Gnd amplitude (º). Indicates the angle that covers the trip zone for single-phase supervision.
❑ Enable Events record. Allows the generation of protection events associated to the function. If set to “NO”, the function’s
protection events are not generated. If set to “YES”, the function’s specific mask is contemplated.
Figure 58 shows the supervision logic diagrams for single-phase and phase-phase directional supervision.

The input signal of this scheme is:

❑ Open Pole. Indicates, there´s any pole open. It is output of the function open pole detector.

Ingeteam Power Technology S.A.


User Manual 75
PROTECTION FUNCTIONS

Figure 58 Single-Phase and Phase - Phase Zone Supervision

There are settings and outputs:

❑ Node: PROT/RDIR1
❑ Settings and logical inputs. There are 6 settings tables. For details, see Table 21.
❑ Outputs: Table 22 shows the function's output data.
 Permission dir IA Forward. Indicates that directional supervision allows distance unit AN to act (for zones programmed
forward).
 Permission dir IB Forward. Indicates that directional supervision allows the distance unit BN to act (for zones
programmed forward).
 Permission dir IC Forward. Indicates that directional supervision allows the distance unit CN to act (for zones
programmed forward).
 Permission dir IAB Forward. Indicates that directional supervision allows the distance unit AB to act (for zones
programmed forward).

Ingeteam Power Technology S.A.


User Manual 76
PROTECTION FUNCTIONS

 Permission dir IBC Forward. Indicates that directional supervision allows the distance unit BC to act (for zones
programmed forward).
 Permission dir ICA Forward. Indicates that directional supervision allows the distance unit CA to act (for zones
programmed forward).
 Permission dir IA Reverse. Indicates that directional supervision allows the distance unit AN to act (for zones
programmed backwards).
 Permission dir IB Reverse. Indicates that directional supervision allows the distance unit BN to act (for zones
programmed backwards).
 Permission dir IC Reverse. Indicates that directional supervision allows the distance unit CN to act (for zones
programmed backwards).
 Permission dir IAB Reverse. Indicates that directional supervision allows the distance unit AB to act (for zones
programmed backwards).
 Permission dir IBC Reverse. Indicates that directional supervision allows the distance unit BC to act (for zones
programmed backwards).
 Permission dir ICA Reverse. Indicates that directional supervision allows the distance unit CA to act (for zones
programmed backwards).

Table 21 Directional Supervision Settings

Data Setting Minimum Maximum Step Remarks Type


PhDirArg Ph-Ph angle (º) 0 359 1 float32
PhAmp Ph-Ph amplitude (º) 90 170 1 float32
GndDirArg Gnd angle (º) 0 359 1 float32
GndAmp Gnd amplitude (º) 90 170 1 float32
MaskEna Enable Events Record NO / YES Boolean

Table 22 Directional Supervision Outputs

Signal Data (Edition 1) Attribute (Edition 1) Data (Edition 2) Attribute (Edition 2)


Permission dir IA Forward DirFw phsA DirFw phsA
Permission dir IB Forward DirFw phsB DirFw phsB
Permission dir IC Forward DirFw phsC DirFw phsC
Permission dir IAB Forward DirFw phsAB DirFwAB general
Permission dir IBC Forward DirFw phsBC DirFwBC general
Permission dir ICA Forward DirFw phsCA DirFwCA general
Permission dir IA Reverse DirRv phsA DirRv phsA
Permission dir IB Reverse DirRv phsB DirRv phsB
Permission dir IC Reverse DirRv phsC DirRv phsC
Permission dir IAB Reverse DirRv phsAB DirRvAB general
Permission dir IBC Reverse DirRv phsBC DirRvBC general
Permission dir ICA Reverse DirRv phsCA DirRvCA general

3.1.9 Capacitive Voltage Transformer (CVT) Lines


With the use of capacitive voltage transformers (CVTs), in the event of a very sharp voltage drop, faults very close to the relay or
with high SIR (Source Impedance Ratio), give rise to very serious transients in the voltage, which tend to cause overreaches in the
distance units. In conditions in which the current is very small, generally when the value of the SIR is very high with respect to the
line impedance, this problem will arise. To avoid it, the voltages are filtered when the seriousness of the transients is very acute.

3.1.9.1 Capacitive Voltage Transformer Logic


If capacitive voltage transformers are being used, this function will be enabled by the settings.

In order to determine when the voltages must be filtered, two conditions must be fulfilled: A fault has occurred and there is a
risk of overreaching (for which the SIR estimation will be used).

To estimate the SIR, the lowest value obtained from amongst all the units indicated by the phase identifier will be used. They
are compared with a threshold which will depend on the CVT type (which can be selected through the settings). If the SIR value

Ingeteam Power Technology S.A.


User Manual 77
PROTECTION FUNCTIONS

calculated is greater than the threshold specified and a fault is detected using the fault detector, then the filtered voltages will
be used. Otherwise, the voltages will be calculated as usual.

The filtered voltages are only used in zone 1 of the distance functions (unit 21). A digital bandpass filter is used.

The settings are as follows:

❑ Enabled: Indicates whether the function is enabled or not.


❑ CVT type: Selects the type of supervision and with it, the threshold used to compare the SIR calculated to determine
whether or not filtered voltages should be used.
 Passive: SIR 10 threshold.
 Active: SIR 1 threshold.
❑ Blocking input: Selects the signal which, when active, blocks the CVT function.
❑ Enable Events record. Allows the generation of protection events associated to the function. If set to “NO”, the function’s
protection events are not generated. If set to “YES”, the function’s specific mask is contemplated.
There are settings, commands and outputs:

❑ Node: PROT/RCVT1
❑ Settings and logical inputs. There are 6 settings tables. For details, see Table 23.
❑ Commands:
 “DOrdBlk”: Function blocking and unblocking. Only acts when the function is enabled.
❑ Outputs: See Table 24.
 “CVT enabled”: Indicates that the CVTs are active and not blocked.
 "Voltages filtered": This is activated while filtered voltages are being used.

Table 23 CVT Settings

Data Setting Minimum Maximum Step Remarks Type


Ena Enabled NO / YES enum
CVTType CVT Type Passive / Active enum
LogInBlk Blocking input uint32
MaskEna Enable Events Record NO / YES Boolean
Table 24 CVT Output

Signal Data Attribute


CVT Enabled StEna general (stVal in Ed2)
Voltages filtered FilterV general

3.1.9.2 SIR Calculation


SIR is understood as the source impedance ratio with respect to the line impedance.

It is calculated with the half cycle dft. The calculation is performed on the units indicated by the phase identifier. The SIR value
to bear in mind will always be the one corresponding to the one with lowest value amongst the units indicated by the phase
identifier.

The SIR and the option to use or not to use filtered voltages is assessed when the fault detector is activated. Depending on the
CVT supervision type ("Passive" or "Active"), different thresholds will be used to determine whether or not to used filtered
voltages.

If the SIR is greater than 1 for the actives or 10 for the passive ones, the high speed tripping is blocked and filtered voltages are
used in Zone 1, for both MHO and QUAD characteristics.

The formulation for calculating the SIR is shown in Table 25:

Ingeteam Power Technology S.A.


User Manual 78
PROTECTION FUNCTIONS

Table 25 Calculating the SIR for Different Units.

SIR for single phase faults SIR for single phase-phase faults
(Vrated/((Ia+3·I0  kn1 +IN2  kM1 )·Z1))-1 (Urated/(Iab·Z1))-1
(Vrated/((Ib+3·I0  kn1 +IN2  kM1 )·Z1))-1 (Urated/(Ibc·Z1))-1
(Vrated/((Ic+3·I0  kn1 +IN2  kM1 )·Z1))-1 (Urated/(Ica·Z1))-1

Where:

❑ Urated: Rated phase-phase voltage (3·Vrat).


❑ Vrated: Rated phase-ground voltage.
❑ Z1: The module of the positive sequence impedance of the line.
❑ Kn1: Zero-sequence compensation for zone 1.
1 zl0
K n = ( − 1)
3 zl1

❑ Km1: Mutual compensation constant for zone 1 (double lines).


𝑍𝑚0
𝐾𝑚 =
3 · zl1

❑ Ia, Ib, Ic: Phase currents.


❑ Iab, Ibc, Ica: Phase - phase currents (Iab = Ia - Ib, Ibc = Ib - Ic, Ica = Ic - Ia).
❑ 3 I0: Calculated neutral current.
❑ IN2: Measured neutral current of the parallel line. Only for double lines.

3.2 SIGNALS AND COMMANDS

In this section all the protection functions are shown, the ones included in each model are indicated in the functional description.

3.2.1 Signals
There are available general signals that group data from several functions (See Table 26). These signals are in the node PROT/PTRC1. In
every model will be only the signals of the available functions.

❑ General Start. Indicates that one of the units that causes a general trip is started.
❑ General Trip. Indicates that one of the units that causes a general trip is activated.
❑ Pole A General Trip. Indicates that one of the units that causes a general trip of pole A is activated.
❑ Pole B General Trip. Indicates that one of the units that causes a general trip of pole B is activated.
❑ Pole C General Trip. Indicates that one of the units that causes a general trip of pole C is activated.
❑ OC General Start. Indicates that one of the overcurrent units is started.
❑ OC General Trip. Indicates that one of the overcurrent units is activated.
❑ 51 Start. Indicates that any of the time delay phase overcurrent unit is started.
❑ 51N Start. Indicates that one of the time delay neutral overcurrent units is started.
❑ 51ES Start. Indicates that one of the time delay earth system overcurrent units is started.
❑ 51UN Start. Indicates that one of the time delay unbalance overcurrent units is started.
❑ 51 Trip. Indicates that one of the time delay phase overcurrent units is activated.
❑ 51N Trip. Indicates that one of the time delay neutral overcurrent units is activated.
❑ 51ES Trip. Indicates that one of the time delay earth system overcurrent units is activated.

Ingeteam Power Technology S.A.


User Manual 79
PROTECTION FUNCTIONS

❑ 51UN Trip. Indicates that one of the time delay unbalance overcurrent units is activated.
❑ 50 Start. Indicates that one of the instantaneous phase overcurrent units is started.
❑ 50N Start. Indicates that one of the instantaneous neutral overcurrent units is started.
❑ 50ES Start. Indicates that one of the instantaneous earth system overcurrent units is started.
❑ 50UN Start. Indicates that one of the instantaneous unbalance overcurrent units is started.
❑ 50 Trip. Indicates that one of the instantaneous phase overcurrent units is activated.
❑ 50N Trip. Indicates that one of the instantaneous neutral overcurrent units is activated.
❑ 50ES Trip. Indicates that one of the instantaneous earth system overcurrent units is activated.
❑ 50UN Trip. Indicates that one of the instantaneous unbalance overcurrent units is activated.
❑ Voltage Start. Indicates that one of the voltage units is started.
❑ IOV Start. Indicates that one of the instantaneous overvoltage units is started.
❑ IUV Start. Indicates that one of the instantaneous undervoltage units is started.
❑ Minimum F Start. Indicates that one of the underfrequency units is started.
❑ Maximum F Start. Indicates that one of the overfrequency units is started.
❑ dfdt Start. Indicates that one of the df/dt units is started.
❑ Voltage Trip. Indicates that one of the voltage units is activated.
❑ IOV Trip. Indicates that one of the instantaneous overvoltage units is activated.
❑ IUV Trip. Indicates that one of the instantaneous undervoltage units is activated.
❑ Minimum F Trip. Indicates that one of the underfrequency units is activated.
❑ Maximum F Trip. Indicates that one of the overfrequency units is activated.
❑ dfdt Trip. Indicates that one of the df/dt units is activated.

Ingeteam Power Technology S.A.


User Manual 80
PROTECTION FUNCTIONS

Table 26 General signals

Signal Data Attribute


General Start Str general
General Trip Op general
Pole A General Trip Op phsA
Pole B General Trip Op phsB
Pole C General Trip Op phsC
OC General Start StrOC stVal
OC General Trip OpOC stVal
51 Start Str51 stVal
51N Start Str51N stVal
51ES Start Str51ES stVal
51UN Start Str51UN stVal
51 Trip Op51 stVal
51N Trip Op51N stVal
51ES Trip Op51ES stVal
51UN Trip Op51UN stVal
50 Start Str50 stVal
50N Start Str50N stVal
50ES Start Str50ES stVal
50UN Start Str50UN stVal
50 Trip Op50 stVal
50N Trip Op50N stVal
50ES Trip Op50ES stVal
50UN Trip Op50UN stVal
Voltage Start StrV stVal
IOV Start StrIOV stVal
IUV Start StrIUV stVal
Minimum F Start StrFmin stVal
Maximum F Start StrFmax stVal
dfdt Start StrDfDt stVal
Voltage Trip OpV stVal
IOV Trip OpIOV stVal
IUV Trip OpIUV stVal
Minimum F Trip OpFmin stVal
Maximum F Trip OpFmax stVal
dfdt Trip OpDfDt stVal

3.2.2 Commands
Certain commands enable actions to be taken on the protection functions. Each function specific characteristics are listed in the
corresponding section. This section lists the general functions. Table 27 shows the functions affected by the general commands.

The blocking/ unblocking commands are stored so that they are maintained when the device is switched off. If a function is enabled by
the settings and blocked by a command, the status shows that is deactivated. All the functions blocked by a command are unblocked
with the command associated to the function, each time an ICD is sent or by the general unblocking command (DOrdRstBlk node
PROT/LLN0). Available from firmware version 5.18.15.4 and ICD version 6.1.13.31.

The general protection commands are in the PROT/PTRC node, allowing the blocking/unblocking of the associated functions:

❑ DOrdPrBl. Protection block. Affects all the protection functions.


❑ DOrdPhBl. Phase block. Affects all the phase functions.
❑ DOrdInsBl. Instantaneous block. Affects all the instantaneous functions.
❑ DOrdInsPhBl. Instantaneous phase block. Affects all the phase instantaneous functions.
❑ DOrdTmPhBl. Timed phase block. Affects all the timed phase functions.
❑ DOrdINBl. Instantaneous neutral block. Affects all the neutral instantaneous functions.
❑ DOrdVBl. Voltage block. Affects all the voltage functions.
❑ DOrdDirBl. Directional block. Affects all the directional functions. Equivalent to giving directional permission.

Ingeteam Power Technology S.A.


User Manual 81
PROTECTION FUNCTIONS

Table 27 Command by functions

DOrdPrBl DOrdPhBl DOrdInsBl DOrdInsPhBl DOrdTmPhBl DOrdINBl DOrdVBl


Distance units
Zone 1 Gnd 
Zone 1 Phase-Phase 
Zone 2 Gnd 
Zone 2 Phase-Phase 
Zone 3 Gnd 
Zone 3 Phase-Phase 
Zone 4 Gnd 
Zone 4 Phase-Phase 
Zone 5 Gnd 
Zone 5 Phase-Phase 
Current units
Phase instantaneous (50)    
Phase timed (51)   
Neutral instantaneous (50)   
Neutral timed (51) 
Ground instantaneous (50)   
Ground timed (51) 
Unbalance instantaneous  
Unbalance block 
46FA Open phase  
37 Undercurrent  
50CSC Second harmonic restraint 
49 Thermal image 
Voltage/ Frequency / Power units
Phase overvoltage timed    
Phase instantaneous overvoltage     
Zero sequence overvoltage timed  
Zero sequence instantaneous overvoltage    
V2 overvoltage timed  
V2 instantaneous overvoltage   
Phase undervoltage timed    
Phase instantaneous undervoltage     
Frequency (81M/m) 
Frequency rate of change (81R) 
Minimum real power 
Maximum real power 
Real power inversion 
Reactive power inversion 
Minimum apparent power 
Maximum apparent power 
Remaining protection functions
Load encroachment 
Fuse failure 
SOFT Switch onto fault 
Line fault 
50BF Breaker failure 

Ingeteam Power Technology S.A.


User Manual 82
PROTECTION FUNCTIONS

3.3 CURRENT UNITS

3.3.1 General overcurrent description

3.3.1.1 Timed characteristics


When enabled and unblocked, the unit acts when the setting value is exceeded during the programmed time.

To reset, the current must fall below 95% of the setting value.

The different curve options are shown in the curve appendix.

The timed unit can be configured with a minimum response time, that is, a limit that prevents any unit from tripping below a
minimum time when the trip time corresponding to the curve in use is met. This is done to prevent timed trips from being
faster than instantaneous trips. It is configured with an additional time setting, so that if it is set to zero, there is no such limit.

The settings used in these functions (Table 28) are:

❑ Enabled. Indicates whether the function is enabled or not.


❑ Operation type. To be selected between:
 “Trip” generates function trips.
 “Start”, in which the function generates a pickup but no trips.
 “Block by IOC1”. The timed unit’s trip is blocked if the instantaneous unit 1 has picked up. The timed pickup is not
deactivated.
 “Block by IOC1, 2”. The timed unit’s trip is blocked if the instantaneous unit 1 or 2 has picked up. The timed pickup is
not deactivated.
 “Block by IOC1, 2, 3”. The timed unit’s trip is blocked if the instantaneous unit 1, 2 or 3 has picked up. The timed pickup
is not deactivated.
❑ Start value (A). Set in secondary amperes. It indicates the current value for which the function is activated.
❑ Operating Curve Type Indicates the type of curve selected from the options:
 ANSI-EI Extreme. Inverse (1)
 ANSI-MI Very inverse (2)
 ANSI-I Normal inverse(3)
 ANSI-MODI Moderately inverse (4)
 IEC-I Normal inverse (9) or Inverse (11)
 IEC-MI Very inverse (10)
 IEC-EI Extreme. Inverse (12)
 IEC-IC Short inverse (13)
 IEC-IL Long inverse (14)
 IEC-MIEs Very inverse special (50)
 User curves 1 (33)
 User curves 2 (34)
 User curves 3 (35)
 User curves 4 (36)
 Definite time (49)
 IEEE Moderate Inverse (89)
 IEEE Very Inverse (90)
 IEEE Extremely Inverse (91)
❑ Time dial. Indicates the time curve within the selected characteristic.

Ingeteam Power Technology S.A.


User Manual 83
PROTECTION FUNCTIONS

❑ Delay/minimum time (ms). It has a different functionality depending on the type of the curve selected:
 When the selected curve is a definite time, it indicates the time during which the conditions for the tripping of the
function must be met.
 In the rest of the curve, it indicates the minimum response time. i.e., in order for a trip to be produced, the time used
will be the greater between this setting and the time associated to the curve.
❑ Torque control. Selects the function’s directional type:
 “NO”. Acts as non-directional.
 “Forward”. Acts when the directional indicates forward.
 “Reverse”. Acts when the directional indicates reverse.
❑ Behaviour with Fuse fail. Defines the function’s action if a fuse failure is detected.
 "Idle". The fuse failure does not affect the function.
 "Non Directional". The function acts as non-directional when a fuse failure is detected.
 "Block". The function blocks, i.e., it does not act, when a fuse failure is detected.
 "Enable". The function is enabled when a fuse failure is detected.
❑ Reset type. Allows the emulation of the induction operation. The following options are available:
 "Instantaneous". If the current drops below 95% of the setting value, both the trip and the pickup reset
instantaneously.
 "Timed". If the current drops below 95% of the setting value, the trip drops out instantaneously, while the pickup reset
time will depend on the selected curve (family and index) and the current. If a definite time curve is selected, the
pickup will reset upon the completion of the time programmed for the pickup as of the moment in which it falls below
the pickup current, regardless of the current value.
❑ Operating Quantity. Indicates the measurement used by the function (52 ½ models only allow "Phasor"):
 "Phasor". Uses the fundamental measurement, without including harmonics.
 "RMS". Uses the effective value, including harmonics.
❑ Blocking Input. Selects the signal which, when active, blocks the function.
❑ Time delay cancel Input. Selects the signal which, when active, generates an instantaneous trip regardless of the set time.
❑ General trip. Indicates if this unit produces general trip or not. For additional details, see the section corresponding to the
recloser (3.12.6).
❑ Trip Permission by recloser. Indicates the trip and block permission in accordance with the recloser status: standby,
blocked, safety time after reclosing, after closing. It is configured bit by bit; for additional details, see section
corresponding to the recloser (3.12.6.3).
❑ Reclose perm.(R1,R2,R3,R4). Indicates whether each trip type can be reclosed or not, in accordance with the recloser's
closing cycle (see reclosure permission mask).
❑ Enable Events record. Allows the generation of protection events associated to the function. If set to “NO”, the function’s
protection events are not generate. If set to “YES”, the function’s specific mask is contemplated.

Ingeteam Power Technology S.A.


User Manual 84
PROTECTION FUNCTIONS

Table 28 Timed overcurrent unit settings

Data Setting Min. Max. Step Remarks Type


PTOCEna Enabled NO / YES enum
Trip (1)
Start (2)
Optype Operation type Block by IOC1 (3) enum
Block by IOC1,2(4)
Block by IOC1,2,3(5)
StrVal Start value (A) 0,02 150,0 0,01 float32
ANSI-EI Extreme. Inverse (1)
ANSI-MI Very inverse (2)
ANSI-I Normal inverse(3)
ANSI-MODI Moderately inverse (4)
IEC-I Normal inverse (9) / Inverse (11)
IEC-MI Very inverse (10)
IEC-EI Extreme. Inverse (12)
IEC-IC Short inverse (13)
IEC-IL Long inverse (14)
TmACrv Operating Curve Type enum
IEC-MIEs Very inverse special (50)
User curves 1 (33)
User curves 2 (34)
User curves 3 (35)
User curves 4 (36)
Definite time (49)
IEEE Moderate Inverse (89)
IEEE Very Inverse (90)
IEEE Extremely Inverse (91)
ANSI: 0,5 - 30 step 0,1
TmMult Time dial 0,025 30 0,005 IEC: 0,025-1,5 step 0,005 float32
IEEE: 0,025-15 step 0,005
OpDlTmms Delay/minimum time (ms) 0 600000* 10 int32
NO (0)
DirMod Torque control Forward (1) enum
Reverse (2)
Idle (0)
Non Directional (1)
FFailBeh Behaviour with Fuse fail enum
Block (2)
Enable (3)
Instantaneous (0)
RstTyp Reset type enum
Timed (1)
Phasor (0)
MesTyp Operating Quantity enum
RMS (1)
LogInBlk Blocking Input uint32
LogInCaTm Time delay cancel Input uint32
GenTrip General trip NO / YES Boolean
TripPerm Trip Permission by recloser 0 255 1 Bit meaning (1) ING
NO (0)
Reclose 1 (1)
Reclose 2 (2)
Reclose 1-2 (3)
Reclose 3 (4)
Reclose 1-3 (5)
Reclose 2-3 (6)
Reclose 1-2-3 (7)
ReclPerm Reclose perm.(R1,R2,R3,R4) 0 15 enum
Reclose 4 (8)
Reclose 1-4 (9)
Reclose 2-4 (10)
Reclose 1-2-4 (11)
Reclose 3-4 (12)
Reclose 1-3-4 (13)
Reclose 2-3-4 (14)
Reclose 1-2-3-4 (15)
MaskEna Enable Events record NO / YES Boolean

Ingeteam Power Technology S.A.


User Manual 85
PROTECTION FUNCTIONS

3.3.1.2 Instantaneous characteristics


When enabled and unblocked, the unit operates when the setting value is exceed during the programmed time.

To reset, the current must fall below 95% of the setting value.

The settings used in these functions (See Table 29) are:

❑ Enabled. Indicates whether the function is enabled or not.


❑ Operation type. To be selected between:
 “Trip” generates function trips.
 “Start”, in which the function generates a pickup but no trips.
❑ Start value (A). Set in secondary amperes. It indicates the current value for which the function is activated.
❑ Delay time (ms). Indicates the time during which the conditions for the tripping of the function must be met.
❑ Torque control. Selects the function’s directional type:
 “NO”. Acts as non-directional.
 “Forward”. Acts when the directional indicates forward.
 “Reverse”. Acts when the directional indicates reverse.
❑ Behaviour with Fuse fail. Defines the function’s action if a fuse failure is detected.
 "Idle". The fuse failure does not affect the function.
 "Non Directional". The function acts as non-directional when a fuse failure is detected.
 "Block". The function blocks, i.e., it does not act, when a fuse failure is detected.
 "Enable". The function is enabled when a fuse failure is detected.
❑ Operating Quantity. Indicates the measurement used by the function:
 "Phasor". Uses the fundamental measurement, without including harmonics.
 "RMS". Uses the effective value, including harmonics.
❑ Blocking Input. Selects the signal which, when active, blocks the function.
❑ Time delay cancel Input. Selects the signal which, when active, generates an instantaneous trip regardless of the setting
time.
❑ General trip. Indicates if this unit produces general trip or not. For additional details, see the section corresponding to the
recloser (3.12.6).
❑ Trip Permission by recloser. Indicates the trip and block permission in accordance with the recloser status: standby,
blocked, safety time after reclosing, after closing. It is configured bit by bit; for additional details, see section
corresponding to the recloser (3.12.6.3).
❑ Reclose perm.(R1,R2,R3,R4). Indicates whether each trip type can be reclosed or not, in accordance with the recloser's
closing cycle (See 6.2.3).
❑ Enable Events record. Allows the generation of protection events associated to the function. If set to “NO”, the function’s
protection events are not generate. If set to “YES”, the function’s specific mask is contemplated.

Ingeteam Power Technology S.A.


User Manual 86
PROTECTION FUNCTIONS

Table 29 Instantaneous overcurrent unit settings

Data Setting Minimum Maximum Step Remarks Type


PIOCEna Enabled NO / YES enum
Trip (1)
Optype Operation type enum
Start (2)
StrVal Start value (A) 0,02 150,0 0,01 float32
OpDlTmms Delay time (ms) 0 600000* 10 int32
NO (0)
DirMod Torque control Forward (1) enum
Reverse (2)
Idle (0)
Non Directional (1)
FFailBeh Behaviour with Fuse fail enum
Block (2)
Enable (3)
Phasor (0)
MesTyp Operating Quantity enum
RMS (1)
LogInBlk Blocking Input uint32
LogInTIn Time delay cancel input uint32
GenTrip General trip NO / YES Boolean
TripPerm Trip Permission by recloser 0 255 1 Bit meaning (1) ING
NO (0)
Reclose 1 (1)
Reclose 2 (2)
Reclose 1-2 (3)
Reclose 3 (4)
Reclose 1-3 (5)
Reclose 2-3 (6)
Reclose 1-2-3 (7)
ReclPerm Reclose perm.(R1,R2,R3,R4) 0 15 enum
Reclose 4 (8)
Reclose 1-4 (9)
Reclose 2-4 (10)
Reclose 1-2-4 (11)
Reclose 3-4 (12)
Reclose 1-3-4 (13)
Reclose 2-3-4 (14)
Reclose 1-2-3-4 (15)
MaskEna Enable Events record NO / YES Boolean

3.3.2 Directional characteristics


The overcurrent units have a setting (torque control) for selecting the unit’s directionality:

❑ No: the unit acts as non-directional.


❑ Forward: the unit acts as directional in a forward direction.
❑ Reverse: the unit acts as directional in a reverse direction.
There are logical trip direction inversion inputs that allow the different units' trip direction to be inverted.

There are logical “function X directional inhibition” inputs that allow the directional units to which they are applied to be converted
into non-directional. These inputs allow for a unit's conversion into non-directional in the case of a fuse failure, for example.

The negative sequence unit can be used in phases and in neutral.

3.3.2.1 Phase directional


The operation can be selected among: quadrature, quadrature 2 out of 3, positive sequence (S1) and positive + negative
sequences (S1+S2). The S2 directional has its own settings.

This function’s general settings and those applied in the quadrature, quadrature 2 out of 3 and positive sequence criteria are in
the PROT/RDIR1 node:

❑ Directional method. Indicates the directional criterion used.

Ingeteam Power Technology S.A.


User Manual 87
PROTECTION FUNCTIONS

 “Quadrature”. Analyses each phase independently.


 “Quad. 2 out of 3”. Analyses each phase independently. However, in order to grant permission it must see the
direction in at least two phases.
 “Positive sequence”. Analyses the positive sequence.
 “S2 and S1 sequence”. Analyses the negative and positive sequences. The positive sequence is analysed only when the
negative sequence indicates polarization failure.
❑ Torque angle (º). Indicates the directional angle. Applies to quadrature, quadrature 2 out of 3 and positive sequence.
❑ Minimum V polarization (V). Indicates the minimum voltage for polarization; the direction cannot be reliably determined
below this value.
❑ Zone amplitude (º). Indicates the angle covered by the trip zone.
❑ Permission with low Vpol. Indicates the functioning of the directional when the polarization voltage is below the threshold.
If set to “YES”, it enables an overcurrent trip if the memorized polarization voltage is lower than the minimum polarization
voltage; if set to “NO”, the overcurrent trip is not allowed under those conditions.
❑ 67 directional Inversion. Selects the signal which, when active, inverts the trip direction.
❑ Phase directional blocking. Selects the signal which, when active, blocks the function. When the directional is blocked, it is
issues permission for the trip.
❑ Enable Events record. Allows the generation of protection events associated to the function. If set to “NO”, the function’s
protection events are not generate. If set to “YES”, the function’s specific mask is contemplated.
Table 30 Phase directional settings (Quadrature and positive sequence)

Data Setting Minimum Maximum Step Remarks Type


Quadrature
Quad. 2 out of 3
PolQty (PolSel in Ed2) Directional method enum
Positive sequence
S2 and S1 sequence
ChrAng Torque angle (º) 0 360359 1 float32
Vpol Minimum V polarization (V) 1 200 0,1 float32
Amp (AmpVal in Ed2) Zone amplitude (º) 90 170 1 float32
EnaOpn (TripVpol in Ed2) Permission with low Vpol NO / YES Boolean
LogInInvDir 67 directional Inversion int32
LogInBlDir Phase directional blocking int32
MaskEna Enable Events record NO / YES Boolean

The minimum polarization current is considered as 50% of the minimum setting of the three timed and instantaneous phase
units (50/51) that are enabled. When all units are disabled, the minimum polarization current is considered as 50% of the phase
rated current.

The quadrature and positive sequence units settings, commands and outputs.

❑ Node: PROT/RDIR1
❑ Settings and logical inputs. There are 6 settings tables. For details, see Table 30.
❑ Commands:
 “DOrdBlk”: Function blocking and unblocking.
 “DOrdInvDir”. Inverts the directional trip direction.
❑ Outputs: Table 31 shows the function’s output data.
 67 Forward X. The detected direction indicates forward. It is independent for each phase.
 67 Reverse X. The detected direction indicates reverse. It is independent for each phase.
 Polarization Failure X. Indicates that the direction has not been detected due to a polarization failure. It is independent
for each phase.
 Phase directional inhibition. Indicates that the directional is inhibited.
 Phase direction inversion. Indicates that the direction is opposite to the setting.

Ingeteam Power Technology S.A.


User Manual 88
PROTECTION FUNCTIONS

Table 31 Phase directional outputs (quadrature and positive sequence)

Signal Data Attribute


67-Forward A Fw67 phsA
67-Forward B Fw67 phsB
67-Forward C Fw67 phsC
67-Reverse A Rv67 phsA
67-Reverse B Rv67 phsB
67-Reverse C Rv67 phsC
Polarization Failure A FailPol phsA
Polarization Failure B FailPol phsB
Polarization Failure C FailPol phsC
Phase Directional Inhibition BlkDir general
Phase Direction Inversion InvDir general

3.3.2.1.1 Quadrature
For the detection of directionality in phases, the polarization voltage corresponds to the quadrature connection (90º), in
which each phase’s current is compared with the phase to phase voltage between the other two phases (See Figure 59).
π
Phase Ia: Spol = Vbc Sop = Ia ∙ e−j∙(90º−MTA_FASES)∙180
π
Phase Ib: Spol = Vca Sop = Ib ∙ e−j∙(90º−MTA_FASES)∙180
π
Phase Ic: Spol = Vab Sop = Ic ∙ e−j∙(90º−MTA_FASES)∙180

Where, MTA_FASES is the setting "Torque angle (º)"

Signals forward when

Amplitude º
|angle(Spol) − angle(Sop)| < ( )
2
Where, Amplitude is the setting "Zone amplitude (º)"

The “Quad. 2 out of 3” means that the unit only signals forward if this direction is seen in 2 phases. Avoids cases in which,
with a reverse fault, certain of the phases detect a forward fault (e.g., weak infeed). In the case of weak infeed due to the
opening of a transformer, there is only zero sequence current and therefore the three phases detect the same current. In
this case, one of the 3 phases will detect the fault in the opposite direction to the other two.

It operates as three single phase units in which polarization voltages are the phase to phase voltages of the healthy phases.

In the case of an ABC phase sequence, polarization is effected with Vab, Vbc and Vac, for Ic, Ia and Ib. In the case of a CBA
phase sequence, polarization is effected with Vba, Vcb and Vac, for Ic, Ia and Ib.

There is a 5º zone between the non-trip zone and the trip zone in which the current directional status is maintained.

This unit’s signals are independent for each of the phases (See Table 31).

Memory

The polarization voltage is the voltage of the previous 3 cycles. If the voltage falls below the setting "Minimum V
polarization (V)", the value memorized in accordance with the memory management explained in the polarization memory
monitoring is used (See 3.3.3). It is also affected by the series compensation logic in so far that if it is set to “YES” the
memorized voltage is used as of the moment in which a fault or a voltage inversion is detected.

Trip permission with low polarization voltage

When the polarization voltage is below the setting "Minimum V polarization (V)" or the operating current is below the
minimum polarization current “Polarization Failure X” is indicated. In this situation, if the trip permission without
polarization V is set to “YES”, the trip is permitted; while if set to “NO”, it is blocked.

Ingeteam Power Technology S.A.


User Manual 89
PROTECTION FUNCTIONS

Figure 59 Phase directional (Quadrature)

3.3.2.1.2 Positive sequence


The direction is determined by the comparison between the positive sequence voltage and current (See Figure 60).

S1pol = V1
π
S1op = I1 ∙ ej∙MTA_FASES∙180

Where, MTA_FASES is the setting "Torque angle (º)"

It signals forward when

Amplitude º
|angle(S1pol) − angle(S1op)| < ( )
2
Where, Amplitude is the setting "Zone amplitude (º)"

There is a 5º zone between the non-trip zone and the trip zone in which the current directional status is maintained.

This unit’s signals are the same as those of the quadrature, with the difference that the three phases are always given
simultaneously (See Table 31).

Memory

The polarization voltage is the positive sequence voltage of the previous 3 cycles. If it falls below the setting "Minimum V1
(V)", the value memorized in accordance with the memory management explained in the polarization memory monitoring
is used (See 3.3.3). It is also affected by the series compensation logic in so far that if it is set to “YES” the memorized
voltage is used as of the moment in which a fault or a voltage inversion is detected.

Trip permission with low Vpol

When the V1 polarization voltage is below the setting “Minimum V polarization (V)” or the operating current is below the
minimum polarization current “Polarization Failure X” is indicated.

The directional block is used when the operating current is below the minimum polarization current.

If V1 is below the setting “Minimum V polarization (V)” but the operating current is above the minimum polarization
current, if the trip permission without polarization V is set to “YES”, the trip is permitted; while if set to “NO”, it is blocked.

Ingeteam Power Technology S.A.


User Manual 90
PROTECTION FUNCTIONS

Figure 60 Phase directional (Positive sequence)

3.3.2.1.3 Negative and positive sequence


Both methods are used to determine the direction, first by analysing the negative sequence:

❑ If the negative sequence indicates the direction, the positive sequence is not consulted.
❑ If the negative sequence indicates a polarization failure, the positive sequence is consulted.

3.3.2.2 Negative sequence


It is used both in phase and neutral directional.

The direction is determined by the comparison between the negative sequence voltage and current, with 3V2 greater than the
threshold "Minimum V polarization (V)" and I2 greater than the thresholds "Minimum I2 / I1 Ph (%)" and "Minimum 3I2 / Irated
(%)" (See Figure 61).

In the case of lines with series compensation, a Z2offset setting, which modifies the polarization voltage, is included.
𝜋
S2pol = −3 ∙ V2 + 3 ∙ I2 ∙ Z2Offset ∙ ej∙MTA_S2∙180
π
S2op = 3 ∙ I2 ∙ ej∙MTA_S2∙180

Where, MTA_S2 is the setting "Torque angle (º)"

It signals forward when

Amplitude º
|angle(S2pol) − angle(S2op)| < ( )
2

Where, Amplitude is the setting "Zone amplitude (º)"

There is a 5º zone between the non-trip zone and the trip zone in which the current directional status is maintained.

If Z2offset is not used:

S2pol is -3·V2

If Z2offset is used:

❑ With series compensation:


 S2pol is calculated with Z2Offset.
❑ Without series compensation:

Ingeteam Power Technology S.A.


User Manual 91
PROTECTION FUNCTIONS

 S2pol depends on the relation between S2pol and the setting "Minimum V polarization (V)". If the S2pol calculated
with Z2Offset is greater than "Minimum V polarization (V)", the calculated S2pol is used. On the other hand, if "-3·V2"
is greater than "Minimum V polarization (V)", S2pol = -3·V2 is used.
Trip permission with low Vpol

When the S2pol polarization voltage is below the setting "Minimum V polarization (V)" or the negative sequence current (I2) is
below any of the thresholds "Minimum I2 / I1 Ph (%)" or "Minimum 3I2 / Irated (%)", “Polarization Failure S2” is indicated.

The directional block is used when the negative sequence current (I2) is below any of the thresholds "Minimum I2 / I1 (%)" or
"Minimum I2 / Irated (%)".

If S2pol is below the setting "Minimum V polarization (V)" and I2 is greater than the thresholds "Minimum I2 / I1 Ph (%)" and
"Minimum 3I2 / Irated (%)", if the trip permission without polarization V is set to “YES”, the trip is permitted; while if set to
“NO”, it is blocked.

For the phase overcurrent units, the negative sequence directional uses the "Permission with low Vpol" setting which is on the
node PROT/RDIR1 (Phase directional).

For the neutral overcurrent units, the negative sequence directional uses the "Permission with low Vpol" setting which is on the
node PROT/GRDIR1 (Ground directional).

For the unbalanced overcurrent units, the negative sequence directional uses the "Permission with low Vpol 67Q" setting which
is on the node PROT/S2RDIR1(Negative sequence directional).

This function’s general settings and those applied in the quadrature and positive sequence criteria are in the PROT/S2RDIR1
node:

❑ Torque angle (º). Indicates the directional angle.


❑ Zone amplitude (º). Indicates the angle covered by the trip zone.
❑ Minimum V polarization (V). Indicates the minimum voltage for polarization; the direction cannot be reliably determined
below this value.
❑ Offset Z2 (Ohm). Offset impedance for the negative sequence directional unit. In multifunction, it must be set to 0.
❑ Minimum I2 / I1 Ph (%).Indicates the minimum value of I2 in relation to the percentage of I1.
❑ Minimum 3I2 / Irated (%). Percentage of rated I. Indicates the minimum value of I2 in relation to rated I.
❑ Blocking Input. Selects the signal which, when active, blocks the function. When the directional is blocked, it is issues
permission for the trip.
❑ S2 Directional inversion. Selects the signal which, when active, inverts the trip direction.
❑ Enable Events record. Allows the generation of protection events associated to the function. If set to “NO”, the function’s
protection events are not generate. If set to “YES”, the function’s specific mask is contemplated.
❑ Permission with low Vpol 67Q4. Indicates the functioning of the directional when the polarization voltage is below the set
threshold. If set to “YES”, it enables an unbalance overcurrent trip if the polarization voltage is lower than the "Minimum V
polarization (V)" setting; if set to “NO”, the unbalance overcurrent trip is not allowed under those conditions.
Table 32 Negative sequence directional settings

Data Setting Minimum Maximum Step Remarks Type


ChrAng Torque angle (º) 0 359 1 float32
Amp (AmpVal in Ed2) Zone amplitude (º) 90 170 1 float32
Vpol Minimum V polarization (V) 1 200 0,1 float32
Ofs Offset Z2 (Ohm) 0 100 1 float32
BlkValI1 Minimum I2 / I1 Ph (%) 1 100 1 Value % of I1 float32
BlkValIn Minimum 3I2 / Irated (%) 1 100 1 Value % of In float32
LogInInvDir S2 Directional inversion int32
LogInBlDir Blocking input int32
MaskEna Enable Events record NO / YES Boolean
TripVpol Permission with low Vpol 67Q NO / YES Boolean

4
Avaliable from firmware version 6.0.8.0 and ICD version 8.1.0.4

Ingeteam Power Technology S.A.


User Manual 92
PROTECTION FUNCTIONS

The negative sequence unit has settings, commands and outputs:

❑ Node: PROT/S2RDIR1
❑ Settings and logical inputs. There are 6 settings tables. See Table 32.
❑ Commands:
 “DOrdBlk”: Function blocking and unblocking.
 “DOrdInvDir”. Inverts the directional trip direction
❑ Outputs: Table 33 shows the function’s output data.
 67-S2 Forward. The detected direction indicates forward.
 67-S2 Reverse. The detected direction indicates reverse.
 Polarization Failure S2. Indicates that the direction has not been detected due to a polarization failure.
 S2 Directional Inhibition. Indicates that the directional is inhibited.
 S2 Direction Inversion. Indicates that the direction is opposite to the setting.
Table 33 Negative sequence directional outputs

Signal Data Attribute


67-S2 Forward Fw67S2 general
67-S2 Reverse Rv67S2 general
Polarization Failure S2 FailS2 general
S2 Directional Inhibition BlkDir general
S2 Direction Inversion InvDir general

Figure 61 Negative sequence directional

Ingeteam Power Technology S.A.


User Manual 93
PROTECTION FUNCTIONS

Figure 62 Negative sequence directional scheme

3.3.2.3 Ground directional


Affects neutral units, allowing or blocking the trip in accordance with the configuration.

The operation can be selected from among: angular, cosine, sine and watt-metric. Various options can be selected from within
the angular criteria.

This unit’s settings are in the PROT/GRDIR node. In accordance with the selected mode, they affect:

General settings.

❑ Ground directional method. Indicates the directional criterion used.


 “Angular criteria”.
 “I·cos phi”
 “I·sin phi”
 “Wattmetric”
❑ Minimum 3I0/Irated gnd (%). Percentage of rated neutral current. Indicates the minimum value of 3 I0 in relation to rated
I. It is used in zero sequence “I·cos” and “I·sin” mode.
❑ Ground directional block. Selects the signal which, when active, blocks the function. When the directional is blocked, it is
issues permission for the trip.
❑ 67N directional Inversion. Selects the signal which, when active, inverts the trip direction.
❑ Enable Events record. Allows the generation of protection events associated to the function. If set to “NO”, the function’s
protection events are not generate. If set to “YES”, the function’s specific mask is contemplated.
Settings with "Ground directional method" as Angular:

❑ Polarization method. Selected the polarization type from the options:


 V. By voltage.
 IPOL. By current
 IPOL → V. By current and, in the event of uncertainty, by voltage.
 IPOL or V. By current or by voltage.
 IPOL and V. By current and by voltage.

Ingeteam Power Technology S.A.


User Manual 94
PROTECTION FUNCTIONS

❑ Voltage directional Type. Only applied if the polarization voltage has been selected.
 S0. Zero sequence.
 S2. Negative sequence.
 S2 and S0. Negative and zero sequence.
 S2 or S0. Negative or zero sequence.
 S2 →S0. Negative sequence and, in the event of uncertainty, zero sequence.
 S0 →S2. Zero sequence and, in the event of uncertainty, negative sequence.
❑ Torque angle (º). Indicates the directional angle.
❑ Zone amplitude (º). Indicates the angle covered by the trip zone.
❑ Minimum V polarization (V). Indicates the minimum voltage for polarization; the direction cannot be reliably determined
below this value.
❑ Permission with low Vpol. Indicates the functioning of the directional when the polarization voltage is below the threshold.
If set to “YES”, it enables an overcurrent trip if the memorized polarization voltage is lower than the minimum polarization
voltage; if set to “NO”, the overcurrent trip is not allowed under those conditions.
❑ Minimum Ipol/Irated gnd (%). Indicates the minimum current for polarization; the direction cannot be reliably determined
below this value.
❑ Offset Z0 (Ohm). Offset impedance for the zero sequence directional unit.
❑ Minimum 3I0/I1 (%). Percentage of I1. Indicates the minimum value of I0 in relation to I1.
Settings with "Ground directional method" as Watt-metric, I·cos, I·sin

❑ Minimum power: Isin, Icos, W: Power value P=Vn·In·cos(-c), in which =Angle between Vn and In. If the power negative
and higher than this value, a forward fault is registered. If it is positive and higher than this value, a reverse fault is
registered.
❑ Icos/Isin method switch. If a signal is assigned to this input, it indicates the directional type used (independent of the
setting) I·cos if the input is 0 (deactivated) and I·sin if the input is 1 (activated). If no signal has been assigned, the
criterion selected for the setting is used.
The neutral units have settings, commands and outputs:

❑ Node: PROT/GRDIR1
❑ Settings and logical inputs. There are 6 settings tables. See Table 34 for details.
❑ Commands:
 “DOrdBlk”: Function blocking and unblocking.
 “DOrdInvDir”. Inverts the directional trip direction.
❑ Outputs: Table 35 shows the function’s output data.
 67N-Forward. The detected direction indicates forward.
 67N-Reverse. The detected direction indicates reverse.
 Polarization Failure In. It indicates that the direction has not been detected due to a polarization failure.
 Gnd directional inhibition. Indicates that the directional is inhibited.
 Ground direction inversion. Indicates that the direction is opposite to the setting.

Ingeteam Power Technology S.A.


User Manual 95
PROTECTION FUNCTIONS

Table 34 Neutral directional settings

Data Setting Minimum Maximum Step Remarks Type


“Angular criteria”
DirTyp “Icos phi”
Ground Directional method enum
“Isin phi”
“Wattmetric”
ChrAng Torque angle(º) 0 359 1 float32
Amp (AmpVal in Ed2) Zone amplitude (º) 90 170 1 float32
BlkValV Minimum V polarization (V) 1 200 0,1 float32
BlkValIn Minimum 3I0/Irated gnd (%) 1 100 1 Value % of I1 float32
LogInInvDir 67N directional Inversion int32
LogInBlDir Ground directional block int32
LogInChSC Icos/Isin method switch int32
V
IPOL
PolTyp
Polarization method IPOL → V enum
IPOL or V
IPOL and V
S0
S2
S2 and S0
PolQty (PolSel in Ed2) Voltage directional Type enum
S2 or S0
S2 →S0
S0 →S2
Ofs Offset Z0 (Ohm) 0 100 1 float32
BlkValI1 Minimum 3I0/I1 (%) 1 100 1 Value % of In float32
EnaOpn (TripVpol in Ed2) Permission with low Vpol NO / YES Boolean
BlkValIpol Minimum Ipol/Irated gnd (%) 1 100 1 Value % of I1 float32
BlkValW Minimum power: Isin,Icos,W 0 100 0,01 float32
MaskEna Enable Events record NO / YES Boolean

Table 35 Neutral directional outputs

Signal Data Attribute


67N-Forward Fw67G neut
67N-Reverse Rv67G neut
Polarization Failure In FailIn neut
Gnd Directional Inhibition BlkDir neut
Ground Direction Inversion InvDir neut

3.3.2.3.1 Combinations with angular criteria


The In=3·I0 measurement can be calculated as the sum of the phase currents or as the measurement of the neutral
transformer, depending on the setting "I0 type: measured/calculated" in the node "PROT/TCIN1".

Polarizations

The various combinations according to the setting "Polarization method" are:

If Ineutral is less than "Minimum 3I0/Irated gnd (%)" of the neutral rated current or less than "Minimum 3I0/I1 (%)" of the
positive sequence current (I1), a “Polarization Failure In” is issued and no other actions are taken.

It is polarized by voltage. Depending on the setting "Voltage directional Type", the polarization voltage can be the zero
sequence, negative sequence or both.

Ipol

If Ineutral is less than "Minimum 3I0/Irated gnd (%)" of the neutral rated current or less than "Minimum 3I0/I1 (%)" of the
positive sequence current (I1), a “Polarization Failure In” is issued and no other actions are taken.

Ingeteam Power Technology S.A.


User Manual 96
PROTECTION FUNCTIONS

It is polarized by the ground current (Ipol). See 3.3.2.3.3.

I→V

If Ineutral is less than "Minimum 3I0/Irated gnd (%)" of the neutral rated current or less than "Minimum 3I0/I1 (%)" of the
positive sequence current (I1), a “Polarization Failure In” is issued and no other actions are taken.

If the I unit does not determine the polarization fault direction, the voltage signal combination is analysed.

If the result is “Without VPOL”, that is, the polarization voltage is below the setting "Minimum V polarization (V)", the trip
permission depends on the setting "Permission with low Vpol".

I and V

If Ineutral is less than "Minimum 3I0/Irated gnd (%)" of the neutral rated current or less than "Minimum 3I0/I1 (%)" of the
positive sequence current (I1), a “Polarization Failure In” is issued and no other actions are taken.

Both units (Ipol and V) are analysed. If both give the same result, a forward or reverse indication is made. It the result is
different, there is no permission.

If any of them does not determine the direction, a “Polarization Failure In” message is indicated and a decision is taken in
accordance with the “Permission with low Vpol” setting.

This combination is applicable to autotransformer when there is a malfunction of Ipol.

I or V

If Ineutral is less than "Minimum 3I0/Irated gnd (%)" of the neutral rated current or less than "Minimum 3I0/I1 (%)" of the
positive sequence current (I1), a “Polarization Failure In” is issued and no other actions are taken.

Both units (Ipol and V) are analysed. If any of them indicates forward or reverse, the corresponding signal is activated. If
one indicates forward and the other reverse, both directions are activated.

If they do not determine the direction, a “Polarization Failure In” message is indicated and a decision is taken in accordance
with the “Permission with low Vpol” setting.

Voltage directional Type

Furthermore, with this setting it can be selected among the following options:

S0

The direction is determined with the neutral current and the neutral voltage as polarization (See 3.3.2.3.2).

S2

The direction is determined with the negative sequence current and the negative sequence voltage as polarization (See
3.3.2.2).

S0 and S2

Both units (S2 and S0) are analysed. If both give the same result, a forward or reverse indication is made. It the result is
different, there is no permission.

If any of them (S0 or S2) does not determine the direction, a "Polarization Failure In” or "Polarization Failure S2" message is
indicated and a decision is taken in accordance with the “Permission with low Vpol” setting.

Specific situations:

One unit set in reverse and one set forward. S0 indicates reverse and S2 forward. No output is given.

Ingeteam Power Technology S.A.


User Manual 97
PROTECTION FUNCTIONS

V0 V2 Result
F F F
F R Nothing
R R R
R F Nothing
F Without Vpol Without Vpol
R Without Vpol Without Vpol
Without Vpol F Without Vpol
Without Vpol R Without Vpol
Without Vpol Without Vpol Without Vpol
S0 or S2

Both units (S2 and S0) are analysed. If any of them indicates forward or reverse, the corresponding signal is activated. If one
indicated forward and the other reverse, both directions are activated.

If both of them (S0 or S2) do not determine the direction, a "Polarization Failure In” or "Polarization Failure S2" message is
indicated and a decision is taken in accordance with the “Permission with low Vpol” setting.

Specific situations:

V0 V2 Result
F F F
F R F&R
R R R
R F F&R
F Without Vpol F
R Without Vpol R
Without Vpol F F
Without Vpol R R
Without Vpol Without Vpol Without Vpol
S2 → S0

If the S2 unit does not determine the direction, a “Polarization Failure S2” signal is activated and S0 is analysed.

If the conditions for determining the direction are still not given, a “Polarization Failure In” signal is activated and a decision
is taken in accordance with the “Permission with low Vpol” setting.

Example of specific situations:

One unit set in reverse and one set forward. S2 indicates reverse and S0 forward. Only reverse would be signalled (due to
S2).

S2 S0 Result
F F or R or Without Vpol F
R F or R or Without Vpol R
Without Vpol F F
Without Vpol R R
Without Vpol Without Vpol Without Vpol
S0 → S2

If the S0 unit does not determine the direction, a “Polarization Failure In” signal is activated and S2 is analysed.

If the conditions for determining the direction are still not given, a “Polarization Failure S2” signal is activated and a decision
is taken in accordance with the “Permission with low Vpol” setting.

Example of specific situations:

One unit set in reverse and one set forward. S0 indicates reverse and S2 forward. Only reverse would be signalled (due to
S0).

S0 S2 Result
F F or R or Without Vpol F
R F or R or Without Vpol R
Without Vpol F F
Without Vpol R R
Without Vpol Without Vpol Without Vpol

Ingeteam Power Technology S.A.


User Manual 98
PROTECTION FUNCTIONS

3.3.2.3.2 S0 polarization
The direction is determined by comparing the neutral current with the neutral voltage as polarization. The angle
determines the range in which the fault is considered as a forward fault and as a reverse fault. A Z0offset setting, which
modifies the polarization voltage, is included.
π
S0pol = −VN + IN ∙ Z0Offset ∙ ej∙MTA_S0∙180
π
S0op = IN ∙ ej∙MTA_S0∙180

Where, MTA_S0 is the setting "Torque angle (º)"

It signals forward when

Amplitude º
|angle(S0pol) − angle(S0op)| < ( )
2
Where, Amplitude is the setting "Zone amplitude (º)"

The In=3·I0 measurement can be calculated as the sum of the phase currents or as the measurement of the neutral
transformer, depending on the setting "I0 type: measured/calculated" in the node "PROT/TCIN1".

The VN=3·V0 voltage can be calculated using the phase to earth voltages of the phases or it can be measured by a
transformer, in accordance with the “3V0 Operating quantity” setting in the PROT/PVGE1 node.

If Z0offset is not used:

S0pol is -3·V0

If Z0offset is used:

❑ With series compensation:


 S0pol is calculated with Z0Offset
❑ Without series compensation:
 S0pol depends on the relation between S0pol and the setting "Minimum V polarization". If the S0pol calculated
with Z0Offset is greater than "Minimum V polarization (V)", the calculated S0pol is used. On the other hand, if "-
3·V0" is greater than "Minimum V polarization (V)", S0pol = "-3·V0 is used.
There is a 5º zone between the non-trip zone and the trip zone in which the current directional status is maintained.

Figure 63 Zero sequence directional

Trip permission with low Vpol

When the S0pol polarization voltage is below the setting "Minimum V polarization (V)" or the neutral current is below to any of
the thresholds "Minimum 3I0 / Irated (%)" and "Minimum 3I0 / I1 (%)", “Polarization Failure In” is indicated.

The directional block is used when the neutral current is below to any of the thresholds "Minimum 3I0 / Irated (%)" and
"Minimum 3I0 / I1 (%)".

If S0pol is below the setting "Minimum V polarization (V)" and the operation current is greater than the thresholds "Minimum
3I0 / Irated (%)" and "Minimum 3I0 / I1 (%)", if the trip permission without polarization V is set to “YES”, the trip is permitted;
while if set to “NO”, it is blocked.

Ingeteam Power Technology S.A.


User Manual 99
PROTECTION FUNCTIONS

Figure 64 Zero sequence directional scheme

3.3.2.3.3 I polarization
The direction is determined by comparing the ground current (Ipol) with the neutral current. To be able to verify the
direction, Ipol must be greater than the percent of neutral rated current indicated in the setting "Minimum Ipol/Irated gnd
(%)".

The In=3·I0 measurement can be calculated as the sum of the phase currents or as the measurement of the neutral
transformer, depending on the setting "I0 type: measured/calculated" in the node "PROT/TCIN1".

Figure 65 Directional with current polarization

There is a 5º zone between the non-trip zone and the trip zone in which the current directional status is maintained, both
for voltage and for current polarization.

Trip permission with low Vpol

When the neutral current is below any of the thresholds "Minimum 3I0 / Irated (%)" and "Minimum 3I0 / I1 (%)",
“Polarization Failure In” is indicated.

When the Ipol is below to the percent of neutral rated current indicated in the setting "Minimum Ipol/Irated (%)",
“Polarization Failure In” is indicated. In this case, there is “NO” trip permission.

Ingeteam Power Technology S.A.


User Manual 100
PROTECTION FUNCTIONS

3.3.2.3.4 Watt-metric directional


This is for lines with Petersen coil compensation.

The In=3·I0 measurement can be calculated as the sum of the phase currents o as the measurement of the neutral
transformer, depending on the setting "I0 type" in the node "PROT/TCIN1".

The VN=3·V0 voltage can be calculated using the phase to earth voltages of the phases or it can be measured by a
transformer, in accordance with the “V0 measurement type” setting in the PROT/PVGE1 node.

In order to allow the directional unit to pickup, the following must be met:

❑ Vn exceeds the setting "Minimum V polarization (V)".


❑ For forward faults, the angle between the current and the displaced voltage, the maximum torque angle must be
between 95 and 265.
95º < 𝑎𝑛𝑔𝑙𝑒(𝐼0) − 𝑎𝑛𝑔𝑙𝑒(𝑉0) + 𝑇𝑜𝑟𝑞𝑢𝑒 𝑎𝑛𝑔𝑙𝑒 < 265º

❑ For reverse faults, the angle between the current and the displaced voltage, the maximum torque angle must be
between 275 and 85.
275º < 𝑎𝑛𝑔𝑙𝑒(𝐼0) − 𝑎𝑛𝑔𝑙𝑒(𝑉0) + 𝑇𝑜𝑟𝑞𝑢𝑒𝑎𝑛𝑔𝑙𝑒 < 85º

❑ The power P=Vn·In·cos(-c) must exceed the minimum power "Minimum power: Isin, Icos, W" by the absolute
value. If the sign of P is negative, the fault is forward. If positive, the fault is reverse.
The equation to be implemented for calculating P is as follows:

P = [Re(V0) ∙ cos c + Im(V0) ∙ sin c] ∙ Re(I0) + [Im(V0) ∙ cos c − Re(V0) ∙ sin c] ∙ Im(I0)

c = Torque angle

 = 𝑎𝑛𝑔𝑙𝑒(𝑉0) − 𝑎𝑛𝑔𝑙𝑒(𝐼0)
Figure 66 Directional with watt-metric polarization

Trip permission without V polarization

If the voltage VN is lower than "Minimum V polarization (V)", "Polarization Failure In" is indicated. If "Permission with low
Vpol" is set to "YES", the trip is allowed, if it is set to "NO", it is blocked.

3.3.2.3.5 I*cos() / I*sin() directional


The In=3·I0 measurement can be calculated as the sum of the phase currents o as the measurement of the neutral
transformer, depending on the setting "I0 type" in the node "PROT/TCIN1".

The VN=3·V0 voltage can be calculated using the phase to earth voltages of the phases or it can be measured by a
transformer, in accordance with the “V0 measurement type” setting in the PROT/PVGE1 node.

An input can be programmed (“Icos/Isin method switch”) such that when activated the operating mode of I*cos() changes
to I*sin(). If programmed, this input cancels the setting: if deactivated, it runs the I*cos() algorithm. If activated, the
I*sin() algorithm is run, independently of the setting. It does not affect either the angular of the watt-metric directional.

Ingeteam Power Technology S.A.


User Manual 101
PROTECTION FUNCTIONS

I*cos() directional

In order to allow the directional unit to pickup, the following must be met:

❑ Vn exceeds the setting "Minimum V polarization (V)".


❑ For forward faults, the angle between the current and the displaced voltage, the maximum torque angle must be
between 95 and 265.
95º < a𝑛𝑔𝑙𝑒(𝐼0) − a𝑛𝑔𝑙𝑒(𝑉0) + 𝑇𝑜𝑟𝑞𝑢𝑒 𝑎𝑛𝑔𝑙𝑒 < 265º

❑ For reverse faults, the angle between the current and the displaced voltage, the maximum torque angle must be
between 275 and 85.
275º < a𝑛𝑔𝑙𝑒(𝐼0) − a𝑛𝑔𝑙𝑒(𝑉0) + 𝑇𝑜𝑟𝑞𝑢𝑒 𝑎𝑛𝑔𝑙𝑒 < 85º

❑ The minimum current "I minimum= In·cos(-c)" must exceed the minimum threshold "Minimum 3I0 / Irated (%)"
by the absolute value. If the sign is negative, the fault is forward. If positive, the fault is reverse.
[Re(V0) ∙ cos c + Im(V0) ∙ sin c] ∙ Re(I0) + [Im(V0) ∙ cos c − Re(V0) ∙ sin c] ∙ Im(I0)
I0 ∙ cos( − c) =
|V0|

c = Torque angle

 = angle(V0) − angle(I0)

Figure 67 Directional with cosine polarization

As the neutral units allow trip permission to be issued with forward and with reverse faults, in reality the characteristics will
be as follows.

Figure 68 Forward/Reverse with cosine polarization

Trip permission without V polarization

If the voltage VN is lower than "Minimum V polarization (V)", "Polarization Failure In" is indicated. If "Permission with low
Vpol" is set to "YES", the trip is allowed, if it is set to "NO", it is blocked.

Ingeteam Power Technology S.A.


User Manual 102
PROTECTION FUNCTIONS

67N I*sin() directional

In order to allow the directional unit to pickup, the following must be met:

❑ Vn exceeds the setting "Minimum V polarization (V)". For forward faults, the angle between the current and the
displaced voltage, the maximum torque angle must be between 185 and 355.
185º < 𝑎𝑛𝑔𝑙𝑒(𝐼0) − 𝑎𝑛𝑔𝑙𝑒(𝑉0) + 𝑇𝑜𝑟𝑞𝑢𝑒 𝑎𝑛𝑔𝑙𝑒 < 355º

❑ For reverse faults, the angle between the current and the displaced voltage, the maximum torque angle must be
between 5 and 175.
5º < 𝑎𝑛𝑔𝑙𝑒(𝐼0) − 𝑎𝑛𝑔𝑙𝑒(𝑉0) + 𝑇𝑜𝑟𝑞𝑢𝑒𝑎𝑛𝑔𝑙𝑒 < 175º

❑ The minimum current "I minimum=In·sin(-c)" must exceed the minimum threshold "Minimum 3I0 / Irated (%)"
by the absolute value. If the sign is negative, the fault is forward. If positive, the fault is reverse.
[Im(V0) ∙ cos c − Re(V0) ∙ sin c] ∙ Re(I0) − [Re(V0) ∙ cos c + Im(V0) ∙ sin c] ∙ Im(I0)
I0 ∙ sin( − c) =
|V0|

c = Torque angle

 = 𝑎𝑛𝑔𝑙𝑒(𝑉0) − 𝑎𝑛𝑔𝑙𝑒(𝐼0)
Figure 69 Directional with sine polarization

Trip permission without V polarization

If the voltage VN is lower than "Minimum V polarization (V)", "Polarization Failure In" is indicated. If "Permission with low
Vpol" is set to "YES", the trip is allowed, if it is set to "NO", it is blocked.

3.3.3 Polarization memory monitoring


It is used in the polarization of the phase directional (positive sequence and quadrature) and in the distance units (mho
characteristics).

Allows the memorized voltage to be used during the configured time when the current voltage is not apt.

This unit’s operating scheme for the distance unit is:

❑ If V1> Minimum V1 is met during at least 4 cycles, the memorized voltage is captured once again.
❑ V1mem is then update to the V1 value registered 3 cycles previously. Thus, in the moment in which the conditions for
using it are met, the value registered 3 cycles previously will be taken.
❑ V1mem is captured in the moment the voltage is above the setting Minimum V1 and is used during the time set in "V1
maintenance time".
❑ If the breaker is open (open pole logic) with the V1 above the setting "Minimum V1", the voltage V1 without memory is
used.
❑ If the series compensation logic is enabled, node PROT.PSEC1, the memorized voltage is used when the fault detection is
activated.

Ingeteam Power Technology S.A.


User Manual 103
PROTECTION FUNCTIONS

❑ If the "Blocking by power swinging" signal is activated, the actual V1 is used (not memorized)
❑ The logic input "Force V1 with memory" forces the use of memorized voltage in the positive sequence polarization.
❑ The logic input "Force V1 without memory" forces the use of non-memorized voltage in the positive sequence polarization.
This unit’s operating scheme for the overcurrent directional units is:

❑ If Vx> Minimum Vx is met during at least 4 cycles, the memorized voltage is captured once again.
❑ Vxmen is then update to the Vx value registered 3 cycles previously. Thus, in the moment in which the conditions for using
it are met, the value registered 3 cycles previously will be taken.
❑ The 67-50/51 units are normally polarized without memory. The memorized voltage is used in the moment in which the
actual Vx voltage drops below Minimum Vx. The memory time is indicated in the maintenance time setting.
❑ If the series compensation is enabled, node PROT.PSEC1, the memorized voltage is used when the fault detection is
activated.
❑ The logic input "Force Vx with memory" forces the use of memorized voltage in the positive sequence polarization.
❑ The logic input "Force Vx without memory" forces the use of non-memorized voltage in the positive sequence polarization.
The positive sequence voltage (V1) and the quadrature voltages are analysed separately (Vab, Vbc and Vac).

The function’s logic diagram is shown in Figure 70 (distance units), Figure 71 (overcurrent units, positive sequence) and Figure
72 (overcurrent units, quadrature).

This unit’s settings are:

❑ Minimum V1 (V). Indicates the minimum V1 value for employing the memorized voltage.
❑ V1 Memory Time (ms). Indicates the time during which the memorized voltage is used in the polarization by positive
sequence.
❑ Minimum Ph-ph voltage (V). Indicates the minimum quadrature voltage for employing the memorized voltage.
❑ Vc Memory Time (ms). Indicates the time during which the memorized voltage is used in the polarization by quadrature.
❑ Force V1 with memory. Forces the use of memorized voltage in the positive sequence polarization.
❑ Force V1 without memory. Forces the use of non-memorized voltage in the positive sequence polarization.
❑ Force Vc with memory. Forces the use of memorized voltage in the quadrature polarization.
❑ Force Vc without memory. Forces the use of non-memorized voltage in the quadrature polarization.
❑ Enable Events record. Allows the generation of protection events associated to the function. If set to “NO”, the function’s
protection events are not generate. If set to “YES”, the function’s specific mask is contemplated.
Table 36 Directional memory monitoring settings

Data Setting Minimum Maximum Step Remarks Type


ValV1 Minimum V1 (V) float
MemV1Tmms V1 Memory Time (ms) int32
ValVc Minimum Ph-ph voltage (V) float
MemVcTmms VC Memory Time (ms) int32
LogInFV1M Force V1 without memory. int32
LogInFV1NM Force V1 with memory int32
LogInFVcM Force Vc without memory. int32
LogInFVcNM Force Vc with memory int32
MaskEna Enable Events record NO / YES Boolean

The memory monitoring units have settings and outputs:

❑ Node: PROT/MSUPPTRC1
❑ Settings and logical inputs. There are 6 settings tables. For details, see Table 36.
❑ Outputs:
 Memorized Ph-Ph Voltage. It is activated while the memorized phase-phase voltage is being used.
 V1 memorized. It is activated while the memorized V1 is being used.

Ingeteam Power Technology S.A.


User Manual 104
PROTECTION FUNCTIONS

 V1 memorized distance. It is activated while the memorized V1 is being used in the distance units.
The input signals of these schemes are:

❑ Fault detection. It´s the output of the Fault detection unit.


❑ Power swing blocking. Blocked by the Power swing detector.
❑ The digital inputs are the settings of the function:
 Force V1 with memory
 Force V1 without memory
 Force VAB with memory. It is the setting "Force Vc with memory".
 Force VAB without memory. It is the setting "Force Vc without memory"

Table 37 Memorized voltage monitoring outputs

Signal Data Attribute


Memorized Ph-Ph Voltage Vcomp general
V1 memorized V1mem general
V1 memorized distance V1dist general

Figure 70 Distance units. Positive sequence memorized monitoring

Ingeteam Power Technology S.A.


User Manual 105
PROTECTION FUNCTIONS

Figure 71 Positive sequence memorized monitoring

Figure 72 Memorized quadrature monitoring

3.3.4 Series compensation


It affects the polarization signal of the distance and overcurrent units.

If it is enabled, the memorized voltage is used when the voltage is below the threshold set or when the fault detection is
activated. This unit applies to the distance and the phase overcurrent units.

The settings are as follows:

❑ Enabled: Enables the function.


❑ Enable Events record. Allows the generation of protection events associated to the function. If set to “NO”, the function’s
protection events are not generated. If set to “YES”, the function’s specific mask is contemplated.
There are settings and outputs:

❑ Node: PROT/PSEC1
❑ Settings and logical inputs. There are 6 settings tables. For details, see Table 38
❑ Outputs: Table 39 shows the function's output data
 Series compensation status: Indicates the function’s status. It is active when enabled and not blocked.

Ingeteam Power Technology S.A.


User Manual 106
PROTECTION FUNCTIONS

Table 38 Series Compensation settings

Data Setting Minimum Maximum Step Remarks Type


SeCoEna Enabled NO / YES enum
MaskEna Enable Events Record NO / YES Boolean

Table 39 Series compensation Outputs

Signal Data Attribute


Series compensation status StEna general (stVal in Ed2)

3.3.5 Phase overcurrent

3.3.5.1 Instantaneous
There are 3 independent units for each of the phases.

Each of the three units has independent settings, commands and outputs.

❑ Nodes:
 Unit 1: PROT/PIOC1
 Unit 2: PROT/PIOC2
 Unit 3: PROT/PIOC3
❑ Settings and logical inputs. There are 6 settings tables. See Table 29.
❑ Commands:
 “DOrdBlk”: Function blocking and unblocking. Only acts when the function is enabled.
❑ Outputs: Table 40 shows the function’s output data.
 IOC1 Start phase X. Indicates that the unit's phase has picked up. It is independent for each phase. Where X is the
phase.
 IOC1 Trip phase X. Indicates that the unit's phase has tripped. It is independent for each phase. Where X is the phase.
 IOC1 Phase Status. Indicates the function’s status. It is active when enabled and not blocked. This is general for all
three phases.
 IOC1 phase Start. Indicates that the unit has picked up
 IOC1 phase Trip. Indicates that the unit has tripped.

Table 40 Instantaneous phase function outputs

Signal PIOC1 Signal PIOC2 Signal PIOC3 Data Attribute


IOC1 Start phase A IOC2 Start phase A IOC3 Start phase A Str phsA
IOC1 Start phase B IOC2 Start phase B IOC3 Start phase B Str phsB
IOC1 Start phase C IOC2 Start phase C IOC3 Start phase C Str phsC
IOC1 Trip phase A IOC2 Trip phase A IOC3 Trip phase A Op phsA
IOC1 Trip phase B IOC2 Trip phase B IOC3 Trip phase B Op phsB
IOC1 Trip phase C IOC2 Trip phase C IOC3 Trip phase C Op phsC
IOC1 Phase Status IOC2 Phase Status IOC3 Phase Status StEna stVal
IOC1 Phase Start IOC2 Phase Start IOC3 Phase Start Str general
IOC1 Phase Trip IOC2 Phase Trip IOC3 Phase Trip Op general

3.3.5.2 Timed
There are 3 independent units for each of the phases.

Each of the three units has independent settings, commands and outputs.

Ingeteam Power Technology S.A.


User Manual 107
PROTECTION FUNCTIONS

❑ Nodes:
 Unit 1: PROT/PTOC1
 Unit 2: PROT/PTOC2
 Unit 3: PROT/PTOC3
❑ Settings and logical inputs. There are 6 settings tables. See Table 28.
❑ Commands:
 “DOrdBlk”: Function blocking and unblocking. Only acts when the function is enabled.
❑ Outputs: Table 41 shows the function’s output data.
 TOC1 Start phase X. Indicates that the unit's phase has picked up. It is independent for each phase. Where X is the
phase.
 TOC1 Trip phase X. Indicates that the unit's phase has tripped. It is independent for each phase. Where X is the phase.
 TOC1 Phase Status. Indicates the function’s status. It is active when enabled and not blocked. This is general for all
three phases.
 TOC1 Phase Start. Indicates that the unit has picked up
 TOC1 Phase Trip. Indicates that the unit has tripped.
Table 41 Timed phase function outputs

Signal PTOC1 Signal PTOC2 Signal PTOC3 Data Attribute


TOC1 Start phase A TOC2 Start phase A TOC3 Start phase A Str phsA
TOC1 Start phase B TOC2 Start phase B TOC3 Start phase B Str phsB
TOC1 Start phase C TOC2 Start phase C TOC3 Start phase C Str phsC
TOC1 Trip phase A TOC2 Trip phase A TOC3 Trip phase A Op phsA
TOC1 Trip phase B TOC2 Trip phase B TOC3 Trip phase B Op phsB
TOC1 Trip phase C TOC2 Trip phase C TOC3 Trip phase C Op phsC
TOC1 Phase Status TOC2 Phase Status TOC3 Phase Status StEna stVal
TOC1 Phase Start TOC2 Phase Start TOC3 Phase Start Str general
TOC1 Phase Trip TOC2 Phase Trip TOC3 Phase Trip Op general

3.3.6 Neutral overcurrent


Uses the neutral transformer input or 3·I0, depending on the setting "I0 type: measured/calculated" in the node "PROT/TCIN1". In
the 52 ½ models only 3·I0 is allowed.

3.3.6.1 Instantaneous
There are 3 independent units.

Each of the three units has independent settings, commands and outputs.

❑ Nodes:
 Unit 1: PROT/GPIOC1
 Unit 2: PROT/GPIOC2
 Unit 3: PROT/GPIOC3
❑ Settings and logical inputs. There are 6 settings tables. See Table 29.
❑ Commands:
 “DOrdBlk”: Function blocking and unblocking. Only acts when the function is enabled.
❑ Outputs: Table 42 shows the function’s output data.
 GIOC1 Start. Indicates that the unit has picked up.
 GIOC1 Trip. Indicates that the unit has tripped.

Ingeteam Power Technology S.A.


User Manual 108
PROTECTION FUNCTIONS

 IOC1 Ground Status. Indicates the function’s status. It is active when enabled and not blocked.
Table 42 Neutral instantaneous function outputs

Signal GIOC1 Signal GIOC2 Signal GIOC3 Data Attribute


GIOC1 Start GIOC2 Start GIOC3 Start Str neut
GIOC1 Trip GIOC2 Trip GIOC3 Trip Op neut
IOC1 Ground Status IOC2 Ground Status IOC3 Ground Status StEna stVal

3.3.6.2 Timed
There are 3 independent units.

Each of the three units has independent settings, commands and outputs.

❑ Nodes:
 Unit 1: PROT/GPTOC1
 Unit 2: PROT/GPTOC2
 Unit 3: PROT/GPTOC3
❑ Settings and logical inputs. There are 6 settings tables. See Table 28.
❑ Commands:
 “DOrdBlk”: Function blocking and unblocking. Only acts when the function is enabled.
❑ Outputs: Table 43 shows the function’s output data.
 GTOC1 Start. Indicates that the unit has picked up.
 GTOC1 Trip. Indicates that the unit has tripped.
 TOC1 Ground Status. Indicates the function’s status. It is active when enabled and not blocked.

Table 43 Timed neutral function outputs

Signal GTOC1 Signal GTOC2 Signal GTOC3 Data Attribute


GTOC1 Start GTOC2 Start GTOC3 Start Str neut
GTOC1 Trip GTOC2 Trip GTOC3 Trip Op neut
TOC1 Ground Status TOC2 Ground Status TOC3 Ground Status StEna stVal

3.3.7 Grounding overcurrent


Not available on all models (see model functions).

Employs the polarization current transformer input as a measurement.

This unit is not directional.

3.3.7.1 Instantaneous
There are 3 independent units.

Each of the three units has independent settings, commands and outputs.

❑ Nodes:
 Unit 1: PROT/ESPIOC1
 Unit 2: PROT/ESPIOC2
 Unit 3: PROT/ESPIOC3
❑ Settings and logical inputs. There are 6 settings tables. See Table 29.
❑ Commands:

Ingeteam Power Technology S.A.


User Manual 109
PROTECTION FUNCTIONS

 “DOrdBlk”: Function blocking and unblocking. Only acts when the function is enabled.
❑ Outputs: Table 44 shows the function’s output data.
 ESIOC1 Start. Indicates that the unit has picked up.
 ESIOC1 Trip. Indicates that the unit has tripped.
 IOC1 Earthing System Status. Indicates the function’s status. It is active when enabled and not blocked.
Table 44 Instantaneous grounding function outputs

Signal ESIOC1 Signal ESIOC2 Signal ESIOC3 Data Attribute


ESIOC1 Start ESIOC2 Start ESIOC3 Start Str general
ESIOC1 Trip ESIOC2 Trip ESIOC3 Trip Op general
IOC1 Earthing System Status IOC2 Earthing System Status IOC3 Earthing System Status StEna stVal

3.3.7.2 Timed
There are 3 independent units.

Each of the three units has independent settings, commands and outputs.

❑ Nodes:
 Unit 1: PROT/ESPTOC1
 Unit 2: PROT/ESPTOC2
 Unit 3: PROT/ESPTOC3
❑ Settings and logical inputs. There are 6 settings tables. See Table 28.
❑ Commands:
 “DOrdBlk”: Function blocking and unblocking. Only acts when the function is enabled.
❑ Outputs: Table 45 shows the function’s output data.
 ESTOC1 Start. Indicates that the unit has picked up.
 ESTOC1 Trip. Indicates that the unit has tripped.
 TOC1 Earthing System Status. Indicates the function’s status. It is active when enabled and not blocked.

Table 45 Timed grounding function outputs

Signal ESTOC1 Signal ESTOC2 Signal ESTOC3 Data Attribute


ESTOC1 Start ESTOC2 Start ESTOC3 Start Str general
ESTOC1 Trip ESTOC2 Trip ESTOC3 Trip Op general
TOC1 Earthing System Status TOC2 Earthing System Status TOC3 Earthing System Status StEna stVal

3.3.8 Unbalanced overcurrent


Employs 3 times the negative sequence as a measurement:

3·I2 = (Ia+a2·Ib+a·Ic) In which a = 1|120º

The calculation of the sequence takes into phase succession order setting (ABC/ACB).

The negative sequence directional is used by this unit.

The measurement type setting is not used, as the fundamental is always used.

3.3.8.1 Instantaneous
There are 3 independent units.

Each of the three units has independent settings, commands and outputs.

Ingeteam Power Technology S.A.


User Manual 110
PROTECTION FUNCTIONS

❑ Nodes:
 Unit 1: PROT/UNPIOC1
 Unit 2: PROT/UNPIOC2
 Unit 3: PROT/UNPIOC3
❑ Settings and logical inputs. There are 6 settings tables. It employs the settings in Table 29, with the exception of the
measurement type.
❑ Commands:
 “DOrdBlk”: Function blocking and unblocking. Only acts when the function is enabled.
❑ Outputs: Table 46 shows the function’s output data.
 UNIOC1 Start. Indicates that the unit has picked up.
 UNIOC1 Trip. Indicates that the unit has tripped.
 IOC1 Unbalanced Status. Indicates the function’s status. It is active when enabled and not blocked.

Table 46 Instantaneous unbalanced function outputs

Signal UNIOC1 Signal UNIOC2 Signal UNIOC3 Data Attribute


UNIOC1 Start UNIOC2 Start UNIOC3 Start Str general
UNIOC1 Trip UNIOC2 Trip UNIOC3 Trip Op general
IOC1 Unbalanced Status IOC2 Unbalanced Status IOC3 Unbalanced Status StEna stVal

3.3.8.2 Timed
There are 3 independent units.

Each of the three units has independent settings, commands and outputs.

❑ Nodes:
 Unit 1: PROT/UNPTOC1
 Unit 2: PROT/UNPTOC2
 Unit 3: PROT/UNPTOC3
❑ Settings and logical inputs. There are 6 settings tables. Employs the settings in Table 28, with the exception of the
measurement type.
❑ Commands:
 “DOrdBlk”: Function blocking and unblocking. Only acts when the function is enabled.
❑ Outputs: Table 47 shows the function’s output data.
 UNTOC1 Start. Indicates that the unit has picked up.
 UNTOC1 Trip. Indicates that the unit has tripped.
 TOC1 Unbalanced Status. Indicates the function’s status. It is active when enabled and not blocked.

Table 47 Timed unbalanced function outputs

Signal UNTOC1 Signal UNTOC2 Signal UNTOC3 Data Attribute


UNTOC1 Start UNTOC2 Start UNTOC3 Start Str general
UNTOC1 Trip UNTOC2 Trip UNTOC3 Trip Op general
TOC1 Unbalanced Status TOC2 Unbalanced Status TOC3 Unbalanced Status StEna stVal

3.3.9 2nd harmonic restraint


It permits the instantaneous and timed phase, neutral and unbalanced overcurrent units to be blocked (51, 50, 51N, 50N and 67Q).

Restraint by phase or for all the phases is available for the 50/51 units. The units to be blocked are selected by settings.

Ingeteam Power Technology S.A.


User Manual 111
PROTECTION FUNCTIONS

To activate the restraint, the following must be met simultaneously:

❑ The fundamental current must exceed the minimum inrush value.


❑ The relationship between the 2nd harmonic value and the fundamental must exceed a set threshold.
❑ The 2nd harmonic current must exceed 1% of In (50mA with In=5A and 10ma with In=1A).
To deactivate the restraint, the following must be met:

❑ The current must be less than 95% of the minimum current threshold, or
❑ The current must be below 95% of the restraint percentage threshold.
The restraint is calculated independently for each phase and neutral.

The phase units’ restraint can act per phase (the restraint in any one phase only blocks the phase in question) or it can be general
(the restraint in any one phase blocks all the phases).

For the unbalanced unit restraint, it is sufficient that the conditions are given in a phase or in the neutral.

The units’ restraint settings are:

❑ Enabled. Indicates whether the function is enabled or not. The options available are:
 YES. It is enabled.
 NO. It is disabled.
 Only in close. It is enabled for a second after closing.
❑ I 2nd/fund. Threshold (%). Indicates the percentage of the 2nd harmonic in relation to the fundamental above which the
restraint is produced.
❑ Minimum current (A). Minimum value of the fundamental current in order for the restraint to be produced. No restraint is
indicated below this value, even when the % I 2nd/Ifund is above the setting.
❑ Restraint. Enables the units on which the restraint is to act to be indicated. There are separate settings for each unit. In
general, the setting is "NO / YES", except in those phases that can be:
 NO. Restraint is not permitted.
 Phase. The restraint in one phase only blocks the phase in question.
 General. The restraint in one phase blocks all the phases.
❑ Harm.Restraint Blocking. Selects the signal which, when active, blocks the function.
❑ Enable Events record. Allows the generation of protection events associated to the function. If set to “NO”, the function’s
protection events are not generate. If set to “YES”, the function’s specific mask is contemplated.
There are independent settings, commands and outputs in each restraint unit.

Phases
❑ Node: PROT/PHAR1
❑ Settings and logical inputs. There are 6 settings tables. For details, see Table 49. There is restraint setting for each timed
and instantaneous phase overcurrent unit (NO / Phase / General) and unbalanced (NO / YES)
❑ Commands:
 “DOrdBlk”: Function blocking and unblocking. Only acts when the function is enabled.
❑ Outputs:
 2nd harmonic restraint Ix. Indicates that the restraint has been activated in this phase. It is independent for each
phase.
 2nd harmonic restraint ph. Indicates that the restraint has been activated in one of the phases.
 Harm. Ph. restraint Status. Indicates the function’s status. It is active when enabled and not blocked. This is general for
all three phases.

Ingeteam Power Technology S.A.


User Manual 112
PROTECTION FUNCTIONS

Table 48 Phase restraint outputs

Signal Data Attribute


2nd harmonic restraint Ia Op phsA
2nd harmonic restraint Ib Op phsB
2nd harmonic restraint Ic Op phsC
2nd harmonic restraint ph Op general
Harm. Ph. restraint Status StEna stVal

Table 49 Phase 2nd harmonic restraint settings

Data Setting Min. Max Step Remarks Type


NO (0)
PHAREna Enabled YES (1) Boolean
Only in close (2)
StrVal I 2nd/fund. Threshold (%) 10 100 1 float32
BlkValA Minimum current (A) 0,1 150,0 0,01 float32
NO (0)
Restr51U1 Restraint 51 Unit 1 Phase (1) enum
General (2)
Restr51U2 Restraint 51 Unit 2 NO/Phase/General enum
Restr51U3 Restraint 51 Unit 3 NO/Phase/General enum
Restr50U1 Restraint 50 Unit 1 NO/Phase/General enum
Restr50U2 Restraint 50 Unit 2 NO/Phase/General enum
Restr50U3 Restraint 50 Unit 3 NO/Phase/General enum
Restr67QT1 Restraint 67QT Unit 1 NO / YES Boolean
Restr67QT2 Restraint 67QT Unit 2 NO / YES Boolean
Restr67QT3 Restraint 67QT Unit 3 NO / YES Boolean
Restr67QI1 Restraint 67QI Unit 1 NO / YES Boolean
Restr67QI2 Restraint 67QI Unit 2 NO / YES Boolean
Restr67QI3 Restraint 67QI Unit 3 NO / YES Boolean
LogInBlk Harm.Restraint Blocking int32
MaskEna Enable Events Record NO / YES Boolean

Neutral
❑ Node: PROT/GPHAR1
❑ Settings and logical inputs. There are 6 settings tables. For details, see Table 51. There is restraint setting for each timed
and instantaneous neutral overcurrent unit (NO / YES).
❑ Commands:
 “DOrdBlk”: Function blocking and unblocking. Only acts when the function is enabled.
❑ Outputs: Table 50 shows the function’s output data.
 2nd harmonic restraint In. It indicates that the neutral restraint has been activated.
 Harm. Gr. restraint Status. Indicates the function’s status. It is active when enabled and not blocked.

Table 50 Neutral restraint outputs

Signal Data Attribute


2nd harmonic restraint In Op neut
Harm. Gr. restraint Status StEna stVal

Ingeteam Power Technology S.A.


User Manual 113
PROTECTION FUNCTIONS

Table 51 Neutral 2nd harmonic restraint settings

Data Setting Min. Max Step Remarks Type


NO (0)
PHAREna Enabled YES (1) Boolean
Only in close (2)
StrVal I 2nd/fund. Threshold (%) 10 100 1 float32
BlkValA Minimum current (A) 0,1 150,0 0,01 float32
Restr51N1 Restraint 51N Unit 1 NO / YES Boolean
Restr51N2 Restraint 51N Unit 2 NO / YES Boolean
Restr51N3 Restraint 51N Unit 3 NO / YES Boolean
Restr50N1 Restraint 50N Unit 1 NO / YES Boolean
Restr50N2 Restraint 50N Unit 2 NO / YES Boolean
Restr50N3 Restraint 50N Unit 3 NO / YES Boolean
LogInBlk Harm.Restraint Blocking int32
MaskEna Enable Events Record NO / YES Boolean

3.3.10 Broken conductor


This is a definite time protection unit.

The pickup value to be set is, expressed as a decimal, and it depends on the setting "Operation type".

There are two modes of operation, selectable by setting. The relay trips once the programmed time has elapsed if the following
conditions are met:

❑ “Always”:
 The positive sequence is greater than 3% of I rated.
 The negative sequence is greater than 3% of I rated.
 I2/I1 ratio exceeds the setting value.
𝐼2 𝐼𝑎 + 𝑎2 · 𝐼𝑏 + 𝑎 · 𝐼𝑐
= 𝐼𝑛 𝑤ℎ𝑖𝑐ℎ, 𝑎 = 1∟120º
𝐼1 𝐼𝑎 + 𝑎 · 𝐼𝑏 + 𝑎2 · 𝐼𝑐

 Current value of one phase is greater than the setting "Minimum Phase I (%Irated)".

❑ “Yes with 52”:


 The positive sequence is greater than 3% of I rated.
 The negative sequence is greater than 3% of I rated.
 I2/Irated exceeds the setting value.
𝐼2 1 𝐼𝑎 + 𝑎2 · 𝐼𝑏 + 𝑎 · 𝐼𝑐
= ( ) 𝐼𝑛 𝑤ℎ𝑖𝑐ℎ, 𝑎 = 1∟120º
𝐼𝑟𝑎𝑡𝑒𝑑 3 𝐼𝑟𝑎𝑡𝑒𝑑

 I0/Irated: I0/Irated is bellow than the setting value. If set to 0, this setting will not be taken into account.
 If the breaker is closed, the current value of one or two phases is lower than the setting "Minimum Phase I (%Irated)".

Figure 73 shows the logic scheme of the function.

The settings used in these functions are:

❑ Enabled. Indicates whether the function is enabled or not.


❑ Operation type. To be selected between:
 “Always”
 “Yes with 52”
❑ Start value (%). If "Operation Type" is "Always", indicates the ratio I2/I1. In case of "Yes with 52", it indicates I2/Irated.
❑ Delay time (ms). Indicates the time during which the conditions for the tripping of the function must be met.

Ingeteam Power Technology S.A.


User Manual 114
PROTECTION FUNCTIONS

❑ Minimum Phase I (%Irated). Minimum phase current value.


❑ Max. Threshold I0/Irated (%). Maximum I0/Irated value (%) necessary to act.
❑ Blocking Input. Selects the signal which, when active, blocks the function.
❑ General trip. Indicates if this unit produces general trip or not. For additional details, see the section corresponding to the
recloser (3.12.6).
❑ Trip Permission by recloser. Indicates the trip and block permission in accordance with the recloser status: standby,
blocked, safety time after reclosing, after closing. It is configured bit by bit; for additional details, see section
corresponding to the recloser (3.12.6.3).
❑ Reclose perm.(R1,R2,R3,R4). Indicates whether each trip type can be reclosed or not, in accordance with the recloser's
closing cycle (See 6.2.3).
❑ Enable Events record. Allows the generation of protection events associated to the function. If set to “NO”, the function’s
protection events are not generated. If set to “YES”, the function’s specific mask is contemplated.
There are independent settings, commands and outputs.

❑ Node: PROT/OPPTOC
❑ Settings and logical inputs. There are 6 settings tables. For details, see Table 52.
❑ Commands:
 “DOrdBlk”: Function blocking and unblocking. Only acts when the function is enabled.
❑ Outputs: Table 53 shows the function’s output data.
 Broken conductor Start. Indicates that the unit has picked up.
 Broken conductor Trip. Indicates that the unit has tripped.
 Broken conductor Status. Indicates the function’s status. It is active when enabled and not blocked.

Table 52 Broken conductor settings

Data Setting Min Max Step Remarks Type


OPPTOCEna Enabled NO / YES enum
Always (1)
Optype Operation type enum
Yes with 52 (2)
StrVal Start value (%) 5 100 0,1 float32
OpDlTmms Delay time (ms) 0 600000 10 int32
BlkIph Minimum Phase I (%Irated) 5 200 0,1 float32
BLkI0I1 Max. Threshold I0/Irated (%) 0 20 0,1 float32
LogInBlk Blocking input uint32
GenTrip General trip NO / YES Boolean
TripPerm Trip Permission by recloser 0 255 1 Bit meaning (1) ING
NO (0)
Reclose 1 (1)
Reclose 2 (2)
Reclose 1-2 (3)
Reclose 3 (4)
Reclose 1-3 (5)
Reclose 2-3 (6)
Reclose 1-2-3 (7)
ReclPerm Reclose perm.(R1,R2,R3,R4) 0 15 enum
Reclose 4 (8)
Reclose 1-4 (9)
Reclose 2-4 (10)
Reclose 1-2-4 (11)
Reclose 3-4 (12)
Reclose 1-3-4 (13)
Reclose 2-3-4 (14)
Reclose 1-2-3-4 (15)
MaskEna Enable Events Record NO / YES Boolean

Ingeteam Power Technology S.A.


User Manual 115
PROTECTION FUNCTIONS

Table 53 Broken conductor function outputs

Signal Data Attribute


Broken conductor Start Str general
Broken conductor Trip Op general
Broken conductor Status StEna stVal
Figure 73 Broken conductor logic

3.3.11 Thermal image


There are independent units for phase and neutral.

This function calculates a thermal capacity in accordance with the protected unit’s recent and current load conditions. The thermal
capacity is displayed as a % of the trip value. If the function is enabled, a warning signal is activated when the programmed value is
reached. When 100% is reached, the thermal image trip signal is activated. Once tripped as a result, it does not drop-out while the
calculated thermal capacity remains above the reset threshold setting and the rest of the locking conditions are fulfilled. The
calculated thermal capacity can be reset by logic input or by command.

The time which elapses before the trip is determined by the following curves, which establish the time in accordance with the ratio
between the current and the programmed rated current, and the programmed heating constant. According to the following
formula (starting from thermal capacity 0):

Ingeteam Power Technology S.A.


User Manual 116
PROTECTION FUNCTIONS

In which:

t: trip time

ζ1: heating constant

I: measured current

I0: programmed rated current

Once it has tripped, there is another programmable time constant for the cooling.

The heating curve is calculated using the following formula:

In which:

Tf: final thermal capacity

Ti: initial thermal capacity

t: time

ζ1: heating time constant

For Ti = 0 the formula is reduced to

As

The heating curve is

The cooling curve is calculated using the following formula:

In which:

Tf: final thermal capacity

Ti: initial thermal capacity

t: time

ζ2: cooling time constant

Starting from Ti = 1 (100 in %), which is the thermal capacity at which the trip is produced, the formula used to obtain a thermal
capacity of Tf = 0 (i.e., current I = 0) is as follows

The current measurements used in the units are:

Ingeteam Power Technology S.A.


User Manual 117
PROTECTION FUNCTIONS

❑ Phases
Ieq2=Imax2

Where:

Imax is the maximum current of the three phases.

❑ Neutral. The transformer grounding current is used. If this transformer does not exist, the neutral current is used.
The settings of each of these units are:

❑ Enabled. Indicates whether the function is enabled or not.


❑ Heating constant (s). Heating constant in seconds.
❑ Cooling constant (s). Cooling constant in seconds.
❑ Alarm threshold (%). Value at which a thermal image warning is issued.
❑ Trip threshold (%).5 Value at which a thermal image trip is issued. It should be greater than the “Alarm threshold (%)”. If it
is smaller it is fixed to 100.
❑ Reset threshold (%). Thermal image reset value.
❑ Start current (A). Rated current for the calculation of the thermal image.
❑ Blocking Input. Selects the signal which, when active, blocks the function.
❑ Init input. Resets the thermal image value.
❑ General trip. Indicates if this unit produces general trip or not. For additional details, see the section corresponding to the
recloser (3.12.6).
❑ Trip Permission by recloser. Indicates the trip and block permission in accordance with the recloser status: standby,
blocked, safety time after reclosing, after closing. It is configured bit by bit; for additional details, see section
corresponding to the recloser (3.12.6.3).
❑ Calculus store. Allows the value calculated for the thermal image to be stored in the non-volatile memory. If set to “YES”,
the stored value will be the initial thermal image value used when the unit is booted; if set to “NO”, the initial thermal
image value is zero.
❑ Enable Events record. Allows the generation of protection events associated to the function. If set to “NO”, the function’s
protection events are not generate. If set to “YES”, the function’s specific mask is contemplated.
There are independent settings, commands and outputs.

❑ Nodes:
 Phases: PROT/PTTR
 Neutral: PROT/GPTTR
❑ Settings and logical inputs. There are 6 settings tables. For details, see Table 54.
❑ Commands:
 “DOrdBlk”: Function blocking and unblocking. Only acts when the function is enabled.
 “DOrdIn”: Resetting to zero of thermal image value.
❑ Outputs: Table 55 shows the phase function’s output data and Table 56 shows ground function’s output data.
 Thermal Image X Start. Indicates that the unit has picked up. Where X is phase or ground.
 Thermal Image X Trip. Indicates that the unit has tripped. Where X is phase or ground.
 Thermal Image X Status. Indicates the function’s status. It is active when enabled and not blocked. Where X is phase or
ground.

5
Available from firmware version 5.17.15.3 and ICD 6.1.13.29

Ingeteam Power Technology S.A.


User Manual 118
PROTECTION FUNCTIONS

Table 54 Thermal image settings

Data Setting Min Max Step Remarks Type


PTTREna Enabled NO / YES Boolean
ConsTms1 Heating constant (s) 30 18000 5 int32
ConsTms2 Cooling constant (s) 30 18000 5 int32
AlmVal Alarm threshold (%) 50 100 1 float32
TripVal Trip threshold (%) 50 100 1 float32
RepVal Reset threshold (%) 50 95 1 float32
Artg (ARtg in Ed2) Start current (A) 0,1 150,0 0,01 float32
LogInBlk Blocking input uint32
LogInIn Init input uint32
PTTREna General trip NO / YES Boolean
TripPerm Trip Permission by recloser 0 255 1 Bit meaning (1) ING
ValStore Calculus Store NO / YES Boolean
MaskEna Enable Events Record NO / YES Boolean

Table 55 Phase Thermal image function outputs

Signal Data Attribute


Thermal Image Phase Start Str general
Thermal Image Phase Trip Op general
Thermal Image Phase Status StEna stVal

Table 56 Neutral Thermal image function outputs

Signal Data Attribute


Thermal Image Ground Start Str general
Thermal Image Ground Trip Op general
Thermal Image Ground Status StEna stVal

3.3.11.1 Calculation Example


Figure 74 shows the trip times according to different heating constants.

Figure 75 shows an example of heating curves with a 3 minute time constant for I/I0 = 1 and for I/I0 = 2

Figure 74 Trip times

Ingeteam Power Technology S.A.


User Manual 119
PROTECTION FUNCTIONS

Figure 75 Heating curve example

Figure 76 shows an example of a cooling curve with 3-minute constant.

Figure 76 Cooling curve example

Examples: Combined examples of cooling and heating


Supposing that it is heated with I/I0 =1 for 200sec, I/I0 =2 for the next 200 sec (without tripping) and, as of that point, it returns
indefinitely to I/I0 = 1 (both with 3 minute time constants):

2. Supposing that it is heated with I/I0 =0.5 for 200sec, I/I0 =1.5 until reaching 100%, at which point the trip is produced, as of
that point, it cools with I/I0 = 0 (both with 3 minute time constants):

Ingeteam Power Technology S.A.


User Manual 120
PROTECTION FUNCTIONS

3.3.12 Undercurrent
There are two independent undercurrent units.

They employ the phases’ fundamental measurements. The unit picks up when the current falls below the setting and drops out
when the current rises above 105% of the setting.

The pickup is generated for each phase, regardless of the setting “Operation type”. However, the unit’s trip takes the operation
type into account.

The settings of each of these units are:

❑ Enabled. Indicates whether the function is enabled or not.


❑ Operation type. To be selected between:
 “All (A,B,C)”. The unit trips when all the phases meet the undercurrent conditions
 “Any (A,B,C)”. The unit trips when at least one of the phases meets the undercurrent conditions
❑ Start value (A). Set in secondary amps. It indicates the current value for which the function is activated.
❑ Delay time (ms). Indicates the time during which the conditions for the tripping of the function must be met.
❑ Blocking Input. Selects the signal which, when active, blocks the function.
❑ General trip. Indicates if this unit produces general trip or not. For additional details, see the section corresponding to the
recloser (3.12.6).
❑ Trip Permission by recloser. Indicates the trip and block permission in accordance with the recloser status: standby,
blocked, safety time after reclosing, after closing. It is configured bit by bit; for additional details, see section
corresponding to the recloser (3.12.6.3).
❑ Enable Events record. Allows the generation of protection events associated to the function. If set to “NO”, the function’s
protection events are not generate. If set to “YES”, the function’s specific mask is contemplated.
Table 57 Undercurrent settings

Data Setting Minimum Maximum Step Remarks Type


PTUCEna Enabled NO / YES enum
All (A,B,C) (1)
Optype Operation type enum
Any (A,B,C)(2)
StrVal Start value (A) 0,02 10 0,01 float32
OpDlTmms Delay time (ms) 0 600000 10 int32
LogInBlk Blocking input uint32
GenTrip General trip NO / YES Boolean
TripPerm Trip Permission by recloser 0 255 1 Bit meaning (1) ING
MaskEna Enable Events Record NO / YES Boolean

There are independent settings, commands and outputs in each unit.

❑ Nodes:
 Unit 1: PROT/PTUC1
 Unit 2: PROT/PTUC2
❑ Settings and logical inputs. There are 6 settings tables. For details, see Table 57.
❑ Commands:

Ingeteam Power Technology S.A.


User Manual 121
PROTECTION FUNCTIONS

 “DOrdBlk”: Function blocking and unblocking. Only acts when the function is enabled.
❑ Outputs: Table 58 shows the function’s output data.
 TUC1 phase X Start. Indicates that the unit's phase has picked up. It is independent for each phase and does not
consider the setting “Operation type”.
 TUC1 phase Start. Pickup of at least one phase. Indicates that at least one of the unit's phases has picked up. It does
not take into account the setting “Operation type”.
 TUC1 Start. Taking into account the setting “Operation type”, it indicates that the unit has picked up.
 TUC1 Trip. Taking into account the setting “Operation type”, it indicates that the unit has tripped.
 Undercurrent Unit 1 Status. Indicates the function’s status. It is active when enabled and not blocked. This is general
for all three phases.
Table 58 Phase undercurrent function outputs

PTUC1 Signals PTUC2 Signals Data Attribute


TUC1 phase A Start TUC2 phase A Start Str phsA
TUC1 phase B Start TUC2 phase B Start Str phsB
TUC1 phase C Start TUC2 phase C Start Str phsC
TUC1 Start TUC2 Start StrUC general
TUC1 Trip TUC2 Trip OpUC general
Undercurrent Unit 1 Status Undercurrent Unit 2 Status StEna stVal
TUC1 phase Start TUC2 phase Start Str general

3.3.13 Stub bus


Stub bus protection is an instantaneous overcurrent unit, but it order for it to be activated, the switch needs to be open. This
function is useful in breaker and a half configurations. It can be used as a fixed time overcurrent unit with its own settings or any of
the units available can be used with a logic which ensures that they are continuously blocked until the line switch is opened.

The settings used are as follows:

❑ Enabled: Indicates whether the function is enabled or not.


❑ Phase threshold (A): It is set as secondary amperes. It indicates the phase current value for which the function is activated.
❑ Phase Delay Time (ms): Indicates the time during which the conditions for tripping the phase function must be met.
❑ Neutral threshold (A): It is set as secondary amperes. It indicates the neutral current value for which the function is
activated.
❑ Neutral Delay Time (ms): Indicates the time during which the conditions for tripping must be met.
❑ Blocking input: Selects the signal which, when active, blocks the function.
❑ Enable Events record. Allows the generation of protection events associated to the function. If set to “NO”, the function’s
protection events are not generated. If set to “YES”, the function’s specific mask is contemplated.
❑ General trip. Indicates if this unit produces general trip or not. For additional details, see the section corresponding to the
recloser (3.12.6).

Table 59 Stub Bus function settings

Data Setting Minimum Maximum Step Remarks Type


Ena Enabled NO / YES enum
PhStrVal Phase threshold (A) 0.02 200 0.01 float32
PhOpTmms Phase Delay Time (ms) 0 600000 10 uint32
NStrVal Neutral threshold (A) 0.02 200 0.001 float32
NOpTmms Neutral Delay Time (ms) 0 600000 10 uint32
LogInBlk Blocking input uint32
MaskEna Enable Events Record NO / YES Boolean
GenTrip General trip NO / YES Boolean

There are independent settings, inputs, commands and outputs in each unit:

❑ Node: PROT/PSTB

Ingeteam Power Technology S.A.


User Manual 122
PROTECTION FUNCTIONS

❑ Settings. There are 6 settings tables. For details, see Table 59.
❑ Logic inputs:
 89 Open/closed input. It indicates the disconnector status
❑ Commands:
 “DOrdBlk”: Function blocking and unblocking. Only acts when the function is enabled.
❑ Outputs: Table 60 shows the function's output data.
 Stub Bus phase x Start. Indicates that the stub protection is started up by a phase. It is independent for each phase.
 Stub Bus neutral Start. Indicates that the stub protection is started up by the neutral.
 Stub Bus phase X Trip. Indicates that the stub protection is tripped by a phase. It is independent for each phase.
 Stub Bus neutral Trip. Indicates that the stub protection is tripped by the neutral.
 Stub Bus Start. Indicates that the stub protection is started up by a phase or by the neutral.
 Stub Bus Trip. Indicates that the stub protection is tripped by a phase or by the neutral.
 Stub Bus Status. Indicates whether the stub protection is enabled or not.
The input signals of this scheme are:

❑ "Disconnector 1 Status (DI) = OPEN". It is the general status of the disconnector (SXWI)
Table 60 Stub Bus function outputs.

Signal Data Attribute


Stub Bus phase A Start Str phsA
Stub Bus phase B Start Str phsB
Stub Bus phase C Start Str phsC
Stub Bus neutral Start Str neutral (neut in Ed2)
Stub Bus phase A Trip Op phsA
Stub Bus phase B Trip Op phsB
Stub Bus phase C Trip Op phsC
Stub Bus neutral Trip Op neutral (neut in Ed2)
Stub Bus Start Str general
Stub Bus Trip Op general
Stub Bus Status StEna general

Figure 77 Stub Bus function diagram

Ingeteam Power Technology S.A.


User Manual 123
PROTECTION FUNCTIONS

3.3.13.1 Differential Stub bus


In the 52 ½ configuration, a differential stub bus protection is available, but in order for it to be activated, the disconnector
needs to be open.

With the function enabled by setting, it is only active when the 3 phases of the disconnector are open

With the disconnector open at one end, the protection is affected:

❑ The phase measurements of the local end are zero; therefore, the measures sent to the remote end are zero.
❑ The line differential of the end with the disconnector open does not trip
❑ It doesn´t allow direct trip commands from the other end.
It is calculated on each of the phases and on 3I0. The differential current and restraint of the two breakers are used, following
the curve of Figure 78.

𝐼𝑑𝑖𝑓 = |𝐼𝐵𝑟1 + 𝐼𝐵𝑟2 |

|𝐼𝐵𝑟1 | + |𝐼𝐵𝑟2 |
𝐼𝑝𝑎𝑠𝑜 =
2
Where

𝐼𝐵𝑟1 breaker 1 current

𝐼𝐵𝑟2 breaker 2 current

Figure 78 Stub differential protection curve with 2 slopes

Idifferential

Trip zone
2

Sensitivity 1
Irestraint

Ires1 Ires2

There are two independent units for phases and neutral (3I0) with settings, commands and outputs:

❑ Phases: Node DIF/PSTB


❑ Neutral: Node NDIF/PSTB

Table 61 shows the settings of each unit:

❑ Enabled: Indicates whether the function is enabled or not.


❑ Sensitivity (p.u.): Indicates the minimum value of the pickup of the differential characteristic in p.u. of rated current.
❑ Rest.current step 1 (p.u.): Indicates the restraint current for which the slope 1 starts in p.u. of rated current.
❑ Rest.current step 2 (p.u.): Indicates the restraint current for which the slope 2 starts in p.u. of rated current
❑ Slope 1 (%): Indicates the value of the slope 1.
❑ Slope 2 (%): Indicates the value of the slope 2.

Ingeteam Power Technology S.A.


User Manual 124
PROTECTION FUNCTIONS

❑ Delay time (ms): Indicates the time during which the conditions for the tripping of the function must be met.
❑ Blocking input: Selects the signal which, when active, blocks the function.
❑ General trip: General trip. Indicates if this unit produces general trip or not. For additional details, see the section
corresponding to the recloser (3.12.6).
❑ Enable Events record: Allows the generation of protection events associated to the function. If set to “NO”, the function’s
protection events are not generated. If set to “YES”, the function’s specific mask is contemplated.

Outputs: Table 62 and Table 63 show the output data of the function.

❑ Phase unit:
 Start Stub diff. X. Indicates that the differential stub protection is started up by a phase. It is independent for each
phase.
 Trip Stub diff. X. Indicates that the differential stub protection is tripped up by a phase. It is independent for each
phase.
 Diff Phases stub status. Enabled and not blocked.
❑ Neutral unit:
 Start Stub diff.Neutro. Indicates that the differential stub protection is started up by neutral.
 Trip Stub diff.Neutro. Indicates that the differential stub protection is tripped up by neutral.
 Diff Neutral stub status. Enabled and not blocked.
Every unit has blocking commands:

❑ “DOrdBlk”: Function blocking and unblocking. Only acts when the function is enabled.

Table 61 Differential stub bus function settings

Data Setting Minimum Maximum Step Remarks Type


Ena Enabled 0 1 1 NO / YES Booleano
LoSet Sensitivity (p.u.) 0,1 10 0,01 float
RstA1 Current step 1 (p.u.) 0 10 0,01 float
RstA2 Current step 2 (p.u.) 0 10 0,01 float
Slope1 Slope 1 (%) 5 100 1 float
Slope2 Slope 2 (%) 5 200 1 float
OpDlTmms Aditional Time (ms) 0 60000 1 float
LogInBlk Blocking input -1 8388607 1 uint32
GenTrip General Trip 0 1 1 NO / YES Booleano
MaskEna Enable Events Record 0 1 1 NO / YES Booleano

Table 62 Phase differential stub bus output.

Signal Data Attribute


Diff Phases stub status StEna general
Start Stub diff.A Str phsA
Start Stub diff.B Str phsB
Start Stub diff.C Str phsC
Trip diff stub A Op phsA
Trip diff stub B Op phsB
Trip diff stub C Op phsC

Table 63 Neutral differential stub bus output.

Signal Data (Edition 1) Attribute (Edition 1) Data (Edition 2) Attribute (Edition 2)


Diff Neutral stub status StEna general StEna general
Start Stub diff.Neutro Str neutral Str neut
Trip diff stub Neutral Op neutral Op neut

Ingeteam Power Technology S.A.


User Manual 125
PROTECTION FUNCTIONS

3.4 VOLTAGE UNITS

3.4.1 General description


When enabled and unblocked, the overvoltage units act when the setting value is exceed during the programmed time. In order to
reset, the voltage must fall below the pickup value return percentage. For example, if the pickup threshold is 50V and the reset
percentage is 10%, the unit must register voltage above 50V in order to pickup and voltage below 45V in order to reset (50-0.1 50).

When enabled and unblocked, the undervoltage units act when the voltage is inferior to the setting value during the programmed
time. In order to reset, the voltage must exceed the pickup value return percentage. For example, if the pickup threshold is 50V and
the reset percentage is 10%, the unit must register voltage below 50V in order to pickup and voltage above 55V in order to reset
(50+0.1 50).

The voltage units are not directional.

The voltage unit’s general settings are available in the PROT/PVGE1 node (return percentages and VO measurement type):

❑ Phase overV drop out (%). Indicates the pickup setting percentage below which the voltage must fall in order that the
instantaneous and timed phased units reset.
❑ Phase underV drop out (%). Indicates the pickup setting percentage above which the voltage must rise in order that the
instantaneous and timed phased units reset.
❑ 3V2 drop out (%). Indicates the pickup setting percentage below which the voltage must fall in order that the
instantaneous and timed V2 units reset.
❑ 3VO drop out (%). Indicates the pickup setting percentage below which the voltage must fall in order that the
instantaneous and timed VO units reset.
❑ 3VO Operating quantity. Indicates the measurement used for the VO overvoltage:
 Calculated: The 3 V0 measurement is used, i.e., the vector sum of the 3 ground to earth phases. 3V0=Va+Vb+Vc
 Measured: The measurement from the transformer configured as Vn is used.

Table 64 General voltage settings

Data Setting Minimum Maximum Step Remarks Type


RepValOVp Phase overV drop out (%) 50 99 1 float32
RepValUVp Phase underV drop out (%) 101 110 1 float32
RepValOV2 3V2 drop out (%) 50 99 1 float32
RepValOV0 3VO drop out (%) 50 99 1 float32
Calculated (0)
SelV0 3VO Operating quantity enum
Measured (1)

3.4.1.1 Instantaneous characteristics


When enabled and unblocked, the unit acts when the setting value is exceed during the programmed time.

The settings used in these functions are:

❑ Enabled. Indicates whether the function is enabled or not.


❑ Operation type. Consult in each unit.
❑ Start value (V). Indicates the voltage value (in secondary volts) at which the function is activated.
❑ Delay time (ms). Indicates the time during which the conditions for the tripping of the function must be met.
❑ Blocking Input. Selects the signal which, when active, blocks the function.
❑ General trip. Indicates if this unit produces general trip or not. For additional details, see the section corresponding to the
recloser (3.12.6).

Ingeteam Power Technology S.A.


User Manual 126
PROTECTION FUNCTIONS

❑ Trip Permission by recloser. Indicates the trip and block permission in accordance with the recloser status: standby,
blocked, safety time after reclosing, after closing. It is configured bit by bit; for additional details, see section
corresponding to the recloser (3.12.6.3).
❑ Enable Events record. Allows the generation of protection events associated to the function. If set to “NO”, the function’s
protection events are not generated. If set to “YES”, the function’s specific mask is contemplated.

Table 65 Instantaneous voltage unit settings

Data Setting Minimum Maximum Step Remarks Type


PIOVEna Enabled NO / YES enum
Standard (0)
Vphase-ground FUND(1)
Optype Operation type Vphase-ground FUND(2) enum
Vphase-ground RMS (3)
Vphase-phase RMS (4)
StrVal Start value (V) 0,5 200 0,01 float32
OpDlTmms Delay time (ms) 0 600000 10 int32
LogInBlk Blocking input uint32
GenTrip General trip NO / YES Boolean
TripPerm Trip Permission by recloser 0 255 1 Bit meaning (1) ING
MaskEna Enable Events Record NO / YES Boolean

3.4.1.2 Timed characteristics


The different curve options are shown in the curve appendix.

The timed unit can be configured with a minimum of response time, that is, a limit that prevents any unit from tripping below a
minimum time when the trip time corresponding to the curve in use is met. This avoids timed trips which are quicker than the
instantaneous trips. It is configured with additional time setting, so that if it set to zero, there is no such limit.

The settings used in these functions are:

❑ Enabled. Indicates whether the function is enabled or not.


❑ Start value (V). Set in secondary volts. Indicates the voltage value at which the function is activated.
❑ Operation type. Consult in each unit.
❑ Operating Curve Type Indicates the type of curve selected from the options:
 ANSI-EI Extreme. Inverse (1)
 ANSI-MI Very inverse (2)
 ANSI-I Normal inverse(3)
 ANSI-MODI Moderately inverse (4)
 IEC-I Normal inverse (9) or Inverse (11)
 IEC-MI Very inverse (10)
 IEC-EI Extreme. Inverse (12)
 IEC-IC Short inverse (13)
 IEC-IL Long inverse (14)
 IEC-MIEs Very inverse special (50)
 User curves 1 (33)
 User curves 2 (34)
 User curves 3 (35)
 User curves 4 (36)
 Definite time (49)
❑ Time dial. Indicates the time curve within the selected characteristic.

Ingeteam Power Technology S.A.


User Manual 127
PROTECTION FUNCTIONS

❑ Delay/minimum time (ms). It has a different functionality depending on the type of curve selected:
❑ When the selected curve is a definite time, it indicates the time during which the conditions for the tripping of the function
must be met.
❑ In the rest of the curve, it indicates the minimum response time. i.e., in order for a trip to be produced, the time used will
be greater between this setting and the time associated to the curve.
❑ Blocking Input. Selects the signal which, when active, blocks the function.
❑ General trip. Indicates if this unit produces general trip or not. For additional details, see the section corresponding to the
recloser (3.12.6).
❑ Trip Permission by recloser. Indicates the trip and block permission in accordance with the recloser status: standby,
blocked, safety time after reclosing, after closing. It is configured bit by bit; for additional details, see section
corresponding to the recloser (3.12.6.3).
❑ Enable Events record. Allows the generation of protection events associated to the function. If set to “NO”, the function’s
protection events are not generated. If set to “YES”, the function’s specific mask is contemplated.

Table 66 Timed voltage unit settings

Data Setting Min Max Step Remarks Type


PTVEna Enabled NO / YES enum
Standard (0)
Vphase-ground FUND (1)
Optype Operation type Vphase-ground FUND (2) enum
Vphase-ground RMS (3)
Vphase-phase RMS (4)
StrVal Start value (V) 0,5 200 0,01 float32
ANSI-EI Extreme. Inverse (1)
ANSI-MI Very inverse (2)
ANSI-I Normal inverse(3)
ANSI-MODI Moderately inverse (4)
IEC-I Normal inverse (9) / Inverse (11)
IEC-MI Very inverse (10)
IEC-EI Extreme. Inverse (12)
TmVCrv Operating curve type IEC-IC Short inverse (13) enum
IEC-IL Long inverse (14)
IEC-MIEs Very inverse special (50)
User curves 1 (33)
User curves 2 (34)
User curves 3 (35)
User curves 4 (36)
Definite time (49)
TmMult Time dial 0,05 30,0 0,01 float32
OpDlTmms Delay/minimum time (ms) 0 600000 10 int32
LogInBlk Blocking input uint32
GenTrip General trip NO / YES Boolean
TripPerm Trip Permission by recloser 0 255 1 Bit meaning (1) ING
MaskEna Enable Events record NO / YES Boolean

3.4.2 Phase overvoltage


The phase overvoltage acts on the phase voltage transformers. If the unit is configured with phase to ground voltages, the
protection is wired with phase to ground measurements (Va, Vb and Vc), while if it is configured with phase to phase voltages, the
protection is wired with phase to phase measurements (Vab, Vbc and Vca).

The return percentage can be configured by the user in the PROT/PVGE1 node.

3.4.2.1 Instantaneous
There are 2 independent units for each of the phases.

The setting “Operation type” allows for a selection to be made from among the following:

Ingeteam Power Technology S.A.


User Manual 128
PROTECTION FUNCTIONS

❑ “Vphase-ground FUND”. Acts with the phase-ground voltage and fundamental value without harmonics.
❑ “Vphase-phase FUND”. Acts with the phase-phase voltage and fundamental value without harmonics.
❑ “Vphase-ground RMS”. Acts with the phase-ground voltage and rms value with harmonics.
❑ “Vphase-phase RMS”. Acts with the phase-phase voltage and rms value with harmonics.
❑ “Standard”. Acts with the phase-ground voltage and fundamental value without harmonics.
If the PROT/TVTR voltage phase setting indicates that at least one of the phase-phase voltage options, the operation type can
only be selected as VFAs-phase Fund or Vphase-phase RMS. If any other type is selected, the unit will correct itself internally.

The return percentage is user-configurable (PVGE1).

Each of the three units has independent settings, commands and outputs.

