Department of Housing and Urban Development


Washington, DC 20410-0100

08/22/2022

REAL ESTATE ASSESSMENT CENTER

713096 / 800234287

SILVER OAKS APTS


4200 Troy Ct
TAMPA, FL 33610 -4635

Dear Owner:

This letter transmits by electronic file the most recent physical inspection summary report for your property.
This inspection was performed by an inspector certified by HUD in the use of the inspection protocol and was
performed pursuant to HUD regulations at 24 CFR Part 5 and Part 200. These regulations may be viewed on the
REAC website at http://www.hud.gov/offices/reac. This site provides information about REAC and the physical
inspection process and allows you to download a free copy of the inspection software and view deficiency
definitions. Also enclosed is a short description of the elements of the report to assist you in interpretation.

If the inspector noted any exigent health and safety (EH&S) deficiencies at the time of the inspection, you or
your representative received a report listing those deficiencies. You are required to correct all EH&S deficiencies
at your property, not only those deficiencies noted by the inspector. You must repair or mitigate all EH&S items
immediately, and you must file a written report with the local field office using your letterhead, certifying to the
repairs or mitigation of the EH&S items within three (3) business days of the date of the inspection. The attached
certification language must be included in your statement of completion. If your property is assigned to a
Performance-Based Contract Administrator (PB-CA), your certification should be sent to the PB-CA and not to
the local HUD office. If the loan is under the 232 program, your certification should be sent to the Account
Executive with the Office of Healthcare Programs (OHP). Do not send your report to REAC.

If your property received a score from 31 to 59, the inspection has been referred to the Multifamily Hub or
local OHP that has jurisdiction over the property for possible enforcement action. A physical Inspection score
below 60 indicates that the owner may not be fulfilling his/her contractual obligations to HUD and that the
residents may not be receiving the quality of housing to which they are entitled. Accordingly, HUD will determine
whether or not it must proceed to take enforcement action as authorized by existing statutes, regulations,
contracts or other business documents. HUD may suspend the administrative procedure described in 24 CFR
200 Subpart P when HUD determines it necessary to protect HUD's financial interests and to protect the
residents as provided by 24 CFR 200.857(i)(4).

You will be contacted by the Hub, Program Center or OHP to set up a meeting or discussion on the
compliance needs of your property. However, you should not delay the commencement of repairs to your
property pending such a meeting. You should complete a survey of the physical needs of your entire property.
While this physical inspection report may provide baseline information, be advised that all property repair needs
must be corrected. This survey should be provided to the Program Center or Hub that has jurisdiction over your
property upon your prompt completion.

If the mortgage on the property is insured by HUD/FHA, please provide copies of all correspondence
regarding this inspection to your mortgagee.

Thank you for your cooperation.

Sincerely,

SAMUEL TUFFOUR
PROGRAM MANAGER, PHYSICAL ASSESSMENT
SUBSYSTEM
Real Estate Assessment Center
Enclosures
Inspection Summary Report (POA) for Inspection #713096

Inspection Snapshot

Inspection ID: 713096 Inspection Time: 08:50 AM - 03:10 PM


Inspection Start Inspection End
Date: 05/24/2022 Date: 05/25/2022
Property ID: 800234287 Property Type: Multifamily
Property Name: SILVER OAKS APTS
Inspection State: Successful Score: 57c*

Report generation date/time: 08/22/2022 01:11 PM Score Version: 2 Page: 1 of 59


Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.
Inspection Summary Report (POA) for Inspection #713096

Property Profile

Property Name: SILVER OAKS APTS


Scattered Site? No Multiple Site? No
Address Line 1: 4200 Troy Ct
Address Line 2:
City: TAMPA State: FL
ZIP: 33610 Extension: 4635
Phone: (813) 626-9337 Extension:
Fax: (813) 664-0190 Email: silveroak@cmiweb.net
Building Units
Type Expected Actual Sampled Expected Actual Sampled
Residential 10 12 12 200 200 24
Common 0 1 1 - - -
Total 10 13 13 200 200 24

Occupancy Information
No. of Occupied Units Occupancy Rate Inspect Vacant Units
185 93 No

Bed Bugs Information


# of Buildings with Bed # of Units with Bed
Bed Bugs Reported Bugs Bugs Bed Bug Comments
No 0 0 N/A

Comments No Covid Units reported, verified no HUD loan.

Report generation date/time: 08/22/2022 01:11 PM Score Version: 2 Page: 2 of 59


Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.
Inspection Summary Report (POA) for Inspection #713096

Participant Profile

Management Agent [Primary Contact / Present During Inspection]


Name (F, MI, L): Bruce Williams
Organization: Cambridge Management Inc
Address Line 1: 1916 64th ave
Address Line 2:
City: Tacoma State: WA
ZIP: 98466 Extension:
Phone: (561) 632-3141 Extension:
Fax: Email: bwilliams@cmiweb.net
Owner [Not Present During Inspection]
Name (F, MI, L): Sue Baker
Organization: Cambridge Management Inc.
Address Line 1: 1916 64th Avenue West
Address Line 2:
City: Tacoma State: WA
ZIP: 98466 Extension:
Phone: (813) 626-9337 Extension:
Fax: Email: sue@vaughnbay.net
Site Manager [Present During Inspection]
Name (F, MI, L): Brittany James
Organization: Silver Oaks
Address Line 1: 4200 Kenneth Court
Address Line 2:
City: Tampa State: FL
ZIP: 33610 Extension:
Phone: (813) 626-9337 Extension:
Fax: (813) 664-0190 Email: SilverOak@cmiweb.net
Other [Present During Inspection]
Name (F, MI, L): Emerson Solis
Organization: Cambridge Management Inc
Address Line 1: 4200 Kenneth Court
Address Line 2:
City: Tampa State: FL
ZIP: 33610 Extension:
Phone: (813) 626-9337 Extension:
Fax: (813) 664-0190 Email: SilverOak@cmiweb.net

Report generation date/time: 08/22/2022 01:11 PM Score Version: 2 Page: 3 of 59


Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.
Inspection Summary Report (POA) for Inspection #713096

Score Summary

Possible Deductions(Excluding Pre H&S H&S


Area Final Points
Points H&S) Points Deductions
Site 19.73 0.00 19.73 7.50 12.23
Building Exterior 17.99 0.67 17.32 0.00 17.32
Building Systems 16.84 0.11 16.73 0.81 15.92
Common Area 2.88 0.18 2.70 0.81 1.90
Unit 42.55 13.11 29.44 19.33 10.11
Total 100.00 14.07 85.93 28.44 57.48

Score Version: 2 Score Date: 08/22/2022 Final Score: 57c*

Score History

Inspection Id Inspection Date Pre H&S Points Final Score


713096 05/24/2022 85.93 57.48c*

Report generation date/time: 08/22/2022 01:11 PM Score Version: 2 Page: 4 of 59


Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.
Inspection Summary Report (POA) for Inspection #713096

Health & Safety Summary

Site Buildings Units Total Health and Safety Narrative


1 site, 13 buildings and 24 units were inspected.
Non-Life Threatening (NLT)
Actual 0 2 39 41 70 health and safety deficiencies(HSD) were
observed.
Projected 0 2 325 327
Percentage Inspected:
Life Threatening (LT)
Site (PIS): 100%
Actual 1 5 13 19 Building (PIB): 100%
Unit (PIU): 12%
Projected 1 5 108 114
Smoke Detectors (SD) Projected HSD:
Site = (Actual HSDS) / PIS
Actual 0 0 10 10
Building = (Actual HSDB) / PIB
Projected 0 0 83 83 Unit = (Actual HSDU) / PIU
Overall If all buildings and units were inspected, it is
Actual 1 7 62 70 projected that a total of 525 health and safety
deficiencies would apply to the property.
Projected 1 7 517 525

Report generation date/time: 08/22/2022 01:11 PM Score Version: 2 Page: 5 of 59


Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.
Inspection Summary Report (POA) for Inspection #713096

Systemic Deficiencies

B/U with Total


Type Area Item Deficiency
defects B/U %
Capital Unit Kitchen Items Unit - Refrigerator - Missing/Damaged/ 13 24 54
Inoperable (Kitchen)
Capital Unit Bathroom Items Unit - Lavatory Sink - Damaged/Missing 10 24 42
(Bathroom)
Ordinary Site Electrical Hazards HS - Exposed Wires/Open Panels 1 1 100
(Electrical Hazards)
Ordinary Site Hazards HS - Lead Hazard Report 1 1 100
Ordinary Unit Doors Unit - Damaged Hardware/Locks 9 24 38
(Doors)
Ordinary Unit Windows Unit - Inoperable/Not Lockable 13 24 54
(Windows)
Ordinary Unit Windows Unit - Damaged/Missing Screens 19 24 79
(Windows)
Ordinary Unit Smoke Detector Unit - Missing/Inoperable (Smoke 8 24 33
Detector)
Ordinary Unit Emergency/Fire Exits HS - Emergency/Fire Exits Blocked/ 11 24 46
Unusable (Emergency/Fire Exits)
Ordinary Unit Infestation HS - Insects /roaches (Infestation) 14 24 58
Note:
B/U - Indicates Buildings or Units
BE - Indicates Building Exterior
BS - Indicates Building Systems
CA - Indicates Common Areas
Capital items are repairs that generally require large cash outlays. (Items such as new roofs and new appliances)
Ordinary items are repairs that require smaller cash outlays. (Items such as light fixtures, fire extinguishers and smoke detectors)

Report generation date/time: 08/22/2022 01:11 PM Score Version: 2 Page: 6 of 59


Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.
Inspection Summary Report (POA) for Inspection #713096

Building/Unit Summary

Entity Expected Actual # Inspected # Reported Uninspectable


Building 10 13 13 4
Unit 200 200 24 3

Building 1 - A-5711- 101-307 [ Excluded not in Universe , Added by Mistake ]

Address Line 1: 5711 Troy Ct


Address Line 2: odd numbers
City: Tampa State: FL
Zip: 33610 Extension: ____
Actual Unit
Type Constructed In Floors Expected Unit Count
Count
Walkup/Multifamily
1973 3 12 12
Apts

Building has Carbon


Flat Roof Roof Access
Monoxide source
No No

Comments:

Building 2 - B-4220- 101-307 [ Excluded not in Universe , Added by Mistake ]

Address Line 1: 4220 Patsy Ct


Address Line 2: Odd numbers
City: Tampa State: FL
Zip: 33610 Extension: ____
Actual Unit
Type Constructed In Floors Expected Unit Count
Count
Walkup/Multifamily
1973 3 12 12
Apts

Building has Carbon


Flat Roof Roof Access
Monoxide source
No No

Comments:

Building 3 - C-4210- 101--307 [ Excluded not in Universe , Added by Mistake ]

Address Line 1: 4210 Faye Ct


Report generation date/time: 08/22/2022 01:11 PM Score Version: 2 Page: 7 of 59
Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.
Inspection Summary Report (POA) for Inspection #713096

Address Line 2: Odd numbers


City: Tampa State: FL
Zip: 33610 Extension: ____
Actual Unit
Type Constructed In Floors Expected Unit Count
Count
Walkup/Multifamily
1973 3 12 12
Apts

Building has Carbon


Flat Roof Roof Access
Monoxide source
No No

Comments:

Building 4 - D-5715-101-309 [ Excluded not in Universe , Added by Mistake ]

Address Line 1: 5715 Stevens Ct


Address Line 2: Odd numbers
City: Tampa State: FL
Zip: 33610 Extension: ____
Actual Unit
Type Constructed In Floors Expected Unit Count
Count
Walkup/Multifamily
1973 3 15 15
Apts

Building has Carbon


Flat Roof Roof Access
Monoxide source
No No

Comments:

Building 5 - E-4201-101-309 [ Sample , Inspected ]

Address Line 1: 4201 Kenneth Ct


Address Line 2: Odd
City: Tampa State: FL
Zip: 33610 Extension: ____
Actual Unit
Type Constructed In Floors Expected Unit Count
Count
Walkup/Multifamily
1973 3 15 15
Apts

Flat Roof Roof Access Building has Carbon

Report generation date/time: 08/22/2022 01:11 PM Score Version: 2 Page: 8 of 59


Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.
Inspection Summary Report (POA) for Inspection #713096

Monoxide source
Yes No No

Comments:

CO
UnInspected Detector CO Detector
Unit # # Bedrooms Occupied? Reason? Present Status
(b) (6)
2 Bedrooms No Vacant No
(b) (6)
2 Bedrooms Yes No
(b) (6)
2 Bedrooms Yes No

Building 6 - F-4203- 101-307 [ Sample , Inspected ]

Address Line 1: 4203 Kenneth Ct


Address Line 2: odd numbers
City: Tampa State: FL
Zip: 33610 Extension: ____
Actual Unit
Type Constructed In Floors Expected Unit Count
Count
Walkup/Multifamily
1973 3 12 12
Apts

Building has Carbon


Flat Roof Roof Access
Monoxide source
Yes No No

Comments:

CO
UnInspected Detector CO Detector
Unit # # Bedrooms Occupied? Reason? Present Status
(b) (6)
2 Bedrooms Yes No
(b) (6)
2 Bedrooms Yes No

Building 7 - G-5502 101-307 [ Sample , Inspected ]

Address Line 1: 5502 N 43rd St


Address Line 2: Odd numbers
City: Tampa State: FL
Zip: 33610 Extension: ____
Actual Unit
Type Constructed In Floors Expected Unit Count
Count
Report generation date/time: 08/22/2022 01:11 PM Score Version: 2 Page: 9 of 59
Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.
Inspection Summary Report (POA) for Inspection #713096

Walkup/Multifamily
1973 3 12 12
Apts

Building has Carbon


Flat Roof Roof Access
Monoxide source
Yes No No

Comments:

CO
UnInspected Detector CO Detector
Unit # # Bedrooms Occupied? Reason? Present Status
(b) (6)
1 Bedroom No Vacant No
(b) (6)
2 Bedrooms Yes No

Building 8 - H-4205- 101-307 [ Sample , Inspected ]

Address Line 1: 4205 Kenneth Ct


Address Line 2: odd numbers
City: Tampa State: FL
Zip: 33610 Extension: ____
Actual Unit
Type Constructed In Floors Expected Unit Count
Count
Walkup/Multifamily
1973 3 12 12
Apts

Building has Carbon


Flat Roof Roof Access
Monoxide source
Yes No No

Comments:

