INSTALLATION GUIDE

Actionair SmokeShield
V1-V2 Upgrade Kit
Contents Purpose
Purpose................................................................. 1 The Actionair V1-V2 kit (supplied as an installation kit or a
fixing kit (see page 2) allows on-site upgrades of Actionair
Applies to............................................................. 1 SmokeShield V1 (2013-2021) dampers to Actionair
Warranty............................................................... 1 SmokeShield V2 (2021-) specification.

Health and safety................................................ 1 This brings performance enhancements as outlined in the


Declaration of Performance (for both V1 and V2), which
Restrictor Template.............................................. 1 is available on the Swegon website.
Selection Matrix................................................... 2
Installation Method............................................. 2 Applies to...
Appendix.............................................................. 6 Actionair SmokeShield V1 (2013 - 2021) - identifiable by an
orange product sticker.
Inspection and hand over sheet......................... 7
Notes..................................................................... 8
Warranty
This upgrade kit does not affect the underlying product
warranty.

Health and safety


This process must be undertaken by competent persons.
More than one person may be required to ensure the safe
handling of large dampers and other materials. Use must
be made of access equipment to ensure unsafe practices
Restrictor template (to scale) As are not used to approach walls or difficult access areas.
C

provided in installation kit. Standard site PPE should be used (minimum steel toe cap
Drawing No:

boots, hard hat); together with any protective eyewear,


TBC

90.0
gloves and masks, when drilling or cutting is being under-
taken. If loud equipment is being used, hearing protection
+ 0.50 should be used. All waste materials should be collected
46.00 - 1.00
and disposed of as defined by the relevant supplier.
6
1 of 1
Sheet
13.6

Rev
1

Scan to see a video


installation guide
3.50

5
Third Angle
Projection

20.0
A
Actionair SmokeShield V1-V2 Kit Installation Guide

Selection Matrix
Damper type Number of Number of
blades restrictors
SmokeShield V1 (2013 - 2021) 2 0
For all installation methods excluding DWFX-F - all widths
SmokeShield V1 (2013 - 2021) 3 2
For all installation methods excluding DWFX-F - all widths
SmokeShield V1 (2013 - 2021) 4 -13 4
For all installation methods excluding DWFX-F - all widths
SmokeShield V1 (2013 - 2021) 2 0
For DWFX-F - widths over 500mm
SmokeShield V1 (2013 - 2021) 3 2
For DWFX-F - widths over 500mm
SmokeShield V1 (2013 - 2021) 4 -13 4
For DWFX-F - widths over 500mm
Please see appendix for more details and location
rules across Actionair SmokeShield V1 damper sizes
and models. To understand the performance impact
of the upgrade kit please refer to the Declaration of
Performance (DoP) on the Swegon website.
This guide details the installation method for Square/
Rectangular dampers. Note this procedure can be
performed to flat oval and circular dampers but
please note the reduced working area. Contact us at
actionair@swegon.com for more information.

Before you start Installation Method


First ensure that all the required equipment and materials 1. Isolate the existing actuator from any electrical supplies
are available before start. following local rules and regulations.
Installation Kit - One Required 2. Remove actuator from shroud by pressing the interface
• 1x 3.2mm drill bit locking pin and pulling the actuator at the same time.
This will allow the ability to move the blades freely
• 1x alignment jig
using an 8mm spanner on the drive pin inside the
• 1x transit plate shroud.
• Part number Note: the snaplock will only disengage and reengage
when the actuator is in the failsafe / closed position.

Fixing kit
• 4x Ø3.18mm steel rivet 18mm length (part no:
RSZN00541)
• 4x blade retaining profile (blade restrictor)
• 1 x product upgrade label
• Part number

Tools Needed
• 1x battery operated drill
• 1x hand rivet gun
• 1 x spanner

3. Clean damper from dust/debris to ensure blades remain


clear and free to operate.

