Professional Documents
Culture Documents
LOAD CALCULATION
TESTING AND
MAINTENANCE
E NG R . ME R VIN C. E D NI LAO
I I E E -SCC 2022 VP - T ECHNICAL
Industrial Motor Load Calculation
• Branch Circuit Conductors
• Motor and Branch Circuit Overload Protection
• Branch Short Circuit-Circuit and Ground Fault Protection
• Feeder Conductors
• Feeder Short Circuit Protection
• Motor Equipment Grounding Conductors
Industrial Motor Testing (Electrical)
• Winding Resistance Test
• Insulation Resistance Test
• Polarization Index Test
• Winding Surge Test
• No Load Test
Industrial Motor Testing (Mechanical)
• Total Run Out Check
• Rotational Speed and Rotation Facing Drive End
• Vibration Analysis
• Bearing and Motor Temperature
Industrial Motor Maintenance
• General Inspection
• Temperature Monitoring of bearing and windings
• Vibration
• Oil Analysis
• Running Current
• Insulation Resistance
• Polarization Index
• Winding Resistance
Advantages of AC Induction Motor
• Variety of Model
• Simple Design
• Low Cost
• Less Noise and Vibration
Who invented
the induction
motor?
AC Induction Motor
SQUIR R EL CAG E MOTO R S WO U ND R OTO R MOTO R S
Industrial Motor Load
Calculation
Industrial Motor Load Calculation
TA B L E VA L U E S NA ME P LAT E VA L U E S
Table 4.30.14.1 Full Load Current in
Amperes, DC motors (p. 370)
Table 4.30.14.2 Full Load Current in
Amperes, Single Phase Alternating
Current Motors(p. 370)
Table 4.30.14.1 Full Load Current ,Two
Phase Alternating Current Motor : 4
wire (p. 371)
TA B L E VA L U E S NA ME P LAT E VA L U E S
4.30.2.2. Single Motor. Conductors that
supply a single motor used in a
continuous duty application shall have
an ampacity of not less than 125% of
the motor full-load current rating
based on table values.
Industrial Motor
Testing (Electrical)
Insulation Resistance Test and
Polarization Index Test
Temperature Correction Factor for insulation
resistance tests taken at temperature other
that 40 deg. C – IEEE43
Industrial Motor
Testing (Electrical)
Insulation Resistance Test and
Polarization Index Test
Recommended minimum values of polarization
index for all machine components insulation
classes per IEC 60085-01: 1984
Industrial Motor
Testing (Electrical)
Insulation Resistance Test and
Polarization Index Test
NOTE—If the 1 min insulation resistance is above
5000 MΩ, the calculated P.I. may not be
meaningful. (IEEE 43)
Applicability of polarization index when IR1 is
greater than 5000 MΩ
When the insulation resistance reading
obtained after the voltage has been applied
for 1 min (IR1) is higher than 5000 MΩ, based
on the magnitude of applied direct voltage,
the total measured current (IT) can be in the
submicroampere range.
Industrial Motor Because of these phenomena, when the IR1 is
Testing (Electrical) higher than 5000 MΩ, the P.I. may or may not
Insulation Resistance Test and
be an indication of the insulation condition
Polarization Index Test and is therefore not recommended as an
assessment tool
Applicability of polarization index when IR1 is
greater than 5000 MΩ
Example: 100HP, 3 ph, 440 induction motor.
Polarization Index Test:
Instrument Used: Baker DX Megger
Applied Voltage: 500V
Industrial Motor Result in 1 minute: 5.12Gigaohms
Testing (Electrical) Result in 10 minutes: 5.18 Gigaohms
Insulation Resistance Test and
Polarization Index Test PI= 5.12/5.18
PI= 1.01 ????? Less than min. value of 2.0
High-potential tests are tests that
consist of the application of a voltage
higher than the rated voltage for a
specified time for the purpose of
determining the adequacy against
breakdown of insulating materials and
spacings under normal conditions
(IEEE 112)
Industrial Motor
Testing (Electrical)
Winding Surge Test
• Typical waveforms expected in the Surge
test
Industrial Motor
Testing (Electrical)
Winding Surge Test
If there is no separation between the two
wave forms indicates good winding.
• Current, applied voltages, and frequency (AC) are
recorded during no load testing
Example: 100HP, 3 ph, 440V induction motor.
No load test:
Instrument Use: Fluke Multitester
L1-L2 Voltage: 447 V, L1 Current=45.8A
L2-L2 Voltage: 460 V, L2 Current=67.7A
Industrial Motor L1-L2 Voltage: 449 V, L3 Current=60.9A
Testing (Electrical) Voltage Unbalance: 1.77%
No Load Test Current Unbalance : 21.2% Failed
For 1-2% voltage unbalance we can expect about
5% current unbalance.