CO
UnInspected Detector CO Detector
Unit # # Bedrooms Occupied? Reason? Present Status
(b) (6)
3 Bedrooms Yes No N/A

Building 9 - Office [ Sample , Inspected ]

Address Line 1: 4200 Kenneth Ct


Address Line 2:
City: Tampa State: FL
Zip: 33610 Extension: ____

Report generation date/time: 08/22/2022 01:11 PM Score Version: 2 Page: 10 of 59


Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.
Inspection Summary Report (POA) for Inspection #713096

Actual Unit
Type Constructed In Floors Expected Unit Count
Count
Non Dwelling
1973 1 0 0
Structure

Building has Carbon


Flat Roof Roof Access
Monoxide source
No No

Comments:

Building 10 - 4201 102-310 [ Sample , Inspected ]

Address Line 1: 4201 Kenneth Ct


Address Line 2: even numbers
City: Tampa State: FL
Zip: 33613 Extension: ____
Actual Unit
Type Constructed In Floors Expected Unit Count
Count
Walkup/Multifamily
1973 3 15 15
Apts

Building has Carbon


Flat Roof Roof Access
Monoxide source
Yes No No

Comments:

CO
UnInspected Detector CO Detector
Unit # # Bedrooms Occupied? Reason? Present Status
(b) (6)
2 Bedrooms Yes No

Building 11 - 4203 102-308 [ Sample , Inspected ]

Address Line 1: 4203 Kenneth Ct


Address Line 2: even numbers
City: Tampa State: FL
Zip: 33610 Extension: ____
Actual Unit
Type Constructed In Floors Expected Unit Count
Count
Walkup/Multifamily
1973 3 12 12
Apts

Report generation date/time: 08/22/2022 01:11 PM Score Version: 2 Page: 11 of 59


Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.
Inspection Summary Report (POA) for Inspection #713096

Building has Carbon


Flat Roof Roof Access
Monoxide source
Yes No No

Comments:

CO
UnInspected Detector CO Detector
Unit # # Bedrooms Occupied? Reason? Present Status
(b) (6)
2 Bedrooms Yes No
(b) (6)
2 Bedrooms Yes Other Hazard No

Building 12 - 4205 102-308 [ Sample , Inspected ]

Address Line 1: 4205 Kenneth Ct


Address Line 2: Even numbers
City: Tampa State: FL
Zip: 33610 Extension: ____
Actual Unit
Type Constructed In Floors Expected Unit Count
Count
Walkup/Multifamily
1973 3 10 10
Apts

Building has Carbon


Flat Roof Roof Access
Monoxide source
Yes No No

Comments:

CO
UnInspected Detector CO Detector
Unit # # Bedrooms Occupied? Reason? Present Status
(b) (6)
2 Bedrooms Yes No

Building 13 - 4210 102-308 [ Sample , Inspected ]

Address Line 1: 4210 Faye Ct


Address Line 2: even numbers
City: Tampa State: FL
Zip: 33610 Extension: ____
Actual Unit
Type Constructed In Floors Expected Unit Count
Count
Walkup/Multifamily 1973 3 12 24
Report generation date/time: 08/22/2022 01:11 PM Score Version: 2 Page: 12 of 59
Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.
Inspection Summary Report (POA) for Inspection #713096

Apts

Building has Carbon


Flat Roof Roof Access
Monoxide source
Yes No No

Comments:

CO
UnInspected Detector CO Detector
Unit # # Bedrooms Occupied? Reason? Present Status
(b) (6)
2 Bedrooms Yes No N/A
(b) (6)
2 Bedrooms Yes No
(b) (6)
2 Bedrooms Yes No

Building 14 - 4220 101-308 [ Sample , Inspected ]

Address Line 1: 4220 Patsy Ct


Address Line 2: Odd
City: Tampa State: FL
Zip: 33610 Extension: ____
Actual Unit
Type Constructed In Floors Expected Unit Count
Count
Walkup/Multifamily
1973 3 11 23
Apts

Building has Carbon


Flat Roof Roof Access
Monoxide source
Yes No No

Comments:

CO
UnInspected Detector CO Detector
Unit # # Bedrooms Occupied? Reason? Present Status
(b) (6)
2 Bedrooms Yes No N/A
(b) (6)
2 Bedrooms Yes No
(b) (6)
2 Bedrooms Yes No N/A

Building 15 - 5502 102-308 [ Sample , Inspected ]

Address Line 1: 5502 Patsy Ct


Address Line 2: Even numbers

Report generation date/time: 08/22/2022 01:11 PM Score Version: 2 Page: 13 of 59


Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.
Inspection Summary Report (POA) for Inspection #713096

City: Tampa State: FL


Zip: 33610 Extension: ____
Actual Unit
Type Constructed In Floors Expected Unit Count
Count
Walkup/Multifamily
1973 3 12 12
Apts

Building has Carbon


Flat Roof Roof Access
Monoxide source
Yes No No

Comments:

CO
UnInspected Detector CO Detector
Unit # # Bedrooms Occupied? Reason? Present Status
(b) (6)
3 Bedrooms Yes No
(b) (6)
3 Bedrooms Yes No

Building 16 - 5711 101-308 [ Sample , Inspected ]

Address Line 1: 5711 Troy Ct


Address Line 2: Even numbers
City: Tampa State: FL
Zip: 33610 Extension: ____
Actual Unit
Type Constructed In Floors Expected Unit Count
Count
Walkup/Multifamily
1973 3 11 23
Apts

Building has Carbon


Flat Roof Roof Access
Monoxide source
Yes No No

Comments:

CO
UnInspected Detector CO Detector
Unit # # Bedrooms Occupied? Reason? Present Status
(b) (6)
2 Bedrooms Yes No
(b) (6)
2 Bedrooms Yes No
(b) (6)
2 Bedrooms Yes No

Report generation date/time: 08/22/2022 01:11 PM Score Version: 2 Page: 14 of 59


Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.
Inspection Summary Report (POA) for Inspection #713096

Building 17 - 5715-101--310 [ Sample , Inspected ]

Address Line 1: 5715 Stevens Ct


Address Line 2: even numbers
City: Tampa State: FL
Zip: 33610 Extension: ____
Actual Unit
Type Constructed In Floors Expected Unit Count
Count
Walkup/Multifamily
1973 3 14 30
Apts

Building has Carbon


Flat Roof Roof Access
Monoxide source
Yes No No

Comments:

CO
UnInspected Detector CO Detector
Unit # # Bedrooms Occupied? Reason? Present Status
(b) (6)
2 Bedrooms Yes No
(b) (6)
1 Bedroom Yes No
(b) (6)
3 Bedrooms Yes No
(b) (6)
3 Bedrooms Yes No N/A

Report generation date/time: 08/22/2022 01:11 PM Score Version: 2 Page: 15 of 59


Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.
Inspection Summary Report (POA) for Inspection #713096

Certificates

Certificate Item Certificate State


Boilers NA - This certificate is not applicable for this property
Elevators NA - This certificate is not applicable for this property
Fire Alarms No - This certificate cannot be provided or is expired
Lead-Based Paint Disclosure Forms Yes - This certificate is provided or is not expired
Lead-Based Paint Inspection Reports No - This certificate cannot be provided or is expired
Sprinkler Systems NA - This certificate is not applicable for this property

Report generation date/time: 08/22/2022 01:11 PM Score Version: 2 Page: 16 of 59


Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.
Inspection Summary Report (POA) for Inspection #713096

Score Details

Note: The inspection software allows for the recording of the same deficiency as many times as it occurs. However, it is only scored once.
The number within the parenthesis after the Deficiency indicates the number of observations for this inspectable area. For example; "Site -
Spalling (Walkway / Steps) (4)" indicates the deficiency was observed and recorded 4 times under Site. Each individual observation can be
found in the Deficiency Details section of this report.

Points Points
Item Deficiency Severity
Deducted Received

Site - SILVER OAKS APTS - Site(0) [Possible Points : 19.73]


Non-Health And Safety Deficiencies
Hazards HS - Lead Hazard Report Level 3 0.00
Health And Safety Deficiencies
Electrical Hazards HS - Exposed Wires/Open Panels (Electrical Level 3 7.50
Hazards) (LT )
7.50 12.23

Building 5 - E-4201-101-309 - Unit (b) (6) [Possible Points : 1.80]


Non-Health And Safety Deficiencies
Bathroom Items Unit - Lavatory Sink - Damaged/Missing (Bathroom) Level 1 0.16
Kitchen Items Unit - Refrigerator - Missing/Damaged/Inoperable Level 1 0.16
(Kitchen)
Health And Safety Deficiencies
Smoke Detector Unit - Missing/Inoperable (Smoke Detector) (SD ) Level 3 0.00
0.32 1.48

Building 5 - E-4201-101-309 - Unit (b) (6) [Possible Points : 1.80]


Non-Health And Safety Deficiencies
Doors Unit - Damaged Hardware/Locks (Doors) (2) Level 3 0.19
Water Heater Unit - Leaking Valves/Tanks/Pipes (Hot Water Level 3 0.58
Heater)
Windows Unit - Damaged/Missing Screens (Windows) Level 1 0.03
Windows Unit - Inoperable/Not Lockable (Windows) Level 1 0.05
0.85 0.96

Building 6 - F-4203- 101-307 - Unit (b) (6)* [Possible Points : 1.77]


Non-Health And Safety Deficiencies
Windows Unit - Damaged/Missing Screens (Windows) Level 1 0.03

Report generation date/time: 08/22/2022 01:11 PM Score Version: 2 Page: 17 of 59


Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.
Inspection Summary Report (POA) for Inspection #713096

Points Points
Item Deficiency Severity
Deducted Received

Health And Safety Deficiencies


Emergency/Fire HS - Emergency/Fire Exits Blocked/Unusable Level 3 1.44
Exits (Emergency/Fire Exits) (2) (LT )
Infestation HS - Insects / roaches (Infestation) (NLT ) Level 3 0.65
Windows Unit - Inoperable/Not Lockable (Windows) (NLT ) Level 3 0.19
* The point deductions for this sub-area exceed the number of possible points. The points received cannot be negative so it is set to zero. 2.31 0.00

Building 6 - F-4203- 101-307 - Unit (b) (6) [Possible Points : 1.77]


Non-Health And Safety Deficiencies
Bathroom Items Unit - Lavatory Sink - Damaged/Missing (Bathroom) Level 1 0.16
Kitchen Items Unit - Plumbing - Leaking Faucet/Pipes (Kitchen) Level 1 0.16
Kitchen Items Unit - Refrigerator - Missing/Damaged/Inoperable Level 1 0.16
(Kitchen)
Walls Unit - Damaged (Walls) Level 2 0.09
Health And Safety Deficiencies
Infestation HS - Insects / roaches (Infestation) (NLT ) Level 3 0.65
Smoke Detector Unit - Missing/Inoperable (Smoke Detector) (SD ) Level 3 0.00
1.22 0.55

Building 7 - G-5502 101-307 - Unit (b) (6) [Possible Points : 1.80]


Non-Health And Safety Deficiencies
Bathroom Items Unit - Lavatory Sink - Damaged/Missing (Bathroom) Level 1 0.16
Ceiling Unit - Mold/Mildew/Water Stains/Water Damage Level 1 0.02
(Ceiling)
Kitchen Items Unit - Refrigerator - Missing/Damaged/Inoperable Level 1 0.16
(Kitchen)
Windows Unit - Damaged/Missing Screens (Windows) (3) Level 1 0.03
Health And Safety Deficiencies
Infestation HS - Insects / roaches (Infestation) (NLT ) Level 3 0.65
1.02 0.78

Building 8 - H-4205- 101-307 - Unit (b) (6) [Possible Points : 1.77]


Non-Health And Safety Deficiencies
Bathroom Items Unit - Lavatory Sink - Damaged/Missing (Bathroom) Level 1 0.16

Report generation date/time: 08/22/2022 01:11 PM Score Version: 2 Page: 18 of 59


Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.
Inspection Summary Report (POA) for Inspection #713096

Points Points
Item Deficiency Severity
Deducted Received

Doors Unit - Deteriorated/Missing Seals (Entry Only) Level 3 0.26


(Doors)
Kitchen Items Unit - Refrigerator - Missing/Damaged/Inoperable Level 1 0.16
(Kitchen)
Outlets/Switches Unit - Missing/Broken Cover Plates Level 1 0.04
(Outlets/Switches)
Windows Unit - Damaged/Missing Screens (Windows) (3) Level 1 0.03
Windows Unit - Inoperable/Not Lockable (Windows) Level 1 0.05
Health And Safety Deficiencies
Infestation HS - Insects / roaches (Infestation) (NLT ) Level 3 0.65
1.35 0.42

Building 9 - Office - Building Systems [Possible Points : 0.68]


Non-Health And Safety Deficiencies
Emergency Power BS- Auxiliary Lighting Inoperable (Emergency Level 3 0.11
Power)
0.11 0.58

Building 10 - 4201 102-310 - Common Areas* [Possible Points : 0.08]


Health And Safety Deficiencies
Emergency/Fire HS - Missing Exit Signs (Emergency/Fire Exits) (NLT Level 3 0.34
Exits )
* The point deductions for this sub-area exceed the number of possible points. The points received cannot be negative so it is set to zero. 0.34 0.00

Building 10 - 4201 102-310 - Unit (b) (6)* [Possible Points : 1.77]


Non-Health And Safety Deficiencies
Bathroom Items Unit - Lavatory Sink - Damaged/Missing (Bathroom) Level 1 0.16
Kitchen Items Unit - Refrigerator - Missing/Damaged/Inoperable Level 1 0.16
(Kitchen)
Windows Unit - Damaged/Missing Screens (Windows) (2) Level 1 0.03
Health And Safety Deficiencies
Emergency/Fire HS - Emergency/Fire Exits Blocked/Unusable Level 3 1.44
Exits (Emergency/Fire Exits) (LT )
Infestation HS - Insects / roaches (Infestation) (NLT ) Level 3 0.65
Windows Unit - Inoperable/Not Lockable (Windows) (2) (NLT ) Level 3 0.19

Report generation date/time: 08/22/2022 01:11 PM Score Version: 2 Page: 19 of 59


Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.
Inspection Summary Report (POA) for Inspection #713096

Points Points
Item Deficiency Severity
Deducted Received

* The point deductions for this sub-area exceed the number of possible points. The points received cannot be negative so it is set to zero. 2.63 0.00

