INGEPAC EF-ZT
User Manual
UME_INGEPAC_ZT_eng Rev. I (11/19)
1. GENERAL DESCRIPTION
Note 1: Available from firmware version 6.2.19.0 and ICD version 8.4.0.0
COM1
COM2
COM3
COM4
COM5
COM6
ETH1
ETH2
I/O 1
I/O 2
I/O 3
I/O 4
I/O 5
I/O 6
I/O 7
I/O 8
INGEPAC EF ZT MODEL INGEPAC EF- Z T - A - - -
MODEL
21, 85 (21), 85 (67/67Q), SOTF, 68LE, 68PS, 68FF, 67, 67N, 50/51, 50N/51N, 50G/51G, 67Q,
46BC, 37, 49, 59, 27, 59N, 47, 81O/u, 81R, 32, 25, 79, 79 (81), 74TC/CC, 50BF, Stub bus, Fault 0
Locator, Quality analysis
21, 85 (21), 85 (67/67Q), 52 ½, SOTF, 68LE, 68PS, 68FF, 67, 67N, 50/51, 50N/51N, 50G/51G,
67Q, 46BC, 37, 49, 59, 27, 59N, 47, 81O/u, 81R, 32, 25, 79, 74TC/CC, 50BF, Stub bus, Fault 1
Locator
HOUSING
1/2 chassis 19" 5U with configurable keyboard A
1/2 chassis 19" 5U with predefined keyboard Note 1 B
Chassis 19" 4U with configurable keyboard C
Chassis 19" 4U with predefined keyboard Note 1 D
TERMINALS
Pin type standard terminals A
Closed terminals Note 2 B
Closed terminals for analog inputs and pin type standard terminals for the rest C
- Reservado
- Reservado
- Reservado
It´s available an external accessory (FC2910) to allow BNC connection with coaxial cable in Irig-B and PPS input.
ZT1 model is specific for breaker and a half. The analog input 7 can be selected between Polarization current and Parallel line Neutral
current 2
Available analog inputs in models
Figure 3 Redundant power supply ½ 19” chassis Figure 4 Redundant power supply 19” chassis
❑ Ethernet. Up to two Ethernet port (IEC8802-3) with options of RJ45, GFO or LC. Redundant ports are optional.
❑ Serial. Up to 6 ports with options: RS232, RS485, GFO and PFO.
1.4 INTERCONNECTIONS
Interconnections depend on the modules selected. The connections associated with each of the modules are indicated, and thus the
diagram will depend on the modules installed.
1.4.1 CPU
Figure 7 3-contact relay and IRIG-B Figure 8 With BNC accessory
❑ Module 1 (Figure 11): Equipped with 11 digital inputs and 9 digital outputs grouped as follows:
Inputs: 4 independent + 3 with a common point + 4 with a common point.
Outputs: 5 independent + 3 with a common point + 1 switched (3 contacts).
❑ Module 2 (Figure 12): Equipped with 16 digital inputs and 16 digital outputs grouped as follows:
Inputs: 16 with a common point.
Outputs: 16 with a common point.
❑ Module 3 (Figure 13): Equipped with 16 digital inputs and 8 digital outputs grouped as follows:
Inputs: 16 with a common point.
Outputs: 8 independent.
❑ Module 5 (Figure 15): Equipped with 16 digital inputs and 8 analogue inputs grouped as follows:
Inputs: 16 with a common point.
Analogue: 8 independent. The analogue inputs have standard configuration, that could be changed among the
options: ±1mA, ±2.5mA, ±5mA, ±20mA, ±5V, ±10V
Standard configuration of analogue inputs
❑ Module 6 (Figure 16): Equipped with 16 digital inputs and 8 analogue inputs (4 isolated) grouped as follows:
Inputs: 16 with a common point.
Analogue: 8 independent, 4 of them are isolated and 4 have a common point. The analogue inputs have
standard configuration, that could be changed among the options: ±1mA, ±2.5mA, ±5mA, ±20mA, ±5V, ±10V
❑ Module 7 (Figure 17): Equipped with 8 digital inputs, 4 high breaking capacity outputs (hbco) and 4 digital outputs
grouped as follows:
Inputs: 8 independent.
Outputs: 8 independent: the 4 hbco outputs are 1 to 4 (pins 1 to 8) and the 4 standard outputs are 5 to 8 (pins
10 a 17).
❑ Module 8 (Figure 18): Equipped with 8 digital inputs, 8 digital outputs grouped as follows:
Inputs: 8 independent.
Outputs: 8 independent.
❑ Module 9 (Figure 19): Equipped with 8 digital inputs, 4 fast and high breaking capacity outputs (hbco) and 4 digital outputs
grouped as follows:
Inputs: 8 independent.
Outputs: 8 independent: the 4 fast and hbco outputs are 1 to 4 (pins 1 to 8) and the 4 standard outputs are 5
to 8 (pins 10 a 17).
Figure 19 Module 8 inputs, 4 outputs (fast and hbco) and 4 digital outputs
❑ Module 10 (Figure 18): Equipped with 8 digital inputs, 8 high breaking capacity outputs (hbco) grouped as follows:
Inputs: 8 independent.
Outputs: 8 hbco independent outputs..
❑ Module 11 (Figure 21): Equipped with 11 RTD inputs and 4 analogue outputs grouped as follows:
RTD Inputs: 11 RTD.
Analogue outputs: 4 independent. The analogue outputs can be configured with the options 0-1mA, 0-20mA,
4-20mA.
Figure 21 Module 11 RTD and 11 analog outputs
ZT0 ZT1
Figure 27 Topology 52 ½
2. HARDWARE
EF devices can be used as autonomous devices or as part of a protection and control system. The devices are implemented based on a
microprocessor and a DSP linked through shared RAM and communication lines.
The digital processing is done by a high accuracy 16 bit converter. Each signal reaches this converter after being conditioned, filtered and
amplified. A high frequency sampling is done at 144 samples per cycle (at 8640 Hz for 60 Hz systems or at 7200Hz for 50 Hz systems). This
sampling is transformed into 24 samples per cycle through a digital process before reaching the protection functions.
INGEPAC EF devices have non-volatile flash memory where the user settings, configurations and application are stored. This kind of
memory allows software updates and modifications without needing to manipulate the device hardware.
The rear section will vary in accordance with the options selected for the unit. The following figures show various possible
configurations.
❑ Supply terminals:
Wire section AWG 16 to 12 (1.5 to 2.5 mm2)
❑ I/O terminals:
Wire section AWG 16 to 12 (1.5 to 2.5 mm2)
❑ Graphic display
❑ 19 general use LEDs with interchangeable labels
❑ 1 2-colour unit status LED
❑ Numeric keypad
❑ 7 operational keys
❑ Ethernet communication
❑ Master USB communication
❑ Depending on the model, the following are available:
5 functional keys for selecting with interchangeable labels + 2 operational keys
3 fixed function keys + 2 operational keys.
❑ Graphic display
❑ 19 general use LEDs with interchangeable labels
❑ Operating range:
Direct: 88Vdc up to 300Vdc
Alternating: 85Vac up to 265Vac
Single power supply 24/48 Vdc models: 24Vdc-20% up to 48Vdc + 20%:
❑ Operating range:
Direct: 18Vdc up to 60Vdc
Redundant power supply 125Vdc models:
❑ Operating range:
❑ Operating range:
Direct: 18Vdc up to 60Vdc
Burden. Depends on the cards connected.
The characteristics of the 3-contact switched, common point signal outputs are:
High break contact outputs (h.b.c.o) and Fast + high break contact outputs (fast + h.b.c.o):
The characteristics of the independent contact outputs are the same except the activation times:
The wires for the I/O terminals should be copper with a section AWG 16 to 12 (1.5 to 2.5 mm2).
Rated V Characteristics
Not activated below 9 Vdc.
24Vdc Activated above 12 Vdc.
Maximum voltage 72 Vdc
Not activated below 32 Vdc.
48Vdc Activated above 37 Vdc.
Maximum voltage 72 Vdc
Not activated below 82 Vdc.
125Vdc They are activated above 87 Vdc.
Maximum voltage 300 Vdc
Not activated below 165 Vdc.
250Vdc Activated above 172 Vdc.
Maximum voltage 300 Vdc
The number of units that can be connected in parallel to a generator depends on the output current supply capacity; a typical value
is 70 mA, which would enable the connection of 6 units (although the length and the type of cable can also influence). The cable
must be shielded and twisted.
According to configuration, it synchronizes with frames B002 , B003 , B006 , B007 type . It also synchronizes with IEE1344.
Optionally, with an external adapter inputs IRIG- B and PPS can be BNC type. The connection must use a 50 Ω coaxial cable with a
male BNC connector.
❑ 100Ω Platinum
❑ 100Ω Nickel
❑ 120Ω Nickel
❑ 10Ω Copper
Measurement range: -50ºC to +250ºC
Accuracy: ±2ºC
2.4.7.1 Accuracy
❑ Current
Measurement range (0 to 1.2*Ir)
With Ir = 1: class 0.2 (0.2% of FS)
With Ir = 5: class 0.2 (0.2% of FS)
Protection range (0 to 200 A)
1 % over the measurement or 1 mA (greater)
❑ Voltage
Measurement range (0 to 1.2*Vr)
Accuracy 0.2% of FS
Protection range (0 to 200 Vac)
1 % over the measurement or 50 mV (greater)
❑ Dephase angle
Accuracy 1º
❑ Power
Measurement range (0 to 1.2*Ir*1.2*Vr)
With Ir = 1: class 0.5 (0,5% of Pr)
With Ir = 5: class 0.5 (0,5% of Pr)
❑ Frequency: ±10mHz
Time accuracy:
The drop-off percentages respect to the start setting in the protection units are:
❑ Overcurrent: 5%
❑ voltage: configurable from 1%
❑ Distance: 5%
❑ Differential: 5%
❑ Frequency: 0,05%
❑ Connector
ST
LC
❑ Wavelength: 1310nm
❑ Multimode glass optical fiber: 62.5 /125 µm and 50/125 µm
❑ Permitted attenuation
8 db with 50/125 µm
11 db with 62.5/125 µm
❑ Typical transmitter optical power: -20dBm to -14dBm
❑ Receiver optical sensitivity: -31dBm
❑ Baud rate: 100 Mb.
❑ Maximum distance: 2 km
❑ ST connector
❑ Wavelength: 820nm
❑ Multimode glass optical fiber: 62.5 /125 µm and 50/125 µm
❑ Permitted attenuation
9 db with 50/125 µm
11 db with 62.5/125 µm
❑ Typical transmitter optical power: -17dBm to -11dBm
❑ Receiver optical sensitivity: -28dBm
❑ Maximum distance: 2 km
Plastic optical fiber
For communications between devices, according to options available in each model, can be used:
FO single-mode (60km)
❑ Connector LC duplex or ST
❑ Wavelength: 1310nm, Laser
❑ Singlemode: 9/125 nm
❑ Permitted attenuation: 30db
❑ Typical transmitter optical power: -5dBm a 0dBm
❑ Receiver maximun optical power: 0dBm
❑ Maximum distance: 60km
❑ Minimum distance: 1km
FO single-mode (20-120km)
❑ Connector LC duplex or ST
❑ Wavelength: 1550nm, Laser
❑ Singlemode: 9/125 nm
❑ Permitted attenuation: 40db
❑ Typical transmitter optical power: 0dBm a 5dBm
❑ Receiver maximun optical power: 0dBm
❑ Maximum distance: 120km
❑ Minimum distance: 20km. It cannot be used below 20km.
❑ ST connector
❑ Wavelength: 850nm
❑ Multimode glass optical fiber: 50/125µm and 62.5/125 µm
❑ Permitted attenuation:
13db with 62,5/125 µm
9dB with 50/125 µm
❑ Typical transmitter optical power: -16dBm a -11dBm
❑ Receiver maximun optical power: -32dBm
❑ Maximum distance: 2km
Operating temperature:
2.5.1 Tropicalized
Printed circuit boards are lacquered to protect against corrosion and biological factors in humid environments. Depending on the
type of card different methods are used, dipping or selective varnishing and different varnishes. It is a treatment that deposits a
layer of low surface energy that repels moisture and some types of dirt. This procedure is made by demand, in the order.
2.6 TESTS
3. PROTECTION FUNCTIONS
Protections have measurement units per phase combination (AN, BN, CN, AB, BC, and CA), per characteristic (quadrilateral and Mho)
and per zone of operation (5 zones).
A distance protection measurement unit compares the voltage and current to calculate the impedance and the distance from the relay
to the fault to determine whether the fault is inside or outside the protected zone.
The protection has 5 zones of operation that can be configured independently with different characteristics. The overreaching zones
are useful as backup protection of the adjacent lines. The typical configuration uses three forward zones and one backwards.
❑ The first zone typically covers up to 80% of the protected line, causing instantaneous trips for faults in this zone.
❑ The second zone covers the rest of the line and part of the following one, usually up to 120% of the line. It provides trips or
signalling, depending on how it is programmed. The trips are not instantaneous, there is an additional programmable time for
giving another protection time to clear the fault if it is outside of its line.
❑ The third zone covers the rest of the overreach line and part of the next one. It provides trips or signalling, depending on how it is
programmed. The trips are not instantaneous, there is an additional programmable time available.
❑ The fourth zone covers the reverse line. It provides trips or signalling, depending on how it is programmed. The trips are not
instantaneous, there is an additional programmable time available.
❑ The fifth zone is used as backup and covers all the zones. It provides trips or signalling, depending on how it is programmed. The
trips are not instantaneous, there is an additional programmable time available.
The distance unit is supervised by the following functions:
The distance units for ground faults correct the current measured in each phase with the zero sequence using different compensation
factors for each zone.
In parallel lines, the distance units for ground faults correct the current measured in each phase with the neutral current using a mutual
compensation factor for each zone.
There are independent settings for each of the five zones (Table 2 and Table 3). Zone 1 has inductive tilting settings which do not exist
in the other zones (Table 2).
The reach of zone 1 can vary depending on the "Zone 1 extension" function.
❑ Nodes:
Zone 1: PROT/PDIS1
Zone 2: PROT/ZPDIS2
Zone 3: PROT/ZPDIS3
Zone 4: PROT/ZPDIS4
Zone 5: PROT/ZPDIS5
There are 6 settings tables.
The settings used in these functions (Table 2 for zone 1 and Table 3 for the other zones) are as follows:
❑ Directional Mode. Indicates the direction of the characteristics. The directional supervision indicates the direction.
Non directional (0). The unit acts as non-directional, in other words, directional supervision is disabled. In the
quadrilateral characteristic it operates forward and backwards, and in the Mho characteristic it operates forward
without being limited by directional supervision.
Forward trip (1). It only operates with forward faults.
Reverse trip (2). It only operates with backwards faults.
Reverse start (3). It only operates with backwards faults. It does not generate trips, only starts.
Forward start (4). It only operates with forward faults. It does not generate trips, only starts. This option is not found in
settings for zone 1.
❑ Characteristic angle (º). Indicates the characteristic angle.
❑ General trip. Indicates if this unit produces general trip or not. For additional details, see the section corresponding to the
recloser (3.12.6).
❑ Reclose Permission. Indicates whether each trip type can be reclosed or not, in accordance with the recloser's closing cycle
(See 6.2.3).
❑ Enable Events record. Allows the generation of protection events associated to the function. If set to “NO”, the function’s
protection events are not generated. If set to “YES”, the function’s specific mask is contemplated.
❑ Phase Enabled (Ph). Indicates whether or not the phase-phase characteristic is enabled.
❑ Phase Characteristic (Ph). Selects the phase-phase characteristic:
Mho (0). Only the mho characteristic is enabled.
Quadrilateral (1). Only the quadrilateral characteristic is enabled.
Mho and Quad (2). Both characteristics are enabled.
❑ Phase Time (ms) (Ph). Indicates the time during which the conditions for the tripping must be met.
❑ Mho Reach (Ph). Indicates the reach of the mho phase-phase characteristic.
❑ Resistive Reach (Ph). Indicates the resistive reach of the quadrilateral phase-phase characteristic.
❑ X Reach Forward (Ph). Indicates the inductive reach forward of the quadrilateral phase-phase characteristic. If the
"Directional Mode" is set to reverse, the setting “X Reach Reverse (Ph)”is used.
❑ X Reach Reverse (Ph). Indicates the inductive reach backwards of the quadrilateral phase-phase characteristic. If the
"Directional Mode" is set to forward, the setting “X Reach Forward (Ph)”is used.
❑ R Blinder Angle (Ph). Indicates the slope angle of the resistive reach of the quadrilateral phase-phase characteristic.
❑ Block phase units (Ph). Selects the signal which, when active, blocks the phase-phase units.
❑ Enabled (Gnd). Indicates whether the phase-ground characteristic is enabled or not.
❑ Gnd Characteristic (Gnd). Selects the phase-ground characteristic:
Mho (0). Only the mho characteristic is enabled.
Quadrilateral (1). Only the quadrilateral characteristic is enabled.
Mho and Quad (2). Both characteristics are enabled.
❑ Phase-ground time (ms). Indicates the time during which the conditions for the tripping must be met.
❑ Kn Module. Indicates the zero sequence compensation factor module.
❑ Kn Angle (º). Indicates the zero sequence compensation factor angle.
❑ Km Module. Indicates the mutual compensation factor module of the parallel lines.
❑ Km Angle (º). Indicates the parallel lines mutual compensation factor angle.
❑ Mho Reach (Gnd). Indicates the reach of the mho phase-ground characteristic.
❑ Resistive Reach (Gnd). Indicates the resistive reach of the quadrilateral phase-ground characteristic.
❑ X Reach Forward (Gnd). Indicates the inductive forward reach of the quadrilateral phase-ground characteristic. If the
"Directional Mode" is set to reverse, the setting “X Reach Reverse (Gnd)”is used.
❑ X Reach Reverse (Gnd). Indicates the inductive backwards reach of the quadrilateral phase-ground characteristic. If the
"Directional Mode" is set to forward, the setting “X Reach Forward (Gnd)”is used.
❑ R Blinder Angle (Gnd). Indicates the slope angle of the resistive reach of the quadrilateral phase-ground characteristic.
❑ Tilt Angle Gnd (º). Indicates the tilting angle of the resistive reach of the quadrilateral phase-ground characteristic. This
setting is only available for zone 1.
❑ Tilt Type (Gnd). Indicates the tilting type selected for the quadrilateral phase-ground characteristic. This setting is available
for zone 1.
Disabled (0). Tilting is disabled.
Time delayed (1). Enabled for the time selected, after fault detected.
Continuous (2). Continuously enabled.
❑ Tilt Time Gnd (ms). Indicates the time during which inductive tilting of the phase-ground quadrilateral characteristic is
applied. This setting is available for zone 1.
❑ Quad. Type (Gnd). Indicates the quadrilateral unit polarization of the quadrilateral phase-ground characteristic.
I0 (0). Zero sequence polarization.
I2 (1). Negative sequence polarization.
Max (I0, I2) (2). Polarization by the greater of the two (zero sequence and negative sequence).
❑ Block Gnd units. Selects the signal which, when active, blocks the phase-ground units.
❑ Block zone. Selects the signal which, when active, blocks the zone, in other words, the phase-ground and phase-phase
units.
❑ Timing type. Allows you to select how each zone's trip is delayed after the unit picks up (only zones 2, 3, 4 and 5). The
various modes are described in the section entitled "Timing Type".
❑ Ph-Ph Threshold (A)1. Each phase combination current must be above this value, to allow the corresponding phase-phase
distance unit of the zone. If it is set to zero, it is always allowed.
❑ Ph-Gnd Threshold (A)1. The phase current must be above this value, to allow the corresponding phase-gnd unit of the
distance zones selected as forward. If it is set to zero, it is always allowed.
❑ 3I0 Threshold (A) 1. The neutral current (3I0) must be above this value, to allow the phase-gnd distance unit of the zone. If
it is set to zero, it is always allowed.
1
Available since firmware version 6.2.19.3 and ICD 8.6.0.0
Start Mho Zx Y. Pickup by MHO, where x is the zone. Y indicates the distance unit (AN, BN, CN, AB, BC or CA) which has
started up It is independent for each zone.
Trip Mho Zx Y. Trip by MHO, where x is the zone. Y indicates the distance unit (AN, BN, CN, AB, BC or CA) which has
tripped. It is independent for each zone.
Start Quad Zx Y. Pickup by QUAD, where x is the zone. Y indicates the distance unit (AN, BN, CN, AB, BC or CA) which
has started up It is independent for each zone.
Trip Quad Zx Y. Trip by QUAD, where x is the zone. Y indicates the distance unit (AN, BN, CN, AB, BC or CA) which has
tripped. It is independent for each zone.
Start Zx single-phase. Single phase pickup by QUAD and/or Mho, where x is the zone. It is independent for each zone.
Start Zx Phase-phase. Two phase pickup by QUAD and/or Mho, where x is the zone. It is independent for each zone.
Trip Zx single-phase. Single phase trip by QUAD and/or Mho, where x is the zone. It is independent for each zone.
Trip Zx Phase-phase. Two phase trip by QUAD and/or Mho, where x is the zone. It is independent for each zone.
Zx start. Pickup by QUAD and/or Mho, where x is the zone. It is independent for each zone.
Zx trip. Trip by QUAD and/or Mho trip, where x is the zone. It is independent for each zone.
Mho zone x ph-gnd Status. Indicates the Mho phase-ground function’s status, where x is the zone. It is active when
enabled and not blocked. It is independent for each zone.
Mho zone x ph-ph Status. Indicates the Mho phase-phase function’s status, where x is the zone. It is active when
enabled and not blocked. It is independent for each zone.
Quad zone x ph-gnd Status. Indicates the Quad phase-ground function’s status, where x is the zone. It is active when
enabled and not blocked. It is independent for each zone.
Quad zone x ph-ph Status. Indicates the Quad phase-phase function’s status, where x is the zone. It is active when
enabled and not blocked. It is independent for each zone.
3.1.1 Mho
The Mho characteristic is used with a cosine type phase comparator with Sop and Spol input phasors.
Hence, the signals used in each phase of the Mho characteristic are shown in Table 5. The operation zone must fulfil:
❑ ZxGF: Phase-ground reach impedance, where x is the zone (one setting per zone). Set in ohms.
❑ ZxF: Phase-phase reach impedance, where x is the zone (one setting per zone). Set in ohms.
❑ ZxAº: Line characteristic angle, where x is the zone (one setting per zone). Set in degrees.
❑ Knx: Zero compensation constant, where x is the zone (one setting per zone).
1 zl0
K n = ( − 1)
3 zl1
❑ Kmx: Mutual compensation constant (double lines) where x is the zone (one setting per zone).
𝑍𝑚0
𝐾𝑚 =
3 · zl1
Va1 1
π
(Vb1) = (e1j·240180 ) · V1
π
Vc1 e1j·120180
❑ Vab1, Vbc1, Vca1: Positive sequence voltages referred to phase - phase voltages. The value will be determined by the
supervision of the memorization voltage (See section 3.3.3).
Equation 2
𝜋
𝑉𝑎𝑏1 𝑒1𝑗·30180
𝜋
( 𝑉𝑏𝑐1 ) = √3 (𝑒1𝑗·270180 ) 𝑉1
𝑉𝑐𝑎1 𝜋
𝑒1𝑗·150180
The voltages and currents used correspond to the type of fault being analysed; for example, for an A phase to ground fault, the
corresponding phasors will be Ia and Va, for an A and B phase - phase fault, they will be Iab and Vab.
The phase current used for single phase faults correspond to the current measured in each phase compensated with the zero
sequence. Double lines are also compensated with neutral current (mutual compensation factor).
Important: To operate, the phase current analysed has to be greater than 10% of the rated current when the rated current is 1A
and greater than 5% of the rated current when the rated current is 5A.
All of the Mho units are supervised by a reactance unit (Inductive X limit). In this way, the tendency for the Mho units to overreach
is prevented due to the influence of the load beforehand.
Zero compensation for double lines (km) is only applicable if the neutral current in the parallel line (IN2) is less than 1.35 times the
neutral current of the protected line (3I0).
If a pole is opened (from the trip), the positive sequence voltage will be calculated without taking into account the open pole's
phase voltage to avoid the distortion from discharging the line capacitors on this open phase. In other words, normally (with 3
poles closed) V1=1/3·(Va+a·Vb+a²·Vc)
Figure 39 shows the logic diagram of the Mho characteristic for units AN and AB forward.
❑ Pole A open, Pole B open, Pole C open: Activated when the pole "x" is open. They are outputs of the function open pole
detector.
❑ Phase A open (I<), Phase B open (I<), Phase C open (I<): Indicates that the phase current is below the open pole detector
level. They are outputs of the function open pole detector.
❑ Perm. I>ZA Forward. It allows the protection unit AN for the zones configured as forward. It is output of the “MHO and
QUAD unit supervision”.
❑ Perm. I> ZAB Forward. The same as precious for phase AB.
❑ Selector AN. It is the signal “AN/BCN Selector” of the "Phase selector".
❑ Selector AB. It is the signal “CN/ABN Selector” of the "Phase selector".
❑ Fuse failure start. Blocked by the fuse failure start signal.
❑ Power swing blocking. Blocked by the Power swing detector.
❑ Open Pole. Indicates, there´s any pole open. It is output of the function open pole detector.
❑ Load Encroachment. Blocked by the load Encroachment signal.
3.1.2 Quadrilateral
The Quadrilateral characteristic is used by making two comparisons for each zone and for each single phase component:
❑ The resistive component of each impedance with the corresponding "Resistive Reach" setting.
❑ The inductive component of each impedance with the corresponding "X Reach forward" or "X Reach reverse" (depending
on the sign and on the "Directional Mode" setting).
Vpol
R = Re ( )
Ieq
For single phase units in zone 1, the inductive component is calculated as follows:
̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅
Im[Vpol · (Ipol · 1∠Z1BASCA˚)]
X = Im(ZL1)Ÿ ·
̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅
Im [ZL1 · (Ieq · (Ipol · 1∠Z1BASCA˚))]
Where:
The intervention of the tilt angle is regulated by two settings (only zone 1 and single phase units):
❑ Tilt type (Gnd): If defined as "Disabled", this angle's value is always 0. If defined as "Time delayed", this angle maintains its
setting value during the time indicated in the setting "Tilt time Gnd (ms)". If defined as "Continuous" it always keeps its
setting value.
❑ Tilt time Gnd (ms): Time, in ms, for applying the tilt angle after the fault detection, only if the setting "Tilt type (Gnd)" is set
as "Time delayed".
Important: To operate, the phase current analysed must be greater than 10% of the rated current.
The signals used in each phase of the Quadrilateral characteristic are shown in Table 6. The operation zone must be such that these
two components are less than the set reach.
Where:
❑ Knx: Zero compensation constant, where x is the zone (one setting per zone). Same setting as for Mho.
❑ Kmx: Mutual compensation constant (double lines), where x is the zone (one setting per zone). Same setting as for Mho.
❑ Ia, Ib, Ic: Phase currents.
❑ Iab, Ibc, Ica: Phase - phase currents (Iab = Ia - Ib, Ibc = Ib - Ic, Ica = Ic - Ia).
❑ 3 I0: Calculated neutral current.
❑ IN2: Measured neutral current of the parallel line. Only for double lines.
❑ Va, Vb, Vc: Phase voltages.
❑ Vab, Vbc, Vca: Phase - phase Voltages.
❑ I2: Negative sequence of the current calculated using the phase currents.
In the case of single phases faults, the polarization current (Ipol) for each phase is chosen according to the "Quad. type (Gnd)"
setting. There are three possible options: zero sequence, negative sequence, and the maximum of both.
In the case of the phase - phase ones, the polarization current applied is always the negative sequence current, unless the value of
the negative sequence is less than the 25%2 of the positive sequence or less than the 5% of the rated current or the current of the
three phases is greater than three times the rated current. In that case, the current between the two phases is used.
The zero compensation and the memory are applied following the same conditions as for the Mho characteristic.
The Figure 41 shows the logic diagram of the quadrilateral characteristic for units AN and AB forward.
❑ Pole A open, Pole B open, Pole C open: Activated when the pole "x" is open. They are outputs of the function open pole
detector.
❑ Phase A open (I<), Phase B open (I<), Phase C open (I<): Indicates that the phase current is below the open pole detector
level. They are outputs of the function open pole detector.
❑ Perm. I>ZA Forward. It allows the protection unit AN for the zones configured as forward. It is output of the “MHO and
QUAD unit supervision”.
❑ Perm. I> ZAB Forward. The same as precious for phase AB.
❑ Selector AN. It is the signal “AN/BCN Selector” of the "Phase selector".
❑ Selector AB. It is the signal “CN/ABN Selector” of the "Phase selector".
❑ Perm. dir IA Forward. Forward directional permission for phase A. Function "Directional supervision".
❑ Perm. dir IAB Forward. The same as precious for phase AB.
❑ Fuse failure start. Blocked by the fuse failure start signal.
❑ Power swing blocking. Blocked by the Power swing detector.
❑ Open Pole. Indicates, there´s any pole open. It is output of the function open pole detector.
❑ Load Encroachment. Blocked by the Load Encroachment signal.
2
Available from DSP firmware version 4.1. Upto this version the limit was 10%.
Forward Reverse
Non directional
❑ Not delayed. This means that different starts in different phases do not delay the trip. For example, if a start takes place in
phase A and the start condition disappears in this phase, but phase B starts, timing continues. Hence, the trip is not
delayed.
❑ Independent. Each phase has an independent timer. For example, if a start takes place in phase A and the start condition
disappears in this phase, but phase B starts, timing for tripping starts again.
In zone 1 (not timed), the "Independent" mode is always applied.
The condition for activating a unit (prior to the trip) is activated if there is a startup in any of the units (this is the case in "Not
delayed" mode) or in the specific unit (this is the case in the "Independent" mode) and the corresponding timing is fulfilled.
In the case of the "Independent" mode, once the corresponding condition for activating the unit has been activated, a seal is
applied so that the condition is not deactivated while there is an overcurrent (only in zones 2, 3, 4 and 5).
In order for a unit to trip, besides the unit having to be activated, there must be a closed phase or V1>80%Vrated for 1/4 cycle.
Figure 42 shows the logic diagram for trip mode without a delay between phases.
❑ Pole A open, Pole B open, Pole C open: Activated when the pole "x" is open. They are outputs of the function open pole
detector.
❑ Phase A open (I<), Phase B open (I<), Phase C open (I<): Indicates that the phase current is below the open pole detector
level. They are outputs of the function open pole detector.
❑ Selector AN/BCN. Enables AN and BC units and blocks the other units. It is the signal “AN/BCN Selector” of the "Phase
selector".
❑ Selector BN/CAN. Enables BN and CA units and blocks the other units. It is the signal “BN/CAN Selector” of the "Phase
selector".
❑ Selector CN/ABN. Enables CN and AB units and blocks the other units. It is the signal “CN/ABN Selector” of the "Phase
selector".
❑ Zone n start AN. Indicated that the AN unit of the zone has started.
❑ Zone n start BN. The same as precious for phase BN.
❑ Zone n start CN. The same as precious for phase CN.
❑ Zone n start AB. The same as precious for phase AB.
❑ Zone n start BC. The same as precious for phase BC.
❑ Zone n start CA. The same as precious for phase CA.
❑ IA>IA Forward. It is the signal "Perm. IA Forward" of the function Overcurrent supervision.
❑ IB>IB Forward. The same as precious for phase B.
❑ IC>IC Forward. The same as precious for phase C.
❑ IAB>IAB Forward. The same as precious for phase AB.
❑ IBC>IBC Forward. The same as precious for phase BC.
❑ ICA>ICA Forward. The same as precious for phases CA.
Figure 44 shows the logic diagram for the independent trip mode for zone 1 in single phase units.
Figure 43 shows the logic diagram for the independent trip mode for zone 1 in two phase units.
It is applied to the mho and quadrilateral characteristics, there is an independent compensation factor for ground faults and for
phase - phase faults.
❑ Node: PROT/RZEX1
❑ Settings and logical inputs. There are 6 settings tables. For details, see Table 7.
❑ Commands:
“DOrdBlk”: Blocks and unblocks the function. Only acts when the function is enabled.
❑ Outputs: Table 8 shows the function's output data.
Zone 1 Extension: Indicates that the zone extension is activated.
Zone 1 Extension Status: Indicates the function’s status. It is active when enabled and not blocked.
Setting
ENABLED = YES
DIGITAL INPUT
Blocking input
DIGITAL SIGNAL
Recloser in standby WORKING SETTING
Working Z1GF=Z1GF·Gnd extension ratio
DIGITAL SIGNAL Working Z1F =Z1F·Ph-Ph extension ratio
Reclosing 1 in progress
WORKING SETTING
DIGITAL SIGNAL Working Z1GF=Z1GF
Safety time 1st reclosing Working Z1F =Z1F
DIGITAL SIGNAL
Recloser Blocked
The high speed zone 1 can only be active if zone 1 is programmed forward and enabled.
The high speed zone 4 will only be active if zone 4 is programmed backwards and enabled.
The high speed zone is made by including an internal zone in zone 1 and zone 4 such as that |X|<80%ZxF, |R|<20%ZxF, where ZxF is
the reach of the corresponding zone.
❑ Zone 1 enabled: Indicates whether the high speed zone 1 is enabled or not.
❑ Zone 4 enabled: indicates whether the high speed zone 4 is enabled or not.
❑ Zone 1 Blocking input: Selects the signal which, when active, blocks the high speed zone 1.
❑ Zone 4 Blocking input: Selects the signal which, when active, blocks the high speed zone 4.
❑ Enable Events record. Allows the generation of protection events associated to the function. If set to “NO”, the function’s
protection events are not generated. If set to “YES”, the function’s specific mask is contemplated.
❑ Node: PROT/PHSZ1
❑ Settings and logical inputs. There are 6 settings tables. For details, see Table 9.
❑ Outputs: Table 10 shows the function's output data.
High speed zone 1: Indicates whether or not the high speed zone 1 is enabled and not blocked.
High speed zone 4: Indicates whether or not the high speed zone 4 is enabled and not blocked.
Figure 46 shows the Mho and Quad characteristics of the high speed zone 1.
Figure 47 shows the functional logic diagram of the high speed operation Mho characteristic.
The input signals of this function are the indicated in the mho and quadrilateral units.
Zero sequence current greater than 5% of Irated (0.25A for Irated=5A and 0.05A for Irated=1A) and the percentage must be greater
than the 10% of the maximum phase current.
Negative sequence current greater than 5% of Irated (0.25A for Irated=5A and 0.05A for Irated=1A) and the percentage must be
greater than the 10% of the positive sequence.
When the fault detector is disabled, all the phase-phase units are enabled.
When the fault detector is enabled, the angle is analysed to determinate the faulted phases:
Where:
If (1) and (2) are fulfilled, the fault is to ground (single phase or phase - phase). In this case, the angular selector becomes involved.
If a single phase / two phase fault to ground is detected, only the units involved will be enabled. If it is a CN/ABN, units CN and AB
are enabled and the others are blocked.
UNDETERMINED IDENTIFICATION
If (1) is fulfilled but (2) is not, all of the units will be enabled, since the relay cannot determine what type of fault is processed.
In the 67NQ teleprotection scheme, single pole trips are allowed. In case of single phase or two phase to ground faults, another
selector is used to determinate the fault type.
Where:
Figure 50 AN and BCN fault identifier Figure 51 BN and CAN fault identifier Figure 52 CN and ABN fault identifier
All of the units will be enabled if there is an open pole, in other words, if a single-pole opening has occurred.
❑ Node: PROT/DISPTRC1
❑ Outputs: Table 12 shows the output data.
AN/BCN Selector: Enables the AN and BC units and blocks the others.
BN/CAN Selector: Enables the BN and CA units and blocks the others.
3
Available from firmware version 6.0.8.0 and ICD version 8.1.0.4
CN/ABN Selector: Enables the CN and AB units and blocks the others.
Unknown Fault: Enables all of the units.
ABC Fault: Enables units AB, BC and CA. This is only indicated if there has been a simultaneous fault in AB, BC and CA.
Phase - Phase Fault: Enables the phase-phase units.
Ground fault: It is activated when there is a ground fault.
AN Selector3: Enables the AN unit and blocks the others.
BN Selector3: Enables the BN unit and blocks the others.
CN Selector3: Enables the CN unit and blocks the others.
AB Selector3: Enables the AB unit and blocks the others.
BC Selector3: Enables the BC unit and blocks the others.
CA Selector3: Enables the CA unit and blocks the others.
❑ Pole A open, Pole B open, Pole C open: Activated when the pole "x" is open. They are outputs of the function open pole
detector.
If any of the poles is open, the phase selector is not taken into account. In this case, the loops containing the open pole are blocked.
E.g.: If the open pole is A, loops AB, CA and AN are blocked. The trip will be three-pole.
In the case of a three-phase opening, if only the breaker status generic input is programmed (not by pole); the phase selector
continues being used. In other words, only the phase selector is disabled in the case of a single-phase opening. In this case, the fault
type is defined by the active distance units. If any of the phase-phase distance units is activated, a phase-phase fault will be
indicated.
It is activated when:
❑ The difference between the actual measurement of the current's positive sequence (I1) and the measurement two cycles
beforehand exceeds the 10% of the rated current and one of the following conditions is fulfilled:
The difference between the current measurement of the negative sequence of the current (I2) and the
measurement two cycles before exceeds 4% of the rated current.
The difference between the current measurement of the zero sequence of the current (I0) and the
measurement two cycles before exceeds 4% of the rated current.
The positive sequence of the current (I1) increases by more than 25% compared to two cycles before.
When one of these thresholds is exceeded or if the phase selector identifies a fault which is not three-phase, the fault detector is
activated. The fault detector stays active for 30ms after the previous situation disappears. If a distance unit or an overcurrent
startup occurs while the fault detector is active, the fault detector will stay active for 30 ms after the trip disappears.
❑ Node: PROT/DISPTRC1
❑ Outputs. Table 13 shows the output data.
Fault detection: Indicates a fault has been detected.
Table 13 Fault Detector Outputs.
❑ 2 Phase Fault. It is the signal "Phase - Phase Fault" of the Phase selector.
❑ Ground fault. It is the signal "Ground fault" of the Phase selector.
❑ Start signals. Indicates that any of the started units generate the general start signal.
Figure 54 Fault Detector's Logic Diagram
Single-Phase Units. The blocking conditions for phase-ground units are as follows:
❑ If the phase identifier does not detect the fault in the corresponding loop.
❑ Pole A open, Pole B open, Pole C open: Activated when the pole "x" is open. They are outputs of the function open pole
detector.
❑ Phase A open (I<), Phase B open (I<), Phase C open (I<): Indicates that the phase current is below the open pole detector
level. They are outputs of the function open pole detector.
❑ Fuse failure start. Blocked by the fuse failure start signal.
❑ Load Encroachment. Blocked by the Load Encroachment signal.
Phase-phase units. The blocking conditions for phase-phase units are as follows:
❑ If the phase selector does not detect the fault in the corresponding loop.
❑ No current is detected in one of the unit phases. If there is no current in A, neither unit AB nor CA unit are activated
("detection logic for open pole by current").
❑ Iab, Ibc, Ica must be 10% greater than Irated for In=1A and 5% for In=5A, even if the overcurrent supervision is not been
used.
❑ If the power swing function is activated and if it is programmed for this.
❑ If the fuse failure function is activated.
❑ If the polarization voltage is less than 2V. Supervision is in directional supervision mode.
❑ If phase-phase unit overcurrent supervision has been enabled. If the phase-phase overcurrent of the direction
corresponding to the zone is not exceeded. The threshold must be exceeded in each phase of the ones involved in the unit
(e.g. in unit AB, currents of phases A and B and AB.
❑ Enable Events record. Allows the generation of protection events associated to the function. If set to “NO”, the function’s
protection events are not generated. If set to “YES”, the function’s specific mask is contemplated.
There are settings and outputs.
❑ Node: PROT/DISPTRC1
❑ Settings and logical inputs. There are 6 settings tables. For details, see Table 14.
❑ Outputs: Table 15 shows the output data.
Permission I>ZA Forward. Indicates that it allows the AN distance unit to operate for zones programmed forward.
I>ZB Forward Permission. Indicates that it allows the BN distance unit to operate for zones programmed forward.
I>ZC Forward Permission. Indicates that it allows the CN distance unit to operate for zones programmed forward.
I>ZAB Forward Permission. Indicates that it allows the AB distance unit to operate for zones programmed forward.
I>ZBC Forward Permission. Indicates that it allows the BC distance unit to operate for zones programmed forward.
I>ZCA Forward Permission. Indicates that it allows the CA distance unit to operate for zones programmed forward.
I>ZA Reverse Permission. Indicates that it allows the AN distance unit to operate for zones programmed backwards.
I>ZB Reverse Permission. Indicates that it allows the BN distance unit to act. For zones programmed backwards.
I>ZC Reverse Permission. Indicates that it allows the CN distance unit to operate for zones programmed backwards.
I>ZAB Reverse Permission. Indicates that it allows the AB distance unit to operate for zones programmed backwards.
I>ZBC Reverse Permission. Indicates that it allows the BC distance unit to operate for zones programmed backwards.
I>ZCA Reverse Permission. Indicates that it allows the CA distance unit to operate for zones programmed backwards.
Table 14 MHO and QUAD Unit Supervision Settings
Single-Phase Units:
Supervises the phase-ground units of the distance characteristics (mho and quadrilateral).
It is used to measure each phase measurement and neutral measurement (In or 3I0 as selected).
It compares the current of each phase with the threshold established as the setting, activating when it is exceed and
deactivating when it is lower than 95%. The analysis is made for each phase independently, generating an output per phase,
which allows the distance units of each phase to operate if the current measured is greater than the threshold and disables it
otherwise.
To have permission in a phase, both the measurements of the phase and of the neutral (3I0) must exceed their corresponding
thresholds.
❑ Node: PROT/GRZOS1
❑ Settings and logical inputs. There are 6 settings tables. For details, see Table 16.
❑ Commands:
“DOrdBlk”: Blocking and unblocking of single-phase overcurrent supervision. Only acts when the function is enabled.
❑ Outputs: Table 17 shows the function's output data.
IA Forwards Permission. Indicates that the overcurrent supervision allows the AN distance unit to act (for zones
programmed forward).
IB Forwards Permission. Indicates that the overcurrent supervision allows the BN distance unit to act (for zones
programmed forward).
IC Forwards Permission. Indicates that the overcurrent supervision allows the CN distance unit to act (for zones
programmed forward).
IA Reverse Permission. Indicates that the overcurrent supervision allows the AN distance unit to act (for zones
programmed backwards).
IB Reverse Permission. Indicates that the overcurrent supervision allows the BN distance unit to act (for zones
programmed backwards).
IC Reverse Permission. Indicates that the overcurrent supervision allows the CN distance unit to act (for zones
programmed backwards).
Gnd supervision status. Indicates that phase-ground overcurrent supervision is activated and not blocked.
Phase-Phase Units:
Supervises the phase-phase units of the distance characteristics (mho and quadrilateral).
It compares the phase - phase current of each two phases and the current of each phase with the threshold established as the
setting, activating when it exceeds it and deactivating when it is lower than 95%. The analysis is made for each phase
combination independently, generating an output per combination, which allows the distance units of each combination to act
if the current measured is greater than the threshold and disables it otherwise.
The threshold must be exceeded for the phase - phase current and for each phase involved in the phase - phase current.
❑ Node: PROT/PHRZOS1
❑ Settings and logical inputs. There are 6 settings tables. For details, see Table 18.
❑ Commands:
“DOrdBlk”: Blocking and unblocking of phase-phase overcurrent supervision. Only acts when the function is enabled.
❑ Outputs: Table 19 shows the function's output data.
IAB Forwards Permission. Indicates that the overcurrent supervision allows the AB distance unit to act (for zones
programmed forward).
IBC Forwards Permission. Indicates that the overcurrent supervision allows the BC distance unit to act (for zones
programmed forward).
ICA Forwards Permission. Indicates that the overcurrent supervision allows the CA distance unit to act (for zones
programmed forward).
IAB Reverse Permission. Indicates that the overcurrent supervision allows the AB distance unit to act (for zones
programmed backwards).
IBC Reverse Permission. Indicates that the overcurrent supervision allows the BC distance unit to act (for zones
programmed backwards).
ICA Reverse Permission. Indicates that the overcurrent supervision allows the CA distance unit to act (for zones
programmed backwards).
Ph-Ph supervision status. Indicates that phase-phase overcurrent supervision is activated and not blocked.
Functioning is conditioned by polarization memory supervision. Hence, if the logic indicates that the memorised voltage must
be used, this is used during the set time. See section 3.3.3.
Table 20 shows the comparisons for determining the direction of the different types of faults:
Unit S1 S2 Calculus
Ia ZGDIRA set Va1 mem
AN |Angle(S1)-Angle(S2)| < ZGAMPA/2
& I2_A ZGDIRA set
Ib ZGDIRA set Vb1 mem
BN |Angle(S1)-Angle(S2)| < ZGAMPA/2
& I2_B ZGDIRA set
Ic ZGDIRA set Vc1 mem
CN |Angle(S1)-Angle(S2)| < ZGAMPA/2
& I2_C ZGDIRA set
AB Iab ZDIRA set Vab1 mem |Angle(S1)-Angle(S2)| < ZAMPA/2
BC Ibc ZDIRA set Vbc1 mem |Angle(S1)-Angle(S2)| < ZAMPA/2
CA Ica ZDIRA set Vca1 mem |Angle(S1)-Angle(S2)| < ZAMPA/2
Where:
The direction is determined by the comparison between the positive sequence voltage and current (See Figure 57).
There is a 5º zone between the non-trip zone and the trip zone in which the current directional status is maintained.
The torque angle is the directional setting angle with the setting amplitude.
In the case of an open pole, only phase current polarizations are used, not by I2.
The maximum torque angle will correspond to the directional angle set with an adjustable margin.
❑ Ph-Ph angle (º). Indicates the directional angle for phase-phase supervision.
❑ Ph-Ph amplitude (º). Indicates the angle that covers the trip zone for phase-phase supervision.
❑ Gnd angle (º). Indicates the directional angle for single-phase supervision.
❑ Gnd amplitude (º). Indicates the angle that covers the trip zone for single-phase supervision.
❑ Enable Events record. Allows the generation of protection events associated to the function. If set to “NO”, the function’s
protection events are not generated. If set to “YES”, the function’s specific mask is contemplated.
Figure 58 shows the supervision logic diagrams for single-phase and phase-phase directional supervision.
❑ Open Pole. Indicates, there´s any pole open. It is output of the function open pole detector.
❑ Node: PROT/RDIR1
❑ Settings and logical inputs. There are 6 settings tables. For details, see Table 21.
❑ Outputs: Table 22 shows the function's output data.
Permission dir IA Forward. Indicates that directional supervision allows distance unit AN to act (for zones programmed
forward).
Permission dir IB Forward. Indicates that directional supervision allows the distance unit BN to act (for zones
programmed forward).
Permission dir IC Forward. Indicates that directional supervision allows the distance unit CN to act (for zones
programmed forward).
Permission dir IAB Forward. Indicates that directional supervision allows the distance unit AB to act (for zones
programmed forward).
Permission dir IBC Forward. Indicates that directional supervision allows the distance unit BC to act (for zones
programmed forward).
Permission dir ICA Forward. Indicates that directional supervision allows the distance unit CA to act (for zones
programmed forward).
Permission dir IA Reverse. Indicates that directional supervision allows the distance unit AN to act (for zones
programmed backwards).
Permission dir IB Reverse. Indicates that directional supervision allows the distance unit BN to act (for zones
programmed backwards).
Permission dir IC Reverse. Indicates that directional supervision allows the distance unit CN to act (for zones
programmed backwards).
Permission dir IAB Reverse. Indicates that directional supervision allows the distance unit AB to act (for zones
programmed backwards).
Permission dir IBC Reverse. Indicates that directional supervision allows the distance unit BC to act (for zones
programmed backwards).
Permission dir ICA Reverse. Indicates that directional supervision allows the distance unit CA to act (for zones
programmed backwards).
In order to determine when the voltages must be filtered, two conditions must be fulfilled: A fault has occurred and there is a
risk of overreaching (for which the SIR estimation will be used).
To estimate the SIR, the lowest value obtained from amongst all the units indicated by the phase identifier will be used. They
are compared with a threshold which will depend on the CVT type (which can be selected through the settings). If the SIR value
calculated is greater than the threshold specified and a fault is detected using the fault detector, then the filtered voltages will
be used. Otherwise, the voltages will be calculated as usual.
The filtered voltages are only used in zone 1 of the distance functions (unit 21). A digital bandpass filter is used.
❑ Node: PROT/RCVT1
❑ Settings and logical inputs. There are 6 settings tables. For details, see Table 23.
❑ Commands:
“DOrdBlk”: Function blocking and unblocking. Only acts when the function is enabled.
❑ Outputs: See Table 24.
“CVT enabled”: Indicates that the CVTs are active and not blocked.
"Voltages filtered": This is activated while filtered voltages are being used.
It is calculated with the half cycle dft. The calculation is performed on the units indicated by the phase identifier. The SIR value
to bear in mind will always be the one corresponding to the one with lowest value amongst the units indicated by the phase
identifier.
The SIR and the option to use or not to use filtered voltages is assessed when the fault detector is activated. Depending on the
CVT supervision type ("Passive" or "Active"), different thresholds will be used to determine whether or not to used filtered
voltages.
If the SIR is greater than 1 for the actives or 10 for the passive ones, the high speed tripping is blocked and filtered voltages are
used in Zone 1, for both MHO and QUAD characteristics.
SIR for single phase faults SIR for single phase-phase faults
(Vrated/((Ia+3·I0 kn1 +IN2 kM1 )·Z1))-1 (Urated/(Iab·Z1))-1
(Vrated/((Ib+3·I0 kn1 +IN2 kM1 )·Z1))-1 (Urated/(Ibc·Z1))-1
(Vrated/((Ic+3·I0 kn1 +IN2 kM1 )·Z1))-1 (Urated/(Ica·Z1))-1
Where:
In this section all the protection functions are shown, the ones included in each model are indicated in the functional description.
3.2.1 Signals
There are available general signals that group data from several functions (See Table 26). These signals are in the node PROT/PTRC1. In
every model will be only the signals of the available functions.
❑ General Start. Indicates that one of the units that causes a general trip is started.
❑ General Trip. Indicates that one of the units that causes a general trip is activated.
❑ Pole A General Trip. Indicates that one of the units that causes a general trip of pole A is activated.
❑ Pole B General Trip. Indicates that one of the units that causes a general trip of pole B is activated.
❑ Pole C General Trip. Indicates that one of the units that causes a general trip of pole C is activated.
❑ OC General Start. Indicates that one of the overcurrent units is started.
❑ OC General Trip. Indicates that one of the overcurrent units is activated.
❑ 51 Start. Indicates that any of the time delay phase overcurrent unit is started.
❑ 51N Start. Indicates that one of the time delay neutral overcurrent units is started.
❑ 51ES Start. Indicates that one of the time delay earth system overcurrent units is started.
❑ 51UN Start. Indicates that one of the time delay unbalance overcurrent units is started.
❑ 51 Trip. Indicates that one of the time delay phase overcurrent units is activated.
❑ 51N Trip. Indicates that one of the time delay neutral overcurrent units is activated.
❑ 51ES Trip. Indicates that one of the time delay earth system overcurrent units is activated.
❑ 51UN Trip. Indicates that one of the time delay unbalance overcurrent units is activated.
❑ 50 Start. Indicates that one of the instantaneous phase overcurrent units is started.
❑ 50N Start. Indicates that one of the instantaneous neutral overcurrent units is started.
❑ 50ES Start. Indicates that one of the instantaneous earth system overcurrent units is started.
❑ 50UN Start. Indicates that one of the instantaneous unbalance overcurrent units is started.
❑ 50 Trip. Indicates that one of the instantaneous phase overcurrent units is activated.
❑ 50N Trip. Indicates that one of the instantaneous neutral overcurrent units is activated.
❑ 50ES Trip. Indicates that one of the instantaneous earth system overcurrent units is activated.
❑ 50UN Trip. Indicates that one of the instantaneous unbalance overcurrent units is activated.
❑ Voltage Start. Indicates that one of the voltage units is started.
❑ IOV Start. Indicates that one of the instantaneous overvoltage units is started.
❑ IUV Start. Indicates that one of the instantaneous undervoltage units is started.
❑ Minimum F Start. Indicates that one of the underfrequency units is started.
❑ Maximum F Start. Indicates that one of the overfrequency units is started.
❑ dfdt Start. Indicates that one of the df/dt units is started.
❑ Voltage Trip. Indicates that one of the voltage units is activated.
❑ IOV Trip. Indicates that one of the instantaneous overvoltage units is activated.
❑ IUV Trip. Indicates that one of the instantaneous undervoltage units is activated.
❑ Minimum F Trip. Indicates that one of the underfrequency units is activated.
❑ Maximum F Trip. Indicates that one of the overfrequency units is activated.
❑ dfdt Trip. Indicates that one of the df/dt units is activated.
3.2.2 Commands
Certain commands enable actions to be taken on the protection functions. Each function specific characteristics are listed in the
corresponding section. This section lists the general functions. Table 27 shows the functions affected by the general commands.
The blocking/ unblocking commands are stored so that they are maintained when the device is switched off. If a function is enabled by
the settings and blocked by a command, the status shows that is deactivated. All the functions blocked by a command are unblocked
with the command associated to the function, each time an ICD is sent or by the general unblocking command (DOrdRstBlk node
PROT/LLN0). Available from firmware version 5.18.15.4 and ICD version 6.1.13.31.
The general protection commands are in the PROT/PTRC node, allowing the blocking/unblocking of the associated functions:
To reset, the current must fall below 95% of the setting value.
The timed unit can be configured with a minimum response time, that is, a limit that prevents any unit from tripping below a
minimum time when the trip time corresponding to the curve in use is met. This is done to prevent timed trips from being
faster than instantaneous trips. It is configured with an additional time setting, so that if it is set to zero, there is no such limit.
❑ Delay/minimum time (ms). It has a different functionality depending on the type of the curve selected:
When the selected curve is a definite time, it indicates the time during which the conditions for the tripping of the
function must be met.
In the rest of the curve, it indicates the minimum response time. i.e., in order for a trip to be produced, the time used
will be the greater between this setting and the time associated to the curve.
❑ Torque control. Selects the function’s directional type:
“NO”. Acts as non-directional.
“Forward”. Acts when the directional indicates forward.
“Reverse”. Acts when the directional indicates reverse.
❑ Behaviour with Fuse fail. Defines the function’s action if a fuse failure is detected.
"Idle". The fuse failure does not affect the function.
"Non Directional". The function acts as non-directional when a fuse failure is detected.
"Block". The function blocks, i.e., it does not act, when a fuse failure is detected.
"Enable". The function is enabled when a fuse failure is detected.
❑ Reset type. Allows the emulation of the induction operation. The following options are available:
"Instantaneous". If the current drops below 95% of the setting value, both the trip and the pickup reset
instantaneously.
"Timed". If the current drops below 95% of the setting value, the trip drops out instantaneously, while the pickup reset
time will depend on the selected curve (family and index) and the current. If a definite time curve is selected, the
pickup will reset upon the completion of the time programmed for the pickup as of the moment in which it falls below
the pickup current, regardless of the current value.
❑ Operating Quantity. Indicates the measurement used by the function (52 ½ models only allow "Phasor"):
"Phasor". Uses the fundamental measurement, without including harmonics.
"RMS". Uses the effective value, including harmonics.
❑ Blocking Input. Selects the signal which, when active, blocks the function.
❑ Time delay cancel Input. Selects the signal which, when active, generates an instantaneous trip regardless of the set time.
❑ General trip. Indicates if this unit produces general trip or not. For additional details, see the section corresponding to the
recloser (3.12.6).
❑ Trip Permission by recloser. Indicates the trip and block permission in accordance with the recloser status: standby,
blocked, safety time after reclosing, after closing. It is configured bit by bit; for additional details, see section
corresponding to the recloser (3.12.6.3).
❑ Reclose perm.(R1,R2,R3,R4). Indicates whether each trip type can be reclosed or not, in accordance with the recloser's
closing cycle (see reclosure permission mask).
❑ Enable Events record. Allows the generation of protection events associated to the function. If set to “NO”, the function’s
protection events are not generate. If set to “YES”, the function’s specific mask is contemplated.
To reset, the current must fall below 95% of the setting value.
There are logical “function X directional inhibition” inputs that allow the directional units to which they are applied to be converted
into non-directional. These inputs allow for a unit's conversion into non-directional in the case of a fuse failure, for example.
This function’s general settings and those applied in the quadrature, quadrature 2 out of 3 and positive sequence criteria are in
the PROT/RDIR1 node:
The minimum polarization current is considered as 50% of the minimum setting of the three timed and instantaneous phase
units (50/51) that are enabled. When all units are disabled, the minimum polarization current is considered as 50% of the phase
rated current.
The quadrature and positive sequence units settings, commands and outputs.
❑ Node: PROT/RDIR1
❑ Settings and logical inputs. There are 6 settings tables. For details, see Table 30.
❑ Commands:
“DOrdBlk”: Function blocking and unblocking.
“DOrdInvDir”. Inverts the directional trip direction.
❑ Outputs: Table 31 shows the function’s output data.
67 Forward X. The detected direction indicates forward. It is independent for each phase.
67 Reverse X. The detected direction indicates reverse. It is independent for each phase.
Polarization Failure X. Indicates that the direction has not been detected due to a polarization failure. It is independent
for each phase.
Phase directional inhibition. Indicates that the directional is inhibited.
Phase direction inversion. Indicates that the direction is opposite to the setting.
3.3.2.1.1 Quadrature
For the detection of directionality in phases, the polarization voltage corresponds to the quadrature connection (90º), in
which each phase’s current is compared with the phase to phase voltage between the other two phases (See Figure 59).
π
Phase Ia: Spol = Vbc Sop = Ia ∙ e−j∙(90º−MTA_FASES)∙180
π
Phase Ib: Spol = Vca Sop = Ib ∙ e−j∙(90º−MTA_FASES)∙180
π
Phase Ic: Spol = Vab Sop = Ic ∙ e−j∙(90º−MTA_FASES)∙180
Amplitude º
|angle(Spol) − angle(Sop)| < ( )
2
Where, Amplitude is the setting "Zone amplitude (º)"
The “Quad. 2 out of 3” means that the unit only signals forward if this direction is seen in 2 phases. Avoids cases in which,
with a reverse fault, certain of the phases detect a forward fault (e.g., weak infeed). In the case of weak infeed due to the
opening of a transformer, there is only zero sequence current and therefore the three phases detect the same current. In
this case, one of the 3 phases will detect the fault in the opposite direction to the other two.
It operates as three single phase units in which polarization voltages are the phase to phase voltages of the healthy phases.
In the case of an ABC phase sequence, polarization is effected with Vab, Vbc and Vac, for Ic, Ia and Ib. In the case of a CBA
phase sequence, polarization is effected with Vba, Vcb and Vac, for Ic, Ia and Ib.
There is a 5º zone between the non-trip zone and the trip zone in which the current directional status is maintained.
This unit’s signals are independent for each of the phases (See Table 31).
Memory
The polarization voltage is the voltage of the previous 3 cycles. If the voltage falls below the setting "Minimum V
polarization (V)", the value memorized in accordance with the memory management explained in the polarization memory
monitoring is used (See 3.3.3). It is also affected by the series compensation logic in so far that if it is set to “YES” the
memorized voltage is used as of the moment in which a fault or a voltage inversion is detected.
When the polarization voltage is below the setting "Minimum V polarization (V)" or the operating current is below the
minimum polarization current “Polarization Failure X” is indicated. In this situation, if the trip permission without
polarization V is set to “YES”, the trip is permitted; while if set to “NO”, it is blocked.
S1pol = V1
π
S1op = I1 ∙ ej∙MTA_FASES∙180
Amplitude º
|angle(S1pol) − angle(S1op)| < ( )
2
Where, Amplitude is the setting "Zone amplitude (º)"
There is a 5º zone between the non-trip zone and the trip zone in which the current directional status is maintained.
This unit’s signals are the same as those of the quadrature, with the difference that the three phases are always given
simultaneously (See Table 31).
Memory
The polarization voltage is the positive sequence voltage of the previous 3 cycles. If it falls below the setting "Minimum V1
(V)", the value memorized in accordance with the memory management explained in the polarization memory monitoring
is used (See 3.3.3). It is also affected by the series compensation logic in so far that if it is set to “YES” the memorized
voltage is used as of the moment in which a fault or a voltage inversion is detected.
When the V1 polarization voltage is below the setting “Minimum V polarization (V)” or the operating current is below the
minimum polarization current “Polarization Failure X” is indicated.
The directional block is used when the operating current is below the minimum polarization current.
If V1 is below the setting “Minimum V polarization (V)” but the operating current is above the minimum polarization
current, if the trip permission without polarization V is set to “YES”, the trip is permitted; while if set to “NO”, it is blocked.
❑ If the negative sequence indicates the direction, the positive sequence is not consulted.
❑ If the negative sequence indicates a polarization failure, the positive sequence is consulted.
The direction is determined by the comparison between the negative sequence voltage and current, with 3V2 greater than the
threshold "Minimum V polarization (V)" and I2 greater than the thresholds "Minimum I2 / I1 Ph (%)" and "Minimum 3I2 / Irated
(%)" (See Figure 61).
In the case of lines with series compensation, a Z2offset setting, which modifies the polarization voltage, is included.
𝜋
S2pol = −3 ∙ V2 + 3 ∙ I2 ∙ Z2Offset ∙ ej∙MTA_S2∙180
π
S2op = 3 ∙ I2 ∙ ej∙MTA_S2∙180
Amplitude º
|angle(S2pol) − angle(S2op)| < ( )
2
There is a 5º zone between the non-trip zone and the trip zone in which the current directional status is maintained.
S2pol is -3·V2
If Z2offset is used:
S2pol depends on the relation between S2pol and the setting "Minimum V polarization (V)". If the S2pol calculated
with Z2Offset is greater than "Minimum V polarization (V)", the calculated S2pol is used. On the other hand, if "-3·V2"
is greater than "Minimum V polarization (V)", S2pol = -3·V2 is used.
Trip permission with low Vpol
When the S2pol polarization voltage is below the setting "Minimum V polarization (V)" or the negative sequence current (I2) is
below any of the thresholds "Minimum I2 / I1 Ph (%)" or "Minimum 3I2 / Irated (%)", “Polarization Failure S2” is indicated.
The directional block is used when the negative sequence current (I2) is below any of the thresholds "Minimum I2 / I1 (%)" or
"Minimum I2 / Irated (%)".
If S2pol is below the setting "Minimum V polarization (V)" and I2 is greater than the thresholds "Minimum I2 / I1 Ph (%)" and
"Minimum 3I2 / Irated (%)", if the trip permission without polarization V is set to “YES”, the trip is permitted; while if set to
“NO”, it is blocked.
For the phase overcurrent units, the negative sequence directional uses the "Permission with low Vpol" setting which is on the
node PROT/RDIR1 (Phase directional).
For the neutral overcurrent units, the negative sequence directional uses the "Permission with low Vpol" setting which is on the
node PROT/GRDIR1 (Ground directional).
For the unbalanced overcurrent units, the negative sequence directional uses the "Permission with low Vpol 67Q" setting which
is on the node PROT/S2RDIR1(Negative sequence directional).
This function’s general settings and those applied in the quadrature and positive sequence criteria are in the PROT/S2RDIR1
node:
4
Avaliable from firmware version 6.0.8.0 and ICD version 8.1.0.4
❑ Node: PROT/S2RDIR1
❑ Settings and logical inputs. There are 6 settings tables. See Table 32.
❑ Commands:
“DOrdBlk”: Function blocking and unblocking.
“DOrdInvDir”. Inverts the directional trip direction
❑ Outputs: Table 33 shows the function’s output data.
67-S2 Forward. The detected direction indicates forward.
67-S2 Reverse. The detected direction indicates reverse.
Polarization Failure S2. Indicates that the direction has not been detected due to a polarization failure.
S2 Directional Inhibition. Indicates that the directional is inhibited.
S2 Direction Inversion. Indicates that the direction is opposite to the setting.
Table 33 Negative sequence directional outputs
The operation can be selected from among: angular, cosine, sine and watt-metric. Various options can be selected from within
the angular criteria.
This unit’s settings are in the PROT/GRDIR node. In accordance with the selected mode, they affect:
General settings.
❑ Voltage directional Type. Only applied if the polarization voltage has been selected.
S0. Zero sequence.
S2. Negative sequence.
S2 and S0. Negative and zero sequence.
S2 or S0. Negative or zero sequence.
S2 →S0. Negative sequence and, in the event of uncertainty, zero sequence.
S0 →S2. Zero sequence and, in the event of uncertainty, negative sequence.
❑ Torque angle (º). Indicates the directional angle.
❑ Zone amplitude (º). Indicates the angle covered by the trip zone.
❑ Minimum V polarization (V). Indicates the minimum voltage for polarization; the direction cannot be reliably determined
below this value.
❑ Permission with low Vpol. Indicates the functioning of the directional when the polarization voltage is below the threshold.
If set to “YES”, it enables an overcurrent trip if the memorized polarization voltage is lower than the minimum polarization
voltage; if set to “NO”, the overcurrent trip is not allowed under those conditions.
❑ Minimum Ipol/Irated gnd (%). Indicates the minimum current for polarization; the direction cannot be reliably determined
below this value.
❑ Offset Z0 (Ohm). Offset impedance for the zero sequence directional unit.
❑ Minimum 3I0/I1 (%). Percentage of I1. Indicates the minimum value of I0 in relation to I1.
Settings with "Ground directional method" as Watt-metric, I·cos, I·sin
❑ Minimum power: Isin, Icos, W: Power value P=Vn·In·cos(-c), in which =Angle between Vn and In. If the power negative
and higher than this value, a forward fault is registered. If it is positive and higher than this value, a reverse fault is
registered.
❑ Icos/Isin method switch. If a signal is assigned to this input, it indicates the directional type used (independent of the
setting) I·cos if the input is 0 (deactivated) and I·sin if the input is 1 (activated). If no signal has been assigned, the
criterion selected for the setting is used.
The neutral units have settings, commands and outputs:
❑ Node: PROT/GRDIR1
❑ Settings and logical inputs. There are 6 settings tables. See Table 34 for details.
❑ Commands:
“DOrdBlk”: Function blocking and unblocking.
“DOrdInvDir”. Inverts the directional trip direction.
❑ Outputs: Table 35 shows the function’s output data.
67N-Forward. The detected direction indicates forward.
67N-Reverse. The detected direction indicates reverse.
Polarization Failure In. It indicates that the direction has not been detected due to a polarization failure.
Gnd directional inhibition. Indicates that the directional is inhibited.
Ground direction inversion. Indicates that the direction is opposite to the setting.
Polarizations
If Ineutral is less than "Minimum 3I0/Irated gnd (%)" of the neutral rated current or less than "Minimum 3I0/I1 (%)" of the
positive sequence current (I1), a “Polarization Failure In” is issued and no other actions are taken.
It is polarized by voltage. Depending on the setting "Voltage directional Type", the polarization voltage can be the zero
sequence, negative sequence or both.
Ipol
If Ineutral is less than "Minimum 3I0/Irated gnd (%)" of the neutral rated current or less than "Minimum 3I0/I1 (%)" of the
positive sequence current (I1), a “Polarization Failure In” is issued and no other actions are taken.
I→V
If Ineutral is less than "Minimum 3I0/Irated gnd (%)" of the neutral rated current or less than "Minimum 3I0/I1 (%)" of the
positive sequence current (I1), a “Polarization Failure In” is issued and no other actions are taken.
If the I unit does not determine the polarization fault direction, the voltage signal combination is analysed.
If the result is “Without VPOL”, that is, the polarization voltage is below the setting "Minimum V polarization (V)", the trip
permission depends on the setting "Permission with low Vpol".
I and V
If Ineutral is less than "Minimum 3I0/Irated gnd (%)" of the neutral rated current or less than "Minimum 3I0/I1 (%)" of the
positive sequence current (I1), a “Polarization Failure In” is issued and no other actions are taken.
Both units (Ipol and V) are analysed. If both give the same result, a forward or reverse indication is made. It the result is
different, there is no permission.
If any of them does not determine the direction, a “Polarization Failure In” message is indicated and a decision is taken in
accordance with the “Permission with low Vpol” setting.
I or V
If Ineutral is less than "Minimum 3I0/Irated gnd (%)" of the neutral rated current or less than "Minimum 3I0/I1 (%)" of the
positive sequence current (I1), a “Polarization Failure In” is issued and no other actions are taken.
Both units (Ipol and V) are analysed. If any of them indicates forward or reverse, the corresponding signal is activated. If
one indicates forward and the other reverse, both directions are activated.
If they do not determine the direction, a “Polarization Failure In” message is indicated and a decision is taken in accordance
with the “Permission with low Vpol” setting.
Furthermore, with this setting it can be selected among the following options:
S0
The direction is determined with the neutral current and the neutral voltage as polarization (See 3.3.2.3.2).
S2
The direction is determined with the negative sequence current and the negative sequence voltage as polarization (See
3.3.2.2).
S0 and S2
Both units (S2 and S0) are analysed. If both give the same result, a forward or reverse indication is made. It the result is
different, there is no permission.
If any of them (S0 or S2) does not determine the direction, a "Polarization Failure In” or "Polarization Failure S2" message is
indicated and a decision is taken in accordance with the “Permission with low Vpol” setting.
Specific situations:
One unit set in reverse and one set forward. S0 indicates reverse and S2 forward. No output is given.
V0 V2 Result
F F F
F R Nothing
R R R
R F Nothing
F Without Vpol Without Vpol
R Without Vpol Without Vpol
Without Vpol F Without Vpol
Without Vpol R Without Vpol
Without Vpol Without Vpol Without Vpol
S0 or S2
Both units (S2 and S0) are analysed. If any of them indicates forward or reverse, the corresponding signal is activated. If one
indicated forward and the other reverse, both directions are activated.
If both of them (S0 or S2) do not determine the direction, a "Polarization Failure In” or "Polarization Failure S2" message is
indicated and a decision is taken in accordance with the “Permission with low Vpol” setting.
Specific situations:
V0 V2 Result
F F F
F R F&R
R R R
R F F&R
F Without Vpol F
R Without Vpol R
Without Vpol F F
Without Vpol R R
Without Vpol Without Vpol Without Vpol
S2 → S0
If the S2 unit does not determine the direction, a “Polarization Failure S2” signal is activated and S0 is analysed.
If the conditions for determining the direction are still not given, a “Polarization Failure In” signal is activated and a decision
is taken in accordance with the “Permission with low Vpol” setting.
One unit set in reverse and one set forward. S2 indicates reverse and S0 forward. Only reverse would be signalled (due to
S2).
S2 S0 Result
F F or R or Without Vpol F
R F or R or Without Vpol R
Without Vpol F F
Without Vpol R R
Without Vpol Without Vpol Without Vpol
S0 → S2
If the S0 unit does not determine the direction, a “Polarization Failure In” signal is activated and S2 is analysed.
If the conditions for determining the direction are still not given, a “Polarization Failure S2” signal is activated and a decision
is taken in accordance with the “Permission with low Vpol” setting.
One unit set in reverse and one set forward. S0 indicates reverse and S2 forward. Only reverse would be signalled (due to
S0).
S0 S2 Result
F F or R or Without Vpol F
R F or R or Without Vpol R
Without Vpol F F
Without Vpol R R
Without Vpol Without Vpol Without Vpol
3.3.2.3.2 S0 polarization
The direction is determined by comparing the neutral current with the neutral voltage as polarization. The angle
determines the range in which the fault is considered as a forward fault and as a reverse fault. A Z0offset setting, which
modifies the polarization voltage, is included.
π
S0pol = −VN + IN ∙ Z0Offset ∙ ej∙MTA_S0∙180
π
S0op = IN ∙ ej∙MTA_S0∙180
Amplitude º
|angle(S0pol) − angle(S0op)| < ( )
2
Where, Amplitude is the setting "Zone amplitude (º)"
The In=3·I0 measurement can be calculated as the sum of the phase currents or as the measurement of the neutral
transformer, depending on the setting "I0 type: measured/calculated" in the node "PROT/TCIN1".
The VN=3·V0 voltage can be calculated using the phase to earth voltages of the phases or it can be measured by a
transformer, in accordance with the “3V0 Operating quantity” setting in the PROT/PVGE1 node.
