Professional Documents
Culture Documents
\~1,1 \ , /|sient
llAlE=IO
I.0 11 lll I l 111\ 1} l current, is also independent of where the voltage is
-g1 , -. {il 111 1# 1 , \ ,/ll
{ applied.
1
/ \tV /{, ' o } ,0JX e \1 XThisof reasoning,
\l8t1 1, \ o \X J \\t|o A showing that in linear circuit, the loca- a
'\ 'V l I I 'v1 R A l, lltion
1\ 1 1 / ' l the resistor does not affect the periodicity of the
circuit, combined with the differential results for analyzer
the nonlinear circuit, indicate that this may well be a
general conclusion. It has been known in practice that
intervening or secondary loads prevent this overexcitation
tVC=0.45 U (a) condition, but the effect had not been previously investi-
gated quantitatively.
P=1.sA5 D. Conclusions
11W=0.75 I \ / } 10 An unloaded transformer, operating at normal densities,
Xif exited through a series capacitor of reasonable reactance,
is susceptible to conditions of large distorted magnetizing
-11
-K/ 1w ICcurrents.
\'-11 These abnormal conditions can be restored to
normal by the addition of a suitable shunting resistor to
(b) the capacitor, as indicated by figure 7, or by the locating
of a certain amount of load on the load side of the capaci-
tor.
The resistor shunting the capacitor, introduces addi-
/E=\06A tional losses. However, in general, this loss is less than
-,:i\0.15y \ , \ per
10 { of the normal line loss and this can usually be
f\ >cent
justified by the improvement in voltage regulation. More-
v. -' / t j ' / '' over, since the presence of the abnormal condition depends
"tVC=O-033
\ / \ /on the initial transient, it may be eliminated by shorting
out the capacitor only while the starting switch is being
Figure 4. Effect oF applied voltage on the apparent perio- closed, or by having the resistor connected only during the
dicity of exciting current energizing period. The shorting switch or temporary re-
sistor may readily be arranged so as to function automati-
r1 = 0.049 1/C = 0.214 (a) E = 1.0 cally whenever the abnormal condition tends to develop.
Rc =o Magnetization curve 1 (b) E = 0.75
L =0.197 a=0 (c) E=0.6
Section 11-Hunting of Synchronous Machines
between the transformer and the capacitor, was also in-
vestigated on the differential analyzer. The critical points A. General
obtained with this circuit agreed very well with the points
for the same resistance when it was shunting the capacitor, An electric power system consists in general of a group
indicating that it made little difference where the resistor of interconnected synchronous machines together with
was located. impedance and induction motor loads. Any such system
From figure 2 it may be seen that the 2 locations of the is subject at practically every instant of its existence to
resistor are equivalent to 2 locations of the applied voltage, disturbances caused by changes in load, switching, pul-
the circuit remaining unchanged. Further, in the canon- sating loads, pulsating driving torques, changes in excita-
r 2CURVE 1
The critical angles recorded in table I are the load angles No capacitor.i.n. ..... r2=1, X4 = 1. 07, r4 = 0.049. 1.88
1i-&i' where 6, is found as described in appendix C and a1' is Capacitor in number 3.... r2 = 1, x4 = 1.07, r4 = 0.049...........2.67
the no-load angle of machine 1 referred to the infinite bus r1See=figure
0
9 for circuit.= 0.023
r3 xg = 0.65 X3 = 0.0516
3. The oscillation of machine 4 was neglected (i.e., k = r2 =co or 1 r4 = 0.05 X2 = 0 Xg = 0.20 or 1.07
0), since it was assumed that the machine t eing investigated xc = 0.105 = capacitive reactance
would have the largest amplitude of oscillation. Also it Note: xq and X4 include both line and machine reactanees.
was found that the necessary load angles were only slightly
affected by the operating angle 64 of machine 4. It is
therefore possible to use the simplified formula (8b.1) for modes of vibration corresponding to the 2 principal natural
nearly every case by simply substituting the value of frequencies of the system of figure 9, or to any impressed
Z3 (Z3 = r3 + jx3) paralleled with Z4 for the Z3 of equation forces, can be very simply calculated if the inertia constants;
(8b.2). of the machine are known. This will not usually be neces-
A more exact study of a system may be made by taking sary, however, since sufficient information can be obtained
the amortisseur windings of the machines into account from a study of the system neglecting amortisseur windings
and computing the damping coefficients by the methods and a knowledge of the general effects of such windings.
of reference 25 for every probable mode of vibration. The (See, for example, reference 19.)
8 + 0l
1 T gl97 e0.497 oi gnormal
tion excita
as a function
Section Ill-Self-Excitation of Induction Motors
MAG. c
- 'CURVE~2 _ OF RC and I1/C.
A
A
General
eea
o '] /7
rl "| Area below each It is well known that an induction machine will operate
-- Icurve is normal, as a generator and that such operation depends on the
L Area aove each
supplying of excitation from either a synchronous machine
4 - - - curve s abnorm or a capacitor even though in case of the capacitor the
4 - ! hG \ - operation has not previously been very well understood.
\|\\l | / SMAG. Now consider an induction motor supplied through a
z
D __ w R line containing a series capacitor. Then in addition to the
e \ / / Figure 8 (below) currents flowing due to normal operation of the motor, un-
2t \ tt / r 1 8 Magnetization der certain conditions the motor may act as an induction
curves. Curve 2 is generator of current of lower than normal frequency. This
curve I with cur- low-frequency current is limited only by the impedance of
rent scale multi- the supply circuit at the low frequency, and may reach
o 0.2 .- 0.4 0.6__I pliedby3
pidb relatively large values. These large low-frequency cur-
CAPACITIVE REACTANCE YC rents manifest themselves not only as current surges and
voltage swings but also as strong oscillations of the motor
1.6e rotor caused by the large pulsating torques produced.
1.4 XtiXl X atm00
- --0 lfl25H 1111111 I This phenomenon of self-excitation will not always take
1s.0 ___L2T EjIIlUlllllll 11|111 line or shunt resistance, or by judiciously locating the
Z0.8titittiji902 - ~~~capacitor. It may, moreover, be calculated with reason-
Z0.6tX 0. z;tXz iH ttx 111111W1^ 1111111111able
t 9 tt0 ] ! 11{211 [
certainty and accuracy by equations given in ap-
J] {SlS11]pendix C, if the circuit constants and operating conditions
Figures 10 to 13 show the regions in which self-excita-
0o0 .1 .
PER UNIT CURRENT -PEAK
. tion is likely to occur for the case of a purely induction
motor load. Figures 10 and 11 show the effect of series
980 Butler, Concordia~-Series Capacitors ELECTRICAL ENGINEERING
Xq Figure 9. Circuit at normal load, a sustained overload may produce self-
El r1 d INFINITE diagram of 2 syn- excitation.
rx BUS chronous ma-
E4 rx E chines connected C. Calculations and Test Results
X2 LOAD to infinite bus and
impedance load In order to check the theory offered for this so-called
"self-excitation phenomenon," tests were conducted on a
miniature set-up, in order to get good control of the vari-
line resistance in preventing self-excitation, while figures ables. A 3-phase 3/4-horsepower wound-rotor induction
12 and 13 show how a resistance in shunt with the capaci- motor was connected to a power source through a series
tor can eliminate the phenomenon. For any practical capacitor and 0.39 per unit external reactance. The
case the reactance of the series capacitor will of course be values of series capacitance were varied over the complete
much less than x', probably about half of x', since x' is range of self-excitation, and the corresponding value of
the short-circuit reactance of the motor including line shunting resistance to insure normal operation was de-
reactance and since the capacitor reactance will usually termined. These tests results, and corresponding calcu-
be no greater than line reactance. Therefore figure 14 lated points on the curve are shown plotted in figure 16.
is given, showing the shunt resistance necessary to pre- The agreement between test and calculated values was
vent self-excitation in the useful range of capacitance, for very gratifying. It is felt that the equations offered can
2 sets of system constants. be used with confidence in predetermining these regions
The values of shunt resistance given in the curves will of abnormal operation.
usually be conservative because the effect of series line The motor was tested running light, hence the speed was
resistances and machine losses, which themselves tend to taken as unity to simplify the calculations. The armature
damp out self-excitation, has been neglected. Equations resistance of the motcr and external circuit was 0.10 per
are given in appendix C which take both shunt and series unit. This high circuit resistance is the reason for the
resistance into account and which should be used to ana- curve in figure 16 intersecting the a = 0 point at such a
lyze any specific problem. These are based on the an- high value of x,. The rotor resistance was likewise very
alysis presented in reference 20. Figure 15 shows an ex- high, hence the motor had a correspondingly small rotor
ample of how the value of a necessary for stability de- time constant. The small rotor time constant gives the
creases with increasing line resistance. motor a greater tendency to self-excite as shown in figures
10 and 12.
B. Discussion of Results In view of the type of motor tested, that is, one having
high resistances, these test results should not be generalized
Figure 10 shows that as long as the capacitive reactance as significant of normal motor performance.
is less than half of the system short-circuit reactance, The line of demarkation between normal operation and
self-excitation will not occur for a normally loaded group of
induction motors. This is because the line resistance is
usually great enough to damp out any tendency to self- 4 - - 1
excite. However, as soon as a certain critical value of - - 1
short-circuit reactance is exceeded the amount of series 1.2 - - | - --
resistance required begins to increase rapidly. This crit- - - - - . - -
ical value of reactance is, of course, a function of the motor -. - - -S ll
characteristics and the impedance of the connected circuit. /x UNSTABLE
If the line is relatively short (i.e., if its reactance is less w
than the motor reactance) it may be compensated more
- /__i.
/
than if it is long, unless a shunt resistor is added to pre- ( 1|
vent self-excitation. 3 06 17.14 { -
Figure 11 shows that as the motor speed decreases the - .
region of self-excitation moves down along the xc ordinate. 04 L
That is, the tendency to self-excite occurs at a lower value
of capacitive reactance at lower motor speeds. Such low 0.2
To= 171.4
speeds occur during starting and during periods of over- UNSTABLE
load. We should thus expect some oscillations as the motor L ' tiL 11 711 I llIi 7T]i
comes up to speed. This iS especially true if a starting 0) 10.4 0.8 1.2 1.6 2.0 2.4 2.87a 32
resistance is- used in the rotor, as figures 10 and 12 indicate 2xt SERIES LINE CAPACITIVE REACTANCE = XC I2x
that an increase of rotor resistance increases the tendency Fgr 0 efectto fidcinmtr iksre
to self-excite. In general it will not be necessary to elimi-
nate these transient oscillations. Actually, in service capacitors
when the system behaves correctly under normal operating Showing series resistdnce required for Stdble operation aS d function of
conditions no trouble during starting has been experienced, the line capacitance and showing effect of varying rotor resistance
If, however, the system does not have very much margin x' =0.4 x = 3.24 To 171.4 and 17.14 X=0.975
AUGUST 1937 Butler, Concordia-Series Cap?acitors 981
self-excitation was very sharp up to x, = 0.6. Calcula- of a found for each value of x,. The current wave was
tions and tests both showed this. Beyond xc = 0.6 the watched through an oscilloscope and self-excitation could
calculated curve became more difficult to determine be- be readily recognized by a change in the wave. In the
cause it seemed to be very broad in the upper regions, lower regions below xC = 0.6, the phenomenon was more
that is, it was difficult by ordinary slide rule methods to violent and critical. A change of a few per cent in the
get a smooth curve, indicating the critical region was not value of shunting resistance R in this region, would be
very sharply defined. Tests bore this point out in the up- sufficient to change the circuit from normal to a definite
per regions. The test points plotted are the largest values state of self-excitation. The region of self-excitation in
the practical and useful range of xc can be readily recog-
nized by calculation since this range is below xc = 0.6.
1.4.- - - - - - Figure 17 is an oscillogram of the current flowing in one
1.4 _
ZI
0.2. I
D. Self-Excitation of Synchronous Machines
A B C ID
0 I__ It has been stated above that in circuits containing
0 .0.4 0.8 1.2 1.6 2.0 2.4 2.8 3.2 series capacitors and induction motors, there may be a
SER IES LINE CAPACITI VE REACTANCE- XC
tendency to self-excite and that in circuits containing series
Figure 11. Self-excitation of induction motors with series capacitors and synchronous machines there may be a
capacitors tendency toward hunting. It is evident, however, that
the tendency to self-excite (that is, to generate amplifying
A--w = 0.2 5 Bow = 0.5 C-or 0m707
= D-or 1e 0 current oscillations even though the rotor inertia prevents
x' = 0.24 x = 3.24 To = 1 71.4 hunting) exists also in synchronous machines. It has been
possible to obtain a satisfactory explanation of operating
1.4 ... experience with synchronous machines on the basis of
| | |
... I l hunting alone but it is conceivable that under certain
1. lconditions purely electrical self-excitation may be en-
countered.
1.o C
t w /W < X <
N I I 11|
While
tF i this
phenomenon
matter has not been thoroughly studied, the
T S1is familiar in relation to the determination of
- - -.I
, I -\ I -} the line charging capacity of synchronous generators.
V0.8 41>1=4+ + t+ < |\| S. B.Crary,2M. Takahashi,22 and Y.H.Ku23 have made
X 17.4 Xa study of this subject and have shown the tendency of
0iUNTAL line resistance to reduce the self-excitation. By means of
the theory given in reference 20, it may further be shown
0
171.4 - - .that a resistance in shunt with the capacitor may also be
0.4>tW 8 used to eliminate the self-excitation (see appendix D).
I.W \ Figure 18 shows, for the same generator as in figure l of
0.2 - -. - reference 21, the effect of shunt resistance.
-+-UNSTABLE - - - - - - Since the effect of rotor circuits in addition to the main
o - ; 1 -I - - - - - field has not yet been determined, no definite conclusions
SERIES LINE CAPACITIVE REACTANCE -Xc can be drawn from this curve, but it is believed worthwhile
to point out the existence of such self-excitation and to
Figure 12. Self-excitation of induction motors with series indicate that it may be corrected exactly as in the case of
capacitors induction motors. The phenomena of self-excitation and
Showing resistance (in shunt with the capacitor) required for stable hnigmyo oreeitsmlaeul n r
operation
as a Fucto ofteln-aaiac n hwnfeto mutually dependent to a limited extent. Their mutulal
varying rotor resistance effects have not yet been studied exactly.
x'= 0.4 x =3.24 X=0.975 r=o The ideal procedure, from a mathematical point of view,
982 Butler, Con.cordia-Series Capacitors ELECTRICAL ENGINEERING
1.2--.--
1 Figurel14. Self. 60 -- -
1.2- F Texcitation
= W W T TTofTFin -__
tt
t tttttttt
-- Z < duction motors
Xt
iX
ttXt.-8
X e $ WW
X with series capaci- 20 t
tors Lu
12-I-0.-6 _ Showing resistance \
io
8 (in shunt with the 8
0.4 .capacitor) required 6
.~~~~~~~~~\~~~~~~~~~~~~~~ ~~~~for stable operation CURVS_
0o2 ISd function oF the Z4
0.l _
___
-A/B -
i
- - - -
1
j 4 4 4line capacitance For
various systems
x=0.4T0=l
x02-4 T 17
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7. 0.8 0.9 I.0 x = 3 r 0 Z \ x=0.16,To=171
SERIES LINE CAPACITIVE REACTANCE -Xc 9x0.4,To=I7.I_0
co 0.975 ML
Figure 13. SelF-excitation of induction motors with series x' =0.4,To=t71
capacitors 0.6 H CUR'VES _ x'=0.4,To= 17.1
Showing effect of varying motor speed 0.4
A-w = 0.25 B- =, 0. 5 C-cX = 0.707 D-X = 1.0
x' 0.4 = x = 3.24 To = 171.4 r=0 xl=0.6,To=I7I
0.2
0 0.2 0.4 0.6 0.8 1.0
RATIO CcIx'
would be to set up the equations of motion of the circuit
including both electrical and mechanical motions, and
then to find out whether the system as a whole was stable R = resistance in shunt with the capacitor
or unstable. This method brings out very clearly the basic k = 6m
identity of the phenomena of hunting and self-excitation abn
but is, from an engineering point of view, at present im- m, n = subscripts given to currents, voltages, impedances, and
angles in relating them to certain machines and circuits
practicable because of the excessive labor involved in the as used in section II
calculations. It is believed that the results obtained by
the approximate studies are practically the same as would
be found by the unified method. Appendix A-Derivation of Equations
Nomenclature Set Up on the Differential Analyzer
The single-phase circuit analyzed is represented in figure 2. The
Section I magnetization curves shown in figure 8 are the 2 iron characteristics
that were investigated and discussed in the body of the paper.