Building 11 - 4203 102-308 - Unit (b) (6) [Possible Points : 1.77]


Non-Health And Safety Deficiencies
Bathroom Items Unit - Plumbing Leaking Faucet/Pipes (Bathroom) Level 1 0.22
Doors Unit - Damaged Hardware/Locks (Doors) Level 2 0.10
Outlets/Switches Unit - Missing/Broken Cover Plates Level 1 0.04
(Outlets/Switches)
Windows Unit - Damaged/Missing Screens (Windows) (3) Level 1 0.03
0.38 1.38

Building 12 - 4205 102-308 - Building Systems* [Possible Points : 0.81]


Health And Safety Deficiencies
Electrical System BS- Missing Breakers/Fuses (Electrical System) (LT Level 3 0.98
)
* The point deductions for this sub-area exceed the number of possible points. The points received cannot be negative so it is set to zero. 0.98 0.00

Building 12 - 4205 102-308 - Common Areas* [Possible Points : 0.15]


Non-Health And Safety Deficiencies
Ceiling CA - Peeling/Needs Paint (Ceiling) Level 1 0.01
Doors CA - Damaged Surface (Holes/Paint/Rust/Glass) Level 3 0.17
(Doors)
Health And Safety Deficiencies
Electrical Hazards HS - Exposed Wires/Open Panels (Electrical Level 3 0.76
Hazards) (2) (LT )
* The point deductions for this sub-area exceed the number of possible points. The points received cannot be negative so it is set to zero. 0.94 0.00

Building 12 - 4205 102-308 - Unit (b) (6) [Possible Points : 1.80]


Non-Health And Safety Deficiencies
Bathroom Items Unit - Plumbing Leaking Faucet/Pipes (Bathroom) Level 1 0.22
Windows Unit - Damaged/Missing Screens (Windows) (2) Level 1 0.03
0.24 1.56

Building 13 - 4210 102-308 - Common Areas* [Possible Points : 0.30]


Health And Safety Deficiencies

Report generation date/time: 08/22/2022 01:11 PM Score Version: 2 Page: 20 of 59


Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.
Inspection Summary Report (POA) for Inspection #713096

Points Points
Item Deficiency Severity
Deducted Received

Electrical Hazards HS - Exposed Wires/Open Panels (Electrical Level 3 0.76


Hazards) (LT )
Emergency/Fire HS - Missing Exit Signs (Emergency/Fire Exits) (NLT Level 3 0.34
Exits )
* The point deductions for this sub-area exceed the number of possible points. The points received cannot be negative so it is set to zero. 1.10 0.00

Building 13 - 4210 102-308 - Unit (b) (6) [Possible Points : 1.77]


Non-Health And Safety Deficiencies
Bathroom Items Unit - Lavatory Sink - Damaged/Missing (Bathroom) Level 1 0.16
Doors Unit - Damaged Hardware/Locks (Doors) Level 1 0.05
Windows Unit - Damaged/Missing Screens (Windows) Level 1 0.03
Windows Unit- Missing/Deteriorated Caulking/Seals/Glazing Level 3 0.43
Compound (Windows) (2)
Health And Safety Deficiencies
Smoke Detector Unit - Missing/Inoperable (Smoke Detector) (SD ) Level 3 0.00
Windows Unit - Inoperable/Not Lockable (Windows) (NLT ) Level 3 0.19
0.86 0.90

Building 13 - 4210 102-308 - Unit (b) (6)* [Possible Points : 1.77]


Non-Health And Safety Deficiencies
Doors Unit - Damaged Hardware/Locks (Doors) Level 2 0.10
Kitchen Items Unit - Refrigerator - Missing/Damaged/Inoperable Level 1 0.16
(Kitchen)
Health And Safety Deficiencies
Emergency/Fire HS - Emergency/Fire Exits Blocked/Unusable Level 3 1.44
Exits (Emergency/Fire Exits) (LT )
Infestation HS - Insects / roaches (Infestation) (NLT ) Level 3 0.65
Windows Unit - Inoperable/Not Lockable (Windows) (2) (NLT ) Level 3 0.19
* The point deductions for this sub-area exceed the number of possible points. The points received cannot be negative so it is set to zero. 2.54 0.00

Building 13 - 4210 102-308 - Unit (b) (6) [Possible Points : 1.77]


Non-Health And Safety Deficiencies
Kitchen Items Unit - Refrigerator - Missing/Damaged/Inoperable Level 1 0.16
(Kitchen)
Windows Unit - Damaged/Missing Screens (Windows) (3) Level 1 0.03

Report generation date/time: 08/22/2022 01:11 PM Score Version: 2 Page: 21 of 59


Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.
Inspection Summary Report (POA) for Inspection #713096

Points Points
Item Deficiency Severity
Deducted Received

Windows Unit - Inoperable/Not Lockable (Windows) Level 1 0.05


Health And Safety Deficiencies
Infestation HS - Insects / roaches (Infestation) (NLT ) Level 3 0.65
Kitchen Items Unit - Cabinets - Missing/Damaged (Kitchen) (NLT ) Level 3 0.36
1.24 0.52

Building 14 - 4220 101-308 - Building Exterior [Possible Points : 2.18]


Non-Health And Safety Deficiencies
Walls BE- Stained/Peeling/Needs Paint (Walls) Level 1 0.18
0.18 1.99

Building 14 - 4220 101-308 - Common Areas* [Possible Points : 0.46]


Non-Health And Safety Deficiencies
Ceiling CA - Peeling/Needs Paint (Ceiling) Level 1 0.02
Walls CA - Peeling/Needs Paint (Walls) Level 1 0.01
Health And Safety Deficiencies
Electrical Hazards HS - Exposed Wires/Open Panels (Electrical Level 3 0.76
Hazards) (LT )
* The point deductions for this sub-area exceed the number of possible points. The points received cannot be negative so it is set to zero. 0.79 0.00

Building 14 - 4220 101-308 - Unit (b) (6)* [Possible Points : 1.77]


Non-Health And Safety Deficiencies
Doors Unit - Damaged Hardware/Locks (Doors) Level 1 0.05
Kitchen Items Unit - Dishwasher/Garbage Disposal - Inoperable Level 2 0.18
(Kitchen)
Kitchen Items Unit - Range/Stove- Missing/Damaged/Inoperable Level 2 0.32
(Kitchen) (2)
Kitchen Items Unit - Refrigerator - Missing/Damaged/Inoperable Level 1 0.16
(Kitchen)
Windows Unit - Damaged/Missing Screens (Windows) Level 1 0.03
Health And Safety Deficiencies
Emergency/Fire HS - Emergency/Fire Exits Blocked/Unusable Level 3 1.44
Exits (Emergency/Fire Exits) (LT )
Kitchen Items Unit - Plumbing - Clogged Drains (Kitchen) (NLT ) Level 3 0.86
Windows Unit - Inoperable/Not Lockable (Windows) (NLT ) Level 3 0.19
Report generation date/time: 08/22/2022 01:11 PM Score Version: 2 Page: 22 of 59
Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.
Inspection Summary Report (POA) for Inspection #713096

Points Points
Item Deficiency Severity
Deducted Received

* The point deductions for this sub-area exceed the number of possible points. The points received cannot be negative so it is set to zero. 3.24 0.00

Building 14 - 4220 101-308 - Unit (b) (6) [Possible Points : 1.77]


Non-Health And Safety Deficiencies
Bathroom Items Unit - Bathroom Cabinets - Damaged/Missing Level 1 0.09
(Bathroom)
Bathroom Items Unit - Plumbing Leaking Faucet/Pipes (Bathroom) Level 1 0.22
Doors Unit - Damaged Hardware/Locks (Doors) Level 2 0.10
Outlets/Switches Unit - Missing/Broken Cover Plates Level 1 0.04
(Outlets/Switches)
Water Heater Unit - General Rust/Corrosion (Hot Water Heater) Level 2 0.22
Windows Unit - Damaged/Missing Screens (Windows) (2) Level 1 0.03
Health And Safety Deficiencies
Windows Unit - Inoperable/Not Lockable (Windows) (NLT ) Level 3 0.19
0.88 0.88

Building 14 - 4220 101-308 - Unit (b) (6)* [Possible Points : 1.77]


Non-Health And Safety Deficiencies
Kitchen Items Unit - Plumbing - Leaking Faucet/Pipes (Kitchen) Level 1 0.16
Windows Unit - Damaged/Missing Screens (Windows) Level 1 0.03
Health And Safety Deficiencies
Emergency/Fire HS - Emergency/Fire Exits Blocked/Unusable Level 3 1.44
Exits (Emergency/Fire Exits) (LT )
Infestation HS - Insects / roaches (Infestation) (NLT ) Level 3 0.65
Windows Unit - Inoperable/Not Lockable (Windows) (2) (NLT ) Level 3 0.19
* The point deductions for this sub-area exceed the number of possible points. The points received cannot be negative so it is set to zero. 2.47 0.00

Building 15 - 5502 102-308 - Unit (b) (6)* [Possible Points : 1.77]


Non-Health And Safety Deficiencies
Bathroom Items Unit - Lavatory Sink - Damaged/Missing (Bathroom) Level 1 0.16
Doors Unit - Deteriorated/Missing Seals (Entry Only) Level 3 0.26
(Doors)
Kitchen Items Unit - Refrigerator - Missing/Damaged/Inoperable Level 1 0.16
(Kitchen)

Report generation date/time: 08/22/2022 01:11 PM Score Version: 2 Page: 23 of 59


Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.
Inspection Summary Report (POA) for Inspection #713096

Points Points
Item Deficiency Severity
Deducted Received

Windows Unit - Damaged/Missing Screens (Windows) Level 1 0.03


Health And Safety Deficiencies
Bathroom Items Unit - Shower/Tub - Damaged/Missing (Bathroom) Level 3 0.86
(NLT )
Emergency/Fire HS - Emergency/Fire Exits Blocked/Unusable Level 3 1.44
Exits (Emergency/Fire Exits) (LT )
Infestation HS - Insects / roaches (Infestation) (NLT ) Level 3 0.65
Windows Unit - Inoperable/Not Lockable (Windows) (NLT ) Level 3 0.19
* The point deductions for this sub-area exceed the number of possible points. The points received cannot be negative so it is set to zero. 3.75 0.00

Building 15 - 5502 102-308 - Unit (b) (6) [Possible Points : 1.80]


Non-Health And Safety Deficiencies
Windows Unit - Damaged/Missing Screens (Windows) (2) Level 1 0.03
Health And Safety Deficiencies
Doors Unit - Damaged Frames/Threshold/Lintels/Trim Level 3 0.11
(Doors) (NLT )
Emergency/Fire HS - Emergency/Fire Exits Blocked/Unusable Level 3 1.44
Exits (Emergency/Fire Exits) (LT )
Smoke Detector Unit - Missing/Inoperable (Smoke Detector) (SD ) Level 3 0.00
Windows Unit - Inoperable/Not Lockable (Windows) (NLT ) Level 3 0.19
1.77 0.04

Building 16 - 5711 101-308 - Building Exterior [Possible Points : 2.18]


Non-Health And Safety Deficiencies
Walls BE- Missing Pieces/Holes/Spalling (Walls) Level 2 0.49
0.49 1.69

Building 16 - 5711 101-308 - Unit (b) (6)* [Possible Points : 1.77]


Non-Health And Safety Deficiencies
Bathroom Items Unit - Lavatory Sink - Damaged/Missing (Bathroom) Level 1 0.16
Bathroom Items Unit - Plumbing Leaking Faucet/Pipes (Bathroom) Level 1 0.22
Kitchen Items Unit - Plumbing - Leaking Faucet/Pipes (Kitchen) Level 1 0.16
Lighting Unit - Missing/Inoperable Fixture (Lighting) Level 2 0.06
Outlets/Switches Unit - Missing/Broken Cover Plates Level 1 0.04
(Outlets/Switches)
Report generation date/time: 08/22/2022 01:11 PM Score Version: 2 Page: 24 of 59
Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.
Inspection Summary Report (POA) for Inspection #713096

Points Points
Item Deficiency Severity
Deducted Received

Windows Unit - Damaged/Missing Screens (Windows) (2) Level 1 0.03


Health And Safety Deficiencies
Bathroom Items Unit - Shower/Tub - Damaged/Missing (Bathroom) Level 3 0.86
(NLT )
Electrical System Unit - GFI - Inoperable (Electrical System) (NLT ) Level 3 0.96
Emergency/Fire HS - Emergency/Fire Exits Blocked/Unusable Level 3 1.44
Exits (Emergency/Fire Exits) (LT )
Infestation HS - Insects / roaches (Infestation) (NLT ) Level 3 0.65
Smoke Detector Unit - Missing/Inoperable (Smoke Detector) (2) (SD ) Level 3 0.00
* The point deductions for this sub-area exceed the number of possible points. The points received cannot be negative so it is set to zero. 4.58 0.00

Building 16 - 5711 101-308 - Unit (b) (6)* [Possible Points : 1.77]


Non-Health And Safety Deficiencies
Doors Unit - Damaged Hardware/Locks (Doors) Level 3 0.19
Doors Unit - Damaged Surface (Holes/Paint/Rust/Glass) Level 3 0.19
(Doors)
Windows Unit - Damaged/Missing Screens (Windows) (3) Level 1 0.03
Health And Safety Deficiencies
Bathroom Items Unit - Shower/Tub - Damaged/Missing (Bathroom) Level 3 0.86
(NLT )
Infestation HS - Insects / roaches (Infestation) (NLT ) Level 3 0.65
* The point deductions for this sub-area exceed the number of possible points. The points received cannot be negative so it is set to zero. 1.93 0.00

Building 16 - 5711 101-308 - Unit (b) (6)* [Possible Points : 1.77]


Non-Health And Safety Deficiencies
Doors Unit - Damaged Hardware/Locks (Doors) Level 2 0.10
Kitchen Items Unit - Dishwasher/Garbage Disposal - Inoperable Level 2 0.18
(Kitchen)
Kitchen Items Unit - Range/Stove- Missing/Damaged/Inoperable Level 3 0.65
(Kitchen)
Kitchen Items Unit - Sink - Missing/Damaged (Kitchen) Level 3 1.44
Lighting Unit - Missing/Inoperable Fixture (Lighting) Level 2 0.06
Health And Safety Deficiencies
Bathroom Items Unit - Shower/Tub - Damaged/Missing (Bathroom) Level 3 0.86

