Professional Documents
Culture Documents
In preparation of Job Execution PLul, die following basic design u<i.u must be identified.
1.1 Codes and Standard (Refer to Code and Standard for Instrumentation)
1.2 Units
1,3 Materials
(1) Codes and standard and possibility to use equivalent materials of other standards.
(3) Materials used for protection against environmental conditions or process nature.
Page 2 of 29
2, DESIGN OF INSTRUMENTS
2,1,1 Thermo-well
(I) Material
For general service Type 304 ar Type 316 stainless steel
for high temperature service Type 310, Type 446, Ceramics, etc,
for corrosive services cansuit with process licenser- manufacturer
(2) Construction
Drilled bar sleek or Pipe with welded end
Tapered or straight
Flanged Of threaded
(3) Installation
Insertion length : distance from free end of well to attachment to a
vessel or pipe
The free end of well will normally be located in Hie center third of the pipe.
However, for practical reasons, well length may be classified in lo several types (i.e.
250mm for pipe and 500 nun for vessel).
For fire box installation , lhe tip should be located approximately 3 inches inside the
tube wall.
Tube surface temperature measurement requires proper shield from furnace radiation,
minimum gap between tube and tip. and reducing mass- at the point of measurement,
(added mass may result temperature different from that of relatively cool tube wall)
If well is. installed at an angle or in an elbow, the tip should point toward lhe flow in
pipe.
(4) Thermo-well shall be so designed that wake frequency (Fw) in normal operation shall
be lower tturn 80% of natural frequency (Fn).
The following is calculation of Fw and Fn, Also refer to ASME PTC 19 3-1974
Fw = St * V / D
St Strouhal number(0.22 at red range of 104 to
10')
D Diameter of well tip in cm
V Fluid velocity in cm/sec
Page 3 of 29
A Sectional area of well lip in cm2
L Well Length In cm
C-0.719+ L069Ll/L+(0-l 4^2.24 (0.5-L1/L) )
(1) Construction
Magnesium insulated metal sheathed assembly
Grounded or isolated hot junction
Iron wire may be provided with anti-corrosion treatment, litis must be removed before
connection.
{1) RTD provides more accurate measurement than is possible with thermocouples,
Accordingly, RTD is used in installation where there greater accuracy is warranted or
narrow measuring range is required.
(3) Ordinary copper 3-wire extension cable is used to compensate fur resistance and
temperature change in the lead wire.
Page 4 of 29
2-1.4 Bimetal type or filled type dial thermometers with thcrmo-weli will be used tor local
temperature indication.
2,[,5 Filled type thermometers with thermo-well may be used as locally mounted
temperature controller or local temperature indicator, with Extended capillary hwtwre
necessary.
2-1-6 Field mounted temperature transmitters may be used instead of thermocouples and
RTD. Field mounted tempera! are transmitters have limitations with regard to ambienl
temperature, accessibility, vibration, electro - magnetic interference and grounding-
Ihc transmitters separately mounted from ihermo-wel] gives greater advantages in
overcoming these difficulties.
v 11 + Pl /r = v2z/2g+P2/r where rl - r2 ” r. ZI = Z2
Pagei of 29
= K'Xp2LP(^ P/rj’/z K t Constant
In case of gfss>
Q KaLp“eD3(^ P/rJ’/a c : Gas expansion
factor
(1) Type
Orifice concentric, eccentric or segmental
Sharp edge (square edge) or quadrant
Flow nozzle for higher velocity and better pressure recovery than orifice,
Venturi for high capacity and good pressure recovery or fluid
contains solids.
Pitot tube for high volume flow with no appreciable pressure drop can
be tolerated. Example: cooling water, flue gas, air duct.
Annubur is one of the averaging pressure type Pitot tube.
Page 6 of 2.9
Vena Contracts Taps 2 to ] 6 I - ’/T' available in L. K. Spink
Pipe Taps (2JZ2EMJD) 2 to 30
Check tap location for radius taps and vena cofllratta tap* because they may fall
in an undesirable location in the flange bub or weld line depend on size and
pressure ruling,
(61 Eccentric or segmental orifices may be used tor horizontal piping in rase fluid
contains large quantity of undissolved gjas or gas containing condensable.
Segmental orifices are recommended for slurry services,
For sizing refer to ASMIL but size available is from 4 to 14 inches with flange and
vena contracts taps.
{7} Quadrant edge orifice is used for viscous stream or for line Reynolds number range
from lOOnOOO down to 3000 to 5000 depending on beta ratio
(square edge orifice coefficient correction factors are available for Reynolds number
down tu approximately 25.000)
(8) Orifice may be provided with a weep hole to prevent buildup of condensate or vapor
in horizontal lines.