2
Swegon reserves the right to alter specifications. 20210720 - L00011
Actionair SmokeShield V1-V2 Kit Installation Guide

4. Close blades before drilling and insert transit plate into 6. Begin to drill through both skins of the blade ensuring
shroud to lock blades into the close position. the drill is perpendicular to the tie bar/jig.

5. Start by positioning the jig over the tie bar ensuring


folded tabs are facing the fishtail on the blade
required this would be the second from top and
penultimate blade, please see appendix for more
detailed rules across damper sizes and models.

7. Remove transit plate from the shroud to enable the


Created using drawing template RAM-F-027 Issue E 12/16
4 3 2 1
All dimensions in mm. Do NOT scale from drawing. If in doubt ASK! blades to be opened.
A3
8. Position the Ø3.18mm steel rivet 18mm length (part
no:SouthRSZN00541) and version 2 restrictors through the
© Swegon Air Management Limited
Street, Whitstable, Kent CT5 3DU
blades. Tel: +44 (0)1227 276100
Email: actionair@swegon.com
D
www.swegon.com/uk

Sheet Metal Component Notes


Part No: folded jig
Material: 1.20 mm thick Steel
Finish:
Est Weight: 0.084 kg
Drawing limits (unless otherwise stated)
No Decimals: 1.00mm
One Decimal: 0.50mm
Two Decimals: 0.25mm
Three Decimals: 0.10mm
Angles: 2.0 degrees
Critical dims and features shown in red and enclosed in box

C
1.2

B
66.2

3
20210720 - L00011 Swegon reserves the right to alter specifications.

ED
Rev: Comments: By: Date:
Drawn By: Malcolm.Kimberley Date: 14/04/2021
Checked By: Date:
Actionair SmokeShield V1-V2 Kit Installation Guide

9. Using a hand rivet gun pull the rivets to fasten the 11. Place the upgrade label...
restrictors to the blade. If the dampers are not connected to the ductwork:
• Remove the orange CE label that is fitted on the inside
of the damper spigot on the access side (side where
the actuator goes).
• Thoroughly clean the area where the old product label
was fitted.
• Stick one new green product label in the area that has
been cleaned ensuring that the label is stuck properly,
and there are no trapped air bubbles.
If ductwork is connected to the damper:
• Find a suitable position on the damper flange on the
same side of the actuator.
• If there is nowhere available on the actuator side of the
damper then it is acceptable to apply the sticker to the
opposite side.
• Ensure that the area is clear from fixings, and any over-
10. Ensure the rivets have been pulled correctly, and the spill of plaster or fire stopping compound.
mandrel’s have been disposed of.
• Clean the area in questions to ensure that there is no
residual oils on the flange.
• Stick one new green product label on the inside of the
spigot and across the shroud, in the area that has been
cleaned, ensuring that the label is stuck properly, and
there are no trapped air bubbles.

4
Swegon reserves the right to alter specifications. 20210720 - L00011
Actionair SmokeShield V1-V2 Kit Installation Guide

12. Ensure the blades are shut to enable the Actuator to


be re inserted by pressing the interface locking pin into
the shroud.

13. Turn actuator back onto electrical supplies following


local rules and regulations. Check damper is fully
operational.
14. Complete recommissioning sheet and collect photo-
graphic evidence.
15. Email completed damper photos and completed
recommissioning sheets to actionair@swegon.com.

5
20210720 - L00011 Swegon reserves the right to alter specifications.
Actionair SmokeShield V1-V2 Kit Installation Guide