Report generation date/time: 08/22/2022 01:11 PM Score Version: 2 Page: 25 of 59


Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.
Inspection Summary Report (POA) for Inspection #713096

Points Points
Item Deficiency Severity
Deducted Received

(NLT )
Bathroom Items Unit - Water Closet/Toilet- Level 3 1.44
Damaged/Clogged/Missing (Bathroom) (NLT )
Emergency/Fire HS - Emergency/Fire Exits Blocked/Unusable Level 3 1.44
Exits (Emergency/Fire Exits) (2) (LT )
Kitchen Items Unit - Refrigerator - Missing/Damaged/Inoperable Level 3 0.65
(Kitchen) (NLT )
Smoke Detector Unit - Missing/Inoperable (Smoke Detector) (SD ) Level 3 0.00
* The point deductions for this sub-area exceed the number of possible points. The points received cannot be negative so it is set to zero. 6.81 0.00

Building 17 - 5715-101--310 - Unit (b) (6)* [Possible Points : 1.77]


Non-Health And Safety Deficiencies
Bathroom Items Unit - Bathroom Cabinets - Damaged/Missing Level 1 0.09
(Bathroom)
Bathroom Items Unit - Water Closet/Toilet- Level 2 0.72
Damaged/Clogged/Missing (Bathroom)
Kitchen Items Unit - Refrigerator - Missing/Damaged/Inoperable Level 1 0.16
(Kitchen)
Walls Unit - Damaged (Walls) Level 2 0.09
Windows Unit - Damaged/Missing Screens (Windows) (3) Level 1 0.03
Health And Safety Deficiencies
Bathroom Items Unit - Plumbing - Clogged Drains (Bathroom) (NLT ) Level 3 1.44
Infestation HS - Insects / roaches (Infestation) (NLT ) Level 3 0.65
Smoke Detector Unit - Missing/Inoperable (Smoke Detector) (2) (SD ) Level 3 0.00
* The point deductions for this sub-area exceed the number of possible points. The points received cannot be negative so it is set to zero. 3.17 0.00

Building 17 - 5715-101--310 - Unit (b) (6) [Possible Points : 1.77]


Non-Health And Safety Deficiencies
Windows Unit - Damaged/Missing Screens (Windows) Level 1 0.03
Health And Safety Deficiencies
Infestation HS - Insects / roaches (Infestation) (NLT ) Level 3 0.65
Kitchen Items Unit - Refrigerator - Missing/Damaged/Inoperable Level 3 0.65
(Kitchen) (NLT )
1.32 0.44

Report generation date/time: 08/22/2022 01:11 PM Score Version: 2 Page: 26 of 59


Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.
Inspection Summary Report (POA) for Inspection #713096

Points Points
Item Deficiency Severity
Deducted Received

Building 17 - 5715-101--310 - Unit (b) (6)* [Possible Points : 1.77]


Non-Health And Safety Deficiencies
Bathroom Items Unit - Lavatory Sink - Damaged/Missing (Bathroom) Level 1 0.16
Kitchen Items Unit - Refrigerator - Missing/Damaged/Inoperable Level 1 0.16
(Kitchen)
Windows Unit - Damaged/Missing Screens (Windows) (2) Level 1 0.03
Health And Safety Deficiencies
Bathroom Items Unit - Shower/Tub - Damaged/Missing (Bathroom) Level 3 0.86
(NLT )
Electrical System Unit - GFI - Inoperable (Electrical System) (NLT ) Level 3 0.96
Emergency/Fire HS - Emergency/Fire Exits Blocked/Unusable Level 3 1.44
Exits (Emergency/Fire Exits) (LT )
Infestation HS - Insects / roaches (Infestation) (NLT ) Level 3 0.65
* The point deductions for this sub-area exceed the number of possible points. The points received cannot be negative so it is set to zero. 4.26 0.00

Building 17 - 5715-101--310 - Unit (b) (6) [Possible Points : 1.77]


Non-Health And Safety Deficiencies
Bathroom Items Unit - Lavatory Sink - Damaged/Missing (Bathroom) Level 1 0.16
Bathroom Items Unit - Plumbing Leaking Faucet/Pipes (Bathroom) Level 1 0.22
Doors Unit - Damaged Hardware/Locks (Doors) Level 2 0.10
Doors Unit - Damaged Surface (Holes/Paint/Rust/Glass) Level 3 0.19
(Doors)
Doors Unit - Deteriorated/Missing Seals (Entry Only) Level 3 0.26
(Doors)
Doors Unit - Missing Door (Doors) Level 1 0.11
Walls Unit - Damaged (Walls) (3) Level 1 0.04
Windows Unit - Inoperable/Not Lockable (Windows) Level 1 0.05
Windows Unit- Missing/Deteriorated Caulking/Seals/Glazing Level 3 0.43
Compound (Windows)
Health And Safety Deficiencies
Smoke Detector Unit - Missing/Inoperable (Smoke Detector) (SD ) Level 3 0.00
1.56 0.21

Report generation date/time: 08/22/2022 01:11 PM Score Version: 2 Page: 27 of 59


Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.
Inspection Summary Report (POA) for Inspection #713096

Deficiency Details

Item Location/Comments Deficiency/Severity Decisions

Site - SILVER OAKS APTS - Site(0)


Non-Health And Safety Deficiencies
Hazards Capture Lead Base Paint HS - Lead Hazard Report - - Lead Hazard Report
Report L3
Health And Safety Deficiencies
Electrical Hazards missing internal cover on HS - Exposed Wires/Open - Exposed bare wires
compactor breaker box Panels (Electrical Hazards) - The exposed bare wires
(LT) - L3 ARE capped BUT NOT
enclosed in a secured
electrical box OR ARE NOT
capped

Building 5 - E-4201-101-309[Sample,Inspected] - Building Exterior


None

Building 5 - E-4201-101-309[Sample,Inspected] - Building Systems


None

Building 5 - E-4201-101-309[Sample,Inspected] - Common Areas


None

Building 5 - E-4201-101-309[Sample,Inspected] - Unit (b) (6)


Non-Health And Safety Deficiencies
Bathroom Items Bathroom Unit - Lavatory Sink - - Bathroom Sink
missing Damaged/Missing - A stopper is missing (only if
(Bathroom) - L1 there is no stopper in the
visible area)
Kitchen Items Kitchen Unit - Refrigerator - Missing - Refrigerator
bottom /Damaged/Inoperable - Door seals are deteriorated
(Kitchen) - L1
Health And Safety Deficiencies
Smoke Detector Hallway Unit - Missing/Inoperable - Inoperable
inop (Smoke Detector) (SD) - L3 - There is NOT another
functioning smoke detector
on same level.

Report generation date/time: 08/22/2022 01:11 PM Score Version: 2 Page: 28 of 59


Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.
Inspection Summary Report (POA) for Inspection #713096

Item Location/Comments Deficiency/Severity Decisions


(b) (6)
Building 5 - E-4201-101-309[Sample,Inspected] - Unit
Non-Health And Safety Deficiencies
Doors Bathroom Unit - Damaged Hardware/ - Bathroom Door
not latching Locks (Doors) - L3 - Hardware is damaged or
missing
- Door does not function as it
should (it does not properly
latch).
Doors Bedroom Unit - Damaged Hardware/ - All Other Doors (includes
bed 1 not latching Locks (Doors) - L2 closet or other interior
doors)
- Hardware is damaged or
missing
- Other interior door does not
function as it should or
cannot be locked.
Water Heater Storage Unit - Leaking Valves/Tanks - Water is leaking from any
cold water pipe on water /Pipes (Hot Water Heater) - water system component,
heater leaking L3 hose bibs.
- This condition DOES NOT
RESULT in a Health and
Safety concern.
Windows Living Area Unit - Damaged/Missing - Screens
left window Screens (Windows) - L1 - One or more screens in a
unit are punctured, torn or
otherwise damaged or
missing
Windows Bedroom Unit - Inoperable/Not - Lock/Operability
bed 2 left window stuck Lockable (Windows) - L1 - Window cannot be opened
or will not stay open (If the
window is designed to do
so.)
- Window is on 3rd floor or
below
- There IS another operable
window in the same floor
area.
- This condition DOES NOT
RESULT in a Health and
Safety concern.

Report generation date/time: 08/22/2022 01:11 PM Score Version: 2 Page: 29 of 59


Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.
Inspection Summary Report (POA) for Inspection #713096

Item Location/Comments Deficiency/Severity Decisions


Building 6 - F-4203- 101-307[Sample,Inspected] - Building Exterior
None

Building 6 - F-4203- 101-307[Sample,Inspected] - Building Systems


None

Building 6 - F-4203- 101-307[Sample,Inspected] - Common Areas


None

Building 6 - F-4203- 101-307[Sample,Inspected] - Unit (b) (6)


Non-Health And Safety Deficiencies
Windows Living Area Unit - Damaged/Missing - Screens
missing Screens (Windows) - L1 - One or more screens in a
unit are punctured, torn or
otherwise damaged or
missing
Health And Safety Deficiencies
Emergency/Fire Exits Bedroom HS - Emergency/Fire Exits - Emergency/Fire Exits
lock reversed on ac Blocked/Unusable (applies only on third or
closet room for person to (Emergency/Fire Exits) (LT) lower floors)
enter primary means - L3 - Blocked
- Blocked Door
Emergency/Fire Exits Bedroom HS - Emergency/Fire Exits - Emergency/Fire Exits
bed 2 window not Blocked/Unusable (applies only on third or
opening 2nd means (Emergency/Fire Exits) (LT) lower floors)
- L3 - Blocked
- Inoperable Window
Infestation Kitchen HS - Insects /roaches - Evidence of roaches
kitchen (Infestation) (NLT) - L3 - Multiple live roaches
observed
Windows Bedroom Unit - Inoperable/Not - Lock/Operability
bed 2 cant open Lockable (Windows) (NLT) - Window cannot be opened
- L3 or will not stay open (If the
window is designed to do
so.)
- Window is on 3rd floor or
below
- There is NOT another
operable window in the
same floor area.
Report generation date/time: 08/22/2022 01:11 PM Score Version: 2 Page: 30 of 59
Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.
Inspection Summary Report (POA) for Inspection #713096

Item Location/Comments Deficiency/Severity Decisions


- This condition MAY
RESULT in a Health and
Safety concern

Building 6 - F-4203- 101-307[Sample,Inspected] - Unit (b) (6)


Non-Health And Safety Deficiencies
Bathroom Items Bathroom Unit - Lavatory Sink - - Bathroom Sink
missing Damaged/Missing - A stopper is missing (only if
(Bathroom) - L1 there is no stopper in the
visible area)
Kitchen Items Kitchen Unit - Plumbing - Leaking - Kitchen Sink
handle leaking Faucet/Pipes (Kitchen) - L1 - There is a leak
- There is a leak or drip, but it
is contained by the sink
basin
Kitchen Items Kitchen Unit - Refrigerator - Missing - Refrigerator
bottom /Damaged/Inoperable - Door seals are deteriorated
(Kitchen) - L1
Walls Bedroom Unit - Damaged (Walls) - - Hole(s)
around tub L2 - Larger than a sheet of
paper, but you cannot see
through the hole
- ONE wall is affected.
Health And Safety Deficiencies
Infestation Kitchen HS - Insects /roaches - Evidence of roaches
kitchen (Infestation) (NLT) - L3 - Multiple live roaches
observed
Smoke Detector Bedroom Unit - Missing/Inoperable - Missing
bed 2 (Smoke Detector) (SD) - L3 - There is NOT another
functioning smoke detector
on same level.

Building 7 - G-5502 101-307[Sample,Inspected] - Building Exterior


None

Building 7 - G-5502 101-307[Sample,Inspected] - Building Systems


None

Building 7 - G-5502 101-307[Sample,Inspected] - Common Areas

Report generation date/time: 08/22/2022 01:11 PM Score Version: 2 Page: 31 of 59


Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.
Inspection Summary Report (POA) for Inspection #713096

Item Location/Comments Deficiency/Severity Decisions


None

Building 7 - G-5502 101-307[Sample,Inspected] - Unit (b) (6)


Non-Health And Safety Deficiencies
Bathroom Items Bathroom Unit - Lavatory Sink - - Bathroom Sink
missing Damaged/Missing - A stopper is missing (only if
(Bathroom) - L1 there is no stopper in the
visible area)
Ceiling Bathroom Unit - Mold/Mildew/Water - Mold or Mildew (for
over tub Stains/Water Damage example, a darkened area)
(Ceiling) - L1 or Water Stains or Water
Damage (for example
evidence of water
infiltration)
- 4 square inches to 1 square
foot and you may or may not
see water
Kitchen Items Kitchen Unit - Refrigerator - Missing - Refrigerator
bottom /Damaged/Inoperable - Door seals are deteriorated
(Kitchen) - L1
Windows Living Area Unit - Damaged/Missing - Screens
missing Screens (Windows) - L1 - One or more screens in a
unit are punctured, torn or
otherwise damaged or
missing
Windows Bedroom Unit - Damaged/Missing - Screens
bed 1 missing Screens (Windows) - L1 - One or more screens in a
unit are punctured, torn or
otherwise damaged or
missing
Windows Dining Area Unit - Damaged/Missing - Screens
bed 2 missing Screens (Windows) - L1 - One or more screens in a
unit are punctured, torn or
otherwise damaged or
missing
Health And Safety Deficiencies
Infestation Laundry Area HS - Insects /roaches - Evidence of roaches
(Infestation) (NLT) - L3 - Multiple live roaches
observed

Report generation date/time: 08/22/2022 01:11 PM Score Version: 2 Page: 32 of 59


Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.
Inspection Summary Report (POA) for Inspection #713096

Item Location/Comments Deficiency/Severity Decisions


Building 8 - H-4205- 101-307[Sample,Inspected] - Building Exterior
None

Building 8 - H-4205- 101-307[Sample,Inspected] - Building Systems


None

Building 8 - H-4205- 101-307[Sample,Inspected] - Common Areas


None

Building 8 - H-4205- 101-307[Sample,Inspected] - Unit (b) (6)


