Professional Documents
Culture Documents
Description
Advantages
The dynamx™ Ultima valves, series DXU_C, are electronic, pressure-independent
4-in-1 solution flow-control valves. They combine four functions: (1) a flow-control valve, (2) a
dynamic, pressure-independent balancing valve a (3) shut-off valve and (4) an
perfect variable flow control energy monitoring device.
flow and energy registration
DXU is used in HVAC systems with variable flow and is designed e.g. for AHU, heat
no minimal ∆p required exchangers, etc. DXU replaces the (static) balancing valve, as well as the control
energy saving valve.
automatic hydronic balancing The DXU series are available as 2-port or 3-port valves with different flow ranges for
optimal sizing. DXU can be used in HVAC systems for buildings with a nominal
remote commissioning
system pressure of 16 bar (PN16) and water temperatures: +2°C..+130°C 2) (non-
patented technology condensing).
EP230793
Optionally, DXU can be implemented in PN25 or additional functions can be added,
for example a water temperature controller.
Content
1. How it works
A
The dynamx™ valves are designed to accurately control the flow through each
consumer device. In order to achieve this, dynamx™ has 4 basic building blocks:
a valve
an actuator
a flow sensor
B
a flow controller
On top of these basic building blocks additional features can be added, like for example a water temperature controller. C
In analog mode, the internal flow controller of the dynamx™ valve receives a setpoint from the external
controller Y1: 0..10Vdc. Internally this setpoint is converted into a flow setpoint, either for heating or
cooling. Example:
All rights reserved © 2008-2018 BELPARTS NV 10/2018 EN18v1.4 Patented – European patent No. 2307938 Subject to change without prior notice
The integrated flow sensor measures continuously the actual flow. The intern control loop will
compare the actual flow with the desired flow and adjust the position of the control valve until the
measured flow is equal to the required flow rate setpoint.
Thus DXU will control the flow towards the desired setpoint, independent of potential pressure
fluctuations in the system e.g. in case of part load. The control valve adapts automatically to the
system parameters and searches for the ideal setpoint, to guarantee a maximum comfort for the user
with minimal energy consumption.
Regardless of the operating mode, DXU can be used for a variable or constant flow control or a
maximum flow limit. The output signal X1: 0..10Vdc, representing the actual measured flow, can be
used for monitoring the actual flow.
The dynamx™ DXU valves can optionally be supplied with a MODBUS RTU
or BACnet MSTP bus-communication interface. By integrating the dynamx™
valves into a MODBUS or BACnet network, the setpoint can also be set via
the bus, the actual flow can be monitored remotely, etc. A selection of
commissioning settings can also be adjusted over the bus.
2. Technical data
Electrical
A
Power supply Uv AC 24 Volt (±10%), 50Hz
Input signal Y 1
Feedback signal X1
0..10Vdc (0.17mA)
0..10Vdc (≤ 2mA) the actual flow, scaled to the B
maximum flow settings for heating or cooling
Electric wiring 1) PVC cable, 4x 0,5mm² (length LC)
Bus connection STP cable, 4x twisted pair, length LC
C
Flow measurement
Sensor type ultrasonic TTM, no moving parts
Flow sensor class approved according to 2014/32/EU
and EN1434-4:2007
All rights reserved © 2008-2018 BELPARTS NV 10/2018 EN18v1.4 Patented – European patent No. 2307938 Subject to change without prior notice
Measuring unit m³/h 2), l/s, l/min, gpm (UK), gpm (US)
Temperature measuring 3)
Sensor type Pt500 or Pt1000 according to EN60751
Sensor pairing according to MID-2014/32/EU, EN1434-4:2007
Hydronics
Construction DXU2 2-port
DXU3 3-port, mixing
Nominal pressure rating PN16 (16 bar) 3)
Control characteristic equal percentage 2) or linear
Valve seat leakage tight sealing ( EN 1349 VI G1)
Differential pressure min. no minimum differential pressure required
max. depending on DN size
Flow setpoint control analog (Y1), via bus communication or via LCD
Medium water (glycol free)
Medium quality according to VDI 2035
Medium temperature +5°C..+130°C
Connections flanges PN16
according to EN1092-2 Type 21
Start-up time 3..5min after power-up
Powerless position last position
Material
Housing polypropylene, steel
Wet parts brass, bronze, EPDM, stainless steel (1.4401,
1.4122, 1.4301), thermoplastics, ceramics
3. LCD display
The DXU flow-control valves are delivered with an LCD display. The display
A
shows the flow, the water temperature and other key values.