❑ Nodes:
 Unit 1: PROT/PIOV1
 Unit 2: PROT/PIOV2
❑ Settings and logical inputs. There are 6 settings tables. For details, see Table 65.
❑ Commands:
 “DOrdBlk”: Function blocking and unblocking. Only acts when the function is enabled.
❑ Outputs: Table 67 shows the function’s output data
 IOV1 Start phase X. Indicates that the unit's phase has picked up. It is independent for each phase. Where X is the
phase.
 IOV1 Trip phase X. Indicates that the unit's phase has tripped. It is independent for each phase. Where X is the phase.
 IOV1 Phase Status. Indicates the function’s status. It is active when enabled and not blocked. This is general for all
three phases.
 IOV1 phase Start. Indicates that the unit has picked up
 IOV1 phase Trip. Indicates that the unit has tripped.
Table 67 Instantaneous phase overvoltage function outputs

PIOV1 Signals PIOV2 Signals Data Attribute


IOV1 Start phase A IOV2 Start phase A Str phsA
IOV1 Start phase B IOV2 Start phase B Str phsB
IOV1 Start phase C IOV2 Start phase C Str phsC
IOV1 Trip phase A IOV2 Trip phase A Op phsA
IOV1 Trip phase B IOV2 Trip phase B Op phsB
IOV1 Trip phase C IOV2 Trip phase C Op phsC
IOV1 Phase Status IOV2 Phase Status StEna stVal
IOV1 Phase Start IOV2 Phase Start Str general
IOV1 Phase Trip IOV2 Phase Trip Op general

3.4.2.2 Timed
There is a single timed unit, which is independent for each of the phases.

The setting “Operation type” allows for a selection to be made from among the following:

❑ “Vphase-ground FUND”. Acts with the phase-ground voltage and fundamental value without harmonics.
❑ “Vphase-phase FUND”. Acts with the phase-phase voltage and fundamental value without harmonics.
❑ “Vphase-ground RMS”. Acts with the phase-ground voltage and rms value with harmonics.
❑ “Vphase-phase RMS”. Acts with the phase-phase voltage and rms value with harmonics.
❑ “Standard”. Acts with the phase-ground voltage and fundamental.

Ingeteam Power Technology S.A.


User Manual 129
PROTECTION FUNCTIONS

If the PROT/TVTR voltage phase setting indicates that at least one of the phase-phase voltage options, the operation type can
only be selected as VFAs-phase Fund or Vphase-phase RMS. If any other type is selected, the unit will correct itself internally.

There are settings, commands and outputs.

❑ Nodes: PROT/PTOV1
❑ Settings and logical inputs. There are 6 settings tables. For details, see Table 66.
❑ Commands:
 “DOrdBlk”: Function blocking and unblocking. Only acts when the function is enabled.
❑ Outputs: Table 68 shows the function’s output data
 TOV Start phase X. Indicates that the unit's phase has picked up. It is independent for each phase. Where X is the
phase.
 TOV Trip phase X. Indicates that the unit's phase has tripped. It is independent for each phase. Where X is the phase.
 TOV Phase Status. Indicates the function’s status. It is active when enabled and not blocked. This is general for all three
phases.
 TOV1 phase Start. Indicates that the unit has picked up
 TOV1 phase Trip. Indicates that the unit has tripped.

Table 68 Timed phase overvoltage function outputs

Signal Data Attribute


TOV Start phase A Str phsA
TOV Start phase B Str phsB
TOV Start phase C Str phsC
TOV Trip phase A Op phsA
TOV Trip phase B Op phsB
TOV Trip phase C Op phsC
TOV Phase Status StEna stVal
TOV Phase Start Str general
TOV Phase Trip Op general

3.4.3 Zero sequence overvoltage


There is a timed and an instantaneous unit.

The following can be configured in the PROT/PVGE1 node:

❑ The measurement used between Vn transformer measurement or the vector sum of the three voltage phases (3 V0).
❑ The return percentage is user-configurable (PVGE1).
The setting “Operation type” is not used, as the fundamental frequency measurement is always used.

3.4.3.1 Instantaneous
There is one unit.

It has independent settings, commands and outputs.

❑ PROT/GPIOV1 node
❑ Settings and logical inputs. There are 6 settings tables. For details, see Table 64 and Table 65.
❑ Commands:
 “DOrdBlk”: Function blocking and unblocking. Only acts when the function is enabled.
❑ Outputs: Table 69 shows the function’s output data

Ingeteam Power Technology S.A.


User Manual 130
PROTECTION FUNCTIONS

 GIOV1 Start. Indicates that the unit has picked up.


 GIOV1 Trip. Indicates that the unit has tripped.
 IOV V0 Status. Indicates the function’s status. It is active when enabled and not blocked.

Table 69 Instantaneous zero sequence overvoltage function outputs

Signal Data Attribute


GIOV1 Start Str neut
GIOV1 Trip Op neut
IOV V0 Status StEna stVal

3.4.3.2 Timed
There is one timed unit.

There are settings, commands and outputs.

❑ Nodes: PROT/GPTOV1
❑ Settings and logical inputs. There are 6 settings tables. For details, see Table 65 and Table 58.
❑ Commands:
 “DOrdBlk”: Function blocking and unblocking. Only acts when the function is enabled.
❑ Outputs: Table 70 shows the function’s output data.
 GTOV1 Start. Indicates that the unit has picked up.
 GTOV1 Trip. Indicates that the unit has tripped.
 TOV (V0) Status. Indicates the function’s status. It is active when enabled and not blocked.
Table 70 Timed zero sequence overvoltage function outputs

Signal Data Attribute


GTOV1 Start Str neut
GTOV1 Trip Op neut
TOV (V0) Status StEna stVal

3.4.4 Negative sequence overvoltage


There is a timed and an instantaneous unit.

Employs 3 times the negative sequence as a measurement:

3 · V2 = (Va + a2 · Vb + a · Vc) In which a = 1|120º

The calculation of the sequence takes into phase succession order setting (ABC/ACB).

The return percentage can be configured by the user in the PROT/PVGE1 node.

The setting “Operation type” is not used, as the fundamental frequency measurement is always used.

3.4.4.1 Instantaneous
There is one unit.

It has independent settings, commands and outputs.

❑ Node: PROT/UNPIOV1
❑ Settings and logical inputs. There are 6 settings tables. For details, see Table 64 and Table 65.
❑ Commands:

Ingeteam Power Technology S.A.


User Manual 131
PROTECTION FUNCTIONS

 “DOrdBlk”: Function blocking and unblocking. Only acts when the function is enabled.
❑ Outputs: Table 71 shows the function’s output data.
 UNIOV1 Start. Indicates that the unit has picked up.
 UNIOV1 Trip. Indicates that the unit has tripped.
 IOV V2 Status. Indicates the function’s status. It is active when enabled and not blocked.
Table 71 Instantaneous V2 overvoltage function outputs

Signal Data Attribute


UNIOV1 Start Str general
UNIOV1 Trip Op general
IOV V2 Status StEna stVal

3.4.4.2 Timed
There is one timed unit.

There are settings, commands and outputs.

❑ Node: PROT/UNPTOV1
❑ Settings and logical inputs. There are 6 settings tables. For details, see Table 66 and Table 64.
❑ Commands:
 “DOrdBlk”: Function blocking and unblocking. Only acts when the function is enabled.
❑ Outputs: Table 72 shows the function’s output data.
 UNTOV1 Start. Indicates that the unit has picked up.
 UNTOV1 Trip. Indicates that the unit has tripped.
 TOV V2 Status. Indicates the function’s status. It is active when enabled and not blocked.
Table 72 Timed V2 overvoltage function outputs

Signal Data Attribute


UNTOV1 Start Str general
UNTOV1 Trip Op general
TOV V2 Status StEna stVal

3.4.5 Phase undervoltage


The phase undervoltage acts on the phase voltage transformers. If the unit is configured with phase to ground voltages, the
protection is wired with phase to ground measurements (Va, Vb and Vc), while if it is configured with phase to phase voltages, the
protection is wired with phase to phase measurements (Vab, Vbc and Vca).

The return percentage can be configured by the user in the PROT/PVGE1 node.

3.4.5.1 Instantaneous
There are 2 independent units for each of the phases.

The setting “Operation type”allows for a selection to be made from among the following:

❑ “Standard”. Acts with the phase-ground voltage and fundamental


❑ “Vphase-ground FUND”. Acts with the phase-ground voltage and fundamental value without harmonics
❑ “Vphase-phase FUND”. Acts with the phase-phase voltage and fundamental value without harmonics
❑ “Vphase-ground RMS”. Acts with the phase-ground voltage and rms value with harmonics
❑ “Vphase-phase RMS”. Acts with the phase-phase voltage and rms value with harmonics
The return percentage is user-configurable (PVGE1).

Ingeteam Power Technology S.A.


User Manual 132
PROTECTION FUNCTIONS

Each of the three units has independent settings, commands and outputs.

❑ Nodes:
 Unit 1: PROT/PIUV1
 Unit 2: PROT/PIUV2
❑ Settings and logical inputs. There are 6 settings tables. For details, see Table 65 and Table 64.
❑ Commands:
 “DOrdBlk”: Function blocking and unblocking. Only acts when the function is enabled.
❑ Outputs: Table 73 shows the function’s output data.
 IUV1 Start phase X. Indicates that the unit's phase has picked up. It is independent for each phase. Where X is the
phase.
 IUV1 Trip phase X. Indicates that the unit's phase has tripped. It is independent for each phase. Where X is the phase.
 IUV1 Phase Status. Indicates the function’s status. It is active when enabled and not blocked. This is general for all
three phases.
 IUV1 phase Start. Indicates that the unit has picked up
 IUV1 phase Trip. Indicates that the unit has tripped.
Table 73 Instantaneous phase undervoltage function outputs

PIUV1 Signals PIUV2 Signals Data Attribute


IUV1 Start phase A IUV2 Start phase A Str phsA
IUV1 Start phase B IUV2 Start phase B Str phsB
IUV1 Start phase C IUV2 Start phase C Str phsC
IUV1 Trip phase A IUV2 Trip phase A Op phsA
IUV1 Trip phase B IUV2 Trip phase B Op phsB
IUV1 Trip phase C IUV2 Trip phase C Op phsC
IUV1 Phase Status IUV2 Phase Status StEna stVal
IUV1 Phase Start IUV2 Phase Start Str general
IUV1 Phase Trip IUV2 Phase Trip Op general

3.4.5.2 Timed
There is a single timed unit, which is independent for each of the phases.

The setting “Operation type” allows for a selection to be made from among the following:

❑ “Standard”. Acts with the phase-ground voltage and fundamental


❑ “Vphase-ground FUND”. Acts with the phase-ground voltage and fundamental value without harmonics
❑ “Vphase-phase FUND”. Acts with the phase-phase voltage and fundamental value without harmonics
❑ “Vphase-ground RMS”. Acts with the phase-ground voltage and rms value with harmonics
❑ “Vphase-phase RMS”. Acts with the phase-phase voltage and rms value with harmonics
There are settings, commands and outputs.

❑ Nodes: PROT/PTUV1
❑ Settings and logical inputs. There are 6 settings tables. For details, see Table 65and Table 58.
❑ Commands:
 “DOrdBlk”: Function blocking and unblocking. Only acts when the function is enabled.
❑ Outputs: Table 74 shows the function’s output data
 TUV1 Start phase X. Indicates that the unit's phase has picked up. It is independent for each phase. Where X is the
phase.

Ingeteam Power Technology S.A.


User Manual 133
PROTECTION FUNCTIONS

 TUV1 Trip phase X. Indicates that the unit's phase has tripped. It is independent for each phase. Where X is the phase.
 TUV Phase Status. Indicates the function’s status. It is active when enabled and not blocked. This is general for all three
phases.
 TUV1 phase Start. Indicates that the unit has picked up
 TUV1 phase Trip. Indicates that the unit has tripped.

Table 74 Timed phase undervoltage function outputs

Signal Data Attribute


TUV1 Start phase A Str phsA
TUV1 Start phase B Str phsB
TUV1 Start phase C Str phsC
TUV1 Trip phase A Op phsA
TUV1 Trip phase B Op phsB
TUV1 Trip phase C Op phsC
TUV Phase Status StEna stVal
TUV1 Phase Start Str general
TUV1 Phase Trip Op general

3.4.6 Minimum voltage


It analyzes the voltages of the two sides of the breaker, generating a trip when both voltages are below the threshold during the set
time

With the "General Trip" setting, the breaker opening command can be generated. The trip generated by this unit is not reclosabled.

In the 52 ½ configuration, two units are available, one for each synchronism voltage (Vs1 and Vs2). In both units the voltage of the
A side is the one selected in the synchronism (node RSYN):

❑ Vsyn1: Node VS/PIUV1


❑ Vsyn2: Node VS/PIUV2
Table 75 shows the settings used in this function:

❑ Enabled. Indicates whether the function is enabled or not


❑ Threshold A (V). Indicates the voltage value (in secondary volts) below which is considered undervoltage on the A side.
❑ Threshold B (V). Indicates the voltage value (in secondary volts) below which is considered undervoltage on the B side.
❑ Delay time (ms). Indicates the time during which the conditions for the tripping of the function must be met
❑ Blocking Input. Selects the signal which, when active, blocks the function.
❑ General trip. Indicates if this unit produces general trip or not. For additional details, see the section corresponding to the
recloser (3.12.6).
❑ Enable Events record. Allows the generation of protection events associated to the function. If set to “NO”, the function’s
protection events are not generated. If set to “YES”, the function’s specific mask is contemplated.

Outputs: Table 76 shows the function’s output data of the two units. The signals are the same for both units

❑ Low voltage status U1. Indicates the function’s status. It is active when enabled and not blocked.
❑ VSPIUV Start A – U1. Indicates that the voltage on the A side is below the “Threshold A” setting.
❑ VSPIUV Start B – U1. Indicates that the voltage on the B side is below the “Threshold B” setting.
❑ VSPIUV Start U 1. Indicates that the voltage of both sides is below the threshold setting.
❑ VSPIUV Trip U 1. Indicates that the voltage of both sides is below the threshold setting during the “Delay time” setting.
Each unit has blocking commands:

❑ “DOrdBlk”: Function blocking and unblocking. Only acts when the function is enabled.

Ingeteam Power Technology S.A.


User Manual 134
PROTECTION FUNCTIONS

Table 75 Minimum voltage settings

Data Setting Minimum Maximum Step Remarks Type


Ena Enabled NO / YES enum
AStrVal Threshold A (V) 0,5 200 0,01 float32
BStrVal Threshold B (V) 0,5 200 0,01 float32
OpDlTmms Delay time (ms) 0 600000 10 int32
GenTrip Blocking input NO / YES Boolean
LogInBlk General Trip int32
MaskEna Enable Events Record NO / YES Boolean

Table 76 Minimum voltage outputs.

VS/PTUV1 VS/PTUV2 Data Attribute


Low voltage status U1 Low voltage status U2 StEna general
VSPIUV Start A – U1 VSPIUV Start A – U2 StrA general
VSPIUV Start B – U1 VSPIUV Start B – U2 StrB general
VSPIUV Start U 1 VSPIUV Start U 2 Str general
VSPIUV Trip U 1 VSPIUV Trip U 2 Op general

3.5 FREQUENCY UNITS

The frequency is measured each cycle and refreshed each half cycle, as shown in Figure 79.

Figure 79 Frequency Calculation

The voltage used in the frequency measurement is calculated as "2·Va-Vb-Vc". The algorithm is executed in the event of the voltage
registering zero. The frequency is calculated if the voltage measurement is greater than 2.5V.

Both the positive and negative registers are measured, although the frequency measurement is carried out for complete cycles.

3.5.1 Frequency
This function is composed of 8 steps, which are programmable as maximum or minimum frequencies.

The function’s node, PROT/PTGF1, has independent settings for each step and common settings for all.

The common settings for all steps are as follows:

❑ Minimum voltage (V). Indicates the minimum voltage value below which the frequency protection does no act, the unit is
not permitted to pickup.
❑ Number of cycles (Start). Indicates the number of cycles during which the frequency conditions necessary for the unit to
pickup must be met.
❑ Number of cycles (Reset). Indicates the number of cycles during which the drop conditions necessary for the unit to reset
must be met in the event of the unit's not having tripped.
❑ OverFreq. Reset time (ms). Once tripped by overfrequency, this is the time during which the reset conditions must be met
in order to clear the trip from the unit. It is applied to all the steps configured as overfrequency.

Ingeteam Power Technology S.A.


User Manual 135
PROTECTION FUNCTIONS

❑ UnderFreq. Reset time (ms). Once tripped by underfrequency, this is the time during which the reset conditions must be
met in order to clear the trip from the unit. It is applied to all the steps configured as underfrequency.
❑ General trip. Indicates if this unit produces general trip or not. For additional details, see the section corresponding to the
recloser (3.12.6).
❑ Trip Permission by recloser. Indicates the trip and block permission in accordance with the recloser status: standby,
blocked, safety time after reclosing, after closing. It is configured bit by bit; for additional details, see section
corresponding to the recloser (3.12.6.3).
❑ Enable Events record. Allows the generation of protection events associated to the function. If set to “NO”, the function’s
protection events are not generated. If set to “YES”, the function’s specific mask is contemplated.
The independent settings for each of the 8 steps are:

❑ Enabled. Indicates whether the step is enabled or not.


❑ Start value (Hz). Indicates the frequency value at which the function is activated.
❑ Delay time (ms). Indicates the time during which the conditions for the tripping of the function must be met.
❑ Function type. Indicates whether its acts on overfrequency or underfrequency.
❑ Blocking Input. Selects the signal which, when active, blocks the step.
The form in which it acts varies in accordance with type of step selected.

❑ Minimum frequency. Each step picks up when the frequency falls below the set value during a number of cycles equal or
higher than the “No. of pickup cycles” setting. Once it picks up, the programmed time must elapse in order for a trip to be
produced. If the unit has tripped, it drops out if the frequency is correct during the underfrequency reset time. If it has
picked up but has not tripped, it drops out if the frequency is correct during reset cycles.
❑ Maximum frequency. Each step picks up when the frequency exceeds the set value during a number of cycles equal or
higher than the “No. of pickup cycles” setting. Once it picks up, the programmed time must elapse in order for a trip to be
produced. If the unit has tripped, it drops out if the frequency is correct during the overfrequency reset time. If it has
picked up but has not tripped, it drops out if the frequency is correct during reset cycles.
There are settings, commands and outputs.

❑ Nodes: PROT/PTGF1
❑ Settings and logical inputs. There are 6 settings tables. For details, see Table 77.
❑ Commands:
 “DOrdBlk”: Function blocking and unblocking. It only acts on the enabled steps. If acts on the 8 steps
 “DOrdFminB”. Blocking and unblocking of the steps configured as minimum frequency. It only acts on the enabled
steps.
 “DOrdFmaxB”. Blocking and unblocking of the steps configured as maximum frequency. It only acts on the enabled
steps.
 “DOrdFL1Bl”. Blocking and unblocking of step 1. It only acts if the step is enabled
 “DOrdFL2Bl”… “DOrdFL8Bl”. As above, but acts on steps 2 to 8.
❑ Outputs: Table 78 shows the function’s output data. They are independent for each step
 Level X Frequency Start. Indicates that the step has picked up. It is independent for each step.
 Level X Frequency Trip. Indicates that the step has tripped. It is independent for each step.
 Level X Frequency Status. Indicates the step’s status. Active when enabled and not blocked. Independent for each step.

Ingeteam Power Technology S.A.


User Manual 136
PROTECTION FUNCTIONS

Table 77 General frequency protection settings

Data Parameter Min Max Step Remarks Type


BlkValV Minimum voltage (V) 15 200 1 float32
StrNumCyc Number of cycles (Start) 3 15 1 int32
RepNumCyc Number of cycles (Reset) 0 10 1 int32
OFRsDlTmms OverFreq. Reset time (ms) 0 600000 10 int32
UFRsDlTmms UnderFreq. Reset time (ms) 0 600000 10 int32
PTGFEna1 Step 1 enabled NO / YES Boolean
StrVal1 Step 1. Start value (Hz) 45 65 0,01 float32
OpDlTmms1 Step 1. Delay time(ms) 0 600000 10 int32
StTyp1 Step 1. Function type Maximum/Minimum enum
LogInBlk1 Step 1. Blocking input uint32
PTGFEna2 Step 2. Enabled NO / YES Boolean
StrVal2 Step 2. Start value (Hz) 45 65 0,01 float32
OpDlTmms2 Step 2. Delay time(ms) 0 600000 10 int32
StTyp2 Step 2. Function type Maximum/Minimum enum
LogInBlk2 Step 2. Blocking input uint32
PTGFEna3 Step 3. Enabled NO / YES Boolean
StrVal3 Step 3. Start value (Hz) 45 65 0,01 float32
OpDlTmms3 Step 3. Delay time(ms) 0 600000 10 int32
StTyp3 Step 3. Function type Maximum/Minimum enum
LogInBlk3 Step 3. Blocking input uint32
PTGFEna4 Step 4. Enabled NO / YES Boolean
StrVal4 Step 4. Start value (Hz) 45 65 0,01 float32
OpDlTmms4 Step 4. Delay time(ms) 0 600000 10 int32
StTyp4 Step 4. Function type Maximum/Minimum enum
LogInBlk4 Step 4. Blocking input uint32
PTGFEna5 Step 5. Enabled NO / YES Boolean
StrVal5 Step 5. Start value (Hz) 45 65 0,01 float32
OpDlTmms5 Step 5. Delay time(ms) 0 600000 10 int32
StTyp5 Step 5. Function type Maximum/Minimum enum
LogInBlk5 Step 5. Blocking input uint32
PTGFEna6 Step 6. enabled NO / YES Boolean
StrVal6 Step 6. Start value (Hz) 45 65 0,01 float32
OpDlTmms6 Step 6. Delay time(ms) 0 600000 10 int32
StTyp6 Step 6. Function type Maximum/Minimum enum
LogInBlk6 Step 6. Blocking input uint32
PTGFEna7 Step 7. enabled NO / YES Boolean
StrVal7 Step 7. Start value (Hz) 45 65 0,01 float32
OpDlTmms7 Step 7. Delay time(ms) 0 600000 10 int32
StTyp7 Step 7. Function type Maximum/Minimum enum
LogInBlk7 Step 7. Blocking input uint32
PTGFEna8 Step 8. enabled NO / YES Boolean
StrVal8 Step 8. Start value (Hz) 45 65 0,01 float32
OpDlTmms8 Step 8. Delay time(ms) 0 600000 10 int32
StTyp8 Step 8. Function type Maximum/Minimum enum
LogInBlk8 Step 8. Blocking input uint32
GenTrip General trip NO / YES Boolean
TripPerm Trip Permission by recloser 0 255 1 Bit meaning (1) ING
MaskEna Enable Events Record NO / YES Boolean

Table 78 Frequency function outputs

Signal Data Attribute


Level 1 Frequency Start Str1 general
Level 1 Frequency Trip Op1 general
Level 1 Frequency Status StEna1 stVal
Same for the rest of the steps
Level 8 Frequency Start Str8 general
Level 8 Frequency Trip OP8 general
Level 8 Frequency Status StEna8 stVal

Ingeteam Power Technology S.A.


User Manual 137
PROTECTION FUNCTIONS

3.5.2 Frequency rate of change


This unit has 8 steps. In each step, a relay is activated if the frequency variation per time unit is higher than the set value. The
variation can represent a reduction and/or an increase in the frequency, depending on the setting “Operation type”.

The function’s node, PROT/PFRC1, has independent settings for each step and common settings for all.

The common settings for all steps are as follows:

❑ Enabled. Indicates whether the unit is enabled or not.


❑ Operation type. Indicates the whether the frequency variation is a reduction (Negative), and increase (Positive) or both
(Negative and positive).
❑ Minimum current level (A). Indicates the minimum current value below which it does no act, the unit is not permitted to
pickup.
❑ Number of cycles (Start). Indicates the number of cycles during which the conditions necessary for the unit to pickup must
be met.
❑ Number of cycles (Reset). Indicates the number of cycles during which the drop conditions necessary for the unit to reset
must be met in the event of the unit's not having tripped.
❑ Reset delay time (ms). Once tripped, this is the time during which the reset conditions must be met in order to clear the
trip from the unit.
❑ Blocking Input. Selects the signal which, when active, blocks the unit.
❑ General trip. Indicates if this unit produces general trip or not. For additional details, see the section corresponding to the
recloser (3.12.6).
❑ Trip Permission by recloser. Indicates the trip and block permission in accordance with the recloser status: standby,
blocked, safety time after reclosing, after closing. It is configured bit by bit; for additional details, see section
corresponding to the recloser (3.12.6.3).
❑ Enable Events record. Allows the generation of protection events associated to the function. If set to “NO”, the function’s
protection events are not generated. If set to “YES”, the function’s specific mask is contemplated.
❑ Minimum allowed voltage (V). The setting as used in the frequency protection (PTGF1). Indicates the minimum voltage
value.
The independent settings for each of the 8 steps are:

❑ Supervision f max. Indicates the maximum frequency above with the frequency rate of change is not measured.
❑ f start value (Hz/s). Indicates the frequency variation value at which the function is activated.
❑ Delay time (ms). Indicates the time during which the conditions for the tripping of the function must be met.
❑ Trip lock. Selects the signal which, when active, locks the activation of the function; so, once activated, the signal is kept
until the lock signal and the rate of change signal are deactivated.
There are settings, commands and outputs.

❑ Nodes: PROT/PFRC1
❑ Settings and logical inputs. There are 6 settings tables. For details, see Table 79.
❑ Commands:
 “DOrdBlk”: Function blocking and unblocking. It only acts on the enabled steps. If acts on the 8 steps
❑ Outputs: Table 80 shows the function’s output data. They are independent for each step
 ROCOF df/dt Status. It is active when enabled and not blocked. Common for all steps.
 Level X df/dt Start. Indicates that the step has picked up. It is independent for each step. Where X indicates the level
from 1 to 8.
 Level X df/dt Trip. Indicates that the step has tripped. It is independent for each step. Where X indicates the level from
1 to 8.

Ingeteam Power Technology S.A.


User Manual 138
PROTECTION FUNCTIONS

Table 79 Frequency rate of change settings

Data Parameter Min. Max Step Remarks Type


PFRCEna Enabled NO / YES Boolean
Negative(0)
Positive (1)
Optype Operation type uint32
Negative and
Positive (2)
BlkValA Minimum current level (A) 0 100,0 0,1 float32
StrNumCyc Number of cycles (Start) 3 15 1 int32
RepNumCyc Number of cycles (Reset) 0 10 1 int32
RsDlTmms Reset delay time (ms) 0 600000 10 int32
BlkValHz1 Step 1: Supervision f max 40 70 0,01 float32
StrVal1 Step 1: f start value (Hz/s) 0,20 10 0,05 float32
OpDlTmms1 Step 1:Delay time (ms) 0 2000 10 int32
LogInTrLck1 Step 1: Trip Lock uint32
BlkValHz2 Step 2: Supervision f max 40 70 0,01 float32
StrVal2 Step 2: f start value (Hz/s) 0,20 10 0,05 float32
OpDlTmms2 Step 2: Delay time (ms) 0 2000 10 int32
LogInTrLck2 Step 2:Trip Lock uint32

Same for the rest of the steps

BlkValHz8 Step 8: Supervision f max 40 70 0,01 float32


StrVal8 Step 8: f start value (Hz/s) 0,20 10 0,05 float32
OpDlTmms8 Step 8: Delay time (ms) 0 2000 10 int32
LogInTrLck8 Step 8: Trip Lock uint32
GenTrip General trip NO / YES Boolean
TripPerm Trip Permission by recloser 0 255 1 Bit meaning (1) ING
LogInBlk Blocking input uint32
MaskEna Enable Events Record NO / YES Boolean

Table 80 Frequency rate of change function outputs

Signal Data Attribute


ROCOF df/dt Status StEna stVal
Level 1 df/dt Start Str1 general
Level 1 df/dt Trip Op1 general
Same for the rest of the steps
Level 8 df/dt Start Str8 general
Level 8 df/dt Trip OP8 general

General operation.

The function is only effective for frequencies inferior to a threshold called “maximum monitoring frequency”, currents greater than
the threshold called “minimum current” and voltages greater than the minimum monitoring threshold:

❑ Minimum monitoring current. The maximum phase current is compared to this setting. If the minimum current circulating
in all the phases is inferior to the setting, the frequency rate of change unit is not allowed to pickup. When a current is
greater than the set threshold appears in at least one of the phases, the relay waits for 10 cycles before running the
frequency rate of change function.
❑ Minimum monitoring voltage. If the phase B voltage is inferior to the setting, the frequency rate of change unit is not
allowed to pickup. When the voltage exceeds the set threshold, the relay waits for 10 cycles before running the frequency
rate of change function.
The frequency is measured each cycle and reloaded every half cycle, as shown in Figure 79.

The algorithm stores the periods of the signal’s last 4 cycles and calculates the frequency rate of change by comparing the current
cycle’s frequency measurement with the measurement taken from 4 cycles previously, taking into account the time lapse between
both (Figure 80).

Ingeteam Power Technology S.A.


User Manual 139
PROTECTION FUNCTIONS

df/dt = (f1 − f5)/(T1 + T2 + T3 + T4)

In which:

f5 =frequency measurement taken 4 cycles previously

f4 =frequency measurement taken 3 cycles previously T4 period of the 4th cycle starting from the end

f3 =frequency measurement taken 2 cycles previously T3 period of the 3rd cycle starting from the end

f2 =frequency measurement taken 1 cycle previously T2 period of the 2nd cycle starting from the end

f1 =Last frequency measurement T1 period of the last cycle

This calculation is repeated, taking into account the measurements separated by two cycles in order to ensure that the frequency
has fallen during the entire period, i.e., to ensure that an incorrect measurement does not lead to a trip. Two checks are carried
out:

❑ the measurement of the current cycle against that of the cycle minus two cycles
df/dt2 = (fn − fn − 4)/(tn − tn − 4)

❑ the measurement of the cycle minus two cycles against that of the cycle minus four cycles
df/dt3 = (fn − 4 − fn − 8)/(tn − 4 − tn − 8)
Figure 80 Frequency rate of change calculation

For the unit to pickup, the frequency rate of change must be exceeded by an absolute value during the set number of cycles. The
pickup is only produced if the frequency rate of change/voltage rate of change value meets the criterion selected in the setting
“Operation type”:

❑ Negative. The frequency rate of change/voltage rate is negative, i.e., when the current frequency is inferior to that
measured 4 cycles previously.
❑ Positive. The frequency rate of change/voltage rate is positive, i.e., when the current frequency is greater than that
measured 4 cycles previously.
❑ Negative and Positive. Acts on frequency rate of change/voltage rate in both directions.
During the pickup process, one measurement is allowed to be out of the pickup range without restarting the process. For example,
if 3 cycles are required to cause a pickup, the threshold need only be exceeded 3 times from a total of 4 consecutive
measurements.

In order for a trip to occur once the unit has picked up, the frequency rate of change measurement must remain between the set
frequency rate of change/voltage rate of change value and a reset value to the frequency rate of change/voltage rate of change
minus 0.05Hz/s during the set time.

In order for the unit to reset once it has picked up, the frequency rate of change/voltage rate of change measurement must be
detected as being 0.05Hz/s below the set value during the number of cycles programmes as reset cycles.

In order for the unit to reset once it has tripped, the frequency rate of change/voltage rate of change measurement must be
detected as being 0.05Hz/s below the set value during the reset time. Any sealing signals that have been configured must register a
value of zero in order for the trip to be deactivated.

Ingeteam Power Technology S.A.


User Manual 140
PROTECTION FUNCTIONS

Figure 81 Frequency rate of change trip diagram

3.6 POWER UNITS

3.6.1 General
Using the voltage and current measurements, the real and reactive powers and the power factor are calculated. The values
obtained are used for the power protection functions.

The trip thresholds are programmed as a percentage of the rated apparent power, S = 3 · V · I, in which:

❑ Vn: rated phase to ground voltage (phase-ground) of the PROT/TVTR node.


❑ In: The rated phase current of the PROT/TCIN node.
The units’ reset threshold is configured in the PROT/PDOP1 node, ranging from 0.1% to 5%:

❑ P reset threshold (%). Indicates the reset threshold for the real power units.
❑ Q reset threshold (%). Indicates the reset threshold for the reactive power units.
❑ S reset threshold (%). Indicates the reset threshold for the apparent power units.
Table 81 Power units reset settings

Data Setting Minimum Maximum Step Remarks Type


RepValP P reset threshold (%) 0.1 5 0,1 float32
RepValQ Q reset threshold (%) 0.1 5 0,1 float32
RepValS S reset threshold (%) 0.1 5 0,1 float32

The power units’ settings are similar to each other. Each unit has independent settings:

❑ Enabled. Indicates whether the function is enabled or not.


❑ Start value (%). Indicates the percentage in relation to the rated power necessary for the unit to pickup.

Ingeteam Power Technology S.A.


User Manual 141
PROTECTION FUNCTIONS

❑ Delay time (ms). Indicates the time during which the conditions for the tripping of the function must be met.
❑ Blocking Input. Selects the signal which, when active, blocks the step.
❑ General trip. Indicates if this unit produces general trip or not. For additional details, see the section corresponding to the
recloser (3.12.6).
❑ Trip Permission by recloser. Indicates the trip and block permission in accordance with the recloser status: standby,
blocked, safety time after reclosing, after closing. It is configured bit by bit; for additional details, see section
corresponding to the recloser (3.12.6.3).
❑ Enable Events record. Allows the generation of protection events associated to the function. If set to “NO”, the function’s
protection events are not generated. If set to “YES”, the function’s specific mask is contemplated.
Table 82 Power unit settings

Data Setting Minimum Maximum Step Remarks Type


PDUPEna (minimum) Boolean
Enabled NO / YES
PDOPEna(maximum) Boolean
PcStrVal Start value (%) 1,0 200,0 0,1 float32
OpDlTmms Delay time (ms) 0 60000 10 int32
GenTrip General trip NO / YES Boolean
TripPerm Trip Permission by recloser 0 255 1 Bit meaning (1) ING
LogInBlk Blocking input uint32
MaskEna Enable Events Record NO / YES Boolean

The settings, commands and outputs available are similar in all the units, with the exception of the node:

❑ Node: Indicated in each specific unit.


❑ Settings and logical inputs. There are 6 settings tables. For details, see Table 81 and Table 82.
❑ Commands:
 “DOrdBlk”: Function blocking and unblocking. Only acts if the unit is enabled.
❑ Outputs: Table 83 shows the function’s output data.
 X Status. It is active when enabled and not blocked.
 X Start. Indicates that the unit has picked up.
 X Trip. Indicates that the unit has tripped.
Where X indicates the Power protection unit.

Table 83 Power function outputs

Signal Data Attribute


X Status StEna stVal
X Start Str general
X Trip Op general

3.6.2 Minimum real power


This unit’s node is PROT/PDUP1.

It provides protection against excessive decreases in the generated power. It compares the real power with the minimum power
given by the setting. In the event of the generated power being inferior to the power established in the setting during the
programmed time, the protection trips the corresponding relay. Any reverse power will be considered as below the minimum
power threshold and will thus activate the function.

In order to reset, the power must exceed the pickup threshold plus the reset percentage. For example, if the reset percentage is set
at 2%, the unit will reset if the power exceeds the 102% of the pickup threshold.

The settings, commands and outputs available are indicated in section 3.6.1.

Ingeteam Power Technology S.A.


User Manual 142
PROTECTION FUNCTIONS

Table 84 Minimum real power function outputs

PDUP1 Signals Data (Edition 1) Attribute (Edition 1) Data (Edition 2) Attribute (Edition 2)
Minimum P Start Str stVal Str general
Minimum P Trip Op stVal Op general
Minimum P Status StEna stVal StEna stVal

3.6.3 Maximum real power


There are two independent units, whose nodes are PROT/PDOP1 and PROT/PDOP2.

It provides protection against excessive increases in the power generated. It compares the real power with the maximum power
given by the setting. In the event of the generated power being greater than the power established in the setting during the
programmed time, the protection trips the corresponding relay.

In order to reset, the power must be inferior to the pickup threshold less the reset percentage. For example, if the reset percentage
is set at 2%, the unit will reset if the power is inferior to 98% of the pickup threshold.

The settings, commands and outputs available are indicated in section 3.6.1.

Table 85 Maximum real power function outputs

PDOP1 Signals PDOP2 Signals Data (Edition 1) Attribute (Edition 1) Data (Edition 2) Attribute (Edition 2)
High Maximum P Start Low Maximum P Start Str stVal Str general
High Maximum P Trip Low Maximum P Trip Op stVal Op general
Maximum P Level 1 Status Maximum P Level 2 Status StEna stVal StEna stVal

3.6.4 Real power inversion


There are two independent units, whose nodes are PROT/PDOP3 and PROT/PDOP4.

The protection is activated when the real power flow is inverted (motorization of generators).

In order to act, the real power must be negative; in the event of the real power exceeding the set value during the programmed
time, the protection trips the corresponding relay.

In order to reset, the power must be inferior to the pickup threshold less the reset percentage.

For example, if the threshold is set at 100W, the unit will pickup as of a measured power of -100w. If the reset percentage is set at
2%, the unit will reset when the power is below -98W (98% of set value).

The settings, commands and outputs available are indicated in section 3.6.1.

Table 86 Real power inversion function outputs

PDOP3 Signals PDOP4 Signals Data (Edition 1) Attribute (Edition 1) Data (Edition 2) Attribute (Edition 2)
High P Inversion Start Low P Inversion Start Str stVal Str general
High P Inversion Trip Low P Inversion Trip Op stVal Op general
P Inversion Level 1 Status P Inversion Level 2 Status StEna stVal StEna stVal

3.6.5 Reactive power inversion


There are two independent units, whose nodes are PROT/PDOP5 and PROT/PDOP6.

The protection is activated when the reactive power flow is inverted (field loss in generators).

In order to act, the reactive power must be negative; in the event of the real power exceeding the set value during the
programmed time, the protection trips the corresponding relay.

In order to reset, the power must be inferior to the pickup threshold less the reset percentage.

Ingeteam Power Technology S.A.


User Manual 143
PROTECTION FUNCTIONS

For example, if the threshold is set at 100W, the unit will pickup as of a measured power of -100w. If the reset percentage is set at
2%, the unit will reset when the power is below -98W (98% of set value).

The settings, commands and outputs available are indicated in section 3.6.1.

Table 87 Reactive power inversion function outputs

PDOP5 Signals PDOP6 Signals Data (Edition 1) Attribute (Edition 1) Data (Edition 2) Attribute (Edition 2)
High Q Inversion Start Low Q Inversion Start Str stVal Str general
High Q Inversion Trip Low Q Inversion Trip Op stVal Op general
Q Inversion Level 1 Status Q Inversion Level 2 Status StEna stVal StEna stVal

3.6.6 Minimum apparent power


This unit’s node is PROT/PDUP2.

It provides protection against excessive decreases in the power generated. It compares the apparent power with the minimum
power given by the setting. In the event of the generated power being inferior to the power established in the setting during the
programmed time, the protection trips the corresponding relay.

In order to reset, the power must exceed the pickup threshold plus the reset percentage. For example, if the reset percentage is set
at 2%, the unit will reset if the power exceeds the 102% of the pickup threshold.

The settings, commands and outputs available are indicated in section 3.6.1.

Table 88 Minimum apparent power function outputs

Signal Data (Edition 1) Attribute (Edition 1) Data (Edition 2) Attribute (Edition 2)


Minimum S Start Str stVal Str general
Minimum S Trip Op stVal Op general
Minimum S Status StEna stVal StEna stVal

3.6.7 Maximum apparent power


There are two independent units, whose nodes are PROT/PDOP7 and PROT/PDOP8.

It provides protection against excessive increases in the power generated. It compares the apparent power with the maximum
power given by the setting. In the event of the generated power being greater than the power established in the setting during the
programmed time, the protection trips the corresponding relay.

In order to reset, the power must be inferior to the pickup threshold less the reset percentage. For example, if the reset percentage
is set at 2%, the unit will reset if the power is inferior to 98% of the pickup threshold.

The settings, commands and outputs available are indicated in section 3.6.1.

Table 89 Maximum apparent power function outputs

PDOP7 Signals PDOP8 Signals Data (Edition 1) Attribute (Edition 1) Data (Edition 2) Attribute (Edition 2)
High Maximum S Start Low Maximum S Start Str stVal Str general
High Maximum S Trip Low Maximum S Trip Op stVal Op general
Maximum S Level 1 Status Maximum S Level 2 Status StEna stVal StEna stVal

Ingeteam Power Technology S.A.


User Manual 144
PROTECTION FUNCTIONS

3.7 LOAD ENCROACHMENT

This unit specifies a functioning zone in which the phase-phase units of the distance functions are blocked (mho and quadrilateral).
Figure 82 shows this unit's diagram.

For the operation of the load encroachment, the following conditions must be fulfilled:

❑ The phase-phase impedance is between impedance margins (See Figure 82)6.


❑ The positive sequence and phase combination current exceeds the threshold (setting).
The unit’s settings are as follows:

❑ Enabled. Indicates whether the function is enabled or not.


❑ Minimum I threshold (A). Indicates the minimum current positive sequence and phase combination value necessary to
activate the unit.
❑ Z forward (Ohm). Indicates the forward load zone impedance module.
❑ Positive angle Forward (º). Indicates the load zone's positive limit angle forward.
❑ Negative angle Forward (º). Indicates the load zone's negative limit angle forward.
❑ Z reverse (Ohm). Indicates the reverse load zone impedance module.
❑ Positive angle reverse (º). Indicates the load zone's positive limit angle backwards.
❑ Negative angle reverse (º). Indicates the load zone's negative limit angle backwards.
❑ Blocking input. Selects the signal which, when active, blocks the function.
❑ Enable Events record. Allows the generation of protection events associated to the function. If set to “NO”, the function’s
protection events are not generated. If set to “YES”, the function’s specific mask is contemplated.
It has independent settings, commands and outputs:

❑ Node: PROT/PLEC1
❑ Settings and logical inputs. There are 6 settings tables. For details, see Table 90.
❑ Commands:
 “DOrdBlk”: Function blocking and unblocking. Only acts when the function is enabled.
❑ Outputs: Table 91 shows the function's output data.
 Load Encroachment. Indicates that the unit is active.
 Load Encroachment Status. Indicates the function’s status. It is active when enabled and not blocked.

Table 90 Load zone settings

Data Setting Min. Max Step Remarks Type


LoEnEna Enabled NO / YES Boolean
BlkValI1 Minimum I threshold (A) 0,05 25 0,01 float32
FwRisLod Z forward (Ohm) 0,01 500 0,01 float32
FwAngLod Positive angle forward (º) 0 90 1 float32
FwNAngLod Negative angle forward (º) 270 359 1 float32
RvRisLod Z reverse (Ohm) 0,01 500 0,01 float32
RvAngLod Positive angle reverse (º) 90 180 1 float32
RvNAngLod Negative angle reverse (º) 180 270 1 float32
LogInBlk Blocking input uint32
MaskEna Enable Events Record NO / YES Boolean

6
Since DSP version 4.0 phase-phase impedance is used. Previoues versions use positive sequence impedance.

Ingeteam Power Technology S.A.


User Manual 145
PROTECTION FUNCTIONS

Table 91 Load zone function outputs

Signal Data Attribute


Load Encroachment Op general
Load Encroachment Status StEna stVal

Figure 82 Load Zone Diagram

3.8 FUSE FAILURE

The measurement obtained from the half-cycle DFT is used to obtain results before the protection units are activated.

The fuse failure conditions are as follows:

❑ The three breakers are closed. (Open pole detector). Signals "Open pole (1 or 2)" and "3 open poles" of the scheme. If the open
pole detector is disabled, the three poles are considered closed.
❑ I1 positive sequence current is greater than 5% of the rated current. 7
❑ The increase in I1 positive sequence and the IN neutral current in relation to the current measured 1 cycle previously must be less
than 0.1A for 5A rated current or 0.02A for rated current 1A.
❑ The fault detection unit must be deactivated (Fault detection signal of the scheme).
❑ Distance units (mho or quadrilateral) and/or overcurrent units (phase, ground, earth system and unbalanced) have not picked up.
❑ The angle difference between currents I1 and I0 and those of 1 cycle previous are less than 5º.
❑ The V1 positive sequence voltage, memorized 1 cycle previously, must exceed VFF and drop below 95% of VFF,
VFF = VN · 80% (V)

With VN as the rated phase to ground voltage (PROT/TVTR node).

If the function detects all the above conditions, or if the “Fuse Failure input” is activated, a fuse failure pickup signal is produced and
used to block the units in question (configurable).

These conditions must be met during a programmable time in order for the fuse failure trip to be activated. Once tripped, the fuse fault
is maintained until the V1 voltage rises above VFF.

If any of the overcurrent functions (phase, ground, earth system and unbalanced) or distance units have picked up or if during the
timeout the relay picks up at least one of these units, the fuse failure output is not activated as the situation is considered a fault, not a
fuse failure.

7
From firmware version 5.19.15.7 and ICD version 6.3.1.4 can be set. In previous versions, it was fixed 5%.

Ingeteam Power Technology S.A.


User Manual 146
PROTECTION FUNCTIONS

The fuse failure pickup and trip are also activated when the digital “Fuse Fail input” is activated independently of the programmed
time. The fuse failure is only deactivated when the input is deactivated.

If the “Fuse Fail input” input is activated, the synchrocheck unit is deactivated.

The fuse failure pickup can be used as a blocking signal for other functions by means of each function’s logic signals.

The overcurrent units have settings that configure their functioning in the event of a fuse failure, allowing the enabling of the function,
the inhibition of directional, etc.

The settings used in these functions are:

❑ Enabled. Indicates whether the function is enabled or not.


❑ Delay time (ms). Indicates the time during which the conditions must be met in order for the trip to take place.
❑ Blocking Input. Selects the signal which, when active, blocks the function.
❑ Fuse Fail input. Selects the signal which, when active, indicates a fuse failure.
❑ FF input (B side-sinc1). It selects the signal which, when activated, indicates a fuse failure on breaker 1’s side B synchronism.
❑ FF input (B side-sinc2). It selects the signal which, when activated, indicates a fuse failure on breaker 2’s side B synchronism.
❑ Minimum I1/Irated(%)7.Indicates the minimum value of I1 in relation to rated I. 7
❑ Enable Events record. Allows the generation of protection events associated to the function. If set to “NO”, the function’s
protection events are not generated. If set to “YES”, the function’s specific mask is contemplated.

Figure 83 Fuse failure scheme

It has independent settings, commands and outputs:

❑ Node: PROT/RFUF1
❑ Settings and logical inputs. There are 6 settings tables. For details, see Table 92.
❑ Commands:
 “DOrdBlk”: Function blocking and unblocking. Only acts when the function is enabled.
❑ Outputs: Table 93 shows the function’s output data.

Ingeteam Power Technology S.A.


User Manual 147
PROTECTION FUNCTIONS

 Fuse Failure Start. Indicates that the fuse failure has picked up.
 Fuse Failure Trip. Indicates that the fuse failure has tripped, that is, the additional time has elapsed with the unit picked up.
 Fuse Failure B1 Activation. Indicates that fuse failure is activated on breaker 1’s synchronism B side.
 Fuse Failure B2 Activation. Indicates that fuse failure is activated on breaker 2’s synchronism B side.
 Fuse Failure Status. Indicates the function’s status. It is active when enabled and not blocked.

Table 92 Fuse failure settings

Data Setting Min. Max. Step Remarks Type


RFUFEna Enabled NO / YES Boolean
OpDlTmms Delay time (ms) 0 10000 10 int32
LogInBlk Blocking input uint32
LogInFF Fuse Fail input uint32
LogInFFB1 FF input (B side-sinc1) uint32
LogInFFB2 FF input (B side-sinc2) uint32
MaskEna Enable Events Record NO / YES Boolean
BlkValI1 Minimum I1/Irated(%) 2 10 1 uint32

Table 93 Fuse failure function outputs

Signal Data Attribute


Fuse Failure Start Str general
Fuse Failure Trip Op general
Fuse Failure B1 Activation FFB1 general
Fuse Failure B2 Activation FFB2 general
Fuse Failure Status StEna stVal

3.9 POWER SWING

This unit determines the function conditions according to which distance function trips is disabled for single-phase and/or phase-phase
units and for each zone, depending on the settings.

Differentiation is made between stable and unstable power swing.

❑ Stable swing: when distance functions can be blocked by generating the "Power Swing Blocked" signal.
❑ Unstable swing: when some system elements can be tripping to prevent the disturbance extending. To do this, this
function generates the "OST- Out of Step Tripping" signal.
To determine swinging conditions, the complete positive sequence impedance is used (for 3 closed poles) or the minimum impedance
of phase (A, B, C) or phase combination (AB, BC or CA) of the closed poles (if there is 1 open pole). By calculating the position of this
impedance in the R/X diagram, it is possible to measure how and at what speed it is moving. To do this, on the one hand, some zones
are defined in the diagram, and on the other some transfer times from one zone to another are defined. These zones and times are
parameterised by settings.

Figure 84 shows the power swinging characteristic diagram.

Ingeteam Power Technology S.A.


User Manual 148
PROTECTION FUNCTIONS

Figure 84 Power Swing Characteristic

Figure 86 shows this unit's logic diagram. On the one hand, it shows the "PSB" signal's activation conditions and on the other, the "OST"
signal's activation conditions.

"Power Swing Blocking" (PSB) is activated when any of the following conditions is fulfilled:

❑ The positive sequence impedance takes a time longer than the "Blocking Time (ms)" (setting) to pass from the outside
zone to the middle zone and the unblocking signal is not activated (See Figure 84).
❑ The positive sequence impedance goes into the middle zone and the time between going from the outside zone to the
middle zone is longer than the "Trip Time (ms)" (setting) and shorter than the "Blocking Time (ms)" (setting) and the
unblocking signal is not activated. In this case the trip must be enabled and not blocked (See Figure 84).
If the 3 poles are closed, blocking only affect the phase-phase units. With 1 pole open, blocking affects all single- and phase-phase
units. The breaker status is determined by digital inputs.

Once activated, the "PSB" signal is maintained for 2 seconds as long as no unblocking conditions are fulfilled and that it is inside the
outer zone. If the "Memory Enabled" setting is "YES", blocking will last 1 second once outside the outer zone. If it is "NO", there is no
blocking once outside the outer zone.

Each of the zones, for both the Mho and Quadrilateral characteristics can be blocked or unblocked by this function depending on the
setting selection: "Zone 1 Blocking"…"Zone 5 Blocking".

It is also possible to block the teleprotection using the setting "Teleprotection Blocking" so that TPR reception and TPT transmission is
ignored.

The activation of "Trip by Power Swing" (OST) is determined depending on the "Trip Enabled" setting. If this setting is "NO", the trip is
never activated.

If the setting is IN_ZMED, the conditions for activation are as follows:

❑ The positive sequence impedance goes into the middle zone and the time between going from the outside zone to the
middle zone is longer than the "Trip Time (ms)" (setting) and shorter than the "Blocking Time (ms)" (setting).See Figure 84.
❑ The unblocking signal is not activated.
If the setting is OUT_ZMED, the conditions for activation are as follows:

❑ If the case is as above (the positive sequence impedance enters the middle zone and the time it takes to go from the outer
zone to the middle zone is greater than "Trip Time (ms)" and less than "Blocking Time (ms)", the impedance leaves the
middle zone through the opposite side to where it entered. See Figure 84.
❑ When the previous condition is fulfilled, if the time set in "Trip delay" is grather than zero, the activation is when the set
time has elapsed since the impedance has left all the zones and has not re-entered in any of they. If the set time is zero,
the previous condition is enough.
❑ The unblocking signal is not activated.
The unblocking signal is activated if any of the following conditions is fulfilled:

❑ The positive sequence threshold is less than "I1 Minimum threshold (A)" (setting).

Ingeteam Power Technology S.A.


User Manual 149
PROTECTION FUNCTIONS

❑ There is more than one pole open.


❑ The fuse fault function is active.
❑ The impedance stays in the internal zone for a time longer than the one indicated in the "Internal Zone unblock T (ms)".
❑ If there are 3 poles closed and the following conditions are fulfilled during "After fault Reset time (ms)" (setting):
 The phase selector detects a two- or single-phase fault using the negative sequence percentage (I2>0.05xIrated
& I2/I1>10%).
 The negative sequence current exceeds "I2 Threshold (A)" (setting).
The unit’s settings are as follows:

❑ Enabled. Indicates whether the function is enabled or not.


❑ Memory Enabled. Indicates whether or not the swing blocking signal will be maintained for 1 second, after leaving the
outer zone.
❑ Zone X Blocking. Enables or disables blocking each zone of the unit.
❑ Teleprotection Blocking. Enables or disables teleprotection blocking.
❑ Middle zone Right R. Resistive limit of the middle zone for R>=0 (See Figure 84).
❑ Middle zone Left R. Resistive limit of the middle zone for R>=0 (See Figure 84).
❑ Middle zone Top Z. Limit impedance of the middle zone for X>=0 (See Figure 84).
❑ Middle zone Bottom Z. Limit impedance of the middle zone for X<0 (See Figure 84).
❑ Internal zone Right R. Resistive limit of the inner zone for R>=0 (See Figure 84).
❑ Internal zone Left R. Resistive limit of the inner zone for R<0 (See Figure 84).
❑ I1 Minimum threshold (A).This is the minimum I1 required to activate the swing function.
❑ Slope angle. Indicates the slope angle of the resistive limits (See Figure 84).
❑ Power swing detection zone (8Distance between zones). Indicates the width of the outer zone (See Figure 84).
❑ Blocking time (ms). Time for going between the outer zone and middle zone for activating blocking.
❑ Trip Enabled. Indicates the way of determining whether there is a trip condition.
❑ Trip Time (ms). Time for going between the outer zone and middle zone for activating the trip.
❑ Internal Zone unblock T (ms). Minimum time in milliseconds for which the impedance must remain in the "inner zone" to
unblock operating in all zones.
❑ I2 threshold (A). With 3 poles closed, if I2 exceeds this threshold and the fault selector is activated, unblocking occurs.
❑ After fault Reset time (ms). This is the time that elapses before disabling swing blocking as soon as a phase-phase or single-
phase fault is detected (based on the I2 threshold in the phase selector).
❑ Trip delay. It is only used, when the power swing trip is enabled with the option “OUT_ZMED”. If it is greater than zero,
once the OUT_ZMED condition is fulfilled, the trip is delayed this time since the impedance has left all the zones and has
not re-entered any of them.
❑ Blocking input. Selects the signal which, when active, blocks the function.
❑ Trip Blocking input. Selects the signal which, when active, blocks the trip by swinging.
❑ General trip. Indicates if this unit produces general trip or not. For additional details, see the section corresponding to the
recloser (3.12.6).
❑ Enable Events record. Allows the generation of protection events associated to the function. If set to “NO”, the function’s
protection events are not generated. If set to “YES”, the function’s specific mask is contemplated.

88
Until the version 8.1.0.0 of ICD the name was " Distance between zones "

Ingeteam Power Technology S.A.


User Manual 150
PROTECTION FUNCTIONS

Table 94 Power swing settings

Data Setting Minimum Maximum Step Remarks Type


OOSEna Enabled NO / YES Boolean
BlkMemEna Memory Enabled NO / YES Boolean
Z1Blk Zone 1 Blocking NO / YES Boolean
: The same for zones 2, 3 , 4
Z5Blk Zone 5 Blocking NO / YES Boolean
TpBlk Teleprotection Blocking NO / YES Boolean
RisMedRi Middle zone Right R 0,05 500 0,01 float32
RisMedLe Middle zone Left R 0,05 500 0,01 float32
ReacMedHi Middlezone Top X 0,05 500 0,01 float32
ReacMedLo Middle zone Bottom X 0,05 500 0,01 float32
RIntRi Internal zone Right R 0,05 500 0,01 float32
RIntLe Internal zone Left R 0,05 500 0,01 float32
I1Val I1 Minimum threshold (A) 0,05 500 0,01 float32
BlArg Slope angle 45 90 0,01 float32
ZDisOhm Power swing detection zone 0,1 100 0,1 float32
SwgTmms Blocking time (ms) 5 100 5 int32
NO (0)
TrEna Trip Enabled IN_ZMED (1) uint32
OUT_ZMED (2)
TrTmms Trip Time (ms) 5 100 5 int32
UnBlTmms Internal Zone unblock T (ms) 60 10000 5 int32
I2Val I2 threshold (A) 0 100 0,01 float32
RstTmms After fault Reset time (ms) 0 1000 5 int32
TrDelay Trip delay 0 1000 5 int32
TrRepNu Repetitions for trip 1 3 1 int32
TrIntTmms Interval time for trip (ms) 0 1000 5 int32
LogInBlk Blocking input uint32
LogInTrBlk Trip Blocking input uint32
GenTrip General Trip NO / YES Boolean
MaskEna Enable Events Record NO / YES Boolean

It has independent settings, commands and outputs:

❑ Node PROT/RPSB1
❑ Settings and logical inputs. There are 6 settings tables. For details, see Table 94.
❑ Commands:
 “DOrdBlk”: Function blocking and unblocking. Only acts when the function is enabled.
 "DOrdOpBlk": Blocking and unblocking of the trip by power swing. Only applicable if the "Trip Enabled" setting is not
set to "NO".
❑ Outputs: Table 95 shows the function's output data.
 Z1 Ph-Ph Blocked PSB. Indicates blocking of the phase-phase units in zone 1.
 ….. Same for zones 2 to 5.
 Z1 Gnd Blocked PSB. Indicates blocking of the single-phase units in zone 1.
 ….. Same for zones 2 to 5.
 Teleprotection blocked PSB. Indicates that the teleprotection is blocked by the power swing.
 Power swing blocked. Time conditions are fulfilled when passing from the outer zone to the middle zone without
detecting a fault.
 Power swing Trip. Trip signal by power swing.
 Power swing unblocked. Blocking reset by power swing.
 PSB unblocked internal zone. The impedance has stayed in the inner zone for the time indicated in the "Inner zone
unblocking time" and no other unblocking conditions have been fulfilled.
 Z in ZMED+. The impedance seen is in the middle zone positive. The impedance has a positive resistive component.

Ingeteam Power Technology S.A.


User Manual 151
PROTECTION FUNCTIONS

 Z in ZMED-. The impedance seen is in the middle zone negative. The impedance has a negative resistive component.
 Z in Middle zone. The impedance seen is in the middle zone.
 Z in External zone. The impedance seen is in the external zone.
 Z in Internal zone. The impedance seen is in the internal zone.
 Power swing status. Indicates whether or not the power swing function is enabled.
 Power swing trip status. Indicates whether or not the trip power swing function is enabled.

Table 95 Power Swing Function Outputs

Signal Data Attribute


Z1 Ph-Ph Blocked PSB Z1PhBl general
… The same for zones 2, 3 , 4 and 5
Z1 Gnd Blocked PSB Z1GndBl general
… The same for zones 2, 3 , 4 and 5
Teleprotection blocked PSB TPBl general
Power swing blocked Blk general (stVal in Ed2)
Power swing Trip Op general
Power swing unblocked UnBlk general
PSB unblocked internal zone ZMUnBl general
Z in ZMED+ ZMPIn general
Z in ZMED- ZMNIn general
Z in Middle Zone Zmed general
Z in External Zone ZEXT general
Z in Internal Zone Zint general
Power swing Status StEna general (stVal in Ed2)
Power swing trip status TrPt general

Figure 85 Power Swing Logic Diagram (Trip).

Ingeteam Power Technology S.A.


User Manual 152
PROTECTION FUNCTIONS

Figure 86 Power Swing Logic Diagram (Blocking).

The input signals of this scheme are:

❑ Fuse failure start. Blocked by the fuse failure start signal.


❑ Breaker status. The breaker status signals are determined by the digital inputs:
 3 poles closed. Indicates the 3 poles are closed.
 52 2 poles open. Indicates 2 poles are open.
 52 3 poles open. Indicates the 3 poles are open.

3.10 SWITCH ONTO FAULT

This unit provides an instantaneous three-phase trip when a fault occurs upon the generation of a breaker closure command (manual
or by input).

The function is enabled during a programmable time ("Activation time (ms)") in the following situations:

❑ Upon the closure of the 3-poles, or


❑ Following the closure command.
Depending on the “Operation type” setting, the action of the switch onto fault is produced when:

 Programmed as “V and I" or "(V and I) or Z2”: The phase voltage is below a threshold (set in the open pole detector) and the
phase current is above a threshold for ½ cycle.

Ingeteam Power Technology S.A.


User Manual 153
PROTECTION FUNCTIONS

 Programmed as “Z2” or “(V and I) or Z2”: The zone 2 of the distance units (mho or quadrilateral) is started.
 Programmed as "programmable pick up I": The Programmable SOTF Pick up input is activated.
During the "Activation time (ms)" that the function is enabled, an offset of 0.1 ohms is applied to the mho characteristic in zone 2. On
the other hand, the X reach is set to 0.05 ohms, contrary to the programmed direction, in the quadrilateral characteristic in zone 2.
Therefore, the three - phase faults are protected in the origin. Also, the directional supervision is not used and both directions are
allowed.

Depending on the configuration set the switch onto fault can be active with any closing. 9

❑ To enable it after a manual closing and to produce a definitive trip (no reclosing allowed):
 Reclose perm. (R1, R2, R3, R4): NO.
 Trip permission by recloser: Only "Recloser lockout" and "Trip permission after manual closing" have to be selected.
❑ To enable it after any closing and to produce a definitive trip (no reclosing allowed):
 Reclose perm. (R1, R2, R3, R4): NO.
 Trip permission by recloser: Select "Recloser lockout" and the desired trip permissions.
❑ To allow reclosings:
 Reclose perm. (R1, R2, R3, R4): Select the desired option.
 Trip permission by recloser: Do not select "Recloser lockout" and select the desired trip permissions.
The function’s settings are:

❑ Enabled. Indicates whether the function is enabled or not.


❑ Operation type. Indicates the unit’s operation type.
 Programmable10. The action is produced with the logical pickup input.
 V and I. The V and I measurements are checked in order to determine the switch onto fault.
 Z2 or (V and I). The V and I measurements or the zone 2 start signals are checked in order to determine the switch onto fault.
 Z2. The zone 2 start signals are checked in order to determine the switch onto fault.
❑ Operation delay start input. When it is enabled and dead line is detected, it allows switch onto fault function.
❑ Normalized voltage Reset. Indicates if resetting due to voltage above the threshold is enabled or not. It only works, if the
"Operation type" is "Z2" or "Z2 or (V and I)".
❑ I phase threshold (A). Indicates the current value for indicating a switch onto fault.
❑ Activation time (ms). Indicates the time during which the unit is enabled once the start conditions have been met.
❑ Blocking Input. Selects the signal which, when active, blocks the function.
❑ SOFT Start input10. Selects the signal which, when active, indicates the activation of the switch onto fault. It only functions if the
operation type is set to “programmable”.
❑ Trip Permission by recloser9. Indicates the trip and block permission in accordance with the recloser status: standby, blocked, safety
time after reclosing, after closing. It is configured bit by bit; for additional details, see section corresponding to the recloser
(3.12.6.3).
❑ Reclose perm. (R1, R2, R3, R4) 9. Indicates whether each trip type can be reclosed or not, in accordance with the recloser's closing
cycle (see reclose permission mask).
❑ Enable Events record. Allows the generation of protection events associated to the function. If set to “NO”, the function’s
protection events are not generated. If set to “YES”, the function’s specific mask is contemplated.
The voltage threshold set in the open pole detector is used.

It has independent settings, commands and outputs:

❑ Node: PROT/PSOF1
❑ Settings and logical inputs. There are 6 settings tables. For details, see Table 96.

9
Available from firmware version 5.19.15.7 and ICD version 6.1.13.27 on. Until that version only acts with manual closings.
10
Available from firmware version 6.2.19.20 and ICD version 8.8.1.0

Ingeteam Power Technology S.A.


User Manual 154
PROTECTION FUNCTIONS

❑ Commands:
 “DOrdBlk”: Function blocking and unblocking. Only acts when the function is enabled.
❑ Outputs: Table 97 shows the function’s output data.
 Switch onto Fault Activation. Indicates that the switch onto fault has been activated.
 Switch onto Fault Status. Indicates the function’s status. It is active when enabled and not blocked.

Table 96 Switch onto fault settings

Data Setting Minimum Maximum Step Remarks Type


PSOFEna Enabled NO / YES Boolean
Programmable (1)11
V and I (2)
Optype Operation type uint32
Z2 or (V and I) (3)
Z2 (4)
TimAutEna Operation delay start input NO / YES
VNorRst Normalized voltage reset NO / YES
IThr I phase threshold (A) 0,01 200,0 0,01 float32
OpTmms Activation time (ms) 100 1000 10 int32
LogInBlk Blocking input uint32
LogInSt SOFT Start input11 uint32
TripPerm Trip Permission by recloser 0 255 1 Bit meaning (1) ING
NO (0)
Reclose 1 (1)
Reclose 2 (2)
Reclose 1-2 (3)
Reclose 3 (4)
Reclose 1-3 (5)
Reclose 2-3 (6)
Reclose 1-2-3 (7)
ReclPerm Reclose perm.(R1,R2,R3,R4) 0 15 enum
Reclose 4 (8)
Reclose 1-4 (9)
Reclose 2-4 (10)
Reclose 1-2-4 (11)
Reclose 3-4 (12)
Reclose 1-3-4 (13)
Reclose 2-3-4 (14)
Reclose 1-2-3-4 (15)
MaskEna Enable Events Record NO / YES Boolean

Table 97 Switch onto fault function outputs

Signal Data Attribute


Switch onto Fault Trip Op general
Switch onto Fault Status StEna stVal

Figure 87 shows the complete switch onto fault unit scheme.

The input signals of this scheme are:

❑ Fuse failure start. Blocked by the fuse failure start signal.


❑ Z2G Start. Indicates that any of the zone 2 phase-ground units have started.
❑ Z2F Start. Indicates that any of the zone 2 phase-phase units have started.
❑ 52_1 Closure command (Manual). Indicates manual close command of breaker 1
❑ 52_1 breaker closed (without reclosure command). The three poles of breaker 1 have been closed without reclose command.
❑ 52_2 Closure command (Manual). Indicates manual close command of breaker 2
❑ 52_2 breaker closed (without reclosure command). The three poles of breaker 2 have been closed without reclose command.
❑ Deenergized line in phases A, B and C. It´s the signal "DeadLine Phase ABC" of the dead line function.

11
Available from firmware version 6.2.19.20 and ICD version 8.8.1.0

Ingeteam Power Technology S.A.


User Manual 155
PROTECTION FUNCTIONS

Figure 87 Switch onto fault scheme

Ingeteam Power Technology S.A.


User Manual 156
PROTECTION FUNCTIONS 

3.11 BREAKER FAILURE

If a fault is detected, it is important to act quickly and for the switch to work correctly. However, it may be that an error occurs and it is
not able to interrupt the fault current.

The breaker failure function checks that there is no current via the switch, for a given time after the trip situation. If it is detected that
the current continues to be above a value established by the setting, a signal is activated so that secondary switches can act.

3.11.1 Single pole breaker Failure


The protection device has a complete breaker fault functional feature, with single-pole or three-pole functioning.

If the unit is enabled, it functions as follows (see Figure 88 y Figure 89):

❑ If the equipment indicates a trip signal or an external protection signal is received via a logic input, depending on the
value of the "Start type" setting, it will heed to one or the other to start up a timer.
❑ If the trip situation disappears or the function is tripping or starting externally, to verify this, the "Time signal relapse
(ms)" must elapse.
❑ If, following the period programmed as “Retrip time delay (ms)”, the current of one of the phases exceeds the
programmed "Phase current threshold (A)", the retrip signal is activated.
❑ If the "52 Supervision" setting is "YES", if, following the period programmed as “Retrip time delay (ms)” one of the poles
remains closed, after that time, the retrigger signal and the retrigger signal of that pole are activated.
❑ If, following the period programmed as “Trip time delay (ms)”, the current of one of the phases exceeds the programmed
"Phase current threshold (A)", the trip signal is activated.
❑ Regardless of the “Trip time delay (ms)”, if a blocked switch logic input is activated, the trip signal is activated.
❑ If the "Sealed by current" setting is "YES", the signals are only deactivated when the phase and neutral currents fall below
their drop out values.
In this unit, functioning does not contemplate the breaker status digital input, but rather the current values. The measurement
obtained from the half-cycle DFT of the full-cycle DFT is used (the lowest of both).

Each of the phases and neutral is analysed independently.

It has independent settings and outputs.

❑ Nodes:
 PROT/FRBRF1. The functions uses the measurements from the transformers 1, 2 and 3 (Ia1, Ib1, Ic1).
 PROT/FRBRF2. The functions uses the measurements from the transformers 4, 5 and 6 (Ia2, Ib2, Ic2). Only with 52 1/2
configurations.
❑ Settings and logical inputs. There are 6 settings tables. For details, see Table 98.
❑ Commands:
 “DOrdBlk”: Blocks and unblocks the function. Only acts when the function is enabled.
❑ Outputs: Table 99 shows the function's output data.
The settings used by this unit are as follows:

❑ Enabled. Indicates whether the function is enabled or not.


❑ Start type. The following options are available:
 External trips: the function's start logic inputs are taken into consideration.
 Internal trips: the equipment's internal trip activations are taken into consideration.
 Both: both the external activations (depending on the initial inputs) and the equipment's internal trip activations are
taken into account.

Ingeteam Power Technology S.A.


User Manual 157
PROTECTION FUNCTIONS 

❑ Operation type. The following options are available:


 Three-pole: functioning according to the Figure 89 diagram.
 Single-pole: functioning according to the Figure 88 diagram.
❑ Sealed by current. Indicates whether or not the disappearance of the trigger signal causes the function to relapse. In
other words, if the trip signal has to be permanent or simply a pulse.
❑ Time signal relapse (ms). Indicates the time for which the start situation is to be maintained, after the disappearance of
the internal trip or input start.
❑ Supervision by current. Indicates whether or not current is simultaneously needed with the trip order, in order for the
timers to start.
❑ Phase current threshold (A). Indicates the current value below which the phase is considered as open.
❑ Gnd current threshold (A). Indicates the current value below which the neutral is considered as open.
❑ Retrip time delay (ms). Indicates the waiting time for the activation of the retrip signal if the current does not drop below
the drop out level.
❑ Trip time delay (ms). Indicates the waiting time for the activation of the trip signal if the current does not drop below the
drop out level.
❑ Blocking input. Selects the signal which, when active, blocks the function.
❑ Pole A BF start input. Selects the signal which, when activated, indicates the start of breaker failure timing for phase A.
❑ Pole B BF start input. Selects the signal which, when activated, indicates the start of breaker failure timing for phase B.
❑ Pole C BF start input. Selects the signal which, when activated, indicates the start of breaker failure timing for phase C.
❑ 3 pole BF start input. Selects the signal which, when active, indicates the start of the breaker fault timing.
❑ Enable Events record. Allows the generation of protection events associated to the function. If set to “NO”, the function’s
protection events are not generated. If set to “YES”, the function’s specific mask is contemplated.
❑ 52 Supervision12. If set to YES, the signals can also be activated if the breaker poles are closed.

Table 98 Breaker failure Settings

Data Setting Minimum Maximum Step Remarks Type


RBRFEna Enabled NO / YES Boolean
External Trips (1)
InitType Start type Internal Trips (2) enum
Both (3)
Three-pole (0)
OpType Operation type enum
Single-pole (1)
CurLoc Sealed by current NO / YES Boolean
InRsTmms Time signal relapse (ms) 0 120000 1 Float
CurSpv Supervision by current NO / YES Boolean
DetValAPhs Phase current threshold (A) 0,02 150 0,01 Float
DetValAGnd Gnd current threshold (A) 0,02 150 0,01 Float
RfailTmms Retrip time delay (ms) 0 120000 1 Float
FailTmms Trip time delay (ms) 0 120000 1 Float
LogInBlk Blocking input Int32
LogInBFInA Pole A BF start input Int32
LogInBFInB Pole B BF start input Int32
LogInBFInC Pole C BF start input Int32
LogInBFI3P 3 pole BF start input Int32
MaskEna Enable Events Record NO / YES Boolean
SupEna 52 Supervision NO / YES Boolean

The breaker failure function's output signals are as follows:

❑ 50BF Retrigger pole A (Br1). Indicates that there has been a retrip due to a breaker failure in phase A.

12
Available from firmware versión 5.18.15.5 and ICDs version 6.1.14.1

Ingeteam Power Technology S.A.


User Manual 158
PROTECTION FUNCTIONS 

❑ 50BF Retrigger pole B (Br1). Indicates that there has been a retrip due to a breaker failure in phase B.
❑ 50BF Retrigger pole C (Br1). Indicates that there has been a retrip due to a breaker failure in phase C.
❑ Retrigger 50BF (Br1). Indicates that there has been a retrip due to a breaker failure in one of the poles.
❑ Time BF completed (Br1). Indicates that the trip signalling timer has finished.
❑ Trip 50BF (Br1). Indicates that there has been a trip due to a switch fault. This means that besides complying with the
timing indicated by "BF time finished", the current that circulates through the switch exceeds the function's activation
threshold.
❑ Start 50BF pole A (Br1). It is activated when the breaker fault conditions for the pole A are met during the set time.
❑ Start 50BF pole B (Br1). It is activated when the breaker fault conditions for the pole B are met during the set time.
❑ Start 50BF pole C (Br1). It is activated when the breaker fault conditions for the pole C are met during the set time.
❑ 50BF Ia exceeded (Br1). Indicates that in the breaker's pole A, the current exceeds the programmed fault detection
threshold.
❑ 50BF Ib exceeded (Br1). Indicates that in the breaker's pole B, the current exceeds the programmed fault detection
threshold.
❑ 50BF Ic exceeded (Br1). Indicates that in the breaker's pole C, the current exceeds the programmed fault detection
threshold.
❑ 50BF In exceeded (Br1). Indicates that in the neutral, the current exceeds the programmed fault detection threshold.
❑ Breaker failure status (Br1). Indicates the function’s status. It is active when enabled and not blocked.

Table 99 Breaker failure function outputs

Signal RBRF1 Signal RBRF2 Data Attribute


50BF Retrigger pole A (Br1) 50BF Retrigger pole A (Br2) ReOp phsA
50BF Retrigger pole B (Br1) 50BF Retrigger pole B (Br2) ReOp phsB
50BF Retrigger pole C (Br1) 50BF Retrigger pole C (Br2) ReOp phsC
Retrigger 50BF (Br1) Retrigger 50BF (Br2) ReOp general
Time BF completed (Br1) Time BF completed (Br2) TmBF general
Trip 50BF (Br1) Trip 50BF (Br2) Op general
50BF Start pole A (Br1) 50BF Start pole A (Br2) StrF phsA
50BF Start pole B (Br1) 50BF Start pole B (Br2) StrF phsB
50BF Start pole C (Br1) 50BF Start pole C (Br2) StrF phsC
50BF Ia exceeded (Br1) 50BF Ia exceeded (Br2) StrThr phsA
50BF Ib exceeded (Br1) 50BF Ib exceeded (Br2) StrThr phsB
50BF Ic exceeded (Br1) 50BF Ic exceeded (Br2) StrThr phsC
50BF In exceeded (Br1) 50BF In exceeded (Br2) StrThr Neut

The input signals to this function are:

❑ Pole A General Trip. Indicates that pole A general trip is operating.


❑ Pole B General Trip. Indicates that pole B general trip is operating.
❑ Pole C General Trip. Indicates that pole C general trip is operating.
❑ Tripolar Trip. Indicates that a 3 poles trip is activated.
❑ IA measurement. It is the fundamental phase A measurement, using ½ cycle DFT.
❑ IB measurement. It is the fundamental phase B measurement, using ½ cycle DFT.
❑ IC measurement. It is the fundamental phase C measurement, using ½ cycle DFT.
❑ IN measurement. It is the fundamental neutral measurement, using ½ cycle DFT.
❑ 52_x Locked. Indicates that the breaker is locked, where "x" is the breaker number.

Ingeteam Power Technology S.A.


User Manual 159
PROTECTION FUNCTIONS 

Figure 88 Single-pole phase A breaker Fault Diagram

The scheme for phases B and C is the same, replacing phase A with B or C as appropriate.

Figure 89 Three-pole Complete breaker Fault Diagram

Ingeteam Power Technology S.A.


User Manual 160
PROTECTION FUNCTIONS 

3.11.2 Breaker failure with low load


It detects breaker failure in three pole trips with low load.

The unit starts when the breaker status or overcurrent and start signal conditions are fulfilled:

❑ 52 status or overcurrent:
 If the "52 Supervision" set to "YES" and any pole is closed. The breaker status is determined with the 52 status digital
inputs.
 When enabled “Enable with Ground current”, the neutral current (3I0 for 52 ½ configuration) is greater than the
setting “Gnd current threshold (A)”.
❑ Start signal:
 Pole x BF start or 3 pole BF start signal lis received.
 If “2 pole trip allowed” is enabled, BF start signal of at least two phases is received.
The setting “Supervision Initial” 13 selects the start mode:

❑ YES. The unit starts when the breaker status or overcurrent conditions are fulfilled and the start signal is activated.
❑ NO. The unit starts when the start signal is activated.
The trip is generated when the “Trip time delay (ms)” finishes and none of the start conditions has been deactivated.

The retrip is generated when the “Retrip time delay (ms)” finishes and none of the start conditions has been deactivated.

If the "Supervision by current" setting is "YES", the retrip and trip signals are only activated when the neutral current is above the
“Gnd current threshold (A)” setting.

If the trip situation disappears or the function is tripping or starting externally, to verify this, the "Time signal relapse (ms)" must
elapse

If the "Sealed by current" setting is "YES", the signals are only deactivated when the neutral current falls below their drop out
values.

In 52 ½ configurations, the function is independent for every breaker, using 3I0 because the neutral measurement is not available.

13
Available from firmware version 6.0.18.2 and ICD version 8.1.0.20

Ingeteam Power Technology S.A.


User Manual 161
PROTECTION FUNCTIONS 

Figure 90 50BF low load scheme

Two independent functions are available (settings, outputs, commands…). Two nodes are used:

❑ Nodes:
 PROT/RGBF1. In 52 ½ configurations, the functions uses the measurements from the transformers 1, 2 and 3 (Ia1, Ib1,
Ic1).
 PROT/ RGBF2. In 52 ½ configurations, the functions uses the measurements from the transformers 4, 5 and 6 (Ia2, Ib2,
Ic2). Only with 52 1/2 configurations.
❑ Settings and logical inputs. There are 6 settings tables. For details, see Table 100.
❑ Commands:
 “DOrdBlk”: Blocks and unblocks the function. Only acts when the function is enabled.
❑ Outputs: Table 101 shows the function's output data.
The settings used by this unit are as follows:

❑ Enabled. Indicates whether the function is enabled or not.


❑ Start type. The following options are available:
 External trips: the function's start logic inputs are taken into account.
 Internal trips: the equipment's internal trip activations are taken into account.
 Both: both the external activations (depending on the initial inputs) and the equipment's internal trip activations are
taken into account.
❑ 2 pole trip allowed. It allows the start of the unit with phase-phase trips.
❑ Enable with Ground current. It allows the start of the unit when the neutral current is greater than the setting “Gnd
current threshold (A)”.

Ingeteam Power Technology S.A.


User Manual 162
PROTECTION FUNCTIONS 

❑ Gnd current threshold (A). Indicates the current value below which the neutral is considered as open.
❑ Retrip time delay (ms). Indicates the waiting time for the activation of the retrip signal if the current does not drop below
the drop out level.
❑ Trip time delay (ms). Indicates the waiting time for the activation of the trip signal if the current does not drop below the
drop out level.
❑ Blocking input. Selects the signal which, when active, blocks the function.
❑ Pole A BF start. Selects the signal which, when activated, indicates the start of breaker failure timing for phase A.
❑ Pole B BF start. Selects the signal which, when activated, indicates the start of breaker failure timing for phase B.
❑ Pole C BF start. Selects the signal which, when activated, indicates the start of breaker failure timing for phase C
❑ 3 pole BF start. Selects the signal which, when activated, indicates the start of breaker failure timing.
❑ Enable Events Record. Allows the generation of protection events associated to the function. If set to “NO”, the function’s
protection events are not generated. If set to “YES”, the function’s specific mask is contemplated.
❑ 52 Supervisión14.If set to YES, the the start of breaker failure can also be activated if the breaker poles are closed.
❑ Sealed by current14. Indicates whether or not the disappearance of the trigger signal causes the function to relapse. In
other words, if the trip signal has to be permanent or simply a pulse.
❑ Time signal relapse (ms)14. Indicates the time for which the start situation is to be maintained, after the disappearance of
the internal trip or input start
❑ Supervision by current13. If set to "YES", the retrip and trip signal are only activated when the neutral current is above the
setting “Gnd current threshold (A)”.
❑ Supervision Initial13. It selects whether the start of the unit is monitored by the status of the breaker and overcurrent or
only the start signal is used.
Table 101 shows the function's output signals:

❑ Retrip BF low load. Indicates that there has been a retrip due to a breaker failure.
❑ Trip BF low load. Indicates that there has been a trip due to a breaker failure.
❑ Start BF low load. It is activated when the breaker fault conditions have happened. If this conditions are activated during
the set time, generate the breaker failure signals.
❑ BF low load status. Indicates the function’s status. It is active when enabled and not blocked.

Table 100 50BF low load setting

Data Setting Minimum Maximum Step Remarks Type


Ena Enabled YES/NO Bolean
External Trips
InitType Start type 1 3 1 Internal Trips enum
Both
TPhTrEna 2 pole trip allowed YES/NO Bolean
GndDetEna Enable with Ground current YES/NO Bolean
BlkGndA Gnd current threshold (A) 0,02 150 0,01 float
RetrTmms Retrip time delay (ms) 0 60000 1 int32
TrTmms Trip time delay (ms) 0 60000 1 int32
LogInBlk Blocking input 1 int32
LogInBFInA Pole A BF start 1 int32
LogInBFInB Pole B BF start 1 int32
LogInBFInC Pole C BF start 1 int32
LogInBFI3P 3 pole BF start 1 int32
MaskEna Enable Events Record NO/YES Boolean
SupEna 52 Supervision NO/YES Boolean
CurLoc Sealed by current 0 1 int32
InRsTmms Time signal relapse (ms) 0 120000 1 int32
CurSpv Supervision by current NO/YES Boolean
IniSpv Supervisión initial13 NO/YES Boolean

14
Available from firmware version 6.0.8.0 and ICDs version 8.1.0.4

Ingeteam Power Technology S.A.


User Manual 163
PROTECTION FUNCTIONS 

Table 101 50BF low load signals

RGBF1 RGBF2 Data Attribute


BF low load status U1 BF low load status U2 StEna stVal
Retrip BF low load - Unid 1 Retrip BF low load - Unid 2 ReOp general
Trip BF low load - Unid 1 Trip BF low load - Unid 2 Op general
Start BF low load - Unid 1 Start BF low load - Unid 2 Str general

Ingeteam Power Technology S.A.


User Manual 164
PROTECTION FUNCTIONS 

3.12 TRIP LOGICS

3.12.1 67NQ Teleprotection Schemes


High voltage line protection requires protection systems which are especially fast, selective and reliable with the aim of not
jeopardising the stability of the electrical system. To fulfil these requirements, it is necessary to use teleprotection systems
associated to the protection equipment installed in each end of the line. The protection device is equipped with a teleprotection
system for completely protecting the line with high-speed protection.

They are based upon the use of teleprotection signals between both end terminals of the line. The effect upon the output relays’
operation is determined according to the signals given by the protection along with the signals given by the other terminal.

From firmware version 6.0.8.0 and ICD version 8.1.0.4, there is a new setting: "TPTx Delay time (ms)".

From firmware version 6.0.8.0 and ICD version 8.1.0.4, in the 67NQ teleprotection schemes, single pole trips are allowed. The
“Single Pole Trip 67NQ” setting must be set to “YES” in the node PROT/ZPMPT (see chapter "Single pole Trip") and the phase
selector must indicate single phase to ground fault (see chapter "Phase selector").

The signals used in the schemes are:

❑ TPTx: teleprotection signal sent by a terminal.


❑ TPRIx: teleprotection signal received by a terminal.
❑ GSL: security channel loss signal (unblocking scheme).
❑ GSLRx: security channel loss signal received (unblocking scheme).

Figure 91 Basic Teleprotection Diagram

3.12.1.1 Introduction
3.12.1.1.1 Fault Detection Units
Teleprotection 67NQ scheme will operate on the instantaneous directional unit No. 1 (forward), 2 (forward) and 3 (backwards).

❑ Zone 1 (forward): Unit 1 with instantaneous, unbalanced and neutral overcurrent (UNPIOC1 and GPIOC1).
❑ Zone 2 (forward): Unit 2 with instantaneous, unbalanced and neutral overcurrent (UNPIOC2 and GPIOC2).
❑ Zone 4 (backwards): Unit 3 with instantaneous, unbalanced and neutral overcurrent (UNPIOC3 and GPIOC3).
Therefore, unit 1 can be assimilated to distance zone 1, unit 2 to zone 2, and unit 3 to zone 4. Unit 3 must be programmed
backwards.

3.12.1.1.2 Scheme Type


The schemes respond to two basic types:

❑ Blocking schemes: The signal received indicates that the fault is outside the protected zone. A relay can trip on an
overreaching zone if, after a definite time, the blocking signal has not been received.

Ingeteam Power Technology S.A.


User Manual 165
PROTECTION FUNCTIONS 

❑ Permissive schemes: The signal received allows an instantaneous trip in the overreaching zone. The additional ECHO,
weak infeed and Current Reversal Blocking schemes can be used.
When selecting a particular scheme, it is useful to bear in mind the following characteristics for each of them: In the case of an
internal fault in the protected line and a communication channel fault in permissive schemes, protection is disabled for tripping,
whilst in blocking schemes, tripping is assured. However, in blocking schemes, if there is an external fault and a communication
channel fault, the device can trip.

If the communication system forms an integral part of the energy transport line, as in the case of carrier waves, it is best to use the
blocking schemes, since internal faults may disturb or attenuate the carrier signal. Likewise, it is best to use blocking schemes in
weak infeed configurations as they are more reliable compared to permissive schemes.

Finally, it should be mentioned that permissive schemes are faster than blocking schemes, given that the latter involve slightly
longer fault clear times, due to the security waiting time for receiving the potential blocking signal.

Several schemes are available:

❑ Step trip (none)


❑ Permissive overreaching (Overreaching POTT)
❑ Permissive underreaching (Underreaching PUTT)
❑ Directional blocking scheme
❑ Directional comparison unblocking scheme
Additionally, the following can be selected together with the schemes:

❑ Direct transfer trip


❑ Echo
❑ Weak infeed
❑ Current Reversal Blocking
3.12.1.1.3 Flexible Units
The signals that activate the sending of the teleprotection between the different overcurrent units can be configured for all the
schemes. Two settings are included - "67NQ Permissive Units" and "67NQ Block Units" which enable both logic inputs to be carried
with the starts of the desired units. In this way, the signals carried to the schemes can be made flexible.

The following logic inputs are configurable using flexible inputs. It is possible to connect any logic input to them:

❑ Faults forward ("67NQ Permissive Units").


❑ Faults backwards ("67NQ Block Units").
Figure 92 Permissive Logic Diagram

Figure 93 Inverse Directional Scheme

Ingeteam Power Technology S.A.


User Manual 166
PROTECTION FUNCTIONS 

3.12.1.1.4 Input / output signals


The following signals are used in the schemes:

❑ TPTx 67NQ: Teleprotection signal sent by a terminal.


❑ TPRIx_67NQ: Teleprotection input received by a terminal.
❑ TPRx_67NQ: Follows the TPRIx input to become activated, but memorises the input during the set time "TPRx Drop out
time (ms)" (RsRTPTmms) to deactivate itself. If this setting is equal to zero, then TPRx coincides with the input TPRIx. TPRx
is used in the teleprotection schemes.
❑ GSLRx_67NQ: Line security signal loss. Indicates that the data channel established between the two teleprotection
devices is inactive.
Figure 94 Teleprotection Reception

Figure 95 TPTx Block Scheme

3.12.1.1.5 Three terminal lines


In the case of three terminal lines, the signals taken into account are the signals received from each terminal.

Figure 96 Teleprotection reception in three terminal lines

Permissive Schemes

Blocking Schemes

Ingeteam Power Technology S.A.


User Manual 167
PROTECTION FUNCTIONS 

3.12.1.1.6 Settings and signals


The settings for selecting the protection schemes are:

❑ Scheme type: Selects the type of scheme. Allows you to select between:
 Step Trip (0)
 Overreaching POTT(1)
 Underreaching PUTT(2)
 Direct.comp. block(3)
 Direct.comp. unbl.(4)
❑ TPRx Drop out time (ms). Memorization time of the teleprotection received signal (TPRx).
❑ Block delay time (ms). Additional waiting time for the block signal.
❑ GSL Minimum time (ms). Minimum security signal loss time to allow trips.
❑ GSL Maximum time (ms). Maximum time during which the trip permission for loss of security signal is enabled.
❑ GSL Drop out time (ms). Drop out time following the recovery of the security channel.
❑ ECHO enabled. Enables the ECHO function.
❑ ECHO pulse time (ms). The duration of the ECHO signal pulse.
❑ ECHO Blocking time (ms). Time after the deactivation of the signal 67NQ_FW during which it is considered as being active.
❑ ECHO delay time (ms). The time during which the conditions for the activation of the ECHO signal must be met.
❑ Current Reversal Blocking. Enables trip blocking for a time after seeing a change in the fault's direction. (Reversal
direction memorisation).
❑ Current rev pickup t. (ms). Reversal direction memorization time.
❑ Weak Infeed Enabled. Enables the weak infeed function.
❑ Weak infeed Threshold (V). Voltage threshold to consider weak infeed.
❑ TPRx_67 line 1. Selects the signal which, when active, indicates that the line 1 teleprotection signal has been received.
❑ TPRx_67 line 2. Selects the signal which, when active, indicates that the line 2 teleprotection signal has been received.
❑ GSLRx_67 line 1. Selects the signal which, when active, indicates that the line 1 security signal loss has been received.
❑ GSLRx_67 line 2. Selects the signal which, when active, indicates that the line 2 security signal loss has been received.
❑ TP Trip Block. Selects the signal which, when active, blocks the teleprotection trip.
❑ TPTx Blocking input. Selects the signal which, when active, indicates the blocking of the TPTX signal transmission.
❑ ECHO Start value. Selects the signal which, when active, indicates ECHO pickup for teleprotection schemes.
❑ Block ECHO (logic input). Selects the signal which, when active, indicates ECHO blocking for teleprotection schemes.
❑ 67NQ Permissive Units. Allows the selection of an alternative pickup signal for unit 2: selects the signal which when
active, indicates the activation of the 67Q pickup signal used in permissive units. If this signal is configured, 67NQ
functions are not taken into account.
❑ 67NQ Block Units. Allows the selection of an alternative pickup signal for unit backwards: selects the signal which when
active, indicates the activation of the 67NQ pickup signal used in blocking units. If this signal is configured, 67NQ
functions are not taken into account.
❑ Weak Infeed Blocking. Selects the signal which, when active, indicates the blocking of the weak infeed scheme.
❑ General trip. Indicates if this unit produces general trip or not. For additional details, see the section corresponding to the
recloser (3.12.6).
❑ Trip permission by recloser. Indicates the trip and block permission in accordance with the recloser status: standby,
blocked, safety time after reclosing, after closing. It is configured bit by bit; for additional details, see section
corresponding to the recloser (3.12.6.3).

Ingeteam Power Technology S.A.


User Manual 168
PROTECTION FUNCTIONS 

❑ Reclose permission15. Indicates whether each trip type can be reclosed or not, in accordance with the recloser's closing
cycle (see reclosure permission mask).
❑ Enable Events record. Allows the generation of protection events associated to the function. If set to “NO”, the function’s
protection events are not generated. If set to “YES”, the function’s specific mask is contemplated.
❑ TPTx Delay time (ms). TPTx signal delay time.

Table 102 Teleprotection scheme settings

Data Setting Minimum Maximum Step Remarks Type


Step Trip (0)
Overreaching POTT (1)
SchTyp Scheme type 0 4 1 Underreaching PUTT (2) enum
Direct. comp. block. (3)
Direct. comp. unbl.(4)
RsRTPTmms TPRx Drop out time (ms) 0 1000 10 int32
BlkTmms Block delay time (ms) 0 1000 10 int32
LoGMinTmms GSL Minimum time (ms) 0 400 10 int32
LoGMaxTmms GSL Maximum time (ms) 0 400 10 int32
LoGRepTmms GSL Drop off time (ms) 0 400 10 int32
EcEna ECHO enabled 0 1 1 NO / YES enum
EcTmms ECHO pulse time (ms) 0 1000 10 int32
EcBlkTmms ECHO Blocking time (ms) 0 1000 10 int32
EcActTmms ECHO delay time (ms) 0 200 10 int32
RvAEna Current Reversal Blocking 0 1 1 NO / YES enum
RvATmms Current rev. pickup T (ms) 0 1000 10 int32
WIEna Weak Infeed Enabled 0 1 1 NO / YES enum
WeiVal Weak Infeed Threshold (V) 0,1 200 0,01 float
LogInRTP1 TPRx _67 line 1 1 int32
LogInRTP2 TPRx _67 line 2 1 int32
LogInPSG1 GSLRx_67 line 1 1 int32
LogInPSG2 GSLRx_67 line 2 1 int32
LogInBl TP Trip Block 1 int32
LogInETPBl TPTx Blocking input 1 int32
LogInECOSt ECHO Start value 1 int32
LogInECOBl Block ECHO 1 int32
LogInAlU 67NQ Permissive Units 1 int32
LogInBlU 67NQ Block Units 1 int32
LogInWIBl Weak Infeed Blocking 1 int32
GenTrip General Trip 0 1 1 NO / YES Boolean
TripPerm Trip permission by recloser 0 254 1 Bit meaning (1) ING
NO (0)
Reclose 1 (1P) (1)
Reclose 1 (3P) (2)
Reclose 1 (1P/3P) (3)
ReclPerm Reclose permission int32
Reclose 2-3-4 (4)
Reclose 1(1P)-2-3-4 (5)
Reclose 1(3P)-2-3-4 (6)
Reclose 1-2-3-4 (7)
MaskEna Enable Events Record 0 1 1 NO / YES Boolean
DlETPTmms TPTx Delay time (ms) 0 1000 10 int32

It has independent settings and outputs:

❑ Node PROT/OCPSCH1
❑ Settings and logical inputs. There are 6 settings tables. For details, see Table 102.
❑ There are no commands.
❑ Outputs: Table 103 shows the function's output data:
 TPRx 67NQ L1. Indicates that the line 1 teleprotection signal has been received.

15
From firmware version 6.0.8.0 and ICD version 8.1.0.4, single pole reclosures are allowed. Until this version, only three
pole reclosure are allowed.

Ingeteam Power Technology S.A.


User Manual 169
PROTECTION FUNCTIONS 

 TPRx 67NQ L2. Indicates that the line 2 teleprotection signal has been received.
 GSR 67NQ L1. Indicates that the line 1 security signal loss has been received.
 GSR 67NQ L2. Indicates that the line 2 security signal loss has been received.
 TPTx 67NQ. Indicates that the teleprotection signal has been activated.
 ECHO 67NQ. Indicates that the ECHO signal has been activated.
 STOP 67NQ. The directional blocking scheme indicates that there is a fault but that it is not backwards. It is used to
indicate that TPTx is not being sent.
 WI 67NQ Trip. Indicates that the weak infeed conditions have been met during the configured time. There are
independent signals for each phase and a general signal.
 Teleprotection 67NQ Trip. Indicates that the teleprotection has tripped.
 Weak infeed phase 67NQ. Indicates that the weak infeed conditions have been met in at least one phase.
 Permissive 67NQ Activation. Indicates that the permissive units have been activated.
 Block Inverted Current 67NQ. Indicates that current inversion block has been activated.
 Memory Inverted Current 67NQ: Current inversion block memorized. Indicates that current inversion block
memorization has been activated.
 85_L1_END_perm_GSL_67NQ. End of permission due to security signal loss in line 1.
 85_L2_END_perm_GSL_67NQ. End of permission due to security signal loss in line 2.
 Teleprotection 67NQ status. Indicates whether or not the teleprotection function is enabled. If the "Scheme type"
setting is selected as "Step Trip", it means that teleprotection is disabled. Any other option means that it is enabled.
 ECHO 67NQ Status. Indicates whether or not the ECHO function is enabled.
 Weak infeed 67NQ status. Indicates whether or not the weak infeed function is enabled.
 Trip 67NQ A. Indicates that the phase A trip is activated, when the "Single Pole Trip 67NQ" setting, located in the
PROT/ZPMPT node, is enabled.
 Trip 67NQ B. Indicates that the phase B trip is activated, when the "Single Pole Trip 67NQ" setting, located in the
PROT/ZPMPT node, is enabled.
 Trip 67NQ C. Indicates that the phase C trip is activated, when the "Single Pole Trip 67NQ" setting, located in the
PROT/ZPMPT node, is enabled.
Table 103 Teleprotection scheme outputs.

Signal Data Attribute


TPRx 67NQ L1 ProRx stVal
TPRx 67NQ L2 ProRx2 stVal
SGR 67NQ L1 GSL1Rx stVal
SGR 67NQ L2 GSL2Rx stVal
TPTx 67NQ ProTx stVal
ECHO 67NQ Echo stVal
STOP 67NQ STOPTx stVal
27WI 67NQ Phase A WeakInF phsA
27WI 67NQ Phase B WeakInF phsB
27WI 67NQ Phase C WeakInF phsC
27WI 67NQ Trip WeakInF stVal
Teleprotection 67NQ Trip Op stVal
Weak Infeed Phase 67NQ StrWeakInF stVal
Permissive 67NQ Activation OpPerUnit stVal
Block Inverted Current 67NQ RvABlk stVal
Memory Inverted Current 67NQ MBlkInvDir stVal
85_L1_END_perm_GSL_67NQ GSL1End stVal
85_L2_END_perm_GSL_67NQ GSL2End stVal
Teleprotection 67NQ status TpSt stVal
ECHO 67NQ Status EchoSt stVal
Weak infeed 67NQ status WeiOpSt stVal
Trip 67NQ A OpNQA stVal
Trip 67NQ B OpNQB stVal
Trip 67NQ C OpNQC stVal

Ingeteam Power Technology S.A.


User Manual 170
PROTECTION FUNCTIONS 

3.12.1.2 Permissive underreaching


It causes an instantaneous teleprotection trip upon the reception of the teleprotection signal (TPRIx), together with the pick up
of unit 2, as long as the reverse memorization of unit 3 is not activated (Memory Inverted Current). It is used to accelerate the
trips at one end with the other indicates this.

This scheme is based on the idea that at least one of the protection devices at one end of the line will see the fault in zone 1. If
a terminal sees the fault in zone 1 and the other one sees it in zone 2, the fault can be considered as being inside the line
between both devices, in the section of the line close to the terminal which sees it in zone 1.

The terminal that sees the fault in unit 1, besides setting off an instantaneous trip, sends the trip permission signal (TPTx) to the
other end while unit 1 is activated. The terminal which detects the fault in unit 2 generates an instantaneous trip with the
reception of the teleprotection signal (TPRIx) together with the activation of unit 2 as long as unit 3 is not activated.

Figure 97 Permissive Underreaching Logic Diagram

Figure 97 and Figure 92 show the permissive underreaching protection scheme. This figure is used to analyse how the
protection devices will act in the event of faults in F1, F2 and F3:

Figure 98 Fault examples

❑ Fault F1: Protection A sees the fault in unit 1, causing an instantaneous trip and sending a permission signal to protection
B. Protection B sees the fault in unit 2 and will set off a high-speed trip when it sees the fault in unit 2 and will receive
protection A's permission command.
❑ Fault F2: Both protection devices see the fault in unit 1, causing a high-speed trip. Furthermore, redundant commands
are given by the communication channels.
❑ Fault F3: None of the protection devices will trip instantaneously. Protection A sees the fault in unit 2 but B does not see
the fault in the line to protect, not sending the permission signal to protection A. Hence, A's action in unit 2 will take place
in unit 2 time.
Inverse direction block: signal "Memory Inverted Current" can be eliminated from the logic by disabling this function. In this
case, "Memory Inverted Current" would be set permanently to 0.

Ingeteam Power Technology S.A.


User Manual 171
PROTECTION FUNCTIONS 

In lines with more than two terminals, to apply this scheme, checks must be made to ensure that in the event on any fault in
any point in the line, at least the protection of one of the ends is detect in zone 1.

The scheme is applied to three-terminal lines by carrying an OR signal to the three of them from the TPRx of the other two ends
(See Figure 96).

3.12.1.3 Permissive overreaching


It produces an instantaneous teleprotection trip upon the reception of the teleprotection signal (TPRx), together with the pick
up of unit 2, as long as the memorized reverse zone is not activated (Memory Inverted Current).

In this protection scheme, a fault is considered internal to the line if both terminals see the fault in unit 2. An instantaneous trip
is caused if the teleprotection signal is received, together with activation of unit 2 as long as the memorised unit 3 is not
activated.

The teleprotection signal is sent upon the activation of the unit 2, without the detection of a reverse fault (Memory Inverted
Current).

Figure 99 Permissive Overreaching Logic Diagram

Figure 99 and Figure 92 show the permissive overreaching protection scheme. This figure is used to analyse how the protection
devices will act in the event of faults in F1, F2 and F3:

❑ Fault F1: Protection A sees the fault in zone 1(PIOC1 or GPIOC1), causing an instantaneous trip and sending a permission
signal to protection B, given that it sees the fault in zone 2 (PIOC2 or GPIOC2) (zone 2 includes zone 1). Protection B trips
instantaneously when it sees the fault in zone 2 and receives a permission order from protection A. Protection B will also
send a permission signal to protection A but it has already instantaneously tripped in zone 1.
❑ Fault F2: Both protection devices see the fault in zone 1, causing a high-speed trip. Furthermore, redundant commands
are given by the communication channels.
❑ Fault F3: Protection A sees the fault in zone 2 and sends the permission signal to B, which sees the fault backwards. When
A does not receive the permission signal from B, zone 2's action will take place in zone 2 time. Protection B receives the
permission signal from A, but when it sees the fault backwards, it will not trip.
Any fault in unit 3 (PIOC3 or GPIOC3) it will normally be eliminated in unit 3 time.

3.12.1.4 Directional unblocking


The directional unblocking scheme is used in overreaching schemes. Together with the TPRx signal, the channel loss signal
(GSLRx) is received.

In usual conditions, the signal GSLRx has the same value as the TPRx signal. Thus, if the TPRx signal is activated, GSLRx is also
activated. If both signals are deactivated there is not fault and the guard channel signal is not lost.

If the overreaching unit 2 (PIOC2 or GPIOC2) acts, the security signal works as an unblocking signal.

An instantaneous teleprotection trip will be issued by the zone 2 activation:

❑ If the unblock signals TPRx and GSLRx are received or


❑ When the device only receives the GSLRx signal, the timers start. When the “GSL minimum time (ms)” (LoGMinTmms)
delay is over without the reception of the TPRx signal, a trip is issued. Once the “GSL maximum time (ms)” has elapsed, no

Ingeteam Power Technology S.A.


User Manual 172
PROTECTION FUNCTIONS 

trip is enabled. Once the loss off channel signal is deactivated again a third timer starts. When the “GSL drop out time
(ms)” delay is over the previous logic is newly applied.

Figure 100 Treatment of Line 1 channel loss signals

Figure 101 Treatment of Line 2 channel loss signals

Figure 102 TPTx and Trip Signal Scheme

Ingeteam Power Technology S.A.


User Manual 173
PROTECTION FUNCTIONS 

The figures show the directional unblocking protection scheme. This figure is used to analyse how the protection devices will
act in the event of faults in F1, F2 and F3:

Figure 103 Directional Unblocking Protection

N.B.: The signals received in GSLRx and TPRx directional blocking can only be received with values (active, active), (active,
inactive) or (inactive, inactive). They can never be (inactive, active) because the transmitter/receiver that sends the signals,
when there is communication and receives TPR gives the signals GSR and TPR and when there is no communication, gives GSR
but not TPR.

The GSLRx signal is active in 2 cases:

❑ When the security signal is lost or


❑ When TPRx is received. In this case, it is converted into a non-blocking signal. It behaves in the same way as in the case of
overreaching.
The GSLRx signal is deactivated when there is communication and there is no TPRx.

Table 104 GSLRx and TPRIx Values in Directional Unblocking

GSLRx TPRIx TRIP Remark


0 0 0 Guard channel is not lost and there is not fault.
1 1 1 Guard channel is not lost and there is fault. GSLRx signal becomes a non-blocking signal
(GSLRx = 1).
1 0 Time Guard channel is not lost and we do not know if there is fault.
window When signal loss of guard channel is activated it opens a time window during which it can
produce GSLRx shot if the signal remains active for the programmed time (TPSG) without
reception of TPRIx
0 1 It is not possible because if we have TPRIx, it is because there is communication

Analysis is made of how the protection devices will act in the event of faults in F1, F2 and F3:

❑ Fault F1: Protection A sees the fault in zone 1, causing an instantaneous trip and changing the security signal to an
unblocking signal given that it sees the fault in zone 2 (zone 2 includes zone 1). Protection B sees the fault in zone 2 and
when it receives the unblocking signal from A, it will speed up the trip. If the security channel is lost, when protection B's
zone 2 is activated, it will speed up its trip if it receives the channel loss signal for the time programmed for "security
signal loss".
❑ Fault F2: Both protection devices see the fault in zone 1, causing a high-speed trip.
❑ Fault F3: Protection A sees the fault in zone 2 but does not speed up its trip given that protection B sees the fault in zone
4 and therefore will not change the security signal for an unblocking signal.

Ingeteam Power Technology S.A.


User Manual 174
PROTECTION FUNCTIONS 

3.12.1.5 Directional blocking


The TPTx blocking signal is sent if a backwards fault is detected (Memory Inverted Current).

A stop channel signal (STOP 67NQ) is activated if a forward fault is detected (overcurrent units 1 and 2) and it is maintained
during “Block delay time (ms)” (BlkTmms), without the detection of a fault in the unit 3 Memory Inverted Current).

If the channel interruption signal (STOP 67NQ) is activated and the signal TPRx is not received, the signal "Teleprotection 67NQ
Trip" is activated.

If the input “TPTx Blocking input” is activated the signal TPRx is not sent. Furthermore, if the “TP Trip Block” input is activated,
the signal "Teleprotection 67NQ Trip" is blocked.

Figure 104 Directional Blocking Scheme

The blocking time is an additional delay time to give time for the blocking signal to be received and is programmable by the
user. The transmission time must be as low as possible with the aim of reducing this delay to a minimum.

The Figure 104, Figure 92 and Figure 93 show the directional blocking protection scheme. This figure is used to analyse how the
protection devices will act in the event of faults in F1, F2 and F3:

Figure 105 Directional Blocking Protection

❑ Fault F1: Protection A detects the fault in zone 1 causing an instantaneous trip. Protection B detects the fault in zone 2
and once the blocking time has elapsed, it will trip given that a blocking command is not received from A since A does not
detect the fault in zone 4.
❑ Fault F2: Both protection devices see the fault in zone 1, causing a high-speed trip.
❑ Fault F3: Protection A detects the fault in zone 2 but does not cause a fast trip given that protection B sees the fault in
zone 4 and will therefore send a blocking signal to A.
Care must be taken with the coordination of the blocking unit backwards (for example, B's zone 4) of each end with the
overreaching unit of the other end (A's zone 2), these being set so that the reach of the reverse unit is always greater than the
overreach's.

Ingeteam Power Technology S.A.


User Manual 175
PROTECTION FUNCTIONS 

Figure 106 Coordinating the Reverse Blocking Unit.

This scheme has the advantage of not being sensitive to noise in the communication channel and has the disadvantage of
possibly causing untimely trips if the communication channel is lost.

The blocking scheme is usually used in long lines when the teleprotection signal is transmitted via the protected line by the
carrier wave and the diminishing of the signal transmitted at the point of fault can be so severe that reception at the other end
of the line cannot always be ensured.

3.12.1.6 ECHO
It is used together with permissive overreaching schemes by acting on the teleprotection (TPTx) signal.

The ECHO 67NQ signal only provides a programmable pulse. The ECHO function sends the teleprotection (TPTx) signal with any
of the following conditions:

❑ The ones corresponding to the permissive overreaching scheme.


❑ If TPRIx is received and no forward or reverse faults are detected.
 programmable for a minimum time (setting " ECHO delay time(ms)"), or
 the breaker is open (in this situation, it does not wait for the programmed time to elapse).
It is used together with permissive overreaching schemes in cases where one end of the line is open (Figure 108 end B) or is a
weak end (Figure 109 end B). In the event of a fault on the line near the weakly-fed or open end, the distance unit of this end of
the line does not detect the fault. Hence, the trip will not be issued, nor will the permission signal be sent to the other end of
the line. Hence, since the permission signal will not be received, the strongly-fed end of the line will not speed up its trip.

To speed up the trip at the strongly-fed end in the event of a fault at the opposite end, the Echo function returns the TPRIx
signal received to the remote terminal if it does not detect a fault forward or backwards, or if the circuit breaker is open.

The resending of the TPRIx received (ECHO 67NQ) will be instantaneous if the circuit breaker is open and will suffer a delay
(EcActTmms) if there is a weak power supply. This delay makes it possible to cover situations in which there is a higher fault
detection time, or it start slightly later due to an unfavourable distribution of the fault current. This delay is usually set to
approximately 40ms.

“ECHO 67NQ” is a pulse that during “ECHO pulse time (ms)” (EcTmms), which is normally set to approximately 50 ms, thus
assuring that the signal received is even recognised with different action times of the protection equipment at ends of the lines
and with different response times of the transmission equipment.

Ingeteam Power Technology S.A.


User Manual 176
PROTECTION FUNCTIONS 

Figure 107 Echo Scheme and Weak Infeed

Figure 108 Echo logic protection with breaker open in B

Ingeteam Power Technology S.A.


User Manual 177
PROTECTION FUNCTIONS 

Figure 108 shows the ECHO Logic Sample, with the circuit breaker in B Open This scheme will be used to analyse how the
protection devices act in the event of faults F1 and F2 with the basic permissive overreaching scheme.

❑ Fault F1: Protection A detects the fault in its zone 1 and hence instantaneously trips and sends a permission signal to B.
End B is open so the fault is cleared.
❑ Fault F2: Protection A detects the fault in zone 2 and sends a permission signal to B. When the protection device in B
detects that the circuit breaker is open, it will resend the permission signal to protection A without delay. When
protection A detects the fault in zone 2 and having received the permission signal, it will speed up its trip.

Figure 109 Echo and weak infeed example

Figure 109 shows the ECHO logic, and Weak infeed. This scheme will be used to analyse how the protection devices act in the
event of faults F1 and F2 with the basic permissive overreaching scheme.

❑ Fault F1: Protection A detects the fault in unit 1 and will hence trip instantaneously and send a permission signal to B. The
protection in B, being weakly fed, will not detect the fault, but as it receives the permission signal, it will send back to A
with the programmed delay, but A will be open. The circuit breaker at end B will remain closed.
❑ Fault F2: Protection A detects the fault in unit 2 and sends a permission signal to B. The protection in B, being weakly fed,
will not detect the fault, but as it receives the permission signal, it will send back to A with the programmed delay. When
protection A sees the fault in unit 2 and has received the permission signal, it will speed up its trip. The circuit breaker at
end B will remain closed.

3.12.1.7 Weak infeed (27WI)


This is a complement to ECHO 67NQ, where if ECHO 67NQ conditions are met, with the circuit breaker closed and undervoltage
in at least one of the phases, a trip is produced.

The undervoltage unit associated to the weak infeed function has its own settings and is not dependent on the undervoltage
units.

The thresholds are 0.1V to 200V.

If an unblocking scheme is used, the TPRIx signal is replaced by TPRIx & GSL.

If one end of the line is weakly fed (Figure 109 end B) with the echo logic, as seen in the previous section, the trip at the
strongly fed end is accelerated. However, the weakly fed end remains closed. This logic allows the opening of this end of the
line.

To detect the fault at the weak end, the following conditions must be fulfilled:

❑ TPRIx signal received (it will be sent to the strongly-fed end, as described in the ECHO function).
❑ The circuit breaker is closed.
❑ Undervoltage is detected in one of the phases (as a consequence of the fault). The settings recommended are 70%Vn for
the voltage.

Ingeteam Power Technology S.A.


User Manual 178
PROTECTION FUNCTIONS 

Figure 110 Protection in the weak infeed Logic, with End B Weakly Fed

Figure 110 shows the weak infeed logic, with end B weakly fed. This scheme will be used to analyse how the protection devices
act in the event of F1 faults with the basic permissive overreaching scheme.

❑ Fault F1: Protection A detects the fault in unit 2 and sends a permission signal to B. The protection in B, being weakly fed,
will not detect the fault and when it receives the permission signal, it will send it to A after the set time. When protection
A sees the fault in unit 2 and has received the permission signal, it will speed up its trip. When protection B fulfills the
ECHO conditions and detects undervoltage (due to the existence of the fault), it will give the trip command.

3.12.1.8 Inverse directional block


It delays the teleprotection trip for a number of cycles in order to allow the remote terminal time to clear the permission signal
(TPTx) following a change in the flow direction due to the opening of the breaker.

It is used in double circuit lines to prevent trips due to the change in the current flow which is caused when the circuit breaker
is opened at one end of the faulty line when this fault is cleared. The reversal of the current implies the reversal of the
protection device's directional elements, as well as the increase in the apparent distance to the fault. The time between the
repositioning of the distance elements and the functioning of the unit may give rise to a trip in the healthy parallel line.

When the scheme is a blocking one, it keeps the blocking signal for a set time "Block delay time (ms)", blocking the trip for a
time after detecting a change in the fault's direction. When the scheme is permissive, it blocks the trip and the emission of the
permission for a set time after changing the direction in which it detects the fault (backwards to forward).

The overcurrent unit 2 signal is used with a memorization time "Current Reversal Blocking(ms)" (RvATmms), which enables the
"Memory Inverted Current" signal to be used in the rest of the schemes (see Figure 93).

The following figures show the change in the current flow when the fault occurs and when circuit breaker K is opened to clear
this fault:

Inverse direction blocking with permissive schemes:

❑ When faults F occurs as can be seen in Figure 111.1, protection K will detect the fault in zone 1, J will either detect it in 1
or 2 and H backwards. In this situation, K instantaneously opens the circuit breaker and sends the permission signal to J
and likewise, G sends the permission signal to H.
❑ When K opens, the current's flow is inverted as can be seen in Figure 111.2. In this new situation, G will detect the fault
backwards and H will detect it in zone 2. These conversions are not simultaneous or instantaneous. Hence, H could trip
before G removes the permission signal. To prevent this trip, the teleprotection trip is delayed for a number of cycles, to
give the remote terminal time to remove the permission signal.

Ingeteam Power Technology S.A.


User Manual 179
PROTECTION FUNCTIONS 

Figure 111 Change in the Current Flow When the Fault Occurs in a Double Circuit Line

Inverse direction blocking with blocking scheme:

❑ When the fault occurs as can be seen in Figure 110, protection K will detect the fault in zone 1, J will either detect it in 1
or 2 and H backwards. When H detects the fault in its zone 4, it sends a blocking signal to G (or it does not send the TPRIx
signal, which is the same), preventing tripping due to acceleration in zone 2.
❑ When K opens, the current's flow is inverted as can be seen in Figure 111.2. In this new situation, G will detect the fault
backwards and H will detect it in zone 2. H would trip before receiving the blocking signal from G. To prevent this, H will
continue to detect the fault backwards, allowing time to receive the blocking signal.
It is recommended that the additional blocking time be set as follows:

Additional blocking time = operating time of the circuit breaker at the other end of the line (typically 3 cycles) + the reset time
of the communication channel (1 cycle) + the reset time of zone 2 of the relay at the other end of the line (1 cycle) = 5 cycles.

3.12.2 Z Teleprotection Schemes


High voltage line protection requires protection systems which are especially fast, selective and reliable with the aim of not
jeopardising the stability of the electrical system. To fulfil these requirements, it is necessary to use teleprotection systems
associated to the protection equipment installed in each end of the line. The protection device is equipped with a teleprotection
system for completely protecting the line with high-speed protection.

They are based upon the use of teleprotection signals between both end terminals of the line. The effect upon the output relays’
operation is determined according to the signals given by the protection along with the signals given by the other terminal.

From firmware version 6.0.8.0 and ICD version 8.1.0.4, the option of the phase-segregated teleprotection is included. When the
phase-segregated teleprotection is chosen, the teleprotection schemes are performed per phase. Moreover, the setting "TPTx
delay time (ms)" is included.

Ingeteam Power Technology S.A.


User Manual 180
PROTECTION FUNCTIONS 

❑ TPTx: teleprotection signal sent by a terminal.


❑ TPRIx: teleprotection signal received by a terminal.
❑ GSL: security channel loss signal (unblocking scheme).
❑ GSLRx: security channel loss signal received (unblocking scheme).

3.12.2.1 Introduction
3.12.2.1.1 Fault Detection Units
Teleprotection Z scheme will operate on the distance unit 21, Zone 1 and Zone 2 (forward), and zone 4 (backwards). Mho and quad
are both affected.

❑ Zone 1 (forward): Unit 21 zone 1 (PDIS1).


❑ Zone 2 (forward): Unit 21 zone 2 (PDIS2).
❑ Zone 4 (backwards): Unit 21 zone 4 (PDIS4).

3.12.2.1.2 Scheme Type


The schemes respond to two basic types:

❑ Blocking schemes: The signal received indicates that the fault is outside the protected zone. A relay can trip on an
overreaching zone if, after a definite time, the blocking signal has not been received.
❑ Permissive schemes: The signal received allows an instantaneous trip in the overreaching zone. The additional ECHO,
weak infeed and Current Reversal Blocking schemes can be used.
When selecting a particular scheme, it is useful to bear in mind the following characteristics for each of them: In the case of an
internal fault in the protected line and a communication channel fault in permissive schemes, protection is disabled for tripping,
whilst in blocking schemes, tripping is assured. However, in blocking schemes, if there is an external fault and a communication
channel fault, the device can trip.

If the communication system forms an integral part of the energy transport line, as in the case of carrier waves, it is best to use the
Current Reversal Blocking scheme, since internal faults may disturb or attenuate the carrier signal. Likewise, it is best to use
blocking schemes in weak infeed configurations as they are more reliable compared to permissive schemes.