Non-Health And Safety Deficiencies
Bathroom Items Bathroom Unit - Lavatory Sink - - Bathroom Sink
missing Damaged/Missing - A stopper is missing (only if
(Bathroom) - L1 there is no stopper in the
visible area)
Doors Living Area Unit - Deteriorated/Missing - Entry Door to Unit
Seals (Entry Only) (Doors) - Seals/caulking is missing or
- L3 deteriorated to the point the
door is not weather-resistant
(if designed to have seals)
Kitchen Items Kitchen Unit - Refrigerator - Missing - Refrigerator
bottom /Damaged/Inoperable - Door seals are deteriorated
(Kitchen) - L1
Outlets/Switches Bedroom Unit - Missing/Broken Cover - Cover plate missing or
bed 1 Plates (Outlets/Switches) - broken
L1 - The electrical connections/
wires are NOT exposed.
Windows Bedroom Unit - Damaged/Missing - Screens
missing Screens (Windows) - L1 - One or more screens in a
unit are punctured, torn or
otherwise damaged or
missing
Windows Bedroom Unit - Damaged/Missing - Screens
bed 2 Screens (Windows) - L1 - One or more screens in a
unit are punctured, torn or
otherwise damaged or
missing
Windows Living Area Unit - Damaged/Missing - Screens
missing Screens (Windows) - L1 - One or more screens in a

Report generation date/time: 08/22/2022 01:11 PM Score Version: 2 Page: 33 of 59


Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.
Inspection Summary Report (POA) for Inspection #713096

Item Location/Comments Deficiency/Severity Decisions


unit are punctured, torn or
otherwise damaged or
missing
Windows Living Area Unit - Inoperable/Not - Lock/Operability
right window not staying Lockable (Windows) - L1 - Window cannot be opened
raised or will not stay open (If the
window is designed to do
so.)
- Window is on 3rd floor or
below
- There IS another operable
window in the same floor
area.
- This condition DOES NOT
RESULT in a Health and
Safety concern.
Health And Safety Deficiencies
Infestation Kitchen HS - Insects /roaches - Evidence of roaches
cabinets (Infestation) (NLT) - L3 - Multiple live roaches
observed

Building 9 - Office[Sample,Inspected] - Building Exterior


None

Building 9 - Office[Sample,Inspected] - Building Systems


Non-Health And Safety Deficiencies
Emergency Power Floor 1 BS- Auxiliary Lighting - Auxiliary lighting does not
key room Inoperable (Emergency function
Power) - L3

Building 9 - Office[Sample,Inspected] - Common Areas


None

Building 10 - 4201 102-310[Sample,Inspected] - Building Exterior


None

Building 10 - 4201 102-310[Sample,Inspected] - Building Systems


None

Building 10 - 4201 102-310[Sample,Inspected] - Common Areas

Report generation date/time: 08/22/2022 01:11 PM Score Version: 2 Page: 34 of 59


Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.
Inspection Summary Report (POA) for Inspection #713096

Item Location/Comments Deficiency/Severity Decisions


Non-Health And Safety Deficiencies
Health And Safety Deficiencies
Emergency/Fire Exits Floor 2 HS - Missing Exit Signs - Exit Signs
next to (b) (6) (Emergency/Fire Exits) - No adjacent or other internal
(NLT) - L3 /external illumination on or
near the sign

Building 10 - 4201 102-310[Sample,Inspected] - Unit (b) (6)


Non-Health And Safety Deficiencies
Bathroom Items Bathroom Unit - Lavatory Sink - - Bathroom Sink
missing Damaged/Missing - A stopper is missing (only if
(Bathroom) - L1 there is no stopper in the
visible area)
Kitchen Items Kitchen Unit - Refrigerator - Missing - Refrigerator
bottom /Damaged/Inoperable - Door seals are deteriorated
(Kitchen) - L1
Windows Kitchen Unit - Damaged/Missing - Screens
missing Screens (Windows) - L1 - One or more screens in a
unit are punctured, torn or
otherwise damaged or
missing
Windows Living Area Unit - Inoperable/Not - Lock/Operability
right window not staying Lockable (Windows) - L1 - Window cannot be opened
raised or will not stay open (If the
window is designed to do
so.)
- Window is on 3rd floor or
below
- There IS another operable
window in the same floor
area.
- This condition DOES NOT
RESULT in a Health and
Safety concern.
Windows Living Area Unit - Damaged/Missing - Screens
missing Screens (Windows) - L1 - One or more screens in a
unit are punctured, torn or
otherwise damaged or
missing
Health And Safety Deficiencies

Report generation date/time: 08/22/2022 01:11 PM Score Version: 2 Page: 35 of 59


Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.
Inspection Summary Report (POA) for Inspection #713096

Item Location/Comments Deficiency/Severity Decisions


Emergency/Fire Exits Bedroom HS - Emergency/Fire Exits - Emergency/Fire Exits
bed 1 window not staying Blocked/Unusable (applies only on third or
raised 2nd means (Emergency/Fire Exits) (LT) lower floors)
- L3 - Blocked
- Inoperable Window
Infestation Bathroom HS - Insects /roaches - Evidence of roaches
bathroom (Infestation) (NLT) - L3 - Multiple live roaches
observed
Windows Bedroom Unit - Inoperable/Not - Lock/Operability
bed 1 Lockable (Windows) (NLT) - Window cannot be opened
- L3 or will not stay open (If the
window is designed to do
so.)
- Window is on 3rd floor or
below
- There is NOT another
operable window in the
same floor area.
- This condition MAY
RESULT in a Health and
Safety concern

Building 11 - 4203 102-308[Sample,Inspected] - Building Exterior


None

Building 11 - 4203 102-308[Sample,Inspected] - Building Systems


None

Building 11 - 4203 102-308[Sample,Inspected] - Common Areas


None

Building 11 - 4203 102-308[Sample,Inspected] - Unit (b) (6)


Non-Health And Safety Deficiencies
Bathroom Items Bathroom Unit - Plumbing Leaking - Shower or Tub (Unit)
shower head Faucet/Pipes (Bathroom) - - There is a leak
L1 - There is a leak or drip, but it
is contained by the shower
or tub basin
Doors Bedroom Unit - Damaged Hardware/ - All Other Doors (includes
bed 2 Locks (Doors) - L2 closet or other interior

Report generation date/time: 08/22/2022 01:11 PM Score Version: 2 Page: 36 of 59


Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.
Inspection Summary Report (POA) for Inspection #713096

Item Location/Comments Deficiency/Severity Decisions


doors)
- Hardware is damaged or
missing
- Other interior door does not
function as it should or
cannot be locked.
Outlets/Switches Bathroom Unit - Missing/Broken Cover - Cover plate missing or
bathroom Plates (Outlets/Switches) - broken
L1 - The electrical connections/
wires are NOT exposed.
Windows Bedroom Unit - Damaged/Missing - Screens
bed 1 Screens (Windows) - L1 - One or more screens in a
unit are punctured, torn or
otherwise damaged or
missing
Windows Bedroom Unit - Damaged/Missing - Screens
bed 2 Screens (Windows) - L1 - One or more screens in a
unit are punctured, torn or
otherwise damaged or
missing
Windows Living Area Unit - Damaged/Missing - Screens
missing Screens (Windows) - L1 - One or more screens in a
unit are punctured, torn or
otherwise damaged or
missing

Building 12 - 4205 102-308[Sample,Inspected] - Building Exterior


None

Building 12 - 4205 102-308[Sample,Inspected] - Building Systems


Non-Health And Safety Deficiencies
Health And Safety Deficiencies
Electrical System Floor 1 BS- Missing Breakers/ - Breaker/fuse missing, or
maint shop bathroom Fuses (Electrical System) open port not properly
missing breakers (LT) - L3 blanked off

Building 12 - 4205 102-308[Sample,Inspected] - Common Areas


Non-Health And Safety Deficiencies
Closet/Utility/ Floor 1 CA - Damaged Surface - All Other Doors (includes
Mechanical maint shop (Holes/Paint/Rust/Glass)
Report generation date/time: 08/22/2022 01:11 PM Score Version: 2 Page: 37 of 59
Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.
Inspection Summary Report (POA) for Inspection #713096

Item Location/Comments Deficiency/Severity Decisions


(Doors) - L3 closet or other interior
doors)
- Surface is damaged
- Door has holes.
- Greater than 1 inch
- This condition DOES NOT
RESULT in a Health and
Safety concern.
Closet/Utility/ Floor 1 CA - Peeling/Needs Paint - Peeling Paint or Needs
Mechanical maint shop (Ceiling) - L1 Paint
- Peeling paint on 1 to 4
ceilings in common areas
Health And Safety Deficiencies
Electrical Hazards Floor 1 HS - Exposed Wires/Open - Exposed bare wires
ac cover in maint shop Panels (Electrical Hazards) - The exposed bare wires
unsecured leaving (LT) - L3 ARE capped BUT NOT
exposed connections on enclosed in a secured
breaker electrical box OR ARE NOT
capped
Electrical Hazards Floor 1 HS - Exposed Wires/Open - Openings in electrical
laundry room behind Panels (Electrical Hazards) panels
dryers gap greater than a (LT) - L3 - The openings in the
1/4 inch in breaker panel electrical panels are NOT
properly covered.

Building 12 - 4205 102-308[Sample,Inspected] - Unit (b) (6)


Non-Health And Safety Deficiencies
Bathroom Items Bathroom Unit - Plumbing Leaking - Shower or Tub (Unit)
head Faucet/Pipes (Bathroom) - - There is a leak
L1 - There is a leak or drip, but it
is contained by the shower
or tub basin
Windows Living Area Unit - Damaged/Missing - Screens
right window Screens (Windows) - L1 - One or more screens in a
unit are punctured, torn or
otherwise damaged or
missing
Windows Bedroom Unit - Damaged/Missing - Screens
bed 1 Screens (Windows) - L1 - One or more screens in a
unit are punctured, torn or

Report generation date/time: 08/22/2022 01:11 PM Score Version: 2 Page: 38 of 59


Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.
Inspection Summary Report (POA) for Inspection #713096

Item Location/Comments Deficiency/Severity Decisions


otherwise damaged or
missing

Building 13 - 4210 102-308[Sample,Inspected] - Building Exterior


None

Building 13 - 4210 102-308[Sample,Inspected] - Building Systems


None

Building 13 - 4210 102-308[Sample,Inspected] - Common Areas


Non-Health And Safety Deficiencies
Health And Safety Deficiencies
Electrical Hazards Floor 1 HS - Exposed Wires/Open - Exposed bare wires
fire panel door not Panels (Electrical Hazards) - The exposed bare wires
secured high voltage (LT) - L3 ARE capped BUT NOT
wiring exposed enclosed in a secured
electrical box OR ARE NOT
capped
Emergency/Fire Exits Floor 1 HS - Missing Exit Signs - Exit Signs
right of (b) (6) (Emergency/Fire Exits) - No adjacent or other internal
(NLT) - L3 /external illumination on or
near the sign

Building 13 - 4210 102-308[Sample,Inspected] - Unit (b) (6)


Non-Health And Safety Deficiencies
Bathroom Items Bathroom Unit - Lavatory Sink - - Bathroom Sink
missing Damaged/Missing - A stopper is missing (only if
(Bathroom) - L1 there is no stopper in the
visible area)
Doors Hallway Unit - Damaged Hardware/ - All Other Doors (includes
damaged lockset Locks (Doors) - L1 closet or other interior
doors)
- Hardware is damaged or
missing
- Closet door does not
function as it should or
cannot be locked.
Windows Bedroom Unit- Missing/Deteriorated - Caulking, Seals, or Glazing
bed 1 leaking thermo seal Caulking/Seals/Glazing Compound (includes
Compound (Windows) - L3 thermopane or insulated
Report generation date/time: 08/22/2022 01:11 PM Score Version: 2 Page: 39 of 59
Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.
Inspection Summary Report (POA) for Inspection #713096

Item Location/Comments Deficiency/Severity Decisions


windows)
- Deteriorated or missing
- Window is damaged and not
weather-resistant OR there
is damage to the
surrounding structure OR
there is condensation or
discoloration between the
glass panes of a
Thermopane
Windows Bedroom Unit- Missing/Deteriorated - Caulking, Seals, or Glazing
bed 2 leaking thermo seal Caulking/Seals/Glazing Compound (includes
Compound (Windows) - L3 thermopane or insulated
windows)
- Deteriorated or missing
- Window is damaged and not
weather-resistant OR there
is damage to the
surrounding structure OR
there is condensation or
discoloration between the
glass panes of a
Thermopane
Windows Bedroom Unit - Damaged/Missing - Screens
missing Screens (Windows) - L1 - One or more screens in a
unit are punctured, torn or
otherwise damaged or
missing
Health And Safety Deficiencies
Smoke Detector Bedroom Unit - Missing/Inoperable - Inoperable
bed 2 inop (Smoke Detector) (SD) - L3 - There is NOT another
functioning smoke detector
on same level.
Windows Bedroom Unit - Inoperable/Not - Lock/Operability
bed 2 window not Lockable (Windows) (NLT) - Window cannot be opened
opening 2nd means - L3 or will not stay open (If the
window is designed to do
so.)
- Window is on 3rd floor or
below
- There is NOT another

Report generation date/time: 08/22/2022 01:11 PM Score Version: 2 Page: 40 of 59


Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.
Inspection Summary Report (POA) for Inspection #713096

Item Location/Comments Deficiency/Severity Decisions


operable window in the
same floor area.
- This condition MAY
RESULT in a Health and
Safety concern

Building 13 - 4210 102-308[Sample,Inspected] - Unit (b) (6)


Non-Health And Safety Deficiencies
Doors Bedroom Unit - Damaged Hardware/ - All Other Doors (includes
bed 2 missing styker Locks (Doors) - L2 closet or other interior
doors)
- Hardware is damaged or
missing
- Other interior door does not
function as it should or
cannot be locked.
Kitchen Items Kitchen Unit - Refrigerator - Missing - Refrigerator
bottom /Damaged/Inoperable - Door seals are deteriorated
(Kitchen) - L1
Health And Safety Deficiencies
Emergency/Fire Exits Bedroom HS - Emergency/Fire Exits - Emergency/Fire Exits
bed 2 window not staying Blocked/Unusable (applies only on third or
raised 2nd means (Emergency/Fire Exits) (LT) lower floors)
- L3 - Blocked
- Inoperable Window
Infestation Kitchen HS - Insects /roaches - Evidence of roaches
kitchen (Infestation) (NLT) - L3 - Multiple live roaches
observed
Windows Bedroom Unit - Inoperable/Not - Lock/Operability
window lock clips Lockable (Windows) (NLT) - Lock is missing or damaged
damaged - L3 (only if the window was
designed to lock)
- Window is NOT accessible
from outside
Windows Bedroom Unit - Inoperable/Not - Lock/Operability
bed 2 Lockable (Windows) (NLT) - Window cannot be opened
- L3 or will not stay open (If the
window is designed to do
so.)
- Window is on 3rd floor or