The terms variable - area meter is derived from principle that internal area of flowing
Lube is variable while differential pressure is constant across the float.
Magnetic flow meters are used on conductive viscous or slurry streams that have
required measure of electrical conductivity (approx, more than 5 p. Stem).
(NOTE : most petroleum hydrocarbons have insufficient conductivity.)
2.2.5
Page 7 of 29
2,2.6 displacement meters
Vortex meler is used for steam water, light hydrocarbons and any gases where large
turndown is required.
Size up to 12 inches.
Accuracy is typically 1%.
Note : Depending on the required turndown, the selected meter size may result in
significant pressure loss al normal flow because of increasing Reynolds number at
minimum flow,
Confirm allowable system pressure loss when selecting meter size.
Page 8 of 29
(2) Gas - Critical Flow,
W - Cd2PI (Mw/ZT)W Pl : IJp-stream Pressure in kgfomZA
Mw: Molecular weight
T : Up steam temperature in K
23 Pressure Instruments
2.3.3 AccesMiries
(1) Siphon : steam service
hot condensable vapors
(2) Pulsation Dampener : pu Isating servicc such as discharge of reci prorating pump
Note : Pressure gauge with liquid-filled cases is also considered for this applications.
Note t Diaphragm seals with or without capillary is also used to minimize heat
tracing
or for vibration free installation.
Consult with vendor where diaphragm seals are applied to vacuum service.
23.5 Range
23.6 Type of element
(1) Mechanical Liquid column
Dead weight
EiasLic raaltr ial
2.4.2 Connection
Level instrument connection must be from the vessel.
Instruments shall be located SO that the midrange position of tile Instnniienl enmes to
the normal liquid level.
NOTE : Improper assembly of the gauge glasses may result in glass failure or
leakage, cluse coordination in design and field fabrication between instrument and
piping is mandatory requirement.
(2) Transparent type gauge glasses: for acid, caustic, dirty liquid, steam, interface service
(4) Magnetic - type gauge : is popular especially for toxic, flammable liquid
(5) Transparent or reflex type gauge glasses with large chamber are often used for the
services which may boil or tend in surge in the gauge glass.
Page Id of 29
(7) Gauge glass pcutetlion agautst etch ing
Mica sheer Teflon and Kel - F should be provided with glass (o prevent etching of
glass by sietUH, hydrofluoric acid amines, caustic file.
NOTE : Such shield can not be applied to reflex type due to construction.
2.4.8 Nuclear
This means is used where other type of instruments can not be used> such as vacuum
tower, catalyst level, etc.
2.4.9 Ultra-sunk
Ultra-sonic type works on the principle of measurement of the time required for
sound waves to travel through space, and suitable for difficult level measurement
applications of liquids and solids.
Accuracy may be affected by variations of pressure, temperalure, relative humidity,
concentration of gases and vapors, as they affect sound velocity.
2.4.10 Capacitance
Capacitance type measures the changing electrical capacitance between probe and
vessel (when vessel is made of electrical conductor). If (he material being measured
is an elec trical conductor, insulated pTobe is used.
This instrument is suitable for level measurement applications of liquids, powders, and
solids.
Accuracy may be affected by variations of temperature and relative humidity, because
thev may affect dielectric constant.
When Float - and - cable lank gauges are used for custody transfer or maximum
accuracy is required, installation should be :
Provide stilling well to avoid turbulence.
Servo-balanced floal to reduce immersion and hysteresis errors.
Mean temperature measurement of the liquid.
Paae 12 of 29
2.5 Control Valves
2.5J Types
(1) Globe body valve (the valves which have globular shaped cavity around port]
Double seat : higher leakage rale than single scat valve but reduces
required actuator force due tn balancing feature of
plus.
design.
Angle valve : for high pressure services- Usually single port type
only.
(2} Butterfly valve : for high capacity and low pressure drop services.
Conventional discs provide throttling conLrol for up
to <iQ degree disc rotation.
(4) Eccentric spherical plug valve. Usually less costly than conventional globe valves
and adaptable to ordinary control requirements.
(2) Rating
Pressure-temperature rating must be compatible with the system in which the valve is
employed. In smaller sizes. It is often more economical to standardize on a minimum
rating such as class 300 #
Page 13 of 29
2.5.3 Materials
Body, bonnrf : Carbon steel
Chrome-moiy steel
Type 304 or 316 stainless steel
1.5.4 Packing
(1) Teflon (solid molded, braided. Chevron ring}:
Packing lubrication is no! required and good resistance !o most known
chemicals. Requires smooth stem finish (easy to leak if stem ar packing
surface is damaged). Recommended temperature range from -4Q deg. C io
230 deg- C.