S0pol is -3·V0
If Z0offset is used:
When the S0pol polarization voltage is below the setting "Minimum V polarization (V)" or the neutral current is below to any of
the thresholds "Minimum 3I0 / Irated (%)" and "Minimum 3I0 / I1 (%)", “Polarization Failure In” is indicated.
The directional block is used when the neutral current is below to any of the thresholds "Minimum 3I0 / Irated (%)" and
"Minimum 3I0 / I1 (%)".
If S0pol is below the setting "Minimum V polarization (V)" and the operation current is greater than the thresholds "Minimum
3I0 / Irated (%)" and "Minimum 3I0 / I1 (%)", if the trip permission without polarization V is set to “YES”, the trip is permitted;
while if set to “NO”, it is blocked.
3.3.2.3.3 I polarization
The direction is determined by comparing the ground current (Ipol) with the neutral current. To be able to verify the
direction, Ipol must be greater than the percent of neutral rated current indicated in the setting "Minimum Ipol/Irated gnd
(%)".
The In=3·I0 measurement can be calculated as the sum of the phase currents or as the measurement of the neutral
transformer, depending on the setting "I0 type: measured/calculated" in the node "PROT/TCIN1".
There is a 5º zone between the non-trip zone and the trip zone in which the current directional status is maintained, both
for voltage and for current polarization.
When the neutral current is below any of the thresholds "Minimum 3I0 / Irated (%)" and "Minimum 3I0 / I1 (%)",
“Polarization Failure In” is indicated.
When the Ipol is below to the percent of neutral rated current indicated in the setting "Minimum Ipol/Irated (%)",
“Polarization Failure In” is indicated. In this case, there is “NO” trip permission.
The In=3·I0 measurement can be calculated as the sum of the phase currents o as the measurement of the neutral
transformer, depending on the setting "I0 type" in the node "PROT/TCIN1".
The VN=3·V0 voltage can be calculated using the phase to earth voltages of the phases or it can be measured by a
transformer, in accordance with the “V0 measurement type” setting in the PROT/PVGE1 node.
In order to allow the directional unit to pickup, the following must be met:
❑ For reverse faults, the angle between the current and the displaced voltage, the maximum torque angle must be
between 275 and 85.
275º < 𝑎𝑛𝑔𝑙𝑒(𝐼0) − 𝑎𝑛𝑔𝑙𝑒(𝑉0) + 𝑇𝑜𝑟𝑞𝑢𝑒𝑎𝑛𝑔𝑙𝑒 < 85º
❑ The power P=Vn·In·cos(-c) must exceed the minimum power "Minimum power: Isin, Icos, W" by the absolute
value. If the sign of P is negative, the fault is forward. If positive, the fault is reverse.
The equation to be implemented for calculating P is as follows:
P = [Re(V0) ∙ cos c + Im(V0) ∙ sin c] ∙ Re(I0) + [Im(V0) ∙ cos c − Re(V0) ∙ sin c] ∙ Im(I0)
c = Torque angle
= 𝑎𝑛𝑔𝑙𝑒(𝑉0) − 𝑎𝑛𝑔𝑙𝑒(𝐼0)
Figure 66 Directional with watt-metric polarization
If the voltage VN is lower than "Minimum V polarization (V)", "Polarization Failure In" is indicated. If "Permission with low
Vpol" is set to "YES", the trip is allowed, if it is set to "NO", it is blocked.
The VN=3·V0 voltage can be calculated using the phase to earth voltages of the phases or it can be measured by a
transformer, in accordance with the “V0 measurement type” setting in the PROT/PVGE1 node.
An input can be programmed (“Icos/Isin method switch”) such that when activated the operating mode of I*cos() changes
to I*sin(). If programmed, this input cancels the setting: if deactivated, it runs the I*cos() algorithm. If activated, the
I*sin() algorithm is run, independently of the setting. It does not affect either the angular of the watt-metric directional.
I*cos() directional
In order to allow the directional unit to pickup, the following must be met:
❑ For reverse faults, the angle between the current and the displaced voltage, the maximum torque angle must be
between 275 and 85.
275º < a𝑛𝑔𝑙𝑒(𝐼0) − a𝑛𝑔𝑙𝑒(𝑉0) + 𝑇𝑜𝑟𝑞𝑢𝑒 𝑎𝑛𝑔𝑙𝑒 < 85º
❑ The minimum current "I minimum= In·cos(-c)" must exceed the minimum threshold "Minimum 3I0 / Irated (%)"
by the absolute value. If the sign is negative, the fault is forward. If positive, the fault is reverse.
[Re(V0) ∙ cos c + Im(V0) ∙ sin c] ∙ Re(I0) + [Im(V0) ∙ cos c − Re(V0) ∙ sin c] ∙ Im(I0)
I0 ∙ cos( − c) =
|V0|
c = Torque angle
= angle(V0) − angle(I0)
As the neutral units allow trip permission to be issued with forward and with reverse faults, in reality the characteristics will
be as follows.
If the voltage VN is lower than "Minimum V polarization (V)", "Polarization Failure In" is indicated. If "Permission with low
Vpol" is set to "YES", the trip is allowed, if it is set to "NO", it is blocked.
In order to allow the directional unit to pickup, the following must be met:
❑ Vn exceeds the setting "Minimum V polarization (V)". For forward faults, the angle between the current and the
displaced voltage, the maximum torque angle must be between 185 and 355.
185º < 𝑎𝑛𝑔𝑙𝑒(𝐼0) − 𝑎𝑛𝑔𝑙𝑒(𝑉0) + 𝑇𝑜𝑟𝑞𝑢𝑒 𝑎𝑛𝑔𝑙𝑒 < 355º
❑ For reverse faults, the angle between the current and the displaced voltage, the maximum torque angle must be
between 5 and 175.
5º < 𝑎𝑛𝑔𝑙𝑒(𝐼0) − 𝑎𝑛𝑔𝑙𝑒(𝑉0) + 𝑇𝑜𝑟𝑞𝑢𝑒𝑎𝑛𝑔𝑙𝑒 < 175º
❑ The minimum current "I minimum=In·sin(-c)" must exceed the minimum threshold "Minimum 3I0 / Irated (%)"
by the absolute value. If the sign is negative, the fault is forward. If positive, the fault is reverse.
[Im(V0) ∙ cos c − Re(V0) ∙ sin c] ∙ Re(I0) − [Re(V0) ∙ cos c + Im(V0) ∙ sin c] ∙ Im(I0)
I0 ∙ sin( − c) =
|V0|
c = Torque angle
= 𝑎𝑛𝑔𝑙𝑒(𝑉0) − 𝑎𝑛𝑔𝑙𝑒(𝐼0)
Figure 69 Directional with sine polarization
If the voltage VN is lower than "Minimum V polarization (V)", "Polarization Failure In" is indicated. If "Permission with low
Vpol" is set to "YES", the trip is allowed, if it is set to "NO", it is blocked.
Allows the memorized voltage to be used during the configured time when the current voltage is not apt.
❑ If V1> Minimum V1 is met during at least 4 cycles, the memorized voltage is captured once again.
❑ V1mem is then update to the V1 value registered 3 cycles previously. Thus, in the moment in which the conditions for
using it are met, the value registered 3 cycles previously will be taken.
❑ V1mem is captured in the moment the voltage is above the setting Minimum V1 and is used during the time set in "V1
maintenance time".
❑ If the breaker is open (open pole logic) with the V1 above the setting "Minimum V1", the voltage V1 without memory is
used.
❑ If the series compensation logic is enabled, node PROT.PSEC1, the memorized voltage is used when the fault detection is
activated.
❑ If the "Blocking by power swinging" signal is activated, the actual V1 is used (not memorized)
❑ The logic input "Force V1 with memory" forces the use of memorized voltage in the positive sequence polarization.
❑ The logic input "Force V1 without memory" forces the use of non-memorized voltage in the positive sequence polarization.
This unit’s operating scheme for the overcurrent directional units is:
❑ If Vx> Minimum Vx is met during at least 4 cycles, the memorized voltage is captured once again.
❑ Vxmen is then update to the Vx value registered 3 cycles previously. Thus, in the moment in which the conditions for using
it are met, the value registered 3 cycles previously will be taken.
❑ The 67-50/51 units are normally polarized without memory. The memorized voltage is used in the moment in which the
actual Vx voltage drops below Minimum Vx. The memory time is indicated in the maintenance time setting.
❑ If the series compensation is enabled, node PROT.PSEC1, the memorized voltage is used when the fault detection is
activated.
❑ The logic input "Force Vx with memory" forces the use of memorized voltage in the positive sequence polarization.
❑ The logic input "Force Vx without memory" forces the use of non-memorized voltage in the positive sequence polarization.
The positive sequence voltage (V1) and the quadrature voltages are analysed separately (Vab, Vbc and Vac).
The function’s logic diagram is shown in Figure 70 (distance units), Figure 71 (overcurrent units, positive sequence) and Figure
72 (overcurrent units, quadrature).
❑ Minimum V1 (V). Indicates the minimum V1 value for employing the memorized voltage.
❑ V1 Memory Time (ms). Indicates the time during which the memorized voltage is used in the polarization by positive
sequence.
❑ Minimum Ph-ph voltage (V). Indicates the minimum quadrature voltage for employing the memorized voltage.
❑ Vc Memory Time (ms). Indicates the time during which the memorized voltage is used in the polarization by quadrature.
❑ Force V1 with memory. Forces the use of memorized voltage in the positive sequence polarization.
❑ Force V1 without memory. Forces the use of non-memorized voltage in the positive sequence polarization.
❑ Force Vc with memory. Forces the use of memorized voltage in the quadrature polarization.
❑ Force Vc without memory. Forces the use of non-memorized voltage in the quadrature polarization.
❑ Enable Events record. Allows the generation of protection events associated to the function. If set to “NO”, the function’s
protection events are not generate. If set to “YES”, the function’s specific mask is contemplated.
Table 36 Directional memory monitoring settings
❑ Node: PROT/MSUPPTRC1
❑ Settings and logical inputs. There are 6 settings tables. For details, see Table 36.
❑ Outputs:
Memorized Ph-Ph Voltage. It is activated while the memorized phase-phase voltage is being used.
V1 memorized. It is activated while the memorized V1 is being used.
V1 memorized distance. It is activated while the memorized V1 is being used in the distance units.
The input signals of these schemes are:
If it is enabled, the memorized voltage is used when the voltage is below the threshold set or when the fault detection is
activated. This unit applies to the distance and the phase overcurrent units.
❑ Node: PROT/PSEC1
❑ Settings and logical inputs. There are 6 settings tables. For details, see Table 38
❑ Outputs: Table 39 shows the function's output data
Series compensation status: Indicates the function’s status. It is active when enabled and not blocked.
3.3.5.1 Instantaneous
There are 3 independent units for each of the phases.
Each of the three units has independent settings, commands and outputs.
❑ Nodes:
Unit 1: PROT/PIOC1
Unit 2: PROT/PIOC2
Unit 3: PROT/PIOC3
❑ Settings and logical inputs. There are 6 settings tables. See Table 29.
❑ Commands:
“DOrdBlk”: Function blocking and unblocking. Only acts when the function is enabled.
❑ Outputs: Table 40 shows the function’s output data.
IOC1 Start phase X. Indicates that the unit's phase has picked up. It is independent for each phase. Where X is the
phase.
IOC1 Trip phase X. Indicates that the unit's phase has tripped. It is independent for each phase. Where X is the phase.
IOC1 Phase Status. Indicates the function’s status. It is active when enabled and not blocked. This is general for all
three phases.
IOC1 phase Start. Indicates that the unit has picked up
IOC1 phase Trip. Indicates that the unit has tripped.
3.3.5.2 Timed
There are 3 independent units for each of the phases.
Each of the three units has independent settings, commands and outputs.
❑ Nodes:
Unit 1: PROT/PTOC1
Unit 2: PROT/PTOC2
Unit 3: PROT/PTOC3
❑ Settings and logical inputs. There are 6 settings tables. See Table 28.
❑ Commands:
“DOrdBlk”: Function blocking and unblocking. Only acts when the function is enabled.
❑ Outputs: Table 41 shows the function’s output data.
TOC1 Start phase X. Indicates that the unit's phase has picked up. It is independent for each phase. Where X is the
phase.
TOC1 Trip phase X. Indicates that the unit's phase has tripped. It is independent for each phase. Where X is the phase.
TOC1 Phase Status. Indicates the function’s status. It is active when enabled and not blocked. This is general for all
three phases.
TOC1 Phase Start. Indicates that the unit has picked up
TOC1 Phase Trip. Indicates that the unit has tripped.
Table 41 Timed phase function outputs
3.3.6.1 Instantaneous
There are 3 independent units.
Each of the three units has independent settings, commands and outputs.
❑ Nodes:
Unit 1: PROT/GPIOC1
Unit 2: PROT/GPIOC2
Unit 3: PROT/GPIOC3
❑ Settings and logical inputs. There are 6 settings tables. See Table 29.
❑ Commands:
“DOrdBlk”: Function blocking and unblocking. Only acts when the function is enabled.
❑ Outputs: Table 42 shows the function’s output data.
GIOC1 Start. Indicates that the unit has picked up.
GIOC1 Trip. Indicates that the unit has tripped.
IOC1 Ground Status. Indicates the function’s status. It is active when enabled and not blocked.
Table 42 Neutral instantaneous function outputs
3.3.6.2 Timed
There are 3 independent units.
Each of the three units has independent settings, commands and outputs.
❑ Nodes:
Unit 1: PROT/GPTOC1
Unit 2: PROT/GPTOC2
Unit 3: PROT/GPTOC3
❑ Settings and logical inputs. There are 6 settings tables. See Table 28.
❑ Commands:
“DOrdBlk”: Function blocking and unblocking. Only acts when the function is enabled.
❑ Outputs: Table 43 shows the function’s output data.
GTOC1 Start. Indicates that the unit has picked up.
GTOC1 Trip. Indicates that the unit has tripped.
TOC1 Ground Status. Indicates the function’s status. It is active when enabled and not blocked.
3.3.7.1 Instantaneous
There are 3 independent units.
Each of the three units has independent settings, commands and outputs.
❑ Nodes:
Unit 1: PROT/ESPIOC1
Unit 2: PROT/ESPIOC2
Unit 3: PROT/ESPIOC3
❑ Settings and logical inputs. There are 6 settings tables. See Table 29.
❑ Commands:
“DOrdBlk”: Function blocking and unblocking. Only acts when the function is enabled.
❑ Outputs: Table 44 shows the function’s output data.
ESIOC1 Start. Indicates that the unit has picked up.
ESIOC1 Trip. Indicates that the unit has tripped.
IOC1 Earthing System Status. Indicates the function’s status. It is active when enabled and not blocked.
Table 44 Instantaneous grounding function outputs
3.3.7.2 Timed
There are 3 independent units.
Each of the three units has independent settings, commands and outputs.
❑ Nodes:
Unit 1: PROT/ESPTOC1
Unit 2: PROT/ESPTOC2
Unit 3: PROT/ESPTOC3
❑ Settings and logical inputs. There are 6 settings tables. See Table 28.
❑ Commands:
“DOrdBlk”: Function blocking and unblocking. Only acts when the function is enabled.
❑ Outputs: Table 45 shows the function’s output data.
ESTOC1 Start. Indicates that the unit has picked up.
ESTOC1 Trip. Indicates that the unit has tripped.
TOC1 Earthing System Status. Indicates the function’s status. It is active when enabled and not blocked.
The calculation of the sequence takes into phase succession order setting (ABC/ACB).
The measurement type setting is not used, as the fundamental is always used.
3.3.8.1 Instantaneous
There are 3 independent units.
Each of the three units has independent settings, commands and outputs.
❑ Nodes:
Unit 1: PROT/UNPIOC1
Unit 2: PROT/UNPIOC2
Unit 3: PROT/UNPIOC3
❑ Settings and logical inputs. There are 6 settings tables. It employs the settings in Table 29, with the exception of the
measurement type.
❑ Commands:
“DOrdBlk”: Function blocking and unblocking. Only acts when the function is enabled.
❑ Outputs: Table 46 shows the function’s output data.
UNIOC1 Start. Indicates that the unit has picked up.
UNIOC1 Trip. Indicates that the unit has tripped.
IOC1 Unbalanced Status. Indicates the function’s status. It is active when enabled and not blocked.
3.3.8.2 Timed
There are 3 independent units.
Each of the three units has independent settings, commands and outputs.
❑ Nodes:
Unit 1: PROT/UNPTOC1
Unit 2: PROT/UNPTOC2
Unit 3: PROT/UNPTOC3
❑ Settings and logical inputs. There are 6 settings tables. Employs the settings in Table 28, with the exception of the
measurement type.
❑ Commands:
“DOrdBlk”: Function blocking and unblocking. Only acts when the function is enabled.
❑ Outputs: Table 47 shows the function’s output data.
UNTOC1 Start. Indicates that the unit has picked up.
UNTOC1 Trip. Indicates that the unit has tripped.
TOC1 Unbalanced Status. Indicates the function’s status. It is active when enabled and not blocked.
Restraint by phase or for all the phases is available for the 50/51 units. The units to be blocked are selected by settings.
❑ The current must be less than 95% of the minimum current threshold, or
❑ The current must be below 95% of the restraint percentage threshold.
The restraint is calculated independently for each phase and neutral.
The phase units’ restraint can act per phase (the restraint in any one phase only blocks the phase in question) or it can be general
(the restraint in any one phase blocks all the phases).
For the unbalanced unit restraint, it is sufficient that the conditions are given in a phase or in the neutral.
❑ Enabled. Indicates whether the function is enabled or not. The options available are:
YES. It is enabled.
NO. It is disabled.
Only in close. It is enabled for a second after closing.
❑ I 2nd/fund. Threshold (%). Indicates the percentage of the 2nd harmonic in relation to the fundamental above which the
restraint is produced.
❑ Minimum current (A). Minimum value of the fundamental current in order for the restraint to be produced. No restraint is
indicated below this value, even when the % I 2nd/Ifund is above the setting.
❑ Restraint. Enables the units on which the restraint is to act to be indicated. There are separate settings for each unit. In
general, the setting is "NO / YES", except in those phases that can be:
NO. Restraint is not permitted.
Phase. The restraint in one phase only blocks the phase in question.
General. The restraint in one phase blocks all the phases.
❑ Harm.Restraint Blocking. Selects the signal which, when active, blocks the function.
❑ Enable Events record. Allows the generation of protection events associated to the function. If set to “NO”, the function’s
protection events are not generate. If set to “YES”, the function’s specific mask is contemplated.
There are independent settings, commands and outputs in each restraint unit.
Phases
❑ Node: PROT/PHAR1
❑ Settings and logical inputs. There are 6 settings tables. For details, see Table 49. There is restraint setting for each timed
and instantaneous phase overcurrent unit (NO / Phase / General) and unbalanced (NO / YES)
❑ Commands:
“DOrdBlk”: Function blocking and unblocking. Only acts when the function is enabled.
❑ Outputs:
2nd harmonic restraint Ix. Indicates that the restraint has been activated in this phase. It is independent for each
phase.
2nd harmonic restraint ph. Indicates that the restraint has been activated in one of the phases.
Harm. Ph. restraint Status. Indicates the function’s status. It is active when enabled and not blocked. This is general for
all three phases.
Neutral
❑ Node: PROT/GPHAR1
❑ Settings and logical inputs. There are 6 settings tables. For details, see Table 51. There is restraint setting for each timed
and instantaneous neutral overcurrent unit (NO / YES).
❑ Commands:
“DOrdBlk”: Function blocking and unblocking. Only acts when the function is enabled.
❑ Outputs: Table 50 shows the function’s output data.
2nd harmonic restraint In. It indicates that the neutral restraint has been activated.
Harm. Gr. restraint Status. Indicates the function’s status. It is active when enabled and not blocked.
The pickup value to be set is, expressed as a decimal, and it depends on the setting "Operation type".
There are two modes of operation, selectable by setting. The relay trips once the programmed time has elapsed if the following
conditions are met:
❑ “Always”:
The positive sequence is greater than 3% of I rated.
The negative sequence is greater than 3% of I rated.
I2/I1 ratio exceeds the setting value.
𝐼2 𝐼𝑎 + 𝑎2 · 𝐼𝑏 + 𝑎 · 𝐼𝑐
= 𝐼𝑛 𝑤ℎ𝑖𝑐ℎ, 𝑎 = 1∟120º
𝐼1 𝐼𝑎 + 𝑎 · 𝐼𝑏 + 𝑎2 · 𝐼𝑐
Current value of one phase is greater than the setting "Minimum Phase I (%Irated)".
I0/Irated: I0/Irated is bellow than the setting value. If set to 0, this setting will not be taken into account.
If the breaker is closed, the current value of one or two phases is lower than the setting "Minimum Phase I (%Irated)".
❑ Node: PROT/OPPTOC
❑ Settings and logical inputs. There are 6 settings tables. For details, see Table 52.
❑ Commands:
“DOrdBlk”: Function blocking and unblocking. Only acts when the function is enabled.
❑ Outputs: Table 53 shows the function’s output data.
Broken conductor Start. Indicates that the unit has picked up.
Broken conductor Trip. Indicates that the unit has tripped.
Broken conductor Status. Indicates the function’s status. It is active when enabled and not blocked.
This function calculates a thermal capacity in accordance with the protected unit’s recent and current load conditions. The thermal
capacity is displayed as a % of the trip value. If the function is enabled, a warning signal is activated when the programmed value is
reached. When 100% is reached, the thermal image trip signal is activated. Once tripped as a result, it does not drop-out while the
calculated thermal capacity remains above the reset threshold setting and the rest of the locking conditions are fulfilled. The
calculated thermal capacity can be reset by logic input or by command.
The time which elapses before the trip is determined by the following curves, which establish the time in accordance with the ratio
between the current and the programmed rated current, and the programmed heating constant. According to the following
formula (starting from thermal capacity 0):
In which:
t: trip time
I: measured current
Once it has tripped, there is another programmable time constant for the cooling.
In which:
t: time
As
In which:
t: time
Starting from Ti = 1 (100 in %), which is the thermal capacity at which the trip is produced, the formula used to obtain a thermal
capacity of Tf = 0 (i.e., current I = 0) is as follows
❑ Phases
Ieq2=Imax2
Where:
❑ Neutral. The transformer grounding current is used. If this transformer does not exist, the neutral current is used.
The settings of each of these units are:
❑ Nodes:
Phases: PROT/PTTR
Neutral: PROT/GPTTR
❑ Settings and logical inputs. There are 6 settings tables. For details, see Table 54.
❑ Commands:
“DOrdBlk”: Function blocking and unblocking. Only acts when the function is enabled.
“DOrdIn”: Resetting to zero of thermal image value.
❑ Outputs: Table 55 shows the phase function’s output data and Table 56 shows ground function’s output data.
Thermal Image X Start. Indicates that the unit has picked up. Where X is phase or ground.
Thermal Image X Trip. Indicates that the unit has tripped. Where X is phase or ground.
Thermal Image X Status. Indicates the function’s status. It is active when enabled and not blocked. Where X is phase or
ground.
5
Available from firmware version 5.17.15.3 and ICD 6.1.13.29
Figure 75 shows an example of heating curves with a 3 minute time constant for I/I0 = 1 and for I/I0 = 2
2. Supposing that it is heated with I/I0 =0.5 for 200sec, I/I0 =1.5 until reaching 100%, at which point the trip is produced, as of
that point, it cools with I/I0 = 0 (both with 3 minute time constants):
3.3.12 Undercurrent
There are two independent undercurrent units.
They employ the phases’ fundamental measurements. The unit picks up when the current falls below the setting and drops out
when the current rises above 105% of the setting.
The pickup is generated for each phase, regardless of the setting “Operation type”. However, the unit’s trip takes the operation
type into account.
❑ Nodes:
Unit 1: PROT/PTUC1
Unit 2: PROT/PTUC2
❑ Settings and logical inputs. There are 6 settings tables. For details, see Table 57.
❑ Commands:
“DOrdBlk”: Function blocking and unblocking. Only acts when the function is enabled.
❑ Outputs: Table 58 shows the function’s output data.
TUC1 phase X Start. Indicates that the unit's phase has picked up. It is independent for each phase and does not
consider the setting “Operation type”.
TUC1 phase Start. Pickup of at least one phase. Indicates that at least one of the unit's phases has picked up. It does
not take into account the setting “Operation type”.
TUC1 Start. Taking into account the setting “Operation type”, it indicates that the unit has picked up.
TUC1 Trip. Taking into account the setting “Operation type”, it indicates that the unit has tripped.
Undercurrent Unit 1 Status. Indicates the function’s status. It is active when enabled and not blocked. This is general
for all three phases.
Table 58 Phase undercurrent function outputs
There are independent settings, inputs, commands and outputs in each unit:
❑ Node: PROT/PSTB
❑ Settings. There are 6 settings tables. For details, see Table 59.
❑ Logic inputs:
89 Open/closed input. It indicates the disconnector status
❑ Commands:
“DOrdBlk”: Function blocking and unblocking. Only acts when the function is enabled.
❑ Outputs: Table 60 shows the function's output data.
Stub Bus phase x Start. Indicates that the stub protection is started up by a phase. It is independent for each phase.
Stub Bus neutral Start. Indicates that the stub protection is started up by the neutral.
Stub Bus phase X Trip. Indicates that the stub protection is tripped by a phase. It is independent for each phase.
Stub Bus neutral Trip. Indicates that the stub protection is tripped by the neutral.
Stub Bus Start. Indicates that the stub protection is started up by a phase or by the neutral.
Stub Bus Trip. Indicates that the stub protection is tripped by a phase or by the neutral.
Stub Bus Status. Indicates whether the stub protection is enabled or not.
The input signals of this scheme are:
❑ "Disconnector 1 Status (DI) = OPEN". It is the general status of the disconnector (SXWI)
Table 60 Stub Bus function outputs.
With the function enabled by setting, it is only active when the 3 phases of the disconnector are open
❑ The phase measurements of the local end are zero; therefore, the measures sent to the remote end are zero.
❑ The line differential of the end with the disconnector open does not trip
❑ It doesn´t allow direct trip commands from the other end.
It is calculated on each of the phases and on 3I0. The differential current and restraint of the two breakers are used, following
the curve of Figure 78.
|𝐼𝐵𝑟1 | + |𝐼𝐵𝑟2 |
𝐼𝑝𝑎𝑠𝑜 =
2
Where
Idifferential
Trip zone
2
Sensitivity 1
Irestraint
Ires1 Ires2
There are two independent units for phases and neutral (3I0) with settings, commands and outputs:
❑ Delay time (ms): Indicates the time during which the conditions for the tripping of the function must be met.
❑ Blocking input: Selects the signal which, when active, blocks the function.
❑ General trip: General trip. Indicates if this unit produces general trip or not. For additional details, see the section
corresponding to the recloser (3.12.6).
❑ Enable Events record: Allows the generation of protection events associated to the function. If set to “NO”, the function’s
protection events are not generated. If set to “YES”, the function’s specific mask is contemplated.
Outputs: Table 62 and Table 63 show the output data of the function.
❑ Phase unit:
Start Stub diff. X. Indicates that the differential stub protection is started up by a phase. It is independent for each
phase.
Trip Stub diff. X. Indicates that the differential stub protection is tripped up by a phase. It is independent for each
phase.
Diff Phases stub status. Enabled and not blocked.
❑ Neutral unit:
Start Stub diff.Neutro. Indicates that the differential stub protection is started up by neutral.
Trip Stub diff.Neutro. Indicates that the differential stub protection is tripped up by neutral.
Diff Neutral stub status. Enabled and not blocked.
Every unit has blocking commands:
❑ “DOrdBlk”: Function blocking and unblocking. Only acts when the function is enabled.
When enabled and unblocked, the undervoltage units act when the voltage is inferior to the setting value during the programmed
time. In order to reset, the voltage must exceed the pickup value return percentage. For example, if the pickup threshold is 50V and
the reset percentage is 10%, the unit must register voltage below 50V in order to pickup and voltage above 55V in order to reset
(50+0.1 50).
The voltage unit’s general settings are available in the PROT/PVGE1 node (return percentages and VO measurement type):
❑ Phase overV drop out (%). Indicates the pickup setting percentage below which the voltage must fall in order that the
instantaneous and timed phased units reset.
❑ Phase underV drop out (%). Indicates the pickup setting percentage above which the voltage must rise in order that the
instantaneous and timed phased units reset.
❑ 3V2 drop out (%). Indicates the pickup setting percentage below which the voltage must fall in order that the
instantaneous and timed V2 units reset.
❑ 3VO drop out (%). Indicates the pickup setting percentage below which the voltage must fall in order that the
instantaneous and timed VO units reset.
❑ 3VO Operating quantity. Indicates the measurement used for the VO overvoltage:
Calculated: The 3 V0 measurement is used, i.e., the vector sum of the 3 ground to earth phases. 3V0=Va+Vb+Vc
Measured: The measurement from the transformer configured as Vn is used.
❑ Trip Permission by recloser. Indicates the trip and block permission in accordance with the recloser status: standby,
blocked, safety time after reclosing, after closing. It is configured bit by bit; for additional details, see section
corresponding to the recloser (3.12.6.3).
❑ Enable Events record. Allows the generation of protection events associated to the function. If set to “NO”, the function’s
protection events are not generated. If set to “YES”, the function’s specific mask is contemplated.
The timed unit can be configured with a minimum of response time, that is, a limit that prevents any unit from tripping below a
minimum time when the trip time corresponding to the curve in use is met. This avoids timed trips which are quicker than the
instantaneous trips. It is configured with additional time setting, so that if it set to zero, there is no such limit.
❑ Delay/minimum time (ms). It has a different functionality depending on the type of curve selected:
❑ When the selected curve is a definite time, it indicates the time during which the conditions for the tripping of the function
must be met.
❑ In the rest of the curve, it indicates the minimum response time. i.e., in order for a trip to be produced, the time used will
be greater between this setting and the time associated to the curve.
❑ Blocking Input. Selects the signal which, when active, blocks the function.
❑ General trip. Indicates if this unit produces general trip or not. For additional details, see the section corresponding to the
recloser (3.12.6).
❑ Trip Permission by recloser. Indicates the trip and block permission in accordance with the recloser status: standby,
blocked, safety time after reclosing, after closing. It is configured bit by bit; for additional details, see section
corresponding to the recloser (3.12.6.3).
❑ Enable Events record. Allows the generation of protection events associated to the function. If set to “NO”, the function’s
protection events are not generated. If set to “YES”, the function’s specific mask is contemplated.
The return percentage can be configured by the user in the PROT/PVGE1 node.
3.4.2.1 Instantaneous
There are 2 independent units for each of the phases.
The setting “Operation type” allows for a selection to be made from among the following:
❑ “Vphase-ground FUND”. Acts with the phase-ground voltage and fundamental value without harmonics.
❑ “Vphase-phase FUND”. Acts with the phase-phase voltage and fundamental value without harmonics.
❑ “Vphase-ground RMS”. Acts with the phase-ground voltage and rms value with harmonics.
❑ “Vphase-phase RMS”. Acts with the phase-phase voltage and rms value with harmonics.
❑ “Standard”. Acts with the phase-ground voltage and fundamental value without harmonics.
If the PROT/TVTR voltage phase setting indicates that at least one of the phase-phase voltage options, the operation type can
only be selected as VFAs-phase Fund or Vphase-phase RMS. If any other type is selected, the unit will correct itself internally.
Each of the three units has independent settings, commands and outputs.
❑ Nodes:
Unit 1: PROT/PIOV1
Unit 2: PROT/PIOV2
❑ Settings and logical inputs. There are 6 settings tables. For details, see Table 65.
❑ Commands:
“DOrdBlk”: Function blocking and unblocking. Only acts when the function is enabled.
❑ Outputs: Table 67 shows the function’s output data
IOV1 Start phase X. Indicates that the unit's phase has picked up. It is independent for each phase. Where X is the
phase.
IOV1 Trip phase X. Indicates that the unit's phase has tripped. It is independent for each phase. Where X is the phase.
IOV1 Phase Status. Indicates the function’s status. It is active when enabled and not blocked. This is general for all
three phases.
IOV1 phase Start. Indicates that the unit has picked up
IOV1 phase Trip. Indicates that the unit has tripped.
Table 67 Instantaneous phase overvoltage function outputs
3.4.2.2 Timed
There is a single timed unit, which is independent for each of the phases.
The setting “Operation type” allows for a selection to be made from among the following:
❑ “Vphase-ground FUND”. Acts with the phase-ground voltage and fundamental value without harmonics.
❑ “Vphase-phase FUND”. Acts with the phase-phase voltage and fundamental value without harmonics.
❑ “Vphase-ground RMS”. Acts with the phase-ground voltage and rms value with harmonics.
❑ “Vphase-phase RMS”. Acts with the phase-phase voltage and rms value with harmonics.
❑ “Standard”. Acts with the phase-ground voltage and fundamental.
If the PROT/TVTR voltage phase setting indicates that at least one of the phase-phase voltage options, the operation type can
only be selected as VFAs-phase Fund or Vphase-phase RMS. If any other type is selected, the unit will correct itself internally.
❑ Nodes: PROT/PTOV1
❑ Settings and logical inputs. There are 6 settings tables. For details, see Table 66.
❑ Commands:
“DOrdBlk”: Function blocking and unblocking. Only acts when the function is enabled.
❑ Outputs: Table 68 shows the function’s output data
TOV Start phase X. Indicates that the unit's phase has picked up. It is independent for each phase. Where X is the
phase.
TOV Trip phase X. Indicates that the unit's phase has tripped. It is independent for each phase. Where X is the phase.
TOV Phase Status. Indicates the function’s status. It is active when enabled and not blocked. This is general for all three
phases.
TOV1 phase Start. Indicates that the unit has picked up
TOV1 phase Trip. Indicates that the unit has tripped.
❑ The measurement used between Vn transformer measurement or the vector sum of the three voltage phases (3 V0).
❑ The return percentage is user-configurable (PVGE1).
The setting “Operation type” is not used, as the fundamental frequency measurement is always used.
3.4.3.1 Instantaneous
There is one unit.
❑ PROT/GPIOV1 node
❑ Settings and logical inputs. There are 6 settings tables. For details, see Table 64 and Table 65.
❑ Commands:
“DOrdBlk”: Function blocking and unblocking. Only acts when the function is enabled.
❑ Outputs: Table 69 shows the function’s output data
3.4.3.2 Timed
There is one timed unit.
❑ Nodes: PROT/GPTOV1
❑ Settings and logical inputs. There are 6 settings tables. For details, see Table 65 and Table 58.
❑ Commands:
“DOrdBlk”: Function blocking and unblocking. Only acts when the function is enabled.
❑ Outputs: Table 70 shows the function’s output data.
GTOV1 Start. Indicates that the unit has picked up.
GTOV1 Trip. Indicates that the unit has tripped.
TOV (V0) Status. Indicates the function’s status. It is active when enabled and not blocked.
Table 70 Timed zero sequence overvoltage function outputs
The calculation of the sequence takes into phase succession order setting (ABC/ACB).
The return percentage can be configured by the user in the PROT/PVGE1 node.
The setting “Operation type” is not used, as the fundamental frequency measurement is always used.
3.4.4.1 Instantaneous
There is one unit.
❑ Node: PROT/UNPIOV1
❑ Settings and logical inputs. There are 6 settings tables. For details, see Table 64 and Table 65.
❑ Commands:
“DOrdBlk”: Function blocking and unblocking. Only acts when the function is enabled.
❑ Outputs: Table 71 shows the function’s output data.
UNIOV1 Start. Indicates that the unit has picked up.
UNIOV1 Trip. Indicates that the unit has tripped.
IOV V2 Status. Indicates the function’s status. It is active when enabled and not blocked.
Table 71 Instantaneous V2 overvoltage function outputs
3.4.4.2 Timed
There is one timed unit.
❑ Node: PROT/UNPTOV1
❑ Settings and logical inputs. There are 6 settings tables. For details, see Table 66 and Table 64.
❑ Commands:
“DOrdBlk”: Function blocking and unblocking. Only acts when the function is enabled.
❑ Outputs: Table 72 shows the function’s output data.
UNTOV1 Start. Indicates that the unit has picked up.
UNTOV1 Trip. Indicates that the unit has tripped.
TOV V2 Status. Indicates the function’s status. It is active when enabled and not blocked.
Table 72 Timed V2 overvoltage function outputs
The return percentage can be configured by the user in the PROT/PVGE1 node.
3.4.5.1 Instantaneous
There are 2 independent units for each of the phases.
The setting “Operation type”allows for a selection to be made from among the following:
Each of the three units has independent settings, commands and outputs.
❑ Nodes:
Unit 1: PROT/PIUV1
Unit 2: PROT/PIUV2
❑ Settings and logical inputs. There are 6 settings tables. For details, see Table 65 and Table 64.
❑ Commands:
“DOrdBlk”: Function blocking and unblocking. Only acts when the function is enabled.
❑ Outputs: Table 73 shows the function’s output data.
IUV1 Start phase X. Indicates that the unit's phase has picked up. It is independent for each phase. Where X is the
phase.
IUV1 Trip phase X. Indicates that the unit's phase has tripped. It is independent for each phase. Where X is the phase.
IUV1 Phase Status. Indicates the function’s status. It is active when enabled and not blocked. This is general for all
three phases.
IUV1 phase Start. Indicates that the unit has picked up
IUV1 phase Trip. Indicates that the unit has tripped.
Table 73 Instantaneous phase undervoltage function outputs
3.4.5.2 Timed
There is a single timed unit, which is independent for each of the phases.
The setting “Operation type” allows for a selection to be made from among the following:
❑ Nodes: PROT/PTUV1
❑ Settings and logical inputs. There are 6 settings tables. For details, see Table 65and Table 58.
❑ Commands:
“DOrdBlk”: Function blocking and unblocking. Only acts when the function is enabled.
❑ Outputs: Table 74 shows the function’s output data
TUV1 Start phase X. Indicates that the unit's phase has picked up. It is independent for each phase. Where X is the
phase.
TUV1 Trip phase X. Indicates that the unit's phase has tripped. It is independent for each phase. Where X is the phase.
TUV Phase Status. Indicates the function’s status. It is active when enabled and not blocked. This is general for all three
phases.
TUV1 phase Start. Indicates that the unit has picked up
TUV1 phase Trip. Indicates that the unit has tripped.
With the "General Trip" setting, the breaker opening command can be generated. The trip generated by this unit is not reclosabled.
In the 52 ½ configuration, two units are available, one for each synchronism voltage (Vs1 and Vs2). In both units the voltage of the
A side is the one selected in the synchronism (node RSYN):
Outputs: Table 76 shows the function’s output data of the two units. The signals are the same for both units
❑ Low voltage status U1. Indicates the function’s status. It is active when enabled and not blocked.
❑ VSPIUV Start A – U1. Indicates that the voltage on the A side is below the “Threshold A” setting.
❑ VSPIUV Start B – U1. Indicates that the voltage on the B side is below the “Threshold B” setting.
❑ VSPIUV Start U 1. Indicates that the voltage of both sides is below the threshold setting.
❑ VSPIUV Trip U 1. Indicates that the voltage of both sides is below the threshold setting during the “Delay time” setting.
Each unit has blocking commands:
❑ “DOrdBlk”: Function blocking and unblocking. Only acts when the function is enabled.
The frequency is measured each cycle and refreshed each half cycle, as shown in Figure 79.
The voltage used in the frequency measurement is calculated as "2·Va-Vb-Vc". The algorithm is executed in the event of the voltage
registering zero. The frequency is calculated if the voltage measurement is greater than 2.5V.
Both the positive and negative registers are measured, although the frequency measurement is carried out for complete cycles.
3.5.1 Frequency
This function is composed of 8 steps, which are programmable as maximum or minimum frequencies.
The function’s node, PROT/PTGF1, has independent settings for each step and common settings for all.
❑ Minimum voltage (V). Indicates the minimum voltage value below which the frequency protection does no act, the unit is
not permitted to pickup.
❑ Number of cycles (Start). Indicates the number of cycles during which the frequency conditions necessary for the unit to
pickup must be met.
❑ Number of cycles (Reset). Indicates the number of cycles during which the drop conditions necessary for the unit to reset
must be met in the event of the unit's not having tripped.
❑ OverFreq. Reset time (ms). Once tripped by overfrequency, this is the time during which the reset conditions must be met
in order to clear the trip from the unit. It is applied to all the steps configured as overfrequency.
❑ UnderFreq. Reset time (ms). Once tripped by underfrequency, this is the time during which the reset conditions must be
met in order to clear the trip from the unit. It is applied to all the steps configured as underfrequency.
❑ General trip. Indicates if this unit produces general trip or not. For additional details, see the section corresponding to the
recloser (3.12.6).
❑ Trip Permission by recloser. Indicates the trip and block permission in accordance with the recloser status: standby,
blocked, safety time after reclosing, after closing. It is configured bit by bit; for additional details, see section
corresponding to the recloser (3.12.6.3).
❑ Enable Events record. Allows the generation of protection events associated to the function. If set to “NO”, the function’s
protection events are not generated. If set to “YES”, the function’s specific mask is contemplated.
The independent settings for each of the 8 steps are:
❑ Minimum frequency. Each step picks up when the frequency falls below the set value during a number of cycles equal or
higher than the “No. of pickup cycles” setting. Once it picks up, the programmed time must elapse in order for a trip to be
produced. If the unit has tripped, it drops out if the frequency is correct during the underfrequency reset time. If it has
picked up but has not tripped, it drops out if the frequency is correct during reset cycles.
❑ Maximum frequency. Each step picks up when the frequency exceeds the set value during a number of cycles equal or
higher than the “No. of pickup cycles” setting. Once it picks up, the programmed time must elapse in order for a trip to be
produced. If the unit has tripped, it drops out if the frequency is correct during the overfrequency reset time. If it has
picked up but has not tripped, it drops out if the frequency is correct during reset cycles.
There are settings, commands and outputs.
❑ Nodes: PROT/PTGF1
❑ Settings and logical inputs. There are 6 settings tables. For details, see Table 77.
❑ Commands:
“DOrdBlk”: Function blocking and unblocking. It only acts on the enabled steps. If acts on the 8 steps
“DOrdFminB”. Blocking and unblocking of the steps configured as minimum frequency. It only acts on the enabled
steps.
“DOrdFmaxB”. Blocking and unblocking of the steps configured as maximum frequency. It only acts on the enabled
steps.
“DOrdFL1Bl”. Blocking and unblocking of step 1. It only acts if the step is enabled
“DOrdFL2Bl”… “DOrdFL8Bl”. As above, but acts on steps 2 to 8.
❑ Outputs: Table 78 shows the function’s output data. They are independent for each step
Level X Frequency Start. Indicates that the step has picked up. It is independent for each step.
Level X Frequency Trip. Indicates that the step has tripped. It is independent for each step.
Level X Frequency Status. Indicates the step’s status. Active when enabled and not blocked. Independent for each step.
The function’s node, PROT/PFRC1, has independent settings for each step and common settings for all.
❑ Supervision f max. Indicates the maximum frequency above with the frequency rate of change is not measured.
❑ f start value (Hz/s). Indicates the frequency variation value at which the function is activated.
❑ Delay time (ms). Indicates the time during which the conditions for the tripping of the function must be met.
❑ Trip lock. Selects the signal which, when active, locks the activation of the function; so, once activated, the signal is kept
until the lock signal and the rate of change signal are deactivated.
There are settings, commands and outputs.
❑ Nodes: PROT/PFRC1
❑ Settings and logical inputs. There are 6 settings tables. For details, see Table 79.
❑ Commands:
“DOrdBlk”: Function blocking and unblocking. It only acts on the enabled steps. If acts on the 8 steps
❑ Outputs: Table 80 shows the function’s output data. They are independent for each step
ROCOF df/dt Status. It is active when enabled and not blocked. Common for all steps.
Level X df/dt Start. Indicates that the step has picked up. It is independent for each step. Where X indicates the level
from 1 to 8.
Level X df/dt Trip. Indicates that the step has tripped. It is independent for each step. Where X indicates the level from
1 to 8.
General operation.
The function is only effective for frequencies inferior to a threshold called “maximum monitoring frequency”, currents greater than
the threshold called “minimum current” and voltages greater than the minimum monitoring threshold:
❑ Minimum monitoring current. The maximum phase current is compared to this setting. If the minimum current circulating
in all the phases is inferior to the setting, the frequency rate of change unit is not allowed to pickup. When a current is
greater than the set threshold appears in at least one of the phases, the relay waits for 10 cycles before running the
frequency rate of change function.
❑ Minimum monitoring voltage. If the phase B voltage is inferior to the setting, the frequency rate of change unit is not
allowed to pickup. When the voltage exceeds the set threshold, the relay waits for 10 cycles before running the frequency
rate of change function.
The frequency is measured each cycle and reloaded every half cycle, as shown in Figure 79.
The algorithm stores the periods of the signal’s last 4 cycles and calculates the frequency rate of change by comparing the current
cycle’s frequency measurement with the measurement taken from 4 cycles previously, taking into account the time lapse between
both (Figure 80).
In which:
f4 =frequency measurement taken 3 cycles previously T4 period of the 4th cycle starting from the end
f3 =frequency measurement taken 2 cycles previously T3 period of the 3rd cycle starting from the end
f2 =frequency measurement taken 1 cycle previously T2 period of the 2nd cycle starting from the end
This calculation is repeated, taking into account the measurements separated by two cycles in order to ensure that the frequency
has fallen during the entire period, i.e., to ensure that an incorrect measurement does not lead to a trip. Two checks are carried
out:
❑ the measurement of the current cycle against that of the cycle minus two cycles
df/dt2 = (fn − fn − 4)/(tn − tn − 4)
❑ the measurement of the cycle minus two cycles against that of the cycle minus four cycles
df/dt3 = (fn − 4 − fn − 8)/(tn − 4 − tn − 8)
Figure 80 Frequency rate of change calculation
For the unit to pickup, the frequency rate of change must be exceeded by an absolute value during the set number of cycles. The
pickup is only produced if the frequency rate of change/voltage rate of change value meets the criterion selected in the setting
“Operation type”:
❑ Negative. The frequency rate of change/voltage rate is negative, i.e., when the current frequency is inferior to that
measured 4 cycles previously.
❑ Positive. The frequency rate of change/voltage rate is positive, i.e., when the current frequency is greater than that
measured 4 cycles previously.
❑ Negative and Positive. Acts on frequency rate of change/voltage rate in both directions.
During the pickup process, one measurement is allowed to be out of the pickup range without restarting the process. For example,
if 3 cycles are required to cause a pickup, the threshold need only be exceeded 3 times from a total of 4 consecutive
measurements.
In order for a trip to occur once the unit has picked up, the frequency rate of change measurement must remain between the set
frequency rate of change/voltage rate of change value and a reset value to the frequency rate of change/voltage rate of change
minus 0.05Hz/s during the set time.
In order for the unit to reset once it has picked up, the frequency rate of change/voltage rate of change measurement must be
detected as being 0.05Hz/s below the set value during the number of cycles programmes as reset cycles.
In order for the unit to reset once it has tripped, the frequency rate of change/voltage rate of change measurement must be
detected as being 0.05Hz/s below the set value during the reset time. Any sealing signals that have been configured must register a
value of zero in order for the trip to be deactivated.
3.6.1 General
Using the voltage and current measurements, the real and reactive powers and the power factor are calculated. The values
obtained are used for the power protection functions.
The trip thresholds are programmed as a percentage of the rated apparent power, S = 3 · V · I, in which:
❑ P reset threshold (%). Indicates the reset threshold for the real power units.
❑ Q reset threshold (%). Indicates the reset threshold for the reactive power units.
❑ S reset threshold (%). Indicates the reset threshold for the apparent power units.
Table 81 Power units reset settings
The power units’ settings are similar to each other. Each unit has independent settings:
❑ Delay time (ms). Indicates the time during which the conditions for the tripping of the function must be met.
❑ Blocking Input. Selects the signal which, when active, blocks the step.
❑ General trip. Indicates if this unit produces general trip or not. For additional details, see the section corresponding to the
recloser (3.12.6).
❑ Trip Permission by recloser. Indicates the trip and block permission in accordance with the recloser status: standby,
blocked, safety time after reclosing, after closing. It is configured bit by bit; for additional details, see section
corresponding to the recloser (3.12.6.3).
❑ Enable Events record. Allows the generation of protection events associated to the function. If set to “NO”, the function’s
protection events are not generated. If set to “YES”, the function’s specific mask is contemplated.
Table 82 Power unit settings
The settings, commands and outputs available are similar in all the units, with the exception of the node:
It provides protection against excessive decreases in the generated power. It compares the real power with the minimum power
given by the setting. In the event of the generated power being inferior to the power established in the setting during the
programmed time, the protection trips the corresponding relay. Any reverse power will be considered as below the minimum
power threshold and will thus activate the function.
In order to reset, the power must exceed the pickup threshold plus the reset percentage. For example, if the reset percentage is set
at 2%, the unit will reset if the power exceeds the 102% of the pickup threshold.
The settings, commands and outputs available are indicated in section 3.6.1.
PDUP1 Signals Data (Edition 1) Attribute (Edition 1) Data (Edition 2) Attribute (Edition 2)
Minimum P Start Str stVal Str general
Minimum P Trip Op stVal Op general
Minimum P Status StEna stVal StEna stVal
It provides protection against excessive increases in the power generated. It compares the real power with the maximum power
given by the setting. In the event of the generated power being greater than the power established in the setting during the
programmed time, the protection trips the corresponding relay.
In order to reset, the power must be inferior to the pickup threshold less the reset percentage. For example, if the reset percentage
is set at 2%, the unit will reset if the power is inferior to 98% of the pickup threshold.
The settings, commands and outputs available are indicated in section 3.6.1.
PDOP1 Signals PDOP2 Signals Data (Edition 1) Attribute (Edition 1) Data (Edition 2) Attribute (Edition 2)
High Maximum P Start Low Maximum P Start Str stVal Str general
High Maximum P Trip Low Maximum P Trip Op stVal Op general
Maximum P Level 1 Status Maximum P Level 2 Status StEna stVal StEna stVal
The protection is activated when the real power flow is inverted (motorization of generators).
In order to act, the real power must be negative; in the event of the real power exceeding the set value during the programmed
time, the protection trips the corresponding relay.
In order to reset, the power must be inferior to the pickup threshold less the reset percentage.
For example, if the threshold is set at 100W, the unit will pickup as of a measured power of -100w. If the reset percentage is set at
2%, the unit will reset when the power is below -98W (98% of set value).
The settings, commands and outputs available are indicated in section 3.6.1.
PDOP3 Signals PDOP4 Signals Data (Edition 1) Attribute (Edition 1) Data (Edition 2) Attribute (Edition 2)
High P Inversion Start Low P Inversion Start Str stVal Str general
High P Inversion Trip Low P Inversion Trip Op stVal Op general
P Inversion Level 1 Status P Inversion Level 2 Status StEna stVal StEna stVal
The protection is activated when the reactive power flow is inverted (field loss in generators).
In order to act, the reactive power must be negative; in the event of the real power exceeding the set value during the
programmed time, the protection trips the corresponding relay.
In order to reset, the power must be inferior to the pickup threshold less the reset percentage.
For example, if the threshold is set at 100W, the unit will pickup as of a measured power of -100w. If the reset percentage is set at
2%, the unit will reset when the power is below -98W (98% of set value).
The settings, commands and outputs available are indicated in section 3.6.1.
PDOP5 Signals PDOP6 Signals Data (Edition 1) Attribute (Edition 1) Data (Edition 2) Attribute (Edition 2)
High Q Inversion Start Low Q Inversion Start Str stVal Str general
High Q Inversion Trip Low Q Inversion Trip Op stVal Op general
Q Inversion Level 1 Status Q Inversion Level 2 Status StEna stVal StEna stVal
It provides protection against excessive decreases in the power generated. It compares the apparent power with the minimum
power given by the setting. In the event of the generated power being inferior to the power established in the setting during the
programmed time, the protection trips the corresponding relay.
In order to reset, the power must exceed the pickup threshold plus the reset percentage. For example, if the reset percentage is set
at 2%, the unit will reset if the power exceeds the 102% of the pickup threshold.
The settings, commands and outputs available are indicated in section 3.6.1.
It provides protection against excessive increases in the power generated. It compares the apparent power with the maximum
power given by the setting. In the event of the generated power being greater than the power established in the setting during the
programmed time, the protection trips the corresponding relay.
In order to reset, the power must be inferior to the pickup threshold less the reset percentage. For example, if the reset percentage
is set at 2%, the unit will reset if the power is inferior to 98% of the pickup threshold.
The settings, commands and outputs available are indicated in section 3.6.1.
PDOP7 Signals PDOP8 Signals Data (Edition 1) Attribute (Edition 1) Data (Edition 2) Attribute (Edition 2)
High Maximum S Start Low Maximum S Start Str stVal Str general
High Maximum S Trip Low Maximum S Trip Op stVal Op general
Maximum S Level 1 Status Maximum S Level 2 Status StEna stVal StEna stVal
This unit specifies a functioning zone in which the phase-phase units of the distance functions are blocked (mho and quadrilateral).
Figure 82 shows this unit's diagram.
For the operation of the load encroachment, the following conditions must be fulfilled:
❑ Node: PROT/PLEC1
❑ Settings and logical inputs. There are 6 settings tables. For details, see Table 90.
❑ Commands:
“DOrdBlk”: Function blocking and unblocking. Only acts when the function is enabled.
❑ Outputs: Table 91 shows the function's output data.
Load Encroachment. Indicates that the unit is active.
Load Encroachment Status. Indicates the function’s status. It is active when enabled and not blocked.
6
Since DSP version 4.0 phase-phase impedance is used. Previoues versions use positive sequence impedance.
The measurement obtained from the half-cycle DFT is used to obtain results before the protection units are activated.
❑ The three breakers are closed. (Open pole detector). Signals "Open pole (1 or 2)" and "3 open poles" of the scheme. If the open
pole detector is disabled, the three poles are considered closed.
❑ I1 positive sequence current is greater than 5% of the rated current. 7
❑ The increase in I1 positive sequence and the IN neutral current in relation to the current measured 1 cycle previously must be less
than 0.1A for 5A rated current or 0.02A for rated current 1A.
❑ The fault detection unit must be deactivated (Fault detection signal of the scheme).
❑ Distance units (mho or quadrilateral) and/or overcurrent units (phase, ground, earth system and unbalanced) have not picked up.
❑ The angle difference between currents I1 and I0 and those of 1 cycle previous are less than 5º.
❑ The V1 positive sequence voltage, memorized 1 cycle previously, must exceed VFF and drop below 95% of VFF,
VFF = VN · 80% (V)
If the function detects all the above conditions, or if the “Fuse Failure input” is activated, a fuse failure pickup signal is produced and
used to block the units in question (configurable).
These conditions must be met during a programmable time in order for the fuse failure trip to be activated. Once tripped, the fuse fault
is maintained until the V1 voltage rises above VFF.
If any of the overcurrent functions (phase, ground, earth system and unbalanced) or distance units have picked up or if during the
timeout the relay picks up at least one of these units, the fuse failure output is not activated as the situation is considered a fault, not a
fuse failure.
7
From firmware version 5.19.15.7 and ICD version 6.3.1.4 can be set. In previous versions, it was fixed 5%.
The fuse failure pickup and trip are also activated when the digital “Fuse Fail input” is activated independently of the programmed
time. The fuse failure is only deactivated when the input is deactivated.
If the “Fuse Fail input” input is activated, the synchrocheck unit is deactivated.
The fuse failure pickup can be used as a blocking signal for other functions by means of each function’s logic signals.
The overcurrent units have settings that configure their functioning in the event of a fuse failure, allowing the enabling of the function,
the inhibition of directional, etc.
❑ Node: PROT/RFUF1
❑ Settings and logical inputs. There are 6 settings tables. For details, see Table 92.
❑ Commands:
“DOrdBlk”: Function blocking and unblocking. Only acts when the function is enabled.
❑ Outputs: Table 93 shows the function’s output data.
Fuse Failure Start. Indicates that the fuse failure has picked up.
Fuse Failure Trip. Indicates that the fuse failure has tripped, that is, the additional time has elapsed with the unit picked up.
Fuse Failure B1 Activation. Indicates that fuse failure is activated on breaker 1’s synchronism B side.
Fuse Failure B2 Activation. Indicates that fuse failure is activated on breaker 2’s synchronism B side.
Fuse Failure Status. Indicates the function’s status. It is active when enabled and not blocked.
This unit determines the function conditions according to which distance function trips is disabled for single-phase and/or phase-phase
units and for each zone, depending on the settings.
❑ Stable swing: when distance functions can be blocked by generating the "Power Swing Blocked" signal.
❑ Unstable swing: when some system elements can be tripping to prevent the disturbance extending. To do this, this
function generates the "OST- Out of Step Tripping" signal.
To determine swinging conditions, the complete positive sequence impedance is used (for 3 closed poles) or the minimum impedance
of phase (A, B, C) or phase combination (AB, BC or CA) of the closed poles (if there is 1 open pole). By calculating the position of this
impedance in the R/X diagram, it is possible to measure how and at what speed it is moving. To do this, on the one hand, some zones
are defined in the diagram, and on the other some transfer times from one zone to another are defined. These zones and times are
parameterised by settings.
Figure 86 shows this unit's logic diagram. On the one hand, it shows the "PSB" signal's activation conditions and on the other, the "OST"
signal's activation conditions.
"Power Swing Blocking" (PSB) is activated when any of the following conditions is fulfilled:
❑ The positive sequence impedance takes a time longer than the "Blocking Time (ms)" (setting) to pass from the outside
zone to the middle zone and the unblocking signal is not activated (See Figure 84).
❑ The positive sequence impedance goes into the middle zone and the time between going from the outside zone to the
middle zone is longer than the "Trip Time (ms)" (setting) and shorter than the "Blocking Time (ms)" (setting) and the
unblocking signal is not activated. In this case the trip must be enabled and not blocked (See Figure 84).
If the 3 poles are closed, blocking only affect the phase-phase units. With 1 pole open, blocking affects all single- and phase-phase
units. The breaker status is determined by digital inputs.
Once activated, the "PSB" signal is maintained for 2 seconds as long as no unblocking conditions are fulfilled and that it is inside the
outer zone. If the "Memory Enabled" setting is "YES", blocking will last 1 second once outside the outer zone. If it is "NO", there is no
blocking once outside the outer zone.
Each of the zones, for both the Mho and Quadrilateral characteristics can be blocked or unblocked by this function depending on the
setting selection: "Zone 1 Blocking"…"Zone 5 Blocking".
It is also possible to block the teleprotection using the setting "Teleprotection Blocking" so that TPR reception and TPT transmission is
ignored.
The activation of "Trip by Power Swing" (OST) is determined depending on the "Trip Enabled" setting. If this setting is "NO", the trip is
never activated.
❑ The positive sequence impedance goes into the middle zone and the time between going from the outside zone to the
middle zone is longer than the "Trip Time (ms)" (setting) and shorter than the "Blocking Time (ms)" (setting).See Figure 84.
❑ The unblocking signal is not activated.
If the setting is OUT_ZMED, the conditions for activation are as follows:
❑ If the case is as above (the positive sequence impedance enters the middle zone and the time it takes to go from the outer
zone to the middle zone is greater than "Trip Time (ms)" and less than "Blocking Time (ms)", the impedance leaves the
middle zone through the opposite side to where it entered. See Figure 84.
❑ When the previous condition is fulfilled, if the time set in "Trip delay" is grather than zero, the activation is when the set
time has elapsed since the impedance has left all the zones and has not re-entered in any of they. If the set time is zero,
the previous condition is enough.
❑ The unblocking signal is not activated.
The unblocking signal is activated if any of the following conditions is fulfilled:
❑ The positive sequence threshold is less than "I1 Minimum threshold (A)" (setting).
88
Until the version 8.1.0.0 of ICD the name was " Distance between zones "
❑ Node PROT/RPSB1
❑ Settings and logical inputs. There are 6 settings tables. For details, see Table 94.
❑ Commands:
“DOrdBlk”: Function blocking and unblocking. Only acts when the function is enabled.
"DOrdOpBlk": Blocking and unblocking of the trip by power swing. Only applicable if the "Trip Enabled" setting is not
set to "NO".
❑ Outputs: Table 95 shows the function's output data.
Z1 Ph-Ph Blocked PSB. Indicates blocking of the phase-phase units in zone 1.
….. Same for zones 2 to 5.
Z1 Gnd Blocked PSB. Indicates blocking of the single-phase units in zone 1.
….. Same for zones 2 to 5.
Teleprotection blocked PSB. Indicates that the teleprotection is blocked by the power swing.
Power swing blocked. Time conditions are fulfilled when passing from the outer zone to the middle zone without
detecting a fault.
Power swing Trip. Trip signal by power swing.
Power swing unblocked. Blocking reset by power swing.
PSB unblocked internal zone. The impedance has stayed in the inner zone for the time indicated in the "Inner zone
unblocking time" and no other unblocking conditions have been fulfilled.
Z in ZMED+. The impedance seen is in the middle zone positive. The impedance has a positive resistive component.
Z in ZMED-. The impedance seen is in the middle zone negative. The impedance has a negative resistive component.
Z in Middle zone. The impedance seen is in the middle zone.
Z in External zone. The impedance seen is in the external zone.
Z in Internal zone. The impedance seen is in the internal zone.
Power swing status. Indicates whether or not the power swing function is enabled.
Power swing trip status. Indicates whether or not the trip power swing function is enabled.
This unit provides an instantaneous three-phase trip when a fault occurs upon the generation of a breaker closure command (manual
or by input).
The function is enabled during a programmable time ("Activation time (ms)") in the following situations:
Programmed as “V and I" or "(V and I) or Z2”: The phase voltage is below a threshold (set in the open pole detector) and the
phase current is above a threshold for ½ cycle.
Programmed as “Z2” or “(V and I) or Z2”: The zone 2 of the distance units (mho or quadrilateral) is started.
Programmed as "programmable pick up I": The Programmable SOTF Pick up input is activated.
During the "Activation time (ms)" that the function is enabled, an offset of 0.1 ohms is applied to the mho characteristic in zone 2. On
the other hand, the X reach is set to 0.05 ohms, contrary to the programmed direction, in the quadrilateral characteristic in zone 2.
Therefore, the three - phase faults are protected in the origin. Also, the directional supervision is not used and both directions are
allowed.
Depending on the configuration set the switch onto fault can be active with any closing. 9
❑ To enable it after a manual closing and to produce a definitive trip (no reclosing allowed):
Reclose perm. (R1, R2, R3, R4): NO.
Trip permission by recloser: Only "Recloser lockout" and "Trip permission after manual closing" have to be selected.
❑ To enable it after any closing and to produce a definitive trip (no reclosing allowed):
Reclose perm. (R1, R2, R3, R4): NO.
Trip permission by recloser: Select "Recloser lockout" and the desired trip permissions.
❑ To allow reclosings:
Reclose perm. (R1, R2, R3, R4): Select the desired option.
Trip permission by recloser: Do not select "Recloser lockout" and select the desired trip permissions.
The function’s settings are:
❑ Node: PROT/PSOF1
❑ Settings and logical inputs. There are 6 settings tables. For details, see Table 96.
9
Available from firmware version 5.19.15.7 and ICD version 6.1.13.27 on. Until that version only acts with manual closings.
10
Available from firmware version 6.2.19.20 and ICD version 8.8.1.0
❑ Commands:
“DOrdBlk”: Function blocking and unblocking. Only acts when the function is enabled.
❑ Outputs: Table 97 shows the function’s output data.
Switch onto Fault Activation. Indicates that the switch onto fault has been activated.
Switch onto Fault Status. Indicates the function’s status. It is active when enabled and not blocked.
11
Available from firmware version 6.2.19.20 and ICD version 8.8.1.0
If a fault is detected, it is important to act quickly and for the switch to work correctly. However, it may be that an error occurs and it is
not able to interrupt the fault current.
The breaker failure function checks that there is no current via the switch, for a given time after the trip situation. If it is detected that
the current continues to be above a value established by the setting, a signal is activated so that secondary switches can act.
❑ If the equipment indicates a trip signal or an external protection signal is received via a logic input, depending on the
value of the "Start type" setting, it will heed to one or the other to start up a timer.
❑ If the trip situation disappears or the function is tripping or starting externally, to verify this, the "Time signal relapse
(ms)" must elapse.
❑ If, following the period programmed as “Retrip time delay (ms)”, the current of one of the phases exceeds the
programmed "Phase current threshold (A)", the retrip signal is activated.
❑ If the "52 Supervision" setting is "YES", if, following the period programmed as “Retrip time delay (ms)” one of the poles
remains closed, after that time, the retrigger signal and the retrigger signal of that pole are activated.
❑ If, following the period programmed as “Trip time delay (ms)”, the current of one of the phases exceeds the programmed
"Phase current threshold (A)", the trip signal is activated.
❑ Regardless of the “Trip time delay (ms)”, if a blocked switch logic input is activated, the trip signal is activated.
❑ If the "Sealed by current" setting is "YES", the signals are only deactivated when the phase and neutral currents fall below
their drop out values.
In this unit, functioning does not contemplate the breaker status digital input, but rather the current values. The measurement
obtained from the half-cycle DFT of the full-cycle DFT is used (the lowest of both).
❑ Nodes:
PROT/FRBRF1. The functions uses the measurements from the transformers 1, 2 and 3 (Ia1, Ib1, Ic1).
PROT/FRBRF2. The functions uses the measurements from the transformers 4, 5 and 6 (Ia2, Ib2, Ic2). Only with 52 1/2
configurations.
❑ Settings and logical inputs. There are 6 settings tables. For details, see Table 98.
❑ Commands:
“DOrdBlk”: Blocks and unblocks the function. Only acts when the function is enabled.
❑ Outputs: Table 99 shows the function's output data.
The settings used by this unit are as follows:
❑ 50BF Retrigger pole A (Br1). Indicates that there has been a retrip due to a breaker failure in phase A.
12
Available from firmware versión 5.18.15.5 and ICDs version 6.1.14.1
❑ 50BF Retrigger pole B (Br1). Indicates that there has been a retrip due to a breaker failure in phase B.
❑ 50BF Retrigger pole C (Br1). Indicates that there has been a retrip due to a breaker failure in phase C.
❑ Retrigger 50BF (Br1). Indicates that there has been a retrip due to a breaker failure in one of the poles.
❑ Time BF completed (Br1). Indicates that the trip signalling timer has finished.
❑ Trip 50BF (Br1). Indicates that there has been a trip due to a switch fault. This means that besides complying with the
timing indicated by "BF time finished", the current that circulates through the switch exceeds the function's activation
threshold.
❑ Start 50BF pole A (Br1). It is activated when the breaker fault conditions for the pole A are met during the set time.
❑ Start 50BF pole B (Br1). It is activated when the breaker fault conditions for the pole B are met during the set time.
❑ Start 50BF pole C (Br1). It is activated when the breaker fault conditions for the pole C are met during the set time.
❑ 50BF Ia exceeded (Br1). Indicates that in the breaker's pole A, the current exceeds the programmed fault detection
threshold.
❑ 50BF Ib exceeded (Br1). Indicates that in the breaker's pole B, the current exceeds the programmed fault detection
threshold.
❑ 50BF Ic exceeded (Br1). Indicates that in the breaker's pole C, the current exceeds the programmed fault detection
threshold.
❑ 50BF In exceeded (Br1). Indicates that in the neutral, the current exceeds the programmed fault detection threshold.
❑ Breaker failure status (Br1). Indicates the function’s status. It is active when enabled and not blocked.
The scheme for phases B and C is the same, replacing phase A with B or C as appropriate.
The unit starts when the breaker status or overcurrent and start signal conditions are fulfilled:
❑ 52 status or overcurrent:
If the "52 Supervision" set to "YES" and any pole is closed. The breaker status is determined with the 52 status digital
inputs.
When enabled “Enable with Ground current”, the neutral current (3I0 for 52 ½ configuration) is greater than the
setting “Gnd current threshold (A)”.
❑ Start signal:
Pole x BF start or 3 pole BF start signal lis received.
If “2 pole trip allowed” is enabled, BF start signal of at least two phases is received.
The setting “Supervision Initial” 13 selects the start mode:
❑ YES. The unit starts when the breaker status or overcurrent conditions are fulfilled and the start signal is activated.
❑ NO. The unit starts when the start signal is activated.
The trip is generated when the “Trip time delay (ms)” finishes and none of the start conditions has been deactivated.
The retrip is generated when the “Retrip time delay (ms)” finishes and none of the start conditions has been deactivated.
If the "Supervision by current" setting is "YES", the retrip and trip signals are only activated when the neutral current is above the
“Gnd current threshold (A)” setting.
If the trip situation disappears or the function is tripping or starting externally, to verify this, the "Time signal relapse (ms)" must
elapse
If the "Sealed by current" setting is "YES", the signals are only deactivated when the neutral current falls below their drop out
values.
In 52 ½ configurations, the function is independent for every breaker, using 3I0 because the neutral measurement is not available.
13
Available from firmware version 6.0.18.2 and ICD version 8.1.0.20
Two independent functions are available (settings, outputs, commands…). Two nodes are used:
❑ Nodes:
PROT/RGBF1. In 52 ½ configurations, the functions uses the measurements from the transformers 1, 2 and 3 (Ia1, Ib1,
Ic1).
PROT/ RGBF2. In 52 ½ configurations, the functions uses the measurements from the transformers 4, 5 and 6 (Ia2, Ib2,
Ic2). Only with 52 1/2 configurations.
❑ Settings and logical inputs. There are 6 settings tables. For details, see Table 100.
❑ Commands:
“DOrdBlk”: Blocks and unblocks the function. Only acts when the function is enabled.
❑ Outputs: Table 101 shows the function's output data.
The settings used by this unit are as follows:
❑ Gnd current threshold (A). Indicates the current value below which the neutral is considered as open.
❑ Retrip time delay (ms). Indicates the waiting time for the activation of the retrip signal if the current does not drop below
the drop out level.
❑ Trip time delay (ms). Indicates the waiting time for the activation of the trip signal if the current does not drop below the
drop out level.
❑ Blocking input. Selects the signal which, when active, blocks the function.
❑ Pole A BF start. Selects the signal which, when activated, indicates the start of breaker failure timing for phase A.
❑ Pole B BF start. Selects the signal which, when activated, indicates the start of breaker failure timing for phase B.
❑ Pole C BF start. Selects the signal which, when activated, indicates the start of breaker failure timing for phase C
❑ 3 pole BF start. Selects the signal which, when activated, indicates the start of breaker failure timing.
❑ Enable Events Record. Allows the generation of protection events associated to the function. If set to “NO”, the function’s
protection events are not generated. If set to “YES”, the function’s specific mask is contemplated.
❑ 52 Supervisión14.If set to YES, the the start of breaker failure can also be activated if the breaker poles are closed.
❑ Sealed by current14. Indicates whether or not the disappearance of the trigger signal causes the function to relapse. In
other words, if the trip signal has to be permanent or simply a pulse.
❑ Time signal relapse (ms)14. Indicates the time for which the start situation is to be maintained, after the disappearance of
the internal trip or input start
❑ Supervision by current13. If set to "YES", the retrip and trip signal are only activated when the neutral current is above the
setting “Gnd current threshold (A)”.
❑ Supervision Initial13. It selects whether the start of the unit is monitored by the status of the breaker and overcurrent or
only the start signal is used.
Table 101 shows the function's output signals:
❑ Retrip BF low load. Indicates that there has been a retrip due to a breaker failure.
❑ Trip BF low load. Indicates that there has been a trip due to a breaker failure.
❑ Start BF low load. It is activated when the breaker fault conditions have happened. If this conditions are activated during
the set time, generate the breaker failure signals.
❑ BF low load status. Indicates the function’s status. It is active when enabled and not blocked.
14
Available from firmware version 6.0.8.0 and ICDs version 8.1.0.4
They are based upon the use of teleprotection signals between both end terminals of the line. The effect upon the output relays’
operation is determined according to the signals given by the protection along with the signals given by the other terminal.
From firmware version 6.0.8.0 and ICD version 8.1.0.4, there is a new setting: "TPTx Delay time (ms)".
From firmware version 6.0.8.0 and ICD version 8.1.0.4, in the 67NQ teleprotection schemes, single pole trips are allowed. The
“Single Pole Trip 67NQ” setting must be set to “YES” in the node PROT/ZPMPT (see chapter "Single pole Trip") and the phase
selector must indicate single phase to ground fault (see chapter "Phase selector").