E = applied voltage, maximum value The differential equations applying to this circuit are:
I = time in radians
a = phase angle of applied voltage E sin (t + a) = r1ii +L- + (il - i2)dt + (la)
ri = line resistance dt C dt
ii = line current 1 C
i2 = current through Rc i2Rc = C J( i - i2)dt (2a)
Re = resistance shunting the capacitor
L = line inductance Rearranging and integrating (la) into a form applicable to the
c = capacitance differential analyzer, there is:
4' = fluxlinkage rr 1 C 1
= voltage across capacitor Li, +4' = ) [E sin (t + a) - rii- C J (i - i2)dtjdt (3a)
Sections II and III The schematic hook-up of the analyzer, giving the solution to
E = internal voltage equations 2a and 3a is shown in figure 3. The input voltage was
ed, e5 = direct and quadrature axis terminal voltages actually not cranked in by an operator. Instead an auxiliary set-up
4'd, 4'.
direct and quadrature axis flux linkages
=
was made that gave the solution to the differential equation
id, ij= direct and quadrature axis currents d2x
Xd, Xq = direct and quadrature axis synchronous reactances dt2 - x (4a)
(section II)
r =
stator line resistance per phase which is a sinusoid, and it was impressed automatically into the
a =angle of voltage E from some reference point hook-up. An operator was needed to crank the current into the
0 =
angular displacement of rotor system by keeping a pointer representing 4', the linkage, on the
XL p6 =rotor speed
= linkage-current characteristic. Values of applied voltage, linkage,
Xc =
line series capacitive reactance capacitor voltage, and total current were plotted by the output
To rotor time constant with open-circuited stator tables.
x = direct or quadrature axis synchronous reactance of induc- The procedure used to determine the points on the resistance-
tion motor including line reactance capacitive reactance curves of figure 7 was as follows. The differen-
x'= direct or quadrature axis transient reactance of induction tial analyzer was started at a point corresponding to application of
motor including line reactance the voltage at the zero point of the wave and the several dependent
a = xc/R variables of the circuit plotted automatically on an output table.
'f6,~ + (I - k) - (MS, cos 5~ - M71 sin 54) 0.8 THIS AREA APES FOR FIELD
a -, E
+ ( - t ) (MIf cos 4 M7sin CIRCUIT D OR CLOSED
X2 ra 0 x2 he
r2 + r4 -r4 X, X2 + X4 -X4
x2 0 r3 72 ° I22+ X22
X2 -X3 0 r2 -ra The right-hand side of equation 8b.2 is recognized as the ratio of
Ms17= -r2 0 X, X2 0 (6b.4) the real to the imaginary part of the transfer impedance from ma-
r2 ra -X2 X3 chine number 1 to the infinite bus ifsx is used for the machine re-
[r + X4 X4 r4 72 + 74 74 actance. Further, if the shunt load is removed (Z2 = x) it checks
the criterion of reference 11.
In the special case for which the motions of the 2 machines are If the shunt load is removed but machine number 4 is kept, the
the same (k = 1), equations 5b reduce to form of equation 5b is unchanged but equations 6b are reduced to:
tan 5, = _ M-1
MJI
(7b) -r3 x, + xa xabl
- Mai = X4 -rl N (9b. 1)
but this is not likely to be a useful case. If k = 0, there is no sim- r4 xg X4
plification. Xa ri + rs r3
If machine number 4 is eliminated by letting x4 and/or r4 be - MG, = -X4 r -7r4 (9b.2)
infinite, M71, Ms, become negligible compared to M31, Mal, and r4 Xg X4
equations 5b reduce to:
-3 ri r
X2 7r 7 l -Al'71 = r3 xg X I (9b.3)
X2 + X3 r3 r2 +r3 -r4 Xg +X4 -X4 1
tan
rg =
L
__
X (8b.1) - Mg, = -3x3 (9b.4)
Xii ri -r2
+ 74
73
x4 4
i
+q 3
- r2 XI -X2
tr2 + r3 X3 X2 + x3 If in equations 5b E4 = 0, or if x4 and/or r4 = there is,
6, = -tan--'- ( lOb)
Figure 1 7. Starting and self-excited current of induction Ai4j = M21E, + M,E3 cos 5, - M6,E3 sin S, +
motor with series capacitance in primary circuit MnE4 cos (a, - 54) - M,E4 sin (51- 64) (llb)
AUGUST 1937 Butler, Concordia-Series Capacitors 985
Then: tions (see reference 20):
-M2,/A is the imaginary part of the driving point admittance (p + a) [ed - Pd + rid + (L4tq I + Xcid = -[e5--;t + riq -@d
at machine number 1 (p + a)[e - Pq + riq - (A'dI + xciq = -w[ed P-d + rid +wkq]
M311 A is the imaginary part of the transfer admittance from i to 3 (Ic)
M61! A is the corresponding real part where, for an induction motor with completely symmetric rotor and
M71/ A is the imaginary part of the transfer admittance from 1 to 4 stator,
M81! A is the corresponding real part {'d = X(P)id
{f= -X(p)iq(C
(2c)
It follows that since
and
real
. = _ *
real
. l ~~~~~~~~(12b)P xop
xTp + x
)maginarYadmittance (imaginary)impedanceT 1xb x'Top (3c)
we have *
Substituting (2c) in (1c) and rearranging; there is:
_ M61l = ( imaginary
real ) impedance 1-3 (13b) {(p +r}ia) [px(p) ++e)ed
r] + xc-wx(p)} c4
id-< (p +a)x(p) + px(p) +
Ms, q= -(p (c)
+eq
and co{(p + a)x(p) +px(p) + r}Iid ± (P + ot)[px(p) + r] + X, -
M81 ( real ( co 2x(p)}iq = -ed - (p + a))eq
__
M71
=
imaginary/impedance 1-4
1(14b) and for constant rotor speed the characteristic determinant (the
denominator of the expression for current as a function of voltage),
All of these transfer impedances and admittances are computed for
a direct-axis current in machine number 1. Also, since it is only the A = { (p + a) [px(p) + r ] + xc - c2x(p) 1 2 + @2 { (p + a)x(p) +
relative magnitude of the components of impedance which enter into px(p) + r }2 (5c)
the final criteria, the impedances calculated entirely by means of
xq can be used. That is, even though Xd occurs in A and affects tita
the true values of the impedances, A does not appear in the results. p, there is:
The method of extension to more than 2 machines is evident from (Top + 1)2A - A' = p6(x'2T02)
equations 2b, 3b, and 4b. + P'[(2x'To)(x + ax'T0 + r TO)]
+ p4[(x + ax'To + rTO)2 + (2x'To) X
Composite Loads (ax + W2x'To + r + arTT, + xcTO)]
+ pI[2x'To(x, + w x) + 2(x + ax' To + rTTO) X
If the shunt load of figure 9 is a composite load'8 of any kind all (ax + 2x'TO + r + carTo + xcTO) ]
W
the criteria given here may be used unchanged if r2, x2 are defined + p2[(ax - Wo2x'To + r + arTo + XCT,)2 +
by the relation: 2(x + ax'To + rTo)(xc -co2X) +
de2 (ax'TTo + 2x + rT, )2c2 + 4W2X'TO,(ax + r)]
= r2 + jx2 (15b) + p[2(ax - C2x'T,O + r + arTo + x,TO) X
di2 (XC- 2x) + 2W2( ax'To + 2x A- rTTO) X
W
at the load voltage e2. (ax + r)] + (xc - w2X)2 + (aX + r)2w'
(6c)
Equation 5c is of the form (A' = a2 + b2) and so may be factored
Appendix C-Self-Excitation of Induction Motors as [A' = (a + jb)(a - jb)] thus at once reducing the order of the
equations to be solved by half. However, this is accomplished at
The object of this appendix is to present criteria to determine the the price of introducing complex coefficients. The real parts of the
limts f sablopraton f iducionmotrs ithseres .ol
it s line caapai-. roots of the 2 factors are identical in pairs; the imaginary parts
eequal and opposite. Thus only one factor need be considered, but
tors. Under certain conditions of load it is found in practice that
it is found that all methods for determining the character of the
there will exist undamped current pulsations of apparently low
roots or solving the equation require about the same amount of
frequency and large magnitude. These pulsations are here con-
sidered to be caused by undamped or negatively damped (ampli- work as doublmg the order and in effect obtaining equation 6c
fying) free electrical oscillations. Thus, to determine whether a
given (electrical) system is stable or unstable the natural currents a + jb = x'Tp'3 + [ (x + ax'T, + rT,,) + jco2x'T,,]p2 +
are examined. The time variation of these natural currents is [(x,T, - cw2x'T, + ax + r + arT,) + jw(2x + ax'T, +
specified by the roots of the characteristic determinant of the system. r To) ]p + [(xc - W2x) + jw( ax + r) I (7c)
If the real part of any one or more of these roots is positive the
system is unstable since then the corresponding component of the with a similar conjugate expression for (a - jb).
transient current is amplifying rather than decaying and will tend It will be observed that equations 6c and 7c are almost symmetrical
to increase indefinitely until limited by changes in the circuit caused in r and a except that ca has sometimes the coefficient x' and some-
by saturation, slowing down or oscillating of the motor rotor, etc. times x, which destroys the symmetry. It is therefore expected
Thus, it is not necessary actually to solve for the roots but only that all the conclusions and curves obtained will be very similar if
to find the signs of their real parts. To find the actual frequency the effect of shunt and series resistances are investigated separately,
of the unstable oscillation it is necessary to solve the equation, using a as the variable in case of the shunt resistance. Here a
which is of the sixth degree (or of the third degree if expressed with may be thought of as the reciprocal of the time constant of the RC
complex coefficients) and has in general 3 conjugate pair of complex circuit considered by itself. It is the negative of the coefficient of
roots or 3 natural frequencies. time in the exponential solution of the RC circuit equations.
Anlyi APPROXIMATE CRITERION FOR INSTABILITY
It will be found that a very simple and sufficient condition for
For an induction or synchronous machine with capacitance and instability is that the coefficient of p in equation 6c be negative.
resistance in shunt connected to the terminals, there are the equa- That is, if this coefficient is negative the system is surely unstable,
4 To
Wtt2 (axC + r ) l/2 determined by equation lOc. Figure 11 shows the effect on the
- u2(XXla2 + r2) - 2 (3x + x') ( + (8c) value of series resistance required if there is no shunt resistance,
2 To while figure 13 shows a similar curve of a versus xc if r = 0.
Equation lOc also provides a means of determining quickly an
The 2 values of xc obtained from (8c) for a given system determine aprxmtepesinfrhevleoarquedoeiiae
the limits of a region which is theoretically surely unstable. instability coprequired
to eliminate
If a set of circuit constants is selected, leaving r and xC free, then the radical in equation 10c to zero, which locates a point
r is varied and x, computed, a region is outlined as in figure 10 equating
(dashecurv).Thifigueshos functionofvery close to the maximum of the a versus x, or r versus xc boundary
(dashed curve). This figure shows r as a function of xc if there iScuv.Te
r as a
no shunt resistor (a = 0). If the effect of shunt resistance alone is curve. Then
determined, letting r = 0, the dashed curve of figure 12 is obtained. a (x + 3x')r' 1
Equation 8c outlines the unstable region very close to the true ku/max =-4xx' - r' +2 4xx' - _ r'r x
boundary over most of the range of instability. However it indi-
cates that instability lies wholly in the range,
-\// + 3x'2'2+ (4xx' - r")[(X X')2- 4r'2] (12c)
Equation lOc shows that as the speed uo is varied the scales of the (XC- ux) + juo(ax + r)(5)
r versus.-r or a versus xc diagram are simply changed so that Pr [(xc-u13x' + ar)]?0 + aX + r] + ju [(aox' + r)T,, + 2x](
XC is proportional to u> (11 c) A further obvious simplification is obtained by neglecting the
r and a areproportional to u
~~terms in the denominator which do not contain ls0.
If P, = Pr + jq
* f otr esstnc i zro(T =o~ ter i n istbiit. Aloi.T then Pr is the decrement factor and (uo + q) the frequency of the
or X = 0 there is obviously no instability, possibly amplifying oscillation. The frequency is u + q rather than
r = 0.035 in figure 10, the 'frequency is found to be very nearly ~~~~~~~~~~~4.NOt RieS CAPACITORS OrDSRUI FeER C Dudley
WHY NOT SERIES CAPACITORS FZOR DISTRIBUTION FEEDB:RS? C. L. Dd
0.7 times normal (rotor speed). At values of xc > x' the frequency and E. H. Snyder. Electrical World, volume 103, June 30, 1934, pages 942-5.
is always very close to, and slightly less than that corresponding to 5. SERIES CAPACITORS, R. E. Marbury and W. H. Cuttino. Electric Journal
the rotor speed. volume 33, March 1936, pages 145-9.
M. Takahashi25 has an approximate solution of equation 7c for 6. LARGEST CAPACITOR BY INSTANTANEOUS RESPONSE ELIMINATES STUBBORN
FLICKER,Electrical
the case of no shunt resistance and has determined regions of self- Lewis. ORIGINATING IN INDUSTRIAL LOAD OFF7,RESIDENTIAL
World, volume 106, November
FEEDER, J. J.
1936, pages 3488-90.
excltation for this case. His results are in general agreement with
7. SERIES CAPACITOR PROVES ECONOMICAL, A. E. Perreten. Electrical West,
those given here. volume 77, December 1936, page 48.
8. IMPROVED VOLTAGE REGULATION WITH SERIES CAPACITORS, R. C. Buell.
General Electric Review, volume 40, April 1937, pages 174-9.
9. EFFECT OF SERIES CAPACITORS UPON STEADY STATE STABILITY OF POWER
Appendix D-Sel-Excitation SYSTEMS, E. S. Allen and J. L. Cantwell. General Electric Review, volume 33,
of Synchronous Machines May 1930, pages 279-82.
10. DIFFERENTIAL ANALYZER ELIMINATES BRAIN FAG, Irven Travis. Machine
Design, July 1935, pages 15-18.
From equations 15 of reference 20, the equations of a synchronous 11. STABILITY OF SYNCERONOUS MACMINES As AFFECTED By ARMATURE
machine operating at synchronous speed, with only one rotor wind- RESISTANCE, C. A. Nickle and C. A. Pierce. AIEE TRANSACTIONS, volume 49,
ing, with series capacitance and resistance in the armature circuit, June 1930, pages 338-350. Discussion, pages 350-1.
and with additional resistors shunting the capacitors, are: 12. EFFECT OF ARMATURE RESISTANCE UPON HUNTING OF SYNCHRONOUS
MACHINES, C. F. Wagner. AIEE TRANSACTIONS, volume 49, 1930, pages
(p + aX)(ed -POd + rid +=,6) + X,id e -p4q + ri, -{d 1011-26. Also refer to discussion of reference 9.
(p + a)(e. P4Pd P'Pq+ri
(P + )(eq + ri, --bq)
-
'P) + Xciq
Xtq = ed P'qd rid
+PV'd
ed + rId 'Pq - -
(d)
13. LEs RhSEAUX DE TRANSMISSION D'ENERGIE (a book), Jean Fallou.
Pages 390-408.
where 14. P. Boucherot, Comptes Rendus des Sgances, Academie des Sciences, volume
4'd -Xd(P)id T= P +
Xd'T.P + Xd. 170. Paris.
= 1 (2d) 15. Jean Fallou, Revue Ginirale de L'Electricite, volume 19, June 1926, page
987.
.1.
q== *x.(pM =-Xq$q
-Xqr$q -x =
(3d)
16. TMEORY OF ABNORMAL LINE-TO-NBUTRAL TRANSFORMER VOLTAGES,
C. W. LaPierre. AIEE TRANSACTIONS, volume 50, March 1931, pages 328-42.
If (ld) are solved for the currents id, i4 in terms of the applied 17. STUDIeS IN NoN-LINEAR CIRCUITS, C. G. Suits. ALEE TRANSACTIONS,
voltages ed, eq, it is found that the operational common denominator volume 50, June 1931, pages 724-32.
of the 2 formulas for current is: 18. STABILITY COMPOSITE
STEADY STATE OF
ENGINEERING, volume 52, November 1933, pages 987-92.
LOADS, S. B. Crary. ELECTRICAL
A' = P5xqXd To 19. FIELD TESTS TO DETERMINE THE DAMPING CHARACTERISTICS OF SYN
4Xqd+rox d)+2TxX CHRONous GENERAT6RS, F. A. Hamilton, Jr. AIEE TRANSACTIONS, volume
+ p4[2xqXd' + XcXq+ Xd') + 2a XXoxrxd
1[(2XqXd'
] 51, September 1932, pages 775-9.
Two THEORY OF SYNCHRONOUS MACHINES WITH ANY BALANCED
+ P + Xe Xq + Xd } ) 7'e + r(xd + Xq + ri'0) +
20.
a(2xdXq + Lxaxqd' To) + 2aerTe(xq + Xd )] TERMINAL REACTION
IMPE:DANCE, C. Concordia. Submitted for publication.
+r P1I2XdXqz + XC(Xd + xqz) + r( To4 2xc + xq + Xd' I + r) + 21. Two REACTION THEORY OF SYNCERONOUS MACEINES, S. B. Crary. ELEC-
a(C ToXe Xq + Xd' } + 2 TeXqXd' + aFXdXq) + ar(2xd + TRICAL ENGINEERING (ALEE TRANSACTIONS), January 1937.