Report generation date/time: 08/22/2022 01:11 PM Score Version: 2 Page: 41 of 59


Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.
Inspection Summary Report (POA) for Inspection #713096

Item Location/Comments Deficiency/Severity Decisions


below
- There is NOT another
operable window in the
same floor area.
- This condition MAY
RESULT in a Health and
Safety concern

Building 13 - 4210 102-308[Sample,Inspected] - Unit (b) (6)


Non-Health And Safety Deficiencies
Kitchen Items Kitchen Unit - Refrigerator - Missing - Refrigerator
bottom /Damaged/Inoperable - Door seals are deteriorated
(Kitchen) - L1
Windows Living Area Unit - Damaged/Missing - Screens
missing Screens (Windows) - L1 - One or more screens in a
unit are punctured, torn or
otherwise damaged or
missing
Windows Living Area Unit - Inoperable/Not - Lock/Operability
left window Lockable (Windows) - L1 - Window cannot be opened
or will not stay open (If the
window is designed to do
so.)
- Window is on 3rd floor or
below
- There IS another operable
window in the same floor
area.
- This condition DOES NOT
RESULT in a Health and
Safety concern.
Windows Bedroom Unit - Damaged/Missing - Screens
bed 1 damaged Screens (Windows) - L1 - One or more screens in a
unit are punctured, torn or
otherwise damaged or
missing
Windows Bedroom Unit - Damaged/Missing - Screens
missing bed 2 Screens (Windows) - L1 - One or more screens in a
unit are punctured, torn or
otherwise damaged or
missing

Report generation date/time: 08/22/2022 01:11 PM Score Version: 2 Page: 42 of 59


Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.
Inspection Summary Report (POA) for Inspection #713096

Item Location/Comments Deficiency/Severity Decisions


Health And Safety Deficiencies
Emergency/Fire Exits Bedroom HS - Emergency/Fire Exits - Emergency/Fire Exits
bed blocking window 2nd Blocked/Unusable (applies only on third or
means (Emergency/Fire Exits) (LT) lower floors)
- L3 - Blocked
- Furniture
Infestation Living Area HS - Insects /roaches - Evidence of roaches
livingroom (Infestation) (NLT) - L3 - Multiple live roaches
observed
Kitchen Items Kitchen Unit - Cabinets - Missing/ - Kitchen Cabinets
1 of 2 drawers Damaged (Kitchen) (NLT) - - Cabinets, doors, shelves, or
L3 laminate damaged or
missing
- More than 50% of cabinets,
doors, shelves, or laminate
damaged or missing

Building 14 - 4220 101-308[Sample,Inspected] - Building Exterior


Non-Health And Safety Deficiencies
Walls rear center 2nd floor BE- Stained/Peeling/Needs - Stains or Peeling Paint or
Paint (Walls) - L1 Needs Paint
- Less than 50% of a single
wall is affected

Building 14 - 4220 101-308[Sample,Inspected] - Building Systems


None

Building 14 - 4220 101-308[Sample,Inspected] - Common Areas


Non-Health And Safety Deficiencies
Closet/Utility/ Floor 1 CA - Peeling/Needs Paint - Peeling Paint or Needs
Mechanical left wall (Walls) - L1 Paint
- 1 to 4 square feet of two or
more wall areas
Laundry Room Floor 1 CA - Peeling/Needs Paint - Peeling Paint or Needs
behind dryers (Ceiling) - L1 Paint
- Peeling paint on 1 to 4
ceilings in common areas
Health And Safety Deficiencies
Electrical Hazards Floor 1 HS - Exposed Wires/Open - Exposed bare wires

Report generation date/time: 08/22/2022 01:11 PM Score Version: 2 Page: 43 of 59


Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.
Inspection Summary Report (POA) for Inspection #713096

Item Location/Comments Deficiency/Severity Decisions


maint shop missing Panels (Electrical Hazards) - The exposed bare wires
knockout in outlet box (LT) - L3 ARE capped BUT NOT
over bench enclosed in a secured
electrical box OR ARE NOT
capped

Building 14 - 4220 101-308[Sample,Inspected] - Unit (b) (6)


Non-Health And Safety Deficiencies
Doors Bedroom Unit - Damaged Hardware/ - All Other Doors (includes
not latching Locks (Doors) - L1 closet or other interior
doors)
- Hardware is damaged or
missing
- Closet door does not
function as it should or
cannot be locked.
Kitchen Items Kitchen Unit - Dishwasher/Garbage - Dishwasher or Garbage
inop Disposal - Inoperable Disposal
(Kitchen) - L2 - Garbage disposal does not
function
Kitchen Items Kitchen Unit - Range/Stove- Missing - Range/Stove/Oven
right rear /Damaged/Inoperable - Electric Range/Stove/Oven
(Kitchen) - L2 - Burner(s) not functioning
- ONE burner is not
functioning.
Kitchen Items Kitchen Unit - Refrigerator - Missing - Refrigerator
bottom inside corner /Damaged/Inoperable - Door seals are deteriorated
(Kitchen) - L1
Kitchen Items Kitchen Unit - Range/Stove- Missing - Range/Stove/Oven
2 of 4 /Damaged/Inoperable - Electric Range/Stove/Oven
(Kitchen) - L1 - A control knob is missing
(knob cannot be located and
reinstalled)
Windows Living Area Unit - Damaged/Missing - Screens
right side missing Screens (Windows) - L1 - One or more screens in a
unit are punctured, torn or
otherwise damaged or
missing
Health And Safety Deficiencies
Emergency/Fire Exits Bedroom HS - Emergency/Fire Exits - Emergency/Fire Exits

Report generation date/time: 08/22/2022 01:11 PM Score Version: 2 Page: 44 of 59


Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.
Inspection Summary Report (POA) for Inspection #713096

Item Location/Comments Deficiency/Severity Decisions


bed 2 window not staying Blocked/Unusable (applies only on third or
raised 2nd means (Emergency/Fire Exits) (LT) lower floors)
- L3 - Blocked
- Inoperable Window
Kitchen Items Kitchen Unit - Plumbing - Clogged - Kitchen Sink
clogged Drains (Kitchen) (NLT) - L3 - There is a problem with the
drainage
- The drain is completely
clogged, and water will not
drain at all
Windows Bedroom Unit - Inoperable/Not - Lock/Operability
bed 2 Lockable (Windows) (NLT) - Window cannot be opened
- L3 or will not stay open (If the
window is designed to do
so.)
- Window is on 3rd floor or
below
- There is NOT another
operable window in the
same floor area.
- This condition MAY
RESULT in a Health and
Safety concern

Building 14 - 4220 101-308[Sample,Inspected] - Unit (b) (6)


Non-Health And Safety Deficiencies
Bathroom Items Bathroom Unit - Plumbing Leaking - Shower or Tub (Unit)
head leaking at threads Faucet/Pipes (Bathroom) - - There is a leak
L1 - There is a leak or drip, but it
is contained by the shower
or tub basin
Bathroom Items Bathroom Unit - Bathroom Cabinets - - Bathroom Cabinets
right drawer damaged Damaged/Missing - Damaged or missing
(Bathroom) - L1 cabinets, shelves, vanity
tops, drawers, medicine
cabinets, or doors. They
ARE NOT functioning for
storage or their intended
purpose.
Doors Bedroom Unit - Damaged Hardware/ - All Other Doors (includes
bed 2 not latching Locks (Doors) - L2 closet or other interior

Report generation date/time: 08/22/2022 01:11 PM Score Version: 2 Page: 45 of 59


Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.
Inspection Summary Report (POA) for Inspection #713096

Item Location/Comments Deficiency/Severity Decisions


doors)
- Hardware is damaged or
missing
- Other interior door does not
function as it should or
cannot be locked.
Outlets/Switches Bathroom Unit - Missing/Broken Cover - Cover plate missing or
right of sink Plates (Outlets/Switches) - broken
L1 - The electrical connections/
wires are NOT exposed.
Water Heater Storage Unit - General Rust/ - Rust or corrosion
leaking ac line rusting out Corrosion (Hot Water - Metal oxides, flaking or
bottom of tank Heater) - L2 discoloration--or a pit or
crevice
- This does NOT prevent the
hot water heater from
functioning.
Windows Bedroom Unit - Damaged/Missing - Screens
bed 2 missing Screens (Windows) - L1 - One or more screens in a
unit are punctured, torn or
otherwise damaged or
missing
Windows Living Area Unit - Damaged/Missing - Screens
missing Screens (Windows) - L1 - One or more screens in a
unit are punctured, torn or
otherwise damaged or
missing
Health And Safety Deficiencies
Windows Living Area Unit - Inoperable/Not - Lock/Operability
left window not locking Lockable (Windows) (NLT) - Lock is missing or damaged
- L3 (only if the window was
designed to lock)
- Window is accessible from
outside (for example,
ground level or by means of
exterior stairway)
- Window can be opened
from outside.

Building 14 - 4220 101-308[Sample,Inspected] - Unit (b) (6)

Report generation date/time: 08/22/2022 01:11 PM Score Version: 2 Page: 46 of 59


Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.
Inspection Summary Report (POA) for Inspection #713096

Item Location/Comments Deficiency/Severity Decisions


Non-Health And Safety Deficiencies
Kitchen Items Kitchen Unit - Plumbing - Leaking - Kitchen Sink
faucet leaking at base Faucet/Pipes (Kitchen) - L1 - There is a leak
- There is a leak or drip, but it
is contained by the sink
basin
Windows Bedroom Unit - Damaged/Missing - Screens
bed 1 Screens (Windows) - L1 - One or more screens in a
unit are punctured, torn or
otherwise damaged or
missing
Health And Safety Deficiencies
Emergency/Fire Exits Bedroom HS - Emergency/Fire Exits - Emergency/Fire Exits
bed 2 window not staying Blocked/Unusable (applies only on third or
raised 2nd means (Emergency/Fire Exits) (LT) lower floors)
- L3 - Blocked
- Inoperable Window
Infestation Kitchen HS - Insects /roaches - Evidence of roaches
kitchen (Infestation) (NLT) - L3 - Multiple live roaches
observed
Windows Bedroom Unit - Inoperable/Not - Lock/Operability
bed 2 Lockable (Windows) (NLT) - Window cannot be opened
- L3 or will not stay open (If the
window is designed to do
so.)
- Window is on 3rd floor or
below
- There is NOT another
operable window in the
same floor area.
- This condition MAY
RESULT in a Health and
Safety concern
Windows Living Area Unit - Inoperable/Not - Lock/Operability
right window locks Lockable (Windows) (NLT) - Lock is missing or damaged
damaged - L3 (only if the window was
designed to lock)
- Window is accessible from
outside (for example,
ground level or by means of
exterior stairway)
Report generation date/time: 08/22/2022 01:11 PM Score Version: 2 Page: 47 of 59
Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.
Inspection Summary Report (POA) for Inspection #713096

Item Location/Comments Deficiency/Severity Decisions


- Window can be opened
from outside.

Building 15 - 5502 102-308[Sample,Inspected] - Building Exterior


None

Building 15 - 5502 102-308[Sample,Inspected] - Building Systems


None

Building 15 - 5502 102-308[Sample,Inspected] - Common Areas


None

Building 15 - 5502 102-308[Sample,Inspected] - Unit (b) (6)


Non-Health And Safety Deficiencies
Bathroom Items Bathroom Unit - Lavatory Sink - - Bathroom Sink
missing Damaged/Missing - A stopper is missing (only if
(Bathroom) - L1 there is no stopper in the
visible area)
Doors Living Area Unit - Deteriorated/Missing - Entry Door to Unit
front entry Seals (Entry Only) (Doors) - Seals/caulking is missing or
- L3 deteriorated to the point the
door is not weather-resistant
(if designed to have seals)
Kitchen Items Kitchen Unit - Refrigerator - Missing - Refrigerator
bottom door /Damaged/Inoperable - Door seals are deteriorated
(Kitchen) - L1
Windows Living Area Unit - Damaged/Missing - Screens
missing Screens (Windows) - L1 - One or more screens in a
unit are punctured, torn or
otherwise damaged or
missing
Health And Safety Deficiencies
Bathroom Items Bathroom Unit - Shower/Tub - - Shower or Tub (Unit)
missing hardware Damaged/Missing - The hardware is missing or
(Bathroom) (NLT) - L3 is not functioning
Emergency/Fire Exits Bedroom HS - Emergency/Fire Exits - Emergency/Fire Exits
bed 2 window cannot be Blocked/Unusable (applies only on third or
opened 2nd means (Emergency/Fire Exits) (LT) lower floors)
- L3 - Blocked

Report generation date/time: 08/22/2022 01:11 PM Score Version: 2 Page: 48 of 59


Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.
Inspection Summary Report (POA) for Inspection #713096

Item Location/Comments Deficiency/Severity Decisions


- Inoperable Window
Infestation Living Area HS - Insects /roaches - Evidence of roaches
livingroom (Infestation) (NLT) - L3 - Multiple live roaches
observed
Windows Bedroom Unit - Inoperable/Not - Lock/Operability
bed 2 lock damaged Lockable (Windows) (NLT) - Window cannot be opened
- L3 or will not stay open (If the
window is designed to do
so.)
- Window is on 3rd floor or
below
- There is NOT another
operable window in the
same floor area.
- This condition MAY
RESULT in a Health and
Safety concern

Building 15 - 5502 102-308[Sample,Inspected] - Unit (b) (6)


Non-Health And Safety Deficiencies
Windows Bedroom Unit - Damaged/Missing - Screens
bed 2 Screens (Windows) - L1 - One or more screens in a
unit are punctured, torn or
otherwise damaged or
missing
Windows Bedroom Unit - Damaged/Missing - Screens
bed 3 Screens (Windows) - L1 - One or more screens in a
unit are punctured, torn or
otherwise damaged or
missing
Health And Safety Deficiencies
Doors Living Area Unit - Damaged Frames/ - Entry Door to Unit
front entry Threshold/Lintels/Trim - Frame is damaged causing
(Doors) (NLT) - L3 the door not to function or
lock (this includes
thresholds, lintels, trim,
headers, and jambs) or light
can be observed around the
edges and you observe no
seal deterioration
- This condition DOES NOT
Report generation date/time: 08/22/2022 01:11 PM Score Version: 2 Page: 49 of 59
Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.
Inspection Summary Report (POA) for Inspection #713096