3.12.1.1 Introduction
3.12.1.1.1 Fault Detection Units
Teleprotection 67NQ scheme will operate on the instantaneous directional unit No. 1 (forward), 2 (forward) and 3 (backwards).
❑ Zone 1 (forward): Unit 1 with instantaneous, unbalanced and neutral overcurrent (UNPIOC1 and GPIOC1).
❑ Zone 2 (forward): Unit 2 with instantaneous, unbalanced and neutral overcurrent (UNPIOC2 and GPIOC2).
❑ Zone 4 (backwards): Unit 3 with instantaneous, unbalanced and neutral overcurrent (UNPIOC3 and GPIOC3).
Therefore, unit 1 can be assimilated to distance zone 1, unit 2 to zone 2, and unit 3 to zone 4. Unit 3 must be programmed
backwards.
❑ Blocking schemes: The signal received indicates that the fault is outside the protected zone. A relay can trip on an
overreaching zone if, after a definite time, the blocking signal has not been received.
❑ Permissive schemes: The signal received allows an instantaneous trip in the overreaching zone. The additional ECHO,
weak infeed and Current Reversal Blocking schemes can be used.
When selecting a particular scheme, it is useful to bear in mind the following characteristics for each of them: In the case of an
internal fault in the protected line and a communication channel fault in permissive schemes, protection is disabled for tripping,
whilst in blocking schemes, tripping is assured. However, in blocking schemes, if there is an external fault and a communication
channel fault, the device can trip.
If the communication system forms an integral part of the energy transport line, as in the case of carrier waves, it is best to use the
blocking schemes, since internal faults may disturb or attenuate the carrier signal. Likewise, it is best to use blocking schemes in
weak infeed configurations as they are more reliable compared to permissive schemes.
Finally, it should be mentioned that permissive schemes are faster than blocking schemes, given that the latter involve slightly
longer fault clear times, due to the security waiting time for receiving the potential blocking signal.
The following logic inputs are configurable using flexible inputs. It is possible to connect any logic input to them:
Permissive Schemes
Blocking Schemes
❑ Scheme type: Selects the type of scheme. Allows you to select between:
Step Trip (0)
Overreaching POTT(1)
Underreaching PUTT(2)
Direct.comp. block(3)
Direct.comp. unbl.(4)
❑ TPRx Drop out time (ms). Memorization time of the teleprotection received signal (TPRx).
❑ Block delay time (ms). Additional waiting time for the block signal.
❑ GSL Minimum time (ms). Minimum security signal loss time to allow trips.
❑ GSL Maximum time (ms). Maximum time during which the trip permission for loss of security signal is enabled.
❑ GSL Drop out time (ms). Drop out time following the recovery of the security channel.
❑ ECHO enabled. Enables the ECHO function.
❑ ECHO pulse time (ms). The duration of the ECHO signal pulse.
❑ ECHO Blocking time (ms). Time after the deactivation of the signal 67NQ_FW during which it is considered as being active.
❑ ECHO delay time (ms). The time during which the conditions for the activation of the ECHO signal must be met.
❑ Current Reversal Blocking. Enables trip blocking for a time after seeing a change in the fault's direction. (Reversal
direction memorisation).
❑ Current rev pickup t. (ms). Reversal direction memorization time.
❑ Weak Infeed Enabled. Enables the weak infeed function.
❑ Weak infeed Threshold (V). Voltage threshold to consider weak infeed.
❑ TPRx_67 line 1. Selects the signal which, when active, indicates that the line 1 teleprotection signal has been received.
❑ TPRx_67 line 2. Selects the signal which, when active, indicates that the line 2 teleprotection signal has been received.
❑ GSLRx_67 line 1. Selects the signal which, when active, indicates that the line 1 security signal loss has been received.
❑ GSLRx_67 line 2. Selects the signal which, when active, indicates that the line 2 security signal loss has been received.
❑ TP Trip Block. Selects the signal which, when active, blocks the teleprotection trip.
❑ TPTx Blocking input. Selects the signal which, when active, indicates the blocking of the TPTX signal transmission.
❑ ECHO Start value. Selects the signal which, when active, indicates ECHO pickup for teleprotection schemes.
❑ Block ECHO (logic input). Selects the signal which, when active, indicates ECHO blocking for teleprotection schemes.
❑ 67NQ Permissive Units. Allows the selection of an alternative pickup signal for unit 2: selects the signal which when
active, indicates the activation of the 67Q pickup signal used in permissive units. If this signal is configured, 67NQ
functions are not taken into account.
❑ 67NQ Block Units. Allows the selection of an alternative pickup signal for unit backwards: selects the signal which when
active, indicates the activation of the 67NQ pickup signal used in blocking units. If this signal is configured, 67NQ
functions are not taken into account.
❑ Weak Infeed Blocking. Selects the signal which, when active, indicates the blocking of the weak infeed scheme.
❑ General trip. Indicates if this unit produces general trip or not. For additional details, see the section corresponding to the
recloser (3.12.6).
❑ Trip permission by recloser. Indicates the trip and block permission in accordance with the recloser status: standby,
blocked, safety time after reclosing, after closing. It is configured bit by bit; for additional details, see section
corresponding to the recloser (3.12.6.3).
❑ Reclose permission15. Indicates whether each trip type can be reclosed or not, in accordance with the recloser's closing
cycle (see reclosure permission mask).
❑ Enable Events record. Allows the generation of protection events associated to the function. If set to “NO”, the function’s
protection events are not generated. If set to “YES”, the function’s specific mask is contemplated.
❑ TPTx Delay time (ms). TPTx signal delay time.
❑ Node PROT/OCPSCH1
❑ Settings and logical inputs. There are 6 settings tables. For details, see Table 102.
❑ There are no commands.
❑ Outputs: Table 103 shows the function's output data:
TPRx 67NQ L1. Indicates that the line 1 teleprotection signal has been received.
15
From firmware version 6.0.8.0 and ICD version 8.1.0.4, single pole reclosures are allowed. Until this version, only three
pole reclosure are allowed.
TPRx 67NQ L2. Indicates that the line 2 teleprotection signal has been received.
GSR 67NQ L1. Indicates that the line 1 security signal loss has been received.
GSR 67NQ L2. Indicates that the line 2 security signal loss has been received.
TPTx 67NQ. Indicates that the teleprotection signal has been activated.
ECHO 67NQ. Indicates that the ECHO signal has been activated.
STOP 67NQ. The directional blocking scheme indicates that there is a fault but that it is not backwards. It is used to
indicate that TPTx is not being sent.
WI 67NQ Trip. Indicates that the weak infeed conditions have been met during the configured time. There are
independent signals for each phase and a general signal.
Teleprotection 67NQ Trip. Indicates that the teleprotection has tripped.
Weak infeed phase 67NQ. Indicates that the weak infeed conditions have been met in at least one phase.
Permissive 67NQ Activation. Indicates that the permissive units have been activated.
Block Inverted Current 67NQ. Indicates that current inversion block has been activated.
Memory Inverted Current 67NQ: Current inversion block memorized. Indicates that current inversion block
memorization has been activated.
85_L1_END_perm_GSL_67NQ. End of permission due to security signal loss in line 1.
85_L2_END_perm_GSL_67NQ. End of permission due to security signal loss in line 2.
Teleprotection 67NQ status. Indicates whether or not the teleprotection function is enabled. If the "Scheme type"
setting is selected as "Step Trip", it means that teleprotection is disabled. Any other option means that it is enabled.
ECHO 67NQ Status. Indicates whether or not the ECHO function is enabled.
Weak infeed 67NQ status. Indicates whether or not the weak infeed function is enabled.
Trip 67NQ A. Indicates that the phase A trip is activated, when the "Single Pole Trip 67NQ" setting, located in the
PROT/ZPMPT node, is enabled.
Trip 67NQ B. Indicates that the phase B trip is activated, when the "Single Pole Trip 67NQ" setting, located in the
PROT/ZPMPT node, is enabled.
Trip 67NQ C. Indicates that the phase C trip is activated, when the "Single Pole Trip 67NQ" setting, located in the
PROT/ZPMPT node, is enabled.
Table 103 Teleprotection scheme outputs.
This scheme is based on the idea that at least one of the protection devices at one end of the line will see the fault in zone 1. If
a terminal sees the fault in zone 1 and the other one sees it in zone 2, the fault can be considered as being inside the line
between both devices, in the section of the line close to the terminal which sees it in zone 1.
The terminal that sees the fault in unit 1, besides setting off an instantaneous trip, sends the trip permission signal (TPTx) to the
other end while unit 1 is activated. The terminal which detects the fault in unit 2 generates an instantaneous trip with the
reception of the teleprotection signal (TPRIx) together with the activation of unit 2 as long as unit 3 is not activated.
Figure 97 and Figure 92 show the permissive underreaching protection scheme. This figure is used to analyse how the
protection devices will act in the event of faults in F1, F2 and F3:
❑ Fault F1: Protection A sees the fault in unit 1, causing an instantaneous trip and sending a permission signal to protection
B. Protection B sees the fault in unit 2 and will set off a high-speed trip when it sees the fault in unit 2 and will receive
protection A's permission command.
❑ Fault F2: Both protection devices see the fault in unit 1, causing a high-speed trip. Furthermore, redundant commands
are given by the communication channels.
❑ Fault F3: None of the protection devices will trip instantaneously. Protection A sees the fault in unit 2 but B does not see
the fault in the line to protect, not sending the permission signal to protection A. Hence, A's action in unit 2 will take place
in unit 2 time.
Inverse direction block: signal "Memory Inverted Current" can be eliminated from the logic by disabling this function. In this
case, "Memory Inverted Current" would be set permanently to 0.
In lines with more than two terminals, to apply this scheme, checks must be made to ensure that in the event on any fault in
any point in the line, at least the protection of one of the ends is detect in zone 1.
The scheme is applied to three-terminal lines by carrying an OR signal to the three of them from the TPRx of the other two ends
(See Figure 96).
In this protection scheme, a fault is considered internal to the line if both terminals see the fault in unit 2. An instantaneous trip
is caused if the teleprotection signal is received, together with activation of unit 2 as long as the memorised unit 3 is not
activated.
The teleprotection signal is sent upon the activation of the unit 2, without the detection of a reverse fault (Memory Inverted
Current).
Figure 99 and Figure 92 show the permissive overreaching protection scheme. This figure is used to analyse how the protection
devices will act in the event of faults in F1, F2 and F3:
❑ Fault F1: Protection A sees the fault in zone 1(PIOC1 or GPIOC1), causing an instantaneous trip and sending a permission
signal to protection B, given that it sees the fault in zone 2 (PIOC2 or GPIOC2) (zone 2 includes zone 1). Protection B trips
instantaneously when it sees the fault in zone 2 and receives a permission order from protection A. Protection B will also
send a permission signal to protection A but it has already instantaneously tripped in zone 1.
❑ Fault F2: Both protection devices see the fault in zone 1, causing a high-speed trip. Furthermore, redundant commands
are given by the communication channels.
❑ Fault F3: Protection A sees the fault in zone 2 and sends the permission signal to B, which sees the fault backwards. When
A does not receive the permission signal from B, zone 2's action will take place in zone 2 time. Protection B receives the
permission signal from A, but when it sees the fault backwards, it will not trip.
Any fault in unit 3 (PIOC3 or GPIOC3) it will normally be eliminated in unit 3 time.
In usual conditions, the signal GSLRx has the same value as the TPRx signal. Thus, if the TPRx signal is activated, GSLRx is also
activated. If both signals are deactivated there is not fault and the guard channel signal is not lost.
If the overreaching unit 2 (PIOC2 or GPIOC2) acts, the security signal works as an unblocking signal.
trip is enabled. Once the loss off channel signal is deactivated again a third timer starts. When the “GSL drop out time
(ms)” delay is over the previous logic is newly applied.
The figures show the directional unblocking protection scheme. This figure is used to analyse how the protection devices will
act in the event of faults in F1, F2 and F3:
N.B.: The signals received in GSLRx and TPRx directional blocking can only be received with values (active, active), (active,
inactive) or (inactive, inactive). They can never be (inactive, active) because the transmitter/receiver that sends the signals,
when there is communication and receives TPR gives the signals GSR and TPR and when there is no communication, gives GSR
but not TPR.
Analysis is made of how the protection devices will act in the event of faults in F1, F2 and F3:
❑ Fault F1: Protection A sees the fault in zone 1, causing an instantaneous trip and changing the security signal to an
unblocking signal given that it sees the fault in zone 2 (zone 2 includes zone 1). Protection B sees the fault in zone 2 and
when it receives the unblocking signal from A, it will speed up the trip. If the security channel is lost, when protection B's
zone 2 is activated, it will speed up its trip if it receives the channel loss signal for the time programmed for "security
signal loss".
❑ Fault F2: Both protection devices see the fault in zone 1, causing a high-speed trip.
❑ Fault F3: Protection A sees the fault in zone 2 but does not speed up its trip given that protection B sees the fault in zone
4 and therefore will not change the security signal for an unblocking signal.
A stop channel signal (STOP 67NQ) is activated if a forward fault is detected (overcurrent units 1 and 2) and it is maintained
during “Block delay time (ms)” (BlkTmms), without the detection of a fault in the unit 3 Memory Inverted Current).
If the channel interruption signal (STOP 67NQ) is activated and the signal TPRx is not received, the signal "Teleprotection 67NQ
Trip" is activated.
If the input “TPTx Blocking input” is activated the signal TPRx is not sent. Furthermore, if the “TP Trip Block” input is activated,
the signal "Teleprotection 67NQ Trip" is blocked.
The blocking time is an additional delay time to give time for the blocking signal to be received and is programmable by the
user. The transmission time must be as low as possible with the aim of reducing this delay to a minimum.
The Figure 104, Figure 92 and Figure 93 show the directional blocking protection scheme. This figure is used to analyse how the
protection devices will act in the event of faults in F1, F2 and F3:
❑ Fault F1: Protection A detects the fault in zone 1 causing an instantaneous trip. Protection B detects the fault in zone 2
and once the blocking time has elapsed, it will trip given that a blocking command is not received from A since A does not
detect the fault in zone 4.
❑ Fault F2: Both protection devices see the fault in zone 1, causing a high-speed trip.
❑ Fault F3: Protection A detects the fault in zone 2 but does not cause a fast trip given that protection B sees the fault in
zone 4 and will therefore send a blocking signal to A.
Care must be taken with the coordination of the blocking unit backwards (for example, B's zone 4) of each end with the
overreaching unit of the other end (A's zone 2), these being set so that the reach of the reverse unit is always greater than the
overreach's.
This scheme has the advantage of not being sensitive to noise in the communication channel and has the disadvantage of
possibly causing untimely trips if the communication channel is lost.
The blocking scheme is usually used in long lines when the teleprotection signal is transmitted via the protected line by the
carrier wave and the diminishing of the signal transmitted at the point of fault can be so severe that reception at the other end
of the line cannot always be ensured.
3.12.1.6 ECHO
It is used together with permissive overreaching schemes by acting on the teleprotection (TPTx) signal.
The ECHO 67NQ signal only provides a programmable pulse. The ECHO function sends the teleprotection (TPTx) signal with any
of the following conditions:
To speed up the trip at the strongly-fed end in the event of a fault at the opposite end, the Echo function returns the TPRIx
signal received to the remote terminal if it does not detect a fault forward or backwards, or if the circuit breaker is open.
The resending of the TPRIx received (ECHO 67NQ) will be instantaneous if the circuit breaker is open and will suffer a delay
(EcActTmms) if there is a weak power supply. This delay makes it possible to cover situations in which there is a higher fault
detection time, or it start slightly later due to an unfavourable distribution of the fault current. This delay is usually set to
approximately 40ms.
“ECHO 67NQ” is a pulse that during “ECHO pulse time (ms)” (EcTmms), which is normally set to approximately 50 ms, thus
assuring that the signal received is even recognised with different action times of the protection equipment at ends of the lines
and with different response times of the transmission equipment.
Figure 108 shows the ECHO Logic Sample, with the circuit breaker in B Open This scheme will be used to analyse how the
protection devices act in the event of faults F1 and F2 with the basic permissive overreaching scheme.
❑ Fault F1: Protection A detects the fault in its zone 1 and hence instantaneously trips and sends a permission signal to B.
End B is open so the fault is cleared.
❑ Fault F2: Protection A detects the fault in zone 2 and sends a permission signal to B. When the protection device in B
detects that the circuit breaker is open, it will resend the permission signal to protection A without delay. When
protection A detects the fault in zone 2 and having received the permission signal, it will speed up its trip.
Figure 109 shows the ECHO logic, and Weak infeed. This scheme will be used to analyse how the protection devices act in the
event of faults F1 and F2 with the basic permissive overreaching scheme.
❑ Fault F1: Protection A detects the fault in unit 1 and will hence trip instantaneously and send a permission signal to B. The
protection in B, being weakly fed, will not detect the fault, but as it receives the permission signal, it will send back to A
with the programmed delay, but A will be open. The circuit breaker at end B will remain closed.
❑ Fault F2: Protection A detects the fault in unit 2 and sends a permission signal to B. The protection in B, being weakly fed,
will not detect the fault, but as it receives the permission signal, it will send back to A with the programmed delay. When
protection A sees the fault in unit 2 and has received the permission signal, it will speed up its trip. The circuit breaker at
end B will remain closed.
The undervoltage unit associated to the weak infeed function has its own settings and is not dependent on the undervoltage
units.
If an unblocking scheme is used, the TPRIx signal is replaced by TPRIx & GSL.
If one end of the line is weakly fed (Figure 109 end B) with the echo logic, as seen in the previous section, the trip at the
strongly fed end is accelerated. However, the weakly fed end remains closed. This logic allows the opening of this end of the
line.
To detect the fault at the weak end, the following conditions must be fulfilled:
❑ TPRIx signal received (it will be sent to the strongly-fed end, as described in the ECHO function).
❑ The circuit breaker is closed.
❑ Undervoltage is detected in one of the phases (as a consequence of the fault). The settings recommended are 70%Vn for
the voltage.
Figure 110 Protection in the weak infeed Logic, with End B Weakly Fed
Figure 110 shows the weak infeed logic, with end B weakly fed. This scheme will be used to analyse how the protection devices
act in the event of F1 faults with the basic permissive overreaching scheme.
❑ Fault F1: Protection A detects the fault in unit 2 and sends a permission signal to B. The protection in B, being weakly fed,
will not detect the fault and when it receives the permission signal, it will send it to A after the set time. When protection
A sees the fault in unit 2 and has received the permission signal, it will speed up its trip. When protection B fulfills the
ECHO conditions and detects undervoltage (due to the existence of the fault), it will give the trip command.
It is used in double circuit lines to prevent trips due to the change in the current flow which is caused when the circuit breaker
is opened at one end of the faulty line when this fault is cleared. The reversal of the current implies the reversal of the
protection device's directional elements, as well as the increase in the apparent distance to the fault. The time between the
repositioning of the distance elements and the functioning of the unit may give rise to a trip in the healthy parallel line.
When the scheme is a blocking one, it keeps the blocking signal for a set time "Block delay time (ms)", blocking the trip for a
time after detecting a change in the fault's direction. When the scheme is permissive, it blocks the trip and the emission of the
permission for a set time after changing the direction in which it detects the fault (backwards to forward).
The overcurrent unit 2 signal is used with a memorization time "Current Reversal Blocking(ms)" (RvATmms), which enables the
"Memory Inverted Current" signal to be used in the rest of the schemes (see Figure 93).
The following figures show the change in the current flow when the fault occurs and when circuit breaker K is opened to clear
this fault:
❑ When faults F occurs as can be seen in Figure 111.1, protection K will detect the fault in zone 1, J will either detect it in 1
or 2 and H backwards. In this situation, K instantaneously opens the circuit breaker and sends the permission signal to J
and likewise, G sends the permission signal to H.
❑ When K opens, the current's flow is inverted as can be seen in Figure 111.2. In this new situation, G will detect the fault
backwards and H will detect it in zone 2. These conversions are not simultaneous or instantaneous. Hence, H could trip
before G removes the permission signal. To prevent this trip, the teleprotection trip is delayed for a number of cycles, to
give the remote terminal time to remove the permission signal.
Figure 111 Change in the Current Flow When the Fault Occurs in a Double Circuit Line
❑ When the fault occurs as can be seen in Figure 110, protection K will detect the fault in zone 1, J will either detect it in 1
or 2 and H backwards. When H detects the fault in its zone 4, it sends a blocking signal to G (or it does not send the TPRIx
signal, which is the same), preventing tripping due to acceleration in zone 2.
❑ When K opens, the current's flow is inverted as can be seen in Figure 111.2. In this new situation, G will detect the fault
backwards and H will detect it in zone 2. H would trip before receiving the blocking signal from G. To prevent this, H will
continue to detect the fault backwards, allowing time to receive the blocking signal.
It is recommended that the additional blocking time be set as follows:
Additional blocking time = operating time of the circuit breaker at the other end of the line (typically 3 cycles) + the reset time
of the communication channel (1 cycle) + the reset time of zone 2 of the relay at the other end of the line (1 cycle) = 5 cycles.
They are based upon the use of teleprotection signals between both end terminals of the line. The effect upon the output relays’
operation is determined according to the signals given by the protection along with the signals given by the other terminal.
From firmware version 6.0.8.0 and ICD version 8.1.0.4, the option of the phase-segregated teleprotection is included. When the
phase-segregated teleprotection is chosen, the teleprotection schemes are performed per phase. Moreover, the setting "TPTx
delay time (ms)" is included.
3.12.2.1 Introduction
3.12.2.1.1 Fault Detection Units
Teleprotection Z scheme will operate on the distance unit 21, Zone 1 and Zone 2 (forward), and zone 4 (backwards). Mho and quad
are both affected.
❑ Blocking schemes: The signal received indicates that the fault is outside the protected zone. A relay can trip on an
overreaching zone if, after a definite time, the blocking signal has not been received.
❑ Permissive schemes: The signal received allows an instantaneous trip in the overreaching zone. The additional ECHO,
weak infeed and Current Reversal Blocking schemes can be used.
When selecting a particular scheme, it is useful to bear in mind the following characteristics for each of them: In the case of an
internal fault in the protected line and a communication channel fault in permissive schemes, protection is disabled for tripping,
whilst in blocking schemes, tripping is assured. However, in blocking schemes, if there is an external fault and a communication
channel fault, the device can trip.
If the communication system forms an integral part of the energy transport line, as in the case of carrier waves, it is best to use the
Current Reversal Blocking scheme, since internal faults may disturb or attenuate the carrier signal. Likewise, it is best to use
blocking schemes in weak infeed configurations as they are more reliable compared to permissive schemes.
Finally, it should be mentioned that permissive schemes are faster than blocking schemes, given that the latter involve slightly
longer fault clear times, due to the security waiting time for receiving the potential blocking signal.
Units (1 bit)" which enable both logic inputs to be carried with the pickups of the desired units. In this way, the signals carried to
the schemes can be made flexible.
The following logic inputs are configurable using flexible inputs. It is possible to connect any logic input to them:
In the case of phase-segregated teleprotection, the permissive and block units have several selection options. One signal per phase
is activated.
❑ TPTx_21. Teleprotection signal sent by a terminal. In the case of phase-segregated teleprotection there is one signal per
phase.
❑ TPRIx_21. Teleprotection input received by a terminal. In the case of phase-segregated teleprotection there is one signal
per phase.
❑ TPRx_21. Follows the TPRIx_21 input to become activated, but memorises the input during the set time “TPRx Drop out
time (ms)” (RsRTPTmms) to deactivate itself. If this setting is equal to zero, then TPRx21 coincides with the input TPRIx
21. TPRx is used in the teleprotection schemes. In the case of phase-segregated teleprotection there is one signal per
phase.
❑ GSLRx_21. Line security signal loss. Indicates that the data channel established between the two teleprotection devices is
inactive.
Figure 116 Teleprotection Reception
Permissive Schemes
Blocking Schemes
❑ Scheme type: Selects the type of scheme. Allows you to select between:
Step Trip (0)
Overreaching POTT(1)
Underreaching PUTT(2)
Direct.comp. block(3)
Direct.comp. unbl.(4)
❑ TPRx Drop out time (ms). Memorization time of the teleprotection received signal (TPRx).
❑ Block delay time (ms). Additional waiting time for the block signal.
❑ GSL Minimum time (ms). Minimum security signal loss time to allow trips.
❑ GSL Maximum time (ms). Maximum time during which the trip permission for loss of security signal is enabled.
❑ GSL Drop out time (ms). Drop out time following the recovery of the security channel.
❑ ECHO enabled. Enables the ECHO function.
❑ ECHO pulse time (ms). The duration of the ECHO signal pulse.
❑ ECHO Blocking time (ms). Time after the deactivation of the signal Z_FW (Z Permissive Units) during which it is considered
as being active.
❑ ECHO delay time (ms). The time during which the conditions for the activation of the ECHO signal must be met.
❑ Current Reversal Blocking. Enables trip blocking for a time after seeing a change in the fault's direction. (Reversal
direction memorisation).
❑ Current rev pickup t. (ms). Reversal direction memorization time.
❑ Weak Infeed Enabled. Enables the weak infeed function.
❑ Weak infeed Threshold (V). Voltage threshold to consider weak infeed.
❑ TPRx_21 line 1. Selects the signal which, when active, indicates that the line 1 teleprotection signal has been received.
❑ TPRx_21 line 2. Selects the signal which, when active, indicates that the line 2 teleprotection signal has been received.
❑ GSLRx_21 line 1. Selects the signal which, when active, indicates that the line 1 security signal loss has been received.
❑ GSLRx_21 line 2. Selects the signal which, when active, indicates that the line 2 security signal loss has been received.
❑ TP Trip Block. Selects the signal which, when active, blocks the teleprotection trip.
❑ TPTx Blocking input. Selects the signal which, when active, indicates the blocking of the TPTX signal transmission.
Figure 122 TPTx Block Scheme
❑ ECHO Start value. Selects the signal which, when active, indicates ECHO start for teleprotection schemes.
❑ Block ECHO (logic input). Selects the signal which, when active, indicates ECHO blocking for teleprotection schemes.
❑ Z Permissive Units (1 bit). Allows the selection of an alternative pickup signal for zone 2: selects the signal which when
active, indicates the activation of the Z pickup signal used in permissive units. If this signal is configured, Z functions are
not taken into account. Only in the non-phase-segregated protection.
❑ Z Block Units (1 bit). Allows the selection of an alternative pickup signal for backwards zone: selects the signal which
when active, indicates the activation of the Z pickup signal used in blocking units. If this signal is configured, Z functions
are not taken into account. Only in the non-phase-segregated protection.
❑ Weak Infeed Blocking. Selects the signal which, when active, indicates the blocking of the weak infeed scheme.
❑ Enable Events record. Allows the generation of protection events associated to the function. If set to “NO”, the function’s
protection events are not generated. If set to “YES”, the function’s specific mask is contemplated.
❑ Reclose permission. Indicates whether each trip type can be reclosed or not, in accordance with the recloser's closing
cycle (see reclosure permission mask).
❑ TPTx Delay time (ms). TPTx signal delay time.
❑ Phase-segregated teleprotection. Enables the phase-segregated teleprotection.
❑ TPRx_21 line 1A. Selects the signal which, when active, indicates that the line 1's phase A teleprotection signal has been
received. Only in phase-segregated teleprotection.
❑ TPRx_21 line 1B. Selects the signal which, when active, indicates that the line 1's phase B teleprotection signal has been
received. Only in phase-segregated teleprotection.
❑ TPRx_21 line 1C. Selects the signal which, when active, indicates that the line 1's phase C teleprotection signal has been
received. Only in phase-segregated teleprotection.
❑ TPRx_21 line 2A. Selects the signal which, when active, indicates that the line 2's phase A teleprotection signal has been
received. Only in phase-segregated teleprotection.
❑ TPRx_21 line 2B. Selects the signal which, when active, indicates that the line 2's phase B teleprotection signal has been
received. Only in phase-segregated teleprotection.
❑ TPRx_21 line 2C. Selects the signal which, when active, indicates that the line 2's phase C teleprotection signal has been
received. Only in phase-segregated teleprotection.
❑ Z Permissive Units (3 bits). It allows to select an alternative zone to zone 2. It selects the zone, whose start, causes the
activation of the permissive units. It is only used when the teleprotection is phase-segregated.
Predefined (0). It correspond to Zone 2.
Zone 3 (1)
Zone 5 (2)
❑ Z Block Units (3 bits). It allows to select an alternative zone to zone 4. It selects the zone, whose start, causes the
activation of the block units. It is only used when the teleprotection is phase-segregated.
Predefined (0). It correspond to Zone 4
Zone 3 (1)
Zone 5 (2)
❑ Node PROT/ZPSCH1
❑ Settings and logical inputs. There are 6 settings tables. For details, see Table 105.
❑ There are no commands
❑ Outputs: Table 106 shows the function's output data:
TPRx Z L1. Indicates that the line 1 teleprotection signal has been received.
TPRx Z L2. Indicates that the line 2 teleprotection signal has been received.
GSR Z L1. Indicates that the line 1 security signal loss has been received.
GSR Z L2. Indicates that the line 2 security signal loss has been received.
TPTx Z. Indicates that the teleprotection signal has been activated.
ECHO Z. Indicates that the ECHO signal has been activated.
STOP Z. The directional blocking scheme indicates that there is a fault but that it is not backwards. It is used to indicate
that TPTx is not being sent.
27WI Z Trip Weak infeed trip. Indicates that the weak infeed conditions have been met during the configured time.
27WI Z Phase X. Weak infeed trip. Indicates that the weak infeed conditions have been met during the configured
time. There are independent signals for each phase.
Teleprotection Z Trip. Indicates that the teleprotection has tripped.
Weak Infeed Phase Z. Indicates that the weak infeed conditions have been met in at least one phase.
Permissive Z Activation. Indicates that the permissive units have been activated.
Block Inverted Current Z. Indicates that current inversion block has been activated.
Memory Inverted Current Z: Current inversion block memorized. Indicates that current inversion block memorization
has been activated.
85_L1_END_perm_GSL_Z. End of permission due to security signal loss in line 1.
85_L2_END_perm_GSL_Z. End of permission due to security signal loss in line 2.
Teleprotection Z status. Indicates whether or not the teleprotection function is enabled. If the "Scheme type" setting is
selected as "Step Trip", it means that teleprotection is disabled. Any other option means that it is enabled.
ECHO Z Status. Indicates whether or not the ECHO Z function is enabled.
Weak infeed Z status. Indicates whether or not the weak infeed function is enabled.
TPRx Z L1A. Indicates that the line 1 phase A teleprotection signal has been received.
TPRx Z L1B. Indicates that the line 1 phase B teleprotection signal has been received.
TPRx Z L1C. Indicates that the line 1 phase C teleprotection signal has been received.
TPRx Z L2A. Indicates that the line 2 phase A teleprotection signal has been received.
TPRx Z L2B. Indicates that the line 2 phase B teleprotection signal has been received.
TPRx Z L2C. Indicates that the line 2 phase C teleprotection signal has been received.
TPTx Z_A. Indicates that the teleprotection phase A signal has been activated.
TPTx Z_B. Indicates that the teleprotection phase B signal has been activated.
TPTx Z_C. Indicates that the teleprotection phase C signal has been activated.
ECHO Z_A. Indicates that the ECHO phase A signal has been activated.
ECHO Z_B. Indicates that the ECHO phase A signal has been activated.
ECHO Z_C. Indicates that the ECHO phase A signal has been activated.
STOP Z_A. The directional blocking scheme indicates that there is a fault but that it is not backwards. It is used to
indicate that TPTx phase A is not being sent.
STOP Z_B. The directional blocking scheme indicates that there is a fault but that it is not backwards. It is used to
indicate that TPTx phase B is not being sent.
STOP Z_C. The directional blocking scheme indicates that there is a fault but that it is not backwards. It is used to
indicate that TPTx phase C is not being sent.
Teleprotección Trip Z_A. Indicates that a teleprotection phase A has tripped.
Teleprotección Trip Z_B. Indicates that a teleprotection phase B has tripped.
Teleprotección Trip Z_C. Indicates that a teleprotection phase C has tripped.
Permissive U activation A. Indicates that the permissive units for phase A have been activated.
Permissive U activation B. Indicates that the permissive units for phase B have been activated.
Permissive U activation C. Indicates that the permissive units for phase C have been activated.
Block invertion current A. Indicates that current A inversion block has been activated.
Block invertion current B. Indicates that current B inversion block has been activated.
Block invertion current C. Indicates that current C inversion block has been activated.
Memory invertion current A. Current A inversion block memorized. Indicates that current A inversion block
memorization has been activated.
Memory invertion current B. Current B inversion block memorized. Indicates that current B inversion block
memorization has been activated.
Memory invertion current C. Current C inversion block memorized. Indicates that current C inversion block
memorization has been activated.
Table 106 Teleprotection schemes signals
This scheme is based on the idea that at least one of the protection devices at one end of the line will see the fault in zone 1. If
a terminal sees the fault in zone 1 and the other one sees it in zone 2, the fault can be considered as being inside the line
between both devices, in the section of the line close to the terminal which sees it in zone 1.
The terminal that sees the fault in zone 1, besides setting off an instantaneous trip, sends the trip permission signal (TPTx) to
the other end while zone 1 is activated. The terminal which detects the fault in zone 2 generates an instantaneous trip with the
reception of the teleprotection signal (TPRIx) together with the activation of a unit in zone 2 as long as zone 4 is not activated.
In the case of phase-segregated teleprotection, a TPTx of the faulted phase will be sent. For producing the teleprotection trip of
one phase, the TPRx of this phase and the corresponding permissive unit has to be activated. In addition, it the does not have
to see the fault backwards in that phase (Z Block units).
Figure 125 and Figure 112 show the permissive underreaching protection scheme. This figure is used to analyse how the
protection devices will act in the event of faults in F1, F2 and F3:
III
II
Protección Protección
x1 u1
x2 u1 x1 u2
x3 u3
A B
F1 F2 I F3
II
III
❑ Fault F1: Protection A sees the fault in zone 1, causing an instantaneous trip and sending a permission signal to protection
B. Protection B sees the fault in zone 2 and will set off a high-speed trip when it sees the fault in zone 2 and will receive
protection A's permission command.
❑ Fault F2: Both protection devices see the fault in zone 1, causing a high-speed trip. Furthermore, redundant commands
are given by the communication channels.
❑ Fault F3: None of the protection devices will trip instantaneously. Protection A sees the fault in zone 2 but B does not see
the fault in the line to protect, not sending the permission signal to protection A. Hence, A's action in zone 2 will take
place in zone 2 time.
Inverse direction block: signal "Memory Inverted Current" can be eliminated from the logic by disabling this function. In this
case, "Memory Inverted Current" would be set permanently to 0.
In lines with more than two terminals, to apply this scheme, it has to be ensured that in the event on any fault in any point in
the line, at least the protection of one of the ends detects it in zone 1.
The scheme is applied to three-terminal lines by carrying an OR signal to the three of them from the TPRx of the other two ends
(See Figure 96).
In this protection scheme, a fault is considered internal to the line if both terminals see the fault in zone 2. An instantaneous
trip is caused if the teleprotection signal is received, together with activation of a unit in zone 2 as long as the memorised zone
4 is not activated.
The teleprotection signal is sent upon the activation of the zone 2 units, without the detection of a reverse fault (Memory
Inverted Current).
In the case of phase-segregated teleprotection, a TPTx of the faulted phase will be sent. For producing the teleprotection trip of
one phase, the TPRx of this phase and the corresponding permissive unit has to be activated. In addition, it the does not have
to see the fault backwards in that phase (Z Block units).
Figure 126 and Figure 112 show the permissive overreaching protection scheme. This figure is used to analyse how the
protection devices will act in the event of faults in F1, F2 and F3:
❑ Fault F1: Protection A sees the fault in zone 1 (PDIS1), causing an instantaneous trip and sending a permission signal to
protection B, given that it sees the fault in zone 2 (PDIS2) (zone 2 includes zone 1). Protection B trips instantaneously
when it sees the fault in zone 2 and receives a permission order from protection A. Protection B will also send a
permission signal to protection A but it has already instantaneously tripped in zone 1.
❑ Fault F2: Both protection devices see the fault in zone 1, causing a high-speed trip. Furthermore, redundant commands
are given by the communication channels.
❑ Fault F3: Protection A sees the fault in zone 2 and sends the permission signal to B, which sees the fault backwards. When
A does not receive the permission signal from B, zone 2's action will take place in zone 2 time. Protection B receives the
permission signal from A, but when it sees the fault backwards, it will not trip.
Any fault in zone 3 (PDIS3) will be eliminated in zone 3 time.
In usual conditions, the signal GSLRx has the same value as the TPRx signal. Thus, if the TPRx signal is activated, GSLRx is also
activated. If both signals are deactivated there is not fault and the guard channel signal is not lost.
If the overreaching zone 2 (PDIS2) acts, the security signal works as an unblocking signal.
❑ When the device only receives the GSLRx signal, the timers start. When the “GSL minimum time (ms)” (LoGMinTmms)
delay is over without the reception of the TPRx signal, a trip is issued. Once the “GSL maximum time (ms)” has elapsed, no
trip is enabled. Once the loss off channel signal is deactivated again a third timer starts. When the “GSL drop out time
(ms)” delay is over the previous logic is newly applied.
The directional unblocking scheme does not allow phase-segregated teleprotection.
The figures show the directional unblocking protection scheme. This figure is used to analyse how the protection devices will
act in the event of faults in F1, F2 and F3:
N.B.: The signals received in the directional blocking (GSLRx and TPRx) can only be received with the values (active, active),
(active, inactive) or (inactive, inactive). They can never be (inactive, active) because the transmitter/receiver that sends the
signals, when there is communication and receives TPR gives the signals GSR and TPR and when there is no communication,
gives GSR but not TPR.
Analysis is made of how the protection devices will act in the event of faults in F1, F2 and F3:
❑ Fault F1: Protection A sees the fault in zone 1, causing an instantaneous trip and changing the security signal to an
unblocking signal given that it sees the fault in zone 2 (zone 2 includes zone 1). Protection B sees the fault in zone 2 and
when it receives the unblocking signal from A, it will speed up the trip. If the security channel is lost, when protection B's
zone 2 is activated, it will speed up its trip if it receives the channel loss signal for the time programmed for "security
signal loss".
❑ Fault F2: Both protection devices see the fault in zone 1, causing a high-speed trip.
❑ Fault F3: Protection A sees the fault in zone 2 but does not speed up its trip given that protection B sees the fault in zone
4 and therefore will not change the security signal for an unblocking signal.
A stop channel signal (STOP Z) is activated if a forward fault is detected (zone 1 or zone 2) and it is maintained during “Block
delay time (ms)” (BlkTmms), without the detection of a fault in zone 4 (Z4_MEM).
If the channel interruption signal (STOP Z) is activated and the signal TPRx is not received, the signal "Teleprotection Z Trip" is
activated.
If the input “TPTx Blocking input” is activated the signal TPRx is not sent. Furthermore, if the “TP Trip Block” input is activated,
the signal "Teleprotection Z Trip" is blocked.
The blocking time is an additional delay time to give time for the blocking signal to be received and is programmable by the
user. The transmission time must be as low as possible with the aim of reducing this delay to a minimum.
In the case of phase-segregated teleprotection, a TPTx of the faulted phase will be sent. For producing the teleprotection trip of
one phase, the TPRx of this phase does not have to be activated. In addition, the STOP signal and the permissive units of this
phase have to be activated.
The signals corresponding to phase A, are activated with the faults AN, AB, CA.
The signals corresponding to phase B, are activated with the faults BN, AB, BC.
The signals corresponding to phase C, are activated with the faults CN, BC, CA.
The Figure 112 and Figure 113 show the directional blocking protection scheme. This scheme is used to analyse how the
protection devices will act in the event of faults in F1, F2 and F3:
❑ Fault F1: Protection A detects the fault in zone 1 causing an instantaneous trip. Protection B detects the fault in zone 2
and once the blocking time has elapsed, it will trip given that a blocking command is not received from A since A does not
detect the fault in zone 4.
❑ Fault F2: Both protection devices see the fault in zone 1, causing a high-speed trip.
❑ Fault F3: Protection A detects the fault in zone 2 but does not cause a fast trip given that protection B sees the fault in
zone 4 and will therefore send a blocking signal to A.
Care must be taken with the coordination of the blocking unit backwards (for example, B's zone 4) of each end with the
overreaching unit of the other end (A's zone 2), these being set so that the reach of the reverse unit is always greater than the
overreach's.
This scheme has the advantage of not being sensitive to noise in the communication channel and has the disadvantage of
possibly causing untimely trips if the communication channel is lost.
The blocking scheme is usually used in long lines when the teleprotection signal is transmitted via the protected line by the
carrier wave and the diminishing of the signal transmitted at the point of fault can be so severe that reception at the other end
of the line cannot always be ensured.
3.12.2.6 ECHO
It is used together with permissive overreaching schemes by acting on the teleprotection (TPTx) signal.
The ECHO Z signal only provides a programmable pulse. The ECHO function sends the teleprotection (TPTx) signal with any of
the following conditions:
In the case of phase-segregated teleprotection, one TPRx will be received per phase, also activating one ECHO per phase.
Figure 138. Echo and weak infeed scheme, phase A, phase-segregated teleprotection
It is used together with permissive overreaching schemes in cases where one end of the line is open (Figure 108 end B) or is a
weak end (Figure 109 end B). In the event of a fault on the line near the weakly-fed or open end, the distance unit of this end of
the line does not detect the fault. Hence, the trip will not be issued, nor will the permission signal be sent to the other end of
the line. Hence, since the permission signal will not be received, the strongly-fed end of the line will not speed up its trip.
To speed up the trip at the strongly-fed end in the event of a fault at the opposite end, the Echo function returns the TPRIx
signal received to the remote terminal if it does not detect a fault forward or backwards, or if the circuit breaker is open.
The resending of the TPRIx received (ECHO Z) will be instantaneous if the circuit breaker is open and will suffer a delay
(EcActTmms) if there is a weak power supply. This delay makes it possible to cover situations in which there is a higher fault
detection time, or it start slightly later due to an unfavourable distribution of the fault current. This delay is usually set to
approximately 40ms.
"ECHO Z" is a pulse that during "ECHO pulse time (ms)" (EcTmms), which is normally set to approximately 50 ms, thus assuring
that the signal received is even recognised with different action times of the protection equipment at ends of the lines and with
different response times of the transmission equipment.
Figure 137 shows the ECHO Logic Sample, with the circuit breaker in B Open This scheme will be used to analyse how the
protection devices act in the event of faults F1 and F2 with the basic permissive overreaching scheme.
❑ Fault F1: Protection A detects the fault in its zone 1 and hence instantaneously trips and sends a permission signal to B.
End B is open so the fault is cleared.
❑ Fault F2: Protection A detects the fault in zone 2 and sends a permission signal to B. When the protection device in B
detects that the circuit breaker is open, it will resend the permission signal to protection A without delay. When
protection A detects the fault in zone 2 and having received the permission signal, it will speed up its trip.
Figure 140 Echo and weak infeed example
Figure 137 shows the ECHO logic, and Weak infeed. This scheme will be used to analyse how the protection devices act in the
event of faults F1 and F2 with the basic permissive overreaching scheme.
❑ Fault F1: Protection A detects the fault in unit 1 and will hence trip instantaneously and send a permission signal to B. The
protection in B, being weakly fed, will not detect the fault, but as it receives the permission signal, it will send back to A
with the programmed delay, but A will be open. The circuit breaker at end B will remain closed.
❑ Fault F2: Protection A detects the fault in unit 2 and sends a permission signal to B. The protection in B, being weakly fed,
will not detect the fault, but as it receives the permission signal, it will send back to A with the programmed delay. When
protection A sees the fault in unit 2 and has received the permission signal, it will speed up its trip. The circuit breaker at
end B will remain closed.
The undervoltage unit associated to the weak infeed function has its own settings and is not dependent on the undervoltage
units.
If an unblocking scheme is used, the TPRIx signal is replaced by TPRIx & GSL.
If one end of the line is weakly fed (Figure 109 end B) with the echo logic, as seen in the previous section, the trip at the
strongly fed end is accelerated. However, the weakly fed end remains closed. This logic allows the opening of this end of the
line.
To detect the fault at the weak end, the following conditions must be fulfilled:
❑ TPRIx signal received (it will be sent to the strongly-fed end, as described in the ECHO function).
❑ The circuit breaker is closed.
❑ Undervoltage is detected in one of the phases (as a consequence of the fault). The settings recommended are 70%Vr for
the voltage.
Figure 141 Protection in the Weak Infeed Logic, with End B Weakly Fed
Figure 110 shows the weak infeed logic, with end B weakly fed. This scheme will be used to analyse how the protection devices
act in the event of F1 faults with the basic permissive overreaching scheme.
❑ Fault F1: Protection A detects the fault in zone 2 and sends a permission signal to B. The protection in B, being Weak
Infeed, will not detect the fault and when it receives the permission signal, it will send it to A after the set time. When
protection A sees the fault in zone 2 and has received the permission signal, it will speed up its trip. When protection B
fulfills the ECHO conditions and detects undervoltage (due to the existence of the fault), it will give the trip command.
It is used in double circuit lines to prevent trips due to the change in the current flow which is caused when the circuit breaker
is opened at one end of the faulty line when this fault is cleared. The reversal of the current implies the reversal of the
protection device's directional elements, as well as the increase in the apparent distance to the fault. The time between the
repositioning of the distance elements and the functioning of the unit may give rise to a trip in the healthy parallel line.
When the scheme is a blocking onee, it keeps the blocking signal for a set time "Block delay time (ms)”, blocking the trip for a
time after detecting a change in the fault's direction. When the scheme is permissive, it blocks the trip and the emission of the
permission for a set time after changing the direction in which it detects the fault (backwards to forward).
The zone 4 signal is used with a memorization time "Current rev pickup t (ms)" (RvATmms), which enables the "Memory
Inverted Current" signal to be used in the rest of the schemes.
In the case of phase-segregated teleprotection, the signal used for the blocking will depend on what is set in "Z Block Units (3
bits)”, activating a signal per phase.
The signals corresponding to phase A, are activated with the faults AN, AB, CA.
The signals corresponding to phase B, are activated with the faults BN, AB, BC.
The signals corresponding to phase C, are activated with the faults CN, BC, CA.
The following figures show the change in the current flow when the fault occurs and when circuit breaker K is opened to clear
this fault:
Figure 142 Change in the Current Flow When the Fault Occurs in a Double Circuit Line
❑ When faults F occurs as can be seen in Figure 111.1, protection K will detect the fault in zone 1, J will either detect it in 1
or 2 and H backwards. In this situation, K instantaneously opens the circuit breaker and sends the permission signal to J
and likewise, G sends the permission signal to H.
❑ When K opens, the current's flow is inverted as can be seen in Figure 111.2. In this new situation, G will detect the fault
backwards and H will detect it in zone 2. These conversions are not simultaneous or instantaneous. Hence, H could trip
before G removes the permission signal. To prevent this trip, the teleprotection trip is delayed for a number of cycles, to
give the remote terminal time to remove the permission signal.
Inverse direction blocking with blocking scheme:
❑ When the fault occurs as can be seen in Figure 110, protection K will detect the fault in zone 1, J will either detect it in 1
or 2 and H backwards. When H detects the fault in its zone 4, it sends a blocking signal to G (or it does not send the TPRIx
signal, which is the same), preventing tripping due to acceleration in zone 2.
❑ When K opens, the current's flow is inverted as can be seen in Figure 111.2. In this new situation, G will detect the fault
backwards and H will detect it in zone 2. H would trip before receiving the blocking signal from G. To prevent this, H will
continue to detect the fault backwards, allowing time to receive the blocking signal.
It is recommended that the additional blocking time be set as follows:
Additional blocking time = operating time of the circuit breaker at the other end of the line (typically 3 cycles) + the reset time
of the communication channel (1 cycle) + the reset time of zone 2 of the relay at the other end of the line (1 cycle) = 5 cycles.
In order to operate correctly, it must be enabled. Furthermore, a digital input must be programmed as a direct trip, otherwise it
is like being disabled.
❑ Direct trip pole A, B or C: Causes an external single-pole trip in the corresponding pole.
❑ Direct trip pole ABC: Causes the command to open as well as an external three-pole trip.
Any digital signal can be used as an output signal for signalling a direct trip to the other extreme, either via the programming of
the digital outputs or via the programmable logics.
A particular feature of the scheme is the direct trip, in which the input signals are generic but unit 1's signals zone used as the
output signals.
The settings for the configuration of this unit are shown in Table 110.
It also provides a setting that performs a mask that allows it to produce a general trip. In the case the general trip is not
allowed, it can be used to start the recloser or the breaker failure (50BF) by external cause. There is another setting for this unit
to indicate if it can be reclosed, if it is allowed, that is, it works as the rest of the trips.
The settings for the configuration of this unit are shown in Table 110.
❑ External trip - pole A. Selects the signal which, when active, indicates that there is an external A pole trip.
❑ External trip - pole B. Selects the signal which, when active, indicates that there is an external B pole trip.
❑ External trip - pole C. Selects the signal which, when active, indicates that there is an external C pole trip.
❑ External trip - 3 pole. Selects the signal which, when active, indicates that there is an external three-pole trip.
❑ General trip. Indicates if this unit produces general trip or not. For additional details, see the section corresponding to the
recloser (3.12.6).
❑ Reclose permission. Indicates whether each trip type can be reclosed or not, in accordance with the recloser's closing
cycle (see reclosure permission mask).
❑ Enable Events record. Allows the generation of protection events associated to the function. If set to “NO”, the function’s
protection events are not generate. If set to “YES”, the function’s specific mask is contemplated.
This unit's settings and outputs are in the PROT/ZPEXT1 logical node:
❑ Settings and logical inputs. There are 6 settings tables (see Table 110).
❑ No commands are available.
❑ Outputs: Table 110 shows the function’s output data.
External trip pole A. Indicates the activation of an external A pole trip.
External trip pole B. Indicates the activation of an external B pole trip.
External trip pole C. Indicates the activation of an external C pole trip.
External trip 3 pole. Indicates the activation of an external three-pole trip.
External trip 1 pole. Indicates the activation of an external single-pole trip.
External trip Status. Indicates the function’s status.
Used as transmitter, the device sends the signals programmed in the communication node (ITPC).
Used as receiver, the device has all the received signals, in the positions “Teleprotection signal 1”, “Teleprotection signal 2”, up
to “Teleprotection signal 16”. All these signals can be used in the teleprotection schemes.
For example, the signal “ETP 67NQ” can be assigned to the “Digital 1” setting of the ITCP node. The status of “ETP 67NQ” is sent
in the first position of the 16 transmitted signals.
The other device receives this signal as “Teleprotection signal 1”, which can be used as the receipt of the remote protection
signal. This setting is the logical input “TPRx_21 line 1”.
❑ Port Number. When the port exists in the device, the options are:
Disabled. The communication is disabled.
COM 1. The communication is enabled in the port COM1.
COM 2. The communication is enabled in the port COM2.
❑ Comm speed (bauds). It refers to communication speed in the selected port. The options are between 19200 and 115200
bauds.
❑ Parity: It refers to an additional bit used in each character to detect transmission errors. It is selected among "None",
"Even" and "Odd".
❑ Number of Stop bits: Number of bits sent at the end of each character.
❑ Digital 1: It refers to the signal sent in the first position of the message. It can be selected among all the available digital
signals of the device. It is the “Teleprotection signal 1” in the receiver device.
❑ Digital x: where x is from 1 to 16. It refers to the signal sent in the “x” position of the message. It can be selected among all
the available digital signals of the device. It is the “Teleprotection signal x” in the receiver device.
This function has settings and signals:
❑ Node PROT/ITPC1
❑ Settings. There is a setting group. See Table 112.
❑ It has no logical input.
❑ It has no command
❑ Outputs: Table 113 shows the function’s output data:
Teleprotection comms failure: It indicates there is a communication failure.
Teleprot comms config alarm: It indicates a failure in the selection of the communication port. It is activated when the
selected port doesn´t exist or it´s occupied.
Teleprotection signal 1: It refers to the signal received in the first position of the communication message.
Teleprotection signal x: where x is from 2 to 16. It refers to the signal received in the position x of the communication
message.
❑ If a unit trips during a specific recloser status (blocked, in security t, etc.) and the corresponding mask is set to “YES”, the
trip is sent to the general trip output.
❑ If the mask is set to “NO”, the trip is produced but the "direct trip" signal is not received. In this way, the recloser is
independent of any trips used for signalling.
❑ If the recloser is out of service, all the units programmed to produce a general trip will issue a trip.
In the event of a specific trip failing to activate the “general trip”, the fault report is not generated.
If a trip is produced at the same time as another trip which activates the general trip, all the trips are reflected in the fault
report: those which go to GT and those which do not.
The picks ups are affected in the same way as with each unit's trips. Each of the relay’s pickups generates a signal. This signal
passes through the trip mask filter and is included in an OR in order to generate a "General pick up" signal.
ZPMPT node allows the enabled of the monopolar trip. The available settings are:
❑ Enabled. It allows one pole trips. If it is disabled, all trips will be 3 poles trips.
❑ Force three pole. Selects the signal which, when active, forces all the trip to be three poles.
❑ Enable Events record. Allows the generation of protection events associated to the function. If set to “NO”, the function’s
protection events are not generate. If set to “YES”, the function’s specific mask is contemplated.
❑ Single Pole Trip 67NQ16. Allows single pole trips for 67NQ remote protection scheme.
❑ Single Pole Trip Weak Infeed16. It allows single pole trips for Weak Infeed in the Z remote protection scheme Z, or in Z and
67NQ.
❑ Single-phase tripping Status. It indicates that the Single Pole Trip is activated.
❑ Force 3 Pole trip. It indicates that the Force three pole input is activated.
❑ Single phase 67NQ status. It indicates that the Single Pole Trip for 67NQ remote protection scheme is activated.
❑ Single phase WI status. It indicates that the Single Pole Trip for 67NQ remote protection scheme is activated.
Single Pole Trip is provoked when the following conditions are fulfilled:
16
Avaliable from firmware version 6.0.8.0 and ICD version 8.1.0.4
❑ When the recloser is enabled, it must be in standby and the Reclose mode must be one of the single pole recloser (1 pole,
1P/3P o Dependent).
When the recloser is disabled by setting, it doesn´t affect and single Pole Trip is generated when the other conditions are
fulfilled. In that case, a reclose of an external device is allowed.
The three poles trip is generated with all the trips that are not single pole.
Indicates if this unit produces a general trip or not. The protection functions can be enabled or disabled and can trigger a trip
and/or a pickup independently of which units are to open the breaker. The general trip signal is sent to the breaker and is
configured by means of this mask.
In order, upon tripping, for a unit to activate the general trip, it must meet (See Figure 144):
❑ Be enabled.
❑ Have its general trip mask set to YES.
❑ If the recloser is enabled, the unit must not be blocked by the trip permission mask.
Each protection unit has an independent setting which is used to enable or disable its general trip. Its reference is "GenTrip"
and allows the options “NO / YES”.
DIGITAL SIGNAL
79 in service
DIGITAL INPUT
51-1 Trip
AJ 51-1 -> D.G.
DIGITAL INPUT
General trip
DIGITAL INPUT
51-2 Trip
AJ 51-2->D.G.
………………………….
DIGITAL INPUT
Unit X Trip
AJ X->D.G.
This mask is used to select which trips are associated to the “general trip” (with the recloser in service), depending on the status of
the recloser.
Independently of these settings, the protection units pickup and trip, activating their corresponding signals.
The unit that is to produce the trip (activate the general trip signal) can be selected by programming 4 trip masks peer unit and
which are active in the following moments:
Each protection unit has independent masks. If a unit trips during a specific recloser status (blocked, in security t, etc.) and the
corresponding mask is set to “YES”, the trip is sent to the general trip output. If the mask is set to “NO”, the trip is produced but the
"direct trip" signal is not received.
Reclosure block. When selected, the trip of this unit blocks the recloser. Detailed description in the chapter “Post-trip reclosure
permission mask”.
Each protection unit has an independent setting which is used to enable or disable the unit’s permissions. The reference is
“TripPerm”. The setting is configured as a bit field where each bit corresponds to a selection, indicating the integer value:
An example of use with trip permissions in standby and following reclosures would be the decimal value 122 (01111010 in binary),
broken down into:
Bit 7 6 5 4 3 2 1 0
Value 0 1 1 1 1 0 1 0
The maximum permitted value with all permissions enabled is 255 (11111111 in binary).
3.13 CT SUPERVISION
If the event of neutral current in the 4th transformer, a fault may be detected in at least one of the relay input channels (adaptation
transformer + internal circuitry). The absolute value of three times the zero sequence current (calculated using the phase currents) is
compared with the current measured at the transformer, taking the phase (RTF) and neutral (RTN) transformation ratios into account.
None of the phases must exceed 1.5 times the rated current.
The unit activates a “CT monitoring alarm signal” when the following conditions are met.
❑ PROT/CCTS1 node
❑ Settings. There are 6 settings tables.
❑ There are no logical inputs or commands.
❑ Outputs: Table 119 shows the function’s output data.
CT Supervision Status. It is active when enabled and not blocked.
CT Supervision. Indicates that the CT monitoring conditions have been met.
3.14 VT SUPERVISION
The negative and zero sequence voltages are compared with the rated voltage, generating alarm signals.
❑ Vn>10%Vn Supervision: it is active when V0 voltage is greater than the 10% of the rated voltage.
❑ V2>10%Vn Supervision: it is active when V2 voltage is greater than the 10% of the rated voltage.
It has no settings nor commands:
❑ Node GEN/LLN0
❑ Outputs: Table 120 shows the function’s output data.
Table 120 VT supervision outputs
4. BREAKER
❑ Configuration type: Indicates the breaker configuration scheme. It can be set to “Single” or "Breaker and a Half". Available
only in the XCBR1.
❑ Breaker type: Indicates the type of breaker employed:
1 or 2 DI.General Status. Only one input is used for the status of the three poles.
3 or 6 DI.Per Pole. An independent input is used for the status of each of the three poles.
❑ Pole failure time (ms): Indicates the time (ms) during which the difference between the type a and type b inputs must be
detected in the breaker status in order for the failure to be registered. Although the setting is unique, it affects the three
poles.
❑ 52a input: If the breaker type is "1 or 2 DI.General Status", it indicates the breaker status.
❑ 52a-Pole A: If the breaker type is "3 or 6 DI.Per Pole", it indicates the phase A breaker status.
❑ 52a-Pole B: The same as phase A, but for B.
❑ 52a-Pole C: The same as phase A, but for C.
❑ 52b input: If the breaker type is "1 or 2 DI.General Status", it indicates the breaker status.
❑ 52b-Pole A: If the breaker type is "3 or 6 DI.Per Pole", it indicates the phase A breaker status.
❑ 52b-Pole B: The same as phase A, but for B.
❑ 52b-Pole C: The same as phase A, but for C.
❑ Open blocking: When active, it blocks the manual breaker open commands. The trips are not blocked.
❑ Close blocking: When active, it blocks the breaker closure commands.
❑ Breaker open command input: When active, it generates a breaker open command.
❑ Close command input: When active, it generates a breaker closure command.
❑ 52 Blocking input: When active, it indicates the breaker is blocked. It is used in 50BF, open pole detector and recloser.
❑ Trip sealed: Allows the open commands to be enabled. When it is enabled, the open command is maintained after the
cause of the trip has disappeared and until the breaker is detected as open.
❑ Close sealed: Allows the closure commands to be enabled. When it is enabled, the closure command is maintained after
the cause of the closure has disappeared and until the breaker is detected as closed.
❑ Enable Events record: Allows the generation of protection events associated to the function. If set to “NO”, the function’s
protection events are not generated. If set to “YES”, the function’s specific mask is contemplated.
❑ 52 Supervision: Allows breaker status supervision function.
❑ Sync. Delay Time (s). This is the maximum time waited before the synchronism grants permission before a manual closure.
If closure permission is granted before the conclusion of this time, a closure command is issued. On the other hand, if this
time elapsed without permission being granted, the closure commnad is not executed. 17
❑ Synchrocheck supervision18. Indicates whether the manual closure is to be monitored with synchronism. If it´s set “YES”,
the manual close permission must be activated to generate the close command .
❑ Synchrocheck type18. Indicates whether the synchronism is internal or external.
17
Available from firmware version 5.19.15.7 and ICD version 6.3.0.0.
18
Available from firmware version 6.0.18.0 and ICD version 8.1.0.0
❑ External syncro. Permission18. Logical external synchronism permission logic. Selects the signal which, when active,
indicates the existence of permission for synchronism.
❑ Min.time general trip(ms)19. Indicates the minimum duration time of the general trip signals per pole and global;
independently if the signal that causes the trip is deactivated before this time.
The status of the general breaker and by pole is determined with the status of digital inputs and breaker type setting. Used to
determine the status of the breaker without uncertainty and employed in functions that require the breaker’s status to be known,
such as the opening and closure sealing logic, the recloser, etc.
The 52b status inputs take precedence over the 52a status inputs, i.e., if 52b status inputs have been configured, the breaker status
is determined by means of these inputs, independently of the status of the 52a inputs.
❑ 1 or 2 DI.General Status. The general 52b Status input is used for the breaker status. If it is not configured, the general 52a
Status input is used. The phase breaker status matches the general.
❑ 3 or 6 DI.Per Pole. The independent phases 52b Status inputs are used for the breaker status. If they are not configured,
the independent phases 52a Status inputs are used. The general breaker status is generated from the phases, taking into
account the following:
Closed general status, if all the phases are closed.
Open general status, if at least one of the phases is open.
Table 122 shows this function’s outputs.
❑ 52_1 Closed (Simple Log.). Indicates the breaker's general status, in accordance with the status of the digital inputs.
❑ 52_1 X Closed (Simple Log.). Indicates the status of each of the breaker's phases, in accordance with the status of the
digital inputs. Where "X" indicates the pole (A, B or C).
19
Available from firmware version 6.0.18.2 and ICD version 8.2.0.0
The status of each pole (open, closed) is determined in accordance with a combination of N/O and N/C inputs. If inconsistencies are
detected between the N/O and the N/C inputs after the failure time (”Pole failure time (ms)”), a failure is signalled and no other
action is taken (relative to the discrepancy) until the anomaly is corrected. The functioning of this unit is shown in Figure 145.
❑ PROT/XCBR1 node
❑ PROT/XCBR2 node. Applies only in configurations with 2 switches
❑ Settings and logical inputs. There are 6 settings tables. For details see Table . The setting "Configuration type" is only
available in XCBR1, while the rest are on both nodes.
❑ There are associated commands:
Pos. Switch opening or closure command.
LOrdLc52Op. Local mode switch opening or closure command.
LOrdMaBl. Locking or unlocking operations command for switch in local mode.
BlkCls. Locking or unlocking switch closure operations command.
❑ Outputs: Table 122 shows the function’s output data.
52_1 Open: Indicates that the 52 is open. There are independent general and phase signals.
52_1 Closed: Indicates that the 52 is closed. There are independent general and phase signals.
52_1 Undetermined: Indicates that the 52 is undetermined. There are independent general and phase signals.
52_1 Failure: Indicates that the 52 has a failure. There are independent general and phase signals.
Close Command - Breaker 1: Indicates that a closure command has been generated.
Open Command - Breaker 1: Indicates that an opening command has been generated.
Ph. X Open Command - Br1: Indicates that a Phase X opening command has been generated. X can be A, B or C.
Close Failure - Br1: Indicates that a failure has occurred in some closing switch pole because maximum closing
time has exceeded.
Ph. X Close Failure- Br1: Indicates that a failure has occurred in closing switch X pole because maximum closing
time has exceeded. X can be A, B or C.
Open Failure - Br1: Indicates that a failure has occurred in some opening switch pole because maximum closing
time has exceeded.
Ph. X Open Failure- Br1: Indicates that a failure has occurred opening switch X pole because maximum closing
time has exceeded. X can be A, B or C.
Breaker settings error: Indicates that breakers are not properly defined and it is activated in the following
situations:
No consistency between the breakers and recloser setting: "Select 2 breakers"
No consistency between the breakers and breaker setting: "Configuration type".
In Figure 145 the state switch logic diagram is displayed. Input signals to this scheme are:
❑ Enab, Logic 52_1: This input indicates the state 52 detection mode. Corresponds to XCBR "52 Status detection" setting and
allows the following values:
"1 or 2 DI.General Status": There is only one digital input to indicate the switch status.
"3 or 6 DI.Per Pole". There are three digital inputs to indicate the status of each phase.
❑ 52a input: Indicates the switch a logic input. Applies to "52a input" setting. Active if the switch is closed.
❑ 52b input: Indicates the switch b logic input. Applies to "52b input" setting. Active if the switch is open.
❑ 52a Pole A: Indicates the phase A 'a logic' input. Applies to "52a-Pole A" Active if the pole is closed.
❑ 52b Pole A: Indicates the phase A 'b logic' input. Applies to "52b-Pole A" Active if the pole is open.
❑ 52a Pole B: Indicates the phase B 'a logic' input. Applies to "52a-Pole B" Active if the pole is closed.
❑ 52b Pole B: Indicates the phase B 'b logic' input. Applies to "52b-Pole B" Active if the pole is open.
❑ 52a Pole C: Indicates the phase C 'a logic' input. Applies to "52a-Pole C" Active if the pole is closed.
❑ 52b Pole C: Indicates the phase C 'b logic' input. Applies to "52b-Pole C" Active if the pole is open.
SETTING
Enab. Logic 52_1 = 1 POLE / 4 STATUSES
SETTING
DIGITAL INPUT POLE
FAILURE T
52a input
0
DIGITAL INPUT
52b input
SETTING
DIGITAL INPUT POLE DIGITAL SIGNAL
FAILURE T DIGITAL SIGNAL 52_1 Undetermined
52a-Pole A
52_1 phase A Undetermined
0
DIGITAL SIGNAL
52_1 phase A Open
DIGITAL SIGNAL
52_1 phase A Closed
DIGITAL SIGNAL
52_1 phase A Failure
DIGITAL INPUT
52b-Pole A
SETTING
DIGITAL INPUT POLE
FAILURE T DIGITAL SIGNAL
52a-Pole B
52_1 phase B Undetermined
0 DIGITAL SIGNAL
DIGITAL SIGNAL 52_1 Open
52_1 phase B Open
DIGITAL SIGNAL
52_1 phase B Closed
DIGITAL SIGNAL
52_1 phase B Failure
DIGITAL INPUT
52b-Pole B
This unit’s settings are grouped in PROT/RBFS1 (breaker 1) and (PROT/RBFS2) logical nodes:
❑ Open failure time (ms): If an open command is given, the breaker should be open before this time.
❑ Close failure time (ms): If a close command is given, the breaker should be closed before this time.
❑ Enable Events record: Allows the generation of protection events associated to the function. If set to “NO”, the function’s
protection events are not generated. If set to “YES”, the function’s specific mask is contemplated.
Table 122 shows the operating logic’s output Data, which are available in the PROT/XCBR nodes.
Figure 146 Trip logic scheme shows Trip logic scheme. The input signals of this scheme are:
❑ Trip Sealed 52-1: Setting that indicates whether trip will be sealed after completing trip conditions and manual opening.
Corresponds to XCBR setting "Trip sealed".
❑ General Trip: Corresponds to the signal "General trip" generated with any trip.
❑ Pole A (B,C) General Trip: Corresponds to the signals "Pole A General Trip", (B, C) generated with any phase trip.
❑ Manual open command input**: Indicates that open command has been generated by the logic input "Open Command -
Breaker 1" or by user command.
❑ Manual Open blocking: Indicates that blocking command has been generated by the logic input "Open blocking" or by user
command.
❑ 52a pole A: Enabled indicates that phase A is closed. Corresponds to the signal "52_1 A Closed (Simple Log.)".
❑ 52a pole B: Enabled indicates that phase B is closed. Corresponds to the signal "52_1 B Closed (Simple Log.)".
❑ 52a pole C: Enabled indicates that phase C is closed. Corresponds to the signal "52_1 C Closed (Simple Log.)".
Figure 147 shows Closure logic scheme. The input signals of this scheme are:
❑ General trip: Indicates the signal generated with any trip. It is shown in "General trip".
❑ Manual open command: Internal signal indicating that open command has been generated by the logic input "Breaker
open command input" or by user command, and is not blocked by the logic input "Open blocking" neither by user
command.
❑ Close sealed: Setting that indicates whether will be sealed after completing the close order. Corresponds to the XCBR
"Close sealed" setting.
❑ RECLOSURE Command**: Internal signal indicating an OR of the reclosure commands. They are displayed on signals "52_1
Reclose Command" (switch reclosure) and "Reclosing Command F_RREC" (frequency reclosure). It should not be blocked
by the logic input "Close Blocked" neither by user command.
❑ Close command: Indicates the logic input "Close Command - Breaker" is enabled, a closure order has been launched by
user command or a close order coupling. Formerly sincrocheck's "Perm. Manual Close" must be enabled and must not be
blocked by the logic input "Close blocking" neither by user command.
❑ 52_1 closed: Signal indicating that switch is closed. Corresponds to the "52_1 Closed (Simple Log.)" signal.
❑ 52_1A closed: Signal indicating that phase A is closed. Corresponds to the "52_1 A Closed (Simple Log.)" signal.
❑ 52_1B closed: Signal indicating that phase B is closed. Corresponds to the "52_1 B Closed (Simple Log.)" signal.
❑ 52_1C closed: Signal indicating that phase C is closed. Corresponds to the "52_1 C Closed (Simple Log.)" signal.
In order for a pole to be considered open, a combination of the following conditions must be met (depending on the operation type
setting):
❑ A phase’s breakers indicate that the phase is open (in the case of 1 ½ breaker, two are employed)
❑ The current is below the threshold set in the open pole due to current detection logic.
❑ The current and the voltage are below the threshold (according to the setting). In this case, if there is a fuse failure the
open pole due to voltage signal is not activated.
To determine the breaker’s status by digital input, the 52b (normally closed) of each phase is employed, when configured. If the
52b is not configured, the 52a is used (normally open).
If a single pole open is detected, the following functions can be blocked, if they are selected by settings:
There is a delay of one cycle before the reset of the 1PO output (when the breaker closes).
Figure 148 shows Open pole detector scheme. The input signals of this scheme are:
❑ 52_1A Closed: Signal indicating that phase A is closed. Corresponds to the "52_1 A Closed (Simple Log.)" signal.
❑ 52_1 Closed: Signal indicating that switch is closed. Corresponds to the "52_1 Closed (Simple Log.)" signal.
❑ 52_1 Blocked: Internal signal indicating that switch is blocked by the breaker 1 logical input "Close blocking" or by a
blocking user command.
❑ 52_2A Closed: Signal indicating that phase A is closed. Corresponds to the "52_2 A Closed (Simple Log.)" signal.
❑ 52_2 Closed: Signal indicating that switch is closed. Corresponds to the "52_2 Closed (Simple Log.)" signal.
❑ 52_2 Blocked: Internal signal indicating that switch is blocked by the breaker 2 logical input "Close blocking" or by a
blocking user command.
❑ Configuration type = Breaker and a Half: Setting that allows to select switches configuration schemes. Corresponds to the
setting "Configuration type".
❑ Phase A Open ( I < ): Signal "Phase A Open ( I < )".
❑ DeadLine Phase A: Signal indicating that phase A is de-energized. Corresponds to "Deadline Phase A" signal.
And their equivalents for phases B and C.
Figure 148 Open pole detector scheme
The settings for the configuration of the open pole detector are shown in Table 124 Open pole detector settings
❑ Enable Events record. Allows the generation of protection events associated to the function. If set to “NO”, the function’s
protection events are not generated. If set to “YES”, the function’s specific mask is contemplated.
Table 124 Open pole detector settings
❑ PROT/POPD1 node
❑ Settings and logical inputs. There are 6 settings tables. See Table 124.
❑ Commands:
“DOrdBlk”: Function block and unblocking. Only acts if the unit is enabled.
❑ Outputs: Table 125 shows the function’s output data.
Open Pole Status. It is active when enabled and not blocked.
Pole A Open. Indicates that the open pole conditions have been met in phase A.
Pole B Open. Indicates that the open pole conditions have been met in phase B.
Pole C Open. Indicates that the open pole conditions have been met in phase C.