The built-in keyboard push buttons enables the user to read and/or modify
settings of all major operating parameters of the DXU. B
LCD display with navigation pad LCD display 2x16 characters (backlit Liquid Crystal Display)
User input 3x push buttons
C
MODBUS RTU
BACnet MSTP
These types of bus communication are very well adapted for communication on a
field level. It is simple, while offering reliable and robust data communication. The
MODBUS communication technology is open, license-free and is available for each
BMS-system on the market.
Technical specifications
MODBUS protocol RTU/MSTP, slave
BACnet protocol MSTP, slave
Physical layer RS485, 2-wire twisted pair
Bus termination 120Ω terminal resistor at each end of the bus
Communication settings 2) 9600, 19200 of 38400 2) Baud
1 start bit
even 2)/odd/no parity
8 data bits
1 stop bit
Topology multi-drop bus, maximum length 1.000m
Drop length maximum 2m, preferably in daisy chain
Bus cable type shielded twisted pair STP or FTP
1) the installer is responsible for complying with local EMC regulations when installing,
connecting and commissioning DXU to a communication bus
3) can be set via the LCD display (when ordered) or via dxLink™ commissioning tool over
MODBUS communication
5. Electrical wiring
DXU_C . _ _4_ _
A
DXU_ C. _ _5_ _
B
C
All rights reserved © 2008-2018 BELPARTS NV 10/2018 EN18v1.4 Patented – European patent No. 2307938 Subject to change without prior notice
- EN 61000-3-2 (2014)
- EN 61000-3-3 (2013)
- EN 61000-6-1 (2007)
- EN 61000-6-3 (2007) ( A1: 2011 / AC: 2012 )
6. Electrical consumption
Type DN P Dim
[ mm ] [W ] [ VA ]
DXU_F050C. _ _ _ _ _ 50 5,5 6
DXU_F065C. _ _ _ _ _ 65 5,5 6
DXU_F080C. _ _ _ _ _ 80 8,5 9
DXU_F100C. _ _ _ _ _ 100 8,5 9
DXU_F150C. _ _ _ _ _ 150 20,5 21
Legend
7. Temperature sensors
The dynamx™ DXU valves are available with two temperature sensors for the measurement of the in- and output water temperature.
Both temperature sensors T1 and T2 have a free cable length of 2m and must be mounted on site.
A
B
C
All rights reserved © 2008-2018 BELPARTS NV 10/2018 EN18v1.4 Patented – European patent No. 2307938 Subject to change without prior notice
DXU2F_C DXU3F_C
1)
temperature sensor with sensor pocket
T1 T2 65mm 90mm
1)
stainless steel AISI 304 (1.4301), process connection R½ (standard 2pcs
sensor pockets included in the scope of delivery)
2)
other mounting accessories for the temperature sensors are not a part of the
delivery scope and have to be ordered separately.
Mounting example
8. Flow range
In order to achieve optimum sizing and to minimize pump consumption, dynamx™ flow-control valves are available with different
A
flow rates.
DXU_F050C. _ _ _ _ _
DXU_F065C. _ _ _ _ _
50
65
30,5
48,8
105
175
6.811
10.903
9.633
15.419
13.623
21.806
30.000
48.759
C
DXU_F080C. _ _ _ _ _ 80 70,7 280 15.811 22.361 31.623 80.000
DXU_F100C. _ _ _ _ _ 100 118,7 420 26.541 37.534 53.081 118.693
DXU_F150C. _ _ _ _ _ 150 254,7 1.050 56.959 80.552 113.917 254.726
All rights reserved © 2008-2018 BELPARTS NV 10/2018 EN18v1.4 Patented – European patent No. 2307938 Subject to change without prior notice
Legend
All dynamx™ flow-control valves can be integrated smoothly into each Building Management Systems or they can also be
implemented as stand-alone devices.