Finally, it should be mentioned that permissive schemes are faster than blocking schemes, given that the latter involve slightly
longer fault clear times, due to the security waiting time for receiving the potential blocking signal.

Several schemes are available:

❑ Step trip (none)


❑ Permissive overreaching (Overreaching POTT)
❑ Permissive underreaching (Underreaching PUTT)
❑ Directional blocking scheme
❑ Directional comparison unblocking scheme
Additionally, the following can be selected together with the schemes:

❑ Direct transfer trip


❑ Echo
❑ Weak infeed
❑ Current Reversal Blocking
3.12.2.1.3 Flexible Units
In the case of the non-phase-segregated teleprotection, the signals that activate the sending of the teleprotection between the
different distance units can be configured for all the schemes. Two settings are included "Z Permissive Units (1 bit)" and "Z Block

Ingeteam Power Technology S.A.


User Manual 181
PROTECTION FUNCTIONS 

Units (1 bit)" which enable both logic inputs to be carried with the pickups of the desired units. In this way, the signals carried to
the schemes can be made flexible.

The following logic inputs are configurable using flexible inputs. It is possible to connect any logic input to them:

❑ Faults forward ("Z Permissive Units (1 bit)").


❑ Faults backward ("Z Block Units (1 bit)").
Figure 112 and Figure 113 show the logic diagrams with the configurable logic inputs.

Figure 112 Permissive Logic Diagram

Figure 113 Inverse Directional Blocking Scheme

In the case of phase-segregated teleprotection, the permissive and block units have several selection options. One signal per phase
is activated.

❑ Z Permissive Units (3 bits).


 Predefined. Correspond to Zone 2
 Zone 3.
 Zone 5
❑ Z Block Units (3 bits).
 Predefined. Correspond to Zone 4
 Zona 3.
 Zona 5

Ingeteam Power Technology S.A.


User Manual 182
PROTECTION FUNCTIONS 

Figure 114 Permissive logic Diagram phase A, phase-segregated teleprotection

Figure 115 Inverse Directional Blocking Scheme, phase A, phase-segregated teleprotection

3.12.2.1.4 Input / output signals


The following signals are used in the schemes:

❑ TPTx_21. Teleprotection signal sent by a terminal. In the case of phase-segregated teleprotection there is one signal per
phase.
❑ TPRIx_21. Teleprotection input received by a terminal. In the case of phase-segregated teleprotection there is one signal
per phase.
❑ TPRx_21. Follows the TPRIx_21 input to become activated, but memorises the input during the set time “TPRx Drop out
time (ms)” (RsRTPTmms) to deactivate itself. If this setting is equal to zero, then TPRx21 coincides with the input TPRIx
21. TPRx is used in the teleprotection schemes. In the case of phase-segregated teleprotection there is one signal per
phase.

Ingeteam Power Technology S.A.


User Manual 183
PROTECTION FUNCTIONS 

❑ GSLRx_21. Line security signal loss. Indicates that the data channel established between the two teleprotection devices is
inactive.
Figure 116 Teleprotection Reception

Figure 117 TPTx Block Scheme

Figure 118 Phase A phase-segregated teleprotection reception

Figure 119 Phase A phase-segregated teleprotection, TPTx Block Scheme

3.12.2.1.5 Three terminal lines


In the case of three terminal lines, the signals taken into account are the signals received from each terminal.

Ingeteam Power Technology S.A.


User Manual 184
PROTECTION FUNCTIONS 

Figure 120 Teleprotection reception in three terminal lines

Permissive Schemes

Blocking Schemes

In the case of phase-segregated teleprotection there is one signal per phase.

Figure 121 Teleprotection reception in 3 terminal lines, phase A, phase-segregated teleprotection.

Permissive Schemes, phase A

Blocking Schemes, phase A

3.12.2.1.6 Settings and signals


The settings for selecting the protection schemes are:

❑ Scheme type: Selects the type of scheme. Allows you to select between:
 Step Trip (0)
 Overreaching POTT(1)
 Underreaching PUTT(2)
 Direct.comp. block(3)
 Direct.comp. unbl.(4)
❑ TPRx Drop out time (ms). Memorization time of the teleprotection received signal (TPRx).
❑ Block delay time (ms). Additional waiting time for the block signal.
❑ GSL Minimum time (ms). Minimum security signal loss time to allow trips.
❑ GSL Maximum time (ms). Maximum time during which the trip permission for loss of security signal is enabled.
❑ GSL Drop out time (ms). Drop out time following the recovery of the security channel.
❑ ECHO enabled. Enables the ECHO function.

Ingeteam Power Technology S.A.


User Manual 185
PROTECTION FUNCTIONS 

❑ ECHO pulse time (ms). The duration of the ECHO signal pulse.
❑ ECHO Blocking time (ms). Time after the deactivation of the signal Z_FW (Z Permissive Units) during which it is considered
as being active.
❑ ECHO delay time (ms). The time during which the conditions for the activation of the ECHO signal must be met.
❑ Current Reversal Blocking. Enables trip blocking for a time after seeing a change in the fault's direction. (Reversal
direction memorisation).
❑ Current rev pickup t. (ms). Reversal direction memorization time.
❑ Weak Infeed Enabled. Enables the weak infeed function.
❑ Weak infeed Threshold (V). Voltage threshold to consider weak infeed.
❑ TPRx_21 line 1. Selects the signal which, when active, indicates that the line 1 teleprotection signal has been received.
❑ TPRx_21 line 2. Selects the signal which, when active, indicates that the line 2 teleprotection signal has been received.
❑ GSLRx_21 line 1. Selects the signal which, when active, indicates that the line 1 security signal loss has been received.
❑ GSLRx_21 line 2. Selects the signal which, when active, indicates that the line 2 security signal loss has been received.
❑ TP Trip Block. Selects the signal which, when active, blocks the teleprotection trip.
❑ TPTx Blocking input. Selects the signal which, when active, indicates the blocking of the TPTX signal transmission.
Figure 122 TPTx Block Scheme

❑ ECHO Start value. Selects the signal which, when active, indicates ECHO start for teleprotection schemes.
❑ Block ECHO (logic input). Selects the signal which, when active, indicates ECHO blocking for teleprotection schemes.
❑ Z Permissive Units (1 bit). Allows the selection of an alternative pickup signal for zone 2: selects the signal which when
active, indicates the activation of the Z pickup signal used in permissive units. If this signal is configured, Z functions are
not taken into account. Only in the non-phase-segregated protection.
❑ Z Block Units (1 bit). Allows the selection of an alternative pickup signal for backwards zone: selects the signal which
when active, indicates the activation of the Z pickup signal used in blocking units. If this signal is configured, Z functions
are not taken into account. Only in the non-phase-segregated protection.
❑ Weak Infeed Blocking. Selects the signal which, when active, indicates the blocking of the weak infeed scheme.
❑ Enable Events record. Allows the generation of protection events associated to the function. If set to “NO”, the function’s
protection events are not generated. If set to “YES”, the function’s specific mask is contemplated.
❑ Reclose permission. Indicates whether each trip type can be reclosed or not, in accordance with the recloser's closing
cycle (see reclosure permission mask).
❑ TPTx Delay time (ms). TPTx signal delay time.
❑ Phase-segregated teleprotection. Enables the phase-segregated teleprotection.
❑ TPRx_21 line 1A. Selects the signal which, when active, indicates that the line 1's phase A teleprotection signal has been
received. Only in phase-segregated teleprotection.
❑ TPRx_21 line 1B. Selects the signal which, when active, indicates that the line 1's phase B teleprotection signal has been
received. Only in phase-segregated teleprotection.
❑ TPRx_21 line 1C. Selects the signal which, when active, indicates that the line 1's phase C teleprotection signal has been
received. Only in phase-segregated teleprotection.
❑ TPRx_21 line 2A. Selects the signal which, when active, indicates that the line 2's phase A teleprotection signal has been
received. Only in phase-segregated teleprotection.

Ingeteam Power Technology S.A.


User Manual 186
PROTECTION FUNCTIONS 

❑ TPRx_21 line 2B. Selects the signal which, when active, indicates that the line 2's phase B teleprotection signal has been
received. Only in phase-segregated teleprotection.
❑ TPRx_21 line 2C. Selects the signal which, when active, indicates that the line 2's phase C teleprotection signal has been
received. Only in phase-segregated teleprotection.
❑ Z Permissive Units (3 bits). It allows to select an alternative zone to zone 2. It selects the zone, whose start, causes the
activation of the permissive units. It is only used when the teleprotection is phase-segregated.
 Predefined (0). It correspond to Zone 2.
 Zone 3 (1)
 Zone 5 (2)
❑ Z Block Units (3 bits). It allows to select an alternative zone to zone 4. It selects the zone, whose start, causes the
activation of the block units. It is only used when the teleprotection is phase-segregated.
 Predefined (0). It correspond to Zone 4
 Zone 3 (1)
 Zone 5 (2)

Ingeteam Power Technology S.A.


User Manual 187
PROTECTION FUNCTIONS 

Table 105 Teleprotection scheme settings

Data Setting Min Max Step Remarks Type


Step Trip (0)
Overreaching POTT (1)
SchTyp Scheme type 0 4 1 Underreaching PUTT (2) enum
Direct. comp. block. (3)
Direct. comp. unbl.(4)
RsRTPTmms TPRx Drop out time (ms) 0 4 1 int32
BlkTmms Block delay time (ms) 0 1000 10 int32
LoGMinTmms GSL Minimum time (ms) 0 1000 10 int32
LoGMaxTmms GSL Maximum time (ms) 0 400 10 int32
LoGRepTmms GSL Drop out time (ms) 0 400 10 int32
EcEna ECHO enabled 0 400 10 NO / YES enum
EcTmms ECHO pulse time (ms) 0 1 1 int32
EcBlkTmms ECHO Blocking time (ms) 0 10000 10 int32
EcActTmms ECHO delay time (ms) 0 1000 10 int32
RvAEna Current Reversal Blocking 0 200 10 NO / YES enum
RvATmms Current rev pickup t. (ms) 0 1 1 int32
WIEna Weak Infeed Enabled 0 10000 10 NO / YES enum
WeiVal Weak Infeed Threshold (V) 0 1 1 float
LogInRTP1 TPRx _21 line 1 0,1 200 0,01 int32
LogInRTP2 TPRx _21 line 2 int32
LogInPSG1 GSLRx_21 line 1 int32
LogInPSG2 GSLRx_21 line 2 int32
LogInBl TP Trip Block int32
LogInETPBl TPTx Blocking input int32
LogInECOSt ECHO Start value int32
LogInECOBl Block ECHO int32
LogInAlU Z Permissive Units int32
LogInBlU Z Block Units int32
LogInWIBl Weak Infeed Blocking int32
MaskEna Enable Events Record NO / YES Boolean
NO (0)
Reclose 1 (1P) (1)
Reclose 1 (3P) (2
Reclose 1 (1P/3P) (3)
ReclPerm Reclose permission 0 1 1 enum
Reclose 2-3-4 (4)
Reclose1(1P)-2-3-4 (5)
Reclose1(3P)-2-3-4 (6)
Reclose 1-2-3-4 (7)
DlETPTmms TPTx Delay time (ms) 0 1000 10 int32
SegTpc Segregated teleprotection NO – 1 bit (0) / YES - 3 bits (1) enum
LogInRTP1A TPRx_21 line 1A int32
LogInRTP1B TPRx_21 line 1B int32
LogInRTP1C TPRx_21 line 1C int32
LogInRTP2A TPRx_21 line 2A int32
LogInRTP2B TPRx_21 line 2B int32
LogInRTP2C TPRx_21 line 2C int32
Predefined (0)
Zone 3 (1) enum
PmsAIU Z Permissive Units (3 bits) Zone 5 (2)
Predefined (0)
Zone 3 (1) enum
BlkBIU Z Block Units (3 bits) Zone 5 (2)

It has independent settings and outputs:

❑ Node PROT/ZPSCH1
❑ Settings and logical inputs. There are 6 settings tables. For details, see Table 105.
❑ There are no commands
❑ Outputs: Table 106 shows the function's output data:
 TPRx Z L1. Indicates that the line 1 teleprotection signal has been received.

Ingeteam Power Technology S.A.


User Manual 188
PROTECTION FUNCTIONS 

 TPRx Z L2. Indicates that the line 2 teleprotection signal has been received.
 GSR Z L1. Indicates that the line 1 security signal loss has been received.
 GSR Z L2. Indicates that the line 2 security signal loss has been received.
 TPTx Z. Indicates that the teleprotection signal has been activated.
 ECHO Z. Indicates that the ECHO signal has been activated.
 STOP Z. The directional blocking scheme indicates that there is a fault but that it is not backwards. It is used to indicate
that TPTx is not being sent.
 27WI Z Trip Weak infeed trip. Indicates that the weak infeed conditions have been met during the configured time.
 27WI Z Phase X. Weak infeed trip. Indicates that the weak infeed conditions have been met during the configured
time. There are independent signals for each phase.
 Teleprotection Z Trip. Indicates that the teleprotection has tripped.
 Weak Infeed Phase Z. Indicates that the weak infeed conditions have been met in at least one phase.
 Permissive Z Activation. Indicates that the permissive units have been activated.
 Block Inverted Current Z. Indicates that current inversion block has been activated.
 Memory Inverted Current Z: Current inversion block memorized. Indicates that current inversion block memorization
has been activated.
 85_L1_END_perm_GSL_Z. End of permission due to security signal loss in line 1.
 85_L2_END_perm_GSL_Z. End of permission due to security signal loss in line 2.
 Teleprotection Z status. Indicates whether or not the teleprotection function is enabled. If the "Scheme type" setting is
selected as "Step Trip", it means that teleprotection is disabled. Any other option means that it is enabled.
 ECHO Z Status. Indicates whether or not the ECHO Z function is enabled.
 Weak infeed Z status. Indicates whether or not the weak infeed function is enabled.
 TPRx Z L1A. Indicates that the line 1 phase A teleprotection signal has been received.
 TPRx Z L1B. Indicates that the line 1 phase B teleprotection signal has been received.
 TPRx Z L1C. Indicates that the line 1 phase C teleprotection signal has been received.
 TPRx Z L2A. Indicates that the line 2 phase A teleprotection signal has been received.
 TPRx Z L2B. Indicates that the line 2 phase B teleprotection signal has been received.
 TPRx Z L2C. Indicates that the line 2 phase C teleprotection signal has been received.
 TPTx Z_A. Indicates that the teleprotection phase A signal has been activated.
 TPTx Z_B. Indicates that the teleprotection phase B signal has been activated.
 TPTx Z_C. Indicates that the teleprotection phase C signal has been activated.
 ECHO Z_A. Indicates that the ECHO phase A signal has been activated.
 ECHO Z_B. Indicates that the ECHO phase A signal has been activated.
 ECHO Z_C. Indicates that the ECHO phase A signal has been activated.
 STOP Z_A. The directional blocking scheme indicates that there is a fault but that it is not backwards. It is used to
indicate that TPTx phase A is not being sent.
 STOP Z_B. The directional blocking scheme indicates that there is a fault but that it is not backwards. It is used to
indicate that TPTx phase B is not being sent.
 STOP Z_C. The directional blocking scheme indicates that there is a fault but that it is not backwards. It is used to
indicate that TPTx phase C is not being sent.
 Teleprotección Trip Z_A. Indicates that a teleprotection phase A has tripped.
 Teleprotección Trip Z_B. Indicates that a teleprotection phase B has tripped.
 Teleprotección Trip Z_C. Indicates that a teleprotection phase C has tripped.
 Permissive U activation A. Indicates that the permissive units for phase A have been activated.
 Permissive U activation B. Indicates that the permissive units for phase B have been activated.
 Permissive U activation C. Indicates that the permissive units for phase C have been activated.

Ingeteam Power Technology S.A.


User Manual 189
PROTECTION FUNCTIONS 

 Block invertion current A. Indicates that current A inversion block has been activated.
 Block invertion current B. Indicates that current B inversion block has been activated.
 Block invertion current C. Indicates that current C inversion block has been activated.
 Memory invertion current A. Current A inversion block memorized. Indicates that current A inversion block
memorization has been activated.
 Memory invertion current B. Current B inversion block memorized. Indicates that current B inversion block
memorization has been activated.
 Memory invertion current C. Current C inversion block memorized. Indicates that current C inversion block
memorization has been activated.
Table 106 Teleprotection schemes signals

Signal Data Attribute


TPRx Z L1 ProRx stVal
TPRx Z L2 ProRx2 stVal
GSR Z L1 GSL1Rx stVal
GSR Z L2 GSL2Rx stVal
TPTx Z ProTx stVal
ECHO Z Echo stVal
STOP Z STOPTx stVal
27WI Z Phase A WeakInF phsA
27WI Z Phase B WeakInF phsB
27WI Z Phase C WeakInF phsC
27WI Z Trip WeakInF stVal
Teleprotection Z Trip Op stVal
Weak Infeed Phase Z StrWeakInF stVal
Permissive Z Activation OpPerUnit stVal
Block Inverted Current Z RvABlk stVal
Memory Inverted Current Z MBlkInvDir stVal
85_L1_END_perm_GSL_Z GSL1End stVal
85_L2_END_perm_GSL_Z GSL2End stVal
Teleprotection Z status TpSt stVal
ECHO Z Status EchoSt stVal
Weak infeed Z status WeiOpSt stVal
TPRx Z L1A ProRxA stVal
TPRx Z L1B ProRxB stVal
TPRx Z L1C ProRxC stVal
TPRx Z L2A ProRx2A stVal
TPRx Z L2B ProRx2B stVal
TPRx Z L2C ProRx2C stVal
TPTx Z_A ProTxA stVal
TPTx Z_B ProTxB stVal
TPTx Z_C ProTxC stVal
ECHO Z_A EchoA stVal
ECHO Z_B EchoB stVal
ECHO Z_C EchoC stVal
STOP Z_A STOPTxA stVal
STOP Z_B STOPTxB stVal
STOP Z_C STOPTxC stVal
Teleprotection Trip Z_A TpcTripA stVal
Teleprotection Trip Z_B TpcTripB stVal
Teleprotection Trip Z_C TpcTripC stVal
Permissive U activation A OpPerUnitA stVal
Permissive U activation B OpPerUnitB stVal
Permissive U activation C OpPerUnitC stVal
Block invertion current A RvABlkA stVal
Block invertion current B RvABlkB stVal
Block invertion current C RvABlkC stVal
Memory invertion current A MBlkInvDirA stVal
Memory invertion current B MBlkInvDirB stVal
Memory invertion current C MBlkInvDirC stVal

Ingeteam Power Technology S.A.


User Manual 190
PROTECTION FUNCTIONS 

3.12.2.2 Permissive underreaching


It causes an instantaneous teleprotection trip upon the reception of the teleprotection signal (TPRIx), together with the pick up
of zone 2, as long as the reverse memorization of zone 4 is not activated (21 memory inverted current). It is used to accelerate
the trips at one end with the other indicates this.

This scheme is based on the idea that at least one of the protection devices at one end of the line will see the fault in zone 1. If
a terminal sees the fault in zone 1 and the other one sees it in zone 2, the fault can be considered as being inside the line
between both devices, in the section of the line close to the terminal which sees it in zone 1.

The terminal that sees the fault in zone 1, besides setting off an instantaneous trip, sends the trip permission signal (TPTx) to
the other end while zone 1 is activated. The terminal which detects the fault in zone 2 generates an instantaneous trip with the
reception of the teleprotection signal (TPRIx) together with the activation of a unit in zone 2 as long as zone 4 is not activated.

Figure 123 Permissive Underreaching Logic Diagram

In the case of phase-segregated teleprotection, a TPTx of the faulted phase will be sent. For producing the teleprotection trip of
one phase, the TPRx of this phase and the corresponding permissive unit has to be activated. In addition, it the does not have
to see the fault backwards in that phase (Z Block units).

There is one signal per phase.

❑ TPTx_A: Fault AN, AB, CA.


❑ TPTx_B: Fault BN, AB, BC.
❑ TPTx_C: Fault CN, BC, CA

Ingeteam Power Technology S.A.


User Manual 191
PROTECTION FUNCTIONS 

Figure 124 Permissive Underreaching Logic Diagram, phase A, phase-segregated teleprotection

Figure 125 and Figure 112 show the permissive underreaching protection scheme. This figure is used to analyse how the
protection devices will act in the event of faults in F1, F2 and F3:

Figure 125 Fault examples

III

II

Protección Protección
x1 u1
x2 u1 x1 u2
x3 u3

A B
F1 F2 I F3
II

III

❑ Fault F1: Protection A sees the fault in zone 1, causing an instantaneous trip and sending a permission signal to protection
B. Protection B sees the fault in zone 2 and will set off a high-speed trip when it sees the fault in zone 2 and will receive
protection A's permission command.

Ingeteam Power Technology S.A.


User Manual 192
PROTECTION FUNCTIONS 

❑ Fault F2: Both protection devices see the fault in zone 1, causing a high-speed trip. Furthermore, redundant commands
are given by the communication channels.
❑ Fault F3: None of the protection devices will trip instantaneously. Protection A sees the fault in zone 2 but B does not see
the fault in the line to protect, not sending the permission signal to protection A. Hence, A's action in zone 2 will take
place in zone 2 time.
Inverse direction block: signal "Memory Inverted Current" can be eliminated from the logic by disabling this function. In this
case, "Memory Inverted Current" would be set permanently to 0.

In lines with more than two terminals, to apply this scheme, it has to be ensured that in the event on any fault in any point in
the line, at least the protection of one of the ends detects it in zone 1.

The scheme is applied to three-terminal lines by carrying an OR signal to the three of them from the TPRx of the other two ends
(See Figure 96).

3.12.2.3 Permissive overreaching


It produces an instantaneous teleprotection trip upon the reception of the teleprotection signal (TPRx), together with the pick
up of zone 2, as long as the memorized reverse zone is not activated (Memory Inverted Current).

In this protection scheme, a fault is considered internal to the line if both terminals see the fault in zone 2. An instantaneous
trip is caused if the teleprotection signal is received, together with activation of a unit in zone 2 as long as the memorised zone
4 is not activated.

The teleprotection signal is sent upon the activation of the zone 2 units, without the detection of a reverse fault (Memory
Inverted Current).

Figure 126 Permissive Overreaching Logic Diagram

In the case of phase-segregated teleprotection, a TPTx of the faulted phase will be sent. For producing the teleprotection trip of
one phase, the TPRx of this phase and the corresponding permissive unit has to be activated. In addition, it the does not have
to see the fault backwards in that phase (Z Block units).

There is one signal per phase.

 TPTx_A: Fault AN, AB, CA.


 TPTx_B: Fault BN, AB, BC.
 TPTx_C: Fault CN, BC, CA.

Ingeteam Power Technology S.A.


User Manual 193
PROTECTION FUNCTIONS 

Figure 127 Permissive Overreaching Logic Diagram, phase A, phase-segregated teleprotection

Figure 126 and Figure 112 show the permissive overreaching protection scheme. This figure is used to analyse how the
protection devices will act in the event of faults in F1, F2 and F3:

❑ Fault F1: Protection A sees the fault in zone 1 (PDIS1), causing an instantaneous trip and sending a permission signal to
protection B, given that it sees the fault in zone 2 (PDIS2) (zone 2 includes zone 1). Protection B trips instantaneously
when it sees the fault in zone 2 and receives a permission order from protection A. Protection B will also send a
permission signal to protection A but it has already instantaneously tripped in zone 1.
❑ Fault F2: Both protection devices see the fault in zone 1, causing a high-speed trip. Furthermore, redundant commands
are given by the communication channels.
❑ Fault F3: Protection A sees the fault in zone 2 and sends the permission signal to B, which sees the fault backwards. When
A does not receive the permission signal from B, zone 2's action will take place in zone 2 time. Protection B receives the
permission signal from A, but when it sees the fault backwards, it will not trip.
Any fault in zone 3 (PDIS3) will be eliminated in zone 3 time.

3.12.2.4 Directional unblocking


The directional unblocking scheme is used in overreaching schemes. Together with the TPRx signal, the channel loss signal
(GSLRx) is received.

In usual conditions, the signal GSLRx has the same value as the TPRx signal. Thus, if the TPRx signal is activated, GSLRx is also
activated. If both signals are deactivated there is not fault and the guard channel signal is not lost.

If the overreaching zone 2 (PDIS2) acts, the security signal works as an unblocking signal.

An instantaneous teleprotection trip will be issued by the zone 2 activation:

❑ If the unblock signals TPRx and GSLRx are received or

Ingeteam Power Technology S.A.


User Manual 194
PROTECTION FUNCTIONS 

❑ When the device only receives the GSLRx signal, the timers start. When the “GSL minimum time (ms)” (LoGMinTmms)
delay is over without the reception of the TPRx signal, a trip is issued. Once the “GSL maximum time (ms)” has elapsed, no
trip is enabled. Once the loss off channel signal is deactivated again a third timer starts. When the “GSL drop out time
(ms)” delay is over the previous logic is newly applied.
The directional unblocking scheme does not allow phase-segregated teleprotection.

Figure 128 Treatment of Line 1 channel loss signals

Figure 129 Treatment of Line 2 channel loss signals

Ingeteam Power Technology S.A.


User Manual 195
PROTECTION FUNCTIONS 

Figure 130 TPTx and Trip Signal Scheme

The figures show the directional unblocking protection scheme. This figure is used to analyse how the protection devices will
act in the event of faults in F1, F2 and F3:

Figure 131 Directional Unblocking Protection scheme

N.B.: The signals received in the directional blocking (GSLRx and TPRx) can only be received with the values (active, active),
(active, inactive) or (inactive, inactive). They can never be (inactive, active) because the transmitter/receiver that sends the
signals, when there is communication and receives TPR gives the signals GSR and TPR and when there is no communication,
gives GSR but not TPR.

The GSLRx signal is active in 2 cases:

❑ When the security signal is lost or


❑ When TPRx is received. In this case, it is converted into a non-blocking signal. It behaves in the same way as in the case of
overreaching.
The GSLRx signal is deactivated when there is communication and there is no TPRx.

Ingeteam Power Technology S.A.


User Manual 196
PROTECTION FUNCTIONS 

Table 107 GSLRx and TPRIx Values in Directional Unblocking

GSLRx TPRIx TRIP Remark


0 0 0 Guard channel is not lost and there is not fault.
1 1 1 Guard channel is not lost and there is a fault. GSLRx signal becomes a non-blocking signal (GSLRx = 1).
Guard channel is not lost and we do not know if there is a fault.
Time
1 0 When signal loss of guard channel is activated it opens a time window during which it can produce GSLRx shot if the
window
signal remains active for the programmed time (TPSG) without reception of TPRIx
0 1 It is not possible because if we have TPRIx, it is because there is communication

Analysis is made of how the protection devices will act in the event of faults in F1, F2 and F3:

❑ Fault F1: Protection A sees the fault in zone 1, causing an instantaneous trip and changing the security signal to an
unblocking signal given that it sees the fault in zone 2 (zone 2 includes zone 1). Protection B sees the fault in zone 2 and
when it receives the unblocking signal from A, it will speed up the trip. If the security channel is lost, when protection B's
zone 2 is activated, it will speed up its trip if it receives the channel loss signal for the time programmed for "security
signal loss".
❑ Fault F2: Both protection devices see the fault in zone 1, causing a high-speed trip.
❑ Fault F3: Protection A sees the fault in zone 2 but does not speed up its trip given that protection B sees the fault in zone
4 and therefore will not change the security signal for an unblocking signal.

3.12.2.5 Directional blocking


The TPTx blocking signal is sent if a backwards fault is detected (Memory Inverted Current).

A stop channel signal (STOP Z) is activated if a forward fault is detected (zone 1 or zone 2) and it is maintained during “Block
delay time (ms)” (BlkTmms), without the detection of a fault in zone 4 (Z4_MEM).

If the channel interruption signal (STOP Z) is activated and the signal TPRx is not received, the signal "Teleprotection Z Trip" is
activated.

If the input “TPTx Blocking input” is activated the signal TPRx is not sent. Furthermore, if the “TP Trip Block” input is activated,
the signal "Teleprotection Z Trip" is blocked.

Figure 132 Directional Blocking Scheme

The blocking time is an additional delay time to give time for the blocking signal to be received and is programmable by the
user. The transmission time must be as low as possible with the aim of reducing this delay to a minimum.

In the case of phase-segregated teleprotection, a TPTx of the faulted phase will be sent. For producing the teleprotection trip of
one phase, the TPRx of this phase does not have to be activated. In addition, the STOP signal and the permissive units of this
phase have to be activated.

There is one signal per phase.

 The signals corresponding to phase A, are activated with the faults AN, AB, CA.

Ingeteam Power Technology S.A.


User Manual 197
PROTECTION FUNCTIONS 

 The signals corresponding to phase B, are activated with the faults BN, AB, BC.
 The signals corresponding to phase C, are activated with the faults CN, BC, CA.

Figure 133 Directional Blocking Scheme, phase A, phase-segregated teleprotection

The Figure 112 and Figure 113 show the directional blocking protection scheme. This scheme is used to analyse how the
protection devices will act in the event of faults in F1, F2 and F3:

❑ Fault F1: Protection A detects the fault in zone 1 causing an instantaneous trip. Protection B detects the fault in zone 2
and once the blocking time has elapsed, it will trip given that a blocking command is not received from A since A does not
detect the fault in zone 4.
❑ Fault F2: Both protection devices see the fault in zone 1, causing a high-speed trip.
❑ Fault F3: Protection A detects the fault in zone 2 but does not cause a fast trip given that protection B sees the fault in
zone 4 and will therefore send a blocking signal to A.

Figure 134 Directional blocking example

Care must be taken with the coordination of the blocking unit backwards (for example, B's zone 4) of each end with the
overreaching unit of the other end (A's zone 2), these being set so that the reach of the reverse unit is always greater than the
overreach's.

Figure 135 Coordinating the Reverse Blocking Unit

Ingeteam Power Technology S.A.


User Manual 198
PROTECTION FUNCTIONS 

This scheme has the advantage of not being sensitive to noise in the communication channel and has the disadvantage of
possibly causing untimely trips if the communication channel is lost.

The blocking scheme is usually used in long lines when the teleprotection signal is transmitted via the protected line by the
carrier wave and the diminishing of the signal transmitted at the point of fault can be so severe that reception at the other end
of the line cannot always be ensured.

3.12.2.6 ECHO
It is used together with permissive overreaching schemes by acting on the teleprotection (TPTx) signal.

The ECHO Z signal only provides a programmable pulse. The ECHO function sends the teleprotection (TPTx) signal with any of
the following conditions:

❑ The ones corresponding to the permissive overreaching scheme.


❑ If TPRIx is received and no forward or reverse faults are detected.
 programmable for a minimum time (setting " ECHO delay time(ms)"), or
 the breaker is open (in this situation, it does not wait for the programmed time to elapse).

Ingeteam Power Technology S.A.


User Manual 199
PROTECTION FUNCTIONS 

Figure 136 Echo and weak infeed scheme

Figure 137 Weak infeed scheme signals

Ingeteam Power Technology S.A.


User Manual 200
PROTECTION FUNCTIONS 

In the case of phase-segregated teleprotection, one TPRx will be received per phase, also activating one ECHO per phase.

Figure 138. Echo and weak infeed scheme, phase A, phase-segregated teleprotection

It is used together with permissive overreaching schemes in cases where one end of the line is open (Figure 108 end B) or is a
weak end (Figure 109 end B). In the event of a fault on the line near the weakly-fed or open end, the distance unit of this end of
the line does not detect the fault. Hence, the trip will not be issued, nor will the permission signal be sent to the other end of
the line. Hence, since the permission signal will not be received, the strongly-fed end of the line will not speed up its trip.

To speed up the trip at the strongly-fed end in the event of a fault at the opposite end, the Echo function returns the TPRIx
signal received to the remote terminal if it does not detect a fault forward or backwards, or if the circuit breaker is open.

The resending of the TPRIx received (ECHO Z) will be instantaneous if the circuit breaker is open and will suffer a delay
(EcActTmms) if there is a weak power supply. This delay makes it possible to cover situations in which there is a higher fault
detection time, or it start slightly later due to an unfavourable distribution of the fault current. This delay is usually set to
approximately 40ms.

Ingeteam Power Technology S.A.


User Manual 201
PROTECTION FUNCTIONS 

"ECHO Z" is a pulse that during "ECHO pulse time (ms)" (EcTmms), which is normally set to approximately 50 ms, thus assuring
that the signal received is even recognised with different action times of the protection equipment at ends of the lines and with
different response times of the transmission equipment.

Figure 139 Echo logic protection with breaker open in B

Figure 137 shows the ECHO Logic Sample, with the circuit breaker in B Open This scheme will be used to analyse how the
protection devices act in the event of faults F1 and F2 with the basic permissive overreaching scheme.

❑ Fault F1: Protection A detects the fault in its zone 1 and hence instantaneously trips and sends a permission signal to B.
End B is open so the fault is cleared.
❑ Fault F2: Protection A detects the fault in zone 2 and sends a permission signal to B. When the protection device in B
detects that the circuit breaker is open, it will resend the permission signal to protection A without delay. When
protection A detects the fault in zone 2 and having received the permission signal, it will speed up its trip.
Figure 140 Echo and weak infeed example

Figure 137 shows the ECHO logic, and Weak infeed. This scheme will be used to analyse how the protection devices act in the
event of faults F1 and F2 with the basic permissive overreaching scheme.

❑ Fault F1: Protection A detects the fault in unit 1 and will hence trip instantaneously and send a permission signal to B. The
protection in B, being weakly fed, will not detect the fault, but as it receives the permission signal, it will send back to A
with the programmed delay, but A will be open. The circuit breaker at end B will remain closed.
❑ Fault F2: Protection A detects the fault in unit 2 and sends a permission signal to B. The protection in B, being weakly fed,
will not detect the fault, but as it receives the permission signal, it will send back to A with the programmed delay. When
protection A sees the fault in unit 2 and has received the permission signal, it will speed up its trip. The circuit breaker at
end B will remain closed.

3.12.2.7 Weak infeed (27WI)


This is a complement to ECHO Z, where if ECHO Z conditions are met, with the circuit breaker closed and undervoltage in at
least one of the phases, a trip is produced.

The undervoltage unit associated to the weak infeed function has its own settings and is not dependent on the undervoltage
units.

The thresholds are 0.1V to 200V.

If an unblocking scheme is used, the TPRIx signal is replaced by TPRIx & GSL.

Ingeteam Power Technology S.A.


User Manual 202
PROTECTION FUNCTIONS 

If one end of the line is weakly fed (Figure 109 end B) with the echo logic, as seen in the previous section, the trip at the
strongly fed end is accelerated. However, the weakly fed end remains closed. This logic allows the opening of this end of the
line.

To detect the fault at the weak end, the following conditions must be fulfilled:

❑ TPRIx signal received (it will be sent to the strongly-fed end, as described in the ECHO function).
❑ The circuit breaker is closed.
❑ Undervoltage is detected in one of the phases (as a consequence of the fault). The settings recommended are 70%Vr for
the voltage.

Figure 141 Protection in the Weak Infeed Logic, with End B Weakly Fed

Figure 110 shows the weak infeed logic, with end B weakly fed. This scheme will be used to analyse how the protection devices
act in the event of F1 faults with the basic permissive overreaching scheme.

❑ Fault F1: Protection A detects the fault in zone 2 and sends a permission signal to B. The protection in B, being Weak
Infeed, will not detect the fault and when it receives the permission signal, it will send it to A after the set time. When
protection A sees the fault in zone 2 and has received the permission signal, it will speed up its trip. When protection B
fulfills the ECHO conditions and detects undervoltage (due to the existence of the fault), it will give the trip command.

3.12.2.8 Inverse directional block


It delays the teleprotection trip for a number of cycles in order to allow the remote terminal time to clear the permission signal
(TPTx) following a change in the flow direction due to the opening of the breaker.

It is used in double circuit lines to prevent trips due to the change in the current flow which is caused when the circuit breaker
is opened at one end of the faulty line when this fault is cleared. The reversal of the current implies the reversal of the
protection device's directional elements, as well as the increase in the apparent distance to the fault. The time between the
repositioning of the distance elements and the functioning of the unit may give rise to a trip in the healthy parallel line.

When the scheme is a blocking onee, it keeps the blocking signal for a set time "Block delay time (ms)”, blocking the trip for a
time after detecting a change in the fault's direction. When the scheme is permissive, it blocks the trip and the emission of the
permission for a set time after changing the direction in which it detects the fault (backwards to forward).

The zone 4 signal is used with a memorization time "Current rev pickup t (ms)" (RvATmms), which enables the "Memory
Inverted Current" signal to be used in the rest of the schemes.

In the case of phase-segregated teleprotection, the signal used for the blocking will depend on what is set in "Z Block Units (3
bits)”, activating a signal per phase.

There is one signal per phase.

 The signals corresponding to phase A, are activated with the faults AN, AB, CA.
 The signals corresponding to phase B, are activated with the faults BN, AB, BC.
 The signals corresponding to phase C, are activated with the faults CN, BC, CA.
The following figures show the change in the current flow when the fault occurs and when circuit breaker K is opened to clear
this fault:

Ingeteam Power Technology S.A.


User Manual 203
PROTECTION FUNCTIONS 

Figure 142 Change in the Current Flow When the Fault Occurs in a Double Circuit Line

Inverse direction blocking with permissive schemes:

❑ When faults F occurs as can be seen in Figure 111.1, protection K will detect the fault in zone 1, J will either detect it in 1
or 2 and H backwards. In this situation, K instantaneously opens the circuit breaker and sends the permission signal to J
and likewise, G sends the permission signal to H.
❑ When K opens, the current's flow is inverted as can be seen in Figure 111.2. In this new situation, G will detect the fault
backwards and H will detect it in zone 2. These conversions are not simultaneous or instantaneous. Hence, H could trip
before G removes the permission signal. To prevent this trip, the teleprotection trip is delayed for a number of cycles, to
give the remote terminal time to remove the permission signal.
Inverse direction blocking with blocking scheme:

❑ When the fault occurs as can be seen in Figure 110, protection K will detect the fault in zone 1, J will either detect it in 1
or 2 and H backwards. When H detects the fault in its zone 4, it sends a blocking signal to G (or it does not send the TPRIx
signal, which is the same), preventing tripping due to acceleration in zone 2.
❑ When K opens, the current's flow is inverted as can be seen in Figure 111.2. In this new situation, G will detect the fault
backwards and H will detect it in zone 2. H would trip before receiving the blocking signal from G. To prevent this, H will
continue to detect the fault backwards, allowing time to receive the blocking signal.
It is recommended that the additional blocking time be set as follows:

Additional blocking time = operating time of the circuit breaker at the other end of the line (typically 3 cycles) + the reset time
of the communication channel (1 cycle) + the reset time of zone 2 of the relay at the other end of the line (1 cycle) = 5 cycles.

3.12.3 Direct trip


This additional teleprotection scheme causes a single-pole or three-pole trip upon the reception of the teleprotection signal,
regardless of the status of the protection functions.

In order to operate correctly, it must be enabled. Furthermore, a digital input must be programmed as a direct trip, otherwise it
is like being disabled.

The reception signals associated to the direct trip are:

❑ Direct trip pole A, B or C: Causes an external single-pole trip in the corresponding pole.
❑ Direct trip pole ABC: Causes the command to open as well as an external three-pole trip.
Any digital signal can be used as an output signal for signalling a direct trip to the other extreme, either via the programming of
the digital outputs or via the programmable logics.

If a trip is received by two or more poles, it is considered to be a three-pole trip.

Ingeteam Power Technology S.A.


User Manual 204
PROTECTION FUNCTIONS 

A particular feature of the scheme is the direct trip, in which the input signals are generic but unit 1's signals zone used as the
output signals.

The settings for the configuration of this unit are shown in Table 110.

❑ Enabled: Enables the direct trip function:


❑ Direct trip - Pole A. Selects the signal which, when active, indicates the reception of the pole A direct trip.
❑ Direct trip - Pole B. Selects the signal which, when active, indicates the reception of the pole B direct trip.
❑ Direct trip - Pole C. Selects the signal which, when active, indicates the reception of the pole C direct trip.
❑ Direct trip - 3 Pole ABC. Selects the signal which, when active, indicates the reception of the pole ABC direct trip.
❑ Enable Events record. Allows the generation of protection events associated to the function. If set to “NO”, the function’s
protection events are not generated. If set to “YES”, the function’s specific mask is contemplated.
❑ Reclose permission. Indicates whether each trip type can be reclosed or not, in accordance with the recloser's closing
cycle (see reclosure permission mask).
This unit's settings and outputs are as follows:

❑ PROT/ZPDTS1 logical node


❑ Settings and logical inputs. There are 6 settings tables. For details, see Table 110.
❑ No commands are available.
❑ Outputs: Table 110 shows the function’s output data.
 Direct Trip Signal A. Indicates that the pole A direct trip signal has been received.
 Direct Trip Signal B. Indicates that the pole B direct trip signal has been received.
 Direct Trip Signal C. Indicates that the pole C direct trip signal has been received.
 Direct Trip Signal ABC. Indicates that the pole ABC direct trip signal has been received.
 Direct Trip Status. Indicates the function’s status.

Table 108 Direct trip settings

Data Setting Min. Max. Step Remarks Type


DTEna Enabled NO / YES
LogInDTA Direct trip - pole A int32
LogInDTB Direct trip - pole B int32
LogInDTC Direct trip - pole C int32
LogInDT Direct trip - 3 pole ABC int32
NO (0)
Reclose 1 (1P) (1)
Reclose 1 (3P) (2
Reclose 1 (1P/3P) (3)
ReclPerm Reclose permission 0 15 enum
Reclose 2-3-4 (4)
Reclose1(1P)-2-3-4 (5)
Reclose1(3P)-2-3-4 (6)
Reclose 1-2-3-4 (7)
MaskEna Enable Events record NO / YES Boolean

Table 109 Direct trip outputs

Signal Data Attribute


Direct Trip Signal A DTTRx phsA
Direct Trip Signal B DTTRx phsB
Direct Trip Signal C DTTRx phsC
Direct Trip Signal ABC DTTRx general
Direct Trip Status StEna stVal

Ingeteam Power Technology S.A.


User Manual 205
PROTECTION FUNCTIONS 

Figure 143 Direct Trip Scheme

3.12.4 External trip


This function allows you to program any signal as an external trip. It can be one pole or three poles trip. It does not have
enabled setting, it is enough the configuration of any of the logical inputs.

It also provides a setting that performs a mask that allows it to produce a general trip. In the case the general trip is not
allowed, it can be used to start the recloser or the breaker failure (50BF) by external cause. There is another setting for this unit
to indicate if it can be reclosed, if it is allowed, that is, it works as the rest of the trips.

Receiving two poles trips it generates three pole trip.

The settings for the configuration of this unit are shown in Table 110.

❑ External trip - pole A. Selects the signal which, when active, indicates that there is an external A pole trip.
❑ External trip - pole B. Selects the signal which, when active, indicates that there is an external B pole trip.
❑ External trip - pole C. Selects the signal which, when active, indicates that there is an external C pole trip.
❑ External trip - 3 pole. Selects the signal which, when active, indicates that there is an external three-pole trip.
❑ General trip. Indicates if this unit produces general trip or not. For additional details, see the section corresponding to the
recloser (3.12.6).
❑ Reclose permission. Indicates whether each trip type can be reclosed or not, in accordance with the recloser's closing
cycle (see reclosure permission mask).
❑ Enable Events record. Allows the generation of protection events associated to the function. If set to “NO”, the function’s
protection events are not generate. If set to “YES”, the function’s specific mask is contemplated.
This unit's settings and outputs are in the PROT/ZPEXT1 logical node:

❑ Settings and logical inputs. There are 6 settings tables (see Table 110).
❑ No commands are available.
❑ Outputs: Table 110 shows the function’s output data.
 External trip pole A. Indicates the activation of an external A pole trip.
 External trip pole B. Indicates the activation of an external B pole trip.
 External trip pole C. Indicates the activation of an external C pole trip.
 External trip 3 pole. Indicates the activation of an external three-pole trip.
 External trip 1 pole. Indicates the activation of an external single-pole trip.
 External trip Status. Indicates the function’s status.

Ingeteam Power Technology S.A.


User Manual 206
PROTECTION FUNCTIONS 

Table 110 External trip settings

Data Setting Min. Max. Step Remarks Type


LogInExTA External trip - pole A int32
LogInExTB External trip - pole B int32
LogInExTC External trip - pole C int32
LogInExABC External trip - 3 pole int32
GenTrip General trip NO / YES Boolean
NO (0)
Reclose 1 (1P) (1)
Reclose 1 (3P) (2
Reclose 1 (1P/3P) (3)
ReclPerm Reclose permission 0 15 enum
Reclose 2-3-4 (4)
Reclose1(1P)-2-3-4 (5)
Reclose1(3P)-2-3-4 (6)
Reclose 1-2-3-4 (7)
MaskEna Enable Events record NO / YES Boolean

Table 111 External trip outputs

Signal Data Attribute


External trip pole A ExtOp phsA
External trip pole B ExtOp phsB
External trip pole C ExtOp phsC
External trip 3 pole ExtOp general
External trip 1 pole ExtMOp general
External trip Status StEna stVal

3.12.5 Teleprotection serial communication


A serial channel is selected to be used for teleprotection communications between the two terminals of the line. It is the same
for 67NQ and distance protection.

The communication between the devices uses a private protocol.

Up to 16 digital signals can be sent.

Used as transmitter, the device sends the signals programmed in the communication node (ITPC).

Used as receiver, the device has all the received signals, in the positions “Teleprotection signal 1”, “Teleprotection signal 2”, up
to “Teleprotection signal 16”. All these signals can be used in the teleprotection schemes.

For example, the signal “ETP 67NQ” can be assigned to the “Digital 1” setting of the ITCP node. The status of “ETP 67NQ” is sent
in the first position of the 16 transmitted signals.

The other device receives this signal as “Teleprotection signal 1”, which can be used as the receipt of the remote protection
signal. This setting is the logical input “TPRx_21 line 1”.

The settings of the communication´s channel are:

❑ Port Number. When the port exists in the device, the options are:
 Disabled. The communication is disabled.
 COM 1. The communication is enabled in the port COM1.
 COM 2. The communication is enabled in the port COM2.
❑ Comm speed (bauds). It refers to communication speed in the selected port. The options are between 19200 and 115200
bauds.
❑ Parity: It refers to an additional bit used in each character to detect transmission errors. It is selected among "None",
"Even" and "Odd".
❑ Number of Stop bits: Number of bits sent at the end of each character.

Ingeteam Power Technology S.A.


User Manual 207
PROTECTION FUNCTIONS 

❑ Digital 1: It refers to the signal sent in the first position of the message. It can be selected among all the available digital
signals of the device. It is the “Teleprotection signal 1” in the receiver device.
❑ Digital x: where x is from 1 to 16. It refers to the signal sent in the “x” position of the message. It can be selected among all
the available digital signals of the device. It is the “Teleprotection signal x” in the receiver device.
This function has settings and signals:

❑ Node PROT/ITPC1
❑ Settings. There is a setting group. See Table 112.
❑ It has no logical input.
❑ It has no command
❑ Outputs: Table 113 shows the function’s output data:
 Teleprotection comms failure: It indicates there is a communication failure.
 Teleprot comms config alarm: It indicates a failure in the selection of the communication port. It is activated when the
selected port doesn´t exist or it´s occupied.
 Teleprotection signal 1: It refers to the signal received in the first position of the communication message.
 Teleprotection signal x: where x is from 2 to 16. It refers to the signal received in the position x of the communication
message.

Table 112. Teleprotection communication setting

Data Setting Min. Max. Step Remarks Type


Disabled(0)
Port Port Number COM1(1) enum
COM2 (2)
19200(6)
38400(7)
VelTrans Comm speed (bauds) enum
57600(8)
115200(9)
Parity Parity None(0) / Even(1) / Odd(2) enum
Stopbit Number of Stop bits 1 2 1 int32
LogInDig1 Digital 1 int32
…same from 2 to 15
LogInDig16 Digital 16 int32

Table 113. Teleprotection communication signals

Signal Data Attribute


general (stVal in
Teleprotection comms failure LosSig
Ed2)
Teleprot comms config alarm TelCfgAlm general
Teleprotection signal 1 TelDig1 general
… same from 2 to 15
Teleprotection signal 16 TelDig16 general

3.12.6 Trip logic


Each protection unit has a mask that allows it to produce a general trip:

❑ If a unit trips during a specific recloser status (blocked, in security t, etc.) and the corresponding mask is set to “YES”, the
trip is sent to the general trip output.
❑ If the mask is set to “NO”, the trip is produced but the "direct trip" signal is not received. In this way, the recloser is
independent of any trips used for signalling.
❑ If the recloser is out of service, all the units programmed to produce a general trip will issue a trip.
In the event of a specific trip failing to activate the “general trip”, the fault report is not generated.

Ingeteam Power Technology S.A.


User Manual 208
PROTECTION FUNCTIONS 

If a trip is produced at the same time as another trip which activates the general trip, all the trips are reflected in the fault
report: those which go to GT and those which do not.

The picks ups are affected in the same way as with each unit's trips. Each of the relay’s pickups generates a signal. This signal
passes through the trip mask filter and is included in an OR in order to generate a "General pick up" signal.

3.12.6.1 Single pole Trip


Depending on the fault, it allows one pole trips, that is, the open command is given to one pole.

ZPMPT node allows the enabled of the monopolar trip. The available settings are:

❑ Enabled. It allows one pole trips. If it is disabled, all trips will be 3 poles trips.
❑ Force three pole. Selects the signal which, when active, forces all the trip to be three poles.
❑ Enable Events record. Allows the generation of protection events associated to the function. If set to “NO”, the function’s
protection events are not generate. If set to “YES”, the function’s specific mask is contemplated.
❑ Single Pole Trip 67NQ16. Allows single pole trips for 67NQ remote protection scheme.
❑ Single Pole Trip Weak Infeed16. It allows single pole trips for Weak Infeed in the Z remote protection scheme Z, or in Z and
67NQ.

Table 114. Single Pole Trip settings

Data Setting Min. Max. Step Remarks Type


MPTEna Enabled NO / YES Boolean
LogInFoTP Force three pole int32
MaskEna Enable Events Record NO / YES Boolean
SPlTr Single Pole Trip 67NQ NO / YES Booleano
NO (0)
SPlTrWei YES only Z (1) enum
Single Pole Trip Weak Infeed YES Z and 67NQ (2)

The output signals are:

❑ Single-phase tripping Status. It indicates that the Single Pole Trip is activated.
❑ Force 3 Pole trip. It indicates that the Force three pole input is activated.
❑ Single phase 67NQ status. It indicates that the Single Pole Trip for 67NQ remote protection scheme is activated.
❑ Single phase WI status. It indicates that the Single Pole Trip for 67NQ remote protection scheme is activated.

Table 115. Single Pole Trip outputs

Signal Data Attribute


Single-phase tripping Status StEna general (stVal in Ed2)
Force 3 Pole trip FoTP general
Single phase 67NQ status SPlSt stVal
Single phase WI status WISt stVal

Single Pole Trip is provoked when the following conditions are fulfilled:

❑ Single Pole Trip must be enabled.


❑ Force three pole input must not be deactivated.
❑ A single pole trip must happen. It can be:
 Zone 1 Single pole trip.
 Zone 2 Single pole trip accelerated by teleprotection. The zone 2 time delay trips are always three pole.
 Single pole external trip.

16
Avaliable from firmware version 6.0.8.0 and ICD version 8.1.0.4

Ingeteam Power Technology S.A.


User Manual 209
PROTECTION FUNCTIONS 

❑ When the recloser is enabled, it must be in standby and the Reclose mode must be one of the single pole recloser (1 pole,
1P/3P o Dependent).
When the recloser is disabled by setting, it doesn´t affect and single Pole Trip is generated when the other conditions are
fulfilled. In that case, a reclose of an external device is allowed.

The three poles trip is generated with all the trips that are not single pole.

3.12.6.2 General trip mask


It is independent for each of the protection units.

Indicates if this unit produces a general trip or not. The protection functions can be enabled or disabled and can trigger a trip
and/or a pickup independently of which units are to open the breaker. The general trip signal is sent to the breaker and is
configured by means of this mask.

In order, upon tripping, for a unit to activate the general trip, it must meet (See Figure 144):

❑ Be enabled.
❑ Have its general trip mask set to YES.
❑ If the recloser is enabled, the unit must not be blocked by the trip permission mask.
Each protection unit has an independent setting which is used to enable or disable its general trip. Its reference is "GenTrip"
and allows the options “NO / YES”.

Table 116 General trip (in each protection node)

Data Parameter Min. Max Step Remarks Type


GenTrip General trip YES/NO

Figure 144 General trip scheme

DIGITAL SIGNAL
79 in service

AJ 51-1 -> D.G.


DIGITAL SIGNAL with 79 blocked
79 blocked

AJ 51-1 -> D.G.


DIGITAL SIGNAL with 79 in standby
79 in stand-by
AJ 51-1 -> D.G.
with 79 in time t
DIGITAL SIGNAL Following manual closure
79 in time following Manual
Closure
AJ 51-1 -> D.G.
DIGITAL INPUT with 79 in recalim t 1
79 in TIME t 1

AJ 51-1 -> D.G.


DIGITAL INPUT with 79 in TIME t 2
79 in TIME t 2

AJ 51-1 -> D.G.


DIGITAL INPUT with 79 in TIME t 3
79 in TIME t 3

AJ 51-1 -> D.G.


DIGITAL INPUT with 79 in time t 4
79 in TIME t 4

DIGITAL INPUT
51-1 Trip
AJ 51-1 -> D.G.

DIGITAL INPUT
General trip
DIGITAL INPUT
51-2 Trip
AJ 51-2->D.G.

………………………….

DIGITAL INPUT
Unit X Trip
AJ X->D.G.

Ingeteam Power Technology S.A.


User Manual 210
PROTECTION FUNCTIONS 

3.12.6.3 Trip permission masks


They are independent for each of the protection units and are configured in the protection nodes.

This mask is used to select which trips are associated to the “general trip” (with the recloser in service), depending on the status of
the recloser.

Independently of these settings, the protection units pickup and trip, activating their corresponding signals.

The unit that is to produce the trip (activate the general trip signal) can be selected by programming 4 trip masks peer unit and
which are active in the following moments:

❑ Standby (supervising or reset).


❑ Reclaim time following manual closure.
❑ Reclaim time following reclosure 1, 2, 3 or 4.
❑ Recloser blocked (external or internal block).
If the recloser is out of service, these masks have no effect, and thus all the units programmed to produce a general trip will issue a
trip.

Each protection unit has independent masks. If a unit trips during a specific recloser status (blocked, in security t, etc.) and the
corresponding mask is set to “YES”, the trip is sent to the general trip output. If the mask is set to “NO”, the trip is produced but the
"direct trip" signal is not received.

Reclosure block. When selected, the trip of this unit blocks the recloser. Detailed description in the chapter “Post-trip reclosure
permission mask”.

Each protection unit has an independent setting which is used to enable or disable the unit’s permissions. The reference is
“TripPerm”. The setting is configured as a bit field where each bit corresponds to a selection, indicating the integer value:

Bit meaning (1) Bit Value


Reclosure block 0 NO / YES
Trip permission 79 standby 1 NO / YES
Trip permission 79 blocked 2 NO / YES
Permission for trip in reclaim time following reclosure 1 3 NO / YES
Permission for trip in reclaim time following reclosure 2 4 NO / YES
Permission for trip in reclaim time following reclosure 3 5 NO / YES
Permission for trip in reclaim time following reclosure 4 6 NO / YES
Permission for trip in reclaim time following manual closure 7 NO / YES

An example of use with trip permissions in standby and following reclosures would be the decimal value 122 (01111010 in binary),
broken down into:

Bit 7 6 5 4 3 2 1 0
Value 0 1 1 1 1 0 1 0

The maximum permitted value with all permissions enabled is 255 (11111111 in binary).

Table 117 Trip permission after reclosing (each protection node)

Data Setting Minimum Maximum Step Remarks Type


TripPerm Trip Permission by reeng. 0 8191 1 int32

3.13 CT SUPERVISION

If the event of neutral current in the 4th transformer, a fault may be detected in at least one of the relay input channels (adaptation
transformer + internal circuitry). The absolute value of three times the zero sequence current (calculated using the phase currents) is
compared with the current measured at the transformer, taking the phase (RTF) and neutral (RTN) transformation ratios into account.
None of the phases must exceed 1.5 times the rated current.

The unit activates a “CT monitoring alarm signal” when the following conditions are met.

Ingeteam Power Technology S.A.


User Manual 211
PROTECTION FUNCTIONS 

❑ The measurements are outside the range:


|Ia + Ib + Ic | ∙ RTF
0.8 < < 1.3
|IN | ∙ RTN
❑ The measurement ratios meet:
|Ia + Ib + Ic | ∙ RTF − |IN | ∙ RTN
> 0.2
RTF
❑ |Ia+Ib+Ic-IN|/3>>10%·max(|Ia|, |Ib|, |Ic|)+5%·Irated
❑ The measurement of 3 current phases is less than 1.5 times the rated current.
The settings for the configuration of the current transformer monitoring are shown in Table 118.

❑ Enabled: Enables the CT monitoring function.


❑ Enable Events record. Allows the generation of protection events associated to the function. If set to “NO”, the function’s
protection events are not generated. If set to “YES”, the function’s specific mask is contemplated.

Table 118 CT monitoring settings

Data Setting Minimum Maximum Step Remarks Type


CTSpvEna Enabled NO / YES enum
MaskEna Enable Events record NO / YES Boolean

It has independent settings, commands and outputs:

❑ PROT/CCTS1 node
❑ Settings. There are 6 settings tables.
❑ There are no logical inputs or commands.
❑ Outputs: Table 119 shows the function’s output data.
 CT Supervision Status. It is active when enabled and not blocked.
 CT Supervision. Indicates that the CT monitoring conditions have been met.

Table 119 CT monitoring outputs

Signal Data Attribute


CT Supervision Status StEna stVal
CT Supervision CTSpv general

3.14 VT SUPERVISION

The negative and zero sequence voltages are compared with the rated voltage, generating alarm signals.

❑ Vn>10%Vn Supervision: it is active when V0 voltage is greater than the 10% of the rated voltage.
❑ V2>10%Vn Supervision: it is active when V2 voltage is greater than the 10% of the rated voltage.
It has no settings nor commands:

❑ Node GEN/LLN0
❑ Outputs: Table 120 shows the function’s output data.
Table 120 VT supervision outputs

Signal Data Attribute


Vn>10%Vn Supervision VnSpv stVal
V2>10%Vn Supervision V2Spv stVal

Ingeteam Power Technology S.A.


User Manual 212
BREAKER

4. BREAKER

4.1 BREAKER LOGICS

4.1.1 Breaker status


The breaker unit uses the PROT/XCBR1 and PROT/XCBR2 logical nodes (if there is more than one breaker). The settings used for
each breaker are:

❑ Configuration type: Indicates the breaker configuration scheme. It can be set to “Single” or "Breaker and a Half". Available
only in the XCBR1.
❑ Breaker type: Indicates the type of breaker employed:
 1 or 2 DI.General Status. Only one input is used for the status of the three poles.
 3 or 6 DI.Per Pole. An independent input is used for the status of each of the three poles.
❑ Pole failure time (ms): Indicates the time (ms) during which the difference between the type a and type b inputs must be
detected in the breaker status in order for the failure to be registered. Although the setting is unique, it affects the three
poles.
❑ 52a input: If the breaker type is "1 or 2 DI.General Status", it indicates the breaker status.
❑ 52a-Pole A: If the breaker type is "3 or 6 DI.Per Pole", it indicates the phase A breaker status.
❑ 52a-Pole B: The same as phase A, but for B.
❑ 52a-Pole C: The same as phase A, but for C.
❑ 52b input: If the breaker type is "1 or 2 DI.General Status", it indicates the breaker status.
❑ 52b-Pole A: If the breaker type is "3 or 6 DI.Per Pole", it indicates the phase A breaker status.
❑ 52b-Pole B: The same as phase A, but for B.
❑ 52b-Pole C: The same as phase A, but for C.
❑ Open blocking: When active, it blocks the manual breaker open commands. The trips are not blocked.
❑ Close blocking: When active, it blocks the breaker closure commands.
❑ Breaker open command input: When active, it generates a breaker open command.
❑ Close command input: When active, it generates a breaker closure command.
❑ 52 Blocking input: When active, it indicates the breaker is blocked. It is used in 50BF, open pole detector and recloser.
❑ Trip sealed: Allows the open commands to be enabled. When it is enabled, the open command is maintained after the
cause of the trip has disappeared and until the breaker is detected as open.
❑ Close sealed: Allows the closure commands to be enabled. When it is enabled, the closure command is maintained after
the cause of the closure has disappeared and until the breaker is detected as closed.
❑ Enable Events record: Allows the generation of protection events associated to the function. If set to “NO”, the function’s
protection events are not generated. If set to “YES”, the function’s specific mask is contemplated.
❑ 52 Supervision: Allows breaker status supervision function.
❑ Sync. Delay Time (s). This is the maximum time waited before the synchronism grants permission before a manual closure.
If closure permission is granted before the conclusion of this time, a closure command is issued. On the other hand, if this
time elapsed without permission being granted, the closure commnad is not executed. 17
❑ Synchrocheck supervision18. Indicates whether the manual closure is to be monitored with synchronism. If it´s set “YES”,
the manual close permission must be activated to generate the close command .
❑ Synchrocheck type18. Indicates whether the synchronism is internal or external.

17
Available from firmware version 5.19.15.7 and ICD version 6.3.0.0.
18
Available from firmware version 6.0.18.0 and ICD version 8.1.0.0

Ingeteam Power Technology S.A.


User Manual 213
BREAKER

❑ External syncro. Permission18. Logical external synchronism permission logic. Selects the signal which, when active,
indicates the existence of permission for synchronism.
❑ Min.time general trip(ms)19. Indicates the minimum duration time of the general trip signals per pole and global;
independently if the signal that causes the trip is deactivated before this time.

Table 121 Breaker status settings

Data Setting Min. Max. Step Remarks Type


BrNum Configuration type Single / Breaker and a Half enum
1 or 2 DI.General Status
BrTyp 52 Status detection enum
3 or 6 DI.Per Pole
FaBrTmms Pole failure time (ms) 0 10000 10 Int32
LogIn52a1 52a input Int32
LogIn52a1A 52a-Pole A Int32
LogIn52a1B 52a-Pole B Int32
LogIn52a1C 52a-Pole C Int32
LogIn52b1 52b input Int32
LogIn52b1A 52b-Pole A Int32
LogIn52b1B 52b-Pole B Int32
LogIn52b1C 52b-Pole C Int32
LogInOpBl Open blocking Int32
LogInClBl Close blocking Int32
LogIn52Op Breaker open command input Int32
LogIn52Cl Close command input Int32
LogInBlBr 52 Blocking input Int32
TrLck Trip sealed NO / YES Boolean
ClLck Close sealed NO / YES Boolean
MaskEna Enable Events Record NO / YES Boolean
SupEna 52 Supervision NO / YES Boolean
SyWaTms Sync. Delay Time (s) 0 600 0.01 float
VSynEna Synchrocheck supervision NO/YES Boolean
SynTyp Synchrocheck type Internal/External enum
LogInExSy External sync. Permission Int32
GTTmms Min.time general trip(ms)19 0 150 10 Int32

Breaker status via digital input

The status of the general breaker and by pole is determined with the status of digital inputs and breaker type setting. Used to
determine the status of the breaker without uncertainty and employed in functions that require the breaker’s status to be known,
such as the opening and closure sealing logic, the recloser, etc.

The 52b status inputs take precedence over the 52a status inputs, i.e., if 52b status inputs have been configured, the breaker status
is determined by means of these inputs, independently of the status of the 52a inputs.

Depending on the breaker type setting, the functioning is:

❑ 1 or 2 DI.General Status. The general 52b Status input is used for the breaker status. If it is not configured, the general 52a
Status input is used. The phase breaker status matches the general.
❑ 3 or 6 DI.Per Pole. The independent phases 52b Status inputs are used for the breaker status. If they are not configured,
the independent phases 52a Status inputs are used. The general breaker status is generated from the phases, taking into
account the following:
 Closed general status, if all the phases are closed.
 Open general status, if at least one of the phases is open.
Table 122 shows this function’s outputs.

❑ 52_1 Closed (Simple Log.). Indicates the breaker's general status, in accordance with the status of the digital inputs.
❑ 52_1 X Closed (Simple Log.). Indicates the status of each of the breaker's phases, in accordance with the status of the
digital inputs. Where "X" indicates the pole (A, B or C).

19
Available from firmware version 6.0.18.2 and ICD version 8.2.0.0

Ingeteam Power Technology S.A.


User Manual 214
BREAKER

Breaker status monitoring

The status of each pole (open, closed) is determined in accordance with a combination of N/O and N/C inputs. If inconsistencies are
detected between the N/O and the N/C inputs after the failure time (”Pole failure time (ms)”), a failure is signalled and no other
action is taken (relative to the discrepancy) until the anomaly is corrected. The functioning of this unit is shown in Figure 145.

52 Supervision setting allows breaker state supervision function

It has independent settings, commands and outputs:

❑ PROT/XCBR1 node
❑ PROT/XCBR2 node. Applies only in configurations with 2 switches
❑ Settings and logical inputs. There are 6 settings tables. For details see Table . The setting "Configuration type" is only
available in XCBR1, while the rest are on both nodes.
❑ There are associated commands:
 Pos. Switch opening or closure command.
 LOrdLc52Op. Local mode switch opening or closure command.
 LOrdMaBl. Locking or unlocking operations command for switch in local mode.
 BlkCls. Locking or unlocking switch closure operations command.
❑ Outputs: Table 122 shows the function’s output data.
 52_1 Open: Indicates that the 52 is open. There are independent general and phase signals.
 52_1 Closed: Indicates that the 52 is closed. There are independent general and phase signals.
 52_1 Undetermined: Indicates that the 52 is undetermined. There are independent general and phase signals.
 52_1 Failure: Indicates that the 52 has a failure. There are independent general and phase signals.
 Close Command - Breaker 1: Indicates that a closure command has been generated.
 Open Command - Breaker 1: Indicates that an opening command has been generated.
 Ph. X Open Command - Br1: Indicates that a Phase X opening command has been generated. X can be A, B or C.
 Close Failure - Br1: Indicates that a failure has occurred in some closing switch pole because maximum closing
time has exceeded.
 Ph. X Close Failure- Br1: Indicates that a failure has occurred in closing switch X pole because maximum closing
time has exceeded. X can be A, B or C.
 Open Failure - Br1: Indicates that a failure has occurred in some opening switch pole because maximum closing
time has exceeded.
 Ph. X Open Failure- Br1: Indicates that a failure has occurred opening switch X pole because maximum closing
time has exceeded. X can be A, B or C.
 Breaker settings error: Indicates that breakers are not properly defined and it is activated in the following
situations:
 No consistency between the breakers and recloser setting: "Select 2 breakers"
 No consistency between the breakers and breaker setting: "Configuration type".

In Figure 145 the state switch logic diagram is displayed. Input signals to this scheme are:

❑ Enab, Logic 52_1: This input indicates the state 52 detection mode. Corresponds to XCBR "52 Status detection" setting and
allows the following values:
 "1 or 2 DI.General Status": There is only one digital input to indicate the switch status.
 "3 or 6 DI.Per Pole". There are three digital inputs to indicate the status of each phase.
❑ 52a input: Indicates the switch a logic input. Applies to "52a input" setting. Active if the switch is closed.
❑ 52b input: Indicates the switch b logic input. Applies to "52b input" setting. Active if the switch is open.
❑ 52a Pole A: Indicates the phase A 'a logic' input. Applies to "52a-Pole A" Active if the pole is closed.

Ingeteam Power Technology S.A.


User Manual 215
BREAKER

❑ 52b Pole A: Indicates the phase A 'b logic' input. Applies to "52b-Pole A" Active if the pole is open.
❑ 52a Pole B: Indicates the phase B 'a logic' input. Applies to "52a-Pole B" Active if the pole is closed.
❑ 52b Pole B: Indicates the phase B 'b logic' input. Applies to "52b-Pole B" Active if the pole is open.
❑ 52a Pole C: Indicates the phase C 'a logic' input. Applies to "52a-Pole C" Active if the pole is closed.
❑ 52b Pole C: Indicates the phase C 'b logic' input. Applies to "52b-Pole C" Active if the pole is open.

Figure 145 Breaker status.

SETTING
Enab. Logic 52_1 = 1 POLE / 4 STATUSES

Enab. Logic 52_1 = 3 POLES / 4 STATUSES

SETTING
DIGITAL INPUT POLE
FAILURE T
52a input
0

DIGITAL INPUT
52b input

SETTING
DIGITAL INPUT POLE DIGITAL SIGNAL
FAILURE T DIGITAL SIGNAL 52_1 Undetermined
52a-Pole A
52_1 phase A Undetermined
0

DIGITAL SIGNAL
52_1 phase A Open
DIGITAL SIGNAL
52_1 phase A Closed

DIGITAL SIGNAL
52_1 phase A Failure
DIGITAL INPUT
52b-Pole A

SETTING
DIGITAL INPUT POLE
FAILURE T DIGITAL SIGNAL
52a-Pole B
52_1 phase B Undetermined
0 DIGITAL SIGNAL
DIGITAL SIGNAL 52_1 Open
52_1 phase B Open
DIGITAL SIGNAL
52_1 phase B Closed

DIGITAL SIGNAL
52_1 phase B Failure
DIGITAL INPUT
52b-Pole B

SETTING DIGITAL SIGNAL


DIGITAL INPUT POLE 52_1 closed
FAILURE T DIGITAL SIGNAL
52a-Pole C
52_1 phase C Undetermined
0
DIGITAL SIGNAL
52_1 phase C Open
DIGITAL SIGNAL
52_1 phase C Closed
DIGITAL SIGNAL
DIGITAL SIGNAL 52_1 failure
DIGITAL INPUT 52_1 phase C Failure
52b-Pole C

Ingeteam Power Technology S.A.


User Manual 216
BREAKER

Table 122 Breaker status outputs

XCBR1 Signal XCBR2 Signal Data Attribute


52_1 Open 52_2 Open OpenBr general
52_1 Closed 52_2 Closed CloseBr general
52_1 Undetermined 52_2 Undetermined UndetBr general
52_1 Failure 52_2 Failure FailureBr general
52_1 Phase A Open 52_2 Phase A Open OpenBr phsA
52_1 Phase A Closed 52_2 Phase A Closed CloseBr phsA
52_1 Phase A Undetermined 52_2 Phase A Undetermined UndetBr phsA
52_1 Phase A Failure 52_2 Phase A Failure FailureBr phsA
52_1 Phase B Open 52_2 Phase B Open OpenBr phsB
52_1 Phase B Closed 52_2 Phase B Closed CloseBr phsB
52_1 Phase B Undetermined 52_2 Phase B Undetermined UndetBr phsB
52_1 Phase B Failure 52_2 Phase B Failure FailureBr phsB
52_1 Phase C Open 52_2 Phase C Open OpenBr phsC
52_1 Phase C Closed 52_2 Phase C Closed CloseBr phsC
52_1 Phase C Undetermined 52_2 Phase C Undetermined UndetBr phsC
52_1 Phase C Failure 52_2 Phase C Failure FailureBr phsC
52_1 Undetermined 52_2 Undetermined Pos stVal
52_1 Open 52_2 Open Pos OpenBr
52_1 Closed 52_2 Closed Pos CloseBr
52_1 Failure 52_2 Failure Pos FailureBr
52_1 Closed (Simple Log.) 52_2 Closed (Simple Log.) BrDISt general
52_1 A Closed (Simple Log.) 52_2 A Closed (Simple Log.) BrDISt phsA
52_1 B Closed (Simple Log.) 52_2 B Closed (Simple Log.) BrDISt phsB
52_1 C Closed (Simple Log.) 52_2 C Closed (Simple Log.) BrDISt phsC
Close Command - Breaker 1 Close Command - Breaker 2 OpCls general
Open Command - Breaker 1 Open Command - Breaker 2 OpOpn general
Ph. A Open Command - Br1 Ph. A Open Command - Br2 OpOpn phsA
Ph. B Open Command - Br1 Ph. B Open Command - Br2 OpOpn phsB
Ph. C Open Command - Br1 Ph. C Open Command - Br2 OpOpn phsC
Close Failure - Br1 Close Failure - Br2 ClsFailBr general
Ph. A Close Failure- Br1 Ph. A Close Failure- Br2 ClsFailBr phsA
Ph. B Close Failure- Br1 Ph. B Close Failure- Br2 ClsFailBr phsB
Ph. C Close Failure- Br1 Ph. C Close Failure- Br2 ClsFailBr phsC
Open Failure - Br1 Open Failure - Br2 OpenFailBr general
Ph. A Open Failure- Br1 Ph. A Open Failure- Br2 OpenFailBr phsA
Ph. B Open Failure- Br1 Ph. B Open Failure- Br2 OpenFailBr phsB
Ph. C Open Failure- Br1 Ph. C Open Failure- Br2 OpenFailBr phsC
Open Blocked - Br1 Open Blocked - Br1 BrBlk general
Closing Blocked - Br1 Closing Blocked - Br1 BrClBlk general
Breaker settings error Error general

4.1.2 Breaker failure and operating logic


The opening and closure failure time settings determine the time lapse between the issue of the corresponding command and the
reception of the breaker’s activity signal, on the understanding that the breaker has acted correctly. To the contrary, the open
failure and closure failure signals are generated and failure and general indications are issued.

This unit’s settings are grouped in PROT/RBFS1 (breaker 1) and (PROT/RBFS2) logical nodes:

❑ Open failure time (ms): If an open command is given, the breaker should be open before this time.
❑ Close failure time (ms): If a close command is given, the breaker should be closed before this time.
❑ Enable Events record: Allows the generation of protection events associated to the function. If set to “NO”, the function’s
protection events are not generated. If set to “YES”, the function’s specific mask is contemplated.
Table 122 shows the operating logic’s output Data, which are available in the PROT/XCBR nodes.

Ingeteam Power Technology S.A.


User Manual 217
BREAKER

Table 123 Breaker status monitoring settings

Data Setting Min. Max. Step Remarks Type


OpTmms Open failure time (ms) 20 100000 1 Int32
ClTmms Close failure time (ms) 20 100000 1 Int32
MaskEna Enable Events Record NO / YES Boolean

4.1.3 Locking logic


The trip and close commands can be locked with the breaker status, depending on the configuration of the trip sealing and closure
sealing settings. Figure 146 and Figure 147 show the sealed trip and closure schemes. The general trip signals have a minimun time
duration set in "Min.time general trip(ms)". 19

Figure 146 Trip logic scheme shows Trip logic scheme. The input signals of this scheme are:

❑ Trip Sealed 52-1: Setting that indicates whether trip will be sealed after completing trip conditions and manual opening.
Corresponds to XCBR setting "Trip sealed".
❑ General Trip: Corresponds to the signal "General trip" generated with any trip.
❑ Pole A (B,C) General Trip: Corresponds to the signals "Pole A General Trip", (B, C) generated with any phase trip.
❑ Manual open command input**: Indicates that open command has been generated by the logic input "Open Command -
Breaker 1" or by user command.
❑ Manual Open blocking: Indicates that blocking command has been generated by the logic input "Open blocking" or by user
command.
❑ 52a pole A: Enabled indicates that phase A is closed. Corresponds to the signal "52_1 A Closed (Simple Log.)".
❑ 52a pole B: Enabled indicates that phase B is closed. Corresponds to the signal "52_1 B Closed (Simple Log.)".
❑ 52a pole C: Enabled indicates that phase C is closed. Corresponds to the signal "52_1 C Closed (Simple Log.)".

Ingeteam Power Technology S.A.


User Manual 218
BREAKER

Figure 146 Trip logic scheme

Figure 147 shows Closure logic scheme. The input signals of this scheme are:

❑ General trip: Indicates the signal generated with any trip. It is shown in "General trip".
❑ Manual open command: Internal signal indicating that open command has been generated by the logic input "Breaker
open command input" or by user command, and is not blocked by the logic input "Open blocking" neither by user
command.
❑ Close sealed: Setting that indicates whether will be sealed after completing the close order. Corresponds to the XCBR
"Close sealed" setting.
❑ RECLOSURE Command**: Internal signal indicating an OR of the reclosure commands. They are displayed on signals "52_1
Reclose Command" (switch reclosure) and "Reclosing Command F_RREC" (frequency reclosure). It should not be blocked
by the logic input "Close Blocked" neither by user command.
❑ Close command: Indicates the logic input "Close Command - Breaker" is enabled, a closure order has been launched by
user command or a close order coupling. Formerly sincrocheck's "Perm. Manual Close" must be enabled and must not be
blocked by the logic input "Close blocking" neither by user command.
❑ 52_1 closed: Signal indicating that switch is closed. Corresponds to the "52_1 Closed (Simple Log.)" signal.
❑ 52_1A closed: Signal indicating that phase A is closed. Corresponds to the "52_1 A Closed (Simple Log.)" signal.
❑ 52_1B closed: Signal indicating that phase B is closed. Corresponds to the "52_1 B Closed (Simple Log.)" signal.
❑ 52_1C closed: Signal indicating that phase C is closed. Corresponds to the "52_1 C Closed (Simple Log.)" signal.

Ingeteam Power Technology S.A.


User Manual 219
BREAKER

Figure 147 Closure logic scheme

4.1.4 Open pole detector


It determines the open pole or poles using the digital inputs, current and/or voltage measurement.

In order for a pole to be considered open, a combination of the following conditions must be met (depending on the operation type
setting):

❑ A phase’s breakers indicate that the phase is open (in the case of 1 ½ breaker, two are employed)
❑ The current is below the threshold set in the open pole due to current detection logic.
❑ The current and the voltage are below the threshold (according to the setting). In this case, if there is a fuse failure the
open pole due to voltage signal is not activated.
To determine the breaker’s status by digital input, the 52b (normally closed) of each phase is employed, when configured. If the
52b is not configured, the 52a is used (normally open).

If a single pole open is detected, the following functions can be blocked, if they are selected by settings:

❑ Neutral overcurrent, sensitive neutral and unbalance.


❑ Overvoltage V0 and V2.
There is a delay of one cycle before the reset of the 3PO output (three open pole). Therefore, there is also a one-cycle delay in the
change from 3PO to 1PO (1 open pole).

There is a delay of one cycle before the reset of the 1PO output (when the breaker closes).

Figure 148 shows Open pole detector scheme. The input signals of this scheme are:

❑ 52_1A Closed: Signal indicating that phase A is closed. Corresponds to the "52_1 A Closed (Simple Log.)" signal.
❑ 52_1 Closed: Signal indicating that switch is closed. Corresponds to the "52_1 Closed (Simple Log.)" signal.
❑ 52_1 Blocked: Internal signal indicating that switch is blocked by the breaker 1 logical input "Close blocking" or by a
blocking user command.
❑ 52_2A Closed: Signal indicating that phase A is closed. Corresponds to the "52_2 A Closed (Simple Log.)" signal.
❑ 52_2 Closed: Signal indicating that switch is closed. Corresponds to the "52_2 Closed (Simple Log.)" signal.

Ingeteam Power Technology S.A.


User Manual 220
BREAKER

❑ 52_2 Blocked: Internal signal indicating that switch is blocked by the breaker 2 logical input "Close blocking" or by a
blocking user command.
❑ Configuration type = Breaker and a Half: Setting that allows to select switches configuration schemes. Corresponds to the
setting "Configuration type".
❑ Phase A Open ( I < ): Signal "Phase A Open ( I < )".
❑ DeadLine Phase A: Signal indicating that phase A is de-energized. Corresponds to "Deadline Phase A" signal.
And their equivalents for phases B and C.
Figure 148 Open pole detector scheme

The settings for the configuration of the open pole detector are shown in Table 124 Open pole detector settings

❑ Enabled: Enables the open pole detector function.


❑ Operation type. Indicates the manner in which the open pole is detected:
 V and I. The voltage and current conditions must be met.
 I and 52. The current and 52 status input conditions must be met.
 V and I and 52. The voltage and current and 52 status input conditions must be met.
 V and I or 52. The voltage and current or the 52 status input conditions must be met.
 Only 52. The 52 status input conditions must be met.
❑ Voltage threshold. Indicates the voltage value below which the phase is considered as broken.
❑ Current threshold. Indicates the current value below which the phase is considered as open.
❑ Neutral and Unbalance Units Block. Indicates whether the unbalance and neutral units are to be blocked upon the
detection of an open pole.
❑ Blocking Input. Selects the signal which, when active, blocks the open pole detector function.

Ingeteam Power Technology S.A.


User Manual 221
BREAKER

❑ Enable Events record. Allows the generation of protection events associated to the function. If set to “NO”, the function’s
protection events are not generated. If set to “YES”, the function’s specific mask is contemplated.
Table 124 Open pole detector settings

Name IEC 61850 Setting Minimum Maximum Step Remarks Type


OPDEna Enabled NO / YES enum
V and I (1)
I and 52 (2)
Optype Operation type V and I and 52 (3) enum
V and I or 52 (4)
Only 52 (5)
OpValV Voltage threshold (V) 10,0 165,0 0,1 floating
OpValI Current threshold (A) 0,01 0,5 0,01 floating
UnbUnBl Neutral and Unbalance Units Block NO / YES Boolean
LogInBlk Blocking input Int32
MaskEna Enable Events record NO / YES Boolean

It has independent settings, commands and outputs:

❑ PROT/POPD1 node
❑ Settings and logical inputs. There are 6 settings tables. See Table 124.
❑ Commands:
 “DOrdBlk”: Function block and unblocking. Only acts if the unit is enabled.
❑ Outputs: Table 125 shows the function’s output data.
 Open Pole Status. It is active when enabled and not blocked.
 Pole A Open. Indicates that the open pole conditions have been met in phase A.
 Pole B Open. Indicates that the open pole conditions have been met in phase B.
 Pole C Open. Indicates that the open pole conditions have been met in phase C.
 1PO- One Pole Open. Indicates that there is only one pole open (A, B or C).
 2PO- Two Pole Open. Indicates that there are two poles open.
 3PO- Three Pole Open. Indicates that there are three poles open.
 PO-Some Pole Open. Indicates that at least one pole is open, but not all three.
 Phase A Open ( I < ). Indicates that the phase A current is below the threshold.
 Phase B open ( I < ). Indicates that the phase B current is below the threshold.
 Phase C open ( I < ). Indicates that the phase C current is below the threshold.
 Deadline Phase A. Indicates that pole A is de-energized.
 Deadline Phase B. Indicates that pole B is de-energized.
 Deadline Phase C. Indicates that pole C is de-energized.
 Deadline Phase ABC. Indicates that the three poles are de-energized.

Ingeteam Power Technology S.A.


User Manual 222
BREAKER

Table 125 Open pole detector outputs

Signal Data Attribute


Open Pole Status StEna stVal
Pole A Open OpenPole phsA
Pole B Open OpenPole phsB
Pole C Open OpenPole phsC
1PO- One Pole Open OneOpenPole general
2PO- Two Pole Open TwoOpenPole general
3PO- Three Pole Open ThreeOpenPole general
PO-Some Pole Open OpenPole general
Phase A Open ( I < ) OpenPhs phsA
Phase B Open ( I < ) OpenPhs phsB
Phase C Open ( I < ) OpenPhs phsC
Deadline Phase A DeadLine phsA
Deadline Phase B DeadLine phsB
Deadline Phase C DeadLine phsC
Deadline Phase ABC DeadLine general

4.1.4.1 Open pole due to current


This is used to detect the breaker status with the current measurement. Using the half- and full-cycle DFT measurements (the
lower of the two), it is determined whether the current is below a minimum noise threshold in at least one of the phases (see
Figure 149)

If the open pole detection is activated in at least one of the phases, the phases overcurrent instantaneous units are reset.

The current threshold is indicated in the open pole detector (PROT/POPD).

The output signals are in the PROT/POPD node (see Table 125):

❑ Phase A Open ( I < ). Indicates that the phase A current is below the threshold.
❑ Phase B open ( I < ). Indicates that the phase B current is below the threshold.
❑ Phase C open ( I < ). Indicates that the phase C current is below the threshold.
Figure 149 Open pole due to current scheme

ANALOGUE INPUT
DIGITAL SIGNAL
IA (min (dft,dft ½)) +
< Phase A Open ( I < )
SETTING -

Current threshold (A)

ANALOGUE INPUT
DIGITAL SIGNAL
IB (min (dft,dft ½)) +
-
< Phase B Open ( I < )

DIGITAL SIGNAL
ANALOGUE INPUT +
< Phase C Open ( I < )
IC (min (dft,dft ½)) -

4.1.4.2 Dead or de-energized line


It detects a line’s disconnected phases. If a phase’s voltage and current levels simultaneously drop below the voltage and
current thresholds, this phase is considered dead. In such cases, the following signal is generated for each phase: "Deadline
Phase x", in which x is A, B or C. Figure 150 shows a diagram of the dead line. The voltage and current thresholds are as
indicated in the open pole detector (PROT/POPD).

The output signals are in the PROT/POPD node (see Table 125):

❑ Deadline Phase A. Indicates that pole A is de-energized.


❑ Deadline Phase B. Indicates that pole B is de-energized.

Ingeteam Power Technology S.A.


User Manual 223
BREAKER

❑ Deadline Phase C. Indicates that pole C is de-energized.


❑ Deadline Phase ABC. Indicates that the three poles are de-energized.

Figure 150 Dead line scheme

4.1.5 Pole discordance


If any of the poles are detected as having a status different to that of the other poles during a configurable period of time, the pole
discordance signal is generated. A differentiation is made between single open pole discordance and two open pole discordance. A
trip can be generated or the action can be limited to signalling. It allows a selection to be made between two modes of operation
(see Figure 151 and Figure 152).

Input signals of this scheme are:

❑ 52_1 failure: Indicates that 52 is in fault because "Pole failure time (ms)" time has been exceeded. Corresponds to "52_1
Failure" signal.
❑ 52_1 phase A open: Signal indicating that switch is closed. Corresponds to the "52_1 A Closed (Simple Log.)" signal
deactivated.
❑ 52_1 phase B open: Signal indicating that switch is closed. Corresponds to the "52_1 B Closed (Simple Log.)" signal
deactivated.
❑ 52_1 phase C open: Signal indicating that switch is closed. Corresponds to the "52_1 C Closed (Simple Log.)" signal
deactivated.
Equivalent signals are used in switch 2.

Ingeteam Power Technology S.A.


User Manual 224
BREAKER

Figure 151 Mode 1 pole discordance

Figure 152 Mode 2 pole discordance

The settings for the configuration of this unit are shown in Table 126.

❑ Enabled: Enables the open pole detector function.


❑ Operation type. Indicates the unit’s operation type.
 M1: Signaling
 M1: Signal and Trip
 M2: Signaling
 M2: Signal and Trip
❑ 1 pole open time (ms). Time for the discordance activation with 1 open pole.
❑ 2 pole open time (ms). Time for the discordance activation with 2 open poles.
❑ Blocking input. Selects the signal which, when active, blocks the function.
❑ Enable Events record. Allows the generation of protection events associated to the function. If set to “NO”, the function’s
protection events are not generated. If set to “YES”, the function’s specific mask is contemplated.

Table 126 Pole discordance settings

Name IEC 61850 Setting Minimum Maximum Step Remarks Type


PDEna Enabled NO / YES enum
M1: Signaling
M1: Signal and Trip
Optype Operation type enum
M2: Signaling
M2: Signal and Trip
PTmms1 1 pole open time (ms 100 60000 10 Int32
PTmms2 2 pole open time (ms 100 60000 10 Int32
LogInBlk Blocking input Int32
MaskEna Enable Events Record NO / YES Boolean

Ingeteam Power Technology S.A.


User Manual 225
BREAKER

It has independent settings, commands and outputs:

❑ Node:
 PROT/RPLD1 for Breaker 1.
 PROT/RPLD2 for Breaker 2.
❑ Settings and logical inputs. There are 6 settings tables.
❑ Commands:
 “DOrdBlk”: Function block and unblocking. Only acts if the unit is enabled.
❑ Outputs: Table 127 Pole discordance outputs shows the function’s output data.
 Pole Discordance Status. It is active when enabled and not blocked.
 52_1 Start Discordance. Indicates that the function has started.
 52_1 Trip Discordance. Indicates that the function has tripped.
 52_1 Discordance open 1P. Indicates that there is discordance with only one open pole.
 52_1 Discordance open 2P. Indicates that there is discordance with two open poles.
Table 127 Pole discordance outputs

Signal Data Attribute


Pole Discordance Status StEna stVal
52_1 Start Discordance StrPDBr1 general
52_1 Trip Discordance OpPDBr1 general
52_1 Discordance open 1P OneOpenBr1 general
52_1 Discordance open 2P TwoOpenBr1 general

4.2 BREAKER OPERATION SUPERVISION

It monitors the breaker’s operations after the trip and closure commands. In addition to signals, the counters generated by these
functions are shown in the statistical data.

In breaker and a half configurations two breakers are supervised:

❑ In models, where there is only one current input, ki2 and electrical supervisions are only performed on breaker 1. In
breaker 2 only mechanical operations are supervised. See Table 128 (breaker 1) and Tabla 129 (breaker 2) for settings and
Table 130 and Table 131 for signals.
❑ In models, where there are two current inputs, ki2 and electrical supervisions are performed on both breakers. See Table
128 and Table 130 for both breakers.

The settings for the configuration of this unit are shown in Table 128 (breaker 1) and Tabla 129 (breaker 2):

❑ ki2 calculation type. Indicates the calculation type between kI2*t, kI2 and kI.
❑ ki2 time (ms). Indicates the timeout following the trip for the measurement of the ki1 calculation current.
❑ Alarm value ki2. Indicates the ki2 summation threshold which, when exceeded, generates a “ki2 exceeded” signal.
❑ Initial value ki2. Indicates the initial value of the ki2 summation when a reset command is received.
❑ Trips exceeded window (min). Time window in minutes for the excessive number of trips counter.
❑ Maximum number of trips. Maximum number of trips permitted in the set time window.
❑ Mechanical opening T (ms). Indicates the maximum time as of the opening command until the detection of the open pole
by the digital input status.
❑ Mechanical closing T (ms). Indicates the maximum time as of the closure command until the detection of the closed pole
by the digital input status.

Ingeteam Power Technology S.A.


User Manual 226
BREAKER

❑ Electrical opening T (ms). Indicates the maximum time as of the opening command until the detection of the absence of
current in the phase.
❑ Electrical closing T (ms). Indicates the maximum time as of the closure command until the detection of the presence of
current in the phase.
❑ Inactivity time (days). Indicates the maximum number of days without breaker activity.
❑ Opening dispersion T (ms). Indicates the maximum dispersion time between two poles upon opening.
❑ Closing dispersion T (ms). Indicates the maximum dispersion time between two poles upon closing.
❑ Enable Events record. Allows the generation of protection events associated to the function. If set to “NO”, the function’s
protection events are not generated. If set to “YES”, the function’s specific mask is contemplated.

There are independent settings and outputs:

❑ Node
 PROT/CBOU1 for Breaker 1.
 PROT/CBOU2 for Breaker 2.
❑ Settings. There are 6 settings tables. See Table 128 and Tabla 129.
❑ Outputs: Table 130 shows the function’s output data. The meaning of each signal is detailed in the function explanation.

Table 128 Operation monitoring settings (All settings)

Data Setting Min Max Step Remarks Type


Ki2 (0)
KIType ki2 calculation type 0 2 1 KI (1) enum
KI2t (2)
KITmms ki2 time (ms) 0 100 10 Int32
KIAlarm Alarm value ki2 0 100000 1 Int32
KIInit Initial value ki2 0 100000 1 Int32
ExTrTmm Trips exceeded window (min) 1 60 1 Int32
ExTrNum Maximum number of trips 0 500 1 Int32
OpMeTmms Mechanical opening T (ms) 0 5000 1 Int32
ClMeTmms Mechanical closing T (ms) 0 5000 1 Int32
OpElTmms Electrical opening T (ms) 0 5000 1 Int32
ClElTmms Electrical closing T (ms) 0 5000 1 Int32
NoOpDays Inactivity time (days) 0 10000 1 Int32
OpDisTmms Opening dispersion T (ms) 0 1000 1 Int32
ClDisTmms Closing dispersion T (ms) 0 1000 1 Int32
MaskEna Enable Events record 0 1 1 NO / YES Boolean

Tabla 129 Operation monitoring settings in Breaker 2 (models with one current input)

Data Setting Min Max Step Remarks Type


ExTrTmm Trips exceeded window (min) 1 60 1 Int32
ExTrNum Maximum number of trips 0 500 1 Int32
OpMeTmms Mechanical opening T (ms) 0 5000 1 Int32
ClMeTmms Mechanical closing T (ms) 0 5000 1 Int32
NoOpDays Inactivity time (days) 0 10000 1 Int32
OpDisTmms Opening dispersion T (ms) 0 1000 1 Int32
ClDisTmms Closing dispersion T (ms) 0 1000 1 Int32
MaskEna Enable Events record 0 1 1 NO / YES Boolean

Ingeteam Power Technology S.A.


User Manual 227
BREAKER

Table 130 Breaker monitoring signals

Signal Data Attribute


Phase A ki2 exceeded KI2 phsA
Phase B ki2 exceeded KI2 phsB
Phase C ki2 exceeded KI2 phsC
ki2 exceeded KI2 general
Maximum ki2 exceeded MaxKI2 general
Pole A mechan.time exceeded MechTmExc phsA
Pole B mechan.time exceeded MechTmExc phsB
Pole C mechan.time exceeded MechTmExc phsC
Pole A electric time exceeded ElecTmExc phsA
Pole B electric time exceeded ElecTmExc phsB
Pole C electric time exceeded ElecTmExc phsC
Pole A inactivity time exceeded NoOpTmExc phsA
Pole B inactivity time exceeded NoOpTmExc phsB
Pole C inactivity time exceeded NoOpTmExc phsC
AB dispersion time exceeded DispTmExc (DiTmExcAB in Ed2) phsAB (general in Ed2)
BC dispersion time exceeded DispTmExc (DiTmExcBC in Ed2) phsBC (general in Ed2)
CA dispersion time exceeded DispTmExc (DiTmExcCA in Ed2) phsCA (general in Ed2)
Pole A excessive nbr trips PolTrExc phsA
Pole B excessive nbr trips PolTrExc phsB
Pole C excessive nbr trips PolTrExc phsC
Excessive nbr trips PolTrExc general

Table 131 Monitoring signals in Breaker 2 (models with one current input)

Signal Data Attribute


Pole A mechan.time exceeded MechTmExc phsA
Pole B mechan.time exceeded MechTmExc phsB
Pole C mechan.time exceeded MechTmExc phsC
Pole A inactivity time exceeded NoOpTmExc phsA
Pole B inactivity time exceeded NoOpTmExc phsB
Pole C inactivity time exceeded NoOpTmExc phsC
AB dispersion time exceeded DispTmExc (DiTmExcAB in Ed2) phsAB (general in Ed2)
BC dispersion time exceeded DispTmExc (DiTmExcBC in Ed2) phsBC (general in Ed2)
CA dispersion time exceeded DispTmExc (DiTmExcCA in Ed2) phsCA (general in Ed2)
Pole A excessive nbr trips PolTrExc phsA
Pole B excessive nbr trips PolTrExc phsB
Pole C excessive nbr trips PolTrExc phsC
Excessive nbr trips PolTrExc general

kI2 sum:

After a trip, the kI2 counter increases in accordance with the selected setting. The value of each phase’s current is calculated in
primary (VT ratio), as kA primary. There are a total of 3 counters (one for each phase). Additionally20, it is available a counter of
maximun kI2, where in each opening the maximum value of the three phases is used to calculate the ki2.

If it exceeds the set threshold (the treatment is pole to pole), a “Phase X Ki2 exceeded” signal is generated. While in this situation, the
corresponding signal is sent to control. The signals are:

❑ Phase X ki2 exceeded. Where X is the phase. It is independent for each phase.
❑ ki2 exceeded. One for all the phases.
❑ Maxki2 exceeded. Activated when the counter of maximun kI2 exceeds the set threshold.
In order to calculate the pole wear, the type of calculation wanted can be programmed from among kI2*t, kI2 and kI.

❑ If Ki2 is chosen, the kA2 are calculated with I as the current measured after exceeding the set timeout following the trip.
❑ If kI is chosen, only the sum of the currents in kA is calculated, with I as the current measured after exceeding the set timeout
following the trip.

20
Available from version 5.24.16.1 of firmware and 7.0.0.0 of ICD.

Ingeteam Power Technology S.A.


User Manual 228
BREAKER

❑ If Ki2 *t is chosen, the Ki2 /100 value is accumulated every 10ms, with I as the current measured after exceeding the set timeout
following the trip. The accumulation terminates when I<0.05 A.
Excessive number of trips:

It counts the trips produced in the time, generating a signal when the number of trips is higher than the programmed number during
the programmed time and changes to a definite trip. The time period is reset upon a manual closure. The counter may be reset to the
initial value at any moment by means of a command. The signals are:

❑ Pole X excessive nbr trips. Independent for each phase


❑ Excessive nbr trips. One for all the phases.
Open counter:

There are independent open and trip counters for each phase:

❑ The trip commands generated by the protection are considered trips.


❑ A breaker's changes from closed to open (including manual and trip openings) are considered openings.
There are 6 counters: 3 trip counters and 3 open counters. There is a reset command for each counter.

Closure counters:

There are independent closure counters for each phase. A breaker's changes from open to close are considered closures.

There is a reset command for each counter.

Operating time for electric opening and closure by pole:

They count the time elapsed from the command sent to the breaker unto its electric operation, measured with the current:

❑ Trip time: The time elapsed from the open command until the detection of the absence of power.
❑ Closure time: The time elapsed from the closure command until the detection of the presence of power.
The open pole detector current threshold is used.

These times are compared with the threshold settings. Events are generated per pole when the thresholds are exceeded “Pole X
electric time exceeded”:

❑ If the time elapsed from the open command exceeds the setting “Electrical opening T (ms)”
❑ If the time elapsed from the closure command exceeds the setting “Electrical closing T (ms)”
Mechanical opening and closure operating time per pole:

They count the time elapsed from the command sent to the breaker unto its mechanical operation, detected in the digital inputs
status:

❑ Trip time: Indicates the time elapsed as of the opening command until the detection of the open pole by the digital input status.
❑ Closure time: Indicates the time elapsed as of the closure command until the detection of the closed pole by the digital input
status.
These times are compared with the threshold settings. Events are generated per pole when the thresholds are exceeded “Pole X
mechan.time exceeded”:

❑ If the time elapsed from the open command exceeds the setting “Mechanical opening T (ms)”
❑ If the time elapsed from the closure command exceeds the setting “Mechanical closing T (ms)”
Opening and closure dispersion time for each pole pair:

They count the difference between the opening and closure times for every two poles. There are opening/closure counters for pole
pairs AB, BC and CA. The breaker status is determined by means of the digital input status.

These times are compared with the threshold settings. Events are generated per pole when the thresholds are exceeded “XY dispersion
time exceeded”:

❑ During the opening, a comparison is made with the "Opening dispersion T (ms)" setting.
❑ During the closure, a comparison is made with the "Closing dispersion T (ms)" setting.

Ingeteam Power Technology S.A.


User Manual 229
BREAKER

Days of breaker inactivity without status change:

The days elapsed, since the last opening or closure of the breaker, are counted for each pole. Complete fractions of 24 hours since the
last action are considered. Partial periods of 24 hours are not accumulated, i.e., if 2 days and 20 hours have passed since the last action,
the counter will indicate 2 days. If at this point the time count is reset to zero, the 20 hours would be lost.

These counters are compared with the “Inactivity Time (days)” setting and an event is generated per pole in the event of it being
exceeded "Pole X inactivity time exceeded".

Last interrupted current:

The current value upon the trip is indicated per pole.

Maximum interrupted current:

The maximum current value measured at the moment of the trip is indicated per pole. The three poles can be reset to zero using the
reset command.

Overcurrent levels:

Indicates the time in seconds during which each phase's current is within each of the following ranges (with In as the set rated current):

❑ Seconds with the current between 2 and 5 times In


❑ Seconds with the current between 5 and 12.5 times In
❑ Seconds with the current between 12.5 and 20 times In
❑ Seconds with the current greater than 20 In
There are 12 counters (4 for each phase).

4.3 TRIP AND CLOSE CIRCUITS SUPERVISION

It monitors the circuits by pole, detecting any discontinuity with the breaker open and closed. It requires the assignment of the
monitoring inputs (the breaker circuit with open and closed breaker, the closure circuit with open and closed breaker). It is activated 20
seconds after the detection of the fault and remains active while the fault persists.

Up to six trip circuits and three closure circuits can be monitored, using the number of digital inputs required.

Figure 153 Closure circuit monitoring Figure 153 shows an example of the wiring for the monitoring of the closure circuit. The wiring for
the trip circuit is similar.

When the breaker is closed, the “52a” contact is also closed. If there is continuity in the circuit, the input programmed as “Close circuit
52 closed” is detected as closed. If there is no continuity, it is detected as open (circuit failure).

When the breaker is open, the “52b” contact is also closed. If there is continuity in the circuit, the input programmed as “Close circuit
52 open” is detected as closed. If there is no continuity, it is detected as open (circuit failure).

The “closing coil failure” or “trip coil failure” signals are activated 20 seconds after the fault is detected, in the event of the fault
persisting upon the conclusion of this period.

Ingeteam Power Technology S.A.


User Manual 230
BREAKER

Figure 153 Closure circuit monitoring

The settings for the configuration of this unit are shown in Table 132:
❑ Trip circuit enabled: Enables the monitoring of the trip circuits.
❑ Close circuit enabled: Enables the monitoring of the closure circuits.
❑ Close circuit 52 open - X. Indicates the signal used to monitor the closure circuit with the breaker open.
❑ Close circuit 52 closed - X. Indicates the signal used to monitor the closure circuit with the breaker closed.
❑ Open circuit 52 open - X. Indicates the signal used to monitor the trip circuit with the breaker open.
❑ Open circuit 52 closed - X. Indicates the signal used to monitor the trip circuit with the breaker closed.
❑ Enable Events record. Allows the generation of protection events associated to the function. If set to “NO”, the function’s
protection events are not generated. If set to “YES”, the function’s specific mask is contemplated.

It has independent settings, commands and outputs:

❑ Node.
 PROT/RBCS1: breaker1's circuit supervision.
 PROT/RBCS2: breaker 2's circuit supervision.
❑ Settings and logical inputs. There are 6 settings tables. See Table 132.
❑ Outputs: Table 133 shows the function’s output data.
 X trip coil failure. Indicates that there has been failure in the pole X trip coil.
 X closing coil failure. Indicates that there has been failure in the pole X closure coil.
 1 trip circuit failure. Indicates that there has been failure in the trip coil of pole A1, B1 or C1.
 2 trip circuit failure. Indicates that there has been failure in the trip coil of pole A2, B2 or C2.
 1 closing circuit failure. Indicates that there has been failure in the closure coil of pole A1, B1 or C1.
 2 closing circuit failure. Indicates that there has been failure in the closure coil of pole A2, B2 or C2.

Ingeteam Power Technology S.A.


User Manual 231
BREAKER

Table 132 Circuit supervision settings

Data Setting Min. Max. Step Remarks Type


TCEna Trip circuit enabled Boolean
CCEna Close circuit enabled Boolean
LogInCCOA1 Close circuit 52 open - A1 Int32
LogInCCOB1 Close circuit 52 open - B1 Int32
LogInCCOC1 Close circuit 52 open - C1 Int32
LogInCCOA2 Close circuit 52 open - A2 Int32
LogInCCOB2 Close circuit 52 open - B2 Int32
LogInCCOC2 Close circuit 52 open - C2 Int32
LogInCCCA1 Close circuit 52 closed - A1 Int32
LogInCCCB1 Close circuit 52 closed - B1 Int32
LogInCCCC1 Close circuit 52 closed - C1 Int32
LogInCCCA2 Close circuit 52 closed - A2 Int32
LogInCCCB2 Close circuit 52 closed - B2 Int32
LogInCCCC2 Close circuit 52 closed - C2 Int32
LogInTCOA1 Open circuit 52 open - A1 Int32
LogInTCOB1 Open circuit 52 open - B1 Int32
LogInTCOC1 Open circuit 52 open - C1 Int32
LogInTCOA2 Open circuit 52 open - A2 Int32
LogInTCOB2 Open circuit 52 open - B2 Int32
LogInTCOC2 Open circuit 52 open - C2 Int32
LogInTCCA1 Open circuit 52 closed - A1 Int32
LogInTCCB1 Open circuit 52 closed - B1 Int32
LogInTCCC1 Open circuit 52 closed - C1 Int32
LogInTCCA2 Open circuit 52 closed - A2 Int32
LogInTCCB2 Open circuit 52 closed - B2 Int32
LogInTCCC2 Open circuit 52 closed - C2 Int32
MaskEna Enable Events record NO / YES Boolean

Table 133 Coil monitoring outputs

RBCS1 Signals RBCS2 Signals Data Attribute


A1 trip coil failure A1 trip coil failure Br2 FailTC1 phsA
B1 trip coil failure B1 trip coil failure Br2 FailTC1 phsB
C1 trip coil failure C1 trip coil failure Br2 FailTC1 phsC
A2 trip coil failure A2 trip coil failure Br2 FailTC2 phsA
B2 trip coil failure B2 trip coil failure Br2 FailTC2 phsB
C2 trip coil failure C2 trip coil failure Br2 FailTC2 phsC
A1 closing coil failure A1 closing coil failure Br2 FailCC1 phsA
B1 closing coil failure B1 closing coil failure Br2 FailCC1 phsB
C1 closing coil failure C1 closing coil failure Br2 FailCC1 phsC
A2 closing coil failure A2 closing coil failure Br2 FailCC2 phsA
B2 closing coil failure B2 closing coil failure Br2 FailCC2 phsB
C2 closing coil failure C2 closing coil failure Br2 FailCC2 phsC
1 trip circuit failure 1 trip circuit failure Br2 FailTC1 general
2 trip circuit failure 2 trip circuit failure Br2 FailTC2 general
1 closing circuit failure 1 closing circuit failure Br2 FailCC1 general
2 closing circuit failure 2 closing circuit failure Br2 FailCC2 general

Ingeteam Power Technology S.A.


User Manual 232
DISCONNECTOR

5. DISCONNECTOR
The disconnector unit uses the PROT/XSWI1 logical node. The settings used are:

❑ Disconnector type: Indicates the type of disconnector employed:


 1 or 2 DI.General Status. Only one input is used for the status of the three poles.
 3 or 6 DI.Per Pole. An independent input is used for the status of each of the three poles.
❑ 89a input: If the disconnector type is "1 or 2 DI.General Status", it indicates the disconnector status.
❑ 89a-Pole A: If the disconnector type is "3 or 6 DI.Per Pole", it indicates the phase A disconnector status.
❑ 89a-Pole B: The same as phase A, but for B.
❑ 89a-Pole C: The same as phase A, but for C.
❑ 89b input: If the disconnector type is "1 or 2 DI.General Status", it indicates the disconnector status.
❑ 89b-Pole A: If the disconnector type is "3 or 6 DI.Per Pole", it indicates the phase A disconnector status.
❑ 89b-Pole B: The same as phase A, but for B.
❑ 89b-Pole C: The same as phase A, but for C.
❑ Enable Events record: Allows the generation of protection events associated to the function. If set to “NO”, the
function’s protection events are not generated. If set to “YES”, the function’s specific mask is contemplated.

Table 134 Disconnector status settings

Data Setting Min. Max. Step Remarks Type


1 or 2 DI.General Status
BrTyp Disconnector type enum
3 or 6 DI.Per Pole
LogIn89a1 89a general status Int32
LogIn89a1A 89a Pole A status Int32
LogIn89a1B 89a Pole B status Int32
LogIn89a1C 89a Pole C status Int32
LogIn89b1 89b general status Int32
LogIn89b1A 89b Pole A status Int32
LogIn89b1B 89b Pole B status Int32
LogIn89b1C 89b Pole C status Int32
MaskEna Enable Events Record NO / YES Boolean

Disconnector status

The status of the general disconnector and by pole is determined with the status of digital inputs and disconnector type setting.
Used to determine the status of the disconnector without uncertainty and employed in functions that require the disconnector’s
status to be known, such as the stub bus protection, etc.

The 89b status inputs take precedence over the 89a status inputs, i.e., if 89b status inputs have been configured, the disconnector
status is determined by means of these inputs, independently of the status of the 89a inputs.

Depending on the disconnector type setting, the functioning is:

❑ 1 or 2 DI.General Status. The "89b general status" input is used for the disconnector status. If it is not configured, the "89a
general status" input is used. The phase disconnector status matches the general.
❑ 3 or 6 DI.Per Pole. The independent "89b Pole X status" inputs are used for the disconnector status. If they are not
configured, the "89a Pole X status" inputs are used, where "X" indicates the pole (A, B or C). The general disconnector
status is generated from the phases, taking into account the following:
 Closed general status, if all the phases are closed.
 Open general status, if at least one of the phases is open.
Table 135 shows this function’s outputs.

❑ Disconnector 1 Status (DI). Indicates the disconnector's general status, in accordance with the status of the digital inputs.

Ingeteam Power Technology S.A.


User Manual 233
DISCONNECTOR

❑ Disconnector 1 X Status (DI). Indicates the status of each of the disconnector's phases, in accordance with the status of the
digital inputs. Where "X" indicates the pole (A, B or C).
Table 135 Disconnector status outputs

XSWI1 Signal Data Attribute


Disconnector 1 Status (DI) StEna general
Disconnector 1 A Status (DI) StEna phsA
Disconnector 1 B Status (DI) StEna phsB
Disconnector 1 C Status (DI) StEna phsC

Ingeteam Power Technology S.A.


User Manual 234
AUTOMATISMS 

6. AUTOMATISMS
The close command of the breaker can be manual close command or automatic (recloser):

❑ Three poles close command can be monitored by synchronism; while one pole close commands are not monitored by synchronism
❑ Manual close command can be monitored by synchronism

6.1 SYNCHRONISM

The synchronism function or “Synchrocheck” waits for the appropriate conditions established in the settings, to determine breaker
closure, both manual and automatic.

Two voltage signals from the two sides of the breaker, which we will call side A and side B, are compared.

Side A corresponds to the voltage input selected with the setting “Side A Phase Select”. This setting selects the analogue input used.
The selection between ground to phase and phase to phase voltages is made with the setting “Operating Voltages” of the node TVTR.
With this setting a compensation factor is applied to equalize the module and the angle of the two voltages compared (side A and side
B).

Side B corresponds to the analogue voltage input connected to the synchronism voltage terminals.

Table 136 shows the settings of this function for undervoltage and synchronism:

❑ Enabled. Indicates whether the function is enabled or not. When enabled, the function tests the synchronism conditions. When
disabled, manual closure permission is granted, but automatic permission is refused.
❑ Side A phase Select: selectable between A/AB, B/BC or C/CA, corresponding to the measurement of the selected voltage
transformer. A/AB for transformer 10, B/BC for transformer 11 and C/CA for transformer 12.
❑ Compensation factor (Vs1): the factor by which the module is multiplied in order to equalize the voltages.
❑ Compensation angle (Vs1): the factor to be added to the angle in order to equalize the voltages.
❑ A-Side Voltage presence (V): the voltage measured in side A must exceed this value in order to consider that there is voltage on
that side of the breaker.
❑ A-Side Lack of Voltage (V): the voltage measured in side A must be lower than this value in order to consider that there is an
absence of voltage on that side of the breaker. It must be at least 5% less than Voltage presence.
❑ B-Side Voltage presence (V): the voltage measured in side B must exceed this value in order to consider that there is voltage on that
side of the breaker.
❑ B-Side Lack of Voltage (V): the voltage measured in side B must be lower than this value in order to consider that there is an
absence of voltage on that side of the breaker. It must be at least 5% less than Voltage presence.
❑ Autoreclose condition. Indicates the conditions for granting reclosing permission with undervoltage:
 Without permission: under no circumstances will the function grant undervoltage permission
 Not A and Yes B: there must be an absence of voltage on side A and presence of voltage on side B in order for the function to
grant undervoltage permission.
 Yes A and Not B: there must be an absence of voltage on side B and presence of voltage on side A in order for the function to
grant undervoltage permission.
 Not A and Not B: there must be an absence of voltage on both sides of the breaker in order for the function to grant
undervoltage permission.
 Not A or Not B: there must be an absence of voltage on one of the sides of the breaker in order for the function to grant
undervoltage permission.
 A xor B: there must be voltage presence on one side of the breaker and an absence on the other in order for the function to
grant undervoltage permission.
 Not A: there must be an absence of voltage on side A in order for the function to grant undervoltage permission.
 Not B: there must be an absence of voltage on side B in order for the function to grant undervoltage permission.
❑ Manual closing condition. Indicates the conditions for granting manual closing permission with undervoltage:

Ingeteam Power Technology S.A.


User Manual 235
AUTOMATISMS 

 Without permission: under no circumstances will the function grant undervoltage permission
 Not A and Yes B: there must be an absence of voltage on side A and presence of voltage on side B in order for the function to
grant undervoltage permission.
 Yes A and Not B: there must be an absence of voltage on side B and presence of voltage on side A in order for the function to
grant undervoltage permission.
 Not A and Not B: there must be an absence of voltage on both sides of the breaker in order for the function to grant
undervoltage permission.
 Not A or Not B: there must be an absence of voltage on one of the sides of the breaker in order for the function to grant
undervoltage permission.
 A xor B: there must be voltage presence on one side of the breaker and an absence on the other in order for the function to
grant undervoltage permission.
 Not A: there must be an absence of voltage on side A in order for the function to grant undervoltage permission.
 Not B: there must be an absence of voltage on side B in order for the function to grant undervoltage permission.
❑ Enabling of synchrocheck with reclosure:
 None: under no circumstances will the function grant synchronism permission.
 No compensation: comparisons between angles, modules and frequencies are taken into account to grant permission if the set
conditions are met during the programmed time
 With compensation: in addition to the module and frequency comparisons, breaker close time is taken into account. See
Figure 154.
 Zero compensation: a specific case of enabling with compensation and also taking into account that closure permission will be
granted when the angle difference is 0°. See Figure 154.
 Always.21 The function grants synchronism permission with present of voltage on both sides of the breaker.
❑ Enabling of synchrocheck with manual closure:
 None: under no circumstances will the function grant synchronism permission.
 No compensation: comparisons between angles, modules and frequencies are taken into account to grant permission if the set
conditions are met during the programmed time
 With compensation: in addition to the module and frequency comparisons, breaker closure time is taken into account. See
Figure 154.
 Zero compensation: a specific case of enabling with compensation and also taking into account that closure permission will be
granted when the argument difference is 0°. See Figure 154.
 Always.21 The function grants synchronism permission with present of voltage on both sides of the breaker.
❑ Breaker close time (s): taken into account when calculating the angle difference and providing that the enabling "with
compensation" has been programmed. In this case, the frequency slip is taken into account to compensate for this time.
❑ Voltage difference (V): the difference between the voltage modules on side A and side B must be less than this value in order for
permission to be granted.
❑ Frequency difference (Hz): the difference between the frequencies on side A and side B must be less than this value in order for
permission to be granted.
❑ Angle difference (º): the difference between the voltage angles on side A and side B must be less than this value in order for
permission to be granted.
❑ Slip threshold (Hz): if the difference between the frequencies in side A and side B is greater than this value there is frequency slip.
Otherwise, it is not considered frequency slip.22
❑ Sync.Time Man.closing(ms): the time during which the conditions for the granting of permission for closure must be met.
❑ Sync. Time Autoreclose(ms): the time during which the conditions for the granting of permission for reclosure must be met.
❑ Blocking input: logic input which, when active, blocks the function. When blocked, manual closure permission is granted, but
automatic permission is refused.
❑ Close blocking: logic input which, when active, blocks the breaker close permission (manual and automatic).

21
Available since firmware version 6.0.18.0 and ICD 8.1.0.0
22
Available since firmware version 5.17.15.2 and ICD 6.1.13.27

Ingeteam Power Technology S.A.


User Manual 236
AUTOMATISMS 

❑ Fuse failure signal: fuse failure logic input which, when active, blocks the breaker close permission (manual and recloser)
❑ A-Side Maximum V. (V)21. To fulfill the synchronism, the side A voltage must be greater than the “A-Side Voltage presence (V)”
setting and below the "A-Side Maximum V" setting. If they are set to the same value, the "A-Side Maximum V" is considered
200V.
❑ B-Side Maximum V. (V)21. To fulfill the synchronism, the side B voltage must be greater than the “B-Side Voltage presence (V)”
setting and below the "B-Side Maximum V" setting. If they are set to the same value, the "B-Side Maximum V" is considered
200V.
❑ A-Side V aux23. It selects the voltage that replaces the synchronization voltage on the A side when the logic input "Side A-V switch"
is activated. The options are:
 Not apply. The option is disabled.
 Vline. It selects the voltage input selected with the setting “Side A Phase Select”.
 Vs1. It selects the voltage input connected to the synchronism voltage terminals Vs1.
 Vs2. It selects the voltage input connected to the synchronism voltage terminals Vs2.
❑ Side A-V switch.23 Logic input which, when active, replaces the line voltage from side A with the one selected in "A-Side V aux".
When the voltage is switched, the compensation factors to be used are those corresponding to the selected voltage. The signal " A
Side V aux selected " is also activated.
❑ B-Side V aux. 23 It selects the voltage that replaces the synchronization voltage on the B side when the logic input " Side B-V switch"
is activated. The options are:
 Not apply. The option is disabled.
 Vline. It selects the voltage input selected with the setting “Side A Phase Select”.
 Vs1. It selects the voltage input connected to the synchronism voltage terminals Vs1.
 Vs2. It selects the voltage input connected to the synchronism voltage terminals Vs2.
❑ Side B-V switch.23 Logic input which, when active, replaces the line voltage from side B with the one selected in "B-Side V aux".
When the voltage is switched, the compensation factors to be used are those corresponding to the selected voltage. The signal “B
Side I1 V aux selected" is also activated.
The synchronism function can be disabled by means of a setting (“NO”). By means of a “fuse failure” or a “breaker closure permission
block” digital input both manual and automatic permission are refused.