1PO- One Pole Open. Indicates that there is only one pole open (A, B or C).
2PO- Two Pole Open. Indicates that there are two poles open.
3PO- Three Pole Open. Indicates that there are three poles open.
PO-Some Pole Open. Indicates that at least one pole is open, but not all three.
Phase A Open ( I < ). Indicates that the phase A current is below the threshold.
Phase B open ( I < ). Indicates that the phase B current is below the threshold.
Phase C open ( I < ). Indicates that the phase C current is below the threshold.
Deadline Phase A. Indicates that pole A is de-energized.
Deadline Phase B. Indicates that pole B is de-energized.
Deadline Phase C. Indicates that pole C is de-energized.
Deadline Phase ABC. Indicates that the three poles are de-energized.
If the open pole detection is activated in at least one of the phases, the phases overcurrent instantaneous units are reset.
The output signals are in the PROT/POPD node (see Table 125):
❑ Phase A Open ( I < ). Indicates that the phase A current is below the threshold.
❑ Phase B open ( I < ). Indicates that the phase B current is below the threshold.
❑ Phase C open ( I < ). Indicates that the phase C current is below the threshold.
Figure 149 Open pole due to current scheme
ANALOGUE INPUT
DIGITAL SIGNAL
IA (min (dft,dft ½)) +
< Phase A Open ( I < )
SETTING -
ANALOGUE INPUT
DIGITAL SIGNAL
IB (min (dft,dft ½)) +
-
< Phase B Open ( I < )
DIGITAL SIGNAL
ANALOGUE INPUT +
< Phase C Open ( I < )
IC (min (dft,dft ½)) -
The output signals are in the PROT/POPD node (see Table 125):
❑ 52_1 failure: Indicates that 52 is in fault because "Pole failure time (ms)" time has been exceeded. Corresponds to "52_1
Failure" signal.
❑ 52_1 phase A open: Signal indicating that switch is closed. Corresponds to the "52_1 A Closed (Simple Log.)" signal
deactivated.
❑ 52_1 phase B open: Signal indicating that switch is closed. Corresponds to the "52_1 B Closed (Simple Log.)" signal
deactivated.
❑ 52_1 phase C open: Signal indicating that switch is closed. Corresponds to the "52_1 C Closed (Simple Log.)" signal
deactivated.
Equivalent signals are used in switch 2.
The settings for the configuration of this unit are shown in Table 126.
❑ Node:
PROT/RPLD1 for Breaker 1.
PROT/RPLD2 for Breaker 2.
❑ Settings and logical inputs. There are 6 settings tables.
❑ Commands:
“DOrdBlk”: Function block and unblocking. Only acts if the unit is enabled.
❑ Outputs: Table 127 Pole discordance outputs shows the function’s output data.
Pole Discordance Status. It is active when enabled and not blocked.
52_1 Start Discordance. Indicates that the function has started.
52_1 Trip Discordance. Indicates that the function has tripped.
52_1 Discordance open 1P. Indicates that there is discordance with only one open pole.
52_1 Discordance open 2P. Indicates that there is discordance with two open poles.
Table 127 Pole discordance outputs
It monitors the breaker’s operations after the trip and closure commands. In addition to signals, the counters generated by these
functions are shown in the statistical data.
❑ In models, where there is only one current input, ki2 and electrical supervisions are only performed on breaker 1. In
breaker 2 only mechanical operations are supervised. See Table 128 (breaker 1) and Tabla 129 (breaker 2) for settings and
Table 130 and Table 131 for signals.
❑ In models, where there are two current inputs, ki2 and electrical supervisions are performed on both breakers. See Table
128 and Table 130 for both breakers.
The settings for the configuration of this unit are shown in Table 128 (breaker 1) and Tabla 129 (breaker 2):
❑ ki2 calculation type. Indicates the calculation type between kI2*t, kI2 and kI.
❑ ki2 time (ms). Indicates the timeout following the trip for the measurement of the ki1 calculation current.
❑ Alarm value ki2. Indicates the ki2 summation threshold which, when exceeded, generates a “ki2 exceeded” signal.
❑ Initial value ki2. Indicates the initial value of the ki2 summation when a reset command is received.
❑ Trips exceeded window (min). Time window in minutes for the excessive number of trips counter.
❑ Maximum number of trips. Maximum number of trips permitted in the set time window.
❑ Mechanical opening T (ms). Indicates the maximum time as of the opening command until the detection of the open pole
by the digital input status.
❑ Mechanical closing T (ms). Indicates the maximum time as of the closure command until the detection of the closed pole
by the digital input status.
❑ Electrical opening T (ms). Indicates the maximum time as of the opening command until the detection of the absence of
current in the phase.
❑ Electrical closing T (ms). Indicates the maximum time as of the closure command until the detection of the presence of
current in the phase.
❑ Inactivity time (days). Indicates the maximum number of days without breaker activity.
❑ Opening dispersion T (ms). Indicates the maximum dispersion time between two poles upon opening.
❑ Closing dispersion T (ms). Indicates the maximum dispersion time between two poles upon closing.
❑ Enable Events record. Allows the generation of protection events associated to the function. If set to “NO”, the function’s
protection events are not generated. If set to “YES”, the function’s specific mask is contemplated.
❑ Node
PROT/CBOU1 for Breaker 1.
PROT/CBOU2 for Breaker 2.
❑ Settings. There are 6 settings tables. See Table 128 and Tabla 129.
❑ Outputs: Table 130 shows the function’s output data. The meaning of each signal is detailed in the function explanation.
Tabla 129 Operation monitoring settings in Breaker 2 (models with one current input)
Table 131 Monitoring signals in Breaker 2 (models with one current input)
kI2 sum:
After a trip, the kI2 counter increases in accordance with the selected setting. The value of each phase’s current is calculated in
primary (VT ratio), as kA primary. There are a total of 3 counters (one for each phase). Additionally20, it is available a counter of
maximun kI2, where in each opening the maximum value of the three phases is used to calculate the ki2.
If it exceeds the set threshold (the treatment is pole to pole), a “Phase X Ki2 exceeded” signal is generated. While in this situation, the
corresponding signal is sent to control. The signals are:
❑ Phase X ki2 exceeded. Where X is the phase. It is independent for each phase.
❑ ki2 exceeded. One for all the phases.
❑ Maxki2 exceeded. Activated when the counter of maximun kI2 exceeds the set threshold.
In order to calculate the pole wear, the type of calculation wanted can be programmed from among kI2*t, kI2 and kI.
❑ If Ki2 is chosen, the kA2 are calculated with I as the current measured after exceeding the set timeout following the trip.
❑ If kI is chosen, only the sum of the currents in kA is calculated, with I as the current measured after exceeding the set timeout
following the trip.
20
Available from version 5.24.16.1 of firmware and 7.0.0.0 of ICD.
❑ If Ki2 *t is chosen, the Ki2 /100 value is accumulated every 10ms, with I as the current measured after exceeding the set timeout
following the trip. The accumulation terminates when I<0.05 A.
Excessive number of trips:
It counts the trips produced in the time, generating a signal when the number of trips is higher than the programmed number during
the programmed time and changes to a definite trip. The time period is reset upon a manual closure. The counter may be reset to the
initial value at any moment by means of a command. The signals are:
There are independent open and trip counters for each phase:
Closure counters:
There are independent closure counters for each phase. A breaker's changes from open to close are considered closures.
They count the time elapsed from the command sent to the breaker unto its electric operation, measured with the current:
❑ Trip time: The time elapsed from the open command until the detection of the absence of power.
❑ Closure time: The time elapsed from the closure command until the detection of the presence of power.
The open pole detector current threshold is used.
These times are compared with the threshold settings. Events are generated per pole when the thresholds are exceeded “Pole X
electric time exceeded”:
❑ If the time elapsed from the open command exceeds the setting “Electrical opening T (ms)”
❑ If the time elapsed from the closure command exceeds the setting “Electrical closing T (ms)”
Mechanical opening and closure operating time per pole:
They count the time elapsed from the command sent to the breaker unto its mechanical operation, detected in the digital inputs
status:
❑ Trip time: Indicates the time elapsed as of the opening command until the detection of the open pole by the digital input status.
❑ Closure time: Indicates the time elapsed as of the closure command until the detection of the closed pole by the digital input
status.
These times are compared with the threshold settings. Events are generated per pole when the thresholds are exceeded “Pole X
mechan.time exceeded”:
❑ If the time elapsed from the open command exceeds the setting “Mechanical opening T (ms)”
❑ If the time elapsed from the closure command exceeds the setting “Mechanical closing T (ms)”
Opening and closure dispersion time for each pole pair:
They count the difference between the opening and closure times for every two poles. There are opening/closure counters for pole
pairs AB, BC and CA. The breaker status is determined by means of the digital input status.
These times are compared with the threshold settings. Events are generated per pole when the thresholds are exceeded “XY dispersion
time exceeded”:
❑ During the opening, a comparison is made with the "Opening dispersion T (ms)" setting.
❑ During the closure, a comparison is made with the "Closing dispersion T (ms)" setting.
The days elapsed, since the last opening or closure of the breaker, are counted for each pole. Complete fractions of 24 hours since the
last action are considered. Partial periods of 24 hours are not accumulated, i.e., if 2 days and 20 hours have passed since the last action,
the counter will indicate 2 days. If at this point the time count is reset to zero, the 20 hours would be lost.
These counters are compared with the “Inactivity Time (days)” setting and an event is generated per pole in the event of it being
exceeded "Pole X inactivity time exceeded".
The maximum current value measured at the moment of the trip is indicated per pole. The three poles can be reset to zero using the
reset command.
Overcurrent levels:
Indicates the time in seconds during which each phase's current is within each of the following ranges (with In as the set rated current):
It monitors the circuits by pole, detecting any discontinuity with the breaker open and closed. It requires the assignment of the
monitoring inputs (the breaker circuit with open and closed breaker, the closure circuit with open and closed breaker). It is activated 20
seconds after the detection of the fault and remains active while the fault persists.
Up to six trip circuits and three closure circuits can be monitored, using the number of digital inputs required.
Figure 153 Closure circuit monitoring Figure 153 shows an example of the wiring for the monitoring of the closure circuit. The wiring for
the trip circuit is similar.
When the breaker is closed, the “52a” contact is also closed. If there is continuity in the circuit, the input programmed as “Close circuit
52 closed” is detected as closed. If there is no continuity, it is detected as open (circuit failure).
When the breaker is open, the “52b” contact is also closed. If there is continuity in the circuit, the input programmed as “Close circuit
52 open” is detected as closed. If there is no continuity, it is detected as open (circuit failure).
The “closing coil failure” or “trip coil failure” signals are activated 20 seconds after the fault is detected, in the event of the fault
persisting upon the conclusion of this period.
The settings for the configuration of this unit are shown in Table 132:
❑ Trip circuit enabled: Enables the monitoring of the trip circuits.
❑ Close circuit enabled: Enables the monitoring of the closure circuits.
❑ Close circuit 52 open - X. Indicates the signal used to monitor the closure circuit with the breaker open.
❑ Close circuit 52 closed - X. Indicates the signal used to monitor the closure circuit with the breaker closed.
❑ Open circuit 52 open - X. Indicates the signal used to monitor the trip circuit with the breaker open.
❑ Open circuit 52 closed - X. Indicates the signal used to monitor the trip circuit with the breaker closed.
❑ Enable Events record. Allows the generation of protection events associated to the function. If set to “NO”, the function’s
protection events are not generated. If set to “YES”, the function’s specific mask is contemplated.
❑ Node.
PROT/RBCS1: breaker1's circuit supervision.
PROT/RBCS2: breaker 2's circuit supervision.
❑ Settings and logical inputs. There are 6 settings tables. See Table 132.
❑ Outputs: Table 133 shows the function’s output data.
X trip coil failure. Indicates that there has been failure in the pole X trip coil.
X closing coil failure. Indicates that there has been failure in the pole X closure coil.
1 trip circuit failure. Indicates that there has been failure in the trip coil of pole A1, B1 or C1.
2 trip circuit failure. Indicates that there has been failure in the trip coil of pole A2, B2 or C2.
1 closing circuit failure. Indicates that there has been failure in the closure coil of pole A1, B1 or C1.
2 closing circuit failure. Indicates that there has been failure in the closure coil of pole A2, B2 or C2.
5. DISCONNECTOR
The disconnector unit uses the PROT/XSWI1 logical node. The settings used are:
Disconnector status
The status of the general disconnector and by pole is determined with the status of digital inputs and disconnector type setting.
Used to determine the status of the disconnector without uncertainty and employed in functions that require the disconnector’s
status to be known, such as the stub bus protection, etc.
The 89b status inputs take precedence over the 89a status inputs, i.e., if 89b status inputs have been configured, the disconnector
status is determined by means of these inputs, independently of the status of the 89a inputs.
❑ 1 or 2 DI.General Status. The "89b general status" input is used for the disconnector status. If it is not configured, the "89a
general status" input is used. The phase disconnector status matches the general.
❑ 3 or 6 DI.Per Pole. The independent "89b Pole X status" inputs are used for the disconnector status. If they are not
configured, the "89a Pole X status" inputs are used, where "X" indicates the pole (A, B or C). The general disconnector
status is generated from the phases, taking into account the following:
Closed general status, if all the phases are closed.
Open general status, if at least one of the phases is open.
Table 135 shows this function’s outputs.
❑ Disconnector 1 Status (DI). Indicates the disconnector's general status, in accordance with the status of the digital inputs.
❑ Disconnector 1 X Status (DI). Indicates the status of each of the disconnector's phases, in accordance with the status of the
digital inputs. Where "X" indicates the pole (A, B or C).
Table 135 Disconnector status outputs
6. AUTOMATISMS
The close command of the breaker can be manual close command or automatic (recloser):
❑ Three poles close command can be monitored by synchronism; while one pole close commands are not monitored by synchronism
❑ Manual close command can be monitored by synchronism
6.1 SYNCHRONISM
The synchronism function or “Synchrocheck” waits for the appropriate conditions established in the settings, to determine breaker
closure, both manual and automatic.
Two voltage signals from the two sides of the breaker, which we will call side A and side B, are compared.
Side A corresponds to the voltage input selected with the setting “Side A Phase Select”. This setting selects the analogue input used.
The selection between ground to phase and phase to phase voltages is made with the setting “Operating Voltages” of the node TVTR.
With this setting a compensation factor is applied to equalize the module and the angle of the two voltages compared (side A and side
B).
Side B corresponds to the analogue voltage input connected to the synchronism voltage terminals.
Table 136 shows the settings of this function for undervoltage and synchronism:
❑ Enabled. Indicates whether the function is enabled or not. When enabled, the function tests the synchronism conditions. When
disabled, manual closure permission is granted, but automatic permission is refused.
❑ Side A phase Select: selectable between A/AB, B/BC or C/CA, corresponding to the measurement of the selected voltage
transformer. A/AB for transformer 10, B/BC for transformer 11 and C/CA for transformer 12.
❑ Compensation factor (Vs1): the factor by which the module is multiplied in order to equalize the voltages.
❑ Compensation angle (Vs1): the factor to be added to the angle in order to equalize the voltages.
❑ A-Side Voltage presence (V): the voltage measured in side A must exceed this value in order to consider that there is voltage on
that side of the breaker.
❑ A-Side Lack of Voltage (V): the voltage measured in side A must be lower than this value in order to consider that there is an
absence of voltage on that side of the breaker. It must be at least 5% less than Voltage presence.
❑ B-Side Voltage presence (V): the voltage measured in side B must exceed this value in order to consider that there is voltage on that
side of the breaker.
❑ B-Side Lack of Voltage (V): the voltage measured in side B must be lower than this value in order to consider that there is an
absence of voltage on that side of the breaker. It must be at least 5% less than Voltage presence.
❑ Autoreclose condition. Indicates the conditions for granting reclosing permission with undervoltage:
Without permission: under no circumstances will the function grant undervoltage permission
Not A and Yes B: there must be an absence of voltage on side A and presence of voltage on side B in order for the function to
grant undervoltage permission.
Yes A and Not B: there must be an absence of voltage on side B and presence of voltage on side A in order for the function to
grant undervoltage permission.
Not A and Not B: there must be an absence of voltage on both sides of the breaker in order for the function to grant
undervoltage permission.
Not A or Not B: there must be an absence of voltage on one of the sides of the breaker in order for the function to grant
undervoltage permission.
A xor B: there must be voltage presence on one side of the breaker and an absence on the other in order for the function to
grant undervoltage permission.
Not A: there must be an absence of voltage on side A in order for the function to grant undervoltage permission.
Not B: there must be an absence of voltage on side B in order for the function to grant undervoltage permission.
❑ Manual closing condition. Indicates the conditions for granting manual closing permission with undervoltage:
Without permission: under no circumstances will the function grant undervoltage permission
Not A and Yes B: there must be an absence of voltage on side A and presence of voltage on side B in order for the function to
grant undervoltage permission.
Yes A and Not B: there must be an absence of voltage on side B and presence of voltage on side A in order for the function to
grant undervoltage permission.
Not A and Not B: there must be an absence of voltage on both sides of the breaker in order for the function to grant
undervoltage permission.
Not A or Not B: there must be an absence of voltage on one of the sides of the breaker in order for the function to grant
undervoltage permission.
A xor B: there must be voltage presence on one side of the breaker and an absence on the other in order for the function to
grant undervoltage permission.
Not A: there must be an absence of voltage on side A in order for the function to grant undervoltage permission.
Not B: there must be an absence of voltage on side B in order for the function to grant undervoltage permission.
❑ Enabling of synchrocheck with reclosure:
None: under no circumstances will the function grant synchronism permission.
No compensation: comparisons between angles, modules and frequencies are taken into account to grant permission if the set
conditions are met during the programmed time
With compensation: in addition to the module and frequency comparisons, breaker close time is taken into account. See
Figure 154.
Zero compensation: a specific case of enabling with compensation and also taking into account that closure permission will be
granted when the angle difference is 0°. See Figure 154.
Always.21 The function grants synchronism permission with present of voltage on both sides of the breaker.
❑ Enabling of synchrocheck with manual closure:
None: under no circumstances will the function grant synchronism permission.
No compensation: comparisons between angles, modules and frequencies are taken into account to grant permission if the set
conditions are met during the programmed time
With compensation: in addition to the module and frequency comparisons, breaker closure time is taken into account. See
Figure 154.
Zero compensation: a specific case of enabling with compensation and also taking into account that closure permission will be
granted when the argument difference is 0°. See Figure 154.
Always.21 The function grants synchronism permission with present of voltage on both sides of the breaker.
❑ Breaker close time (s): taken into account when calculating the angle difference and providing that the enabling "with
compensation" has been programmed. In this case, the frequency slip is taken into account to compensate for this time.
❑ Voltage difference (V): the difference between the voltage modules on side A and side B must be less than this value in order for
permission to be granted.
❑ Frequency difference (Hz): the difference between the frequencies on side A and side B must be less than this value in order for
permission to be granted.
❑ Angle difference (º): the difference between the voltage angles on side A and side B must be less than this value in order for
permission to be granted.
❑ Slip threshold (Hz): if the difference between the frequencies in side A and side B is greater than this value there is frequency slip.
Otherwise, it is not considered frequency slip.22
❑ Sync.Time Man.closing(ms): the time during which the conditions for the granting of permission for closure must be met.
❑ Sync. Time Autoreclose(ms): the time during which the conditions for the granting of permission for reclosure must be met.
❑ Blocking input: logic input which, when active, blocks the function. When blocked, manual closure permission is granted, but
automatic permission is refused.
❑ Close blocking: logic input which, when active, blocks the breaker close permission (manual and automatic).
21
Available since firmware version 6.0.18.0 and ICD 8.1.0.0
22
Available since firmware version 5.17.15.2 and ICD 6.1.13.27
❑ Fuse failure signal: fuse failure logic input which, when active, blocks the breaker close permission (manual and recloser)
❑ A-Side Maximum V. (V)21. To fulfill the synchronism, the side A voltage must be greater than the “A-Side Voltage presence (V)”
setting and below the "A-Side Maximum V" setting. If they are set to the same value, the "A-Side Maximum V" is considered
200V.
❑ B-Side Maximum V. (V)21. To fulfill the synchronism, the side B voltage must be greater than the “B-Side Voltage presence (V)”
setting and below the "B-Side Maximum V" setting. If they are set to the same value, the "B-Side Maximum V" is considered
200V.
❑ A-Side V aux23. It selects the voltage that replaces the synchronization voltage on the A side when the logic input "Side A-V switch"
is activated. The options are:
Not apply. The option is disabled.
Vline. It selects the voltage input selected with the setting “Side A Phase Select”.
Vs1. It selects the voltage input connected to the synchronism voltage terminals Vs1.
Vs2. It selects the voltage input connected to the synchronism voltage terminals Vs2.
❑ Side A-V switch.23 Logic input which, when active, replaces the line voltage from side A with the one selected in "A-Side V aux".
When the voltage is switched, the compensation factors to be used are those corresponding to the selected voltage. The signal " A
Side V aux selected " is also activated.
❑ B-Side V aux. 23 It selects the voltage that replaces the synchronization voltage on the B side when the logic input " Side B-V switch"
is activated. The options are:
Not apply. The option is disabled.
Vline. It selects the voltage input selected with the setting “Side A Phase Select”.
Vs1. It selects the voltage input connected to the synchronism voltage terminals Vs1.
Vs2. It selects the voltage input connected to the synchronism voltage terminals Vs2.
❑ Side B-V switch.23 Logic input which, when active, replaces the line voltage from side B with the one selected in "B-Side V aux".
When the voltage is switched, the compensation factors to be used are those corresponding to the selected voltage. The signal “B
Side I1 V aux selected" is also activated.
The synchronism function can be disabled by means of a setting (“NO”). By means of a “fuse failure” or a “breaker closure permission
block” digital input both manual and automatic permission are refused.
When disabled, manual closure permission is granted but not automatic closure permission. In order to give closure permission when
enabled, the function contemplates the conditions that grant undervoltage permission or synchronism permission. If any of them
grants permission, closure permission is granted. Manual and automatic closure permissions are analysed independently.
❑ Undervoltage:
When disabled undervoltage permission is refused.
When enabled, undervoltage conditions are analysed. If undervoltage permission is granted, closure permission is granted,
independently of synchronism conditions.
❑ Synchronism: when undervoltage permission is not granted, synchronism conditions are analysed.
When disabled synchronism permission is refused.
When enabled, synchronism conditions are analysed.
23
Available since firmware version 6.0.18.2 and ICD 8.2.0.0
24
Available since firmware version 6.0.18.0 and ICD 8.1.0.14
❑ Positive slip Breaker 1: it is active if the frequency on the side B is also greater than that on side A by more than the setting.
❑ Negative slip Breaker 1: it is active if the frequency on the side A is also greater than that on side B by more than the setting.
❑ Underfrequency side B B1: it is active if the frequency difference of both sides exceeds the setting value and the frequency on side
A is greater than that on side B.
❑ Overfrequency side B B1: it is active if the frequency difference of both sides exceeds the setting value and the frequency on side B
is greater than that on side A.
❑ Delay without comp. side B 1: when the difference between the angles exceeds the setting value and is greater on side A than on
side B.
❑ Adv. without comp.side B B1: when the difference between the angles exceeds the setting value and is greater on side B than on
side A.
❑ Delay with comp. side B 1: when the difference between the angles, calculated by taking into account breaker closure time,
exceeds the setting value and is greater on side A than on side B.
❑ Advance with comp. side B 1: when the difference between the angles, calculated by taking into account breaker closure time,
exceeds the setting value and is greater on side B than on side A.
❑ Over Module side B B1: when the voltage difference is greater than the programmed setting and the voltage in B is greater than in
A.
❑ Under Module side B B1: when the voltage difference is greater than the programmed setting and the voltage in A is greater than in
B.
❑ Perm. without comp. B1: indicates that differences in voltage, angle and frequencies are lower than the corresponding settings.
25
Available since firmware version 6.0.18.2 and ICD 8.2.0.
❑ Perm. with comp. B1: when the necessary conditions related to the voltage, angle argument and frequencies differences are given,
taking into account the breaker closure time for calculating the angle argument difference.
❑ Perm. Manual Close V B1: Manual closure permission for voltage checks. It´s active when the undervoltage conditions are met.
❑ Permission Recloser V B1: Reclosure permission for voltage checks. It´s active when the undervoltage conditions are met.
❑ Perm. Manual Close B1: closure permission for undervoltage or for synchronism. It is active, due to compliance with the
undervoltage conditions or the synchronism conditions. If the function is disabled, manual closure permission will also be signalled.
❑ Perm. Reclose Br 1: reclosure permission for undervoltage or synchronism, so that the recloser decides on the automatic closure of
the breaker. It is actived, due to compliance with the undervoltage conditions or the synchronism conditions.
The function has independent settings, commands and outputs:
❑ Node: PROT/RSYN1
❑ Settings and logical inputs: There are 6 settings tables. See Table 136.
❑ Commands:
DOrdSyBlk1: Function block and unblocking. Only acts when the function is enabled.
DOrdPeBlk1: Close permission block and unblock. Only acts when the function is enabled.
❑ Outputs: Table 137 shows the function’s output data.
The detection of the presence or the absence of voltage is always done in all the phases. However, the analysis of the conditions for
granting or refusing breaker close permission is only carried out if the function is enabled.
If “Sync. Enabled” is selected “with compensation”, the frequency slip is used to compensate the breaker closing time:
In which:
To consider the slip frequency difference must exceed the "Slip threshold (Hz)" setting.
If this angle difference decreases when the “Sync. Enabled” is set with compensation and closure in 0º, the condition for granting
permission will be:
When the “Sync. Enabled” is set with compensation, in order for permission to be granted the difference must be around 0º, the
following must be met:
As in the first breaker, this unit has function to check the presence of voltage on both sides of the breaker, and the test of the
synchronism conditions to give close permission.
The side A voltage is the same for both synchronisms, so the same voltage and settings are used (“Side A phase Select”,
“Compensation factor (Vs1)” and “Compensation angle (Vs1)”).
When “Side A-Vs1 selection” signal is activated, the side A voltage corresponds to the analogue voltage input connected to the
synchronism voltage terminals (Vs1) and side B voltage to the Vs2 (V synchronism 2).
For breaker and a half applications, with closing sequence reclosing "Brk1 then Brk2" or " Brk2 then Brk1" the setting "Autoreclose
condition" depends on the state of the breaker, so that if the first breaker of the sequence is blocked, the second breaker uses the
first breaker´s setting . For example, with "Brk1 then Brk2" if breaker 1 is blocked , it will not be close command of that breaker, so
the "Autoreclose condition" of the second breaker ( RSYN2 ) will use the setting of the first breaker ( RSYN1 ).
The function has independent settings, commands and outputs for the second breaker. The meaning of these data is the same as
the first breaker.
❑ Node: PROT/SECRSYN1
❑ Settings and logical inputs: There are 6 settings tables. See Table 139.
❑ Outputs: Table 138 shows the function’s output data. They are similar to the first breaker, but for the second.
26
Available since firmware version 6.0.18.0 and ICD 8.1.0.14
In double busbar configuration, there is only one breaker and the synchronism unit 1 (RSYN1) is used.
The side A voltage is independent of the disconnectors, but the side B voltage depends on the disconnector. When 89_1 is closed,
Vs1 is used, but when it is opened Vs2 is used. It affects the voltage (module and argument) and frequency used in the synchronism
function. The settings could be:
❑ Disconnector Status 89_1 closed. The voltage selected on the A side is compared with the voltage of the input Vs1.
❑ Disconnector Status 89_1 opened. The voltage selected on the A side is compared with the voltage of the input Vs2.
52 ½ Configuration
Figure 156 52 ½
In 52 ½busbar configuration, there are two breakers and both units of synchronism unit 1 are used (RSYN1 and SEC/RSYN).
❑ RSYN1
A-Side V aux: Vs1
Side A-V switch: disconnector Status 89_1 opened
B-Side V aux: Vs2
Side B-V switch: disconnector Status 89_1 opened
❑ SEC/RSYN1
B-Side V aux. Not apply
Side B-V switch. Not asigned
6.2 RECLOSER
The unit allows up to 4 reclosures to be effected. The first one can be single-pole or three-pole, but the next 3 must be three-pole. In
order to make the recloser as useful as possible, the number of reclosures allowed is programmable (0 is not permitted).
There are different close times for each of the closures and for the first single-pole or three-pole.
The recloser is put into service – out of service by means of a setting. Only when enabled by setting can it be put into service-out of
service by means of a command via communications or the keyboard.
Programmable reclaim time following manual closure and following automatic closure.
The 4 closure counters (total, first, second and third closures) are stored in non-volatile memory and can be viewed in the console and
on the display. These counters can be set to 0 by command or by the keyboard.
The closure cycle can be started either by the unit's own protection trips or by external trips from other protections.
❑ Supervising status.
This is the normal status, during which the recloser “monitors” for the occurrence of any trips. If any trip occurs, the recloser is
activated.
Definitions:
❑ Reclosable units.
These units are capable of initiating the reclosure process. By default, they are overcurrent or distance units. The non-reclosable
units are those whose trips do not initiate the reclosure cycle (voltage, frequency, power units, etc). There is an input “External
trip” that can be one pole or three poles.
1P/3P. It allows as many closures as there are programmed in the number of closures before giving the final trip. The
first closure will be single-pole if the first trip was single-pole and three-pole if it was three-pole. All other closures of
the cycle will be three-pole.
Dependent. If the first trip is single-pole, it allows as many closures as there are programmed in the number of
closures before giving the final trip; while if the first trip is three-pole, it only allows one closure.
Configurable:27 The Reclose mode is selected with the logical inputs or commands: “Enable/Disable 1P mode” and
“Enable/Disable 3P mode”. When no option is selected, the recloser is blocked.
❑ Reclose number. Indicates the maximum number allowed before the issue of the definitive trip.
❑ 3 Pole Reclose 1 time (s). This is the timeout following the first three-pole trip until the recloser issues a closure command
❑ 1 Pole Reclose 1 time (s). This is the timeout following the first single-pole trip until the recloser issues a closure
command
❑ Reclose 2 time (s). This is the timeout following the three-pole trip until the recloser issues the second closure command
❑ Reclose 3 time (s). This is the timeout following the three-pole trip until the recloser issues the third closure command
❑ Reclose 4 time (s). This is the timeout following the three-pole trip until the recloser issues the fourth closure command
❑ Time after man. closing(s). Reclaim time following manual closure. The time following the manual closure of the breaker,
during which the existence of a protection trip is monitored. In such a case, a definitive trip is triggered instead of a
change to supervising status.
❑ Reclaim time Ph-Ph (s). Reclaim time following automatic closure following three-pole trip. This is the time following the
automatic closure of the breaker due to a three-pole trip, during which the existence of a protection trip is monitored. In
such a case, the cycle is continued instead of a change to supervising status.
❑ Reclaim time ground (s). Reclaim time following automatic closure following single-pole trip. This is the time following the
automatic closure of the breaker due to a single-pole trip, during which the existence of a protection trip is monitored. In
such a case, the cycle is continued instead of a change to supervising status.
❑ Incomplete sequence. Indicates whether the incomplete sequence function is enabled or not.
❑ Incomplete sequence T (s). Indicates the maximum time for the completion of the reclosure process.
❑ 79 Blocking level input. Selects the signal which, when active, blocks the recloser. The recloser must be enabled by
setting; on the other hand this input is not available.
❑ 79 Blocking pulse input. Selects the signal which, when there is a status change from deactivated to activated, blocks the
recloser. The recloser must be enabled by setting; on the other hand this input is not available. Since firmware version
5.18.15.5, if recloser is blocked by pulse, when the input is set “Not assigned”, the recloser is unblocked.
❑ 79 Unblock pulse input. Selects the signal which, when there is a status change from deactivated to activated, unblocks
the recloser. The recloser must be enabled by setting; on the other hand this input is not available.
❑ Pause+Reset AR time input. Selects the signal which, when active, restarts the closure time.
❑ Pause input. Selects the signal which, when active, stops the closure time.
❑ Autoreclose sequence reset. Selects the signal which, when active, restarts the closure process. If the breaker is open,
“Recloser Lock 52 open” is activated and waits for it to be closed. If it is close, “Recloser Lock manual closing” is activated.
In any case, once closed, it waits for the reclaim time following manual closure to return to supervising status.
❑ On line pulse input. Selects the signal which, when there is a status change from deactivated to activated, the recloser
goes to “On service”. The recloser must be enabled by setting; on the other hand this input is not available.
❑ Out of line pulse input. Selects the signal which, when there is a status change from deactivated to activated, the recloser
goes to “Out of service”. The recloser must be enabled by setting; on the other hand this input is not available. Since
firmware version 5.18.15.5, if recloser is Out of line by pulse, when the input is set “Not assigned”, the recloser is On line.
❑ Enable 1P mode27. Selects the signal which, when there is a status change from deactivated to activated, enables the 1P
mode, when the setting “Reclose mode” is "Configurable". The recloser mode will be:
"1 Pole" when the 3P mode is not selected
"1P/3P" when the 3P mode is not selected
❑ Disable 1P mode 27. Selects the signal which, when there is a status change from deactivated to activated, disable the 1P
mode, when the setting “Reclose mode” is "Configurable". The recloser mode will be:
27
Available since firmware version 5.17.15.4 and ICD 6.1.13.30
The general settings used for the supervising for synchronism (PROT/RLSS1 node) are (see Table 141):
❑ External syncro. Permission. Logical external synchronism permission logic. Selects the signal which, when active,
indicates the existence of permission for synchronism.
❑ Enable Events record. Allows the generation of protection events associated to the function. If set to “NO”, the function’s
protection events are not generated. If set to “YES”, the function’s specific mask is contemplated.
Table 141 Monitoring by synchronism settings
The settings used for the monitoring by reference voltage (PROT/RVRS1 node) are (see Table 142):
Table 143 shows the output signal of the monitoring by reference voltage (PROT/RVRS1 node):
The setting used for blocking a closure due to a failure in the breaker’s coils (PROT/RTCS1 node) is (see Table 144):
❑ Block by Coil failure. Indicates whether the recloser blocking by failure in the breaker’s coils is enabled or not.
Table 144 Closure block settings
Signals
The recloser’s output signals are in the PROT/ZRREC1 node and are shown in Table 145 and Table 146.
❑ Recloser in service. Indicates whether it is enabled and not locked by an external blocking input. Internal blocking signals
don´t affect this signal. When the recloser is disabled by setting, the recloser´s signals don´t activate.
❑ Recloser in standby. Indicates that it is in standby or supervising.
❑ Recloser Blocked. Indicates that it is locked. If the recloser is out of service, this signal is activated. If the recloser is on
line, this signal is activated by internal and external block.
❑ Definitive trip. Indicates that it is in the definitive trip. It´s activated by maximum reclose number or a trip with the
recloser blocked.
❑ Definitive Trip+Ext blocked. Indicates that it is in definitive trip and external block. It includes trips with the recloser out of
service or blocked.
❑ Reclose command. Automatic breaker closure command.
❑ 79 in progress. Active from the moment the breaker is opened by a trip until the monitoring or definitive trip status is
reached.
❑ Reclosing 1 in progress. During the closure cycle 1. As of the opening of the breaker by the first trip or until supervising is
reached following the reclaim time or trip which leads to it being blocked (by Definitive T.) or a new cycle is produced.
❑ Reclosing 1 1P in progress. During the closure cycle 1, if only one pole is open by a single-pole trip.
❑ Reclosing 1 3P in progress. During the closure cycle 1, the three poles are open by a three-pole trip.
❑ Reclosing 2 in progress. During the closure cycle 2. As of the opening of the breaker by a three-pole trip during the
reclaim time following the first reclosure until the closure command is given or the block is produced.
❑ Reclosing 3 in progress. During the closure cycle 3. As of the opening of the breaker by a three-pole trip during the
reclaim time following the second reclosure until the closure command is given or the block is produced.
❑ Reclosing 4 in progress. During the closure cycle 4. As of the opening of the breaker by a three-pole trip during the
reclaim time following the second reclosure until the closure command is given or the block is produced.
❑ Safety time. Following the closure of the breaker, the reclaim time is counted until supervising is entered or a new closure
cycle is initiated.
❑ Safety time manual closing. Following the automatic closure of the breaker, the reclaim time is counted until supervising
is entered or a new closure cycle is initiated.
❑ Safety time reclosing. Following the manual closure of the breaker, the reclaim time is counted until supervising is
entered or a new closure cycle is initiated.
❑ Safety time 1st reclosing. Following the closure of the breaker by the first closure, the reclaim time is counted until
supervising is entered, a new closure cycle is initiated or the definitive trip is triggered.
❑ Safety time 2nd reclosing. Following the closure of the breaker by the second closure, the reclaim time is counted until
supervising is entered, a new closure cycle is initiated or the definitive trip is triggered.
❑ Safety time 3rd reclosing. Following the closure of the breaker by the third closure, the reclaim time is counted under
supervising is entered or the definitive trip is triggered.
❑ Safety time 4th reclosing. Following the closure of the breaker by the fourth closure, the reclaim time is counted under
supervising is entered or the definitive trip is triggered.
❑ Presence of Vref. Indicates the presence of reference voltage.
❑ Recloser paused. Indicates that the recloser is in pause in the closure time counter.
❑ Reclosing Started. Indicates that the reclosure process has started.
❑ Reclosing 1 Started. Indicates that the first reclosure process has started.
❑ Reclosing 2 Started. Indicates that the second reclosure process has started.
❑ Reclosing 3 Started. Indicates that the third reclosure process has started.
❑ Reclosing 4 Started. Indicates that the fourth reclosure process has started.
❑ Successful Reclosing. Indicates that the reclosure process was completed successfully.
❑ Breaker Reclosing ongoing. Indicates that the breaker is reclosing.
❑ Prepare 3 pole trip. Indicates that the following trips will be three-pole.
If the recloser is enabled by setting, it happens when:
❑ 79 Internal Block. Indicates that the recloser is in internal block due to any cause.
❑ 79 Block Definitive Trip. Indicates that the recloser is in internal block due to a definitive trip.
❑ 79 Block 52 open. Indicates that the recloser is in internal block due to a manual opening.
❑ 79 Block Trip Exceeded. Indicates that the recloser is in internal block due to an excessive number of trips.
❑ 79 Block switch on fault. Indicates that the recloser is in internal block due to a switch onto fault, i.e., a trip is produced
during the reclaim time following a manual closure.
❑ 79 Block 3P trip. Indicates that the recloser is in internal block due to a three-pole trip, in the single-pole modes. Recloser
Lock No Syncrocheck. Indicates that the recloser is in internal block due to the absence of syncrcheck.
❑ 79 Block without Vref. Indicates that the recloser is in internal block due to the absence of vref.
❑ 79 Block Pole discordance. If the discordance function acts, the reclosure cycle is blocked.
❑ 79 Block Close Failure. Indicates that the recloser is in internal block due to the close failure. Related to the breaker
monitoring.
❑ 79 Block opening Failure. Indicates that the recloser is in internal block due to the open failure. Related to the breaker
monitoring.
❑ 79 External Block. Indicates that the recloser is in external block due to any cause.
❑ 79 External Block Comms. Indicates that the recloser is in external block due to command.
❑ 79 External Block Input. Indicates that the recloser is in external block due to logical input.
❑ 79 Block Start failure. Indicates that the recloser is blocked due to reclosing start failure.
❑ 79 Block A Start failure. Indicates that the recloser is blocked due to pole A reclosing start failure.
❑ 79 Block B Start failure. Indicates that the recloser is blocked due to pole B reclosing start failure.
❑ 79 Block C Start failure. Indicates that the recloser is blocked due to pole C reclosing start failure.
❑ 79 Block End of cycle. Indicates that the recloser is blocked due to the end of the reclosing cycle.
❑ 79 Block manual closing. Indicates that the recloser is blocked due to manual reclosing.
❑ 79 Block Trip In Safety time. Indicates that the recloser is blocked due to a trip in safety time.
❑ 79 Block Incomplete sequence. Indicates that the recloser is blocked because the sequence time is exceeded.
❑ 79 Block TC Failure. Indicates that the recloser is blocked due to breaker circuit supervision failure.
Commands
❑ "DOrdReEn" . It enables/Disables the recloser. This command only operates, when the recloser is enabled by setting. It is
maintained at shutdown.
❑ "DOrdReclEn" It enables/Disables the recloser in local mode. This command only operates, when the recloser is enabled
by setting and in local mode. It is maintained at shutdown.
❑ BlkRec. It blocks/unblocks the recloser. It is not maintained at shutdown.
❑ "DOrdRecIni". It resets the recloser counters.
❑ "1P mode".27 It enables/disables the 1P mode, when the setting “Reclose mode” is "Configurable". With these
commands the recloser mode can be 1 P, 1P/3P or blocked.
❑ "3P mode".27 It enables/disables the 3P mode, when the setting “Reclose mode” is "Configurable". With these
commands the recloser mode can be 3 P, 1P/3P or blocked.
They are stored in a non-volatile memory and displayed in the statistical data (communications and display).
A signal is generated the trip limit is exceeded (“Reclose number” setting) within a set time (“Trips exceeded window (min)”
setting in the CBOU node).
It sets recloser to “Internal block”, signalling “Excessive nbr trips” and “Definitive trip”.
It remains in the Manual Opening and Definitive Trip statuses until the breaker is closed manually.
❑ If the breaker does not open during the block (or reclaim) time, it goes to Supervising status.
❑ If there is a manual opening, it enters Manual Opening Block.
During each cycle a programmed time is observed and the breaker closes. If the breaker does not trip due to a protection within
the reclaim time, the Supervising (standby) status is entered. If it does, the following closure is initiated. If this was the last, the
Definitive Trip is initiated.
If, following the action of the protection, the breaker does not open in the preset time or the relay continues to trip, the internal
block begins to operate. If, following a closure and while the safety time is being counted, there is a manual opening. In this case, it
enters Manual Opening Block and exits the cycle.
If, while the reclosure time is being counted, a manual closure is produced, the recloser aborts the reclosure cycle and enters
“Manual closure”. Following the corresponding reclaim time, it returns to standby.
The action of the external block prevents the cycle from being entered, or the exit from any ongoing cycle. If the breaker opens
while the block is in effect, it enters Definitive Trip block.
If the synchrocheck function is enabled and the synchrocheck monitoring setting is set to “YES”, this function must issue closure
permission in order for the closure relay to be activated.
The figures below show the sequence of events for a reclosure which has been programmed for three reclosure attempts (TR1, TR2
and TR3, respectively), with a reclaim time of Tsec, for different situations:
Once the Supervising status has been reached, a new trip causes a new cycle to begin and reclosure 1 is started once more, as
shown below:
d.- Changes to definitive trip after exhausting the number of programmed reclosures.
e.- Changes to definitive trip due to a trip during the reclaim time following a manual closure.
The enabling of the corresponding R1, R2 and R3 post-trip reclosure permission mask is checked with each trip. If they are not
enabled, the reclosure cycle is interrupted.
In the event of simultaneous trips (before the opening of the breaker), the units with reclosure permission are taken into account in
order start the reclosure cycle.
Additionally, the trips which force the recloser to enter a block are also checked.
If consecutive trips are produced in different units, the relay reviews the tripped units’ masks and allows as many reclosures as
correspond to the minimum number allowed for the units involved.
That is, if the minimum number of reclosures is set to 3, reclosures 1, 2 and 3 are allowed.
Once the number of permitted cycles has been exceeded, a new trip causes the recloser to enter “Definitive trip block”.
Reclosable trips
These are trips that are capable of initiating the reclosure cycle is programmed accordingly. In general, they are trips corresponding
to the overcurrent and distance units, as well as the external trip inputs.
If various units issue a trip command during a fault and at least one of the tripped units has reclosure permission, the reclosure
cycle is initiated, unless one of the units is set to produce a 79 block.
Likewise, there are various unit block inputs (for status and for pulses), thus making it possible to transfer any signal that is to be
used to avoid the reclosure to this input.
Non-reclosable trips
If a non-reclosable trip is produced (27, 59, 59N, 81, 81R), the reclosure unit will not launch the reclosure sequence for this cause
and, depending on whether the reclosure block mask has been set to “YES”, it will force the recloser to enter the definitive trip
status.
If the trip does not open the breaker (because it has not given rise to the general trip), the recloser will remain in its current status.
Non-reclosable unit’s can be made to produce a reclosure by means of the connection to the trip output corresponding to the
“Configurable autoreclose” input.
This is used when a specific unit is not to produce a reclosure following a trip and when this unit is to prevail over those with
permissions in the event of simultaneous trips.
If this mask is not used, two units may trip simultaneously and the recloser may reclose due to one of the units being reclosable.
In the event of the non-reclosable unit tripping on its own, the breaker will open and remain in a blocked status.
In addition to these masks, the relay has logic inputs that allow the recloser to be blocked. Through the logical assignment of
internal signals to these inputs, the user can modify the operation of the recloser.
Each protection unit has an independent setting which is used to enable or disable this unit’s reclosure due to trip permissions. The
reference is “ReC1Perm”. The setting is configured as a menu of options.
The PacFactory has a drop-down menu showing the possible combinations. These options are different between the distance units
that generates single-pole trip and the units that only produces three-pole trip:
Data Reference
0 NO None reclose is allowed
1 Reclose 1 Only the first reclose is allowed.
2 Reclose 2 Only the second reclose is allowed.
3 Reclose 1-2 The first and second recloses are allowed.
4 Reclose 3 Only the thrird reclose is allowed.
5 Reclose 1-3 The first and thrird recloses are allowed.
6 Reclose 2-3 The second and thrird recloses are allowed.
7 Reclose 1-2-3 All recloses are allowed
8 Reclose 4 Only the fourth reclose is allowed.
9 Reclose 1-4 The first and fourth recloses are allowed.
10 Reclose 2-4 The second and fourth recloses are allowed.
11 Reclose 1-2-4 The first, second and fourth recloses are allowed.
12 Reclose 3-4 The thrird and fourth recloses are allowed.
13 Reclose 1-3-4 The first, thrird and fourth recloses are allowed.
14 Reclose 2-3-4 The second, thrird and fourth recloses are allowed.
15 Reclose 1-2-3-4 All recloses are allowed
Table 148 Options of reclosure permissions following trip (distance units with one pole trip)
Data Reference
0 NO None reclose is allowed after a trip of the unit
1 Reclose 1 (1P) Only the first reclose is allowed after a one pole trip of that unit
2 Reclose 1 (3P) Only the first reclose is allowed after a three poles trip of that unit
3 Reclose 1 (1P/3P) Only the first reclose is allowed after a trip of that unit
4 Reclose 2-3-4 The second, third and fourth recloses are allowed
5 Reclose1(1P)-2-3-4 The first (if it is one pole),the second, third and fourth recloses are allowed
6 Reclose1(3P)-2-3-4 The first (if it is three poles), the second, third and fourth recloses are allowed
7 Reclose 1-2-3-4 All recloses are allowed
Table 149 Options of reclosure permissions following trip (distance units with three poles trip)
Data Reference
0 NO None reclose is allowed after a trip of the unit
2 Reclose 1 (3P) Only the first reclose is allowed after a trip of that unit
4 Reclose 2-3-4 The second, third and fourth recloses are allowed after a trip of that unit
7 Reclose 1-2-3-4 All recloses are allowed after a trip of that unit
Table 150 Reclosure permissions following trip (in each protection node)
Internal Trips
❑ Reclosure following a single-pole trip. This trip is produced by distance zone 1 and teleprotection unit.
❑ Reclosure following a three-pole trip (the rest).
If a single-pole trip evolves to a three-pole trip before the reclosing, the times are restarted in accordance with the three-pole trip.
External trips
If during this programmed period of time the breaker opens, the ongoing cycle is initiated and the “79CC-Ongoing cycle” signal is
activated.
This signal will remain active until the cycle terminates upon its completion and a standby or block status is entered.
If the 52 NO and NC inputs are programmed, the 52b (NC) will be taken into consideration to detect the opening. If only the 52a
(NO) input is programmed, this signal at zero will be used as an open status.
The reclosures which are to be possible following the tripping of a specific unit can also be selected.
The enabling of the corresponding R1, R2, R3 and R4 permission mask is checked with each trip. If they are not enabled, the
reclosure cycle is interrupted.
In the event of simultaneous trips (before the opening of 52), the units with reclosure permission are taken into account in order
start the reclosure cycle.
Additionally, the trips which force the recloser to enter a block are also checked.
If consecutive trips are produced in different units, the relay reviews the tripped units’ masks and allows as many reclosures as
correspond to the minimum number allowed for the units involved. That is, if the minimum number of reclosures is set to 3,
reclosures 1, 2 and 3 are allowed.
Once the number of permitted cycles has been exceeded, a new trip causes the recloser to enter “Definitive trip block”.
All the trips (reclosable, non-reclosable and block) are checked up to the moment in which the breaker opens.
Any block trips which appear are sent directly to a blocked recloser.
If there are only reclosable trips, the reclosure cycle is begun with the time of the first reclosable produced by the trip.
Examples of operation.
The total number of reclosure cycles is set to 2 and Autoreclose mode to Dependent.
Example 1:
❑ Unit 50 trips (three-pole trip with reclosure available in all except the first one). Recloser does not reclose as the reclosure
permission is not allowed in CC1. Recloser would enter “Internal Block-Definitive Trip”
Example 2:
❑ In standby, Zone 1 single-pole trips (with R1 reclosure permission for single-pole trips). 79 recloses with “single-pole
Reclose 1 time (s)”.
❑ With 52 closed, and while “Reclaim time ground (s)” is running, a three-pole trip happens (with R2 and R3 reclosure
permission for three-pole trips). 79 recloses with “Reclose 2 time (s)”.
❑ With 52 closed, and while “Reclaim time ground (s)” is running, a three-pole trip happens (with R2 and R3 reclosure
permission for three-pole trips). 79 recloses with “Reclose 3 time (s)”.
❑ With 52 closed, and while “Reclaim time ground (s)” is running, a three-pole trip. 79 recloses with “Reclose 3 time (s)”.
Recloser does not reclose because the maximum reclosure number is exceeded. Recloser would enter “Internal Block-
Definitive Trip”
Example 4:
❑ While in standby, a 50 trip with R1 permission is produced and, before 52 opens, another 50N with R2 permission,
programmed without blocking, trip is produced.
❑ In this case, the 50 trip would take precedence, provoking the reclosure cycle.
Example 5:
❑ While in standby, a 50 trip with R1 permission is produced and, before 52 opens, another 50N programmed with blocking
trip is produced.
❑ In this case, when the 50N trip is produced and the breaker opens, the reclosure cycle would be interrupted and “Internal
Block-Definitive Trip” would be entered.
This monitoring is equivalent to a pause signal that halts the reclosure cycle during the VREF timeout.
It operates as follows:
❑ Once the breaker has opened and the trip has dropped out, the reclosure cycle is initiated and the reclosure time is
launched.
❑ In the absence of VREF, “VREF timeout” is launched, during which the VREF signal should be activated to allow the
continuation of the reclosure process.
❑ If the VREF signal does not appear prior to the elapse of this time, the internal 79 block due to absence of VREF” status is
entered.
❑ This status is cancelled by means of a closure or following the activation of the recloser reset input.
When the “Pause with reclosure reinitiation” input is activated, the recloser time counter (dead time) is reset to zero and the 79 is
halted until this input is cleared.
When this input is activated, the reclosure time counter (dead time) is halted until this input is cleared.
This timed is used to check that the recloser has exceeded a defined time without issuing a closure command nor becoming
blocked or resetting, thus causing the recloser to enter a block by incomplete sequence status.
After a three-pole trip, if a specific reclosure is set to “monitored by synchronism” and once the reclosure time has elapsed, there is
a maximum timeout equivalent to the “Sync. Delay Time (s)” setting in which the “synchronism permission” signal is to activate.
Upon the issue of the synchronism permission the reclosure command is activated.
If synchronism permission is not activated, the “Block due to lack of synchronism” status is entered.
The first and the rest of the reclosures can be set to monitoring by synchronism by means of a setting. This allows the first
reclosures to be carried out quickly and without the need to check for synchronism, in the case of specific faults, and normal
reclosures for the rest.
Settings can be used to establish whether the synchronism is to check the relay’s functioning or that or an external input.
There is a setting within the synchronism unit to enable monitoring by synchronism for the recloser and for manual closing. As they
are independent settings, by disabling function 25 it is possible to monitor the reclosure with the external synchronism input.
If the setting “Synchrocheck type” is internal, the recloser waits the permission signal is activated. If the setting is external, the
recloser waits the activation of the “External syncro. Permission” input.
This status is cancelled by the manual closure of the breaker following the elapse of the reclaim time.
If the 52 NO and NC inputs are programmed, the 52b (NC) will be taken into consideration to detect the closure.
If only the 52b (NC) is programmed, this denied signal will be used.
❑ Out of service.
❑ Supervising, standby or reset.
❑ Manual opening.
❑ Internal block. Includes the Definitive trip.
❑ External block.
❑ Reclosure successful
If it is in service, it can be placed out of service by pressing the R key on the keyboard or by means of a command or logical
input.
This status is exited when the function is enabled by a setting or command (R key or command or logical input). The transitory
manual closure setting is entered if the breaker is closed at this time. If the breaker is open, internal block (due to manual
opening) is entered.
The functioning is similar when the relay lights and the reclosure setting is set to “YES”.
❑ Whenever the breaker is closed for a period that exceeds the reclaim time (following a manual closure or following
a trip).
❑ If the breaker is closed and in the external block status, when the block signal is cleared.
This status is exited:
❑ By the action of the protection and the subsequent opening of the breaker. If reclosure is to follow, the cycle is
initiated. If not, Definitive trip is entered.
❑ Due to the manual opening of the breaker. Manual Opening is entered.
This status is cancelled when the 52 is closed manually (by command, contact, etc., by not by reclosure).
❑ Opening failure
❑ Closure failure
❑ Manual opening
❑ Three-phase Trip
❑ Definitive trip
❑ Incomplete sequence
The reclosure cycle is not started in this status. The cycle is abandoned if it has already been started and Definitive Trip is
signalled if the breaker has opened as a result of a protection trip.
This status is cancelled by the closure of the breaker following the elapse of the reclaim time.
In all cases, a generic “internal block” signal is activated, in addition to a specific signal identifying the cause of the block. In
those cases where the block status occurs after a trip and the opening of the 52, “definitive trip block” is also indicated.
This status is entered if, following the elapse of the breaker fault time after a trip, the breaker remains closed.
This status is cancelled when the breaker opens. The opening failure time is the same as that of the opening fault with
contact function.
DGITAL SIGNAL
General trip Time
❑ If the breaker remains open following the elapse of the breaker closure failure time after a closure command.
“Definitive trip” is also signalled.
❑ If the trip circuit failure block is enabled. If, when activating the closure command, the command activates the trip
and closure circuits’ monitoring logic’s "trip circuit failure” signal, the closure command is not issued and “closure
command blocked" is signalled. Following the elapse of the closure failure time, the block by closure failure status
is entered.
This status is cancelled by the manual closure of the breaker following the elapse of the reclaim time.
This status is entered by a manual opening or by means of a breaker command when the 79 is in standby or in a current
cycle.
It is cancelled by a manual breaker closure. The transitory Manual Closure status is entered.
Definitive trip
This status is activated following a trip that fails to produce a reclosure due to a 79 block or for having reached the end of
the cycle with the fault intact:
❑ A trip is produced within a period that is shorter than the reclaim time following a manual breaker closure.
❑ A trip is produced in a period that is shorter than the reclaim time following the last reclosure.
❑ A protection trip is produced while the block status is active.
❑ A protection trip is produced while the recloser is out of service.
❑ An excessive number of trips are produced within a defined time.
❑ The recloser does not issue a closure command due a voltage monitoring failure (synchronism).
❑ The recloser issues a closure command and the recloser does not close in the closure failure time.
❑ The recloser does not issue a closure command due to an interlock (for example, a trip circuit failure) and the
recloser does not close in the closure failure time.
❑ The voltage presence conditions are not met during a current cycle.
❑ If a trip does not produce a reclosure due the programming of a block (with the block taking precedence over other
functions with permissions) or the absence of the programming of a reclosure (unless there is another function
with reclosure permission trips simultaneously).
❑ A switch onto fault function trip following a manual closure.
❑ By incomplete sequence.
This status is cancelled by one of the following causes.
❑ Manual breaker closure, following which the transitory MC (Manual Closure) status is activated.
❑ Reception of recloser’s reset input.
The “successful reclosure” signal is activated and remains so until the relay trips once again.
❑ Due to the manual opening of the breaker. An internal block due to manual opening is activated.
❑ Due to the action of the protection. An internal block due to definitive trip is activated.
❑ Following the elapse of the safety time. Standby is activated.
❑ Due to the activation of the external block input or block command. An external block is activated.
❑ Due to the action of the protection following an opening failure (52 does not open or the unit remains tripped). An
internal block due to an opening fault is activated.
At the same time as the closure time count, the monitoring by VREF (during a maximum “VREF timeout” period) and by
synchronism.
❑ Manual breaker closure. “Internal block” is activated and “Temporary block by manual closure” is signalled.
❑ Following the elapse of the reclosure time. Phase 2 of the closure is entered.
❑ Activation of the external block input. “External block” is activated.
❑ Failure to meet the reference voltage (VREF) monitoring conditions. An internal block is activated and Internal
block due to absence of VREF and Definitive trip is signalled.
❑ Failure to meet the synchronism monitoring conditions. An internal block is activated and Internal block due to
synchronism fault and Definitive trip is signalled.
It is cancelled:
❑ Because the breaker has closed in the permitted time. Phase 3 entered.
❑ Because the permitted time has elapsed without the closure of the breaker. An internal block is activated and
“Internal block due to closure failure” and “Definitive trip” is signalled. The relay’s Breaker failure due to contact
signal is also activated.
It is cancelled:
❑ Due to the manual opening of the breaker. “Internal block” is activated and “Internal block by manual opening” is
signalled.
❑ Due to a protection trip. The second reclosure process is entered, phase 1.
❑ Because the block time has elapsed without the opening of the breaker. Standby is activated.
A low current permanent fault may cause tripping following the elapse of the safety period. To avoid, in the event of all the
reclosures being first reclosures and no definitive trip is produced, the automatic extension of the timeout due the pick up
of a unit capable of producing a reclosable general trip in standby (“Trip permission with 79 in standby” set to “YES”) until
reset or a trip is produced.
If, during the operating cycle, a manual order (or command) is given to the circuit breaker, the recloser suspends the cycle
and switches "internal block due to manual opening" or "manual closure".
After a single phase trip, the recloser waits for the opening of only one pole in both breakers. If more than one pole opens, it blocks
and signalizes definitive trip. If the tripped pole does not open in both breakers, after waiting a time, it blocks by open failure. To
begin the process, both breakers have to open.
If both breakers open correctly, the reclosing cycle begins after the time set, to close the breaker selected with the closing
sequence. If a single phase fault is detected, it can evolve to a three phase fault during the ongoing cycle. At this moment, a new
three phase reclosing waiting time begins to give closing permission. If, when giving a reclosing permission, the breaker is open or
tripped, it blocks.
The recloser considers that a breaker is blocked, if a manual opening has been made or if it is blocked by a digital input or setting. In
this case, it does not operate, and will only be able to operate the other breaker if the setting "Permit closure 52_x with 52_y
blocked" says so.
With manual closing of a breaker, the recloser is blocked by manual closing , counting the safety time after manual closing.
❑ Brk1. The reclose cycle only generates close command for breaker 1.
Generates open command on both breakers and wait for them to open. If any of them is not open,then it will block by
open failure and not continue reclosure cycle.
Generates close command for breaker 1 and waits for closure (with or without synchronism). Breaker 2 is not closed.
❑ Brk2. The reclose cycle only generates close command for breaker 2.It is same as above, but breakers are exchanged.
❑ Brk1 and Brk2. The reclose cycle generates close command for both breakers simultaneously.
Generates open command on both breakers and wait for them to open. If any of them is not open,then it will block by
open failure and not continue reclosure cycle.
Generates close command for both breakers and wait for closure (with or without separate synchronism) to pass
safety time. If one of them gives closure failure, the setting value Block by Br1 Close Fail is checked
NO:The closing sequence continues considering only the other breaker
YES: Recloser is locked and it will block by close failure.
If either closed, it starts counting recloser safety time.
If recloser safety time ends up without trips and breaker is closed, it returns to standby.
If new protection trip is produced, a new closing sequence is started
If an excessive number of trips are produced in any breaker, then it will block and not continue reclosure cycle
❑ Brk1 then Brk2. The reclose cycle generates close command for breaker 1. When the reclose cycle has finished
successfully (Successful Reclosing), the breaker 2 close command is generated, once the sequence time since the breaker
1 close command has finished
Generates open command on both breakers and wait for them to open. If any of them is not open, then it will block by
open failure and not continue reclosure cycle
Generates close command for breaker 1 and waits for closure (with or without synchronism). When recloser safety
time ends up without trips and breaker 1 is closed (Successful Reclosing), the breaker 2 close command is generated. If
one of them gives closure failure, the setting value Block by Br1 Close Fail is checked
NO: Closing sequence continues considering only the breaker 2 checking synchronism 2.
YES: Recloser is locked and it will block by close failure.
If an excessive number of trips are produced in any breaker, then it will block and not continue reclosure cycle
❑ Brk2 then Brk1. The reclose cycle generates close command for breaker 2. When the reclose cycle has finished
successfully (Successful Reclosing), the breaker 1 close command is generated, once the sequence time since the breaker
2 close command has finished. It is same as above, but breakers are exchanged.
❑ Brk1 - Brk2. The reclose cycle generates close command for breaker 1. When the breaker 1 has closed, the sequence time
starts. When the sequence time finishes without a new trip, the breaker 2 close command is generated. If during sequence
time with the breaker 1 closed, there is a trip, the next reclose cycle starts until the maximum allowed reclosure by setting.
The sequence is the following:
Generates open command on both breakers and wait for them to open. If any of them is not open, then it will
block by open failure and not continue reclosure cycle
Generates close command for breaker 1 and waits for closure (with or without synchronism). When the
breaker 1 is closed, the sequence time starts. When the sequence time finishes without a new trip, the breaker
2 close command is generated. If breaker 1 gives closure failure, the setting value Block by Br1 Close Fail is
checked
NO: Closing sequence continues considering only the breaker 2 checking synchronism 2.
YES: Recloser is locked and it will block by close failure.
If an excessive number of trips are produced in any breaker, then it will block and not continue reclosure cycle
❑ Brk2 - Brk1. The reclose cycle generates close command for breaker 2. When the breaker 1 has closed, the sequence time
starts. When the sequence time finishes without a new trip, the breaker 2 close command is generated. It is same as Brk1 -
Brk2, but breakers are exchanged.
If the close sequence is "Brk1 then Brk2" or " Brk1 - Brk2" and breaker 1 is blocked or in manual opening, the breaker 2 close
condition (ReCond2) uses the first breaker´s setting (ReCond1). In case of "Brk2 then Brk1" or " Brk2 - Brk1" and breaker 2 is
blocked or in manual opening, the breaker 1 close condition (ReCond1) uses the second breaker´s setting (ReCond2).
❑ Select 2 breakers
It allows operating with two breakers (“YES”). In that case, follows the settings detailed bellow to include a second breaker
in the closing scheme.
❑ Closing sequence
Definition of the breaker or breakers that will reclose automatically. In the case of having to reclose two breakers, it can be
done simultaneously or following a sequence.
When set to “NO”, when there is breaker 1 close failure, it allows following the sequence selected for closing the breaker 2.
When set to “NO”, when there is breaker 2 close failure, it allows following the sequence selected for closing the breaker 1
When set to “NO”, it does not allow the closing of the breaker 1, if the breaker 2 is blocked.
When set to “NO”, it does not allow the closing of the breaker 2, if the breaker 1 is blocked.
❑ Reset sequence.
It stops the closing sequence and is activated in the following situations:
The opening of the breaker is detected without initializing the recloser cycle. Once the opening is detected, waits two
cycles before signalling manual opening. This time avoids the opening by an external trip.
52_1 blocked. Breaker 1 blocking status, caused by the setting “52_1 reclosing lock”, the internal signal “Operations
Locked - Br.1” or the manual opening of the breaker.
52_1 Successful Reclosing: Breaker 1 reclosing activation order state..Breaker 1 has properly completed its reclosing
cycle.
❑ Signals of the breaker 2:
52_2 Reclose Command: Breaker 2 reclosing activation order.
52_2 closure failure: Breaker 2 closure failure activation.
The breaker 1 is not closed, after the closing time.
52_2 Manual opening: Breaker 2 manual opening activation signal.
The opening of the breaker is detected without initializing the recloser cycle. Once the opening is detected, waits two
cycles before signalling manual opening. This time avoids the opening by an external trip.
52_2 blocked. Breaker 2 blocking status, caused by the setting “52_2 reclosing lock”, the internal signal “Operations
Locked - Br.2” or the manual opening of the breaker.
52_2 Successful Reclosing: Breaker 2 reclosing activation order state..Breaker 2 has properly completed its reclosing
cycle.
The unit, following a minimum frequency trip and in the case of the function having been enabled and not locked, will only attempt one
reclosure.
The logical input “Restoration trip (start)” must be activated, to start the reclosing.
When the trip occurs, the 79f-breaker closure lock signal is activated and the period programmed as the “definite trip timeout” is
observed. If the minimum frequency condition is set to “NO” or if the frequency is higher than the minimum programmed value during
the programmed “closure time”, a closure command is issued to the breaker. If the minimum voltage condition is set to “YES” and is
not met, the definitive trip is activated.
The 79f-breaker closure block will remain active until the reclosure or definitive trip conditions are met.
If the “Enab. maximum reset time” is set to “YES” and the programmed “maximum reset time (s)” elapses without the reclosure
conditions having been met, an internal block due to failure to meet conditions (with definitive trip) is activated. If the setting is set to
“NO”, the reclosure conditions are waited for indefinitely.
A “reclaim time” is observed following the closure. If a new minimum frequency trip occurs during this period, it moves to internal
block with definitive trip.
The frequency recloser’s general operation is shown in Figure 176 to Figure 183.
❑ Reposition time (s). Indicates the time during which the reset conditions must be met in order for the reset command to
be issued.
❑ After close safety time(s). Indicates the timeout following a reset command. No trips must be produced during this time
in order for the reclosure to be considered as successful. If a trip is produced, an end of cycle block is activated.
❑ Reset maximum time Enable. Indicates whether the maximum reset time limit is enabled.
❑ Reset maximum time (s). Indicates the maximum timeout in which the reset conditions are to be met. To the contrary, a
block due to the absence of reset conditions is generated.
❑ Minimum V supervi. enabled. Indicates whether the minimum voltage monitoring is enabled or not.
❑ Reclose Minimum Voltage. Indicates the minimum voltage above which reset permission is given.
❑ Synchrocheck supervision. Indicates whether the synchronism conditions check is enabled or not.
❑ F restoration blocking. Logic input, which selects the signal which, when active, blocks the frequency recloser.
❑ Restoration trip (start). Logic input, which selects the signal which, when active, indicates that a reclosable trip has been
produced.
❑ f restoration reset input. Logic input, which selects the signal which, when active, resets the frequency recloser.
❑ Synchrocheck type.28 Indicates whether the synchronism is internal or external.
❑ External syncro. Permission.28 Logical external synchronism permission logic. Selects the signal which, when active,
indicates the existence of permission for synchronism.
❑ Enable Events record. Allows the generation of protection events associated to the function. If set to “NO”, the function’s
protection events are not generated. If set to “YES”, the function’s specific mask is contemplated.
❑ PROT/FRREC1 node
❑ Settings. There are 6 settings tables. See Table 153.
❑ There are no commands
❑ Outputs: Table 154 shows the function’s output data.
Start reclosing F_RREC. Indicates the start of the reclosing cycle (Figure 177). It begins with the trip and finishes with a
successful reclosing or recloser blocked or the activation of the “f restoration reset input”.
28
Available from firmware version 5.25.16.1 and ICD version 7.0.0.2
In progress F_RREC. It is active since the breaker is open by a trip until a successful reclosing or recloser blocked or the
activation of the “f restoration reset input” (Figure 183).
Successful Reclosing F_RREC. Indicates a Successful reclosing (Figure 181). The safety time after closing has finished
and the breaker has not open, there is no trip and the “f restoration reset input” is desactivated.
Recloser Safety time F_RREC. After a reclosing, the safety time is ongoing before the recloser goes to standby or Finally
Interlock (Figure 181).
Block End Cycle F_RREC. Indicates the breaker is open or a trip has happened during the safety time (Figure 181).
Block closure failure F_RREC. Indicates the recloser is in internal block, caused by a close failure (breaker supervision).
See Figure 181.
Block opening failure F_RREC. . Indicates the recloser is in internal block, caused by an open failure (breaker
supervision). See Figure 178.
Block reset cond. F_RREC. After the breaker opening, the recloser is waitng during the “Reset maximum time (s)” that
the reposition conditions are met. If the maximum time is enabled, when the time finishs without close command, the
recloser is blocked by absence reset conditions. See Figure 180.
Reclosing Permission F_RREC. Indicates the reposition conditions are met (Figure 179).
Reclosing Command F_RREC. Close command after all the setting conditions are met (Figure 179).
Reclosing Blocked F_RREC. Indicates the recloser is blocked by setting, internal or external causes (Figure 182).
Definitive Trip F_RREC. Definitive trip when the recloser is blocked by absence of reposition conditions, end of cycle or
close failure (Figure 182).
Close Blocked F_RREC. Activated during the closure time (Figure 180).
In standby F_RREC. Activated when the recloser is standby
The current inputs are independent for every breaker. There are two inputs for every phase.
The analog input 7 can be selected with the setting "Current 7 type" of the node TCIN:
❑ Local End polarity Br1. It selects the polarity (incoming / outgoing) of the currents IA1, IB1, IC1.
❑ Local End polarity Br2. It selects the polarity (incoming / outgoing) of the currents IA2, IB2, IC2.
In topology 52 ½, the total phase current is calculated as the sum of the current of each breaker, taking into account the polarity. If
incoming it´s sum, if outgoing it´s subtraction.
ZT1
Distance functions
Quadrilateral Characteristic (5 zones)
Mho Characteristic (5 zones)
21 High Speed
Zone 1 Extension
Double Lines (Nota 2)
Lines with Series Compensation
CVT: Lines with Capacitive Voltage Transformers
Common protection functions
SOFT Switch onto fault
27 Undervoltage
59 Overvoltage
59N Zero sequence overvoltage
47 V2 overvoltage protection
Minimun voltage
Frequency (81M/m)
Frequency rate of change (81R)
3x50/51 (67) Solo fasor
50N/51N (67N) Solo I0
50G/51G. Grounding overcurrent (Nota 1)
46TOC (67Q), 46IOC(67Q)
46FA Broken conductor
50CSC Second harmonic restraint Solo fases
37 Undercurrent
49 Thermal image (Nota 3)
32 Power units
Stub bus differential
Teleprotection
Teleprotection (21)
Teleprotection (67/67Q)
Monitoring Units
68LE Load encroachment
68FF Fuse failure
78 Power Swing
Fault locator
Breaker Monitoring
k12 breaker monitoring per pole
Closing and trip circuit monitoring
Excessive number of trips
Open pole / Faulted line detector
Breaker status logic
Pole discordance
50BF breaker failure two breakers
50BF breaker failure (Single-pole/Three-pole)
Low load breaker failure
Automatisms two breakers
Synchronism
Recloser (Single-pole/Three-pole)
Frequency recloser
Note 2: Available if the analog input 7 is used as Parallel line Neutral current 2.
Note 3: The phase unit is always available and the neutral is available when the analog input 7 is used as polarization current
Table 155 shows the available functions. Some of them that depends on the analog 7 type.
If In2 current is not available, current compensation is not used, so the calculations of the characteristics don´t take into account
the settings of the 5 zones:
❑ Km Module. Indicates the mutual compensation factor module of the parallel lines.
❑ Km Angle (º). Indicates the parallel lines mutual compensation factor angle.
The signals used in each phase of the Mho characteristic are:
If In2 current is not available, current compensation is not used, the the calculations of SIR for CVT is:
SIR for single phase faults SIR for single phase-phase faults
(Vnom/((Ia + 3·I0kn1 )·Z1)) - 1 (Unom/(Iab·Z1)) - 1
(Vnom/((Ib + 3·I0kn1 )·Z1)) - 1 (Unom/(Ibc·Z1)) - 1
(Vnom/((Ic + 3·I0kn1 )·Z1)) - 1 (Unom/(Ica·Z1)) - 1
Phase overcurrent.