2Xq + 2 Tar + lisa { xq + Xd' )1] 22. TRANSIENT PEENOMENA OF AN ALTERNATOR UPON CONDENSI'JE LOAD,
+ P [ To(Xc -xq)(xc -Xd') + rt(xd + Xq + 2xc + r TO) + M. Takahashi. Researches of the Electrotechnical Laboratory, Tokyo, Japan,
c4x , Xd+X XX iqdT) + s(xTe+2 23. TRANSIENT ANALYSIS OF ALTERNATING CURRENT MACRINERY, V. H. KU.
ctIIXd+tXQA + err?0O Journal of Electrical Engineering, China, volume 3, number 4, AugUSt 1932,
+ [(Xd - Xc)(x - xc) + r1 + c11XdX5 + 2arxc + (ar)1] (4d) pages 179-206.
If the same generator as in reference 21 iS taken, with r = 0, and 24. ADVANCED RIGID DYNAMICS (a book), E. J. Routh. Page 168.
the stability of the system as affected by a is studied by means of 25. Two REACTION THEEORY OF SYNCHRONOUS MACMINE:S, R. H. Park. Part I,
Routh's14 criterion, the results of figure 18 are obtained. Also in a ACTIONS, VOlUme 52, 1933, pages 352-5.
1878
LUG0 500 kV LINES. EACH -I SYMBOL
REPRESENTS 6.75% OF THE TOTALLINE
REACTANCE.
c@ UNIT 2
PHOENIX
Fig 2. Schematic Dicrgmm of Transmission System into Which the Mdurve Generating Station was Connected
During Test Fig. 1shows the mechanical test arrangements for the HP and LP
It was knownfromexperience and system analysis thatthe machines of unit 2 including the rotational displacement and strain
Mohave units were subjected to the greatest subsynchronous hazard mewrement lomtiom. Fig. 3 shows the electricaltest configuration
when the MohaveEldorado 5OOkV line was open. Under these for the HP machine of unit 2, which was identical to that for theLP
conditions, the critical number of series capacitor modules per phase machine of unit 2.
in the MohaveLugo line was known to be men. Because safety of Determination of shaft torsional hquencies, damping and mode
the Mohave generating units w s of prime importance, the shapes required accurate measurement of torsional oscillation. Two
LugddohaveEldorado 5OOkV loop was retained inhctfor the methods were employed to obtain this information. Shaft torsional
entire test and no more than four series capacitor modules per phase strain w s measured diRctly on the exciter shaftof the HP machine,
were wed in the Mohave-Lug0 line. At three points on each shaft, instantaneous rotational velocity was
measured. This w s processed as described below to obtain angular
displacement due to torsional oscillations. Coxrelations between
DESCRIPTION OF TEST INSTRUMENTATION these two measurements were conducted to confirm the validity of
using rotational
displacement
measurement to calculate
shaft
torques.
General Considerations Toadequately d e& the forcing functioninbothsinusoidal
A number of criteria governed the selection of parameters to be excitation tests and transient events, the several electrical quantities
mewled. shown in Table I were measured. Tbese signals were p d to
obtain the subsgnchronous components.
1.Sufficient information to satisfy all test objectivesmust be
obtained.
2. Safety and integrity of theturbinegenerator andaesociated
equipment was of prime importance.
3. The instrumentation techniques employed were to have no effect
on normal station instnunentation.
4. Installation and operation of test equipment shouldhave no effect
on scheduled operationof the turbinegenerator.
Table 1 lists the parameterswhich were measured.
TABLE I
Parameter No. of Channels
HPshaft
exciter torsional strain 2
HP rotational
machine
displacement 3 Fig 3. Illushation of Method U s d to
LP machine rotational displacement 3 Sepamtely Excite Torsional Frequencies
HP&LP generator field current (If) 2 Shaft Strain Measurement
HP&LP generatorvoltage
field (Vi) 2
HP&LP generator
armature
current (Ia) 4 The strain gages mounted on the shaft between the HP generator
HP&LP generator power 2 and exciter weae to provide a precise monitor of shaft strains during
Generator tenninal voltage (q) 2 the tests and to confirm calculated relationship between rotational
displacementmeasurements and shaft torques. Measurements
involving transducers mounted on rotatingshafts require special
1879
techniques for connecting leads to stationary instrumentation. Slip
rings are often used, hut they generally must be mounted at theend
of the shaft and the transducer leads run to them. In this case, the
measurement hardwarewas confined to a small section of shaft
between two rotors, so it wasnecessary to use a radio telemetry
system as a wireless data link. Two strain channels were used in this
application to increase the reliability of the measurementand permit
two strain ranges The low sensitivity channelcovered the maximum
strain encountered in the test and the high sensitivity channel gave
improved signal-to-noise ratio
for
the lower
level strains. A
conventional 4 active arm strain. gage bridgewired to measure
torsional strain andcancel bending strains wasinstalled on the
exciter shaft. The remaining shaft mounted hardware was packaged
in a titanium ring, fabricated in two halves and clamped around the
shaft next to the strain gages. strain gage leads were run to their
respective transmitterconnections wrapped
and with a
fiberglass-epoxyband.Eachhalf of the titanium ring contained a Fig. 6. Test Site Equipment
transmitter, 2 battery modules, a “g”-switch, and an interconnection
circuit board.The batteries had sufficientcapacity to power the ‘Ihe monitoring of data during testing wasrequired for several
systemfor 6 days of cumulative operation.The “g”-switch reasons. First, the test procedure required setting forcing functions
connected the battery to the transmitter when the turbine-generator to achieve a specifiedvalue of machine response whichrequired
reached a pre-selected speed, generally about 109% of rated speed. real-time observation of the shaft strain and rotational displacement
“hiis feature conserved battery life during those periods when the signals. To ensure safety of the machine, maximum values for each
machine was not operating. The stationary equipment forthe system parameter weredefinedand a minimum of one of each type
consists of the receiving antenna and receiverdemodulator.The measurement was continuously monitored during testing. Several of
antenna is a continuous loop device, mounted around the shaft in the signals were incorporated into an automatic trip circuit where the
close proximity to the transmitters. The receiverdemodulator limits were preset. If the machine response were to exceed the limit
produces a signal proportional to the bridge output, i.e., torsional values for any parameter, the trip circuit automatically removed the
Strain. test oscillator forcing function. An additional function of the chart
recordingswas to provide sufficientdatafor preliminary o n d e
Rotational Displacement Measurement analysis of mechanical damping and mode shapes.
Because the measurement of shaft torsional
with
radio
telemetry
equipment is complex
and costly,
the
rotational
displacement measurementsdescribedbelowwere used as the METHOD OF TESTING
primary indicator of shaft torsional oscillation. A magnetic pick-up is
located next to a shaft mounted toothed wheel or gear as shown in Methods and Procedures
Fig. 4. For aconstantshaftrotational speed, S revolutionsper Implementing test procedures to precisely me8w1R the torsional
second, and N teeth on the toothed wheel or gear, the fundamental mechanical frequencies and damping as a function of electrical load
frequency component &om the pickup will be N x S Hz. If the shaft on the turbinegenerator was quite simple in concept, but required
oscillates torsionally, this valuewillbe frequency modulated. It is utmost care to ensure that no damage was incurred by the
necessary to demodulate the signal prior to recording to obtain the turbinegenerator. Tbe following is description
a of the tests
torsional oscillation information in its direct form. A phase locked conducted.
loop discriminatorw a designed to accomplish this function. The requirement of excitingthenaturaltorsionalmodes of
vibration of the turbine-generatorwas met with fourforms of
stimulation. The f i i t test with the turbinegenerator set stationary
was engagement and disengagement of the turning gear. The turning
gear is provided to slowly rotate the turbinegenerator when hot to
eliminaterotor bowingand theresultant balanceproblems.The
turning gear is physically located between the generator and turbine.
The force transmitted torsionally dueto gear engagementproduces a
general multi-modal responsewhich can bemeasured using strain
gages on the shaft. Frequency analysis of the strain signals served to
identifythe natural frequencies that were stimulated.Thestrain
responses filtered through band pass filters at the measured torsional
frequencies provided a measure of the damping of eachmode
stimulateddue to strain energy dissipationdue to mechanical
Fig. 4. Toothed Wheel hysteresis and bearingfriction.
The second test to provide a torsional stimuluswas that produced
Generator Electrical Parameters by manual synchronization of the generator to the power system.
Measurement of generator output current andvoltageandfield The mall mismatch of angle between the incoming and running bus
current andvoltage
required current
traasformers,
potential voltages provides an impulsive force to the generator to produce a
transformers, current probes and voltage attenuators respectively, to response of thetorsionalsystem which is somewhatdifferent in
convert these large signals to suitable instrumentation s ig
n& They modal content from that produced by turning gear jogs due to the
were then processed to obtain signals representing subsynchronous different axial location of the forcing function.
oscillation components.Generator powerwas computedfromthe The third method of providing a torsional stimulus and by far the
current andvoltagesignalsandsimilarlyprocessed to obtainthe most accurate is that produced by sinusoidal variation of the exciter
subsynchronous components. power output.This test allows accuratedetermination of the
torsional frequencies,damping,and mode shape as afunctionof
Data Recording and Monitoring turbinegenerator output power.Fig. 3 is aschematic of the test
system providing a general picture of the essential ingredients of this
In each of the foregoing measurement descriptions, avoltage was test. The excitationsystem supplied on the Mohave units is the
obtained representing the quantity beingmeasured.Each of t h e ,
was recorded on magnetic tape for permanent record and later analy- Althyrex system. This system embodies rotating
a 4.7 MVA
sis.Many of them were monitored during the testwith oscillosmpes synchronous machine mechanically coupled to the main generator,
or oscillograph chart recorders. Fig. 5 shows some of the recording whose output is fed to a full wave three-phase thyristor controlled
=and monitoring equipmentat thetest site. rectifier system. The thyristor’s ruing is controlled by the voltage
regulator whose output is derived from the setting of the voltage
1880
reference and theerrorbetweenthissetpointandthe sensed This sample clearly
shows that
the mechanical system is
terminal voltage. responding principally in two of its normal modes 88 indicated by
Sinusoidal forcing of exciterandgeneratorpower output was thebeatfrequency of about 3.3 Hz which corresponds to the
obtained by enteringa signal froma voltage controlledoscillator difference between the f i i two flauile torsional modes of the
(VCO) at the summing junctionof the regulator. The VCO produces system. It also indicates the lightness of the mechanical damping
a variable frequency, constant amplitudeoutput, with sweeprate and present as there was no appreciableattenuation of the strain
sweep widthadjustablefor each test condition.The VCO was amplitude over a period of five seconds of which Fig. 6 is part.
adjusted to produce a sweep of output frequency of about t0.5 Hz The frequency analysis of the strain response shown in Fig. 6,
around a torsional frequency deduced from spectral analysis of the which gives the relative amplitude of the strain signal as a function
earlierperformedturning gearand synchronization events. The of frequency, gave peaks at 26.75 Hz and 30 Hz which
sweep rate was adjusted low enough t o e m r e that no SignXicant corresponded to the first two flexible torsionalnatural frequencies
resonant amplitude or frequency distortions were obtained by the of the H p machine. Fig. 7 shows the results of a frequency analysis
rate being too high. The s u c w of this test was predicated on the of the strain signal for the HP machine following synchronization
ability to use the exciter generator as a wide-band, large, dynamic of the generator to the line.
range power amplXer providing torsional excitationin the frequency
range of 10 Hz to 60 Hz.
This excitation system meets these requirements as it is a high
initial response system whoseresponse time is onlylimited by
transport delay in fiing the thyristor. Having a full wave thyristor I
!
I
I
I I
1
bridgeprovided thecapability of full exciterpower output both
pogitive and negative due to the transient inverting capability. The
objective of sinusoidalforcing is to set up puremodaltorsional
vibrations of aconstantamplitude,then remove the excitation
source at a zero crossing and record the decay of shaft strains and 60
rotational displacementg The rate of decay and the instantaneous 0 IO 20 30
magnitude and phssebetweenmeasurementsatdifferentshaft FREP-Hz
locations provides torsional damping constant and mode shape data
respectively. Fig. 7. Synchronization Frequency Amly&
The fourth method of introducing a torsional disturbance is that
produced by insertion and bypass of transmission line compensating
capacitors.
The
accurate
determination of thedynamics of It is seen that in addition to the identification of the first two
interaction between theelectricalpowersystem and the torsional torsional natural frequencies at 26.7 Hz and 30.1 Hz, the third
mechanical system is vital forcalibration of mathematical models torsionalnaturalfrequency was also identirled at 56.1 Hz. By
used in the prediction of the onset of a subsynchronous resonance similar
analysis of rotational
displacement signals on the
event. The measurements taken during a capacitor switching event l8oORpM L2 machine following synchronization of unit 2 to the
provide a measure of the mechanical response
and also the line, the f i t two mechanical torsionals were identified as 10.3
amplitude,
frequency and damping associated with the and 17.9 Hz.
subsynchronous cunents in the power system. The forcing of the The calculated torsional natural frequencies for the HP machine
mechanical system due to capacitor switching approximates a step using a lumped inertia model are compared below withthe
function of torque on the generator as far as the torsional responses memred values. It was found that great careneeded to be
are concerned. A sudden change of systemreactance causes the exercisedin thepreparation of the mathematical model if
generator to accelerate or decelerate to a new angular position with accuracies better than 3% are to be attained.
respect to the synchronously rotating reference frame. This would
include oscillationsat about 1-2 H z dependent on the total inertiaof
the system and the electrical stiffness. The Value
insertionCalculated Value
of capacitance Measured
and the chargingenergy requirementproduces an oscillationin
transmission system energy storage causing subsynchronous currents
to flow intothe generator and produceatorque at afrequency ~
-
0 77% FULL LOAD
rtd
=
zs- s
YZ
0.0 I4
"0.0 I 2
%.OlO
80.008
-I 0.006
0.004
0.002
m ~ l , ' l I l l , , I 1
% FULL LOAD
Fig. 8. First Torsion Mode Decay -
Fig. 10. Modal Damping Load
The bottom trace on the charts is the sinusoidal driving signal and
the time at which thii signal is turned off which conesponds to
the start of the decays may be idenM1ed. The top threetraces are
the decays of the oscillatory
component of rotational
displacement atthefmnt standard,turning gear andexciter
locations respectively. The signals were obtained by processing the
output from amagnetic pickup lookingat themotion of a toothed
wheel or gear withaphasedetector to yield theoscillatory
rotationaldisplacement at eachlocation. The fourth and fifth
traces are the oscillatory component of strain measured with a
strain gage on the shaft span between the generator and exciter
and the fluctuation of generator fieldvoltage,respectively. The
reason that the signals at the exciter location were superior to Fig. 11. HP Mode 3 Decay Envelope Following Synchronization
thoae measured at the turning gear and front standard locations,is
that in the first tomion mode the exciter motion is significantly
higher than at the other locations and hence the signal to noise c) Sinusoidal Torsional Response Characteristicsof the Rotor System
ratio was correspondingly better.
Fig. 9 shows the effect of load on the vibration decay rates in the Mode Shapes
first torsion mode for the HP machine. It shows that there is a Fig. 12 shows the calculated torsional normal mode shapes for the
marked increase in damping with anincrease in load, however, the HF' rotor system. The circled pointsrepresentthe measured
damping even near full load on the HP machine is extremely light rotational displacement signals under steady state conditions due
correspondingto a system magnification factor of over 200. to sinusoidal variations in the exciter power output, obtained by
Mode 2 of the HP machine was found to have gimilar modulating the voltage regulator reference supply at the fmt two
characteristics It was not possible to excite mode 3 of the HP torsional naturalfrequenciesinturn. These measurements have
machineormodes 2 and 3 of the L?' machine by sinusoidal been normalized to the same base ES the calculated mode shapes 80
perturbation of the voltage regulator reference supply for reasons that a direct companion can be made. The measured results shown
to be discussed in the next section. Damping information was, in Fig. 12, for the P i t two modes correspondto a load of 77% of
however, obtained for these modes, at various loads, by passing full load, and are seen to be in good agreement withthe calculated
themulti-modal mechanical response signals obtainedfollowing shapes. At lower loads because of decreased damping itwas found
1882
Agreement is seen to be good andour abilityto derive strains from
vibratory rotational signals has M e r been c o n f i i e d by more
extensme testing recentlyconducted on atandemcompound
EN EXCITER turbinegenerator for which several shaft spans were strain gaged.
I 2 3 4 5 6 7 8 910
Double ResonancePeak Phenomenon
Fig. 13 shows the form of the torsional amplitude response that
was obtained at all measurementlocations on the HP machine
when sweeping sinusoidally through the frequency range in the
*
proximity of the calculated second torsional natural frequency.It
willbe noted that two resonance peaks were obtained- 0.09 Hz
apart. Torsional natural frequency calculations for the HP rotor
shaft system showed that it was inconceivable that two torsional
natural frequencies could be so close together. It was therefore,
postulated thatthe electrical power system was couplingthe
motions of the HP machines of Unit 1and Unit 2.
30.07 Hz 30.16 Hz
Fig. 12. HP N o m 1 Mode Shapes
FRONT STANDARD
that agreement was not as good due to the difficulty in exciting DISPLACEMENT
the rotor system precisely at its natural frequencies because of the
increasing sharpness of the resonance peaks. It was not possible
during the test to excite the third torsional mode by the above
method due to the small motion of the exciterinthis mode.