When disabled, manual closure permission is granted but not automatic closure permission. In order to give closure permission when
enabled, the function contemplates the conditions that grant undervoltage permission or synchronism permission. If any of them
grants permission, closure permission is granted. Manual and automatic closure permissions are analysed independently.

❑ Undervoltage:
 When disabled undervoltage permission is refused.
 When enabled, undervoltage conditions are analysed. If undervoltage permission is granted, closure permission is granted,
independently of synchronism conditions.
❑ Synchronism: when undervoltage permission is not granted, synchronism conditions are analysed.
 When disabled synchronism permission is refused.
 When enabled, synchronism conditions are analysed.

23
Available since firmware version 6.0.18.2 and ICD 8.2.0.0

Ingeteam Power Technology S.A.


User Manual 237
AUTOMATISMS 

Table 136 Synchronism settings

Data Setting Minimum Maximum Step Remarks Type


SynEna Enabled NO/YES enum
SiASel Side A Phase Select A/AB, B/BC, C/CA enum
CoModVs1 Compensation factor (Vs1) 0.1 3 0.01 float
CoArgVs1 Compensation angle (Vs1) 0 330 30 float
PrVSiA A-Side Voltage presence (V) 10 200 0.1 float
AbVSiA A-Side Lack of Voltage (V) 10 200 0.1 float
BrClTmms1 Closing time (ms) 0 100000 10 float
None
No compensation
SyWReEna1 Sync. Enabled (AR) Zero compensation enum
With compensation
Always
None
No compensation
SyWMaClEna1 Sync. Enabled (Close) Zero compensation enum
With compensation
Always
SyDifV1 Voltage difference (V) 0 90 0.1 float
SyDifF1 Frequency difference(Hz) 0.01 5 0.01 float
SyDifA1 Angle difference (º) 0 360 1 float
SlThr Slip threshold (Hz) 0.01 0.5 0.01 float
ReTmms1 Sync. Time (Autoreclose) 0 100000 10 float
MaClTmms1 Sync.Time (Man.closing) 0 100000 10 float
PrVSiB1 B-Side Voltage presence (V) 10 200 0.1 float
AbVSiB1 B-Side Lack of Voltage (V) 10 200 0.1 float
Without permission
Not A and Yes B
Yes A and Not B
Not A and Not B
ClCond1 Manual closing condition enum
Not A or Not B
A xor B
Not A
Not B
Without permission
Not A and Yes B
Yes A and Not B
Not A and Not B
ReCond1 Autoreclose condition enum
Not A or Not B
A xor B
Not A
Not B
LogInBlSy1 Blocking input Int32
LogInBlCl1 Close blocking Int32
LogInRFF Fuse failure signal Int32
MaskEna Enable Events Record NO/YES Boolean
MaxVSiA24 A-Side Maximum V. (V) 10 200 0.1 float
MaxVSiB24 B-Side Maximum V. (V) 10 200 0.1 float
Not apply
Vline
AuxVSiA A-Side V aux. enum
Vs1
Vs2
LogInSwA Side A-V switch Int32
Not apply
Vline
AuxVSiB B-Side V aux. enum
Vs1
Vs2
LogInSwB Side B-V switch Int32

24
Available since firmware version 6.0.18.0 and ICD 8.1.0.14

Ingeteam Power Technology S.A.


User Manual 238
AUTOMATISMS 

Synchrocheck function signals (see Table 137).

❑ Enable Synchro Breaker 1: Indicates whether the function is enabled or not.


❑ V presence Va/Vab side A: indicates if the voltage on the phase A/AB of side A is greater than the setting “A-Side Voltage presence
(V)”
❑ V presence Vb/Vbc side A: indicates if the voltage on the phase B/BC of side A is greater than the setting “A-Side Voltage presence
(V)”.
❑ V presence Vc/Vca side A: indicates if the voltage on the phase C/CA of side A is greater than the setting “A-Side Voltage presence
(V)”.
❑ V presence ABC side A: indicates if the voltage of the three phases of side A is greater than the setting “A-Side Voltage presence
(V)”.
❑ V presence side B B1: indicates if the voltage on the side B is greater than the setting “B-Side Voltage presence (V)”.
❑ No Voltage Va/Vab side B: indicates if the voltage on the phase A/AB of side A is less than the setting “A-Side Voltage presence (V)”.
❑ No Voltage Vb/Vbc side B: indicates if the voltage on the phase B/BC of side A is greater than the setting “A-Side Voltage presence
(V)”.
❑ No Voltage Vc/Vca side B: indicates if the voltage on the phase C/CA of side A is greater than the setting “A-Side Voltage presence
(V)”.
❑ No Voltage ABC side A: indicates if the voltage of the three phases of side A is less than the setting “A-Side Voltage presence (V)”.
❑ No Voltage side B B1: indicates if the voltage on the side B is less than the setting “B-Side Voltage presence (V)”.
❑ A Side Maximun V exceeded 25: It indicates that the voltage on the A side is geater than the setting “A-Side Maximum V. (V)”.
❑ B Side I1 Maximun V exceeded25: It indicates that the voltage on the B side is geater than the setting “B-Side Maximum V. (V)”.
❑ A Side V aux selected 25. It indicates that the auxiliary voltage on the A side has been selected. This auxiliary voltage will be used as
the side A voltage of the synchronism unit.
❑ B Side I1 V aux selected 25. It indicates that the auxiliary voltage Vs1 on the B side has been selected. This auxiliary voltage will be
used as the side B voltage of the synchronism unit.
For the following signals, it is necessary that voltage presence is detected on both sides of the breaker:

❑ Positive slip Breaker 1: it is active if the frequency on the side B is also greater than that on side A by more than the setting.
❑ Negative slip Breaker 1: it is active if the frequency on the side A is also greater than that on side B by more than the setting.
❑ Underfrequency side B B1: it is active if the frequency difference of both sides exceeds the setting value and the frequency on side
A is greater than that on side B.
❑ Overfrequency side B B1: it is active if the frequency difference of both sides exceeds the setting value and the frequency on side B
is greater than that on side A.
❑ Delay without comp. side B 1: when the difference between the angles exceeds the setting value and is greater on side A than on
side B.
❑ Adv. without comp.side B B1: when the difference between the angles exceeds the setting value and is greater on side B than on
side A.
❑ Delay with comp. side B 1: when the difference between the angles, calculated by taking into account breaker closure time,
exceeds the setting value and is greater on side A than on side B.
❑ Advance with comp. side B 1: when the difference between the angles, calculated by taking into account breaker closure time,
exceeds the setting value and is greater on side B than on side A.
❑ Over Module side B B1: when the voltage difference is greater than the programmed setting and the voltage in B is greater than in
A.
❑ Under Module side B B1: when the voltage difference is greater than the programmed setting and the voltage in A is greater than in
B.
❑ Perm. without comp. B1: indicates that differences in voltage, angle and frequencies are lower than the corresponding settings.

25
Available since firmware version 6.0.18.2 and ICD 8.2.0.

Ingeteam Power Technology S.A.


User Manual 239
AUTOMATISMS 

❑ Perm. with comp. B1: when the necessary conditions related to the voltage, angle argument and frequencies differences are given,
taking into account the breaker closure time for calculating the angle argument difference.
❑ Perm. Manual Close V B1: Manual closure permission for voltage checks. It´s active when the undervoltage conditions are met.
❑ Permission Recloser V B1: Reclosure permission for voltage checks. It´s active when the undervoltage conditions are met.
❑ Perm. Manual Close B1: closure permission for undervoltage or for synchronism. It is active, due to compliance with the
undervoltage conditions or the synchronism conditions. If the function is disabled, manual closure permission will also be signalled.
❑ Perm. Reclose Br 1: reclosure permission for undervoltage or synchronism, so that the recloser decides on the automatic closure of
the breaker. It is actived, due to compliance with the undervoltage conditions or the synchronism conditions.
The function has independent settings, commands and outputs:

❑ Node: PROT/RSYN1
❑ Settings and logical inputs: There are 6 settings tables. See Table 136.
❑ Commands:
 DOrdSyBlk1: Function block and unblocking. Only acts when the function is enabled.
 DOrdPeBlk1: Close permission block and unblock. Only acts when the function is enabled.
❑ Outputs: Table 137 shows the function’s output data.

Table 137 Synchronism function outputs for breaker 1

Signal Data Atribute


Positive Slip Breaker 1 PosSlipBr1 stVal
Negative Slip Breaker 1 NegSlipBr1 stVal
Underfrequency side B B1 UFSideBBr1 stVal
Overfrequency side B B1 OFSideBBr1 stVal
Delay without comp. side B 1 DBNSlipBr1 stVal
Adv. without comp.side B B1 ABNSlipBr1 stVal
Delay with comp. side B B1 DBSlipBr1 stVal
Advance with comp. side B 1 ABSlipBr1 stVal
Over Module side B B1 OAbsBBr1 stVal
Under Module side B B1 UAbsBBr1 stVal
Perm. without comp. B1 PNoSlipBr1 stVal
Perm. with comp. B1 PSlip0Br1 stVal
Perm. Manual Close B1 PMCBr1 stVal
Perm. Close Recloser Br 1 PRecBr1 stVal
Perm. Manual Close V B1 PMClVChBr1 stVal
Permission Recloser V B1 PRecVChBr1 stVal
Permission with compens. 1 PSlipBr1 stVal
Enable Synchro Breaker 1 EnaBr1 stVal
V presence Va/Vab side A SAVPres phsA
V presence Vb/Vbc side A SAVPres phsB
V presence Vc/Vca side A SAVPres phsC
V presence ABC side A SAVPres general
No Voltage Va/Vab side A SAVAbs phsA
No Voltage Vb/Vbc side A SAVAbs phsB
No Voltage Vc/Vca side A SAVAbs phsC
No Voltage ABC side A SAVAbs general
Voltage presence side A SAPres stVal
No Voltage side A SAAbs stVal
V presence side B B1 SBVPresBr1 stVal
No Voltage side B B1 SBVAbsBr1 stVal
A Side Maximun V exceeded25 SAVExc stVal
B Side I1 Maximun V exceeded25 SBVExcBr1 stVal
A Side V aux selected25 AuxASel stVal
B Side I1 V aux selected25 AuxVs1Sel stVal

Ingeteam Power Technology S.A.


User Manual 240
AUTOMATISMS 

6.1.1 Undervoltage permission


Permission is granted if there is voltage on one or on both sides of the breaker. In order to verify whether there is no voltage
present on one side of the breaker, the voltage measured is checked to see whether it is lower than the programmed value (see
Table 136).

The detection of the presence or the absence of voltage is always done in all the phases. However, the analysis of the conditions for
granting or refusing breaker close permission is only carried out if the function is enabled.

6.1.2 Synchronism permission


Synchronism permission is given when following conditions indicated by the corresponding setting are simultaneously fulfilled
during a programmable time. These conditions are based on the comparison of voltage modules, phases and frequency on both
sides of the breaker. The analysis is performed whenever there is voltage on both sides of the breaker and it is below the maximum
voltage setting.

Figure 154 Synchronism check with compensation

If “Sync. Enabled” is selected “with compensation”, the frequency slip is used to compensate the breaker closing time:

ϕUB (with compensation) =ϕUB + ωslip·TCB

∆ϕ with compensation =ϕUB (with compensation) -ϕUA

In which:

Frequency slip ∆f=fB-fA (Hz)

Slip speed ωslip=∆f·360º (º/s)

Breaker closure time TCB (s)

To consider the slip frequency difference must exceed the "Slip threshold (Hz)" setting.

If this angle difference decreases when the “Sync. Enabled” is set with compensation and closure in 0º, the condition for granting
permission will be:

|∆ϕ with compensation|=0

If the angle difference is increasing, the following must be met:

|∆ϕ with compensation|<angle difference setting

When the “Sync. Enabled” is set with compensation, in order for permission to be granted the difference must be around 0º, the
following must be met:

|∆ϕ with compensation|<angle difference setting

Synchronism function measurements available in the unit status:

Ingeteam Power Technology S.A.


User Manual 241
AUTOMATISMS 

❑ Module, angle, frequency of the voltage on side A.


❑ Module, angle, frequency of the voltage on side B.
❑ The difference between the module, angle, frequency of the voltage on side A and side B. They are only available when
the voltage presence conditions are met on both sides.

6.1.3 Two breakers application


It is available an independent synchronism function for a second breaker.

As in the first breaker, this unit has function to check the presence of voltage on both sides of the breaker, and the test of the
synchronism conditions to give close permission.

The side A voltage is the same for both synchronisms, so the same voltage and settings are used (“Side A phase Select”,
“Compensation factor (Vs1)” and “Compensation angle (Vs1)”).

The side B voltage is the Vs2 (V synchronism 2).

When “Side A-Vs1 selection” signal is activated, the side A voltage corresponds to the analogue voltage input connected to the
synchronism voltage terminals (Vs1) and side B voltage to the Vs2 (V synchronism 2).

For breaker and a half applications, with closing sequence reclosing "Brk1 then Brk2" or " Brk2 then Brk1" the setting "Autoreclose
condition" depends on the state of the breaker, so that if the first breaker of the sequence is blocked, the second breaker uses the
first breaker´s setting . For example, with "Brk1 then Brk2" if breaker 1 is blocked , it will not be close command of that breaker, so
the "Autoreclose condition" of the second breaker ( RSYN2 ) will use the setting of the first breaker ( RSYN1 ).

The function has independent settings, commands and outputs for the second breaker. The meaning of these data is the same as
the first breaker.

❑ Node: PROT/SECRSYN1
❑ Settings and logical inputs: There are 6 settings tables. See Table 139.
❑ Outputs: Table 138 shows the function’s output data. They are similar to the first breaker, but for the second.

Table 138 Synchronism function outputs for breaker 2

Signal Data Atribute


Positive Slip Breaker 2 PosSlipBr2 stVal
Negative Slip Breaker 2 NegSlipBr2 stVal
Underfrequency side B B2 UFSideBBr2 stVal
Overfrequency side B B2 OFSideBBr2 stVal
Delay without comp. side B 2 DBNSlipBr2 stVal
Adv. without comp. side B B2 ABNSlipBr2 stVal
Delay with comp. side B B2 DBSlipBr2 stVal
Advance with comp. side B 2 ABSlipBr2 stVal
Over Module side B B 2 OAbsBBr2 stVal
Under Module side B B2 UAbsBBr2 stVal
Perm. without comp. B2 PNoSlipBr2 stVal
Perm. with comp.B2 PSlip0Br2 stVal
Perm. Manual Close B2 PMCBr2 stVal
Perm. Close Recloser B2 PRecBr2 stVal
Perm. Manual Close V B 2 PMClVChBr2 stVal
Perm. Recloser V B2 PRecVChBr2 stVal
Permission with compens. 2 PSlipBr2 general
Enable Synchro Breaker 2 EnaBr2 general (stVal in Ed2)
Voltage presence side B B2 SBVPresBr2 general (stVal in Ed2)
No Voltage side B B2 SBVAbsBr2 general (stVal in Ed2)
B Side I2 Maximun V exceeded25 SBVExc2 stVal
B Side I2 V aux selected25 AuxVs2Sel stVal

Ingeteam Power Technology S.A.


User Manual 242
AUTOMATISMS 

Table 139 Synchronism settings for breaker 2

Data Setting Minimum Maximum Step Remarks Type


SynEna Enabled NO/YES enum
CoModVs2 Compensation factor (Vs1) 0.1 3 0.01 float
CoArgVs2 Compensation angle (Vs1) 0 330 30 float
BrClTmms2 Closing time (ms) 0 10000 10 float
No, Without compensation,
With compensation (0º),
SyWReEna2 Sync. Enabled (AR) enum
With compensation
Always
No, Without compensation,
With compensation (0º),
WMaClEna2 Sync. Enabled (Close) enum
With compensation
Always
SyDifV2 Voltage difference (V) 0 90 0.1 float
SyDifF2 Frequency difference(Hz) 0.01 2 0.01 float
SyDifA2 Angle difference (º) 0 360 1 float
SlThr Slip threshold (Hz) 0.01 0.5 0.01 float
MaClTmms2 Sync. Time (Autoreclose) 0 10000 10 float
ReTmms2 Sync.Time (Man.closing) 0 10000 10 float
PrVSiB2 B-Side Voltage presence(V) 0 200 0.1 float
AbVSiB2 B-Side Lack of Voltage (V) 0 200 0.1 float
Without permission
Not A and Yes B
Yes A and Not B
Not A and Not B
ClCond2 Manual closing condition enum
Not A or Not B
A xor B
Not A
Not B
Without permission
Not A and Yes B
Yes A and Not B
Not A and Not B
ReCond2 Autoreclose condition enum
Not A or Not B
A xor B
Not A
Not B
LogInBlSy2 Blocking input Int32
LogInBlCl2 Close blocking Int32
LogInRFF Fuse failure signal Int32
MaskEna Enable Events Record NO/YES Boolean
MaxVSiB226 B-Side Maximum V. (V) 10 200 0.1 float
Not apply
Vline
AuxVSiB B-Side V aux. enum
Vs1
Vs2
LogInSwB Side B-V switch Int32

26
Available since firmware version 6.0.18.0 and ICD 8.1.0.14

Ingeteam Power Technology S.A.


User Manual 243
AUTOMATISMS 

6.1.4 Application auxiliary voltage


Two examples of application and use of auxiliary voltages according to configuration are shown.

Double busbar configuration

Figure 155 Double busbar

In double busbar configuration, there is only one breaker and the synchronism unit 1 (RSYN1) is used.

The side A voltage is independent of the disconnectors, but the side B voltage depends on the disconnector. When 89_1 is closed,
Vs1 is used, but when it is opened Vs2 is used. It affects the voltage (module and argument) and frequency used in the synchronism
function. The settings could be:

❑ A-Side V aux: Not apply


❑ Side A-V switch: Not asigned
❑ B-Side V aux: Vs2
❑ Side B-V switch: disconnector Status 89_1 opened
The synchronism function (undervoltage and synchronism) depends on the disconnector status:

❑ Disconnector Status 89_1 closed. The voltage selected on the A side is compared with the voltage of the input Vs1.
❑ Disconnector Status 89_1 opened. The voltage selected on the A side is compared with the voltage of the input Vs2.

Ingeteam Power Technology S.A.


User Manual 244
AUTOMATISMS 

52 ½ Configuration

Figure 156 52 ½

In 52 ½busbar configuration, there are two breakers and both units of synchronism unit 1 are used (RSYN1 and SEC/RSYN).

With the disconnector closed, the synchronism units use:

❑ RSYN1. It compares side A voltage with Vs1.


❑ SEC/RSYN1. It compares side A voltage with Vs2.
With the disconnector open, both synchronism units compare Vs1 with Vs2.

The settings could be:

❑ RSYN1
 A-Side V aux: Vs1
 Side A-V switch: disconnector Status 89_1 opened
 B-Side V aux: Vs2
 Side B-V switch: disconnector Status 89_1 opened
❑ SEC/RSYN1
 B-Side V aux. Not apply
 Side B-V switch. Not asigned

Ingeteam Power Technology S.A.


User Manual 245
AUTOMATISMS 

6.2 RECLOSER

The unit allows up to 4 reclosures to be effected. The first one can be single-pole or three-pole, but the next 3 must be three-pole. In
order to make the recloser as useful as possible, the number of reclosures allowed is programmable (0 is not permitted).

There are different close times for each of the closures and for the first single-pole or three-pole.

The recloser is put into service – out of service by means of a setting. Only when enabled by setting can it be put into service-out of
service by means of a command via communications or the keyboard.

Programmable reclaim time following manual closure and following automatic closure.

The 4 closure counters (total, first, second and third closures) are stored in non-volatile memory and can be viewed in the console and
on the display. These counters can be set to 0 by command or by the keyboard.

The closure cycle can be started either by the unit's own protection trips or by external trips from other protections.

The main recloser statuses are:

❑ Supervising status.
This is the normal status, during which the recloser “monitors” for the occurrence of any trips. If any trip occurs, the recloser is
activated.

❑ Ongoing cycle status.


The status of the recloser while activated, from the first trip up to the closure of the breaker and the elapse of the reclaim time
(successful reclosure), or until all the programmed reclosures have been unsuccessfully executed. In the first case, the recloser
switches to “supervising” and, in the second, to “definitive trip”.

❑ Definitive trip status.


The recloser’s final situation once it has run all the programmed attempts and the breaker remains open due to the existence of a
permanent fault. It only leaves this status when the breaker is closed manually.

❑ Internal block status.


The status is reached as a result of different causes. The reclosure cycle cannot be started nor can the termination of the cycle be
provoked if the cycle is running. It is cancelled by a breaker closure.

Definitions:

❑ Reclosable units.
These units are capable of initiating the reclosure process. By default, they are overcurrent or distance units. The non-reclosable
units are those whose trips do not initiate the reclosure cycle (voltage, frequency, power units, etc). There is an input “External
trip” that can be one pole or three poles.

❑ Trips permitted following reclosure.


Each of the units that are blocked during the reclaim time following each reclosure are programmed by means of "YES" or "NO".

6.2.1 Settings, signals and commands


The general settings used in the recloser (PROT/ZRREC node) are (see Table 140):

❑ Enabled. Indicates whether the function is enabled or not.


❑ Reclose mode. Indicates the reclose mode between:
 1 Pole. It allows a single closure only if the first trip is single-pole. In any other case, it gives a definitive trip.
 3 Pole. It allows as many closures as there are programmed in the number of closures before giving the final trip. It
forces all trips to be three-pole.

Ingeteam Power Technology S.A.


User Manual 246
AUTOMATISMS 

 1P/3P. It allows as many closures as there are programmed in the number of closures before giving the final trip. The
first closure will be single-pole if the first trip was single-pole and three-pole if it was three-pole. All other closures of
the cycle will be three-pole.
 Dependent. If the first trip is single-pole, it allows as many closures as there are programmed in the number of
closures before giving the final trip; while if the first trip is three-pole, it only allows one closure.
 Configurable:27 The Reclose mode is selected with the logical inputs or commands: “Enable/Disable 1P mode” and
“Enable/Disable 3P mode”. When no option is selected, the recloser is blocked.
❑ Reclose number. Indicates the maximum number allowed before the issue of the definitive trip.
❑ 3 Pole Reclose 1 time (s). This is the timeout following the first three-pole trip until the recloser issues a closure command
❑ 1 Pole Reclose 1 time (s). This is the timeout following the first single-pole trip until the recloser issues a closure
command
❑ Reclose 2 time (s). This is the timeout following the three-pole trip until the recloser issues the second closure command
❑ Reclose 3 time (s). This is the timeout following the three-pole trip until the recloser issues the third closure command
❑ Reclose 4 time (s). This is the timeout following the three-pole trip until the recloser issues the fourth closure command
❑ Time after man. closing(s). Reclaim time following manual closure. The time following the manual closure of the breaker,
during which the existence of a protection trip is monitored. In such a case, a definitive trip is triggered instead of a
change to supervising status.
❑ Reclaim time Ph-Ph (s). Reclaim time following automatic closure following three-pole trip. This is the time following the
automatic closure of the breaker due to a three-pole trip, during which the existence of a protection trip is monitored. In
such a case, the cycle is continued instead of a change to supervising status.
❑ Reclaim time ground (s). Reclaim time following automatic closure following single-pole trip. This is the time following the
automatic closure of the breaker due to a single-pole trip, during which the existence of a protection trip is monitored. In
such a case, the cycle is continued instead of a change to supervising status.
❑ Incomplete sequence. Indicates whether the incomplete sequence function is enabled or not.
❑ Incomplete sequence T (s). Indicates the maximum time for the completion of the reclosure process.
❑ 79 Blocking level input. Selects the signal which, when active, blocks the recloser. The recloser must be enabled by
setting; on the other hand this input is not available.
❑ 79 Blocking pulse input. Selects the signal which, when there is a status change from deactivated to activated, blocks the
recloser. The recloser must be enabled by setting; on the other hand this input is not available. Since firmware version
5.18.15.5, if recloser is blocked by pulse, when the input is set “Not assigned”, the recloser is unblocked.
❑ 79 Unblock pulse input. Selects the signal which, when there is a status change from deactivated to activated, unblocks
the recloser. The recloser must be enabled by setting; on the other hand this input is not available.
❑ Pause+Reset AR time input. Selects the signal which, when active, restarts the closure time.
❑ Pause input. Selects the signal which, when active, stops the closure time.
❑ Autoreclose sequence reset. Selects the signal which, when active, restarts the closure process. If the breaker is open,
“Recloser Lock 52 open” is activated and waits for it to be closed. If it is close, “Recloser Lock manual closing” is activated.
In any case, once closed, it waits for the reclaim time following manual closure to return to supervising status.
❑ On line pulse input. Selects the signal which, when there is a status change from deactivated to activated, the recloser
goes to “On service”. The recloser must be enabled by setting; on the other hand this input is not available.
❑ Out of line pulse input. Selects the signal which, when there is a status change from deactivated to activated, the recloser
goes to “Out of service”. The recloser must be enabled by setting; on the other hand this input is not available. Since
firmware version 5.18.15.5, if recloser is Out of line by pulse, when the input is set “Not assigned”, the recloser is On line.
❑ Enable 1P mode27. Selects the signal which, when there is a status change from deactivated to activated, enables the 1P
mode, when the setting “Reclose mode” is "Configurable". The recloser mode will be:
 "1 Pole" when the 3P mode is not selected
 "1P/3P" when the 3P mode is not selected
❑ Disable 1P mode 27. Selects the signal which, when there is a status change from deactivated to activated, disable the 1P
mode, when the setting “Reclose mode” is "Configurable". The recloser mode will be:

27
Available since firmware version 5.17.15.4 and ICD 6.1.13.30

Ingeteam Power Technology S.A.


User Manual 247
AUTOMATISMS 

 "3 Pole" when the 3P mode is selected


 "Blocked" when the 3P mode is not selected
❑ Enable 3P mode 27. Selects the signal which, when there is a status change from deactivated to activated, enables the 3P
mode, when the setting “Reclose mode” is "Configurable". The recloser mode will be:
 "3 Pole" when the 1P mode is not selected
 "1P/3P " when the 1P mode is selected
❑ Disable 3P mode 27. Selects the signal which, when there is a status change from deactivated to activated, disable the 3P
mode, when the setting “Reclose mode” is "Configurable". The recloser mode will be:
 "1 Pole" when the 1P mode is selected
 "Blocked" when the 1P mode is not selected
❑ Enable Events record. Allows the generation of protection events associated to the function. If set to “NO”, the function’s
protection events are not generated. If set to “YES”, the function’s specific mask is contemplated.

Table 140 General recloser settings

Data Setting Minimum Maximum Step Remarks Type


RecEna Enabled 0 1 1 NO/YES Enum
1 Pole
3 Pole
RecTyp Reclose mode 0 3 1 1P/3P Enum
Dependent
Configurable
UseCyc Reclose number 1 4 1 Int32
Rec1PhTms 3 Pole Reclose 1 time (s) 0,05 600 0,01 float
Rec2PhTms Reclose 2 time (s) 1 600 1 float
Rec3PhTms Reclose 3 time (s) 1 600 1 float
Rec4PhTms Reclose 4 time (s) 1 600 1 float
Rec1GTms 1 Pole Reclose 1 time (s) 0,05 600 0,01 float
PReSe3Tms Reclaim time Ph-Ph (s) 1 600 1 float
PReSe1Tms Reclaim time ground (s) 1 600 1 float
MaClSeTms Time after man. closing(s) 1 600 1 float
BlInSecEna Incomplete sequence 0 1 1 NO/YES enum
BlInSecTms Incomplete sequence T (s) 1 600 1 float
LogInReLB 79 Blocking level input Int32
LogInRePB 79 Blocking pulse input Int32
LogInRePUb 79 Unblock pulse input Int32
LogInTmRst Pause+Reset AR time input Int32
LogInTmPau Pause input Int32
LogInRst Autoreclose sequence reset Int32
LogInRPOn On line pulse input Int32
LogInRPOff Out of line pulse input Int32
LogIn1POn Enable 1P mode Int32
LogIn1POff Disable 1P mode Int32
LogIn3POn Enable 3P mode Int32
LogIn3POff Disable 3P mode Int32
MaskEna Enable Events Record 0 1 1 NO/YES Boolean

The general settings used for the supervising for synchronism (PROT/RLSS1 node) are (see Table 141):

❑ Synchrocheck type. Indicates whether the synchronism is internal or external.


❑ Check 3 pole first reclose. Three-phase closure 1 monitoring. Indicates whether the first closure is to be monitored with
synchronism.
❑ Check rest of autorecloses. Monitoring remaining closures. Indicates whether the closures other than the first are to be
monitored with synchronism.
❑ Sync. Delay Time (s). Synchronism timeout. This is the maximum time waited before the synchronism grants permission
before a three-phase closure. If closure permission is granted before the conclusion of this time, a closure command is
issued. On the other hand, if this time elapsed without permission being granted, a definitive trip is triggered.

Ingeteam Power Technology S.A.


User Manual 248
AUTOMATISMS 

❑ External syncro. Permission. Logical external synchronism permission logic. Selects the signal which, when active,
indicates the existence of permission for synchronism.
❑ Enable Events record. Allows the generation of protection events associated to the function. If set to “NO”, the function’s
protection events are not generated. If set to “YES”, the function’s specific mask is contemplated.
Table 141 Monitoring by synchronism settings

Data Setting Minimum Maximum Step Remarks Type


SynTyp Synchrocheck type Internal/External enum
Rec1SyEna Check 3pole first reclose NO/YES Boolean
RecSyEna Check rest of autorecloses NO/YES Boolean
SyWaTms Sync. Delay Time (s) 0.05 600 0.01 float
MaskEna Enable Events Record NO/YES Boolean
LogInExSy External syncro. Permission Int32

The settings used for the monitoring by reference voltage (PROT/RVRS1 node) are (see Table 142):

❑ Enabled. Indicates whether the function is enabled or not.


❑ Delay time (s). This is the time, following the opening of the breaker that is waited for the activation of the reference
voltage signal to allow the reclosure. It is used to wait for the activation of an external signal before allowing a reclosure.
E.g., to wait for the line voltage to disappear following a trip (e.g., if there were motors or batteries connected) before
reconnecting the line.
❑ Minimum time (s). This is the minimum time during which the vref signal must be seen to be active in order to consider
the existence of reference voltage.
❑ Reference Voltage input. Logical Vref input. Selects the signal which, when active, indicates the existence of reference
voltage (Vref).
❑ Enable Events record. Allows the generation of protection events associated to the function. If set to “NO”, the function’s
protection events are not generated. If set to “YES”, the function’s specific mask is contemplated.
Table 142 Monitoring by Vref settings

Name IEC 61850 Setting Minimum Maximum Step Remarks Type


VrefEna Enabled NO/YES enum
VrefWaTms Delay time (s) 0.05 600 0.01 float
VrefMinTms Minimum time (s) 0.05 600 0.01 float
LogInVref Reference Voltage input Int32
MaskEna Enable Events Record NO/YES Boolean

Table 143 shows the output signal of the monitoring by reference voltage (PROT/RVRS1 node):

❑ Presence of Vref. Indicates the presence of reference voltage.


❑ Blocked without Vref. Indicates blocking by absence of reference voltage.
Table 143 Monitoring by Vref outputs

Signal Data Atribute


Presence of Vref PresVref general
Blocked without Vref BlkVref general

The setting used for blocking a closure due to a failure in the breaker’s coils (PROT/RTCS1 node) is (see Table 144):

❑ Block by Coil failure. Indicates whether the recloser blocking by failure in the breaker’s coils is enabled or not.
Table 144 Closure block settings

Data Setting Minimum Maximum Step Remarks Type


ClBlTCF Block by Coil failure NO/YES Boolean

Signals

The recloser’s output signals are in the PROT/ZRREC1 node and are shown in Table 145 and Table 146.

The general recloser signals are:

Ingeteam Power Technology S.A.


User Manual 249
AUTOMATISMS 

❑ Recloser in service. Indicates whether it is enabled and not locked by an external blocking input. Internal blocking signals
don´t affect this signal. When the recloser is disabled by setting, the recloser´s signals don´t activate.
❑ Recloser in standby. Indicates that it is in standby or supervising.
❑ Recloser Blocked. Indicates that it is locked. If the recloser is out of service, this signal is activated. If the recloser is on
line, this signal is activated by internal and external block.
❑ Definitive trip. Indicates that it is in the definitive trip. It´s activated by maximum reclose number or a trip with the
recloser blocked.
❑ Definitive Trip+Ext blocked. Indicates that it is in definitive trip and external block. It includes trips with the recloser out of
service or blocked.
❑ Reclose command. Automatic breaker closure command.
❑ 79 in progress. Active from the moment the breaker is opened by a trip until the monitoring or definitive trip status is
reached.
❑ Reclosing 1 in progress. During the closure cycle 1. As of the opening of the breaker by the first trip or until supervising is
reached following the reclaim time or trip which leads to it being blocked (by Definitive T.) or a new cycle is produced.
❑ Reclosing 1 1P in progress. During the closure cycle 1, if only one pole is open by a single-pole trip.
❑ Reclosing 1 3P in progress. During the closure cycle 1, the three poles are open by a three-pole trip.
❑ Reclosing 2 in progress. During the closure cycle 2. As of the opening of the breaker by a three-pole trip during the
reclaim time following the first reclosure until the closure command is given or the block is produced.
❑ Reclosing 3 in progress. During the closure cycle 3. As of the opening of the breaker by a three-pole trip during the
reclaim time following the second reclosure until the closure command is given or the block is produced.
❑ Reclosing 4 in progress. During the closure cycle 4. As of the opening of the breaker by a three-pole trip during the
reclaim time following the second reclosure until the closure command is given or the block is produced.
❑ Safety time. Following the closure of the breaker, the reclaim time is counted until supervising is entered or a new closure
cycle is initiated.
❑ Safety time manual closing. Following the automatic closure of the breaker, the reclaim time is counted until supervising
is entered or a new closure cycle is initiated.
❑ Safety time reclosing. Following the manual closure of the breaker, the reclaim time is counted until supervising is
entered or a new closure cycle is initiated.
❑ Safety time 1st reclosing. Following the closure of the breaker by the first closure, the reclaim time is counted until
supervising is entered, a new closure cycle is initiated or the definitive trip is triggered.
❑ Safety time 2nd reclosing. Following the closure of the breaker by the second closure, the reclaim time is counted until
supervising is entered, a new closure cycle is initiated or the definitive trip is triggered.
❑ Safety time 3rd reclosing. Following the closure of the breaker by the third closure, the reclaim time is counted under
supervising is entered or the definitive trip is triggered.
❑ Safety time 4th reclosing. Following the closure of the breaker by the fourth closure, the reclaim time is counted under
supervising is entered or the definitive trip is triggered.
❑ Presence of Vref. Indicates the presence of reference voltage.
❑ Recloser paused. Indicates that the recloser is in pause in the closure time counter.
❑ Reclosing Started. Indicates that the reclosure process has started.
❑ Reclosing 1 Started. Indicates that the first reclosure process has started.
❑ Reclosing 2 Started. Indicates that the second reclosure process has started.
❑ Reclosing 3 Started. Indicates that the third reclosure process has started.
❑ Reclosing 4 Started. Indicates that the fourth reclosure process has started.
❑ Successful Reclosing. Indicates that the reclosure process was completed successfully.
❑ Breaker Reclosing ongoing. Indicates that the breaker is reclosing.
❑ Prepare 3 pole trip. Indicates that the following trips will be three-pole.
 If the recloser is enabled by setting, it happens when:

Ingeteam Power Technology S.A.


User Manual 250
AUTOMATISMS 

 The Autoreclose mode is 3 Poles


 The Autoreclose mode is 1P/3P or Dependent 3 Poles and the first trip has happened.
 The recloser is blocked
 The recloser is paused by absence of Vref
 The fault has changed from single-pole to three-pole.
 If the recloser is disabled by setting, it happens when:
 The “Single Pole Trip” is disabled by setting (node ZPMPT)
 The input “Force three pole” is activated
❑ Pole trip allowed. Indicates that single-pole trip is allowed. It happens if the Autoreclose mode is 1 Pole, 1P/3P or
Dependent and the recloser is “in standby”.
❑ Last pole trip. Indicates the last trip has been single-pole.
❑ Evolving fault. Indicates the fault has evolved from single-pole to three-pole
❑ Mode 1P Enabled.27 Indicates that selected reclose type allows 1P reclose.
❑ Mode 3P Enabled.27 Indicates that selected reclose type allows 3P reclose.

Table 145 General recloser outputs

Signal Data Atribute


Auto
Recloser in service general
(RecSt in Ed2)
Recloser in standby RestST general
RecCyc
79 in progress general
(RecCycOn in Ed2)
Successful Reclosing RecOK general
Definitive Trip DefTrip general
Reclose Command OpCls general
Blk
Recloser Blocked general
(RecBlk in Ed2)
Reclosing 1 in progress RecCyc1 general
Reclosing 1 1P in progress RecCycMon1 general
Reclosing 1 3P in progress RecCycTr1 general
Reclosing 2 in progress RecCyc2 general
Reclosing 3 in progress RecCyc3 general
Reclosing 4 in progress RecCyc4 general
Safety time SecTime general
Safety time manual closing ManClSecT general
Safety time reclosing RecSecT general
Safety time 1st reclosing Rec1SecT general
Safety time 2nd reclosing Rec2SecT general
Safety time 3rd reclosing Rec3SecT general
Safety time 4th reclosing Rec4SecT general
Recloser paused Pause general
Reclosing Started RecPrIn general
Reclosing 1 Started RecPrIn1 general
Reclosing 2 Started RecPrIn2 general
Reclosing 3 Started RecPrIn3 general
Reclosing 4 Started RecPrIn4 general
Definitive Trip+Ext blocked DefTripBlk general
Breaker Reclosing ongoing BrRec general
Prepare 3 pole trip Op3pol general
Pole trip allowed EnaPol general
Last pole trip OpPol general
Evolving fault EvOp general
Mode 1P Enabled Rec1PEn general
Mode 3P Enabled Rec3PEn general

The recloser blocking signals are:

❑ 79 Internal Block. Indicates that the recloser is in internal block due to any cause.

Ingeteam Power Technology S.A.


User Manual 251
AUTOMATISMS 

❑ 79 Block Definitive Trip. Indicates that the recloser is in internal block due to a definitive trip.
❑ 79 Block 52 open. Indicates that the recloser is in internal block due to a manual opening.
❑ 79 Block Trip Exceeded. Indicates that the recloser is in internal block due to an excessive number of trips.
❑ 79 Block switch on fault. Indicates that the recloser is in internal block due to a switch onto fault, i.e., a trip is produced
during the reclaim time following a manual closure.
❑ 79 Block 3P trip. Indicates that the recloser is in internal block due to a three-pole trip, in the single-pole modes. Recloser
Lock No Syncrocheck. Indicates that the recloser is in internal block due to the absence of syncrcheck.
❑ 79 Block without Vref. Indicates that the recloser is in internal block due to the absence of vref.
❑ 79 Block Pole discordance. If the discordance function acts, the reclosure cycle is blocked.
❑ 79 Block Close Failure. Indicates that the recloser is in internal block due to the close failure. Related to the breaker
monitoring.
❑ 79 Block opening Failure. Indicates that the recloser is in internal block due to the open failure. Related to the breaker
monitoring.
❑ 79 External Block. Indicates that the recloser is in external block due to any cause.
❑ 79 External Block Comms. Indicates that the recloser is in external block due to command.
❑ 79 External Block Input. Indicates that the recloser is in external block due to logical input.
❑ 79 Block Start failure. Indicates that the recloser is blocked due to reclosing start failure.
❑ 79 Block A Start failure. Indicates that the recloser is blocked due to pole A reclosing start failure.
❑ 79 Block B Start failure. Indicates that the recloser is blocked due to pole B reclosing start failure.
❑ 79 Block C Start failure. Indicates that the recloser is blocked due to pole C reclosing start failure.
❑ 79 Block End of cycle. Indicates that the recloser is blocked due to the end of the reclosing cycle.
❑ 79 Block manual closing. Indicates that the recloser is blocked due to manual reclosing.
❑ 79 Block Trip In Safety time. Indicates that the recloser is blocked due to a trip in safety time.
❑ 79 Block Incomplete sequence. Indicates that the recloser is blocked because the sequence time is exceeded.
❑ 79 Block TC Failure. Indicates that the recloser is blocked due to breaker circuit supervision failure.

Table 146 Recloser block outputs

Signal Data Atribute


79 Internal Block BlkInt general
79 Block Definitive Trip BlkIntDeTr general
79 Block 52 open BlkIntOpBr general
79 Block Trip Exceeded BlkInExcTr general
79 Block switch on fault BlkIntSOF general
79 Block 3P trip BlkInt3PTr general
79 Block No Syncronism BlkINoSync general
79 Block without Vref BlkINoVref general
79 Block Pole discordance BlkIPoleD general
79 Block Close failure BlkIClFail general
79 Block opening failure BlkIOpFail general
79 External Block BlkExt general
79 External Block Comms BlkExtComs general
79 External Block Input BlkExtDI general
79 Block Start failure BlkIntInFa general
79 Block A Start failure BlkIAInFa general
79 Block B Start failure BlkIBInFa general
79 Block C Start failure BlkICInFa general
79 Block End of cycle BlkICyEnd general
79 Block manual closing BlkIManCl general
79 Block Trip In Safety time BlkITrMaSe general
79 Block Incomplete sequence BlkInSec general
79 Block TC Failure BlkClsTrip general

Ingeteam Power Technology S.A.


User Manual 252
AUTOMATISMS 

Commands

The recloser commands are in the node PROT/ZRREC1:

❑ "DOrdReEn" . It enables/Disables the recloser. This command only operates, when the recloser is enabled by setting. It is
maintained at shutdown.
❑ "DOrdReclEn" It enables/Disables the recloser in local mode. This command only operates, when the recloser is enabled
by setting and in local mode. It is maintained at shutdown.
❑ BlkRec. It blocks/unblocks the recloser. It is not maintained at shutdown.
❑ "DOrdRecIni". It resets the recloser counters.
❑ "1P mode".27 It enables/disables the 1P mode, when the setting “Reclose mode” is "Configurable". With these
commands the recloser mode can be 1 P, 1P/3P or blocked.
❑ "3P mode".27 It enables/disables the 3P mode, when the setting “Reclose mode” is "Configurable". With these
commands the recloser mode can be 3 P, 1P/3P or blocked.

6.2.1.1 Reclosure counters


There are independent reclosure counters for the first (single-pole and three-pole), second, third, fourth reclosures and for the
totals.

They are stored in a non-volatile memory and displayed in the statistical data (communications and display).

These counters can be set to 0 by command.

6.2.1.2 Excessive number of trips


It allows the number of trips within the time to be limited.

A signal is generated the trip limit is exceeded (“Reclose number” setting) within a set time (“Trips exceeded window (min)”
setting in the CBOU node).

It sets recloser to “Internal block”, signalling “Excessive nbr trips” and “Definitive trip”.

6.2.2 General operation


After a certain period following the introduction of voltage (or after resetting), the recloser enters in one of the states:

❑ If the recloser is enabled:


 Supervising status when the breaker is closed (passing through manual closure) or
 Manual Opening (manual opening block) if the breaker is open.
❑ If the recloser is disabled or there is a block signal, the reclosure cycle is not launched and it remains in the blocked status
Figure 157 Recloser initialization

It remains in the Manual Opening and Definitive Trip statuses until the breaker is closed manually.

Following the closure:

❑ If the breaker does not open during the block (or reclaim) time, it goes to Supervising status.
❑ If there is a manual opening, it enters Manual Opening Block.

Ingeteam Power Technology S.A.


User Manual 253
AUTOMATISMS 

❑ If there is an opening by a protection, it enters Definitive Trip Block.


If the protection acts but the breaker does not open (or the trip remains active) during the programmed time, it enters internal
block due to opening failure and the corresponding signal is activated. It leaves this status following a manual opening, a breaker
closure command or a reset.

The Supervising (or standby) status is maintained until:

❑ There is a manual opening.


❑ The protection acts and opens the breaker, initiating the cycle when applicable.
The cycle consists of 1 to 3 reclosures.

During each cycle a programmed time is observed and the breaker closes. If the breaker does not trip due to a protection within
the reclaim time, the Supervising (standby) status is entered. If it does, the following closure is initiated. If this was the last, the
Definitive Trip is initiated.

If, following the action of the protection, the breaker does not open in the preset time or the relay continues to trip, the internal
block begins to operate. If, following a closure and while the safety time is being counted, there is a manual opening. In this case, it
enters Manual Opening Block and exits the cycle.

If, while the reclosure time is being counted, a manual closure is produced, the recloser aborts the reclosure cycle and enters
“Manual closure”. Following the corresponding reclaim time, it returns to standby.

If, once closed, a reset is received, it also enters manual closure.

The action of the external block prevents the cycle from being entered, or the exit from any ongoing cycle. If the breaker opens
while the block is in effect, it enters Definitive Trip block.

If the synchrocheck function is enabled and the synchrocheck monitoring setting is set to “YES”, this function must issue closure
permission in order for the closure relay to be activated.

The figures below show the sequence of events for a reclosure which has been programmed for three reclosure attempts (TR1, TR2
and TR3, respectively), with a reclaim time of Tsec, for different situations:

a.- Successful first reclosure.

Once the Supervising status has been reached, a new trip causes a new cycle to begin and reclosure 1 is started once more, as
shown below:

Ingeteam Power Technology S.A.


User Manual 254
AUTOMATISMS 

b.- Successful second reclosure.

c.- Successful third reclosure.

d.- Changes to definitive trip after exhausting the number of programmed reclosures.

e.- Changes to definitive trip due to a trip during the reclaim time following a manual closure.

Ingeteam Power Technology S.A.


User Manual 255
AUTOMATISMS 

6.2.3 Post-trip reclosure permission mask


They are independent for each of the protection units and are configured in the protection nodes.

The enabling of the corresponding R1, R2 and R3 post-trip reclosure permission mask is checked with each trip. If they are not
enabled, the reclosure cycle is interrupted.

In the event of simultaneous trips (before the opening of the breaker), the units with reclosure permission are taken into account in
order start the reclosure cycle.

Additionally, the trips which force the recloser to enter a block are also checked.

If consecutive trips are produced in different units, the relay reviews the tripped units’ masks and allows as many reclosures as
correspond to the minimum number allowed for the units involved.

That is, if the minimum number of reclosures is set to 3, reclosures 1, 2 and 3 are allowed.

Once the number of permitted cycles has been exceeded, a new trip causes the recloser to enter “Definitive trip block”.

Reclosable trips

These are trips that are capable of initiating the reclosure cycle is programmed accordingly. In general, they are trips corresponding
to the overcurrent and distance units, as well as the external trip inputs.

Each trip’s programming options are:

❑ Reclosure following a trip set to “YES”


In order to allow reclosure following a specific trip type, the reclosure permission settings must be set to “YES”.

If various units issue a trip command during a fault and at least one of the tripped units has reclosure permission, the reclosure
cycle is initiated, unless one of the units is set to produce a 79 block.

❑ Reclosure following a trip set to “NO”


If, in the event of simultaneous trips, reclosure is not to be produced by a specific unit but rather the units with permission are to
have precedence, i.e., the reclosure cycle is to be initiated.

Likewise, there are various unit block inputs (for status and for pulses), thus making it possible to transfer any signal that is to be
used to avoid the reclosure to this input.

Non-reclosable trips

If a non-reclosable trip is produced (27, 59, 59N, 81, 81R), the reclosure unit will not launch the reclosure sequence for this cause
and, depending on whether the reclosure block mask has been set to “YES”, it will force the recloser to enter the definitive trip
status.

If the trip does not open the breaker (because it has not given rise to the general trip), the recloser will remain in its current status.

Non-reclosable unit’s can be made to produce a reclosure by means of the connection to the trip output corresponding to the
“Configurable autoreclose” input.

Recloser block due to trip

This is used when a specific unit is not to produce a reclosure following a trip and when this unit is to prevail over those with
permissions in the event of simultaneous trips.

If this mask is not used, two units may trip simultaneously and the recloser may reclose due to one of the units being reclosable.

In the event of the non-reclosable unit tripping on its own, the breaker will open and remain in a blocked status.

In addition to these masks, the relay has logic inputs that allow the recloser to be blocked. Through the logical assignment of
internal signals to these inputs, the user can modify the operation of the recloser.

Each protection unit has an independent setting which is used to enable or disable this unit’s reclosure due to trip permissions. The
reference is “ReC1Perm”. The setting is configured as a menu of options.

The PacFactory has a drop-down menu showing the possible combinations. These options are different between the distance units
that generates single-pole trip and the units that only produces three-pole trip:

Ingeteam Power Technology S.A.


User Manual 256
AUTOMATISMS 

Table 147 Options of reclosure permissions following trip (tripolar units)

Data Reference
0 NO None reclose is allowed
1 Reclose 1 Only the first reclose is allowed.
2 Reclose 2 Only the second reclose is allowed.
3 Reclose 1-2 The first and second recloses are allowed.
4 Reclose 3 Only the thrird reclose is allowed.
5 Reclose 1-3 The first and thrird recloses are allowed.
6 Reclose 2-3 The second and thrird recloses are allowed.
7 Reclose 1-2-3 All recloses are allowed
8 Reclose 4 Only the fourth reclose is allowed.
9 Reclose 1-4 The first and fourth recloses are allowed.
10 Reclose 2-4 The second and fourth recloses are allowed.
11 Reclose 1-2-4 The first, second and fourth recloses are allowed.
12 Reclose 3-4 The thrird and fourth recloses are allowed.
13 Reclose 1-3-4 The first, thrird and fourth recloses are allowed.
14 Reclose 2-3-4 The second, thrird and fourth recloses are allowed.
15 Reclose 1-2-3-4 All recloses are allowed

Table 148 Options of reclosure permissions following trip (distance units with one pole trip)

Data Reference
0 NO None reclose is allowed after a trip of the unit
1 Reclose 1 (1P) Only the first reclose is allowed after a one pole trip of that unit
2 Reclose 1 (3P) Only the first reclose is allowed after a three poles trip of that unit
3 Reclose 1 (1P/3P) Only the first reclose is allowed after a trip of that unit
4 Reclose 2-3-4 The second, third and fourth recloses are allowed
5 Reclose1(1P)-2-3-4 The first (if it is one pole),the second, third and fourth recloses are allowed
6 Reclose1(3P)-2-3-4 The first (if it is three poles), the second, third and fourth recloses are allowed
7 Reclose 1-2-3-4 All recloses are allowed

Table 149 Options of reclosure permissions following trip (distance units with three poles trip)

Data Reference
0 NO None reclose is allowed after a trip of the unit
2 Reclose 1 (3P) Only the first reclose is allowed after a trip of that unit
4 Reclose 2-3-4 The second, third and fourth recloses are allowed after a trip of that unit
7 Reclose 1-2-3-4 All recloses are allowed after a trip of that unit

Table 150 Reclosure permissions following trip (in each protection node)

Data Parameter Min. Max Step Remarks Type


ReclPerm Reclosure permission 0 255 1 Int32

Ingeteam Power Technology S.A.


User Manual 257
AUTOMATISMS 

Figure 158 Recloser start

Ingeteam Power Technology S.A.


User Manual 258
AUTOMATISMS 

Figure 159 Example of trip and reclosure permission operation

Ingeteam Power Technology S.A.


User Manual 259
AUTOMATISMS 

6.2.4 Fault type selection


Depending on which unit has provoked the initiation of the reclosure process, the reclosure time to elapse before the generation of
the reclosure signal, as well as the reclaim time following the reclosure, is selected.

Internal Trips

Depending on the type of trip produced, there are 2 types of reclosure:

❑ Reclosure following a single-pole trip. This trip is produced by distance zone 1 and teleprotection unit.
❑ Reclosure following a three-pole trip (the rest).
If a single-pole trip evolves to a three-pole trip before the reclosing, the times are restarted in accordance with the three-pole trip.

External trips

Includes the following signals:

❑ DPE - External protection trip: Can be single-pole or three-pole.


❑ DPR-Reclosable programmable trip. An internal signal which is wired for logics and whose activation allows the reclosure
cycle to be initiated.
Upon the opening of the breaker and once it has been determined whether the fault is single-pole or three-pole, a reclosure time
that is programmed in accordance with the chosen setting is launched.

6.2.5 Breaker open timeout


Once the relay has tripped (activation of the general trip), the recloser waits during the opening failure time, till the breaker opens
(by contact) and the trip disappears. If the breaker does not open upon the conclusion of this time, “opening failure block” is
entered.

If during this programmed period of time the breaker opens, the ongoing cycle is initiated and the “79CC-Ongoing cycle” signal is
activated.

This signal will remain active until the cycle terminates upon its completion and a standby or block status is entered.

If the 52 NO and NC inputs are programmed, the 52b (NC) will be taken into consideration to detect the opening. If only the 52a
(NO) input is programmed, this signal at zero will be used as an open status.

6.2.6 Number of reclosures available


The total number of reclosures can be selected by settings.

The reclosures which are to be possible following the tripping of a specific unit can also be selected.

The enabling of the corresponding R1, R2, R3 and R4 permission mask is checked with each trip. If they are not enabled, the
reclosure cycle is interrupted.

In the event of simultaneous trips (before the opening of 52), the units with reclosure permission are taken into account in order
start the reclosure cycle.

Additionally, the trips which force the recloser to enter a block are also checked.

If consecutive trips are produced in different units, the relay reviews the tripped units’ masks and allows as many reclosures as
correspond to the minimum number allowed for the units involved. That is, if the minimum number of reclosures is set to 3,
reclosures 1, 2 and 3 are allowed.

Once the number of permitted cycles has been exceeded, a new trip causes the recloser to enter “Definitive trip block”.

All the trips (reclosable, non-reclosable and block) are checked up to the moment in which the breaker opens.

Any block trips which appear are sent directly to a blocked recloser.

Ingeteam Power Technology S.A.


User Manual 260
AUTOMATISMS 

If there are only reclosable trips, the reclosure cycle is begun with the time of the first reclosable produced by the trip.

Examples of operation.

The total number of reclosure cycles is set to 2 and Autoreclose mode to Dependent.

Example 1:

❑ Unit 50 trips (three-pole trip with reclosure available in all except the first one). Recloser does not reclose as the reclosure
permission is not allowed in CC1. Recloser would enter “Internal Block-Definitive Trip”
Example 2:

❑ 52 is closed and reclaim time following manual closure is initiated.


❑ Unit 51N trips (with R1, R2 and R3 reclosure permission for three-pole trips). 79 recloses with “Three-pole Reclose 1 time
(s)”.
❑ With 52 closed, and while “Reclaim time Ph-Ph (s)” is running, unit 50 trips (with R2 and R3 reclosure permission)
Reclosure R2 is not performed because the first trips has been three-pole. Recloser would enter “Internal Block-Definitive
Trip”
Example 3:

❑ In standby, Zone 1 single-pole trips (with R1 reclosure permission for single-pole trips). 79 recloses with “single-pole
Reclose 1 time (s)”.
❑ With 52 closed, and while “Reclaim time ground (s)” is running, a three-pole trip happens (with R2 and R3 reclosure
permission for three-pole trips). 79 recloses with “Reclose 2 time (s)”.
❑ With 52 closed, and while “Reclaim time ground (s)” is running, a three-pole trip happens (with R2 and R3 reclosure
permission for three-pole trips). 79 recloses with “Reclose 3 time (s)”.
❑ With 52 closed, and while “Reclaim time ground (s)” is running, a three-pole trip. 79 recloses with “Reclose 3 time (s)”.
Recloser does not reclose because the maximum reclosure number is exceeded. Recloser would enter “Internal Block-
Definitive Trip”
Example 4:

❑ While in standby, a 50 trip with R1 permission is produced and, before 52 opens, another 50N with R2 permission,
programmed without blocking, trip is produced.
❑ In this case, the 50 trip would take precedence, provoking the reclosure cycle.
Example 5:

❑ While in standby, a 50 trip with R1 permission is produced and, before 52 opens, another 50N programmed with blocking
trip is produced.
❑ In this case, when the 50N trip is produced and the breaker opens, the reclosure cycle would be interrupted and “Internal
Block-Definitive Trip” would be entered.

6.2.7 Reference voltage monitoring


This is used to wait for the activation of an external signal before allowing a reclosure. For example, to wait for the disappearance
of the line voltage following a trip (if there were motors or batteries connected to the line) or for a specific network condition
(power fluctuations, etc).

This monitoring is equivalent to a pause signal that halts the reclosure cycle during the VREF timeout.

It operates as follows:

❑ Once the breaker has opened and the trip has dropped out, the reclosure cycle is initiated and the reclosure time is
launched.
❑ In the absence of VREF, “VREF timeout” is launched, during which the VREF signal should be activated to allow the
continuation of the reclosure process.

Ingeteam Power Technology S.A.


User Manual 261
AUTOMATISMS 

❑ If the VREF signal does not appear prior to the elapse of this time, the internal 79 block due to absence of VREF” status is
entered.
❑ This status is cancelled by means of a closure or following the activation of the recloser reset input.

Figure 160 Reference voltage monitoring scheme

6.2.8 Re-initiation of reclosure time


The digital “Pause with reclosure reinitiation” input is used to reset the reclosure time counter to zero.

When the “Pause with reclosure reinitiation” input is activated, the recloser time counter (dead time) is reset to zero and the 79 is
halted until this input is cleared.

When this input is deactivated, the reclosure time count is restarted.

6.2.9 Pausing of reclosure time


The digital “Pause input” input is used to pause the reclosure time counter.

When this input is activated, the reclosure time counter (dead time) is halted until this input is cleared.

When this input is deactivated, the reclosure time count continues.

Figure 161 Reclosure time with pause and restart scheme

Ingeteam Power Technology S.A.


User Manual 262
AUTOMATISMS 

6.2.10 Incomplete sequence block


The two pause inputs can be used to wait for a certain signal, although the cycle can be extended indefinitely. It is thus important
to prevent the recloser from remaining permanently in the current cycle.

This timed is used to check that the recloser has exceeded a defined time without issuing a closure command nor becoming
blocked or resetting, thus causing the recloser to enter a block by incomplete sequence status.

Figure 162 Block by incomplete sequence scheme

6.2.11 Synchronism monitoring


It only applies to three-pole trips. If the trip is single-pole, the synchronism is not checked before reclosure command.

After a three-pole trip, if a specific reclosure is set to “monitored by synchronism” and once the reclosure time has elapsed, there is
a maximum timeout equivalent to the “Sync. Delay Time (s)” setting in which the “synchronism permission” signal is to activate.
Upon the issue of the synchronism permission the reclosure command is activated.

If synchronism permission is not activated, the “Block due to lack of synchronism” status is entered.

The first and the rest of the reclosures can be set to monitoring by synchronism by means of a setting. This allows the first
reclosures to be carried out quickly and without the need to check for synchronism, in the case of specific faults, and normal
reclosures for the rest.

Settings can be used to establish whether the synchronism is to check the relay’s functioning or that or an external input.

There is a setting within the synchronism unit to enable monitoring by synchronism for the recloser and for manual closing. As they
are independent settings, by disabling function 25 it is possible to monitor the reclosure with the external synchronism input.

If the setting “Synchrocheck type” is internal, the recloser waits the permission signal is activated. If the setting is external, the
recloser waits the activation of the “External syncro. Permission” input.

6.2.12 Closure block by trip circuit monitoring


If the closure block by trip circuit monitoring is set to “YES”, when the reclosure command is activated while the trip circuit
monitoring logic’s “trip circuit failure” signal, the closure command is not received and "Internal block due to failure in the SPV trip
circuit" is signalled.

This status is cancelled by the manual closure of the breaker following the elapse of the reclaim time.

6.2.13 52 closure timeout


Once the relay has issued a reclosure command (Activation of the 79 output-reclosure command), the breaker should close during
the closure failure timeout (by contact), If the breaker has not closed upon the conclusion of the timeout, "79 block due to closure
failure" s entered and the reclosure command is deactivated. If there is a trip during that time, the reclose command is cancelled
and a definitive trip is generated.

Ingeteam Power Technology S.A.


User Manual 263
AUTOMATISMS 

This status is cancelled by means of a manual closure.

If the 52 NO and NC inputs are programmed, the 52b (NC) will be taken into consideration to detect the closure.

If only the 52b (NC) is programmed, this denied signal will be used.

6.2.14 Recloser statuses


During its operation, the recloser enters through various statuses that are grouped together as stables and transitory.

6.2.14.1 Stable statuses


The "Recloser" function has 5 stable statuses, i.e., statuses in which it can remain indefinitely until something occurs to cancel
the status. They are:

❑ Out of service.
❑ Supervising, standby or reset.
❑ Manual opening.
❑ Internal block. Includes the Definitive trip.
❑ External block.
❑ Reclosure successful

6.2.14.1.1 Out of service


It will be placed out of service by settings (Enabled “NO”).

If it is in service, it can be placed out of service by pressing the R key on the keyboard or by means of a command or logical
input.

This status is exited when the function is enabled by a setting or command (R key or command or logical input). The transitory
manual closure setting is entered if the breaker is closed at this time. If the breaker is open, internal block (due to manual
opening) is entered.

The functioning is similar when the relay lights and the reclosure setting is set to “YES”.

6.2.14.1.2 Supervising or standby


This is the normal status, during which the recloser “monitors” for the occurrence of any trips. If any trips occur, the
recloser is activated.

This status is entered:

❑ Whenever the breaker is closed for a period that exceeds the reclaim time (following a manual closure or following
a trip).
❑ If the breaker is closed and in the external block status, when the block signal is cleared.
This status is exited:

❑ By the action of the protection and the subsequent opening of the breaker. If reclosure is to follow, the cycle is
initiated. If not, Definitive trip is entered.
❑ Due to the manual opening of the breaker. Manual Opening is entered.

6.2.14.1.3 Manual opening


This status is entered by a manual opening command (by command, contact or other causes, but not by a trip).

This status is cancelled when the 52 is closed manually (by command, contact, etc., by not by reclosure).

Ingeteam Power Technology S.A.


User Manual 264
AUTOMATISMS 

Figure 163 Manual opening

6.2.14.1.4 Internal block


There is a general internal block status with different signalling, in accordance with the cause. This status is entered as
result of different causes:

❑ Opening failure
❑ Closure failure
❑ Manual opening
❑ Three-phase Trip
❑ Definitive trip
❑ Incomplete sequence
The reclosure cycle is not started in this status. The cycle is abandoned if it has already been started and Definitive Trip is
signalled if the breaker has opened as a result of a protection trip.

This status is cancelled by the closure of the breaker following the elapse of the reclaim time.

In all cases, a generic “internal block” signal is activated, in addition to a specific signal identifying the cause of the block. In
those cases where the block status occurs after a trip and the opening of the 52, “definitive trip block” is also indicated.

Ingeteam Power Technology S.A.


User Manual 265
AUTOMATISMS 

Figure 164 Block scheme

Internal block as a result of an opening fault

This status is entered if, following the elapse of the breaker fault time after a trip, the breaker remains closed.

This status is cancelled when the breaker opens. The opening failure time is the same as that of the opening fault with
contact function.

Figure 165 Opening failure block scheme

DGITAL SIGNAL
General trip Time

DIGITAL SIGNAL S RECLAIM T


OPENING
52 DIGITAL SIGNAL
Phase A open command Recloser Lock opening failure
0
DIGITAL SIGNAL R
52_1 A Closed (Simple Log.)

Ingeteam Power Technology S.A.


User Manual 266
AUTOMATISMS 

Internal block as a result of a closure failure

This status is entered of any of the following conditions are met:

❑ If the breaker remains open following the elapse of the breaker closure failure time after a closure command.
“Definitive trip” is also signalled.
❑ If the trip circuit failure block is enabled. If, when activating the closure command, the command activates the trip
and closure circuits’ monitoring logic’s "trip circuit failure” signal, the closure command is not issued and “closure
command blocked" is signalled. Following the elapse of the closure failure time, the block by closure failure status
is entered.
This status is cancelled by the manual closure of the breaker following the elapse of the reclaim time.

Internal block by open breaker (manual opening)

This status is entered by a manual opening or by means of a breaker command when the 79 is in standby or in a current
cycle.

It is cancelled by a manual breaker closure. The transitory Manual Closure status is entered.

Definitive trip

This status is activated following a trip that fails to produce a reclosure due to a 79 block or for having reached the end of
the cycle with the fault intact:

❑ A trip is produced within a period that is shorter than the reclaim time following a manual breaker closure.
❑ A trip is produced in a period that is shorter than the reclaim time following the last reclosure.
❑ A protection trip is produced while the block status is active.
❑ A protection trip is produced while the recloser is out of service.
❑ An excessive number of trips are produced within a defined time.
❑ The recloser does not issue a closure command due a voltage monitoring failure (synchronism).
❑ The recloser issues a closure command and the recloser does not close in the closure failure time.
❑ The recloser does not issue a closure command due to an interlock (for example, a trip circuit failure) and the
recloser does not close in the closure failure time.
❑ The voltage presence conditions are not met during a current cycle.
❑ If a trip does not produce a reclosure due the programming of a block (with the block taking precedence over other
functions with permissions) or the absence of the programming of a reclosure (unless there is another function
with reclosure permission trips simultaneously).
❑ A switch onto fault function trip following a manual closure.
❑ By incomplete sequence.
This status is cancelled by one of the following causes.

❑ Manual breaker closure, following which the transitory MC (Manual Closure) status is activated.
❑ Reception of recloser’s reset input.

Ingeteam Power Technology S.A.


User Manual 267
AUTOMATISMS 

Figure 166 Internal block statuses diagram

Incomplete sequence block.

See the “Incomplete sequence block” section.

6.2.14.1.5 External block


This status is activated by:

❑ Activation of the recloser’s logical block input.


❑ Reception of a block command. There are block and unblock commands.
No cycles are started while the block is active and any cycles which had already been started are terminated. “internal 79
block”, “external 79 block by communication” or “external 79 block by input” is signalled. “Definitive trip + Trip &
extern.block” is also signalled if the breaker has been opened by a protection trip (general trip) or by an external protection.

6.2.14.1.6 Successful reclosure


Successful reclosure is signalled when, following the issue of a closure command and the closure of the three 52 poles, the
reclaim time elapses without a new trip being produced.

The “successful reclosure” signal is activated and remains so until the relay trips once again.

6.2.14.2 Transitory statuses


Transitory statues are those statuses in which the system cannot remain for longer than a specific time.

Ingeteam Power Technology S.A.


User Manual 268
AUTOMATISMS 

6.2.14.2.1 Manual closure


This status is activated as a result of a manual breaker closure or by means of a command (not be reclosure), independently
of whether a cycle is in progress. It maximum duration is equivalent to the reclaim time following manual closure.

This status is cancelled by one of the following causes:

❑ Due to the manual opening of the breaker. An internal block due to manual opening is activated.
❑ Due to the action of the protection. An internal block due to definitive trip is activated.
❑ Following the elapse of the safety time. Standby is activated.
❑ Due to the activation of the external block input or block command. An external block is activated.
❑ Due to the action of the protection following an opening failure (52 does not open or the unit remains tripped). An
internal block due to an opening fault is activated.

Figure 167 Reclaim time following manual closure

6.2.14.2.2 First closure. Phase 1: Timed.


This is reached at the start of the cycle. Its maximum duration is equivalent to the first closure time. If monitoring by
synchronism is activated, the synchronism timeout is added, if there is no synchronism upon the termination of the
reclosure time count. There are different settings for the first single-pole and three-pole reclosing.

At the same time as the closure time count, the monitoring by VREF (during a maximum “VREF timeout” period) and by
synchronism.

This is cancelled by:

❑ Manual breaker closure. “Internal block” is activated and “Temporary block by manual closure” is signalled.
❑ Following the elapse of the reclosure time. Phase 2 of the closure is entered.
❑ Activation of the external block input. “External block” is activated.
❑ Failure to meet the reference voltage (VREF) monitoring conditions. An internal block is activated and Internal
block due to absence of VREF and Definitive trip is signalled.
❑ Failure to meet the synchronism monitoring conditions. An internal block is activated and Internal block due to
synchronism fault and Definitive trip is signalled.

Ingeteam Power Technology S.A.


User Manual 269
AUTOMATISMS 

Figure 168 Reclosure line scheme

Figure 169 Opening timeout scheme

Ingeteam Power Technology S.A.


User Manual 270
AUTOMATISMS 

Figure 170 Reclosure timeout scheme

6.2.14.2.3 First closure. Phase 2: closure command.


This is reached once the first closure timed is complied with. It activates the closure command and increments the closures
meter.

It is cancelled:

❑ Because the breaker has closed in the permitted time. Phase 3 entered.
❑ Because the permitted time has elapsed without the closure of the breaker. An internal block is activated and
“Internal block due to closure failure” and “Definitive trip” is signalled. The relay’s Breaker failure due to contact
signal is also activated.

6.2.14.2.4 First closure. Phase 3: breaker closure.


This is reached following the closure command issued in phase 2 when the breaker has closed. It maximum duration is
equivalent to the reclaim time following automatic closure. It deactivates the closure signal.

It is cancelled:

❑ Due to the manual opening of the breaker. “Internal block” is activated and “Internal block by manual opening” is
signalled.
❑ Due to a protection trip. The second reclosure process is entered, phase 1.
❑ Because the block time has elapsed without the opening of the breaker. Standby is activated.
A low current permanent fault may cause tripping following the elapse of the safety period. To avoid, in the event of all the
reclosures being first reclosures and no definitive trip is produced, the automatic extension of the timeout due the pick up
of a unit capable of producing a reclosable general trip in standby (“Trip permission with 79 in standby” set to “YES”) until
reset or a trip is produced.

Ingeteam Power Technology S.A.


User Manual 271
AUTOMATISMS 

Figure 171 Closure scheme

Figure 172 Timeout following closure scheme

6.2.14.2.5 Second closure


This is reached as a result of protection trip in the timeout following the closure originated by the first closure. Its
functioning (phases, activated relays, etc.) is the same as that of the first closure.

6.2.14.2.6 Third closure


This is reached as a result of protection trip in the timeout following the closure originated by the second closure. Its
functioning (phases, activated relays, etc.) is the same as that of the first closure.

6.2.14.2.7 Ongoing cycle


The status of the recloser while activated, from the first trip and the opening of the breaker up to the closure of the breaker
and the elapse of the safety period (successful reclosure), or until all the programmed reclosures have been unsuccessfully
executed. In the first case, the recloser switches to “supervising” and, in the second, to “definitive trip”

If, during the operating cycle, a manual order (or command) is given to the circuit breaker, the recloser suspends the cycle
and switches "internal block due to manual opening" or "manual closure".

These same applies if a reset signal is received.

Ingeteam Power Technology S.A.


User Manual 272
AUTOMATISMS 

Figure 173 Ongoing cycle scheme

6.2.15 Application with two breakers


When having a double breaker configuration, both breakers trip at the same time. With this function, the recloser operation mode
with the two breakers can be selected between:

❑ Both breakers reclose simultaneously.


❑ Combine the closings following a programmed sequence.
❑ Automatically, only closes one of the breakers.
In any of those cases, once the security time has passed, both breakers must be closed in order to finish the reclosing successfully.

After a single phase trip, the recloser waits for the opening of only one pole in both breakers. If more than one pole opens, it blocks
and signalizes definitive trip. If the tripped pole does not open in both breakers, after waiting a time, it blocks by open failure. To
begin the process, both breakers have to open.

If both breakers open correctly, the reclosing cycle begins after the time set, to close the breaker selected with the closing
sequence. If a single phase fault is detected, it can evolve to a three phase fault during the ongoing cycle. At this moment, a new
three phase reclosing waiting time begins to give closing permission. If, when giving a reclosing permission, the breaker is open or
tripped, it blocks.

The recloser considers that a breaker is blocked, if a manual opening has been made or if it is blocked by a digital input or setting. In
this case, it does not operate, and will only be able to operate the other breaker if the setting "Permit closure 52_x with 52_y
blocked" says so.

With manual closing of a breaker, the recloser is blocked by manual closing , counting the safety time after manual closing.

The "Closing sequence" defines how the recloser acts:

❑ Brk1. The reclose cycle only generates close command for breaker 1.
 Generates open command on both breakers and wait for them to open. If any of them is not open,then it will block by
open failure and not continue reclosure cycle.
 Generates close command for breaker 1 and waits for closure (with or without synchronism). Breaker 2 is not closed.
❑ Brk2. The reclose cycle only generates close command for breaker 2.It is same as above, but breakers are exchanged.
❑ Brk1 and Brk2. The reclose cycle generates close command for both breakers simultaneously.
 Generates open command on both breakers and wait for them to open. If any of them is not open,then it will block by
open failure and not continue reclosure cycle.
 Generates close command for both breakers and wait for closure (with or without separate synchronism) to pass
safety time. If one of them gives closure failure, the setting value Block by Br1 Close Fail is checked
 NO:The closing sequence continues considering only the other breaker
 YES: Recloser is locked and it will block by close failure.
 If either closed, it starts counting recloser safety time.
 If recloser safety time ends up without trips and breaker is closed, it returns to standby.
 If new protection trip is produced, a new closing sequence is started
 If an excessive number of trips are produced in any breaker, then it will block and not continue reclosure cycle
❑ Brk1 then Brk2. The reclose cycle generates close command for breaker 1. When the reclose cycle has finished
successfully (Successful Reclosing), the breaker 2 close command is generated, once the sequence time since the breaker
1 close command has finished

Ingeteam Power Technology S.A.


User Manual 273
AUTOMATISMS 

 Generates open command on both breakers and wait for them to open. If any of them is not open, then it will block by
open failure and not continue reclosure cycle
 Generates close command for breaker 1 and waits for closure (with or without synchronism). When recloser safety
time ends up without trips and breaker 1 is closed (Successful Reclosing), the breaker 2 close command is generated. If
one of them gives closure failure, the setting value Block by Br1 Close Fail is checked
 NO: Closing sequence continues considering only the breaker 2 checking synchronism 2.
 YES: Recloser is locked and it will block by close failure.
 If an excessive number of trips are produced in any breaker, then it will block and not continue reclosure cycle
❑ Brk2 then Brk1. The reclose cycle generates close command for breaker 2. When the reclose cycle has finished
successfully (Successful Reclosing), the breaker 1 close command is generated, once the sequence time since the breaker
2 close command has finished. It is same as above, but breakers are exchanged.
❑ Brk1 - Brk2. The reclose cycle generates close command for breaker 1. When the breaker 1 has closed, the sequence time
starts. When the sequence time finishes without a new trip, the breaker 2 close command is generated. If during sequence
time with the breaker 1 closed, there is a trip, the next reclose cycle starts until the maximum allowed reclosure by setting.
The sequence is the following:
 Generates open command on both breakers and wait for them to open. If any of them is not open, then it will
block by open failure and not continue reclosure cycle
 Generates close command for breaker 1 and waits for closure (with or without synchronism). When the
breaker 1 is closed, the sequence time starts. When the sequence time finishes without a new trip, the breaker
2 close command is generated. If breaker 1 gives closure failure, the setting value Block by Br1 Close Fail is
checked
 NO: Closing sequence continues considering only the breaker 2 checking synchronism 2.
 YES: Recloser is locked and it will block by close failure.
 If an excessive number of trips are produced in any breaker, then it will block and not continue reclosure cycle
❑ Brk2 - Brk1. The reclose cycle generates close command for breaker 2. When the breaker 1 has closed, the sequence time
starts. When the sequence time finishes without a new trip, the breaker 2 close command is generated. It is same as Brk1 -
Brk2, but breakers are exchanged.
If the close sequence is "Brk1 then Brk2" or " Brk1 - Brk2" and breaker 1 is blocked or in manual opening, the breaker 2 close
condition (ReCond2) uses the first breaker´s setting (ReCond1). In case of "Brk2 then Brk1" or " Brk2 - Brk1" and breaker 2 is
blocked or in manual opening, the breaker 1 close condition (ReCond1) uses the second breaker´s setting (ReCond2).

It has independent settings and outputs (logical node PROT/SECRREC)

Table 151 shows the settings of this function:

❑ Select 2 breakers
It allows operating with two breakers (“YES”). In that case, follows the settings detailed bellow to include a second breaker
in the closing scheme.

❑ Closing sequence
Definition of the breaker or breakers that will reclose automatically. In the case of having to reclose two breakers, it can be
done simultaneously or following a sequence.

❑ Sequence time (ms):


Time passed between the first breaker reclosing order and the second, following the aforementioned closing sequence.
Used only by the "Brk1 then Brk2" and "Brk2 then Brk1" sequences.

❑ Block by Br2 Close Fail


When set to “YES”, it blocks the recloser if there is closing failure in the breaker 1.

When set to “NO”, when there is breaker 1 close failure, it allows following the sequence selected for closing the breaker 2.

❑ Block by Br1 Close Fail


When set to “YES”, it blocks the recloser if there is closing failure in the breaker 2.

Ingeteam Power Technology S.A.


User Manual 274
AUTOMATISMS 

When set to “NO”, when there is breaker 2 close failure, it allows following the sequence selected for closing the breaker 1

❑ Br1 Permission if 2 blocked


When set to “YES”, it allows the closing of the breaker 1, if the breaker 2 is blocked.

When set to “NO”, it does not allow the closing of the breaker 1, if the breaker 2 is blocked.

❑ Br2 Permission if 1 blocked


When set to “YES”, it allows the closing of the breaker 2, if the breaker 1 is blocked.

When set to “NO”, it does not allow the closing of the breaker 2, if the breaker 1 is blocked.

❑ 52_1 reclosing block


Selects the signal which, when active, blocks the closing of the breaker 1.

❑ 52_2 reclosing block


Selects the signal which, when active, blocks the closing of the breaker 2.

❑ Enable Events record


Allows the generation of protection events associated to the function. If set to “NO”, the function’s protection events are
not generated. If set to “YES”, the function’s specific mask is contemplated.

Table 151 Two breaker recloser settings

Data Setting Minimum Maximum Step Remarks Type


SelBr2 Select 2 breakers NO/YES Boolean
Brk1 (0)
Brk2 (1)
Brk1 and Brk2 (2)
ClSec Closing sequence Brk1 then Brk2 (3) enum
Brk2 then Brk1 (4)
Brk1 - Brk2 (5)
Brk2 - Brk1 (6)
SecTmms Sequence time (ms): 50 600000 10 Int32
BlkF1 Block by Br2 Close Fail NO/YES Boolean
BlkF2 Block by Br1 Close Fail NO/YES Boolean
Cl1Br2LcEna Br1 Permission if 2 blocked NO/YES Boolean
Cl2Br1LcEna Br2 Permission if 1 blocked NO/YES Boolean
BlkBr1 52_1 reclosing block Int32
BlkBr2 52_2 reclosing block Int32
MaskEna Enable Events record NO/YES Boolean

Table 152 shows the outputs of the breaker 1:

❑ Reset sequence.
It stops the closing sequence and is activated in the following situations:

 The recloser is in standby.


 The recloser is blocked. Also if there is a closing failure in any of the breakers.
 Start of each of the ongoing cycles.
❑ Signals of the breaker 1:
 52_1 Reclose Command: Breaker 1 reclosing activation order.
 52_1 closure failure: Breaker 1 closure failure activation.
 The breaker 1 is not closed, after the closing time.
 52_1 Manual opening: Breaker 1 manual opening activation signal.

Ingeteam Power Technology S.A.


User Manual 275
AUTOMATISMS 

 The opening of the breaker is detected without initializing the recloser cycle. Once the opening is detected, waits two
cycles before signalling manual opening. This time avoids the opening by an external trip.
 52_1 blocked. Breaker 1 blocking status, caused by the setting “52_1 reclosing lock”, the internal signal “Operations
Locked - Br.1” or the manual opening of the breaker.
 52_1 Successful Reclosing: Breaker 1 reclosing activation order state..Breaker 1 has properly completed its reclosing
cycle.
❑ Signals of the breaker 2:
 52_2 Reclose Command: Breaker 2 reclosing activation order.
 52_2 closure failure: Breaker 2 closure failure activation.
 The breaker 1 is not closed, after the closing time.
 52_2 Manual opening: Breaker 2 manual opening activation signal.
 The opening of the breaker is detected without initializing the recloser cycle. Once the opening is detected, waits two
cycles before signalling manual opening. This time avoids the opening by an external trip.
 52_2 blocked. Breaker 2 blocking status, caused by the setting “52_2 reclosing lock”, the internal signal “Operations
Locked - Br.2” or the manual opening of the breaker.
 52_2 Successful Reclosing: Breaker 2 reclosing activation order state..Breaker 2 has properly completed its reclosing
cycle.

Table 152 Two breaker recloser outputs (breaker 1)


Signal Data Atribute
Reset sequence ReSec general
52_1 Reclose Command RecOrdBrk1 general
52_1 closure failure RecFailBr1 general
52_1 Manual opening ManOpen1 general
52_1 blocked BlkBrk1 general
52_1 Successful Reclosing RecOK1 general
52_2 Reclose Command RecOrdBrk2 general
52_2 closure failure RecFailBr2 general
52_2 Manual opening ManOpen2 general
52_2 blocked BlkBrk2 general
52_2 Successful Reclosing RecOK2 general

Figura 174 Breakers` blocking type

Ingeteam Power Technology S.A.


User Manual 276
AUTOMATISMS 

Figure 175. Autoreclose sequence with 2 breakers

6.3 FREQUENCY RECLOSER

The unit, following a minimum frequency trip and in the case of the function having been enabled and not locked, will only attempt one
reclosure.

The logical input “Restoration trip (start)” must be activated, to start the reclosing.

When the trip occurs, the 79f-breaker closure lock signal is activated and the period programmed as the “definite trip timeout” is
observed. If the minimum frequency condition is set to “NO” or if the frequency is higher than the minimum programmed value during
the programmed “closure time”, a closure command is issued to the breaker. If the minimum voltage condition is set to “YES” and is
not met, the definitive trip is activated.

The 79f-breaker closure block will remain active until the reclosure or definitive trip conditions are met.

If the “Enab. maximum reset time” is set to “YES” and the programmed “maximum reset time (s)” elapses without the reclosure
conditions having been met, an internal block due to failure to meet conditions (with definitive trip) is activated. If the setting is set to
“NO”, the reclosure conditions are waited for indefinitely.

A “reclaim time” is observed following the closure. If a new minimum frequency trip occurs during this period, it moves to internal
block with definitive trip.

The frequency recloser’s general operation is shown in Figure 176 to Figure 183.

The settings used in this unit are shown in Table 153:

❑ Enabled. Indicates whether the function is enabled or not.


❑ Minimum F supervi. enabled. Indicates whether the minimum frequency monitoring is enabled or not.
❑ Minimum F for closing (Hz) Indicates the minimum frequency above which reset permission is given.

Ingeteam Power Technology S.A.


User Manual 277
AUTOMATISMS 

❑ Reposition time (s). Indicates the time during which the reset conditions must be met in order for the reset command to
be issued.
❑ After close safety time(s). Indicates the timeout following a reset command. No trips must be produced during this time
in order for the reclosure to be considered as successful. If a trip is produced, an end of cycle block is activated.
❑ Reset maximum time Enable. Indicates whether the maximum reset time limit is enabled.
❑ Reset maximum time (s). Indicates the maximum timeout in which the reset conditions are to be met. To the contrary, a
block due to the absence of reset conditions is generated.
❑ Minimum V supervi. enabled. Indicates whether the minimum voltage monitoring is enabled or not.
❑ Reclose Minimum Voltage. Indicates the minimum voltage above which reset permission is given.
❑ Synchrocheck supervision. Indicates whether the synchronism conditions check is enabled or not.
❑ F restoration blocking. Logic input, which selects the signal which, when active, blocks the frequency recloser.
❑ Restoration trip (start). Logic input, which selects the signal which, when active, indicates that a reclosable trip has been
produced.
❑ f restoration reset input. Logic input, which selects the signal which, when active, resets the frequency recloser.
❑ Synchrocheck type.28 Indicates whether the synchronism is internal or external.
❑ External syncro. Permission.28 Logical external synchronism permission logic. Selects the signal which, when active,
indicates the existence of permission for synchronism.
❑ Enable Events record. Allows the generation of protection events associated to the function. If set to “NO”, the function’s
protection events are not generated. If set to “YES”, the function’s specific mask is contemplated.

Table 153 Frequency recloser settings

Data Setting Minimum Maximum Step Remarks Type


FRecEna Enabled NO (0) / YES (1) enum
FminEna Minimum F supervi. enabled NO (0) / YES (1) enum
FminVal Minimum F for closing (Hz) 40 70 0.1 float
RepTms Reposition time (s) 1 3600 1 Int32
SegTms After close safety time(s) 1 600 1 float
ReTmLiEna Reset maximum time Enable NO (0) / YES (1) enum
MaxReTms Reset maximum time (s) 0 86400 1 Int32
VRecEna Minimum V supervi. enabled NO (0) / YES (1) enum
VrecVal Reclose Minimum Voltage 0 200 0.1 float
VSynEna Synchrocheck supervision NO (0) / YES (1) enum
LogInBlk F restoration blocking 1 Int32
LogInTr Restoration trip (start) 1 Int32
LogInRst f restoration reset input 1 Int32
MaskEna Enable Events Record 0 1 1 Boolean
SynTyp Synchrocheck type Internal/External enum
LogInExSy External syncro. Permission Int32

It has independent settings, commands and outputs:

❑ PROT/FRREC1 node
❑ Settings. There are 6 settings tables. See Table 153.
❑ There are no commands
❑ Outputs: Table 154 shows the function’s output data.
 Start reclosing F_RREC. Indicates the start of the reclosing cycle (Figure 177). It begins with the trip and finishes with a
successful reclosing or recloser blocked or the activation of the “f restoration reset input”.

28
Available from firmware version 5.25.16.1 and ICD version 7.0.0.2

Ingeteam Power Technology S.A.


User Manual 278
AUTOMATISMS 

 In progress F_RREC. It is active since the breaker is open by a trip until a successful reclosing or recloser blocked or the
activation of the “f restoration reset input” (Figure 183).
 Successful Reclosing F_RREC. Indicates a Successful reclosing (Figure 181). The safety time after closing has finished
and the breaker has not open, there is no trip and the “f restoration reset input” is desactivated.
 Recloser Safety time F_RREC. After a reclosing, the safety time is ongoing before the recloser goes to standby or Finally
Interlock (Figure 181).
 Block End Cycle F_RREC. Indicates the breaker is open or a trip has happened during the safety time (Figure 181).
 Block closure failure F_RREC. Indicates the recloser is in internal block, caused by a close failure (breaker supervision).
See Figure 181.
 Block opening failure F_RREC. . Indicates the recloser is in internal block, caused by an open failure (breaker
supervision). See Figure 178.
 Block reset cond. F_RREC. After the breaker opening, the recloser is waitng during the “Reset maximum time (s)” that
the reposition conditions are met. If the maximum time is enabled, when the time finishs without close command, the
recloser is blocked by absence reset conditions. See Figure 180.
 Reclosing Permission F_RREC. Indicates the reposition conditions are met (Figure 179).
 Reclosing Command F_RREC. Close command after all the setting conditions are met (Figure 179).
 Reclosing Blocked F_RREC. Indicates the recloser is blocked by setting, internal or external causes (Figure 182).
 Definitive Trip F_RREC. Definitive trip when the recloser is blocked by absence of reposition conditions, end of cycle or
close failure (Figure 182).
 Close Blocked F_RREC. Activated during the closure time (Figure 180).
 In standby F_RREC. Activated when the recloser is standby

Table 154 Frequency recloser outputs

Signal Data Attribute


Start reclosing F_RREC RecInit stVal
In progress F_RREC RecCyc (RecCycOn in Ed2) stVal (general in Ed2)
Successful Reclosing F_RREC ClOK stVal
Recloser Safety time F_RREC SecTime stVal
Block End Cycle F_RREC BlkCycEnd stVal
Block closure failure F_RREC BlkIClFail stVal
Block opening failure F_RREC BlkIOpFail stVal
Block reset cond. F_RREC BlkINoCond stVal
Reclosing Permission F_RREC Fperm stVal
Reclosing Command F_RREC FClOrd stVal
Reclosing Blocked F_RREC FRecBlk stVal
Definitive Trip F_RREC DefTrip general
Close Blocked F_RREC BrClBlk stVal
In standby F_RREC RestST stVal

Figure 176 Trip with reset scheme

Ingeteam Power Technology S.A.


User Manual 279
AUTOMATISMS 

Figure 177 Process start scheme

Figure 178 Opening timeout scheme

Figure 179 Reset permission scheme

Ingeteam Power Technology S.A.


User Manual 280
AUTOMATISMS 

Figure 180 Reset command scheme

Figure 181 Reset timeout scheme

Ingeteam Power Technology S.A.


User Manual 281
AUTOMATISMS 

Figure 182 Start scheme

Figure 183 Frequency recloser signals

Ingeteam Power Technology S.A.


User Manual 282
BREAKER AND A HALF CONFIGURATION 

7. BREAKER AND A HALF CONFIGURATION


The model ZT1 is specific for breaker and a half configurations.

The current inputs are independent for every breaker. There are two inputs for every phase.

The analog input 7 can be selected with the setting "Current 7 type" of the node TCIN:

❑ Ipol. The analog input 7 is used as polarization current.


❑ In2. The analog input 7 is used as Parallel line Neutral current 2.
The polarity of the phases of each of the breaker can be selected as incoming / outgoing, with the settings of the node TCIN:

❑ Local End polarity Br1. It selects the polarity (incoming / outgoing) of the currents IA1, IB1, IC1.
❑ Local End polarity Br2. It selects the polarity (incoming / outgoing) of the currents IA2, IB2, IC2.

Available analog inputs in model ZT1 are:

Model T1 T2 T3 T4 T5 T6 T7 T8 T9 T10 T11 T12


ZT1 I A1 I B1 I C1 I A2 I B2 I C2 In2/Ipol Vs2 Vs1 VA VB VC

In topology 52 ½, the total phase current is calculated as the sum of the current of each breaker, taking into account the polarity. If
incoming it´s sum, if outgoing it´s subtraction.

Br1 incoming Br1 incoming Br1 outgoing Br1 outgoing


Br2 incoming Br2 outgoing Br2 incoming Br2 outgoing
Ia = Ia1 + Ia2 Ia = Ia1 - Ia2 Ia = -Ia1 + Ia2 Ia = -Ia1 - Ia2

Ib = Ib1 + Ib2 Ib = Ib1 - Ib2 Ib = -Ib1 + Ib2 Ib = -Ib1 - Ib2

Ic = Ic1 + Ic2 Ic = Ic1 - Ic2 Ic = -Ic1 + Ic2 Ic = -Ic1 - Ic2

As neutral current, the zero sequence is used (3·I0).

The calculations for sequences are performed with total currents.

7.1 PROTECTION FUNCTIONS

The following points indicate the functions affected by the configuration 52 ½.

The breaker status follows the criteria:

❑ To consider closed, simply one of the breaker is closed


❑ To consider open, both breakers must be open.

Ingeteam Power Technology S.A.


User Manual 283
BREAKER AND A HALF CONFIGURATION 

Table 155 Available functions

ZT1
Distance functions
Quadrilateral Characteristic (5 zones) 
Mho Characteristic (5 zones) 
21 High Speed 
Zone 1 Extension 
Double Lines  (Nota 2)
Lines with Series Compensation 
CVT: Lines with Capacitive Voltage Transformers 
Common protection functions
SOFT Switch onto fault 
27 Undervoltage 
59 Overvoltage 
59N Zero sequence overvoltage 
47 V2 overvoltage protection 
Minimun voltage 
Frequency (81M/m) 
Frequency rate of change (81R) 
3x50/51 (67) Solo fasor
50N/51N (67N) Solo I0
50G/51G. Grounding overcurrent  (Nota 1)
46TOC (67Q), 46IOC(67Q) 
46FA Broken conductor 
50CSC Second harmonic restraint Solo fases
37 Undercurrent 
49 Thermal image  (Nota 3)
32 Power units 
Stub bus differential 
Teleprotection
Teleprotection (21) 
Teleprotection (67/67Q) 
Monitoring Units
68LE Load encroachment 
68FF Fuse failure 
78 Power Swing 
Fault locator 
Breaker Monitoring
k12 breaker monitoring per pole 
Closing and trip circuit monitoring 
Excessive number of trips 
Open pole / Faulted line detector 
Breaker status logic 
Pole discordance 
50BF breaker failure two breakers
50BF breaker failure (Single-pole/Three-pole) 
Low load breaker failure 
Automatisms two breakers
Synchronism 
Recloser (Single-pole/Three-pole) 
Frequency recloser 

Note 1: Available if the analog input 7 is used as polarization current.

Note 2: Available if the analog input 7 is used as Parallel line Neutral current 2.

Note 3: The phase unit is always available and the neutral is available when the analog input 7 is used as polarization current

Ingeteam Power Technology S.A.


User Manual 284
BREAKER AND A HALF CONFIGURATION 

Table 155 shows the available functions. Some of them that depends on the analog 7 type.

❑ Neutral overcurrent. It always uses the zero sequence.


❑ Directional. If the polarization current is not available, the I polarization is not allowed.
❑ Distance units. If In2 current is not available, current compensation is not used, independently of the value of the setting
"Km Module".
❑ The calculations for sequences are performed with total currents.
❑ Grounding overcurrent. It´s only available when analog input 7 is configured us polarization current.
❑ Neutral 50BF is not available.
❑ Breaker logic. It uses both breakers independently.

7.1.1 Distance functions


Phase measurements used are the sum of the current phasor of each breaker for both fundamental and harmonics.

If In2 current is not available, current compensation is not used, so the calculations of the characteristics don´t take into account
the settings of the 5 zones:

❑ Km Module. Indicates the mutual compensation factor module of the parallel lines.
❑ Km Angle (º). Indicates the parallel lines mutual compensation factor angle.
The signals used in each phase of the Mho characteristic are:

Table 156 Mho characteristic signals

Unit Sop (Operation signal) Spol (Polarization signal)


AN [ Ia + 3·I0  knx ] (|ZxGF|ZxAº) – Va Va1: current or memorized
BN [ Ib + 3·I0  knx ] (|ZxGF|ZxAº) – Vb Vb1: current or memorized
CN [ Ic + 3·I0  knx ] (|ZxGF|ZxAº) – Vc Vc1: current or memorized
AB Iab  (|ZxF|ZxAº) – Vab Vab1: current or memorized
BC Ibc  (|ZxF|ZxAº) – Vbc Vbc1: current or memorized
CA Ica  (|ZxF|ZxAº) – Vca Vca1: current or memorized

The signals used in each phase of the quadrilateral characteristic are:

Table 157 quadrilateral characteristic signals

Unit Ieq Vpol Ipol


AN [ Ia + 3·I0  k0x ] Va 3I0, 3I2 or Max(3I0, 3i2)
BN [ Ib + 3·I0  k0x ] Vb 3I0, 3I2·a or Max(3I0, 3I2·a)
CN [ Ic + 3·I0  k0x ] Vc 3I0, 3I2· a2 or Max(3I0, 3I2·a2)
AB Iab Vab I2· a2 or Iab
BC Ibc Vbc I2 or Ibc
CA Ica Vca I2· a or Ica

If In2 current is not available, current compensation is not used, the the calculations of SIR for CVT is:

Table 158 Calculating the SIR for Different Units

SIR for single phase faults SIR for single phase-phase faults
(Vnom/((Ia + 3·I0kn1 )·Z1)) - 1 (Unom/(Iab·Z1)) - 1
(Vnom/((Ib + 3·I0kn1 )·Z1)) - 1 (Unom/(Ibc·Z1)) - 1
(Vnom/((Ic + 3·I0kn1 )·Z1)) - 1 (Unom/(Ica·Z1)) - 1

Ingeteam Power Technology S.A.


User Manual 285
BREAKER AND A HALF CONFIGURATION 

7.1.2 General protection functions


Phase measurements used are the sum of the current phasor of each breaker for both fundamental and harmonics.

As neutral current, the zero sequence is used (3·I0).

Phase overcurrent.

The measure can only be phasor.

Neutral overcurrent.

It uses the zero sequence (3·I0). The measure can only be phasor.

If the polarization current is not available, the I polarization is not allowed.

Watt-metric and I*cos() / I*sin() directional always use 3·I0.

Grounding overcurrent.

It´s only available when analog input 7 is configured us polarization current.

Second and fifth harmonic block

It´s only available when analog input 7 is configured us polarization current; because it´s used to block Grounding overcurrent.

Thermal image.

It´s only available for phase.

The neutral unit is available when analog input 7 is configured us polarization current.

Stub bus differential.

It´s only available in 52 ½ models.

The operation is indicated by the "Stub bus" in chapter "Protection functions".

7.1.3 Breaker
The breaker status uses both breakers:

❑ To consider closed, simply one of the breaker is closed


❑ To consider open, both breakers must be open.
Breaker logic uses both breakers independently (see chapter "Breaker") with nodes:

❑ Breaker status. Nodes XCBR1 and XCBR2


❑ Inputs based breaker failure. Nodes RBFS1 and RBFS2.
❑ Pole discordance. Nodes RPLD1 and RPLD2.
❑ Breaker operation supervision. Nodes CBOU1 and CBOU2.

7.1.3.1 Breaker failure (50BF)


The operation is indicated by the "Breaker failure" in chapter "Protection functions".

The function is performed independently on each of the breakers.

Neutral 50BF is not available.

There are independent functions (settings, signals, commnads…) for every breaker. The nodes are:

❑ Node PROT/FRBRF1. The function uses the measures of the current transformers 1, 2 y 3 (Ia1, Ib1, Ic1).
❑ Node PROT/FRBRF2. The function uses the measures of the current transformers 4, 5 y 6 (Ia2, Ib2, Ic2).

Ingeteam Power Technology S.A.


User Manual 286
BREAKER AND A HALF CONFIGURATION 

7.1.3.2 Open pole detector


The operation is indicated by the "Open pole detector" in chapter "Breaker".

It uses the sum of the current phasor of each breaker.

To consider open, both breakers must be open.

The signals generated by this function are used in other protection functions:

❑ Distance mho and quadrilateral CharacteristicS


❑ 21 High Speed zone
❑ Phase selector
❑ Directional
❑ Mho and quadrilateral supervision
❑ Load encroachment
❑ Power swing

7.1.3.3 Dead or de-energized line


Dead line analysis is performed for each of the breaker 29. The settings are common for both breaker and are indicated in the
dead line function. Table 159 shows the available signals.

Table 159 Dead line signals per breaker

Signal Data Atributte


A1 open phase (I <) OpnPhs1 phsA
B1 open phase (I <) OpnPhs1 phsB
C1 open phase (I <) OpnPhs1 phsC
A2 open phase (I <) OpnPhs2 phsA
B2 open phase (I <) OpnPhs2 phsB
C2 open phase (I <) OpnPhs2 phsC

7.1.4 Breaker and a half supervision


It is used to avoid

It is used to avoid nuisance tripping on near faults but outside the area to be protected.

In external faults with large current flow, one of the current transformers can saturate without providing line current to the fault
and in this case:

❑ There is phase current with any direction (as measured current is spurious ) and voltage close to zero , which can generate
a trip of the distance unit
❑ If the fault is biphasic, homopolar current appears due to saturation and can act neutral directional units
An output signal is available.

❑ Node: PROT/BHPTRC1
❑ Output: Table 160 shows the signals of this function.
 Block by External Fault: It´s activated when an external fault to protect the area, which can cause false alarms is
detected.
Table 160 52 ½ supervision

Signal Data Atributte


Block by External Fault ExFIBI general

29
From firmware version 6.0.8.0 and ICD version 8.1.0.20

Ingeteam Power Technology S.A.


User Manual 287
BREAKER AND A HALF CONFIGURATION 

Phase currents of the two breakers are compared (IA1 and IA2, IB1 and IB2, IC1 and IC2).

An external fault is considered when, at least at some phase, the current of the two breakers exceed 3 times the rated current in
rms value.

If the currents are in phase, the fault is internal; while if the current are in opposite phase (continuous current) the fault is external.
There are several factors that make the currents are not exactly in phase in internal faults and not in opposite phase in external
faulat, the following angular criteria is applied:

Figura 184. Angular criteria for external faults

The signal "Block by External Fault" is activated when in some phase the following conditions are met:

❑ The current at the same phase of the two breakers exceeds 3 times the nominal current in rms value
❑ The angle difference between the same phase of the two breakers is between 110º and 250º.
In this situation the following units are blocked:

❑ Distance units, programmed as forward, which have involved the phase that indicates external fault. And for zone 1 all
units programmed as forward are blocked.
❑ Neutral directional programmed as forward is blocked

Ingeteam Power Technology S.A.


User Manual 288
FAULT LOCATOR 

8. FAULT LOCATOR
The fault locator for single and double lines processes the information collected in relation to each fault and calculates the estimated
distance to the point in which the fault has occurred, as well as the fault resistance.

The initial data necessary in order to arrive at the final calculation is:

❑ Sample by sample values of the voltage and current signals collected in the moment in which the fault is produced.
❑ The impedance parameters of the line in which the fault has occurred.
❑ Length of the line.
❑ The Voltage transformers and Current transformers transformation ratios of the bay that captured the fault.
The result is the distance to the fault in km or miles, together with the fault resistance and a locator exit code.

The node corresponding to the fault locator is PROT/RFLO.

All the settings are in primary values.

The settings necessary for the operation of the distance calculation algorithm are as follows (see Table 161):

❑ Enabled. Indicates whether the locator is enabled or not.


❑ Line length (Kms or miles). Indicates the length of the protected line.
❑ Z1 Imp. (Ohm p.u.length). The line’s positive sequence impedance module by unit length.
❑ Z1 angle (º). The line’s positive sequence impedance angle.
❑ Z0 Imp.(Ohm p.u.length). The line’s zero sequence impedance module per unit length.
❑ Z0 angle (º). The line’s zero sequence impedance angle.
❑ Y1(1/ohm p.u.length)*10e-9. Imaginary part of the line’s positive sequence admittance.
❑ Y0(1/ohm p.u.length)*10e-9. Imaginary part of the line’s zero sequence admittance.
❑ Z1 Local Source (Ohm). Local source positive sequence impedance module.
❑ Z1 Local Source angle (º). Local source positive sequence impedance angle.
❑ Z0 Local Source (Ohm). Local source zero impedance module. This setting only applies when the relay is set to receive phase to
phase voltages and the fault locator is enabled. The relay internally calculates the zero sequence voltage from the zero sequence
current (I0=IN/3) and the settled local source zero sequence impedance. With this value and with the phase to phase voltages is
able to calculate the single phase voltages and execute the calculation like the normal case.
❑ Z0 Local Source angle (º). Local source zero sequence impedance angle. This setting only applies when the relay is set to receive
phase to phase voltages.
❑ Z1 Remote Source (ohm). Remote source positive sequence impedance module.
❑ Z1 Remote Source angle (º). Remote source positive sequence impedance angle.
❑ Z1eq Parallel (Ohm). Positive sequence impedance module in parallel with the line.
❑ Z1eq Parallel Angle (º). Positive sequence impedance angle in parallel with the line.
❑ Phase current sens. (A). Minimum variation threshold in the phase current (in primary value) for the detection of the fault.
❑ Ground current sens. (A). Minimum variation threshold in the neutral current (in primary value) for the detection of the fault.
❑ Voltage sensitivity (V). Minimum variation threshold in the voltage (in primary value) for the detection of the fault.
❑ Locator output permanent. Indicates whether the distance measurement is maintained until the next fault (set to “YES”) or only the
seconds indicated in the “Locator output duration(s)” setting (set to “NO”).
❑ Locator output duration(s). Distance measurement maintenance time (s).
❑ Line type. Allows the user to select between single line or double line.
❑ Z0M Mutual(Ohm p.u.length). Mutual impedance module, by unit length. This setting only applies when the relay is set to double
lines.
❑ Z0M Mutual angle (º). Mutual impedance angle. This setting only applies when the relay is set to double lines.

Ingeteam Power Technology S.A.


User Manual 289
FAULT LOCATOR 

❑ Filter enabled. If set to “YES” and if the fault point is detected during the ten cycles following a breaker closure, the neutral current
is checked to see whether is exceeds the “I Minimum after close (A)” setting. If it is, inrush is considered to exist and prefault
current values equal to zero are employed in order to avoid the inrush distortion in these measurements. The neutral current is
also checked to see whether it exceeds the “Ground maximum current (A)” setting. If it is set to “NO”, neither the inrush nor the
neutral current are measured.
❑ I Minimum after close (A). Current threshold (in primary value) for the detection of inrush. Only used if the filter setting is enabled.
If a switch on to fault is detected (by the status of the breaker) during the first 10 cycles, single – phase ground faults that do not go
beyond the INmin threshold are blocked. If it is set to 4999A all the faults (single – phase and polyphase) are blocked. A possible
use is when there is a great distortion in the shape of a wave after a closing. For example, in the case of a distribution with a lot of
transformers hanging from the line, the breaker closing will cause a high inrush that can make the low current earth faults
calculation results distorted. With the I0min threshold the earth fault calculation is filtered, the I0of which must be lower than this
threshold.
❑ Ground maximum current (A). Threshold (in primary value) indicating the system’s maximum neutral current under normal
conditions. It is only used if the filter setting is enabled.

Ohm p.u indicates ohms per unit of length. For a line length of 100 km and a line impedance of 100 ohm, the setting in ohm p.u is
calculated as follows:

Ohm p.u = Line impedance / line length = 100 ohm /100km = 1 ohm p.u,

If the impedances are available in secondary values, these can be converted to primary values with the following formula:
𝑉_𝑇𝑟𝑎𝑛𝑠_𝑅𝑎𝑡𝑖𝑜
𝑍𝑃𝑟𝑖𝑚𝑎𝑟𝑦 = 𝑍𝑆𝑒𝑐𝑜𝑛𝑑𝑎𝑟𝑦
𝐼_𝑇𝑟𝑎𝑛𝑠_𝑅𝑎𝑡𝑖𝑜
There are independent settings:

❑ PROT/RFLO node:
❑ Settings: There are 6 settings tables. For details see Table 146.

Table 161 Locator settings

Data Setting Minimum Maximum Step Remarks Type


LocEna Enabled Boolean
LinLenKm (LinLenkm in Ed2) Line length (Kms or miles) 0.1 5000 0.1 float
Z1Mod Z1 Imp. (Ohm p.u.length) 0.001 300 0.001 float
Z1Ang Z1 angle (º) 15 90 0.1 float
Z0Mod Z0 Imp.(Ohm p.u.length) 0.001 300 0.001 float
Z0Ang Z0 angle (º) 15 90 0.1 float
Y1 Y1(1/ohm p.u.length)*10e-9 0 50000 0.1 float
Y0 Y0(1/Ohm p.u.length)*10e-9 0 50000 0.1 float
Z1LMod Z1 Local Source (Ohm) 0.001 20000 0.001 float
Z1LAng Z1 Local Source angle (º) 15 90 0.1 float
Z0LMod Z0 Local Source (Ohm) 0.001 300 0.001 float
Z0LAng Z0 Local Source angle (º) 15 90 0.1 float
Z1RMod Z1 Remote Source (Ohm) 0.001 20000 0.001 float
Z1RAng Z1 Remote Source angle(º) 15 90 0.1 float
Z1mMod Z1eq Parallel (Ohm) 0.001 20000 0.001 float
Z1mAng Z1eq Parallel angle (º) 15 90 0.1 float
PhsASens Phase current sens. (A) 10 100000 0.1 float
NeuSens Ground current sens. (A) 10 100000 0.1 float
PhsVSens Voltage sensitivity (V) 10 100000 0.1 float
PlsTms Locator output duration(s) 0 7200 1 Int32
PlsFEna Locator output permanent 0 1 1 Boolean
Linetype Line type 0 1 1 Single /Double enum
ZmMod Z0M Mutual(Ohm p.u.length) 0.0001 300 0.0001 float
ZmAng Z0M Mutual angle (º) 15 90 0.1 float
FilEna Filter enabled 0 1 1 Boolean
IminAfCl I Minimum after close (A) 0 5000 0.1 float
NMaxVal Ground maximum current (A) 0 5000 0.1 float
MaskEna Enable Events Record 0 1 1 Boolean

Ingeteam Power Technology S.A.


User Manual 290
FAULT LOCATOR 

From firmware version 5.20.15.8 and ICD version 6.3.0.0, the angle range is 15-90º. In previous versions it was 0-360º.

If any of the following parameters is unknown, the recommended values are:

Admittances (Y1,Y0): 0

Source impedance (Z1R, Z1S):

Module: 20000

Argument: 45º

Parallel impedance (Z1eq):

Module: 20000

Argument: 45º

Sensitivities:

I = 50% pick up 51 (A)

I0 = 50% pick up 51N (A)

V = 5% nominal voltage (V)

8.1 LOCATOR OPERATION

The process that follows the locator’s algorithm can be summarized in 4 steps, which are explained below:

❑ Fault instant detection


❑ Pre-fault and post-fault filtering
❑ Determination of the fault type
❑ Localization algorithm

8.1.1 Fault detection


Once the protection has picked up, the fault detection algorithm starts processing the analogue signals received in search of the
exact instant in which a fault has been produced. This search is made by comparing samples from consecutive cycles.

8.1.2 Pre-fault and post-fault filtering


The distance calculation algorithm uses the fundamental components of the voltage and current waves. The filtering extracts the
components from the signals stored at the pick up.

The collected signals are processed by a digital filter which provides the fundamental voltage and current components. A cosine
filter is used for this stage.

8.1.3 Determination of the fault type


Before launching the distance calculation algorithm in conjunction with the pre-fault and fault measurements calculated in the
previous step, the fault type must be defined.

The locator includes an algorithm that determines which phases have been affected by the fault. The algorithm is based on the
well-known Girgis method for distance relays. This procedure, which analyses the different magnitudes of change between the pre-
fault and post-fault situations in the current’s fundamental component, has demonstrated enviable precision in its results.

Ingeteam Power Technology S.A.


User Manual 291
FAULT LOCATOR 

8.1.4 Distance calculation


The distance calculation algorithm has been developed for single (see Figure 185) and double lines.

When a fault happens in a line corresponding to our relay, the information gathered by the locator, placed at one extreme of the
line, is reduced to the voltage and current values.

The data necessary to fully determine the system are obtained from the situation existing in the instant immediately preceding the
fault and in the situation of the fault itself.

8.1.4.1 Filtered by the maximum neutral current level (cross country faults)
In cross country faults (simultaneous faults in different lines or in the same line, e.g. AN in the protected line and BN in the
adjacent line), the zero sequence current level detected in the system is superior to the maximum zero sequence current level
for single phase faults.

In these situations, the protection locates the fault but indicates that the “Ground maximum current (A)” setting has been
exceeded, as in these situations the voltages are distorted by the lack of the adjacent line fault and can cause erroneous
calculations in the fault distance.

This mode is only operative if the “Filter enabled” setting is active. In this case, the result of the localization will be displayed in
the fault report, although in the control measurements it will be reported as invalid.

Figure 185 Line topology

8.2 PRESENTATION OF THE RESULTS

The presentation of the results is carried out in several ways:

❑ By display. In the “Fault reports” submenu.


❑ In the faults report.
❑ In a control measurement. It remains active during the programmed time or until another fault is produced.
In addition to the distance calculated, the fault resistance and the locator exit code are provided both in the display and in the fault
report. The locator exit codes are shown below:

❑ LOCATED: The fault has been located.


❑ LITTLE PREFAULT/ LITTLE PRE: There are few pre-fault cycles, pre-fault cycles <3 cycles.

Ingeteam Power Technology S.A.


User Manual 292
FAULT LOCATOR 

❑ LITTLE POSTFAULT/ LITTLE POST: There are few post-fault cycles.


❑ TRUNC: The fault has been processed but the localization algorithm has been truncated because the high number of
iterations.
❑ IN>I: The neutral current (IN) is greater than the set maximum neutral current.
❑ IN<I: The neutral current (IN) is lower than the set minimum neutral current following closure.
❑ NOT FAULT: The fault instant has not been detected.
❑ OUT OF LINE: The calculated distance is out of the set line length. If the calculated distance is greater than 150% of the
line length, the distance value is not shown.
❑ NOT ENABLED: The locator is not enabled.
❑ NEGATIVE DISTANCE: The distance calculated is negative. In this case, the distance value is not displayed.
❑ NOT LOCATED: The locator algorithm has not run.
For example, a locator result indicating the LITTLE PRE/IN>I/OUT OF LINE code should be interpreted as follows:

The location algorithm does not have sufficient pre-fault cycles and therefore considers that the fault sample is in the cycle in which the
digital pick up was produced. Furthermore, the neutral current in the system has exceeded the current value set in the “Ground
maximum current (A)” setting (this check is only carried out when the “Filter enabled” setting is set to “YES”). By exceeding this value,
the distance calculation may be erroneous. Therefore, although it is shown in the fault report it is marked as an invalid control
measure. Finally, the distance calculation has returned a value in excess of the value established in the “Line length” setting. If this
result is between 100% and 150% of the line length, it will be displayed. If it is greater, the distance will appear as NOT CALCULATED.

The distance is always calculated but it will not be sent to the dispatching centre (61850 nor Procome) if one of the blockings codes of
the locator is activated. In the fault report, the distance is always included with the locator exit code.

The locator blocking causes are:

❑ Not enough cycles (< 2.5 cycles). In this case, no calculation is done.
❑ Ineutral is below the setting “I Minimum after close (A)” (resistive or distant fault). In this case the calculation is done, but
it is not sent to the dispatching centre.
❑ Ineutral is above the setting “Ground maximum current (A)” (possible cross country fault). In this case the calculation is
done, but it is not sent to the dispatching centre.
❑ General block by switch onto fault. In this case the calculation is done, but it is not sent to the dispatching centre.

8.3 CONFIGURATION EXAMPLE

The model used in the example is a single distribution line.

The capacity values of the positive, negative and zero sequences are zero, so that these values do not affect the reach.

Line parameters, in primary values, are the following:

Current and voltage transformers:

Current transformation ratio (CT): 3000/1

Voltage transformation ratio (VT): 360000/100

Line parameters

Line length: 20km

Positive sequence resistance: 0.0315 Ω/km

Positive sequence inductance: 0.312 Ω/km

Zero sequence resistance: 0.269 Ω/km

Zero sequence inductance: 0.766 Ω/km

Ingeteam Power Technology S.A.


User Manual 293
FAULT LOCATOR 

Local Source parameters:

Impedance: 6Ω

Angle: 84.2º

FOR A LINE WITH THE FEATURES DESCRIBED ABOVE, FAULT LOCATOR COULD BE SET AS FOLLOWS:

Setting Value
Enabled YES
Line length 20
Z1 Imp. (ohm p.u. length) 0.314
Z1 angle (º) 84.2
Z0 Imp. (ohm p.u. length) 0.81
Z0 angle (º) 70.6
Y1 (1/ohm p.u. length)*10e-9 0
Y0 (1/ohm p.u. length)*10e-9 0
Z1 Local Source (ohm) 6
Z1 Local Source Angle.(º) 84.2
Z1 Remote Source (ohm) 20000
Z1 Remote Source Angle (º) 45
Z1eq Parallel (ohm) 20000
Z1eq Parallel Angle. (º) 45
Phase Current sensitivity (A) 40% PhaseOverCurr.Setting * CT
Ground Current sensitivity (A) 40% GroundOverCurr.Setting* GCT
Voltage sensitivity (V) 5% Vrated * VT
Locator output duration(s) 7200
Locator output permanent YES
Line type Simple
Filter enabled NO
Enable Events Record YES

WHERE:

PhaseOverCurr.Setting: Starting threshold of the phase overcurrent units.

GroundOverCurr.Setting: Starting threshold of the ground overcurrent units.

Vrated: Rated Voltage

CT: Phase current ratio.

GCT: Ground current ratio

VT: Phase voltage ratio.

Ingeteam Power Technology S.A.


User Manual 294
MONITORING 

9. MONITORING

9.1 EXTERNAL POWER SUPPLY MONITORING

This function checks if the external supply voltage is within the set range. It generates two signals:

❑ Auxiliary power supply greater than maximum threshold. If the supply voltage exceeds the set maximum threshold.
❑ Auxiliary power supply lower than minimum threshold. If the supply voltage is below the set minimum threshold.
The settings for configuring the external power supply monitoring (Table 162):

❑ Enabled: Enables the external power supply monitoring function.


❑ Minimum threshold. Indicates the minimum power supply voltage threshold, below which an alarm is issued.
❑ Maximum threshold. Indicates the maximum power supply voltage threshold, above which an alarm is issued.
❑ Enable Events record. Allows the generation of protection events associated to the function. If set to “NO”, the function’s
protection events are not generated. If set to “YES”, the function’s specific mask is contemplated.

Table 162 External power supply monitoring settings

Data Setting Minimum Maximum Step Remarks Type


SupSpvEna Enabled NO (0) / YES (1) enum
LoSuppV Minimum threshold 10 280 1 float
HiSuppV Maximum threshold 10 280 1 float
MaskEna Enable Events record NO (0) / YES (1) Boolean

There are two independent functions with settings, commands and outputs:

❑ Node:
 PROT/CESS1 for power supply 1
 PROT/CESS2 for power supply 2 (only in devices with redundant power supply)
❑ Settings. There are 6 settings tables. For details see Table 162.
❑ There are no logical inputs or commands
❑ Outputs: Table 163 shows the function’s output data.
 Vcc Supervision Status. It is active when enabled and not blocked.
 HH Infeed. Indicates that the power supply has exceeded the maximum threshold.
 LL Infeed. Indicates that the power supply is below the minimum threshold.
❑ Measurement. The external power supply values are available in the node GEN/LLN0 (see Table 164)

Table 163 Power supply monitoring outputs

Signal (CESS1) Signal (CESS2: redundant power supply) Data Attribute


Vcc Supervision Status Vcc 2 Supervision Status StEna stVal
HH Infeed HH Infeed 2 OverVcc general
LL Infeed LL Infeed 2 UnderVcc general

Ingeteam Power Technology S.A.


User Manual 295
MONITORING 

Table 164 Power supply measurement

Measurement Data Attribute


Power supply Psup net
Power supply2 Psup2 net

9.2 TEMPERATURE MONITORING

This function checks if the temperature is within the set range. It generates two signals:

❑ Temperature greater than maximum threshold. If the temperature exceeds the set maximum threshold.
❑ Temperature lower than minimum threshold. If the temperature is below the set minimum threshold.
The settings for configuring the external power supply monitoring (Table 162):

❑ Enabled: Enables the temperature monitoring function.