Neutral overcurrent.
It uses the zero sequence (3·I0). The measure can only be phasor.
Grounding overcurrent.
It´s only available when analog input 7 is configured us polarization current; because it´s used to block Grounding overcurrent.
Thermal image.
The neutral unit is available when analog input 7 is configured us polarization current.
7.1.3 Breaker
The breaker status uses both breakers:
There are independent functions (settings, signals, commnads…) for every breaker. The nodes are:
❑ Node PROT/FRBRF1. The function uses the measures of the current transformers 1, 2 y 3 (Ia1, Ib1, Ic1).
❑ Node PROT/FRBRF2. The function uses the measures of the current transformers 4, 5 y 6 (Ia2, Ib2, Ic2).
The signals generated by this function are used in other protection functions:
It is used to avoid nuisance tripping on near faults but outside the area to be protected.
In external faults with large current flow, one of the current transformers can saturate without providing line current to the fault
and in this case:
❑ There is phase current with any direction (as measured current is spurious ) and voltage close to zero , which can generate
a trip of the distance unit
❑ If the fault is biphasic, homopolar current appears due to saturation and can act neutral directional units
An output signal is available.
❑ Node: PROT/BHPTRC1
❑ Output: Table 160 shows the signals of this function.
Block by External Fault: It´s activated when an external fault to protect the area, which can cause false alarms is
detected.
Table 160 52 ½ supervision
29
From firmware version 6.0.8.0 and ICD version 8.1.0.20
Phase currents of the two breakers are compared (IA1 and IA2, IB1 and IB2, IC1 and IC2).
An external fault is considered when, at least at some phase, the current of the two breakers exceed 3 times the rated current in
rms value.
If the currents are in phase, the fault is internal; while if the current are in opposite phase (continuous current) the fault is external.
There are several factors that make the currents are not exactly in phase in internal faults and not in opposite phase in external
faulat, the following angular criteria is applied:
The signal "Block by External Fault" is activated when in some phase the following conditions are met:
❑ The current at the same phase of the two breakers exceeds 3 times the nominal current in rms value
❑ The angle difference between the same phase of the two breakers is between 110º and 250º.
In this situation the following units are blocked:
❑ Distance units, programmed as forward, which have involved the phase that indicates external fault. And for zone 1 all
units programmed as forward are blocked.
❑ Neutral directional programmed as forward is blocked
8. FAULT LOCATOR
The fault locator for single and double lines processes the information collected in relation to each fault and calculates the estimated
distance to the point in which the fault has occurred, as well as the fault resistance.
The initial data necessary in order to arrive at the final calculation is:
❑ Sample by sample values of the voltage and current signals collected in the moment in which the fault is produced.
❑ The impedance parameters of the line in which the fault has occurred.
❑ Length of the line.
❑ The Voltage transformers and Current transformers transformation ratios of the bay that captured the fault.
The result is the distance to the fault in km or miles, together with the fault resistance and a locator exit code.
The settings necessary for the operation of the distance calculation algorithm are as follows (see Table 161):
❑ Filter enabled. If set to “YES” and if the fault point is detected during the ten cycles following a breaker closure, the neutral current
is checked to see whether is exceeds the “I Minimum after close (A)” setting. If it is, inrush is considered to exist and prefault
current values equal to zero are employed in order to avoid the inrush distortion in these measurements. The neutral current is
also checked to see whether it exceeds the “Ground maximum current (A)” setting. If it is set to “NO”, neither the inrush nor the
neutral current are measured.
❑ I Minimum after close (A). Current threshold (in primary value) for the detection of inrush. Only used if the filter setting is enabled.
If a switch on to fault is detected (by the status of the breaker) during the first 10 cycles, single – phase ground faults that do not go
beyond the INmin threshold are blocked. If it is set to 4999A all the faults (single – phase and polyphase) are blocked. A possible
use is when there is a great distortion in the shape of a wave after a closing. For example, in the case of a distribution with a lot of
transformers hanging from the line, the breaker closing will cause a high inrush that can make the low current earth faults
calculation results distorted. With the I0min threshold the earth fault calculation is filtered, the I0of which must be lower than this
threshold.
❑ Ground maximum current (A). Threshold (in primary value) indicating the system’s maximum neutral current under normal
conditions. It is only used if the filter setting is enabled.
Ohm p.u indicates ohms per unit of length. For a line length of 100 km and a line impedance of 100 ohm, the setting in ohm p.u is
calculated as follows:
Ohm p.u = Line impedance / line length = 100 ohm /100km = 1 ohm p.u,
If the impedances are available in secondary values, these can be converted to primary values with the following formula:
𝑉_𝑇𝑟𝑎𝑛𝑠_𝑅𝑎𝑡𝑖𝑜
𝑍𝑃𝑟𝑖𝑚𝑎𝑟𝑦 = 𝑍𝑆𝑒𝑐𝑜𝑛𝑑𝑎𝑟𝑦
𝐼_𝑇𝑟𝑎𝑛𝑠_𝑅𝑎𝑡𝑖𝑜
There are independent settings:
❑ PROT/RFLO node:
❑ Settings: There are 6 settings tables. For details see Table 146.
From firmware version 5.20.15.8 and ICD version 6.3.0.0, the angle range is 15-90º. In previous versions it was 0-360º.
Admittances (Y1,Y0): 0
Module: 20000
Argument: 45º
Module: 20000
Argument: 45º
Sensitivities:
The process that follows the locator’s algorithm can be summarized in 4 steps, which are explained below:
The collected signals are processed by a digital filter which provides the fundamental voltage and current components. A cosine
filter is used for this stage.
The locator includes an algorithm that determines which phases have been affected by the fault. The algorithm is based on the
well-known Girgis method for distance relays. This procedure, which analyses the different magnitudes of change between the pre-
fault and post-fault situations in the current’s fundamental component, has demonstrated enviable precision in its results.
When a fault happens in a line corresponding to our relay, the information gathered by the locator, placed at one extreme of the
line, is reduced to the voltage and current values.
The data necessary to fully determine the system are obtained from the situation existing in the instant immediately preceding the
fault and in the situation of the fault itself.
8.1.4.1 Filtered by the maximum neutral current level (cross country faults)
In cross country faults (simultaneous faults in different lines or in the same line, e.g. AN in the protected line and BN in the
adjacent line), the zero sequence current level detected in the system is superior to the maximum zero sequence current level
for single phase faults.
In these situations, the protection locates the fault but indicates that the “Ground maximum current (A)” setting has been
exceeded, as in these situations the voltages are distorted by the lack of the adjacent line fault and can cause erroneous
calculations in the fault distance.
This mode is only operative if the “Filter enabled” setting is active. In this case, the result of the localization will be displayed in
the fault report, although in the control measurements it will be reported as invalid.
The location algorithm does not have sufficient pre-fault cycles and therefore considers that the fault sample is in the cycle in which the
digital pick up was produced. Furthermore, the neutral current in the system has exceeded the current value set in the “Ground
maximum current (A)” setting (this check is only carried out when the “Filter enabled” setting is set to “YES”). By exceeding this value,
the distance calculation may be erroneous. Therefore, although it is shown in the fault report it is marked as an invalid control
measure. Finally, the distance calculation has returned a value in excess of the value established in the “Line length” setting. If this
result is between 100% and 150% of the line length, it will be displayed. If it is greater, the distance will appear as NOT CALCULATED.
The distance is always calculated but it will not be sent to the dispatching centre (61850 nor Procome) if one of the blockings codes of
the locator is activated. In the fault report, the distance is always included with the locator exit code.
❑ Not enough cycles (< 2.5 cycles). In this case, no calculation is done.
❑ Ineutral is below the setting “I Minimum after close (A)” (resistive or distant fault). In this case the calculation is done, but
it is not sent to the dispatching centre.
❑ Ineutral is above the setting “Ground maximum current (A)” (possible cross country fault). In this case the calculation is
done, but it is not sent to the dispatching centre.
❑ General block by switch onto fault. In this case the calculation is done, but it is not sent to the dispatching centre.
The capacity values of the positive, negative and zero sequences are zero, so that these values do not affect the reach.
Line parameters
Impedance: 6Ω
Angle: 84.2º
FOR A LINE WITH THE FEATURES DESCRIBED ABOVE, FAULT LOCATOR COULD BE SET AS FOLLOWS:
Setting Value
Enabled YES
Line length 20
Z1 Imp. (ohm p.u. length) 0.314
Z1 angle (º) 84.2
Z0 Imp. (ohm p.u. length) 0.81
Z0 angle (º) 70.6
Y1 (1/ohm p.u. length)*10e-9 0
Y0 (1/ohm p.u. length)*10e-9 0
Z1 Local Source (ohm) 6
Z1 Local Source Angle.(º) 84.2
Z1 Remote Source (ohm) 20000
Z1 Remote Source Angle (º) 45
Z1eq Parallel (ohm) 20000
Z1eq Parallel Angle. (º) 45
Phase Current sensitivity (A) 40% PhaseOverCurr.Setting * CT
Ground Current sensitivity (A) 40% GroundOverCurr.Setting* GCT
Voltage sensitivity (V) 5% Vrated * VT
Locator output duration(s) 7200
Locator output permanent YES
Line type Simple
Filter enabled NO
Enable Events Record YES
WHERE:
9. MONITORING
This function checks if the external supply voltage is within the set range. It generates two signals:
❑ Auxiliary power supply greater than maximum threshold. If the supply voltage exceeds the set maximum threshold.
❑ Auxiliary power supply lower than minimum threshold. If the supply voltage is below the set minimum threshold.
The settings for configuring the external power supply monitoring (Table 162):
There are two independent functions with settings, commands and outputs:
❑ Node:
PROT/CESS1 for power supply 1
PROT/CESS2 for power supply 2 (only in devices with redundant power supply)
❑ Settings. There are 6 settings tables. For details see Table 162.
❑ There are no logical inputs or commands
❑ Outputs: Table 163 shows the function’s output data.
Vcc Supervision Status. It is active when enabled and not blocked.
HH Infeed. Indicates that the power supply has exceeded the maximum threshold.
LL Infeed. Indicates that the power supply is below the minimum threshold.
❑ Measurement. The external power supply values are available in the node GEN/LLN0 (see Table 164)
This function checks if the temperature is within the set range. It generates two signals:
❑ Temperature greater than maximum threshold. If the temperature exceeds the set maximum threshold.
❑ Temperature lower than minimum threshold. If the temperature is below the set minimum threshold.
The settings for configuring the external power supply monitoring (Table 162):
❑ PROT/CTSU1 node
❑ Settings. There are 6 settings tables. For details see Table 165.
❑ There are no logical inputs or commands
❑ Outputs: Measurement. The temperature value is available (see Table 167)
❑ Table 166 shows the function’s output data.
Enabled. It is active when enabled and not blocked.
Temperature greater than maximum threshold. Indicates that the temperature has exceeded the maximum threshold.
Temperature lower than minimum threshold. Indicates that the temperature is below the minimum threshold.
❑ Measurement. The temperature value is available (see Table 167)
Table 166 Temperature monitoring outputs
If enabled, it checks that the external power supply exceeds the battery failure threshold, generating an alarm signal when it is below
the threshold.
In devices with redundant power supply, every power supply generates an independent DFFA signal. With the setting "Power Supply" a
general DFFA signal in generated.
The settings for configuring the battery failure monitoring (Table 168)
❑ PROT/CSUS1 node
❑ Settings. There are 6 settings tables. See Table 168.
❑ There are no logical inputs or commands
❑ Outputs: Table 169 shows the function’s output data.
Enabled. It is active when enabled and not blocked.
Weak Infeed DFFA. Indicates that the external power supply is below the minimum threshold as indicated in the
setting "Power supply".
Weak Infeed DFFA1. Indicates that the external power supply 1 is below the minimum threshold.
Weak Infeed DFFA2. Indicates that the external power supply 2 is below the minimum threshold.
Table 169 Battery failure monitoring outputs
The internal battery used for data maintenance is checked to ensure that it does not fall below a security level.
❑ GEN/LPHD1 node
❑ It does not use settings.
❑ There are no logical inputs or commands.
❑ Outputs: Table 170 shows the function’s output data.
Internal battery failure. Indicates that the internal battery level is below the minimum threshold.
❑ Measurement. The battery value is available (see Table 171)
The unit continually checks the various incorporated elements and cards. If an error is detected in any of the elements or cards, an
alarm is generated. If the error affects the unit’s operation, a critical error is generated, which in addition to the signal acts on :
❑ Colour front LED. Non-configurable status LED, which indicates the unit’s general status. If the LED is green, it indicates
that everything is correct, while if it is red it indicates a critical error in the unit.
❑ CPU Relay. Non-configurable 3-contact relay, which indicates the unit’s general status. If the LED is active (common
terminal – NO), it indicates that everything is correct, while if it is deactivated (common terminal– NC) it indicates a critical
error in the unit. If the unit is switched off, the relay is deactivated.
❑ The unit's alarm signals are to be found in the LPHD node. The available signals indicate faults in the card check, in the
communications between the cards, in the unit’s configuration, etc.:
❑ Critical hardware error. Indicates that a critical error has been produced. In addition to this signal, the cause that produced
the signal will be indicated.
❑ CPU error. Indicates that the check has detected an error in the CPU. It generates critical error signal.
❑ Analogue error. Indicates an error in transformers card. It generates critical error signal.
❑ I/O micro error. Indicates an error in the I/O cards’ micro.
❑ Analogue connection error. Indicates that a fault has been produced in the communications between the CPU and the
transformers card. It generates critical error signal.
❑ I/O connection error. Indicates that a fault has been produced in the communication between the CPU and an I/O card. It
generates critical error signal. Additionally, it will indicate the card which has suffered the failure:
Error card address x. Indicates that there is a communication error with the card with the address x.
❑ Front connection error. Indicates that a fault has been produced in the communications between the CPU and the unit’s
front card. It generates critical error signal.
❑ Shared analogue memory error. Indicates that a fault has been produced in the Data exchange memory between the CPU
and the transformers card. It generates critical error signal.
❑ Error shared I/O memory. Indicates that a fault has been produced in the Data exchange memory between the CPU and
the I/O cards. It generates critical error signal.
❑ RTC clock error. Indicates that the check has detected an error in the real time clock.
❑ Continuous component monitoring alarm. Indicates that an error in the continuous measurement monitoring has been
detected in the transformers card.
❑ Alarm settings. Indicates that errors have been detected in the storage of the unit’s settings. It generates critical error
signal.
❑ FW Alarm. Indicates that the relay firmware versions are incompatible.
❑ Memory check alarm. Indicates that errors have been detected in the checking of the unit’s memory. It generates critical
error signal.
❑ Converter check alarm. Indicates that errors have been detected in the transformers card AD converter. It generates
critical error signal.
❑ Converter voltage level alarm. Indicates that errors have been detected in the transformers card reference voltages. It
generates critical error signal.
❑ Relay activation alarm. Indicates that an error has been detected in the activation of at least one of the I/O cards’ relays. It
generates critical error signal.
❑ I/O configuration error. Indicates that the configuration of the I/O cards does not coincide with the unit’s correct
configuration. It generates critical error signal.
❑ General Vdc error. Indicates a failure in the internal power supply levels. It generates critical error signal.
❑ Frequency configuration error. This is not a unit failure, but rather a configuration failure. Indicates that the frequency
measurement of the signals being injected into the unit do not match the set measurement, that is, the unit is configured
as 50Hz and the signals which are being injected are greater than 55Hz; or that the unit is configured as 60 Hz and the
signals being injected are less than 55 Hz.
❑ Internal battery failure. Indicates that the data storage battery is below the security levels and that the data may be lost at
shutdown.
❑ Version compatibility error. Indicates that the versions of the unit's firmware are not correct.
❑ Time setting configuration alarm. Indicates that there is an error in the configuration of the unit’s time setting.
❑ For each I/O card there is are 5 signals, indicating:
Status OK. Indicates that the card is configured correctly and without errors.
Configured & No_detected. Indicates that the card is configured by the user, but not detected in the unit. This may be
because it is not assembled or because it has an error. Equivalent to the current communication error.
Different configuration. The type indicated by the user and the type detected by the unit do not coincide.
No_configured & detected. Indicates that card that has not been configured by the user has been detected in an
address.
Internal card error. A card check error has been received (includes relay check).
❑ ICD error. Indicates the last ICD received by the device was wrong and it was refused by the device. Once activated, this
signal is deactivated when a correct ICD is received.
❑ Power supply 1 OFF. Indicates that the power supply 1 is turned off. It is only available in devices with redundant power
supply.
❑ Power supply 2 OFF. Indicates that the power supply 2 is turned off. It is only available in devices with redundant power
supply.
❑ SV Board Error. Indicates that there is an error in the sampled values board.
10. CONFIGURATION
10.1 CID
Independently of the form used from among those listed above, the changes to the affected setting are stored in the unit’s CID file.
❑ Where “XXX” is an integer counter that is incremented each time paramRev is updated by a setting change.
❑ "paramRev origin text“depends on the origin of the setting change:
In the case of “New CID”, only those settings in the CID sent to the unit and which are out of range will be updated in
paramRev.
10.2 GENERAL
Two nodes are used for the general configuration of the unit
The settings available in the GEN/LLN0 node are shown in protection events mask enablind. Allows the generation of protection events
associated to the function. If set to "NO", the function's protection events are not generated. If set to "YES", the function's specific
mask is contemplated:
❑ Language. Indicates the unit’s language. Affects the display, reports, etc.
❑ Functional key block. It allows the functional key to be blocked. When blocked commands with functional key are not
allowed.
❑ Functional keys (remote). It allows key commands with the device in remote mode.
❑ Leds Blocking. Allows the activation of the LEDs to be blocked.
❑ Blocking allowed by command. It allows blocking the reception of block/unblock protection commands.
❑ Reset Digital Output. Indicates the logic input that, when activated, reset all the digital outputs.
❑ The supported IRIG-B formats are B002, B003, B006, B007 and IEEE1344. It select whether the year is taken into account in
the synchronization by IRIG. The options are:
“UTC without year”. The year is not taken into account and all the formats are admitted.
“UTC with year”. With formats B006, B007 and IEE1344 the year is not taken into account. It cannot be used with
formats B002 and B003 because they set the year to zero value.
“Local without year”. The year is not taken into account. All the formats are admitted.
“Local with year”. With formats B006, B007 and IEE1344 the year is not taken into account. It cannot be used with
formats B002 and B003 because they set the year to zero value.
❑ Local/remote selection. Indicates the logic input that, when activated,changes the device between local/remote.
❑ Erase records. Indicates the logic input that, when activated, deletes the unit’s report queues. Affects protection events,
faults, disturbance reports, historical measurement reports, etc.
❑ Remote/ Local type. It indicates how the unit will behave when it has to block the commands it is sent. See 17.2.1
❑ Flicker Enable. Enables the digital inputs’ swing supervising function.See 10.4.3
❑ Enable Events record. Allows the generation of protection events associated to the function. If set to “NO”, the function’s
protection events are not generated. If set to “YES”, the function’s specific mask is contemplated.
❑ Block full records. When set to "NO", queues are circular, when the maximun number of registers is fullfiled, the oldest
one is erased. If sets to "YES", when the maximun number of registers is fullfiled, the queue is blocked and no more
registers are stored. It affects protection events, faults, disturbance reports, historical measurement reports.
The settings available in the PROT/LLN0 node are shown in protection events mask enabling. Allows the generation of protection
events associated to the function. If set to "NO", the function's protection events are not generated. If set to "YES", the function's
specific mask is contemplated:
❑ Relay ON. Indicates whether the relay in service or not. If it is out of service, the protection functions do not act.
❑ Phase order. Selects the phase sequence ABC/CBA. Affects the direct and inverse sequences and, therefore, the functions
that use them. To check whether the order corresponds to wiring, check that the values expected for the indicated
configuration are obtained in the sequence measurements and that the phase current arguments (as seen in the status
screen) match selected sequence.
❑ Select Setting group 1. Indicates the logic input which, when activated, selects the settings table 1 as active.
❑ Select Setting group 2. Indicates the logic input which, when activated, selects the settings table 2 as active.
❑ Select Setting group 3. Indicates the logic input which, when activated, selects the settings table 3 as active.
❑ Select Setting group 4. Indicates the logic input which, when activated, selects the settings table 4 as active.
❑ Select Setting group 5. Indicates the logic input which, when activated, selects the settings table 5 as active.
❑ Select Setting group 6. Indicates the logic input which, when activated, selects the settings table 6 as active.
❑ Fault reports (Prim./sec.). Select the measurements of the display fault reports between primary and secondary.
❑ Enable Events record. Allows the generation of protection events associated to the function. If set to “NO”, the function’s
protection events are not generated. If set to “YES”, the function’s specific mask is contemplated.
The current and voltage transformers are configured in independent nodes, in which the units’ rated values, transformation ratios and
frequencies are indicated.
10.3.1 Current
Two PROT/TCTR nodes are used for the transformation ratios and PROT/TCIN for rated currents.
The settings used for the configuration of the current transformers ratios, which are used to provide primary measurements, are
(see Table 175):
❑ 3I0-IN measurement type. Selects the neutral measurement from between the measurement calculated for the
phase currents and the transformer measurement.
❑ Change sign P. Indicates if the sign change in the real power calculation is enabled.
❑ Change sign Q. Indicates if the sign change in the reactive calculation is enabled.
❑ Real energy constant. Indicates the real energy impulse factor, i.e., the number of kWh by virtue of which the
counter is incremented by one unit.
❑ Reactive energy constant. Indicates the reactive energy impulse factor, i.e., the number of kWh by virtue of which
the counter is incremented by one unit.
The energy counters value is available in the PROT/MMTR node, with the data:
10.4 INPUTS/OUTPUTS
The unit can host a variable number of input-output cards variable (from 1 to 7). Each card is configured with an internal address from
2 to 7. The power supply is assigned address 1, which is not configurable.
Each card is represented in the IEC 61850 data model as an instance of the GGIO node in the Logical Device called “GEN”. Each GGIO
has the internal address of the physical card as an instance. Thus, for example, if a unit has two input-output cards with internal
addresses 1 and 4, the GEN/GGIO1 and GEN/GGIO4 nodes will exist in the data model.
The number of digital input settings and signals present in each GGIO depends on the type of card used. Continuing the example, if the
card with the internal address 1 has 6 digital inputs and 4 digital outputs, the GGIO1 node will have 6 digital input signals and 4 digital
output signals, as well as the settings corresponding to each digital input and output available.
The data model associated to the GGIOs is common to all and has 32 digital inputs and 16 digital outputs. Nevertheless, in each card
only the data associated with its own inputs and outputs are updated.
For each GGIO there is a boolean setting called MaskEna (event record enabled). If set to “YES”, the activation/deactivation of the
digital inputs and outputs will generate protection events. To the contrary, they will not be stored as event records.
10.4.1 Inputs
There are 2 settings available for each digital input:
❑ DIxTmms: Digital input time x (ms). This is a software filter for the activation/deactivation of digital inputs. It
indicates the milliseconds (range 0 to 100 ms30) which a digital input must be seen to be active in order to be
considered active. In order to calculate an input's total activation time, the input’s hardware filter delay – which is
approximately 1ms – must be added to this time.
❑ DIxType: Digital input type x. Defines whether the input is to be interpreted as active when it is seen as closed (NO)
or when it is seen as open (NC)
Each digital input has an associated digital signal indicating its status (see Table 179). Each GGIO indicates the status of all its digital
inputs (up to 32).
30
From firmware version 5.20.15.8 and ICD version 6.3.0.0. In previous versions the maximun was 20ms
10.4.2 Outputs
There are 3 settings available for each digital output:
❑ DOxSig: Assignment digital output x. Assigns the activation of the digital output. There are several assignment
possibilities:
Signals: They can be signals generated by the unit (trips, logics, hw check, digital inputs and outputs)
Commands: All of the commands available in the unit can be directly programmed to a physical output
❑ DOxTmms: Digital output time x (ms). The output activation time defines the minimum operational time of each
physical output following activation (in milliseconds). The range is 0.05 to 5000 ms. The output remains active in
accordance with this time setting or the duration of the associated signal, whichever is greater.
❑ DOxTyp: Digital output type. Each output’s type is defined from among the options:
“Not”. The output follows the assigned signal, i.e., the output is activate when the signal is active. When the
signal is deactivated, the output will deactivate if the digital output time has elapsed. To the contrary, the
output will remain active until this time elapses.
“Stored”. Once activated, the output remains active until the relay deactivation command is issued, with the
signal assigned to the output deactivated. The command can be issued by the action of a digital input
programmed as “Local reset”, a command or by keyboard/display.
“Trip”. Once activated, the output remains active until the following conditions are met: the signal assigned to
the output is deactivated and the breaker is open.
“Close”. Once activated, the output remains active until the following conditions are met: the signal assigned
to the output is deactivated and the breaker is closed.
Each digital input has an associated digital signal indicating its status (see Table 181). Each GGIO indicates the status of all its digital
outputs (up to 16).
The supervising of the swing in the digital inputs or the supervising of the flicker is conducted in accordance with certain user-
configurable settings.
On the one hand, there is a general setting that allows this function to be enabled or disabled. If this setting is disabled, not flicker
treatment is performed.
General setting for the configuration of the flicker treatment (Table 182):
❑ GEN/LLN0 node
Once the general flicker setting has been enabled (Table 182), there are two more setting per card for treating the swing.
They are “OscTms” and “Nchanges” which can be seen in Table 180:
❑ OscTms: The time between changes in the same direction in order for a signal to be deemed to be swinging. When a signal
is swinging a swinging signal is produced. The unit is seconds.
❑ Nchanges: The number of changes that must be produced in a swinging signal in order for the signal to become invalid and
cease from sending changes. If this setting is set to zero, it disables the swing treatment for this card, i.e., the flicker
treatment is not performed for this card.
❑ GEN/GGIOx node, in which x depends on the card’s internal address (see section 10.4)
Once a signal has been detected as swinging, it becomes questionable and oscillatory.
If this situation continues and the number of set changes (“Nchanges” setting) is exceed, the signal becomes invalid and oscillatory.
It ceases to send the changes and sends the signal's last known valid status.
When the time difference between two changes is greater than the inputs’ swing time (“OscTms” setting), the signal changes to
valid.
10.5 LEDS
❑ LexSig: Assignment led x. Assigns the activation of LED x using any of the signals generated by the unit
❑ LExTyp: LED type x. It can be programmed as “not” and “stored”. In the first case, the activation of the LED follows the
activation of the signal programmed in the setting described above. If it is programmed as “stored”, the LED’s activation
will remain even if the signal that provoked its activation drops out, until the signal programmed in the LogInReLed setting
available in the IHMI node is activated.
There is a general setting for all the LEDs that indicates the logic signal used to switch of the LEDs:
❑ LED reset. Selects the signal which, when active, switches off the LEDs.
The LEDs are updated every 200ms. Thus, for the correct activation of the LEDs, the assigned signal must remain active for at least
150 ms. To the contrary, the LED cannot be activated.
❑ The parameterization of the assignment of LEDs is carried out by the settings present in the CTRL/IHMI node.
❑ The parameterization of the LEDs type is carried out by the settings present in the CTRL/IHMI node.
The settings present in this node are detailed below
❑ InRefx: Assignment led x. Assings the activation of LED x using any of the signals generated by the unit. The
assignment is carried out by means of a character string (see next section “Configuration with InRef”)
❑ LEDSex: LED type x. It can be programmed as “not” and “stored”. In the first case, the activation of the LED follows
the activation of the signal programmed in the setting described above. If it is programmed as “stored”, the LED’s
activation will remain even if the signal that provoked its activation drops out, until the signal programmed in the
LogInReLed setting available in the GEN/IHMI node (defined in the previous section) is activated.
The InRef type settings are programmed by a string of characters in which the reference of the IEC 61850 object containing the value to
be employed as an input is indicated. The following format, as defined in the part 7.2 of the IEC 61850 standard, is employed:
LDName/LNName.DataObjectName[.SubDataObjectName[. ...]].DataAttributeName
For example,
❑ In order to program InRef1 with the GGIO1 input signal 1, the reference to be written in the InRef is:
GEN/GGIO1.Ind1.stVal
❑ In order to program the PTOC 1 phase A trip, the reference is:
PROT/PTOC1.Op.phsA
Generic commands are available within the Logical Device "GEN" on the ordGGIO1 node, which will be active for 100msg.
Are available signals associated with these generic commands, which will be available in logic, output, etc.
10.8 NAMES
The PROT/LPHD node is used for the general configuration of the units’ names and the installation.
Short names are used for the generation of the disturbance recorder and fault file names.
These settings are considered special and they are configurable via an IEC 61850 connection or sending the CID file after editing the
values from pacFactory tool (menu Settings -> IPRV). They do not appear in the display or section pacFactory protection settings.
❑ LocalTim: Allows to force sending local time in IEC 61850 timestamps. It is important to know that this is not normative
because IEC 61850 standard defines that the timestamps must be sent in UTC format. However, with this option the device
is adapted to systems that only use local time. The default value is 0, which indicates the use of UTC. The value 1 indicates
the use of local time.
❑ MaxConn: Sets the maximum number of IEC 61850 connections that are accepted. Limited to a maximum value of 16.
❑ AplicTms: Defines the disconnection timeout at the application level. After this time (in seconds) without receiving any IEC
61850 messages the server automatically closes the connection.
❑ TipoServ: Defines some operation modes of the device.
Value 0: Default operation mode.
Value 1: Special operation mode that includes:
Enable IP checking to validate a new ICD/CID file. If the IP address indicated in the communications section of
the ICD/CID file does not match the address of the device the file is not validated. If the IP address of the
device is changed once the file has been validated, the IEC 61850 server is disabled and waits for the change of
the IP address of the device with the one in the file or to receive a new CID file with the correct IP.
When a command is received, the value that the device saves in "orIdent" attribute is the IP address from
which the command was sent, regardless of the value that the client sent in the message.
❑ AuthReq: Allows activating the password authentication in the establishment of IEC 61850 connection. The password
received is checked against the one assigned to the user “user61850”.
The default password for this user is: user61850.
❑ DevGoose: Selects the Ethernet port for GOOSE messages. Any online change of this value requires the reset of the device
and therefore the signal ResetDev is activated.
Eth1: GOOSE publication and reception enabled on interface ETH1.
Eth2: GOOSE publication and reception enabled on interface ETH2.
Both (Eth1): Reception on both interfaces (ETH1 and ETH2). Publication is sent by only one configurable
interface for each GOOSE. By default port ETH1.
Both (Eth2): Reception on both interfaces (ETH1 and ETH2). Publication is sent by only one configurable
interface for each GOOSE. By default port ETH2.
❑ NoGsVlan: Defines the use of the VLAN tag in GOOSE messages. Any change in this value causes the activation of the signal
ResetDev. Default value is 0.
Value 0: GOOSE messages are sent with VLAN TAG and are received with or without VLAN TAG.
Value 1: GOOSE messages are sent and received only without VLAN TAG.
❑ IprvMod: Sets the access level to reports, commands and logs from the different IP addresses configured in the IPRV logical
nodes defined in the following paragraph:
Permissive: By default all IP addresses not configured in the IPRV logical nodes have access to reports,
commands and logs. The IP addresses included in the IPRV logical nodes will have the configured access level.
Restrictive: Only IP addresses configured in the IPRV logical nodes have access to reports, commands and logs.
The access level is configured individually for each IP address. Other IP addresses do not have access.
❑ IprvConn: The value 1 limits the IEC 61850 connections only to IP addresses configured on IPRV logical nodes and any
connection from other IP address will be rejected. The value 0 allows the connection from any IP address.
Only the settings that indicate the activation of the signal ResetDev require a restart of the device to be effective.
These settings are considered special and they are configurable via an IEC 61850 connection or sending the CID file after editing the
values from pacFactory tool (menu Settings -> IPRV). They do not appear in the display or section pacFactory protection settings.
Measures logical nodes which have the AdRanMea setting have the possibility of the automatic configuration of the measures
ranges (with value 1 in the AdRanMea setting).
AdRanMea settings in different logical nodes are independent. Each logical node can be configured independently.
If the value of AdRanMea setting is 1, the range configuration cannot be modified via IEC 61850 protocol.
Measures:
❑ rangeC.hhLim.f
❑ rangeC.hLim.f
❑ rangeC.lLim.f
❑ rangeC.llLim.f
❑ rangeC.min.f
❑ rangeC.max.f
Angles:
❑ rangeAngC.hhLim.f
❑ rangeAngC.hLim.f
❑ rangeAngC.lLim.f
❑ rangeAngC.llLim.f
❑ rangeAngC.min.f
❑ rangeAngC.max.f
The calculation is made based on the values of scale range and transformation ratio of each measure as follows:
❑ Signed measures:
❑ max: scale range * transformation ratio
❑ min: - (scale range * transformation ratio)
❑ Unsigned measures
❑ max: scale range * transformation ratio
❑ min: 0
And the value of the factor configured in the multiplier attribute is applied:
❑ hLim = max
❑ hhLim = max
❑ lLim = max * 4 / 5
❑ llLim = max * 4 / 5
The rest of the configuration values of each measurement (db, SIUnits, multiplier, dbAng, limDb) are not modified.
11. SYNCHRONIZATION
Several synchronization sources are permitted, with the following priority:
❑ IEEE1588v231
❑ IRIG-B
❑ SNTP
❑ Communication protocols
❑ pacFactory (see specific user manual)
❑ Local display
In case of active synchronization with any of the sources, the sources of lower priority are blocked. Some examples:
❑ If there is synchronization by IEEE1588v2, synchronization for any other cause is not permitted. In order to consider the absence of
IEEE1588v2 synchronization and to allow other sources, 1.5 minutes must elapse without synchronization:
When disabled by setting
When you lose IEEE 1588v2 communication through the port (synchronization does not arrive)
When it loses traceability or precision (the master is not synchronized)
❑ If there is synchronization by IRIG, synchronization for any other cause is not permitted. In order to consider the absence of IRIG
synchronization and to allow other sources, 1.5 minutes must elapse without the reception of correct IRIG frames.
❑ If there SNTP synchronization, the synchronization of protocols is not permitted, nor pacFactory nor display. However, if IRIG
synchronization is received, the SNTP is blocked and IRIG is synchronized.
❑ Synchronization by pacFactory and by display have the same priority and can be run simultaneously.
The unit’s data model has a GEN/LTIM node for the configuring the summer/winter time change. The node has the following settings
(see Table 185):
❑ Offset Local Time-UTC (min): Offset Local Time-UTC (min). A setting that indicates the number of minutes by which the time setting
must be put forward/put back when changing between summer/winter time. Range between -720 and 720 minutes (-12 to + 12
hours)
❑ Summer-winter time change enabled: Time change enabled. A boolean setting that allows the time setting to be changed
❑ Summer Calendar Pattern: Summer Calendar Pattern. Three selectable values:
Last of month: Last week, refers to the weekday set in WkDayD
First of month: First week, refers to the weekday set in WkDayD
Second of month: Second week, refers to the weekday set in WkDayD
Third of month: Third week, refers to the weekday set in WkDayD
Fourth of month: Fourth week, refers to the weekday set in WkDayD
Day of month: Selects the day of the month indicated in DayD
❑ Day Week Summer: Indicates the day of the week for the change to summer time (Monday.. Sunday)
❑ Month Summer: Indicates the month in which the change to summer time occurs (January.. December)
❑ Day Summer: Indicates the day in which the change to summer time occurs (1.. 31)
❑ Time Summer: Indicates the time at which the time changes to summer time
❑ Minute Summer: Indicates the minute (within the time set on HrD) when the time changes to summer time
❑ Winter Calendar Pattern: Winter Calendar Pattern. Equivalent to OccD but from winter to summer
31
Available from firmware version 6.0.18.0
Ingeteam Power Technology S.A.
User Manual 313
SYNCHRONIZATION
❑ Day Week Winter: Indicates the day of the week for the change to winter time (Monday.. Sunday)
❑ Month Winter: Indicates the month in which the change to winter time occurs (January.. December)
❑ Day Winter: Indicates the day in which the change to winter time occurs (1.. 31)
❑ Time Winter: Indicates the time at which the time changes to winter time
❑ Minute Winter: Indicates the minute (within the time set on HrS) when the time changes to winter time
❑ Not Synchro Time (min): Timeout to activate synchronization alarm.
Table 185 Synchronization settings
❑ Synchronization by IEEE1588: Active when the device is synchronized by IEEE1588. It is maintained activated for 90 seconds after
an IEEE1588 synchronization.
❑ Synchronization by IRIG-B: Active when the device is synchronized by IRIG-B. It is maintained activated for 90 seconds after an IRIG-
B synchronization.
❑ SNTP synchronization: Active when the device is synchronized by SNTP. It is maintained activated the period defined by not synchro
timeout SNTP setting (ValTm) after an SNTP synchronization.
❑ Synchronization by protocols: Active if the last synchronization was been received by communications protocols.
❑ Synchronization by display: Active if the last synchronization was been received by the front keyboard.
❑ Synchronization by console: Active if the last synchronization has been received from the PacFactory console.
❑ Device not synchronized: Synchronization alarm. Active if a valid synchronization (IRIG-B, SNTP or protocols) has not been received
during the timeout configured by the not synchro time setting (SyncAlmTm).
❑ Daylight saving time: Active if the local time has summer correction.
The IEEE Std. 1588-2008, also known as IEEE 1588v2 or PTPv2, offers a good solution for clock synchronization in distributed systems
with high accuracy requirements. It works through Ethernet networks and achieves accuracy in the submicrosecond range.
Ingepac EF IEDs support IEEE 1588v2 and specifically the IEC 61850-9-3:2016 Ed1, also nown as Power Utility Profile (PUP), which allows
compliance with the highest synchronization classes of IEC 61850-5 and IEC 61869-9.
❑ The PTP over IEEE 802.3 transport mapping, specified in Annex F of IEEE 1588v2, shall be the only transport mechanism used.
❑ The peer delay request mechanism specified in Chapter 11.4 and Annex J.4 of IEEE 1588v2 shall be the only path delay
measurement mechanism in operation.
Ingepac EF IEDs support IEEE 62439-3:2016 Ed 3 Annex A when 1588 synchronization over PRP or HSR is needed.
11.2.1 Settings
There are 3 settings to set up IEEE 1588v2. They all belong to the GEN/LTMS logical node described in 1.4.1.
❑ Main Time Source: The string “1588” must be set up in this setting in order to enable 1588v2.
❑ PTP interface: This setting specifies the interface in which the IED will listen to IEEE 1588v2 messages.
❑ PTP delay mechanism: The Mechanism used peer to peer (P2P).
11.3 IRIG-B
The device is equipped with an input for synchronization by GPS, using IRIG-B time codes (consult chapter 2 for more details about the
input).
The supported IRIG-B formats are B002, B003, B006, B007 and IEEE1344. The configuration is with the IrgType setting in the GEN\LLN0
logical node (General configuration). The different options are (depending on whether the GPS send UTC or local time):
❑ “UTC without year”. The year is not taken into account and all the formats are admitted.
❑ “UTC with year”. With formats B006, B007 and IEE1344 the year is not taken into account. It cannot be used with formats
B002 and B003 because they set the year to zero value.
❑ “Local without year”. The year is not taken into account. All the formats are admitted.
❑ “Local with year”. With formats B006, B007 and IEE1344 the year is not taken into account. It cannot be used with formats
B002 and B003 because they set the year to zero value.
11.4 SNTP
The available implementation of the SNTP (Simple Network Time Protocol) is based on the points described in RFC5905. To improve the
accuracy of the synchronization and to take into account the possible delays introduced by the network, the "On-Wire" protocol, which
is described within the RFC itself, is used.
This correction algorithm uses four timestamps numbered from T1 to T4, with the timestamp of sending or receiving each message, to
calculate the offset that is required to apply to the time of the equipment after sending each synchronization request.
The time offset obtained using this calculation is the deviation to be applied in the SNTP client clock to obtain the time of the SNTP
server that synchronizes it. It is a valid method for both LAN networks as well as for WAN networks that have higher response times.
Note: There is an optional configuration mode with the SNTP-IP value in the communications section of the ICD file, which is
maintained for backward compatibility with previous configuration files. The IED only uses that option if no configuration is included in
the LTMS node. Nevertheless, the recommended configuration option is through the LTMS node settings.
11.4.1 Settings
The SNTP settings are in the GEN/LTMS logical node:
❑ Main Time Source: IP address of the main NTP server. Broadcast addresses are not allowed. Value 0.0.0.0 disables the
main source.
❑ Secondary Time Source: IP address of the secondary NTP server. Broadcast addresses are not allowed. Value 0.0.0.0
disables the secondary source.
❑ Not Synchro time SNTP (min): Elapsed time in which it has not been received any correct SNTP response (the checked
fields are detailed below) from any of the sources configured for SNTP synchronization to consider the SNTP as not
synchronized. Range value is 1 to 1440 min.
❑ SNTP Polling Time (seg): Time interval between synchronization requests to the NTP servers. Range value is 10 to 3600
seconds. If the configured time is less than the real polling communication process (requests and retries in case of failure)
the synchronization active request will finish normally and a new polling timer will be started.
❑ SNTP Time delay Unicast message (seg): Waiting time for the response to an unicast synchronization request. If no
response is received in that time interval a unicast request retry cycle will be started. Range value is 1 to 60 seg.
❑ Retry number: Number of unicast request retries in case there is no response from the NTP server to a request. If the
configured number of retries finishes without response with the main source the device tries to synchronize with the
secondary source. If the configured number of retries finishes without response with the secondary source that
synchronization process is finished and the device waits the polling period to send a new request. Range value is 0 to 9.
❑ PTP interface: This setting specifies the interface in which the IED will listen to IEEE 1588v2 messages.
❑ PTP delay mechanism: This settings specifies which delay Mechanism to use: peer to peer (P2P) or end to end (E2E) delay
mechanism.
(*) Available from firmware version 6.3.20.0, the necessary settings to enable and configure symmetric key authentication in SNTP
requests:
❑ SNTP authentication: This setting enables the authentication in SNTP messages based on the keys file configured.
❑ SNTP key: The number of the key used for the authentication. It shall match with the value configured in the SNTP server
used as synchronization source.
The keys file is configurable from the website 32, and it shall be shared between the IED and the SNTP server. The following key types
are supported by the IED:
❑ MD5
❑ SHA
❑ SHA1
❑ RIPEMD160
To provide additional information, a digital signal and a counter have been added with data about the status of the SNTP
authentication:
❑ AuthCfgErr: Configuration error boolean signal. Indicates that there is some type of error in the configuration of the keys
file or in the selected settings. In this case, the IED sends SNTP requests without authentication so it can be synchronized.
❑ AuthRspErr: Counter with the number of not authenticated responses or with authentication failure. When this occurs, the
response obtained is discarded and the device is not synchronized. This counter is increased in case of:
The SNTP server rejected the request (because the key was not configured or the expected signed value did
not match).
The received authentication is not considered valid (the calculated signed value does not match the expected
one).
32
Available from firmware version 6.5.22.0
The following values are checked in the synchronization responses to consider them valid and apply the time to the internal clock:
❑ Message length.
❑ Flags mode: Server.
❑ Flags version number: NTP version 4.
❑ Flags leap indicator: Different from 3.
From the following firmware versions of Ingepac EF these checks are also available:
In the IEC 61850 data there are quality flags which detail the validity of the time in a timestamp sent by communications. These are the
used quality flags:
❑ Clock Not Synchronized: Active jointly with the synchronization failure alarm.
❑ Leap Second: It is activated if the synchronization source provides this data. Active for SNTP, IRIG-B and 1588.
❑ Clock Failure: Active jointly with the failure of the internal RTC clock.
The status report indicates the current status of the protection, showing instantaneous values. This report is updated approximately
every 1 second.
<CapacitorBank.> Indicate the input measurements to capacitor bank connect/disconnection automatism, voltage
and reactive.
❑ Input and output status. The status of the digital inputs and outputs is indicated in each of the cards available in the unit.
Each card is distinguished by its address, indicated in GGIO1 to GGIO8.
Digital inputs. Ind1.stVal to Ind32.stVal indicate “Y” if enabled and “N” if not. There are as many values as there are
inputs in the card.
Digital outputs. SPCSO1.stVal to SPCSO16.stVal indicate “Y” if enabled and “N” if not. There are as many values as
there are outputs in the card.
❑ Protection units. Indicates the current status of each of the functions: enabled, pick up, trip and last trip. In each of the
functions the data available in each node are indicated.
Status. In <StEna.stVal>, the function is indicated as active and not blocked with “Y”. “N” is used to indicate that the
function is not enabled or blocked or in operation
Pick up. Indicates in <Str> whether the unit is picked up “Y” or not “N”. The data depends on the unit, for example, for
phase A it would be Str.phsA.
Activation. Indicates in <Op> whether the unit is tripped “Y” or not “N”. The data depends on the unit, for example, for
phase A it would be Str.phsA.
Last trip. Indicated within <l>. “Y” is used to indicate if the last trip was due to this cause, whilst "N" is used to indicate
otherwise.
❑ Recloser status: Indicates the current status of the recloser. The signals are in <RREC1>. “Y” is used to indicate active
signals, whereas "N" is used to indicate inactive signals. The available signals and their references are indicated in the
recloser section. These include:
in service/blocked.
in stand-by.
ongoing cycle, indicating the closure cycle that is currently active.
definitive trip.
internal block, distinguishing different causes.
External block.
“Put Into Service and “Put Out of Service” buttons
❑ Frequency recloser status: Indicates the current status of the frequency recloser. The signals are in <FRREC1>. “Y” is used
to indicate active signals, whereas "N" is used to indicate inactive signals. The available signals and their references are
indicated in the frequency recloser section.
❑ Synchronism check unit status. The general status of the synchronism is displayed in RSYN1 and the presence of voltage in
RVRS1. “Y” is used indicated active signals and "N" for inactive signals. The available signals and their references are
indicated in the synchronism section.
❑ In CB models (Capacitor Bank): Status of capacitor bank connect/disconnection automatism. Indicates the actual state of
automatism. The signals are in <ZCAP>, indicating for each of the signals if is active "Y" or no "N". In the section of
capacitor bank automatism are indicated available signals and their reference, among which are:
Automatism Status
Trip Block 86
Reactive Converter Fail
Manoeuvre Inhibit for each breaker
Excesive Manoeuvre
Open command
Period type (Rush, Off-peak, Normal)
Season
❑ Protection status. With the “PROT” data in LLN0, “Y” indicates whether the relay is in service, “N” indicates if the relay is
out of service.
❑ General status. Indicated in LLN0 with the “GEN” data, in which the following is indicated:
❑ PacFactory. All the status message information is displayed, grouped in tabs according to the information:
General. The date, active table, versions and measurements are displayed.
I/O. The digital inputs and outputs are displayed.
Enabled. Indicates whether the units are operative (enabled and not blocked) or not.
Protection status. The status of the protection units is displayed, i.e., if they are picked up and/or tripped.
Breaker and monitoring. The breaker, breaker monitoring and circuits statuses are displayed.
Recloser, synchronism or capacitor bank. The status of the recloser, synchronism or capacitor bank units is displayed.
Check. The results of the various checks that are carried out in the unit are displayed.
❑ Display. Grouped into several screens and displaying:
General: Date and active table.
Transformer measurements and configuration.
Current and voltage maximeters.
I/O. The digital inputs and outputs are displayed.
This report indicates the measurement transformers’ primary measurements, applying the transformer ratio. The maximeter
information is used for the maximeter reports.
❑ Distance. In the <Distance> tag, indicating the distance of the last fault.
❑ Currents. Within the <Currents> tag, showing the rms current measurements in primary:
Earth-phase.
The module and angle of each phase, neutral and sensitive neutral.
The average current module of the three phases.
THD of each phase, neutral and sensitive neutral.
Thermal image <Thermal>. Value of phase and neutral thermal image.
Sequences <Sequence>. Current sequences module (I0, I1, I2)
❑ Voltages Within the <Voltage> tag, showing the rms voltage measurements in primary:
Earth-phase.
The module and angle of each phase and neutral.
The average voltage module of the three phases.
THD of each phase and neutral.
Phase-phase <Phase>.
Phase pair module (AB, BC and CA) and average.
❑ Sequences. Voltage sequences module (V0, V1, V2)
Frequency. Frequency value.
Powers. Within the <Power> tag, showing the rms measurements for each phase and total:
Real power. Per phase and total.
The fault reports include information about the unit’s data during the fault, as well as the active settings during the fault. The last 20
faults are stored in a non-volatile memory.
The name of the file uses the standard IEEE C37.232-2007, using the fields:
Start Date, Start Time, Time Code, Station Identifier, Device Identifier, Company Name
❑ Start Date: Trip date with a 2-character format for the year, the month and the day. For example, 26/june/2010 would be 100626.
❑ Start Time: Indicates the milliseconds as of 00:00 of the day, that is, milliseconds as of midnight.
❑ Time Code: Indicates the time zone amplitude sign, and can indicate minutes if necessary. For example, “t +2” indicates time zone
2, while “+2 h30t” indicates that the time zone is 2 hours 30 minutes.
❑ Station Identifier. Indicates the substation name. The installation’s short name (InsShNam) from the “PROT/LPHD1” node is used"
❑ Device Identifier. Indicates the unit’s name. The relay’s short name (RelShNam) from the “PROT/LPHD1” node is used"
❑ Company Name. Indicates the name of unit’s manufacturer, in this case, Ingeteam.
The information available in the fault is:
❑ Date and time: <Fecha>. Indicates the date as a string in the “dd/mm/yy hh:mm:ss.ms” format, i.e., “23/04/09 10_41_30_256”.
There are three dates available
Start of the fault (first unit picked up): <Inicio>
Trip (first unit tripped): <Disparo>.
End of fault (when the trip signal disappears): <Fin>
❑ Configuration: <Config>. Indicates the configuration of each of the 12 transformers: type and scale range.
❑ Pre-fault and fault. Indicates the values measured before the fault and upon the fault. They are grouped into “Pre-fault” and
“Fault”, and the same data is available in both cases:
Transformer measurements <Analog>. It indicates the measurement in the module and the angle of each transformer.
Sequences. Indicates the measurements in the module and the angle of the current sequences (I0, I1 and I2) and the voltage
(V0, V1 and V2).
Powers. Indicates the measurements of the total real, reactive and apparent powers.
The LD models show information of:
Differential current. Indicates the fundamental value of the three phases.
Restraint current. Indicates the Restraint current of the three phases
2° harmonic differential current. Indicates the value of the three phases.
End measures. For each end, indicates the fundamental and 2° harmonic of the total currents (module and
angle) of the three phases.
The TD models show information of:
Differential current. Indicates the fundamental value of the three phases.
Restraint current. Indicates the Restraint current of the three phases.
Sequences of current, maximeter and thermal image are independent of each winding.
❑ Distance to fault.
❑ Frequency in the moment of the fault.
❑ Thermal image upon trip. The thermal image is indicated as a % of phases and neutral.
❑ Fault max. Maximum values of the current channels and I0 during the fault.
❑ Breaker. Indicates breaker monitoring data upon the fault.
Open current. For each phase, indicates the current value upon the trip.
Sigma ki. For each phase, indicates the sigma ki2 value.
Num. reclose. Number of recloser performances.
❑ Fault and trip type <Tipo/Type>: Summary of the fault with the 3-letter code formed by combinations of the characters A, B, C, N,
NS and G (if tripped by a phase, neutral, sensitive neutral or ground), DIF (differential), RG (restricted earth), RTP (teleprotection),
IF (phase overcurrent), IN (neutral overcurrent), D (current unbalance), VO (zero-sequence overvoltage), HV (overvoltage), LV
(undervoltage), RTP (teleprotection), DT (transferred trip), DP (pole discordance), v/f (overexcitation v/f), IT (thermal image).
Example: AC is a two-phase fault in phases A and C.
Fault type: Indicates the pick up type.
Trip type: Indicates the trip type.
❑ Details of units. Indicates the picked up and tripped units. Indicates whether the unit is active “Y” or not “N” for each logical node
available in the unit.
Pick up. Indicates in <Str> whether the unit is picked up “Y” or not “N”. The data depends on the unit, for example, for phase A
it would be Str.phsA.
Activation. Indicates in <Op> whether the unit is tripped “Y” or not “N”. The data depends on the unit, for example, for phase
A it would be Str.phsA.
❑ Active settings. Active settings in the moment of the fault. Indicates the setting file name. It can be accessed to consult the settings.
Figure 188 PacFactory fault screen
The unit stores in a queue of 1000 non-simultaneous protection events in a non-volatile memory. Each protection event is recorded
with its date and time, as well as the current and voltage measurements of all the transformers and the frequency.
The protection events can be masked individually, so that only protection events configured by the user are generated. These enablings
are available in the GEN/RSUC node.
The unit saves a queue of historical measurement reports in the non-volatile memory. Depending on the registered measurements,
4000 or 1000 registers are available.
Each record includes the maximum, minimum and average currents of each measurement, calculated within a programmable time
window, detected during a programmable recording period. The measurements are secondary.
The historical measurement report is grouped into records in which the first corresponds to the oldest and the last to most recent, so
that when the file is opened, the first item we see is the oldest.
❑ Record number
❑ Date: With second precision: Day and Time
❑ Measurements: Maximum/minimum/average magnitude values:
The settings employed by this unit are in the PROT/MHRE node:
❑ Sample time window. Indicates the time in minutes during which the average is calculated
❑ Record interval. Indicates the time in minutes in which each record is created
❑ Start time. Indicates the time after which the historical measurement record is started
❑ End time. Indicating the time up to which the historical measurements record is carried out
❑ Calendar mask. Indicates whether the historical measurements record is created every day (YES) or if it is only created on
the days indicated in the day selection mask.
❑ Day selection. It indicated, for each day of the week, whether the record was created.
❑ Register mode33. Selects between standard or extended:
Standard. It saves 4000 registers, with máximum, mínimum and average of the mean currents and voltages, real,
reactive and apparent power, frequency and external power supply.
Extended. Extended number of measures. It saves 1000 registers, with máximum, mínimum and average of the phase
and neutral currents, phase voltages, current and voltage sequences, real, reactive and apparent power, power factor
and the result of 10 measurements data logics AutGGIO.AnIn.
The units of the measurements are:
33
Available from firmware version 5.19.15.7 and ICD version 6.3.0.0. Previous versions is fixed “Standard”.
</REG>
Displays the statistical data calculated in the unit: currents, action times and counters. It has reset buttons.
❑ The current statistics are grouped in the <Current> tag and include:
<ki2> Ki2 accumulated by each of the 3 phases. Each phase can be independently reset to the initial value.
<Cut> Opened current. Indicates the last (Last) and maximum (Maximum) open current per phase
❑ The counters are grouped in the <Counters> tag and include:
<Reclose> Reclosure counter. Indicates the number of reclosures effected, separating them according to first, second,
third and fourth reclosure. There is a command for resetting the counter.
<Openings>. Opening counter for each of the 3 phases, includes trips and manual openings. There are commands for
resetting each phase's counter and a global counter for all the phases.
<Trip>. Trip counter for each of the 3 phases. There are commands for resetting each phase's counter and a global
counter for all the phases.
<Close>. Closure counter for each of the 3 phases. There are commands for resetting each phase's counter and a global
counter for all the phases.
❑ The timers are grouped in the <Timers> tag and include:
<Opening>. Indicates the electric (Electrical) and mechanical (Mechanical) opening times in milliseconds per phase
(maximum, average and last) and the dispersion for each pair of phases (maximum, average and last).
<Close>. Indicates the electric (Electrical) and mechanical (Mechanical) closure times in milliseconds per phase
(maximum, average and last) and the dispersion for each pair of phases (maximum, average and last).
<Inactivity> Indicates the days of breaker inactivity for each phase.
❑ There are commands to reset:
Opening and close times
Inactivity days
Dispersion times.
❑ There is a command for the complete reset of each breaker: opening, trip and close counters, ki2, cut current and times.
The reclose counter is not reset.
❑ Models with two breakers, current, counters and times are independent for each breaker.
❑ <Time> Indicates the time in seconds during which the current has been within specific ranges.
From 2 to 5 times In
Displays the maximum and minimum values integrated in the time. It has buttons to individually reset the maximeters and/or
minimeters.
12.8 OSCILLOGRAPHY
The oscillography is stored in binary comtrade format. There is a CFG config file and a DAT data file for each.
For additional information see on “IEEE Standard Common Format for Transient Data Exchange (COMTRADE) for Power Systems”.
The trigger signals are selected among the registered signals, when the set “Trigger Signal” is set to “YES”. If it is set to “NO”, that signal
is registered but does not start the oscillography.
The length is set in cycles (Total Duration), from 20 up to 420 cycles (8,4 seconds for 50Hz and 7 seconds for 60Hz).
Pre-fault duration (cycles) indicates the pre-fault cycles that are stored in each disturbance recorder prior to the trigger, being able to
vary between 1 and 415 cycles.
The number of samples can be selected among the options of the following table. Depending on the device and ICD used, the number
of the samples per cycle is different to adapt to the different devices. The relationship between them is shown in the following table
34
Available since firmware version 6.0.18.2 and ICD 8.2.0.0. Up to that version there are 100 digital signals and 3 frequencies
The continuous mode allows increasing the length if at the end of the register there is a trigger signal activated. In that case, the
register continues the number of cycles set in the “Total Duration (cycles)”, checking again the trigger signals at the end of the new
register. The total register is limited to 5Mb or 3 times the setting “Total Duration (cycles)” (the most restrictive of both).
In order for the trigger signal to act, it has to change the status, that is, it has to pass from deactivated to activated. If one trigger signal
is continuously activated, it does not start, nor extend the oscillography register.
The digital signals set to “NO” in the “Trigger signal” setting are displayed, but do not start, nor extend the oscillography register.
The oscillography allows to display signals that do not start the register. For example, the protection trip signal can initialize an
oscillography register, where the start signals are displayed. Table 190 shows an example of an oscillography configuration, with 11
digital signals registered but only three signals start the register (General trip, 51 trip and GGIO1 Digital input 1). At the end of the
register, if one of these three signals, continues activated, the oscillography is extended the cycles set in “Total Duration (cycles)”;
otherwise the oscillography is finished.
Settings Value
Recorded signal 01 General trip
Trigger Signal 01 YES
Recorded signal 02 General start
Trigger Signal 02 NO
Recorded signal 03 51 start
Trigger Signal 03 NO
Recorded signal 04 51 trip
Trigger Signal 04 YES
Señal registrada oscilo 05 IOC1 Trip phase A
Trigger Signal 05 NO
Recorded signal 06 IOC1 Trip phase B
Trigger Signal 06 NO
Recorded signal 07 IOC1 Trip phase C
Trigger Signal 07 NO
Recorded signal 08 IOC1 Start phase A
Trigger Signal 08 NO
Recorded signal 09 IOC1 Start phase B
Trigger Signal 09 NO
Recorded signal 10 IOC1 Start phase C
Trigger Signal 10 NO
Recorded signal 11 GGIO1Digital input 1
Trigger Signal 11 YES
10Mb of non volatile memory is available to store oscillography registers. The total number of registers depends on the settings. Table
191 shows some examples of the capacity (with the continuous mode set to “NO”), where the most influential settings are the length
and the number of samples.
35
Available since ICD version 8.1.0.18
Total Duration
Number of samples/cycle Number of digital signals Number of oscillographys
(cycles)
420 144 100 3
420 144 32 3
420 36 100 13
420 36 32 15
50 144 100 27
50 144 32 32
50 36 100 98
50 36 32 121
20 144 100 34
20 144 32 78
20 36 100 206
20 36 32 271
20 16 100 350
20 16 32 499
❑ Total Duration (cycles). Indicates the total duration of disturbance recorder (in cycles).
❑ Pre-fault duration (cycles). Indicates the pre-fault cycles that are stored in each disturbance recorder
❑ Number of samples/cycle. Indicates the samples per cycle stored in the disturbance recorder.
❑ Recorded signal X. Indicates the signal that is stored in record position X. If programmed as -1, no signals are recorded.
❑ Trigger X signal. If the signal is configured, it indicates whether it provokes a disturbance recorder pick up (1) or not (0). If
set to “No”, it is only displayed.
The trigger and recorded signals are repeated up to 100 possible signals.
The disturbance record configuration file (CFG) contains the general disturbance recorder information (Figure 194):
❑ Total number of analogue and digital channels available in the disturbance recorder.
❑ Analogue channel data: bay, identification, measurements scaled (multiplier "a", offset "b") and limits (maximum and minimum).
The real value of the signal, using the value of the sample is "a·sample + b".
❑ Indication that samples are secondary values ("S") and conversion factor to primary values (it`s the setting “transformer ratio” of
the channel). As the samples are secondary values, the conversion factor to secondary is “1”.
❑ Digital input data: bay and identification.
❑ Sample data: signal frequency, sampling frequency, number of the last sample.
❑ Disturbance recorder start and end dates.
❑ Data file format
The disturbance recorder data file (DAT) includes the information captured in the disturbance recorder, with the following available for
each sample:
❑ Sample number
❑ Sample time
❑ Analogue samples values
❑ Digital signals values
The name of the file uses the standard IEEE C37.232-2007, using the fields:
Start Date, Start Time, Time Code, Station Identifier, Device Identifier, Company Name
❑ Start Date: Trip date with a 4-character format for the year, the month and the day. For example, 26/june/2010 would be
20100626.
❑ Start Time: Indicates the milliseconds since 00:00 of the day, that is, milliseconds since midnight.
❑ Time Code: Indicates the time zone amplitude sign, and can indicate minutes if necessary. For example, “t +2” indicates
time zone 2, while “+2 h30t” indicates that the time zone is 2 hours 30 minutes.
❑ Station Identifier. Indicates the substation name. The installation’s short name (InsShNam) from the “PROT/LPHD1” node
is used".
❑ Device Identifier. Indicates the unit’s name. The relay’s short name (RelShNam) from the “PROT/LPHD1” node is used".
❑ Company Name. Indicates the name of unit’s manufacturer, in this case, Ingeteam.
The USB port can be configured from the local HMI (Menu: Password -> USB Configuration).
When a pendrive is inserted, the following appears in the front above the current screen, indicating that the device has been detected:
USB Detected
While the data is being downloaded, the following appears in the front above the current screen:
USB Detected
Downloading data
Just in case there is a CID, an ICD or and IID in the pendrive, the user will be asked for a confirmation to load this file into the unit.
WANT TO START
CANCEL
ACCEPT
USB Detected
Downloading data
If canceled, downloading is assumed to be complete, and the following appears on the screen for 5 seconds:
REMOVE THE
USB DEVICE
Only the reports existent in the unit at the time of the download will appear in the pendrive, with the data structure:
Ingeteam Power Technology S.A.
User Manual 335
USB ACCESS
❑ Root with the short installation and relay name (PROT/LPHD node), and the iedName, separated by “_”·, i.e.,
“Instalacion_Rele_iedName”
❑ COMTRADE. This directory contains the disturbance recorders generated in the unit
❑ FAULT RECORDS. This directory contains the fault records generated in the unit.
❑ The rest of the unit’s reports are dependent on the root:
Maximetro.xml
Sucesos.xml
Informe_Estadisticos.xml
Registro.xml
CID
For detailed information about these reports, see Chapter 10, “DATA ACQUISITION FUNCTIONS
”.
When a pendrive is inserted into the front USB port, a check is run to see if an ICD exists. If there is an ICD, it is copied into the directory
“public/SCL/notvalidated” in order that it may be operative in the unit.
During the search for the ICD, the existence of a file with an ICD, icd, CID, cid, IID or iid extension is checked. There is not a established
filename as only the extension is checked.
If there is more than one file with one of the indicated extensions, the ICD is considered invalid and not ICD is captured.
When a pendrive is inserted into the front USB port, a check is run to see if a firewall configuration file exists. In that case, it is copied
into the directory “public/SCL/notvalidated” in order that it may be operative in the unit.
During the search, the existence of a file with “fwc” extension is checked. There is not a established filename as only the extension is
checked.
If there is more than one file with one of the indicated extensions, the file is considered invalid and not captured.
For firmware update via USB, a USB flash drive must be inserted in the front USB port, with a "FW" directory with a valid firmware file.
In the local display, the user will be prompted for a confirmation to start the update. It is very important that during the process of
updating firmware the device is not turned off since in that case the device could become unusable.
After the update the device will restart automatically and the result of the update can be consulted either in the device versions screen
or in the latest updates screen (consult display section).
To increase the security of the device, the USB port can be disabled, preventing access to the device via USB. With the USB disabled,
ICD and firmware loading and data download of the equipment are not allowed.
USB enable / disable can only be performed from the display (consult display section). It is done from the Password screen. The setting
will have 3 possible values:
❑ User: ftpuser
❑ Password: ftpuser
Available from firmware version 5.25.16.1, the device implements a sFTP access for secure connections as follows:
❑ User: sftpuser
❑ Password: sftpuser
The passwords can be modified from the local display or from the software tool pacFactory.
The key modification meets the criteria defined by the IEEE1686 standard (available from firmware version 6.3.20.0):
It is not allowed to reuse the previous key: including modifying only uppercase / lowercase. It is required a minimum of 4
characters modified with respect to the previous string.
Palindromes are not accepted.
These user profiles allows direct access to the following directorys and files:
Config directory:
❑ SCL/NotValidated: Directory to copy the new CID file to configure the device.
❑ SCL/Validated: Directory with the active CID configuracion file (read only).
❑ User: ftpUpdat
❑ Password: ftpUpdat
With this user you can access the directory "downloads" where a valid firmware file should be copied. Once the file is copied the update
will start automatically.
It is very important that during the process of updating firmware the device is not turned off since in that case the device could become
unusable.
After the update the device will restart automatically and the result of the update can be consulted either in the device versions screen or
in the latest updates screen (consult display section).
Available from firmware version 5.25.16.1: The device incorporates a management of failed accesses which after 5 consecutive
attempts to establish a connection using a wrong password, the access to that user is blocked for 10 minutes. From this moment, any
failed attempt blocks the user 10 more minutes. While a user is blocked the correct password is also not accepted to access.
The goal is to harden the system to avoid "brute-force attacks" to recover a key by trying all possible combinations until finding the one
that gains access.
There is a signal on GEN/LLN0 indicating the activation of this block for some user.
In addition, all FTP accesses are registered in a log file located in /config/SYSTEM_LOG folder called ftp.log.
In this file, the accesses of any FTP client are recorded, indicating the source IP address and the date and time. Any uploads or
downloads of files are also recorded.
The sAddr attribute allows the allocation of a short address to DO attributes. According to the IEC 61850 standard short addresses can be
used as IED internal identification for the attribute. In this scope the format of the content is private to the IED and any tool that process
the ICD/CID file shall preserve imported contents in exported SCL files.
All the signals (trips, logics, hw check, digital inputs-outputs, etc.), measurements and meters that are generated in the unit are identified
by a number that appears in the sAddress of each of these elements.
In the factory ICD configuration file, all the internal data is preconfigured, and the user cannot modified them apart from the description
texts.
For new data created at engineering phase, as control logics output data, the software configuration tool allows the creation of sAddress
values.
15.1 SIGNALS
The distribution of the unit’s signals is effected using four numbers as a base: 0, 8192, 16384, 24576. All the unit’s signals are divided
into four types, taking these four digits as references:
❑ Digital Inputs
Identification number between 0 and 287.
Example: sAddr="S,0,5,0;TX1:GGIO1.Digital input 6,TX2:GGIO1.Digital Input 6,AC:1.2,ED:1.1,AD:0.0"
In the example, we can see the identification number of digital input number six from the first card in the ICD
sAddress.
GEN/GGIO node
❑ Goose Signals
In turn, the Goose signals are divided into RIO modules and LGOS nodes.
RIO modules
Identification number between 288 and 607.
Example: sAddr="GS,0,288,0;TX1:RIO1.St,TX2:RIO1.St,AC:1.2,ED:1.1,AD:0.0"
In the example, we can see the identification number of the first signal from the first RIO module in the ICD
sAddress.
GEN/RIO node
❑ LGOS nodes
Identification number between 608 and 1695.
Example: sAddr="GS,0,608,0;TX1:LGOS1.St,TX2:LGOS1.St,AC:1.2,ED:1.1,AD:0.1"
In the example, we can see the identification number of the first signal from the first LGOS node in the ICD
sAddress.
GEN/LGOS node
Therefore, the distribution of these signals based on their identification number is as follows:
DIGITAL
INPUTS
(0 - 287)
GOOSE
SIGNALS
(288 - 1695)
This type of signal includes type B protection signals, fast protection logic signals and fast control logic signals.
Therefore, the distribution of these signals based on their identification number is as follows:
PROTECTION SIGNALS
TYPE B
(8192 - 9215)
(9216 - 9343)
(9344 - 9471)
ADDITIONAL
PROTECTION SIGNALS
TYPE B
(9472 -10399)
TYPE C PROTECTION
SIGNALS
(16384 - 16831)
This type of signal includes the type D protection signals, the communication failure signals for all the bays that are connected to
the unit, the slow logic control signals, signals resulting from orders and Loc and LocSta signals (for more information about these
signals go to 1.2.1 Command blocks by command hierarchies, in IEC 61850 commands)
LOC SIGNALS
(27424 - 27679)
LOCSTA SIGNALS
(27680 – 27935)
ADDITIONAL
PROTECTION SIGNALS
(27936 - 27967)
15.2 MEASUREMENTS
❑ Protection measurements.
Identification number between 0 and 299.
Example: sAddr="M,0,124,1;TX1:I average,TX2: AVERAGE I"
In the example, we can see the identification number of a protection measurement in the ICD sAddress.
Additional measurements: Identification number between 744 – 948 and 979 - 1266.
PROT node
❑ Goose Measurements
Identification number between 300 and 555.
Example: sAddr="GM,0,300,0"
In the example, we can see the identification number of the first Goose measurement in the ICD sAddress.
GEN/LGOS node
Therefore, the distribution of these measurements based on their identification number is as follows:
PROTECTION MEASUREMENTS
(0 - 299)
GOOSE MEASUREMENTS
(300 - 555)
ADDITIONAL
PROTECTION MEASUREMENTS
(744 - 948)
ADDITIONAL
PROTECTION MEASUREMENTS
(979 - 1266)
The number of measurements reserved in the unit is 1267.
15.3 COUNTERS
❑ Protection counters
Identification number between 0 and 31.
Example: sAddr="C,0,0;TX1:Active energy out,TX2:Active Energy Out"
In the example, we can see the identification number of the first protection counter in the ICD sAddress.
Additional protection counters: Identification number between 150 and 192.
GEN and PROT node
❑ Counters resulting from logics
Identification number between 32 and 149.
Example: sAddr="LC,0,32;TX1:Logic counter 1,TX2:Logic counter 1"
In the example, we can see the identification number of the first logic counter in the ICD sAddress.
CTRL/AutGGIO1 node
Therefore, the distribution of these counters based on their identification number is as follows:
PROTECTION COUNTERS
(0 - 31)
ADDITIONAL
PROTECTION COUNTERS
(150 - 192)
16. LOGICS
This document explains the operating mode of the logics generation tool of logic devices.
The EF family’s logics are fragments of executable code generated by the user using a PC tool, both in text and graphic formats. These
logics can be defined in an IED’s data model (using iedFactory) or in a particular instance (using substationFactory or the pacFactory
settings tool).
There are two different types of logics: control logics and protection logics.
In this chapter the device logics are defined and an introduction to the configuration options is presented. For more details about the logics
configuration consult the user manual of the software configuration tool (pacFactory / energyFactorySuite).
The logics can be used to customize the behaviour of an IED. For example, automatism can be added or calculations between different
magnitudes can be carried out.
The logics are run in two different tasks, each with different priorities: one for fast logics and one for slow logics.
The running time for the fast logics is 2 milliseconds. The running time for the slow logics is approximately 10 milliseconds, although
given that this is a lower priority task it may occasionally be affected by other higher priority tasks.
Each configured logic must be included in one of these two tasks, in accordance with the manner in which they are to be run – fast
logics or slow logics.
To edit a control logic from substationFactory, the user must select the corresponding IED and click on the editor icon. To edit the
control logic from pacFactory, click on the "Logics" option in the “Configuration” menu or in the side menu.
The logics are defined in program blocks called POU (program organization unit). Two of the languages defined in the IEC-61131-3
standard are offered for the creation of each POU: one textual (ST) and one graphic (FBD).