Calculations of thefrequency response characteristics of the Fig. 13. Double Resonance Peak
generator - exciter - voltage regulator electrical system,showed
that by modulating the v o l m regulator reference supply at the If vibration analysis is conducted on the two HP units, considered
third torsional natural frequency, the majority of the oscillatory as a singIe system and interconnected at thegenerator locationsby
torque will be applied at theexciter location.Fig. 1 2 shows that in a spring to represent the electrical cross coupling, torsional modes
the third mode the motion of the exciter is very small relative to of vibration w li be calculated that involve the motions of both
that in the firet two modes. This means that it will be much more units. These modes can be conveniently grouped in pairs, due to
difficult to excite the third mode in comparison to the first two the modes in each pair having frequencies extremely close to one
by applying torques at this location. In fact, in the limiting case another, the separation beiig determined by the magnitude of the
wheE it is assumed that the exciter is at a node inthe third mode, electrical cross coupling between the two units.One mode of each
it would be impossible to stimulate this mode at all by a torque pair will correspond to both units moving in phase with respect to
applied at theexciter. An additional important effect in producing one another with a frequency and mode shape for each unit very
torsional displacement is the relative phase angle of the torques nearly equal to that obtained from the analysis of one unit on its
applied at the generator and exciter locations with respect to the own with no electrical coupling effects. The second mode in each
phase angle of the modal displacement at these two locatio= If pair will differ in characteristics only in that the units in thiscase
the modal displacement of the exciter and generator rotors are in will be vibrating in antiphase to one another. It was observed that
phase opposition then the applied torques should ideally respond the double resonance peak phenomenon was only observed in the
inthe samerelativephaseand proportions, else the torques region of the conventional second torsion mode and only then at
produced may cancel one another to produce no net displacement, low load. Appendix C postulates the reasons for these effects by
or a very small value. This is believed to be the principal reason for the use of a simple mathematicalmodel. Further work needs to be
our inability to stimulate the second and third modes of the LP conducted to obtainabetterrepresentation based on the test
generator by sinusoidal perturbation. results, particularly in the context of quantifying the magnitudeof
the electrical cross coupling present.
Shaft Strain Correlation Theunderstanding of thedouble resonance phenomenon is
An important aspectof the test program was to determine the important as it may directlyreflect on the design of auxiliary
accuracy with which shaft strains could be predictedfrom equipment required to help eliminate the subsynchronous resonance
measured rotational displacement signals and a knowledge of the problem. It should as0 be noted that ingeneral if there axe N
calculated mode shapes. Successful correlation would mean that nominally identical units in a station feeding into the same line, the
torsionalvibrationmonitoringequipmentcould bebased on electrical cross coupling will result in families of N closely separated
rotational displacement rather than rotorstrain measurements, the modes. Non duplicate units will have simiiar characteristics except
latter requiring a more complicated telemetry system to transmit the modes are no longer closely separated. Subsynchronous currents
therotor strain signals to stationary equipment. Appendix B, flowing in the line due to disturbances will be shared between units
shows the relationship betweenthe shaftstrains and the rotational inthe ratio of theirreactances.This implies duplicate machine
displacements when the turbine-generator is vibrating in oneof its installations are advantageous due to equal current sharing and the
normal modes of vibration. Table II shows comparisons between lesser number of distinctlydifferent machine torsionalnatural
the measuredand calculated strain values for the HP machine frequencies that require protection.
when vibrating in the modespecified.
TABLE I1 CONCLUSIONS
Rotational The measurements obtained during the test led to the following
displacement conclusions:
% o f full ModeNo. measurement Measured Strain 1)Sinusoidalmodulation of theexciter power output is a good
load excited location calculated strain method of stimulating the turbine-generator set to respond in pure
modes of torsional vibration, enabling accurate measurements of
Turning gear torsionalnaturalfrequencies, modeshapes,andmodal damping
1.026 Exciter values to be obtained.
1.027 Exciter 2)Good correlation was obtained between measured and calculated
2 26.7 Exciter 0.993 torsional natural frequenciesand mode shapes.
2 66.7 Exciter 0.956 3)The modal damping values increase significantly with increases in
17.3 2 Exciter 0.927 electrical load, but even at the highest load for which data were
1883
obtained, the damping is shown to be extremely light.
4) The damping information obtained from filtering the multi-modal
responses following transients caused by switching in and
bypeeeing modules of capacitance in the trammission line was in
good agreement with that obtained in the sinusoidal excitation
tests.
5)The calculated shaft strain valuesbased on measured rotational
displacement signals and a knowledge of the normal mode shapes
agreed wellwith the measured strain values.
6)If N nominally identical turbinegenerators are electrically
coupled, the number of torsional natural frequencies will be N
times the number for a single set. The modes will be in groupsof
N that are cloeely separated in frequency,each mode involving the
motion of all the turbinegeneratom
This test served to obtain a better understanding of the torsional Fig. 15. Tmnsient Decay Envelope
dynamiccharacteristics of theturbinegenerator,includingthe
interactive effects of the electrical trammission system. These tests I€theamplitudeatt=t,isA,
have
laid the
foundation
for seeking
a solution to the
sub-synchronous mnance problem in a systematic fashion.Work is
required and is presently underway in thedesign and development of andtheamplitudeat t= is A,
auxiliaryequipment to helpeliminatethis serious application
problem. The solution to the problem will involve close cooperative
effort between the Electric Utilities and the manufacturers of steam
then V by definition
-
A,
=20LoG10 (")
turbine generators.
'** AN = lOv/zo
APPENDICES hN=f(tN-tro)
where f = frequency of the fdtered mode in the decay
(Hz)
Append= A
The mechanical damping values quoted previously are in terms of substituting into (1)yields
the logarithmic decrement(LOG DEC). It is defined as:
LOG DEC=O.l151V/(f (tN -to ))
Appendix B
where the parameters involved are defied in Fig. 14. Relationship between the strain gage signal and the toothed wheel
signals.
For LOG DEC values less than 0.6, the relationships given below E=&+ us,
2
are accurate to better than 1/2%. E E
1884
-
UNIT I UNIT 2
1 2 3 4 5 6 7 0 9 10
~ i g18.
. Double Reeononce Peak Model
4 in Fig. 18.
The analysis that follows will predict the form of the resonance
c u m for units1 and 2 to compare with them e d results.
"%e equations of motion are:
where k has units LB IN/R
6 hasunitsdegrees -k 0
rYas units IN k+el+e2 0
G has units Lam2 0 k
Note that 6 and E are quantitiea measured in the test and -
69 -e 1 -k
610
can be determined fromthe mode shape.
For simplicity in what follows, it is assumed that I1 = I2 = I, as the
mode shapes then degenerate to all unity terms as shown below.
For low values of electrical c r o s coupling stiffness relative to the
shaftspan stiffness, as is the case at Mohave, theflexiblemode
shapes of the systemare as given below:
E- = k
'6
r3 G 180
where 61 a d are the meleuredvibratorydisplacements atthe 'Ihis result would be obtained by solving the eigenvalue problem
for the system shown in Fig. 18, andinvolvesapair of modes in
front standud and turning mu locations respectively %,2,'10 which both rotor strings vibrate in phase and in antiphase with one
'1 61 '6 another respectively. At a forcing frequency thatis close to either of
& -
69
cpll be obtained from the calculated modeshapes. these modes, the system will respond in a linear combinationof each,
and the motion can be represented by two generalized coordinates
'6
91 and 92.
1885
where the natural frequenciesare given by: be seen in part from Fk. 19 where it is seen that as the damping is
increased, the peaks merge together to form a single broad peak,
witness the full load damping curve. The extent to which a double
resonance peak is formed is also a function of the frequency
separation between the in phase and antiphase modes. It was found
by doing a detailed analysis using ten inertias for each Mohave unit,
For low values of elthese two frequencies will be extremely close, that the frequency separation was much smaller in the first and thiid
as o b s e d at Mohave and in the limit when q = 0, the frequencies pair of flexible modes comparedto thesecond and this is thought to
will be identical, W i g the natural frequencies of each rotor string be the reason for the apparentabsence of the double resonance peaks
separately, Le., an uncoupled system. in these modeseven at lowloada
If a sinusoidal response solution is assumed and the modal
damping terms added, the followingsolutionfor the generalized
coordinates w libe obtained. REFERENCES
-T
“= 41 EwN~’ ~ w 2 ) + 321 w N I 4 1) J.W. Butler and C. Concordii “Analysis of Series Capacitor
application Problems,” AIEE Trans,1937.
2) C. Concordia and GX. Carter, “NegativeDamping of Electric
Machinery,” AIEE T r q V 0 1 . 60, pp. 116-120,1941.
+T 3) CP. Wagner, “Self Excitation of Induction Motors with Series
92 = Capacitors,” AIEE Trans, Vol. 60, pp. 12414247,1941.
42 [ w - ~w 2 ) ~+ at2
~ uN2w where21and 22 are the 4) RD. Bodine, C. Concordia, G. &on, “Self Excited Oscitions
modal damping values. of CapacitorCompensatedLong Distance Transmission
Systems,” AIEE Trans, Vol. 62. pp. 4 1 4 discussion pp.
The rotational displacement responee may now be obtained by 371-372,1943.
back substitution into thetransformation equation (3). 5) RB.Marbury and JB. Owens, “New Series Capacitor Protective
By way of example, the mnance shape was calculated for this Device,” AIEE Trans.1946.
system with a frequency separation that corresponds to the value 6) A.A. Johnson, “Application
Considerations of Series
measured for theMohave HP second pairof flexible modeswhere: . Capacitors, W&gho& Engineering Journal, 1948.
7) H. Rustebacke and C. Concordia. “Self Excited Oscillationsin a
~~ ~ ~~ ~~
uN1 = 30.07 Hz & uN2 30.16 Hz ’ Transmission Systemusing se;ies CapacitoA,” IEEE ~rans,
PAS89, No. 7, pp. 1504-1512,1970.
8) L.A. Kilgore, L.C. Elliott, E.R. Taylor,“ThePredictionand
Control of Self Excited Oscillations Dueto Series Capacitors in
Power Systems,” IEEX Trans,PASSO, Vol. 3,1971.
w2 9) J.W. Ballance and S. Goldberg, “Subsynchronous Resonance in
SeriesCompensated Trananission Lines,” IEEE Trans, Vol.
2
v) PAS92, NO. 5, pp. 1649-1658.1973.
!$i 10) C.E.J. Bowler, D.N. Ewart, C. Concordia, “Self Excited
cu
Torsional Frequency Oscillations with Series Capacitors,” >
E
5 w V 0 1 . PAS92, NO. 5, pp. 1688-1695,1973.
11) R.A. Hedin, R.C. Dancy, KB.Stump, “AnAnalysis of the
SubsynchronousInteraction of Synchronous Machinesand
Tr&ission Networb,” Roc. h e r . Power Conf., Vol. 35, pp.
30.25 30.20 30.15
30 30.10 30.05 1112-1119.1973.
FORCING FREQUENCY 12) L.A. Kilgok, E.R. Taylor, Jr., D.G. h e y , RG. Farmer, E.
Katz, A.L. Schwalb, “Solutions to the
Problems of
Fig 19. Forced Response Subsynchronous Resonance in Power Systems with Series
The results are shown in Fig. 19 for three different mechanical Capacitors,” Roc. Amer. Power Conf., Vol. 35, pp. 1120-1128,
damping values, beiig zero and the values m e d for the second 1973.
mode at no load and full load respectively. W i g the test, the 13) C. Concordia, J.B. “ice, C.E.J. Bowler, “Subsynchronous
double monance peak phenomenon WBS only observed when Torques on Generating Units Feeding Seridapacitor
sweeping through the second flexible torsional natural frequency at ~ opie nsae
td~ines,”ROC. h e r . Power Cod., VOI. 35, pp.
low loadswhich corresponds to low damping, Thereason for this can 1129-1136,1973.
1886
Discussion The frequency results are tabulated in Figure 2. As in the Mohave
tests, frequencies were measured by three methods, turning gear jogs,
K. Murotani (Nissin Electric Co., Ltd., Kyoto, Japan): The authorsare synchronization, and by sinusoidallyvarying the exciter power output
to be congratulated for having presented such useful and fundamental at each natural frequency in turn by a method similar to that described
data on the torsional natural frequencies and mode shapes which are in the paper. Theslightdownward trend in themagnitudes of the
very important tostudythe sybsynchronousresonanceproblem. torsional frequencies as the electrical load is increased is thought to be
I would like to raise two questions aboutthis paper. due to the increase in the temperature of the rotorshaft system as the
In the paperpresented by theauthor*atthe1973 Power load is increased, resultingin a slight reduction of the torsional stiffness
Engineering Winter Meeting they reported that the turbine generator of the turbine-generator.
torsional damping, as defined in Dl 2, is very important and theyused No double resonance peaks were observed in the test, which fits
three values, such as 0.0,0.6 and 1.2 for their example of the hydraulic thehypothesis givenin the paper fortheoccurrence of this phe-
system. nomenon at Mohave, as at the time of the test, Navajo 2 and 3, which
I wish to knowtherelationshipbetweentheturbine-generator are duplicates of No. 1, were not in service.
tortional damping in that paper and the logarithmic decrementgiven in
Figure I O of the author's paper.
Then what kindofcounter measures theauthorsare now
proposing to prevent theshaftfailuresdue to thesubsynchronous
resonance at theMohave Generating Station orhas any countermeasure
actually been installed?
(*) Reference Number 10 W
Y
-
NAVAJO #l I u o u w K * L yLI#IuyLIsIJ
1887
MEASURED MODAL DAMPING vs LOAD
FIG 8
r
/
MODE 3
0.018
0.016
Y “ E D VALUES ( BASED
1.0 ON 0.72 AT FRONT STANDARD)
a 0.6
0.6
6- 0.4
0.2
J
a 00.002
~ 0 0 4 ~ 0 D E
2 0
2
t -0.2
I-
&-0.4
!
W
Z -0.6
s -0.8 L I I I I 1 I
0 20 40 60 80 100 12(
-1.0 %OF FULL LOAD
U J
-0.4 and may act between adjacent inertias and or from each inertia to
Z -0.6 ground, the corresponding non dimensional modal logarithmic damping
5 -0.8
W
K
values may be obtained by uncoupling and then non dimensionalizing
theequations of motionby using thetransformation shown in
-1.0 Appendix C.
If the form of one of the uncoupled modal equations is:
Figure 7 shows the calculated mode shape for the fifthmode with I q + &+Kq = T(t)
a calculated natural frequency of 51.5 Hertz. The fifth modecould not
be stimulated by sinusoidallyvarying the exciter power output. The it may be nondimentionalized by dividingby the modal inertia I to
explanation is similar to that given in the paper for mode 3 of the yield:
Mohave high pressure machine. This figure shows that in mode 5 the
exciter and generator are virtually stationary and it would, therefore, + 2cWN(1+ W N 2q = T (t)/I
require extremely high torque values to be applied at either of these
locations to stimulate this mode. Thefrequency of this mode was, where W N = an undamped natural frequency and { is the corresponding
however, measured to be 53.2 Hertz by passing a long time sample of non dimensional damping ratio.
normal operating data from thefront standard rotational displacement, Appendix A, shows that the modal“logdec” = 2n X modal {.
(for which there is large relative motion in this mode),into a frequency
spectrum analyzer. Manuscript received April 18, 1975.
1888
The definition of o shown in Fig. 5 of paper Reference 10 is given arbitrarily provided the net modal damping is achieved. Most modem
by FUNS for a pure modal response, henceo = LOG DEC X f, where torsional vibration response programs use the modaldampingvalues
f is the undamped natural frequency in Hz. directly and the task of deducing the individual dashpotconstants,
Figure 10 of this paper shows that in mode 2 at full load the log even if it were possible, is not required.
dec = 0.013 and for mode2, f = 30.1 Hz. With regard to the second question, the counter measure adopted
Hence using the relationship above, o = 0.3913 rad/sec. This result to prevent subsynchronous resonance failures at Mohave has been the
is to be compared with a value of 0.6 in Reference 10. It should be reduction in the amount of series capacitor compensation used. This
appreciated that the dampingusedin Reference 10 was estimated in measuremoves the critical electrical resonance away from the
advance of any test results, which in this case gave reasonable values. mechanical resonance such that there is no significant torsional
It must also be pointed out that the discrete dampers can be assigned interaction.
1889
ArticleCode : pqa_3311
1 1 0.035 (5)
PSS
bus1 bus2 X L1
TCSC X system λi λ 0.08θ. θp3 1
G
Generator X L2 Infinite
Wind farm Bus θp is the angle between the plane of rotation and the
Three phase
to Ground blade cross-section chord [16],[17].