❑ Minimum temperature (ºC). Indicates the minimum temperature threshold, below which an alarm is issued.
❑ Maximum temperature (ºC). Indicates the maximum temperature threshold, above which an alarm is issued.
❑ Enable Events record. Allows the generation of protection events associated to the function. If set to “NO”, the function’s
protection events are not generated. If set to “YES”, the function’s specific mask is contemplated.
Table 165 Temperature monitoring settings

Data Setting Minimum Maximum Step Remarks Type


TmpSpvEna Enabled NO (0) / YES (1) enum
LoTmpVal Minimum temperature (ºC) -40 0 1 float
HiTmpVal Maximum temperature (ºC) 50 100 1 float
MaskEna Enable Events record NO (0) / YES (1) Boolean

It has independent settings, commands and outputs:

❑ PROT/CTSU1 node
❑ Settings. There are 6 settings tables. For details see Table 165.
❑ There are no logical inputs or commands
❑ Outputs: Measurement. The temperature value is available (see Table 167)
❑ Table 166 shows the function’s output data.
 Enabled. It is active when enabled and not blocked.
 Temperature greater than maximum threshold. Indicates that the temperature has exceeded the maximum threshold.
 Temperature lower than minimum threshold. Indicates that the temperature is below the minimum threshold.
❑ Measurement. The temperature value is available (see Table 167)
Table 166 Temperature monitoring outputs

Signal Data Attribute


Enabled StEna stVal
Power supply greater than maximum OverTemp general
Power supply lower than minimum UnderTemp general

Table 167 Temperature measurement

Measurement Data Attribute


Temperature Temp net

Ingeteam Power Technology S.A.


User Manual 296
MONITORING 

9.3 DIS BLOCKING BY LACK OF VAUX

If enabled, it checks that the external power supply exceeds the battery failure threshold, generating an alarm signal when it is below
the threshold.

In devices with redundant power supply, every power supply generates an independent DFFA signal. With the setting "Power Supply" a
general DFFA signal in generated.

The settings for configuring the battery failure monitoring (Table 168)

❑ Enabled: Enables the battery failure monitoring function.


❑ Power Supply: In devices with redundant power supply, selects which power supply generates the DFFA signal:
 PS1. Only Power supply 1 generates DFFA
 PS2. Only Power supply 2 generates DFFA
 PS1 or PS2. Weak Infeed DFFA1 or DFF2 indicates DFFA
 PS1 and PS2. Both power supplies must indicate DFFA.
❑ Enable Events record. Allows the generation of protection events associated to the function. If set to “NO”, the function’s
protection events are not generated. If set to “YES”, the function’s specific mask is contemplated.
Table 168 Battery failure monitoring settings

Data Setting Minimum Maximum Step Remarks Type


SupSpvEna Enabled NO (0) / YES (1) enum
PS1
PS2
SrcSpv Power Supply enum
PS1 or PS2
PS1 and PS2
MaskEna Enable Events record NO (0) / YES (1) Boolean

There are independent settings and outputs:

❑ PROT/CSUS1 node
❑ Settings. There are 6 settings tables. See Table 168.
❑ There are no logical inputs or commands
❑ Outputs: Table 169 shows the function’s output data.
 Enabled. It is active when enabled and not blocked.
 Weak Infeed DFFA. Indicates that the external power supply is below the minimum threshold as indicated in the
setting "Power supply".
 Weak Infeed DFFA1. Indicates that the external power supply 1 is below the minimum threshold.
 Weak Infeed DFFA2. Indicates that the external power supply 2 is below the minimum threshold.
Table 169 Battery failure monitoring outputs

Signal Data Attribute


Enabled StEna stVal
Weak Infeed DFFA DFFA general
Weak Infeed DFFA1 DFFA1 general
Weak Infeed DFFA2 DFFA2 general

9.4 INTERNAL BATTERY FAILURE MONITORING

The internal battery used for data maintenance is checked to ensure that it does not fall below a security level.

There are independent outputs:

Ingeteam Power Technology S.A.


User Manual 297
MONITORING 

❑ GEN/LPHD1 node
❑ It does not use settings.
❑ There are no logical inputs or commands.
❑ Outputs: Table 170 shows the function’s output data.
 Internal battery failure. Indicates that the internal battery level is below the minimum threshold.
❑ Measurement. The battery value is available (see Table 171)

Table 170 Internal battery failure outputs

Signal Data Attribute


Battery failure BatAlm general

Table 171 Internal battery measurement

Measurement Data Attribute


internal battery IntBat net

9.5 UNIT CHECKS

The unit continually checks the various incorporated elements and cards. If an error is detected in any of the elements or cards, an
alarm is generated. If the error affects the unit’s operation, a critical error is generated, which in addition to the signal acts on :

❑ Colour front LED. Non-configurable status LED, which indicates the unit’s general status. If the LED is green, it indicates
that everything is correct, while if it is red it indicates a critical error in the unit.
❑ CPU Relay. Non-configurable 3-contact relay, which indicates the unit’s general status. If the LED is active (common
terminal – NO), it indicates that everything is correct, while if it is deactivated (common terminal– NC) it indicates a critical
error in the unit. If the unit is switched off, the relay is deactivated.
❑ The unit's alarm signals are to be found in the LPHD node. The available signals indicate faults in the card check, in the
communications between the cards, in the unit’s configuration, etc.:
❑ Critical hardware error. Indicates that a critical error has been produced. In addition to this signal, the cause that produced
the signal will be indicated.
❑ CPU error. Indicates that the check has detected an error in the CPU. It generates critical error signal.
❑ Analogue error. Indicates an error in transformers card. It generates critical error signal.
❑ I/O micro error. Indicates an error in the I/O cards’ micro.
❑ Analogue connection error. Indicates that a fault has been produced in the communications between the CPU and the
transformers card. It generates critical error signal.
❑ I/O connection error. Indicates that a fault has been produced in the communication between the CPU and an I/O card. It
generates critical error signal. Additionally, it will indicate the card which has suffered the failure:
 Error card address x. Indicates that there is a communication error with the card with the address x.
❑ Front connection error. Indicates that a fault has been produced in the communications between the CPU and the unit’s
front card. It generates critical error signal.
❑ Shared analogue memory error. Indicates that a fault has been produced in the Data exchange memory between the CPU
and the transformers card. It generates critical error signal.
❑ Error shared I/O memory. Indicates that a fault has been produced in the Data exchange memory between the CPU and
the I/O cards. It generates critical error signal.
❑ RTC clock error. Indicates that the check has detected an error in the real time clock.
❑ Continuous component monitoring alarm. Indicates that an error in the continuous measurement monitoring has been
detected in the transformers card.

Ingeteam Power Technology S.A.


User Manual 298
MONITORING 

❑ Alarm settings. Indicates that errors have been detected in the storage of the unit’s settings. It generates critical error
signal.
❑ FW Alarm. Indicates that the relay firmware versions are incompatible.
❑ Memory check alarm. Indicates that errors have been detected in the checking of the unit’s memory. It generates critical
error signal.
❑ Converter check alarm. Indicates that errors have been detected in the transformers card AD converter. It generates
critical error signal.
❑ Converter voltage level alarm. Indicates that errors have been detected in the transformers card reference voltages. It
generates critical error signal.
❑ Relay activation alarm. Indicates that an error has been detected in the activation of at least one of the I/O cards’ relays. It
generates critical error signal.
❑ I/O configuration error. Indicates that the configuration of the I/O cards does not coincide with the unit’s correct
configuration. It generates critical error signal.
❑ General Vdc error. Indicates a failure in the internal power supply levels. It generates critical error signal.
❑ Frequency configuration error. This is not a unit failure, but rather a configuration failure. Indicates that the frequency
measurement of the signals being injected into the unit do not match the set measurement, that is, the unit is configured
as 50Hz and the signals which are being injected are greater than 55Hz; or that the unit is configured as 60 Hz and the
signals being injected are less than 55 Hz.
❑ Internal battery failure. Indicates that the data storage battery is below the security levels and that the data may be lost at
shutdown.
❑ Version compatibility error. Indicates that the versions of the unit's firmware are not correct.
❑ Time setting configuration alarm. Indicates that there is an error in the configuration of the unit’s time setting.
❑ For each I/O card there is are 5 signals, indicating:
 Status OK. Indicates that the card is configured correctly and without errors.
 Configured & No_detected. Indicates that the card is configured by the user, but not detected in the unit. This may be
because it is not assembled or because it has an error. Equivalent to the current communication error.
 Different configuration. The type indicated by the user and the type detected by the unit do not coincide.
 No_configured & detected. Indicates that card that has not been configured by the user has been detected in an
address.
 Internal card error. A card check error has been received (includes relay check).
❑ ICD error. Indicates the last ICD received by the device was wrong and it was refused by the device. Once activated, this
signal is deactivated when a correct ICD is received.
❑ Power supply 1 OFF. Indicates that the power supply 1 is turned off. It is only available in devices with redundant power
supply.
❑ Power supply 2 OFF. Indicates that the power supply 2 is turned off. It is only available in devices with redundant power
supply.
❑ SV Board Error. Indicates that there is an error in the sampled values board.

Ingeteam Power Technology S.A.


User Manual 299
MONITORING 

Table 172 Checking signals

Signal Data Attribute


Critical hardware error HwCrAlm stVal
CPU error CPUAlm stVal
Analogue error AnaAlm stVal
I/O micro error ESAlm stVal
Analogue connection error AnaComAlm stVal
I/O connection error ESComAlm stVal
Front connection error MMIComAlm stVal
Shared analogue memory error AnDPMAlm stVal
Shared I/O memory error ESDPMAlm stVal
RTC clock error RTCAlm stVal
Continuous component monitoring alarm Harm0Alm stVal
Alarm settings SettingAlm stVal
Firmware alarm FwAlm stVal
Memory check alarm MemAlm stVal
Converter check alarm ADCAlm stVal
Converter voltage level alarm VRefAlm stVal
Relay activation alarm DOAlm stVal
I/O configuration error IOCnfError stVal
Card address error 1 GGIO1Alm stVal
Same as rest of I/O up to 8
Card address error x (x from 2 to 8) GGIOxAlm stVal
General Vdc error VccError stVal
Frequency configuration error FrConfAl stVal
Internal battery failure BatAlm stVal
Version compatibility error VerAlm stVal
Time setting configuration alarm HSetAlm stVal
ICD error FailICD stVal
Card 1 ok GGIO1Ok stVal
Card 1 ConfiguredYNo_detected GGIO1Nodet stVal
Card 1 Different configuration GGIO1Dif stVal
Card 1 No_configured Y Detected GGIO1NConf stVal
Card 1 Internal card error GGIO1HwErr stVal
Same as rest of I/O up to 8
Front ok FRONTOk stVal
Front Configured Y No_detected FRONTNodet stVal
Different front configuration FRONTDif stVal
Front No_configured Y Detected FRONTNConf stVal
Front Internal card error FRONTHwErr stVal
Power supply 1 OFF FailSup1 stVal
Power supply 2 OFF FailSup2 stVal
SV Board Error SVError stVal

Ingeteam Power Technology S.A.


User Manual 300
CONFIGURATION 

10. CONFIGURATION

10.1 CID

10.1.1 Data Storage


The unit has a CID file that follows the format defined in section 6 of the IEC 61850 standard. It is available via the following path by
FTP “SCL/validated”, in which all the unit’s configuration information is saved, either structured in nodes that follow the IEC 61850
format or in private parts.

10.1.2 Updating CID


There are different ways to change the settings. They are listed below:

❑ Using MMS in IEC 61850


❑ Using local display
❑ Using the pacFactory (PC tool)
❑ By sending the CID by FTP to the “SCL/notvalidated” directory

Independently of the form used from among those listed above, the changes to the affected setting are stored in the unit’s CID file.

CONFIGURATIONS USING ED1:


On devices with IEC61850 Edition 1 configurations, when any setting is changed, the paramRev field in the node in which the
new setting has been written, as well as the LLN0 node of the Logical Device to which the node belongs, are updated in the CID
file.

The format of the paramRev data is as follows:

XXX year.month.day.time.minute.second [paramRev origin text]

❑ Where “XXX” is an integer counter that is incremented each time paramRev is updated by a setting change.
❑ "paramRev origin text“depends on the origin of the setting change:

Origin of settings change paramRev text origin


MMS IEC 61850 client BROWSER IP
Local display USER DISPLAY
pacFactory USER TOOL
New CID CID UPDATE

In the case of “New CID”, only those settings in the CID sent to the unit and which are out of range will be updated in
paramRev.

10.2 GENERAL

Two nodes are used for the general configuration of the unit

❑ GEN/LLN0. Includes the unit’s generic configuration settings


❑ PROT/LLN0. Includes the protection units’ generic configuration settings

Ingeteam Power Technology S.A.


User Manual 301
CONFIGURATION 

The settings available in the GEN/LLN0 node are shown in protection events mask enablind. Allows the generation of protection events
associated to the function. If set to "NO", the function's protection events are not generated. If set to "YES", the function's specific
mask is contemplated:

❑ Language. Indicates the unit’s language. Affects the display, reports, etc.
❑ Functional key block. It allows the functional key to be blocked. When blocked commands with functional key are not
allowed.
❑ Functional keys (remote). It allows key commands with the device in remote mode.
❑ Leds Blocking. Allows the activation of the LEDs to be blocked.
❑ Blocking allowed by command. It allows blocking the reception of block/unblock protection commands.
❑ Reset Digital Output. Indicates the logic input that, when activated, reset all the digital outputs.
❑ The supported IRIG-B formats are B002, B003, B006, B007 and IEEE1344. It select whether the year is taken into account in
the synchronization by IRIG. The options are:
 “UTC without year”. The year is not taken into account and all the formats are admitted.
 “UTC with year”. With formats B006, B007 and IEE1344 the year is not taken into account. It cannot be used with
formats B002 and B003 because they set the year to zero value.
 “Local without year”. The year is not taken into account. All the formats are admitted.
 “Local with year”. With formats B006, B007 and IEE1344 the year is not taken into account. It cannot be used with
formats B002 and B003 because they set the year to zero value.
❑ Local/remote selection. Indicates the logic input that, when activated,changes the device between local/remote.
❑ Erase records. Indicates the logic input that, when activated, deletes the unit’s report queues. Affects protection events,
faults, disturbance reports, historical measurement reports, etc.
❑ Remote/ Local type. It indicates how the unit will behave when it has to block the commands it is sent. See 17.2.1
❑ Flicker Enable. Enables the digital inputs’ swing supervising function.See 10.4.3
❑ Enable Events record. Allows the generation of protection events associated to the function. If set to “NO”, the function’s
protection events are not generated. If set to “YES”, the function’s specific mask is contemplated.
❑ Block full records. When set to "NO", queues are circular, when the maximun number of registers is fullfiled, the oldest
one is erased. If sets to "YES", when the maximun number of registers is fullfiled, the queue is blocked and no more
registers are stored. It affects protection events, faults, disturbance reports, historical measurement reports.

Table 173 General settings

Data Setting Minimum Maximum Step Remarks Type


Lang Language Spanish (0) / English (1) Boolean
BlkFKeys Functional keys blocking NO (0) / YES (1) Boolean
FKeysRem Functional keys (remote) Boolean
BlkFrCom Leds Blocking NO (0) / YES (1) Boolean
LogInReDO Blocking allowed by command Int32
BlkComm Reset Digital Outputs Boolean
UTC without year /
UTC with year /
IrgType IRIG-B002 format enum
Local without year /
Local with year
LogInLR Local/remote selection Int32
LogInDelRe Erase records Int32
Not treated (0)
Iberdrola (1)
LRmode Remote/Local Type 0 3 1 enum
Exclusive (2)
No HMI (3)
FlickerEna Flicker Enabled 0 1 1 NO (0) / YES (1) enum
MaskEna Enable Events Record NO (0) / YES (1) Boolean
BlkFRec Block full records NO (0) / SI (1) Boolean

Ingeteam Power Technology S.A.


User Manual 302
CONFIGURATION 

The settings available in the PROT/LLN0 node are shown in protection events mask enabling. Allows the generation of protection
events associated to the function. If set to "NO", the function's protection events are not generated. If set to "YES", the function's
specific mask is contemplated:

❑ Relay ON. Indicates whether the relay in service or not. If it is out of service, the protection functions do not act.
❑ Phase order. Selects the phase sequence ABC/CBA. Affects the direct and inverse sequences and, therefore, the functions
that use them. To check whether the order corresponds to wiring, check that the values expected for the indicated
configuration are obtained in the sequence measurements and that the phase current arguments (as seen in the status
screen) match selected sequence.
❑ Select Setting group 1. Indicates the logic input which, when activated, selects the settings table 1 as active.
❑ Select Setting group 2. Indicates the logic input which, when activated, selects the settings table 2 as active.
❑ Select Setting group 3. Indicates the logic input which, when activated, selects the settings table 3 as active.
❑ Select Setting group 4. Indicates the logic input which, when activated, selects the settings table 4 as active.
❑ Select Setting group 5. Indicates the logic input which, when activated, selects the settings table 5 as active.
❑ Select Setting group 6. Indicates the logic input which, when activated, selects the settings table 6 as active.
❑ Fault reports (Prim./sec.). Select the measurements of the display fault reports between primary and secondary.
❑ Enable Events record. Allows the generation of protection events associated to the function. If set to “NO”, the function’s
protection events are not generated. If set to “YES”, the function’s specific mask is contemplated.

Table 174 General protection settings

Data Setting Minimum Maximum Step Remarks Type


OnLine Relay ON NO (0) / YES (1) Boolean
PhsOrd Phase order ABC (0) /CBA (1) enum
LogInSet1 Select Setting group 1 Int32
LogInSet2 Select Setting group 2 Int32
LogInSet3 Select Setting group 3 Int32
LogInSet4 Select Setting group 4 Int32
LogInSet5 Select Setting group 5 Int32
LogInSet6 Setting change table 6 Int32
FaRepTy Fault reports (Prim./sec.) Secondary (0) / Primary (1) enum
MaskEna Enable Events record NO (0) / YES (1) Boolean

10.3 FRECUENCY, MEASUREMENT AND TRANSFORMERS

The current and voltage transformers are configured in independent nodes, in which the units’ rated values, transformation ratios and
frequencies are indicated.

10.3.1 Current
Two PROT/TCTR nodes are used for the transformation ratios and PROT/TCIN for rated currents.

The settings used for the configuration of the current transformers ratios, which are used to provide primary measurements, are
(see Table 175):

❑ Phase current ratio. Indicates the phase current transformation ratio.


❑ Neutral current ratio. Indicates the neutral current transformation ratio.
❑ Polarization current. Indicates the polarization current transformation ratio.
The settings used for configuring the rated currents are (see Table 176):

❑ I rated phases. Selects the value of the rated phase current.


❑ I rated neutral. Selects the value of the rated neutral current.

Ingeteam Power Technology S.A.


User Manual 303
CONFIGURATION 

❑ 3I0-IN measurement type. Selects the neutral measurement from between the measurement calculated for the
phase currents and the transformer measurement.

Table 175 Current transformation ratios

Data Setting Minimum Maximum Step Remarks Type


PhsRat Phase current ratio 1 10000 0.1 float
GndRat Neutral current ratio 1 10000 0.1 float
PolARat Polarization current 1 10000 0.1 float

Table 176 Rated currents

Data Setting Minimum Maximum Step Remarks Type


PhsInom I rated phases 1A (1)/ 5A (2) enum
GndInom I rated neutral 1A (1)/ 5A (2) enum
SelI0 3I0-IN measurement type Calculated (0)/Trafo (1) enum

10.3.2 Frequency and voltage


The PROT/TVTR node is used for the voltage and rated voltage transformation ratios (see Table 177).

❑ Phase transformation ratio. Indicates the phase voltage transformation ratio.


❑ Rated phase-earth V (V sec). Selects the rated voltage.
❑ Voltage phases used. Selects the voltage phases used in the protection functions. Different phase combinations
(both earth to phase and phase to phase) can be selected:
 None. No voltage is enabled
 A. Earth-phase voltage only operates in phase A
 B. Earth-phase voltage only operates in phase B
 A-B. Earth-phase voltages operate in phases A and B
 C. Earth-phase voltage only operates in phase C
 A-C. Earth-phase voltages operate in phases A and C
 B-C. Earth-phase voltages operate in phases B and C
 A-B-C. The three earth-phase voltage operate
❑ Frequency. Selects the unit’s rated operating frequency 50Hz or 60Hz
❑ VN transformation ratio. Indicates the neutral voltage transformer ratio.
❑ Synchro I voltage ratio. Indicates synchronism 1 voltage transformer ratio.
❑ Synchro II voltage ratio. Indicates synchronism 2 voltage transformer ratio. Only in devices with two synchronism
voltages.

Table 177 Voltage characteristics

Data Setting Minimum Maximum Step Remarks Type


VRat Phase transformation ratio 1 10000 0.1 float
VRtg Rated phase-earth V (V sec) 40 200 0.1 float
VSel Voltage phases used 0 8 1 enum
HzRtg (HzVal in Ed2) Frequency 50Hz (0) /60Hz (1) enum
VNRat VN transformation ratio 1 10000 0.1 float
VsRat1 Synchro I voltage ratio 1 10000 0.1 float
VsRat2 Synchro II voltage ratio 1 10000 0.1 float

10.3.3 Power and energy


The PROT/MPWE node, which indicates the conditions for the power calculation, is used (see Table 178):

❑ Change sign P. Indicates if the sign change in the real power calculation is enabled.

Ingeteam Power Technology S.A.


User Manual 304
CONFIGURATION 

❑ Change sign Q. Indicates if the sign change in the reactive calculation is enabled.
❑ Real energy constant. Indicates the real energy impulse factor, i.e., the number of kWh by virtue of which the
counter is incremented by one unit.
❑ Reactive energy constant. Indicates the reactive energy impulse factor, i.e., the number of kWh by virtue of which
the counter is incremented by one unit.
The energy counters value is available in the PROT/MMTR node, with the data:

❑ Positive real energy counter: SupWh.


❑ Negative real energy counter: DmdWh.
❑ Positive reactive energy counter: SupVArh.
❑ Negative reactive energy counter: DmdVArh.

Table 178 Power characteristics

Data Setting Minimum Maximum Step Remarks Type


PSiCh Sign change P NO (0) / YES (1) float
QSiCh Sign change Q NO (0) / YES (1) float
CorWh Constant real power (kWh) 1 1000 1 enum
CorVArh Constant reactive power 1 1000 1 enum

10.4 INPUTS/OUTPUTS

The unit can host a variable number of input-output cards variable (from 1 to 7). Each card is configured with an internal address from
2 to 7. The power supply is assigned address 1, which is not configurable.

Each card is represented in the IEC 61850 data model as an instance of the GGIO node in the Logical Device called “GEN”. Each GGIO
has the internal address of the physical card as an instance. Thus, for example, if a unit has two input-output cards with internal
addresses 1 and 4, the GEN/GGIO1 and GEN/GGIO4 nodes will exist in the data model.

The number of digital input settings and signals present in each GGIO depends on the type of card used. Continuing the example, if the
card with the internal address 1 has 6 digital inputs and 4 digital outputs, the GGIO1 node will have 6 digital input signals and 4 digital
output signals, as well as the settings corresponding to each digital input and output available.

The data model associated to the GGIOs is common to all and has 32 digital inputs and 16 digital outputs. Nevertheless, in each card
only the data associated with its own inputs and outputs are updated.

For each GGIO there is a boolean setting called MaskEna (event record enabled). If set to “YES”, the activation/deactivation of the
digital inputs and outputs will generate protection events. To the contrary, they will not be stored as event records.

10.4.1 Inputs
There are 2 settings available for each digital input:

❑ DIxTmms: Digital input time x (ms). This is a software filter for the activation/deactivation of digital inputs. It
indicates the milliseconds (range 0 to 100 ms30) which a digital input must be seen to be active in order to be
considered active. In order to calculate an input's total activation time, the input’s hardware filter delay – which is
approximately 1ms – must be added to this time.
❑ DIxType: Digital input type x. Defines whether the input is to be interpreted as active when it is seen as closed (NO)
or when it is seen as open (NC)
Each digital input has an associated digital signal indicating its status (see Table 179). Each GGIO indicates the status of all its digital
inputs (up to 32).

30
From firmware version 5.20.15.8 and ICD version 6.3.0.0. In previous versions the maximun was 20ms

Ingeteam Power Technology S.A.


User Manual 305
CONFIGURATION 

Table 179 Digital input signals

Signal Data Attribute


Digital input 1 Ind1 stVal
Digital input 2 Ind2 stVal
Remaining inputs
Digital input 32 Ind32 stVal

10.4.2 Outputs
There are 3 settings available for each digital output:

❑ DOxSig: Assignment digital output x. Assigns the activation of the digital output. There are several assignment
possibilities:
 Signals: They can be signals generated by the unit (trips, logics, hw check, digital inputs and outputs)
 Commands: All of the commands available in the unit can be directly programmed to a physical output
❑ DOxTmms: Digital output time x (ms). The output activation time defines the minimum operational time of each
physical output following activation (in milliseconds). The range is 0.05 to 5000 ms. The output remains active in
accordance with this time setting or the duration of the associated signal, whichever is greater.
❑ DOxTyp: Digital output type. Each output’s type is defined from among the options:
 “Not”. The output follows the assigned signal, i.e., the output is activate when the signal is active. When the
signal is deactivated, the output will deactivate if the digital output time has elapsed. To the contrary, the
output will remain active until this time elapses.
 “Stored”. Once activated, the output remains active until the relay deactivation command is issued, with the
signal assigned to the output deactivated. The command can be issued by the action of a digital input
programmed as “Local reset”, a command or by keyboard/display.
 “Trip”. Once activated, the output remains active until the following conditions are met: the signal assigned to
the output is deactivated and the breaker is open.
 “Close”. Once activated, the output remains active until the following conditions are met: the signal assigned
to the output is deactivated and the breaker is closed.
Each digital input has an associated digital signal indicating its status (see Table 181). Each GGIO indicates the status of all its digital
outputs (up to 16).

Table 180 Input/output settings

Data Setting Min Max Step Remarks Type


MaskEna Enable Events record NO (0) / YES (1) Boolean
OscTms Input oscillation time (s) 1 60 1 Int32
Nchanges Number of changes 0 255 1 Int32
DI1Tmms Digital Input Time 1 (ms) 0 100 1 Int32
DI1Type Digital Input Type 1 NO (0) / NC (1) enum
DI2Tmms Digital Input Time 2 (ms) 0 100 1 Int32
DI2Type Digital Input Type 2 NO (0) / NC (1) enum
Remaining inputs DI3x, DI4x..
DO1Sig Digital Output Assignment 1 Int32
DO1Tmms Minimum Output Time 1 (ms) 0 5000 1 Int32
DO1Ty Digital Output Type 1 enum
DO2Sig Digital Output Assignment 2 enum
DO2Tmms Minimum Output Time 2 (ms) 0 5000 1 enum
DO2Ty Digital Output Type 2 Int32
Remaining inputs DI3x, DI4x..

Ingeteam Power Technology S.A.


User Manual 306
CONFIGURATION 

Table 181 Digital output signals

Signal Data Attribute


Digital output 1 SPCSO1 stVal
Digital output 2 SPCSO2 stVal
Remaining outputs
Digital output 16 SPCSO16 stVal

10.4.3 Treatment of digital input flicker


Flicker consists of a fast and continuous change of a digital input, usually associated with a failure in the input’s contact. The
function allows a control to be performed to disable the flickering digital inputs or signals in order to prevent them from interfering
with the control system, as a disabled digital does not generate status changes.

The supervising of the swing in the digital inputs or the supervising of the flicker is conducted in accordance with certain user-
configurable settings.

On the one hand, there is a general setting that allows this function to be enabled or disabled. If this setting is disabled, not flicker
treatment is performed.

General setting for the configuration of the flicker treatment (Table 182):

❑ FlickerEna: Enables the digital inputs’ swing supervising function.

Table 182 General flicker treatment setting

Data Setting Minimum Maximum Step Remarks Type


FlickerEna Flicker enabled 0 1 1 NO (0) / YES (1) enum

❑ GEN/LLN0 node
Once the general flicker setting has been enabled (Table 182), there are two more setting per card for treating the swing.
They are “OscTms” and “Nchanges” which can be seen in Table 180:

❑ OscTms: The time between changes in the same direction in order for a signal to be deemed to be swinging. When a signal
is swinging a swinging signal is produced. The unit is seconds.
❑ Nchanges: The number of changes that must be produced in a swinging signal in order for the signal to become invalid and
cease from sending changes. If this setting is set to zero, it disables the swing treatment for this card, i.e., the flicker
treatment is not performed for this card.
❑ GEN/GGIOx node, in which x depends on the card’s internal address (see section 10.4)
Once a signal has been detected as swinging, it becomes questionable and oscillatory.

If this situation continues and the number of set changes (“Nchanges” setting) is exceed, the signal becomes invalid and oscillatory.
It ceases to send the changes and sends the signal's last known valid status.

When the time difference between two changes is greater than the inputs’ swing time (“OscTms” setting), the signal changes to
valid.

10.5 LEDS

10.5.1 Via GEN/IHMI node


The LEDs are programmed within the IHMI node located in the “GEN” Logical Device. There are 2 settings available for each LED:

❑ LexSig: Assignment led x. Assigns the activation of LED x using any of the signals generated by the unit

Ingeteam Power Technology S.A.


User Manual 307
CONFIGURATION 

❑ LExTyp: LED type x. It can be programmed as “not” and “stored”. In the first case, the activation of the LED follows the
activation of the signal programmed in the setting described above. If it is programmed as “stored”, the LED’s activation
will remain even if the signal that provoked its activation drops out, until the signal programmed in the LogInReLed setting
available in the IHMI node is activated.
There is a general setting for all the LEDs that indicates the logic signal used to switch of the LEDs:

❑ LED reset. Selects the signal which, when active, switches off the LEDs.
The LEDs are updated every 200ms. Thus, for the correct activation of the LEDs, the assigned signal must remain active for at least
150 ms. To the contrary, the LED cannot be activated.

Table 183 LED settings

Data Setting Minimum Maximum Step Remarks Type


LogInReLed LED reset Int32
Le1Sig Led 1 assignment 0 20 1 Int32
Le1Ty Led 1 type Not (0) /Stored (1) enum
Le2Sig Led 2 assignment 0 20 1 Int32
Le2Ty Led 2 type Not (0) /Stored (1) enum
Remaining LEDs up to 19

10.5.2 Via CTRL/IHMI node


If the unit, in addition to the “GEN” Logical Device’s IHMI node defined in the previous section, has an IHMI node located in “CTRL”
Logical Device, the unit’s treatment in relation to the configuration of the LEDs differs as follows:

❑ The parameterization of the assignment of LEDs is carried out by the settings present in the CTRL/IHMI node.
❑ The parameterization of the LEDs type is carried out by the settings present in the CTRL/IHMI node.
The settings present in this node are detailed below

Data Setting Minimum Maximum Step Remarks Type


InRef1 Led 1 assignment - - - InRef
LEDSe1 Led 1 type Not (0) /Stored (1) enum
InRef2 Led 2 assignment - - - InRef
LEDSe2 Led 2 type Not (0) /Stored (1) enum
Remaining LEDs up to 19
There are 2 settings available for each LED:

❑ InRefx: Assignment led x. Assings the activation of LED x using any of the signals generated by the unit. The
assignment is carried out by means of a character string (see next section “Configuration with InRef”)
❑ LEDSex: LED type x. It can be programmed as “not” and “stored”. In the first case, the activation of the LED follows
the activation of the signal programmed in the setting described above. If it is programmed as “stored”, the LED’s
activation will remain even if the signal that provoked its activation drops out, until the signal programmed in the
LogInReLed setting available in the GEN/IHMI node (defined in the previous section) is activated.

10.6 CONFIGURATION WITH INREF

The InRef type settings are programmed by a string of characters in which the reference of the IEC 61850 object containing the value to
be employed as an input is indicated. The following format, as defined in the part 7.2 of the IEC 61850 standard, is employed:

LDName/LNName.DataObjectName[.SubDataObjectName[. ...]].DataAttributeName

For example,

❑ In order to program InRef1 with the GGIO1 input signal 1, the reference to be written in the InRef is:
GEN/GGIO1.Ind1.stVal
❑ In order to program the PTOC 1 phase A trip, the reference is:
PROT/PTOC1.Op.phsA

Ingeteam Power Technology S.A.


User Manual 308
CONFIGURATION 

10.7 GENERIC COMMAND

Generic commands are available within the Logical Device "GEN" on the ordGGIO1 node, which will be active for 100msg.

The commnad are the following:

❑ SPCS01, Generic command 1


❑ SPCS02, Generic command 2
❑ ………..
❑ SPCS016, Generic command 16

Are available signals associated with these generic commands, which will be available in logic, output, etc.

Signal Data Attribute


Generic command 1 activation Ind1 stVal
Generic command 2 activation Ind2 stVal
--------- stVal
Generic command 16 activation Ind16 stVal
Generic command 1 desactivation Ind17 stVal
Generic command 2 desactivation Ind18 stVal
--------- stVal
Generic command 16 desactivation Ind32 stVal

10.8 NAMES

The PROT/LPHD node is used for the general configuration of the units’ names and the installation.

Short names are used for the generation of the disturbance recorder and fault file names.

The settings for this node are shown in Table 184:

❑ Installation name: Full name of the installation.


❑ Short name of the installation. Short name of the installation. Limited to 10 characters, this is used in the generation of
disturbance recorder and fault files. Neither spaces nor commas are permitted in the name.
❑ Relay name. Full name of the relay.
❑ Short relay name. Short name of the installation. Limited to 10 characters, this is used in the generation of disturbance
recorder and fault files. Neither spaces nor commas are permitted in the name.
❑ Name of breaker 1. Full name of breaker 1.
❑ Name of breaker 2. Full name of breaker 1.
Table 184 Name settings

Data Setting Minimum Maximum Step Remarks Type


InstNam Installation name String
InstShNam Short name of the installation 10 characters String
RelNam Relay name. String
RelShNam Short relay name 10 characters String
BkrNam1 Name of breaker 1 String
BkrNam2 Name of breaker 2 String

Ingeteam Power Technology S.A.


User Manual 309
CONFIGURATION 

10.9 IPRV NODES CONFIGURATION

10.9.1 General IPRV settings


The device has several settings (included in the GEN/genIPRV logical node) to set certain operating modes.

These settings are considered special and they are configurable via an IEC 61850 connection or sending the CID file after editing the
values from pacFactory tool (menu Settings -> IPRV). They do not appear in the display or section pacFactory protection settings.

The settings included in this logical node are:

❑ LocalTim: Allows to force sending local time in IEC 61850 timestamps. It is important to know that this is not normative
because IEC 61850 standard defines that the timestamps must be sent in UTC format. However, with this option the device
is adapted to systems that only use local time. The default value is 0, which indicates the use of UTC. The value 1 indicates
the use of local time.
❑ MaxConn: Sets the maximum number of IEC 61850 connections that are accepted. Limited to a maximum value of 16.
❑ AplicTms: Defines the disconnection timeout at the application level. After this time (in seconds) without receiving any IEC
61850 messages the server automatically closes the connection.
❑ TipoServ: Defines some operation modes of the device.
 Value 0: Default operation mode.
 Value 1: Special operation mode that includes:
 Enable IP checking to validate a new ICD/CID file. If the IP address indicated in the communications section of
the ICD/CID file does not match the address of the device the file is not validated. If the IP address of the
device is changed once the file has been validated, the IEC 61850 server is disabled and waits for the change of
the IP address of the device with the one in the file or to receive a new CID file with the correct IP.
 When a command is received, the value that the device saves in "orIdent" attribute is the IP address from
which the command was sent, regardless of the value that the client sent in the message.
❑ AuthReq: Allows activating the password authentication in the establishment of IEC 61850 connection. The password
received is checked against the one assigned to the user “user61850”.
 The default password for this user is: user61850.
❑ DevGoose: Selects the Ethernet port for GOOSE messages. Any online change of this value requires the reset of the device
and therefore the signal ResetDev is activated.
 Eth1: GOOSE publication and reception enabled on interface ETH1.
 Eth2: GOOSE publication and reception enabled on interface ETH2.
 Both (Eth1): Reception on both interfaces (ETH1 and ETH2). Publication is sent by only one configurable
interface for each GOOSE. By default port ETH1.
 Both (Eth2): Reception on both interfaces (ETH1 and ETH2). Publication is sent by only one configurable
interface for each GOOSE. By default port ETH2.
❑ NoGsVlan: Defines the use of the VLAN tag in GOOSE messages. Any change in this value causes the activation of the signal
ResetDev. Default value is 0.
 Value 0: GOOSE messages are sent with VLAN TAG and are received with or without VLAN TAG.
 Value 1: GOOSE messages are sent and received only without VLAN TAG.
❑ IprvMod: Sets the access level to reports, commands and logs from the different IP addresses configured in the IPRV logical
nodes defined in the following paragraph:
 Permissive: By default all IP addresses not configured in the IPRV logical nodes have access to reports,
commands and logs. The IP addresses included in the IPRV logical nodes will have the configured access level.
 Restrictive: Only IP addresses configured in the IPRV logical nodes have access to reports, commands and logs.
The access level is configured individually for each IP address. Other IP addresses do not have access.
❑ IprvConn: The value 1 limits the IEC 61850 connections only to IP addresses configured on IPRV logical nodes and any
connection from other IP address will be rejected. The value 0 allows the connection from any IP address.
Only the settings that indicate the activation of the signal ResetDev require a restart of the device to be effective.

Ingeteam Power Technology S.A.


User Manual 310
CONFIGURATION 

10.9.2 IEC 61850 clients IPRV settings


There are 8 instances of this logical node (GEN/IPRVx) to configure the level access to reports, commands and logs of up to 8 IEC
61850 clients. Each client is identify by its IP address. The available settings for each logical node are:

❑ Addr: IP address of the client.


❑ EnaRpt: Enumerated value to configure the access level to reports from the defined IP address.
 [0] All: Allows access to all reports.
 [1] Yes: Allows access only to the reports defined in RptNam fields.
 [2] No: Not allowed access to any report.
❑ CmdEna: Boolean setting that with value 1 allows the execution of commands from the defined IP address.
❑ EnaLog: Enumerated value to configure the access level to logs from the defined IP address.
 [0] Read only: Only read access to the logs.
 [1] Read/write: Read and write access to the logs.
The signal GEN/IPRVx.St.stVal indicates whether the address configured on that node is in communication with the device. In case
of multiple connections from the same IP, the signal is 0 when all are closed.

These settings are considered special and they are configurable via an IEC 61850 connection or sending the CID file after editing the
values from pacFactory tool (menu Settings -> IPRV). They do not appear in the display or section pacFactory protection settings.

10.10 MEASUREMENT’S RANGE AUTOMATIC CONFIGURATION

Measures logical nodes which have the AdRanMea setting have the possibility of the automatic configuration of the measures
ranges (with value 1 in the AdRanMea setting).

AdRanMea settings in different logical nodes are independent. Each logical node can be configured independently.

Only de ranges of measures with a sAddress value are calculated.

If the value of AdRanMea setting is 1, the range configuration cannot be modified via IEC 61850 protocol.

The values that are automatically calculated are:

Measures:

❑ rangeC.hhLim.f
❑ rangeC.hLim.f
❑ rangeC.lLim.f
❑ rangeC.llLim.f
❑ rangeC.min.f
❑ rangeC.max.f
Angles:

❑ rangeAngC.hhLim.f
❑ rangeAngC.hLim.f
❑ rangeAngC.lLim.f
❑ rangeAngC.llLim.f
❑ rangeAngC.min.f
❑ rangeAngC.max.f
The calculation is made based on the values of scale range and transformation ratio of each measure as follows:

Ingeteam Power Technology S.A.


User Manual 311
CONFIGURATION 

❑ Signed measures:
❑ max: scale range * transformation ratio
❑ min: - (scale range * transformation ratio)
❑ Unsigned measures
❑ max: scale range * transformation ratio
❑ min: 0
And the value of the factor configured in the multiplier attribute is applied:

❑ If multiplier > 0 it is divided by 10 multiplier


❑ If multiplier < 0 it is multiplied by 10 multiplier
In both cases the limits are configured as:

❑ hLim = max
❑ hhLim = max
❑ lLim = max * 4 / 5
❑ llLim = max * 4 / 5
The rest of the configuration values of each measurement (db, SIUnits, multiplier, dbAng, limDb) are not modified.

Ingeteam Power Technology S.A.


User Manual 312
SYNCHRONIZATION 

11. SYNCHRONIZATION
Several synchronization sources are permitted, with the following priority:

❑ IEEE1588v231
❑ IRIG-B
❑ SNTP
❑ Communication protocols
❑ pacFactory (see specific user manual)
❑ Local display
In case of active synchronization with any of the sources, the sources of lower priority are blocked. Some examples:

❑ If there is synchronization by IEEE1588v2, synchronization for any other cause is not permitted. In order to consider the absence of
IEEE1588v2 synchronization and to allow other sources, 1.5 minutes must elapse without synchronization:
 When disabled by setting
 When you lose IEEE 1588v2 communication through the port (synchronization does not arrive)
 When it loses traceability or precision (the master is not synchronized)
❑ If there is synchronization by IRIG, synchronization for any other cause is not permitted. In order to consider the absence of IRIG
synchronization and to allow other sources, 1.5 minutes must elapse without the reception of correct IRIG frames.
❑ If there SNTP synchronization, the synchronization of protocols is not permitted, nor pacFactory nor display. However, if IRIG
synchronization is received, the SNTP is blocked and IRIG is synchronized.
❑ Synchronization by pacFactory and by display have the same priority and can be run simultaneously.

11.1 GENERAL SETTINGS

The unit’s data model has a GEN/LTIM node for the configuring the summer/winter time change. The node has the following settings
(see Table 185):

❑ Offset Local Time-UTC (min): Offset Local Time-UTC (min). A setting that indicates the number of minutes by which the time setting
must be put forward/put back when changing between summer/winter time. Range between -720 and 720 minutes (-12 to + 12
hours)
❑ Summer-winter time change enabled: Time change enabled. A boolean setting that allows the time setting to be changed
❑ Summer Calendar Pattern: Summer Calendar Pattern. Three selectable values:
 Last of month: Last week, refers to the weekday set in WkDayD
 First of month: First week, refers to the weekday set in WkDayD
 Second of month: Second week, refers to the weekday set in WkDayD
 Third of month: Third week, refers to the weekday set in WkDayD
 Fourth of month: Fourth week, refers to the weekday set in WkDayD
 Day of month: Selects the day of the month indicated in DayD
❑ Day Week Summer: Indicates the day of the week for the change to summer time (Monday.. Sunday)
❑ Month Summer: Indicates the month in which the change to summer time occurs (January.. December)
❑ Day Summer: Indicates the day in which the change to summer time occurs (1.. 31)
❑ Time Summer: Indicates the time at which the time changes to summer time
❑ Minute Summer: Indicates the minute (within the time set on HrD) when the time changes to summer time
❑ Winter Calendar Pattern: Winter Calendar Pattern. Equivalent to OccD but from winter to summer

31
Available from firmware version 6.0.18.0
Ingeteam Power Technology S.A.
User Manual 313
SYNCHRONIZATION 

❑ Day Week Winter: Indicates the day of the week for the change to winter time (Monday.. Sunday)
❑ Month Winter: Indicates the month in which the change to winter time occurs (January.. December)
❑ Day Winter: Indicates the day in which the change to winter time occurs (1.. 31)
❑ Time Winter: Indicates the time at which the time changes to winter time
❑ Minute Winter: Indicates the minute (within the time set on HrS) when the time changes to winter time
❑ Not Synchro Time (min): Timeout to activate synchronization alarm.
Table 185 Synchronization settings

Data Setting Minimum Maximum Step Remarks Type


TmOfsTmm Offset Local Time-UTC (min) -720 720 1 Int32
TmUseDT Summer-winter time change enabled NO (0) / YES (1) Boolean
OccD Summer Calendar Pattern 0 2 1 enum
WkDayD Day Week Summer 0 6 1 enum
MthD Month Summer 1 12 1 enum
DayD Day Summer 1 31 1 Int32
HrD Time Summer 0 23 1 Int32
MnD Minute Summer 0 59 1 Int32
OccS Winter Calendar Pattern 0 2 1 enum
WkDayS Day Week Winter 0 6 1 enum
Mths Month Winter 1 12 1 enum
DayS Day Winter 1 31 1 Int32
HrS Time Winter 0 23 1 Int32
MnS Minute Winter 0 59 1 Int32
SyncAlmTm Not Synchro Time (min) 1 1440 1 Int32

There are signals indicating the synchronization source (Table 186):

❑ Synchronization by IEEE1588: Active when the device is synchronized by IEEE1588. It is maintained activated for 90 seconds after
an IEEE1588 synchronization.
❑ Synchronization by IRIG-B: Active when the device is synchronized by IRIG-B. It is maintained activated for 90 seconds after an IRIG-
B synchronization.
❑ SNTP synchronization: Active when the device is synchronized by SNTP. It is maintained activated the period defined by not synchro
timeout SNTP setting (ValTm) after an SNTP synchronization.
❑ Synchronization by protocols: Active if the last synchronization was been received by communications protocols.
❑ Synchronization by display: Active if the last synchronization was been received by the front keyboard.
❑ Synchronization by console: Active if the last synchronization has been received from the PacFactory console.
❑ Device not synchronized: Synchronization alarm. Active if a valid synchronization (IRIG-B, SNTP or protocols) has not been received
during the timeout configured by the not synchro time setting (SyncAlmTm).
❑ Daylight saving time: Active if the local time has summer correction.

Table 186 Synchronization source

Signal Data Attribute


Synchronization by IEEE1588 SyncPTP stVal
Synchronization by IRIG-B SyncIRIGB stVal
Synchronization by SNTP SyncSNTP stVal
Synchronization by protocols SyncProt stVal
Synchronization by display SyncDispl stVal
Synchronization by console SyncCons stVal
Device not synchronized SyncAlm stVal
Daylight saving time TmDT stVal

Ingeteam Power Technology S.A.


User Manual 314
SYNCHRONIZATION 

11.2 IEEE 1588V2

The IEEE Std. 1588-2008, also known as IEEE 1588v2 or PTPv2, offers a good solution for clock synchronization in distributed systems
with high accuracy requirements. It works through Ethernet networks and achieves accuracy in the submicrosecond range.

Ingepac EF IEDs support IEEE 1588v2 and specifically the IEC 61850-9-3:2016 Ed1, also nown as Power Utility Profile (PUP), which allows
compliance with the highest synchronization classes of IEC 61850-5 and IEC 61869-9.

Following the IEC 61850-9-3:2016 Ed1 profile:

❑ The PTP over IEEE 802.3 transport mapping, specified in Annex F of IEEE 1588v2, shall be the only transport mechanism used.
❑ The peer delay request mechanism specified in Chapter 11.4 and Annex J.4 of IEEE 1588v2 shall be the only path delay
measurement mechanism in operation.
Ingepac EF IEDs support IEEE 62439-3:2016 Ed 3 Annex A when 1588 synchronization over PRP or HSR is needed.

11.2.1 Settings
There are 3 settings to set up IEEE 1588v2. They all belong to the GEN/LTMS logical node described in 1.4.1.

❑ Main Time Source: The string “1588” must be set up in this setting in order to enable 1588v2.
❑ PTP interface: This setting specifies the interface in which the IED will listen to IEEE 1588v2 messages.
❑ PTP delay mechanism: The Mechanism used peer to peer (P2P).

11.3 IRIG-B

The device is equipped with an input for synchronization by GPS, using IRIG-B time codes (consult chapter 2 for more details about the
input).

The supported IRIG-B formats are B002, B003, B006, B007 and IEEE1344. The configuration is with the IrgType setting in the GEN\LLN0
logical node (General configuration). The different options are (depending on whether the GPS send UTC or local time):

❑ “UTC without year”. The year is not taken into account and all the formats are admitted.
❑ “UTC with year”. With formats B006, B007 and IEE1344 the year is not taken into account. It cannot be used with formats
B002 and B003 because they set the year to zero value.
❑ “Local without year”. The year is not taken into account. All the formats are admitted.
❑ “Local with year”. With formats B006, B007 and IEE1344 the year is not taken into account. It cannot be used with formats
B002 and B003 because they set the year to zero value.

11.4 SNTP

The available implementation of the SNTP (Simple Network Time Protocol) is based on the points described in RFC5905. To improve the
accuracy of the synchronization and to take into account the possible delays introduced by the network, the "On-Wire" protocol, which
is described within the RFC itself, is used.

This correction algorithm uses four timestamps numbered from T1 to T4, with the timestamp of sending or receiving each message, to
calculate the offset that is required to apply to the time of the equipment after sending each synchronization request.

Ingeteam Power Technology S.A.


User Manual 315
SYNCHRONIZATION 

The following image shows in a general way the synchronization scheme:

The time offset obtained using this calculation is the deviation to be applied in the SNTP client clock to obtain the time of the SNTP
server that synchronizes it. It is a valid method for both LAN networks as well as for WAN networks that have higher response times.

The SNTP settings are included in the LTMS logical node.

Note: There is an optional configuration mode with the SNTP-IP value in the communications section of the ICD file, which is
maintained for backward compatibility with previous configuration files. The IED only uses that option if no configuration is included in
the LTMS node. Nevertheless, the recommended configuration option is through the LTMS node settings.

11.4.1 Settings
The SNTP settings are in the GEN/LTMS logical node:

❑ Main Time Source: IP address of the main NTP server. Broadcast addresses are not allowed. Value 0.0.0.0 disables the
main source.
❑ Secondary Time Source: IP address of the secondary NTP server. Broadcast addresses are not allowed. Value 0.0.0.0
disables the secondary source.
❑ Not Synchro time SNTP (min): Elapsed time in which it has not been received any correct SNTP response (the checked
fields are detailed below) from any of the sources configured for SNTP synchronization to consider the SNTP as not
synchronized. Range value is 1 to 1440 min.
❑ SNTP Polling Time (seg): Time interval between synchronization requests to the NTP servers. Range value is 10 to 3600
seconds. If the configured time is less than the real polling communication process (requests and retries in case of failure)
the synchronization active request will finish normally and a new polling timer will be started.
❑ SNTP Time delay Unicast message (seg): Waiting time for the response to an unicast synchronization request. If no
response is received in that time interval a unicast request retry cycle will be started. Range value is 1 to 60 seg.
❑ Retry number: Number of unicast request retries in case there is no response from the NTP server to a request. If the
configured number of retries finishes without response with the main source the device tries to synchronize with the
secondary source. If the configured number of retries finishes without response with the secondary source that
synchronization process is finished and the device waits the polling period to send a new request. Range value is 0 to 9.
❑ PTP interface: This setting specifies the interface in which the IED will listen to IEEE 1588v2 messages.
❑ PTP delay mechanism: This settings specifies which delay Mechanism to use: peer to peer (P2P) or end to end (E2E) delay
mechanism.
(*) Available from firmware version 6.3.20.0, the necessary settings to enable and configure symmetric key authentication in SNTP
requests:

❑ SNTP authentication: This setting enables the authentication in SNTP messages based on the keys file configured.
❑ SNTP key: The number of the key used for the authentication. It shall match with the value configured in the SNTP server
used as synchronization source.

Ingeteam Power Technology S.A.


User Manual 316
SYNCHRONIZATION 

Table 187 SNTP settings LTMS node

Data Setting Minimum Maximum Step Remarks Type


TmSrcSet1 Main Time Source IP address VisString255
TmSrcSet2 Secondary Time Source IP address VisString255
ValTm Not Synchro timeout SNTP (min) 1 1440 1 Int32
PollTms SNTP Polling Time (seg) 10 3600 1 Int32
EspTms SNTP Time delay Unicast message (seg) 1 60 1 Int32
NRetry Retry number 0 9 1 Int32
PTPIface PTP Interface 1 2 1 Eth1/Eth2 enum
PTPDelM PTP delay mechanism 0 1 1 P2P / E2P enum
SNTPAuth SNTP authentication (*) NO / YES Boolean
TrustedKey SNTP key (*) 1 65535 1 Int32

The keys file is configurable from the website 32, and it shall be shared between the IED and the SNTP server. The following key types
are supported by the IED:

❑ MD5
❑ SHA
❑ SHA1
❑ RIPEMD160

To provide additional information, a digital signal and a counter have been added with data about the status of the SNTP
authentication:

❑ AuthCfgErr: Configuration error boolean signal. Indicates that there is some type of error in the configuration of the keys
file or in the selected settings. In this case, the IED sends SNTP requests without authentication so it can be synchronized.
❑ AuthRspErr: Counter with the number of not authenticated responses or with authentication failure. When this occurs, the
response obtained is discarded and the device is not synchronized. This counter is increased in case of:
 The SNTP server rejected the request (because the key was not configured or the expected signed value did
not match).
 The received authentication is not considered valid (the calculated signed value does not match the expected
one).

The following diagram details the synchronization process:

32
Available from firmware version 6.5.22.0

Ingeteam Power Technology S.A.


User Manual 317
SYNCHRONIZATION 

The following values are checked in the synchronization responses to consider them valid and apply the time to the internal clock:

❑ Message length.
❑ Flags mode: Server.
❑ Flags version number: NTP version 4.
❑ Flags leap indicator: Different from 3.
From the following firmware versions of Ingepac EF these checks are also available:

 Ingepac EF version 6.1.18.5:


❑ Flags version number: NTP version 3 or 4.
❑ Valid stratum value: Between 1 and 15.

 Ingepac EF version 6.3.20.0:
❑ The origin timestamp received in the response packet must match with the transmitted timestamp on the request.

Ingeteam Power Technology S.A.


User Manual 318
SYNCHRONIZATION 

11.5 QUALITY FLAGS IEC 61850

In the IEC 61850 data there are quality flags which detail the validity of the time in a timestamp sent by communications. These are the
used quality flags:

❑ Clock Not Synchronized: Active jointly with the synchronization failure alarm.
❑ Leap Second: It is activated if the synchronization source provides this data. Active for SNTP, IRIG-B and 1588.
❑ Clock Failure: Active jointly with the failure of the internal RTC clock.

Ingeteam Power Technology S.A.


User Manual 319
DATA ACQUISITION FUNCTIONS 

12. DATA ACQUISITION FUNCTIONS


The information generated by the unit is stored in xml format files, except the format of the oscillography, which is stored in comtrade
format.

12.1 STATUS REPORT

The status report indicates the current status of the protection, showing instantaneous values. This report is updated approximately
every 1 second.

The information available in the status message is:

❑ Version. Indicates the unit version:


 CPU: Shows the CPU’s main firmware version.
 CPU2: Shows the firmware version of the FPGA and interface with I/O modules.
 OTHER: Shows the analogue card's firmware and I/O modules.
 Only in models with sampled values reception modules:
 SV: Shows the module main firmware version
 SV-FPGA: Shows the firmware version of the FPGA.
❑ General. Displays the unit’s general data:
 Relay date and time. Within the <Date> tag, the date (Date) and time (Time) are shown.
 Active table. Within the <Setting Group> tag, the active table number is shown.
❑ Measurements: Within the Measurements tag, the unit’s measurements are shown. The measurements correspond to
the fundamental frequency.
 <Analog>: Type, module and angle of each of the unit’s 12 transformers.
 <Sequence>: Direct, inverse and zero sequences of currents and voltages (module and angle).
 <Power>: Total real, reactive and apparent power.
 <Frequency>. Frequency value.
 <Battery> External power supply battery voltage.
 <InternalBattery> Internal battery voltage for maintenance of Data.
 <Maximeter>. Indicates the maximeter value for each current and voltage phase. It has a “Reset” button.
 <Thermal>. Phase and neutral thermal image value. It also has a “Reset” button.
 <Temperature> Indicates the unit’s temperature.
 The LD models show information of:
 Differential current. Indicates the fundamental value of the three phases.
 Restraint current. Indicates the Restraint current of the three phases.
 2° harmonic differential current. Indicates the value of the three phases.
 End measures. For each end, indicates the fundamental and 2° harmonic of the total currents (module and
angle) of the three phases.
 Total current. Indicates the total current of the three phases. Only in 52 ½ configurations.
 The TD models show information of:
 Differential current. Indicates the fundamental value of the three phases.
 Restraint current. Indicates the Restraint current of the three phases.
 2° to 5th harmonic differential current. Indicates the value of the three phases.
 Sequences of current, maximeter and thermal image are independent of each winding.
 The CB models show information of:

Ingeteam Power Technology S.A.


User Manual 320
DATA ACQUISITION FUNCTIONS 

 <CapacitorBank.> Indicate the input measurements to capacitor bank connect/disconnection automatism, voltage
and reactive.
❑ Input and output status. The status of the digital inputs and outputs is indicated in each of the cards available in the unit.
Each card is distinguished by its address, indicated in GGIO1 to GGIO8.
 Digital inputs. Ind1.stVal to Ind32.stVal indicate “Y” if enabled and “N” if not. There are as many values as there are
inputs in the card.
 Digital outputs. SPCSO1.stVal to SPCSO16.stVal indicate “Y” if enabled and “N” if not. There are as many values as
there are outputs in the card.
❑ Protection units. Indicates the current status of each of the functions: enabled, pick up, trip and last trip. In each of the
functions the data available in each node are indicated.
 Status. In <StEna.stVal>, the function is indicated as active and not blocked with “Y”. “N” is used to indicate that the
function is not enabled or blocked or in operation
 Pick up. Indicates in <Str> whether the unit is picked up “Y” or not “N”. The data depends on the unit, for example, for
phase A it would be Str.phsA.
 Activation. Indicates in <Op> whether the unit is tripped “Y” or not “N”. The data depends on the unit, for example, for
phase A it would be Str.phsA.
 Last trip. Indicated within <l>. “Y” is used to indicate if the last trip was due to this cause, whilst "N" is used to indicate
otherwise.
❑ Recloser status: Indicates the current status of the recloser. The signals are in <RREC1>. “Y” is used to indicate active
signals, whereas "N" is used to indicate inactive signals. The available signals and their references are indicated in the
recloser section. These include:
 in service/blocked.
 in stand-by.
 ongoing cycle, indicating the closure cycle that is currently active.
 definitive trip.
 internal block, distinguishing different causes.
 External block.
 “Put Into Service and “Put Out of Service” buttons
❑ Frequency recloser status: Indicates the current status of the frequency recloser. The signals are in <FRREC1>. “Y” is used
to indicate active signals, whereas "N" is used to indicate inactive signals. The available signals and their references are
indicated in the frequency recloser section.
❑ Synchronism check unit status. The general status of the synchronism is displayed in RSYN1 and the presence of voltage in
RVRS1. “Y” is used indicated active signals and "N" for inactive signals. The available signals and their references are
indicated in the synchronism section.
❑ In CB models (Capacitor Bank): Status of capacitor bank connect/disconnection automatism. Indicates the actual state of
automatism. The signals are in <ZCAP>, indicating for each of the signals if is active "Y" or no "N". In the section of
capacitor bank automatism are indicated available signals and their reference, among which are:
 Automatism Status
 Trip Block 86
 Reactive Converter Fail
 Manoeuvre Inhibit for each breaker
 Excesive Manoeuvre
 Open command
 Period type (Rush, Off-peak, Normal)
 Season
❑ Protection status. With the “PROT” data in LLN0, “Y” indicates whether the relay is in service, “N” indicates if the relay is
out of service.
❑ General status. Indicated in LLN0 with the “GEN” data, in which the following is indicated:

Ingeteam Power Technology S.A.


User Manual 321
DATA ACQUISITION FUNCTIONS 

 Unit hw status. Indicating if there is failure "Y" or "N".


 Local/remote mode. Indicating if it is local, "Y" or "N".
 Events pending dispatch. Indicating if there is an event pending dispatch, "Y" or "N".
 Failure in IRIG synchronization. Indicating if there is failure, "Y" or "N".
 V2 and Vn voltage monitoring. Indicating if there is failure, "Y" or "N".
 Check on internal communication between cards. Indicating if there is failure, "Y" or "N".
❑ Open pole logic status. Shown in POPD1, indicating:
 StEna.stVal. Indicates whether the function is enabled, “Y” or “N”.
 OpenPole. For each pole and general, indicating whether open “Y” or closed “N”
 Number of open poles. One (OneOpPole), two (TwoOpPole), three (ThreeOpPol) or at least one (OpenPole)
 Broken conductor. Indicating whether the phase is broken for each of the poles, “Y” or “N”.
 Deal line. Indicating whether there is a dead line for each of the poles, “Y” or “N”.
❑ Breaker status. Shown in XCBR. There is independent information of every breaker, indicating:
 BrDISt. For each pole and general, the status of the associated digital input: closed “Y”, open “N”.
 CloseOrdBr. For each pole and general, the status of the closure command: active “Y”, inactive “N”.
 OpenOrdBr. For each pole and general, the status of the opening command: active “Y”, inactive “N”.
 ClsFailBr. For each pole and general, indicating whether there has been a failure in the closure command, “Y” or “N”
 OpenFailBr. For each pole and general, indicating whether there has been a failure in the opening command, “Y” or
“N”
❑ Breaker monitoring status. Shown in CBOU1, indicating the value of the ki2 sum for each pole.
❑ Monitoring units.
 CCTS1. CT monitoring. There is function enabled data (StEna.stVal) and CT monitoring activation data (CTSpv.general)
 CTSU1. Temperature monitoring. There is a function enabling data (StEna.stVal) and an indication of the temperature
above (OverTemp) and below (UnderTemp) the threshold.
 CESS1. External power supply monitoring. Indication of external power supply above (OverVcc) or below (UnderVcc)
the threshold. Also indicates whether the function is enabled or not (StEna.stVal).
 CSUS1. Indicates battery failure status (DFFA), if it is activated “Y" or deactivated “N”.
The status data are displayed on the PacFactory console and in the unit's display:

❑ PacFactory. All the status message information is displayed, grouped in tabs according to the information:
 General. The date, active table, versions and measurements are displayed.
 I/O. The digital inputs and outputs are displayed.
 Enabled. Indicates whether the units are operative (enabled and not blocked) or not.
 Protection status. The status of the protection units is displayed, i.e., if they are picked up and/or tripped.
 Breaker and monitoring. The breaker, breaker monitoring and circuits statuses are displayed.
 Recloser, synchronism or capacitor bank. The status of the recloser, synchronism or capacitor bank units is displayed.
 Check. The results of the various checks that are carried out in the unit are displayed.
❑ Display. Grouped into several screens and displaying:
 General: Date and active table.
 Transformer measurements and configuration.
 Current and voltage maximeters.
 I/O. The digital inputs and outputs are displayed.

Ingeteam Power Technology S.A.


User Manual 322
DATA ACQUISITION FUNCTIONS 

Figure 186 PacFactory status screen

12.2 PRIMARY MEASUREMENTS REPORT

This report indicates the measurement transformers’ primary measurements, applying the transformer ratio. The maximeter
information is used for the maximeter reports.

The information available in the measurements message is:

❑ Distance. In the <Distance> tag, indicating the distance of the last fault.
❑ Currents. Within the <Currents> tag, showing the rms current measurements in primary:
 Earth-phase.
 The module and angle of each phase, neutral and sensitive neutral.
 The average current module of the three phases.
 THD of each phase, neutral and sensitive neutral.
 Thermal image <Thermal>. Value of phase and neutral thermal image.
 Sequences <Sequence>. Current sequences module (I0, I1, I2)
❑ Voltages Within the <Voltage> tag, showing the rms voltage measurements in primary:
 Earth-phase.
 The module and angle of each phase and neutral.
 The average voltage module of the three phases.
 THD of each phase and neutral.
 Phase-phase <Phase>.
 Phase pair module (AB, BC and CA) and average.
❑ Sequences. Voltage sequences module (V0, V1, V2)
 Frequency. Frequency value.
 Powers. Within the <Power> tag, showing the rms measurements for each phase and total:
 Real power. Per phase and total.

Ingeteam Power Technology S.A.


User Manual 323
DATA ACQUISITION FUNCTIONS 

 Reactive power. Per phase and total.


 Apparent power. Per phase and total.
 Power factor <Power Factor>. Per phase and average.
 Energy counters <Energy>. There is a reset button for the energy counters.
 Last reset command date
 Positive and negative real energy counter value
 Positive and negative reactive energy counter value
❑ Maximeters. Shows the maximum value and the date on which it was produced. There is a reset button for the
maximeter.
 Current. For each phase.
 Voltage. For each phase.
 Real power. For phase and total.
 Reactive power. For phase and total.
 Apparent power. For phase and total.

Figure 187 PacFactory measurements screen

12.3 FAULT REPORT

The fault reports include information about the unit’s data during the fault, as well as the active settings during the fault. The last 20
faults are stored in a non-volatile memory.

The name of the file uses the standard IEEE C37.232-2007, using the fields:

Start Date, Start Time, Time Code, Station Identifier, Device Identifier, Company Name

For example, “100626, 46702262,+2h30t,Substation,Rele1,Ingeteam”, which means:

❑ Start Date: Trip date with a 2-character format for the year, the month and the day. For example, 26/june/2010 would be 100626.
❑ Start Time: Indicates the milliseconds as of 00:00 of the day, that is, milliseconds as of midnight.

Ingeteam Power Technology S.A.


User Manual 324
DATA ACQUISITION FUNCTIONS 

❑ Time Code: Indicates the time zone amplitude sign, and can indicate minutes if necessary. For example, “t +2” indicates time zone
2, while “+2 h30t” indicates that the time zone is 2 hours 30 minutes.
❑ Station Identifier. Indicates the substation name. The installation’s short name (InsShNam) from the “PROT/LPHD1” node is used"
❑ Device Identifier. Indicates the unit’s name. The relay’s short name (RelShNam) from the “PROT/LPHD1” node is used"
❑ Company Name. Indicates the name of unit’s manufacturer, in this case, Ingeteam.
The information available in the fault is:

❑ Date and time: <Fecha>. Indicates the date as a string in the “dd/mm/yy hh:mm:ss.ms” format, i.e., “23/04/09 10_41_30_256”.
There are three dates available
 Start of the fault (first unit picked up): <Inicio>
 Trip (first unit tripped): <Disparo>.
 End of fault (when the trip signal disappears): <Fin>
❑ Configuration: <Config>. Indicates the configuration of each of the 12 transformers: type and scale range.
❑ Pre-fault and fault. Indicates the values measured before the fault and upon the fault. They are grouped into “Pre-fault” and
“Fault”, and the same data is available in both cases:
 Transformer measurements <Analog>. It indicates the measurement in the module and the angle of each transformer.
 Sequences. Indicates the measurements in the module and the angle of the current sequences (I0, I1 and I2) and the voltage
(V0, V1 and V2).
 Powers. Indicates the measurements of the total real, reactive and apparent powers.
 The LD models show information of:
 Differential current. Indicates the fundamental value of the three phases.
 Restraint current. Indicates the Restraint current of the three phases
 2° harmonic differential current. Indicates the value of the three phases.
 End measures. For each end, indicates the fundamental and 2° harmonic of the total currents (module and
angle) of the three phases.
 The TD models show information of:
 Differential current. Indicates the fundamental value of the three phases.
 Restraint current. Indicates the Restraint current of the three phases.
 Sequences of current, maximeter and thermal image are independent of each winding.
❑ Distance to fault.
❑ Frequency in the moment of the fault.
❑ Thermal image upon trip. The thermal image is indicated as a % of phases and neutral.
❑ Fault max. Maximum values of the current channels and I0 during the fault.
❑ Breaker. Indicates breaker monitoring data upon the fault.
 Open current. For each phase, indicates the current value upon the trip.
 Sigma ki. For each phase, indicates the sigma ki2 value.
 Num. reclose. Number of recloser performances.
❑ Fault and trip type <Tipo/Type>: Summary of the fault with the 3-letter code formed by combinations of the characters A, B, C, N,
NS and G (if tripped by a phase, neutral, sensitive neutral or ground), DIF (differential), RG (restricted earth), RTP (teleprotection),
IF (phase overcurrent), IN (neutral overcurrent), D (current unbalance), VO (zero-sequence overvoltage), HV (overvoltage), LV
(undervoltage), RTP (teleprotection), DT (transferred trip), DP (pole discordance), v/f (overexcitation v/f), IT (thermal image).
Example: AC is a two-phase fault in phases A and C.
 Fault type: Indicates the pick up type.
 Trip type: Indicates the trip type.
❑ Details of units. Indicates the picked up and tripped units. Indicates whether the unit is active “Y” or not “N” for each logical node
available in the unit.

Ingeteam Power Technology S.A.


User Manual 325
DATA ACQUISITION FUNCTIONS 

 Pick up. Indicates in <Str> whether the unit is picked up “Y” or not “N”. The data depends on the unit, for example, for phase A
it would be Str.phsA.
 Activation. Indicates in <Op> whether the unit is tripped “Y” or not “N”. The data depends on the unit, for example, for phase
A it would be Str.phsA.
❑ Active settings. Active settings in the moment of the fault. Indicates the setting file name. It can be accessed to consult the settings.
Figure 188 PacFactory fault screen

12.4 INCIDENT REPORT

The unit stores in a queue of 1000 non-simultaneous protection events in a non-volatile memory. Each protection event is recorded
with its date and time, as well as the current and voltage measurements of all the transformers and the frequency.

The protection events can be masked individually, so that only protection events configured by the user are generated. These enablings
are available in the GEN/RSUC node.

The information available in each record is:

❑ Date: With a resolution of one millisecond.


❑ Information. Within the <Inf> tag the protection event signal number and its status 0 (Deactivation) / 1 (Activation) are
indicated. Each protection event record can have up to 16 simultaneous signals.
❑ Measurements. The transformer measurements at the time of the protection event (module and angle) and frequency
measurement are shown for each of the unit’s transformers.
❑ The LD models show information of:
 Differential current. Indicates the fundamental value of the three phases.
 Restraint current. Indicates the Restraint current of the three phases
 2° harmonic differential current. Indicates the value of the three phases.

Ingeteam Power Technology S.A.


User Manual 326
DATA ACQUISITION FUNCTIONS 

Figure 189 Example of protection event record

<Reg Fecha="15-06-10 21:50:38:792">


<Inf Sen="8426" Status="1"/>
<Inf Sen="8433" Status="0"/>
<Med>
<T1 Mod="0.00" Arg="0.00"/>
<T2 Mod="0.00" Arg="0.00"/>
<T3 Mod="0.00" Arg="0.00"/>
<T4 Mod="0.00" Arg="0.00"/>
<T5 Mod="0.00" Arg="0.00"/>
<T6 Mod="0.00" Arg="38.10"/>
<T7 Mod="31.68" Arg="58.53"/>
<T8 Mod="99.94" Arg="-62.01"/>
<T9 Mod="99.95" Arg="178.00"/>
<T10 Mod="31.67" Arg="58.54"/>
<T11 Mod="99.98" Arg="-62.02"/>
<T12 Mod="99.94" Arg="178.00"/>
<FRE Hz="50.00"/>
</Med>
</Reg>

Figure 190 PacFactory protection event screen

12.5 HISTORICAL MEASUREMENT REPORT

The unit saves a queue of historical measurement reports in the non-volatile memory. Depending on the registered measurements,
4000 or 1000 registers are available.

Each record includes the maximum, minimum and average currents of each measurement, calculated within a programmable time
window, detected during a programmable recording period. The measurements are secondary.

The historical measurement report is grouped into records in which the first corresponds to the oldest and the last to most recent, so
that when the file is opened, the first item we see is the oldest.

The format of this file for each record is:

❑ Record number
❑ Date: With second precision: Day and Time
❑ Measurements: Maximum/minimum/average magnitude values:
The settings employed by this unit are in the PROT/MHRE node:

Ingeteam Power Technology S.A.


User Manual 327
DATA ACQUISITION FUNCTIONS 

❑ Sample time window. Indicates the time in minutes during which the average is calculated
❑ Record interval. Indicates the time in minutes in which each record is created
❑ Start time. Indicates the time after which the historical measurement record is started
❑ End time. Indicating the time up to which the historical measurements record is carried out
❑ Calendar mask. Indicates whether the historical measurements record is created every day (YES) or if it is only created on
the days indicated in the day selection mask.
❑ Day selection. It indicated, for each day of the week, whether the record was created.
❑ Register mode33. Selects between standard or extended:
 Standard. It saves 4000 registers, with máximum, mínimum and average of the mean currents and voltages, real,
reactive and apparent power, frequency and external power supply.
 Extended. Extended number of measures. It saves 1000 registers, with máximum, mínimum and average of the phase
and neutral currents, phase voltages, current and voltage sequences, real, reactive and apparent power, power factor
and the result of 10 measurements data logics AutGGIO.AnIn.
The units of the measurements are:

❑ Current. The units are secondary amps.


❑ Voltage. The units are secondary volts.
❑ Real power. The units are secondary watts.
❑ Reactive power. The units are secondary VAR.
❑ Apparent power. The units are secondary VA.
❑ Frequency. Units are Hz.
❑ External power supply. The units are volts.

Table 188 Historical measurement settings

Data Setting Min. Max Step Remarks Type


SmTmm Sample time window 1 15 1 minutes uint32
RegIntTmm Record interval 1 1440 minutes uint32
StH Start time 0 23 1 uint32
EndH End time 0 23 1 uint32
DayEna Calendar mask YES/NO Boolean
SunEna Selection Sunday YES/NO Boolean
MonEna Selection Monday YES/NO Boolean
TueEna Selection Tuesday YES/NO Boolean
WedEna Selection Wednesday YES/NO Boolean
ThuEna Selection Thursday YES/NO Boolean
FriEna Selection Friday YES/NO Boolean
SatEna Selection Saturday YES/NO Boolean
RegType Register mode Standard / Extended Boolean

33
Available from firmware version 5.19.15.7 and ICD version 6.3.0.0. Previous versions is fixed “Standard”.

Ingeteam Power Technology S.A.


User Manual 328
DATA ACQUISITION FUNCTIONS 

Figure 191 Example of records

<REG Num="0" Day="18/04/10" Time="00:00:37">

<I_A Max="0.000" Min="0.000" Media="0.000"/>

<V_V Max="0.000" Min="0.000" Media="0.000"/>

<P_W Max="0.00" Min="0.00" Media="0.00"/>

<Q_VAR Max="0.00" Min="0.00" Media="0.00"/>

<S_VA Max="0.00" Min="0.00" Media="0.00"/>

<f_Hz Max="0.000" Min="0.000" Media="0.000"/>

<Batery_V Max="120.51" Min="120.51" Media="120.51"/>

</REG>

12.6 STATISTICAL DATA REPORT

Displays the statistical data calculated in the unit: currents, action times and counters. It has reset buttons.

The values available are:

❑ The current statistics are grouped in the <Current> tag and include:
 <ki2> Ki2 accumulated by each of the 3 phases. Each phase can be independently reset to the initial value.
 <Cut> Opened current. Indicates the last (Last) and maximum (Maximum) open current per phase
❑ The counters are grouped in the <Counters> tag and include:
 <Reclose> Reclosure counter. Indicates the number of reclosures effected, separating them according to first, second,
third and fourth reclosure. There is a command for resetting the counter.
 <Openings>. Opening counter for each of the 3 phases, includes trips and manual openings. There are commands for
resetting each phase's counter and a global counter for all the phases.
 <Trip>. Trip counter for each of the 3 phases. There are commands for resetting each phase's counter and a global
counter for all the phases.
 <Close>. Closure counter for each of the 3 phases. There are commands for resetting each phase's counter and a global
counter for all the phases.
❑ The timers are grouped in the <Timers> tag and include:
 <Opening>. Indicates the electric (Electrical) and mechanical (Mechanical) opening times in milliseconds per phase
(maximum, average and last) and the dispersion for each pair of phases (maximum, average and last).
 <Close>. Indicates the electric (Electrical) and mechanical (Mechanical) closure times in milliseconds per phase
(maximum, average and last) and the dispersion for each pair of phases (maximum, average and last).
 <Inactivity> Indicates the days of breaker inactivity for each phase.
❑ There are commands to reset:
 Opening and close times
 Inactivity days
 Dispersion times.
❑ There is a command for the complete reset of each breaker: opening, trip and close counters, ki2, cut current and times.
The reclose counter is not reset.
❑ Models with two breakers, current, counters and times are independent for each breaker.
❑ <Time> Indicates the time in seconds during which the current has been within specific ranges.
 From 2 to 5 times In

Ingeteam Power Technology S.A.


User Manual 329
DATA ACQUISITION FUNCTIONS 

 From 5 to 12.5 times In


 From 12.5 to 20 times In
 From 20 to 40 times In

Figure 192 PacFactory statistics screen

12.7 MAXIMETER/MINIMETER REPORT

Displays the maximum and minimum values integrated in the time. It has buttons to individually reset the maximeters and/or
minimeters.

The Data displayed are:

❑ Each phase’s current


❑ Each phase’s voltage
❑ Real power per phase and total
❑ Reactive power per phase and total
❑ Apparent power per phase and total
❑ Frequency
❑ External battery measurement

Ingeteam Power Technology S.A.


User Manual 330
DATA ACQUISITION FUNCTIONS 

Figure 193 PacFactory maximeter/minimeter screen

12.8 OSCILLOGRAPHY

The oscillography is stored in binary comtrade format. There is a CFG config file and a DAT data file for each.

For additional information see on “IEEE Standard Common Format for Transient Data Exchange (COMTRADE) for Power Systems”.

It allows 16 analogue signals:

❑ 12 analogue inputs from the transformers (current and voltages)


❑ 4 frequency measurements34 (V phase B, V synchronism, frequency 2Va-Vb-Vc, V synchronism 234)
❑ External battery used as the power supply of the equipment
❑ LD models show the differential and restraint currents of the three phases.
It allows up to 15034 digital signals, selected among all the signal of the equipment.

The trigger signals are selected among the registered signals, when the set “Trigger Signal” is set to “YES”. If it is set to “NO”, that signal
is registered but does not start the oscillography.

The length is set in cycles (Total Duration), from 20 up to 420 cycles (8,4 seconds for 50Hz and 7 seconds for 60Hz).

Pre-fault duration (cycles) indicates the pre-fault cycles that are stored in each disturbance recorder prior to the trigger, being able to
vary between 1 and 415 cycles.

The number of samples can be selected among the options of the following table. Depending on the device and ICD used, the number
of the samples per cycle is different to adapt to the different devices. The relationship between them is shown in the following table

34
Available since firmware version 6.0.18.2 and ICD 8.2.0.0. Up to that version there are 100 digital signals and 3 frequencies

Ingeteam Power Technology S.A.


User Manual 331
DATA ACQUISITION FUNCTIONS 

Table 189 Options of samples per cycle

Equivalent Conventional Sampled values Sampled values


Setting35
setting Devices 80/cycle 96/cycle
Full 144 144 80 96
1 de 2 72 72 40 48
1 de 3 48 48 40 32
1 de 4 36 36 20 24
1 de 6 24 24 20 16
1 de 9 16 16 20 16

The continuous mode allows increasing the length if at the end of the register there is a trigger signal activated. In that case, the
register continues the number of cycles set in the “Total Duration (cycles)”, checking again the trigger signals at the end of the new
register. The total register is limited to 5Mb or 3 times the setting “Total Duration (cycles)” (the most restrictive of both).

In order for the trigger signal to act, it has to change the status, that is, it has to pass from deactivated to activated. If one trigger signal
is continuously activated, it does not start, nor extend the oscillography register.

The digital signals set to “NO” in the “Trigger signal” setting are displayed, but do not start, nor extend the oscillography register.

The oscillography allows to display signals that do not start the register. For example, the protection trip signal can initialize an
oscillography register, where the start signals are displayed. Table 190 shows an example of an oscillography configuration, with 11
digital signals registered but only three signals start the register (General trip, 51 trip and GGIO1 Digital input 1). At the end of the
register, if one of these three signals, continues activated, the oscillography is extended the cycles set in “Total Duration (cycles)”;
otherwise the oscillography is finished.

Table 190 Oscillography configuration example

Settings Value
Recorded signal 01 General trip
Trigger Signal 01 YES
Recorded signal 02 General start
Trigger Signal 02 NO
Recorded signal 03 51 start
Trigger Signal 03 NO
Recorded signal 04 51 trip
Trigger Signal 04 YES
Señal registrada oscilo 05 IOC1 Trip phase A
Trigger Signal 05 NO
Recorded signal 06 IOC1 Trip phase B
Trigger Signal 06 NO
Recorded signal 07 IOC1 Trip phase C
Trigger Signal 07 NO
Recorded signal 08 IOC1 Start phase A
Trigger Signal 08 NO
Recorded signal 09 IOC1 Start phase B
Trigger Signal 09 NO
Recorded signal 10 IOC1 Start phase C
Trigger Signal 10 NO
Recorded signal 11 GGIO1Digital input 1
Trigger Signal 11 YES

10Mb of non volatile memory is available to store oscillography registers. The total number of registers depends on the settings. Table
191 shows some examples of the capacity (with the continuous mode set to “NO”), where the most influential settings are the length
and the number of samples.

35
Available since ICD version 8.1.0.18

Ingeteam Power Technology S.A.


User Manual 332
DATA ACQUISITION FUNCTIONS 

Table 191 Oscillography capacity

Total Duration
Number of samples/cycle Number of digital signals Number of oscillographys
(cycles)
420 144 100 3
420 144 32 3
420 36 100 13
420 36 32 15
50 144 100 27
50 144 32 32
50 36 100 98
50 36 32 121
20 144 100 34
20 144 32 78
20 36 100 206
20 36 32 271
20 16 100 350
20 16 32 499

The settings employed by this unit are in the PROT/RDRE node:

❑ Total Duration (cycles). Indicates the total duration of disturbance recorder (in cycles).
❑ Pre-fault duration (cycles). Indicates the pre-fault cycles that are stored in each disturbance recorder
❑ Number of samples/cycle. Indicates the samples per cycle stored in the disturbance recorder.
❑ Recorded signal X. Indicates the signal that is stored in record position X. If programmed as -1, no signals are recorded.
❑ Trigger X signal. If the signal is configured, it indicates whether it provokes a disturbance recorder pick up (1) or not (0). If
set to “No”, it is only displayed.
The trigger and recorded signals are repeated up to 100 possible signals.

Table 192 Oscillography settings

Data Setting Min. Max Step Remarks Type


OscCyc Total Duration (cycles) 20 420 1 cycles Int32
PreCyc Prefault duration (cycles) 1 415 1 cycles Int32
NuSaCy Number of samples/cycle enum
OscReg1 Recorded signal 1 Int32
OscTrg1 Trigger 1 signal 0 1 1 YES/NO Boolean
OscReg2 Recorded signal 2 Int32
OscTrg2 Trigger 2 signal 0 1 1 YES/NO Boolean
Recorded signal and trigger up to 15034 0 1 1 YES/NO Boolean

The disturbance record configuration file (CFG) contains the general disturbance recorder information (Figure 194):

❑ Total number of analogue and digital channels available in the disturbance recorder.
❑ Analogue channel data: bay, identification, measurements scaled (multiplier "a", offset "b") and limits (maximum and minimum).
The real value of the signal, using the value of the sample is "a·sample + b".

❑ Indication that samples are secondary values ("S") and conversion factor to primary values (it`s the setting “transformer ratio” of
the channel). As the samples are secondary values, the conversion factor to secondary is “1”.
❑ Digital input data: bay and identification.
❑ Sample data: signal frequency, sampling frequency, number of the last sample.
❑ Disturbance recorder start and end dates.
❑ Data file format
The disturbance recorder data file (DAT) includes the information captured in the disturbance recorder, with the following available for
each sample:

Ingeteam Power Technology S.A.


User Manual 333
DATA ACQUISITION FUNCTIONS 

❑ Sample number
❑ Sample time
❑ Analogue samples values
❑ Digital signals values
The name of the file uses the standard IEEE C37.232-2007, using the fields:

Start Date, Start Time, Time Code, Station Identifier, Device Identifier, Company Name

For example, “20100626, 46702262,+2h30t,Substation,Rele1,Ingeteam”, which means:

❑ Start Date: Trip date with a 4-character format for the year, the month and the day. For example, 26/june/2010 would be
20100626.
❑ Start Time: Indicates the milliseconds since 00:00 of the day, that is, milliseconds since midnight.
❑ Time Code: Indicates the time zone amplitude sign, and can indicate minutes if necessary. For example, “t +2” indicates
time zone 2, while “+2 h30t” indicates that the time zone is 2 hours 30 minutes.
❑ Station Identifier. Indicates the substation name. The installation’s short name (InsShNam) from the “PROT/LPHD1” node
is used".
❑ Device Identifier. Indicates the unit’s name. The relay’s short name (RelShNam) from the “PROT/LPHD1” node is used".
❑ Company Name. Indicates the name of unit’s manufacturer, in this case, Ingeteam.

Figure 194 Configuration file


USB ACCESS 

13. USB ACCESS


The unit can be accessed via the front USB to retrieve reports and CID from the device and to load a new CID or a firmware update.

The USB port can be configured from the local HMI (Menu: Password -> USB Configuration).

The configuration options are:

❑ Without password: No password is needed.


❑ With password: The local HMI password must be entered before any USB operation.
❑ Disabled: The USB port is disabled.

13.1 DOWNLOADING REPORTS

When a pendrive is inserted, the following appears in the front above the current screen, indicating that the device has been detected:

USB Detected

The unit’s reports are automatically dumped onto the pendrive.

While the data is being downloaded, the following appears in the front above the current screen:

USB Detected

Downloading data

Just in case there is a CID, an ICD or and IID in the pendrive, the user will be asked for a confirmation to load this file into the unit.

WANT TO START

THE CID UPDATE

CANCEL

ACCEPT

PRESS ENTER: RUN OPTION

If accepted, the following appears on the screen:

USB Detected

Downloading data

If canceled, downloading is assumed to be complete, and the following appears on the screen for 5 seconds:

REMOVE THE

USB DEVICE

As of this moment, the pendrive can be removed.

Only the reports existent in the unit at the time of the download will appear in the pendrive, with the data structure:
Ingeteam Power Technology S.A.
User Manual 335
USB ACCESS 

❑ Root with the short installation and relay name (PROT/LPHD node), and the iedName, separated by “_”·, i.e.,
“Instalacion_Rele_iedName”
❑ COMTRADE. This directory contains the disturbance recorders generated in the unit
❑ FAULT RECORDS. This directory contains the fault records generated in the unit.
❑ The rest of the unit’s reports are dependent on the root:
 Maximetro.xml
 Sucesos.xml
 Informe_Estadisticos.xml
 Registro.xml
 CID
For detailed information about these reports, see Chapter 10, “DATA ACQUISITION FUNCTIONS

”.

Figure 195 USB Tree

13.2 LOADING CID

When a pendrive is inserted into the front USB port, a check is run to see if an ICD exists. If there is an ICD, it is copied into the directory
“public/SCL/notvalidated” in order that it may be operative in the unit.

During the search for the ICD, the existence of a file with an ICD, icd, CID, cid, IID or iid extension is checked. There is not a established
filename as only the extension is checked.

If there is more than one file with one of the indicated extensions, the ICD is considered invalid and not ICD is captured.

13.3 LOADING FIREWALL CONFIGURATION

When a pendrive is inserted into the front USB port, a check is run to see if a firewall configuration file exists. In that case, it is copied
into the directory “public/SCL/notvalidated” in order that it may be operative in the unit.

During the search, the existence of a file with “fwc” extension is checked. There is not a established filename as only the extension is
checked.

If there is more than one file with one of the indicated extensions, the file is considered invalid and not captured.

13.4 FIRMWARE UPDATE

For firmware update via USB, a USB flash drive must be inserted in the front USB port, with a "FW" directory with a valid firmware file.

Ingeteam Power Technology S.A.


User Manual 336
USB ACCESS 

In the local display, the user will be prompted for a confirmation to start the update. It is very important that during the process of
updating firmware the device is not turned off since in that case the device could become unusable.

After the update the device will restart automatically and the result of the update can be consulted either in the device versions screen
or in the latest updates screen (consult display section).

13.5 USB ENABLING

To increase the security of the device, the USB port can be disabled, preventing access to the device via USB. With the USB disabled,
ICD and firmware loading and data download of the equipment are not allowed.

USB enable / disable can only be performed from the display (consult display section). It is done from the Password screen. The setting
will have 3 possible values:

❑ Disabled: USB is not available.


❑ With Password: USB processing is available but you need to enter the password of the settings menu.
❑ Without Password: USB processing is available without the need to enter a password.

Ingeteam Power Technology S.A.


User Manual 337
FTP ACCESS 

14. FTP ACCESS


The public user for FTP access is as follows:

❑ User: ftpuser
❑ Password: ftpuser
Available from firmware version 5.25.16.1, the device implements a sFTP access for secure connections as follows:

❑ User: sftpuser
❑ Password: sftpuser
The passwords can be modified from the local display or from the software tool pacFactory.

The key modification meets the criteria defined by the IEEE1686 standard (available from firmware version 6.3.20.0):

 Minimum length of 8 characters.


 At least one character of each type: uppercase, lowercase, numeric and special (not alphanumeric).

In addition to some own criteria to provide additional security:

 It is not allowed to reuse the previous key: including modifying only uppercase / lowercase. It is required a minimum of 4
characters modified with respect to the previous string.
 Palindromes are not accepted.

These user profiles allows direct access to the following directorys and files:

Config directory:

❑ config/SYSTEM_LOG: Text files with system information.


❑ CIDupdates.log: Log of events of the CID files received.
❑ swupdates.log: Log of events of the firmware upddates.
❑ System.log: Los of system information events.
❑ Versions.log: Versions of the device.
❑ ftp.log: Log of events of the FTP access (available from firmware version 5.25.16.1)

❑ config/VALIDATION_TRACES: Text files with the received CIDs validation information.


❑ log_lib850.log: Log of events related with the IEC 61850 parser.
❑ validation_traces.log: Los of events of general parser.
LD directory:

❑ LD/PROT/COMTRADE: Oscilografy files in Comtrade format.


❑ LD/PROT/FAULT_RECORDS: Fault report files.
❑ LD/PROT/FAULT_SETTINGS: Settings files associated with fault reports.
SCL directory:

❑ SCL/NotValidated: Directory to copy the new CID file to configure the device.
❑ SCL/Validated: Directory with the active CID configuracion file (read only).

The user for ftp firmware update is as follows:

❑ User: ftpUpdat

Ingeteam Power Technology S.A.


User Manual 338
FTP ACCESS 

❑ Password: ftpUpdat

With this user you can access the directory "downloads" where a valid firmware file should be copied. Once the file is copied the update
will start automatically.

It is very important that during the process of updating firmware the device is not turned off since in that case the device could become
unusable.

After the update the device will restart automatically and the result of the update can be consulted either in the device versions screen or
in the latest updates screen (consult display section).

14.1 ACCESS CONTROL

Available from firmware version 5.25.16.1: The device incorporates a management of failed accesses which after 5 consecutive
attempts to establish a connection using a wrong password, the access to that user is blocked for 10 minutes. From this moment, any
failed attempt blocks the user 10 more minutes. While a user is blocked the correct password is also not accepted to access.

The goal is to harden the system to avoid "brute-force attacks" to recover a key by trying all possible combinations until finding the one
that gains access.

There is a signal on GEN/LLN0 indicating the activation of this block for some user.

 AccAlm: Access alarm. Active when access control is blocking a user.

In addition, all FTP accesses are registered in a log file located in /config/SYSTEM_LOG folder called ftp.log.

In this file, the accesses of any FTP client are recorded, indicating the source IP address and the date and time. Any uploads or
downloads of files are also recorded.

Ingeteam Power Technology S.A.


User Manual 339
MAPPING THE UNIT’S SIGNALS, MEASUREMENTS AND METERS

15. MAPPING THE UNIT’S SIGNALS, MEASUREMENTS AND METERS


The binding of the IED internal data to the IEC 61850 data model is configured in the short address (sAddress) attribute.

The sAddr attribute allows the allocation of a short address to DO attributes. According to the IEC 61850 standard short addresses can be
used as IED internal identification for the attribute. In this scope the format of the content is private to the IED and any tool that process
the ICD/CID file shall preserve imported contents in exported SCL files.

All the signals (trips, logics, hw check, digital inputs-outputs, etc.), measurements and meters that are generated in the unit are identified
by a number that appears in the sAddress of each of these elements.

In the factory ICD configuration file, all the internal data is preconfigured, and the user cannot modified them apart from the description
texts.

For new data created at engineering phase, as control logics output data, the software configuration tool allows the creation of sAddress
values.

15.1 SIGNALS

The distribution of the unit’s signals is effected using four numbers as a base: 0, 8192, 16384, 24576. All the unit’s signals are divided
into four types, taking these four digits as references:

15.1.1 Type A signals


This type of signal refers to all those signals with sAddress identification numbers between digits 0 and 8191.

These signals include digital inputs and Goose signals.

❑ Digital Inputs
 Identification number between 0 and 287.
Example: sAddr="S,0,5,0;TX1:GGIO1.Digital input 6,TX2:GGIO1.Digital Input 6,AC:1.2,ED:1.1,AD:0.0"
In the example, we can see the identification number of digital input number six from the first card in the ICD
sAddress.
 GEN/GGIO node
❑ Goose Signals
 In turn, the Goose signals are divided into RIO modules and LGOS nodes.
 RIO modules
 Identification number between 288 and 607.
Example: sAddr="GS,0,288,0;TX1:RIO1.St,TX2:RIO1.St,AC:1.2,ED:1.1,AD:0.0"
In the example, we can see the identification number of the first signal from the first RIO module in the ICD
sAddress.
 GEN/RIO node
❑ LGOS nodes
 Identification number between 608 and 1695.
Example: sAddr="GS,0,608,0;TX1:LGOS1.St,TX2:LGOS1.St,AC:1.2,ED:1.1,AD:0.1"
In the example, we can see the identification number of the first signal from the first LGOS node in the ICD
sAddress.
 GEN/LGOS node
Therefore, the distribution of these signals based on their identification number is as follows:

Ingeteam Power Technology S.A.


User Manual 340
MAPPING THE UNIT’S SIGNALS, MEASUREMENTS AND METERS

Table 193 Type A signal mapping

DIGITAL
INPUTS
(0 - 287)

GOOSE
SIGNALS
(288 - 1695)

The number of this type of signal reserved in the unit is 1696.

15.1.2 Type B signals


This type of signal refers to all those signals with sAddress identification numbers between digits 8192 and 16383.

This type of signal includes type B protection signals, fast protection logic signals and fast control logic signals.

❑ Type B protection signals


 Identification number between 8192 and 9215.
Example: sAddr="S,0,9091,0;TX1:TOC1 Phase trip,TX2:TOC1 Phase Trip,AC:1.2,ED:1.1,AD:0.0"
In the example, we can see the identification number of a type B protection signal in the ICD sAddress.
 Additional type B protection signals: Identification number between 9472 and 10399
 PROT node
❑ Fast protection logics
 Identification number between 9216 and 9343.
Example: sAddr="PS,0,9216,0;TX1:Protection logic 1,TX2:Protection logic 1,AC:1.2,ED:1.1,AD:0.0"
 In the example, we can see the identification number of the first protection logic in the ICD sAddress.
 GEN/pGGIO node
❑ Fast control logics
 Identification number between 9344 and 9471.
Example: sAddr="LS,0,9344,0;TX1:Fst logic 1,TX2:Fast logic 1,AC:1.2,ED:1.1,AD:0.0"
In the example, we can see the identification number of the first fast control logic in the ICD sAddress.
 CTRL/AutGGIO2 node

Therefore, the distribution of these signals based on their identification number is as follows:

Ingeteam Power Technology S.A.


User Manual 341
MAPPING THE UNIT’S SIGNALS, MEASUREMENTS AND METERS

Table 194.Type B signal mapping

PROTECTION SIGNALS
TYPE B
(8192 - 9215)

FAST PROTECTION LOGIC


SIGNALS

(9216 - 9343)

FAST CONTROL LOGIC


SIGNALS

(9344 - 9471)

ADDITIONAL
PROTECTION SIGNALS
TYPE B
(9472 -10399)

The number of this type of signal reserved in the unit is 2208.

15.1.3 Type C signals


This type of signal refers to all those signals with sAddress identification numbers between digits 16384 and 24575.

These signals include the type C protection signals.

❑ Type C protection signals


 Identification number between 16384 and 16831.
Example: sAddr="S,0,16384,0;TX1:Recloser in service,TX2:,AC:1.2,ED:1.1,AD:0.0"
In the example, we can see the identification number of the first type C protection signal in the ICD sAddress.
 PROT node
Therefore, the distribution of these signals based on their identification number is as follows:

Ingeteam Power Technology S.A.


User Manual 342
MAPPING THE UNIT’S SIGNALS, MEASUREMENTS AND METERS

Table 195.Type C signal mapping

TYPE C PROTECTION
SIGNALS
(16384 - 16831)

The number of this type of signal reserved in the unit is 448.

15.1.4 Type D signals


This type of signal refers to all those signals with sAddress identification numbers between digits 24576 and higher.

This type of signal includes the type D protection signals, the communication failure signals for all the bays that are connected to
the unit, the slow logic control signals, signals resulting from orders and Loc and LocSta signals (for more information about these
signals go to 1.2.1 Command blocks by command hierarchies, in IEC 61850 commands)

❑ Type D protection signals


 Identification number between 24576 and 24991.
Example: sAddr="S,0,24576,0;TX1:Relay in service,TX2:OnLine,AC:1.2,ED:1.1,AD:0.0"
In the example, we can see the identification number of the first type D protection signal in the ICD sAddress.
 Additional protection signals: Identification number between 27936 and 27967
 PROT node
❑ Communication failure control signals
 Identification number between 24992 and 25119.
❑ Slow control logics
 Identification number between 25120 and 26399.
Example: sAddr="LS,0,25120,0;TX1:Slow logic 1,TX2:Slow logic 1,AC:1.2,ED:1.1,AD:0.0"
In the example, we can see the identification number of the first slow control logic in the ICD sAddress.
 CTRL/AutGGIO1 node
❑ Signals resulting from orders
 Identification number between 26400 and 27423.
 Example: sAddr=" RS,0,26908,4;TX1:CSWI4 opClsOr,TX2:,AC:3.7.8.4,ED:1.1.1.1,AD:0.0.0.0"
❑ Loc signals
 Identification number between 27424 and 27679.
 Example: sAddr=" S,0,27424,0;TX1:GEN.LLN0.Loc,TX2:GEN.LLN0.Loc,AC:1.2,ED:0.0,AD:0.0"
❑ LocSta signals
 Identification number between 27680 and 27935.
 Example: sAddr="S,0,27680,0;TX1:GEN.RIOGGIO1.LocSta,TX2:GEN.RIOGGIO1.LocSta,AC:1.2,ED:0.0,AD:0.0"
Therefore, the distribution of these signals based on their identification number is as follows:

Ingeteam Power Technology S.A.


User Manual 343
MAPPING THE UNIT’S SIGNALS, MEASUREMENTS AND METERS

Table 196 Type D signal mapping

TYPE D PROTECTION SIGNALS


(24576 - 24991)

CONTROL SIGNALS (COM FAILURE)


(24992 - 25119)

SLOW LOGIC CONTROL SIGNALS


(25120 - 26399)

SIGNALS RESULTING FROM


ORDERS
(26400 - 27423)

LOC SIGNALS
(27424 - 27679)

LOCSTA SIGNALS
(27680 – 27935)

ADDITIONAL
PROTECTION SIGNALS
(27936 - 27967)

The number of this type of signal reserved in the unit is 3392.

15.2 MEASUREMENTS

All the unit's measurements are divided into four types:

❑ Protection measurements.
 Identification number between 0 and 299.
Example: sAddr="M,0,124,1;TX1:I average,TX2: AVERAGE I"
In the example, we can see the identification number of a protection measurement in the ICD sAddress.
 Additional measurements: Identification number between 744 – 948 and 979 - 1266.
 PROT node
❑ Goose Measurements
 Identification number between 300 and 555.
Example: sAddr="GM,0,300,0"
In the example, we can see the identification number of the first Goose measurement in the ICD sAddress.
 GEN/LGOS node

Ingeteam Power Technology S.A.


User Manual 344
MAPPING THE UNIT’S SIGNALS, MEASUREMENTS AND METERS

❑ Measurements resulting from logics


 Identification number between 556 and 687.
Example: sAddr="LM,0,556,0;TX1:Logic measurement 1,TX2:Logic analog 1"
In the example, we can see the identification number of the first logic measurement in the ICD sAddress.
 CTRL/AutGGIO1 node
❑ Measurements resulting from analogical input boards
 Identification number between 688 and 743.
Example: sAddr="M,0,688,0;TX1:Measure 1,TX2:Measure 1"
In the example, we can see the identification number of the first measurement in the ICD sAddress.
 GEN/GGIO node
❑ RTD boards measurements
 Identification number between 949 and 978.
Example: sAddr="M,0,949,0;TX1:Temperatura 1,TX2:Temperature 1"
 GEN/RTD

Therefore, the distribution of these measurements based on their identification number is as follows:

Table 197 Measurement mapping

PROTECTION MEASUREMENTS
(0 - 299)

GOOSE MEASUREMENTS
(300 - 555)

MEASUREMENTS RESULTING FROM CONTROL LOGICS


(556 - 687)

MEASUREMENTS RESULTING FROM ANALOGICAL


INPUT BOARDS
(688 - 743)

ADDITIONAL
PROTECTION MEASUREMENTS
(744 - 948)

RTD BOARDS MEASUREMENTS


(949 - 978)

ADDITIONAL
PROTECTION MEASUREMENTS
(979 - 1266)
The number of measurements reserved in the unit is 1267.

Ingeteam Power Technology S.A.


User Manual 345
MAPPING THE UNIT’S SIGNALS, MEASUREMENTS AND METERS

15.3 COUNTERS

All the unit's counters are divided into two types:

❑ Protection counters
 Identification number between 0 and 31.
Example: sAddr="C,0,0;TX1:Active energy out,TX2:Active Energy Out"
In the example, we can see the identification number of the first protection counter in the ICD sAddress.
 Additional protection counters: Identification number between 150 and 192.
 GEN and PROT node
❑ Counters resulting from logics
 Identification number between 32 and 149.
Example: sAddr="LC,0,32;TX1:Logic counter 1,TX2:Logic counter 1"
In the example, we can see the identification number of the first logic counter in the ICD sAddress.
 CTRL/AutGGIO1 node
Therefore, the distribution of these counters based on their identification number is as follows:

Table 198 Counter mapping

PROTECTION COUNTERS
(0 - 31)

COUNTERS RESULTING FROM CONTROL LOGICS


(32 - 149)

ADDITIONAL
PROTECTION COUNTERS
(150 - 192)

The number of counters reserved in the unit is 193.

Ingeteam Power Technology S.A.


User Manual 346
LOGICS

16. LOGICS
This document explains the operating mode of the logics generation tool of logic devices.

The EF family’s logics are fragments of executable code generated by the user using a PC tool, both in text and graphic formats. These
logics can be defined in an IED’s data model (using iedFactory) or in a particular instance (using substationFactory or the pacFactory
settings tool).

There are two different types of logics: control logics and protection logics.

In this chapter the device logics are defined and an introduction to the configuration options is presented. For more details about the logics
configuration consult the user manual of the software configuration tool (pacFactory / energyFactorySuite).

16.1 CONTROL LOGICS

The logics can be used to customize the behaviour of an IED. For example, automatism can be added or calculations between different
magnitudes can be carried out.

The logics are run in two different tasks, each with different priorities: one for fast logics and one for slow logics.

The running time for the fast logics is 2 milliseconds. The running time for the slow logics is approximately 10 milliseconds, although
given that this is a lower priority task it may occasionally be affected by other higher priority tasks.

Each configured logic must be included in one of these two tasks, in accordance with the manner in which they are to be run – fast
logics or slow logics.

To edit a control logic from substationFactory, the user must select the corresponding IED and click on the editor icon. To edit the
control logic from pacFactory, click on the "Logics" option in the “Configuration” menu or in the side menu.

The logics are defined in program blocks called POU (program organization unit). Two of the languages defined in the IEC-61131-3
standard are offered for the creation of each POU: one textual (ST) and one graphic (FBD).

There are three types of POU, as defined in the IEC-61131-3 standard: PROGRAM, FUNCTION_BLOCK and FUNCTION. The programs are
the senior hierarchy POUs, with each one corresponding to a task to be run on the device. Each PROGRAM can refer to several
FUNCTION_BLOCK and FUNCTION. In turn, a FUNCTION_BLOCK can refer to one or more FUNCTION.

At the IED level, two PROGRAM corresponding to the two above tasks are automatically defined: one for the fast logics (FastLog) and
the other for the slow logics (SlowLog). These PROGRAM cannot be deleted nor can their names be modified. New PROGRAM cannot
be created at any level, either.

All the new signals, measurements and counters that are created in the data model must be assigned a number that appears in the
sAddress of each of these elements.

The range values are:

❑ Fast control logics signals: Value between 9344 and 9471.


❑ Slow control logics signals: Value between 25120 and 26399.
❑ Measurements: Value between 556 and 687.
❑ Counters: Value between 32 and 149.

Ingeteam Power Technology S.A.


User Manual 347
LOGICS

16.2 PROTECTION LOGICS

The various protection functions can be configured by means of settings associated to the unit’s internal signals, vg enablings or blocks.
The protection functions treat these signals as inputs, although they do not modify their value. In order to assign them a value, the
protection logics are used.

The protection logics have two main differences in relation to the control logics:

❑ The result of a protection logic is always a Boolean value, to be assigned in one of the protection function's settings.
❑ The protection logic editor has been simplified to facilitate the programming of this type of logic.
The number of available logics is defined by the unit’s data model.

Each logic signal has a value obtained from an associated logic. These logics are fragments of code created in one of the two possible
languages - ST (text) or FBD (graphic). The corresponding language must be selected when a logic corresponding to a signal is edited for
the first time.

Each protection logic is independent from the rest and need not be included in a POU in order to be run. When a protection logic is
saved in the editor, an attempt is made to compile the information. If no error is found, a call to the logic in question is automatically
generated so that the logic is run when a CID (configured IED description) message is sent to the device or sent from pacFactory.

The protection logics are run every 2 milliseconds, as are the fast control logics.

To edit a protection logic from substationFactory, the user must select the corresponding logic signal and click on the editor icon. This
icon has three statuses to indicate the status of the corresponding logic:

Icon Logic statuses:


No logic has been edited for this signal. The value of the signal will be 0 (false).
Logic edited and ready to be run.
Logic edited, but with errors. Logic will not be run.

The following image shows a detail of the expander with four signals with logic signals of different statuses:

Details of the expander with protection logic signals

To edit a protection logic from pacFactory, click on the "Protection Logics" option in the “Configuration” menu or in the side menu.

A screen with a list of the available protection logic signals, along with the logic’s status icon and an access button for each logic’s
editor, will be shown.

Ingeteam Power Technology S.A.


User Manual 348
LOGICS

Details of the protection logics list in pacFactory

16.3 DATABASE SIGNALS

All of the IED’s database signals, measurements, meters and commands can be accessed as readings from the logics (the data model’s
basic data with valid sAddress). There is a set of data within this database that can be modified from the control logics:

Signal type Description


Critical signals Digital signals that can be modified from the fast task (FastLog)
Non-critical signals Digital signals that can be modified from the slow task (SlowLog)
Measurements Floating point data that can be modified from both tasks
Meters Whole numbers that can modified from both tasks
Commands Commands can only be generated from the slow task (SlowLog)

Both the data’s value and its quality can be accessed. If data is modifiable from the logic, the same will apply to the value and the
quality.

The data that can be modified from the logic may be preset in the unit's data model or they can be configured in the engineering
phase.

Only the status of the signal to which the logic in question is associated can be modified from the protection logics.

16.4 OUTPUT DATA UPON POWER-UP

Output data can maintain its value after the device is powered off and on.

In the logics, user can define variables of type RETAIN, which have the property of remaining with the value that they had before the
power off of the device.

Ingeteam Power Technology S.A.


User Manual 349
LOGICS

The maximum size allowed for all the logics of each group (protection and control) is 96 bytes. This means that if the variables that we
define with this property are of type BOOL (that is, the type associated to the logical signals) we can define a maximum of 96 RETAIN
variables.

Example of using variables in the logics:

There are global variables belonging to the model that can be used in the logic. For example all the signals like Trips or Starts of
protection functions. In the protection logics, each logic has a variable associated with it that is the output of that logic. That output is
also visible as a signal and can be sent in reports or GOOSES, assign it to a digital output, etc.

Each logic can also have internal variables. Once inside the logic editor, click on the "Show interface editor" option to see and / or add
internal variables to the logic (select the VAR tab).

A new variable can be created in 2 ways:

1.- When a non-recognized text is written in the algorithm, an assistant appears asking if you want to add it as a variable.

2.- Writing directly in the cell (if in tabular mode), as shown in next figure.

An internal variable to the logic can be made permanent selecting the RETAIN option in the Retain column.

Ingeteam Power Technology S.A.


User Manual 350
LOGICS

The initial value is optional. If it is assigned, it is the value it takes the first time the logic is executed. In the case of the variables not
marked as Retain each time the device is started, the variable is restarted with that value. In the case of Retain variables, it is only
started when the logic has been created or changed. Of course, it is highly recommended to initialize the variables.

When a "Function Block" is used in a logic, it is also considered a variable. If one of the predefined "Function Block" in the editor's right-
hand tab is dragged into the editing window, such as a SR flip-flop (SetReset), an SR1 variable of type SR is added. By activating the
option "Show interface editor" we can see how it is in the list of variables (next figure). In this case, if we want to store the internal
states of this block, we must also select the corresponding RETAIN option.

In the case of the "Function Blocks" with RETAIN option, the size in bytes used depends on the number of internal variables of that
block. In the case of the SR they are 3 bytes.

The example (previous figure) is a simple logic in graphic language to demonstrate how to make permanent the internal state of a SR
flip-flop.

Ingeteam Power Technology S.A.


User Manual 351
IEC 61850 COMMANDS

17. IEC 61850 COMMANDS

17.1 RUNNING IEC 61850 COMMANDS

Commands can be issued for controllable elements (elements whose functional constraint is “CO”) that may
belong to different Data classes (detailed in IEC 61850-7-3). Control class model implemented by the IED are:

❑ Controllable single point (SPC)


❑ Controllable double point (DPC)
❑ Controllable enumerated status (ENC)

The device implements the following services defined by IEC 61850 standard:

❑ Select (Sel) / SelectWithValue (SelVal)


❑ Cancel
❑ Operate (Oper)
❑ CommandTermination (CmdTerm)

The structure required to operate the command has the following fields:

❑ CtlVal. Command value. The type will be different, in accordance with element’s the CDC (Common
Data Class).
❑ Origin. It includes information about the origin of the command, divided into two fields:
 orCat. Origin category. Indicates the type of origin that issues the command (local, substation,
remote command, etc.)
 orIdent. Octect string that allows the identification of the command origin.
❑ CtlNum. It is the sequence number of the command.
❑ T: The timestamp when the command was generated.
❑ Test: It defines whether the control service request is going to be used with test purposes or not.
❑ Check: Delimits the kind of checkup that must be performed to the command before running it.

Because the Ingepac EF device implements edition 2 of the IEC61850 standard but maintains compatibility with the existing
configurations of edition 1, the differences in the data used to track orders are explained below:

CONFIGURATIONS USING ED1:

In addition to informing of the changes in the status signals of the elements on which the commands are to be run,
the reports also provide information on the changes in the status of the two data associated with the command
process itself: OpOpnOr and OpClsOr.

These data have four possible statuses:

Table 199 OpOpnOr and OpClsOr statuses

Value Explanation enum


STANDBY Command in standby 0
IN PROGRESS Command in process 1
SUCCESSFUL Command run successfully 2
UNSUCCESSFUL Failure in running of command 3

For opening commands in general, OpClsOr remains in STANDBY, the sequence for OpOpnOr would be STANDBY -
IN PROGRESS - SUCCESSFUL / UNSUCCESSFUL – STANDBY. In the case of a closure command, OpOpnOr would
remain in standby and OpClsOr would continue the complete sequence. If the command’s CtlModel indicates that

Ingeteam Power Technology S.A.


User Manual 352
IEC 61850 COMMANDS

the command has normal security, no return information is available from the device and, therefore, the sequence
would be STANDBY - IN PROGRESS – STANDY.

CONFIGURACIONES USING ED2:

In the second edition of IEC61850 standard, three new data elements are defined in order to follow the command
process: opOk, OpRcvd and tOpOk. These new elements have a new functional constraint, “OR”.

OpRcvd is activated upon the reception of a command and deactivated about 10 milliseconds later.

OpOk is activated at the same time as the command pulse (the pulse that will afterwards be transmitted to a digital
output, for example) and tOpOk shows the timestamp when opOk was activated.

OpOk and OpRcvd may be set as RS signals, editing their sAddr in the CID using the configuration tool. In this way,
their values will be refreshed in the internal database and will be available for internal logics.

In addition to these elements, it is also possible to generate a series of indications, through signals from the
database, to provide complementary information on the return of the orders.

In the logical nodes where it is necessary to have this return information of the controls, the normative class has
been extended defining the following data objects with CDC = "ACT", which in turn includes the optional data
"originSrc".

❑ OpOpnPrg / OpClsPrg: Execution of opening and closing controls (order in progress).


❑ OpOpnFail / OpClsFail: Failure of opening and closing controls (command failure).

The configuration for the use of these return signals is done through the configuration tool, through the sAddr field
of the command itself. However, the return signals have an RS type sAddr.

In both configurations, upon completion of an order execution, part 7-2 of the IEC 61850 standard defines the possible
reasons for termination. The following table lists the AddCause values used by the device:

Ingeteam Power Technology S.A.


User Manual 353
IEC 61850 COMMANDS

Table 200 AddCause considered

Value Cause Explanation enum


Unknown Unknown cause Command not successful due to unknown causes 0
Not-Supported Not configured 1
Blocked-by-switching- Not successful since one of the downstream Loc switches like in CSWI has
Blocked by hierarchy 2
hierarchy the value TRUE
Select-failed Selection failure Cancelled due to an unsuccessful selection (select service) 3
Control action is aborted due to invalid switch position (Pos in XCBR or
Invalid-position Invalid position 4
XSWI) or the switch reaches an invalid position.
Position-reached Position reached Switch is already in the intended position (Pos in XCBR or XSWI) 5
Parameter-change-in- Parameter change in
Control action is blocked due to running parameter change 6
execution execution
Control action is blocked, because the LN (CSWI or XCBR/XSWI) is in a
Blocked-by-Mode 8
mode (Mod) which does not allow any switching
Blocked-by- Block signal Control action is blocked due to interlocking of switching devices (in CILO
10
interlocking activated attribute EnaOpn.stVal=“FALSE” or EnaCls.stVal=“FALSE”
Command-already-in- Command in Control service or cancel is rejected, because control action is already
12
execution execution running
Health signal Control action is blocked due to some internal event that prevents a
Blocked-by-health 13
activated successful operation (Health)
Control action is blocked, because another control action in a domain (for
1-of-n-control 1 of n block example, substation) is already running (in any XCBR or XSWI, the 14
DPC.stSeld=“TRUE”).
Abortion-by-cancel Command cancelled Control action is aborted due to cancel service 15
Time-limit-over Time exceeded Control action is terminated due to exceed of some time limit 16
Object not selected Object not selected Control action is rejected, since object is not selected 18
Object-already- Object already Select action is not executed, because the addressed object is already
19
selected selected selected
Abortion-by- Abortion by Control action is aborted due to the loss of connection with the client that
23
communication-loss communication loss issued the control
None Command accepted Control action successfully executed 25
Inconsistent- Inconsistent
The parameters between successive control services are not consistent 26
parameters parameters
Locked-by-other- Locked by other
Another client has already reserved the objet 27
client client

On the other hand, the operating mode of a specific command is defined by the ctlModel configuration parameter
associated with that command, according to the following table:
Table 201 Possible ctlModel

Value Explanation enum


The object is not controllable, only the services that apply to a status object are supported. The
status-only 0
attribute ctlVal does not exist.
direct-with-normal-
Direct control with normal security according to IEC 61850-7-2. 1
security
sbo-with-normal-security SBO control with normal security according to IEC 61850-7-2. 2
direct-with-enhanced-
Direct control with enhanced security according to IEC 61850-7-2. 3
security
sbo-with-enhanced-
SBO control with enhanced security according to IEC 61850-7-2. 4
security

Other configuration parameters that determine the progress of the command are:

❑ PulseConfig. This data structure defines the command’s output pulse type (pulse, duration, pulse
train). The command is not terminated until the last pulse ends.
❑ OperTimeOut. Maximum switching time, after which, failure occurs if the command has not been
successfully executed.
❑ sboTimeout. The time during which the command selection remains activated.

In the following sections, the operation process of a command depending on the ctlModel is described in detail.

Ingeteam Power Technology S.A.


User Manual 354
IEC 61850 COMMANDS

17.1.1 DIRECT_WITH_NORMAL_SECURITY (1)

If the command’s ctlModel is DIRECT_WITH_NORMAL_SECURITY (1), the process to follow will be as shown in
the following figure:
Figure 196 Direct command process with normal security

IEC 61850 Client IEC 61850 Server Process

Operate

Checkup for
operation
Origin, blocks…

Operate
Response

Upon receiving a request to run a command by an Operate Request, the device analyses the validity of the
request, checking the client’s authorization and any possible blocks, and responds positively or negatively by an
Operate Response to the client. If the response is positive, the command is sent to the device.

17.1.2 SBO_WITH_NORMAL_SECURITY (2)

If the command’s ctlModel is SBO_WITH_NORMAL_SECURITY (2), the process is similar, but including a
selection prior to execution:

Figure 197 Command process with select before operate and normal security

IEC 61850 Client IEC 61850 Server Process

Select
Checkup for
selection
Origin,
selection…
Select
Response

Operate Checkup for


operation
Origin, blocks…

Operate
Response

Ingeteam Power Technology S.A.


User Manual 355
IEC 61850 COMMANDS

In this case, after receiving a selection request the selection's permission is checked and, when applicable, a
positive response is sent. At that moment a timer starts. This timer will cancel the selection after the sboTimeOut
timeout ends. If an operate request is received before the conclusion of the timeout, the same process as
described for the direct commands with normal security is followed.

If the selection is not accepted, the response will be negative and the process is concluded.