There are three types of POU, as defined in the IEC-61131-3 standard: PROGRAM, FUNCTION_BLOCK and FUNCTION. The programs are
the senior hierarchy POUs, with each one corresponding to a task to be run on the device. Each PROGRAM can refer to several
FUNCTION_BLOCK and FUNCTION. In turn, a FUNCTION_BLOCK can refer to one or more FUNCTION.
At the IED level, two PROGRAM corresponding to the two above tasks are automatically defined: one for the fast logics (FastLog) and
the other for the slow logics (SlowLog). These PROGRAM cannot be deleted nor can their names be modified. New PROGRAM cannot
be created at any level, either.
All the new signals, measurements and counters that are created in the data model must be assigned a number that appears in the
sAddress of each of these elements.
The various protection functions can be configured by means of settings associated to the unit’s internal signals, vg enablings or blocks.
The protection functions treat these signals as inputs, although they do not modify their value. In order to assign them a value, the
protection logics are used.
The protection logics have two main differences in relation to the control logics:
❑ The result of a protection logic is always a Boolean value, to be assigned in one of the protection function's settings.
❑ The protection logic editor has been simplified to facilitate the programming of this type of logic.
The number of available logics is defined by the unit’s data model.
Each logic signal has a value obtained from an associated logic. These logics are fragments of code created in one of the two possible
languages - ST (text) or FBD (graphic). The corresponding language must be selected when a logic corresponding to a signal is edited for
the first time.
Each protection logic is independent from the rest and need not be included in a POU in order to be run. When a protection logic is
saved in the editor, an attempt is made to compile the information. If no error is found, a call to the logic in question is automatically
generated so that the logic is run when a CID (configured IED description) message is sent to the device or sent from pacFactory.
The protection logics are run every 2 milliseconds, as are the fast control logics.
To edit a protection logic from substationFactory, the user must select the corresponding logic signal and click on the editor icon. This
icon has three statuses to indicate the status of the corresponding logic:
The following image shows a detail of the expander with four signals with logic signals of different statuses:
To edit a protection logic from pacFactory, click on the "Protection Logics" option in the “Configuration” menu or in the side menu.
A screen with a list of the available protection logic signals, along with the logic’s status icon and an access button for each logic’s
editor, will be shown.
All of the IED’s database signals, measurements, meters and commands can be accessed as readings from the logics (the data model’s
basic data with valid sAddress). There is a set of data within this database that can be modified from the control logics:
Both the data’s value and its quality can be accessed. If data is modifiable from the logic, the same will apply to the value and the
quality.
The data that can be modified from the logic may be preset in the unit's data model or they can be configured in the engineering
phase.
Only the status of the signal to which the logic in question is associated can be modified from the protection logics.
Output data can maintain its value after the device is powered off and on.
In the logics, user can define variables of type RETAIN, which have the property of remaining with the value that they had before the
power off of the device.
The maximum size allowed for all the logics of each group (protection and control) is 96 bytes. This means that if the variables that we
define with this property are of type BOOL (that is, the type associated to the logical signals) we can define a maximum of 96 RETAIN
variables.
There are global variables belonging to the model that can be used in the logic. For example all the signals like Trips or Starts of
protection functions. In the protection logics, each logic has a variable associated with it that is the output of that logic. That output is
also visible as a signal and can be sent in reports or GOOSES, assign it to a digital output, etc.
Each logic can also have internal variables. Once inside the logic editor, click on the "Show interface editor" option to see and / or add
internal variables to the logic (select the VAR tab).
1.- When a non-recognized text is written in the algorithm, an assistant appears asking if you want to add it as a variable.
2.- Writing directly in the cell (if in tabular mode), as shown in next figure.
An internal variable to the logic can be made permanent selecting the RETAIN option in the Retain column.
The initial value is optional. If it is assigned, it is the value it takes the first time the logic is executed. In the case of the variables not
marked as Retain each time the device is started, the variable is restarted with that value. In the case of Retain variables, it is only
started when the logic has been created or changed. Of course, it is highly recommended to initialize the variables.
When a "Function Block" is used in a logic, it is also considered a variable. If one of the predefined "Function Block" in the editor's right-
hand tab is dragged into the editing window, such as a SR flip-flop (SetReset), an SR1 variable of type SR is added. By activating the
option "Show interface editor" we can see how it is in the list of variables (next figure). In this case, if we want to store the internal
states of this block, we must also select the corresponding RETAIN option.
In the case of the "Function Blocks" with RETAIN option, the size in bytes used depends on the number of internal variables of that
block. In the case of the SR they are 3 bytes.
The example (previous figure) is a simple logic in graphic language to demonstrate how to make permanent the internal state of a SR
flip-flop.
Commands can be issued for controllable elements (elements whose functional constraint is “CO”) that may
belong to different Data classes (detailed in IEC 61850-7-3). Control class model implemented by the IED are:
The device implements the following services defined by IEC 61850 standard:
The structure required to operate the command has the following fields:
❑ CtlVal. Command value. The type will be different, in accordance with element’s the CDC (Common
Data Class).
❑ Origin. It includes information about the origin of the command, divided into two fields:
orCat. Origin category. Indicates the type of origin that issues the command (local, substation,
remote command, etc.)
orIdent. Octect string that allows the identification of the command origin.
❑ CtlNum. It is the sequence number of the command.
❑ T: The timestamp when the command was generated.
❑ Test: It defines whether the control service request is going to be used with test purposes or not.
❑ Check: Delimits the kind of checkup that must be performed to the command before running it.
Because the Ingepac EF device implements edition 2 of the IEC61850 standard but maintains compatibility with the existing
configurations of edition 1, the differences in the data used to track orders are explained below:
In addition to informing of the changes in the status signals of the elements on which the commands are to be run,
the reports also provide information on the changes in the status of the two data associated with the command
process itself: OpOpnOr and OpClsOr.
For opening commands in general, OpClsOr remains in STANDBY, the sequence for OpOpnOr would be STANDBY -
IN PROGRESS - SUCCESSFUL / UNSUCCESSFUL – STANDBY. In the case of a closure command, OpOpnOr would
remain in standby and OpClsOr would continue the complete sequence. If the command’s CtlModel indicates that
the command has normal security, no return information is available from the device and, therefore, the sequence
would be STANDBY - IN PROGRESS – STANDY.
In the second edition of IEC61850 standard, three new data elements are defined in order to follow the command
process: opOk, OpRcvd and tOpOk. These new elements have a new functional constraint, “OR”.
OpRcvd is activated upon the reception of a command and deactivated about 10 milliseconds later.
OpOk is activated at the same time as the command pulse (the pulse that will afterwards be transmitted to a digital
output, for example) and tOpOk shows the timestamp when opOk was activated.
OpOk and OpRcvd may be set as RS signals, editing their sAddr in the CID using the configuration tool. In this way,
their values will be refreshed in the internal database and will be available for internal logics.
In addition to these elements, it is also possible to generate a series of indications, through signals from the
database, to provide complementary information on the return of the orders.
In the logical nodes where it is necessary to have this return information of the controls, the normative class has
been extended defining the following data objects with CDC = "ACT", which in turn includes the optional data
"originSrc".
The configuration for the use of these return signals is done through the configuration tool, through the sAddr field
of the command itself. However, the return signals have an RS type sAddr.
In both configurations, upon completion of an order execution, part 7-2 of the IEC 61850 standard defines the possible
reasons for termination. The following table lists the AddCause values used by the device:
On the other hand, the operating mode of a specific command is defined by the ctlModel configuration parameter
associated with that command, according to the following table:
Table 201 Possible ctlModel
Other configuration parameters that determine the progress of the command are:
❑ PulseConfig. This data structure defines the command’s output pulse type (pulse, duration, pulse
train). The command is not terminated until the last pulse ends.
❑ OperTimeOut. Maximum switching time, after which, failure occurs if the command has not been
successfully executed.
❑ sboTimeout. The time during which the command selection remains activated.
In the following sections, the operation process of a command depending on the ctlModel is described in detail.
If the command’s ctlModel is DIRECT_WITH_NORMAL_SECURITY (1), the process to follow will be as shown in
the following figure:
Figure 196 Direct command process with normal security
Operate
Checkup for
operation
Origin, blocks…
Operate
Response
Upon receiving a request to run a command by an Operate Request, the device analyses the validity of the
request, checking the client’s authorization and any possible blocks, and responds positively or negatively by an
Operate Response to the client. If the response is positive, the command is sent to the device.
If the command’s ctlModel is SBO_WITH_NORMAL_SECURITY (2), the process is similar, but including a
selection prior to execution:
Figure 197 Command process with select before operate and normal security
Select
Checkup for
selection
Origin,
selection…
Select
Response
Operate
Response
In this case, after receiving a selection request the selection's permission is checked and, when applicable, a
positive response is sent. At that moment a timer starts. This timer will cancel the selection after the sboTimeOut
timeout ends. If an operate request is received before the conclusion of the timeout, the same process as
described for the direct commands with normal security is followed.
If the selection is not accepted, the response will be negative and the process is concluded.
Operate
Checkup for
operation
Origin, blocks…
Operate
Response
Command
Termination
After sending the operate request to the device, the return information of the element on which the command is
executed is expected, so that the device can inform the client throught a Command Termination if the operation
has been successfully executed.
If the device’s return information is received before the conclusion of the operTimeout (the maximum execution
time) and the position requested has been reached, the IED then sends to the client a positive Command
Termination.
If the operTimeout time is exceeded without having received the information from the device, or if it is received but
the position requested has not been reached, the Command Termination will be negative. In this case, the cause
of the failure of the command will be included in the AddCause field.
The ctlModel SBO_WITH_ENHANCED_SECURITY (4) includes, in addition to the enhanced security process of
the commands modelled as DIRECT_WITH_ENHANCED_SECURITY, the SelectWithValue service in order to
select the command before operate. In this way, it is verified that the value sent in the selection process is the
same as the one sent during the execution. The scheme to be followed is:
Figure 199 Command process with select before operate and enhanced security
Operate
Checkup for
operation
Operate Origin, blocks…
Response
Command
Terminationn
Similarly to direct orders with enhanced security, if the order fails, the cause of the failure is reported in the
AddCause field.
The commands sent to the device can be blocked for different reasons in which the execution cannot be allowed.
In part 7-2, of the IEC 61850 standard, the possible reasons for failure of a command are detailed.
The following subsections describe the different blocks implemented by the device.
IMPORTANT NOTE: The order of these sections matches exactly with the order of blocking verification
that the IED follows. So once a block is applied, the command will not prosper and next blocks will not be
checked.
The reason for command failure when this block is generated is "inconsistent parameters" (AddCause = 26).
In the standard IEC 61850, part 7-3, it is defined the possible origins of a command that are affected by
blockages due to the switching hierarchy.
"not-supported": Only accepted in the mode that the order hierarchy is not handled.
"remote-control": corresponds to a remote origin.
"station-control" or "maintenance": corresponds to a console.
"bay-control": corresponds to a console at bay / local level or to the display.
"automatic-bay", "automatic-static" or "automatic-remote". By default, orders sent by
IEC61850 with these origins are allowed, except for the modes that strictly check the local
origin of the order (LRMode, Edition 2 and Exclusive Edition 2).
Under the section "Command blocks by interlocking" it is explained the particular operation
for these origins in H automation architectures.
"process": Commands with this origin are not accepted in any case. The process source is
reserved for changes in the state of control elements that do not come from commands. If
there is a change in a signal associated with a command but the change of state has not
been a consequence of an order, but a spontaneous change, the order orCat will be written
to "PROCESS".
The "Remote/Local Type" setting determines how the device will behave at the moment of blocking the
commands by hierarchy. It is found in the data model as "GEN/LLN0.LRmode" or in the display under
"General configuration: Remote / Local Type". The following values are available:
To interpret the tables in the next sections with edition 1 configurations, it is necessary to consider the first columns
according to the following relation:
❑ Loc = RemCtlBlk
❑ LocSta = Lockey
In any case, for these configurations, as the data model specific to ICD Ed2 is required, any LRMode associated with
Edition 2 is not available.
MltLev is a boolean setting that can be found in the data model in "GEN/LLN0.MltLev", and indicates if more than
one level (Originator) has the switching authority. This setting only applies to Edition2 and ExclusiveEd2 modes.
Loc is a boolean status signal ("GEN/LLN0.Loc.stVal"). It shows the local status, which is unique for the device, so all
the Loc signals show always the same status (the standard defines this signal in several nodes with configured
commands). To be able to modify this state, we have two options:
Sending a command on the RemCtlBlk ("GEN/LLN0.RemCltBlk") element. This way, every Loc signal
will be set to the same value as "GEN/LLN0.RemCltBlk.stVal".
Configuring the LogInLR setting ("GEN/LLN0.LogInLR") to a valid signal reference, so that this signal
status stablishes the value of every Loc. It is important to note that this setting predominates over
sending the command to the RemCtlBlk element explained in the previous point. Therefore, when
this setting is configured the command over the RemCtlBlk element is not allowed.
LocSta is a boolean status signal ("GEN/LLN0.LocSta.stVal"). Its status shows if station or remote origins are
accepted, and as in the case of Loc, it is unique for the device although it may exist in several logical nodes. To
modify the status of LocSta, a command on the controllable LocSta element "GEN/LLN0.LocSta" can be issued. Every
LocSta element in the device will show the same status value.
The operating characteristics of each of the LRmode values are detailed in the following points:
No switching hierarchy blocking on commands is applied. It is the only mode that allows commands
from the "not-supported" origin.
❑ LRMode: Iberdrola
The status of Loc and LocSta signals is taken into account. The following tables show for each
combination whether the order is blocked or allowed, depending on the origin of the order.
Table 204. Command blocks by switching hierarchy for RemCtlBlk on mode "Iberdrola"
Table 205. Command blocks by switching hierarchy for LocSta on mode "Iberdrola"
❑ LRMode: Exclusive
This mode of operation implies that when activating the status of the RemCtlBlk (associated with Loc),
the activation of the value of the LocSta signal is automatically generated. Deactivation is independent.
The status of Loc and LocSta signals is taken into account in this mode.
Because the activation of the RemCtlBlk signal triggers the activation of the LocSta, in the "Exclusive"
LRMode, it is not possible to reach the Loc = 1 and LocSta = 0 state from the table’s origins. It is only
possible to reach this value after a LRMode change or using "automatic" origin, however, the behavior
is exactly the same as for Loc = 1 and LocSta = 1.
Table 207. Command blocks by switching hierarchy for RemCtlBlk on mode "Exclusive"
Table 208. Command blocks by switching hierarchy for LocSta on mode "Exclusive"
❑ LRMode: No HMI
Only the status of the Loc signal is taken into account. The following table shows for each combination
whether the command is blocked or allowed, depending on the origin.
Table 210. Command blocks by switching hierarchy for RemCtlBlk on mode "No HMI"
* The LocSta table has not been included because is not used in this mode. The command blocks
applied will be those of RemCtlBlk.
❑ LRMode: ExclusiveBR
This is a particular case of the "Exclusive" LRMode mode. This LRMode differs in that the LocSta
variable is not activated automatically when the RemCtlBlk is activated and it is possible to modify the
LocSta if the equipment is in local mode (Loc = 1) from the same origin (bay-control).
The following tables show for each combination whether the order is blocked or allowed, depending on
the origin of the order.
Table 212. Command blocks by switching hierarchy for RemCtlBlk on mode "ExclusiveBR"
Table 213. Command blocks by switching hierarchy for LocSta on mode "ExclusiveBR"
❑ LRMode: Edition2
Only for Edition 2 configurations. If LRMode is "Edition2", the normative hierarchies of commands
described in Part 7-4 of Edition 2 of IEC61850 standard (Annex B) apply.
This implies that the local origin of the command is considered strictly, so that if Loc = 1, no command
(nor selection) from IEC61850 communications is accepted regardless of what is indicated in the origin
field (even if it is a bay-level console and commands with 'bay-control' origin). Therefore, when the
equipment is in local mode (Loc = 1) only commands sent from display or logic are accepted.
In this mode, the MltLev setting of the LLN0 of the logical device GEN, as well as the status of Loc and
LocSta signals, is used to determine if a command is required to be blocked by switching hierarchy.
The following table shows for each combination whether the command is blocked or allowed,
depending on the origin. This table affects all orders, including RemCtlBlk and LocSta.
❑ LRMode: ExclusiveEd2
Only for Edition 2 configurations. If the LRMode is set to "ExclusiveEd2", the command switching
hierarchy blocks are the same as in the "Edition2" case, except for the commands over the LocSta and
RemCtlBlk.
When operating a command on these two elements, the verification of the local origin is not strict, that
is, commands received from IEC61850 communications with origin 'bay-control' or 'automatic' sources
are allowed.
The following tables show the behavior of the switching hierarchy blocks on these two orders:
Table 215. Command blocks by switching hierarchy for RemCtlBlk on mode "ExclusiveEd2"
Table 216. Command blocks by switching hierarchy for LocSta on mode "ExclusiveEd2"
For all other commands, the local origin check remains strict, as detailed in the LRMode "Edition2"
mode.
Ingeteam Power Technology S.A.
User Manual 362
IEC 61850 COMMANDS
In protection commands, hierarchy locks are the same as those in control commands, with the exception
of the following commands, that are never blocked by switching hierarchy.
In the LLN0 node of the logical device GEN the FKeysRem setting is defined. When is set to '1', it allows any
order given from the device’s display without any hierarchical blocking.
Additionally, with the configuration tool it is possible to set (in the sAddress), for each command of type SPC
and DPC, if the switching hierarchy blocks shall be avoided. It can be choosen whether this affects the
opening command, the closing command, or both.
When the Beh is Off this block also applies to the selection of the command. As the test bit is not sent in the selection
request, it can not be checked in the other cases. The value Off is only defined in those logical nodes that it makes sense
to disable the node (for example protection functions).
Only with Edition2 configurations, to determine the Beh status of the logical node on which the command is executed,
different levels of hierarchy are defined:
The GrRef setting is defined in the Edition2 of the standard and allows to relate a logical device to depend on a higher
hierarchy logical device. Its data type is objRef and it is found in the LLN0. The format to be used is the own logical
device concatenated to the IEDname of the installation.
The following table details the calculation of Beh of a logical node according to the different levels of hierarchy. The
GrRef can have an empty value and therefore considered unconfigured (NC):
On the other hand, in edition 1 configurations or other protocols different than IEC61850, the block by interlocking is
always checked.
The standard defines that the signals of the CILO logical nodes shall be used, but using the configuration tool it is
allowed to select these or any other signal in a generic way to perform the interlocking block. Signals can be set for both
the opening and closing blocks. The reason for the failure associated with this type of block is the "blocked by
Interlocking" (AddCause = 10).
In addition, within interlocking blocks, there is a check for installations in H automation architectures. This configuration is
performed using the configuration tool (automation signal sAddress field). When this signal is configured, the following
logic is followed:
For this section it is important to take into account the order followed to check the blocks, so that for example, with
LRMode configured to Edition2, and with the IED in local mode, automatic orders will be blocked by switching hierarchy
before reaching this kind of block.
These blocks are configured through the configuration tool (in a sAddress field) indicating the desired operating mode for
each command.
Estado invalido /
Open status Close status
desconocido
Open Close Open Close Open Close
Command Mode 0 / -1 ALLOWED ALLOWED ALLOWED ALLOWED ALLOWED ALLOWED
Command Mode 1 BLOCK (1) ALLOWED ALLOWED BLOCK (1) BLOCK (2) BLOCK (2)
Command Mode 2 BLOCK (1) ALLOWED ALLOWED BLOCK (1) ALLOWED BLOCK (2)
Command Mode 3 ALLOWED ALLOWED ALLOWED BLOCK (1) ALLOWED BLOCK (2)
Thus, the blocks marked with (1) are blocks by "position reached" (AddCause = 5) and those marked with (2) are by
"invalid position" (AddCause = 4).
The configuration of these commands is related to the protocol by which they are propagated.
When the command is configured as a command of another device or UCL, the order will be sent to the corresponding
device behaving as a direct order with normal security (ctlModel = 1). The check of return information, pulseConfig, timeouts
and blocks must be performed on the device to which the order belongs.
Through the sAddress fields of each command the behavior explained in some of the previous sections can be modified.
The method for modifying the sAddress fields must always be the configuration tool. Manually changing these values can
cause errors and malfunction of the associated command.
❑ a:= O (letter corresponding to the command) / LO (Letters corresponding to the command logics)
❑ b:= Command UCL number. Maximum 4 characters.
Value 0 is used to select internal Ucl.
The table with the explanation of each mode can be found in the corresponding blocks section.
If signal value is '1', H automation is activated, so command requests over this element from any
origin that is not “automatic” will be blocked
If signal value is '0', H automation is not activated, so command requests over this element from any
“automatic” origin will be blocked
❑ j:= UCL number of the enabling off/aperture signal (field d). Maximum 4 characters.
The value 0 is used to refer to internal ucl. If it is empty the ucl number of the command is used.
❑ k:= UCL number of the enabling on/close signal (field e). Maximum 4 characters.
The value 0 is used to refer to internal ucl. If it is empty the ucl number of the command is used.
❑ l:= UCL number of the H automation signal (field i). Maximum 4 characters.
The value 0 is used to refer to internal ucl. If it is empty the ucl number of the command is used.
❑ o:= UCL number of the H automation signal (field i). Maximum 4 characters.
The value 0 is used to refer to internal ucl. If it is empty the ucl number of the command is used.
❑ p: RS signal associated with return of command (only Ed2): opOpnPrg. Maximum 5 characters.
❑ q: RS signal associated with return of command (only Ed2): opClsPrg. Maximum 5 characters.
❑ r: RS signal associated with return of command (only Ed2): opOpnFail. Maximum 5 characters.
❑ s: RS signal associated with return of command (only Ed2): opClsFail. Maximum 5 characters.
The UCL associated to the four return signals of commands Ed2 is the UCL of the command itself.
❑ TX1:= Command text language1. Maximum 16 characters.
❑ TX2:= Command text language2. Maximum 16 characters.
18.1 CONFIGURATION
The RIO modules are configured using the RIOGGIO logic nodes A maximum of 8 nodes of this type is contemplated.
Each node has series of attributes that allow us to select the RIO modules with which we are to communicate and to configure the
outputs to be published:
ATTRIBUTE DESCRIPTION
The RIO number to which we want to associate the current node. It is a configurable value
NumRIO.setVal
between 0 and 99.
The RIO module to which we want to associate. It can accept the 1 (12 inputs / 4 outputs) or 2
TypeRIO.setVal
(8 inputs / 2 outputs). The value 0 is reserved to indicate that the node is not configured.
ATTRIBUTE DESCRIPTION
The RIO number to which we want to associate the current node. It is a configurable value
NumRIO.setVal
between 0 and 99.
The RIO module to which we want to associate. It can accept the 1 (12 inputs / 4 outputs) or 2
TypeRIO.setVal
(8 inputs / 2 outputs). The value 0 is reserved to indicate that the node is not configured.
18.2 OPERATION
When we have configured a RIOGGIO logical node correctly, the expected performance in the different attributes is as follows:
ATTRIBUTE DESCRIPTION
Status of the communication with the associated RIO module. The value 1 indicates that it is
St.stVal
correct.
Indicates that the configured RIO type does not match that which is being received. This value
CfgErr.stVal
is only displayed in IEC 61850, it has no associated signal in the internal data base.
The values sent to the RIO module. The value always coincides with the signals configured in
SPSCO[1..4].stVal
the InRefs in the same index.
Both the elements received and the communication status has associated signals with fixed position in the internal database. The
signals are distributed as follows:
For standard IEC61850 Ed1 configurations only, after a change on LGOS logical node subscription settings, the server does not require a
reset only if the LGOS was completely configured when the server started. In other case, the change of any of the settings will activate the
reset required signal.
The following table details the possible causes to activate this signal:
Table 224 Setting changes that require the manual reset of the device
For the details of the IEC 61850 interface implementation consult the following documents for the Ingepac EF family:
❑ PICS: Protocol Implementation Conformance Statement for the IEC 61850 interface
❑ PIXIT: Protocol Implementation eXtra Information for Testing for the IEC 61850 interface
❑ TICS: Technical Issues Implementation Conformance Statement
The Ingepac EF family maintains compatibility with the existing ICDs developed following Edition 1. The last point of this section
describes the GOOSEs subscription for that case. The remaining points refer to functionalities associated with Edition 2
configurations.
According to IEC 61850 Edition 2 the GOOSE subscription is configured using the Inputs-ExtRef elements in the CID file.
The Inputs section defines all external signals that will be received via GOOSE messages from other IEDs. In this section,
each ExtRef element references to one external item and the intAddr element makes the binding of the external signal to an
IED internal configured data.
The CID file of an IED with configured GOOSE subscriptions contains several IED sections. The IED section of the server device itself and
IED sections from each of the IEDs sending GOOSE messages to which the device is subscribed.
These external IED sections only contain the data model needed for the subscription to reduce the size of the CID file.
LGOS logical node is used to monitor GOOSE subscriptions. There are 32 instances of LGOS logical node, which allow
monitoring up to 32 GOOSE subscriptions.
The only configuration value in the LGOS logical node is the GoCBRef (Reference to the subscribed GOOSE control block).
❑ NdsCom: Subscription needs commissioning. When true, the received GOOSE message does not conform the current
subscription configuration; either the dataSetRef is wrong, the data set members, the configuration revision number, ...
❑ St:If true, the GOOSE subscription is active, other is inactive
❑ SimSt: If true, subscribed GOOSE messages with the simulation bit set are being received and accepted
❑ LastStNum: Last state number received
❑ ConfRevNum: Expected configuration revision number of the GOOSE messages
❑ RxConfRevNum: Configuration revision number of the received GOOSE messages
The St and SimSt data are mapped to the internal database to be used in for example logics or local display. The other
values are only available through the IEC 61850 communication.
The factory CID file contains 2 logical nodes (GOOGGIO1 and GOOGGIO2) with available data for the internal binding of
the received values.
In models with the "Extended control" option the IED data model can be extended with more logical nodes in the control
logical device for internal binding of the data received in GOOSE messages.
Extension capacity:
❑ Signals: Up to a total of 1024 internal signals (including the 2 GOOGGIO nodes) and taking into account that the dbpos
signals occupy 4 internal signals.
❑ Measures: Up to a total of 256 measures (float values).
As established in Edition 2 of the standard, it is possible to subscribe to both data attributes and data objects. The recommendation
following criteria of efficiency and response time is to use data attributes in GOOSE messages. In any case, the device supports the
subscription to data objects of the following CDCs:
For more information about the GOOSE subscription configuration process consult the software tool manual
(energyFactorySuite/pacFactory).
The device implements the GOOSE simulation mode defined in the IEC 61850 Edition 2.
This mode allows the simulation of any GOOSE that is present in the communication network so that two GOOSES with the same
information data will be present at the same moment, the real one without the simulation bit active and the simulated one with the
simulation bit active. If the subscriber is in simulation mode, once it has received the first simulation GOOSE its values will be used
instead of the values of the original GOOSE.
Therefore, if the device is in simulation mode, it still accepts 'original' GOOSE messages, and only discards the 'original' GOOSE
messages for those GOOSEs which are simulated.
Simulation mode is enabled with the controllable data "Sim" included in the LPHD logical node in the GEN logical device.
In each LGOS logical node, used to monitor GOOSE subscription, the SimSt status shows with TRUE value that subscribed GOOSE
messages with the simulation bit set are being received and accepted.
When the subscriber is not in simulation mode (GEN/LPHD.Sim.stVal=false) the simulated GOOSEs are ignored. The device keep on
using the "real" GOOSE messages.
When the subscriber is in simulation mode (GEN/LPHD.Sim.stVal=true) the simulated GOOSEs are used for operational purposes. The
device ignore the "real" GOOSE messages after a first simulated one has been received. The corresponding LGOS.SimSt is set when the
first simulated message is received and only cleared when LPHD.Sim.stVal is set to false.
Once the device has received a simulated message for one of the subscribed GOOSE messages, it will not process the real one until the
simulation mode of the device (LPHD.Sim.stVal) is set to false.
The following state machine, from IEC 61850 TISSUES data base (num. 1151), displays the different states and illustrates the
supervision of GOOSE subscription with regards to LGOS.St and LGOS.SimSt
stm LGOS
[LPHD.Sim.stVal==FALSE]
Initial
LPHD.Sim.stVal
== TRUE
[y] [n]
subscription normal
goose as long as no
[LPHD.Sim.stVal == TRUE] subscribtion normal [normal GOOSE message received] w ait for normal GOOSE
w ait for normal or [TAL expired] simulated GOOSE
goose
simulated GOOSE receiv ed
[LPHD.Sim.stVal == FALSE] [TAL expired] SimSt.stVal = FALSE
SimSt.stVal = FALSE St.stVal = FALSE
SimSt.stVal = FALSE SimSt.stVal = FALSE
St.stVal = TRUE
St.stVal = FALSE [normal GOOSE received] St.stVal = TRUE
[LPHD.Sim.stVal==FALSE]
[simulated GOOSE received] [LPHD.Sim.stVal == FALSE]
It is possible to enable a GOOSE transmission simulation mode with the "TestEna" and "LogInTest" setpoints, included in GEN\LPHD
logical node:
❑ TestEna: If this setpoint is TRUE enables the GOOSE transmission simulation mode
❑ LogInTest: This setpoint allows to configure a signal which, when active, enables the GOOSE transmission simulation mode
In this mode all the GOOSEs transmitted by the device have the simulation field with TRUE value and the mode is indicated in the status
data GEN\LPHD.TestSt.
❑ TestEna=FALSE : TestSt=FALSE
❑ TestEna=TRUE and LogInTest=(not configured) : TestSt=TRUE
❑ TestEna=TRUE and LogInTest=(Signal data with value=TRUE) : TestSt=TRUE
❑ TestEna=TRUE and LogInTest=(Signal data with value=FALSE) : TestSt=FALSE
The device implements the Test mode defined in the IEC 61850 Edition 2.
Switching between the modes (Mod.stVal) only happen as a result of an operator command to the data object Mod.
❑ On:
❑ The application represented by the LN works.
❑ All communication services work and get updated values.
❑ Control commands with test bit will be rejected with AddCause "Blocked-by-mode".
❑ Test:
❑ The application represented by the LN works.
❑ All communication services work and get updated values.
❑ Data objects will be transmitted with quality “test”.
❑ Control commands with test bit will be accepted only by LNs in “test” mode.
❑ Off:
❑ The application represented by the LN doesn’t work.
❑ No process output is possible. No control command should be acknowledged (negative response).
❑ Data objects will be transmitted with quality “invalid”.
❑ Only the data object Mod and Beh should be accessible by the services.
LLN0 of the logical devices that can be configured with a hierarchy contains a setting data named GrRef whose type is
objRef.
In order to configure a hierarchy the format of the GrRef value must be set with the name of the higher level logical device
concatenated to the IEDname of the installation. It is also possible that it is not configured.
GEN is considered the main logical node and its LLN0 logical node does not have the GrRef setting. CTRL and PROT
logical devices can be configured with a hierarchy.
So the typical hierarchy configuration is to assign the GEN logical device as higher level of CTRL and PROT. In this case, the
functions of CTRL and PROT logical devices are considered sub-functions of the GEN logical node and if the mode of
the GEN logical device is modified (GEN/LLN0.Mod) it will affect the CTRL and PROT logical devices also.
The mode of the LNs in any logical device may be changed individually with its own Mod, or globally by means of LLN0 of
each logical device. Only changes in GEN/LLN0.Mod will affect the other logical devices that are configured as lower level
in the hierarchy.
For more details about how hierarchy affects commands behaviour, consult on this manual the "Command Blocks: Commands
blocks by mode (Mod/Beh)" section.
Service tracking is represented by the logical node LTRK and is defined as the function in charge of recording the
parameters values used by any service defined in IEC 61850-7-2 (after a service execution). It is thus possible to read, report
or log these values for system behavior analysis.
The trigger option for these data is "data-update", so it has to be configured in the associated control block if, for example, it is
included in a report.
❑ 16 - SelectActiveSG
❑ 17 - SelectEditSG
❑ 19 - ConfirmEditSGValues
❑ 24 - SetBRCBValues
❑ 26 - SetURCBValues
❑ 34 - SetGoCBValues
❑ 43 - Select
❑ 44 - SelectWithValue
❑ 45 - Cancel
❑ 46 - Operate
❑ 47 - CommandTermination
❑ 54 - InternalChange
❑ 0 - no-error
❑ 1 - instance-not-available
❑ 2 - instance-in-use
❑ 3 - access-violation
❑ 4 - access-not-allowed-in-current-state
❑ 5 - parameter-value-inappropriate
❑ 6 - parameter-value-inconsistent
❑ 7 - class-not-supported
❑ 8 - instance-locked-by-other-client
❑ 9 - control-must-be-selected
❑ 10 - type-conflict
❑ 11 - failed-due-to-communications-constraint
❑ 12 - failed-due-to-server-constraint
The logical node LTRK contains data classes with functional constraint FC=SR needed for track the previously defined services. The
following common attributes are included in all services:
❑ objRef: Reference of the object that is being tracked: either a control block that is being accessed or a control object that is
being controlled.
❑ serviceType: Type of the tracked service.
❑ errorCode: Error associated to the service that is specified by serviceType; value no-error for successful service.
❑ originatorID: Originator of the service. In general, the IP address of the client.
❑ t: TimeStamp of the completion of the service.
❑ d: Description
The following specific data objects are and included in the LTRK logical node:
Each enumerated has its own particular EncTrk, in which the ctlVal matches with the enumerated type defined for the controllable
object.
The index at the end may be incremented (For example EncTrk2) to define different instances.
The IED generates a tracking register when a SetURCBValues is done over the following attributes: rptID, rptEna, datSet, optFlds,
bufTm, trgOps, intPd and resv, what is according to IEC 61850-7-2 Subclause 15.3.2.3.1.
The change of other attributes associated to a URCB like confRev, gi, etc. will not generate a tracking register.
The attributes RptEna and Resv of the URCB instances are tracked at loss of association with the Client, with ServiceType =
InternalChange, with “127.0.0.1” as content of the originatorID field.
Associated services:
▪ SetURCBValues
The IED generates a tracking register when a SetBRCBValues is done over the following attributes: rptID, rptEna, datSet, optFlds,
bufTm, trgOps, intPd, purgeBuf, entryID, and resvTms, what is according to IEC 61850-7-2 Subclause 15.3.2.2.1.
The setting of other attributes associated to a BRCB like confRev, gi, etc. will not generate a tracking register.
The attributes RptEna and ResvTms of the control block are tracked at loss of association with the Client with ServiceType =
InternalChange, with “127.0.0.1” as content of the originatorID field.
▪ SetGoCBValues
It allows to establish individually the values of some data that are sent through the protocol IEC61850.
Usually, input from the process or the result of the calculation from a function provides the value of a data (in that case, the
source is called "process"). In case of substitution model, the value of the data may be provided by an operator making use
of an IEC 61850 client.
Data classes that allow substitution have an attribute "subEna". If it is set to TRUE, the value of the data used for the IEC
61850 communications is the value configured in the following attribute (depending on the data type):
❑ Value:
❑ subVal: SPS, DPS, INS, SPC, DPC
❑ subMag: MV
❑ subCVal: CMV
❑ Quality: The attribute "subQ" is the value used to substitute the data attribute q. When subEna is true, the source quality
bit substituted is always set.
On measurement data substitution, the value is checked against the configuration of the measure (max, min, db …) so the
substituted value is affected by such configuration.
It is the responsibility of the client application, in particular in the case of multiple attributes to be substituted, to set the
relevant substitution values before enabling substitution, as well as, disable substitution on all substituted values.
The substituted values only apply to the IEC 61850 communication values. These means that the substituted values are not
used in the logics or protection functions of the device.
There are several data with a special behavior for which the substitution of the value affects to the behaviour of the
IEC61850 server:
The IED implements the IEC61850 MMS file services. Following the Edition 2 of the IEC61850 standard, the structure of files and
directories is based on a FLAT FILESYSTEM with pseudofolders. This means that it is not accessed through folders, it is only allowed to
read the root directory where all the existing files in the different subfolders are shown concatenating the path to the file name.
The available permissions are the same as those of the user 'ftpuser', and only writing the pseudofolder /SCL/notvalidated/ is allowed.
This behavior is used from firmware version 6.0.17.0 for both Edition 1 and Edition 2 configurations. In firmware versions prior to this
(only Edition 1 configurations were supported) the file and directory structure is based on folders, being able to access and read each
one separately.
Only for ICD configured as Ed1: This model makes it possible to configure and supervise the complete status of each reception goose
within a single logical node.
Each goose subscription is associated with one LGOS logical node wich contains the configuration for that subscription, so there can be
as many subscriptions as LGOS logical nodes in the data model. The factory CID file contains up to 32 LGOS logical nodes that allow the
subcription to up to 32 goose messages.
To use the received data in the goose message they must be mapped to LGOS data. Each LGOS has:
ATTRIBUTE DESCRIPTION
The reference to the signal in which the goose element established by the InRef index is
InRef[..].intAddr
received. It must be a mapped signal within the goose signals range.
These values, apart from the “intAddr” for the internal data assignement, must be the same ones received in the Goose message.
The data mapping is configured with the InRef data (InRef1 to InRef34). The InRef index indicates the reception goose data position
associated with that InRef (InRef1 associated to first goose data, InRef2 associated to second goose data, etc.)
In the InRefx.intAddr attibute must be configured the LGOS data in which the value will be copied. The value must be:
To configure this assignment the user must know the format of the data of the Goose message because the selected data in the
LGOS node to copy the received value must have the same format.
Each LGOS logical node in the the factory CID data model has 34 InRef data so the device can subscribe to Gooses with up to 34
elements.
For example if the configured value is InRef3.intAddr = Ind2.stVal this means that the third value in the received goose (that must
be a boolean value) will be copied to the LGOSx.Ind2.stVal data.
The software tool allows configuring these goose subscritpions manually or automatically (for more information consult the
pacFactory software tool manual).
ATTRIBUTE DESCRIPTION
St.stVal Subscription status. Value “1” indicates that the subscription was successful.
NdsCom.stVal Activated when the subscription has the “Needs Commissioning” flag activated.
Note: Only the St data is mapped to the internal database to be used in for example logics or local display. The other values are
only available through the IEC 61850 communication.
21.1 DESCRIPTION
In the device has a front Ethernet interface and may have up to two rear Ethernet interfaces. Each of which can be configured to
belong to the network that the user wants, as seen in the figure below:
The rear ethernets can be selected from one of the following options (see commercial code):
❑ Independent port
❑ Redundancy module configurable between PRP, HSR and Switch mode
❑ Link failover redundancy (both ethernet ports used)
The device has signals to indicate the link status of each of the ethernet ports in the LPHD1 node of the logical device GEN:
Redundant Link indications are only used in the case of redundant communications. In non-redundant communications, the link
indications are shown in the Eth1ALink and Eth2ALink data.
In the link failover redundancy the link indications are shown in the Eth1ALink and Eth1BLink data.
The device has several options of physical communications redundancy divided into two hardware solutions:
When the device has the PRP/HSR/Switch mode module, the user can configure any of the three options or consult the configured
option from the local display (Initial menu - Communications - Configuration PRP / HSR / Sw) or from the web server of the device
(Maintenance menu - Communications - IP network configuration).
In the PRP protocol the device use two redundant ethernet ports and the protocol is based on the simultaneous transmission and
reception of data via both independent ports.
In PRP solutions two independent ethernet networks are used. Each device is attached to both networks and sends and receives all
the frames over both LANs simultaneously, consumes the first frame and discards the duplicate. With this mechanism PRP ensures
zero-packet loss and zero recovery time upon single network failures.
The two LANs have no connection between them and are assumed to be fail-independent, both are identical in protocol at the
MAC-LLC level, but they can differ in performance and topology.
With the PRP protocol additional information called RCT (Redundancy Control Trailer) is added to the Ethernet frame at the link
layer in order to control redundancy. This information is transparent for devices that do not use PRP protocol and it is used by PRP
devices to discard the duplicate frames.
Devices without PRP can be connected to one of the redundant ethernet networks but in that case they only can communicate with
the devices connected to the same network. In order to enable redundancy in non-PRP devices an external converter called RedBox
(Redundancy Box) can be used.
In the HSR protocol the device use two redundant ethernet ports and the protocol is based on the simultaneous transmission and
reception of data via both independent ports.
In the HSR networks no external switches are used, instead each device has two ring ports, and all the devices are connected in a
ring topology, with one port of the device connected to the previous device and the other connected to the following device.
For each frame to send, the device sends it duplicated over both ports. So one frame travels in the ring in the clockwise direction
and the other frame travels in counter-clockwise direction. Each direction is treated as a separate network. So if there is a failure in
one point of the network, the frames reach the destination using the other direction in the ring. With this mechanism HSR ensures
zero-packet loss and zero recovery time upon single network failure.
An HSR tag is placed at the beginning of each frame to allow early identification of frames. With this tag each device can identify
the HSR tagged traffic and reject the duplicated frames coming from the both ports of a device and the frames circulating in the
ring. When a device receives a frame directed to it or that it sent, the frame is discarded and it is not forwarded again in the ring.
The frame is also discarded if it is a frame that it already sent in the same direction (i.e. multicast frames).
Devices within the ring are restricted to be HSR-capable IEDs. In order to enable redundancy in non-HSR devices an external
converter called RedBox (Redundancy Box) can be used.
The recommended network topology would be a cascade or Daisy-chain connection without closing a communication ring because
the IED integrated switch does not implement the RSTP protocol.
In this redundancy mode the device communicates by one of the ethernet ports and if there is a link failure in that port, switches to
the redundant port if the link status of that port is active.
If the link status of the passive port returns to normal, the communication is maintained in the active port and the devices only
change the active port in case of link failure.
In this redundancy, unlike the case of PRP redundancy, it should not be used two independent ethernet networks. The two
Ethernet ports of the equipment must be connected to different network switches, but must belong to the same network, so that
the switches should be connected at some point in the network.
This switching is almost instantaneous, allowing even Gooses redundancy without loss or minimal loss (1 repetition). Regarding
communications with IEC 61850 clients, depending on the ring reconfiguration time communications, we even could not lose the
connection or the open session.
The device has link failover redundancy status signals in the logical node LPHD1 of the GEN logic device, to indicate which of the
two channels is active and to indicate possible failures in the redundancy.
When configuring the network of the device it must be taken into account the following considerations:
❑ From version 5.25.16.1 of firmware it is possible to configure several IP addresses in the same ethernet interface. For
previous versions it is not allowed.
❑ Gateways configuration:
There can be only one default Gateway in the devices and it will be associated to a specific Ethernet interface.
If a Gateway is configurec, the static routes for the ethernet traffic will be determined by up to 10 groups or three
parameters:
IP address of the network or destination host. This IP address indicates the network or the device you want
to connect to.
Network mask or destination host mask.
Gateway IP address. It must be in the same net segment than the IP address configured in that ethernet
port; because in another way the device will not access to the gateway.
If the IP address of the network or destination host or the mask of the network or destination host are not configured,
the default values are:
IP address: 0.0.0.0, it will be all the networks or default gateway.
Network Mask: 255.255.255.255, it will be all networks or default gateway.
The configuration of gateways can only be done from the Display.
When changing the IP address, the gateways that are no longer accessible by the new IP will be removed
permanently.
The IP change command keeps the mask that was associated with that Ethernet interface.
Do not configure two different Ethernet interfaces within the same network segment. When you configure
two interfaces within the same network segment, the device will use only one of them.
21.4 GOOSES
GOOSE messages (IEC 61850 peer-to-peer communications) are not on the TCP/IP layer, they are Ethernet packets and are configured
at the MAC level.
The devices subscribes to multicast MAC addresses for receiving messages and transmit to a specific Multicast MAC address.
21.5 FIREWALL
From firmware version 5.25.16.1 the device incorporates a firewall functionality through which any port in TCP/IP communications (eg
PING, FTP, sFTP, HTTP, etc.) can be blocked.
The firewall function can be enabled or disabled independently for each of the network interfaces. In case of link failover redundancy
interfaces, only the ETH1 interface shall be configured for both rear Ethernets.
Each TCP or UDP port can be configured as "closed" or "opened". When the firewall function is enabled on a network interface by
default all TCP ports are closed and those that want to be left opened must be configured. And in the case of configuring a port as open
the IP addresses from which the port will be accessible can be configured or leave it open for any IP address.
Configuration is done from the pacFactory / energyFactorySuite software tool. Refer to the user manual of the tool for more details on
the configuration.
Direct connection (without a telecommunications network) between the ends can be achieved via RS-232, RS-485, multi-mode optical
fibre or single-mode optical fibre. The conditions of possible noise and interference and the distances supported are limitations which
incline towards choosing Optical Fibre.
This type of connection always involves joining the transmission channel (Tx) of one end to the reception end (Rx) of the other.
Ingepac EF devices must have the correct interfaces to permit this type of connection. The options are contained in the commercial
code (see section "Model Encoding").
Maximum
Cable Type Permitted attenuation Wavelength Connector
distance
Multi-mode glass optical fibre:
62.5/125 µm 11db 2km 820nm ST
50 /125 µm 9dB
Multi-mode optical fibre:
V-Pin connector
200Μm HCS (silicone) 22dB 1.9 km 660nm
(HP standard)
1Mm plastic 24.7db 115 m
It is highly recommended that you use attenuators if you are going to connect single-mode optical fibre cables shorter than the
length indicated as the minimum distance. Attenuators should be placed at the transmitter output (connector Tx).
Connections via a telecommunications network are made using communications devices which permit the connection of Ingepac EF
devices to the network, establishing a virtual link between them. These devices are called multiplexers (MUX) or Pulse Code
Multiplexers (PCM). They use standard protocols such as:
The port used with this communication must be configured with 38400 baud, even parity and 1 stop bit.
In the second case, information will be needed to adapt the optocoupler device. The section gives a practical example of using
external converter devices.
The characteristics of multi-mode optical fibre for this connection are as follows:
Permitted Maximum
Cable type Wavelength Connector
attenuation distance
Multi-mode glass optical fibre:
62.5/125 µm 13db 2km 850nm ST
50/125 µm 9dB
This section describes how to connect an Ingepac EF device to a multiplexer using an external C37.94 to G.703 converter. This
optocouplers or converter devices can be used to connect to MUX for access to SDH and PDH networks.
The G.703 standard has different interfaces: E0 (64Kbs), E1 (2Mb), etc. Hence, there are different C37.94 to G703 converters for
converting to E0, to non-structured E1, to structured E1, etc.
As a general rule, connect the Tx transmission line of the Ingepac EF-LD device to the Rx reception line of the device and vice versa.
In 21-219 devices, you can use two C37.94 channels, but in this example, we will limit ourselves to using Channel 0.
In this device, the part of the G.703 E1 2Mb interface consists of two BNC 75 Ohm connectors for connection to the MUXs. If two
21-219 converters are to be connected to each other, output Tx of one must go to input Rx of the other and vice versa.
There are different alternatives for defining the master clock used in the G.703 standard:
In terms of the 21-219 converters, the external clock source must be configured for synchronisation in both devices. To do
this, there is a rotational switch on the front of the 21-219 which allows you to select the clock source, amongst other
items. In this case, the switch must be set to “0”, which is the default configuration.
To achieve this, the internal clock source in only one of the 21-219 devices must be configured so that there is only one
master clock. In this case, the rotational switch must be set to position “1”.
The other 21-219 devices must be configured with the external clock option as indicated in the previous section.
Also, this option must be applied when the network does not provide such a precise clock (e.g. PDH networks) and the
multiplexers are configured so that they do not interfere with synchronisation (functioning in transparent mode).
There are also menu pages (which include the protection, control and general settings, such as the date and time, password, FW
versions, etc.), which are treated differently to those mentioned above.
By clicking on the “ (Up), (Down)” keys in any screen, the screens belonging to the same type are shown. The I/O, SOE, and fault
pages are presented in a preconfigured order. However, in the graphic and alarm screens the presentation order is defined using an
external tool.
If, when in any screen belonging to specific type, we press “(Left), →(Right)”, the following screen type is displayed whilst the
screen position remains within the type in question. Thus, when scrolling through the screen types the last screen types selected
when exiting a specific type are shown.
If no keys are pressed within a period greater than 5 minutes, the unit returns to the start page and the first page of each type is
selected.
By pressing on <ESC> from any screen we return to the start page, whilst the current page of each screen type is maintained.
There is a special screen type called “Menu to Other Screens” that contains an index of screens not considered important enough
to have been defined as main screens and which enables access to the same. This screen is configurable via a PC tool.
By pressing <MENU> from within any screen, the first page of the settings menus is displayed.
If the unit is fitted with an IP protection cover, only certain buttons will be accessible from the front, depending on the model in
question:
The INF button allows the different screens to be displayed in a circular mode, whilst the order is configurable via a PC tool.
The DOT button allows the different screens to be displayed in a circular mode, whilst the order is configurable via a PC tool.
The possible values of the status signal associated to the functional key and its corresponding representation via the LEDs are:
This mode will be applied for both the graphical screens commands and the functional key commands (contemplating
that we can be in any of the display screens)
NOTE 1: To change this setting from the display, the settings menu is accessed and in the initial menu select the 'general settings'
menu and press the ENTER key. Within this node, the setting is 'Command Type'. The 'With confitmation' option is selected and the
settings are validated.
NOTE 2: When a function key has not a configured signal but it has a configured command the 2 LEDs remain OFF until the function
key is pressed. At that moment the 2 LEDs start blinking.
Use the “ (Up), (Down)” keys to switch from one group of graphic screens to another.
The order of the “live points” that have commands and the sequence of the graphic screens can be modified using the PC tool.
Figure 1 Single Line diagram Figure 2 Single Line diagram with indication of non-run command
❑ To run a command, we must first select the item to be sent. To do so, and once we have selected the screen
containing the item to be sent, we must press “SEL”. The symbol of the item that has been configured to priority 1
and which has an associated command will appear and begin to flash.
❑ By pressing “SEL” we scroll through the different “live points” with commands, in accordance with the preset
order.
❑ Once the item to be sent has been selected, the process is as follows:
Press the key “I” for the following commands: close, in service, automatic, remote control, etc.
Press the key “O” for the following commands: open, out of order, manual, local, etc.
By pressing the key “DES” (if the item has maintenance configured), the command will be run, in accordance
with the item's status – if it is set to maintenance, the command will be “remove maintenance”, if it is not in
maintenance, the command will be “set to maintenance”.
If the command fails or if it can not be run due to a block, a small screen indicating the reason for the failure will be
displayed. This indication appears for 5 seconds, during which no operations can be carried out on the item.
❑ If the command is successful, no additional screen will be shown and the item's status will be refreshed.
❑ If it is in the control selection, only the “SEL”, <ESC> and “I, O, DES” keys are allowed.
The treatment of controls WITHOUT Preset Keys:
❑ To run a command, we must first select the item to be sent. To do so, and once we have selected the screen
containing the item to be sent, we must press (Enter). The symbol of the item that has been configured to
priority 1 and which has an associated command will appear and begin to flash.
❑ By pressing the “(Left), →(Right)” keys, we scroll through the different “live points” with commands, in
accordance with the preset order.
❑ Once the item to be sent has been selected, the process is as follows:
Press the key “I” for the following commands: close, in services, automatic, remote control, etc.
Press the key “O” for the following commands: open, out of order, manual, local, etc.
❑ If the command fails or if it can not be run due to a block, a small screen indicating the reason for the failure will be
displayed. This indication appears for 5 seconds, during which no operations can be carried out on the item.
❑ If the command is successful, no additional screen will be shown and the item's status will be refreshed to show
"normal".
❑ If it is in the control selection, only the <ESC>, (Left), →(Right) and “I, O” keys are allowed.
By pressing <ESC>, we exit the control selection, as we also do if we refrain from pressing any keys for a period of more than “10
sec”.
The measurements are displayed with the number of decimal points and digits preset with the configuration tool. The possible
situations that are covered when viewing a measurement are:
❑ Invalid: An '*' is placed in front of the measurement, there is no associated flashing. E.g.: * 25.3
❑ Outside range: '####' is displayed without flashing when the measurement’s value exceeds the maximum value for
the specified nº of digits and decimal points. E.g.: measurement value = 100 and number of digits = 2.
❑ Alarm: An 'A' is displayed in front of the measurement, with flashing, when the measurement exceeds the set
range. There is an upper and a lower limit. E.g.: If an alarm is activated when the upper limit is greater than 200 A,
the measurement will be displayed as follows: A 202.
Each of the measurements displayed in the graphic screens can be configured so that their values are referred to the primary or the
secondary.
A text indicating the type of card, the address of the module assigned by HW and an indication of the current page number/number
of total pages, which is the same as that of the card, is displayed at the top of the screen.
An indication of a card failure is shown in the lower part of the screen. If the circle is filled, the card is in failure, whereas if it is
empty, the card is functioning correctly (Figure 200).The order of this type of screen is defined by the different card’s addresses –
the card with the lowest address is displayed first and the pages can be scrolled using the “ (Up), (Down)” keys.
The digital I/O data are listed in 2 columns. Each column contains a graphic symbol (a circle), followed by the input or output text
and the corresponding number of terminals:
The digital signals are displayed as an empty circle, when disabled, or a filled circle, when enabled. In the event of an invalid signal,
an empty circle with a cross is displayed to represent a disabled status and a filled circle with an inverted cross is displayed to
represent an enabled status (Figure 201).
Figure 200 I/O Screen Figure 201 I/O Screen with card failure
Each event’s presentation includes the date and time to the millisecond, a 29 character text and a 7 character acronym.
The texts to be displayed, as well as the signals’ identification, are set in attributes of the CID and may be modified using an
external tool.
The screen order is defined chronologically. Their display order goes from the newest to the oldest. Within each screen, the most
recent are shown at the top of the page and the oldest at the bottom.
We can scroll through the pages using the “ (Up), (Down)” keys, going from the last page to the first, and vice-versa. The page
order runs from the first page, which has the most recent events, to the last page, which has the oldest events. The “ (Down)” key
is used to scroll from the first page to the following in increasing order, whereas the “ (Up)” key is used to scroll from the last page
to the previous pages.
The total number of pages and the number of the page currently displayed, as well as the number of events in the display, is shown
in the last row.
Treatment:
When accessing this screen for the first time, the most recent events are displayed. The “ (Down)” and “ (Up)” arrows are used
to scroll through the pages, as indicated above.
If new changes are registered whilst we are viewing the 1st page of this type of screen, the Display is refreshed accordingly and the
older changes are moved downwards.
When viewing any page other than the 1st page if new changes are registered, the Display will not be refreshed and the previous
data is shown. In such a case, a flashing, inverted video “NEW CHANGES” message is shown at the top of the page.
This indication is cleared when the most recent changes are viewed. To do so, we must go to the first screen.
The texts to be displayed are defined in attributes of the CID. Signals are identified as protection events by means of the
corresponding enabling function in the corresponding settings node and by configuring the event masks. They can be modified
using the PC tool.
The screen order is defined chronologically. Their display order goes from the most recent to the oldest. Within each screen, the
most recent are shown at the top of the page and the oldest at the bottom (Figure 203). If the protection event list is empty, a text
indicating that the protection event queue is empty will appear.
We can scroll through the pages using the “ (Up), (Down)” keys, going from the last page to the first, and vice-versa. The page
order runs from the first page, which has the most recent protection events, to the last page, which has the oldest protection
events. The “ (Down)” key is used to scroll from the first page to the following in increasing order, whereas the “ (Up)” key is
used to scroll from the last page to the previous pages.
Only the last 160 protection events are displayed in these pages.
The (Enter) key is used to select the first protection event from the screen being viewed, whilst the “ (Up), (Down)” keys are
used to scroll to the next protection event, with the following treatments:
❑ If, whilst at the bottom of the page, we press “ (Down)”, we are taken to the next page with the first selected
protection event, unless we are already viewing the last page, which case the display will not be changed.
❑ If we are in the protection event selected and we press “ (Up)” key, we are taken to the previous page, although
the last protection event remains activated, unless we are in the first page and in which case the display will remain
unchanged.
Once this protection event has been selected, we can press (Enter) to view the page with the measurements associated to the
protection event. Use the “ (Up), (Down)” keys to switch from one page to another if there is more than one measurements
page per protection event. These pages are browsed in a cyclical manner, going from the first to the last, and vice-versa, as
corresponds.
Use <ESC> to exit the screen displaying the measurements associated to the protection event. Within the protection events’
screen, the change is deselected by clicking on <ESC> once again.
The total number of pages and the number of the page is currently displayed, as well as the number of protection events in the
display’s queue, is shown in the last row.
Treatment:
When accessing this screen for the first time, the most recent protection events are displayed.
The “ (Down)” and “ (Up)” arrows are used to scroll through the pages, as indicated above
If the appearance of new protection events is detected, a flashing, inverted video “NEW INC” (new protection event) message is
shown at the top of the page.
This indication is cleared when the latest protection events are viewed. To do so, no protection events must be selected and we
must go to the first screen. Once we have arrived at this screen, if we scroll back the first screen with the most recent protection
events to have been registered will be displayed.
2 lines of 12 characters can be displayed within each rectangle. Each alarm’s texts, identification and the number of alarms are
configured using an external tool.
When in standby status, the text is displayed in a normal video with white background and, when enabled, in an inverted video
with a dark background.
When the alarm changes status, the signal’s text begins to flash and appears and disappears within the new status.
If the signal is invalid, the text will be displayed with a cross covering the entire rectangle. If the signal does not exist, the
corresponding alarm's gap will be displayed.
Individual acknowledgements of receipt are not issued for the alarms. Instead, it is possible to issue acknowledgement for all the
alarms displayed in the page that is being viewed. To do so, we must press (Enter) in an active alarm page and the following
message will appear in a small screen:
If we then press <ESC>, the message is cleared and no acknowledgment of the alarms is issued. If we press (Enter), the message
disappears and an acknowledgment is issued for all the alarms displayed on the page.
An indication of the total pages and the number of the page displayed will appear at the top of the page.
❑ Screen 1:
Relay date and time.
Frequency value.
Type, module and angle of each of the unit’s 12 transformers.
❑ Screen 2:
Direct, inverse and zero sequences of currents and voltages (module and angle).
Total real, reactive and apparent power.
❑ Screen 3:
Active table number (not available in CDx models).
External power supply battery voltage.
Phase and neutral thermal image value (only for MDx models).
Restricted Earth value (only for MD0, MD2, TDx and LDx models).
Maximeter value for each current and voltage phase (not available in CD0 model).
Device temperature.
Measures reactive power (only for CB model).
NOTE: The CD0 model only has a single screen with the following information:
Device temperature.
❑ Screen 1:
Relay date and time.
Frequency value.
Type, module and angle of each of the unit’s 12 transformers.
❑ Screen 2:
Maximeter value for each current phase of each winding
Maximeter value for each current and voltage in TD0 model
❑ Screen 3:
Active table number (not available in CDx models).
External power supply battery voltage.
Phase and neutral thermal image value (only for MDx models).
Restricted Earth value (only for MD0, MD2, TDx and LDx models).
Maximeter value for each current and voltage phase (not available in CD0 model).
Device temperature.
Measures reactive power (only for CB model).
❑ Measurements screen (4)
Differential measures
Restraint measures
Differential 2º harmonics measures.
Restricted Earth values.
❑ Measurements screen (5)
Direct, inverse and zero sequences of currents (module and angle) of each winding.
Direct, inverse and zero sequences of voltages (module and angle) in TD0 model.
❑ Measurements Screen 1:
Relay date and time.
Frequency value.
Type, module and angle of each of the unit’s 12 transformers.
❑ Measurements screen 2
Direct, inverse and zero sequences of currents and voltages (module and angle).
NOTE: The LD3 model does not have voltages and power.
These screens are divided into two levels. The first level displays a list of the most recent faults, as well as the fault number and the
fault trip date for each case (Figure 209). The total number of pages and the number of the page being displayed is shown at the
top, whilst the number of faults stored in the unit is shown in the last row.
If the fault list is empty, a text indicating that the fault queue is empty will appear (Figure 208).
The faults are ordered from the most recent or latest (Fault nº 1) to the oldest.
The second level displays all the information related to the fault, organized in several pages. The page is displayed with the number
of the fault being displayed, as well as an indication of the number of the current page and the total number of pages per fault.
Use the “ (Up), (Down)” keys to navigate through the first level screen. The page scroll is cyclical - when the end of the page is
reached we are taken to the next first level page and we are taken from the first page to the last page and vice-versa in accordance
with the key we press.
By pressing (Enter), we access the second level of the selected fault. Use the “ (Up), (Down)” keys to move between the
second level screens pertaining to a single fault. Use <ESC> to return to the first level page.
The values can refer to the primary or to the secondary. It is allowed to enable / disable the treatment to automatically display the
last fault on the display from the Configuration / Settings section of the display configuration tool.
The contents of each screen may differ depending on the model, then the different possibilities:
Pre-fault and fault. Indicates the values measured before the fault and upon the fault. This screen displays the
following values:
Transformer measurements <Trafos>. It indicates the measurement in the module and the angle of
each transformer.
Restricted Earth value.
❑ Fault screen, with the text “Fault information (II)”.
Pre-fault and fault. Indicates the values measured before the fault and upon the fault. This screen displays the
following values:
Sequences. Indicates the measurements in the module and the angle of the current sequences (I0,
I1 and I2) and the voltage (V0, V1 and V2).
Power. Indicates the measurements of the total real, reactive and apparent powers.
❑ Tripped units screen, displays the picked up and the tripped units.
NOTE: only the first 7 picked up and tripped units are displayed. If the number is greater than 7, a text appears at the bottom of
the screen indicating that there are more picked up units.
Figure 212 2nd level Fault Screens, page 1, page 2 and page 3
NOTE: Certain wiring diagrams have invalid measurements that do not exist. They are represented by “---“.
The content of this screen is set using the external configuration tool. Screens that are included in the main screen list cannot be
included in this menu.
The image below shows the following types of screen grouped in this screen: Events and Faults.
It contains those commands that can be given to the unit without having to enter a Password. The commands will vary in
accordance with the unit’s family.
We can access the menu pages with either viewing or modification permissions.
If we enter the correct password and press (Enter), we will have permission to change settings. The “♦” symbol will appear in
the bottom left of the screen, as will the text “CHANGE SETTINGS”. However, if we press <ESC>, we will only be permitted to
consult the settings. Further more, a text indicating “VIEW SETTINGS” will be shown. The <ESC> key will function even when
some of the password’s numbers have been entered.
For more information, consult the point 4.2 of the Password Management section in this manual.
To move from a menu to a submenu we must select the menu that we want to explore and press (Enter). To return to the
previous menu, we must press <ESC>. The <MENU> key enables us to return to the start menu from any submenu.
The (Up), (Down) keys can be used to change a menu's active line. If all the menu’s options can be displayed on the screen,
only the active line is changed when we change line. On the other hand, if not all of the menu’s options can be displayed on the
screen at the same time and the cursor is situated over the first or the last of the screen's menus, the menu will scroll up or
down, in accordance with the key used.
An indication of the number of the item selected from the total number of items in the menu on the screen currently displayed
is shown in the bottom right of the screen.
In the settings screens when a node does not exist in the cid an '*' before the text is displayed, indicating that the
node is disabled.
The display change active table indicated by the following "(A)" the active table at that time.
Figure 222 Initial Settings Menu
If all the node’s settings can be displayed on the screen, only the selected setting is changed when we change setting. On the
other hand, if not all of the menu’s options can be displayed on the screen at the same time and the cursor is situated over the
first or the last of the screen's settings, the settings will scroll up or down, in accordance with the key used. To return to the
menu screen, we must press <ESC>.
If the node is disabled, it is not allowed to modify settings and the display of the settings would be similar to the one you have
when entering the settings only mode. In the last row the text "DISABLED NODE" is displayed.
Figure 223 Settings change screen Figure 224 Setting Validated Screen
By pressing <ESC> after modifying a setting in the page, a confirmation message indicating that the user is about exit without
saving the settings in the CID appears:
Thus, by pressing (Enter) we exit the screen and all the changes made so far in that menu are cleared. If we press <ESC> when
the message appears, we remain where we were.
By pressing (Enter) after having modified one of the page's settings, another window appears. At this point, the user has 2
options:
❑ Wait until the CID modification process is completed with the new settings. At this point there are 3 possible
situations:
If the modification is carried out successfully, a “Changing the settings OK” text will appear (Figure 224).
If an error occurs during the CID modification process, an “Error in changing settings” text will appear.
If a time out failure occurs whilst saving the modified settings, a “Time out in changing settings " message will
appear.
❑ Press (Enter) and return to the settings change screen without the assurance of having modified the CID.
Using the (Up), (Down) keys, we can move through the different options in a circular manner, that is, when we reach
the last option we are returned to the first option. The selection option is chosen by pressing (Enter). To exit without
selecting, press <ESC>.
The desired value is entered directly. The digits are entered from left to right. For example, to enter the number 2345, we
must successively press 2, 3, 4, 5, (Enter).
The entered value is checked in order to ensure that it meets the maximum, minimum and step restrictions. Should it fail to
meet any of these restrictions, the “INVALID VALUE” text is shown. This text disappears when a number key is pressed.
There are 2 possibilities within this type, depending on the number, decimal or integer format.
Integer: There are some integer type settings whose value is a signal number. In such cases, the “NOT DEFINED” text (Figure
228) indicates that this setting has no associated signal. If we wish to associate a signal, we must enter the desired signal
number with numeric keypad and press (Enter).
Figure 226 Small screen for modifying DECIMAL Figure 227 Small screen for modifying INTEGER Figure 228 Small screen for modifying INTEGER
type setting type setting type setting
2 digits must always be entered for year, month and date. This means that in order to enter “1” we must enter “01”.
If the user enters an incorrect value, the last character entered can be deleted with the “” (Left) key.
Once the correct data have been entered, press (Enter) to check that the values entered are valid. In the event of an
error, an “INCORRECT DATE” text will be shown. If the data are valid, no windows will be shown.
When we press a numeric key within the password screen, each keystroke will be considered part of the password and will be
indicated in the display with “*”. When we have entered between 4 and 8 characters and pressed "Enter", the data entered will
be validated against the unit’s password. If the password entered is incorrect, a warning text will be displayed.
Pressing <ESC> enables us to access the settings menus with viewing only permissions. If we enter the correct password we will
be able to view and modify. <ESC> will function even when certain of the password’s numbers have been entered, i.e., if we
press <ESC> while we are entering the password we will access the menu with viewing only permission.
The user can change the password, providing that he or she knows the former password.
You will be asked to type the password twice before changing it. The password numbers will appear hidden as they are entered
(the “*” will appear for each number entered). Once the first password has been entered, press (Enter) and enter the second
password. Once the second password has been entered, press (Enter) and the password will be changed (providing the two
passwords entered are the same). As with the numbers, they are entered from left to right.
Operation
❑ We must use the (Up), (Down), (Left) and → (Right) keys to navigate around the virtual keyboard,
whilst (Enter) is used to confirm the selected keyboard field.
❑ We must enter the old password and select the "Validate" field before finally pressing (Enter).
❑ We must then enter the new password and select the "Validate" field before finally pressing (Enter).
❑ A small window showing the result of the password modification (OK or the cause of the failure) will be
displayed.
If the user enters an incorrect value, must leave and enter the screen and start again.
In graphic displays when you press the select key command the small screen that will ask the key display, after entering the
correct password will have some time to execute orders. After this time, the execution of orders will not be allowed. The
function keys have the same function.
The key settings menu and commands execution is the same, if you access the settings menu with the correct password will
be able to execute commands from the function keys without re-enter the password.
On the other hand, if you accessed the settings menu but only with permission from view settings, if you want to run a
command from the function keys will have to enter the password, same operation as if they were in a main menu screen.
The device considers the origin of these commands as "Remote" and applies the configured Local / Remote command
hierarchy.
For security reasons this functionality is disabled in the factory configuration and can only be enabled or disabled from the
local HMI of the device. It is not possible to modify the configuration by communications or from the pacFactory
configuration tool.
The function is configured by the setting "pacFactory Commands" ("YES": enabled / "NO": disabled).
If the device has this functionality enabled, the pacFactory configuration tool will detect it at the beginning of the
communication and enable an access to the command window in the "Tools -> Sending commands" menu.
From the display it is possible to view and modify the network parameters of the equipment. For this there are a series Network
configuration menus.
❑ Figure 232 shows that the equipment has a network configuration with the 3 independent and enabled interfaces.
❑ Figure 233 shows that the device has a network configuration of ETH1 and ETH2 in Link Redundancy mode, and ETH1 has
been disabled.
Figure 235 shows how the network interface, IP address, netmask, MAC address, and status link parameters are displayed
on the display, indicating whether the network cable is connected.
Depending on the configuration of the back ethernets the representation of some data of these interfaces varies:
ETH2 link: When a device is configured as a switch or link redundancy in the Network configuration screen on the ETH2
interface line, the text of Switch or Link Redundancy. The network parameters are the same as the ETH1 interface except
the link. For this reason, the ETH2 link status is displayed on the ETH1 screen.
❑ Ips Editing
From the display screen (Figure 235) and having permissions to change settings by pressing the (Enter) key, the screen in
Figure 237 shows the current data and a second row where you can enter the new values. Use the (Up), (Down) keys to
navigate the IP and MASK fields in a circular way, that is, when you reach the last, you return to the first one.
Only the IP and MASK fields can be modified. If you want to change any of these fields, you must activate the special
mode keypad to do this, press the <MENU> key. For more information, consult the point 1.2.1 in this manual.
If the user enters an incorrect value, the last character entered can be deleted with the “” (Left) key.
Once the correct data have been entered, press (Enter) to check that the values entered are valid. In the event of an
error, a small screen displaying the cause of the error will be shown.
❑ Ips Removing
From the ip display screen (Figure 235) you can delete the ip that is being displayed by pressing the (Left) key.
For information on how to enter the numbers, refer to the Functioning of the menus in this manual.
The (Left) key is used to delete the last entered value.
The (Up) and (Down) keys to move between the IP line and the MASK line.
The <ESC> key is used to exit the previous menu.
The (Enter) key is used to apply the change.
Figure 238 Figure 239
The (Up), (Down) and (Left) keys to change the setting value.
The <ESC> key is used to exit the previous menu.
The (Enter) key is used to apply the change.
When an ethernet is disabled, all ips associated with that interface will be deleted. The DISABLED text will appear in the
Network Setup menu. If we access the menu of this interface will be shown the screen of Figure 242, with the ip 0.0.0.0.
If you want to enable again, change the setting to YES and then edit the IP1 to add the desired ip and mask
Figure 242
The following figures show the screens with the different interfaces for the unit’s network and gateways. We can see that a default
gateway with IP address 192.169.183.4 and a gateway with IP address 192.168.183.1 have been configured. The remaining
gateways have not been configured.
❑ Viewing a Gateway
If we select Gateway 2 and press (Enter), the following screen appears (Figure 244) showing the Gateway’s data values
and a legend at the bottom with the different options available to the user.
Figure 243 Network Configuration Figure 244 Gateway display screen Figure 245 Default Gateway edition screen
If we select Gateway 1 and press (Enter), the default gateway screen appears (Figure 245).
To add a new Gateway, select a non-configured gateway, for example Gateway 3, and press (Enter).
This screen shows the values of the Gateway’s 3 fields as non-configured. In such a case, we can only exit or edit (add) the
Gateway. By pressing (Enter) again, the Gateway edition/creation screen will be displayed.
The (Up), (Down) keys are used to move between destination IP address, destination network mask and the Gateway IP
address fields in a circular manner. This is not possible in the default Gateway, which has a single editable field.
If the user enters an incorrect value, the last character entered can be deleted with the “” (Left) key.
If we want to enter the Gateway with the destination IP 10.15.1.6, Gateway mask 255.255.255.255 and Gateway IP address
192.168.182.252, you must activate the special mode keypad to do this, press the <MENU> key. For more
information, consult the point 1.2.1 in this manual.
Once the correct data have been entered, press (Enter) to check that the values entered are valid. In the event of an
error, a small screen displaying the cause of the error will be shown.
The screen will display the new configuration and the new Gateway introduced.
NOTE: If a default Gateway is configured, the last Gateway will ALWAYS be displayed, even if more gateways with a specific
network destination are added.
❑ Deleting a Gateway
If we press the “” (Left) key in the Gateway configuration screen and we have permission to change settings (having
entered the correct password into the password screen), the Gateway that is being displayed will be deleted.
If we then press (Up) the contrast’s intensity will increase, and if we press (Down), the intensity will decrease. To exit this
screen, press (Enter).