Fault
Xc (1)
fe f0
Xl
The generated subsynchronous currents will outcome in
rotor torque at the complementary frequency, i.e.
fr=f0-fe (2)
If fr=f0-fe is near to one of the torsional frequencies of
the rotor shaft, the torsional oscillations will be excited (b)
and this condition lead to detrimental phenomenon Fig. 2: Blade pitch angle θp (a), Power coefficient versus blade pitch
angle (b)
In recent years, Fuzzy Logic Damping Controllers
(FLDCs) have been appeared as an effective implement
to stabilize the power network. [19], [20]. FLDCs are
more robust and effective than Conventional Damping
Controllers (CDCs) in the power. In this paper two Fuzzy
Logic Damping Controllers (FLDCs) have been applied
to pitch angle control in wind turbine and TCSC
controller.
In this article Power deviation ( ΔP ), its derivatives
ΔP
( ) are inputs of fuzzy controllers and pitch angle
t
( θp ) is output of fuzzy controller.
Fig. 3: Wind Turbine modeled with Simulink 1n 1p
1 2n 2p
1
equipped by FLDC of pitch angle. Wind power plants are 0.4 0.4
not sustainable like fuel energy production. The wind 0.2 0.2
-3 -2 -1 0 1 2 3
0
-3 -2 -1 0 1 2 3
support the power generator for the time that wind turbine Power deviation
1
on oz op
Power derivatives
system. 0.4
0.2
Capacitor (TCSC) Fig. 6: Membership functions for the FLDC of pitch angle controller
A TCSC comprise of a capacitor in parallel with an
inductor that is connected to a couple of opposite-poled The control rules of the fuzzy controllers are showed
thyristors. By adjusting the firing angle of the thyristors, below. The fuzzy sets have been determined as: N:
the inductor reactance is varied and it can lead to change negative, Z: zero, P: Positive, respectively.
the effective impedance of TCSC. The TCSC is ΔP
1. If ( ΔP is P) and ( is P) then ( θp is N)
commonly operated in capacitive region, while inductive t
mode operation can be used during severe possibilities ΔP
[18]. Schematic diagram of TCSC has been shown in figure 4. 2. If ( ΔP is P) and ( is N) then ( θp is Z)
t
ΔP
3. If ( ΔP is N) and ( is P) then ( θp is Z)
t
LTCR ΔP
TCR 4. If ( ΔP is N) and ( is N) then ( θp is P)
t
In TCSC controller, rotor speed deviation ( Δ ),
iTCR Δ
its derivatives ( ) have been used as the fuzzy
t
controllers inputs and firing angle derivatives is output of
i i-iTCR CTCR fuzzy controllers.
Fig 4: Schematic diagram of TCSC 1
mf1 mf2
mf1
1
mf2
input2 of TCSC fuzzy controllers
input1 of TCSC fuzzy controllers
0.8
0.8
0.6 0.6
0.4
Vabc Impedance 0.4
Controller
0.2 0.2
Impedance capacitive mode Alpha
Iabc calculation calculator 0 0
Irms Controller -0.03 -0.02 -0.01 0 0.01 0.02 0.03
-0.03 -0.02 -0.01 0 0.01 0.02 0.03
rotor speed derivatives
inductive mode rotor speed deviation
mf4 mf2 mf3
1
Anfis controller
dw
Output of TCSC fuzzy controller
0.8
+
0.6
ωr Alpha 0.4
t TCR pulses
0.2
Firing unite
0
-15 -10 -5 0 5 10 15
Δ
1. If ( Δ is P) and ( is P) then ( Δ is P)
10
t 0
Δ -10
t -50
0 1 2 3 4 5 6
Δ Time(sec)
4. If ( Δ is N) and ( is N) then ( Δ is N) c
t
Fig. 8: Simulation results for un-damped mode: (a): rotor speed
90 Δ (7) deviation, (b): speed deviation between generator, Low pressure
and high pressure turbine, (c): torque between generator, Low
pressure and high pressure turbines.
7. Results and Simulink in Matlab
SSR oscillations in wind turbine have been shown in
For verifying the efficacy of the offered control method figure 9.
to mitigate the SSR phenomenon, the IEEE Second 80
Benchmark combined with the TCSC is modeled in Mechanical Electromagnetic Torque
60
MATLAB/Simulink. Two cases for studying are
Mechanical Electromagnetic Torque
-60
0.2
Rotor speed deviation -80
0 1 2 3 4 5 6
0.15
Time(sec)
0.1 a
Rotor Speed Deviation
0.05 0.05
Rotor Speed Deviation
0
0
-0.05
-0.05
-0.1
Rotor Speed Deviation
-0.1 -0.15
-0.15 -0.2
-0.25
-0.2
0 1 2 3 4 5 6
-0.3
Time(sec)
a -0.35
-0.4
0.25
-0.45
0.2 0 1 2 3 4 5 6
Time(sec)
Speed Deviation (Gen, LP and HP)
0.15
b
0.1
50
0.05
Electrical Power
40 Pitch Angle
0
Mechanical Power
30
-0.05
20
Power and Pitch Angle
-0.1
10
-0.15
0
-0.2
-10
-0.25
0 1 2 3 4 5 6 -20
Time(sec)
-30
b
-40
-50
0 1 2 3 4 5 6
Time(sec)
c
Fig. 9: Simulation results for un-damped mode: (a): mechanical
electromagnetic torque, (b): rotor speed deviation in wind turbine, (c):
mechanical and electrical power and pitch angle.
12
Figure 9 shows the oscillations in wind turbine due to Mechanical Electromagnetic Torque
10
SSR phenomenon without TCSC.
-2
-4
0.025
-6
0.02 0 1 2 3 4 5 6 7 8 9
Time(sec)
0.015
a
Rotor Speed Deviation
0.01
0 0.03
-0.005 0.02
-0.02 -0.02
0 1 2 3 4 5 6 7 8 9
Time(sec) -0.03
a -0.04
-0.05
0.04
-0.06
0 1 2 3 4 5 6 7 8 9
0.03 Time(sec)
Speed Deviation (Gen, LP and HP)
b
0.02
14
0.01 Pitch Angle
12 Mechanical Power
Electrical Powwer
0 10
8
Power and Pitch Angle
-0.01
6
-0.02 4
2
-0.03
0 1 2 3 4 5 6 7 8 9 0
Time(sec)
-2
b
-4
4
-6
0 1 2 3 4 5 6 7 8 9
3 Time(sec)
2 c
Torque (Gen-LP) and (LP-HP)
1
Fig. 11: Simulation results for results with damping SSR by
TCSC with FLDC for pitch anlgle controling: (a): mechanical
0
electromagnetic torque, (b): rotor speed deviation in wind
-1
turbine, (c): mechanical and electrical power and pitch angle.
-2
Figure 10 illustrates that the TCSC with auxiliary The increasing requirement to the clean and renewable
FLDC controller can be able to mitigate SSR. energy has led to the rapid development of wind power
systems all over the world. With growing usage wind
power in power systems, impact of wind generators on
subsynchronous resonance (SSR) is importance.
This paper proposed a technique for damping the SSR
by TCSC. The IEEE second benchmark system equipped
by steam and wind turbine as a hybrid energy production
system was studied. A TCSC is originally employed to 122. [17] S. Mishra, P. K. Dash, P. K. Hota, and M. Tripathy,
“Genetically Optimized Neuro-Fuzzy IPFC for Damping Modal
increase power transfer capability of the transmission. As Oscillations of Power System,” IEEE Transactions On Power
shown The TCSC with auxiliary FLDC controller can be Systems, Vol. 17, No. 4, November 2002.
able to damp the oscillations of SSR phenomenon. [20] H. He, “Fuzzy Modeling and Fuzzy Control [Book Review],”
With applied FLDC controller to TCSC and applied Computational Intelligence Magazine, IEEE,
10.1109/MCI.2008.926613.
FLDC for controlling pitch angle of wind turbine, TCSC .
mitigated the SSR and mechanic and electric power of
wind generator were closed to together. By this work
wind generator produced power in near the 1pu.
References
[1] Yazhou Lei, Alan Mullane, Gordon Lightbody and Robert
Yacamini. "Modeling of the Wind Turbine with a Doubly
FedInduction Generator for Grid Integration Studies".IEEE
TRANSACTIONS ON ENERGY CONVERSION, VOL. 21, NO.
1, MARCH 2006.
[2] Rajiv. K. Varma, and Soubhik Auddy,” Mitigation of
Subsynchronous Oscillations in a Series Compensated Wind Farm
with Static Var Compensator”, IEEE, 2006.
[3] Alejandro Rolan, Alvaro Luna, Ge rardo Vazquez, Daniel Aguilar
and Gustavo Azevedo. " Modeling of a Variable SpeedWind
Turbine with a Permanent Magnet Synchronous Generator". IEEE
International Symposium on Industrial Electronics, 2009.
[4] T. Ackerman, Wind Power in Power Systems. John Wiley&Sons,
2005.
[5] P. Kundur, Power System Stability and Control. New York:
McGraw-Hill, 1994.
[6] Luiz A. S. Pilotto, André Bianco, Willis F. Long, and Abdel-Aty
Edris, “IEEE TRANSACTIONS ON POWER DELIVERY”,
VOL. 18, NO. 1, JANUARY 2003.
[7]. A. B. L. Anderson, P. M. and J. E. Van Ness, Subsynchronous
resonance in power systems, New York: IEEE Press, 1990.
[8]. M. S. El-Moursi, B. Bak-Jensen, M. H. Abdel-Rahman “Novel
STATCOM Controller for Mitigating SSR and Damping Power
System Oscillations in a Series Compensated Wind Park,” IEEE
Trans. Power Delivery., vol. 25, no. 2, pp. 429–441, Feb 2010.
[9] Tang Yi, and Yu Rui-qian, ” Impacts of Large-Scale Wind Power
Integration on Subsynchronous Resonance”, IEEE, 2011.
[10]. R. K. Varma, Y. Semsedini and S. Auddy, “Mitigation of
Subsynchronous Oscillations in a Series Compensated Wind Farm
with Thyristor Controlled Series Capacitor (TCSC),” in Proc.
IEEE Power Eng. Soc. General Meeting Conf, pp. 1–7, 2007.
[11] IEEE SSR Working Group, Second Benchmark Model for
Computer Simulation of Subsynchronous Resonance, IEEE Trans.
on Power Apparatus and Systems. 104, N0.5 PP:1057-1064, 1985.
[12]. IEEE Committee Rep., “First benchmark model for
computersimulation of subsynchronous resonance,” IEEE Trans.
Power Appl. Syst., vol. PAS- 96, no. 5, pp. 1565–1572, Sep./Oct.
1977.
[13]. IEEE Subsynchronous Resonance Working Group, “Terms,
definitions and symbols for subsynchronous oscillations,” IEEE
Trans. Power Apparatus and Systems, vol. PAS-104, no. 6, pp.
1326–1334, 1985.
[14]. A. B. L. Anderson, P. M. and J. E. Van Ness, Subsynchronous
resonance in power systems, New York: IEEE Press, 1990.
[15] K. R. Padiyar, Power System Dynamics: Stability and
Control.Bangalore, India: Interline, 1996.
[16] Alejandro Rolan, Alvaro Luna, Ge rardo Vazquez, Daniel Aguilar
and Gustavo Azevedo. " Modeling of a Variable Speed Wind
Turbine with a Permanent Magnet Synchronous Generator". IEEE
International Symposium on Industrial Electronics, 2009.
[17] Nicolae MUNTEAN, Octavian CORNEA and Diana PETRILA,
"A New Conversion and Control System for a Small off – Grid
Wind Turbine".12th International Conference on Optimization of
Electrical and Electronic Equipment, OPTIM 2010.
[18] I.Mohammad Hoseiny Naveh, Elyas Rakhshani, Reza Heidari,
”Application of Linear Observer on Control of Subsynchronous
oscillations Using TCSC”, IEEE, POWERENG, Lisbon, Portugal,
pp. 540–545, March 2009.
[19] Qun Gu, A. Pandey, and S. K. Starrett, “Fuzzy Logic Control for
SVC Compensator to Control System Damping Using Global
Signal”, Electric Power Systems Research, 67(1)(2003), pp. 115–
Transfer Capability Study of Tie-line Installed TCSC Considering
Transient Stability Constraints
WU Yanjuan[1㧘2] LI Linchuan[1]
1. Key Laboratory of Smart Grid of Ministry of Education, 2. School of Automation, Tianjin University of Technology,
Tianjin University;,Tianjin 300072, China Tianjin 300384, China
Abstract—The transfer capability of tie-lines installed Thyristor The study concerns transfer capability of tie-line installed
Controlled Series Capacitor (TCSC) is studied in multi-machine TCSC which applies DSC to satisfy transient stability
systems considering transient stability constraints. Since the constraints. It is a key to select the time of DSC, otherwise,
conversion time of TCSC mode has the important effect on instability of the power system is deteriorated probably in the
transient stability, the discrete control strategy(DCS) is presented case of selection of DSC improper time. According to the
based on corrected transient energy function. The multi-machine corrected transient energy function theory[5], the special
system is divided up sending-end and receiving-end two moments at which the corrected equivalent generator angular
equivalent machine systems. The moment just at which the velocity and the corrected potential energy derivative reach
corrected kinetic energy reach the maximum value is used as the the special values act as the moment of discrete control. The
start moment of TCSC maximum capacitive impedance in order method is verified by the study systems of 4-generator-10-bus
to increase compensation degree, and the moment just at which
and 10-generator-39-bus.
the corrected potential energy reach especial value is used as the
start moment of TCSC bypass mode in order to reduce short-
circuit current. IEEE 4-generator system and New England 10- II. MATHEMATICS MODEL
generator system are used as case studies, transfer capabilities of
tie-lines considering transient stability constraints are calculated A. Flow equation
with the conventional control of TCSC and with the discrete Polar form of flow equation acts as the following based on
control of TCSC, respectively. The calculation results show that continuous flow method.
the discrete control of TCSC enhances significantly the transfer
capability of tie-lines in multi-machine system considering
transient stability constraints compared with the conventional P gi − P Di − V i ¦V j (G ij cosθ ij + B ij sin θ ij ) = 0 ˄1˅
control of TCSC. ° j∈ N
®
°Q gi − Q Di − V i ¦V j (G ij sin θ ij − B ij cosθ ij ) = 0
Keywords- TCSC; Transient stability; Transfer capability; ¯ j∈ N
___________________________________
978-1-4244-9690-7/11/$26.00 ©2011 IEEE
motion are as follows relative to the system center of inertia protection action because of the large line current. This will
(COI). lead to compensation effect of TCSC being inadequate, make
the MOV protection overload and increase the accumulation of
energy. However, the TCSC operates in bypass mode properly
δ = ωi [7,8], which can change the total impedance of TCSC and the
° ˄3˅
® M ω = P − P − M i P = f (δ ) phase angle, inhibit short-circuit current, reduce the burden of
° i i gi ei
M¦
COI i
¯ MOV protection and improve the effect of TCSC
compensation.
Where,
Ng
PCOI = ¦ ( Pgj − Pej ) M¦ = ¦ Mi
j =1 i∈Ng
1 A
X 䯴 α䯵 = − [䯴2 π − α 䯵 + sin 䯴2 π − α 䯵 ] +
TCSC
ωC πω C
4 A cos 䯴 π − α 䯵
2
ω
0
ω 02 −ω 2
LC
Installation of TCSC equipment will significantly improve
TCSC steady-state control model is shown in Figure 1, the stability in power system [9], especially, the TCSC mode
error between active power of tie-line and the reference value conversion time play important role in dynamic stability.
can change the XTCSC, and further change admittance matrix Selection of the wrong time not only is defeated to improve
elements in the flow calculation. system stability but also make instability deteriorated. For
TCSC in the system to determine the mode transition time is
usually estimated ether using more experience or offline
testing. Lyapunov energy function as a online successful
method has been successfully applied to power system
switching control of TCSC [10,11]. However, the energy
function will increase the number of equations of complex
nonlinear multi-machine power systems. COI based on the
Fig 1 Stability model of TCSC with active power control amendment energy function significantly reduce the number of
equations to accelerate the calculation speed. The DSC is to
study control strategy of TCSC mode conversion time in the
Impedance of TCSC adopting the maximum capacitance multi-machine system based on the corrected energy function.
value in transient stability control process results in the MOV Multi-machine system is treated as two groups of generators
which are connected by tie-line. The corrected energy function iterations, compute flow. If stable, repeat the third step,
of tie-line can be calculated. The moments of its special values otherwise enter the fourth step. The fourth step is that the last
act as TCSC conversion control moment. In summary, the iteration of transfer power is transfer power limit satisfying the
system equation of motion (3) is modified as the following: transient stability constraints. Return to the second step. The
fifth step is to adjust λ ,γ of formula (1) and reduce transfer
power, plus a number of iterations , calculate power flow, if
= ω eq stable, back to the second step, otherwise, repeat the fifth step.
°δ eq
° M eq
°
eq = M eq (ω A − ω B ) =
° M eq ω ¦ (P − P − IV. EXAMPLE ANALYSIS
°
M A i∈M A gi ei
® Mi M eq Mj
° P COI ) − ¦ ( P gj − P ej − P COI ) The first test system is IEEE 4 machines system shown in
° MΣ M B j ∈M B MΣ Fig 4. Three-phase short circuit fault occurs near the bus 7.
