You are on page 1of 12

Guidelines for inspection

and maintenance of
main circuit contacts
ABB A-line and EH series Contactors
Contents
Page
Mechanical wear 1
Maintenance of contacts 2
Interpreting levels of electrical
contact wear 3
Changing contacts 5
Trouble shooting 8
Mechanical wear
The number of mechanical If so the contactor needs to Contact bounce
operations has a low im- be exchanged. The operational limit of the
pact on the life of the main Another reason for AC-hum contactor is between 85
contacts and their overall could be corrosion caused and 110% of the rated coil
electrical life. However by environmental condi- voltage.
general information con- tions that exceed the con- A voltage variation of ± 5%
cerning mechanical wear tactor specifications. will minimize the contact
could be of interest. Contactors need to be pro- wear. The reason for this is
tected from condensation that higher voltages will
AC-Hum in order to keep the pole increase the speed of the
Pollution of the magnet surfaces of the magnet free electromagnet at closing.
pole surfaces will create a from corrosion. Lower voltages will de-
slight hum coming from the For more specific informa- crease the speed at clos-
contactor in the closed tion regarding this please ing. Both these factors can
position. see the our technical cata- lead to a higher level of
When cleaning, use a soft logue, section: Climatic contact bounce at closing.
and dry piece of cloth. withstand of devices. High voltage and the in-
Hum can also occur if the creased speed at closing
pole surfaces are deform- also contribute to some
ed. increased sound level.
A louder hum will occur if 1
the shading coil is broken
because the magnet will
cause the contactor to
chatter.
Maintenance of Contacts
A contact is not necessar- Filing of contacts Also lack of cleanliness
ily damaged or worn out, Today, with highly devel- when attempting to restore
just because the surface oped contact materials the contacts can influence
is rough and discolored. and high performance the contactor performance.
The contacts in the figure contactors, filing, grinding, Maintenance should be
below may look rather or other attempts to re- limited to inspection of the
inferior but experience has store contacts or contact contacts for the level of
shown that they are better surfaces should be contact wear. This is to
than a new set of con- avoided. ensure a trouble free
tacts. Our experience shows that operation of the contactor
This is because they are this increases the risk of until the next service is
”electrically seated” and causing other problems. required.
make good contact over For example the risk of At the same time observa-
the entire surface. increasing the contacts tions can be made to judge
Based on this it would be resistance is high due to if the contactor operates
completely wrong to remnants from grinding well in the application and
change a contact only by paper, etc. that no signs of abnormal
judging from the appear- wear or damages are
ance of the surface. present on the contacts.

The appearance of contacts after a very low number of operation in an


AC-3 application.

A contact just having reached a ‘good worn in’ level in an AC-3 application.
Interpreting levels of electrical contact wear
Determining the level of General AC-1. (General purpose)
wear on contactors in use The rate of wear is differ- Non-inductive or slightly
is essential from both the ent depending of the utili- inductive loads, resis-
functional and economical zation category or the tance furnaces.
point of view. Premature application of the contac- The closing of the main
service on contactors will tor. For motor control it contacts is relatively easy
increase the overall cost. also depends on the se- as the starting current is
However, service at the lected starting method. equivalent to the rated
right time to avoid inter- The following main utiliza- current of the load. Break-
ruptions or breakdowns tion categories are the ing is made at full voltage,
is more cost effective. most common. the arc has a rather low
level of energy.
AC-2. Slip-ring motors.
Starting, switching off
Typical making and break-
ing is with approximately
2,5 times the rated cur-
rent of the motor (Ie x 2.5)
the voltage is correspond-
ing to the nominal voltage.
Early stage of fixed and movable contacts in an AC-3 application.
AC-3. Cage motors. 3
Starting, switching off
running motors
Closing of the main con-
tacts with approximately 6
to 8 times the rated motor
current, depending on
motor characteristics and
type of load.
Breaking is easier, as the
current equals the rated
Mid-life stage of fixed and movable contacts in an AC-3 application
motor current, and volt-
age is reduced to 17 % of
the rated voltage.
Typical electrical wear
comes from the contact
making operation.
Visual inspection of an AC-3
application normally shows
none or very little material
from the contact tips
thrown out into the arc-
extinction packages.
End of life of fixed and movable contacts in an AC-3 application
AC 4. Cage motors. Contact wear in AC 4 application, making/breaking locked
Starting, plugging, inch- rotor current
ing.
Making and breaking the
motor starting current ap-
proximately 6 to 8 times
the rated motor current.
Voltage is not reduced and
equals the rated voltage of
the motor.
Both making and breaking Early stage of fixed (above) and
are contributing to the con- movable contacts (right), 5000
tact wear. The arc-extinc- operations.

tion packages have an


important role in extin-
guishing the arc. Therefore
material from the contact
tips is in most cases
thrown out in the pack-
ages. See Figure B on
page 5.