17.1.3 DIRECT_WITH_ENHANCED_SECURITY (3)


When the command’s ctlModel is DIRECT_WITH_ENHANCED_SECURITY (3), the process starts exactly as the
direct commands with normal security, as shown in the diagram below:

Figure 198 Direct command process with enhanced security

IEC 61850 Client IEC 61850 Server Process

Operate

Checkup for
operation
Origin, blocks…
Operate
Response

Command
Termination

After sending the operate request to the device, the return information of the element on which the command is
executed is expected, so that the device can inform the client throught a Command Termination if the operation
has been successfully executed.

If the device’s return information is received before the conclusion of the operTimeout (the maximum execution
time) and the position requested has been reached, the IED then sends to the client a positive Command
Termination.

If the operTimeout time is exceeded without having received the information from the device, or if it is received but
the position requested has not been reached, the Command Termination will be negative. In this case, the cause
of the failure of the command will be included in the AddCause field.

17.1.4 SBO_WITH_ENHANCED_SECURITY (4)

The ctlModel SBO_WITH_ENHANCED_SECURITY (4) includes, in addition to the enhanced security process of
the commands modelled as DIRECT_WITH_ENHANCED_SECURITY, the SelectWithValue service in order to
select the command before operate. In this way, it is verified that the value sent in the selection process is the
same as the one sent during the execution. The scheme to be followed is:

Ingeteam Power Technology S.A.


User Manual 356
IEC 61850 COMMANDS

Figure 199 Command process with select before operate and enhanced security

IEC 61850 Client 61850 Server Process


Select
Checkup for
selection
Origin,
Select selection…
Response

Operate
Checkup for
operation
Operate Origin, blocks…
Response

Command
Terminationn

Similarly to direct orders with enhanced security, if the order fails, the cause of the failure is reported in the
AddCause field.

Ingeteam Power Technology S.A.


User Manual 357
IEC 61850 COMMANDS

17.2 COMMAND BLOCKS

The commands sent to the device can be blocked for different reasons in which the execution cannot be allowed.
In part 7-2, of the IEC 61850 standard, the possible reasons for failure of a command are detailed.

The following subsections describe the different blocks implemented by the device.

IMPORTANT NOTE: The order of these sections matches exactly with the order of blocking verification
that the IED follows. So once a block is applied, the command will not prosper and next blocks will not be
checked.

17.2.1 Command blocks by inconsistent parameters


The parameters of the command are checked to ensure that there have been no changes to them.
This block only affects commands with ctlModel SBO_WITH_ENHANCED_SECURITY (4) that are performed
through the SelectWithValue service.

The reason for command failure when this block is generated is "inconsistent parameters" (AddCause = 26).

17.2.2 Command blocks by switching hierarchy


The next possible cause of locking a command is switching hierarchy blocking (AddCause = 2). The IED
implements a hierarchy of commands that implies the blocking of the orders according to their origin and the
configuration of the device.

In the standard IEC 61850, part 7-3, it is defined the possible origins of a command that are affected by
blockages due to the switching hierarchy.

 "not-supported": Only accepted in the mode that the order hierarchy is not handled.
 "remote-control": corresponds to a remote origin.
 "station-control" or "maintenance": corresponds to a console.
 "bay-control": corresponds to a console at bay / local level or to the display.
 "automatic-bay", "automatic-static" or "automatic-remote". By default, orders sent by
IEC61850 with these origins are allowed, except for the modes that strictly check the local
origin of the order (LRMode, Edition 2 and Exclusive Edition 2).
Under the section "Command blocks by interlocking" it is explained the particular operation
for these origins in H automation architectures.
 "process": Commands with this origin are not accepted in any case. The process source is
reserved for changes in the state of control elements that do not come from commands. If
there is a change in a signal associated with a command but the change of state has not
been a consequence of an order, but a spontaneous change, the order orCat will be written
to "PROCESS".

The "Remote/Local Type" setting determines how the device will behave at the moment of blocking the
commands by hierarchy. It is found in the data model as "GEN/LLN0.LRmode" or in the display under
"General configuration: Remote / Local Type". The following values are available:

Table 202. Available values for LRMode

LRmode Numeric Value


Not treated 0
Iberdrola 1
Exclusive 2
No HMI 3
ExclusiveBR 4
Edition2 5
ExclusiveEd2 6

Ingeteam Power Technology S.A.


User Manual 358
IEC 61850 COMMANDS

CONFIGURATIONS USING ED1:


Depending on the mode selected, it can be taken into account the status of the signals GEN/LLN0.RemCtlBlk
(remote control signal status) and GEN/LLN0.Lockey (HMI signal status).

To interpret the tables in the next sections with edition 1 configurations, it is necessary to consider the first columns
according to the following relation:

❑ Loc = RemCtlBlk
❑ LocSta = Lockey

In any case, for these configurations, as the data model specific to ICD Ed2 is required, any LRMode associated with
Edition 2 is not available.

CONFIGURATIONS USING ED2:


Depending on the mode selected, the MltLev setting of the LLN0 of the logical device GEN can be taken into
account, as well as the status of the Loc and LocSta signals.

MltLev is a boolean setting that can be found in the data model in "GEN/LLN0.MltLev", and indicates if more than
one level (Originator) has the switching authority. This setting only applies to Edition2 and ExclusiveEd2 modes.

Loc is a boolean status signal ("GEN/LLN0.Loc.stVal"). It shows the local status, which is unique for the device, so all
the Loc signals show always the same status (the standard defines this signal in several nodes with configured
commands). To be able to modify this state, we have two options:

 Sending a command on the RemCtlBlk ("GEN/LLN0.RemCltBlk") element. This way, every Loc signal
will be set to the same value as "GEN/LLN0.RemCltBlk.stVal".
 Configuring the LogInLR setting ("GEN/LLN0.LogInLR") to a valid signal reference, so that this signal
status stablishes the value of every Loc. It is important to note that this setting predominates over
sending the command to the RemCtlBlk element explained in the previous point. Therefore, when
this setting is configured the command over the RemCtlBlk element is not allowed.

LocSta is a boolean status signal ("GEN/LLN0.LocSta.stVal"). Its status shows if station or remote origins are
accepted, and as in the case of Loc, it is unique for the device although it may exist in several logical nodes. To
modify the status of LocSta, a command on the controllable LocSta element "GEN/LLN0.LocSta" can be issued. Every
LocSta element in the device will show the same status value.

The operating characteristics of each of the LRmode values are detailed in the following points:

❑ LRMode: Not treated

No switching hierarchy blocking on commands is applied. It is the only mode that allows commands
from the "not-supported" origin.

❑ LRMode: Iberdrola

The status of Loc and LocSta signals is taken into account. The following tables show for each
combination whether the order is blocked or allowed, depending on the origin of the order.

Table 203. Command blocks by switching hierarchy on mode "Iberdrola"

Loc LocSta Bay Station Remote


(1) (1) allowed blocked blocked
(1) (0) allowed allowed blocked
(0) (1) blocked blocked allowed
(0) (0) blocked blocked allowed

Ingeteam Power Technology S.A.


User Manual 359
IEC 61850 COMMANDS

Table 204. Command blocks by switching hierarchy for RemCtlBlk on mode "Iberdrola"

Loc LocSta Bay Station Remote


(1) (1) allowed blocked blocked
(1) (0) allowed allowed blocked
(0) (1) allowed blocked blocked
(0) (0) allowed allowed blocked

Table 205. Command blocks by switching hierarchy for LocSta on mode "Iberdrola"

Loc LocSta Bay Station Remote


(1) (1) allowed blocked blocked
(1) (0) allowed blocked blocked
(0) (1) blocked blocked blocked
(0) (0) blocked blocked blocked

❑ LRMode: Exclusive

This mode of operation implies that when activating the status of the RemCtlBlk (associated with Loc),
the activation of the value of the LocSta signal is automatically generated. Deactivation is independent.

The status of Loc and LocSta signals is taken into account in this mode.

Because the activation of the RemCtlBlk signal triggers the activation of the LocSta, in the "Exclusive"
LRMode, it is not possible to reach the Loc = 1 and LocSta = 0 state from the table’s origins. It is only
possible to reach this value after a LRMode change or using "automatic" origin, however, the behavior
is exactly the same as for Loc = 1 and LocSta = 1.

Table 206. Command blocks by switching hierarchy on mode "Exclusive"

Loc LocSta Bay Station Remote


(1) (1) allowed blocked blocked
(1) (0) allowed blocked blocked
(0) (1) blocked blocked allowed
(0) (0) blocked allowed blocked

Table 207. Command blocks by switching hierarchy for RemCtlBlk on mode "Exclusive"

Loc LocSta Bay Station Remote


(1) (1) allowed blocked blocked
(1) (0) allowed blocked blocked
(0) (1) allowed blocked blocked
(0) (0) allowed blocked blocked

Table 208. Command blocks by switching hierarchy for LocSta on mode "Exclusive"

Loc LocSta Bay Station Remote


(1) (1) blocked blocked blocked
(1) (0) blocked blocked blocked
(0) (1) blocked allowed blocked
(0) (0) blocked allowed blocked

❑ LRMode: No HMI

Ingeteam Power Technology S.A.


User Manual 360
IEC 61850 COMMANDS

Only the status of the Loc signal is taken into account. The following table shows for each combination
whether the command is blocked or allowed, depending on the origin.

Table 209. Command blocks by switching hierarchy on mode "No HMI"

Loc Bay Station Remote


(1) allowed blocked blocked
(0) blocked allowed allowed

Table 210. Command blocks by switching hierarchy for RemCtlBlk on mode "No HMI"

Loc Bay Station Remote


(1) allowed blocked blocked
(0) allowed blocked blocked

* The LocSta table has not been included because is not used in this mode. The command blocks
applied will be those of RemCtlBlk.

❑ LRMode: ExclusiveBR

This is a particular case of the "Exclusive" LRMode mode. This LRMode differs in that the LocSta
variable is not activated automatically when the RemCtlBlk is activated and it is possible to modify the
LocSta if the equipment is in local mode (Loc = 1) from the same origin (bay-control).

The following tables show for each combination whether the order is blocked or allowed, depending on
the origin of the order.

Table 211. Command blocks by switching hierarchy on mode "ExclusiveBR"

Loc LocSta Bay Station Remote


(1) (1) allowed blocked blocked
(1) (0) allowed blocked blocked
(0) (1) blocked blocked allowed
(0) (0) blocked allowed blocked

Table 212. Command blocks by switching hierarchy for RemCtlBlk on mode "ExclusiveBR"

Loc LocSta Bay Station Remote


(1) (1) allowed blocked blocked
(1) (0) allowed blocked blocked
(0) (1) allowed blocked blocked
(0) (0) allowed blocked blocked

Table 213. Command blocks by switching hierarchy for LocSta on mode "ExclusiveBR"

Loc LocSta Bay Station Remote


(1) (1) allowed blocked blocked
(1) (0) allowed blocked blocked
(0) (1) blocked allowed blocked
(0) (0) blocked allowed blocked

❑ LRMode: Edition2

Only for Edition 2 configurations. If LRMode is "Edition2", the normative hierarchies of commands
described in Part 7-4 of Edition 2 of IEC61850 standard (Annex B) apply.

Ingeteam Power Technology S.A.


User Manual 361
IEC 61850 COMMANDS

This implies that the local origin of the command is considered strictly, so that if Loc = 1, no command
(nor selection) from IEC61850 communications is accepted regardless of what is indicated in the origin
field (even if it is a bay-level console and commands with 'bay-control' origin). Therefore, when the
equipment is in local mode (Loc = 1) only commands sent from display or logic are accepted.

In this mode, the MltLev setting of the LLN0 of the logical device GEN, as well as the status of Loc and
LocSta signals, is used to determine if a command is required to be blocked by switching hierarchy.

The following table shows for each combination whether the command is blocked or allowed,
depending on the origin. This table affects all orders, including RemCtlBlk and LocSta.

Table 214. Command blocks by switching hierarchy on mode "Edition2"

MltLev Loc LocSta Bay Station Remote


(0) (1) (1) allowed* blocked blocked
(0) (1) (0) allowed* blocked blocked
(0) (0) (1) blocked allowed blocked
(0) (0) (0) blocked blocked allowed

(1) (1) (1) allowed blocked blocked


(1) (1) (0) allowed blocked blocked
(1) (0) (1) allowed allowed blocked
(1) (0) (0) allowed allowed allowed

* The local origin is checked strictly: Only display or logics.

❑ LRMode: ExclusiveEd2

Only for Edition 2 configurations. If the LRMode is set to "ExclusiveEd2", the command switching
hierarchy blocks are the same as in the "Edition2" case, except for the commands over the LocSta and
RemCtlBlk.

When operating a command on these two elements, the verification of the local origin is not strict, that
is, commands received from IEC61850 communications with origin 'bay-control' or 'automatic' sources
are allowed.

The following tables show the behavior of the switching hierarchy blocks on these two orders:

Table 215. Command blocks by switching hierarchy for RemCtlBlk on mode "ExclusiveEd2"

Loc LocSta Bay Station Remote


(1) (1) allowed blocked blocked
(1) (0) allowed blocked blocked
(0) (1) allowed blocked blocked
(0) (0) allowed blocked blocked
NOTE: MtlLev is not included as it does not modify the table.

Table 216. Command blocks by switching hierarchy for LocSta on mode "ExclusiveEd2"

MltLev Loc LocSta Bay Station Remote


(0) (1) (1) blocked blocked blocked
(0) (1) (0) blocked blocked blocked
(0) (0) (1) blocked allowed blocked
(0) (0) (0) blocked allowed blocked

(1) (1) (1) blocked blocked blocked


(1) (1) (0) blocked blocked blocked
(1) (0) (1) allowed allowed blocked
(1) (0) (0) allowed allowed blocked

For all other commands, the local origin check remains strict, as detailed in the LRMode "Edition2"
mode.
Ingeteam Power Technology S.A.
User Manual 362
IEC 61850 COMMANDS

17.2.2.1 Exceptions to switching hierarchy blocks


Any order sent from the logics or from the pacFactory tool is not affected by switching hierarchy blocks.

In protection commands, hierarchy locks are the same as those in control commands, with the exception
of the following commands, that are never blocked by switching hierarchy.

 Reset commands for statistical data


 Reset commands for maximeter and minimeters
 Reset commands for energy counters
 Reset commands for queues
 Reset commands for LEDs and relays
 Battery connection/disconnection commands

In the LLN0 node of the logical device GEN the FKeysRem setting is defined. When is set to '1', it allows any
order given from the device’s display without any hierarchical blocking.

Additionally, with the configuration tool it is possible to set (in the sAddress), for each command of type SPC
and DPC, if the switching hierarchy blocks shall be avoided. It can be choosen whether this affects the
opening command, the closing command, or both.

17.2.3 Command 1 of n blocks


It ensures that multiple orders are not executed simultaneously. If a second command is received before the first
command is completed, the error is indicated as "1 of n" block (AddCause = 14).

17.2.4 Command blocks by mode (Mod/Beh)


This block is performed depending on whether the test bit of the received command is activated or not, and based on the
Beh status of the logic node. It has to be taken into account that the mode block is not checked in the case of making
commands over the Mod element. In case of blocking, the order is rejected with "blocked by mode" reason (AddCause =
8).
Table 217. Blocks by mode (Mod/Beh)

Command Test Bit Beh=On(1) Beh=Test(3) Beh=Off(5)


0 Allowed BLOCKED_BY_MODE BLOCKED_BY_MODE
1 BLOCKED_BY_MODE Allowed BLOCKED_BY_MODE

The IED contemplates 3 possible Beh / Mod values: 1: ON / 3: TEST / 5: OFF.

When the Beh is Off this block also applies to the selection of the command. As the test bit is not sent in the selection
request, it can not be checked in the other cases. The value Off is only defined in those logical nodes that it makes sense
to disable the node (for example protection functions).

Only with Edition2 configurations, to determine the Beh status of the logical node on which the command is executed,
different levels of hierarchy are defined:

❑ Mod of the own logical node.


❑ Mod of the LLN0 of the logical device to which the logical node belongs.
❑ Mod of the LLN0 of the logical device defined in the GrRef.

The GrRef setting is defined in the Edition2 of the standard and allows to relate a logical device to depend on a higher
hierarchy logical device. Its data type is objRef and it is found in the LLN0. The format to be used is the own logical
device concatenated to the IEDname of the installation.

The following table details the calculation of Beh of a logical node according to the different levels of hierarchy. The
GrRef can have an empty value and therefore considered unconfigured (NC):

Ingeteam Power Technology S.A.


User Manual 363
IEC 61850 COMMANDS

Table 218. Calculation of Beh according to hierarchy

GrRef LD LDMode LNMode LNBeh



LLN0.Mod LLN0.Mod LN.Mod LN.Beh
On / NC On On ➔ On
On / NC On Test ➔ Test
On / NC On Off ➔ Off
On / NC Test On ➔ Test
On / NC Test Test ➔ Test
On / NC Test Off ➔ Off
Test On On ➔ Test
Test On Test ➔ Test
Test On Off ➔ Off
Test Test On ➔ Test
Test Test Test ➔ Test
Test Test Off ➔ Off

NOTE: Mod / Beh to Off is not accepted in LLN0 nodes.

17.2.5 Command blocks by Heatlh


The possibility of blocking commands based on a selectable alarm signal via the configuration tool (in a sAddress field) is
available. If this alarm signal is activated, the command will be blocked by "Blocked by Health" reason (AddCause = 13).
It is possible to set a different configuration for each command.

17.2.6 Command blocks by Interlocking


In IEC61850 Edition 2 configurations, the blocks by interlocking (EnaOpn/EnaCls) are only checked if the command is
issued with the “interlock-check” bit activated. If not, the command will not be checked against this blocking conditions.

On the other hand, in edition 1 configurations or other protocols different than IEC61850, the block by interlocking is
always checked.

The standard defines that the signals of the CILO logical nodes shall be used, but using the configuration tool it is
allowed to select these or any other signal in a generic way to perform the interlocking block. Signals can be set for both
the opening and closing blocks. The reason for the failure associated with this type of block is the "blocked by
Interlocking" (AddCause = 10).

In addition, within interlocking blocks, there is a check for installations in H automation architectures. This configuration is
performed using the configuration tool (automation signal sAddress field). When this signal is configured, the following
logic is followed:

❑ Automation signal activated:


 Only commands whose origin is "automatic" are accepted.
❑ Automation signal deactivated:
 Commands whose origin is "automatic" will be blocked.

For this section it is important to take into account the order followed to check the blocks, so that for example, with
LRMode configured to Edition2, and with the IED in local mode, automatic orders will be blocked by switching hierarchy
before reaching this kind of block.

17.2.7 Commands blocks due to invalid/reached position


The IED allows configuring blocks on commands based on the status of the item on which the order is intended and
taking into account whether an opening or closing is sent.

Ingeteam Power Technology S.A.


User Manual 364
IEC 61850 COMMANDS

These blocks are configured through the configuration tool (in a sAddress field) indicating the desired operating mode for
each command.

The commands will be blocked in accordance with the following table:


Table 219 Blocks in accordance with the command mode

Estado invalido /
Open status Close status
desconocido
Open Close Open Close Open Close
Command Mode 0 / -1 ALLOWED ALLOWED ALLOWED ALLOWED ALLOWED ALLOWED
Command Mode 1 BLOCK (1) ALLOWED ALLOWED BLOCK (1) BLOCK (2) BLOCK (2)
Command Mode 2 BLOCK (1) ALLOWED ALLOWED BLOCK (1) ALLOWED BLOCK (2)
Command Mode 3 ALLOWED ALLOWED ALLOWED BLOCK (1) ALLOWED BLOCK (2)

Thus, the blocks marked with (1) are blocks by "position reached" (AddCause = 5) and those marked with (2) are by
"invalid position" (AddCause = 4).

17.3 COMMANDS FOR OTHER POSITIONS

The configuration of these commands is related to the protocol by which they are propagated.

When the command is configured as a command of another device or UCL, the order will be sent to the corresponding
device behaving as a direct order with normal security (ctlModel = 1). The check of return information, pulseConfig, timeouts
and blocks must be performed on the device to which the order belongs.

17.4 COMMAND SADDRESS

Through the sAddress fields of each command the behavior explained in some of the previous sections can be modified.
The method for modifying the sAddress fields must always be the configuration tool. Manually changing these values can
cause errors and malfunction of the associated command.

Indicatively, the sAddress of a command has the following format:

sAddr = " a,b,c,d,e,f,g,h,i,j,k,l,m,n,o,p,q,r,s;TX1:Language 1 text,TX2: Language 2 text "

❑ a:= O (letter corresponding to the command) / LO (Letters corresponding to the command logics)
❑ b:= Command UCL number. Maximum 4 characters.
Value 0 is used to select internal Ucl.

❑ c:= Command number. Maximum 4 characters.


Number of the first associated internal command. Each control element has two internal commands associated.
The first corresponds to the “ON” command (ctlVal = 1) and the second to the “OFF” command (ctlVal = 0). The
sAddress value has to be configured always as the number of the first command, which corresponds to the “ON”.

❑ d:= Enabling off/aperture signal number (EnaOpn). Maximum 5 characters.


Only if configured: It is the number of the signal that allows or blocks the OFF/aperture command, in case of it is
activated or deactivated respectively.

❑ e:= Enabling on/close signal number (EnaCls). Maximum 5 characters.


Only if configured: It is the number of the signal that allows or blocks the ON/close command, in case of it is
activated or deactivated respectively.

❑ f:= Expected status inverted. (1 character)


When set to 1 indicates that the expected status of the signal associated with the command is inverted.

Ingeteam Power Technology S.A.


User Manual 365
IEC 61850 COMMANDS

❑ g:= Health signal number. Maximum 5 characters.


Only if configured: It is the number of the alarm signal that is used to block the order. If the alarm signal is not
active, the remaining locks are checked.

❑ h:= Command Mode. It accepts four possible values (0-3)


Depending on this field, the commands will be blocked for "invalid position" or "position reached". The absence of
this field or a -1 value, assumes the same operation as that corresponds to a 0 value.

The table with the explanation of each mode can be found in the corresponding blocks section.

❑ i:= H automation signal number. Maximum 5 characters.


Only if configured: If it is a valid signal number, the status of the signal is checked to know if the equipment is in
automatic or not:

 If signal value is '1', H automation is activated, so command requests over this element from any
origin that is not “automatic” will be blocked
 If signal value is '0', H automation is not activated, so command requests over this element from any
“automatic” origin will be blocked
❑ j:= UCL number of the enabling off/aperture signal (field d). Maximum 4 characters.
The value 0 is used to refer to internal ucl. If it is empty the ucl number of the command is used.

❑ k:= UCL number of the enabling on/close signal (field e). Maximum 4 characters.
The value 0 is used to refer to internal ucl. If it is empty the ucl number of the command is used.

❑ l:= UCL number of the H automation signal (field i). Maximum 4 characters.
The value 0 is used to refer to internal ucl. If it is empty the ucl number of the command is used.

❑ m:= Disable block by switching hierarchy (ON/close). 1 character.


Setting this field to value 1 disables blocks per switching hierarchy for the ON command.

❑ n:= Disable block by switching hierarchy (OFF/aperture). 1 character.


Setting this field to value 1 disables blocks per switching hierarchy for the OFF command.

❑ o:= UCL number of the H automation signal (field i). Maximum 4 characters.
The value 0 is used to refer to internal ucl. If it is empty the ucl number of the command is used.

❑ p: RS signal associated with return of command (only Ed2): opOpnPrg. Maximum 5 characters.
❑ q: RS signal associated with return of command (only Ed2): opClsPrg. Maximum 5 characters.
❑ r: RS signal associated with return of command (only Ed2): opOpnFail. Maximum 5 characters.
❑ s: RS signal associated with return of command (only Ed2): opClsFail. Maximum 5 characters.
The UCL associated to the four return signals of commands Ed2 is the UCL of the command itself.
❑ TX1:= Command text language1. Maximum 16 characters.
❑ TX2:= Command text language2. Maximum 16 characters.

Ingeteam Power Technology S.A.


User Manual 366
RIO MODULES

18. RIO MODULES

18.1 CONFIGURATION

The RIO modules are configured using the RIOGGIO logic nodes A maximum of 8 nodes of this type is contemplated.

Each node has series of attributes that allow us to select the RIO modules with which we are to communicate and to configure the
outputs to be published:

Table 220 RIO module configuration attributes in Edition 1

ATTRIBUTE DESCRIPTION
The RIO number to which we want to associate the current node. It is a configurable value
NumRIO.setVal
between 0 and 99.

The RIO module to which we want to associate. It can accept the 1 (12 inputs / 4 outputs) or 2
TypeRIO.setVal
(8 inputs / 2 outputs). The value 0 is reserved to indicate that the node is not configured.

InRef1.setRef IEC 61850 reference to the RIO module’s first output.

InRef2.setRef IEC 61850 reference to the RIO module’s second output.

InRef3.setRef IEC 61850 reference to the RIO module’s third output.

InRef4.setRef IEC 61850 reference to the RIO module’s fourth output.

Table 221 RIO module configuration attributes in Edition 2

ATTRIBUTE DESCRIPTION
The RIO number to which we want to associate the current node. It is a configurable value
NumRIO.setVal
between 0 and 99.

The RIO module to which we want to associate. It can accept the 1 (12 inputs / 4 outputs) or 2
TypeRIO.setVal
(8 inputs / 2 outputs). The value 0 is reserved to indicate that the node is not configured.

InRef1.setSrcRef IEC 61850 reference to the RIO module’s first output.

InRef2.setSrcRef IEC 61850 reference to the RIO module’s second output.

InRef3.setSrcRef IEC 61850 reference to the RIO module’s third output.

InRef4.setSrcRef IEC 61850 reference to the RIO module’s fourth output.

18.2 OPERATION

When we have configured a RIOGGIO logical node correctly, the expected performance in the different attributes is as follows:

Ingeteam Power Technology S.A.


User Manual 367
RIO MODULES

Table 222 Operation of RIO module attributes

ATTRIBUTE DESCRIPTION
Status of the communication with the associated RIO module. The value 1 indicates that it is
St.stVal
correct.

Indicates that the configured RIO type does not match that which is being received. This value
CfgErr.stVal
is only displayed in IEC 61850, it has no associated signal in the internal data base.

Ind[1..17].stVal The values received from the RIO module.

The values sent to the RIO module. The value always coincides with the signals configured in
SPSCO[1..4].stVal
the InRefs in the same index.

Both the elements received and the communication status has associated signals with fixed position in the internal database. The
signals are distributed as follows:

Table 223 Internal signals associated with RIO modules

LOGICAL NODE ELEMENT ASSOCIATED INTERNAL SIGNALS

Communication status 288


RIOGGIO1
Values received in command From 289 to 305.

Communication status 306


RIOGGIO2
Values received in command From 307 to 323.

Communication status 324


RIOGGIO3
Values received in command From 325 to 341.

Communication status 342


RIOGGIO4
Values received in command From 343 to 359.

Communication status 360


RIOGGIO5
Values received in command From 361 to 377.

Communication status 378


RIOGGIO6
Values received in command From 379 to 395.

Communication status 396


RIOGGIO7
Values received in command From 397 to 413.

Communication status 414


RIOGGIO8
Values received in command From 415 to 431.

Ingeteam Power Technology S.A.


User Manual 368
CHANGES REQUIRING THE REBOOTING OF THE DEVICE

19. CHANGES REQUIRING THE REBOOTING OF THE DEVICE


The modification of the value of certain attributes requires the resetting of the device in order for the modification to have effect. In order
to inform of the need to manually reset of the device, the ResetDev.stVal signal has been defined within the GEN node’s LLN0. In some
cases, it is enough to send a new ICD / CID file.

For standard IEC61850 Ed1 configurations only, after a change on LGOS logical node subscription settings, the server does not require a
reset only if the LGOS was completely configured when the server started. In other case, the change of any of the settings will activate the
reset required signal.

The following table details the possible causes to activate this signal:

Table 224 Setting changes that require the manual reset of the device

LOGICAL NODE ATTRIBUTE DESCRIPTION DEACTIVATION WITH ICD FILE


The multicast reception MAC associated to
MAC.setVal YES
the goose

GoCBRef.setRef Goose control block reference YES

LGOS – Applies only on


IEC61850 Ed1 GoDatSetRef.setRef Dataset reference YES
configurations.

(Only if not completely GoID.setVal Goose identifier YES


configured at start-up)

ConfRev.setVal Configuration revision YES

LGOS data attribute assigned to one goose


InRef_.intAddr YES
data value

RIO module Type. Involves modifying the


RIOGGIO TypeRIO.setVal YES
structure of the goose.

Network interface associated to the Goose


genIPRV DevGoose.setVal YES
messages.

genIPRV NoGsVlan.setVal VLAN use in Goose messages YES

YES, it is also deactivated after the


LLN0 IRMod.setVal InRefs mode
modification of an InRef data
Change of the I/O cards configuration from
- Commercial code the local HMI (change in the commercial NO
code)

Ingeteam Power Technology S.A.


User Manual 369
RECEPTION GOOSES

20. RECEPTION GOOSES


The IEC 61850 server is conforming to IEC 61850 Edition 2.

For the details of the IEC 61850 interface implementation consult the following documents for the Ingepac EF family:

❑ PICS: Protocol Implementation Conformance Statement for the IEC 61850 interface
❑ PIXIT: Protocol Implementation eXtra Information for Testing for the IEC 61850 interface
❑ TICS: Technical Issues Implementation Conformance Statement

The Ingepac EF family maintains compatibility with the existing ICDs developed following Edition 1. The last point of this section
describes the GOOSEs subscription for that case. The remaining points refer to functionalities associated with Edition 2
configurations.

20.1 GOOSE SUBSCRIPTION

According to IEC 61850 Edition 2 the GOOSE subscription is configured using the Inputs-ExtRef elements in the CID file.

The Inputs section defines all external signals that will be received via GOOSE messages from other IEDs. In this section,
each ExtRef element references to one external item and the intAddr element makes the binding of the external signal to an
IED internal configured data.

The CID file of an IED with configured GOOSE subscriptions contains several IED sections. The IED section of the server device itself and
IED sections from each of the IEDs sending GOOSE messages to which the device is subscribed.

These external IED sections only contain the data model needed for the subscription to reduce the size of the CID file.

LGOS logical node is used to monitor GOOSE subscriptions. There are 32 instances of LGOS logical node, which allow
monitoring up to 32 GOOSE subscriptions.

The only configuration value in the LGOS logical node is the GoCBRef (Reference to the subscribed GOOSE control block).

The monitored values are:

❑ NdsCom: Subscription needs commissioning. When true, the received GOOSE message does not conform the current
subscription configuration; either the dataSetRef is wrong, the data set members, the configuration revision number, ...
❑ St:If true, the GOOSE subscription is active, other is inactive
❑ SimSt: If true, subscribed GOOSE messages with the simulation bit set are being received and accepted
❑ LastStNum: Last state number received
❑ ConfRevNum: Expected configuration revision number of the GOOSE messages
❑ RxConfRevNum: Configuration revision number of the received GOOSE messages

The St and SimSt data are mapped to the internal database to be used in for example logics or local display. The other
values are only available through the IEC 61850 communication.

The factory CID file contains 2 logical nodes (GOOGGIO1 and GOOGGIO2) with available data for the internal binding of
the received values.

Each of these logical nodes contains:

Ingeteam Power Technology S.A.


User Manual 370
RECEPTION GOOSES

❑ 32 boolean signals (Ind1 to Ind32 data)


❑ 4 dbpos signals (DPSInd1 to DPSInd4 data)
❑ 4 float values (AnIn1 to AnIn4 data)

In models with the "Extended control" option the IED data model can be extended with more logical nodes in the control
logical device for internal binding of the data received in GOOSE messages.

Extension capacity:

❑ Signals: Up to a total of 1024 internal signals (including the 2 GOOGGIO nodes) and taking into account that the dbpos
signals occupy 4 internal signals.
❑ Measures: Up to a total of 256 measures (float values).

As established in Edition 2 of the standard, it is possible to subscribe to both data attributes and data objects. The recommendation
following criteria of efficiency and response time is to use data attributes in GOOSE messages. In any case, the device supports the
subscription to data objects of the following CDCs:

❑ Status: SPS, DPS, ENS, ACT, ACD.


❑ Measured: MV, CMV, WYE, DEL, SEQ, DEL y SEQ.
❑ Controllable: SPC, DPC, ENC.

For more information about the GOOSE subscription configuration process consult the software tool manual
(energyFactorySuite/pacFactory).

20.2 GOOSE SIMULATION

The device implements the GOOSE simulation mode defined in the IEC 61850 Edition 2.

This mode allows the simulation of any GOOSE that is present in the communication network so that two GOOSES with the same
information data will be present at the same moment, the real one without the simulation bit active and the simulated one with the
simulation bit active. If the subscriber is in simulation mode, once it has received the first simulation GOOSE its values will be used
instead of the values of the original GOOSE.

Therefore, if the device is in simulation mode, it still accepts 'original' GOOSE messages, and only discards the 'original' GOOSE
messages for those GOOSEs which are simulated.

Simulation mode is enabled with the controllable data "Sim" included in the LPHD logical node in the GEN logical device.

In each LGOS logical node, used to monitor GOOSE subscription, the SimSt status shows with TRUE value that subscribed GOOSE
messages with the simulation bit set are being received and accepted.

When the subscriber is not in simulation mode (GEN/LPHD.Sim.stVal=false) the simulated GOOSEs are ignored. The device keep on
using the "real" GOOSE messages.

When the subscriber is in simulation mode (GEN/LPHD.Sim.stVal=true) the simulated GOOSEs are used for operational purposes. The
device ignore the "real" GOOSE messages after a first simulated one has been received. The corresponding LGOS.SimSt is set when the
first simulated message is received and only cleared when LPHD.Sim.stVal is set to false.

Once the device has received a simulated message for one of the subscribed GOOSE messages, it will not process the real one until the
simulation mode of the device (LPHD.Sim.stVal) is set to false.

Ingeteam Power Technology S.A.


User Manual 371
RECEPTION GOOSES

The following state machine, from IEC 61850 TISSUES data base (num. 1151), displays the different states and illustrates the
supervision of GOOSE subscription with regards to LGOS.St and LGOS.SimSt

stm LGOS

[LPHD.Sim.stVal==FALSE]

Initial

LPHD.Sim.stVal
== TRUE

[y] [n]

subscription normal
goose as long as no
[LPHD.Sim.stVal == TRUE] subscribtion normal [normal GOOSE message received] w ait for normal GOOSE
w ait for normal or [TAL expired] simulated GOOSE
goose
simulated GOOSE receiv ed
[LPHD.Sim.stVal == FALSE] [TAL expired] SimSt.stVal = FALSE
SimSt.stVal = FALSE St.stVal = FALSE
SimSt.stVal = FALSE SimSt.stVal = FALSE
St.stVal = TRUE
St.stVal = FALSE [normal GOOSE received] St.stVal = TRUE

[LPHD.Sim.stVal==FALSE]
[simulated GOOSE received] [LPHD.Sim.stVal == FALSE]

[simulated GOOSE received]

w ait for Simulated


subscription simulated [TAL expired] GOOSE
GOOSE
[simulated GOOSE received] SimSt.stVal = TRUE
SimSt.stVal = TRUE St.stVal = FALSE
St.stVal = TRUE

It is possible to enable a GOOSE transmission simulation mode with the "TestEna" and "LogInTest" setpoints, included in GEN\LPHD
logical node:

❑ TestEna: If this setpoint is TRUE enables the GOOSE transmission simulation mode
❑ LogInTest: This setpoint allows to configure a signal which, when active, enables the GOOSE transmission simulation mode

In this mode all the GOOSEs transmitted by the device have the simulation field with TRUE value and the mode is indicated in the status
data GEN\LPHD.TestSt.

The following logic for the two configuration setpoints is used:

❑ TestEna=FALSE : TestSt=FALSE
❑ TestEna=TRUE and LogInTest=(not configured) : TestSt=TRUE
❑ TestEna=TRUE and LogInTest=(Signal data with value=TRUE) : TestSt=TRUE
❑ TestEna=TRUE and LogInTest=(Signal data with value=FALSE) : TestSt=FALSE

Ingeteam Power Technology S.A.


User Manual 372
RECEPTION GOOSES

20.3 TEST MODE

The device implements the Test mode defined in the IEC 61850 Edition 2.

Switching between the modes (Mod.stVal) only happen as a result of an operator command to the data object Mod.

The values of Mod and Beh that are used are:

❑ On:
❑ The application represented by the LN works.
❑ All communication services work and get updated values.
❑ Control commands with test bit will be rejected with AddCause "Blocked-by-mode".
❑ Test:
❑ The application represented by the LN works.
❑ All communication services work and get updated values.
❑ Data objects will be transmitted with quality “test”.
❑ Control commands with test bit will be accepted only by LNs in “test” mode.
❑ Off:
❑ The application represented by the LN doesn’t work.
❑ No process output is possible. No control command should be acknowledged (negative response).
❑ Data objects will be transmitted with quality “invalid”.
❑ Only the data object Mod and Beh should be accessible by the services.

On-blocked and test/blocked values are not supported.

20.3.1 Logical devices management hierarchy


Logical devices or LD, are used to represent a group of typical automation, protection or other functions. The functions
are defined as logical nodes contained and managed in logical devices. The hierarchy determines how the mode (e.g.
On, Off, Test …) of these functions and sub-functions is managed, so that a change in the value of the mode at higher
level influences the lower levels.

LLN0 of the logical devices that can be configured with a hierarchy contains a setting data named GrRef whose type is
objRef.

In order to configure a hierarchy the format of the GrRef value must be set with the name of the higher level logical device
concatenated to the IEDname of the installation. It is also possible that it is not configured.

The device implements the hierarchy on these logical devices:

❑ CTRL: Control functions (only present in devices with "Extended control")


❑ GEN: General functions
❑ PROT: Protection functions

GEN is considered the main logical node and its LLN0 logical node does not have the GrRef setting. CTRL and PROT
logical devices can be configured with a hierarchy.

So the typical hierarchy configuration is to assign the GEN logical device as higher level of CTRL and PROT. In this case, the
functions of CTRL and PROT logical devices are considered sub-functions of the GEN logical node and if the mode of
the GEN logical device is modified (GEN/LLN0.Mod) it will affect the CTRL and PROT logical devices also.

Ingeteam Power Technology S.A.


User Manual 373
RECEPTION GOOSES

The mode of the LNs in any logical device may be changed individually with its own Mod, or globally by means of LLN0 of
each logical device. Only changes in GEN/LLN0.Mod will affect the other logical devices that are configured as lower level
in the hierarchy.

For more details about how hierarchy affects commands behaviour, consult on this manual the "Command Blocks: Commands
blocks by mode (Mod/Beh)" section.

20.4 SERVICE TRACKING

Service tracking is represented by the logical node LTRK and is defined as the function in charge of recording the
parameters values used by any service defined in IEC 61850-7-2 (after a service execution). It is thus possible to read, report
or log these values for system behavior analysis.

The trigger option for these data is "data-update", so it has to be configured in the associated control block if, for example, it is
included in a report.

Service type values tracked by Ingepac EF:

❑ 16 - SelectActiveSG
❑ 17 - SelectEditSG
❑ 19 - ConfirmEditSGValues
❑ 24 - SetBRCBValues
❑ 26 - SetURCBValues
❑ 34 - SetGoCBValues
❑ 43 - Select
❑ 44 - SelectWithValue
❑ 45 - Cancel
❑ 46 - Operate
❑ 47 - CommandTermination
❑ 54 - InternalChange

Service error implemented values:

❑ 0 - no-error
❑ 1 - instance-not-available
❑ 2 - instance-in-use
❑ 3 - access-violation
❑ 4 - access-not-allowed-in-current-state
❑ 5 - parameter-value-inappropriate
❑ 6 - parameter-value-inconsistent
❑ 7 - class-not-supported
❑ 8 - instance-locked-by-other-client
❑ 9 - control-must-be-selected
❑ 10 - type-conflict
❑ 11 - failed-due-to-communications-constraint
❑ 12 - failed-due-to-server-constraint

Ingeteam Power Technology S.A.


User Manual 374
RECEPTION GOOSES

The logical node LTRK contains data classes with functional constraint FC=SR needed for track the previously defined services. The
following common attributes are included in all services:

❑ objRef: Reference of the object that is being tracked: either a control block that is being accessed or a control object that is
being controlled.
❑ serviceType: Type of the tracked service.
❑ errorCode: Error associated to the service that is specified by serviceType; value no-error for successful service.
❑ originatorID: Originator of the service. In general, the IP address of the client.
❑ t: TimeStamp of the completion of the service.
❑ d: Description

The following specific data objects are and included in the LTRK logical node:

Command service tracking:

Each enumerated has its own particular EncTrk, in which the ctlVal matches with the enumerated type defined for the controllable
object.

The index at the end may be incremented (For example EncTrk2) to define different instances.

❑ SpcTrk: Control service tracking for controllable single point.


❑ DpcTrk: Control service tracking for controllable double point.
❑ EncTrk1: Control service tracking for enumerated controllable. Mod (OFF)
❑ EncTrk2: Control service tracking for enumerated controllable. Mod (Test)
 Associated services:
▪ Select, SelectWithValue, Cancel, Operate

 Specific attributes (in addition to common attributes):


▪ ctlVal
▪ origin
▪ ctlNum
▪ T
▪ Test
▪ Check
▪ respAddCause

Unbuffered report service tracking:

The IED generates a tracking register when a SetURCBValues is done over the following attributes: rptID, rptEna, datSet, optFlds,
bufTm, trgOps, intPd and resv, what is according to IEC 61850-7-2 Subclause 15.3.2.3.1.

The change of other attributes associated to a URCB like confRev, gi, etc. will not generate a tracking register.

The attributes RptEna and Resv of the URCB instances are tracked at loss of association with the Client, with ServiceType =
InternalChange, with “127.0.0.1” as content of the originatorID field.

❑ UrcbTrk: Access service tracking for unbuffered report control block.

Ingeteam Power Technology S.A.


User Manual 375
RECEPTION GOOSES

 Associated services:
▪ SetURCBValues

 Specific attributes (in addition to common attributes):


▪ rptID
▪ rptEna
▪ resv
▪ datSet
▪ confRev
▪ optFlds
▪ bufTm
▪ sqNum
▪ trgOps
▪ intgPd
▪ gi
▪ owner

Buffered report service tracking:

The IED generates a tracking register when a SetBRCBValues is done over the following attributes: rptID, rptEna, datSet, optFlds,
bufTm, trgOps, intPd, purgeBuf, entryID, and resvTms, what is according to IEC 61850-7-2 Subclause 15.3.2.2.1.

The setting of other attributes associated to a BRCB like confRev, gi, etc. will not generate a tracking register.

The attributes RptEna and ResvTms of the control block are tracked at loss of association with the Client with ServiceType =
InternalChange, with “127.0.0.1” as content of the originatorID field.

❑ BrcbTrk: Access service tracking for buffered report control block.


 Associated services:
▪ SetBRCBValues

 Specific attributes (in addition to common attributes):


▪ rptID
▪ rptEna
▪ datSet
▪ confRev
▪ optFlds
▪ bufTm
▪ sqNum
▪ trgOps
▪ intgPd
▪ gi
▪ purgeBuf
▪ entryID
▪ timeOfEntry
▪ resvTms
▪ owner

Goose service tracking:

❑ GocbTrk: Access service tracking for goose control block.


 Associated services:

Ingeteam Power Technology S.A.


User Manual 376
RECEPTION GOOSES

▪ SetGoCBValues

 Specific attributes (in addition to common attributes):


▪ goEna
▪ goID
▪ datSet
▪ confRev
▪ ndsCom
▪ dstAddress
▪ minTime
▪ maxTime
▪ fixedOffs

Settings service tracking

❑ SgcbTrk: Access service tracking for setting group control block.


 Associated services:
▪ SelectActiveSG
▪ SelectEditSG
▪ ConfirmEditSGValues

 Specific attributes (in addition to common attributes):


▪ numOfSG
▪ actSG
▪ editSG
▪ cnfEdit
▪ lActTm
▪ resvTms

20.5 SUBSTITUTION MODEL

It allows to establish individually the values of some data that are sent through the protocol IEC61850.

Usually, input from the process or the result of the calculation from a function provides the value of a data (in that case, the
source is called "process"). In case of substitution model, the value of the data may be provided by an operator making use
of an IEC 61850 client.

Substitution model is available for the following common data classes:

❑ SPS (Single Point Status)


❑ DPS (Double Point Status)
❑ INS (Integer Status)
❑ SPC (Single Point Control)
❑ DPC (Double Point Control)
❑ MV (Measured Value)
❑ CMV (Complex Measured Value)
The IEC 61850 standard does not define the substitution model for other classes like ACT (Protection activation
information), ACD (Directional protection activation information), VSS (Visible String Status) or any of the settings classes.

Data classes that allow substitution have an attribute "subEna". If it is set to TRUE, the value of the data used for the IEC
61850 communications is the value configured in the following attribute (depending on the data type):

Ingeteam Power Technology S.A.


User Manual 377
RECEPTION GOOSES

❑ Value:
❑ subVal: SPS, DPS, INS, SPC, DPC
❑ subMag: MV
❑ subCVal: CMV
❑ Quality: The attribute "subQ" is the value used to substitute the data attribute q. When subEna is true, the source quality
bit substituted is always set.
On measurement data substitution, the value is checked against the configuration of the measure (max, min, db …) so the
substituted value is affected by such configuration.

It is the responsibility of the client application, in particular in the case of multiple attributes to be substituted, to set the
relevant substitution values before enabling substitution, as well as, disable substitution on all substituted values.

The substituted values only apply to the IEC 61850 communication values. These means that the substituted values are not
used in the logics or protection functions of the device.

There are several data with a special behavior for which the substitution of the value affects to the behaviour of the
IEC61850 server:

❑ BlkGoose.stVal: It allows blocking the transmission of all gooses.


❑ TestSt.stVal: It allows enabling the simulation bit in transmitted gooses.
❑ Sim.stVal: It allows activating the simulation mode.
Also defined in the substitution model, it is available the attribute "subID". When the substitution is activated, the device
automatically sets the subId to the IP address of the client device that activated the substitution. After this moment, the client can
write any other string to identify itself. Later when substitution is deactivated, the value is modified to a fixed empty string. In
conclusion, this attribute can be only modified after setting subEna to true.

20.6 FILE TRANSFER

The IED implements the IEC61850 MMS file services. Following the Edition 2 of the IEC61850 standard, the structure of files and
directories is based on a FLAT FILESYSTEM with pseudofolders. This means that it is not accessed through folders, it is only allowed to
read the root directory where all the existing files in the different subfolders are shown concatenating the path to the file name.

The available permissions are the same as those of the user 'ftpuser', and only writing the pseudofolder /SCL/notvalidated/ is allowed.

This behavior is used from firmware version 6.0.17.0 for both Edition 1 and Edition 2 configurations. In firmware versions prior to this
(only Edition 1 configurations were supported) the file and directory structure is based on folders, being able to access and read each
one separately.

20.7 EDITION1 SUBSCRIPTION. LGOS MODEL.

Only for ICD configured as Ed1: This model makes it possible to configure and supervise the complete status of each reception goose
within a single logical node.

Each goose subscription is associated with one LGOS logical node wich contains the configuration for that subscription, so there can be
as many subscriptions as LGOS logical nodes in the data model. The factory CID file contains up to 32 LGOS logical nodes that allow the
subcription to up to 32 goose messages.

To use the received data in the goose message they must be mapped to LGOS data. Each LGOS has:

❑ 17 boolean signals (Ind1 to Ind17 data)


❑ 4 dbpos signals (DPSInd1 to DPSInd4 data)

Ingeteam Power Technology S.A.


User Manual 378
RECEPTION GOOSES

❑ 8 float values (AnIn1 to AnIn8 data)

20.7.1 Configuration values


Used to establish the desired subscription parameters for each goose.

To create a subscription it must be configured:

❑ Configuration data of the Goose message to subscribe.


❑ Data assignment: Each data from the received Goose message can be assigned to one data in the LGOS logical node
in which the received value will be copied.

Table 225 LGOS model configuration values

ATTRIBUTE DESCRIPTION

ConfRev.setVal Must match the value received in the goose.

GoCBRef.setRef The goose reference to which we subscribe.

GoDatSetRef.setRef The reference of the dataset to which we subscribe.

GoID.setVal The identifier of the goose to which we subscribe.

The reference to the signal in which the goose element established by the InRef index is
InRef[..].intAddr
received. It must be a mapped signal within the goose signals range.

MAC.setVal The multicast MAC to which we subscribe.

These values, apart from the “intAddr” for the internal data assignement, must be the same ones received in the Goose message.

The data mapping is configured with the InRef data (InRef1 to InRef34). The InRef index indicates the reception goose data position
associated with that InRef (InRef1 associated to first goose data, InRef2 associated to second goose data, etc.)

In the InRefx.intAddr attibute must be configured the LGOS data in which the value will be copied. The value must be:

❑ Boolean signals: Indx.stVal / Indx.q


❑ Dbpos signals: DPSIndx.stVal / DPSIndx.q
❑ Float values: AnInx.mag.f / AnInx.q
If in the Goose message the qualities of the data are also received they must be assigned to a “q” data of one of the LGOS node
data, like the rest of the Goose data.

To configure this assignment the user must know the format of the data of the Goose message because the selected data in the
LGOS node to copy the received value must have the same format.

Each LGOS logical node in the the factory CID data model has 34 InRef data so the device can subscribe to Gooses with up to 34
elements.

For example if the configured value is InRef3.intAddr = Ind2.stVal this means that the third value in the received goose (that must
be a boolean value) will be copied to the LGOSx.Ind2.stVal data.

The software tool allows configuring these goose subscritpions manually or automatically (for more information consult the
pacFactory software tool manual).

Ingeteam Power Technology S.A.


User Manual 379
RECEPTION GOOSES

20.7.2 Supervision values


They indicate information about the status of the goose subscription at all times. The status signal conditions the updating of the
rest of the Data. If the status is incorrect, the rest of the signals will not be updated with the values received.

Table 226 LGOS model supervision values

ATTRIBUTE DESCRIPTION

St.stVal Subscription status. Value “1” indicates that the subscription was successful.

Sim.stVal Activated when the subscription is received in test mode.

NdsCom.stVal Activated when the subscription has the “Needs Commissioning” flag activated.

LastStNum.stVal The last status number received.

ConfRevNum.stVal The configuration revision received.

Note: Only the St data is mapped to the internal database to be used in for example logics or local display. The other values are
only available through the IEC 61850 communication.

20.7.3 Checked values


The following values are checked to decide if the goose message is valid:

❑ TAL (Time Allowed to Live) not zero


❑ MAC multicast
❑ Dataset
❑ GoCBRef
❑ GoID
It is also checked that the types of each goose data mach the types of the LGOS data in which they will be copied.

Ingeteam Power Technology S.A.


User Manual 380
TCP/IP NEWORK CONFIGURATION

21. TCP/IP NEWORK CONFIGURATION

21.1 DESCRIPTION

In the device has a front Ethernet interface and may have up to two rear Ethernet interfaces. Each of which can be configured to
belong to the network that the user wants, as seen in the figure below:

❑ ETH0, frontal Ethernet.


❑ ETH1, rear Ethernet.
❑ ETH2, rear Ethernet.

The rear ethernets can be selected from one of the following options (see commercial code):

❑ Independent port
❑ Redundancy module configurable between PRP, HSR and Switch mode
❑ Link failover redundancy (both ethernet ports used)

The configuration of each network can be made:

❑ From the device Display (see section of the display).


❑ From PacFactory configuration tool (see user manual pacFactory).

The device has signals to indicate the link status of each of the ethernet ports in the LPHD1 node of the logical device GEN:

Table 227. Link status signals

Señal Dato Atributo


Link Ethernet 0 Eth0Link stVal
Link Ethernet 1 Eth1ALink stVal
Link Ethernet 1 redundant Eth1BLink stVal
Link Ethernet 2 Eth2ALink stVal
Link Ethernet 2 redundant Eth2BLink stVal

Ingeteam Power Technology S.A.


User Manual 381
TCP/IP NEWORK CONFIGURATION

Redundant Link indications are only used in the case of redundant communications. In non-redundant communications, the link
indications are shown in the Eth1ALink and Eth2ALink data.

In the link failover redundancy the link indications are shown in the Eth1ALink and Eth1BLink data.

21.2 COMMUNICATIONS REDUNDANCY

The device has several options of physical communications redundancy divided into two hardware solutions:

❑ PRP / HSR / Switch mode (Options O and P of the commercial code)


❑ Link redundancy (Options I, J and K of the commercial code)

When the device has the PRP/HSR/Switch mode module, the user can configure any of the three options or consult the configured
option from the local display (Initial menu - Communications - Configuration PRP / HSR / Sw) or from the web server of the device
(Maintenance menu - Communications - IP network configuration).

21.2.1 PARALLEL REDUNDANCY PROTOCOL (PRP)


The PRP (Parallel Redundancy Protocol) is a redundancy communication protocol defined in the IEC 62439-3 standard and it is one
of the redundancy mechanism recommended in IEC 61850 networks.

In the PRP protocol the device use two redundant ethernet ports and the protocol is based on the simultaneous transmission and
reception of data via both independent ports.

In PRP solutions two independent ethernet networks are used. Each device is attached to both networks and sends and receives all
the frames over both LANs simultaneously, consumes the first frame and discards the duplicate. With this mechanism PRP ensures
zero-packet loss and zero recovery time upon single network failures.

The two LANs have no connection between them and are assumed to be fail-independent, both are identical in protocol at the
MAC-LLC level, but they can differ in performance and topology.

With the PRP protocol additional information called RCT (Redundancy Control Trailer) is added to the Ethernet frame at the link
layer in order to control redundancy. This information is transparent for devices that do not use PRP protocol and it is used by PRP
devices to discard the duplicate frames.

Devices without PRP can be connected to one of the redundant ethernet networks but in that case they only can communicate with
the devices connected to the same network. In order to enable redundancy in non-PRP devices an external converter called RedBox
(Redundancy Box) can be used.

21.2.2 HIGH-AVAILABILITY SEAMLESS REDUNDANCY (HSR)


The HSR is a redundancy communication protocol defined in the IEC 62439-3 standard and it is one of the redundancy mechanism
recommended in IEC 61850 networks.

In the HSR protocol the device use two redundant ethernet ports and the protocol is based on the simultaneous transmission and
reception of data via both independent ports.

In the HSR networks no external switches are used, instead each device has two ring ports, and all the devices are connected in a
ring topology, with one port of the device connected to the previous device and the other connected to the following device.

For each frame to send, the device sends it duplicated over both ports. So one frame travels in the ring in the clockwise direction
and the other frame travels in counter-clockwise direction. Each direction is treated as a separate network. So if there is a failure in
one point of the network, the frames reach the destination using the other direction in the ring. With this mechanism HSR ensures
zero-packet loss and zero recovery time upon single network failure.

An HSR tag is placed at the beginning of each frame to allow early identification of frames. With this tag each device can identify
the HSR tagged traffic and reject the duplicated frames coming from the both ports of a device and the frames circulating in the
ring. When a device receives a frame directed to it or that it sent, the frame is discarded and it is not forwarded again in the ring.
The frame is also discarded if it is a frame that it already sent in the same direction (i.e. multicast frames).

Ingeteam Power Technology S.A.


User Manual 382
TCP/IP NEWORK CONFIGURATION

Devices within the ring are restricted to be HSR-capable IEDs. In order to enable redundancy in non-HSR devices an external
converter called RedBox (Redundancy Box) can be used.

21.2.3 SWITCH MODE


In the switch mode both ethernet ports act as an unmanaged switch forwarding the network traffic.

The recommended network topology would be a cascade or Daisy-chain connection without closing a communication ring because
the IED integrated switch does not implement the RSTP protocol.

21.2.4 LINK FAILOVER REDUNDANCY


With the link failover redundancy the device uses two ethernet ports for a redundant communication.

In this redundancy mode the device communicates by one of the ethernet ports and if there is a link failure in that port, switches to
the redundant port if the link status of that port is active.

If the link status of the passive port returns to normal, the communication is maintained in the active port and the devices only
change the active port in case of link failure.

In this redundancy, unlike the case of PRP redundancy, it should not be used two independent ethernet networks. The two
Ethernet ports of the equipment must be connected to different network switches, but must belong to the same network, so that
the switches should be connected at some point in the network.

This switching is almost instantaneous, allowing even Gooses redundancy without loss or minimal loss (1 repetition). Regarding
communications with IEC 61850 clients, depending on the ring reconfiguration time communications, we even could not lose the
connection or the open session.

The device has link failover redundancy status signals in the logical node LPHD1 of the GEN logic device, to indicate which of the
two channels is active and to indicate possible failures in the redundancy.

Table 228. Link failover redundacy status signals

Señal Dato Atributo


Channel A active Ethernet 1 Eth1Ast stVal
Channel B active Ethernet 1 Eth1Bst stVal
Ethernet redundancy Alarm EthRAlm stVal

21.3 GENERAL CONSIDERATIONS ABOUT NETWORK CONFIGURATION

When configuring the network of the device it must be taken into account the following considerations:

❑ Basic concepta about networks:


 The format of the IP address or mask have the dotted decimal notation. The checks are performed according to this
standard.
 Addresses ending in 0 correspond to networks, not devices. For example : 192.168.200.0
 Addresses ending in 255 correspond to broadcast messages. For example : 192.168.200.255
 All network traffic for an IP address that is not included in the configured networks, will be redirected to the default
gateway configured.
❑ It is not allowed the IP address or mask 0.0.0.0.
❑ It is not allowed the IP address or mask 255.255.255.255.

Ingeteam Power Technology S.A.


User Manual 383
TCP/IP NEWORK CONFIGURATION

❑ From version 5.25.16.1 of firmware it is possible to configure several IP addresses in the same ethernet interface. For
previous versions it is not allowed.
❑ Gateways configuration:
 There can be only one default Gateway in the devices and it will be associated to a specific Ethernet interface.
 If a Gateway is configurec, the static routes for the ethernet traffic will be determined by up to 10 groups or three
parameters:
 IP address of the network or destination host. This IP address indicates the network or the device you want
to connect to.
 Network mask or destination host mask.
 Gateway IP address. It must be in the same net segment than the IP address configured in that ethernet
port; because in another way the device will not access to the gateway.
 If the IP address of the network or destination host or the mask of the network or destination host are not configured,
the default values are:
 IP address: 0.0.0.0, it will be all the networks or default gateway.
 Network Mask: 255.255.255.255, it will be all networks or default gateway.
 The configuration of gateways can only be done from the Display.
 When changing the IP address, the gateways that are no longer accessible by the new IP will be removed
permanently.
 The IP change command keeps the mask that was associated with that Ethernet interface.
 Do not configure two different Ethernet interfaces within the same network segment. When you configure
two interfaces within the same network segment, the device will use only one of them.

21.4 GOOSES

GOOSE messages (IEC 61850 peer-to-peer communications) are not on the TCP/IP layer, they are Ethernet packets and are configured
at the MAC level.

The devices subscribes to multicast MAC addresses for receiving messages and transmit to a specific Multicast MAC address.

Ethernet interface ETH0 is not ready to receive / transmit packets GOOSE.

21.5 FIREWALL

From firmware version 5.25.16.1 the device incorporates a firewall functionality through which any port in TCP/IP communications (eg
PING, FTP, sFTP, HTTP, etc.) can be blocked.

The firewall function can be enabled or disabled independently for each of the network interfaces. In case of link failover redundancy
interfaces, only the ETH1 interface shall be configured for both rear Ethernets.

Each TCP or UDP port can be configured as "closed" or "opened". When the firewall function is enabled on a network interface by
default all TCP ports are closed and those that want to be left opened must be configured. And in the case of configuring a port as open
the IP addresses from which the port will be accessible can be configured or leave it open for any IP address.

Configuration is done from the pacFactory / energyFactorySuite software tool. Refer to the user manual of the tool for more details on
the configuration.

Ingeteam Power Technology S.A.


User Manual 384
COMMUNICATION BETWEEN DEVICES 

22. COMMUNICATION BETWEEN DEVICES


This section gives a general description of the communications features for teleprotection schemes and the connections needed in the
devices. It only applies to MD and ZT models with teleprotection. The general features are summarised below:

❑ 1 or 2 ports that can be selected:


 GOF, POF, RS232C, RS485
 Single-mode optical fibre with the following options:
 ST or LC type connectors.
 Scope from 20 to 120km.
 IEEE C37.94 (multi-mode OF). ST connector.
With IEEE C37.94, the port must be configured with the settings:

❑ Comm speed (bauds). 38400 bauds.


❑ Parity: "Even".
❑ Number of Stop bits: "1".

22.1 DIRECT CONNECTION (POINT-TO-POINT)

Direct connection (without a telecommunications network) between the ends can be achieved via RS-232, RS-485, multi-mode optical
fibre or single-mode optical fibre. The conditions of possible noise and interference and the distances supported are limitations which
incline towards choosing Optical Fibre.

This type of connection always involves joining the transmission channel (Tx) of one end to the reception end (Rx) of the other.

Ingepac EF devices must have the correct interfaces to permit this type of connection. The options are contained in the commercial
code (see section "Model Encoding").

The connection options via optical fibre are explained below.

22.1.1 Multimode Optical Fibre


The possible options are as follows:

Maximum
Cable Type Permitted attenuation Wavelength Connector
distance
Multi-mode glass optical fibre:
62.5/125 µm 11db 2km 820nm ST
50 /125 µm 9dB
Multi-mode optical fibre:
V-Pin connector
200Μm HCS (silicone) 22dB 1.9 km 660nm
(HP standard)
1Mm plastic 24.7db 115 m

22.1.2 Single-mode optical fibre


The possible options are as follows:

Permitted Maximum Minimum


Cable type Wavelength Connector
attenuation distance distance
Single-mode optical fibre LC duplex
30db 60 Km 1 Km 1310nm, Laser
9/125 nm ST
Single-mode optic fibre LC duplex
40db 120 Km 20 Km 1550nm, Laser
9/125 nm ST
N.B.:

Ingeteam Power Technology S.A.


User Manual 385
COMMUNICATION BETWEEN DEVICES 

It is highly recommended that you use attenuators if you are going to connect single-mode optical fibre cables shorter than the
length indicated as the minimum distance. Attenuators should be placed at the transmitter output (connector Tx).

22.2 CONNECTION WITH COMMUNICATIONS DEVICES (MULTIPLEXER)

Connections via a telecommunications network are made using communications devices which permit the connection of Ingepac EF
devices to the network, establishing a virtual link between them. These devices are called multiplexers (MUX) or Pulse Code
Multiplexers (PCM). They use standard protocols such as:

❑ IEEE-C37.94 (Optical Fibre Interface)


❑ UIT-G.703 (Galvanical Interface)

22.2.1 IEEE-C37.94 Interface


This interface offers the possibility of using up to twelve 64 Kbs channels each. If a device needs to send at a higher speed (always
Nx64), N channels of the ones available will need to be occupied. It provides a connection via multi-mode optical fibre.

The port used with this communication must be configured with 38400 baud, even parity and 1 stop bit.

There are different user options for this interface:

❑ Direct connection to a MUX device which uses this standard.


❑ Connection to an external optocoupler device (C37.94 optical to G.703 electrical interface converter).
From the perspective of Ingepac EF, the two cases are identical and no special adjustment needs to be made.

In the second case, information will be needed to adapt the optocoupler device. The section gives a practical example of using
external converter devices.

The characteristics of multi-mode optical fibre for this connection are as follows:

Permitted Maximum
Cable type Wavelength Connector
attenuation distance
Multi-mode glass optical fibre:
62.5/125 µm 13db 2km 850nm ST
50/125 µm 9dB

22.3 EXAMPLE OF CONNECTING A C37.94 - G.703 CONVERTER

This section describes how to connect an Ingepac EF device to a multiplexer using an external C37.94 to G.703 converter. This
optocouplers or converter devices can be used to connect to MUX for access to SDH and PDH networks.

The G.703 standard has different interfaces: E0 (64Kbs), E1 (2Mb), etc. Hence, there are different C37.94 to G703 converters for
converting to E0, to non-structured E1, to structured E1, etc.

22.3.1 C37.94 - G.703 E1 2Mb Converter.


This example indicates the steps for installing the 21-219, C37.94 to structured G.703 E1 converter.

Ingeteam Power Technology S.A.


User Manual 386
COMMUNICATION BETWEEN DEVICES 

As a general rule, connect the Tx transmission line of the Ingepac EF-LD device to the Rx reception line of the device and vice versa.
In 21-219 devices, you can use two C37.94 channels, but in this example, we will limit ourselves to using Channel 0.

In this device, the part of the G.703 E1 2Mb interface consists of two BNC 75 Ohm connectors for connection to the MUXs. If two
21-219 converters are to be connected to each other, output Tx of one must go to input Rx of the other and vice versa.

Configuring the clock source for G.703 synchronisation.

There are different alternatives for defining the master clock used in the G.703 standard:

❑ Network’s master clock.


SDH networks have a precise master clock for keeping a system quite safe with a very low error rate. In this case, 21-219
converter devices can be synchronised with the network’s master clock. To do this, the MUXs must be configured so that
re-synchronisation and a telegram format compatible with the G.704 standard is permitted.

In terms of the 21-219 converters, the external clock source must be configured for synchronisation in both devices. To do
this, there is a rotational switch on the front of the 21-219 which allows you to select the clock source, amongst other
items. In this case, the switch must be set to “0”, which is the default configuration.

❑ Master clock of one of the 21-219 devices.


The internal clock of one of the 21-219 devices can be used as the master clock. This option is applicable to a test phase, in
which the converters are connected to each other with a crossed G.703 connection (without multiplexers).

To achieve this, the internal clock source in only one of the 21-219 devices must be configured so that there is only one
master clock. In this case, the rotational switch must be set to position “1”.

Ingeteam Power Technology S.A.


User Manual 387
COMMUNICATION BETWEEN DEVICES 

The other 21-219 devices must be configured with the external clock option as indicated in the previous section.

Also, this option must be applied when the network does not provide such a precise clock (e.g. PDH networks) and the
multiplexers are configured so that they do not interfere with synchronisation (functioning in transparent mode).

22.3.2 C37.94 - G.703 E0 Converter.


For the converter to the G703 E0 (64Kbs) standard, 21-216, the steps are practically the same. In this case, the G.703 interface is an
RJ45 codirectional port. Twisted pair cables must be used. If you want to connect the two 21-216 devices to each other, a specific
crossed cable must be made.

The list of pins in the RJ45 port is as follows:

RJ45 pin Signal


1 Tx + (TIP-out)
2 Tx - (RING-out)
4 Rx + (TIP-in)
5 Rx - (RING-out)
Case Mesh

Ingeteam Power Technology S.A.


User Manual 388
KEYBOARD AND GRAPHIC DISPLAY 

23. KEYBOARD AND GRAPHIC DISPLAY

23.1 GENERAL OPERATION

23.1.1 Display structure


The screens are grouped into the following types:

❑ Graphic pages. Only available in models featuring "extended monitoring functions".


❑ I/O pages
❑ Secuence of Events (SOE)
❑ Protection events pages
❑ Alarm pages. Only available in models featuring "extended monitoring functions".
❑ Device status pages
❑ Fault pages. Not available in CDx models.
❑ Measurements pages. Only available in CD1 y CD2 models
❑ Grouping of other screens
Each display type has its own treatment.

There are also menu pages (which include the protection, control and general settings, such as the date and time, password, FW
versions, etc.), which are treated differently to those mentioned above.

23.1.2 Organization of the pages


The pages are organized into screen types, whose order of presentation is configurable using an external tool. The tool also enables
the unit’s start page to be assigned. The keys “(Left), →(Right)” allow the user to scroll through the different screen types
defined as main screens. The screens can be scrolled in both directions: upon reaching the last screen type the display returns to
the first screen, and vice-versa.

By clicking on the “ (Up),  (Down)” keys in any screen, the screens belonging to the same type are shown. The I/O, SOE, and fault
pages are presented in a preconfigured order. However, in the graphic and alarm screens the presentation order is defined using an
external tool.

If, when in any screen belonging to specific type, we press “(Left), →(Right)”, the following screen type is displayed whilst the
screen position remains within the type in question. Thus, when scrolling through the screen types the last screen types selected
when exiting a specific type are shown.

If no keys are pressed within a period greater than 5 minutes, the unit returns to the start page and the first page of each type is
selected.

By pressing on <ESC> from any screen we return to the start page, whilst the current page of each screen type is maintained.

There is a special screen type called “Menu to Other Screens” that contains an index of screens not considered important enough
to have been defined as main screens and which enables access to the same. This screen is configurable via a PC tool.

By pressing <MENU> from within any screen, the first page of the settings menus is displayed.

The possibility of multi-language is available.

Device with IP protection covers

If the unit is fitted with an IP protection cover, only certain buttons will be accessible from the front, depending on the model in
question:

Ingeteam Power Technology S.A.


User Manual 389
KEYBOARD AND GRAPHIC DISPLAY 

❑ Preset Keys (1/2 chassis – 5U and 19” chassis – 4U)


The only keys available are I, O, SEL, INF and DES.

The INF button allows the different screens to be displayed in a circular mode, whilst the order is configurable via a PC tool.

❑ Functional Keys (1/2 chassis – 5U and 19” chassis – 4U)


The only keys available are I, O, F1, F2, F3, F4, F5 and the DOT key.

The DOT button allows the different screens to be displayed in a circular mode, whilst the order is configurable via a PC tool.

23.1.3 Treatment of the functional keys


The functional keys are configured with the PC tool, with the control and associated status being configured for each key. In
addition there is a check box to reverse the status of the signal associated with the functional key. This option only applies to
Boolean (not double) signals.

The possible values of the status signal associated to the functional key and its corresponding representation via the LEDs are:

❑ Not configured: the 2 LEDs OFF.


❑ Unknown Status: the 2 LEDs OFF.
❑ OFF Status: upper LED OFF and lower LED ON.
❑ ON Status: upper LED ON and lower LED OFF.
❑ Invalid Status: the 2 LEDs ON.

The functional keys have 3 operating modes configurable by setting “GEN/LLN0/FbuttType”:

❑ “Functional keys” Mode:


 By pressing the key, the associated item is selected and the corresponding LED or LEDs blink.
 Once the item has been selected, the associated command can be executed by pressing the “I” or “O” keys.
 Once the above-mentioned key has been pressed, the unit executes the command and the lit LED or LEDs cease to
blink.
 Once a command has been executed, the status of the associated LED or LEDs is updated. In case of a failure, a
window indicating the cause of the failure will appear in the display.

❑ “Command 52 + Functional” Mode:


 By pressing the key, the associated item is selected and the corresponding LED or LEDs blink.
 Once the item is selected, depending on its status one of this windows is shown:
 ON Status: displays the confirmation window for the OFF command.
 OFF Status: displays the confirmation window for the ON command.
 Unknown / Undetermined Status: Displays the confirmation window for the two possible ON and OFF
commands. With the " (Up) or  (Down)" keys the desired command is selected and with the  (Enter) key
the command confirmation window appears. With the "ESC" key to exit the selection screen.
 Once a command has been executed, the status of the associated LED or LEDs is updated. In case of a failure, a
window indicating the cause of the failure will appear in the display.

❑ “Command Confirmation” Mode:


 The operation is the same as the "Functional Keys" mode but with the particularity that every time the user executes
an command (I / O buttons) a confirmation message will appear on the display (pressing the ENTER key executes the
command and Pressing ESC cancels).

Ingeteam Power Technology S.A.


User Manual 390
KEYBOARD AND GRAPHIC DISPLAY 

This mode will be applied for both the graphical screens commands and the functional key commands (contemplating
that we can be in any of the display screens)

NOTE 1: To change this setting from the display, the settings menu is accessed and in the initial menu select the 'general settings'
menu and press the ENTER key. Within this node, the setting is 'Command Type'. The 'With confitmation' option is selected and the
settings are validated.

NOTE 2: When a function key has not a configured signal but it has a configured command the 2 LEDs remain OFF until the function
key is pressed. At that moment the 2 LEDs start blinking.

Ingeteam Power Technology S.A.


User Manual 391
KEYBOARD AND GRAPHIC DISPLAY 

23.1.4 Graphics pages


The maximum number of graphic screens is 9.

Use the “ (Up),  (Down)” keys to switch from one group of graphic screens to another.

The order of the “live points” that have commands and the sequence of the graphic screens can be modified using the PC tool.

Figure 1 Single Line diagram Figure 2 Single Line diagram with indication of non-run command

The treatment of controls WITH Preset Keys:

❑ To run a command, we must first select the item to be sent. To do so, and once we have selected the screen
containing the item to be sent, we must press “SEL”. The symbol of the item that has been configured to priority 1
and which has an associated command will appear and begin to flash.
❑ By pressing “SEL” we scroll through the different “live points” with commands, in accordance with the preset
order.
❑ Once the item to be sent has been selected, the process is as follows:
 Press the key “I” for the following commands: close, in service, automatic, remote control, etc.
 Press the key “O” for the following commands: open, out of order, manual, local, etc.
 By pressing the key “DES” (if the item has maintenance configured), the command will be run, in accordance
with the item's status – if it is set to maintenance, the command will be “remove maintenance”, if it is not in
maintenance, the command will be “set to maintenance”.
If the command fails or if it can not be run due to a block, a small screen indicating the reason for the failure will be
displayed. This indication appears for 5 seconds, during which no operations can be carried out on the item.
❑ If the command is successful, no additional screen will be shown and the item's status will be refreshed.
❑ If it is in the control selection, only the “SEL”, <ESC> and “I, O, DES” keys are allowed.
The treatment of controls WITHOUT Preset Keys:

❑ To run a command, we must first select the item to be sent. To do so, and once we have selected the screen
containing the item to be sent, we must press  (Enter). The symbol of the item that has been configured to
priority 1 and which has an associated command will appear and begin to flash.
❑ By pressing the “(Left), →(Right)” keys, we scroll through the different “live points” with commands, in
accordance with the preset order.

Ingeteam Power Technology S.A.


User Manual 392
KEYBOARD AND GRAPHIC DISPLAY 

❑ Once the item to be sent has been selected, the process is as follows:
 Press the key “I” for the following commands: close, in services, automatic, remote control, etc.
 Press the key “O” for the following commands: open, out of order, manual, local, etc.
❑ If the command fails or if it can not be run due to a block, a small screen indicating the reason for the failure will be
displayed. This indication appears for 5 seconds, during which no operations can be carried out on the item.
❑ If the command is successful, no additional screen will be shown and the item's status will be refreshed to show
"normal".
❑ If it is in the control selection, only the <ESC>, (Left), →(Right) and “I, O” keys are allowed.

By pressing <ESC>, we exit the control selection, as we also do if we refrain from pressing any keys for a period of more than “10
sec”.

The measurements are displayed with the number of decimal points and digits preset with the configuration tool. The possible
situations that are covered when viewing a measurement are:

❑ Invalid: An '*' is placed in front of the measurement, there is no associated flashing. E.g.: * 25.3
❑ Outside range: '####' is displayed without flashing when the measurement’s value exceeds the maximum value for
the specified nº of digits and decimal points. E.g.: measurement value = 100 and number of digits = 2.
❑ Alarm: An 'A' is displayed in front of the measurement, with flashing, when the measurement exceeds the set
range. There is an upper and a lower limit. E.g.: If an alarm is activated when the upper limit is greater than 200 A,
the measurement will be displayed as follows: A 202.

Each of the measurements displayed in the graphic screens can be configured so that their values are referred to the primary or the
secondary.

Ingeteam Power Technology S.A.


User Manual 393
KEYBOARD AND GRAPHIC DISPLAY 

23.1.5 I/O pages


The device may be equipped with different types of cards, which are distinguished by the combination of inputs and outputs
grouped in 2 columns. Each card’s information is grouped in a page.

A text indicating the type of card, the address of the module assigned by HW and an indication of the current page number/number
of total pages, which is the same as that of the card, is displayed at the top of the screen.

An indication of a card failure is shown in the lower part of the screen. If the circle is filled, the card is in failure, whereas if it is
empty, the card is functioning correctly (Figure 200).The order of this type of screen is defined by the different card’s addresses –
the card with the lowest address is displayed first and the pages can be scrolled using the “ (Up),  (Down)” keys.

The digital I/O data are listed in 2 columns. Each column contains a graphic symbol (a circle), followed by the input or output text
and the corresponding number of terminals:

The digital signals are displayed as an empty circle, when disabled, or a filled circle, when enabled. In the event of an invalid signal,
an empty circle with a cross is displayed to represent a disabled status and a filled circle with an inverted cross is displayed to
represent an enabled status (Figure 201).

Figure 200 I/O Screen Figure 201 I/O Screen with card failure

Ingeteam Power Technology S.A.


User Manual 394
KEYBOARD AND GRAPHIC DISPLAY 

23.1.6 Event pages


The event screens display a chronological record of all the changes that take place in the signals that have been configured as
events in the display.

Each event’s presentation includes the date and time to the millisecond, a 29 character text and a 7 character acronym.

The texts to be displayed, as well as the signals’ identification, are set in attributes of the CID and may be modified using an
external tool.

The screen order is defined chronologically. Their display order goes from the newest to the oldest. Within each screen, the most
recent are shown at the top of the page and the oldest at the bottom.

We can scroll through the pages using the “ (Up),  (Down)” keys, going from the last page to the first, and vice-versa. The page
order runs from the first page, which has the most recent events, to the last page, which has the oldest events. The “ (Down)” key
is used to scroll from the first page to the following in increasing order, whereas the “ (Up)” key is used to scroll from the last page
to the previous pages.

Only the last 160 events are displayed in these pages.

The total number of pages and the number of the page currently displayed, as well as the number of events in the display, is shown
in the last row.

Treatment:

When accessing this screen for the first time, the most recent events are displayed. The “ (Down)” and “ (Up)” arrows are used
to scroll through the pages, as indicated above.

If new changes are registered whilst we are viewing the 1st page of this type of screen, the Display is refreshed accordingly and the
older changes are moved downwards.

When viewing any page other than the 1st page if new changes are registered, the Display will not be refreshed and the previous
data is shown. In such a case, a flashing, inverted video “NEW CHANGES” message is shown at the top of the page.

This indication is cleared when the most recent changes are viewed. To do so, we must go to the first screen.

Figure 202 Event Screen

Ingeteam Power Technology S.A.


User Manual 395
KEYBOARD AND GRAPHIC DISPLAY 

23.1.7 Protection event pages


The protection event screens display a chronological record of all the changes that take place in the signals that have been set as
such. Each protection event’s presentation includes the date and time to the millisecond, a 29 character text and a 7 character
acronym.

The texts to be displayed are defined in attributes of the CID. Signals are identified as protection events by means of the
corresponding enabling function in the corresponding settings node and by configuring the event masks. They can be modified
using the PC tool.

Figure 203 Protection event Screen

The screen order is defined chronologically. Their display order goes from the most recent to the oldest. Within each screen, the
most recent are shown at the top of the page and the oldest at the bottom (Figure 203). If the protection event list is empty, a text
indicating that the protection event queue is empty will appear.

We can scroll through the pages using the “ (Up),  (Down)” keys, going from the last page to the first, and vice-versa. The page
order runs from the first page, which has the most recent protection events, to the last page, which has the oldest protection
events. The “ (Down)” key is used to scroll from the first page to the following in increasing order, whereas the “ (Up)” key is
used to scroll from the last page to the previous pages.

Only the last 160 protection events are displayed in these pages.

The  (Enter) key is used to select the first protection event from the screen being viewed, whilst the “ (Up),  (Down)” keys are
used to scroll to the next protection event, with the following treatments:

❑ If, whilst at the bottom of the page, we press “ (Down)”, we are taken to the next page with the first selected
protection event, unless we are already viewing the last page, which case the display will not be changed.
❑ If we are in the protection event selected and we press “ (Up)” key, we are taken to the previous page, although
the last protection event remains activated, unless we are in the first page and in which case the display will remain
unchanged.
Once this protection event has been selected, we can press  (Enter) to view the page with the measurements associated to the
protection event. Use the “ (Up),  (Down)” keys to switch from one page to another if there is more than one measurements
page per protection event. These pages are browsed in a cyclical manner, going from the first to the last, and vice-versa, as
corresponds.

Use <ESC> to exit the screen displaying the measurements associated to the protection event. Within the protection events’
screen, the change is deselected by clicking on <ESC> once again.

The total number of pages and the number of the page is currently displayed, as well as the number of protection events in the
display’s queue, is shown in the last row.

Ingeteam Power Technology S.A.


User Manual 396
KEYBOARD AND GRAPHIC DISPLAY 

Treatment:

When accessing this screen for the first time, the most recent protection events are displayed.

The “ (Down)” and “ (Up)” arrows are used to scroll through the pages, as indicated above

If the appearance of new protection events is detected, a flashing, inverted video “NEW INC” (new protection event) message is
shown at the top of the page.

This indication is cleared when the latest protection events are viewed. To do so, no protection events must be selected and we
must go to the first screen. Once we have arrived at this screen, if we scroll back the first screen with the most recent protection
events to have been registered will be displayed.

23.1.8 Alarm pages


These screens emulate an alarm panel, displaying each alarm as a rectangle with a text inside. The page format is set and includes 2
columns containing 6 rectangles each. There will be a maximum of 15 alarm pages, i.e., a maximum of 180 alarms.

2 lines of 12 characters can be displayed within each rectangle. Each alarm’s texts, identification and the number of alarms are
configured using an external tool.

When in standby status, the text is displayed in a normal video with white background and, when enabled, in an inverted video
with a dark background.

When the alarm changes status, the signal’s text begins to flash and appears and disappears within the new status.

If the signal is invalid, the text will be displayed with a cross covering the entire rectangle. If the signal does not exist, the
corresponding alarm's gap will be displayed.

Use the “ (Up),  (Down)” keys to switch from page to another.

Individual acknowledgements of receipt are not issued for the alarms. Instead, it is possible to issue acknowledgement for all the
alarms displayed in the page that is being viewed. To do so, we must press  (Enter) in an active alarm page and the following
message will appear in a small screen:

Confirm receipt of all alarms of the page?

If we then press <ESC>, the message is cleared and no acknowledgment of the alarms is issued. If we press  (Enter), the message
disappears and an acknowledgment is issued for all the alarms displayed on the page.

An indication of the total pages and the number of the page displayed will appear at the top of the page.

Ingeteam Power Technology S.A.


User Manual 397
KEYBOARD AND GRAPHIC DISPLAY 

Figure 204 Alarm panel

23.1.9 Device status pages


The device status displays may differ depending on the model. Values may be referred to the primary or secondary.

NOTE: The measurements correspond to the fundamental frequency.

The different screens depending on the model samples of the device:

23.1.9.1 MDx, CDx, ZTx, CBx and BFx Models


There are 3 pages which describe the device status.

❑ Screen 1:
 Relay date and time.
 Frequency value.
 Type, module and angle of each of the unit’s 12 transformers.
❑ Screen 2:
 Direct, inverse and zero sequences of currents and voltages (module and angle).
 Total real, reactive and apparent power.
❑ Screen 3:
 Active table number (not available in CDx models).
 External power supply battery voltage.
 Phase and neutral thermal image value (only for MDx models).
 Restricted Earth value (only for MD0, MD2, TDx and LDx models).
 Maximeter value for each current and voltage phase (not available in CD0 model).
 Device temperature.
 Measures reactive power (only for CB model).
NOTE: The CD0 model only has a single screen with the following information:

 Relay date and time.


 External power supply battery voltage.

Ingeteam Power Technology S.A.


User Manual 398
KEYBOARD AND GRAPHIC DISPLAY 

 Device temperature.

Figure 205 Device Status page 1, page 2 and page 3

23.1.9.2 TDx Models


There are 5 pages which describe the device status.

❑ Screen 1:
 Relay date and time.
 Frequency value.
 Type, module and angle of each of the unit’s 12 transformers.
❑ Screen 2:
 Maximeter value for each current phase of each winding
 Maximeter value for each current and voltage in TD0 model
❑ Screen 3:
 Active table number (not available in CDx models).
 External power supply battery voltage.
 Phase and neutral thermal image value (only for MDx models).
 Restricted Earth value (only for MD0, MD2, TDx and LDx models).
 Maximeter value for each current and voltage phase (not available in CD0 model).
 Device temperature.
 Measures reactive power (only for CB model).
❑ Measurements screen (4)
 Differential measures
 Restraint measures
 Differential 2º harmonics measures.
 Restricted Earth values.
❑ Measurements screen (5)
 Direct, inverse and zero sequences of currents (module and angle) of each winding.
 Direct, inverse and zero sequences of voltages (module and angle) in TD0 model.

Ingeteam Power Technology S.A.


User Manual 399
KEYBOARD AND GRAPHIC DISPLAY 

 Total real, reactive and apparent power.

Figure 206 Device Status page 1, page 2 and page 3

Figure 207 Device Status page 4 and page 5

23.1.9.3 LDx Models


There are 5 pages which describe the device status.

❑ Measurements Screen 1:
 Relay date and time.
 Frequency value.
 Type, module and angle of each of the unit’s 12 transformers.
❑ Measurements screen 2
 Direct, inverse and zero sequences of currents and voltages (module and angle).

Ingeteam Power Technology S.A.


User Manual 400
KEYBOARD AND GRAPHIC DISPLAY 

 Total real, reactive and apparent power.


❑ Measurements Screen 3:
 Active table number.
 External power supply battery voltage.
 Phase and neutral thermal image value.
 Maximeter value for each current and voltage phase.
 Device temperature.
❑ Measurements screen (4) Figure 207
 Differential measures
 Restraint measures
 Differential 2º harmonics measures
 Restricted Earth values.
❑ Terminal Measurements screen (5)
 Synchronized measurements all terminals.

NOTE: The LD3 model does not have voltages and power.

Ingeteam Power Technology S.A.


User Manual 401
KEYBOARD AND GRAPHIC DISPLAY 

23.1.10 Fault pages


These pages display the last 20 fault reports filed by the protection.

These screens are divided into two levels. The first level displays a list of the most recent faults, as well as the fault number and the
fault trip date for each case (Figure 209). The total number of pages and the number of the page being displayed is shown at the
top, whilst the number of faults stored in the unit is shown in the last row.

If the fault list is empty, a text indicating that the fault queue is empty will appear (Figure 208).

The faults are ordered from the most recent or latest (Fault nº 1) to the oldest.

Figure 208 Empty fault list Figure 209 Fault list

The second level displays all the information related to the fault, organized in several pages. The page is displayed with the number
of the fault being displayed, as well as an indication of the number of the current page and the total number of pages per fault.

Use the “ (Up),  (Down)” keys to navigate through the first level screen. The page scroll is cyclical - when the end of the page is
reached we are taken to the next first level page and we are taken from the first page to the last page and vice-versa in accordance
with the key we press.

By pressing  (Enter), we access the second level of the selected fault. Use the “ (Up),  (Down)” keys to move between the
second level screens pertaining to a single fault. Use <ESC> to return to the first level page.

The values can refer to the primary or to the secondary. It is allowed to enable / disable the treatment to automatically display the
last fault on the display from the Configuration / Settings section of the display configuration tool.

Each screen’s content will be displayed as follows:

The contents of each screen may differ depending on the model, then the different possibilities:

23.1.10.1 MD, ZT, BC, BF and PB Models


There are 4 screens with data for each fault:

❑ Start Screen, which includes fault’s data.


 Date and time: Indicates the date in the “dd/mm/yy hh:mm:ss.ms” format. There are three dates:
 Start of the fault (first unit picked up).
 Trip (first unit tripped).
 End of fault (when the trip signal disappears).

Ingeteam Power Technology S.A.


User Manual 402
KEYBOARD AND GRAPHIC DISPLAY 

 Frequency in the moment of the fault.


 Pick up and trip types: Summary of the fault with the 3-letter code formed by combinations of the characters
A, B, C, N, NS and G (if tripped by a phase, neutral, sensitive neutral or ground), RTP (teleprotection), IF (phase
overcurrent), IN (neutral overcurrent), D (current unbalance), VO (zero-sequence overvoltage), HV
(overvoltage), LV (undervoltage), RTP (teleprotection), DT (transferred trip), DP (pole discordance), IT (thermal
image). Example: AC is a two-phase fault in phases A and C.
 Pick up type.
 Trip type.
 Distance: distance to the fault.
 Rf: resistance fault.
 LOC: locator code.
 Thermal image upon trip. The thermal image is indicated as a % of phases and neutral.
 Breaker. Indicates breaker monitoring data upon the fault:
 Open current. For each phase, indicates the current value upon the trip.
 Sigma ki. For each phase, indicates the sigma ki2 value.
❑ Fault screen, with the text “Fault information (I)”.
Figure 210 2nd level Fault Screens, page 1 and page 2

 Pre-fault and fault. Indicates the values measured before the fault and upon the fault. This screen displays the
following values:
 Transformer measurements <Trafos>. It indicates the measurement in the module and the angle of
each transformer.
 Restricted Earth value.
❑ Fault screen, with the text “Fault information (II)”.
 Pre-fault and fault. Indicates the values measured before the fault and upon the fault. This screen displays the
following values:
 Sequences. Indicates the measurements in the module and the angle of the current sequences (I0,
I1 and I2) and the voltage (V0, V1 and V2).
 Power. Indicates the measurements of the total real, reactive and apparent powers.
❑ Tripped units screen, displays the picked up and the tripped units.

Ingeteam Power Technology S.A.


User Manual 403
KEYBOARD AND GRAPHIC DISPLAY 

Figure 211 2nd level Fault Screens, page 3 and page 4

NOTE: only the first 7 picked up and tripped units are displayed. If the number is greater than 7, a text appears at the bottom of
the screen indicating that there are more picked up units.

23.1.10.2 TDx Models


There are 4 screens with data for each fault:

❑ Start Screen, which includes fault’s data.


 Date and time: Indicates the date in the “dd/mm/yy hh:mm:ss.ms” format. There are three dates:
 Start of the fault (first unit picked up).
 Trip (first unit tripped).
 End of fault (when the trip signal disappears).
 Frequency in the moment of the fault.
 Pick up and trip types: Summary of the fault with the 3-letter code formed by combinations of the characters
A, B, C, N, NS and G (if tripped by a phase, neutral, sensitive neutral or ground), DIF (differential), RG (restricted
earth), IF (phase overcurrent), IN (neutral overcurrent), D (current unbalance), VO (zero-sequence
overvoltage), HV (overvoltage), LV (undervoltage), v/f (overexcitation v/f), IT (thermal image). Example: AC is a
two-phase fault in phases A and C.
 Pick up type.
 Trip type.
 Thermal image upon trip. The thermal image is indicated as a % of phases and neutral of each winding.
❑ Fault screen, with the text “Fault information (I)”
 Breaker. Indicates breakers monitoring data upon the fault of each winding:
 Open current. For each phase, indicates the current value upon the trip.
 Sigma ki. For each phase, indicates the sigma ki2 value.

❑ Fault screen, with the text “Fault information (II)”.


 Pre-fault and fault. Indicates the values measured before the fault and upon the fault. This screen displays the
following values:
 Transformer measurements <Trafos>. It indicates the measurement in the module and the angle of
each transformer.

Ingeteam Power Technology S.A.


User Manual 404
KEYBOARD AND GRAPHIC DISPLAY 

Figure 212 2nd level Fault Screens, page 1, page 2 and page 3

❑ Fault screen, with the text “Fault information (III)”.


 Pre-fault and fault. Indicates the values measured before the fault and upon the fault. This screen displays the
following values:
 Differential current measure
 Restraint current measure
 Restricted Earth values.
❑ Fault screen, with the text “Fault information (IV)”.
 Pre-fault and fault. Indicates the values measured before the fault and upon the fault. This screen displays the
following values:
 Sequences. Indicates the measurements in the module and the angle of the current sequences (I0,
I1 and I2) of each winding.
 Sequences. Indicates the measurements in the module and the angle of the voltage (V0, V1 and V2)
in TD0 model.
 Power. Indicates the measurements of the total real, reactive and apparent powers.
❑ Tripped units screen, displays the picked up and the tripped units.
Figure 213 2nd level Fault Screens, page 4, page 5 and page 6

Ingeteam Power Technology S.A.


User Manual 405
KEYBOARD AND GRAPHIC DISPLAY 

23.1.10.3 LDx Models


There are 5 screens with data for each fault:

❑ 0Start Screen, which includes fault’s data.


 Date and time: Indicates the date in the “dd/mm/yy hh:mm:ss.ms” format. There are three dates:
 Start of the fault (first unit picked up).
 Trip (first unit tripped).
 End of fault (when the trip signal disappears).
 Frequency in the moment of the fault.
 Pick up and trip types: Summary of the fault with the 3-letter code formed by combinations of the characters
A, B, C, N, NS and G (if tripped by a phase, neutral, sensitive neutral or ground), DIF (differential), RG (restricted
earth), IF (phase overcurrent), IN (neutral overcurrent), D (current unbalance), VO (zero-sequence
overvoltage), HV (overvoltage), LV (undervoltage), v/f (overexcitation v/f), IT (thermal image). Example: AC is a
two-phase fault in phases A and C.
 Pick up type.
 Trip type.
 Distance: distance to the fault.
 Rf: resistance fault.
 LOC: locator code.
 Thermal image upon trip. The thermal image is indicated as a % of phases and neutral.
 Breaker. Indicates breaker monitoring data upon the fault:
 Open current. For each phase, indicates the current value upon the trip.
 Sigma ki. For each phase, indicates the sigma ki2 value.

❑ Fault screen, with the text “Fault information (I)”


 Pre-fault and fault. Indicates the values measured before the fault and upon the fault. This screen displays the
Transformer measurements <Trafos>. It indicates the measurement in the module and the angle of each
transformer.
❑ Fault screen, with the text “Fault information (II)”.
 Pre-fault and fault. Indicates the values measured before the fault and upon the fault. This screen displays the
following values:
 Sequences. Indicates the measurements in the module and the angle of the current sequences (I0,
I1 and I2) and the voltage (V0, V1 and V2).
 Power. Indicates the measurements of the total real, reactive and apparent powers.
❑ Fault screen, with the text “Fault information (III)”.
 Pre-fault and fault. Indicates the values measured before the fault and upon the fault. This screen displays the
following values: Differential current measure and Restraint current measure.
 Restricted Earth value.
❑ Tripped units screen, displays the picked up and the tripped units.

23.1.11 Measurement pages


There are 5 screens displaying the unit’s rms measurements referred to the primary (not available for devices without measure
module, for example CD0).

NOTE: Certain wiring diagrams have invalid measurements that do not exist. They are represented by “---“.

Ingeteam Power Technology S.A.


User Manual 406
KEYBOARD AND GRAPHIC DISPLAY 

❑ Measurements screen (I)


 Module and angle of each of the unit’s 8 transformers and phase to phase voltages.
❑ Measurements screen (II)
 Direct, inverse and zero sequences of currents and voltages (module).
 Frequency.
❑ Measurements screen (III)
 Power by real and reactive phase and apparent rms.
 Power factor per phase.
❑ Measurements screen (IV)
 Total real, reactive and apparent rms power.
 Total power factor.
 Real and Reactive Energy.
❑ Measurements screen (V)
 The harmonic distortion (%) of the 8 transformers’ measurements.

Ingeteam Power Technology S.A.


User Manual 407
KEYBOARD AND GRAPHIC DISPLAY 

Figure 214 Screen 1 Figure 215 Screen 2 Figure 216 Screen 3

Figure 217 Screen 4 Figure 218 Screen5

23.1.12 Menu to other screens page


This screen allows an access menu for the other types of screen that have not been given the consideration of main screens to be
displayed. We can group little-used screens within this screen and thus reduce the size of the main loop, making the movement
between those screens that are considered the most important quicker.

The content of this screen is set using the external configuration tool. Screens that are included in the main screen list cannot be
included in this menu.

The image below shows the following types of screen grouped in this screen: Events and Faults.

Ingeteam Power Technology S.A.


User Manual 408
KEYBOARD AND GRAPHIC DISPLAY 

Figure 219 Other screens

23.1.13 Shortcut menu page


This screen appears when we press “R”.

It contains those commands that can be given to the unit without having to enter a Password. The commands will vary in
accordance with the unit’s family.

Some examples are given below.


❑ Recloser command.
❑ Bank automatism command (for unit’s with a capacitor bank).
❑ .....
By pressing “R”, this page appears showing the first selected command. By clicking on the “ (Up),  (Down)” keys we can move
between the commands. By pressing “ (Enter)”, the selected command is run.

Figure 220 Quick access menu

Ingeteam Power Technology S.A.


User Manual 409
KEYBOARD AND GRAPHIC DISPLAY 

23.2 CONTROL AND PROTECTION MENUS PAGES

23.2.1 Operation of the menus


These screens enable us to view and modify the control and protection settings values. They consist of several levels of menus and
sub-menus.

23.2.1.1 Access to settings Menus


By pressing <MENU> from any of the other types of screen, a screen such as the one shown in Figure 230 will appear and
request that a password be entered.

Figure 221 Password request screen

We can access the menu pages with either viewing or modification permissions.

If we enter the correct password and press  (Enter), we will have permission to change settings. The “♦” symbol will appear in
the bottom left of the screen, as will the text “CHANGE SETTINGS”. However, if we press <ESC>, we will only be permitted to
consult the settings. Further more, a text indicating “VIEW SETTINGS” will be shown. The <ESC> key will function even when
some of the password’s numbers have been entered.

For more information, consult the point 4.2 of the Password Management section in this manual.

23.2.1.2 General operation


We can access the start menu screen by pressing <MENU> from any of the other pages described in the preceding paragraphs.
To exit the menus pages from the start page we must press <MENU> or <ESC>.

To move from a menu to a submenu we must select the menu that we want to explore and press  (Enter). To return to the
previous menu, we must press <ESC>. The <MENU> key enables us to return to the start menu from any submenu.

The  (Up),  (Down) keys can be used to change a menu's active line. If all the menu’s options can be displayed on the screen,
only the active line is changed when we change line. On the other hand, if not all of the menu’s options can be displayed on the
screen at the same time and the cursor is situated over the first or the last of the screen's menus, the menu will scroll up or
down, in accordance with the key used.

An indication of the number of the item selected from the total number of items in the menu on the screen currently displayed
is shown in the bottom right of the screen.

In the settings screens when a node does not exist in the cid an '*' before the text is displayed, indicating that the
node is disabled.

Ingeteam Power Technology S.A.


User Manual 410
KEYBOARD AND GRAPHIC DISPLAY 

The display change active table indicated by the following "(A)" the active table at that time.
Figure 222 Initial Settings Menu

23.2.1.3 Settings change operation


By pressing  (Enter) on an item from a settings menu screen that has no submenus, the settings changes screen will appear
(Figure 223). This screen displays the data corresponding to the first 6 settings. The selected setting can be modified using 
(Up),  (Down).

If all the node’s settings can be displayed on the screen, only the selected setting is changed when we change setting. On the
other hand, if not all of the menu’s options can be displayed on the screen at the same time and the cursor is situated over the
first or the last of the screen's settings, the settings will scroll up or down, in accordance with the key used. To return to the
menu screen, we must press <ESC>.

If the node is disabled, it is not allowed to modify settings and the display of the settings would be similar to the one you have
when entering the settings only mode. In the last row the text "DISABLED NODE" is displayed.

The following data can be seen on this screen:

❑ The following will appear at the top of the screen:


 Description of the settings node.
 Name of the settings node in IEC 61850.
 Current table (for settings which have the possibility of multiple tables).
 The number of the selected setting and the total number of the node’s settings.
❑ There are 3 lines for each setting, indicating the following:
 Description of the setting.
 Name of the setting in IEC 61850 and its corresponding value.
 New value of the setting. When this screen is accessed for the first time, the current value and the new value
coincide.
❑ The “VALIDATE PARAMETERS?” text appears in the last line. When selected and after pressing  (Enter), all the
changes to the screen's settings are validated. Until we press  (Enter) with the last line selected the changed
settings will not be validated.
❑ WARNING: If the user only has viewing permissions, the last line will not appear on the settings change screens.

Ingeteam Power Technology S.A.


User Manual 411
KEYBOARD AND GRAPHIC DISPLAY 

Figure 223 Settings change screen Figure 224 Setting Validated Screen

By pressing <ESC> after modifying a setting in the page, a confirmation message indicating that the user is about exit without
saving the settings in the CID appears:

Exit without changing settings?

Thus, by pressing  (Enter) we exit the screen and all the changes made so far in that menu are cleared. If we press <ESC> when
the message appears, we remain where we were.

By pressing  (Enter) after having modified one of the page's settings, another window appears. At this point, the user has 2
options:

❑ Wait until the CID modification process is completed with the new settings. At this point there are 3 possible
situations:
 If the modification is carried out successfully, a “Changing the settings OK” text will appear (Figure 224).
 If an error occurs during the CID modification process, an “Error in changing settings” text will appear.
 If a time out failure occurs whilst saving the modified settings, a “Time out in changing settings " message will
appear.
❑ Press  (Enter) and return to the settings change screen without the assurance of having modified the CID.

23.2.1.4 Settings Types


By pressing  (Enter) on one of the items that enables settings to be changed (the settings are text strings only be
displayed), and providing that the user has modification permissions, one of different types of small window will appear:

23.2.1.4.1 Option Type


By pressing  (Enter) on a setting of this type, a small window (Figure 225) displaying the following data appears:

❑ Setting name in IEC 61850.


❑ Setting description.
❑ Current setting value.
❑ New value of the setting. When this screen is accessed for the first time, the current value and the new value
coincide.
❑ The number of the current option from among the options available

Ingeteam Power Technology S.A.


User Manual 412
KEYBOARD AND GRAPHIC DISPLAY 

Using the  (Up),  (Down) keys, we can move through the different options in a circular manner, that is, when we reach
the last option we are returned to the first option. The selection option is chosen by pressing  (Enter). To exit without
selecting, press <ESC>.

Figure 225 Small screen for modifying OPTION type setting

23.2.1.4.2 Numeric Type


These can be changed using the numeric keys. The number is validated by pressing  (Enter), whilst <ESC> is used to cancel
and start again. The following data is displayed in each small window:

❑ Setting name in IEC 61850.


❑ Setting description.
❑ Current setting value.
❑ The setting’s new value. This field, which is empty, is where the value of the new setting entered via the keyboard
will be displayed.
❑ Maximum setting value.
❑ Minimum setting value.
❑ Setting step or increase.

The desired value is entered directly. The digits are entered from left to right. For example, to enter the number 2345, we
must successively press 2, 3, 4, 5,  (Enter).

The entered value is checked in order to ensure that it meets the maximum, minimum and step restrictions. Should it fail to
meet any of these restrictions, the “INVALID VALUE” text is shown. This text disappears when a number key is pressed.

There are 2 possibilities within this type, depending on the number, decimal or integer format.

Decimal: See Figure 226.

Integer: There are some integer type settings whose value is a signal number. In such cases, the “NOT DEFINED” text (Figure
228) indicates that this setting has no associated signal. If we wish to associate a signal, we must enter the desired signal
number with numeric keypad and press  (Enter).

Ingeteam Power Technology S.A.


User Manual 413
KEYBOARD AND GRAPHIC DISPLAY 

Figure 226 Small screen for modifying DECIMAL Figure 227 Small screen for modifying INTEGER Figure 228 Small screen for modifying INTEGER
type setting type setting type setting

23.2.1.4.3 Date Type


Equivalent to a numeric, although the numeric data entered are successively allocated in blocks of two to Day, month, year,
hour, minute, second. When the seconds have been entered, no further data can be entered until we have press  (Enter)
or <ESC> (the latter key deletes the data entered. If no data has been entered, we exit the settings modification). The
format displayed on the screen is: Day/Month/Year Hour:Min:sec

2 digits must always be entered for year, month and date. This means that in order to enter “1” we must enter “01”.

If the user enters an incorrect value, the last character entered can be deleted with the “” (Left) key.

To exit without saving any changes, press <ESC>.

Once the correct data have been entered, press  (Enter) to check that the values entered are valid. In the event of an
error, an “INCORRECT DATE” text will be shown. If the data are valid, no windows will be shown.

Figure 229 Unit date and time setting screen

Ingeteam Power Technology S.A.


User Manual 414
KEYBOARD AND GRAPHIC DISPLAY 

23.2.2 Password management

23.2.2.1 Changing the Settings Menu Password


The password may contain between 4 and 8 digits. The password is 1357 by default.

When we press a numeric key within the password screen, each keystroke will be considered part of the password and will be
indicated in the display with “*”. When we have entered between 4 and 8 characters and pressed "Enter", the data entered will
be validated against the unit’s password. If the password entered is incorrect, a warning text will be displayed.

Pressing <ESC> enables us to access the settings menus with viewing only permissions. If we enter the correct password we will
be able to view and modify. <ESC> will function even when certain of the password’s numbers have been entered, i.e., if we
press <ESC> while we are entering the password we will access the menu with viewing only permission.

The user can change the password, providing that he or she knows the former password.

You will be asked to type the password twice before changing it. The password numbers will appear hidden as they are entered
(the “*” will appear for each number entered). Once the first password has been entered, press  (Enter) and enter the second
password. Once the second password has been entered, press  (Enter) and the password will be changed (providing the two
passwords entered are the same). As with the numbers, they are entered from left to right.

Figure 230 Password modification screen

23.2.2.2 Changing FTP and SFTP Passwords


The FTP or SFTP password modification screen is accessed via the settings menu. This screen shows a virtual keyboard with
numbers from 0 to 9, the alphabet in uppercase and in lowercase.

Operation

❑ We must use the  (Up),  (Down),  (Left) and → (Right) keys to navigate around the virtual keyboard,
whilst  (Enter) is used to confirm the selected keyboard field.
❑ We must enter the old password and select the "Validate" field before finally pressing  (Enter).
❑ We must then enter the new password and select the "Validate" field before finally pressing  (Enter).
❑ A small window showing the result of the password modification (OK or the cause of the failure) will be
displayed.
If the user enters an incorrect value, must leave and enter the screen and start again.

Ingeteam Power Technology S.A.


User Manual 415
KEYBOARD AND GRAPHIC DISPLAY 

Figure 231 FTP Password modification screen

23.2.2.3 Commands management


23.2.2.3.1 Commands from the keyboard
There is a new settings menu within the Password screen to set the handling of commands from the keyboard. These
settings can only be changed from the display. There are 2 settings:

❑ Enabling key request to execute a command.


❑ Maximum time in which the entered password is valid, after this time you must enter the password again (time in
seconds).
Operation:

In graphic displays when you press the select key command the small screen that will ask the key display, after entering the
correct password will have some time to execute orders. After this time, the execution of orders will not be allowed. The
function keys have the same function.

The key settings menu and commands execution is the same, if you access the settings menu with the correct password will
be able to execute commands from the function keys without re-enter the password.

On the other hand, if you accessed the settings menu but only with permission from view settings, if you want to run a
command from the function keys will have to enter the password, same operation as if they were in a main menu screen.

23.2.2.3.2 PacFactory commands


From firmware version 6.1.18.5, the device implements the possibility of receiving remote control commands from the
pacFactory software tool as an alternative control channel to the telecontrol center.

The device considers the origin of these commands as "Remote" and applies the configured Local / Remote command
hierarchy.

For security reasons this functionality is disabled in the factory configuration and can only be enabled or disabled from the
local HMI of the device. It is not possible to modify the configuration by communications or from the pacFactory
configuration tool.

The function is configured by the setting "pacFactory Commands" ("YES": enabled / "NO": disabled).

If the device has this functionality enabled, the pacFactory configuration tool will detect it at the beginning of the
communication and enable an access to the command window in the "Tools -> Sending commands" menu.

Ingeteam Power Technology S.A.


User Manual 416
KEYBOARD AND GRAPHIC DISPLAY 

23.3 NETWORK CONFIGURATION

From the display it is possible to view and modify the network parameters of the equipment. For this there are a series Network
configuration menus.

Figure 232 Figure 233

The previous figures show 2 examples of possible situations:

❑ Figure 232 shows that the equipment has a network configuration with the 3 independent and enabled interfaces.
❑ Figure 233 shows that the device has a network configuration of ETH1 and ETH2 in Link Redundancy mode, and ETH1 has
been disabled.

23.3.1 Ethernet Configuration


❑ Ethernets Viewing
When accessing the data of an interface from the main menu of network configuration, a screen similar to Figure 234 will
be displayed, where the list of ips is presented, and 2 additional menus: Create new ips and enable or disable the interface
It is showing.

Figure 235 shows how the network interface, IP address, netmask, MAC address, and status link parameters are displayed
on the display, indicating whether the network cable is connected.

Depending on the configuration of the back ethernets the representation of some data of these interfaces varies:

ETH2 link: When a device is configured as a switch or link redundancy in the Network configuration screen on the ETH2
interface line, the text of Switch or Link Redundancy. The network parameters are the same as the ETH1 interface except
the link. For this reason, the ETH2 link status is displayed on the ETH1 screen.

Ingeteam Power Technology S.A.


User Manual 417
KEYBOARD AND GRAPHIC DISPLAY 

Figure 234 Figure 235 Figure 236

❑ Ips Editing
From the display screen (Figure 235) and having permissions to change settings by pressing the  (Enter) key, the screen in
Figure 237 shows the current data and a second row where you can enter the new values. Use the  (Up),  (Down) keys to
navigate the IP and MASK fields in a circular way, that is, when you reach the last, you return to the first one.

Figure 237 Ethernet parameters setting changes screen

To exit, press <ESC>.

Only the IP and MASK fields can be modified. If you want to change any of these fields, you must activate the special
mode keypad to do this, press the <MENU> key. For more information, consult the point 1.2.1 in this manual.

If the user enters an incorrect value, the last character entered can be deleted with the “” (Left) key.

Once the correct data have been entered, press  (Enter) to check that the values entered are valid. In the event of an
error, a small screen displaying the cause of the error will be shown.

❑ Ips Removing
From the ip display screen (Figure 235) you can delete the ip that is being displayed by pressing the (Left) key.

Ingeteam Power Technology S.A.


User Manual 418
KEYBOARD AND GRAPHIC DISPLAY 

❑ Creating new ips


Once on this screen (Figure 238) you can use the following keys:

 For information on how to enter the numbers, refer to the Functioning of the menus in this manual.
 The  (Left) key is used to delete the last entered value.
 The  (Up) and  (Down) keys to move between the IP line and the MASK line.
 The <ESC> key is used to exit the previous menu.
 The  (Enter) key is used to apply the change.
Figure 238 Figure 239

❑ Disabling / Enabling Ethernets


Once on this screen (Figure 240 and Figure 241) you can use the following keys:

 The  (Up),  (Down) and  (Left) keys to change the setting value.
 The <ESC> key is used to exit the previous menu.
 The  (Enter) key is used to apply the change.

Ingeteam Power Technology S.A.


User Manual 419
KEYBOARD AND GRAPHIC DISPLAY 

Figure 240 Figure 241

When an ethernet is disabled, all ips associated with that interface will be deleted. The DISABLED text will appear in the
Network Setup menu. If we access the menu of this interface will be shown the screen of Figure 242, with the ip 0.0.0.0.

If you want to enable again, change the setting to YES and then edit the IP1 to add the desired ip and mask

❑ Network configuration screen when there is a failure in the display configuration.


When there is a fault in the configuration of the display, there is the possibility to see the network configuration of the
equipment, pressing the  (Enter) key alternates the display of the error message and the screen with the network
configuration. The network configuration screen is shown below.

Figure 242

❑ Restore factory settings


At the end of the Network Configuration menu there is an option to restore the factory settings of the ethernets.

Ingeteam Power Technology S.A.


User Manual 420
KEYBOARD AND GRAPHIC DISPLAY 

23.3.2 Gateway Configuration


From the display it is also possible to view, add, modify and delete the gateways that are configured on the device. Up to 10
gateways can be configured, ONLY 1 of which can be a default gateway.

The following figures show the screens with the different interfaces for the unit’s network and gateways. We can see that a default
gateway with IP address 192.169.183.4 and a gateway with IP address 192.168.183.1 have been configured. The remaining
gateways have not been configured.

❑ Viewing a Gateway
If we select Gateway 2 and press  (Enter), the following screen appears (Figure 244) showing the Gateway’s data values
and a legend at the bottom with the different options available to the user.

Figure 243 Network Configuration Figure 244 Gateway display screen Figure 245 Default Gateway edition screen

If we select Gateway 1 and press  (Enter), the default gateway screen appears (Figure 245).

❑ Editing or creating a Gateway


If we press  (Enter) in the Gateway configuration screen and we have permission to change settings (having entered the
correct password into the password screen), the Gateway edition and creation screen will appear with the current data and
a second row into which the new values can be entered.

The following situations may arise when configuring a Gateway:

❑ Gateway Not Configured


 To add a default Gateway, we only have to complete the GATEWAY field (the Gateway IP address) and press 
(Enter). If not, an error will occur.
 To add a Gateway with a specific network destination, we must complete the 3 fields and press  (Enter). If
not, an error will occur.
❑ Gateway Configured
 To edit a default Gateway (Figure 245), we only have to modify the GATEWAY field (the Gateway’s IP address)
and, once the desired value has been entered, press  (Enter) for the change to become effective.
 To edit a Gateway with a specific network destination, we change the desired parameter(s) and press 
(Enter). Any parameters that are not modified will retain the current values.

To add a new Gateway, select a non-configured gateway, for example Gateway 3, and press  (Enter).

This screen shows the values of the Gateway’s 3 fields as non-configured. In such a case, we can only exit or edit (add) the
Gateway. By pressing  (Enter) again, the Gateway edition/creation screen will be displayed.

Ingeteam Power Technology S.A.


User Manual 421
KEYBOARD AND GRAPHIC DISPLAY 

The  (Up),  (Down) keys are used to move between destination IP address, destination network mask and the Gateway IP
address fields in a circular manner. This is not possible in the default Gateway, which has a single editable field.

If the user enters an incorrect value, the last character entered can be deleted with the “” (Left) key.

To exit without saving any changes, press <ESC>.

If we want to enter the Gateway with the destination IP 10.15.1.6, Gateway mask 255.255.255.255 and Gateway IP address
192.168.182.252, you must activate the special mode keypad to do this, press the <MENU> key. For more
information, consult the point 1.2.1 in this manual.

Once the correct data have been entered, press  (Enter) to check that the values entered are valid. In the event of an
error, a small screen displaying the cause of the error will be shown.

The screen will display the new configuration and the new Gateway introduced.

NOTE: If a default Gateway is configured, the last Gateway will ALWAYS be displayed, even if more gateways with a specific
network destination are added.

Figure 246 Gateway parameters setting changes screen

❑ Deleting a Gateway
If we press the “” (Left) key in the Gateway configuration screen and we have permission to change settings (having
entered the correct password into the password screen), the Gateway that is being displayed will be deleted.

Ingeteam Power Technology S.A.


User Manual 422
KEYBOARD AND GRAPHIC DISPLAY 

23.4 OTHER SCREENS

23.4.1 Contrast setting


To access the contrast setting screen we must press “0” and “9” at the same time in a screen that is not within the unit's settings
menu. Once we have pressed these two keys, the following image will appear in the display:

Figure 247 Contrast setting screen

If we then press  (Up) the contrast’s intensity will increase, and if we press  (Down), the intensity will decrease. To exit this
screen, press  (Enter).

23.4.2 USB treatment


When the user inserts a USB key, a small window will appear in the display indicating that a USB device has been detected and the
USB treatment will begin.

Figure 248 USB detected Figure 249 Remove the USB device

Ingeteam Power Technology S.A.


User Manual 423
KEYBOARD AND GRAPHIC DISPLAY 

Once the treatment has terminated, the following window will appear in the display indicating that we can remove the USB device.

NOTE: If the USB device is not removed within 5 seconds, the small screen will disappear and the display will return to the previous
screen.

Added a new menu of settings in the Password screen to set the USB treatment, this setting can only be changed from the display.
The setting will have 3 possible values:

❑ Disabled: The USB treatment is not available.


❑ With password: The USB treatment is available but needs the introduction of the key settings menu.
❑ Without password: The USB treatment is available without having to enter the password.

23.4.3 System Information


In this menu the information concerning Product Information and detailed version of the device.

The content of each submenu is:

❑ Product information: commercial computer code and the serial number of the CPU is displayed.
❑ Device versions:
 Versions of the CPU and the boards of the device are displayed.
 Sampled values firmware version. Only in models with sampled values modules.
 Micros expansion boards versions (CPU and HMI).
 Logic and CID versions.
❑ Last updates: last 18 updates are shown, for each update there is a record with the following data:
 Date and time of the update.
 Filename update.
 Result of the update.
❑ Last CIDs loaded: The display will show the latest cids loaded from the device boots where the following
information is displayed:
 Date and time.
 Cid name.
 Result validation.

Ingeteam Power Technology S.A.


User Manual 424
KEYBOARD AND GRAPHIC DISPLAY 

23.4.4 CID validation


Messages relating to the receipt and processing of a new CID on the device are displayed in a small window, the operation is as
follows:

❑ After a new CID give the device a small window indicating that you are validating the CID is displayed. Throughout
the process of validation when any key is pressed, the window disappears and you can access the different
menus display.
❑ Once the validation process resulting CID (CID Validated / CID unvalidated) is indicated in a new window, which will
remain on the display until you press any key or two minutes have elapsed.
Messages received new setting display is visualized between the windows and the window CID validating the result.

23.4.5 Security Logs


Are available which record user actions from the keyboard / display, such as:

❑ if the password setting menu or the key is modified FTP


❑ If the password is correct or incorrect
❑ Whether to enable / disable Enabling Ethernet ports
❑ If there is a change in the network configuration

23.4.6 Test Screens


There are 2 test screens on your device for digital outputs and programmable LEDs. To enter these screens need to have entered
the correct password to enter the settings menu.

The output test screen is in the Setup menu of GGIO cards. It defines the different cards and display equipment shown to modify
the time setting output activation.

Once access to one of the cards all outputs and the corresponding connection is. To activate the desired output is only necessary to
select and press  (Enter).

Pressing  (Up) or  (Down), keys allow to select different outputs. To return to the previous menu, press the '<ESC> key.

Ingeteam Power Technology S.A.


User Manual 425
KEYBOARD AND GRAPHIC DISPLAY 

Figure 250 Digital Output Test Figure 251 GGIO1 Test Figure 252 Leds Test

The LED screen test is in the I/O/Leds configuration menu.

To activate the desired LED is only necessary to select and press  (Enter) key. Pressing  (Up) or  (Down), keys allow to select
different led. To return to the previous menu, press the '<ESC> key.