Figure 248 USB detected Figure 249 Remove the USB device
Once the treatment has terminated, the following window will appear in the display indicating that we can remove the USB device.
NOTE: If the USB device is not removed within 5 seconds, the small screen will disappear and the display will return to the previous
screen.
Added a new menu of settings in the Password screen to set the USB treatment, this setting can only be changed from the display.
The setting will have 3 possible values:
❑ Product information: commercial computer code and the serial number of the CPU is displayed.
❑ Device versions:
Versions of the CPU and the boards of the device are displayed.
Sampled values firmware version. Only in models with sampled values modules.
Micros expansion boards versions (CPU and HMI).
Logic and CID versions.
❑ Last updates: last 18 updates are shown, for each update there is a record with the following data:
Date and time of the update.
Filename update.
Result of the update.
❑ Last CIDs loaded: The display will show the latest cids loaded from the device boots where the following
information is displayed:
Date and time.
Cid name.
Result validation.
❑ After a new CID give the device a small window indicating that you are validating the CID is displayed. Throughout
the process of validation when any key is pressed, the window disappears and you can access the different
menus display.
❑ Once the validation process resulting CID (CID Validated / CID unvalidated) is indicated in a new window, which will
remain on the display until you press any key or two minutes have elapsed.
Messages received new setting display is visualized between the windows and the window CID validating the result.
The output test screen is in the Setup menu of GGIO cards. It defines the different cards and display equipment shown to modify
the time setting output activation.
Once access to one of the cards all outputs and the corresponding connection is. To activate the desired output is only necessary to
select and press (Enter).
Pressing (Up) or (Down), keys allow to select different outputs. To return to the previous menu, press the '<ESC> key.
Figure 250 Digital Output Test Figure 251 GGIO1 Test Figure 252 Leds Test
To activate the desired LED is only necessary to select and press (Enter) key. Pressing (Up) or (Down), keys allow to select
different led. To return to the previous menu, press the '<ESC> key.
24.1 INTRODUCTION
This document describes the features and capabilities of the Web Application, which is supplied within the firmware and allows to set
up and monitor the target IED.
The Web Application has been built in order to be responsive, HTML5 and CSS3 compliant and as lightweight as possible. It is supported
by the following browsers and versions:
First, the IP address of the IED must be entered into the browser's address bar in order to load the login page, i.e.: http://100.0.0.1.
24.2.1 Login
The login page needs a username and its password to login.
There are two users defined by default: a management user and a read-only user. The main difference between them is that
management user is able to modify parameters while read-only user is not. However, when a user with management permissions
logs in, it is asked whether he would like to login with management permissions or with read-only permissions. The corresponding
user name and passwords are the following by default:
When a management user tries to login, if there is already a management user logged in, the new user will be asked whether to log
in as read-only user or throw away already logged user.
Once the login has been successful the web page starts to load several tabs described below.
24.3 TABS
❑ Reports
❑ Settings
❑ Maintenance
❑ SW/Configuration
❑ Logout
24.3.1 Reports
The following subtabs are displayed in this tab:
❑ Status
❑ Events
24.3.1.1 Status
In the Status tab real-time information about measures and signals is shown. It is possible to read this information periodically or
each time the read button is clicked.
In the Measurements menu, the main measures taken in the secondary are shown.
In the Signals menu, the most important signals regarding IED status, protection units, input and outputs status, etc. are shown.
24.3.1.2 Events
In this tab, the list of events recorded by the IED can be displayed and a compressed file with all the events can be downloaded.
24.3.2 Settings
In this tab, it is possible to read and change the settings of the IED.
The settings are arranged in menus regarding their functionality and they are read from the IED according to these menus. At the
bottom of the page there are three buttons in order to read settings, erase changes and send changes to the IED.
The settings are displayed as tables where the first column is the description of the setting, the second column is its value in the IED
and the last column is its value in the web. The background color of each setting's row changes according to its value. If the value in
the IED and the value in the web do not match the background will turn into yellow. On the other hand, if the value in the web is
not valid the background will turn into red.
In addition, it is possible to change the active table and view the value of each setting for every table.
24.3.3 Maintenance
This tab contains the following tabs:
❑ Communications
❑ Users
24.3.3.1 Communications
The following menus are available:
❑ Synchronization. It is possible to synchronize the IED with the desired date and time.
❑ IP Network configuration. It allows to configure the IED's IP addresses and static routes configuration
❑ IP Network Tools. It is possible to execute a ping command from the IED and view IED's actual IP configuration and
routing tables.
24.3.3.2 Users
In this tab, detailed information about current active sessions logged into the web is shown.
24.3.4 SW/Configuration
The SW/Configuration tab contains the following tabs:
❑ Configuration
24.3.4.1 Configuration
In this tab it is possible to load the configuration file.
24.3.5 Logout
This tab is to end the session in the web.
25.1 INTRODUCTION
The device provides a DNP interface to act as RTU and to communicate with a DNP master (for example a remote control station).
The communication can be selected for a serial line or via Ethernet, using encapsulation by means of the TCP/IP protocol.
❑ Enable protocol:
Yes
No
❑ Slave address: DNP slave address of the device. Value between 0 and 65532.
❑ Master address: DNP master address of the master device. Value between 0 and 65532.
❑ Port Number: This setting enables the selection between the available communication channels:
Disable
COM1
COM2
COM3
COM4
COM5
COM6
Ethernet 1
Ethernet2
❑ Comm speed (bauds): This setting enables the selection of the serial baud rate.
600 baud
1200 baud
2400 baud
4800 baud
9600 baud
19200 baud
38400 baud
57600 baud
❑ Parity: Enables the selection of the parity type to be used in transmission. The recommended default value is 0 (without
parity), as indicated by the DNP protocol.
None
Even
Odd
❑ Number of Stop bits: Enables the selection of the number of stop bits.
1 Bit
2 Bit
❑ Communication control: Enables de selection of the communication control type.
Normal
Fixed + DCD
RTS
RTS+CTS
RTS+CTS+DCD
RS485
❑ Min. respond delay (ms): Waiting time for the activation of the RTS and the transmission of a message after the reception
of a message. Value between 0 and 1000.
❑ CTS max delay (ms): Waiting time for the CTS activation after the RTS activation. Value between 0 and 1000.
❑ Carrier stabilization (ms): Waiting time for the transmission of the message after the CTS detection in order to allow the
carrier stabilization. Value between 0 and 1000.
❑ RTS drop-off time (ms): Waiting time for the RTS deactivation after the message last byte transmission.
❑ ACK delay time(ms): Timeout for Link Confirm. Value between 0 and 1000.
❑ Need time delay (m): Waiting time in minutes that must elapse before the validity of the clock is checked after receiving a
synchronization or start up message. If it is invalid, synchronization is requested to the master. Value between 0 and 10.
❑ Permission to synchronize: Synchronization permission from control centre.
Yes
No
It is used to configure the synchronization source when there are several available.
Bit Value
0 Send all with status
1 Send digitals with status
2 Send measurements with status
3 Send counters with status
4 Send frozen counters with status
Bin. output status default: Indicates whether the reply message to a class 0 data request also includes the object corresponding to the
binary outputs with status.
NO
YES
❑ Analog output status def.: Indicates whether the reply message to a class 0 data request also includes the object
corresponding to the analog outputs with status.
NO
YES
❑ Frozen Counters status def.: Indicates whether the reply message to a class 0 data request also includes the object
corresponding to the frozen counters with status.
NO
SI
❑ Analog input bits default: Indicates the default value for the "Var" field in the analog objects when no variation is
requested.
16 Bits
32 Bits
Short floating point
❑ Normalized: Indicates the analog format.
Secondary.
Normalized.
Primary. (Not operative in the current version, if used, the device configures Normalized)
❑ Counter bits default: Indicates the default value for the "Var" field in the counter objects when no variation is requested.
16 Bits
32 Bits
❑ Enable unsolicited: Enables the use of unsolicited responses with class 1, 2 o 3.
NO
YES
❑ Enable collision avoidance: Enables the collision avoidance detection with DCD method.
NO
YES
❑ Fixed Unsolicited T.out (ms): Fixed waiting time before transmitting an unsolicited response. Value between 0 and 5000.
❑ Variable Unsolicited T.out (ms): Variable waiting time additional to the previous setting of fixed time. The value options
are :
❑ Unsolicited Repeat T.out (s): Waiting time in seconds before a retransmission of an unsolicited response when there is
not a link or application acknowledge to the previous message. Value between 0 and 630 seconds.
❑ Max.number rep. without solic.: Maximum number of retransmission of an unsolicited response. Value between 0 and
65535. Infinite for value 0.
❑ Special operations: Enables the activation of certain operational characteristics.
❑ Change wait time (s): Waiting time for the SOE in the internal queue before processing the events. It is only necessary if
there are data from different IEDs in order to sort them chronologically.
❑ TCP Listen Port: TCP port used as server.
❑ Unsolicited react. delay (s): The waiting time to retry again the maximum number of retries an unsolicited message. Value
between 0 and 3600 seconds. Zero does not apply.
❑ Command selection time (ms): The waiting time to abort the selection command. Value between 100 and 15000
miliseconds. Default 15000.
❑ Max command wait time (ms): The maximum time waiting the protocol to the result of the command before responding
to the master. If expired is indicated “Not supported” Default 0.
❑ Enable T.correct.buf.events: True value performs the correction date all still digital events queues when the first
syncrhronization is received. The device does not answer with digital events since the first synchronization. Default No.
The configuration settings for the first DNP are in the GEN\DNPITCP1 node IEC 61850 data model, as detailed in the following
table:
25.3 TABLES
There are 4 tables to configure the list of digital status (binary inputs), analogs, counters and commands.
❑ DNP signal: DNP analog number. Values between 0 and 1023. Gaps are allowed.
❑ Internal IED: IED of the analog value. Value 0 corresponds to the device itself.
❑ Internal ID: Internal analog number that identifies the element inside the device. Selectable from a list.
❑ Class: Class assigned to the analog value. With value 0 the analog value does not cause events.
Class 0
Class 1
Class 2
Class 3
❑ Dead band: Absolute variation value to cause an event. Values between 0 and 10000. It is applied over the value
stored in 16 bits.
❑ Dec: Number of decimal places for the analog value when the setting “Normalizado” is set to Primary or Secondary.
(Factor of 10 raised to the number of decimal). Values between 0 to 4. At value 0, the value is sent without
modifications.
❑ Limit scale: Full scale used when the setting “Normalizado” takes the Normalized value. It is the value that causes
32767 to be sent in DNP.
❑ The deadband is defined as the value that the analog value must vary to be sent as a event. It is always applied on
the current value of the measure to be sent.
When the analog values are to be sent, the current value is compared to the last sent value and if the difference is greater than
the DeadBand the current value is transmitted. A zero value does not generate any events.
❑ DNP signal: DNP counter number. Values between 0 and 63. Gaps are allowed.
❑ Internal IED: IED of the counter value. Value 0 corresponds to the device itself.
❑ Internal ID: Internal counter number that identifies the element inside the device. Selectable from a list.
❑ Class: Class assigned to the counter. With value 0 the counter value does not cause changes.
Class 0
Class 1
Class 2
Class 3
❑ Dead band: Absolute variation value to cause an event. Values between 0 and 10000.
CLOSE
Latch ON
Latch OFF
Pulse ON
Pulse OFF (deprecated)
❑ Comand type:
All. All types supported.
SBO. Only Selec Before Operate supported.
DO. OnlyDirect operate supported.
Order configuration fields on the device itself:
❑ Internal IED: IED of the command. Value 0 corresponds to the device itself.
❑ Internal ID: Internal counter number that identifies the element inside the device. Selectable from a list. The
internal value is affected by the next field.
❑ ON_OFF: Internal command value. Use to select Internal ID.
ON
OFF
❑ Origin:
Bay Control
Station Control
Remote Control
Automatic Bay
Automatic Station
Automatic Remote
Maintenance
Process
Only one command is accepted in each message, count = 1. The On Time and Off Time fields are not used.
Reports Binary Input Change Events when no specific variation Reports time-tagged Binary Input Change Events when no specific
requested: variation requested:
Never Never
Only time-tagged Binary Input Change With Time
Only non-time-tagged Binary Input Change With Relative Time
Configurable to send both, one or the other (attach explanation) Configurable (attach explanation)
Sends Unsolicited Responses:
Never Sends Static Data in Unsolicited Responses:
Configurable (attach explanation) Never
Only certain objects When Device Restarts
Sometimes (attach explanation) When Status Flags Change
ENABLE/DISABLE UNSOLICITED
Function codes supported
Supports Collision Avoidance: Configurable Collision Avoidance Detection Method: DCD
Default Counter Object/Variation: Counters Roll Over at:
No Counters Reported No Counters Reported
Configurable (attach explanation) Configurable (attach explanation)
Default Object _________ 16 Bits
Default Variation ______ 32 Bits
Point-by-point list attached Other Value _____________
REQUEST RESPONSE
OBJECT
(slave must parse) (master must parse)
Func Codes Qual Codes Func Codes
Obj Var Description Qual Codes (hex)
(dec) (hex) (dec)
30 0 Analog Input - All Variations 1, 22 00,01,06
30 1 32-Bit Analog Input 1 00,01,06 129 00, 01
30 2 16-Bit Analog Input 1 00,01,06 129 00,01
30 3 32-Bit Analog Input without flag 1 00,01,06 129 00, 01
30 4 16-Bit Analog Input without flag 1 00,01,06 129 00, 01
30 5 Analog Input — Single-prec flt-pt with flag 1 00,01,06 129 00, 01
32 0 Analog Change Event - All Variations 1 06,07,08
32 1 32-Bit Analog Change Event without Time 1 06,07,08 129, 130 28
32 2 16-Bit Analog Change Event without Time 1 06,07,08 129, 130 28
Analog Input Event — Single-prec flt-pt without
32 5 1 06,07,08 129,130 28
time
2 07, quantity=1
50 1 Time and Date
1 07, quantity=1 129 07, quantity=1
51 1 Time and Date CTO 129 07, quantity=1
51 2 Unsynchronized Time and Date CTO 129 07, quantity=1
52 2 Time Delay Fine 129 07, quantity=1
60 1 Class 0 Data 1 06
1 06,07,08
60 2 Class 1 Data
20, 21,22 06
1 06,07,08
60 3 Class 2 Data
20, 21, 22 06
1 06,07,08
60 4 Class 3 Data
20, 21, 22 06
1 00, 01 129 00
80 1 Internal Indications
2 00, index=7
No Object 13, 14
No Object 23
26.1 INTRODUCTION
The device provides an IEC 60870-5-103 interface to act as RTU and to communicate with a IEC 60870-5-103 master (for example a
remote control station).
❑ Enable protocol:
Yes
No
❑ Slave address: Slave address of the device. Value between 1 and 254.
❑ Port Number: This setting enables the selection between the available communication channels:
COM1
COM2
COM3
COM4
COM5
COM6
❑ Comm speed (bauds): This setting enables the selection of the serial baud rate.
600 baud
1200 baud
2400 baud
4800 baud
9600 baud
19200 baud
38400 baud
57600 baud
❑ Parity: Enables the selection of the parity type to be used in transmission.
None
Even
Odd
❑ Number of Stop bits: Enables the selection of the number of stop bits.
1 Bit
2 Bit
❑ Communication control: Enables de selection of the communication control type.
Normal
Fixed + DCD
RTS
RTS+CTS
RTS+CTS+DCD
RS485
❑ Min. respond delay (ms): Waiting time for the activation of the RTS and the transmission of a message after the reception
of a message. Value between 0 and 1000.
❑ CTS max delay (ms): Waiting time for the CTS activation after the RTS activation. Value between 0 and 1000.
❑ Carrier stabilization (ms): Waiting time for the transmission of the message after the CTS detection in order to allow the
carrier stabilization. Value between 0 and 1000.
❑ RTS drop-off time (ms): Waiting time for the RTS deactivation after the message last byte transmission.
❑ Permission to synchronize: Synchronization permission from control centre.
Yes
No
It is used to select the synchronization source when there are several available.
❑ Communication fail T.(min): Waiting time in minutes without receiving any valid measure before indicate communication
failure. Value between 0 and 10000.
❑ Change wait time (s): Waiting time for the SOE in the internal queue before processing the events. It is only necessary if
there are data from different IEDs in order to sort them chronologically.
❑ VDEW Compatible: A “No” value allows the use of private data range.
No
Yes
Compatible mode (Yes):
Digital control signals that are sent are those configured with a compatible Funtion Type. The zero value in the table
indicates Funtion Type = Compatible. The other signals do not appear.
The user is responsible for selecting the digital signals of the device in accordance to the IEC 60870-5-103 standard.
Analog measurements are at most the first nine measures configured in the table. The Function Type and Information
Number to use (144, 145, 146 o 148) depends on the number of configured measures. 1, 2, 4 or 9 measures in the
measurements table respectively. In the last case the ASDU 9 is used instead of ASDU 3. The user is responsible for selecting
the device measures in accordance with IEC 60870-5-103.
Only the compatible commands are processed, those which in the table are configured by Function type = 0. The user is
responsible for selecting them according to IEC 60870-5-103.
The measures are sent with the Function Type field equal to "TYP in measurands ASDU" and Information Number field
equal to "INF in measuransds ASDU".
❑ Function type: Value used to describe the type of protection equipment used.
distance protection ( 128 )
overcurrent protection ( 160 )
transformer differential protection ( 176 )
line differential protection ( 192 )
❑ TYP in measurands ASDU: This setting only applies when the adjustment VDEW is set to No. Indicates the Function Type
that is used in measurands ASDU.
❑ INF in measurands ASDU: The setting only applies when the adjustment VDEW is set to not. The field indicates the
Information Number used in measurands ASDU.
❑ Transformation ratio: Transformation ratio applied in the measurands.
Secundary
Primary
The configuration settings for the IEC 60870-5-103 are in the GEN\103ITCP1 node IEC 61850 data model, as detailed in the following
table:
26.3 TABLES
There are 3 tables to configure the list of digital signals, measurements and commands.
For each element the following fields must be configured with the software configuration tool:
When simple type signals are used, the field is sent as is the norm in section 7.2.6.5. Double-point information:
<1> := OFF
<2> := ON
When using DP type signals, the meaning of the values 0 and 3 changes, becoming:
<1> := OFF
<2> := ON
❑ Measure number: Measure position inside the ASDU. The first position is zero.
❑ Internal IED: IED of the signal value. Value 0 corresponds to the device itself.
❑ Internal ID: Internal measure number that identifies the element inside the device. In the case that the measure
belongs to the compatible range, the user is responsible for selecting the measure of the device in accordance to
the IEC 60870-5-103 standard.
❑ Límit scale: Real positive measurement value corresponding to 4095 internal units. If the value is zero and the
transformation ratio setting indicates secondary, the database limit scale is applied to the measure. If the value is
zero and transformation ratio setting indicates primary, the database limit scale is applied to the measure
multiplied by the transformation ratio.
❑ Function type: Function Type field for the signal. In the case that the signal belongs to the compatible range, (128,
160, 176 o 192), it should be configured a value of 0.
❑ Information number: Information Number for the signal.
❑ DCO: ON/OFF value of the command.
❑ IED interno: IED of the command value. Value 0 corresponds to the device itself
❑ Internal ID: Internal command number that identifies the element inside the device. In the case that the command
belongs to the compatible range, the user is responsible for selecting the command of the device in accordance to
the IEC 60870-5-103 standard
❑ Origin: Command origin. Allowed values:
Bay Control
Station Control
Remote Control
Automatic Bay
Automatic Station
Automatic Remote
Maintenance
Process
27.1 INTRODUCTION
The device provides a Procome interface to act as RTU and to communicate with a Procome master (for example a remote control
station).
The communication can be selected for a serial line or via Ethernet, using encapsulation by means of the TCP/IP protocol.
❑ Port Number: This setting enables the selection between the available communication channels:
Disable
COM1
COM2
COM3
COM4
COM5
COM6
Ethernet 1
Ethernet 2
❑ Procome address: Procome slave address of the device. Value between 0 and 254.
❑ Comm speed (bauds): This setting enables the selection of the serial baud rate.
300 baud
600 baud
1200 baud
2400 baud
4800 baud
9600 baud
19200 baud
38400 baud
57600 baud
115200 baud
❑ Parity: Enables the selection of the parity type to be used in transmission.
Without parity
Even
Odd
❑ Number of Stop bits: Value between 1 and 2.
❑ Carrier stabilization (ms): Waiting time for the transmission of the message after the CTS detection in order to allow the
carrier stabilization. Value between 0 and 1000.
❑ CTS wait time (ms): Waiting time for the CTS activation after the RTS activation. Value between 0 and 10000.
❑ RTS activation time (ms): Waiting time for the activation of the RTS and the transmission of a message after the reception
of a message. Value between 0 and 1000.
❑ RTS drop out time (ms): Waiting time for the RTS deactivation after the message last byte transmission.
❑ Channel Type: Enables de selection of the communication control type.
Standard
RTS Control
By Phone
❑ Change wait time (s): Waiting time for the SOE in the internal queue before processing the events. It is only necessary if
there are data from different IEDs in order to sort them chronologically.
❑ Permission to synchronize: Synchronization permission from control centre.
Yes
No
It is used to configure the synchronization source when there are several available.
The configuration settings for the first PROCOME are in the GEN\ITCP1 node IEC 61850 data model, as detailed in the following
table:
27.3 TABLES
There are 4 tables to configure the list of digital status (binary inputs), analogs, counters and commands.
❑ Remte Signal, (nP): Procome signal number. Values between 0 and 1023.
❑ IED, (UCL): IED of the signal. Value 0 corresponds to the device itself.
❑ Internal signal, (nUCL): Internal signal number that identifies the element inside the device.
❑ Inverted, (Inv): Indicates if the signal status is inverted. By default is not inverted.
Not inverted (0)
Inverted (1)
❑ Reference 61850 of signal.
❑ Remote Measure, (nP): number of measure Procome. Values between 0 and 255. Gaps are allowed.
❑ Internal IED, (UCL): IED of the analog value. Value 0 corresponds to the device itself.
❑ Internal ID, (nUCL): Internal analog number that identifies the element inside the device.
❑ Reference 61850 of measure.
❑ Remote counter, (nP): Procome counter number. Values between 0 and 255. Gaps are allowed.
❑ Internal IED, (UCL): IED of the counter value. Value 0 corresponds to the device itself.
❑ Internal ID, (nUCL): Internal counter number that identifies the element inside the device.
❑ Reference 61850 of counter.
❑ Remote command, (nP): Procome command number. Values between 0 and 1023.
❑ Internal IED: IED of the command. Value 0 corresponds to the device itself.
❑ Internal ID, (nUCL): Internal command number that identifies the element inside the device. The value of the
Internal command ON corresponds to the number of even order and the value to be the odd OFF
❑ Source (origen):
Station Control
Remote Control
Automatic Station
Automatic Remote
NOTE: If the 'source' field does not exist in the file, it takes as default Control Station.
❑ Reference 61850 of command.
28.1 INTRODUCTION
The Modbus master protocol allows communication with control and/or protection and measuring devices.
Currently, the device has only asynchronous serial communication, with a start bit, 8 bits of data and configurable parity and stop bits.
The protocol allows the database to update with digital signals, measurements and counters. It also allows to send commands. For
some type of devices it allows to send synchronization messages and request for signal changes or events.
A configuration table, generated with a software tool dedicated to this effect, will indicate the number of information elements of each
type that each equipment has, as well as its address according to the Modbus RTU protocol.
❑ Enable protocol:
No
Yes
❑ Port Number: It allows to set the communication channel between the available serial COMs.
COM1
COM2
COM3
COM4
COM5
COM6
❑ Comm speed (bauds): It allows to select the serial transmission speed.
600 baud
1200 baud
2400 baud
4800 baud
9600 baud
19200 baud
38400 baud
57600 baud
❑ Parity: It allows to select the type of parity to be used in the transmission.
None
Even
Odd
❑ Number of stop bits:
1 Bit
2 Bit
❑ Communication control: It allows to select the type of communication channel.
RS232_FO
RS485
❑ RTS activation delay Time (ms): Minimum waiting time to activate the RTS and start the transmission. Value between 0 and 5000.
❑ CTS max delay (ms): How much time the device will wait to activate the CTS after the activation of the RTS. Value between 0 and
10000.
❑ Carrier stabilization (ms): Waiting time to start the transmission, once CTS has been detected, in order to stabilize the carrier. Value
between 0 and 5000
❑ RTS dropoff time (ms): This is the time that the RTS signal keeps activated after the transmission of the last byte. Value between 0
and 5000.
❑ Respond delay time (ms): Maximum time that the master waits to receive the slave response. Value between 10 and 30000.
❑ Inter request time (ms): The time between two request cycles of the master device. Value between 10 and 30000.
❑ Transmission retries number: Indicates the number of data request retries the master device does, if it does not receive any
response from the slave device at a given time (Respond delay time). Value between 0 and 10.
The protocol allows the master device to read signals, measurements and counters from the slave devices. It also allows sending
commands to the devices. In addition it allows to request signal changes and synchronization for the next devices: PL300 and TCP-IH.
Different types and formats of signals, measurements and counters are supported. The device configuration will indicate the data and
formats to be requested for each slave.
28.3.2 Measurements
The Modbus master has the following measurement types:
11 15 bits plus sign Measurements in 16-bit signed format with sign in the higher bit
28.3.3 Counters
Table 236 Counter types
28.3.4 Commands
The Modbus functions implemented in the device for the execution of commands are F05 and F16. Only one type of function can
be used for each device.
The information related to the Modbus functions is in the sections of Implemented functions and RTU types of this manual.
28.3.6 Synchronization
Currently, the synchronization it is only implemented for PL300 and TCP-IH.
The Modbus master functions that may be used for requesting and writing data in the slave devices are the following:
The Modbus master will use these functions taking into account the type and database of the device configured in the “Modbus master
configurator”
The following table shows the type of devices currently considered in the Modbus master and the Modbus functions used for each
type:
❑ RTU type 1: It supports reading digital outputs bit by bit, reading registers and writing digital outputs bit by bit
F01: Function for reading digital outputs bit by bit
F04: Function for reading registers
F05: Function for writing digital outputs bit by bit
❑ RTU type 3: It supports reading digital outputs bit by bit, reading registers and writing multiple registers
F01: Function for reading digital outputs bit by bit
F03: Function for reading registers
F16: Function for writing multiple registers
❑ RTU type 4: It supports reading digital inputs bit by bit, reading registers and exception states and writing digital outputs bit by bit
F02: Function for reading digital inputs bit by bit
F03: Function for reading registers
The Modbus master protocol is configured using the “Modbus master configurator” available in the PacFactory configuration SW and
EFS tools. This tool generates a configuration file that is sent to the device.
❑ IED
Modbus address
Address of the slave device (1 - 128). It is the value of the Modbus address of the device to communicate with.
Internal address
Address of the slave device in the internal database. Its value is between 1 and 32. All the elements that are requested from
the device will be mapped on this address of the master database.
RTU type
This field can take the following values: 1, 3, 4, 5, 10 and 14. The characteristics of each of these values are given in the RTU
Types section of this manual. It shows the functions used for each type of device.
Sync RTU
Enables sending synchronization to the slave device. It is only implemented for RTU type 10 (TCP-IH or PL300).
To enable synchronization, the Sync RTU flag is activated. Once enabled, the following screen appears:
The synchronization address of the device is indicated in the Sync address field.
Sync adjust (ftrans) is the time in ms that will be added to the synchronization time to correct possible drifts.
Events request
It enables the request of signal changes of the slave device. It is only supported for RTU type 10 (PL300 or TCP-IH).
In the Event address field, the signal change start address for the given device is indicated. PL300 = 20480 and TCP-IH =
1664.
Endianness
It can take two values: Big Endian and Little Endian. Default value: Big endian.
It indicates the way in which the slave equipment sends the data.
Examples:
Big endian
Hexadecimal value 43 54 80 00
Little endian
212.5
Decimal value
Hexadecimal value 43 54 80 00
❑ Digital signals
Modbus address
Modbus address of the slave device. It can take values between 1 and 128.
Modbus signal
Initial memory address of the signal to be read in the slave device database.
Type
Type of signal to be read. See the “Digital signals” section of this manual.
No. of registers
It is the number of signals or the number of registers to be read, depending on the type of signal.
Digital signal (16 signals / WORD) or Digital signal (1 signal / WORD): number of registers.
Internal ID
It indicates the first position in the master internal communication database on which these signals will be mapped. The
automatic assignment must be used by clicking on the button highlighted in red in the image, Set internal IDs
❑ Measurements
Modbus address
Modbus address of the slave device. It can take values between 1 and 128.
Modbus measurement
First memory address of the measurement to be read in the slave device database.
Type
Type of measurement to be read. See the “Measurements” section of this manual.
Format
Format of the measurement to be read. See the “Measurements” section of this manual.
Swapping
Possible values: No swap, Byte Word swap, Byte swap and Word swap. Default value: No swap.
It indicates the order in which the slave device sends data greater than one byte. Usually used for measurements and / or
32bit counters.
Examples:
No swap
Hexadecimal value 00 01 11 70
Hexadecimal value 00 01 11 70
Byte swap
Hexadecimal value 00 01 11 70
Word swap
Hexadecimal value 00 01 11 70
No. of elements
It is the number of measurements to be read from the “Modbus measurement” field.
Scale factor
The measurement value in the internal database is the value read multiplied by the scale factor.
By double-clicking on this field, it appears a screen for the scale factor configuration for this measurement.
Internal ID
It indicates the first position in the master internal communication database, where these measurements will be mapped.
The automatic assignment must be used by clicking on the button highlighted in red in the image, Set internal IDs.
❑ Counters
Modbus address
Modbus address of the slave device. It can take values between 1 and 128.
Modbus counter
Initial memory address of the counters to be read in the slave device database.
Format
Format of the counters to be read. See the “Counters” section of this manual.
Swapping
Possible values: No swap, Byte Word swap, Byte swap and Word swap. Default value: No swap.
It indicates the order in which the slave device sends data greater than one byte. Usually used for measurements and / or
32 bit counters.
Examples:
No swap
Hexadecimal value 00 01 D4 C0
Hexadecimal value 00 01 D4 C0
Byte swap
Hexadecimal value 00 01 D4 C0
Word swap
Hexadecimal value 00 01 D4 C0
No. of elements
It is the number of counters to be read from the “Modbus counter” field.
Scale factor
The counter value in the internal database is the value read, multiplied by the scale factor.
By double-clicking on this field, it appears a screen for the scale factor configuration for that counter.
Internal ID
It indicates the first position in the master internal communication database where these counters will be mapped. The
automatic assignment must be used by clicking on the button highlighted in red in the image, Set internal IDs.
❑ Commands
Modbus address
Modbus address of the slave device. It can take values between 1 and 128.
Command No.
Number of command in the master internal database (0-3071).
Modbus command
Modbus address for the command to be executed.
Value
Value to be written on the Modbus command field.
❑ Big endian
❑ Events request: No
❑ Synchronization: No
❑ Signals to be read
From address 0
Number of signals: 2
Type: Digital outputs
❑ Measurements to read
From address 0
Number of measurements: 2
Format: 16-bit unsigned
Swapping: No swap
Scale factors
▪ Measurement 0: 0.1
▪ Measurement 1: 0.01
From address 40
Number of measurements: 1
Format: 16-bit signed
Swapping: No swap
Scale factors
▪ Measurement 0: 0.001
From address 66
Number of measurements: 3
Format: 32-bit unsigned
Swapping: No swap
Scale factors
▪ Measurement 0: 1
▪ Measurement 1: 1
▪ Measurement 2: 1
From address 500
Number of measurements: 1
Format: 32-bit signed
Swapping: No swap
Scale factors
▪ Measurement 0: 0.1
From address 530
Number of measurements: 2
Format: float
Swapping: No swap
Scale factors
▪ Measurement 0: 0.1
▪ Measurement 1: 0.1
❑ Counters to read
From address 60
Number of counters: 4
Format: 32-bit unsigned
Swapping: No swap
Scale factors
▪ Counter 0: 0.001
▪ Counter 1: 0.001
▪ Counter 2: 0.001
▪ Counter 3: 0.001
❑ Commands to execute
Number of command 0
Address: 0
Value: 255
With this configuration, digital output 1 is activated.
Number of command 1
Address: 1
Value: 255
With this configuration, digital output 2 is activated.
Number of command 2
Address: 0
Value: 0
With this configuration, digital output 1 is deactivated.
Number of command 3
Address: 1
Value: 0
With this configuration, digital output 2 is deactivated.
Database configuration:
❑ IED
❑ Digital signals
❑ Measurements
❑ Counters
❑ Commands
The format of the serial communication messages used by the Modbus Master protocol is shown below, with the functions used by the
device as an example.
28.7.1 Format
❑ Master request:
Remote address - 1 byte
Function code - 1 byte
Data - variable number of bytes
CRC - 2 byte
❑ Slave response:
Remote address - 1 byte
Function code: If it is > 127 (bit MSB to 1) it means that the remote has not performed the required function and will answer with
an error code.
28.7.2 Examples
❑ Function code 01 – Read n output bits
❑ Example:
Remote address: 1
Request of 12 output bits, from output 3 to 14 (All of these bits are activated)
Table 240 Request
CRC 2 xx xx
CRC 2 xx xx
❑ In the request response, the LSB of the Outputs status byte contains the value of the first output (output 3). The rest of the
bytes are sent in lowest to highest order. If the number of bits requested is not a multiple of 8, the byte will be filled with
zeros.
❑ Function code 02 – Read n input bits
❑ Request and response frames are identical to the function 01.
❑ Function code 03 – Read n output words
CRC 2 xx xx
CRC 2 xx xx
CRC 2 xx xx
CRC 2 xx xx
CRC 2 xx xx
CRC 2 xx xx
Example:
Remote address: 1
Writing command number 24 to 1
CRC 2 xx xx
CRC 2 xx xx
29.1 INTRODUCTION
The device has a Modbus slave protocol which can communicate with a telecontrol station or with any system that works as a master.
❑ RTU (Remote terminal unit): Asynchronous serial communication, with a start bit, 8 bits of data and configurable parity and stop
bits.
❑ TCP/IP: Uses a TCP/IP network connecting through the registered port 502.
The protocol allows sending digital signals, measurements and counters to the master. It also allows the synchronization of the device
and the execution of commands.
A configuration table, generated with a software tool dedicated to this effect, will indicate the number of information elements that
the equipment has.
❑ Enable protocol:
No
Yes
❑ Modbus address: Modbus address of the slave device. Value between 1 and 128.
❑ Port number: It allows to set the communication channel
COM1
COM2
COM3
COM4
COM5
COM6
Ethernet
❑ TCP listen port: It allows to set a number of network port to communicate via TCP/IP. Value between 0 and 65535. Default value
502.
Function
Description Use
Code
Function
Description Use
Code
❑ Function 03
❑ Reading a register on 0000h address (see "Equipment address map" section of this manual). The device respond is a byte
with the LOCAL/REMOTE STATE of the device.
❑ Function 04
❑ It works the same way as Function F03.
❑ Function 01
❑ Reading boolean data.
❑ Function 02
❑ Reading boolean data.
❑ Function 03
❑ Reading registers.
❑ Function 04
❑ Reading registers.
❑
Address range:
❑ Function 03
❑ Reading registers.
❑ Function 04
❑ Reading registers.
❑
Address range:
❑ Reading the address 0680h gets the number of changes to send by the slave device
❑ To obtain the information of the changes, reading the quantity of "number of changes x 5" on address 0682h is needed.
Reading range 0682h - 06FFh.
❑ The maximum quantity of registers that can be read is 125. This is the same as reading 25 changes since the information of
a digital signal change is stored in 5 registers. The number of registers to be read must be multiple of 5.
❑ Signal change structure format:
Number
MSB LSB
of Address
(Most Signifant Byte) (Least Significant Byte)
change (n)
0682h e v E V Bits and Signal number Signal number
0683h Milliseconds Milliseconds
n=1 0684h Hours Minutes
0685h Month Day of the week and day of the month
0686h --- Year
1 < n < 25 … … …
06FBh e v E V Bits and Signal number Signal number
06FCh Milliseconds Milliseconds
n = 25 06FDh Hours Minutes
06FEh Month Day of the week and day of the month
06FFh --- Year
Signal number: It is stored in the first byte of the information of a digital signal change and in the first four bits of the
next byte.
V Bit: Validity of the signal after its change (0: valid / 1: invalid)
E Bit: State of the signal after its change (0 / 1)
v Bit: It indicates if the signal change is due to a change in the validity V (0 / 1)
e Bit: It indicates if the signal change is due to a change in the state E (0 / 1)
Milliseconds: It is stored in the second register of the information of a signal change. Range of values 0 - 59999.
Minutes: It is stored in the first byte of the third register of the information of a signal change. Range of values 0 - 59.
Hours: It is stored in the second byte of the third register of the information of a signal change. Range of values 0 - 23.
Day of the month: It is stored in the first byte of the fourth register of the information of a signal change. Its value is
registered in the first five bits of that byte. Range of values 1 - 31.
Day of the week: It is stored in the first byte of the fourth register of the information of a signal change. Its value is
registered in the last three bits of that byte. Range of values 1 - 7.
Month: It is stored in the second byte of the fourth register of the information of a signal change. Range of values 1 -
12.
Year: It is stored in the fifth register of the information of a signal change. Range of values 0 - 99.
❑ Writing the value 0 in address 0681h the last signal changes sent are validated. This means that the signal changes of the
device are considered as sent.
❑ If the signal changes are not validated, the device will consider that they have not been sent.
❑ If the device had more signal changes it will indicate it in the address 0680h and the master station could request them
repeating the process
❑ To read all the signal changes of the device, the process must continue until the reading of the address 0680h indicates
value 0
The requests are made with functions F03 and F04 and the writings with function F16.
Functioning:
❑ The configured addresses must be written using function F16. Range of the writing area 0180h - 01FCh
❑ The data of the configured addresses must be read using function F03 or F04. Range of the reading area 0100h - 017Ch
❑ Up to 124 registers can be read and written
❑ The configured addresses must be in the range 0400h - 0680h and 0700h - 0900h
❑ To read the data of the configured addresses, the following must be taken into account:
The position in the reading area from which to request the data, must be the same as the position in the writing area
where the configured addresses have been written
Example:
For a writing in address 0185h the reading has to be in address 0105h.
Writing
Writing address: 0185h
Position in the writing area: 0185h - 0180h(initial address) = 0005h
Reading
The reading address must be: 0105h
Position in the reading area: 0105h - 0100h(initial address) = 0005h
The number of registers to be requested must be equal to the number of registers that add up the data of the
configured addresses
Example:
For a writing in address 0185h of the address 0400h, 0486h and 0581h the number of registers to be requested must
be 4.
It must be ask for a register for the signals, another for the measurements of integer type and two registers for the
counters.
Writing
Writing address: 0185h
Addresses configured:
▪ 0400h: First word of digital signals
▪ 0486h: Seventh measurement of integer type
▪ 0581h: Second counter
Reading
Reading address: 0105h
The number of registers to request must be 4:
29.4.6 Synchronization
To synchronize the device it must be written with the function F16 the following information in the address 00F0h:
MSB LSB
Address
(Most Signifant Byte) (Least Significant Byte)
00F0h Milliseconds Milliseconds
00F1h Hours Minutes
00F2h Month Day
00F3h - Year
To synchronize the device the four words must always be written. The partial writing of some data is not allowed, it is
always necessary to write the whole structure
It is possible to read the address 00F0h to get the current time of the equipment. Any register can be read as long as
the range does not exceed the address 00F3h. For reading, functions F03 or F04 must be used
❑ Function F05
❑ It allows the execution of commands to OFF and ON in the slave device database.
For an OFF command it must be sent the number of command to execute and the operation value field to 0x0000.
For an ON command it must be sent the number of command to execute and the operation value field to 0xFF00.
❑ Function F06
❑ It allows the execution of commands to ON in the slave device database.
It must be written the number of command to execute in the address 0080h.
❑ Function F15
❑ It allows the execution of commands to OFF and ON in the slave device database.
For an OFF command it must be sent the number of command to execute, the number of coils to be forced to one and
the operation value field to 0.
For an ON command it must be sent the number of command to execute, the number of coils to be forced to one and
the operation value field to 1.
It is only allowed the writing of one coil.
❑ Function F16
❑ It allows the execution of commands to ON in the slave device database.
It must be written the number of command to execute in the address 0080h.
It is only allowed the writing of one register.
Range of number of command to execute: 0 - 511
Register Memory
Description Length (words)
address(hex) zone
Identification of the equipment
0000 Device status 1 G1
Command address (*)
0080 Number of command to be executed 1 G2
System date
00F0 Milliseconds 1 G3
00F1 Hours and minutes 1 G4
00F2 Month and day 1 G5
00F3 Year 1 G6
User map
0100 User map values 124 G7
0180 User map addresses 124 G8
Reading zone
0400 Digital signal states 128 G9
0480 Measurements 256 G10
0580 Counters 256 G11
Digital signal changes zone
0680 Number of changes to be sent 1 G12
0681 Validation of sent changes (*) 1 G13
0682 Digital signal changes reading zone 125 G14
Reading zone
0700 Measurement 512 G15
Free memory zone
0900 Free
0HF Free
The values of the Memory zone column are explained in the "Data format" section.
Data format depending on the memory zone (see section "Equipment address map"):
Memory
Format Description
zone
READING AREA OF THE DEVICE MODE
In the bit 0 LOCAL/REMOTE STATE of the device is indicated
G1 16 bits Value 0: REMOTE STATE
Value 1: LOCAL
Size of the area: A register (word)
WRITING AREA OF THE NUMBER OF COMMAND TO BE EXECUTED IN THE SLAVE DEVICE
DATABASE
G2 16 bits
Range of values: 0 - 511
Size of the area: A register (word)
MILLISECONDS READING AREA
G3 Unsigned 16 bits Range of values: 0 - 59999
Size of the area: A register (word)
READING AREA OF MINUTES AND HOURS
- Minutes: 0 to 7 bits
Range of values: 0 - 59
G4 16 bits
- Hours: 8 to 15 bits
Range of values: 0 - 23
Size of the area: A register (word)
READING AREA OF THE DAY OF THE WEEK AND MONTH
- Day: 0 to 7 bits
Range of values: 1 - 31
G5
16 bits - Month: 8 to 15 bits
Range of values: 1 - 12
Size of the area: A register (word)
READING AREA OF THE YEAR
- Year: 0 to 7 bits
G6 16 bits Range of values: 0 - 99
- It is not used: 8 to 15 bits
Size of the area: A register (word)
READING AREA OF THE VALUES OF THE CONFIGURED DATA ADDRESSES
- The unsigned 16 bits format is used for reading signals
16 bits - The signed 16 bits format is used for reading integer measurements
G7
Unsigned 32 bits - The unsigned 32 bits format is used for reading counters
Float - The Float format is used for reading floating type measurements
Size of the area: 124 registers (words)
WRITING AREA OF THE CONFIGURED ADDRESSES
G8 16 bits Range of values: 0400h - 0680h and 0700h - 0900h
Size of the area: 124 registers (words)
READING AREA OF SIGNALS
G9 16 bits Compacted bits. A bit to 0 value means signal deactivated and to value 1 activated
Size of the area: 128 registers (words)
READING AREA OF INTEGER MEASUREMENTS
G10 Signed 16 bits
Size of the area: 256 registers (words)
READING AREA OF COUNTERS
G11 Unsigned 32 bits
Size of the area: 256 registers (words)
READING AREA OF SIGNAL CHANGES TO BE SENT
G12 16 bits
Size of the area: A register (word)
WRITING AREA OF VALUE 0 TO VALIDATE THE SIGNAL CHANGES THAT HAS BEEN SENT
G13 16 bits
Size of the area: A register (word)
SIGNAL CHANGES INFORMATION AREA
G14
Unsigned 16 bits For more information go to the section "Request for digital signal changes"
Size of the area: 125 registers (word)
READING AREA OF FLOATING TYPE MEASUREMENTS
G15 Float
Size of the area: 512 registers (words)
The Modbus slave protocol is configured with the "Modbus Slave Configurator" available in the PacFactory configuration SW and the
EFS tools. This tool generates a configuration file that is sent to the device.
Modbus address
The number of the signal in the Modbus slave database. Range of values 0 - 2047.
Internal IED
The address of the remote device from which read the signals. Range of values 0 - 32. The value 0 is the address of the
device itself.
Internal ID
The number of the signal in the slave device database. It must be selected by clicking on button and choosing the signal
to be read. This signal will be mapped to the position indicated by Modbus address.
Description
It doesn´t need to be configured. The own tool does it.
IEC-61850 ref
It doesn´t need to be configured. The own tool does it.
Inverted
It allows to invert the value of the signal.
❑ Measurements
Modbus address
The number of the measurement in the Modbus slave database. Range of values 0 - 255.
Internal IED
The address of the remote device from which read the measurements. Range of values 0 - 32. The value 0 is the address of
the device itself.
Internal ID
The number of the measurement in the slave device database. It must be selected by clicking on button and choosing
the measurement to be read. This measurement will be mapped to the position indicated by Modbus address.
Description
It doesn´t need to be configured. The own tool does it.
IEC-61850 ref
It doesn´t need to be configured. The own tool does it.
❑ Counters
Modbus address
The number of the counter in the Modbus slave database. Range of values 0 - 127.
Internal IED
The address of the remote device from which read the counters. Range of values 0 - 32. The value 0 is the address of the
device itself.
Internal ID
The number of the counter in the slave device database. It must be selected by clicking on button and choosing the
counter to be read. This counter will be mapped to the position indicated by Modbus address.
Description
It doesn´t need to be configured. The own tool does it.
IEC-61850 ref
It doesn´t need to be configured. The own tool does it.
❑ Commands
❑ There are two options for the execution of commands depending on the function that is used (go to the section
"Command execution" for more detail): Commands to ON and to OFF/ON.
❑ The default configuration allows executing ON commands only.
❑ COMMANDS TO ON:
Command
Number of the command in the Modbus slave database. Range of values: 0 - 511.
Internal IED
The address of the remote device in which execute the commands. Range of values 0 - 32. The value 0 is the address of the
device itself.
Internal ID
The number of the command in the slave device database. It must be selected by clicking on button and choosing the
command to execute. The execution of this command is a consequence of the activation of the command number that
appears in the field Command.
Description
It doesn´t need to be configured. The own tool does it.
IEC-61850 ref
It doesn´t need to be configured. The own tool does it.
ON/OFF
It doesn´t need to be configured. The own tool does it.
Origin
It is the origin from where the commands are executed.
To do this, go to the "View" menu, click on "Options…" and the following image appears:
Enabling "Show OFF command" option in Modbus Slave and clicking on OK the following image where commands to ON
and OFF are configured is shown:
Command
Number of the command in the Modbus slave database. Range of values: 0 - 511.
Internal IED
The address of the remote device in which execute the commands. Range of values 0 - 32. The value 0 is the address of the
device itself.
Internal ID(ON)
The number of the command in the slave device database. It must be selected by clicking on button and choosing the
command to execute. The execution of this command is a consequence of the activation of the command number that
appears in field Command.
Description (ON)
It doesn´t need to be configured. The own tool does it.
ON/OFF (ON)
It doesn´t need to be configured. The own tool does it.
Internal ID(OFF)
The number of the command in the slave device database. It must be selected by clicking on button and choosing the
command to execute. The execution of this command is a consequence of the deactivation of the command number that
appears in field Command.
Description (OFF)
It doesn´t need to be configured. The own tool does it.
ON/OFF (OFF)
It doesn´t need to be configured. The own tool does it.
Origin
It is the origin from where the commands are executed.
❑ 10 digital signals
❑ 5 measurements
❑ 5 counters
❑ 4 commands
Database configuration:
❑ Digital signals
Five logical counters of the device, whose value is stored in the positions 0, 5, 10, 15 and 20 of the Modbus slave
counters database.
❑ Commands
The format of the serial communication messages used by the Modbus slave protocol is shown below, with the functions used by the
device as an example.
29.8.1 Format
❑ Master request:
Remote address - 1 byte
Function code - 1 byte
Data - variable number of bytes
CRC - 2 byte
❑ Slave response:
Remote address - 1 byte
Function code - 1 byte
Data - variable number of bytes
CRC - 2 byte
Remote address: Modbus address (Value between 1 and 128). Broadcast messages (address 0) are not allowed.
Function code: If it is > 127 (bit MSB to 1) it means that the remote device has not performed the required function and will answer
with an error code.
29.8.2 Examples
❑ Function code 01 – Read coils
❑ For reading boolean data.
❑ Example:
Remote address: 1
Request of 12 output bits, from output 3 to 14 (All of these bits are activated)
CRC 2 xx xx
Table 3. Response
CRC 2 xx xx
❑ In the request response, the LSB of the Digital outputs value contains the value of the first output (output 3). The rest of
the bytes are sent in lowest to highest order. If the number of bits requested is not a multiple of 8, the byte will be filled
with zeros.
❑ Function code 02 – Read discrete inputs
❑ For reading boolean data.
❑ Request and response frames are identical to the function 01.
❑ Function code 03 – Read holding registers
❑ For reading digital signals, measurements and counters.
❑ Example:
Remote address: 1
Address: 0400h - Data: 00AAh
Address: 0401h - Data: 00FFh
Table 4. Request
CRC 2 xx xx
Table 5. Response
0x00
Register value 1 2
0xAA
0x00
Register value 2 2
0xFF
CRC 2 xx xx
Table 6. Request
CRC 2 xx xx
Table 7. Response
CRC 2 xx xx
Example:
Remote address: 1
Writing command number 24 to 1
Table 8. Request
CRC 2 xx xx
Table 9. Response
CRC 2 xx xx
Example:
Remote address: 1
Writing command number 24 to 1
CRC 2 xx xx
CRC 2 xx xx
Example:
Remote address: 1
Writing command number 24 to 1
0x00
Number of command to execute 2
0x18
CRC 2 xx xx
CRC 2 xx xx
29.9.1 Format
The message contains the following elements:
❑ Header
❑ It contains the following fields:
Length
Fields Description Client Server
(bytes)
Identification of a Modbus Recopied by the
Transaction Initialized by the
2 request/response server from the
identifier client
transaction received request
Recopied by the
Protocol It takes value 0 for Initialized by the
2 server from the
identifier Modbus protocol client
received request
Recopied by the
Identification of the Initialized by the
Unit identifier 1 server from the
connected slave device client
received request
Transaction Protocol
Length Unit identifier Function code Data
identifier identifier
(2 bytes) (1 byte) (1 byte) (n bytes)
(2 bytes) (2 bytes)
All the messages are sent via TCP to registered port 502.
❑ Master request:
❑ Slave response:
Transaction Id. - Copy of the value received from the master device
Protocol Id. - Copy of the value received from the master device
Length - Number of bytes of Unity Id. + Function code + Data
Unity Id. - Copy of the value received from the master device
Function code
Data - Number of variable bytes
29.9.2 Examples
The types of message are the same as the serial ones. The address map of the device and the way to treat it is the same as explained
before, only changes the structure of the message to send/receive.
Enclosed below are the groups of curves, according to BS142, which correspond to the following types:
k tr
T = M TRECAIDA = M
2
I −1 I −1
I I
0 0
In which:
The following represent the curves which correspond to indexes 0.05, 0.1, 0.2, 0.3, 0.4, 0.5, 0.6, 0.7, 0.8, 0.9 and 1.0 for each type of
characteristic. Bear in mind that there are another 9 curves between each of the two curves illustrated, except between 0.05 and 0.1,
between which there are another 4.
For the values of I/Io greater than 40, the trip time is the correspond time of I/Io=40.
k tr
T = M TRECAIDA = M
2
I −1 I −1
I I
0 0
M\I/Io 0 0.25 0.5 0.75 1.05 1.10 1.20 1.30 1.50 2.00 2.50 3.00 5.00 10.00 20.00 40.00
0.05 0.485 0.517 0.647 1.109 7.170 3.669 1.916 1.331 0.860 0.501 0.378 0.315 0.214 0.149 0.113 0.091
0.06 0.582 0.621 0.776 1.330 8.604 4.402 2.299 1.597 1.032 0.602 0.454 0.378 0.257 0.178 0.136 0.110
0.07 0.679 0.724 0.905 1.552 10.038 5.136 2.683 1.863 1.204 0.702 0.530 0.441 0.300 0.208 0.159 0.128
0.08 0.776 0.828 1.035 1.774 11.472 5.870 3.066 2.129 1.376 0.802 0.606 0.504 0.342 0.238 0.181 0.146
0.09 0.873 0.931 1.164 1.995 12.906 6.604 3.449 2.395 1.547 0.903 0.681 0.567 0.385 0.267 0.204 0.165
0.10 0.970 1.035 1.293 2.217 14.340 7.337 3.832 2.661 1.719 1.003 0.757 0.630 0.428 0.297 0.227 0.183
0.11 1.067 1.138 1.423 2.439 15.774 8.071 4.216 2.927 1.891 1.103 0.833 0.693 0.471 0.327 0.249 0.201
0.12 1.164 1.242 1.552 2.661 17.208 8.805 4.599 3.193 2.063 1.203 0.908 0.756 0.514 0.356 0.272 0.219
0.13 1.261 1.345 1.681 2.882 18.642 9.539 4.982 3.459 2.235 1.304 0.984 0.819 0.556 0.386 0.295 0.238
0.14 1.358 1.449 1.811 3.104 20.076 10.272 5.365 3.725 2.407 1.404 1.060 0.882 0.599 0.416 0.317 0.256
0.15 1.455 1.552 1.940 3.326 21.510 11.006 5.749 3.992 2.579 1.504 1.135 0.945 0.642 0.446 0.340 0.274
0.16 1.552 1.655 2.069 3.547 22.944 11.740 6.132 4.258 2.751 1.605 1.211 1.008 0.685 0.475 0.363 0.293
0.17 1.649 1.759 2.199 3.769 24.378 12.474 6.515 4.524 2.923 1.705 1.287 1.071 0.728 0.505 0.385 0.311
0.18 1.746 1.862 2.328 3.991 25.812 13.207 6.898 4.790 3.095 1.805 1.363 1.134 0.770 0.535 0.408 0.329
0.19 1.843 1.966 2.457 4.213 27.246 13.941 7.282 5.056 3.267 1.906 1.438 1.197 0.813 0.564 0.431 0.347
0.20 1.940 2.069 2.587 4.434 28.680 14.675 7.665 5.322 3.439 2.006 1.514 1.260 0.856 0.594 0.453 0.366
0.25 2.425 2.587 3.233 5.543 35.850 18.344 9.581 6.653 4.299 2.507 1.892 1.575 1.070 0.743 0.567 0.457
0.30 2.910 3.104 3.880 6.651 43.021 22.012 11.497 7.983 5.158 3.009 2.271 1.891 1.284 0.891 0.680 0.549
0.35 3.395 3.621 4.527 7.760 50.191 25.681 13.413 9.314 6.018 3.510 2.649 2.206 1.498 1.040 0.794 0.640
0.40 3.880 4.139 5.173 8.869 57.361 29.350 15.329 10.644 6.878 4.012 3.028 2.521 1.712 1.188 0.907 0.731
0.45 4.365 4.656 5.820 9.977 64.531 33.018 17.246 11.975 7.737 4.513 3.406 2.836 1.926 1.337 1.020 0.823
0.50 4.850 5.173 6.467 11.086 71.701 36.687 19.162 13.305 8.597 5.015 3.785 3.151 2.140 1.485 1.134 0.914
0.55 5.335 5.691 7.113 12.194 78.871 40.356 21.078 14.636 9.457 5.516 4.163 3.466 2.354 1.634 1.247 1.006
0.60 5.820 6.208 7.760 13.303 86.041 44.025 22.994 15.966 10.317 6.017 4.542 3.781 2.568 1.782 1.360 1.097
0.65 6.305 6.725 8.407 14.411 93.211 47.693 24.910 17.297 11.176 6.519 4.920 4.096 2.782 1.931 1.474 1.188
0.70 6.790 7.243 9.053 15.520 100.381 51.362 26.827 18.627 12.036 7.020 5.299 4.411 2.996 2.079 1.587 1.280
0.75 7.275 7.760 9.700 16.629 107.551 55.031 28.743 19.958 12.896 7.522 5.677 4.726 3.210 2.228 1.701 1.371
0.80 7.760 8.277 10.347 17.737 114.721 58.700 30.659 21.288 13.755 8.023 6.056 5.042 3.424 2.376 1.814 1.463
0.85 8.245 8.795 10.993 18.846 121.891 62.368 32.575 22.619 14.615 8.525 6.434 5.357 3.638 2.525 1.927 1.554
0.90 8.730 9.312 11.640 19.954 129.062 66.037 34.491 23.949 15.475 9.026 6.813 5.672 3.852 2.674 2.041 1.646
0.95 9.215 9.829 12.287 21.063 136.232 69.706 36.408 25.280 16.335 9.528 7.191 5.987 4.066 2.822 2.154 1.737
1.00 9.700 10.347 12.933 22.171 143.402 73.374 38.324 26.611 17.194 10.029 7.570 6.302 4.280 2.971 2.267 1.828
1.05 10.185 10.864 13.580 23.280 150.572 77.043 40.240 27.941 18.054 10.530 7.948 6.617 4.494 3.119 2.381 1.920
k tr
T = M TRECAIDA = M
2
I −1 I −1
I I
0
@Fig.160.png-H:61,65-W:103,7@ @Fig.161.png-H:62,2-W:145,75@
0
K = 120, = 1 tr = 120
M\I/Io 0 0.25 0.50 0.75 1.05 1.10 1.20 1.30 1.50 2.00 2.50 3.00 5.00 10.00 20.00 40.00
0.05 6.000 6.400 8.000 13.714 120.000 60.000 30.000 20.000 12.000 6.000 4.000 3.000 1.500 0.667 0.316 0.154
0.06 7.200 7.680 9.600 16.457 144.000 72.000 36.000 24.000 14.400 7.200 4.800 3.600 1.800 0.800 0.379 0.185
0.07 8.400 8.960 11.200 19.200 168.000 84.000 42.000 28.000 16.800 8.400 5.600 4.200 2.100 0.933 0.442 0.215
0.08 9.600 10.240 12.800 21.943 192.000 96.000 48.000 32.000 19.200 9.600 6.400 4.800 2.400 1.067 0.505 0.246
0.09 10.800 11.520 14.400 24.686 216.000 108.000 54.000 36.000 21.600 10.800 7.200 5.400 2.700 1.200 0.568 0.277
0.10 12.000 12.800 16.000 27.429 240.000 120.000 60.000 40.000 24.000 12.000 8.000 6.000 3.000 1.333 0.632 0.308
0.11 13.200 14.080 17.600 30.171 264.000 132.000 66.000 44.000 26.400 13.200 8.800 6.600 3.300 1.467 0.695 0.338
0.12 14.400 15.360 19.200 32.914 288.000 144.000 72.000 48.000 28.800 14.400 9.600 7.200 3.600 1.600 0.758 0.369
0.13 15.600 16.640 20.800 35.657 312.000 156.000 78.000 52.000 31.200 15.600 10.400 7.800 3.900 1.733 0.821 0.400
0.14 16.800 17.920 22.400 38.400 336.000 168.000 84.000 56.000 33.600 16.800 11.200 8.400 4.200 1.867 0.884 0.431
0.15 18.000 19.200 24.000 41.143 360.000 180.000 90.000 60.000 36.000 18.000 12.000 9.000 4.500 2.000 0.947 0.462
0.16 19.200 20.480 25.600 43.886 384.000 192.000 96.000 64.000 38.400 19.200 12.800 9.600 4.800 2.133 1.011 0.492
0.17 20.400 21.760 27.200 46.629 408.000 204.000 102.000 68.000 40.800 20.400 13.600 10.200 5.100 2.267 1.074 0.523
0.18 21.600 23.040 28.800 49.371 432.000 216.000 108.000 72.000 43.200 21.600 14.400 10.800 5.400 2.400 1.137 0.554
0.19 22.800 24.320 30.400 52.114 456.000 228.000 114.000 76.000 45.600 22.800 15.200 11.400 5.700 2.533 1.200 0.585
0.20 24.000 25.600 32.000 54.857 480.001 240.000 120.000 80.000 48.000 24.000 16.000 12.000 6.000 2.667 1.263 0.615
0.25 30.000 32.000 40.000 68.571 600.001 300.000 150.000 100.000 60.000 30.000 20.000 15.000 7.500 3.333 1.579 0.769
0.30 36.000 38.400 48.000 82.286 720.001 360.000 180.000 120.000 72.000 36.000 24.000 18.000 9.000 4.000 1.895 0.923
0.35 42.000 44.800 56.000 96.000 840.001 420.000 210.000 140.000 84.000 42.000 28.000 21.000 10.500 4.667 2.211 1.077
0.40 48.000 51.200 64.000 109.714 960.001 480.000 240.000 160.000 96.000 48.000 32.000 24.000 12.000 5.333 2.526 1.231
0.45 54.000 57.600 72.000 123.429 1080.001 540.000 270.000 180.000 108.000 54.000 36.000 27.000 13.500 6.000 2.842 1.385
0.50 60.000 64.000 80.000 137.143 1200.001 600.000 300.000 200.000 120.000 60.000 40.000 30.000 15.000 6.667 3.158 1.538
0.55 66.000 70.400 88.000 150.857 1320.001 660.000 330.000 220.000 132.000 66.000 44.000 33.000 16.500 7.333 3.474 1.692
0.60 72.000 76.800 96.000 164.571 1440.002 720.000 360.000 240.000 144.000 72.000 48.000 36.000 18.000 8.000 3.789 1.846
0.65 78.000 83.200 104.000 178.286 1560.002 780.000 390.000 260.000 156.000 78.000 52.000 39.000 19.500 8.667 4.105 2.000
0.70 84.000 89.600 112.000 192.000 1680.002 840.000 420.000 280.000 168.000 84.000 56.000 42.000 21.000 9.333 4.421 2.154
0.75 90.000 96.000 120.000 205.714 1800.002 900.000 450.000 300.000 180.000 90.000 60.000 45.000 22.500 10.000 4.737 2.308
0.80 96.000 102.400 128.000 219.429 1920.002 960.000 480.000 320.000 192.000 96.000 64.000 48.000 24.000 10.667 5.053 2.462
0.85 102.000 108.800 136.000 233.143 2040.002 1020.000 510.000 340.000 204.000 102.000 68.000 51.000 25.500 11.333 5.368 2.615
0.90 108.000 115.200 144.000 246.857 2160.002 1080.000 540.000 360.000 216.000 108.000 72.000 54.000 27.000 12.000 5.684 2.769
0.95 114.000 121.600 152.000 260.571 2280.003 1140.000 570.000 380.000 228.000 114.000 76.000 57.000 28.500 12.667 6.000 2.923
1.00 120.000 128.000 160.000 274.286 2400.003 1200.000 600.000 400.000 240.000 120.000 80.000 60.000 30.000 13.333 6.316 3.077
1.05 126.000 134.400 168.000 288.000 2520.003 1260.000 630.000 420.000 252.000 126.000 84.000 63.000 31.500 14.000 6.632 3.231
k tr
T = M TRECAIDA = M
2
I −1 I −1
I I
0 0
M\I/Io 0 0.25 0.5 0.75 1.05 1.10 1.20 1.30 1.50 2.00 2.50 3.00 5.00 10.00 20.00 40.00
0.05 0.025 0.027 0.033 0.057 1.280 0.655 0.342 0.237 0.153 0.089 0.067 0.056 0.038 0.026 0.020 0.016
0.06 0.030 0.032 0.040 0.069 1.536 0.785 0.410 0.284 0.183 0.107 0.080 0.067 0.045 0.031 0.024 0.019
0.07 0.035 0.037 0.047 0.080 1.792 0.916 0.478 0.332 0.214 0.124 0.094 0.078 0.053 0.036 0.027 0.022
0.08 0.040 0.043 0.053 0.091 2.048 1.047 0.546 0.379 0.245 0.142 0.107 0.089 0.060 0.041 0.031 0.025
0.09 0.045 0.048 0.060 0.103 2.304 1.178 0.615 0.427 0.275 0.160 0.121 0.100 0.068 0.047 0.035 0.028
0.10 0.050 0.053 0.067 0.114 2.559 1.309 0.683 0.474 0.306 0.178 0.134 0.111 0.075 0.052 0.039 0.031
0.11 0.055 0.059 0.073 0.126 2.815 1.440 0.751 0.521 0.336 0.196 0.147 0.122 0.083 0.057 0.043 0.035
0.12 0.060 0.064 0.080 0.137 3.071 1.571 0.820 0.569 0.367 0.213 0.161 0.134 0.090 0.062 0.047 0.038
0.13 0.065 0.069 0.087 0.149 3.327 1.702 0.888 0.616 0.398 0.231 0.174 0.145 0.098 0.067 0.051 0.041
0.14 0.070 0.075 0.093 0.160 3.583 1.833 0.956 0.664 0.428 0.249 0.188 0.156 0.105 0.073 0.055 0.044
0.15 0.075 0.080 0.100 0.171 3.839 1.964 1.025 0.711 0.459 0.267 0.201 0.167 0.113 0.078 0.059 0.047
0.16 0.080 0.085 0.107 0.183 4.095 2.094 1.093 0.758 0.489 0.285 0.214 0.178 0.120 0.083 0.063 0.050
0.17 0.085 0.091 0.113 0.194 4.351 2.225 1.161 0.806 0.520 0.302 0.228 0.189 0.128 0.088 0.067 0.053
0.18 0.090 0.096 0.120 0.206 4.607 2.356 1.230 0.853 0.550 0.320 0.241 0.200 0.135 0.093 0.071 0.057
0.19 0.095 0.101 0.127 0.217 4.863 2.487 1.298 0.900 0.581 0.338 0.254 0.211 0.143 0.098 0.075 0.060
0.20 0.100 0.107 0.133 0.229 5.119 2.618 1.366 0.948 0.612 0.356 0.268 0.223 0.150 0.104 0.079 0.063
0.25 0.125 0.133 0.167 0.286 6.399 3.273 1.708 1.185 0.764 0.445 0.335 0.278 0.188 0.130 0.098 0.079
0.30 0.150 0.160 0.200 0.343 7.678 3.927 2.049 1.422 0.917 0.534 0.402 0.334 0.226 0.155 0.118 0.094
0.35 0.175 0.187 0.233 0.400 8.958 4.582 2.391 1.659 1.070 0.622 0.469 0.390 0.263 0.181 0.137 0.110
0.40 0.200 0.213 0.267 0.457 10.238 5.236 2.732 1.896 1.223 0.711 0.536 0.445 0.301 0.207 0.157 0.126
0.45 0.225 0.240 0.300 0.514 11.518 5.891 3.074 2.133 1.376 0.800 0.603 0.501 0.338 0.233 0.177 0.142
0.50 0.250 0.267 0.333 0.571 12.797 6.545 3.416 2.370 1.529 0.889 0.670 0.556 0.376 0.259 0.196 0.157
0.55 0.275 0.293 0.367 0.629 14.077 7.200 3.757 2.607 1.682 0.978 0.737 0.612 0.414 0.285 0.216 0.173
0.60 0.300 0.320 0.400 0.686 15.357 7.854 4.099 2.844 1.835 1.067 0.804 0.668 0.451 0.311 0.236 0.189
0.65 0.325 0.347 0.433 0.743 16.637 8.509 4.440 3.081 1.988 1.156 0.871 0.723 0.489 0.337 0.255 0.204
0.70 0.350 0.373 0.467 0.800 17.916 9.163 4.782 3.318 2.141 1.245 0.938 0.779 0.526 0.363 0.275 0.220
0.75 0.375 0.400 0.500 0.857 19.196 9.818 5.123 3.555 2.293 1.334 1.005 0.835 0.564 0.389 0.295 0.236
0.80 0.400 0.427 0.533 0.914 20.476 10.472 5.465 3.792 2.446 1.423 1.071 0.890 0.602 0.415 0.314 0.252
0.85 0.425 0.453 0.567 0.971 21.756 11.127 5.806 4.029 2.599 1.512 1.138 0.946 0.639 0.441 0.334 0.267
0.90 0.450 0.480 0.600 1.029 23.035 11.781 6.148 4.265 2.752 1.601 1.205 1.002 0.677 0.466 0.353 0.283
0.95 0.475 0.507 0.633 1.086 24.315 12.436 6.489 4.502 2.905 1.690 1.272 1.057 0.714 0.492 0.373 0.299
1.00 0.500 0.533 0.667 1.143 25.595 13.090 6.831 4.739 3.058 1.778 1.339 1.113 0.752 0.518 0.393 0.314
1.05 0.525 0.560 0.700 1.200 26.875 13.745 7.173 4.976 3.211 1.867 1.406 1.169 0.790 0.544 0.412 0.330
k tr
T = M TRECAIDA = M
2
I −1 I −1
I I
0 0
K = 13,5, = 1 tr = 43.2
M\I/Io 0 0.25 0.5 0.75 1.05 1.10 1.20 1.30 1.50 2.00 2.50 3.00 5.00 10.00 20.00 40.00
0.05 2.160 2.304 2.880 4.937 13.500 6.750 3.375 2.250 1.350 0.675 0.450 0.338 0.169 0.075 0.036 0.017
0.06 2.592 2.765 3.456 5.925 16.200 8.100 4.050 2.700 1.620 0.810 0.540 0.405 0.203 0.090 0.043 0.021
0.07 3.024 3.226 4.032 6.912 18.900 9.450 4.725 3.150 1.890 0.945 0.630 0.472 0.236 0.105 0.050 0.024
0.08 3.456 3.686 4.608 7.899 21.600 10.800 5.400 3.600 2.160 1.080 0.720 0.540 0.270 0.120 0.057 0.028
0.09 3.888 4.147 5.184 8.887 24.300 12.150 6.075 4.050 2.430 1.215 0.810 0.607 0.304 0.135 0.064 0.031
0.10 4.320 4.608 5.760 9.874 27.000 13.500 6.750 4.500 2.700 1.350 0.900 0.675 0.337 0.150 0.071 0.035
0.11 4.752 5.069 6.336 10.862 29.700 14.850 7.425 4.950 2.970 1.485 0.990 0.742 0.371 0.165 0.078 0.038
0.12 5.184 5.530 6.912 11.849 32.400 16.200 8.100 5.400 3.240 1.620 1.080 0.810 0.405 0.180 0.085 0.042
0.13 5.616 5.990 7.488 12.837 35.100 17.550 8.775 5.850 3.510 1.755 1.170 0.877 0.439 0.195 0.092 0.045
0.14 6.048 6.451 8.064 13.824 37.800 18.900 9.450 6.300 3.780 1.890 1.260 0.945 0.472 0.210 0.099 0.048
0.15 6.480 6.912 8.640 14.811 40.500 20.250 10.125 6.750 4.050 2.025 1.350 1.013 0.506 0.225 0.107 0.052
0.16 6.912 7.373 9.216 15.799 43.200 21.600 10.800 7.200 4.320 2.160 1.440 1.080 0.540 0.240 0.114 0.055
0.17 7.344 7.834 9.792 16.786 45.900 22.950 11.475 7.650 4.590 2.295 1.530 1.148 0.574 0.255 0.121 0.059
0.18 7.776 8.294 10.368 17.774 48.600 24.300 12.150 8.100 4.860 2.430 1.620 1.215 0.608 0.270 0.128 0.062
0.19 8.208 8.755 10.944 18.761 51.300 25.650 12.825 8.550 5.130 2.565 1.710 1.283 0.641 0.285 0.135 0.066
0.20 8.640 9.216 11.520 19.749 54.000 27.000 13.500 9.000 5.400 2.700 1.800 1.350 0.675 0.300 0.142 0.069
0.25 10.800 11.520 14.400 24.686 67.500 33.750 16.875 11.250 6.750 3.375 2.250 1.688 0.844 0.375 0.178 0.087
0.30 12.960 13.824 17.280 29.623 81.000 40.500 20.250 13.500 8.100 4.050 2.700 2.025 1.013 0.450 0.213 0.104
0.35 15.120 16.128 20.160 34.560 94.500 47.250 23.625 15.750 9.450 4.725 3.150 2.363 1.181 0.525 0.249 0.121
0.40 17.280 18.432 23.040 39.497 108.000 54.000 27.000 18.000 10.800 5.400 3.600 2.700 1.350 0.600 0.284 0.138
0.45 19.440 20.736 25.920 44.434 121.500 60.750 30.375 20.250 12.150 6.075 4.050 3.038 1.519 0.675 0.320 0.156
0.50 21.600 23.040 28.800 49.371 135.000 67.500 33.750 22.500 13.500 6.750 4.500 3.375 1.688 0.750 0.355 0.173
0.55 23.760 25.344 31.680 54.309 148.500 74.250 37.125 24.750 14.850 7.425 4.950 3.713 1.856 0.825 0.391 0.190
0.60 25.920 27.648 34.560 59.246 162.000 81.000 40.500 27.000 16.200 8.100 5.400 4.050 2.025 0.900 0.426 0.208
0.65 28.080 29.952 37.440 64.183 175.500 87.750 43.875 29.250 17.550 8.775 5.850 4.388 2.194 0.975 0.462 0.225
0.70 30.240 32.256 40.320 69.120 189.000 94.500 47.250 31.500 18.900 9.450 6.300 4.725 2.363 1.050 0.497 0.242
0.75 32.400 34.560 43.200 74.057 202.500 101.25 50.625 33.750 20.250 10.125 6.750 5.063 2.531 1.125 0.533 0.260
0.80 34.560 36.864 46.080 78.994 216.000 108.00 54.000 36.000 21.600 10.800 7.200 5.400 2.700 1.200 0.568 0.277
0.85 36.720 39.168 48.960 83.931 229.500 114.75 57.375 38.250 22.950 11.475 7.650 5.738 2.869 1.275 0.604 0.294
0.90 38.880 41.472 51.840 88.869 243.000 121.50 60.750 40.500 24.300 12.150 8.100 6.075 3.038 1.350 0.639 0.312
0.95 41.040 43.776 54.720 93.806 256.500 128.25 64.125 42.750 25.650 12.825 8.550 6.413 3.206 1.425 0.675 0.329
1.00 43.200 46.080 57.600 98.743 270.000 135.00 67.500 45.000 27.000 13.500 9.000 6.750 3.375 1.500 0.711 0.346
1.05 45.360 48.384 60.480 103.68 283.500 141.75 70.875 47.250 28.350 14.175 9.450 7.088 3.544 1.575 0.746 0.363
k tr
T = M TRECAIDA = M
2
I −1 I −1
I I
0 0
K = 80, = 2 tr =58.2
M\I/Io 0 0.25 0.5 0.75 1.05 1.10 1.20 1.30 1.50 2.00 2.50 3.00 5.00 10.00 20.00 40.00
0.05 2.910 3.104 3.880 6.651 39.024 19.048 9.091 5.797 3.200 1.333 0.762 0.500 0.167 0.040 0.010 0.003
0.06 3.492 3.725 4.656 7.982 46.829 22.857 10.909 6.957 3.840 1.600 0.914 0.600 0.200 0.048 0.012 0.003
0.07 4.074 4.346 5.432 9.312 54.634 26.667 12.727 8.116 4.480 1.867 1.067 0.700 0.233 0.057 0.014 0.004
0.08 4.656 4.966 6.208 10.642 62.439 30.476 14.545 9.275 5.120 2.133 1.219 0.800 0.267 0.065 0.016 0.004
0.09 5.238 5.587 6.984 11.973 70.244 34.286 16.364 10.435 5.760 2.400 1.371 0.900 0.300 0.073 0.018 0.005
0.10 5.820 6.208 7.760 13.303 78.049 38.095 18.182 11.594 6.400 2.667 1.524 1.000 0.333 0.081 0.020 0.005
0.11 6.402 6.829 8.536 14.633 85.854 41.905 20.000 12.754 7.040 2.933 1.676 1.100 0.367 0.089 0.022 0.006
0.12 6.984 7.450 9.312 15.963 93.659 45.714 21.818 13.913 7.680 3.200 1.829 1.200 0.400 0.097 0.024 0.006
0.13 7.566 8.070 10.088 17.294 101.464 49.524 23.636 15.072 8.320 3.467 1.981 1.300 0.433 0.105 0.026 0.007
0.14 8.148 8.691 10.864 18.624 109.268 53.333 25.455 16.232 8.960 3.733 2.133 1.400 0.467 0.113 0.028 0.007
0.15 8.730 9.312 11.640 19.954 117.073 57.143 27.273 17.391 9.600 4.000 2.286 1.500 0.500 0.121 0.030 0.008
0.16 9.312 9.933 12.416 21.285 124.878 60.952 29.091 18.551 10.240 4.267 2.438 1.600 0.533 0.129 0.032 0.008
0.17 9.894 10.554 13.192 22.615 132.683 64.762 30.909 19.710 10.880 4.533 2.590 1.700 0.567 0.137 0.034 0.009
0.18 10.476 11.174 13.968 23.945 140.488 68.571 32.727 20.870 11.520 4.800 2.743 1.800 0.600 0.145 0.036 0.009
0.19 11.058 11.795 14.744 25.275 148.293 72.381 34.545 22.029 12.160 5.067 2.895 1.900 0.633 0.154 0.038 0.010
0.20 11.640 12.416 15.520 26.606 156.098 76.190 36.364 23.188 12.800 5.333 3.048 2.000 0.667 0.162 0.040 0.010
0.25 14.550 15.520 19.400 33.257 195.122 95.238 45.455 28.986 16.000 6.667 3.810 2.500 0.833 0.202 0.050 0.013
0.30 17.460 18.624 23.280 39.909 234.147 114.286 54.545 34.783 19.200 8.000 4.571 3.000 1.000 0.242 0.060 0.015
0.35 20.370 21.728 27.160 46.560 273.171 133.333 63.636 40.580 22.400 9.333 5.333 3.500 1.167 0.283 0.070 0.018
0.40 23.280 24.832 31.040 53.211 312.195 152.381 72.727 46.377 25.600 10.667 6.095 4.000 1.333 0.323 0.080 0.020
0.45 26.190 27.936 34.920 59.863 351.220 171.429 81.818 52.174 28.800 12.000 6.857 4.500 1.500 0.364 0.090 0.023
0.50 29.100 31.040 38.800 66.514 390.244 190.476 90.909 57.971 32.000 13.333 7.619 5.000 1.667 0.404 0.100 0.025
0.55 32.010 34.144 42.680 73.166 429.269 209.524 100.000 63.768 35.200 14.667 8.381 5.500 1.833 0.444 0.110 0.028
0.60 34.920 37.248 46.560 79.817 468.293 228.571 109.091 69.565 38.400 16.000 9.143 6.000 2.000 0.485 0.120 0.030
0.65 37.830 40.352 50.440 86.469 507.318 247.619 118.182 75.362 41.600 17.333 9.905 6.500 2.167 0.525 0.130 0.033
0.70 40.740 43.456 54.320 93.120 546.342 266.667 127.273 81.159 44.800 18.667 10.667 7.000 2.333 0.566 0.140 0.035
0.75 43.650 46.560 58.200 99.771 585.367 285.714 136.364 86.957 48.000 20.000 11.429 7.500 2.500 0.606 0.150 0.038
0.80 46.560 49.664 62.080 106.423 624.391 304.762 145.455 92.754 51.200 21.333 12.190 8.000 2.667 0.646 0.160 0.040
0.85 49.470 52.768 65.960 113.074 663.415 323.810 154.545 98.551 54.400 22.667 12.952 8.500 2.833 0.687 0.170 0.043
0.90 52.380 55.872 69.840 119.726 702.440 342.857 163.636 104.348 57.600 24.000 13.714 9.000 3.000 0.727 0.180 0.045
0.95 55.290 58.976 73.720 126.377 741.464 361.905 172.727 110.145 60.800 25.333 14.476 9.500 3.167 0.768 0.190 0.048
1.00 58.200 62.080 77.600 133.029 780.489 380.952 181.818 115.942 64.000 26.667 15.238 10.000 3.333 0.808 0.201 0.050
1.05 61.110 65.184 81.480 139.680 819.513 400.000 190.909 121.739 67.200 28.000 16.000 10.500 3.500 0.848 0.211 0.053
k tr
T = M TRECAIDA = M
2
I −1 I −1
I I
0
@Fig.170.png-H:61,65-W:103,7@ @Fig.171.png-H:62,2-W:145,75@
0
K = 2,6 =1
M \ I/Io 1.05 1.10 1.20 1.30 1.40 1.50 2.00 2.50 3.00 4.00 5.00 7.00 10.00 12.00 15.00 20.00 30.00 40.00
0.05 2.600 1.300 0.650 0.433 0.325 0.260 0.130 0.087 0.065 0.043 0.032 0.022 0.014 0.012 0.009 0.007 0.004 0.003
0.06 3.120 1.560 0.780 0.520 0.390 0.312 0.156 0.104 0.078 0.052 0.039 0.026 0.017 0.014 0.011 0.008 0.005 0.004
0.07 3.640 1.820 0.910 0.607 0.455 0.364 0.182 0.121 0.091 0.061 0.045 0.030 0.020 0.017 0.013 0.010 0.006 0.005
0.08 4.160 2.080 1.040 0.693 0.520 0.416 0.208 0.139 0.104 0.069 0.052 0.035 0.023 0.019 0.015 0.011 0.007 0.005
0.09 4.680 2.340 1.170 0.780 0.585 0.468 0.234 0.156 0.117 0.078 0.058 0.039 0.026 0.021 0.017 0.012 0.008 0.006
0.10 5.200 2.600 1.300 0.867 0.650 0.520 0.260 0.173 0.130 0.087 0.065 0.043 0.029 0.024 0.019 0.014 0.009 0.007
0.11 5.720 2.860 1.430 0.953 0.715 0.572 0.286 0.191 0.143 0.095 0.071 0.048 0.032 0.026 0.020 0.015 0.010 0.007
0.12 6.240 3.120 1.560 1.040 0.780 0.624 0.312 0.208 0.156 0.104 0.078 0.052 0.035 0.028 0.022 0.016 0.011 0.008
0.13 6.760 3.380 1.690 1.127 0.845 0.676 0.338 0.225 0.169 0.113 0.084 0.056 0.038 0.031 0.024 0.018 0.012 0.009
0.14 7.280 3.640 1.820 1.213 0.910 0.728 0.364 0.243 0.182 0.121 0.091 0.061 0.040 0.033 0.026 0.019 0.013 0.009
0.15 7.800 3.900 1.950 1.300 0.975 0.780 0.390 0.260 0.195 0.130 0.098 0.065 0.043 0.035 0.028 0.021 0.013 0.010
0.16 8.320 4.160 2.080 1.387 1.040 0.832 0.416 0.277 0.208 0.139 0.104 0.069 0.046 0.038 0.030 0.022 0.014 0.011
0.17 8.840 4.420 2.210 1.473 1.105 0.884 0.442 0.295 0.221 0.147 0.111 0.074 0.049 0.040 0.032 0.023 0.015 0.011
0.18 9.360 4.680 2.340 1.560 1.170 0.936 0.468 0.312 0.234 0.156 0.117 0.078 0.052 0.043 0.033 0.025 0.016 0.012
0.19 9.880 4.940 2.470 1.647 1.235 0.988 0.494 0.329 0.247 0.165 0.124 0.082 0.055 0.045 0.035 0.026 0.017 0.013
0.20 10.400 5.200 2.600 1.733 1.300 1.040 0.520 0.347 0.260 0.173 0.130 0.087 0.058 0.047 0.037 0.027 0.018 0.013
0.25 13.000 6.500 3.250 2.167 1.625 1.300 0.650 0.433 0.325 0.217 0.163 0.108 0.072 0.059 0.046 0.034 0.022 0.017
0.30 15.600 7.800 3.900 2.600 1.950 1.560 0.780 0.520 0.390 0.260 0.195 0.130 0.087 0.071 0.056 0.041 0.027 0.020
0.35 18.200 9.100 4.550 3.033 2.275 1.820 0.910 0.607 0.455 0.303 0.228 0.152 0.101 0.083 0.065 0.048 0.031 0.023
0.40 20.800 10.400 5.200 3.467 2.600 2.080 1.040 0.693 0.520 0.347 0.260 0.173 0.116 0.095 0.074 0.055 0.036 0.027
0.45 23.400 11.700 5.850 3.900 2.925 2.340 1.170 0.780 0.585 0.390 0.293 0.195 0.130 0.106 0.084 0.062 0.040 0.030
0.50 26.000 13.000 6.500 4.333 3.250 2.600 1.300 0.867 0.650 0.433 0.325 0.217 0.144 0.118 0.093 0.068 0.045 0.033
0.55 28.600 14.300 7.150 4.767 3.575 2.860 1.430 0.953 0.715 0.477 0.358 0.238 0.159 0.130 0.102 0.075 0.049 0.037
0.60 31.200 15.600 7.800 5.200 3.900 3.120 1.560 1.040 0.780 0.520 0.390 0.260 0.173 0.142 0.111 0.082 0.054 0.040
0.65 33.800 16.900 8.450 5.633 4.225 3.380 1.690 1.127 0.845 0.563 0.423 0.282 0.188 0.154 0.121 0.089 0.058 0.043
0.70 36.400 18.200 9.100 6.067 4.550 3.640 1.820 1.213 0.910 0.607 0.455 0.303 0.202 0.165 0.130 0.096 0.063 0.047
0.75 39.000 19.500 9.750 6.500 4.875 3.900 1.950 1.300 0.975 0.650 0.488 0.325 0.217 0.177 0.139 0.103 0.067 0.050
0.80 41.600 20.800 10.400 6.933 5.200 4.160 2.080 1.387 1.040 0.693 0.520 0.347 0.231 0.189 0.149 0.109 0.072 0.053
0.85 44.200 22.100 11.050 7.367 5.525 4.420 2.210 1.473 1.105 0.737 0.553 0.368 0.246 0.201 0.158 0.116 0.076 0.057
0.90 46.800 23.400 11.700 7.800 5.850 4.680 2.340 1.560 1.170 0.780 0.585 0.390 0.260 0.213 0.167 0.123 0.081 0.060
0.95 49.400 24.700 12.350 8.233 6.175 4.940 2.470 1.647 1.235 0.823 0.618 0.412 0.274 0.225 0.176 0.130 0.085 0.063
1.00 52.000 26.000 13.000 8.667 6.500 5.200 2.600 1.733 1.300 0.867 0.650 0.433 0.289 0.236 0.186 0.137 0.090 0.067
1.05 54.600 27.300 13.650 9.100 6.825 5.460 2.730 1.820 1.365 0.910 0.683 0.455 0.303 0.248 0.195 0.144 0.094 0.070
Enclosed below are the groups of curves, according to ANSI, which correspond to the following types:
❑ Normal Inverse.