(4) Graphite:
Packing lubrication is hot required.
Suitable lor high temperature serv ices.
Note : (Packing lubrication ( Silicon Grease) is provided for reduction of friction and
improvement of sealing.
For higher temperature, care should be taken that rhe lubricant may oxide and cause a
problem in obtaining a tight packing seal.
Packing should not be lubricated for the valve in oxygen service.
Class II 05% of rated capacity. Test medium is 3.5 bar air or water
Class HI 0.1 % of rated capacity Tesl medium is 3.5 bar air or water
Class IV 0.01 % of rated capacity Test medium is 3-5 bar air or water
Page 14 cif 29
valve crave] with a fairly linear relationship, and
lesser flow
increase as the plug opens further,
(normally not used for throttling service)
225.7 Sizing
(1) Valve Capacity Coefficient (Cv)
Cv is the number of gallons per minutes of water at 60 " F (15 UC) that will pass
through a given flow restriction with a pressure drop of 1 psi.
hl for Gas
CV = V (Mw T / P(P J +-P2 ))16 /1460 PO. 5 P]
Page 15 of 29
Reynolds Number ; For low Reynolds number applications such as viscous or small
flow, the bask sizing equation can not be used without correc1ionK
since the equation is based on Lhe turbulence flow.
Correction factor will be available from lhe manufacturer.
Usually the corrections can be ignored, (when Reynolds number is
greater than 4000, the correction will be 10% or less.)
Pressure recovery: As flow pzissrs through the restriction, there is a contraction of the
flow stream. The minimum cross-sectional area of the contraction
is called the vena contacts.
At the vena contracta, the velocity is maximum and pressure is
minimum. Further down stream, as the fluid stream expands in to a
large area velocity decreases and pressure increases. This
phenomena is called pressure recovery .
As a general, globe valves have lower pressure recovery than ball
or butterfly valves.
Choked flow ■ When die pressure at vena contracts drops below the vapor pressure
of the liquid), bubbles Will form in the Stream. The formation of (he
hubbies causes a crowding condition at lhe vena contracta which
tends to restrict flow, and further increase in pressure drop will not
produce increase in flow. This is called u Clicked flow”.
fin case of gas, choked flow means outlet velocity reaches sonic
velocity.)
The limiting pressure difference Pt (delta P) is called "
Maximum allowable differential pressure tor sizing*' and
determined by following
Cavitation: When the pressure at vena conUacla drops below the vapor pressure
of the liquid , bubbles will form in the stream. And if downstream
pressure recovery is sufficient to raise the outlet pressure above die
vapor pressure of the liquid, the bubbles collapse and produce
cavitation.
To prevent cavitation, the valve with low-pressure recovery should
be used And in some cases special component or mulii stage
pressure reduction should be considered.
Flashing. When the pressure at vena contracla drops below the vapor
pressure of the liquid, bubbles will form in the stream. And if the
pressure at valve ouLlet remains below the vapor pressure of the
liquid, (he bubbles remain in lhe downstream, and this process is
sajd as “"flashing".
To determine proper valve size, required Cv is sum of that tor
liquid ptiase and vapor phase separately calculated, in order to do
so, ptTccnLage of flashed vapor is required.
Liquid
V = Q/(0-0036. Jt <j2/4) Q : Flow in m3/h
d : valve diameter In mm
V : Flow velocity in m/sec
Gas. a nd Steam
By following formula. Lire diameter tn which fluid velocity reaches sonic
velocity is obiained. Therefore, the valve must be larger than the Hd-
For Gai
d=1.2 (QGfH/P2)£
d = 0.07 (Q T GfH/P2}& in case 1> 70 °C
For Steam
d=50(W/P2)1d
d : Diameter in mm
Q : Gas flow in NmB/h
Gf : Specific gravity at operating temp
P2 Outlet pressure in kg/cml as.
T : Operating teni pcrature in0 K
W z Steam flow in r.-Ti
1.5.8 Noise
(1) Source of noise
a) Mechanical vibration
b) Caviiaiion
c) Aerodynamic noise : Xoise resulting from turbulent flow of gases
17 of 29
(2) Noise reduction
a) Acoustic insulation
b) Use low-noise trim
c) In-line mufflers
d} Several valves Of valves and orifices in series
(2) Type
a) Spring d iaphragjn actuators
b) Piston actuators (Spring relumed or Double acting)
c) Motor actuators
(3) Nates
a) Maximum air pressure for actua<OT design should not exceed 4 kg/cm2g.
b) Unless maximum differential pressure at control valve is given in process
data, use maximum upstream pressure for determination of the thrust
required,
2.5. UJ Accessories
(1 j Extension bonnet
A bonnet with an extension between the packing box and bonnet flange.