Type Description
009940 DX.10E.009940 dxLink™ software license
1)
requires a DXU MODBUS version
Flow direction A
The DXU flow-control valves have a fixed flow direction, as specified in the drawing. An arrow on the valve body indicates the
in- and output of the flow control valve.
B
C
All rights reserved © 2008-2018 BELPARTS NV 10/2018 EN18v1.4 Patented – European patent No. 2307938 Subject to change without prior notice
C.101 - 01 Mounting instructions
C.101 - 02 User manual MODBUS RTU/MSTP
C.101 - 03 User manual BACnet/MSTP
C.101 - 04 Data files REVIT
Belparts, dynamx, dynamic flow networking, DFN and dxLink are registered brands and/or tr ademarks of Belparts NV. All rights
reserved.
MS Windows is a registered trademark of Microsoft Corp. MODBUS is a registered trademark of Schneider Electric. BACnet is a
registered trademark of the American Society of Heating, Refrigerating and Air-Conditioning Engineers (Ashrae).
13.
www.belparts.com
Dimensions
DXU3F_C
DXU2F_C
C101
www.belparts.com
valve flow sensor
Type DN Øk1 d1 z b1 Øk2 d2 z b2 D L L2 H H1 H2 H4 B1 m
[ mm ] [ mm ] [ mm ] # [ mm ] [ mm ] # [ mm ] [ mm ] [ mm ] [ mm ] [ mm ] [ mm ] [ mm ] [ mm ] [ mm ] [ kg ]
13. Dimensions (continued)
DXU2F050C._ 1 _ _ _ 125 Ø18 4 20 125 Ø18 4 20 165 503 115 412 282 225 130 109 31,5
50
DXU2F050C._ 2 _ _ _ 125 Ø18 4 20 125 Ø18 4 20 165 503 115 488 358 298 130 109 32,5
DXU2F065C._ 1 _ _ _ 145 Ø18 4 20 145 Ø18 8 22 185 593 145 485 335 225 150 109 51,1
65
DXU2F065C._ 2 _ _ _ 145 Ø18 4 20 145 Ø18 8 22 185 593 145 636 486 376 150 109 52,8
DXU2F080C._ 1 _ _ _ 160 Ø18 8 22 160 Ø18 8 24 200 613 155 658 496 376 162 104 65,0
80
DXU2F080C._ 2 _ _ _ 160 Ø18 8 22 160 Ø18 8 24 200 613 155 817 655 670 162 104 68,8
DXU2F100C._ 1 _ _ _ 180 Ø18 8 24 180 Ø18 8 24 220 713 175 688 506 376 182 104 102,5
100
DXU2F100C._ 2 _ _ _ 180 Ø18 8 24 180 Ø18 8 24 220 713 175 847 665 370 182 104 106,3
DXU2F150C._ 1 _ _ _ 240 Ø22 8 26 240 Ø23 8 31 285 983 240 1012 805 670 207 135 234,3
150
DXU2F150C._ 2 _ _ _ 240 Ø22 8 26 240 Ø23 8 31 285 983 240 1012 805 670 207 135 234,3
DXU3F050C._ 1 _ _ _ 125 Ø18 4 20 125 Ø18 4 20 165 503 115 382 282 225 100 109 27,8
50
DXU3F050C._ 2 _ _ _ 125 Ø18 4 20 125 Ø18 4 20 165 503 115 458 358 298 100 109 28,8
DXU3F065C._ 1 _ _ _ 145 Ø18 4 20 145 Ø18 8 22 185 593 145 455 335 225 120 109 46,3
65
DXU3F065C._ 2 _ _ _ 145 Ø18 4 20 145 Ø18 8 22 185 593 145 606 486 376 120 109 48,0