Appendix Created using drawing template RAM-F-027 Issue E 12/16

6 5 4 3 2 1
Drawing No: Sheet Rev Third Angle
- A3 All dimensions in mm. Do NOT scale from drawing. If in doubt ASK!
1 of 1 1 Projection
All Non Flanged Variants for Smoke Shield V2
Drawing © Swegon Air Management Limited
Description CE Marking South Street, Whitstable, Kent CT5 3DU
Number
D Tel: +44 (0)1227 276100 D
DWFX-C DWFX-C CE Email: actionair@swegon.com
AAF8008 Z-Frame NON-CE www.swegon.com/uk
AAF8018S1 Install Frame Plint on Slab CE
AAF10700 I/F in Floor CE
AAF10702 I/F in Wall CE
AAF10708 DWFX-C Dry Wall CE
AAF10714 Sleeve Angle - Dry Wall CE
AAF10716 Sleeve Angle - Masonry Wall CE
AAF10724 Sleeve & Angle + Batt Horizontal CE
AAF10727 Sleeve & Angle Horizontal NON-CE
AAF10730 Up Against Slab Cleat CE
AAF10950 T&B Angles & 'Z' Frame CE
AAF12368 Compound Seal NON-CE
AAF12452 IF Inverted End Cap (68mm) CE
AAF12453 DWFX-C Inverted End Cap (50mm) CE
C C
AAF12455 IF Inverted End Cap (43mm) CE
AAF12456 DWFX-C Inverted Damper & End Cap (50mm) CE
AAF6021 Fire Curtain NON-CE

2 BLADES 3 BLADES 4 - 13 BLADES


NBDW 200 - 1000 MM NBDW 200 - 1000 MM NBDW 200 - 1000 MM
NBDH 200 - 207 MM

NBDH 208 - 282 MM

NBDH 283 - 1000 MM


B B

Tie bar with no blade restrictors


Tie bar with 2 blade restrictors (1 each side)
2nd blade only Rev: Comments: By: Date:
Tie bar with 4 blade restrictors (2 each side) Restrictor position as
2nd & penultimate blade only defined by SA006
Drawn By: Andrew Illidge Date: 05/07/2021

Restrictors as per C00182 Checked By: Date:


Approved By: Date:
Product: SmokeShield
Client: SAML
Project: -
A A
Description:
Production Build Drawing for New Blade
Restrictors - Non Flanged Variants
Drawing No: Sheet Rev
AA-PTC-6002 1 of 1 1
6 5 4 3 2 1
The information disclosed herein was originated by and is the property of Swegon Air Management Limited (SAML). SAML reserves all patent, proprietary,design, use, sale, manufacturing and reproduction rights thereto. This does not apply to any vendor parts.

Created using drawing template RAM-F-027 Issue E 12/16


6 5 4 3 2 1
Drawing No: Sheet Rev Third Angle
- A3 All dimensions in mm. Do NOT scale from drawing. If in doubt ASK!
1 of 1 1 Projection
Flanged Variants for Smoke Shield V2
Drawing © Swegon Air Management Limited
Description CE Marking South Street, Whitstable, Kent CT5 3DU
Number
D Tel: +44 (0)1227 276100 D
DWFX-F DWFX-F CE Email: actionair@swegon.com
AAF10704 DWFX-F Dry Wall CE www.swegon.com/uk
AAF10706 Flange Masonry Wall CE
AAF10710 Smoke Shield + DWFX-F & Ablative Batt - Dry Wall CE
AAF11945 DWFX-3F CE
AAF12394 DWFX-3F CE
AAF12454 DWFX-F Inverted End Cap (50mm) CE
AAF12457 DWFX-F Inverted Damper & End Cap (25mm) CE
AAF12493 DWFX-F With Pattress in Masonry Wall CE
AAF13069 DWFX-F Option 2 - No Drop Rods CE

C C

2 BLADES 3 BLADES 4 - 13 BLADES


NBDW 501 - 1000 MM NBDW 501 - 1000 MM NBDW 501 - 1000 MM
NBDH 200 - 207 MM

NBDH 208 - 282 MM

NBDH 283 - 1000 MM

B B

Tie bar with no blade restrictors


Tie bar with 2 blade restrictors (1 each side)
2nd blade only
Tie bar with 4 blade restrictors (2 each side) Restrictor position as
2nd & penultimate blade only defined by SA006
Restrictors as per C00182

Rev: Comments: By: Date:


Drawn By: Andrew Illidge Date: 05/07/2021

ALL FLANGED DAMPERS 200 - 500 MM NBDW TO HAVE NO TIE BARS & NO RESTRICTORS Checked By: Date:
Approved By: Date:
Product: SmokeShield
Client: SAML
Project: -
A A
Description:
Production Build Drawing for New Blade
Restrictors - Flanged Variants
Drawing No: Sheet Rev
AA-PTC-6001 1 of 1 1
6 5 4 3 2 1
The information disclosed herein was originated by and is the property of Swegon Air Management Limited (SAML). SAML reserves all patent, proprietary,design, use, sale, manufacturing and reproduction rights thereto. This does not apply to any vendor parts.

6
Swegon reserves the right to alter specifications. 20210720 - L00011
Actionair SmokeShield V1-V2 Kit Installation Guide

Retrofit re-commissioning sheet


Based on DW145
This certificate applies only to Swegon Fire Dampers. The installer must complete this installation certificate when
installing fire and smoke dampers. A separate certificate must be completed for each individual fire and smoke damper.

Question Action
1 Are the dampers the correct type? Confirm damper is correct type for the application
2 Are the dampers located correctly? The damper location is to be checked against the installation
drawings/details
3 Are the dampers correctly identified? Unique system ID to be clearly indicated on the damper or
other agreed location.
4 Have supports for both the damper and the adjacent
ductwork been installed in accordance with the appro-
ved manner?
5 Are the dampers fitted in the correct orientation? Confirm the damper is installed with any actuators (if app-
licable) on the left or right hand side. Not on the top or the
bottom (i.e. blade pivot running vertically).
6 Is access through the ductwork, to the damper unob- Unobstructed space should be provided for safe access to the
structed? damper. This must include access through ceiling voids and ad-
jacent services. Damper installer to advise the system designer
if problems are foreseen.
7 Has the space around the damper and within the Other services within the installation opening will invalidate
opening been left clear and not been used for other the installation method. Damper installer to advise the lead
services? contractor if problems are foreseen.
8 Using the access opening provided, check that blades Check position of damper blades.
open and close.
9 Has the damper been checked for internal cleanliness, With the damper in the closed position, inspect for damage.
free from damage and that vertical casings in particular
are free from debris?
10 Has the damper been released to simulate operation of Ensure damper operation is free from interference.
the thermal release? (Damper drop test)
11 Have the damper blades been re-set following drop After re-setting the damper, check the position shown on the
test and the access panel replaced? blade position indicator is correct.
12 At the time of damper handover, is the fire barrier and Damper installer to record on the handover register if
penetration seal complete? any following trades are still to complete their activities.
13 Is the damper installation complete and available for Obtain the relevant acceptance of the damper installation from
handover prior to system commissioning? the CDM coordinator.
14 Is the completed handover register cross-referenced
back to the identification codes listed in the system
designers damper schedule?

Damper Unique System I.D: ..........................................................................................................................................................................................


Upgrade Kit Serial number: ...........................................................................................................................................................................................
Name of installation location:........................................................................................................................................................................................
Address:..................................................................................................................................................................................................................................
Installation location identification section/floor/room: ......................................................................................................................................
Damper product type: .....................................................................................................................................................................................................
Release fuse temperature: .............................................................................................................................................................................................
Notes/Considerations: .....................................................................................................................................................................................................
Installed by: .........................................................................................................................................................................................................................
Company Name: ................................................................................................................................................................................................................
Address: ................................................................................................................................................................................................................................
Company Telephone No: ................................................................................................................................................................................................
Installers Name: ..................................................................................................................................................................................................................
Installers Telephone No: .................................................................................................................................................................................................
Date of installation: ..........................................................................................................................................................................................................
It is hereby verified that the damper detailed above has been installed and tested according to the manufactures
recommendations:
Installers signature: ................................................................................................ Date: ................................................

7
20210720 - L00011 Swegon reserves the right to alter specifications.