Mid-life stage of fixed (above) and


movable contacts (right) 10000
operations.

End of life.
Changing Contacts
Changing contacts on
installed units.
EH/ EK Contactors
(1SFC 380002-89)
Replace all of the main contacts
at the same time.

EH 100 ... 300


Fig. A ● Remove the arc-chute.
● Press out the moving con-
tacts. Lift the contact some-
what to let the contact
easier slide out.
● Exchange the fixed contacts.
● Put in the new moving con-
tacts.

EH 370...800,
EK 370...1000
● Remove the arc-chute.
Fig. B ● Press out the moving arc 5
Typical appearance of contacts contacts, see Fig. 1.
(Fig. A) and extinction package ● Moving main contacts: Lift
(Fig B) when breaking locked rotor the respective clamp and
current (LRC) in an AC-4 applica- press the contact into
tion. neutral position. See Fig. 2.
Remove the contacts.
● Exchange the fixed con-
tacts. See Fig. 3.
● Put in the new movable
contacts. Fig. 1

Fig. 2 Fig. 3

A-Line Contactors – see page 6 ➞


Changing Contacts (cont.)
Changing contacts
on installed units.
A-Line Contactors, A 95-110

4
1
3 2x3
5

ZL95,ZL110
ZLU 95
77 13
x3
6

6 2x3 14
10
9
11
8
x3

12 2x3

5309 660-64
A-Line Contactors, A(F) 145 - AF 750

3 2x3

1/4

1 x4

4 KZ 185...750 8

7
2x3
x3
5
x3
6 7
KZ 185...750

10
9

2x3

11
2x3
1/4
12

13
x4

1SFC 380 003-89


Trouble shooting
Some examples of common Restarting with motor delta is important. If no
reasons for excessive idling timer or other device is
contact wear and shorten- ● Attempting to restart the used to get an idle time
ed contact life: motor before the motor between opening of the
Voltage drop during has come to a full stop star contactor and clos-
start up of the motor will cause a current peak ing of the delta contac-
Voltage drop to less than that theoretically can tor, there is a risk that the
85 % of nominal voltage reach twice the current arc inside the star con-
for 5 to 10 ms can be compared to starting tactor could remain and
enough for the contactor the motor from a stand- create a short circuit.
to start opening. still.
If the elapsed time is too
Also, other disturbances in This can result in welded
long, the motor starts to
the control voltage could contacts.
decelerate and the delta
be responsible for this STAR DELTA (WYE- closing will create a higher
problem. current peak than ex-
DELTA) STARTERS
The result of these voltage pected. This can result
Change over time
problems can be increased in welded contacts.
between star and delta.
contact wear and also lead Generally the idle time
to welding of main con- ● Setting the change over should not exceed
tacts. time between star and 50 ms.
delta too short will not
8 ...related to different
allow the motor to reach
starting methods.
80-90% of its nominal
DIRECT ON LINE speed. This will cause the
(ACROSS-THE-LINE) star contactor to break a
MOTOR STARTING higher current than ex-
Current peaks due to pected. If the starter
heavy duty starting stays in the star position
● If the application requires for too long of a period;
a high level of torque this will increase the
during start-up, for ex- stress of the star con-
ample a fan or a pump, it tactor because the star
is important that the con- contactor is mainly sized
tactor’s making capacity for the short time current
and short time withstand rating.
current are capable of
handling the starting cur- ● The change over time
rent and current peak. between the star and
1 Terminal bar
2 Moving contact 5
3 Fixed contact
4 Operating coil 7
5 Armature
6 Core 4
7 Coil terminal
6 2
3
1

7 4

6 5
ABB Automation T echnology Pr oducts AB / Control SE-721 61 Västerås, Sweden
Telephone + 46 21 32 07 00 Fax + 46 21 12 60 01
Pamphlet 1SFC 101001M0201, December , 2001

You might also like