For temperature exceeding 200X7 an extension bonnet containing sufficient area tn
provide radiating heat loss may be used.
A similar bonnet design is employed on low temperature application,. GX7 and below.
In no case should such a bonnet be covered with insulation materials.
(3) Positioners
Functions of positioners
a) Provide split range control
b) Reverse the valve action without changing the fail safe action
c) Improve response
d) Improve the resolution or sensitivity
2.6.1 General
The safety valves must comply with the technical regulations in accordance with the
applicable codes and standards.
2.6.2 Type
Direct spring loaded : Conventional type
Balanced safety relief valve
Pitol operated type
Page IS of 29-
Balanced safety relief valve should he used when back pressure is variable or built-up
back pressure exceeds 10% of (he set pressure,
Pilot operated type Ls lmJ where live operating pressure is clew to set pressure or
influence of back pressure is to be eliminated.
Pilot operated type should not be used for dirty, viscous sendees.
2.6,4 Notes
(1) Depending on the regulation, pilot operated valves can not be used without
combination of the spring loaded safety valves.
(2) Set pressure must be equal or less than the maximum allowable working pressure of
the equipment.
CAUTION : above figures arc reference only, see Codes and Standard tor detail.
{41 In case of multiple valve arrangement, set pressure and accumulation of the first valve
shall be as per above (2} and (3)„ and Lhose of (he supplemental valves may he over
such limitation. Detailed are referred to applicable Codes and Standards.
(5) If rupture disk is installed at safety valve inlet consider the dc-rating factor (0.9 by
API)
(6) Blowdown is usually more than 5% of set pressure and re-scaling pressure must be
higher than the operating pressure, Thus it is recommended safety valves be set al a
minimum of 10% above the operating, pressure.
(7) Where a conventional safety valve is used in service against constant buck pressure,
the set pressure minus constant back pressure shall te used for spring set pressure.
(S) To compensate reduction of set pressure due to effect of service temperature on the
spring and expansion of body bonnet, set pressure increasing factor must be
considered when the valves are tested at ambient conditions,
2.6.5 Piping; for Safety Valves
(1) The pressure loss in the inlet line must be less than 3% of the set pressure
(2) Cross sectional area of inlet pipe shall be always larger than the safety valve inlet
flange. This must be ensured where calculated pipe (not scheduled pipe) is employed
for inlet pipe line such as high pressure services etc. because calculated pipe inside
diameter is sometime smaller than Lhul of die scheduled pipe,
2.6.6 Definition
(1) Safety Valve :
An automatic pressure relieving device actuated by the static pressure upstream of the
valve, and characterized by rapid full opening ar pop action.
Page 19 of 39
(2) Retief Valve
An automatic pressure relieving device actuated by tiie static pressure upstream of the
valve, which opens in proportion to the increase in pressure over the opening
pressure.
(7) Over-pressure
A pressure increase over the set pressure
(8) Accumulation
A pressure increase over the maximum allowable working pressure
(9) Blowdown
Difference between stiual popping pressure and actual re-scaling pressure
3 INSTRUMENTATION AUXILIARIES
Page 20 of 29
UPS comply to the power quality requirements shown above and normally provided
with 50 minutes back-up batten1 capacity.
3.2 Grounding
3-2-1 General
Instrument power supply, equipment and signal ground should not be interconnected.
33.2 Capacity*
1) Sizing by normal air consumption rate :
A ir consumption rate 14 Nl/min.
System capacity’ 2x14 Nl/min. x No. of pilots
Page 21 of 29
3,3.3 Distribution
The size of header shall be determined in accordance with the following table.
Number of Air Pilots Piping Size (in,)
1 1/4
4 1/2
10 3/4
25 1
80 1-1/2
150 2
300 3
Note If A> fl R and JlC are also used for classification of electrical equipments which
Page 22 of 29
are associated with flame proof or intrinsic safety design.
Note : The same Ls also used for classification of maximum surface temperatures of
electrical equipment,
Principle i Any flame paths from the inside to outside are dimensioned to cool any
products of an internal explosion to a level which can not ignite the Specific outside
flammable environment.
Principle : Electrical apparatus and its associated wiring which is located in the hazardous
area has insufficient electrical or thermal energy under normal of ahnonnaJ condition 1o ignite
the specific hazardous atmospheric mixture.