❑ Very Inverse.
❑ Extremely Inverse.
❑ Moderate Inverse.
These curves comply with the general formula
T = M A +
B D E tr
+ + TRECAIDA = M
− CI 2 3
I I − C I − C 2
I −1
0 I I I
0 0 0
@Fig.172.png-H:47,8-W:219,45@ @Fig.173.png-H:51,25-W:119,25@
in which:
The following represent the curves which correspond to indexes 0.5, 1.0, 2.0, 3.0, 4.0, 6.0, 8.0, 10.0, 15.0, 20.0 and 30.0 for each type
of characteristic. Take into account that between every two curves differentiated in 1.0 there are another 9 curves.
For the values of I/Io greater than 40, the trip time is the correspond time of I/Io=40.
T = M A +
B D E tr
+ + TRECAIDA = M
I − C 2 3
I I − C I − C 2
I −1
0 I I I
0 0 0
@Fig.174.png-H:54,7-W:250@ @Fig.175.png-H:61,65-W:143,4@
M \ I/Io 0 0.25 0.5 0.75 1.05 1.10 1.20 1.30 1.50 2.00 2.50 3.00 5.00 10.00 20.00 40.00
0.5 0.495 0.528 0.660 1.131 8.614 7.067 4.944 3.613 2.142 0.883 0.523 0.377 0.203 0.113 0.066 0.041
1.0 0.990 1.056 1.320 2.263 17.229 14.134 9.888 7.226 4.284 1.766 1.047 0.754 0.407 0.226 0.133 0.082
2.0 1.980 2.112 2.640 4.526 34.457 28.268 19.775 14.452 8.568 3.531 2.094 1.508 0.814 0.452 0.265 0.164
3.0 2.970 3.168 3.960 6.789 51.686 42.402 29.663 21.678 12.853 5.297 3.140 2.262 1.220 0.678 0.398 0.246
4.0 3.960 4.224 5.280 9.051 68.915 56.536 39.550 28.904 17.137 7.062 4.187 3.016 1.627 0.904 0.530 0.327
5.0 4.950 5.280 6.600 11.314 86.144 70.670 49.438 36.131 21.421 8.828 5.234 3.770 2.034 1.130 0.663 0.409
6.0 5.940 6.336 7.920 13.577 103.372 84.804 59.325 43.357 25.705 10.594 6.281 4.524 2.441 1.356 0.796 0.491
7.0 6.930 7.392 9.240 15.840 120.601 98.938 69.213 50.583 29.989 12.359 7.328 5.277 2.848 1.582 0.928 0.573
8.0 7.920 8.448 10.560 18.103 137.830 113.072 79.100 57.809 34.274 14.125 8.374 6.031 3.254 1.808 1.061 0.655
9.0 8.910 9.504 11.880 20.366 155.059 127.206 88.988 65.035 38.558 15.890 9.421 6.785 3.661 2.034 1.193 0.737
10.0 9.900 10.560 13.200 22.629 172.287 141.340 98.875 72.261 42.842 17.656 10.468 7.539 4.068 2.260 1.326 0.818
11.0 10.890 11.616 14.520 24.891 189.516 155.474 108.763 79.487 47.126 19.422 11.515 8.293 4.475 2.486 1.458 0.900
12.0 11.880 12.672 15.840 27.154 206.745 169.608 118.650 86.713 51.410 21.187 12.562 9.047 4.881 2.712 1.591 0.982
13.0 12.870 13.728 17.160 29.417 223.974 183.742 128.538 93.939 55.694 22.953 13.608 9.801 5.288 2.938 1.724 1.064
14.0 13.860 14.784 18.480 31.680 241.202 197.876 138.425 101.165 59.979 24.719 14.655 10.555 5.695 3.164 1.856 1.146
15.0 14.850 15.840 19.800 33.943 258.431 212.010 148.313 108.392 64.263 26.484 15.702 11.309 6.102 3.390 1.989 1.228
16.0 15.840 16.896 21.120 36.206 275.660 226.144 158.200 115.618 68.547 28.250 16.749 12.063 6.509 3.616 2.121 1.310
17.0 16.830 17.952 22.440 38.469 292.889 240.278 168.088 122.844 72.831 30.015 17.796 12.817 6.915 3.842 2.254 1.391
18.0 17.820 19.008 23.760 40.731 310.117 254.412 177.975 130.070 77.115 31.781 18.842 13.571 7.322 4.068 2.387 1.473
19.0 18.810 20.064 25.080 42.994 327.346 268.546 187.863 137.296 81.400 33.547 19.889 14.324 7.729 4.294 2.519 1.555
20.0 19.800 21.120 26.400 45.257 344.575 282.680 197.750 144.522 85.684 35.312 20.936 15.078 8.136 4.520 2.652 1.637
21.0 20.790 22.176 27.720 47.520 361.803 296.814 207.638 151.748 89.968 37.078 21.983 15.832 8.543 4.746 2.784 1.719
22.0 21.780 23.232 29.040 49.783 379.032 310.948 217.525 158.974 94.252 38.843 23.030 16.586 8.949 4.972 2.917 1.801
23.0 22.770 24.288 30.360 52.046 396.261 325.082 227.413 166.200 98.536 40.609 24.076 17.340 9.356 5.198 3.050 1.883
24.0 23.760 25.344 31.680 54.309 413.490 339.216 237.300 173.426 102.821 42.375 25.123 18.094 9.763 5.424 3.182 1.964
25.0 24.750 26.400 33.000 56.571 430.718 353.350 247.188 180.653 107.105 44.140 26.170 18.848 10.170 5.650 3.315 2.046
26.0 25.740 27.456 34.320 58.834 447.947 367.484 257.075 187.879 111.389 45.906 27.217 19.602 10.576 5.876 3.447 2.128
27.0 26.730 28.512 35.640 61.097 465.176 381.618 266.963 195.105 115.673 47.671 28.264 20.356 10.983 6.102 3.580 2.210
28.0 27.720 29.568 36.960 63.360 482.405 395.752 276.850 202.331 119.957 49.437 29.310 21.110 11.390 6.328 3.713 2.292
29.0 28.710 30.624 38.280 65.623 499.633 409.886 286.738 209.557 124.242 51.203 30.357 21.864 11.797 6.554 3.845 2.374
30.0 29.700 31.680 39.600 67.886 516.862 424.020 296.625 216.783 128.526 52.968 31.404 22.618 12.204 6.780 3.978 2.455
T = M A +
B D E tr
+ + TRECAIDA = M
− C
I 2 3
I I − C I − C 2
I −1
0 I I I
0 0 0
@Fig.176.png-H:54,7-W:250@ @Fig.177.png-H:61,65-W:143,4@
M \ I/Io 0 0.25 0.5 0.75 1.05 1.10 1.20 1.30 1.50 2.00 2.50 3.00 5.00 10.00 20.00 40.00
0.5 2.339 2.495 3.119 5.346 5.970 4.924 3.487 2.582 1.567 0.663 0.386 0.268 0.130 0.073 0.051 0.041
1.0 4.678 4.990 6.237 10.693 11.940 9.848 6.975 5.164 3.134 1.325 0.772 0.537 0.260 0.146 0.102 0.082
2.0 9.356 9.980 12.475 21.385 23.881 19.696 13.949 10.327 6.268 2.650 1.545 1.074 0.520 0.291 0.204 0.163
3.0 14.034 14.970 18.712 32.078 35.821 29.544 20.924 15.491 9.402 3.976 2.317 1.611 0.780 0.437 0.306 0.245
4.0 18.712 19.959 24.949 42.770 47.762 39.393 27.898 20.655 12.537 5.301 3.090 2.148 1.040 0.583 0.408 0.326
5.0 23.390 24.949 31.187 53.463 59.702 49.241 34.873 25.819 15.671 6.626 3.862 2.685 1.299 0.728 0.510 0.408
6.0 28.068 29.939 37.424 64.155 71.642 59.089 41.848 30.982 18.805 7.951 4.635 3.221 1.559 0.874 0.612 0.489
7.0 32.746 34.929 43.661 74.848 83.583 68.937 48.822 36.146 21.939 9.276 5.407 3.758 1.819 1.020 0.714 0.571
8.0 37.424 39.919 49.899 85.541 95.523 78.785 55.797 41.310 25.073 10.602 6.179 4.295 2.079 1.165 0.815 0.652
9.0 42.102 44.909 56.136 96.233 107.464 88.633 62.771 46.474 28.207 11.927 6.952 4.832 2.339 1.311 0.917 0.734
10.0 46.780 49.899 62.373 106.926 119.404 98.481 69.746 51.637 31.341 13.252 7.724 5.369 2.599 1.457 1.019 0.815
11.0 51.458 54.889 68.611 117.618 131.344 108.330 76.721 56.801 34.475 14.577 8.497 5.906 2.859 1.602 1.121 0.897
12.0 56.136 59.878 74.848 128.311 143.285 118.178 83.695 61.965 37.610 15.902 9.269 6.443 3.119 1.748 1.223 0.978
13.0 60.814 64.868 81.085 139.003 155.225 128.026 90.670 67.128 40.744 17.228 10.041 6.980 3.379 1.893 1.325 1.060
14.0 65.492 69.858 87.323 149.696 167.165 137.874 97.645 72.292 43.878 18.553 10.814 7.517 3.638 2.039 1.427 1.141
15.0 70.170 74.848 93.560 160.389 179.106 147.722 104.619 77.456 47.012 19.878 11.586 8.054 3.898 2.185 1.529 1.223
16.0 74.848 79.838 99.797 171.081 191.046 157.570 111.594 82.620 50.146 21.203 12.359 8.591 4.158 2.330 1.631 1.304
17.0 79.526 84.828 106.035 181.774 202.987 167.419 118.568 87.783 53.280 22.528 13.131 9.127 4.418 2.476 1.733 1.386
18.0 84.204 89.818 112.272 192.466 214.927 177.267 125.543 92.947 56.414 23.853 13.904 9.664 4.678 2.622 1.835 1.468
19.0 88.882 94.807 118.509 203.159 226.867 187.115 132.518 98.111 59.549 25.179 14.676 10.201 4.938 2.767 1.937 1.549
20.0 93.560 99.797 124.747 213.851 238.808 196.963 139.492 103.275 62.683 26.504 15.448 10.738 5.198 2.913 2.039 1.631
21.0 98.238 104.787 130.984 224.544 250.748 206.811 146.467 108.438 65.817 27.829 16.221 11.275 5.458 3.059 2.141 1.712
22.0 102.916 109.777 137.221 235.237 262.689 216.659 153.441 113.602 68.951 29.154 16.993 11.812 5.718 3.204 2.243 1.794
23.0 107.594 114.767 143.459 245.929 274.629 226.507 160.416 118.766 72.085 30.479 17.766 12.349 5.977 3.350 2.344 1.875
24.0 112.272 119.757 149.696 256.622 286.569 236.356 167.391 123.930 75.219 31.805 18.538 12.886 6.237 3.496 2.446 1.957
25.0 116.950 124.747 155.933 267.314 298.510 246.204 174.365 129.093 78.353 33.130 19.310 13.423 6.497 3.641 2.548 2.038
26.0 121.628 129.737 162.171 278.007 310.450 256.052 181.340 134.257 81.487 34.455 20.083 13.960 6.757 3.787 2.650 2.120
27.0 126.306 134.726 168.408 288.699 322.391 265.900 188.314 139.421 84.622 35.780 20.855 14.497 7.017 3.933 2.752 2.201
28.0 130.984 139.716 174.645 299.392 334.331 275.748 195.289 144.584 87.756 37.105 21.628 15.034 7.277 4.078 2.854 2.283
29.0 135.662 144.706 180.883 310.085 346.271 285.596 202.264 149.748 90.890 38.431 22.400 15.570 7.537 4.224 2.956 2.364
30.0 140.340 149.696 187.120 320.777 358.212 295.444 209.238 154.912 94.024 39.756 23.173 16.107 7.797 4.370 3.058 2.446
T = M A +
B D E tr
+ + TRECAIDA = M
− C
I 2 3
I I − C I − C I −1
2
0 I I I
0 0 0
M \ I/Io 0 0.25 0.5 0.75 1.05 1.10 1.20 1.30 1.50 2.00 2.50 3.00 5.00 10.00 20.00 40.00
0.5 3.004 3.204 4.005 6.866 7.373 6.063 4.307 3.220 2.000 0.872 0.499 0.330 0.124 0.049 0.030 0.024
1.0 6.008 6.409 8.011 13.733 14.746 12.125 8.615 6.439 4.001 1.744 0.997 0.659 0.247 0.098 0.060 0.048
2.0 12.016 12.817 16.021 27.465 29.492 24.250 17.230 12.879 8.002 3.489 1.994 1.319 0.495 0.196 0.119 0.095
3.0 18.024 19.226 24.032 41.198 44.239 36.376 25.844 19.318 12.003 5.233 2.992 1.978 0.742 0.295 0.179 0.143
4.0 24.032 25.634 32.043 54.930 58.985 48.501 34.459 25.758 16.004 6.977 3.989 2.638 0.990 0.393 0.239 0.191
5.0 30.040 32.043 40.053 68.663 73.731 60.626 43.074 32.197 20.004 8.722 4.986 3.297 1.237 0.491 0.298 0.238
6.0 36.048 38.451 48.064 82.395 88.477 72.751 51.689 38.636 24.005 10.466 5.983 3.956 1.484 0.589 0.358 0.286
7.0 42.056 44.860 56.075 96.128 103.224 84.876 60.303 45.076 28.006 12.210 6.981 4.616 1.732 0.688 0.418 0.334
8.0 48.064 51.268 64.085 109.861 117.970 97.002 68.918 51.515 32.007 13.955 7.978 5.275 1.979 0.786 0.477 0.381
9.0 54.072 57.677 72.096 123.593 132.716 109.127 77.533 57.954 36.008 15.699 8.975 5.934 2.227 0.884 0.537 0.429
10.0 60.080 64.085 80.107 137.326 147.462 121.252 86.148 64.394 40.009 17.443 9.972 6.594 2.474 0.982 0.597 0.476
11.0 66.088 70.494 88.117 151.058 162.208 133.377 94.763 70.833 44.010 19.188 10.969 7.253 2.722 1.081 0.656 0.524
12.0 72.096 76.902 96.128 164.791 176.955 145.502 103.377 77.273 48.011 20.932 11.967 7.913 2.969 1.179 0.716 0.572
13.0 78.104 83.311 104.139 178.523 191.701 157.628 111.992 83.712 52.012 22.676 12.964 8.572 3.216 1.277 0.776 0.619
14.0 84.112 89.719 112.149 192.256 206.447 169.753 120.607 90.151 56.013 24.421 13.961 9.231 3.464 1.375 0.835 0.667
15.0 90.120 96.128 120.160 205.989 221.193 181.878 129.222 96.591 60.013 26.165 14.958 9.891 3.711 1.474 0.895 0.715
16.0 96.128 102.537 128.171 219.721 235.940 194.003 137.837 103.030 64.014 27.909 15.956 10.550 3.959 1.572 0.955 0.762
17.0 102.136 108.945 136.181 233.454 250.686 206.128 146.451 109.470 68.015 29.654 16.953 11.210 4.206 1.670 1.014 0.810
18.0 108.144 115.354 144.192 247.186 265.432 218.254 155.066 115.909 72.016 31.398 17.950 11.869 4.453 1.768 1.074 0.858
19.0 114.152 121.762 152.203 260.919 280.178 230.379 163.681 122.348 76.017 33.142 18.947 12.528 4.701 1.866 1.134 0.905
20.0 120.160 128.171 160.213 274.651 294.924 242.504 172.296 128.788 80.018 34.887 19.944 13.188 4.948 1.965 1.194 0.953
21.0 126.168 134.579 168.224 288.384 309.671 254.629 180.910 135.227 84.019 36.631 20.942 13.847 5.196 2.063 1.253 1.001
22.0 132.176 140.988 176.235 302.117 324.417 266.754 189.525 141.666 88.020 38.375 21.939 14.506 5.443 2.161 1.313 1.048
23.0 138.184 147.396 184.245 315.849 339.163 278.879 198.140 148.106 92.021 40.120 22.936 15.166 5.691 2.259 1.373 1.096
24.0 144.192 153.805 192.256 329.582 353.909 291.005 206.755 154.545 96.022 41.864 23.933 15.825 5.938 2.358 1.432 1.144
25.0 150.200 160.213 200.267 343.314 368.655 303.130 215.370 160.985 100.022 43.608 24.931 16.485 6.185 2.456 1.492 1.191
26.0 156.208 166.622 208.277 357.047 383.402 315.255 223.984 167.424 104.023 45.353 25.928 17.144 6.433 2.554 1.552 1.239
27.0 162.216 173.030 216.288 370.779 398.148 327.380 232.599 173.863 108.024 47.097 26.925 17.803 6.680 2.652 1.611 1.286
28.0 168.224 179.439 224.299 384.512 412.894 339.505 241.214 180.303 112.025 48.841 27.922 18.463 6.928 2.751 1.671 1.334
29.0 174.232 185.847 232.309 398.245 427.640 351.631 249.829 186.742 116.026 50.586 28.920 19.122 7.175 2.849 1.731 1.382
30.0 180.240 192.256 240.320 411.977 442.387 363.756 258.444 193.182 120.027 52.330 29.917 19.782 7.422 2.947 1.790 1.429
T = M A +
B D E tr
+ + TRECAIDA = M
− C
I 2 3
I I − C I − C 2
I −1
0 I I I
0 0
0
A = 0.1735, B = 0.6791, C = 0.8000, D = -0.0800, E = 0.1271 tr = 1.2
M \ I/Io 0 0.25 0.5 0.75 1.05 1.10 1.20 1.30 1.50 2.00 2.50 3.00 5.00 10.00 20.00 40.00
0.5 0.600 0.640 0.800 1.371 4.872 3.128 1.679 1.114 0.675 0.379 0.286 0.239 0.166 0.123 0.104 0.095
1.0 1.200 1.280 1.600 2.743 9.744 6.256 3.357 2.229 1.351 0.757 0.571 0.478 0.332 0.247 0.209 0.191
2.0 2.400 2.560 3.200 5.486 19.489 12.511 6.714 4.457 2.702 1.515 1.142 0.955 0.665 0.493 0.417 0.382
3.0 3.600 3.840 4.800 8.229 29.233 18.767 10.072 6.686 4.053 2.272 1.713 1.433 0.997 0.740 0.626 0.572
4.0 4.800 5.120 6.400 10.971 38.977 25.023 13.429 8.914 5.404 3.030 2.285 1.910 1.329 0.986 0.835 0.763
5.0 6.000 6.400 8.000 13.714 48.722 31.278 16.786 11.143 6.755 3.787 2.856 2.388 1.662 1.233 1.043 0.954
6.0 7.200 7.680 9.600 16.457 58.466 37.534 20.143 13.371 8.106 4.544 3.427 2.866 1.994 1.479 1.252 1.145
7.0 8.400 8.960 11.200 19.200 68.210 43.790 23.500 15.600 9.457 5.302 3.998 3.343 2.327 1.726 1.461 1.335
8.0 9.600 10.240 12.800 21.943 77.954 50.045 26.857 17.828 10.807 6.059 4.569 3.821 2.659 1.972 1.669 1.526
9.0 10.800 11.520 14.400 24.686 87.699 56.301 30.215 20.057 12.158 6.817 5.140 4.298 2.991 2.219 1.878 1.717
10.0 12.000 12.800 16.000 27.429 97.443 62.557 33.572 22.285 13.509 7.574 5.712 4.776 3.324 2.465 2.087 1.908
11.0 13.200 14.080 17.600 30.171 107.187 68.813 36.929 24.514 14.860 8.332 6.283 5.253 3.656 2.712 2.295 2.099
12.0 14.400 15.360 19.200 32.914 116.932 75.068 40.286 26.742 16.211 9.089 6.854 5.731 3.988 2.958 2.504 2.289
13.0 15.600 16.640 20.800 35.657 126.676 81.324 43.643 28.971 17.562 9.846 7.425 6.209 4.321 3.205 2.713 2.480
14.0 16.800 17.920 22.400 38.400 136.420 87.580 47.001 31.199 18.913 10.604 7.996 6.686 4.653 3.451 2.921 2.671
15.0 18.000 19.200 24.000 41.143 146.165 93.835 50.358 33.428 20.264 11.361 8.567 7.164 4.986 3.698 3.130 2.862
16.0 19.200 20.480 25.600 43.886 155.909 100.091 53.715 35.656 21.615 12.119 9.139 7.641 5.318 3.945 3.339 3.052
17.0 20.400 21.760 27.200 46.629 165.653 106.347 57.072 37.885 22.966 12.876 9.710 8.119 5.650 4.191 3.547 3.243
18.0 21.600 23.040 28.800 49.371 175.398 112.602 60.429 40.113 24.317 13.633 10.281 8.597 5.983 4.438 3.756 3.434
19.0 22.800 24.320 30.400 52.114 185.142 118.858 63.787 42.342 25.668 14.391 10.852 9.074 6.315 4.684 3.965 3.625
20.0 24.000 25.600 32.000 54.857 194.886 125.114 67.144 44.570 27.019 15.148 11.423 9.552 6.647 4.931 4.173 3.815
21.0 25.200 26.880 33.600 57.600 204.630 131.369 70.501 46.799 28.370 15.906 11.994 10.029 6.980 5.177 4.382 4.006
22.0 26.400 28.160 35.200 60.343 214.375 137.625 73.858 49.027 29.720 16.663 12.565 10.507 7.312 5.424 4.591 4.197
23.0 27.600 29.440 36.800 63.086 224.119 143.881 77.215 51.256 31.071 17.421 13.137 10.985 7.645 5.670 4.799 4.388
24.0 28.800 30.720 38.400 65.829 233.863 150.136 80.572 53.484 32.422 18.178 13.708 11.462 7.977 5.917 5.008 4.579
25.0 30.000 32.000 40.000 68.571 243.608 156.392 83.930 55.713 33.773 18.935 14.279 11.940 8.309 6.163 5.217 4.769
26.0 31.200 33.280 41.600 71.314 253.352 162.648 87.287 57.941 35.124 19.693 14.850 12.417 8.642 6.410 5.425 4.960
27.0 32.400 34.560 43.200 74.057 263.096 168.903 90.644 60.170 36.475 20.450 15.421 12.895 8.974 6.656 5.634 5.151
28.0 33.600 35.840 44.800 76.800 272.841 175.159 94.001 62.398 37.826 21.208 15.992 13.373 9.306 6.903 5.843 5.342
29.0 34.800 37.120 46.400 79.543 282.585 181.415 97.358 64.627 39.177 21.965 16.564 13.850 9.639 7.149 6.051 5.532
30.0 36.000 38.400 48.000 82.286 292.329 187.671 100.716 66.855 40.528 22.722 17.135 14.328 9.971 7.396 6.260 5.723
Enclosed below are the groups of curves, according to IEC 60255-151, which correspond to the following types:
𝑘 𝑡𝑟
𝑇 = 𝑀[ 𝐼 𝛼
+ 𝑐] 𝑇𝐷𝑅𝑂𝑃 = 𝑀 [ 𝐼 2
]
( ) −1 1−( )
𝐼0 𝐼0
in which:
Constants IEEE Moderte Inverse IEEE Very Inverse IEEE Extremely Inverse
K 0.0515 19.61 28.2
0.02 2 2
c 0.114 0.491 0.1217
tr 4.85 21.6 29.1
The following represent the curves which correspond to indexes 0.05, 0.1, 0.2, 0.3, 0.4, 0.5, 0.6, 0.7, 0.8, 0.9 and 1.0 for
each type of characteristic. Bear in mind that there are another 9 curves between each of the two curves illustrated, except
between 0.05 and 0.1, between which there are another 4.
36
Avaliable from firmware version 6.0.8.2 and ICD version 8.2.0.0.
𝑘 𝑡𝑟
𝑇 = 𝑀[ 𝐼 𝛼
+ 𝑐] 𝑇𝑅𝐸𝐶𝐴𝐼𝐷𝐴 = 𝑀 [ 𝐼 2
]
( ) −1 1−( )
𝐼0 𝐼0
M\I/Io 0 0.25 0.5 0.75 1.05 1.10 1.20 1.30 1.50 2.00 2.50 3.00 5.00 10.00 20.00 40.00
0.05 0.243 0.259 0.323 0.554 2.643 1.355 0.711 0.495 0.322 0.190 0.145 0.122 0.084 0.060 0.047 0.039
0.06 0.291 0.310 0.388 0.665 3.172 1.626 0.853 0.594 0.386 0.228 0.174 0.146 0.101 0.072 0.057 0.047
0.340 0.362 0.453 0.776 3.701 1.897 0.995 0.693 0.451 0.266 0.203 0.170 0.118 0.084 0.066 0.055
0.07
0.08 0.388 0.414 0.517 0.887 4.229 2.168 1.137 0.792 0.515 0.304 0.232 0.195 0.135 0.097 0.076 0.063
0.09 0.437 0.466 0.582 0.998 4.758 2.439 1.279 0.891 0.580 0.342 0.261 0.219 0.152 0.109 0.085 0.071
0.485 0.517 0.647 1.109 5.287 2.711 1.421 0.990 0.644 0.380 0.290 0.243 0.169 0.121 0.095 0.079
0.10
0.11 0.534 0.569 0.711 1.219 5.815 2.982 1.563 1.089 0.708 0.418 0.319 0.268 0.186 0.133 0.104 0.087
0.12 0.582 0.621 0.776 1.330 6.344 3.253 1.705 1.188 0.773 0.456 0.348 0.292 0.203 0.145 0.114 0.094
0.631 0.673 0.841 1.441 6.872 3.524 1.848 1.287 0.837 0.494 0.377 0.316 0.219 0.157 0.123 0.102
0.13
0.14 0.679 0.724 0.905 1.552 7.401 3.795 1.990 1.386 0.901 0.532 0.406 0.341 0.236 0.169 0.133 0.110
0.15 0.728 0.776 0.970 1.663 7.930 4.066 2.132 1.485 0.966 0.570 0.435 0.365 0.253 0.181 0.142 0.118
0.776 0.828 1.035 1.774 8.458 4.337 2.274 1.584 1.030 0.609 0.464 0.389 0.270 0.193 0.152 0.126
0.16
0.17 0.825 0.879 1.099 1.885 8.987 4.608 2.416 1.683 1.095 0.647 0.493 0.413 0.287 0.205 0.161 0.134
0.18 0.873 0.931 1.164 1.995 9.516 4.879 2.558 1.783 1.159 0.685 0.522 0.438 0.304 0.217 0.171 0.142
0.922 0.983 1.229 2.106 10.044 5.150 2.700 1.882 1.223 0.723 0.551 0.462 0.321 0.229 0.180 0.149
0.19
0.20 0.970 1.035 1.293 2.217 10.573 5.421 2.842 1.981 1.288 0.761 0.580 0.486 0.338 0.241 0.190 0.157
0.25 1.213 1.293 1.617 2.771 13.216 6.776 3.553 2.476 1.610 0.951 0.725 0.608 0.422 0.302 0.237 0.197
1.455 1.552 1.940 3.326 15.860 8.132 4.263 2.971 1.932 1.141 0.870 0.730 0.506 0.362 0.284 0.236
0.30
0.35 1.698 1.811 2.263 3.880 18.503 9.487 4.974 3.466 2.254 1.331 1.015 0.851 0.591 0.422 0.332 0.275
0.40 1.940 2.069 2.587 4.434 21.146 10.842 5.685 3.961 2.576 1.521 1.159 0.973 0.675 0.483 0.379 0.315
2.183 2.328 2.910 4.989 23.789 12.197 6.395 4.456 2.898 1.711 1.304 1.094 0.760 0.543 0.427 0.354
0.45
0.50 2.425 2.587 3.233 5.543 26.433 13.553 7.106 4.951 3.220 1.902 1.449 1.216 0.844 0.603 0.474 0.393
0.55 2.668 2.845 3.557 6.097 29.076 14.908 7.816 5.447 3.541 2.092 1.594 1.338 0.929 0.664 0.521 0.433
2.910 3.104 3.880 6.651 31.719 16.263 8.527 5.942 3.863 2.282 1.739 1.459 1.013 0.724 0.569 0.472
0.60
0.65 3.153 3.363 4.203 7.206 34.362 17.618 9.238 6.437 4.185 2.472 1.884 1.581 1.097 0.784 0.616 0.511
0.70 3.395 3.621 4.527 7.760 37.006 18.974 9.948 6.932 4.507 2.662 2.029 1.703 1.182 0.845 0.664 0.551
3.638 3.880 4.850 8.314 39.649 20.329 10.659 7.427 4.829 2.852 2.174 1.824 1.266 0.905 0.711 0.590
0.75
0.80 3.880 4.139 5.173 8.869 42.292 21.684 11.369 7.922 5.151 3.043 2.319 1.946 1.351 0.965 0.758 0.629
0.85 4.123 4.397 5.497 9.423 44.935 23.040 12.080 8.417 5.473 3.233 2.464 2.067 1.435 1.026 0.806 0.669
4.365 4.656 5.820 9.977 47.579 24.395 12.790 8.913 5.795 3.423 2.609 2.189 1.519 1.086 0.853 0.708
0.90
0.95 4.608 4.915 6.143 10.531 50.222 25.750 13.501 9.408 6.117 3.613 2.754 2.311 1.604 1.146 0.901 0.747
1.00 4.850 5.173 6.467 11.086 52.865 27.105 14.212 9.903 6.439 3.803 2.899 2.432 1.688 1.207 0.948 0.787
1.05 5.093 5.432 6.790 11.640 55.509 28.461 14.922 10.398 6.761 3.993 3.044 2.554 1.773 1.267 0.995 0.826
1.5 7.275 7.760 9.700 16.629 79.298 40.658 21.317 14.854 9.659 5.705 4.348 3.648 2.532 1.810 1.422 1.180
2.5 12.125 12.933 16.167 27.714 132.163 67.763 35.529 24.757 16.098 9.508 7.246 6.081 4.221 3.017 2.370 1.967
4.0 19.400 20.693 25.867 44.343 211.461 108.421 56.847 39.611 25.756 15.213 11.594 9.729 6.753 4.827 3.792 3.146
6.0 29.100 31.040 38.800 66.514 317.192 162.632 85.270 59.417 38.634 22.819 17.391 14.593 10.130 7.241 5.688 4.720
10.0 48.500 51.733 64.667 110.857 528.653 271.053 142.117 99.029 64.390 38.032 28.986 24.322 16.883 12.068 9.481 7.866
15.0 72.750 77.600 97.000 166.286 792.979 406.580 213.175 148.543 96.585 57.049 43.479 36.483 25.325 18.101 14.221 11.799
𝑘 𝑡𝑟
𝑇 = 𝑀[ 𝐼 𝛼
+ 𝑐] 𝑇𝑅𝐸𝐶𝐴𝐼𝐷𝐴 = 𝑀 [ 𝐼 2
]
( ) −1 1−( )
𝐼0 𝐼0
M\I/Io 0 0.25 0.5 0.75 1.05 1.10 1.20 1.30 1.50 2.00 2.50 3.00 5.00 10.00 20.00 40.00
0.05 1.080 1.152 1.440 2.469 9.590 4.694 2.253 1.446 0.809 0.351 0.211 0.147 0.065 0.034 0.027 0.025
0.06 1.296 1.382 1.728 2.962 11.508 5.632 2.704 1.735 0.971 0.422 0.254 0.177 0.078 0.041 0.032 0.030
1.512 1.613 2.016 3.456 13.427 6.571 3.154 2.024 1.133 0.492 0.296 0.206 0.092 0.048 0.038 0.035
0.07
0.08 1.728 1.843 2.304 3.950 15.345 7.510 3.605 2.313 1.294 0.562 0.338 0.235 0.105 0.055 0.043 0.040
0.09 1.944 2.074 2.592 4.443 17.263 8.448 4.055 2.602 1.456 0.632 0.380 0.265 0.118 0.062 0.049 0.045
2.160 2.304 2.880 4.937 19.181 9.387 4.506 2.891 1.618 0.703 0.423 0.294 0.131 0.069 0.054 0.050
0.10
0.11 2.376 2.534 3.168 5.431 21.099 10.326 4.957 3.180 1.780 0.773 0.465 0.324 0.144 0.076 0.059 0.055
0.12 2.592 2.765 3.456 5.925 23.017 11.265 5.407 3.469 1.941 0.843 0.507 0.353 0.157 0.083 0.065 0.060
2.808 2.995 3.744 6.418 24.935 12.203 5.858 3.758 2.103 0.914 0.549 0.382 0.170 0.090 0.070 0.065
0.13
0.14 3.024 3.226 4.032 6.912 26.853 13.142 6.308 4.048 2.265 0.984 0.592 0.412 0.183 0.096 0.076 0.070
0.15 3.240 3.456 4.320 7.406 28.771 14.081 6.759 4.337 2.427 1.054 0.634 0.441 0.196 0.103 0.081 0.075
3.456 3.686 4.608 7.899 30.689 15.020 7.209 4.626 2.589 1.124 0.676 0.471 0.209 0.110 0.086 0.081
0.16
0.17 3.672 3.917 4.896 8.393 32.607 15.958 7.660 4.915 2.750 1.195 0.718 0.500 0.222 0.117 0.092 0.086
0.18 3.888 4.147 5.184 8.887 34.525 16.897 8.111 5.204 2.912 1.265 0.761 0.530 0.235 0.124 0.097 0.091
4.104 4.378 5.472 9.381 36.444 17.836 8.561 5.493 3.074 1.335 0.803 0.559 0.249 0.131 0.103 0.096
0.19
0.20 4.320 4.608 5.760 9.874 38.362 18.774 9.012 5.782 3.236 1.406 0.845 0.588 0.262 0.138 0.108 0.101
0.25 5.400 5.760 7.200 12.343 47.952 23.468 11.265 7.228 4.045 1.757 1.057 0.736 0.327 0.172 0.135 0.126
6.480 6.912 8.640 14.811 57.542 28.162 13.518 8.673 4.854 2.108 1.268 0.883 0.392 0.207 0.162 0.151
0.30
0.35 7.560 8.064 10.080 17.280 67.133 32.855 15.771 10.119 5.663 2.460 1.479 1.030 0.458 0.241 0.189 0.176
0.40 8.640 9.216 11.520 19.749 76.723 37.549 18.024 11.565 6.472 2.811 1.690 1.177 0.523 0.276 0.216 0.201
9.720 10.368 12.960 22.217 86.314 42.242 20.277 13.010 7.281 3.162 1.902 1.324 0.589 0.310 0.243 0.226
0.45
0.50 10.800 11.520 14.400 24.686 95.904 46.936 22.530 14.456 8.090 3.514 2.113 1.471 0.654 0.345 0.270 0.252
0.55 11.880 12.672 15.840 27.154 105.494 51.630 24.783 15.901 8.898 3.865 2.324 1.618 0.719 0.379 0.297 0.277
12.960 13.824 17.280 29.623 115.085 56.323 27.036 17.347 9.707 4.217 2.536 1.765 0.785 0.413 0.324 0.302
0.60
0.65 14.040 14.976 18.720 32.091 124.675 61.017 29.288 18.792 10.516 4.568 2.747 1.912 0.850 0.448 0.351 0.327
0.70 15.120 16.128 20.160 34.560 134.266 65.710 31.541 20.238 11.325 4.919 2.958 2.060 0.916 0.482 0.378 0.352
16.200 17.280 21.600 37.029 143.856 70.404 33.794 21.683 12.134 5.271 3.170 2.207 0.981 0.517 0.405 0.377
0.75
0.80 17.280 18.432 23.040 39.497 153.446 75.098 36.047 23.129 12.943 5.622 3.381 2.354 1.046 0.551 0.432 0.403
0.85 18.360 19.584 24.480 41.966 163.037 79.791 38.300 24.575 13.752 5.974 3.592 2.501 1.112 0.586 0.459 0.428
19.440 20.736 25.920 44.434 172.627 84.485 40.553 26.020 14.561 6.325 3.804 2.648 1.177 0.620 0.486 0.453
0.90
0.95 20.520 21.888 27.360 46.903 182.218 89.178 42.806 27.466 15.370 6.676 4.015 2.795 1.243 0.655 0.513 0.478
1.00 21.600 23.040 28.800 49.371 191.808 93.872 45.059 28.911 16.179 7.028 4.226 2.942 1.308 0.689 0.540 0.503
1.05 22.680 24.192 30.240 51.840 201.398 98.566 47.312 30.357 16.988 7.379 4.438 3.089 1.373 0.724 0.567 0.528
1.5 32.400 34.560 43.200 74.057 287.712 140.808 67.589 43.367 24.269 10.542 6.339 4.413 1.962 1.034 0.810 0.755
2.5 54.000 57.600 72.000 123.429 479.520 234.680 112.648 72.278 40.448 17.569 10.566 7.356 3.270 1.723 1.350 1.258
4.0 86.400 92.160 115.200 197.486 767.232 375.488 180.237 115.645 64.716 28.111 16.905 11.769 5.232 2.756 2.161 2.013
6.0 129.600 138.240 172.800 296.229 1150.848 563.232 270.355 173.468 97.074 42.166 25.357 17.654 7.849 4.134 3.241 3.020
10.0 216.000 230.400 288.000 493.714 1918.081 938.720 450.592 289.113 161.790 70.277 42.262 29.423 13.081 6.891 5.401 5.033
15.0 324.000 345.600 432.000 740.571 2877.121 1408.079 675.888 433.669 242.685 105.415 63.394 44.134 19.621 10.336 8.102 7.549
𝑘 𝑡𝑟
𝑇 = 𝑀[ 𝐼 𝛼
+ 𝑐] 𝑇𝑅𝐸𝐶𝐴𝐼𝐷𝐴 = 𝑀 [ 𝐼 2
]
( ) −1 1−( )
𝐼0 𝐼0
M\I/Io 0 0.25 0.5 0.75 1.05 1.10 1.20 1.30 1.50 2.00 2.50 3.00 5.00 10.00 20.00 40.00
0.05 1.455 1.552 1.940 3.326 13.762 6.720 3.211 2.050 1.134 0.476 0.275 0.182 0.065 0.020 0.010 0.007
0.06 1.746 1.862 2.328 3.991 16.515 8.064 3.853 2.459 1.361 0.571 0.330 0.219 0.078 0.024 0.012 0.008
2.037 2.173 2.716 4.656 19.267 9.409 4.495 2.869 1.588 0.667 0.385 0.255 0.091 0.028 0.013 0.010
0.07
0.08 2.328 2.483 3.104 5.321 22.019 10.753 5.137 3.279 1.815 0.762 0.439 0.292 0.104 0.033 0.015 0.011
0.09 2.619 2.794 3.492 5.986 24.772 12.097 5.779 3.689 2.041 0.857 0.494 0.328 0.117 0.037 0.017 0.013
2.910 3.104 3.880 6.651 27.524 13.441 6.421 4.099 2.268 0.952 0.549 0.365 0.130 0.041 0.019 0.014
0.10
0.11 3.201 3.414 4.268 7.317 30.277 14.785 7.063 4.509 2.495 1.047 0.604 0.401 0.143 0.045 0.021 0.015
0.12 3.492 3.725 4.656 7.982 33.029 16.129 7.706 4.919 2.722 1.143 0.659 0.438 0.156 0.049 0.023 0.017
3.783 4.035 5.044 8.647 35.782 17.473 8.348 5.329 2.949 1.238 0.714 0.474 0.169 0.053 0.025 0.018
0.13
0.14 4.074 4.346 5.432 9.312 38.534 18.817 8.990 5.739 3.175 1.333 0.769 0.511 0.182 0.057 0.027 0.020
0.15 4.365 4.656 5.820 9.977 41.287 20.161 9.632 6.149 3.402 1.428 0.824 0.547 0.195 0.061 0.029 0.021
4.656 4.966 6.208 10.642 44.039 21.505 10.274 6.559 3.629 1.523 0.879 0.583 0.207 0.065 0.031 0.022
0.16
0.17 4.947 5.277 6.596 11.307 46.791 22.849 10.916 6.969 3.856 1.619 0.934 0.620 0.220 0.069 0.033 0.024
0.18 5.238 5.587 6.984 11.973 49.544 24.193 11.558 7.378 4.083 1.714 0.989 0.656 0.233 0.073 0.035 0.025
5.529 5.898 7.372 12.638 52.296 25.537 12.200 7.788 4.310 1.809 1.044 0.693 0.246 0.077 0.037 0.026
0.19
0.20 5.820 6.208 7.760 13.303 55.049 26.881 12.843 8.198 4.536 1.904 1.099 0.729 0.259 0.081 0.038 0.028
0.25 7.275 7.760 9.700 16.629 68.811 33.602 16.053 10.248 5.670 2.380 1.373 0.912 0.324 0.102 0.048 0.035
8.730 9.312 11.640 19.954 82.573 40.322 19.264 12.297 6.805 2.857 1.648 1.094 0.389 0.122 0.058 0.042
0.30
0.35 10.185 10.864 13.580 23.280 96.335 47.043 22.474 14.347 7.939 3.333 1.923 1.276 0.454 0.142 0.067 0.049
0.40 11.640 12.416 15.520 26.606 110.097 53.763 25.685 16.397 9.073 3.809 2.197 1.459 0.519 0.163 0.077 0.056
13.095 13.968 17.460 29.931 123.860 60.483 28.896 18.446 10.207 4.285 2.472 1.641 0.584 0.183 0.087 0.063
0.45
0.50 14.550 15.520 19.400 33.257 137.622 67.204 32.106 20.496 11.341 4.761 2.747 1.823 0.648 0.203 0.096 0.070
0.55 16.005 17.072 21.340 36.583 151.384 73.924 35.317 22.545 12.475 5.237 3.021 2.006 0.713 0.224 0.106 0.077
17.460 18.624 23.280 39.909 165.146 80.644 38.528 24.595 13.609 5.713 3.296 2.188 0.778 0.244 0.115 0.084
0.60
0.65 18.915 20.176 25.220 43.234 178.908 87.365 41.738 26.644 14.743 6.189 3.571 2.370 0.843 0.264 0.125 0.091
0.70 20.370 21.728 27.160 46.560 192.671 94.085 44.949 28.694 15.877 6.665 3.845 2.553 0.908 0.285 0.135 0.098
21.825 23.280 29.100 49.886 206.433 100.806 48.159 30.743 17.011 7.141 4.120 2.735 0.973 0.305 0.144 0.105
0.75
0.80 23.280 24.832 31.040 53.211 220.195 107.526 51.370 32.793 18.145 7.617 4.395 2.917 1.037 0.325 0.154 0.111
0.85 24.735 26.384 32.980 56.537 233.957 114.246 54.581 34.843 19.279 8.093 4.669 3.100 1.102 0.346 0.164 0.118
26.190 27.936 34.920 59.863 247.719 120.967 57.791 36.892 20.414 8.570 4.944 3.282 1.167 0.366 0.173 0.125
0.90
0.95 27.645 29.488 36.860 63.189 261.481 127.687 61.002 38.942 21.548 9.046 5.218 3.464 1.232 0.386 0.183 0.132
1.00 29.100 31.040 38.800 66.514 275.244 134.407 64.213 40.991 22.682 9.522 5.493 3.647 1.297 0.407 0.192 0.139
30.555 32.592 40.740 69.840 289.006 141.128 67.423 43.041 23.816 9.998 5.768 3.829 1.362 0.427 0.202 0.146
1.05
1.5 43.650 46.560 58.200 99.771 412.865 201.611 96.319 61.487 34.023 14.283 8.240 5.470 1.945 0.610 0.289 0.209
2.5 72.750 77.600 97.000 166.286 688.109 336.019 160.532 102.478 56.704 23.804 13.733 9.117 3.242 1.016 0.481 0.348
4.0 116.400 124.160 155.200 266.057 1100.975 537.630 256.850 163.965 90.727 38.087 21.973 14.587 5.187 1.626 0.770 0.557
6.0 174.600 186.240 232.800 399.086 1651.462 806.444 385.276 245.948 136.090 57.130 32.959 21.880 7.780 2.439 1.154 0.836
10.0 291.000 310.400 388.000 665.143 2752.437 1344.074 642.126 409.913 226.817 95.217 54.931 36.467 12.967 4.065 1.924 1.393
15.0 436.500 465.600 582.000 997.714 4128.655 2016.111 963.189 614.869 340.226 142.826 82.397 54.701 19.451 6.098 2.886 2.090
The user can programme FOUR curves by entering the desired points into the “User curve 1” to “User curve 4” user curve nodes.
The time corresponding to each I/Ia is programmed in seconds, with a minimum value of 0.020 seconds. These times correspond to the
curve of index 1, but as in curves IEC, the user can programme a time index between 0.05 and 1.09 in the overcurrent protection
settings.
It is not necessary to programme all the points on the curve, the unit will assign the time of the first programmed point to all those I/Ia
of a lower value and the last programmed time to all those of a higher I/Ia, that is to say, the graph will generally start and finish with
straight, horizontal lines. The points between the two programmed points will be calculated by the console as a lineal interpolation.
I/Ia values for times which are superior to that which corresponds to an inferior I/Ia are not admitted, that is to say, ascendant straight
lines are not allowed.
❑ Crv0 (Low Frame Curve). For setting (milliseconds) the activation times for 1.03 and 1.05 I/IAJ ratios.
❑ Crv1 (Medium Frame Curve). For setting (milliseconds) the activation times for 1.1 and 4 I/IAJ ratios, with steps of 0.1.
❑ Crv1 (High Frame Curve). For setting (milliseconds) the activation times for 4 and 20 I/IAJ ratios, with steps of 0.5.
The programming carried out via PacFactory is done using the programming screen shown in Figure 253, in which:
❑ The times of the curves different points are entered (left table) and the curve’s graph is displayed (right table).
❑ Interpolate points of the curve and enter the known points. By clicking on “Calculate Curve Values”, the missing values are
calculated for the curve.
❑ Reset the curve values “Reset PC column”.
❑ “Save values”. Saves the values entered in order to send them to unit.
❑ “Close”. Returns to the general settings screen, from where they can be sent to the unit.
I/Ia 2 4 8 12 15
37
From firmware version 6.0.18.0 and ICD version 8.1.0.20
Table 269. Breaker 2 - Operation supervision (only models with two breakers)
The available signals indicate faults in the card check, in the communications between the cards, in the unit’s configuration, etc.
❑ Status report
❑ Incident report
❑ Sequence of events (SOE)
❑ Digital outputs and CPU hardware alarm output.
❑ IHMI leds and status leds
The errors can be critical and non critical, depending on the effect they have in the device.
Critical errors
Critical hardware error. Indicates that a critical error has been produced. In addition to this signal, the cause that produced the signal
will be indicated.
If the error affects the unit’s operation, a critical error is generated, which in addition to the signal acts on:
❑ Colour front LED. Non-configurable status LED, which indicates the unit’s general status. If the LED is green, it indicates
that everything is correct, while if it is red it indicates a critical error in the unit.
❑ CPU Relay. Non-configurable 3-contact relay, which indicates the unit’s general status. If the LED is active (common
terminal – NO), it indicates that everything is correct, while if it is deactivated (common terminal– NC) it indicates a critical
error in the unit. If the unit is switched off, the relay is deactivated.
The causes that produce errors are:
❑ CPU error. Indicates that the check has detected an error in the CPU
❑ Analogue error. Indicates an error in transformers card.
❑ I/O micro error. Indicates an error in the I/O cards’ micro.
❑ Analogue connection error. Indicates that a fault has been produced in the communications between the CPU and the
transformers card.
❑ I/O connection error. Indicates that a fault has been produced in the communication between the CPU and an I/O card.
Additionally, it will indicate the card which has suffered the failure:
Error card address x. Indicates that there is a communication error with the card with the address x.
❑ Front connection error. Indicates that a fault has been produced in the communications between the CPU and the unit’s
front card.
❑ Shared analogue memory error. Indicates that a fault has been produced in the Data exchange memory between the CPU
and the transformers card.
❑ Error shared I/O memory. Indicates that a fault has been produced in the Data exchange memory between the CPU and
the I/O cards.
❑ Alarm settings. Indicates that errors have been detected in the storage of the unit’s settings.
❑ FW Alarm. Indicates that the relay firmware versions are incompatible.
❑ Memory check alarm. Indicates that errors have been detected in the checking of the unit’s memory.
❑ Converter check alarm. Indicates that errors have been detected in the transformers card AD converter.
❑ Converter voltage level alarm. Indicates that errors have been detected in the transformers card reference voltages..
❑ Relay activation alarm. Indicates that an error has been detected in the activation of at least one of the I/O cards’ relays.
❑ I/O configuration error. Indicates that the configuration of the I/O cards does not coincide with the unit’s correct
configuration.
❑ General Vdc error. Indicates a failure in the internal power supply levels.
❑ For each I/O card there is are 5 signals, indicating:
Status OK. Indicates that the card is configured correctly and without errors
Configured & No_detected. Indicates that the card is configured by the user, but not detected in the unit. This may be
because it is not assembled or because it has an error. Equivalent to the current communication error.
Different configuration. The type indicated by the user and the type detected by the unit do not coincide.
No_configured & detected. Indicates that card that has not been configured by the user has been detected in an
address.
Internal card error. A card check error has been received (includes relay check).
Non critical errors
These errors have a limited effect on the device.
❑ RTC clock error. Indicates that the check has detected an error in the real time clock.
❑ Continuous component monitoring alarm. Indicates that an error in the continuous measurement monitoring has been
detected in the transformers card.
❑ Frequency configuration error. This is not a unit failure, but rather a configuration failure. Indicates that the frequency
measurement of the signals being injected into the unit do not match the set measurement, that is, the unit is configured
as 50Hz and the signals which are being injected are greater than 55Hz; or that the unit is configured as 60 Hz and the
signals being injected are less than 55 Hz.
❑ Internal battery failure. Indicates that the data storage battery is below the security levels and that the data may be lost at
shutdown.
❑ Version compatibility error. Indicates that the versions of the unit's firmware are not correct.
❑ Time setting configuration alarm. Indicates that there is an error in the configuration of the unit’s time setting.
Status report:
Figure 254 shows the screen of the PacFactory that show the available check signals.
The example screen shows activation of critical error (HW error), generated by I/O configuration error (card 2 is not detected). It
also indicates Internal battery failure. On the other hand, it shows I/O card 1 is correct.
The procedure will depend on the detected error and the device status.
❑ If the device is off, check that the power supply is correct. If the device is well supplied, contact the technical service
❑ If the device is on but it shows failure, return to the events screen and check which type of error it is
If critical error, with no specific indication, is shown and the error persists after turning the unit off and on,
contact the technical service.
If converter or reference voltage error is shown. Check the Measurements, and if they are correct, turn off and
on the unit; if the error does not disappear, contact the technical service.
If Clock error is shown, synchronize manually. If the error persists, contact the technical service.
If error in the setting is shown, send the settings again. If error persists contact the technical service
They can be connected to merging units or electronic transformers that follow IEC61850-9-2 or IEC61869-9 standards.
The device can communicate through two physical Ethernet interfaces RJ45 or optic fibre. PRP/HSR redundancy and Link failover
redundancy are available.
Available measures and their accuracy are determined by the accuracy of the external SV publishers. These publishers will be responsible
for capturing and sending analog measurements of the lines, generating SV frames through an Ethernet communications network. The
device will only subscribe, among all the available measures, to those that are necessary for their correct operation.
Local measures captured directly through current and / or voltage input channels are allowed. Therefore, some of the measures can be
local and some others sampled values. In order to operate correctly, the measures must be synchronized by GPS.
The following figures show, according to model encoding, the board position.
Figure 256 19” chassis and redundant power supply and communications
There are multifunction protection (MD), distance (ZT), differential transformer (TD), line differential (LD) and control with measure
(CD). The detailed functions included in every family are explained in the user manual of the family.
The device model code includes three additional characters at the end of the model encoding to select the sampled values ports and
the type of measures (see chapter 1).
In these devices, the housing must be Chassis 19" 4U and I/O board 6, 7 and 8 are not available.
CONTROL
HOUSING
ANALOG
MODEL
COM1
COM2
COM3
COM4
COM5
COM6
ETH1
ETH2
ETH1
ETH2
I/O 1
I/O 2
I/O 3
I/O 4
I/O 5
I/O 6
I/O 7
I/O 8
INGEPAC EF XX MODEL INGEPAC EF- - A - A - A
It is necessary to have configuration files (CID) or configuration data of the SV publishers. If the subscription is made using PacFactory
configuration tool, it is mandatory to import the CID files of the publishers and receivers into the same installation.
The sampled values subscription is performed according to the IEC61850 standard (edition 2).
❑ It is only allowed sampled values that comply with the recommended for protection and measurement, indicated in IEC61850-9-
2LE ("Implementation guideline for digital interface to instrument transformers using IEC 61850-9-2" of UCA International Users
Group) and IEC61869-9 ("Instrument transformers - Part 9: Digital interface for instrument transformers") standards, allowing the
subscription up to 8 publishers. All subscribed publishers must use the same standard. If it is subscribed to publishers with different
standards, the CID will be erased because of a non-valid configuration.
❑ After sending a configuration file, the subscription and reception remain operative until the CID has been parsed and fully
validated. Then, the new subscription settings are loaded.
❑ The subscription is made with EC61850 edition 2 and can be used with edition 1.
33.3.1 Configuration
According to IEC 61850 edition 2, the sampled values subscription uses the Inputs-ExtRef in the CID.
The Inputs section defines all external values that will be received from other computers. In this section each ExtRef element refers
to an external data and the element intAddr performs the mapping or association to a data of the device.
In the case of sampled values, the Inputs section is included in the logical node "PHSMMXU". This node has an "OpPhasor" element
associated with each analog measurement of the device. In this way, an external measurement, received through sampled values,
can be assigned to an internal measurement of the subscriber device.
The CID file of an IED with subscriptions to configured SMV messages contains several sections of IEDs. The section of the IED itself
and sections of each merging unit IEDs that publishes the sampled values to which it is subscribed.
These sections of the external IEDs only contain the data model necessary to perform the subscription in order to reduce the size of
the CID file.
For more information about the sampled values subscription configuration process, refer to the configuration software tool's user
manual (energyFactorySuite/pacFactory).
Once the 61850 configuration menu is selected, through the icon , the subscriptions configurator is accessed, valid both for
subscriptions to Gooses and to sampled values. In this case, "Sampled Values" option will be selected, as shown in Figure 259.
Configuration tool shows all the sampled values control blocks available in the installation, allowing a maximum of 8 subscriptions
(Figure 258).
"Data Binding" tab (Figure 261) shows the measurement channels used by the protection (depending on the model), and the current
and voltage measurements (TCTR and TVTR) available in the added control blocks. Each data channel of the protection can be assigned
a data, respecting the type of measurement of each channel, TCTR for intensities and TVTR for voltages.
33.3.3 Monitoring
The LSVS logical node of the data model is used to monitor subscriptions to SV messages. There are 8 instances of LSVS logical
nodes that allow to monitor up to 8 subscriptions to sampled values.
The configuration value in the LSVS logical node is the SvCBRef data (reference to the Sampled Values control block subscribed).
This reference must be filled out when doing the configuration of the subscription, additionally allows to be modified in execution
through an IEC 61850 client.
❑ NdsCom: Subscription needs commissioning. When true, the received SV message does not correspond to the current
subscription settings. Verify that the configuration revision is correct.
❑ St: When true, the subscription is active. Otherwise it is inactive.
❑ SimSt: If true, subscribed SV messages with the simulation bit set are being received and accepted
❑ ConfRevNum: The expected configuration revision number in SV messages.
❑ RxConfRevNum: The configuration revision number received in SV messages.
All this data are mapped in the internal database of the device and can be used in logics of the device and in the local display.
The following table, shows the integer signals. Internally they are mapped to counters
The device code selection has different options for the local measures.
In the "-" option, all measures are received through communications, using sampled values messages.
In the "D" option, depending on the binary file loaded on the analog card, or all the measurements are wired directly to the analog
card's measurement transformers (conventional wiring), or all of them are received by communications in the form of sampled
values. The options are:
The device implements the simulation mode defined in the IEC 61850 Edition 2.
This mode allows the simulation of any SV that is present in the communication network so that two SV with the same information
data will be present at the same moment, the real one without the simulation bit active and the simulated one with the simulation bit
active. If the subscriber is in simulation mode, once it has received the first simulation SV its values will be used instead of the values of
the original SV. Therefore, if the device is in simulation mode, it still accepts 'original' SV messages, and only discards the 'original' SV
messages for those SVs which are simulated.
Simulation mode is enabled with the controllable data "Sim" included in the LPHD logical node in the GEN logical device.
In each LSVS logical node, used to monitor SV subscription, the SimSt status shows with TRUE value that subscribed SV messages with
the simulation bit set are being received and accepted.
When the subscriber is not in simulation mode (GEN/LPHD.Sim.stVal=false) the simulated SVs are ignored. The device keep on using
the "real" SV messages.
When the subscriber is in simulation mode (GEN/LPHD.Sim.stVal=true) the simulated SVs are used for operational purposes. The device
ignores the "real" SV messages after a first simulated one has been received. The corresponding LSVS.SimSt is set when the first
simulated message is received and only cleared when LPHD.Sim.stVal is set to false.
Once the device has received a simulated message for one of the subscribed SV messages, it will not process the real one until the
simulation mode of the device (LPHD.Sim.stVal) is set to false.
If the device is in test mode for the SV, only the measurements received in the message of sampled values with the Quality bit of the
test mode active will be considered valid.
The device can be set to test mode for SV using the "SV test mode On" Setting, included in GEN/LPHD logical node.
The signal "SV mode test Status" is activated when the device is in test mode for SV.
When a loss of synchronization is detected in the sampled value messages, the device can keep on protection or not depending on the
settings.
There is a setting that indicates how the device should operate when sampled values are not synchronized or when local
synchronization is used. It is included in the logical node GEN/LPHD.
❑ Lost SV synchronization. Indicates the behaviour of the device depending on the synchronization type received in the
sampled values messages. The available options are:
Allow local. The device has to see the measures synchronized (Locally or globally) to consider them valid.
Allow only global. The device has to see the measures with global synchronization to consider them valid.
A device subscribed to a single MU, even if the measures it receives are not synchronized, it treats them as measures with local
synchronization.