23.4.7 Other Communications Menu Screens


The following submenus are available within the Communications menu:
❑ Network Configuration: mentioned in its corresponding section.
❑ PRP / HSR / Sw configuration: the ethernet corresponding to PRP, HSR or switch is configured (only available in models
with redundancy module PRP/HSR/Switch mode).
❑ Process Bus: shows the information of ethernets 3 and 4 if they are available (only available in models with sampled
values subscriptions).
❑ Communications protocols: a series of slave / server and master protocols are available depending on the model of the
equipment.

Ingeteam Power Technology S.A.


User Manual 426
WEB APPLICATION 

24. WEB APPLICATION

24.1 INTRODUCTION

This document describes the features and capabilities of the Web Application, which is supplied within the firmware and allows to set
up and monitor the target IED.

The Web Application has been built in order to be responsive, HTML5 and CSS3 compliant and as lightweight as possible. It is supported
by the following browsers and versions:

❑ Google Chrome version 40.0.2214 or higher.


❑ Mozilla Firefox version 35.0.1 or higher.
❑ Internet Explorer version 10 or higher.

24.2 WEB APPLICATION LOGIN

First, the IP address of the IED must be entered into the browser's address bar in order to load the login page, i.e.: http://100.0.0.1.

24.2.1 Login
The login page needs a username and its password to login.

There are two users defined by default: a management user and a read-only user. The main difference between them is that
management user is able to modify parameters while read-only user is not. However, when a user with management permissions
logs in, it is asked whether he would like to login with management permissions or with read-only permissions. The corresponding
user name and passwords are the following by default:

Management user: user name admin and password modifica.

Read-only user: user name consulta and password consulta.

Ingeteam Power Technology S.A.


Manual de usuario 427
WEB APPLICATION 

When a management user tries to login, if there is already a management user logged in, the new user will be asked whether to log
in as read-only user or throw away already logged user.

Once the login has been successful the web page starts to load several tabs described below.

24.3 TABS

The main tabs are the following:

❑ Reports
❑ Settings
❑ Maintenance
❑ SW/Configuration
❑ Logout

24.3.1 Reports
The following subtabs are displayed in this tab:

❑ Status
❑ Events

24.3.1.1 Status
In the Status tab real-time information about measures and signals is shown. It is possible to read this information periodically or
each time the read button is clicked.

In the Measurements menu, the main measures taken in the secondary are shown.

Ingeteam Power Technology S.A.


Manual de usuario 428
WEB APPLICATION 

In the Signals menu, the most important signals regarding IED status, protection units, input and outputs status, etc. are shown.

Ingeteam Power Technology S.A.


Manual de usuario 429
WEB APPLICATION 

24.3.1.2 Events
In this tab, the list of events recorded by the IED can be displayed and a compressed file with all the events can be downloaded.

Ingeteam Power Technology S.A.


Manual de usuario 430
WEB APPLICATION 

24.3.2 Settings
In this tab, it is possible to read and change the settings of the IED.

The settings are arranged in menus regarding their functionality and they are read from the IED according to these menus. At the
bottom of the page there are three buttons in order to read settings, erase changes and send changes to the IED.

The settings are displayed as tables where the first column is the description of the setting, the second column is its value in the IED
and the last column is its value in the web. The background color of each setting's row changes according to its value. If the value in
the IED and the value in the web do not match the background will turn into yellow. On the other hand, if the value in the web is
not valid the background will turn into red.

In addition, it is possible to change the active table and view the value of each setting for every table.

Ingeteam Power Technology S.A.


Manual de usuario 431
WEB APPLICATION 

24.3.3 Maintenance
This tab contains the following tabs:

❑ Communications
❑ Users

24.3.3.1 Communications
The following menus are available:

❑ Synchronization. It is possible to synchronize the IED with the desired date and time.
❑ IP Network configuration. It allows to configure the IED's IP addresses and static routes configuration
❑ IP Network Tools. It is possible to execute a ping command from the IED and view IED's actual IP configuration and
routing tables.

Ingeteam Power Technology S.A.


Manual de usuario 432
WEB APPLICATION 

24.3.3.2 Users
In this tab, detailed information about current active sessions logged into the web is shown.

Additionally, it is possible to change username and password.

24.3.4 SW/Configuration
The SW/Configuration tab contains the following tabs:

❑ Configuration

24.3.4.1 Configuration
In this tab it is possible to load the configuration file.

Ingeteam Power Technology S.A.


Manual de usuario 433
WEB APPLICATION 

24.3.5 Logout
This tab is to end the session in the web.

Ingeteam Power Technology S.A.


Manual de usuario 434
DNP PROTOCOL 

25. DNP PROTOCOL

25.1 INTRODUCTION

The device provides a DNP interface to act as RTU and to communicate with a DNP master (for example a remote control station).

The communication can be selected for a serial line or via Ethernet, using encapsulation by means of the TCP/IP protocol.

Below are described the following topics:

❑ Protocol configuration settings


❑ Protocol configuration tables for digital signals, measurements, counters and commands (which are configured with the
software configuration tool)
❑ Implemented Device Profile and object table.

25.2 CONFIGURATION SETTINGS

The protocol has the following configuration settings:

❑ Enable protocol:
 Yes
 No
❑ Slave address: DNP slave address of the device. Value between 0 and 65532.
❑ Master address: DNP master address of the master device. Value between 0 and 65532.
❑ Port Number: This setting enables the selection between the available communication channels:
 Disable
 COM1
 COM2
 COM3
 COM4
 COM5
 COM6
 Ethernet 1
 Ethernet2
❑ Comm speed (bauds): This setting enables the selection of the serial baud rate.
 600 baud
 1200 baud
 2400 baud
 4800 baud
 9600 baud
 19200 baud
 38400 baud
 57600 baud

Ingeteam Power Technology S.A.


Manual de usuario 435
DNP PROTOCOL 

❑ Parity: Enables the selection of the parity type to be used in transmission. The recommended default value is 0 (without
parity), as indicated by the DNP protocol.
 None
 Even
 Odd
❑ Number of Stop bits: Enables the selection of the number of stop bits.
 1 Bit
 2 Bit
❑ Communication control: Enables de selection of the communication control type.
 Normal
 Fixed + DCD
 RTS
 RTS+CTS
 RTS+CTS+DCD
 RS485
❑ Min. respond delay (ms): Waiting time for the activation of the RTS and the transmission of a message after the reception
of a message. Value between 0 and 1000.
❑ CTS max delay (ms): Waiting time for the CTS activation after the RTS activation. Value between 0 and 1000.
❑ Carrier stabilization (ms): Waiting time for the transmission of the message after the CTS detection in order to allow the
carrier stabilization. Value between 0 and 1000.
❑ RTS drop-off time (ms): Waiting time for the RTS deactivation after the message last byte transmission.
❑ ACK delay time(ms): Timeout for Link Confirm. Value between 0 and 1000.
❑ Need time delay (m): Waiting time in minutes that must elapse before the validity of the clock is checked after receiving a
synchronization or start up message. If it is invalid, synchronization is requested to the master. Value between 0 and 10.
❑ Permission to synchronize: Synchronization permission from control centre.
 Yes
 No
It is used to configure the synchronization source when there are several available.

❑ Local time offset (h): Local offset for the time.


❑ Communication fail T.(min): Waiting time in minutes without receiving any valid measure before indicate communication
failure. Value between 0 and 10000 minutes.
❑ Data link confirm: Indicates if confirm is requested at the connection level. The value must be set to NO for TCP/IP.
 NO
 YES
❑ Max. App Fragment Size: Maximum number of bytes in an application message. Value between 512 and 3072.
❑ Freeze time counters: : Indicates if the counters are frozen with or without time. Only acts when zero variation is
requested.
 NO
 YES
❑ Default Status: Indicates whether the digital signal objects, measurements and counters are sent with status or without
status in messages sent in response to requests in which variation is not specified. Also valid for responses to class 0
requests. The bits have the following meanings:

Ingeteam Power Technology S.A.


Manual de usuario 436
DNP PROTOCOL 

Bit Value
0 Send all with status
1 Send digitals with status
2 Send measurements with status
3 Send counters with status
4 Send frozen counters with status

Bin. output status default: Indicates whether the reply message to a class 0 data request also includes the object corresponding to the
binary outputs with status.

 NO
 YES
❑ Analog output status def.: Indicates whether the reply message to a class 0 data request also includes the object
corresponding to the analog outputs with status.
 NO
 YES
❑ Frozen Counters status def.: Indicates whether the reply message to a class 0 data request also includes the object
corresponding to the frozen counters with status.
 NO
 SI
❑ Analog input bits default: Indicates the default value for the "Var" field in the analog objects when no variation is
requested.
 16 Bits
 32 Bits
 Short floating point
❑ Normalized: Indicates the analog format.
 Secondary.
 Normalized.
 Primary. (Not operative in the current version, if used, the device configures Normalized)
❑ Counter bits default: Indicates the default value for the "Var" field in the counter objects when no variation is requested.
 16 Bits
 32 Bits
❑ Enable unsolicited: Enables the use of unsolicited responses with class 1, 2 o 3.
 NO
 YES
❑ Enable collision avoidance: Enables the collision avoidance detection with DCD method.
 NO
 YES
❑ Fixed Unsolicited T.out (ms): Fixed waiting time before transmitting an unsolicited response. Value between 0 and 5000.
❑ Variable Unsolicited T.out (ms): Variable waiting time additional to the previous setting of fixed time. The value options
are :

Ingeteam Power Technology S.A.


Manual de usuario 437
DNP PROTOCOL 

Setting Value Time in ms


0 255
1 127
2 63
3 31
4 15
5 7
6 3
7 1

❑ Unsolicited Repeat T.out (s): Waiting time in seconds before a retransmission of an unsolicited response when there is
not a link or application acknowledge to the previous message. Value between 0 and 630 seconds.
❑ Max.number rep. without solic.: Maximum number of retransmission of an unsolicited response. Value between 0 and
65535. Infinite for value 0.
❑ Special operations: Enables the activation of certain operational characteristics.

Bit Bit indication at 1


0 Dispatch of current counters with OBJ = 21
1 Reserve
2 Dispatch of unsolicited responses up to the IIN included each 10 seconds
3 Reserve
4 Reserve
5 Reserve
6 Restart message not sent on start up

❑ Change wait time (s): Waiting time for the SOE in the internal queue before processing the events. It is only necessary if
there are data from different IEDs in order to sort them chronologically.
❑ TCP Listen Port: TCP port used as server.
❑ Unsolicited react. delay (s): The waiting time to retry again the maximum number of retries an unsolicited message. Value
between 0 and 3600 seconds. Zero does not apply.
❑ Command selection time (ms): The waiting time to abort the selection command. Value between 100 and 15000
miliseconds. Default 15000.
❑ Max command wait time (ms): The maximum time waiting the protocol to the result of the command before responding
to the master. If expired is indicated “Not supported” Default 0.
❑ Enable T.correct.buf.events: True value performs the correction date all still digital events queues when the first
syncrhronization is received. The device does not answer with digital events since the first synchronization. Default No.

The configuration settings for the first DNP are in the GEN\DNPITCP1 node IEC 61850 data model, as detailed in the following
table:

Ingeteam Power Technology S.A.


Manual de usuario 438
DNP PROTOCOL 

Table 229 DNP protocol settings

Data Setting Minimum Maximum Step Remarks Type


ProtEna Enable protocol NO/YES Boolean
Slave Slave address 0 65532 1 Int32
Master Master address 0 65532 1 Int32
Disable
COM1
COM2
COM3
Port Port Number COM4 Enum
COM5
COM6
Ethernet 1
Ethernet2
600 baud
1200 baud
2400 baud
4800 baud
Speed Comm speed (bauds) Enum
9600 baud
19200 baud
38400 baud
57600 baud
Parity Parity None, Even, Odd Enum
Stopbit Number of Stop bits 1Bit, 2 Bit Enum
Normal
Fixed + DCD
RTS
RtsType Communication control Enum
RTS+CTS
RTS+CTS+DCD
RS485
RtsTmms Min. respond delay(ms) 0 1000 10 Int32
CtsTmms CTS max delay (ms) 0 1000 10 Int32
CarTmms Carrier stabilization (ms) 0 1000 10 Int32
RtsOffTmms RTS drop-off time (ms) 0 1000 1 Int32
AckTmms ACK delay time(ms) 100 10000 10 Int32
SynDl Need time delay(m) 0 10 1 Int32
SynEna Permission to synchronize NO/YES Boolean
SynOfs Local time offset(h) -12 12 1 Int32
ComFailTm Communication fail T.(min) 0 10000 1 Int32
LinkAck Data link confirm NO/YES Boolean
MaxAppSize Max. App Fragment Size 512 3072 256 Int32
FrzCnt Freeze time counters NO/YES Boolean
StDefault Default status 0 31 1 Meaning of bits (1) Int32
BinOutSt Bin. output status default NO/YES Boolean
AnOutSt Analog output status def. NO/YES Boolean
FrCntSt Frozen Counters status def. NO/YES Boolean
16 Bits
AnInBits Analog input bits default 32 Bits Enum
Short floating point
Primary, Normalized
Normalized Normalized Enum
Secondary
CntBits Counter bits default 16 Bits, 32 Bits Enum
UnSolEna Enable unsolicited NO/YES Boolean
CollEna Enable collision avoidance NO/YES Boolean
FixedTmms Fixed Unsolicit.Timeout (ms) 0 5000 10 Int32
255, 127, 63, 31, 15, 7,
VarTmms Var. Unsolicit. Timeout (ms) Enum
3, 1
UnSolTmms Unsolicit. Repeat T.out (s) 0 630 1 Int32
UnSolMaxR Max.number rep. without solic. 0 65535 1 Int32
SpecialBeh Special operations 0 255 1 Int32
CambTms Change wait time (s) 0 20 1 Int32
TcpPort TCP Listen Port 0 65535 1 Int32

Ingeteam Power Technology S.A.


Manual de usuario 439
DNP PROTOCOL 

ReacTms Unsolicited react. delay (s) 0 3600 1 Int32


TselecTmms Command selection time (ms) 100 15000 10 Int32
TOWaitTmms Max command wait time (ms) 0 1000 10 Int32
FixSynEna Enable T.correct.buf.events 0 1 1 Boolean
Where:

Meaning of bits (1) Bit Value


Send all with status 0 YES/NO
Send digitals with status 1 YES/NO
Send measurements with status 2 YES/NO
Send counters with status 3 YES/NO
Send frozen counters with status 4 YES/NO

25.3 TABLES

There are 4 tables to configure the list of digital status (binary inputs), analogs, counters and commands.

25.3.1 Digital status table


For each element the following fields must be configured*:

❑ Type: Type of signal.


 Simple.
❑ DNP Signal: Signal number with respect to the DNP protocol. Values from 0 to 4093. It should start at 0 and gaps
are not allowed.
❑ CIN: Signal incidence code:
 SP→ Value change in simple signaling
❑ InternalIED: IED of the signal. Value 0 corresponds to the device itself.
❑ Internal ID: Internal signal number that identifies the element inside the device.
❑ Class: Default class assigned to the signal. With value 0 the signal does not cause changes.
 Class 0
 Class 1
 Class 2
 Class 3
❑ Time: Time format for changes.
 Without time
 Absolute time
 Relative time
❑ Inverted: Indicates if the signal status is inverted. By default is not inverted.
 Not inverted
 Inverted
*The protocol configurator allows other non-operational options in this version.

25.3.2 Analog values table


For each element the following fields must be configured:

❑ DNP signal: DNP analog number. Values between 0 and 1023. Gaps are allowed.

Ingeteam Power Technology S.A.


Manual de usuario 440
DNP PROTOCOL 

❑ Internal IED: IED of the analog value. Value 0 corresponds to the device itself.
❑ Internal ID: Internal analog number that identifies the element inside the device. Selectable from a list.
❑ Class: Class assigned to the analog value. With value 0 the analog value does not cause events.
 Class 0
 Class 1
 Class 2
 Class 3
❑ Dead band: Absolute variation value to cause an event. Values between 0 and 10000. It is applied over the value
stored in 16 bits.
❑ Dec: Number of decimal places for the analog value when the setting “Normalizado” is set to Primary or Secondary.
(Factor of 10 raised to the number of decimal). Values between 0 to 4. At value 0, the value is sent without
modifications.
❑ Limit scale: Full scale used when the setting “Normalizado” takes the Normalized value. It is the value that causes
32767 to be sent in DNP.
❑ The deadband is defined as the value that the analog value must vary to be sent as a event. It is always applied on
the current value of the measure to be sent.

When the analog values are to be sent, the current value is compared to the last sent value and if the difference is greater than
the DeadBand the current value is transmitted. A zero value does not generate any events.

25.3.3 Counters table

For each element the following fields must be configured:

❑ DNP signal: DNP counter number. Values between 0 and 63. Gaps are allowed.
❑ Internal IED: IED of the counter value. Value 0 corresponds to the device itself.
❑ Internal ID: Internal counter number that identifies the element inside the device. Selectable from a list.
❑ Class: Class assigned to the counter. With value 0 the counter value does not cause changes.
 Class 0
 Class 1
 Class 2
 Class 3
❑ Dead band: Absolute variation value to cause an event. Values between 0 and 10000.

25.3.4 Commands table


For each element the following fields must be configured:

Fields that are expected to be received in the DNP command message:

❑ DNP command: DNP command number. Values between 0 and 255.


❑ Op type: DNP command value.
 TRIP

Ingeteam Power Technology S.A.


Manual de usuario 441
DNP PROTOCOL 

 CLOSE
 Latch ON
 Latch OFF
 Pulse ON
 Pulse OFF (deprecated)
❑ Comand type:
 All. All types supported.
 SBO. Only Selec Before Operate supported.
 DO. OnlyDirect operate supported.
Order configuration fields on the device itself:

❑ Internal IED: IED of the command. Value 0 corresponds to the device itself.
❑ Internal ID: Internal counter number that identifies the element inside the device. Selectable from a list. The
internal value is affected by the next field.
❑ ON_OFF: Internal command value. Use to select Internal ID.
 ON
 OFF
❑ Origin:
 Bay Control
 Station Control
 Remote Control
 Automatic Bay
 Automatic Station
 Automatic Remote
 Maintenance
 Process

Only one command is accepted in each message, count = 1. The On Time and Off Time fields are not used.

Ingeteam Power Technology S.A.


Manual de usuario 442
DNP PROTOCOL 

25.4 DEVICE PROFILE

DEVICE PROFILE DOCUMENT


Vendor Name: INGETEAM S.A.
Device Name: INGEPAC EF
Highest DNP Level Supported:
Device Function:
For Requests Level 3
 Master  Slave
For Responses Level 3
Notable objects, functions, and/or qualifiers supported in addition to the Highest DNP Levels Supported (the complete list is described in the
attached table):
Maximum Data Link Frame Size (octets): Maximum Application Fragment Size (octets):
Transmitted 292 Transmitted 1024< >3072( configurable)
Received 292 Received 1024
Maximum Data Link Re-tries:
Maximum Application Layer Re-tries:
 None
 None
 Fixed at 1
 Configurable, range ____ to ____
 Configurable, range __ to __
Requires Data Link Layer Confirmation:
 Never
 Always
 Sometimes
 Configurable
Requires Application Layer Confirmation:
 When reporting Event Data
 When sending multi-fragment responses
Timeouts while waiting for:
Data Link Confirm  None  Fixed at _________  Variable  Configurable
Complete Appl. Fragment  None  Fixed at _________  Variable  Configurable
Application Confirm  None  Fixed at __10 sg____  Variable  Configurable
Complete Appl. Response  None  Fixed at _________  Variable  Configurable
Others
Sends/Executes Control Operations:
WRITE Binary Outputs  Never  Always  Sometimes  Configurable
SELECT/OPERATE  Never  Always  Sometimes  Configurable
DIRECT OPERATE  Never  Always  Sometimes  Configurable
DIRECT OPERATE – NO ACK Never  Always  Sometimes  Configurable
Count > 1  Never  Always  Sometimes  Configurable
Pulse On  Never  Always  Sometimes  Configurable
Pulse Off  Never  Always  Sometimes  Configurable
Latch On  Never  Always  Sometimes  Configurable
Latch Off  Never  Always  Sometimes  Configurable
Queue  Never  Always  Sometimes  Configurable
Clear Queue  Never  Always  Sometimes  Configurable

Reports Binary Input Change Events when no specific variation Reports time-tagged Binary Input Change Events when no specific
requested: variation requested:
 Never  Never
 Only time-tagged  Binary Input Change With Time
 Only non-time-tagged  Binary Input Change With Relative Time
 Configurable to send both, one or the other (attach explanation)  Configurable (attach explanation)
Sends Unsolicited Responses:
 Never Sends Static Data in Unsolicited Responses:
 Configurable (attach explanation)  Never
 Only certain objects  When Device Restarts
 Sometimes (attach explanation)  When Status Flags Change
 ENABLE/DISABLE UNSOLICITED
Function codes supported
Supports Collision Avoidance: Configurable Collision Avoidance Detection Method: DCD
Default Counter Object/Variation: Counters Roll Over at:
 No Counters Reported  No Counters Reported
 Configurable (attach explanation)  Configurable (attach explanation)
 Default Object _________  16 Bits
Default Variation ______  32 Bits
 Point-by-point list attached  Other Value _____________

Ingeteam Power Technology S.A.


Manual de usuario 443
DNP PROTOCOL 

 Point-by-point list attached


Sends Multi-Fragment Responses:  Yes  No

25.4.1 OBJECT TABLE


REQUEST RESPONSE
OBJECT
(slave must parse) (master must parse)
Func Codes Qual Codes Func Codes
Obj Var Description Qual Codes (hex)
(dec) (hex) (dec)
1 0 Binary Input – All Variations 1,22 00,01,06
1 1 Binary Input 1 00,01,06 129 00,01
1 2 Binary Input with Status 1 00,01,06 129 00,01
2 0 Binary Input Change - All Variations 1 06,07,08
2 1 Binary Input Change without Time 1 06,07,08 129, 130 28
2 2 Binary Input Change with Time 1 06,07,08 129, 130 28
2 3 Binary Input Change with Relative Time 1 06,07,08 129, 130 28
10 0 Binary Output - All Variations 1 00,01,06
10 2 Binary Output Status 1 00,01,06 129 00,01
12 1 Control Relay Output Block 3, 4, 5, 6 17, 28 129 Echo of request
1, 7, 8, 9,
20 0 Binary Counter - All Variations 00,01,06
10,22
1, 7, 8, 9,
20 1 32-Bit Binary Counter 00,01,06 129 00,01
10
1, 7, 8, 9,
20 2 16-Bit Binary Counter 00,01,06 129 00,01
10
20 3 32-Bit Delta Counter 1 00,01,06 129 00,01
20 4 16-Bit Delta Counter 1 00,01,06 129 00,01
20 5 32-Bit Binary Counter without Flag 1 00,01,06 129 00, 01
20 6 16-Bit Binary Counter without Flag 1 00,01,06 129 00, 01
20 7 32-Bit Delta Counter without Flag 1 00,01,06 129 00,01
20 8 16-Bit Delta Counter without Flag 1 00,01,06 129 00,01
21 0 Frozen Counters - All Variations 1, 22 00,01,06
21 1 32-Bit Frozen Counter 1 00,01,06 129 00,01
21 2 16-Bit Frozen Counter 1 00,01,06 129 00,01
21 3 32-Bit Frozen Delta Counter 1 00,01,06 129 00,01
21 4 16-Bit Frozen Delta Counter 1 00,01,06 129 00,01
21 5 32-Bit Frozen Counter with Time of Freeze 1 00,01,06 129 00, 01
21 6 16-Bit Frozen Counter with Time of Freeze 1 00,01,06 129 00, 01
32-Bit Frozen Delta Counter with Time of
21 7 1 00,01,06 129 00,01
Freeze
16-Bit Frozen Delta Counter with Time of
21 8 1 00,01,06 129 00,01
Freeze
21 9 32-Bit Frozen Counter without Flag 1 00,01,06 129 00,01
21 10 16-Bit Frozen Counter without Flag 1 00,01,06 129 00,01
21 11 32-Bit Frozen Delta Counter without Flag 1 00,01,06 129 00,01
21 12 16-Bit Frozen Delta Counter without Flag 1 00,01,06 129 00,01
22 0 Counter Change Event – All Variations 1 06,07,08

22 1 32-Bit Counter Change Event without Time 1 06,07,08 129, 130 28

22 2 16-Bit Counter Change Event without Time 1 06,07,08 129, 130 28


32-Bit Delta Counter Change Event without
22 3 1 06, 07, 08 129 28
Time
16-Bit Delta Counter Change Event without
22 4 1 06, 07, 08 129 28
Time
23 0 Frozen Counter Events – All Variations 1 06, 07, 08 129
23 1 32-Bit Frozen Counter Event without Time 1 06, 07, 08 129 28
23 2 16-Bit Frozen Counter Event without Time 1 06, 07, 08 129 28
23 3 32-Bit Frozen Delta Counter Event without Time 1 06, 07, 08 129 28
23 4 16-Bit Frozen Delta Counter Event without Time 1 06, 07, 08 129 28

Ingeteam Power Technology S.A.


Manual de usuario 444
DNP PROTOCOL 

REQUEST RESPONSE
OBJECT
(slave must parse) (master must parse)
Func Codes Qual Codes Func Codes
Obj Var Description Qual Codes (hex)
(dec) (hex) (dec)
30 0 Analog Input - All Variations 1, 22 00,01,06
30 1 32-Bit Analog Input 1 00,01,06 129 00, 01
30 2 16-Bit Analog Input 1 00,01,06 129 00,01
30 3 32-Bit Analog Input without flag 1 00,01,06 129 00, 01
30 4 16-Bit Analog Input without flag 1 00,01,06 129 00, 01
30 5 Analog Input — Single-prec flt-pt with flag 1 00,01,06 129 00, 01
32 0 Analog Change Event - All Variations 1 06,07,08
32 1 32-Bit Analog Change Event without Time 1 06,07,08 129, 130 28
32 2 16-Bit Analog Change Event without Time 1 06,07,08 129, 130 28
Analog Input Event — Single-prec flt-pt without
32 5 1 06,07,08 129,130 28
time
2 07, quantity=1
50 1 Time and Date
1 07, quantity=1 129 07, quantity=1
51 1 Time and Date CTO 129 07, quantity=1
51 2 Unsynchronized Time and Date CTO 129 07, quantity=1
52 2 Time Delay Fine 129 07, quantity=1
60 1 Class 0 Data 1 06
1 06,07,08
60 2 Class 1 Data
20, 21,22 06
1 06,07,08
60 3 Class 2 Data
20, 21, 22 06
1 06,07,08
60 4 Class 3 Data
20, 21, 22 06
1 00, 01 129 00
80 1 Internal Indications
2 00, index=7
No Object 13, 14
No Object 23

Ingeteam Power Technology S.A.


Manual de usuario 445
IEC 60870-5-103 PROTOCOL 

26. IEC 60870-5-103 PROTOCOL

26.1 INTRODUCTION

The device provides an IEC 60870-5-103 interface to act as RTU and to communicate with a IEC 60870-5-103 master (for example a
remote control station).

Below are described the following topics:

❑ Protocol configuration settings


❑ Protocol configuration tables for digital signals, measurements and commands (which are configured with the software
configuration tool)

26.2 CONFIGURATION SETTINGS

Depending on the model, the device has the following settings:

❑ Enable protocol:
 Yes
 No
❑ Slave address: Slave address of the device. Value between 1 and 254.
❑ Port Number: This setting enables the selection between the available communication channels:
 COM1
 COM2
 COM3
 COM4
 COM5
 COM6
❑ Comm speed (bauds): This setting enables the selection of the serial baud rate.
 600 baud
 1200 baud
 2400 baud
 4800 baud
 9600 baud
 19200 baud
 38400 baud
 57600 baud
❑ Parity: Enables the selection of the parity type to be used in transmission.
 None
 Even
 Odd
❑ Number of Stop bits: Enables the selection of the number of stop bits.
 1 Bit
 2 Bit
❑ Communication control: Enables de selection of the communication control type.

Ingeteam Power Technology S.A.


Manual de usuario 446
IEC 60870-5-103 PROTOCOL 

 Normal
 Fixed + DCD
 RTS
 RTS+CTS
 RTS+CTS+DCD
 RS485
❑ Min. respond delay (ms): Waiting time for the activation of the RTS and the transmission of a message after the reception
of a message. Value between 0 and 1000.
❑ CTS max delay (ms): Waiting time for the CTS activation after the RTS activation. Value between 0 and 1000.
❑ Carrier stabilization (ms): Waiting time for the transmission of the message after the CTS detection in order to allow the
carrier stabilization. Value between 0 and 1000.
❑ RTS drop-off time (ms): Waiting time for the RTS deactivation after the message last byte transmission.
❑ Permission to synchronize: Synchronization permission from control centre.
 Yes
 No
It is used to select the synchronization source when there are several available.

❑ Communication fail T.(min): Waiting time in minutes without receiving any valid measure before indicate communication
failure. Value between 0 and 10000.

❑ Change wait time (s): Waiting time for the SOE in the internal queue before processing the events. It is only necessary if
there are data from different IEDs in order to sort them chronologically.
❑ VDEW Compatible: A “No” value allows the use of private data range.
 No
 Yes
Compatible mode (Yes):

Digital control signals that are sent are those configured with a compatible Funtion Type. The zero value in the table
indicates Funtion Type = Compatible. The other signals do not appear.

The user is responsible for selecting the digital signals of the device in accordance to the IEC 60870-5-103 standard.

Analog measurements are at most the first nine measures configured in the table. The Function Type and Information
Number to use (144, 145, 146 o 148) depends on the number of configured measures. 1, 2, 4 or 9 measures in the
measurements table respectively. In the last case the ASDU 9 is used instead of ASDU 3. The user is responsible for selecting
the device measures in accordance with IEC 60870-5-103.

Only the compatible commands are processed, those which in the table are configured by Function type = 0. The user is
responsible for selecting them according to IEC 60870-5-103.

Private mode (No):

All programmed control signals are sent.

The measures are sent with the Function Type field equal to "TYP in measurands ASDU" and Information Number field
equal to "INF in measuransds ASDU".

Supported commands are all that are programmed in the table.

❑ Function type: Value used to describe the type of protection equipment used.
 distance protection ( 128 )
 overcurrent protection ( 160 )
 transformer differential protection ( 176 )
 line differential protection ( 192 )

Ingeteam Power Technology S.A.


Manual de usuario 447
IEC 60870-5-103 PROTOCOL 

❑ TYP in measurands ASDU: This setting only applies when the adjustment VDEW is set to No. Indicates the Function Type
that is used in measurands ASDU.
❑ INF in measurands ASDU: The setting only applies when the adjustment VDEW is set to not. The field indicates the
Information Number used in measurands ASDU.
❑ Transformation ratio: Transformation ratio applied in the measurands.
 Secundary
 Primary

The configuration settings for the IEC 60870-5-103 are in the GEN\103ITCP1 node IEC 61850 data model, as detailed in the following
table:

Table 230 IEC 60870-5-103 protocol settings

Data Setting Minimum Maximum Step Remarks Type


ProtEna Enable protocol NO/YES Boolean
Slave Slave address 1 254 1 Int32
COM1
COM2
COM3
Port Port Number Enum
COM4
COM5
COM6
600 baud
1200 baud
2400 baud
4800 baud
Speed Comm speed (bauds) Enum
9600 baud
19200 baud
38400 baud
57600 baud
None
Parity Parity Even Enum
Odd
1Bit
Stopbit Number of Stop bits Enum
2 Bit
Normal
Fixed + DCD
RTS
RtsType Communication control Enum
RTS+CTS
RTS+CTS+DCD
RS485
RtsTmms Min. respond delay(ms) 0 1000 10 Int32
CtsTmms CTS max delay (ms) 0 1000 10 Int32
CarTmms Carrier stabilization (ms) 0 1000 10 Int32
RtsOffTmms RTS drop-off time (ms) 0 1000 1 Int32
CambTms Change wait time (s) 0 20 1 Int32
VDEW VDEW Compatible NO/YES Boolean
distance protection
overcurrent -
protection
FunTyp Function type transformer - Enum
differential protection-
line differential
protection
FunTypMed TYP in measurands ASDU 0 255 1 Int32
InfMed INF in measurands ASDU 0 255 1 Int32
RT Transformation ratio Secundary/Primary Boolean

Ingeteam Power Technology S.A.


Manual de usuario 448
IEC 60870-5-103 PROTOCOL 

26.3 TABLES

There are 3 tables to configure the list of digital signals, measurements and commands.

26.3.1 Digital signals table


Each digital signal device is identified in the IEC60870-5-103 protocol by the pair of fields Function Type and Information Number.

For each element the following fields must be configured with the software configuration tool:

❑ Type: Tipe of signal. Simple or double.


 Simple. (Default)
 DP
❑ CIN: Signal incidence code:
 SP→Value change in simple signaling. (Default)
 DP Open→ If the field Type = DP: Change in the calculated signal giving the 01 or open state of a double signal.
 DP Closed→ Change in the calculated signal giving the 10 or closed state of a double signal.
 DP Intermediate→ Change in the calculated signal giving the state 00 or intermediate of a double signal.
 DP Indeterminate→ Change in the calculated signal that gives the 11 or indeterminate of a double signal.
❑ Function type: Function type field of the signal. In the case that the signal belongs to the compatible range, (128,
160, 176 o 192), it should be configured a value of 0. The following values are not allowed: 129, 144, 145, 161, 177,
193, 208, 209, 224, 225, 240, 241, 254, 255.
❑ Information number: Information Number for the signal.
❑ Internal IED: IED of the signal value. Value 0 corresponds to the device itself.
❑ Internal ID: Internal signal number that identifies the element inside the device. In the case that the signal belongs
to the compatible range, the user is responsible for selecting the digital signals of the device in accordance to the
IEC 60870-5-103 standard.
❑ General interrogation: When selected it indicates that the information is included in the general interrogation (GI).
For these Information Numbers both status changes (OFF to ON and ON to OFF) are transmitted spontaneously.
For the others Information Numbers only the status OFF to ON are transmitted.
❑ Inverted: Indicates if the signal status is inverted. By default is not inverted
In the case of using a double-type signal, the four signals forming the double signal must be configured (Open, Close, Intermediate
and Indeterminate). Using this type of signal expands the meaning of the DPI field sent in the ASDUs:

When simple type signals are used, the field is sent as is the norm in section 7.2.6.5. Double-point information:

DPI := UI2[1..2] <0..3>

With <0> := not used

<1> := OFF

<2> := ON

<3> := not used

When using DP type signals, the meaning of the values 0 and 3 changes, becoming:

DPI := UI2[1..2] <0..3>

With <0> := Intermediate, (transitioning between end conditions)

<1> := OFF

<2> := ON

<3> := Indeterminate, (abnormal or custom condition)

Ingeteam Power Technology S.A.


Manual de usuario 449
IEC 60870-5-103 PROTOCOL 

26.3.2 Measurements table


For each element the following fields must be configured:

❑ Measure number: Measure position inside the ASDU. The first position is zero.
❑ Internal IED: IED of the signal value. Value 0 corresponds to the device itself.
❑ Internal ID: Internal measure number that identifies the element inside the device. In the case that the measure
belongs to the compatible range, the user is responsible for selecting the measure of the device in accordance to
the IEC 60870-5-103 standard.
❑ Límit scale: Real positive measurement value corresponding to 4095 internal units. If the value is zero and the
transformation ratio setting indicates secondary, the database limit scale is applied to the measure. If the value is
zero and transformation ratio setting indicates primary, the database limit scale is applied to the measure
multiplied by the transformation ratio.

26.3.3 Commands table


For each element the following fields must be configured:

❑ Function type: Function Type field for the signal. In the case that the signal belongs to the compatible range, (128,
160, 176 o 192), it should be configured a value of 0.
❑ Information number: Information Number for the signal.
❑ DCO: ON/OFF value of the command.
❑ IED interno: IED of the command value. Value 0 corresponds to the device itself
❑ Internal ID: Internal command number that identifies the element inside the device. In the case that the command
belongs to the compatible range, the user is responsible for selecting the command of the device in accordance to
the IEC 60870-5-103 standard
❑ Origin: Command origin. Allowed values:
 Bay Control
 Station Control
 Remote Control
 Automatic Bay
 Automatic Station
 Automatic Remote
 Maintenance
 Process

Ingeteam Power Technology S.A.


Manual de usuario 450
SLAVE PROCOME PROTOCOL 

27. SLAVE PROCOME PROTOCOL

27.1 INTRODUCTION

The device provides a Procome interface to act as RTU and to communicate with a Procome master (for example a remote control
station).

The communication can be selected for a serial line or via Ethernet, using encapsulation by means of the TCP/IP protocol.

Below are described the following topics:

❑ Protocol configuration settings


❑ Protocol configuration tables for digital signals, measurements, counters and commands (which are configured with the
software configuration tool)

27.2 CONFIGURATION SETTINGS

The protocol has the following configuration settings:

❑ Port Number: This setting enables the selection between the available communication channels:
 Disable
 COM1
 COM2
 COM3
 COM4
 COM5
 COM6
 Ethernet 1
 Ethernet 2
❑ Procome address: Procome slave address of the device. Value between 0 and 254.
❑ Comm speed (bauds): This setting enables the selection of the serial baud rate.
 300 baud
 600 baud
 1200 baud
 2400 baud
 4800 baud
 9600 baud
 19200 baud
 38400 baud
 57600 baud
 115200 baud
❑ Parity: Enables the selection of the parity type to be used in transmission.
 Without parity
 Even
 Odd
❑ Number of Stop bits: Value between 1 and 2.

Ingeteam Power Technology S.A.


User Manual 451
SLAVE PROCOME PROTOCOL 

❑ Carrier stabilization (ms): Waiting time for the transmission of the message after the CTS detection in order to allow the
carrier stabilization. Value between 0 and 1000.
❑ CTS wait time (ms): Waiting time for the CTS activation after the RTS activation. Value between 0 and 10000.
❑ RTS activation time (ms): Waiting time for the activation of the RTS and the transmission of a message after the reception
of a message. Value between 0 and 1000.
❑ RTS drop out time (ms): Waiting time for the RTS deactivation after the message last byte transmission.
❑ Channel Type: Enables de selection of the communication control type.
 Standard
 RTS Control
 By Phone
❑ Change wait time (s): Waiting time for the SOE in the internal queue before processing the events. It is only necessary if
there are data from different IEDs in order to sort them chronologically.
❑ Permission to synchronize: Synchronization permission from control centre.
 Yes
 No
It is used to configure the synchronization source when there are several available.

❑ TCP Listen Port: TCP port used as server.

The configuration settings for the first PROCOME are in the GEN\ITCP1 node IEC 61850 data model, as detailed in the following
table:

Ingeteam Power Technology S.A.


User Manual 452
SLAVE PROCOME PROTOCOL 

Table 231 Slave Procome protocol settings

Data Setting Mín. Max. Step Remarks Type


Disable
COM1
COM2
COM3
Port Port Number COM4 Enum
COM5
COM6
Ethernet 1
Ethernet 2
DirEnl Procome Address 0 254 1 Uint32
300 baud
600 baud
1200 baud
2400 baud
4800 baud
VelTrans Speed (Bauds) Enum
9600 baud
19200 baud
38400 baud
57600 baud
115200 baud
Parity Parity None / Even / Odd Enum
Stopbit Number of Stop Bits 1 2 1 Uint32
PorTmms Carrier stabilization (ms) 0 1000 10 Uint32
ActCtsTmms CTS wait time (ms) 0 10000 5 Uint32
ActRtsTmms RTS activation time (ms) 0 5000 10 Uint32
DesRtsTmms RTS drop out time (ms) 0 5000 1 Uint32
Standard
TipoCan Channel type RTS Control Enum
By Phone
CambTms Change wait time (s) 0 20 1 Uint32
SynEna Permission to synchronize NO/YES Enum
TcpPort TCP Listen Port 0 65535 1 Uint32

27.3 TABLES

There are 4 tables to configure the list of digital status (binary inputs), analogs, counters and commands.

27.3.1 Digital status table


For each element the following fields must be configured:

❑ Remte Signal, (nP): Procome signal number. Values between 0 and 1023.
❑ IED, (UCL): IED of the signal. Value 0 corresponds to the device itself.
❑ Internal signal, (nUCL): Internal signal number that identifies the element inside the device.
❑ Inverted, (Inv): Indicates if the signal status is inverted. By default is not inverted.
 Not inverted (0)
 Inverted (1)
❑ Reference 61850 of signal.

27.3.2 Analog values table


For each element the following fields must be configured:

❑ Remote Measure, (nP): number of measure Procome. Values between 0 and 255. Gaps are allowed.
❑ Internal IED, (UCL): IED of the analog value. Value 0 corresponds to the device itself.

Ingeteam Power Technology S.A.


User Manual 453
SLAVE PROCOME PROTOCOL 

❑ Internal ID, (nUCL): Internal analog number that identifies the element inside the device.
❑ Reference 61850 of measure.

27.3.3 Counters table


For each element the following fields must be configured:

❑ Remote counter, (nP): Procome counter number. Values between 0 and 255. Gaps are allowed.
❑ Internal IED, (UCL): IED of the counter value. Value 0 corresponds to the device itself.
❑ Internal ID, (nUCL): Internal counter number that identifies the element inside the device.
❑ Reference 61850 of counter.

27.3.4 Commands table


For each element the following fields must be configured:

❑ Remote command, (nP): Procome command number. Values between 0 and 1023.
❑ Internal IED: IED of the command. Value 0 corresponds to the device itself.
❑ Internal ID, (nUCL): Internal command number that identifies the element inside the device. The value of the
Internal command ON corresponds to the number of even order and the value to be the odd OFF
❑ Source (origen):
 Station Control
 Remote Control
 Automatic Station
 Automatic Remote
NOTE: If the 'source' field does not exist in the file, it takes as default Control Station.
❑ Reference 61850 of command.

Ingeteam Power Technology S.A.


User Manual 454
MODBUS MASTER PROTOCOL 

28. MODBUS MASTER PROTOCOL

28.1 INTRODUCTION

The Modbus master protocol allows communication with control and/or protection and measuring devices.

Currently, the device has only asynchronous serial communication, with a start bit, 8 bits of data and configurable parity and stop bits.

The protocol allows the database to update with digital signals, measurements and counters. It also allows to send commands. For
some type of devices it allows to send synchronization messages and request for signal changes or events.

A configuration table, generated with a software tool dedicated to this effect, will indicate the number of information elements of each
type that each equipment has, as well as its address according to the Modbus RTU protocol.

The following are detailed:

❑ Protocol configuration settings


❑ Data types that can be requested/written from/to slave devices
❑ Modbus functions that are implemented in the protocol
❑ Types of RTU to communicate with
❑ Configuration software tool
❑ Modbus messages supported

28.2 CONFIGURATION SETTINGS

The protocol has the following configuration settings:

❑ Enable protocol:
 No
 Yes
❑ Port Number: It allows to set the communication channel between the available serial COMs.
 COM1
 COM2
 COM3
 COM4
 COM5
 COM6
❑ Comm speed (bauds): It allows to select the serial transmission speed.
 600 baud
 1200 baud
 2400 baud
 4800 baud
 9600 baud
 19200 baud
 38400 baud

Ingeteam Power Technology S.A.


User Manual 455
MODBUS MASTER PROTOCOL 

 57600 baud
❑ Parity: It allows to select the type of parity to be used in the transmission.
 None
 Even
 Odd
❑ Number of stop bits:
 1 Bit
 2 Bit
❑ Communication control: It allows to select the type of communication channel.
 RS232_FO
 RS485
❑ RTS activation delay Time (ms): Minimum waiting time to activate the RTS and start the transmission. Value between 0 and 5000.
❑ CTS max delay (ms): How much time the device will wait to activate the CTS after the activation of the RTS. Value between 0 and
10000.
❑ Carrier stabilization (ms): Waiting time to start the transmission, once CTS has been detected, in order to stabilize the carrier. Value
between 0 and 5000
❑ RTS dropoff time (ms): This is the time that the RTS signal keeps activated after the transmission of the last byte. Value between 0
and 5000.
❑ Respond delay time (ms): Maximum time that the master waits to receive the slave response. Value between 10 and 30000.
❑ Inter request time (ms): The time between two request cycles of the master device. Value between 10 and 30000.
❑ Transmission retries number: Indicates the number of data request retries the master device does, if it does not receive any
response from the slave device at a given time (Respond delay time). Value between 0 and 10.

Table 232 Modbus Master protocol settings

Data Setting Min. Max. Step Remarks Type


ProtEna Enable protocol NO/YES Boolean
COM1
COM2
COM3
Port Port Number Enum
COM4
COM5
COM6
600 baud
1200 baud
2400 baud
4800 baud
BaudRate Comm speed (bauds) Enum
9600 baud
19200 baud
38400 baud
57600 baud
Parity Parity None / Even / Odd Enum
Stopbit Number of stop bits 1 Bit / 2 Bit Enum
RS232_FO
ChType Communication control Enum
RS485
ActRtsTmms RTS activation delay Time (ms) 0 5000 10 int32
ActCtsTmms CTS max delay (ms) 0 10000 10 int32
CarTmms Carrier stabilization (ms) 0 5000 10 int32
DesRtsTmms RTS dropoff time (ms) 0 5000 10 int32
RespTmms Respond delay time (ms) 10 30000 10 int32
IntgcTmms Inter request time (min) 10 30000 10 int32
RetryNumb Transmission retries number 0 10 1 Int32

Ingeteam Power Technology S.A.


User Manual 456
MODBUS MASTER PROTOCOL 

28.3 DATA TYPES

The protocol allows the master device to read signals, measurements and counters from the slave devices. It also allows sending
commands to the devices. In addition it allows to request signal changes and synchronization for the next devices: PL300 and TCP-IH.

Different types and formats of signals, measurements and counters are supported. The device configuration will indicate the data and
formats to be requested for each slave.

28.3.1 Digital signals


The Modbus master has the following signal types:

Table 233 Digital signal types

Type Description Remarks


1 Relay status Status of relays bit by bit
4 Digital signal (16 signals/WORD) Digital inputs as 16-bit registers, 16 signals in each word
Similar to type 1 and 14 but to read the information of one
5 Device status
single byte: Fast read of a byte.
12 Digital signal (1 signal/WORD) Digital inputs as 16-bit registers. One digital input per word
14 Input status Digital inputs bit by bit

Type 14 can only be used for RTU type 5.

28.3.2 Measurements
The Modbus master has the following measurement types:

Table 234 Measurement types

Type Description Remarks


2 Measurement For reading measurements with F03/F04 functions
7 Additional measurement For reading measurements with F03 function

Type 7 can only be used for RTU type 5.

The Modbus master has the following measurement formats:

Table 235 Measurement format types

Format Description Remarks

0 8 bits, unsigned Measurements in 8-bit unsigned format

1 8 bits, signed Measurements in 8-bit signed format

2 16 bits, unsigned Measurements in 16-bit unsigned format

3 16 bits, signed Measurements in 16-bit signed format

4 32 bits, unsigned Measurements in 32-bit unsigned format

5 32 bits, signed Measurements in 32-bit signed format

6 Float point Measurements in floating format

10 Procome Measurements in Procome format in accounts

11 15 bits plus sign Measurements in 16-bit signed format with sign in the higher bit

Ingeteam Power Technology S.A.


User Manual 457
MODBUS MASTER PROTOCOL 

28.3.3 Counters
Table 236 Counter types

Type Description Remarks

3 Counter Counter reading

The following counter formats are supported

Table 237 Counter format types

Format Description Remarks

0 8 bits, unsigned Counters in 8-bit unsigned format

1 8 bits, signed Counters in 8-bit signed format

2 16 bits, unsigned Counters in 16-bit unsigned format

3 16 bits, signed Counters in 16-bit signed format

4 32 bits, unsigned Counters in 32-bit unsigned format

5 32 bits, signed Counters in 32-bit signed format

6 Float point Counters in floating format

Counters in 32-bit floating format:


7 Float point / 1000
The value is sent divided by 1000

28.3.4 Commands
The Modbus functions implemented in the device for the execution of commands are F05 and F16. Only one type of function can
be used for each device.

The information related to the Modbus functions is in the sections of Implemented functions and RTU types of this manual.

28.3.5 Request of events to Ingeteam Power Technology devices


Currently, the request of events or signal changes it is only implemented for PL300 and TCP-IH. This request may be enabled from
the “Modbus master configurator”.

28.3.6 Synchronization
Currently, the synchronization it is only implemented for PL300 and TCP-IH.

Ingeteam Power Technology S.A.


User Manual 458
MODBUS MASTER PROTOCOL 

28.4 IMPLEMENTED FUNCTIONS

The Modbus master functions that may be used for requesting and writing data in the slave devices are the following:

Table 238 Implemented Modbus functions

Function Code Description


01 Read Coils
02 Read Discrete Inputs
03 Read Holding Registers
04 Read Input Registers
05 Write single coil
07 Read exception status
16 Write multiple registers

The Modbus master will use these functions taking into account the type and database of the device configured in the “Modbus master
configurator”

28.5 RTU TYPES

The following table shows the type of devices currently considered in the Modbus master and the Modbus functions used for each
type:

Table 239 Characteristics of RTU types

RTU types Signal changes/Events Data request Command execution Synchronization


F01
1 NO F05 NO
F04
F01
3 NO F16 NO
F03
F02
F03
4 NO F05 NO
F04
F07
F01
F02
5 NO F16 NO
F03
F04
F01
10 YES F16 YES
F03
14 NO F04 NOT IMPLEMENTED NO

❑ RTU type 1: It supports reading digital outputs bit by bit, reading registers and writing digital outputs bit by bit
 F01: Function for reading digital outputs bit by bit
 F04: Function for reading registers
 F05: Function for writing digital outputs bit by bit
❑ RTU type 3: It supports reading digital outputs bit by bit, reading registers and writing multiple registers
 F01: Function for reading digital outputs bit by bit
 F03: Function for reading registers
 F16: Function for writing multiple registers
❑ RTU type 4: It supports reading digital inputs bit by bit, reading registers and exception states and writing digital outputs bit by bit
 F02: Function for reading digital inputs bit by bit
 F03: Function for reading registers

Ingeteam Power Technology S.A.


User Manual 459
MODBUS MASTER PROTOCOL 

 F04: Function for reading registers


 F07: Function for reading exception states
 F05: Function for writing digital outputs bit by bit
❑ RTU type 5: It supports reading outputs and digital inputs bit by bit, reading registers and writing multiple registers
 F01: Function for reading digital outputs bit by bit
 F02: Function for reading digital inputs bit by bit
 F03: Function for reading registers
 F04: Function for reading registers
 F16: Function for reading multiple registers
❑ RTU type 10: It supports reading digital outputs bit by bit, reading registers and writing multiple registers
 F01: Function for reading digital outputs bit by bit
 F03: Function for reading registers
 F16: Function for reading multiple registers
The request of events and synchronization is currently only implemented for PL300 and TCP-IH.
 F03: Function for event requests
 F16: Function for synchronizing
❑ RTU type 14: It supports reading registers
 F04: Function for reading registers

28.6 SW CONFIGURATION TOOL

The Modbus master protocol is configured using the “Modbus master configurator” available in the PacFactory configuration SW and
EFS tools. This tool generates a configuration file that is sent to the device.

28.6.1 Fields to be configured


The tool has different tabs that are filled based on what is going to be integrated. Each tab has several fields.

❑ IED

 Modbus address
Address of the slave device (1 - 128). It is the value of the Modbus address of the device to communicate with.

 Internal address
Address of the slave device in the internal database. Its value is between 1 and 32. All the elements that are requested from
the device will be mapped on this address of the master database.

 RTU type
This field can take the following values: 1, 3, 4, 5, 10 and 14. The characteristics of each of these values are given in the RTU
Types section of this manual. It shows the functions used for each type of device.

Ingeteam Power Technology S.A.


User Manual 460
MODBUS MASTER PROTOCOL 

 Sync RTU
Enables sending synchronization to the slave device. It is only implemented for RTU type 10 (TCP-IH or PL300).

To enable synchronization, the Sync RTU flag is activated. Once enabled, the following screen appears:

The synchronization address of the device is indicated in the Sync address field.

PL300 = 240 and TCP-IH = 240.

Sync adjust (ftrans) is the time in ms that will be added to the synchronization time to correct possible drifts.

 Events request
It enables the request of signal changes of the slave device. It is only supported for RTU type 10 (PL300 or TCP-IH).

Once enabled, the following screen appears:

Ingeteam Power Technology S.A.


User Manual 461
MODBUS MASTER PROTOCOL 

In the Event address field, the signal change start address for the given device is indicated. PL300 = 20480 and TCP-IH =
1664.

 Endianness
It can take two values: Big Endian and Little Endian. Default value: Big endian.

It indicates the way in which the slave equipment sends the data.

Examples:

 Big endian

Description Floating data

Decimal value 212.5

Hexadecimal value 43 54 80 00

Data sent by communications 43 54 80 00

 Little endian

Description Floating data

212.5
Decimal value

Hexadecimal value 43 54 80 00

Data sent by communications 00 80 54 43

❑ Digital signals

 Modbus address
Modbus address of the slave device. It can take values between 1 and 128.

 Modbus signal
Initial memory address of the signal to be read in the slave device database.

 Type
Type of signal to be read. See the “Digital signals” section of this manual.

Ingeteam Power Technology S.A.


User Manual 462
MODBUS MASTER PROTOCOL 

 No. of registers
It is the number of signals or the number of registers to be read, depending on the type of signal.

Relay status, Device status or Input status: number of signals.

Digital signal (16 signals / WORD) or Digital signal (1 signal / WORD): number of registers.

 Internal ID
It indicates the first position in the master internal communication database on which these signals will be mapped. The
automatic assignment must be used by clicking on the button highlighted in red in the image, Set internal IDs

❑ Measurements

 Modbus address
Modbus address of the slave device. It can take values between 1 and 128.

 Modbus measurement
First memory address of the measurement to be read in the slave device database.

 Type
Type of measurement to be read. See the “Measurements” section of this manual.

 Format
Format of the measurement to be read. See the “Measurements” section of this manual.

 Swapping
Possible values: No swap, Byte Word swap, Byte swap and Word swap. Default value: No swap.

It indicates the order in which the slave device sends data greater than one byte. Usually used for measurements and / or
32bit counters.

Examples:

 No swap

Description Integer data

Decimal value 70000

Hexadecimal value 00 01 11 70

Data sent by communications 00 01 11 70

This is the most usual option.

Ingeteam Power Technology S.A.


User Manual 463
MODBUS MASTER PROTOCOL 

 Byte Word swap

Description Integer data

Decimal value 70000

Hexadecimal value 00 01 11 70

Data sent by communications 70 11 01 00

 Byte swap

Description Integer data

Decimal value 70000

Hexadecimal value 00 01 11 70

Data sent by communications 01 00 70 11

 Word swap

Description Integer data

Decimal value 70000

Hexadecimal value 00 01 11 70

Data sent by communications 11 70 00 01

 No. of elements
It is the number of measurements to be read from the “Modbus measurement” field.

 Scale factor
The measurement value in the internal database is the value read multiplied by the scale factor.

By double-clicking on this field, it appears a screen for the scale factor configuration for this measurement.

Ingeteam Power Technology S.A.


User Manual 464
MODBUS MASTER PROTOCOL 

 Internal ID
It indicates the first position in the master internal communication database, where these measurements will be mapped.
The automatic assignment must be used by clicking on the button highlighted in red in the image, Set internal IDs.

❑ Counters

 Modbus address
Modbus address of the slave device. It can take values between 1 and 128.

 Modbus counter
Initial memory address of the counters to be read in the slave device database.

 Format
Format of the counters to be read. See the “Counters” section of this manual.

 Swapping
Possible values: No swap, Byte Word swap, Byte swap and Word swap. Default value: No swap.

It indicates the order in which the slave device sends data greater than one byte. Usually used for measurements and / or
32 bit counters.

Examples:

Ingeteam Power Technology S.A.


User Manual 465
MODBUS MASTER PROTOCOL 

 No swap

Description Integer data

Decimal value 120000

Hexadecimal value 00 01 D4 C0

Data sent by communications 00 01 D4 C0

This is the most usual option.

 Byte Word swap

Description Integer data

Decimal value 120000

Hexadecimal value 00 01 D4 C0

Data sent by communications C0 D4 01 00

 Byte swap

Description Integer data

Decimal value 120000

Hexadecimal value 00 01 D4 C0

Data sent by communications 01 00 C0 D4

 Word swap

Description Integer data

Decimal value 120000

Hexadecimal value 00 01 D4 C0

Data sent by communications D4 C0 00 01

Ingeteam Power Technology S.A.


User Manual 466
MODBUS MASTER PROTOCOL 

 No. of elements
It is the number of counters to be read from the “Modbus counter” field.

 Scale factor
The counter value in the internal database is the value read, multiplied by the scale factor.

By double-clicking on this field, it appears a screen for the scale factor configuration for that counter.

 Internal ID
It indicates the first position in the master internal communication database where these counters will be mapped. The
automatic assignment must be used by clicking on the button highlighted in red in the image, Set internal IDs.

❑ Commands

 Modbus address
Modbus address of the slave device. It can take values between 1 and 128.

 Command No.
Number of command in the master internal database (0-3071).

 Modbus command
Modbus address for the command to be executed.

 Value
Value to be written on the Modbus command field.

Ingeteam Power Technology S.A.


User Manual 467
MODBUS MASTER PROTOCOL 

28.6.2 Configuration example


Database of the device to be integrated:

❑ Big endian
❑ Events request: No
❑ Synchronization: No
❑ Signals to be read
 From address 0
 Number of signals: 2
 Type: Digital outputs
❑ Measurements to read
 From address 0
 Number of measurements: 2
 Format: 16-bit unsigned
 Swapping: No swap
 Scale factors
▪ Measurement 0: 0.1
▪ Measurement 1: 0.01
 From address 40
 Number of measurements: 1
 Format: 16-bit signed
 Swapping: No swap
 Scale factors
▪ Measurement 0: 0.001
 From address 66
 Number of measurements: 3
 Format: 32-bit unsigned
 Swapping: No swap
 Scale factors
▪ Measurement 0: 1
▪ Measurement 1: 1
▪ Measurement 2: 1
 From address 500
 Number of measurements: 1
 Format: 32-bit signed
 Swapping: No swap
 Scale factors
▪ Measurement 0: 0.1
 From address 530
 Number of measurements: 2
 Format: float
 Swapping: No swap
 Scale factors
▪ Measurement 0: 0.1
▪ Measurement 1: 0.1

Ingeteam Power Technology S.A.


User Manual 468
MODBUS MASTER PROTOCOL 

❑ Counters to read
 From address 60
 Number of counters: 4
 Format: 32-bit unsigned
 Swapping: No swap
 Scale factors
▪ Counter 0: 0.001
▪ Counter 1: 0.001
▪ Counter 2: 0.001
▪ Counter 3: 0.001
❑ Commands to execute
 Number of command 0
 Address: 0
 Value: 255
With this configuration, digital output 1 is activated.

 Number of command 1
 Address: 1
 Value: 255
With this configuration, digital output 2 is activated.

 Number of command 2
 Address: 0
 Value: 0
With this configuration, digital output 1 is deactivated.

 Number of command 3
 Address: 1
 Value: 0
With this configuration, digital output 2 is deactivated.

Database configuration:

❑ IED

❑ Digital signals

Ingeteam Power Technology S.A.


User Manual 469
MODBUS MASTER PROTOCOL 

❑ Measurements

❑ Counters

❑ Commands

28.7 SERIAL MESSAGES

The format of the serial communication messages used by the Modbus Master protocol is shown below, with the functions used by the
device as an example.

28.7.1 Format
❑ Master request:
 Remote address - 1 byte
 Function code - 1 byte
 Data - variable number of bytes
 CRC - 2 byte
❑ Slave response:
 Remote address - 1 byte

Ingeteam Power Technology S.A.


User Manual 470
MODBUS MASTER PROTOCOL 

 Function code - 1 byte


 Data – variable number of bytes
 CRC - 2 byte
Remote address: Modbus address (Value between 1 and 128). Broadcast messages (address 0) are not allowed.

Function code: If it is > 127 (bit MSB to 1) it means that the remote has not performed the required function and will answer with
an error code.

CRC: LSB is sent first, followed by the MSB.

CRC generator (polynomial): x16 + x15 + x2 +1

28.7.2 Examples
❑ Function code 01 – Read n output bits
❑ Example:
 Remote address: 1
 Request of 12 output bits, from output 3 to 14 (All of these bits are activated)
Table 240 Request

Description Bytes Example (Hex)

Remote address 1 0x01

Function code 1 0x01


0x00
Starting address 2
0x03 Start reading on digital output 3
0x00
Number of digital outputs 2
0x0C Reading of 12 digital outputs

CRC 2 xx xx

Table 241 Response

Description Bytes Example (Hex)

Remote address 1 0x01

Function code 1 0x01


0x02
Byte count 1
2 bytes
0x0F
Outputs status 2
0xFF

CRC 2 xx xx

❑ In the request response, the LSB of the Outputs status byte contains the value of the first output (output 3). The rest of the
bytes are sent in lowest to highest order. If the number of bits requested is not a multiple of 8, the byte will be filled with
zeros.
❑ Function code 02 – Read n input bits
❑ Request and response frames are identical to the function 01.
❑ Function code 03 – Read n output words

Ingeteam Power Technology S.A.


User Manual 471
MODBUS MASTER PROTOCOL 

❑ To read digital signals, measurements and counters.


❑ Example:
 Remote address: 1
 Address: 0400h - Data: 00AAh
 Address: 0401h - Data: 00FFh
Table 242 Request

Description Bytes Example (Hex)

Remote address 1 0x01

Function code 1 0x03


0x04
Starting address 2
0x00
0x00
Number of registers (words) 2
0x02

CRC 2 xx xx

Table 243 Response

Description Bytes Example (Hex)

Remote address 1 0x01

Function code 1 0x03


0x04
Byte count 1
2 registers = 4 bytes
0x00
Register value 1 2
0xAA Value in address 0x400
0x00
Register value 2 2
0xFF Value in address 0x401

CRC 2 xx xx

❑ Function code 04 – Read n input words


❑ For reading digital signals, measurements and counters.
❑ Request and response frames are identical to the function 03.
❑ Function code 05 – One-bit writing
❑ For writing a bit to ON or OFF.
❑ Example:
 Remote address: 1
 Writing command number 24 to 1

Ingeteam Power Technology S.A.


User Manual 472
MODBUS MASTER PROTOCOL 

Table 244 Request

Description Bytes Example (Hex)

Remote address 1 0x01

Function code 1 0x05


0x00
Command number 2
0x18
0xFF
Output value 2
0x00 Writing to 1

CRC 2 xx xx

Table 245 Response

Description Bytes Example (Hex)

Remote address 1 0x01

Function code 1 0x05


0x00
Command number 2
0x18
0xFF
Output value 2
0x00 Writing to 1

CRC 2 xx xx

❑ Function code 07 – Read exception status


❑ Quick reading of a byte.
❑ Example:
 Remote address: 1
Table 246 Request

Description Bytes Example (Hex)

Remote address 1 0x01

Function code 1 0x07

CRC 2 xx xx

Table 247 Response

Description Bytes Example (Hex)

Remote address 1 0x01

Function code 1 0x07

Output data 1 0x6D

CRC 2 xx xx

Ingeteam Power Technology S.A.


User Manual 473
MODBUS MASTER PROTOCOL 

❑ Function code 16 – Write multiple registers


Writing of values on the device.

Example:

 Remote address: 1
 Writing command number 24 to 1

Table 248 Request

Description Bytes Example (Hex)

Remote address 1 0x01

Function code 1 0x10


0x00
Starting address 2
0x80
0x00
Number of registers (words) 2
0x01
0x02
Byte count 1
1 register = 2 bytes
0x00
Register value 2
0x18 Number of command to execute

CRC 2 xx xx

Table 249 Response

Description Bytes Example (Hex)

Remote address 1 0x01

Function code 1 0x10


0x00
Starting address 2
0x80
0x00
Number of registers (words) 2
0x01

CRC 2 xx xx

Ingeteam Power Technology S.A.


User Manual 474
MODBUS SLAVE PROTOCOL

29. MODBUS SLAVE PROTOCOL


Available since 6.2.19.0 version of firmware and 8.3.0.5 of CID.

29.1 INTRODUCTION

The device has a Modbus slave protocol which can communicate with a telecontrol station or with any system that works as a master.

The device has two types of communication:

❑ RTU (Remote terminal unit): Asynchronous serial communication, with a start bit, 8 bits of data and configurable parity and stop
bits.
❑ TCP/IP: Uses a TCP/IP network connecting through the registered port 502.
The protocol allows sending digital signals, measurements and counters to the master. It also allows the synchronization of the device
and the execution of commands.

A configuration table, generated with a software tool dedicated to this effect, will indicate the number of information elements that
the equipment has.

The following are detailed:

❑ Protocol configuration settings


❑ Protocol profile
❑ Control processes
❑ Equipment address map
❑ Data format
❑ Configuration software tool
❑ Modbus messages supported (serial and TCP/IP)

29.2 CONFIGURATION SETTINGS

The protocol has the following configuration settings:

❑ Enable protocol:
 No
 Yes
❑ Modbus address: Modbus address of the slave device. Value between 1 and 128.
❑ Port number: It allows to set the communication channel
 COM1
 COM2
 COM3
 COM4
 COM5
 COM6
 Ethernet
❑ TCP listen port: It allows to set a number of network port to communicate via TCP/IP. Value between 0 and 65535. Default value
502.

Ingeteam Power Technology S.A.


User Manual
475
MODBUS SLAVE PROTOCOL

❑ Comm speed(bauds): It allows to set the speed of the serial transmission


 600 baud
 1200 baud
 2400 baud
 4800 baud
 9600 baud
 19200 baud
 38400 baud
 57600 baud
❑ Parity: It allows to select the type of parity to use in the transmission
 None
 Even
 Odd
❑ Number of stop bits:
 1Bit
 2Bit
❑ Communication control: It allows to select the type of communication channel
 RS232_FO
 RS485
❑ RTS activation delay time (ms): Minimum waiting time to activate the RTS and start the transmission. Value between 0 and 5000.
❑ CTS max delay (ms): How much time the device will wait to activate the CTS after the activation of the RTS. Value between 0 and
10000.
❑ Carrier stabilization (ms): Waiting time to start the transmission, once CTS has been detected, in order to stabilize the carrier. Value
between 0 and 5000.
❑ RTS dropoff time (ms): This is the time that the RTS signal keeps activated after the transmission of the last byte. Value between 0
and 5000.
❑ Change wait time (s): Waiting time in queue of the changes configured in the protocol tables before starting their treatment. It only
makes sense if signals from different IEDs are configured for their previous chronological ordering.
❑ Request for changes: It allows to set if the master device makes the request for changes to the slave equipment
 No
 Yes
❑ Data transmission type: It allows to set the order of the data to be transmitted
 Big endian
 Little endian
❑ Permission to synchronize: It allows to set if the master device makes the synchronization of the slave equipment
 No
 Yes
❑ Server IP address: It filters the possible connections available in the slave device configuring an IP. Possible values in the IP address
range. The value 255.255.255.255 allows connecting to any available connection

Ingeteam Power Technology S.A.


User Manual
476
MODBUS SLAVE PROTOCOL

Table 250. Modbus slave protocol settings

Data Setting Min. Max. Step Possible values Type

ProtEna Enable protocol NO/YES Boolean


DirEnl Modbus address 1 128 1 int32
COM1
COM2
COM3
Port Port number COM4 Enum
COM5
COM6
Ethernet
TcpPort TCP listen port 0 65535 1 int32
600 baud
1200 baud
2400 baud
4800 baud
BaudRate Comm speed (bauds) Enum
9600 baud
19200 baud
38400 baud
57600 baud
Parity Parity None / Even / Odd Enum
Stopbit Number of stop bits 1Bit / 2 Bit Enum
RS232_FO
ChType Communication control Enum
RS485
ActRtsTmms RTS activation delay time (ms) 0 5000 10 int32
ActCtsTmms CTS max delay (ms) 0 10000 10 int32
CarTmms Carrier stabilization (ms) 0 5000 10 int32
DesRtsTmms RTS dropoff time (ms) 0 5000 10 int32
EspColTms Change wait time (s) 0 20 1 int32
SolicChgs Request for changes NO/YES Boolean
Big endian
Endianness Data transmission type Enum
Little endian
SynEna Permission to synchronize NO/YES Boolean
IPRTU Server IP address 0 65535 1 IP

Ingeteam Power Technology S.A.


User Manual
477
MODBUS SLAVE PROTOCOL

29.3 PROTOCOL PROFILE

29.3.1 Implemented functions in Modbus RTU


The implemented functions for serial communication are shown below:

Function
Description Use
Code

This function code is used to read contiguous status of


01 Read Coils
signals in a remote device
This function code is used to read contiguous status of
02 Read Discrete Inputs
signals in a remote device
This function code is used to read the contents of a
03 Read Holding Registers
contiguous block of registers in a remote device

This function code is used to read the contents of a


04 Read Input Registers
contiguous block of registers in a remote device

This function code is used to write a single output to either


05 Write Single Coil
ON or OFF in a remote device
Writes a single register in a remote device (it is used to
06 Write Single Register
execute commands)
This function code is used to write a single output to either
15 Write Multiple Coils
ON or OFF in a remote device
Writes a single register in a remote device (it is used to
16 Write Multiple Registers
execute commands)

29.3.2 Implemented functions in Modbus TCP/IP


The implemented functions for TCP/IP communication are shown below:

Function
Description Use
Code

This function code is used to read contiguous status of


01 Read Coils
signals in a remote device
This function code is used to read contiguous status of
02 Read Discrete Inputs
signals in a remote device
This function code is used to read the contents of a
03 Read Holding Registers
contiguous block of registers in a remote device

This function code is used to read the contents of a


04 Read Input Registers
contiguous block of registers in a remote device

This function code is used to write a single output to either


05 Write Single Coil
ON or OFF in a remote device
Writes a single register in a remote device (it is used to
06 Write Single Register
execute commands)
This function code is used to write a single output to either
15 Write Multiple Coils
ON or OFF in a remote device
Writes a single register in a remote device (it is used to
16 Write Multiple Registers
execute commands)

Ingeteam Power Technology S.A.


User Manual
478
MODBUS SLAVE PROTOCOL

29.3.3 Exception codes


The protocol has the following exception codes:

Function Description Meaning


Code
The function code received in the query is
01 Illegal function
unknown by the server
The data address received in the query is not an
02 Illegal data address
allowable address for the server

A value contained in the query data field is not


03 Illegal data value
an allowable value for server
The server is processing other task. The client
06 Server device busy should retransmit the message later when the
server is free

29.4 CONTROL PROCESSES

29.4.1 Request for equipment status


Two functions can be used:

❑ Function 03
❑ Reading a register on 0000h address (see "Equipment address map" section of this manual). The device respond is a byte
with the LOCAL/REMOTE STATE of the device.
❑ Function 04
❑ It works the same way as Function F03.

29.4.2 Request for digital signals


The following functions can be used:

❑ Function 01
❑ Reading boolean data.
❑ Function 02
❑ Reading boolean data.
❑ Function 03
❑ Reading registers.
❑ Function 04
❑ Reading registers.

Address range:

 Digital signals: 0400h - 0480h

29.4.3 Request for measurements and counters


The following functions can be used:

Ingeteam Power Technology S.A.


User Manual
479
MODBUS SLAVE PROTOCOL

❑ Function 03
❑ Reading registers.
❑ Function 04
❑ Reading registers.

Address range:

 Integer measurements: Address range 0480h - 0580h


 Counters: Address range 0580h - 0680h
 Floating type measurements: Address range 0700h - 0900h

29.4.4 Request for digital signal changes


The master device can get the information of all digital signal changes of the slave device, with the instant of time in which they
have happened. The process to do it is the following:

❑ Reading the address 0680h gets the number of changes to send by the slave device
❑ To obtain the information of the changes, reading the quantity of "number of changes x 5" on address 0682h is needed.
Reading range 0682h - 06FFh.
❑ The maximum quantity of registers that can be read is 125. This is the same as reading 25 changes since the information of
a digital signal change is stored in 5 registers. The number of registers to be read must be multiple of 5.
❑ Signal change structure format:

Number
MSB LSB
of Address
(Most Signifant Byte) (Least Significant Byte)
change (n)
0682h e v E V Bits and Signal number Signal number
0683h Milliseconds Milliseconds
n=1 0684h Hours Minutes
0685h Month Day of the week and day of the month
0686h --- Year
1 < n < 25 … … …
06FBh e v E V Bits and Signal number Signal number
06FCh Milliseconds Milliseconds
n = 25 06FDh Hours Minutes
06FEh Month Day of the week and day of the month
06FFh --- Year

 Signal number: It is stored in the first byte of the information of a digital signal change and in the first four bits of the
next byte.
 V Bit: Validity of the signal after its change (0: valid / 1: invalid)
 E Bit: State of the signal after its change (0 / 1)
 v Bit: It indicates if the signal change is due to a change in the validity V (0 / 1)
 e Bit: It indicates if the signal change is due to a change in the state E (0 / 1)
 Milliseconds: It is stored in the second register of the information of a signal change. Range of values 0 - 59999.
 Minutes: It is stored in the first byte of the third register of the information of a signal change. Range of values 0 - 59.
 Hours: It is stored in the second byte of the third register of the information of a signal change. Range of values 0 - 23.
 Day of the month: It is stored in the first byte of the fourth register of the information of a signal change. Its value is
registered in the first five bits of that byte. Range of values 1 - 31.
 Day of the week: It is stored in the first byte of the fourth register of the information of a signal change. Its value is
registered in the last three bits of that byte. Range of values 1 - 7.

Ingeteam Power Technology S.A.


User Manual
480
MODBUS SLAVE PROTOCOL

 Month: It is stored in the second byte of the fourth register of the information of a signal change. Range of values 1 -
12.
 Year: It is stored in the fifth register of the information of a signal change. Range of values 0 - 99.
❑ Writing the value 0 in address 0681h the last signal changes sent are validated. This means that the signal changes of the
device are considered as sent.
❑ If the signal changes are not validated, the device will consider that they have not been sent.
❑ If the device had more signal changes it will indicate it in the address 0680h and the master station could request them
repeating the process
❑ To read all the signal changes of the device, the process must continue until the reading of the address 0680h indicates
value 0
The requests are made with functions F03 and F04 and the writings with function F16.

29.4.5 Requesting data via memory map


The data of the configured addresses can be read in a single request. The addresses can be non-consecutive.

Functioning:

❑ The configured addresses must be written using function F16. Range of the writing area 0180h - 01FCh
❑ The data of the configured addresses must be read using function F03 or F04. Range of the reading area 0100h - 017Ch
❑ Up to 124 registers can be read and written
❑ The configured addresses must be in the range 0400h - 0680h and 0700h - 0900h
❑ To read the data of the configured addresses, the following must be taken into account:
 The position in the reading area from which to request the data, must be the same as the position in the writing area
where the configured addresses have been written
 Example:
 For a writing in address 0185h the reading has to be in address 0105h.
 Writing
 Writing address: 0185h
 Position in the writing area: 0185h - 0180h(initial address) = 0005h
 Reading
 The reading address must be: 0105h
 Position in the reading area: 0105h - 0100h(initial address) = 0005h
 The number of registers to be requested must be equal to the number of registers that add up the data of the
configured addresses
 Example:
 For a writing in address 0185h of the address 0400h, 0486h and 0581h the number of registers to be requested must
be 4.
 It must be ask for a register for the signals, another for the measurements of integer type and two registers for the
counters.
 Writing
 Writing address: 0185h
 Addresses configured:
▪ 0400h: First word of digital signals
▪ 0486h: Seventh measurement of integer type
▪ 0581h: Second counter
 Reading
 Reading address: 0105h
 The number of registers to request must be 4:

Ingeteam Power Technology S.A.


User Manual
481
MODBUS SLAVE PROTOCOL

▪ 0400h: Occupies a register (G9)


▪ 0486h: Occupies a register (G10)
▪ 0581h: Occupies two registers (G11)
 See section "Equipment address map" and "Data format" for G9, G10 and G11.

29.4.6 Synchronization
To synchronize the device it must be written with the function F16 the following information in the address 00F0h:

MSB LSB
Address
(Most Signifant Byte) (Least Significant Byte)
00F0h Milliseconds Milliseconds
00F1h Hours Minutes
00F2h Month Day
00F3h - Year

 To synchronize the device the four words must always be written. The partial writing of some data is not allowed, it is
always necessary to write the whole structure
 It is possible to read the address 00F0h to get the current time of the equipment. Any register can be read as long as
the range does not exceed the address 00F3h. For reading, functions F03 or F04 must be used

29.4.7 Command execution


The following functions can be used:

❑ Function F05
❑ It allows the execution of commands to OFF and ON in the slave device database.
 For an OFF command it must be sent the number of command to execute and the operation value field to 0x0000.
 For an ON command it must be sent the number of command to execute and the operation value field to 0xFF00.
❑ Function F06
❑ It allows the execution of commands to ON in the slave device database.
 It must be written the number of command to execute in the address 0080h.
❑ Function F15
❑ It allows the execution of commands to OFF and ON in the slave device database.
 For an OFF command it must be sent the number of command to execute, the number of coils to be forced to one and
the operation value field to 0.
 For an ON command it must be sent the number of command to execute, the number of coils to be forced to one and
the operation value field to 1.
 It is only allowed the writing of one coil.
❑ Function F16
❑ It allows the execution of commands to ON in the slave device database.
 It must be written the number of command to execute in the address 0080h.
 It is only allowed the writing of one register.
Range of number of command to execute: 0 - 511

29.5 EQUIPMENT ADDRESS MAP

Distribution of the equipment address map:

Ingeteam Power Technology S.A.


User Manual
482
MODBUS SLAVE PROTOCOL

Register Memory
Description Length (words)
address(hex) zone
Identification of the equipment
0000 Device status 1 G1
Command address (*)
0080 Number of command to be executed 1 G2
System date
00F0 Milliseconds 1 G3
00F1 Hours and minutes 1 G4
00F2 Month and day 1 G5
00F3 Year 1 G6
User map
0100 User map values 124 G7
0180 User map addresses 124 G8
Reading zone
0400 Digital signal states 128 G9
0480 Measurements 256 G10
0580 Counters 256 G11
Digital signal changes zone
0680 Number of changes to be sent 1 G12
0681 Validation of sent changes (*) 1 G13
0682 Digital signal changes reading zone 125 G14
Reading zone
0700 Measurement 512 G15
Free memory zone
0900 Free
0HF Free

(*) Only for writing

The values of the Memory zone column are explained in the "Data format" section.

Ingeteam Power Technology S.A.


User Manual
483
MODBUS SLAVE PROTOCOL

29.6 DATA FORMAT

Data format depending on the memory zone (see section "Equipment address map"):

Memory
Format Description
zone
READING AREA OF THE DEVICE MODE
In the bit 0 LOCAL/REMOTE STATE of the device is indicated
G1 16 bits Value 0: REMOTE STATE
Value 1: LOCAL
Size of the area: A register (word)
WRITING AREA OF THE NUMBER OF COMMAND TO BE EXECUTED IN THE SLAVE DEVICE
DATABASE
G2 16 bits
Range of values: 0 - 511
Size of the area: A register (word)
MILLISECONDS READING AREA
G3 Unsigned 16 bits Range of values: 0 - 59999
Size of the area: A register (word)
READING AREA OF MINUTES AND HOURS
- Minutes: 0 to 7 bits
Range of values: 0 - 59
G4 16 bits
- Hours: 8 to 15 bits
Range of values: 0 - 23
Size of the area: A register (word)
READING AREA OF THE DAY OF THE WEEK AND MONTH
- Day: 0 to 7 bits
Range of values: 1 - 31
G5
16 bits - Month: 8 to 15 bits
Range of values: 1 - 12
Size of the area: A register (word)
READING AREA OF THE YEAR
- Year: 0 to 7 bits
G6 16 bits Range of values: 0 - 99
- It is not used: 8 to 15 bits
Size of the area: A register (word)
READING AREA OF THE VALUES OF THE CONFIGURED DATA ADDRESSES
- The unsigned 16 bits format is used for reading signals
16 bits - The signed 16 bits format is used for reading integer measurements
G7
Unsigned 32 bits - The unsigned 32 bits format is used for reading counters
Float - The Float format is used for reading floating type measurements
Size of the area: 124 registers (words)
WRITING AREA OF THE CONFIGURED ADDRESSES
G8 16 bits Range of values: 0400h - 0680h and 0700h - 0900h
Size of the area: 124 registers (words)
READING AREA OF SIGNALS
G9 16 bits Compacted bits. A bit to 0 value means signal deactivated and to value 1 activated
Size of the area: 128 registers (words)
READING AREA OF INTEGER MEASUREMENTS
G10 Signed 16 bits
Size of the area: 256 registers (words)
READING AREA OF COUNTERS
G11 Unsigned 32 bits
Size of the area: 256 registers (words)
READING AREA OF SIGNAL CHANGES TO BE SENT
G12 16 bits
Size of the area: A register (word)
WRITING AREA OF VALUE 0 TO VALIDATE THE SIGNAL CHANGES THAT HAS BEEN SENT
G13 16 bits
Size of the area: A register (word)
SIGNAL CHANGES INFORMATION AREA
G14
Unsigned 16 bits For more information go to the section "Request for digital signal changes"
Size of the area: 125 registers (word)
READING AREA OF FLOATING TYPE MEASUREMENTS
G15 Float
Size of the area: 512 registers (words)

Ingeteam Power Technology S.A.


User Manual
484
MODBUS SLAVE PROTOCOL

29.7 CONFIGURATION SOFTWARE TOOL

The Modbus slave protocol is configured with the "Modbus Slave Configurator" available in the PacFactory configuration SW and the
EFS tools. This tool generates a configuration file that is sent to the device.

29.7.1 Fields to be configured


❑ Digital signals

 Modbus address
The number of the signal in the Modbus slave database. Range of values 0 - 2047.

 Internal IED
The address of the remote device from which read the signals. Range of values 0 - 32. The value 0 is the address of the
device itself.

 Internal ID
The number of the signal in the slave device database. It must be selected by clicking on button and choosing the signal
to be read. This signal will be mapped to the position indicated by Modbus address.

 Description
It doesn´t need to be configured. The own tool does it.

 IEC-61850 ref
It doesn´t need to be configured. The own tool does it.

 Inverted
 It allows to invert the value of the signal.

❑ Measurements

 Modbus address
The number of the measurement in the Modbus slave database. Range of values 0 - 255.

 Internal IED
The address of the remote device from which read the measurements. Range of values 0 - 32. The value 0 is the address of
the device itself.

 Internal ID
The number of the measurement in the slave device database. It must be selected by clicking on button and choosing
the measurement to be read. This measurement will be mapped to the position indicated by Modbus address.

Ingeteam Power Technology S.A.


User Manual
485
MODBUS SLAVE PROTOCOL

 Description
 It doesn´t need to be configured. The own tool does it.
 IEC-61850 ref
 It doesn´t need to be configured. The own tool does it.

❑ Counters

 Modbus address
The number of the counter in the Modbus slave database. Range of values 0 - 127.

 Internal IED
The address of the remote device from which read the counters. Range of values 0 - 32. The value 0 is the address of the
device itself.

 Internal ID
The number of the counter in the slave device database. It must be selected by clicking on button and choosing the
counter to be read. This counter will be mapped to the position indicated by Modbus address.

 Description
It doesn´t need to be configured. The own tool does it.

 IEC-61850 ref
It doesn´t need to be configured. The own tool does it.

❑ Commands
❑ There are two options for the execution of commands depending on the function that is used (go to the section
"Command execution" for more detail): Commands to ON and to OFF/ON.
❑ The default configuration allows executing ON commands only.
❑ COMMANDS TO ON:

 Command
Number of the command in the Modbus slave database. Range of values: 0 - 511.

 Internal IED
The address of the remote device in which execute the commands. Range of values 0 - 32. The value 0 is the address of the
device itself.

 Internal ID

Ingeteam Power Technology S.A.


User Manual
486
MODBUS SLAVE PROTOCOL

The number of the command in the slave device database. It must be selected by clicking on button and choosing the
command to execute. The execution of this command is a consequence of the activation of the command number that
appears in the field Command.

 Description
It doesn´t need to be configured. The own tool does it.

 IEC-61850 ref
It doesn´t need to be configured. The own tool does it.

 ON/OFF
It doesn´t need to be configured. The own tool does it.

 Origin
It is the origin from where the commands are executed.

 COMMANDS TO ON AND OFF:


To execute commands to OFF the option in the "Modbus Slave Configurator" must to be enabled.

To do this, go to the "View" menu, click on "Options…" and the following image appears:

Enabling "Show OFF command" option in Modbus Slave and clicking on OK the following image where commands to ON
and OFF are configured is shown:

Ingeteam Power Technology S.A.


User Manual
487
MODBUS SLAVE PROTOCOL

 Command
Number of the command in the Modbus slave database. Range of values: 0 - 511.

 Internal IED
The address of the remote device in which execute the commands. Range of values 0 - 32. The value 0 is the address of the
device itself.

 Internal ID(ON)
The number of the command in the slave device database. It must be selected by clicking on button and choosing the
command to execute. The execution of this command is a consequence of the activation of the command number that
appears in field Command.

 Description (ON)
It doesn´t need to be configured. The own tool does it.

 IEC-61850 ref (ON)


It doesn´t need to be configured. The own tool does it.

 ON/OFF (ON)
It doesn´t need to be configured. The own tool does it.

 Internal ID(OFF)
The number of the command in the slave device database. It must be selected by clicking on button and choosing the
command to execute. The execution of this command is a consequence of the deactivation of the command number that
appears in field Command.

 Description (OFF)
It doesn´t need to be configured. The own tool does it.

 IEC-61850 ref (OFF)


It doesn´t need to be configured. The own tool does it.

 ON/OFF (OFF)
It doesn´t need to be configured. The own tool does it.

 Origin
It is the origin from where the commands are executed.

29.7.2 Configuration example


Below is an example of a Modbus slave database. This database contains elements which the master device can read or in which
can write.

Elements of the Modbus slave database:

❑ 10 digital signals
❑ 5 measurements
❑ 5 counters
❑ 4 commands

Ingeteam Power Technology S.A.


User Manual
488
MODBUS SLAVE PROTOCOL

Database configuration:

❑ Digital signals

 This configuration allows the access to:


 The state of eight digital inputs of the input/output board 1 of the device, which value is stored in the first eight
positions of the Modbus slave signal database.
 The state of two digital inputs of the input/output board 2 of the device, storing the state of the first input in the
position 15 of the Modbus slave signal database and the state of the second input in the position 31.
❑ Measurements

❑ This configuration allows the access to:


 Five logical measurements of the device, whose value is stored in the positions 0,3,7,8 and 9 of the Modbus slave
measurements database.
❑ Counters

❑ This configuration allows the access to:

Ingeteam Power Technology S.A.


User Manual
489
MODBUS SLAVE PROTOCOL

 Five logical counters of the device, whose value is stored in the positions 0, 5, 10, 15 and 20 of the Modbus slave
counters database.

❑ Commands

❑ This configuration allows:


 Activate the digital output 1 of the input/output board 1 of the device, activating the command number 0 of the
Modbus slave database.
 Activate the digital output 2 of the input/output board 1 of the device, activating the command number 1 of the
Modbus slave database.
 Activate the digital output 3 of the input/output board 1 of the device, activating the command number 7 of the
Modbus slave database.
 Activate the digital output 1 of the input/output board 2 of the device, activating the command number 10 of the
Modbus slave database.
 Activate the digital output 2 of the input/output board 2 of the device, deactivating the command 10 of the Modbus
slave database.

29.8 SERIAL MESSAGES

The format of the serial communication messages used by the Modbus slave protocol is shown below, with the functions used by the
device as an example.

29.8.1 Format
❑ Master request:
 Remote address - 1 byte
 Function code - 1 byte
 Data - variable number of bytes
 CRC - 2 byte

❑ Slave response:
 Remote address - 1 byte
 Function code - 1 byte
 Data - variable number of bytes
 CRC - 2 byte

Remote address: Modbus address (Value between 1 and 128). Broadcast messages (address 0) are not allowed.

Function code: If it is > 127 (bit MSB to 1) it means that the remote device has not performed the required function and will answer
with an error code.

CRC: LSB is sent first, followed by the MSB.

Ingeteam Power Technology S.A.


User Manual
490
MODBUS SLAVE PROTOCOL

29.8.2 Examples
❑ Function code 01 – Read coils
❑ For reading boolean data.
❑ Example:
 Remote address: 1
 Request of 12 output bits, from output 3 to 14 (All of these bits are activated)

Table 251. Request

Description Bytes Example (Hex)

Remote address 1 0x01

Function code 1 0x01


Address of the first digital 0x00
2
output 0x03
0x00
Number of digital outputs 2
0x0C

CRC 2 xx xx

Table 3. Response

Description Bytes Example (Hex)

Remote address 1 0x01

Function code 1 0x01


Number of bytes to store
the state of the digital 1 0x02
outputs
0xFF (LSB)
Digital outputs value 2
0x0F (MSB)

CRC 2 xx xx

❑ In the request response, the LSB of the Digital outputs value contains the value of the first output (output 3). The rest of
the bytes are sent in lowest to highest order. If the number of bits requested is not a multiple of 8, the byte will be filled
with zeros.
❑ Function code 02 – Read discrete inputs
❑ For reading boolean data.
❑ Request and response frames are identical to the function 01.
❑ Function code 03 – Read holding registers
❑ For reading digital signals, measurements and counters.
❑ Example:
 Remote address: 1
 Address: 0400h - Data: 00AAh
 Address: 0401h - Data: 00FFh

Ingeteam Power Technology S.A.


User Manual
491
MODBUS SLAVE PROTOCOL

Table 4. Request

Description Bytes Example (Hex)

Remote address 1 0x01

Function code 1 0x03


0x04
Starting address 2
0x00
0x00
Number of registers (words) 2
0x02

CRC 2 xx xx

Table 5. Response

Description Bytes Example (Hex)

Remote address 1 0x01

Function code 1 0x03

Byte count 1 0x04

0x00
Register value 1 2
0xAA
0x00
Register value 2 2
0xFF

CRC 2 xx xx

❑ Function code 04 – Read input registers


❑ For reading digital signals, measurements and counters.
❑ Request and response frames are identical to the function 03.
❑ Function code 05 – Write single coil
❑ For writing a bit to ON or OFF.
❑ Example:
 Remote address: 1
 Writing command number 24 to 1

Table 6. Request

Description Bytes Example (Hex)

Remote address 1 0x01

Function code 1 0x05


0x00
Command number 2
0x18
0xFF
Writing to 1 2
0x00

CRC 2 xx xx

Ingeteam Power Technology S.A.


User Manual
492
MODBUS SLAVE PROTOCOL

Table 7. Response

Description Bytes Example (Hex)

Remote address 1 0x01

Function code 1 0x05


0x00
Command number 2
0x18
0xFF
Writing to 1 2
0x00

CRC 2 xx xx

❑ Function code 06 – Write single register


For writing a single register.

Example:

 Remote address: 1
 Writing command number 24 to 1

Table 8. Request

Description Bytes Example (Hex)

Remote address 1 0x01

Function code 1 0x06


0x00
Register address 2
0x80
0x00
Number of command to execute 2
0x18

CRC 2 xx xx

Table 9. Response

Description Bytes Example (Hex)

Remote address 1 0x01

Function code 1 0x06


0x00
Register address 2
0x80
0x00
Number of command to execute 2
0x18

CRC 2 xx xx

❑ Function code 15 – Write multiple coils


For writing a bit to ON or OFF.

Example:

 Remote address: 1
 Writing command number 24 to 1

Ingeteam Power Technology S.A.


User Manual
493
MODBUS SLAVE PROTOCOL

Table 10. Response

Description Bytes Example (Hex)

Remote address 1 0x01

Function code 1 0x0F


0x00
Number of command 2
0x18
Number of bits to 0x00
2
be forced 0x01

Byte count 1 0x01

Command value 1 0x01

CRC 2 xx xx

Table 11. Request

Description Bytes Example (Hex)

Remote address 1 0x01

Function code 1 0x0F


0x00
Number of command 2
0x18
0x00
Number of forced bits 2
0x01

CRC 2 xx xx

❑ Function code 16 – Write multiple registers


For writing a single register.

Example:

 Remote address: 1
 Writing command number 24 to 1

Table 12. Request

Description Bytes Example (Hex)

Remote address 1 0x01

Function code 1 0x10


0x00
Register address 2
0x80
Number of registers to be 0x00
2
written (words) 0x01
Byte count 1 0x02

0x00
Number of command to execute 2
0x18

CRC 2 xx xx

Ingeteam Power Technology S.A.


User Manual
494
MODBUS SLAVE PROTOCOL

Table 13. Response

Description Bytes Example (Hex)

Remote address 1 0x01

Function code 1 0x10


0x00
Starting address 2
0x80
Number of written registers 0x00
2
(words) 0x01

CRC 2 xx xx

29.9 TCP/IP MESSAGES

29.9.1 Format
The message contains the following elements:

❑ Header
❑ It contains the following fields:

Length
Fields Description Client Server
(bytes)
Identification of a Modbus Recopied by the
Transaction Initialized by the
2 request/response server from the
identifier client
transaction received request
Recopied by the
Protocol It takes value 0 for Initialized by the
2 server from the
identifier Modbus protocol client
received request

Number of following Initialized by the Initialized by the


Length 2
bytes client (request) server (response)

Recopied by the
Identification of the Initialized by the
Unit identifier 1 server from the
connected slave device client
received request

❑ This fields are transmitted by communications as Big Endian.


❑ Function code
❑ Function code of the request/response. Size: 1 byte. If it is > 127 (bit MSB to 1) it means that the remote has not
performed the required function and will answer with an error code.
❑ Data

TCP/IP complete message:

Transaction Protocol
Length Unit identifier Function code Data
identifier identifier
(2 bytes) (1 byte) (1 byte) (n bytes)
(2 bytes) (2 bytes)

All the messages are sent via TCP to registered port 502.

❑ Master request:

Ingeteam Power Technology S.A.


User Manual
495
MODBUS SLAVE PROTOCOL

 Transaction Id. - Unique per transaction or 0x00


 Protocol Id. - Always 0
 Length - Number of bytes of Unity Id. + Function code + Data
 Unity Id. - Possible values: 0x00,0xFF or remote device number
 Function code
 Data - Number of variable bytes

❑ Slave response:
 Transaction Id. - Copy of the value received from the master device
 Protocol Id. - Copy of the value received from the master device
 Length - Number of bytes of Unity Id. + Function code + Data
 Unity Id. - Copy of the value received from the master device
 Function code
 Data - Number of variable bytes

29.9.2 Examples
The types of message are the same as the serial ones. The address map of the device and the way to treat it is the same as explained
before, only changes the structure of the message to send/receive.

Ingeteam Power Technology S.A.


User Manual
496
CURVES FOR TIMED CHARACTERISTICS 

30. CURVES FOR TIMED CHARACTERISTICS

30.1 CEI 255-4 / BS142 CURVES

Enclosed below are the groups of curves, according to BS142, which correspond to the following types:

❑ Inverse or Normal Inverse


❑ Very Inverse
❑ Extremely Inverse
❑ Short-Time Inverse
❑ Long-Time Inverse
❑ Very Inverse Special Time
❑ User Curve.
These curves comply with the general formula

k tr
T = M  TRECAIDA = M 
 2
 I  −1  I  −1
I  I 
 0  0

In which:

❑ T : trip time (sec)


❑ TDROP : drop time (sec)
❑ M: multiplier (“time dial”). Valid range 0.025 to 1.5, in steps of 0.005
❑ I: Measured current
❑ Io: Pickup current setting
❑ K, , tr: constants which depend on the type of curve:

Inverse / Short-Time Long-Time Extremely Very Inverse


Constants Very inverse
Normal inverse inverse inverse inverse Especial
K 0.14 0.05 120 13.50 80.00 2.60
 0.02 0.04 1 1.00 2.00 1.00
tr 9.7 0.5 120 43.2 58.2 21.2

The following represent the curves which correspond to indexes 0.05, 0.1, 0.2, 0.3, 0.4, 0.5, 0.6, 0.7, 0.8, 0.9 and 1.0 for each type of
characteristic. Bear in mind that there are another 9 curves between each of the two curves illustrated, except between 0.05 and 0.1,
between which there are another 4.

For the values of I/Io greater than 40, the trip time is the correspond time of I/Io=40.

Ingeteam Power Technology S.A.


User Manual
497
CURVES FOR TIMED CHARACTERISTICS 

Inverse or normal inverse curve

k tr
T = M  TRECAIDA = M 
 2
 I  −1  I  −1
I  I 
 0  0

K = 0,14,  = 0,02 tr = 9.7

Theoretical values given by the formula:

M\I/Io 0 0.25 0.5 0.75 1.05 1.10 1.20 1.30 1.50 2.00 2.50 3.00 5.00 10.00 20.00 40.00
0.05 0.485 0.517 0.647 1.109 7.170 3.669 1.916 1.331 0.860 0.501 0.378 0.315 0.214 0.149 0.113 0.091

0.06 0.582 0.621 0.776 1.330 8.604 4.402 2.299 1.597 1.032 0.602 0.454 0.378 0.257 0.178 0.136 0.110

0.07 0.679 0.724 0.905 1.552 10.038 5.136 2.683 1.863 1.204 0.702 0.530 0.441 0.300 0.208 0.159 0.128

0.08 0.776 0.828 1.035 1.774 11.472 5.870 3.066 2.129 1.376 0.802 0.606 0.504 0.342 0.238 0.181 0.146

0.09 0.873 0.931 1.164 1.995 12.906 6.604 3.449 2.395 1.547 0.903 0.681 0.567 0.385 0.267 0.204 0.165

0.10 0.970 1.035 1.293 2.217 14.340 7.337 3.832 2.661 1.719 1.003 0.757 0.630 0.428 0.297 0.227 0.183

0.11 1.067 1.138 1.423 2.439 15.774 8.071 4.216 2.927 1.891 1.103 0.833 0.693 0.471 0.327 0.249 0.201

0.12 1.164 1.242 1.552 2.661 17.208 8.805 4.599 3.193 2.063 1.203 0.908 0.756 0.514 0.356 0.272 0.219

0.13 1.261 1.345 1.681 2.882 18.642 9.539 4.982 3.459 2.235 1.304 0.984 0.819 0.556 0.386 0.295 0.238

0.14 1.358 1.449 1.811 3.104 20.076 10.272 5.365 3.725 2.407 1.404 1.060 0.882 0.599 0.416 0.317 0.256

0.15 1.455 1.552 1.940 3.326 21.510 11.006 5.749 3.992 2.579 1.504 1.135 0.945 0.642 0.446 0.340 0.274

0.16 1.552 1.655 2.069 3.547 22.944 11.740 6.132 4.258 2.751 1.605 1.211 1.008 0.685 0.475 0.363 0.293

0.17 1.649 1.759 2.199 3.769 24.378 12.474 6.515 4.524 2.923 1.705 1.287 1.071 0.728 0.505 0.385 0.311

0.18 1.746 1.862 2.328 3.991 25.812 13.207 6.898 4.790 3.095 1.805 1.363 1.134 0.770 0.535 0.408 0.329

0.19 1.843 1.966 2.457 4.213 27.246 13.941 7.282 5.056 3.267 1.906 1.438 1.197 0.813 0.564 0.431 0.347

0.20 1.940 2.069 2.587 4.434 28.680 14.675 7.665 5.322 3.439 2.006 1.514 1.260 0.856 0.594 0.453 0.366

0.25 2.425 2.587 3.233 5.543 35.850 18.344 9.581 6.653 4.299 2.507 1.892 1.575 1.070 0.743 0.567 0.457

0.30 2.910 3.104 3.880 6.651 43.021 22.012 11.497 7.983 5.158 3.009 2.271 1.891 1.284 0.891 0.680 0.549

0.35 3.395 3.621 4.527 7.760 50.191 25.681 13.413 9.314 6.018 3.510 2.649 2.206 1.498 1.040 0.794 0.640

0.40 3.880 4.139 5.173 8.869 57.361 29.350 15.329 10.644 6.878 4.012 3.028 2.521 1.712 1.188 0.907 0.731

0.45 4.365 4.656 5.820 9.977 64.531 33.018 17.246 11.975 7.737 4.513 3.406 2.836 1.926 1.337 1.020 0.823

0.50 4.850 5.173 6.467 11.086 71.701 36.687 19.162 13.305 8.597 5.015 3.785 3.151 2.140 1.485 1.134 0.914

0.55 5.335 5.691 7.113 12.194 78.871 40.356 21.078 14.636 9.457 5.516 4.163 3.466 2.354 1.634 1.247 1.006

0.60 5.820 6.208 7.760 13.303 86.041 44.025 22.994 15.966 10.317 6.017 4.542 3.781 2.568 1.782 1.360 1.097

0.65 6.305 6.725 8.407 14.411 93.211 47.693 24.910 17.297 11.176 6.519 4.920 4.096 2.782 1.931 1.474 1.188

0.70 6.790 7.243 9.053 15.520 100.381 51.362 26.827 18.627 12.036 7.020 5.299 4.411 2.996 2.079 1.587 1.280

0.75 7.275 7.760 9.700 16.629 107.551 55.031 28.743 19.958 12.896 7.522 5.677 4.726 3.210 2.228 1.701 1.371

0.80 7.760 8.277 10.347 17.737 114.721 58.700 30.659 21.288 13.755 8.023 6.056 5.042 3.424 2.376 1.814 1.463

0.85 8.245 8.795 10.993 18.846 121.891 62.368 32.575 22.619 14.615 8.525 6.434 5.357 3.638 2.525 1.927 1.554

0.90 8.730 9.312 11.640 19.954 129.062 66.037 34.491 23.949 15.475 9.026 6.813 5.672 3.852 2.674 2.041 1.646

0.95 9.215 9.829 12.287 21.063 136.232 69.706 36.408 25.280 16.335 9.528 7.191 5.987 4.066 2.822 2.154 1.737

1.00 9.700 10.347 12.933 22.171 143.402 73.374 38.324 26.611 17.194 10.029 7.570 6.302 4.280 2.971 2.267 1.828

1.05 10.185 10.864 13.580 23.280 150.572 77.043 40.240 27.941 18.054 10.530 7.948 6.617 4.494 3.119 2.381 1.920

Ingeteam Power Technology S.A.


User Manual
498
CURVES FOR TIMED CHARACTERISTICS 

Ingeteam Power Technology S.A.


User Manual
499
CURVES FOR TIMED CHARACTERISTICS 

Long duration curve (IEC)

k tr
T = M  TRECAIDA = M 
 2
 I  −1  I  −1
I  I 
 0
@Fig.160.png-H:61,65-W:103,7@ @Fig.161.png-H:62,2-W:145,75@
 0

K = 120,  = 1 tr = 120

Theoretical values given by the formula:

M\I/Io 0 0.25 0.50 0.75 1.05 1.10 1.20 1.30 1.50 2.00 2.50 3.00 5.00 10.00 20.00 40.00
0.05 6.000 6.400 8.000 13.714 120.000 60.000 30.000 20.000 12.000 6.000 4.000 3.000 1.500 0.667 0.316 0.154

0.06 7.200 7.680 9.600 16.457 144.000 72.000 36.000 24.000 14.400 7.200 4.800 3.600 1.800 0.800 0.379 0.185

0.07 8.400 8.960 11.200 19.200 168.000 84.000 42.000 28.000 16.800 8.400 5.600 4.200 2.100 0.933 0.442 0.215

0.08 9.600 10.240 12.800 21.943 192.000 96.000 48.000 32.000 19.200 9.600 6.400 4.800 2.400 1.067 0.505 0.246

0.09 10.800 11.520 14.400 24.686 216.000 108.000 54.000 36.000 21.600 10.800 7.200 5.400 2.700 1.200 0.568 0.277

0.10 12.000 12.800 16.000 27.429 240.000 120.000 60.000 40.000 24.000 12.000 8.000 6.000 3.000 1.333 0.632 0.308

0.11 13.200 14.080 17.600 30.171 264.000 132.000 66.000 44.000 26.400 13.200 8.800 6.600 3.300 1.467 0.695 0.338

0.12 14.400 15.360 19.200 32.914 288.000 144.000 72.000 48.000 28.800 14.400 9.600 7.200 3.600 1.600 0.758 0.369

0.13 15.600 16.640 20.800 35.657 312.000 156.000 78.000 52.000 31.200 15.600 10.400 7.800 3.900 1.733 0.821 0.400

0.14 16.800 17.920 22.400 38.400 336.000 168.000 84.000 56.000 33.600 16.800 11.200 8.400 4.200 1.867 0.884 0.431

0.15 18.000 19.200 24.000 41.143 360.000 180.000 90.000 60.000 36.000 18.000 12.000 9.000 4.500 2.000 0.947 0.462

0.16 19.200 20.480 25.600 43.886 384.000 192.000 96.000 64.000 38.400 19.200 12.800 9.600 4.800 2.133 1.011 0.492

0.17 20.400 21.760 27.200 46.629 408.000 204.000 102.000 68.000 40.800 20.400 13.600 10.200 5.100 2.267 1.074 0.523

0.18 21.600 23.040 28.800 49.371 432.000 216.000 108.000 72.000 43.200 21.600 14.400 10.800 5.400 2.400 1.137 0.554

0.19 22.800 24.320 30.400 52.114 456.000 228.000 114.000 76.000 45.600 22.800 15.200 11.400 5.700 2.533 1.200 0.585

0.20 24.000 25.600 32.000 54.857 480.001 240.000 120.000 80.000 48.000 24.000 16.000 12.000 6.000 2.667 1.263 0.615

0.25 30.000 32.000 40.000 68.571 600.001 300.000 150.000 100.000 60.000 30.000 20.000 15.000 7.500 3.333 1.579 0.769

0.30 36.000 38.400 48.000 82.286 720.001 360.000 180.000 120.000 72.000 36.000 24.000 18.000 9.000 4.000 1.895 0.923

0.35 42.000 44.800 56.000 96.000 840.001 420.000 210.000 140.000 84.000 42.000 28.000 21.000 10.500 4.667 2.211 1.077

0.40 48.000 51.200 64.000 109.714 960.001 480.000 240.000 160.000 96.000 48.000 32.000 24.000 12.000 5.333 2.526 1.231

0.45 54.000 57.600 72.000 123.429 1080.001 540.000 270.000 180.000 108.000 54.000 36.000 27.000 13.500 6.000 2.842 1.385

0.50 60.000 64.000 80.000 137.143 1200.001 600.000 300.000 200.000 120.000 60.000 40.000 30.000 15.000 6.667 3.158 1.538

0.55 66.000 70.400 88.000 150.857 1320.001 660.000 330.000 220.000 132.000 66.000 44.000 33.000 16.500 7.333 3.474 1.692

0.60 72.000 76.800 96.000 164.571 1440.002 720.000 360.000 240.000 144.000 72.000 48.000 36.000 18.000 8.000 3.789 1.846

0.65 78.000 83.200 104.000 178.286 1560.002 780.000 390.000 260.000 156.000 78.000 52.000 39.000 19.500 8.667 4.105 2.000

0.70 84.000 89.600 112.000 192.000 1680.002 840.000 420.000 280.000 168.000 84.000 56.000 42.000 21.000 9.333 4.421 2.154

0.75 90.000 96.000 120.000 205.714 1800.002 900.000 450.000 300.000 180.000 90.000 60.000 45.000 22.500 10.000 4.737 2.308

0.80 96.000 102.400 128.000 219.429 1920.002 960.000 480.000 320.000 192.000 96.000 64.000 48.000 24.000 10.667 5.053 2.462

0.85 102.000 108.800 136.000 233.143 2040.002 1020.000 510.000 340.000 204.000 102.000 68.000 51.000 25.500 11.333 5.368 2.615

0.90 108.000 115.200 144.000 246.857 2160.002 1080.000 540.000 360.000 216.000 108.000 72.000 54.000 27.000 12.000 5.684 2.769

0.95 114.000 121.600 152.000 260.571 2280.003 1140.000 570.000 380.000 228.000 114.000 76.000 57.000 28.500 12.667 6.000 2.923

1.00 120.000 128.000 160.000 274.286 2400.003 1200.000 600.000 400.000 240.000 120.000 80.000 60.000 30.000 13.333 6.316 3.077

1.05 126.000 134.400 168.000 288.000 2520.003 1260.000 630.000 420.000 252.000 126.000 84.000 63.000 31.500 14.000 6.632 3.231

Ingeteam Power Technology S.A.


User Manual
500
CURVES FOR TIMED CHARACTERISTICS 

Ingeteam Power Technology S.A.


User Manual
501
CURVES FOR TIMED CHARACTERISTICS 

Short duration curve IEC

k tr
T = M  TRECAIDA = M 
 2
 I  −1  I  −1
I  I 
 0  0

K = 0.05,  = 0.04 tr = 0.5

Theoretical values given by the formula:

M\I/Io 0 0.25 0.5 0.75 1.05 1.10 1.20 1.30 1.50 2.00 2.50 3.00 5.00 10.00 20.00 40.00
0.05 0.025 0.027 0.033 0.057 1.280 0.655 0.342 0.237 0.153 0.089 0.067 0.056 0.038 0.026 0.020 0.016

0.06 0.030 0.032 0.040 0.069 1.536 0.785 0.410 0.284 0.183 0.107 0.080 0.067 0.045 0.031 0.024 0.019

0.07 0.035 0.037 0.047 0.080 1.792 0.916 0.478 0.332 0.214 0.124 0.094 0.078 0.053 0.036 0.027 0.022

0.08 0.040 0.043 0.053 0.091 2.048 1.047 0.546 0.379 0.245 0.142 0.107 0.089 0.060 0.041 0.031 0.025

0.09 0.045 0.048 0.060 0.103 2.304 1.178 0.615 0.427 0.275 0.160 0.121 0.100 0.068 0.047 0.035 0.028

0.10 0.050 0.053 0.067 0.114 2.559 1.309 0.683 0.474 0.306 0.178 0.134 0.111 0.075 0.052 0.039 0.031

0.11 0.055 0.059 0.073 0.126 2.815 1.440 0.751 0.521 0.336 0.196 0.147 0.122 0.083 0.057 0.043 0.035

0.12 0.060 0.064 0.080 0.137 3.071 1.571 0.820 0.569 0.367 0.213 0.161 0.134 0.090 0.062 0.047 0.038

0.13 0.065 0.069 0.087 0.149 3.327 1.702 0.888 0.616 0.398 0.231 0.174 0.145 0.098 0.067 0.051 0.041

0.14 0.070 0.075 0.093 0.160 3.583 1.833 0.956 0.664 0.428 0.249 0.188 0.156 0.105 0.073 0.055 0.044

0.15 0.075 0.080 0.100 0.171 3.839 1.964 1.025 0.711 0.459 0.267 0.201 0.167 0.113 0.078 0.059 0.047

0.16 0.080 0.085 0.107 0.183 4.095 2.094 1.093 0.758 0.489 0.285 0.214 0.178 0.120 0.083 0.063 0.050

0.17 0.085 0.091 0.113 0.194 4.351 2.225 1.161 0.806 0.520 0.302 0.228 0.189 0.128 0.088 0.067 0.053

0.18 0.090 0.096 0.120 0.206 4.607 2.356 1.230 0.853 0.550 0.320 0.241 0.200 0.135 0.093 0.071 0.057

0.19 0.095 0.101 0.127 0.217 4.863 2.487 1.298 0.900 0.581 0.338 0.254 0.211 0.143 0.098 0.075 0.060

0.20 0.100 0.107 0.133 0.229 5.119 2.618 1.366 0.948 0.612 0.356 0.268 0.223 0.150 0.104 0.079 0.063

0.25 0.125 0.133 0.167 0.286 6.399 3.273 1.708 1.185 0.764 0.445 0.335 0.278 0.188 0.130 0.098 0.079

0.30 0.150 0.160 0.200 0.343 7.678 3.927 2.049 1.422 0.917 0.534 0.402 0.334 0.226 0.155 0.118 0.094

0.35 0.175 0.187 0.233 0.400 8.958 4.582 2.391 1.659 1.070 0.622 0.469 0.390 0.263 0.181 0.137 0.110

0.40 0.200 0.213 0.267 0.457 10.238 5.236 2.732 1.896 1.223 0.711 0.536 0.445 0.301 0.207 0.157 0.126

0.45 0.225 0.240 0.300 0.514 11.518 5.891 3.074 2.133 1.376 0.800 0.603 0.501 0.338 0.233 0.177 0.142

0.50 0.250 0.267 0.333 0.571 12.797 6.545 3.416 2.370 1.529 0.889 0.670 0.556 0.376 0.259 0.196 0.157

0.55 0.275 0.293 0.367 0.629 14.077 7.200 3.757 2.607 1.682 0.978 0.737 0.612 0.414 0.285 0.216 0.173

0.60 0.300 0.320 0.400 0.686 15.357 7.854 4.099 2.844 1.835 1.067 0.804 0.668 0.451 0.311 0.236 0.189

0.65 0.325 0.347 0.433 0.743 16.637 8.509 4.440 3.081 1.988 1.156 0.871 0.723 0.489 0.337 0.255 0.204

0.70 0.350 0.373 0.467 0.800 17.916 9.163 4.782 3.318 2.141 1.245 0.938 0.779 0.526 0.363 0.275 0.220

0.75 0.375 0.400 0.500 0.857 19.196 9.818 5.123 3.555 2.293 1.334 1.005 0.835 0.564 0.389 0.295 0.236

0.80 0.400 0.427 0.533 0.914 20.476 10.472 5.465 3.792 2.446 1.423 1.071 0.890 0.602 0.415 0.314 0.252

0.85 0.425 0.453 0.567 0.971 21.756 11.127 5.806 4.029 2.599 1.512 1.138 0.946 0.639 0.441 0.334 0.267

0.90 0.450 0.480 0.600 1.029 23.035 11.781 6.148 4.265 2.752 1.601 1.205 1.002 0.677 0.466 0.353 0.283

0.95 0.475 0.507 0.633 1.086 24.315 12.436 6.489 4.502 2.905 1.690 1.272 1.057 0.714 0.492 0.373 0.299

1.00 0.500 0.533 0.667 1.143 25.595 13.090 6.831 4.739 3.058 1.778 1.339 1.113 0.752 0.518 0.393 0.314

1.05 0.525 0.560 0.700 1.200 26.875 13.745 7.173 4.976 3.211 1.867 1.406 1.169 0.790 0.544 0.412 0.330

Ingeteam Power Technology S.A.


User Manual
502
CURVES FOR TIMED CHARACTERISTICS 

Ingeteam Power Technology S.A.


User Manual
503
CURVES FOR TIMED CHARACTERISTICS 

Very inverse curve

k tr
T = M  TRECAIDA = M 
 2
 I  −1  I  −1
I  I 
 0  0

K = 13,5,  = 1 tr = 43.2

Theoretical values given by the formula:

M\I/Io 0 0.25 0.5 0.75 1.05 1.10 1.20 1.30 1.50 2.00 2.50 3.00 5.00 10.00 20.00 40.00
0.05 2.160 2.304 2.880 4.937 13.500 6.750 3.375 2.250 1.350 0.675 0.450 0.338 0.169 0.075 0.036 0.017

0.06 2.592 2.765 3.456 5.925 16.200 8.100 4.050 2.700 1.620 0.810 0.540 0.405 0.203 0.090 0.043 0.021

0.07 3.024 3.226 4.032 6.912 18.900 9.450 4.725 3.150 1.890 0.945 0.630 0.472 0.236 0.105 0.050 0.024

0.08 3.456 3.686 4.608 7.899 21.600 10.800 5.400 3.600 2.160 1.080 0.720 0.540 0.270 0.120 0.057 0.028

0.09 3.888 4.147 5.184 8.887 24.300 12.150 6.075 4.050 2.430 1.215 0.810 0.607 0.304 0.135 0.064 0.031

0.10 4.320 4.608 5.760 9.874 27.000 13.500 6.750 4.500 2.700 1.350 0.900 0.675 0.337 0.150 0.071 0.035

0.11 4.752 5.069 6.336 10.862 29.700 14.850 7.425 4.950 2.970 1.485 0.990 0.742 0.371 0.165 0.078 0.038

0.12 5.184 5.530 6.912 11.849 32.400 16.200 8.100 5.400 3.240 1.620 1.080 0.810 0.405 0.180 0.085 0.042

0.13 5.616 5.990 7.488 12.837 35.100 17.550 8.775 5.850 3.510 1.755 1.170 0.877 0.439 0.195 0.092 0.045

0.14 6.048 6.451 8.064 13.824 37.800 18.900 9.450 6.300 3.780 1.890 1.260 0.945 0.472 0.210 0.099 0.048

0.15 6.480 6.912 8.640 14.811 40.500 20.250 10.125 6.750 4.050 2.025 1.350 1.013 0.506 0.225 0.107 0.052

0.16 6.912 7.373 9.216 15.799 43.200 21.600 10.800 7.200 4.320 2.160 1.440 1.080 0.540 0.240 0.114 0.055

0.17 7.344 7.834 9.792 16.786 45.900 22.950 11.475 7.650 4.590 2.295 1.530 1.148 0.574 0.255 0.121 0.059

0.18 7.776 8.294 10.368 17.774 48.600 24.300 12.150 8.100 4.860 2.430 1.620 1.215 0.608 0.270 0.128 0.062

0.19 8.208 8.755 10.944 18.761 51.300 25.650 12.825 8.550 5.130 2.565 1.710 1.283 0.641 0.285 0.135 0.066

0.20 8.640 9.216 11.520 19.749 54.000 27.000 13.500 9.000 5.400 2.700 1.800 1.350 0.675 0.300 0.142 0.069

0.25 10.800 11.520 14.400 24.686 67.500 33.750 16.875 11.250 6.750 3.375 2.250 1.688 0.844 0.375 0.178 0.087

0.30 12.960 13.824 17.280 29.623 81.000 40.500 20.250 13.500 8.100 4.050 2.700 2.025 1.013 0.450 0.213 0.104

0.35 15.120 16.128 20.160 34.560 94.500 47.250 23.625 15.750 9.450 4.725 3.150 2.363 1.181 0.525 0.249 0.121

0.40 17.280 18.432 23.040 39.497 108.000 54.000 27.000 18.000 10.800 5.400 3.600 2.700 1.350 0.600 0.284 0.138

0.45 19.440 20.736 25.920 44.434 121.500 60.750 30.375 20.250 12.150 6.075 4.050 3.038 1.519 0.675 0.320 0.156

0.50 21.600 23.040 28.800 49.371 135.000 67.500 33.750 22.500 13.500 6.750 4.500 3.375 1.688 0.750 0.355 0.173

0.55 23.760 25.344 31.680 54.309 148.500 74.250 37.125 24.750 14.850 7.425 4.950 3.713 1.856 0.825 0.391 0.190

0.60 25.920 27.648 34.560 59.246 162.000 81.000 40.500 27.000 16.200 8.100 5.400 4.050 2.025 0.900 0.426 0.208

0.65 28.080 29.952 37.440 64.183 175.500 87.750 43.875 29.250 17.550 8.775 5.850 4.388 2.194 0.975 0.462 0.225

0.70 30.240 32.256 40.320 69.120 189.000 94.500 47.250 31.500 18.900 9.450 6.300 4.725 2.363 1.050 0.497 0.242

0.75 32.400 34.560 43.200 74.057 202.500 101.25 50.625 33.750 20.250 10.125 6.750 5.063 2.531 1.125 0.533 0.260

0.80 34.560 36.864 46.080 78.994 216.000 108.00 54.000 36.000 21.600 10.800 7.200 5.400 2.700 1.200 0.568 0.277

0.85 36.720 39.168 48.960 83.931 229.500 114.75 57.375 38.250 22.950 11.475 7.650 5.738 2.869 1.275 0.604 0.294

0.90 38.880 41.472 51.840 88.869 243.000 121.50 60.750 40.500 24.300 12.150 8.100 6.075 3.038 1.350 0.639 0.312

0.95 41.040 43.776 54.720 93.806 256.500 128.25 64.125 42.750 25.650 12.825 8.550 6.413 3.206 1.425 0.675 0.329

1.00 43.200 46.080 57.600 98.743 270.000 135.00 67.500 45.000 27.000 13.500 9.000 6.750 3.375 1.500 0.711 0.346

1.05 45.360 48.384 60.480 103.68 283.500 141.75 70.875 47.250 28.350 14.175 9.450 7.088 3.544 1.575 0.746 0.363

Ingeteam Power Technology S.A.