“Simple Apparatus" is defined ns an apparatus which does not generate power exceeding 1.2
Vu 100mA, 25 mW or 20 p. J, such as thermocouples- RID, Contact terminal strips, junction
boxes, etc. They arc not required to be certified and connected to the intrinsic safety loops
without approvals.
Principle :
Payt 23 of 29
NouinccndirvE circuits may contain components which spark under normal operation,
but The energy released by such components limited in normal operation io values
incapable of causing ignition.
Example 2: Ex c 11 T3
increased safety equipment designed for use in explosive atmosphere
and equipment surface temperature is limited to 200 C.
Example 3 : ExdHBT4
Flame proof equipment designed for use in (he gases classified SIB
and equipment surface temperature is limited to 135 C.
Note I : LA, I IB and IIC used in the equipment labeling arc classification of
hardware design of i ntrinsic safety and flameproof equi pment (but not far
eus grouping).
4.2.1 Nube
(]) Common mode noise :
Unwanted voltages between the signal line and ground.
24 of 29
circuit.
Page 25 of 29
It is recommeiKied that all spare conductors in a multi-conductor cable be grounded
so that they do not induce large voltage surges on signal circuits when nearly
lightning strikes occur.
4.4.1 General
Seal and Purge : to prevent the process fluid from entering the instrument line,
Heating to prevent formation of ice, solidification and undesirable
condensation.
4.4.2 Seal
Diaphragm seals: Diaphragm seal with or without capillary instruments
Check charauterisctcs of filled liquids to ensure proper
operation against process fluid temperature and lowest
ambient temperature.
4-4.3 Purge
Application solid-bearing stream
stream subject to choking or solidification
currostve fluid
4.44 Healing
(1) Steam heating
Type Heavy tracing (tracer contacts instrument lines)
Light tracing (keep space between tracer and lines by
insulators)
Hook-up
a) Tracing should slope downward continuously
b) Provide shut-olT valve for each tracer.
c) Provide individual trap and condensate isolation valve for each tracer.
d) Joint of tracing tubing should be avoided. Where necessary,, they should be
made outside the insulation with expansion loops to prevent slress on the
fitting.
Page 26 of 29
Important : If pockets exist in the tracing line, total stun of height of pockets is
limited by Total height of pockets (cm) /1 CKte Steam header press (kgtanlg)
Type Description
Type 1 Crcneral Purpose - Indoor
Type 2 Drip - proof - Indoor
Type 3 Dust ■ tight. Rain - tight and Sleet (Ice) - resist - Outdoor
Type 3R Rain - proof and Sleet (Ice) - resistant - Outdoor
Type 38 Dust - tight, Rain - tight and Sleet (Ice) - proof-Outdoor
Type 4 Waler - tight and Dust - tight - Indoor and Outdoor
Type 4X Water - tight Dust - tight and Corrasion resistant - Indoor and Outdoor
Type 5 - Superseded by Type 12 for contra 1 apparatus -
Type 6 Submersible, Waler - tight, Dust - tight and Stect (Ice) - resistant - Indoor and
Outdoor
Type 7 Class I. Group A, B, C or D - Indoor Hazardous Locations, Air Break Equipment
Types Class 1. Group A. B, C or D - Indoor Hazardous Locations, Oil ■ immersed
Type 9 Class IL Group E, F or G - Indoor Hazardous Locations, Air Break Equipment
Type 10 Bureau of Mines
Type 11 Corrosion - resistant and Drip - proof Oil - immersed - Indoor Equipment
Type 12 Industrial use, Dust - tight and Drip - light - [nrkior
Type 13 Oil ■ tight and Dust - tight - Indoor
Page 27 of 29
Wind-blow dust yes yes yes yes yes
Hose-down - yes yes yes
Corrosive agents — ■ yes -
Occasional sutnuerstun - - - yes
54 Alarms
Nate : First-out and sequence of events are usually implemented by dedicated alarm
systems, because integrated systems may not be capable of providing the
required! time discrimination for a true sequence of Events.
Emergency systems shall mean those required far initiating automatically such action
as valve closure, to prevent or reduce further operation upset.
5.24 System
(1) Hard-wired logic systems
(2) Solid state logic systems
(PLC with redundant nr fault tolerant controller configuration)
5.2.3 Testing (provisions for checking of Emergency system during plant operation)
(1) Shut-off valves with bypass by c ar-sealed close valves
(2) Electrical bypass switches for motor control circuit
(3) Electrical bypass switches for sensors
PiLjie 2K Lif 2V
Paj-c 39 ul’24