• Current, applied voltages, and frequency
(AC) are recorded during no load testing
Example: 100HP, 3 ph, 440V induction motor.
No load test:
Instrument Use: Fluke Multitester
L1-L2 Voltage: 447 V, L1 Current=45.8A
Industrial Motor L2-L2 Voltage: 460 V, L2 Current=67.7A
Testing (Electrical) L1-L2 Voltage: 449 V, L3 Current=60.9A
No Load Test
Industrial Motor Testing
(Mechanical)
100HP, 3 ph, 440V induction motor.
Instrument Use: SKF Laser Tachometer Set
TMRT-1
Result
Speed Drawn: 1804 rpm
Rotation: Clockwise
Industrial Motor % slip = (1800-1804)/1800= 0.2% PASSED
Testing (Mechanical) Standard: +/- 20% of rated slip rpm as per
Rotational Speed and Rotation NEMA MGI
Facing Drive End
100HP, 3 ph, 440V induction motor
Instrument Use: IRD Vibration Analyzer and
Balance Kit 258
Result @ Non Drive End
Vertical : 0.50 mm/s - GOOD
Horizontal : 0.60 mm/s -GOOD
Industrial Motor Axial: 0.90 mm/s -GOOD
Testing (Mechanical) PASSED!
Vibration Analysis
Standard: 3.8 mm/s for motor 1200 rpm above
and resiliently mounted as per NEMA MG1
1. Bearing Housing Diametral Reading
a. Drive End Bearing Housing
b. Non Drive End Bearing Housing
2. Bearing Journal Diametral Reading
a. Drive End Bearing Housing
b. Non Drive End Bearing Housing
Industrial Motor
Maintenance
Recommended Maintenance
Practices and Frequencies
6.2 Insulation resistance(IR) every 24 months <
600 Volt motors (Installed and Offline)
a. Perform IR check between motor leads and
ground. This determines condition of the
ground insulation. Record, temperature
correct and trend.
7.1 Polarization index (PI)) every 12 months >
600 Volt motors (Installed and Offline)
Industrial Motor a. Ratio of the 10 minute IR to the 1 minute
IR.(10 min IR / 1 min IR)
Maintenance
Recommended Maintenance b. Determines condition of ground insulation.
Practices and Frequencies
Test voltages similar to the IR test voltages.
Acceptance criteria ratio > 2
7.2 Polarization index (PI)) every 24 months < 600
Volt motors (Installed and Offline)
a. Ratio of the 10 minute IR to the 1 minute IR.(10
min IR / 1 min IR)
b. Determines condition of ground insulation.
Test voltages similar to the IR test voltages.
Acceptance criteria ratio > 2
8.1 Winding resistance every 12 months > 600 Volt
motors (Installed and Offline)
Industrial Motor A comparison of the line to line resistances of the
Maintenance motor’s winding. This test should be done at the
motor terminals using a meter capable
Recommended Maintenance of measuring low resistance (milliohms). A typical
Practices and Frequencies ohm meter does not have adequate
accuracy. Record, temperate correct and trend.
Each phase should be within +/- (3% - 5%) of the
average of all three phase.
8.2 Winding resistance every 24 months < 600
Volt motors (Installed and Offline)
A comparison of the line to line resistances of
the motor’s winding. This test should be done
at the motor terminals using a meter capable
of measuring low resistance (milliohms). A
typical ohm meter does not have adequate
accuracy. Record, temperate correct and trend.
Industrial Motor Each phase should be within +/- (3% - 5%) of
the average of all three phase.
Maintenance
Recommended Maintenance
Practices and Frequencies
9. Shaft total indicated run out(TIR) every 60
months (Overhaul)
Measure the trueness of the shaft extension.
A high value can cause vibration issues.
Acceptance criteria:
3600 rpm max .001 in
Industrial Motor < 3600 rpm max .003 in
Maintenance
Recommended Maintenance
Practices and Frequencies
10. Inspection and measurements of bearing
journals and housing fits every 60 months
(Overhaul)
Diameters of the fits should be measured and co
mpared to bearing industry standards. Brg
journals and housing bores should be visually
inspected for finish, pitting, rubbing and
corrosion.
11. Stator visual Inspection every 60 months
(Overhaul)
Industrial Motor
Inspection should look for:
Maintenance
Recommended Maintenance coil movement, plugged vent holes, soft or
Practices and Frequencies degraded insulation, coil bracing adequate and
intact, lamination damage, partial discharge
activity and tightness of wedges
12. Rotor / Shaft visual Inspection every 60
months (Overhaul)
Inspection should look for:
a. cracks in rotor bars
b. balance weights properly secured
c. signs of bar movement