User Manual
504
CURVES FOR TIMED CHARACTERISTICS 

Ingeteam Power Technology S.A.


User Manual
505
CURVES FOR TIMED CHARACTERISTICS 

Extremely inverse curve

k tr
T = M  TRECAIDA = M 
 2
 I  −1  I  −1
I  I 
 0  0

K = 80,  = 2 tr =58.2

Theoretical values given by the formula:

M\I/Io 0 0.25 0.5 0.75 1.05 1.10 1.20 1.30 1.50 2.00 2.50 3.00 5.00 10.00 20.00 40.00
0.05 2.910 3.104 3.880 6.651 39.024 19.048 9.091 5.797 3.200 1.333 0.762 0.500 0.167 0.040 0.010 0.003

0.06 3.492 3.725 4.656 7.982 46.829 22.857 10.909 6.957 3.840 1.600 0.914 0.600 0.200 0.048 0.012 0.003

0.07 4.074 4.346 5.432 9.312 54.634 26.667 12.727 8.116 4.480 1.867 1.067 0.700 0.233 0.057 0.014 0.004

0.08 4.656 4.966 6.208 10.642 62.439 30.476 14.545 9.275 5.120 2.133 1.219 0.800 0.267 0.065 0.016 0.004

0.09 5.238 5.587 6.984 11.973 70.244 34.286 16.364 10.435 5.760 2.400 1.371 0.900 0.300 0.073 0.018 0.005

0.10 5.820 6.208 7.760 13.303 78.049 38.095 18.182 11.594 6.400 2.667 1.524 1.000 0.333 0.081 0.020 0.005

0.11 6.402 6.829 8.536 14.633 85.854 41.905 20.000 12.754 7.040 2.933 1.676 1.100 0.367 0.089 0.022 0.006

0.12 6.984 7.450 9.312 15.963 93.659 45.714 21.818 13.913 7.680 3.200 1.829 1.200 0.400 0.097 0.024 0.006

0.13 7.566 8.070 10.088 17.294 101.464 49.524 23.636 15.072 8.320 3.467 1.981 1.300 0.433 0.105 0.026 0.007

0.14 8.148 8.691 10.864 18.624 109.268 53.333 25.455 16.232 8.960 3.733 2.133 1.400 0.467 0.113 0.028 0.007

0.15 8.730 9.312 11.640 19.954 117.073 57.143 27.273 17.391 9.600 4.000 2.286 1.500 0.500 0.121 0.030 0.008

0.16 9.312 9.933 12.416 21.285 124.878 60.952 29.091 18.551 10.240 4.267 2.438 1.600 0.533 0.129 0.032 0.008

0.17 9.894 10.554 13.192 22.615 132.683 64.762 30.909 19.710 10.880 4.533 2.590 1.700 0.567 0.137 0.034 0.009

0.18 10.476 11.174 13.968 23.945 140.488 68.571 32.727 20.870 11.520 4.800 2.743 1.800 0.600 0.145 0.036 0.009

0.19 11.058 11.795 14.744 25.275 148.293 72.381 34.545 22.029 12.160 5.067 2.895 1.900 0.633 0.154 0.038 0.010

0.20 11.640 12.416 15.520 26.606 156.098 76.190 36.364 23.188 12.800 5.333 3.048 2.000 0.667 0.162 0.040 0.010

0.25 14.550 15.520 19.400 33.257 195.122 95.238 45.455 28.986 16.000 6.667 3.810 2.500 0.833 0.202 0.050 0.013

0.30 17.460 18.624 23.280 39.909 234.147 114.286 54.545 34.783 19.200 8.000 4.571 3.000 1.000 0.242 0.060 0.015

0.35 20.370 21.728 27.160 46.560 273.171 133.333 63.636 40.580 22.400 9.333 5.333 3.500 1.167 0.283 0.070 0.018

0.40 23.280 24.832 31.040 53.211 312.195 152.381 72.727 46.377 25.600 10.667 6.095 4.000 1.333 0.323 0.080 0.020

0.45 26.190 27.936 34.920 59.863 351.220 171.429 81.818 52.174 28.800 12.000 6.857 4.500 1.500 0.364 0.090 0.023

0.50 29.100 31.040 38.800 66.514 390.244 190.476 90.909 57.971 32.000 13.333 7.619 5.000 1.667 0.404 0.100 0.025

0.55 32.010 34.144 42.680 73.166 429.269 209.524 100.000 63.768 35.200 14.667 8.381 5.500 1.833 0.444 0.110 0.028

0.60 34.920 37.248 46.560 79.817 468.293 228.571 109.091 69.565 38.400 16.000 9.143 6.000 2.000 0.485 0.120 0.030

0.65 37.830 40.352 50.440 86.469 507.318 247.619 118.182 75.362 41.600 17.333 9.905 6.500 2.167 0.525 0.130 0.033

0.70 40.740 43.456 54.320 93.120 546.342 266.667 127.273 81.159 44.800 18.667 10.667 7.000 2.333 0.566 0.140 0.035

0.75 43.650 46.560 58.200 99.771 585.367 285.714 136.364 86.957 48.000 20.000 11.429 7.500 2.500 0.606 0.150 0.038

0.80 46.560 49.664 62.080 106.423 624.391 304.762 145.455 92.754 51.200 21.333 12.190 8.000 2.667 0.646 0.160 0.040

0.85 49.470 52.768 65.960 113.074 663.415 323.810 154.545 98.551 54.400 22.667 12.952 8.500 2.833 0.687 0.170 0.043

0.90 52.380 55.872 69.840 119.726 702.440 342.857 163.636 104.348 57.600 24.000 13.714 9.000 3.000 0.727 0.180 0.045

0.95 55.290 58.976 73.720 126.377 741.464 361.905 172.727 110.145 60.800 25.333 14.476 9.500 3.167 0.768 0.190 0.048

1.00 58.200 62.080 77.600 133.029 780.489 380.952 181.818 115.942 64.000 26.667 15.238 10.000 3.333 0.808 0.201 0.050

1.05 61.110 65.184 81.480 139.680 819.513 400.000 190.909 121.739 67.200 28.000 16.000 10.500 3.500 0.848 0.211 0.053

Ingeteam Power Technology S.A.


User Manual
506
CURVES FOR TIMED CHARACTERISTICS 

Ingeteam Power Technology S.A.


User Manual
507
CURVES FOR TIMED CHARACTERISTICS 

Very Inverse Special Curve

k tr
T = M  TRECAIDA = M 
 2
 I  −1  I  −1
I  I 
 0
@Fig.170.png-H:61,65-W:103,7@ @Fig.171.png-H:62,2-W:145,75@
 0
K = 2,6 =1

Theoretical values given by the formula:

M \ I/Io 1.05 1.10 1.20 1.30 1.40 1.50 2.00 2.50 3.00 4.00 5.00 7.00 10.00 12.00 15.00 20.00 30.00 40.00
0.05 2.600 1.300 0.650 0.433 0.325 0.260 0.130 0.087 0.065 0.043 0.032 0.022 0.014 0.012 0.009 0.007 0.004 0.003

0.06 3.120 1.560 0.780 0.520 0.390 0.312 0.156 0.104 0.078 0.052 0.039 0.026 0.017 0.014 0.011 0.008 0.005 0.004

0.07 3.640 1.820 0.910 0.607 0.455 0.364 0.182 0.121 0.091 0.061 0.045 0.030 0.020 0.017 0.013 0.010 0.006 0.005

0.08 4.160 2.080 1.040 0.693 0.520 0.416 0.208 0.139 0.104 0.069 0.052 0.035 0.023 0.019 0.015 0.011 0.007 0.005

0.09 4.680 2.340 1.170 0.780 0.585 0.468 0.234 0.156 0.117 0.078 0.058 0.039 0.026 0.021 0.017 0.012 0.008 0.006

0.10 5.200 2.600 1.300 0.867 0.650 0.520 0.260 0.173 0.130 0.087 0.065 0.043 0.029 0.024 0.019 0.014 0.009 0.007

0.11 5.720 2.860 1.430 0.953 0.715 0.572 0.286 0.191 0.143 0.095 0.071 0.048 0.032 0.026 0.020 0.015 0.010 0.007

0.12 6.240 3.120 1.560 1.040 0.780 0.624 0.312 0.208 0.156 0.104 0.078 0.052 0.035 0.028 0.022 0.016 0.011 0.008

0.13 6.760 3.380 1.690 1.127 0.845 0.676 0.338 0.225 0.169 0.113 0.084 0.056 0.038 0.031 0.024 0.018 0.012 0.009

0.14 7.280 3.640 1.820 1.213 0.910 0.728 0.364 0.243 0.182 0.121 0.091 0.061 0.040 0.033 0.026 0.019 0.013 0.009

0.15 7.800 3.900 1.950 1.300 0.975 0.780 0.390 0.260 0.195 0.130 0.098 0.065 0.043 0.035 0.028 0.021 0.013 0.010

0.16 8.320 4.160 2.080 1.387 1.040 0.832 0.416 0.277 0.208 0.139 0.104 0.069 0.046 0.038 0.030 0.022 0.014 0.011

0.17 8.840 4.420 2.210 1.473 1.105 0.884 0.442 0.295 0.221 0.147 0.111 0.074 0.049 0.040 0.032 0.023 0.015 0.011

0.18 9.360 4.680 2.340 1.560 1.170 0.936 0.468 0.312 0.234 0.156 0.117 0.078 0.052 0.043 0.033 0.025 0.016 0.012

0.19 9.880 4.940 2.470 1.647 1.235 0.988 0.494 0.329 0.247 0.165 0.124 0.082 0.055 0.045 0.035 0.026 0.017 0.013

0.20 10.400 5.200 2.600 1.733 1.300 1.040 0.520 0.347 0.260 0.173 0.130 0.087 0.058 0.047 0.037 0.027 0.018 0.013

0.25 13.000 6.500 3.250 2.167 1.625 1.300 0.650 0.433 0.325 0.217 0.163 0.108 0.072 0.059 0.046 0.034 0.022 0.017

0.30 15.600 7.800 3.900 2.600 1.950 1.560 0.780 0.520 0.390 0.260 0.195 0.130 0.087 0.071 0.056 0.041 0.027 0.020

0.35 18.200 9.100 4.550 3.033 2.275 1.820 0.910 0.607 0.455 0.303 0.228 0.152 0.101 0.083 0.065 0.048 0.031 0.023

0.40 20.800 10.400 5.200 3.467 2.600 2.080 1.040 0.693 0.520 0.347 0.260 0.173 0.116 0.095 0.074 0.055 0.036 0.027

0.45 23.400 11.700 5.850 3.900 2.925 2.340 1.170 0.780 0.585 0.390 0.293 0.195 0.130 0.106 0.084 0.062 0.040 0.030

0.50 26.000 13.000 6.500 4.333 3.250 2.600 1.300 0.867 0.650 0.433 0.325 0.217 0.144 0.118 0.093 0.068 0.045 0.033

0.55 28.600 14.300 7.150 4.767 3.575 2.860 1.430 0.953 0.715 0.477 0.358 0.238 0.159 0.130 0.102 0.075 0.049 0.037

0.60 31.200 15.600 7.800 5.200 3.900 3.120 1.560 1.040 0.780 0.520 0.390 0.260 0.173 0.142 0.111 0.082 0.054 0.040

0.65 33.800 16.900 8.450 5.633 4.225 3.380 1.690 1.127 0.845 0.563 0.423 0.282 0.188 0.154 0.121 0.089 0.058 0.043

0.70 36.400 18.200 9.100 6.067 4.550 3.640 1.820 1.213 0.910 0.607 0.455 0.303 0.202 0.165 0.130 0.096 0.063 0.047

0.75 39.000 19.500 9.750 6.500 4.875 3.900 1.950 1.300 0.975 0.650 0.488 0.325 0.217 0.177 0.139 0.103 0.067 0.050

0.80 41.600 20.800 10.400 6.933 5.200 4.160 2.080 1.387 1.040 0.693 0.520 0.347 0.231 0.189 0.149 0.109 0.072 0.053

0.85 44.200 22.100 11.050 7.367 5.525 4.420 2.210 1.473 1.105 0.737 0.553 0.368 0.246 0.201 0.158 0.116 0.076 0.057

0.90 46.800 23.400 11.700 7.800 5.850 4.680 2.340 1.560 1.170 0.780 0.585 0.390 0.260 0.213 0.167 0.123 0.081 0.060

0.95 49.400 24.700 12.350 8.233 6.175 4.940 2.470 1.647 1.235 0.823 0.618 0.412 0.274 0.225 0.176 0.130 0.085 0.063

1.00 52.000 26.000 13.000 8.667 6.500 5.200 2.600 1.733 1.300 0.867 0.650 0.433 0.289 0.236 0.186 0.137 0.090 0.067

1.05 54.600 27.300 13.650 9.100 6.825 5.460 2.730 1.820 1.365 0.910 0.683 0.455 0.303 0.248 0.195 0.144 0.094 0.070

Ingeteam Power Technology S.A.


User Manual
508
CURVES FOR TIMED CHARACTERISTICS 

Ingeteam Power Technology S.A.


User Manual
509
CURVES FOR TIMED CHARACTERISTICS 

30.2 ANSI CURVES

Enclosed below are the groups of curves, according to ANSI, which correspond to the following types:

❑ Normal Inverse.
❑ Very Inverse.
❑ Extremely Inverse.
❑ Moderate Inverse.
These curves comply with the general formula

T = M   A + 
B D E tr
+ + TRECAIDA = M 
  − CI 2 3
 I   I − C  I − C  2
 I  −1
 0  I  I  I 
  0   0    0
@Fig.172.png-H:47,8-W:219,45@ @Fig.173.png-H:51,25-W:119,25@

in which:

❑ T : trip time (sec)


❑ TDROP : drop time (sec)
❑ M : multiplier (“time dial”). Valid range 0.05 to 30.0, in steps of 0.1
❑ I: Measured current
❑ Io: Pickup current setting
❑ A, B, C, D, E, tr: constants which depend on the type of curve:

Constants Inverse. Very inverse Extremely inverse Moderate inverse


A 0.0274 0.0615 0.0399 0.1735
B 2.2614 0.7989 0.2294 0.6791
C 0.3000 0.3400 0.5000 0.8000
D -4.1899 -0.2840 3.0094 -0.0800
E 9.1272 4.0505 0.7222 0.1271
tr 0.99 4.678 6.008 1.2

The following represent the curves which correspond to indexes 0.5, 1.0, 2.0, 3.0, 4.0, 6.0, 8.0, 10.0, 15.0, 20.0 and 30.0 for each type
of characteristic. Take into account that between every two curves differentiated in 1.0 there are another 9 curves.

For the values of I/Io greater than 40, the trip time is the correspond time of I/Io=40.

Ingeteam Technology S.A.


User Manual 510
CURVES FOR TIMED CHARACTERISTICS 

Normal inverse curve

T = M   A + 
B D E tr
+ + TRECAIDA = M 
  I − C 2 3
 I   I − C  I − C  2
 I  −1
 0  I  I  I 
  0   0    0
@Fig.174.png-H:54,7-W:250@ @Fig.175.png-H:61,65-W:143,4@

A = 0.0274, B = 2.2614, C = 0.3000, D = -4.1899, E = 9.1272 tr = 0.99

Theoretical values given by the formula:

M \ I/Io 0 0.25 0.5 0.75 1.05 1.10 1.20 1.30 1.50 2.00 2.50 3.00 5.00 10.00 20.00 40.00
0.5 0.495 0.528 0.660 1.131 8.614 7.067 4.944 3.613 2.142 0.883 0.523 0.377 0.203 0.113 0.066 0.041

1.0 0.990 1.056 1.320 2.263 17.229 14.134 9.888 7.226 4.284 1.766 1.047 0.754 0.407 0.226 0.133 0.082

2.0 1.980 2.112 2.640 4.526 34.457 28.268 19.775 14.452 8.568 3.531 2.094 1.508 0.814 0.452 0.265 0.164

3.0 2.970 3.168 3.960 6.789 51.686 42.402 29.663 21.678 12.853 5.297 3.140 2.262 1.220 0.678 0.398 0.246

4.0 3.960 4.224 5.280 9.051 68.915 56.536 39.550 28.904 17.137 7.062 4.187 3.016 1.627 0.904 0.530 0.327

5.0 4.950 5.280 6.600 11.314 86.144 70.670 49.438 36.131 21.421 8.828 5.234 3.770 2.034 1.130 0.663 0.409

6.0 5.940 6.336 7.920 13.577 103.372 84.804 59.325 43.357 25.705 10.594 6.281 4.524 2.441 1.356 0.796 0.491

7.0 6.930 7.392 9.240 15.840 120.601 98.938 69.213 50.583 29.989 12.359 7.328 5.277 2.848 1.582 0.928 0.573

8.0 7.920 8.448 10.560 18.103 137.830 113.072 79.100 57.809 34.274 14.125 8.374 6.031 3.254 1.808 1.061 0.655

9.0 8.910 9.504 11.880 20.366 155.059 127.206 88.988 65.035 38.558 15.890 9.421 6.785 3.661 2.034 1.193 0.737

10.0 9.900 10.560 13.200 22.629 172.287 141.340 98.875 72.261 42.842 17.656 10.468 7.539 4.068 2.260 1.326 0.818

11.0 10.890 11.616 14.520 24.891 189.516 155.474 108.763 79.487 47.126 19.422 11.515 8.293 4.475 2.486 1.458 0.900

12.0 11.880 12.672 15.840 27.154 206.745 169.608 118.650 86.713 51.410 21.187 12.562 9.047 4.881 2.712 1.591 0.982

13.0 12.870 13.728 17.160 29.417 223.974 183.742 128.538 93.939 55.694 22.953 13.608 9.801 5.288 2.938 1.724 1.064

14.0 13.860 14.784 18.480 31.680 241.202 197.876 138.425 101.165 59.979 24.719 14.655 10.555 5.695 3.164 1.856 1.146

15.0 14.850 15.840 19.800 33.943 258.431 212.010 148.313 108.392 64.263 26.484 15.702 11.309 6.102 3.390 1.989 1.228

16.0 15.840 16.896 21.120 36.206 275.660 226.144 158.200 115.618 68.547 28.250 16.749 12.063 6.509 3.616 2.121 1.310

17.0 16.830 17.952 22.440 38.469 292.889 240.278 168.088 122.844 72.831 30.015 17.796 12.817 6.915 3.842 2.254 1.391

18.0 17.820 19.008 23.760 40.731 310.117 254.412 177.975 130.070 77.115 31.781 18.842 13.571 7.322 4.068 2.387 1.473

19.0 18.810 20.064 25.080 42.994 327.346 268.546 187.863 137.296 81.400 33.547 19.889 14.324 7.729 4.294 2.519 1.555

20.0 19.800 21.120 26.400 45.257 344.575 282.680 197.750 144.522 85.684 35.312 20.936 15.078 8.136 4.520 2.652 1.637

21.0 20.790 22.176 27.720 47.520 361.803 296.814 207.638 151.748 89.968 37.078 21.983 15.832 8.543 4.746 2.784 1.719

22.0 21.780 23.232 29.040 49.783 379.032 310.948 217.525 158.974 94.252 38.843 23.030 16.586 8.949 4.972 2.917 1.801

23.0 22.770 24.288 30.360 52.046 396.261 325.082 227.413 166.200 98.536 40.609 24.076 17.340 9.356 5.198 3.050 1.883

24.0 23.760 25.344 31.680 54.309 413.490 339.216 237.300 173.426 102.821 42.375 25.123 18.094 9.763 5.424 3.182 1.964

25.0 24.750 26.400 33.000 56.571 430.718 353.350 247.188 180.653 107.105 44.140 26.170 18.848 10.170 5.650 3.315 2.046

26.0 25.740 27.456 34.320 58.834 447.947 367.484 257.075 187.879 111.389 45.906 27.217 19.602 10.576 5.876 3.447 2.128

27.0 26.730 28.512 35.640 61.097 465.176 381.618 266.963 195.105 115.673 47.671 28.264 20.356 10.983 6.102 3.580 2.210

28.0 27.720 29.568 36.960 63.360 482.405 395.752 276.850 202.331 119.957 49.437 29.310 21.110 11.390 6.328 3.713 2.292

29.0 28.710 30.624 38.280 65.623 499.633 409.886 286.738 209.557 124.242 51.203 30.357 21.864 11.797 6.554 3.845 2.374

30.0 29.700 31.680 39.600 67.886 516.862 424.020 296.625 216.783 128.526 52.968 31.404 22.618 12.204 6.780 3.978 2.455

Ingeteam Technology S.A.


User Manual 511
CURVES FOR TIMED CHARACTERISTICS 

Ingeteam Technology S.A.


User Manual 512
CURVES FOR TIMED CHARACTERISTICS 

Very inverse curve

T = M   A + 
B D E tr
+ + TRECAIDA = M 
  − C
I 2 3
 I   I − C  I − C  2
 I  −1
 0  I  I  I 
  0   0    0
@Fig.176.png-H:54,7-W:250@ @Fig.177.png-H:61,65-W:143,4@

A = 0.0615, B = 0.7989, C = 0.3400, D = -0.2840, E = 4.0505 tr = 4.678

Theoretical values given by the formula:

M \ I/Io 0 0.25 0.5 0.75 1.05 1.10 1.20 1.30 1.50 2.00 2.50 3.00 5.00 10.00 20.00 40.00
0.5 2.339 2.495 3.119 5.346 5.970 4.924 3.487 2.582 1.567 0.663 0.386 0.268 0.130 0.073 0.051 0.041

1.0 4.678 4.990 6.237 10.693 11.940 9.848 6.975 5.164 3.134 1.325 0.772 0.537 0.260 0.146 0.102 0.082

2.0 9.356 9.980 12.475 21.385 23.881 19.696 13.949 10.327 6.268 2.650 1.545 1.074 0.520 0.291 0.204 0.163

3.0 14.034 14.970 18.712 32.078 35.821 29.544 20.924 15.491 9.402 3.976 2.317 1.611 0.780 0.437 0.306 0.245

4.0 18.712 19.959 24.949 42.770 47.762 39.393 27.898 20.655 12.537 5.301 3.090 2.148 1.040 0.583 0.408 0.326

5.0 23.390 24.949 31.187 53.463 59.702 49.241 34.873 25.819 15.671 6.626 3.862 2.685 1.299 0.728 0.510 0.408

6.0 28.068 29.939 37.424 64.155 71.642 59.089 41.848 30.982 18.805 7.951 4.635 3.221 1.559 0.874 0.612 0.489

7.0 32.746 34.929 43.661 74.848 83.583 68.937 48.822 36.146 21.939 9.276 5.407 3.758 1.819 1.020 0.714 0.571

8.0 37.424 39.919 49.899 85.541 95.523 78.785 55.797 41.310 25.073 10.602 6.179 4.295 2.079 1.165 0.815 0.652

9.0 42.102 44.909 56.136 96.233 107.464 88.633 62.771 46.474 28.207 11.927 6.952 4.832 2.339 1.311 0.917 0.734

10.0 46.780 49.899 62.373 106.926 119.404 98.481 69.746 51.637 31.341 13.252 7.724 5.369 2.599 1.457 1.019 0.815

11.0 51.458 54.889 68.611 117.618 131.344 108.330 76.721 56.801 34.475 14.577 8.497 5.906 2.859 1.602 1.121 0.897

12.0 56.136 59.878 74.848 128.311 143.285 118.178 83.695 61.965 37.610 15.902 9.269 6.443 3.119 1.748 1.223 0.978

13.0 60.814 64.868 81.085 139.003 155.225 128.026 90.670 67.128 40.744 17.228 10.041 6.980 3.379 1.893 1.325 1.060

14.0 65.492 69.858 87.323 149.696 167.165 137.874 97.645 72.292 43.878 18.553 10.814 7.517 3.638 2.039 1.427 1.141

15.0 70.170 74.848 93.560 160.389 179.106 147.722 104.619 77.456 47.012 19.878 11.586 8.054 3.898 2.185 1.529 1.223

16.0 74.848 79.838 99.797 171.081 191.046 157.570 111.594 82.620 50.146 21.203 12.359 8.591 4.158 2.330 1.631 1.304

17.0 79.526 84.828 106.035 181.774 202.987 167.419 118.568 87.783 53.280 22.528 13.131 9.127 4.418 2.476 1.733 1.386

18.0 84.204 89.818 112.272 192.466 214.927 177.267 125.543 92.947 56.414 23.853 13.904 9.664 4.678 2.622 1.835 1.468

19.0 88.882 94.807 118.509 203.159 226.867 187.115 132.518 98.111 59.549 25.179 14.676 10.201 4.938 2.767 1.937 1.549

20.0 93.560 99.797 124.747 213.851 238.808 196.963 139.492 103.275 62.683 26.504 15.448 10.738 5.198 2.913 2.039 1.631

21.0 98.238 104.787 130.984 224.544 250.748 206.811 146.467 108.438 65.817 27.829 16.221 11.275 5.458 3.059 2.141 1.712

22.0 102.916 109.777 137.221 235.237 262.689 216.659 153.441 113.602 68.951 29.154 16.993 11.812 5.718 3.204 2.243 1.794

23.0 107.594 114.767 143.459 245.929 274.629 226.507 160.416 118.766 72.085 30.479 17.766 12.349 5.977 3.350 2.344 1.875

24.0 112.272 119.757 149.696 256.622 286.569 236.356 167.391 123.930 75.219 31.805 18.538 12.886 6.237 3.496 2.446 1.957

25.0 116.950 124.747 155.933 267.314 298.510 246.204 174.365 129.093 78.353 33.130 19.310 13.423 6.497 3.641 2.548 2.038

26.0 121.628 129.737 162.171 278.007 310.450 256.052 181.340 134.257 81.487 34.455 20.083 13.960 6.757 3.787 2.650 2.120

27.0 126.306 134.726 168.408 288.699 322.391 265.900 188.314 139.421 84.622 35.780 20.855 14.497 7.017 3.933 2.752 2.201

28.0 130.984 139.716 174.645 299.392 334.331 275.748 195.289 144.584 87.756 37.105 21.628 15.034 7.277 4.078 2.854 2.283

29.0 135.662 144.706 180.883 310.085 346.271 285.596 202.264 149.748 90.890 38.431 22.400 15.570 7.537 4.224 2.956 2.364

30.0 140.340 149.696 187.120 320.777 358.212 295.444 209.238 154.912 94.024 39.756 23.173 16.107 7.797 4.370 3.058 2.446

Ingeteam Technology S.A.


User Manual 513
CURVES FOR TIMED CHARACTERISTICS 

Ingeteam Technology S.A.


User Manual 514
CURVES FOR TIMED CHARACTERISTICS 

Extremely inverse curve

T = M   A + 
B D E tr
+ + TRECAIDA = M 
  − C
I 2 3
 I   I − C  I − C   I  −1
2

 0  I  I  I 
  0   0    0

A = 0.0399, B = 0.2294, C = 0.5000, D = 3.0094, E = 0.7222 tr = 6.008

Theoretical values given by the formula:

M \ I/Io 0 0.25 0.5 0.75 1.05 1.10 1.20 1.30 1.50 2.00 2.50 3.00 5.00 10.00 20.00 40.00
0.5 3.004 3.204 4.005 6.866 7.373 6.063 4.307 3.220 2.000 0.872 0.499 0.330 0.124 0.049 0.030 0.024

1.0 6.008 6.409 8.011 13.733 14.746 12.125 8.615 6.439 4.001 1.744 0.997 0.659 0.247 0.098 0.060 0.048

2.0 12.016 12.817 16.021 27.465 29.492 24.250 17.230 12.879 8.002 3.489 1.994 1.319 0.495 0.196 0.119 0.095

3.0 18.024 19.226 24.032 41.198 44.239 36.376 25.844 19.318 12.003 5.233 2.992 1.978 0.742 0.295 0.179 0.143

4.0 24.032 25.634 32.043 54.930 58.985 48.501 34.459 25.758 16.004 6.977 3.989 2.638 0.990 0.393 0.239 0.191

5.0 30.040 32.043 40.053 68.663 73.731 60.626 43.074 32.197 20.004 8.722 4.986 3.297 1.237 0.491 0.298 0.238

6.0 36.048 38.451 48.064 82.395 88.477 72.751 51.689 38.636 24.005 10.466 5.983 3.956 1.484 0.589 0.358 0.286

7.0 42.056 44.860 56.075 96.128 103.224 84.876 60.303 45.076 28.006 12.210 6.981 4.616 1.732 0.688 0.418 0.334

8.0 48.064 51.268 64.085 109.861 117.970 97.002 68.918 51.515 32.007 13.955 7.978 5.275 1.979 0.786 0.477 0.381

9.0 54.072 57.677 72.096 123.593 132.716 109.127 77.533 57.954 36.008 15.699 8.975 5.934 2.227 0.884 0.537 0.429

10.0 60.080 64.085 80.107 137.326 147.462 121.252 86.148 64.394 40.009 17.443 9.972 6.594 2.474 0.982 0.597 0.476

11.0 66.088 70.494 88.117 151.058 162.208 133.377 94.763 70.833 44.010 19.188 10.969 7.253 2.722 1.081 0.656 0.524

12.0 72.096 76.902 96.128 164.791 176.955 145.502 103.377 77.273 48.011 20.932 11.967 7.913 2.969 1.179 0.716 0.572

13.0 78.104 83.311 104.139 178.523 191.701 157.628 111.992 83.712 52.012 22.676 12.964 8.572 3.216 1.277 0.776 0.619

14.0 84.112 89.719 112.149 192.256 206.447 169.753 120.607 90.151 56.013 24.421 13.961 9.231 3.464 1.375 0.835 0.667

15.0 90.120 96.128 120.160 205.989 221.193 181.878 129.222 96.591 60.013 26.165 14.958 9.891 3.711 1.474 0.895 0.715

16.0 96.128 102.537 128.171 219.721 235.940 194.003 137.837 103.030 64.014 27.909 15.956 10.550 3.959 1.572 0.955 0.762

17.0 102.136 108.945 136.181 233.454 250.686 206.128 146.451 109.470 68.015 29.654 16.953 11.210 4.206 1.670 1.014 0.810

18.0 108.144 115.354 144.192 247.186 265.432 218.254 155.066 115.909 72.016 31.398 17.950 11.869 4.453 1.768 1.074 0.858

19.0 114.152 121.762 152.203 260.919 280.178 230.379 163.681 122.348 76.017 33.142 18.947 12.528 4.701 1.866 1.134 0.905

20.0 120.160 128.171 160.213 274.651 294.924 242.504 172.296 128.788 80.018 34.887 19.944 13.188 4.948 1.965 1.194 0.953

21.0 126.168 134.579 168.224 288.384 309.671 254.629 180.910 135.227 84.019 36.631 20.942 13.847 5.196 2.063 1.253 1.001

22.0 132.176 140.988 176.235 302.117 324.417 266.754 189.525 141.666 88.020 38.375 21.939 14.506 5.443 2.161 1.313 1.048

23.0 138.184 147.396 184.245 315.849 339.163 278.879 198.140 148.106 92.021 40.120 22.936 15.166 5.691 2.259 1.373 1.096

24.0 144.192 153.805 192.256 329.582 353.909 291.005 206.755 154.545 96.022 41.864 23.933 15.825 5.938 2.358 1.432 1.144

25.0 150.200 160.213 200.267 343.314 368.655 303.130 215.370 160.985 100.022 43.608 24.931 16.485 6.185 2.456 1.492 1.191

26.0 156.208 166.622 208.277 357.047 383.402 315.255 223.984 167.424 104.023 45.353 25.928 17.144 6.433 2.554 1.552 1.239

27.0 162.216 173.030 216.288 370.779 398.148 327.380 232.599 173.863 108.024 47.097 26.925 17.803 6.680 2.652 1.611 1.286

28.0 168.224 179.439 224.299 384.512 412.894 339.505 241.214 180.303 112.025 48.841 27.922 18.463 6.928 2.751 1.671 1.334

29.0 174.232 185.847 232.309 398.245 427.640 351.631 249.829 186.742 116.026 50.586 28.920 19.122 7.175 2.849 1.731 1.382

30.0 180.240 192.256 240.320 411.977 442.387 363.756 258.444 193.182 120.027 52.330 29.917 19.782 7.422 2.947 1.790 1.429

Ingeteam Technology S.A.


User Manual 515
CURVES FOR TIMED CHARACTERISTICS 

Ingeteam Technology S.A.


User Manual 516
CURVES FOR TIMED CHARACTERISTICS 

Moderate inverse curve

T = M   A + 
B D E tr
+ + TRECAIDA = M 
  − C
I 2  3
 I   I − C  I − C  2
 I  −1
 0  I  I  I 
  0   0  
 0
A = 0.1735, B = 0.6791, C = 0.8000, D = -0.0800, E = 0.1271 tr = 1.2

Theoretical values given by the formula:

M \ I/Io 0 0.25 0.5 0.75 1.05 1.10 1.20 1.30 1.50 2.00 2.50 3.00 5.00 10.00 20.00 40.00
0.5 0.600 0.640 0.800 1.371 4.872 3.128 1.679 1.114 0.675 0.379 0.286 0.239 0.166 0.123 0.104 0.095

1.0 1.200 1.280 1.600 2.743 9.744 6.256 3.357 2.229 1.351 0.757 0.571 0.478 0.332 0.247 0.209 0.191

2.0 2.400 2.560 3.200 5.486 19.489 12.511 6.714 4.457 2.702 1.515 1.142 0.955 0.665 0.493 0.417 0.382

3.0 3.600 3.840 4.800 8.229 29.233 18.767 10.072 6.686 4.053 2.272 1.713 1.433 0.997 0.740 0.626 0.572

4.0 4.800 5.120 6.400 10.971 38.977 25.023 13.429 8.914 5.404 3.030 2.285 1.910 1.329 0.986 0.835 0.763

5.0 6.000 6.400 8.000 13.714 48.722 31.278 16.786 11.143 6.755 3.787 2.856 2.388 1.662 1.233 1.043 0.954

6.0 7.200 7.680 9.600 16.457 58.466 37.534 20.143 13.371 8.106 4.544 3.427 2.866 1.994 1.479 1.252 1.145

7.0 8.400 8.960 11.200 19.200 68.210 43.790 23.500 15.600 9.457 5.302 3.998 3.343 2.327 1.726 1.461 1.335

8.0 9.600 10.240 12.800 21.943 77.954 50.045 26.857 17.828 10.807 6.059 4.569 3.821 2.659 1.972 1.669 1.526

9.0 10.800 11.520 14.400 24.686 87.699 56.301 30.215 20.057 12.158 6.817 5.140 4.298 2.991 2.219 1.878 1.717

10.0 12.000 12.800 16.000 27.429 97.443 62.557 33.572 22.285 13.509 7.574 5.712 4.776 3.324 2.465 2.087 1.908

11.0 13.200 14.080 17.600 30.171 107.187 68.813 36.929 24.514 14.860 8.332 6.283 5.253 3.656 2.712 2.295 2.099

12.0 14.400 15.360 19.200 32.914 116.932 75.068 40.286 26.742 16.211 9.089 6.854 5.731 3.988 2.958 2.504 2.289

13.0 15.600 16.640 20.800 35.657 126.676 81.324 43.643 28.971 17.562 9.846 7.425 6.209 4.321 3.205 2.713 2.480

14.0 16.800 17.920 22.400 38.400 136.420 87.580 47.001 31.199 18.913 10.604 7.996 6.686 4.653 3.451 2.921 2.671

15.0 18.000 19.200 24.000 41.143 146.165 93.835 50.358 33.428 20.264 11.361 8.567 7.164 4.986 3.698 3.130 2.862

16.0 19.200 20.480 25.600 43.886 155.909 100.091 53.715 35.656 21.615 12.119 9.139 7.641 5.318 3.945 3.339 3.052

17.0 20.400 21.760 27.200 46.629 165.653 106.347 57.072 37.885 22.966 12.876 9.710 8.119 5.650 4.191 3.547 3.243

18.0 21.600 23.040 28.800 49.371 175.398 112.602 60.429 40.113 24.317 13.633 10.281 8.597 5.983 4.438 3.756 3.434

19.0 22.800 24.320 30.400 52.114 185.142 118.858 63.787 42.342 25.668 14.391 10.852 9.074 6.315 4.684 3.965 3.625

20.0 24.000 25.600 32.000 54.857 194.886 125.114 67.144 44.570 27.019 15.148 11.423 9.552 6.647 4.931 4.173 3.815

21.0 25.200 26.880 33.600 57.600 204.630 131.369 70.501 46.799 28.370 15.906 11.994 10.029 6.980 5.177 4.382 4.006

22.0 26.400 28.160 35.200 60.343 214.375 137.625 73.858 49.027 29.720 16.663 12.565 10.507 7.312 5.424 4.591 4.197

23.0 27.600 29.440 36.800 63.086 224.119 143.881 77.215 51.256 31.071 17.421 13.137 10.985 7.645 5.670 4.799 4.388

24.0 28.800 30.720 38.400 65.829 233.863 150.136 80.572 53.484 32.422 18.178 13.708 11.462 7.977 5.917 5.008 4.579

25.0 30.000 32.000 40.000 68.571 243.608 156.392 83.930 55.713 33.773 18.935 14.279 11.940 8.309 6.163 5.217 4.769

26.0 31.200 33.280 41.600 71.314 253.352 162.648 87.287 57.941 35.124 19.693 14.850 12.417 8.642 6.410 5.425 4.960

27.0 32.400 34.560 43.200 74.057 263.096 168.903 90.644 60.170 36.475 20.450 15.421 12.895 8.974 6.656 5.634 5.151

28.0 33.600 35.840 44.800 76.800 272.841 175.159 94.001 62.398 37.826 21.208 15.992 13.373 9.306 6.903 5.843 5.342

29.0 34.800 37.120 46.400 79.543 282.585 181.415 97.358 64.627 39.177 21.965 16.564 13.850 9.639 7.149 6.051 5.532

30.0 36.000 38.400 48.000 82.286 292.329 187.671 100.716 66.855 40.528 22.722 17.135 14.328 9.971 7.396 6.260 5.723

Ingeteam Technology S.A.


User Manual 517
CURVES FOR TIMED CHARACTERISTICS 

Ingeteam Technology S.A.


User Manual 518
CURVES FOR TIMED CHARACTERISTICS 

30.2.1 Battery voltage curves


Only available in CB models

Ingeteam Technology S.A.


User Manual 519
CURVES FOR TIMED CHARACTERISTICS 

30.3 IEC 60255-151 CURVES36

Enclosed below are the groups of curves, according to IEC 60255-151, which correspond to the following types:

❑ IEEE Moderate Inverse


❑ IEEE Very Inverse
❑ IEEE Extremely Inverse
These curves comply with the general formula

𝑘 𝑡𝑟
𝑇 = 𝑀[ 𝐼 𝛼
+ 𝑐] 𝑇𝐷𝑅𝑂𝑃 = 𝑀 [ 𝐼 2
]
( ) −1 1−( )
𝐼0 𝐼0

in which:

❑ T : trip time (sec)


❑ TDROP : drop time (sec)
❑ M : multiplier (“time dial”). Valid range 0.025 to 15.0, in steps of 0.005
❑ I: Measured current
❑ Io: Pickup current setting
❑ K, , tr, c: constants which depend on the type of curve:

Constants IEEE Moderte Inverse IEEE Very Inverse IEEE Extremely Inverse
K 0.0515 19.61 28.2
 0.02 2 2
c 0.114 0.491 0.1217
tr 4.85 21.6 29.1

The following represent the curves which correspond to indexes 0.05, 0.1, 0.2, 0.3, 0.4, 0.5, 0.6, 0.7, 0.8, 0.9 and 1.0 for
each type of characteristic. Bear in mind that there are another 9 curves between each of the two curves illustrated, except
between 0.05 and 0.1, between which there are another 4.

36
Avaliable from firmware version 6.0.8.2 and ICD version 8.2.0.0.

Ingeteam Technology S.A.


User Manual 520
CURVES FOR TIMED CHARACTERISTICS 

IEEE Moderate Inverse curve

𝑘 𝑡𝑟
𝑇 = 𝑀[ 𝐼 𝛼
+ 𝑐] 𝑇𝑅𝐸𝐶𝐴𝐼𝐷𝐴 = 𝑀 [ 𝐼 2
]
( ) −1 1−( )
𝐼0 𝐼0

K = 0,0515,  = 0,02, c = 0,114, tr = 4,85

Theoretical values given by the formula:

M\I/Io 0 0.25 0.5 0.75 1.05 1.10 1.20 1.30 1.50 2.00 2.50 3.00 5.00 10.00 20.00 40.00
0.05 0.243 0.259 0.323 0.554 2.643 1.355 0.711 0.495 0.322 0.190 0.145 0.122 0.084 0.060 0.047 0.039

0.06 0.291 0.310 0.388 0.665 3.172 1.626 0.853 0.594 0.386 0.228 0.174 0.146 0.101 0.072 0.057 0.047

0.340 0.362 0.453 0.776 3.701 1.897 0.995 0.693 0.451 0.266 0.203 0.170 0.118 0.084 0.066 0.055
0.07
0.08 0.388 0.414 0.517 0.887 4.229 2.168 1.137 0.792 0.515 0.304 0.232 0.195 0.135 0.097 0.076 0.063

0.09 0.437 0.466 0.582 0.998 4.758 2.439 1.279 0.891 0.580 0.342 0.261 0.219 0.152 0.109 0.085 0.071

0.485 0.517 0.647 1.109 5.287 2.711 1.421 0.990 0.644 0.380 0.290 0.243 0.169 0.121 0.095 0.079
0.10
0.11 0.534 0.569 0.711 1.219 5.815 2.982 1.563 1.089 0.708 0.418 0.319 0.268 0.186 0.133 0.104 0.087

0.12 0.582 0.621 0.776 1.330 6.344 3.253 1.705 1.188 0.773 0.456 0.348 0.292 0.203 0.145 0.114 0.094

0.631 0.673 0.841 1.441 6.872 3.524 1.848 1.287 0.837 0.494 0.377 0.316 0.219 0.157 0.123 0.102
0.13
0.14 0.679 0.724 0.905 1.552 7.401 3.795 1.990 1.386 0.901 0.532 0.406 0.341 0.236 0.169 0.133 0.110

0.15 0.728 0.776 0.970 1.663 7.930 4.066 2.132 1.485 0.966 0.570 0.435 0.365 0.253 0.181 0.142 0.118

0.776 0.828 1.035 1.774 8.458 4.337 2.274 1.584 1.030 0.609 0.464 0.389 0.270 0.193 0.152 0.126
0.16
0.17 0.825 0.879 1.099 1.885 8.987 4.608 2.416 1.683 1.095 0.647 0.493 0.413 0.287 0.205 0.161 0.134

0.18 0.873 0.931 1.164 1.995 9.516 4.879 2.558 1.783 1.159 0.685 0.522 0.438 0.304 0.217 0.171 0.142

0.922 0.983 1.229 2.106 10.044 5.150 2.700 1.882 1.223 0.723 0.551 0.462 0.321 0.229 0.180 0.149
0.19
0.20 0.970 1.035 1.293 2.217 10.573 5.421 2.842 1.981 1.288 0.761 0.580 0.486 0.338 0.241 0.190 0.157

0.25 1.213 1.293 1.617 2.771 13.216 6.776 3.553 2.476 1.610 0.951 0.725 0.608 0.422 0.302 0.237 0.197

1.455 1.552 1.940 3.326 15.860 8.132 4.263 2.971 1.932 1.141 0.870 0.730 0.506 0.362 0.284 0.236
0.30
0.35 1.698 1.811 2.263 3.880 18.503 9.487 4.974 3.466 2.254 1.331 1.015 0.851 0.591 0.422 0.332 0.275

0.40 1.940 2.069 2.587 4.434 21.146 10.842 5.685 3.961 2.576 1.521 1.159 0.973 0.675 0.483 0.379 0.315

2.183 2.328 2.910 4.989 23.789 12.197 6.395 4.456 2.898 1.711 1.304 1.094 0.760 0.543 0.427 0.354
0.45
0.50 2.425 2.587 3.233 5.543 26.433 13.553 7.106 4.951 3.220 1.902 1.449 1.216 0.844 0.603 0.474 0.393

0.55 2.668 2.845 3.557 6.097 29.076 14.908 7.816 5.447 3.541 2.092 1.594 1.338 0.929 0.664 0.521 0.433

2.910 3.104 3.880 6.651 31.719 16.263 8.527 5.942 3.863 2.282 1.739 1.459 1.013 0.724 0.569 0.472
0.60
0.65 3.153 3.363 4.203 7.206 34.362 17.618 9.238 6.437 4.185 2.472 1.884 1.581 1.097 0.784 0.616 0.511

0.70 3.395 3.621 4.527 7.760 37.006 18.974 9.948 6.932 4.507 2.662 2.029 1.703 1.182 0.845 0.664 0.551

3.638 3.880 4.850 8.314 39.649 20.329 10.659 7.427 4.829 2.852 2.174 1.824 1.266 0.905 0.711 0.590
0.75
0.80 3.880 4.139 5.173 8.869 42.292 21.684 11.369 7.922 5.151 3.043 2.319 1.946 1.351 0.965 0.758 0.629

0.85 4.123 4.397 5.497 9.423 44.935 23.040 12.080 8.417 5.473 3.233 2.464 2.067 1.435 1.026 0.806 0.669

4.365 4.656 5.820 9.977 47.579 24.395 12.790 8.913 5.795 3.423 2.609 2.189 1.519 1.086 0.853 0.708
0.90
0.95 4.608 4.915 6.143 10.531 50.222 25.750 13.501 9.408 6.117 3.613 2.754 2.311 1.604 1.146 0.901 0.747

1.00 4.850 5.173 6.467 11.086 52.865 27.105 14.212 9.903 6.439 3.803 2.899 2.432 1.688 1.207 0.948 0.787

1.05 5.093 5.432 6.790 11.640 55.509 28.461 14.922 10.398 6.761 3.993 3.044 2.554 1.773 1.267 0.995 0.826

1.5 7.275 7.760 9.700 16.629 79.298 40.658 21.317 14.854 9.659 5.705 4.348 3.648 2.532 1.810 1.422 1.180

2.5 12.125 12.933 16.167 27.714 132.163 67.763 35.529 24.757 16.098 9.508 7.246 6.081 4.221 3.017 2.370 1.967

4.0 19.400 20.693 25.867 44.343 211.461 108.421 56.847 39.611 25.756 15.213 11.594 9.729 6.753 4.827 3.792 3.146

6.0 29.100 31.040 38.800 66.514 317.192 162.632 85.270 59.417 38.634 22.819 17.391 14.593 10.130 7.241 5.688 4.720

10.0 48.500 51.733 64.667 110.857 528.653 271.053 142.117 99.029 64.390 38.032 28.986 24.322 16.883 12.068 9.481 7.866

15.0 72.750 77.600 97.000 166.286 792.979 406.580 213.175 148.543 96.585 57.049 43.479 36.483 25.325 18.101 14.221 11.799

Ingeteam Technology S.A.


User Manual 521
CURVES FOR TIMED CHARACTERISTICS 

Ingeteam Technology S.A.


User Manual 522
CURVES FOR TIMED CHARACTERISTICS 

IEEE Very Inverse curve

𝑘 𝑡𝑟
𝑇 = 𝑀[ 𝐼 𝛼
+ 𝑐] 𝑇𝑅𝐸𝐶𝐴𝐼𝐷𝐴 = 𝑀 [ 𝐼 2
]
( ) −1 1−( )
𝐼0 𝐼0

K = 19,61,  = 2, c = 0,491, tr = 21,6

Theoretical values given by the formula:

M\I/Io 0 0.25 0.5 0.75 1.05 1.10 1.20 1.30 1.50 2.00 2.50 3.00 5.00 10.00 20.00 40.00
0.05 1.080 1.152 1.440 2.469 9.590 4.694 2.253 1.446 0.809 0.351 0.211 0.147 0.065 0.034 0.027 0.025

0.06 1.296 1.382 1.728 2.962 11.508 5.632 2.704 1.735 0.971 0.422 0.254 0.177 0.078 0.041 0.032 0.030

1.512 1.613 2.016 3.456 13.427 6.571 3.154 2.024 1.133 0.492 0.296 0.206 0.092 0.048 0.038 0.035
0.07
0.08 1.728 1.843 2.304 3.950 15.345 7.510 3.605 2.313 1.294 0.562 0.338 0.235 0.105 0.055 0.043 0.040

0.09 1.944 2.074 2.592 4.443 17.263 8.448 4.055 2.602 1.456 0.632 0.380 0.265 0.118 0.062 0.049 0.045

2.160 2.304 2.880 4.937 19.181 9.387 4.506 2.891 1.618 0.703 0.423 0.294 0.131 0.069 0.054 0.050
0.10
0.11 2.376 2.534 3.168 5.431 21.099 10.326 4.957 3.180 1.780 0.773 0.465 0.324 0.144 0.076 0.059 0.055

0.12 2.592 2.765 3.456 5.925 23.017 11.265 5.407 3.469 1.941 0.843 0.507 0.353 0.157 0.083 0.065 0.060

2.808 2.995 3.744 6.418 24.935 12.203 5.858 3.758 2.103 0.914 0.549 0.382 0.170 0.090 0.070 0.065
0.13
0.14 3.024 3.226 4.032 6.912 26.853 13.142 6.308 4.048 2.265 0.984 0.592 0.412 0.183 0.096 0.076 0.070

0.15 3.240 3.456 4.320 7.406 28.771 14.081 6.759 4.337 2.427 1.054 0.634 0.441 0.196 0.103 0.081 0.075

3.456 3.686 4.608 7.899 30.689 15.020 7.209 4.626 2.589 1.124 0.676 0.471 0.209 0.110 0.086 0.081
0.16
0.17 3.672 3.917 4.896 8.393 32.607 15.958 7.660 4.915 2.750 1.195 0.718 0.500 0.222 0.117 0.092 0.086

0.18 3.888 4.147 5.184 8.887 34.525 16.897 8.111 5.204 2.912 1.265 0.761 0.530 0.235 0.124 0.097 0.091

4.104 4.378 5.472 9.381 36.444 17.836 8.561 5.493 3.074 1.335 0.803 0.559 0.249 0.131 0.103 0.096
0.19
0.20 4.320 4.608 5.760 9.874 38.362 18.774 9.012 5.782 3.236 1.406 0.845 0.588 0.262 0.138 0.108 0.101

0.25 5.400 5.760 7.200 12.343 47.952 23.468 11.265 7.228 4.045 1.757 1.057 0.736 0.327 0.172 0.135 0.126

6.480 6.912 8.640 14.811 57.542 28.162 13.518 8.673 4.854 2.108 1.268 0.883 0.392 0.207 0.162 0.151
0.30
0.35 7.560 8.064 10.080 17.280 67.133 32.855 15.771 10.119 5.663 2.460 1.479 1.030 0.458 0.241 0.189 0.176

0.40 8.640 9.216 11.520 19.749 76.723 37.549 18.024 11.565 6.472 2.811 1.690 1.177 0.523 0.276 0.216 0.201

9.720 10.368 12.960 22.217 86.314 42.242 20.277 13.010 7.281 3.162 1.902 1.324 0.589 0.310 0.243 0.226
0.45
0.50 10.800 11.520 14.400 24.686 95.904 46.936 22.530 14.456 8.090 3.514 2.113 1.471 0.654 0.345 0.270 0.252

0.55 11.880 12.672 15.840 27.154 105.494 51.630 24.783 15.901 8.898 3.865 2.324 1.618 0.719 0.379 0.297 0.277

12.960 13.824 17.280 29.623 115.085 56.323 27.036 17.347 9.707 4.217 2.536 1.765 0.785 0.413 0.324 0.302
0.60
0.65 14.040 14.976 18.720 32.091 124.675 61.017 29.288 18.792 10.516 4.568 2.747 1.912 0.850 0.448 0.351 0.327

0.70 15.120 16.128 20.160 34.560 134.266 65.710 31.541 20.238 11.325 4.919 2.958 2.060 0.916 0.482 0.378 0.352

16.200 17.280 21.600 37.029 143.856 70.404 33.794 21.683 12.134 5.271 3.170 2.207 0.981 0.517 0.405 0.377
0.75
0.80 17.280 18.432 23.040 39.497 153.446 75.098 36.047 23.129 12.943 5.622 3.381 2.354 1.046 0.551 0.432 0.403

0.85 18.360 19.584 24.480 41.966 163.037 79.791 38.300 24.575 13.752 5.974 3.592 2.501 1.112 0.586 0.459 0.428

19.440 20.736 25.920 44.434 172.627 84.485 40.553 26.020 14.561 6.325 3.804 2.648 1.177 0.620 0.486 0.453
0.90
0.95 20.520 21.888 27.360 46.903 182.218 89.178 42.806 27.466 15.370 6.676 4.015 2.795 1.243 0.655 0.513 0.478

1.00 21.600 23.040 28.800 49.371 191.808 93.872 45.059 28.911 16.179 7.028 4.226 2.942 1.308 0.689 0.540 0.503

1.05 22.680 24.192 30.240 51.840 201.398 98.566 47.312 30.357 16.988 7.379 4.438 3.089 1.373 0.724 0.567 0.528

1.5 32.400 34.560 43.200 74.057 287.712 140.808 67.589 43.367 24.269 10.542 6.339 4.413 1.962 1.034 0.810 0.755

2.5 54.000 57.600 72.000 123.429 479.520 234.680 112.648 72.278 40.448 17.569 10.566 7.356 3.270 1.723 1.350 1.258

4.0 86.400 92.160 115.200 197.486 767.232 375.488 180.237 115.645 64.716 28.111 16.905 11.769 5.232 2.756 2.161 2.013

6.0 129.600 138.240 172.800 296.229 1150.848 563.232 270.355 173.468 97.074 42.166 25.357 17.654 7.849 4.134 3.241 3.020

10.0 216.000 230.400 288.000 493.714 1918.081 938.720 450.592 289.113 161.790 70.277 42.262 29.423 13.081 6.891 5.401 5.033

15.0 324.000 345.600 432.000 740.571 2877.121 1408.079 675.888 433.669 242.685 105.415 63.394 44.134 19.621 10.336 8.102 7.549

Ingeteam Technology S.A.


User Manual 523
CURVES FOR TIMED CHARACTERISTICS 

Ingeteam Technology S.A.


User Manual 524
CURVES FOR TIMED CHARACTERISTICS 

IEEE Extremely Inverse curve

𝑘 𝑡𝑟
𝑇 = 𝑀[ 𝐼 𝛼
+ 𝑐] 𝑇𝑅𝐸𝐶𝐴𝐼𝐷𝐴 = 𝑀 [ 𝐼 2
]
( ) −1 1−( )
𝐼0 𝐼0

K = 28,2,  = 2, c = 0,1217, tr = 29,1

Theoretical values given by the formula:

M\I/Io 0 0.25 0.5 0.75 1.05 1.10 1.20 1.30 1.50 2.00 2.50 3.00 5.00 10.00 20.00 40.00
0.05 1.455 1.552 1.940 3.326 13.762 6.720 3.211 2.050 1.134 0.476 0.275 0.182 0.065 0.020 0.010 0.007

0.06 1.746 1.862 2.328 3.991 16.515 8.064 3.853 2.459 1.361 0.571 0.330 0.219 0.078 0.024 0.012 0.008

2.037 2.173 2.716 4.656 19.267 9.409 4.495 2.869 1.588 0.667 0.385 0.255 0.091 0.028 0.013 0.010
0.07
0.08 2.328 2.483 3.104 5.321 22.019 10.753 5.137 3.279 1.815 0.762 0.439 0.292 0.104 0.033 0.015 0.011

0.09 2.619 2.794 3.492 5.986 24.772 12.097 5.779 3.689 2.041 0.857 0.494 0.328 0.117 0.037 0.017 0.013

2.910 3.104 3.880 6.651 27.524 13.441 6.421 4.099 2.268 0.952 0.549 0.365 0.130 0.041 0.019 0.014
0.10
0.11 3.201 3.414 4.268 7.317 30.277 14.785 7.063 4.509 2.495 1.047 0.604 0.401 0.143 0.045 0.021 0.015

0.12 3.492 3.725 4.656 7.982 33.029 16.129 7.706 4.919 2.722 1.143 0.659 0.438 0.156 0.049 0.023 0.017

3.783 4.035 5.044 8.647 35.782 17.473 8.348 5.329 2.949 1.238 0.714 0.474 0.169 0.053 0.025 0.018
0.13
0.14 4.074 4.346 5.432 9.312 38.534 18.817 8.990 5.739 3.175 1.333 0.769 0.511 0.182 0.057 0.027 0.020

0.15 4.365 4.656 5.820 9.977 41.287 20.161 9.632 6.149 3.402 1.428 0.824 0.547 0.195 0.061 0.029 0.021

4.656 4.966 6.208 10.642 44.039 21.505 10.274 6.559 3.629 1.523 0.879 0.583 0.207 0.065 0.031 0.022
0.16
0.17 4.947 5.277 6.596 11.307 46.791 22.849 10.916 6.969 3.856 1.619 0.934 0.620 0.220 0.069 0.033 0.024

0.18 5.238 5.587 6.984 11.973 49.544 24.193 11.558 7.378 4.083 1.714 0.989 0.656 0.233 0.073 0.035 0.025

5.529 5.898 7.372 12.638 52.296 25.537 12.200 7.788 4.310 1.809 1.044 0.693 0.246 0.077 0.037 0.026
0.19
0.20 5.820 6.208 7.760 13.303 55.049 26.881 12.843 8.198 4.536 1.904 1.099 0.729 0.259 0.081 0.038 0.028

0.25 7.275 7.760 9.700 16.629 68.811 33.602 16.053 10.248 5.670 2.380 1.373 0.912 0.324 0.102 0.048 0.035

8.730 9.312 11.640 19.954 82.573 40.322 19.264 12.297 6.805 2.857 1.648 1.094 0.389 0.122 0.058 0.042
0.30
0.35 10.185 10.864 13.580 23.280 96.335 47.043 22.474 14.347 7.939 3.333 1.923 1.276 0.454 0.142 0.067 0.049

0.40 11.640 12.416 15.520 26.606 110.097 53.763 25.685 16.397 9.073 3.809 2.197 1.459 0.519 0.163 0.077 0.056

13.095 13.968 17.460 29.931 123.860 60.483 28.896 18.446 10.207 4.285 2.472 1.641 0.584 0.183 0.087 0.063
0.45
0.50 14.550 15.520 19.400 33.257 137.622 67.204 32.106 20.496 11.341 4.761 2.747 1.823 0.648 0.203 0.096 0.070

0.55 16.005 17.072 21.340 36.583 151.384 73.924 35.317 22.545 12.475 5.237 3.021 2.006 0.713 0.224 0.106 0.077

17.460 18.624 23.280 39.909 165.146 80.644 38.528 24.595 13.609 5.713 3.296 2.188 0.778 0.244 0.115 0.084
0.60
0.65 18.915 20.176 25.220 43.234 178.908 87.365 41.738 26.644 14.743 6.189 3.571 2.370 0.843 0.264 0.125 0.091

0.70 20.370 21.728 27.160 46.560 192.671 94.085 44.949 28.694 15.877 6.665 3.845 2.553 0.908 0.285 0.135 0.098

21.825 23.280 29.100 49.886 206.433 100.806 48.159 30.743 17.011 7.141 4.120 2.735 0.973 0.305 0.144 0.105
0.75
0.80 23.280 24.832 31.040 53.211 220.195 107.526 51.370 32.793 18.145 7.617 4.395 2.917 1.037 0.325 0.154 0.111

0.85 24.735 26.384 32.980 56.537 233.957 114.246 54.581 34.843 19.279 8.093 4.669 3.100 1.102 0.346 0.164 0.118

26.190 27.936 34.920 59.863 247.719 120.967 57.791 36.892 20.414 8.570 4.944 3.282 1.167 0.366 0.173 0.125
0.90
0.95 27.645 29.488 36.860 63.189 261.481 127.687 61.002 38.942 21.548 9.046 5.218 3.464 1.232 0.386 0.183 0.132

1.00 29.100 31.040 38.800 66.514 275.244 134.407 64.213 40.991 22.682 9.522 5.493 3.647 1.297 0.407 0.192 0.139

30.555 32.592 40.740 69.840 289.006 141.128 67.423 43.041 23.816 9.998 5.768 3.829 1.362 0.427 0.202 0.146
1.05
1.5 43.650 46.560 58.200 99.771 412.865 201.611 96.319 61.487 34.023 14.283 8.240 5.470 1.945 0.610 0.289 0.209

2.5 72.750 77.600 97.000 166.286 688.109 336.019 160.532 102.478 56.704 23.804 13.733 9.117 3.242 1.016 0.481 0.348

4.0 116.400 124.160 155.200 266.057 1100.975 537.630 256.850 163.965 90.727 38.087 21.973 14.587 5.187 1.626 0.770 0.557

6.0 174.600 186.240 232.800 399.086 1651.462 806.444 385.276 245.948 136.090 57.130 32.959 21.880 7.780 2.439 1.154 0.836

10.0 291.000 310.400 388.000 665.143 2752.437 1344.074 642.126 409.913 226.817 95.217 54.931 36.467 12.967 4.065 1.924 1.393

15.0 436.500 465.600 582.000 997.714 4128.655 2016.111 963.189 614.869 340.226 142.826 82.397 54.701 19.451 6.098 2.886 2.090

Ingeteam Technology S.A.


User Manual 525
CURVES FOR TIMED CHARACTERISTICS 

Ingeteam Technology S.A.


User Manual 526
CURVES FOR TIMED CHARACTERISTICS 

30.4 USER CURVES

The user can programme FOUR curves by entering the desired points into the “User curve 1” to “User curve 4” user curve nodes.

The time corresponding to each I/Ia is programmed in seconds, with a minimum value of 0.020 seconds. These times correspond to the
curve of index 1, but as in curves IEC, the user can programme a time index between 0.05 and 1.09 in the overcurrent protection
settings.

It is not necessary to programme all the points on the curve, the unit will assign the time of the first programmed point to all those I/Ia
of a lower value and the last programmed time to all those of a higher I/Ia, that is to say, the graph will generally start and finish with
straight, horizontal lines. The points between the two programmed points will be calculated by the console as a lineal interpolation.

I/Ia values for times which are superior to that which corresponds to an inferior I/Ia are not admitted, that is to say, ascendant straight
lines are not allowed.

The nodes for the configuration of the curves are:

❑ PROT/RUSC1 user curve 1


❑ PROT/RUSC2 user curve 2
❑ PROT/RUSC3 user curve 3
❑ PROT/RUSC4 user curve 4
Each node uses 3 settings frames, into which the milliseconds of activation for each I/IAJ are entered, with a range of 20 to 600,000
milliseconds.

❑ Crv0 (Low Frame Curve). For setting (milliseconds) the activation times for 1.03 and 1.05 I/IAJ ratios.
❑ Crv1 (Medium Frame Curve). For setting (milliseconds) the activation times for 1.1 and 4 I/IAJ ratios, with steps of 0.1.
❑ Crv1 (High Frame Curve). For setting (milliseconds) the activation times for 4 and 20 I/IAJ ratios, with steps of 0.5.
The programming carried out via PacFactory is done using the programming screen shown in Figure 253, in which:

❑ The times of the curves different points are entered (left table) and the curve’s graph is displayed (right table).
❑ Interpolate points of the curve and enter the known points. By clicking on “Calculate Curve Values”, the missing values are
calculated for the curve.
❑ Reset the curve values “Reset PC column”.
❑ “Save values”. Saves the values entered in order to send them to unit.
❑ “Close”. Returns to the general settings screen, from where they can be sent to the unit.

Ingeteam Technology S.A.


User Manual 527
CURVES FOR TIMED CHARACTERISTICS 

Figure 253. User curve configuration screen

An example is shown below

I/Ia 2 4 8 12 15

T (s) 200 100 70 50 5

Ingeteam Technology S.A.


User Manual 528
MEASUREMENT LIST 

31. MEASUREMENT LIST


The following tables show the list of available measurements. If the model doesn´t have a function, the measurements of that unit are no
available.

Table 252. General measurements

Measurement Node Instance Data Attribute Refresh (ms)


VA MMXU 1 PhV phsA 100
VB MMXU 1 PhV phsB 100
VC MMXU 1 PhV phsC 100
VN MMXU 1 PhV neut 100
AVERAGE V MMXU 1 PhV net 100
VAB MMXU 1 PPV phsAB 100
VBC MMXU 1 PPV phsBC 100
VCA MMXU 1 PPV phsCA 100
AVERAGE U MMXU 1 PPV (PPVm in Ed2) net 100
IN MMXU 1 A neut 100
IA MMXU 1 A phsA 100
IB MMXU 1 A phsB 100
IC MMXU 1 A phsC 100
AVERAGE I MMXU 1 A net 100
ACTIVE POWER P MMXU 1 TotW mag 100
REACTIVE POWER Q MMXU 1 TotVAr mag 100
POWER S MMXU 1 TotVA mag 100
Frequency MMXU 1 Hz net 2
Phase A Active Power MMXU 1 W phsA 100
Phase B Active Power MMXU 1 W phsB 100
Phase C Active Power MMXU 1 W phsC 100
Phase A Reactive Power MMXU 1 VAr phsA 100
Phase B Reactive Power MMXU 1 VAr phsB 100
Phase C Reactive Power MMXU 1 VAr phsC 100
Phase A S Power MMXU 1 VA phsA 100
Phase B S Power MMXU 1 VA phsB 100
Phase C S Power MMXU 1 VA phsC 100
Fault phase A Current MMXU 1 FltA phsA 1000
Fault phase B Current MMXU 1 FltA phsB 1000
Fault phase C Current MMXU 1 FltA phsC 1000
Fault Neutral Current MMXU 1 FltA neut 1000
Max. fault phase A Current MMXU 1 MaxFltA phsA 1000
Max. fault phase B Current MMXU 1 MaxFltA phsB 1000
Max. fault phase C Current MMXU 1 MaxFltA phsC 1000
Max. fault Neutral Current MMXU 1 MaxFltA neut 1000
Cosine phi rms phase A MMXU 1 PF phsA 100
Cosine phi rms phase B MMXU 1 PF phsB 100
Cosine phi rms phase C MMXU 1 PF phsC 100
Cosine phi rms average MMXU 1 PF net 100
Average Power Factor MMXU 1 TotPF mag 100

Ingeteam Power Technology S.A.


Manual de usuario 529
MEASUREMENT LIST 

Table 253. Fundamental measurements

Measurement Node Instance Data Attribute Refresh (ms)


IA fundamental FUNMMXU 1 FunA phsA 100
IB fundamental FUNMMXU 1 FunA phsB 100
IC fundamental FUNMMXU 1 FunA phsC 100
IN fundamental FUNMMXU 1 FunA neut 100
VA fundamental FUNMMXU 1 FunPhV phsA 100
VB fundamental FUNMMXU 1 FunPhV phsB 100
VC fundamental FUNMMXU 1 FunPhV phsC 100
VN fundamental FUNMMXU 1 FunPhV neut 100
Cosine phi phase A (fund) FUNMMXU 1 FunPF phsA 100
Cosine phi phase B (fund) FUNMMXU 1 FunPF phsB 100
Cosine phi phase C (fund) FUNMMXU 1 FunPF phsC 100
Cosine phi average (fund) FUNMMXU 1 FunPF net 100
ACTIVE POWER P (fund) FUNMMXU 1 FunTotW mag 100
REACTIVE POWER Q (fund) FUNMMXU 1 FunTotVAr mag 100
POWER S (fund) FUNMMXU 1 FunTotVA mag 100
Phase A Active P (fund) FUNMMXU 1 FunW phsA 100
Phase B Active P (fund) FUNMMXU 1 FunW phsB 100
Phase C Active P (fund) FUNMMXU 1 FunW phsC 100
Phase A Reactive Q (fund) FUNMMXU 1 FunVAr phsA 100
Phase B Reactive Q (fund) FUNMMXU 1 FunVAr phsB 100
Phase C Reactive Q (fund) FUNMMXU 1 FunVAr phsC 100
Phase A S (fund) FUNMMXU 1 FunVA phsA 100
Phase B S (fund) FUNMMXU 1 FunVA phsB 100
Phase C S (fund) FUNMMXU 1 FunVA phsC 100

Table 254. Instantaneous Fundamental measurements

Measurement Node Instance Data Attribute Refresh (ms)


Analog 1 PHSMMXU 1 OpPhasor1 phsA 100
Analog 2 PHSMMXU 1 OpPhasor2 phsB 100
Analog 3 PHSMMXU 1 OpPhasor3 phsC 100
Analog 4 PHSMMXU 1 OpPhasor4 neut 100
Analog 5 PHSMMXU 1 OpPhasor5 phsA 100
Analog 6 PHSMMXU 1 OpPhasor6 phsB 100
Analog 7 PHSMMXU 1 OpPhasor7 phsC 100
Analog 8 PHSMMXU 1 OpPhasor8 neut 100
Analog 9 PHSMMXU 1 OpPhasor9 phsA 100
Analog 10 PHSMMXU 1 OpPhasor10 phsB 100
Analog 11 PHSMMXU 1 OpPhasor11 phsC 100
Analog 12 PHSMMXU 1 OpPhasor12 net 100

Table 255. Energy counter

Measurement Node Instance Data Attribute Refresh (ms)


Active Energy Out MMTR 1 SupWh actVal 100
Active Energy In MMTR 1 DmdWh actVal 100
Reactive Energy Out MMTR 1 SupVArh actVal 100
Reactive Energy In MMTR 1 DmdVArh actVal 100

Ingeteam Power Technology S.A.


Manual de usuario 530
MEASUREMENT LIST 

Table 256. Sequences

Measurement Node Instance Data Attribute Refresh (ms)


I0 MSQI 1 SeqA c1 2
V0 MSQI 1 SeqV c1 2
I1 MSQI 1 SeqA c2 2
V1 MSQI 1 SeqV c2 2
I2 MSQI 1 SeqA c3 2
V2 MSQI 1 SeqV c3 2

Table 257. THD

Measurement Node Instance Data Attribute Refresh (ms)


THD phase A Current MHAI 1 ThdA phsA 100
THD phase B Current MHAI 1 ThdA phsB 100
THD phase C Current MHAI 1 ThdA phsC 100
THD Neutral Current MHAI 1 ThdA neut 100
THD Average Current MHAI 1 ThdA net 100
THD phase A Voltage MHAI 1 ThdPhV phsA 100
THD phase B Voltage MHAI 1 ThdPhV phsB 100
THD phase C Voltage MHAI 1 ThdPhV phsC 100
THD Neutral Voltage MHAI 1 ThdPhV neut 100
THD Averagel Voltage MHAI 1 ThdPhV net 100

Table 258. Historic Edition 1

Measurement Node Instance Data Attribute Refresh (ms)


Imax Historic phase A MSTA 1 MaxAmps phsA 1000
Imin Historic phase A MSTA 1 MinAmps phsA 1000
Imax Historic phase B MSTA 1 MaxAmps phsB 1000
Imin Historic phase B MSTA 1 MinAmps phsB 1000
Imax Historic phase C MSTA 1 MaxAmps phsC 1000
Imin Historic phase C MSTA 1 MinAmps phsC 1000
Vmax Historic phase A MSTA 1 MaxVolts phsA 1000
Vmin Historic phase A MSTA 1 MinVolts phsA 1000
Vmax Historic phase B MSTA 1 MaxVolts phsB 1000
Vmin Historic phase B MSTA 1 MinVolts phsB 1000
Vmax Historic phase C MSTA 1 MaxVolts phsC 1000
Vmin Historic phase C MSTA 1 MinVolts phsC 1000
VAmax Historic MSTA 1 MaxVA net 1000
VAmin Historic MSTA 1 MinVA net 1000
Wmax Historic MSTA 1 MaxW net 1000
Wmin Historic MSTA 1 MinW net 1000
VAr max Historic MSTA 1 MaxVAr net 1000
VAr min Historic MSTA 1 MinVAr net 1000

Ingeteam Power Technology S.A.


Manual de usuario 531
MEASUREMENT LIST 

Table 259. Historic Edition 2

Measurement Node Instance Data Attribute Refresh (ms)


Imax Historic phase A maxMMXU 1 A phsA.cVal 1000
Imin Historic phase A minMMXU 1 A phsA.cVal 1000
Imax Historic phase B maxMMXU 1 A phsB.cVal 1000
Imin Historic phase B minMMXU 1 A phsB.cVal 1000
Imax Historic phase C maxMMXU 1 A phsC.cVal 1000
Imin Historic phase C minMMXU 1 A phsC.cVal 1000
Vmax Historic phase A maxMMXU 1 PhV phsA.cVal 1000
Vmin Historic phase A minMMXU 1 PhV phsA.cVal 1000
Vmax Historic phase B maxMMXU 1 PhV phsB.cVal 1000
Vmin Historic phase B minMMXU 1 PhV phsB.cVal 1000
Vmax Historic phase C maxMMXU 1 PhV phsC.cVal 1000
Vmin Historic phase C minMMXU 1 PhV phsC.cVal 1000
VAmax Historic maxMMXU 1 TotVA mag.f 1000
VAmin Historic minMMXU 1 TotVA mag.f 1000
Wmax Historic maxMMXU 1 TotW mag.f 1000
Wmin Historic minMMXU 1 TotW mag.f 1000
VAr max Historic maxMMXU 1 TotVAr mag.f 1000
VAr min Historic minMMXU 1 TotVAr mag.f 1000

Ingeteam Power Technology S.A.


Manual de usuario 532
MEASUREMENT LIST 

Table 260. Individual harmonics

Measurement Node Instance Data Attribute Refresh (ms) Refresco (ms)


Harmonic 0 phsA current (%) Harmonics 2nd to 25th MHAI 1 HA phsAHar 100
Harmonic 0 phsB current (%) Harmonics 2nd to 25th MHAI 1 HA phsBHar 100
Harmonic 0 phsC current (%) Harmonics 2nd to 25th MHAI 1 HA phsCHar 100
Harmonic 0 phsA voltage (%) Harmonics 2nd to 25th MHAI 1 HPhV phsAHar 100
Harmonic 0 phsB voltage (%) Harmonics 2nd to 25th MHAI 1 HPhV phsBHar 100
Harmonic 0 phsC voltage (%) Harmonics 2nd to 25th MHAI 1 HPhV phsCHar 100

Table 261. Sag and swell

Measurement Node Instance Data Attribute Refresh (ms)


Event number QVVR 1 EvtNum mag 1000
Last event time QVVR 1 VVaTm mag 1000
Last event V variation QVVR 1 VVa mag 1000
Dip/Swell A start QVVR 1 DipSwlIniA mag 1000
Dip/Swell A end QVVR 1 DipSwlEndA mag 1000
Dip/Swell A max QVVR 1 DipSwlMaxA mag 1000
Dip/Swell A avg QVVR 1 DipSwlAvgA mag 1000
Dip/Swell B start QVVR 1 DipSwlIniB mag 1000
Dip/Swell B end QVVR 1 DipSwlEndB mag 1000
Dip/Swell B max QVVR 1 DipSwlMaxB mag 1000
Dip/Swell B avg QVVR 1 DipSwlAvgB mag 1000
Dip/Swell C start QVVR 1 DipSwlIniC mag 1000
Dip/Swell C end QVVR 1 DipSwlEndC mag 1000
Dip/Swell C max QVVR 1 DipSwlMaxC mag 1000
Dip/Swell C avg QVVR 1 DipSwlAvgC mag 1000

Table 262. Breaker Edition 1

Measurement Node Instance Data Attribute Refresh (ms)


Openings Counter B1 XCBR 1 OpCnt stVal 100
Max.Amp.Switch.ph.A B1 XCBR 1 MCut phsA 1000
Max.Amp.Switch.ph.B B1 XCBR 1 MCut phsB 1000
Max.Amp.Switch.ph.C B1 XCBR 1 MCut phsC 1000
Last Amp.Switch.ph.A B1 XCBR 1 LCut phsA 1000
Last .Amp.Switch.ph.B B1 XCBR 1 LCut phsB 1000
Last .Amp.Switch.ph.C B1 XCBR 1 LCut phsC 1000
Open Counter ph.A B1 XCBR 1 OpenCnt phsA 100
Open Counter ph.B B1 XCBR 1 OpenCnt phsB 100
Open Counter ph.C B1 XCBR 1 OpenCnt phsC 100
Trip Counter ph.A B1 XCBR 1 TripCnt phsA 100
Trip Counter ph.B B1 XCBR 1 TripCnt phsB 100
Trip Counter ph.C B1 XCBR 1 TripCnt phsC 100
Close Counter ph.A B1 XCBR 1 ClCnt phsA 100
Close Counter ph.B B1 XCBR 1 ClCnt phsB 100
Close Counter ph.C B1 XCBR 1 ClCnt phsC 100

Ingeteam Power Technology S.A.


Manual de usuario 533
MEASUREMENT LIST 

Table 263. Breaker Edition 2

Measurement Node Instance Data Attribute Refresh (ms)


Openings Counter B1 XCBR 1 OpCnt stVal 100
Max.Amp.Switch.ph.A B1 XCBR 1 MCut phsA 1000
Max.Amp.Switch.ph.B B1 XCBR 1 MCut phsB 1000
Max.Amp.Switch.ph.C B1 XCBR 1 MCut phsC 1000
Last Amp.Switch.ph.A B1 XCBR 1 LCut phsA 1000
Last .Amp.Switch.ph.B B1 XCBR 1 LCut phsB 1000
Last .Amp.Switch.ph.C B1 XCBR 1 LCut phsC 1000
Open Counter ph.A B1 XCBR 1 OpenCntA stVal 100
Open Counter ph.B B1 XCBR 1 OpenCntB stVal 100
Open Counter ph.C B1 XCBR 1 OpenCntC stVal 100
Trip Counter ph.A B1 XCBR 1 TripCntA stVal 100
Trip Counter ph.B B1 XCBR 1 TripCntB stVal 100
Trip Counter ph.C B1 XCBR 1 TripCntC stVal 100
Close Counter ph.A B1 XCBR 1 ClCntA stVal 100
Close Counter ph.B B1 XCBR 1 ClCntB stVal 100
Close Counter ph.C B1 XCBR 1 ClCntC stVal 100

Ingeteam Power Technology S.A.


Manual de usuario 534
MEASUREMENT LIST 

Table 264. Breaker 1 - Operation supervision

Measurement Node Instance Data Attribute Refresh (ms)


Ki2 accumulated ph.A B1 CBOU 1 KI2A phsA 1000
Ki2 accumulated ph.B B1 CBOU 1 KI2A phsB 1000
Ki2 accumulated ph.C B1 CBOU 1 KI2A phsC 1000
Max.Ki2 accumulated B1 CBOU 1 MaxKI2A general 1000
T.electric opening Br.1 A CBOU 1 ElOpnTmsA mag 1000
T.electric opening Br.1 B CBOU 1 ElOpnTmsB mag 1000
T.electric opening Br.1 C CBOU 1 ElOpnTmsC mag 1000
T.mechanic opening Br.1 A CBOU 1 MeOpnTmsA mag 1000
T.mechanic opening Br.1 B CBOU 1 MeOpnTmsB mag 1000
T.mechanic opening Br.1 C CBOU 1 MeOpnTmsC mag 1000
T.opening dispersion Br.1 AB CBOU 1 DiOpnTmsAB mag 1000
T.opening dispersion Br.1 BC CBOU 1 DiOpnTmsBC mag 1000
T.opening dispersion Br.1 CA CBOU 1 DiOpnTmsCA mag 1000
T.electric closing Br.1 A CBOU 1 ElClsTmsA mag 1000
T.electric closing Br.1 B CBOU 1 ElClsTmsB mag 1000
T.electric closing Br.1 C CBOU 1 ElClsTmsC mag 1000
T.mechanic closing Br.1 A CBOU 1 MeClsTmsA mag 1000
T.mechanic closing Br.1 B CBOU 1 MeClsTmsB mag 1000
T.mechanic closing Br.1 C CBOU 1 MeClsTmsC mag 1000
T.closing dispersion Br.1 AB CBOU 1 DiClsTmsAB mag 1000
T.closing dispersion Br.1 BC CBOU 1 DiClsTmsBC mag 1000
T.closing dispersion Br.1 CA CBOU 1 DiClsTmsCA mag 1000
Inactive days Br.1 A CBOU 1 NoOpDayA mag 1000
Inactive days Br.1 B CBOU 1 NoOpDayB mag 1000
Inactive days Br.1 C CBOU 1 NoOpDayC mag 1000
Max.dispersion opening 1 AB CBOU 1 MaxDiOpAB mag 1000
Max.dispersion opening 1 BC CBOU 1 MaxDiOpBC mag 1000
Max.dispersion opening 1 CA CBOU 1 MaxDiOpCA mag 1000
Max.dispersion closing 1 AB CBOU 1 MaxDiClAB mag 1000
Max.dispersion closing 1 BC CBOU 1 MaxDiClBC mag 1000
Max.dispersion closing 1 CA CBOU 1 MaxDiClCA mag 1000
Avg.dispersion opening 1 AB CBOU 1 MedDiOpAB mag 1000
Avg.dispersion opening 1 BC CBOU 1 MedDiOpBC mag 1000
Avg.dispersion opening 1 CA CBOU 1 MedDiOpCA mag 1000
Avg.dispersion closing 1 AB CBOU 1 MedDiClAB mag 1000
Avg.dispersion closing 1 BC CBOU 1 MedDiClBC mag 1000
Avg.dispersion closing 1 CA CBOU 1 MedDiClCA mag 1000
Avg.electric opening 1 A CBOU 1 MedElOpAB mag 1000
Avg.electric opening 1 B CBOU 1 MedElOpBC mag 1000
Avg.electric opening 1 C CBOU 1 MedElOpCA mag 1000
Avg.electric closing 1 A CBOU 1 MedElClAB mag 1000
Avg.electric closing 1 B CBOU 1 MedElClBC mag 1000
Avg.electric closing 1 C CBOU 1 MedElClCA mag 1000
Avg.mechanical opening 1 A CBOU 1 MedMeOpAB mag 1000
Avg.mechanical opening 1 B CBOU 1 MedMeOpBC mag 1000
Avg.mechanical opening 1 C CBOU 1 MedMeOpCA mag 1000
Avg.mechanical closing 1 A CBOU 1 MedMeClAB mag 1000
Avg.mechanical closing 1 B CBOU 1 MedMeClBC mag 1000
Avg.mechanical closing 1 C CBOU 1 MedMeClCA mag 1000
Max.electric opening 1 A CBOU 1 MaxElOpAB mag 1000
Max.electric opening 1 B CBOU 1 MaxElOpBC mag 1000
Max.electric opening 1 C CBOU 1 MaxElOpCA mag 1000
Max.electric closing 1 A CBOU 1 MaxElClAB mag 1000
Max.electric closing 1 B CBOU 1 MaxElClBC mag 1000
Max.electric closing 1 C CBOU 1 MaxElClCA mag 1000
Max.mechanical opening 1 A CBOU 1 MaxMeOpAB mag 1000
Max.mechanical opening 1 B CBOU 1 MaxMeOpBC mag 1000
Max.mechanical opening 1 C CBOU 1 MaxMeOpCA mag 1000
Max.mechanical closing 1 A CBOU 1 MaxMeClAB mag 1000
Max.mechanical closing 1 B CBOU 1 MaxMeClBC mag 1000

Ingeteam Power Technology S.A.


Manual de usuario 535
MEASUREMENT LIST 

Max.mechanical closing 1 C CBOU 1 MaxMeClCA mag 1000


Br1 Pole wear A CBOU 1 BrWear phsA 1000
Br1 Pole wear B CBOU 1 BrWear phsB 1000
Br1 Pole wear C CBOU 1 BrWear phsC 1000

Tabla 265. Breaker 2 measurements (only models with two breakers)

Measurement Node Instance Data Attribute Refresh (ms)


IA2 MDIF 2 OpARem phsA 2
IB2 MDIF 2 OpARem phsB 2
IC2 MDIF 2 OpARem phsC 2
IA2 fundamental MDIF 2 FunARem phsA 2
IB2 fundamental MDIF 2 FunARem phsB 2
IC2 fundamental MDIF 2 FunARem phsC 2
Fault phase A2 Current MDIF 2 FltARem phsA 2
Fault phase B2 Current MDIF 2 FltARem phsB 2
Fault phase C2 Current MDIF 2 FltARem phsC 2
THD phase A2 Current MDIF 2 ThdARem phsA 2
THD phase B2 Current MDIF 2 ThdARem phsB 2
THD phase C2 Current MDIF 2 ThdARem phsC 2
Max. fault phase A2 Current MDIF 2 MaxFltARem phsA 1000
Max. fault phase B2 Current MDIF 2 MaxFltARem phsB 1000
Max. fault phase C2 Current MDIF 2 MaxFltARem phsC 1000

Table 266. Sequences 52 ½ (Only models with two breakers)37

Measurement Node Instance Data Attribute Refresh (ms)


3I0 breaker 1 BH/PTRC 1 SeqA c1 2
3I0 breaker 2 BH/PTRC 1 SeqA c2 2

Table 267. Breaker 2 Edition 1

Measurement Node Instance Data Attribute Refresh (ms)


Openings Counter B1 XCBR 2 OpCnt stVal 100
Max.Amp.Switch.ph.A B1 XCBR 2 MCut phsA 1000
Max.Amp.Switch.ph.B B1 XCBR 2 MCut phsB 1000
Max.Amp.Switch.ph.C B1 XCBR 2 MCut phsC 1000
Last Amp.Switch.ph.A B1 XCBR 2 LCut phsA 1000
Last .Amp.Switch.ph.B B1 XCBR 2 LCut phsB 1000
Last .Amp.Switch.ph.C B1 XCBR 2 LCut phsC 1000
Open Counter ph.A B1 XCBR 2 OpenCnt phsA 100
Open Counter ph.B B1 XCBR 2 OpenCnt phsB 100
Open Counter ph.C B1 XCBR 2 OpenCnt phsC 100
Trip Counter ph.A B1 XCBR 2 TripCnt phsA 100
Trip Counter ph.B B1 XCBR 2 TripCnt phsB 100
Trip Counter ph.C B1 XCBR 2 TripCnt phsC 100
Close Counter ph.A B1 XCBR 2 ClCnt phsA 100
Close Counter ph.B B1 XCBR 2 ClCnt phsB 100
Close Counter ph.C B1 XCBR 2 ClCnt phsC 100

37
From firmware version 6.0.18.0 and ICD version 8.1.0.20

Ingeteam Power Technology S.A.


Manual de usuario 536
MEASUREMENT LIST 

Table 268. Breaker 2 Edition 2

Measurement Node Instance Data Attribute Refresh (ms)


Openings Counter B1 XCBR 2 OpCnt stVal 100
Max.Amp.Switch.ph.A B1 XCBR 2 MCut phsA 1000
Max.Amp.Switch.ph.B B1 XCBR 2 MCut phsB 1000
Max.Amp.Switch.ph.C B1 XCBR 2 MCut phsC 1000
Last Amp.Switch.ph.A B1 XCBR 2 LCut phsA 1000
Last .Amp.Switch.ph.B B1 XCBR 2 LCut phsB 1000
Last .Amp.Switch.ph.C B1 XCBR 2 LCut phsC 1000
Open Counter ph.A B1 XCBR 2 OpenCntA stVal 100
Open Counter ph.B B1 XCBR 2 OpenCntB stVal 100
Open Counter ph.C B1 XCBR 2 OpenCntC stVal 100
Trip Counter ph.A B1 XCBR 2 TripCntA stVal 100
Trip Counter ph.B B1 XCBR 2 TripCntB stVal 100
Trip Counter ph.C B1 XCBR 2 TripCntC stVal 100
Close Counter ph.A B1 XCBR 2 ClCntA stVal 100
Close Counter ph.B B1 XCBR 2 ClCntB stVal 100
Close Counter ph.C B1 XCBR 2 ClCntC stVal 100

Ingeteam Power Technology S.A.


Manual de usuario 537
MEASUREMENT LIST 

Table 269. Breaker 2 - Operation supervision (only models with two breakers)

Measurement Node Instance Data Attribute Refresh (ms)


Ki2 accumulated ph.A B2 CBOU 2 KI2A phsA 1000
Ki2 accumulated ph.B B2 CBOU 2 KI2A phsB 1000
Ki2 accumulated ph.C B2 CBOU 2 KI2A phsC 1000
Max.Ki2 accumulated B2 CBOU 2 MaxKI2A general 1000
T.electric opening Br.2 A CBOU 2 ElOpnTmsA mag 1000
T.electric opening Br.2 B CBOU 2 ElOpnTmsB mag 1000
T.electric opening Br.2 C CBOU 2 ElOpnTmsC mag 1000
T.mechanic opening Br.2 A CBOU 2 MeOpnTmsA mag 1000
T.mechanic opening Br.2 B CBOU 2 MeOpnTmsB mag 1000
T.mechanic opening Br.2 C CBOU 2 MeOpnTmsC mag 1000
T.opening dispersion Br.2 AB CBOU 2 DiOpnTmsAB mag 1000
T.opening dispersion Br.2 BC CBOU 2 DiOpnTmsBC mag 1000
T.opening dispersion Br.2 CA CBOU 2 DiOpnTmsCA mag 1000
T.electric closing Br.2 A CBOU 2 ElClsTmsA mag 1000
T.electric closing Br.2 B CBOU 2 ElClsTmsB mag 1000
T.electric closing Br.2 C CBOU 2 ElClsTmsC mag 1000
T.mechanic closing Br.2 A CBOU 2 MeClsTmsA mag 1000
T.mechanic closing Br.2 B CBOU 2 MeClsTmsB mag 1000
T.mechanic closing Br.2 C CBOU 2 MeClsTmsC mag 1000
T.closing dispersion Br.2 AB CBOU 2 DiClsTmsAB mag 1000
T.closing dispersion Br.2 BC CBOU 2 DiClsTmsBC mag 1000
T.closing dispersion Br.2 CA CBOU 2 DiClsTmsCA mag 1000
Inactive days Br.2 A CBOU 2 NoOpDayA mag 1000
Inactive days Br.2 B CBOU 2 NoOpDayB mag 1000
Inactive days Br.2 C CBOU 2 NoOpDayC mag 1000
Max.dispersion opening 2 AB CBOU 2 MaxDiOpAB mag 1000
Max.dispersion opening 2 BC CBOU 2 MaxDiOpBC mag 1000
Max.dispersion opening 2 CA CBOU 2 MaxDiOpCA mag 1000
Max.dispersion closing 2 AB CBOU 2 MaxDiClAB mag 1000
Max.dispersion closing 2 BC CBOU 2 MaxDiClBC mag 1000
Max.dispersion closing 2 CA CBOU 2 MaxDiClCA mag 1000
Avg.dispersion opening 2 AB CBOU 2 MedDiOpAB mag 1000
Avg.dispersion opening 2 BC CBOU 2 MedDiOpBC mag 1000
Avg.dispersion opening 2 CA CBOU 2 MedDiOpCA mag 1000
Avg.dispersion closing 2 AB CBOU 2 MedDiClAB mag 1000
Avg.dispersion closing 2 BC CBOU 2 MedDiClBC mag 1000
Avg.dispersion closing 2 CA CBOU 2 MedDiClCA mag 1000
Avg.electric opening 2 A CBOU 2 MedElOpAB mag 1000
Avg.electric opening 2 B CBOU 2 MedElOpBC mag 1000
Avg.electric opening 2 C CBOU 2 MedElOpCA mag 1000
Avg.electric closing 2 A CBOU 2 MedElClAB mag 1000
Avg.electric closing 2 B CBOU 2 MedElClBC mag 1000
Avg.electric closing 2 C CBOU 2 MedElClCA mag 1000
Avg.mechanical opening 2 A CBOU 2 MedMeOpAB mag 1000
Avg.mechanical opening 2 B CBOU 2 MedMeOpBC mag 1000
Avg.mechanical opening 2 C CBOU 2 MedMeOpCA mag 1000
Avg.mechanical closing 2 A CBOU 2 MedMeClAB mag 1000
Avg.mechanical closing 2 B CBOU 2 MedMeClBC mag 1000
Avg.mechanical closing 2 C CBOU 2 MedMeClCA mag 1000
Max.electric opening 2 A CBOU 2 MaxElOpAB mag 1000
Max.electric opening 2 B CBOU 2 MaxElOpBC mag 1000
Max.electric opening 2 C CBOU 2 MaxElOpCA mag 1000
Max.electric closing 2 A CBOU 2 MaxElClAB mag 1000
Max.electric closing 2 B CBOU 2 MaxElClBC mag 1000
Max.electric closing 2 C CBOU 2 MaxElClCA mag 1000
Max.mechanical opening 2 A CBOU 2 MaxMeOpAB mag 1000
Max.mechanical opening 2 B CBOU 2 MaxMeOpBC mag 1000
Max.mechanical opening 2 C CBOU 2 MaxMeOpCA mag 1000
Max.mechanical closing 2 A CBOU 2 MaxMeClAB mag 1000
Max.mechanical closing 2 B CBOU 2 MaxMeClBC mag 1000

Ingeteam Power Technology S.A.


Manual de usuario 538
MEASUREMENT LIST 

Max.mechanical closing 2 C CBOU 2 MaxMeClCA mag 1000


Br2 Pole wear A CBOU 2 BrWear phsA 1000
Br2 Pole wear B CBOU 2 BrWear phsB 1000
Br2 Pole wear C CBOU 2 BrWear phsC 1000

Table 270. Recloser

Measurement Node Instance Data Attribute Refresh (ms)


Total Reclose Counter ZRREC 1 RecCnt actVal 100
1st 1phase Reclose Counter ZRREC 1 Rec1P1Cnt actVal 100
1st 3phase Reclose Counter ZRREC 1 Rec1P3Cnt actVal 100
Second Reclose Counter ZRREC 1 Rec2Cnt actVal 100
Third Reclose Counter ZRREC 1 Rec3Cnt actVal 100
Fourth Reclose Counter ZRREC 1 Rec4Cnt actVal 100

Table 271. Synchronism

Measurement Node Instance Data Attribute Refresh (ms)


V synchro RSYN 1 PhV net 100
Sychro Frequency RSYN 1 Hz mag 2
V synchro Diff RSYN 1 DifVClc mag 2
Ang synchro Diff RSYN 1 DifAngClc mag 2
Hz synchro Diff RSYN 1 DifHzClc mag 2

Table 272. Synchronism 2 (models with 2 synchronism units)

Measurement Node Instance Data Attribute Refresh (ms)


V synchro SECRSYN 1 PhV net 100
Sychro Frequency SECRSYN 1 Hz mag 2
V synchro Diff SECRSYN 1 DifVClc mag 2
Ang synchro Diff SECRSYN 1 DifAngClc mag 2
Hz synchro Diff SECRSYN 1 DifHzClc mag 2

Table 273. Locator

Measurement Node Instance Data Attribute Refresh (ms)


Fault Distance RFLO 1 FltDiskm net 100

Tabla 274. Thermal Image

Measurement Node Instance Data Attribute Refresh (ms)


Thermal Img. Phases PTTR 1 TmpRl mag 100
Thermal Img. Gr. GPTTR 1 TmpRl mag 100

Ingeteam Power Technology S.A.


Manual de usuario 539
MEASUREMENT LIST 

Table 275. Board 1 of RTD and analogue outputs

Measurement Node Instance Data Attribute Refresh (ms)


Temperature 1 RTDGGIO 1 Tmp1 mag 1000
Temperature 2 RTDGGIO 1 Tmp2 mag 1000
Temperature 3 RTDGGIO 1 Tmp3 mag 1000
Temperature 1 RTDGGIO 1 Tmp4 mag 1000
Temperature 2 RTDGGIO 1 Tmp5 mag 1000
Temperature 3 RTDGGIO 1 Tmp6 mag 1000
Temperature 1 RTDGGIO 1 Tmp7 mag 1000
Temperature 2 RTDGGIO 1 Tmp8 mag 1000
Temperature 3 RTDGGIO 1 Tmp9 mag 1000
Temperature 1 RTDGGIO 1 Tmp10 mag 1000
Temperature 2 RTDGGIO 1 Tmp11 mag 1000
Analog. output 1 RTDGGIO 1 OutAn1 mag 1000
Analog. output 2 RTDGGIO 1 OutAn2 mag 1000
Analog. output 3 RTDGGIO 1 OutAn3 mag 1000
Analog. output 4 RTDGGIO 1 OutAn4 mag 1000

Table 276. Board 2 of RTD and analogue outputs

Measurement Node Instance Data Attribute Refresh (ms)


Temperature 1 RTDGGIO 2 Tmp1 mag 1000
Temperature 2 RTDGGIO 2 Tmp2 mag 1000
Temperature 3 RTDGGIO 2 Tmp3 mag 1000
Temperature 1 RTDGGIO 2 Tmp4 mag 1000
Temperature 2 RTDGGIO 2 Tmp5 mag 1000
Temperature 3 RTDGGIO 2 Tmp6 mag 1000
Temperature 1 RTDGGIO 2 Tmp7 mag 1000
Temperature 2 RTDGGIO 2 Tmp8 mag 1000
Temperature 3 RTDGGIO 2 Tmp9 mag 1000
Temperature 1 RTDGGIO 2 Tmp10 mag 1000
Temperature 2 RTDGGIO 2 Tmp11 mag 1000
Analog. output 1 RTDGGIO 2 OutAn1 mag 1000
Analog. output 2 RTDGGIO 2 OutAn2 mag 1000
Analog. output 3 RTDGGIO 2 OutAn3 mag 1000
Analog. output 4 RTDGGIO 2 OutAn4 mag 1000

Table 277. Temperature

Measurement Node Instance Data Attribute Refresh (ms)


Temperature CTSU 1 Temp net 1000

Table 278. Power supply

Measurement Node Instance Data Attribute Refresh (ms)


Power Supply GENLLN0 1 PSup net 1000
Power Supply 2 GENLLN0 1 PSup2 net 1000

Table 279. Internal battery

Measurement Node Instance Data Attribute Refresh (ms)


Internal battery LPHD 1 IntBat net 1000

Ingeteam Power Technology S.A.


Manual de usuario 540
PREVENTIVE MAINTENANCE 

32. PREVENTIVE MAINTENANCE


The unit continually checks the various incorporated elements and cards. If an error is detected in any of the elements or cards, an
alarm is generated.

The available signals indicate faults in the card check, in the communications between the cards, in the unit’s configuration, etc.

The detected errors are shown in:

❑ Status report
❑ Incident report
❑ Sequence of events (SOE)
❑ Digital outputs and CPU hardware alarm output.
❑ IHMI leds and status leds
The errors can be critical and non critical, depending on the effect they have in the device.

Critical errors
Critical hardware error. Indicates that a critical error has been produced. In addition to this signal, the cause that produced the signal
will be indicated.

If the error affects the unit’s operation, a critical error is generated, which in addition to the signal acts on:

❑ Colour front LED. Non-configurable status LED, which indicates the unit’s general status. If the LED is green, it indicates
that everything is correct, while if it is red it indicates a critical error in the unit.
❑ CPU Relay. Non-configurable 3-contact relay, which indicates the unit’s general status. If the LED is active (common
terminal – NO), it indicates that everything is correct, while if it is deactivated (common terminal– NC) it indicates a critical
error in the unit. If the unit is switched off, the relay is deactivated.
The causes that produce errors are:

❑ CPU error. Indicates that the check has detected an error in the CPU
❑ Analogue error. Indicates an error in transformers card.
❑ I/O micro error. Indicates an error in the I/O cards’ micro.
❑ Analogue connection error. Indicates that a fault has been produced in the communications between the CPU and the
transformers card.
❑ I/O connection error. Indicates that a fault has been produced in the communication between the CPU and an I/O card.
Additionally, it will indicate the card which has suffered the failure:
 Error card address x. Indicates that there is a communication error with the card with the address x.
❑ Front connection error. Indicates that a fault has been produced in the communications between the CPU and the unit’s
front card.
❑ Shared analogue memory error. Indicates that a fault has been produced in the Data exchange memory between the CPU
and the transformers card.
❑ Error shared I/O memory. Indicates that a fault has been produced in the Data exchange memory between the CPU and
the I/O cards.
❑ Alarm settings. Indicates that errors have been detected in the storage of the unit’s settings.
❑ FW Alarm. Indicates that the relay firmware versions are incompatible.
❑ Memory check alarm. Indicates that errors have been detected in the checking of the unit’s memory.
❑ Converter check alarm. Indicates that errors have been detected in the transformers card AD converter.
❑ Converter voltage level alarm. Indicates that errors have been detected in the transformers card reference voltages..
❑ Relay activation alarm. Indicates that an error has been detected in the activation of at least one of the I/O cards’ relays.
❑ I/O configuration error. Indicates that the configuration of the I/O cards does not coincide with the unit’s correct
configuration.

Ingeteam Power Technology S.A.


Manual de usuario 541
PREVENTIVE MAINTENANCE 

❑ General Vdc error. Indicates a failure in the internal power supply levels.
❑ For each I/O card there is are 5 signals, indicating:
 Status OK. Indicates that the card is configured correctly and without errors
 Configured & No_detected. Indicates that the card is configured by the user, but not detected in the unit. This may be
because it is not assembled or because it has an error. Equivalent to the current communication error.
 Different configuration. The type indicated by the user and the type detected by the unit do not coincide.
 No_configured & detected. Indicates that card that has not been configured by the user has been detected in an
address.
 Internal card error. A card check error has been received (includes relay check).
Non critical errors
These errors have a limited effect on the device.

❑ RTC clock error. Indicates that the check has detected an error in the real time clock.
❑ Continuous component monitoring alarm. Indicates that an error in the continuous measurement monitoring has been
detected in the transformers card.
❑ Frequency configuration error. This is not a unit failure, but rather a configuration failure. Indicates that the frequency
measurement of the signals being injected into the unit do not match the set measurement, that is, the unit is configured
as 50Hz and the signals which are being injected are greater than 55Hz; or that the unit is configured as 60 Hz and the
signals being injected are less than 55 Hz.
❑ Internal battery failure. Indicates that the data storage battery is below the security levels and that the data may be lost at
shutdown.
❑ Version compatibility error. Indicates that the versions of the unit's firmware are not correct.
❑ Time setting configuration alarm. Indicates that there is an error in the configuration of the unit’s time setting.

32.1 ERROR DETECTION

The error detection can be made by any of the indicated ways.

Status report:
Figure 254 shows the screen of the PacFactory that show the available check signals.

The example screen shows activation of critical error (HW error), generated by I/O configuration error (card 2 is not detected). It
also indicates Internal battery failure. On the other hand, it shows I/O card 1 is correct.

Incident reports and sequence of events:


The available check signals are shown in both messages.

Led and digital outputs:


The leds and digital output can be configured with any of the error signals

Status Led and critical error output:


Colour front LED and CPU relay are activated when a critical error is detected. They are not configurable.

Ingeteam Power Technology S.A.


Manual de usuario 542
PREVENTIVE MAINTENANCE 

Figure 254 Device checks screen

32.2 ERROR HANDLING PROCEDURE

The procedure will depend on the detected error and the device status.

❑ If the device is off, check that the power supply is correct. If the device is well supplied, contact the technical service
❑ If the device is on but it shows failure, return to the events screen and check which type of error it is
 If critical error, with no specific indication, is shown and the error persists after turning the unit off and on,
contact the technical service.
 If converter or reference voltage error is shown. Check the Measurements, and if they are correct, turn off and
on the unit; if the error does not disappear, contact the technical service.
 If Clock error is shown, synchronize manually. If the error persists, contact the technical service.
 If error in the setting is shown, send the settings again. If error persists contact the technical service

Ingeteam Power Technology S.A.


Manual de usuario 543
PROTECTION DEVICES WITH SAMPLED VALUES 

33. PROTECTION DEVICES WITH SAMPLED VALUES


These protection units receive samples of analog measurements using Sampled Values (SV) protocol, through an Ethernet network.

They can be connected to merging units or electronic transformers that follow IEC61850-9-2 or IEC61869-9 standards.

The device can communicate through two physical Ethernet interfaces RJ45 or optic fibre. PRP/HSR redundancy and Link failover
redundancy are available.

Available measures and their accuracy are determined by the accuracy of the external SV publishers. These publishers will be responsible
for capturing and sending analog measurements of the lines, generating SV frames through an Ethernet communications network. The
device will only subscribe, among all the available measures, to those that are necessary for their correct operation.

Local measures captured directly through current and / or voltage input channels are allowed. Therefore, some of the measures can be
local and some others sampled values. In order to operate correctly, the measures must be synchronized by GPS.

The following figures show, according to model encoding, the board position.

Figure 255 19” chassis and redundant communications

Figure 256 19” chassis and redundant power supply and communications

Ingeteam Power Technology S.A.


User Manual 544
PROTECTION DEVICES WITH SAMPLED VALUES 

33.1 DEVICE MODELS

There are multifunction protection (MD), distance (ZT), differential transformer (TD), line differential (LD) and control with measure
(CD). The detailed functions included in every family are explained in the user manual of the family.

The device model code includes three additional characters at the end of the model encoding to select the sampled values ports and
the type of measures (see chapter 1).

In these devices, the housing must be Chassis 19" 4U and I/O board 6, 7 and 8 are not available.

Figure 257 Sampled values options

CONTROL

HOUSING

ANALOG
MODEL

COM1
COM2
COM3
COM4
COM5
COM6

ETH1
ETH2

ETH1
ETH2
I/O 1

I/O 2

I/O 3

I/O 4

I/O 5

I/O 6

I/O 7

I/O 8
INGEPAC EF XX MODEL INGEPAC EF- - A - A - A

MSV COMMUNICATION PORT (Sample values)


E GFO ETH-1
F RJ45 ETH-2
L LC
O GFO (ETH with PRP/HSR/Switch)
P RJ45 (ETH with PRP/HSR/Switch)
- Nada

LOCAL ANALOG MEASURES


No local measures -
Configurable (All/None local) D

33.2 PUBLISHERS DECLARATION

It is necessary to have configuration files (CID) or configuration data of the SV publishers. If the subscription is made using PacFactory
configuration tool, it is mandatory to import the CID files of the publishers and receivers into the same installation.

For detailed information see the "Add-in of subscription" chapter.

33.3 SAMPLED VALUES SUBSCRIPTION

The sampled values subscription is performed according to the IEC61850 standard (edition 2).

The details of this functionality are:

❑ It is only allowed sampled values that comply with the recommended for protection and measurement, indicated in IEC61850-9-
2LE ("Implementation guideline for digital interface to instrument transformers using IEC 61850-9-2" of UCA International Users
Group) and IEC61869-9 ("Instrument transformers - Part 9: Digital interface for instrument transformers") standards, allowing the
subscription up to 8 publishers. All subscribed publishers must use the same standard. If it is subscribed to publishers with different
standards, the CID will be erased because of a non-valid configuration.
❑ After sending a configuration file, the subscription and reception remain operative until the CID has been parsed and fully
validated. Then, the new subscription settings are loaded.
❑ The subscription is made with EC61850 edition 2 and can be used with edition 1.

33.3.1 Configuration
According to IEC 61850 edition 2, the sampled values subscription uses the Inputs-ExtRef in the CID.

The Inputs section defines all external values that will be received from other computers. In this section each ExtRef element refers
to an external data and the element intAddr performs the mapping or association to a data of the device.

In the case of sampled values, the Inputs section is included in the logical node "PHSMMXU". This node has an "OpPhasor" element
associated with each analog measurement of the device. In this way, an external measurement, received through sampled values,
can be assigned to an internal measurement of the subscriber device.

Ingeteam Power Technology S.A.


User Manual 545
PROTECTION DEVICES WITH SAMPLED VALUES 

The CID file of an IED with subscriptions to configured SMV messages contains several sections of IEDs. The section of the IED itself
and sections of each merging unit IEDs that publishes the sampled values to which it is subscribed.

These sections of the external IEDs only contain the data model necessary to perform the subscription in order to reduce the size of
the CID file.

For more information about the sampled values subscription configuration process, refer to the configuration software tool's user
manual (energyFactorySuite/pacFactory).

33.3.2 ADD-IN of subscription


The configuration tool has an add-in that allows the relay to subscribe to the publishers of sampled values in an easy way. To access it,
it is necessary to access the 61850 configuration menu, as shown in Figure 258.

Once the 61850 configuration menu is selected, through the icon , the subscriptions configurator is accessed, valid both for
subscriptions to Gooses and to sampled values. In this case, "Sampled Values" option will be selected, as shown in Figure 259.

Configuration tool shows all the sampled values control blocks available in the installation, allowing a maximum of 8 subscriptions
(Figure 258).

It is also possible to monitor the subscriptions by using LSVS logical nodes.

"Data Binding" tab (Figure 261) shows the measurement channels used by the protection (depending on the model), and the current
and voltage measurements (TCTR and TVTR) available in the added control blocks. Each data channel of the protection can be assigned
a data, respecting the type of measurement of each channel, TCTR for intensities and TVTR for voltages.

Figure 258 Subscription menu selection

Ingeteam Power Technology S.A.


User Manual 546
PROTECTION DEVICES WITH SAMPLED VALUES 

Figure 259 Subscription configuration

Figure 260 Sampled values control blocks selection

Ingeteam Power Technology S.A.


User Manual 547
PROTECTION DEVICES WITH SAMPLED VALUES 

Figure 261 LSVS nodes assignment

Figure 2622 Channel assignment

33.3.3 Monitoring
The LSVS logical node of the data model is used to monitor subscriptions to SV messages. There are 8 instances of LSVS logical
nodes that allow to monitor up to 8 subscriptions to sampled values.

The configuration value in the LSVS logical node is the SvCBRef data (reference to the Sampled Values control block subscribed).
This reference must be filled out when doing the configuration of the subscription, additionally allows to be modified in execution
through an IEC 61850 client.

The values monitored in this logical node are:

❑ NdsCom: Subscription needs commissioning. When true, the received SV message does not correspond to the current
subscription settings. Verify that the configuration revision is correct.
❑ St: When true, the subscription is active. Otherwise it is inactive.
❑ SimSt: If true, subscribed SV messages with the simulation bit set are being received and accepted
❑ ConfRevNum: The expected configuration revision number in SV messages.
❑ RxConfRevNum: The configuration revision number received in SV messages.
All this data are mapped in the internal database of the device and can be used in logics of the device and in the local display.

The assigned Boolean signals are listed in the following table:

Ingeteam Power Technology S.A.


User Manual 548
PROTECTION DEVICES WITH SAMPLED VALUES 

Table 280. LSVS internal signals

LOGICAL NODE ELEMENT ASOCIATED INTERNAL SIGNAL


St (Subscription status) 24960
LSVS1 NdsCom (Needs commissioning) 24961
SimSt (Simulation status) 24962
St (Subscription status) 24963
LSVS2 NdsCom (Needs commissioning) 24964
SimSt (Simulation status) 24665
St (Subscription status) 24966
LSVS3 NdsCom (Needs commissioning) 24967
SimSt (Simulation status) 24968
St (Subscription status) 24969
LSVS4 NdsCom (Needs commissioning) 24970
SimSt (Simulation status) 24971
St (Subscription status) 24972
LSVS5 NdsCom (Needs commissioning) 24973
SimSt (Simulation status) 24974
St (Subscription status) 24975
LSVS6 NdsCom (Needs commissioning) 24976
SimSt (Simulation status) 24977
St (Subscription status) 24978
LSVS7 NdsCom (Needs commissioning) 24979
SimSt (Simulation status) 24980
St (Subscription status) 24981
LSVS8 NdsCom (Needs commissioning) 24982
SimSt (Simulation status) 24983

The following table, shows the integer signals. Internally they are mapped to counters

Table 281. LSVS counters

LOGICAL NODE ELEMENT ASOCIATED INTERNAL COUNTER


ConfRevNum (ConfRev configured) 177
LSVS1
RxConfRevNum (ConfRev received) 178
ConfRevNum (ConfRev configured) 179
LSVS2
RxConfRevNum (ConfRev received) 180
ConfRevNum (ConfRev configured) 181
LSVS3
RxConfRevNum (ConfRev received) 182
ConfRevNum (ConfRev configured) 183
LSVS4
RxConfRevNum (ConfRev received) 184
ConfRevNum (ConfRev configured) 185
LSVS5
RxConfRevNum (ConfRev received) 186
ConfRevNum (ConfRev configured) 187
LSVS6
RxConfRevNum (ConfRev received) 188
ConfRevNum (ConfRev configured) 189
LSVS7
RxConfRevNum (ConfRev received) 190
ConfRevNum (ConfRev configured) 191
LSVS8
RxConfRevNum (ConfRev received) 192

Ingeteam Power Technology S.A.


User Manual 549
PROTECTION DEVICES WITH SAMPLED VALUES 

33.4 CONFIGURABLE LOCAL MEASURES

The device code selection has different options for the local measures.

In the "-" option, all measures are received through communications, using sampled values messages.

In the "D" option, depending on the binary file loaded on the analog card, or all the measurements are wired directly to the analog
card's measurement transformers (conventional wiring), or all of them are received by communications in the form of sampled
values. The options are:

❑ All measures received from local transformer.


 The signal "SV receiver device" is deactivated.
 The device´s version doesn´t include the SV board versions.

❑ All measures received from sampled values.


 The signal "SV receiver device" is activated.
 The device´s version includes the SV board versions.

33.5 SAMPLED VALUES SIMULATION

The device implements the simulation mode defined in the IEC 61850 Edition 2.

This mode allows the simulation of any SV that is present in the communication network so that two SV with the same information
data will be present at the same moment, the real one without the simulation bit active and the simulated one with the simulation bit
active. If the subscriber is in simulation mode, once it has received the first simulation SV its values will be used instead of the values of
the original SV. Therefore, if the device is in simulation mode, it still accepts 'original' SV messages, and only discards the 'original' SV
messages for those SVs which are simulated.

Simulation mode is enabled with the controllable data "Sim" included in the LPHD logical node in the GEN logical device.

In each LSVS logical node, used to monitor SV subscription, the SimSt status shows with TRUE value that subscribed SV messages with
the simulation bit set are being received and accepted.

When the subscriber is not in simulation mode (GEN/LPHD.Sim.stVal=false) the simulated SVs are ignored. The device keep on using
the "real" SV messages.

When the subscriber is in simulation mode (GEN/LPHD.Sim.stVal=true) the simulated SVs are used for operational purposes. The device
ignores the "real" SV messages after a first simulated one has been received. The corresponding LSVS.SimSt is set when the first
simulated message is received and only cleared when LPHD.Sim.stVal is set to false.

Once the device has received a simulated message for one of the subscribed SV messages, it will not process the real one until the
simulation mode of the device (LPHD.Sim.stVal) is set to false.

Ingeteam Power Technology S.A.


User Manual 550
PROTECTION DEVICES WITH SAMPLED VALUES 

33.6 TEST MODE FOR SAMPLED VALUES

The device implements the test mode for the SV reception.

If the device is in test mode for the SV, only the measurements received in the message of sampled values with the Quality bit of the
test mode active will be considered valid.

The device can be set to test mode for SV using the "SV test mode On" Setting, included in GEN/LPHD logical node.

Table 282. Test mode for sampled values setting

Data Setting Min. Max. Step Remarks Type


SVTestEna SV Test mode On NO/Yes enum

The signal "SV mode test Status" is activated when the device is in test mode for SV.

Table 283. Test mode for sampled values signal

Signal Data Attribute


SV mode test Status SVTestSt stVal

33.7 BEHAVIOUR WITH LOSS OF SYNCHRONIZATION

When a loss of synchronization is detected in the sampled value messages, the device can keep on protection or not depending on the
settings.

There is a setting that indicates how the device should operate when sampled values are not synchronized or when local
synchronization is used. It is included in the logical node GEN/LPHD.

❑ Lost SV synchronization. Indicates the behaviour of the device depending on the synchronization type received in the
sampled values messages. The available options are:
 Allow local. The device has to see the measures synchronized (Locally or globally) to consider them valid.
 Allow only global. The device has to see the measures with global synchronization to consider them valid.

Table 284. Behavior with loss of synchronization setting

Data Setting Min. Max. Step Remarks Type


Allow local (1)
SyncLostMod Lost SV synchronization enum
Allow only global (2)

A device subscribed to a single MU, even if the measures it receives are not synchronized, it treats them as measures with local
synchronization.

Ingeteam Power Technology S.A.


User Manual 551
Parque Tecnológico de Bizkaia • Edificio 110
48170 Zamudio, Bizkaia, Spain
Tel + 34 944 039 600
Fax +34 944 039 345
technology@ingeteam.com

Ingeteam Power Technology, S.A.


www.ingeteam.com