°
° M eq M eq
° = ¦ (P − P ) − ¦ (P − P ) = P Supposing that fault occurs at 0s and clears at 0.1s. Time step
¯ M A i∈ M A gi ei M B j ∈M B gj ej eq
M eq ω eq2 ³ p eq dδ eq
δ
2
sep
eq
greatly improving transfer capability of multi-machine system
and strengthening transient stability.
REFERENCE
[1] Peng Wu, Haozhong Cheng, Jie Xing, et al. “A new transmission
network planning model considering power reserve”, Automation of
Electric Power Systems, 33(6):44-48, 2009
[2] Jing-jing Zhao, Wei Wei, Cheng-shan Wang, “Distributed transfer
capability computation of electric power system based on decomposed
system network”, Proceedings of the CSEE, 2008, 28(7): 1-6
[3] Jingqiang Sun, Dazhong Fang, “Total transfer capability with transient
Fig.5 Maximum D-value of power-angle curve stability constraints”. Automation of Electric Power Systems, 2005,
29(8): 21-25,70
[4] Ming Wei, Yuhong Wang, Chaobo Dai , “Experimental research on
To better illustrate the advantages of the DSC, the fig.5 control strategy of TCSC for UHVAC transmission system from Yimin
shows maximum Power angle difference curves of two control to Fengtun by real-time digital simulator”, Power System Technology,
method at the same 500.9MW of transmission power. 2009,33(4): 71-76
Obviously, the DSC ensure transient stability, yet the [5] Yanjuan Wu, Lin-chuan Li, “Transient stability constrained optimal
conventional PSS control has lost. power flow based on sensitivity of transient energy margin”. Power
System Technology,.2005,29(15): 28-33
The second test system is 10 machine 39 bus system in [6] Xiaoxin Zhou, Jianbo Guo,Jiming,et,al, “TCSC on power system”,
which single line of line16-19 is changed into double lines. Beijing, Science Process, 2009
Three-phase short circuit fault occurs at the near the bus 16, [7] Xu Zheng, Zhihong Pei, Shaorong Wang,et,al “Study on transient
yet other conditions with reference to 4 machines system. characteristics of TCSC with dynamic simulation”, Electric Power
Table 3 lists the discrete control time. Table 4 lists the active Automation Equipment, 2005,25(6):17-21
power limits of four cases considering transient stability [8] Jiming Lin, Jianchao Zheng, Chengqi Wu,et,al. “Digital simulation of
basic control and overvoltage protection for TCSC” Automation of
constraints. Improvement of transfer capability satisfying Electric Power System,2000, 24(8):26-28
transient stability evidently is seen because of adoption of the
[9] Nicklas P. Johansson, Lennart Angquist, Hans-Peter Nee, “Adaptive
DSC of TCSC. control of controlled series compensators for power system stability
improvement, 2007 IEEE Lausanne Powertech Proceedings, 2007: 355-
Table3 Discrete control schedule of 39-bus system 360.
i 1 2 3 4 [10] Padiyar,,K.R.,Uma,Rao,K., “Discrete control of series compensation for
stability improvement in power systems”, International Journal of
tci(s) 0.02 2.38 4.38 5.8
Electrical Power and Energy System, 1997,19(5): 311-319.
[11] BORTONI G, LUSVARGHI R, LACOSTE J, et al. Impact newly
Tci(ms) 80 40 20 20 conceived flexible AC transmission system control strategies on
the dynamic behaviour of power system[C],International Symposium
tLi(s) 0.96 3.0 5.0 6.38 on Electric Power Engineering, Stockholm,Sweden, 1995:89-94.
[12] Yusheng Xue, Van Custem,Thierry,Ribbens-Pavella, Mania, “Extended
TLi(ms) 40 40 20 20
equal area criterion justify cations,,generalizations,,applications”,IEEE
Transactions on Power Systems, v 4, n 1, p 44-52, Feb 1989
[13] Qiang Guo, Xiaoxin Zhou, “ Parameter optimization of auto disturbance
Table 4 Look-up table of transmission active power limit by tie line satisfying
rejection control of thyristor controlled series capacitor”, Power System
transient stability
Technology,1999,23(11): 28-30
With TCSC
Tie-line Without additional With FSC
equipment PSS DCS
ฎUGCONCLUSION
Research on Design and Application Based on TCSC
Optimal Model for Congestion
Fei Li Xianshan Li
College of Electrical Engineering and Information Science College of Electrical Engineering and Information Science
China Three Gorges University China Three Gorges University
Yichang, China Yichang, China
Lifei_ctgu@163.com lixianshan@ctgu.edu.cn
Abstract-People pay more attention to the use of FACTS devices As the special advantage of flexible AC transmission
to ease grid congestion problems. On the base of the traditional device (FACTS) [4], such as quickly adjusting, convenient,
optimal power flow (OPF), an optimal congestion dispatch model directional adjustment as needed and good effects, it plays an
with TCSC devices is proposed in this paper, expressing the increasingly important role in the network congestion
control of the TCSC over the power systems as additional power scheduling.
equations. Instead of introducing a TCSC controller equation,
optimization can be achieved in the variable space including
In the early time, transmission congestion can be eased by
TCSC controlled parameters. Non-linear interior point method improving the tie-line power flow capacity through power flow
(Nonlinear IP method) is used to solve the optimal problems. The control [5]. Based on DC power flow model, the control effects
results show that the control of TCSC can flexibly adjust the of TCSC and TCPS are expressed as additional power flow of
network power flow, and effectively ease the network congestion nodes. Coordination and optimization for congestion
problems. controlled problems of power system which contains a number
of phase shifter is deeply studied in reference [6], and
Keywords- Congestion; TCSC; Additional power; Nonlinear IP interior-point method is applied to the solution process.
method Recently, the injection power of FACTS device is expressed as
independent variables [7], and introduced it to the global
I. INTRODUCTION optimal control mode of FACTS device, using non-linear
With the interconnection of the large regional power grid programming method to solve the problem for improving
and the establishment of the future electricity market, since the system transmission capacity. Using FACTS device to
grid power flow randomness and the probability of improve system security is presented in reference [8]. It gives a
transmission congestion occurred greatly increased, new format for solving the optimization problem: It expresses
transmission congestion has become more serious that affects additional injected power and control parameters of FACTS
the safe and stability of the modern power grid [1], which is bad device as independent variables introduced to the optimization
for the efficient and economical operation of electricity problems, and successive quadratic programming algorithm is
market. How to solve the transmission network congestion used to the solution, but lack of the analysis of convergence
problems have become forefront topics at the field of performance. Many scholars have considered that the
electricity market. introduction of FACTS control parameters will increase the
system's non-linear and non-convexity, and in some cases, the
In the traditional vertical management mode, once the convergence will be affected by using numerical method
transmission power exceeds the limited case, the dispatch directly, even not converge. The introduction of UPFC control
center schedules independently according to certain principles, parameters affecting the convergence of optimization
which is different from the electricity market environment. The algorithm is proposed in reference [9, 10].
electrical energy is circulated by electricity trading. The
economic interests of all market participants is involved in In this background, from a point of view of technology,
eliminating the congestion process, meanwhile, eliminating this paper focuses on the study of the optimization congestion
congestion requires not only the technical support, but also the method including the FACTS devices (e.g. TCSC). The part 1
consideration of the justice and benefits, which makes the introduces FACTS congestion model, and the optimization
congestion problem more complicated. Elimination of congestion model containing TCSC is proposed in part 2.
congestion mainly uses two types of technical and economic Using the system of IEEE5 to check the method is in part3,
methods. The former mainly relies on the advanced and and the part4 comes to the conclusions.
reasonable scheduling means (e.g. FACTS controlling
technology [2]); the latter mainly uses the price mechanism [3]. II. FACTS CONGESTION MODEL
FACTS devices using to active power regulation are as
Fig.1 TCSC equivalent circuit model ⎧ ΔPi = −ViV j sin θij KTCSC / X ij
⎪
⎪⎪ ΔQi = −Vi 2 KTCSC / X ij + ViV j cos θij KTCSC / X ij
i Zij=rij+jxij j ⎨
⎪ ΔPj = ViV j sin θij KTCSC / X ij
⎪
⎪⎩ ΔQ j = −V j KTCSC / X ij + ViV j cos θij KTCSC / X ij
2
△Si △Sj
Fig.2 TCSC power injection model ΔPij = ViV j sin θ ij K TCSC / X ij
(5)
Fig.2 shows the power injection model of TCSC. The
injected power of lines at both ends can be expressed as: The simplified equations ignore the resistance of line and
eliminate the nonlinear term, which helps to improve the
⎧ΔPi = Vi2 ΔGij − VVi j (ΔGij cos θij + ΔBij sin θij )
convergence of resolving the power flow, while it also affects
⎪ the accuracy inevitably.
⎪ΔQi = −Vi2 ΔBij + VV i j (ΔBij cos θij − ΔGij sin θij )
⎪
⎨
⎪ΔPj = V j ΔGij − ViV j (ΔGij cos θij − ΔBij sin θij )
2 III. OPTIMIZATION CONGESTION MANAGEMENT
⎪ MODEL ADDING TCSC
i j (ΔGij cos θij + ΔBij sin θij )
2
⎪⎩ΔQ j = −V j ΔBij + VV
(1) In the system environment, the total cost of fuel to
generate electricity (6) and net loss can be chosen as the
KC X ij2 ( KC − 2) objective function for optimal congestion model.
ΔGij =
(rij2 + X ij2 ) ⎡⎣ rij2 + X ij2 (1 − K C ) 2 ⎤⎦
KC X ij ⎡⎣ X ij2 (1 − KC ) − rij2 ⎤⎦
Fcos t = ∑
i∈S
( a 2 i PGi2 + a1i PGi + a 0 i ) (6)
ΔBij = G
⎪⎪ ΔPi = PGi − PDi + ΔPi − Vi ∑ V j (Gij cos θij + Bij sin θij ) = 0
expressed as: '
j∈i
(7)
⎨ n
ΔPij = Pij ′ − Pij = −Vi 2 ΔGij + ViV j (ΔGij cos θ ij + ΔBij sin θ ij ) ⎪ ΔQi = QGi − QDi + ΔQi' − Vi ∑ V j (Gij sin θij − Bij cos θ ij ) = 0
(3) ⎪⎩ j∈i
KC is defined as the compensation degree of TCSC. When ΔPi ' , ΔQi' are the additional active power and reactive
KC >0, TCSC comprehensive reactance represents capacitive, power of the nodes connected with TCSC respectively.
otherwise is perceptual. It considers as controlled parameters
of TCSC. The value range of TCSC is among the maximum of B. Inequality constraint are as follows:
the capacitive and perceptual compensation degree. In Upper and lower bounds constraints of generator’s active
practical engineering calculations, since the reactance is much power and reactive power are as follows:
⎧⎪ Pgimin ≤ Pgi ≤ Pgimax i ∈ mp IV. SIMULATION EXAMPLES
⎨ min max IEEE standard 5-node system (Fig.3) is used to explain
⎪⎩Qgi ≤ Qgi ≤ Qgi i ∈ mp
(8) congestion phenomenon. The active power of 1# generator is
6p.u. TCSC is installed at the branch (2-3), the boundary of
Upper and lower bounds constraints of node-voltage are as the active power of each branch (1-2,1-3,2-3,2-4,3-5) is
follows: respectively 2p.u.,0.65 p.u.,2 p.u.,6 p.u. and 5 p.u..
4 2 3 5
Vi min ≤ Vi ≤ Vi max i∈n 1# 2#
(9)
G G
The line flow constraints are as follows:
-2
10 0
△ Plij is the additional active transmission power
generated in the line i-j due to the introduction of TCSC; KC -4
10 -0.05
Abstract— Nowadays, the power transmission network transmission of electrical energy. It is meant to enhance
is expanding and is getting more complicated day by day. The controllability and increase power the transfer capability of the
problems of uncontrolled loop flows, overloading, excess of short network. An efficient and reliable PSCAD stands for Power
circuit current levels and system instabilities are causes of System Computer Aided Design based simulation is used for
concern for a power engineer. These serious problems have solving the power system oscillation damping problem is
necessitated new transmission technologies to be adopted such as
presented. The proposed approach is carried out in simple two
FACTS (Flexible AC Transmission System) devices which make
electrical energy transmission more efficient and reliable. Among bus system [1] and [7].
the FACTS controllers the TCSC (Thyristor Controlled Series
II. FACTS CONTROLLERS
Compensators) plays a major role. TCSC is mainly used to
enhance line loadability and damp inter-area oscillations for A. FACTS
smooth synchronous operation of the interconnected regions.
Thus TCSC is used to enhance the effective performance of the Alternating current transmission systems incorporating
system. The main objective of this paper is to examine the power electronic-based and other static controllers to enhance
improvement of power system stability by introducing TCSC in controllability and increase power transfer capability. A power
the power system model through the inspection of their electronic-based system and other static equipment that
waveforms, where the design and simulation is done by using provide control of one or more AC transmission system
PSCAD (Power System Computer Aided Design). parameters [8].
Keywords- FACTS, TCSC, PSCAD, Dynamic Response, B. Basic Types Of FACTS Controllers
Three Phase Fault. In general, FACTS Controllers can be divided into
three categories.
I. INTRODUCTION
In a power system the effective power generation, • Series Controllers:
transmission and utilization is the foremost goals for an
electrical engineer. Among these three modules of a power The series controller could be variable impedance, such
system the transmission is more important to be considered as as capacitor, reactor, etc. or a combination to serve the desired
it includes more losses and instabilities. Nowadays, due to need. In principle, all series controllers inject voltage in series
increase in population the power transmission is expanding with the line. Even variable impedance multiplied by the
and is getting more complicated day by day. This leads to the current flow through it, represents an injected series voltage in
necessity of using new technologies to achieve effective power the line. As long as the voltage is in phase quadrature with the
transmission. line current, the series controller only supplies or consumes
• Increase transfer capability of transmission lines. variable reactive power. Any other phase relationship will
• Control the power flows. involve handling of real power as well.
• Assurance of system reliability, by increasing various
stability margins. • Shunt Controllers:
• More importantly, increase the overall efficiency by
optimizing the available facilities. As in the case of series controllers, the shunt controllers
may be variable impedance, variable source, or a combination
All these can be done using a group of high speed power of these. In principle, all shunt controllers inject current in to
electronics controllers called FACTS controllers. These the system at the point of connection. Even variable shunt
groups of controllers are expected to revolutionize the utilities impedance connected to the line voltage causes a variable
in many ways by rapidly and smoothly controlling power current flow and hence represents injection of current in to the
system quantities. Flexible Alternating Current Transmission line. As long as the injected current is in phase quadrature with
System (FACTS) is static equipment used for the AC the line voltage, the shunt controller only supplies or
Where ‘k’ is the degree of series compensation given in (3) IV. POWER SYSTEM COMPUTER AIDED DESIGN (PSCAD)
i.e., A. Introduction to PSCAD
PSCAD stands for Power System Computer Aided
Design. PSCAD is the Professional’s Tool for Power Systems
In series compensation, the FACTS are connected in Simulation. It is a powerful Transients Simulation Software by
series with the power system. It works as a controllable Manitoba HVDC Research Centre. PSCAD is a general-
voltage source. Series inductance occurs in long transmission purpose time domain simulation tool for studying behavior of
lines, and when a large current flow it causes a large voltage electrical networks. First developed in 1976, the EMTDC
drop. To compensate, series capacitors are connected. simulation program has been constantly evolving in its scope
and capabilities. Presently, it is used as a Graphical User
Interface for the EMTDC transients’ instantaneous solution
III. THYRISTOR CONTROLLER SERIES CAPACITOR (TCSC) engine. Users can now harness the power of EMTDC through
A capacitive reactance compensator which consists of a the user-friendly PSCAD interface on personal computers.
series capacitor bank shunted by a thyristor controlled reactor This seamlessly integrated visual environment supports all
in order to provide a smoothly variable series capacitive aspects of conducting a simulation including circuit assembly,
reactance. The Control Attributes of TCSC are listed below. real-time control, analysis and reporting. Simply put, PSCAD
• Current control is the professional’s tool for electromagnetic transient’s
• Damping Oscillations simulation. PSCAD comes with a comprehensive library of
• Transient and Dynamic stability models encompassing all aspects of AC and DC power
• Voltage Stability systems and controls. If we need a model that is not in the
• Fault current limiting. PSCAD library, we can create your own model and libraries
using the built-in graphical Component Workshop. PSCAD
supports models written in FORTRAN/C/C++, so constructing
models is easy. Engineers working with circuits consisting of
power electronic switches such as thyristors and GTOs will
99
2013 International Conference on Power, Energy and Control (ICPEC)
benefit from PSCAD’s Interpolated Network Solution. This PSCAD is a multi-purpose power system simulator and
permits study of circuits that would be impractical or almost can thus be used for any scenario where a detailed
impossible to simulate using other tools, and ensures a highly understanding of the full time domain of analysis is beneficial.
accurate solution in the least amount of time. The size of a This includes the design and modeling of virtually any
circuit to be simulated is limited only by the resources of the electrical power system. PSCAD in used in the planning,
computer. PSCAD automatically resizes to give the optimum design and operational phases of power systems. It is also very
performance. PSCAD has many advanced features to boost prevalent in power system research around the world.
productivity, including intelligent data forms, interactive
control and feedback, up-to-date documentation of the circuit V. DESIGN AND SIMULATION OF POWER SYSTEM
along with plots and comments, context sensitive help,
hierarchical designs, and multiple levels of zooming. PSCAD Here the simple two bus system as shown in fig 2 is
enables you to design circuits in a fraction of the time you considered for investigate the effectiveness of the proposed
would otherwise spend with text-based or semi-graphical approach [3] – [5]. The system with three phase fault with out
tools. PSCAD is a fast, accurate and easy-to-use power system TCSC as shown in fig 3. The corresponding voltage waveform
simulator for the design and verification of all types of power and the current waveform are shown in fig 7, fig 8 and fig 9;
systems. For power quality studies, power electronic design, the maximum system voltage is 300V and damping distortion
distributed generation and transmission planning, PSCAD time is 0.35. When one TCSC is connected to transmission
improves our power system performance and reliability [9]. line of the two bus system as shown in fig 10, the system
voltage is reduced to 250V and the damping distortion time
B. Applications reduced to 0.32sec. The voltage and current waveforms are
PSCAD becomes an indispensable tool for a variety shown in fig 14, fig 15and fig 16. When two TCSC is applied
of power system designs and studies. It is a multi-purpose tool. the two bus system as shown in fig 17, the system voltage is
It is equally capable in the areas of power electronic design reduced to 240V and the damping distortion time reduced to
and simulation, power quality analysis, and electrical utility 0.31sec. The voltage and current waveforms are shown in fig
system planning studies. 21 and fig 22.