Item Location/Comments Deficiency/Severity Decisions


RESULT in a Health and
Safety concern.
Emergency/Fire Exits Bedroom HS - Emergency/Fire Exits - Emergency/Fire Exits
bed 2 window stops Blocked/Unusable (applies only on third or
intalled incorectly and (Emergency/Fire Exits) (LT) lower floors)
windows cannot be - L3 - Blocked
opened 2nd meand - Inoperable Window
Smoke Detector Hallway Unit - Missing/Inoperable - Missing
missing (Smoke Detector) (SD) - L3 - There is NOT another
functioning smoke detector
on same level.
Windows Living Area Unit - Inoperable/Not - Lock/Operability
windows sealed shut Lockable (Windows) (NLT) - Window cannot be opened
- L3 or will not stay open (If the
window is designed to do
so.)
- Window is on 3rd floor or
below
- There is NOT another
operable window in the
same floor area.
- This condition MAY
RESULT in a Health and
Safety concern

Building 16 - 5711 101-308[Sample,Inspected] - Building Exterior


Non-Health And Safety Deficiencies
Walls front right corner 3rd BE- Missing Pieces/Holes/ - Hole(s)
story Spalling (Walls) - L2 - Greater than 1/2" in
diameter, but smaller than a
sheet of paper

Building 16 - 5711 101-308[Sample,Inspected] - Building Systems


None

Building 16 - 5711 101-308[Sample,Inspected] - Common Areas


None

Building 16 - 5711 101-308[Sample,Inspected] - Unit (b) (6)


Non-Health And Safety Deficiencies

Report generation date/time: 08/22/2022 01:11 PM Score Version: 2 Page: 50 of 59


Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.
Inspection Summary Report (POA) for Inspection #713096

Item Location/Comments Deficiency/Severity Decisions


Bathroom Items Bathroom Unit - Lavatory Sink - - Bathroom Sink
missing Damaged/Missing - A stopper is missing (only if
(Bathroom) - L1 there is no stopper in the
visible area)
Bathroom Items Bathroom Unit - Plumbing Leaking - Shower or Tub (Unit)
shower head Faucet/Pipes (Bathroom) - - There is a leak
L1 - There is a leak or drip, but it
is contained by the shower
or tub basin
Kitchen Items Kitchen Unit - Plumbing - Leaking - Kitchen Sink
faucet leak at base Faucet/Pipes (Kitchen) - L1 - There is a leak
- There is a leak or drip, but it
is contained by the sink
basin
Lighting Living Area Unit - Missing/Inoperable - In 2 rooms in this unit, a
hallway dining area Fixture (Lighting) - L2 permanent lighting fixture is
missing or not functioning
- There is NOT another
permanent switched light
source in room.
Outlets/Switches Kitchen Unit - Missing/Broken Cover - Cover plate missing or
left of stove Plates (Outlets/Switches) - broken
L1 - The electrical connections/
wires are NOT exposed.
Windows Living Area Unit - Damaged/Missing - Screens
missing Screens (Windows) - L1 - One or more screens in a
unit are punctured, torn or
otherwise damaged or
missing
Windows Bedroom Unit - Damaged/Missing - Screens
bed 2 Screens (Windows) - L1 - One or more screens in a
unit are punctured, torn or
otherwise damaged or
missing
Health And Safety Deficiencies
Bathroom Items Bathroom Unit - Shower/Tub - - Shower or Tub (Unit)
missing overflow Damaged/Missing - The hardware is missing or
(Bathroom) (NLT) - L3 is not functioning
Electrical System Kitchen Unit - GFI - Inoperable - GFI does not function when

Report generation date/time: 08/22/2022 01:11 PM Score Version: 2 Page: 51 of 59


Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.
Inspection Summary Report (POA) for Inspection #713096

Item Location/Comments Deficiency/Severity Decisions


not testing right of sink (Electrical System) (NLT) - self-test button is pressed
L3
Emergency/Fire Exits Bedroom HS - Emergency/Fire Exits - Emergency/Fire Exits
bed 1 2nd means Blocked/Unusable (applies only on third or
(Emergency/Fire Exits) (LT) lower floors)
- L3 - Blocked
- Inoperable Window
Infestation Kitchen HS - Insects /roaches - Evidence of roaches
(Infestation) (NLT) - L3 - Multiple live roaches
observed
Smoke Detector Bedroom Unit - Missing/Inoperable - Missing
bed 1 (Smoke Detector) (SD) - L3 - There is NOT another
functioning smoke detector
on same level.
Smoke Detector Bedroom Unit - Missing/Inoperable - Missing
bed 2 (Smoke Detector) (SD) - L3 - There is NOT another
functioning smoke detector
on same level.

Building 16 - 5711 101-308[Sample,Inspected] - Unit (b) (6)


Non-Health And Safety Deficiencies
Doors Bedroom Unit - Damaged Surface - All Other Doors (includes
bed 2 closet door (Holes/Paint/Rust/Glass) closet or other interior
(Doors) - L3 doors)
- Surface is damaged
- Door has holes.
- Greater than 1 inch
- This condition DOES NOT
RESULT in a Health and
Safety concern.
Doors Bathroom Unit - Damaged Hardware/ - Bathroom Door
damaged Locks (Doors) - L3 - Hardware is damaged or
missing
- Door does not function as it
should (it does not properly
latch).
Windows Living Area Unit - Damaged/Missing - Screens
left window Screens (Windows) - L1 - One or more screens in a
unit are punctured, torn or
otherwise damaged or

Report generation date/time: 08/22/2022 01:11 PM Score Version: 2 Page: 52 of 59


Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.
Inspection Summary Report (POA) for Inspection #713096

Item Location/Comments Deficiency/Severity Decisions


missing
Windows Bedroom Unit - Damaged/Missing - Screens
missing Screens (Windows) - L1 - One or more screens in a
unit are punctured, torn or
otherwise damaged or
missing
Windows Bedroom Unit - Damaged/Missing - Screens
bed 2 missing Screens (Windows) - L1 - One or more screens in a
unit are punctured, torn or
otherwise damaged or
missing
Health And Safety Deficiencies
Bathroom Items Bedroom Unit - Shower/Tub - - Shower or Tub (Unit)
drain spider damaged Damaged/Missing - The hardware is missing or
(Bathroom) (NLT) - L3 is not functioning
Infestation Kitchen HS - Insects /roaches - Evidence of roaches
sink (Infestation) (NLT) - L3 - Multiple live roaches
observed

Building 16 - 5711 101-308[Sample,Inspected] - Unit (b) (6)


Non-Health And Safety Deficiencies
Doors Dining Area Unit - Damaged Hardware/ - All Other Doors (includes
unable to test Locks (Doors) - L2 closet or other interior
doors)
- Hardware is damaged or
missing
- Other interior door does not
function as it should or
cannot be locked.
Kitchen Items Kitchen Unit - Sink - Missing/ - Kitchen Sink
cant inspect Damaged (Kitchen) - L3 - The sink''s hardware is
missing or is not functioning
Kitchen Items Kitchen Unit - Range/Stove- Missing - Range/Stove/Oven
unable to test /Damaged/Inoperable - Electric Range/Stove/Oven
(Kitchen) - L3 - Oven is not functioning
- This condition MAY
RESULT in a Health and
Safety concern
Kitchen Items Kitchen Unit - Dishwasher/Garbage - Dishwasher or Garbage

Report generation date/time: 08/22/2022 01:11 PM Score Version: 2 Page: 53 of 59


Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.
Inspection Summary Report (POA) for Inspection #713096

Item Location/Comments Deficiency/Severity Decisions


unable to test Disposal - Inoperable Disposal
(Kitchen) - L2 - Dishwasher does not
function
Lighting Kitchen Unit - Missing/Inoperable - In 2 rooms in this unit, a
inop Fixture (Lighting) - L2 permanent lighting fixture is
missing or not functioning
- There is NOT another
permanent switched light
source in room.
Health And Safety Deficiencies
Bathroom Items Bathroom Unit - Shower/Tub - - Shower or Tub (Unit)
unable to inspect Damaged/Missing - The hardware is missing or
(Bathroom) (NLT) - L3 is not functioning
Bathroom Items Bedroom Unit - Water Closet/Toilet- - Toilet (Unit)
unable to test Damaged/Clogged/Missing - It does not flush
(Bathroom) (NLT) - L3
Emergency/Fire Exits Living Area HS - Emergency/Fire Exits - Emergency/Fire Exits
hoarding conditions Blocked/Unusable (applies only on third or
blocking egress (Emergency/Fire Exits) (LT) lower floors)
- L3 - Blocked
- Other Condition (Please
explain other condition in
the box below)
Emergency/Fire Exits Bedroom HS - Emergency/Fire Exits - Emergency/Fire Exits
hoarding conditions Blocked/Unusable (applies only on third or
(Emergency/Fire Exits) (LT) lower floors)
- L3 - Blocked
- Other Condition (Please
explain other condition in
the box below)
Kitchen Items Laundry Area Unit - Refrigerator - Missing - Refrigerator
unable to inspect /Damaged/Inoperable - Does not cool adequately
(Kitchen) (NLT) - L3 for the safe storage of food
Smoke Detector Hallway Unit - Missing/Inoperable - Inoperable
turned off at breaker (Smoke Detector) (SD) - L3 - There is NOT another
functioning smoke detector
on same level.

Building 17 - 5715-101--310[Sample,Inspected] - Building Exterior


None
Report generation date/time: 08/22/2022 01:11 PM Score Version: 2 Page: 54 of 59
Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.
Inspection Summary Report (POA) for Inspection #713096

Item Location/Comments Deficiency/Severity Decisions


Building 17 - 5715-101--310[Sample,Inspected] - Building Systems
None

Building 17 - 5715-101--310[Sample,Inspected] - Common Areas


None

Building 17 - 5715-101--310[Sample,Inspected] - Unit (b) (6)


Non-Health And Safety Deficiencies
Bathroom Items Bathroom Unit - Water Closet/Toilet- - Toilet (Unit)
missing flush handle Damaged/Clogged/Missing - Seat, hinge, cover, or flush
(Bathroom) - L2 handle is missing or
damaged
Bathroom Items Bathroom Unit - Bathroom Cabinets - - Bathroom Cabinets
missing 1 of 2 doors Damaged/Missing - Damaged or missing
(Bathroom) - L1 cabinets, shelves, vanity
tops, drawers, medicine
cabinets, or doors. They
ARE NOT functioning for
storage or their intended
purpose.
Kitchen Items Kitchen Unit - Refrigerator - Missing - Refrigerator
top of bottom door /Damaged/Inoperable - Door seals are deteriorated
(Kitchen) - L1
Walls Bathroom Unit - Damaged (Walls) - - Hole(s)
around tub L2 - Larger than a sheet of
paper, but you cannot see
through the hole
- ONE wall is affected.
Windows Bedroom Unit - Damaged/Missing - Screens
bed 1 Screens (Windows) - L1 - One or more screens in a
unit are punctured, torn or
otherwise damaged or
missing
Windows Bedroom Unit - Damaged/Missing - Screens
bed 2 missing Screens (Windows) - L1 - One or more screens in a
unit are punctured, torn or
otherwise damaged or
missing
Windows Living Area Unit - Damaged/Missing - Screens

Report generation date/time: 08/22/2022 01:11 PM Score Version: 2 Page: 55 of 59


Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.
Inspection Summary Report (POA) for Inspection #713096

Item Location/Comments Deficiency/Severity Decisions


missing Screens (Windows) - L1 - One or more screens in a
unit are punctured, torn or
otherwise damaged or
missing
Health And Safety Deficiencies
Bathroom Items Bathroom Unit - Plumbing - Clogged - Bathroom Sink
clogged drain Drains (Bathroom) (NLT) - - There is a problem with the
L3 drainage
- The drain is completely
clogged, and water will not
drain at all OR shows
extensive deterioration
Infestation Kitchen HS - Insects /roaches - Evidence of roaches
cabinets (Infestation) (NLT) - L3 - Multiple live roaches
observed
Smoke Detector Hallway Unit - Missing/Inoperable - Missing
missing (Smoke Detector) (SD) - L3 - There is NOT another
functioning smoke detector
on same level.
Smoke Detector Bedroom Unit - Missing/Inoperable - Missing
bed 2 (Smoke Detector) (SD) - L3 - There is NOT another
functioning smoke detector
on same level.