DXU3F080C._ 1 _ _ _ 160 Ø18 8 22 160 Ø18 8 24 200 613 155 626 496 376 130 100 59,2
80
DXU3F080C._ 2 _ _ _ 160 Ø18 8 22 160 Ø18 8 24 200 613 155 785 655 670 130 100 63,0
DXU3F100C._ 1 _ _ _ 180 Ø18 8 24 180 Ø18 8 24 220 713 175 656 506 376 150 100 95,6
100
DXU3F100C._ 2 _ _ _ 180 Ø18 8 24 180 Ø18 8 24 220 713 175 815 665 370 150 100 99,4
DXU3F150C._ 1 _ _ _ 240 Ø22 8 26 240 Ø23 8 31 285 983 240 975 805 670 170 135 221,3
150
DXU3F150C._ 2 _ _ _ 240 Ø22 8 26 240 Ø23 8 31 285 983 240 975 805 670 170 135 221,3
T20181017001
C101
A
B
C
Type AC 24 DN IP Kvs Vmax V10 ∆ps # ports T1+T 2 LC
2 port
DXU2F050C.11421 50 54 30,5 30.000 9.633 150 M 2p 2m
DXU2F065C.11421 65 54 48,8 48.759 15.419 100 M 2p 2m
DXU2F080C.11421 80 54 70,7 80.000 22.361 230 M 2p 2m
DXU2F100C.11421 100 54 118,7 118.693 37.534 140 M 2p 2m
DXU2F150C.11421 150 54 254,7 254.726 80.552 120 M 2p 2m
3 port
DXU3F050C.11421 50 54 30,5 30.000 9.633 150 M 3p 2m
DXU3F065C.11421 65 54 48,8 48.759 15.419 100 M 3p 2m
DXU3F080C.11421 80 54 70,7 80.000 22.361 230 M 3p 2m
DXU3F100C.11421 100 54 118,7 118.693 37.534 140 M 3p 2m
DXU3F150C.11421 150 54 254,7 254.726 80.552 120 M 3p 2m
OPTIONS
Type
Legend
DN valve body size Vmax flow range ( 0..Vmax ) T1 medium temperature sensor Nr.1
M MODBUS RTU V10 flow range at ∆p 10kPa T2 medium temperature sensor Nr.2
B BACnet MSTP ∆ps maximum close-off pressure Lc standard cable length (PVC)
standard on request (min. quantities and/or longer lead times may apply. Please contact us)
A
B
C
Type AC 24 DN IP Kvs Vmax V10 ∆ps # ports T1+T 2 LC
2 port
DXU2F050C.11521 50 54 30,5 30.000 9.633 150 B 2p 2m
DXU2F065C.11521 65 54 48,8 48.759 15.419 100 B 2p 2m
DXU2F080C.11521 80 54 70,7 80.000 22.361 230 B 2p 2m
DXU2F100C.11521 100 54 118,7 118.693 37.534 140 B 2p 2m
DXU2F150C.11521 150 54 254,7 254.726 80.552 120 B 2p 2m
3 port
DXU3F050C.11521 50 54 30,5 30.000 9.633 150 B 3p 2m
DXU3F065C.11521 65 54 48,8 48.759 15.419 100 B 3p 2m
DXU3F080C.11521 80 54 70,7 80.000 22.361 230 B 3p 2m
DXU3F100C.11521 100 54 118,7 118.693 37.534 140 B 3p 2m
DXU3F150C.11521 150 54 254,7 254.726 80.552 120 B 3p 2m
OPTIONS
Type
Legend
DN valve body size Vmax flow range ( 0..Vmax ) T1 medium temperature sensor Nr.1
M MODBUS RTU V10 flow range at ∆p 10kPa T2 medium temperature sensor Nr.2
B BACnet MSTP ∆ps maximum close-off pressure Lc standard cable length (PVC)
standard on request (min. quantities and/or longer lead times may apply. Please contact us)