As electrical power and power electronic systems Z1 = 52.9 [ohm] /_ 80.0 [°]
become more prevalent in electric vehicles, ships, trains, and 100.0 [MVA]
V Ph 230.0 [kV], 60.0 [Hz]
distributed generation system, the need for easy-to-use and
accurate simulation and modeling tools becomes ever more SUBSTATION 1 100.0 km SUBSTATION 2
important. It is easier and much less expensive to design and TLine
optimize electrical devices and systems prior to prototyping or 230.0 [kV], 60.0 [Hz] Ph V
manufacturing. Thus, PSCAD is becoming a true Power 100.0 [MVA]
V1 V2
System Computer Aided Design tool for a variety of industry Z1 = 52.9 [ohm] /_ 80.0 [°]
applications. PSCAD users include engineers and Figure 2 Design of simple power system PSCAD model
technologists from energy utilities, electrical equipment
manufacturers, engineering consulting firms, research and
Z1 = 52.9 [ohm] /_ 80.0 [°]
academic institutions. The applications of PSCAD are listed 5000.0 [MVA]
below. V Ph 230.0 [kV], 60.0 [Hz]
SUBSTATION 1 100.0 km SUBSTATION 2
TLine
• To investigate power system instabilities created by
harmonic resonance or control system interactions. 230.0 [kV], 60.0 [Hz] Ph V
5000.0 [MVA]
• To perform insulation co-ordination studies. Z1 = 52.9 [ohm] /_ 80.0 [°]
V1 V2
100
2013 International Conference on Power, Energy and Control (ICPEC)
1 .0
Z1 = 52.9 [ohm] /_ 80.0 [°]
Timed Com.
Fault Bus
Figure 6 ABC->G Logic AM
VOLTAGE 1 GM
V1a V1b V1c
400
300
200
AO
100
KB
0 6 Pulse
y
-100 Bridge
-200
-300 TIME
0.160 0.180 0.200 0.220 0.240 0.260 0.280 0.300 0.320 0.340 0.360 .
.
.
Figure 10 Systems with TCSC
Figure 7 Voltages at Bus Bar 1 V1 V2
VOLTAGE 2
1 V1A 1 V2A
400
V2a V2b V2c V1a V2a
300 2 V1B 2 V2B
200 V1b V2b
100
3 V1C 3 V2C
0
y
FAULT CURRENT
Ia Ib Ic
10.0
8.0 Figure 13
6.0
4.0
2.0
0.0
y
-2.0 VOLTAGE 1
-4.0
-6.0 V1a V1b V1c
300
-8.0
200
0.180 0.200 0.220 0.240 0.260 0.280 0.300 0.320 0.340 .
. 100
.
0
y
101
2013 International Conference on Power, Energy and Control (ICPEC)
VOLTAGE 2 V1
V2a V2b V2c V2
250
200
150 1 V1A
100 1 V2A
50 V1a
0 V2a
-50 2 V1B
y
-100 2 V2B
-150 V1b V2b
-200
-250 3 V1C 3 V2C
0.150 0.175 0.200 0.225 0.250 0.275 0.300 0.325 0.350 0.375 V1c V2c
Figure 18 Figure 19
FAULT CURRENT
Ia Ib Ic
10.0
8.0
6.0
4.0
2.0
0.0
y
-2.0
-4.0 Figure 20
-6.0
-8.0
0.180 0.200 0.220 0.240 0.260 0.280 0.300 0.320 0.340 VOLTAGE 1
V1a V1b V1c
300
Figure 16 Fault Current 200
Z1 = 52.9 [ohm] /_ 80.0 [°] 100
5000.0 [MVA] 0
V Ph 230.0 [kV], 60.0 [Hz]
y
1 .0
5000.0 [MVA] Com. 0.150 0.175 0.200 0.225 0.250 0.275 0.300 0.325 0.350 .
Z1 = 52.9 [ohm] /_ 80.0 [°] Bus .
AM .
GM
Timed Figure 21 Voltages at Bus Bar 2
Fault
ABC->G Logic
AO VOLTAGE 2
Com. KB V2a V2b V2c
Bus 6 Pulse 300
AM Bridge
200
GM
100
TIME
0
y
-100
AO -200
KB -300
6 Pulse
Bridge 0.160 0.180 0.200 0.220 0.240 0.260 0.280 0.300 0.320 0.340 .
.
.
TIME
Figure 22 Voltages at Bus Bar 2
WITHOUT TCSC:
Maximum Voltage V1 about 300 V
Maximum Voltage V2 about 300 V
Damping of Distortions at 0.35 sec
102
2013 International Conference on Power, Energy and Control (ICPEC)
VI. CONCLUSION
WITH TCSC: In this paper, an efficient PSCAD based simulation
Maximum Voltage V1 about 250 V using TCSC has been solved the power oscillation damping
Maximum Voltage V2 about 250 V problem. TCSC is very necessary when National Grid is
Damping of Distortions at 0.32 sec formed, to channel the power properly with firing angle
control mechanism. By controlling the firing angle of the
WITH TWO SERIES TCSC: thyristor valve from 180 degree to lower values the effective
Maximum Voltage V1 about 240 V impedance of the TCSC can be varied from capacitor
Maximum Voltage V2 about 240 V impedance to 3 times the capacitor impedance. During power
Damping of Distortions at 0.31 sec oscillations the impedance can be varied very fast between the
capacitor impedance and the maximum impedance.
vca
C C C C C
g1
1.0 1.0 0.1 1.0
phase with the line current. If the additional voltage created by
BRK
B
B
A
Power
Power
Q
P
1 .0
1 .0
T2
g2 g3
physical reactance of the capacitor. Thus TCSC is an effective
of impedance control to transmit more power. Also it is a
T3
g4 g5
VII. REFERENCES
T5
T6
[1] Chi-Shan Yu; Chih Wen Liu " A practical design of TCSC controllers
g6 for the inter-area transient stability control using real-time
measurements”, Power Engineering Society Winter Meeting, IEEE
Figure 23 Electric Systems with a Circuit Breaker Using TCSC Volume: 1 , Page(s): 661 - 666 vol.1 , 1999.
ACTIVE POWER [2] Dubey G. K, Doradla S. R, Joshi A and Sinha R. M. K, “Thyristor
2.0k
P1 Power Controllers”, New Age International Publishers, 2005.
0.0 [3] Fan L, Feliachi A and Schoder K, “Selection and design of A TCSC
-2.0k control signal in damping power system inter-area oscillations for
-4.0k multiple operating conditions.” Electrical Power & Energy Systs., vol-
-6.0k 62, pp. 127-137, 2002.
y
-8.0k [4] Jaewon Chang , Troy NY, Chow J.H."Time-optimal series capacitor
-10.0k control for damping interarea modes in interconnected power systems”,
-12.0k IEEE Power & Energy Society, Volume: 12 , Issue: 1 Page(s): 215 –
-14.0k
221,1997.
0.00 0.10 0.20 0.30 0.40 0.50 .
.
.
[5] Klein M, Rogers G. J and Kundur P, “A Fundamental Study of Inter-
Area Oscillations in Power Systems,” IEEE Transactions on Power
Figure 24 Active Power Systems, Vol. 6, No. 3, pp. 914-921, 1991.
[6] Mathur R. M, Verma R. K, "Thyristor based FACTS controllers for
REACTIVE POWER
electrical transmission systems", IEEE Press, 2002, pp 277-288.
0.2k
Q1 [7] Misra S. C, Prashar V. K, Jha I. S, Seema Gupta and Thiagarajan V,
“TCSC – Major role to play synchronous interconnections between two
0.0
regions”, 11th NPSC, India, 2000.
-0.2k
[8] Narain G. Hingorani and Laszlo Gyugyi,, “Understanding FACTS,”
-0.4k Standard Publishers Distributors, 2001.
KW
-0.6k [9] Olimpo Anaya-Lara and Acha E, “Modelling and Analysis of Custom
-0.8k Power Systems by PSCAD/EMTDC”, IEEE Transaction on power
-1.0k delivery, Vol 12, No. 1, pp. 266-272, Jan 2002..
-1.2k
0.00 0.10 0.20 0.30 0.40 0.50 .
.
.
103
Selection of TCSC Parameters: Capacitor and
Inductor
S. Meikandasivam1, Rajesh Kumar Nema2, and Shailendra Kumar Jain3
T1
XL
Capacitive region
L L
Clim to 180
Varies from XL to infinity
T2
10
study concentrates only on the above three factors. Firing angle in Deg.
-14
(ohms) (ohms)
-16
131.1929 406.5 96.0981 555.0
-18
KB Transmission Line Power Angle Curves With & Without FC
600
Without FC
-20 With FC
X: 90
Y: 552.2
500
-22
X: 90
Y: 405.1
-24 400
90 100 110 120 130 140 150 160 170 180
Firing angle in Deg.
Power in MW
Fig: 7 Reactance characteristic curve for < 1(only capacitive region)
300
O c c uranc e of Two
Res onanc e Points 100
50
X: 105
TCSC Reactance in %
Y: 0.05824
0
0 20 40 60 80 100 120 140 160 180
0 Delta in Deg.
X: 104
Y: -0.07175
Fig. 10 Power angle curves of KB transmission line with and without FC.
-50 O c c uranc e of c ross ove r be twee n
Capac itanc e to Induc tanc e Power angle curves for Kanpur-Ballabhgarh transmission
line and along with FC are shown in Fig. 11. Table III shows
-100
the possible power flows for various values of ‘’ from 1.4 to
3 and also Kanpur-Ballabhgarh line power flows are also
-150
90 100 110 120 130 140
Firing angle in Deg.
150 160 170 180 mentioned at ‘’ = 2.7432. Data which are highlighted in
Fig: 8 Multi Resonance Reactance characteristic curve for > 3 Table III are in capacitive mode of TCSC and rests are in
inductive mode. From the analysis, capacitive mode power
VII. CASE STUDY ON KANPUR - BALLABHGARH TCSC flows are greater than 555 MW (power at which line along
PROJECT with FC) and inductive modes are lesser, also shown in same
Fig. 10. Data specified in bold are power flows nearer to
First TCSC project commissioned in India is between
resonance region which are not to trigger on those firing
Kanpur-Ballabhgarh 3-phase, 400 kV, 400 km long
angles.
transmission line to increase the power flow, approximately
from 400 MW to 600 MW[10]. Fig. 9 shows the single phase
equivalent to Kanpur-Ballabhgarh transmission line. The TABLE III.
POWER FLOW PKB AT TRANSMISSION ANGLE 90O WITH FC +TCSC
transmission line has line reactance of 1.044 mH/km, fixed
Power Transfer PKB at transmission angle 90o with FC
series compensation of 27% (Capacitor of 90.7μF) and TCSC and TCSC (MW)
of 8 to 20% of compensation (Capacitor is 306 μF and =
Firing Firing Firing Firing Firing Firing
Inductor is 4.4 mH) was chosen [12] with factor ‘’ is 2.7432. XC/XL angle angle angle angle angle angle
Considering Kanpur-Ballabhgarh transmission line for 90o 108o 126o 144o 162o 180o
1.4 498.7 396.0 818.0 644.0 624.4 622.4
TCSC characteristics study, Table II shows the net reactance 1.6 519.0 479.8 -363.2 655.8 625.2 622.4
and power flow PKB between the transmission line with and 1.8 529.4 508.7 36.7 675.8 626.0 622.4
without fixed capacitor [9]. Maximum Power transfer on the 2.0 535.7 523.2 469.8 715.6 627.0 622.4
line without any compensation is 406.5 MW (approximately) 2.2 539.8 531.9 505.0 831.2 628.3 622.4
2.4 542.7 537.6 522.7 441.6 629.7 622.4
and along with fixed series compensation (FC) is 555 MW. 2.6 544.8 541.7 533.3 31.4 631.5 622.4
Also shown through power angle curves in Fig. 10 2.743 546.3 544.9 540.4 458.0 633.7 622.4
2.8 546.3 544.9 540.4 458.0 633.7 622.4
3 547.6 547.5 545.5 502.9 636.3 622.4
Table III shows maximum power flows between 90o to thyristor controlled series compensation”, 30th Annual Conference
IEEE Industrial Electronics Society, vol. 2, pp. 1128- 1132, 2004.
180o of firing angles for various values of ‘’. For = 1.4, [6] C. R. Fuerte-Esquivel, E. Acha, and H. Ambriz-PBrez, “A Thyristor
possible variation of capacitive mode power flows are from Controlled Series Compensator Model for the Power Flow Solution of
622.4 MW to 818 MW between 180o to 126o of firing angle Practical Power Networks”, TEEE Transactions on Power Systems. vol.
15, no. 1, pp. 58- 64, February 2000.
and change in power with respect to firing angle is smaller. At
[7] Geng juncheng, Tong luyuan, and Wang Zhonghong, and Ge Jun,
=3, variation is from 622.4 MW to 636.6 MW for 180o to “Mathematical Model for describing characteristics of TCSC”, IEEE
162o of firing angle and change in power is greater. From the 2002 PP- 14981-502
analysis, fine tuning for improving the power flow is possible [8] L. F. W. de Souza, E. H. Watanabe, J . E. R. Alves, and L. A. S.
Pilotto, “Thyristor and Gate Controlled Series Capacitors Comparison of
at ‘’ is small, but effect of harmonics has to be considered. Components Rating”, IEEE, 2003, pp: 2542-2547.
Also firing angle at 90o, inductive mode power flow is varied [9] Bijoy Kumar Sahoo and Narendra Kumar, “Power Flow Control Using
from 498.7 MW to 547.6 MW for various values of ‘’; 1.4 to TCSC”, M.Tech dissertation, Dept. of Electrical Engineering, Delhi
college of Engineering, 2005-2006.
3. From the discussion, depends on the requirement of end [10] Arunachalam M, Ghamandi Lal, Rajiv C G, BHEL, Bangalore Babu
side demands, ‘’ has been selected. Narayanan MM, CPRI, Bangalore, India, performance verification of
2200
Power Angle Curves with TCSC K=8%, w=1.4 TCSC control and protection equipment using RTDS, 15th PSCC, Liege,
X: 90
Y: 2169
2005,pp 22-26.
2000
1800
X. BIOGRAPHIES
1600 Powe r c urve s with
& without FC
Power in MW
1400
1200
800
X: 90
Y: 552.2
600
X: 90
Y: 405.1
400
X: 90
200 Y: 333
0
0 20 40 60 80 100 120 140 160 180
Delta in Deg.
o
Fig. 11 Power angle curves at firing angle 108 and 162 for various ‘’
S. Meikandasivam was received the Bachelor Degree in Electrical and
Electronics Engineering in 2002 and Master Degree (Power Systems) in 2005.
VIII. CONCLUSION He also worked as a Lecturer in EEE dept. of Sri Chandrasekharendra
This paper discusses about the operation, reactance Saraswati Viswa Mahavidyalaya (Deemed University), Kanchipuram. Now he
is pursuing the PhD Degree at Maulana Azad National Institute of
characteristic and resonance condition of TCSC. It Technology (MANIT), Bhopal, India. Currently he is working as Assistant
investigates the condition of single and multi resonance points Professor in VIT University, Vellore.
for different values of ‘’. From the report of resonance Rajesh Kumar Nema was received his PhD degree in Electrical Engineering
behavior, it is concluded that ‘’ should be optimum between from Barkatullah University, Bhopal, India in 2004. He is currently AP at the
Depart. of Electrical Engg., MANIT, Bhopal, India. His current research
1.4 to 3 to select an appropriate value of inductor and interest include power conditioning unit for Renewable Energy storage system
capacitor. particularly Solar Energy, Hybrid Energy Systems, Grid Interconnection of
For the selected value of ‘’, study has been conducted to Renewable Energy sources.