Building 17 - 5715-101--310[Sample,Inspected] - Unit (b) (6)


Non-Health And Safety Deficiencies
Windows Bedroom Unit - Damaged/Missing - Screens
bed 1 missing Screens (Windows) - L1 - One or more screens in a
unit are punctured, torn or
otherwise damaged or
missing
Health And Safety Deficiencies
Infestation Bathroom HS - Insects /roaches - Evidence of roaches
bathroom (Infestation) (NLT) - L3 - Multiple live roaches
observed
Kitchen Items Kitchen Unit - Refrigerator - Missing - Refrigerator
missing /Damaged/Inoperable - Missing
(Kitchen) (NLT) - L3

Report generation date/time: 08/22/2022 01:11 PM Score Version: 2 Page: 56 of 59


Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.
Inspection Summary Report (POA) for Inspection #713096

Item Location/Comments Deficiency/Severity Decisions


(b) (6)
Building 17 - 5715-101--310[Sample,Inspected] - Unit
Non-Health And Safety Deficiencies
Bathroom Items Bathroom Unit - Lavatory Sink - - Bathroom Sink
missing Damaged/Missing - A stopper is missing (only if
(Bathroom) - L1 there is no stopper in the
visible area)
Kitchen Items Kitchen Unit - Refrigerator - Missing - Refrigerator
bottom /Damaged/Inoperable - Door seals are deteriorated
(Kitchen) - L1
Windows Bedroom Unit - Damaged/Missing - Screens
bed 1 missing Screens (Windows) - L1 - One or more screens in a
unit are punctured, torn or
otherwise damaged or
missing
Windows Bedroom Unit - Damaged/Missing - Screens
missing bed 2 Screens (Windows) - L1 - One or more screens in a
unit are punctured, torn or
otherwise damaged or
missing
Health And Safety Deficiencies
Bathroom Items Bathroom Unit - Shower/Tub - - Shower or Tub (Unit)
missing overflow Damaged/Missing - The hardware is missing or
(Bathroom) (NLT) - L3 is not functioning
Electrical System Hallway Unit - GFI - Inoperable - GFI does not function when
gfci breaker not testing (Electrical System) (NLT) - self-test button is pressed
L3
Emergency/Fire Exits Bedroom HS - Emergency/Fire Exits - Emergency/Fire Exits
bed 3 bed blocking Blocked/Unusable (applies only on third or
window 2nd means (Emergency/Fire Exits) (LT) lower floors)
- L3 - Blocked
- Inoperable Window
Infestation Bedroom HS - Insects /roaches - Evidence of roaches
bed 2 (Infestation) (NLT) - L3 - Multiple live roaches
observed

Building 17 - 5715-101--310[Sample,Inspected] - Unit (b) (6)


Non-Health And Safety Deficiencies
Bathroom Items Bathroom Unit - Plumbing Leaking - Shower or Tub (Unit)
threads at head Faucet/Pipes (Bathroom) - - There is a leak

Report generation date/time: 08/22/2022 01:11 PM Score Version: 2 Page: 57 of 59


Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.
Inspection Summary Report (POA) for Inspection #713096

Item Location/Comments Deficiency/Severity Decisions


L1 - There is a leak or drip, but it
is contained by the shower
or tub basin
Bathroom Items Bathroom Unit - Lavatory Sink - - Bathroom Sink
missing Damaged/Missing - A stopper is missing (only if
(Bathroom) - L1 there is no stopper in the
visible area)
Doors Living Area Unit - Deteriorated/Missing - Entry Door to Unit
front entry Seals (Entry Only) (Doors) - Seals/caulking is missing or
- L3 deteriorated to the point the
door is not weather-resistant
(if designed to have seals)
Doors Bedroom Unit - Damaged Surface - All Other Doors (includes
bed 2 (Holes/Paint/Rust/Glass) closet or other interior
(Doors) - L3 doors)
- Surface is damaged
- Door has holes.
- Greater than 1 inch
- This condition DOES NOT
RESULT in a Health and
Safety concern.
Doors Bedroom Unit - Damaged Hardware/ - All Other Doors (includes
bed 2 Locks (Doors) - L2 closet or other interior
doors)
- Hardware is damaged or
missing
- Other interior door does not
function as it should or
cannot be locked.
Doors Bedroom Unit - Missing Door (Doors) - All Other Doors (includes
bed 1 - L1 closet or other interior
doors)
- Door is missing
- One door is missing
Walls Bedroom Unit - Damaged (Walls) - - Hole(s)
bed 1 behind door L1 - Between one square inch
and up to a sheet of paper,
but, you cannot see through
the hole
Walls Bedroom Unit - Damaged (Walls) - - Hole(s)

Report generation date/time: 08/22/2022 01:11 PM Score Version: 2 Page: 58 of 59


Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.
Inspection Summary Report (POA) for Inspection #713096

Item Location/Comments Deficiency/Severity Decisions


bed 2 L1 - Between one square inch
and up to a sheet of paper,
but, you cannot see through
the hole
Walls Bedroom Unit - Damaged (Walls) - - Hole(s)
bed 3 behind door L1 - Between one square inch
and up to a sheet of paper,
but, you cannot see through
the hole
Windows Bedroom Unit- Missing/Deteriorated - Caulking, Seals, or Glazing
bed 1 thermo seal Caulking/Seals/Glazing Compound (includes
Compound (Windows) - L3 thermopane or insulated
windows)
- Deteriorated or missing
- Window is damaged and not
weather-resistant OR there
is damage to the
surrounding structure OR
there is condensation or
discoloration between the
glass panes of a
Thermopane
Windows Living Area Unit - Inoperable/Not - Lock/Operability
right window Lockable (Windows) - L1 - Window cannot be opened
or will not stay open (If the
window is designed to do
so.)
- Window is on 3rd floor or
below
- There IS another operable
window in the same floor
area.
- This condition DOES NOT
RESULT in a Health and
Safety concern.
Health And Safety Deficiencies
Smoke Detector Bedroom Unit - Missing/Inoperable - Inoperable
not sounding bed 3 (Smoke Detector) (SD) - L3 - There is NOT another
functioning smoke detector
on same level.

Report generation date/time: 08/22/2022 01:11 PM Score Version: 2 Page: 59 of 59


Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.
Notice: Modifications to the Inspection Summary Report

With the rollout of the new Uniform Physical Condition Standards (UPCS) inspection software (version 4.0).
PIH-REAC now has the capability to collect more detailed information about observations made during the
inspection of properties. Therefore, the report has been modified to provide this detailed information, and also to
make the results of the inspection more clear. The following explains the major changes to the report.

Changes to Score Summary - The section of the report, which summarizes the score, has been modified
to better explain how the final score was derived for the property, and the source of lost points. Additionally,
score information from the two most recent inspections of the property is provided to allow comparison to
this inspection's score.

Addition of scored and non-scored deficiency reports - The section of the report that displays observed
deficiencies has been divided into two sections: the Score Report and the Deficiency Report. Non-scored
deficiencies refer to multiple deficiencies of the same type observed with the same sub-area, they are
reported for informational purposes only and are not scored. Only one deficiency of the same type for the
same sub-area is counted for scoring purposes.

Score Report - a detailed account of only the scored deficiencies by sub-area.

Deficiency Report - A detailed account of all deficiencies, both scored and non-scored, by sub-area.
In addition, standardized locations and more descriptive information for each deficiency are provided.

To read more about the above, and for additional assistance in understanding the report, you may access the
Inspection Summary Report Guide (version 4.0) at
http://www.hud.gov/offices/reac/products/pass/inspectionrpt40.cfm
PHYSICAL INSPECTION SUMMARY REPORT

The Inspection Summary Report is designed to achieve two objectives:

1. Provide the Public Housing Agency or owner and/or owner agent (POA) with the background information, i.e.
addresses, phone numbers, building names, etc., collected during the property inspection.

2. Provide the POA the results of the REAC physical inspection of a specific property.

The items below describe the information provided in the Inspection Summary Report.

Inspection Number : The inspection number is unique for each property inspection conducted by REAC. Each
time a property is inspected by REAC, a new inspection number is used. These unique numbers may be used to
communicate with REAC on any matter concerning a particular inspection.

Property Information : Information related to a property is provided:

- Property identification number (in parentheses) - a unique number in HUD databases


- Property name
- Status as scattered site (Yes/No)
- Relevant addresses, phone numbers, fax numbers, and e-mail addresses for the property

Each of these should be checked carefully for accuracy. All discrepancies should be reported to the REAC
Physical Inspection Operations Center at 1-877-406-9220.

Building Unit Count : The total number of buildings and units on the property are given, along with the number of
buildings and units actually inspected by REAC

Scores : An overall numerical score is given as a value from zero to 100. Separate numerical scores are also
given for each of five areas:

- site
- building exterior
- building systems
- common areas
- units

The five area scores range from zero to the maximum number of points possible for each area. The possible
points for a given area are determined for a specific property based on the inspectable items actually present in
each area. The sum of the area points identifies what the overall score would be if there were no health & safety
(H&S) deficiencies. The overall numerical score is then calculated by subtracting the sum of deductions for H&S
deficiencies from the sum of the individual "area points".

Examples of overall scores are: 95c; 67b*; 84a*; 100b; 78a; and 43c*. The asterisk(*) indicates that H&S
deficiencies were found with respect to smoke detectors. The lower-case letter indicates whether or not other
kinds of H&S deficiencies were observed, as follows:

- The letter "a" is given if no health and safety deficiencies were observed other than for smoke detectors.

- The lower-case letter "b" is given if one or more non-life threatening H&S deficiencies, but no exigent/fire safety
H&S deficiencies were observed other than for smoke detectors.

- The lower-case letter "c" is given if one or more exigent/ fire safety (calling for immediate attention or remedy)
H&S deficiencies were observed.

Although all H&S deficiencies, except for smoke detector problems and "other" hazards, affect the scores with
appropriate deductions, the letter grades are added to highlight the serious nature of H&S deficiencies, all of
which need to be addressed by the POA.

Health and Safety Counts: In addition to the counts of actual H&S deficiencies observed in the inspected
buildings and units, the estimated number of H&S deficiencies that would have been found had all buildings and
units been inspected is also given. This projected count gives a sense of the total H&S problem for the inspected
property. The projection is calculated by dividing the counts actually observed in buildings or units by the
proportion of buildings or units inspected. The percent of buildings and units inspected is additionally given to
show the basis for the calculations.

rd
Systemic Deficiencies: Defects observed in at least one third (1/3 ) of the inspected units or buildings are listed
by whether or not they are repairs generally requiring large cash outlays ("Capital" items) or generally requiring
smaller cash outlays ("Ordinary" items).

Participants & Buildings/Units: Information provided includes:

- relevant addresses, phone numbers, fax numbers, and e-mail addresses for participants

- name, year built, number of units and address for each building on the property. Note: All buildings on the
property should be listed.

As before, each of these should be checked carefully for accuracy and any discrepancies should be reported to
the REAC Technical Assistance Center (TAC) at 1-888-245-4860.

Inspectable Items: This portion of the report details all deficiencies found in the inspection. The main headings in
the first column refer to the inspectable area -- site, building exterior, building systems, common area, unit or
health & safety where the deficiency was observed. The entries are "inspectable items" within which the
deficiencies were found. Some items may not be present for a given property. In such cases, appropriate
adjustments are made in the points of each area. Items present, but with no deficiencies found, are not listed.
Inspectable items are:

Site: fencing & gates, grounds, mail boxes/project signs market appeal, parking lots/driveways/roads, play areas
and equipment, refuse disposal, retaining walls, storm drainage and walkways/stairs.

Building Exterior: doors, fire escapes, foundations, lighting, roofs, walls and windows.

Building Systems: domestic water, electrical system, elevators, emergency power, exhaust system, fire
protection, heating/ ventilation/ air-conditioning and sanitary system.

Common Areas: basement/garage/carport, closet/utility/mechanical, community room, day care,


halls/corridors/stairs, kitchen, laundry room, lobby, office, other community spaces, patio/porch/balcony, pools
and related structures, rest rooms/pool structures, storage and trash collection areas.

Unit: bathroom, call-for-aid, ceiling, doors, electrical system, floors, heating/ventilation/air-conditioning, hot water
heater, kitchen, laundry area (room), lighting, outlets/switches, patio/porch/balcony, smoke detectors, stairs,
walls and windows.

Health & Safety: air quality, electrical hazards, elevator, emergency/ fire exits, flammable materials, garbage and
debris, hazards, infestation.

Column labeled NO/OD:

NO: The inspection protocol requires the inspector to check for the existence of certificates for certain items such
as lead-based paint, elevators, etc. If the inspector verifies all the required certificates, the report will not include
any certificate information. If a certificate is not present, the first inspectable item listed will be "certificates" and
the designation "NO" will be listed for each unavailable certificate.

OD: If the inspector records a deficiency, then an OD in this column refers to the "observed deficiency" for the
given item.

Column labeled Observation: The column lists each specific deficiency observed within a given inspectable item.
Each deficiency has a definition, which specifies what must be observed for that deficiency to be recorded. Also
noted in this column are observations about Health & Safety items. These are:

- (LT) - Exigent/Fire Safety (calling for immediate attention or remedy)

- (NLT) - Non-Life Threatening

- (SD) - Smoke Detector

Definitions for all deficiencies are given in the physical inspection section at REAC's web site on the Internet
(www.hud.gov/reac/). Click on "Products" then "Physical Inspection" and then "Physical Inspection Definitions"

Column labeled Severity: Deficiencies differ by "severity". The definitions specify what must be recorded for a
given deficiency under one of three possible severity levels - level 1, level 2 and level 3. The severity level is
given on the report to indicate which part of the definition actually applies for the specific deficiency observed.
Severity levels are defined within a given deficiency and do not necessarily indicate which deficiencies are the
worst. For more serious deficiencies, a level 2 severity may be more of a problem and may reduce the overall
score more than less serious deficiencies with a severity of level 3.

Location/Comments: Comments are required for all severity level 3 deficiencies.

Column labeled Ded.: This column gives the points deducted from the overall property score for the observed
deficienies. In the shaded heading the possible points are given for that area and building or unit. Although the
listed points deducted may sum to more than the possible points, the total deducted from the overall property
score for that area and building or unit does not exceed its possible points. The listing of points deducted is
rounded to the nearest tenth of a point, so "<0.05" is listed when the points deducted is a very small fraction, but
greater than zero. Where there is a blank or zero, such as for lack of a certificate or observed smoke detector
problems, it means no points are deducted from the property score.
PROJECT OWNER'S CERTIFICATION THAT ALL EXIGENT
HEALTH AND SAFETY ITEMS HAVE BEEN CORRECTED
SEND OR FAX SIGNED COPY TO LOCAL MF OFFICE

[Name of Project Owner:] _________________________________________________________ (the "Project


Owner"), the owner of [Project Name:] ________________________________________________________,
[City:] __________________________, [State:] ________________ [Project Number:] _______________ (the
"Project") by and through its duly authorized representative identified below, hereby certifies that:

1. All Exigent Health and Safety ("EH&S") items at the Project have been corrected. Such EH&S items
include those identified in the Notification of Exigent and Fire Safety Hazards Observed, dated
________________.

2. The attached Report accurately identifies the repairs that have been made to correct the EH&S items,
the location of those repairs, and the date or dates the repairs were made. If repairs were not made,
the dangerous condition was eliminated.

This certification is made by the Project Owner and is signed by a duly authorized representative of the Project
Owner, who is so authorized by reason of his/her position as the [State Fully Relationship Between Signer of
Certification and Project Owner:] _______________________________________________________________
_________________________________________________________________________________________
_________________________________________________________________________________________.

All of the foregoing statements, as well as the date, signature and identifying information of the signer and the
Project Owner that follows, are HEREBY CERTIFIED as true and accurate this _______ day of
__________________, 20___.

Project Owner: _______________________________

By: Signature: _______________________________

Print Name: _______________________________

Title: _______________________________