Shailendra Kumar Jain received his B.E.(Elect.), M.E.(Power Elex), Ph.D.
simulate power transfers over Kanpur–Ballabhgarh degree in 1990, 1994 and 2003 respectively and his PDF at UWO London,
transmission line. Possible power flows on the Transmission ON, Canada in 2007. He is currently working as Assistant Professor at the
line are tabulated in both capacitive and inductive modes of Department of Electrical Engineering, NIT, Bhopal, India. He has been
awarded “Career Award for Young Teachers” by AICTE New Delhi, India for
TCSC for various values of ‘’. the year 2003-2004. His research interests include power electronics and
This focus an idea for selecting the TCSC parameters: electric drives, power quality improvement, active power filters, high-power
inductor and capacitor as per the requirement of power factor converters and fuel cell based distributed generation.
demands on end side. Above study is based on consideration
of degree of series compensation and ‘’, but not considering
the thermal loading of the transmission line, maximum
allowable current limit and TCSC loop current limit etc.
IX. REFERENCES
[1] Arthur R. Bergen Vijay Vittal, “Power System Analysis”, Second
Edition, Pearson Education Asia, pp 528-529.
[2] N. G. Hingorani and L. Gyugyi, Understanding FACTS Concepts and
Technology of Flexible AC Transmission Systems, IEEE Press,
[3] R. M. Mathur and R.K. Varma, Thyristor based FACTS controllers for
Electrical transmission systems, John Wiley & Sons Inc.,
[4] http://www.answers.com/topic/subsynchronous-
resonance?cat=technology
[5] Guowen H U, Ming CHENG, and Guilong CAI, “Relation between
Fundamental Frequency Equivalent Impedance and Resonant Point for
1
Abstract— Wind power penetration is rapidly growing all over It will be further necessary to transmit the generated power
the world as the alternative, renewable and environment friendly through transmission networks that can sustain large power
resource of energy production. With this rapid growth of wind flows. It is well known that series compensation is an effective
power, the power systems of future will likely see the integration means of increasing power transfer capability of an existing
of large wind farms with electrical networks that are series transmission network.
compensated for ensuring stable transmission of bulk power. This
may potentially lead to subsynchronous resonance (SSR) issues. However, series compensation is shown to cause a highly
Although SSR is a well-understood phenomenon that can be detrimental phenomenon called Subsynchronous Resonance
mitigated with FACTS devices, scant information is available on (SSR) in electrical networks. SSR manifests itself in two ways:
the SSR problem in a series compensated wind farm. This paper
the induction generator (IG) effect and torsional interaction
reports the occurrence and mitigation of SSR caused by induction
generator (IG) effect as well as torsional interactions (TI), in a (TI). The induction generator effect is caused by the interplay
series compensated wind farm. SSR suppression is achieved as an of the series compensated network and the generator stator
added advantage of a Thyristor Controlled Series Capacitor circuit. Meanwhile, torsional interaction is caused by the
(TCSC) actually installed to increase the power transfer interaction of the mechanical/torsional system and the
capability of the transmission line. In this study, a wind farm electrical network. Flexible AC Transmission Systems
employing self-excited induction generator (SEIG) is connected to (FACTS) can provide an effective solution to mitigate SSR [1-
the grid through a series compensated line. A Thyristor 3].
Controlled Series Capacitor (TCSC) is shown to damp A vast body of literature is available on the mitigation of
subsynchronous oscillations when provided with closed loop
subsynchronous resonance in a conventional thermal power
current control. Extensive simulations have been carried out
using EMTDC/PSCAD to validate the performance of TCSC in plant [1]. However, very little information is presented on the
damping SSR. subsynchronous resonance issues in a series compensated wind
farm [2]. The major difference between WECS and
Index Terms—Wind power systems, FACTS, Self-excited conventional power plants is that WECS uses induction
Induction Generator (SEIG), Series Compensation, generators as opposed to synchronous generators. In this
Subsynchronous Resonance (SSR), Thyristor Controlled paper, it is shown that induction generators are also prone to
Series Capacitors (TCSC), Open Loop Control, Closed SSR interplay. Growing subsynchronous oscillations both due
loop Current Control. to induction generator (IG) effect as well as torsional
interaction (TI) are shown to be the cause of system instability
in a series compensated wind farm.
I. INTRODUCTION A thyristor controlled series capacitor (TCSC) is employed
farm. The wind farm is connected to the grid through a series Ns − N r (3)
s=
compensated transmission network. The study system is Ns
derived from the IEEE First Benchmark Model (FBM) and the
wind farm is modeled by a group of coherent induction
When the magnitude of this resistance exceeds the sum of the
generators with shunt capacitance. The entire mechanical
armature and network resistances at a resonant frequency,
system, comprising the gear train, rotor blades and tower, of
the wind turbine is modeled by a single mass, as their there will be self-excitation.
individual natural resonant frequencies are very close.
Nonlinear time domain simulations of fault studies are carried The induction generator effect can be explained in case of a
out using EMTDC/PSCAD. wind farm comprising induction generator from its equivalent
circuit drawn in Fig. 1.
The organization of the paper is as follows. The two
mechanisms of SSR - induction generator (IG) effect and R1 jX1 jX2
torsional interaction (TI) are briefly described in section II.
Section III outlines the study system configuration; section IV
proves the potential occurrence of SSR both due to IG effect
and TI interactions in a series compensated wind farm. Rc jXm R2/s
Section V covers the selection of TCSC parameters. The
performance of the TCSC in mitigating SSR is shown in
section VI; finally section VII concludes the paper.
0.8
0.7
0.6
Fig. 2 Wind generator study system with TCSC
0.5
0.4
IV. SSR IN SERIES COMPENSATED WIND FARM
In this section both the induction generator self excitation 4 4.5 5 5.5 6
and torsional interaction effects are studied in the study system Time (s)
Fig. 4 Generator terminal voltage for 100 MW power transfer for 90% series
depicted in Fig. 2. The firing angle control of the TCSC is
compensation
blocked so that the possibility of SSR can be examined in a
non-FACTS equipped series compensated wind farm. A three
phase to ground fault is implemented to study potential of both 1.07
self excitation and transient torque SSR. The power flow 1.06
1.03
A. Induction Generator Self-excitation Effect
1.02
Studies reported in this section show that there are two 1.01
• Power transfer level. Fig. 5 Generator rotor speed for 100 MW power transfer for 90% series
• Level of series compensation. compensation
These factors are addressed separately.
The generator power output is now increased to 500 MW.
For a power transfer of 100 MW, the induction generator At this high power level, the induction generator is operated at
self excitation effect is not seen to be so prominent. Even a much higher speed over the synchronous speed. This
though oscillations are visible in the electromagnetic torque, increased power transfer makes the apparent negative rotor
machine terminal voltage and rotor speed, they are seen to resistance exceed the sum of total armature and network
decay with time. This is depicted in Fig. 3 - Fig. 5. If the line resistance. Thus giving rise to subsynchronous oscillations.
resistance is decreased, these oscillations become larger and The dominant electrical mode in this case is 20.54 Hz.
continue for a longer duration which is expected of induction
generator self excitation oscillations. However, the line Next, the series compensation level is varied for 500 MW
resistance reduction is not a realistic option and is hence not generator power output. It is observed that with increasing
reported here. series compensation levels the oscillations due to induction
generator self excitation get enhanced making the system
eventually unstable. The electromagnetic torque is depicted for
1
50%, 65% and 90% in Fig. 6, 7 and 8, respectively. The
0.5 electrical frequencies fe in the electromagnetic torque increases
Electromagnetic Torque (p.u.)
0
according to (1) and consequently, the rotor torque frequency
fr decreases as in (2).
-0.5
-1
-1.5
-2
-2.5
4 4.5 5 5.5 6
Time (s)
Fig. 3 Electromagnetic torque for 100 MW power transfer for 90% series
compensation
4
1
It is observed that with increasing series compensation
0.5
levels the oscillations due to torsional interaction also get
Electromagnetic torque (p.u.)
0 enhanced making the system eventually unstable. The
-0.5
mechanical torque between Mass 1 and Mass 2 is depicted for
50%, 65% and 90% in Fig. 9, 10 and 11 respectively.
-1
-1.5 2
-2
0.5
Electromagnetic torque (p.u.)
0
0
-0.5
-0.5
0 5 10 15 20
-1 Time (s)
-1.5 Fig. 9 Mechanical torque between mass 1 and 2 (T12) for 50% series
compensation and fr = 0.8 Hz
-2
3
-2.5
4
0
Electromagnetic torque (p.u.)
2
-1
0
-2
5 10 15 20
-2 Time (s)
Fig. 10 Mechanical torque between mass 1 and 2 (T12) for 65% series
compensation and fn = 0.8 Hz
-4
4
-6
4 4.5 5 5.5 6 3
Mechanical Torque between
Mass 1 and Mass 2 (p.u.)
Time (s)
Fig. 8 Electromagnetic torque for 90% series compensation 2
B. Torsional Interactions 0
α
In this application, the TCSC is assumed to be primarily
employed in the network for controlling line reactance and
hence control of power flow. The SSR damping function is
added through constant current control for this study. It is
reported [4] that a TCSC when operating at fundamental
frequency offers a pure capacitive reactance to increase the
power transfer capability of the network. On the other hand the
same TCSC offers resistive impedance at subsynchronous Fig. 13 TCSC Constant Current Controller
frequencies which need to be damped. The resistive impedance
of the TCSC increases with the increased boost factor which is Here Iref is the pre-fault or pre-contingency current
the ratio of the capacitive reactance offered by the TCSC and calculated from EMTDC/PSCAD line-current phasor. The
the total line reactance. Hence, the TCSC also provides a main current controller is a PI Controller. The parameters of
resistive damping to the subsynchronous oscillations. this controller are also adjusted systematically through
electromagnetic transient simulation studies by hit-trial to get
the minimum settling time or fastest damping criterion.
The general configuration of a TCSC is shown below:
X C2 2β + sin2β 4X C2 cos 2 β ktankβ − tanβ In this case also, the damping performance of the TCSC is
X TCSC = X C − +
XC − XL π XC − XL k 2 − 1 π shown for the worst possible operating condition of 500 MW
(4) power flow and 90% series compensation. The signals
reported to show the damping performance of TCSC are:
where β = angle of advance (before the forward voltage
becomes zero) = π-α; α is the firing angle of the thyristors. It Electromagnetic torque of the generator (Te)
is noted from (4) that a parallel resonance is created between Generator rotor speed (Wr)
XC and XL at the fundamental frequency, corresponding to the Generator terminal voltage (Vt)
values of firing angle αres, given by:
πω Fig. 14, 15 and 16 display the generator electromagnetic-
α res = π - (2m - 1) (5) torque, generator rotor speed, machine terminal voltage,
2ω r
respectively.
3
The different resonances can be reduced to one by proper Without TCSC
choice of k = ωr/ω = √ XC/ XL in the range of 900 < α < 1800. 2 With TCSC CC
Electromagnetic torque (p.u.)
-5
4 5 6 7 8 9 10
Time(s)
Fig. 14 Damping of SSO in the electromagnetic torque
6
1.08 1.6
Without TCSC Without TCSC
With TCSC CC 1.5 With TCSC CC
1.4
1.04
1.3
1.02
1.2
1
1.1
0.98 1
0.96 0.9
4 5 6 7 8 9 10 5 10 15 20
Time(s) Time(s)
Fig. 15 Damping of SSO in the generator speed Fig. 18 Damping of SSO in the rotor speed by TCSC
1.6
Without TCSC
Generator terminal voltage (p.u.)
380
1.4 With TCSC CC
1.2
375
1
Xtcsc (Ohm)
0.8
370
0.6
0.4 365
0.2
4 5 6 7 8 9 10
Time(s) 360
5 10 15 20
Fig. 16 Damping of SSO in the generator terminal voltage Time(s)
Fig. 19 Variation of TCSC reactance in damping of SSO
B. Damping performance of TCSC for TI
Mechanical torque between Mass 1 and Mass 2. With the rapid growth of wind power penetration into the
power system grid, wind farms will likely be evacuating bulk
Generator rotor speed (Wr)
power through series compensated networks. This will render
TCSC reactance (XTCSC)
the power system vulnerable to SSR. In this paper a thyristor
controlled series capacitor is applied to damp SSR in such a
Fig 17, 18 and 19 demonstrate mechanical torque between series compensated wind farm. The following conclusions are
Mass 1 and 2, generator rotor speed and TCSC susceptance drawn from extensive electromagnetic transient simulation
respectively. It is apparent from the figures that TCSC closed- studies over widely varying levels of series compensation:
loop current control effectively damps the SSO due to TI
effect. SSR is a potential threat in series compensated wind
4 farms even at realistic levels of series compensation.
Without FACTS
With TCSC CC
A TCSC which is originally employed to improve
3
power transfer capability of the transmission line is
Mechanical Torque between
Mass 1 and Mass 2 (p.u.)
K = Percentage series compensation XC/X∑ =90%, 65%, 50%; Ysni Semsedini received his B. Sc and M. Sc degrees in
XL = Calculated from (4) to avoid multiple resonant peaks in Electrical and Computer Engineering from the University
of Western Ontario, London, Ontario, Canada in 2003 and
TCSC reactance-firing angle characteristics. TCSC Current 2006 respectively. He was a distribution engineer in
Controller: KP = 0.0; KI = 200; Kitchener – Wilmot Hydro, Kitchener, Ontario, Canada
from 2003 to 2004. Currently he is working in London
REFERENCES Hydro, London, ON. His research interests include
modeling and performance studies of wind farms and
FACTS.
[1] IEEE Working Committee Report, “Third Supplement to a Bibliography
for the Study of Subsynchronous Resonance between Rotating
Machines and Power Systems,” IEEE Trans. on Power Systems, vol. 6,
Soubhik Auddy received the B.E. degree in Electrical
no. 2, pp. 830-834, May 1991
Engineering from Jadavpur University, Calcutta, India in
[2] P. Pourbeik, R. J. Koessler, D. L. Dickmander, and W. Wong,
2000 and the M.Tech. degree in Electrical Engineering
“Integration of Large Wind Farms into Utility Grids (Part 2 –
from the Indian Institute of Technology Kanpur, India in
Performance Issues),” in Proc. 2003 IEEE PES General Meeting Conf,
2003. He is currently working towards the Ph.D. degree at
pp. 1520-1525.
the University of Western Ontario, Ontario, Canada. His
[3] R.M. Mathur and R.K. Varma, Thyristor-Based FACTS Controllers for
research interests include FACTS, power system dynamics
Electrical Transmission Systems IEEE Press and Wiley Interscience,
and stability.
New York, USA, Feb. 2002.
[4] W. Zhu, R. Spee, R.R. Mohler, G.C. Alexander, W.A. Mittelstadt, D.
Maratukulam, “An EMTP Study of SSR Mitigation Using the Thyristor
Controlled Series Capacitor”, IEEE Transactions on Power Delivery,
Vol. 10, No. 3, pp. 1479-1485, July 95.
[5] IEEE Committee Report, “Reader’s Guide to Subsynchronous
Resonance,” IEEE Trans. on Power Systems, vol. 7, no. 1, pp. 150-157,
February 1992.
[6] J.F. Hauer, W.A. Mittelstadt, R.J. Piwko, B.L. Damsky, and J.D. Eden,
“Modulation and SSR Tests Performed on the BPA 500kV Thyristor
Controlled Series Capacitor Unit at Slatt Substation”, IEEE Trans.
Power Systems, vol. 11, No.2 May 1996, pp. 801-06
[7] T. Thiringer and J. A. Dahlberg, “Periodic Pulsations from a Three-
Bladed Wind Turbine,” IEEE Trans. on Energy Conversion, vol. 16, no.
2, pp. 128-133, June 2001.
[8] E. N. Henrichsen and P. J. Nolan, “Dynamics and Stability of Wind
Turbine Generators,” IEEE Trans. on Power Apparatus and Systems,
vol. PAS-101, no. 8, pp. 2640-2648, Aug. 1982
[9] R. K. Varma and S. Auddy, “Mitigation of subsynchronous resonance in
a series compensated wind farm using static var compensator,”
presented at the IEEE General Meeting, Montréal, Québec, June 18–22,
2006, Paper 06 GM1272.
[10] IEEE Committee Report, “First Benchmark Model for Computer
Simulation of Subsynchronous Resonance,” IEEE Trans. on Power
Apparatus and Systems ,vol. PAS-96, no. 5, pp. 1565-1572, Sept. / Oct.
1977
[11] DSA Power Tools User manual, Power Tech Lab, Surrey, BC, 2005
[12] EMTDC PSCAD User Manual, HVDC Research Center, Manitoba,
2003.
[13] P. Kundur, Power Systems Stability and Control: New McGraw-Hill,
1994